Mitsubishi SRK10CES, SRK22ZEV-S, SRK13CES, SRK19CES, SRK25CES Technical Manual

...
2005 ROOM AIR-CONDITIONING
TECHNICAL HANDBOOK
INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)
SRK13ZEV-S SRK22ZEV-S
WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air cooled cooling only type)
SRK10CES, 13CES SRK19CES, 25CES
TECHNICAL MANUAL
-
1
-
1.1 SRK13ZEV-S ............................................................. 2
1.2 SRK22ZEV-S ........................................................... 60
1. INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER
Split system, air to air heat pump type
( )
-
2
-
CONTENTS
1.1.1 GENERAL INFORMATION ...................................................................... 3
(1) Specific features ...................................................................................................... 3
(2) How to read the model name .................................................................................. 3
1.1.2 SELECTION DATA................................................................................... 4
(1) Specifications ......................................................................................................... 4
(2) Range of usage & limitations ................................................................................ 5
(3) Exterior dimensions ............................................................................................... 5
(4) Piping system ......................................................................................................... 6
(5) Selection chart........................................................................................................ 7
1.1.3 ELECTRICAL DATA ................................................................................ 8
(1) Electrical wiring ...................................................................................................... 8
1.1.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 9
(1) Operation control function by remote control switch ......................................... 9
(2) Unit ON/OFF button ................................................................................................ 10
(3) Power blackout auto restart function ...................................................................10
(4) Custom cord switching procedure .......................................................................11
(5) Flap control ............................................................................................................. 11
(6) Comfortable timer setting ...................................................................................... 12
(7) Outline of heating operation.................................................................................. 12
(8) Outline of cooling operation.................................................................................. 15
(9) Outline of dehumidifying operation......................................................................16
(10) Outline of automatic operation ............................................................................. 19
(11) Outline of fan operation .........................................................................................19
(12) ION operation ..........................................................................................................20
(13) Protective control function ....................................................................................20
1.1.5 APPLICATION DATA ............................................................................... 25
(1) Selection of location for installation ..................................................................... 26
(2) Installation of indoor unit ......................................................................................27
(3) Installation of outdoor unit .................................................................................... 30
(4) Refrigerant piping................................................................................................... 30
(5) Test run ....................................................................................................................31
(6) Precautions for wireless remote control installation and operation ................. 32
1.1.6 MAINTENANCE DATA............................................................................. 33
(1) Troubleshooting procedures for electrical equipment ........................................ 33
(2) Servicing .................................................................................................................44
1.1.7 REFRIGERANT PIPING INSTALLATION/SERVICING MANUAL
FOR AIR CONDITIONERS USING R410A ............................................. 45
(1) Outline .....................................................................................................................45
(2) Refrigerant piping installation............................................................................... 46
(3) Installation, removal and servicing ....................................................................... 52
(4) Refrigerant recovery ..............................................................................................57
MODEL SRK13ZEV-S
-
3
-
Over heat of compressor
Error of signal transmission
Outdoor fan motor error
1.1.1 GENERAL INFORMATION
(1) Specific features
The “Mitsubishi Daiya” room air-conditioner: SRK series are of split and wall mounted type and the unit consists of indoor unit and
outdoor unit with refrigerant precharged in factory. The indoor unit is composed of room air cooling or heating equipment with opera-
tion control switch and the outdoor unit is composed of condensing unit with compressor.
(a) Inverter (Frequency converter) for multi-steps power control
¡ Heating/Cooling
The rotational speed of a compressor is changed in step in relation to varying load, interlocked with the indoor and outdoor unit
fans controlled to change frequency, thus controlling the capacity.
¡ Allowing quick heating/cooling operation during start-up period. Constant room temperature by fine-tuned control after the
unit has stabilized.
(b) Fuzzy control
¡ Fuzzy control calculates the amount of variation in the difference between the return air temperature and the setting temperature
in compliance with the fuzzy rules in order to control the air capacity and the inverter frequency.
(c) Remote control flap
The flap can be automatically controlled by operating wireless remote control.
¡ Air scroll (AUTO): Flap operation is automatically control.
¡ Swing: This will swing the flap up and down.
¡ Memory flap: Once the flap position is set, the unit memorizes the position and continues to operate at the same position from
the next time.
(d) Self diagnosis function
¡ We are constantly trying to do better service to our customers by installing such judges that show abnormality of operation as
follows.
Outdoor heat exchanger sensor error
Discharge pipe sensor error
Outdoor air temperature sensor error
2 time flash
4 time flash
RUN light keeps flashing
1 time flash
OFF
OFF
OFF
Trouble of outdoor unit
Over current
Current cut
2 time flash
3 time flash
RUN light
ON
1 time flash
2 time flash
3 time flash
1 time flash
5 time flash 5 time flash
TIMER light Outdoor (LED)
Room temperature sensor error
Indoor fan motor error
Heat exchanger sensor error
2 time flash
6 time flash
TIMER light
ON
1 time flash
RUN light
Rotor lock
6 time flash 6 time flash
7 time flash ON
2 time flash 7 time flash
RUN light
2 time flash
(2) How to read the model name
Example : SR K 13 Z EV - S
R410A models
Series No.
Inverter type
Product capacity
Wall mounted type
Split type room air-conditioner
-
4
-
Item
Model
SRK13ZEV-S SRC13ZEV-S
Cooling capacity
(1)
W 4000 (400~5000)
Heating capacity
(1)
W 6000 (400~9000)
Power source 1 Phase, 220V, 50Hz
Cooling input kW 0.93 (0.105~1.5) Running current (Cooling) A 5.5 Heating input kW 1.38 (0.095~2.490) Running current (Heating) A 6.8 Inrush current A 6.8
COP Cooling: 4.30 Heating: 4.35
Noise level
Cooling Sound level 46 47
Heating Sound level 46 47
Exterior dimensions
Height × Width × Depth
mm
298 × 840 × 259 595 × 780 × 290
Color Cool white Stucco white Net weight kg 12 39 Refrigerant equipment
Compressor type & Q’ty
5CS102XFA (Scroll type) × 1
Motor kW 1.1
Starting method Line starting Heat exchanger Louver fins & inner grooved tubing Straight fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Refrigerant
(3)
kg R410A 1.35 (Pre-Charged up to the piping length of 15m) Refrigerant oil R 0.36 (RB68A) Deice control Microcomputer control
Air handling equipment
Fan type & Q’ty
Tangential fan × 1 Propeller fan × 1
Motor W 33 34
(Cooling)
Air flow (at High)
(Heating)
CMM
Air filter, Q’ty Polypropylene net (washable) × 2
Shock & vibration absorber Cushion rubber (for compressor) Electric heater –– Operation control
Operation switch
Wireless-Remote control
Room temperature control Microcomputer thermostat Pilot light RUN (Green), TIMER (Yellow), JET/HI POWER (Green), ION (Green)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4) Gas line: φ9.52 (3/8″) Connecting method Flare connecting Attached length of piping Liquid line: 0.54 m
Gas line : 0.47 m
Insulation Necessary (Both sides) Drain hose Connectable Power source cord 2 m (3 cores with Earth)
Size × Core number 1.5 mm2 × 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit, Clean filter (Allergen clear filter × 1, Natural enzyme filter × 1) Optional parts
Notes (1) The data are measured at the following conditions.
