Mitsubishi Heavy Industries SRK10CNV, SRK13CNS, SRK13CNS-2, SRK10CNS, SRK13CNV Technical Manual

...
RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air cooled cooling only type)
SRK10CNV, 13CNV SRK10CNS, 13CNS SRK10CNS-2, 13CNS-2 SRK19CNS, 25CNS
Manual No.'14•SRK-T-153
-
1
-
'14•SRK-T-153
TECHNICAL MANUAL
1. SRK10CNV, 13CNV SRK10CNS, 13CNS
SRK10CNS-2, 13CNS-2 ............................................. 2
2. SRK19CNS, 25CNS................................................... 38
-
2
-
'14•SRK-T-153
( )
1. SRK10CNV, 13CNV SRK10CNS, 13CNS SRK10CNS-2, 13CNS-2
WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS
Split system, air cooled cooling only type
'10 • SRK-T-099
CONTENTS
1.1 SPECIFICATIONS .................................................................................... 5
(2) Outdoor units .................................................................................... 10
(3) Wireless remote control
.................................................................... 11
........................................................................ 9
(1) Indoor units ......................................................................................... 9
1.2 EXTERIOR DIMENSIONS
1.3 ELECTRICAL WIRING ............................................................................. 12
(1) Indoor units ......................................................................................... 12
(2) Outdoor units ...................................................................................... 14
....................................................... 16
1.5 RANGE OF USAGE & LIMITATIONS
1.4 PIPING SYSTEM ..................................................................................... 15
............................................................................... 18
1.6 APPLICATION DATA
1.7 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 25
(6) 3D auto operation
............................................................................. 29
(7) Timer operation
................................................................................. 30
(5) Flap and louver control ..................................................................... 28
...................................................... 27(4) Custom cord switching procedure
........................................................................ 27(3) Auto restart function
(2) Unit ON/OFF button
.......................................................................... 27
(1) Operation control function by remote control
..................................... 25
(8) Installation location setting ................................................................. 30
(10) Outline of automatic operation .......................................................... 31
(9) Outline of cooling operation .............................................................. 31
(11) Protective control function
.................................................................. 32
.............................................................................. 33
.................... 34
(4) Troubleshooting procedure (If the air conditioner runs)
(3) Troubleshooting procedure
(If the air conditioner does not run at all)
....... 33
(1) Cautions
............................................................................................ 33
(2) Items to check before troubleshooting ................................................ 33
(5) Self-diagnosis table ............................................................................ 34
(6) Inspection procedures corresponding to detail of trouble ................... 35
1.8 MAINTENANCE DATA
-
3
-
'14•SRK-T-153
'10 • SRK-T-099
CONTENTS
1.1 SPECIFICATIONS .................................................................................... 5
(2) Outdoor units .................................................................................... 10
(3) Wireless remote control
.................................................................... 11
........................................................................ 9
(1) Indoor units ......................................................................................... 9
1.2 EXTERIOR DIMENSIONS
1.3 ELECTRICAL WIRING ............................................................................. 12
(1) Indoor units ......................................................................................... 12
(2) Outdoor units ...................................................................................... 14
....................................................... 16
1.5 RANGE OF USAGE & LIMITATIONS
1.4 PIPING SYSTEM ..................................................................................... 15
............................................................................... 18
1.6 APPLICATION DATA
1.7 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 25
(6) 3D auto operation
............................................................................. 29
(7) Timer operation
................................................................................. 30
(5) Flap and louver control ..................................................................... 28
...................................................... 27(4) Custom cord switching procedure
........................................................................ 27(3) Auto restart function
(2) Unit ON/OFF button
.......................................................................... 27
(1) Operation control function by remote control
..................................... 25
(8) Installation location setting ................................................................. 30
(10) Outline of automatic operation .......................................................... 31
(9) Outline of cooling operation .............................................................. 31
(11) Protective control function
.................................................................. 32
.............................................................................. 33
.................... 34
(4) Troubleshooting procedure (If the air conditioner runs)
(3) Troubleshooting procedure
(If the air conditioner does not run at all)
....... 33
(1) Cautions
............................................................................................ 33
(2) Items to check before troubleshooting ................................................ 33
(5) Self-diagnosis table ............................................................................ 34
(6) Inspection procedures corresponding to detail of trouble ................... 35
1.8 MAINTENANCE DATA
-
4
-
'14•SRK-T-153
'10 • SRK-T-099
(9) How to make sure of wireless remote control ..................................... 37
(7)
Phenomenon observed after shortcircuit, wire breakage on sensor
........ 36
(8) Checking the indoor electrical equipment
.......................................... 36
How to read the model name
Example: SRK 10 C
Series code
Cooling only type
Product capacity
Model name SRK : Wall mounted type
SRC : Outdoor unit
NV
-
5
-
'14•SRK-T-153
1.1 SPECIFICATIONS
Model
Item
SRK10CNV
Indoor unit SRK10CNV Outdoor unit SRC10CNV Cooling capacity (1) W 2800 Power supply 1 Phase, 220 V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.77
Running current
Cooling
A
3.5
Inrush current 18 COP Cooling 3.64 Noise level
Cooling Sound level dB(A) 40 45
Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 213 540 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 8.5 28
Refrigerant equipment
Compressor type & Q'ty RMC201A011 (Rotary type) x 1 Motor (Starting method) kW 0.69 (Line starting) Refrigerant oil 0.35 (SUNISO 4GSI or ATMOS NM56) Refrigerant (4) kg R22 0.58 (Pre-Charged up to the piping length of 7.5m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 16 14.5 Air flow Cooling m3/min 10.0 26.5 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
ECONO : Orange
Safety devices
Frost protection, Fan motor error protection,
Internal thermostat (for Compressor)
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.4
Gas line : 0.33
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2.5m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable) Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
,
Clean filter (Natural enzyme filterx1, Photocatalytic washable deodorizing filterx1)
Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C JIS C 9612, TISI 1155, 2134, 812
(2) This air-conditioner is manufactured and tested in conformity with the TISI. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping. (Purging is not required even for the short piping.)
