Mitsubishi Heavy Industries SRK05CM, SRK05CM-3, SRK09CM-3, SRK09CM-4, SRK09CM-5 Technical Manual

...
RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air cooled cooling only type)
SRK05CM, 05CM-3 SRK05CMP-3 SRK09CM-3, 09CM-4, 09CM-5 SRK09CMP-3, 09CMP-4 SRK12CM-3, 12CM-4, 12CM-5
Manual No.'13•SRK-T-141
-
1
-
'13•SRK-T-141
TECHNICAL MANUAL
-
2
-
'13•SRK-T-141
'10 • SRK-T-099
CONTENTS
1. SPECIFICATIONS .................................................................................... 4
(2) Outdoor units ...................................................................................... 17
(3) Wireless remote control
...................................................................... 19
........................................................................ 15
(1) Indoor units ......................................................................................... 15
2. EXTERIOR DIMENSIONS
3. ELECTRICAL WIRING ............................................................................. 20
(1) Indoor units ......................................................................................... 20
(2) Outdoor units ...................................................................................... 21
....................................................... 24
5. RANGE OF USAGE & LIMITATIONS
4. PIPING SYSTEM ..................................................................................... 23
............................................................................... 26
6. APPLICATION DATA
7. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 40
(6) Timer operation
................................................................................. 43
(5) Flap control ....................................................................................... 43
...................................................... 42(4) Custom cord switching procedure
........................................................................ 42(3) Auto restart function
(2) Unit ON/OFF button
.......................................................................... 42
(1) Operation control function by remote control
..................................... 40
(8) Outline of automatic operation .......................................................... 44
(7) Outline of cooling operation .............................................................. 44
(9) Protective control function
.................................................................. 45
.............................................................................. 46
.................... 47
(4) Troubleshooting procedure (If the air conditioner runs)
(3) Troubleshooting procedure
(If the air conditioner does not run at all)
....... 46
(1) Cautions
............................................................................................ 46
(2) Items to check before troubleshooting ................................................ 46
(5) Self-diagnosis table ............................................................................ 47
(6) Inspection procedures corresponding to detail of trouble ................... 48
8. MAINTENANCE DATA
-
3
-
'13•SRK-T-141
'10 • SRK-T-099
(7)
Phenomenon observed after shortcircuit, wire breakage on sensor
........ 49
How to read the model name
Example: SRK 05 C
Series code
Cooling only type
Product capacity
Model name SRK : Wall mounted type
SRC : Outdoor unit
MP
(8) How to make sure of wireless remote control ..................................... 50
-
4
-
'13•SRK-T-141
1. SPECIFICATIONS
Model
Item
SRK05CM
Indoor unit SRK05CM Outdoor unit SRC05CM Cooling capacity (1) W 1500 Power supply 1 Phase, 220V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.42
Running current
Cooling
A
2.0
Inrush current 9.5 COP Cooling 3.57 Noise level
Cooling Sound level dB(A) 42 47
Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 19
Refrigerant equipment
Compressor type & Q'ty RMC201A009 (Rotary type) x 1 Motor (Starting method) kW 0.35 (PSC) Refrigerant oil 0.29 (SUNISO 4GSI or ATMOS NM56M) Refrigerant (3) kg R22 0.40 (Pre-Charged up to the piping length of 7.5m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 8.5 23.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C JIS C 9612, TISI 1155, 2134, 812
(2) This air-conditioner is manufactured and tested in conformity with the TISI. (3) The operation data are applied to the 220V districts. (4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 7.5m to 15m, additional refrigerant is 10g per each 1m longer than 7.5m.
The pipe length is 7.5m.
