Mitsubishi Electronics PUY-ANHA3-BS, PUY-ANHA3, PUZ-ANHA3-BS, PUZ-ANHA3 User Manual

Air-Conditioners PUZ-A·NHA3, PUZ-A·NHA3-BS PUY-A·NHA3, PUY-A·NHA3-BS
INSTALLATION MANUAL
For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing the air-conditioner unit.
MANUEL D’INSTALLATION
Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil intérieur pour une utilisation sûre et correcte.
MANUAL DE INSTALACIÓN
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado.
FOR INSTALLER
POUR L’INSTALLATEUR
PARA EL INSTALADOR
English
Français
Español
Contents
1. Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. Installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3. Installing the outdoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4. Installing the refrigerant piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5. Drainage piping work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1. Safety precautions
Before installing the unit, make sure you read all the “Safety precau-
tions”.
Please report to or take consent by the supply authority before connec-
tion to the system.
Warning: Describes precautions that must be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that must be observed to prevent damage to the unit.
Warning:
• The unit must not be installed by the user. Ask a dealer or an authorized
technician to install the unit. If the unit is installed incorrectly, water leakage,electric shock, or fi re may result.
• For installation work, follow the instructions in the Installation Manual and
use tools and pipe components specifi cally made for use with R410A re- frigerant. The R410A refrigerant in the HFC system is pressurized 1.6 times the pressure of usual refrigerants. If pipe components not designed for R410A refrigerant are used and the unit is not installed correctly, the pipes may burst and cause damage or injuries. In addition, water leakage, electric shock, or fi re may result.
• The unit must be installed according to the instructions in order to mini-
mize the risk of damage from earthquakes, typhoons, or strong winds. An incorrectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its
weight. If the unit is mounted on an unstable structure, it may fall down and cause damage or injuries.
• If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Consult a dealer regarding the appropriate measures to prevent the allowable concentration from be­ing exceeded. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a fl ame, poisonous gases will be released.
• All electric work must be performed by a qualifi ed technician according to
local regulations and the instructions given in this manual. The units must be powered by dedicated power lines and the correct voltage and circuit breakers must be used. Power lines with insuffi cient capacity or incorrect electrical work may result in electric shock or fi re.
6. Electrical work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7. Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8. Special Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
9. System control (Fig. 9-1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
After installation work has been completed, explain the “Safety Precautions,” use,and maintenance of the unit to the customer according to the information in the Operation Manual and perform the test run to ensure normal operation. Both the Installation Manual and Operation Manual must be given to the user for keeping. These manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affi xed to the main unit.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. If the pipes are not connected cor­rectly, the unit will not be properly grounded and electric shock may result.
• Use only specified cables for wiring. The connections must be made se­curely without tension on the terminals. If the cables are connected or in­stalled incorrectly, overheating or fi re may result.
• The terminal block cover panel of the outdoor unit must be fi rmly attached. If the cover panel is mounted incorrectly and dust and moisture enter the unit, electric shock or fi re may result.
• When installing or moving the air conditioner, use only the specifi ed refrig- erant (R410A) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them. If accessories are incorrectly in­stalled, water leakage, electric shock, or fi re may result.
• Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are not performed correctly, water leakage, electric shock, or fi re may result.
• The user should never attempt to repair the unit or transfer it to another location. If the unit is installed incorrectly, water leakage, electric shock, or fi re may result. If the air conditioner must be repaired or moved, ask a dealer or an authorized technician.
• After installation has been completed, check for refrigerant leaks. If refrig­erant leaks into the room and comes into contact with the fl ame of a heater or portable cooking range, poisonous gases will be released.
1.1. Before installation
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is installed in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, areas exposed to high salt content such as the seaside, or areas where the unit will be covered by snow, the performance can be sig­nifi cantly reduced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, ow, or accumulate. If combustible gas accumulates around the unit, fi re or explosion may result.
• The outdoor unit produces condensation during the heating operation. Make sure to provide drainage around the outdoor unit if such condensa­tion is likely to cause damage.
1.2. Before installation (relocation)
Caution:
• Be extremely careful when transporting the units. 2 or more persons are needed to handle the unit, as it weighs 20 kg, 44 Ibs or more. Do not grasp the packaging bands. Wear protective gloves to remove the unit from the packaging and to move it, as you can injure your hands on the fi ns or the edge of other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials, such as nails and other metal or wooden parts may cause stabs or other injuries.
• When installing the unit in a hospital or communications offi ce, be prepared for noise and electronic interference. Inverters, home appliances, high­frequency medical equipment, and radio communications equipment can cause the air conditioner to malfunction or breakdown. The air conditioner may also affect medical equipment, disturbing medical care, and communi­cations equipment, harming the screen display quality.
