Mitsubishi PWFY-P100VM-E-BU, PWFY-P100VM-E-AU, PWFY-P200VM-E-AU, WCB CMB-PW202V-J DATA BOOK

DATA BOOK
2nd edition
AIR CONDITIONERS
MODEL
PWFY-P100VM-E-BU PWFY-P100VM-E-AU PWFY-P200VM-E-AU
• Do not use steel pipes as water pipes.
- Copper pipes are recommended.
• The water circuit should be a closed circuit.
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water
leakage, electric shock, or re.
• Install the unit in a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down,
resulting in injuries.
• Do not touch the unit. The unit surface can be hot.
• Do not install the unit where corrosive gas is generated.
• Usethespeciedcablesforwiring.Makethe
connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate
heat and cause a re.
• Prepare for rain and other moisture and
earthquakesandinstalltheunitatthespecied
place.
- Improper installation may cause the unit to topple
and result in injury.
• Always use an strainer and other accessories
speciedbyMitsubishiElectric.
- Ask an authorized technician to install the accesso
-
ries. Improper installation by the user may result in
water leakage, electric shock, or re.
• Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage,
electric shock, or re may result.
• Do not touch the refrigerant pipes and Water pipes.
- Improper handling may result in injury.
• When handling this product, always wear protec
-
tive equipment.
 EG:Gloves,fullarmprotectionnamelyboilersuit,
and safety glasses.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a ame,
poisonous gases will be released.
• InstalltheunitaccordingtothisInstallationManu­al.
- If the unit is installed improperly, water leakage,
electric shock, or re may result.
• Have all electric work done by a licensed electri
-
cianaccordingto“ElectricFacilityEngineering
Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric
work is performed improperly, electric shock and re
may result.
• Keep the electric parts away from water (washing water etc.).
- It might result in electric shock, catching re or
smoke.
• Securely install the heat source unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly,
dust or water may enter the heat source unit and re
or electric shock may result.
• When installing and moving the air conditioner to another site, do not charge it with a refrigerant
differentfromtherefrigerant(R410A)speciedon
the unit.
- If a different refrigerant or air is mixed with the origi
­nal refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refriger
­ant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate meas
­ures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water
leakage, electric shock, or re may result.
- i -
• After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or other heat source, it may gen erate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other
protection device is shorted and operated forcibly,
or parts other than those specied by Mitsubishi Electric are used, re or explosion may result.
• To dispose of this product, consult your dealer.
• The installer and system specialist shall secure
-
safety against leakage according to local regula tion or standards.
- Following standards may be applicable if local regu lation are not available.
• Pay a special attention to the place, such as a
basement, etc. where refrigeration gas can stay, since refrigeration is heavier than the air.
-
-
• Do not use the existing refrigerant piping.
- The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to dete riorate.
- R410A is a high-pressure refrigerant and can cause the existing piping to burst.
• Use refrigerant piping made of C1220 (CU-DHP)
phosphorusdeoxidizedcopperasspeciedinthe
JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the in ner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav­ing particles, oils, moisture, or any other contami­nant.
- Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil to deteriorate.
• Store the piping to be used during installation
indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
• Apply a small amount of ester oil, ether oil, or
alkylbenzenetoares.(forindoorunit)
- Inltration of a large amount of mineral oil may
cause the refrigerant oil to deteriorate.
• Useliquidrefrigeranttollthesystem.
- If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
-
• Do not use a refrigerant other than R410A.
- If another refrigerant (R22, etc.) is mixed with
-
R410A, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
• Useavacuumpumpwithareverseowcheck
valve.
- The vacuum pump oil may ow back into the refrig
erant cycle and cause the refrigerant oil to deterio­rate.
• Do not use the following tools that are used with conventional refrigerants.
 (Gaugemanifold,chargehose,gasleakdetector,
reverseowcheckvalve,refrigerantchargebase,
refrigerant recovery equipment)
- If the conventional refrigerant and refrigerant oil are
mixed in the R410A, the refrigerant may deterio rated.
- If water is mixed in the R410A, the refrigerant oil
may deteriorate.
- Since R410A does not contain any chlorine, gas
leak detectors for conventional refrigerants will not react to it.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant
to deteriorate.
• Do not use antioxidant or leak-detection additive.
• Be especially careful when managing the tools.
- If dust, dirt, or water gets in the refrigerant cycle, the
refrigerant may deteriorate.
-
-
- ii -
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an
explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
• Do not use the air conditioner in special environ ments.
- Oil, steam, sulfuric smoke, etc. can signicantly reduce
the performance of the air conditioner or damage its parts.
-
• When installing the unit in a hospital, communica
tionstation,orsimilarplace,providesufcient
protection against noise.
- The inverter equipment, private power generator, high-frequency medical equipment, or radio commu nication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may
cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged, condensation may drip from the indoor unit. Perform collective drainage work together with the unit, as required.
-
-
- iii -
• Groundtheunit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or telephone ground lines. Improper grounding may result in electric shock.
• Install the power cable so that tension is not
applied to the cable.
- Tension may cause the cable to break and generate
heat and cause a re.
• Install a leak circuit breaker, as required.
- If a leak circuit breaker is not installed, electric shock may result.
• Usepowerlinecablesofsufcientcurrent
carrying capacity and rating.
- Cables that are too small may leak, generate heat,
and cause a re.
• Use only a circuit breaker and fuse of the
speciedcapacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit
failure or re.
• Do not wash the air conditioner units.
- Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall
and cause personal injury or damage property.
• Install the drain piping according to this
InstallationManualtoensureproperdrainage.
Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage and
damage to furniture and other possessions.
• Be very careful about product transportation.
- If the unit weighs more than 20kg, carry the unit with
more than one person.
- Some products use PP bands for packaging. Do not
use any PP bands for a means of transportation. It is dangerous.
- When transporting the unit, support it at the specied
positions on the unit base. Also support the unit at four points so that it cannot slip side ways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or
wooden parts, may cause stabs or other injuries.
- Tear apart and throw away plastic packaging bags
so that it is out of reach of children. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
- iv -
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the
main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
• Donottouchtheswitcheswithwetngers.
- Touching a switch with wet ngers can cause elec
tric shock.
• Do not touch the refrigerant pipes during and im mediately after operation.
- During and immediately after operation, the
refrigerant pipes are may be hot and may be cold,
depending on the condition of the refrigerant owing
through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause
injuries.
-
• Do not turn off the power immediately after stopping operation.
- Always wait at least ve minutes before turning off
the power. Otherwise, water leakage and trouble may occur.
• Do not touch the surface of the compressor during servicing.
- If unit is connected to the supply and not running,
crank case heater at compressor is operating.
-
• Do not touch the panels near the fan outlet with
barehands:theycangethotwhiletheunitisin
operation (even if it is stopped) or immediately after operation to prevent burns. Wear gloves to protect your hands when it is necessary to touch the panels.
• While the unit is in operation or immediately after operation, high-temperature exhaust air may blow out of the fan exhaust outlet. Do not hold your hands over the outlet or touch the panels near the outlet.
• Be sure to provide a pathway for the exhaust air from the fan.
• Water pipes can get very hot, depending on the preset temperature. Wrap the water pipes with insulating materials to prevent burns.