The pipe length is 7.5m.
-
6
-
'14•SRK-T-153
Model
Item
SRK13CNV
Indoor unit SRK13CNV Outdoor unit SRC13CNV Cooling capacity (1) W 3600 Power supply 1 Phase, 220 V, 50Hz
Operation data (1)
Power consumption
Cooling kW 1.00
Running current
Cooling
A
4.7
Inrush current 29 COP Cooling 3.60 Noise level
Cooling Sound level dB(A) 40 49
Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 213 540 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 8.5 36
Refrigerant equipment
Compressor type & Q'ty RMC201A012 (Rotary type) x 1 Motor (Starting method) kW 1.10(Line starting) Refrigerant oil 0.45 (BARREL FREEZE 32SAM) Refrigerant (4) kg R22 0.86 (Pre-Charged up to the piping length of 7.5m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 16 25 Air flow Cooling m3/min 10.0 29.5 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
ECONO : Orange
Safety devices
Frost protection, Fan motor error protection,
Internal thermostat (for Compressor)
Installation data
Refrigerant piping size (O.D) mm Liquid line :φ6.35 (1/4") Gas line :φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.40 Gas line : 0.33
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2.5m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable) Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
,
Clean filter (Natural enzyme filterx1, Photocatalytic washable deodorizing filterx1)
Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C JIS C 9612, TISI 1155, 2134, 812
(2) This air-conditioner is manufactured and tested in conformity with the TISI. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping. (Purging is not required even for the short piping.)
The pipe length is 7.5m.
-
7
-
'14•SRK-T-153
Model
Item
SRK10CNS(-2)
Indoor unit SRK10CNS(-2) Outdoor unit SRC10CNS(-2) Cooling capacity (1) W 2800 Power supply 1 Phase, 220 V, 50Hz
Operation data (1)
Power consumption
Cooling kW 0.77
Running current
Cooling
A
3.5
Inrush current 18 COP Cooling 3.64 Noise level
Cooling Sound level dB(A) 40 45
Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 213 540 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 8.5 28
Refrigerant equipment
Compressor type & Q'ty RMC201A011 (Rotary type) x 1 Motor (Starting method) kW 0.69 (Line starting) Refrigerant oil 0.35 (SUNISO 4GSI or ATMOS NM56) Refrigerant (4) kg R22 0.58 (Pre-Charged up to the piping length of 7.5m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 16 15 Air flow Cooling m3/min 10.0 26.5 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
3D AUTO : Green
Safety devices
Frost protection, Fan motor error protection,
Internal thermostat (for Compressor)
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.4
Gas line : 0.33
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2.5m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable) Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
,
Clean filter (Natural enzyme filterx1, Photocatalytic washable deodorizing filterx1)
Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C JIS C 9612, TISI 1155, 2134, 812
(2) This air-conditioner is manufactured and tested in conformity with the TISI. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping. (Purging is not required even for the short piping.)
The pipe length is 7.5m.
-
8
-
'14•SRK-T-153
Model
Item
SRK13CNS(-2)
Indoor unit SRK13CNS(-2) Outdoor unit SRC13CNS(-2) Cooling capacity (1) W 3600 Power supply 1 Phase, 220 V, 50Hz
Operation data (1)
Power consumption
Cooling kW 1.00
Running current
Cooling
A
4.7
Inrush current 29 COP Cooling 3.60 Noise level
Cooling Sound level dB(A) 40 49
Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 213 540 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 8.5 36
Refrigerant equipment
Compressor type & Q'ty RMC201A012 (Rotary type) x 1 Motor (Starting method) kW 1.10(Line starting) Refrigerant oil 0.45 (BARREL FREEZE 32SAM) Refrigerant (4) kg R22 0.86 (Pre-Charged up to the piping length of 7.5m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 16 25 Air flow Cooling m3/min 10.0 29.5 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
3D AUTO : Green
Safety devices
Frost protection, Fan motor error protection,
Internal thermostat (for Compressor)
Installation data
Refrigerant piping size (O.D) mm Liquid line :φ6.35 (1/4") Gas line :φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.40 Gas line : 0.33
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2.5m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable) Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
,
Clean filter (Natural enzyme filterx1, Photocatalytic washable deodorizing filterx1)
Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C JIS C 9612, TISI 1155, 2134, 812
(2) This air-conditioner is manufactured and tested in conformity with the TISI. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping. (Purging is not required even for the short piping.)
