SAFETY PRECAUTIONS

WARNING
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.
(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle
the product correctly.
Manual for a description of the PLC system safety precautions.
In this manual, the safety precautions are classified into two levels: " WARNING" and " CAUTION".
Under some circumstances, failure to observe the precautions given under " CAUTION" may lead to serious
consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future reference.
[Design Precautions]
WARNING
Configure safety circuits external to the programmable controller to ensure that the entire system operates safely even when a fault occurs in the external power supply or the programmable controller. Failure to do so may result in an accident due to an incorrect output or malfunction. (1) Emergency stop circuits, protection circuits, and protective interlock circuits for conflicting
operations (such as forward/reverse rotations or upper/lower limit positioning) must be configured external to the programmable controller.
(2) When the programmable controller detects an abnormal condition, it stops the operation and all
outputs are:
• Turned off if the overcurrent or overvoltage protection of the power supply module is activated.
• Held or turned off according to the parameter setting if the self-diagnostic function of the CPU module detects an error such as a watchdog timer error.
(3) All outputs may be turned on if an error occurs in a part, such as an I/O control part, where the
CPU module cannot detect any error. To ensure safety operation in such a case, provide a safety mechanism or a fail-safe circuit external to the programmable controller. For a fail-safe circuit example, refer to "General Safety Requirements" in the MELSEC iQ-R Module Configuration Manual.
(4) Outputs may remain on or off due to a failure of a component such as a relay and transistor in an
output circuit. Configure an external circuit for monitoring output signals that could cause a serious accident.
In an output circuit, when a load current exceeding the rated current or an overcurrent caused by a load short-circuit flows for a long time, it may cause smoke and fire. To prevent this, configure an external safety circuit, such as a fuse.
Configure a circuit so that the programmable controller is turned on first and then the external power supply. If the external power supply is turned on first, an accident may occur due to an incorrect output or malfunction.
1
[Design Precautions]
WARNING
For the operating status of each station after a communication failure, refer to manuals relevant to the network. Incorrect output or malfunction due to a communication failure may result in an accident.
When connecting an external device with a CPU module or intelligent function module to modify data of a running programmable controller, configure an interlock circuit in the program to ensure that the entire system will always operate safely. For other forms of control (such as program modification, parameter change, forced output, or operating status change) of a running programmable controller, read the relevant manuals carefully and ensure that the operation is safe before proceeding. Improper operation may damage machines or cause accidents.
Especially, when a remote programmable controller is controlled by an external device, immediate action cannot be taken if a problem occurs in the programmable controller due to a communication failure. To prevent this, configure an interlock circuit in the program, and determine corrective actions to be taken between the external device and CPU module in case of a communication failure.
Do not write any data to the "system area" and "write-protect area" of the buffer memory in the module. Also, do not use any "use prohibited" signals as an output signal from the CPU module to each module. Doing so may cause malfunction of the programmable controller system. For the "system area", "write-protect area", and the "use prohibited" signals, refer to the user's manual for the module used.
If a communication cable is disconnected, the network may be unstable, resulting in a communication failure of multiple stations. Configure an interlock circuit in the program to ensure that the entire system will always operate safely even if communications fail. Failure to do so may result in an accident due to an incorrect output or malfunction.
To maintain the safety of the programmable controller system against unauthorized access from external devices via the network, take appropriate measures. To maintain the safety against unauthorized access via the Internet, take measures such as installing a firewall.
Configure safety circuits external to the programmable controller to ensure that the entire system operates safely even when a fault occurs in the external power supply or the programmable controller. Failure to do so may result in an accident due to an incorrect output or malfunction.
If safety standards (ex., robot safety rules, etc.,) apply to the system using the module, servo amplifier and servo motor, make sure that the safety standards are satisfied.
Construct a safety circuit externally of the module or servo amplifier if the abnormal operation of the module or servo amplifier differs from the safety directive operation in the system.
Do not remove the SSCNET cable while turning on the control circuit power supply of modules and servo amplifier. Do not see directly the light generated from SSCNET connector of the module or servo amplifier and the end of SSCNET cable. When the light gets into eyes, you may feel something wrong with eyes. (The light source of SSCNET complies with class1 defined in JISC6802 or IEC60825-1.)
2
[Design Precautions]
CAUTION
Do not install the control lines or communication cables together with the main circuit lines or power cables. Keep a distance of 100mm or more between them. Failure to do so may result in malfunction due to noise.
During control of an inductive load such as a lamp, heater, or solenoid valve, a large current (approximately ten times greater than normal) may flow when the output is turned from off to on. Therefore, use a module that has a sufficient current rating.
After the CPU module is powered on or is reset, the time taken to enter the RUN status varies depending on the system configuration, parameter settings, and/or program size. Design circuits so that the entire system will always operate safely, regardless of the time.
Do not power off the programmable controller or reset the CPU module while the settings are being written. Doing so will make the data in the flash ROM and SD memory card undefined. The values need to be set in the buffer memory and written to the flash ROM and SD memory card again. Doing so also may cause malfunction or failure of the module.
When changing the operating status of the CPU module from external devices (such as the remote RUN/STOP functions), select "Do Not OPEN in Program" for "Open Method Setting" of "Module Parameter". If "OPEN in Program" is selected, an execution of the remote STOP function causes the communication line to close. Consequently, the CPU module cannot reopen the line, and external devices cannot execute the remote RUN function.
[Installation Precautions]
WARNING
Shut off the external power supply (all phases) used in the system before mounting or removing the module. Failure to do so may result in electric shock or cause the module to fail or malfunction.
3
[Installation Precautions]
CAUTION
Use the programmable controller in an environment that meets the general specifications in the Safety Guidelines included with the base unit. Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
To mount a module, place the concave part(s) located at the bottom onto the guide(s) of the base unit, and push in the module until the hook(s) located at the top snaps into place. Incorrect mounting may cause malfunction, failure, or drop of the module.
To mount a module with no module fixing hook, place the concave part(s) located at the bottom onto the guide(s) of the base unit, push in the module, and fix it with screw(s). Incorrect mounting may cause malfunction, failure, or drop of the module.
When using the programmable controller in an environment of frequent vibrations, fix the module with a screw.
Tighten the screws within the specified torque range. Undertightening can cause drop of the screw, short circuit, or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
When using an extension cable, connect it to the extension cable connector of the base unit securely. Check the connection for looseness. Poor contact may cause malfunction.
When using an SD memory card, fully insert it into the SD memory card slot. Check that it is inserted completely. Poor contact may cause malfunction.
Securely insert an extended SRAM cassette into the cassette connector of the CPU module. After insertion, close the cassette cover and check that the cassette is inserted completely. Poor contact may cause malfunction.
Do not directly touch any conductive parts and electronic components of the module, SD memory card, extended SRAM cassette, or connector. Doing so may cause malfunction or failure of the module.
[Wiring Precautions]
WARNING
Shut off the external power supply (all phases) used in the system before installation and wiring. Failure to do so may result in electric shock or cause the module to fail or malfunction.
After installation and wiring, attach the included terminal cover to the module before turning it on for operation. Failure to do so may result in electric shock.
4
[Wiring Precautions]
CAUTION
