Mitsubishi Electronics PUZ-HA30NHA, PUZ-HA36NHA User Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL DATA BOOK
November 2008
No. OCS12
REVISED EDITION-A
<Indoor unit> [Model names]
<Outdoor unit> [Model name]
HYPER HEATING INVERTER
PLA-A·BA PKA-A·GA PKA-A·GAL PKA-A·FA
Revision :
• PUZ-HA30NHA is added in REVISED EDITION-A.
• Some descriptions have been modifi ed.
• Please void OCS12.
PKA-A·FAL
PUZ-HA30NHA PUZ-HA36NHA
CONTENTS
1. REFERENCE SERVICE MANUAL ·············································2
2. SPECIFICATIONS ······································································3
3. OUTLINES AND DIMENSIONS ················································· 4
4. WIRING DIAGRAM ·····································································9
5. REFRIGERANT SYSTEM DIAGRAM ······································13
6. PERFORMANCE CURVES ······················································14
8. AIR FLOW DATA ······································································18
9. NOISE CRITERION CURVES ··················································24
10. OPTIONAL PARTS ····································································27
1
REFERENCE SERVICE MANUAL
For information on service, please refer to the service manual as follows.
1-1. INDOOR UNIT
Model name Service Ref.
PLA-A18/30/36BA PLA-A18BA PLA-A18BA
PLA-A30BA
1
PLA-A36BA PLA-A36BA
1
1
Service Manual No.
OCH420 OCB420
PKA-A18GA PKA-A18GA/GA PKA-A18GAL PKA-A18GAL/GAL
PKA-A30/36FA PKA-A36FA/FA1/FA
1
/GA
2
1
/GAL
2
PKA-A30/36FAL PKA-A36FAL/FAL1/FAL
1-2. OUTDOOR UNIT
Model name Service Ref.
PUZ-HA30/36NHA PUZ-HA30/36NHA
2
PKA-A30FA
2
PKA-A30FAL
OC369
2
2
Service Manual No.
OCH426 OCB426
2
2
SPECIFICATIONS
Model name Indoor unit
Cooling Max. Capacity BTU/h
Heating Max. Capacity BTU/h
Heating at 17°F(-8.3°C) Capacity BTU/h
Heating at 5°F(-15°C) Capacity BTU/h
Power supply Phase, Cycle, Voltage
Voltage Indoor - Outdoor S1 - S2
Indoor unit MCA A
Remote Controller Outdoor unit MCA A
Refrigerant Type
Refrigerant pipe size Gas side O.D. mm[inch]
Refrigerant pipe length Height difference
Refrigerant Piping Not supplied Connection Method
Outdoor unit
Rated Capacity BTU/h Min. Capacity BTU/h Total Input W EER BTU/h/W SEER BTU/h/W Moisture Removal Pints/h 6.8 7.1
*1 SHF
Rated Capacity BTU/h Min. Capacity BTU/h Total Input W COP W/W
*1 HSPF(4/5) BTU/h/W
Total Input W
*2 COP W/W
Total Input W
*3 COP W/W
Breaker size A
Indoor - Outdoor S2 - S3 Indoor - Remote Controller
MOCP A Fan Motor F.L.A. 1.00 0.52 Fan Motor Output W Airflow (Lo-M2-M1-Hi) DRY CMM Airflow (Lo-M2-M1-Hi) WET CMM Airflow (Lo-M2-M1-Hi) DRY CFM Airflow (Lo-M2-M1-Hi) WET CFM External pressure Pa Sound level (Lo-M2-M1-Hi) dB(A) External finish (Grille) Dimension Unit (Grille) W : mm[inch]
Weight Unit(Grille) kg Weight Unit(Grille) lbs Field drain pipe size mm[inch]
MOCP A Fan Motor F.L.A. Fan Motor Output W Compressor Type
Air flow CMM[CFM] Refrigerant Control Defrost Method Reverse Cycle Sound level at cooling dB(A) Sound level at heating dB(A) External finish Ivory Munsell 3Y 7.8/1.1 Dimension W : mm[inch]
Weight kg[lbs]
Charge kg[lbs, oz] Oil L[oz]
Liquid side O.D. mm[inch]
Length
D : mm[inch] H : mm[inch]
R.L.A. L.R.A.
D : mm[inch] H : mm[inch]
PLA-A30BA
PUZ-HA30NHA
30,000 30,000 18,000
2,450
12.2
15.6
7.2
0.73 34,000 32,000 18,000
3,440
2.73
8.8 / 7.0 32,000
5,720
1.64
32,000
6,630
1.41 1.90 1phase, 60Hz, 208/230V 1phase, 60Hz, 208/230V
AC208/230V
1
0.51 50
14-16-18-21
13-15-17-20 490-570-640-740 460-530-600-710 700-890 (Lo-Hi)
White Munsell 6.4Y 8.9/0.4 White Munsell 3.4Y 7.7/0.8
840(950) [33-1/16(37-3/8)] 1680 [66-1/8]1400 [55-1/8] 840(950) [33-1/16(37-3/8)] 235 [9-1/4]
258(35) [10-3/16(1-3/8)]
23(6) 28
O.D. 32 [1-1/4] I.D. 20 [13/16]
Attached in Grille Attached in Indoor unit
0.4 + 0.4
100[3,530]
Electronic Expansion Valve
950 [37-3/8]
330 + 30 [13 + 1-3/16]
1,350 [53-1/8]
121 [267]
5.5 [12 lbs]
1.4(FV50S) [45]
15.88 [5/8]
9.52 [3/8] Max.30m [Max.100ft] Max.75m [Max.245ft]
PLA-A36BA PKA-A36FA(L)
PUZ-HA36NHA PUZ-HA36NHA
36,000 34,200 36,000 34,200 18,000 18,000
3,120 2,950
11.5 11.6
16.0 16.0
0.79 0.77 40,000 40,000 38,000 38,000 18,000 18,000
3,230 3,100
3.45 3.59
9.4 / 7.3 9.4 / 7.3 38,000 38,000
5,300 5,300
2.10 2.10
38,000 38,000
5,860 5,860
1.90
PKA-A30FA(L)
PUZ-HA30NHA
30,000 30,000 18,000
2,730
11.0
14.5
7.9
0.70 34,000 32,000 18,000
3,460
2.71
8.9 / 7.2 32,000
5,600
1.67
32,000
6,370
1.47
30 30
DC24V DC24V DC12V DC12V : Wired type
15 15
00
55(13) 62
28 40
60 + 60
18
27.5
21
0.43
120 70 20-23-26-30 22-28 (Lo-Hi) 19-22-25-29 20-25 (Lo-Hi)
710-810-920-1060 780-990 (Lo-Hi) 670-770-880-1030
32-34-37-4028-30-32-34 46-49 (Lo-Hi)
298(35) [11-3/4(1-3/8)]
25(6)
45 15-20 (Lo-Hi) 14-18 (Lo-Hi)
530-705 (Lo-Hi) 480-635 (Lo-Hi)
39-45 (Lo-Hi)
24
53
ANB33FJCMTANB33FJEMT ANB33FJEMT
Electronic Expansion Valve
52 53
Ivory Munsell 3Y 7.8/1.1
330 + 30 [13 + 1-3/16]
R410A
Max.30m [Max.100ft] Max.75m [Max.245ft]
Flared
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F) *2.Rating conditions (heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F) *3.Rating conditions (heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -15°C(5°F), W.B. -15°C(5°F)
Operating range
Cooling
Heating
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
D.B. 32°C(90°F), W.B. 23°C(73°F) D.B. 19°C(66°F), W.B. 15°C(59°F)
D.B. 28°C(83°F) D.B. 17°C(63°F)
Outdoor intake air temperature
D.B. 46°C(115°F)
D.B. -18°C(0°F)*
D.B. 21.1°C(70°F), W.B. 15°C(59°F)
D.B. -25°C(-13°F), W.B. -25°C(-13°F)
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5°C(23°F)DB.)