The pipe length is 7.5m.
-
9
-
'14•SRK-T-153
1.2 EXTERIOR DIMENSIONS
(1) Indoor units
All models
Piping hole (ø65)
( )
Piping hole (ø65)
53.5
380.6
Piping for Liquid 448.6 (ø6.35)
10 :ø9.52 13 :ø12.7
Piping for Gas
Drain hose 520 (ø16)
53.5
44.5
252.2
7.5
8.3
102.5
585
102.5
133.5450206.5
202450138
44.5
43.2
39.3
200
45
45
60
17.5
60
27
788
Terminal block
Piping hole right (left)
9
213 3
45
60
268
790
A
VIEW A
Unit:mm
-
10
-
'14•SRK-T-153
(2) Outdoor units
All models
63.4
390.6
390.6
69.4
111.6 510 158.4
780 61.9
17.9
14.8 312.5 24.3
351.6
50.6
12
290
15.8
540
97.7 42.5
40°
40°
138.4 33.5
Anchor bolt holeDrain discharge holes
Terminal block
Service valve (Liquid) Flare connection ø6.35(1/4")
Service valve (Gas) Flare connection 10: ø9.52(3/8") 13: ø12.7(1/2")
Unit:mm
-
11
-
'14•SRK-T-153
(3) Wireless remote control
Unit: mm
60
17.3
150
Unit: mm
60
17.3
150
Models SRK10CNS, 13CNS
SRK10CNS-2, 13CNS-2
Models SRK10CNV, 13CNV
Unit: mm
17.3
150
Unit: mm
17.3
150
-
12
-
'14•SRK-T-153
1.3 ELECTRICAL WIRING
U
MFM
BK
Color symbol
BL BR LB YE
RD
YG
WH
Red
YellowGreen
White
Black
Blue
Brown
Light blue
Yellow
Symbol
Meaning of Marks
Parts name Symbol Parts name
Capacitor forCF
I
FM
I
FM ZNR
FM
I
Fuse Fan motor Flap motor Varistor
Th2 T
Room temp. thermistor Heat exchanger thermistor Terminal block
F
Th1
Power source 220230240V 50Hz
YG
LB
BR
Printed circuit board
T
YG
BL
BR
WH BK
TO OUTDOOR UNIT
Th1
Th2
Wireless R-Amp
Display
CNE
CNG
YE WH RD
M
CNW
IC15
ZNR
1 5 3
CNU
CF
I
52C-4 52C-3
52C
F
250V 3.15A
CONTROL BOX
1
2
Back up Sw
CNM
N
t°
1
FM
I
t°
(1) Indoor units
Models SRK10CNV, 13CNV
-
13
-
'14•SRK-T-153
Models SRK10CNS, 13CNS
SRK10CNS-2, 13CNS-2
U
M
M
M
LM
LM
FM
BK
Color symbol
BL BR LB YE
RD
YG
WH
Red
YellowGreen
White
Black
Blue
Brown
Light blue
Yellow
Symbol
Meaning of Marks
Parts name Symbol Parts name
Capacitor forCF
I
FM
I
FM ZNR
FM
I
Fuse Fan motor Flap motor Varistor
Louver motorRIGHTLM
Th2 T
Room temp. thermistor Heat exchanger thermistor Terminal block
F Th1
Power source 220230240V 50Hz
YG
LB
BR
Printed circuit board
T
YG
BL
BR
WH BK
TO OUTDOOR UNIT
Th1
Th2
Wireless R-Amp
Display
CNE
CNG
YE WH RD
M
CNW
CNY
IC15
ZNR
1 5 3
CNU
CF
I
52C-4 52C-3
52C
F
250V 3.15A
CONTROL BOX
1
2
Back up Sw
CNX
CNM
N
R
Louver motorLEFTLM
L
t°
1
R
L
FM
I
t°
-
14
-
'14•SRK-T-153
(2) Outdoor units
All models
Symbol
Meaning of Marks
Parts name Capacitor for CMCc Capacitor for FMoCFo Compressor motorCM Fan motorFMo Motor protector for CM51C Terminal blockT ConnectorSh
1
Power source 220-240V 50Hz
INDOOR UNIT
FMo
BLACK ORANGE
WHITE
RED
WHITE
Cc
ORANGE
CFo
WHITE
ORANGE
WHITE
WHITE
BLACK
BLACK
WHITE
1 2
T
WHITE
CM
BLACK
BLACK
51C
2
3
1
RED
C
S
R
Sh
1
T
WHITE
1 2
CAPACITOR
-
15
-
'14•SRK-T-153
1.4 PIPING SYSTEM
Outdoor unitIndoor unit
Room temp. sensor
Heat exchanger
Flare connecting
Heat exchanger sensor
Liquid pipe
ø6.35
Check joint
Service valve (Liquid)
Flare connecting
Heat exchanger
Compressor
Capillary tube
Accumulator
Service valve
Cooling cycle
(Gas)
Capillary tube
10 : ø9.52
Gas pipe
13 : ø12.7
( )
All models
-
16
-
'14•SRK-T-153
1.5 RANGE OF USAGE & LIMITATIONS
Net capacity = Capacity shown on specification Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
All models
Models
Item
Indoor return air temperature (
Upper, lower limits
)
Outdoor air temperature (
Upper, lower limits
)
Refer to the selection chart
Refrigerant line (one way) length
Max. 15m
Max. 5m (Outdoor unit is higher
)
Max. 5m (Outdoor unit is lower
)
Min. 3 minutes
Max. 10 times/h
Min. 85% of rating
Vertical height difference between outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON−OFF cycle
ON and OFF interval
Rating 10%
14 16 18 20 22
15
20
25
30
35
40
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
43
24
ISO-T1 Standard ConditionIndoor air W.B. temperature °C W.B.
