Mitsubishi Electronics R410A User Manual

Air-Conditioners OUTDOOR UNIT
PUMY-P·NHMU (-BS)
For use with R410A
INSTALLATION MANUAL
For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing the air-conditioner unit.
MANUAL DE INSTALACIÓN
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado.
MANUEL D’INSTALLATION
Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil intérieur pour une utilisation sûre et correcte.
FOR INSTALLER
PARA EL INSTALADOR
POUR L’INSTALLATEUR
English
Français
Contents
1. Safety precautions ................................................................................... 2
2. Installation location .................................................................................. 3
3. Installing the outdoor unit......................................................................... 5
4. Installing the refrigerant piping................................................................. 5
Confirmation of parts attached
In addition to this manual, the following parts are supplied with the outdoor unit. They are used for grounding the S terminals of transmission terminal blocks TB3, TB7. For details refer to “6. Electrical work”.
1. Safety precautions
s Before installing the unit, make sure you read all the “Safety precau-
tions”.
s Please report to or take consent by the supply authority before connec-
tion to the system.
Warning: Describes precautions that must be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that must be observed to prevent damage to the unit.
Warning:
• The unit must not be installed by the user. Ask a dealer or an authorized
technician to install the unit. If the unit is installed incorrectly, water leakage, electric shock, or fire may result.
• For installation work, f ollow the instructions in the Installation Manual and use
tools and pipe components specifically made for use with R410A refrigerant. The R410A refrigerant in the HFC system is pressurized 1.6 times the pressure of usual refrigerants. If pipe components not designed for R410A refrigerant are used and the unit is not installed correctly, the pipes may burst and cause damage or injuries. In addition, water leaka ge, electric shock, or fire may result.
• The unit must be installed according to the instructions in or der to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor­rectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down and cause damage or injuries.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Consult a dealer regarding the appro­priate measures to prevent the allowable concentration from being exceeded. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual. The units must be powered by dedicated power lines and the correct volta ge and cir cuit break­ers must be used. Power lines with insufficient capacity or incorrect electri­cal work may result in electric shock or fire.
5. Drainage piping work ............................................................................... 8
6. Electrical work.......................................................................................... 8
7. Test run ................................................................................................... 1 1
Grounding lead wire (× 2)
After installation work has been completed, explain the “Safety Precautions”, use, and maintenance of the unit to the customer according to the information in the Op­eration Manual and perform the test run to ensure normal operation. Both the Instal­lation Manual and Operation Manual must be given to the user for keeping. These manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affixed to the main unit.
• Use C1220 copper phosphorus, for copper and copper allo y seamless pipes, to connect the refrigerant pipes. If the pipes are not connected correctly, the unit will not be properly grounded and electric shock may result.
• Use only specified cables for wiring. The connections must be made securely without tension on the terminals. If the cables are connected or installed in­correctly, overheating or fire may result.
• The terminal block cover panel of the outdoor unit must be firml y attached. If the cover panel is mounted incorrectly and dust and moisture enter the unit, electric shock or fire may result.
• When installing or moving the air conditioner , use only the specified refriger­ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig­erant and do not allow air to remain in the lines. Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them. If accessories are incorrectly in­stalled, water leakage, electric shock, or fire may result.
• Do not alter the unit. Consult a dealer for repair s. If alterations or repairs are not performed correctly, water leakage, electric shock, or fire may result.
• The user should never attempt to repair the unit or transfer it to another loca­tion. If the unit is installed incorrectly, water leakage, electric shock, or fire may result. If the air conditioner must be repaired or moved, ask a dealer or an authorized technician.
• After installation has been completed, check for refrigerant leaks. If refriger­ant leaks into the room and comes into contact with the flame of a heater or portable cooking range, poisonous gases will be released.
1.1. Before installation
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is in­stalled in areas exposed to steam, v olatile oil (including machine oil), or sulfuric gas, areas exposed to high salt content such as the seaside, or areas where the unit will be covered by snow, the performance can be significantly re­duced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be pr oduced, flow, or accumulate. If combustible gas accum ulates around the unit, fire or explo­sion may result.
• The outdoor unit produces condensation during the heating operation. Make sure to provide drainage around the outdoor unit if such condensation is likely to cause damage.
1.2. Before installation (relocation)
Caution:
• Be extremely careful when transporting the units. Two or more persons are needed to handle the unit, as it weighs 20 kg [44 lbs] or more. Do not grasp the packaging bands. Wear protective gloves to remove the unit from the packag­ing and to move it, as you can injure your hands on the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials, such as nails and other metal or wooden parts may cause stabs or other injuries.
• The base and attachments of the outdoor unit must be periodically chec ked for looseness, cracks or other damage. If such defects are left uncorrected, the unit may fall down and cause damage or injuries.