Individually ground the FG and LG terminals of the programmable controller with a ground resistance of 100 ohms or less. Failure to do so may result in electric shock or malfunction.
Use applicable solderless terminals and tighten them within the specified torque range. If any spade solderless terminal is used, it may be disconnected when the terminal screw comes loose, resulting in failure.
Check the rated voltage and signal layout before wiring to the module, and connect the cables correctly. Connecting a power supply with a different voltage rating or incorrect wiring may cause fire or failure.
Connectors for external devices must be crimped or pressed with the tool specified by the manufacturer, or must be correctly soldered. Incomplete connections may cause short circuit, fire, or malfunction.
Securely connect the connector to the module. Poor contact may cause malfunction.
Do not install the control lines or communication cables together with the main circuit lines or power
cables. Keep a distance of 100mm or more between them. Failure to do so may result in malfunction due to noise.
Place the cables in a duct or clamp them. If not, dangling cable may swing or inadvertently be pulled, resulting in damage to the module or cables or malfunction due to poor contact. Do not clamp the extension cables with the jacket stripped. Doing so may change the characteristics of the cables, resulting in malfunction.
Check the interface type and correctly connect the cable. Incorrect wiring (connecting the cable to an incorrect interface) may cause failure of the module and external device.
Tighten the terminal screws or connector screws within the specified torque range. Undertightening can cause drop of the screw, short circuit, fire, or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, fire, or malfunction.
When disconnecting the cable from the module, do not pull the cable by the cable part. For the cable with connector, hold the connector part of the cable. For the cable connected to the terminal block, loosen the terminal screw. Pulling the cable connected to the module may result in malfunction or damage to the module or cable.
Prevent foreign matter such as dust or wire chips from entering the module. Such foreign matter can cause a fire, failure, or malfunction.
A protective film is attached to the top of the module to prevent foreign matter, such as wire chips, from entering the module during wiring. Do not remove the film during wiring. Remove it for heat dissipation before system operation.
Programmable controllers must be installed in control panels. Connect the main power supply to the power supply module in the control panel through a relay terminal block. Wiring and replacement of a power supply module must be performed by qualified maintenance personnel with knowledge of protection against electric shock. For wiring, refer to the MELSEC iQ-R Module Configuration Manual.
For Ethernet cables to be used in the system, select the ones that meet the specifications in the user's manual for the module used. If not, normal data transmission is not guaranteed.
5
[Startup and Maintenance Precautions]
WARNING
Do not touch any terminal while power is on. Doing so will cause electric shock or malfunction.
Correctly connect the battery connector. Do not charge, disassemble, heat, short-circuit, solder, or
throw the battery into the fire. Also, do not expose it to liquid or strong shock. Doing so may cause the battery to generate heat, explode, ignite, or leak, resulting in injury or fire.
Shut off the external power supply (all phases) used in the system before cleaning the module or retightening the terminal screws, connector screws, or module fixing screws. Failure to do so may result in electric shock.
[Startup and Maintenance Precautions]
CAUTION
When connecting an external device with a CPU module or intelligent function module to modify data of a running programmable controller, configure an interlock circuit in the program to ensure that the entire system will always operate safely. For other forms of control (such as program modification, parameter change, forced output, or operating status change) of a running programmable controller, read the relevant manuals carefully and ensure that the operation is safe before proceeding. Improper operation may damage machines or cause accidents.
Especially, when a remote programmable controller is controlled by an external device, immediate action cannot be taken if a problem occurs in the programmable controller due to a communication failure. To prevent this, configure an interlock circuit in the program, and determine corrective actions to be taken between the external device and CPU module in case of a communication failure.
Do not disassemble or modify the modules. Doing so may cause failure, malfunction, injury, or a fire.
Use any radio communication device such as a cellular phone or PHS (Personal Handy-phone
System) more than 25cm away in all directions from the programmable controller. Failure to do so may cause malfunction.
Shut off the external power supply (all phases) used in the system before mounting or removing the module. Failure to do so may cause the module to fail or malfunction.
Tighten the screws within the specified torque range. Undertightening can cause drop of the component or wire, short circuit, or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
After the first use of the product, do not mount/remove the module to/from the base unit, and the terminal block to/from the module, and do not insert/remove the extended SRAM cassette to/from the CPU module more than 50 times (IEC 61131-2 compliant) respectively. Exceeding the limit of 50 times may cause malfunction.
After the first use of the product, do not insert/remove the SD memory card to/from the CPU module more than 500 times. Exceeding the limit of 500 times may cause malfunction.
Do not touch the metal terminals on the back side of the SD memory card. Doing so may cause malfunction or failure.
Do not touch the integrated circuits on the circuit board of an extended SRAM cassette. Doing so may cause malfunction or failure.
Do not drop or apply shock to the battery to be installed in the module. Doing so may damage the battery, causing the battery fluid to leak inside the battery. If the battery is dropped or any shock is applied to it, dispose of it without using.
6
[Startup and Maintenance Precautions]
CAUTION
Startup and maintenance of a control panel must be performed by qualified maintenance personnel with knowledge of protection against electric shock. Lock the control panel so that only qualified maintenance personnel can operate it.
Before handling the module, touch a conducting object such as a grounded metal to discharge the static electricity from the human body. Failure to do so may cause the module to fail or malfunction.
Before testing the operation, set a low speed value for the speed limit parameter so that the operation can be stopped immediately upon occurrence of a hazardous condition.
Confirm and adjust the program and each parameter before operation. Unpredictable movements may occur depending on the machine.
When using the absolute position system function, on starting up, and when the module or absolute position motor has been replaced, always perform a home position return.
Before starting the operation, confirm the brake function.
Do not perform a megger test (insulation resistance measurement) during inspection.
After maintenance and inspections are completed, confirm that the position detection of the absolute
position detection function is correct.
Lock the control panel and prevent access to those who are not certified to handle or install electric equipment.
[Operating Precautions]
CAUTION
When changing data and operating status, and modifying program of the running programmable controller from an external device such as a personal computer connected to an intelligent function module, read relevant manuals carefully and ensure the safety before operation. Incorrect change or modification may cause system malfunction, damage to the machines, or accidents.
Do not power off the programmable controller or reset the CPU module while the setting values in the buffer memory are being written to the flash ROM in the module. Doing so will make the data in the flash ROM and SD memory card undefined. The values need to be set in the buffer memory and written to the flash ROM and SD memory card again. Doing so also may cause malfunction or failure of the module.
Note that when the reference axis speed is specified for interpolation operation, the speed of the partner axis (2nd, 3rd, or 4th axis) may exceed the speed limit value.
Do not go near the machine during test operations or during operations such as teaching. Doing so may lead to injuries.
[Disposal Precautions]
CAUTION
When disposing of this product, treat it as industrial waste.
When disposing of batteries, separate them from other wastes according to the local regulations. For
details on battery regulations in EU member states, refer to the MELSEC iQ-R Module Configuration Manual.
7
[Transportation Precautions]
CAUTION
When transporting lithium batteries, follow the transportation regulations. For details on the regulated models, refer to the MELSEC iQ-R Module Configuration Manual.
The halogens (such as fluorine, chlorine, bromine, and iodine), which are contained in a fumigant used for disinfection and pest control of wood packaging materials, may cause failure of the product. Prevent the entry of fumigant residues into the product or consider other methods (such as heat treatment) instead of fumigation. The disinfection and pest control measures must be applied to unprocessed raw wood.
8

