- If a different refrigerant or air is mixed with the origi
nal refrigerant, the refrigerant cycle may malfunction
and the unit may be damaged.
• If the air conditioner is installed in a small room,
measures must be taken to prevent the refriger
ant concentration from exceeding the safety limit
even if the refrigerant should leak.
- Consult the dealer regarding the appropriate meas
ures to prevent the safety limit from being exceeded.
Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of oxygen
in the room could result.
• When moving and reinstalling the air conditioner,
consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water
leakage, electric shock, or re may result.
- i -
• After completing installation work, make sure that
refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan
heater, stove, oven, or other heat source, it may gen
erate noxious gases.
• Do not reconstruct or change the settings of the
protection devices.
- If the pressure switch, thermal switch, or other
protection device is shorted and operated forcibly,
or parts other than those specied by Mitsubishi
Electric are used, re or explosion may result.
• To dispose of this product, consult your dealer.
• The installer and system specialist shall secure
-
safety against leakage according to local regula
tion or standards.
- Following standards may be applicable if local regu
lation are not available.
• Pay a special attention to the place, such as a
basement, etc. where refrigeration gas can stay,
since refrigeration is heavier than the air.
-
-
• Do not use the existing refrigerant piping.
- The old refrigerant and refrigerant oil in the existing
piping contains a large amount of chlorine which
may cause the refrigerant oil of the new unit to dete
riorate.
- R410A is a high-pressure refrigerant and can cause
the existing piping to burst.
• Use refrigerant piping made of C1220 (CU-DHP)
phosphorusdeoxidizedcopperasspeciedinthe
JIS H3300 “Copper and copper alloy seamless
pipes and tubes”. In addition, be sure that the in
ner and outer surfaces of the pipes are clean and
free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping
may cause the refrigerant residual oil to deteriorate.
• Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Store elbows and other
joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle,
deterioration of the oil and compressor trouble may
result.
- The inverter equipment, private power generator,
high-frequency medical equipment, or radio commu
nication equipment may cause the air conditioner to
operate erroneously, or fail to operate. On the other
hand, the air conditioner may affect such equipment
by creating noise that disturbs medical treatment or
image broadcasting.
• Do not install the unit on a structure that may
cause leakage.
- When the room humidity exceeds 80 % or when the
drain pipe is clogged, condensation may drip from
the indoor unit. Perform collective drainage work
together with the unit, as required.
-
-
- iii -
• Groundtheunit.
- Do not connect the ground wire to gas or water
pipes, lightning rods, or telephone ground lines.
Improper grounding may result in electric shock.
• Install the power cable so that tension is not
applied to the cable.
- Tension may cause the cable to break and generate
heat and cause a re.
• Install a leak circuit breaker, as required.
- If a leak circuit breaker is not installed, electric shock
may result.
• Usepowerlinecablesofsufcientcurrent
carrying capacity and rating.
- Cables that are too small may leak, generate heat,
and cause a re.
• Use only a circuit breaker and fuse of the
speciedcapacity.
- A fuse or circuit breaker of a larger capacity or a
steel or copper wire may result in a general unit
failure or re.
• Do not wash the air conditioner units.
- Washing them may cause an electric shock.
• Be careful that the installation base is not
damaged by long use.
- If the damage is left uncorrected, the unit may fall
and cause personal injury or property damage.
• Install the drain piping according to this
InstallationManualtoensureproperdrainage.
Wrap thermal insulation around the pipes to
prevent condensation.
- Improper drain piping may cause water leakage and
damage to furniture and other possessions.
• Be very careful about product transportation.
- Only one person should not carry the product if it
weighs more than 20 kg.
- Some products use PP bands for packaging. Do not
use any PP bands for a means of transportation. It
is dangerous.
- When transporting the unit, support it at the
specied positions on the unit base. Also support the
unit at four points so that it cannot slip side ways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or
wooden parts, may cause stabs or other injuries.
- Tear apart and throw away plastic packaging bags
so that children will not play with them. If children
play with a plastic bag which was not torn apart,
they face the risk of suffocation.
- iv -
• Turn on the power at least 12 hours before
starting operation.
- Starting operation immediately after turning on the
main power switch can result in severe damage
to internal parts. Keep the power switch turned on
during the operational season.
• Donottouchtheswitcheswithwetngers.
- Touching a switch with wet ngers can cause elec
tric shock.
• Do not touch the refrigerant pipes during and im
mediately after operation.
- During and immediately after operation, the
refrigerant pipes are may be hot and may be cold,
depending on the condition of the refrigerant owing
through the refrigerant piping, compressor, and
other refrigerant cycle parts. Your hands may suffer
burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels
and guards removed.
- Rotating, hot, or high-voltage parts can cause
injuries.
-
• Do not turn off the power immediately after
stopping operation.
- Always wait at least ve minutes before turning off
the power. Otherwise, water leakage and trouble
may occur.
• Do not touch the surface of the compressor
during servicing.
- If unit is connected to the supply and not running,
crank case heater at compressor is operating.
-
• Do not touch the panels near the fan exhaust
outletwithbarehands:theycangethotwhile
the unit is in operation (even if it is stopped) or
immediately after operation and poses a risk of
burns. Wear gloves to protect your hands when it
is necessary to touch the panels.
• While the unit is in operation or immediately after
operation, high-temperature exhaust air may blow
out of the fan exhaust outlet. Do not hold your
hands over the outlet or touch the panels near the
outlet.
• Be sure to provide a pathway for the exhaust air
from the fan.
• Water pipes can get very hot, depending on the
preset temperature. Wrap the water pipes with
insulating materials to prevent burns.
- v -
Contents
Safety Precautions
IGeneralEquipmentDescriptions
1. Unit conguration table ············································ 1
2. Operable temperature range ··································· 1
3. Connectable outdoor unit capacity range ················
Outdoor unit will change its software to PWFY connection version automatically when PWFY is connected.
R2 series allow higher temperature range than Y series, the reason is that R2 has an effective heat exchanger
bypass circuit against Hi-cut.
(WB)
<PWFY-P100, P200VM-E-AU>
<PWFY-P100VM-E-BU>
10 to 35˚C
10 to 35˚C
Inlet water temperature
R2 series
Y series
Heating
PWFY with standard indoor units
10 to 40˚C
10 to 40˚C
-5 to 43˚C
-5 to 43˚C
R2 series
Y series
Outdoor temperature
-20 to 32˚C
-20 to 15.5˚C
Only PWFY
(WB)
Cooling
10 to 35˚C
10 to 35˚C
Heating
10 to 40˚C
10 to 40˚C
-5 to 43˚C
-5 to 43˚C
-20 to 32˚C
-20 to 15.5˚C
Cooling
-
-
Inlet water temperature
R2 series
Y series
Heating
-
-
-5 to 43˚C
-5 to 43˚C
R2 series
Y series
Outdoor temperature
-20 to 15.5˚C
Only standard indoor units
(WB)
Cooling
50 to 100%R2 series
PWFY with
standard indoor units
Only standard
indoor units
50 to 150%50 to 150%
Only PWFY
<PWFY-P100, P200VM-E-AU>
50 to 100%Y series
50 to 130%50 to 130%
-20 to 15.5˚C
I
- 1 -
II
Model
Power source
kWHeating capacity
kcal / h(Nominal )
Btu / h
kW
A
W.B
dB<A>
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm
in.
kg(lb)
kW
-
Power input
Liquid
Gas
Current input
Outdoor temp.