2
• When installing the unit in a hospital or communications office, be prepared for noise and electronic interference. Inverters, home appliances, high-fre­quency medical equipment, and radio communications equipment can cause the air conditioner to malfunction or breakdown. The air conditioner may also affect medical equipment, disturbing medical care, and comm unications equip­ment, harming the screen display quality.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too much, the flare nut can break after an extended period and refrigerant can leak out.
37-13/32
13+1-3/16
53-5/32
6-7/8
23-5/8
14-9/16
1. Safety precautions
1.3. Before electric work
Caution:
Be sure to install circuit breakers. If not installed, electric shock may result.
For the power lines, use standard cables of sufficient capacity. Otherwise, a
short circuit, overheating, or fire may result.
When installing the power lines, do not apply tension to the cables. If the connections are loosened, the cables can snap or break and overheating or fire may result.
1.4. Before starting the test run
Caution:
T urn on the main power s witch more than 12 hours before starting operation. Starting operation just after turning on the power switch can severely dam­age the internal parts. Keep the main power switch turned on during the op­eration season.
Before starting operation, check that all panels, guards and other protective parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.
1.5. Using R410A refrigerant air conditioners
Caution:
Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust. Use pipes with the specified thickness. (Refer to page
5) Note the following if reusing existing pipes that carried R22 refrigerant.
- Replace the existing flare nuts and flare the flared sections again.
- Do not use thin pipes. (Refer to page 5)
Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing. (Leave elbow joints, etc. in their packaging.) If dust, debris, or moisture enters the refrigerant lines, oil dete­rioration or compressor breakdown may result.
Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections. If mineral oil is mixed in the refrigeration oil, oil deterioration may result.
Be sure to ground the unit. Do not connect the ground wire to gas or water pipes, lighting rods, or telephone grounding lines. If the unit is not properly grounded, electric shock may result.
Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specified capacity . If the circuit breaker capacity is larger than the specified capacity, breakdown or fire may result.
Do not touch any switch with wet hands. Electric shock may result.
Do not touch the refrigerant pipes with bare hands during operation. The
refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant. If you touch the pipes, burns or frostbite may result.
After stopping operation, be sure to wait at least five minutes before turning off the main power switch. Otherwise, water leakage or breakdown may result.
Do not use refrigerant other than R410A refrigerant. If another refrigerant is used, the chlorine will cause the oil to deteriorate.
Use the following tools specifically designed for use with R410A refrigerant. The following tools are necessary to use R410A refrigerant. Contact your nearest dealer for any questions.
Tools (for R410A)
Gauge manifold Flare tool
Charge hose Size adjustment gauge
Gas leak detector Vacuum pump adapter
Torque wrench Electronic refrigerant charging scale
Be sure to use the correct tools. If dust, debris, or moisture enters the refrig­erant lines, refrigeration oil deterioration may result.
Do not use a charging cylinder. If a charging cylinder is used, the composi­tion of the refrigerant will change and the efficiency will be lowered.
1.6. Precautions for salt damage–resistant model (-BS model)
Although this product (only “-BS” model) has been designed to be resistant to salt damage, observe the following precautions to maintain the performance of the unit.
1.Avoid installing the unit in a location where it will be exposed directly to sea water or
sea breeze.
2.If the cover panel may become covered with salt, be sure to install the unit in a
location where the salt will be washed away by rainwater. (If a sunshade is in­stalled, it may be difficult for rainwater to clean the panel.)
2. Installation location
2.1. Refrigerant pipe
Refer to Fig. 4-1.
2.2. Choosing the outdoor unit installation location
Avoid locations exposed to sources of heat.
Select a location from which noise emitted by the unit will not inconvenience neighbors.
Select a location permitting easy wiring and pipe access to the power source and
indoor unit.
Avoid locations where comb ustible gases ma y leak, be produced, flow , or accum ulate.
Note that water may drain from the unit during operation.
Select a level location that can bear the weight and vibration of the unit.
Fig. 2-1
(inch)
3.To ensure that w ater does not collect in the base of the outdoor unit, make sure that the base is level, not at angle. Water collecting in the base of the outdoor unit could cause rust.
4.If the unit is installed in a coastal area, clean the unit with water regularly to remove any salt build-up.
5.If the unit is damaged during installation or maintenance, be sure to repair it.
6.Be sure to check the condition of the unit regularly.
7.Be sure to install the unit in a location with good drainage.
Avoid locations where the unit can be co vered by sno w. In areas where hea vy snow f all is anticipated, special precautions such as raising the installation location or installing a hood on the air intake must be taken to prevent the snow from blocking the air intake or blowing directly against it. This can reduce the airflow and a malfunction may result.
Avoid locations exposed to oil, steam, or sulfuric gas.
Use the transportation handles of the outdoor unit to transport the unit. If the unit is
carried from the bottom, hands or fingers may be pinched.
