Read before installation and performing electrical work
Thoroughly read the following safety precautions prior to installation.
Observe these safety precautions for your safety.
This equipment may have adverse effects on the equipment on the same power supply system.
Contact the local power authority before connecting to the system.
Symbol explanations
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam-
age to the unit.
Indicates an action that must be avoided.
Indicates important instructions.
Indicates a parts that requires grounding.
Indicates that caution must be taken with rotating parts. (This symbol is on the main unit label.) <Color: Yellow>
Indicates that the parts that are marked with this symbol pose a risk of electric shock. (This symbol is on the main
unit label.) <Color: Yellow>
Carefully read the labels affixed to the main unit.
Do not use refrigerant other than the type indicated in the
manuals provided with the unit and on the nameplate.
Doing so may cause the unit or pipes to burst, or result in
explosion or fire during use, during repair, or at the time of
disposal of the unit.
It may also be in violation of applicable laws.
MITSUBISHI ELECTRIC CORPORATION cannot be held
responsible for malfunctions or accidents resulting from the
use of the wrong type of refrigerant.
Ask your dealer or a qualified technician to install the unit.
Improper installation by the user may result in water leakage, electric shock, or fire.
Properly install the unit on a surface that can withstand its
weight.
Unit installed on an unstable surface may fall and cause injury.
Only use specified cables. Securely connect each cable so
that the terminals do not carry the weight of the cable.
Improperly connected cables may produce heat and start a
fire.
Take appropriate safety measures against wind gusts and
earthquakes to prevent the unit from toppling over.
Improper installation may cause the unit to topple over and
cause injury or damage to the unit.
Only use accessories (i.e., air cleaners, humidifiers, electric
heaters) recommended by Mitsubishi Electric.
Do not make any modifications or alterations to the unit.
Consult your dealer for repair.
Improper repair may result in water leakage, electric shock,
or fire.
Do not touch the heat exchanger fins with bare hands.
The fins are sharp and pose a risk of cuts.
In the event of a refrigerant leak, thoroughly ventilate the
room.
If gaseous refrigerant leaks out and comes in contact with
an open flame, toxic gases will be generated.
Properly install the unit according to the instructions in the
Installation Manual.
Improper installation may result in water leakage, electric
shock, or fire.
HWE1405AGB
ii
Have all electrical work performed by an authorized electrician according to the local regulations and the instructions
in this manual. Use a dedicated circuit.
Insufficient power supply capacity or improper installation
of the unit may result in malfunctions of the unit, electric
shock, or fire.
Keep electrical parts away from water.
Wet electrical parts pose a risk of electric shock, smoke, or
fire.
Consult your dealer or a qualified technician when moving
or reinstalling the unit.
Improper installation may result in water leakage, electric
shock, or fire.
After completing the service work, check for a refrigerant
leak.
If leaked refrigerant is exposed to a heat source, such as a
fan heater, stove, or electric grill, toxic gases will be generated.
Securely attach the control box cover.
If the cover is not installed properly, dust or water may infiltrate and pose a risk of electric shock, smoke, or fire.
Only use the type of refrigerant that is indicated on the unit
when installing or relocating the unit.
Infiltration of any other types of refrigerant or air into the unit
may adversely affect the refrigerant cycle and may cause
the pipes to burst or explode.
When installing the unit in a small space, take appropriate
precautions to prevent leaked refrigerant from reaching the
limiting concentration.
Leaked refrigerant gas will displace oxygen and may cause
oxygen starvation. Consult your dealer before installing the
unit.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature
switch by defeating the safety features for these devices, or
the use of accessories other than the ones that are recommended by Mitsubishi Electric may result in smoke, fire, or
explosion.
Consult your dealer for proper disposal method.
Do not use a leak detection additive.
HWE1405AGB
ii
CAUTION
Precautions for handling units for use with R410A
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the residual refrigerant and refrigerator oil in the existing piping
may cause the refrigerator oil in the new unit to deteriorate.
Use refrigerant piping materials made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the
pipes clean and free of such contaminants as sulfur, oxides,
dust, dirt, shaving particles, oil, and moisture.
Contaminants in the refrigerant piping may cause the refrigerator oil to deteriorate.
Store the piping materials indoors, and keep both ends of
the pipes sealed until immediately before brazing. (Keep elbows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerator oil to deteriorate or cause the
compressor to malfunction.
Use a small amount of ester oil, ether oil, or alkyl benzene
to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the refrigerator oil to deteriorate.
Charge the system with refrigerant in the liquid phase.
If gaseous refrigerant is drawn out of the cylinder first, the
composition of the remaining refrigerant in the cylinder will
change and become unsuitable for use.
Only use R410A.
