AIR CONDITIONERS
MODEL
PWFY-P100VM-E-BU PWFY-P100VM-E-AU PWFY-P200VM-E-AU
DATA BOOK
2nd edition
•Do not use steel pipes as water pipes.
- Copper pipes are recommended.
•The water circuit should be a closed circuit.
•Ask the dealer or an authorized technician to install the air conditioner.
-Improper installation by the user may result in water leakage, electric shock, or fire.
•Install the unit in a place that can withstand its weight.
-Inadequate strength may cause the unit to fall down, resulting in injuries.
•Do not touch the unit. The unit surface can be hot.
•Do not install the unit where corrosive gas is generated.
•Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
-Inadequate connection and fastening may generate heat and cause a fire.
•Prepare for rain and other moisture and earthquakes and install the unit at the specified place.
-Improper installation may cause the unit to topple and result in injury.
•Always use an strainer and other accessories specified by Mitsubishi Electric.
-Ask an authorized technician to install the accessories. Improper installation by the user may result in water leakage, electric shock, or fire.
•Never repair the unit. If the air conditioner must be repaired, consult the dealer.
-If the unit is repaired improperly, water leakage, electric shock, or fire may result.
•Do not touch the refrigerant pipes and Water pipes.
-Improper handling may result in injury.
•When handling this product, always wear protective equipment.
EG: Gloves, full arm protection namely boiler suit, and safety glasses.
-Improper handling may result in injury.
•If refrigerant gas leaks during installation work, ventilate the room.
-If the refrigerant gas comes into contact with a flame, poisonous gases will be released.
•Install the unit according to this Installation Manual.
-If the unit is installed improperly, water leakage, electric shock, or fire may result.
•Have all electric work done by a licensed electrician according to “Electric Facility Engineering
Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
-If the power source capacity is inadequate or electric work is performed improperly, electric shock and fire may result.
•Keep the electric parts away from water (washing water etc.).
-It might result in electric shock, catching fire or smoke.
•Securely install the heat source unit terminal cover (panel).
-If the terminal cover (panel) is not installed properly, dust or water may enter the heat source unit and fire or electric shock may result.
•When installing and moving the air conditioner to another site, do not charge it with a refrigerant different from the refrigerant (R410A) specified on the unit.
-If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
•If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
-Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
•When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
-If the air conditioner is installed improperly, water leakage, electric shock, or fire may result.
- -
•After completing installation work, make sure that refrigerant gas is not leaking.
-If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or other heat source, it may generate noxious gases.
•Do not reconstruct or change the settings of the protection devices.
-If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
•To dispose of this product, consult your dealer.
•The installer and system specialist shall secure safety against leakage according to local regulation or standards.
-Following standards may be applicable if local regulation are not available.
•Pay a special attention to the place, such as a basement, etc. where refrigeration gas can stay, since refrigeration is heavier than the air.
• Do not use the existing refrigerant piping.
-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to deteriorate.
-R410A is a high-pressure refrigerant and can cause the existing piping to burst.
•Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized copper as specified in the
JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
-Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil to deteriorate.
•Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
•Apply a small amount of ester oil, ether oil, or alkyl benzene to flares. (for indoor unit)
-Infiltration of a large amount of mineral oil may cause the refrigerant oil to deteriorate.
•Use liquid refrigerant to fill the system.
-If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
• Do not use a refrigerant other than R410A.
-If another refrigerant (R22, etc.) is mixed with R410A, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
•Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
•Do not use the following tools that are used with conventional refrigerants.
(Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, refrigerant recovery equipment)
-If the conventional refrigerant and refrigerant oil are mixed in the R410A, the refrigerant may deteriorated.
-If water is mixed in the R410A, the refrigerant oil may deteriorate.
-Since R410A does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
• Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
•Do not use antioxidant or leak-detection additive.
•Be especially careful when managing the tools.
-If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
- ii -
•Do not install the unit where combustible gas may leak.
-If the gas leaks and accumulates around the unit, an explosion may result.
•Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept.
-The quality of the food, etc. may deteriorate.
•Do not use the air conditioner in special environments.
-Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
•When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
-The inverter equipment, private power generator, high-frequency medical equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
•Do not install the unit on a structure that may cause leakage.
-When the room humidity exceeds 80 % or when the drain pipe is clogged, condensation may drip from the indoor unit. Perform collective drainage work together with the unit, as required.
- iii -
• Ground the unit.
-Do not connect the ground wire to gas or water pipes, lightning rods, or telephone ground lines. Improper grounding may result in electric shock.
•Install the power cable so that tension is not applied to the cable.
-Tension may cause the cable to break and generate heat and cause a fire.
• Install a leak circuit breaker, as required.
-If a leak circuit breaker is not installed, electric shock may result.
•Use power line cables of sufficient current carrying capacity and rating.
-Cables that are too small may leak, generate heat, and cause a fire.
•Use only a circuit breaker and fuse of the specified capacity.
-A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire.
• Do not wash the air conditioner units.
-Washing them may cause an electric shock.
•Be careful that the installation base is not damaged by long use.
-If the damage is left uncorrected, the unit may fall and cause personal injury or damage property.
•Install the drain piping according to this
Installation Manual to ensure proper drainage.
Wrap thermal insulation around the pipes to prevent condensation.
-Improper drain piping may cause water leakage and damage to furniture and other possessions.
• Be very careful about product transportation.
-If the unit weighs more than 20kg, carry the unit with more than one person.
-Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
-When transporting the unit, support it at the specified positions on the unit base. Also support the unit at four points so that it cannot slip side ways.
• Safely dispose of the packing materials.
-Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
-Tear apart and throw away plastic packaging bags so that it is out of reach of children. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
- iv -
•Turn on the power at least 12 hours before starting operation.
-Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
• Do not touch the switches with wet fingers.
-Touching a switch with wet fingers can cause electric shock.
•Do not touch the refrigerant pipes during and immediately after operation.
-During and immediately after operation, the refrigerant pipes are may be hot and may be cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
•Do not operate the air conditioner with the panels and guards removed.
-Rotating, hot, or high-voltage parts can cause injuries.
•Do not turn off the power immediately after stopping operation.
-Always wait at least five minutes before turning off the power. Otherwise, water leakage and trouble may occur.
•Do not touch the surface of the compressor during servicing.
-If unit is connected to the supply and not running, crank case heater at compressor is operating.
•Do not touch the panels near the fan outlet with bare hands: they can get hot while the unit is in operation (even if it is stopped) or immediately after operation to prevent burns. Wear gloves to protect your hands when it is necessary to touch the panels.
•While the unit is in operation or immediately after operation, high-temperature exhaust air may blow out of the fan exhaust outlet. Do not hold your hands over the outlet or touch the panels near the outlet.
•Be sure to provide a pathway for the exhaust air from the fan.
•Water pipes can get very hot, depending on the preset temperature. Wrap the water pipes with insulating materials to prevent burns.
--
Contents
Safety Precautions
I General Equipment Descriptions
1.Unit configuration table············································ 1
2.Operable temperature range···································· 1
3.Connectable outdoor unit/heat source unit
capacity range·························································· 1
IIProduct Specifications
1.Specifications··························································· 2
(1)PWFY-P100VM-E-BU
(2)PWFY-P100VM-E-AU
(3)PWFY-P200VM-E-AU
(4)CMB-P104V-G
(5)CMB-PW202V-J
2.External Dimensions················································ 6
(1)PWFY-P100VM-E-BU
(2)PWFY-P100, 200VM-E-AU
(3)CMB-P104,105,106,108,1010,1013,1016V-G
(4)CMB-PW202V-J
3.Electrical Wiring Diagrams····································· 10
(1)PWFY-P100VM-E-BU
(2)PWFY-P100, 200VM-E-AU
(3)CMB-P104V-G
(4)CMB-PW202V-J
4.Accessories···························································· 14
(1)PWFY
(2)CMB-P104V-G
(3)CMB-PW202V-J
IIIProduct Data
1.Capacity tables······················································· 15
(1)Correction by temperature
(2)Correction by water flow rate
(3)Correction by total indoor
(4)Correction by refrigerant piping length
(5)Correction at frosting and defrosting
(6)Water pressure drop
(7)Operation temperature range
2.Sound pressure levels············································ 41
(1)PWFY-P100VM-E-BU
(2)PWFY-P100, 200VM-E-AU
3.Vibration levels······················································· 42
(1)PWFY-P100VM-E-BU
4.Refrigerant circuit diagrams and
thermal sensors······················································ 43
(1)PWFY-P100VM-E-BU
(2)PWFY-P100VM-E-AU
(3)PWFY-P200VM-E-AU
IV Installation
1.How to calculate the necessary heating capacity·· 44
(1)Heating capacity calculation
(2)Calculation example
2.Installation······························································ 45
(1)Selecting an installation site
(2)Installing the unit
(3)Refrigerant pipe and drain pipe specifications
(4)Connecting refrigerant pipes and drain pipes
3.Water pipe installation············································ 51
(1)Water circuit sample
(2)Selecting a water pump
(3)Installing the strainer
(4)Precautions during installation
(5)Example of unit installation
(6)Insulation installation
(7)Water processing and water quality control
(8)Pump interlock
(9)Anti freeze mode
V System Design
1.Electrical work························································ 56
(1)General cautions
(2)Power supply for PWFY unit
(3)Connecting remote controller,
indoor and outdoor transmission cables
(4)Transmission cable specifications
(5)Connecting electrical connections
(6)Indoor unit address setting
(7)External input/output function
(8)BC controller piping design
(9)WCB piping design
VI Controller
1.PAR-W21MAA specifications································· 67
2.Dip switch functions··············································· 68
VII Maintenance Cycle
1.Routine maintenance checks································· 69
2.Parts Replacement Cycle······································· 69
VIII Product Data (additional
information for chapter III.)
