Mitsubishi Heavy Industries SCM60ZM-S, SCM80ZM-S, SCM50ZM-S, SCM71ZM-S, SCM45ZM-S Technical Manual

...
TECHNICAL MANUAL
Manual No.'14•SCM-T-167
INVERTER MULTI-SPLIT SYSTEM RESIDENTIAL AIR-CONDITIONERS
(Split system, air to air heat pump type)
(OUTDOOR UNIT)
SCM40ZM-S
SCM71ZM-S
100ZM-S
125ZM-S
(INDOOR UNIT)
Wall mounted type
SRK20ZMX-S
25ZMX-S 35ZMX-S 50ZMX-S 60ZMX-S
SRK20ZM-S
SRK71ZM-S
Floor standing type SRF25ZMX-S
35ZMX-S 50ZMX-S
4way ceiling cassette type FDTC25VF
35VF 50VF 60VF
Ceiling concealed type SRR25ZJ-S
35ZJ-S 50ZJ-S 60ZJ-S1
Ceiling suspended type FDEN50VF
Duct connected Low/Middle static pressure type FDUM50VF
updated November 27, 2014
-
1
-
'14 • SCM-T-167
CONTENTS
1. SPECIFICATIONS ......................................................................................... 2
2. EXTERIOR DIMENSIONS ............................................................................. 10
3. ELECTRICAL WIRINGS ............................................................................... 15
4. TECHNICAL INFORMATION ..................................................................... 20
(3) Model SCM50ZM-S
(1) Model SCM40ZM-S .............................................................................. 20
.............................................................................. 22
.............................................................................. 24
.............................................................................. 28
.............................................................................. 32
.............................................................................. 38
.............................................................................. 44
(2) Model SCM45ZM-S
(4) Model SCM60ZM-S
(5) Model SCM71ZM-S
(6) Model SCM80ZM-S
(7) Model SCM100ZM-S
Outdoor unit Regarding the outdoor unit
■Table of outdoor unit models
SCM40ZM-S SCM40ZJ-S
SCM45ZJ-S
SCM50ZJ-S1
SCM60ZJ-S1
SCM71ZJ-S1
SCM80ZJ-S1
SCM100ZJ-S1
SCM125ZJ-S1
SCM45ZM-S
SCM50ZM-S
SCM60ZM-S
SCM71ZM-S
SCM80ZM-S
SCM100ZM-S
SCM125ZM-S
This technical manual describes matters related to the outdoor units. For any others and those related to the indoor units, refer to the Technical Manual ’14 • SCM-T-150. For applicable models, refer to the following comparison table.
-
2
-
'14 • SCM-T-167
Model
Item
SCM40ZM-S
Cooling capacity (1) W 4000 (1800 (Min.)−5900 (Max.)) Heating capacity (1) W 4500 (1400 (Min.)−6900 (Max.)) Power source 1 Phase, 220−240 V, 50Hz
Operation data (1)
Power consumption
Cooling
kW
0.84 (0.49−1.90)
Heating 0.90 (0.47−2.30)
Running current
Cooling
A
3.9 / 3.7 / 3.5 (220 / 230 / 240 V)
Heating 4.1 / 4.0 / 3.8 (220 / 230 / 240 V) Inrush current 4.1 / 4.0 / 3.8 (220 / 230 / 240 V) Max current (5) 14
COP
Cooling 4.76
Heating 5.00
Noise level
Cooling
Sound level dB (A) 47
Power level dB 60
Heating
Sound level dB (A) 48
Power level dB 62
Exterior dimensions (Height x Width x Depth) mm 640 x 850 x 290 Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 47
Refrigerant equipment
Compressor type & Q'ty RM-T5113MDE2 (Twin rotary type) x 1 Motor (Starting method) kW 1.4 (Line starting) Refrigerant oil
0.45 (DIAMOND FREEZE MA68) Refrigerant (4) kg R410A 2 (Pre-Charged up to the piping length of 30m) Heat exchanger M fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Propeller fan x 1 Motor W 34
Air flow
Cooling
m
3
/min
40.0
Heating 40.0 Shock & vibration absorber Cushion rubber (for compressor) Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm
Liquid line: φ6.35 (1/4") × 2
Gas line: φ9.52 (3/8") × 2 Connecting method Flare connecting Insulation for piping Necessary (Both sides), independent Length for one indoor unit
m
Max. 25 Total length for all rooms Max. 30 Vertical height difference between
outdoor unit and indoor unit
Max. 15 (Outdoor unit is higher)
Max. 15 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 25
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4 Accessories (included) Installation sheet, Elbow, Grommet
Indoor unit to be combined
SRK20,25,35ZMX(A)-S
SRK20,25,35ZM(A)-S
SRF25,35ZMX(A)-S
SRR25,35ZJ-S
FDTC25,35VF Number of connectable indoor units 2 Total of indoor units kW Max. 6
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO -T1 , J IS C 9 612
Heating 20˚C 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230/240V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 30m connecting piping. (Purging is not required even for the short piping.) (5) Current value at maximum number of indoor units connected.
The pipe length for one indoor unit is 7.5m.
RWC 000 Z28 4
Adapted to RoHS directive
1. SPECIFICATIONS
-
3
-
'14 • SCM-T-167
Model
Item
SCM45ZM-S
Cooling capacity (1) W 4500 (1800 (Min.)−6400 (Max.)) Heating capacity (1) W 5600 (1400 (Min.)−7400 (Max.)) Power source 1 Phase, 220−240 V, 50Hz
Operation data (1)
Power consumption
Cooling
kW
1.04 (0.49−2.14)
Heating 1.20 (0.47−2.57)
Running current
Cooling
A
4.8 / 4.6 / 4.4 (220 / 230 / 240 V)
Heating 5.5 / 5.3 / 5.1 (220 / 230 / 240 V) Inrush current 5.5 / 5.3 / 5.1 (220 / 230 / 240 V) Max current (5) 14
COP
Cooling 4.33
Heating 4.67
Noise level
Cooling
Sound level dB (A) 47
Power level dB 60
Heating
Sound level dB (A) 49
Power level dB 62
Exterior dimensions (Height x Width x Depth) mm 640 x 850 x 290 Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 47
Refrigerant equipment
Compressor type & Q'ty RM-T5113MDE2 (Twin rotary type) x 1 Motor (Starting method) kW 1.4 (Line starting) Refrigerant oil
0.45 (DIAMOND FREEZE MA68) Refrigerant (4) kg R410A 2 (Pre-Charged up to the piping length of 30m) Heat exchanger M fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Propeller fan x 1 Motor W 34
Air flow
Cooling
m
3
/min
40.0
Heating 40.0 Shock & vibration absorber Cushion rubber (for compressor) Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm
Liquid line: φ6.35 (1/4") × 2
Gas line: φ9.52 (3/8") × 2 Connecting method Flare connecting Insulation for piping Necessary (Both sides), independent Length for one indoor unit
m
Max. 25 Total length for all rooms Max. 30 Vertical height difference between
outdoor unit and indoor unit
Max. 15 (Outdoor unit is higher) Max. 15 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 25
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4 Accessories (included) Installation sheet, Elbow, Grommet
Indoor unit to be combined
SRK20,25,35ZMX(A)-S
SRK20,25,35ZM(A)-S
SRF25,35ZMX(A)-S
SRR25,35ZJ-S
FDTC25,35VF Number of connectable indoor units 2 Total of indoor units kW Max. 7
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO -T1 , J IS C 9 612
Heating 20˚C 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230/240V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 30m connecting piping. (Purging is not required even for the short piping.) (5) Current value at maximum number of indoor units connected.
The pipe length for one indoor unit is 7.5m.
Adapted to RoHS directive
RWC 000 Z28 4
-
4
-
'14 • SCM-T-167
Model
Item
SCM50ZM-S
Cooling capacity (1) W 5000 (1800 (Min.)−7100 (Max.)) Heating capacity (1) W 6000 (1400 (Min.)−7500 (Max.)) Power source 1 Phase, 220−240 V, 50Hz
Operation data (1)
Power consumption
Cooling
kW
1.08 (0.50−2.15)
Heating 1.31 (0.48−2.58)
Running current
Cooling
A
5.0 / 4.7 / 4.5 (220 / 230 / 240 V)
Heating 6.0 / 5.8 / 5.5 (220 / 230 / 240 V) Inrush current 6.0 / 5.8 / 5.5 (220 / 230 / 240 V) Max current (5) 15
COP
Cooling 4.63
Heating 4.58
Noise level
Cooling
Sound level dB (A) 49
Power level dB 62
Heating
Sound level dB (A) 52
Power level dB 65
Exterior dimensions (Height x Width x Depth) mm 640 x 850 x 290 Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 48
Refrigerant equipment
Compressor type & Q'ty RM-T5113MDE2 (Twin rotary type) x 1 Motor (Starting method) kW 1.4 (Line starting) Refrigerant oil
0.45 (DIAMOND FREEZE MA68) Refrigerant (4) kg R410A 2.5 (Pre-Charged up to the piping length of 40m) Heat exchanger M fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Propeller fan x 1 Motor W 34
Air flow
Cooling
m
3
/min
41.0
Heating 41.0 Shock & vibration absorber Cushion rubber (for compressor) Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm
Liquid line: φ6.35 (1/4") × 3
Gas line: φ9.52 (3/8") × 3 Connecting method Flare connecting Insulation for piping Necessary (Both sides), independent Length for one indoor unit
m
Max. 25 Total length for all rooms Max. 40 Vertical height difference between
outdoor unit and indoor unit
Max. 15 (Outdoor unit is higher)
Max. 15 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 25
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4 Accessories (included) Union : (φ9.52扌φ12.7 ) × 1, Installation sheet, Elbow, Grommet
Indoor unit to be combined
SRK20,25,35,50ZMX(A)-S
SRK20,25,35,50ZM(A)-S
SRF25,35,50ZMX(A)-S
SRR25,35,50ZJ-S
FDTC25,35,50VF
FDEN50VF,FDUM50VF
Number of connectable indoor units Min. 2−Max. 3 Total of indoor units kW Max. 8.5
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO -T1 , J IS C 9 612
Heating 20˚C 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230/240V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 40m connecting piping. (Purging is not required even for the short piping.) (5) Current value at maximum number of indoor units connected.
The pipe length for one indoor unit is 7.5m.
Adapted to RoHS directive
RWC 000 Z28 4
-
5
-
'14 • SCM-T-167
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO -T1 , J IS C 9 612
Heating 20˚C 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230/240V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 40m connecting piping. (Purging is not required even for the short piping.) (5) Current value at maximum number of indoor units connected.
Model
Item
SCM60ZM-S
Cooling capacity (1) W 6000 (1800 (Min.)−7500 (Max.)) Heating capacity (1) W 6800 (1500 (Min.)−7800 (Max.)) Power source 1 Phase, 220−240 V, 50Hz
Operation data (1)
Power consumption
Cooling
kW
1.43 (0.50−2.39)
Heating 1.51 (0.60−3.00)
Running current
Cooling
A
6.8 / 6.5 / 6.2 (220 / 230 / 240 V)
Heating 7.1 / 6.8 / 6.6 (220 / 230 / 240 V) Inrush current 7.1 / 6.8 / 6.6 (220 / 230 / 240 V) Max current (5) 17
COP
Cooling 4.2
Heating 4.5
Noise level
Cooling
Sound level dB(A) 50
Power level dB 63
Heating
Sound level dB(A) 52
Power level dB 65
Exterior dimensions (Height x Width x Depth) mm 640 x 850 x 290 Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 49
Refrigerant equipment
Compressor type & Q'ty RM-T5118MDE2 (Twin rotary type) x 1 Motor (Starting method) kW 1.4 (Line starting) Refrigerant oil
0.675 (DIAMOND FREEZE MA68) Refrigerant (4) kg R410A 2.5 (Pre-Charged up to the piping length of 40m) Heat exchanger M fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Propeller fan x 1 Motor W 34
Air flow
Cooling
m
3
/min
42.0
Heating 42.0 Shock & vibration absorber Cushion rubber (for compressor) Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm
Liquid line:φ6.35 (1/4") × 3
Gas line:φ9.52 (3/8") × 3 Connecting method Flare connecting Insulation for piping Necessary (Both sides), independent Length for one indoor unit
m
Max. 25 Total length for all rooms Max. 40 Vertical height difference between
outdoor unit and indoor unit
Max. 15 (Outdoor unit is higher)
Max. 15 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 25
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4 Accessories (included) Union : (φ9.52扌φ12.7) × 2, Installation sheet, Elbow, Grommet
Indoor unit to be combined
SRK20,25,35,50,60ZMX(A)-S
SRK20,25,35,50ZM(A)-S
SRF25,35,50ZMX(A)-S
SRR25,35,50ZJ-S,60ZJ-S1
FDTC25,35,50,60VF
FDEN50VF,FDUM50VF
Number of connectable indoor units Min. 2−Max. 3 Total of indoor units kW Max. 11
Adapted to RoHS directive
The pipe length for one indoor unit is 7.5m.