AC208/230V
340 [13-3/8]
28 40
0.4 + 0.4 60 + 60
ANB33FJCMT
18
27.5
100[3,530]
Reverse Cycle
52 53
950 [37-3/8]
1,350 [53-1/8]
121 [267]
R410A
5.5 [12 lbs]
1.4(FV50S) [45]
15.88 [5/8]
9.52 [3/8]
Not supplied
Flared
3
3
OUTLINES AND DIMENSIONS
INDOOR UNIT Unit : inch (mm) PLA-A18BA PLA-A30BA PLA-A36BA
25/32 to 1-25/32(20~45)
Fresh air intake hole
33-1/16(840)
Suspension bolt M10 or W3/8
6-11/16
+
Suspension bolt lower edge
Air intake grille
(160)
6-5/16
Branch duct hole
(90)
(150)
3-17/32
5-29/32
D
C
1
2
(170)
5-1/2
(140)
+
(50~70)
(500)
(950)
37-3/8
19-11/16
Air outlet hole
(83)
3-17/64
(36)
1-27/64
Ceiling
Grille
Entire periphery
33-27/32 to 35-13/16(860~910)
Suspension bolt pitch
6-5/16
(160)
For MA-Remote controller terminal block
Indoor unit/Outdoor unit connecting terminal block
7-3/8
(187.5)
2-3/8
1-15/16~2-3/4
M
Corner pocket
(60)
33-1/16
(284)
M
Indoor unit
Min.19-11/16(500)
Ceiling hole
31-7/8(810)
For wiring replacement kit terminal block
(840)
(377)
14-27/3211-3/16
23-1/2
(597)
Air intake hole
(500)
19-11/16
Air outlet hole
(950)
37-3/8
Min.94-1/2(2400) from floor
Floor
M
6-5/16
(160)
25/32 to 1-25/32(20~45)
Drain pipe connected to VP-25
Ceiling
Grille
M
1-27/64
3-17/64
(83)
25/32 to
(7.5)
(5/16)(5/16)
+35
-5
(605 )
(620)
-3/16
+1-3/8
24-13/32
(160)
23-13/16
(24)
Suspension bolt pitch
(156)
6-9/64
7-15/32
+
Auto vane
(Air outlet)
Air intake hole
(7.5)
(190)
+3/16
11/ 16
33-27/32 to 35-13/1625/32
A
+5
0
6-5/16
15/16
(105)
4-1/8
++
Drain hole Drain pump clean hole and Drain emergency drainage hole
(597)
23-1/2
Note1. As for drain pipe, please use VP-25(O.D. :32 PVC TUBE). Drain pump is included. Max. lifting height is 70-7/18(850mm) from the ceiling.
Vane motor
(36)
2. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
3. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/power wires connection.
4. The height of the indoor unit is able to be adjusted with the grille attached.
5. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Add 5-5/16(135mm) to the dimensions + marked on the figure.
2) The optional high efficiency filter becomes optional multi-functional casement and concomitant use.
6. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.)
7. As for necessary installation/service space, please refer to the left figure.
Models
PLA-A12BA PLA-A18BA
PLA-A24BA PLA-A30BA
PLA-A36BA PLA-A42BA
~45)
1-25/32
(20
(860~910)
Branch duct
Ceiling hole
hole
to 1-25/32
(20~45)
Connected the attached flexible pipe or socket.
Keep 25/64(10)to 19/32(15) between unit ceiling and ceiling slab.
B
+
0
(35)
(17 )
1-3/8
In case of standard grille
Refrigerant pipe
: 6.35mm
···· Flared connection
····1/4
Refrigerant pipe
····
: 9.52mm
Flared connection
····3/8
Detail connecting of branch duct(Both aspects)
3-15/16
3-17/32
(90)
:
6-7/8
(
:
175)
Burring hole pitch
(100)
13-25/32
(350)
3-15/16
3-17/32
:
Cut out hole
(100)
(90)
Cut out hole
5-29/32
3-15/16
14-:1/8
Burring hole
(
:
150)
(100)
(
(130)
5-1/8
14-:2.8
Detail drawing of fresh air intake hole
Burring hole
)(
3-:1/8(3-:2.8)
6-7/32
+
( 158)
+
In case of wireless remote controller
Emergency operation switch<Cooling>
Receiver
Operation lamp
1
2
Refrigerant pipe
····
: 12.7mm
Flared connection
····1/2
Refrigerant pipe
: 15.88mm
···· Flared connection
····5/8
120°
9-1/2 (241)
11-1/16
(281)
Burring hole pitch
:
4-29/32(:125)
Cut out hole
120°
:
3-15/16(:100)
Ceiling
Emergency operation switch<Heating>
DEFROST/STAND BY lamp
10-3/16
3-5/32
(80)
(258)
3-11/32
11-3/4
(85)
(298)
DCBA
2-29/32
(74)
3-1/32
(77)
(155)
6-3/32
++
)
(167)
6-9/16
44
PKA-A18GA PKA-A18GAL Unit : inch (mm)
Left side
Knockout hole for left piping Refrigerant pipe.Drain pipe. Wiring hole.
Front view
28-5/32(715) Air intake 8-27/32(225)
13-3/8(340)
Air intake
3-5/32(80)
11-1/32(280) 9-3/16(233)
Air intake
Right side
Less than 19/32(15)
9-21/32(245)
13/16(21)
2-3/8(60)
2-3/4(70)
1-31/32(50)
1-3/8(35)
Drain hose
Service space required around indoor unit
Field drain pipe size 13/ 16 (20=) I.D
13-3/8(340)
2-3/32(53)
Lower side
12-Louvers(manual)
3-1/8(79)
Front view (top open the grille)
Liquid pipe
Gas pipe
Filter grip
39(990)
27-3/4(705) Air outlet 9-1/4(235)
27-9/16(700)
(Flexible hose total length 31-1/2(800))
Right side
Auto vane
6-5/16(160) 1-9/16(40)
2-3/4(70) 1-3/8(35)
3-1/8(80)
22-7/8(581)
17-11/16(449)
7-15/32(190)
15-9/16(395)15-3/4(400)
MODEL 18
Liquid pipe
Gas pipe
3/16(5)
Air intake
7-25/32(198)
2-3/8(60)
9-1/4(235)
Knockout hole for under piping Refrigerant piping.Drain pipe. Wiring hole
2-3/8(60)
Service panel (Power supply access)
Wiring entrance holes
1-11/32(34)
1(25)
1-5/16(33) 2-1/8(54)
3-3/8(86)
6-1/32(153)
(Right side piping installation)
1-7/32(31) 11-1/32(280)
1/4
1/2
9-21/32(245)
13/16(21)
Knockout hole for right piping Refrigerant pipe.Drain pipe. Wiring hole
2-3/4(70)
1-31/32(50) or more
Details of installation plate
5-29/32(150) or more
14-:9/16(:14)holes for bolts
49-:3/16(:5)holes for tapping screw
Left-rear piping hole
Knockout hole for left-rear piping
1-13/16(30) or more
7-3/32(180) or more
(Necessary clearance for Unit installation)
19-1/2(495)
11-13/16(300)
14-3/16(360)
15-15/16(405)
R2-1/16(R52.5)
16-17/32(420)
Less than 5-1/8(130)
5-5/16(135)
7-15/32(190)
9-21/32(245)
R2-1/16(R52.5)
Knockout hole for right-rear piping
9-1/16(230)
8-9/32(210)
Installation plate balance point hole
Unit center
1-1/4(32)
25/32(20)
2-15/16(75)
0
1-3/8(35)
3-3/4(95)
R2-1/16(R52.5)
0
55
Through holeSleeve *1
ø2-15/16(ø75)
ø2-15/16~ø3-5/32
(ø75~ø80)
*1 Sleeves are available on the market. *2 This size shows the lower end of through hole.
