Mitsubishi PWFY-P100VM-E-BU, PWFY-P100VM-E-AU, PWFY-P200VM-E-AU DATA BOOK

Models
PWFY-P100VM-E-BU PWFY-P100VM-E-AU PWFY-P200VM-E-AU
DATA BOOK
AIR CONDITIONERS
• Do not use steel pipes as water pipes.
- Copper pipes are recommended.
• The water circuit should be a closed circuit.
• Ask the dealer or an authorized technician to
install the air conditioner.
- Improper installation by the user may result in water
leakage, electric shock, or re.
• Install the unit in a place that can withstand its
weight.
- Inadequate strength may cause the unit to fall down,
resulting in injuries.
• Do not touch the unit. The unit surface can be hot.
• Do not install the unit where corrosive gas is
generated.
• Usethespeciedcablesforwiring.Makethe
connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate
heat and cause a re.
• Prepare for rain and other moisture and
earthquakesandinstalltheunitatthespecied
place.
- Improper installation may cause the unit to topple
and result in injury.
• Always use an strainer and other accessories
speciedbyMitsubishiElectric.
- Ask an authorized technician to install the accesso
-
ries. Improper installation by the user may result in
water leakage, electric shock, or re.
• Never repair the unit. If the air conditioner must
be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage,
electric shock, or re may result.
• Do not touch the refrigerant pipes and Water
pipes.
- Improper handling may result in injury.
• When handling this product, always wear protec
-
tive equipment.
 EG:Gloves,fullarmprotectionnamelyboilersuit,
and safety glasses.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a ame,
poisonous gases will be released.
• InstalltheunitaccordingtothisInstallationManu­al.
- If the unit is installed improperly, water leakage,
electric shock, or re may result.
• Have all electric work done by a licensed electri
-
cianaccordingto“ElectricFacilityEngineering
Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric
work is performed improperly, electric shock and re
may result.
• Keep the electric parts away from water (washing water etc.).
- It might result in electric shock, catching re or
smoke.
• Securely install the heat source unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly,
dust or water may enter the heat source unit and re
or electric shock may result.
• When installing and moving the air conditioner to another site, do not charge it with a refrigerant
differentfromtherefrigerant(R410A)speciedon
the unit.
- If a different refrigerant or air is mixed with the origi
­nal refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refriger
­ant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate meas
­ures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water
leakage, electric shock, or re may result.
- i -
• After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or other heat source, it may gen erate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other
protection device is shorted and operated forcibly,
or parts other than those specied by Mitsubishi Electric are used, re or explosion may result.
• To dispose of this product, consult your dealer.
• The installer and system specialist shall secure
-
safety against leakage according to local regula tion or standards.
- Following standards may be applicable if local regu lation are not available.
• Pay a special attention to the place, such as a
basement, etc. where refrigeration gas can stay, since refrigeration is heavier than the air.
-
-
• Do not use the existing refrigerant piping.
- The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to dete riorate.
- R410A is a high-pressure refrigerant and can cause the existing piping to burst.
• Use refrigerant piping made of C1220 (CU-DHP)
phosphorusdeoxidizedcopperasspeciedinthe
JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the in ner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav­ing particles, oils, moisture, or any other contami­nant.
- Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil to deteriorate.
• Store the piping to be used during installation
indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
• Use ester oil, ether oil or alkylbenzene (small
amount)astherefrigerantoiltocoataresand angeconnections.
- The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.
• Useliquidrefrigeranttollthesystem.
- If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
-
• Do not use a refrigerant other than R410A.
- If another refrigerant (R22, etc.) is mixed with
-
R410A, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
• Useavacuumpumpwithareverseowcheck
valve.
- The vacuum pump oil may ow back into the refrig
erant cycle and cause the refrigerant oil to deterio­rate.
• Do not use the following tools that are used with conventional refrigerants.
 (Gaugemanifold,chargehose,gasleakdetector,
reverseowcheckvalve,refrigerantchargebase,
refrigerant recovery equipment)
- If the conventional refrigerant and refrigerant oil are
mixed in the R410A, the refrigerant may deterio rated.
- If water is mixed in the R410A, the refrigerant oil
may deteriorate.
- Since R410A does not contain any chlorine, gas
leak detectors for conventional refrigerants will not react to it.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant
to deteriorate.
• Be especially careful when managing the tools.
- If dust, dirt, or water gets in the refrigerant cycle, the
refrigerant may deteriorate.
-
-
- ii -
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an
explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
• Do not use the air conditioner in special environ ments.
- Oil, steam, sulfuric smoke, etc. can signicantly reduce
the performance of the air conditioner or damage its parts.
-
• When installing the unit in a hospital, communica
tionstation,orsimilarplace,providesufcient
protection against noise.
- The inverter equipment, private power generator, high-frequency medical equipment, or radio commu nication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may
cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged, condensation may drip from the indoor unit. Perform collective drainage work together with the unit, as required.
-
-
- iii -
• Groundtheunit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or telephone ground lines. Improper grounding may result in electric shock.
• Install the power cable so that tension is not
applied to the cable.
- Tension may cause the cable to break and generate
heat and cause a re.
• Install a leak circuit breaker, as required.
- If a leak circuit breaker is not installed, electric shock may result.
• Usepowerlinecablesofsufcientcurrent
carrying capacity and rating.
- Cables that are too small may leak, generate heat,
and cause a re.
• Use only a circuit breaker and fuse of the
speciedcapacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit
failure or re.
• Do not wash the air conditioner units.
- Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall
and cause personal injury or property damage.
• Install the drain piping according to this
InstallationManualtoensureproperdrainage.
Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage and
damage to furniture and other possessions.
• Be very careful about product transportation.
- Only one person should not carry the product if it
weighs more than 20 kg.
- Some products use PP bands for packaging. Do not
use any PP bands for a means of transportation. It is dangerous.
- When transporting the unit, support it at the
specied positions on the unit base. Also support the
unit at four points so that it cannot slip side ways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or
wooden parts, may cause stabs or other injuries.
- Tear apart and throw away plastic packaging bags
so that children will not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
- iv -
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the
main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
• Donottouchtheswitcheswithwetngers.
- Touching a switch with wet ngers can cause elec
tric shock.
• Do not touch the refrigerant pipes during and im mediately after operation.
- During and immediately after operation, the
refrigerant pipes are may be hot and may be cold,
depending on the condition of the refrigerant owing
through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause
injuries.
-
• Do not turn off the power immediately after stopping operation.
- Always wait at least ve minutes before turning off
the power. Otherwise, water leakage and trouble may occur.
• Do not touch the surface of the compressor during servicing.
- If unit is connected to the supply and not running,
crank case heater at compressor is operating.
-
• Do not touch the panels near the fan exhaust
outletwithbarehands:theycangethotwhile
the unit is in operation (even if it is stopped) or immediately after operation and poses a risk of burns. Wear gloves to protect your hands when it is necessary to touch the panels.
• While the unit is in operation or immediately after operation, high-temperature exhaust air may blow out of the fan exhaust outlet. Do not hold your hands over the outlet or touch the panels near the outlet.
• Be sure to provide a pathway for the exhaust air from the fan.
• Water pipes can get very hot, depending on the preset temperature. Wrap the water pipes with insulating materials to prevent burns.
- v -
Contents
Safety Precautions
IGeneralEquipmentDescriptions
1. Unit conguration table ············································ 1
2. Operable temperature range ··································· 1
3. Connectable outdoor unit capacity range ················
IIProductSpecications
1. Specications ·························································· 2
2. External Dimensions
(1) PWFY-P100VM-E-BU
(2) PWFY-P100, 200VM-E-AU
3. Electrical Wiring Diagrams ······································
(1) PWFY-P100VM-E-BU
(2) PWFY-P100, 200VM-E-AU
4. Accessories ·····························································
················································ 5
III Product Data
1. Capacity tables ······················································ 10
(1) Correction by temperature
(2) Correction by water ow rate
(3) Correction by total indoor
(4) Correction by refrigerant piping length
(5) Correction at frosting and defrosting
(6) Water pressure drop
(7) Temperature range of running
2. Sound levels ·························································· 27
(1) PWFY-P100VM-E-BU
(2) PWFY-P100, 200VM-E-AU
3. Vibration levels ······················································
(1) PWFY-P100VM-E-BU
4. Refrigerant circuit diagrams and thermal sensors ····················································· 29
(1) PWFY-P100VM-E-BU
(2) PWFY-P100VM-E-AU
(3) PWFY-P200VM-E-AU
28
3. Water pipe installation ···········································
(1) Water circuit sample
(2) Selecting a water pump
(3) Installing the strainer
(4) Precautions during installation
1
(5) Example of unit installation (using light piping)
(6) Insulation installation
(7) Water processing and water quality control
(8) Pump interlock
V System Design
1. Electrical work ······················································· 42
7
(1) General cautions
(2) Power supply for PWFY unit
(3) Connecting remote controller, indoor and outdoor transmission cabls
9
(4) Transmission cable specications
(5) Connecting electrical connections
(6) Address setting
(7) External input/output function
VI Control
1. Dip switch functions ··············································· 50
2. Remote controller specications···························· 51
VIIMaintenanceCycle
1. Routine maintenance checks ································ 52
2. Parts Replacement Cycle ······································ 52
VIII Product Data (supplemental information for chapter III.)
1. Capacity tables ······················································ 53
(1) Correction by total indoor
(2) Correction by refrigerant piping length
(3) Correction at frosting and defrosting
37
IV Installation
1. How to calculate the necessary heat capacity······· 30
(1) Heating capacity calculation
(2) A calculation example
2. Installation ·····························································
(1) Selecting an installation site
(2) Installing the unit
(3) Refrigerant pipe and drain pipe specications
(4) Connecting refrigerant pipes and drain pipes
31
GeneralEquipmentDescriptions
2. Operable temperature range
3. Connectable outdoor unit capacity range
1. Unit configuration table
Model
Outdoor unit
PWFY-P100VM-E-BU PWFY-P200VM-E-AU
PURY-(E)P*Y(S)HM-A(-BS)
PUHY-(E)P* Y(S)HM-A(-BS)
PURY-(E)P* Y(S)HM-A(-BS)
PWFY-P100VM-E-AU
<PWFY-P100VM-E-BU>
10 to 70˚C
-20 to 32˚C
Inlet water temperature R2 series
R2 seriesOutdoor temperature
Heating
PWFY with
standard indoor unit
Only standard
indoor units
10 to 70˚C
-20 to 32˚C
-
-20 to 15.5˚C
Only PWFY
50 to 100%R2 series
PWFY with
standard indoor units
Only standard
indoor units
50 to 150% 50 to 150%
Only PWFY
Outdoor unit will change its software to PWFY connection version automatically when PWFY is connected. R2 series allow higher temperature range than Y series, the reason is that R2 has an effective heat exchanger bypass circuit against Hi-cut.
(WB)
<PWFY-P100, P200VM-E-AU>
<PWFY-P100VM-E-BU>
10 to 35˚C
10 to 35˚C
Inlet water temperature
R2 series
Y series
Heating
PWFY with standard indoor units
10 to 40˚C
10 to 40˚C
-5 to 43˚C
-5 to 43˚C
R2 series
Y series
Outdoor temperature
-20 to 32˚C
-20 to 15.5˚C
Only PWFY
(WB)
Cooling
10 to 35˚C
10 to 35˚C
Heating
10 to 40˚C
10 to 40˚C
-5 to 43˚C
-5 to 43˚C
-20 to 32˚C
-20 to 15.5˚C
Cooling
-
-
Inlet water temperature
R2 series
Y series
Heating
-
-
-5 to 43˚C
-5 to 43˚C
R2 series
Y series
Outdoor temperature
-20 to 15.5˚C
Only standard indoor units
(WB)
Cooling
50 to 100%R2 series
PWFY with
standard indoor units
Only standard
indoor units
50 to 150% 50 to 150%
Only PWFY
<PWFY-P100, P200VM-E-AU>
50 to 100%Y series
50 to 130% 50 to 130%
-20 to 15.5˚C
I
- 1 -
II
Model
Power source
kWHeating capacity kcal / h(Nominal ) Btu / h kW A W.B
dB<A> mm(in.) mm(in.) mm(in.) mm(in.) mm(in.)
mm in. kg(lb)
kW
-
Power input
Liquid Gas
Current input Outdoor temp. Inlet Water temp. Total capacity
Temp. range of heating Connectable outdoor unit
Model / Quantity
Noise level (measured in anechoic room) Diameter of refrigerant pipe Diameter of water pipe Field drain pipe size
External finish External dimension H × W × D
Net weight Compressor
Maker
Type
Starting method Motor output
Circulating water
Range Protection on Internal circuit (R134a)
High pressure protection
Inverter circuit (COMP)
Compressor
Type × original chargeRefrigerant
Control
R410aDesign pressure
R134a
Water
ExternalDrawing
Standard attachment
Optional parts
Remark
Note:
*1 Nominal heating conditions Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB)
kcal = kW × 860
Pipe length : 7.5 m (24-9/16 ft)
Btu/h = kW × 3,412
Level difference : 0m (0ft)
cfm = m3/min x 35.31
Inlet water Temp 65°C Water flow rate 2.15m3/h
lb = kg / 0.4536
* Due to continuing improvement, the above specifications may be subject to change without notice. * Install the unit in an environment where the
wet bulb Temp. will not exceed 32degC.
* The unit is not designed for outside installations.
