Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm305 x 920 x 220640 x 800 (+71) x 290
Exterior appearance
(Equivalent color)
Net weightkg1343.0
Compressor type & Quantity—RMT5111MCE2(Twin rotary type) x 1
Compressor motor (Starting method)kW—0.75 (Inverter driven)
Refrigerant oil (Amount, type)ℓ—0.35 (DIAMOND FREEZE MA68)
Refrigerant (Type, amount, pre-charge length)kgR410A 1.45 in outdoor unit (Incl. the amount for the piping of 15m)
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)34 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A2.5
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit (SC-BIKN-E)
Remote controlWireless - remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green, TIMER: Yellow, ECO: Blue
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.55 / Gas line : 0.48—
Insulation for pipingNecessary (Both sides), independent
Refrigerant line (one way) lengthmMax.25
Vertical height diff. between O.U. and I.U.mMax.15 (Outdoor unit is higher) / Max.15 (Outdoor unit is lower)
Drain hoseHose connectable (VP 16)Holes φ20 x 5 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
Item
DBWBDBWB
SRK20ZSX-S
0.32 (0.16 - 0.74)
1.9 / 1.8 / 1.7 (220/ 230/ 240V)
76
Munsell : (4.2Y 7.5/1.1), RAL : 7004
Rubber sleeve (for fan motor & compressor)
The pipe length is 5m.
Standards
Stucco white
RWA000Z269
-
-
3
'17 • SRK-T-203
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm305 x 920 x 220640 x 800 (+71) x 290
Exterior appearance
(Equivalent color)
Net weightkg1343.0
Compressor type & Quantity—RMT5111MCE2(Twin rotary type) x 1
Compressor motor (Starting method)kW—0.75 (Inverter driven)
Refrigerant oil (Amount, type)ℓ—0.35 (DIAMOND FREEZE MA68)
Refrigerant (Type, amount, pre-charge length)kgR410A 1.45 in outdoor unit (Incl. the amount for the piping of 15m)
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)34 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A3.0
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit (SC-BIKN-E)
Remote controlWireless - remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green, TIMER: Yellow, ECO: Blue
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.55 / Gas line : 0.48—
Insulation for pipingNecessary (Both sides), independent
Refrigerant line (one way) lengthmMax.25
Vertical height diff. between O.U. and I.U.mMax.15 (Outdoor unit is higher) / Max.15 (Outdoor unit is lower)
Drain hoseHose connectable (VP 16)Holes φ20 x 5 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
Item
DBWBDBWB
SRK25ZSX-S
0.44 (0.16 - 0.89)
2.5 / 2.4 / 2.3 (220/ 230/ 240V)
80
Munsell : (4.2Y 7.5/1.1), RAL : 7004
Rubber sleeve (for fan motor & compressor)
The pipe length is 5m.
Standards
Stucco white
RWA000Z269
-
-
4
'17 • SRK-T-203
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm305 x 920 x 220640 x 800(+71) x 290
Exterior appearance
(Equivalent color)
Net weightkg1343.0
Compressor type & Quantity—RMT5111MCE2(Twin rotary type) x 1
Compressor motor (Starting method)kW—0.90 (Inverter driven)
Refrigerant oil (Amount, type)ℓ—0.35 (DIAMOND FREEZE MA68)
Refrigerant (Type, amount, pre-charge length)kgR410A 1.45 in outdoor unit (Incl. the amount for the piping of 15m)
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)34 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A4.3
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit (SC-BIKN-E)
Remote controlWireless - remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green, TIMER: Yellow, ECO: Blue
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.55 / Gas line : 0.48—
Insulation for pipingNecessary (Both sides), independent
Refrigerant line (one way) lengthmMax.25
Vertical height diff. between O.U. and I.U.mMax.15 (Outdoor unit is higher) / Max.15 (Outdoor unit is lower)
Drain hoseHose connectable (VP 16)Holes φ20 x 5 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
Item
DBWBDBWB
SRK35ZSX-S
0.78 (0.16 - 1.26)
3.9 / 3.7 / 3.6 (220/ 230/ 240V)
91
Munsell : (4.2Y 7.5/1.1), RAL : 7004
Rubber sleeve (for fan motor & compressor)
The pipe length is 5m.
Standards
Stucco white
RWA000Z269
-
-
5
'17 • SRK-T-203
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm305 x 920 x 220640 x 800 (+71) x 290
Exterior appearance
(Equivalent color)
Net weightkg1345
Compressor type & Quantity—RMT5113MCE2(Twin rotary type) x 1
Compressor motor (Starting method)kW—1.50 (Inverter driven)
Refrigerant oil (Amount, type)ℓ—0.45 (DIAMOND FREEZE MA68)
Refrigerant (Type, amount, pre-charge length)kgR410A 1.50 in outdoor unit (Incl. the amount for the piping of 15m)
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)34 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A5.0
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit (SC-BIKN-E)
Remote controlWireless - remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green, TIMER: Yellow, ECO: Blue
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2" )
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.55 / Gas line : 0.48—
Insulation for pipingNecessary (Both sides), independent
Refrigerant line (one way) lengthmMax.30
Vertical height diff. between O.U. and I.U.mMax.20 (Outdoor unit is higher) / Max.20 (Outdoor unit is lower)
Drain hoseHose connectable (VP 16)Holes φ20 x 5 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
Item
DBWBDBWB
SRK50ZSX-S
1.30 (0.19 - 1.80)
6.0 / 5.7 / 5.5 (220/ 230/ 240V)
99
Munsell : (4.2Y 7.5/1.1), RAL : 7004
Rubber sleeve (for fan motor & compressor)
The pipe length is 5m.