CONDITIONS OF USE FOR THE PRODUCT

(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;
i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident;
and
ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the
case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general industries.
MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL
RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY
INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE
OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR
WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL
BULLETINS AND GUIDELINES FOR the PRODUCT.
("Prohibited Application")
Prohibited Applications include, but not limited to, the use of the PRODUCT in;
• Nuclear Power Plants and any other power plants operated by Power companies, and/or any other cases in which the
public could be affected if any problem or fault occurs in the PRODUCT.
• Railway companies or Public service purposes, and/or any other cases in which establishment of a special quality
assurance system is required by the Purchaser or End User.
• Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as Elevator and Escalator,
Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and
Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other
applications where there is a significant risk of injury to the public or property.
Notwithstanding the above, restrictions Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or
more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific
applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or
other safety features which exceed the general specifications of the PRODUCTs are required. For details, please
contact the Mitsubishi representative in your region.

INTRODUCTION

Thank you for purchasing the Mitsubishi Electric MELSEC iQ-R series programmable controllers.
This manual describes the system configuration, specifications, installation, wiring, maintenance and inspection, and
troubleshooting of the relevant products listed below.
Before using this product, please read this manual and the relevant manuals carefully and develop familiarity with the
functions and performance of the MELSEC iQ-R series programmable controller to handle the product correctly.
When applying the program examples provided in this manual to an actual system, ensure the applicability and confirm that it
will not cause system control problems.
Please make sure that the end users read this manual.
Relevant products
R16MTCPU, R32MTCPU, R64MTCPU
9

COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES

Method of ensuring compliance
To ensure that Mitsubishi programmable controllers maintain EMC and Low Voltage Directives when incorporated into other
machinery or equipment, certain measures may be necessary. Please refer to one of the following manuals.
MELSEC iQ-R Module Configuration ManualSafety Guidelines (This manual is included with the base unit.)
The CE mark on the side of the programmable controller indicates compliance with EMC and Low Voltage Directives.
Additional measures
To ensure that this product maintains EMC and Low Voltage Directives, please refer to the following manual. MELSEC iQ-R Motion Controller User's Manual
10

CONTENTS

SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
CONDITIONS OF USE FOR THE PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
RELEVANT MANUALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
TERMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
MANUAL PAGE ORGANISATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
CHAPTER 1 SYSTEM CONFIGURATION 16
1.1 Motion System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Equipment configuration in system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Peripheral device configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
R64MTCPU/R32MTCPU/R16MTCPU system overall configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Function explanation of the Motion CPU modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Restrictions on Motion systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.2 System Configuration Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Configuration equipment list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Software packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
1.3 Checking Production Information and Operating System Software Version . . . . . . . . . . . . . . . . . . . . . . .27
Checking production information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Checking operating system software version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1.4 Restrictions by the Software's Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.5 Engineering Software Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
CONTENTS
CHAPTER 2 EQUIPMENT SPECIFICATIONS 31
2.1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.2 Motion CPU Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Name of parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
LED display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Rotary switch setting and operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
2.3 Serial Absolute Synchronous Encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
2.4 SSCNETIII Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Connection between the Motion CPU module and servo amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Setting of the axis No. and switch of servo amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Precautions for SSCNETIII cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
CHAPTER 3 INSTALLATION AND WIRING 50
3.1 Mounting Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3.2 Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Mounting position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Installation of the base unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Installation and removal of module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3.3 Installation and Removal of SD Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3.4 Mounting of Serial Absolute Synchronous Encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
11
Power supply circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Safety circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
CHAPTER 4 START-UP PROCEDURES 56
4.1 Start-up Adjustment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
CHAPTER 5 INSPECTION AND MAINTENANCE 59
5.1 Daily Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.2 Periodic Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
5.3 Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
CHAPTER 6 TROUBLESHOOTING 62
6.1 Troubleshooting Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
6.2 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
6.3 Checking LED Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Checking LED display of the Motion CPU module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
6.4 Checking With Engineering Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.5 Troubleshooting by Circumstance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
When the READY LED of the Motion CPU module has turned OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
When an error is displayed or flickering in the dot matrix LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
When cannot write to Motion CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
When cannot read from Motion CPU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
When the servo amplifier does not start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
CHAPTER 7 EMC DIRECTIVES 68
7.1 Requirements for Compliance with the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Standards relevant to the EMC directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Installation instructions for EMC directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Parts of measure against noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Measure against noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
APPENDICES 74
Appendix 1 Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
SSCNETIII cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Serial absolute synchronous encoder cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
SSCNETIII cables (SC-J3BUSM-C) manufactured by Mitsubishi Electric System & Service. . . . . . . . . . . . . . 79
Appendix 2 Exterior Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Motion CPU module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Serial absolute synchronous encoder (Q171ENC-W8) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
REVISIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .84
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
TRADEMARKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
12