RWC 000 Z28 4
-
6
-
'14 • SCM-T-167
Model
Item
SCM71ZM-S
Cooling capacity (1) W 7100 (1800 (Min.)−8800 (Max.)) Heating capacity (1) W 8600 (1500 (Min.)−9400 (Max.)) Power source 1 Phase, 220−240 V, 50Hz
Operation data (1)
Power consumption
Cooling
kW
1.74 (0.48−2.75)
Heating 2.00 (0.60−3.35)
Running current
Cooling
A
8.0 / 7.6 / 7.3 (220 / 230 / 240 V)
Heating 9.2 / 8.8 / 8.4 (220 / 230 / 240 V) Inrush current 9.2 / 8.8 / 8.4 (220 / 230 / 240 V) Max current (5) 20
COP
Cooling 4.08
Heating 4.30
Noise level
Cooling
Sound level dB (A) 52
Power level dB 65
Heating
Sound level dB (A) 54
Power level dB 66
Exterior dimensions (Height x Width x Depth) mm 750 x 880 x 340 Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 62
Refrigerant equipment
Compressor type & Q'ty RM-T5118MDE2 (Twin rotary type) x 1 Motor (Starting method) kW 1.4 (Line starting) Refrigerant oil
0.675 (DIAMOND FREEZE MA68) Refrigerant (4) kg R410A 3.15 (Pre-Charged up to the piping length of 40m) Heat exchanger M fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Propeller fan x 1 Motor W 86
Air flow
Cooling
m
3
/min
56.0
Heating 56.0 Shock & vibration absorber Cushion rubber (for compressor) Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm
Liquid line: φ6.35 (1/4") × 4
Gas line: φ9.52 (3/8") × 4 Connecting method Flare connecting Insulation for piping Necessary (Both sides), independent Length for one indoor unit
m
Max. 25 Total length for all rooms Max. 70 Vertical height difference between
outdoor unit and indoor unit
Max. 20 (Outdoor unit is higher) Max. 20 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 25
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4 Accessories (included) Union : (φ9.52扌φ12.7) × 2, Installation sheet, Elbow, Grommet × 2
Indoor unit to be combined
SRK20,25,35,50,60ZMX(A)-S
SRK20,25,35,50ZM(A)-S
SRF25,35,50ZMX(A)-S
SRR25,35,50ZJ-S,60ZJ-S1
FDTC25,35,50,60VF
FDEN50VF,FDUM50VF
Number of connectable indoor units Min. 2−Max. 4 Total of indoor units kW Max. 12.5
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO -T1 , J IS C 9 612
Heating 20˚C 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230/240V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 40m connecting piping. (Purging is not required even for the short piping.) (5) Current value at maximum number of indoor units connected.
The pipe length for one indoor unit is 7.5m.
Adapted to RoHS directive
RWC 000 Z28 4
-
7
-
'14 • SCM-T-167
Model
Item
SCM80ZM-S
Cooling capacity (1) W 8000 (1800 (Min.)−9200 (Max.)) Heating capacity (1) W 9300 (1500 (Min.)−9800 (Max.)) Power source 1 Phase, 220−240 V, 50Hz
Operation data (1)
Power consumption
Cooling
kW
2.16 (0.48−2.83)
Heating 2.26 (0.60−3.43)
Running current
Cooling
A
9.9 / 9.4 / 9.0 (220 / 230 / 240 V)
Heating 10.4 / 10.0 / 9.5 (220 / 230 / 240 V) Inrush current 10.4 / 10.0 / 9.5 (220 / 230 / 240 V) Max current (5) 20
COP
Cooling 3.70
Heating 4.12
Noise level
Cooling
Sound level dB(A) 54
Power level dB 66
Heating
Sound level dB(A) 54
Power level dB 66
Exterior dimensions (Height x Width x Depth) mm 750 x 880 x 340 Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 62
Refrigerant equipment
Compressor type & Q'ty RM-T5118MDE2 (Twin rotary type) x 1 Motor (Starting method) kW 1.4 (Line starting) Refrigerant oil
0.675 (DIAMOND FREEZE MA68) Refrigerant (4) kg R410A 3.15 (Pre-Charged up to the piping length of 40m) Heat exchanger M fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Propeller fan x 1 Motor W 86
Air flow
Cooling
m
3
/min
56.0
Heating 56.0 Shock & vibration absorber Cushion rubber (for compressor) Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm
Liquid line:φ6.35 (1/4") × 4
Gas line:φ9.52 ( 3/8") × 4 Connecting method Flare connecting Insulation for piping Necessary (Both sides), independent Length for one indoor unit
m
Max. 25 Total length for all rooms Max. 70 Vertical height difference between
outdoor unit and indoor unit
Max. 20 (Outdoor unit is higher)
Max. 20 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 25
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4 Accessories (included) Union : (φ9.52扌φ12.7) × 2, Installation sheet, Elbow, Grommet × 2
Indoor unit to be combined
SRK20,25,35,50,60ZMX(A)-S
SRK20,25,35,50ZM(A)-S
SRF25,35,50ZMX(A)-S
SRR25,35,50ZJ-S,60ZJ-S1
FDTC25,35,50,60VF
FDEN50VF,FDUM50VF
Number of connectable indoor units Min. 2−Max. 4 Total of indoor units kW Max. 13.5
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO -T1 , J IS C 9 612
Heating 20˚C 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230/240V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 40m connecting piping. (Purging is not required even for the short piping.) (5) Current value at maximum number of indoor units connected.
The pipe length for one indoor unit is 7.5m.
Adapted to RoHS directive
RWC 000 Z28 4
-
8
-
'14 • SCM-T-167
Model
Item
SCM100ZM-S
Cooling capacity (1) W 10000 (1800 (Min.)−12000 (Max.)) Heating capacity (1) W 12000 (1500 (Min.)−13500 (Max.)) Power source 1 Phase, 220−240 V, 50Hz
Operation data (1)
Power consumption
Cooling
kW
2.86 (0.65−4.03)
Heating 2.93 (0.70−3.40)
Running current
Cooling
A
13.0 / 12.4 / 11.9 (220 / 230 / 240 V)
Heating 13.3 / 12.8 / 12.2 (220 / 230 / 240 V) Inrush current 13.3 / 12.8 / 12.2 (220 / 230 / 240 V) Max current (6) 28
COP
Cooling 3.50
Heating 4.10
Noise level
Cooling
Sound level dB (A) 56
Power level dB 68
Heating
Sound level dB (A) 59
Power level dB 71
Exterior dimensions (Height x Width x Depth) mm 945 x 970 x 370 Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 92
Refrigerant equipment
Compressor type & Q'ty RM-T5126MDE21 (Twin rotary type) x 1 Motor (Starting method) kW 4.0 (Line starting) Refrigerant oil
1.0 (DIAMOND FREEZE MA68) Refrigerant (4) kg R410A 6.00 (Pre-Charged up to the piping length of 50m) Heat exchanger M fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Propeller fan x 1 Motor W 86
Air flow
Cooling
m
3
/min
75.0
Heating 75.0 Shock & vibration absorber Cushion rubber (for compressor) Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm
Liquid line: φ6.35 (1/4") × 5
Gas line: φ9.52 (3/8") × 5 Connecting method Flare connecting Insulation for piping Necessary (Both sides), independent Length for one indoor unit
m
Max. 25 Total length for all rooms Max. 90 Vertical height difference between
outdoor unit and indoor unit
Max. 20 (Outdoor unit is higher)
Max. 20 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 30
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4 Accessories (included) Union, Installation sheet, Elbow, Grommet × 2
Indoor unit to be combined
SRK20,25,35,50,60ZMX(A)-S,SRK20,25,35,50,71ZM(A)-S
SRF25,35,50ZMX(A)-S
SRR25,35,50ZJ-S,60ZJ-S1
FDTC25,35,50,60VF
FDEN50VF,FDUM50VF Number of connectable indoor units Min. 2−Max. 5 (5) Total of indoor units kW Max. 16.0
Note (1) The data are measured at the following conditions.
Item
Operation
Indoorairtemperature Outdoorairtemperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO-T1,JISC 961 2
Heating 20˚C 7 ˚C 6˚C
(2)Thisair-conditionerismanufacturedandtestedinconformitywiththeISO. (3)Theoperationdataareappliedtothe220/230/240Vdistrictsrespectively. (4)Therefrigerantquantitytobechargedincludestherefrigerantin50mconnectingpiping. (Purgingisnotrequiredevenfortheshortpiping.) (5)IncaseofcombinationwithSRK-ZMX-S,SRK71ZM-S,FDEN50VFonly3indoorunitscanbeconnectable. IncaseofSRK71ZM-S+SRK71ZM-S,2indoorunitscanbeconnectable. (6)Currentvalueatmaximumnumberofindoorunitsconnected.
Thepipelengthforoneindoorunitis7.5m.
AdaptedtoRoHS directive
RWC 000 Z28 4
#
-
9
-
'14 • SCM-T-167
Model
Item
SCM125ZM-S
Cooling capacity (1) W 12500 (1800 (Min.)−14000 (Max.)) Heating capacity (1) W 13500 (1500 (Min.)−14000 (Max.)) Power source 1 Phase, 220−240 V, 50Hz
Operation data (1)
Power consumption
Cooling
kW
3.90 (0.65−4.80)
Heating 3.25 (0.70−3.42)
Running current
Cooling
A
17.7 / 17.0 / 16.3 (220 / 230 / 240 V)
Heating 14.8 / 14.1 / 13.6 (220 / 230 / 240 V) Inrush current 17.7 / 17.0 / 16.3 (220 / 230 / 240 V) Max current (6) 29
COP
Cooling 3.21
Heating 4.15
Noise level
Cooling
Sound level dB (A) 57
Power level dB 69
Heating
Sound level dB (A) 60
Power level dB 72
Exterior dimensions (Height x Width x Depth) mm 945 x 970 x 370 Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 92
Refrigerant equipment
Compressor type & Q'ty RM-T5126MDE21 (Twin rotary type) x 1 Motor (Starting method) kW 4.0 (Line starting) Refrigerant oil
1.0 (DIAMOND FREEZE MA68) Refrigerant (4) kg R410A 6.00 (Pre-Charged up to the piping length of 50m) Heat exchanger M fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Propeller fan x 1 Motor W 86
Air flow
Cooling
m
3
/min
75.0
Heating 82.0 Shock & vibration absorber Cushion rubber (for compressor) Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm
Liquid line: φ6.35 (1/4") × 6
Gas line: φ9.52 (3/8") × 6 Connecting method Flare connecting Insulation for piping Necessary (Both sides), independent Length for one indoor unit
m
Max. 25 Total length for all rooms Max. 90 Vertical height difference between
outdoor unit and indoor unit
Max. 20 (Outdoor unit is higher)
Max. 20 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 30
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4 Accessories (included) Union, Installation sheet, Elbow, Grommet × 2
Indoor unit to be combined
SRK20,25,35,50,60ZMX(A)-S,SRK20,25,35,50,71ZM(A)-S
SRF25,35,50ZMX(A)-S
SRR25,35,50ZJ-S,60ZJ-S1
FDTC25,35,50,60VF
FDEN50VF,FDUM50VF Number of connectable indoor units Min. 2−Max. 6 (5) Total of indoor units kW Max. 19.5
Note (1) The data are measured at the following conditions.