* Please don't use the steel material for the water piping material. * The water circuit must use the closed circuit.
* Please do not use it as a drinking water.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less. * Please always make water circulate or pull out the circulation water completely when not using it. * Please do not use groundwater and well water.
* The specification data is subject to rounding variation.
Unit converter
Lubricant
Operation volume
Inlet
Outlet
Accessory
Wiring
Document
m3/h
MPa MPa MPa
1.00
Installation Manual, Instruction Book
800 (785 without legs) × 450 × 300
E64C226X01
Inverter
1.0
Over-heat protection, Over-current protection
R134a × 1.1kg (0.50lb)
10,800
12.5
WKB94L762
NONE
44
NO
Strainer, Heat insulation material, 2 × Connector sets
PWFY-P100VM-E-BU
1-phase 220-230-240V 50/60Hz
PT3/4 Screw
MITSUBISHI ELECTRIC CORPORATION
NEO22
Φ32 (1-1/4'')
Inverter rotary hermetic compressor
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16”
60 (133)
PT3/4 Screw
11.63 - 11.12 - 10.66
50~100% of outdoor unit capacity
PURY-P200YHM-A(-BS)~PURY-P400YHM-A(-BS) PURY-P450YSHM-A(-BS)~PURY-P800YSHM-A(-BS) PURY-EP200YHM-A(-BS)~PURY-EP300YHM-A(-BS)
PURY-EP400YSHM-A(-BS)~PURY-EP600YSHM-A(-BS)
Φ15.88 (Φ5/8") Brazed
-20~32°C (59~90°F)
Φ9.52 (Φ3/8") Brazed
42,700
10~70°C (50~158°F)
2.48
0.6~2.15
LEV
4.15
High pressure sensor, High pressure switch at 3.60 MPa (601 psi)
Discharge thermo protection, Over-current protection
3.60
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
ProductSpecications
1.Specications
- 2 -
Model
Power source
kW*1Heating capacity kcal / h Btu / h kW A W.B
*1(Nominal)
*1 Power input Current input Outdoor temp.
Temp. range of
W.B
-
heating
Inlet Water temp.
kW*2Cooling capacity kcal / h Btu / h kW A D.B
*2(Nominal)
*2 Power input Current input Outdoor temp.
Temp. range of cooling
D.B
-Inlet Water temp. Total capacity Model / Quantity
Connectable outdoor unit
Noise level (measured in anechoic room) dB<A>
mm(in.) mm(in.)
Diameter of refrigerant pipe
mm(in.) mm(in.)
Diameter of water pipe
mm(in.)
mm
Field drain pipe size
External finish External dimension H × W × D
in.
kg(lb)
Net weight Circulating water
Range
Design pressure
Water
R410a
Drawing
Standard attachment
Optional parts
Remark
Note:
*2 Nominal cooling conditions *1 Nominal heating conditions
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB) Outdoor Temp. : 35°CB (95°FDB)
kcal = kW × 860 Btu/h = kW × 3,412
Pipe length : 7.5 m (24-9/16 ft)Pipe length : 7.5 m (24-9/16 ft) Level difference : 0m (0ft)Level difference : 0m (0ft)
cfm = m3/min × 35.31
Inlet water Temp 30°C
Water flow rate 2.15m3/h
Inlet water Temp 23°C
Water flow rate 1.93m3/h * Install the unit in an environment where the
lb = kg / 0.4536
* Due to continuing improvement, the above specifications may be subject to change without notice.
wet bulb Temp. will not exceed 32degC. * The unit is not designed for outside installations. * Please don't use the steel material for the water piping material. * The water circuit must use the closed circuit. * Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less. * Please always make water circulate or pull out the circulation water completely when not using it.
Inlet Outlet
Operation Volume
Liquid Gas
m3/h
MPa
MPa
Accessory
External Wiring Document
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Unit converter
* The specification data is subject to rounding variation.
38,200
10~35°C (50~95°F)
0.015
Φ15.88 (Φ5/8") Brazed
Φ9.52 (Φ3/8") Brazed
PT3/4 Screw
Installation Manual, Instruction Book
PT3/4 Screw
NO
WKB94L763
0.068 - 0.065 - 0.063
50~100% of outdoor unit capacity
PURY-P200YHM-A(-BS)~PURY-P400YHM-A(-BS) PURY-P450YSHM-A(-BS)~PURY-P800YSHM-A(-BS) PURY-EP200YHM-A(-BS)~PURY-EP300YHM-A(-BS)
PURY-EP400YSHM-A(-BS)~PURY-EP600YSHM-A(-BS)
PUHY-P200YHM-A(-BS)~PUHY-P450YHM-A(-BS)
PUHY-P500YSHM-A(-BS)~PUHY-P1250YSHM-A(-BS)
PUHY-EP200YHM-A(-BS)~PUHY-EP300YHM-A(-BS)
PUHY-EP400YSHM-A(-BS)~PUHY-EP900YSHM-A(-BS)
-5~43°C (23~110°F) PURY - series
-5~43°C (23~110°F) PUHY - series
0.6~2.15
1.00
Strainer, Heat insulation material, 2 × Connector sets
Φ32 (1-1/4'')
PWFY-P100VM-E-AU
1-phase 220-230-240V 50/60Hz
9,600
11.2
29
12.5
800 (785 without legs) × 450 × 300
E00C223
4.15
NONE
10,800 42,700
-20~15.5°C (-4~60°F) PUHY - series 10~40°C (50~104°F)
0.015
0.068 - 0.065 - 0.063
-20~32°C (-4~90°F) PURY - series
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16”
35 (78)
* Please do not use it as a drinking water.
* Please do not use groundwater and well water.
- 3 -
Model
Power source
kW*1Heating capacity kcal / h Btu / h kW A W.B
*1(Nominal)
*1 Power input Current input Outdoor temp.
Temp. range of
W.B
-
heating
Inlet Water temp.
kW*2Cooling capacity kcal / h Btu / h kW A D.B
*2(Nominal)
*2 Power input Current input Outdoor temp.
Temp. range of cooling
D.B
-Inlet Water temp. Total capacity Model / Quantity
Connectable outdoor unit
Noise level (measured in anechoic room) dB<A>
mm(in.) mm(in.)
Diameter of refrigerant pipe
mm(in.) mm(in.)
Diameter of water pipe
mm(in.)
mm
Field drain pipe size
External finish External dimension H × W × D
in.
kg(lb)
Net weight Circulating water
Range
Design pressure
Water
R410a
Drawing
Standard attachment
Optional parts
Remark
Note:
Inlet Outlet
Operation Volume
Liquid Gas
m3/h
MPa
MPa
Accessory
External Wiring Document
Unit converter
*2 Nominal cooling conditions *1 Nominal heating conditions
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB) Outdoor Temp. : 35°CDB (95°FDB)
Pipe length : 7.5 m (24-9/16 ft)Pipe length : 7.5 m (24-9/16 ft) Level difference : 0m (0ft)
Level difference : 0m (0ft) Inlet water Temp 30°C
Water flow rate 4.30m3/h
Inlet water Temp 23°C
Water flow rate 3.86m3/h
* Due to continuing improvement, the above specifications may be subject to change without notice.
* Install the unit in an environment where the wet bulb Temp. will not exceed 32degC.
* The unit is not designed for outside installations. * Please don't use the steel material for the water piping material. * The water circuit must use the closed circuit. * Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less. * Please always make water circulate or pull out the circulation water completely when not using it.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
10~40°C (50~104°F)
0.015
0.068 - 0.065 - 0.063
-20~32°C (-4~90°F) PURY - series
21,500 85,300
-20~15.5°C (-4~60°F) PUHY - series
E94C228X01
NONE
Φ32 (1-1/4'')
PWFY-P200VM-E-AU
1-phase 220-230-240V 50/60Hz
19,300
22.4
29
25.0
1.2~4.30
1.00
Strainer, Connecter, Heat insulation material, 2 × Connector sets, Expansion joint
PT 1 Screw
Installation Manual, Instruction Book
NO
WKB94L763
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16”
38 (84)
800 (785 without legs) × 450 × 300
4.15
0.015
Φ19.05 (Φ3/4") Brazed
Φ9.52 (Φ3/8") Brazed
PT 1 Screw
0.068 - 0.065 - 0.063
76,400
10~35°C (50~95°F)
50~100% of outdoor unit capacity
PURY-P200YHM-A(-BS)~PURY-P400YHM-A(-BS) PURY-P450YSHM-A(-BS)~PURY-P800YSHM-A(-BS) PURY-EP200YHM-A(-BS)~PURY-EP300YHM-A(-BS)
PURY-EP400YSHM-A(-BS)~PURY-EP600YSHM-A(-BS)
PUHY-P200YHM-A(-BS)~PUHY-P450YHM-A(-BS)
PUHY-P500YSHM-A(-BS)~PUHY-P1250YSHM-A(-BS)
PUHY-EP200YHM-A(-BS)~PUHY-EP300YHM-A(-BS)
PUHY-EP400YSHM-A(-BS)~PUHY-EP900YSHM-A(-BS)
-5~43°C (23~110°F) PURY - series
-5~43°C (23~110°F) PUHY - series
kcal = kW × 860
Btu/h = kW × 3,412
cfm = m3/min × 35.31 lb = kg / 0.4536 * The specification data is subject to rounding variation.
* Please do not use it as a drinking water.
* Please do not use groundwater and well water.
- 4 -
2.ExternalDimensions
Piping space
(right side)
Fig. A
Service space
(front side)
Top view
300
400
600
ø27 Knockout hole
<Hole for external wiring output>
Drain (R1 screw)
Control box
Water outlet
(RC3/4 screw)
ø
27 Knockout hole
<Hole for external wiring input>
ø27 Knockout hole
<Hole for power supply>
ø27 Knockout hole
<Hole for control wiring>
Service panel
Top view
Right side view
Front view
2X2-
ø
14 Hole
Connection pipe of outdoor unit
(Liquid)
ø
15.88 <Brazed>
ø9.52 <Brazed>
Connection pipe of outdoor unit
(Gas)
Water inlet
(R3/4 screw)
525
(Mounting pitch)
(Mounting pitch)
205
800 300
450
500
55
35
35
91
91
134
480
46
60140
100191
80165
102
54
184
114
Note 1.Ensure no rain water or debris can enter the unit through any gaps around
wiring or piping.
2.Ensure adequate service space is right around the unit, according to Fig A.
3.Please always make water circulate or add the brine to the circulation water
when the ambient temperature becomes 0°C or less.
4.The unit is not designed for outside installations.
5.Install the unit in an environment where the wet bulb Temp.
will not exceed 32degC.
6.Please always make water circulate or pull out the circulation
water completely when not using it.
7.The water circuit must use the closed circuit.
8.Please don't use the steel material for the water piping material.
9.Connect the strainer which is put as accessory to water inlet pipe.
<Accessories>
●Y-type strainer (RC3/4) ·························· 1pc.
●Heat Insulation material ························· 1pc.
●Connector set ········································ 2set
<Unit:mm>
(1) PWFY-P100VM-E-BU
- 5 -
(2) PWFY-P100, 200VM-E-AU
300600
Fig. A
Service space
(front side)
Top view
400
Piping space
(right side)
P200:Use the Expansion joint
of accessories
Drain (R1 screw)
ø9.52 <Brazed>
ø27 Knockout hole
<Hole for control wiring>
ø27 Knockout hole
<Hole for power supply>
Water outlet
(RC3/4 screw)
Water inlet
(R3/4 screw)
P100:ø15.88 <Brazed>
P200:ø19.05 <Brazed>
ø27 Knockout hole
<Hole for external wiring input>
ø27 Knockout hole
<Hole for external wiring output>
Connection pipe of outdoor unit
(Gas)
Connection pipe of outdoor unit
(Liquid)
Front view
Right side view
Control box
Service panel
Top view
2X2-
ø
14 Hole
525
(Mounting pitch)
450
(Mounting pitch)
300800
205
500
<Accessories>
●Y-type strainer (RC3/4)
·····························
1pc.
●Heat Insulation material
····························
1pc.
●Connector set
············································
2set
●Expansion joint (P200)
······························
2pc.
[From RC3/4 to RC1]
Note 1.Ensure no rain water or debris can enter the unit through any gaps around
wiring or piping.
2.Ensure adequate service space is right around the unit, according to Fig A.
3.Please always make water circulate or add the brine to the circulation water
when the ambient temperature becomes 0
°C
or less.
4.The unit is not designed for outside installations.
5.Install the unit in an environment where the wet bulb Temp.
will not exceed 32degC.
6.Please always make water circulate or pull out the circulation
water completely when not using it.
7.The water circuit must use the closed circuit.
8.Please don't use the steel material for the water piping material.
9.Connect the strainer which is put as accessory to water inlet pipe.