• The base and attachments of the outdoor unit must be periodically checked for looseness, cracks or other damage. If such defects are left uncorrected,the unit may fall down and cause damage or injuries.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all fl are nuts to specifi cation using a torque wrench. If tightened too much, the fl are nut can break after an extended period and refrigerant can leak out.
2
1. Safety precautions
1.3. Before electric work
Caution:
• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of suffi cient capacity. Otherwise, a short circuit, overheating, or fi re may result.
• When installing the power lines, do not apply tension to the cables. If the connections are loosened, the cables can snap or break and overheating or re may result.
1.4. Before starting the test run
Caution:
• Turn on the main power switch more than 12 hours before starting opera­tion. Starting operation just after turning on the power switch can severely damage the internal parts. Keep the main power switch turned on during the operation season.
• Before starting operation, check that all panels, guards and other protective parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.
• Do not touch any switch with wet hands. Electric shock may result.
1.5. Using R410A refrigerant air conditioners
Caution:
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust. Use pipes with the specifi ed thick- ness. (Refer to page 5) Note the following if reusing existing pipes that car­ried R22 refrigerant.
- Replace the existing fl are nuts and fl are the fl ared sections again.
- Do not use thin pipes. (Refer to page 5)
• Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing. (Leave elbow joints, etc. in their packaging.) If dust, debris, or moisture enters the refrigerant lines, oil deterioration or compressor breakdown may result.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the fl ared sections. If mineral oil is mixed in the refrigeration oil, oil deterioration may result.
• Be sure to ground the unit. Do not connect the ground wire to gas or water pipes, lighting rods, or telephone grounding lines. If the unit is not properly grounded, electric shock may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specifi ed capacity. If the circuit breaker capacity is larger than the specified capacity, breakdown or fire may result.
• Do not touch the refrigerant pipes with bare hands during operation. The refrigerant pipes are hot or cold depending on the condition of the fl owing refrigerant. If you touch the pipes, burns or frostbite may result.
• After stopping operation, be sure to wait at least fi ve minutes before turn- ing off the main power switch. Otherwise, water leakage or breakdown may result.
• Do not use refrigerant other than R410A refrigerant. If another refrigerant is used, the chlorine will cause the oil to deteriorate.
• Use the following tools specifi cally designed for use with R410A refrigerant. The following tools are necessary to use R410A refrigerant. Contact your nearest dealer for any questions.
Tools (for R410A)
Gauge manifold Flare tool
Charge hose Size adjustment gauge
Gas leak detector Vacuum pump adapter
Torque wrench Electronic refrigerant charging scale
• Be sure to use the correct tools. If dust, debris, or moisture enters the re­frigerant lines, refrigeration oil deterioration may result.
• Do not use a charging cylinder. If a charging cylinder is used, the composi­tion of the refrigerant will change and the effi ciency will be lowered.
2. Installation location
D
B
Fig. 2-1
A12, A18
11-13/16+29/32
23-5/8
5-29/32
19-11/16
31-1/2
2-23/32
(inch) (inch)
13
Fig. 2-2
A
C
A24, A30, A36, A42
13+1-3/16
37-1/8(53-5/32)
6-7/8
23-5/8
E
37-13/32
14-9/16
2.1. Refrigerant pipe (Fig. 2-1)
Check that the difference between the heights of the indoor and outdoor
units, the length of refrigerant pipe, and the number of bends in the pipe are within the limits shown below.
Models
A12, A18 Max. 30 m, 100 ft Max. 30 m,100 ft Max. 15
A24,A30,A36,A42 Max. 50 m, 165 ft Max. 30 m,100 ft Max. 15
• Height difference limitations are binding regardless of which unit, indoor or out­door, is positioned higher.
D Indoor unit E Outdoor unit
APipe length
(one way)
BHeight
difference
C
Number of
bends (one way)
2.2. Choosing the outdoor unit installation location
• Avoid locations exposed to direct sunlight or other sources of heat.
• Select a location from which noise emitted by the unit will not inconvenience neighbors.
• Select a location permitting easy wiring and pipe access to the power source and indoor unit.
• Avoid locations where combustible gases may leak, be produced, fl ow, or accu- mulate.
• Note that water may drain from the unit during operation.
• Select a level location that can bear the weight and vibration of the unit.
• Avoid locations where the unit can be covered by snow. In areas where heavy snow fall is anticipated, special precautions such as raising the installation loca­tion or installing a hood on the air intake must be taken to prevent the snow from blocking the air intake or blowing directly against it. This can reduce the airfl ow and a malfunction may result.
• Avoid locations exposed to oil, steam, or sulfuric gas.