1.1.2 SELECTION DATA
(1) Specifications
Model SRK13ZEV-S (Indoor unit)
SRC13ZEV-S (Outdoor unit)
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC19ºC35ºC24ºC ISO-T1, JIS C9612
Heating 20ºC 7ºC6ºC ISO-T1, JIS C9612
(2) The operation data are applied to the 220V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even for the short piping.)
If the piping length is longer, when it is 15 to 25 m, add 20 g refrigerant per meter.
Operation data
(1)
Refrigerant
piping
Compressor overheat protection, Heating overload protection (High pressure control), Overcurrent protection, Frost protection, Serial signal error protection, Indoor fan motor error protection, Cooling overload protection
The piping length is 7.5m.
(220V)
-
5
-
(2) Range of usage & limitations
(3) Exterior dimensions
(a) Indoor unit
Model SRK13ZEV-S
Indoor return air temperature (Upper, lower limits)
Refrigerant line (one way) length Max. 25m
SRK13ZEV-S
Refer to the selection chart
Power source voltage Rating ± 10%
Voltage at starting Min. 85% of rating
Frequency of ON-OFF cycle Max. 10 times/h
ON and OFF interval Max. 3 minutes
Outdoor air temperature (Upper, lower limits)
Vertical height difference between outdoor unit and indoor unit
Max. 15m (Outdoor unit is higher) Max. 15m (Outdoor unit is lower)
Item
Model
840
298
A
Piping hole right
259
9
44
right: 67
left : 60
3
60
60
14.5
813
603
44
44
60
60
VIEW A
44.5
47.5220.5
50
207.5
73.5
53.5
Piping hole (ø65)
Piping hole (ø65)
Indoor unit
Installating board
Drain hose 515 (ø16)
Piping for gas 533.5 (ø9.52)
Piping for liquid 603.5 (ø6.35)
63.5
8.5
5.3
284.2
44.5
73.5
182.5
50
450
693
25
-
6
-
(b) Outdoor unit
Model SRC13ZEV-S
(4) Piping system
Model SRK13ZEV-S
Outdoor unitIndoor unit
Heat exchanger
Room temp. sensor
Humidity sensor
Heat exchanger
Heat exchanger
Solenoid valve
Flare connecting
Heat exchanger sensor
Piping (Liquid) ø6.35
Piping (Gas) ø9.52
Check joint
4 way valve
Service valve (Liquid)
Flare connecting
Discharge pipe temp. sensor
Cooling cycle
Heating cycle
Outdoor air temp. sensor
Heat exchanger sensor
Compressor
uffler
M
Capillary tube Capillary tube
Strainer
Service valve (Gas)
Electronic expansion valve
14.4
595
96.5
42.5
35°
35°
90.6
29.7
340
13.5
312.5
14
17.5
164
286.4
290
45.4
49.6
463
62780
106 510
12
50
Drain holes
2-16 × 12
Ground terminal
Terminal block
Service valve (Liquid)
Service valve (Gas)
Flare connection ø6.35 (1/4")
Flare connection ø9.52 (3/8")
Unit: mm
-
7
-
(5) Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be
obtained in the following way.
Net capacity = Capacity shown on specificationCorrection factors as follows.
(a) Coefficient of cooling and heating capacity in relation to temperatures
(b) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way piping length between the indoor and outdoor units.
(c) Correction relative to frosting on outdoor heat exchanger during heating
In additions to the foregoing corrections (a), (b) the heating capacity needs to be adjusted also with respect to the frosting on the outdoor heat exchanger.
How to obtain the cooling and heating capacity
Example : The net cooling capacity of the model SRK13ZEV-S with the piping length of 15m, indoor wet-bulb temperature at 19.0˚C
and outdoor dry-bulb temperature 35˚C is Net cooling capacity = 4000 0.975 1.0 = 3900 W
SRK13ZEV-S Length 15m
Factor by air temperatures
15
ISO-T1 Standard ConditionOutdoor air W.B. temperature °C W.B.
010-10 -5 5
14 16 18 20 22
15
10
27 25
20
15
20
25
30
35
40
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
43
24
20
ISO-T1 Standard ConditionIndoor air W.B. temperature °C W.B.
Heating
Cooling
Applicable range
Coefficient of cooling &
Heating capacity in
relation to temperature
Cooling operation
Outdoor air D.B.
temperature
°C D.B.
Heating operation
Indoor air D.B.
temperature
°C D.B.
Piping length [m]
Cooling
Heating
7
1.0
1.0
10
0.99
1.0
15
0.975
1.0
20
0.965
1.0
25
0.95
1.0
Air inlet temperature of
outdoor unit in ˚C WB
Adjustment coefficient
-10
0.95-90.94-70.93-50.91-30.88-10.8610.8730.9251.00
-
8
-
1.1.3 ELECTRICAL DATA
(1) Electrical wiring
Model SRK13ZEV-S
Outdoor unit
Indoor unit
Printed circuit
board
TB TB
F (250V 20A)
BK
WH
RD
U V
W
BK
C2 S.IN R.IN
Re
G
WH
RD
Th4
Th5
Th6
CNB
CNE
CNA
CND
1
2
3
NP
Power
transistor
20S
EEV
FMo
DS
CM
Black Brown Red Blue White
Yellow/Green
BK BR RD BL WH
Y/GN
Yellow
Y
Color symbol
Meaning of marks
Symbol
Parts name
CM
Compressor motor
F
Fuse
FM
I
F
Fan motor (Indoor)
FMo
F
an motor (Outdoor)
SM RE
Flap motor Reactor
Symbol
Parts name
Th
1
Room temp. sensor
Th
2
Heat exchanger sensor (Indoor unit)
Th
3
Humidity sensor
Th
4
Heat exchanger sensor (Outdoor unit)
Th
5
Outdoor air temp. sensor
Th
6
Discharge temp. sensor
Symbol
Parts name
20S
4 way valve (coil)
ZNR
Varistor
52C
Magnetic contactor
DS
Diode stack
EEV
Electronic expansion valve
SV
Solenoid valve
ZNR
250V 3A
F
CNM
Printed circuit board
JEM-ACNFCNE
1
2
3
52C3
CNG
SJ
52C
52C4
4
CNU
1
RD
RD
3
WH
WH
BK
BK
BK
6 5
BL
BL
BR
BL
Y
CNL
CNV
CNN
T4 ION generator
Safety switch
Display
Wireless R-Amp
Back-up switch
Y/G
G
SV
SM
Th1 Th2 Th3
HA
FM
I
Heat exchanger
Power source 1 Phase
220V 50Hz
( )
-
9
-
1.1.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
(1) Operation control function by remote control switch
TEMP
SLEEP
ECONO
ACL
ON
OFF
DRY MODE
AIR FLOW
CANCEL
ion
START
JET/
JET
ECONO
H
AM PM
ON
SLEEP
LO
MED
HI
AUTO
FAN SPEED
MODE
TIME
SET UP
TIMER
FAN SPEED button
Each time the button is pushed, the indi­cator is switched over in turn.
The above illustration shows all controls, but in practice only the relevant parts are shown.
OPERATION MODE select button
Each time the button is pushed, the indi­cator is switched over in turn.
ION button
This button selects ION operation.
ON/OFF button
Press for starting operation, press again for stopping.
JET/HI POWER button
This button changes the JET/HI POWER mode
.
DRY MODE button
This button changes the DRY mode.
RESET switch
Switch for resetting microcomputer.
SLEEP button
This button selects SLEEP operation.
ECONO switch
This switch changes the ECONOMY mode.
TIME SET UP switch
This switch for setting the TIME.
TEMPERATURE button
This button sets the room temperature. (This button changes the present time and
TIMER time.)