1.Outdoor unit capacity tables··································· 70
(1)Correction by total indoor
(2)Correction by refrigerant piping length
(3)Correction at frosting and defrosting
|
I |
|
General Equipment Descriptions |
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
||||||||||||||
1. Unit configuration table |
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
Model |
|
|
|
|
|
|
PWFY-P100VM-E-BU |
|
|
PWFY-P100VM-E-AU |
|
PWFY-P200VM-E-AU |
||||||
|
Outdoor unit |
PURY-(E)P•Y(S)HM-A(-BS) / PQRY-P•Y(S)HM-A |
|
PUHY-(E)/(H)P•Y(S)HM-A(-BS) / PQHY-P•(S)HM-A |
|||||||||||||||
|
|
PURY-(E)P•Y(S)HM-A(-BS) / PQRY-P•Y(S)HM-A |
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
BC controller |
|
|
BC controller: CMB-P104,105,106,108,1010,1013,1016V-G |
|||||||||||
|
Connection |
|
|
Main BC controller: CMB-P108,1010,1013,1016V-GA / CMB-P1016V-HA |
|||||||||||||||
|
|
|
|
|
|
|
Sub BC controller: CMB-P104,108V-GB / CMB-P1016V-HB |
||||||||||||
|
|
|
|
|
WCB |
|
|
|
|
|
|
CMB-PW202V-J |
|
|
|
||||
2. Operable temperature range |
|
|
|
|
|
|
|
|
|
||||||||||
|
<PWFY-P100VM-E-BU> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
Only PWFY |
|
|
PWFY with |
|
Only standard |
|
|
||
|
|
|
|
|
|
|
|
|
|
standard indoor unit |
|
indoor units |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
|
|
|
|
|
|
|
Inlet water temperature |
R2/WR2 series |
|
10 to 70ºC |
|
|
10 to 70ºC |
|
― |
|
|
|
|||||||
|
Outdoor temperature |
R2 series |
|
-20 to 32ºCWB |
|
-20 to 32ºCWB |
|
-20 to 15.5ºCWB |
|
|
|||||||||
|
Circulating water temperature |
WR2 series |
|
10 to 45ºC |
|
|
10 to 45ºC |
|
10 to 45ºC |
|
|
|
|||||||
|
<PWFY-P100,200VM-E-AU> |
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
Only PWFY |
|
PWFY with standard indoor units |
|
||||||
|
|
|
|
|
|
|
|
|
|
Cooling |
|
|
Heating |
|
Cooling |
|
Heating |
|
|
|
Inlet water temperature |
R2/WR2 series |
|
10 to 35ºC |
|
|
10 to 40ºC |
|
10 to 35ºC |
|
10 to 40ºC |
|
|||||||
|
Y/HP/WY series |
10 to 35ºC |
|
|
10 to 40ºC |
|
10 to 35ºC |
|
10 to 40ºC |
|
|||||||||
|
|
|
|
|
|
|
R2 series |
|
-5 to 43ºCDB |
|
-20 to 32ºCWB |
|
-5 to 43ºCDB |
-20 to 32ºCWB |
|
||||
|
Outdoor temperature |
Y series |
|
-5 to 43ºCDB |
-20 to 15.5ºCWB |
|
-5 to 43ºCDB |
-20 to 15.5ºCWB |
|
||||||||||
|
|
|
|
|
|
|
HP series |
|
-5 to 43ºCDB |
-25 to 15.5ºCWB |
|
-5 to 43ºCDB |
-25 to 15.5ºCWB |
|
|||||
|
Circulating water |
WR2 series |
|
10 to 45ºC |
|
|
10 to 45ºC |
|
10 to 45ºC |
|
10 to 45ºC |
|
|||||||
|
temperature |
|
|
|
WYseries |
|
10 to 45ºC |
|
|
10 to 45ºC |
|
10 to 45ºC |
|
10 to 45ºC |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
Only standard indoor units |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
Cooling |
|
|
Heating |
|
|
|
|
|
|
|
|
|
|
|
|
|
R2 series |
|
-5 to 43ºCDB |
-20 to 15.5ºCWB |
|
|
|
|
|
|
|||
|
Outdoor temperature |
Y series |
|
-5 to 43ºCDB |
-20 to 15.5ºCWB |
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
HP series |
|
-5 to 43ºCDB |
-25 to 15.5ºCWB |
|
|
|
|
|
|
|||
|
Circulating water |
WR2 series |
|
10 to 45ºC |
|
|
10 to 45ºC |
|
|
|
|
|
|
||||||
|
temperature |
|
|
|
WYseries |
|
10 to 45ºC |
|
|
10 to 45ºC |
|
|
|
|
|
|
|||
3. Connectable outdoor unit/heat source unit capacity range |
|
|
|
||||||||||||||||
|
<PWFY-P100VM-E-BU> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
Only PWFY |
|
|
PWFY with |
|
Only standard |
|
|
||
|
|
|
|
|
|
|
|
|
|
standard indoor unit |
|
indoor units |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
R2/WR2 series |
|
50 to 100% |
|
50 to 150%*1 |
|
50 to 150%*1 |
|
|
*1 In case of WCB connection, the capacity range will be "50 to 130%".
<PWFY-P100,200VM-E-AU>
|
Only PWFY |
PWFY with |
Only standard |
|
|
standard indoor unit |
indoor units |
||
|
|
|
||
R2/WR2 series |
50 |
to 100% |
50 to 150%*1 |
50 to 150%*1 |
Y/HP/WY series |
50 |
to 100% |
50 to 130% |
50 to 130% |
*1 In case of WCB connection, the capacity range will be "50 to 130%".
<BC controller>
|
Connectable unit |
|
CMB-P104/P105/106/107/1010/ |
PURY-(E)P200-350YHM-A(-BS) |
|
1013/1016V-G |
PQRY-P200-300YHM-A |
|
CMB-P108/1010/1013/1016V-GA |
PURY-(E)P200-650Y(S)HM-A(-BS) |
|
PQRY-P200-600Y(S)HM-A |
||
|
||
CMB-P1016V-HA |
PURY-P700-800YSHM-A(-BS) |
|
CMB-P104/108V-GB, CMB-P1016V-HB |
CMB-P108/1010/1013/1016V-GA, CMB-P1016V-HA |
|
<WCB> |
|
|
|
Connectable unit |
|
CMB-PW202V-J |
PURY-(E)P200-350YHM-A(BS) |
|
PQRY-P200-300YHM-A |
||
|
--
IIProduct Specifications
1.Specifications
(1) PWFY-P100VM-E-BU
Model |
|
|
|
|
|
PWFY-P100VM-E-BU |
|
|
||
|
|
|
|
|
|
|
|
|||
Power source |
|
|
|
|
|
1-phase 220-230-240V 50/60Hz |
|
|||
Heating capacity |
*1 |
kW |
|
|
12.5 |
|
|
|
||
(Nominal ) |
|
*1 |
kcal / h |
|
|
10,800 |
|
|
|
|
|
|
*1 |
BTU / h |
|
|
42,700 |
|
|
|
|
|
|
Power input |
kW |
|
|
2.48 |
|
|
|
|
|
|
Current input |
A |
|
|
11.63 - 11.12 - 10.66 |
|
|
|
|
Temp. range of |
|
Outdoor temp. |
W.B |
|
|
-20~32°C (-4~90°F) PURY-series |
|
|||
heating |
|
Circulating Water temp. |
- |
|
|
10~45°C (50~113°F) PQRY-series |
|
|||
|
|
Inlet Water temp. |
- |
|
|
10~70°C (50~158°F) |
|
|
||
Connectable |
|
Total capacity |
|
|
|
50~100% of outdoor unit/heat source unit capacity |
||||
outdoor unit |
|
Model / Quantity |
|
|
|
PURY-(E)P • Y(S)HM-A(-BS) |
|
|||
/heat source unit |
|
|
|
|
PQRY-P • Y(S)HM-A |
|
|
|||
Sound pressure level (measured |
in anechoic room) |
dB<A> |
|
|
44 |
|
|
|
||
Diameter of |
|
Liquid |
mm(in.) |
|
|
Φ9.52 (Φ3/8") Brazed |
|
|
||
refrigerant pipe |
|
Gas |
mm(in.) |
|
|
Φ15.88 (Φ5/8") Brazed |
|
|
||
Diameter of |
|
Inlet |
mm(in.) |
|
|
PT3/4 |
Screw |
|
|
|
water pipe |
|
Outlet |
mm(in.) |
|
|
PT3/4 |
Screw |
|
|
|
Field drain pipe size |
|
mm(in.) |
|
|
Φ32 (1-1/4'') |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
External finish |
|
|
|
|
|
NO |
|
|
||
External dimension H × W × D |
|
mm |
|
|
800 (785 without legs) × 450 × 300 |
|
||||
|
|
|
in. |
|
|
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16” |
||||
Net weight |
|
|
kg(lb) |
|
|
60 (133) |
|
|
|
|
Compressor |
|
Type |
|
|
|
Inverter rotary hermetic compressor |
|
|||
|
|
Maker |
|
|
|
MITSUBISHI ELECTRIC CORPORATION |
||||
|
|
Starting method |
|
|
|
Inverter |
|
|
||
|
|
Motor output |
kW |
|
|
1.0 |
|
|
|
|
|
|
Lubricant |
|
|
|
NEO22 |
|
|
||
Circulating water |
Operation volume |
m3/h |
|
|
0.6~2.15 |
|
|
|
||
|
|
Range |
|
|
|
|
|
|||
Protection on Internal circuit |
High pressure protection |
|
|
|
High pressure sensor, High pressure switch at 3.60 MPa (601 psi) |
|||||
(R134a) |
|
Inverter circuit (COMP) |
|
|
|
Over-heat protection, Over-current protection |
||||
|
|
Compressor |
|
|
|
Discharge thermo protection, Over-current protection |
||||
Refrigerant |
|
Type × original charge |
|
|
|
R134a × 1.1kg (0.50lb) |
|
|
||
|
|
Control |
|
|
|
LEV |
|
|
||
Design pressure |
R410a |
MPa |
|
|
4.15 |
|
|
|
||
|
|
R134a |
MPa |
|
|
3.60 |
|
|
|
|
|
|
Water |
MPa |
|
|
1.00 |
|
|
|
|
Drawing |
|
External |
|
|
|
WKB94L762 |
|
|
||
|
|
Wiring |
|
|
|
E64C226X01 |
|
|
||
Standard attachment |
Document |
|
|
|
Installation Manual, Instruction Book |
|
||||
|
|
Accessory |
|
|
|
Strainer, Heat insulation material, 2 × Connector sets |
||||
Optional parts |
|
|
|
|
|
NONE |
|
|
||
|
|
|
|
|
|
|||||
Remark |
|
|
|
|
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and |
|||||
|
|
|
|
|
other items shall be referred to the Installation Manual. |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
Note: |
*1 Nominal heating conditions |
|
|
|
|
|
|
|
Unit converter |
|
|
<PURY-series> |
|
|
<PQRY-series> |
|
|
|
kcal |
= kW × 860 |
|
|
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB) |
Circulating water Temp. : 20°C (68°F) |
|
|
BTU/h = kW × 3,412 |
|||||
|
Pipe length : 7.5 m (24-9/16 ft) |
|
Pipe length : 7.5 m (24-9/16 ft) |
|
|
|||||
|
|
|
|
cfm |
= m3/min x 35.31 |
|||||
|
Level difference : 0m (0ft) |
|
Level difference : 0m (0ft) |
|
|
|
lb |
= kg / 0.4536 |
||
|
Inlet water Temp 65°C Water flow rate 2.15m3/h |
Inlet water Temp 65°C |
Water flow rate 2.15m3/h |
|
|
|||||
|
|
|
|
|
||||||
* Due to continuing improvement, the above specifications may be subject to change without notice. |
* Install the unit in an environment where the |
|
* The specification data is subject |
|||||||
* The unit is not designed for outside installations. |
|
|
|
wet bulb Temp. will not exceed 32degC. |
|
to rounding variation. |
||||
* Please don't use the steel material for the water piping material. |
|
|
|
* The water circuit must use the closed circuit. |
|
|
|
|||
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less. |
|
|
|
|
||||||
* Please always make water circulate or pull out the circulation water completely when not using it. |
* Please do not use it as a drinking water. |
|
|
|
||||||
* Please do not use groundwater and well water. |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
--
(2) PWFY-P100VM-E-AU
Model |
|
|
Power source |
|
|
Heating capacity |
*1 |
kW |
(Nominal) |
*1 |
kcal / h |
|
*1 |
BTU / h |
|
Power input |
kW |
|
Current input |
A |
Temp. range of |
Outdoor temp. |
W.B |
heating |
|
W.B |
|
Circulating Water temp. |
- |
|
|
- |
|
Inlet Water temp. |
- |
