Manual No.'15•SRK-T-171
-
1
-
'15 • SRK-T-171
TECHNICAL MANUAL
-
2
-
'15 • SRK-T-171
'10 • SRK-T-099
CONTENTS
1. SPECIFICATIONS .................................................................................... 4
(2) Outdoor units ...................................................................................... 28
(3) Wireless remote control
...................................................................... 30
........................................................................ 26
(1) Indoor units ......................................................................................... 26
2. EXTERIOR DIMENSIONS
3. ELECTRICAL WIRING ............................................................................. 31
(1) Indoor units ......................................................................................... 31
(2) Outdoor units ...................................................................................... 32
....................................................... 41
6. RANGE OF USAGE & LIMITATIONS
5. PIPING SYSTEM ..................................................................................... 40
4. NOISE LEVEL ..................................................................................... 34
7. CAPACITY TABLES
............................................................................... 46
............................................................................... 43
8. APPLICATION DATA
9. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 56
(6) Timer operation
................................................................................. 59
(5) Flap control ....................................................................................... 59
...................................................... 58(4) Custom cord switching procedure
........................................................................ 58(3) Auto restart function
(2) Unit ON/OFF button
.......................................................................... 58
(1) Operation control function by remote control
..................................... 56
(8) Outline of automatic operation .......................................................... 60
(7) Outline of cooling operation .............................................................. 60
(9) Protective control function
.................................................................. 61
.............................................................................. 62
.................... 63
(4) Troubleshooting procedure (If the air-conditioner runs)
(3) Troubleshooting procedure
(If the air-conditioner does not run at all)
....... 62
(1) Cautions
............................................................................................ 62
(2) Items to check before troubleshooting ................................................ 62
(5) Self-diagnosis table ............................................................................ 63
(6) Inspection procedures corresponding to detail of trouble ................... 64
10. MAINTENANCE DATA
-
3
-
'15 • SRK-T-171
'10 • SRK-T-099
(7)
Phenomenon observed after shortcircuit, wire breakage on sensor
........ 65
How to read the model name
Example: SRK 05 C
Series code
Cooling only type
Product capacity
Model name SRK : Wall mounted type
SRC : Outdoor unit
R-S
(8) How to make sure of wireless remote control ..................................... 66
-
4
-
'15 • SRK-T-171
1. SPECIFICATIONS
Model
Item
SRK05CR-S
Indoor unit SRK05CR-S Outdoor unit SRC05CR-S Cooling capacity (1) W 1465 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.375
Running current
Cooling
A
1.70
Inrush current 10 COP Cooling 3.91 Noise level
Cooling
Sound level dB(A) 42 48
Power level dB 56 59 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 20
Refrigerant equipment
Compressor type & Q'ty GAB046PAA (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.23 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.46 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 8.5 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
5
-
'15 • SRK-T-171
Model
Item
SRK05CR-S3
Indoor unit SRK05CR-S3 Outdoor unit SRC05CR-S3 Cooling capacity (1) W 1465 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.375
Running current
Cooling
A
1.70
Inrush current 10 COP Cooling 3.91 Noise level
Cooling
Sound level dB(A) 42 48
Power level dB 56 59 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 20
Refrigerant equipment
Compressor type & Q'ty GAB046PAA (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.23 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.46 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 8.5 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
6
-
'15 • SRK-T-171
Model
Item
SRK05CR-S6
Indoor unit SRK05CR-S6 Outdoor unit SRC05CR-S6 Cooling capacity (1) W 1465 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.400
Running current
Cooling
A
1.80
Inrush current 10 COP Cooling 3.66 Noise level
Cooling
Sound level dB(A) 42 50
Power level dB 56 61 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 20
Refrigerant equipment
Compressor type & Q'ty GAB046PAA (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.23 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.46 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 8.5 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
7
-
'15 • SRK-T-171
Model
Item
SRK05CRP-S
Indoor unit SRK05CRP-S Outdoor unit SRC05CRP-S Cooling capacity (1) W 1465 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.490
Running current
Cooling
A
2.30
Inrush current 10 COP Cooling 2.99 Noise level
Cooling
Sound level dB(A) 42 50
Power level dB 56 61 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 19.5
Refrigerant equipment
Compressor type & Q'ty GAB046PAA (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.23 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.44 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 8.5 20 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
8
-
'15 • SRK-T-171
Model
Item
SRK05CRP-S3
Indoor unit SRK05CRP-S3 Outdoor unit SRC05CRP-S3 Cooling capacity (1) W 1465 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.490
Running current
Cooling
A
2.30
Inrush current 10 COP Cooling 2.99 Noise level
Cooling
Sound level dB(A) 42 50
Power level dB 56 61 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 19.5
Refrigerant equipment