2.3. Outline dimensions (Outdoor unit) (Fig. 2-1)
Constraints on indoor unit installation
You should note that indoor units that can be connected to this outdoor unit are the following models.
Indoor units with model numbers P06-P54 (PUMY-P36 : P06-P36) can be con­nected. Refer to the tab le below for possib le 1-8 (PUMY-P36 : 1-6) room, indoor unit combinations.
Verification
The rated capacity should be determined by observing the table below. The unit’s quantities are limited in 1 to 8 units. For the next step, make sure that the total rated capacity selected will stay in a range of 50% - 130% of the outdoor unit capacity.
PUMY-P36 18,000 - 46,800 Btu/h
PUMY-P48 24,000 - 62,400 Btu/h
Indoor unit type P06 P08 P12 P15 P18 P24 P30 P36 P48 P54 Rated capacity (Cooling) (Btu/h)
Combinations in which the total capacity of indoor units exceeds the capacity of the outdoor unit will reduce the cooling capacity of each indoor unit below their rated cooling capacity. Thus, combine indoor units with an outdoor unit within the outdoor units capacity, if possible.
6,000 8,000 12,000 15,000 18,000 24,000 30,000 36,000 48,000 54,000
3
5-29/32
11-13/16
39-3/8
Max. 19-11/16
7-7/8
11-13/16
7-7/8
39-3/8
5-29/32
39-3/8
9-27/32
9-27/32
59-1/16
19-11/16
Max. 19-11/16
11-13/16
59-1/16
19-11/16
59-1/16
Max. 11-13/16
59-1/16
59-1/16
19-11/16
39-3/8
23-5/8
78-24/32
5-29/32
59-1/16
23-5/8
118-4/32
19-11/16
59-1/16
31-1/2
5-29/32
2. Installation location
2.4. Ventilation and service space
2.4.1. When installing a single outdoor unit
Minimum dimensions are as follows, e xcept for Max., meaning Maximum dimensions, indicated. Refer to the figures for each case.
1 Obstacles at rear only (Fig. 2-2) 2 Obstacles at rear and above only (Fig. 2-3)
Do not install the optional air outlet guides for upward airflow.
3 Obstacles at rear and sides only (Fig. 2-4) 4 Obstacles at front only (Fig. 2-5)
When using an optional air outlet guide, the clearance is 500 mm [19-11/16 inch] or more.
5 Obstacles at front and rear only (Fig. 2-6)
When using an optional air outlet guide, the clearance is 500 mm [19-11/16 inch] or more.
6 Obstacles at rear, sides, and above only (Fig. 2-7)
Do not install the optional air outlet guides for upward airflow.
2.4.2. When installing multiple outdoor units
Leave 10 mm [13/32 inch] space or more between the units.
1 Obstacles at rear only (Fig. 2-8) 2 Obstacles at rear and above only (Fig. 2-9)
No more than three units must be installed side by side. In addition, leave space as shown.
Do not install the optional air outlet guides for upward airflow.
3 Obstacles at front only (Fig. 2-10)
When using an optional air outlet guide, the clearance is 1000 mm [39-3/8 inch] or more.
4 Obstacles at front and rear only (Fig. 2-11)
When using an optional air outlet guide, the clearance is 1000 mm [39-3/8 inch] or more.
5 Single parallel unit arrangement (Fig. 2-12)
When using an optional air outlet guide installed for upward airflow, the clearance is 1000
mm [39-3/8 inch] or more.
6 Multiple parallel unit arrangement (Fig. 2-13)
When using an optional air outlet guide installed for upward airflow, the clearance is 1500
mm [59-1/16 inch] or more.
7 Stacked unit arrangement (Fig. 2-14)
The units can be stacked up to two units high.
No more than two stacked units must be installed side b y side. In addition, leave space as shown.
(inch)
Fig. 2-6
Fig. 2-9
Fig. 2-3
Fig. 2-5Fig. 2-4Fig. 2-2
Fig. 2-7
Fig. 2-8
Fig. 2-10 Fig. 2-11
4
Fig. 2-12 Fig. 2-13 Fig. 2-14
B
Max. 1-3/16
B
2. Installation location
D
23-5/8 23-5/8Min. 14-6/32
Min. 13/32
37-13/32
63/64
13
14-9/16
6-7/8 6-7/8
A
A
C
2.4.3. Windy location installation
When installing the outdoor unit on a rooftop or other location unprotected from the wind, situate the air outlet of the unit so that it is not directly exposed to strong winds. Strong wind entering the air outlet may impede the normal airflow and a malfunction may result. The following shows two examples of precautions against strong winds. 1 Install an optional air guide if the unit is installed in a location where strong winds
from a typhoon, etc. may directly enter the air outlet. (Fig. 2-15)
A Air guide
2 Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-16)
B Wind direction
Fig. 2-15
3. Installing the outdoor unit
A M10 (3/8") bolt B Base C As long as possible. D Vent
Fig. 2-16
(inch)
Be sure to install the unit in a sturdy, level surface to prevent rattling noises during operation. (Fig. 3-1)
<Foundation specifications>
Foundation bolt M10 (3/8") Thickness of concrete 120 mm [4-23/32 inch] Length of bolt 70 mm [2-3/4 inch] Weight-bearing capacity 320 kg [705 lbs]
Make sure that the length of the foundation bolt is within 30 mm [1-3/16 inch] of the bottom surface of the base.
