Mitsubishi Electric PVFY-P12, PVFY-P36, PVFY-P48, PVFY-P54NAMU-E1, PVFY-P18 Service Manual

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
2015
Air-Conditioners
PVFY-P12, 18, 24, 30, 36, 48, 54NAMU-E1 Multi-Position Air Handler
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
Model name <Indoor unit>
Model name <Indoor unit>
Series PVA
2015
Contents
1 SAFETY PRECAUTION ................................................................................................................................................... 2
2 FEATURES ......................................................................................................................................................................5
3 PART NAMES AND FUNCTIONS ....................................................................................................................................6
4 SPECIFICATION ..............................................................................................................................................................9
5 OUTLINES & DIMENSIONS .......................................................................................................................................... 13
6 WIRING DIAGRAM ........................................................................................................................................................ 15
7 REFRIGERANT SYSTEM DIAGRAM ............................................................................................................................ 16
8 MICROPROCESSOR CONTROL ..................................................................................................................................17
9 TROUBLESHOOTING ................................................................................................................................................... 29
10 DISASSEMBLY PROCEDURE ......................................................................................................................................39
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
2
SAFETY PRECAUTION1
Safety Precautions
Read before installation and performing electrical work
Symbol explanations
Thoroughly read the following safety precautions prior to installation.Observe these safety precautions for your safety.This equipment may have adverse effects on the equipment on the same power supply system.Contact the local power authority before connecting to the system.
WARNING
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.
CAUTION
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam-
age to the unit.
Indicates an action that must be avoided.
Indicates important instructions.
Indicates a parts that requires grounding.
Indicates that caution must be taken with rotating parts. (This symbol is on the main unit label.) <Color: Yellow>
Indicates that the parts that are marked with this symbol pose a risk of electric shock. (This symbol is on the main unit label.) <Color: Yellow>
WARNING
Carefully read the labels affixed to the main unit.
WARNING
Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.
Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, during repair, or at the time of disposal of the unit. It may also be in violation of applicable laws. MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant.
Ask your dealer or a qualified technician to install the unit.
Improper installation by the user may result in water leak­age, electric shock, or fire.
Properly install the unit on a surface that can withstand its weight.
Unit installed on an unstable surface may fall and cause in­jury.
Only use specified cables. Securely connect each cable so that the terminals do not carry the weight of the cable.
Improperly connected cables may produce heat and start a fire.
Take appropriate safety measures against wind gusts and earthquakes to prevent the unit from toppling over.
Improper installation may cause the unit to topple over and cause injury or damage to the unit.
Only use accessories (i.e., air cleaners, humidifiers, electric heaters) recommended by Mitsubishi Electric.
Do not make any modifications or alterations to the unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock, or fire.
Do not touch the heat exchanger fins with bare hands.
The fins are sharp and pose a risk of cuts.
In the event of a refrigerant leak, thoroughly ventilate the room.
If gaseous refrigerant leaks out and comes in contact with an open flame, toxic gases will be generated.
Properly install the unit according to the instructions in the Installation Manual.
Improper installation may result in water leakage, electric shock, or fire.
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
3
Have all electrical work performed by an authorized electri­cian according to the local regulations and the instructions in this manual. Use a dedicated circuit.
Insufficient power supply capacity or improper installation of the unit may result in malfunctions of the unit, electric shock, or fire.
Keep electrical parts away from water.
Wet electrical parts pose a risk of electric shock, smoke, or fire.
Securely attach the control box cover.
If the cover is not installed properly, dust or water may infil­trate and pose a risk of electric shock, smoke, or fire.
Only use the type of refrigerant that is indicated on the unit when installing or relocating the unit.
Infiltration of any other types of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.
When installing the unit in a small space, take appropriate precautions to prevent leaked refrigerant from reaching the limiting concentration.
Leaked refrigerant gas will displace oxygen and may cause oxygen starvation. Consult your dealer before installing the unit.
Consult your dealer or a qualified technician when moving or reinstalling the unit.
Improper installation may result in water leakage, electric shock, or fire.
After completing the service work, check for a refrigerant leak.
If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, toxic gases will be gener­ated.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature switch by defeating the safety features for these devices, or the use of accessories other than the ones that are recom­mended by Mitsubishi Electric may result in smoke, fire, or explosion.
Consult your dealer for proper disposal method.
Do not use a leak detection additive.
4
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
Precautions for handling units for use with R410A
CAUTION
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the re­sidual refrigerant and refrigerator oil in the existing piping may cause the refrigerator oil in the new unit to deteriorate.
Use refrigerant piping materials made of phosphorus deox­idized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and moisture.
Contaminants in the refrigerant piping may cause the refrig­erator oil to deteriorate.
Store the piping materials indoors, and keep both ends of the pipes sealed until immediately before brazing. (Keep el­bows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate or cause the compressor to malfunction.
Use a small amount of ester oil, ether oil, or alkyl benzene to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the re­frigerator oil to deteriorate.
Charge the system with refrigerant in the liquid phase.
If gaseous refrigerant is drawn out of the cylinder first, the composition of the remaining refrigerant in the cylinder will change and become unsuitable for use.
Only use R410A.
The use of other types of refrigerant that contain chloride may cause the refrigerator oil to deteriorate.
Use a vacuum pump with a check valve.
If a vacuum pump that is not equipped with a check valve is used, the vacuum pump oil may flow into the refrigerant cy­cle and cause the refrigerator oil to deteriorate.
Prepare tools for exclusive use with R 410A. Do not use the following tools if they have been used with the conventional refrigerant: gauge manifold, charging hose, gas leak detec­tor, check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.
If the refrigerant or the refrigerator oil that may be left on these tools are mixed in with R410A, it may cause the refrigerator oil in the new system to deteriorate. Infiltration of water may cause the refrigerator oil to deteriorate. Leak detectors for conventional refrigerants will not detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant in the cylinder will change and become unsuitable for use.
Exercise special care when handling tools for use with R410A.
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate.
5
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
FEATURES2
Model
Cooling capacity/Heating capacity
Btu/h kW
PVFY-P12NAMU-E1 12000/13500 3.5/4.0
PVFY-P18NAMU-E1 18000/20000 5.3/5.9
PVFY-P24NAMU-E1 24000/27000 7.0/7.9
PVFY-P30NAMU-E1 30000/34000 8.8/10.0
PVFY-P36NAMU-E1 36000/40000 10.6/11.7
PVFY-P48NAMU-E1 48000/54000 14.1/15.8
PVFY-P54NAMU-E1 54000/60000 15.8/17.6
6
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
PART NAMES AND FUNCTIONS3
1. Indoor Unit
Air inlet
Air outlet
(1)Vertical
(2)Horizontal Right
Air inlet
Air outlet
Air inlet
Air outlet
(3)Horizontal left
(4)Down flow
7
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
1. Remote Controller
[PAC-YT53CRAU]
Once the operation mode is selected, the unit will remain in the selected mode until changed.
(1) Remote Controller Buttons
.
Backlit LCD
TEMP. button
MODE button
ON/OFF lamp
ON/OFF button
FAN button
VANE button
The lamp will light up in green when turned on, and blink during startup and when an error occurs.
