Before installing the unit, thoroughly read the following safety precautions.
Observe these safety precautions for your safety.
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or death.
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or damage to the unit.
After reading this manual, give it to the user to retain for future reference.
Keep this manual for easy reference. When the unit is moved or repaired, give this manual to those who provide these
services.
When the user changes, make sure that the new user receives this manual.
Do not use refrigerant other than the type indicated in
the manuals provided with the unit and on the nameplate.
Doing so may cause the unit or pipes to burst, or result in
explosion or fire during use, during repair, or at the time of
disposal of the unit.
It may also be in violation of applicable laws.
MITSUBISHI ELECTRIC CORPORATION cannot be held
responsible for malfunctions or accidents resulting from the
use of the wrong type of refrigerant.
Ask your dealer or a qualified technician to install the
unit.
Improper installation by the user may result in water leakage, electric shock, smoke, and/or fire.
Properly install the unit on a surface that can withstand the weight of the unit.
Unit installed on an unstable surface may fall and cause injury.
Only use specified cables. Securely connect each cable so that the terminals do not carry the weight of the
cable.
Improperly connected or fixed cables may produce heat
and start a fire.
Take appropriate safety measures against strong
winds and earthquakes to prevent the unit from falling.
If the unit is not installed properly, the unit may fall and
cause serious injury to the person or damage to the unit.
Do not make any modifications or alterations to the
unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock,
smoke, and/or fire.
Do not touch the heat exchanger fins.
The fins are sharp and dangerous.
In the event of a refrigerant leak, thoroughly ventilate
the room.
If refrigerant gas leaks and comes in contact with an open
flame, poisonous gases will be produced.
When installing the All-Fresh type units, take it into
consideration that the outside air may be discharged
directly into the room when the thermo is turned off.
Direct exposure to outdoor air may have an adverse effect
on health. It may also result in food spoilage.
Properly install the unit according to the instructions
in the installation manual.
Improper installation may result in water leakage, electric
shock, smoke, and/or fire.
Have all electrical work performed by an authorized
electrician according to the local regulations and instructions in this manual, and a dedicated circuit must
be used.
Insufficient capacity of the power supply circuit or improper
installation may result in malfunctions of the unit, electric
shock, smoke, and/or fire.
HWE1116DGB
ii
WARNING
Securely attach the terminal block cover (panel) to the
unit.
If the terminal block cover (panel) is not installed properly,
dust and/or water may infiltrate and pose a risk of electric
shock, smoke, and/or fire.
After completing the service work, check for a gas
leak.
If leaked refrigerant is exposed to a heat source, such as a
fan heater, stove, or electric grill, poisonous gases may be
produced.
Only use the type of refrigerant that is indicated on the
unit when installing or reinstalling the unit.
Infiltration of any other type of refrigerant or air into the unit
may adversely affect the refrigerant cycle and may cause
the pipes to burst or explode.
When installing the unit in a small room, exercise caution and take measures against leaked refrigerant
reaching the limiting concentration.
Consult your dealer with any questions regarding limiting
concentrations and for precautionary measures before installing the unit. Leaked refrigerant gas exceeding the limiting concentration causes oxygen deficiency.
Consult your dealer or a specialist when moving or reinstalling the unit.
Improper installation may result in water leakage, electric
shock, and/or fire.
To reduce the risk of burns, do not touch electrical
parts during or directly after operation.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature
switch by defeating the safety features of these devices, or
the use of accessories other than the ones that are recommended by MITSUBISHI may result in smoke, fire, and/or
explosion.
Only use accessories recommended by MITSUBISHI.
Ask a qualified technician to install the unit. Improper installation by the user may result in water leakage, electric
shock, smoke, and/or fire.
Control box houses high-voltage parts.
When opening or closing the front panel of the control box,
do not let it come into contact with any of the internal components. Before inspecting the inside of the control box,
turn off the power, keep the unit off for at least 10 minutes,
and confirm that the voltage across the terminals of the inverter circuit main capacitor has dropped to DC20V or less.
