Series code
Inverter type
Product capacity (Cooling capacity : 2.0kW)
Model nameSRK : Wall mounted type
SRC : Outdoor unit
-
-
2
'18 • SRK-T-250
1. SPECIFICATIONS
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230540 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg9.531.5
Compressor type & Quantity—RM-C5077SBE71( Rotary type ) x 1
Compressor motor (Starting method)kW—0.75 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.30 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length)kgR32 0.62 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A3.2 / 3.0 / 2.9 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green, TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.20
Vertical height diff. between O.U. and I.U.mMax.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
SRK20ZS-W
0.44 ( 0.19 - 0.80 )
2.6 / 2.5 / 2.4 (220/ 230/ 240V)
79
( 4.2Y 7.5/1.1 ) , ( 7044 )
Rubber sleeve (for fan motor & compressor)
The pipe length is 5m.
Standards
Max. 9
Stucco white
RWA000Z274
-
-
3
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230540 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg9.531.0
Compressor type & Quantity—RM-C5077SBE71( Rotary type ) x 1
Compressor motor (Starting method)kW—0.75 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.30 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length)kgR32 0.62 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A3.7 / 3.6 / 3.4 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.20
Vertical height diff. between O.U. and I.U.mMax.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z274
-
-
4
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230540 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg9.534.5
Compressor type & Quantity—RM-B5077SBE2( Rotary type ) x 1
Compressor motor (Starting method)kW—0.90 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.30 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length)kgR32 0.78 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A4.6 / 4.4 / 4.2 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.20
Vertical height diff. between O.U. and I.U.mMax.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z274
-
-
5
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230595 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg10.036.0
Compressor type & Quantity—9RS102XDA21( Rotary type ) x 1
Compressor motor (Starting method)kW—1.50 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.32 ( FW50S )
Refrigerant (Type, amount, pre-charge length)kgR32 1.05 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA20
L.R.A. (Locked rotor ampere)A7.2 / 6.9 / 6.6 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2" )
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.25
Vertical height diff. between O.U. and I.U.mMax.15 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z274
-
-
6
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230540 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg9.531.0
Compressor type & Quantity—RM-C5077SBE71( Rotary type ) x 1
Compressor motor (Starting method)kW—0.75 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.30 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length)kgR32 0.6 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A3.2 / 3.0 / 2.9 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.20
Vertical height diff. between O.U. and I.U.mMax.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z274
-
-
7
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230540 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg9.531.0
Compressor type & Quantity—RM-C5077SBE71( Rotary type ) x 1
Compressor motor (Starting method)kW—0.75 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.30 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length)kgR32 0.62 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A3.7 / 3.6 / 3.4 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.20
Vertical height diff. between O.U. and I.U.mMax.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z274
-
-
8
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230540 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg9.534.5
Compressor type & Quantity—RM-B5077SBE2( Rotary type ) x 1
Compressor motor (Starting method)kW—0.90 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.30 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length)kgR32 0.78 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A4.6 / 4.4 / 4.2 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.20
Vertical height diff. between O.U. and I.U.mMax.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z274
-
-
9
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230595 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg10.036.0
Compressor type & Quantity—9RS102XDA21( Rotary type ) x 1
Compressor motor (Starting method)kW—1.50 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.32 ( FW50S )
Refrigerant (Type, amount, pre-charge length)kgR32 1.05 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA20
L.R.A. (Locked rotor ampere)A7.2 / 6.9 / 6.6 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2" )
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.25
Vertical height diff. between O.U. and I.U.mMax.15 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
-
10
RWA000Z274
-
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230540 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg9.531.0
Compressor type & Quantity—9RS102XDA21( Rotary type ) x 1
Compressor motor (Starting method)kW—1.50 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.32 ( FW50S )
Refrigerant (Type, amount, pre-charge length)kgR32 0.62 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchanger0M fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A3.2 / 3.0 / 2.9 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.20