-
5
-
'13•SRK-T-141
Model
Item
SRK05CM-3
Indoor unit SRK05CM-3 Outdoor unit SRC05CM-3 Cooling capacity (1) W 1465 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.375
Running current
Cooling
A
1.8
Inrush current 9.5 COP Cooling 3.91 Noise level
Cooling Sound level dB(A) 42 48
Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 20
Refrigerant equipment
Compressor type & Q'ty RMC201A055 (Rotary type) x 1 Motor (Starting method) kW 0.35 (PSC) Refrigerant oil 0.23 (SUNISO 4GSI or ATMOS NM56M) Refrigerant (3) kg R22 0.45 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 8.5 23.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
6
-
'13•SRK-T-141
Model
Item
SRK05CMP-3
Indoor unit SRK05CMP-3 Outdoor unit SRC05CMP-3 Cooling capacity (1) W 1465 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.49
Running current
Cooling
A
2.3 / 2.2
Inrush current 9.5 COP Cooling 2.99 Noise level
Cooling Sound level dB(A) 42 47
Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 19
Refrigerant equipment
Compressor type & Q'ty RMC201A009 (Rotary type) x 1 Motor (Starting method) kW 0.35 (PSC) Refrigerant oil 0.29 (SUNISO 4GSI or ATMOS NM56M) Refrigerant (3) kg R22 0.34 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 8.5 20.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220 / 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
7
-
'13•SRK-T-141
Model
Item
SRK09CM-3
Indoor unit SRK09CM-3 Outdoor unit SRC09CM-3 Cooling capacity (1) W 2638 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.90
Running current
Cooling
A
4.2 / 4.0
Inrush current 21.0 COP Cooling 2.93 Noise level
Cooling Sound level dB(A) 43 50
Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 22.5
Refrigerant equipment
Compressor type & Q'ty RMC201A054 (Rotary type) x 1 Motor (Starting method) kW 0.7 (PSC) Refrigerant oil 0.28 (SUNISO 4GSI or ATMOS NM56M) Refrigerant (3) kg R22 0.45 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9.0 23.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220 / 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
8
-
'13•SRK-T-141
Model
Item
SRK09CM-4
Indoor unit SRK09CM-4 Outdoor unit SRC09CM-4 Cooling capacity (1) W 2638 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.90
Running current
Cooling
A
4.2 / 4.0
Inrush current 21.0 COP Cooling 2.93 Noise level
Cooling Sound level dB(A) 43 50
Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 22.5
Refrigerant equipment
Compressor type & Q'ty RMC201A054 (Rotary type) x 1 Motor (Starting method) kW 0.7 (PSC) Refrigerant oil 0.28 (SUNISO 4GSI or ATMOS NM56M) Refrigerant (3) kg R22 0.45 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9.0 23.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220 / 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
9
-
'13•SRK-T-141
Model
Item
SRK09CM-5
Indoor unit SRK09CM-5 Outdoor unit SRC09CM-5 Cooling capacity (1) W 2638 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.90
Running current
Cooling
A
4.2 / 4.0
Inrush current 21.0 COP Cooling 2.93 Noise level
Cooling Sound level dB(A) 43 50
Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 22.5
Refrigerant equipment
Compressor type & Q'ty RMC201A054 (Rotary type) x 1 Motor (Starting method) kW 0.7 (PSC) Refrigerant oil 0.28 (SUNISO 4GSI or ATMOS NM56M) Refrigerant (3) kg R22 0.45 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9.0 23.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220 / 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
10
-
'13•SRK-T-141
Model
Item
SRK09CMP-3
Indoor unit SRK09CMP-3 Outdoor unit SRC09CMP-3 Cooling capacity (1) W 2500 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.925
Running current
Cooling
A
4.7 / 4.6
Inrush current 21.0 COP Cooling 2.70 Noise level
Cooling Sound level dB(A) 43 50
Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 22
Refrigerant equipment
Compressor type & Q'ty RMC201A054 (Rotary type) x 1 Motor (Starting method) kW 0.7 (PSC) Refrigerant oil 0.28 (SUNISO 4GSI or ATMOS NM56M) Refrigerant (3) kg R22 0.41 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9.0 23.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220 / 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