Secure the base of the unit firmly with four-M10 foundation bolts in sturdy locations.
Installing the outdoor unit
Do not block the vent. If the vent is blocked, operation will be hindered and break­down may result.
In addition to the unit base, use the installation holes on the back of the unit to attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 15 mm [ø13/16 × 19/32 inch] or less) and install on site.
Warning:
The unit must be securely installed on a structure that can sustain its weight. If the unit is mounted on an unstable structure, it may fall down and cause damage or injuries.
The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons, or strong winds. An incor­rectly installed unit may fall down and cause damage or injuries.
4. Installing the refrigerant piping
Fig. 3-1
4.1. Precautions for devices that use R410A refrigerant
Refer to page 3 for precautions not included below on using air conditioner s with R410A refrigerant.
Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections.
Use C1220 copper phosphorus, for copper and copper allo y seamless pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses specified in the table to the below. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric com­pounds, oxidants, debris, or dust.
Warning: When installing or moving the air conditioner, use only the specified refriger­ant (R410A) to charge the refrigerant lines. Do not mix it with any other refriger­ant and do not allow air to remain in the lines. Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards.
Indoor unit type P06-P18 P24-P54
Liquid pipe
Gas pipe
Do not use pipes thinner than those specified above.
ø6.35 mm [1/4 inch] ø9.52 mm [3/8 inch]
thickness 0.8 mm [1/32 inch] thickness 0.8 mm [1/32 inch]
ø12.7 mm [1/2 inch] ø15.88 mm [5/8 inch]
thickness 0.8 mm [1/32 inch] thickness 1.0 mm [5/128 inch]
5
B
A
H
B C
L
r
d
ahb c
C
C
CC
90° ±0.5°
øA
R0.4~R0.8
A
45°±2°
B
C
D
A
A
B
4. Installing the refrigerant piping
B
A
a
b
c
C
C
CC
d
H
h
L
r
A+a+b+c+d = 120 m [394 ft] L = A+d = 80 m [262 ft], R= d = 30 m [100 ft] H = 30 m [100 ft] (Outdoor lower H = 20 m [70 ft]) h = 12 m [39 ft]
A Flare cutting dimensions B Flare nut tightening torque
A+B+C+a+b+c+d = 120 m [394 ft] L = A+B+C+d = 80 m [262 ft] R= B+C+d = 30 m [100 ft] H = 30 m [100 ft] (Outdoor lower H = 20 m [70 ft]) h = 12 m [39 ft]
A : Outdoor Unit B : First Branch C : Indoor unit
Fig. 4-1
(inch)
A (mm [inch])
Å Liquid pipe ı Gas pipe
PUMY ø9.52 [3/8] ø15.88 [5/8]
B, C, D (mm [inch])
Ç Total capacity of indoor units Å Liquid pipe ı Gas pipe
ø9.52 [3/8] ø15.88 [5/8]
a, b, c, d, e, f (mm [inch])
Î Model number Å Liquid pipe ı Gas pipe P06, P08, P12, P15, P18 ø6.35 [1/4] ø12.7 [1/2] P24, P30, P36, P48, P54 ø9.52 [3/8] ø15.88 [5/8]
Branch kit model
CMY-Y62-G-E
Ï 4-Branching header Ì 8-Branching header
CMY-Y64-G-E CMY-Y68-G-E
4.2. Connecting pipes (Fig. 4-2)
Fig. 4-1 is a sample of piping system.
When commercially available copper pipes are used, wrap liquid and gas pipes with commercially available insulation materials (heat-resistant to 100°C [212°F] or more, thickness of 12 mm [1/2 inch] or more).
The indoor parts of the drain pipe should be wrapped with polyethylene foam insu­lation materials (specific gravity of 0.03, thickness of 9 mm [23/64 inch] or more).
Apply thin layer of refrigerant oil to pipe and joint seating surf ace before tightening flare nut. A
Use two wrenches to tighten piping connections. B
Use leak detector or soapy water to check f or gas leaks after connections are com-
pleted.