91
91
35
55
35
480102
206
134
114
100191
46
6014080165
54
<Unit:mm>
- 6 -
3.ElectricalWiringDiagrams
M
4-20mA
4-20mA
gray
2
1
gray
black
To outdoor unit/
BC controller
To MA remote
controller
Power Supply
~220/230/240V
50Hz/60Hz
3
2
1
blue
red
yellow/green
bluered
CN4
63LS
CN63HS
1
1
3
2
2
3
THHS
12
CN63LS
123
TH8
2
1
CN403
red
TH6
1 2
CN404
black
3 1
CT1
Moter
3~
CYN
RS4
MS
RS3
(Compressor)
CN3A
blue
U
red
yellow
TH22
CN405
IPM
W
V
U
black
1
63HS
7
2
1
3
1
2
CN3
2
1
CN401
CN2
2 56
red
CN5
2
1
TH11
1 2
TH13
2
1
white
CN402
green
red
5
6
RS1
black
2
CN52C
R1
LO
U
CNAC2
red
2
CN5
1
1
2
red
blue
red
LEV2W
M
LI
24V
blue
+
CB3
Z2
1
U
CT1
LEV1W
1
CN2
63H1
6
5
CNAC
2
red
1
CX2
L
CN506A
L3
N
6
5
N
CN-E1
CN631
DSA
pink
E2
3
1
E1
432
1
CY4
P
CY3
31
L4
Z1
NI
CB1
+
1
TB2
CN661
2L23
X506
W
4
CN4
blue
U
CN52C
1 2
+
CX3
INV control
circuit
PFC
E3
1
L1
2
M
ZNR01
ACL
CY1CY2
CT2
Noise
Filter
red
Fan motor
1
3
(DC)
CX5
CYP
CIS
CX6
1 2
7
V
yellow
LED3:Lit when powered
INV Board
Control Board
CB2
(DC)
CY6
S
CX4
R
CNAC1
M
CNLVA
NO
Fan motor
3
1 2
RS2
CY5
P
CNLVB
blue
CX1
CX7
CN506B
CPS
+
RS
F01
AC250V
6.3A
F631
DC700V
4A
Power
Supply circuit
blue
red
TB5
M1 M2
S(SHIELD) S(SHIELD)
TB15
yellow
purple
black
orange
gray
red
black
white
gray
gray
52C
1 2
CN2M
blue
3 1
*4
IN2
TB141B
TB142B
IN6
COM+
OUT5
TB142C
OUT7
OUT6
X515 X517
X516
IN8
IN5 IN7
TB142A
X514
OUT2
X512
X511 X513
OUT1 OUT3
OUT4
TB141A
*5 *6 *7
IN3 IN4
COM+
LED4:Remote controller
when powered
SWU1
10
SW1
5
ON
OFF
1
Unit address setting(SWU1,SWU2)
Connection No.(SWU3)
LED1 Display setting(SW2)
Function setting(SW1,SW3,SW4)
SWP3
SW5
SWP1
SWU3
SWP2
SWU2
OFF
ON
1 10
SW4
OFF
ON
1 10
LED1
OFF
ON
1
SW3
OFF
ON
1 10
SW2
IN1
gray
CN421
black
3 1
CN422
blue
IN1
IN2
3 1
CN421
black
3 1
CN422
blue
2
2
2
2
BC controller/outdoor unit
Booster unit
Linear
expansion valve
LEV1W
LEV2W
IN7 Anti-freeze
IN6 Heating ECO
Symbol
Function
COM+ Common
IN5 Hot water
IN4 Operation ON/OFF
Connection demand
Symbol
IN3
Function
Symbol
Pump interlock
Function
IN1
*4 TB141A(output)
*5 TB142A(input)
*6 TB142B(input)
*7 TB142C(input)
Function
Symbol
OUT1 Operation ON/OFF
OUT2 Defrost
OUT3 Compressor
OUT4 Error signal
<HIGH VOLTAGE WARNING>
·Control box houses high-voltage parts.
Before inspecting the inside of the control box, turn off the power,
keep the unit off for at least 10 minutes,and confirm that the voltage
CN631 on Control Board has dropped to DC20V or less.
<CAUTION FOR INSTALLATION>
·Prior to installation,read the Installation Manual carefully.
*1.Single-dotted lines indicate wiring not supplied with the unit.
*2.Dot-dash lines indicate the control box boundaries.
*3.Faston terminals have a locking function.
Make sure the terminals are securely locked in place after insertion.
Press the tab on the terminals to removed them.
TH8 water outlet temp
TH6 water inlet temp
TH22 liquid pipe temp
TH13 Evaporator outlet temp
Compressor discharge tempTH11 Thermistor
TB15 MA remote controller
TB5 Outdoor unit/BC controller
AC reactor
Pressure
switch
High pressure switch
(High pressure protection for the booster unit)
Discharge pressure
Low pressure
TB2
CT1,CT2
ACL
THHS
Magnetic relay(main circuit)
Current sensor(AC)
Explanation
Terminal
block
Power supply
IGBT temp
Pressure
sensor
Symbol
63H1
63HS
63LS
52C
<Symbol explanation>
(1) PWFY-P100VM-E-BU
- 7 -
(2) PWFY-P100, 200VM-E-AU
gray
red
M
For opening/closing the bypass circuit
Solenoid valve
SV1
IN1
TB5
M1 M2
S(SHIELD)
To outdoor unit/
BC controller/
4-20mA
4-20mA
132
CN421
black
132
CN422
blue
132
CN422
blue
2
black
CN421
13
IN1
234
5
yellow/green
LEV1Wa
LEV1Wb
Linear
expansion valve
BC controller/outdoor unit
BC controller/outdoor unit
Function
Function
Function
black
yellow purple
bluered
NL
IN7
IN8IN6
IN5COM+
IN4IN3
orange
*3.Difference of appliance
*4 TB141A(output)
*5 TB142A(input)
*6 TB142B(input)
*7 TB142C(input)
Model name
Appliance
P100 *3 do not exist
P200 *3 exist
*7*6*5
*4
Cooling
TH23 gas pipe temp
CN502
black
COM+
TH8
TH6
TH23
blue
CN2M
2
1
2
1
CN402
green
2
1
CN403
red
1 2
CN404
black
yellow
CN405
TH22
1 2
21
To MA remote
controller
Power Supply
~220/230/240V
50Hz/60Hz
Unit address setting(SWU1,SWU2)
Connection No.(SWU3)
LED1
TB15
ZNR1
U
DSA1
CN1
1
3
SWU2
SWU1
SWP3
SWP2
SWP1
OFF
ON
1 10
SW4
OFF
ON
1 10
SW3
OFF
ON
1 10
SW1
OFF
ON
1 10
SW2
LED4:Remote controller
when powered
5
CNLVC
6
1
LEV1Wb
123
4
X502
CN507
3
1
M
5
6
ON
OFF
1
SW5
SWU3
LED3:Lit when powered
Control Board
CNLVB
LEV1Wa
TB2
SV1
*3
DSA Board
CN3T
red
13
T01
ZNR01
3
1
1
2
CNAC
red
U
F01
AC250V
6.3A
LED1 Display setting(SW2)
Function setting(SW1,SW3,SW4)
OUT4
OUT3
OUT2
X514
X513
X512
TB141A
OUT1
X511
3 1
CN3A
blue
TB142CTB142B
X516
X517X515
OUT6
OUT7OUT5
TB141B
TB142A
IN2
IN8
IN7 Anti-freeze
IN6 Heating ECO
Symbol
COM+ Common
IN5 Heating
IN4 Operation ON/OFF
Connection demand
Symbol
IN3
Symbol
Pump interlockIN1
Function
Symbol
OUT1 Operation ON/OFF
OUT2 Defrost
OUT4 Error signal
<CAUTION FOR INSTALLATION>
·
Prior to installation,read the Installation Manual carefully.
*1.Single-dotted lines indicate wiring not supplied with the unit.
*2.Dot-dash lines indicate the control box boundaries.
TH8 water outlet temp
TH6 water inlet temp
TH22 liquid pipe temp
Thermistor
TB15 MA remote controller
TB5 Outdoor unit/BC controller
TB2
Explanation
Terminal
block
Power supply
Symbol
<Symbol explanation>
- 8 -
4. Accessories
(A) Strainer (B) Heat insulation material
*1
*1. PWFY-P200VM-E-AU only
(C) Connecter sets 2 (D) Expansion joint 2
(A) Install the strainer at the water pipe inlet. (B) This insulation is for exclusive use with the strainer. Wrap the strainer with the insulation after water pipes are
installed. (C) These are analog input connectors. Cut the wire before using.
(D) Supplied only with the PWFY-P200VM-E-AU. Install them at the strainer inlet. Refer to P39 for details.
- 9 -
III
PURY- P200,250YHM-A
EP200YHM-A
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of heating capacity
30°C
20°C
10°C
40°C
50°C
60°C
65°C
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of booster unit input
65°C
60°C
50°C
40°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
50°C
60°C
65°C
30°C
20°C
10°C
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
Product Data
1. Capacity tables
(1) Correction by temperature
(1)-1 PWFY-P100VM-E-BU
- 10 -
PURY- P300,350,400YHM-A EP300,400YHM-A
Outdoor temp. [°CWB]
Ratio of heating capacity
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of booster unit input
65°C
60°C
50°C
40°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
50°C
60°C
65°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
30°C
20°C
10°C
40°C
50°C
60°C
65°C
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
- 11 -
30°C
20°C
10°C
40°C
50°C
60°C
65°C
PURY- P450,500,550,600,650YHM-A EP450,500,550,600YHM-A
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of heating capacity
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of booster unit input
65°C
60°C
50°C
40°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
50°C
60°C
65°C
30°C
20°C
10°C
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
- 12 -
PURY- P700,750,800YHM-A
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Ratio of heating capacity
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Ratio of booster unit input
65°C
60°C
50°C
40°C
30°C
20°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Ratio of outdoor unit input
40°C
50°C
60°C
65°C
30°C
20°C
10°C
Outdoor temp. [°CWB]
Outdoor temp. [°CWB]
Outdoor temp. [°CWB]
30°C
20°C
10°C
40°C
50°C 60°C
65°C
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
- 13 -
(1)-2 PWFY-P100, 200VM-E-AU
PUHY- P200,250YHM-A EP200YHM-A
Heating
Cooling
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
30°C
20°C
10°C
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Outdoor temp. [°CWB]
Ratio of heating capacity
10°C
20°C
30°C
40°C
Inlet water temp.
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
Outdoor temp. [°CDB]
Ratio of cooling capacity
35°C
30°C 25°C
20
°C
15°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Outdoor temp. [°CDB]
Ratio of outdoor unit input
35°C 30°C 25°C 20°C 15°C
10
°C
Inlet water temp.
Inlet water temp.
Inlet water temp.
-20
-15
-10 -5
0
5
10
15
-20
-15
-10 -5
0
5
10
15
-5
0
5
10
15
20
25
30
35
40
-5
0
5
10
15
20
25
30
35
40
- 14 -
Heating
Cooling
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
30°C
20°C
10°C
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Outdoor temp. [°CWB]
Ratio of heating capacity
10°C
20°C
30°C
40°C
Inlet water temp.
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
Outdoor temp. [°CDB]
Ratio of cooling capacity
35°C
30°C 25°C
20
°C
15°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Outdoor temp. [°CDB]
Ratio of outdoor unit input
35°C 30°C 25°C 20°C 15°C
10
°C
Inlet water temp.
Inlet water temp.
Inlet water temp.
EP300,400YHM-APUHY- P300,350,400YHM-A
-20
-15
-10 -5
0
5
10
15
-20
-15 -10 -5
0
5
10
15
-5
0
5
10
15
20
25
30
35
40
-5
0
5
10
15
20
25
30
35
40
- 15 -
PUHY- P450,500,550,600,650YHM-A EP450,500,550,600,650YHM-A
Heating
Cooling
Outdoor temp. [°CWB]
Ratio of outdoor unit input
Inlet water temp.
Inlet water temp.
Outdoor temp. [°CWB]
Ratio of heating capacity
Inlet water temp.
Outdoor temp. [°CDB]
Ratio of cooling capacity
Outdoor temp. [°CDB]
Ratio of outdoor unit input
Inlet water temp.
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3 10°C
20°C
30°C
40°C
40°C
30°C
20°C
10°C
35°C 30°C
25°C
20°C
15°C
10°C
35°C
30°C
25°C 20°C
15°C 10°C
-20
-15
-10 -5
0
5
10
15
-20
-15
-10 -5
0
5
10
15
-5
0
5
10
15
20
25
30
35
40
-5
0
5
10
15
20
25
30
35
40
- 16 -
PUHY- EP700,750,800YHM-A
Heating
Cooling
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
30°C
20°C
10°C
Inlet water temp.
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Outdoor temp. [°CWB]
Ratio of heating capacity
Inlet water temp.
10°C
20°C
30°C
40°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
Outdoor temp. [°CDB]
Ratio of cooling capacity
Inlet water temp.
35°C
30°C
25°C
20°C
15°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Outdoor temp. [°CDB]
Ratio of outdoor unit input
Inlet water temp.
30°C
35°C
25°C
20°C 15°C 10°C
-20
-15
-10 -5
0
5
10
15
-20
-15 -10 -5
0
5
10
15
-5
0
5
10
15
20
25
30
35
40
-5
0
5
10
15
20
25
30
35
40
P700,750,800YHM-A
- 17 -
PUHY- P850,900,950,1000,1050,1100,1150,1200,1250YHM-A EP850,900YHM-A
Heating
Cooling
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor temp. [°CWB]
Ratio of outdoor unit input
40°C
30°C
20°C
10°C
Inlet water temp.
Inlet water temp.
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Outdoor temp. [°CWB]
Ratio of heating capacity
Inlet water temp.
10°C
20°C
30°C
40°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
Outdoor temp. [°CDB]
Ratio of cooling capacity
35°C
30°C
25°C
20°C
15°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Outdoor temp. [°CDB]
Ratio of outdoor unit input
Inlet water temp.