11
-
'13•SRK-T-141
Model
Item
SRK09CMP-4
Indoor unit SRK09CMP-4 Outdoor unit SRC09CMP-4 Cooling capacity (1) W 2500 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.925
Running current
Cooling
A
4.7 / 4.6
Inrush current 21.0 COP Cooling 2.70 Noise level
Cooling Sound level dB(A) 43 50
Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 22
Refrigerant equipment
Compressor type & Q'ty RMC201A054 (Rotary type) x 1 Motor (Starting method) kW 0.7 (PSC) Refrigerant oil 0.28 (SUNISO 4GSI or ATMOS NM56M) Refrigerant (3) kg R22 0.41 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9.0 23.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220 / 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
12
-
'13•SRK-T-141
Model
Item
SRK12CM-3
Indoor unit SRK12CM-3 Outdoor unit SRC12CM-3 Cooling capacity (1) W 3517 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 1.09
Running current
Cooling
A
5.1
Inrush current 25.0 COP Cooling 3.23 Noise level
Cooling Sound level dB(A) 43 50
Exterior dimensions (Height x Width x Depth) mm 262 x 769 x 210 540 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 29
Refrigerant equipment
Compressor type & Q'ty RMC201A056 (Rotary type) x 1 Motor (Starting method) kW 0.92 (PSC) Refrigerant oil 0.38 (SUNISO 4GSI or ATMOS NM56) Refrigerant (3) kg R22 0.58 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 25 Air flow Cooling m3/min 10.0 32.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line :φ6.35 (1/4") Gas line :φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.45 Gas line : 0.41
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 15
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
13
-
'13•SRK-T-141
Model
Item
SRK12CM-4
Indoor unit SRK12CM-4 Outdoor unit SRC12CM-4 Cooling capacity (1) W 3517 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 1.09 / 1.11
Running current
Cooling
A
5.1 / 5.0
Inrush current 25.0 COP Cooling 3.23 / 3.17 Noise level
Cooling Sound level dB(A) 43 50 / 51
Exterior dimensions (Height x Width x Depth) mm 262 x 769 x 210 540 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 29
Refrigerant equipment
Compressor type & Q'ty RMC201A056 (Rotary type) x 1 Motor (Starting method) kW 0.92 (PSC) Refrigerant oil 0.38 (SUNISO 4GSI or ATMOS NM56) Refrigerant (3) kg R22 0.58 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 25 Air flow Cooling m3/min 10.0 32.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line :φ6.35 (1/4") Gas line :φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.45 Gas line : 0.41
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 15
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220 / 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
14
-
'13•SRK-T-141
Model
Item
SRK12CM-5
Indoor unit SRK12CM-5 Outdoor unit SRC12CM-5 Cooling capacity (1) W 3517 Power supply 1 Phase, 220 - 240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 1.09
Running current
Cooling
A
5.1
Inrush current 25.0 COP Cooling 3.23 Noise level
Cooling Sound level dB(A) 43 50
Exterior dimensions (Height x Width x Depth) mm 262 x 769 x 210 540 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 29
Refrigerant equipment
Compressor type & Q'ty RMC201A056 (Rotary type) x 1 Motor (Starting method) kW 0.92 (PSC) Refrigerant oil 0.38 (SUNISO 4GSI or ATMOS NM56) Refrigerant (3) kg R22 0.58 (Pre-Charged up to the piping length of 5.0m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 25 Air flow Cooling m3/min 10.0 32.0 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat — Operation Display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line :φ6.35 (1/4") Gas line :φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.45 Gas line : 0.41
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 15
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts. (4) The refrigerant quantity to be charged includes the refrigerant in 5.0m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5.0m.
-
15
-
'13•SRK-T-141
2. EXTERIOR DIMENSIONS
(1) Indoor units
Models SRK05CM, 05CM-3
SRK05CMP-3
SRK09CM-3, 09CM-4, 09CM-5
SRK09CMP-3, 09CMP-4
Note(1)Themodelnamelabelisattached
   ontheundersideofthepanel.