8-1/16(205)
10-1/4(260)
5-29/32(150)
R2-1/16(R52.5)
7-15/32(190)
6-11/16(170)
12-19/32(320)
19-1/2(495)
13-19/32(345)
Right-rear piping hole
16-23/32(425)
0
0
1-3/8(35) 2-5/32(55) 3-5/32(80)
5-1/8(130)
7-15/32(190) 9-1/16(230)
10-23/32(272) 12-7/32(310)
12-11/16(322)+1
PKA-A30FA PKA-A30FAL Unit : inch (mm)
Top side
9-1/4(235)
1-25/32(45)
Front view
Left side
A
13-3/8(340)
Knockout hole for left piping
31/32(25)
Drain hose for left-hand side piping
Lower side
21-23/32(552) Air outlet
Under panel(Removable at left-hand side piping)
Service space required around indoor unit
1-31/32(50) or more
9-27/32(250) or more
9-1/4(235)
1-25/32(45)
42-29/32(1090) Air intake
Auto vanes
Knockout hole for under-piping Refrigerant pipe /Drain pipe
Air intake
Air outlet
9-1/4(235)
1-25/32(45)
55-1/8(1400)
Field drain pipe size
Drain hose
13/16 (20mm) I.D
Wiring entrance holes
43-11/16(1110) Drain hose
44-3/32(1120)
21-23/32(552) Air outlet
1-3/16(30) or more
Less than 9-27/32(250)
9-1/4(235)
Louvers(Manual)
9-7/16(240)
1/2(13) 2-15/32(62.5)
Terminal blockTerminal block
2
1-5/16(34)
1-7/16(36)
1-21/32(42)
15/16(24)
2-5/32(55)
4-23/32(120)
7-7/32(183)
B
Right side
9-1/4(235)
C
7-3/4(197)
Knockout hole for right piping
Less than 19/32(15)
Bolt
2-9/32(58)
Drain hose
1
MODEL
1
Liquid pipe
2
Gas pipe
Sleeve
ø3-17/32 (ø90)
*1
4-7/32(107)
4-3/8(111)
24/30
3/8
5/8
Through hole ø3-17/32~ø3-15/16
(ø90~ø100)
*1 Sleeves are available on the market.
Knockout hole for wiring
AB C
1-3/16(30)
1-17/32(39)
3-15/16(100)
5/32(4)
1-9/16(39)
1-15/32(37)
2-29/32(74)
3-27/32(98)
2-9/16(65)
1-15/32(37)
1-1/4(32)
9-27/32(250) or more
1-3/16(30)
1-15/32(37)
2-29/32(74)
Details of installation plate
Drainage range on
3-15/16(100)
1-17/32(39)
left hand side
Wall fixture
5/32(4)
66-ø1/4(ø6) holes for tapping screws
32-ø15/32(ø12) holes for bolts
Unit center
38-31/32(990)
13/32*3-19/32=(35-13/16) (10*91=(910))
35-7/16(900)
23/32(18)
23/32(18)
8-27/32(225)
9-7/16(240)
7-3/32(180)
12-ø1/4(ø6) holes for tapping screws
6
17-29/32(455)
3-19/32(91)
11-1/32(280) 12-3/8(314)
24-1/32(610)
Range for left rear piping hole
9-21/32(245)
11-7/32(285)
3/4(19)
Drainage range on right-hand side
13/32(10)
1-3/16(30)
7-1/4(184)
1-3/16(30)
1-3/16(30)
3-17/32(90)
1-5/32(29)
11-1/32(280)
3-1/8(80)
2-3/8(60)
Rear piping hole
PKA-A36FA PKA-A36FAL Unit : inch (mm)
Top side
2-15/32(62.5)
9-1/4(235)
1-25/32(45)
Left side
A
Knockout hole for left piping
Drain hose for left-hand side piping
Service space required around indoor unit
1-31/32(50) or more
Knockout hole for wiring
ACB
1-3/16(30)
3-15/16(100)
5/32(4) 1-17/32(39)
1-15/32(37)
2-29/32(74)
Front view
13-3/8(340)
31/32(25)
Lower side
9-27/32(250) or more
1-17/32(39)
3-27/32(98)
9-1/4(235)
1-25/32(45)
53-15/16(1370) Air intake
Drain hose
27-5/16(694) Air outlet
Auto vanes
Air intake
9-27/32(250) or more
1-3/16(30)
2-9/16(65)
1-15/32(37)
1-15/32(37)
1-1/4(32)
9-1/4(235)
1-25/32(45)
Air outlet
9-1/4(235)
1-25/32(45)
66-1/8(1680)
Field drain pipe size 13/16 (20mm) I.D
Wiring entrance holes
43-11/16(1110) Drain hose
55-1/8(1400)
27-5/16(694) Air outlet
Louvers(Manual)
Under panel(Removable at left-hand side piping)
Knockout hole for under-piping Refrigerant pipe /Drain pipe
1-3/16(30) or more
Less than 5-29/32(150)
Drainage range on left hand side
3-15/16(100)
84-ø1/4(ø6) holes for tapping screws
2-29/32(74)
5/32(4)
1-17/32(39)
9-1/4(235)
Knockout hole for right piping
1/2(13)
Right side
9-1/4(235)
C
7-3/4(197)
Terminal block
15/16(24) 2-5/32(55) 4-23/32(120) 7-7/32(183)
9-7/16(240)
2
2-9/32(58)
1-5/16(34)
1-7/16(36)
1-21/32(42)
B
1
Less than 9/16(15)
Bolt
4-1/32(102)
4-3/8(111)
MODEL 36
Liquid pipe
Gas pipe
Sleeve *1
ø3-17/32 (ø90)
3/8
5/8
Through hole
ø3-17/32~ø3-15/16 (ø90~ø100)
*1 Sleeves are available on the market.
Drainage range on
Unit out line
Wall fixture
23/32(18) 23/32(18)
Unit center
50(1270)
1/2*3-19/32=(46-9/16) (13*91=(1183))
right-hand side
23-7/16(595)
35-7/16(900)
9-21/32(245)
11-7/32(285)
3/4(19)
3-19/32(91)
13/32(10)
1-3/16(30)1-3/16(30)
1-5/32(29)
3-5/32(80)
11-1/32(280)
11-5/8(295) 8-27/32(225)
41-ø15/32(ø12) holes for bolts
7
9-7/16(240) 7-3/32(180) 11-1/32(280)
12-ø1/4(ø6) holes for tapping screws
12-3/8(314)
29-17/32(750)
Range for left rear piping hole
1-3/16(30) 7-1/4(184)
3-9/16(90)
Rear piping hole
2-3/8(60)
PUZ-HA30NHA PUZ-HA36NHA Unit : mm<inch>
19<3/4>
2-U Shaped notched hole
(Foundation Bolt M10<W3/8>)
175<6-7/8>
600<23-5/8>
Rear Air Intake
175<6-7/8>
417<16-13/32>
370<14-9/16>
56<2-7/32>
45<1-25/32>
330<13>30<1-3/16>
28<1-3/32>
53<2-3/32>
42<1-21/32>66<2-5/8>
2-12%36 Oval hole
(Foundation Bolt M10<W3/8>)
Air Discharge
Side Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
FOUNDATION
<1-3/16>
<Foundation bolt height>
Please secure the unit firmly
with 4 foundation (M10<W3/8>)
bolts. (Bolts and washers must
3 FOUNDATION BOLTS
be purchased locally.)
<5-29/32> 150mm Min.