Pressing this button starts and stops the operation.
• Keep the remote controller out of direct sunlight to ensure accurate measurement of room temperature.
• The thermistor at the lower right-hand section of the remote controller must be free from obstructions to
ensure accurate measurement of room temperature.
• To set the functions that are not available on this controller (PAC-YT53CRAU), use MA remote controller or
the centralized controller.
8
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
*2 icon
For M-Series and P-Series, when an error occurs, power indicator will blink, and refrigerant address (two digits), error code (two digits), and unit No. will blink. For City Multi, when an error occurs, power indicator will blink, and unit address (three digits) and error code (four digits) will blink. Check the error status, stop the operation, and consult your dealer.
When only error code blinks, air conditioning units stay in operation, but an error may have occurred. Check the error code, and consult your dealer.
Room
Set to
AUTO COOLHEATFAN DRYING VENTI. SETBACK
Unit address blinks.
Error code blinks.
Room
Set to
AUTO COOL HEATFAN DRYING VENTI. SETBACK
Error code blinks.
icon appears while the unit is operated in the
energy-save mode
* All icons are displayed for explanation.
icon appears when Operation lock setting is
effective.
icon appears when indoor unit functions are set up.
(Refer to the Installation Manual.)
Fan speed icon Vane icon
icon appears when the power is on.
Indoor temperature
Operation modes
CENTRAL icon *1
CHECK icon *2
Preset temperature *3
*1 icon
Appears when one of the following local operations is prohibited: ON/OFF; operation mode; preset temperature; fan speed; vane.
CENTRAL
*3 Preset temperature
* Centigrade or Fahrenheit is selectable. Refer to the Installation Manual for details.
In COOL, DRYING, HEAT, or AUTO (single set point) modes
In AUTO (dual set point) or
SETBACK modes
Room
Set to
AUTO COOL HEATFAN DRYING VENTI. SETBACK
Preset temperature
Room
Set to
AUTO COOLHEATFAN
DRYING VENTI. SETBACK
Heating preset temperature
Cooling preset temperature
(2) Remote Controller Display
9
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
1. Specifications
Model PVFY-P12NAMU-E1 PVFY-P18NAMU-E1 PVFY-P24NAMU-E1
Power source 1-phase 208/230V 60Hz
Cooling capacity (Nominal)
*1 Btu / h 12,000 18,000 24,000
*1 kW 3.5 5.3 7.0
Power input kW 0.08 0.13 0.18
Current input A 0.80/0.70 1.20/1.10 1.60/1.40
Heating capacity *2 Btu / h 13,500 20,000 27,000
(Nominal) *2 kW 4.0 5.9 7.9
Power input kW 0.08 0.13 0.18
Current input A 0.80/0.70 1.20/1.10 1.60/1.40
External finish Galvanized steel cabinet -Powder coated slate gray
External dimension
H x W x D
In. 50-1/4x17x21-5/8
mm 1275 x 432 x 548
Net weight Lbs. (kg) 113(51)
Heat exchanger Cross fin (Aluminium fin and copper tube)
FAN
Type x Quantity Sirocco fan x 1
External static press.
In.WG <0.30>-0.50-<0.80>
Pa <75>-125-<200>
Motor type DC motor
Motor output kW 0.121
Driving mechanism Direct-driven by motor
Airflow rate (Low-Mid-High)
CFM 280-340-400 410-497-585 515-625-735
m³ / min 7.9-9.6-11.3 11.6-14.1-16.6 14.6-17.7-20.8
L / s 132-160-188 193-235-277 243-295-347
Sound pressure level (Low-Mid-High) (measured in anechoic room)
dB <A> 27-31-35 28-32-36 30-34-38
Insulation material EPS, Polyethylene foam, Urethane foam, Polyester
Air filter PP honeycomb fabric
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A CITY MULTI
Diameter of refrigerant
pipe (O.D.)
Liquid
(R410A)
In. (mm) 1/4 (6.35) Brazed 1/4 (6.35) Brazed 3/8 (9.52) Brazed
Gas
(R410A)
In. (mm) 1/2 (12.7) Brazed 1/2 (12.7) Brazed 5/8 (15.88) Brazed
Diameter of drain pipe In. (mm) 3/4 (19.05) FPT
Drawing External PA94C593
Wiring PA94C598
Refrigerant cycle -
Standard attachment
Document Installation Manual, Instruction Book
Accessory Tie band, Plastic tube, Drain pan seal
Optional parts
External heater adapter CN24RELAY-KIT-CM3
Remark Installation
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual. Due to continuing improvement, above specifications may be subject to change without notice.
SPECIFICATION4
10
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
Model PVFY-P30NAMU-E1 PVFY-P36NAMU-E1
Power source 1-phase 208/230V 60Hz
Cooling capacity (Nominal)
*1 Btu / h 30,000 36,000
*1 kW 8.8 10.6
Power input kW 0.21 0.34
Current input A 2.00/1.70 3.00/2.70
Heating capacity *2 Btu / h 34,000 40,000
(Nominal) *2 kW 10.0 11.7
Power input kW 0.21 0.34
Current input A 2.00/1.70 3.00/2.70
External finish Galvanized steel cabinet -Powder coated slate gray
External dimension
H x W x D
In. 54-1/4x21x21-5/8
mm 1378 x 534 x 548
Net weight Lbs. (kg) 141(64)
Heat exchanger Cross fin (Aluminium fin and copper tube)
FAN
Type x Quantity Sirocco fan x 1
External static press.
in.WG <0.30>-0.50-<0.80>
Pa <75>-125-<200>
Motor type DC motor
Motor output kW 0.244
Driving mechanism Direct-driven by motor
Airflow rate (Low-Mid-High)
CFM 613-744-875 767-931-1095
m³ / min 17.3-21.1-24.8 21.7-26.4-31.0
L / s 290-352-413 362-440-517
Sound pressure level (Low-Mid-High) (measured in anechoic room)
dB <A> 32-36-40 35-39-43
Insulation material EPS, Polyethylene foam, Urethane foam, Polyester
Air filter PP honeycomb fabric
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A CITY MULTI
Diameter of refrigerant
pipe (O.D.)
Liquid
(R410A)
In. (mm) 3/8 (9.52) Brazed
Gas
(R410A)
In. (mm) 5/8 (15.88) Brazed
Diameter of drain pipe In. (mm) 3/4 (19.05) FPT
Drawing External PA94C593
Wiring PA94C598
Refrigerant cycle -
Standard attachment
Document Installation Manual, Instruction Book
Accessory Tie band, Plastic tube, Drain pan seal
Optional parts
External heater adapter CN24RELAY-KIT-CM3
Remark Installation
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual. Due to continuing improvement, above specifications may be subject to change without notice.