Standards
Stucco white
RWA000Z269
-
-
6
'17 • SRK-T-203
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm305 x 920 x 220640 x 800(+71) x 290
Exterior appearance
(Equivalent color)
Net weightkg1345
Compressor type & Quantity—RMT5113MCE2(Twin rotary type) x 1
Compressor motor (Starting method)kW—1.50 (Inverter driven)
Refrigerant oil (Amount, type)ℓ—0.45 (DIAMOND FREEZE MA68)
Refrigerant (Type, amount, pre-charge length)kgR410A 1.50 in outdoor unit (Incl. the amount for the piping of 15m)
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)34 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A5.0
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit (SC-BIKN-E)
Remote controlWireless - remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green, TIMER: Yellow, ECO: Blue
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2" )
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.55 / Gas line : 0.48—
Insulation for pipingNecessary (Both sides), independent
Refrigerant line (one way) lengthmMax.30
Vertical height diff. between O.U. and I.U.mMax.20 (Outdoor unit is higher) / Max.20 (Outdoor unit is lower)
Drain hoseHose connectable (VP 16)Holes φ20 x 5 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
Space for installation and service when viewing from the front
6570
DBAEC
47
76.6
RLF000Z201
'17 • SRK-T-203
(2) Outdoor units
Models SRC20ZSX-S, 25ZSX-S, 35ZSX-S
φ9.52(3/8")( Flare)
Content
AService valve connection(Gas side)
Symbol
M10-12×4 places
φ20×5 places
φ6.35(1/4")( Flare)
Drain discharge hole
Service valve connection(Liquid side)
EAnchor bolt hole
D
B
CPipe/cable draw-out hole
L4
Service
space
( )
Inlet
17.9
L1
Outlet
71.2
L3
Inlet
L2
Notes
( 1) The unit must not be surrounded by walls on the four sides.
( 2) The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
( 3) If the unit is installed in the location where there is a possibility of
strong winds, place the unit such that the direction of air from the
outlet gets perpendicular to the wind direction.
( 4) Leave 200mm or more space above the unit.
( 5) The wall height on the outlet side should be 1200mm or less.
( 6) The model name label is attached on the right side of the unit.
351.6
24.3312.514.8
Ⅳ
180
Ⅲ
280
280
IⅡ
Open
Minimum installation space
installation
L1
Examples
Size
C
Terminal block
Open
Open
75
100
L2
80
80
80
100
L3
40°
Open
Unit:mm
250
Open
250
L4
40°
A
33.5148.4
B
290
9342.5
12
50.6
520.6161
Center of gravity
327.3
38.6
E
DE
2-12X16
2-R
E
35.6
43.5
90.6
290
327.3
E
83.5
145
800
Slot hole
520
89510201
640
Center of gravity
12.4
RCT000Z019
-
-
9
'17 • SRK-T-203
Model SRC50ZSX-S, 60ZSX-S
φ12.7(1/2")(Flare)
Content
AService valve connection(Gas side)
Symbol
M10-12×4 places
φ20×5 places
φ6.35(1/4")(Flare)
Service valve connection(Liquid side)
Drain discharge hole
EAnchor bolt hole
D
B
CPipe/cable draw-out hole
L4
Service
space
( )
L3
Inlet
L2
Notes
(1) The unit must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
(3) If the unit is installed in the location where there is a possibility of
strong winds, place the unit such that the direction of air from the
outlet gets perpendicular to the wind direction.
(4) Leave 200mm or more space above the unit.
(5) The wall height on the outlet side should be 1200mm or less.
(6) The model name label is attached on the front side of the unit.
351.6
24.3312.514.8
E
17.9
L1
Outlet
Inlet
Terminal block
71.2
Ⅳ
Ⅲ
IⅡ
Minimum installation space
installation
Examples
Size
C
180
Open
280
Open
75
280
100
Open
L2
L1
40°
40°
80
80
80
100
L3
Open
250
Open
250
L4
B
290
Unit:mm
A
33.5148.4
9342.5
12
50.6
520.6161
Center of gravity
327.3
38.6
E
D
2-12X16
2-R
E
35.6
43.5
90.6
290
327.3
E
83.5
145
800
Slot hole
520
89510201
640
Center of gravity
12.4
RCT000Z020
-
-
10
'17 • SRK-T-203
(3) Remote control
(3) Remote control
Wireless remote control
Unit : mm
167
60
26
-
11
-
'17 • SRK-T-203
(b) Wired remote control (option parts)
Interface kit (SC-BIKN-E) is required to use the wired remote control.