Cooling capacity |
*2 |
kW |
(Nominal) |
*2 |
kcal / h |
|
*2 |
BTU / h |
|
Power input |
kW |
|
Current input |
A |
Temp. range of cooling |
Outdoor temp. |
D.B |
|
|
D.B |
|
Circulating Water temp. |
- |
|
|
- |
Connectable |
Inlet Water temp. |
- |
Total capacity |
|
|
outdoor unit |
Model / Quantity |
|
/heat source unit |
|
|
Sound pressure level (measured in anechoic room)
Diameter of |
Liquid |
refrigerant pipe |
Gas |
Diameter of |
Inlet |
water pipe |
Outlet |
Field drain pipe size |
|
External finish |
|
External dimension H × W × D |
|
Net weight |
|
Circulating water |
Operation Volume |
|
Range |
Design pressure |
R410a |
|
Water |
Drawing |
External |
|
Wiring |
Standard attachment |
Document |
|
Accessory |
Optional parts |
|
dB<A>
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm in. kg(lb)
m3/h
MPa
MPa
PWFY-P100VM-E-AU 1-phase 220-230-240V 50/60Hz
12.5
10,800
42,700
0.015
0.068 - 0.065 - 0.063 -20~32°C (-4~90°F) PURY - series -20~15.5°C (-4~60°F) PUHY - series
10~45°C (50~113°F) PQRY - series 10~45°C (50~113°F) PQHY - series 10~40°C (50~104°F)
11.2
9,600
38,200
0.015
0.068 - 0.065 - 0.063 -5~43°C (23~110°F) PURY - series -5~43°C (23~110°F) PUHY - series
10~45°C (50~113°F) PQRY - series
10~45°C (50~113°F) PQHY - series 10~35°C (50~95°F)
50~100% of outdoor unit/heat source unit capacity
PUHY-(E)/(H)P • Y(S)HM-A(-BS)
PQHY-P • Y(S)HM-A
PURY-(E)P • Y(S)HM-A(-BS)
PQRY-P • Y(S)HM-A 29
Φ9.52 (Φ3/8") Brazed
Φ15.88 (Φ5/8") Brazed
PT3/4 Screw
PT3/4 Screw Φ32 (1-1/4'')
NO
800 (785 without legs) × 450 × 300
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16” 35 (78)
0.6~2.15
4.15
1.00
WKB94L763
E00C223
Installation Manual, Instruction Book Strainer, Heat insulation material, 2 × Connector sets
NONE
Remark |
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and |
|
other items shall be referred to the Installation Manual. |
Note: |
*1 Nominal heating conditions |
|
|
|
|
<PUHY/PURY-series> |
|
<PQHY/PQRY-series> |
|
|
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB) |
Circulating water Temp. : 20°C (68°F) |
||
|
Pipe length : 7.5 m (24-9/16 ft) |
Pipe length : 7.5 m (24-9/16 ft) |
||
|
Level difference : 0m (0ft) |
|
Level difference : 0m (0ft) |
|
|
Inlet water Temp 30°C |
Water flow rate 2.15m3/h |
Inlet water Temp 30°C |
Water flow rate 2.15m3/h |
|
*2 Nominal cooling conditions |
|
|
|
|
<PUHY/PURY-series> |
|
<PQHY/PQRY-series> |
|
|
Outdoor Temp. : 35°CB (95°FDB) |
Circulating water Temp. : 30°C (86°F) |
||
|
Pipe length : 7.5 m (24-9/16 ft) |
Pipe length : 7.5 m (24-9/16 ft) |
||
|
Level difference : 0m (0ft) |
|
Level difference : 0m (0ft) |
|
|
Inlet water Temp 23°C |
Water flow rate 1.93m3/h |
Inlet water Temp 23°C |
Water flow rate 1.93m3/h |
* Due to continuing improvement, the above specifications may be subject to change without notice. |
* Install the unit in an environment where the |
|
* The unit is not designed for outside installations. |
|
wet bulb Temp. will not exceed 32degC. |
* Please don't use the steel material for the water piping material. |
* The water circuit must use the closed circuit. |
|
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less. |
||
* Please always make water circulate or pull out the circulation water completely when not using it. |
* Please do not use it as a drinking water. |
|
* Please do not use groundwater and well water. |
|
|
|
|
Unit converter |
kcal |
= |
kW × 860 |
BTU/h= |
kW × 3,412 |
|
cfm |
= |
m3/min × 35.31 |
lb |
= |
kg / 0.4536 |
*The specification data is subject to rounding variation.
--
(3) PWFY-P200VM-E-AU
Model |
|
|
PWFY-P200VM-E-AU |
Power source |
|
|
1-phase 220-230-240V 50/60Hz |
Heating capacity |
*1 |
kW |
25.0 |
(Nominal) |
*1 |
kcal / h |
21,500 |
|
*1 |
BTU / h |
85,300 |
|
Power input |
kW |
0.015 |
|
Current input |
A |
0.068 - 0.065 - 0.063 |
Temp. range of |
Outdoor temp. |
W.B |
-20~32°C (-4~90°F) PURY - series |
heating |
|
W.B |
-20~15.5°C (-4~60°F) PUHY - series |
|
Circulating Water temp. |
- |
10~45°C (50~113°F) PQRY - series |
|
|
- |
10~45°C (50~113°F) PQHY - series |
|
Inlet Water temp. |
- |
10~40°C (50~104°F) |
Cooling capacity |
*2 |
kW |
22.4 |
(Nominal) |
*2 |
kcal / h |
19,300 |
|
*2 |
BTU / h |
76,400 |
|
Power input |
kW |
0.015 |
|
Current input |
A |
0.068 - 0.065 - 0.063 |
Temp. range of cooling |
Outdoor temp. |
D.B |
-5~43°C (23~110°F) PURY - series |
|
|
D.B |
-5~43°C (23~110°F) PUHY - series |
|
Circulating Water temp. |
- |
10~45°C (50~113°F) PQRY - series |
|
|
- |
10~45°C (50~113°F) PQHY - series |
|
Inlet Water temp. |
- |
10~35°C (50~95°F) |
Connectable |
Total capacity |
|
50~100% of outdoor unit/heat source unit capacity |
outdoor unit |
Model / Quantity |
|
PUHY-(E)/(H)P • Y(S)HM-A(-BS) |
/heat source unit |
|
|
PQHY-P • Y(S)HM-A |
|
|
|
PURY-(E)P • Y(S)HM-A(-BS) |
|
|
|
PQRY-P • Y(S)HM-A |
Sound pressure level (measured in anechoic room) |
dB<A> |
29 |
|
Diameter of |
Liquid |
mm(in.) |
Φ9.52 (Φ3/8") Brazed |
refrigerant pipe |
Gas |
mm(in.) |
Φ19.05 (Φ3/4") Brazed |
Diameter of |
Inlet |
mm(in.) |
PT 1 Screw |
water pipe |
Outlet |
mm(in.) |
PT 1 Screw |
Field drain pipe size |
|
mm(in.) |
Φ32 (1-1/4'') |
External finish |
|
|
NO |
External dimension H × W × D |
|
mm |
800 (785 without legs) × 450 × 300 |
|
|
in. |
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16” |
Net weight |
|
kg(lb) |
38 (84) |
Circulating water |
Operation Volume |
m3/h |
1.2~4.30 |
|
Range |
||
|
|
4.15 |
|
Design pressure |
R410a |
MPa |
|
|
Water |
MPa |
1.00 |
Drawing |
External |
|
WKB94L763 |
|
Wiring |
|
E94C228X01 |
Standard attachment |
Document |
|
Installation Manual, Instruction Book |
|
Accessory |
|
Strainer, Connecter, Heat insulation material, 2 × Connector sets, Expansion joint |
Optional parts |
|
|
NONE |
Remark |
|
|
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and |
|
|
|
other items shall be referred to the Installation Manual. |
Note: |
*1 Nominal heating conditions |
|
|
|
|
<PUHY/PURY-series> |
|
<PQHY/PQRY-series> |
|
|
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB) |
Circulating water Temp. : 20°C (68°F) |
||
|
Pipe length : 7.5 m (24-9/16 ft) |
Pipe length : 7.5 m (24-9/16 ft) |
||
|
Level difference : 0m (0ft) |
|
Level difference : 0m (0ft) |
|
|
Inlet water Temp 30°C |
Water flow rate 4.30m3/h |
Inlet water Temp 30°C |
Water flow rate 4.30m3/h |
|
*2 Nominal cooling conditions |
|
|
|
|
<PUHY/PURY-series> |
|
<PQHY/PQRY-series> |
|
|
Outdoor Temp. : 35°CDB (95°FDB) |
Circulating water Temp. : 30°C (86°F) |
||
|
Pipe length : 7.5 m (24-9/16 ft) |
Pipe length : 7.5 m (24-9/16 ft) |
||
|
Level difference : 0m (0ft) |
|
Level difference : 0m (0ft) |
|
|
Inlet water Temp 23°C |
Water flow rate 3.86m3/h |
Inlet water Temp 23°C |
Water flow rate 3.86m3/h |
|
|
Unit converter |
kcal |
= |
kW × 860 |
BTU/h= |
kW × 3,412 |
|
cfm |
= |
m3/min × 35.31 |
lb |
= |
kg / 0.4536 |
*The specification data is subject to rounding variation.
* Due to continuing improvement, the above specifications may be subject to change without notice. |
* Install the unit in an environment where the |
|
* The unit is not designed for outside installations. |
|
wet bulb Temp. will not exceed 32degC. |
* Please don't use the steel material for the water piping material. |
* The water circuit must use the closed circuit. |
|
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less. |
||
* Please always make water circulate or pull out the circulation water completely when not using it. |
* Please do not use it as a drinking water. |
|
* Please do not use groundwater and well water. |
|
|
--
(4) CMB-P104V-G
Model
Number of branch
Power source
Power input |
|
|
kW |
Current |
|
|
A |
External finish |
|
|
|
Connectable outdoor unit/heat source unit |
|
||
Indoor unit capacity connectable to 1 branch |
kW |
||
External dimension H x W x D |
|
mm(in.) |
|
Refrigerant |
To |
|
|
piping |
outdoor unit |
|
|
diameter |
/heat source |
High press. pipe |
mm(in.) |
|
unit |
Low press. pipe |
mm(in.) |
|
To |
Liquid pipe |
mm(in.) |
|
indoor |
|
mm(in.) |
|
unit |
Gas pipe |
|
Field drain pipe size |
|
|
|
Net weight |
|
|
kg(lb) |
Accessories
*Other models of BC controller are available. For unit information, refer to the Data Book.
|
CMB-P104V-G |
|
4 |
|
1N ~ 220/230/240V |
50Hz |
60Hz |
Cooling : 0.067/0.076/0.085 |
Cooling : 0.054/0.061/0.067 |
Heating : 0.030/0.034/0.038 |
Heating : 0.024/0.027/0.030 |
Cooling : 0.31/0.34/0.36 |
Cooling : 0.25/0.27/0.28 |
Heating : 0.14/0.15/0.16 |
Heating : 0.11/0.12/0.13 |
Galvanized steel plate (Lower part drain pan painting N1.5)
PURY-(E)P200/250/300/350YHM-A(-BS) / PQRY-P200/250/300YHM-A
Model P80 or smaller
(Use optional joint pipe combining 2 branches when the total capacity exceeds 81.) (Use the reducer (standard accessory) when the indoor unit Model 50 or smaller is connected.)
284 x 648 x 432 (11-3/16 x 25-9/16 x 17-1/16) Connectable outdoor unit capacity
P200 |
P250/P300 |
P350 |
ø15.88 (ø5/8) Brazed |
ø19.05 (ø3/4) Brazed |
ø19.05 (ø3/4) Brazed |
ø19.05 (ø3/4) Brazed |
ø22.2 (ø7/8) Brazed |
ø28.58 (ø1-1/8) Brazed |
ø9.52 (ø3/8) Flare
(ø6.35 (ø1/4) with attached reducer used, ø12.7 (ø1/2) with optional joint pipe used.)