11
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
Model PVFY-P48NAMU-E1 PVFY-P54NAMU-E1
Power source 1-phase 208/230V 60Hz
Cooling capacity (Nominal)
*1 Btu / h 48,000 54,000
*1 kW 14.1 15.8
Power input kW 0.42 0.48
Current input A 3.50/3.30 3.90/3.70
Heating capacity *2 Btu / h 54,000 60,000
(Nominal) *2 kW 15.8 17.6
Power input kW 0.42 0.48
Current input A 3.50/3.30 3.90/3.70
External finish Galvanized steel cabinet -Powder coated slate gray
External dimension
H x W x D
In. 59-1/2x25x21-5/8
mm 1511 x 635 x 548
Net weight Lbs. (kg) 172(78)
Heat exchanger Cross fin (Aluminium fin and copper tube)
FAN
Type x Quantity Sirocco fan x 1
External static press.
In.WG <0.30>-0.50-<0.80>
Pa <75>-125-<200>
Motor type DC motor
Motor output kW 0.430
Driving mechanism Direct-driven by motor
Airflow rate (Low-Mid-High)
CFM 980-1190-1400 1040-1262-1485
m³ / min 27.7-33.7-39.6 29.4-35.7-42.0
L / s 463-562-660 492-595-702
Sound pressure level (Low-Mid-High) (measured in anechoic room)
dB <A> 35-39-43 36-40-44
Insulation material EPS, Polyethylene foam, Urethane foam, Polyester
Air filter PP honeycomb fabric
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A CITY MULTI
Diameter of refrigerant
pipe (O.D.)
Liquid
(R410A)
In. (mm) 3/8 (9.52) Brazed
Gas
(R410A)
In. (mm) 5/8 (15.88) Brazed
Diameter of drain pipe In. (mm) 3/4 (19.05) FPT
Drawing External PA94C593
Wiring PA94C598
Refrigerant cycle -
Standard attachment
Document Installation Manual, Instruction Book
Accessory Tie band, Plastic tube, Drain pan seal
Optional parts
External heater adapter CN24RELAY-KIT-CM3
Remark Installation
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual. Due to continuing improvement, above specifications may be subject to change without notice.
12
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
Notes
Note : *1 Nominal cooling conditions *2 Nominal heating conditions Unit convertor
Indoor : 80° F D.B. / 67° F W.B. 70° F D.B. kcal/h = kW x 860
(26.7° C D.B. / 19.4° C W.B.) (21.1° C D.B.) Btu/h = kW x 3,412
Outdoor : 95° F D.B. 47° F D.B. / 43° gF W.B. cfm = m3/min x 35.31
(35° C D.B.) (8.3° C D.B. / 6.1° C W.B.) lbs = kg / 0.4536
Pipe length : 25 ft. (7.6 m) 25 ft. (7.6 m) *Above specification
data is subject to rounding variation.
Level difference : 0 ft. (0 m) 0 ft. (0 m)
*The external static pressure is set to 0.50in. WG(125Pa) at factory shipment.
*Due to continuing improvement, above specification may be subject to change without notice.
Component Symbol PVFY-P12NAMU-E1 PVFY-P18NAMU-E1 PVFY-P24NAMU-E1 Room temperature thermistor
TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ Fuse FUSE 250V 6.3A
Fan motor
8-pole, Output 121W
SIC-71FW-D8121-3
Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse) Power supply terminal block
TB2 (L1, L2, G) 250V 20A
Transmission terminal block
TB5
TB15
(1, 2) 250V 15A, (M1, M2, S) 250V 20A
Component Symbol PVFY-P30NAMU-E1 PVFY-P36NAMU-E1 Room temperature thermistor
TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ Fuse FUSE 250V 6.3A
Fan motor
8-pole, Output 244W
SIC-81FW-D8244-1
Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse) Power supply terminal block
TB2 (L1, L2, G) 250V 20A
Transmission terminal block
TB5
TB15
(1, 2) 250V 15A, (M1, M2, S) 250V 20A
Component Symbol PVFY-P48NAMU-E1 PVFY-P54NAMU-E1 Room temperature thermistor
TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ Fuse FUSE 250V 6.3A
Fan motor
8-pole, Output 430W
M-MW-430-A-1
Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse) Power supply terminal block
TB2 (L1, L2, G) 250V 20A
Transmission terminal block
TB5
TB15
(1, 2) 250V 15A, (M1, M2, S) 250V 20A
2. Electrical component specifications
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
13
OUTLINES & DIMENSIONS5
INDOOR UNIT
PVFY-P12,18, 24, 30, 36, 48, 54NAMU-E1
Unit : mm(in.)
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
14
609.6(24)
Width of Unit
609.6(24)
Length of Unit
Clearance Area
Vertical Installation
Horizontal Installation
Unit : mm(in.)
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
15
6 WIRING DIAGRAM
PVFY-P12,18, 24, 30, 36, 48, 54NAMU-E1
U
U
INSIDE SECTION OF CONTROL BOX
SYMBOL
EXPLANATION
SYMBOL
SYMBOL SYMBOL
CN24-2
TB5
TB2
I.B.
CN32
SW1(I.B.)
SW2(I.B.)
SW3(I.B.)
SW4(I.B.)
SW5(I.B.)
SW11(I.B.)
SW12(I.B.)
SW14(I.B.)
SWA(I.B.)
SWC(I.B.)
SWE(I.B.)
LED1
LED2
CN41
CN51
CN52
CN90
CN105
CN2A
CNEC2
CNF
TH21
TH22
TH23
TB15
CN25
F01
ZNR01,02
DSA
X10
CN24-1
P.B.
CN22
NAME NAME NAME
Indoor controller board
Power supply board
Connector (Humidity output
)
Power source terminal bloc
k
Transmission terminal block
Transmission terminal block
Connector (Fan control)
Connector (Heater control 1st)
Fuse AC250V 6.3A
Varistor
Arrester
Aux. relay
Connector (Heater control 2nd)
Connector (0-10V Analog input)
Connector (IT terminal)
Connector (HA terminal-A)
Thermistor (inlet air temp.detection)
Connector (Centrally control)
Connector (Remote switch)
Connector (Wireless)
Thermistor (piping temp.detection/liquid)
Thermistor (piping temp.detection/gas)
Connector (FAN indication)
Connector (Humidity input)
Connector (Remote indication)
LED (Power supply)
LED (Remote controller supply)
Switch (connection No.set)
Switch (for static pressure selection)
Switch (for static pressure selection)
Connector (emergency operation)
Switch (for mode selection)
Switch (for capacity code)
Switch (for mode selection)
Switch (for model selection)
Switch (for mode selection)
Switch (1st digit address set)
Switch (10ths digit address set)
NOTE:1.Symbols used in wiring diagram above are,
:Connector
:Terminal
(Heavy dotted line):Field wiring
2.Use copper supply wires.
UTILISER DES FILS D'ALIMENTATION EN CUIVRE.
M
MS
3~
4567
1
1232153214 4
LEV
FAN MOTOR
DC280-340V
X10
CNXC1 CNMFCNXA1
TH23
TH22
t
°
t
°
CNXB1
CNEC1
CNEC2
(RED)
TH21
t
°
5321476
RECTIFIER
CIRCUIT
(BLUE)
1
3
21653
4
CN32
CN22
SWE
CN90
SW1
SWA
SW4
SW11
SW12
SW14
SWC
SW5
(GREEN)
LED2
OFF
ON
CN24-2CN24-1
SW3
SW2
CN3A
(BLUE)
(BLUE)(YELLOW)
CN60
CN7V
CN25
2
1
6
534
7
3
213
4
4
1
2
1
431
2
2
1
542
3
CN52
CN20
CN41
CN4F
CN51
CNXB2
CNXC2
(RED)
CN44
(GREEN)
CNXA2
(BLUE)
CNF
(GREEN)
2
1
351
I.B.