- v -
Contents
Safety Precautions
IGeneralEquipmentDescriptions
1. Unit conguration table ············································ 1
2. Operable temperature range ··································· 1
3. Connectable outdoor unit/heat source unit capacity range ·························································
IIProductSpecications
1. Specications ·························································· 2
(1) PWFY-P100VM-E-BU
(2) PWFY-P100VM-E-AU
(3) PWFY-P200VM-E-AU
(4) CMB-P104V-G
(5) CMB-PW202V-J
2. External Dimensions
(1) PWFY-P100VM-E-BU
(2) PWFY-P100, 200VM-E-AU
(3) CMB-P104,105,106,108,1010,1013,1016V-G
(4) CMB-PW202V-J
3. Electrical Wiring Diagrams ····································
(1) PWFY-P100VM-E-BU
(2) PWFY-P100, 200VM-E-AU
(3) CMB-P104V-G
(4) CMB-PW202V-J
4. Accessories ···························································
(1) PWFY
(2) CMB-P104V-G
(3) CMB-PW202V-J
················································ 6
10
14
III Product Data
1. Capacity tables ······················································ 15
(1) Correction by temperature
(2) Correction by water ow rate
(3) Correction by total indoor
(4) Correction by refrigerant piping length
(5) Correction at frosting and defrosting
(6) Water pressure drop
(7) Operation temperature range
2. Sound pressure levels ··········································· 41
(1) PWFY-P100VM-E-BU
(2) PWFY-P100, 200VM-E-AU
3. Vibration levels ······················································
(1) PWFY-P100VM-E-BU
4. Refrigerant circuit diagrams and thermal sensors ····················································· 43
(1) PWFY-P100VM-E-BU
(2) PWFY-P100VM-E-AU
(3) PWFY-P200VM-E-AU
42
IV Installation
1. How to calculate the necessary heating capacity ·· 44
(1) Heating capacity calculation
(2) Calculation example
2. Installation ·····························································
(1) Selecting an installation site
1
(2) Installing the unit
(3) Refrigerant pipe and drain pipe specications
(4) Connecting refrigerant pipes and drain pipes
3. Water pipe installation ···········································
(1) Water circuit sample
(2) Selecting a water pump
(3) Installing the strainer
(4) Precautions during installation
(5) Example of unit installation
(6) Insulation installation
(7) Water processing and water quality control
(8) Pump interlock
(9) Anti freeze mode
V System Design
1. Electrical work ······················································· 56
(1) General cautions
(2) Power supply for PWFY unit
(3) Connecting remote controller, indoor and outdoor transmission cables
(4) Transmission cable specications
(5) Connecting electrical connections
(6) Indoor unit address setting
(7) External input/output function
(8) BC controller piping design
(9) WCB piping design
VI Controller
1. PAR-W21MAA specications ································· 67
2. Dip switch functions ···············································
VIIMaintenanceCycle
1. Routine maintenance checks ································ 69
2. Parts Replacement Cycle ······································ 69
VIII Product Data (additional information for chapter III.)
1. Outdoor unit capacity tables ·································· 70
(1) Correction by total indoor
(2) Correction by refrigerant piping length
(3) Correction at frosting and defrosting
45
51
68
GeneralEquipmentDescriptions
I
1.Unitcongurationtable
Model PWFY-P100VM-E-BU
Outdoor unit
Connection
PURY-(E)P•Y(S)HM-A(-BS) / PQRY-P•Y(S)HM-A
BC controller
WCB
BC controller: CMB-P104,105,106,108,1010,1013,1016V-G
Main BC controller: CMB-P108,1010,1013,1016V-GA / CMB-P1016V-HA
Sub BC controller: CMB-P104,108V-GB / CMB-P1016V-HB
PWFY-P100VM-E-AU PWFY-P200VM-E-AU PUHY-(E)/(H)P•Y(S)HM-A(-BS) / PQHY-P•(S)HM-A
PURY-(E)P•Y(S)HM-A(-BS) / PQRY-P•Y(S)HM-A
CMB-PW202V-J
2. Operable temperature range
<PWFY-P100VM-E-BU>
Only PWFY
Inlet water temperature R2/WR2 series 10 to 70ºC 10 to 70ºC Outdoor temperature R2 series -20 to 32ºCWB -20 to 32ºCWB -20 to 15.5ºCWB
Circulating water
temperature
WR2 series 10 to 45ºC 10 to 45ºC 10 to 45ºC
PWFY with
standard indoor unit
Heating
<PWFY-P100,200VM-E-AU>
Only PWFY PWFY with standard indoor units
Cooling Heating Cooling Heating
Inlet water temperature
Outdoor temperature
Circulating water temperature
R2/WR2 series Y/HP/WY series R2 series Y series HP series WR2 series WYseries
10 to 35ºC 10 to 40ºC 10 to 35ºC 10 to 40ºC 10 to 35ºC 10 to 40ºC 10 to 35ºC 10 to 40ºC
-5 to 43ºCDB -20 to 32ºCWB -5 to 43ºCDB -20 to 32ºCWB
-5 to 43ºCDB
-5 to 43ºCDB -25 to 15.5ºCWB -5 to 43ºCDB -25 to 15.5ºCWB
10 to 45ºC 10 to 45ºC 10 to 45ºC 10 to 45ºC 10 to 45ºC 10 to 45ºC 10 to 45ºC 10 to 45ºC
-20 to 15.5ºCWB -5 to 43ºCDB
Only standard
indoor units
-20 to 15.5ºCWB
Only standard indoor units
Cooling Heating
Outdoor temperature
Circulating water temperature
R2 series Y series HP series WR2 series WYseries
-5 to 43ºCDB -20 to 15.5ºCWB
-5 to 43ºCDB -20 to 15.5ºCWB
-5 to 43ºCDB -25 to 15.5ºCWB
10 to 45ºC 10 to 45ºC 10 to 45ºC 10 to 45ºC
3. Connectable outdoor unit/heat source unit capacity range
<PWFY-P100VM-E-BU>
Only PWFY
R2/WR2 series
*1 In case of WCB connection, the capacity range will be "50 to 130%".
50 to 100% 50 to 150%
PWFY with
standard indoor unit
*1
<PWFY-P100,200VM-E-AU>
Only PWFY
R2/WR2 series
Y/HP/WY series 50 to 100% 50 to 130% 50 to 130%
*1 In case of WCB connection, the capacity range will be "50 to 130%".
50 to 100% 50 to 150%
PWFY with
standard indoor unit
*1
<BC controller>
Connectable unit
CMB-P104/P105/106/107/1010/
1013/1016V-G
CMB-P108/1010/1013/1016V-GA
CMB-P1016V-HA PURY-P700-800YSHM-A(-BS)
CMB-P104/108V-GB, CMB-P1016V-HB CMB-P108/1010/1013/1016V-GA, CMB-P1016V-HA
PURY-(E)P200-350YHM-A(-BS)
PQRY-P200-300YHM-A
PURY-(E)P200-650Y(S)HM-A(-BS)
PQRY-P200-600Y(S)HM-A
<WCB>
Connectable unit
CMB-PW202V-J
PURY-(E)P200-350YHM-A(BS)
PQRY-P200-300YHM-A
Only standard
indoor units
50 to 150%
Only standard
indoor units
50 to 150%
*1
*1
- 1 -
II
Model
Power source
kWHeating capacity
*1 *1*1kcal / h(Nominal )
BTU / h kW A W.B
dB<A> mm(in.) mm(in.) mm(in.) mm(in.) mm(in.)
mm in. kg(lb)
kW
-
Power input
Liquid Gas
Current input Outdoor temp.
Inlet Water temp.
-Circulating Water temp.