Inlet Water temp.
Total capacity
Temp. range of
heating
Connectable
outdoor unit
Model / Quantity
Noise level (measured in anechoic room)
Diameter of
refrigerant pipe
Diameter of
water pipe
Field drain pipe size
* Due to continuing improvement, the above specifications may be subject to change without notice.* Install the unit in an environment where the
wet bulb Temp. will not exceed 32degC.
* The unit is not designed for outside installations.
* Please don't use the steel material for the water piping material.* The water circuit must use the closed circuit.
* Please do not use it as a drinking water.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less.
* Please always make water circulate or pull out the circulation water completely when not using it.
* Please do not use groundwater and well water.
* The specification data is subject
to rounding variation.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
ProductSpecications
1.Specications
- 2 -
Model
Power source
kW*1Heating capacity
kcal / h
Btu / h
kW
A
W.B
*1(Nominal)
*1
Power input
Current input
Outdoor temp.
Temp. range of
W.B
-
heating
Inlet Water temp.
kW*2Cooling capacity
kcal / h
Btu / h
kW
A
D.B
*2(Nominal)
*2
Power input
Current input
Outdoor temp.
Temp. range of cooling
D.B
-Inlet Water temp.
Total capacity
Model / Quantity
Water flow rate 1.93m3/h
* Install the unit in an environment where the
lb = kg / 0.4536
* Due to continuing improvement, the above specifications may be subject to change without notice.
wet bulb Temp. will not exceed 32degC. * The unit is not designed for outside installations.
* Please don't use the steel material for the water piping material.* The water circuit must use the closed circuit.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less.
* Please always make water circulate or pull out the circulation water completely when not using it.
Inlet
Outlet
Operation Volume
Liquid
Gas
m3/h
MPa
MPa
Accessory
External
Wiring
Document
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
Unit converter
* The specification data is subject
to rounding variation.
Pipe length : 7.5 m (24-9/16 ft)Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate 4.30m3/h
Inlet water Temp 23°C
Water flow rate 3.86m3/h
* Due to continuing improvement, the above specifications may be subject to change without notice.
* Install the unit in an environment where the
wet bulb Temp. will not exceed 32degC.
* The unit is not designed for outside installations.
* Please don't use the steel material for the water piping material.* The water circuit must use the closed circuit.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less.
* Please always make water circulate or pull out the circulation water completely when not using it.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
●Heat Insulation material ························· 1pc.
●Connector set ········································ 2set
<Unit:mm>
(1) PWFY-P100VM-E-BU
- 5 -
(2) PWFY-P100, 200VM-E-AU
300600
Fig. A
Service space
(front side)
Top view
400
Piping space
(right side)
P200:Use the Expansion joint
of accessories
Drain (R1 screw)
ø9.52 <Brazed>
ø27 Knockout hole
<Hole for control wiring>
ø27 Knockout hole
<Hole for power supply>
Water outlet
(RC3/4 screw)
Water inlet
(R3/4 screw)
P100:ø15.88 <Brazed>
P200:ø19.05 <Brazed>
ø27 Knockout hole
<Hole for external wiring input>
ø27 Knockout hole
<Hole for external wiring output>
Connection pipe of outdoor unit
(Gas)
Connection pipe of outdoor unit
(Liquid)
Front view
Right side view
Control box
Service panel
Top view
2X2-
ø
14 Hole
525
(Mounting pitch)
450
(Mounting pitch)
300800
205
500
<Accessories>
●Y-type strainer (RC3/4)
·····························
1pc.
●Heat Insulation material
····························
1pc.
●Connector set
············································
2set
●Expansion joint (P200)
······························
2pc.
[From RC3/4 to RC1]
Note 1.Ensure no rain water or debris can enter the unit through any gaps around
wiring or piping.
2.Ensure adequate service space is right around the unit, according to Fig A.
3.Please always make water circulate or add the brine to the circulation water
when the ambient temperature becomes 0
°C
or less.
4.The unit is not designed for outside installations.
5.Install the unit in an environment where the wet bulb Temp.
will not exceed 32degC.
6.Please always make water circulate or pull out the circulation
water completely when not using it.
7.The water circuit must use the closed circuit.
8.Please don't use the steel material for the water piping material.
9.Connect the strainer which is put as accessory to water inlet pipe.
91
91
35
55
35
480102
206
134
114
100191
46
6014080165
54
<Unit:mm>
- 6 -
3.ElectricalWiringDiagrams
M
4-20mA
4-20mA
gray
2
1
gray
black
To outdoor unit/
BC controller
To MA remote
controller
Power Supply
~220/230/240V
50Hz/60Hz
3
2
1
blue
red
yellow/green
bluered
CN4
63LS
CN63HS
1
1
3
2
2
3
THHS
12
CN63LS
123
t°
TH8
2
1
CN403
red
t°
TH6
1
2
CN404
black
t°
3 1
CT1
Moter
3~
CYN
RS4
MS
RS3
(Compressor)
CN3A
blue
U
t°
red
yellow
TH22
CN405
IPM
W
V
U
black
1
63HS
7
2
1
3
1
2
CN3
2
1
t°
CN401
CN2
2 56
t°
red
CN5
2
1
TH11
1
2
TH13
2
1
white
CN402
green
red
5
6
RS1
black
2
CN52C
R1
LO
U
CNAC2
red
2
CN5
1
1
2
red
blue
red
LEV2W
M
LI
24V
blue
+
CB3
Z2
1
U
CT1
LEV1W
1
CN2
63H1
6
5
CNAC
2
red
1
CX2
L
CN506A
L3
N
6
5
N
CN-E1
CN631
DSA
pink
E2
3
1
E1
432
1
CY4
P
CY3
31
L4
Z1
NI
CB1
+
1
TB2
CN661
2L23
X506
W
4
CN4
blue
U
CN52C
1
2
+
CX3
INV control
circuit
PFC
E3
1
L1
2
M
ZNR01
ACL
CY1CY2
CT2
Noise
Filter
red
Fan motor
1
3
(DC)
CX5
CYP
CIS
CX6
1
2
7
V
yellow
LED3:Lit when powered
INV Board
Control Board
CB2
(DC)
CY6
S
CX4
R
CNAC1
M
CNLVA
NO
Fan motor
3
1
2
RS2
CY5
P
CNLVB
blue
CX1
CX7
CN506B
CPS
+
RS
F01
AC250V
6.3A
F631
DC700V
4A
Power
Supply circuit
blue
red
TB5
M1 M2
S(SHIELD)S(SHIELD)
TB15
yellow
purple
black
orange
gray
red
black
white
gray
gray
52C
1
2
CN2M
blue
3 1
*4
IN2
TB141B
TB142B
IN6
COM+
OUT5
TB142C
OUT7
OUT6
X515 X517
X516
IN8
IN5 IN7
TB142A
X514
OUT2
X512
X511 X513
OUT1 OUT3
OUT4
TB141A
*5*6*7
IN3 IN4
COM+
LED4:Remote controller
when powered
SWU1
10
SW1
5
ON
OFF
1
Unit address setting(SWU1,SWU2)
Connection No.(SWU3)
LED1 Display setting(SW2)
Function setting(SW1,SW3,SW4)
SWP3
SW5
SWP1
SWU3
SWP2
SWU2
OFF
ON
110
SW4
OFF
ON
110
LED1
OFF
ON
1
SW3
OFF
ON
110
SW2
IN1
gray
CN421
black
3 1
CN422
blue
IN1
IN2
3 1
CN421
black
3 1
CN422
blue
2
2
2
2
BC controller/outdoor unit
Booster unit
Linear
expansion valve
LEV1W
LEV2W
IN7Anti-freeze
IN6Heating ECO
Symbol
Function
COM+ Common
IN5Hot water
IN4Operation ON/OFF
Connection demand
Symbol
IN3
Function
Symbol
Pump interlock
Function
IN1
*4 TB141A(output)
*5 TB142A(input)
*6 TB142B(input)
*7 TB142C(input)
Function
Symbol
OUT1 Operation ON/OFF
OUT2 Defrost
OUT3 Compressor
OUT4 Error signal
<HIGH VOLTAGE WARNING>
·Control box houses high-voltage parts.