CANCEL button
This button cancels the ON timer and SLEEP timer.
JET
ECONO
H
AM PM
ON
SLEEP
LO
MED
HI
AUTO
OPERATION MODE indicator
Indicates selected operation with lamp.
[ (Auto) (Cool) (Heat) • (Dry) • (Fan)]
TEMPERATURE indicator
Indicates set temperature. (Does not indicate temperature when operation
mode is on AUTO)
FAN SPEED indicator
Indicates set air flow rate with lamp.
ECONOMY MODE indicator
Indicates during economy mode operation.
SLEEP indicator
Indicates during SLEEP operation.
ON TIMER indicator
Indicates during ON TIMER operation.
HI POWER MODE indicator
Indicates during Hi power mode operation.
Time indicator
Indicates present time or timer setting time.
DRY MODE indicator
Shows the various DRY modes.
START button
This button selects ON TIMER operation.
(Air scroll) (Flap stopped)
AIR FLOW button
This button changes the flap mode. When pressed, this button changes the mode in the following order:
AIR FLOW indicator
Shows selected flap mode.
S Indication section
Model SRK13ZEV-S
Remote control
S Operation section
-
10
-
(2) Unit ON/OFF button
When the remote control batteries become weak, or if the remote control is lost or malfunctioning, this button may be used to turn the
unit on and off.
(a) Operation
Push the button once to place the unit in the automatic mode. Push it once more to turn the unit off.
(b) Details of operation
The unit will go into the automatic mode in which it automatically determines, from room temperature (as detected by sensor),
whether to go into the cooling, thermal dry or heating modes.
Function
Room temperature
Operation mode
setting
Fan speed Flap Timer switch
Cooling About 24ºC
Thermal dry About 25ºC Auto Auto Continuous
Heating About 26ºC
(3) Power blackout auto restart function
(a) Power blackout auto restart function is a function that records the operational status of the air-conditioner immediately prior to it
being switched off by a power cut, and then automatically resumes operations at that point after the power has been restored.
(b) The following settings will be cancelled:
(i) Timer settings
(ii) High-power operations
Notes (1) The power blackout auto restart function is set at on when the air-conditioner is shipped from the
factory. Consult with your dealer if this function needs to be switched off.
(2) When power failure ocurrs, the timer setting is cancelled. Once power is resumed, reset the timer.
(3)
If the jumper wire (J1) is cut, auto restart is disabled. (See the diagram at right)
Unit ON/OFF button
ION light (green)
Illuminates during ION operation.
JET/HI POWER light (green)
Illuminates during JET/HIGH POWER operation.
RUN (HOT KEEP) light (green)
Illuminates during operation.
Blinks at air flow stop due to the ‘HOT KEEP’.
TIMER light (yellow)
Illuminates during TIMER operation.
Unit indication section
Model SRK13ZEV-S
Jumper wire (J1)
-
11
-
(5) Flap control
Control the flap by AIRFLOW button on the wireless remote control.
(a) Air scroll
The flap will be automatically set to the angle of air flow best to operation.
(i) Starting time of operation
(ii) When not operating
The flap returns to the position of air flow directly below, when operation has stopped.
(b) Memory flap
While the flap is operating if the AIRFLOW button is pushed once, it stops swinging at an angle.
As this angle is memorized in the microcomputer, the flap will be automatically set to the angle when next operation is started.
¡ Recommendable stopping angle of the flap
(c) Swing flap
Flap moves in upward and downward directions continuously.
s
During cooling and
t
dry operation
Thick line : Rapid movement
Thin line : Slow movement
Stops for approximately 5 seconds in the horizontal position.
s
During heating
t
operation
Stops for approximately 5 seconds in this position.
Thick line : Rapid movement
Thin line : Slow movement
Horizontal blowing
COOLDRY
Slant forward blowing
HEAT
(4) Custom cord switching procedure
If two wireless remote controls are installed in one room, in order to prevent wrong
operation due to mixed signals, please modify the printed circuit board in the indoor
units control box and the remote control using the following procedure. Be sure to modify
both boards. If only one board is modified, receiving (and operation) cannot be done.
(a) Modifying the indoor unit’s printed circuit board
Take out the printed circuit board from the control box and cut off jumper wire
(J2) using wire cutters.
After cutting of the jumper wire, take measures to prevent contact with the other
the lead wires, etc.
(b) Modifying the wireless remote control
i) Remove the battery.
ii) Cut the jumper wire shown in the figure at right.
Cut
Jumper wire (J2)
-
12
-
Corrects the starting time of next operation by calculating the temperature difference.
(Example) Heating
Setting temperature
Room temperature
Operation starting time
Time
Setting time
15 min. 10 min. 5 min. earlier earlier earlier
¡ If the difference (= Setting temperature – Room tempera-
ture) is 4ºC, the correction value is found to be +5 min­utes from the table shown above so that the starting time of next operation is determined as follows:
15 min. earlier + 5 min. = 20 min. earlier
↑↑
Current operation Correction value start time
(6) Comfortable timer setting
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation
is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the
relationship between the room temperature at the setting time (temperature of room temperature sensor) and the setting temperature.
(Max. 60 minutes)
Operation mode Operation start time correction value (Min.)
3 < Room temp. – Setting temp. 1 < Room temp. – Setting temp. 3 Room temp. – Setting temp. 1
At cooling
+5 No change –5
3 < Setting temp. – Room temp. 2 < Setting temp. – Room temp. 3 Setting temp. – Room temp. 2
At heating
+5 No change –5
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature sensor (Th1).
(2) This function does not operate when in the Dry or Auto Dry mode.
However, the operation in item (1) does operate in the Auto Dry mode.
(3) During the comfortable timer operation, both the RUN light and TIMER light illuminate and the TIMER light goes off after expiration of the timer, ON setting
time.
=
=
=
=
(7) Outline of heating operation
(a) Operation of major functional components in heating mode
(b) Air flow selection
(i) Speed of inverter changes within the range of selected air flow.
(ii) When the defrosting, protection device, etc. is actuated, operation is performed in the corresponding mode. (iii) Outdoor unit blower operates in accordance with the inverter command speed.
Item
Indoor fan motor ON ON OFF
Flaps ON or OFF ON or OFF Stop position control
Display Lights up Lights up Lights up or flashes
52C ON ON OFF after stop mode
Outdoor fan motor OFF ON OFF
4-way valve
Depending on the stop mode
ON
Depending on the stop mode
Electronic expansion valve Depending on the EEV control
Solenoid valve OFF OFF OFF
When the inverter
speed is 0rps
When the inverter speed
is other than 0rps
When the inverter speed is 0rps
due to an anomalous stop
Functional components
Model
SRK13ZEV-S
Air flow selection
Inverter command speed 12~118rps
Air flow Depends on inverter command speed.
Inverter command speed 12~118rps
Air flow Depends on inverter command speed.
Inverter command speed 12~78rps
Air flow Depends on inverter command speed.
Inverter command speed 12~38rps
Air flow 4th speed fixed
Auto
HI
MED
LO
-
13
-
Note (1) Refer to the table shown above right for the values A and B.
¡ Normal mode (Normal heating operation, operation after HI POWER completion)
Indoor heat exchanger temp. (˚C)
¡ Values of A, B
AB
At 0 rps command 22 25
Other than 0 rps
17 19
command
AB 2823 29.5 31.5 34 36 37.5 39 40
1st speed
2nd speed
3rd speed
4th speed
5th speed
6th speed
OFF
Indoor fan
(c) Details of control at each operation mode (pattern)
(i) Fuzzy operation
Deviation between the room temperature setting correction temperature and the suction air temperature is calculated in accordance with the fuzzy rule, and used for control of the air capacity and the inverter speed.
