Mitsubishi Electric PUZ-HA30NHA5, PUZ-HA36NHA5 Service Manual

SERVICE MANUAL
CONTENTS
1. REFERENCE MANUAL ·································· 2
2. SAFETY PRECAUTION ·································· 2
3. FEATURES ······················································ 6
4. SPECIFICATIONS ··········································· 7
5. DATA ································································ 8
6. OUTLINES AND DIMENSIONS ···················· 10
7. WIRING DIAGRAM ·········································11
8. WIRING SPECIFICATIONS ··························· 12
9.
REFRIGERANT SYSTEM DIAGRAM
10. TROUBLESHOOTING ··································· 17
11. EASY MAINTENANCE FUNCTION··············· 73
12. FUNCTION SETTING ···································· 75
13.
MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER
············ 84
14. DISASSEMBLY PROCEDURE ······················ 94
R410A
Notes:
• This manual describes service data of the outdoor units only.
• RoHS compliant products have <G> mark on the spec name plate.
[Model Name]
PUZ-HA30NHA5
PUZ-HA36NHA5
[Service Ref.]
PUZ-HA30NHA5 PUZ-HA36NHA5
PARTS CATALOG (OCB607)
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
No. OCH607
October 2015
2
2 SAFETY PRECAUTION
1
REFERENCE MANUAL
Before obtaining access to terminal, all supply circuits must be disconnected.
Preparation before the repair service.
• Prepare the proper tools.
• Prepare the proper protectors.
• Provide adequate ventilation.
• After stopping the operation of the air conditioner, turn off the power-supply beaker.
• Discharge the condenser before the work involving the electric parts.
Precautions during the repair service.
• Do not perform the work involving the electric parts with wet hands.
• Do not pour water into the electric parts.
• Do not touch the refrigerant.
• Do not touch the hot or cold areas in the refrigerating cycle.
• When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to touch the live parts.
2-1. ALWAYS OBSERVE FOR SAFETY
INDOOR UNIT
Model name Service Ref. Service manual No.
PLA-A18/30/36BA6 PLA-A18/30/36BA6 OCH581/OCB581
PKA-A18HA6 PKA-A18HA6 OCH580/OCB580
PKA-A30/36KA6 PKA-A30/36KA6.TH OCH584/OCB584
PEA-A18AA6 PEA-A18AA6.TH HWE08070
PEAD-A30/36AA5 PEAD-A30/36AA5 HWE14030
PCA-A30/36KA6 PCA-A30/36KA6 OCH585/OCB585
PVA-A30/36AA4 PVA-A30/36AA4 HWE14060
OCH607
3
Cautions for units utilizing refrigerant R410A
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Use new refrigerant pipes.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contaminants such as sulfur, oxides, dirt, shaving particles, etc. which are hazard to refrigerant cycle. In addition, use pipes with specified thickness.
Store the piping indoors, and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbenzene oil in a small amount.
In case of using the existing pipes for R22, be careful with the following.
· Be sure to clean the pipes and make sure that the insides of the pipes are clean.
· Change flare nut to the one provided with this product. Use a newly flared pipe.
· Avoid using thin pipes.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil, etc.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil, etc.
Do not use refrigerant other than R410A.
If other refrigerant (R22, etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil, etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil, etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Use the specified refrigerant only.
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
OCH607
4
Gravimeter
Unit
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
1 Gauge manifold · Only for R410A
· Use the existing fitting
specifications
.
· Use high-tension side pressure of 5.3MPa·G or over.
2 Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4 Gas leak detector · Use the detector for R134a, R407C or R410A.
5 Adaptor for reverse flow check · Attach on vacuum pump.
6 Refrigerant charge base
7 Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8 Refrigerant recovery equipment
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is a syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
OCH607
5
2-3. CAUTIONS FOR REFRIGERANT PIPING WORK
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
1Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness shown below. (Never use pipes of 7/256 in [0.7 mm] or below.)
2Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrigerants. Therefore, to enhance air tightness and strength, flare cutting dimension of copper pipe for R410A has been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also has partly been changed to increase strength as shown below. Set copper pipe correctly referring to cop­per pipe flaring dimensions for R410A below. For 1/2 and 5/8 inch pipes, the dimension B changes. Use torque wrench corresponding to each dimension.
3Tools for R410A (The following table shows whether conventional tools can be used or not.)
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
1/32 [0.8]
1/32 [0.8]
1/32 [0.8]
5/128 [1.0]
1/32 [0.8]
1/32 [0.8]
1/32 [0.8] 5/128 [1.0] 5/128 [1.0]
Nominal
dimensions
(in)
Diagram below: Piping diameter and thickness
Outside
diameter
(mm)
Thickness
: in [mm]
R410A R22
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
11/32-23/64 [ 9.1] 1/2-33/64 [13.2] 41/64-21/32 [16.6] 49/64-25/32 [19.7] —
9.0
13.0
16.2
19.4
23.3
Nominal
dimensions (in)
Flare cutting dimensions
Outside
diameter (mm)
Dimension A
( )
+0
-0.4
R410A R22
(mm)(in [mm])
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
43/64 [17.0] 7/8 [22.0] 1-3/64 [26.0] 1-9/64 [29.0]
17.0
22.0
24.0
27.0
36.0
Nominal
dimensions (in)
Flare nut dimensions
Outside
diameter (mm)
Dimension B (in [mm])
R410A
R22 (mm)
Gauge manifold Charge hose Gas leak detector
Refrigerant recovery equipment Refrigerant cylinder Applied oil
Safety charger
Charge valve
Vacuum pump
Flare tool
Bender Pipe cutter Welder and nitrogen gas cylinder Refrigerant charging scale Vacuum gauge or thermis­tor vacuum gauge and vacuum valve Charging cylinder
Air purge, refrigerant charge and operation check Gas leak check
Recover refrigerant Refrigerant charge
Apply to flared section
Prevent compressor malfunction when charging refrigerant by
spraying liquid refrigerant Prevent gas from blowing out
when detaching charge hose Vacuum drying and air purge
Flaring work of piping
Bend the pipes Cut the pipes Weld the pipes Recover refrigerant Check the degree of vacuum. (Vacuum valve prevents back flow of oil and refri­gerant to thermistor vacuum gauge) Recover refrigerant
Tool exclusive for R410A Tool exclusive for R410A Tool for HFC refrigerant Tool exclusive for R410A Tool exclusive for R410A Ester oil and alkylbenzene oil (minimum amount) Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can be used if equipped with adop­ter for reverse flow check Tools for other refrigerants can be used by adjusting flaring dimension Tools can be used for other refrigerants Tools can be used for other refrigerants Tools can be used for other refrigerants Tools can be used for other refrigerants Tools can be used for other refrigerants
Tool exclusive for R410A
Tools and materials Use R410A tools Can R22 tools be used?
(Usable if equipped with adopter for rever­ se flow)
(Usable by adjusting flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) : Tools for other refrigerants can be used under certain conditions. : Tools for other refrigerants can be used.
Dimension A
Dimension B
OCH607
6
3 FEATURES
HIGH HEATING CAPACITY
Industry-first flash injection circuit is equipped, which enables to keep the equal capacity to the rating even when outside tem­perature is 5°F [−15°C].
HIGH SPEED HEATING START UP
The performance of heating start up is improved. Compared to PUZ-A type, Hyper Heating Inverter reduced the time for heat­ing start up by about half. After starting operation, the airflow temperature goes up to 105°F [41°C] quickly in 10 minutes. With industry first shorter and less frequent defrost, defrosting time is cut down by 15% compared to PUZ-A type and heating operation can continuously run for maximum 150 minutes.
WIDE HEATING RANGE
The heating range is expanded to −13°F [−25°C] compared to PUZ-A type which is up to 10°F [−12°C].
CHARGELESS SYSTEM PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT. Maximum 100 ft, 30m
The refrigerant circuit with LEV (Linear Expansion Valve) and power receiver always control the optimal refrigerant level regardless of the length (maximum: 100 ft [30 m] and minimum: 16 ft [5 m]) of piping. The additional refrigerant charg­ing work during installation often causes problems. It is completely eliminated by chargelss system. This unique system improves the quality and reliability of the work done. It also helps to speed up the installation time.
PUZ-HA30NHA5 PUZ-HA36NHA5
Outdoor W.B. temp.
Heating capacity
-13°F
[-25°C]
-4°F
[-20°C]
5°F
[-15°C]
14°F
[-10°C]
23°F
[-5°C]
32°F [0°C]
A36
HA36
40,000
(Btu/h)
30,000
23,500BTU/h
38,000BTU/h
0
Performance
about
60%UP
33,000Btu/h (Outlet air temp. 105°F[41°C])
About 5min.
Stable
About 50% CUT
Elapsed time(min.)
Heating capacity(peak)
About 10 min.
When stabled,
hot air of 122˚F[50˚C]
PUZ-A type: Outlet air temp. 105˚F[41˚C]
HA36
Outlet air temp.105˚F[41˚C]
w1
40,000
(Btu/h)
30,000
5 100
w1 Condition Room temp. 70°F[21°C](D.B.) Outdoor temp. 35°F[1.7°C](D.B.) / 33°F[0.6°C](W.B.) : Hi notch
It does not become
122˚F[50˚C]
when outside air temp.
is too low.
0
Expanded
Up to -13
°F
Outdoor wet-bulb temperature
A36 type
HA36 type
-13°F
10°F
-13°F
[-25°C]
-4°F
[-20°C]
5°F
[-15°C]
14°F
[-10°C]
23°F
[-5°C]
32°F [0°C]
OCH607
7
4 SPECIFICATIONS
Service Ref.
Power supply Phase Single
Cycle 60 Hz
Voltage 208/230 V MCA A 28 MOCP A 40 Breaker size A 30 External finish Munsell 3Y 7.8/1.1 Heat exchanger Plate fin coil Defrost method Reverse cycle Crankcase heater
kW
Compressor Hermetic
Model
Motor output kW 2.5
R.L.A. 20
L.R.A. 27.5
Starter type Inverter Fan Fan(drive) o No. Propeller fan o 2
Fan motor output
kW
0.086 + 0.086
Fan motor
F.L.A.
0.40 + 0.40
Airflow m
3
/min 100
CFM 3530
Sound level Cooling dB 52
Heating dB 53 Protection devices
HP switch LP switch
Discharge thermo
Dimension W mm 950
D mm 330+30
H mm 1350
W in 37-12/32
D in 13 + 1-3/16
H in 53-5/32 Weight kg
lb
Refrigerant
Charged kg 5.5
R410A
lb 12 Control Linear expansion valve Oil Model Ether (FV50S) Charged L 1.4
oz 45 Refrigerant Pipe size OD mm 9.52 piping Liquid in 3/8
Pipe size OD mm 15.88 Gas in 5/8 Connection method Indoor Flared Connection method Outdoor Flared Height difference m Maximum 30 IU - OU ft Maximum 100 Piping length m Maximum 75
ft Maximum 245
PUZ-HA30NHA5 PUZ-HA36NHA5
ANB33FJEMT
120 265
OCH607
8
Piping Length (one way
)
Charged
Factory
Service Ref. 100 ft 110 ft 120 ft 130 ft 140 ft 150 ft 160 ft 165 ft
30 m 33 m 37 m 40 m 43 m 46 m 49 m 50 m
PUZ-HA30NHA5 PUZ-HA36NHA5
194 oz 200 oz 206 oz 212 oz 218 oz 224 oz 230 oz 237 oz 195 oz
5.5 kg 5.7 kg 5.9 kg 6.0 kg 6.2 kg 6.4 kg 6.6 kg 6.7 kg
180 ft 200 ft 210 ft 230 ft 245 ft
55 m 61 m 64 m 70 m 75 m
242 oz 254 oz 260 oz 272 oz 280 oz
6.9 kg 7.2 kg 7.4 kg 7.7 kg 7.9 kg 5.5 kg
Additional charge is required for pipes longer than 100 ft
.
Service Ref.
Compressor model
(")
Winding Resistance
U-V
U-W
W-V
(at 68°F [20°C])
PUZ-HA30NHA5 PUZ-HA36NHA5
ANB33FJEMT
0.188
0.188
0.188
5-1. REFILLING REFRIGERANT CHARGE (R410A: oz, kg)
5-2. COMPRESSOR TECHNICAL DATA
5
DATA
5-3. NOISE CRITERION CURVES
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
PUZ-HA30NHA5 PUZ-HA36NHA5
COOLING
MODE
HEATING
52
SPL(dB)
53
LINE
5 ft
3.3 ft
MICROPHONE
UNIT
GROUND
OCH607
9
PUZ-HA30NHA5
Representative matching
PKA-A36KA6
Mode
COOLING HEATING
Total Capacity BTU/h
33,500
2,790
38,000
3,410
Input W
Electrical circuit
Indoor unit model
PKA-A36KA6
Phase
Single
Cycle
60 Hz
Voltage
230 V
Current
0.36A
Outdoor unit model
PUZ-HA36NHA5
Phase
Single
Cycle
60Hz
Voltage
230V
Current
Refrigerant circuit
Discharge pressure MPa
Suction pressure MPa
Discharge temperature °C
Condensing temperature °C
Suction temperature °C
Ref. Pipe length m
Discharge pressure PSIG
Suction pressure PSIG
Discharge temperature °F
Condensing temperature °F
Suction temperature °F
Ref. Pipe length ft
side
Indoor
Intake air temperature DB °C
Intake air temperature WB °C
Discharge air temperature DB °C
side
Outdoor
Intake air temperature DB °C
Intake air temperature WB °C
side
Indoor
Intake air temperature DB °F
Intake air temperature WB °F
Discharge air temperature DB °F
side
Outdoor
Intake air temperature DB °F
Intake air temperature WB °F
SHF
BF
PKA-A30KA6
COOLING HEATING
12.2 A
2.58
0.87
70.8
44.4
10.5
7.6
374
126
159
112
51
25
26.7
19.4
12.5
35
23.9
80
67
55
95
75
0.71
0.09
15.4 A
2.94
0.73
75.6
49.7
2.8
7.6
427
106
168
121
37
25
21.1
15.6
43.5
8.3
6.1
70
60
110
47
43
30,000
2,500
32,000
2,930
PKA-A30KA6
0.57A
11.1 A
2.51
0.88
67.7
43.3
10.8
7.6
364
128
154
110
51
25
26.7
19.4
12.3
35
23.9
80
67
54
95
75
0.70
0.09
13.0 A
2.92
0.71
78.1
49.4
2.5
7.6
424
103
173
121
37
25
21.1
15.6
43.4
8.3
6.1
70
60
110
47
43
5-4. STANDARD OPERATION DATA
OCH607
10
6
OUTLINES AND DIMENSIONS
PUZ-HA30NHA5 Unit : mm<inch> PUZ-HA36NHA5
Min. 1000mm
<39-3/8>
Min. 150mm
<5-29/32>
Min. 10mm
<3/8>
Min. 10mm
<3/8>
FREE
<Foundation bolt height>
FOUNDATION
Service space
Terminal Block
Left···Power supply wiring
Right····Indoor/Outdoor wiring
Earth terminal
Service panel
Handle
1
2
23<29/32>
1076<42-3/8>
* 1 447<17-19/32>
* 1 443<17-7/16>
Handle
Front piping cover
Rear piping cover
Air Discharge
Rear Air Intake
Side Air Intake
31<1-7/32>
145
<5-23/32>
145
<5-23/32>
220
<8-21/32>
30<1-3/16>
145
<5-23/32>
81<3-3/16>
219<8-5/8>
71<2-13/16>
71<2-13/16>
Bottom piping hole
(Knockout)
Drain hole
5-[33<1-5/16>
Handle
Side Air Intake
Air intake
Rear Air Intake
Handle
Handle
40<1-9/16>
74<2-19/32>
When installing the conduit.
Set the attachment to the
inner side of each panel.
2-[22.2<7/8>
1/2 Conduit attachment
45<1-25/32>
40<1-9/16>
65<2-9/16>
92<3-5/8>
27<1-1/16>
55<2-3/16>
23<29/32>
73<2-7/8>
63<2-1/2>
Rear piping hole
(Knockout)
Rear trunking hole
(Knockout)
Conduit hole
(2-[27<1-1/16>Knockout)
[92
<3-5/8>
19<3/4>
55<2-3/16>
92<3-5/8>
75
<2-31/32>
40<1-9/16>
73<2-7/8>
63<2-1/2>
23<29/32>
27<1-1/16>
92<3-5/8>
Right piping hole
(Knockout)
Right trunking hole
(Knockout)
Conduit hole
(2-[27<1-1/16>Knockout)
[92
<3-5/8>
92<3-5/8>
65<2-9/16>
45<1-25/32>
40<1-9/16>
27<1-1/16>
55<2-3/16>
23<29/32>
73<2-7/8>
63
<2-1/2>
Front piping hole
(Knockout)
Front trunking hole
(Knockout)
Conduit hole
(2-[27<1-1/16>Knockout)
[92
<3-5/8>
371<14-19/32>
330<13>30<1-3/16>
175<6-7/8>
600<23-5/8>
175<6-7/8>
42<1-21/32>66<2-5/8>
950<37-13/32>
322<12-11/16>
1350<53-5/32>
635<25>
19<3/4>
417<16-13/32>
370<14-9/16>
2-U Shaped notched hole
(Foundation Bolt M10<W3/8>)
56<2-7/32>
28<1-3/32>
53<2-3/32>
45<1-25/32>
2-12 o 36 Oval hole
(Foundation Bolt M10<W3/8>)
1····Refrigerant GAS pipe connection (FLARE)[15.88<5/8>
2····Refrigerant LIQUID pipe connection (FLARE)[ 9.52<3/8>
*1 ····Indication of STOP VALVE connection location.
Example of Notes
1 FREE SPACE (Around the unit)
2 SERVICE SPACE
3 FOUNDATION BOLTS
4 PIPING-WIRING DIRECTIONS
Piping Knockout Hole Details
The diagram below shows a
basic example.
Explanation of particular details are
given in the installation manuals, etc.
Dimensions of space needed
for service access are
shown in the below diagram.
Please secure the unit firmly
with 4 foundation (M10<W3/8>)
bolts. (Bolts and washers must
be purchased locally.)
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
Min.
10mm<3/8>
Min.
500mm
<19-11/16>
Min.
500mm
<19-11/16>
Min.
150mm
<5-29/32>
Min.
30mm
<1-3/16>
OCH607
11
7
WIRING DIAGRAM
PUZ-HA30NHA5 PUZ-HA36NHA5
TB1 MC MF1, MF2 21S4 63H
TH3 TH4 TH6 TH7 TH8
LEV-A, LEV-B, LEV-C DCL
Terminal Block<Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (4-Way Valve) High Pressure Switch
63L Low Pressure Switch
Thermistor<Liquid>
TH32
Thermistor<Suction>
TH33
Thermistor<Ref. check>
Thermistor<Discharge> Thermistor<2-Phase Pipe> Thermistor<Ambient> Thermistor
<Heat Sink
>
Linear Expansion Valve
Reactor
P.B.
Power Circuit Board
ACTM
Active Filter Module
CB
Main Smoothing Capacitor
CY1, CY2
Capacitor
Noise Filter Circuit Board
N.F.
Controller Circuit Board
C.B.
SYMBOL NAME SYMBOL NAME
Switch<Function Switch> Switch<Function Switch> Switch<Function Switch>
Switch
<Manual Defrost, Defect History Record Reset, Refrigerant Address> Switch<Test Operation> Switch<Function Switch, Model Select> Switch<Model Select>
SW7
SW1
SW4 SW5 SW6
SW8 SW9
Switch<Pump Down>
SWP
Connector<Emergency Operation>
CN31
F1, F2, F3, F4
CNM CNMNT CNVMNT CNDM
Connector<Connection for Option>
CN51
Fuse<T6.3AL250V
>
SS
Connector<Connection for Option>
Connector<Connection for Option>
Connector<Connection for Option>
Connector<Connection for Option>
Connector<Connection for Option>
1 2 3 4 5 6 7 8
MODEL
SW6
*
1 MODEL SELECT
*
2 SW5 -1 to 5 : Function Switch
SW5-6 *2
OFF
ON
30N
OFF
ON
1 2 3 4 5 6
1 2 3 4 5 6 7 8
OFF
ON
36N
OFF
ON
1 2 3 4 5 6
The black square(■)indicates a switch position.
SYMBOL
M-NET ADAPTER
NAME TB7 CN5 CND CN2M
Terminal Block<M-NET connection> Connector<Transmission> Connector<Power Supply> Connector<M-NET communication>
CN5
(WH)
3 1
TB7
2
1
CND (WH)
CN2M
(WH)
M-NET ADAPTER
M-NET
A B S
When M-NET Adapter is connected
CNVMNT
(WH)
31
CNDM
(WH)
CN51
(WH)
1
3
1
5
CNMNT
(WH)
CNM (WH)
51
LEV-A
(WH)
LEV-A
C. B.
LEV-B
(RD)
LEV-B
6
3
5
5
1
TH7/6
(RD)
63H (YE)
TRANS
X55
X51
TH3
(WH)
CNDC
(PK)
CNF1 (WH)
CNF2 (WH)
TH4
(WH)
TH7 TH6 TH3 TH4
41 21
TH32 (BK)
TH32
2
1 2 1
SW7
SW6SW1
SW9
CN31
141
MF1
MF2
M M
7
1
CN2
(WH)
CNS
(WH)
CNAC
(WH)
CN4
(WH)
SV2 (BU)
SS
(WH)
21S4 (GN)
2
1
LED1
LED2
X52
F1
F2
F4
F3
*1*
1
21
43
SW5SW8SW4 SWP
IPM
UVW
21S4
61
31
7
1
3
1
2
3 1
71
LEV-C
(BU)
6
1
7
2
TH33
(YE)
TH33
31
13 13 13
CN52C
(RD)
221
TABN
TABP
CN3
(WH)
CNAF
(WH)
CN2
(WH)
CN4
(WH)
CN5 (RD)
TH8
CB
1
4
1
7
7
1 2
1 2 1 2
2
2
3
2
6
RD
RD
TABP2
WH
WH
P. B.
CNDC
(PK)
TABU
TABV
TABW
BK
WH
DS2
DS3
TABT
TABS
TABP1
TABN1
BK
1
TABN2
WH
WH
BU
BU
RD
CY1
CY2
LI NI
LO NO
EI
E2
POWER SUPPLY 208/230VAC 60Hz
TO INDOOR UNIT
TB1
L1 L2 GR S1 S2 S3
N. F.
MC
1
2
2
3
1
3
1
1
2
2
CN5 (RD)
RD
RD
CNAC1
(WH)
CNAC2
(RD)
CN52C
(BK)
BU
DCL
ACTM
L1
L2
N2
N1
P
Io
RD
BK
RD
WH
WH
BK
61
4
BU
YEGNOG
BN
63H
63L
(RD)
31
63L
LEV-C
M
5
3
5
1
RD
5
*
Use copper supply wires.
Utilisez des fils d'alimentation en cuivre.
BK
BK
OCH607
12
8
WIRING SPECIFICATIONS
8-1. INDOOR UNIT POWER SUPPLIED FROM OUTDOOR UNIT
The following connection patterns are available. The outdoor unit power supply patterns vary on models.
1:1 System Simultaneous twin system
A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit/outdoor unit connecting cords F Remote controller G Indoor unit H Indoor unit earth
S1
S2
L1
L2
GR
1 2
S1
S2
S3
S3
1 2
S1
S2
S3
1 2
S1
S2
S3
Warning: In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Indoor unit model
PLA-A18, 30
PCA-A30, PKA-A18, 30, 36
PLA-A36 PCA-A36
1A 2A
15A 15A
A
D
C
B
S1
S2
L1
L2
GR
S3
A
D
C
B
E
F
E
F
GG G
HH H
Indoor unit power supply Minimum circuit ampacity Maximum rating of overcurrent protective device
*1. Maximum 147 ft [45 m] If AWG13 is used, maximum 164 ft [50 m]. If AWG13 is used and S3 is separated, maximum 262 ft [80 m]. *2. The 30 ft [10 m] wire is attached in the remote controller accessory. Maximum 1500 ft *3. The figures are NOT always against the ground. S3 terminal has 24 V DC against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device. *4. Use earth leakage breaker (NV)
1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.
3. Use wires rated 600V or more for the power supply cables and the indoor/outdoor unit connecting cables.
4. Install an earth longer than other cables.
Notes:
Outdoor unit model Outdoor unit power supply Breaker size Minimum circuit ampacity Maximum rating of overcurrent protective device
Outdoor unit power supply Outdoor unit power supply earth Indoor unit-Outdoor unit *1 Indoor unit earth Remote controller-Indoor unit *2 Outdoor unit L1-L2 *3 Indoor unit-Outdoor unit S1-S2 *3 Indoor unit-Outdoor unit S2-S3 *3 Remote controller-Indoor unit *3
HA30
Single, 208/230 V, 60 Hz
30A 28A
40A 2 o Min. AWG 10 1 o Min. AWG 10
3 o AWG 16 (polar)
1 o Min. AWG 16
2 o AWG 22 (Non-polar)
208/230 V AC
24 V DC
Wiring
Wire No. o
size
Circuit
rating
S1
S2
S3
S1
S2
S3
A-Control
Outdoor Unit
3 poles isolator
208/230 V
Single phase
Isolator
A-Control
Indoor Unit
*4
• Turn on the main power when the ambient temperature is −4°F [20°C] or higher.
• In below −4°F [20°C] condition, it needs at least 4 hr standby to operate in order to warm the electrical parts.
208/230 V AC
12 V DC
OCH607
13
8-2. SEPARATE INDOOR UNIT/OUTDOOR UNIT POWER SUPPLIES
The following connection patterns are available. The outdoor unit power supply patterns vary on models.
1:1 System
S1 S2
1 2
S1 S2 S3
S3
Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
The optional indoor power supply terminal kit is required.
Outdoor unit power supply
Wiring circuit breaker or isolating switch Outdoor unit Indoor unit/outdoor unit connecting cords Remote controller Indoor unit Indoor unit power supply
Simultaneous twin system
If the indoor and outdoor units have separate power supplies, refer to the table below. Change the indoor unit electrical box wiring referring to the figure in the right and the DIP switch settings of the outdoor unit control board.
Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Outdoor unit power supply
Wiring circuit breaker or isolating switch Outdoor unit Indoor unit/outdoor unit connecting cords Remote controller Indoor unit Indoor unit power supply
ON OFF 1 2
(SW8)
3
Indoor unit electrical box connector con­nection change
Label affixed near each wiring diagram for the indoor and outdoor units
Outdoor unit DIP switch settings (when using separate indoor unit/outdoor unit power supplies only)
Indoor unit specifications
Required
Required
*1. Maximum 165 ft [50 m] *2. The 30 ft [10 m] wire is attached in the remote controller accessory . Maximum 1500 ft [500 m] *3. The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.
3. Use wires rated 300 V or more for the power supply cables.
4. Install an earth longer than other cables.
Indoor unit model
Indoor unit power supply Minimum circuit ampacity Maximum rating of overcurrent protective device
Indoor unit power supply Indoor unit power supply earth Indoor unit-Outdoor unit *1 Indoor unit earth Remote controller-Indoor unit *2 Indoor unit L1-L2 *3 Indoor unit-Outdoor unit S1-S2 *3 Indoor unit-Outdoor unit S2-S3 *3 Remote controller-Indoor unit *3
PLA-A18, 30
PCA-A30, PKA-A18
PLA-A36, PCA-A36
Single 208/230 V, 60 Hz ,Single 208/230 V 60 Hz
1 A 2A
15A 15A
2
o Min. AWG16 2 o Min. AWG16
1
o Min. AWG16 1 o Min. AWG16
2
o AWG22 (polar) 2 o AWG22 (polar)
2
o AWG22 (Non-polar) 2 o AWG22 (Non-polar)
208/230 V AC
24 V DC 24 V DC 12 V DC 12 V DC
Circuit
rating
Connectors (connections when shipped from the factory are for indoor unit power supplied from outdoor unit)
Indoor unit power supplied from outdoor unit (Initial setting)
If the indoor and outdoor units have separate power supplies, change the connections of the connectors as shown in the following figure.
Connectors
Indoor unit
control board
Separate indoor unit/outdoor unit power supplies
Indoor unit
control board
Note: There are three types of labels (labels A, B, and C).
Affix the appropriate labels to the units according to the wiring method.
S1 S2
1 2
L1 L2
L1 L2
GR GR
L1 L2 GR
S1 S2 S3
1 2
S1 S2 S3
S3
S1
S2
S3
L1
L2 GR
BLUE
BLUE
YELLOW
YELLOW
CN01
S1
S2
S3
L1
L2
GR
YELLOW
BLUE
BLUE
YELLOW
Wiring
Wire No.
o
size
A
Earth leakage breaker
B C D E F G H
Option
J
Option
J
A
Earth leakage breaker
B C D E F G H
A
J
J
D
C
B
E
F
G
A
D
E
F
G G
CN01
K
Indoor unit earth
K
208/230 V AC
H
C
B
C
B
H
C
B
L1 L2 GR
L1 L2 GR
OCH607
14
8-3. INDOOR – OUTDOOR CONNECTING CABLE
Note: The Maximum cable length may vary depending on the condition of installation, humidity or materials, etc.
Indoor unit-Outdoor unit
Outdoor power supply
Max. 147 ft [45 m] 3 o AWG15(polar)
Max. 164 ft [50 m]
3 o AWG13(polar)
Max. 262 ft [80 m]
3 o AWG13(polar) and S3 separated
Wire No. o Size
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections). Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the intermediate connection point.
Indoor unit-Outdoor unit
Indoor/Outdoor separate power supply
Max. 393 ft [120 m]
2 o Min. AWG22
Wire No. o Size
Note: The optional indoor power supply terminal kit is necessary.
8-4. M-NET WIRING METHOD
Points to notice:
(1)
Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from making
an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same conduit tube. (2) Terminal block (TB7) for transmission wires should never be connected to 208/230 V power supply. If it is connected, electronic parts on M-NET P.C. board may be burnt out. (3) Use 2-core x AWG16 [1.25 mm2] shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be
sent or received normally if different types of transmission wires are put together in the same multi-conductor cable. Never
do this because this may cause a malfunction.
It is acceptable if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise. “Ed” error will appear on the LED display of outdoor unit. “0403” error will appear on the central-control remote controller.
If there are more than 2 grounding spots on the shield wire, noise may enter into the shield wire because the ground wire and shield
wire form one circuit and the electric potential difference occurs due to the impedance difference among grounding spots. In case of
single spot grounding, noise does not enter into the shield wire because the ground wire and shield wire do not form 1 circuit. To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
Centralized controller
Refrigerant address 00
M-NET address 01
A-control remote controller
A-control remote controller
A-control remote controller
Refrigerant address 00
M-NET address 02
Refrigerant address 00
M-NET address 03
Power
supply unit
Centralized
controller
M-NET transmission wire
O Bad example (Multi spot grounding of shield wire)
Good example 1 (Single spot grounding of shield wire)
Power
supply unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET transmission wire
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET transmission wire
M-NET type outdoor unit
M-NET type outdoor unit
Good example 2 (Single spot grounding of shield wire)
Centralized
controller
Centralized
controller
Power
supply unit
Power
supply unit
OCH607
15
8-4-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above sec­tion. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
Note: Refrigerant addresses can be overlapped if they are in the different group.
Note: In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the
group. As “03” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the group for the outdoor unit whose refrigerant address is “00”.
8-4-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI series, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches (SW11 for ones digit and SW12 for tens digit), which is located on the M-NET board of outdoor unit. (Initial setting: all addresses are set to “0”.)
8-4-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group set­ting is not conducted. Set the refrigerant address by using DIP SW1-3 to 1-6 on the outdoor controller board. [Initial setting: all switches are OFF. (All refrigerant addresses are “00”.)]
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1 2
50
M-NET Address No.
<Setting example>
Switching
setting
SW11 ones digit
SW12 tens digit
OFF
ON
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
0
Refrigerant address
OFF
ON
8
OFF
ON
1
OFF
ON
9
OFF
ON
10
OFF
ON
11
OFF
ON
12
OFF
ON
13
OFF
ON
14
OFF
ON
15
OFF
ON
2
OFF
ON
3
OFF
ON
4
OFF
ON
5
OFF
ON
6
OFF
ON
7
A-control remote controller
Group A Group B Group C
A-control remote controller
TB5
A-control remote controller
Refrigerant address 00
M-NET address 01
Refrigerant address 00
M-NET address 02
Refrigerant address 01
M-NET address 03
Refrigerant address 00
M-NET address 04
Power
supply unit
Centralized
controller
Power
supply unit
A-control remote controller
A-control remote controller
TB5
Group A Group B
Refrigerant address 00
M-NET address 01
Refrigerant address 01
M-NET address 02
Refrigerant address 00
M-NET address 04
Refrigerant address 01
M-NET address 03
Refrigerant address 02
M-NET address 05
Centralized
controller
M-NET wiring
(1) Use 2-core x AWG16 [1.25 mm2] shield wire for electric wires. (Excluding the case connecting to system controller.) (2) Connect the wire to the M-NET terminal block. Connect one core of the transmission wire (non-polar) to A terminal and the other to B. Peel the shield wire, twist the shield part to a string and connect it to S terminal. (3) In the system which several outdoor units are being connected, the terminal (A(M1), B(M2), S) on M-NET terminal block should be individually wired to the other outdoor unit’s terminal, i.e. A to A, B to B and S to S. In this case, choose one of those outdoor units and drive a screw to fix an ground wire on the plate as shown on the right figure.
Transmission
wire
Shield part
M-NET terminal block
Ground wire
A B S
OCH607
16
9
REFRIGERANT SYSTEM DIAGRAM
PUZ-HA30NHA5 PUZ-HA36NHA5 Unit: mm (in)
Distributor
Thermistor TH7 (Ambient)
Heat exchanger
Refrigerant GAS pipe connection [15.88(5/8)
Refrigerant LIQUID pipe connection [9.52 (3/8)
Stop valve (with service port)
Strainer (#100)
Power receiver
Linear expansion valve-B
Linear expansion valve-C
Linear expansion valve-A
Thermistor TH6 (2-phase pipe)
Thermistor TH3 (Liquid)
Charge plug (Low pressure)
Charge plug (High pressure)
Heat inter change circuit
Thermistor TH4 (Discharge)
Compressor
Injection port
Strainer (#50)
Solenoid valve (4-way valve)
Strainer (#100)
Strainer (#100)
Strainer (#100)
Strainer (#100)
Muffler
Ball valve
Thermistor TH33 (Ref. check)
Thermistor TH32 (Suction)
Low pressure switch 63L
High pressure switch 63H
Refrigerant flow in cooling Refrigerant flow in heating
Thermistor TH8 (Heat sink)
Power circuit board
REFRIGERANT COLLECTING (PUMP DOWN)
When relocating or disposing of the indoor/outdoor unit, pump down the system following the procedures below so that no refrig­erant is released into the atmosphere.
1 Turn off the power supply (circuit breaker). 2 Connect the low-pressure valve on the gauge manifold to the charge plug (low-pressure side) on the outdoor unit. 3 Close the liquid stop valve completely. 4 Supply power (circuit breaker).
When power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If “CEN-
TRALLY CONTROLLED” is displayed, the refrigerant collecting (pump down) cannot be completed normally.
Start-up of the indoor-outdoor communication takes about 3 minutes after the power (circuit breaker) is turned on. Start the
pump-down operation 3 to 4 minutes after the power (circuit breaker) is turned on.
5 Perform the refrigerant collecting operation (cooling test run).
Push the pump-down SWP switch (push-button type) on the control board of the outdoor unit. The compressor and ventilators
(indoor and outdoor units) start operating (refrigerant collecting operation begins). (LED1 and LED2 on the control board of the outdoor unit are lit.)
Only push the pump-down SWP switch if the unit is stopped. However, even if the unit is stopped and the pump-down SWP
switch is pushed less than 3 minutes after the compressor stops, the refrigerant collecting operation cannot be performed. Wait until the compressor has been stopped for 3 minutes and then push the pump-down SWP switch again.
6 Fully close the ball valve on the gas pipe side of the outdoor unit when the pressure gauge on the gauge manifold shows 0.05
to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm²) and quickly stop the air conditioner.
Because the unit automatically stops in about 3 minutes when the refrigerant collecting operation is completed (LED1 off,
LED2 lit), be sure to quickly close the gas ball valve. However, if LED1 is lit, LED2 is off, and the unit is stopped, open the
liquid stop valve completely, close the valve completely after 3 minutes or more have passed, and then repeat step 5. (Open the gas ball valve completely.)
If the refrigerant collecting operation has been completed normally (LED1 off, LED2 lit), the unit will remain stopped until the
power supply is turned off.
Note that when the extension piping is very long with a large refrigerant amount, it may not be possible to perform a pump-
down operation. In this case, use refrigerant recovery equipment to collect all of the refrigerant in the system.
7 Turn off the power supply (circuit breaker), remove the gauge manifold, and then disconnect the refrigerant pipes.
Warning:
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
If the refrigerant pipes are disconnected while the compressor is operating and the stop valve (ball valve) is open, the pressure in the refrigeration cycle could become extremely high if air is drawn in, causing the pipes to burst, personal injury, etc.
OCH607
17
10 TROUBLESHOOTING
<Check code displayed by self-diagnosis and actions to be taken for service (summary)>
Present and past check codes are logged, and they can be displayed on the wired remote controller and control board of out­door unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summa­rized in the table below. Check the contents below before investigating details.
10-1. TROUBLESHOOTING
Unit conditions at service
Check code
Actions to be taken for service (summary)
The trouble is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “10-4. SELF-DIAGNOSIS ACTION TABLE”.
Conduct trouble shooting and ascertain the cause of the trouble according to “10-5. TROUBLESHOOTING BY INFERIOR PHENOMENA”.
The trouble is not reoccurring.
Logged
Not logged
1 Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise, etc. Re-check the symptom, and check the installation environment, refrigerant amount, when the trouble occurred, matters related to wiring, etc. 2
Reset check code logs and restart the unit after finishing
service. 3 There is no abnormality concerning of parts such as
electrical component, controller board, remote controller,
etc.
1 Re-check the abnormal symptom. 2
Conduct troubleshooting and ascertain the cause of the trouble according to “10-5. TROUBLESHOOTING
BY
INFERIOR PHENOMENA”. 3 Continue to operate unit for the time being if the cause is not ascertained. 4 There is no abnormality concerning of parts such as
electrical component, controller board, remote controller,
etc.
10-2. CHECK POINT UNDER TEST RUN
(1) Before test run
After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
Measure impedance between the ground and the power supply terminal block (L1, L2) on the outdoor unit by 500 V Megger
and check that it is 1.0 M" or over.
Note: Do not use 500 V Megger to indoor/outdoor connecting wire terminal block (S1, S2, S3) and remote controller terminal
block (1, 2). This may cause malfunction.
Make sure that test run switch (SW4) is set to OFF before turning on power supply.
Turn on power supply 12 hours before test run in order to protect compressor.
For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “12. FUNCTION SETTING".
Make sure to read operation manual before test run. (Especially items to secure safety.)
OCH607
18
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Test run Input maintenance info. Function setting Check Self check
F1 F2 F3 F4
Test run menu
Cursor
Service menu:
Test run Drain pump test run
1
Select "Service" from the Main menu, and press the button.
2
Select "Test run" with the F1 or F2 button, and press the button.
Select "Test run" with the F1
or F2 button, and press the button.
F1 F2 F3 F4
Cool
Pipe
Auto
Switch disp.
Mode Fan
RemainTest run
F1 F2 F3 F4
Remain
Vane
Cool mode: Check the cold air blows out. Heat mode: Check the heat blows out.
Press the F1
button to go through the operation modes in the order of "Cool
and Heat".
Check the auto vane with the F1
F2 buttons.
Press the
button to return to “Test run operation”.
Press the
button.
When the test run is completed, the “Test run menu” screen will appear. The test run will automatically stop after 2 hours.
Test run operation
Auto vane check
Press the button and open the Vane setting screen.
Function buttons
F1 F2 F3 F4
MENU RETURN SELECT ON/OFF
10-2-1. Test run for wired remote controller
Check the operation of the outdoor unit fan.
OCH607
19
F1 F2 F3 F4
Error information
Error code Error unit IU Ref. address Unt# Model name Serial No.
ResetPage
Error information
Contact information Dealer Tel
ResetPage
Reset error: Reset button
Reset error: Reset button
blinks
1
Check code, error unit, refrigerant address, unit model name, and serial number will appear.
The model name and serial number will appear only if the information has been registered.
Press the
F1
or
F2
button to go to the next page.
When an error occurs, the following screen will appear. Check the error status, stop the operation, and consult your dealer.
Contact information (dealer's phone number) will appear if the information has been registered.
F1 F2 F3 F4
F1 F2 F3 F4
Error information
Error reset
Error reset
Error code Error unit IU Ref. address Unt# Model name Serial No.
ResetPage
Reset current error?
Error reset
OKCancel
Main menu:
Reset error: Reset button
blinks
2
Press the
F4
button or the button to reset the error that is occurring.
Errors cannot be reset while the ON/OFF operation is prohibited.
Select "OK" with the
F4
button.
Navigating through the screens
• To go back to the Main menu ..........
button
<Error information>
OCH607
20
F1 F2 F3 F4
Main
Main display:
Cursor Page
Main menu
Restriction Energy saving Night setback Filter information Error information
blinks
While no errors are occurring, page 2/2 of the error information can be viewed by selecting "Error information" from the Main menu. Errors cannot be reset from this screen.
<Checking the error information>
<Error history>
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Test run Input maintenance info. Function setting Check Self check
Check menu
Cursor
Service menu:
Error history Refrigerant volume check Refrigerant leak check Smooth maintenance Request code
F1 F2 F3 F4
Error history
Page
Delete
Check menu:
Error Unt#
dd/mm/yy
Error history
Cancel OK
Delete error history?
Error history
Check menu:
Error history deleted
2
Select "Error history" with the F1 or F2 button, and press the button.
Select "Check" with the F1
or F2 button, and press the button.
3
Select "Error history" from the Check menu, and press the button to view up to 16 error history records.
4 records are shown per page, and the top record on the rst page indicates the latest error record.
Error history
4
To delete the error history, press the F4 button (Delete) on the screen that shows error history.
A conrmation screen will appear asking if you want to delete the error history.
Press the F4
button (OK) to delete the history.
"Error history deleted" will appear on the screen.
Press the
button to go back to the Check menu screen.
Deleting the error history
1
Select "Service" from the Main menu, and press the button.
OCH607
21
10-2-3. Start and finish of test run [For outdoor controller board]
Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation mode (cooling/heating) can be set up.
1Set the operation mode (cooling/heating) using SW4-2. 2Turn on SW4-1 to start test run with the operation mode set by SW4-2. 3Turn off SW4-1 to finish the test run.
There may be a faint knocking sound around the machine room after power is supplied.
However, this is not a problem with product because the linear expansion pipe is just mov­ing to adjust opening pulse.
There may be a knocking sound around the machine room for several seconds after com-
pressor starts operating. However, this is not a problem with product because the check valve itself generates the sound because pressure difference is small in the refrigerant circuit.
Note: The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1, change the operation mode and restart the test run by SW4-1.)
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
TEST
RUN
COOL
7
5
6
2
3,4
Test run [for IR wireless remote controller]
Measure an impedance between the power supply terminal block on the outdoor unit and ground with a 500 V Megger and check that it is equal to or greater than 1.0 M".
1 Turn on the main power to the unit. 2 Press the
TEST RUN
button twice continuously.
(Start this operation from the turned off status of remote controller
display.)
TEST RUN
and current operation mode are displayed.
3 Press the
MODE
( ) button to activate
COOL
mode, then
check whether cool air blows out from the unit.
4 Press the
MODE
( ) button to activate
HEAT
mode, then
check whether warm air blows out from the unit.
5 Press the
FAN
button and check whether strong air blows out
from the unit.
6 Press the
VANE
button and check whether the auto vane operates
properly.
7 Press the ON/OFF button to stop the test run.
Notes:
• Point the remote controller towards the indoor unit receiver
while following steps 2 to 7.
• It is not possible to run in FAN, DRY or AUTO mode.
OFF
1 2
ON
<SW4>
A B
C D
A Stop C Operation B Cooling D Heating
10-2-2. Test run for wireless remote controller
OCH607
22
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Test run Input maintenance info. Function setting Check Self check
kcehc fleS
:tceleS
Ref. address
sserddA
kcehc fleS
Ref. address
Return:
teseR
Error Unt # CI.prG
Self check
Return:
Reset
Ref. address
Error Grp.
--
-
Unt#
--
When there is no error history
Self check
Delete error history?
Ref. address
Cancel OK
Self check
Return:
Ref. address
Error history deleted
2
With theF1or
F2
button, enter the refrigerant address, and press the button.
Select "Self check" with the F1 or F2 button, and press the button.
1
Select "Service" from the Main menu, and press the button.
3
Check code, unit number, attribute will appear.
"-" will appear if no error history is available.
4
Resetting the error history.
Press the
F4
button (Reset) on the screen that shows the error history.
A conrmation screen will appear asking if you want to delete the error history.
Press the
F4
button (OK) to delete the error history.
If deletion fails, "Request rejected" will appear. "Unit not exist" will appear if no indoor units that are correspond to the entered address are found.
Navigating through the screens
• To go back to the Main menu ..........
button
• To return to the previous screen .......
button
10-3. HOW TO PROCEED "SELF-DIAGNOSIS"
10-3-1. Self-diagnosis
OCH607
23
If operations cannot be completed with the remote controller, diagnose the remote controller with this function.
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Maintenance password Remote controller check
F1 F2 F3 F4
Remote controller check
:nigeB
Start checking?
Remote controller check
:nigeB
Start checking?
1
Select "Service" from the Main menu, and press the button.
Select "Remote controller check" with the F1
or F2 button, and press
the
button.
2
Select "Remote controller check" from the Service menu, and press the but-
ton to start the remote controller check and see the check results.
To cancel the remote controller check and exit the "Remote controller check" menu screen, press the
or the button.
The remote controller will not reboot itself.
Check the remote controller display and see if anything is displayed (including lines). Nothing will appear on the remote controller display if the correct voltage (8.5–12 V DC) is not supplied to the remote control­ler. If this is the case, check the remote controller wiring and indoor units.
OK: No problems are found with the remote controller. Check other parts
for problems.
E3, 6832: There is noise on the transmission line, or the indoor unit or another
remote controller is faulty. Check the transmission line and the other remote controllers.
NG (ALL0, ALL1):
Send-receive circuit fault. The remote controller needs replac-
ing.
ERC:
The number of data errors is the discrepancy between the number of bits in the data transmitted from the remote controller and that of the data that was actually transmitted over the transmission line. If data errors are found, check the transmission line for external noise interfer
ence.
Remote controller check results screen
If the button is pressed after the remote controller check results are dis­played, remote controller check will end, and the remote controller will automati-
cally reboot itself.
10-3-2. Remote controller check
3
OCH607
24
• "CHECK" lights, and refrigerant address "00" blinks.
• Check that the remote controller's display has stopped before continuing.
• Select the refrigerant address of the indoor unit for the self-diagnosis. Note: Set refrigerant address using the outdoor unit’s DIP switch (SW1). (For more information, see the outdoor unit installation manual.)
• If an air conditioner error occurs, the indoor unit's sensor emits an intermit­ tent buzzer sound, the operation lamp blinks, and the check code is output. (It takes 3 seconds at most for check code to appear.)
• The check mode is cancelled.
[Procedure]
1. Press the CHECK button twice.
2. Press the TEMP buttons.
3. Point the remote controller at the sensor on the indoor unit and press the HOUR button.
4. Point the remote controller at the sensor on the indoor unit and press the ON/OFF button.
<Malfunction-diagnosis method at maintenance service>
10-3-4. Malfunction-diagnosis method by IR wireless remote controller
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK display
Temperature button
CHECK button
Refrigerant address display
HOUR button
ON/OFF button
OCH607
25
[Output pattern A] Errors detected by indoor unit
[Output pattern B]
E9
1. If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on, there are no error records.
2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 seconds)” after the initial 2 beeps to confirm the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION INDICATOR lamp blink pattern
Beep Beep Beep Beep Beep
Beep Beep
Off
Approx. 2.5 s
On
Approx. 3 s
On
0.5 sOn0.5 sOn0.5 s
On
0.5 s
Off
Approx. 2.5 sOnApprox. 3 sOn0.5 sOn0.5 s
··· Repeated
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
[Output pattern B]
OPERATION INDICATOR lamp blink pattern
Beep
Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sOn0.5 sOn0.5 s.On0.5 s
On
0.5 s
Off
Approx. 2.5 sOn0.5 sOn0.5 s
··· Repeated
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
Refer to the following tables for details on the check codes. [Output pattern A]
Notes:
*The check code in the parenthesis indicates PAR-30/31MAA model.
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
(Number of times)
IR wireless remote controller
Wired remote controller
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Symptom Remark
1
Indoor/outdoor unit communication error
2
(Transmitting error) (Outdoor unit)
3
Open/short of outdoor unit thermistors
4
Compressor overcurrent interruption (When compressor locked)
5
Abnormal high discharging temperature/49C worked/ insufficient refrigerant
6
Abnormal high pressure (63H worked)/Overheating protection operation
7
Abnormal temperature of heat sink
8
Outdoor unit fan protection stop
9
Compressor overcurrent interruption/Abnormal of power module
11
Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error
12
13
U2
U5
UP U3,U4 UF
U1,Ud (UD)*
U8 U6
U9,UH
Others
– –
– –
14
Other errors
For details, check the LED display of the outdoor controller board.
Compressor overcurrent interruption
Beeper sounds/OPERATION
INDICATOR lamp blinks 1 Check code
Symptom Remark
(Number of times)
IR wireless remote controller
Wired remote controller
1 P1
Intake sensor error
P9
Pipe (TH5) sensor error
2
P2
Pipe (TH2) sensor error
3 E6,E7
Indoor/outdoor unit communication error
4 P4
Drain sensor error/Float switch connector open
5
P5 PA
Drain pump error Forced compressor stop (due to water leakage abnormality)
6 P6
Freezing/Overheating protection operation
7 EE
Communication error between indoor and outdoor units
8 P8
Pipe temperature error
9 E4, E5
Remote controller signal receiving error
10
11
– –
12 14
Fb (FB)* PL
Indoor unit control system error (memory error, etc.) Refrigerant circuit abnormal
E0, E3
E1, E2
Remote controller control board error
Remote controller transmission error
As for indoor unit, refer to indoor unit's service manual.
OCH607
26
10-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
Check code
Abnormal point and detection method Case
Judgment and action
None
1 No voltage is supplied to termi-
nal block(TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or disconnec-
tion of power supply terminal
c) Open phase (L1 or L2
phase)
2 Electric power is not charged
to power supply terminal of outdoor power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board
Disconnection of connector TABT or TABS
3 Electric power is not supplied
to outdoor controller circuit board.
a) Disconnection of connector
(CNDC)
4 Disconnection of reactor (DCL)
5 Disconnection of outdoor noise
filter circuit board or parts fail­ure in outdoor noise filter circuit board It is especially needed to check the resistance RS1 on the noise filter circuit board.
6 Defective outdoor power circuit
board
7 Defective outdoor controller
circuit board
1 Check following items.
a) Power supply breaker b) Connection of power supply terminal
block (TB1)
c) Connection of power supply terminal
block (TB1)
2 Check following items.
a) Connection of power supply terminal
block (TB1)
b) Connection of terminal on outdoor
power circuit board Disconnection of connector TABT or TABS Refer to "10-9. TEST POINT DIAGRAM".
3 Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector, CNDC,
on the outdoor power circuit board. Refer to "10-9. TEST POINT DIAGRAM".