Cooling
Applicable range
Coefficient of cooling
capacity in relation
to temperature
Cooling operation
Outdoor air D.B.
temperature
°C D.B.
-
17
-
'14•SRK-T-153
(2) Correction of cooling capacity in relation to one way length of refrigerant piping
How to obtain the cooling capacity
=
Piping length [m]
Cooling
7
1.0
10
0.99 0.975
15
3600
SRK13CNV
SRK13CNV
3510
-
18
-
'14•SRK-T-153
1.6 APPLICATION DATA
Safety precautions
Please read these “Safety Precautions” first then accurately execute the installation work.
Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points which are
related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed in the CAUTION section as well. In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please expla in operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner’s manual.
Moreover, ask the customer to keep this sheet together with the owner’s manual.
WARNING
To disconnect the appliance from the mains supply this appliance must be connected to the mains by means of a circuit breaker or a switch (use a recognized 20A) with a contact separation of at least 3mm.
The appliance shall be installed in accordance with national wiring regulations.
This system should be applied to places as households, residences and the like. Application to inferior environment such as engineering shop
could cause equipment malfunction.
Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installa­tions can be the cause of water leakage, electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires.
For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient, injury can result from a falling of the unit.
For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used. Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and fires.
Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it improper connection or securing can result in heat generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. It’s improper installation can also result heat generation or fire.
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated refrigerant (R22) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing.
Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water
leakage, electric shock, fire and refrigerant leakage.
Ventilate the work area when refrigerant leaks during the operation. Coming in contact with fire, refrigerant could generate toxic gas.
Confirm after the foundation construction work that refrigerant does not leak. If coming in contact with fire of a fan heater, a stove or movable cooking stove, etc., refrigerant leaking in the room could generate toxic gas.
CAUTION
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone ground wire. Improper placement of ground wires can result in electric shock.
The installation of an earth leakage breaker is necessary depending on the established location of the unit. No installing an earth leakage breaker may result in electric shock.
Do not install the unit where there is a concern about leakage of combustible gas. The rare even of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
Install the outdoor unit so that the aluminum fins on the air heat exchanger cannot be touched. Failure to observe this may result in injury.
Do not place objects near the outdoor unit or allow leaves to gather around the unit. If there are objects or leaves around the outdoor unit, small
animals may enter unit and contact electrical parts resulting in break down, emission of smoke or flame.
Cautions for installation
The system should be applied to places as households, residences and the like.The equipment shall be installed in accordance with national wiring regulations.The connection to the fixed wiring of the mains supply must be made via a double pole isolating switch with a contact gap of at least
3mm in each pole.
When the outdoor unit has a possibility of being overturned or being displaced and fall from its original installation position , the
outdoor unit should be fixed in its position by use of anchor bolts or wires.
-
19
-
'14•SRK-T-153
Necessary tools for the installation work
1 Plus headed driver (Phillips screwdriver)
2 Knife
3 Saw
4 Tape measure
5 Hammer
6 Spanner wrench
7 Torque wrench
8 Hole core drill (65mm in diameter)
9 Wrench key (Hexagon)
[4m/m]
10 Vacuum pump
11
Vacuum pump adapter (Anti-reverse flow type)
12 Gauge manifold
13 Charge hose
14 Flaring tool set
15 Gas leak detector
( )
Standard accessories
(Installation kit) Q’ty
Accessories for indoor unit
Installation board
1
(Attached to the rear of the indoor unit)
Wireless remote control 1
Remote control holder 1
Tapping screws
5
(for installation board 4dia. by 25mm)
Wood screw
2
(for remote contorol switch holder 3.5dia. by 16mm)
Baterry [R03 (AAA, Micro) 1.5V]
2
Air-cleaning filters 2
Filter holders
2
(Attached to the front panel of the indoor unit)
Option parts Q’ty
1etalp gnilaeS
1eveelS
Inclination plate 1
1yttuP
Drain hose (extention hose) 1
Piping cover (for insulation of
1
connection piping)
A place where good air circulation can be obtained and where rain,
snow or sunshine will not directly strike the unit.