Item
Operation
Indoorairtemperature Outdoorairtemperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO-T1,JISC 961 2
Heating 20˚C 7 ˚C 6˚C
(2)Thisair-conditionerismanufacturedandtestedinconformitywiththeISO. (3)Theoperationdataareappliedtothe220/230/240Vdistrictsrespectively. (4)Therefrigerantquantitytobechargedincludestherefrigerantin50mconnectingpiping. (Purgingisnotrequiredevenfortheshortpiping.) (5)IncaseofcombinationwithSRK-ZMX-S,SRK71ZM-S,FDEN50VFonly,3indoorunitscanbeconnectable. IncaseofSRK71ZM-S+SRK71ZM-S,2indoorunitscanbeconnectable. (6)Currentvalueatmaximumnumberofindoorunitsconnected.
Thepipelengthforoneindoorunitis7.5m.
AdaptedtoRoHS directive
RWC 000 Z28 4
#
-
10
-
'14 • SCM-T-167
2. EXTERIOR DIMENSIONS
Models SCM40ZM-S, 45ZM-S
Unit:mm
43.5
286.4
49.6
290
476
203.1 510 136.9
14 312.5
50
12
13.5
340
640
15
850
100.3 42.7
124.1 34.6
2-16x12
211 42.7
20°
20°
20°
20°
103.2
385.9
14.6
17.9
65
Symbol Content
A Service valve connection(gas side) φ9.52(3/8")(Flare) B Service valve connection(liquid side) φ6.35(1/4")(Flare) C Pipecable draw-out hole D Drain discharge hole φ20 x 3 places E Anchor bolt hole M10 x 4 places
Service panel
Terminal block
L1
L3
Intake
No obstacles
Service space
L2
Intake
Outlet
Note
1It must not be surrounded by walls on four sides.2The unit must be fixed with anchor bolts. An anchor bolt
must not protrude more than 15mm.
3Where the unit is subjected to strong winds, lay it in such a
direction that the blower outlet faces perpendicularly to the dominant wind direction.
4Leave 1.2m or more space above the unit.5A wall in front of the blower outlet must not exceed the
unit's height.
6The model name label is attached on the service panel.
100
600 L2 L3
L1
Examples of
100
Installation
Dimensions
Minimum installation space
for electrical parts
D
B
A
C
E
RW C0 00 Z28 0
-
11
-
'14 • SCM-T-167
Models SCM50ZM-S, 60ZM-S
Unit:mm
43.5
286.4
49.6
136.9
14 312.5
50
12
13.5
340
640
15
100.3 42.7
124.1 34.6
211 42.7
20°
20°
20°
20°
321.7 42.7
20°
20°
290
476
203.1 510 850
103.2
385.9
14.6
2-16x12
17.9
65
Symbol Content
A Service valve connection(gas side)
φ
9.52(3/8")(Flare)
B Service valve connection(liquid side)
φ
6.35(1/4")(Flare)
C Pipecable draw-out hole D Drain discharge hole
φ
20 x 3 places
E Anchor bolt hole M10 x 4 places
Service panel
Terminal block
L1
L3
Intake
L2
Intake
Outlet
Note
1It must not be surrounded by walls on four sides.2The unit must be fixed with anchor bolts. An anchor bolt
must not protrude more than 15mm.
3Where the unit is subjected to strong winds, lay it in such a
direction that the blower outlet faces perpendicularly to the dominant wind direction.
4Leave 1.2m or more space above the unit.5A wall in front of the blower outlet must not exceed the
unit's height.
6The model name label is attached on the service panel.
100
600 L2 L3
L1
Examples of
100
Installation
Dimensions
Minimum installation space
No obstacles
Service space
for electrical parts
D
B
A
C
E
RW C0 00 Z28 1
-
12
-
'14 • SCM-T-167
Models SCM71ZM-S, 80ZM-S
Unit:mm
L1
L3
Intake
L2
Intake
Outlet
Notes
1It must not be surrounded by walls on four sides.2The unit must be fixed with anchor bolts. An anchor bolt
must not protrude more than 15mm.
3Where the unit is subjected to strong winds, lay it in such a
direction that the blower outlet faces perpendicularly to the dominant wind direction.
4Leave 1.2m or more space above the unit.5A wall in front of the blower outlet must not exceed the
unit's height.
6The model name label is attached on the rear panel.
100
600 L2 L3
L1
Examples of
100
Installation
Dimensions
Minimum installation space
Terminal block
Symbol Content
A Service valve connection(gas side) φ9.52(3/8")(Flare) B Service valve connection(liquid side) φ6.35(1/4")(Flare) C Pipecable draw-out hole D Drain discharge hole φ20 x 3 places E Anchor bolt hole M10 x 4 places
No obstacles
Service space
for electrical parts
15
60
38019
418
73880
150 580 150 26
340
2-R7.5
223
47.5
310
61
61
110.4 52 185 10
24
750
214.4 52
318.4 52
422.4 52
20
D
C
E
B
A
RW C0 00 Z27 7
-
13
-
'14 • SCM-T-167
Model SCM100ZM-S
L1
L3
Intake
Outlet
Intake
Minimum installation space
space
Service
Notes
1 It must not be surrounded by walls on the four sides.2The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
3 Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicularly to the dominant wind direction.
4 Leave 1m or more space above the unit.5 A wall in front of the blower outlet must not exceed the units height.6The model name label is attached on the rear panel.
φ
9.52(3/8")(Flare)
Content
C Pipecable draw-out hole D E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(gas side
M10×4places
φ
20×3places
Service valve connection(liquid side)
φ
6.35(1/4")(Flare)
L2 L3
L1
300 150
Open
Open
150
500
Open
300
5
Unit:mm
Examples of
Dimensions
installation
L2
No obstacles
Service space
for electrical parts
580
76
190
60
55
20
200
262.8 325
945
410
40370
40
20
52115.2
219.2 52
52
52
52531.2
427.2
323.2
26
970
10170
15
15
580
177
393
10
73
Terminal block
Center of gravity
Center of gravity
Rear panel
B
A
C
E
D
RW C0 00 Z27 8
-
14
-
'14 • SCM-T-167
Model SCM125ZM-S
RW C0 00 Z27 9
B
A
C
E
D
L1
L3
Intake
Outlet
Intake
Minimum installation space
space
Service
Notes
1 It must not be surrounded by walls on the four sides.2The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
3 Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicularly to the dominant wind direction.
4 Leave 1m or more space above the unit.5 A wall in front of the blower outlet must not exceed the units height.6The model name label is attached on the rear panel.
φ
9.52(3/8")(Flare)
Content
C Pipecable draw-out hole D E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(gas side
M10×4places
φ
20×3places
Service valve connection(liquid side)
φ
6.35(1/4")(Flare)
L2 L3
L1
300 150
Open
Open
150
500
Open
300
5
Unit:mm
Examples of
Dimensions
installation
L2
No obstacles
Service space
for electrical parts
580
76
190
60
55
20
200
262.8 325
945
410
40370
40
20
52115.2
219.2 52
52
52
52531.2
427.2
323.2
26
970
10170
15
52635.2
15
580
177
393
10
73
Terminal block
Center of gravity
Center of gravity
Rear panel
-
15
-
'14 • SCM-T-167
3. ELECTRICAL WIRINGS
Models SCM40ZM-S, 45ZM-S
Color Marks
Mark Color Mark Color Item
Meaning of Marks
Description Item Description
BKBRBlack
Brown
RD YGRed YellowGreen WH White
OR Orange
CNA-CN20S
EEV A,EEV B
R
Compressor motor Electric expansion valve coil
Reactor
Tho-A Tho-D
Heat exchanger sensor
Outdoor air temp. sensor Discharge pipe temp. sensor
CM
Tho-R
Connector
20S 4 Way valvecoil
Suction pipe temp. sensor
Tho-S
FMo Fan motor
Terminal blockTB1-TB3
outdoor unit
HEATER Crank case heater
FunctionColorIndication lamp
Warning lampRedLED e 1
Self diagnosis function by led e
1-Time flash Current cut
2-Time flash Trouble of outdoor unit
3-Time flash Over current
4-Time flash Transmission error
5-Time flash Over heat of compressor
6-Time flash Error of signal transmission
7-Time flash Lock of compressor
8-Time flash Sensor error
Except discharge pipe sensor
Four sec light
and Discharge pipe sensor error
four sec off
Caution When the compressor does not run Immediately after hitting on the button,wait for 5 to 10 minutes.There is possibility of delayed start.
High voltage is produced in the control box. don't touch
electrical parts in the control box for 5 minutes after
cutting power source.
Light on Outdoor fan motor error
EEV
S
BK
WH
RD
V
W
U
FM0
CM
R
CNTH
CNFAN
S-2
BK
WH
WH
S-1
CNSUB
CNMAIN
S
R
BK
WH
IN
IN
S
R
O
O
250V 15A
FUSE
CN20S
G2
YG
C-2
RD
C-1
CN20V
CN20V
5
2
G1
YG
G
YG
CNEEV1
CNTH
TB2
CNA
CNB
TB1
N
L
A
EEV
B
YG
WH
BK
UNIT A
UNIT B
M
3
M
M
M
Power source 1 Phase AC 220−240V 50Hz
WH
RD
PCB 2SUB
PCB 1MAIN
20S
HEATER
WH
RD
CNHEAT
T2
T1
R
OR
YE
3
2
1
BK WH RD
3
2
1
BK WH BR
TB3
2 2 2
t
t
t
t
2
Tho-S
Tho-R Tho-A Tho-D
YE Yellow
A
RWC000Z2 32
-
16
-
'14 • SCM-T-167
Models SCM50ZM-S, 60ZM-S
Color Marks
Mark Color Mark Color Item
Meaning of Marks
Description Item Description BK BRBlack Brown BL YEBlue Yellow RD YGRed YellowGreen WH White
OR Orange
EEV
S
BK
WH
RD
V
W
U
FMo
CM
R
CNTH
CNFAN
S-2
BK
WH
WH
S-1
CNSUB
CNMAIN
S
R
BK
WH
IN
IN
S
R
O
O
250V 15A
FUSE
CN20S
G2
YG
C-2
RD
C-1
CN20V
CN20V
5
2
G1
YG
G
YG
CNEEV1
CNEEV3
CNTH
TB2
CNA
CNB
CNC
TB1
N
L
A
EEVBEEV
C
YG
WH
BK
UNIT A
UNIT B
UNIT C
M
3
M
M
M
M
WH
RD BL
PCB 2SUB
PCB 1MAIN
20S
HEATER
WH
RD
CNHEAT
T2
T1
R
OR
YE
250V 20A
3
2
1
BK
WH
RD
3
2
1
3
2
1
BK
WH
BR
BK
WH
BL
2 2 2
t
t
t
t
2
Tho-S
Tho-R Tho-A Tho-D
CNA-CN20S
EEV A,EEV B
EEV C
R
Compressor motor Electric expansion valve coil
Reactor
Tho-A Tho-D
Heat exchanger sensor
Outdoor air temp. sensor Discharge pipe temp. sensor
CM
Tho-R
Connector
20S 4 Way valvecoil
Suction pipe temp. sensor
Tho-S
FMo Fan motor
Terminal blockTB1,TB2
outdoor unit
HEATER Crank case heater
FunctionColorIndication lamp
Warning lampRedLED e 1
Self diagnosis function by led e
1-Time flash Current cut
2-Time flash Trouble of outdoor unit
3-Time flash Over current
4-Time flash Transmission error
5-Time flash Over heat of compressor
6-Time flash Error of signal transmission
7-Time flash Lock of compressor
8-Time flash Sensor error
Except discharge pipe sensor
Four sec light
and Discharge pipe sensor error
four sec off
Caution When the compressor does not run Immediately after hitting on the button,wait for 5 to 10 minutes.There is possibility of delayed start.
High voltage is produced in the control box. don't touch
electrical parts in the control box for 5 minutes after
cutting power source.
Light on Outdoor fan motor error
Power source 1 Phase AC 220−240V 50Hz
B
RWC 000 Z25 2
-
17
-
'14 • SCM-T-167
Models SCM71ZM-S, 80ZM-S
Color Marks
Mark Color Mark Color Item
Meaning of Marks
Description Item Description BK RDBlack Red BL WHBlue White BR Brown Yellow GN Green
OR Orange
FunctionColorIndication lamp
Warning lampRedLED e 1
Self diagnosis function by led e
1-Time flash Current cut
2-Time flash Trouble of outdoor unit
3-Time flash Over current
4-Time flash Transmission error
5-Time flash Over heat of compressor
6-Time flash Error of signal transmission
7-Time flash Lock of compressor
8-Time flash Sensor error
Except discharge pipe sensor
Four sec light
and Discharge pipe sensor error
four sec off
Caution When the compressor does not run Immediately after hitting on the button,wait for 5 to 10 minutes. There is possibility of delayed start.