60
150
17.3
2555
45
55
45
25
615
615
262
3210
45
609
44
56
247.1
(Servicespace)
15
7.2 7.7
44
56 40152.1
100
(Servicespace)
155.4
181.9 250 181.9
100
(Servicespace)
303 155.4
Unit
100
(Servicespace)
445.9
398.2
Installationplate
Unit:mm
Wirelessremotecontrol
Spaceforinstallationandservicewhenviewingfromthefront
Holeonwallforrightrearpiping
Holeonwallforleftrearpiping
Outletforwiring
Drainhose
Liquidpiping
F
ECD
B
Symbol
(φ65)
VP16
φ6.35(1/4")(Flare)
Content
(φ65)
Outletforpiping(onbothside)
G
Outletfordownpiping
(Refertotheaboveview)
D E AB C
Gaspiping
A
φ9.52(3/8")(Flare)
G
F
Terminalblock
-
16
-
'13•SRK-T-141
G
Terminal block
F
GG
Unit:mm
Wireless remote control
Outlet for down piping
Refer to the above view
Space for installation and service when viewing from the front
D E C
Hole on wall for right rear piping
Hole on wall for left rear piping
Gas piping
Outlet for wiring
Drain hose
Liquid piping
F
ECD
B
Symbol
A
65)
VP16
φ6.35(1/4")(Flare)
Content
65)
Outlet for pipingon both side
G
φ12.7(1/2")(Flare)
AB
Note1The model name label is attached
    on the underside of the indoor unit.
60
150
17.3
190 40.1
47
130.5 508 130.5
157 455 157
187.5 394 187.5
47
7.6247.5
6.9
Service space
65
Service space
15
50
Service space
100
Service space
55
409
449
530
55
Installation plate
Unit
6025 60 25
768.1
45
45
769
262
45
609
210 3
Models SRK12CM-3, 12CM-4, 12CM-5
-
17
-
'13•SRK-T-141
(2) Outdoor units Models SRC05CM, 05CM-3
SRC05CMP-3 SRC09CM-3, 09CM-4, 09CM-5 SRC09CMP-3, 09CMP-4
eralF()"83(25.9φ
Content
C Pipecable draw-out hole
D
E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(gas side)
M10×4places
φ20×2places
Service valve connection(liquid side)
eralF()"41
53.6φ
Minimum installation space
Notes
.sedisruofllanosllawybdednuorrusebtontsumtI1
 (2The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
 (3Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicular ly
to the dominant wind direction.
 (4Leave 1m or more space above the unit.
 (5A wall in front of the blower outlet must not exceed the unit height.
 (6The model name label is attached on the right side of the unit.
L2
L3
L4
L1 600
100
100
Examples of
Dimensions
Unit:mm
mm
installation
Outlet
Intake
L3
L1
L2
Intake
Service
space
( )
L4
Open
322
50
40
12
135
275
120.5
74.5 480 91 19.7
694.2
16.8304.414.8
336
2-16x12
Terminal block
147.2
2
0
°
2
0
°
86.3 43.2
16.5
437
E
D
BCA
-
18
-
'13•SRK-T-141
Models SRC12CM-3, 12CM-4, 12CM-5
eralF()"41(53.6φ
Content
C Pipecable draw-out hole
D
E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(gas side)
M10×4places
φ20×2places
Service valve connection(liquid side)
eralF()"21(7.21φ
L2
Intake
Outlet
Intake
L3
L1
Minimum installation space
Service
space
( )
Notes
.sedisruofllanosllawybdednuorrusebtontsumtI1
 (2 The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
 (3 Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicularly
to the dominant wind direction.
 (4 Leave 1m or more space above the unit.
 (5 A wall in front of the blower outlet must not exceed the unit height.
 (6 The model name label is attached on the right side of the unit.