A place where discharged hot air or unit’s operating sound will not
be a nuisance to the neighborhood.
A place where servicing space can be secured.A place where vibration will not be enlarged.
*Avoid installing in the following places.
A place near the bedroom and the like, so that the operation noise
will cause no trouble.
A place where there is possibility of flammable gas leakage.
A place exposed to strong wind.
In a salt-laden atmosphere or a place where the generation of oil mist, vapor or fume is expected.
Blowing out port and suction port on the back side of the unit can be installed at a distance of 10cm from walls.
(In case the barrier is 1.2m or above in height, or is overhead, the sufficient space between the unit and wall shall be secured.)
When the unit is installed, the space of the following dimension and above shall be secured.
OUTDOOR UNIT
Note (1) If the wall is higher than 1.2 m or a ceiling is
present, distances larger than indicated in the above table must be provided.
Selection of installation location
Where there is no obstructions to the air flow and where the
cooled air can be evenly distributed.
A solid place where the unit or the wall will not vibrate.A place where there will be enough space for servicing. (Where
space mentioned right can be secured)
Where wiring and the piping work will be easy to conduct.The place where receiving part is not exposed to the direct rays of
the sun or the strong rays of the street lighting.
A place where it can be easily drained.A place separated at least 1m away from the television or the ra-
dio. (To prevent interfence to images and sounds.)
INDOOR UNIT
Left side
Right side
14.0 ~ 61. 0N · m (1.4 ~ 6.1 kgf · m)
( )
Designed s pecifically
for R22
( )
Designed s pecifically
for R22
( )
Designed s pecifically
for R22
( )
Designed s pecifically
for R22
( )
Designed s pecifically
for R22
10 cm
5 cm
10 cm
-
20
-
'14•SRK-T-153
Installation of indoor unit
Installation of installation board
• Adjustment of the installation board in the horizontal direction is to be conducted with five screws in a temporary tightened state.
• Adjust so that board will be level by turning the board with the standard hole as the center.
Standard hole
Look for the inside wall structures (Intersediate support or pillar and firaly install the unit after level surface has been checked.)
Mating mark for level surface
450
INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW)
Unit : mm
Piping hole( 65) Piping hole( 65)
Installation board
Indoor unit
53.5
Piping for Gas 380.6
Piping for Liquid 448.6
Drain hose 520( 16)
53.5
Space
for service*
Space
for service
44.5
252.2
7.5
8.3
Space for
service
50
Space for service 100
102.5
585
102.5
133.5
450206.5
202450138
44.5
43.2
39.3
200
100
15
Limitations for one way piping length and vertical height difference
One way piping length ( ) 15 m
Outdoor
unit is lower
5 m
Outdoor unit
is higher
5 m
Vertical height
difference (h)
* Leave extra space on the right side to enable removal of the lid screw.
-
21
-
'14•SRK-T-153
Preparation of indoor unit
Pipe
Drain hose
Mounting of connecting wires
Remove the lid.Remove the wiring clamp.Connect the connecting wire securely to the terminal block.
Use cable for interconnection wiring to avoid loosening of the wires. CENELEC code for cables Required field cables.
H05RNR3G1.5 (Example) or 245IEC57
H Harmonized cable type 05 300/500 volts R Natural-and/or synth. rubber wire insulation N Polychloroprene rubber conductors insulation R Standed core
4or5 Number of conductors
G One conductor of the cables is the earth conductor (yel-
low/green)
1.5 Section of copper wire (mm
2
)
Connect the connection wire securely to the terminal block. If the wire is not affixed completely, contact will be poor, and it is dangerous as the terminal block may heat up and catch fire.
Take care not to confuse the terminal numbers for indoor and outdoor connections.
Affix the connection wire using the wiring clamp.
Fix the connecting wire by wiring clamp.Attach the lid.Close the air inlet panel.
For power supply, indoor outdoor
For power supply, indoor outdoor
1 Brown
2 Blue
Shaping the pipe
Taping of the exterior
Hol d the bottom of the pipe and change its direc­tion befor e stretching it and shap ing it.
Tap e only the p ortion that runs throug h the wall . Always ta pe the cros sover wires with the p ipe.
Cautions when piping from the left and the rear center of the unit
[ Top View ]
L oose n and r emov e the spring-typ e clamp.
Rem ove with your hand or a pair of pliers.
Use a hexagonal wrench to correctly insert the drain cap which was removed in 2. Caution: Be careful because if th e cap i s not i nse rted pro perty , water l eak may occur.
Lo osen the spring-type clamp and sec urely inse rt the drai n hose. Caution: Be care ful because if the drai n hos e is not i nsert ed properly, wa ter leak ma y occur.
gnipiP ediS thgiRgnipiP ediS tfeL
Right rear pipingLeft rear piping
gnipip edis thgiRgnipip edis tfeL
Left downward
Right
Rear
Downward
Left rear
Left
Piping is possible in the rear, left, left rear, left downward, right or downward direction.