(It takes about 10 minutes to discharge electricity after the
power supply is turned off.)
HWE1116DGB
ii
CAUTION
Precautions for handling units for use with R410A
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the re-
sidual refrigerant and refrigerating machine oil in the existing piping may cause the refrigerating machine oil in the
new unit to deteriorate.
R410A is a high-pressure refrigerant and can cause the
existing pipes to burst.
Use refrigerant pipes made of phosphorus deoxidized
copper. Keep the inner and outer surfaces of the pipes
clean and free of such contaminants as sulfur, oxides,
dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes
may cause the refrigerant oil to deteriorate.
Store the pipes to be installed indoors, and keep both
ends of the pipes sealed until immediately before brazing. (Keep elbows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerating machine oil to deteriorate or
cause the unit to malfunction.
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the refrigerating machine oil to deteriorate.
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and
may result in performance loss.
Use a vacuum pump with a reverse-flow check valve.
If a vacuum pump that is not equipped with a reverse-flow
check valve is used, the vacuum pump oil may flow into the
refrigerant cycle and cause the refrigerating machine oil to
deteriorate.
Prepare tools for exclusive use with R410A. Do not use
the following tools if they have been used with the conventional refrigerant (gauge manifold, charging hose,
gas leak detector, reverse-flow check valve, refrigerant
charge base, vacuum gauge, and refrigerant recovery
equipment.).
If the refrigerant or the refrigerating machine oil left on
these tools are mixed in with R410A, it may cause the refrigerating machine oil to deteriorate.
Infiltration of water may cause the refrigerating machine
oil to deteriorate.
Gas leak detectors for conventional refrigerants will not
detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant will change, and the unit may experience power loss.
Exercise special care when handling the tools for use
with R410A.
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerating machine oil to deteriorate.
HWE1116DGB
iiiiii
Before installing the unit
WARNING
Do not install the unit where a gas leak may occur.
If gaseous refrigerant leaks and piles up around the unit, it
may be ignited.
Do not use the unit to keep food items, animals, plants,
artifacts, or for other special purposes.
The unit is not designed to preserve food products.
Do not use the unit in an unusual environment.
Do not install the unit where a large amount of oil or steam
is present or where acidic or alkaline solutions or chemical
sprays are used frequently. Doing so may lead to a remarkable drop in performance, electric shock, malfunctions, smoke, and/or fire.
The presence of organic solvents or corrosive gas (i.e.
ammonia, sulfur compounds, and acid) may cause gas
leakage or water leakage.
When installing the unit in a hospital, take appropriate
measures to reduce noise interference.
High-frequency medical equipment may interfere with the
normal operation of the air conditioner or vice versa.The
product may affect communication equipment. Visual interruption to video images and noise may occur.
Do not install the unit on or over things that cannot get
wet.
When the humidity level exceeds 80% or if the drainage
system is clogged, the indoor unit may drip water. Drain water is also discharged from the outdoor unit. Install a centralized drainage system if necessary.
HWE1116DGB
iv
CAUTION
Before installing the unit (moving and reinstalling the unit) and performing
electrical work
Properly ground the unit.
Do not connect the grounding wire to a gas pipe, water pipe,
lightning rod, or grounding wire from a telephone pole. Improper grounding may result in electric shock, smoke, fire,
and/or malfunction due to noise interference.
Do not put tension on the power supply wires.
If tension is put on the wires, they may break and result in
excessive heat, smoke, and/or fire.
Install an earth leakage breaker for the inverter circuit
to avoid the risk of electric shock.
Failure to install an earth leakage breaker for the inverter
circuit may result in electric shock, smoke, and/or fire.
Use the kind of power supply wires that are specified
in the installation manual.
The use of wrong kind of power supply wires may result in
current leak, electric shock, and/or fire.
Use breakers and fuses (current breaker, remote
switch <switch + Type-B fuse>, moulded case circuit
breaker) with the proper current capacity.
The use of wrong capacity fuses, steel wires, or copper
wires may result in malfunctions, smoke, and/or fire.