High voltage is produced in the control box. don't touch
electrical parts in the control box for 5 minutes after
cutting power source.
CNA-CN20S
EEV A,EEV B EEV C,EEV D
R
Compressor motor Electric expansion valve coil
Reactor
Tho-A
Tho-D
Heat exchanger sensor
Outdoor air temp. sensor Discharge pipe temp. sensor
CM
Tho-R
Connector
20S 4 Way valvecoil
Suction pipe temp. sensor
Tho-S
FMo Fan motor
Terminal blockTB15
outdoor unit
YG YellowGreen
Light on Outdoor fan motor error
EEV
S
BK
WH
RD
V
W
U
FMo
CM
R
CNTH
CNFAN
S-2
BK
WH
WH
S-1
CNSUB
CNMAIN
S
R
BK
WH
IN
IN
S
R
O
O
250V 20A
FUSE
CN20S
2 2 2
G2
YG
C-2
RD
C-1
CN20V
CN20V
5
2
G1
YG
G
YG
CNEEV1
CNEEV2
Tho-S
CNTH
t
2
TB2
CNA
CNB
CNC
CND
TB1
N
L
A
EEVBEEVCEEV
D
TB3
TB4
TB5
3
2
1
3
2
1
3
2
1
3
2
1
YG
WH
BK
BK
WH RD YG
BK WH
BL
YG
BK WH YE
YG
BK WH BR YG
UNIT A
UNIT B
UNIT C
UNIT D
M
3
M
M
M
M
M
YG
WH
RD BL
GN
PCB 2SUB
PCB 1MAIN
t
20S
HEATER
WH
RD
t
t
CNHEAT
T2
T1
R
OR
YE
Tho-R Tho-A Tho-D
YE
HEATER Crank case heater
Power source 1 Phase AC 220−240V 50Hz
B
RWC 000 Z25 0
-
18
-
'14 • SCM-T-167
Model SCM100ZM-S
L
N
RD RD
WH
30A 250V
Y/G
TB3
TB4
TB5
TB6
TB7 TB8
RD
WH
TB3
TB4
TB5
TB6
TB7
RD
WH
2
AC
3
+1
-4
RD
BL
P1
N1
1 2
4 3
P2
N2
RD
BL
+
-
L1 L2
CNACT
P
N2
BK
RD RD
BL
BL
CNACT1
P3
N3
BL
RD
RD
UWHVBLW
U
V
W
MS
3
CNI2
CNI4
CNI1
CNI3
CNA2
CNA1
BL
4
BL
3
4A
250V
Y/G
Y/G
Y/G
RD
WH
RD
WH
L-IN N-IN
CNTRI
CNTRO
CNS2
CNX2
G
WH
RD
BK WH
BK WH
Y/G
CNA
CNB
CNC
CND
CNE
CN
EEV1CNEEV2CNEEV3
4
+
5 5 5 5 5
BK
1 2 3
WH
RD
BK
WH
BR
BK
WH
BL
BK
WH
Y
BK
WH
OR
CNW
CNS1
CNX1
CNTH CNP1
2 2 2 2 2
UNIT A
UNIT B
UNIT C
UNIT D
UNIT E
2
2
5 5 5 55
BLRDWH GN BK
WH
WH
WH
WH
WH
WH) (WH) (WH
Y
BK
WH
WH
BK
Y
BK
WH
GN
WH
WH
CN
EEV1
5
M
RD
M
5
CNL1
BL
CN
FAN1
WH
3
CNR1
WH
2
CNN1
RD
2
Power source 1 Phase AC 220
240V
50Hz
3
BKBKBKYBK
BR
BL
MMMMM
LED1
LED2 LED3
CHECKER PC
CNE CNV
WH
1 2 3
1 2 3
1 2 3
1 2 3
1.Instructions for correct operation
Before you turn on power,please carefully read the installation
  manual and the operation manual supplied with the unit.
Please check the following points before operation.
This unit is designed exclusively for use with R410A. Do not use      any refrigerant other than R410A.
To protect the compressor,turn on power for the air conditioner
  6 hours before operation so as warm up sufficiently the dome   temperature of compressor.
Open the service valves of liquid pipe at first. Secondarily open
  the one of gas pipe. Before you operate the unit,make sure again   that the service valves are in open position.
Please note that the pressure valves detected at the charge port
  in the unit and the gas service valves are different during the   cooling operation and the heating operation. High pressure is   replaced with the low pressure depending on whether it is in the   cooling or heating operation.
2.Error indication
t°t°t°
TB1
PCB5 NOISE
PCB3
CT1
DS
L
AF
PCB2
INV PCB
IPM
30A 600V
CM
F
PCB1
CONTROL PCB
PCB4
SUB PCB
C1
EEV AEEVBEEVCEEVDEEV
E
TB2
TB3
Tho-R
Tho-D
Tho-S
Tho-A
Tho-AF
TR
F
2
FILTER
NOISE FILTER
1
EEV-H
HPS CH 20S
FM
MODULE
CH Crankcase heater
HPS
CM
DS EEV
Compressor motor
Diode stack Electronic expansion coil
EEV-H
Electronic expansion coilFor heating
FM Fan motor
CT Current sensor
High pressure sensor
F Fuse
Tho-A Thermistoroutdoor air temperature
Mark Name
CNA-Z
Tho-D Thermistordischarge pipe Tho-R Thermistorheat exchanger Tho-S Thermistorsuction pipe Tho-AF Ther mistorpower transistor
20S 4-way valve coil
IPM
Intelligent power module
LED1
Indicator lampRed-Inspection indicator
LED2
Indicator lampGreen-Microcomputer normality indicator
LED3 Indicator lampGreen-For service
TR Trance former
TB Terminal block
L Reactor
Connector
A/F MODULE
Active filter module
LED E 1 RED WARNING LAMP
Note(1) used only at our factory.
INDICATION LAMP COLOR FUNCTION
SELF DIAGNOSIS FUNCTION BY LED E 1-TIME FLASH 2-TIME FLASH
CURRENT CUT TROUBLE OF OUTDOOR UNIT
FOUR SEC LIGHT
3-TIME FLASH
5-TIME FLASH 6-TIME FLASH
OVER CURRENT
OVER HEAT OF COMPRESSOR ERROR OF SIGNAL TRANSMISSION
DISCHARGE PIPE SENSOR ERRORAND
FOUR SEC OFF
8-TIME FLASH SENSOR ERROR
EXCEPT DISCHARGE PIPE SENSOR
LIGHT ON OUTDOOR FAN MOTOR ERROR
4-TIME FLASH TRANSMISSION ERROR
Color
RD
Mark
YellowGreen
YG
BlackBK BlueBL BrownBR
YellowY
WhiteWH
Red
OrangeOR PinkPK
GreenGN
A
RWC 000 Z27 6
-
19
-
'14 • SCM-T-167
Model SCM125ZM-S
L
N
RD RD
WH
30A 250V
Y/G
TB3
TB4
TB5
TB6
TB7 TB8
RD
WH
TB3
TB4
TB5
TB6
TB7
RD
WH
2
AC
3
+1
-4
RD
BL
P1
N1
1 2
4 3
P2
N2
RD
BL
+
-
L1 L2
CNACT
P
N2
BK
RD RD
BL BL
CNACT1
P3
N3
BL
RD
RD
UWHVBLW
U
V
W
MS
3
CNI2
CNI4
CNI1
CNI3
CNA2
CNA1
BL
4
BL
3
Y/G
Y/G
Y/G
RD
WH
RD
WH
L-IN N-IN
CNTRI
CNTRO
CNS2
CNX2
G
WH
RD
BK
WH
BK
WH
Y/G
CNA
CNB
CNC
CND
CNE
CNF
CN
EEV1CNEEV2CNEEV3CNEEV4
4
+
5 5 5 5 5 5
BK
1 2 3
WH RD
BK WH BR
BK WH BL
BK WH
Y
BK WH OR
BK WH PK
CNW
CNS1
CNX1
CNTH CNP1
2 2 2 2 2
UNIT A
UNIT B
UNIT C
UNIT D
UNIT E
UNIT F
2
2
5 5 5 5 55
BLRDWH GN BK Y
WH
WH
WH
WH
WH
WH) (WH) (WH)(WH
Y
BK
WH
WH
BK
Y
BK
WH
GN
WH
WH
CN
EEV1
5
M
RD
M
5
CNL1
BL
CN
FAN1
WH
3
CNR1
WH
2
CNN1
RD
2
3
BKBKBKYBK
BR
BL
WH
MMMMMM
LED1
LED2 LED3
CHECKER PC
CNE CNV
WH
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1.Instructions for correct operation
Before you turn on power,please carefully read the installation
  manual and the operation manual supplied with the unit.
Please check the following points before operation.
This unit is designed exclusively for use with R410A. Do not use      any refrigerant other than R410A.
To protect the compressor,turn on power for the air conditioner
  6 hours before operation so as warm up sufficiently the dome   temperature of compressor.
Open the service valves of liquid pipe at first. Secondarily open
  the one of gas pipe. Before you operate the unit,make sure again   that the service valves are in open position.
Please note that the pressure valves detected at the charge port
  in the unit and the gas service valves are different during the   cooling operation and the heating operation. High pressure is   replaced with the low pressure depending on whether it is in the   cooling or heating operation.
2.Error indication
t°t°t°t°t°
TB1
TB2
PCB5
NOISE
PCB3
CT1
DS
L
AF
PCB2
INV PCB
IPM
30A 600V
CM
PCB1
CONTROL PCB
PCB4
SUB PCB
C1
EEVAEEVBEEVCEEVDEEVEEEV
F
Tho-R
Tho-D
Tho-S
Tho-A
Tho-AF
TR
FILTER
NOISE FILTER
F
1
EEV-H
HPS CH 20S
FM
MODULE
TB3
4A
250V
F
2
CH Crankcase heater
HPS
CM
DS EEV
Compressor motor
Diode stack Electronic expansion coil
EEV-H
Electronic expansion coilFor heating
FM Fan motor
CT Current sensor
High pressure sensor
F Fuse
Tho-A
Thermistoroutdoor air temperature
Mark Name
CNA-Z
Tho-D Thermistordischarge pipe Tho-R
Thermistorheat exchanger
Tho-S Thermistorsuction pipe Tho-AF
Thermistorpower transistor
20S 4-way valve coil
IPM
Intelligent power module
LED1
Indicator lampRed-Inspection indicator
LED2
Indicator lampGreen-Microcomputer normality indicator
LED3 Indicator lampGreen-For service
TR Trance former
TB Terminal block
L Reactor
Connector
A/F MODULE
Active filter module
LED E 1 RED WARNING LAMP
INDICATION LAMP COLOR FUNCTION
SELF DIAGNOSIS FUNCTION BY LED E 1-TIME FLASH 2-TIME FLASH
CURRENT CUT TROUBLE OF OUTDOOR UNIT
FOUR SEC LIGHT
3-TIME FLASH
5-TIME FLASH 6-TIME FLASH
OVER CURRENT
OVER HEAT OF COMPRESSOR ERROR OF SIGNAL TRANSMISSION
DISCHARGE PIPE SENSOR ERRORAND
FOUR SEC OFF
8-TIME FLASH SENSOR ERROR
EXCEPT DISCHARGE PIPE SENSOR
LIGHT ON OUTDOOR FAN MOTOR ERROR
4-TIME FLASH TRANSMISSION ERROR
Color
RD
Mark
YellowGreen
YG
BlackBK BlueBL BrownBR
YellowY
WhiteWH
Red
OrangeOR PinkPK
GreenGN
Note(1) used only at our factory.