• Use the transportation handles of the outdoor unit to transport the unit. If the unit is carried from the bottom, hands or fi ngers may be pinched.
2.3. Outline dimensions (Outdoor unit) (Fig. 2-2)
The fi gure in parenthesis is for A42 model.
3
2. Installation location
Fig. 2-3
Fig. 2-4
2.4.2. When installing a single outdoor unit (Refer to the last page)
Minimum dimensions are as follows, except for Max., meaning Maximum dimen­sions, indicated. The fi gures in parentheses are for A42 models.
A
Refer to the fi gures for each case.
1 Obstacles at rear only (Fig. 2-6) 2 Obstacles at rear and above only (Fig. 2-7) 3 Obstacles at rear and sides only (Fig. 2-8)
350mm, 13-25/32 inch for A12, A18
*
4 Obstacles at front only (Fig. 2-9)
When using an optional air outlet guide, the clearance for A42 models is 500 mm,
*
19-11/16 inch or more.
5 Obstacles at front and rear only (Fig. 2-10)
When using an optional air outlet guide, the clearance for A42 models is 500 mm,
*
19-11/16 inch or more.
6 Obstacles at rear, sides, and above only (Fig. 2-11)
350mm, 13-25/32 inch for A12, A18
*
• Do not install the optional air outlet guides for upward airfl ow.
B
Fig. 2-5
2.4. Ventilation and service space
2.4.1. Windy location installation
When installing the outdoor unit on a rooftop or other location unprotected from the wind, situate the air outlet of the unit so that it is not directly exposed to strong winds. Strong wind entering the air outlet may impede the normal airfl ow and a malfunction may result. The following shows three examples of precautions against strong winds. 1 Face the air outlet towards the nearest available wall about 50 cm, 19-11/16 inch
away from the wall. (Fig. 2-3)
2
Install an optional air outlet guide and air guide if the unit is installed in a location where strong winds from a typhoon, etc. may directly enter the air outlet. (Fig. 2-4)
AAir outlet guide 3 Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-5)
B Wind direction
3. Installing the outdoor unit
(inch)
(inch)
Max. 23/32 for A12, A18
Max. 1-3/16 for A24-A42
M10(3/8”)bolt
Base
As long as possible.
Vent
Set deep in the ground.
Min. 25-19/32
19-11/16 19-11/16
A24-A42A12, A18
Min. 14-3/16
23-5/8 23-5/8
A24-A42A12, A18
2.4.3. When installing multiple outdoor units (Refer to the last page)
Leave 350 mm, 13-25/32 inch for A18 and 10 mm, 13/32 inch for A24-A42 space or more between the units.
1 Obstacles at rear only (Fig. 2-12) 2 Obstacles at rear and above only (Fig. 2-13)
• No more than three units must be installed side by side. In addition, leave space as shown.
• Do not install the optional air outlet guides for upward airfl ow.
3 Obstacles at front only (Fig. 2-14)
When using an optional air outlet guide, the clearance for A42 models is 1000 mm,
*
39-3/8 inch or more.
4 Obstacles at front and rear only (Fig. 2-15)
When using an optional air outlet guide, the clearance for A42 models is 1000 mm,
*
39-3/8 inch or more.
5 Single parallel unit arrangement (Fig. 2-16)
When using an optional air outlet guide installed for upward airfl ow, the clearance is 500
*
(1000) mm, 19-11/16 (39-3/8) inch or more.
6 Multiple parallel unit arrangement (Fig. 2-17)
When using an optional air outlet guide installed for upward airfl ow, the clearance is 1000
*
(1500) mm, 39-3/8 (59-1/16) inch or more.
7 Stacked unit arrangement (Fig. 2-18)
• The units can be stacked up to 2 units high.
• No more than two stacked units must be installed side by side. In addition, leave space as shown.
• Be sure to install the unit in a sturdy, level surface to prevent rattling noises dur­ing peration. (Fig. 3-1)
<Foundation specifi cations>
Foundation bolt M10 (3/8") Thickness of concrete 120 mm, 4-23/32 inch Length of bolt 70 mm, 2-3/4 inch Weight-bearing capacity 320 kg, 264 lbs
• Make sure that the length of the foundation bolt is within 30 mm, 1-3/16 inch of
the bottom surface of the base. Secure the base of the unit fi rmly with four-M10 foundation bolts in sturdy locations.
Installing the outdoor unit
• Do not block the vent. If the vent is blocked, operation will be hindered and break-
down may result.
• In addition to the unit base, use the installation holes on the back of the unit to at-
tach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 15 mm, ø13/16 × 19/32 inch or less) and install on site.
Warning:
• The unit must be securely installed on a structure that can sustain its
weight. If the unit is mounted on an unstable structure, it may fall down and cause damage or injuries.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor­rectly installed unit may fall down and cause damage or injuries.