Wiring outlet
Cut off the upper thin part of remote control lower case with a nipper or knife,
Exposed mounting
0.3mm2×2 cores.
In case of pulling out
from upper left
L C D
48
In case of pulling out
from center
TEMP ON/OFF
and grind burrs with a file etc.
In case of pulling out
from upper left
Upper
Board
X Y
In case of pulling out
from center
Lower case
Lower part
Sheath
Upper cace
Upper part
Upper
Sheath
Upper cace
Board
YX
X, Y Terminal block
Attach M3 screw
□120
with washer
Pearl whiteExterior appearance
(Munsell color)(N8.5) near equivalent
Embedded mounting
Wall surface
Wiring
Electrical box
(Not included)
19
Remote
control
outline
Wiring oulet
12×7 Slot hole
Lower
In case of pulling out from
The peeling-off length of sheath
Pulling out from upper left
X wiring : 215mm
Y wiring : 195mm
Wiring
upper left
Pulling out from center
X wiring : 170mm
Y wiring : 190mm
Remote control installation dimensions
83.5
120
46
23
44
42
11.511
Installation hole
9.5×5 Slot hole (4 places)
Tighten the screws after
cutting off the thin part of
screw mounting part.
120
45
(1) Installation screw for remote control
M4 screw (2 pieces)
Lower
In case of pulling out from center
Wiring
The peeling-off length
of sheath
Unit:mm
Wiring specifications
(1) If the prolongation is over 100m, change to the size below.
But, wiring in the remote control case should be under 0.5mm
the case according to wire connecting. Waterproof treatment is necessary at the wire connecting
section. Be careful about contact failure.
Switchgear or circuit breaker capacity should be chosen according to national or regional electricity
The power cable specifications are based on the assumption that a metal or plastic conduit is used
with no more than three cables contained in a conduit and a voltage drop is 2%. For an installation
SRC35ZSX-S
SRC25ZSX-S2.0mm
The wire numbers include earth wire(Yellow/Green)*regulations.
falling outside of these conditions, please follow the national or regional electricity regulations.
RWC000Z297
-
-
14
'17 • SRK-T-203
Models SRC50ZSX-S, 60ZSX-S
(RD)
UP
POWER
TRANSISTOR
MS
(WH)
VWU
CM
3~
(BK)
V
W
N
F3
T 1A L 250V
M
(WH)
CNFAN
FMo
+
++
T2
T12
(BL)
(YE)
L1
L2
(BL)
(YE)
T1
T11
+
-
DIODE
STACK1
~
~
PCB ASSY PCB1
F8
PAM
PAM
DIODE
250V 20A
CIRCUIT
CIRCUIT
SWITCHING
+
STACK2
~
F1
POWER
CIRCUIT
-
~
F 3.15A L 250V
(RD)
(WH)
(BK)
CNTHCNEEV
CN20S
M
EEV
ItemDescription
20SSolenoid coil for 4 way valve
CNFAN
CNEEV
CN20SConnector
EEVElectric expansion valve(coil)
CMCompressor motor
CNTH
TH3Discharge pipe temp. sensor
TH2Outdoor air temp. sensor
TH1Heat exchanger sensor
L1,2Reactor
FMo Fan motor
Meaning of marks
t゜
t゜
t゜
222
TH1 TH2 TH3
20S
Connecting cable
Power cable length
Color
BKBlack
Mark
Color marks
x 4
2
wire size x number*
(m)
BLBlue
RDRed
YEYellow
WHWhite
Yellow/Green
YG
S.IN
R.IN
(BK)
(WH)
F4
250V 20A
(BK)
N
L
TB1
BLOCK 1
TERMINAL
3
220V 60Hz
220-240V 50Hz
Power source
1 Phase
wire size x number*(A)
MAX running currentPower cable
Model name
SRC50ZSX-S
x 3131.5mm
2
2.0mm
15
SRC60ZSX-S
Switchgear or circuit breaker capacity should be chosen according to national or regional electricity
The power cable specifications are based on the assumption that a metal or plastic conduit is used
with no more than three cables contained in a conduit and a voltage drop is 2%. For an installation
The wire numbers include earth wire(Yellow/Green)*regulations.
falling outside of these conditions, please follow the national or regional electricity regulations.
G1
G2
(YG)
(YG)
(WH)
(YG)
BLOCK 2
TERMINAL
(BK)
TB2
C-2
(RD)
]
N
N
1
2
(YG)
3
4
2
3
1
POWER WIRES
SIGNAL WIRE
EARTH WIRE
TO INDOOR UNIT
Power cable, indoor-outdoor connecting wires
[
RWC000Z298
-
-
15
'17 • SRK-T-203
Mid octave band frequency (Hz)
N50
N30
N40
N60
N2
Mid octave band frequency (Hz)
N50
N40
N20
N30
Mike position: at highest noise level in position as mentioned below
Mike position
0.8m
1m
Unit
Mike position(Center & Low points)
Mike position
4. NOISE LEVEL
Model SRK20ZSX-S
(Indoor Unit)
ModelSRK20ZSX-S
Noise
Level
Cooling38 dB(A)
Heating38 dB(A)
ConditionISO5151 T1/H1
1m
0.8m
×
......