30°C
35°C
25°C
20°C
15°C
10°C
-20
-15 -10 -5
0
5
10
15
-20
-15 -10 -5
0
5
10
15
-5
0
5
10
15
20
25
30
35
40
-5
0
5
10
15
20
25
30
35
40
- 18 -
PURY- P200,250YHM-A EP200YHM-A
Heating
Cooling
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
-5 5 15 25 35
35°C
30°C
25°C
20°C
15°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
-5 5 15 25 35
35°C
30°C
25°C
20°C
15°C
10°C
Inlet water temp.
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Outdoor Temp. [°CWB]
Ratio of heating capacity
40°C
10°C
20°C
30°C
Inlet Water Temp.
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor Temp. [°CWB]
Ratio of outdoor unit input
Inlet Water Temp.
Inlet Water Temp.
-20
-15
-10
0-5
5
10
15
20
25
30
-20
-15
-10
0-5
5
10
15
20
25
30
40°C
30°C
20°C
10°C
1.4
Outdoor temp. [°CDB]
Ratio of cooling capacity
Outdoor temp. [°CDB]
Ratio of outdoor unit input
- 19 -
PURY- P300,350,400YHM-A
EP300,400YHM-A
Heating
Cooling
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
35°C
30°C
25°C
20°C
15°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Inlet water temp.
30°C
35°C
25°C
20°C
15°C
10°C
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Outdoor Temp. [°CWB]
Ratio of heating capacity
40°C
10°C
20°C
30°C
Inlet Water Temp.
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor Temp. [°CWB]
Ratio of outdoor unit input
40°C
30°C
20°C
10°C
Inlet Water Temp.
Inlet Water Temp.
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15
-10 -5
0
5
10
15 20 25 30
-5
5
15
25
35
-5
5
15
25
35
Outdoor temp. [°CDB]
Ratio of cooling capacity
Outdoor temp. [°CDB]
Ratio of outdoor unit input
- 20 -
PURY- P450,500,550,600,650YHM-A EP450,500,550,600YHM-A
Heating
Cooling
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
35°C 30°C 25°C
20°C
15°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Inlet water temp. 35°C
30°C 25°C
20°C
15°C
10°C
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Outdoor Temp. [°CWB]
Ratio of heating capacity
40°C
10°C
20°C
30°C
Inlet Water Temp.
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor Temp. [°CWB]
Ratio of outdoor unit input
40°C
30°C
20°C
10°C
Inlet Water Temp.
Inlet Water Temp.
-20
-15
-10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
-5
5
15
25
35
-5
5
15
25
35
Outdoor temp. [°CDB]
Ratio of cooling capacity
Outdoor temp. [°CDB]
Ratio of outdoor unit input
- 21 -
PURY- P700,750,800YHM-A
Heating
Cooling
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
Inlet water temp.
35°C 30°C 25°C 20
°C
15°C
10°C
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
Inlet water temp.
35°C 30°C 25°C 20°C 15°C 10°C
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Outdoor Temp. [°CWB]
Ratio of heating capacity
40
°C
10°C 20°C 30°C
Inlet Water Temp.
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor Temp. [°CWB]
Ratio of outdoor unit input
40°C 30°C
Inlet Water Temp.
20°C 10°C
-20
-15 -10 -5
0
5
10
15 20 25 30
-20
-15 -10 -5
0
5
10
15 20 25 30
-5
5
15
25
35
-5
5
15
25
35
Outdoor temp. [°CDB]
Ratio of cooling capacity
Outdoor temp. [°CDB]
Ratio of outdoor unit input
- 22 -
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
1.20
Water Flow rate [m3/h]
Ratio of heating capacity
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
1.20
Water Flow rate [m3/h]
Ratio of booster unit input
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
1.20
Water Flow rate [m3/h]
Ratio of outdoor unit input
(2) Correction by water flow rate
<PWFY-P100VM-E-BU>
0.5
1
1.5
2
0.5
1
1.5
2
0.5
1
1.5
2
(2) Correction by water ow rate
(2)-1 PWFY-P100VM-E-BU
- 23 -
(2)-2 PWFY-P100VM-E-AU
<PWFY-P100VM-E-AU>
Heating Cooling
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
0.5 1.0 1.5 2.0
0.5 1.0 1.5 2.0
0.5 1.0 1.5 2.0
0.5 1.0 1.5 2.0
Water flow rate [m3/h]
Ratio of heating capacity
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Water flow rate [m3/h]
Ratio of outdoor unit input
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Water flow rate [m3/h]
Ratio of cooling capacity
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Water flow rate [m3/h]
Ratio of outdoor unit input
<PWFY-P100VM-E-AU>
Heating Cooling
<PWFY-P200VM-E-AU>
Heating Cooling
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
0.5 1.0 1.5 2.0
0.5 1.0 1.5 2.0
0.5 1.0 1.5 2.0
0.5 1.0 1.5 2.0
Water flow rate [m3/h]
Ratio of heating capacity
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Water flow rate [m3/h]
Ratio of outdoor unit input
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Water flow rate [m3/h]
Ratio of cooling capacity
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Water flow rate [m3/h]
Ratio of outdoor unit input
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
Water flow rate [m3/h]
Ratio of heating capacity
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Water flow rate [m3/h]
Ratio of outdoor unit input
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Water flow rate [m3/h]
Ratio of cooling capacity
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Water flow rate [m3/h]
Ratio of outdoor unit input
(2)-3 PWFY-P200VM-E-AU
- 24 -
0
10
20
30
40
50
0.5 1 1.5 2
Water flow rate [m3/h]
Water-pressure drop [kPa]
Refer to Chapter .
Refer to Chapter .
Refer to Chapter .
(3) Correction by total indoor
(6) Water pressure drop
<PWFY-P100/P200VM-E-AU>
0
10
20
30
40
50
60
70
80
90
100
Water flow rate [m3/h]
Water-pressure drop [kPa]
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
0.5
1
1.5
2
2.5
3
3.5
4
4.5
Refer to Chapter IX.
(4) Correction by refrigerant piping length
Refer to Chapter IX.
(5) Correction at frosting and defrosting
Refer to Chapter IX.
(6) Water pressure drop
(6)-1 PWFY-P100VM-E-BU
(6)-2 PWFY-P100, 200VM-E-AU
- 25 -
(7) Temperature range of running
<PWFY-P100VM-E-BU>
Heating
0
10
20
30
40
50
60
70
80
Outdoor temp. [°CWB]
Inlet water temp. [°C]
-5-10-15-20
0
5
10
15
20
25
30 35 40
Heating
Cooling
0
10
20
30
40
50
Outdoor temp. [°CWB]
Inlet water temp. [°C]
0
10
20
30
40
50
Outdoor temp. [°CDB]
Inlet water temp. [°C]
PUHY-(E)P.Y(S)HM-A(-BS)
PURY-(E)P.Y(S)HM-A(-BS)
-5-10-15-20
0
5
10
15
20
25
30
35
40 45 50
-5
-10-15-20
0
5
10
15
20
25
30
35
40 45 50
0
10
20
30
40
50
Outdoor temp. [°CWB]
Inlet water temp. [°C]
-5
-10-15-20
0
5
10
15
20
25
30
35
40 45 50
(7) Temperature range of running
(7)-1 PWFY-P100VM-E-BU
(7)-2 PWFY-P100, 200VM-E-AU
- 26 -
2. Sound levels
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Sound level of PWFY-P100VM-E-BU
Measurement condition PWFY-P100VM-E-BU
50/60Hz
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Sound level of PWFY-P100, 200VM-E-AU
Approximate minimum audible limit on continuous noise
dB(A)
29.0
8k
12.0
4k
15.0
2k
14.5
1k
22.5
500k
25.0
250
33.0
125
32.0
63
42.0
50/60Hz
dB(A)
44.0
8k
27.0
4k
27.5
2k
32.0
1k
39.0
500k
42.0
250
37.0
125
53.5
63
41.0
Measurement condition PWFY-P100, 200VM-E-AU
Measurement location
1m
1m
Measurement location
1m
1m
Octave band center frequency <Hz>
(1) PWFY-P100VM-E-BU
(2) PWFY-P100, 200VM-E-AU
- 27 -
3. Vibration levels
PWFY-P100VM-E-BU
PWFY-P100VM-E-BU
Model Vibration Levels[dBA]
34
10cm
20cm
Measurement location
Service panel
Concrete
VIBRATION LEVELS
(1) PWFY-P100VM-E-BU
- 28 -
TH6
TH23
LEV1Wa
TH8
TH22
SV1
CV1
ST2
ST3
Water inlet
Water outlet
screw
screw
Hex
Hex
Brazed
Brazed
TH6
TH23
LEV1Wa
TH8
TH22
LEV1Wb
SV1
ST2
ST4
CV1
Water inlet
Water outlet
screw
screw
Brazed
Brazed
4. Refrigerant circuit diagrams and thermal sensors
Refrigerant Circuit Diagrams And Termal Sensors
TH11
63H1
63HS
63LS
TH13
TH22
LEV1W
LEV2W
COMP
Water outlet
TH6
TH8
ST3
ST1
ST2
CJ
Brazed
Brazed
screw
screw
Water inlet
Hex
Hex
(1) PWFY-P100VM-E-BU
(2) PWFY-P100VM-E-AU
(3) PWFY-P200VM-E-AU
- 29 -
+
+
A
. For Air conditioning using such as Panel Heaters, Floor Heating and Fan coil units
Required total heating capacity kW Safety factor; %
B. For Sanitary use such as Shower and Bathrooms
Conditions
Tank inlet water Temp.; °C Tank outlet water Temp.; °C
(Set Temp -5 °C) Safety factor for Heat Loss; % Operating time; Hours For Shower; /person x Person = (Water Temp. Condition °C)
°C)
For Bathrooms; /Person x Person = (Water Temp. Condition (The examples of water volume might be need to be changed as you need.)
The conversion of water volume to °C
x ( - ) / ( - ) + x ( - ) / ( - ) = ℓ /day
Heating Capacity Calculation for sanitary usage
/
1,000 x ( - ) = M cal / day
The conversion of M cal to kW
/ 860 x 1,000 /
= kW
C. Total (A+B)
Total Heating Capacity
x
(100%
+x
(100%
%) +
x (100% %) = kW
D. No. of units required
Safety factor; %
%) / 12.5 kW = units
units are required
TankPWFY unit
4
3 3
3
3
7
IV
+
+
A
. For Air conditioning using such as Panel Heaters, Floor Heating and Fan coil units
Required total heating capacity 20
10
10 60
60
15
8 20 30
1,200
240
40 45
1,200
240
40
45
10
10
60
60
10
10
888
888
44.4
20
29.42 20
3
2.82
10
20
6.45 15 29.42
8 6.45
60 10 44.4
kW
Safety factor; %
B. For Sanitary use such as Shower and Bathrooms
Conditions
Tank inlet water Temp.; °C Tank outlet water Temp.; °C
(Set Temp -5 °C) Safety factor for Heat Loss; % Operating time; Hours For Shower; 60 /person x Person = (Water Temp. Condition °C)
°C)
For Bathrooms; 8 /Person x Person = (Water Temp. Condition (The examples of water volume might be need to be changed as you need.)
The conversion of water volume to °C
x ( - ) / ( - ) + x ( - ) / ( - ) = ℓ /day
Heating Capacity Calculation for sanitary usage
/1,000 x ( - ) = M cal / day
The conversion of M cal to kW
/ 860 x 1,000 /
= kW
C. Total (A+B)
Total Heating Capacity
x
(100%
+x
(100%
%) +
x (100% %) = kW
D. No. of units required
Safety factor; %
%) / 12.5 kW = units
units are required
TankPWFY unit
4
3 3
3
3
7
Installation
1. How to calculate the necessary heat capacity
(1) Heating capacity calculation
(2) A calculation example
- 30 -
2. Installation
(B)
a
b
c
(C)
(A)
(1) Selecting an installation site
• Do not install outdoors. The unit is not waterproof.
• BackupsystemisrecommendedincaseofPWFYunitbreakdown.
• The unit will get hot. Do not install in a location where heat gets trapped inside.
• Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
• Do not install the unit where corrosive gas is generated.
• Have installation work in order to protect against earthquake.
 Anyinstallationdeciencymaycauseunittofalldown,resultinginapersonalinjury.
• Pay a special attention to the place, such as a basement, etc. where refrigeration gas can stay, since refrigera tion is heavier than the air.
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Wheninstallingtheunitinahospital,communicationstation,orsimilarplace,providesufcientprotection
against noise.
- The inverter equipment, private power generator, high-frequency medical equipment, or radio communication
equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged, condensation may drip from the indoor
unit. Perform collective drainage work together with the unit, as required.
-
(1)-1 Securing installation and service space
Please allow for the following service spaces after installation.
(All servicing can be performed from the front of the unit) [Fig. IV. 2. (1). 1]
(A) Piping space (right side)
(B) Top view
(C) Service space (front side)
Warning:
• Be sure to install the unit in a location which can adequately support its weight.
- If there is insufcient strength to support the unit’s weight, it could fall and cause injuries.
(1)-2 Combining indoor units with BC controllers and outdoor units
For combining indoor units with BC controllers and outdoor units, refer to section BC controllers and outdoor units
installation manual.
- 31 -
(2) Installing the unit
X Y Z
272 355 119
Model PWFY-P100VM-E-BU
450 300
800
Y
X Z
500
525
13 47 205
(2)-1 Lifting method
Caution:
Be very careful when carrying the product.