Periodically check the installation base for damage.
If the unit is left on a damaged platform, it may fall and
cause injury.
Properly install the drain pipes according to the instructions in the installation manual. Keep them insulated to avoid dew condensation.
Improper plumbing work may result in water leakage and
damage to the furnishings.
Exercise caution when transporting products.
Products weighing more than 20 kg should not be carried
alone.
Do not carry the product by the PP bands that are used on
some products.
Do not touch the heat exchanger fins. They are sharp and
dangerous.
When lifting the unit with a crane, secure all four corners
to prevent the unit from falling.
Properly dispose of the packing materials.
Nails and wood pieces in the package may pose a risk of
injury.
Plastic bags may pose a risk of choking hazard to chil-
dren. Tear plastic bags into pieces before disposing of
them.
Do not spray water on the air conditioner or immerse
the air conditioner in water.
Otherwise, electric shock and/or fire may result.
When handling units, always wear protective gloves to
protect your hands from metal parts and high-temperature parts.
To reduce the risk of burns, do not touch electrical
parts during or directly after operation.
HWE1116DGB
vv
Before the test run
CAUTION
Turn on the unit at least 12 hours before the test run.
Keep the unit turned on throughout the season. If the unit is
turned off in the middle of a season, it may result in malfunctions.
To avoid the risk of electric shock or malfunction of the
unit, do not operate switches with wet hands.
Do not touch the refrigerant pipes with bare hands during and immediately after operation.
During or immediately after operation, certain parts of the
unit such as pipes and compressor may be either very cold
or hot, depending on the state of the refrigerant in the unit
at the time. To reduce the risk of frost bites and burns, do
not touch these parts with bare hands.
Do not operate the unit without panels and safety
guards.
Rotating, high-temperature, or high-voltage parts on the unit
pose a risk of burns and/or electric shock.
Do not turn off the power immediately after stopping
the operation.
Keep the unit on for at least five minutes before turning off
the power to prevent water leakage or malfunction.
Do not operate the unit without the air filter.
Dust particles may build up in the system and cause malfunctions.
HWE1116DGB
vi
CONTENTS
I
II
III
IV
V
VI
VII
VIII
IX
Read Before Servicing
[1] Read Before Servicing.............................................................................................................. 3
[2] Necessary Tools and Materials ................................................................................................ 4
[10] Remedies to be taken in case of a Refrigerant Leak ....................................................... 12
[11] Characteristics of the Conventional and the New Refrigerants .......................................13
[12] Notes on Refrigerating Machine Oil ................................................................................. 14
HWE1116DGB
- 1 -
HWE1116DGB
- 2 -
[ I Read Before Servicing ]
CAUTION
I Read Before Servicing
[1] Read Before Servicing
1. Check the type of refrigerant used in the system to be serviced.
Refrigerant Type
Multi air conditioner for building application CITY MULTI R2 TKMU-A, YKMU-A series R410A
2. Check the symptoms exhibited by the unit to be serviced.
Refer to this service handbook for symptoms relating to the refrigerant cycle.
3. Thoroughly read the safety precautions at the beginning of this manual.
4. Preparing necessary tools: Prepare a set of tools to be used exclusively with each type of refrigerant.
Refer to "Necessary Tools and Materials" for information on the use of tools.(page 4)
5. Verification of the connecting pipes: Verify the type of refrigerant used for the unit to be moved or replaced.
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free
of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
6. If there is a leak of gaseous refrigerant and the remaining refrigerant is exposed to an open flame, a poisonous gas
hydrofluoric acid may form. Keep workplace well ventilated.
Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.
The use of refrigerant that contains chloride, such as R22, will cause the refrigerating machine oil to deteriorate.