Power source 1 Phase AC 220
240V
50Hz
B
RWC 000 Z24 4
-
20
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZMX-S x 2
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM40ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
4.00
kW cooling SEER
5.92 A+
heating / Average Pdesignh
5.20
kW heating / Average SCOP/A
4.05 A+ heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
4.41
kW heating / Average (-10) elbu
0.79
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
4.00
kW Tj=35 EERd
4.76
-
Tj=30 Pdc
3.00
kW Tj=30 EERd
7.20
-
Tj=25 Pdc
3.30
kW Tj=25 EERd
8.90
-
Tj=20 Pdc
3.60
kW Tj=20 EERd
7.40
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh 4.60 kW Tj=-7 COPd
2.80
-
Tj=2 Pdh 2.80 kW Tj=2 COPd
3.90
-
Tj=7 Pdh 2.20 kW Tj=7 COPd
5.50
-
Tj=12 Pdh 3.10 kW Tj=12 COPd
6.90
-
Tj=bivalent temperature Pdh 4.60 kW Tj=bivalent temperature COPd
2.80
-
Tj=operating limit Pdh 4.10 kW Tj=operating limit COPd
2.50
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
13
W cooling Qce
237
kWh/a
standby mode Psb
13
W heating / Average Qhe
1798
kWh/a
thermostat-off mode Pto
25
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
53
dB(A)
Sound power level(outdoor) Lwa
60
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
690
m3/h
variable
Yes
Rated air flow(outdoor) -
2400
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4
4. TECHNICAL INFORMATION
(1) Model SCM40ZM-S
A
-
21
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZM-S x 2
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM40ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
4.00
kW cooling SEER
5.72 A+ heating / Average Pdesignh
5.20
kW heating / Average SCOP/A
3.84 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
4.41
kW heating / Average (-10) elbu
0.79
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc kW Tj=35 EERd ­Tj=30 Pdc kW Tj=30 EERd ­Tj=25 Pdc kW Tj=25 EERd
-
Tj=20 Pdc kW Tj=20 EERd
4.00 4.54
3.00 6.90
3.30 8.50
3.60 7.20
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
4.60
kW Tj=-7 COPd
2.60
-
Tj=2 Pdh
2.80
kW Tj=2 COPd
3.60
-
Tj=7 Pdh
2.20
kW Tj=7 COPd
5.50
-
Tj=12 Pdh
3.10
kW Tj=12 COPd
6.90
-
Tj=bivalent temperature Pdh
4.60
kW Tj=bivalent temperature COPd
2.60
-
Tj=operating limit Pdh
4.10
kW Tj=operating limit COPd
2.40
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
13
W cooling Qce
245
kWh/a
standby mode Psb
13
W heating / Average Qhe
1897
kWh/a
thermostat-off mode Pto
25
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
49
dB(A)
Sound power level(outdoor) Lwa
60
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
468
m3/h
variable
Yes
Rated air flow(outdoor) -
2400
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
22
-
'14 • SCM-T-167
(2) Model SCM45ZM-S
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZMX-S + SRK25ZMX-S
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM45ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
4.50
kW cooling SEER
5.98 A+ heating / Average Pdesignh
5.80
kW heating / Average SCOP/A
4.03 A+ heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
4.95
kW heating / Average (-10) elbu
0.85
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
4.50
kW Tj=35 EERd
4.33
-
Tj=30 Pdc
3.30
kW Tj=30 EERd
7.00
-
Tj=25 Pdc
3.30
kW Tj=25 EERd
8.90
-
Tj=20 Pdc
3.60
kW Tj=20 EERd
7.40
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
5.10
kW Tj=-7 COPd
2.40
-
Tj=2 Pdh
3.10
kW Tj=2 COPd
4.00
-
Tj=7 Pdh
2.20
kW Tj=7 COPd
5.50
-
Tj=12 Pdh
3.10
kW Tj=12 COPd
6.90
-
Tj=bivalent temperature Pdh
5.10
kW Tj=bivalent temperature COPd
2.40
-
Tj=operating limit Pdh
4.70
kW Tj=operating limit COPd
2.10
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
13
W cooling Qce
264
kWh/a
standby mode Psb
13
W heating / Average Qhe
2014
kWh/a
thermostat-off mode Pto
25
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
55
dB(A)
Sound power level(outdoor) Lwa
60
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
750
m3/h
variable
Yes
Rated air flow(outdoor) -
2400
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
23
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZM-S+SRK25ZM-S
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM45ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling Yes Warmer(if designated)
No
heating Yes Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc 4.50 kW cooling SEER
5.80 A+ heating / Average Pdesignh 5.80 kW heating / Average SCOP/A
3.82 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
4.95
kW heating / Average (-10) elbu
0.85
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu --kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
4.50
kW Tj=35 EERd
4.12
-
Tj=30 Pdc
3.30
kW Tj=30 EERd
6.85
-
Tj=25 Pdc
3.30
kW Tj=25 EERd
8.50
-
Tj=20 Pdc
3.60
kW Tj=20 EERd
7.20
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
5.10
kW Tj=-7 COPd
2.30
-
Tj=2 Pdh
3.10
kW Tj=2 COPd
3.65
-
Tj=7 Pdh
2.20
kW Tj=7 COPd
5.50
-
Tj=12 Pdh
3.10
kW Tj=12 COPd
6.85
-
Tj=bivalent temperature Pdh
5.10
kW Tj=bivalent temperature COPd
2.30
-
Tj=operating limit Pdh
4.70
kW Tj=operating limit COPd
2.10
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
13
W cooling Qce
272
kWh/a
standby mode Psb
13
W heating / Average Qhe
2128
kWh/a
thermostat-off mode Pto
25
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
50
dB(A)
Sound power level(outdoor) Lwa
60
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
474
m3/h
variable
Yes
Rated air flow(outdoor) -
2400
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
24
-
'14 • SCM-T-167
(3) Model SCM50ZM-S
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK25ZMX-S×2
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM50ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling Yes Warmer(if designated)
No
heating Yes Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
5.00
kW cooling SEER
5.61 A+ heating / Average Pdesignh
5.80
kW heating / Average SCOP/A
3.82 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
4.90
kW heating / Average (-10) elbu
0.90
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
5.00
kW Tj=35 EERd
3.70
-
Tj=30 Pdc
3.70
kW Tj=30 EERd
5.75
-
Tj=25 Pdc
3.30
kW Tj=25 EERd
8.15
-
Tj=20 Pdc
3.60
kW Tj=20 EERd
7.40
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
5.20
kW Tj=-7 COPd
2.50
-
Tj=2 Pdh
3.20
kW Tj=2 COPd
3.71
-
Tj=7 Pdh
2.10
kW Tj=7 COPd
5.20
-
Tj=12 Pdh
2.30
kW Tj=12 COPd
5.90
-
Tj=bivalent temperature Pdh
5.20
kW Tj=bivalent temperature COPd
2.50
-
Tj=operating limit Pdh
4.40
kW Tj=operating limit COPd
1.90
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
12
W cooling Qce
312
kWh/a
standby mode Psb
12
W heating / Average Qhe
2125
kWh/a
thermostat-off mode Pto
30
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
50
dB(A)
Sound power level(outdoor) Lwa
62
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
474
m3/h
variable
Yes
Rated air flow(outdoor) -
2460
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
25
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZMX-S x 3
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM50ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling Yes Warmer(if designated)
No
heating Yes Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
5.00
kW cooling SEER
6.62 A++ heating / Average Pdesignh
5.90
kW heating / Average SCOP/A
3.95 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -
-heating / Colder Pdesignh - kW heating / Colder SCOP/C -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
4.90
kW heating / Average (-10) elbu
1.00
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
5.00
kW Tj=35 EERd
4.63
-
Tj=30 Pdc
3.70
kW Tj=30 EERd
7.10
-
Tj=25 Pdc
3.60
kW Tj=25 EERd
9.90
-
Tj=20 Pdc
3.90
kW Tj=20 EERd
9.00
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
5.20
kW Tj=-7 COPd
2.60
-
Tj=2 Pdh
3.20
kW Tj=2 COPd
3.90
-
Tj=7 Pdh
2.00
kW Tj=7 COPd
5.10
-
Tj=12 Pdh
2.30
kW Tj=12 COPd
6.30
-
Tj=bivalent temperature Pdh
5.20
kW Tj=bivalent temperature COPd
2.60
-
Tj=operating limit Pdh
4.40
kW Tj=operating limit COPd
2.20
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
13
W cooling Qce
265
kWh/a
standby mode Psb
13
W heating / Average Qhe
2091
kWh/a
thermostat-off mode Pto
28
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
53
dB(A)
Sound power level(outdoor) Lwa
62
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
690
m3/h
variable
Yes
Rated air flow(outdoor) -
2460
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4B
-
26
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK25ZM-S×2
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM50ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
5.00
kW cooling SEER
5.60
A+
heating / Average Pdesignh
6.10
kW heating / Average SCOP/A
3.80
A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
5.14
kW heating / Average (-10) elbu
0.96
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
5.00
kW Tj=35 EERd
3.40
-
Tj=30 Pdc
3.70
kW Tj=30 EERd
5.70
-
Tj=25 Pdc
3.30
kW Tj=25 EERd
8.10
-
Tj=20 Pdc
3.60
kW Tj=20 EERd
7.40
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
5.40
kW Tj=-7 COPd
2.40
-
Tj=2 Pdh
3.30
kW Tj=2 COPd
3.73
-
Tj=7 Pdh
2.20
kW Tj=7 COPd
5.20
-
Tj=12 Pdh
2.80
kW Tj=12 COPd
5.90
-
Tj=bivalent temperature Pdh
5.40
kW Tj=bivalent temperature COPd
2.40
-
Tj=operating limit Pdh
4.70
kW Tj=operating limit COPd
1.90
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
11
W cooling Qce
313
kWh/a
standby mode Psb
11
W heating / Average Qhe
2247
kWh/a
thermostat-off mode Pto
25
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
50
dB(A)
Sound power level(outdoor) Lwa
62
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
474
m3/h
variable
Yes
Rated air flow(outdoor) -
2460
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
27
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZM-S×3
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM50ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
5.00
kW cooling SEER
6.52 A++
heating / Average Pdesignh
6.30
kW heating / Average SCOP/A
3.88 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
5.19
kW heating / Average (-10) elbu
1.11
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu --kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
5.00
kW Tj=35 EERd
4.50
-
Tj=30 Pdc
3.70
kW Tj=30 EERd
7.00
-
Tj=25 Pdc
3.50
kW Tj=25 EERd
9.60
-
Tj=20 Pdc
4.00
kW Tj=20 EERd
8.80
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
5.60
kW Tj=-7 COPd
2.40
-
Tj=2 Pdh
3.40
kW Tj=2 COPd
3.60
-
Tj=7 Pdh
2.20
kW Tj=7 COPd
5.60
-
Tj=12 Pdh
2.80
kW Tj=12 COPd
7.10
-
Tj=bivalent temperature Pdh
5.60
kW Tj=bivalent temperature COPd
2.40
-
Tj=operating limit Pdh
4.50
kW Tj=operating limit COPd
2.20
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
12
W cooling Qce
269
kWh/a
standby mode Psb
12
W heating / Average Qhe
2276
kWh/a
thermostat-off mode Pto
32
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
49
dB(A)
Sound power level(outdoor) Lwa
62
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
468
m3/h
variable
Yes
Rated air flow(outdoor) -
2460
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4B
-
28
-
'14 • SCM-T-167
(4) Model SCM60ZM-S
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK25ZMX-S+SRK35ZMX-S
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM60ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling Yes Warmer(if designated)
No
heating Yes Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
6.00
kW cooling SEER
5.61 A+ heating / Average Pdesignh
7.00
kW heating / Average SCOP/A
3.82 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.56
kW heating / Average (-10) elbu
0.44
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
6.00
kW Tj=35 EERd
3.15
-
Tj=30 Pdc
4.42
kW Tj=30 EERd
4.75
-
Tj=25 Pdc
3.19
kW Tj=25 EERd
8.62
-
Tj=20 Pdc
4.20
kW Tj=20 EERd
7.38
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.41
kW Tj=-7 COPd
2.37
-
Tj=2 Pdh
3.88
kW Tj=2 COPd
3.85
-
Tj=7 Pdh
3.24
kW Tj=7 COPd
5.25
-
Tj=12 Pdh
3.83
kW Tj=12 COPd
5.97
-
Tj=bivalent temperature Pdh
6.41
kW Tj=bivalent temperature COPd
2.37
-
Tj=operating limit Pdh
6.82
kW Tj=operating limit COPd
2.3
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
12