L4
L2
L3
L4
L1
100
100
600
Open
Examples of
Dimensions
installation
15.8
543.8
390.6
390.6
63.469.4
290
111.6 510 158.4
780 61.9
18.9
14.8
351.6
2-16x12
312.5 24.3
50.6
12
97.7 42.5
Terminal block
40
°
4
0
°
138.4 33.5
19.9
D
E
A
C
B
Unit:mm
mm
-
19
-
'13•SRK-T-141
(3) Wireless remote control
Unit: mm
60
17.3
150
Models All model
Unit: mm
17.3
150
-
20
-
'13•SRK-T-141
3. ELECTRICAL WIRING
(1) Indoor units
Models All model
Printed circuit board
Wireless
R-Amp
Display
CNE
WHRDBK
M
CNW
IC15
ZNR
153
CNU
CF
I
L 52C-3
52C
F
250V 3.15A
CONTROL BOX
Back up Sw
CNG
CNM
N
1
FM
I
T1
Th1
Th2
2N
L
1
Symbol
Meaning of Marks
Parts name Symbol Parts name
Capacitor forCF
IFMI
FM
ZNR
FM
I
Fuse
Fan motor
Flap motor
Varistor
F
Th2
T1
Room temp. thermistor
Heat exchanger thermistor
Terminal block
Th1
BK
Color symbol
BL
Black
Blue
RD
WH
Red
White
BL
WH
BK
Power source
220230240V 50Hz
TO
OUTDOOR
UNIT
U
MFM
-
21
-
'13•SRK-T-141
(2) Outdoor units Models SRC05CM, 05CM-3 SRC05CMP-3 SRC09CM-3, 09CM-4, 09CM-5 SRC09CMP-3, 09CMP-4
Power source
220-240V 50Hz
INDOOR UNIT
FMo
BLACK
ORANGE
WHITE
RED
Cc
ORANGE
CFo
ORANGE
WHITE
WHITE
BLACK
BLACK
WHITE
1 2
T1
WHITE
CM
BLACK
BLACK
51C
2
3
1
RED
C
S
R
T2
WHITE
CAPACITOR
L
1
2/N
ORANGE
Symbol
Meaning of Marks
Parts name
Capacitor for CMCc
Capacitor for FMoCFo
Compressor motorCM
Fan motorFMo
Motor protector for CM51C
Terminal blockT1,T2
OUTDOOR UNIT
-
22
-
'13•SRK-T-141
Models SRC12CM-3, 12CM-4, 12CM-5
Symbol
Meaning of Marks
Parts name
Capacitor for CMCc
Capacitor for FMoCFo
Compressor motorCM
Fan motorFMo
Terminal blockT1,T2
Powersource
220-240V50Hz
INDOORUNIT
BLACK
ORANGE
WHITE
RED
Cc
ORANGE
CFo
ORANGE
WHITE
WHITE
BLACK
BLACK
WHITE
1 2
T1
WHITE
CM
BLACK
RED
C
S
R
T2
WHITE
CAPACITOR
L
1
2/N
ORANGE
OUTDOORUNIT
BLACK
FMo
-
23
-
'13•SRK-T-141
4. PIPING SYSTEM
Outdoor unitIndoor unit
Room temp. sensor
Heat exchanger
Flare connecting
Heat exchanger
sensor
Piping (Liquid) ø6.35
Check joint
Service valve (Liquid)
Flare connecting
Heat exchanger
Compressor
Accumulator
Service valve
(Gas)
Capillary tube
ø9.52
Piping (Gas)
Outdoor unitIndoor unit
Room temp. sensor
Heat exchanger
Flare connecting
Heat exchanger sensor
Piping (Liquid) ø6.35
Check joint
Service valve (Liquid)
Flare connecting
Heat exchanger
Compressor
Capillary tube
Accumulator
Service valve
(Gas)
Capillary tube
Piping (Gas)
ø12.7
Models SRK05CM, 05CM-3 SRK05CMP-3 SRK09CM-3, 09CM-4, 09CM-5 SRK09CMP-3, 09CMP-4
Models SRK12CM-3, 12CM-4, 12CM-5
-
24
-
'13•SRK-T-141
5. RANGE OF USAGE & LIMITATIONS
Net capacity = Capacity shown on specification Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
All model
Models
Item
Indoor return air temperature (
Upper, lower limits
)
Outdoor air temperature (
Upper, lower limits
)
Refer to the selection chart
Refrigerant line (one way) length
Max. 15m
Max. 5m (Outdoor unit is higher
)
Max. 5m (Outdoor unit is lower
)
Min. 3 minutes
Max. 10 times/h
Min. 85% of rating
Vertical height difference between outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON−OFF cycle
ON and OFF interval
Rating 10%
14 16 18 20 22
15
20
25
30
35
40
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
43
24
ISO-T1 Standard ConditionIndoor air W.B. temperature °C W.B.