Total capacity
Temp. range of heating
Connectable outdoor unit /heat source unit
Model / Quantity
Sound pressure level (measured in anechoic room) Diameter of refrigerant pipe Diameter of water pipe Field drain pipe size
External finish External dimension H × W × D
Net weight Compressor
Maker
Type
Starting method Motor output
Circulating water
Range Protection on Internal circuit (R134a)
High pressure protection
Inverter circuit (COMP)
Compressor
Type × original charge
Refrigerant
Control
R410a
Design pressure
R134a
Water
External
Drawing
Standard attachment
Optional parts
Remark
Note:
*1 Nominal heating conditions
<PURY-series>
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB)
kcal = kW × 860
Pipe length : 7.5 m (24-9/16 ft)
BTU/h = kW × 3,412
Level difference : 0m (0ft)
cfm = m3/min x 35.31
Inlet water Temp 65°C Water flow rate 2.15m3/h
<PQRY-series>
Circulating water Temp. : 20°C (68°F) Pipe length : 7.5 m (24-9/16 ft) Level difference : 0m (0ft) Inlet water Temp 65°C Water flow rate 2.15m3/h
lb = kg / 0.4536
* Due to continuing improvement, the above specifications may be subject to change without notice. * Install the unit in an environment where the
wet bulb Temp. will not exceed 32degC.
* The unit is not designed for outside installations. * Please don't use the steel material for the water piping material. * The water circuit must use the closed circuit.
* Please do not use it as a drinking water.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less. * Please always make water circulate or pull out the circulation water completely when not using it. * Please do not use groundwater and well water.
* The specification data is subject to rounding variation.
Unit converter
Lubricant
Operation volume
Inlet
Outlet
Accessory
Wiring
Document
m3/h
MPa MPa MPa
1.00
Installation Manual, Instruction Book
800 (785 without legs) × 450 × 300
E64C226X01
Inverter
1.0
Over-heat protection, Over-current protection
R134a × 1.1kg (0.50lb)
10,800
12.5
WKB94L762
NONE
44
NO
Strainer, Heat insulation material, 2 × Connector sets
PWFY-P100VM-E-BU
1-phase 220-230-240V 50/60Hz
PT3/4 Screw
MITSUBISHI ELECTRIC CORPORATION
NEO22
Φ32 (1-1/4'')
Inverter rotary hermetic compressor
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16”
60 (133)
PT3/4 Screw
11.63 - 11.12 - 10.66
50~100% of outdoor unit/heat source unit capacity
PURY-(E)P • Y(S)HM-A(-BS)
PQRY-P • Y(S)HM-A
Φ15.88 (Φ5/8") Brazed
-20~32°C (-4~90°F) PURY-series
10~45°C (50~113°F) PQRY-series
Φ9.52 (Φ3/8") Brazed
42,700
10~70°C (50~158°F)
2.48
0.6~2.15
LEV
4.15
High pressure sensor, High pressure switch at 3.60 MPa (601 psi)
Discharge thermo protection, Over-current protection
3.60
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
ProductSpecications
1.Specications
(1) PWFY-P100VM-E-BU
- 2 -
Model
Power source
kW*1Heating capacity kcal / h BTU / h kW A W.B
*1(Nominal)
*1 Power input Current input Outdoor temp.
Temp. range of
W.B
-
-
-
heating
Inlet Water temp.
Circulating Water temp.
kW*2Cooling capacity kcal / h BTU / h kW A D.B
*2(Nominal)
*2 Power input Current input Outdoor temp.
Temp. range of cooling
D.B
-Inlet Water temp. Total capacity Model / Quantity
Connectable outdoor unit /heat source unit
Sound pressure level (measured in anechoic room) dB<A>
mm(in.) mm(in.)
Diameter of refrigerant pipe
mm(in.) mm(in.)
Diameter of water pipe
mm(in.)
mm
Field drain pipe size
External finish External dimension H × W × D
in.
kg(lb)
Net weight Circulating water
Range
Design pressure
Water
R410a
Drawing
Standard attachment
Optional parts
Remark
Note:
*2 Nominal cooling conditions
*1 Nominal heating conditions
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB)
Outdoor Temp. : 35°CB (95°FDB)
kcal = kW × 860 BTU/h= kW × 3,412
Pipe length : 7.5 m (24-9/16 ft)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Level difference : 0m (0ft)
<PUHY/PURY-series>
<PUHY/PURY-series>
Circulating water Temp. : 20°C (68°F) Pipe length : 7.5 m (24-9/16 ft) Level difference : 0m (0ft)
<PQHY/PQRY-series>
<PQHY/PQRY-series>
cfm = m3/min × 35.31
Inlet water Temp 30°C
Water flow rate 2.15m3/h
Inlet water Temp 30°C
Water flow rate 2.15m3/h
Inlet water Temp 23°C
Water flow rate 1.93m3/h
Circulating water Temp. : 30°C (86°F) Pipe length : 7.5 m (24-9/16 ft) Level difference : 0m (0ft) Inlet water Temp 23°C
Water flow rate 1.93m3/h
* Install the unit in an environment where the
lb = kg / 0.4536
* Due to continuing improvement, the above specifications may be subject to change without notice.
wet bulb Temp. will not exceed 32degC. * The unit is not designed for outside installations. * Please don't use the steel material for the water piping material. * The water circuit must use the closed circuit. * Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less. * Please always make water circulate or pull out the circulation water completely when not using it.
Inlet Outlet
Operation Volume
Liquid Gas
m3/h
MPa
MPa
Accessory
External Wiring Document
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Unit converter
* The specification data is subject to rounding variation.
38,200
10~35°C (50~95°F)
0.015
Φ15.88 (Φ5/8") Brazed
Φ9.52 (Φ3/8") Brazed
PT3/4 Screw
Installation Manual, Instruction Book
PT3/4 Screw
NO
WKB94L763
0.068 - 0.065 - 0.063
50~100% of outdoor unit/heat source unit capacity
PUHY-(E)/(H)P • Y(S)HM-A(-BS)
PQHY-P • Y(S)HM-A
PURY-(E)P • Y(S)HM-A(-BS)
PQRY-P • Y(S)HM-A
-5~43°C (23~110°F) PURY - series
-5~43°C (23~110°F) PUHY - series
0.6~2.15
1.00
Strainer, Heat insulation material, 2 × Connector sets
Φ32 (1-1/4'')
PWFY-P100VM-E-AU
1-phase 220-230-240V 50/60Hz
9,600
11.2
29
12.5
800 (785 without legs) × 450 × 300
E00C223
4.15
NONE
10,800 42,700
-20~15.5°C (-4~60°F) PUHY - series 10~45°C (50~113°F) PQRY - series 10~45°C (50~113°F) PQHY - series
-
-
Circulating Water temp.
10~45°C (50~113°F) PQRY - series 10~45°C (50~113°F) PQHY - series
10~40°C (50~104°F)
0.015
0.068 - 0.065 - 0.063
-20~32°C (-4~90°F) PURY - series
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16”
35 (78)
* Please do not use it as a drinking water.
* Please do not use groundwater and well water.
(2) PWFY-P100VM-E-AU
- 3 -
Model
Power source
kW*1Heating capacity kcal / h BTU / h kW A W.B
*1(Nominal)
*1 Power input Current input Outdoor temp.
Temp. range of
W.B
-
heating
Inlet Water temp.
kW*2Cooling capacity kcal / h BTU / h kW A D.B
*2(Nominal)
*2 Power input Current input Outdoor temp.