Unit
Cooling,
Mike position
(Center & Low points)
Heating
70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
(Outdoor Unit)
ModelSRC20ZSX-S
Noise
Level
Cooling43 dB(A)
Heating44 dB(A)
70
Distance from front side 1m
......
×
Cooling, Heating
70
N70
60
50
40
30
20
0
10
70
N70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
-
16
60
N60
50
40
30
20
10
-
'17 • SRK-T-203
Model SRK25ZSX-S
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
Mike position: at highest noise level in position as mentioned below
Mike position
0.8m
1m
Unit
Mike position(Center & Low points)
Mike position
(Indoor Unit)
ModelSRK25ZSX-S
Noise
Level
Cooling39 dB(A)
Heating40 dB(A)
70
ConditionISO5151 T1/H1
1m
0.8m
×
......
Unit
Cooling,
Mike position
(Center & Low points)
Heating
70
N70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
(Outdoor Unit)
ModelSRC25ZSX-S
Noise
Level
Cooling44 dB(A)
Heating45 dB(A)
70
Distance from front side 1m
......
×
Cooling, Heating
60
N60
50
N50
40
N40
30
N30
20
N20
10
70
N70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
-
17
60
N60
50
N50
40
N40
30
N30
20
N20
10
-
'17 • SRK-T-203
Model SRK35ZSX-S
Mid octave band frequency (Hz)
Mike position: at highest noise level in position as mentioned below
Mike position
0.8m
1m
Unit
Mike position(Center & Low points)
Mike position
(Indoor Unit)
ModelSRK35ZSX-S
Noise
Level
Cooling43 dB(A)
Heating41 dB(A)
70
ConditionISO5151 T1/H1
1m
0.8m
×
......
Unit
Cooling,
Mike position
(Center & Low points)
Heating
70
N70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
(Outdoor Unit)
ModelSRC35ZSX-S
Noise
Level
Cooling48 dB(A)
Heating47 dB(A)
70
Distance from front side 1m
......
×
Cooling,
60
N60
50
N50
40
N40
30
N30
20
N20
10
Heating
70
N70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
Mid octave band frequency (Hz)
-
18
60
N60
50
N50
40
N40
30
N30
20
N20
-
'17 • SRK-T-203
Mike position
Model SRK50ZSX-S
Mike position: at highest noise level in position as mentioned below
Mike position
0.8m
1m
Unit
Mike position(Center & Low points)
(Indoor Unit)
ModelSRK50ZSX-S
Noise
Level
Cooling44 dB(A)
Heating46 dB(A)
70
ConditionISO5151 T1/H1
1m
0.8m
×
......
Unit
Cooling,
Mike position
(Center & Low points)
Heating
70
N70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
(Outdoor Unit)
ModelSRC50ZSX-S
Noise
Level
Cooling50 dB(A)
Heating49 dB(A)
70
Mid octave band frequency (Hz)
Distance from front side 1m
......
×
Cooling,
60
N60
50
N50
40
N40
30
N30
20
N20
10
Heating
70
N70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
Mid octave band frequency (Hz)
-
19
60
N60
50
N50
40
N40
30
N30
20
N20
10
-
'17 • SRK-T-203
Model SRK60ZSX-S
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
Mike position: at highest noise level in position as mentioned below
Mike position
0.8m
1m
Unit
Mike position(Center & Low points)
Mike position
(Indoor Unit)
ModelSRK60ZSX-S
Noise
Level
Cooling46 dB(A)
Heating46 dB(A)
70
ConditionISO5151 T1/H1
1m
0.8m
×
......
Unit
Cooling,
Mike position
(Center & Low points)
Heating
N70
70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
(Outdoor Unit)
ModelSRC60ZSX-S
Noise
Level
Cooling52 dB(A)
Heating52 dB(A)
70
Distance from front side 1m
......
×
Cooling,
60
N60
50
N50
40
N40
30
N30
20
N20
10
Heating
70
N70
60
50
Pa)
-5
40
(Standard 2×10
30
Sound pressure level (dB)
20
10
631252505001000200040008000
-
20
60
N60
50
N50
40
N40
30
N30
20
N20
10
-
'17 • SRK-T-203
5. PIPING SYSTEM
Models SRK20ZSX-S, 25ZSX-S, 35ZSX-S
Indoor unit
Room temp.