4 Check connection of reactor. (DCL)
Check connection of “L1” and “L2” on the
active filter module.(ACTM)
Refer to "10-9. TEST POINT DIAGRAM".
5 a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to "10-9. TEST POINT DIAGRAM".
6 Replace outdoor power circuit board.
7 Replace controller board (When items
above are checked but the units cannot be repaired).
F3
(5202)
63L connector open
Abnormal if 63L connector circuit is open for 3 minutes continuously after power supply.
63L: Low pressure switch
1 Disconnection or contact failure
of 63L connector on outdoor controller circuit board
2 Disconnection or contact failure
of 63L
3 63L is working due to refriger-
ant leakage or defective parts.
4 Defective outdoor controller circuit board
1 Check connection of 63L connector on outdoor controller circuit board. Refer to "10-9. TEST POINT DIAGRAM".
2 Check the 63L side of connecting wire.
3 Check refrigerant pressure.
Charge additional refrigerant. Check continuity by tester. Replace the parts if the parts are defective. 4 Replace outdoor controller circuit board.
Note: Refer to indoor unit section for the
codes starting with P and E.
OCH607
27
Check code
Abnormal point and detection method Judgment and action
Eb
(6845)
Miswiring of indoor/outdoor unit connecting wire (converse wiring or dis­connection)
Outdoor controller circuit board can automatically set the unit number of indoor units. Abnormal if the indoor unit number can­not be set within 4 minutes after power on because of miswiring (converse wiring or disconnection) of indoor/outdoor unit con­necting wire.
EC
(6846)
Startup time over
The unit cannot finish startup process within 4 minutes after power on.
Case
1 Contact failure of indoor/ outdoor unit connecting wire 2 Diameter or length of indoor/
outdoor unit connecting wire is out of specified capacity.
7 2 or more outdoor units have
refrigerant address “0”.
(In case of group control) 8 Noise has entered into power
supply or indoor/outdoor unit connecting wire.
1 Contact failure or miswiring of
indoor/outdoor unit connecting wire
2 Diameter or length of indoor/
outdoor unit connecting wire is out of specified capacity.
4 Defective transmitting receiving
circuit of outdoor controller circuit board
5 Defective transmitting receiving
circuit of indoor controller board
6 Defective indoor power board 7 2 or more outdoor units have
refrigerant address “0” .
(In case of group control) 8 Noise has entered into power
supply or indoor/outdoor unit connecting wire.
Indoor/outdoor unit connector miswiring, excessive number of units (4 units or more)
1. Outdoor controller circuit board can automatically check the number of
connected indoor units. Abnormal if the
number cannot be checked automati­cally due to miswiring of indoor/outdoor unit connecting wire, etc. after power is turned on for 4 minutes.
2. Abnormal if outdoor controller circuit board recognizes the number of
connected indoor units as “4 units or
more”.
1 Check disconnection or looseness or polar-
ity of indoor/outdoor unit connecting wire of indoor and outdoor units.
2 Check diameter and length of indoor/outdoor
unit connecting wire. Total wiring length: 262 ft [80 m] (including wiring connecting each indoor unit
and between indoor and outdoor unit) Also check if the connection order of flat
cable is S1, S2, S3.
3 Check the number of indoor units that are
connected to one outdoor unit. (If EA is
detected)
46 Turn the power off once, and on again to check. Replace outdoor controller circuit board, indoor controller board or indoor power board if abnormality occurs again.
7 Check if refrigerant addresses (SW1-3 to
SW1-6 on outdoor controller circuit board)
are overlapping in case of group control system.
8 Check transmission path, and remove the
cause.
Note: The descriptions above 1–8 are for EA,
Eb and EC.
1 Contact failure or miswiring of
indoor/outdoor unit connecting wire
2 Diameter or length of indoor/
outdoor unit connecting wire is out of specified capacity.
3 4 or more indoor units are connected to 1 outdoor unit. 4 Defective transmitting receiving
circuit of outdoor controller
circuit board 5 Defective transmitting receiving
circuit of indoor controller board
6 Defective indoor power board 7 2 or more outdoor units have
refrigerant address “0”.
(In case of group control) 8 Noise has entered into power supply or indoor/outdoor unit connecting wire.
EA
(6844)
F5
(5201)
63H connector open
Abnormal if 63H connector circuit is open for 3 minutes continuously after power supply.
63H: High pressure switch
1 Disconnection or contact failure
of 63H connector on outdoor controller circuit board
2 Disconnection or contact failure
of 63H
3 63H is working due to defective
parts.
4 Defective outdoor controller circuit board
1 Check connection of 63H connector on outdoor controller circuit board. Refer to "10-9. TEST POINT DIAGRAM".
2 Check the 63H side of connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective. 4 Replace outdoor controller circuit board.
F9
(4119)
2 connector open
Abnormal if both 63H and 63L connector circuits are open for 3 minutes continuously after power supply.
63H: High pressure switch 63L: Low pressure switch
1 Disconnection or contact failure
of connector (63H,63L) on
outdoor controller circuit board. 2 Disconnection or contact failure
of 63H, 63L
3 63H and 63L are working due
to defective parts.
4 Defective outdoor controller
board
1 Check connection of connector (63H,63L) on outdoor controller circuit board. Refer to "10-9. TEST POINT DIAGRAM". 2 Check the 63H and 63L side of connecting
wire. 3 Check continuity by tester. Replace the parts if the parts are defective. 4 Replace outdoor controller circuit board.
OCH607
28
<Abnormalities detected while unit is operating>
Check code
Abnormal point and detection method Judgment and action
U1
(1302)
High pressure (High-pressure switch 63H worked)
Abnormal if high-pressure switch 63H worked (*) during compressor operation. *602 PSIG [4.15 MPa]
63H: High pressure switch
1 Short cycle of indoor unit 2 Clogged filter of indoor unit 3 Decreased airflow caused by
dirt of indoor fan
4 Dirt of indoor heat exchanger 5 Locked indoor fan motor 6 Malfunction of indoor fan motor 7 Defective operation of stop
valve (Not full open)
8 Clogged or broken pipe 9 Locked outdoor fan motor
0 Malfunction of outdoor fan
motor
1 Short cycle of outdoor unit 2 Dirt of outdoor heat exchanger 3 Decreased airflow caused by
defective inspection of outside temperature thermistor
(It detects lower temperature
than actual temperature.)
4 Disconnection or contact failure
of connector (63H) on outdoor controller board
5 Disconnection or contact failure
of 63H connection
6 Defective outdoor controller
board
7 Defective action of linear
expansion valve
8 Malfunction of fan driving circuit
1–6 Check indoor unit and repair defect.
7 Check if stop valve is fully open.
8 Check piping and repair defect. 9–2 Check outdoor unit and repair defect.
3 Check the detected temperature of outside
temperature thermistor on LED display.
(SW2 on A-Control Service Tool : Refer
to "10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS". )
46 Turn the power off and check F5 is displayed when the power is on again. When F5 is displayed, refer to “Judgment
and action” for F5.
7 Check linear expansion valve. Refer to "10-6. HOW TO CHECK THE
PARTS".
8 Replace outdoor controller board.
Case
U2
(1102)
High discharge temperature
(1) Abnormal if discharge temperature thermistor (TH4) exceeds 257˚F [125:] or 230˚F [110:] continuously for 5 minutes. Abnormal if condenser/evaporator temperature thermistor (TH5) exceeds 104˚F [40:] during defrosting and discharge temperature thermistor (TH4) exceeds 230˚F [110:].
(2) Abnormal if discharge superheat (Cooling: TH4−TH5/Heating: TH4−TH6) exceeds 126˚F [70:].
1 Overheated compressor opera-
tion caused by shortage of refrigerant
2 Defective operation of stop
valve
3 Defective thermistor 4 Defective outdoor controller
board
5 Defective action of linear
expansion valve
6 Clogging with foreign objects in
refrigerant circuit.
Note: logging occurs in the parts
which become below freezing point when water enters in the refrigerant circuit.
1 Check intake superheat. Check leakage of refrigerant. Charge additional refrigerant.
2 Check if stop valve is fully open.
34 Turn the power off and check if U3 is dis-
played when the power is on again.
When U3 is displayed, refer to “Judgment
and action” for U3.
5 Check linear expansion valve. Refer to "10-6. HOW TO CHECK THE
PARTS".
6 After recovering refrigerant, remove water
from entire refrigerant circuit under vacuum more than 1 hour.
<Abnormalities detected while unit is operating>
U3
(5104)
Open/short circuit of discharge temperature thermistor (TH4)
Abnormal if open (37˚F [3:] or less) or short (422˚F [217:] or more) is detected during compressor operation. (Detection is inoperative for 10 minutes of compressor starting process and for 10 minutes after and during defrosting.)
1 Disconnection or contact failure
of connector (TH4) on the out­door controller circuit board
2 Defective thermistor 3 Defective outdoor controller cir-
cuit board
1 Check connection of connector (TH4) on the
outdoor controller circuit board.
Check breaking of the lead wire for ther-
mistor (TH4). Refer to "10-9. TEST POINT DIAGRAM".
2 Check resistance value of thermistor
(TH4) or temperature by microcomputer. (Thermistor/TH4: Refer to "10-6. HOW TO CHECK THE PARTS".) (SW2 on A-Control Service Tool: Refer to "10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS".)
3 Replace outdoor controller board.
OCH607
29
Thermistors
Open detection Short detection
Symbol Name
TH3,TH32,TH33
TH6 TH7 TH8
40°F [40:] or below
40°F [40:] or below
40°F [40:] or below
17°F [27:] or below
194°F [90:] or above 194°F [90:] or above 194°F [90:] or above
216°F [102:] or above
Thermistor <Liquid>, <Suction>, <Ref. check>
Thermistor <2-phase pipe>
Thermistor <Ambient>
Thermistor <Heat sink>
Check code
Abnormal point and detection method Case Judgment and action
U5
(4230)
Temperature of heat sink
Abnormal if heat sink thermistor (TH8) detects temperature indicated below. HA30, 36 ······························ 183˚F [84:]
1 The outdoor fan motor is
locked.
2 Failure of outdoor fan motor 3 Air flow path is clogged. 4 Rise of ambient temperature 5 Defective thermistor 6 Defective input circuit of out-
door power circuit board
7 Failure of outdoor fan drive cir-
cuit
12 Check outdoor fan.
3 Check air flow path for cooling. 4 Check if there is something which causes
temperature rise around outdoor unit. (Upper limit of ambient temperature is 114˚F [46:].) Turn off power, and on again to check if U5 is displayed within 30 minutes. If U4 is displayed instead of U5, follow the action to be taken for U4.
5 Check resistance value of thermistor (TH8)
or temperature by microcomputer. (Thermistor/TH8: Refer to "10-6. HOW TO CHECK THE PARTS".) (SW2 on A-Control Service Tool: Refer to "10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS".)
6 Replace outdoor power circuit board. 7 Replace outdoor controller circuit board.
U4,
TH32, TH33
(TH3:5105) (TH6:5107) (TH7:5106) (TH8:5110)
Open/short of outdoor unit thermistors (TH3, TH32, TH33, TH6, TH7, and TH8)
Abnormal if open or short is detected dur­ing compressor operation. Open detection of thermistors TH3,TH32,TH33 and TH6 is inoperative for 10 seconds to 10 minutes after compressor starting and 10 minutes after and during defrosting.
Note: Check which unit has abnormality in
its thermistor by switching the mode of SW2. (PAC-SK52ST) (Refer to "10-10. FUNCTION OF SWITCHES,
CONNECTORS AND JUMPERS".)
1 Check connection of connector
(TH3,TH,32,TH33,TH7/6) on the outdoor controller circuit board. Check connection of connector (CN3) on the outdoor power circuit board. Check breaking of the lead wire for thermistor (TH3,TH32,TH33,TH6,TH7,TH8). Refer to "10-9. TEST POINT DIAGRAM".
2 Check resistance value of thermistor
(TH3,TH32,TH33,TH6,TH7,TH8) or check temperature by microprocessor. (Thermistor/ TH3,TH6,TH7,TH8: Refer to "10-6. HOW TO CHECK THE PARTS".) (SW2 on A-Control Service Tool: Refer to "10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS".)
3 Replace outdoor controller circuit board.
Note: Emergency operation is available in case
of abnormalities of TH3,TH32,TH33,TH6 and TH7. Refer to "10-8. EMERGENCY OPERATION".
U6
(4250)
Power module
Check abnormality by driving power mod­ule in case overcurrent is detected. (UF or UP error condition)
1 Outdoor stop valve is closed. 2
Decrease of power supply voltage
3 Looseness, disconnection or
converse of compressor wiring connection
4 Defective compressor 5 Defective outdoor power circuit
board
1 Open stop valve. 2 Check facility of power supply. 3 Correct the wiring (U·V·W phase) to com-
pressor. Refer to "10-9. TEST POINT DIAGRAM" (Outdoor power circuit board).
4 Check compressor referring to "10-6. HOW
TO CHECK THE PARTS".
5 Replace outdoor power circuit board.
1 Disconnection or contact failure
of connectors Outdoor controller circuit board: TH3, TH32, TH33,TH7/TH6 Outdoor power circuit board:
CN3
2 Defective thermistor 3 Defective outdoor controller cir-
cuit board
(
(
U7
(1520)
Too low superheat due to low discharge temperature
Abnormal if discharge superheat is con­tinuously detected less than or equal to 5˚F[−15˚C] for 3 minutes even though lin­ear expansion valve has minimum open pulse after compressor starts operating for 10 minutes.
1 Disconnection or loose connec-
tion of discharge temperature thermistor (TH4)
2 Defective holder of discharge
temperature thermistor
3 Disconnection or loose connection
of linear expansion valve’s coil
4 Disconnection or loose connec-
tion of linear expansion valve’s connector
5 Defective linear expansion valve
12 Check the installation conditions of dis-
charge temperature thermistor (TH4).
3 Check the coil of linear expansion valve. Refer to "10-7. HOW TO CHECK THE
COMPONENTS".
4 Check the connection or contact of LEV-A and
LEV-B on outdoor controller circuit board.
5 Check linear expansion valve. Refer to "10-6.
HOW TO CHECK THE PARTS".
OCH607
30
Check code
Abnormal point and detection method Case Judgment and action
U8
(4400)
Outdoor fan motor
The outdoor fan motor is considered to be abnormal if the rotational frequency of fan motor is abnormal when detected during operation. Fan motor rotational frequency is abnor­ mal if;
• 100 rpm or below detected continuously for 15 seconds at 68˚F [20:] or more outside air temperature
• 50 rpm or below or 1500 rpm or more detected continuously for 1 minute.
1 Failure in the operation of the
DC fan motor
2 Failure in the outdoor circuit
controller board
1 Check or replace the DC fan motor.
2 Check the voltage of the outdoor circuit con-
troller board during operation.
3 Replace the outdoor circuit controller board.
(when the failure is still indicated even after performing the remedy 1 above.)
U9
(4220)
To find out the detail history (latest) about U9 error, turn ON SW2-1, 2-2 and 2-6. Refer to "10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS".
1 Check the field facility for the power supply. 2 Correct the wiring (U.V.W phase) to
compressor.
Refer to "10-9. TEST POINT
DIAGRAM" (Outdoor power circuit board).
3 Replace outdoor power circuit board. 4 Check compressor for electrical insulation.
Replace compressor.
1 Decrease in power source voltage, instantaneous stop. 2 Disconnection or loose
connection of CN52C on the outdoor power circuit board/ controller circuit board
3 Defective converter drive circuit
in outdoor power circuit board
4 Defective 52C drive circuit in
outdoor power circuit board
5 Disconnection or loose
connection of CN2 on the outdoor power circuit board/ controller circuit board
6 Power circuit failure on DC
supply for 18 V DC output on outdoor controller circuit board
04
Input current sensor error/ L1-phase open error
• Decrease in input current through outdoor unit to 0.1 A only if operation frequency is more than or equal to 40 Hz or compressor current is more than or equal to 6 A.
1 Defective input current detection
circuit in outdoor power circuit board
2 Defective outdoor controller
circuit board
1 Replace outdoor power circuit board.
2 Replace outdoor controller circuit board.
Detailed
codes
01
Overvoltage error
• Increase in DC bus voltage to 400 V
1 Abnormal increase in power source voltage 2
Disconnection of compressor
wiring 3 Defective outdoor power circuit board 4 Compressor has a ground fault.
02
Undervoltage error
• Instantaneous decrease in DC bus voltage to 200 V
1 Check the field facility for the power supply. 2 Check CN52C wiring.
3 Replace outdoor power circuit board.
4 Replace outdoor power circuit board.
5 Check CN2 wiring.
6 Replace outdoor controller circuit board.
20
PFC/IGBT error (Undervoltage)
• When compressor is running, DC bus voltage stays at 310 V or lower for consecutive 10 seconds
1 Incorrect switch settings on the
outdoor controller circuit board for model select
2 Defective outdoor power circuit
board
3 Defective outdoor controller
circuit board
1 Correction of a model select
2 Replace outdoor power circuit board.
3 Replace outdoor controller circuit board.
OCH607
31
UH
(5300)
Current sensor error
Abnormal if current sensor detects −1.5A
to 1.5A during compressor operation. (This error is ignored in case of test run mode.)
1 Disconnection of compressor
wiring
2 Defective circuit of current sen-
sor on outdoor power circuit board
1 Correct the wiring (U·V·W phase) to compres-
sor. Refer to "10-9. TEST POINT DIAGRAM" (Outdoor power circuit board).
2 Replace outdoor power circuit board.
UF
(4100)
Compressor overcurrent interruption (When compressor locked)
Abnormal if overcurrent of DC bus or compressor is detected within 30 seconds after compressor starts operating.
1 Stop valve is closed. 2 Decrease of power supply volt-
age
3 Looseness, disconnection or
converse of compressor wiring connection
4 Defective compressor
5 Defective outdoor power board
1 Open stop valve. 2 Check facility of power supply.
3 Correct the wiring (U·V·W phase) to compres-
sor.
Refer to "10-9. TEST POINT DIAGRAM"
(Outdoor power circuit board).
4 Check compressor. Refer to "10-6. HOW TO
CHECK THE PARTS".
5 Replace outdoor power circuit board.
Ud
(1504)
Overheat protection
Abnormal if outdoor pipe thermistor (TH3) detects 158˚F [70:] or more during com­pressor operation.
1 Defective outdoor fan (fan
motor) or short cycle of out­door unit during cooling opera­tion
2 Defective outdoor pipe ther-
mistor (TH3)
1 Check outdoor unit air passage.
23 Turn the power off and on again to check
the check code. If U4 is displayed, follow the U4 processing direction.
Check code
Abnormal point and detection method
Case Judgment and action
UL
(1300)
Abnormal low pressure (63L worked)
Abnormal if 63L is worked (under −4 PSIG [−0.03 MPa]) during compressor operation.
63L: Low pressure switch
1 Stop valve of outdoor unit is
closed during operation.
2 Disconnection or loose con-
nection of connector (63L) on outdoor controller board
3 Disconnection or loose connec-
tion of 63L
4 Defective outdoor controller
board
5 Leakage or shortage of refriger-
ant
6 Malfunction of linear expansion
valve
1 Check stop valve.
2–4 Turn the power off and on again to check
if F3 is displayed on restarting. If F3 is displayed, follow the F3 process-
ing direction.
5 Correct to proper amount of refrigerant. 6 Check linear expansion valve. Refer to "10-6.
HOW TO CHECK THE PARTS".
UP
(4210)
Compressor overcurrent interruption
Abnormal if overcurrent DC bus or com­pressor is detected after compressor starts operating for 30 seconds.
1 Stop valve of outdoor unit is
closed.
2 Decrease of power supply volt-
age
3 Looseness, disconnection or
converse of compressor wiring connection
4 Defective fan of indoor/outdoor
units
5 Short cycle of indoor/outdoor
units
6 Defective input circuit of out-
door controller board
7 Defective compressor
1 Open stop valve.
2 Check facility of power supply.
3 Correct the wiring (U·V·W phase) to com-
pressor. Refer to "10-9. TEST POINT DIAGRAM" (Outdoor power circuit board).
4 Check indoor/outdoor fan. 5 Solve short cycle. 6 Replace outdoor controller circuit board. 7 Check compressor. Refer to "10-6. HOW TO
CHECK THE PARTS".
Note: Before the replacement of the outdoor
controller circuit board, disconnect the wiring to compressor from the outdoor power circuit board and check the output voltage among phases, U, V, W, during test run. No defect on board if voltage among phases (U-V, V-W and W-U) is same. Make sure to perform the voltage check with same performing frequency.
OCH607
32
Check code
Abnormal point and detection method Judgment and actionCase
E0
or
E4
(6831
or
6834)
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote control-
ler cannot receive normally any trans­mission from indoor unit of refrigerant address “0” for 3 minutes.
(Check code: E0) 2 Abnormal if sub-remote controller could
not receive any signal for 2 minutes. (Check code: E0)
1 Abnormal if indoor controller board can
not receive any data normally from remote controller board or from other indoor controller board for 3 minutes. (Check code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for 2 minutes. (Check code: E4)
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”. If there is no problem with the action above. 3 Check wiring of remote controller.
Total wiring length: maximum 1640 ft [500 m]
(Do not use cable o 3 or more.)
• The number of connecting indoor units: maximum 16 units
• The number of connecting remote control­ler: maximum 2 units
If the cause of trouble is not any of 1–3 above, 4 Diagnose remote controllers.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-06” is dis-
played, noise may be causing abnormality.
Note: If the unit is not normal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
3 Miswiring of remote controller 4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiv-
ing circuit of indoor controller board of refrigerant address “0”.
6 Noise has entered into the
transmission wire of remote controller.
E1
or
E2
Remote controller control board
1 Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the remote controller control board.
(Check code: E1)
2 Abnormal if the clock function of remote
controller cannot be operated normally. (Check code: E2)
1 Defective remote controller 1 Replace remote controller.
E3
or
E5
(6832
or
6833)
Remote controller transmission error (E3)/signal receiving error (E5)
1 Abnormal if remote controller could not
find blank of transmission path for 6 sec­onds and could not transmit.
(Check code: E3) 2 Remote controller receives transmitted
data at the same time, compares the
data, and when detecting it, judges different data to be abnormal 30 continuous times. (Check code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path. (Check code: E5) 2 Indoor controller board receives trans-
mitted data at the same time, compares
the data, and when detecting it, judges
different data to be abnormal 30 continuous times. (Check code: E5)
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4–6 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem. Turn the power off, and on again to check. When becoming abnormal again, replace
indoor controller board. b) When “RC NG” is displayed, replace
remote controller. c)
When “RC E3”or “ERC 00-66” is dis-
played, noise may be causing abnormality.
1 2 remote controllers are set as
“main.” (In case of 2 remote controllers)
2 Remote controller is connected
with 2 indoor units or more.
3 Repetition of refrigerant
address
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
6 Noise has entered into trans-
mission wire of remote control­ler.
OCH607
33
Check code
Abnormal point and detection method Judgment and action
E9
(6841)
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
1 Abnormal if “0” receiving is detected 30
times continuously though outdoor con­troller circuit board has transmitted “1”.
2 Abnormal if outdoor controller circuit
board could not find blank of transmis­sion path for 3 minutes.
1 Indoor/outdoor unit connecting
wire has contact failure.
2 Defective communication cir-
cuit of outdoor controller circuit board
3
Noise has entered power supply.
4 Noise has entered indoor/ out-
door unit connecting wire.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire.
24 Turn the power off, and on again to
check. Replace outdoor controller circuit board if abnormality is displayed again.
EF
(6607
or
6608)
Non-defined check code
This code is displayed when non-defined check code is received.
1 Noise has entered transmission
wire of remote controller.
2 Noise has entered indoor/ out-
door unit connecting wire.
3 Outdoor unit is not inverter
model.
12 Turn the power off, and on again to check.
Replace indoor controller board or outdoor controller circuit board if abnormality is dis­played again.
3 Replace outdoor unit with inverter model.
Case
E8
(6840)
Indoor/outdoor unit communication error (Signal receiving error) (Outdoor unit)
Abnormal if outdoor controller circuit board could not receive anything normally for 3 minutes.
1 Contact failure of indoor/out-
door unit connecting wire
2 Defective communication cir-
cuit of outdoor controller circuit board
3 Defective communication circuit
of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor or out­door units.
24 Turn the power off, and on again to
check. Replace indoor controller board or outdoor controller circuit board if abnor­mality is displayed again.
E6
(6840)
Indoor/outdoor unit communication error (Signal receiving error)
1 Abnormal if indoor controller board could
not receive any signal normally for 6 minutes after turning the power on.
2 Abnormal if indoor controller board could
not receive any signal normally for 3 minutes.
3 Consider the unit as abnormal under
the following condition; When 2 or more indoor units are connected to an out­door unit, indoor controller board could not receive a signal for 3 minutes from outdoor controller circuit board, a signal which allows outdoor controller circuit board to transmit signals.
Note: Check LED display on outdoor controller
circuit board. (Connect A-Control service tool (PAC-SG50ST))
Refer to EA–EC item if LED displays EA–AC.
1 Check disconnecting or looseness of indoor/
outdoor unit connecting wire of indoor unit or outdoor unit.
Check all the units in case of twin indoor unit
system.
24
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor
controller circuit board. 5 Turn the power off, and detach fan motor
from connector (CNF1,2). Then turn the power on again.
If abnormality is not displayed, replace fan
motor.
If abnormality is displayed, replace outdoor
controller circuit board.
6
Check RS1 on outdoor noise filter board with tester. If open is detected, replace the board .
Note: Other indoor controller board may have
defect in case of twin indoor unit system.
1 Contact failure, short circuit or
miswiring (converse wiring) of indoor/outdoor unit connecting wire
2 Defective transmitting receiv-
ing circuit of outdoor controller circuit board.
3 Defective transmitting receiv-
ing circuit of indoor controller board.
4 Noise has entered into indoor/
outdoor unit connecting wire.