Temp. range of cooling
D.B
-Inlet Water temp. Total capacity Model / Quantity
Connectable outdoor unit /heat source unit
Sound pressure level (measured in anechoic room) dB<A>
mm(in.) mm(in.)
Diameter of refrigerant pipe
mm(in.) mm(in.)
Diameter of water pipe
mm(in.)
mm
Field drain pipe size
External finish External dimension H × W × D
in.
kg(lb)
Net weight Circulating water
Range
Design pressure
Water
R410a
Drawing
Standard attachment
Optional parts
Remark
Note:
Inlet Outlet
Operation Volume
Liquid
Gas
m3/h
MPa
MPa
Accessory
External Wiring Document
Unit converter
*2 Nominal cooling conditions
*1 Nominal heating conditions
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB)
Outdoor Temp. : 35°CDB (95°FDB) Pipe length : 7.5 m (24-9/16 ft)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C Water flow rate 4.30m3/h Inlet water Temp 30°C Water flow rate 4.30m3/h
Inlet water Temp 23°C
Water flow rate 3.86m3/h
Inlet water Temp 23°C
Water flow rate 3.86m3/h
* Due to continuing improvement, the above specifications may be subject to change without notice.
* Install the unit in an environment where the wet bulb Temp. will not exceed 32degC.
* The unit is not designed for outside installations. * Please don't use the steel material for the water piping material. * The water circuit must use the closed circuit. * Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less. * Please always make water circulate or pull out the circulation water completely when not using it.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
10~40°C (50~104°F)
0.015
0.068 - 0.065 - 0.063
-20~32°C (-4~90°F) PURY - series
21,500 85,300
-20~15.5°C (-4~60°F) PUHY - series
E94C228X01
NONE
Φ32 (1-1/4'')
PWFY-P200VM-E-AU
1-phase 220-230-240V 50/60Hz
19,300
22.4
29
25.0
1.2~4.30
1.00
Strainer, Connecter, Heat insulation material, 2 × Connector sets, Expansion joint
PT 1 Screw
Installation Manual, Instruction Book
NO
WKB94L763
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16”
38 (84)
800 (785 without legs) × 450 × 300
4.15
0.015
Φ19.05 (Φ3/4") Brazed
Φ9.52 (Φ3/8") Brazed
PT 1 Screw
0.068 - 0.065 - 0.063
76,400
10~35°C (50~95°F)
50~100% of outdoor unit/heat source unit capacity
PUHY-(E)/(H)P • Y(S)HM-A(-BS)
PQHY-P • Y(S)HM-A
PURY-(E)P • Y(S)HM-A(-BS)
PQRY-P • Y(S)HM-A
-5~43°C (23~110°F) PURY - series
-5~43°C (23~110°F) PUHY - series
kcal = kW × 860
BTU/h = kW × 3,412
cfm = m3/min × 35.31 lb = kg / 0.4536 * The specification data is subject to rounding variation.
-
-
Circulating Water temp.
10~45°C (50~113°F) PQRY - series 10~45°C (50~113°F) PQHY - series
-
-
Circulating Water temp.
10~45°C (50~113°F) PQRY - series 10~45°C (50~113°F) PQHY - series
<PUHY/PURY-series>
<PUHY/PURY-series>
Circulating water Temp. : 20°C (68°F) Pipe length : 7.5 m (24-9/16 ft) Level difference : 0m (0ft)
<PQHY/PQRY-series>
<PQHY/PQRY-series>
Circulating water Temp. : 30°C (86°F) Pipe length : 7.5 m (24-9/16 ft) Level difference : 0m (0ft)
* Please do not use it as a drinking water.
* Please do not use groundwater and well water.
(3) PWFY-P200VM-E-AU
- 4 -
Model
Power source
Number of branch
Power input
Current
External finish
Connectable outdoor unit/heat source unit
Indoor unit capacity connectable to 1 branch
External dimension H x W x D
Field drain pipe size Net weight
Accessories
kW
A
kW
mm(in.)
mm(in.) mm(in.) mm(in.)
mm(in.)
kg(lb)
Refrigerant piping diameter
To outdoor unit /heat source unit
To indoor unit
High press. pipe Low press. pipe
Liquid pipe
Gas pipe
Note:
*1. Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items shall be referred to the Installation Manual. *2. The equipment is for R410A refrigerant. *3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away from any indoor units.) *4. Indoor units P100,P125,P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)
PURY-(E)P200/250/300/350YHM-A(-BS) / PQRY-P200/250/300YHM-A
Cooling : 0.067/0.076/0.085 Heating : 0.030/0.034/0.038
Cooling : 0.054/0.061/0.067 Heating : 0.024/0.027/0.030
Cooling : 0.31/0.34/0.36 Heating : 0.14/0.15/0.16
Cooling : 0.25/0.27/0.28 Heating : 0.11/0.12/0.13
Galvanized steel plate
(Lower part drain pan painting N1.5)
CMB-P104V-G
1N ~ 220/230/240V
50Hz 60Hz
24 (53) 27 (60)
4
Model P80 or smaller
(Use optional joint pipe combining 2 branches when the total capacity exceeds 81.)
(Use the reducer (standard accessory) when the indoor unit Model 50 or smaller is connected.)
O.D. 32mm (1-1/4)
284 x 648 x 432 (11-3/16 x 25-9/16 x 17-1/16)
Connectable outdoor unit capacity
ø19.05 (ø3/4) Brazed
ø9.52 (ø3/8) Flare
(ø6.35 (ø1/4) with attached reducer used, ø12.7 (ø1/2) with optional joint pipe used.)
·Drain Connection pipe (with flexible hose and insulation)
·Reducer
ø15.88 (ø5/8) Flare
(ø12.7 (ø1/2) with attached reducer used, ø19.05 (ø3/4) with optional joint pipe used.)
P200
ø15.88 (ø5/8) Brazed
ø22.2 (ø7/8) Brazed
P250/P300
ø19.05 (ø3/4) Brazed
ø28.58 (ø1-1/8) Brazed
P350
ø19.05 (ø3/4) Brazed
(4) CMB-P104V-G
Model
Power source
Number of branch
Power input
Current
External finish
Connectable outdoor unit
Connectable unit capacity
External dimension H x W x D
Field drain pipe size Net weight
Accessories
kW
A
Total Indoor / PWFY branch PWFY branch mm(in.)
mm(in.) mm(in.)
mm(in.)
mm(in.)
kg(lb)
Refrigerant piping diameter
To outdoor unit /heat source unit
To indoor/ PWFY unit
High press. pipe Low press. pipe
Liquid pipe
Gas pipe
Note:
*1. For installation/foundation work, electrical connection work, insulation work, and power source switch etc., refer to the Installation Manual. *2. The equipment is for R410A refrigerant. *3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background noise, position the Water system Connection Box at least 5m away from any indoor units.) *4. Install the unit horizontally. *5. The indoor / PWFY unit branch is for cooling / heating. The indoor / PWFY unit cannot be simultaneously operated in different operation modes. *6. The PWFY unit branch is for the heating only. *7. Seal the unused branch using the optional cover cap (CMY-S202-J).