(ii) Heating thermostat operation
¡ Operating conditions
If the speed obtained with the fuzzy calculation drops below -24 rps during the heating fuzzy operation, the operation changes to the heating thermostat operation.
¡ Detail of operation
Model
SRK13ZEV-S
Item
Inverter speed 0rps [Comp. stopped] Indoor fan Hot keep normal mode 1st speed
Outdoor fan Stop
Flap Horizontal
7th speed
8th speed
Note (1) Refer to the table shown above right for the values A and B.
¡ Hot keep M mode [During HI POWER operation (for 15 min.)]
Indoor heat exchanger temp. (˚C)
A B 29 31 32 34 40 47
55
1st speed
2nd speed
3rd speed
4th speed
5th speed
6th speed
OFF
Indoor fan
(iv) Defrosting operation
1) Starting conditions (Defrosting operation can be started only when all of the following conditions are met.)
1 After start of heating operation When it elapsed 35 minutes. (Accumulated operation time) 2 After end of defrosting operation When it elapsed 35 minutes. (Accumulated compressor operation time) 3 Outdoor unit heat exchanger sensor (Th4) temperature When the temperature has been below –2ºC for 3 minutes
continuously.
4 When the temperature difference between the outdoor air temperature sensor and the outdoor unit heat exchanger
sensor temperature exceeded 4.5°C
5 During continuous compressor operation
In addition, when the speed command from the indoor controller of the indoor unit during heating operation has counted 0 rps 10 times or more and all conditions of 1, 2 and 3 above are satisfied (note that when the temperature for Th4 is -2°C or less: 62 rps or more, -1°C or less: less than 62 rps), defrost operation is started.
¡ Values of A, B
AB
At 0 rps command 22 25
Other than 0 rps
17 19
command
7th speed
(iii) Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor blower is controlled based on the temperature of the indoor unit heat exchanger (detected with Th2, indoor unit heat exchanger sensor) to prevent blowing of cool wind.
-
14
-
Indoor fan
RUN light
Corresponding to speed
OFF
ON
Flashing
(Hot keep)
Outdoor fan
Inverter command
Fuzzy calculated
value
70 rps
0
Corresponding
to speed
OFF
OFF
ON
(1)
4-way valve
OFF
ON
Solenoid valve
Final defrost operation
Defrost control
Hot keep
Indoor unit
Outdoor unit
120 sec.
Hot keep
100 sec.
Normal heating operation restored
Defrost end
(Th4 5˚C, 10 minutes)
Defrost operation
Defrost operation preparation
6th speed 6th speed
> =
Note (1) When outdoor unit heat exchanger sensor (Th4) temperature becomes 2°C or higher, inverter command changes 70 rps to 50
rps.
2) Operation of functional components during defrosting operation
3) Ending conditions (Operation returns to the heating cycle when either one of the following is met.)
1 Outdoor heat exchanger sensor (Th4) temperature: 5ºC or higher 2 Continued operation time of defrosting For more than 10 min.
(v) Heating HI POWER operation (HI POWER button on remote control: ON)
Operation is maintained for 15 minutes with a higher blow out air temperature.
¡ Detail of operation
Model
SRK13ZEV-S
Item
Inverter speed 118 rps
Indoor fan Hot keep M mode (max 7th speed)
Outdoor fan 6th speed
Notes (1) Room temperature is not adjusted during the HI POWER operation.
(2) Protective functions will actuate with priority even during the HI POWER operation.
(vi) Heating JET operation (JET button on remote control: ON)
1) Detail of operation
2) Indoor fan control
The indoor fan is controlled as shown at right in accordance with
the difference between the room temperature and setting
temperature. However, the limit after increasing the speed by 1
speed is 8 speeds.
Model
SRK13ZEV-S
Item
Inverter speed 12~122 rps
Air flow Depends on inverter command speed
Depends on inverter command speed
1 speed up
-3
-2
Room temp. - Setting temp. (deg)
-
15
-
(8) Outline of cooling operation
(a) Operation of major functional components in cooling mode
Item
Indoor fan motor ON ON OFF
Flaps ON or OFF ON or OFF Stop position control
Display Lights up Lights up Lights up or flashes
52C ON ON OFF after stop mode
Outdoor fan motor OFF ON OFF
4-way valve
Depending on the stop mode
OFF
Depending on the stop mode
Electronic expansion valve Depending on the EEV control
Solenoid valve OFF OFF OFF
When the inverter
speed is 0rps
When the inverter speed
is other than 0rps
When the inverter speed is 0rps
due to an anomalous stop
Functional components
(c) Detail of control in each mode (Pattern)
(i) Fuzzy operation
During the fuzzy operation, the air flow and the inverter speed are controlled by calculating the difference between the room
temperature setting correction temperature and the suction air temperature.
(ii) Cooling thermostat operation
1) Operating conditions
During the cooling fuzzy operation or when the speed obtained by the fuzzy calculation is less than -24 rps.
2) Detail of operation
(b) Air flow selection
(i) Speed of inverter changes within the range of selected air flow.
(ii) When any protective function actuates, the operation is performed in the mode corresponding to the function. (iii) Outdoor blower is operated in accordance with the inverter command speed.
(iii) Cooling “HI POWER operation (HI POWER button on remote control: ON)
The unit is operated continuously for 15 minutes regardless of the setting temperature.
1) Detail of operation
Model
SRK13ZEV-S
Item
Inverter speed 0 rps [Comp. stopped]
Indoor fan Corresponds to fan speed switch.
Outdoor fan Stop
Notes (1) Protective functions will actuate with priority even during the HI POWER operation.
(2) Room temperature is not adjusted during the “HI POWER” operation
Model
SRK13ZEV-S
Item
Inverter speed 94rps
Indoor fan 7th speed
Outdoor fan 6th speed
Model
SRK13ZEVS
Air flow selection
Inverter command speed 12~94rps
Air flow Depends on inverter command speed.
Inverter command speed 12~94rps
Air flow Depends on inverter command speed.
Inverter command speed 12~50rps
Air flow Depends on inverter command speed.
Inverter command speed 12~30rps
Air flow 2nd speed fixed.
Auto
HI
MED
LO
-
16
-
(iv) Cooling JET operation (JET button on remote control: ON)
1) Detail of operation
2) Indoor fan control
The indoor fan is controlled as shown at right in accordance with the
difference between the room temperature and setting temperature.
However, the limit after increasing the speed by 1 speed is 8 speeds.
Model
SRK13ZEV-S
Item
Inverter speed 12~96 rps
Air flow Depends on inverter command speed
(9) Outline of dehumidifying operation
(a) Operation start control
For 20 seconds when each type of dehumidifying starts, during judgment each hour, for 3 minutes when switching operations,
when the indoor fan is at 4th speed, the outdoor fan is at 3rd speed dehumidifying operates and the indoor and outdoor temperatures
are detected. However, during operation, (except when the On timer is in the wait state) each type of dehumidifying operation
starts immediately.
(b) Dehumidifying operation
After implementing operation start control, the operation content is determined in accordance with room temperature and the set
temperature.
If one hour passes following the decision on the dehumidifying operation mode, and after operation start control, the decision is
made for another dehumidification cooling operation, a heating oriented dehumidifying operation or a reheat dehumidifying.
