7
-
'14 • SCM-T-167
Model
Item
SCM80ZM-S
Cooling capacity (1) W 8000 (1800 (Min.)−9200 (Max.))
Heating capacity (1) W 9300 (1500 (Min.)−9800 (Max.))
Power source 1 Phase, 220−240 V, 50Hz
Operation
data (1)
Power
consumption
Cooling
kW
2.16 (0.48−2.83)
Heating 2.26 (0.60−3.43)
Running
current
Cooling
A
9.9 / 9.4 / 9.0 (220 / 230 / 240 V)
Heating 10.4 / 10.0 / 9.5 (220 / 230 / 240 V)
Inrush current 10.4 / 10.0 / 9.5 (220 / 230 / 240 V)
Max current (5) 20
COP
Cooling 3.70
Heating 4.12
Noise
level
Cooling
Sound level dB(A) 54
Power level dB 66
Heating
Sound level dB(A) 54
Power level dB 66
Exterior dimensions (Height x Width x Depth) mm 750 x 880 x 340
Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 62
Refrigerant
equipment
Compressor type & Q'ty RM-T5118MDE2 (Twin rotary type) x 1
Motor (Starting method) kW 1.4 (Line starting)
Refrigerant oil
0.675 (DIAMOND FREEZE MA68)
Refrigerant (4) kg R410A 3.15 (Pre-Charged up to the piping length of 40m)
Heat exchanger M fins & inner grooved tubing
Refrigerant control Capillary tubes + Electronic expansion valve
Device control Microcomputer control
Air handling
equipment
Fan type & Q'ty Propeller fan x 1
Motor W 86
Air flow
Cooling
m
3
/min
56.0
Heating 56.0
Shock & vibration absorber Cushion rubber (for compressor)
Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation
data
Refrigerant piping size (O.D) mm
Liquid line:φ6.35 (1/4") × 4
Gas line:φ9.52 ( 3/8") × 4
Connecting method Flare connecting
Insulation for piping Necessary (Both sides), independent
Length for one indoor unit
m
Max. 25
Total length for all rooms Max. 70
Vertical height difference between
outdoor unit and indoor unit
Max. 20 (Outdoor unit is higher)
Max. 20 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 25
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4
Accessories (included) Union : (φ9.52扌φ12.7) × 2, Installation sheet, Elbow, Grommet × 2
Indoor unit to be combined
SRK20,25,35,50,60ZMX(A)-S
SRK20,25,35,50ZM(A)-S
SRF25,35,50ZMX(A)-S
SRR25,35,50ZJ-S,60ZJ-S1
FDTC25,35,50,60VF
FDEN50VF,FDUM50VF
Number of connectable indoor units Min. 2−Max. 4
Total of indoor units kW Max. 13.5
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO -T1 , J IS C 9 612
Heating 20˚C — 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) The operation data are applied to the 220/230/240V districts respectively.
(4) The refrigerant quantity to be charged includes the refrigerant in 40m connecting piping.
(Purging is not required even for the short piping.)
(5) Current value at maximum number of indoor units connected.
The pipe length for one indoor unit is 7.5m.
Adapted to RoHS directive
RWC 000 Z28 4