The use of other types of refrigerant that contain chloride
may cause the refrigerator oil to deteriorate.
Use a vacuum pump with a check valve.
If a vacuum pump that is not equipped with a check valve is
used, the vacuum pump oil may flow into the refrigerant cycle and cause the refrigerator oil to deteriorate.
Prepare tools for exclusive use with R 410A. Do not use the
following tools if they have been used with the conventional
refrigerant: gauge manifold, charging hose, gas leak detector, check valve, refrigerant charge base, vacuum gauge,
and refrigerant recovery equipment.
If the refrigerant or the refrigerator oil that may be left on these
tools are mixed in with R410A, it may cause the refrigerator oil
in the new system to deteriorate.
Infiltration of water may cause the refrigerator oil to deteriorate.
Leak detectors for conventional refrigerants will not detect an
R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant
in the cylinder will change and become unsuitable for use.
Exercise special care when handling tools for use with R410A.
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerator oil to deteriorate.
Once the operation mode is selected, the unit will remain in the selected mode until changed.
(1) Remote Controller Buttons
ON/OFF lamp
The lamp will light up in green when
turned on, and blink during startup
Backlit LCD
and when an error occurs.
ON/OFF button
Pressing this button starts and
TEMP. button
MODE button
stops the operation.
FAN button
VANE button
Keep the remote controller out of direct sunlight to ensure accurate measurement of room temperature.
The thermistor at the lower right-hand section of the remote controller must be free from obstructions to ensure accurate mea-
surement of room temperature.
To set the functions that are not available on this controller (PAC-YT53CRAU), use MA remote controller or the centralized
controller.
HWE1405AGB
- 3 -
[ II Components and Functions ]
(2) Remote Controller Display
CENTRAL icon *1
* All icons are displayed for explanation.
CHECK icon *2
Preset temperature *3
icon appears while the unit is operated in the
energy-save mode
icon appears when Operation lock setting is
effective.
icon appears when indoor unit functions are set up.
(Refer to the Installation Manual.)
Fan speed icon
Vane icon
icon appears when the power is on.
Indoor temperature
Operation modes
*1 icon
CENTRAL
Appears when one of the following local operations is prohibited: ON/OFF; operation mode; preset temperature;
fan speed; vane.
*2 icon
For M-Series and P-Series, when an error occurs, power indicator will blink, and refrigerant address (two digits),
error code (two digits), and unit No. will blink.
For City Multi, when an error occurs, power indicator will blink, and unit address (three digits) and error code (four
digits) will blink.
Check the error status, stop the operation, and consult your dealer.
Set to
Room
Unit address
blinks.
AUTO COOLHEATFAN
DRYING VENTI. SETBACK
Error code
blinks.
When only error code blinks, air conditioning units stay in operation, but an error may have occurred.
Check the error code, and consult your dealer.
Set to
Room
AUTO COOLHEATFAN
DRYING VENTI. SETBACK
Error code
blinks.
*3 Preset temperature
* Centigrade or Fahrenheit is selectable. Refer to the Installation Manual for details.
3. Press the button to set the desired temperature.
TEMP.
MODE
The set temperature changes 2°F when the button is
TEMP.
pressed one time. Cooling 67 to 87°F
1. Termoregulating function
(1) Thermoregulating function (Function to prevent restarting for 3 minutes)
When indoor units are connected to the PUHY/PURY/PQHY/PQRY series of outdoor units.
Room temperature desired temperature + 0.9°F ···Thermo ON
Room temperature desired temperature - 0.9°F···Thermo OFF
When indoor units are connected to the PUMY series of outdoor units.
Room temperature desired temperature + 1.8°F ···Thermo ON
Room temperature desired temperature ···Thermo OFF
(2) Anti-freezing control
Detected condition :
When the liquid pipe temp. (TH22) is 32°F or less in 16 minutes from compressors start up, anti-freezing control starts and
the thermo OFF.
Released condition :
The timer which prevents reactivating is set for 3 minutes, and anti-freezing control is cancelled when any one of the following
conditions is satisfied.
1) Liquid pipe temp. (TH22) turns 50°F or above.
2) The condition of the thermo OFF has become complete by thermoregulating, etc.
3) The operation modes became mode other than COOL.
4) The operation stopped.
2. Fan
(1) By the remote controller setting (switch of 3 speeds+Auto)
TypeFan speed notch
3 speeds + Auto type[Low], [Med], [High], [Auto]
When [Auto] is set, fan speed is changed depending on the value of: Room temperature - Desired temperature
HWE1405AGB
- 12 -
[ VII Microprocessor Control ]
.
ON/OFF
2. Fan operation
1. Fan
(1) Set by remote controller.