(i) Cooling oriented dehumidifying operation
1) Detail of operation
Note (1) When a JET operation signal is received from the remote control, the indoor units fan speed is increased by 1 speed.
Model
SRK13ZEV-S
Item
Inverter speed 60 rps
Indoor fan motor 4th speed
Outdoor fan motor 5th speed
4-way valve OFF
Solenoid valve OFF
2) Operation change conditions
After 3 minutes have passed since the start of a cooling oriented dehumidifying operation, when the room setting
temperature becomes less than 0 degree, the dehumidifying operation changes to reheat dehumidifying.
(ii) Reheat dehumidifying
1) Operation range
The operation range is determined in accordance with the room temperature, setting temperature and humidity.
Temperature range
Humidity range
I range II range III range
a range A range A range B range b range A range B range C range c range B range B range C range
Depends on inverter command speed
1 speed up
2
3
Room temp. - Setting temp. (deg)
Low -3 +3 High
Cooling oriented
dehumidifying
Heating oriented
dehumidifying
Reheat dehumidifying
Room temp. _ Setting temp. (deg)
c Range
b Range
a Range
45
50 55
Humidity (%)
III Range
II Range
I Range
-2
+10-1
Room Temp. – Setting Temp. (deg)
-
17
-
2) Detail of operation
Notes (1) If the operation range switches from a range other than the A range to the A range, the command speed is set at 10 rps for 10 seconds.
Notes (2) The indoor units fan speed does not change even if JET operation signals are received from the remote control.
3) Operation change conditions
a) After 12 minutes of a reheat dehumidifying operation have passed, if the room temperature < setting temperature -5
(during gentle dry is -10), after the stop mode is implemented, the operation change to a heating oriented
dehumidifying operation.
b) After 12 minutes of a reheat dehumidifying operation have passed, if the room temperature > setting temperature +5,
after the stop mode is implemented, the operation changes to a cooling oriented dehumidifying operation.
4) Reheat dehumidifying outdoor unit fan control
The outdoor units fan speed is controlled as shown below in accordance with the outdoor temperature.
5) Reheat dehumidifying frost prevention control
a) Operating conditions
After 10 minutes have passed since a speed command other than 0 rps has been output, when either of the following
conditions is satisfied.
1 Indoor unit heat exchanger temperature
< =
2ºC or lower continuously for 30 minutes
2 Indoor unit heat exchanger temperature
< =
-1ºC
b) Detail of operation
1 Command speed: 0 rps
2 Indoor unit fan: 3rd speed
3 Outdoor unit fan: Stopped
c) Reset conditions
Indoor unit heat exchanger temperature: 4ºC or higher.
30 30
A
Range
3rd speed
1st speed
ON OFF
Outdoor fan motor
Solenoid valve
Indoor fan motor
Inverter speed
12 minutes 12 minutes
Reheat
dehumidifying
control
Reheat
dehumidifying
control
+ 1 speed up
12 minutes
Temperature and humidity check
Reheat dehumidifying
operation range decision
0
OFF
B
Range
C
Range
2nd speed
1st speed
Stop
10 22 248
Outdoor temperature (°C)
-
18
-
(iii) Heating oriented dehumidifying
1) Detail of operation
2) Operation change conditions
After 3 minutes have passed since the start of heating oriented dehumidifying, if the room temperature > setting
temperature -1 and the discharge pipe temperature is 50ºC or higher, the stop mode is implemented, then cooling cycle
operation begins and changes to the reheat dehumidifying operation.
3) Cooling cycle operation control
a) Detail of operation
Notes (1) When a JET operation signal is received from the remote control, the indoor unit fan’s speed is raised 1 speed.
b) Reset conditions
When 6 minutes have passed and the outdoor heat exchanger temperature is
> =
9ºC. However, the maximum
operating time is 9 minutes regardless of the outdoor heat exchanger temperature.
(c) Gentle dry operation control
(i) After the operation start control in item (a) is performed, the setting temperature is determined in accordance with the room
temperature.
Setting temperature = Room temperature
However, if the setting temperature becomes
> =
28ºC, the setting temperature upper limit is set at 28ºC. The setting humidity is 55%.
(ii) Determining the operation content
1 Outdoor temperature < 20ºC: Heating oriented dehumidifying regardless of the setting temperature. 2 Outdoor temperature
>
=
20ºC:
If the room temperature < setting temperature + 3ºC, operation is in the reheat dehumidifying mode.
If the room temperature
> =
setting temperature + 3ºC, operation is in the cooling oriented dehumidifying mode.
For the dehumidifying operation, see the dehumidifying operation for item (b).
(d) Laundry dry operation control
(i) After the operation start control in item (a) is performed, the setting temperature is determined in accordance with the room
temperature and outdoor temperature.
Setting temperature = Room temperature + 6ºC or the room temperature, whichever is lower.
However, if the setting temperature is
< =
20ºC the bottom limit of the setting temperature is 20ºC.
If the setting temperature becomes
> =
25ºC, the setting temperature upper limit is set at 25ºC. The setting humidity is 40%.
(ii) Determining the operation content
1 Outdoor temperature < 20ºC: Heating oriented dehumidifying regardless of the setting temperature. 2 Outdoor temperature
> =
20ºC: If the room temperature < setting temperature - 3ºC, operation is in the heating oriented
dehumidifying mode.
If the setting temperature – 3ºC
< =
room temperature < setting temperature + 3ºC, operation
is in the reheat dehumidifying mode.
If the room temperature
> =
setting temperature +3°C, operation is in the cooling oriented
dehumidifying mode.
For the dehumidifying operation, see the dehumidifying operation for item (b).
(iii) Stop conditions
1 After 3 hours pass. 2 After 1 hour has passed, when it is judged 4 times to continue reheat dehumidifying in the A range, and it doesnt occur
the 4th time.
Model
SRK13ZEV-S
Item
Inverter command speed 80 rps
Indoor unit fan 4th speed
Outdoor unit fan 5th speed
4-way valve ON
Solenoid valve OFF
Model
SRK13ZEV-S
Item
Inverter speed 30 rps
Indoor fan motor OFF
Outdoor fan motor OFF
4-way valve OFF
Solenoid valve OFF
-
19
-
(e) Low temperature dehumidifying protective control (Cooling oriented dehumidifying or reheat dehumidifying)
(i) Operating condition: When the room temperature or outdoor temperature becomes lower than 4ºC.
(ii) Detail of operation
(iii) Reset condition: After 7 minutes have passed.
Model
SRK13ZEV-S
Item
Inverter speed 0 rps
Indoor fan motor 2nd speed
Outdoor fan motor Stop mode
4-way valve Stop mode
Solenoid valve Stop mode
(10) Outline of automatic operation
(a) Determination of operation mode
The unit checks the room temperature and the outdoor air temperature after operating the indoor and outdoor blowers for 20
seconds, determines the operation mode and the room temperature setting correction value, and then begins in the automatic
operation.
Heating
Dehumidifying
Cooling
Room temperature (˚C)
Outdoor temperature (˚C)
27.5
25.5
19.5
18
30
(b) The unit checks the temperature every hour after the start of operation and, if the result of check is not same as the previous
operation mode, changes the operation mode.
(c) When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is selected
during heating, cooling or dehumidifying operation, the unit is operated in the previous operation mode.
(d) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the signals of the
wireless remote control and the setting temperature.