Apply refrigerating machine oil over the entire flare seat surface. C
Use the flare nuts for the following pipe size. D
(mm [inch])
Indoor unit Outdoor unit
P06-P18 P24-P54 P48
Gas side Pipe size ø12.7 [1/2] ø15.88 [5/8] ø15.88 [5/8]
Liquid side Pipe size ø6.35 [3/8] ø9.52 [3/8] ø9.52 [3/8]
Fig. 4-2
A (Fig. 4-2)
Copper pipe O.D. Flare dimensions
øA dimensions
ø6.35 [1/4] 8.7 - 9.1 [11/32-23/64] ø9.52 [3/8] 12.8 - 13.2 [1/2-33/64] ø12.7 [1/2] 16.2 - 16.6 [41/64-21/32]
ø15.88 [5/8] 19.3 - 19.7 [49/64-25/32]
B (Fig. 4-2)
Copper pipe O.D. Flare nut O.D. Tightening torque
(mm [inch]) (mm [inch]) (N·m [ft·lbs])
ø6.35 [1/4] 17 [43/64] 14 - 18 [10-13] ø6.35 [1/4] 22 [7/8] 34 - 42 [25-30] ø9.52 [3/8] 22 [7/8] 34 - 42 [25-30] ø12.7 [1/2] 26 [1-3/64] 49 - 61 [35-44]
ø12.7 [1/2] 29 [1-9/64] 68 - 82 [49-59] ø15.88 [5/8] 29 [1-9/64] 68 - 82 [49-59] ø15.88 [5/8] 36 [1-27/64] 100 - 120 [71-87]
6
(mm [inch])
A Die B Copper pipe
Fig. 4-3
When bending the pipes, be careful not to break them. Bend radius of 100 mm [3­15/16 inch] to 150 mm [5-27/32 inch] is sufficient.
Make sure the pipes do not contact the compressor. Abnormal noise or vibration may result.
1 Pipes must be connected starting from the indoor unit.
Flare nuts must be tightened with a torque wrench.
2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil
(Applied on site).
When usual pipe sealing is used, refer to Table 1 for flaring of R410A refrigerant pipes. The size adjustment gauge can be used to confirm A measurements.
Table 1 (Fig. 4-3)
Copper pipe O.D. A (mm [inch])
(mm [inch]) Clutch type
ø6.35 [1/4] 1.0 - 1.5 [3/64-1/16] ø9.52 [3/8] 1.0 - 1.5 [3/64-1/16] ø12.7 [1/2] 1.0 - 1.5 [3/64-1/16]
ø15.88 [5/8] 1.0 - 1.5 [3/64-1/16]
C
B
A
E
D
4. Installing the refrigerant piping
A
B
H
I
C D
E F
G
C
B
G
H
E
D
I
E
G
G
A
B
C
D
F
A
B
J
D
E
G
A Front piping cover B Piping cover C Stop valve D Service panel E Bend radius : 100 mm - 150 mm
Fig. 4-4
A Stop valve <Liquid side> B Stop valve <Gas side> C Service port D Open/Close section E Local pipe
F Sealed, same way for gas side G Pipe cover H Do not use a wrench here.
Refrigerant leakage may result.
I Use two wrenches here.
Fig. 4-5
4.3. Refrigerant piping (Fig. 4-4)
Remove the service panel D (three screws) and the front piping cover A (two screws) and rear piping cover B (two screws). 1 Perform refrigerant piping connections for the indoor/outdoor unit when the out-
door units stop valve is completely closed.
2 Vacuum-purge air from the indoor unit and the connection piping. 3 After connecting the refrigerant pipes, check the connected pipes and the indoor
unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)
4 Vacuumize the refrigerant lines through the service port of the liquid and gas stop
valves. And then open the stop v alves completely (f or both the liquid and gas stop valves). This will completely connect the refrigerant lines of the indoor and out­door units.
If the stop valves are left closed and the unit is operated, the compressor and control valves will be damaged.
Use a leak detector or soapy water to check for gas leaks at the pipe connec­tion sections of the outdoor unit.
Do not use the refrigerant from the unit to purge air from the refrigerant lines.
After the valve work is completed, tighten the valve caps to the correct torque:
20 to 25 N·m [14 to 18 ft·lbs] (200 to 250 kgf·cm). Failure to replace and tighten the caps may result in refrigerant leakage. In addition, do not damage the insides of the valve caps as they act as a seal to prevent refrigerant leakage.
5 Use sealant to seal the ends of the thermal insulation around the pipe connection
sections to prevent water from entering the thermal insulation.
4.4. Refrigerant pipe airtight testing method
(1)Connect the testing tools.
Make sure the stop valves A B are closed and do not open them.
Add pressure to the refr igerant lines through the service por t C of the liquid
stop valve A and the gas stop valve B.
(2) Do not add pressure to the specified pressure all at once; add pressure little by little .