3 speeds + Auto type[Low], [Med], [High], [Auto]
<How to operate>
1. Press POWER button.
2. Press the operation button to display FAN.
MODE
TypeFan speed notch
When [Auto] is set, fan speed becomes [Low].
HWE1405AGB
- 13 -
[ VII Microprocessor Control ]
.
ON/OFF
TEMP.
3. Heat operation
<How to operate>
1. Press POWER button.
2. Press the operation button to display HEAT.
3. Press the button to set the desired temperature.
TEMP.
The set temperature changes 2°F when the button is
pressed one time. Heating 63 to 83°F.
1. Termoregulating function
(1) Thermoregulating function (Function to prevent restarting for 3 minutes)
When indoor units are connected to the PUHY/PURY/PQHY/PQRY series of outdoor units.
Room temperature desired temperature -0.9°F ···Thermo ON
Room temperature desired temperature +0.9°F ···Thermo OFF
MODE
When indoor units are connected to the PUMY series of outdoor units.
Room temperature desired temperature -1.8°F ···Thermo ON
Room temperature desired temperature ···Thermo OFF
2. Fan
(1) By the remote controller setting (switch of 3 speeds+Auto)
TypeFan speed notch
3 speeds + Auto type[Low], [Med], [High], [Auto]
When [Auto] is set, fan speed is changed depending on the value of:
Desired temperature - Room temperature
Give priority to under-mentioned controlled mode
1) Hot adjust mode
2) Preheating exclusion mode
3) Thermo OFF mode (When the compressor off by the thermoregulating)
4) Cool air prevention mode (Defrosting mode)
5) Capacity increasing mode
(2) Hot adjust mode
The fan controller becomes the hot adjuster mode for the following conditions.
1) When starting the HEAT operation
2) When the thermoregulating function changes from OFF to ON.
3) When release the HEAT defrosting operation
Hot adjust mode
Set fan speed by the remote controller
[Low]
*1
[Extra Low]
A: Hot adjust mode starts.
B: 5 minutes have passed since the condition A or the indoor liquid pipe temperature turned 95°F or more.
C: 2 minutes have passed since the condition A. (Terminating the hot adjust mode)
*1 The fan may stop, depending on the operation status of the indoor units or on the unit settings.
HWE1405AGB
CAB
- 14 -
[ VII Microprocessor Control ]
.
ON/OFF
(3) Preheating exclusion mode
When the condition changes the auxiliary heater ON to OFF (thermoregulating or operation stop, etc.), the indoor fan operates
in [Low] mode for 1 minute.
This control is same for the model without auxiliary heater.
(4) Thermo OFF mode
When the thermoregulating function changes to OFF, the indoor fan operates in [Extra low].
(5) Heat defrosting mode
The indoor fan stops.
4. Auto operation [Automatic cool / heat change over operation]
<How to operate>
1. Press POWER button.
2. Press the operation button to display AUTO.
3. Press the button to set the desired temperature.
TEMP.
MODE
The set temperature changes 2°F when the button is
pressed one time. Automatic 67 to 83°F
1. Initial value of operation mode
(1) HEAT mode for room temperature < Desired temperature
(2) COOL mode for room temperature Desired temperature
2. Mode change
(1) HEAT mode -> COOL mode
Room temperature Desired temperature + 3°F. or 3 min. has passed
(2) COOL mode -> HEAT mode
Room temperature Desired temperature - 3°F. or 3 min. has passed
3. COOL mode
(1) Same control as cool operation
4. HEAT mode
(1) Same control as heat operation
The value "3°F" is modifiable from 1.8°F to 9°F by maintenance tool.
TEMP.
HWE1405AGB
- 15 -
[ VII Microprocessor Control ]
5. Heater control
1. Control specifications and DIP S/W setting
Table 1 shows how the field-installed heater is controlled. Select the desired pattern in the table below, and set the DIP S/W
on the outdoor and indoor units as shown in Table 1. See section 3 "Installation" for details. The table below shows Heater
Control patterns #1, 2, and 3.
Table.1
Outdoor unit
setting
DIP S/W OFF
In the case of:
TGMU:
S/W5-2 OFF
THMU/YHMU/
TJMU/YJMU:
S/W5-10 OFF
TKMU/YKMU:
SW4: 932 OFF
PUMY:
S/W4-4 OFF
Condition of outdoor unit
N / A
DIP S/W
(Indoor unit)
SW3-2SW3-4PatternDefrostError
-OFF#1OFFOFF
OFFON#2OFFON
ONON#3OFFON
PVFY-NAMU-E
Heater control
*1
*1
DIP S/W ON
In the case of:
TGMU:
S/W5-2 ON
THMU/YHMU/
TJMU/YJMU:
S/W5-10 ON
TKMU/YKMU:
SW4: 932 ON
PUMY:
S/W4-4 ON
Norm al drive
Defrost drive
Condition of O/U
abcd
Outdoor temp.