Cooling
Applicable range
Coefficient of cooling
capacity in relation
to temperature
Cooling operation
Outdoor air D.B.
temperature
°C D.B.
-
25
-
'13•SRK-T-141
(2) Correction of cooling capacity in relation to one way length of refrigerant piping
How to obtain the cooling capacity
Model SRK05CM
=
Piping length [m]
Cooling
7.5
1.0
10
0.99 0.975
15
Models SRK05CM-3
SRK05CMP-3 SRK09CM-3, 09CM-4, 09CM-5 SRK09CMP-3, 09CMP-4 SRK12CM-3, 12CM-4, 12CM-5
Piping length [m]
Cooling
5
1.0
10
0.985 0.97
15
1500
SRK05CM
SRK05CM
1463
-
26
-
'13•SRK-T-141
Safety precautions
Please read these “Safety Precautions” rst then accurately execute the installation work.
Though the precautionary points indicated herein are divided under two headings,
WARNING
and
CAUTION
, those points which are related
to the strong possibility of an installation done in error resulting in death or serious injury are listed in the
WARNING
section. However, there
is also a possibility of serious consequences in relationship to the points listed in the
CAUTION
section as well. In either case, important safety
related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with conrming that no abnormalities were seen from the operation tests, please explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner’s manual.
Moreover, ask the customer to keep this sheet together with the owner’s manual.
WARNING
To disconnect the appliance from the mains supply this appliance must be connected to the mains by means of a circuit breaker or a switch (use a recognized 10A) with a contact separation of at least 3mm.
The appliance shall be installed in accordance with national wiring regulations.
This systemshould be applied to placesas households, residences and thelike. Application to inferiorenvironment such as engineering shopcould
cause equipment malfunction.
Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installations can be the cause of water leakage, electric shocks and res.
Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and res.
For installation, conrm that the installation site can suf ciently support heavy weight. When strength is insuf
cient, injury can result from a
falling of the unit.
For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used. Insufcient power source circuit capacity and defective installment execution can be the cause of electric shocks and res.
This equipmentmust be installed with earth leakage circuit breaker (ELCB). Otherwise, it may causeelectrical shock and re incase of equipment breakdown.
Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it improper connection or securing can result in heat generation or re.
Take care that wiring does not rise upward, and accurately install the lid/service panel. It’s improper installation can also result heat generation or re.
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated refrigerant (R22) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing.
Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, re and refrigerant leakage.
Ventilate the work area when refrigerant leaks during the operation. Coming in contact with re, refrigerant could generate toxic gas.
Conrm after the foundation construction work that refrigerant does not leak. If coming in contact with re of a fan heater, a stove or movable cooking stove, etc., refrigerant leaking in the room could generate toxic gas.
CAUTION
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone ground wire. Improper placement of ground wires can result in electric shock.
The installation of an earth leakage breaker is necessary depending on the established location of the unit. No installing an earth leakage breaker may result in electric shock.
Do not install the unit where there is a concern about leakage of combustible gas. The rare even of leaked gas collecting around the unit could result in an outbreak of re.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
Install the outdoor unit so that the aluminum ns on the air heat exchanger cannot be touched. Failure to observe this may result in injury.
Do not place objects near the outdoor unit or allow leaves to gather around the unit. If there are objects or leaves around the outdoor unit, small
animals may enter unit and contact electrical parts resulting in break down, emission of smoke or ame.
Cautions for installation
The system should be applied to places as households, residences and the like.The equipment shall be installed in accordance with national wiring regulations.The connection to the xed wiring of the mains supply must be made via a double pole isolating switch with a contact gap of at least
3mm in each pole.