1 Pressurize to 0.5 MPa [73 PSIG], wait five minutes, and make sure the
pressure does not decrease.
2 Pressurize to 1.5 MPa [218 PSIG], wait five minutes, and make sure the pres-
sure does not decrease.
3 Pressurize to 3.8 MPa [550 PSIG] and measure the surrounding temperature
and refrigerant pressure.
(3)If the specified pressure holds for about one day and does not decrease, the pipes
have passed the test and there are no leaks.
If the surrounding temperature changes by 1°C [1.8°F], the pressure will change
by about 0.01 MPa [1.5 PSIG]. Make the necessary corrections.
(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the
source of the gas leak.
(1)
Type A Type B
(2) 1
Fig. 4-6
Fig. 4-7
4.5. Stop valve opening method
(1)Gas side (Fig. 4-6) Type A 1 Remove the cap, then turn one-quarter rotation counter-clockwise with a flat-bladed
screwdriver to complete open.
2 Check that the valves are fully open, then return the cap to its original state and
tighten it down. Type B 1 Remove the cap, pull the handle toward you and rotate 1/4 turn in a counterclock-
wise direction to open. 2 Make sure that the stop valve is open completely, push in the handle and rotate
the cap back to its original position. (2)Liquid side (Fig. 4-7) 1 Remove the cap and turn the valve rod counterclockwise as far as it will go with
the use of a 4 mm [5/32 inch] hexagonal wrench. Stop turning when it hits the
stopper.
(ø6.35 [1/4 inch]: Approximately 4.5 revolutions) (ø9.52 [3/8 inch]: Approximately
2
10 revolutions) 2 Make sure that the stop valve is open completely, push in the handle and rotate
the cap back to its original position.
A Valve
B Unit side
C Handle
D Cap
E Local pipe side
Refrigerant pipes are protectively wrapped
The pipes can be protectively wrapped up to a diameter of ø90 mm [ø3-35/64 inch]
before or after connecting the pipes. Cut out the knockout in the pipe cover follow­ing the groove and wrap the pipes.
Pipe inlet gap
Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain.
(If the gaps are not closed, noise may be emitted or water and dust will enter the unit and breakdown may result.)
F Open position side G Service port H Wrench hole I Refrigerant flow direction J Operation section
7
4. Installing the refrigerant piping
* The figure to the left is an example only.
The stop valve shape, service port po­sition, etc., may vary according to the model.
* Turn section A only.
(Do not further tighten sections A and
B together. )
C Charge hose D Service port
Fig. 4-8
4.6. Additional refrigerant charge
Refrigerant of 3 kg [6.6 lbs] equivalent to 50 m [165 ft] total extended piping length is already included when the outdoor unit is shipped. Thus, if the total extended piping length is 50 m [165 ft] or less, there is no need to charge with additional refrigerant.
Calculation of Additional Refrigerant Charge
If the total extended piping length exceeds 50 m [165 ft], calculate the required additional refrigerant charge using the procedure shown below.
If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
<Additional Charge>
Additional refrigerant charge
[lbs]
Liquid pipe size Total length of ø9.52 × 0.06 kg
=+–
[3/8" × 0.041 lbs]
kg
(m) × 0.06 (kg/m), [ft] × 0.041 [lbs/ft]
Liquid pipe size Total length of ø6.35 × 0.024 kg [1/4" × 0.016 lbs]
(m) × 0.024 (kg/m), [ft] × 0.016 [lbs/ft]
Refrigerant amount for outdoor unit
3.0 kg
[6.6 lbs]
Precautions when using the charge valve (Fig.4-8)
Do not tighten the service port too much when installing it, otherwise, the valve core could be deformed and become loose, causing a gas leak. After positioning section B in the desired direction, turn section A only and tighten it. Do not further tighten sections A and B together after tightening section A.
<Example> (Please see the lower half of Fig. 4-1.) Outdoor model : P48 Indoor 1: P24 A: ø9.52 [3/8"] 30 m [98 ft] a: ø9.52 [3/8"] 15 m [49 ft] 2: P15 b: ø6.35 [1/4"] 10 m [33 ft] 3: P08 c: ø6.35 [1/4"] 10 m [33 ft] 4: P06 d: ø6.35 [1/4"] 20 m [66 ft] The total length of each liquid line is as follows
ø9.52 [3/8"] : A + a = 30 m + 15 m = 45 m [98 ft + 49 ft = 147 ft] ø6.35 [1/4"] : b + c + d = 10 m + 10 m + 20 m = 40 m [33 ft + 33 ft + 66 ft = 132 ft]
Therefore, <Calculation example> Additional refrigerant charge = 45 m × 0.06 kg + 40 m × 0.024 kg – 3.0 kg = 0.7 kg (rounded up)
= [147 ft × 0.041 lbs + 132 ft × 0.016 lbs – 6.6 lbs = 1.54 lbs]
At the conditions below:
5. Drainage piping work
Outdoor unit drainage pipe connection
When drain piping is necessary, use the drain socket or the drain pan (option).