RELEVANT MANUALS

Manual Name [Manual Number] Description Available form
MELSEC iQ-R Motion Controller User's Manual [IB-0300235] (This manual)
MELSEC iQ-R Motion Controller Programming Manual (Common) [IB-0300237]
MELSEC iQ-R Motion Controller Programming Manual (Program Design) [IB-0300239]
MELSEC iQ-R Motion Controller Programming Manual (Positioning Control) [IB-0300241]
MELSEC iQ-R Motion Controller Programming Manual (Advanced Synchronous Control) [IB-0300243]
MELSEC iQ-R Motion Controller Programming Manual (Machine Control) [IB-0300309]
MELSEC iQ-R Motion Controller Programming Manual (G-Code Control) [IB-0300371]
This manual explains specifications of the Motion CPU modules, SSCNET cables, synchronous encoder, troubleshooting, and others.
This manual explains the Multiple CPU system configuration, performance specifications, common parameters, auxiliary/applied functions, error lists and others.
This manual explains the functions, programming, debugging for Motion SFC and others.
This manual explains the servo parameters, positioning instructions, device lists and others.
This manual explains the dedicated instructions to use synchronous control by synchronous control parameters, device lists and others.
This manual explains the dedicated instructions to use machine control by machine control parameters, machine positioning data, device lists and others.
This manual explains the dedicated instructions to use G-code control by G-code control parameters and G-code programs.
Print book
e-Manual PDF
Print book
e-Manual PDF
Print book
e-Manual PDF
Print book
e-Manual PDF
Print book
e-Manual PDF
Print book
e-Manual PDF
Print book
e-Manual PDF
e-Manual refers to the Mitsubishi FA electronic book manuals that can be browsed using a dedicated tool.
e-Manual has the following features:
• Required information can be cross-searched in multiple manuals.
• Other manuals can be accessed from the links in the manual.
• The hardware specifications of each part can be found from the product figures.
• Pages that users often browse can be bookmarked.
13

TERMS

Unless otherwise specified, this manual uses the following terms.
Ter m Description
R64MTCPU/R32MTCPU/R16MTCPU or Motion CPU (module)
MR-J4(W)-B Servo amplifier model MR-J4-B/MR-J4W-B
MR-J3(W)-B Servo amplifier model MR-J3-B/MR-J3W-B
AMP or Servo amplifier General name for "Servo amplifier model MR-J4-B/MR-J4W-B/MR-J3-B/MR-J3W-B"
RnCPU, PLC CPU or PLC CPU module Abbreviation for MELSEC iQ-R series CPU module
Multiple CPU system or Motion system Abbreviation for "Multiple PLC system of the R series"
CPUn Abbreviation for "CPU No.n (n = 1 to 4) of the CPU module for the Multiple CPU system"
Operating system software General name for "SW10DNC-RMTFW"
Engineering software package General name for MT Developer2/GX Works3
MELSOFT MT Works2 General product name for the Motion controller engineering software "SW1DND-MTW2"
MT Developer2 Abbreviation for the programming software included in the "MELSOFT MT Works2" Motion controller
GX Works3 General product name for the MELSEC PLC software package "SW1DND-GXW3"
Serial absolute synchronous encoder or Q171ENC-W8
SSCNET/H
SSCNET
SSCNET(/H) General name for SSCNET/H, SSCNET
Absolute position system General name for "system using the servomotor and servo amplifier for absolute position"
Intelligent function module General name for module that has a function other than input or output such as A/D converter module and D/A
SSCNET/H head module
Optical hub unit or MR-MV200 Abbreviation for SSCNET/H Compatible Optical Hub Unit (MR-MV200)
Sensing module General name for SSCNET/H compatible sensing module MR-MT2000 series
Sensing SSCNET/H head module MR-MT2010
Sensing extension module General name for I/O module (MR-MT2100), pulse I/O module (MR-MT2200), analog I/O module (MR-
Sensing I/O module or MR-MT2100 Abbreviation for I/O module (MR-MT2100)
Sensing pulse I/O module or MR-MT2200 Abbreviation for pulse I/O module (MR-MT2200)
Sensing analog I/O module or MR-MT2300 Abbreviation for analog I/O module (MR-MT2300)
Sensing encoder I/F module or MR-MT2400 Abbreviation for encoder I/F module (MR-MT2400)
*1
*1
*1
*1
Abbreviation for MELSEC iQ-R series Motion controller
engineering software
Abbreviation for "Serial absolute synchronous encoder (Q171ENC-W8)"
High speed synchronous network between Motion controller and servo amplifier
converter module.
Abbreviation for "MELSEC-L series SSCNET/H head module (LJ72MS15)"
or
Abbreviation for SSCNET/H head module (MR-MT2010)
MT2300), encoder I/F module (MR-MT2400)
*1 SSCNET: Servo System Controller NETwork
14