Do not place t he power su pply cords above the gutter, bec ause the air conditioner is structur ed i n a way wh ere condensati on o n th e back side is collect ed in to th e drain pan before dra inage.
Do not make tr aps in the drain hose line.
Declining slope
Inverted s lipe
Trap
* Leave space to allow
removal of this screw
after installation.
[ Procedure for exchanging the drain hose ]
Wall
Gutter
Pipes storage area
-
22
-
'14•SRK-T-153
Installing steps
1.Hook the upper part of the indoor unit to the installation board.
2.The unit can be installed simply by gently push­ing in the lower part.
Securing the indoor unit to the installation board
Wall
Indoor un it base low er latch
Installati on board
Latch (2 l ocations)
Installati on board
Indoor uni t
How to remove the indoor unit from the installation board
Push up at the marked portion of the indoor unit base
lower latch, and slightly pull it toward you. (both right and left hand sides) (The indoor unit base lower latch can be removed from the installation board)
Push up the indoor unit upward. So the indoor unit
will be removed from the installation board.
Removal and installation of the front panel
Open/close and detachment/attachment of air inlet panel
Set screw s
Removing
Remove the 2 set screws.
Mov e the lower part of the panel forward and push
upwards to remove. (Remove the 3 latches in the upper section.)
Fitting
Do remove the air filter.
Cover the body with the front panel.
Push the circled portion at the front.
Tighten the 2 set screws.
Fit the air filter. Carry out in the above order.
To open, pull the panel at both ends of lower part and
rel ease lat ches, then pull up th e panel unt il you feel resistance. (The air inlet panel stops at approx. 60˚ open position.)
To close, hold the panel at both ends of lower part to lower
downward and push it slightly until the latch works, then push the center portion slightly.
To remove, pull up the panel to the position shown in right
illustration and pull it toward you.
To install, insert the air inlet panel arm into the slot on the
front panel from the position shown in right illustration, hold the panel at both ends of lower part, lower it downward slow ly, then push it slightly until the latch works and further push the center portion slightly.
The marke d portion o f the indoor un it base low er latch
-
23
-
'14•SRK-T-153
1 2
Installation of outdoor unit
For power supply, indoor outdoor
For power supply, indoor outdoor
1 Brown
2 Blue
Make sure that the unit is stable in installation. Fix the unit
to stable base.
Perfrom wiring, making wire terminal numbers conform to
terminal numbers of indoor unit terminal block.
Terminal block
Interconne cting wi re
Connection of refrigerant pipings
Preparation
Connection of refrigerant piping
Air purge
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. from entering them.
Specified torquing value: Liquid side (ø6.35) : 14~18N·m (1.4~1.8kgf·m) Gas side (ø9.52) : 34~42N·m (3.4~4.2kgf·m) Gas side (ø12.7) : 49~61N·m (4.9~6.1kgf·m)
Use one more spanner to fix the valve.
Tighten all flare nuts in the pipings both indoor and outside wall so as not to cause leak.Connect service valve, charge hose, manifold valve and vacuum pump as is illustrated below.Open manifold valve handle Lo to its full width, and perform vacuum or evacuation.
Continue the vacuum or evacuation operation for 15 minutes or more and check to see that the vacuum gauge reads – 0.1 MPa (– 76 cmHg).
After completing vacuum operation, fully open service valve (Both gas and liquid sides) with hexagon headed wrench.Detach the charge hoses.Check for possible leakage of gas in the connection parts of both indoor and outdoor.
Remo ve the flar ed nuts. (on both liquid and gas sides)
Rem ove the fla red nuts. (on both l iquid and ga s sides)
Inst all the remov ed flared nuts t o the pipes to be con­nected, th en flare t he pipes.
Dimension A Liquid si de (ø6.35): 9.0 dia Gas side (ø9.52): 13.0 di a (ø12.7): 16.2 d ia
Press
Remove
Remove
(Do not turn)
Spanner
for fixing the piping )
Torque wrench
Specified torquing value: Liquid side (ø6.35) : 14~18N·m (1.4~1.8kgf·m) Gas side (ø9.52) : 34~42N·m (3.4~4.2kgf·m) Gas side (ø12.7) : 49~61N·m (4.9~6.1kgf·m)
Indoor unit side
Outdoor unit side
Indoor unit side Outdoor unit side
Connect firmly gas and liquid side pipings by Torque wrench.
Connect firmly gas and liquid side pipings by Torque wrench.
Always use a Torque wrench and back up spanner to tighten the flare nut.
Manifol d Valve
-76 cm Hg
Handle Lo (pressure )
Charge ho se
Stop valv e (Two-way valve)
Service p ort
Stop value (Three- way value)
Compound (Gauge)
Pressure gauge
Handle Hi (pressure)
Charge ho se
Vacuum pu mp
-
24
-
'14•SRK-T-153
When refrigerant piping exceeds 7.5m conduct additional refrigerant charge after refrigerant sweeping.