P36·P48 Drain socket PAC-SG61DS-E Drain pan PAC-SG64DP-E
6. Electrical work
6.1. Caution
1 Follow ordinance of your governmental organization for technical standard re-
lated to electrical equipment, wiring regulations and guidance of each electric power company.
2 Wiring for control (hereinafter referred to as transmission line) shall be (5 cm [2
inch] or more) apart from power source wiring so that it is not influenced by elec­tric noise from power source wiring. (Do not insert transmission line and power source wire in the same conduit.)
3 Be sure to provide designated grounding work to outdoor unit. 4 Give some allowance to wiring for electrical part box of indoor and outdoor units,
because the box is sometimes removed at the time of service work.
5 Never connect the main power source to terminal block of transmission line. If
connected, electrical parts will be burnt out.
6 Use 2-core shield cable for transmission line. If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor transmit­ting and receiving will cause erroneous operations.
7 Only the transmission line specified should be connected to the terminal block for
outdoor unit transmission. (T ransmission line to be connected with indoor unit : Terminal block TB3 f or trans­mission line, Other : Terminal block TB7 for centralized control) Erroneous connection does not allow the system to operate.
8 In case to connect with the upper class controller or to conduct group operation in
different refrigerant systems, the control line for transmission is required betw een the outdoor units each other. Connect this control line between the terminal blocks for centralized control. (2­wire line with no polarity) When conducting group operation in different refrigerant systems without con­necting to the upper class controller, replace the insertion of the short circuit connector from CN41 of one outdoor unit to CN40.
9 Group is set by operating the remote controller.
8
=
=
=
=
=
=
6. Electrical work
M1SM2
A
B
M1SM2L1L2GR
TB3 TB7
CONDUIT PLATE : accessory
A : Power source B : Transmission line
Fig. 6-1
6.3. Wiring transmission cables
1 Types of control cables
1. Wiring transmission cables
Types of transmission cables: Shielding wire CVVS or CPEVS
Cable diameter: More than 1.25 mm
Maximum wiring length: Within 200 m [656 ft]
2. M-NET Remote control cables Kind of remote control cable
Cable diameter
Remarks
2
[AWG16]
Shielding wire MVVS
0.5 to 1.25 mm When 10 m [32 ft] is exceeded, use cable with the same specifications as transmission line wir­ing
2
[AWG20 to AWG16]
6.2. Control box and connecting position of wiring (Fig. 6-1)
1. Connect the indoor unit transmission line to transmission terminal block (TB3), or
connect the wiring between outdoor units or the wiring with the centralized con­trol system to the centralized control terminal block (TB7). When using shielded wiring, connect shield ground of the indoor unit transmis-
sion line to the earth screw ( outdoor units and the central control system transmission line to the shield (S)
terminal of the centralized control terminal block (TB7) shield (S) terminal. In addition, in the case of outdoor units whose power supply connector CN41 has been replaced by CN40, the shield terminal (S) of terminal block (TB7) of the
centralized control system should also be connected to the ground (
2. Conduit mounting plates (ø27 [1-1/16 inch]) are being provided. Pass the power
supply and transmission wires through the appropriate knock-out holes, then re­move the knock-out piece from the bottom of the terminal box and connect the wires.
3. Fix power source wiring to terminal box by using buffer bushing for tensile force
(PG connection or the like).
3. MA Remote control cables
Kind of remote control cable
Cable diameter
2 Wiring examples
Controller name, symbol and allowable number of controllers.
Name Outdoor unit controller Indoor unit controller
Remote controller
) and connect shield ground of the line between
2-core cable (unshielded)
2
(AWG22) to 1.25 mm2 (AWG16)
0.3 mm
Symbol
OC
IC
RC
(M-NET)
MA
Allowable number of controllers
One to eight controllers for one OC Maximum of 16 controllers for one OC Maximum of two per group
).
Example of a group operation system with multiple outdoor units (Shielding wires and address setting are necessary.)
<Examples of Transmission Cable Wiring>
M-NET Remote Controller (Fig. 6-2)
MA Remote Controller (Fig. 6-3)
<Wiring Method and Address Settings> a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals. b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2
and terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC). d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC). e. The jumper connector CN41 on the control panel does not change.
f. Connect the terminal S on the terminal block for central control for the power supply unit to the ground terminal ( g. Set the address setting switch as follows.