MANUAL PAGE ORGANISATION

Representation of device No. used in this manual
The "R" and "Q" beside the device No. of positioning dedicated signals such as "[Rq.1140] Stop command (R: M34480+32n/
Q: M3200+20n)" indicate the device No. for the device assignment methods shown below. When "R" and "Q" are not beside
the device No., the device No. is the same for both device assignment methods.
Symbol Device assignment method
R MELSEC iQ-R Motion device assignment
Q Q series Motion compatible device assignment
15
1 SYSTEM CONFIGURATION
Extension of the R series module
Motion CPU module
(R64MTCPU/R32MTCPU/
R16MTCPU)
: Selected according to the system
Main base unit
(R35B, R38B, R312B)
Power supply module/RnCPU/ I/O module/Intelligent function
module of the R series
Power supply module/
I/O module/Intelligent function
module of the R series
Extension cable
(RCB)
Servo amplifier
(MR-J4(W)-B)
Servo amplifier
(MR-J3(W)-B)
R6B extension base unit
(R65B, R68B, R312B)
SSCNETµcable
(MR-J3BUSM(-A/-B))
This section describes the Motion controller system configuration, precautions on use of system and configured equipment.
1.1 Motion System Configuration

Equipment configuration in system

16

1 SYSTEM CONFIGURATION

1.1 Motion System Configuration

Peripheral device configuration

Ethernet cable
*1
Personal computer
Motion CPU module
(R64MTCPU/R32MTCPU/
R16MTCPU)
Ethernet configuration
*1 Corresponding Ethernet cables
Part name Connection type Cable type Ethernet standard Specification
Ethernet cable Connection with HUB Straight cable 10BASE-T Compliant with Ethernet standards, category 5 or
100BASE-TX
Direct connection Straight cable
Crossover cable
10BASE-T
100BASE-TX
Selection criterion of cable
• Category : 5 or higher
• Diameter of lead: AWG26 or higher
• Shield: Copper braid shield and drain wire or copper braid shield and aluminium layered type shield
higher.
• Shielded twisted pair cable (STP cable)
1
1 SYSTEM CONFIGURATION
1.1 Motion System Configuration
17

R64MTCPU/R32MTCPU/R16MTCPU system overall configuration

RMT CPU
RCPU
R61P
PLC CPU/
Motion CPU
Main base unit
(R3B)
Extension base unit (R6B)
Extension cable (RCB)
Up to 7 extensions
RX
Line 1 SSCNETµ(/H) (CN1)
Line 2 SSCNETµ(/H) (CN2)
SSCNETµ cable (MR-J3BUSM(-A/-B))
RY
Motion CPU controlled modules
RD62R6AD
/
R6DA
P Manual pulse generator x2/module
Incremental synchronous encoder x2/module
Intelligent
function module
E
I/O module/ Intelligent function module
Analog Input/Output
Input/Output (Up to 4096 points)
External input signals
d01
M
E
d02 d16
M
E
d01
M
E
d02
M
E
M
E
d16
M
E
Power supply
module
Personal computer
GOT
USB/Ethernet
PERIPHERAL I/F
Cognex Corporation vision system
Sensing module MR-MT2000 series
*3
I/O module, Intelligent function module
L61P LJ72MS15
MELSEC-L series SSCNETµ/H head module (LJ72MS15)
*3
Sensing module MR-MT2000 series
*3
R64MTCPU: 2 lines (Up to 8 stations (Up to 4 stations/line)) R32MTCPU: 2 lines (Up to 8 stations (Up to 4 stations/line)) R16MTCPU: 1 line (Up to 4 stations)
I/O module, Intelligent function module
L61P LJ72MS15
R64MTCPU: 2 lines (Up to 64 axes (Up to 32 axes/line))
*2
R32MTCPU: 2 lines (Up to 32 axes (Up to 16 axes/line)) R16MTCPU: 1 line (Up to 16 axes)
External input signals of servo amplifier
Serial absolute synchronous
encoder
*1
(Q171ENC-W8)
Serial absolute synchronous encoder cable (Q170ENCCBLM-A)
E
MR-J3(W)-B/MR-J4(W)-B model servo amplifier Optical hub unit (MR-MV200) Inverter FR-A800/FR-A700 series VC´ series/VPH series servo driver manufactured by CKD Nikki Denso Co., Ltd. Stepping motor module AlphaStep/5-phase manufactured by ORIENTAL MOTOR Co., Ltd. IAI electric actuator controller manufactured by IAI Corporation
Upper stroke limit Lower stroke limit Stop signal Proximity dog/Speed-position switching
Upper stroke limit Lower stroke limit Proximity dog/Speed-position switching
18
*1 MR-J4-B-RJ only *2 Up to 16 axes per line for R64MTCPU when communication type is SSCNET. *3 SSCNET/H only
CAUTION
• Construct a safety circuit externally of the Motion controller or servo amplifier if the abnormal operation of the Motion controller or servo amplifier differ from the safety directive operation in the system.
• The ratings and characteristics of the parts (other than Motion controller, servo amplifier and servomotor) used in a system must be compatible with the Motion controller, servo amplifier and servomotor.
• Set the parameter values to those that are compatible with the Motion controller, servo amplifier, servomotor and regenerative resistor model and the system application. The protective functions may not function if the settings are incorrect.
1 SYSTEM CONFIGURATION
1.1 Motion System Configuration

Function explanation of the Motion CPU modules

• The following servo amplifiers can be controlled in Motion CPU module.
Motion CPU Servo amplifier control
R64MTCPU Up to 64 axes per 2 lines (up to 32 axes per 1 line)
R32MTCPU Up to 32 axes per 2 lines (up to 16 axes per 1 line)
R16MTCPU Up to 16 axes per 1 line
• It is possible to set the program which synchronized with the motion operation cycle and executed at fixed cycle (Min.
0.222ms).
• It is possible to execute a download of servo parameters to servo amplifier, servo ON/OFF to servo amplifier and position
commands, etc. by connecting between the Motion CPU module and servo amplifier with SSCNET cable.
• I/O modules and intelligent function modules (excluding some modules) can be controlled with the Motion CPU module.
(Page 24 PLC module which can be controlled by Motion CPU)
• Data exchange between CPU modules is possible by CPU buffer memory in the Multiple CPU system.
• Wiring is reduced by issuing the external signal (upper/lower stroke limit signal, proximity dog signal) via the servo amplifier.
• Battery is not required for the Motion CPU.