HWE1116DGB
- 3 -
[ I Read Before Servicing ]
[2] Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C)
1. To be used exclusively with R410A (not to be used if used with R22 or R407C)
Tools/MaterialsUseNotes
Gauge ManifoldEvacuation and refrigerant chargingHigher than 5.09MPa[738psi] on the
Charging HoseEvacuation and refrigerant chargingThe hose diameter is larger than the
Refrigerant Recovery CylinderRefrigerant recovery
Refrigerant CylinderRefrigerant chargingThe refrigerant type is indicated. The
Charging Port on the Refrigerant Cylinder Refrigerant chargingThe charge port diameter is larger
Flare NutConnection of the unit with the pipesUse Type-2 Flare nuts.
2. Tools and materials that may be used with R410A with some restrictions
Tools/MaterialsUseNotes
Gas Leak DetectorGas leak detectionThe ones for use with HFC refrigerant
Vacuum PumpVacuum dryingMay be used if a check valve adapter
Flare ToolFlare processingFlare processing dimensions for the
Refrigerant Recovery EquipmentRefrigerant recoveryMay be used if compatible with
high-pressure side
conventional model.
cylinder is pink.
than that of the current port.
may be used.
is attached.
piping in the system using the new refrigerant differ from those of R22. Refer to I [3] Piping Materials.
R410A.
3. Tools and materials that are used with R22 or R407C that may also be used with R410A
Tools/MaterialsUseNotes
Vacuum Pump with a Check ValveVacuum drying
BenderBending pipes
Torque WrenchTightening flare nutsOnly the flare processing dimensions
for pipes that have a diameter of
ø12.70 (1/2") and ø15.88 (5/8") have
been changed.
Pipe CutterCutting pipes
Welder and Nitrogen CylinderWelding pipes
Refrigerant Charging MeterRefrigerant charging
Vacuum GaugeVacuum level check
4. Tools and materials that must not be used with R410A
Tools/MaterialsUseNotes
Charging CylinderRefrigerant chargingProhibited to use
Tools for R410A must be handled with special care to keep moisture and dust from infiltrating the cycle.
HWE1116DGB
- 4 -
[ I Read Before Servicing ]
[3] Piping Materials
Do not use the existing piping!
1. Copper pipe materials
O-material (Annealed)Soft copper pipes (annealed copper pipes). They can easily be bent with hands.
1/2H-material (Drawn)Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed)
The distinction between O-materials (Annealed) and 1/2H-materials (Drawn) is made based on the strength of the pipes them-
selves.
O-materials (Annealed) can easily be bent with hands.
1/2H-materials (Drawn) are considerably stronger than O-material (Annealed) at the same thickness.
2. Types of copper pipes
Maximum working pressureRefrigerant type
3.45 MPa [500psi]R22, R407C etc.
4.30 MPa [624psi]R410A etc.
3. Piping materials/Radial thickness
Use refrigerant pipes made of phosphorus deoxidized copper.
The operation pressure of the units that use R410A is higher than that of the units that use R22.
Use pipes that have at least the radial thickness specified in the chart below.
(Pipes with a radial thickness of 0.7 mm or less may not be used.)
at the same radial thickness.
Pipe size (mm[in])Radial thickness (mm)Type
ø6.35[1/4"]0.8t
ø9.52[3/8"]0.8t
ø12.7[1/2"]0.8t
ø15.88[5/8"]1.0t
ø19.05[3/4"]1.0t
ø22.2[7/8"]1.0t
ø25.4[1"]1.0t
ø28.58[1-1/8"]1.0t
ø31.75[1-1/4"]1.1t
ø34.93[1-3/8"]1.1t
ø41.28[1-5/8"]1.2t
The pipes in the system that uses the refrigerant currently on the market are made with O-material (Annealed), even if the
pipe diameter is less than ø19.05 (3/4"). For a system that uses R410A, use pipes that are made with 1/2H-material (Drawn)
unless the pipe diameter is at least ø19.05 (3/4") and the radial thickness is at least 1.2t.
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
O-material (Annealed)
1/2H-material,
H-material (Drawn)
HWE1116DGB
- 5 -
[ I Read Before Servicing ]
4. Thickness and refrigerant type indicated on the piping materials
Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5. Flare processing (O-material (Annealed) and OL-material only)
The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.