Dimensions of space needed
for service access are
shown in the below diagram.
2 SERVICE SPACE
30mm Min.
<19-11/16> 500mm Min.
Min.
10mm<3/8>
Min.
500mm
<19-11/16>
Service space
Terminal Block
Left···Power supply wiring
950<37-13/32>
Earth terminal
322<12-11/16>
Handle
Side Air Intake
Rear Air Intake
Right····Indoor/Outdoor wiring
Service panel
Handle
Handle
635<25>
Handle
Handle
1076<42-3/8>
1350<53-5/32>
1
* 1 447<17-19/32>
2
Air intake
Front piping cover
* 1 443<17-7/16>
23<29/32>
371<14-19/32>
Rear piping cover
71<2-13/16>
71<2-13/16>
Bottom piping hole
(Knockout)
219<8-5/8>
1/2 Conduit attachment
When installing the conduit.
Set the attachment to the
inner side of each panel.
2-:22.2<7/8>
Conduit hole
(2-:27<1-1/16>Knockout)
Rear trunking hole
(Knockout)
40<1-9/16>
55<2-3/16>
63<2-1/2>
45<1-25/32>
Right trunking hole
(Knockout)
Conduit hole
(2-:27<1-1/16>Knockout)
40<1-9/16>
75
<2-31/32>
63<2-1/2>
<2-1/2>
63
55<2-3/16>
45<1-25/32>
92<3-5/8>
73<2-7/8>
Right piping hole
(Knockout)
40<1-9/16>
:92
<3-5/8>
73<2-7/8>
92
/8>
:
<3-5
27<1-1/16>
Drain hole
5-:33<1-5/16>
145
<5-23/32>
145
<5-23/32>
145
<5-23/32>
220
<8-21/32>
81<3-3/16>
30<1-3/16>
31<1-7/32>
74<2-19/32>
Rear piping hole
(Knockout)
92<3-5/8>
65<2-9/16>
92<3-5/8>
55<2-3/16>
19<3/4>
27<1-1/16>
23<29/32>
73<2-7/8>
23<29/32>
23<29/32>
27<1-1/16>
Min. 10mm
<3/8>
FREE
The diagram below shows a
basic example.
Explantion of particular details are
1 FREE SPACE (Around the unit)
given in the installation manuals etc.
<3/8>
Min. 10mm
Min. 150mm
<5-29/32>
<39-3/8>
Min. 1000mm
Example of Notes
····Refrigerant GAS pipe connction (FLARE):15.88<5/8>
····Refrigerant LIQUID pipe connection (FLARE): 9.52<3/8>
*1 ····Indication of STOP VALVE connection location.
8
/8>
92
:
(Knockout)
<3-5
65<2-9/16>
92<3-5/8>
Front piping hole
(Knockout)
40<1-9/16>
Conduit hole
(2-:27<1-1/16>Knockout)
Piping Knockout Hole Details
Front trunking hole
4
WIRING DIAGRAM
PLA-A18BA PLA-A30BA PLA-A36BA
[LEGEND]
SYMBOL SYMBOLNAME NAME
I.B INDOOR CONTROLLER BOARD
CN2L CN24 CONNECTOR<BACK-UP HEATING> CN30 CONNECTOR<LLC> CN32 CN41 CN51 DSA FUSE LED1 LED2 LED3 SW1 SW2 SWE X1
ZNR01, 02 DP FS
I.B
13
CN3G (BLK)
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) SURGE ABSORBER FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) +See table 1. SWITCH (CAPACITY CODE) +See table 2. CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) VAR IST OR
DRAIN-UP MACHINE DRAIN FLOAT SWITCH
Refer to tables 1 and 2.
VAN E
CNV
(WHT)
1011121314151617181920
123456789
LED3 LED2 LED1
I-SEE
SENSOR
CN4Y (WHT)
4
I-SEE
BZ
SENSOR
LED2
I-SEE SENSOR CORNER PANEL
LED1
RU
(OPTIONAL PART)
W.B
GRILLE
5555
MMMM
MVMVMVMV
WIRELESS
CN90
(WHT)
9
CNB
SW1
SW2
SENSOR MOTOR
5
M
MT
SW2SW1
I-SEE
CN6Y
(RED)
21 TB6
R.B
J42J41
Pair No.
CN2L
21
CNAC (WHT)
36141911
MF MV TB4 TB5, TB6
TH1
TH2
TH5
OPTION PART
W.B
TB5
TRANSMISSION WIRES DC12V
CN32
(WHT)
1
CN51
(WHT)
CN24
51
CN41
(WHT)
41
SWE
ON OFF
FLOAT SW
LIQUID/PIPE
CN4F
(WHT)
FS
FAN MOTOR VANE MOTOR TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (32˚F/15kΩ, 77˚F/5.4kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (32˚F/15kΩ, 77˚F/5.4kΩ DETECT) COND. / EVA. TEMP. THERMISTOR (32˚F/15kΩ, 77˚F/5.4kΩ DETECT)
PCB FOR WIRELESS REMOTE CONTROLLER
BZ
BUZZER
LED1
LED (OPERATION INDICATION: GREEN)
LED2
LED (PREPARATION FOR HEATING: ORANGE) RECEIVING UNIT
RU SW1
EMERGENCY OPERATION (HEAT/DOWN)
SW2
EMERGENCY OPERATION (COOL/UP)
2 1
3
(YLW)
2
CN44
(WHT)
REMOCON
t˚t˚
TH5TH2
INDOOR/OUTDOOR
COMMUNICATION
112
CN22
(BLU)
INTAKE
CN20 (RED)
t˚
TH1
13
CN3C
(BLU)
DC280V
RECTIFICATION
FAN CN30 (GRN)
13
CNMF
(WHT
71121414 4 31
MS
MF
3~
+Be sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in fan motor.)
OUTDOOR
CN01
(BLK)
DSA
ZNR02
)
135
U
M
1~ DP
U
ZNR01
X1
D.U.M
CNP
(BLU)
FUSE
YLW
ORN
ORN BRN
YLW ORN
TB4
+1
S1
TO
S2
OUTDOOR UNIT
S3
<Table 1>SW1(MODEL SELECTION)
SW1
Service
12345
ON OFF
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal block.
<Table 2>SW2(CAPACITY CODE)
MODELS
PLA-A12BA
PLA-A18BA
PLA-A24BA
Service
12345
12345
12345
ON OFF
ON OFF
ON OFF
SW2
MODELS
PLA-A30BA
PLA-A36BA
PLA-A42BA
Service
12345
12345
12345
ON OFF
ON OFF
ON OFF
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
+1. Use copper supply wires.
[Self-diagnosis]
1. For details on how to operate self-diagnosis with the wireless remote control, refer to the technical manuals etc.
2. For the wired remote control: When you quickly press twice the CHECK switch on the remote control, the unit begins self-diagnosis, and Check Codes generated in the past appear on the display.
9
PKA-A18GA PKA-A18GAL
SYMBOL NAME P.B I.B
P. B
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD FUSE FUSE (6.3A/250V) ZNR VARISTOR CN2L CONNECTOR <LOSSNAY> CN24 CONNECTOR <BACK-UP HEATING> CN30 CONNECTOR <LLC> CN32 CONNECTOR <REMOTE SWITCH> CN41 CONNECTOR <HA TERMINAL-A> CN51 CONNECTOR <CENTRALLY CONTROL> SW1 SWITCH <MODEL SELECTION> SW2 SWITCH <CAPACITY CODE> SWE
SWITCH <EMERGENCY OPERATION>
X4 RELAY <FAN MOTOR>
FAN CONTROL ELEMENT
BCR LED1 POWER SUPPLY <I.B>
CNSK (RED)
1
3
DC13.1V
CN2S
(WHT)
1
2
+
See Table 1.
