Mitsumi electronic LGH-F1200RX3-E, LGH-F300RX3-E, LGH-F470RX3-E, LGH-F600RX3-E User Manual

Page 1
0509873HC9203
Lossnay
Models:
LGH-F300RX3-E LGH-F470RX
3-E
LGH-F600RX3-E LGH-F1200RX3-E
Operating Instructions (For the user)
Please read through these instructions in order to familiarize yourself with the proper and safe procedures for operat­ing the Lossnay. After reading this manual, keep it in an easily accessible and safe place for future reference.
Safety precautions
The following signs indicate that death or serious injury may be caused by a failure to heed the precautions described below and the resultant mishandling of the product.
English
WARNING
This product must not be disassembled under any circumstances. Only authorized repair technicians are qualified to conduct
No
disassembly
Prohibited
Do not touch
Instructions
must be followed
disassembly and repairs. (Failure to heed this warning may result in fire, electrical shock or injury.) If your product needs to be repaired, consult your dealer.
Do not splash water over this product. (Failure to heed this warning may result in fire and/or electrical shock.)
If flammable gases should leak, do not turn the Lossnay’s switch on or off. (Failure to heed this warning may cause the electrical contacts to generate sparks which may result in an explosion.) Open windows to ventilate.
Do not poke your fingers or sticks into the air intake and outlet while the product is operating. (Failure to heed this warning may result in injury.)
Gloves should be worn when doing the installation and maintenance work. (Failure to heed this warning may result in injury.)
Be sure that the power board circuit breaker is in the OFF position and is securely locked by lock and key before proceeding with maintenance work. (Failure to heed this warning may result in electrical shock or injury.)
In the event of trouble (smell of burning, etc.), shut down operation, set the power board circuit breaker to its OFF position and consult your dealer. (Continued operation without remedying the trouble may result in electrical shock, fire, etc.)
Names of the parts
Models LGH-F300, F470, F600RX3-E Model LGH-F1200RX3-E
1 Maintenance cover
2 Control box 4 Air supply fan
5 Lossnay core
6 Air exhaust fan
3 Lossnay core holder
7 Air filter
8 Damper plate
1 Maintenance cover
2 Control box
7 Air filter5 Lossnay core
3 Lossnay core holder
4 Air supply fan
8 Damper plate8 Air exhaust fan
1
Page 2
Operation
1. For connection of a remote controller (PZ-41SLB-E)
If the Lossnays operation is linked with the operation of an external device such as an air conditioner, the method of use will differ, so carry out the appropriate operation in accordance with the following table. Also, please see the installation and users manual for the remote controller (PZ-41SLB-E).
<If not connected to an external device>
Example of System Function
Lossnay
Remote Controller
(Optional parts)
Power Supply
(PZ-41SLB-E)
<If connected to an external device>
Remote Controller
Lossnay
Lossnay
Power Supply
Power Supply
External device
External device
(Optional parts)
(PZ-41SLB-E)
Power Supply
Operation switch for the external device
Power Supply
Operation switch for the external device
Operation
Run using the remote controller.
If an external device is connected the “On/Off” function of this device will also control the Lossnay operation.
If 2 remote controllers are used, the last controller to be used has priority. (Last Command)
If you would like to turn ON the Lossnay alone while the external device is OFF, operate it by the Lossnay remote control­ler.
The fan speed is on High.
The ventilation mode is Ventilation Mode Auto Select.
2. For connection of a Mitsubishi Electric Air-Conditioner Network System (MELANS) or City Multi.
This is to be incorporated and used in the Mitsubishi Electric Air­Conditioner Network System. This is interlocked with the City Multi and operated by it.
Note
• Remote controller PZ-41SLB-E cannot be used with this sys­tem.
System diagram
Interlocked to the City Multi indoor unit
City Multi indoor unit
A/Cs remote controller
M-NET transmission line
Lossnay unit
3-E
LGH-**RX
Power supply
LOSSNAY VENTILATE setting
Both fresh air supply and return air pass through the Lossnay core(s). Resulting in full heat exchange. Lossnay ventilate setting is used for cooling in the summer and heating in the winter period.
Models LGH-F300, F470, F600RX3-E Model LGH-F1200RX3-E
Damper
Return air
Supply air
Exhaust air
Fresh air
Lossnay core
Damper
Return air
Supply air
Exhaust air
Fresh air
Lossnay core
BY-PASS VENTILATE setting
The fresh air passes through the Lossnay core(s) and the return room air is exhausted direct. Lossnay bypass ventilate is normally operated during the spring/autumn months.
Models LGH-F300, F470, F600RX3-E Model LGH-F1200RX3-E
Exhaust air
Fresh air
Lossnay core
Damper
Return air
Supply air
Exhaust air Fresh air
Lossnay core
Damper
Return air
Supply air
AUTOMATIC VENTILATION setting
The automatic damper mode automatically provides the correct ven­tilation for the conditions in the room. The following shows the effect By-pass ventilation will have under various conditions.