CN105
CN2M
F01
DSA
ZNR01
ZNR02
(BLUE)
LED1
CN2A
(BLACK)
(RED)
P. B.
(RED)
CND
TB2
POWER SUPPLY
AC208/230V
S
(SHIELD)
M2
M1
TB5
L2GL1
2
1
TB15
TO OUTDOOR UNIT
BC CONTROLLER
REMOTE CONTROLLER
TO MA REMOTE
CONTROLLER
60Hz
16
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
7 REFRIGERANT SYSTEM DIAGRAM
PVFY-P12,18, 24, 30, 36, 48, 54NAMU-E1
(H)
(I)
(F)
(E)(E)
(C)
(G)
(A)
(D)
(B)
(A) Gas pipe thermistor TH23 (B) Gas pipe (C) Liquid pipe (D) Brazed connections (E) Strainer (#100 mesh) (F) Linear expansion valve (G) Liquid pipe thermistor TH22 (H) Heat exchanger
(I) Room temperature thermistor TH21
Capacity PVFY-P12, 18NAMU-E1 PVFY-P24, 30, 36, 48, 54NAMU-E1 Gas pipe ø12.7 [1/2] ø15.88 [5/8]
Liquid pipe ø6.35 [1/4] ø9.52 [3/8]
17
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
1. Cool operation
.
1.) Thermo-regulating function
(1) Thermo-regulating function (Function to prevent restarting for 3 minutes) When indoor units are connected to the PUHY/PURY/PQHY/PQRY series of outdoor units.
• Room temperature ≥ desired temperature + 0.9° F ···Thermo ON
• Room temperature < desired temperature - 0.9° F···Thermo OFF
When indoor units are connected to the PUMY series of outdoor units.
• Room temperature ≥ desired temperature + 0.9° F ···Thermo ON
• Room temperature < desired temperature - 0.9° F···Thermo OFF
(2) Anti-freezing control
• Detected condition :
When the liquid pipe temp. (TH22) is 32° F or less in 16 minutes from compressors start up, anti-freezing control starts and the thermo OFF.
• Released condition :
The timer which prevents reactivating is set for 3 minutes, and anti-freezing control is cancelled when any one of the following conditions is satisfied.
1) Liquid pipe temp. (TH22) turns 50° F or above.
2) The condition of the thermo OFF has become complete by thermo-regulating, etc.
3) The operation modes became mode other than COOL.
4) The operation stopped.
2) Fan
(1) By the remote controller setting (switch of 3 speeds+Auto).
Type Fan speed notch
3 speeds + Auto type [Low], [Med], [High], [Auto]
• When [Auto] is set, fan speed is changed depending on the value of:
Room temperature - Desired temperature
8 MICROPROCESSOR CONTROL
<How to operate>
1) Press POWER
ON/OFF
button.
2) Press the operation
MODE
button to display COOL.
3) Press the
TEMP.
button to set the desired temperature.
Note:
The set temperature changes 2° F when the
TEMP.
button is
pressed one time. Cooling 67 to 87° F.
18
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
2. Dry operation
.
1.) Thermo regulating function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes) Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21).
• Room temperature ≥ desired temperature + 2° F ···Dry Thermo ON
• Room temperature < desired temperature ···Dry Thermo OFF
Room temperature
3 min. passed since starting operation
Dry thermo
ON time (min)
Dry thermo
OFF time (min)
Thermo regulating
signal
Room temperature
(T1)
Over 64°F
ON
T1 ≥ 83°F 9 3
83°F > T1 ≥ 79°F 7 3
79°F > T1 ≥ 75°F 5 3
75°F > T1 3 3
OFF Unconditional 3 10
Less than 64°F Dry thermo OFF
(2) Frozen prevention control
• No control function
2) Fan
(1) Indoor fan operation controlled depends on the compressor conditions.
Dry thermo Fan speed notch
ON [Low]
OFF
Room temp. ≥ 64°F Stop
Room temp. < 64°F [Low]
<How to operate>
1) Press POWER
ON/OFF
button.
2) Press the operation
MODE
button to display COOL.
3) Press the
TEMP.
button to set the desired temperature.
Note:
The set temperature changes 2° F when the
TEMP.
button is
pressed one time. Cooling 67 to 87° F.
19
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
3. Fan operation
.
1) Fan
(1) Set by remote controller.
Type Fan speed notch
3 speeds + Auto type [Low], [Med], [High], [Auto]
• When [Auto] is set, fan speed becomes [Low].
<How to operate>
1) Press POWER
ON/OFF
button.
2) Press the operation
MODE
button to display FAN.
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
20
4. Heat operation
.
1.) Thermo-regulating function
(1) Thermo-regulating function (Function to prevent restarting for 3 minutes) When indoor units are connected to the PUHY/PURY/PQHY/PQRY series of outdoor units.
• Room temperature < desired temperature - 0.9° F ···Thermo ON
• Room temperature ≥ desired temperature + 0.9° F···Thermo OFF
When indoor units are connected to the PUMY series of outdoor units.
• Room temperature < desired temperature - 0.9° F ···Thermo ON
• Room temperature ≥ desired temperature + 0.9° F···Thermo OFF
2) Fan
(1) By the remote controller setting (switch of 3 speeds+Auto).
Type Fan speed notch
3 speeds + Auto type [Low], [Med], [High], [Auto]
• When [Auto] is set, fan speed is changed depending on the value of:
Desired temperature - Room temperature Give priority to under-mentioned controlled mode
1.) Hot adjust mode
2.) Preheating exclusion mode
3.) Thermo OFF mode (When the compressor off by the thermo-regulating)
4.) Cool air prevention mode (Defrosting mode)
5.) Capacity increasing mode
(2) Hot adjust mode
• The fan controller becomes the hot adjuster mode for the following conditions.
1.) 6.) When starting the HEAT operation
1.) 7.) When the thermo-regulating function changes from OFF to ON.
1.) 8.) When release the HEAT defrosting operation
<How to operate>
1.) Press POWER
ON/OFF
button.
2.) Press the operation
MODE
button to display COOL.
3.) Press the
TEMP.
button to set the desired temperature.
Note:
The set temperature changes 2° F when the
TEMP.
button is
pressed one time. Heating 63 to 83° F.
CAB
[Extra Low]
[Low]
Set fan speed by the remote controller
Hot adjust mode
*1
A: Hot adjust mode starts. B: 5 minutes have passed since the condition A or the indoor liquid pipe temperature turned 95°F or more. C: 2 minutes have passed since the condition A. (Terminating the hot adjust mode)
*1 The fan may stop, depending on the operation status of the indoor units or on the unit settings.
21
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
5. Auto operation [Automatic cool / heat change over operation]
.
<How to operate>
1) Press POWER
ON/OFF
button.
2) Press the operation
MODE
button to display AUTO.
