Mitsubishi Heavy Industries SRK20ZG-S, SRK50ZG-S, SRK25ZG-S, SRK35ZG-S, SRK25ZG-SS Technical Manual

...
INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type )
SRK20ZG-S, SRK25ZG-S, SRK35ZG-S, SRK50ZG-S
Manual No. ’06
.
SRK-T
.
CONTENTS
1 GENERAL INFORMATION.................................................................... 1
1.1 Specific features............................................................................ 1
1.2 How to read the model name ....................................................... 1
2 SELECTION DATA ................................................................................ 2
2.1 Specifications ................................................................................ 2
2.2 Range of usage & limitations ....................................................... 6
2.3 Exterior dimensions ...................................................................... 6
2.4 Piping system ................................................................................ 8
2.5 Selection chart .............................................................................. 9
3 ELECTRICAL DATA .............................................................................. 10
3.1 Electrical wiring ............................................................................. 10
4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ......... 12
4.1 Operation control function by remote control switch................ 12
4.2 Unit ON/OFF button....................................................................... 13
4.3 Power blackout auto restart function .......................................... 13
4.4 Custom cord switching procedure .............................................. 13
4.5 Flap and louver control................................................................. 14
4.6 3D auto operation .......................................................................... 15
4.7 Timer operation ............................................................................. 16
4.8 Installation location setting .......................................................... 16
4.9 Outline of heating operation ........................................................ 17
4.10 Outline of cooling operation ........................................................ 18
4.11 Outline of automatic operation .................................................... 18
4.12 Protective control function........................................................... 19
5 APPLICATION DATA ............................................................................. 24
5.1 Selection of location for installation ........................................... 25
5.2 Installation of indoor unit ............................................................. 26
5.3 Installation of outdoor unit ........................................................... 29
5.4 Connection of refrigerant pipings ............................................... 29
5.5 Test run .......................................................................................... 31
5.6 Precautions for wireless remote control installation and
operation ........................................................................................ 31
6 MAINTENANCE DATA .......................................................................... 32
6.1 Troubleshooting procedures for electrical equipment .............. 32
6.2 Servicing ........................................................................................ 51
7 INTERFACE KIT (OPTIONAL PARTS).................................................. 52
7.1 Applicable model........................................................................... 52
7.2 List of connectable devices ......................................................... 52
7.3 Exterior dimensions ...................................................................... 52
7.4 Circuit board component layout .................................................. 52
7.5 System configuration.................................................................... 53
7.6 Installation of interface kit ............................................................ 54
7.7 Wired remote control .................................................................... 59
7.8 Insatallation of wired remote control .......................................... 60
7.9 Setting functions using the wired remote control ..................... 61
7.10 Super link adapter ......................................................................... 65
7.11 Operation permission/prohibition control .................................. 67
7.12 External control (remote display) /control of input signal......... 68
8 REFRIGERANT PIPING INSTALLATION / SERVICING MANUAL
FOR AIR CONDITIONERS USING R410A........................................... 69
8.1 Outline ............................................................................................ 69
8.2 Refrigerant piping installation ..................................................... 70
8.3 Installation, removal and servicing.............................................. 76
8.4 Refrigerant recovery ..................................................................... 81
-
1
-
Over heat of compressor
Error of signal transmission
Outdoor fan motor error
1 GENERAL INFORMATION
1.1 Specific features
The “MITSUBISHI HEAVY INDUSTRIES, LTD” room air-conditioner: SRK series are of split and wall mounted type and the unit
consists of indoor unit and outdoor unit with refrigerant precharged in factory. The indoor unit is composed of room air cooling or
heating equipment with operation control switch and the outdoor unit is composed of condensing unit with compressor.
(1) Inverter (Frequency converter) for multi-steps power control
¡ Heating/Cooling
The rotational speed of a compressor is changed in step in relation to varying load, interlocked with the indoor and outdoor unit
fans controlled to change frequency, thus controlling the capacity.
¡Allowing quick heating/cooling operation during start-up period. Constant room temperature by fine-tuned control after the unit
has stabilized.
(2) Fuzzy control
¡ Fuzzy control calculates the amount of variation in the difference between the return air temperature and the setting temperature
in compliance with the fuzzy rules in order to control the air capacity and the inverter frequency.
(3) Remote control flap & louver
The flap & louver can be automatically controlled by operating wireless remote control.
¡Flap swing : The flaps swing up and down successively. ¡Louver swing : The louvers swing left and right successively. ¡3D auto operation : Fan speed and air flow direction are automatically controlled, allowing the entire room to be efficiently
conditioned.
¡Memory flap : Once the flap & louver position is set, the unit memorizes the position and continues to operate at the
same position from the next time.
(4) Self diagnosis function
¡ We are constantly trying to do better service to our customers by installing such judges that show abnormality of operation as
follows.
Outdoor heat exchanger liquid pipe sensor error
Discharge pipe sensor error
Outdoor temperature sensor error
2 time flash
4 time flash
RUN light keeps flashing
1 time flash
Trouble of outdoor unit
Over current
Current cut
2 time flash
3 time flash
RUN light
ON
1 time flash
5 time flash
TIMER light
R410A models
Series No.
Inverter type
Product capacity
Wall mounted type
Split type room air-conditioner
1.2 How to read the model name
Example : SR K 35 Z G - S
Room temperature sensor error
Indoor fan motor error
Heat exchanger sensor error
2 time flash
6 time flash
TIMER light
ON
1 time flash
RUN light
Rotor lock
6 time flash
7 time flash
2 time flash
RUN light
2 time flash
4 time flash
Power transistor error
-
2
-
Item
Model
SRK20ZG-S SRC20ZG-S
Cooling capacity
(1)
W 2000 (500~2800)
Heating capacity
(1)
W 2700 (500~4600)
Power source 1 Phase, 220-240V, 50Hz
Cooling input kW 0.44 (0.1~0.91) Running current (Cooling) A 2.4/2.3/2.2 Heating input kW 0.62 (0.09~1.27) Running current (Heating) A 3.0/2.9/2.8 Inrush current A 3.0/2.9/2.8 COP Cooling: 4.55 Heating: 4.35
Cooling
Sound level Hi 35, Me 29, Lo 21 44
Noise level
Power level
dB
51 58
Heating
Sound level Hi 35, Me 32, Lo 25 45
Power level 53 59
Exterior dimensions
Height × Width × Depth
mm
268 × 790 × 199 540 × 780 × 290
Color Fine snow Stucco white Net weight kg 8.5 35 Refrigerant equipment
Compressor type & Q’ty
RM-B5077MD1 (Rotary type) × 1
Motor kW 0.75
Starting method Line starting Heat exchanger Louver fins & inner grooved tubing Straight fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Refrigerant
(3)
kg R410A 0.9 (Pre-Charged up to the piping length of 15m) Refrigerant oil R 0.35 (MA68) Deice control Microcomputer control
Air handling equipment
Fan type & Q’ty
Tangential fan × 1 Propeller fan × 1
Motor W 38 24
(Cooling) 7.4 30
Air flow (at High)
(Heating)
CMM
8.5 23
Air filter, Q’ty Polypropylene net (washable) × 2–
Shock & vibration absorber Cushion rubber (for compressor) Electric heater –– Operation control
Operation switch
Wireless-Remote control
Room temperature control Microcomputer thermostat Pilot lamp RUN (Green), TIMER (Yellow), HI POWER (Green), 3D AUTO (Green)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4) Gas line: φ9.52 (3/8″) Connecting method Flare connecting Attached length of piping Liquid line: 0.4 m
Gas line : 0.33 m
Insulation Necessary (Both sides) Drain hose Connectable Power source cord 2 m (3 cores with Earth)
Size × Core number 1.5 mm2 × 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit, Clean filter (Allergen clear filter x1, Photocatalytic washable deodorizing filter x1)
Optional parts Interface kit
Notes (1) The data are measured at the following conditions.