7.5m over 15m:Additional charge amount per meter = 10g/m
[Example]
How much amount of additional charge for 15m piping?
(15 – 7.5)m × 10g/m=75g 75g for additional charge
Additional refrigerant charge
Installation of wireless remote control
Insulation of connecting portion
Mounting method of battery
Earthing work
Cover the connection portion of the refrigerant piping with the
pipe cover and seal them. If neglecting to do so, moisture occurs on the piping and water
will drip out.
Finishing and fixing
Tie up the piping with wrapping tape, and shape it so that it con-
forms to which the pipe is attached.
Fix them with clamps as right figure.
Vinyl tap e
To c over the c onnecting portion with insula­tion mate rials, cut upper porti on and then seal it with i nsulation m aterials.
Cover th e exterior portion with cov ­ering ta pe and sh ape the piping so it will m atch the contou rs of the route that the piping to take . Al so fi x th e wiring and pipi ngs to the wall with clamps.
Insulation
Refrigeran t piping Electrica l wiring
Covering tape Drain hos e
Tapping s crew
-
+
Uncover the wireless remote control, and mount the bat­teries [R03(AAA, Micro)×2 pieces] in the body regu­larly.
(Fit the poles with the indication marks, ⊕ & ⊖without fail)
Earth work shall be carried out without fail in order to prevent electric shock and noise generation.
The connection of the earth cable to the following substances causes dangerous failures, therefore it shall never be done.
City water pipe, Town gas pipe, TV antenna, lightning conductor, telephone line, etc.
Trial run and operation
Conduct trial run after confirming that there is no gas leaks.When conducting trial run set the remote control thermostat to continuous operation position. However when the power source is cut
off or when the unit’s operation switch is turned off or was turned to fan operation position, the unit will not go into opera tion in order to protect the compressor.
Explain to the customer on the correct usage of the air-conditioner in simple layman’s terms.Make sure that drain flows properly.
Battery
Cover
Fixing to pillar or wall
Conventionally, operate the wireless remote control by holding in your hand.
Avoid installing it on a clay wall etc.
Screws
+
-
-
25
-
'14•SRK-T-153
Remote control
1.7
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
(1) Operation control function by remote control
Operation section
Models SRK10CNV, 13CNV
ECONO light (orange)
Illuminate s during ECO NOMY operati on.
HI POWER light (green)
Illuminate s during H IGH POWER opera tion.
RUN light (green)
Illuminate s during o peration and CLEAN operation.
TIMER light (yellow)
Illuminate s during TIM ER operatio n.
FAN SPEED button
Each time the button i s pushed, th e indicator is switche d over in t urn.
HI POWER/ECONO button
This butt on changes the HIGH PO WER/ ECONOMY mo de.
TEMPERATURE Button
This butt on sets the room tempe rature. (This but ton changes the presen t time and
TIMER time .)
ON TIMER button
This butt on selects ON TIMER op eration.
SLEEP button
This butt on changes to SLEEP op eration.
CLEAN switch
This swic h changes t he CLEAN mo de.
OPERATION MODE select button
Each time the button pushed, th e indicator is switched over in turn .
ON/OFF (luminous) button
Press for starting o peration, p ress agian for stoppi ng.
AIR FLOW (UP/DOWN) button
This butto n changes th e air flow ( up/ down) mode .
The above illustration shows all controls, but in practi ce only the r elevant parts a re shown.
OFF TIMER button
This butto n selects OFF TIMER o peration.
CANCEL button
This butt on cancels the ON time r, OFF timer, and SLEEP opera tion.
RESET switch
Switch fo r resetting microcompu ter and setting t ime.
Unit display section
-
26
-
'14•SRK-T-153
Operation section
Unit display section
Models SRK10CNS, 13CNS
SRK10CNS-2, 13CNS-2
3D AUTO light (green)
Illuminate s during 3D AUTO operation.
HI POWER light (green)
Illuminate s during HI GH POWER opera tion.
RUN light (green)
Illuminate s during op eration and CLEAN operation.
TIMER light (yellow)
Illuminate s during TIM ER operatio n.
Operation and indication section for remote control
Operation section
SRK10YJV-S SRK13YJV-S
FAN SPEED button
Each time the button is pushed, the indicator is switched ov er in turn.
v
The above illustratio n shows all controls, but in practice only the r elevant par ts are show n.
OPERATION MODE select button
Each time the button push ed, the indicator is switched ove r in turn.
ON/OFF (luminous) button
Press for sta rting operat ion, press again for stoppi ng.
HI POWER/ECONO button
This butt on ch anges th e HIG H POW ER/ ECONOMY mo de.
AIR FLOW (UP/DOWN) button
This butto n changes t he air flow (up/down) mode .
This butto n changes t he air flow (left/righ t) mode.
SLEEP button
This butto n changes t o SLEEP ope ration.
CLEAN switch
This switc h changes t he CLEAN mo de.
ON TIMER button
This butto n selects O N TIMER ope ration.
AIR FLOW (LEFT/RIGHT) button
3D AUTO button
Thi s b utto n set s 3D AUTO ope ratio n.