Before inspecting the inside of the control box, turn off the power,
keep the unit off for at least 10 minutes,and confirm that the voltage
CN631 on Control Board has dropped to DC20V or less.
<CAUTION FOR INSTALLATION>
·Prior to installation,read the Installation Manual carefully.
*1.Single-dotted lines indicate wiring not supplied with the unit.
*2.Dot-dash lines indicate the control box boundaries.
*3.Faston terminals have a locking function.
Make sure the terminals are securely locked in place after insertion.
Press the tab on the terminals to removed them.
TH8water outlet temp
TH6water inlet temp
TH22liquid pipe temp
TH13Evaporator outlet temp
Compressor discharge tempTH11 Thermistor
TB15MA remote controller
TB5Outdoor unit/BC controller
AC reactor
Pressure
switch
High pressure switch
(High pressure protection for the booster unit)
Discharge pressure
Low pressure
TB2
CT1,CT2
ACL
THHS
Magnetic relay(main circuit)
Current sensor(AC)
Explanation
Terminal
block
Power supply
IGBT temp
Pressure
sensor
Symbol
63H1
63HS
63LS
52C
<Symbol explanation>
(1) PWFY-P100VM-E-BU
- 7 -
(2) PWFY-P100, 200VM-E-AU
gray
red
M
For opening/closing the bypass circuit
Solenoid valve
SV1
IN1
TB5
M1 M2
S(SHIELD)
To outdoor unit/
BC controller/
4-20mA
4-20mA
132
CN421
black
132
CN422
blue
132
CN422
blue
2
black
CN421
13
IN1
234
5
yellow/green
LEV1Wa
LEV1Wb
Linear
expansion valve
BC controller/outdoor unit
BC controller/outdoor unit
Function
Function
Function
black
yellow purple
bluered
NL
IN7
IN8IN6
IN5COM+
IN4IN3
orange
*3.Difference of appliance
*4 TB141A(output)
*5 TB142A(input)
*6 TB142B(input)
*7 TB142C(input)
Model name
Appliance
P100*3 do not exist
P200*3 exist
*7*6*5
*4
Cooling
TH23gas pipe temp
CN502
black
COM+
TH8
TH6
TH23
t°
t°
t°
blue
CN2M
2
1
2
1
CN402
green
2
1
CN403
red
1
2
CN404
black
yellow
CN405
t°
TH22
1
2
21
To MA remote
controller
Power Supply
~220/230/240V
50Hz/60Hz
Unit address setting(SWU1,SWU2)
Connection No.(SWU3)
LED1
TB15
ZNR1
U
DSA1
CN1
1
3
SWU2
SWU1
SWP3
SWP2
SWP1
OFF
ON
110
SW4
OFF
ON
110
SW3
OFF
ON
110
SW1
OFF
ON
110
SW2
LED4:Remote controller
when powered
5
CNLVC
6
1
LEV1Wb
123
4
X502
CN507
3
1
M
5
6
ON
OFF
1
SW5
SWU3
LED3:Lit when powered
Control Board
CNLVB
LEV1Wa
TB2
SV1
*3
DSA Board
CN3T
red
13
T01
ZNR01
3
1
1
2
CNAC
red
U
F01
AC250V
6.3A
LED1 Display setting(SW2)
Function setting(SW1,SW3,SW4)
OUT4
OUT3
OUT2
X514
X513
X512
TB141A
OUT1
X511
3 1
CN3A
blue
TB142CTB142B
X516
X517X515
OUT6
OUT7OUT5
TB141B
TB142A
IN2
IN8
IN7Anti-freeze
IN6Heating ECO
Symbol
COM+ Common
IN5Heating
IN4Operation ON/OFF
Connection demand
Symbol
IN3
Symbol
Pump interlockIN1
Function
Symbol
OUT1 Operation ON/OFF
OUT2 Defrost
OUT4 Error signal
<CAUTION FOR INSTALLATION>
·
Prior to installation,read the Installation Manual carefully.
*1.Single-dotted lines indicate wiring not supplied with the unit.
*2.Dot-dash lines indicate the control box boundaries.
TH8water outlet temp
TH6water inlet temp
TH22liquid pipe temp
Thermistor
TB15MA remote controller
TB5Outdoor unit/BC controller
TB2
Explanation
Terminal
block
Power supply
Symbol
<Symbol explanation>
- 8 -
4. Accessories
(A) Strainer(B) Heat insulation material
*1
*1. PWFY-P200VM-E-AU only
(C) Connecter sets 2(D) Expansion joint 2
(A) Install the strainer at the water pipe inlet.
(B) This insulation is for exclusive use with the strainer. Wrap the strainer with the insulation after water pipes are
installed.
(C) These are analog input connectors. Cut the wire before using.
(D) Supplied only with the PWFY-P200VM-E-AU. Install them at the strainer inlet. Refer to P39 for details.