PURY-(E)P200/250/300/350YHM-A (-BS)
PQRY-P200/250/300YHM-A
Cooling : 0.019/0.020/0.021 Heating : 0.020/0.022/0.024
Cooling : 0.018/0.019/0.019 Heating : 0.019/0.020/0.021
Cooling : 0.09/0.09/0.09 Heating : 0.10/0.10/0.10
Cooling : 0.09/0.09/0.09 Heating : 0.09/0.09/0.09
Galvanized steel plate
(Lower part drain pan painting N1.5)
CMB-PW202V-J
1N ~ 220/230/240V
50Hz 60Hz
20 (45)
2
O.D. 32mm (1-1/4" )
284 x 648 x 432 (11-3/16" x 25-9/16" x 17-1/16" )
50% ~ 130% of outdoor unit/heat source unit
up to 130% of outdoor unit/heat source unit
up to 100% of outdoor unit/heat source unit
Total down-stream Indoor unit capacity
Connectable outdoor unit capacity
ø19.05 (ø3/4" ) Brazed
·Drain Connection pipe (with flexible hose and insulation)
·Refrigerant connection pipe
P200
ø15.88 (ø5/8" ) Brazed
ø15.88 (ø5/8" )
Brazed
~P140
ø9.52 (ø3/8" )
Brazed
ø19.05 (ø3/4" )
Brazed
P141~P200
ø9.52 (ø3/8" )
Brazed
ø22.2 (ø7/8" )
Brazed
P201~P300
ø9.52 (ø3/8" )
Brazed
ø28.58 (ø1-1/8" )
Brazed
P301~P400
ø12.70 (ø1/2" )
Brazed
ø28.58 (ø1-1/8" )
Brazed
P401~
ø15.88 (ø5/8" )
Brazed
ø22.2 (ø7/8" ) Brazed
P250/P300
ø19.05 (ø3/4" ) Brazed
ø28.58 (ø1-1/8" ) Brazed
P350
ø19.05 (ø3/4" ) Brazed
*Other models of BC controller are available. For unit information, refer to the Data Book.
(5) CMB-PW202V-J
- 5 -
2.ExternalDimensions
Piping space
(right side)
Fig. A
Service space
(front side)
Top view
300
400
600
ø27 Knockout hole
<Hole for external wiring output>
Drain (R1 screw)
Control box
Water outlet
(RC3/4 screw)
ø27 Knockout hole
<Hole for external wiring input>
ø27 Knockout hole
<Hole for power supply>
ø27 Knockout hole
<Hole for control wiring>
Service panel
Top view
Right side view
Front view
2X2-ø14 Hole
Connection pipe of outdoor unit
(Liquid)
ø15.88 <Brazed>
ø9.52 <Brazed>
Connection pipe of outdoor unit
(Gas)
Water inlet
(R3/4 screw)
525
(Mounting pitch)
(Mounting pitch)
205
800 300
450
500
55
35
35
91
91
134
480
46
60140
100191
80165
102
54
184
114
Note 1.Ensure no rain water or debris can enter the unit through any gaps around
wiring or piping.
2.Ensure adequate service space is right around the unit, according to Fig A.
3.Please always make water circulate or add the brine to the circulation water
when the ambient temperature becomes 0°C or less.
4.The unit is not designed for outside installations.
5.Install the unit in an environment where the wet bulb Temp.
will not exceed 32degC.
6.Please always make water circulate or pull out the circulation
water completely when not using it.
7.The water circuit must use the closed circuit.
8.Please don't use the steel material for the water piping material.
9.Connect the strainer which is put as accessory to water inlet pipe.
<Accessories>
●Y-type strainer (RC3/4) ·························· 1pc.
●Heat Insulation material ························· 1pc.
●Connector set ········································ 2set
<Unit:mm>
(1) PWFY-P100VM-E-BU
- 6 -
(2) PWFY-P100, 200VM-E-AU
300600
Fig. A
Service space
(front side)
Top view
400
Piping space
(right side)
P200:Use the Expansion joint
of accessories
Drain (R1 screw)
ø9.52 <Brazed>
ø27 Knockout hole
<Hole for control wiring>
ø27 Knockout hole
<Hole for power supply>
Water outlet
(RC3/4 screw)
Water inlet
(R3/4 screw)
P100:ø15.88 <Brazed>
P200:ø19.05 <Brazed>
ø
27 Knockout hole
<Hole for external wiring input>
ø27 Knockout hole
<Hole for external wiring output>
Connection pipe of outdoor unit
(Gas)
Connection pipe of outdoor unit
(Liquid)
Front view
Right side view
Control box
Service panel
Top view
2X2-ø14 Hole
525
(Mounting pitch)
450
(Mounting pitch)
300800
205
500
<Accessories>
●Y-type strainer (RC3/4) ····························· 1pc.
●Heat Insulation material
····························
1pc.
●Connector set
············································
2set
●Expansion joint (P200) ······························ 2pcs.
[From RC3/4 to RC1]
Note 1.Ensure no rain water or debris can enter the unit through any gaps around
wiring or piping.
2.Ensure adequate service space is right around the unit, according to Fig A.
3.Please always make water circulate or add the brine to the circulation water
when the ambient temperature becomes 0°C or less.
4.The unit is not designed for outside installations.
5.Install the unit in an environment where the wet bulb Temp.
will not exceed 32degC.
6.Please always make water circulate or pull out the circulation
water completely when not using it.
7.The water circuit must use the closed circuit.
8.Please don't use the steel material for the water piping material.
9.Connect the strainer which is put as accessory to water inlet pipe.
91
91
35
55
35
480102
206
134
114
100191
46
6014080165
54
<Unit:mm>
- 7 -
<Accessories>
• Refrigerant<Low pressure> conn. pipe ··············· 2pcs.
• Refrigerant<High pressure> conn. pipe ·············· 1pc.
• Reducer(Large,Small) ········································· Quantity for all connections
• Drain hose I.D. 32 (1-1/4") ··································· 1pc.
• Hose band ··························································· 1pc.
• Tie band ······························································ 1pc.
Note1. Suspension bolt(
ø10),washer(M10),and nut(M10)
prepare in the field.
2. Take notice of service space as follows.
(Please give attention not to occupy service
space by letting ducts and pipes through.)