- Do not have only one person to carry product if it is more than 20 kg.
- Do not tilt the unit while transporting.
- PP bands are used to pack some products. Do not use them as a mean for transportation because they are
dangerous.
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may
suffocate children to death.
(2)-2 Product net weight
Model
Net weight
(2)-3 Center of gravity
(2)-3-1 PWFY-P100VM-E-BU
PWFY-P100VM-E-BU
60 kg
PWFY-P100VM-E-AU
35 kg
PWFY-P200VM-E-AU
38 kg
- 32 -
(A)
(B)
205
300
450
500
525
(2)-3-2 PWFY-P100, 200VM-E-AU
X 289 277
Model PWFY-P100VM-E-AU PWFY-P200VM-E-AU
Z
103
99
Y 346 347
20513
X
Y
800
500
525
300
450
Z
47
(2)-4 Installation method
Using the anchoring holes shown below, rmly bolt the unit to the base.
[Fig. IV. 2. (2). 1]
(A) 4-ø14 (Anchoring hole)
(B) (Top view)
Bases
Be sure to install unit in a place strong enough to withstand its weight. If the base is unstable, reinforce with a con
crete base.
The unit must be anchored on a level surface. Use a level to check after installation.
If the unit is installed near a room where noise is a problem, using an anti-vibration stand on the base of the unit is recommended.
- 33 -
-
(3) Refrigerant pipe and drain pipe specications
(D)
(A)
(B)
(C)
(E)
480
100191
54
102
114
134
184 (206*1)
(3)-1 Refrigerant pipe and drain pipe specications
To avoid dew drops, provide sufcient antisweating and insulating work to the refrigerant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commercially available insulating material (with a heat-resisting temperature of more than 100 °C and thickness given below) onto both liquid and gas pipes.
Be also sure to wind commercially available insulating material (with a form polyethylene’s specic gravity of 0.03 and
thickness given below) onto all pipes which pass through rooms.
1) Select the thickness of insulating material by pipe size.
Model
Gas
Liquid
Drain
Insulating material's thickness
PWFY-P100VM-E-BU
ø
15.88
ø
9.52
PWFY-P100VM-E-AU
ø
15.88
ø
9.52
ø
32
More than 10 mm
PWFY-P200VM-E-AU
ø
19.05
ø
9.52
2) If the unit is used on the highest story of a building and under conditions of high temperature and humidity, it is
necessary to use pipe size and insulating material’s thickness more than those given in the table above.
3) If there are customer’s specications, simply follow them.
(3)-2 Refrigerant pipe, drain pipe and lling port
(A) Refrigerant piping (gas)
(B) Refrigerant piping (liquid)
(C) Water inlet (D) Water outlet (E) Drain outlet
*1: PWFY-P100, 200VM-E-AU
- 34 -
(4) Connecting refrigerant pipes and drain pipes
(A)
(A)
(E)
(C)
(F)
(B)
(D)
(4)-1 Refrigerant piping work
This piping work must be done in accordance with the installation manuals for both outdoor unit and BC controller
(simultaneous cooling and heating series R2).
Series R2 is designed to operate in a system that the refrigerant pipe from an outdoor unit is received by BC controller and branches at the BC controller to connect between indoor units.
The PWFY unit should be connected to 2 ports on the BC controller. (Set BC controller DIP SW 4-6 to ON)
For constraints on pipe length and allowable difference of elevation, refer to the outdoor unit manual.
The method of pipe connection is brazing connection.
Caution:
• Install the refrigerant piping for the indoor unit in accordance with the following.
1. Cut the tip of the indoor unit piping, remove the gas, and then remove the brazed cap.
[Fig. IV. 2. (4). 1]
(A) Cut here
(B) Remove brazed cap
2. Pull out the thermal insulation on the site refrigerant piping, braze the unit piping, and replace the insulation in its original position.
Wrap the piping with insulating tape.
Note:
• Pay strict attention when wrapping the copper piping since wrapping the piping may cause condensation
instead of preventing it.
* Before brazing the refrigerant piping, always wrap the piping on the main body, and the thermal insulation
piping, with damp cloths to prevent heat shrinkage and burning the thermal insulation tubing.
ensure that the ame does not come into contact with the main body itself.
[Fig. IV. 2. (4). 2]
Take care to
(A) Thermal insulation
(B) Pull out insulation
(C) Wrap with damp cloth (D) Return to original position (E) Ensure that there is no gap here (F) Wrap with insulating tape
- 35 -
Cautions On Refrigerant Piping
(A)
(B)
(a)
(C) (C) (C)
(D) (b)
(E)
• Be sure to use non-oxidative brazing for brazing to ensure that no foreign matter or moisture enter
into the pipe.
esuretoapplyrefrigeratingmachineoilovertheareconnectionseatingsurfaceandtightenthe
connection using a double spanner.
• Provide a metal brace to support the refrigerant pipe so that no load is imparted to the indoor unit
endpipe.Thismetalbraceshouldbeprovided50cmawayfromtheindoorunit’sareconnection.
Warning:
When installing and moving the unit, do not charge it with refrigerant other than the refrigerant (R407C or R22)
speciedontheunit.
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to malfunction and result in severe damage.
Caution:
• UserefrigerantpipingmadeofC1220(CU-DHP)phosphorusdeoxidizedcopperasspeciedintheJISH3300
“Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
• Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerator oil in the existing piping will cause the new refrigerant to deteriorate.
• Store the piping to be used during installation indoors and keep both ends of the piping sealed until just
before brazing.
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and the compressor may fail.
(4)-2 Drain piping work
1. Ensure that the drain piping is downward (pitch of more than 1/100) to the outdoor (discharge) side. Do not provide any trap or irregularity on the way. (a)
2. Ensure that any cross-wise drain piping is less than 20 m (excluding the difference of elevation). If the drain piping is long, provide metal braces to prevent it from waving. Never provide any air vent pipe. Otherwise drain may be ejected.
3. Use a hard vinyl chloride pipe VP-25 (with an external diameter of 32 mm) for drain piping.
4. Ensure that collected pipes are 10 cm lower than the unit body’s drain port as shown in (b).
5. Do not provide any odor trap at the drain discharge port.
6. Put the end of the drain piping in a position where no odor is generated.
7. Do not put the end of the drain piping in any drain where ionic gases are generated.
[Fig. IV. 2. (4).3]
(A) Downward slope 1/100 or more
(B) Drain hose
(C) Unit (D) Collective piping
(E) Maximize this length to approx. 10 cm
- 36 -
3. Water pipe installation
Water-side heat exchanger
Solid arrows in the figure indicate the direction of water flow.
PWFY
Field supply
Tank Outlet
Inlet
City water
Overflowed water
Roof
To drain outlet
Uphill gradient ≥ 1/200
P
P
T
T
P
1)
1)
1)
1)
2)
2)
3)
3) 3)
4)
4) 4)4)
5)
5)
5)
6)
7)
8)
8)
9)
11) 11)
12)
(1) Water circuit sample
Sample of water circuit for HWS/ATW
Consider the following when designing and installing a water piping system. (Items (1)-(12) in the gure are explained
below.)
1) Union joints/ange joints etc.
Install a ange etc. to allow for easy replacement of connected equipment.
2) Thermometer
For checking unit performance and operation monitoring
3) Water pressure gauge
For operation status monitoring
4) Valve
Install a valve for easy replacement and cleaning of the refrigerant ow control device. Install a refrigerant ow control valve on the fan coil outlet side.
5) Flexible joint
Recommended to prevent the noise and vibration from the pump from being transmitted.
6) Drain pipe
Install the drain pipe with an inclination of between 1/100 and 1/200 to provide a downward ow of drain water.
For cold climate installation, take an appropriate measure (e.g., drain heater) to prevent the drain water from
freezing.
7) Pump
Use a pump that is large enough to compensate for the total water pressure loss and to supply sufcient water to the
unit.
8) Air vent valve
Provide air vent valves on the pipes.
9) Expansion tank
Install an expansion tank to accommodate expanded water and to supply water.
10) Cold/Hot water pipe
Use pipes that allow for easy air purging, and provide sufcient insulation.
11) Drain valve
Install drain valves so that water can be drained for servicing.
12) Strainer
Install a strainer near the PWFY unit to keep foreign materials from entering the water-side heat exchanger.
- 37 -
(1)-1 Caution for water pipe installation
(A)
45°
Consider the following when designing and installing a water piping system.
Do not use steel pipes as water pipes.
- Copper pipes or stainless steel pipes are recommended.If iron pipes are used in the existing system, do not connect a new circuit to the old one. Keep the existing and new circuits separate.
Light pipes are similar to other air-conditioning pipes, however, please observe the following precautions during installation.
Before a long period of non use, purge the water out of the pipes and thoroughly let them dry.
Use a closed water circuit.
When using the unit for cooling, add brine to the circulating water to prevent it from freezing.
When installed in a low-ambient temperature environment, keep the water circulating at all times. If that is not possible, purge the water out of the pipes completely.
Do not use the water used for this unit for drinking or food manufacturing.
When the ambient temperature is 0 ˚C or lower during stop operation, keep the water circulating at all times, or
purge the water out of the pipes completely.
Model
PWFY-P100VM-E-BU
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
*1 When the attached expan-
sion joints are installed.
Water inlet
PT 3/4 Screw
PT 3/4 Screw
PT 1 Screw*1
Water outlet
PT 3/4 Screw
PT 3/4 Screw
PT 1 Screw*1
(2) Selecting a water pump
Use a pump that is large enough to compensate for the total water pressure loss and to supply sufcient water to the unit.
(3) Installing the strainer
Install the strainer at the angle of 45˚ or less as shown in [Fig. IV 3.(3).1].
Install the supplied strainer at the water inlet.
[Fig. IV 3.(3).1]
(A) Y-type strainer
(4) Precautions during installation
Use the reverse-return method to insure proper pipe resistance to each unit.
To insure easy maintenance, inspection, and replacement of the unit, use a proper joint, valve, etc. on the water intake and outlet port. In addition, be sure to install a strainer on the water intake pipe. (In order to maintain the heat source unit, a strainer on the circulating water inlet is necessary.)
* An example of the heat source unit installation is shown in the diagram below.
Install a suitable air vent on the water pipe. After sending water through the pipe, be sure to vent the excess air.
Compressed water may form in the low-temperature sections of heat source unit. Use a drainage pipe connected to the drain valve at the base of the unit to drain the water.
Install a back ow-prevention valve on the pump and a exible joint to prevent excess vibration.
Use a sleeve to protect the pipes where they go through a wall.
Use metal ttings to secure the pipes, and install them so that they have maximum protection against breakage and
bending.
Do not confuse the water intake and outlet valves.
This unit doesn’t have any heater to prevent freezing within tubes. When the water ow is stopped on low ambient,
take out the water from tubes.
The unused knockout holes should be closed and the opening of refrigerant pipes, water pipes, power source and
transmission wires should be lled with putty and so on to prevent from rain. (eld construction)
Wrap some sealing tape around the screw part to prevent water leakage.
Hold the pipe on the unit side in place with a spanner when installing the pipes or strainer. Tighten screws to a torque of 50 N.m.
Water pipes can get very hot, depending on the preset temperature. Wrap the water pipes with insulating materials to prevent burns.
On the PWFY-P200VM-E-AU model, install the expansion joint (accessory) at the inlet after installing the strainer,
and outlet.
- 38 -
(5) Example of unit installation (using light piping)
(A)
(A)
(D)
(C)
(B)
(E)
(F)
(E)
(B)
(C)
(G)
(G)
(A)
(B)
[Fig. IV. 3.(5).1]
PWFY- P200VM-E-AU
(A) Close valve
(B) Water inlet
(C) Water outlet
(E) Y-type strainer (F) Drain pipe (G) Expansion joint
(D) Refrigerant piping
(6) Insulation installation
The surface temperature of the water pipe would be very high, depending on the set temperature. Insulate the pipe
to prevent burns. When operating PWFY-P100, P200VM-E-AU with cold water, insulate the water pipe to prevent
condensation. Wrap insulation material around water pipes as shown in [Fig. IV. 3.(6).1].
Any heat source piping.
Indoor piping in cold-weather regions where frozen pipes are a problem.
When air coming from the outside causes condensation to form on piping.
Any drainage piping.
[Fig. IV. 3.(6).1]
(A) Heat insulation material (accessory)
(B) Inject with caulking material
- 39 -
(7) Water processing and water quality control
To preserve water quality, use the closed type of cooling tower for unit. When the circulating water quality is poor, the water heat exchanger can develop scales, leading to a reduction in heat-exchange power and possible corrosion of the heat exchanger. Please pay careful attention to water processing and water quality control when installing the water circulation system.
Removal of foreign objects or impurities within the pipes.
During installation, be careful that foreign objects, such as welding fragments, sealant particles, or rust, do not enter
the pipes.