3.) Press the
TEMP.
button to set the desired
temperature.
Note:
The set temperature changes 2° F when the
TEMP.
button
is pressed one time. Heating 63 to 83° F.
(3) Preheating exclusion mode
• When the condition changes the auxiliary heater ON to OFF (thermo-regulating or operation stop, etc.), the
indoor fan operates in [Low] mode for 1 minute.
Note:
This control is same for the model without auxiliary heater.
(4) Thermo OFF mode
• When the thermo-regulating function changes to OFF, the indoor fan operates in [Extra low].
(5) Heat defrosting mode
• The indoor fan stops.
1.) Initial value of operation mode
(1) HEAT mode for room temperature < Desired temperature (2) COOL mode for room temperature ≥ Desired temperature
2) Mode change
(1) HEAT mode -> COOL mode Room temperature Desired temperature + 3°F. or 3 min. has passed (2) COOL mode -> HEAT mode Room temperature Desired temperature - 3°F. or 3 min. has passed
3) COOL mode
(1) Same control as cool operation
4) HEAT mode
(1) Same control as heat operation The value "3°F" is modifiable from 1.8°F to 9°F by maintenance tool.
22
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
6. Heater control
1. Control specifications and DIP S/W setting
• Table 1 shows the function settings the field-installed heater. Select the desired pattern in the table below, and
set the DIP SW on the outdoor and indoor units as shown in Table 1.
Table 1.
Outdoor unit
setting
Condition of outdoor unit
PVFY-NAMU-E
DIP S/W
(Indoor unit)*1
Heater control
SW3-2 SW3-4 Pattern Defrost Error
DIP S/W OFF In the case of:
TGMU:
S/W5-2 OFF THMU/YHMU/ TJMU/YJMU: S/W5-10 OFF TKMU/YKMU:
SW4: 932 OFF
TLMU/YLMU:
SW4: 932 OFF PUMY:
S/W4-4 OFF
N / A
OFF - Heater not Available
ON OFF
Heater
Available
OFF OFF
ON ON
Heater
Available
ON ON*2
DIP S/W ON In the case of:
TGMU:
S/W5-2 ON THMU/YHMU/ TJMU/YJMU: S/W5-10 ON TKMU/YKMU:
SW4: 932 ON
TLMU/YLMU:
SW4: 932 ON PUMY:
S/W4-4 ON
Normal drive
Defrost drive
H/P drive
H/P stop
Condition of O/U
㻼㼍㼞㼍㼙㼑㼠㼑㼞㼟㻌a/b/c/d are set by maintenance tool.
abcd
Outdoor temp.
Normal drive
OFF - Heater not Available
ON OFF
Heater
Available
OFF OFF
ON ON
Heater
Available
ON ON*2
Defrost drive H/P drive H/P
stop
OFF - Heater not Available
ON OFF
Heater
Available
OFF OFF
ON ON
Heater
Available
ON ON*2
*1 Default settings: SW3-2 OFF, SW3-4 OFF *2 Heater will not operate during all error modes. Heater will only operate during a communication error between indoor unit and outdoor unit.
23
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
• Table 2 shows how the field-installed heater is controlled.
Table. 2 [Heater Control Table]
Mode Change
Condition
(To -TRA) >
2.7 ° F
[1.5 °C]
AND
TRA has not
increased by
0.9 °F [0.5°
C] in X min
EH1 ON for
> 5 min
AND
(To -TRA) >
2.7 ° F
[1.5 ° C]
AND
TRA has not
increased by 0.9 ° F
[0.5° C] in 5 min
(To -TRA) <
0.9 °F
[0.5° C]
EH1 ON AND
EH2 ON AND AND
EH1 OFF
EH2 OFF
KEY
• EH1: Electric Heater 1
• EH2: Electric Heater 2
• To: Set point temperature
• TRA: Return Air temperature
• X: Time delay (Selectable. Default is 20 min. Selectable to 10, 15, or 25 min)
• Table 3 shows how the time delay is selected
Table. 3 [Time Delay Selection Table]
Function Setting
*1
Action
*3
108-1 Set Time Delay to 10 minutes
108-2 Set Time Delay to 15 minutes
108-3 Set Time Delay to 20 minutes
*2
108-4 Set Time Delay to 25 minutes
*1
Time delay can only be selected with MA controller. If use of a non-MA controller is desired, the time delay must first be
selected with the MA controller. Then the non-MA controller can be attached and used.
*2
The default time delay setting is 20 minutes.
*3 Time delays are approximate.
24
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
• Chart 1 and Table 4 show an example of heater operation.
Chart 1 [Heater Operation Example]
EH2
ON
OFF
To - 0.9 °F [0.5 °C]
To - 2.7 °F [1.5 °C]
ON
OFF
EH1
T
o
T
RA
X min
X min
X min
> 5 min
Table. 4 [Heater Operation Example]
Step Condition Result
(To -TRA) > 2.7 °F [1.5 °C] AND TRA has not increased by 0.9 °F [0.5°C] in X min EH1 ON
(To -TRA) < 2.7 °F [1.5 °C] AND TRA increasing faster than 0.9 °F [0.5°C] in 5 min EH2 not ON
(To -TRA) < 0.9 °F [0.5°C] EH1 OFF
(To -TRA) > 2.7 °F [1.5 °C] AND TRA has not increased by 0.9 °F [0.5°C] in X min EH1 ON
(To -TRA) > 2.7 °F [1.5 °C] AND TRA not increasing faster than 0.9 °F [0.5°C] in 5 min EH2 ON
(To -TRA) < 0.9 °F [0.5°C]
EH1 OFF EH2 OFF
T
RA
T
RA
T
RA
25
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
Note:
(1) Turning on the heater with the fan setting set to OFF requires that the DIP S/W and connectors on the indoor units are set on site.
Fan control
Pattern
PVFY-NAMU-E1
CN22 for FAN control
(CN24RELAY-KIT-CM3)
DIP S/W3-2 (Indoor unit)
DIP S/W3-4
(Indoor unit)
Fan in error
*1
Fan in defrost
Fan
(All modes other than
defrost and error)
1
Disabled
ON
OFF Stop (Heater OFF)
Set (Heater ON)
High *2 (Heater ON)
2 ON
Stop (Heater OFF)
High (Heater ON)
3
Enabled
OFF Low (Heater OFF) Stop (Heater OFF)
Stop (Heater OFF)
Stop (Heater ON)
4 ON
Low (Heater OFF)
Low (Heater ON)
Stop (Heater OFF)
Stop (Heater ON)
*1 Heater will not operate during all error modes. Heater will only operate during a communication error between indoor unit and outdoor unit *2 While the heater is on, the fan will operate at high speed regardless of the fan setting on the remote controller.
* If a heater is installed in the duct, do not use CN22. By doing so, the fan will turn off when the heater is on,
which may result in fire.
(2) Back-up heating will not be performed when the heater turns on while demand control is performed (not a request item). (3) This is applicable only to the R410 series. Make the settings for the following dip switches on the outdoor unit control board before switching on the power.