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
631252505001k2k4k8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Sound level of PWFY-P100VM-E-BU
Measurement condition
PWFY-P100VM-E-BU
50/60Hz
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
631252505001k2k4k8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Sound level of PWFY-P100, 200VM-E-AU
Approximate minimum
audible limit on
continuous noise
dB(A)
29.0
8k
12.0
4k
15.0
2k
14.5
1k
22.5
500k
25.0
250
33.0
125
32.0
63
42.0
50/60Hz
dB(A)
44.0
8k
27.0
4k
27.5
2k
32.0
1k
39.0
500k
42.0
250
37.0
125
53.5
63
41.0
Measurement condition
PWFY-P100, 200VM-E-AU
Measurement
location
1m
1m
Measurement
location
1m
1m
Octave band center frequency <Hz>
(1) PWFY-P100VM-E-BU
(2) PWFY-P100, 200VM-E-AU
- 27 -
3. Vibration levels
PWFY-P100VM-E-BU
PWFY-P100VM-E-BU
ModelVibration Levels[dBA]
34
10cm
20cm
Measurement
location
Service
panel
Concrete
VIBRATION LEVELS
(1) PWFY-P100VM-E-BU
- 28 -
TH6
TH23
LEV1Wa
TH8
TH22
SV1
CV1
ST2
ST3
Water inlet
Water outlet
screw
screw
Hex
Hex
Brazed
Brazed
TH6
TH23
LEV1Wa
TH8
TH22
LEV1Wb
SV1
ST2
ST4
CV1
Water inlet
Water outlet
screw
screw
Brazed
Brazed
4. Refrigerant circuit diagrams and thermal sensors
Refrigerant Circuit Diagrams And Termal Sensors
TH11
63H1
63HS
63LS
TH13
TH22
LEV1W
LEV2W
COMP
Water outlet
TH6
TH8
ST3
ST1
ST2
CJ
Brazed
Brazed
screw
screw
Water inlet
Hex
Hex
(1) PWFY-P100VM-E-BU
(2) PWFY-P100VM-E-AU
(3) PWFY-P200VM-E-AU
- 29 -
+
+
A
. For Air conditioning using such as Panel Heaters, Floor Heating and Fan coil units
Required total heating capacity kW
Safety factor;%
B. For Sanitary use such as Shower and Bathrooms
Conditions
Tank inlet water Temp.;°C
Tank outlet water Temp.;°C
(Set Temp -5 °C)
Safety factor for Heat Loss;%
Operating time;Hours
For Shower; /person xPerson =(Water Temp. Condition°C)
°C)
For Bathrooms;/Person xPerson =(Water Temp. Condition
(The examples of water volume might be need to be changed as you need.)
The conversion of water volume to°C
x(-)/(-)
+x(-)/(-)
=ℓ /day
Heating Capacity Calculation for sanitary usage
/
1,000 x (-) =M cal / day
The conversion of M cal to kW
/ 860 x 1,000 /
=kW
C. Total (A+B)
Total Heating Capacity
x
(100%
+x
(100%
%) +
x (100%%) =kW
D. No. of units required
Safety factor;%
%) / 12.5 kW =units
units are required
TankPWFY unit
4
33
3
3
7
IV
+
+
A
. For Air conditioning using such as Panel Heaters, Floor Heating and Fan coil units
Required total heating capacity 20
10
10
60
60
15
8
20
30
1,200
240
40
45
1,200
240
40
45
10
10
60
60
10
10
888
888
44.4
20
29.4220
3
2.82
10
20
6.451529.42
86.45
601044.4
kW
Safety factor;%
B. For Sanitary use such as Shower and Bathrooms
Conditions
Tank inlet water Temp.;°C
Tank outlet water Temp.;°C
(Set Temp -5 °C)
Safety factor for Heat Loss;%
Operating time;Hours
For Shower; 60/person xPerson =(Water Temp. Condition°C)
°C)
For Bathrooms; 8/Person xPerson =(Water Temp. Condition
(The examples of water volume might be need to be changed as you need.)
The conversion of water volume to°C
x(-)/(-)
+x(-)/(-)
=ℓ /day
Heating Capacity Calculation for sanitary usage
/1,000 x (-) =M cal / day
The conversion of M cal to kW
/ 860 x 1,000 /
=kW
C. Total (A+B)
Total Heating Capacity
x
(100%
+x
(100%
%) +
x (100%%) =kW
D. No. of units required
Safety factor;%
%) / 12.5 kW =units
units are required
TankPWFY unit
4
33
3
3
7
Installation
1. How to calculate the necessary heat capacity
(1) Heating capacity calculation
(2) A calculation example
- 30 -
2. Installation
(B)
a
b
c
(C)
(A)
(1) Selecting an installation site
• Do not install outdoors. The unit is not waterproof.
- The inverter equipment, private power generator, high-frequency medical equipment, or radio communication
equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air
conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged, condensation may drip from the indoor
unit. Perform collective drainage work together with the unit, as required.
-
(1)-1 Securing installation and service space
• Please allow for the following service spaces after installation.
(All servicing can be performed from the front of the unit)
[Fig. IV. 2. (1). 1]
(A) Piping space (right side)
(B) Top view
(C) Service space (front side)
Warning:
• Be sure to install the unit in a location which can adequately support its weight.
- If there is insufcient strength to support the unit’s weight, it could fall and cause injuries.
(1)-2 Combining indoor units with BC controllers and outdoor units
For combining indoor units with BC controllers and outdoor units, refer to section BC controllers and outdoor units
installation manual.
- 31 -
(2) Installing the unit
XYZ
272355119
Model
PWFY-P100VM-E-BU
450300
800
Y
XZ
500
525
1347205
(2)-1 Lifting method
Caution:
Be very careful when carrying the product.
- Do not have only one person to carry product if it is more than 20 kg.
- Do not tilt the unit while transporting.
- PP bands are used to pack some products. Do not use them as a mean for transportation because they are
dangerous.
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may
suffocate children to death.
(2)-2 Product net weight
Model
Net weight
(2)-3 Center of gravity
(2)-3-1 PWFY-P100VM-E-BU
PWFY-P100VM-E-BU
60 kg
PWFY-P100VM-E-AU
35 kg
PWFY-P200VM-E-AU
38 kg
- 32 -
(A)
(B)
205
300
450
500
525
(2)-3-2 PWFY-P100, 200VM-E-AU
X
289
277
Model
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
Z
103
99
Y
346
347
20513
X
Y
800
500
525
300
450
Z
47
(2)-4 Installation method
• Using the anchoring holes shown below, rmly bolt the unit to the base.
[Fig. IV. 2. (2). 1]
(A) 4-ø14 (Anchoring hole)
(B) (Top view)
Bases
• Be sure to install unit in a place strong enough to withstand its weight. If the base is unstable, reinforce with a con
crete base.
• The unit must be anchored on a level surface. Use a level to check after installation.
• If the unit is installed near a room where noise is a problem, using an anti-vibration stand on the base of the unit is
recommended.
- 33 -
-
(3) Refrigerant pipe and drain pipe specications
(D)
(A)
(B)
(C)
(E)
480
100191
54
102
114
134
184 (206*1)
(3)-1 Refrigerant pipe and drain pipe specications
To avoid dew drops, provide sufcient antisweating and insulating work to the refrigerant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commercially available insulating material (with a
heat-resisting temperature of more than 100 °C and thickness given below) onto both liquid and gas pipes.
Be also sure to wind commercially available insulating material (with a form polyethylene’s specic gravity of 0.03 and
thickness given below) onto all pipes which pass through rooms.
1) Select the thickness of insulating material by pipe size.