PURY-P200 : ø
19.05 <Brazed> (use attachment pipe)
PURY-P250, P300 :
ø
22.2 <Brazed>
PURY-P350 :
ø
28.6 <Brazed> (use attachment pipe)
Service
space
ø19.05 <Brazed>
Detail of X section
Detail of Y section
Control box
12
14
30
Drain pipe O.D. 32 (1-1/4")
B
A
Connection pipe of outdoor unit (Low pressure)
103
Connection pipe of
outdoor unit
(High pressure)
248
ø31
A B C D
ø9.52 <Flare>
161514
1312
11
109
876543
2
1
ø15.88 <Flare>
Access
door
450
(Lifting bolt pitch)
(Lifting bolt pitch)
345
7
9
12
15
180
240
300
420
540
720
900
702
1152
648
1098
CMB-P104V-G
CMB-P105V-G
CMB-P108V-G
CMB-P106V-G
CMB-P1010V-G
CMB-P1016V-G
CMB-P1013V-G
298
181
200
130 23
60
Y
362 70
Drain hose I.D. 32 (1-1/4")
Band (Accessory)
X
70
200
27
700
250
Connection pipe of
indoor unit (Gas)
Connection pipe of
indoor unit (Liquid)
64
64
58
128
255
284
200
60XC=D76
<Unit:mm>
(3) CMB-P104,105,106,108,1010,1013,1016V-G
- 8 -
(4) CMB-PW202V-J
Connection pipe of
PWFY (Gas)
Connection pipe of
PWFY (Liquid)
Connection pipe of
indoor unit/PWFY (Liquid)
Connection pipe of
indoor unit/PWFY (Gas)
Liquid line
Indoor unit/PWFY
(Cooling/Heating)
PWFY(Heating only)
Gas line
Liquid line
Gas line
(Lifting bolt pitch)
(Lifting bolt pitch)
250
700
200
200
Access
door
450
~P300: ø9.52<Brazed>(use attachment pipe)
P301~P400: ø12.7<Brazed>(use attachment pipe)
P401~: ø15.88<Brazed>
~P140: ø15.88<Brazed>(use attachment pipe)
P141~P200: ø19.05<Brazed>(use attachment pipe)
P201~P300: ø22.2<Brazed>(use attachment pipe)
P301~: ø28.58<Brazed>(use attachment pipe)
~P140: ø15.88<Brazed>(use attachment pipe)
P141~P200: ø19.05<Brazed>
P201~P300: ø22.2<Brazed>(use attachment pipe)
~P300: ø9.52<Brazed>
Drain hose(Accessory)
Band(Accessory)
Connection pipe of outdoor unit (Low pressure)
Connection pipe of outdoor unit (High pressure)
12
14
30
ø
31
27
Y
X
Dtail of Y section
284
648
90
Drain piping
VP-25 connection
Control box
200
255
Detail of X section
298
702
190423
300
252
103
58
90
127 21
90 181
255
70362
103
PURY-P200: ø19.05<Brazed>(use attachment pipe)
PURY-P250,P300: ø22.2<Brazed>
PURY-P350: ø28.58<Brazed>(use attachment pipe)
PURY-P200: ø15.88<Brazed>(use attachment pipe)
PURY-P250,P300,P350: ø19.05<Brazed>
<Accessories>
Refrigerant<Low pressure> conn. pipe
Refrigerant<High pressure> conn. pipe
Refrigerant<Gas> conn. pipe
Refrigerant<Liquid> conn. pipe
Drain hose(VP-25 connection)
Hose band
Tie band
2pcs.
1pc.
6pcs.
2pcs.
1pc.
1pc.
1pc.
Note1. Suspension bolt (ø10), washer (M10), and nut (M10)
prepare in the field.
2. Take notice of service space as follows.
(Please give attention not to occupy service
space by letting ducts and pipes through.)
3. Install this product in a location where noise (refrigerant noise)
emitted by the unit will not disturb the neighbors.
(For use in quiet enviroments with low background noise, position
the BC CONTROLLER at least 5m away from any indoor units.)
4. Install the unit horizontally.
5. The indoor unit/PWFY branch is for cooling/heating.The indoor unit/PWFY
cannot be simultaneously operated in different operation modes.
6. The PWFY unit branch is for the heating only.
Service
space
<Unit:mm>
- 9 -
3.ElectricalWiringDiagrams
M
4-20mA
4-20mA
gray
2
1
gray
black
To outdoor unit/
BC controller/WCB
To MA remote
controller
Power Supply
~220/230/240V
50Hz/60Hz
3
2
1
blue
red
yellow/green
bluered
CN4
63LS
CN63HS
1
1
3
2
2
3
THHS
12
CN63LS
123
TH8
2
1
CN403
red
TH6
1 2
CN404
black
3 1
CT1
Moter
3~
CYN
RS4
MS
RS3
(Compressor)
CN3A
blue
U
red
yellow
TH22
CN405
IPM
W
V
U
black
1
63HS
7
2
1
3
1
2
CN3
2
1
CN401
CN2
2 5 6
red
CN5
2 1
TH11
1 2
TH13
2
1
white
CN402
green
red
5
6
RS1
black
2
CN52C
R1
LO
U
CNAC2
red
2
CN5
1
1
2
red
blue
red
LEV2W
M
LI
24V
blue
+
CB3
Z2
1
U
CT1
LEV1W
1
CN2
63H1
6
5
CNAC
2
red
1
CX2
L
CN506A
L3
N
6
5
N
CN-E1
CN631
DSA
pink
E2
3
1
E1
432
1
CY4
P
CY3
31
L4
Z1
NI
CB1
+
1
TB2
CN661
2L23
X506
W
4
CN4
blue
U
CN52C
1 2
+
CX3
INV control
circuit
PFC
E3
1
L1
2
M
ZNR01
ACL
CY1CY2
CT2
Noise
Filter
red
Fan motor
1
3
(DC)
CX5
CYP
CIS
CX6
1 2
7
V
yellow
LED3:Lit when powered
INV Board
Control Board
CB2
(DC)
CY6
S
CX4
R
CNAC1
M
CNLVA
NO
Fan motor
3
1 2
RS2
CY5
P
CNLVB
blue
CX1
CX7
CN506B
CPS
+
RS
F01
AC250V
6.3A
F631
DC700V
4A
Power
Supply circuit
blue
red
TB5
M1 M2
S(SHIELD) S(SHIELD)
TB15
yellow
purple
black
orange
gray
red
black
white
gray
gray
52C
1 2
CN2M
blue
3 1
*4
IN2
TB141B
TB142B
IN6
COM+
OUT5
TB142C
OUT7
OUT6
X515 X517
X516
IN8
IN5 IN7
TB142A
X514
OUT2
X512
X511 X513
OUT1 OUT3
OUT4
TB141A
*5 *6 *7
IN3 IN4
COM+
LED4:Remote controller
when powered
SWU1
10
SW1
5
ON
OFF
1
Unit address setting(SWU1,SWU2)
Connection No.(SWU3)
LED1 Display setting(SW2)
Function setting(SW1,SW3,SW4)
SWP3
SW5
SWP1
SWU3
SWP2
SWU2
OFF
ON
1 10
SW4
OFF
ON
1 10
LED1
OFF
ON
1
SW3
OFF
ON
1 10
SW2
IN1
gray
CN421
black
3 1
CN422
blue
IN1
IN2
3 1
CN421
black
3 1
CN422
blue
2
2
2
2
BC controller/WCB/outdoor unit
Booster unit
Linear
expansion valve
LEV1W
LEV2W
IN7 Anti-freeze
IN6 Heating ECO
Symbol
Function
COM+ Common
IN5 Hot water
IN4 Operation ON/OFF
Connection demand
Symbol
IN3
Function
Symbol
Pump interlock
Function
IN1
*4 TB141A(output)
*5 TB142A(input)
*6 TB142B(input)
*7 TB142C(input)
Function
Symbol
OUT1 Operation ON/OFF
OUT2 Defrost
OUT3 Compressor
OUT4 Error signal
<HIGH VOLTAGE WARNING>
·Control box houses high-voltage parts.
Before inspecting the inside of the control box, turn off the power,
keep the unit off for at least 10 minutes,and confirm that the voltage
CN631 on Control Board has dropped to DC20V or less.
<CAUTION FOR INSTALLATION>
·Prior to installation,read the Installation Manual carefully.
*1.Single-dotted lines indicate wiring not supplied with the unit.
*2.Dot-dash lines indicate the control box boundaries.
*3.Faston terminals have a locking function.
Make sure the terminals are securely locked in place after insertion.
Press the tab on the terminals to removed them.