W cooling Qce
375
kWh/a
standby mode Psb
12
W heating / Average Qhe
2569
kWh/a
thermostat-off mode Pto
25
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
58
dB(A)
Sound power level(outdoor) Lwa
63
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
810
m3/h
variable
Yes
Rated air flow(outdoor) -
2520
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
29
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZMX-S×3
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM60ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
6.00
kW cooling SEER
6.55 A++ heating / Average Pdesignh
7.10
kW heating / Average SCOP/A
4.01 A+ heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.37
kW heating / Average (-10) elbu
0.73
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
6.00
kW Tj=35 EERd
4.08
-
Tj=30 Pdc
4.47
kW Tj=30 EERd
6.32
-
Tj=25 Pdc
3.27
kW Tj=25 EERd
9.63
-
Tj=20 Pdc
4.55
kW Tj=20 EERd
9.19
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.50
kW Tj=-7 COPd
2.30
-
Tj=2 Pdh
4.04
kW Tj=2 COPd
4.14
-
Tj=7 Pdh
2.65
kW Tj=7 COPd
5.25
-
Tj=12 Pdh
2.93
kW Tj=12 COPd
6.11
-
Tj=bivalent temperature Pdh
6.50
kW Tj=bivalent temperature COPd
2.30
-
Tj=operating limit Pdh
6.14
kW Tj=operating limit COPd
2.56
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
14
W cooling Qce
321
kWh/a
standby mode Psb
14
W heating / Average Qhe
2480
kWh/a
thermostat-off mode Pto
30
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
53
dB(A)
Sound power level(outdoor) Lwa
63
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
690
m3/h
variable
Yes
Rated air flow(outdoor) -
2520
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4B
-
30
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK25ZM-S+SRK35ZM-S
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM60ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
6.00
kW cooling SEER
5.55 A heating / Average Pdesignh
7.20
kW heating / Average SCOP/A
3.80 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.56
kW heating / Average (-10) elbu
0.64
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
6.00
kW Tj=35 EERd
3.03
-
Tj=30 Pdc
4.42
kW Tj=30 EERd
4.72
-
Tj=25 Pdc
3.19
kW Tj=25 EERd
8.62
-
Tj=20 Pdc
4.20
kW Tj=20 EERd
7.38
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.41
kW Tj=-7 COPd
2.37
-
Tj=2 Pdh
3.88
kW Tj=2 COPd
3.83
-
Tj=7 Pdh
3.24
kW Tj=7 COPd
5.19
-
Tj=12 Pdh
3.83
kW Tj=12 COPd
5.95
-
Tj=bivalent temperature Pdh
6.41
kW Tj=bivalent temperature COPd
2.37
-
Tj=operating limit Pdh
6.82
kW Tj=operating limit COPd
2.14
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
12
W cooling Qce
379
kWh/a
standby mode Psb
12
W heating / Average Qhe
2656
kWh/a
thermostat-off mode Pto
35
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
58
dB(A)
Sound power level(outdoor) Lwa
63
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
606
m3/h
variable
Yes
Rated air flow(outdoor) -
2520
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4
-
31
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZM-S×3
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM60ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
6.00
kW cooling SEER
6.21 A++ heating / Average Pdesignh
7.10
kW heating / Average SCOP/A
3.91 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.46
kW heating / Average (-10) elbu
0.64
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
6.00
kW Tj=35 EERd
3.98
-
Tj=30 Pdc
4.47
kW Tj=30 EERd
6.10
-
Tj=25 Pdc
3.27
kW Tj=25 EERd
9.10
-
Tj=20 Pdc
4.55
kW Tj=20 EERd
8.50
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.65
kW Tj=-7 COPd
2.37
-
Tj=2 Pdh
4.04
kW Tj=2 COPd
3.90
-
Tj=7 Pdh
2.65
kW Tj=7 COPd
5.25
-
Tj=12 Pdh
2.93
kW Tj=12 COPd
6.11
-
Tj=bivalent temperature Pdh
6.65
kW Tj=bivalent temperature COPd
2.37
-
Tj=operating limit Pdh
6.14
kW Tj=operating limit COPd
2.56
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
14
W cooling Qce
338
kWh/a
standby mode Psb
14
W heating / Average Qhe
2544
kWh/a
thermostat-off mode Pto
40
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
49
dB(A)
Sound power level(outdoor) Lwa
63
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
468
m3/h
variable
Yes
Rated air flow(outdoor) -
2520
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4B
-
32
-
'14 • SCM-T-167
(5) Model SCM71ZM-S
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK35ZMX-Sx2
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM71ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
7.10
kW cooling SEER
5.85 A+ heating / Average Pdesignh
7.30
kW heating / Average SCOP/A
3.81 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
5.98
kW heating / Average (-10) elbu
1.32
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
7.10
kW Tj=35 EERd
3.34
-
Tj=30 Pdc
5.29
kW Tj=30 EERd
5.25
-
Tj=25 Pdc
3.30
kW Tj=25 EERd
7.85
-
Tj=20 Pdc
4.31
kW Tj=20 EERd
9.25
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.62
kW Tj=-7 COPd
2.45
-
Tj=2 Pdh
3.95
kW Tj=2 COPd
3.99
-
Tj=7 Pdh
2.49
kW Tj=7 COPd
4.57
-
Tj=12 Pdh
2.63
kW Tj=12 COPd
5.58
-
Tj=bivalent temperature Pdh
6.62
kW Tj=bivalent temperature COPd
2.45
-
Tj=operating limit Pdh
4.90
kW Tj=operating limit COPd
1.80
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
15
W cooling Qce
425
kWh/a
standby mode Psb
15
W heating / Average Qhe
2682
kWh/a
thermostat-off mode Pto
40
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
58
dB(A)
Sound power level(outdoor) Lwa
65
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
810
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
33
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZMX-S+SRK25ZMX-Sx2
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM71ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
7.10
kW cooling SEER
6.09 A+ heating / Average Pdesignh
7.30
kW heating / Average SCOP/A
3.81 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
5.98
kW heating / Average (-10) elbu
1.32
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
7.10
kW Tj=35 EERd
3.85
-
Tj=30 Pdc
5.29
kW Tj=30 EERd
5.55
-
Tj=25 Pdc
3.30
kW Tj=25 EERd
8.05
-
Tj=20 Pdc
4.31
kW Tj=20 EERd
9.35
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.62
kW Tj=-7 COPd
2.45
-
Tj=2 Pdh
3.95
kW Tj=2 COPd
3.99
-
Tj=7 Pdh
2.49
kW Tj=7 COPd
4.57
-
Tj=12 Pdh
2.63
kW Tj=12 COPd
5.58
-
Tj=bivalent temperature Pdh
6.62
kW Tj=bivalent temperature COPd
2.45
-
Tj=operating limit Pdh
4.90
kW Tj=operating limit COPd
1.80
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
15
W cooling Qce
409
kWh/a
standby mode Psb
15
W heating / Average Qhe
2682
kWh/a
thermostat-off mode Pto
40
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
55
dB(A)
Sound power level(outdoor) Lwa
65
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
750
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
34
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZMX-S × 4
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM71ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
7.10
kW cooling SEER
6.41 A++ heating / Average Pdesignh
7.30
kW heating / Average SCOP/A
3.81 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
5.98
kW heating / Average (-10) elbu
1.32
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
7.10
kW Tj=35 EERd
4.14
-
Tj=30 Pdc
5.29
kW Tj=30 EERd
5.94
-
Tj=25 Pdc
3.30
kW Tj=25 EERd
8.28
-
Tj=20 Pdc
4.31
kW Tj=20 EERd
10.19
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.62
kW Tj=-7 COPd
2.45
-
Tj=2 Pdh
3.95
kW Tj=2 COPd
3.99
-
Tj=7 Pdh
2.49
kW Tj=7 COPd
4.57
-
Tj=12 Pdh
2.63
kW Tj=12 COPd
5.58
-
Tj=bivalent temperature Pdh
6.62
kW Tj=bivalent temperature COPd
2.45
-
Tj=operating limit Pdh
4.90
kW Tj=operating limit COPd
1.80
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
15
W cooling Qce
388
kWh/a
standby mode Psb
15
W heating / Average Qhe
2682
kWh/a
thermostat-off mode Pto
40
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
53
dB(A)
Sound power level(outdoor) Lwa
65
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
690
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4B
-
35
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK35ZM-S×2
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM71ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
7.10
kW cooling SEER
5.67 A+ heating / Average Pdesignh
7.40
kW heating / Average SCOP/A
3.80 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.83
kW heating / Average (-10) elbu
0.57
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
7.10
kW Tj=35 EERd
2.91
-
Tj=30 Pdc
5.26
kW Tj=30 EERd
4.71
-
Tj=25 Pdc
3.36
kW Tj=25 EERd
8.65
-
Tj=20 Pdc
4.14
kW Tj=20 EERd
9.13
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.65
kW Tj=-7 COPd
2.21
-
Tj=2 Pdh
3.86
kW Tj=2 COPd
4.19
-
Tj=7 Pdh
3.04
kW Tj=7 COPd
4.64
-
Tj=12 Pdh
3.58
kW Tj=12 COPd
5.35
-
Tj=bivalent temperature Pdh
6.65
kW Tj=bivalent temperature COPd
2.21
-
Tj=operating limit Pdh
7.12
kW Tj=operating limit COPd
1.99
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
18
W cooling Qce
439
kWh/a
standby mode Psb
18
W heating / Average Qhe
2726
kWh/a
thermostat-off mode Pto
50
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
58
dB(A)
Sound power level(outdoor) Lwa
65
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
606
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
36
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZM-S+SRK25ZM-Sx2
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM71ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
7.10
kW cooling SEER
5.81 A+ heating / Average Pdesignh
7.40
kW heating / Average SCOP/A
3.80 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.83
kW heating / Average (-10) elbu
0.57
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
7.10
kW Tj=35 EERd
3.73
-
Tj=30 Pdc
5.26
kW Tj=30 EERd
4.71
-
Tj=25 Pdc
3.36
kW Tj=25 EERd
8.65
-
Tj=20 Pdc
4.14
kW Tj=20 EERd
9.13
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.65
kW Tj=-7 COPd
2.21
-
Tj=2 Pdh
3.86
kW Tj=2 COPd
4.19
-
Tj=7 Pdh
3.04
kW Tj=7 COPd
4.64
-
Tj=12 Pdh
3.58
kW Tj=12 COPd
5.35
-
Tj=bivalent temperature Pdh
6.65
kW Tj=bivalent temperature COPd
2.21
-
Tj=operating limit Pdh
7.12
kW Tj=operating limit COPd
1.99
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
19
W cooling Qce
429
kWh/a
standby mode Psb
19
W heating / Average Qhe
2726
kWh/a
thermostat-off mode Pto
52
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
50
dB(A)
Sound power level(outdoor) Lwa
65
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
474
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
37
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZM-Sx4
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM71ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
7.10
kW cooling SEER
5.94 A+ heating / Average Pdesignh
7.40
kW heating / Average SCOP/A
3.80 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.83
kW heating / Average (-10) elbu
0.57
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
7.10
kW Tj=35 EERd
3.94
-
Tj=30 Pdc
5.26
kW Tj=30 EERd
5.03
-
Tj=25 Pdc
3.36
kW Tj=25 EERd
8.65
-
Tj=20 Pdc
4.14
kW Tj=20 EERd
9.27
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.65
kW Tj=-7 COPd
2.21
-
Tj=2 Pdh
3.86
kW Tj=2 COPd
4.19
-
Tj=7 Pdh
3.04
kW Tj=7 COPd
4.64
-
Tj=12 Pdh
3.58
kW Tj=12 COPd
5.35
-
Tj=bivalent temperature Pdh
6.65
kW Tj=bivalent temperature COPd
2.21
-
Tj=operating limit Pdh
7.12
kW Tj=operating limit COPd
1.99
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
19
W cooling Qce
419
kWh/a
standby mode Psb
19
W heating / Average Qhe
2726
kWh/a
thermostat-off mode Pto
52
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
46
dB(A)
Sound power level(outdoor) Lwa
65
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
468
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
38
-
'14 • SCM-T-167
(6) Model SCM80ZM-S
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK35ZMX-S+SRK50ZMX-S
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM80ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
8.00
kW cooling SEER
5.74 A+ heating / Average Pdesignh
7.50
kW heating / Average SCOP/A
3.81 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
5.98
kW heating / Average (-10) elbu