ø15.88 (ø5/8) Flare
(ø12.7 (ø1/2) with attached reducer used, ø19.05 (ø3/4) with optional joint pipe used.) O.D. 32mm (1-1/4)
24 (53) 27 (60)
·Drain Connection pipe (with flexible hose and insulation) ·Reducer
Note: *1. Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items shall be referred to the Installation Manual. *2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away from any indoor units.) *4. Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)
(5) CMB-PW202V-J
Model |
|
|
CMB-PW202V-J |
Number of branch |
|
|
2 |
Power source |
|
|
1N ~ 220/230/240V |
|
kW |
50Hz |
60Hz |
Power input |
Cooling : 0.019/0.020/0.021 |
Cooling : 0.018/0.019/0.019 |
|
|
|
Heating : 0.020/0.022/0.024 |
Heating : 0.019/0.020/0.021 |
Current |
A |
Cooling : 0.09/0.09/0.09 |
Cooling : 0.09/0.09/0.09 |
|
|
Heating : 0.10/0.10/0.10 |
Heating : 0.09/0.09/0.09 |
External finish |
|
|
|
Connectable outdoor unit |
|
|
|
Connectable unit capacity |
|
Total |
|
|
|
|
Indoor / PWFY |
|
|
|
branch |
External dimension H x W x D |
|
PWFY branch |
|
|
mm(in.) |
||
Refrigerant |
To |
|
|
piping |
outdoor unit |
|
|
diameter |
/heat source |
High press. pipe |
mm(in.) |
|
unit |
Low press. pipe |
mm(in.) |
|
To |
|
|
|
indoor/ |
|
mm(in.) |
|
PWFY unit |
Liquid pipe |
|
|
|
Gas pipe |
mm(in.) |
|
|
|
|
Field drain pipe size |
|
|
|
Net weight |
|
|
kg(lb) |
Accessories
Galvanized steel plate (Lower part drain pan painting N1.5)
PURY-(E)P200/250/300/350YHM-A (-BS)
PQRY-P200/250/300YHM-A
50% ~ 130% of outdoor unit/heat source unit
|
up to 130% of outdoor unit/heat source unit |
|
||
|
up to 100% of outdoor unit/heat source unit |
|
||
|
284 x 648 x 432 (11-3/16" x 25-9/16" x 17-1/16" ) |
|
||
|
Connectable outdoor unit capacity |
|
||
P200 |
|
P250/P300 |
|
P350 |
ø15.88 (ø5/8" ) Brazed |
ø19.05 (ø3/4" ) Brazed |
ø19.05 (ø3/4" ) Brazed |
||
ø19.05 (ø3/4" ) Brazed |
ø22.2 (ø7/8" ) Brazed |
ø28.58 (ø1-1/8" ) Brazed |
||
|
Total down-stream Indoor unit capacity |
|
||
~P140 |
P141~P200 |
P201~P300 |
P301~P400 |
P401~ |
ø9.52 (ø3/8" ) |
ø9.52 (ø3/8" ) |
ø9.52 (ø3/8" ) |
ø12.70 (ø1/2" ) |
ø15.88 (ø5/8" ) |
Brazed |
Brazed |
Brazed |
Brazed |
Brazed |
ø15.88 (ø5/8" ) |
ø19.05 (ø3/4" ) |
ø22.2 (ø7/8" ) |
ø28.58 (ø1-1/8" ) |
ø28.58 (ø1-1/8" ) |
Brazed |
Brazed |
Brazed |
Brazed |
Brazed |
|
|
O.D. 32mm (1-1/4" ) |
|
|
|
|
20 (45) |
|
|
·Drain Connection pipe (with flexible hose and insulation) ·Refrigerant connection pipe
Note: *1. For installation/foundation work, electrical connection work, insulation work, and power source switch etc., refer to the Installation Manual. *2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the Water system Connection Box at least 5m away from any indoor units.) *4. Install the unit horizontally.
*5. The indoor / PWFY unit branch is for cooling / heating. The indoor / PWFY unit cannot be simultaneously operated in different operation modes. *6. The PWFY unit branch is for the heating only.
*7. Seal the unused branch using the optional cover cap (CMY-S202-J).
--
Control box
- -
ceServ panel
450
500
(Mounting pitch)
525
Top vew
Front ewv
205 (Mounting pitch) 300
2X2-ø14 Hole
<Accessories>
●Y-type nerstra (RC3/4) ·························· 1pc. ●Heat Insulation material ························· 1pc. ●Connector set ········································ 2set
Note 1.Ensure no ran water or debrs can enter the unt through any gaps around wrng or p.png
2.Ensure adequate ceserv space s ghtr around the t,un ngaccord to gF A. 3.Please always make water rculatec or add the nebr to the onrculatc water
when the ambent temperature becomes 0°C or less. 4.The unt s not desgned for outsde nstallatons.
5.Install the tun n an ronmentenv where the wet bulb Temp. llw not exceed 32degC.
6.Please always make water crculate or pull out the crculaton water completely when not usng t.
7.The water trcuc must use the closed trcuc.
8.Please don't use the steel materal for the water ppng mater.al 9.Connect the straner whch s put as accessory to water nlet p.pe
35 |
|
|
|
|
|
|
46 |
91 |
800 |
60 |
134 |
|
480 |
|
|
|
140 |
|
|
91 |
|
|
100 |
|
|
80 |
|
|
102 |
165 |
191 54 |
35 |
114 |
55 |
184 |
ø27 Knockout hole |
Rght sde vew |
<Hole for control wiring> |
Water outlet (RC3/4 screw)
ø27 Knockout hole
<Hole for external wiring input>
ø27 Knockout hole
<Hole for external wiring output>
Connecton ppe of outdoor unt
(Gas)
ø15.88 <Brazed>
ø27 Knockout hole
<Hole for power supply>
Connecton ppe of outdoor unt (Lqud)
ø9.52 <Brazed>
Water nlet (R3/4 screw)
nDra (R1 screw)
Ppng space |
400 |
|
(rght sde) |
|
|
Top ewv |
|
300 |
ceServ space |
600 |
|
(front de)s |
gF. A
<Unit:mm>
Dimensions External .2 BU-E-P100VM-PWFY (1)
450
500 (Mounting pitch)
525
Top vew
Control box
- -
ceServ panel
Front ewv
205 (Mounting pitch) 300
2X2-ø14 Hole
<Accessories>
●Y-type straner (RC3/4) ····························· 1pc. ●Heat Insulation material ···························· 1pc. ●Connector set ············································ 2set ●Expansion joint (P200) ······························ 2pcs.
[From RC3/4 to RC1]
Note 1.Ensure no ran water or debrs can enter the unt through any gaps around wrng or p.png
2.Ensure adequate ceserv space s ghtr around the t,un ngaccord to gF A. 3.Please always make water rculatec or add the nebr to the onrculatc water
when the ambent temperature becomes 0°C or less. 4.The unt s not desgned for outsde nstallatons.
5.Install the tun n an ronmentenv where the wet bulb Temp. llw not exceed 32degC.
6.Please always make water crculate or pull out the crculaton water completely when not usng t.
7.The water trcuc must use the closed trcuc.
8.Please don't use the steel materal for the water ppng mater.al 9.Connect the straner whch s put as accessory to water nlet p.pe
35 |
|
|
|
|
|
|
|
|
46 |
91 |
800 |
60 |
|
|
|
480 |
|
|
134 |
|
140 |
|
|
|
91 |
|
|
100 |
|
|
|
80 |
|
|
|
102 |
165 |
191 |
54 |
35 |
114 |
55 |
206 |
ø27 Knockout hole |
Rght sde vew |
<Hole for control wiring> |
Water outlet (RC3/4 screw)
P200:Use the Expansion joint of accessores
ø27 Knockout hole
<Hole for external wiring input>
ø27 Knockout hole
<Hole for external wrng output>
onConnect pep of outdoor tun
(Gas)
P100:ø15.88 <Brazed>
P200:ø19.05 <Brazed>
ø27 Knockout hole
<Hole for power supply>
Connecton ppe of outdoor unt (Lqud)
ø9.52 <Brazed>
Water nlet (R3/4 screw)
nDra (R1 screw)
Ppng space |
400 |
|
(rght sde) |
|
|
Top ewv |
|
300 |
ceServ space |
600 |
|
(front de)s |
gF. A
<Unit:mm>
AU-E-200VM P100,-PWFY (2)
- -
Drain pipe O.D. 32 (1-1/4")
181
64
Band (Accessory) Drain hose I.D. 32 (1-1/4")
ø31
Detail of X section
Connection pipe of outdoor unit
(High pressure) ø19.05 <Brazed>
Y
X
64 103 248
30 |
12 |
14
Detail of Y section
Control box
|
|
130 |
23 |
|
|
Connection pipe of outdoor unit (Low pressure) |
|||||
PURY-P200 |
: ø19.05 <Brazed> (use attachment pipe) |
||||
PURY-P250, P300 : ø22.2 |
<Brazed> |
|
|
||
PURY-P350 |
: ø28.6 |
<Brazed> (use attachment pipe) |
|||
|
|
|
|
|
27 |
|
|
|
|
128 |
58 |
|
|
|
284 |
255 |
|
200
|
|
|
|
|
|
|
|
A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
B |
|
|
|
|
|
|
|
|
|
|
|
|
|
(Lifting bolt pitch) |
|
|
|
|
|
||||
70 76 |
|
|
|
|
|
|
60XC=D |
|
|
|
|
|
|
|
|
|
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
14 |
15 |
16 |
<Accessories>
•Refrigerant<Low pressure> conn. pipe ··············· 2pcs.
•Refrigerant<High pressure> conn. pipe ·············· 1pc.
•Reducer(Large,Small) ········································· Quantity for all connections
•Drain hose I.D. 32 (1-1/4") ··································· 1pc.
•Hose band ··························································· 1pc.
•Tie band ······························································ 1pc. Note1. Suspension bolt(ø10),washer(M10),and nut(M10)
prepare in the field.
2.Take notice of service space as follows. (Please give attention not to occupy service space by letting ducts and pipes through.)