Model
Gas
Liquid
Drain
Insulating material's thickness
PWFY-P100VM-E-BU
ø
15.88
ø
9.52
PWFY-P100VM-E-AU
ø
15.88
ø
9.52
ø
32
More than 10 mm
PWFY-P200VM-E-AU
ø
19.05
ø
9.52
2) If the unit is used on the highest story of a building and under conditions of high temperature and humidity, it is
necessary to use pipe size and insulating material’s thickness more than those given in the table above.
3) If there are customer’s specications, simply follow them.
(3)-2 Refrigerant pipe, drain pipe and lling port
(A) Refrigerant piping (gas)
(B) Refrigerant piping (liquid)
(C) Water inlet
(D) Water outlet
(E) Drain outlet
*1: PWFY-P100, 200VM-E-AU
- 34 -
(4) Connecting refrigerant pipes and drain pipes
(A)
(A)
(E)
(C)
(F)
(B)
(D)
(4)-1 Refrigerant piping work
This piping work must be done in accordance with the installation manuals for both outdoor unit and BC controller
(simultaneous cooling and heating series R2).
• Series R2 is designed to operate in a system that the refrigerant pipe from an outdoor unit is received by BC
controller and branches at the BC controller to connect between indoor units.
• The PWFY unit should be connected to 2 ports on the BC controller. (Set BC controller DIP SW 4-6 to ON)
• For constraints on pipe length and allowable difference of elevation, refer to the outdoor unit manual.
• The method of pipe connection is brazing connection.
Caution:
• Install the refrigerant piping for the indoor unit in accordance with the following.
1. Cut the tip of the indoor unit piping, remove the gas, and then remove the brazed cap.
[Fig. IV. 2. (4). 1]
(A) Cut here
(B) Remove brazed cap
2. Pull out the thermal insulation on the site refrigerant piping, braze the unit piping, and replace the insulation in its
original position.
Wrap the piping with insulating tape.
Note:
• Pay strict attention when wrapping the copper piping since wrapping the piping may cause condensation
instead of preventing it.
* Before brazing the refrigerant piping, always wrap the piping on the main body, and the thermal insulation
piping, with damp cloths to prevent heat shrinkage and burning the thermal insulation tubing.
ensure that the ame does not come into contact with the main body itself.
[Fig. IV. 2. (4). 2]
Take care to
(A) Thermal insulation
(B) Pull out insulation
(C) Wrap with damp cloth
(D) Return to original position
(E) Ensure that there is no gap here
(F) Wrap with insulating tape
- 35 -
Cautions On Refrigerant Piping
(A)
(B)
(a)
(C)(C)(C)
(D)(b)
(E)
• Be sure to use non-oxidative brazing for brazing to ensure that no foreign matter or moisture enter
“Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of
the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any
other contaminant.
• Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerator oil in the existing piping will cause the new
refrigerant to deteriorate.
• Store the piping to be used during installation indoors and keep both ends of the piping sealed until just
before brazing.
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and the compressor may fail.
(4)-2 Drain piping work
1. Ensure that the drain piping is downward (pitch of more than 1/100) to the outdoor (discharge) side. Do not provide
any trap or irregularity on the way. (a)
2. Ensure that any cross-wise drain piping is less than 20 m (excluding the difference of elevation). If the drain piping
is long, provide metal braces to prevent it from waving. Never provide any air vent pipe. Otherwise drain may be
ejected.
3. Use a hard vinyl chloride pipe VP-25 (with an external diameter of 32 mm) for drain piping.
4. Ensure that collected pipes are 10 cm lower than the unit body’s drain port as shown in (b).
5. Do not provide any odor trap at the drain discharge port.
6. Put the end of the drain piping in a position where no odor is generated.
7. Do not put the end of the drain piping in any drain where ionic gases are generated.
[Fig. IV. 2. (4).3]
(A) Downward slope 1/100 or more
(B) Drain hose
(C) Unit
(D) Collective piping
(E) Maximize this length to approx. 10 cm
- 36 -
3. Water pipe installation
Water-side
heat exchanger
Solid arrows in the figure indicate
the direction of water flow.
PWFY
Field supply
TankOutlet
Inlet
City water
Overflowed water
Roof
To drain outlet
Uphill gradient ≥ 1/200
P
P
T
T
P
1)
1)
1)
1)
2)
2)
3)
3)3)
4)
4)4)4)
5)
5)
5)
6)
7)
8)
8)
9)
11)11)
12)
(1) Water circuit sample
Sample of water circuit for HWS/ATW
Consider the following when designing and installing a water piping system. (Items (1)-(12) in the gure are explained
below.)
1) Union joints/ange joints etc.
Install a ange etc. to allow for easy replacement of connected equipment.
2) Thermometer
For checking unit performance and operation monitoring
3) Water pressure gauge
For operation status monitoring
4) Valve
Install a valve for easy replacement and cleaning of the refrigerant ow control device.
Install a refrigerant ow control valve on the fan coil outlet side.
5) Flexible joint
Recommended to prevent the noise and vibration from the pump from being transmitted.
6) Drain pipe
Install the drain pipe with an inclination of between 1/100 and 1/200 to provide a downward ow of drain water.
For cold climate installation, take an appropriate measure (e.g., drain heater) to prevent the drain water from
freezing.
7) Pump
Use a pump that is large enough to compensate for the total water pressure loss and to supply sufcient water to the
unit.
8) Air vent valve
Provide air vent valves on the pipes.
9) Expansion tank
Install an expansion tank to accommodate expanded water and to supply water.
10) Cold/Hot water pipe
Use pipes that allow for easy air purging, and provide sufcient insulation.
11) Drain valve
Install drain valves so that water can be drained for servicing.
12) Strainer
Install a strainer near the PWFY unit to keep foreign materials from entering the water-side heat exchanger.
- 37 -
(1)-1 Caution for water pipe installation
(A)
45°
Consider the following when designing and installing a water piping system.
• Do not use steel pipes as water pipes.
- Copper pipes or stainless steel pipes are recommended.If iron pipes are used in the existing system, do not connect
a new circuit to the old one. Keep the existing and new circuits separate.
• Light pipes are similar to other air-conditioning pipes, however, please observe the following precautions during
installation.
• Before a long period of non use, purge the water out of the pipes and thoroughly let them dry.
• Use a closed water circuit.
• When using the unit for cooling, add brine to the circulating water to prevent it from freezing.
• When installed in a low-ambient temperature environment, keep the water circulating at all times. If that is not
possible, purge the water out of the pipes completely.
• Do not use the water used for this unit for drinking or food manufacturing.
• When the ambient temperature is 0 ˚C or lower during stop operation, keep the water circulating at all times, or
purge the water out of the pipes completely.
Model
PWFY-P100VM-E-BU
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
*1 When the attached expan-
sion joints are installed.
Water inlet
PT 3/4 Screw
PT 3/4 Screw
PT 1 Screw*1
Water outlet
PT 3/4 Screw
PT 3/4 Screw
PT 1 Screw*1
(2) Selecting a water pump
Use a pump that is large enough to compensate for the total water pressure loss and to supply sufcient water to the unit.