Restrictions on Motion systems

Combination of Multiple CPU system
• Motion CPU module cannot be used as standalone module. Be sure to install the MELSEC iQ-R series PLC CPU module
to CPU No.1. Refer to the following for the configurations in a Multiple CPU system with the PLC CPU module as CPU
No.1. MELSEC iQ-R Module Configuration Manual
• Up to four modules of MELSEC iQ-R series PLC CPU modules/Motion CPU modules can be installed from the CPU slot
(the slot on the right side of power supply module) to the I/O slot 6 of the main base unit. CPU modules are called CPU
No.1 to CPU No.4 from the left sequentially. There is no restriction on the installation order of CPU No.2 to No.4. For CPU
module other than CPU No.1, CPU reservation setting (allocating a CPU No. without actually installing a CPU module) can
be made.
• It takes about 10 seconds to startup (a state where it can be controlled) the Motion CPU. After startup, each CPU requires
time for initializing. For a system that begins executing programs without waiting for the startup of other CPUs, change the
Multiple CPU synchronous startup setting.
1
Motion CPU module restrictions
• The Motion CPU module only controls MELSEC iQ-R series modules. It cannot control MELSEC Q series modules.
• To execute the forced stop input, use a device set in the forced stop input setting ([Motion CPU Common Parameter]
[Basic Setting])
• Refer to the following for details of installing Motion CPU module to a DIN rail.
MELSEC iQ-R Module Configuration Manual
• Use the Graphic Operation Terminal (GOT) that supports Motion CPU (R64MTCPU/R32MTCPU/R16MTCPU).
1 SYSTEM CONFIGURATION
1.1 Motion System Configuration
19
SSCNET communication restrictions
• Set "SSCNET/H" or "SSCNET" for every line in the SSCNET setting ([Motion CPU Common Parameter] [Servo Network Setting]) to communicate with the servo amplifiers and SSCNET compatible equipment. The following shows the servo amplifiers and SSCNET compatible equipment that can be used when "SSCNET/H" and "SSCNET" are set.
: Usable, : Unusable
Servo amplifier/SSCNETIII compatible equipment SSCNET setting
SSCNETIII/H SSCNETIII
Servo amplifier MR-J4(W)-B 
MR-J3(W)-B 
Inverter FR-A800 series 
FR-A700 series 
Sensing module MR-MT2000 series 
SSCNET/H head module LJ72MS15 
VC series/VPH series servo driver manufactured by CKD Nikki Denso Co., Ltd 
Stepping motor module AlphaStep/5-phase manufactured by ORIENTAL MOTOR Co., Ltd 
IAI electric actuator controller manufactured by IAI Corporation 
*1 Operated in J3 compatibility mode
• The maximum No. of control axes per line for the Motion CPU (R64MTCPU/R32MTCPU/R16MTCPU) are shown below by
the communication type set in SSCNET setting. Settings that exceed the maximum No. of control axes per line cannot be
made.
Motion CPU Communication type
SSCNETIII/H SSCNETIII
R64MTCPU 32 axes 16 axes
R32MTCPU 16 axes
R16MTCPU 16 axes
*1
• The following are restrictions for the communication type depending on the operation cycle.
: No restriction
Operation cycle
0.222ms • Maximum 12 control axes per line.
0.444ms • Maximum 24 control axes per line.
0.888ms or more • Up to 4 stations per line can be set with the SSCNET/H head
*1 When the number of control axes per line setting exceeds the maximum number of control axes per line, operation is carried out at the
following operation cycles.
Maximum number of control axes per line Operation cycle
SSCNETIII/H SSCNETIII
13 to 24 axes 5 to 8 axes 0.444ms
25 axes or more 9 axes or more 0.888ms
Communication type
SSCNETIII/H SSCNETIII
*1
• MR-J4W3-B (software version A2 or earlier) cannot be used.
• 1 station per line can be set with the SSCNET/H head module
or sensing module.
• AlphaStep/5-phase cannot be used.
• Up to 2 axes per IAI electric actuator controller can be set.
• Up to 2 stations per line can be set with the SSCNET/H head
module and/or the sensing module.
• Up to 4 axes per IAI electric actuator controller can be set.
module and/or the sensing module.
*3
*4
*6
*1
*3
*6
*3
• The maximum number of control axes per line is 4 control axes.
*2
• Set the axis select rotary switch of the servo amplifier to "0 to 3". If the axis select rotary switch of servo amplifier is set to "4 to F", the servo amplifiers are not recognized.
• MR-J4W3-B (software version A2 or earlier) cannot be used.
•MR-J3W-B cannot be used.
• FR-A700 series, VC series, and VPH series cannot be used.
• The maximum number of control axes per line is 8 axes.
• Set the axis select rotary switch of the servo amplifier to "0 to 7". If the axis select rotary switch of servo amplifier is set to "8 to F", the servo amplifiers are not recognized.
*1
*1
*2
*5
*2 MR-J4W3-B (Software version "A3" or later) supports operation cycle 0.222ms. However, when using operation cycle 0.222ms, some
functions are restricted. Refer to the following for details. Servo amplifier Instruction Manual
1 SYSTEM CONFIGURATION
20
1.1 Motion System Configuration
*3 When using the sensing module in axis mode, there are no restrictions on the number of stations for the sensing module. *4 When AlphaStep/5-phase is present, operation is carried out at 0.444ms operation cycle. *5 When FR-A700 series, VC series, or VPH series are present, operation is carried out at 0.444ms operation cycle. *6 When the setting exceeds the number of control axes per controller, a minor error (error code: 1C83H) occurs.
Set the operation cycle as follows according to the number of control axes per controller.
Number of control axes per controller Operation cycle
1 to 2 axes 0.222ms or more
3 to 4 axes 0.444ms or more
5 axes or more 0.888ms or more
• When using MR-J4W-B, if there is at least one axis which has not been set in servo network setting, all axes of the
applicable servo amplifier cannot be connected, and all servo amplifiers after the applicable servo amplifier cannot be
connected. Set "Not used" to the applicable axis with a dip switch for the axis which is not used by MR-J4W-B.
• When using a multi-axis servo amplifier (MR-J4W-B), there is a restriction on the number of connectable units (servo
amplifier (MR-J4(W)-B), SSCNET/H head module, other drivers etc.) between the Motion CPU and the multi-axis servo
amplifier. The number of connectable units are shown below. When more than the number of connectable units are
connected, a warning (error code: 0C82H) occurs. While communication with MR-J4W-B is still possible when the
warning occurs, communication becomes unstable, therefore the unit configuration should be reviewed. Furthermore, when
an optical hub unit is used, the number of connectable units is reduced. Refer to the following for details of when an optical
hub unit is connected. MELSEC iQ-R Motion Controller Programming Manual (Common)
Servo amplifier Number of connectable units
MR-J4-B No restriction
MR-J4W2-B 1 axis set
2 axes set 14 units or less
MR-J4W3-B 1 axis set No restriction
2 axes set 14 units or less
3 axes set 13 units or less
1
1 SYSTEM CONFIGURATION
1.1 Motion System Configuration
21
1.2 System Configuration Equipment