Flare processing dimensions (mm[in])
A dimension (mm)
Pipe size (mm[in])
R410AR22, R407C
ø6.35[1/4"]9.19.0
ø9.52[3/8"]13.213.0
ø12.7[1/2"]16.616.2
Dimension A
ø15.88[5/8"]19.719.4
ø19.05[3/4"]24.023.3
If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0
and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
6. Flare nut
The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.
Flare nut dimensions (mm[in])
B dimension (mm)
Pipe size (mm[in])
R410AR22, R407C
ø6.35[1/4"]17.017.0
ø9.52[3/8"]22.022.0
ø12.7[1/2"]26.024.0
Dimension B
ø15.88[5/8"]29.027.0
ø19.05[3/4"]36.036.0
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
HWE1116DGB
- 6 -
[ I Read Before Servicing ]
[4] Storage of Piping
1. Storage location
Store the pipes to be used indoors. (Warehouse at site or owner's warehouse)
If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe.
2. Sealing the pipe ends
Both ends of the pipes should be sealed until just before brazing.
Keep elbow pipes and T-joints in plastic bags.
The new refrigerator oil is 10 times as hygroscopic as the conventional refrigerating machine oil (such as Suniso) and, if not
handled with care, could easily introduce moisture into the system. Keep moisture out of the pipes, for it will cause the oil to
deteriorate and cause a compressor failure.
[5] Pipe Processing
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Use a minimum amount of oil.
Use only ester oil, ether oil, and alkylbenzene.
HWE1116DGB
- 7 -
[ I Read Before Servicing ]
[6] Brazing
No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide
scale, water, and dust) out of the refrigerant system.
Example: Inside the brazed connection
Use of no inert gas during brazingUse of inert gas during brazing
1. Items to be strictly observed
Do not conduct refrigerant piping work outdoors if raining.
Use inert gas during brazing.
Use a brazing material (BCuP-3) that requires no flux when brazing between copper pipes or between a copper pipe and
copper coupling.
If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.
2. Reasons
The new refrigerating machine oil is 10 times as hygroscopic as the conventional oil and is more likely to cause unit failure if
water infiltrates into the system.
Flux generally contains chloride. Residual flux in the refrigerant circuit will cause sludge to form.
3. Notes
Do not use commercially available antioxidants because they may cause the pipes to corrode or refrigerating machine oil to
deteriorate.
HWE1116DGB
- 8 -
[ I Read Before Servicing ]
[7] Air Tightness Test
No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak.
Halide torch R22 leakage detector
1. Items to be strictly observed
Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight-
ness, taking temperature variations into account.
Refrigerant R410A must be charged in its liquid state (vs. gaseous state).
2. Reasons
Oxygen, if used for an air tightness test, poses a risk of explosion. (Only use nitrogen to check air tightness.)
Refrigerant R410A must be charged in its liquid state. If gaseous refrigerant in the cylinder is drawn out first, the composition
of the remaining refrigerant in the cylinder will change and become unsuitable for use.
3. Notes
Procure a leak detector that is specifically designed to detect an HFC leak. A leak detector for R22 will not detect an
HFC(R410A) leak.
1. Vacuum pump with a reverse-flow check valve (Photo1)
To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum
pump with a reverse-flow check valve.
A reverse-flow check valve may also be added to the vacuum pump currently in use.
2. Standard of vacuum degree (Photo 2)
Use a vacuum pump that attains 0.5Torr(65Pa) or lower degree of vacuum after 5 minutes of operation, and connect it directly
to the vacuum gauge. Use a pump well-maintained with an appropriate lubricant. A poorly maintained vacuum pump may not
be able to attain the desired degree of vacuum.
3. Required precision of vacuum gauge
Use a vacuum gauge that registers a vacuum degree of 5Torr(650Pa) and measures at intervals of 1Torr(130Pa). (A recommended vacuum gauge is shown in Photo2.)
Do not use a commonly used gauge manifold because it cannot register a vacuum degree of 5Torr(650Pa).