Compressor type & Q'ty GAB046PAA (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.23 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.44 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 8.5 20 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
9
-
'15 • SRK-T-171
Model
Item
SRK09CR-S
Indoor unit SRK09CR-S Outdoor unit SRC09CR-S Cooling capacity (1) W 2500 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.893
Running current
Cooling
A
4.1 / 3.9
Inrush current 15 COP Cooling 2.80 Noise level
Cooling
Sound level dB(A) 43 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 24.5
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.52 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
10
-
'15 • SRK-T-171
Model
Item
SRK09CR-S3
Indoor unit SRK09CR-S3 Outdoor unit SRC09CR-S3 Cooling capacity (1) W 2500 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.893
Running current
Cooling
A
4.1 / 3.9
Inrush current 15 COP Cooling 2.80 Noise level
Cooling
Sound level dB(A) 43 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 24.5
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.52 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
11
-
'15 • SRK-T-171
Model
Item
SRK09CR-S4
Indoor unit SRK09CR-S4 Outdoor unit SRC09CR-S4 Cooling capacity (1) W 2500 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.893
Running current
Cooling
A
4.1 / 3.9
Inrush current 15 COP Cooling 2.80 Noise level
Cooling
Sound level dB(A) 43 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 24.5
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.52 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
12
-
'15 • SRK-T-171
Model
Item
SRK09CR-S5
Indoor unit SRK09CR-S5 Outdoor unit SRC09CR-S5 Cooling capacity (1) W 2500 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.893
Running current
Cooling
A
4.1 / 3.9
Inrush current 15 COP Cooling 2.80 Noise level
Cooling
Sound level dB(A) 43 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 24.5
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.52 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
13
-
'15 • SRK-T-171
Model
Item
SRK09CRP-S
Indoor unit SRK09CRP-S Outdoor unit SRC09CRP-S Cooling capacity (1) W 2500 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.925
Running current
Cooling
A
4.3
Inrush current 15 COP Cooling 2.70 Noise level
Cooling
Sound level dB(A) 43 51
Power level dB 57 62 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 24
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.48 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
14
-
'15 • SRK-T-171
Model
Item
SRK09CRP-S3
Indoor unit SRK09CRP-S3 Outdoor unit SRC09CRP-S3 Cooling capacity (1) W 2500 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.925
Running current
Cooling
A
4.3
Inrush current 15 COP Cooling 2.70 Noise level
Cooling
Sound level dB(A) 43 51
Power level dB 57 62 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 24
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.48 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
15
-
'15 • SRK-T-171
Model
Item
SRK09CRP-S5
Indoor unit SRK09CRP-S5 Outdoor unit SRC09CRP-S5 Cooling capacity (1) W 2500 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.925
Running current
Cooling
A
4.3
Inrush current 15 COP Cooling 2.70 Noise level
Cooling
Sound level dB(A) 43 51
Power level dB 57 62 Exterior dimensions (Height x Width x Depth) mm 262 x 615 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 6 24
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.48 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 9 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.46 Gas line : 0.40
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
16
-
'15 • SRK-T-171
Model
Item
SRK09CRR-S
Indoor unit SRK09CRR-S Outdoor unit SRC09CRR-S Cooling capacity (1) W 2638 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.868
Running current
Cooling
A
4.0 / 3.8
Inrush current 15 COP Cooling 3.04 Noise level
Cooling
Sound level dB(A) 43 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 262 x 769 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 24.5
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.54 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 10 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.45 Gas line : 0.41
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
17
-
'15 • SRK-T-171
Model
Item
SRK09CRR-S3
Indoor unit SRK09CRR-S3 Outdoor unit SRC09CRR-S3 Cooling capacity (1) W 2638 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.868
Running current
Cooling
A
4.0 / 3.8
Inrush current 15 COP Cooling 3.04 Noise level
Cooling
Sound level dB(A) 43 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 262 x 769 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 24.5
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.54 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 10 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.45 Gas line : 0.41
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
18
-
'15 • SRK-T-171
Model
Item
SRK09CRR-S4
Indoor unit SRK09CRR-S4 Outdoor unit SRC09CRR-S4 Cooling capacity (1) W 2638 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.868
Running current
Cooling
A
4.0 / 3.8
Inrush current 15 COP Cooling 3.04 Noise level
Cooling
Sound level dB(A) 43 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 262 x 769 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 24.5
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.54 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 10 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.45 Gas line : 0.41
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
19
-
'15 • SRK-T-171
Model
Item
SRK09CRR-S5
Indoor unit SRK09CRR-S5 Outdoor unit SRC09CRR-S5 Cooling capacity (1) W 2638 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 0.868
Running current
Cooling
A
4.0 / 3.8
Inrush current 15 COP Cooling 3.04 Noise level
Cooling
Sound level dB(A) 43 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 262 x 769 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 24.5
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.54 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 10 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.45 Gas line : 0.41
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
20
-
'15 • SRK-T-171
Model
Item
SRK09CRR-S6
Indoor unit SRK09CRR-S6 Outdoor unit SRC09CRR-S6 Cooling capacity (1) W 2638 Power source 1 Phase, 220-230V, 50Hz
Operation data