2 SELECTION DATA
2.1 Specifications
Model SRK20ZG-S (Indoor unit)
SRC20ZG-S (Outdoor unit)
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612
Heating 20ºC 7ºC 6ºC ISO-T1, JIS C9612
(2) The operation data are applied to the 220/230/240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even for the short piping.)
(4) If the interface kit (SC-BIK-E) (sold separately) is connected to the terminals on the indoor unit’s circuit board, a wired remote control (sold separately)
can be connected, a Super Link can be connected, and the unit can be turned on and off from a CNT terminal.
Operation data
(1)
Refrigerant
piping
Compressor overheat protection, Heating overload protection (High pressure control), Overcurrent protection, Frost protection, Serial signal error protection, Indoor fan motor error protection, Cooling overload protection
The piping length is 7.5m.
(220/230/240V)
-
3
-
Item
Model
SRK25ZG-S SRC25ZG-S
Cooling capacity
(1)
W 2500 (500~3000)
Heating capacity
(1)
W 3400 (500~4800)
Power source 1 Phase, 220-240V, 50Hz
Cooling input kW 0.62 (0.1~0.97)
Running current (Cooling) A 3.1/3.0/2.9
Heating input kW 0.93 (0.09~1.30)
Running current (Heating) A 4.5/4.3/4.1
Inrush current A 4.5/4.3/4.1
COP Cooling: 4.03 Heating: 3.66
Cooling
Sound level Hi 36, Me 30, Lo 22 44
Noise level
Power level
dB
52 58
Heating
Sound level Hi 36, Me 33, Lo 26 47
Power level 54 62
Exterior dimensions
Height × Width × Depth
mm
268 × 790 × 199 540 × 780 × 290
Color Fine snow Stucco white Net weight kg 8.5 35 Refrigerant equipment
Compressor type & Q’ty
RM-B5077MD1 (Rotary type) × 1
Motor kW 0.75
Starting method Line starting
Heat exchanger Louver fins & inner grooved tubing Straight fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Refrigerant
(3)
kg R410A 0.9 (Pre-Charged up to the piping length of 15m) Refrigerant oil R 0.35 (MA68) Deice control Microcomputer control
Air handling equipment
Fan type & Q’ty
Tangential fan × 1 Propeller fan × 1
Motor W 38 24
(Cooling) 7.6 30
Air flow (at High)
(Heating)
CMM
8.7 23
Air filter, Q’ty Polypropylene net (washable) × 2–
Shock & vibration absorber Cushion rubber (for compressor) Electric heater –– Operation control
Operation switch
Wireless-Remote control
Room temperature control Microcomputer thermostat Pilot lamp RUN (Green), TIMER (Yellow), HI POWER (Green), 3D AUTO (Green)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4) Gas line: φ9.52 (3/8″) Connecting method Flare connecting Attached length of piping Liquid line: 0.4 m
Gas line : 0.33 m
Insulation Necessary (Both sides) Drain hose Connectable Power source cord 2 m (3 cores with Earth)
Size × Core number 1.5 mm2 × 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit, Clean filter (Allergen clear filter x1, Photocatalytic washable deodorizing filter x1)
Optional parts Interface kit
Notes (1) The data are measured at the following conditions.
Model SRK25ZG-S (Indoor unit)
SRC25ZG-S (Outdoor unit)
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612
Heating 20ºC 7ºC 6ºC ISO-T1, JIS C9612
(2) The operation data are applied to the 220/230/240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even for the short piping.)
(4) If the interface kit (SC-BIK-E) (sold separately) is connected to the terminals on the indoor unit’s circuit board, a wired remote control (sold separately)
can be connected, a Super Link can be connected, and the unit can be turned on and off from a CNT terminal.
Operation data
(1)
Refrigerant
piping
Compressor overheat protection, Heating overload protection (High pressure control), Overcurrent protection, Frost protection, Serial signal error protection, Indoor fan motor error protection, Cooling overload protection
The piping length is 7.5m.
(220/230/240V)
-
4
-
Item
Model
SRK35ZG-S SRC35ZG-S
Cooling capacity
(1)
W 3500 (500~3900)
Heating capacity
(1)
W 4200 (500~5100)
Power source 1 Phase, 220-240V, 50Hz
Cooling input kW 1.05 (0.1~1.22)
Running current (Cooling) A 4.9/4.7/4.5
Heating input kW 1.14 (0.09~1.32)
Running current (Heating) A 5.3/5.1/4.9
Inrush current A 5.3/5.1/4.9
COP Cooling: 3.33 Heating: 3.68
Cooling
Sound level Hi 40, Me 32, Lo 23 48
Noise level
Power level
dB
56 62
Heating
Sound level Hi 41, Me 36, Lo 27 50
Power level 59 64
Exterior dimensions
Height × Width × Depth
mm
268 × 790 × 199 540 × 780 × 290
Color Fine snow Stucco white Net weight kg 8.5 38 Refrigerant equipment
Compressor type & Q’ty
RM-B5077MD1 [Rotary type] × 1
Motor kW 0.90
Starting method Line starting
Heat exchanger Louver fins & inner grooved tubing Straight fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Refrigerant
(3)
kg R410A 1.1 (Pre-Charged up to the piping length of 15m) Refrigerant oil R 0.35 (MA68) Deice control Microcomputer control
Air handling equipment
Fan type & Q’ty
Tangential fan × 1 Propeller fan × 1
Motor W 38 24
(Cooling) 8.5 30
Air flow (at High)
(Heating)
CMM
10.8 33
Air filter, Q’ty
Polypropylene net (washable) × 2
Shock & vibration absorber Cushion rubber (for compressor) Electric heater –– Operation control
Operation switch
Wireless-Remote control
Room temperature control Microcomputer thermostat Pilot lamp RUN (Green), TIMER (Yellow), HI POWER (Green), 3D AUTO (Green)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4) Gas line: φ9.52 (3/8″) Connecting method Flare connecting Attached length of piping Liquid line: 0.4 m
Gas line : 0.33 m
Insulation Necessary (Both sides) Drain hose Connectable Power source cord 2 m (3 cores with Earth)
Size × Core number 1.5 mm2 × 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit, Clean filter (Allergen clear filter x1, Photocatalytic washable deodorizing filter x1)
Optional parts Interface kit
Notes (1) The data are measured at the following conditions.
Model SRK35ZG-S (Indoor unit)
SRC35ZG-S (Outdoor unit)
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612
Heating 20ºC 7ºC 6ºC ISO-T1, JIS C9612
(2) The operation data are applied to the 220/230/240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even for the short piping.)