TH8 water outlet temp
TH6 water inlet temp
TH22 liquid pipe temp
TH13 Evaporator outlet temp
Compressor discharge tempTH11 Thermistor
TB15 MA remote controller
TB5 Outdoor unit/BC controller/WCB
AC reactor
Pressure
switch
High pressure switch
(High pressure protection for the booster unit)
Discharge pressure
Low pressure
TB2
CT1,CT2
ACL
THHS
Magnetic relay(main circuit)
Current sensor(AC)
Explanation
Terminal
block
Power supply
IGBT temp
Pressure
sensor
Symbol
63H1
63HS
63LS
52C
<Symbol explanation>
(1) PWFY-P100VM-E-BU
- 10 -
(2) PWFY-P100, 200VM-E-AU
gray
red
M
For opening/closing the bypass circuit
Solenoid valve
SV1
IN1
TB5
M1 M2
S(SHIELD)
To outdoor unit/
BC controller/
WCB
4-20mA
4-20mA
132
CN421
black
132
CN422
blue
132
CN422
blue
2
black
CN421
13
IN1
234
5
yellow/green
LEV1Wa
LEV1Wb
Linear
expansion valve
BC controller/WCB/outdoor unit
BC controller/WCB/outdoor unit
Function
Function
Function
black
yellow purple
bluered
NL
IN7
IN8IN6
IN5COM+
IN4IN3
orange
*3.Difference of appliance
*4 TB141A(output)
*5 TB142A(input)
*6 TB142B(input)
*7 TB142C(input)
Model name
Appliance
P100 *3 do not exist
P200 *3 exist
*7*6*5
*4
Cooling
TH23 gas pipe temp
CN502
black
COM+
TH8
TH6
TH23
blue
CN2M
2
1
2
1
CN402
green
2
1
CN403
red
1 2
CN404
black
yellow
CN405
TH22
1 2
21
To MA remote
controller
Power Supply
~220/230/240V
50Hz/60Hz
Unit address setting(SWU1,SWU2)
Connection No.(SWU3)
LED1
TB15
ZNR1
U
DSA1
CN1
1
3
SWU2
SWU1
SWP3
SWP2
SWP1
OFF
ON
1 10
SW4
OFF
ON
1 10
SW3
OFF
ON
1 10
SW1
OFF
ON
1 10
SW2
LED4:Remote controller
when powered
5
CNLVC
6
1
LEV1Wb
123
4
X502
CN507
3
1
M
5
6
ON
OFF
1
SW5
SWU3
LED3:Lit when powered
Control Board
CNLVB
LEV1Wa
TB2
SV1
*3
DSA Board
CN3T
red
13
T01
ZNR01
3
1
1
2
CNAC
red
U
F01
AC250V
6.3A
LED1 Display setting(SW2)
Function setting(SW1,SW3,SW4)
OUT4
OUT3
OUT2
X514
X513
X512
TB141A
OUT1
X511
3 1
CN3A
blue
TB142CTB142B
X516
X517X515
OUT6
OUT7OUT5
TB141B
TB142A
IN2
IN8
IN7 Anti-freeze
IN6 Heating ECO
Symbol
COM+ Common
IN5 Heating
IN4 Operation ON/OFF
Connection demand
Symbol
IN3
Symbol
Pump interlockIN1
Function
Symbol
OUT1 Operation ON/OFF
OUT2 Defrost
OUT4 Error signal
<CAUTION FOR INSTALLATION>
·
Prior to installation,read the Installation Manual carefully.
*1.Single-dotted lines indicate wiring not supplied with the unit.
*2.Dot-dash lines indicate the control box boundaries.
TH8 water outlet temp
TH6 water inlet temp
TH22 liquid pipe temp
Thermistor
TB15 MA remote controller
TB5 Outdoor unit/WCB/BC controller
TB2
Explanation
Terminal
block
Power supply
Symbol
<Symbol explanation>
- 11 -
(3) CMB-P104V-G
CONT.B
Pressure sensor
TR
TH11,12,15,16
LEV1,3
PS1,3
Symbol Name
Transformer
Thermistor sensor
Expansion valve
SV1
~
4A,B,C Solenoid valve
TB01
Terminal block
(for power source)
TB02
Terminal block
(for Transmission)
T1~4 Terminal
F01
Fuse AC250V 6.3A F
Solenoid valve
SVM1
TR
TB02
CN26
3
1
CN12
1
5
3
CN05
6 5 4 3 2 1
CONT.B
1
2
CN02
3
CNP1
1
2
3
CNP3
211
2
3
4
567
8
4
3
2
1
123 2 1
CN03
CN13
CN10
CN11
CN07
TH11
TH12
TH15
TH16
PS1
PS3
6 5 4 3 2 1
TB01
1VEL
3 VEL
S(SHIELD)
M2
M1
220V~240V
20V
~
22V
L
1
234
10
9
8
423
10
2
143
SV3A
SV3B
SV2B
SV3C
SV2C
SV2A
243
756
4
3
2
1
2
3
4
1
234
2
3
4
9
8
7
6
5
SV1C
SV1A
SV1B
7
5
3
1
7
5
3
1
7
5
3
1
X2
X1
X30
X4
X3
X31
X6
X5
X32
CN27(Red)
CN28(Blue)
1
1
1
1
234
13
12
11
16
15
14
13
12
11
SV4B
SV4C
SV4A
15
16
14
1
2
3
4
1
7
5
3
1
X8
X7
X33
CN29(Green)
SVM1
123
1
2
3
1
3
CN36(Green)
X21
N
ZNR01
ZNR02
CNTR
(Red)
2
2
PE
3
1
3
1
T2
T3
T1
T4
PE
TO NEXT INDOOR UNIT
PULL BOX
FUSE(16A)
BREAKER(16A)
POWER SUPPLY
~220V-240V
50Hz/60Hz
Indoor/outdoor
Transmission Line
ON
OFF
1
SW5
OFF
8
SW4
ON
1
8
BC controller
Circuit
board
SW2 SW1
1
10
F01
250VAC
6.3A F
(Black)
(Red)
(Yellow)
(Red)
(Yellow)
DSA
Note:1.TB02 is transmission terminal block.
Never connect power line to it.
2.The initial set values of switch on
CONT.B are as follows.
SW1:0
SW2:0
Symbol explanation
*Other models of BC controller are available. For unit information, refer to the Data Book.
- 12 -
(4) CMB-PW202V-J
TB01
M1
M2
WCB Board
Note:1. TB02 is transmission terminal block.
Never connect power line to it.
2. The initial set values of switch on
WCB Board are as follows.
SW1:0
SW2:0
Expansion valve
Thermistor sensor
Transformer
(Symbol explanation)
Name
Symbol
TB01
Terminal block
(for power source)
Terminal block
(for Transmission)
TB02
Solenoid valve
SVM1
21S4a
4-way valve
TO NEXT
INDOOR UNIT
PULL BOX
FUSE(16A)
BREAKER(16A)
50Hz/60Hz
POWER SUPPLY
~220V-240V
S(SHIELD)
TB02
Indoor/outdoor
Transmission line
1
2
3
6
5
4
CN05
CN07
1
2
3
6
5
4
TH16
TH15
123
4
CN11
TH12
TH11
112
CN13
2
3
CN10
45678
F01
AC250V
6.3A F
ZNR01
ZNR02
CN12
1
3 5
1
3
20V~22V
TR
220V~240V
1 13 2 2
CN02
CN03
F01
Fuse AC250V 6.3A F
TH13
TH14
TR
TH11~16
LEV1,3
Yellow
Red
Red
Yellow
SW1SW2
ON
OFF
ON
OFF
ON
OFF
81
81
81
SW4
SW5
SW6
1
3
X02
CN26
5
7
X01
SVM1
21S4a
123
4
4
3
2
1
1132
4
324
T1
CNTR
Red
N
L
DSA
UU
LEV3
LEV1
M
M
LD1:CPU in
operation
1's
digit
Unit address
setting
10's
digit
Function
setting
317
5
- 13 -
4. Accessories
(A) Strainer (B) Heat insulation material
*1
*1. PWFY-P200VM-E-AU only
(C) Connecter sets 2 (D) Expansion joint 2
(1) PWFY
(A) Install the strainer at the water pipe inlet. (B) This insulation is for exclusive use with the strainer. Wrap the strainer with the insulation after water pipes are
installed. (C) These are analog input connectors. Cut the wire before using.