(3) Installing the strainer
• Install the strainer at the angle of 45˚ or less as shown in [Fig. IV 3.(3).1].
• Install the supplied strainer at the water inlet.
[Fig. IV 3.(3).1]
(A) Y-type strainer
(4) Precautions during installation
• Use the reverse-return method to insure proper pipe resistance to each unit.
• To insure easy maintenance, inspection, and replacement of the unit, use a proper joint, valve, etc. on the water
intake and outlet port. In addition, be sure to install a strainer on the water intake pipe. (In order to maintain the heat
source unit, a strainer on the circulating water inlet is necessary.)
* An example of the heat source unit installation is shown in the diagram below.
• Install a suitable air vent on the water pipe. After sending water through the pipe, be sure to vent the excess air.
• Compressed water may form in the low-temperature sections of heat source unit. Use a drainage pipe connected to
the drain valve at the base of the unit to drain the water.
• Install a back ow-prevention valve on the pump and a exible joint to prevent excess vibration.
• Use a sleeve to protect the pipes where they go through a wall.
• Use metal ttings to secure the pipes, and install them so that they have maximum protection against breakage and
bending.
• Do not confuse the water intake and outlet valves.
• This unit doesn’t have any heater to prevent freezing within tubes. When the water ow is stopped on low ambient,
take out the water from tubes.
• The unused knockout holes should be closed and the opening of refrigerant pipes, water pipes, power source and
transmission wires should be lled with putty and so on to prevent from rain. (eld construction)
• Wrap some sealing tape around the screw part to prevent water leakage.
• Hold the pipe on the unit side in place with a spanner when installing the pipes or strainer. Tighten screws to a torque
of 50 N.m.
• Water pipes can get very hot, depending on the preset temperature. Wrap the water pipes with insulating materials
to prevent burns.
• On the PWFY-P200VM-E-AU model, install the expansion joint (accessory) at the inlet after installing the strainer,
and outlet.
- 38 -
(5) Example of unit installation (using light piping)
The surface temperature of the water pipe would be very high, depending on the set temperature. Insulate the pipe
to prevent burns. When operating PWFY-P100, P200VM-E-AU with cold water, insulate the water pipe to prevent
condensation.
Wrap insulation material around water pipes as shown in [Fig. IV. 3.(6).1].
• Any heat source piping.
• Indoor piping in cold-weather regions where frozen pipes are a problem.
• When air coming from the outside causes condensation to form on piping.
• Any drainage piping.
[Fig. IV. 3.(6).1]
(A) Heat insulation material (accessory)
(B) Inject with caulking material
- 39 -
(7) Water processing and water quality control
To preserve water quality, use the closed type of cooling tower for unit. When the circulating water quality is poor, the
water heat exchanger can develop scales, leading to a reduction in heat-exchange power and possible corrosion of the
heat exchanger. Please pay careful attention to water processing and water quality control when installing the water
circulation system.
• Removal of foreign objects or impurities within the pipes.
During installation, be careful that foreign objects, such as welding fragments, sealant particles, or rust, do not enter
the pipes.
• Water Quality Processing
a) Depending on the quality of the cold-temperature water used in the air-conditioner, the copper piping of the heat
exchanger may become corroded. We recommend regular water quality processing.
Cold water circulation systems using open heat storage tanks are particularly prone to corrosion.
When using an open-type heat storage tank, install a water-to-water heat exchanger, and use a closed-loop
circuit on the air conditioner side. If a water supply tank is installed, keep contact with air to a minimum, and
keep the level of dissolved oxygen in the water no higher than 1mg/liter.
Ammonium ion (mg NH
Residual chlorine (mg Cl/liter)
Free carbon dioxide (mg CO
Ryzner stability index
-
/liter)
2-
/liter)
(mg CaCO3/liter)
3
/liter)
3
/liter)
2
/liter)
(mg S2-/liter)
+
4
/liter)
2
/liter)
Lower mid-range temperature water system
Water Temp.
Recirculating water
7.0 ~ 8.0
30 or less
[300 or less]
50 or less
50 or less
50 or less
70 or less
50 or less
30 or less
1.0 or less
1.0 or less
not to be
detected
0.3 or less
0.25 or less
0.4 or less
–
=<
60 ˚C
Make-up water
7.0 ~ 8.0
30 or less
[300 or less]
50 or less
50 or less
50 or less
70 or less
50 or less
30 or less
0.3 or less
1.0 or less
not to be
detected
0.1 or less
0.3 or less
4.0 or less
–
Higher mid-range temperature water system
Recirculating water
Water Temp. > 60 ˚C
7.0 ~ 8.0
30 or less
[300 or less]
30 or less
30 or less
50 or less
70 or less
50 or less
30 or less
1.0 or less
1.0 or less
not to be
detected
0.1 or less
0.1 or less
0.4 or less
–
Make-up water
7.0 ~ 8.0
30 or less
[300 or less]
30 or less
30 or less
50 or less
70 or less
50 or less
30 or less
0.3 or less
1.0 or less
not to be
detected
0.1 or less
0.3 or less
4.0 or less
–
Corrosive
Reference : Guideline of Water Quality for Refrigeration and Air Conditioning Equipment. (JRA GL02E-1994)
c) Please consult with a water quality control specialist about water quality control methods and water quality
calculations before using anti-corrosive solutions for water quality management.
d) When replacing a previously installed air conditioning device (even when only the heat exchanger is being
replaced), rst conduct a water quality analysis and check for possible corrosion.
Corrosion can occur in cold-water systems even if there has been no prior signs of corrosion.
If the water quality level has dropped, please adjust water quality sufciently before replacing the unit.
The maximum amount of circulating water in the water pipe is 100L. Make sure that this amount is not exceeded.
Tendency
Scale-forming
- 40 -
(8) Pump interlock
IN1
TB142A
Water Pump
Strainer
Control Box
Broken lines are field
supply products.
Operation signal
Pump interlock
The unit may become damaged if it is operated with no water circulating through the pipes.
Be sure to interlock unit operation and the water-circuit pump. Use the terminal blocks for interlocking TB142A (IN1) that
1. Be sure to take power from the special branch circuit.
2. Be sure to install an earth leakage breaker to the power.
3. Install the unit to prevent that any of the control circuit cables (remote controller, transmission cables, or external
input/output line) is brought in direct contact with the power cable outside the unit.
4. Ensure that there is no slack on all wire connections.
5. Some cables (power, remote controller, transmission cables external input/output line) above the ceiling may be
bitten by mouses. Use as many metal pipes as possible to insert the cables into them for protection.
6. Never connect the power cable to leads for the transmission cables. Otherwise the cables would be broken.
7. Be sure to connect control cables to the indoor unit, remote controller, and the outdoor unit.
8. Be sure to ground the unit.
9. Select control cables from the conditions given in page
42.
Caution:
Be sure to put the unit to the ground on the outdoor unit side. Do not connect the earth cable to any gas pipe,
water pipe, lightening rod, or telephone earth cable. Incomplete grounding may cause a risk of electric shock.