(4) If the interface kit (SC-BIK-E) (sold separately) is connected to the terminals on the indoor unit’s circuit board, a wired remote control (sold
separately) can be connected, a Super Link can be connected, and the unit can be turned on and off from a CNT terminal.
Operation data
(1)
Refrigerant
piping
Compressor overheat protection, Heating overload protection (High pressure control), Overcurrent protection, Frost protection, Serial signal error protection, Indoor fan motor error protection, Cooling overload protection
The piping length is 7.5m.
(220/230/240V)
-
5
-
Model SRK50ZG-S (Indoor unit)
SRC50ZG-S (Outdoor unit)
Item
Model
SRK50ZG-S SRC50ZG-S
Cooling capacity
(1)
W 5000 (600~5300)
Heating capacity
(1)
W 5800 (600~7900)
Power source 1 Phase, 220-240V, 50Hz
Cooling input kW 1.66 (0.12~2.1)
Running current (Cooling) A 7.6/7.3/7.0
Heating input kW 1.70 (0.11~2.71)
Running current (Heating) A 7.9/7.5/7.2
Inrush current A 7.9/7.5/7.2
COP Cooling: 3.01 Heating: 3.41
Cooling
Sound level Hi 47, Me 42, Lo 26 48
Noise level
Power level
dB
61 61
Heating
Sound level Hi 48, Me 40, Lo 34 50
Power level 62 64
Exterior dimensions
Height × Width × Depth
mm
268 × 790 × 199 640 × 850 × 290
Color Fine snow Stucco white Net weight kg 8.5 43 Refrigerant equipment
Compressor type & Q’ty
5CS102XFA [Scroll type] × 1
Motor kW 1.5
Starting method Line starting
Heat exchanger Slit fins + Louver fins & inner grooved tubing Straight fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Refrigerant
(3)
kg R410A 1.35 (Pre-Charged up to the piping length of 15m) Refrigerant oil R 0.36 (RB68A) Deice control Microcomputer control
Air handling equipment
Fan type & Q’ty
Tangential fan × 1 Propeller fan × 1
Motor W 38 34
(Cooling) 11.5 42
Air flow (at High)
(Heating)
CMM
13.0 42
Air filter, Q’ty
Polypropylene net (washable) × 2
Shock & vibration absorber Cushion rubber (for compressor) Electric heater –– Operation control
Operation switch
Wireless-Remote control
Room temperature control Microcomputer thermostat Pilot lamp RUN (Green), TIMER (Yellow), HI POWER (Green), 3D AUTO (Green)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4) Gas line: φ12.7 (1/2″) Connecting method Flare connecting Attached length of piping Liquid line: 0.4 m
Gas line : 0.33 m
Insulation Necessary (Both sides) Drain hose Connectable Power source cord 2 m (3 cores with Earth)
Size × Core number 1.5 mm2 × 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit, Clean filter (Allergen clear filter x1, Photocatalytic washable deodorizing filter x1)
Optional parts Interface kit
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612
Heating 20ºC 7ºC 6ºC ISO-T1, JIS C9612
(2) The operation data are applied to the 220/230/240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even for the short piping.)
If the piping length is longer, when it is 15 to 25m, add 20 g refrigerant per meter.
(4) If the interface kit (SC-BIK-E) (sold separately) is connected to the terminals on the indoor unit’s circuit board, a wired remote control (sold
separately) can be connected, a Super Link can be connected, and the unit can be turned on and off from a CNT terminal.
Operation data
(1)
Refrigerant
piping
Compressor overheat protection, Heating overload protection (High pressure control), Overcurrent protection, Frost protection, Serial signal error protection, Indoor fan motor error protection, Cooling overload protection
The piping length is 7.5m.
(220/230/240V)
-
6
-
2.2 Range of usage & limitations
2.3 Exterior dimensions
(1) Indoor unit
Models SRK20ZG-S, 25ZG-S, 35ZG-S, 50ZG-S
Indoor return air temperature (Upper, lower limits)
Refrigerant line (one way) length Max. 15m
SRK20ZG-S, 25ZG-S, 35ZG-S SRK50ZG-S
Cooling operation : Approximately 18 to 32˚C Heating operation : Approximately 15 to 30˚C
Cooling operation : Approximately -15 to 46˚C Heating operation : Approximately -15 to 21˚C
Power source voltage Rating ± 10%
Voltage at starting Min. 85% of rating
Frequency of ON-OFF cycle
Max. 7 times/h
(Inching prevention 5 minutes)
Max. 4 times/h
(Inching prevention 10 minutes)
ON and OFF interval Max. 3 minutes
Outdoor air temperature (Upper, lower limits)
Vertical height difference between outdoor unit and indoor unit
Max. 10m (Outdoor unit is higher) Max. 10m (Outdoor unit is lower)
Max. 25m
Max. 15m (Outdoor unit is higher) Max. 15m (Outdoor unit is lower)
Item
Models
Unit: mm
Piping hole (ø65)
( )
Piping hole (ø65)
53.5
380.6
Pipng for Liquid 448.6 (ø6.35)
20, 25, 35 : ø9.52 50 : ø12.7
Pipng for Gas
Drain hose 520 (ø16)
53.5
44.5
252.2
7.5
8.3
102.5
585
102.5
133.5450206.5
202450138
44.5
43.2
39.3
200
45
45
60
17.5
60
27
788
60
9
45
199
3
Terminal block
Piping hole right(left)
268
790
A
VIEW A
-
7
-
Drain holes
286.4
12
50
290
49.6
43.5
850
203.1
510 136.9
476
2-16×12
314
12
328
Terminal block
Service valve (Liquid)
ø6.35 (1/4'')
Service valve (Gas)
ø12.7 (1/2'')
Ground terminal
124
34.6
20˚
20˚
42.7
100.3
15
640
14
Model SRC50ZG-S
Unit: mm
(2) Outdoor unit
Models SRC20ZG-S, 25ZG-S, 35ZG-S
2-16×12
Drain holes (ø20)
138.4
40
˚
61.9
18.9165.1510104.9
439.1
111.4
99.4
349.5
313.1
43.1
290
12
50
350
23.5312.5
14
33.5
40
˚
42.595.9
14
540
780
Service valve (Liquid)
Flare connection ø6.35 (1/4'')
Service valve (Gas)
Flare connection ø9.52 (3/8'')
Terminal block
-
8
-
2.4 Piping system
Models SRK20ZG-S, 25ZG-S, 35ZG-S
Outdoor unitIndoor unit
Room temp. sensor
Heat exchanger
Flare connection
Heat exchanger sensor
Piping (Liquid) ø6.35
Check joint
4 way valve
Service valve (Liquid)
Flare connetion
Discharge pipe temp. sensor
Cooling cycle
Heating cycle
Outdoor air temp. sensor
Heat exchanger
Heat exchanger sensor
Compressor
Capillary tube
Strainer
Accumulator
Service valve (Gas)
Electronic expansion valve
Piping (Gas) ø9.52
Model SRK50ZG-S
Outdoor unitIndoor unit
Room temp. sensor
Heat exchanger
Flare connection
Heat exchanger sensor
Piping (Liquid) ø6.35
Check joint
4 way valve
Service valve (Liquid)
Flare connection
Discharge pipe temp. sensor
Cooling cycle
Heating cycle
Outdoor air temp. sensor
Heat exchanger
Heat exchanger sensor
Compressor
Capillary tube
Strainer
Strainer
Service valve (Gas)
Capillary tube
Electronic expansion valve
Piping (Gas)
ø12.7
Muffler
Capillary tube
Muffler
Humidity sensor (35 type only)
Humidity sensor
-
9
-
2.5 Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be
obtained in the following way.