Min. 13-25/32
4
5-29/32 5-29/32
31-1/2
13
11-13/16
1-9/32
Fig. 3-1
Min. 13/32
6-7/8 6-7/8
37-13/32
13
14-9/16
1-3/32
4. Installing the refrigerant piping
90˚± 0.5˚
Flare cutting dimensions
Flare nut tightening torque
A (Fig. 4-1)
Copper pipe O.D.
(mm) (inch) (mm) (inch) ø6.35 1/4” 8.7 - 9.1 11/32 - 23/64 ø9.52 3/8” 12.8 - 13.2 1/2 - 33/64 ø12.7 1/2” 16.2 - 16.6 41/64 - 21/32
ø15.88 5/8” 19.3 - 19.7 49/64 - 25/32
B (Fig. 4-1)
Copper pipe O.D. Flare nut O.D. Tightening torque
(mm) (inch) (mm) (inch) (N·m) (ft·lbs) ø6.35 1/4” 17 43/64 14 - 18 10 - 13 ø9.52 3/8” 22 7/8 34 - 42 25 - 30 ø12.7 1/2” 26 1 - 3/64 49 - 61 35 - 44
ø15.88 5/8” 29 1 - 9/64 68 - 82 49 - 59
Front piping cover
Piping cover
Stop valve
Service panel
Bend radius : 100 mm, 3-15/16 inch-150 mm, 5-27/32 inch
A Liquid pipe B Gas pipe C Inslation D Taping
Fig. 4-1
(inch)
45˚± 2˚
A ø
R1/64
to R1/32
Fig. 4-2
Flare dimensions
øA dimensions
A24-A42A12, A18
Fig. 4-3
4.1.
Precautions for devices that use R410A refrigerant
• Refer to page 3 for precautions not included below on using air condition­ers with R410A refrigerant.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the fl ared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thick­nesses specified in the table to the below. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sul­furic compounds, oxidants, debris, or dust.
Warning: When installing or moving the air conditioner, use only the specifi ed refriger- ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig­erant and do not allow air to remain in the lines. Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards.
A12, A18 A24-A42
Liquid pipe
Gas pipe
• Do not use pipes thinner than those specifi ed above.
ø6.35 mm, 1/4inch
thickness 0.8 mm, 1/32 inch
ø12.7 mm, 1/2 inch
thickness 0.8 mm, 1/32 inch
ø9.52 mm, 3/8 inch
thickness 0.8 mm, 1/32 inch
ø15.88 mm, 5/8 inch
thickness 1.0 mm, 3/64 inch
4.2. Connecting pipes (Fig. 4-1) (Fig. 4-2)
When commercially available copper pipes are used, inslate both the liquid and
gas pipes separately with commercially available insulation materials (heat-resis­tant to 100 °C, 212 °F or more, thickness of 12 mm, 1/2 inch or more). (Fig. 4-1)
The indoor parts of the drain pipe should be wrapped with polyethylene foam insu­lation materials (specifi c gravity of 0.03, thickness of 9 mm, 23/64 inch or more).
[Fig. 4-2]
• Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening
are nut. A
• Use 2 wrenches to tighten piping connections. B
• Use leak detector or soapy water to check for gas leaks after connections are
completed.
• Apply refrigerating machine oil over the entire fl are seat surface. C
• Use the fl are nuts for the following pipe size. D
Gas side Pipe size (mm, inch) ø12.7, 1/2” ø15.88, 5/8”
Liquid side Pipe size (mm, inch) ø6.35, 1/4” ø9.52, 3/8”
*1: The fl are nut is attached to its pipe. *2: The fl are nut is in the outdoor unit accessory. Do not use the fl are nut attached. If it is used, a gas leakage or even a pipe ex-
traction may occur.
• When bending the pipes, be careful not to break them. Bend radii of 100 mm,
3-15/16 inch to 150 mm, 5-27/32 inch are suffi cient.
• Make sure the pipes do not contact the compressor. Abnormal noise or vibration
may result.
1 Pipes must be connected starting from the indoor unit.
Flare nuts must be tightened with a torque wrench.
2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil
(Applied on site).
A12, A18 A24 - A42
4.3. Refrigerant piping (Fig. 4-3)
For A12, A18
Remove the service panel D (1 screw).
For A24-A42
Remove the service panel D (3 screws) and the front piping cover A (2 screws) and rear piping cover B (2 screws). 1 Perform refrigerant piping connections for the indoor/outdoor unit when the out-
door unit’s stop valve is completely closed.