sensor
(Th1)
Humidity
sensor
(Th3)
Flare
connection
Heat
exchanger
sensor
(Th2
2)
Heat
exchanger
Heat
exchanger
sensor
1)
(Th2
Gas pipe
(φ9.52)
Liquid
pipe
(φ6.35)
Outdoor unit
Service valve
Gas
)
(
Muffler
Check joint
4-way valve
Service valve
(Liquid)
Discharge pipe
temp. sensor
(TH3)
Muffler
Compressor
Electronic
expansion valve
(EEV)
Capillary tube
Cooling cycle
Heating cycle
Accumulator
Capillary tube
Muffler
Outdoor air
temp. sensor
(TH2)
Heat
exchanger
Heat
exchanger
sensor
(TH1)
Flare connection
Models SRK50ZSX-S,60ZSX-S
Indoor unit
Room temp.
sensor
(Th1)
Humidity
sensor
(Th3)
Flare
connection
Heat
exchanger
sensor
(Th2
2)
Heat
exchanger
Heat
exchanger
sensor
1)
(Th2
Gas pipe
(φ12.7)
Liquid
pipe
(φ6.35)
Service valve
StrainerMuffler
Outdoor unit
Gas
)
(
Muffler
Check joint
4-way valve
Service valve
(Liquid)
Muffler
Receiver
Discharge pipe
temp. sensor
(TH3)
Compressor
Electronic
expansion valve
Capillary tube
(EEV)
Cooling cycle
Heating cycle
Accumulator
Capillary tube
Outdoor air
temp. sensor
(TH2)
Heat
exchanger
Heat
exchanger
sensor
(TH1)
Flare connection
Strainer
-
21
Muffler
-
'17 • SRK-T-203
6. RANGE OF USAGE & LIMITATIONS
RANGE OF USAGE & LIMITATIONS
Models
SRK20, 25, 35ZSX-S
SRK50, 60ZSX-S
Item
Indoor return air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Cooling operation : Approximately 18 to 32℃ D.B.
Heating operation : Approximately 10 to 30℃ D.B.
(Refer to the selection chart)
Cooling operation : Approximately -15 to 46℃ D.B.
Heating operation : Approximately -20 to 24℃ D.B.
(Refer to the selection chart)
Max. 25mMax. 30m
Max. 15m
(Outdoor unit is higher)
Max. 15m
(Outdoor unit is lower)
(Outdoor unit is lower)
Max. 20m
(Outdoor unit is higher)
Max. 20m
Power source voltageRating ±10%
Voltage at startingMin. 85% of rating
Frequency of ON-OFF cycle
Max. 4 times/h
(Inching prevention 10 minutes)
ON and OFF intervalMin. 3 minutes
Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be
obtained in the following way.
Net capacity = Capacity shown on specification ×Correction factors as follows.
(1) Coefficient of cooling and heating capacity in relation to temperatures
1.3
&
1.2
1.1
1.0
0.9
0.8
Coefficient of cooling
Heating capacity in
relation to temperature
0.7
0.6
46
40
35
30
°C D. B.
25
temperature
20
Outdoor air D.B.
Cooling operation
0
-5
-10
-15
27
25
20
15
°C D. B.
10
temperature
Indoor air D.B.
Heating operation
Indoor air W.B. temperature °C W.B
-15-20-10-5051015
Cooling
Depends on installed situation
.
ISO-T1 Standard Condition
Outdoor air W.B. temperature °C W.B.
ISO-T1 Standard Condition
Heating
Applicable range
26
24
2220181614
-
22
-
'17 • SRK-T-203
'09•SRK-DB-087D
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
Piping length [m]
Cooling
Heating
(3) Correction relative to frosting on outdoor heat exchanger during heating
Depending on the system control, there may be ranges where the operation
is not conducted continuously.
These data show the case where the operation frequency of a compressor is
fixed.
(2) Capacities are based on the following conditions.
Corresponding refrigerant piping length :7m
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity (kW)
SHC : Sensible heat capacity (kW)
HC : Heating capacity (kW)
Depending on the system control, there may be ranges where the operation
is not conducted continuously.
These data show the case where the operation frequency of a compressor is
fixed.
(2) Capacities are based on the following conditions.
Corresponding refrigerant piping length :7m
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity (kW)
SHC : Sensible heat capacity (kW)
HC : Heating capacity (kW)
indoor air temp
indoor air temp
-
25
-
'17 • SRK-T-203
WARNING
CAUTION
WARNING
CAUTION
8. APPLICATION DATA
(1) Installation of indoor unit
•
This installation manual deals with an indoor unit installation only. For an outdoor unit installation, refer to page 30.
• Before installation, read the “SAFETY PRECAUTIONS” carefully and strictly follow it during the installation work in order to protect yourself.
•
The precautionary items mentioned below are distinguished into two levels,
Indicates a potentially hazardous situation which, if not avoided, can result in serious con-
sequences such as death or severe injury.
Indicates a potentially hazardous situation which, if not avoided, can result in personal inju-
Both mention the important items to protect your health and safety. Therefore, strictly follow them by any means.
• Be sure to use only for residential purpose.
If this unit is installed in inferior environment such as machine shop, vehicle (like ship), warehouse,
• When installing the unit in small rooms, make sure that refrigerant density
If refrigerant density exceeds the limit, consult the dealer and install the ventilation system.
Otherwise lack of oxygen can occur resulting in serious accident.
