3
-
Item
Model
FDTCA201R FDCVA402HESAR
Nominal cooling capacity
(1)
kW 10.0 [6.1~11.2]
Nominal heating capacity
(1)
kW 11.2 [5.6~12.5]
Power source 3 Phase, 380-415V 50Hz/380V 60Hz
Cooling power consumption kW 2.84/2.84
Running current (Cooling) A 4.2/4.4
Power factor (Cooling) % 98/98
Heating power consumption kW 3.08/3.08
Running current (Heating) A 4.5/4.8
Power factor (Heating) % 99/97
Inrush current (L.R.A) A 5
Noise level dB(A)
35 52
Exterior dimensions
mm
Unit 248 × 570 × 570
845 × 970 × 370
Height × Width × Depth Panel 35 × 700 × 700
Net weight kg 19.5 (Unit:16 Panel:3.5) 74
Refrigerant equipment
– RM-B5125MDE31
Compressor type & Q’ty
Starting method – Direct line start
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control – Electronic expansion valve
Refrigerant R410A
Quantity kg –
3.8 [Pre-charged up to the piping length of 30m]
Refrigerant oil r – 0.7 (M-MA68)
Defrost control Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Turbo fan × 1 Propeller fan × 1
Motor W 50 × 1 120 × 1
Starting method Direct line start Direct line start
Air flow CMM Cooling: 75, Heating: 73
Outside air intake Available –
Air filter, Q’ty Long life filter ×1(washable) –
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber mount (for compressor)
Electric heater W – 20 (Crank case heater)
Operation control Wired remote control switch (Optional : RC-E1R)
Operation switch Wireless kit (Optional:RCND-KIT-HER)
– (Indoor unit side)
Room temperature control Thermostat by electronics –
Safety equipment Internal thermostat for fan motor. Internal thermostat for fan motor.
Frost protection thermostat. Anomalous discharge temperature protection.
Installation data Liquid line mm Indoor branch pipe, Outdoor main pipe: φ9.52 (3/8″)
Refrigerant piping size Gas line (in) Indoor branch pipe: φ12.7 (1/2″), Outdoor main pipe: φ15.88 (5/8″)
Connecting method Flare piping
Drain hose Connectable with VP25 (I.D.25mm, O.D.32mm) –
Insulation for piping Necessary (both Liquid & Gas lines)
Accessories Mounting kit. Drain hose
Optional parts Decorative Panel
Operation data
(3)
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
(5) Indoor unit specifications show the specifications for one unit. Capacity and running characteristics values are shown for the case where two indoor units
are combined and run together.
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C – 7˚C 6˚C
ISO-T1
FDTCVA402HESP2R
Powerful mode Hi:46 Me:42 Lo:38
Mild mode Hi:42 Me:38 Lo:35
Powerful mode Hi:13.5 Me:11.5 Lo:10
Mild mode Hi:11.5 Me:10 Lo:8
50
1.2 SELECTION DATA
1.2.1 Specifications
(1) Ceiling recessed compact type (FDTC)
(a) Twin type
Model FDTCVA402HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)