1.52
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
8.00
kW Tj=35 EERd
3.23
-
Tj=30 Pdc
5.94
kW Tj=30 EERd
5.01
-
Tj=25 Pdc
3.70
kW Tj=25 EERd
7.2
-
Tj=20 Pdc
4.31
kW Tj=20 EERd
9.51
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.62
kW Tj=-7 COPd
2.45
-
Tj=2 Pdh
3.95
kW Tj=2 COPd
3.99
-
Tj=7 Pdh
2.57
kW Tj=7 COPd
4.57
-
Tj=12 Pdh
2.63
kW Tj=12 COPd
5.58
-
Tj=bivalent temperature Pdh
6.62
kW Tj=bivalent temperature COPd
2.45
-
Tj=operating limit Pdh
4.90
kW Tj=operating limit COPd
1.80
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
14
W cooling Qce
489
kWh/a
standby mode Psb
14
W heating / Average Qhe
2755
kWh/a
thermostat-off mode Pto
35
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
60
dB(A)
Sound power level(outdoor) Lwa
66
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
810
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
39
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZMX-S+SRK25ZMX-S+SRK35ZMX-S
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM80ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
8.00
kW cooling SEER
5.95 A+ heating / Average Pdesignh
7.50
kW heating / Average SCOP/A
3.81 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
5.98
kW heating / Average (-10) elbu
1.52
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
8.00
kW Tj=35 EERd
3.52
-
Tj=30 Pdc
5.94
kW Tj=30 EERd
5.12
-
Tj=25 Pdc
3.70
kW Tj=25 EERd
7.65
-
Tj=20 Pdc
4.31
kW Tj=20 EERd
9.85
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.62
kW Tj=-7 COPd
2.45
-
Tj=2 Pdh
3.95
kW Tj=2 COPd
3.99
-
Tj=7 Pdh
2.57
kW Tj=7 COPd
4.57
-
Tj=12 Pdh
2.63
kW Tj=12 COPd
5.58
-
Tj=bivalent temperature Pdh
6.62
kW Tj=bivalent temperature COPd
2.45
-
Tj=operating limit Pdh
4.90
kW Tj=operating limit COPd
1.80
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
15
W cooling Qce
471
kWh/a
standby mode Psb
15
W heating / Average Qhe
2755
kWh/a
thermostat-off mode Pto
40
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
58
dB(A)
Sound power level(outdoor) Lwa
66
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
810
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
40
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZMX-S × 4
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM80ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
8.00
kW cooling SEER
6.29 A++ heating / Average Pdesignh
7.50
kW heating / Average SCOP/A
3.81 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
5.98
kW heating / Average (-10) elbu
1.52
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
8.00
kW Tj=35 EERd
3.80
-
Tj=30 Pdc
5.94
kW Tj=30 EERd
5.50
-
Tj=25 Pdc
3.70
kW Tj=25 EERd
8.15
-
Tj=20 Pdc
4.31
kW Tj=20 EERd
10.19
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.62
kW Tj=-7 COPd
2.45
-
Tj=2 Pdh
3.95
kW Tj=2 COPd
3.99
-
Tj=7 Pdh
2.57
kW Tj=7 COPd
4.57
-
Tj=12 Pdh
2.63
kW Tj=12 COPd
5.58
-
Tj=bivalent temperature Pdh
6.62
kW Tj=bivalent temperature COPd
2.45
-
Tj=operating limit Pdh
4.90
kW Tj=operating limit COPd
1.80
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
15
W cooling Qce
446
kWh/a
standby mode Psb
15
W heating / Average Qhe
2755
kWh/a
thermostat-off mode Pto
40
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
53
dB(A)
Sound power level(outdoor) Lwa
66
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
690
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4B
-
41
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK35ZM-S+SRK50ZM-S
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM80ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
7.50
kW cooling SEER
5.66 A+ heating / Average Pdesignh
7.60
kW heating / Average SCOP/A
3.80 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.69
kW heating / Average (-10) elbu
0.91
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
7.50
kW Tj=35 EERd
2.79
-
Tj=30 Pdc
5.54
kW Tj=30 EERd
4.74
-
Tj=25 Pdc
3.52
kW Tj=25 EERd
8.46
-
Tj=20 Pdc
4.19
kW Tj=20 EERd
9.27
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.80
kW Tj=-7 COPd
2.29
-
Tj=2 Pdh
3.99
kW Tj=2 COPd
4.12
-
Tj=7 Pdh
3.04
kW Tj=7 COPd
4.64
-
Tj=12 Pdh
3.58
kW Tj=12 COPd
5.35
-
Tj=bivalent temperature Pdh
6.80
kW Tj=bivalent temperature COPd
2.29
-
Tj=operating limit Pdh
6.50
kW Tj=operating limit COPd
2.14
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
18
W cooling Qce
464
kWh/a
standby mode Psb
18
W heating / Average Qhe
2803
kWh/a
thermostat-off mode Pto
52
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
61
dB(A)
Sound power level(outdoor) Lwa
66
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
678
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
42
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZM-S+SRK25ZM-S+SRK35ZM-S
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM80ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
7.50
kW cooling SEER
5.76 A+ heating / Average Pdesignh
7.60
kW heating / Average SCOP/A
3.80 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.69
kW heating / Average (-10) elbu
0.91
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
7.50
kW Tj=35 EERd
3.52
-
Tj=30 Pdc
5.54
kW Tj=30 EERd
4.74
-
Tj=25 Pdc
3.52
kW Tj=25 EERd
8.46
-
Tj=20 Pdc
4.19
kW Tj=20 EERd
9.27
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.80
kW Tj=-7 COPd
2.29
-
Tj=2 Pdh
3.99
kW Tj=2 COPd
4.12
-
Tj=7 Pdh
3.04
kW Tj=7 COPd
4.64
-
Tj=12 Pdh
3.58
kW Tj=12 COPd
5.35
-
Tj=bivalent temperature Pdh
6.80
kW Tj=bivalent temperature COPd
2.29
-
Tj=operating limit Pdh
6.50
kW Tj=operating limit COPd
2.14
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
20
W cooling Qce
456
kWh/a
standby mode Psb
20
W heating / Average Qhe
2803
kWh/a
thermostat-off mode Pto
52
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
58
dB(A)
Sound power level(outdoor) Lwa
66
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
606
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
43
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK20ZM-S x 4
information relates to. Indicated values should relate to one
Outdoor unit model name
SCM80ZM-S
heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory)
Yes
cooling
Yes
Warmer(if designated)
No
heating
Yes
Colder(if designated)
No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc
7.50
kW cooling SEER
5.85 A+ heating / Average Pdesignh
7.60
kW heating / Average SCOP/A
3.80 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh
6.69
kW heating / Average (-10) elbu
0.91
kW
heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19) and Declared energy efficiency ratio, at indoor temperature 27(19)and outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc
7.50
kW Tj=35 EERd
3.57
-
Tj=30 Pdc
5.54
kW Tj=30 EERd
5.03
-
Tj=25 Pdc
3.52
kW Tj=25 EERd
8.68
-
Tj=20 Pdc
4.19
kW Tj=20 EERd
9.27
-
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh
6.80
kW Tj=-7 COPd
2.29
-
Tj=2 Pdh
3.99
kW Tj=2 COPd
4.12
-
Tj=7 Pdh
3.04
kW Tj=7 COPd
4.64
-
Tj=12 Pdh
3.58
kW Tj=12 COPd
5.35
-
Tj=bivalent temperature Pdh
6.80
kW Tj=bivalent temperature COPd
2.29
-
Tj=operating limit Pdh
6.50
kW Tj=operating limit COPd
2.14
-
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor temperature 20 and outdoor temperature Tj temperature 20and outdoor temperature Tj Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW
Tj=operating limit COPd - -
Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv
-7
heating / Average Tol
-15
heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacit
y
Cycling interval efficienc
y
for cooling Pcyc
c
- kW for cooling EERcy
c
- -
for heating Pcych - kW for heating COPcy
c
- -
Degradation coefficient Degradation coefficient cooling Cdc
0.25
- heating Cdh
0.25
-
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff
22
W cooling Qce
449
kWh/a
standby mode Psb
22
W heating / Average Qhe
2803
kWh/a
thermostat-off mode Pto
52
W heating / Warmer Qhe - kWh/a
crankcase heater mode Pck
0
W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa
46
dB(A)
Sound power level(outdoor) Lwa
66
dB(A)
fixed
No
Global warming potential GWP
1975
kgCO2eq.
staged
No
Rated air flow(indoor) -
468
m3/h
variable
Yes
Rated air flow(outdoor) -
3360
m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
44
-
'14 • SCM-T-167
(7) Model SCM100ZM-S
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name
SRK25ZMX-Sx2+SRK50ZMX-S
information relates to. Indicated values should relate to one
Outdoor unit model name SCM100ZM
S heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yes cooling Yes Warmer(if designated) No heating Yes Colder(if designated) No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc 10.00 kW cooling SEER 4.95 B heating / Average Pdesignh 10.10 kW heating / Average SCOP/A 3.89 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh 8.62 kW heating / Average (-10 ) elbu 1.48 kW heating / Warmer (2) Pdh - kW heating / Warmer (2 ) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared ca
p
acity for cooling, at indoor temperature 27(19℃ and Declared energy efficiency ratio, at indoor temperature 27(1and
outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc 10.00 kW Tj=35 EERd 3.51 ­Tj=30 Pdc 7.65 kW Tj=30 EERd 5.45 ­Tj=25 Pdc 8.10 kW Tj=25 EERd 6.98 ­Tj=20 Pdc 7.81 kW Tj=20 EERd 7.55 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh 8.93 kW Tj=-7 COPd 2.43 ­Tj=2 Pdh 5.49 kW Tj=2 COPd 3.88 ­Tj=7 Pdh 4.61 kW Tj=7 COPd 5.35 ­Tj=12 Pdh 5.34 kW Tj=12 COPd 6.72 ­Tj=bivalent temperature Pdh 8.93 kW Tj=bivalent temperature COPd 2.43 ­Tj=operating limit Pdh 8.11 kW Tj=operating limit COPd 2.29 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - ­Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv -7 heating / Average Tol -15 heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacity Cycling interval efficiency for cooling Pcycc - kW for cooling EERcyc - ­for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficient cooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff 39 W cooling Qce 707 kWh/a standby mode Psb 39 W heating / Average Qhe 3633 kWh/a thermostat-off mode Pto 48 W heating / Warmer Qhe
- kWh/a
crankcase heater mode Pck 0 W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa 60 dB(A) Sound power level(outdoor) Lwa 68 dB(A)
fixed No Global warming potential GWP 1975
kgCO2eq. staged No Rated air flow(indoor) - 810 m3/h variable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4
-
45
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name SRK25ZMX-S×4 information relates to. Indicated values should relate to one Outdoor unit model name SCM100ZM
S heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yes cooling Yes Warmer(if designated) No heating Yes Colder(if designated) No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc 10.00 kW cooling SEER 5.01 B heating / Average Pdesignh 10.10 kW heating / Average SCOP/A 3.95 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10)
Pdh 8.62 kW
heating / Average (-10)
elbu 1.48 kW
heating / Warmer (2)
Pdh - kW
heating / Warmer (2)
elbu - kW
heating / Colder (-22)
Pdh - kW
heating / Colder (-22)
elbu - kW
Declared ca
p
acity for cooling, at indoor temperature 27(19℃ and Declared energy efficiency ratio, at indoor temperature 27(1and
outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc 10.00 kW Tj=35 EERd 3.57 ­Tj=30 Pdc 7.65 kW Tj=30 EERd 5.55 ­Tj=25 Pdc 8.10 kW Tj=25 EERd 7.04 ­Tj=20 Pdc 7.81 kW Tj=20 EERd 7.65 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh 8.93 kW Tj=-7 COPd 2.45 ­Tj=2 Pdh 5.49 kW Tj=2 COPd 3.90 ­Tj=7 Pdh 4.61 kW Tj=7 COPd 5.55 ­Tj=12 Pdh 5.34 kW Tj=12 COPd 6.82 ­Tj=bivalent temperature Pdh 8.93 kW Tj=bivalent temperature COPd 2.45 ­Tj=operating limit Pdh 8.11 kW Tj=operating limit COPd 2.29 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - ­Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv -7 heating / Average Tol -15 heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacity Cycling interval efficiency for cooling Pcycc - kW for cooling EERcyc - ­for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficient cooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff 39 W cooling Qce 699 kWh/a standby mode Psb 39 W heating / Average Qhe 3584 kWh/a thermostat-off mode Pto 48 W heating / Warmer Qhe