Power consumption
Cooling kW 0.868
Running current
Cooling
A
4.0 / 3.8
Inrush current 15 COP Cooling 3.04 Noise level
Cooling
Sound level dB(A) 43 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 262 x 769 x 210 435 x 645 (+50) x 275 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 24.5
Refrigerant equipment
Compressor type & Q'ty GKS102PAB (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 (POE [RB68A] or PVE [FVC68D]) Refrigerant (4) kg R410A 0.54 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Cross flow fan x 1 Propeller fan x 1 Motor W 17 22 Air flow Cooling m3/min 10 23 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 1
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor Fan motor error protection,
Cooling overload protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ9.52 (3/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.45 Gas line : 0.41
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 10
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
21
-
'15 • SRK-T-171
Model
Item
SRK12CR-S
Indoor unit SRK12CR-S Outdoor unit SRC12CR-S Cooling capacity (1) W 3450 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 1.120
Running current
Cooling
A
5.1
Inrush current 7.5 COP Cooling 3.08 Noise level
Cooling
Sound level dB(A) Hi : 43 Me : 39 Lo : 36 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 222 595 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 31
Refrigerant equipment
Compressor type & Q'ty GKS139PAA ( Rotary type ) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 ,POE(RB68A) or PVE(FVC68D) Refrigerant (4) kg R410A 0.78 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 17 25 Air flow Cooling m3/min 15 38 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection,
Frost protection, Serial signal error protection, Fan motor error protection,
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.57 Gas line : 0.55
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C JIS C 9612, TISI 1155, 2134, 812
(2) This air-conditioner is manufactured and tested in conformity with the TISI. (3) The operation data are applied to the 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
22
-
'15 • SRK-T-171
Model
Item
SRK12CR-S3
Indoor unit SRK12CR-S3 Outdoor unit SRC12CR-S3 Cooling capacity (1) W 3450 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 1.12
Running current
Cooling
A
5.1
Inrush current 7.5 COP Cooling 3.08 Noise level
Cooling
Sound level dB(A) Hi : 43 Me : 39 Lo : 36 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 222 595 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 31
Refrigerant equipment
Compressor type & Q'ty GKS139PAA ( Rotary type ) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 ,POE(RB68A) or PVE(FVC68D) Refrigerant (4) kg R410A 0.78 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 17 25 Air flow Cooling m3/min 15 38 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection,
Frost protection, Serial signal error protection, Fan motor error protection,
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.57 Gas line : 0.55
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
23
-
'15 • SRK-T-171
Model
Item
SRK12CR-S4
Indoor unit SRK12CR-S4 Outdoor unit SRC12CR-S4 Cooling capacity (1) W 3450 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 1.12
Running current
Cooling
A
5.1
Inrush current 7.5 COP Cooling 3.08 Noise level
Cooling
Sound level dB(A) Hi : 43 Me : 39 Lo : 36 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 222 595 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 31
Refrigerant equipment
Compressor type & Q'ty GKS139PAA ( Rotary type ) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 ,POE(RB68A) or PVE(FVC68D) Refrigerant (4) kg R410A 0.78 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 17 25 Air flow Cooling m3/min 15 38 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection,
Frost protection, Serial signal error protection, Fan motor error protection,
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.57 Gas line : 0.55
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
24
-
'15 • SRK-T-171
Model
Item
SRK12CR-S5
Indoor unit SRK12CR-S5 Outdoor unit SRC12CR-S5 Cooling capacity (1) W 3450 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 1.12
Running current
Cooling
A
5.1
Inrush current 7.5 COP Cooling 3.08 Noise level
Cooling
Sound level dB(A) Hi : 43 Me : 39 Lo : 36 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 222 595 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 31
Refrigerant equipment
Compressor type & Q'ty GKS139PAA ( Rotary type ) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 ,POE(RB68A) or PVE(FVC68D) Refrigerant (4) kg R410A 0.78 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 17 25 Air flow Cooling m3/min 15 38 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection,
Frost protection, Serial signal error protection, Fan motor error protection,
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.57 Gas line : 0.55
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
25
-
'15 • SRK-T-171
Model
Item
SRK12CR-S6
Indoor unit SRK12CR-S6 Outdoor unit SRC12CR-S6 Cooling capacity (1) W 3450 Power source 1 Phase, 220-240V, 50Hz
Operation data
Power consumption
Cooling kW 1.12
Running current
Cooling
A
5.1
Inrush current 7.5 COP Cooling 3.08 Noise level
Cooling
Sound level dB(A) Hi : 43 Me : 39 Lo : 36 50
Power level dB 57 61 Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 222 595 x 780 (+62) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 7 31
Refrigerant equipment
Compressor type & Q'ty GKS139PAA ( Rotary type ) x 1 Motor (Starting method) kW PSC Refrigerant oil
0.30 ,POE(RB68A) or PVE(FVC68D) Refrigerant (4) kg R410A 0.78 ( Pre-charged up to the piping length of 5m ) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes Device control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 17 25 Air flow Cooling m3/min 15 38 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat — Operation display RUN : Green, TIMER : Yellow
Safety devices
Compressor overheat protection,
Frost protection, Serial signal error protection, Fan motor error protection,
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.57 Gas line : 0.55
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.5 (Outdoor unit is higher)
Max.5 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 5m connecting piping. (Purging is not required even for the short piping.)