2 Vacuum-purge air from the indoor unit and the connection piping. 3 After connecting the refrigerant pipes, check the connected pipes and the indoor
unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)
4 Vacuumize the refrigerant lines through the service port of the liquid stop valve
and then open the stop valves completely (for both the liquid and gas stop valves). This will completely connect the refrigerant lines of the indoor and out-
door units.
• If the stop valves are left closed and the unit is operated, the compressor and
control valves will be damaged.
• Use a leak detector or soapy water to check for gas leaks at the pipe connec-
tion sections of the outdoor unit.
• Do not use the refrigerant from the unit to purge air from the refrigerant lines.
• After the valve work is completed, tighten the valve caps to the correct torque:
20 to 25 N·m, 14 to 18 ft·lbs (200 to 250 kgf·cm).
Failure to replace and tighten the caps may result in refrigerant leakage. In
addition, do not damage the insides of the valve caps as they act as a seal to prevent refrigerant leakage.
5 Use sealant to seal the ends of the thermal insulation around the pipe connec-
tion sections to prevent water from entering the thermal insulation.
5
4. Installing the refrigerant piping
Stop valve <Liquid side>
  Stop valve <Gas side>Service portOpen/Close section
(1)
(2)
1
 
Local pipe
Sealed, same way for gas side
Pipe cover
Do not use a wrench here.
Refrigerant leakage may result. Use 2 wrenches here.
Fig. 4-4
Fig. 4-5
Fig. 4-6
The fi gure to the left is an example only.
*
The stop valve shape, service port po-
sition, etc., may vary according to the model.
Turn section A only.
*
(Do not further tighten sections A and B together.)
C Charge hose D Service port
4.4. Refrigerant pipe airtight testing method
(1) Connect the testing tools.
• Make sure the stop valves
• Add pressure to the refrigerant lines through the service port
D
.
(2) Do not add pressure to the specifi ed pressure all at once; add pressure little by little.
1
Pressurize to 0.5 MPa (5 kgf/cm2G), wait 5 minutes, and make sure the pressure does
not decrease.
2
Pressurize to 1.5 MPa (15 kgf/cm2G), wait 5 minutes, and make sure the pressure
does not decrease.
3
Pressurize to 4.15 MPa (41.5 kgf/cm2G) and measure the surrounding temperature
and refrigerant pressure.
(3) If the specifi ed pressure holds for about one day and does not decrease, the pipes have
passed the test and there are no leaks.
• If the surrounding temperature changes by 1 °C, the pressure will change by about 0.03 MPa (0.3 kgf/cm
(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the source of
the gas leak.
A B
are closed and do not open them.
2
G). Make the necessary corrections.
C
of the liquid stop valve
4.5. Stop valve opening method
(1) Gas side of A24-A42 (Fig. 4-5) 1 Remove the cap, pull the handle toward you and rotate 1/4 turn in a counter-
clockwise direction to open.
2 Make sure that the stop valve is open completely, push in the handle and rotate
the cap back to its original position. (2) Liquid side of A24-A42 and Gas/Liquid side of A12, A18 (Fig. 4-6) 1 Remove the cap and turn the valve rod counterclockwise as far as it will go with
the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper. (ø6.35, 1/4 inch: Approximately 4.5 revolutions) (ø9.52, 3/8 inch: Approximately
10 revolutions) 2 Make sure that the stop valve is open completely, push in the handle and rotate
he cap back to its original position.
A Valve B Unit side C Operation section D Cap E Local pipe side F Pipe cover G Service port H Wrench hole
Refrigerant pipes are protectively wrapped for A24-A42
• The pipes can be protectively wrapped up to a diameter of ø90 mm, 3-35/64
inch before or after connecting the pipes. Cut out the knockout in the pipe cover following the groove and wrap the pipes.
Pipe inlet gap for A24-A42
• Use putty or sealant to seal the pipe inlet around the pipes so that no gaps
remain.(If the gaps are not closed, noise may be emitted or water and dust will enter the unit and breakdown may result.)
Precautions when using the charge valve (Fig.4-7)
Do not tighten the service port too much when installing it, otherwise, the valve core could be deformed and become loose, causing a gas leak. After positioning section B in the desired direction, turn section A only and tighten it. Do not further tighten sections A and B together after tightening section A.
I Double spanner section (Do not apply a spanner other than to this sec-
tion.Doing so would cause refrigerant leaks.) J Seal section (Seal the end of the heat insulation material at
the pipe connection section with whatever seal
material you have on hand so that water does
not infi ltrate the heat insulation material.) K Handle
Fig. 4-7
4.6. Addition of refrigerant
• Additional charging is not necessary if the pipe length does not exceed 20 m, 70 ft for A12-A36, 30 m 100 ft for A42. If the pipe length exceeds the specifi ed length above, charge the unit with addi-
• tional R410A refrigerant according to the permitted pipe lengths in the chart below.