26
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
2. CN24RELAY-KIT-CM3 (Optional Parts) installation
The following section describes installation of the External Heater Adapter that connects to CITY MULTI air conditioner R410A series indoor unit. This products is the special wiring parts to drive an electric heater with the air conditioner.
(1) Parts list
• Check that the following parts are included in the package.
1) External output cable.............................2 in total
Two types of cables with different connectors are included.
2) Panel heater connector..........................3 in total
White: 3
(2) Connection to the indoor unit
• Use the cables that fit the connectors on the indoor unit control board.
1) External output cable
This cable is used to connect a relay circuit for an interlocked operation with either an electric or a panel
heater.Select the heater output pattern (1st =CN24-1 or 2nd = CN24-2) to use, and connect the cable to the connector on the indoor unit control board that corresponds to the selection.
1) Panel heater connector
This connector is used to perform an interlocked operation with a panel heater. Depending on the indoor unit
control board specification, connect the cable to CN22 as appropriate
The following section describes installation of the External Heater Adapter that connects to PEA-A AA series indoor unit. This products is the special wiring parts to drive an electric heater wi th the air conditioner.
(1) Parts list
Check that the following par ts are included in the package.
1) External output cable (with a yellow connector).............................2 in total
Tw o types of cables with differen t connectors are included.
2) Panel heater connector........... ................................................... .... 3 in total
White: 1 Green: 2 (2 types)
(2) Connection to the indoor unit
Use the cables that t the connectors on the indoor unit control board.
1) External output cable (with a yellow connector) This cable is used to connect a rela y circuit for an interlocked operati on with either an electric or a panel heater. C onnect the cable to CN24 on the indoor unit control board.
2) Panel heater co nnector (with a white connector) This connector is used to perform an interlocked operation
with a p anel heater. Depending on the indoor unit
control board specification , connect the cable to CN4Y as appropriate
CN4Y for FAN control (CN24RELAY-KIT-CM3)
<Image>
6-3. PAC-YU25HT (Optional Parts) installation
27
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
(3) Wiring
• A basic connection method is shown below.
CN24
X
X
Remote control board Relay circuit
Adapter
Indoor unit
control board
retaeH cirtcelE
ecruos rewop
Red 1
White 2
Preparations in the eld
Maximum cable length is 10 m (32ft)
White
Electric Heater or panel heater
Outdoor unit
control board
• PUHY, PURY-P-TGMU type Dip switch SW5-2 “ON/OFF”
• PUHY, PURY-P-THMU/ YHMU/TJMU/YJMU type Dip switch SW5-10 “ON/ OFF”
• PUHY, PURY-P-TKMU/ YKMU type Dip switch SW4: 932 “ON/OFF”
• PUMY series Dip switch SW4-4 “ON/OFF”
• PUHY, PURY-P-TLMU/ YKMU type Dip switch SW4: 932 “ON/OFF”
CN22
White 1
White 2
White
• The length of the electrical wiring for the CN24RELAY-KIT-CM3 is 2 meters (6-1/2 ft.)
• To extend this length, use sheathed 2-core cable.
Control cable type: CVV, CVS, CPEV or equivalent. Cable size: 0.5 mm2 ~ 1.25 mm2 (16 to 22 AWG) Don't extend the cable more than 10 meters (32ft)
Recommended circuit
Wiring diagram
1-phase power supply
208V, 230V/60Hz
Control board
FS1, 2 ----- Thermal fuse
H1, H2 ----- Heater
26H --------- Overheat protection
thermostat
88H --------- Electromagnetic contactor
FS1
FS2 FS1
FS2
R
S
R
S
CN24-1 or CN24-2
H2
88H
H1
88H
26H
88H
(4) Wiring restrictions
• Keep the length of the cable connecting to the circuit board of the indoor unit shorter than 10 meters (32ft).
• Longer than 10 meters (32ft) could cause improper operation.
• Use a transit relay when extending wiring such as remote wiring.
28
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
7. Humidifier control
The below table shows how the field installed humidifier and fan speed is controlled.
A basic connection method is shown below.
1. Control specifications and DIP S/W setting
2. Installation
DIP switch
setting
Humidistat output
Condition (no defrost/no error) CN25 output Fan speed
SW16 CNFinput
OFF OFFHeat operation & Thermo OFFOFF RC setting
Heat operation & Thermo ON
ON Heat operation & Thermo OFF OFFRC setting
Heat operation & Thermo ON ON High
ON OFFHeat operation & Thermo OFF OFFRC setting
Heat operation & Thermo ON
ON Heat operation & Thermo OFF ON High
Heat operation & Thermo ON
- -Except for heat operation OFFRC setting
RC:Remote controller The fan continues to run for 30 seconds after the humidifier stops.
CNF
CN25
Humidistat
XA
SVA
Humidifier
XA
Indoor unit control board
On-site preparation Maximum cable length is 10m(32ft)
Humidifier
power source
Use XA relay having following specifications
Rated voltage:12VDC Power consumption:1W or less
Humidistat:Minimum applicable load 1mAat DC
Contact rating voltage:15VDC or more Contact rating current:0.1A or more
7. Fan indication
The below table shows how the fan indication is controlled.
A basic connection method is shown below.
1. Indication specifications
2. Installation
Condition Fan speed
CNEC2 output
Relay on the board No. of CNEC2
Very low X11 1 Low X12 2
Middle X13 3 High X14 4
Indoor unit power board
XF1
XF2
XF3
XF4
COM
High
Middle
Low
Very low
1
2
3
4
5
On-site preparation Maximum cable length is 10m(32ft)
XF1,2,3,4 power source: DC30V, 1A or less,
AC230V, 1A or less
X11
X12
X13
X14
CNEC2
1
2
3
4
5
29
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
1. Check methods
1. Component and check points (1) Thermistor
• Room temperature thermistor (TH21)
• Liquid pipe thermistor (TH22)
• Gas pipe thermistor (TH23)
Rt = 15 exp { 3480(
)}
1
273+t
1
273
Disconnect the connector and measure the resistance between terminals with a tester. (Ambient temperature 10°C - 30°C[50°F-86°F])
Normal Abnormal
4.3k - 9.6k Open or short
(Refer to the thermistor characteristic graph below.)
1) Thermistor characteristic graph
Low-temperature thermistor
• Room temperature thermistor (TH21)
• Liquid pipe thermistor (TH22)
• Gas pipe thermistor (TH23)
• Drain sensor (DS)
• Thermistor R
0
= 15 kΩ±3%
• Multiplier of B = 3480 kΩ±2%
0°C 32°F 15k 10°C 50°F 9.6k 20°C 68°F 6.3k 25°C 77°F 5.2k 30°C 86°F 4.3k 40°C 104°F 3.0k
(A) Temperature (°C)[°F] (B) Resistance (kΩ)
0
10
20
30
40
50
-20 -10 01020304050
-4 14 32 50 68 86 104 122
(A)
(B)
(2) Fan motor (CNMF) Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valve Disconnect the connector, and measure the resistance between terminals with a tester. Refer to the next page for details.