• Install the unit in a location where unit will remain stable, horizontal and free
noise can be heard during the test run, consult the dealer.
• Be sure to explain the operating methods as well as the maintenance methods of this equipment to the
.
user according to the user’s manual.
• Be sure to keep the installation manual together with user’s manual at a place where it is easily accessible to the user any time. Moreover, ask the user to hand the manuals to a new user, whenever required.
WARNING
• During pump down work, be sure to stop the compressor before closing ser
vice valves and removing connecting pipes.
If the connecting pipes are removed when the compressor is in operation and service valves are
open, air can be sucked into the refrigerant circuit which can cause anomalous high pressure result
inginburstorpersonalinjury.
• In the event of refrigerant leakage during installation, be sure to ventilate the
• A solid place where the unit or the wall will not vibrate.
• A place where there will be enough space for servicing.
(Where space mentioned on the right side can be secured.)
• Where it is easy to conduct wiring and piping work.
• A place where unit is not directly exposed to sunlight or street light.
• A place where it can be easily drained.
• A place separated at least 1m away from the television or the radio.
(To prevent interference to images and sounds.)
• A place where this unit is not affected by the high frequency equipment or electric equipment.
• Avoid installing this unit in place where there is much oil mist.
• A place where there is no electric equipment or household.
• Installtheindoorunitonthewallwheretheheightfromtheoortothebottomoftheunitis
more than 180 cm.
2.Wirelessremotecontrol
• A place where the air-conditioner can receive the signal surely during operating the wireless
remote control.
• A place where it is not affected by the TV and radio etc.
• Do not place where it is exposed to direct sunlight or near heat devices such as a stove.
3. INSTALLING INSTALLATION BOARD
• Installation board should be installed on the wall which can support the weight of the indoor unit.
• Adjustment of the installation board in the horizontal direction is to be conducted with 4 screws in a
temporary tightened state.
• With the standard hole as a center, adjust the board and level it.
Bolt
(M6X12)
Standard
568
In case of fixing the unit on
concrete wall, use nut anchor.
CAUTION
Improper adjustment of the installation board can cause water leakage.
10 cm minimum
from the wall
Remote control holder
Wireless
remote control
Wood screws
(Service Space)
88.6
76.6
100
48.6
47
65
(In the case of less than 10 cm,
there is a possibility of performance
degradation.)
145630
(a) Sleeve
460
Installation board
10 cm minimum
from the wall
568176
Installation example
2 cm
Indoor
unit
Be sure that the
flap of outlet
should not
touch any
obstacles.
Obstacle such
as curtain
180 cm minimum from the floor
100
118.5118.5683
176
145
460
480 (Gas pipe)
533 (Drain hose)
548 (Liquid pipe)
70
Unit: mm
Maximum
moving range
11 cm 12 cm
Flap removal
position
Need to
secure a
space for
service
(Service Space)
65
47
120
7.9 cm
56.4
7.0
cm
10.3
4.DRILLINGHOLEANDFIXTUREOFSLEEVE
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use sealing plate, sleeve and inclination plate (Locally procured parts).
5
ø65
(1) Drill a hole with hole
core drill.
(a) Sleeve
Top
Thickness of the wall + 1.5cm
(2) Cut sleeve to adjust to wall
thickness. In case of rear
piping draw out, cut off the
lower and the right side
portions of the sleeve collar.
Cut
(a) Sleeve
(3) Fix sealing plate, sleeve
and inclination plate.
(b) Sealing plate
Turn to
tighten
CAUTION
After passing the wirings and pipes
through the hole, completely seal
the hole on the wall with putty to
prevent water leakage.
(1) Remove the 3 screws (in the cap).
(2) Remove the hooks of left and right side
and then bottom panel can be removed.
NOTE
• Openthecapusingane-tippedtool.
• When opening the cap, exercise care not to
damage the design surface.
Sleeve
3. Connecting cable
(1) Remove the terminal cover.
(2) Remove the cable clamp.
(3) Connect the connecting wires to the terminal block.
(4) Fix the connecting cable by cable clamp.
(5) Fix the terminal cover.
NOTE
Take care not to confuse the terminal numbers for indoor and outdoor connections.
• Earth wire shall be Yellow/Green (Y/G) in color and
longer than other wires for safety reason.
-
27
-
'17 • SRK-T-203
6. FORMING PIPING AND DRAIN HOSE
Cut out the panel smoothly along the
Right
Left downward
Left
Piping in the left direction
Piping in the left rear direction
Piping in the right rear direction
Piping in the right direction
(1)(2)(3)(4)
Higher than
specifie
Gutter
Pipe space
Indoor unit
Bottom panel
A
B
(Do not turn)
Liquid side
Tape
Insulation pad
Position it so that the slit area faces upward.
Connecting cable
Liquid pip
Drain hose
Gas pipe
Clamp
1. Forming piping
Piping is possible in the right, rear, downward, left, left rear or left downward direction.
NOTE
Sufcientcaremustbetakennottodamage
the panels when connecting pipes.
line in case of side or bottom piping.