+
See Table 2.
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
SYMBOL NAME
POWER SUPPLY <R.B>
LED2
C MF MV TB4
TB5, TB6
TH1
TH2
TH5
R.B
TRANSMISSION <INDOOR-OUTDOOR>LED3
CAPACITOR <FAN MOTOR> FAN MOTOR VANE MOTOR TERMINAL BLOCK <INDOOR/OUTDOOR CONNECTING LINE> TERMINAL BLOCK <REMOTE CONTROLLER TRANSMISSION LINE > ROOM TEMP.THERMISTOR <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> PIPE TEMP.THERMISTOR/LIQUID <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> COND./EVA.TEMP.THERMISTOR <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> WIRED REMOTE CONTROLLER BOARD
SYMBOL
W.B
Table 2
MODELS
PKA­A12GA(L)
WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT
RU BZ
BUZZER
LED1
LED<RUN INDICATOR >
LED2
LED<HOT ADJUST>
SW1
SWITCH<HEATING ON/OFF>
SW2
SWITCH<COOLING ON/OFF>
NAME
Table 1
SW1
Service board
1 2 3 4 5
SW2
Service board Service board
1 2 3 4 5
ON OFF
MODELS
PKA­A18GA(L)
1 2 3 4 5
ON OFF
ON OFF
YLW ORN
YLW ORN
BRN
TB4
S1
S2
S3
+1
TO OUTDOOR UNIT
MF
M 1~
1
32
C
BLK
WHT
RED
I.B
FAN
(
)
WHT
5
3
1
BCR
SW2 SW1
SWE
ON OFF
Refer to tables 1 and 2 for service PCB.
POWER
X4
CNDK (RED)
WHT
RED
3
11
POWER
CND
(ORN)
ZNR
U
YLW
LED3 LED2 LED1
LIQUID
YLW
INTAKE
CN20
)
(
)
RED
12
2121212
1
CN24
(
t˚ t˚ t˚
ORN
BLK
WHT
1
3
POWER
CN2D
FUSE
(WHT)
CN41
CN51
51
PIPE
CN21
CN29
(
)
(
WHT
BLK
TH2
TH5TH1
BRN
1
2
A-CONTROL
CN3C
(BLU)
(
)
WHT
14
(
)
WHT
REMOCON
CN22
)
(
)
BLU
ORN
3
(
CN2L
RED
12
(
CN32
WHT
13
CN30
(
BLK
6
VANE CN6V (GRN)
)
1
6
1
)
WIRELESS
CN90
(WHT)
)
9
13
1
TRANSMISSION WIRES DC12V
2
TB5
M
MV
99
RU
RECEIVER
BZ
LED1 LED2 SW2 SW1
R.B
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires have polarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring.
3. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
4. This diagram shows the wiring of Indoor and Outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal.
+1. Use copper supply wires.
For A12/18GAL
CNB
W.B
1 2
TB6
For A12/18GA
[Self-diagnosis] Please refer to technical manuals etc.
10
PKA-A30FA PKA-A30FAL PKA-A36FA PKA-A36FAL
[LEGEND]
P.B I.B
P.B
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD FUSE FUSE (6.3A/250V) ZNR VARISTOR CN2L CONNECTOR <LOSSNAY> CN24 CONNECTOR <BACK-UP HEATING> CN30 CONNECTOR <LLC> CN32 CONNECTOR <REMOTE SWITCH> CN41 CONNECTOR <HA TERMINAL-A> CN51 CONNECTOR <CENTRALLY CONTROL> SW1 SWITCH <MODEL SELECTION>+See Table 1. SW2 SWITCH <CAPACITY CODE>+See Table 2. SWE SWITCH <EMERGENCY OPERATION> X4 RELAY <FAN MOTOR>
FAN CONTROL ELEMENT
BCR LED1 POWER SUPPLY <I.B>
CNSK (RED)
1
DC13.1V
3
CN2S
(WHT)
1
2
NAME
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
MF
M
1~
SYMBOL NAME
POWER SUPPLY <R.B>
LED2
TRANSMISSION <INDOOR-OUTDOOR>LED3 C MF MV TB4
TB5,TB6
TH1
TH2
TH5
R.B
CAPACITOR <FAN MOTOR> FAN MOTOR VANE MOTOR TERMINAL BLOCK <INDOOR/OUTDOOR CONNECTING LINE> TERMINAL BLOCK <REMOTE CONTROLLER TRANSMISSION LINE > ROOM TEMP.THERMISTOR <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> PIPE TEMP.THERMISTOR/LIQUID <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> COND./EVA.TEMP.THERMISTOR <32˚F/15kΩ, 77˚F/5.2kΩ DETECT> WIRED REMOTE CONTROLLER BOARD
YLW ORN
YLW ORN
BRN
TB4
S1 S2 S3
SYMBOL
W.B
+
1
TO OUTDOOR UNIT
WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT
RU BZ
BUZZER
LED1
LED <RUN INDICATOR >
LED2
LED <HOT ADJUST>
SW1
SWITCH <HEATING ON/OFF>
SW2
SWITCH <COOLING ON/OFF>
NAME
Table 1
SW1
Service board
1 2 3 4 5
ON OFF
Table 2
SW2
MODELS
PKA­A24FA(L)
MODELS
PKA­A30FA(L)
MODELS
PKA­A36FA(L)
Service board
1 2 3 4 5
Service board
1 2 3 4 5
Service board
1 2 3 4 5
ON OFF
ON OFF
ON OFF
1
32
C
BLK
WHT
RED
I.B
FAN
(
)
WHT
5
3
1
BCR
SW2 SW1
SWE ON OFF
Refer to tables 1 and 2 for service PCB.
POWER
CNDK (RED)
X4
WHT
RED
3
11
POWER
CND
(ORN)
ZNR
U
YLW
LED3 LED2 LED1
INTAKE
CN24
(
YLW
CN20
)
(
)
RED
12
2121212
1
ORN
BLK
1
3
POWER
CN2D (WHT)
FUSE
CN41
CN51
51
LIQUID
PIPE
CN21
CN29
(
)
(
WHT
BLK
TH2
TH5TH1
WHT
1
2
A-CONTROL
CN3C (BLU)
(
)
WHT
14
(
)
WHT
REMOCON
CN22
)
(
BLU
BRN
ORN
3
CN2L
CN32
13
)
(
RED
12
(
WHT
CN30
(
BLK
)
6
VANE
CN6V
(GRN)
6
1 1
)
WIRELESS
CN90
(WHT)
)
9
13
1
TRANSMISSION WIRES DC12V
2
TB5
M
MV
99
RU
RECEIVER
For A24/30/36FAL
CNB
BZ
LED1 LED2 SW2 SW1
W.B
R.B
1 2
TB6
For A24/30/36FA
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal block.
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
4. This diagram shows the wiring of Indoor and Outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. +1. Use copper supply wires. [Self-diagnosis] Please refer to technical manuals etc.
11
PUZ-HA30NHA PUZ-HA36NHA
[LEGEND]
SYMBOL TB1 MC MF1, MF2 21S4 63H 63L Low Pressure Switch SV TH3,TH32,TH33 TH4 TH6 TH7 TH8 LEV-A, LEV-B,LEV-C DCL ACTM CB CY1, CY2
Terminal Block<Power Supply, Indoor/Outdoor > Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch
Solenoid Valve (Bypass Valve)
Thermistor <Outdoor Pipe>
Thermistor <Discharge> Thermistor <Outdoor 2-Phase Pipe> Thermistor <Outdoor> Thermistor <Heatsink> Electronic Expansion Valve
Reactor Active Filter Module Main Smoothing Capacitor Capacitor
C. B.
MF1
MS
3~
MF2
MS
3~
NAME
TH7 TH6 TH3 TH4
TH32
TH33
°
°
t
7
1
1
CNF1
(WHT)
7
CNF2 (WHT)
3
2
CNDC
1
(PNK)
CNS
(WHT)
t
2
121
3
1
TH32
TH33
)
)
(BLK
(YLW
TRANS
F2
F1
31
SYMBOL NAME SYMBOL NAME
P.B.