2
Page 3
Operation (Continued)
English
1. Reduces cooling load
If the air outside is cooler than the air inside the building during the cooling season (such as early morning or at night), By-pass ventilation will draw in the cooler outside air and reduce the cool­ing load on the system.
2. Night purge
By-pass ventilation can be used to release hot air from inside the building that has accumulated in buildings a business district during the hot summer season.
Maintenance
Remove all dust and dirt on air filters and Lossnay core(s) at regular intervals in order to prevent a deterioration in the Lossnay functions. Guideline: Clean the air filters once a year.
Clean the Lossnay core(s) once two year.
Removing the parts
1) Maintenance cover
Locate and remove the cover fixing screw. Pull back the hinged clip. Open the door and lift off of the hinge brackets.
Hinge bracket
Maintenance cover
Hinge bracket
Maintenance covers
3. Office equipment room cooling
During cold season, outdoor air can be drawn in and used as is to cool rooms where the temperature has risen due to the use of office equipment. (Only when interlocked with City Multi and Mr. Slim indoor unit)
Velcro
Lossnay core
Air filters
Hinge
Hinge
Models LGH-F300, F470, F600RX3-E Model LGH-F1200RX3-E
2) Lossnay core(s)
Take hold of the handle and draw the Lossnay cores out from the main unit.
Model LGH-F300, F470, F600RX3-E: ....................... 2 cores
Models LGH-F1200RX3-E: ....................................... 4 cores
Handle
Lossnay core
Main unit
Models LGH-F300, F470, F600RX3-E Model LGH-F1200RX3-E
Lossnay
core
Handle
Cleaning the parts
1) Air filters
Use a vacuum cleaner to remove light dust. To remove stubborn dirt wash in a mild solution of detergent and lukewarm water. (under 104°F)
Vacuum cleaner
Air filter
CAUTION
Never wash the filters in very hot water and never wash them by rubbing them.
Do not dry the filters by exposing them to a flame.
2) Lossnay core
Use a vacuum cleaner to suck up the dust and dirt on the exposed surfaces of the Lossnay cores. Use a soft brush only to clean ex­posed surface areas.
Do NOT wash in water.
Lossnay core
3) Air filters
After pulling out the Lossnay core(s), pull the air filters, located at the bottom left and right of the Lossnay core(s), off the velcro that holds them in place.
Model LGH-F300, F470, F600RX3-E: ....................... 4 filters
Models LGH-F1200RX3-E: ....................................... 8 filters
Corner Vacuum cleaner
(with brush attachment)
CAUTION
Do not use the hard nozzle of the vacuum cleaner. It may dam­age the exposed surfaces of the Lossnay core(s).
Under no circumstances should the Lossnay core(s) be washed in water.
3
Page 4
Maintenance (Continued)
Assembly after maintenance
1. Bearing in mind the following points, assemble the parts following the sequence for their removal in reverse.
Align the air filter with the grooves on the Lossnay and holder and
push it in.
When installing the air filters, take care not to damage the exposed
surfaces of the Lossnay cores.
Specifications
Air volume
(CFM)
Model name
LGH-
3
F300RX
LGH­F470RX
LGH­F600RX
-E
3
-E
3
-E
Voltage (V)
1-Phase
208 - 230
1-Phase
208 - 230
1-Phase
208 - 230
Line
frequency
(Hz)
Current (A)
60 1.3 278 300 69 62 44 73
60 2.5 560 470 69 62 44 1430.96 50.539
60 2.9 654 600 69 62 44 159
Power
consumption
(W)
2. Press the filter button on the remote controller (PZ-41SLB-E) two times in succession. (This clears the Lossnays operating time cumulative data.)
Relevant button
(Press twice)
Static
pressure
(in. H2O)
0.65
0.80
FILTER
Excharge efficiency (%)
Temperature
Relevant display items
Enthalpy
Heating Cooling
FILTER
Sound level (dB(A))
Below
the unit
36
39
Air
outlets
44
47
Weight
(Ibs)
LGH­F1200RX
* The values given in the table for the sound level reflect the levels measured at a position 59 inch immediately below the unit in an anechoic
chamber.
* The sound at the air outlets is the values at a 45° angle, 59 inch in front of the unit.
* The above values apply during Lossnay ventilation when the fan speed is set to extra high speed.
* The values are under 230V 60Hz.
3
-E
1-Phase
208 - 230
60 5.7 1290 1200 69 62 44 395
0.75
41
52
After-sales servicing
Consult with your dealer about the after-sales services provided for this Lossnay product.
If you hear strange sounds, if no air is blown out or if some other trouble occurs, switch off the power and contact your dealer. Consult with your dealer concerning the cost of inspection or repair work.
MITSUBISHI ELECTRIC CORPORATION
4