1 2 3 4
6
LEV
M
(A)
(C)
(D)
(E)
(F)
CN60
Normal Abnormal
1-6 2-6 3-6 4-6
Open or short
White-Red Yellow-Red Orange-Red Blue-Red
(150) 10%
(A) Red
(C) Blue (D) Orange (E)Yellow (F)White
9 TROUBLESHOOTING
30
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
1) Summary of linear expansion valve (LEV) operation
• The LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor control
board.
• The LEV position changes in response to the pulse signal.
Indoor control board and LEV connection
4
3
6
5
2
1
(G)
(H)
(I)
(J)
(A)
(A)
(B)
(C)
(C)
(D)
(D)
(E)
(E)
(F)
(F)
12VDC
M
4
6
2
3
5
1
(A) Red (G) Control board (C) Blue (H) Connection (CN60) (D) Orange (I) Drive circuit (E) Yellow (J) Linear expansion valve (F) White
Pulse signal output and valve operation
Phase
number
Output pulse
1 2 3 4
ø1 ON OFF OFF ON
ø2 ON ON OFF OFF
ø3 OFF ON ON OFF
ø4 OFF OFF ON ON
The output pulse changes in the following order: When the valve closes 1 -> 2 -> 3 -> 4 -> 1 When the valve opens 4 -> 3 -> 2 -> 1 -> 4
• When the valve position remains the same, all output signals will be OFF.
• If any output signal is missing or if the signal remains ON, the motor vibrates and makes clicking noise.
31
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
2) LEV operation
(f)
(a)
(b)
(e)
(d)
(c)
(a) Close (b) Open (c) Fully open valve (2000 pulses or 3000 pulses) (d) No. of pulses (e) Extra tightening (41 - 100 pulse) (f) Valve opening degree
• When the power is turned on, a pulse signal of fully open pulse + 10% pulse is output (valve closure signal),
to bring the valve to position A.
• When the valve is operating normally, it is free of vibration noise. If the valve locks or when it goes from point
E to A in the figure, it makes louder noise than would be heard when there is an open phase.
• Check for abnormal sound/vibration by placing the metal tip of a screwdriver against the valve and the handle
side against your ear.
3) Troubleshooting
Symptom Checking Criteria Remedy
Circuit failure on the microcomputer
Disconnect the connectors on the control board, and connect LEDs to test the circuit as shown below.
Replace the indoor control board if driving circuit failure is detected.
6
5
4
3
2
1
1 k
LED
Pulse signals are output for 10 seconds when the main power is turned on. If there are LEDs that do not light up at all or remain lit after the pulses are turned off, there is a problem with the driving circuit.
Locked LEV The motor will idle and make small clicking noise if it is run while the
LEV is locked. If this clicking noise is heard both when the valve is fully closed and while it is being opened, it indicates a problem.
Replace the LEV.
Disconnected or
shorted LEV motor coils
Measure the resistance between the coils with a tester (red-white, red-orange, Red-yellow, Red-blue). The normal range of resistance is 150kΩ±10%
Replace the LEV.
32
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
Symptom Checking Criteria Remedy
Valve closure failure (leaky valve)
To check the LEV on the indoor unit, check the indoor unit liquid pipe temperature that appears on the operation monitor on the outdoor unit's multi control board while operating the indoor unit in question in the FAN mode and the other indoor units in the cooling mode.
Replace the LEV if the amount of leakage is great.
(A)
LEV
(A) Termistor (TH22)
Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly lower than the inlet temperature on the remote controller, valve closure failure is suspected. If the amount of leakage is insignificant, replacement of LEV is unnecessary unless it is causing a problem.
Misconnections of
connectors or
contact failure
Perform a visual check for disconnected connectors. Perform a visual check of lead wire color.
Disconnect the connectors on the control board and perform a continuity
test.
33
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
2. DC fan motor (fan motor/indoor control board
1. CAUTION
• A high voltage is applied to the connector for connection to the fan motor (CNMF).
• Do not unplug the connector CNMF with the unit energized to avoid damage to the indoor control board and
fan motor.
2. Troubleshooting
Symptom : The indoor fan cannot turn around.
No
NG
NG
Wiring contact check
Contact of fan motor connector (CNMF)
Check the fuse (FUSE) on indoor controller board.
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
board.
TEST POINT
1 :VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC310~340V
TEST POINT 2 :V
CC
(between 5 (+) and 4 (-) of the fan connector): VCC DC15V
Wiring recovery
Replace drain pump (DP).
Replace indoor controller board.
Measuring points Resistance
PVFY-
P12,18,24,30,36
NAMU-E1
PVFY-
P48,54
NAMU-E1
pin 1 - pin 4
pin 5 - pin 4 50k
pin 6 - pin 4 150k
O.L.
O.L.
47k
143k
1M
O.L.
pin 7 - pin 4
Replace indoor controller board (I.B). Replace fan motor (MF).
Replace indoor
controller board.
Is the resistance of the fan motor
normal?(Refer to below table)
Does the voltage between pin 7 and pin 4
of connector CNMF repeat 0V and 5V?
Replace the fan motor.
Is the voltage normal?
Is there no contact failure?
Ye s
Ye s
Ye s
No
No
No
No
Ye s
Did the fuse blow?
Check the drain pump (DP) Is the resistance between terminals normal?
No
Ye s
Ye s
No
Check the operation of fan.
*To measure the resistance, connect the negative (-) end of the tester to pin 3.
Ye s
Check the operation.
Does the fan motor rotate smoothly?
Tu rn OFF the power supply and connect the connector CNMF. Tu rn ON the power supply and measure the voltage of connector CNMF while rotaing the motor by the hand.
END
OK
END
OK
NG
Replace indoor controller board.
Replace the fan motor.
Check the operation of fan.
Measure the resistance of the fan motor.
Ye s
END
OK
34
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
3, Address switch setting
Make sure that power to the unit is turned off.
ON
OFF
ON
OFF
(A)
(B)
(A) Indoor unit control board (B) Factory setting (all models)
1. Address settings vary in different systems. Refer to the section on address setting in the outdoor unit installation manual.
2. Address is set with a combination of SW12 (10's digit) and SW11 (1's digit). To set the address to "3," set SW12 to "0" and SW11 to "3." To set the address to "25," set SW 12 to "2" and SW 11 to "5."
35
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
4. Voltage test points on the control board
1. PVFY-P12, 18, 24, 30, 36, 48, 54NAMU-E1
CND F01
CNEC1
CNEC2
FMNC1AXNC1CXNC1BXNC
PC51
(*1)
C25
(*1)
C53
(*1)
CN3A
CN2M
SW4
CN24-1
CN24-2
CN32
Indoor controller board
SW3
CN41
CN51
CN52
CN20
CN22
CN7V
CN4F
CN44
SWE
SW2
F01 Fuse (AC 250V 6.3A)
CND Power supply voltage (220 - 240VAC)
CN2M For M-NET transmission cable
connection (24 - 30VDC)
SWE Emergency operation
SW2 Capacity setting
SW4 Function setting
SW3 Function setting
CN32 Remote start/stop adapter
CN3A For MA remote controller cable
connection
(10 - 13 VDC (Between 1 and 3.))