(2) Power supply for PWFY unit
(2)-1 Electrical characteristics of PWFY unit
• Power supply cords of appliances shall not be lighter than design 245 IEC 57 or 227 IEC 57.
• A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.
Model
PWFY-P100VM-E-BU
Model
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
Hz
50/60
50/60
220-230-240 V
Hz
Power supplyCompressor
Volts
220-230-240 V
Voltage range
Max. 264 V
Min. 198 V
Power supply
Volts
MCA (A)
15.71
Voltage range
Max. 264 V
Min. 198 V
Output (kW)
1.0
MCA (A)
0.085
SC (A)
1.25
Cooling
RLA (A)
Heating
11.63-11.12-10.66
RLA (A)
Heating
0.068-0.065-0.063
(2)-2 Power cable specications
Model
PWFY-P100VM-E-BU
Model
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
[Fig. V. 1.(2).1]
Minimum wire thickness (mm2)
Main cable
2.5
Total
operating
current
16 A or less
25 A or less
32 A or less
branch
-
Minimum wire thickness (mm2)
Main cable
1.5
2.5
4.0
Ground
2.5
branch
Breaker for
current leakage
30 A 30 mA 0.1 sec or less
Ground
1.5
2.5
4.0
1.5
2.5
4.0
20 A 30 mA 0.1 sec. or less
30 A 30 mA 0.1 sec. or less
40 A 30 mA 0.1 sec. or less
Breaker for current
leakage
Local swich (A)
capacity
25
capacity
fuse
25
Local swich (A)
fuse
16
25
32
16
25
32
Breaker for wiring (NFB) (A)
30
Breaker for wiring (NFB) (A)
20
30
40
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too
Install wiring so that it is not tight and under tension. Wiring under tension may break, or overheat and burn.
• Fix power source external input/output line wiring to control box by using buffer bushing for tensile force to prevent
electric shock. (PG connection or the like.) Connect transmission wiring to transmission terminal block through the
knockout hole of control box using ordinary bushing.
• After wiring is complete, make sure again that there is no slack on the connections, and attach the cover onto the
control box in the reverse order removal.
[Fig. IV. 1.(5).2]
(A) To prevent external tensile force from applying to the wiring
connection section of power source terminal block use buffer
bushing like PG connection or the like.
(B) External signal input cable
(C) External signal output cable
(D) Power source wiring
(E) Tensile force
(F) Use ordinary bushing
(G) Transmission cable and MA remote controller cable
(Be sure to operate with the main power turned OFF.)
[Fig. V. 1.(6).1]
<Address board>
• There are two types of rotary switch setting available: setting addresses 1 to 9 and over 10, and setting branch
numbers.
a) How to set addresses
Example: If Address is “3”, remain SWU2 (for over 10) at “0”, and match SWU1 (for 1 to 9) with “3”.
b) How to set branch numbers SWU3 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC controller’s end connection number. Remain other than R2 at “0”.
• The rotary switches are all set to “0” when shipped from the factory. These switches can be used to set unit address
es and branch numbers at will.
-
- 45 -
(6)-2 Rule of setting address
Unit
PWFY unit
Standard indoor unit
ME, LOSSNAY
Remote controller
(Main)
ME, LOSSNAY
Remote controller
(Sub)
Address setting
01 ~ 50
52 ~ 99, 100
101 ~ 150
151 ~ 199, 200
NoteExample
The address of outdoor unit + 1
Please reset one of them to an address between 52
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
System remote
controller
ON/OFF remote
controller
G-50A
GB-50A
AG-150A
000, 201 ~ 250
000, 201 ~ 250
000, 201 ~ 250
Local remote controller
System controller
The address of main remote controller + 50
The address automatically becomes "200" if it is set
as "00"
101
101
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
101
101
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
101
101100
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
101100
101100
LMAP02-E
201 ~ 250
1
1
Fixed
Fixed
Group remote
controller
201 ~ 250
The smallest group No. to be managed + 200
101
2
Fixed
2
Fixed
Outdoor unit
BC controller
(Main)
53 ~ 99, 100
Lowest address within the indoor units connected to
the BC controller (Sub) plus 50.
101
BC controller
(Sub)
51 ~ 99, 100
The smallest address of indoor unit in same refrigerant
system + 50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC and OS are
automatically detected. (Note 2)
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
Use the most recent address within the same group of
indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
If applicable, set the sub BC controllers in an PURY
system in the following order:
(1)
Indoor unit to be connected to the BC controller (Main)
(2)
Indoor unit to be connected to the BC controller (No.1 Sub)
(3)
Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
101
(Note1)
0,20~50~9
Note1: To set the address to "100", set it to "50"
Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.
- 46 -
(6)-3 System examples
2. Address should be set to Indoor units, LOSSNAY and central controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and MA RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to Data book G4 2-3 "System configuration
restrictions".
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
*1
01
BC controller
53
BC controller
(Main)
93
033020
TB15
TB55BT20BT2BT5BT
Transmission Booster
PAC-SF46EPA
TB5
3BT51BT51BT
TB15
MA R/C
(Main)(Sub)
MA R/C
TB15
ME R/C
MA R/C
PZ-52SF
SRU
Wireless R/C
*1
*1142143
4142
4395
4546
TB15
TB55BT20BT
LOSSNAY
5BT5BT5BT
TB15
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
BC controller
(Sub1)
Group 2
12 puorG1 puorG
Group 3243 puorG33 puorG13 puorG
TB3
TB77BT7BT7BT
TB7
TB3
201
PSU
5251
OCOS
PURY-(E)P-YSHM
SC
TB3TB3
9291
OCOS
PURY-(E)P-YSHM
TB3
97
OC
CN41CN40CN41CN40CN41CN40CN4114NC04NCCN40
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
PURY-(E)P-YHM
4. Indoor units should be set with a branch number.
5. Assign an address to each of the sub BC controllers (SC1 and SC2) which equals the sum of the smallest address of the indoor
units that are connected to each sub BC controller and 50.
*2
(6)-3-1 MA remote controller, Multi-refrigerant-system, System Controller at TB7 side, Booster for long
2. Address should be set to Indoor units, LOSSNAY and central controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and MA consume the M-NET power for transmission use.
The power balance is needed to consider for long M-NET wiring. Details refer to Data book G4 2-3 "System configuration restrictions".
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
Indoor unit
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
MA
(Main)
WMA
MA
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
03302010
TB15
5BT5BT2BT5BT
Transmission Booster
PAC-SF46EPA
TB5
3BT51BT51BT
TB15
MA
(Main)MA(Sub)
TB15
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
WMAMA
4142
43
4546
TB15
5BT5BT
LOSSNAY
5BT5BT5BT
TB15
SRU
Wireless R/C
*1
*1
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
External input is input through CN421, CN422 on the circuit board. (Fig. V. 1.(7).1)
[Fig. V. 1.(7).1]
Use the supplied connector.
If no temperature settings are made via the MA remote controller, the temperature changes with the current of generator.
Refer to the instructions manual that came with the MA remote controller for how to make the settings.