5 Defective fan motor 6 Defective rush current resistor
OCH607
34
P8
1 Slight temperature difference
between indoor room tempera­ture and pipe <liquid or con­denser/evaporator> tempera­ture thermistor
• Shortage of refrigerant
• Disconnected holder of pipe <liquid or condenser/
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of exten-
sion pipe (on plural units con­nection)
3 Converse wiring of indoor/ outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe <condenser/evaporator>
temperature thermistor 5 Stop valve is not opened com-
pletely.
Pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes after compressor start and 6 minutes after the liquid or condenser/evaporator pipe is out of cooling range. Note 1:
It takes at least 9 minutes to detect
.
Note 2: Abnormality P8 is not detected in
drying mode.
Cooling range : Indoor pipe temperature
(TH2 or TH5) – room temperature (TH1) [ −5.4˚F [−3:]
TH: Lower temperature between liquid pipe
temperature and condenser/
evaporator temperature
<Heating mode> When 10 seconds have passed after the compressor starts operation and the hot adjustment mode has finished, the unit is detected as abnormal when condenser/ evaporator pipe temperature is not in heat­ing range within 20 minutes.
Note 3: It takes at least 27 minutes to
detect abnormality.
Note 4: It excludes the period of defrosting
(Detection restarts when defrosting mode is over)
Heating range: 5.4˚F [3:] [ (Condenser/
Evaporator temperature(TH5)− room temperature(TH1))
14 Check pipe <liquid or condenser/ evaporator> temperature with room tem-
perature display on remote controller and
outdoor controller circuit board. Pipe <liquid or condenser/evaporator> temperature display is indicated by setting SW2 of outdoor controller circuit board as follows.
Conduct temperature check with outdoor controller circuit board after connecting ‘A-Control Service Tool(PAC-SK52ST)’.
23 Check converse connection of extension pipe or converse wiring of indoor/outdoor unit connecting wire.
(
)
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 234 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
A-Control Service Tool SW2 setting
Temperature display of indoor liquid pipe Indoor 1
Temperature display of indoor liquid pipe Indoor 2
Temperature display of indoor condenser/ evaporator pipe Indoor 1
Temperature display of indoor condenser/ evaporator pipe Indoor 2
Check code
Abnormal point and detection method Judgment and actionCase
Ed
(0403)
Serial communication error
1. Abnormal if serial communication between outdoor controller circuit board and outdoor power circuit board is defec­tive.
1 Breaking of wire or contact failure of connector CN2
between the outdoor controller circuit board and the outdoor power circuit board
2 Breaking of wire or contact failure of connector CN4
between the outdoor controller circuit board and the outdoor power circuit board
3 Defective communication circuit
of outdoor power circuit board
4 Defective communication cir-
cuit of outdoor controller circuit board for outdoor power circuit board
12 Check connection of each connector CN2
and CN4 between the outdoor controller circuit board and the outdoor power circuit board.
3 Replace outdoor power circuit board.
4 Replace outdoor controller circuit board.
1 Breaking of wire or contact
failure of connector between
outdoor controller circuit board and M-NET board
2 Contact failure of M-NET board
power supply line
3 Noise has entered into M-NET
transmission wire.
2. Abnormal if communication between out­door controller circuit board and M-NET board is not available.
1
Check disconnection, looseness, or breaking of connection wire between outdoor controller cir­cuit board (CNMNT) and M-NET board (CN5)
.
2
Check disconnection, looseness, or breaking of connection wire between outdoor controller cir­cuit board (CNMNT) and M-NET board (CND)
.
3 Check M-NET transmission wiring method.
OCH607
35
Check Code
Abnormal point and detection method Case Judgment and action
A0
(6600)
Address duplicate definition
This error is displayed when transmission from the units of same address is detected. Note: The address and attribute displayed
at remote controller indicate the con­troller that detected abnormality.
1 There are 2 or more same
address of controller of out­door unit, indoor unit, FRESH MASTER, or LOSSNAY.
2 Noise has entered into trans-
mission signal and signal was transformed.
Search the unit with same address as abnormali­ty occurred. If the same address is found, turn off the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for 2 minutes or more after the address is corrected, and turn the power on again. Check transmission waveform or noise on trans­mission wire.
A2
(6602)
Hardware error of transmission processor
Transmission processor intended to trans­mit “0”, but “1” appeared on transmission wire. Note: The address and attribute display at
remote controller indicate the con­troller that detected abnormality.
1 Error is detected if waveform is
transformed when wiring works of transmission wire of out­door unit, indoor unit, FRESH MASTER or LOSSNAY are done, or polarity is changed with the power on and transmis­sion data collide each other.
2 Defective transmitting receiving
circuit of transmission processor
3 Transmission data is changed
by the noise on transmission.
1 If the works of transmission wire is done
with the power on, turn off the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for 2 minutes or more, and turn the power on again.
2 Check transmission waveform or noise on
transmission wire.
A3
(6603)
BUS BUSY
1. Overtime error by collision damage Abnormal if transmitting signal is not
possible for 8 to 10 minutes continuously because of collision of transmission.
2. Data could not reach transmission wire for 8 to 10 minutes continuously because of noise, etc.
Note: The address and attribute displayed
at remote controller indicate the con­troller that detected abnormality.
1 Transmission processor could
not transmit signal because short cycle voltage of noise and the like have entered into transmission wire continuously.
2 Transmission quantity has
increased and transmission is not possible because there was wiring mistake of terminal block for transmission wire (TB3) and terminal block for central con­trol (TB7) in outdoor unit.
3 Transmission are mixed with others and occupation rate on
transmission wire rose because of defective repeater (a func­tion to connector or disconnect transmission of control and central control system) of out­door unit, then abnormality is detected.
1 Check if transmission wire of indoor unit,
FRESH MASTER, LOSSNAY, or remote controller is not connected to terminal block for central control (TB7) of outdoor unit.
2 Check if transmission wire of indoor unit,
FRESH MASTER or LOSSNAY is not con­nected to terminal block for transmission wire of outdoor unit.
3 Check if terminal block for transmission wire
(TB3) and terminal block for central control (TB7) is not connected.
4 Check transmission waveform or noise on
transmission wire.
<M-NET communication error> Note: “Indoor unit” in the text indicates M-NET board in outdoor unit.
A6
(6606)
Communication error with communica­tion processor
Defective communication between unit processor and transmission processor Note: The address and attribute display at
remote controller indicate the con­troller that detected abnormality.
1 Data of transmission proces-
sor or unit processor is not transmitted normally because of accidental trouble such as noise or thunder surge.
2 Address forwarding from unit
processor is not transmitted normally because of defective transmission processor hard­ware.
Turn off the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for 2 minutes or more, and turn the power on again. System returns to normal if abnormality was accidental malfunc­tion. If the same abnormality generates again, abnormality-generated controller may be defec­tive.
OCH607
36
Continued to the next page.
Check
Code
Abnormal point and detection method Case Judgment and action
A7
(6607)
NO ACK signal
1. Transmitting side controller detects abnormal if a message was transmitted but there is no reply (ACK) that a mes­sage was received. Transmitting side detects abnormality every 30 seconds, 6 times continuously.
Note: The address and attribute displayed
at remote controller is indicate the controller that did not reply (ACK).
Common factor that has no rela­tion with abnormality source. 1 The unit of former address
does not exist as address switch has changed while the unit was energized.
2 Extinction of transmission wire
voltage and signal is caused by over-range transmission wire.
• Maximum distance���� 656 ft [200 m]
• Remote controller line (39 ft [12 m])
3 Extinction of transmission wire
voltage and signal is caused by type-unmatched transmis­sion wire. Type����
With shield wire­ CVVS, CPEVS With normal wire (no shield)­ VCTF, VCTFK, CVV CVS, VVR, VVF, VCT
Diameter����
AWG16 [1.25 mm2]
or more
4 Extinction of transmission wire
voltage and signal is caused by over-numbered units.
5 Accidental malfunction of
abnormality-detected controller (noise, thunder surge)
6 Defective of abnormality gen-
erated controller
2. If displayed address or attribute is out­door unit, indoor unit detects abnormality when indoor unit transmitted to outdoor unit and there was no reply (ACK).
1
Contact failure of transmission wire of outdoor unit or indoor unit
2 Disconnection of transmission
connector (CN2M) of outdoor unit
3 Defective transmitting receiving
circuit of outdoor unit or indoor unit
Always try the following when the error “A7” occurs.
1 Turn off the power supply of outdoor unit
and indoor unit and FRESH MASTER or LOSSNAY at the same time for 2 minutes or more, and turn the power on again. If mal­function was accidental, the unit returns to normal.
2 Check address switch of abnormality gener-
ated address.
3 Check disconnection or looseness of abnor-
mality generated or abnormality detected transmission wire (terminal block and con­nector)
4 Check if tolerance range of transmission wire
is not exceeded.
5 Check if type of transmission wire is correct
or not.
If the cause of trouble is in 1–5, repair the defective, then turn off the power supply of out­door unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for 2 minutes or more, and turn the power on again.
• If there was no trouble with 1–5 above in
single refrigerant system (one outdoor unit), controller of displayed address or attribute is defective.
• If there was no trouble with 1–5 above in dif-
ferent refrigerant system (2 or more outdoor units), judge with 6.
6 If address of abnormality source is the
address that should not exist, there is the unit that memorizes nonexistent address information. Delete useless address informa­tion with manual setting function of remote controller.
Only the system FRESH MASTER or
LOSSNAY are connected to, or the system that is equipped with group setting of differ­ent refrigerant system.
If the cause of trouble is not any of 1-6 above, replace the controller board of displayed address or attribute. If the unit does not return to normal, multi-con­troller board of outdoor unit may be defective (repeater circuit). Replace multi-controller board one by one to check if the unit returns to normal.
3. If displayed address or attribute is indoor unit, remote controller detects abnormal­ity when remote controller transmitted to indoor unit and there was no reply (ACK).
1 During group operation with
indoor unit of multi- refrigerant system, if remote controller transmit to indoor unit while outdoor unit power supply of one refrigerant system is turned off or within 2 min­utes of restart, abnormality is detected.
2 Contact failure of transmission
wire of remote controller or indoor unit
3
Disconnection of transmission connector (CN2M) of indoor unit
4 Defective transmitting receiving
circuit of indoor unit or remote controller
OCH607
37
5. If displayed address or attribute is FRESH MASTER, indoor unit detects abnormality when indoor unit transmitted to FRESH MASTER and there was no reply (ACK).
1 During sequential operation
of indoor unit and FRESH MASTER of other refrigerant system, if indoor unit transmits to FRESH MASTER while outdoor unit power supply of same refrigerant system with FRESH MASTER is turned off or within 2 minutes of restart, abnormality is detected.
2 Contact failure of transmission
wire of indoor unit or FRESH MASTER
3 Disconnection of transmission
connector (CN2M) of indoor unit or FRESH MASTER
4 Defective transmitting receiving
circuit of indoor unit or FRESH MASTER
Check Code
Abnormal point and detection method Case Judgment and action
A7
(6607)
6. If displayed address or attribute is LOSSNAY, indoor unit detects abnor­mality when indoor unit transmitted to LOSSNAY and there was no reply (ACK).
1 If the power supply of
LOSSNAY is off, indoor unit detects abnormality when it transmits to LOSSNAY.
2 During sequential operation
of indoor unit and LOSSNAY of other refrigerant system, if indoor unit transmits to LOSSNAY while outdoor unit power supply of same refriger­ant system with LOSSNAY is turn off or within 2 minutes of restart, abnormality is detected.
3 Contact failure of transmis-
sion wire of indoor unit of LOSSNAY
4 Disconnection of transmission
connector (CN2M) of indoor unit
5 Defective transmitting receiv-
ing circuit of indoor unit or LOSSNAY
7. If displayed address or attribute is non­existent,
1 The unit of former address
does not exist as address switch has changed while the unit was energized.
2 Abnormality is detected
when indoor unit transmit­ted because the address of FRESH MASTER and LOSSNAY are changed after sequential operation of FRESH MASTER and LOSSNAY by remote controller.
From the previous page.
4. If displayed address or attribute is
remote controller,
Indoor unit detects abnormality when
indoor unit transmitted to remote control­ler and there was no reply (ACK).
1 During group operation with
indoor unit of multi- refrigerant system, if indoor unit transmit to remote controller while out­door unit power supply of one refrigerant system is turned off or within 2 minutes of restart, abnormality is detected.
2 Contact failure of transmission
wire of remote controller or indoor unit
3 Disconnection of transmission
connector (CN2M) of indoor unit
4 Defective transmitting receiving
circuit of indoor unit or remote controller
Same as mentioned in “A7” of the previous page.
OCH607
38
10-5. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena Factor Countermeasure
1. Remote controller display does not work.
2. “PLEASE WAIT” display is remained on the remote controller.
3. When pressing the remote controller operation switch the OPERATION display is appeared but it will be turned off soon.
1 After cancelling to select function from the remote
controller, the remote controller operation switch will not be accepted for approx. 30 seconds.
1 Normal operation
1 At longest 2 minutes after the power supply “PLEASE
WAIT” is displayed to start up.
2 Communication error between the remote controller
and indoor unit
3
Communication error between the indoor and outdoor unit
4 Outdoor unit protection device connector is open.
1 12 V DC is not supplied to remote controller.
(Power supply display is not indicated on LCD.) 2 12–15 V DC is supplied to remote controller, how-
ever, no display is indicated.
“PLEASE WAIT” is not displayed.
“PLEASE WAIT” is displayed.
1 Check LED2 on indoor controller board. (1) When LED2 is lit. Check the remote controller wiring for breaking or contact failure. (2) When LED2 is blinking. Check short circuit of remote controller wiring. (3) When LED2 is not lit. Refer to No.3 below. 2 Check the following.
Failure of remote controller if “PLEASE
WAIT” is not displayed
Refer to No.2 below if “PLEASE WAIT” is
displayed.
1 Normal operation 2 Self-diagnosis of remote controller 3 “PLEASE WAIT” is displayed for 6 min-
utes at most in case of indoor/outdoor unit communication error. Check LED3 on indoor controller board. (1)When LED3 is not blinking. Check indoor/outdoor connecting wire for miswiring. (Converse wiring of S1 and S2, or break of S3 wiring.) (2)When LED3 is blinking. Indoor/outdoor connecting wire is nor­ mal. 4 Check LED display on outdoor controller circuit board. Refer to "10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS".). Check protection device connector (63L and 63H) for contact failure. Refer to "10-9. TEST POINT DIAGRAM".
Check Code
Abnormal point and detection method Case Judgment and action
A8
(6608)
M-NET NO RESPONSE
Abnormal if a message was transmitted and there were reply (ACK) that message was received, but response command does not return. Transmitting side detects abnormality every 30 seconds, 6 times continuously. Note: The address and attribute displayed
at remote controller indicate the con­troller that did not reply (ACK).
1 Transmitting condition is
repeated fault because of noise and the like.
2 Extension of transmission wire
voltage and signal is caused by over-range transmission wire.
• Maximum distance���� 656 ft [200 m]
Remote controller line
(39 ft
[12 m])
3 Extension of transmission wire
voltage and signal is caused by type-unmatched transmis­sion wire.
Type����
With shield wire­ CVVS, CPEVS With normal wire (no shield)­ VCTF, VCTFK, CVV CVS, VVR, VVF, VCT
Diameter����AWG16 [1.25mm2]
or more
4 Accidental malfunction of
abnormality-generated
controller
1 Check transmission waveform or noise on
transmission wire.
2 Turn off the power supply of outdoor unit
and indoor unit and FRESH MASTER or LOSSNAY at the same time for 2 minutes or more, and turn the power on again. If mal­function was accidental, the unit returns to normal. If the same abnormality generates again, controller of displayed address and attribute may be defective.
OCH607
39
Phenomena
Factor
Countermeasure
7. Remote controller display works nor­mally and the unit performs heating operation, however, the capacity cannot be fully obtained.
1 Linear expansion valve fault
Opening cannot be adjusted well due to linear expan-
sion valve fault.
2 Refrigerant shortage
3 Lack of insulation for refrigerant piping 4 Filter clogging
5 Heat exchanger clogging
6 Air duct short cycle 7 Bypass circuit of outdoor unit fault
1 Discharging temperature and indoor heat
exchanger temperature does not rise. Inspect the failure by checking discharg­ing pressure. Replace linear expansion valve.
2 If refrigerant leaks, discharging tempera-
ture rises and LEV opening increases. Inspect leakage by checking the tempera­ture and opening.
Check pipe connections for gas leakage.
3 Check the insulation. 4 Open intake grill and check the filter.
Clean the filter by removing dirt or dust on it.
5
If the filter is clogged, indoor pipe tempera­ture rises and discharging pressure increas­es. Check if heat exchanger is clogged by inspecting discharging pressure.
Clean the heat exchanger.
6 Remove the shield. 7
Check refrigerant system during operation.
8. 1For 3 minutes after temperature
adjuster turns off, the compressor will not start operating even if temperature adjuster is turned on. 2For 3 minutes after temperature adjuster turns on, the compressor will not stop operating even if temperature adjuster is turned off. (Compressor stops operating immediately when turning off by the remote controller.)
12 Normal operation (For protection of compressor)
12 Normal operation
4. Even controlling by the IR wireless remote controller no beep is heard and the unit does not start operat­ing. Operation display is indicated on the IR wireless remote controller.
1 The pair number settings of the IR wireless remote
controller and indoor controller board are mismatched.
1 Check the pair number settings.
5. When operating by the IR wireless remote controller, beep sound is heard, however, unit does not start operating.
1 No operation for 2 minutes at most after the power
supply ON.
2 Hand-held remote controller operation is prohibited.
• Remote controlling adaptor is connected to CN32 on the indoor controller board.
• Hand-held remote controller operation is prohibited
by centralised controller etc. since it is connected to MELANS.
3 Refer to factor of No.2 on previous page.
1 Normal operation
2 Normal operation
3 Check phenomena of No.2.
6. Remote controller display works normally and the unit performs cool-
ing operation, however, the capacity cannot be fully obtained. (The air does not cool well.)
1 Refrigerant shortage
2 Filter clogging
3 Heat exchanger clogging
4 Air duct short cycle
1 If refrigerant leaks, discharging tempera-
ture rises and LEV opening increases. Inspect leakage by checking the tempera­ture and opening. Check pipe connections for gas leakage.
2 Open intake grille and check the filter.
Clean the filter by removing dirt or dust on it.
3
If the filter is clogged, indoor pipe tempera­ture rises and discharging pressure increas­es. Check if heat exchanger is clogged by inspecting discharging pressure.
Clean the heat exchanger.
4 Remove the shield.
OCH607
40
How long is “PLEASE WAIT”
kept being displayed on the
remote controller?
6 minutes or more
2 minutes or less
2 to 6 minutes
NO
NO
YES
YES
Are any check codes
displayed on the
remote controller?
Are any check codes
displayed on the LED?
Symptoms: “PLEASE WAIT” is kept being displayed on the remote controller.
Check the display time of “PLEASE WAIT”
after turning on the main power.
“PLEASE WAIT” will be displayed during the start-up
diagnosis after turning on the main power.
• Normal
The start-up diagnosis will
be over in around 2 minutes.
• Miswiring of indoor/
outdoor connecting wire
• Breaking of indoor/
outdoor connecting wire (S3)
• Defective indoor
controller board
• Defective outdoor
controller circuit board
• Refer to “Self-diagnosis
action table” in order to solve the trouble.
• In case of communication
errors, the display of remote controller may not match the LED display of the outdoor unit.
• Defective indoor
controller board
• Defective remote
controller
Check the LED display of the outdoor controller circuit board.
Diagnosis flow Cause
Inspection method and troubleshooting
OCH607
41
187 to 253 V AC?
187 to 253 V AC?
187 to 253 V AC?
12 to 16 V DC?
12 to 16 V DC?
NO
YES
NO
YES
NO
YES
YES
NO
YES
NO
Check the voltage between S1 and S2 on the terminal block (TB4) of the indoor unit.
Check the voltage among L1 and L2 on the terminal block (TB1) of the outdoor power circuit board.
Check the voltage of indoor controller board (CN2D).
Check the voltage of the unit after removing the indoor power board (CN2S).
Check the voltage between S1 and S2 on the terminal block (TB1) of the outdoor unit which is used to connect the indoor unit and the outdoor unit.
Troubles concerning
power supply
• Check the power wiring
to the outdoor unit.
• Check the breaker.
• Bad wiring of the
outdoor controller board
• The fuses on the
outdoor controller circuit board are blown.
• Check the wiring of the
outdoor unit.
• Check if the wiring is bad.
Check if the fuses are blown. The fuses on the outdoor controller circuit board will be blown when the indoor /outdoor connecting wire short-circuits.
• Bad wiring of the
outdoor controller board
• The fuses on the
outdoor controller circuit board are blown.
• Check if miswiring, breaking
or poor contact is causing this problem. Indoor/outdoor connecting wire is polarized 3-core type. Connect the indoor unit and the outdoor unit by wiring each pair of
S1, S2 and S3 on the both
side of indoor/outdoor terminal blocks.
• Defective indoor
power board
• Replace the indoor
power board.
• Defective indoor
controller board
• Replace the indoor
controller board.
• Miswiring, breaking
or poor connection of indoor/outdoor connecting wire
Check if there is miswiring
or breaking of wire.
Symptoms: Nothing is displayed on the remote controller. 1
Diagnosis flow Cause
Inspection method and troubleshooting
LED display of the indoor controller board LED1 : LED2 : LED3 :
OCH607
42
187 to 253 V AC?
Are there looseness or
disconnection of the indoor/
outdoor connecting wire?
Is anything displayed?
17 to 28 V DC?
Is “E8” displayed?
Can all the indoor
unit be operated?
Check the voltage between S2 and S3 on the terminal block of the outdoor unit.
NO
YES
Not lighting.
Blinking
NO
YES
NO
YES
Not displayed.
Displayed.
YES
NO
YES
NO
Check the voltage between S1 and
S2 on the terminal block (TB4)
of the indoor
unit.
Check the refrigerant address of the outdoor unit. (SW1-3 to 1-6)
Check the looseness or disconnection of the indoor/outdoor connecting wire.
Check the LED display of the outdoor unit after turning on the main power again.
Can the unit be restarted?
• Breaking or poor
contact of the indoor/ outdoor connecting wire
• Fix the breaking or poor
contact of the indoor/outdoor connecting wire.
• Defective outdoor
controller circuit board
• Replace the outdoor
controller circuit board.
• Normal
Only the unit which has the refrigerant address “0” supplies power to the remote controller.
• Set the refrigerant
address to “0”. In case of the multiple grouping system, recheck the refrigerant address again.
• Defective indoor
power board
• Replace the indoor
power board.
• Defective outdoor
power circuit board
• Replace the outdoor
power circuit board.
• Defective indoor
controller board
Replace the indoor controller
board of the indoor unit which does not operate.
• Defective outdoor
controller circuit board
• Replace the outdoor
controller circuit board.
• Influence of
electromagnetic noise
• Not abnormal.
There may be the influence of electromagnetic noise.
Check the transmission wire and get rid of the causes.
Symptoms: Nothing is displayed on the remote controller. 2
Diagnosis flow Cause
Inspection method and troubleshooting
LED display of the indoor controller board LED1 : LED2 : LED3 : or
Check the status of the indoor controller board LED3 display.
Is the refrigerant address “0”?
NO
YES
NO
YES
Is “EA” or “Eb” displayed?
OCH607
43
10 to 16 V DC?
YES
NO
Lighting
Blinking
Lighting
Blinking
Check the voltage of the terminal block (TB6) of the indoor unit.
Check the status of the LED2 after disconnecting the remote controller wire from the terminal block (TB5) of the indoor unit.
• Defective
remote controller
• Replace the
remote controller.
• Breaking or poor
contact of the remote controller wire
• Check if there is breaking or poor contact of the
remote controller wire. Check the voltage of the terminal block (TB5) connecting the remote controller wire.
If it is not between 10
and 16 V DC, the indoor controller board must be defective.
• The remote controller
wire short-circuits
• Check if the remote
controller wire is short-circuited.
• Defective indoor
controller board
• Replace the indoor
controller board.
Diagnosis flow Cause
Inspection method and
troubleshooting
Symptoms: Nothing is displayed on the remote controller. 3
LED display of the indoor
controller board LED1 : LED2 : or LED3 : —
Check the status of the LED2.
Check the status of the LED2.
OCH607
44
1
The operating display of remote
controller does not come on.
Phone Calls From Customers How to Respond Note
1 Check if power is supplied to air conditioner. Nothing appears on the display unless power is supplied.
2 Unit cannot be restarted for a while after it’s stopped.
2 Wait around 3 minutes to restart unit. The air conditioner is in a state of being protected by the microcomputer’s directive. Once the compressor is stopped, the unit cannot be restarted for 3 minutes. This control is also applied when the unit is turned on and off by remote controller or thermostat.
3
Check code appears and blinks on the display of remote controller.
Refer to “SELF-DIAGNOSIS ACTION TABLE”. Check if servicing is required for the error.
Display time of “FILTER” depends on the model. Long life filter: 2500 hrs. Regular filter: 100 hrs.
3 Check code will be displayed if any protection devices of the air conditioner are actuated.
What is check code?
1
“PLEASE WAIT” is displayed on the screen.
1 Wait around 2 minutes. An automatic startup test will be conducted for 2 minutes when power is supplied to the air conditioner. “PLEASE WAIT” will be kept displayed while that time.
2
“FILTER” is displayed on the screen.
2 This indicates that it is time to clean the air filters. Clean the air filters. Press the FILTER button on the remote controller twice to clear “FILTER” from the display. See the operation manual that came with the product for how to clean the filters.
3
“STANDBY” is displayed on the screen.
3 This is displayed when the unit starts HEAT operation, when the thermostat puts the compressor in operation mode, or when the outdoor unit ends DEFROST operation and returns to HEAT operation. The display will automatically disappear around
10 minutes later. While “STANDBY” is displayed on the remote controller, the airflow amount will be restricted because the indoor unit’s heat exchanger is not fully heated up. In addition to that, the up/down vane will be automatically set to horizontal blow in order to prevent cold air from directly blowing out to human body. The up/down vane will return to the setting specified by the remote controller when “STANDBY” is released.