298 (Lifting bolt pitch) 362 70
Connection pipe of indoor unit (Liquid)
ø9.52 <Flare>
Connection pipe of indoor unit (Gas)
ø15.88 <Flare>
|
|
200 |
|
|
Access |
|
|
|
door |
|
|
|
450 |
|
|
Service |
|
|
|
space |
|
|
700 |
|
|
|
|
|
|
|
250 |
200 |
|
|
|
|
A B |
C |
D |
CMB-P104V-G |
|
3 |
180 |
CMB-P105V-G |
|
4 |
240 |
CMB-P106V-G 648 702 |
5 |
300 |
|
CMB-P108V-G |
|
7 |
420 |
CMB-P1010V-G |
|
9 |
540 |
CMB-P1013V-G |
1098 1152 |
12 |
720 |
CMB-P1016V-G |
|
15 |
900 |
G-P104,105,106,108,1010,1013,1016V-CMB (3)
<Unit:mm>
|
Band(Accessory) |
|
|
|
|
Note1. Suspension bolt (ø10), washer (M10), and nut (M10) |
|
<Accessories> |
|
|||
|
|
|
|
|
|
Refrigerant<Low pressure> conn. pipe |
2pcs. |
|||||
|
|
|
|
|
|
|
prepare in the field. |
|
|
|
||
|
Drain hose(Accessory) |
12 |
|
|
|
|
2. Take notice of service space as follows. |
|
|
Refrigerant<High pressure> conn. pipe |
1pc. |
|
|
|
|
|
|
(Please give attention not to occupy service |
|
Refrigerant<Gas> conn. pipe |
6pcs. |
||||
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|||||
|
|
30 |
|
|
|
|
space by letting ducts and pipes through.) |
|
|
Refrigerant<Liquid> conn. pipe |
2pcs. |
|
|
|
|
|
|
|
3. Install this product in a location where noise (refrigerant noise) |
Drain hose(VP-25 connection) |
1pc. |
||||
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
emitted by the unit will not disturb the neighbors. |
|
Hose band |
1pc. |
||
|
ø31 |
|
|
|
|
|
(For use in quiet enviroments with low background noise, position |
Tie band |
1pc. |
|||
|
|
14 |
|
|
|
the BC CONTROLLER at least 5m away from any indoor units.) |
|
|
||||
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
4. Install the unit horizontally. |
|
|
|
|
|
|
Detail of X section |
Dtail of Y section |
|
|
|
5. The indoor unit/PWFY branch is for cooling/heating.The indoor unit/PWFY |
|
|||||
|
|
|
|
cannot be simultaneously operated in different operation modes. |
|
|
||||||
|
|
Connection pipe of outdoor unit (High pressure) |
|
6. The PWFY unit branch is for the heating only. |
|
|
|
|||||
|
|
|
|
|
|
|
|
|
||||
Drain piping |
PURY-P200: ø15.88<Brazed>(use attachment pipe) |
Y |
|
|
|
|
|
|
||||
PURY-P250,P300,P350: ø19.05<Brazed> |
|
|
|
|
|
|
|
|||||
VP-25 connection |
|
|
|
|
|
|
Control box |
|
|
70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
X |
|
|
|
|
|
298 (Lifting bolt pitch) |
|
|
- |
181 |
103 |
255 |
|
|
|
|
|
|
362 |
|
|
- |
90 |
90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
127 |
21 |
|
|
|
|
|
648 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
Connection pipe of outdoor unit (Low pressure) |
|
|
|
|
702 |
|
|
|
|
||
|
|
|
|
|
(Lifting bolt pitch) |
|
|
Connection pipe of |
|
|||
|
PURY-P200: ø19.05<Brazed>(use attachment pipe) |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
indoor unit/PWFY (Liquid) |
|
|||
|
PURY-P250,P300: ø22.2<Brazed> |
|
|
90 |
252 |
300 |
|
|
~P300: ø9.52<Brazed>(use attachment pipe) |
|
||
|
PURY-P350: ø28.58<Brazed>(use attachment pipe) |
58 |
27 |
|
|
|
|
|
|
|||
|
|
|
|
|
|
P301~P400: ø12.7<Brazed>(use attachment pipe) |
|
|||||
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
P401~: ø15.88<Brazed> |
|
|
|
200 |
|
103 |
|
|
|
Liquid line Indoor unit/PWFY |
Liquid line |
|
Connection pipe of |
|
|
|
|
|
|
|
|
(Cooling/Heating) |
PWFY(Heating only) |
|
|
||
|
|
|
|
284 255 |
|
|
|
Gas line |
Gas line |
|
PWFY (Liquid) |
|
|
Access |
|
|
|
|
|
|
|
|
~P300: ø9.52<Brazed> |
|
|
|
door |
|
|
|
|
|
|
|
|
|
|
|
45 |
|
|
|
|
|
|
|
|
|
Connection pipe of |
|
|
|
|
|
|
|
|
|
|
|
PWFY (Gas) |
|
||
|
|
|
700 |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
~P140: ø15.88<Brazed>(use attachment pipe) |
|
||
|
|
|
|
|
|
|
|
|
|
|
||
|
Service |
250 |
|
|
|
|
|
|
|
P141~P200: ø19.05<Brazed> |
|
|
|
space |
|
|
|
200 |
423 |
|
190 |
P201~P300: ø22.2<Brazed>(use attachment pipe) |
|
||
|
|
|
|
|
|
|
||||||
|
|
|
|
Connection pipe of |
|
|
|
|
|
|
|
|
|
|
|
|
indoor unit/PWFY (Gas) |
|
|
|
|
|
|
||
|
|
|
|
~P140: ø15.88<Brazed>(use attachment pipe) |
|
|
|
|
|
|||
|
|
|
|
P141~P200: ø19.05<Brazed>(use attachment pipe) |
|
|
|
|
|
|||
|
200 |
|
|
P201~P300: ø22.2<Brazed>(use attachment pipe) |
|
|
|
<Unit:mm> |
|
|||
|
|
|
|
P301~: ø28.58<Brazed>(use attachment pipe) |
|
|
|
|
J-PW202V-CMB (4)
0
63H1
P
63HS |
1 |
|
|
|
|
|
|
|
F01 |
|
|
2 |
|
|
|
P |
N |
|
|
CNAC |
|
||
|
3 |
|
|
|
CN631 |
|
AC250V |
1 2 |
|||
|
3 2 1 |
CN63HS |
|
1 |
3 |
ZNR01 |
6.3A |
red |
|||
|
|
|
nkp |
|
|
|
|
||||
63LS |
1 |
|
|
|
F631 |
|
|
U |
|
|
|
2 |
|
|
|
|
|
|
|
|
|||
|
3 |
|
CN63LS |
1 3 |
DC700V |
|
|
|
|
|
|
|
3 2 1 |
4A |
|
|
|
|
|
|
|||
|
red |
CN661 |
|
|
|
|
|
|
|
||
TH22 t° |
|
|
yellow |
Power |
|
|
|
|
|
|
|
CN405 |
|
Supply trcuc |
|
|
|
|
|||||
|
21 |
yellow |
|
|
|
|
|
|
|
|
TH13 t° |
21 |
CN404 |
|
|
|
|
|
|
|
|
|
Control Board |
|
|
|
|
|
|
|
|
||||||
|
|
|
black |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
TH6 |
|
|
|
|
|
|
|
|
|
|
LED3:Lit when powered |
|
|
|
|
|
|
|
|
24V |
|
|
M |
Fan motor |
||
t° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
21 |
CN403 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(DC) |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
X506 CN506A 2 |
|
|
|||||
|
|
|
|
|
red |
|
|
|
|
|
|
|
|
|
|
|
|
|
tUn address ng(SWU1,SWU2)sett |
|
1 |
|
||||
TH8 |
t° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
21 |
CN402 |
|
|
|
|
|
|
|
|
|
|
|
|
|
onConnect No.(SWU3) |
CN506B 2 |
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
||||||||
|
|
|
|
green |
|
|
|
|
|
|
|
LED1 splayD ng(SW2)sett |
|
|
|
SWU1 |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SWP1 |
SWP3 |
|
|
|
M |
Fan motor |
||||||
TH11 t° |
|
|
|
|
|
|
|
|
|
|
onFunct ng(SW1,SW3,SW4)sett |
|
|
|
|
|||||||||||
21 |
CN401 |
|
|
|
|
|
|
|
SWP2 SWU2 SWU3 |
CN52C |
|
|
|
(DC) |
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
SW1 |
|
SW3 |
|
2 |
|
1 |
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
LED1 |
|
ON |
ON |
|
blue |
|
|
||||||||
4-20mA |
|
|
|
|
|
|
|
|
|
|
|
|
ON SW5 |
OFF 1 |
|
10 OFF 1 |
|
10 |
|
|
|
|
|
|
|
|
3 2 1 |
CN421 |
3 2 |
1 |
CN421 |
|
|
|
|
LED4:Remote controller |
ON SW2 |
ON SW4 |
|
|
|
|
CN4 2 |
|
1 |
|
|||||||
black |
black |
|
|
|
|
OFF 1 5 |
OFF 1 |
|
10 OFF 1 |
|
|
|
|
|
|
|
||||||||||
4-20mA |
|
|
|
|
|
|
|
|
|
|
when powered |
|
|
10 |
|
|
|
|
|
7 |
|
|
||||
|
CN422 |
|
|
CN422 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
|
|
|
3 2 1 |
3 2 |
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 |
|
|
|||
blue |
blue |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CN2 |
|
|
|
|||||
|
|
|
21 |
CN2M |
X511 |
X512 |
X513 |
X514 |
X515 |
X516 |
X517 |
|
|
|
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
blue |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CNLVA |
|
5 |
M |
LEV2W |
|
|
|
|
|
CN3A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
|||
|
|
|
3 |
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
blue |
|
3 |
|
|
|
|
|
|
blue |
|
|
|
|
|
|
|
|
|
|
*5 |
|
*6 |
|
*7 |
|
|
2 |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TB142A |
TB142B |
TB142C |
|
|
1 |
|
|
|||
|
|
|
|
|
TB141A |
|
|
|
|
|
|
TB141B |
|
|
|
|
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CNLVB |
5 |
M |
LEV1W |
|||
|
|
|
|
|
*4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
OUT1 |
OUT3 |
OUT5 |
|
OUT7 |
|
|
|
|
IN2 |
|
|
|
IN8 |
|
|
1 |
|
|
||
|
|
|
|
|
|
|
OUT2 OUT4 |
|
OUT6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IN1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IN3 IN4 |
|
COM+ IN6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
COM+ IN5 IN7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IN2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IN1 |
|
|
|
|
|
|
|
|
|
|
|
|
- 10 -
|
|
|
THHS |
|
|
|
|
|
|
|
|
|
|
|
|
blue |
|
|
|
|
|
|
t° |
|
|
|
|
|
|
|
|
|
|
red |
|
|
|
|
|
|
CN5 |
CN4 |
CN3 |
|
CN2 |
INV Board |
|
|
|
|
|
LO |
|
|
NO |
|
|
||
|
12 |
12 |
1 2 |
|
1 2 5 6 7 |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
red |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CN52C |
|
|
|
IPM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
RS |
|
52C |
|
black |
1 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
|||
|
|
CYN |
|
|
CYP |
|
|
|
|
|
|
|
|
CX7 |
|
|
|||
|
|
|
|
|
INV control |
|
|
|
|
seNo |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
CX6 |
|
|
|
|||
|
|
|
|
|
|
CIS |
|
trcuc |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
lterF |
|
CX5 |
|
CN5 |
||
|
|
RS3 |
|
|
CT1 |
|
|
|
|
|
|
|
|
|
|
|
|
red |
|
|
RS4 |
|
|
CT2 |
|
|
|
|
|
|
|
L3 |
|
|
|
|
1 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CY5 |
CY6 |
|
|
2 |
|
|
|
|
|
|
|
CB3 |
|
|
|
|
CNAC2 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
+ |
|
blue |
red |
1 |
red |
|
CX4 |
|
|
|
||
|
|
|
|
red |
|
|
CB2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
U |
tewh |
black |
+ |
|
ACL |
|
3 |
|
|
|
|
L2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
V |
W |
CB1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
+ |
|
|
|
E3 |
|
|
|
|
CX3 |
CT1 |
|
|
|
|
|
|
|
|
|
|
|
blue |
red |
|
|
|
|
|
|
|||
black |
|
|
|
|
CPS |
|
|
|
|
|
|
CX2 |
|
|
|
||||
|
|
|
|
|
|
+ |
|
|
|
|
gray |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PFC |
|
|
|
|
|
|
|
|
CY3 |
CY4 |
|
|
|
|
|
|
|
|
|
|
RS1 RS2 |
|
|
|
|
|
|
|
CY2 |
CY1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L4 |
|
|
L1 |
|
|
|
|
|
|
|
|
R |
S |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CX1 |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
red |
blue |
|
|
|
|
|
|
|
|
Z1 |
|
Z2 |
|
|
MS |
U red |
|
|
|
|
|
|
|
|
|
|
|
|
|
U |
|
U |
|
|
V tewh |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DSA |
|
|
3~ |
black |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MoterW |
|
|
|
|
|
|
|
|
|
1 |
3 |
CNAC1 |
LI |
|
NI |
E1 |
E2 |
|
|
(Compressor) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
gray |
gray |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
yellow purple |
gray |
orange |
black |
gray |
|
|
red |
blue |
|
yellow/green |
|
||
|
|
|
|
|
|
M1 |
M2 |
S(SHIELD) TB5 |
1 |
2 |
S(SHIELD) |
TB15 |
L |
N |
|
TB2 |
|
||
|
|
|
|
|
|
To outdoor unt/ |
To MA remote |
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
BC controller/WCB |
controller |
|
|
|
|
|
|
|
|
Power Supply ~220/230/240V 50Hz/60Hz
3 2 1 CN-E1
gray
<HIGH VOLTAGE WARNING>
·Control box houses ghh-voltage parts.