CN52 Remote display
CN51 Centralized control
CN41 JAMA standard HA terminal A
CN44 Thermistor (liquid/gas temperature)
CN4F Float sensor
CN22 For fan control
CN24-1 For 1st heater control
CN24-2 For 2nd heater control
CN20 Thermistor (Inlet temperature)
CNMF Fan motor output
1 - 4: 294 - 340 VDC
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC
(0 - 15 pulse)
CN7V Connect to the indoor power board
CNEC1 Connect to the indoor controller board
CNEC2 FAN OUT
(*1)
VFG Voltage on the (-) side of PC51 and C25
(Same with the voltage between 7 (+) and 4 (-) of CNMF)
VCC Voltage between the C25 pins
15 VDC
(Same with the voltage between 5 (+) and 4 (-) of CNMF)
Vsp Voltage between the C53 pins
0VDC (with the fan stopped)
1 - 6.5VDC (with the fan in operation)
(Same with the voltage between 6 (+) and 4 (-) of CNMF)
36
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
5. Dipswitch setting (Factory setting)
1. Function setting
(1) SW1
Switch
position
Function
Switch setting
ON OFF
1
Active Thermistor (Intake air thermistor)
Built-in thermistor on the remote controller
Indoor unit
2
Filter clogging
detection
Available Unavailable
3 Filter life 2500 hr 100 hr
4 Outdoor air intake Enabled Disabled
5 Remote display Thermo-ON signal Fan output
6 Humidifier operation During heating mode During heating operation
7 Fan speed Low Very low
8
Fan speed at heating Thermo-OFF
Preset fan speed Follows the setting of SW1-7
9
Auto restart after power failure
Enabled Disabled
10 Power start/stop Enabled Disabled
1) Adress board
Factory setting
(2) SW3
Switch
position
Function
Switch setting
ON OFF
1 Unit type Cooling only Heat pump
2
Heater
available
Heater available Heater not available
3 - - -
4
Heater control
Heater ON during defrost and error Heater OFF during defrost and error
5 -
6 - - -
7 - - -
8
Heating
4-deg up
Disabled Enabled
9 - - -
10 - - -
Indoor control board Dipswitch settings must be made while the unit is stopped. Factory setting
37
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
2. Capacity code setting
(1) SW2
1) Indoor control board Dipswitch settings must be made while the unit is stopped. Factory setting The switches are set to correspond to the unit capacity.
PVFY-P12NAMU-E1
PVFY-P18NAMU-E1 PVFY-P24NAMU-E1
PVFY-P30NAMU-E1
PVFY-P36NAMU-E1 PVFY-P48NAMU-E1 PVFY-P54NAMU-E1
3. Model setting
(1) SW4
1) Indoor control board Dipswitch settings must be made while the unit is stopped.
Factory setting
Note:
Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller off). There is no need to power cycle the unit.
4. Power voltage setting
(1) SW5
1) Indoor control board Dipswitch settings must be operated with the main power turned OFF.
Factory setting
220V
(208V)
240V
(230V)
Set SW5 to 240V side when the power supply is 230 volts. When the power supply is 208 volts, set SW5 to 220V side.
38
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
5. External static pressure (1) SWA, SWC
1) Indoor control board
All models
75Pa(0.30in.WG)
1
2
3
SWA
Vertical, Horizontal Right, Horizontal left
SWC
125Pa(0.50in.WG)
1
2
3
SWA SWC
200Pa(0.80in.WG)
1
2
3
SWA SWC
75Pa(0.30in.WG)
1
2
3
SWA
Down flow
SWC
125Pa(0.50in.WG)
1
2
3
SWA SWC
200Pa*(0.80in.WG)
1
2
3
SWA SWC
*PVFY-P36 in Downflow External static pressure: 150Pa (0.60in.WG)
PVFY-P54 in Downflow External static pressure: 175Pa (0.70in.WG)
1
1
2
1
2
1
2
1
2
2
1
2
1
2
Factory setting
1
2
3
SWA SWC
1
2
Note:
Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation status (RUN/STOP) or the remote controller status (ON/OFF).
6. 1s and 10ths digits (1) SW11, SW12 (Rotary switch)
The use of a ME remote controller requires address setting.
1) Indoor control board Address settings must be made while the unit is stopped.
Factory setting
7. Connection No. setting
(1) SW14 (Rotary switch)
This switch is used when the unit connected to an R2 series of outdoor unit.
1) Indoor control board
Factory setting
Note:
Changes to the dipswitches SW11, SW12, SW14, and SW15 must be made while the unit is stopped and the remote controller is OFF.
39
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
1. Control box
Exercise caution when removing heavy parts.
1. Remove the Electric panel (2 screws).
Fig.1
10 DISASSEMBLY PROCEDURE
40
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
2. Thermistor (Return Air)
Exercise caution when removing heavy parts.
1. Remove the Filter panel (2 thumbscrews).
A
B
C
D
E
F
G
H
I
16151413121110
987654321
COMMERCIAL TOLERANCE
WORK GRADE
CASTING
FINE COARSE
PRESS WORKING
ED
CBA
ITEM MODEL NAME
Fig. 3
2. Remove the Blower panel (2 screws).
3. Remove the cover over the Return Air thermistor box and unplug the thermistor.
4. Pull out the thermistor holder and thermistor inside the box.
A
B
C
D
E
F
G
H
16151413121110
Fig. 4
41
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
3. Coil Assembly (thermistor, drainpan, heat exchanger) Exercise caution when removing heavy parts.
1. Remove the Electrical, Blower and Filter panel indicated in sections 1 and 2.
2. Remove the Coil panel by removing all of the screws securing it to the (3) smaller panels for refrigerant and drain lines.
A
B
C
D
E
F
G
H
I
16151413121110
987654321
COMMERCIAL TOLERANCE
WORK GRADE
CASTING
FINE COARSE
PRESS WORKING
ED
CBA
ITEM MODEL NAME
The parts are required to meet the latest RoHS directive.
DETAIL A
DETAIL B
Fig. 5
3. Slide the smaller panels in the directions indicated and remove.
Fig. 6
4. Remove the (1 or 2) brackets that secure the coil, unplug the thermistors and LEV from the control board and route the wires out of the control box area and into the coil section. Next, slide the coil from the frame.
Fig. 7
987654321
The parts are required to meet the latest RoHS directive.
Fig. 8
42
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
5. Remove the plate covering the coil assembly to access the thermistors.
Fig. 9
6. Remove lower and side drain pan.
Fig. 10
43
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
4. Blower/Fan Assembly
Exercise caution when removing heavy parts.
1. Remove the Blower and Filter panel (along with filter if installed) indicated in section 2.
2. Remove the (1 or 2) brackets that secure the coil assembly. (Fig.11)
Fig. 11
3. Remove the door that covers the small enclosure attached to the fan assembly (Fig.12). Unplug the motor and route the wire harness out of the enclosure.
4. Remove the (2) screws that secure the fan assembly and slide out.
Fig. 12
MEUS DOC# MD-1404-K007, January 2017
Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
www.mitsubishielectric-usa.com
Toll Free: 800-433-4822
MITSUBISHI ELECTRIC US, INC.
Please be sure to put the contact address/telephone number on
this manual before handing it to the customer.
This product is designed and intended for use in the residential,
commercial and light-industrial environment.
Loading...