* When the unit is stopped, charge the unit with the additional refrigerant through
the liquid stop valve after the pipe extensions and indoor unit have been vacu­umized. When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant directly to the check valve.
Model
A12, A18 30 m, 100 ft 30 m, 100 ft 0
A24, A30, A36 50 m, 165 ft 30 m, 100 ft 0
A42 50 m, 165 ft 30 m, 100 ft 0 0 0 0
Max pipe
length
Max height
difference
20 m 25 m 27 m 30 m 33.5 m 36.6 m 40 m 43 m 45.5 m 48.8 m 50 m 70 ft 80 ft 90 ft 100 ft 110 ft 120 ft 130 ft 140 ft 150 ft 160 ft 165 ft
0.06 kg 0.11 kg 0.17 kg 2 oz 4 oz 6 oz
0.17 kg 0.34 kg 0.51 kg 0.68 kg 0.85 kg 1.02 kg 1.19 kg 1.36 kg 1.53 kg 1.70 kg 6oz 12oz 18oz 24oz 30oz 36oz 42oz 48oz 54oz 60oz
6
* After charging the unit with refrigerant, note the added refrigerant amount on
the service label (attached to the unit). Refer to the “1.5. Using R410A refrigerant air conditioners” for more information.
• Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have a serious effect on operation per­formance.
Additional refrigerant charging amount (kg/oz)
–––––––
0.17 kg 0.34 kg 0.51 kg 0.68 kg 0.85 kg 1.02 kg 1.19 kg 6oz 12oz 18oz 24oz 30oz 36oz 42oz
4. Installing the refrigerant piping
B
C
A
A24, A36 : A+B+C 50m, 165 ft
|
B–C| 8m, 26 ft
Fig. 4-8
5. Drainage piping work
Outdoor unit drainage pipe connection
When drain piping is necessary, use the drain socket or the drain pan (option).
Drain socket PAC-SG61DS-E Drain pan PAC-SG63DP-E PAC-SG64DP-E
A12, A18 A24-A42
4.7. For twin combination (For A24, A36 only)
Refrigerant piping limitation of length, height difference are shown in the fi gure. (Fig. 4-8) A Indoor unit B Outdoor unit C Multi distribution pipe (option) D Height difference (Indoor unit-Outdoor unit) Max. 30 m, 100 ft E Height difference (Indoor unit-Indoor unit) Max. 1 m, 3 ft
6. Electrical work
6.1. Outdoor unit (Fig. 6-1, Fig. 6-2)
1 Remove the service panel. 2 Wire the cables referring to the Fig. 6-1 and the Fig. 6-2.
S1 S2
S3
Fig. 6-1
    
For Power
For Power
GR
S3
S2S1L1 L2

Indoor unit Outdoor unit Remote controller Main switch (Breaker) Earth
A12, A18
 
A24-A42
Earth terminal
Terminal block
Clamp
Service panel
Wire thecablessothatthey do not
contact the center of the service panel or the gas valve.
L1GRL2 S1 S2 S3
L1GRL2 S1 S2 S3
Fig. 6-2
7
A12, A18
CORD COVER
TERMINAL BED
CABLE STRAP
GRL2L1 S1 S2 S3
CONDUIT COVER
A24-A42
SERVICE PANEL
CONDUIT PLATE : accessory
8
6. Electrical work
6.2. Field electrical wiring
Outdoor unit model A12 A18 A24 A30 A36 A42 Outdoor unit power supply Breaker size *4 15 A 15 A 25 A 30 A 30 A 30 A Minimum circuit ampacity 13 A 13 A 18 A 25 A 25 A 26 A Maximum rating of overcurrent protective device 15 A 20 A 30 A 40 A 40 A 40 A
Outdoor unit power supply 2 × Min. AWG 14 2 × Min. AWG 14 2 × Min. AWG 12 2 × Min. AWG 10 2 × Min. AWG 10 2 × Min. AWG 10 Outdoor unit power supply earth 1 × Min. AWG 14 1 × Min. AWG 14 1 × Min. AWG 12 1 × Min. AWG 10 1 × Min. AWG 10 1 × Min. AWG 10 Indoor unit-Outdoor unit *1 3 × AWG 16 (polar) 3 × AWG 16 (polar) 3 × AWG 16 (polar) 3 × AWG 16 (polar) 3 × AWG 16 (polar) 3 × AWG 16 (polar)
size
Wiring
Indoor unit earth *1 1 × Min. AWG 16 1 × Min. AWG 16 1 × Min. AWG 16 1 × Min. AWG 16 1 × Min. AWG 16 1 × Min. AWG 16
Wire No. ×
Remote controller-Indoor unit *2 Outdoor unit L1-L2 *3 AC 208/230 V AC 208/230 V AC 208/230 V AC 208/230 V AC 208/230 V AC 208/230 V Indoor unit-Outdoor unit S1-S2 *3 AC 208/230 V AC 208/230 V AC 208/230 V AC 208/230 V AC 208/230 V AC 208/230 V Indoor unit-Outdoor unit S2-S3 *3 DC 24 V DC 24 V DC 24 V DC 24 V DC 24 V DC 24 V
rating
Circuit
Remote controller-Indoor unit *3 DC 12 V DC 12 V DC 12 V DC 12 V DC 12 V DC 12 V
*1. Max. 45 m, 147 ft If 2.5 mm If 2.5 mm *2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max 1500 ft *3. The fi gures are NOT always against the ground. S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulataed by the transformer or other device. *4. Use earth leakage breaker (NV)
2
used, Max. 50 m, 164 ft
2
used and S3 separated, Max. 80 m, 262ft
Notes: 1. Wiring size must comply with the applicable local and national code.