Net capacity = Capacity shown on specificationCorrection factors as follows.
(1) Coefficient of cooling and heating capacity in relation to temperatures
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way piping length between the indoor and outdoor units.
(3) Correction relative to frosting on outdoor heat exchanger during heating
In additions to the foregoing corrections (1), (2) the heating capacity needs to be adjusted also with respect to the frosting on the outdoor heat exchanger.
How to obtain the cooling and heating capacity
Example : The net cooling capacity of the model SRK20ZG-S with the piping length of 15m, indoor wet-bulb temperature at 19.0˚C
and outdoor dry-bulb temperature 35˚C is Net cooling capacity = 2000 0.975 1.0 = 1950 W
Length 15m
Factor by air temperatures
Piping length [m]
Cooling
Heating
7
1.0
1.0
10
0.99
1.0
15
0.975
1.0
20
0.965
1.0
25
0.95
1.0
SRK20ZG-S
Cooling
Heating
2220181614
0.6
0.7
0.8
0.9
1.0
1.2
1.1
1.3
0
-5
-10
-15
Applicable range
Depends on installed situation
24
26
20
25
30
35
40
46
10
15
20
25
27
Outdoor air W.B. temperature ˚C W.B.
-15 -10 -5 0 5 10 15
Indoor air W.B. temperature ˚C W.B.
ISO-T1 Standard Condition
Cooling operation
Outdoor air D.B.
temperature
˚CD. B.
Coefficient of cooling &
Heating capacity in
relation to temperature
Heating operation
Indoor air D.B.
temperature
˚CD. B.
ISO-T1 Standard Condition
Air inlet temperature of
outdoor unit in ˚C WB
Adjustment coefficient
-10
0.95-90.94-70.93-50.91-30.88-10.8610.8730.9251.00
-
10
-
3 ELECTRICAL DATA
3.1 Electrical wiring
Models SRK20ZG-S, 25ZG-S, 35ZG-S
+
~~
-
+
+
+
Indoor unit Outdoor unit
BL Y
WH BK RD
FM
I
6
CNU
1
3
4
5
CNM
5
SM
52C
CNX
5
LM
1
LM
2
CNY
5
R-AMP
WIRELESS
DISPLAY
Th
1
Th
2
Th
3
CNE
BACK UP SW
8
BOARD
PRINTED CIRCUIT
PRINTED CIRCUIT BOARD
CNG
22
(35 TYPE ONLY)
2
CNF
250V 3.15A
F
52C
ZNR
52C-4 52C-3NGJ
1
3
2/N
1
3
2/N
Y/GN
RD WH
BK
RD
WH
BK
BR
WH
BK
Y/GN
RD
EXCHANGER
HEAT
BR
LB
Y/GN
220/230/240V 50Hz
1 Phase
POWER SOURCE
BOX
CONTROL
U
TB TB
250V 15A
F
R.IN C-2S.IN
N
P
POWER
TRANSISTOR
U
V
W
RD
WH
BK
CM
CND
Th
4
Th
5
Th
6
CNA
FM
O
CNB
20S
EEV
DS
L
G
G
CNE
BK BL BR
Y
WH
LB
Y/G
RD
Color symbol
Black Blue Brown
Yellow
White
Light blue
Yellow/Green
Red
Meaning of marks
Symbol
Parts name
Symbol
Parts name
Symbol
Parts name
CM F FM
I
FM
O
SM LM
1
Th
1
Th
2
Compressor motor Fuse Fan motor(Indoor) Fan motor(Outdoor) Flap motor Louver motor(L)
LM
2
Louver motor(R)
Room temp.sensor Heat exch.sensor(Indoor unit)
Th
3
Th
4
Th
5
Th
6
ZNR
20S EEV DSHumidity sensor
Heat exch.sensor(Outdoor unit)
TB Terminal blockOutdoor air temp.sensor Discharge pipe temp.sensor Varistor
4 way valve(coil) Electronic expansion valve Diode stack
L Inductor
-
11
-
Model SRK50ZG-S
Indoor unit Outdoor unit
BL Y
WH BK RD
FM
I
6
CNU
1
3
4
5
CNM
5
SM
CNX
5
LM
1
LM
2
CNY
5
R-AMP
WIRELESS
DISPLAY
Th
1
Th
4
Th
5
Th
6
Th
2
Th
3
CNE
BACK UP SW
8
BOARD
PRINTED CIRCUIT
CNG
22 2
CNF
250V 3.15A
250V 15A
F
52C
ZNR
52C-4 52C-3NGJ
1
3
2/N
1
3
2/N
Y/GN
RD WH
BK
RD
WH
BK
BR
WH
BK
Y/GN
RD
EXCHANGER
HEAT
BR
LB
Y/GN
220/230/240V 50Hz
1 Phase
POWER SOURCE
BOX
CONTROL
U
TB TB
F
BK BL BR
Y
WH
LB
Y/G
RD
Color symbol
Black Blue Brown
GR Gray
Yellow
White
Light blue
OR Orange
Yellow/Green
Red
Meaning of marks
Symbol
Parts name
Symbol
Parts name
Symbol
Parts name
CM F FM
I
FM
O
SM LM
1
Th
1
Th
2
Compressor motor Fuse Fan motor(Indoor) Fan motor(Outdoor) Flap motor Louver motor(L)
LM
2
Louver motor(R)
Room temp.sensor Heat exch.sensor(Indoor unit)
Th
3
Th
4
Th
5
Th
6
ZNR
20S
EEV
DSHumidity sensor Heat exch.sensor(Outdoor unit)
TB
Terminal block
Outdoor air temp.sensor Discharge pipe temp.sensor Varistor
4 way valve(coil) Electronic expansion valve Diode stack
L Inductor
FM
O
20S
CNT
CNB
CND
EEV
CNJ
CNI
CNH CNH
CNGCNG
PWB1(MAIN)
PWB2(POWER)
AF_L2
AF_L1
V
W
U
BK
WH
RD
OR
OROR
OR
BK
RD
WH
L
CM
N_1
P_1
AC.N
AC.L
AC.N AC.L
BL
GR
BL
GR
BK
RD
N_1
P_1
DC-N
DC-P
CNG
PWB3(CAPACITOR)
BK
RD
L-1G3 N-1 CNO.1
Y/G
52C
-
12
-
Models All models
Remote control
S Operation section
4
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
4.1 Operation control function by remote control switch
RUN TIMER
ON / OFF
HI POWER 3D AUTO
ON
OFF
1.5 sec.
0.5 sec.
3D AUTO light (green)
Illuminates during 3D AUTO operation.
HI POWER light (green)
Illuminates during HIGH POWER operation.
RUN (HOT KEEP) light (green)
Illuminates during operation and CLEAN
operation.
Blinks at air flow stop due to the ‘HOT KEEP’.
TIMER light (yellow)
Illuminates during TIMER operation.