4
“DEFROST” is displayed on the screen. (No air comes out of the unit.)
4 The outdoor unit gets frosted when the outside
temperature is low and the humidity is high.
“DEFROST” indicates the DEFROST operation
is being performed to melt this frost. The
DEFROST operation ends in around 10 minutes
(at most 15 minutes).
During the DEFROST operation, the indoor unit’s
heat exchanger becomes cold, so the blower is
stopped. The up/down vane will be automatically
set to horizontal blow in order to prevent cold air
from directly blowing out to human body. The
display will turn into “STANDBY” when DEFROST
operation ends.
Unit does not operate at all.
Remote controller
• Before repair
Frequent calling from customers
OCH607
45
Phone Calls From Customers How to Respond Note
1 Check the set temperature of remote controller. The outdoor unit cannot be operated if the set temperature is not appropriate.
The outdoor unit operates in the following modes. COOL: When the set temperature is lower than the room temperature. HEAT: When the set temperature is higher than the room temperature.
2 Check if filters are not dirty and clogged. If filters are clogged, the airflow amount will be reduced and the unit capacity will be lowered. See the instruction manual that came with the product for how to clean the filters.
3 Check there is enough space around the air conditioner.
If there are any obstacles in the air intake or air outlet
of indoor/outdoor units, they block the airflow direction so that the unit capacity will be lowered.
1
An gas escaping sound is heard
sometimes.
1 This is not a malfunction. This is the sound which is heard when the flow of refrigerant in the air conditioner is switched.
2
A cracking sound is heard
sometimes.
2 This is not a malfunction. This is the sound which is heard when internal parts of units expand or contract when the temperature changes.
3
A buzzing sound is heard
sometimes.
3 This is not a malfunction. This is the sound which is heard when the outdoor unit starts operating.
4
A ticking sound is heard from
the outdoor unit sometimes.
4 This is not a malfunction. This is the sound which is heard when the blower of the outdoor unit is controlling the airflow amount in order to keep the optimum operating condition.
5
A sound, similar to water
flowing, is heard from the unit.
5 This is not a malfunction. This is the sound which is heard when the refrigerant is flowing inside the indoor unit.
2
The fan speed does not match the setting of the remote controller in HEAT operation.
The up/down vane will be automatically set to horizontal blow in these cases listed up on the left (13). After a while, the up/down vane will be automatically moved according to the setting of the remote controller.
2 This is not a malfunction.
1) When the HEAT operation starts, to prevent the unit from blowing cold air, the fan speed is gradually increased from zero to the set speed, in proportion to the temperature rise of the discharged air.
2) When the room temperature reaches the set temperature and the outdoor unit stops, the unit starts the LOW AIR operation.
3) During the HEAT operation, the DEFROST operation is performed to defrost the outdoor unit. During the DEFROST operation, the blower is stopped to prevent cold air coming out of the indoor unit.
Sound comes out from the air conditioner.
1
The fan speed does not match the setting of the remote controller during DRY operation.(No air comes out sometimes during DRY operation.)
1 This is not a malfunction. During the DRY operation, the blower’s ON/OFF is controlled by the microcomputer to prevent overcooling and to ensure efficient dehumidification. The fan speed cannot be set by the remote controller during DRY operation.
Something is wrong with the blower…..
The room cannot be cooled or heated sufficiently.
OCH607
46
3
Air blows out for a while after HEAT operation is stopped.
Phone Calls From Customers How to Respond Note
3 This is not a malfunction. The blower is operating just for cooling down the heated-up air conditioner. This will be done within 1 minute. This control is conducted only when the HEAT operation is stopped with the electric heater ON.
However, this control is also applied to the models which has no electric heater.
“STANDBY” will be displayed on the remote controller in case of 1) and 2). “DEFROST” will be displayed on the screen in case of 3).
1
The airflow direction is changed during COOL operation.
1 If the up/down vane is set to downward in COOL operation, it will be automatically set to horizontal blow by the microcomputer in order to prevent water from dropping down. “1 Hr.” will be displayed on the remote controller if the up/down vane is set to downward with the fan speed set to be less than “LOW”.
2
The airflow direction is changed during HEAT operation. (The airflow direction cannot be set by remote controller.)
2 In HEAT operation, the up/down vane is automatically controlled according to the temperature of the indoor unit’s heat exchanger. In the following cases written below, the up/down vane will be set to horizontal blow, and the setting cannot be changed by remote controller.
1) At the beginning of the HEAT operation
2) While the outdoor unit is being stopped by thermostat or when the outdoor unit gets started to operate.
3) During DEFROST operation The airflow direction will be back to the setting of remote controller when the above situations are released.
3
The airflow direction does not change. (Up/down vane, left/right louver)
3 1) Check if the vane is set to a fixed position. (Check if the vane motor connector is removed.)
2) Check if the air conditioner has a function for switching the air direction.
3) If the air conditioner does not have that function, “NOT AVAILABLE” will be displayed on the remote controller when “AIR DIRECTION” or “LOUVER” button is pressed.
Something is wrong with the blower…..
Something is wrong with the airflow direction….
1 Check if you set ON/OFF timer. The air conditioner starts operating at the time designated if ON timer has been set before.
2 Check if any operations are ordered by distant control system or the central remote controller.
While “CENTRALLY CONTROLLED INDICATOR” is displayed on the remote controller, the air conditioner is under the control of external directive.
The air conditioner starts operating even though any buttons on the remote controller are not pressed.
1 Check if you set ON/OFF timer. The air conditioner stops operating at the time designated if OFF timer has been set before.
The air conditioner stops even though any buttons on the remote controller are not pressed.
There might be a case that “CENTRALLY CONTROLLED
INDICATOR
” will not be
displayed.
There might be a case that “CENTRALLY CONTROLLED INDICATOR” will not be displayed.
3 Check if power is recovered from power failure (black out). The units will automatically start operating when power is recovered after power failure (black out) occurs. This function is called “auto recovery feature from power ”.
2
Check if any operations are ordered by distant control system or the central remote controller. While “CENTRALLY CONTROLLED INDICATOR” is displayed on the remote controller, the air conditioner is under the control of external directive.
OCH607
47
Phone Calls From Customers How to Respond Note
This is not a malfunction. This may occur when the operation gets started in the room of high humidity.
A white mist is expelled from the indoor unit.
COOL: When pipes or piping joints are cooled, they get sweated and water drips down. HEAT: Water drips down from the heat exchanger. Note: Use optional parts “Drain Socket” and “Drain
pan” if these water needs to be collected and drained out for once.
Water or moisture is expelled from the outdoor unit.
Batteries are being exhausted. Replace them and press the reset button of remote controller.
The display of the IR wireless remote controller gets dim or does not come on. The indoor unit does not receive a signal from remote controller at a long distance.
OCH607
48
1 2 3 4 5 6
M
Gray
Orange
Red
Yellow
Black
Parts name
Check points
Disconnect the connector then measure the resistance with a tester. (Ambient temperature 50 to 86°F [10 to 30:])
Thermistor (TH3) <Liquid>
Thermistor (TH4) <Discharge>
Thermistor (TH6) <2-phase pipe>
Thermistor (TH7) <Ambient>
Thermistor (TH8) <Heat sink>
Thermistor (TH32) <Suction>
Thermistor (TH33) <Ref. check>
Normal
160 to 410 k"
4.3 to 9.6 k"
39 to 105 k"
TH4
TH3
TH6
TH7
TH32
TH33
TH8
Abnormal
Open or short
Measure the resistance between the terminals with a tester. (Ambient temperature 68°F [20
:
])
Solenoid valve coil <4-way valve> (21S4)
Motor for compressor (MC)
Linear expansion valve (LEV-A/LEV-B/LEV-C)
Normal
Abnormal
Open or short
Disconnect the connector then measure the resistance with a tester. (Winding temperature 68°F [20
:
])
Refer to the next page.
Fan motor(MF1,MF2)
1435 i 150 "
0.188 "
Measure the resistance between the terminals with a tester. (Winding temperature 68°F [20
:
])
Normal Abnormal
Open or short
W
V
U
Normal
Gray - Black Gray - Red
Gray - Yellow
Gray - Orange
Abnormal
46 i 3 "
Open or short
10-6. HOW TO CHECK THE PARTS PUZ-HA30NHA5 PUZ-HA36NHA5
OCH607
49
Notes
· High voltage is applied to the connecter (CNF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNF1, 2) for the motor with the power supply on. (It causes trouble of the outdoor controller circuit
board and fan motor.)
Self check Symptom : The outdoor fan cannot rotate.
1
2
Check method of DC fan motor (fan motor/outdoor controller circuit board)
No
Fail
Fail
Wiring contact check
Contact of fan motor connector (CNF1, 2)
Fuse check
Check the fuse (F5) on outdoor controller board.
Power supply check (Remove the connector (CNF1, 2))
Measure the voltage in the outdoor controller circuit
board.
TEST POINT
1 : VDC (between 1 (+) and 4 () of the fan connector): VDC 250–330 V DC
TEST POINT 2 : VCC (between 5 (+) and 4 () of the fan connector): VCC 15 V DC
Wiring recovery
Replace the outdoor controller board.
Replace the fan motor.
Replace outdoor controller board (C.B) and fan motor (MF1, 2).
Replace the outdoor
controller board.
Replace the fan motor.
Is the voltage normal?
Is there contact failure?
Yes
Yes
No
Did the fuse blow?
No
Yes
Check the operation of fan. END
Yes
OK
Check the operation. END
OK
OCH607
50
10-7. HOW TO CHECK THE COMPONENTS
<Thermistor feature chart>
Low temperature thermistors
• Thermistor <Liquid> (TH3)
• Thermistor <2-phase pipe> (TH6)
• Thermistor <Ambient> (TH7)
• Thermistor <Suction> (TH32)
• Thermistor <Ref. check> (TH33)
32˚F [0:] 15 k" 50˚F [10:] 9.6 k" 68˚F [20:] 6.3 k" 77˚F [25:] 5.2 k"
86˚F [30:] 4.3 k" 104˚F [40:] 3.0 k"
68˚F [20:] 250 k" 86˚F [30:] 160 k" 104˚F [40:] 104 k" 122˚F [50:] 70 k" 140˚F [60:] 48 k"
158˚F [70:] 34 k" 176˚F [80:] 24 k" 194˚F [90:] 17.5 k" 212˚F [100:] 13.0 k" 230˚F [110:] 9.8 k"
High temperature thermistor
• Thermistor <Discharge> (TH4)
0
10
20
30
40
50
20 10 0 10 20 30 40 50
4 14 32 50 68 86 104122:°F
Temperature
Resistance (k")
500
400
300
200
100
0
25
50 75 100 120
77
122 167 212 248
:
°F
Temperature
Resistance (k")
32˚F [0:] 180 k" 77˚F [25:] 50 k" 122˚F [50:] 17 k" 158˚F [70:] 8 k" 194˚F [90:] 4 k"
Medium temperature thermistor
• Thermistor <Heat sink> (TH8)
200
150
100
50
0
25 50 75 100 110 125
77 122 167 212 230 257:°F
Temperature
Resistance (k")
Thermistor R0 = 15 k" ± 3% B constant = 3480 ± 2%
t (:): Rt =15exp{3480(
273+t – 273
)}
T (˚F): RT =15exp{3480(
273+(T– 32)/1.8 – 273
)}
1
1
1 1
Thermistor R50 = 17 k" ± 2% B constant = 4170 ± 3%
t (:): Rt =17exp{4170(
273+t – 323
)}
T (˚F): R
T=17exp{4170(
273+(T– 32)/1.8 – 323
)}
1
1
1 1
Thermistor R120 = 7.465 k" ± 2% B constant = 4057 ± 2%
t (:): Rt =7.465exp{4057(
273+t – 393
)}
T (˚F): R
T =7.465exp{4057(
273+(T– 32)/1.8 – 393
)}
1
1
1 1
OCH607
51
<Output pulse signal and the valve operation>
(2) Linear expansion valve operation
A
B
C
Open
Extra tightning (about 32 pulse)
Pulse number
500 pulse Opening a valve all the way
Close
Valve position (capacity)
Opening a valve : 8 → 7 → 6 → 5 → 4 → 3 → 2 → 1 → 8 Closing a valve : 1 → 2 → 3 → 4 → 5 → 6 → 7 → 8 → 1 The output pulse shifts in above order.
• When linear expansion valve operation stops, all output phases become OFF.
• When the power is turned on, 700 pulse closing valve signal will be sent till it goes to
A point in order to define the valve position.
(The pulse signal is being sent for about 20 seconds.)
When the valve moves smoothly, there is no sound or vibration
occurring from the linear expansion valve ; however, when the pulse number moves from
B to A or when the valve is locked,
sound can be heard.
No sound is heard when the pulse number moves from
B to A i n
case coil is burnt out or motor is locked by open-phase.
• Sound can be detected by placing the ear against the screw driv­er handle while putting the screw driver to the linear expansion valve.
LEV
M
1
6
[4
[4
[3
[2
[1
1
Gray
Orange
Red
Yellow
Black
3
4
5
6
Connector LEV-A
LEV-B
LEV-C
12 V DC
Outdoor controller board
Drive circuit
[3
[2
[1
3
2
5
4
Linear expansion valve
(1) Operation summary of the linear expansion valve
• Linear expansion valve opens/closes through stepping motor after receiving the pulse signal from the outdoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
1
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
[1
Output
(Phase)
Output
[2
[3
[4
2 3 4
5 6 7 8
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OCH607
52
Main body
Lead wire
Stopper
Coil
(3) How to attach and detach the coil of linear expansion valve
<Composition> Linear expansion valve is separable into the main body and the coil as shown in the diagram below.
Be sure to attach the stopper.
A
<How to attach the coil>
Hold the lower part of the main body (shown as A) firmly so that the main body does not move and attach the coil by inserting it downward into the main body. Then securely attach the coil stop­per to main body. (At this time, be careful that stress is not added to lead wire and main body is not wound by lead wire.) If the stopper is not firmly attached to main body, coil may be detached from the main body and that can cause defective operation of lin­ear expansion valve. To prevent piping stress, be sure to attach the coil holding the main body of linear expansion valve firmly. Otherwise pipe may break.
A
<How to detach the coil>
Hold the lower part of the main body (shown as A) firmly so that the main body does not move and detach the coil by pulling it upward. Be sure to detach the coil holding main body firmly. Otherwise pipes can bend due to stress.
OCH607
53
(4) Releasing emergency operation
1 Turn the main power supply off. 2 Set the emergency operation switch (SWE) on indoor controller board to OFF. 3 Set the shorting pins of emergency operation connector (CN31) on outdoor controller board to OFF. 4 Set SW4-2 on outdoor controller board as shown in the right.
Note: If shorting pins are not set on emergency operation connector (CN31), the setting remains OFF.
SW4
1 2 Cooling
Heating
ON
10-8. EMERGENCY OPERATION
(1) When any check codes shown below is displayed on outdoor unit, or microcomputer for wired remote controller or indoor
unit has a failure while no other problems are found, emergency operation will be available by setting the emergency opera­tion switch (SWE) ON and short-circuiting the connector (CN31) on outdoor controller board.
(2) Check the following items and cautions for emergency operation
1 Make sure that there is no abnormality in outdoor unit other than the above abnormalities. (Emergency operation will not be available when check codes other than the above are indicated.) 2 For emergency operation, it is necessary to set the emergency operation switch (SWE) on indoor controller board. Refer to the electrical wiring diagram of indoor unit for how to set the indoor unit.) 3 During emergency operation, the air-conditioner will continuously be operated by supplying power and stopping it. It can not be turned on or off by remote control, and temperature control is not possible. 4 Do not perform emergency heating operation for an extended period of time. If the outdoor unit starts defrosting during this period, cold air will blow out from the indoor unit. 5 Do not perform emergency cooling operation for more than 10 hours. Neglecting this could result in freezing the heat exchanger in indoor unit.
(3) Emergency operation procedure
1 Turn the main power supply off. 2 Turn on the emergency operation switch (SWE) on indoor controller board. 3 Set the shorting pins of emergency operation connector (CN31) on outdoor controller board to ON. 4 Use SW4-2 on outdoor controller board to set the operation mode (cooling or heating). (SW4-1 is not used.)
5 Turning the main power supply on will start the emergency operation.
SW4
1 2 Cooling
Heating
ON
ON
OFF
CN31
Shorting pins
Inspected content
Open/short of thermistor (TH3/TH6/TH7/TH32/TH33/TH8)
Indoor/outdoor unit communication error •Signal receiving error (Outdoor unit)
Indoor/outdoor unit communication error •Transmitting error (Indoor unit)
Communication error other than outdoor unit
Communication error between outdoor controller board and M-NET board (Serial communication error)
Check code
U4
E8
E9
E0–E7
Ed
When following abnormalities occur, emergency operation will be available.
OCH607
54
(5) Operation data during emergency operation
During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation are set to the following values:
Intake temperature (TH1)
Indoor liquid temperature (TH2)
Indoor 2-phase pipe temperature (TH5)
Set temperature
Outdoor liquid temperature (TH3)
Outdoor 2-phase pipe temperature (TH6)
Outdoor ambient temperature (TH7)
Temperature difference code (intake temperatureset temperature) (Tj)
Discharge superheat (SHd)
Sub-cool (SC)
Operation mode
COOL
81°F [27:]
41°F [5:]
41°F [5:]
77°F [25:]
113°F [45:]
122°F [50:]
95°F [35:]
5
54°F [30:]
9°F [5:]
HEAT
69°F [20.5:]
113°F [45:]
122°F [50:]
72°F [22:]
41°F [5:]
41°F [5:]
45°F [7:]
5
54°F [30:]
9°F [5:]
(*1)
(*1)
(*1)
(*1)
(*2)
Remarks
*1: If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data. If the unit enters emergency operation because TH values have become mismatched, setting the thermistors to open/short corrects the settings.
*2: If one thermistor is set to open/short, the values for each will be different. [Example] When pipe temperature thermistor (TH3) has an open or short circuit.
COOL
113°F [45:]
Ta
Tc
41°F [5:]
41°F [5:]
HEAT
41°F [5:]
Tb
Td
122°F [50:]
122°F [50:]
Thermistor
TH3
TH6
TH4
TH5
TH2
Regard normal figure as effective data.
Regard normal figure as effective data.
Discharge superheat (SHd) Cooling = TH4TH6 = TcTa Heating = TH4 TH5 = Td(122°F [50:])
Degree of subcooling (SC) Cooling = TH6TH3 = Ta−(113°F[45:]) Heating = TH5TH2 = 122°F113°F = 9°F [50:45: = 5:]
Operation data
OCH607
55
Communication power supply D71 Voltage 24 V DC
CNS
S1-S2: 208/230 V AC
CNAC
2 to 4: Power supply for out­door controller circuit board (208/230 V AC) 1 to 3: Power supply for indoor and outdoor unit connec­tion wire (208/230 V AC)
CNF1, CNF2 Connect to the fan motor
1–4: 280 V DC 5–4: 15 V DC 6–4: 0−6.5 V DC 7–4: 15 V DC(When stopped)
7.5 V DC(When operated) (0–15 V pulse)
21S4
4-way valve
63H
High pressure switch
CN4
Transmission to out­door power circuit board (CN4)
SW4
Test operation
SW6
Model select
SW5
Function switch
SW1
Manual defrost, detect history record reset, refrigerant address
CNDM
1 to 2: Input of low-level sound priority mode 1 to 3: Input of external con­tact point
TH4
Thermistor <Discharge>
TH3
Thermistor <Liquid>
TH7/6
Thermistor <Ambient/ 2-phase pipe>
CNDC
280 V DC (1+, 3−) Connect to the outdoor power circuit board (CNDC)
+ -
VFG (TEST POINT 4)
(Voltage between right pins of PC5C and PC5D, pin 3 and pin 4) (Same as
(CNF1
7(+)–4(−))
VSP (TEST POINT 3)
(Voltage between pins of C5A, C5B): 0 V DC(when stopped), 1–6.5 V DC (when operated)
SW7
Demand control setting
CN51
External signal output
• Compressor operat­ing signal
• Abnormal signal
LEV-A,B,C
Linear expansion valve
SWP
Pump down
SW8
Pipe replace Wiring replace
CNM Connect to A control service tool
CNMNT Connect to M-NET adapter(CN5)
CNVMNT Connect to M-NET adapter(CND)
CN2
Connect to the outdoor power circuit board (CN2) 15: Reception from
power circuit board
25: Zero cross signal (0–5 V DC) 34:
18 V DC
6–5: 16 V DC 7–5: 16 V DC
CN52C
(Connect to the noise filter circuit board (CN52C))
10-9. TEST POINT DIAGRAM Outdoor controller circuit board PUZ-HA30NHA5 PUZ-HA36NHA5
<CAUTION> TEST POINT1 is high voltage.
TH32, TH33
Thermistor <Suction>, <Ref. check>
63L Low pressure switch
OCH607
56
CNAC1, CNAC2 208/230 V AC (Connect to the outdoor control­ler circuit board (CNAC))
EI Connect to the ground
CN5 Primary current (Connect to the outdoor power circuit board (CN5))
LO, NO Voltage of 208/230 V AC is output (Connect to the outdoor power circuit board (TABS, TABT))
Outdoor noise filter circuit board PUZ-HA30NHA5 PUZ-HA36NHA5
CN52C 52C driving signal (Connect to the outdoor controller circuit board (CN52C))
E2 Connect to the ground
LI, NI Voltage of 208/230 V AC is input (Connect to the terminal block(TB1))
RS1
OCH607
57
Outdoor power circuit board PUZ-HA30NHA5 PUZ-HA36NHA5
TABP1 Connect to 52C
TABP2/SC-P2 Connect to the ACTM
CN4 Connect to the outdoor controller circuit board (CN4)
CN2 Connect to the outdoor controller circuit board (CN2) 15: Transmitting signal to the outdoor controller circuit board (0–5 V DC)
2–5: Zero cross signal (0–5 V DC) 3–4: 18 V DC 6–5: 16 V DC 7–5: 16 V DC
CN3 Thermistor (TH8) <Heat sink>
CN5 Detection of primary current Connect to the outdoor noise filter circuit board (CN5)
CNDC 280–380 V DC (1+, 3−) Connect to the outdoor controller circuit board (CNDC)
TABS/TABT Connect to the outdoor noise filter circuit board Voltage among phases: 208/230 V AC
Brief check of POWER MODULE Usually, they are in a state of being short-circuited if they are broken. Measure the resistance in the following points (connectors, etc.). If they are short-circuited, it means that they are broken.
1. Check of diode bridge TABP1-TABS, TABN1-TABS, TABP1-TABT,TABN1-TABT
2. Check of DIP-IPM P-U, P-V, P-W, N-U, N-V, N-W
TABN2 Connect to ACTM
TABN Connect to the smoothing capacitor CB –
TABU/V/W Connect to the compressor (MC) Voltage among phases:10–180 V AC
TABP Connect to the smoothing capaci­tor CB +
TABN1 Connect to ACTM
DIP-IPM
CNAF Connect to ACTM
OCH607
58
Active filter module PUZ-HA30NHA5 PUZ-HA36NHA5
L1, L2 Connect to the DCL(Reactor)
Connect to the outdoor power circuit board (TABP1)
Connect to the outdoor power circuit board(TABN1)
+
Io Connect to the outdoor power circuit board (TABN2)
N2
Non-connect
N1 Non-connect
P Connect to the outdoor power circuit board (TABP2)
Connect to the outdoor power circuit board(CNAF)
1 : GND 2–1 : 18 V DC
3–1 : Control signal 4, 5 : Not used 6–1 : Control signal
Upper side
Lower side
+
DCL
L1 L2
ACTM
P
Io
N1 N2
(+)
(- )
Load
Connection and internal circuit diagram
Error condition Normal value (reference)
Symptom when the unit is in trouble
(–) and Io open less than 1"
1
The unit does not operate (cannot be switched ON)
(–) and L2
short 100 k" to 1 M"
1
The breaker operates
open *1
1
The unit does not operate (cannot be switched ON) 2U9 Abnormal stop (*2)
P and L2
short 100 k" to 1 M"
1
The breaker operates
open *1
1
The unit does not operate (cannot be switched ON) 2U9 Abnormal stop (*2)
P and Io
short 100 k" to 1 M"
1
The breaker operates
open *1
1
The unit does not operate (cannot be switched ON) 2U9 Abnormal stop (*2)
L2 and Io
short 100 k" to 1 M"
1
The breaker operates
open *1
1
The unit does not operate (cannot be switched ON) 2U9 Abnormal stop (*2)
Tester check points of Active lter module
*1
. The symptom when the unit is in open error condition is described to determine open error by tester check.
*2
. SW2 setting : Code "20" display
1 6
ON OFF
OCH607
59
*1 Manual defrost should be done as follows.
1 Change the DIP SW1-1 on the outdoor controller board from OFF to ON. 2 Manual defrost will start by the above operation 1 if all these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor started operating or previous manual defrost is finished.
• Pipe temperature is less than or equal to 46ºF [8ºC].
Manual defrost will finish if certain conditions are satisfied. Manual defrost can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON. After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again. This depends on the service conditions.
Switch
Type
of
switch
DIP
switch
Push
switch
SW1
1
2
No.
Function Effective timing
Action by the switch operation
Manual defrost *
1
Start Normal
When compressor is working in heating operation.