Signals of wireless remote control (Display)
–6 –5 –4 –3 –2 –1 ±0+1+2+3+4+5+6
Setting
Cooling 18 19 20 21 22 23 24 25 26 27 28 29 30
temperature
Dehumidifying 19 20 21 22 23 24 25 26 27 28 29 30 31
Heating 20 21 22 23 24 25 26 27 28 29 30 31 32
(11) Outline of fan operation
(a) Operation of major functional components
Inverter command speed
Indoor fan motor
Outdoor fan motor
Flap
Speed 6 Speed 5
0rps
OFF
Depend on the flap control
Speed 3 Speed 2
AUTO HI MED LO
Functional components
Fan speed switching
-
20
-
(12) ION operation (Ion button on the remote control is ON)
The negative ion generator operates, generating negative ions.
Operation content
(13) Protective control function
(a) Dew condensation prevention control [Cooling (including automatic), cooling oriented dehumidifying operation]
(i) Operation conditions: When the following conditions are met after 20 minutes or more of continuous operation after
operation starts.
1) When the inverter command speed is higher than 28 rps.
2) When the humidity sensor value is higher than 68%.
(ii) Detail of operation:
Notes (1) The A range and B range are as shown at right.
Notes (2) There is no 1-speed rise in speed during JET operation control.
(iii) Resets conditions: When either of the following conditions satisfied.
1) The inverter speed is less than 28 rps.
2) The humidity sensor value less than 63%.
(b) Frost prevention for indoor heat exchanger (During cooling or dehumidifying)
(i) Operating conditions
1) Indoor heat exchanger temperature (detected with Th2) is lower than 5ºC.
2) 10 minutes after reaching the inverter command speed except 0 rps.
(ii) Detail of anti-frost operation
5°C or lower 2.5°C or lower
Item
Indoor command speed 12 rps 0rps
Indoor fan Depends on operation mode 2nd speed
Outdoor fan 4th speed OFF
4-way valve OFF Depends on stop mode
Solenoid valve Depends on operation mode Depends on stop mode
(iii) Reset conditions: After 5 minutes of operation,
the indoor heat exchanger temperature (Th2) is 8ºC or higher.
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature (°C)
2.5 5 8
0 rps
12 rps
Inverter
command
speed
Humidity (%)
68 73
A range
B range
Model
SRK13ZEV-S
Item
Upper limit of inverter speed A range: 50 rps, B range: 30 rps
Indoor fan motor 5th speed
Upper limit of inverter speed A range: 50 rps, B range: 30 rps
Indoor fan motor 4th speed
Upper limit of inverter speed A range: 50 rps, B range: 30 rps
Indoor fan motor Depends on inverter speed
Air flow MED
Air flow LO
Other Settings
63
Operates
Stopped
68
Humidity (%)
Note (1) The negative ion generator is run and stopped in
accordance with the humidity sensor value.
Negative ion generator ON
Air conditioner operating In accordance with the air conditioner settings
Air conditioner stopped In accordance with fan operation settings
ION light Lights up.
Indoor
unit fan
(c) Indoor fan motor protection
When the air conditioner is operating and the indoor fan motor is turned ON, if the indoor fan motor has operated at 300 rpm or
under for more than 30 seconds, the unit enters first in the stop mode and then stops the entire system.
TIMER light illuminates simultaneously and the RUN light flashing 6 times at each 8-second.
-
21
-
(d) Prevention of continuous low speed operation: For oil return to compressor
(i) Operating condition: When command speed of less than 26 rps continues for 60 minutes
(ii) Detail of operation: The unit is operated at command speed of 30 rps forcibly for 15 seconds. (The indoor and outdoor
fans are not changed.)
Note (1) When the command of exceeding 30 rps is directed during 30 rps forced operation, the unit follows it.
(e) Compressor protection start
(i) When the indoor unit calculated speed is 64 rps or over at operation start, the unit is operated with 64 rps for 1 minute and 45
seconds.
(ii) After (i) above, if the decision speed is 96 rps or higher, it runs for 5 minutes at 96 rps, then changes to the decision speed. (iii) At thermo operation (OFF ON) this control is not executed.
(iv) The indoor unit fan corresponds to the command speed of each operation mode.
Note (1) When the calculated speed is less than 64 rps, the unit is started with low load starting described in article (e).
(f) Low load starting
(i) When the unit is started with calculated speed of less than 30 rps, it is operated with 30 rps for 60 seconds, then the operation
is moved to the command speed.
(ii) The indoor fan corresponds to the operation mode.
Cooling: Speed corresponding to the command speed of air flow switching
Dehumidification: Speed decided in the operation region
Heating: The lower one between the speed corresponding to the command speed and the hot keep speed
(g) Inching prevention
When the compressor goes into the thermo operation within 3 minutes since operation start or becomes various dehumidifying
operations, the operation is continued with the command speed of 12 rps forcibly.
(h) Current safe
(i) Purpose: Current is controlled not to exceed the upper limit of the setting operation current.
(ii) Detail of operation: Input current to the converter is monitored with the current sensor fixed on the printed circuit board of
the outdoor unit and, if the operation current value reaches the limiting current value, the inverter speed is reduced.
If the mechanism is actuated when the speed of outdoor unit is less than 30 rps, the compressor is stopped immediately.
Operation starts again after a delay time of 3 minutes.
(i) Current cut
(i) Purpose: Inverter is protected from overcurrent.
(ii) Detail of operation: Output current from the converter is monitored with a shunt resistor and, if the current exceeds the
setting value, the compressor is stopped immediately. Operation starts again after a delay time of 3 minutes.
(j) Heating overload protective control
(i) Operating conditions : When the unit is operating with the outdoor unit speed other than 0 rps or when the outdoor air
temperature (detected by Th5) rose beyond 17ºC for 2 minutes continuously.
(ii) Detail of operation
1) Indoor fan speed is raised forcibly by 1 step. However, when the air flow is LO, the fan speed is not raised by 1 step.
2) Taking the upper limit of control speed range at 60 rps, if the output speed obtained with the fuzzy calculation exceeds the
upper limit, the upper limit value is maintained.
3) The outdoor fan is set on 2nd speed.
4) JET operation control does not raise the speed by 1 step
5) The lower limit of control speed is set to 35 rps and even if the calculated result becomes lower than that after fuzzy
calculation, the speed is kept to 35 rps. However, when the thermo becomes OFF, the speed is reduced to 0 prs.
(iii) Reset condition: When the outdoor air temperature drops below 16ºC.
-
22
-
(k) Cooling overload protective control
(i) Operating conditions: When the outdoor unit is operating with the speed of other than 0 rps, or when the outdoor air
temperature (detected by Th5) becomes 41ºC or over for 30 seconds continuously.
(ii) Detail of operation
1) Outdoor fan is stepped up by 3 speed step.
2) The lower limit of control speed is set to 30 rps and even if the calculated result becomes lower than that after fuzzy
calculation, the speed is kept to 30 rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
3) The upper limit of control speed is 96 rps.
(iii) Restoration condition: When the outdoor air temperature becomes 40ºC or less
(l) Freezing cycle system protective control
(i) Operating conditions: When both of following conditions have continued for more than 5 minutes later than 5 minutes
after the start of operation.
1) Command speed is higher than 60 rps
2) During cooling, dehumidifying: Indoor heat exchanger temperature - Room temperature > –4ºC
During heating: Indoor heat exchanger temperature - Room temperature < 6ºC
(ii) Detail of operation
The command speed repeats 30 minutes at 30rps 2 minutes at 62 rps.