Water Quality Processing
a) Depending on the quality of the cold-temperature water used in the air-conditioner, the copper piping of the heat
exchanger may become corroded. We recommend regular water quality processing. Cold water circulation systems using open heat storage tanks are particularly prone to corrosion. When using an open-type heat storage tank, install a water-to-water heat exchanger, and use a closed-loop
circuit on the air conditioner side. If a water supply tank is installed, keep contact with air to a minimum, and keep the level of dissolved oxygen in the water no higher than 1mg/liter.
b) Water quality standard
Items
pH (25 ˚C) Electric conductivity (mS/m) (25 ˚C) (µ s/cm) (25 ˚C)
Chloride ion (mg Cl Sulfate ion (mg SO4
Standard
Acid consumption (pH4.8)
items
Total hardness (mg CaCO Calcium hardness (mg CaCO Ionic silica (mg SiO
Refer-
Iron (mg Fe/liter)
ence
Copper (mg Cu/liter)
items
Sulde ion
Ammonium ion (mg NH Residual chlorine (mg Cl/liter) Free carbon dioxide (mg CO Ryzner stability index
-
/liter)
2-
/liter)
(mg CaCO3/liter)
3
/liter)
3
/liter)
2
/liter)
(mg S2-/liter)
+
4
/liter)
2
/liter)
Lower mid-range temperature water system
Water Temp.
Recirculating water
7.0 ~ 8.0
30 or less
[300 or less]
50 or less 50 or less
50 or less
70 or less 50 or less 30 or less
1.0 or less
1.0 or less not to be detected
0.3 or less
0.25 or less
0.4 or less
=<
60 ˚C
Make-up water
7.0 ~ 8.0
30 or less
[300 or less]
50 or less 50 or less
50 or less
70 or less 50 or less 30 or less
0.3 or less
1.0 or less not to be detected
0.1 or less
0.3 or less
4.0 or less
Higher mid-range temperature water system
Recirculating water
Water Temp. > 60 ˚C
7.0 ~ 8.0
30 or less
[300 or less]
30 or less 30 or less
50 or less
70 or less 50 or less 30 or less
1.0 or less
1.0 or less not to be detected
0.1 or less
0.1 or less
0.4 or less
Make-up water
7.0 ~ 8.0
30 or less
[300 or less]
30 or less 30 or less
50 or less
70 or less 50 or less 30 or less
0.3 or less
1.0 or less not to be detected
0.1 or less
0.3 or less
4.0 or less
Corrosive
Reference : Guideline of Water Quality for Refrigeration and Air Conditioning Equipment. (JRA GL02E-1994) c) Please consult with a water quality control specialist about water quality control methods and water quality
calculations before using anti-corrosive solutions for water quality management.
d) When replacing a previously installed air conditioning device (even when only the heat exchanger is being
replaced), rst conduct a water quality analysis and check for possible corrosion.
Corrosion can occur in cold-water systems even if there has been no prior signs of corrosion.
If the water quality level has dropped, please adjust water quality sufciently before replacing the unit. The maximum amount of circulating water in the water pipe is 100L. Make sure that this amount is not exceeded.
Tendency
Scale-forming
- 40 -
(8) Pump interlock
IN1
TB142A
Water Pump
Strainer
Control Box
Broken lines are field supply products.
Operation signal
Pump interlock
The unit may become damaged if it is operated with no water circulating through the pipes.
Be sure to interlock unit operation and the water-circuit pump. Use the terminal blocks for interlocking TB142A (IN1) that
can be found on the unit. [Fig. IV. 3. (8).1]
Example drawing for pump interlock
- 41 -
V
(A) (B)
(A) (B)
(C)
(E) (E)
PE
PE
PE
(D)
PE
(D) (D)
PWFY-P100VM-E-BU
PWFY-P100,200VM-E-AU
System Design
1.Electricalwork
(1) General cautions
Warning:
Electricalworkshouldbedonebyqualiedelectricalengineersinaccordancewith“EngineeringStandards ForElectricalInstallation”andsuppliedinstallationmanuals.Specialcircuitsshouldalsobeused.Ifthepower circuitlackscapacityorhasaninstallationfailure,itmaycauseariskofelectricshockorre.
1. Be sure to take power from the special branch circuit.
2. Be sure to install an earth leakage breaker to the power.
3. Install the unit to prevent that any of the control circuit cables (remote controller, transmission cables, or external input/output line) is brought in direct contact with the power cable outside the unit.
4. Ensure that there is no slack on all wire connections.
5. Some cables (power, remote controller, transmission cables external input/output line) above the ceiling may be bitten by mouses. Use as many metal pipes as possible to insert the cables into them for protection.
6. Never connect the power cable to leads for the transmission cables. Otherwise the cables would be broken.
7. Be sure to connect control cables to the indoor unit, remote controller, and the outdoor unit.
8. Be sure to ground the unit.
9. Select control cables from the conditions given in page
42.
Caution:
Be sure to put the unit to the ground on the outdoor unit side. Do not connect the earth cable to any gas pipe, water pipe, lightening rod, or telephone earth cable. Incomplete grounding may cause a risk of electric shock.
(2) Power supply for PWFY unit
(2)-1 Electrical characteristics of PWFY unit
Power supply cords of appliances shall not be lighter than design 245 IEC 57 or 227 IEC 57.
A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.
Model
PWFY-P100VM-E-BU
Model
PWFY-P100VM-E-AU PWFY-P200VM-E-AU
Hz
50/60
50/60
220-230-240 V
Hz
Power supply Compressor
Volts
220-230-240 V
Voltage range
Max. 264 V
Min. 198 V
Power supply
Volts
MCA (A)
15.71
Voltage range
Max. 264 V
Min. 198 V
Output (kW)
1.0
MCA (A)
0.085
SC (A)
1.25
Cooling
RLA (A) Heating
11.63-11.12-10.66
RLA (A)
Heating
0.068-0.065-0.063
(2)-2 Power cable specications
Model
PWFY-P100VM-E-BU
Model
PWFY-P100VM-E-AU PWFY-P200VM-E-AU
[Fig. V. 1.(2).1]
Minimum wire thickness (mm2)
Main cable
2.5
Total operating current
16 A or less
25 A or less
32 A or less
branch
-
Minimum wire thickness (mm2)
Main cable
1.5
2.5
4.0
Ground
2.5
branch
Breaker for
current leakage
30 A 30 mA 0.1 sec or less
Ground
1.5
2.5
4.0
1.5
2.5
4.0
20 A 30 mA 0.1 sec. or less
30 A 30 mA 0.1 sec. or less
40 A 30 mA 0.1 sec. or less
Breaker for current
leakage
Local swich (A)
capacity
25
capacity
fuse
25
Local swich (A)
fuse
16
25
32
16
25
32
Breaker for wiring (NFB) (A)
30
Breaker for wiring (NFB) (A)
20
30
40
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too
largecapacitymaycauseariskofmalfunctionorre.
- 42 -
(A) Breaker for current leakage (B) Local switch or breakers for wiring (C) PWFY-P100VM-E-BU (D) PWFY-P100, 200VM-E-AU
(E) Pull box
(3) Connecting remote controller, indoor and outdoor transmission cabls
TB02
TB15
earth cable (shielded)
TB5
SM1M2 SM1M2
TB3
M1M2
(A) (B) (C)
(D)
(E)
(E)
1 2 S
TB15TB5
SM1M2 1 2
(shielding wire)
(B)
(A)
S
2
1
L
N
DC10~13V
1 2
A B
(C)
S
M2
M1
(D)
(E)
2
S
M2
M1
(A)
(B)
(D)
(E)
1
L
N
DC10~13V
A B 1 2
(C)
Connect unit TB5 and outdoor unit TB3. (Non-polarized 2-wire (shield))
The “S” on unit TB5 is a shielding wire connection. For specications about the connecting cables, refer to the
outdoor unit installation manual.
Install a remote controller following the manual supplied with the remote controller.
(3)-1 Power supply examples
(3)-1-1 Using MA Remote controller (Remote controller is optionally available)
Connect the “1” and “2” on unit TB15 to a MA remote controller. (Non-polarized 2-wire)
[Fig. V. 1. (3). 1] MA Remote controller
(A) Outdoor unit
(B) BC controller (C) PWFY-P100VM-E-BU (D) PWFY-P100, 200VM-E-AU (E) MA remote controller
DC 10 to 13 V between 1 and 2 (MA remote controller)
[Fig. V. 1. (3). 2] MA Remote controller
PWFY- P100VM-E-BU PWFY- P100, 200VM-E-AU
The MA remote controller cannot be used at the same time or interchangeably.
Note:
Ensurethatthewiringisnotpinchedwhenttingtheterminalboxcover.Pinchingthewiringmaycutit.
Caution:
Use wire with supplemental insulation.
Input to TB142A, TB142B, and TB142C should not carry voltage.
Cables from equipment connected to external input/output should have supplemental insulation.
Use a single multiple-core cable for external input/output to allow for connection to the PG screw.
Caution:
Wirethepowersupplysothatnotensionisimparted.Otherwisedisconnection,heatingorreresult.
(A) Non-polarized
(B) TB15 (MA remote controller cables) (C) MA remote Controller (D) TB5 (Transmission cables) (E) TB2 (Power supply wiring)
- 43 -
(4) Transmission cable specications
(A)
(C)
(B)
(C)
(A)
(A)
(A)
(B)
(D)
(E)
(G)
(F)
(4)-1 Transmission cables
PWFY-P100VM-E-BU
Type of cable
Cable diameter
Remarks
Transmission cables
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25 mm
2
-
MA Remote controller cables
Sheathed 2-core cable (shielded)
CVVS
0.3 ∼ 1.25 mm2 (0.75 ∼ 1.25 mm2)*1
Max.length: 200 m
External input
Sheathed multi-core cable (shielded)
CVVS or MVVS
0.3 ∼ 0.5 mm
Max.length: 100 m
2
External output
Sheathed multi-core cable (unshielded)
CVV or MVV
0.3 ∼ 1.25 mm
Rated voltage: L1-N: 220
Rated load: 0.6 A
2
∼ 240 V
PWFY-P100, 200VM-E-AU
Transmission cables
Type of cable
Cable diameter
Remarks
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25 mm
2
-
*1 Connected with simple remote controller. CVVS, MVVS: PVC insulated PVC jacketed shielded control cable
CVV, MVV : PVC insulated PVC sheathed control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
MA Remote controller cables
Sheathed 2-core cable
CVV (unshielded)
0.3 ∼ 1.25 mm2 (0.75 ∼ 1.25 mm2)*1
Max.length: 200 m
External input
Sheathed multi-core cable
CVV or MVV (unshielded)
0.3 ∼ 0.5 mm
Max.length: 100 m
2
External output
Sheathed multi-core cable (unshielded)
CVV or MVV
0.3 ∼ 1.25 mm
Rated voltage: L1-N: 220
Rated load: 0.6 A
2
∼ 240 V
(5) Connecting electrical connections
Verify that the model name on the operating instructions on the cover of the control box is the same as the model name on the nameplate.
Step 1 Remove the screws holding the terminal box cover in place. [Fig. V.1.(5).1]
(A) Screws
(B) Front panel
(C) Control box
Note:
Ensurethatthewiringisnotpinchedwhenttingtheterminalboxcover.Pinchingthewiringmaycutit.
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension may break, or overheat and burn.
Fix power source external input/output line wiring to control box by using buffer bushing for tensile force to prevent electric shock. (PG connection or the like.) Connect transmission wiring to transmission terminal block through the knockout hole of control box using ordinary bushing.
After wiring is complete, make sure again that there is no slack on the connections, and attach the cover onto the control box in the reverse order removal.
[Fig. IV. 1.(5).2]
(A) To prevent external tensile force from applying to the wiring connection section of power source terminal block use buffer bushing like PG connection or the like.
(B) External signal input cable
(C) External signal output cable (D) Power source wiring (E) Tensile force (F) Use ordinary bushing
(G) Transmission cable and MA remote controller cable
Caution:
Wirethepowersupplysothatnotensionisimparted.Otherwisedisconnection,heatingorreresult.
- 44 -
(6) Address setting
SWU2 SWU3
SWU1
(6)-1 Switch operation
(Be sure to operate with the main power turned OFF.)
[Fig. V. 1.(6).1] <Address board>
There are two types of rotary switch setting available: setting addresses 1 to 9 and over 10, and setting branch numbers.
a) How to set addresses Example: If Address is “3”, remain SWU2 (for over 10) at “0”, and match SWU1 (for 1 to 9) with “3”. b) How to set branch numbers SWU3 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC controller’s end connection number. Remain other than R2 at “0”.
The rotary switches are all set to “0” when shipped from the factory. These switches can be used to set unit address es and branch numbers at will.
-
- 45 -
(6)-2 Rule of setting address
Unit
PWFY unit
Standard indoor unit
ME, LOSSNAY Remote controller (Main)
ME, LOSSNAY Remote controller (Sub)
Address setting
01 ~ 50
52 ~ 99, 100
101 ~ 150
151 ~ 199, 200
NoteExample
The address of outdoor unit + 1
Please reset one of them to an address between 52
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
System remote controller
ON/OFF remote controller
G-50A GB-50A AG-150A
000, 201 ~ 250
000, 201 ~ 250
000, 201 ~ 250
Local remote controller
System controller
The address of main remote controller + 50
The address automatically becomes "200" if it is set
as "00"
10 1
10 1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
10 1
10 1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
10 1
10 1100
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
10 1100
10 1100
LMAP02-E
201 ~ 250
1
1
Fixed
Fixed
Group remote controller
201 ~ 250
The smallest group No. to be managed + 200
10 1
2
Fixed
2
Fixed
Outdoor unit
BC controller (Main)
53 ~ 99, 100
Lowest address within the indoor units connected to the BC controller (Sub) plus 50.