2.
Use copper supply wires.
3. Use wires rated 600V or more for the power supply cables and the indoor/outdoor unit connecting cables.
4. Install an earth longer than other cables.
Single, 208/230 V, 60 Hz Single, 208/230 V, 60 Hz Single, 208/230 V, 60 Hz Single, 208/230 V, 60 Hz Single, 208/230 V, 60 Hz Single, 208/230 V, 60 Hz
2 × AWG 22 (Non-polar) 2 × AWG 22 (Non-polar) 2 × AWG 22 (Non-polar) 2 × AWG 22 (Non-polar) 2 × AWG 22 (Non-polar) 2 × AWG 22 (Non-polar)
208/230V
Single phase
A-Control
Outdoor Unit
Isolator
S1
S2
S3
3 poles isolator
S1
S2
S3
A-Control
Indoor Unit
Warning: In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
7. Test run
7.1. Before test run
After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0M. Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning: Do not use the air conditioner if the insulation resistance is less than 1.0M.
Insulation resistance
After installation or after the power source to the unit has been cut for an extended period, the insulation resistance will drop below 1 MΩ due to refrigerant accumulat­ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of
the compressor.
2. If the insulation resistance is below 1 MΩ, the compressor is faulty or the resis-
tance dropped due the accumulation of refrigerant in the compressor.
3. After connecting the wires to the compressor, the compressor will start to warm
up after power is supplied. After supplying power for the times indicated below, measure the insulation resistance again.
• The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 MΩ after the compressor is warmed up for two to three hours. (The time necessary to warm up the compressor varies according to atmo­spheric conditions and refrigerant accumulation.)
• To operate the compressor with refrigerant accumulated in the compressor, the compressor must be warmed up at least 12 hours to prevent breakdown.
4. If the insulation resistance rises above 1 MΩ, the compressor is not faulty.
Caution:
• The compressor will not operate unless the power supply phase connection
is correct.
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result
in severe damage to internal parts. Keep the power switch turned on during the operational season.
The followings must be checked as well.
• The outdoor unit is not faulty. LED1 and LED2 on the control board of the outdoor
unit fl ash when the outdoor unit is faulty.
• Both the gas and liquid stop valves are completely open.
A protective sheet covers the surface of the DIP switch panel on the control board of
the outdoor unit. Remove the protective sheet to operate the DIP switches easily.
• Make sure that the all of the SW5 DIP switches for function changes on the con-
trol board of the outdoor unit are set to OFF. If all of the SW5 switches are not set to OFF, record the settings and then set all of the switches to OFF. Begin recov­ering the refrigerant. After moving the unit to a new location and completing the test run, set the SW5 switches to the previously recorded settings.
9
7. Test run
7.2. Test run
7.2.1. Using SW4 in outdoor unit
1) PUH Type, PUZ Type
SW4-1 ON SW4-2 OFF SW4-1 ON SW4-2 ON
Cooling operation
Heating operation
2) PUY Type
SW4-1 ON SW4-2 ON or OFF
* After performing the test run, set SW4-1 to OFF.
Cooling operation
8. Special Functions
A
A Circuit diagram example (low noise mode) B On-site arrangement C External input adapter (PAC-SC36NA)
B C D
Red
Brown
Orange
SW1
E
3
1
Fig. 8-1
CNDM
D Outdoor unit control board E Max. 10 m, 33 ft
• After power is supplied, a small clicking noise may be heard from the inside of the outdoor unit. The electronic expansion valve is opening and closing. The unit is not faulty.