Vertical height diff. between O.U. and I.U.mMax.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
-
11
RWA000Z274
-
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230540 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg9.531.0
Compressor type & Quantity—RM-C5077SBE71( Rotary type )
Compressor motor (Starting method)kW—0.75 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.30 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length)kgR32 0.62 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A3.2 / 3.0 / 2.9 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.20
Vertical height diff. between O.U. and I.U.mMax.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
-
12
RWA000Z274
-
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230540 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg9.534.5
Compressor type & Quantity—RM-B5077SBE2( Rotary type ) x 1
Compressor motor (Starting method)kW—0.90 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.30 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length)kgR32 0.78 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A4.6 / 4.4 / 4.2 (220/ 230/ 240 V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8")
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.20
Vertical height diff. between O.U. and I.U.mMax.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
-
13
RWA000Z274
-
'18 • SRK-T-250
Item
Power source1 Phase, 220 - 240V, 50Hz / 220V, 60Hz
Operation
data
Exterior dimensions (Height x Width x Depth)mm290 x 870 x 230595 x 780(+62) x 290
Exterior appearance
(Equivalent color : Munsell, RAL)
Net weightkg10.036.0
Compressor type & Quantity—9RS102XDA21( Rotary type ) x 1
Compressor motor (Starting method)kW—1.50 ( Inverter driven )
Refrigerant oil (Amount, type)ℓ—0.32 ( FW50S )
Refrigerant (Type, amount, pre-charge length)kgR32 1.05 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchangerLouver fins & inner grooved tubingM fins & inner grooved tubing
Refrigerant controlCapillary tubes + Electronic expansion valve
Fan type & QuantityTangential fan x 1Propeller fan x 1
Fan motor (Starting method)W42 x1 (Direct drive)24 x1 (Direct drive)
Air flow
Available external static pressurePa00
Outside air intakeNot possible—
Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —
Shock & vibration absorberRubber sleeve (for fan motor)
Electric heater——
Operation
control
Safety equipments
Installation
data
Drain pump, max lift heightmm——
Recommended breaker sizeA16
L.R.A. (Locked rotor ampere)A7.2 / 6.9 / 6.6 (220/ 230/ 240V)
Interconnecting wiresSize x Core number1.5mm
IP numberIPX0IPX4
Standard accessories
Option partsInterface kit ( SC-BIKN2-E )
Remote controlWireless-remote control
Room temperature controlMicrocomputer thermostat
Operation displayRUN: Green , TIMER: Yellow
Refrigerant piping size (O.D)mmLiquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2" )
Connecting methodFlare connectionFlare connection
Attached length of pipingmLiquid line : 0.54 / Gas line : 0.47—
Insulation for pipingNecessary ( Both sides ), independent
Refrigerant line (one way) lengthmMax.25
Vertical height diff. between O.U. and I.U.mMax.15 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower )
Drain hoseHose connectable ( VP 16 )Hole φ20 x 2 pcs
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
-
14
RWA000Z274
-
'18 • SRK-T-250
Packing material weight list
Material
Model
SRK20ZS-W11.51.210.000.330.880.000.000.000.00
SRK25ZS-W11.51.210.000.330.880.000.000.000.00
SRK35ZS-W11.51.210.000.330.880.000.000.000.00
SRK50ZS-W12.01.210.000.330.880.000.000.000.00
SRK20ZS-WB11.51.210.000.330.880.000.000.000.00
Indoor
Outdoor
SRK25ZS-WB11.51.210.000.330.880.000.000.000.00
SRK35ZS-WB11.51.210.000.330.880.000.000.000.00
SRK50ZS-WB12.01.210.000.330.880.000.000.000.00
SRK20ZS-WT11.51.210.000.330.880.000.000.000.00
SRK25ZS-WT11.51.210.000.330.880.000.000.000.00
SRK35ZS-WT11.51.210.000.330.880.000.000.000.00
SRK50ZS-WT12.01.210.000.330.880.000.000.000.00
SRC20ZS-W32.52.040.000.351.690.000.000.000.00
SRC25ZS-W32.52.040.000.351.690.000.000.000.00
SRC35ZS-W36.02.040.000.351.690.000.000.000.00
SRC50ZS-W38.02.130.000.351.780.000.000.000.00
Gross
Weight
Packing
Parts
weight
(Total)
GlassPlastic
Paper
and
board
Metal
Aluminium
Steel
Unit: kg
WoodOther
-
15
-
Space for installation and service when viewing from the front
strong winds, place the unit such that the direction of air from the
(2) The unit must be fixed with anchor bolts. An anchor bolt must not
(1) The unit must not be surrounded by walls on the four sides.
Notes
(Flare)
φ9.52(3/8")
outlet gets perpendicular to the wind direction.
(3) If the unit is installed in the location where there is a possibility of
(Flare)
φ6.35(1/4")
(4) Leave 200mm or more space above the unit.
(5) The wall height on the outlet side should be 1200mm or less.
(6) The model name label is attached on the right side of the unit.
φ20×2 places
M10-12×4 places
260
50.6
12
L1
Outlet
Inlet
351.6
E
100 or more
280 or more
Installation space
L2L3L4
L1
16.4
14.8312.524.3
130
80 or more
250 or more
17.9
Terminal block
C
40°
B
40°
A
138.433.5
270
97.742.5
Center of gravity
Content
AService valve connection(gas side)
Symbol
Service valve connection(liquid side)
Drain discharge hole
B
EAnchor bolt hole
D
CPipe/cable draw-out hole
D
Center of gravity
390.6
E
14.6
2-R
63.4
29054020
-
-
17
2-12×16
Slot hole
390.6
69.4
78061.9
111.6510158.4
15.8
RCV000Z036
Model SRC50ZS-W
'18 • SRK-T-250
L4
Service
space
( )
L3
Inlet
L2
(1) The unit must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
(3) If the unit is installed in the location where there is a possibility of
strong winds, place the unit such that the direction of air from the
outlet gets perpendicular to the wind direction.
(4) Leave 200mm or more space above the unit.
(5) The wall height on the outlet side should be 1200mm or less.
Notes
(6) The model name label is attached on the right side of the unit.