*
1
Abnormal history clear
Refrigerant address
setting
When power supply ON
Clear Normal off or operating
SWP
6
5
4
3
Under suspension
Pump down Start Normal
SW4
SW8
1
2
1
2
3
Test run Operating OFF
Under suspension
Test run mode setting Heating Cooling
Use of existing pipe Used Not used
No function
Separate indoor/outdoor
unit power supplies
Used Not used
Always
When power supply ON
ON OFF
1 2 3
0 1 2 3
4 5 6ON1 2 3 4 5 6ON1 2 3 4 5 6ON1 2 3 4 5 6
ON
1 2 3
4 5 6 7
4 5 6ON1 2 3 4 5 6ON1 2 3 4 5 6ON1 2 3 4 5 6
ON
1 2 3
8 9 10 11
4 5 6ON1 2 3 4 5 6ON1 2 3 4 5 6ON1 2 3 4 5 6
ON
1 2 3
12 13 14 15
4 5 6ON1 2 3 4 5 6ON1 2 3 4 5 6ON1 2 3 4 5 6
ON
10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS
(1) Function of switches
Continue to the next page
OCH607
60
1 2 3 4 5 6 7 8
OFF
ON
36N
OFF
ON
1 2 3 4 5 6
1 2 3 4 5 6 7 8
MODEL SW6 SW5-6
OFF
ON
30N
OFF
ON
1 2 3 4 5 6
1
2
3,4,5
6
3
4
5
6
1
2
3,4
1
2
3
4
5
6
7
8
6
ON OFF
No.
Function Effective timing
Action by the switch operation
No function
Power failure
automatic recovery *
2
No function
Model select
Max. Hz setting (cooling)
Max. Hz setting (heating)
No function
Defrost setting
No function
Function switch
No function
Switch
SW5
SW7
*
4
DIP
switch
SW9
SW6
SW5
Type of
Switch
Auto recovery
Max. Hz (cooling)
o
0.8
Max. Hz (heating)
o
0.8
For high humidity
Valid
No auto recovery
Normal
Normal
Normal
Normal
When power supply ON
Always
Always
Always
Always
Always
Setting of demand
control
*
3
1
2
SW7-1 SW7-2
OFF
0% (Operation stop)
75%
50%
OFF
ON
OFF
OFF
ON
Power consumption (Demand switch ON)
Model select
Following SW5-6 reference
CN31
Types
Connector
Function Effective timing
Connector
Start
Short Open
Action by open/ short operation
Emergency operation
When power supply ON
Normal
(2) Function of connector
*2 “Power failure automatic recovery” can be set by either remote controller or this DIP SW. If one of them is set to ON, “Auto recovery” activates. Please set “Auto recovery” basically by remote controller because all units do not have DIP SW. Please refer to the indoor unit installation manual. *3 SW7-1,2 are used for demand control. SW7-1,2 are effective only at the demand control. (Refer to next page : Special function (b)) *4 Please do not use SW7-3 to 7-6 usually. Trouble might be caused by the usage condition.
OCH607
61
Special function
(a) Low-level sound priority mode (Local wiring) Unit enters into Low-level sound priority mode by external signal input setting. Inputting external signals to the outdoor unit decreases the outdoor unit operation sound 3 to 4 dB lower than that of usual. Adding a commercial timer or on-off switch contactor setting to the CNDM connector which is optional contactor for demand
input located on the outdoor controller board enables to control compressor operation frequency.
Note: The performance depends on the load of conditioned outdoor temperature.
How to wire
1) Make the circuit as shown above with adapter for external signal input (PAC-SC36NA).
2) Turn SW1 to on for Low-level sound priority mode. Turn SW1 to off to release Low-level sound priority mode and normal operation.
(b) On demand control (Local wiring) Demand control is available by external input. In this mode, power consumption is decreased within the range of usual
0–100%.
How to wire Basically, the wiring is same with (a). Connect an SW 1 which is procured locally between Orange and Red(1 and 3) of the adapter for external signal input (PAC-SC36NA), and insulate the tip of the brown lead wire.
It is possible to set it to the following power consumption (compared with ratings) by setting the SW7-1, 2.
CNDM
X
SW1
~
X
Max. 33 ft [10 m] including local wiring
SW1 : Switch X : Relay (Contact spec. : DC1mA)
Relay supply
Red 3
Brown 2
Orange 1
Purchased locally
Adapter for external signal input (PAC-SC36NA)
Outdoor unit controller board
3 2 1
Insulate this point securely as this is not used.
<Low-level sound priority mode circuit>
SW7-1 SW7-2
OFF
0% (Operation stop)
75%
50%
OFF
ON
OFF
OFF
ON
Power consumption
(SW1 on)
OCH607
62
<Display function of inspection for outdoor unit>
The blinking patterns of both LED1 (green) and LED2 (red) indicate the types of abnormality when it occurs. Types of abnormality can be indicated in details by connecting an optional part “A-Control Service Tool (PAC-SK52ST)” to connector CNM on outdoor controller board.
F3 F5 F9
E6
E7
E0
E3
E4
E5
EF
Ed
A0–A8
[Display] (1)Normal condition
(2)Abnormal condition
Unit condition
Outdoor controller board A-Control Service Tool
LED1 (Green) LED2 (Red) Check code
When the power is turned on When unit stops When compressor is warming up When unit operates
Lighted Lighted Lighted Lighted Lighted
Not lighted
Indication of the display
Alternately blinking display
Operation mode
Not lighted
Lighted
00, etc. 08, etc.
C5, H7, etc.
Indication Error
Check
code
*1
Outdoor controller board
Contents Inspection method
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
2 blinking 1 blinking
2 blinking
3 blinking
4 blinking
5 blinking
Connector(63L) is open. Connector(63H) is open. 2 connectors are open.
Startup time over
Check code is not defined.
Miswiring of indoor/outdoor unit conne­cting wire, excessive number of indoor units (4 units or more)
Miswiring of indoor/outdoor unit co­nnecting wire (converse wiring or di­sconnection)
Indoor/outdoor unit communication error (signal receiving error) is detected by in­door unit.
Indoor/outdoor unit communication error (transmitting error) is detected by indoor unit.
Indoor/outdoor unit communication error (signal receiving error) is detected by outdoor unit.
Indoor/outdoor unit communication error (transmitting error) is detected by outdoor unit.
Remote controller signal receiving error is detected by remote controller.
Remote controller transmitting error is detected by remote controller.
Remote controller signal receiving error is detected by indoor unit.
Remote controller transmitting error is detected by indoor unit.
Serial communication error <Communication between outdoor controller board and outdoor power board> <Communication between outdoor controller board and M-NET P.C. board>
Communication error of M-NET system
*1 Check code displayed on remote controller *2
Refer to service manual for indoor unit.
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if 4 or more indoor units are connected to outdoor unit.
3 Check if noise entered into indoor/outdoor connecting wire or power supply.
4 Re-check error by turning off power, and on again.
1 Check if connector (63L or 63H) on the outdoor controller
board is
not disconnected.
2
Check continuity of pressure switch (63H) by tester.
1
Check if connector (CN4) on outdoor controller board and
outdoor power board is not disconnected.
2
Check if there is poor connection of connector on outdoor
controller board(CNMNT and CNVMNT).
3
Check M-NET communication signal.
1 Check if remote controller is MA remote controller (PAR-21MAA). 2 Check if noise entered into transmission wire of remote controller. 3 Check if noise entered into indoor/outdoor connecting wire. 4
Re-check error by turning off power, and on again.
1
Check if connecting wire of indoor unit or remote controller
is connected correctly. 2 Check if noise entered into transmission wire of remote controller.
3 Re-check error by turning off power, and on again.
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if noise entered into indoor/outdoor connecting wire or
power supply.
3
Check if noise entered into indoor/outdoor controller board.
4
Re-check error by turning off power, and on again.
P.26 P.27 P.27 P.27
(EA)
P.27 (Eb) P.27
(EC)
*2
*2
P.33 (E8)
P.33 (E9)
P.32
P.32
P.32
P.32
P.33
P.34
P.35–
P.38
Detailed
reference
page
Continue to the next page
OCH607
63
U2
U7
U1
UL
U8
Ud UF
UP
UH
U6 U3 U4
U5
U9
P1 P2 P9
P4
P5
P6
P8
Indication Error
Check
code
*1
Outdoor controller board
Contents Inspection method
LED1 (Green)
LED2 (Red)
3 blinking 1 blinking
2 blinking
3 blinking
*1 Check code displayed on remote controller *2 Refer to service manual for indoor unit.
4 blinking
5 blinking
6 blinking
7 blinking
1 blinking
2 blinking
3 blinking
4 blinking
4 blinking
Abnormality of shell thermostat and discharging temperature (TH4)
Abnormality of superheat due to low discharge temperature
1 Check if stop valves are open. 2 Check if connectors (TH4, LEV-A, and LEV-B) on outdoor controller
board are not disconnected.
3 Check if unit is filled with specified amount of refrigerant. 4 Measure resistance values among terminals on indoor valve and
outdoor linear expansion valve using a tester.
Abnormal high pressure (High pressure switch 63H worked.) Abnormal low pressure (Low pressure switch 63L worked.) Abnormality of outdoor fan motor rotational speed
1 Check if indoor/outdoor units have a short cycle on their air ducts. 2 Check if connector
(63H)(63L) on outdoor controller board is not disconnected.
3 Check if heat exchanger and filter is not dirty. 4 Measure resistance values among terminals on linear expansion valve
using a tester.
1 Check if stop valves are open. 2 Check looseness, disconnection, and converse connection of
compressor wiring. 3
Measure resistance values among terminals on compressor using a tester.
4 Check if outdoor unit has a short cycle on its air duct.
Compressor overcurrent breaking(Start-up locked)
Compressor overcurrent breaking Abnormality of current sensor (P.B.) Abnormality of power module Open/short of discharge thermistor (TH4)
Open/short of outdoor thermistors (TH3, TH32, TH33, TH6, TH7 and TH8)
1 Check if connectors
(TH3,TH32,TH33,TH4, and TH7/6)
on outdoor
controller board and connector
(CN3)
on outdoor power board are not
disconnected. 2 Measure resistance value of outdoor thermistors.
Abnormality of heatsink temperature
1 Check if indoor/outdoor units have a short cycle on their air ducts. 2 Measure resistance value of outdoor thermistor(TH8).
1 Check the outdoor fan motor. 2 Check if connector
(TH3)
on outdoor controller board is disconnected.
Abnormality of voltage 1 Check looseness, disconnection, and converse connection of
compressor wiring. 2
Measure resistance value among terminals on compressor using a tester
.
3 Check if power supply voltage decreases. 4 Check the wiring of CN52C. 5 Check the wiring of CNAF.
Abnormality of room temperature thermistor (TH1) Abnormality of pipe temperature thermistor /Liquid (TH2) Abnormality of pipe temperature thermistor/Condenser-Evaporator
1 Check if connectors (CN20, CN21, CN29 and CN44) on indoor controller board are not disconnected. 2 Measure resistance value of indoor thermistors.
Abnormality of drain sensor (DS) Float switch connector open (FS)
Indoor drain overflow protection
1 Check if connector (CN31)(CN4F) on indoor controller board is not
disconnected.
2 Measure resistance value of indoor thermistors. 3 Measure resistance value among terminals on drain-up machine using
a tester.
4 Check if drain-up machine works. 5 Check drain function.
Freezing (cooling)/overheating (heating) protection
1 Check if indoor unit has a short cycle on its air duct. 2 Check if heat exchanger and filter is not dirty. 3 Measure resistance value on indoor and outdoor fan motors. 4 Check if the inside of refrigerant piping is not clogged.
Abnormality of pipe temperature
1 Check if indoor thermistors (TH2 and TH5) are not disconnected from holder. 2 Check if stop valve is open. 3
Check converse connection of extension pipe. (on plural units connection)
4 Check if indoor/outdoor connecting wire is connected correctly. (on plural units connection)
P.28
P.29
P.28
P.31
P.30
P.31
P.31 P.31 P.29 P.28 P.29
P.29
P.30
*2 *2 *2
*2
*2
*2
Detailed
reference
page
Protection from overheat operation(TH3)
P.31
OCH607
64
<Outdoor unit operation monitor function> [When optional part “A-Control Service Tool(PAC-SK52ST)” is connected to outdoor controller board(CNM)]
Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of check code by controlling DIP SW2 on “A-Control Service Tool”.
SW2 setting
1ON2 3 4 5 6
Display detail
Explanation for display Unit
Operation indicator SW2 : Indicator change of self diagnosis
<Digital indicator LED1 working details>
(Be sure that 1 to 6 in the SW2 are set to OFF.)
(1) Display when the power supply ON When the power supply ON, blinking displays by turns. Wait for 4 minutes at the longest. (2) When the display lights (Normal operation) 1Operation mode display
1ON2 3 4 5 6
(Initial setting)
SW2
1 second
interval
LED1
(Lighting)
Display Operation Model
The tens digit : Operation mode
The ones digit : Relay output
O
C
H
d
Display
0
1
2
3
4
5
6
7
8
A
Compressor
Warming-up Compressor
4-way valve
Solenoid valve
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF/FAN
COOLING/DRY
HEATING
DEFROSTING
2Display during error postponement Postponement code is displayed when compressor stops due to the work of protection device. Postponement code is displayed while error is being postponed.
(3) When the display blinks Inspection code is displayed when compressor stops due to the work of protection devices.
Display Contents to be inspected (When power is turned on)
F3 F5 F9 E8 E9 EA Eb
EC
E0–E7
63L connector (red) is open. 63H connector (yellow) is open. 2 connectors (63H/63L) are open. Indoor/outdoor communication error (Signal receiving error) (Outdoor unit) Indoor/outdoor communication error (Transmitting error) (Outdoor unit) Miswiring of indoor/outdoor unit connecting wire, excessive number of indoor units (4 units or more) Miswiring of indoor/outdoor unit connecting wire (converse wiring or disconnection) Startup time over Communication error except for outdoor unit
Display Inspection unit
0
1
2
Outdoor unit
Indoor unit 1
Indoor unit 2
Display
Contents to be inspected (During operation)
U1 U2 U3 U4 U5 U6 U7 U8 Ud UF
UH
UL
UP P1–P8 A0–A7
Abnormal high pressure (63H worked) Abnormal high discharging temperature, shortage of refrigerant Open/short circuit of discharging thermistor (TH4) Open/short of outdoor unit thermistors (
TH3, TH32, TH33, TH6, TH7 and TH8
) Abnormal temperature of heatsink Abnormality of power module Abnormality of superheat due to low discharge temperature Abnormality in outdoor fan motor Overheat protection Compressor overcurrent interruption (When Comp. locked) Current sensor error Abnormal low pressure(63L worked) Compressor overcurrent interruption Abnormality of indoor units Communication error of M-NET system
OCH607
65
SW2 setting
1ON2 3 4 5 6
Display detail
Explanation for display Unit
Pipe temperature/Liquid (TH3)
−40–194
−40–194 (−40–90:) (When the coil thermistor detects 0˚F or below, “–” and temperature are displayed by turns.) (Example) When −10˚F;
0.5 s 0.5 s 2 s
˚F
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
Discharge temperature (TH4) 37–327
Output step of outdoor FAN 0–10
The number of ON/OFF times of com­pressor 0–9999
Compressor integrating operation times 0–9999
37–327 (3–164:) (When the discharge thermistor detects 100˚F or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 105˚F;
0.5 s 0.5 s 2 s
˚F
Step
100 times
10 hours
0–10
0–9999 (When the number of times is 100 or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 42500 times (425 ×100 times);
0.5 s 0.5 s 2 s
0–9999 (When it is 100 hours or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 2450 hours (245 ×10 hours);
0.5 s 0.5 s 2 s
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
Compressor operating current 0–50
LEV-A opening pulse 0–480
0–50 Note: Omit the figures after the decimal fractions.
0–480 (When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 150 pulse;
0.5 s 0.5 s 2 s
A
Pulse
Error postponement code history (1) of outdoor unit
Postponement code display Blinking: During postponement Lighting: Cancellation of postponement “00” is displayed in case of no postponement.
Code
display
Code
display
Operation mode on error occurring Operation mode of when operation stops due to
error is displayed by setting SW2 like below.
1ON2 3 4 5 6
(SW2)
10
1ON2 3 4 5 6
Compressor operating frequency 0–255
0–255 (When it is 100 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 125 Hz;
0.5 s 0.5 s 2 s
Hz
1
05
4
25
4
25
1
25
1
50
1ON2 3 4 5 6
OCH607
66
SW2 setting
1ON2 3 4 5 6
Display detail
Explanation for display Unit
Pipe temperature/Liquid (TH3) on error occurring
−40–194
−40–194 (–40–90:) (When the coil thermistor detects 0˚F or below, “–” and temperature are displayed by turns.) (Example) When –15˚F;
0.5 s 0.5 s 2 s
˚F
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
Compressor temperature (TH4) or discharge temperature (TH4) on error occurring 37–327
Compressor operating current on error occurring 0–50
Error history (1) (latest) Alternate display of abnormal unit number and code
Error history (2) Alternate display of error unit number and code
37–327 (3–164:) (When the temperature is 100˚F or more, the hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 130˚F;
0.5 s 0.5 s 2 s
˚F
A
Code
display
Code
display
0–50
When no error history, “ 0 ” and “– –” are displayed by turns.
When no error history, “ 0 ” and “– –” are displayed by turns.
1ON2 3 4 5 6
Thermostat ON time 0–999
Test run elapsed time 0–120
0–999 (When it is 100 minutes or more, the hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 245 minutes;
0.5 s 0.5 s 2 s
0–120 (When it is 100 minutes or more, the hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 105 minutes;
0.5 s 0.5 s 2 s
Minute
Minute
15
1
30
2
45
1
05
OCH607
67
SW2 setting
1ON2 3 4 5 6
Display detail
Explanation for display
Unit
Capacity setting display
Displayed as an outdoor capacity code
Code
display
1ON2 3 4 5 6
1ON2 3 4 5 6
Outdoor unit setting information
Indoor pipe temperature/Liquid (TH2(1)) Indoor 1
−38–190
Code
display
˚F
−38–190 (−39–88:) (When the temperature is 0ºF or less, “–” and temperature are displayed by turns.)
1ON2 3 4 5 6
1ON2 3 4 5 6
Indoor room temperature (TH1) 46–102
HA30N
Capacity Code
14 20
HA36N
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P/
Cooling only
Single phase/3 phase
Display details
0: H·P 1: Cooling only
0:
Single phase
2:
3 phase
Setting details
Defrosting switch
Display details
0: Normal 1: For high humidity
(Example) When heat pump, 3 phase and defrosting
(normal) are set up, “20” is displayed.
1ON2 3 4 5 6
1ON2 3 4 5 6
Indoor pipe temperature/Cond./Eva. (TH5(1)) Indoor 1
−38–190
−38–190 (−39–88:) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.)
˚F
−38–190 (−39–88:) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.)
−38–190 (−39–88:) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.)
˚F
˚F
˚F
46–102 (8–39:)
Indoor pipe temperature/Liquid (TH2(2)) Indoor 2
−38–190
Indoor pipe temperature/Cond./Eva. (TH5(2)) Indoor 2
−38–190
1ON2 3 4 5 6
The number of connected indoor units
Unit
0–3 (The number of connected indoor units are dis­played.)
OCH607
68
1ON2 3 4 5 6
˚F
Discharge superheat. SHd 0–327
Cooling = TH4−TH6 Heating = TH4−TH5
0–327 (0–182:) (When the temperature is 100˚F or more, hun­ dreds digit, tens digit and ones digit are displayed by turns.)
˚F
Sub cool. SC 0–234
Cooling = TH6-TH3 Heating = TH5-TH2
0–234 (0–130:) (When the temperature is 100˚F or more, hundreds digit, tens digit and ones digit are displayed by turns.)
0.1 A
Input current of outdoor unit
0–500 (When it is 100 or more, hundreds digit, tens digit and ones digit are displayed by turns.)
Code
display
U9 error detail history (latest)
Error details Code (No error) 00 Overvoltage 01 Undervoltage 02 Input current sensor error 04 ACTM error 20
DC bus voltage 180–370
180–370 (When it is 100V or more, hundreds digit, tens digit and ones digit are displayed by turns.)
V
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
SW2 setting
1ON2 3 4 5 6
Display detail
Explanation for display Unit
˚F
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
Indoor setting temperature 62–86
Outdoor pipe temperature/2-phase (TH6)
−38–190
Outdoor heat sink temperature (TH8)
−40–327
62–86 (17–30:)
˚F
˚F
˚F
−38–190 (−39–88:) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.)
−40–327 (−40–164:) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.) (When the thermistor detects 100˚F or more, hundreds digit, tens digit and ones digit are displayed by turns.)
Outdoor ambient temperature (TH7)
−38–190
−38–190 (−39–88:) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.)
Display examples for multiple errors: Overvoltage (01) + Undervoltage (02) = 03 Input current sensor error (04) + ACTM error = 24
OCH607
69
SW2 setting
Display detail
Explanation for display Unit
1ON2 3 4 5 6
%
Capacity save 0–100 When air conditioner is connected to M-NET and capacity save mode is demanded, a value from “0” to “100” is displayed. When there is no setting of capacity save “100” is displayed.
0–100 (When the capacity is 100%, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 100%;
0.5 s 0.5 s 2 s
00
1
Code
display
Error postponement code history (2) of outdoor unit
Postponement code display Blinking: During postponement Lighting: Cancellation of postponement “00” is displayed in case of no postponement.
Code
display
Error postponement code history (3) of outdoor unit
Postponement code display Blinking: During postponement Lighting: Cancellation of postponement “00” is displayed in case of no postponement.
Code
display
Error history (3) (Oldest) Alternate display of abnormal unit number and code.
When no error history, “0” and “– –“ are displayed by turns.
3: Outdoor pipe temperature/Liquid (TH3, TH32) 6: Outdoor pipe temperature/2-phase (TH6) 7: Outdoor ambient temperature (TH7) 8: Outdoor heat sink (TH8)
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
Error thermistor display
When there is no error thermistor, “–“ is displayed.
Code
display
Operation frequency on error occurring 0–255
0–255 (When it is 100 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 125 Hz;
0.5 s 0.5 s 2 s
25
1
1ON2 3 4 5 6
Hz
Fan step on error occurring 0–10
0–10
1ON2 3 4 5 6
Step
OCH607
70
SW2 setting
Display detail
Explanation for display Unit
1ON2 3 4 5 6
Pulse
LEV-A opening pulse on error occurring 0–480
0–480 (When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 130 pulse;
0.5 s 0.5 s 2 s
30
1
˚F
Indoor room temperature (TH1) on error occurring 46–102
46–102 (8–39°C)
˚F
Indoor pipe temperature/Liquid (TH2) on error occurring
−38–190
−38–190 (−39–88°C) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.) (Example) When −15˚F;
0.5 s 0.5 s 2 s
15
Indoor pipe temperature/Cond./Eva. (TH5) on error occurring
−38–190
−38–190 (−39–88°C) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.) (Example) When –15˚F;
0.5 s 0.5 s 2 s
15
Outdoor pipe temperature/2-phase (TH6) on error occurring
−38–190
−38–190 (−39–88°C) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.) (Example) When –15˚F;
0.5 s 0.5 s 2 s
15
Outdoor ambient temperature (TH7) on error occurring
−38–190
−38–190 (−39–88°C) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.) (Example) When –15˚F;
0.5 s 0.5 s 2 s
15
Outdoor heat sink temperature (TH8) on error occurring
−40–392
−40–392 (−40–200°C) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.) (When the temperature is 100˚F or more, hundreds digit, tens digit and ones digit are displayed by turns.)
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
˚F
˚F
˚F
˚F
OCH607
71
SW2 setting Display detail Explanation for display Unit
°F
0–327 (0–182:) (When the temperature is 100˚F or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 150°F;
0.5 s 0.5 s 2 s
50
1
Sub cool on error occurring. SC 0–234
Cooling = TH6−TH3 Heating = TH5−TH2
0–234 (0–130:) (When the temperature is 100˚F or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 115°F;
0.5 s 0.5 s 2 s
15
1
Thermo-ON time until error stops 0–999
0–999 (When it is 100 minutes or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 415 minutes;
0.5 s 0.5 s 2 s
15
4
1ON2 3 4 5 6
Discharge superheat on error occurring SHd 0–327
Cooling = TH4−TH6 Heating = TH4−TH5
1ON2 3 4 5 6
1ON2 3 4 5 6
°F
Minute
1ON2 3 4 5 6
U9 Error details (To be shown while error call is deferred.)
Code
display
Pulse
LEV-B opening pulse 0–480
0–480 (When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns.)
1ON2 3 4 5 6
0–480 (When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns.)
Pulse
1ON2 3 4 5 6
LEV-C opening pulse 0–480
Outdoor pipe temperature (TH33)
−38–190
1ON2 3 4 5 6
˚F
−38–190 (−39–88°C) (When the temperature is 0˚F or less, “–” and temperature are displayed by turns.) (Example) When –15˚F;
0.5 s 0.5 s 2 s
15
Error details Code (No error) 00 Overvoltage 01 Undervoltage 02 Input current sensor error 04 ACTM error 20
Display examples for multiple errors: Overvoltage (01) + Undervoltage (02) = 03 Input current sensor error (04) + ACTM error = 24
OCH607
72
SW2 setting
Display detail
Explanation for display Unit
Controlling status of compressor operating frequency
1ON2 3 4 5 6
Code
display
The following code will be a help to know the operating status of unit.
Display
Compressor operating frequency control
Display Compressor operating frequency control
Primary current control Secondary current control
1 2
1
4
8
2
The tens digit
The ones digit
(In this digit, the total number of
activated control is displayed.)
Preventive control for excessive temperature rise of discharge temperature Preventive control for excessive temperature rise of condensing temperature Frosting preventing control
Preventive control for excessive temperature rise of heat sink
(Example) The following controls are activated.
• Primary current control
• Preventive control for excessive temper-
ature rise of condensing temperature
• Preventive control for excessive temper-
ature rise of heat sink
1a
LED
OCH607
73
11
EASY MAINTENANCE FUNCTION
11-1. SMOOTH MAINTENANCE
Maintenance data, such as the indoor/outdoor unit’s heat exchanger temperature and compressor operation current can be displayed with “Smooth maintenance”.
This cannot be executed during test operation. Depending on the combination with the outdoor unit, this may not be supported by some models.