Configuration equipment list

Motion controller related module
Part name Model name
Motion CPU module R64MTCPU Up to 64 axes control, Operation cycle 0.222[ms] or more, Built-in Ethernet 1.20
R32MTCPU Up to 32 axes control, Operation cycle 0.222[ms] or more, Built-in Ethernet 1.20
R16MTCPU Up to 16 axes control, Operation cycle 0.222[ms] or more, Built-in Ethernet 1.20
*2
PLC CPU module
C Controller module
Power supply module
Main base unit
*2
R00CPU Program capacity 10k steps, LD instruction processing speed 31.3ns,
R01CPU Program capacity 15k steps, LD instruction processing speed 31.3ns,
R02CPU Program capacity 20k steps, LD instruction processing speed 3.92ns,
R04CPU Program capacity 40k steps, LD instruction processing speed 0.98ns,
R08CPU Program capacity 80k steps, LD instruction processing speed 0.98ns,
R16CPU Program capacity 160k steps, LD instruction processing speed 0.98ns,
R32CPU Program capacity 320k steps, LD instruction processing speed 0.98ns,
R120CPU Program capacity 1200k steps, LD instruction processing speed 0.98ns,
R04ENCPU Program capacity 40k steps, LD instruction processing speed 0.98ns,
R08ENCPU Program capacity 80k steps, LD instruction processing speed 0.98ns,
R16ENCPU Program capacity 160k steps, LD instruction processing speed 0.98ns,
R32ENCPU Program capacity 320k steps, LD instruction processing speed 0.98ns,
R120ENCPU Program capacity 1200k steps, LD instruction processing speed 0.98ns,
R08PCPU Program capacity 80k steps, LD instruction processing speed 0.98ns,
R16PCPU Program capacity 160k steps, LD instruction processing speed 0.98ns,
R32PCPU Program capacity 320k steps, LD instruction processing speed 0.98ns,
R120PCPU Program capacity 1200k steps, LD instruction processing speed 0.98ns,
*2
R12CCPU-V Endian format: Little endian, OS: VxWorks Version 6.9 1.26
*3
R61P 100 to 240VAC input, 5VDC 6.5A output
R62P 100 to 240VAC input, 5VDC 3.5A/24VDC 6.0A output
R63P 24VDC input, 5VDC 6.5A output
R64P 100 to 240VAC input, 5VDC 9A output
R35B Number of I/O modules: 5 slots 0.58
R38B Number of I/O modules: 8 slots 0.71
R312B Number of I/O modules: 12 slots 0.88
R310B-HT Number of I/O modules: 10 slots, extended temperature range 0.82
*1
Description Current
Built-in Ethernet port
Built-in Ethernet port
Built-in Ethernet port
Built-in Ethernet port
Built-in Ethernet port
Built-in Ethernet port
Built-in Ethernet port
Built-in Ethernet port
Built-in Ethernet port, Built-in CC-Link IE
Built-in Ethernet port, Built-in CC-Link IE
Built-in Ethernet port, Built-in CC-Link IE
Built-in Ethernet port, Built-in CC-Link IE
Built-in Ethernet port, Built-in CC-Link IE
Built-in Ethernet port
Built-in Ethernet port
Built-in Ethernet port
Built-in Ethernet port
Remark consumption 5VDC[A]
0.67
0.67
0.67
0.67
0.67
0.67
0.67
0.67
1.49
1.49
1.49
1.49
1.49
0.76
0.76
0.76
0.76
22
1 SYSTEM CONFIGURATION