In emergencies, this button can be used for turning on/off the unit when remote control is not available.
Remote control signal receiver
Unit ON/OFF button
FAN SPEED button
Each time the button is pushed, the indicator is switched over in turn.
The above illustration shows all controls, but in practice only the relevant parts are shown.
OPERATION MODE select button
Each time the button pushed, the indicator is switched over in turn.
ON/OFF (luminous) button
Press for starting operation, press again for stopping.
HI POWER/ECONO button
This button changes the HIGH POWER/ ECONOMY mode.
AIR FLOW (UP/DOWN) button
This button changes the air flow (up/down) mode.
This button changes the air flow (left/right) mode.
SLEEP button
This button selects to SLEEP operation.
CLEAN switch
This switch changes the CLEAN mode.
ON TIMER button
This button selects ON TIMER operation.
AIR FLOW (LEFT/RIGHT) button
3D AUTO button
This button sets 3D AUTO operation.
This button selects ALLERGEN CLEAR operation.
ALLERGEN CLEAR button
RESET switch
Switch for resetting microcomputer and setting time.
OFF TIMER button
This button selects OFF TIMER operation.
TEMPERATURE button
This button sets the room temperature. (This button changes the present time and TIMER time.)
This button cancels the ON timer, OFF timer, and SLEEP operation.
CANCEL button
Unit indication section
Models All models
-
13
-
Unit ON/OFF button
4.2 Unit ON/OFF button
When the remote control batteries become weak, or if the remote control is lost or malfunctioning, this button may be used to turn the
unit on and off.
(1) Operation
Push the button once to place the unit in the automatic mode. Push it once more to turn the unit off.
(2) Details of operation
The unit will go into the automatic mode in which it automatically determines, from room temperature (as detected by sensor),
whether to go into the cooling, thermal dry or heating modes.
Function
Room temperature
Operation mode
setting
Fan speed
Flap
Timer switch
Cooling About 24ºC
Thermal dry About 24ºC Auto Auto Continuous
Heating About 26ºC
4.3 Power blackout auto restart function
(1) Power blackout auto restart function is a function that records the operational status of the air-conditioner immediately prior to it
being switched off by a power cut, and then automatically resumes operations at that point after the power has been restored.
(2) The following settings will be cancelled:
(a) Timer settings
(b) High-power operations
Notes (1) The power blackout auto restart function is set at on when the air-conditioner is shipped from the
factory. Consult with your dealer if this function needs to be switched off.
(2) When power failure ocurrs, the timer setting is cancelled. Once power is resumed, reset the timer.
(3)
If the jumper wire (J12) “AUTO RESTART” is cut, auto restart is disabled. (See the diagram at right)
4.4 Custom cord switching procedure
If two wireless remote controls are installed in one room, in order to prevent wrong operation
due to mixed signals, please modify the printed circuit board in the indoor unit’s control box
and the remote control using the following procedure. Be sure to modify both boards. If only
one board is modified, receiving (and operation) cannot be done.
(1) Modifying the indoor unit’s printed circuit board
Take out the printed circuit board from the control box and cut off jumper wire (J13)
using wire cutters.
After cutting of the jumper wire, take measures to prevent contact with the other the lead
wires, etc.
(2) Modifying the wireless remote control
(a) Remove the battery.
(b) Cut the jumper wire shown in the figure at right.
Jumper wire (J12)
Jumper wire (J13)
Cut
-
14
-
4.5 Flap and louver control
Control the flap and louver by AIRFLOW
 
(UP/DOWN) and

(LEFT/RIGHT) button on the wireless remote control.
(1) Flap
Each time when you press the AIRFLOW
 
(UP/DOWN) button the mode changes as follows.
(2) Louver
Each time when you press the AIRFLOW

(LEFT/RIGHT) button the mode changes as follows.
(3) Swing
(a) Swing flap
Flap moves in upward and downward
directions continuously.
(b) Swing louver
Louver moves in left and right directions continuously.
(4) Memory flap (Flap or Louver stopped)
When you press the AIRFLOW (UP/DOWN or LEFT/RIGHT) button once while the flap or louver is operating, it stops swinging
at an angle. Since this angle is memorized in the microcomputer, the flap or louver will automatically be set at this angle when the
next operation is started.
(5) When not operating
The flap returns to the position of air flow directly below, when operation has stopped.
COOL , DRY
Remote control display
HEAT
Angle of Flap from Horizontal
Approx. 10
˚
Approx. 20˚
Approx. 20˚
Approx. 35˚
Approx. 30˚
Approx. 50˚
Approx. 45˚
Approx. 60˚
Approx. 60˚
Approx. 70˚
(Swing)
(Flap stopped)
Center installation
Remote control display
Right end installation
Left end installation
Angle of Louver
Left Approx. 45˚
Left Approx. 45˚
Left Approx. 20˚
Left Approx. 30˚
Center
Left Approx. 20˚
Right Approx. 20˚
Center
Right Approx. 45˚
Right Approx. 20˚
Left Approx. 20˚
Center
Right Approx. 20˚ Right Approx. 30˚ Right Approx. 45˚
(Louver stopped)
(Swing) (Spot) (Wide)
S In HEAT operation S In COOL, DRY operation S In HEAT operation S In COOL, DRY operation
Approx. 30˚
Approx. 70˚
Approx.
10˚
Approx. 30˚
-
15
-
4.6 3D auto operation
Control the flap and louver by 3D AUTO button on the wireless remote control.
Air flow selection and air flow direction are automatically controlled, allowing the entire room to efficiently conditioned.
(1) During Cooling and Heating (Including auto cooling and heating)
(a) Air flow selection is determined according to room temperature and setting temperature.
(b) Air flow direction is controlled according to the room temperature and setting temperature.
1) When 3D auto operation starts
2) When Room temp. – Setting temp. is ≤_ 5ºC during cooling and when Setting temp. – Room temp. is ≤_ 5ºC during
heating, the system switches to the following air flow direction control. After the louver swings left and right symmetrically
for 3 cycles, control is switched to the control in 3).
3) After the flap swings for 5 cycles, control is switched to the control in 4).
4) For 5 minutes, the following air flow direction control is carried out.
5) After 5 minutes have passed, the air flow direction is determined according to the room temperature and setting
temperature.
(2) During DRY Operation (including auto DRY operation)
At cooling
Air flow selection
Operation mode
AUTO HI MED LO
At heating
Room temp. – Setting temp. >5˚C Room temp. – Setting temp. ≤_ 5˚C
Setting temp. – Room temp. >5˚C Setting temp. – Room temp. ≤_ 5˚C
HIGH POWER AUTO
HI MED LO
HIGH POWER AUTO
Flap Louver
Cooling
Up/down Swing
Heating
Wide (fixed) Center (fixed)
Flap Louver
Cooling Heating
Left/right Swing
Horizontal blowing (Fixed) Slant forwardl blowing (Fixed)
Flap Louver
Cooling
Up/down Swing
Heating
Center (Fixed)
Wide (Fixed)
Flap Louver
Cooling Heating
Horizontal blowing (Fixed) Slant forwardl blowing (Fixed)
Operation mode
Room temp. – Setting temp. ≤_ 2˚C
Setting temp. – Room temp. ≤_ 2˚C
At heating
At cooling
Air flow direction contorol
2˚C < Setting temp.