10 1
BC controller (Sub)
51 ~ 99, 100
The smallest address of indoor unit in same refrigerant system + 50 Assign sequential address numbers to the outdoor units in one refrigerant circuit system. OC and OS are automatically detected. (Note 2)
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
Use the most recent address within the same group of indoor units. Make the indoor units address connected to the BC controller (Sub) larger than the indoor units address connected to the BC controller (Main). If applicable, set the sub BC controllers in an PURY system in the following order: (1)
Indoor unit to be connected to the BC controller (Main)
(2)
Indoor unit to be connected to the BC controller (No.1 Sub)
(3)
Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
10 1
(Note1)
0,2 0~5 0~9
Note1: To set the address to "100", set it to "50" Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected. OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
- 46 -
(6)-3 System examples
2. Address should be set to Indoor units, LOSSNAY and central controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and MA RC consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to Data book G4 2-3 "System configuration
restrictions".
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected. OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
Indoor unit
Indoor unit
PWFY-P100VM-E-BU PWFY-P100VM-E-AU PWFY-P200VM-E-AU
PWFY-P100VM-E-BU PWFY-P100VM-E-AU PWFY-P200VM-E-AU
C/R AMWMA
(Main) (Sub)
MA R/C
SRU
Wireless R/C
*1
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
*1
01
BC controller
53
BC controller
(Main)
93
033020
TB15
TB5 5BT20BT 2BT5BT
Transmission Booster
PAC-SF46EPA
TB5
3BT51BT51BT
TB15
MA R/C
(Main) (Sub)
MA R/C
TB15
ME R/C
MA R/C
PZ-52SF
SRU
Wireless R/C
*1
*1 142 143
41 42
43 95
45 46
TB15
TB5 5BT20BT
LOSSNAY
5BT5BT5BT
TB15
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
BC controller
(Sub1)
Group 2
12 puorG1 puorG
Group 32 43 puorG33 puorG13 puorG
TB3
TB7 7BT7BT7BT
TB7
TB3
201
PSU
5251
OC OS
PURY-(E)P-YSHM
SC
TB3TB3
9291
OC OS
PURY-(E)P-YSHM
TB3
97
OC
CN41CN40CN41CN40 CN41CN40CN41 14NC04NC CN40
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
PURY-(E)P-YHM
4. Indoor units should be set with a branch number.
5. Assign an address to each of the sub BC controllers (SC1 and SC2) which equals the sum of the smallest address of the indoor units that are connected to each sub BC controller and 50.
*2
(6)-3-1 MA remote controller, Multi-refrigerant-system, System Controller at TB7 side, Booster for long
M-NET wiring
PWFY-P100VM-E-BU/PWFY-P100,200VM-E-AUwithR2seriesoutdoorunits
- 47 -
PWFY-P100,200VM-E-AUwithYseriesoutdoorunits
2. Address should be set to Indoor units, LOSSNAY and central controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and MA consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to Data book G4 2-3 "System configuration restrictions".
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
Indoor unit
PWFY-P100VM-E-AU PWFY-P200VM-E-AU
PWFY-P100VM-E-AU PWFY-P200VM-E-AU
MA
(Main)
WMA
MA
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
03302010
TB15
5BT5BT 2BT5BT
Transmission Booster
PAC-SF46EPA
TB5
3BT51BT51BT
TB15
MA
(Main)MA(Sub)
TB15
PWFY-P100VM-E-AU PWFY-P200VM-E-AU
WMA MA
41 42
43
45 46
TB15
5BT5BT
LOSSNAY
5BT5BT5BT
TB15
SRU
Wireless R/C
*1
*1
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
Group 2
12 puorG1 puorG
Group 32 43 puorG33 puorG13 puorG
TB3 TB3
TB7 7BT7BT7BT7BT
TB7
TB3
201
PSU
*2
535251
OC OS1 OS2
PUHY-(E)P-YSHM
SC
TB3TB3
9291
OC OS1
PUHY-(E)P-YSHM
TB3
97
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41 14NC04NC CN40
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
PUHY-(E)P-YHM
Wireless R/C
*1
*1
- 48 -
(7) External input/output function
OUT4OUT3OUT2
TB141A
OUT1
IN1 IN2 IN3 IN4
IN5IN6 IN7 IN8
TB142CTB142BTB142A
COM+
CN421
(BK)(BU)
CN422
32211
3
CN421
(BK)
(BU)
CN422
3
2
+
211
3
current direction
Current generator
Eaternal analog input
+
current direction
Presettemperatureinput(externalanaloginput:4mA-20mA)
External input is input through CN421, CN422 on the circuit board. (Fig. V. 1.(7).1)
[Fig. V. 1.(7).1]
Use the supplied connector.
If no temperature settings are made via the MA remote controller, the temperature changes with the current of generator. Refer to the instructions manual that came with the MA remote controller for how to make the settings.
4 mA → 10 °C 20 mA → 70 °C
Externaloutputterminal
External output terminal (refer to Fig. V. 1.(7).2) is ineffective when the circuit is open. Refer to Table V. 1.(7).1 for information about each contact. The current in the circuit to be connected to the external output terminal must be 0.6A or less. Table V. 1.(7).1
OUT1
OUT2
OUT3
OUT4
Operation ON/OFF
Defrost
Compressor
Error signal
Externalinputterminal
The piping length must be within 100 m. External input terminal (refer to Fig. V. 1.(7).2 is ineffective when the circuit is open. Refer to Table V. 1.(7).2 through Table V. 1.(7).4 for information about each contact. Only the “pump interlock” function is ineffective when the circuit is short-circuited. Connect a relay circuit to the external output terminal as shown in Fig. V. 3.(8).1.
The specications of the relay circuit to be connected must meet the following conditions.
Contact rating voltage >= DC15V Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC [Table V. 1.(7).2] TB142A
IN1
Pump interlock
[Table V. 1.(7).3] TB142B
IN3 IN4
Connection demand
Operation ON/OFF
[Table V. 1.(7).4] TB142C
[Fig. V. 1.(7).2]
[Fig. V. 1.(7).3]
COM+
IN5 *1 IN6 *2 IN7 *3
Common
Hot Water/Heating
Heating ECO *4
Anti-freeze *5
*1 PWFY-P100VM-E-BU Hot Water PWFY-P100, 200VM-E-AU Heating
*2 Effective when SW 4-3 is set to ON. *3 Effective when SW 4-4 is set to ON. *4 When Heating ECO mode is effective, the outlet water temp. will be changed based on ambient temp. automatically. *5 When Anti-freeze mode is effective, the unit will work for keeping set water temp. automatically.
Note: DipS/W1-1OFF:WaterInletTemp. DipS/W1-1ON:WaterOutletTemp. ThefactorysettingforDipSW1-1isOFF.
Signal priority = External input > centralizied controller > remote controller
- 49 -
VI
Switch Function
Function according to switch setting
Switch setting timing
OFF ON
SW1
1 T
Operation after power recovery
*1
Operation after power recovery
H0 thermistor selection Water inlet thermistor TH6 Water outlet thermistor TH8 Before power on
Before power on
Before power on
2 - - - -
3
Remains stopped
Depends on the SW1-3 setting
Auto recovery (to the status before power failure)
Forced to operate
*1 Valid only when SW1-4 is set to OFF
4
5 - - - -
6 - - - -
7 Test-run mode OFF ON Any time
8 Error history deleted Normal Deleted Any time
9
Effective only when SW1-7 is set to ON and only on the AT W models.
Heating Cooling Any time
10 - - - -
SW2 1-10
For self-diagnosis/operation monitoring
- - Any time
SW3
1 Capacity setting (AT W only) 4HP 8HP (ATW only) Before power on
2 Service LED display selection Display in Centigrade Display in Fahrenheit Any time
3 - - - -
4 - - - -
5
Cumulative compressor opera­tion time is deleted.
Normal Deleted Any time
6 - - - -
7 - - - -
8 - - - -
9 - - - -
10 - - - -
SW4
1
2
3
Use to change pr
Do not change from factory setting.
Do not change from factory setting.
eset tempera­ture range for the Heating ECO mode.
HWS : Ineffective ATW : Ine ffective
HWS : 30°C to 50°C ATW : 30 °C to 50°C
Before power on
4
Use to change preset tempera­ture range for the Anti-freeze mode.
BU : Ineffective WH : Ineffective
BU : 10°C to 45°C WH : 10°C to 45°C
Before power on
5 - - - -
6 - - - -
7 - - - -
8 - - - -
9 - - - -
10 - - - -
SW5
1 Error detection enabled
Enabling/disabling ACCT sensor error detection
Error detection disable (No load operation is possible)
Any time
2 - - - -
3 - - - -
4 - - - -
Control
1. Dip switch functions
- 50 -
2.Remotecontrollerspecications
FUNCTION
ON/OFF
Operation mode switching
Water temperature setting
Preset temperature range
Water temperature display
Permit / Prohibit local operation
Weekly scheduler
Error
Self check (Error history)
Test run
Circulating water replacement warning
LANGUAGE setting
Operation locking function
Runs and stops the operation of a group of units Switches between Hot Water / Heating / Heating ECO / Anti-freeze / Cooling * Available operation modes vary depending on the unit to be connected. * Switching limit setting can be made via a remote controller. Temperature can be set within the ranges below. (in increments of 1°C or 1°F) Hot Water 35°C min. ~ 70°C max. (in increments of 1°C or 2°F) Heating 30°C min. ~ 45°C max. (in increments of 1°C or 2°F) Anti-freeze 10°C min. ~ 45°C max. (in increments of 1°C or 1°F) Cooling 10°C min. ~ 30°C max. (in increments of 1°C or 1°F) * The settable range varies depending on the unit to be connected. Preset temperature range setting can be limited via a remote controller. 10°C min. ~ 90°C max. (in increments of 1°C or 1°F) * The settable range varies depending on the unit to be connected. Individually prohibits operations of each local remote control function :ON/OFF, Operation modes,water temperature setting, Circulating water replacement warning reset. *
Upper level controller may not be connected depending on the unit to be connected. ON / OFF / Water temperature setting can be done up to 6 times one day in the week. (in increments of a minute) When an error is currently occurring on a unit, the afflicted unit and the error code are displayed. Searches the latest error history by pressing the CHECK button twice. Enables the Test run mode by pressing the TEST button twice. * Test run mode is not available depending on the unit to be connected. Displays the circulating water replacement warning via the unit message. Clears the display by pressing the CIR.WATER button twice. * Circulating water replacement warning is not available depending on the unit to be connected. The language on the dot matrix LCD can be changed. (Seven languages) English/German/Spanish/Russian/Italian/French/Swedish Remote controller operation can be locked or unlocked.
·All-switch locking
·Locking except ON/OFF switch
Item Description
Operations
Display
- 51 -
VII
Components
Refrigerant
circuit
components
Electric circuit
parts
What to look for
Maintenance cycle
(times/year)
Replacement cycle
Compressor
Water-refrigerant heat exchanger Solenoid valve (PWFY-P100, 200VM-E-AU) Check valve (PWFY-P100, 200VM-E-AU) Linear expansion valve Strainer Capillary tube Pipes
Electromagnetic contactor
Overcurrent relay
Relay
Solenoid valve Fuse Electronic board Switch Pressure switch Terminal block Cable/connector Fan Motor
High/low pressure, vibration, noise Insulation resistance, loose terminals High/low pressure, water pressure loss
Operation, leakage, clogging
Operation, leakage, clogging
Operation Inlet/outlet temperature difference Contact wear, Vibration Contact wear, Vibration Corroded contact, loose terminals Insulation resistance loose terminals Operation, Contact resistance. Insulation resistance Insulation resistance External appearance External appearance Operation, Contact resistance. Contact resistance. loose terminals Looseness, corrosion, and wearing Balance Insulation resistance, noise, vibration
20,000 hours
10 Years
7 Years
10 Years
7 Years
While in heavy use
10 Years 10 Years
8 Years
7 to 10Years
6 Years
7 Years 8 Years 8 Years 8 Years
7 to 10Years
8 Years 10 Years 10 Years
6 to 10Years
2
2
2
1
2 1 1 1
2
2
2
2 2 2 2 2 2 2 2 2
Regular preventive maintenance and parts replacement help keep the unit running smoothly and minimize problems. The table below shows the maintenance schedule. Use the replacement timing in the table only as a guide. Some parts may need to be replaced sooner, depending on the usage.
MaintenanceCycle
1. Routine maintenance checks
Periodically and thoroughly check the circulating water circuit. (See table below.)
Consult a maintenance technician.
2. Parts Replacement Cycle
- 52 -
VIII
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
10.0
10.0
20.0
30.0
40.0
50.0
0.0
5.0
100 200 300 400
100 200 300 400 500
Capa
city(kW)
Input
(kW)
Total capacity of indoor units
10.0
20.0
30.0
40.0
50.0
0.0
5.0
10.0
Cooling Heating
Cooling Heating
P300 P350
Cooling Heating
Cooling Heating
P200 P250
PUHY-P200,250YHM-A
Ref: PUHY_YHM-A_CbTIU_EUDB_P200-P350
PUHY-P300,350YHM-A
Product Data (supplemental information for chapter III.)