L1
Outlet
Inlet
351.6
145
80 or more
100 or more
280 or more
Installation space
L2L3L4
L1
16.4
14.8312.524.3
17.9
250 or more
Terminal block
C
40°
Unit:mm
40°
A
138.433.5
B
275
97.742.5
φ12.7(1/2")(Flare)
Content
AService valve connection(gas side)
Symbol
φ20×2 places
M10-12×4 places
φ6.35(1/4")(Flare)
Drain discharge hole
Service valve connection(liquid side)
EAnchor bolt hole
D
B
CPipe/cable draw-out hole
50.6
12
270
EDE
Center of gravity
390.6
14.6
2-R
63.4
29020
-
18
2-12×16
Slot hole
390.6
69.4
-
Center of gravity
78061.9
111.6510158.4
15.8
595
RCV000Z037
(3) Remote control
(a) Wireless remote control
'18 • SRK-T-250
Unit : mm
167
60
24
-
19
-
(b) Wired remote control (Option parts)
Interface kit (SC-BIKN2-E) is required to use the wired remote control.
Model RC-EX3A
'18 • SRK-T-250
Fixing holes
固定穴
Dimensions (Viewed from front)
372323
372323
120
120
18.3
18.383.5
120
83.5
120
19
19
Installation space
配線
Wiring
30mm
30mm
120mm
120mm
● Do not install the remote control at following places.
(1) It could cause break-down or deformation of remote control.
・Where it is exposed to direct sunlight
・Where the ambient temperature becomes 0 °C or below, or 40 °C or above
・Where the surface is not flat
・Where the strength of installation area is insufficient
(2) Moisture may be attached to internal parts of the remote control, resulting in a display failure.
・Place with high humidity where condensation occurs on the remote control
・Where the remote control gets wet
(3) Accurate room temperature may not be detected using the temperature sensor of the remote
control.
・Where the average room temperature cannot be detected
・Place near the equipment to generate heat
・Place affected by outside air in opening/closing the door
・Place exposed to direct sunlight or wind from air-conditioner
・Where the difference between wall and room temperature is large
(4) When you are using the automatic grille up and down panel in the IU, you may not be able to
confirm the up and down motion.
・Where the IU cannot be visually confirmed
30mm
30mm
30mm
30mm
R/C temperature sensor
Secure minimum spaces for disassembling the case.
Upper left and Upper right sides
……30mm or more
Bottom side…120mm or more
If using L-shaped screwdriver, 50mm or more is
available.
2
R/C cable:0.3mm
When the cable length is longer than 100 m,
the max size for wires used in the R/C case
is 0.5 mm2 . Connect them to wires of larger
size near the outside of R/C. When wires are
connected, take measures to prevent water,
etc. from entering inside.
200 m0.5 mm
≦
300m0.75 mm
≦
400m1.25 mm
≦
600m2.0 mm
≦
x2 cores
2
x 2 cores
2
x 2 cores
2
x 2 cores
2
x 2 cores
● When installing the unit at a hospital, telecommunication facility, etc., take
measures to suppress electric noises.
It could cause malfunction or break-down due to hazardous effects on the inverter, private power
generator, high frequency medical equipment, radio communication equipment, etc.
The influences transmitted from the remote control to medical or communication equipment could
disrupt medical activities, video broadcasting or cause noise interference.
-
-
20
Adapted RoHS directive
PJZ000Z333
'18 • SRK-T-250
Wiring outlet
Model RC-E5
Exposed mounting
0.3mm2×2 cores
In case of pulling out
from upper left
L C D
48
In case of pulling out
from center
TEMP ON/OFF
ڧ120
Pearl whiteExterior appearance
(Munsell color)(N8.5) near equivalent
Embedded mounting
Cut off the upper thin part of remote control lower case with a nipper or knife,
and grind burrs with a file etc.
X, Y Terminal block
Attach M3 screw
with washer
The peeling-off length of sheath
Pulling out from upper left
Remote control installation dimensions
In case of pulling out
from upper left
Upper
Board
XY
Lower
In case of pulling out from
upper left
X wiring : 215mm
Y wiring : 195mm
In case of pulling out
from center
Upper part
Lower case
Lower part
Sheath
Upper cace
Wiring
Pulling out from center
X wiring : 170mm
Y wiring : 190mm
Upper
In case of pulling out from center
Sheath
Board
YX
Lower
Wiring
The peeling-off length
of sheath
Upper cace
Wall surface
Wiring
Electrical box
䠄Not included䠅
Remote
control
outline
83.5
Wiring oulet
12×7 Slot hole
42
120
46
23
44
11.511
9.5×5 Slot hole 䠄4 places䠅
Tighten the screws after
cutting off the thin part of
screw mounting part.
120
45
Installation hole
䠄1䠅 Installation screw for remote control
19
M4 screw (2 pieces)
Wiring specifications
(1) If the prolongation is over 100m, change to the size below.
But, wiring in the remote control case should be under 0.5mm
the case according to wire connecting. Waterproof treatment is necessary at the wire connecting
section. Be careful about contact failure.