Room temp. ≤_ 5˚C
2˚C < Room temp.
Setting temp. ≤_ 5˚C
Room temp. – Setting temp. > 5˚C
Setting temp. – Room temp. > 5˚C
The control in 4) continues. Control returns to the control in 2). Control returns to the control in 1).
The control in 4) continues. Control returns to the control in 2). Control returns to the control in 1).
Wide (Fixed)
Flap
Air flow selection
Louver
According to DRY operation.
Horizontal blowing (Fixed)
-
16
-
(2) Sleep timer operation
Pressing the SLEEP button causes the temperature to be controlled as shown in the following chart with respect to the set tempera-
ture.
4.7 Timer operation
(1) Comfortable timer setting (ON timer)
(3) OFF timer operation
The Off timer can be set at a specific time (in 10-minute units) within a 24-hour period.
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the relationship between the room temperature at the setting time (temperature of room temperature sensor) and the
setting temperature.
4.8 Installation location setting
When the indoor unit is installed at the end of a room, control the air flow direction so that it is not toward the side walls. If you set the
remote control’s installation position, keep it so that the air flow is within the range shown in the following figure.
(1) Setting
1 If the air conditioning unit is running, press the ON/OFF button to stop.
The installation location setting cannot be made while the unit is running.
2 Press the AIR FLOW
 
(UP/DOWN) button and the
AIRFLOW

(LEFT/RIGHT) button together for 5 seconds
or more.
The installation location display illuminates.
3 Setting the air-conditioning installation location.
Press the AIR FLOW

(LEFT/RIGHT) button and adjust to the desired
location.
Each time the AIR FLOW

(LEFT/RIGHT) button is pressed, the
indicator is switched in the order of:
4 Press the ON/OFF button.
The air-conditioner's installation location is set.
Press within 60 seconds of setting the installation location (while the
installation location setting display illuminates).
Airflow range Airflow range Airflow range
(Left End Installation) (Center Installation) (Right End Installation)
1, 4
2 3
(Center Installation) (Right End Installation) (Left End Installation)
-
17
-
4.9 Outline of heating operation
(1) Operation of major functional components in heating mode
(2) Details of control at each operation mode (pattern)
(a) Fuzzy operation
Deviation between the room temperature setting correction temperature and the suction air temperature is calculated in accordance with the fuzzy rule, and used for control of the air capacity and the inverter speed.
When the defrosting, protection device, etc. is actuated, operation is performed in the corresponding mode.
(b) Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor blower is controlled based on the temperature of the indoor unit heat exchanger (detected with Th2, indoor unit heat exchanger sensor) to prevent blowing of cool wind.
ON OFF OFF
ON ON OFF
ON
OFF
(few minutes ON)
OFF
ON ON(HOT KEEP) OFF
OFF
OFF
(3 minutes ON)
OFF
OFF
Thermostat ON Thermostat OFF Defrost Failure
Heating
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
30~100rps 30~102rps 15~122rps
30~100rps 30~102rps 15~122rps
30~70rps 30~72rps 30~84rps 15~84rps
30~44rps 30~54rps 30~62rps 15~66rps
SRK20ZG-S
Model
Fan speed
SRK25ZG-S SRK35ZG-S SRK50ZG-S
Auto
MED
HI
LO
(3) Defrosting operation
(a) Starting conditions (Defrosting operation can be started only when all of the following conditions are met.)
1 After start of heating operation
When it elapsed 45 minutes (35, 50 type : 35 minutes). (Accumulated compressor operation time)
2 After end of defrosting operation
When it elapsed 45 minutes(35, 50 type : 35 minutes). (Accumulated compressor operation time)
3 Outdoor unit heat exchanger sensor (Th4) temperature
When the temperature has been below –5ºC for 3 minutes continuously.
4 The difference between the outdoor air sensor temperature and the outdoor unit heat exchanger sensor temperature
¡ The outdoor air temperature _ -17°C : 7°C (35type : 5°C, 50type : 4°C) on higher ¡ The outdoor air temperature < -17°C : -5°C or higher
5 During continuous compressor operation
In addition, when the speed command from the indoor controller of the indoor unit during heating operation has counted
0 rps 10 times or more and all conditions of 1, 2, 3 and 5 above and the outdoor air temperature is 3°C or less are
satisfied (note that when the temperature for Th4 is -5°C or less: 62 rps or more, -4°C or less: less than 62 rps), defrost
operation is started.
(b) Ending conditions (Operation returns to the heating cycle when either one of the following is met.)
1 Outdoor heat exchanger sensor (Th4) temperature: 13ºC or higher
2 Continued operation time of defrosting For more than 10 min.
-
18
-
27.5
25.5
19.5
18
30
4.10 Outline of cooling operation
(1) Operation of major functional components in Cooling mode
(2) Detail of control in each mode (Pattern)
(a) Fuzzy operation
During the fuzzy operation, the air flow and the inverter speed are controlled by calculating the difference between the room
temperature setting correction temperature and the suction air temperature.
ON OFF OFF
OFF OFF OFF
ON
OFF
(few minutes ON)
OFF
(few minutes ON)
ON ON ON
Thermostat ON Thermostat OFF Failure
Cooling
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
20~64rps 20~68rps 15~100rps
20~64rps 20~68rps
20~98rps
20~98rps 15~100rps
20~48rps 20~52rps 20~74rps 15~62rps
20~32rps 20~38rps 20~46rps 15~30rps
SRK20ZG-S
Model
Fan speed
SRK25ZG-S SRK35ZG-S SRK50ZG-S
Auto
MED
HI
LO
4.11 Outline of automatic operation
(1) Determination of operation mode
The unit checks the room temperature and the outdoor air temperature, determines the operation mode, and then begins in the
automatic operation.
Heating
Dehumidifying
Cooling
Room temperature (˚C)
Outdoor temperature (˚C)
(2) The unit checks the temperature every hour after the start of operation and, if the result of check is not same as the previous
operation mode, changes the operation mode.
(3) When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is selected
during heating, cooling or dehumidifying operation, the unit is operated in the previous operation mode.
(4) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the signals of the
wireless remote control and the setting temperature.
Signals of wireless remote control (Display)
–6 –5 –4 –3 –2 –1 ±0+1+2+3+4+5+6
Setting
Cooling 18 19 20 21 22 23 24 25 26 27 28 29 30
temperature
Dehumidifying 18 19 20 21 22 23 24 25 26 27 28 29 30
Heating 20 21 22 23 24 25 26 27 28 29 30 31 32
-
19
-
4.12 Protective control function
(1) Frost prevention for indoor heat exchanger (During cooling or dehumidifying)
(a) Operating conditions
1) Indoor heat exchanger temperature (detected with Th2) is lower than 5ºC.
2) 10 minutes after reaching the inverter command speed except 0 rps.
(b) Detail of anti-frost operation
5°C or lower 2.5°C or lower
Item
20, 25 type : 44 rps
Upper limit speed 35 type : 70 rps 0rps
50 type : 76 rps
Indoor fan Depends on operation mode
Protects the fan tap just before
frost prevention control
Outdoor fan Depends on operation mode
Depends on stop mode
4-way valve OFF
(c) Reset conditions: The indoor heat exchanger temperature (Th2) is 8ºC or higher after 5 minutes of operation following
control of the inverter command speed upper limit.