TABU/V/W TABS/T TABP1/P2/P TABN1/N2/N DS2, DS3 IPM
N.F.
LI/LO NI/NO EI, E2 52C
C.B.
SW1
SW4 SW5
t°t°t°t
°
4121
TH7/6
TH3
TH4
)
(RED)
(WHT
(WHT
CNAC (WHT)
21
43
P. B.
4
1
CNAF
(WHT)
6
7
1
CN2
IPM
(WHT)
7 1 2
(WHT)
1 2
(RED)
1 2
(WHT)
TABN
TABP
CN3
CN5
CN4
TABP2
RED
TABU
RED
UVW
MS 3~
TABV
WHT
BLK
MC
TH8
t
°
2
2
WHT
CB
RED
)
(YLW)
F3
F4
TABW
Power Circuit Board Connection Terminal <U/V/W-Phase> Connection Terminal <L/N-Phase>
Connection Terminal <DC Voltage> Connection Terminal <DC Voltage> Diode Bridge
Power Module
Noise Filter Circuit Board Connection Terminal <L-Phase> Connection Terminal <N-Phase> Connection Terminal <Ground>
52C Relay
Controller Circuit Board Switch <Forced Defrost, Defect History Record Reset, Refrigerant Address>
Switch <Test Operation>
Switch <Function Switch>
LEV-C
63H
63H
31
CN2
(WHT)
CNDC
(PNK)
1
3
LEV-A
63L
MM
LEV-A (WHT)
31
63L
LED2
(RED)
71
2
7
21S4
(GRN)
2
U
TABN1
BLK
61
CN4
(WHT)
21
DS3
DS2
TABN2
WHT
LED1
M
LEV-B
5
6
1
LEV-B (RED)
5
1
LEV-C (BLU)
X52
13 13 13
TABT
BLU
TABS
WHT
TABP1
RED
CNVMNT
(WHT)
6
SV21S4
3
31
CNM
(WHT)
X55
SV2
(BLU)
CNMNT
(WHT)
CN52C
(RED)
SW6 SW7
SW8 SW9 SWP CN31
SS
CNM
CNMNT
CNVMNT
CNDM
LED1, LED2
F1~F4 X51,X52,X55
5
+1+
1
51
SW5SW8SW4 SWP
SW6SW1
141
CN31
221
(WHT)
CNDM
CN51
(WHT)
X51
SS
(WHT)
Switch <Model Select> Switch <Function Setup>
Switch <Function Setup> Switch Switch <Pump Down> Connector <Emergency Operation>
Connector <Connection for Option>
Connector <A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
< Connected for Option (Contact Input)>
LED <Operation Inspection Indicators>
Fuse<T6.3AL250V
Relay
When M-NET adapter is connected
5
SW7
SW9
1
3
1
5
3
1
CNAC2
(RED)
3
1
CNAC1
(WHT)
WHT
LO NO
LI NI
RED
ABS
52C
U
BLU
5
CN5
SW1
(WHT)
1
LED2
LED3
LED4
M-NET SUBSTRATE
2
CN2M (WHT)
1
LED1
LED5
TB7
M-NET
N. F.
1
2
CN52C
(BLK)
E2
1
2
CN5
(RED)
EI
U
BLU
>
SW11
SW12
CND
(WHT)
31
3
BLK
BLK
2
2
M-NET ADAPTER
SYMBOL TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5
Terminal Block <M-net connection> Connector <Transmission> Connector <Power Supply> Connector <M-NET communication> Switch <Status of communication> Switch <Address setting: 1s digit> Switch <Address setting: 10ths digit> LED <Power Supply: DC5V> LED <Connection to Outdoor Unit> LED <Transmission: Sending> LED <Transmission: Recelving> LED <Power Supply: DC12V>
NAME
DCL
RED
BLK
ACTM
+1MODEL SELECT
MODEL SW6
ON
30N
OFF
12345678
ON
36N
OFF
12345678
BLK
4
WHT
L1
L2
61
RED
P
N1 N2
WHT
Io
SW5-6+2
ON OFF
123456
ON OFF
123456
RED
L1 L2 GR S1 S2 S3
POWER SUPPLY ~/N 208/230V 60Hz
2. SW5 -1 to 5: Function Switch
+
YLW
ORN
BLU
GRN
INDOOR UNIT
+
Use copper supply wires.
BRN
CY1
CY2
TB1
12
5
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT PLA-A·BA PKA-A·GA PKA-A·GAL PKA-A·FA PKA-A·FAL
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Thermistor TH5 (Cond./Eva. temperature)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
Distributor with strainer(#50)
Thermistor TH1 (Room temperature)
Thermistor TH2 Pipe temperature (Liquid)
(Flare)
Strainer(#50)
5-2. OUTDOOR UNIT PUZ-HA30NHA PUZ-HA36NHA
Refrigerant GAS pipe connection :15.88 (5/8)
Ball valve
Strainer #50
Electronic expansion valve B
Charge plug (Low pressure)
Strainer #100
Power receiver
Solenoid valve (Four-way valve)
Charge plug (High pressure)
Low pressure switch 63L
Strainer #100
Strainer #100
Muffler
Compressor
Heat exchanger
High pressure switch 63H
Thermistor TH32 (Outdoor pipe)
Thermistor TH4 (Discharge)
Electronic expansion valve A
Injection port
Strainer #100
unit : mm (inch)
Thermistor TH7 (Outdoor)
Thermistor TH6 (Outdoor 2-phase pipe)
Thermistor TH3 (Outdoor pipe)
Distributor
Thermistor TH33 (Outdoor pipe)
Bypass valve
Replace filter
Refrigerant LIQUID pipe connection :9.52 (3/8)
Stop valve (with service port)
Strainer #100
Electronic expansion valve C
13
Heat inter change circuit
Restrictor valve
Strainer #100
Refrigerant flow in cooling Refrigerant flow in heating
6
PERFORMANCE CURVES
FOR THE COMBINATION OF OUTDOOR UNIT PUZ-HA·NHA
Cooling performance curve
1.4
1.2 INDOOR W.B.
CAPACITY (RATIO)TOTAL INPUT (RATIO)
1.0
0.8
1.2
1.0
72°F (22°C)
68°F (20°C)
64°F (18°C)
61°F (16°C)
INDOOR
W.B.
72°F (22°C) 68°F (20°C) 64°F (18°C) 61°F (16°C)
0.8
0.6
0.4
23
(-5°C)
Note : This diagram shows the case where the operation frequency of a compressor is fixed.
30
(-1°C)
50
(10°C)
OUTDOOR D.B.(°F)
70
(21°C)
90
(32°C)
(43°C)
14
110
Rated heating capacity
1.40
1.20
1.00
0.80
0.60
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60
-26 -23 -21 -18 -15 -12 -9 -7 -4 -1 2 4 7 10 13 16
Rated heating performance curve
60˚F (16˚C)
70˚F (21˚C)
80˚F (27˚C)
Indoor intake air dry-bulb temperature (˚F DB)
(˚FWB) (˚CWB)
Outdoor ambient temp.
Heating input
2.00
1.50
1.00
INPUT (RATIO) CAPACITY (RATIO)
0.50
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60
-26 -23 -21 -18 -15 -12 -9 -7 -4 -1 2 4 7 10 13 16
80˚F (27˚C)
70˚F (21˚C)
60˚F (16˚C)
Indoor intake air dry-bulb temperature (˚F DB)
(˚FWB) (˚CWB)
Outdoor ambient temp.