When the outdoor unit has a possibility of being overturned or being displaced and fall from its original installation position, the outdoor
unit should be xed in its position by use of anchor bolts or wires.
6. APPLICATION DATA
Models SRK05CM, 05CM-3 SRK09CM-3, 09CM-4, 09CM-5
SRK05CMP-3 SRK09CMP-3, 09CMP-4
-
27
-
'13•SRK-T-141
A place where good air circulation can be obtained and where rain,
snow or sunshine will not directly strike the unit.
A place where discharged hot air or unit’s operating sound will not be a
nuisance to the neighborhood.
A place where servicing space can be secured.A place where vibration will not be enlarged.
*Avoid installing in the following places.
A place near the bedroom and the like, so that the operation noise will
cause no trouble.
A place where there is possibility of flammable gas leakage.
A place exposed to strong wind.
In a salt-laden atmosphere or a place where the generation of oil mist, vapor or fume is expected.
Blowing out port and suction port on the back side of the unit can be installed at a distance of 10cm from walls.
(In case the barrier is 1.2m or above in height, or is overhead, the sufficient space between the unit and wall shall be secured.)
When the unit is installed, the space of the following dimension and above shall be secured.
OUTDOOR UNIT
Selection of installation location
Where there is no obstructions to the air flow and where the cooled
air can be evenly distributed.
A solid place where the unit or the wall will not vibrate.A place where there will be enough space for servicing. (Where
space mentioned right can be secured)
Where wiring and the piping work will be easy to conduct.The place where receiving part is not exposed to the direct rays of
the sun or the strong rays of the street lighting.
A place where it can be easily drained.A place separated at least 1m away from the television or the
radio. (To prevent interfence to images and sounds.)
INDOOR UNIT
Standard accessories
(Installation kit)
Accessories for indoor unit
Q’ty
Installation board (Attached to the rear of the indoor unit)
1
Wireless remote control 1
Remote control holder 1
Tapping screws (for installation board 4dia. by 25mm)
5
Wood screw (for remote control switch holder 3.5dia. by 16mm)
2
Battery [R03 (AAA, Micro) 1.5V]
2
Option parts Q’ty
Sealing plate 1
Sleeve 1
Inclination plate 1
Putty 1
Drain hose (extention hose) 1
Piping cover (for insulation of connection piping)
1
Necessary tools for the installation work
1 Plus headed driver (Phillips screwdriver)
2 Knife
3 Saw
4 Tape measure
5 Hammer
6 Spanner wrench
7
Torque wrench
( )
14.0 ~ 61.0N · m (1.4 ~ 6.1kgf · m)
8 Hole core drill (65mm in diameter)
9 Wrench key (Hexagon) [4m/m]
10 Vacuum pump
11
Vacuum pump adapter (Anti-reverse flow type)
( )
Designed specifically
for R22
12
Gauge manifold
( )
Designed specifically
for R22
13
Charge hose
( )
Designed specifically
for R22
14
Flaring tool set
( )
Designed specifically
for R22
15
Gas leak detector
( )
Designed specifically
for R22
Note (1) If the wall is higher than 1.2 m or a ceiling is present,
distances larger thanindicated in the above table must be provided.
Air intake
Air outlet
No obstacles (Service space for electrical parts)
Air intake
10 cm MIN
60 cm MIN
10 cm MIN
Left side
10 cm
10 cm
Right side
10 cm
-
28
-
'13•SRK-T-141
Installation of indoor unit
Installation of installation board
• Adjustment of the installation board inthe horizontal direction is to be conducted with ve screws in a temporary tightened state.
• Adjust so that board will be level byturning the board with the standard hole as the center.
Standard hole
Limitations for one way piping length and vertical height difference
One way piping length ( )
15 m
Vertical height difference (h)
Outdoor unit is lower
5 m
Outdoor unit is higher
5 m
Look f or the inside wall structu res (Int ersediate support or pillar and raly install the uni t after l evel surface has be en checked.)
Mating mark fo r level surface
250
* Leave extra space on the right side to enable removal of the lid screw.
INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW)
Unit : mm
Drilling of holes and fixture sleeve (Option parts)
Drill a hole with Ø65 whole core drill
Install the sleeve
Adjusting sleeve length
Note (1) Drill a hole with incline of 5 degree from
indoor side to outdoor side.
Wall thickness
+ 1.5 cm
Cut off the sleeve collar that can be seen from beneath the unit.
Cut off the sleeve collar in case of drawing piping out to rear.
Indoor side
Indoor side
Indoor side
View of sleeve when installed
Outdoor side
Outdoor side
Outdoor side
(Inserting sleeve) (*Sleeve + *Inclined + *Sealing plate)
Paste
Sleeve
Turn to tighten
In cli ne d
ange
Seali ng plate
Space for service
Space for service
Space for
service
Space for
service*
Indoor unit
181.9181.9
44
44
40
56
69.9
15
56
100
7.2 7.7
250
Installation board
Piping for Gas 398.2
Piping for Liquid 445.9
Drain hose 386.3 (
Ø16)
Piping hole (
Ø65)
Piping hole (Ø65)
100
100
155.4
155.4
-
29
-
'13•SRK-T-141
Preparation of indoor unit
Mounting of connecting wires
Remove the lid. ⓑRemove the wiring clamp. ⓒConnect the connecting wire securely to the terminal block.
Use cable for interconnection wiring to avoid loosening of the wires. CENELEC code for cables Required eld cables.
75CEI542ro)elpmaxE(5.1G4RNR50H
H Harmonized cable type
05 300/500 volts
R Natural-and/or synth. rubber wire insulation N Polychloroprene rubber conductors insulation R Standed core
srotcudnocforebmuN5ro4
G
One conductor of the cables is the earth conductor (yellow/green)
1.5 Section of copper wire (mm2)
Connect the connection wire securely to the terminal block. If the wire is not afxed completely, contact will be poor, and it is dangerous as the terminal block may heat up and catch re.
Take care not to confuse the t erminal numbers for p ower source indoor and outdoor connections.
Earthlead wireshall be longerthan theother lead wiresfor theelectrical safety in case of the slipping out of the cord from the anchorage.
The earth line of power cord must be properly earthed.
L
N
Connecting diagram.
Power supply source
Terminal on the indoor unit
L 2/N
2
N
L
1
1
Terminal on the outdoor unit
Afx the connection wire using the wiring clamp.
ⓓFix the connecting wire by wiring clamp. ⓔAttach the lid.
Shaping the pipe
Taping of the exterior
Hold the bottom of the pipe and change its direction before stretching it and shaping it.
Tape only the portion that runs through the wall. Always tape the crossover wires with the pipe.
Cautions when piping from the left and the rear center of the unit
[ Top View ]
R emov e th e sc rew an d pull th e drain hose, w hile twisting.
Re move i t wi th ha nd o r pliers.
I nser t th e d rai n c ap w hic h was removed at procedure “2” se cure ly us ing a hex ago nal wrench etc. Note: Be careful that if it is not inserted securely, water leakage may occur.
Insert the drain hose securely, pus h t he dr ain h ose wh ile twisting. Install the screw. Note: Be careful that if it is not ins erted secure ly, water leakage may occur.
Piping is possible in the rear, left, left rear, l eft dow nward, right or downward direction.
Do not place the power supply cords above the gutter, because the air conditioner is structuredin a way where condensation on theback side is collected in to the drain pan before drainage.
Do not make traps in the drain hose line.
Declining slope
Inverted slipe
Trap
* Leave space to allow
removal of this screw after installation.
[ Drain hose changing procedures ]
Pipe
Drain hose
Terminal block
Screw*
Clamp
Lid
Left Side Piping Right Side Piping
Left rear piping
Left side piping
Right rear piping
Right side piping
Right
Left
Left rear
Rear
Downward
Left downward
1. Remove the drain hose. 2. Remove the drain cap. 3. Insert the drain cap. 4. Connect the drain hose.
Gutter
Pipes storage area
Wall
Loading...
+ 67 hidden pages