(D) Supplied only with the PWFY-P200VM-E-AU. Install them at the strainer inlet. Refer to P53 for details.
(2) CMB-P104V-G
SIZE Unit
ø15.88 are - IDø12.8 4
ø9.52 are - IDø6.45 4
ODø19.05 - IDø15.88 1
ODø22.2 - IDø19.05 1
ODø22.2 - IDø28.6 1
Drain hose set
Installation Manual 1
1set
(3) CMB-PW202V-J
SIZE Unit
ODø19.05 - IDø15.88 2
ODø22.2 - IDø19.05 1
ODø15.88 - IDø9.52 1
ODø15.88 - IDø12.7 1
ODø25.4 - IDø19.05 1
ODø25.4 - IDø22.2 1
ODø19.05 - IDø22.2 1
ODø25.4 - IDø28.6 1
ODø22.2 - IDø28.6 1
ODø25.4 - IDø15.88 1
Drain hose set
Installation Manual 1
1 set
- 14 -
III
PURY- P200,250YHM-A(-BS)
EP200,250YHM-A(-BS)
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of heating capacity
30°C
20°C
10°C
40°C
50°C
60°C
65°C
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of booster unit input
65°C
60°C
50°C
40°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
50°C
60°C
65°C
30°C
20°C
10°C
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15
-10 -5
0
5
10
15 20 25 30
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Product Data
1. Capacity tables
(1) Correction by temperature
(1)-1 R2 series + PWFY-P100VM-E-BU
- 15 -
PURY- P300,350,400YHM-A(-BS) EP300,400Y(S)HM-A(-BS)
Outdoor temp. [°CWB]
Ratio of heating capacity
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of booster unit input
65°C
60°C
50°C
40°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
50°C
60°C
65°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
30°C
20°C
10°C
40°C
50°C
60°C
65°C
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
- 16 -
30°C
20°C
10°C
40°C
50°C
60°C
65°C
PURY-
P450,500,550,600,650YSHM-A(-BS) EP450,500,550,600YSHM-A(1)(-BS)
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of heating capacity
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of booster unit input
65°C
60°C
50°C
40°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
50°C
60°C
65°C
30°C
20°C
10°C
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
- 17 -
PURY- P700,750,800YSHM-A(-BS)
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Ratio of heating capacity
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Ratio of booster unit input
65°C
60°C
50°C
40°C
30°C
20°C 10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Ratio of outdoor unit input
40°C
50°C
60°C
65°C
30°C
20°C
10°C
Outdoor temp. [°CWB]
Outdoor temp. [°CWB]
Outdoor temp. [°CWB]
30°C
20°C
10°C
40°C
50°C 60°C
65°C
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
- 18 -
PURY- P200,250YHM-A(-BS) EP200,250YHM-A(-BS)
Outdoor temp. [°CWB]
Ratio of heating capacity
0.2
0.4
0.6
0.8
1.0
1.2
Outdoor temp. [°CWB]
Ratio of booster unit input
65°C 60°C
50°C
40°C
30°C
20°C
10°C
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
50°C
60°C 65°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
30°C
20°C
10°C
40°C 50°C
60°C 65°C
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
(1)-2 R2 series + PWFY-P100VM-E-BU + WCB Energy saving mode*
*For energy saving mode, set WCB DIP SW 6-5 ON.
- 19 -
PURY- P300,350YHM-A(-BS) EP300YHM-A(-BS)
Outdoor temp. [°CWB]
Ratio of heating capacity
0.2
0.4
0.6
0.8
1.0
1.2
Outdoor temp. [°CWB]
Ratio of booster unit input
65°C 60°C
50°C
40°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
50°C
60°C 65°C
30°C
20°C 10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
30°C
20°C
10°C
40°C 50°C
60°C 65°C
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
- 20 -
(1)-3 WR2 series + PWFY-P100VM-E-BU
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Heat source unit (WR2) inlet-water temp. [°C]
Ratio of Heat source unit input
40°C
50°C
60°C
65°C
10°C
30°C 20°C
0.2
0.0
0.4
0.6
0.8
1.0
1.2
1.4
Heat source unit (WR2) inlet-water temp. [°C]
Ratio of Booster unit input
40°C
30°C
20°C
10°C
50°C
60°C
65°C
0.7
0.8
0.9
1.0
1.1
1.2
Heat source unit (WR2) inlet-water temp. [°C]
Ratio of Booster unit capacity
40°C
50°C
10°C
10
15 20 25 30 35 40 45
0.7
0.8
0.9
1.0
1.1
1.2
10
15 20 25 30 35 40 45
10
15 20 25 30 35 40 45
60°C
65°C
30°C 20°C
PQRY- P200,250,300,400,450,500,550,600Y(S)HM-A
- 21 -
(1)-4 WR2 series + PWFY-P100VM-E-BU + WCB Energy saving mode*
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Booster unit inlet-water temp. [°C]
Heat source unit (WR2) inlet-water temp. [°C]
Ratio of Heat source unit input
40°C
50°C
60°C
65°C 10°C
30°C 20°C
0.2
0.0
0.4
0.6
0.8
1.0
1.2
1.4
Heat source unit (WR2) inlet-water temp. [°C]
Ratio of Booster unit input
40°C
30°C
20°C
10°C
50°C
60°C
65°C
0.7
0.8
0.9
1.0
1.1
1.2
Heat source unit (WR2) inlet-water temp. [°C]
Ratio of Booster unit capacity
40°C
50°C
60°C
65°C
30°C 20°C
10°C
10
15 20 25 30 35 40 45
10
15 20 25 30 35 40 45
10
15 20 25 30 35 40 45
0.6
0.5
0.7
0.8
0.9
1.0
1.1
1.2
PQRY- P200,250,300,400,450,500,550,600Y(S)HM-A
*For energy saving mode, set WCB DIP SW 6-5 ON.
- 22 -
(1)-5 Y series + PWFY-P100,200VM-E-AU
PUHY- P200,250YHM-A(-BS) EP200,250YHM-A(-BS)
Heating
Cooling
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.2
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Outdoor temp. [°CWB]
Ratio of heating capacity
10°C 20°C 30°C
35°C
40°C
10°C
20°C
30°C
35°C
40°C
HEX unit inlet-water temp. [°C]
HEX unit inlet-water temp. [°C]
HEX unit inlet-water temp. [°C]
HEX unit inlet-water temp. [°C]
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
Outdoor temp. [°CDB]
Ratio of cooling capacity
35°C
30°C 25°C
20
°C
15°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Outdoor temp. [°CDB]
Ratio of outdoor unit input
35°C 30°C 25°C 20°C 15°C
10
°C
-20
-15
-10 -5
0
5
10
15
-20
-15
-10 -5
0
5
10
15
-5
0
5
10
15
20
25
30
35
40
-5
0
5
10
15
20
25
30
35
40
- 23 -
Loading...
+ 71 hidden pages