- kWh/a
crankcase heater mode Pck 0 W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa 55 dB(A) Sound power level(outdoor) Lwa 68 dB(A)
fixed No Global warming potential GWP 1975
kgCO2eq. staged No Rated air flow(indoor) - 750 m3/h variable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4
-
46
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name SRK20ZMX-S×5 information relates to. Indicated values should relate to one Outdoor unit model name SCM100ZM
S heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yes cooling Yes Warmer(if designated) No heating Yes Colder(if designated) No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc 10.00 kW cooling SEER 5.10 A heating / Average Pdesignh 10.10 kW heating / Average SCOP/A 4.02 A+ heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10)
Pdh 8.62 kW
heating / Average (-10)
elbu 1.48 kW
heating / Warmer (2)
Pdh - kW
heating / Warmer (2)
elbu - kW
heating / Colder (-22)
Pdh - kW
heating / Colder (-22)
elbu - kW
Declared ca
p
acity for cooling, at indoor temperature 27(19℃ and Declared energy efficiency ratio, at indoor temperature 27(1and
outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc 10.00 kW Tj=35 EERd 3.57 ­Tj=30 Pdc 7.65 kW Tj=30 EERd 5.76 ­Tj=25 Pdc 8.10 kW Tj=25 EERd 7.14 ­Tj=20 Pdc 7.81 kW Tj=20 EERd 7.82 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh 8.93 kW Tj=-7 COPd 2.52 ­Tj=2 Pdh 5.49 kW Tj=2 COPd 3.97 ­Tj=7 Pdh 4.61 kW Tj=7 COPd 5.64 ­Tj=12 Pdh 5.34 kW Tj=12 COPd 6.89 ­Tj=bivalent temperature Pdh 8.93 kW Tj=bivalent temperature COPd 2.52 ­Tj=operating limit Pdh 8.11 kW Tj=operating limit COPd 2.29 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - ­Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv -7 heating / Average Tol -15 heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacity Cycling interval efficiency for cooling Pcycc - kW for cooling EERcyc - ­for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficient cooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff 39 W cooling Qce 687 kWh/a standby mode Psb 39 W heating / Average Qhe 3519 kWh/a thermostat-off mode Pto 48 W heating / Warmer Qhe
- kWh/a
crankcase heater mode Pck 0 W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa 53 dB(A) Sound power level(outdoor) Lwa 68 dB(A)
fixed No Global warming potential GWP 1975
kgCO2eq. staged No Rated air flow(indoor) - 690 m3/h variable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4A
-
47
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name SRK71ZM-S x 2 information relates to. Indicated values should relate to one Outdoor unit model name SCM100ZM
S heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yes cooling Yes Warmer(if designated) No heating Yes Colder(if designated) No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc 10.00 kW cooling SEER 4.88 B heating / Average Pdesignh 10.10 kW heating / Average SCOP/A 3.83 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10)
Pdh 8.62 kW
heating / Average (-10)
elbu 1.48 kW
heating / Warmer (2)
Pdh - kW
heating / Warmer (2)
elbu - kW
heating / Colder (-22)
Pdh - kW
heating / Colder (-22)
elbu - kW
Declared ca
p
acity for cooling, at indoor temperature 27(19℃ and Declared energy efficiency ratio, at indoor temperature 27(1and
outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc 10.00 kW Tj=35 EERd 3.50 ­Tj=30 Pdc 7.65 kW Tj=30 EERd 5.40 ­Tj=25 Pdc 8.10 kW Tj=25 EERd 6.78 ­Tj=20 Pdc 7.81 kW Tj=20 EERd 7.45 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh 8.93 kW Tj=-7 COPd 2.40 ­Tj=2 Pdh 5.49 kW Tj=2 COPd 3.80 ­Tj=7 Pdh 4.61 kW Tj=7 COPd 5.30 ­Tj=12 Pdh 5.34 kW Tj=12 COPd 6.70 ­Tj=bivalent temperature Pdh 8.93 kW Tj=bivalent temperature COPd 2.40 ­Tj=operating limit Pdh 8.11 kW Tj=operating limit COPd 2.20 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - ­Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv -7 heating / Average Tol -15 heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacity Cycling interval efficiency for cooling Pcycc - kW for cooling EERcyc - ­for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficient cooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff 39 W cooling Qce 718 kWh/a standby mode Psb 39 W heating / Average Qhe 3689 kWh/a thermostat-off mode Pto 48 W heating / Warmer Qhe
- kWh/a
crankcase heater mode Pck 0 W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa 60 dB(A) Sound power level(outdoor) Lwa 68 dB(A)
fixed No Global warming potential GWP 1975
kgCO2eq. staged No Rated air flow(indoor) - 1170 m3/h variable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4
-
48
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name SRK25ZMX-Sx2+FDEN50VF information relates to. Indicated values should relate to one Outdoor unit model name SCM100ZM-S heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yes cooling Yes Warmer(if designated) No heating Yes Colder(if designated) No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc 10.00 kW cooling SEER 4.85 B heating / Average Pdesignh 10.20 kW heating / Average SCOP/A 3.83 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh 8.92 kW heating / Average (-10) elbu 1.28 kW heating / Warmer (2) Pdh - kW heating / Warmer (2 ) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared ca
p
acity for cooling, at indoor temperature 27(19℃ and Declared energy efficiency ratio, at indoor temperature 27(1and
outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc 10.00 kW Tj=35 EERd 3.10 ­Tj=30 Pdc 7.37 kW Tj=30 EERd 4.91 ­Tj=25 Pdc 6.86 kW Tj=25 EERd 7.14 ­Tj=20 Pdc 6.80 kW Tj=20 EERd 8.08 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh 9.02 kW Tj=-7 COPd 2.35 ­Tj=2 Pdh 5.49 kW Tj=2 COPd 3.97 ­Tj=7 Pdh 4.61 kW Tj=7 COPd 5.19 ­Tj=12 Pdh 5.44 kW Tj=12 COPd 5.39 ­Tj=bivalent temperature Pdh 9.02 kW Tj=bivalent temperature COPd 2.35 ­Tj=operating limit Pdh 8.75 kW Tj=operating limit COPd 2.62 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - ­Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv -7 heating / Average Tol -15 heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacity Cycling interval efficiency for cooling Pcycc - kW for cooling EERcyc - ­for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficient cooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff 45 W cooling Qce 723 kWh/a standby mode Psb 45 W heating / Average Qhe 3730 kWh/a thermostat-off mode Pto 55 W heating / Warmer Qhe
- kWh/a
crankcase heater mode Pck 0 W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa 60 dB(A) Sound power level(outdoor) Lwa 68 dB(A)
fixed No Global warming potential GWP 1975
kgCO2eq. staged No Rated air flow(indoor) - 780 m3/h variable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4
-
49
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name SRK25ZM-S×4 information relates to. Indicated values should relate to one Outdoor unit model name SCM100ZM-S heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yes cooling Yes Warmer(if designated) No heating Yes Colder(if designated) No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc 10.00 kW cooling SEER 4.85 B heating / Average Pdesignh 10.20 kW heating / Average SCOP/A 3.83 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh 8.92 kW heating / Average (-10) elbu 1.28 kW heating / Warmer (2) Pdh - kW heating / Warmer (2) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared ca
p
acity for cooling, at indoor temperature 27(19℃ and Declared energy efficiency ratio, at indoor temperature 27(1and
outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc 10.00 kW Tj=35 EERd 3.10 ­Tj=30 Pdc 7.37 kW Tj=30 EERd 4.91 ­Tj=25 Pdc 6.86 kW Tj=25 EERd 7.14 ­Tj=20 Pdc 6.80 kW Tj=20 EERd 8.08 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh 9.02 kW Tj=-7 COPd 2.35 ­Tj=2 Pdh 5.49 kW Tj=2 COPd 3.97 ­Tj=7 Pdh 4.61 kW Tj=7 COPd 5.19 ­Tj=12 Pdh 5.44 kW Tj=12 COPd 5.39 ­Tj=bivalent temperature Pdh 9.02 kW Tj=bivalent temperature COPd 2.35 ­Tj=operating limit Pdh 8.75 kW Tj=operating limit COPd 2.62 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - ­Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv -7 heating / Average Tol -15 heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacity Cycling interval efficiency for cooling Pcycc - kW for cooling EERcyc - ­for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficient cooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff 45 W cooling Qce 723 kWh/a standby mode Psb 45 W heating / Average Qhe 3730 kWh/a thermostat-off mode Pto 55 W heating / Warmer Qhe
- kWh/a
crankcase heater mode Pck 0 W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa 50 dB(A) Sound power level(outdoor) Lwa 68 dB(A)
fixed No Global warming potential GWP 1975
kgCO2eq. staged No Rated air flow(indoor) - 474 m3/h variable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4
-
50
-
'14 • SCM-T-167
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the Indoor unit model name SRK20ZM-S×5 information relates to. Indicated values should relate to one Outdoor unit model name SCM100ZM-S heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yes cooling Yes Warmer(if designated) No heating Yes Colder(if designated) No
Item symbol value unit Item symbol value class Design load Seasonal efficiency and energy efficiency class cooling Pdesignc 10.00 kW cooling SEER 4.85 B heating / Average Pdesignh 10.20 kW heating / Average SCOP/A 3.83 A heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - ­heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unit Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh heating / Average (-10) Pdh 8.92 kW heating / Average (-10) elbu 1.28 kW heating / Warmer (2) Pdh - kW heating / Warmer (2 ) elbu - kW heating / Colder (-22) Pdh - kW heating / Colder (-22) elbu - kW
Declared ca
p
acity for cooling, at indoor temperature 27(19℃ and Declared energy efficiency ratio, at indoor temperature 27(1and
outdoor temperature Tj outdoor temperature Tj Tj=35 Pdc 10.00 kW Tj=35 EERd 3.10 ­Tj=30 Pdc 7.37 kW Tj=30 EERd 4.91 ­Tj=25 Pdc 6.86 kW Tj=25 EERd 7.14 ­Tj=20 Pdc 6.80 kW Tj=20 EERd 8.08 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh 9.02 kW Tj=-7 COPd 2.35 ­Tj=2 Pdh 5.49 kW Tj=2 COPd 3.97 ­Tj=7 Pdh 4.61 kW Tj=7 COPd 5.19 ­Tj=12 Pdh 5.44 kW Tj=12 COPd 5.39 ­Tj=bivalent temperature Pdh 9.02 kW Tj=bivalent temperature COPd 2.35 ­Tj=operating limit Pdh 8.75 kW Tj=operating limit COPd 2.62 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor tem
p
erature 20℃ and outdoor temperature
T
temperature 20℃ and outdoor temperature
T
Tj=-7 Pdh - kW Tj=-7 COPd - ­Tj=2 Pdh - kW Tj=2 COPd - ­Tj=7 Pdh - kW Tj=7 COPd - ­Tj=12 Pdh - kW Tj=12 COPd - ­Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - ­Tj=operating limit Pdh - kW Tj=operating limit COPd - ­Tj=-15 Pdh - kW Tj=-15 COPd - -
Bivalent temperature Operating limit temperature heating / Average Tbiv -7 heating / Average Tol -15 heating / Warmer Tbiv - heating / Warmer Tol - heating / Colder Tbiv - heating / Colder Tol -
Cycling interval capacity Cycling interval efficiency for cooling Pcycc - kW for cooling EERcyc - ­for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficient cooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumption off mode Poff 45 W cooling Qce 723 kWh/a standby mode Psb 45 W heating / Average Qhe 3731 kWh/a thermostat-off mode Pto 60 W heating / Warmer Qhe
- kWh/a
crankcase heater mode Pck 0 W heating / colder Qhe - kWh/a
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa 46 dB(A) Sound power level(outdoor) Lwa 68 dB(A)
fixed No Global warming potential GWP 1975
kgCO2eq. staged No Rated air flow(indoor) - 468 m3/h variable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative. more information
Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd. 7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
RWC 000 Z28 4
INVERTER MULTI-SPLIT SYSTEM RESIDENTIAL AIR-CONDITIONERS
Air-Conditioning & Refrigeration Division
16-5, Konan 2-chome, Minato-ku, Tokyo, 108-8215 Japan
http://www.mhi.co.jp
Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.