㻼㼍㼞㼍㼙㼑㼠㼑㼞㼟㻌a/b/c/d are set by㻌
maintenance tool.
Normal drive
H/P drive
H/P stop
Defrost drive
H/P drive
H/P stop
-OFF#1OFFOFF
OFFONOFFOFFOFF
ONONOFFOFFOFF
-OFF#1OFFOFF
OFFON#2OFFON
ONON#3OFFON
*1. Not applicable to communication error, return air thermistor error, and motor error.
*1
*1
HWE1405AGB
- 16 -
[ VII Microprocessor Control ]
Heater controlDIP switch
setting
Initial
setting
PatternOutputDetailsSW3-2SW3-4
#1
(Enable
heater
basic
control)
1
st
st
nd
st
nd
Table 2
When indoor units are connected to the PUHY/PURY/PQHY/PQRY series of outdoor units
Heater OFF
Inlet air temp. set temp.≥+0.9°F(+0.5°C)
Heater ON
Inlet air temp.< set temp. -2.7°F(- 1.5°C)
· The fan will stop and the heater will turn off when [ DEFROST ] or [ERROR] is disp layed.
Set temp.+0.9°F(+0.5°C)
Inlet air temp.
Heater output
#2
(Enable
heater
comfort
mode)
1
2
Heater OFF
Inlet air temp.≥ set temp. +0.9°F(+0.5°C)
Heater ON
Inlet air t emp.< set temp. -0.9°F(- 0.5°C)
· The fan will stop and the heater will turn off when [DEFROST] is displayed.
Inlet air temp.
Heater output
Heater OFF
Set temp.(Room temperature setting)
Set temp.-0.9°F(-0.5°C)
Set temp.-2.7°F(-1.5°C)
ON
OFF
Set temp.+0.9°F(+0.5°C)
Set temp.(Room temperature setting)
Set temp.-0.9°F(-0.5°C)
ON
OFF
Inlet air temp.≥ set temp. +0.9°F(+0.5°C)
Heater ON
Inlet air t emp.< set temp. -1.8°F( -1°C)
· The fan will stop and the heater will turn off when [DEFROST] is displayed.
Set temp.+0.9°F(+0.5°C)
Inlet air temp.
Heater output
Set temp.(Room temperature setting)
Set temp.-0.9°F(-0.5°C)
Set temp.-1.8°F(-1°C)
ON
OFF
OFFON
OFF
#3
(Enable
heater
economy
mode)
1
Heater OFF
Inlet air temp.≥ set temp.-0.9°F(-0.5°C)
Heater ON
Inlet air t emp.< s et temp. -2.7°F(-1.5°C)
· The fan will stop and the heater will turn off when [DEFROST] is displayed.
Inlet air temp.
Heater output
2
Inlet air temp. ≥ set temp.-0.9 °F(-0.5°C)
Heater ON
Inlet air t emp.< set temp. -3.6°F(- 2°C)
· The fan will stop and the heater will turn off when [DEFROST] is displayed.
Inlet air temp.
Heater output
1st: Heater output from CN24-1(yellow) on the indoor unit control board
nd
2
: Heater outp ut from CN2 4-2(blu e) on the indoor unit contr ol board
Set temp.+0.9°F(+0.5°C)
Set temp.(Room temperature setting)
Set temp.-0.9°F(-0.5°C)
Set temp.-2.7°F(-1.5°C)
Set temp.+0.9°F(+0.5°C)
Set temp.(Room temperature setting)
Set temp.-0.9°F(-0.5°C)
Set temp.-3.6°F(-2°C)
ON
OFF
ONON
HWE1405AGB
- 17 -
[ VII Microprocessor Control ]
Heater controlDIP switch
setting
Initial
setting
PatternOutputDetailsSW3-2SW3-4
#1
(Enable
heater
basic
control)
1
st
st
nd
st
nd
Table 3
When indoor units are connected to the PUMY series of outdoor units
Heater OFF
Inlet air temp. set temp.≥
Heater ON
Inlet air temp.< set temp. -3.6°F(- 2°C)
· The fan will stop and the heater will turn off when [ DEFROST ] or [ERROR] is disp layed.
Set temp.(Room temperature setting)
Inlet air temp.
Heater output
#2
(Enable
heater
comfort
mode)
1
2
Heater OFF
Inlet air temp.≥ set temp.
Heater ON
Inlet air temp.< set temp. -1 .8°F(- 1°C)
· The fan will stop and the heater will turn off when [DEFROST] is displayed.
Inlet air temp.