Before inspecting the inside of the control box, turn off the power, keep the tun off for at least 10 nutes,andm rmconf that the voltage
CN631 on Control Board has dropped to DC20V or less.
<CAUTION FOR INSTALLATION>
·Prior to installation,read the Installation Manual carefully. *1.ngleS-dotted nesl catend ngrw not edsuppl thw the tun. *2.Dot-dash nesl catend the control box esboundar. *3.Faston nalsterm have a nglock onfunct.
Make sure the terminals are securely locked in place after insertion.
Press the tab on the nalsterm to removed them. *4 TB141A(output)
Symbol Functon
OUT1 |
Operaton ON/OFF |
OUT2 |
Defrost |
OUT3 |
Compressor |
OUT4 |
Error sgnal |
*5 TB142A(input)
Symbol Functon
IN1 |
Pump nterlock |
*6 TB142B(input)
Symbol onFunct
IN3 |
Connecton demand |
IN4 |
Operaton ON/OFF |
*7 TB142C(input)
Symbol Functon
COM+ |
Common |
IN5 |
Hot water |
IN6 |
Heatng ECO |
IN7 |
Ant-freeze |
Diagrams Wiring Electrical .3 BU-E-P100VM-PWFY (1)
- 11 -
|
3 |
1 |
ZNR01 |
|
CN3T |
U |
|
TH22 t° |
red |
|
|
CN405 |
|
|
|
21 |
|
|
|
yellow |
|
|
TH23 |
t° |
21 |
CN404 |
|
|
|
|
|
|
|
|
|
|
Control Board |
|
|
|
||||||
|
|
|
black |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
TH6 |
|
|
|
|
|
|
|
|
|
|
|
LED3:Lit when powered |
|
|
|
|
|
|
|
|
|
||
t° |
21 |
CN403 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
red |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TH8 |
t° |
21 |
CN402 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
green |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
4-20mA |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 2 1 |
CN421 |
3 2 1 |
CN421 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
black |
black |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
tUn address ng(SWU1,SWU2)sett |
||||||
4-20mA |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
3 2 1 |
CN422 |
3 2 1 |
CN422 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
onConnect No.(SWU3) |
||||
blue |
blue |
|
|
|
|
|
|
|
|
LED1 splayD ng(SW2)sett |
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SWP1 |
SWP3 |
SWU1 |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
onFunct ng(SW1,SW3,SW4)sett |
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SWP2 SWU2 |
SWU3 |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
LED1 |
|
ON |
SW1 |
|
ON |
SW3 |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
21 |
CN2M |
|
|
|
|
|
|
|
|
ON SW5 |
OFF 1 |
|
10 |
OFF 1 |
|
10 |
|
|
|
|
|
|
|
blue |
|
|
|
|
LED4:Remote controller |
ON SW2 |
|
ON SW4 |
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
OFF 1 5 |
OFF 1 |
|
10 |
OFF 1 |
|
10 |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
when powered |
|
|
|
|
|
||||||
|
|
|
3 |
1 |
CN3A |
X511 |
X512 |
X513 |
X514 |
X515 |
X516 |
X517 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
blue |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*5 |
|
*6 |
|
*7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TB142A |
TB142B |
TB142C |
|||
|
|
|
|
|
TB141A |
|
|
|
|
|
|
|
TB141B |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OUT1 |
OUT3 |
OUT5 |
|
OUT7 |
|
|
|
|
|
IN2 |
|
|
|
|
|||
|
|
|
|
|
|
|
OUT2 OUT4 |
|
OUT6 |
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IN1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IN3 IN4 |
COM+ IN6 |
IN8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
COM+ IN5 IN7 |
T01
F01 |
|
|
|
|
AC250V CNAC |
1 |
2 |
||
6.3A |
red |
|
||
|
CN507 1 |
|
3 |
|
X502 |
CN502 |
1 |
|
3 |
|
black |
|
|
|
6
5 CNLVB 43
2
1
6
5 CNLVC 43
2
1
SV1
MLEV1Wa
MLEV1Wb
*3
|
IN1 |
|
|
|
|
|
|
DSA Board |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
red |
CN1 |
ZNR1 |
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
U DSA1 |
yellow purple |
|
orange |
black |
|
red |
blue |
yellow/green |
|
|
M1 M2 |
S(SHIELD) TB5 |
1 |
2 |
TB15 |
L |
N |
|
TB2 |
|
To outdoor unt/ |
To MA remote |
|
|
|
3 |
|
|||
BC controller/ |
controller |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
gray |
|
WCB |
Power Supply |
|
|
|
~220/230/240V |
|
50Hz/60Hz |
<CAUTION FOR INSTALLATION> |
-PWFY (2) |
|||
P100, |
||||
·Prior to installation,read the Installation Manual carefully. |
||||
*1.ngleS-dotted nesl catend ngrw not edsuppl thw the tun. |
|
|||
*2.Dot-dash nesl catend the control box esboundar. |
|
|||
*3.fferenceD of anceappl |
|
|||
Model name anceAppl |
|
-200VM |
||
OUT2 |
Defrost |
|
||
P100 *3 do not stex |
|
|||
P200 |
*3 stex |
|
|
|
*4 TB141A(output) |
|
|
||
Symbol onFunct |
|
|
||
OUT1 |
onOperat ON/OFF |
-E |
||
OUT4 |
Error gnals |
|
||
*5 TB142A(input) |
|
AU |
||
Symbol onFunct |
|
|
||
IN1 |
Pump nterlock |
|
|
|
*6 TB142B(input) |
|
|
||
Symbol onFunct |
|
|
||
IN3 |
Connecton demand |
|
||
IN4 |
Operaton ON/OFF |
|
||
*7 TB142C(input) |
|
|
||
Symbol onFunct |
|
|
||
COM+ |
Common |
|
|
|
IN5 |
Heatng |
|
|
|
IN6 |
Heatng ECO |
|
|
|
IN7 |
Ant-freeze |
|
|
|
IN8 |
Coolng |
|
|
|
<Symbol explanation> |
|
|||
Symbol onExplanat |
|
|
||
SV1 |
dSoleno valve For ngng/closopen the bypass trcuc |
|
||
LEV1Wa |
nearL |
BC controller/WCB/outdoor unit |
|
|
LEV1Wb |
onexpans valve |
BC controller/WCB/outdoor unit |
|
|
TB2 |
nalTerm |
Power supply |
|
|
TB5 |
block |
Outdoor unit/WCB/BC controller |
|
|
TB15 |
|
MA remote controller |
|
|
TH22 |
storTherm |
dqul pep temp |
|
|
TH23 |
|
gas pep temp |
|
|
TH6 |
|
water nlet temp |
|
|
TH8 |
|
water outlet temp |
|
- 12 -
PS1
PS3
TH11
TH12
TH15
TH16
TR
20V~22V 220V~240V
CONT.B
3 |
1 |
|
|
|
|
|
|
2 |
|
|
|
|
|
||
2 |
3 |
2 |
1 |
2 |
1 |
||
1 |
|||||||
3 |
|||||||
|
CN03 |
CN02 |
|||||
|
|
||||||
|
CNP1 |
(Yellow) |
|
|
|||
|
(Black) |
|
|
|
|
|
3 1
22 CNP3
13
1 CN13
2 (Red)
1
2
3
4 CN10
5
6 |
|
|
10 |
1 |
|
|
7 |
|
|
|
|
|
|
8 |
|
|
SW2 SW1 |
|
|
|
|
|
|
|
|
||
1 |
|
|
1 |
8 |
|
|
|
ON |
|
|
|
|
|
|
|
|
|
|
|
|
2 |
CN11 |
OFF |
|
SW4 |
|
|
3 |
|
|
|
|
|
|
4 |
|
|
1 |
8 |
|
|
|
ON |
|
|
|
|
|
|
|
|
|
|
DSA |
|
|
|
OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SW5 |
|
|
|
|
CN07 |
|
|
CN05 |
|
|
|
(Yellow) |
|
(Red) |
|
|
|
1 |
2 3 4 5 |
6 |
1 |
2 3 4 5 |
6 |
|
|
LEV3 |
|
|
LEV1 |
|
ZNR01 ZNR02
F01
250VAC 6.3A F
1 3 5
CN12
CNTR |
1 |
|
3 |
||
(Red) |
||
|
||
X2 |
CN26 |
|
1 |
X1 |
3 |
|
|
X30 |
5 |
|
|
|
7 |
X4CN27(Red) |
|
|
1 |
X3 |
3 |
|
|
X31 |
5 |
|
|
|
7 |
CN28(Blue) |
|
X6 |
1 |
|
|
X5 |
3 |
|
|
X32 |
5 |
|
|
|
7 |
CN29(Green) |
|
X8 |
1 |
|
|
X7 |
3 |
|
|
X33 |
5 |
|
|
|
7 |
CN36(Green) |
|
X21 |
1 |
|
|
|
3 |
TB02
S(SHIELD) Indoor/outdoor
|
|
M2 |
|
Transmission Line |
|
|
|
M1 |
|
|
|
1 |
1 |
1 |
1 |
|
|
|
|
|
|
||
2 |
2 |
2 |
2 |
|
SV1B |
|
|
T1 |
|
||
3 |
3 |
3 |
3 |
SV1A |
|
|
|
|
|
||
4 |
4 |
4 |
4 |
|
SV1C |
|
|
|
|
||
|
|
1 |
1 |
|
|
5 |
5 |
2 |
2 |
|
SV2B |
|
|
T2 |
|
||
6 |
6 |
3 |
3 |
SV2A |
|
|
|
|
|
||
7 |
7 |
4 |
4 |
|
SV2C |
|
|
|
|
||
|
|
1 |
1 |
|
|
8 |
8 |
2 |
2 |
|
SV3B |
|
|
T3 |
|
||
9 |
9 |
3 |
3 |
SV3A |
|
|
|
|
|
||
10 10 |
4 |
4 |
|
SV3C |
|
|
|
|
|
||
|
|
1 |
1 |
|
|
11 11 |
2 |
2 |
|
SV4B |
|
|
|
T4 |
|
||
12 12 |
3 |
3 |
SV4A |
||
|
|
|
|
||
13 13 |
4 |
4 |
|
SV4C |
|
|
|
|
|
||
|
|
1 |
1 |
|
|
14 14 |
2 |
2 |
|
SVM1 |
|
3 |
3 |
|
|||
15 15 |
|
|
|||
|
|
|
|
||
16 16 |
|
|
|
|
|
TB01 |
TO NEXT INDOOR UNIT |
|
|||
|
|
|
|
||
L |
|
|
|
|
|
N |
|
|
PULL BOX |
|
PE |
FUSE(16A) |
|
|
PE |
|
|
BREAKER(16A) |
|
POWER SUPPLY |
|
~220V-240V |
|
50Hz/60Hz |
Symbol explanation
Symbol |
Name |
|
TR |
Transformer |
|
TH11,12,15,16 |
Thermistor sensor |
|
LEV1,3 |
Expansion valve |
|
PS1,3 |
Pressure sensor |
|
CONT.B |
Circuit |
|
board BC controller |
||
TB01 |
Terminal block |
|
(for power source) |
||
|
||
TB02 |
Terminal block |
|
(for Transmission) |
||
|
||
SV1~4A,B,C |
Solenoid valve |
|
SVM1 |
Solenoid valve |
|
T1~4 |
Terminal |
|
F01 |
Fuse AC250V 6.3A F |
Note:1.TB02 is transmission terminal block. Never connect power line to it.