Rear
Left
Downward
rear
Forming of pipings
• Hold the bottom of the
pipingandxdirection
before stretching it
and shaping it.
2.Drainchangeprocedures
(1) Remove the screw and drain hose.
(2) Remove the drain cap by hand or pliers.
(3) Insert the drain cap which was removed at procedure (2) securely using a hexagonal wrench etc.
(4) Install the drain hose and screw securely.
Pipings
Taping of the exterior
• Tape only the portion that
goes through the wall.
• Always tape the wiring
with the piping.
Left hand side pipingRight hand side piping
7. DRAINAGE WORK
• Arrange the drain hose in a downward angle.
• Avoid the following drain piping.
The drain hose
tip is in water.
d
Wavy
8.INSTALLINGINDOORUNIT
1. Installing the indoor unit to installation board2.Removingtheindoorunitfrominstallationboard
(1) Pass the pipe through the hole
in the wall, and hook the upper
part of the indoor unit to the
installation board.
(2)
Gently push the lower part to
fix the indoor unit base lower
latch to installation board.
(3) Install the latches of the bottom panel
(7 locations).
Secure the bottom panel with the 3 screws
(in the cap).
9. CONNECTING PIPING WORK
1. Preparation of connecting pipe
1.1. Selecting connecting pipe
Select connecting pipe according to the following table.
Gas pipeø9.52ø12.7
Liquid pipeø6.35ø6.35
• Pipe wall thickness must be greater than or equal to 0.8 mm.
• Pipe material must be O-type (Phosphorus deoxidized seamless copper pipe ICS 23.040.15, ICS
77.150.30).
1.2.Cuttingconnectingpipe
(1) Cut the connecting pipe to the required length with pipe cutter.
(2)
Hold the pipe downward and remove the burrs. Make sure that no foreign material enters the pipe.
Incorrect installation of drain hose and cap can cause water leakage.
• Pour water to the drain pan located under the heat exchanger, and ensure that the water is discharged outdoor.
• When extended drain hose is present inside the room, insulate it securely with heat insulator available in the market.
Since this air-conditioner is designed to collect dew drops on the rear surface to the
drain pan, do not install the connecting wire above the gutter.
CAUTION
Incorrect drainage work can cause water leakage.
(1) Remove the bottom panel. (Refer to 5.2)
(2) Pull the indoor unit base latch downward. (both right and left
hand sides). (The indoor unit base latch can be removed from the
installation board.)
(3) Push up the indoor unit upward so that it can be removed from
installation board.
Installation board
3. Heating and condensation prevention
(1) Dress the connecting pipes (both liquid and gas pipes) with insulation to prevent it from heating and
dew condensation.
Use the heat insulating material which can withstand 120°C or higher temperature. Make sure that insu
lation is wrapped tightly around the pipes and no gap is left between them.
(2) Wrap the refrigerant pipings of indoor unit with indoor unit heat insulation using tape.
(3) Coverthe are-connectedjoints (indoorside) with theindoor unitheat insulation andwrap itwith an
insulation pad (standard accessory provided with indoor unit).
(4) Wrap the connecting pipes, connecting cable and drain hose with the tape.
(2)(3)(4)
NOTE
Locations where relative humidity exceeds 70%, both liquid and gas pipes need to be dressed with 20mm
thicker heat insulation materials.
CAUTION
• Improper insulation can cause condensate(water) formation during cooling operation.
Condensate can leak or drip causing damage to household property.
• Poor heat insulating capacity can cause pipe outer surface to reach high temperature during heating
operation. It can cause cable deterioration and personal injury.
4. Finishing work
(1) Make sure that the exterior portion of connecting pipes, connecting cable
and drain hose is wrapped properly with tape. Shape the connecting pipes
to match with the contours of the pipe assembly route.
(2) Fix the pipe assembly with the wall using clamps and screws. Pipe assem-
bly should be anchored every 1.5m or less to isolate the vibration.
(3) Install the service cover securely. Water may enter the unit if service cover
is not installed properly, resulting in unit malfunction and failure.
CAUTION
Make sure that the connecting pipes do not touch the components within the unit. If pipes touch the
internal components, it may generate abnormal sounds and/or vibrations.
-
-
28
Installation board
Indoor unit base latch
(2 locations)
Wall
Wall
Bottom panel
e
Insulation
Pipe
assembly
Screw
Tape
-
or
'17 • SRK-T-203
Air inlet panel
Panel ar
Cut
<Top view>
Scre
CNS terminal
<Right side>
Front panel
Bottom panel
)
Screw
Side panel (L)
Interface kit
Latch
cable through here.
Unit ON/OFF button
Wirekess
remote contro
Cover
Battery
10.HOWTOOPEN,CLOSE,REMOVEANDINSTALL
THE AIR INLET PANEL
1. Open
Pull the air inlet panel at both ends of lower part
and release latches, then pull up the panel until
you feel resistance.
(The panel stops at approx. 60° open position)
2.Close
Hold the panel at both ends of lower part, lower
it downward slowly, then push it slightly until the
latch works.