15
7
CORRECTION FACTORS
7-1. COOLING CAPACITY CORRECTION FACTORS
Outdoor unit
PUZ-HA30NHA PUZ-HA36NHA
20m (70ft)10m (33ft)5m (16ft)
1.00 0.985 0.957 0.931 0.908 0.886 0.876 0.865 0.846 0.829
Refrigerant piping length (one way)
30m (100ft) 40m (130ft) 50m (165ft) 55m (180ft) 60m (195ft) 70m (230ft) 80m (260ft)
7-2. HEATING CAPACITY CORRECTION FACTORS
Outdoor unit
PUZ-HA30NHA PUZ-HA36NHA
20m (70ft)10m (33ft)5m (16ft)
1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955
Refrigerant piping length (one way)
30m (100ft) 40m (130ft) 50m (165ft) 55m (180ft) 60m (195ft) 70m (230ft) 80m (260ft)
7-3. CAPACITY CORRECTION
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below. Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m) Corrected pipe length (ft) = actual pipe length (ft) + number of bends x 1 (ft)
100
95
90
85
Capacity ratio [%]
80
75
Note: The permitted pipe length is up to 80m<260ft>.
70
5
<16>10<33>15<50>20<70>25<80>
30
<100>35<115>40<130>45<150>50<165>55<180>60<195>65<215>70<230>75<245>80<260>m<ft>
Heating HA30,36
Cooling HA30,36 model
Cooling
Heating
Corrected pipe length [m]
When gas pipe is one size larger than standard size, capacity can be obtained by referring to capacity curves of standard size.
16
7-4. ADDITION OF REFRIGERANT
• Additional charging is not necessary if the pipe length does not exceed 30 m (100 ft).
• If the pipe length exceeds the specified length above, charge the unit with additional R410A refrigerant according to the permitted pipe lengths in the chart below.
* When the unit is stopped, charge the unit with the additional refrigerant through the liquid stop valve after the pipe
extensions and indoor unit have been vacuumized.
* When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant
directly to the check valve.
* After charging the unit with refrigerant, note the added refrigerant amount on the service label (attached to the unit).
• Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have a serious effect on operation performance.
Model
HA30,36
Max. pipe
length
75 m
245 ft
Max. height
difference
30 m
100 ft
30 m 33 m 37 m 40 m 43 m 46 m 49 m 52 m 55 m 58 m 61 m 64 m 67 m 70 m 73 m 75 m
100 ft 110 ft 120 ft 130 ft 140 ft 150 ft 160 ft 170 ft 180 ft 190 ft 200 ft 210 ft 220 ft 230 ft 240 ft 245 ft
0 oz 6 oz 12 oz 18 oz 24 oz 30 oz 36 oz 42 oz 48 oz 54 oz 60 oz 66 oz 72 oz 78 oz 84 oz 86 oz 0 kg 0.2 kg 0.4 kg 0.5 kg 0.7 kg 0.9 kg 1.0 kg 1.2 kg 1.4 kg 1.5 kg 1.7 kg 1.9 kg 2.0 kg 2.2 kg 2.3 kg 2.4 kg
Additional refrigerant charging amount
17
8
AIR FLOW DATA
8-1. OUTLET AIR SPEED AND COVERAGE RANGE
PLA-A18BA
Airflow Air speed Coverage range
Airflow Air speed Coverage range
Airflow Air speed Coverage range
The air coverage range is the distance to which the 0.8 ft/sec. air can reach, when air is blown out horizontally from the unit at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furni­ture inside the room.
ft/sec.(m/sec.)
ft/sec.(m/sec.)
ft/sec.(m/sec.)
CFM
ft (m)
CFM
ft (m)
CFM
ft (m)
640
10.5 (3.2) 15 (4.8)
PKA-A18GA
PKA-A18GAL
17.4 (5.3) 33 (10)
PKA-A30FA
PKA-A30FAL
705
16.1 (4.9) 41 (12.4)
PLA-A30BA
740
12.1 (3.7) 18 (5.6)
425
PKA-A36FA
PKA-A36FAL
990
17.7 (5.4)
50 (15.3)
PLA-A36BA
1060
17.4 (5.3) 26 (8.0)
18
8-2. PLA-A·BA
8-2-1 FRESH AIR INTAKE AND BRANCH DUCT
1. Branch duct hole and fresh air intake hole (Fig. 1)
At the time of installation, use the duct holes (cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 5-5/16 to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
Unit : inch(mm)
[Fig. 1]
Fresh air intake hole
Indoor unit
Branch duct hole
3-:1/8(:2.8) burring hole
Fresh air intake hole diagram
:4-29/32(:125) burring hole pitch
120
3-:15/16(:100) cut out hole
(*158)
6-7/32
120
Ceiling
Branch duct hole diagram
Drain pipe
Refrigerant pipe
:6-7/8(:175) burring hole pitch
(view from either side)
3-17/32
(90)
70
3-15/16
3-15/16
(100)
(90)
13-25/32(350)
3-17/32
(90)
3-15/16(100)
14-:1/8(:2.8) burring hole
:5-29/32(:150) cut out hole
5-1/8(130)
*6-3/32(155)
*6-9/16(167)
2. Fresh air intake (Installation at site)
By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct flange (option) onto it further, fresh exterior air intake can be accomplished. (The mounting of the multi-function casement increases the height of the ceiling plenum by 5-5/16 (135mm).)
19
3. Fresh air intake amount & static pressure characteristics
1 PLA-A18BA PLA-A30BA
Multifunction casement + High efficiency filter Multifunction casement + Standard filter
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 012
50 100 150 200
Taking air into the unit
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 012
50 100 150 200
2 PLA-A36BA
2 - inlet
1 - inlet
6
345
Airflow rate Airflow rate
3456
Airflow rate
[CMM]
[CFM]
[CMM]
[CFM]
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 012
How to read curves
Curve in the
1
graphs
0
Q
2
Q
3
Q
Qa
2 - inlet
1 - inlet
50 100 150 200
Duct characteristics at site
A
C
B
345
Q…Designed amount of fresh air intake A…Static pressure loss of fresh air intake
duct system with airflow amount Q <Pa(in.W.G.o10-2)> B…Forced static pressure at air condi-
A
EC
tioner inlet with airflow amount Q
<Pa(in.W.G.o10-2)>
C…Static pressure of booster fan with air-
flow amount Q <Pa(in.W.G.o10-2)> D…Static pressure loss increase amount
of fresh air intake duct system for air-
flow amount Q <Pa(in.W.G.o10 E…Static pressure of indoor unit with air-
AD
flow amount Q <Pa(in.W.G.o10 Qa…Estimated amount of fresh air intake
without D <CMM(CFM)>
<CMM(CFM)>
Multifunction casement + Standard filter Multifunction casement + High efficiency filter
[CMM]
6
[CFM]
-2
-2
)> )>
50(20)
)]
-2
0 0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 02
50 100 150 200 250
Taking air into the unit
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 02
50 100 150 200 250
50(20)
)]
-2
-50(-20)
2 - inlet
1 - inlet
48
Airflow rate
48
Airflow rate
6
6
[CMM]
[CFM]
[CMM]
[CFM]
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80)
1 - inlet
02
50 100 150 200 250
48
Airflow rate
2 - inlet
6
[CMM]
[CFM]
20
4. Change of outlet numbers
The optional air outlet is necessary. To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter.
When the air outlets are closed, close the vane by removing the vane connector.
Indoor unit
Button
Vane motor
Up/down vanes
Connector
Vane motor
Connector
Button
5. Branch duct and change of outlet numbers
<4- way air flow and branch duct>
Branch duct
Air intake
+ Branch duct should be connected to one of the branch duct holes on the main unit.