2.The initial set values of switch on CONT.B are as follows.
SW1:0
SW2:0
G-P104V-CMB (3)
.Book Data the to refer information, unit For .available are controller BC of models *Other
- 13 -
TH11
TH12
TH13
TH14
TH15
TH16
M
LEV3
M
LEV1
TR
20V~22V 220V~240V
1
3 2 1 2 1
CN03 CN02 Yellow
1CN13
2Red
1
2
3
4 CN10
5
6
7
8
1
23 CN11
4
1
2
3 CN07
4 Yellow
5
6
1
2
3 CN05
45 Red
6
SW2 SW1
10's 1's digit digit
Unit address setting
1 8
ON
OFF
SW4
1 8
ON
OFF
SW5
1 8
ON
OFF
SW6
WCB Board
LD1:CPU in
operation
Function setting
ZNR01 ZNR02
U |
|
U |
|
F01 |
|
DSA |
AC250V |
|
6.3A F |
||
1 |
3 |
5 |
CN12
3
CNTR
Red
CN26 1 X02 3 X01 5
7
TB02 |
|
Indoor/outdoor |
|
|
|||
S(SHIELD) |
|
|
|
|
|||
|
|
Transmission line |
(Symbol explanation) |
||||
M2 |
|
|
|||||
|
|
|
|
||||
M1 |
|
|
|
|
Symbol |
Name |
|
|
|
|
|
|
|||
|
|
|
|
|
TR |
Transformer |
|
|
|
|
|
|
TH11~16 |
Thermistor sensor |
|
|
|
|
|
|
LEV1,3 |
Expansion valve |
|
|
|
|
|
|
TB01 |
Terminal block |
|
|
|
|
|
|
(for power source) |
||
|
|
|
|
T1 |
|
||
|
|
1 |
1 |
TB02 |
Terminal block |
||
1 |
1 |
2 |
2 |
21S4a |
(for Transmission) |
||
2 |
2 |
SVM1 |
|||||
|
Solenoid valve |
||||||
|
|
SVM1 |
|||||
3 |
3 |
3 |
3 |
||||
|
|
|
21S4a |
4-way valve |
|||
4 |
4 |
4 |
4 |
|
|||
|
|
|
F01 |
Fuse AC250V 6.3A F |
|||
|
|
|
|
|
Note:1. TB02 is transmission terminal block. Never connect power line to it.
2. The initial set values of switch on WCB Board are as follows.
SW1:0
SW2:0
|
TO NEXT |
|
|
INDOOR UNIT |
POWER SUPPLY |
|
|
|
TB01 |
PULL BOX |
~220V-240V |
L |
50Hz/60Hz |
N
FUSE(16A) BREAKER(16A)
J-PW202V-CMB (4)
4. Accessories
(1) PWFY
(A) Strainer |
(B) Heat insulation material |
(C) Connecter sets 2 |
(D) Expansion joint 2 |
*1
*1. PWFY-P200VM-E-AU only
(A)Install the strainer at the water pipe inlet.
(B)This insulation is for exclusive use with the strainer. Wrap the strainer with the insulation after water pipes are installed.
(C)These are analog input connectors. Cut the wire before using.
(D)Supplied only with the PWFY-P200VM-E-AU. Install them at the strainer inlet. Refer to P53 for details.
(2) CMB-P104V-G
SIZE |
Unit |
ø15.88 flare - IDø12.8 |
4 |
ø9.52 flare - IDø6.45 |
4 |
ODø19.05 - IDø15.88 |
1 |
ODø22.2 - IDø19.05 |
1 |
ODø22.2 - IDø28.6 |
1 |
Drain hose set |
1set |
Installation Manual |
1 |
(3) CMB-PW202V-J
SIZE |
Unit |
ODø19.05 - IDø15.88 |
2 |
ODø22.2 - IDø19.05 |
1 |
ODø15.88 - IDø9.52 |
1 |
ODø15.88 - IDø12.7 |
1 |
ODø25.4 - IDø19.05 |
1 |
ODø25.4 - IDø22.2 |
1 |
ODø19.05 - IDø22.2 |
1 |
ODø25.4 - IDø28.6 |
1 |
ODø22.2 - IDø28.6 |
1 |
ODø25.4 - IDø15.88 |
1 |
Drain hose set |
1 set |
Installation Manual |
1 |
- 14 -
IIIProduct Data
1.Capacity tables
(1) Correction by temperature
(1)-1 R2 series + PWFY-P100VM-E-BU
PURY- |
P200,250YHM-A(-BS) |
EP200,250YHM-A(-BS) |
Ratio of heating capacity
1.1 |
|
|
|
|
|
|
Booster unit inlet-water temp. [°C]40°C |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50°C |
1.0 |
|
|
|
|
|
|
|
|
|
60°C |
|
|
|
|
|
|
|
|
|
|
65°C |
0.9 |
|
|
|
|
|
|
|
|
|
30°C |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20°C |
0.7 |
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10°C |
0.5 |
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Outdoor temp. [°CWB]
Booster unit inlet-water temp. [°C]
|
1.1 |
|
|
|
|
|
|
|
|
|
|
input |
1.0 |
|
|
|
|
|
|
|
|
|
65°C |
0.9 |
|
|
|
|
|
|
|
|
|
60°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
unit |
0.8 |
|
|
|
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
|
||
0.7 |
|
|
|
|
|
|
|
|
|
|
|
booster |
|
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
40°C |
|
0.5 |
|
|
|
|
|
|
|
|
|
||
of |
|
|
|
|
|
|
|
|
|
30°C |
|
|
|
|
|
|
|
|
|
|
|
||
Ratio |
0.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20°C |
||
0.3 |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.2 |
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Outdoor temp. [°CWB]
Booster unit inlet-water temp. [°C]
|
1.1 |
|
|
|
|
|
|
|
|
|
|
input |
1.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
unit |
0.9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
40°C |
|
outdoor |
|
|
|
|
|
|
|
|
|
|
|
0.8 |
|
|
|
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
|
|
60°C 30°C |
|
of |
0.7 |
|
|
|
|
|
|
|
|
|
65°C 20°C |
Ratio |
|
|
|
|
|
|
|
|
|
|
10°C |
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Outdoor temp. [°CWB]
- 15 -
|
PURY- |
P300,350,400YHM-A(-BS) |
|
|
EP300,400Y(S)HM-A(-BS) |
|
|
|||||
|
1.1 |
|
|
|
|
|
|
Booster unit inlet-water temp. [°C] |
40°C |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50°C |
capacity |
1.0 |
|
|
|
|
|
|
|
|
|
|
60°C |
|
|
|
|
|
|
|
|
|
|
|
65°C |
|
0.9 |
|
|
|
|
|
|
|
|
|
|
30°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
heating |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20°C |
|
of |
0.7 |
|
|
|
|
|
|
|
|
|
|
|
Ratio |
|
|
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10°C |
|
0.5 |
|
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
|
Ratio of booster unit input
Outdoor temp. [°CWB]
Booster unit inlet-water temp. [°C]
1.1
1.0 65°C
0.9 60°C
0.8 |
50°C |
|
|
||
0.7 |
|
|
0.6 |
40°C |
|
|
||
0.5 |
30°C |
|
|
||
0.4 |
|
|
0.3 |
20°C |
|
10°C |
||
|
||
0.2 |
|
-20 -15 -10 -5 0 5 10 15 20 25 30
Outdoor temp. [°CWB]
Booster unit inlet-water temp. [°C]
|
1.1 |
|
|
|
|
|
|
|
|
|
|
|
input |
1.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
unit |
0.9 |
|
|
|
|
|
|
|
|
|
40°C |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
outdoor |
0.8 |
|
|
|
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
|
60°C |
30°C |
||
|
|
|
|
|
|
|
|
|
|
|||
0.7 |
|
|
|
|
|
|
|
|
|
65°C |
20°C |
|
of |
|
|
|
|
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
|
|
||
Ratio |
|
|
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
|
Outdoor temp. [°CWB]
- 16 -
PURY- |
P450,500,550,600,650YSHM-A(-BS) |
EP450,500,550,600YSHM-A(1)(-BS) |
Ratio of heating capacity
1.1 |
|
|
|
|
|
|
Booster unit inlet-water temp. [°C] 40°C |
|||
|
|
|
|
|
|
|
|
|
|
50°C |
1.0 |
|
|
|
|
|
|
|
|
|
60°C |
|
|
|
|
|
|
|
|
|
|
65°C |
0.9 |
|
|
|
|
|
|
|
|
|
30°C |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20°C |
0.7 |
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10°C |
0.5 |
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Ratio of booster unit input
|
Outdoor temp. [°CWB] |
1.1 |
Booster unit inlet-water temp. [°C] |
|
|
1.0 |
65°C |
0.9 |
60°C |
|
|
0.8 |
50°C |
|
|
0.7 |
|
0.6 40°C
0.5
30°C
0.4
20°C 0.3 10°C
0.2
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Outdoor temp. [°CWB]
|
1.1 |
|
|
|
|
|
|
Booster unit inlet-water temp. [°C] |
|||
|
|
|
|
|
|
|
|
|
|
|
|
input |
1.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
unit |
0.9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
outdoor |
0.8 |
|
|
|
|
|
|
|
|
|
40°C |
|
|
|
|
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
|
|
60°C 30°C |
|
of |
0.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
65°C 20°C |
||
Ratio |
|
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Outdoor temp. [°CWB]
- 17 -
Ratio of heating capacity
PURY- |
|
P700,750,800YSHM-A(-BS) |
|
|
|
|
|
|
||
1.1 |
|
|
|
|
|
|
Booster unit inlet-water temp. [°C] |
|||
|
|
|
|
|
|
|
|
|
40°C |
|
|
|
|
|
|
|
|
|
|
|
50°C |
1.0 |
|
|
|
|
|
|
|
|
|
60°C |
|
|
|
|
|
|
|
|
|
|
65°C |
0.9 |
|
|
|
|
|
|
|
|
|
30°C |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20°C |
0.7 |
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10°C |
0.5 |
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Outdoor temp. [°CWB]
|
1.1 |
|
|
|
|
|
|
Booster unit inlet-water temp. [°C] |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
1.0 |
|
|
|
|
|
|
|
|
|
65°C |
input |
0.9 |
|
|
|
|
|
|
|
|
|
60°C |
|
|
|
|
|
|
|
|
|
|
||
0.8 |
|
|
|
|
|
|
|
|
|
|
|
unit |
|
|
|
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
|
|
||
0.7 |
|
|
|
|
|
|
|
|
|
|
|
of booster |
|
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
40°C |
|
|
|
|
|
|
|
|
|
|
|
||
0.5 |
|
|
|
|
|
|
|
|
|
30°C |
|
Ratio |
|
|
|
|
|
|
|
|
|
|
|
0.4 |
|
|
|
|
|
|
|
|
|
20°C |
|
|
|
|
|
|
|
|
|
|
|
||
|
0.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10°C |
|
|
0.2 |
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Outdoor temp. [°CWB]
|
1.1 |
|
|
|
|
|
|
Booster unit inlet-water temp. [°C] |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
input |
1.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
unit |
0.9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
40°C |
|
|
of outdoor |
|
|
|
|
|
|
|
|
|
|
|
|
0.8 |
|
|
|
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
|
|
|
60°C |
30°C |
|
0.7 |
|
|
|
|
|
|
|
|
|
65°C |
20°C |
|
Ratio |
|
|
|
|
|
|
|
|
|
|
|
10°C |
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
|
Outdoor temp. [°CWB]
- 18 -
(1)-2 R2 series + PWFY-P100VM-E-BU + WCB Energy saving mode*
*For energy saving mode, set WCB DIP SW 6-5 ON.