Unit Range Setting Method
IC (Main) 01 to 50 Use the most recent address within the same group of indoor units
IC (Sub) 01 to 50
Outdoor Unit 51 to 100
M-NET R/C (Main) 101 to 150 Set at an IC (Main) address within the same group plus 100
M-NET R/C (Sub) 151 to 200 Set at an IC (Main) address within the same group plus 150
MA R/C Unnecessary address setting (Necessary main/sub setting)
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on. <Permissible Lengths>
1 M-NET Remote controller
Max length via outdoor units: L
Max transmission cable length: L
Remote controller cable length: r
2 MA Remote controller
Max length via outdoor unit (M-NET cable): L
Max transmission cable length (M-NET cable): L
Remote controller cable length:c
1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6+L7
1 and L3+L4 and L3+L5 and L6 and L2+L6 and L7
1, r2, r2 +r3,r4
If the length exceeds 10 m [33 ft], use a 1.25 mm calculation of the maximum length and overall length.
1 and c1+c2 +c3 and c1+c2+c3+c4
Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be in sequence with the IC (Main) Use the most recent address of all the indoor units plus 50 * The address automatically becomes “100” if it is set as 01 - 50”.
500 m [1640 ft] (1.25 mm2 [AWG16] or more)
10 m [33 ft] (0.5 to 1.25 mm2 [AWG20 to AWG16])
1+L2+L3+L4 and L1+L2+L6+L7
1 and L3+L4 and L6 and L2+L6 and L7
200 m [656 ft] (1.25 mm2 [AWG16] or more)
2
[AWG16] shielded wire. The length of this section (L8) should be included in the
500 m [1640 ft] (1.25 mm2 [AWG16] or more)
200 m [656 ft] (0.3 to 1.25 mm2 [AWG20 to AWG16])
200 m [656 ft] (1.25 mm2 [AWG16] or more)
) in the electrical component box.
9
6. Electrical work
A
B
~/N 208/230 V
GR
D D
C
A
D D
~/N 208/230 V
A
B
C
E
D
M1M2S
M1 M2 S
TB7
TB3
IC
(51)
M1 M2 S
TB5
RC
(01)
IC
M1 M2 S
TB5
(03)
IC
M1 M2 S
TB5
(02)
IC
M1 M2 S
TB5
(04)
IC
M1 M2 S
TB5
(05)
IC
M1 M2 S
TB5
(07)
IC
M1 M2 S
TB5
(06)
L2
L1
(101)
RC
(105)
RC
(104)
RC
(155)
OC
M1 M2 S
TB7
(53)
OC
r3
M1M2S
Power Supply
Unit
M1M2S
G-50A
L3
L6L7
L4
L5
r2
r4
r1
AB AB AB
AB
M1M2 S
TB3
A
B
C
E
D
M1 M2 S
TB7
IC
(51)
M1 M2 1 2S
TB5 TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
MA
(01)
IC
M1 M2 S
TB5
(03)
IC
M1 M2 S
TB5
(02)
IC
M1 M2 S
TB5
(04)
IC
M1 M2 S
TB5
(05)
IC
M1 M2 S
TB5
(07)
IC
M1 M2 S
TB5
(06)
L2
L1
MAMAMA
OC
M1 M2 S
TB7
(53)
OC
c1
c4
c3
S
Power Supply
Unit
S
G-50A
L3
L6L7
L4
c3
ABABAB
M1M2
M1M2
c1
c1
c2 c2
AB
M1M2S
TB3
M1M2S
TB3
M-NET Remote Controller
A : Group 1 B : Group 3 C : Group 5 D : Shielded Wire E : Sub Remote Controller
( ): Address
MA Remote Controller
Fig. 6-2 Fig. 6-3
6.4. Wiring of main power supply and equipment capacity
Schematic Drawing of Wiring (Example) (Fig. 6-4)
A : Switch (Breakers for Wiring and Current Leakage) B : Outdoor Unit C : Pull Box D : Indoor Unit
Fig. 6-4
Thickness of Wire for Main Power Supply and On/Off Capacities
Minimum
circuit
ampacity
26 A
Model
Outdoor Unit
Indoor Unit
P36, P48
Power Supply
~/N (single), 60 Hz, 208/230 V ~/N (single), 60 Hz, 208/230 V
Minimum Wire Thickness
Main Cable*2
(mm
2
[AWG])
Ground
5.3 [AWG10]5.3 [AWG10]
Breaker for
Wiring*1
Refer to installation manual of indoor unit.
Breaker for Current
Leakage
30 A 30 mA 0.1 sec. or less30 A
*1. A breaker with at least 3.0 mm [1/8 inch] contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Use copper supply wires. Use the electric wires over the rating voltage 300 V.
1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops. Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57). For example, use wiring such as YZW.
6. Install an earth longer than other cables.
Warning:
Be sure to use specified wires to connect so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause heating or fire.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.
Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction
of unit or fire.
10
Maximum rating
of over current
protector device
40 A
Loading...
+ 22 hidden pages