F1 F2 F3 F4
Check menu
Cursor
Service menu:
Error history Refrigerant volume check Refrigerant leak check Smooth maintenance Request code
Smooth maintenance
Begin:
Smooth maintenance
Exit:
Ref.address Stable mode
Cursor
Address
Ref.address Stable mode
Stabilization→Collecting
Cool / Heat/ Normal
Cool / Heat/ Normal
Smooth maintenance
Return:
Smooth maintenance
Return:
Smooth maintenance
Return:
Page
Page
Page
COMP. current COMP. run time COMP. On / Off COMP. frequency
A
Hz
Hr times
Hr
Ref. address
Cool
Ref.address
Cool
Ref.address
Cool
Sub cool OU TH4 temp. OU TH6 temp. OU TH7 temp.
IU air temp. IU HEX temp. IU filter time
Select "Smooth maintenance" with the F1 or F2 button, and press the button.
Select "Check" with the F1
or F2 button, and press the button.
Select "Service" from the Main menu, and press the
button.
Set each item.
Select the item to be changed with the
F1orF2
button.
Select the required setting with the
F3
or
F4
button.
<Ref.address>setting [ 0 ] to [ 15 ]
<Stable mode>setting [ Cool ] / [ Heat ] / [ Normal ]
Press the
button, Fixed operation will start.
Note: Stable mode will take approx. 20 minutes.
The operation data will appear.
The Compressor-Accumulated operating (COMP. run) time is 10-hour unit, and the Compressor-Number of operation times (COMP. ON/OFF) is a 100­time unit (fractions discarded).
Navigating through the screens
• To go back to the Main menu ..........
button
• To return to the previous screen .......
button
1
2
3
OCH607
74
11-2. GUIDE FOR OPERATION CONDITION
Inspection item Result
Power supply
Loose con-
nection
Breaker Good Retightened
Terminal block Outdoor Unit Good Retightened
Indoor Unit Good Retightened
(Insulation resistance) M"
(Voltage) V
1 Accumulated operating time Time
2 Number of ON/OFF times Times
3 Current A
4
Refrigerant/heat exchanger temperature
COOL °F HEAT °F
5
Refrigerant/discharge temperature
COOL °F HEAT °F
6 Air/outside air temperature COOL °F HEAT °F
(Air/discharge temperature) COOL °F HEAT °F
Appearance Good
Cleaning required
Heat exchanger Good
Cleaning required
Sound/vibration None Present
Air/intake air temperature COOL °F HEAT °F
(Air/discharge temperature) COOL °F HEAT °F
8
7
9
Refrigerant/heat exchanger temperature
COOL °F HEAT °F
Filter operating time *
1
Time
Decorative panel Good
Cleaning required
Filter Good
Cleaning required
Fan Good
Cleaning required
Heat exchanger Good
Cleaning required
Sound/vibration None Present
Com-
pressor
Temperature
Cleanli-
ness
Outdoor Unit
Temperature
Cleanliness
Indoor Unit
*1 The filter operating time is the time that has elapsed since the filter was reset.
Check Points
Enter the temperature differences between 5, 4, 7 and 8 into the graph given below. Operation state is determined according to the plotted areas on the graph. For data measurements, set the fan speed to "Hi" before activat­ing maintenance mode.
Is "000" displayed stably in Display D on the remote controller?
Is "000" displayed stably in Display
D
on the remote controller?
(
5
Discharge temperature) – (4 Outdoor
heat exchanger temperature)
(
7
Indoor intake air temperature) – (
8
Indoor heat exchanger temperature)
(
5
Discharge temperature) – (8 Indoor
heat exchanger temperature)
(
8
Indoor heat exchanger temperature) –
(
7
Indoor intake air temperature)
Cool
Classification Item Result
Inspection
Temperature
difference
Heat
Inspection
Temperature
difference
Stable Unstable
°F
°F
Stable Unstable
°F
°F
Notes:
Fixed Hz operation may not be possible under the following tempera­ture ranges. A)In cool mode, outdoor intake air temperature is 104 °For higher or
indoor intake air temperature is 73 °F or lower.
B)In heat mode, outdoor intake air temperature is 68 °F or higher or
indoor intake air temperature is 77 °F or lower.
2. If the air conditioner is operated at a temperature range other than the ones above but operation is not stabilized after 30 minutes or more have elapsed, carry out inspection.
3. In heat mode, the operation state may vary due to frost forming on the outdoor heat exchanger.
°F
81
72
63
54
45
36
27
18
9
ºF
81
70
63
54
45
36
27
18
9
ºF
81
70
63
54
45
36
27
18
9
0 18 36 54 72 90 108 126 144
Normal
Filter inspection
Inspection C
Inspection A
Inspection B
°F
81
72
63
54
45
36
27
18
9
°F°F
Normal
Filter inspection
Inspection C
Inspection A
Inspection B
Cool mode Heat mode
(
7
Indoor intake air temperature)— (
8
Indoor
heat exchanger temperature)
(
8
Indoor heat exchanger temperature) —
(
7
Indoor intake air temperature)
[5 Discharge temperature] – [4 Outdoor heat exchanger temperature)
[5 Discharge temperature] – [8 Indoor heat exchanger temperature)
Result
Normal operation state
Filter may be clogged.
*
2
Performance has dropped. Detailed in-
spection is necessary.
Refrigerant amount is dropping.
Filter or indoor heat exchanger may be
clogged.
Area Check item
Judgment
Cool Heat
Normal
Filter inspection
Inspection A
Inspection B
Inspection C
18 36 54 72 90 108 126 144
1.
Note: The above judgment is just guide based on Japanese standard conditions. It may be changed depending on the indoor and outdoor temperature.
*
2
It may be judged as “filter inspection” due to the outdoor and indoor
temperature, even though it is not clogged.
OCH607
75
12 FUNCTION SETTING
Power failure automatic recovery Indoor temperature detecting
LOSSNAY connectivity
Power supply voltage Frost prevention temperature Humidifier control
Change of defrosting control
Not available Available Average data from each indoor unit Data from the indoor unit with remote controllers Data from main remote controller Not supported Supported (indoor unit dose not intake outdoor air through LOSSNAY) Supported (indoor unit intakes outdoor air through LOSSNAY) 230 V 208 V 36°F [2:] (Normal) 37°F [3:] When the compressor operates, the humidifier also operates. When the fan operates, the humidifier also operates. Standard For high humidity
1 2 1 2 3 1 2 3 1 2 1 2 1 2 1 2
01
(101)
02
(–)
03
(103)
04
(104)
15
(115)
16
(116)
17
(117)
The setting is applied to all the units in the same refrigerant system.
Mode No.
Wired remote controller
(RF thermostat)
Function Settings
Setting No.
: Initial setting
(when sent from the factory)
Remarks
12-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be be set as necessary using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1.
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
<Table 1> Function selections
Meaning of "Function setting" mode02:indoor temperature detecting
No.
Indoor temperature(ta)=
No.1
Average data of the sensor on all the indoor units
Initial setting
ta=(A+B)/2 ta=(A+B)/2 ta=A ta=A
No.2
Data of the sensor on the indoor unit that connected with remote controller
ta=A ta=B ta=A ta=A
No.3
Data of the sensor on main remote controller
ta=C ta=C ta=C ta=C
OUTDOOR
INDOOR
REMOTE (MAIN)
REMOTE (SUB)
INDOOR
OUTDOOR
INDOOR
REMOTE (MAIN)
REMOTE (SUB)
OUTDOOR
INDOOR
REMOTE (MAIN)
OUTDOOR
INDOOR
REMOTE (MAIN)
REMOTE (SUB)
INDOOR
OCH607
76
Function
Settings
Setting No.
Filter sign
100h 2500h "Clean the filter" indicator is not displayed
Air flow
Quiet
(
Fan speed
)
Standard High ceiling
No.of air outlets
4 directions 3 directions 2 directions
Optional high efficiency
Not supported
filter
Supported
Vane setting
No vanes (Vane No.3 setting: PLA only) Vane No.1 setting Vane No.2 setting
Optional humidifier
Not supported
(
PLA only
)
Supported
Vane differential setting
No.1 setting (TH5: 75−82˚F [24–28:])
in heating mode
No.2 setting (Standard, TH5: 82–90˚F [28–32:])
(
cold wind prevention
)
No.3 setting (TH5: 90–100˚F [32–38:])
Swing
Set temperature in heating mode (7.2˚F [4:] up
) *1
Fan speed when the
Extra low
heating thermostat is OFF
Stop Keeping fan speed set by remote controller
Fan speed when the
Keeping fan speed set by remote controller
cooling thermostat is OFF
Stop
Detection of abnormality of
Detect
07
(107)
08
(108)
09
(109)
10
(110)
11
(111 )
13
(113)
14
(114)
23
(123)
24
(124)
25
(125)
27
(127)
28
(128)
the pipe temperature (P8
)
Neglect
1 2 3 1 2 3 1 2 3 1 2 1 2 3 1 2 1 2 3 1 2 1 2 1 2 3 1 2 1 2
Not available Swing Available Wave air flow Available Not available
}
PLA-BA
: Initial setting (Factory setting
)
- : Not available
4-Way
cassette
PLA-BA
PKA-HA
PKA-HAL
-
-
-
-
-
-
-
-
-
-
PKA-KA
PKA-KAL
-
-
-
-
-
-
-
-
-
-
Ceiling
Suspended
PCA-KA
-
-
-
-
-
Mode No.
Wired remote controller
(RF thermostat)
Wall mounted
(2) Functions available when setting the unit number to 01-03 or AL (07 in the case of the IR wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the indoor unit number.
• When setting functions for a simultaneous twin indoor unit system, set the unit number to 01 to 03 for each indoor unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin-indoor unit system, set refrigerant address to AL (07 in the case of the IR wireless remote controller) referring to 4 setting the indoor unit number.
Mode No.11
Setting No. Settings PLA-BA
1
Vane No.3 setting
(
Downward position than the standard
)
Less smudging
2 Vane No.1 setting Standard
3 Vane No.2 setting
(
Upward position than the standard
)
Less draft *
* Be careful of the smudge on ceiling.
PCA-KA
No vane function
Standard Less draft *
(
Upward position than the standard
)
*1 PKA-HA(L)/KA(L): 3.6-F [2:]) up
OCH607
77
Main
Main display:
Cursor Page
Main menu
Maintenance Initial setting Service
F1 F2 F3 F4
Service menu
Cursor
Select:
Enter maintenance password
unem ecivreS
unem ecivreS
rosruC
rosruC
:unem niaM
:unem niaM
Test run Input maintenance info. Function setting Check Self check
Maintenance password Remote controller check
Service menu
Service menu:
Not available.
Please stop the unit.
2
When the Service menu is selected, a window will appear asking for the pass­word.
To enter the current maintenance password (4 numerical digits), move the cursor to the digit you want to change with the F1
or F2 button.
Set each number (0 through 9) with the
F3
or
F4
button.
Then, press the
button.
1
Select "Service" from the Main menu, and press the button.
*At the main display, the menu button and select "Service" to make the
maintenance setting.
Maintenance password is required
Note: The initial maintenance password is "9999". Change the default
password as necessary to prevent unauthorized access. Have the password available for those who need it.
: If you forget your maintenance password, you can initialize the
password to the default password "9999" by pressing and holding the
F1
and
F2
buttons simultaneously for three seconds on the
maintenance password setting screen.
3
If the password matches, the Service menu will appear.
The type of menu that appears depends on the connected indoor units’ type.
Note: Air conditioning units may need to be stopped to make certain set-
tings. There may be some settings that cannot be made when the system is centrally controlled.
A screen will appear that indicates the setting has been saved.
Navigating through the screens
• To go back to the Main menu ..................
button
• To return to the previous screen ...............
button
12-1-1. Selecting functions using the wired remote controller
<Service menu>
OCH607
78
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Test run Input maintenance info. Function setting Check Self check
F1 F2 F3 F4
Function setting
Cursor Address
Monitor:
Ref. address Unit No.
Grp./1/2/3/4/All
Function setting
Cursor Cursor
Request:
Ref. address Mode 1 Mode 2 Mode 3 Mode 4
Grp.
F1 F2 F3 F4
Function setting
Cursor Cursor
Request:
Ref. address Mode 5 Mode 6 Mode 15 Mode 16
Grp.
2
Set the indoor unit refrigerant addresses and unit numbers with the F1
through F4 buttons, and then press the button to confirm the current setting.
Select "Function setting" with the F1
or F2 button, and press the button.
3
When data collection from the indoor units is completed, the current settings appears highlighted.
Non-highlighted items indicate that no function settings are made. Screen appearance varies depending on the "Unit No." setting.
4
Use the F1 or F2 button to move the cursor to select the mode number,
and change the setting number with the F3
or F4 button.
1
Select "Service" from the Main menu, and press the button.
<Checking the indoor unit No.>
When the
button is pressed, the target indoor unit will start fan operation.
If the unit is common or when running all units, all indoor units for the selected
refrigerant address will start fan operation.
F1 F2 F3 F4
Function setting
Ref. address
Sending data
Grp.
5
When the settings are completed, press the button to send the setting data from the remote controller to the indoor units.
When the transmission is successfully completed, the screen will return to the Function setting screen.
Note: • Make the above settings only on Mr. Slim units as necessary.
The above function settings are not available for the City Multi units.
Table 1 summarizes the setting options for each mode number. Refer to the indoor unit Installation Manual for the detailed information about ini­tial settings, mode numbers, and setting numbers for the indoor units.
Be sure to write down the settings for all functions if any of the initial settings has been changed after the completion of installation work.
<Function setting>
OCH607
79
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESET
SET
CLOCK
Flow of function selection procedure
The flow of the function selection procedure is shown below. This example shows how to turn off the function that raises the set temperature by 4 degrees during HEAT operation. The procedure is given after the flow chart.
1 Check the function selection setting.
2 Switch to function selection mode.
(Enter address "50" in troubleshooting mode, then press the HOUR button.)
Troubleshooting mode is the mode entered when you press the CHECK button twice to display "CHECK".
3 Specify unit No. "01" (since the function applies to unit 01). (Set address "01" while still in troubleshooting mode, then press the MINUTE button.) Note: You cannot specify the refrigerant address.
4
Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation).
(Set address "24" while still in troubleshooting mode, then press the HOUR button.)
6
Finished
8 End function selection mode. (End troubleshooting mode.)
YES
NO
Note: When you switch to function selection mode on the IR wireless remote controller's operation area, the unit ends function selection mode automatically if nothing is input for 10 minutes or longer.
5 Select setting No. "02" (OFF). (Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change unit No.
YES
NO
7
[Flow of function selection procedure]
12-1-2. Selecting functions using the IR wireless remote controller (Type C)
Functions can be selected with the IR wireless remote controller. Function selection using the IR wireless remote controller is available only for refrigerant system with wireless function. Refrigerant address cannot be specified by the IR wireless remote controller.
By setting unit number with the button, specified indoor unit starts performing fan operation. Detect which unit is assigned to which number using this function. If unit number is set to AL, all the indoor units in same refrigerant system start performing fan operation simultaneously.
[Operating instructions]
1 Check the function settings. 2 Press the button twice continuously.
CHECK
is lit and “00” blinks. Press the TEMP button once to set “50”. Direct the IR wireless remote controller toward the receiver of the indoor unit and press the button. 3 Set the unit number. Press the TEMP button to set the unit number. (Press “01” to specify the indoor unit whose unit number is 01.)
Direct the IR wireless remote controller toward the receiver of the indoor unit and press the
min
button.
Notes:
1. If a unit number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the unit number setting.
2. If the signal was not received by the sensor, you will not hear a beep or a “double ping sound” may be heard. Reenter the unit number setting
.
4 Select a mode. Press the TEMP button to set a mode. Press “24” to turn on the function that raises the set temperature by 4 degrees
during heat operation. Direct the IR wireless remote controller toward the sensor of the indoor unit and press the
h
button.
→ The sensor-operation indicator will blink and beeps will be heard to indicate the current setting number. Current setting number: 1 = 1 beep (one second) 2 = 2 beeps (one second each) 3 = 3 beeps (one second each) Notes:
1. If a mode number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the mode number.
2. If the signal was not received by the sensor, you will not hear a beep or a “double ping sound” may be heard. Reenter the mode number. 5 Select the setting number. Press the TEMP button to select the setting number. (02: Not available)
Direct the IR wireless remote controller toward the receiver of the indoor unit and press the
h
button.
→ The sensor-operation indicator will blink and beeps will be heard to indicate the setting number. Setting number: 1 = 2 beeps (0.4 seconds each) 2 = 2 beeps (0.4 seconds each, repeated twice) 3 = 2 beeps (0.4 seconds each, repeated three times)
Notes:
1. If a setting number that cannot be recognized by the unit is entered, the setting will turn back to the original setting.
2. If the signal was not received by the sensor, you will not hear a beep or a “double ping sound” may be heard. Reenter the setting number.
6 Repeat steps 4 and 5 to make an additional setting without changing unit number. 7 Repeat steps 3 to 5 to change unit number and make function settings on it. 8 Complete the function settings
Press button. Note: Do not use the IR wireless remote controller for 30 seconds after completing the function setting.
h
CHECK
min
OCH607
80
Function buttons
F1 F2 F3 F4
Press to turn ON/OFF the indoor unit.
ON/OFF button
When the backlight is off, pressing any button turns the backlight on and does not perform its function.
(except for the
(ON/OFF) button)
The functions of the function buttons change depending on the screen. Refer to the button function guide that appears at the bottom of the LCD for the functions they serve on a given screen. When the system is centrally controlled, the button function guide that corresponds to the locked button will not appear.
Press to save the setting.
SELECT button
Press to return to the previous screen.
RETURN button
Press to bring up the Main menu.
MENU button
Operation settings will appear. When the backlight is off, pressing any button turns the backlight on and it will stay lit for a certain period of time depending on the screen.
Backlit LCD
This lamp lights up in green while the unit is in operation. It blinks while the remote controller is starting up or when there is an error.
ON/OFF lamp
Main display : Press to change the operation mode. Main menu : Press to move the cursor down.
Function button
F1
Main display : Press to decrease temperature. Main menu : Press to move the cursor up.
Function button
F2
Main display : Press to increase temperature. Main menu : Press to go to the previous page.
Function button
F3
Main display : Press to change the fan speed. Main menu : Press to go to the next page.
Function button
F4
Fri
Room
Set temp.
Mode Temp. Fan
Cool Auto
Main
Main display:
Cursor Page
Main menu
Vane·Louver·Vent. (Lossnay) High power Timer Weekly timer OU silent mode
<Main display> <Main menu>
Function guide
12-2. FUNCTION SELECTION OF REMOTE CONTROLLER
OCH607
81
Not all functions are available on all models of indoor units.
Energy saving
Auto return
Schedule
Night setback
Main menu
Press the
MENU
button.
Move the cursor to the desired item with the
F1
and
F2
buttons, and press the
SELECT
button.
Vane · Louver · Vent. (Lossnay)
High power
Weekly timer
Restriction
Maintenance
Initial setting
ON/OFF timer
Auto-Off timer
Temp. range
Operation lock
Manual vane angle
Main/sub
Timer
Main display
Contrast
Display details
Auto mode
Administrator password
Language selection
Service
Input maintenance info.
Function setting
Check
Self check
Maintenance password
Remote controller check
Test run
Clock
Auto descending panel
Menu structure
Filter information
Error information
OCH607
82
Setting and display items Setting details
Vane · Louver · Vent. (Lossnay) Use to set the vane angle.
• Select a desired vane setting from ve different settings.
Use to turn ON/OFF the louver.
• Select a desired setting from "ON" and "OFF."
Use to set the amount of ventilation.
• Select a desired setting from "Off," "Low," and "High."
High power Use to reach the comfortable room temperature quickly.
• Units can be operated in the High-power mode for up to 30 minutes.
Timer ON/OFF timer* Use to set the operation ON/OFF times.
• Time can be set in 5-minute increments.
Auto-Off timer Use to set the Auto-Off time.
• Time can be set to a value from 30 to 240 in 10-minute increments.
Weekly timer* Use to set the weekly operation ON/OFF times.
• Up to 8 operation patterns can be set for each day. (Not valid when the ON/OFF timer is enabled.)
Restriction Temp. range Use to restrict the preset temperature range.
• Different temperature ranges can be set for different operation modes.
Operation lock Use to lock selected functions.
• The locked functions cannot be operated.
Energy saving Auto return Use to get the units to operate at the preset temperature after performing energy-save operation for a
specied time period.
• Time can be set to a value from 30 and 120 in 10-minute increments. (This function will not be valid when the preset temperature ranges are restricted.)
Schedule* Set the start/stop times to operate the units in the energy-save mode for each day of the week, and set the
energy-saving rate.
• Up to 4 energy-save operation patterns can be set for each day.
• Time can be set in 5-minute increments.
• Energy-saving rate can be set to a value from 0% or 50 to 90% in 10% increments.
Night setback* Use to make Night setback settings.
• Select "Yes" to enable the setting, and "No" to disable the setting. The temperature range and the start/stop times can be set.
Filter information Use to check the lter status.
• The lter sign can be reset.
Error information Use to check error information when an error occurs.
• Check code, error source, refrigerant address, unit model, manufacturing number, contact information (dealer's
phone number) can be displayed.
(The unit model, manufacturing number, and contact information need to be registered in advance to be displayed.)
Maintenance Auto descending panel Auto descending panel (Optional parts) Up / Down you can do.
Manual vane angle Use to set the vane angle for each vane to a xed position.
Initial setting Main/Sub When connecting two remote controllers, one of them needs to be designated as a sub controller.
Clock Use to set the current time.
Main display Use to switch between "Full" and "Basic" modes for the Main display.
• The initial setting is "Full."
Contrast Use to adjust screen contrast.
Display details Make the settings for the remote controller related items as necessary.
Clock: The initial settings are "Yes" and "24h" format. Temperature: Set either Celsius (°C) or Fahrenheit (°F). Room temp. : Set Show or Hide. Auto mode: Set the Auto mode display or Only Auto display.
Auto mode Whether or not to use the Auto mode can be selected by using the button.
This setting is valid only when indoor units with the Auto mode function are connected.
Administrator password
The administrator password is required to make the settings for the following items.
• Timer setting • Energy-save setting • Weekly timer setting
• Restriction setting • Outdoor unit silent mode setting • Night set back
Language selection Use to select the desired language.
Service Test run Select "Test run" from the Service menu to bring up the Test run menu.
• Test run • Drain pump test run
Input maintenance Select "Input maintenance Info." from the Service menu to bring up the Maintenance information screen.
The following settings can be made from the Maintenance Information screen.
• Model name input • Serial No. input • Dealer information input
Function setting Make the settings for the indoor unit functions via the remote controller as necessary. Check Error history: Display the error history and execute “delete error history”.
Refrigerant leak check: Refrigerant leaks can be judged. Smooth maintenance: The indoor and outdoor maintenance data can be displayed. Request code: Details of the operation data including each thermistor temperature and error history can be checked.
Self check Error history of each unit can be checked via the remote controller. Maintenance password Use to change the maintenance password. Remote controller check
When the remote controller does not work properly, use the remote controller checking function to trouble­shoot the problem.
Main menu list
* Clock setting is required.
OCH607
83
12-3. Function selection of the IR wireless remote controller TEMPERATURE DISPLAY -C/-F SETTING (Change of temp mode from -F to -C)
1 Press the set button with something sharp at the end.
MODEL SELECT
blinks.
2 Press the
AUTO START
button. “°F” blinks.
3 Press the
button. “°C” blinks.
4 Press the set button with something sharp at the end.
MODEL SELECT
is lighted for 3 seconds, then turned off.
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST
RUN
°F °C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
1 4
1 4
2
2
3
3
OCH607
84
13
MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER
Details on the operation data including each thermistor temperature and error history can be conrmed with the remote controller.
F1 F2 F3 F4
Check menu
Cursor
Service menu:
Error history Refrigerant volume check Refrigerant leak check Smooth maintenance Request code
Select "Request code" with the F1 or F2 button, and press the button.
Select "Check" with the F1
or F2 button, and press the button.
2
Set the Refrigerant address and Request code.
Select the item to be changed with the
F1
or
F2
button.
Select the required setting with the
F3
or
F4
button.
<Ref.address>setting [ 0 ] – [ 15 ]
<Request code>setting
Press the
button, Data will be collected and displayed.
F1 F2 F3 F4
Request code
Request:
Request:
Request code
Ref.address
Request code
Cursor −+
Ref.address
Request code
Cursor
−+
Request code: 004 Discharge temperature: 156
°F
1
Select "Service" from the Main menu, and press the button.
13-1. HOW TO "MONITOR THE OPERATION DATA"
13-1-1. PAR-30MAA/PAR-31MAA
OCH607
85
13-2. REQUEST CODE LIST
Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed.
Request code
Request content
Description
(Display range)
Unit Remarks
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
Operation state
Compressor-Operating current (rms)
Compressor-Accumulated operating time
Compressor-Number of operation times
Discharge temperature (TH4)
Outdoor unit - Liquid pipe 1 temperature (TH3)
Outdoor unit - Liquid pipe 2 temperature
Outdoor unit-2-phase pipe temperature (TH6)
Outdoor unit-Ambient air temperature (TH7)
Outdoor unit-Heatsink temperature (TH8)
Discharge superheat (SHd)
Sub-cool (SC)
Compressor-Operating frequency
Compressor-Target operating frequency
Outdoor unit-Fan output step
Outdoor unit-Fan 1 speed
(Only for air conditioners with DC fan motor)
Outdoor unit-Fan 2 speed
(Only for air conditioners with DC fan motor)
LEV (A) opening
LEV (B) opening
Primary current
DC bus voltage
Number of connected indoor units
Indoor unit-Setting temperature
Indoor unit-Intake air temperature <Measured by thermostat>
Indoor unit-Intake air temperature (Unit No. 1)
<Heat mode-4-deg correction>
Indoor unit-Intake air temperature (Unit No. 2)
<Heat mode-4-deg correction>
Indoor unit-Intake air temperature (Unit No. 3)
<Heat mode-4-deg correction>
Indoor unit-Intake air temperature (Unit No. 4)
<Heat mode-4-deg correction>
Indoor unit - Liquid pipe temperature (Unit No. 1)
Indoor unit - Liquid pipe temperature (Unit No. 2)
Indoor unit - Liquid pipe temperature (Unit No. 3)
Indoor unit - Liquid pipe temperature (Unit No. 4)
Indoor unit-Cond./Eva. pipe temperature (Unit No. 1)
Indoor unit-Cond./Eva. pipe temperature (Unit No. 2)
Indoor unit-Cond./Eva. pipe temperature (Unit No. 3)
Indoor unit-Cond./Eva. pipe temperature (Unit No. 4)
Thermostat ON operating time
Test run elapsed time
Refer to “13-2-1. Detail Contents in Request Code”.