3. Removing
Open the panel by 80 degrees (as shown in the
right illustration) and then pull it forward.
4. Installing
Insert the panel arm into the slot on the front
panel from the position shown in right illustration,
hold the panel at both ends of lower part, lower
it downward slowly, then push it slightly until the
latch works.
NOTE
• When carrying out maintenance, handle the air
inlet panel with care.
m
Approx. 80°
11.HOWTOREMOVEANDINSTALLTHESIDEAND
FRONT PANEL
1. Side panel (R/L)
1.1. Removing
(1) Remove the 2 screws.
(2) Remove the 3 latches and then side panel
can be removed.
1.2.Installing
(1)Covertheunitwiththesidepanelandx
3 latches.
(2) Secure the side panel with the 2 screws.
Latch
2.Frontpanel
2.1.Removing
(1) Remove the side panel (R/L), the air inlet
panel,theairltersandthebottompanel.
(2) Remove the 3 screws.
(3) Remove the 4 upper latches and then front
panel can be removed.
2.2.Installing
(1)Covertheunitwiththefrontpanelandx4
upper latches.
(2) Secure the front panel with the 3 screws.
(3) Install the bottom panel, the side panel
(R/L),theairinletpanelandtheairlters.
Screw
Side panel (R
13.
INSTALLING TWO AIR-CONDITIONERS IN THE SAME ROOM
In case two air-conditioners are installed in the same room, apply this setting so that one unit can be
operated with only one wirelesss remote control.
Setting one wirelesss remote control
(1) Slide and take out the cover and batteries.
(2) Cut the switching line next to the battery with
wire cutters.
(3) Set the batteries and cover again.
Setting one indoor unit
(1) Turn off the power source and turn it on after
1 minute.
(2) Send the signal by pressing the ACL switch
on the wireless remote control that was set
according to the procedure described on the
above side.
(3) Check that the reception buzzer sound “peep”
is emitted from the indoor unit. Since the signal
is sent about 6 seconds after the ACL switch is
pressed, point the wireless remote control to the
indoor unit for a while.
NOTE
If no reception buzzer is emitted, restart the setting
from the beginning.
TIME SETUP ACL
Reception
Peep
14. TERMINAL CONNECTION FOR AN INTERFACE
To install wired remote control, superlink etc., interface kit is needed.
Remove the air inlet panel, bottom panel
(1)
and side panel (R).
(2) Remove the control cover. (Remove
the screw.)
(3) There is a terminal (respectively marked
with CNS) for the indoor control board.
While connecting an interface, connect
to the respective terminal securely with
the connection harness supplied with
an option “Interface kit SC-BIKN-E” and
fasten the connection harness onto the
indoor control box with the clamp and
screw supplied with the kit.
(4)
Hooktoxtheinterfacekittothe2
latches on side panel (L).
For more details, refer to the user’s
manual of “Interface kit SC-BIKN-E”.
w
Indoor PCB
Control cover
Fixing point of
the clamp
Latches
Side panel (L)
Screw (Front panel)
Latches
Side panel (R)
Pass the interface kit
12.INSTALLINGWIRELESSREMOTECONTROL
Mount the batteries
(1) Slide and take out the cover of backside.
(2) Mount the batteries [R03 (AAA, Micro),
×2 pieces] in the body properly.
(Fithepoleswiththeindicationmarks+&−)
(3) Set the cover again.
NOTE
• Do not use new and old batteries together.
• In case the unit is not operated for a long time,
take out the batteries
Installing remote control holder
(1) Select the place where the unit can receive
signals.
(2) Fix the holder to pillar or wall with wood
screws.
l
Wood screws
ø3.5 X 16
15. PUMP DOWN WORK
For the environmental protection, be sure to pump down when relocating or disposing of the unit.
Pump down is the method of recovering refrigerant from the indoor unit to the outdoor unit before
the connecting pipes are removed from the unit. When pump down is carried out, forced cooling
operation is needed.
Forced cooling operation
(1) Turn off the power source and turn it on
again after 1 minute. The air inlet panel
andapopenandclose.
(2) After the air inlet panel closes, press the
ON/OFF button continuously for at least 5
seconds. Then operation will start.
For the detail of pump down, refer to the
installation manual of outdoor unit.
Both liquid and gas service valves are fully open.
No gas leaks from the joints of the service valves.
Indoor and outdoor side pipe joints have been insulated.
Hole on the wall is completely sealed with putty.
Drain hose and cap are installed properly.
Screw of the terminal cover is tightened securely.
Test run
Check following points during test run.
Indoor unit receives signal of wireless remote control.
Air-conditioning operation is normal.
There is no abnormal noise.
Water drains out smoothly.
Display of wireless remote control is normal.
After test run
Explain the operating and maintenance methods to the
user according to the user’s manual.
Keep this installation manual together with user’s
manual.
-
-
29
NOTE
During restart or change in operation mode, the unit will not start
operating for approximately 3 minutes. This is to protect the unit
and it is not malfunction.
Side panel (L)
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.