1.2 System Configuration Equipment

Part name Model name
*1
Description Current
Remark consumption 5VDC[A]
Extension base unit *2R65B Number of I/O modules: 5 slots 0.70
R68B Number of I/O modules: 8 slots 0.81
R612B Number of I/O modules: 12 slots 0.92
R610B-HT Number of I/O modules: 10 slots, extended temperature range 0.85
Extension cable RC06B Length 0.6m(1.97ft.)
RC12B Length 1.2m(3.94ft.)
RC30B Length 3m(9.84ft.)
RC50B Length 5m(16.40ft.)
DIN rail installation adaptor
Serial absolute synchronous encoder
Serial absolute synchronous encoder cable
Connector set for serial absolute synchronous encoder cable
SSCNET cable MR-J3BUSM • R64MTCPU/R32MTCPU/R16MTCPU MR-J4(W)-B/
R6DIN1 Length 5m(16.40ft.)
Q171ENC-W8 Resolution: 4194304pulse/rev
Q170ENCCBLM-A Serial absolute synchronous encoder Q171ENC-W8 MR-J4-B-RJ
MR-J3CN2 MR-J4-B-RJ side connector
MR-J3BUSM-A • R64MTCPU/R32MTCPU/R16MTCPU MR-J4(W)-B/
MR-J3BUSM-B
For connection of R35B/R38B/R312B/R65B/R68B/R612B
Permitted axial loads Radial load: Up to 19.6N, Thrust load: Up to 9.8N Permitted speed: 3600r/min
2m(6.56ft.), 5m(16.40ft.), 10m(32.81ft.), 20m(65.62ft.), 30m(98.43ft.), 50m(164.04ft.)
Plug: 36210-0100PL Shell: 36310-3200-008 Q171ENC-W8 side connector Plug: D/MS3106B22-14S Cable clamp: D/MS3057-12A
MR-J4(W)-B MR-J4(W)-B/MR-J4(W)-B LJ72MS15
• R64MTCPU/R32MTCPU/R16MTCPU MR-J3(W)-B/ MR-J3(W)-B MR-J3(W)-B
• Standard cord for inside panel
0.15m(0.49ft.), 0.3m(0.98ft.), 0.5m(1.64ft.), 1m(3.28ft.), 3m(9.84ft.)
MR-J4(W)-B MR-J4(W)-B/MR-J4(W)-B LJ72MS15
• R64MTCPU/R32MTCPU/R16MTCPU MR-J3(W)-B/ MR-J3(W)-B MR-J3(W)-
tandard cable for outside panel
S
• 5m(16.40ft.), 10m(32.81ft.), 20m(65.62ft.)
*4
• R64MTCPU/R32MTCPU/R16MTCPU MR-J4(W)-B/ MR-J4(W)-B MR-J4(W)-B/MR-J4(W)-B LJ72MS15
• R64MTCPU/R32MTCPU/R16MTCPU MR-J3(W)-B/ MR-J3(W)-B MR-J3(W)-B
• Long distance cable 30m(98.43ft.), 40m(131.23ft.), 50m(164.04ft.)
B
0.25
*1 =Cable length
(015: 0.15m(0.49ft.), 03: 0.3m(0.98ft.), 05: 0.5m(1.64ft.), 1: 1m(3.28ft.), 2: 2m(6.56ft.), 3: 3m(9.84ft.), 5: 5m(16.40ft.), 10: 10m(32.81ft.), 20: 20m(65.62ft.), 25: 25m(82.02ft.), 30: 30m(98.43ft.), 40: 40m(131.23ft.), 50:50m(164.04ft.)
*2 5VDC internal current consumption of shared equipment with PLC might be changed. Be sure to refer to the MELSEC iQ-R series PLC
Manuals. *3 Be sure to use the power supply module within the range of power supply capacity. *4 Please contact your nearest Mitsubishi sales representative for the cable of less than 30m(98.43ft.).
1
1 SYSTEM CONFIGURATION
1.2 System Configuration Equipment
23
PLC module which can be controlled by Motion CPU
Part name Model name Description Current
consumption
*1
Remark
5VDC[A]
Input module RX10 AC input, input 16 points 0.11 Refer to the MELSEC
RX40C7 DC input, plus common/minus common shared type, input 16 points 0.11
RX41C4 DC input, plus common/minus common shared type, input 32 points 0.15
RX42C4 DC input, plus common/minus common shared type, input 64 points 0.18
RX40PC6H DC input, plus common type, input 16 points 0.10
RX40NC6H DC input, minus common type, input 16 points 0.10
RX41C6HS DC input, plus common/minus common shared type, input 32 points 0.15
RX61C6HS DC input, plus common/minus common shared type, input 32 points 0.15
Output module RY10R2 Contact output, output 16 points 0.45
RY40NT5P Transistor output, sink type, output 16 points 0.14
RY41NT2P Transistor output, sink type, output 32 points 0.18
RY41NT2H Transistor output, sink type, output 32 points 0.42
RY42NT2P Transistor output, sink type, output 64 points 0.25
RY40PT5P Transistor output, source type, output 16 points 0.13
RY41PT1P Transistor output, source type, output 32 points 0.19
RY41PT2H Transistor output, source type, output 32 points 0.41
RY42PT1P Transistor output, source type, output 64 points 0.29
Input/Output composite module
Analogue input module
Analogue output module
High-speed counter module
Temperature input module
RH42C4NT2P DC input, plus common/ minus common shared type, input 32 points,
transistor output, sink type, output 32 points
R60AD4 Voltage/current input, 4ch 0.22
R60ADV8 Voltage input, 8ch 0.23
R60ADI8 Current input, 8ch 0.22
R60AD8-G Voltage/current input, 8ch, channel isolated 0.33
R60AD16-G Voltage/current input, 16ch, channel isolated 0.52
R60DA4 Voltage/current output, 4ch 0.16
R60DAV8 Voltage output, 8ch 0.16
R60DAI8 Current output, 8ch 0.16
R60DA8-G Voltage/current output, 8ch, channel isolated 0.18
R60DA16-G Voltage/current output, 16ch, channel isolated 0.25
R60ADH4 Voltage/current output, 4ch 0.73
RD62P2 DC input, sink output type, 2ch 0.11
RD62P2E DC input, source type, 2ch 0.20
RD62D2 Differential input, sink output type, 2ch 0.17
R60TD8-G Thermocouple (B, R, S, K, E, J, T, N) input, 8ch, channel isolated 0.36
R60RD8-G RTD (Pt100, JPt100, Ni100, Pt50) input, 8ch, channel isolated 0.35
0.22
iQ-R series manuals for each module.
*1 5VDC internal current consumption of shared equipment with PLC might be changed. Be sure to refer to the manuals for each module.
24
1 SYSTEM CONFIGURATION
1.2 System Configuration Equipment
SSCNETIII(/H) compatible equipment
SSCNETIII/H compatible equipment
Part name Model name Description Remarks
MR-J4 series servo amplifier MR-J4-B Refer to the servo amplifier instruction manuals.
MR-J4-B-RJ
MR-J4-B-LL
MR-J4W-B For 2-axis type, 3-axis type
Sensing module MR-MT2010 Sensing SSCNET/H head module Refer to the sensing module instruction manuals.
MR-MT2100 Sensing I/O module
MR-MT2200 Sensing pulse I/O module
MR-MT2300 Sensing analog I/O module
MR-MT2400 Sensing encoder I/F module
SSCNET/H head module LJ72MS15 Maximum link points: Input 64 bytes,
Output 64 bytes Transmission cycle: 0.222ms,
0.444ms, 0.888ms
Optical hub unit MR-MV200 3 branches, 1 unit, 24VDC power
supply connector is attached
Refer to the MELSEC-L series PLC manuals.
SSCNETIII compatible equipment
Part name Model name Description Remarks
MR-J3 series servo amplifier MR-J3-B Refer to the servo amplifier instruction manuals.
MR-J3W-B For 2-axis type
MR-J3-B-RJ006 For fully closed control
MR-J3-B-RJ004 For linear servo motor
MR-J3-B-RJ080W For direct drive motor
MR-J3-B Safety For drive safety servo
1
1 SYSTEM CONFIGURATION
1.2 System Configuration Equipment
25
Loading...