Heater output
Heater OFF
Set temp.-0.9°F(-0.5°C)
Set temp.-1.8°F(-1°C)
Set temp.-3.6°F(-2°C)
ON
OFF
Set temp.(Room temperature setting)
Set temp.-0.9°F(-0.5°C)
Set temp.-1.8°F(-1°C)
ON
OFF
Inlet air temp.≥ set temp. +0.9°F(+0.5°C)
Heater ON
Inlet air t emp.< set temp. -1.8°F( -1°C)
· The fan will stop and the heater will turn off when [DEFROST] is displayed.
Set temp.(Room temperature setting)
Inlet air temp.
Heater output
Set temp.-0.9°F(-0.5°C)
Set temp.-1.8°F(-1°C)
Set temp.-2.7°F(-1.5°C)
ON
OFF
OFFON
OFF
#3
(Enable
heater
economy
mode)
1
Heater OFF
Inlet air temp.≥ set temp.-0.9°F(-0.5°C)
Heater ON
Inlet air t emp.< s et temp. -2.7°F(-1.5°C)
· The fan will stop and the heater will turn off when [DEFROST] is displayed.
Inlet air temp.
Heater output
2
Inlet air temp. ≥ set temp.-0.9 °F(-0.5°C)
Heater ON
Inlet air t emp.< set temp. -3.6°F(- 2°C)
· The fan will stop and the heater will turn off when [DEFROST] is displayed.
Inlet air temp.
Heater output
1st: Heater output from CN24-1(yellow) on the indoor unit control board
nd
2
: Heater outp ut from CN2 4-2(blu e) on the indoor unit contr ol board
Set temp.(Room temperature setting)
Set temp.-0.9°F(-0.5°C)
Set temp.-1.8°F(-1°C)
Set temp.-3.6°F(-2°C)
Set temp.(Room temperature setting)
Set temp.-0.9°F(-0.5°C)
Set temp.-1.8°F(-1°C)
Set temp.-4.5°F(-2.5°C)
ON
OFF
ONON
HWE1405AGB
- 18 -
[ VII Microprocessor Control ]
(1) Turning on the heater with the fan setting set to OFF requires that the DIP S/W and connectors on the indoor units are set on
site.
Fan control
PatternPVFY-NAMU-E
CN22 for FAN control (YU25)DIP S/W3-4 (Indoor unit)Fan in defrost
1Disabled
(CN22 cannot be used with
2
this unit)
OFFStop (Heater OFF)Set (Heater ON)
ONStop (Heater OFF)High
Fan (All modes other
than Defrost)
*1
(Heater ON)
*1. While the heater is on, the fan will operate at high speed regardless of the fan setting on the remote controller.
* If a heater is installed in the duct, do not use CN22. By doing so, the fan will turn off when the heater is on,
which may result in fire.
(2) Back-up heating will not be performed when the heater turns on while demand control is performed (not a request item).
(3) This is applicable only to the R410 series. Make the settings for the following dip switches on the outdoor unit control board
before switching on the power.
2. PAC-YU25HT (Optional Parts) installation
The following section describes installation of the External Heater Adapter that connects to CITY MULTI air conditioner R410A
series indoor unit. This products is the special wiring parts to drive an electric heater with the air conditioner.
(1) Parts list
Check that the following parts are included in the package.
1) External output cable (with a yellow connector).............................2 in total
Two types of cables with different connectors are included.
2) Panel heater connector.................................................................. 3 in total
White: 1
Green: 2 (2 types)
* Panel heater connectors cannot be used with this unit.
(2) Connection to the indoor unit
Use the cables that fit the connectors on the indoor unit control board.
1) External output cable (with a yellow connector)
This cable is used to connect a relay circuit for an interlocked operation with either an electric or a panel heater.Select the
heater output pattern (1st =CN24-1 or 2nd = CN24-2) to use, and connect the cable to the connector on the indoor unit control
board that corresponds to the selection.
(3) Locally procured wiring
A basic connection method is shown below.
Remote control boardRelay circuit
retaeH cirtcelE
ecruos rewop
X
Electric Heater
or panel
heater
Preparations in the field
Indoor unit
Adapter
Red1
X
White 2
Maximum cable length
is 10 m (32ft)
control board
CN24-1 or CN24-2
wolle
Y
Outdoor unit
control board
• PUHY, PURY-P-TGMU
type Dip switch SW5-2
“ON/OFF”
• PUHY, PURY-P-THMU/
YHMU/TJMU/YJMU type
Dip switch SW5-10 “ON/
OFF”
• PUHY, PURY-P-TKMU/
YKMU type Dip switch
SW4: 932 “ON/OFF”
• PUMY series
Dip switch SW4-4
“ON/OFF”
For relay X use the specifications given below Operation coil
Rated voltage: 12VDC
Power consumption: 1W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU25HT is 2 meters (6-1/2 ft.)