Thi s b utto n can cels the ON t imer, OFF timer, and SLE EP operatio n.
CANCEL button
RESET switch
Switch for resetting microcomput er and setting ti me.
OFF TIMER button
This butto n selects O FF TIMER op eration.
TEMPERATURE button
This butto n sets the room temper ature. (This butt on changes the pre sent time a nd
TIMER time .)
Remote control
-
27
-
'14•SRK-T-153
(2) Unit ON/OFF button
When the remote control batteries become weak, or if the remote control is lost or malfunctioning, this button may be used to
turn the unit on and off.
(a) Operation
Push the button once to place the unit in the automatic mode. Push it once more to turn the unit off.
(b) Details of operation
The unit will go into the automatic mode in which it automatically determines, from room temperature (as detected by
sensor), whether to go into the cooling or thermal dry modes.
(3) Auto restart function
(a)
Auto restart function records the operational status of the air-conditioner immediately prior to be switched off by a power
cut, and then automatically resumes operations after the power has been restored.
(b)
The following settings will be cancelled:
(i) Timer settings
(ii) HIGH POWER operations
Notes (1) Auto restart function is set at on when the air-conditioner is shipped from the factory.
Consult with your dealer if this function needs to be switched off.
(2) When power failure ocurrs, the timer setting is cancelled. Once power is resumed, reset
the timer.
(3)
If the jumper wire (J7) “AUTO RESTART” is cut, auto restart is disabled. (See the diagram
at right)
(4) Custom cord switching procedure
If two wireless remote control are installed in one room, in order to prevent wrong
operation due to mixed signals, please modify the printed circuit board in the indoor
unit’s control box and the remote control using the following procedure. Be sure to
modify both boards. If only one board is modied, receiving (and operation) can-
not be done.
(a) Modifying the indoor unit’s printed circuit board
Take out the printed circuit board from the control box and cut off jumper
wire (J6) using wire cutters.
After cutting of the jumper wire, take measures to prevent contact with the other
the lead wires, etc.
(b) Modifying the wireless remote control
(i) Remove the battery.
(ii) Cut the jumper wire shown in the gure at right.
Cut
Function
Operation mode
Room temperature
setting
Fan speed
Flap
Timer switch
COOL
About 23ºC
Auto Auto Continuous
DRY
About 24ºC
Jumper wire (J7)
Jumper wire (J6)
Unit ON/OFF button
In emergen cies, this button c an be used for turni ng on/off the unit when remote con trol is not availab le.
Page 15
RUN light (green)
Illuminate s during operation and CLEAN operation.
TIMER light (yellow)
Illuminate s during TIMER oper ation.
Unit ON/OFF button
-
28
-
'14•SRK-T-153
(5) Flap and louver control (Louver control function only CNS and CNS-2 models)
(a) Flap
(b) Louver
(c) Swing
(i)
(d) Memory flap (Flap or Louver stopped)
(e) When not operating
COOL , DRY, FAN
Remote control display
Approx. 10° Approx. 20° Approx. 30°
(Swing)
(Flap stopped)
Approx. 45° Approx. 60°
Angle of Flap from Horizontal
Center installation
Remote control display
Right end installation
Left end installation
Angle of Louver
Left Approx. 45°
Left Approx. 45°
Left Approx. 20°
Left Approx. 30°
Center
Left Approx. 20°
Right Approx. 20°
Center
Right Approx. 45°
Right Approx. 20°
Left Approx. 20°
Center
Right Approx. 20° Right Approx. 30° Right Approx. 45°
(Louver stopped)
(Swing) (Spot) (Wide)
In COOL, DRY, FAN operation
Approx.
10°
Approx. 60°
(ii)
-
29
-
'14•SRK-T-153
(6) 3D auto operation (only CNS and CNS-2 models)
Operation step
Flap
Louver
Conditions for jumping to next STEP
Fan speed Setting fan speed
_
20 cycle
60 cycle
60 cycle
Auto : HIGH POWER
Setting fan speed
STEP1 STEP2 STEP3 STEP4
Left louver
The left louver and right louver operate in the same direction left and right.
The left louver and right louver operate in opposite directions to each other on the left and right sides.
The left louver and right louver operate in opposite directions to each other on the left and right sides.
Right louver
Left louver Right louver
Left louver Right louver
1.4.6 3D auto operation
(only SRK10CJV-2, 13CJV-2)
Control the flap and louver by 3D AUTO button on the wireless remote control.
Fan speed and air flow direction are automatically controlled, allowing the entire room to efficiently conditioned.
(a) Detail of operation
(i) Perform STEP1 → STEP2 → STEP3 → STEP4 one time.
(ii) After performing STEP4 in (i) above, the next steps to be carried out are determined by the difference between
the room
temperature and the setting temperature.
1) Room temperature – Setting temperature > 5ºC: STEP2 STEP3 →→ STEP4 are performed.
2) Room temperature – Setting temperature
<
5ºC: STEP3
=
STEP4 are performed.
Other than Auto: Setting fan speed
Loading...
+ 119 hidden pages