• A few seconds after the compressor starts, a clanging noise may be heard from the inside of the outdoor unit. The noise is coming from the check valve due to the small difference in pressure in the pipes. The unit is not faulty.
The test run operation mode cannot be changed by DIP switch SW4-2 during the test run. (To change the test run operation mode during the test run, stop the test run by DIP switch SW4-1. After changing the test run operation mode, resume the test run by switch SW4-1.)
7.2.2. Using remote controller
Refer to the indoor unit installation manual.
8.1. Low noise mode (on-site modifi cation) (Fig. 8-1)
By performing the following modifi cation, operation noise of the outdoor unit can be reduced by about 3-4 dB. The low noise mode will be activated when a commercially available timer or the contact input of an ON/OFF switch is added to the CNDM connector (option) on the control board of the outdoor unit.
• The capacity may be insuffi cient according to the outdoor temperature and condi-
tions, etc.
1 Complete the circuit as shown when using the external input adapter (PAC-
SC36NA). (Option) 2 SW1 ON: Low noise mode SW1 OFF: Normal operation
A
B C D
Red
Brown
Orange
SW2
CNDM
3
Fig. 8-2
1
E
C
A
Circuit diagram example (Demand function)
B On-site arrangement
External input adapter (PAC-SC36NA)
D Outdoor unit control board E Max. 10 m, 33 ft
8.3. Refrigerant collecting (pump down)
Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit. 1 Supply power (circuit breaker). * When power is supplied, make sure that “CENTRALLY CONTROLLED” is not
displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis­played, the refrigerant collecting (pump down) cannot be completed normally.
2 After the gas stop valve is closed, set the SWP switch on the control board of the
outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and outdoor units) start operating and refrigerant collecting operation begins. LED1 and LED2 on the control board of the outdoor unit are lit.
* Only set the SWP switch (push-button type) to ON if the unit is stopped. How-
ever, even if the unit is stopped and the SWP switch is set to ON less than three minutes after the compressor stops, the refrigerant collecting operation cannot be performed. Wait until compressor has been stopped for three min­utes and then set the SWP switch to ON again.
8.2. Demand function (on-site modifi cation) (Fig. 8-2)
By performing the following modifi cation, energy consumption can be reduced to 0 –100% of the normal consumption. The demand function will be activated when a commercially available timer or the contact input of an ON/OFF switch is added to the CNDM connector (option) on the control board of the outdoor unit. 1 Complete the circuit as shown when using the external input adapter (PAC-SC36NA). (Option) 2 By setting SW7-1 and SW7-2 on the control board of the outdoor unit, the ener-
gy consumption (compared to the normal consumption) can be limited as shown
below.
SW7-1 SW7-2 Energy consumption (SW2 ON)
OFF OFF 0% (Stop)
ON OFF 50%
OFF ON 75%
3 Because the unit automatically stops in about two to three minutes after the
refrigerant collecting operation (LED1 and LED2 are lit), be sure to quickly close the gas stop valve. When LED1 and LED2 are lit and the outdoor unit is stopped, open the liquid stop valve completely, and then repeat step 2 after three minutes have passed.
* If the refrigerant collecting operation has been completed normally (LED1 and
LED2 are lit), the unit will remain stopped until the power supply is turned off.
4 Turn off the power supply (circuit breaker).
10
9. System control (Fig. 9-1)
E SW 1 - 3 ~ 6
F SW 1 - 3 ~ 6
G SW 1 - 3 ~ 6
TB1 TB4
TB5
ON OFF
3 4 5 6
ON OFF
3 4 5 6
A Outdoor unit B Indoor unit C Master remote controller D Subordinate remote controller E Standard 1:1 (Refrigerant address = 00)
Simultaneous twin (Refrigerant address = 01)
F G
Simultaneous twin (Refrigerant address = 02)
ON OFF
3 4 5 6
A GFAA E
TB1 TB1 TB4
B B B B B
2
TB5
1
C
1
D
TB4 TB4
2
TB4
TB5
Fig. 9-1
* Set the refrigerant address using the DIP switch of the outdoor unit. 1 Wiring from the Remote Control
This wire is connected to TB5 (terminal board for remote controller) of the indoor
unit (non-polar).
2 When a Different Refrigerant System Grouping is Used.
Up to 16 refrigerant systems can be controlled as one group using the slim MA
remote controller.
Note: In single refrigerant system (twin), there is no need of wiring 2.
SW1 Function table
<SW1>
ON OFF
123456
SW1 function settings
Function
1 Compulsory
defrosting
2 Error history
clear
3
Refrigerant
4
system ad-
5
dress setting
6
Operation according to switch setting
ON OFF
Start Normal
Clear Normal
Settings for outdoor unit addresses 0 to 15
11
Loading...
+ 25 hidden pages