(iii) Restoration conditions: When the condition becomes outside of either conditions 1) or 2) shown above
Note (1) This control is valid when the room air temperature is in the range of 10 to 40ºC at cooling and dehumidification operation and 0 to 40ºC at heating
operation.
(m) Compressor overheat protection
(i) Purpose: It is designed to prevent deterioration of oil, burnout of motor coil and other trouble resulting from the compressor
overheat.
(ii) Detail of operation
1) Speeds are controlled with temperature detected by the sensor mounted on the discharge pipe.
Discharge pipe temperature (˚C)
Lower limit
(4)
After lapse of 3 min. or over
(3)
After lapse of 3 min. or over
(3)
After lapse of 3 min. or over
(3)
4 rps
4 rps
(1)
0 rps
(Example) Fuzzy
80 90 110
Notes (1) When the discharge pipe temperature is in the range of 90 to 110ºC, the speed is reduced by 4 rps.
(2) When the discharge pipe temperature is raised and continues operation for 20 seconds without changing, then the speed is reduced again by 4 rps.
(3) If the discharge pipe temperature is still 80ºC or greater but less than 90ºC even when the inverter command speed is maintained for 3 minutes when
the temperature is 80ºC or greater but less than 90ºC, the speed is raised by 2 rps and kept at that speed for 3 minutes. This process is repeated until
the command speed is reached.
(4) Lower Limit Speed
Cooling Heating
SRK13ZEV-S 22 38
2) If the temperature of 110ºC is detected by the sensor on the discharge pipe, then the compressor will stop immediately.
When the discharge pipe temperature drops and the time delay of 3 minutes is over, the unit starts again within 1 hour but
there is no start at the third time.
(n) Serial signal transmission error protection
(i) Purpose: Prevents malfunction resulting from error on the indoor outdoor signals. (ii) Detail of operation: When the indoor unit controller outdoor unit controller signals cannot be received, the compressor
is stopped immediately. Once the operation stops, it does not start any more.
(TIMER light on the indoor unit flashing at the same time.)
-
23
-
(o) High pressure control
(i) Purpose: Prevents anomalous high pressure operation during heating.
(ii) Detector: Indoor unit heat exchanger sensor (Th2)
(iii) Detail of operation:
Note (1) RPSmin: The lower one between the outdoor unit speed and the command speed
¡ Temperature list
ABC
RPSmin < 88 46 53.5 58.5
88
<
=
RPSmin < 108 41 48.5 53.5
108
< =
RPSmin 36 43.5 48.5
Notes (1) When the indoor unit heat exchanger temperature is in the range of B~C ºC, the speed is reduced by 8 rps at each 20 seconds. When the temperature is C
ºC or over for 1 minute continuously, the inverter is stopped.
(2) When the indoor unit heat exchanger temperature is in the range of A~B ºC, if the inverter command speed is been maintained and the operation has
continued for more than 20 seconds at the same speed, it returns to the normal heating operation.
(3) Indoor blower retains the fan tap when it enters in the high pressure control. Outdoor blower is operated in accordance with the speed.
Unit : ºC
(Example) Fuzzy
Indoor unit heat exchanger temperature (˚C)
Lower limit speed 35 rps
After lapse of 20 Sec. or over
(2)
After lapse of 20 Sec. or over
(2)
After lapse of 20 Sec. or over
(2)
B
C
8 rps
(1)
8 rps
0 rps
A
(p) Heating low outdoor temperature protective control
< I > (i) Operating conditions: When the outdoor air temperature sensor (Th5) is 4°C or lower continues for 30 seconds while
outdoor speed is other than 0rps.
(ii) Detail of operation: When the inverter command speed is less than 22rps, the speed is forcibly set at 22rps. However,
when the thermo becomes OFF, the speed is reduced to 0rps.
(iii) Reset condition: When the outdoor air temperature sensor (Th5) becomes 6°C or higher.
< II > (i) Operating conditions: When the outdoor air temperature sensor (Th5) is 0°C or lower continues for 5 minutes while
outdoor speed is other than 0rps.
(ii) Detail of operation: Outdoor fan is stepped up by 1 speed step. (Upper limit 7th speed) (iii) Reset condition: When the outdoor air temperature sensor (Th5) becomes 2°C or higher.
< III >
(i) Operating conditions: When the outdoor unit is operating with the speed of other than 0rps, and when the outdoor heat
exchanger temperature (Th4) is less than -10°C for 1 minutes.
(ii) Detail of operation:
1 Outdoor air temperature
< =
-7°C: The upper limit of inverter command speed is 60 rps.
2 Outdoor air temperature > -7°C: The upper limit of inverter command speed is 70 rps.
(iii) Reset conditions: When the either of the following conditions is satisfied
1 When the outdoor heat exchanger temperature (Th4) becomes -7°C or higher.
2 When the inverter command speed is 0rps.
-
24
-
(q) Prevention of continuous low speed operation: For oil return to compressor
(i) Operating condition: When inverter command speed of less than 26 rps continues for 60 minutes
(ii) Detail of operation: The unit is operated at inverter command speed of 30 rps forcibly for 15 seconds. (The indoor and
outdoor fans are not changed.)
Note (1) When the inverter command of exceeding 30 rps is directed during 30 rps forced operation, the unit follows it.
(r) Outdoor fan motor protection
If the outdoor fan motor has operated at 75rpm or under for more than 30 seconds, the inverter and fan motor are stopped.
(s) Stop mode
(i) Operating conditions: When the operation mode is changed, when the dehumidifying operation is changed from the
heating oriented mode to the cooling oriented mode or vice versa, or when the dehumidifying operation is changed from
reheat dehumidifying to the heating or when the inverter speed turns to 0 rps. [When 0 rps is commanded from the indoor unit
controller, or when an outdoor protective function is actuated]
(ii) Detail of operation
Function Operation
Heating,
heating oriented dehumidifying
Heating,
heating oriented dehumidifying
Cooling,
cooling oriented dehumidifying
Cooling,
cooling oriented dehumidifying
When stopped by indoor unit controller
Reheat
dehumidifying
Reheat
dehumidifying
When stopped or reset by outdoor unit protective function
Inverter
speed
3 min.
6 th speed 6 th speed 6 th speed
6 th speed
6 th speed 6 th speed
3 min. 3 min.
2 min. 55 sec.
2 min. 45 sec.
2 min. 45 sec.
4 min. 40 sec.
2 min.
55 sec.
1 min 1 min 1 min 1 min 1 min
1st speed
1 min
2 min.
55 sec.
2 min.
55 sec.
Indoor
fan
Outdoor
fan
4-way valve
Solenoid
valve
Stop
Full stop
[0 rps command]
Stop
Full stop
[0 rps command]
Stop
Full stop
[0 rps command]
Stop
Restart
[0 rps command]
Stop
Restart
[0 rps command]
Stop
Restart
[0 rps command]
ON
OFF
ON
OFF
OFF
Command speed
0 rps
Speed dependent
OFF
ON
OFF
Speed responsive
or reheat
dehumidifying
control
Indoor
power
relay
Hot keep
-
25
-
1.1.5 APPLICATION DATA SAFETY PRECAUTIONS
¡ Please read these “Safety Precautions” first then accurately execute the installation work.
¡
Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points
which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the
WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed in the
CAUTION section as well. In either case, important safety related information is indicated, so by all means, properly observe all
that is mentioned.
¡ After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain
operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner’s manual.
Moreover, ask the customer to keep this sheet together with the owner’s manual.