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature (°C)
2.5 5 8
0 rps
Upper
limit
speed
Inverter
command
speed
(2) Cooling overload protective control
(a) Operating conditions: When the outdoor unit is operating with the outdoor unit speed of other than 0 rps, and when the
outdoor air temperature sensor (Th5) becomes 41ºC or over for 30 seconds continuously.
(b) Detail of operation
1) Outdoor fan is stepped up by 3 speed step. (Upper limit speed is 7th speed.)
2) The lower limit of control speed is set to 30 rps and even if the calculated result becomes lower than that after fuzzy
calculation, the speed is kept to 30 rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
(c) Reset conditions: When either of the following condition is satisfied.
1 When the outdoor air temperature becomes 40ºC or less.
2 When the inverter command speed is 0rps.
(3) Cooling low outdoor temperature protective control
< I >
(a) Operating conditions: When the outdoor air temperature sensor (Th5) is 22ºC or lower continues for 30 seconds while
outdoor speed is other than 0rps.
(b) Detail of operation: After the outdoor fan operates at A speed for 60 seconds; the corresponding outdoor heat
exchanger temperature shall implement the following controls.
1 Outdoor heat exchanger temperature
=
<
21ºC
After the outdoor fan speed drops (down) to one speed for 60 seconds; if the outdoor heat exchanger temperature is
lower than 21°C, gradually reduce the outdoor fan speed by 1 speed. (Lower limit speed is 1st speed)
2 21ºC < Outdoor heat exchanger temperature
=
<
38ºC
After the outdoor fan speed maintains at A speed for 20 seconds; if the outdoor heat exchanger temperature is 21°C~
38°C, maintain outdoor fan speed.
3 Outdoor heat exchanger tempeature > 38ºC
After the outdoor fan speed rises (up) to 1 speed for 60 seconds; if the outdoor heat exchanger temperature is
higher than 38°C, gradually increase outdoor fan speed by 1 speed. (Upper limit speed is 3rd speed)
(c) Reset conditions: When the either of the following conditions is satisfied
1 When the outdoor air temperature sensor (Th5) becomes 25ºC or higher. 2 When the inverter command speed is 0rps.
Outdoor temperature > 10˚C
Outdoor temperature ≤_ 10˚C
2nd speed
Outdoor fan
1st speed
¡ Value of A
-
20
-
< II >
(a) Operating conditions: When the outdoor air temperature sensor (Th5) is 22ºC or lower continues for 30 seconds while
outdoor speed is other than 0rps.
(b) Detail of operation:
1 The lower limit of inverter command speed is set to C(D)rps and even if the speed becomes lower than C(D)rps, the
speed is kept to C(D)rps. However, when the thermo becomes OFF, the speed is reduced to 0rps.
2 The upper limit of control speed is set to A(B)rps and even if the calculated result becomes higher than that after fuzzy
calculation, the speed is kept to A(B)rps.
22 25
OFF
03
Upper limit Arps Lower limit Crps
ON
ON
Upper limit Brps Lower limit Drps
Outdoor air temp.(°C)
20, 25, 35 type
50 type
40
A
Upper limit Lower limit
BCD
60 30 30
50 60 44 30
¡ Values of A, B, C, D
(c) Reset conditions: When the either of the following condition is satisfied
1 When the outdoor air temperature sensor (Th5) becomes 25ºC or higher.
2 When the inverter command speed is 0rps.
(4) High pressure control
(a) Purpose: Prevents anomalous high pressure operation during heating.
(b) Detector: Indoor unit heat exchanger sensor (Th2)
(c) Detail of operation:
A
B
C
D
Indoor unit heat exchanger temperature(˚C)
4rps
(1)
8rps
(2)
8rps
(2)
4rps
(1)
0rps
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
lower limit
speed 20(35) rps
(Example) Fuzzy
Notes (1) When the indoor unit heat exchanger temperature is in the range of B~C ºC, the speed is reduced by 4 rps at each 20 seconds.
(2) When the indoor unit heat exchanger temperature is in the range of C~D ºC, the speed is reduced by 8 rps at each 20 seconds. When the temperature is D
ºC or over for 1 minute continuously, the inverter is stopped.
(3) When the indoor unit heat exchanger temperature is in the range of A~B ºC, if the inverter command speed is been maintained and the operation has
continued for more than 20 seconds at the same speed, it returns to the normal heating operation.
(4) Indoor blower retains the fan tap when it enters in the high pressure control. Outdoor blower is operated in accordance with the speed.
Notes (1) RPSmin: The lower one between the outdoor unit speed and the command speed
Note (2) Values in ( ) are for Type 50.
¡ Temperature list
ABCD
RPSmin < 40(88) 48 (48.5) 53 (55) 55 (58) 58 (61)
40(88)
< =
RPSmin < 50(108)
48 (44) 53 (50.5) 55 (53) 58 (56.5)
50(108)
< =
RPSmin 48.5 (39) 56 (45.5) 58 (48) 61 (51.5)
Unit : ºC
-
21
-
(5) Heating overload protective control
(a) Operating conditions: When the unit is operating with the outdoor unit speed other than 0 rps or when the outdoor air
temperature sensor (Th5) rose beyond 22ºC for 30 seconds continuously.
(b) Detail of operation:
1 Taking the upper limit of control speed range at 60 rps, if the output speed obtained with the fuzzy calculation exceeds the
upper limit, the upper limit value is maintained.
2 The lower limit of control speed is set to 40(35) rps and even if the calculated result becomes lower than that after fuzzy
calculation, the speed is kept to 40(35) rps. However, when the thermo becomes OFF, the speed is reduced to 0 prs.
3 Inching prevention control is activated and inching prevention control is carried out with the minimum speed set at 40
(35) rps.
4 The outdoor fan is set on 2nd speed.
(c) Reset conditions: When the outdoor air temperature drops below 21ºC.
Note (1) Values in ( ) are for Type 50.
(6) Heating low outdoor temperature protective control
<I>
(a) Operating conditions: When the outdoor air temperature sensor (Th5) is 4ºC or lower continues for 5 minutes while the
outdoor speed is other than 0 rps.
(b) Detail of operation:
1 When the command speed is less than 40(22) rps, the command speed is forcibly set at 40(22) rps. However, when the
thermo becomes OFF, the speed is reduced 0 rps.
2 Inching prevention control is activated and inching prevention control is carried out with the minimum speed set at 40
(22) rps.
(c) Reset conditions: When the either of the following condition is satisfied.
1 When the outdoor air temperature sensor (Th5) becomes 6ºC or higher.
2 When the inverter command speed is 0 rps.
<II >
(a) Operating conditions: When the outdoor air temperature sensor (Th5) is 0ºC or lower continuously for 30 seconds while
the outdoor speed is other than 0 rps.
(b) Detail of operation: The outdoor fan motor speed is stepped up by 1(2) speed step. (Upper limit 7th speed)
(c) Reset conditions: When the either of the following condition is satisfied.
1 When the outdoor air temperature sensor (Th5) becomes 2ºC or higher.
2 When the inverter command speed is 0 rps.
<III > (SRK50ZG-S only)
(a) Operating conditions: When the outdoor heat exchanger sensor (Th4) is –10ºC or lower continuously for 10 minutes
while the outdoor speed is other than 0 rps.