HWE1405AGB
- 19 -
[ VII Microprocessor Control ]
To extend this length, use sheathed 2-core cable.
Control cable type: CVV, CVS, CPEV or equivalent.
Cable size: 0.5 mm
2
~ 1.25 mm2 (16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
Recommended circuit
Wiring diagram
1-phase power
supply
208V, 230V/60Hz
R
S
R
S
Control board
FS1
88H
FS2
FS1
FS2
88H
88H
CN24-1 or CN24-2
26H
H1
H2
FS1, 2 ----- Thermal fuse
H1, H2 ----- Heater
26H --------- Overheat protection
88H --------- Electromagnetic contactor
thermostat
(4) Wiring restrictions
Keep the length of the cable connecting to the circuit board of the indoor unit shorter than 10 meters (32ft).
Longer than 10 meters (32ft) could cause improper operation.
Use a transit relay when extending wiring such as remote wiring.
HWE1405AGB
- 20 -
[ VII Microprocessor Control ]
The below table shows how the field installed humidifier and fan speed is controlled.
A basic connection method is shown below.
1. Control specifications and DIP S/W setting
2. Installation
DIP switch
setting
Humidistat
output
Condition (no defrost/no error) CN25 output Fan speed
SW1 6CNF input
OFF OFFHeat operation & Thermo OFF OFFRC setting
Heat operation & Thermo ON
ONHeat operation & Thermo OFF OFFRC setting
Heat operation & Thermo ON ONHigh
ON OFFHeat operation & Thermo OFF OFFRC setting
Heat operation & Thermo ON
ONHeat operation & Thermo OFF ONHigh
Heat operation & Thermo ON
- -Except for heat operation OFFRC setting
RC:Remote controller
The fan continues to run for 30 seconds after the humidifier stops.
CNF
CN25
Humidistat
XA
SVA
Humidifier
XA
Indoor unit
control board
On-site preparation
Maximum cable length is 10m(32ft)
Humidifier
power source
Use XA relay having following specifications
Rated voltage:12VDC
Power consumption:1W or less
Humidistat:Minimum applicable load 1mA at DC
Contact rating voltage:15VDC or more
Contact rating current:0.1A or more
6. Humidifier control
7. Fan indication
1. Indication specifications
The below table shows how the fan indication is controlled.
Condition
Fan speed
Very low X11 1
Low X12 2
Middle X13 3
High X14 4
2. Installation
A basic connection method is shown below.
Very lo w
Middle
COM
CNEC2 output
Relay on the board No. of CNEC2
XF1
Low
High
On-site preparation
Maximum cable length is 10m(32ft)
Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
NormalAbnormal
(150 ) 10%
M
LEV
(F)
(E)
(D)
(C)
(A)
CN60
1
2
3
4
6
1-62-63-64-6Open or short
White-RedYellow-RedOrange-RedBlue-Red
(A)Red(E)Yellow
(C)Blue(F)White
(D)Orange
HWE1405AGB
- 22 -
[ VIII Troubleshooting ]
1) Summary of linear expansion valve (LEV) operation
The LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor control board.
The LEV position changes in response to the pulse signal.
Indoor control board and LEV connection
(G)
12VDC
(F)
(J)
(C)
4
M
5
1
(D)
(B)
(A)
6
(E)
2
3
(A)
(C)
(D)
(E)
(F)
6
5
4
3
2
1
(H)
(A)Red(G)Control board
(C)Blue(H)Connection (CN60)
(D)Orange(I)Drive circuit
(E)Yellow(J)Linear expansion valve
(F)White
Pulse signal output and valve operation
Phase
number
1234
Output pulse
ø1ONOFFOFFON
ø2ONONOFFOFF
ø3OFFONONOFF
ø4OFFOFFONON
The output pulse changes in the following order:
When the valve closes 1 -> 2 -> 3 -> 4 -> 1
When the valve opens 4 -> 3 -> 2 -> 1 -> 4
When the valve position remains the same, all output signals will be OFF.
If any output signal is missing or if the signal remains ON, the motor vibrates and makes clicking noise.
(I)
HWE1405AGB
- 23 -
[ VIII Troubleshooting ]
2) LEV operation
(a)Close
(b)Open
(c)Fully open valve (2000 pulses or 3000 pulses)
(d)No. of pulses
(a)
(f)
(b)
(c)
(d)
(e)
(e)Extra tightening (41 - 100 pulse)
(f)Valve opening degree
When the power is turned on, a pulse signal of fully open pulse + 10% pulse is output (valve closure signal), to bring the valve
to position A.