WARNING
¡ To disconnect the appliance from the mains supply this appliance must be connected to the mains by means of
a circuit breaker or a switch (use a recognized 16A) with a contact separation of at least 3mm.
¡ The appliance shall be installed in accordance with national wiring regulations. ¡ This system should be applied to places as households, residences and the like. Application to inferior environ-
ment such as engineering shop could cause equipment malfunction.
¡ Please entrust installation to either the company which sold you the equipment or to a professional contractor.
Defects from improper installations can be the cause of water leakage, electric shocks and fires.
¡ Execute the installation accurately, based on following the installation manual. Again, improper installations can
result in water leakage, electric shocks and fires.
¡ For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insuffi-
cient, injury can result from a falling of the unit.
¡ For electrical work, please see that a licensed electrician executes the work while following the safety standards
related to electrical equipment, and local regulations as well as the installation instructions, and that only exclu­sive use circuits are used. Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and fires.
¡ Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted
to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.
¡ Take care that wiring does not rise upward, and accurately install the lid/service panel.It’s improper installation
can also result in heat generation or fire.
¡ When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the
designated refrigerant (R410A) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing.
¡ Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this
company can result in water leakage, electric shock, fire and refrigerant leakage.
¡ Ventilate the work area when refrigerant leaks during the operation.
Coming in contact with fire, refrigerant could generate toxic gas.
¡ Confirm after the foundation construction work that refrigerant does not leak.
If coming in contact with fire of a fan heater, a stove or movable cooking stove, etc., refrigerant leaking in the room could generate toxic gas.
¡ In joining pipes, do not use conventional (R22) pipng flare nuts, etc. The use of conventional pipng materials may
lead to the rapture of piping due to higher pressure used for the refrigerant cycle and possible personal injury. (Use only piping material designed specifically for R410A)
CAUTION
¡ Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone
ground wire. Improper placement of ground wires can result in electric shock.
¡ The installation of an earth leakage breaker is necessary depending on the established location of the unit.
Not installing an earth leakage breaker may result in electric shock.
¡ Do not install the unit where there is a concern about leakage of combustible gas.
The rare even of leaked gas collecting around the unit could result in an outbreak of fire.
¡ For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it
to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
-
26
-
(1) Selection of location for installation
(a) Indoor unit
(i) Where there is no obstructions to the air flow and where the cooled
air can be evenly distributed.
(ii) A solid place where the unit or the wall will not vibrate.
(iii) A place where there will be enough space for servicing. (Where
space mentioned below can be secured)
(iv) Where wiring and the piping work will be easy to conduct.
(v) The place where receiving part is not exposed to the direct rays of
the sun or the strong rays of the street lighting.
(b) Outdoor unit
(i) A place where good air circulation can be obtained and where rain, snow or sunshine will not directly strike the unit.
(ii) A place where discharged hot air or unit’s operating sound will not be a nuisance to the neighborhood.
(iii) A place where servicing space can be secured.
(iv) A place where vibration will not be enlarged.
Model
SRK13ZEV-S
Item One way piping length (R) 25 m
Outdoor unit is lower
15 m
Outdoor unit is higher
15 m
r
h
Left side
Right side
5 cm
10 cm
1.5 cm
6.5 cm
Air inlet
Air inlet
Air Outlet
100
100
600
No obstacles (Service space for electrical parts)
Unit : mm
Notes (1) Blowing out port and suction port on the back side of the unit can be
installed at a distance of 10cm from walls.
In case the barrier is 1.2m or above in height, or is overhead, the
sufficient space between the unit and wall shall be secured.
(2) When the unit is installed, the space of the following dimension and
above shall be secured.
(v) In heating operation, snow deposit on the heat-exchanger of outdoor unit must be
prevented for keeping the normal performance capacity.
1) Snow-hood on outdoor unit as in drawing, will reduce the frequency of
defrost operation.
When installing the snow hood, take care so that the air outlet of the snow
hood will not face directly into the most windy direction.
2) Design the base higher than possible snow deposit.
(c) Limitations for one way piping length and vertical
height difference.
()
Vertical height difference (h)
Snow hood
Height: Must be over the possible snow deposit height
-
27
-
Fixing on concrete wall
Use of nut anchor Use of bolt anchor
Bolt (M6 × 12)
Mounting board
Nut (M6)
Mounting board
Max. 10
Adjustment of the installation board in the horizontal
direction is to be conducted with four screws in a
temporary tightened state.
(2) Installation of indoor unit
(a) Installation of installation board
(i) Fixing of installation board
(b) Drilling of holes and fixture sleeve (Option parts)
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.
(i) Drill a hole with ø65
whole core drill
(ii) Adjusting sleeve length
Adjust so that board will be level by turning the board
with the standard hole as the center.
Standard hole
(iii) Install the sleeve
(Inserting sleeve) (*Sleeve + *Inclined + *Sealing plate)
Note (1) Drill a hole with incline of 5 degree from
indoor side to outdoor side.
Indoor side Outdoor side
Cut off the sleeve collar in case of drawing piping out to rear.
Cut off the sleeve collar that can be seen from beneath the unit.
Wall thickness
+ 1.5 cm
Indoor side
Outdoor side
Turn to tighten
Paste
View of sleeve when installed
Inclined flange
Sealing plate
Sleeve
Indoor side Outdoor side
Look for the inside wall structures (Intersediate support or pillar and firaly install the unit after level surface has been checked.)
Mating mark for level surface
450
450207.5
53.5
63.5
182.5
693
50
50 50
73.5 73.5
100
8.5284.25.3
44.5
44.5
47.5220.5
40 Speace
for service
15 Speace
for service
Speace for service
Speace for
service
Indoor unit
Installation board
Piping hole (ø65) Piping hole (ø65)
Drain hose 515 (ø16)
Piping for liquid 603.5
Piping for Gas 533.5
INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW)
Unit : mm
-
28
-
(c) Preparation of indoor unit
(i) Mounting of connecting wires
1) Remove the lid.
2) Remove the wiring clamp.
3) Connect the connecting wire securely to the terminal block.
1 Connect the connection wire securely to the terminal block. If the wire is not affixed completely, contact will be poor,
and it is dangerous as the terminal block may heat up and catch fire.
2 Take care not to confuse the terminal numbers for indoor and outdoor connections.
3 Affix the connection wire using the wiring clamp.
4) Fix the connecting wire by wiring clamp.
5) Attach the lid.
6) Close the air inlet grille.
(ii) Installing the support of piping
Use cables for interconnection wiring to avoid loosening of the wires. CENELEC code for cables. Required field cables. H05RNR3G1.5 (Example) or 245IEC57
H Harmonized cable type
05 300/500 volts
R Natural-and/or synth, rubber wire insulation N Polychloroprene rubber conductors insulation R Standed core
4or5 Number of conductors
G One conductor of the cable is the earth conductor (yellow/
green)
1.5 Section of copper wire (mm2)
Clamp
Lid
Terminal block
[When the hose is extended to left and taken out from the rear center]
Piping
Drain hose
¡ Tape only the portion that goes through the wall.
Always tape the crossover wiring with the piping.
¡ Hold the bottom of the piping and fix direction before
stretching it and shaping it.
[Top View]
[Shaping the piping] [Taping of the exterior]
Left-hand-sided-piping
Piping in the left rear direction
Piping in the right rear direction
Right
Rear
Downward
Left rear
Left downward
Left
Piping in the left direction
Piping in the right direction
Right-hand-sided-piping
Piping is possible in the rear, left, left rear, left downward, right or downward direction.
Loading...
+ 230 hidden pages