0–50
0–9999
0–9999
37–327
40–194
40–194
0–9999
0–9999
0–50
A
10 hours
100 times
°F
°F
°F
°F
Outdoor suction pipe temperature (TH32)
°F
°F
°F
°F
°F
Hz
Hz
Step
rpm
rpm
Pulses
Pulses
LEV (C) opening
Pulses
A
V
Units
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
Minutes
Minutes
"0" is displayed if the air conditioner is a single-fan type.
"0" is displayed if the target unit is not present.
"0"
is displayed if the target unit is not present.
"0"
is displayed if the target unit is not present.
Not possible to activate maintenance mode during the test run.
38–190
38–190
38–190
40–327
0–327
0–234
0–255
0–255
0–10
0–500
0–500
0–500
180–370
0–4
62–86
46–102
46–102
46–102
46–102
46–102
−38–190
−38–190
−38–190
−38–190
−38–190
−38–190
−38–190
−38–190
0–999
0–120
OCH607
86
Request code
Request content
Description
(Display range)
Unit Remarks
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
Indoor unit-Control state
Outdoor unit-Control state
Compressor-Frequency control state
Outdoor unit-Fan control state
Actuator output state
Error content (U9)
Signal transmission demand capacity
Contact demand capacity
External input state (silent mode, etc.)
Outdoor unit-Capacity setting display
Outdoor unit-Setting information
Outdoor unit-SW1 setting information
Outdoor unit-SW2 setting information
Outdoor unit-SW4 setting information
Outdoor unit-SW5 setting information
Outdoor unit-SW6 setting information
Outdoor unit-SW7 setting information
Outdoor unit-SW8 setting information
Outdoor unit-SW9 setting information
Outdoor unit-SW10 setting information
M-NET adapter connection (presence/absence)
Display of execution of replace/wash operation
Outdoor unit-Microcomputer version information
Outdoor unit-Microcomputer version information (sub No.)
Outdoor unit - Error postponement history 1 (latest)
Outdoor unit - Error postponement history 2 (previous)
Outdoor unit - Error postponement history 3 (last but one)
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to
“13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
"0000": Not connected
Examples) Ver 5.01
Auxiliary information (displayed after
version information)
Examples) Ver 5.01 A000
Displays postponement code. (" - - " is
displayed if no postponement code is present)
Displays postponement code. (" - - " is
displayed if no postponement code is present)
Displays postponement code. (" - - " is
displayed if no postponement code is present)
%
Ver
Code
Code
Code
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to 13-2-1.Detail Contents in Request Code.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
Refer to “13-2-1.Detail Contents in Request Code”.
"0001": Connected
"0000": Not washed "0001": Washed
"0501"
"A000"
0–255
OCH607
87
Request code
Request content
Description
(Display range)
Unit Remarks
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
~
146
147
148
149
150
151
152
Displays error history. (" - - " is displayed if no history is present.)
Displays error history. (" - - " is displayed if no history is present.)
Displays error history. (" - - " is displayed if no history is present.)
: TH3
6 : TH6
7 : TH7
8 : TH8
0 : No thermistor error
Displayed in the same way as request code "0".
Code
Code
Code
Sensor
number
A
10 hours
100 times
˚F
˚F
˚F
˚F
˚F
˚F
˚F
˚F
Hz
Step
rpm
rpm
Pulses
Pulses
Minutes
˚F
˚F
˚F
˚F
˚F
˚F
"0" is displayed if the air conditioner is a single-
fan type.
Average value of all indoor units is displayed if the air condi-
tioner consists of 2 or more indoor units (twin).
Average value of all indoor units is displayed if the air condi-
tioner consists of 2 or more indoor units (twin).
Error history 1 (latest)
Error history 2 (second to last)
Error history 3 (third to last)
Abnormal thermistor display
(TH3/TH6/TH7/TH8)
Operation mode at time of error
Compressor-Operating current at time of error
Compressor-Accumulated operating time at time of error
Compressor-Number of operation times at time of error
Discharge temperature at time of error
Outdoor unit - Liquid pipe 1 temperature (TH3) at time of error
Outdoor unit - Liquid pipe 2 temperature at time of error
Outdoor unit-2-phase pipe temperature (TH6) at time of error
Outdoor unit-Outside air temperature (TH7) at time of error
Outdoor unit-Heat sink temperature (TH8) at time of error
Discharge super heat (SHd) at time of error
Sub-cool (SC) at time of error
Compressor-Operating frequency at time of error
Outdoor unit at time of error
· Fan output step
Outdoor unit at time of error
· Fan 1 speed (Only for air conditioners with DC fan)
Outdoor unit at time of error
· Fan 2 speed (Only for air conditioners with DC fan)
LEV (A) opening at time of error
LEV (B) opening at time of error
Thermostat ON time until operation stops due to error
Indoor - Liquid pipe temperature at time of error
Indoor-Cond./Eva. pipe temperature at time of error
Indoor at time of error
· Intake air temperature <Thermostat judge temperature>
Indoor-Actual intake air temperature
Indoor - Liquid pipe temperature
Indoor-Cond./Eva. pipe temperature
3
0–9999
37–327
−40–194
−40–194
−38–190
−38–190
−40–327
0–327
0–234
0–255
0–10
0–9999
0–9999
0–500
0–500
0–999
−38–190
−38–190
−38–190
−38–190
−38–190
−38–190
0–50
0–9999
OCH607
88
Request code
Request content
Description
(Display range)
Unit Remarks
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
~
189
190
191
192
~
764
765
766
767
Fan control data
00 **" "**" indicates fan control data.
"00 **" "**" indicates fan control data.
Refer to “13-2-1 Detail Contents in Request Code”.
Undefined
Refer to “13-2-1 Detail Contents in Request Code”.
Undefined
Examples) Ver 5.01 "0501"
Auxiliary information (displayed after version information)
Examples) Ver 5.01 A000 "A000"
1 hour
10 hours
Ver
For indoor fan phase control
For indoor fan pulsation control
For indoor DC brushless motor control
Indoor-Fan operating time
(After filter is reset)
Indoor-Total operating time
(Fan motor ON time)
Indoor fan output value (Sj value)
Indoor fan output value
(Pulsation ON/OFF)
Indoor fan output value (duty value)
Indoor unit-Model setting information
Indoor unit-Capacity setting information
Indoor unit-SW3 information
Wireless pair No. (indoor control board side) setting
Indoor unit-SW5 information
Indoor unit-Microcomputer version information
Indoor unit-Microcomputer version information (sub No.)
Stable operation (Heat mode)
Stable operation (Cool mode)
Stable operation cancellation
This request code is not provided to collect data. It is used to fix the operation state.
This request code is not provided to collect data. It is used to fix the operation state.
This request code is not provided to collect data. It is used to cancel the operation state that has been
fixed by request codes "765" and "766".
"
Refer to “13-2-1 Detail Contents in Request Code”.
0–9999
0–9999
0–255
OCH607
89
Frequency control state
2
Display
Discharge temperature
Condensation temperature
Anti-freeze
Heat sink temperature
overheat prevention
overheat prevention
protection control
overheat prevention 0 1 Controlled 2 Controlled 3 Controlled Controlled 4 Controlled 5 Controlled Controlled 6 Controlled Controlled 7 Controlled Controlled Controlled 8 Controlled 9 Controlled Controlled
A Controlled Controlled
b Controlled Controlled Controlled
C Controlled Controlled
d Controlled Controlled Controlled
E Controlled Controlled Controlled F Controlled Controlled Controlled Controlled
13-2-1. Detail Contents in Request Code
[Operation state] (Request code ":0")
Data display
Example) Request code "004"
Discharge temperature 156°F Refrigerant address "00"
C4
Relay output state
Operation mode
[Indoor unit – Control state] (Request code :" 50 ")
Data display
Operation mode
Display Operation mode
0 STOP FAN
C COOL DRY H HEAT
d DEFROST
Relay output state
Display
Power currently
Compressor 4-way valve Solenoid valve
supplied to compressor
Unit No. 4 state
Unit No. 3 state
Unit No. 2 state
Unit No. 1 state
Display State
0 Normal 1 Preparing for heat operation. 2 – 3 – 4 Heater is ON. 5 Anti-freeze protection is ON. 6 Overheat protection is ON. 7 Requesting compressor to turn OFF.
F There are no corresponding units.
[Outdoor unit – Control state] (Request code ":51")
Data display State 0 0 0 0 Normal 0 0 0 1 Preparing for heat operation. 0 0 0 2 Defrost
[Compressor – Frequency control state] (Request code ":52")
Data display
00
Frequency control state
2
Frequency control state
1
Frequency control state
1
Display Current limit control
0 No current limit 1 Primary current limit control is ON. 2 Secondary current limit control is ON.
ON ON
0 1 2 3 4 5 6 7 8 A
ON ON ON ON
ON ON
ON ON
ON
ON
ON
ON
ON
Request:
Request code
Ref.address
Request code
Cursor
−+
OCH607
90
[Fan control state] (Request code :" 53 ")
Data display
Fan step correction value by heatsink temperature overheat prevention control
Fan step correction value by cool condensation temperature overheat prevention control
00
Display Correction value
- (minus) – 1 0 0
2
[Actuator output state] (Request code :"54")
Data display
Actuator output state 1
Actuator output state 2
00
Actuator output state
1
Display SV1 Four-way valve Compressor
0 1
2 3
4 5
6 7
8 9
A
b
C
d
E F
ON
ON
ON
ON
ON
ON
ON
ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON ON ON
ON ON
ON ON
ON ON ON ON
Actuator output state
2
Display 52C SV2 SS
0 1
2 3 4 5 6 7
ON
ON
ON
ON
ON ON
ON ON
ON ON ON ON
[Error content (U9)] (Request code :"55")
Data display
Error content 1
Error content 2
00
Error content
1
: Detected
Display
Overvoltage Undervoltage L
1
-phase
Power synchronizing
error error open error
signal error 0 1 2 3 4 5 6 7 8 9
A
b
C
d
E F
Error content
2
: Detected
Display
Converter Fo
PAM error
error 0 1 2 3
Compressor is
warming up
1
+1
+2
OCH607
91
[Contact demand capacity] (Request code "61")
Data display
000
Setting content
[External input state] (Request code "62")
Data display
000
Input state
Input state : Input present
Display
Contact demand Silent mode Spare 1 Spare 2
input input input input 0 1 2 3 4 5 6 7 8 9
A
b
C
d
E
F
[Outdoor unit – Capacity setting display] (Request code : "70")
Data display
Capacity
10 18
9 12
11 24 14 30 20 36 25 42
[Outdoor unit – Setting information] (Request code "71")
Data display
Setting information 1
Setting information 2
00
Setting information 1
Display Defrost mode
0 Standard 1 For high humidity
Setting information 2
Display
Single-/ Heat pump/
three-phase
cooling only
0
Single-phase
Heat pump
1
Cooling only
2
Three-phase
Heat pump
3
Cooling only
Setting content
Display Setting value
Setting
SW7-1 SW7-2 0 1 50%
ON
ON
2 75% ON
ON
0%
3 100%
OCH607
92
SW1, SW2, SW6, SW7
123456
000000 00 00 100000 00 01 010000 00 02 11 0000 00 03 001000 00 04 101000 00 05 011000 00 06 11 1000 00 07 000100 00 08 100100 00 09 010100 00 0A 11 0100 00 0b 00110 0 00 0C 10110 0 00 0d 01110 0 00 0E 11 1100 00 0F 000010 00 10 100010 010010 11 0010 001010 101010 011010 11 1010 00011 0 10011 0 01011 0 11 0110 00111 0 10111 0 01111 0 11 111 0 000001 100001 010001 11 0001 001001 101001 011001 11 1001 000101 100101 010101 11 0101 00110 1 10110 1 01110 1 11 1101 000011 100011 010011 11 0011 001011 101011 011011 11 1011 00011 1 10011 1 01011 1 11 0111 00111 1 10111 1 01111 1 11 111 1
[Outdoor unit switch setting display (SW1 to SW10, except SW3)] Request codes: 73 to 82
0: Switch OFF 1: Switch ON
Data display
SW5
1234
0000 00 00 1000 00 01 0100 00 02 11 00 00 03 0010 00 04 1010 00 05 0110 00 06 11 10 00 07 0001 00 08 1001 00 09 0101 00 0A 11 01 00 0b 0011 00 0C 1011 00 0d 0111 00 0E 11 11 00 0F
0: Switch OFF 1: Switch ON
Data display
SW8
123
000 00 00 100 00 01 010 00 02 11 0 00 03 001 00 04 101 00 05 011 00 06 11 1 00 07
0: Switch OFF 1: Switch ON
Data display
SW4, SW9, SW10
12
0 0 00 00 1 0 00 01 0 1 00 02 1 1 00 03
0: Switch OFF 1: Switch ON
Data display
00 11 00 12 00 13 00 14 00 15 00 16 00 17 00 18 00 19 00 1A 00 1B 00 1C 00 1D 00 1E 00 1F 00 20 00 21 00 22 00 23 00 24 00 25 00 26 00 27 00 28 00 29 00 2A 00 2B 00 2C 00 2D 00 2E 00 2F 00 30 00 31 00 32 00 33 00 34 00 35 00 36 00 37 00 38 00 39 00 3A 00 3B 00 3C 00 3D 00 3E 00 3F
OCH607
93
[Indoor unit – Model setting information] (Request code : 162 )
Data display
00
See the table on the right.
Display Model setting state Display Model setting state
00 20 01 21 02 22
PLA-A·BA
03 23 04 24 05 25 06 26 07 27 08 28 09 29 0A 2A 0b 2b 0C 2C 0d 2d 0E 2E 0F 2F 10 30 11 31 12 32 13 33 14 34 15 35 16 36 17 37 18 38 19 39 1A 3A 1b 3b 1C 3C 1d 3d 1E 3E 1F 3F
[Indoor unit – Capacity setting information] (Request code 163 )
Data display
00
See the table on the right.
Display Capacity setting state Display Capacity setting state
00 10 42 01 11 02 12 03 13 04 14 05 15 06 12 16 07 17 08 18 09 18 19 0A 1A 0b 24 1b 0C 1C 0d 30 1d 0E 1E 0F 36 1F
Display Pair No. setting state
00 No. 0 01 No. 1 J41 disconnected 02 No. 2 J42 disconnected 03 No. 3 J41, J42 disconnected
[Wireless pair No. (indoor control board side) setting] (Request code 165 )
Data display
00
See the table on the right.
PEA-A·AA PCA-A·KA PKA-A·HA(L)/KA(L)
PEAD-A·AA PEAD-A·AA
PVA-A·AA
PEAD-A·AA PEAD-A·AA
OCH607
94
PUZ-HA30NHA5 PUZ-HA36NHA5
Fan motor fixing screws
Fan motor
Fan motor fixing screws
Propeller
Front panel
Nut
14 DISASSEMBLY PROCEDURE
OPERATING PROCEDURE PHOTOS & ILLUSTRATION
1. Removing the service panel and top panel
(1) Remove the service panel fixing screws (3 for front/ 5 x
12), then slide the service panel downward to remove it. (The service panel is fixed to the side panel (R) with a hook on the right side.)
(2) Remove the top panel fixing screws (3 for front and 3 for
rear/ 5 x 12) to remove the top panel.
Note:
When removing service panel and top panel at the
same time, count one less screw since they share a screw.
2. Removing the fan motor (MF1, MF2)
(1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove the fan grille fixing screws (5 for front/ 5 x 12) to
remove the fan grille. (See Figure 1) (For the each fan motor on top and under)
(4) Remove the screw of nut (1 for front/ M6), then slide the
propeller fan forward to remove it. (For the each fan motor on top and under)
(5) Disconnect the connectors, CNF1 (WT) and CNF2 (WT)
on the controller circuit board in the electrical parts box. (See Photo 3)
(6) Loosen the clamp for the lead wire on motor support,
separator, and electrical parts box.
(7) Remove the fan motor fixing screws (4 for front/ 5 x 20) to
remove the fan motor. (For the each fan motor on top and under)
Top panel fixing screws
Top panel
Service panel fixing screws
Cover panel (front)
Service panel
Fan grille fixing screws
Fan grille
Grille fixing screws
Slide
Photo 1
Photo 2
Figure 1
OCH607
95
OPERATING PROCEDURE PHOTOS
3. Removing the electrical parts box
(1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3)
Disconnect the power supply cable from terminal block.
(4) Disconnect the indoor/outdoor connecting wire from
terminal block.
(5) Disconnect the connector CNF1 (WT), CNF2 (WT), TH3
(WT), TH4 (WT), TH7/ 6 (RD), TH32 (BK), TH33 (YE), 63H (YE), 63L (RD), 21S4 (GN), LEV-A (WT), LEV-B (RD), LEV-C (BU) from the controller circuit board. <Symbols on the board>
• Fan motor (CNF1, CNF2)
• Thermistor <Liquid> (TH3)
• Thermistor <Discharge> (TH4)
• Thermistor <Ambient/2-Phase Pipe> (TH7/6)
• Thermistor <Suction> (TH32)
• Thermistor <Ref. check> (TH33)
• High pressure switch (63H)
• Low pressure switch (63L)
• 4-way valve (21S4)
• LEV (LEV-A, LEV-B, LEV-C)
(6)
Loosen the clamps, fasteners and cable strap for the lead
wire in the electrical parts box and separator. (7) Loosen the lead wires fixed to the pipes with bands. (8) To disconnect the COMP lead wire, remove the terminal
cover. (9) Remove the electrical parts box fixing screw (1 for front/
4 x 10), then slide the electrical parts box upward to
remove it.
(The electrical parts box is fixed to the side panel (R)
with a hook on the right side, and to the separator with a
hook on the left side.)
Photo 3
Electrical parts box
Controller circuit board(C.B.)
Electrical parts box fixing screw
Terminal cover
Compressor (MC)
Terminal block (TB1)
Cover panel (rear)
Side panel (R)
Valve bed
OCH607
96
OPERATING PROCEDURE PHOTOS
4. Removing the thermistor <2-Phase Pipe> (TH6)
(1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Disconnect the connector TH7/6 (RD) on the controller
circuit board in the electrical parts box. (See Photo 3)
(4) Loosen the fastener for the lead wire in the electrical parts
box.
(5) Loosen the clamp for the lead wire on the rear of electrical
parts box.
(6) Pull out the thermistor <2-phase pipe> (TH6) from
thermistor holder.
Note: When replacing thermistor <2-phase pipe> (TH6),
replace it together with thermistor <Ambient> (TH7) since they are combined together. Refer to procedure No.5 to remove the thermistor <Ambient> (TH7).
5. Removing the thermistor <Ambient> (TH7)
(1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Disconnect the connector TH7/6 (RD) on the controller
circuit board in the electrical parts box. (See Photo 3)
(4)
Loosen the fastener for the lead wire in the electrical parts box.
(5) Loosen the clamps for the lead wire on rear of the
electrical parts box.
(6)
Pull out the thermistor <Ambient> (TH7) from sensor holder.
6. Removing the thermistor <Discharge> (TH4)
(1) Remove the service panel. (See Figure 1) (2) Disconnect the connector TH4 (WT) on the controller
circuit board in the electrical parts box. (See Photo 3)
(3) Loosen the fastener, cable strap and band for the lead
wire on the controller circuit board in the electrical parts
box. (4) Loosen clamps for the lead wire on the separator. (5) Pull out the thermistor <Discharge> (TH4) from the
thermistor holder.
7. Removing the thermistor <Liquid> (TH3) and thermistor <Suction> (TH32).
(1) Remove the service panel. (See Figure 1) (2) Disconnect the connector, TH3 (WT), TH32 (BK) on the
controller circuit board in the electrical parts box. (See Photo 3)
(3) Loosen the fastener, cable strap and band for the lead
wire on the controller circuit board in the electrical parts
box. (4)Loosen the clamp for the lead wire on separator. (5) Pull out the thermistor <Liquid> (TH3) from thermistor
holder. (6) Pull out the thermistor <Suction> (TH32) from thermistor
holder.
Note: When replacing thermistor <Ambient> (TH7), replace
it together with thermistor <2-phase pipe> (TH6), since they are combined together. Refer to procedure No.4 to remove the thermistor <2-phase pipe>(TH6).
Photo 7
Photo 8
Photo 6
Clamp
Muffler
Separator
Compressor (MC)
Thermistor <Discharge> (TH4)
Photo 4
Clamp
Heat exchanger
Thermistor <2-phase pipe> (TH6)
Electrical parts box
Sensor holder
Photo 5
Lead wire of thermistor <Ambient> (TH7)
Clamp (for TH3)
Thermistor <Liquid> (TH3)
Power receiver
Thermistor <Suction> (TH32)
Low pressure switch(63L)
OCH607
97
OPERATING PROCEDURE ILLUSTRATION
8. Removing the thermistor <Ref. check> (TH33)
(1) Remove the service panel. (See Figure 1) (2) Disconnect the connector, TH33 (YE), on the controller
circuit board in the electrical parts box. (See Photo 3)
(3) Loosen the fastener and clamp for the lead wire on the
controller circuit board in the electrical parts box.
(4) Pull out the thermistor <Ref. check> (TH33) from
thermistor holder.
9. Removing the 4-way valve coil (21S4), LEV coil (LEV-A, LEV-B, LEV-C) and lead wire for high pressure switch (63H) and low pressure switch (63L).
(1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove the electrical parts box. (See Photo 3) (4) Loosen the clamp for the lead wire on separator.
[Removing the lead wire for pressure switch]
(5) Disconnect the lead wire from the pressure switch.
[Removing the 4-way valve coil]
(5) Remove the 4-way valve coil fixing screw (1 for front/ M4)
to remove the 4-way valve coil.
(6) Slide the 4-way valve coil forward to remove it.
[Removing the LEV coil]
(5) Loosen the lead wires fixed to the pipes with bands. (6) Slide the LEV coil upward to remove it.
10. Removing the 4-way valve, LEV (LEV-A, LEV-B, LEV-C), high pressure switch and low pressure swich.
(1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove the electrical parts box. (See Photo 3) (4) Remove the cover panel (front). (See Figure 1) (5) Remove the cover panel (rear). (See Photo 3) (6) Remove the valve bed. (See Photo 3) (7) Remove the side panel (R). (8) Recover refrigerant.
[Removing the 4-way valve]
(9) Remove the 4-way valve coil. (See Figure 2) (10) Remove the welded part of 4-way valve (4 positions) to
remove the 4-way valve.
[Removing the LEV]
(9) Remove the LEV coil. (See Figure 2) (10) Remove the welded part of LEV (2 positions) to remove
the LEV.
[Removing the pressure switch]
(9) Disconnect the lead wire from the pressure switch. (10) Remove the welded part of pressure switch
(1 position) to remove the pressure switch.
Note 1: Recover refrigerant without spreading it in the
air.
Note 2: The welded part can be removed easily by
removing the side panel (R).
Note 3: When installing the following parts, cover it
with a wet cloth to prevent it from heating as the temperature below, then braze the pipes so that the inside of pipes are not oxidized;
• 4-way valve, 250°F [120°C] or more
• LEV, 250°F [120°C] or more
• Pressure switch, 210°F [100°C] or more
Figure 2
LEV coil (LEV-C)
LEV (Linear expansion valve)
LEV coil (LEV-A)
Thermistor <Ref. check> (TH33)
LEV
LEV coil (LEV-B)
Low pressure switch (63L)
High pressure switch (63H)
4-way valve coil (21S4)
4-way valve
4-way valve coil fixing screw
OCH607
98
OPERATING PROCEDURE PHOTOS
11. Removing the reactor (DCL) and capacitor (CB)
(1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove the electrical parts box. (See Photo 3)
[Removing the reactor]
(4) Remove the reactor fixing screws (4 for rear/4 × 10) and
remove the reactor.
[Removing the capacitor]
(4) Remove the capacitor band fixing screws (2 for rear/
4 × 10) and remove the capacitor.
(The reactor and capacitor are fixed to the electrical parts box on the rear side.)
12. Removing the compressor (MC)
(1) Remove the service panel. (See Figure 1) (2) Remove the top panel. (See Figure 1) (3) Remove the electrical parts box. (See Photo 3) (4) Remove the cover panel (front). (See Figure1) (5) Remove the cover panel (rear). (See Photo 3) (6) Remove the valve bed. (See Photo 10) (7) Remove the side panel (R). (See Photo 3) (8) Remove the front panel fixing screws (4 for front/ 5x12
and 2 for front/ 4x10), then slide the front panel upward to remove it. (The front panel is fixed with 4 hooks; 3 on the left side fixing to the side panel (L), and the other on the right side fixing to the separator.)
(9) Remove the separator fixing screws (3 for front/ 4x10),
then slide the separator upward to remove it.
(
The
separator is fixed to a hook of the side plate.) (10) Recover refrigerant. (11) Remove the welded part of compressor (2 positions). (12) Remove the 3 compressor fixing nuts (M6) to remove the
compressor.
Note 1:
Recover refrigerant without spreading it in the air.
Note 2: The compressor can be easily removed by
removing separator.
Capacitor band fixing screws
Photo 9
Reactor fixing screws
Reactor fixing screws
Reactor (DCL)
Electrical parts box
Capacitor (CB)
Photo 10
Compressor (MC)
Valve bed
Separator
Power receiver
Compressor fixing nuts
OCH607
99
OCH607
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2015 MITSUBISHI ELECTRIC CORPORATION Distributed in Oct. 2015 No. OCH607 Made in Japan
New publication, effective Oct. 2015 Specifications are subject to change without notice.
Loading...