When the valve is operating normally, it is free of vibration noise. If the valve locks or when it goes from point E to A in the
figure, it makes louder noise than would be heard when there is an open phase.
Check for abnormal sound/vibration by placing the metal tip of a screwdriver against the valve and the handle side against
your ear.
3) Troubleshooting
SymptomChecking CriteriaRemedy
Circuit failure on
the microcomputer
Disconnect the connectors on the control board, and connect LEDs to test the circuit as shown below.
6
5
4
3
2
1 k
LED
1
Pulse signals are output for 10 seconds when the main power is turned on. If there
are LEDs that do not light up at all or remain lit after the pulses are turned off, there
is a problem with the driving circuit.
Locked LEVThe motor will idle and make small clicking noise if it is run while the LEV is locked.
If this clicking noise is heard both when the valve is fully closed and while it is being
opened, it indicates a problem.
Disconnected or
shorted LEV motor
Measure the resistance between the coils with a tester (red-white, red-orange,
Red-yellow, Red-blue). The normal range of resistance is 15010%
coils
Replace the indoor control
board if driving
circuit failure is
detected.
Replace the LEV.
Replace the LEV.
HWE1405AGB
- 24 -
[ VIII Troubleshooting ]
SymptomChecking CriteriaRemedy
Valve closure failure (leaky valve)
Misconnections of
connectors or contact failure
To check the LEV on the indoor unit, check the indoor unit liquid pipe temperature
that appears on the operation monitor on the outdoor unit's multi control board while
operating the indoor unit in question in the FAN mode and the other indoor units in
the cooling mode.
(A)Termistor (TH22)
(A)
LEV
Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is
leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly
lower than the inlet temperature on the remote controller, valve closure failure is
suspected. If the amount of leakage is insignificant, replacement of LEV is unnecessary unless it is causing a problem.
Perform a visual check for disconnected connectors.
Perform a visual check of lead wire color.
Replace the LEV
if the amount of
leakage is great.
Disconnect the
connectors on
the control board
and perform a
continuity test.
HWE1405AGB
- 25 -
[ VIII Troubleshooting ]
2. DC fan motor (fan motor/indoor control board)
1. CAUTION
A high voltage is applied to the connector for connection to the fan motor (CNMF).
Do not unplug the connector CNMF with the unit energized to avoid damage to the indoor control board and fan motor.
2. Troubleshooting
Symptom : The indoor fan cannot turn around.
Check the fuse (FUSE) on indoor
controller board.
Did the fuse blow?
No
Wiring contact check
Contact of fan motor connector (CNMF)
Ye s
Check the drain pump (DP)
Is the resistance between
terminals normal?
No
Replace drain pump (DP).
Wiring recovery
Is there no contact failure?
Ye s
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
TEST POINT
1 :VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC310~340V
No
board.
TEST POINT2 :VCC (between 5 (+) and 4 (-) of the fan connector): V
Is the voltage normal?
No
Replace indoor
controller board.
Check the operation.
NG
Replace the fan motor.
OK
END
Measure the resistance of the fan motor.
Ye s
Is the resistance of the fan motor
normal?(Refer to below table)
Does the fan motor rotate smoothly?
Turn OFF the power supply and
connect the connector CNMF.
Turn ON the power supply and
measure the voltage of connector
CNMF while rotaing the motor by
the hand.
Ye s
Ye s
CC
DC15V
No
No
Ye s
Replace indoor controller board (I.B).
Replace fan motor (MF).
PVFY-
P12,18,24,30,36
NAMU-E
Measuring pointsResistance
pin 1 - pin 3
O.L.
pin 4 - pin 350kΩ
pin 5 - pin 3150kΩ
pin 6 - pin 3
*To measure the resistance, connect
the negative (-) end of the tester to pin 3.
HWE1405AGB
O.L.
Does the voltage between pin 6 and pin 3
of connector CNMF repeat 0V and 5V?
Ye s
Check the operation of fan.
NG
OK
Replace indoor controller board.
PVFY-
P48,54
NAMU-E
1MΩ
47kΩ
143kΩ
O.L.
- 26 -
END
No
Replace the fan motor.
Check the operation of fan.
Replace indoor controller board.
Ye s
NG
OK
END
[ VIII Troubleshooting ]
3. Address switch setting
Make sure that power to the unit is turned off.
(A)
(B)
ON
OFF
(A)Indoor unit control board
(B)Factory setting (all models)
1. When using an ME remote controller, set the address with the rotary switches (SW11, SW12).
Address setting is not required when the unit remote controller is used.
On-site address setting is required for the indoor units to run.
2. Address settings vary in different systems.
Refer to the section on address setting in the outdoor unit installation manual.