Air outlet
Outlet concave portion
Air outlet shutter plate (Option)
<3- way air flow and branch duct>
Branch duct
Air outlet closed position
<2- way air flow and branch duct>
Branch duct
Air
Air
outlet
outlet
closed
closed
position
position
Air intake
Air intake
+ Close the outlet on the side of branch duct and air flows in 3 directions.
Air outlet
+ The outlet on the side of branch duct and one of the other outlets are closed. Air flows in 2 directions.
Air outlet closed position
21
• Airflow rate of PLA-A18BA can be calculated from the airflow rate based on the char­acteristic of the duct for PLA-A30BA.
PLA-A30BA
30(12)
4-way airflow (horizontal vane) Round duct
)]Static pressure [Pa(in.W.G%10
-2
Duct
20(8)
4-way airflow (horizontal vane) Rectangular duct
30(12)
)]Static pressure [Pa(in.W.G%10
-2
Duct
20(8)
10(4)
10(4)
High
Static pressure [Pa(in.W.G%10
Low
0
0
0 50 100 150 200 250 [CFM]
2
4 6 8[CMM]
Airflow rate Airflow rate
80(32)
70(28)
)]Static pressure [Pa(in.W.G%10
-2
60(24)
50(20)
40(16)
30(12)
20(8)
10(4)
3-way airflow (horizontal vane) Round duct
Duct
Close
Low
0
0 2 4 6 8 10[CMM]
0 50 100 150 200 250 300 [CFM]
High
Airflow rate Airflow rate
2-way airflow (horizontal vane) Round duct
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
20(8)
Low
10(4)
0
024681012[CMM]
0 50 100 150 200 250 300 [CFM]
• Use 1 of the 2 duct holes on the indoor unit.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
Close
High
Airflow rate
Duct
Close
350 400
Static pressure [Pa(in.W.G%10
0
0
0 50 100 150 200 250 [CFM]
3-way airflow (horizontal vane) Rectangular duct
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
20(8)
10(4)
0
0 2 4 6 8 10[CMM]
0 50 100 150 200 250 300 [CFM]
2-way airflow (horizontal vane) Rectangular duct
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
20(8)
Static pressure [Pa(in.W.G%10
10(4)
0
024681012[CMM]
0 50 100 150 200 250 300 [CFM]
Low
2 4 6 8[CMM]
High
Duct
Close
High
Low
Duct
Close
Low
High
350 400
Airflow rate
Close
22
• Airflow rate of PLA-A36BA can be calculated from the airflow rate based on the char­acteristic of the duct for PLA-A42BA.
PLA-A42BA
4-way airflow (horizontal vane) Round duct
30(12)
)]Static pressure [Pa(in.W.G%10
-2
)]
-2
4-way airflow (horizontal vane) Rectangular duct
30(12)
Duct
20(8)
10(4)
Static pressure [Pa(in.W.G%10
Low
0
0
0 50 100 150
3-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct
80(32)
70(28)
)]Static pressure [Pa(in.W.G%10
-2
60(24)
50(20)
40(16)
30(12)
20(8)
10(4)
2 4 6 8[CMM]
Low
High
Airflow rate
Duct
Close
High
200
250 [CFM]
20(8)
10(4)
Static pressure [Pa(in.W.G%10
0
0
0 50 100 150
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
20(8)
Static pressure [Pa(in.W.G%10
10(4)
2 4 6 8[CMM]
Duct
Low
Airflow rate
Duct
Close
Low
200
High
High
250 [CFM]
0
0246810[CMM]
0 50 100 150 200 250 300 [CFM]
2-way airflow (horizontal vane) Round duct
100(40)
90(36)
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
20(8)
10(4)
0
Low
0 2 4 6 8 10 12[CMM]
0 50 100 150 200 250 300 [CFM]
Airflow rate Airflow rate
100(40)
Duct
Close
Close
High
90(36)
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
Static pressure [Pa(in.W.G%10
350 400
Airflow rate Airflow rate
• Use 1 of the 2 duct holes on the indoor unit.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
0
0 2 4 6 8 10[CMM]
0 50 100 150 200 250 300 [CFM]
2-way airflow (horizontal vane) Rectangular duct
Duct
Close
High
Low
20(8)
10(4)
0
0 2 4 6 8 10 12[CMM]
0 50 100 150 200 250 300 [CFM]
Close
350 400
23
9
NOISE CRITERION CURVES
9-1. INDOOR UNIT
PLA-A18BA
NOTCH SPL(dB) LINE
High 32 Medium1 31 Medium2 29
Low 28
PLA-A30BA
NOTCH SPL(dB) LINE
High 34 Medium1 32 Medium2 30
Low 28
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
PLA-A36BA
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB) LINE
High 40 Medium1 37 Medium2 34
Low 32
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
CEILING
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
UNIT
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
5ft
MICROPHONE
24
PKA-A18GA PKA-A18GAL
NOTCH
High Medium1 Medium2
Low
SPL(dB)
43 41 38 36
LINE
PKA-A30FA PKA-A30FAL
NOTCH
High
Low
SPL(dB)39LINE
45
90
) bar
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB= 0.0002
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 bar)
PKA-A36FA PKA-A36FAL
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NOTCH
High
Low
SPL(dB)46LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
49
UNIT
3.3ft
3.3ft
MICROPHONE
WALL
25
90
)
80
bar
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB= 0.0002
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
9-2. OUTDOOR UNIT
PUHZ-HA30NHA PUHZ-HA36NHA
90
80
70
60
MODE
COOLING
HEATING
SPL(dB)
52 53
LINE
NC-70
NC-60
MICROPHONE
3.3 ft UNIT
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-50
NC-40
NC-30
NC-20
5 ft
GROUND
26
10
OPTIONAL PARTS
10-1. INDOOR UNIT
Part Name Model Name Applicable model Remote sensor (extensible) PAC-SE41TS-E Connector for CN51 (output for remote display + pulse12V input)
Connector for CN32 (remote ON/OFF)
Connector for CN24 (Back up heating) Connector for CN30 (LLC)
Power supply terminal kit
Decoration panel with Wired remote controller Decoration panel Multi-function casement
Flange for fresh air intake
High-efficiency filter element (PAC-SH53TM-E is needed.)
i-see sensor corner panel
Wireless signal receiver Wireless remote controller kit
Space panel
Air outlet shutter plate L shape connection pipe
PAC-88HA-E(1pc.) PAC-725AD(10pcs.)
PAC-SE55RA-E
PAC-SE56RA-E PAC-SE57RA-E
PAC-SH55HR-E PAC-SH98HR-E
PLP-42BAMD
PLP-40BAU PAC-SH53TM-E PAC-SH65OF-E PAC-SH59KF-E
PAC-SA1ME-E
PAR-SA9FA-E PAR-SW96U-E
PAC-SH48AS-E
PAC-SH51SP-E PAC-SC84PI-E
All models
PLA-A·BA PKA-A·GA(L)/FA(L)
PLA-A·BA
PKA-A30/36FA(L)
27
10-2. OUTDOOR UNIT FOR PUZ-HA30/36NHA
Part Name Model Name
M-NET adapter PAC-SF80MA-E
A-control service tool PAC-SK52ST
Drain socket PAC-SG61DS-E
Air outlet guide(HA30/36 needs 2 pieces.) Air protect guide(HA30/36 needs 2 pieces.)
Drain pan
Distribution pipe for twin use MSDD-50SR-E
PAC-SG59SG-E
PAC-SH63AG-E PAC-SG64DP-E
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Nov. 2008 No.OCS12 REVISED EDITION-A PDF 6 Distributed in Oct. 2007 No.OCS12 PDF 7 Made in Japan
New publication, effective Nov. 2008 Specifications subject to change without notice.