4 mA → 10 °C 20 mA → 70 °C
Externaloutputterminal
External output terminal (refer to Fig. V. 1.(7).2) is ineffective when the circuit is open.
Refer to Table V. 1.(7).1 for information about each contact.
The current in the circuit to be connected to the external output terminal must be 0.6A or less.
Table V. 1.(7).1
OUT1
OUT2
OUT3
OUT4
Operation ON/OFF
Defrost
Compressor
Error signal
Externalinputterminal
The piping length must be within 100 m.
External input terminal (refer to Fig. V. 1.(7).2 is ineffective when the circuit is open.
Refer to Table V. 1.(7).2 through Table V. 1.(7).4 for information about each contact.
Only the “pump interlock” function is ineffective when the circuit is short-circuited.
Connect a relay circuit to the external output terminal as shown in Fig. V. 3.(8).1.
The specications of the relay circuit to be connected must meet the following conditions.
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
[Table V. 1.(7).2] TB142A
IN1
Pump interlock
[Table V. 1.(7).3] TB142B
IN3
IN4
Connection demand
Operation ON/OFF
[Table V. 1.(7).4] TB142C
[Fig. V. 1.(7).2]
[Fig. V. 1.(7).3]
COM+
IN5 *1
IN6 *2
IN7 *3
Common
Hot Water/Heating
Heating ECO *4
Anti-freeze *5
*1 PWFY-P100VM-E-BU Hot Water
PWFY-P100, 200VM-E-AU Heating
*2 Effective when SW 4-3 is set to ON.
*3 Effective when SW 4-4 is set to ON.
*4 When Heating ECO mode is effective, the outlet water temp. will be changed based on ambient temp. automatically.
*5 When Anti-freeze mode is effective, the unit will work for keeping set water temp. automatically.
H0 thermistor selectionWater inlet thermistor TH6Water outlet thermistor TH8 Before power on
Before power on
Before power on
2----
3
Remains stopped
Depends on the SW1-3 setting
Auto recovery (to the status
before power failure)
Forced to operate
*1 Valid only when SW1-4 is set to OFF
4
5----
6----
7Test-run modeOFFONAny time
8Error history deletedNormalDeletedAny time
9
Effective only when SW1-7 is
set to ON and only on the AT W
models.
HeatingCoolingAny time
10----
SW21-10
For self-diagnosis/operation
monitoring
--Any time
SW3
1Capacity setting (AT W only)4HP8HP (ATW only)Before power on
2Service LED display selectionDisplay in CentigradeDisplay in FahrenheitAny time
3----
4----
5
Cumulative compressor operation time is deleted.
NormalDeletedAny time
6----
7----
8----
9----
10----
SW4
1
2
3
Use to change pr
Do not change from factory setting.
Do not change from factory setting.
eset temperature range for the Heating ECO
mode.
HWS : Ineffective
ATW : Ine ffective
HWS : 30°C to 50°C
ATW : 30 °C to 50°C
Before power on
4
Use to change preset temperature range for the Anti-freeze
mode.
BU : Ineffective
WH : Ineffective
BU : 10°C to 45°C
WH : 10°C to 45°C
Before power on
5----
6----
7----
8----
9----
10----
SW5
1Error detection enabled
Enabling/disabling ACCT sensor
error detection
Error detection disable
(No load operation is possible)
Any time
2----
3----
4----
Control
1. Dip switch functions
- 50 -
2.Remotecontrollerspecications
FUNCTION
ON/OFF
Operation mode switching
Water temperature setting
Preset temperature range
Water temperature display
Permit / Prohibit
local operation
Weekly scheduler
Error
Self check (Error history)
Test run
Circulating water
replacement warning
LANGUAGE setting
Operation locking function
Runs and stops the operation of a group of units
Switches between Hot Water / Heating / Heating ECO / Anti-freeze / Cooling
* Available operation modes vary depending on the unit to be connected.
* Switching limit setting can be made via a remote controller.
Temperature can be set within the ranges below. (in increments of 1°C or 1°F)
Hot Water 35°C min. ~ 70°C max. (in increments of 1°C or 2°F)
Heating 30°C min. ~ 45°C max. (in increments of 1°C or 2°F)
Anti-freeze 10°C min. ~ 45°C max. (in increments of 1°C or 1°F)
Cooling 10°C min. ~ 30°C max. (in increments of 1°C or 1°F)
* The settable range varies depending on the unit to be connected.
Preset temperature range setting can be limited via a remote controller.
10°C min. ~ 90°C max.
(in increments of 1°C or 1°F)
* The settable range varies depending on the unit to be connected.
Individually prohibits operations of each local remote control function :ON/OFF,
Operation modes,water temperature setting, Circulating water replacement
warning reset.
*
Upper level controller may not be connected depending on the unit to be connected.
ON / OFF / Water temperature setting can be done up to 6 times one day in the week.
(in increments of a minute)
When an error is currently occurring on a unit, the afflicted unit and the error code
are displayed.
Searches the latest error history by pressing the CHECK button twice.
Enables the Test run mode by pressing the TEST button twice.
* Test run mode is not available depending on the unit to be connected.
Displays the circulating water replacement warning via the unit message.
Clears the display by pressing the CIR.WATER button twice.
* Circulating water replacement warning is not available depending on the unit to
be connected.
The language on the dot matrix LCD can be changed. (Seven languages)
English/German/Spanish/Russian/Italian/French/Swedish
Remote controller operation can be locked or unlocked.
Regular preventive maintenance and parts replacement help keep the unit running smoothly and minimize problems.
The table below shows the maintenance schedule. Use the replacement timing in the table only as a guide. Some parts
may need to be replaced sooner, depending on the usage.
MaintenanceCycle
1. Routine maintenance checks
• Periodically and thoroughly check the circulating water circuit. (See table below.)
• Consult a maintenance technician.
2. Parts Replacement Cycle
- 52 -
VIII
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
10.0
10.0
20.0
30.0
40.0
50.0
0.0
5.0
100200300400
100200300400500
Capa
city(kW)
Input
(kW)
Total capacity of indoor units
10.0
20.0
30.0
40.0
50.0
0.0
5.0
10.0
Cooling
Heating
Cooling
Heating
P300P350
Cooling
Heating
Cooling
Heating
P200P250
PUHY-P200,250YHM-A
Ref: PUHY_YHM-A_CbTIU_EUDB_P200-P350
PUHY-P300,350YHM-A
Product Data (supplemental information for chapter III.)
Due to frosting at the outdoor heat exchanger and the automatical defrosting operation, the heating capacity of the
outdoor unit should be considered by multiplying the correction factor which shown in the table below.
(3)-1 Y series
(3)-2 R2 series
- 70 -
DATA BOOK PWFY-P100VM-E-BU
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
Issued in Aug. 2008 MEE08K022
Printed in Japan
HEA D OF FICE: TO KYO BLD G., 2-7-3 , MA RUNOUC HI, CHIYODA- KU, TOKYO 100-8 310, JAPAN
New publication effective Aug. 2008.
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.