3. Address is set with a combination of SW12 (10's digit) and SW11 (1's digit).
To set the address to "3," set SW12 to "0" and SW11 to "3."
To set the address to "25," set SW 12 to "2" and SW 11 to "5."
*1. While the heater is on, the fan will operate at high speed regardless of the fan setting on the remote controller.
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
HWE1405AGB
- 29 -
[ VIII Troubleshooting ]
2. Capacity code setting
(1) SW2
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
The switches are set to correspond to the unit capacity.
PVFY-P12NAMU-E
PVFY-P18NAMU-EPVFY-P24NAMU-E
PVFY-P30NAMU-E
PVFY-P36NAMU-EPVFY-P48NAMU-EPVFY-P54NAMU-E
3. Model setting
(1) SW4
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
Note:
Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller
off). There is no need to power cycle the unit.
4. Power voltage setting
(1) SW5
1) Indoor control board
Dipswitch settings must be operated with the main power turned OFF.
Factory settingSet SW5 to 240V side when the power supply is 230 volts.
220V
(208V)
240V
(230V)
When the power supply is 208 volts, set SW5 to 220V side.
HWE1405AGB
- 30 -
[ VIII Troubleshooting ]
1
2
3
SWA SWC
1
2
5. External static pressure
(1) SWA, SWC
1) Indoor control board
All modelsFactory
1
Vertical, Horizontal Right, Horizontal left
75Pa(0.30in.WG)
3
2
1
SWA
2
Down flow
75Pa(0.30in.WG)
3
2
1
SWA
*PVFY-P36 in Downflow External static pressure: 150Pa (0.60in.WG)
PVFY-P54 in Downflow External static pressure: 175Pa (0.70in.WG)
2
1
SWC
2
1
SWC
125Pa(0.50in.WG)
2
3
2
1
1
SWASWC
125Pa(0.50in.WG)
2
3
2
1
1
SWASWC
200Pa(0.80in.WG)
2
3
2
1
1
SWASWC
200Pa*(0.80in.WG)
2
3
2
1
1
SWASWC
setting
Note:
Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation
status (RUN/STOP) or the remote controller status (ON/OFF).
6. 1s and 10ths digits
(1) SW11, SW12 (Rotary switch)
The use of a network remote controller (PAR-F27MEA) requires address setting.
1) Indoor control board
Address settings must be made while the unit is stopped.
Factory setting
7. Connection No. setting
(1) SW14 (Rotary switch)
This switch is used when the unit connected to an R2 series of outdoor unit.
1) Indoor control board
Factory setting
Note:
Changes to the dipswitches SW11, SW12, SW14, and SW15 must be made while the unit is stopped and the remote controller
is OFF.
HWE1405AGB
- 31 -
[ IX Disassembly Procedure ]
IX Disassembly Procedure
[1] Disassembly Procedure
1. Control box
Exercise caution when removing heavy parts.
1. Remove the Electric panel (2 screws)
.
2. Remove the Control box cover (1 screw).
Fig.1
Fig.2
HWE1405AGB
- 32 -
[ IX Disassembly Procedure ]
2. Thermistor (Return Air)
Exercise caution when removing heavy parts.
1. Remove the Filter panel (2 thumbscrews).
2. Remove the Blower panel (2 screws).
3. Remove the cover over the Return Air thermistor box
and unplug the thermistor.
4. Pull out the thermistor holder and thermistor inside the
box.
1. Remove the Electrical, Blower and Filter panel indicated
in sections 1 and 2.
2. Remove the Coil panel by removing all of the screws securing it to the (3) smaller panels for refrigerant and drain
lines.
Fig.5
3. Slide the smaller panels in the directions indicated and
remove.
4. Remove the (1 or 2) brackets that secure the coil, unplug
the thermistors and LEV from the control board and
route the wires out of the control box area and into the
coil section. Next, slide the coil from the frame.
Fig.6
Fig.7
HWE1405AGB
Fig.8
- 34 -
[ IX Disassembly Procedure ]
5. Remove the plate covering the coil
assembly to access the thermistors.
6. Remove lower and side drain pan.
Fig.9
HWE1405AGB
Fig.10
- 35 -
[ IX Disassembly Procedure ]
4. Blower/Fan Assembly
Exercise caution when removing heavy parts.
1. Remove the Blower and Filter panel (along with filter if
installed) indicated in section 2.
2. Remove the (1 or 2) brackets that secure the coil assembly. (Fig.11)
3. Remove the door that covers the small enclosure attached to the fan assembly (Fig.12). Unplug the motor
and route the wire harness out of the enclosure.
4. Remove the (2) screws that secure the fan assembly
and slide out.
Fig.11
Fig.12
HWE1405AGB
- 36 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.