(b) Detail of operation: When the command speed upper limit is set at 50 rps.
(c) Reset conditions: When the either of the following condition is satisfied.
1 When the outdoor heat exchanger sensor (Th4) becomes -7ºC or higher.
2 When the inverter command speed is 0 rps.
3 After 2 minutes have passed since this control started.
-
22
-
(7) Compressor overheat protection
(a) Purpose: It is designed to prevent deterioration of oil, burnout of motor coil and other trouble resulting from the compressor
overheat.
(b) Detail of operation
1) Speeds are controlled with temperature detected by the sensor mounted on the discharge pipe.
Discharge pipe temperature (˚C)
Lower limit
(4)
After lapse of 3 min. or over
(3)
After lapse of 3 min. or over
(3)
After lapse of 3 min. or over
(3)
4 rps
4 rps
(1)
0 rps
(Example) Fuzzy
90
(80)
100 (90)
125 (110)
Notes (1) When the discharge pipe temperature is in the range of 100(90) to 125(110)ºC, the speed is reduced by 4 rps.
(2) When the discharge pipe temperature is raised and continues operation for 20 seconds without changing, then the speed is reduced again by 4 rps.
(3) If the discharge pipe temperature is still 90 (80) ºC or greater but less than 100 (90) ºC even when the inverter command speed is maintained for 3
minutes when the temperature is 90 (80) ºC or greater but less than 100 (90) ºC, the speed is raised by 2 rps and kept at that speed for 3 minutes. This
process is repeated until the command speed is reached.
(4) Lower Limit Speed
Cooling Heating
20, 25, 35 type 20 rps 30 rps
50 type 22 rps 38 rps
(5) Values in ( ) are for Type 50.
2) If the temperature of 125 (110)ºC is detected by the sensor on the discharge pipe, then the compressor will stop immediately.
When the discharge pipe temperature drops and the time delay of 3 minutes is over, the unit starts again within 1 hour but
there is no start at the third time.
(8) Current safe
(a) Purpose: Current is controlled not to exceed the upper limit of the setting operation current.
(b) Detail of operation: Input current to the converter is monitored with the current sensor fixed on the printed circuit board
of the outdoor unit and, if the operation current value reaches the limiting current value, the outdoor
unit speed is reduced.
If the mechanism is actuated when the speed of outdoor unit is less than 30 rps, the compressor is
stopped immediately. Operation starts again after a delay time of 3 minutes.
(9) Current cut
(a) Purpose: Inverter is protected from overcurrent.
(b) Detail of operation: Output current from the converter is monitored with a shunt resistor and, if the current exceeds the
setting value, the compressor is stopped immediately. Operation starts again after a delay time of 3
minutes.
(10) Outdoor unit failure
This is a function for determining when there is trouble with the outdoor unit during air conditioning.
The compressor is stopped if any one of the following in item 1), 2) is satisfied. Once the unit is stopped by this function, it is not
restarted.
1) When the input current is measured at 1 A or less for 3 continuous minutes or more.
2) If the outdoor unit sends a 0 rps signal to the indoor unit 3 times or more within 20 minutes of the power being turned on.
(11) Inching prevention
When the compressor goes into the thermo operation within 10(5) minutes since operation start or becomes various dehumidifying
operations, the operation is continued with the lower limit speed forcibly.
Note (1) Values in ( ) are for Type 50.
-
23
-
(12) Indoor fan motor protection
When the air conditioner is operating and the indoor fan motor is turned ON, if the indoor fan motor has operated at 300 rpm or
under for more than 30 seconds, the unit enters first in the stop mode and then stops the entire system.
(13) Serial signal transmission error protection
(a) Purpose: Prevents malfunction resulting from error on the indoor outdoor signals.
(b) Detail of operation: If the compressor is operating and a serial signal cannot be received from the indoor control with
outdoor control having serial signals continuously for 1 minute and 55 seconds, the compressor is
stopped.
After the compressor has been stopped, it will be restarted after the compressor start delay if a serial
signal can be received again from the indoor control.
(14) Rotor lock
If the motor for the compressor does not turn 1/12 revolution 0.044 seconds after it has been started, it is determined that a
compressor lock has occurred and the compressor is stopped.
(15) Outdoor fan motor protection
If the outdoor fan motor has operated at 75rpm or under for more than 30 seconds, the inverter and fan motor are stopped.
-
24
-
5 APPLICATION DATA
SAFETY PRECAUTIONS
¡ Please read these “Safety Precautions” first then accurately execute the installation work. ¡ Though the precautionary points indicated herein are divided under two headings,
WARNING and CAUTION , those points which are
related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the
WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed in the CAUTION
section as well. In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
¡ After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain
operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner’s manual. Moreover, ask the customer to keep this sheet together with the owner’s manual.
WARNING
¡ To disconnect the appliance from the mains supply this appliance must be connected to the mains by means of
a circuit breaker or a switch (use a recognized 16A) with a contact separation of at least 3mm.
¡ The appliance shall be installed in accordance with national wiring regulations. ¡ When a plug is connected to the power cord, a plug conforming to the IEC60884-1 standard must be used. ¡ This system should be applied to places as households, residences and the like. Application to inferior environ-
ment such as engineering shop could cause equipment malfunction.
¡ Please entrust installation to either the company which sold you the equipment or to a professional contractor.
Defects from improper installations can be the cause of water leakage, electric shocks and fires.
¡ Execute the installation accurately, based on following the installation manual. Again, improper installations can
result in water leakage, electric shocks and fires.
¡ For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insuffi-
cient, injury can result from a falling of the unit.
¡ For electrical work, please see that a licensed electrician executes the work while following the safety standards
related to electrical equipment, and local regulations as well as the installation instructions, and that only exclu­sive use circuits are used. Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and fires.
¡ Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted
to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.
¡ Take care that wiring does not rise upward, and accurately install the lid/service panel.It’s improper installation
can also result in heat generation or fire.
¡ When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the
designated refrigerant (R410A) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing.
¡ Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this
company can result in water leakage, electric shock, fire and refrigerant leakage.
¡ Ventilate the work area when refrigerant leaks during the operation.
Coming in contact with fire, refrigerant could generate toxic gas.
¡ Confirm after the foundation construction work that refrigerant does not leak.
If coming in contact with fire of a fan heater, a stove or movable cooking stove, etc., refrigerant leaking in the room could generate toxic gas.
¡ In joining pipes, do not use conventional (R22) pipng flare nuts, etc. The use of conventional pipng materials may
lead to the rapture of piping due to higher pressure used for the refrigerant cycle and possible personal injury. (Use only piping material designed specifically for R410A)
CAUTION
¡ Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone
ground wire. Improper placement of ground wires can result in electric shock.
¡ The installation of an earth leakage breaker is necessary depending on the established location of the unit.
Not installing an earth leakage breaker may result in electric shock.
¡ Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
¡ For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it
to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
¡ Do not place objects near the outdoor unit or allow leaves to gather around the unit. If there are objects or leaves
around the outdoor unit, small animals may enter unit and contact electrical parts resulting in break down, emission of smoke or flame.
Loading...
+ 60 hidden pages