If the piping length is 5m to 15m, additional refrigerant is 10g per each 1m longer than 5m.
The pipe length is 5m.
-
26
-
'15 • SRK-T-171
2. EXTERIOR DIMENSIONS
(1) Indoor units
Models SRK05CR-S, S3, S6
SRK05CRP-S, S3
SRK09CR-S, S3, S4, S5
SRK09CRP-S, S3, S5
Note(1)Themodelnamelabelisattached
   ontheundersideofthepanel.
60
150
17.3
2555
45
55
45
25
615
615
262
3210
45
609
44
56
247.1
(Servicespace)
15
7.2 7.7
44
56 40152.1
100
(Servicespace)
155.4
181.9 250 181.9
100
(Servicespace)
303 155.4
Unit
100
(Servicespace)
445.9
398.2
Installationplate
Unit:mm
Wirelessremotecontrol
Spaceforinstallationandservicewhenviewingfromthefront
Holeonwallforrightrearpiping
Holeonwallforleftrearpiping
Outletforwiring
Drainhose
Liquidpiping
F
ECD
B
Symbol
(φ65)
VP16
eralF()"41(53.6φ
Content
(φ65)
Outletforpiping(onbothside)
G
Outletfordownpiping
(Refertotheaboveview)
D E AB C
Gaspiping
A
eralF()"83(25.9φ
G
F
Terminalblock
-
27
-
'15 • SRK-T-171
G
Terminal block
F
GG
Unit:mm
Wireless remote control
Outlet for down piping
Refer to the above view
Space for installation and service when viewing from the front
D E C
Hole on wall for right rear piping
Hole on wall for left rear piping
Gas piping
Outlet for wiring
Drain hose
Liquid piping
F
ECD
B
Symbol
A
65)
VP16
φ6.35(14")(Flare)
Content
65)
Outlet for pipingon both side
G
Model 09 ; φ9.52(38")(Flare)
Model 12 ; φ12.7(14")(Flare)
AB
Note1The model name label is attached
    on the underside of the indoor unit.
60
150
17.3
190 40.1
47
130.5 508 130.5
157 455 157
187.5 394 187.5
47
7.6247.56.9
Service space
65
Service space
15
50
Service space
100
Service space
55
409
449
530
55
Installation plate
Unit
6025 60 25
768.1
45
45
769
262
45
609
210 3
Models SRK09CRR-S, S3, S4, S5, S6
SRK12CR-S, S3, S4, S5, S6
-
28
-
'15 • SRK-T-171
(2) Outdoor units Models SRC05CR-S, S3, S6
SRC05CRP-S, S3 SRC09CR-S, S3, S4, S5 SRC09CRP-S, S3, S5 SRC09CRR-S, S3, S4, S5, S6
eralF()"83(25.9φ
Content
C Pipecable draw-out hole
D
E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(gas side)
M10×4places
φ20×2places
Service valve connection(liquid side)
eralF()"41
53.6φ
Minimum installation space
Notes
.sedisruofllanosllawybdednuorrusebtontsumtI1
 (2The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
 (3Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicular ly
to the dominant wind direction.
 (4Leave 1m or more space above the unit.
 (5A wall in front of the blower outlet must not exceed the unit height.
 (6The model name label is attached on the right side of the unit.
L2
L3
L4
L1 600
100
100
Examples of
Dimensions
Unit:mm
mm
installation
Outlet
Intake
L3
L1
L2
Intake
Service
space
( )
L4
Open
322
50
40
12
135
275
120.5
74.5 480 91 19.7
694.2
16.8304.414.8
336
2-16x12
Terminal block
147.2
2
0
°
20
°
86.3 43.2
16.5
437
E
D
BCA
Loading...