|
PURY- |
P200,250YHM-A(-BS) |
|
|
|
EP200,250YHM-A(-BS) |
|
|
||||
|
1.1 |
|
|
|
|
|
|
Booster unit inlet-water temp. [°C] |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
capacity |
1.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
40°C |
|
|
0.9 |
|
|
|
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
|
|
60°C |
30°C |
||
|
|
|
|
|
|
|
|
|
|
|||
of heating |
|
|
|
|
|
|
|
|
|
|
||
0.8 |
|
|
|
|
|
|
|
|
|
65°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
0.7 |
|
|
|
|
|
|
|
|
|
20°C |
|
|
Ratio |
|
|
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
|
Ratio of booster unit input
Outdoor temp. [°CWB]
Booster unit inlet-water temp. [°C]
1.2
1.0
65°C
60°C
0.8 50°C
0.6 |
40°C |
30°C
0.4
20°C
10°C
0.2
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Outdoor temp. [°CWB]
Booster unit inlet-water temp. [°C]
|
1.0 |
|
|
|
|
|
|
|
|
|
|
|
input |
0.9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
unit |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
outdoor |
0.7 |
|
|
|
|
|
|
|
|
|
40°C |
30°C |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
50°C |
20°C |
|
0.6 |
|
|
|
|
|
|
|
|
|
|
10°C |
|
of |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Ratio |
|
|
|
|
|
|
|
|
|
|
60°C |
|
0.5 |
|
|
|
|
|
|
|
|
|
65°C |
|
|
|
0.4 |
|
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
|
Outdoor temp. [°CWB]
- 19 -
|
PURY- |
P300,350YHM-A(-BS) |
|
|
|
EP300YHM-A(-BS) |
|
|
|
|||
|
1.1 |
|
|
|
|
|
|
Booster unit inlet-water temp. [°C] |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
capacity |
1.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
40°C |
|
|
0.9 |
|
|
|
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
|
|
60°C |
30°C |
||
|
|
|
|
|
|
|
|
|
|
|||
of heating |
|
|
|
|
|
|
|
|
|
|
||
0.8 |
|
|
|
|
|
|
|
|
|
65°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
0.7 |
|
|
|
|
|
|
|
|
|
20°C |
|
|
Ratio |
|
|
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
|
Outdoor temp. [°CWB]
Booster unit inlet-water temp. [°C]
|
1.2 |
|
|
|
|
|
|
|
|
|
|
input |
1.0 |
|
|
|
|
|
|
|
|
|
65°C |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
60°C |
|
unit |
0.8 |
|
|
|
|
|
|
|
|
|
50°C |
of booster |
|
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
40°C |
|
|
|
|
|
|
|
|
|
|
|
30°C |
|
Ratio |
|
|
|
|
|
|
|
|
|
|
|
0.4 |
|
|
|
|
|
|
|
|
|
20°C |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10°C |
|
0.2 |
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
Outdoor temp. [°CWB]
Booster unit inlet-water temp. [°C]
|
1.1 |
|
|
|
|
|
|
|
|
|
|
|
input |
1.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
unit |
0.9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
outdoor |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
40°C |
30°C |
|
0.7 |
|
|
|
|
|
|
|
|
|
|
|
|
of |
|
|
|
|
|
|
|
|
|
50°C |
20°C |
|
|
|
|
|
|
|
|
|
|
|
|||
Ratio |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
10°C |
|
0.6 |
|
|
|
|
|
|
|
|
|
60°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
|
65°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
|
Outdoor temp. [°CWB]
- 20 -
(1)-3 WR2 series + PWFY-P100VM-E-BU |
|
|
|
|
|
||||
|
PQRY- |
P200,250,300,400,450,500,550,600Y(S)HM-A |
|
|
|
|
|||
|
1.2 |
|
|
|
|
Booster unit inlet-water temp. [°C] |
|
||
|
|
|
|
|
|
|
|
|
|
capacity |
1.1 |
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
40°C |
|
||
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
60°C |
|
|
unit |
1.0 |
|
|
|
|
|
|
30°C |
|
|
|
|
|
|
|
65°C |
20°C |
||
of Booster |
0.9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ratio |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
|
|
|
0.7 |
|
|
|
|
|
|
|
|
|
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
|
Ratio of Booster unit input
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
Heat source unit (WR2) inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
65°C
60°C
50°C
40°C
30°C
20°C
10°C
|
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
|
|
|
|
Heat source unit (WR2) inlet-water temp. [°C] |
|
|
|
|||
|
1.2 |
|
|
|
|
Booster unit inlet-water temp. [°C] |
|
||
|
|
|
|
|
|
|
|
|
|
input |
1.1 |
|
|
|
|
|
|
|
|
unit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
source |
1.0 |
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
40°C |
|
|
of Heat |
0.9 |
|
|
|
|
|
|
60°C |
30°C |
|
|
|
|
|
|
|
65°C |
20°C |
|
Ratio |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10°C |
|
|
0.7 |
|
|
|
|
|
|
|
|
|
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
|
Heat source unit (WR2) inlet-water temp. [°C]
- 21 -
(1)-4 WR2 series + PWFY-P100VM-E-BU + WCB Energy saving mode*
*For energy saving mode, set WCB DIP SW 6-5 ON.
|
PQRY- |
P200,250,300,400,450,500,550,600Y(S)HM-A |
|
|
|
|
|||
|
1.2 |
|
|
|
|
Booster unit inlet-water temp. [°C] |
|
||
|
|
|
|
|
|
|
|
|
|
capacity |
1.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
|
40°C |
|
|
unit |
|
|
|
|
|
|
|
|
|
1.0 |
|
|
|
|
|
|
|
|
|
of Booster |
|
|
|
|
|
|
|
60°C |
30°C |
0.9 |
|
|
|
|
|
|
65°C |
20°C |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
Ratio |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.7 |
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
|
|
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
|
Ratio of Booster unit input
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
Heat source unit (WR2) inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
65°C
60°C
50°C
40°C
30°C
20°C
10°C
|
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
|
|
|
|
Heat source unit (WR2) inlet-water temp. [°C] |
|
|
|
|||
|
1.2 |
|
|
|
|
Booster unit inlet-water temp. [°C] |
|
||
|
|
|
|
|
|
|
|
|
|
unit input |
1.1 |
|
|
|
|
|
|
|
|
1.0 |
|
|
|
|
|
|
|
|
|
source |
0.9 |
|
|
|
|
|
|
50°C |
|
|
|
|
|
|
|
|
40°C |
|
|
of Heat |
0.8 |
|
|
|
|
|
|
|
|
0.7 |
|
|
|
|
|
|
60°C |
|
|
Ratio |
|
|
|
|
|
|
30°C |
||
0.6 |
|
|
|
|
|
|
|
20°C |
|
|
|
|
|
|
|
65°C |
|
||
|
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
|
|
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
|
Heat source unit (WR2) inlet-water temp. [°C]
- 22 -
(1)-5 Y series + PWFY-P100,200VM-E-AU |
|
|
|
|
||||
|
PUHY- P200,250YHM-A(-BS) |
|
|
EP200,250YHM-A(-BS) |
|
|||
Heating |
|
|
|
|
HEX unit inlet-water temp. [°C] |
|||
|
1.3 |
|
|
|
|
|||
capacity |
|
|
|
|
|
|
10°C |
|
1.2 |
|
|
|
|
|
|
||
|
|
|
|
|
|
20°C |
||
1.1 |
|
|
|
|
|
|
30°C |
|
1.0 |
|
|
|
|
|
|
35°C |
|
0.9 |
|
|
|
|
|
|
|
|
heating |
|
|
|
|
|
|
40°C |
|
0.8 |
|
|
|
|
|
|
||
0.7 |
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
of |
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
Ratio |
|
|
|
|
|
|
|
|
0.4 |
|
|
|
|
|
|
|
|
0.3 |
|
|
|
|
|
|
|
|
|
0.2 |
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
Outdoor temp. [°CWB]
HEX unit inlet-water temp. [°C]
input |
1.2 |
|
|
|
|
|
|
|
1.1 |
|
|
|
|
|
|
|
|
unit |
1.0 |
|
|
|
|
|
|
40°C |
0.9 |
|
|
|
|
|
|
||
outdoor |
|
|
|
|
|
|
35°C |
|
0.8 |
|
|
|
|
|
|
||
|
|
|
|
|
|
30°C |
||
0.7 |
|
|
|
|
|
|
20°C |
|
|
|
|
|
|
|
|
||
of |
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
10°C |
||
Ratio |
0.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
0.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-20 |
-15 |
-10 |
-5 |
0 |
5 |
10 |
15 |
Outdoor temp. [°CWB]
Cooling |
HEX unit inlet-water temp. [°C] |
|
capacity |
1.4 |
|
|
|
|
|
|
|
|
|
1.3 |
|
|
|
|
|
|
|
|
|
|
1.2 |
|
|
|
|
|
|
|
|
|
|
1.1 |
|
|
|
|
|
|
|
|
35°C |
|
cooling |
|
|
|
|
|
|
|
|
||
1.0 |
|
|
|
|
|
|
|
|
30°C |
|
0.9 |
|
|
|
|
|
|
|
|
25°C |
|
0.8 |
|
|
|
|
|
|
|
|
20°C |
|
of |
|
|
|
|
|
|
|
|
||
0.7 |
|
|
|
|
|
|
|
|
15°C |
|
Ratio |
|
|
|
|
|
|
|
|
||
0.6 |
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
||
|
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
35 |
40 |
Outdoor temp. [°CDB]
input |
|
|
|
|
|
|
HEX unit inlet-water temp. [°C] |
35°C |
|||
1.2 |
|
|
|
|
|
30°C |
|||||
|
|
|
|
|
|
|
|
|
|||
1.1 |
|
|
|
|
|
|
|
|
|
25°C |
|
unit |
|
|
|
|
|
|
|
|
|
20°C |
|
1.0 |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
15°C |
||
outdoor |
0.9 |
|
|
|
|
|
|
|
|
|
10°C |
|
|
|
|
|
|
|
|
|
|
||
0.8 |
|
|
|
|
|
|
|
|
|
|
|
0.7 |
|
|
|
|
|
|
|
|
|
|
|
of |
|
|
|
|
|
|
|
|
|
|
|
0.6 |
|
|
|
|
|
|
|
|
|
|
|
Ratio |
|
|
|
|
|
|
|
|
|
|
|
0.5 |
|
|
|
|
|
|
|
|
|
|
|
|
-5 |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
35 |
40 |
|
Outdoor temp. [°CDB]
- 23 -