1. Capacity tables
(1) Correction by total indoor (1)-1 Y series
- 53 -
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
20.0
10.0
10.0
15.0
30.0
40.0
50.0
60.0
0.0
5.0
200 300 400 500 600
200 300 400 500 600 700 800
Capa
city(kW)
Input
(kW)
Total capacity of indoor units
30.0
40.0
50.0
60.0
70.0
0.0
5.0
15.0
20.0
10.0
Cooling Heating
Cooling Heating
P500 P550
Cooling Heating
Cooling Heating
P400 P450
PUHY-P400,450YHM-A
Ref: PUHY_YHM-A_CbTIU_EUDB_P400-P550
PUHY-P500,550YSHM-A
- 54 -
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
50.0
40.0
30.0
20.0
60.0
70.0
80.0
90.0
0.0
10.0
200 300 400 500 600 700 800 900
300 400 500 600 700 800 900 1000
Capa
city(kW)
Input
(kW)
Total capacity of indoor units
40.0
20.0
60.0
80.0
100.0
120.0
0.0
10.0
30.0
20.0
Cooling Heating
Cooling Heating
P700 P750
Cooling Heating
Cooling Heating
P600 P650
PUHY-P600,650YSHM-A
Ref: PUHY_YHM-A_CbTIU_EUDB_P600-P750
PUHY-P700,750YSHM-A
- 55 -
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
40.0
20.0
60.0
80.0
100.0
120.0
0.0
10.0
40.0
30.0
400 600 800 1000 14001200
400 500 600 700 800 1200900 1000 1100
Capa
city(kW)
Input
(kW)
Total capacity of indoor units
60.0
40.0
80.0
100.0
120.0
140.0
0.0
10.0
30.0
20.0
Cooling Heating
Cooling Heating
P900 P950
Cooling Heating
Cooling Heating
P800 P850
PUHY-P800,850YSHM-A
Ref: PUHY_YHM-A_CbTIU_EUDB_P800-P950
PUHY-P900,950YSHM-A
- 56 -
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
80.0
60.0
20.0
30.0
40.0
100.0
120.0
140.0
160.0
0.0
10.0
400 600 800 1000 1200 1400
400 600 800 1000 1200 1400 1600
Capa
city(kW)
Input
(kW)
Total capacity of indoor units
80.0
100.0
120.0
140.0
160.0
0.0
10.0
30.0
40.0
20.0
Cooling Heating
P1150 Cooling Heating
P1100
Cooling Heating
Cooling Heating
P1000 P1050
PUHY-P1000,1050YSHM-A
Ref: PUHY_YHM-A_CbTIU_EUDB_P1000-P1150
PUHY-P1100,1150YSHM-A
- 57 -
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
100.0
80.0
60.0
40.0
120.0
140.0
160.0
180.0
0.0
20.0
400 600 800 1000 1200 1400 1600 1800
Cooling Heating
Cooling Heating
P1250
PUHY-P1200,1250YSHM-A
Ref: PUHY_YHM-A_CbTIU_EUDB_P1200-P1250
P1200
- 58 -
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
15.0
10.0
10.0
20.0
25.0
30.0
35.0
2.0
6.0
8.0
4.0
100 200 300 400
100 200 300 400 500
Capa
city(kW)
Input
(kW)
Total capacity of indoor units
10.0
20.0
30.0
40.0
50.0
4.0
8.0
6.0
12.0
14.0
10.0
Cooling Heating
Cooling Heating
Cooling Heating
P350 Cooling Heating
P300
P200 P250
PURY-P200,250YHM-A(-BS)
Ref: PURY_YHM-A_CbTIU_EUDB_P200-P350
PURY-P300,350YHM-A(-BS)
(1)-2 R2 series
- 59 -
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
20.0
20.0
10.0
30.0
40.0
50.0
60.0
0
10.0
15.0
5.0
200 300 400 500 600 700 800
200 300 500 700400 600 800 900
Capa
city(kW)
Input
(kW)
Total capacity of indoor units
50.0
40.0
30.0
60.0
70.0
80.0
10.0
5.0
20.0
15.0
Cooling Heating
Cooling Heating
Cooling Heating
P550 Cooling Heating
P500
P400 P450
PURY-P400,450Y(S)HM-A(-BS)
Ref: PURY_YHM-A_CbTIU_EUDB_P400-P550
PURY-P500,550YSHM-A(-BS)
- 60 -
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
50.0
40.0
60.0
70.0
80.0
90.0
15.0
20.0
10.0
5.0 200 300 500 600 700400 800 900 1000
400300 500 600 700 800 900 1000 1100 1200
Capa
city(kW)
Input
(kW)
Total capacity of indoor units
40.0
60.0
80.0
100.0
10.0
5.0
20.0
25.0
30.0
15.0
Cooling Heating
Cooling Heating
Cooling Heating
P750 Cooling Heating
P700
P600 P650
PURY-P600,650YSHM-A(-BS)
Ref: PURY_YHM-A_CbTIU_EUDB_P600-P750
PURY-P700,750YSHM-A(-BS)
- 61 -
400 500 600 800 1000700 900 1100 1200 1300
Capa
cit
y
(kW)
Input
(kW)
Total capacity of indoor units
60.0
40.0
80.0
100.0
120.0
15.0
10.0
25.0
30.0
20.0
Cooling Heating
P800
Ref: PURY_YHM-A_CbTIU_EUDB_P800
PURY-P800YSHM-A(-BS)
- 62 -
(2) Correction by refrigerant piping length
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P200YHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P200_C
Total capacity of indoor unit
100
150
200 260
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PUHY-(E)P400Y(S)HM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P400_C
Total capacity of indoor unit
200
300
400
520
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-P250YHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P250_C
Total capacity of indoor unit
125
188
250 325
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P450Y(S)HM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P450_C
225
338
450
585
Total capacity of indoor unit
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P300YHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P300_C
Total capacity of indoor unit
150
225
300
390
0 20 40 60 80 100 120 140 160 180
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P500YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P500_C
Total capacity of indoor unit
250
375
500
650
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PUHY-P350YHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P350_C
Total capacity of indoor unit
175
263
350
455
Piping equivalent length [m]
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P550YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P550_C
275
413
550
715
Total capacity of indoor unit
0 20 40 60 80 100 120 140 160 180
(2)-1 Y series
(2)-1-1 Cooling capacity correction
- 63 -
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PUHY-(E)P600YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P600_C
Total capacity of indoor unit
300
450
600 780
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P800YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P800_C
Total capacity of indoor unit
400
600
800
1040
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P650YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P650_C
Total capacity of indoor unit
325
488
650
845
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PUHY-(E)P850YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P850_C
Total capacity of indoor unit
425
637
850
1105
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P700YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P700_C
Total capacity of indoor unit
350
525
700
910
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P900YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P900_C
Total capacity of indoor unit
450
675
900
1170
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-(E)P750YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P750_C
Total capacity of indoor unit
375
563
750
975
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-P950YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P950_C
Total capacity of indoor unit
475
712
950
1235
0 20 40 60 80 100 120 140 160 180
- 64 -
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PUHY-P1000YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P1000_C
Total capacity of indoor unit
500
750
1000 1300
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PUHY-P1150YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P1150_C
Total capacity of indoor unit
575
862
1150
1495
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PUHY-P1050YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P1050_C
Total capacity of indoor unit
525
787
1050
1365
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-P1200YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P1200_C
Total capacity of indoor unit
600
900
1200
1560
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PUHY-P1100YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P1100_C
Total capacity of indoor unit
550
825
1100
1430
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PUHY-P1250YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P1250_C
Total capacity of indoor unit
625
937
1250
1625
- 65 -
0.90 0 20 40 60 80 100 120 140 160 180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P200,250YHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P200-P250_H
0.90 0 20 40 60 80 100 120 140 160 180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P700,750,800YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P700-P800_H
0.90 0 20 40 60 80 100 120 140 160 180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P300,350,400,450Y(S)HM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P300-P450_H
0.90 0 20 40 60 80 100 120 140 160 180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P850,900,950,1000YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P850-P1000_H
0.90 0 20 40 60 80 100 120 140 160 180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P500,550,600,650YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P500-P650_H
0.85
0.90
0 20 40 60 80 100 120 140 160 180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-P1050,1100,1150,1200,1250YSHM-A
Ref.: PUHY_YHM-A_CbRPL_EUDB_P1050-P1250_H
(2)-1-2 Heating capacity correction
- 66 -
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-(E)P200YHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P200_C
Total capacity of indoor unit
100
150
200 300
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PURY-(E)P400Y(S)HM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P400_C
Total capacity of indoor unit
200
300
400
600
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-P250YHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P250_C
Total capacity of indoor unit
125
188
250 375
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-(E)P450YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P450_C
225
338
450
675
Total capacity of indoor unit
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-(E)P300YHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P300_C
Total capacity of indoor unit
150
225
300
450
0 20 40 60 80 100 120 140 160 180
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-(E)P500YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P500_C
Total capacity of indoor unit
250
375
500
750
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PURY-P350YHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P350_C
Total capacity of indoor unit
175
263
350
525
Piping equivalent length [m]
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-(E)P550YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P550_C
275
413
550
825
Total capacity of indoor unit
0 20 40 60 80 100 120 140 160 180
(2)-2 R2 series
(2)-2-1 Cooling capacity correction
- 67 -
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
0 20 40 60 80 100 120 140 160 180
PURY-(E)P600YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P600_C
Total capacity of indoor unit
300
450
600 900
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-P750YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P750_C
Total capacity of indoor unit
375
563
750
1125
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-P650YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P650_C
Total capacity of indoor unit
325
488
650
975
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-P800YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P800_C
Total capacity of indoor unit
400
600
800
1200
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)
1
0.9
0.8
0.95
0.85
0.75
0.65
0.7
Cooling capacity correction factor
PURY-P700YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P700_C
Total capacity of indoor unit
350
525
700
1050
0 20 40 60 80 100 120 140 160 180
- 68 -
0.80 0 20 40 60 80 100 120 140 160
Heating capacity correction factor
0.90
1.00
Piping equivalent length (m)
PURY-(E)P200YHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P200_H
0.80 0 20 40 60 80 100 120 140 160
Heating capacity correction factor
0.90
1.00
PURY-(E)P450,500YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P450_H
Piping equivalent length (m)
0.80 0 20 40 60 80 100 120 140 160
Heating capacity correction factor
0.90
1.00
Piping equivalent length (m)
PURY-(E)P250,300YHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P250_H
0.80 0 20 40 60 80 100 120 140 160
Heating capacity correction factor
0.90
1.00
PURY-(E)P550,600,650YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P550_H
Piping equivalent length (m)
0.80 0 20 40 60 80 100 120 140 160
Heating capacity correction factor
0.90
1.00
PURY-P350YHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P350_H.
Piping equivalent length (m)
0.80 0 20 40 60 80 100 120 140 160
Heating capacity correction factor
0.90
1.00
PURY-P700,750,800YSHM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P700_H
Piping equivalent length (m)
0.80 0 20 40 60 80 100 120 140 160
Heating capacity correction factor
0.90
1.00
PURY-(E)P400Y(S)HM-A(-BS)
Ref.: PURY_YHM-A_CbRPL_EUDB_P400_H
Piping equivalent length (m)
(2)-2-2 Heating capacity correction
- 69 -
(3) Correction at frosting and defrosting
<R2 series>
Ref.: PURY_YHM-A_CbFROST_EUDB_ALL
PURY-(E)P200YHM-A(-BS) PURY-P250YHM-A(-BS) PURY-(E)P300YHM-A(-BS) PURY-P350YHM-A(-BS) PURY-(E)P400Y(S)HM-A(-BS) PURY-(E)P450YSHM-A(-BS) PURY-(E)P500YSHM-A(-BS) PURY-(E)P550YSHM-A(-BS) PURY-(E)P600YSHM-A(-BS) PURY-P650YSHM-A(-BS) PURY-P700YSHM-A(-BS)
PURY-P750YSHM-A(-BS) PURY-P800YSHM-A(-BS)
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.95
0.95
0.93
0.93
0.95
0.98
0.98
0.94
0.94
0.94
0.98
0.98
0.98
0.84
0.84
0.82
0.85
0.90
0.89
0.89
0.87
0.84
0.84
0.89
0.89
0.89
0.83
0.83
0.80
0.83
0.87
0.87
0.86
0.86
0.86
0.86
0.88
0.88
0.88
0.83
0.83
0.82
0.84
0.88
0.89
0.89
0.87
0.87
0.87
0.89
0.89
0.89
0.87
0.87
0.86
0.86
0.89
0.90
0.90
0.88
0.88
0.88
0.90
0.90
0.90
0.90
0.90
0.90
0.90
0.90
0.92
0.92
0.90
0.90
0.90
0.92
0.92
0.92
0.95
0.95
0.90
0.90
0.95
0.95
0.95
0.90
0.90
0.90
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.93
0.93
0.93
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.93
0.93
0.93
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.93
0.93
0.93
0.95
0.95
0.95
Due to frosting at the outdoor heat exchanger and the automatical defrosting operation, the heating capacity of the outdoor unit should be considered by multiplying the correction factor which shown in the table below.
(3)-1 Y series
(3)-2 R2 series
- 70 -
DATA BOOK PWFY-P100VM-E-BU
PWFY-P100VM-E-AU PWFY-P200VM-E-AU
Issued in Aug. 2008 MEE08K022 Printed in Japan
HEA D OF FICE: TO KYO BLD G., 2-7-3 , MA RUNOUC HI, CHIYODA- KU, TOKYO 100-8 310, JAPAN
New publication effective Aug. 2008.
Specifications subject to change without notice.
Loading...