4. Evacuation time
After the degree of vacuum has reached 5Torr(650Pa), evacuate for an additional 1 hour. (A thorough vacuum drying re-
moves moisture in the pipes.)
Verify that the vacuum degree has not risen by more than 1Torr(130Pa) 1hour after evacuation. A rise by less than
1Torr(130Pa) is acceptable.
If the vacuum is lost by more than 1Torr(130Pa), conduct evacuation, following the instructions in section 6. Special vacuum
drying.
5. Procedures for stopping vacuum pump
To prevent the reverse flow of vacuum pump oil, open the relief valve on the vacuum pump side, or draw in air by loosening
the charge hose, and then stop the operation.
The same procedures should be followed when stopping a vacuum pump with a reverse-flow check valve.
6. Special vacuum drying
When 5Torr(650Pa) or lower degree of vacuum cannot be attained after 3 hours of evacuation, it is likely that water has pen-
etrated the system or that there is a leak.
If water infiltrates the system, break the vacuum with nitrogen. Pressurize the system with nitrogen gas to
0.5kgf/cm
2
G(0.05MPa) and evacuate again. Repeat this cycle of pressurizing and evacuation either until the degree of vac-
uum below 5Torr(650Pa) is attained or until the pressure stops rising.
Only use nitrogen gas for vacuum breaking. (The use of oxygen may result in an explosion.)
HWE1116DGB
- 10 -
[ I Read Before Servicing ]
7. Triple Evacuation
The method below can also be used to evacuate the system.
Evacuate the system to 4,000 microns from both service valves. System manifold gauges must not be used to measure vac-
uum. A micron gauge must be used at all times. Break the vacuum with Nitrogen (N2) into the discharge service valve to 0
PSIG.
Evacuate the system to 1,500 microns from the suction service valve. Break the vacuum with Nitrogen (N2) into the discharge
service valve to 0 PSIG.
Evacuate the system to 500 microns. System must hold the vacuum at 500 microns for a minimum of 1 hour.
Conduct a rise test for a minimum of 30 minutes
8. Notes
To evacuate air from the entire system
Applying a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1
and 2) is not enough to attain the desired vacuum pressure.
Be sure to apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure
sides (BV1 and 2) and also through the check joints on the high and low pressure sides (CJ1 and 2).
To evacuate air only from the outdoor units
Apply a vacuum through the check joints on the high and low pressure sides (CJ1, and 2).
To evacuate air from the indoor units and extension pipes
Apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1
and 2).
HWE1116DGB
- 11 -
[ I Read Before Servicing ]
[9] Refrigerant Charging
Cylinder with a siphon
Cylinder without a siphon
Cylin-
Cylin-
der
der
Cylinder color R410A is pink.Refrigerant charging in the liquid state
ValveValve
liquid
liquid
1. Reasons
R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled
the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid
phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and become unsuitable for use.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check
the type of the cylinder on the label before use.
[10] Remedies to be taken in case of a Refrigerant Leak
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in the
liquid state.)
Refer to "IX [5] Refrigerant Leak."(page 338)
HWE1116DGB
- 12 -
[ I Read Before Servicing ]
[11] Characteristics of the Conventional and the New Refrigerants
1. Chemical property
As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant.
However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will
accumulate at the bottom of the room and may cause hypoxia.
If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a confined area.
New Refrigerant (HFC type)Conventional Refriger-
ant (HCFC type)
R410AR407CR22
R32/R125R32/R125/R134aR22
Composition (wt%)(50/50)(23/25/52)(100)
Type of RefrigerantPseudo-azeotropic
Refrigerant
Non-azeotropic
Refrigerant
Single Refrigerant
ChlorideNot includedNot includedIncluded
Safety ClassA1/A1A1/A1A1
Molecular Weight72.686.286.5
Boiling Point (°C/°F)-51.4/-60.5-43.6/-46.4-40.8/-41.4
Steam Pressure
1.557/2260.9177/1330.94/136
(25°C,MPa/77°F,psi) (gauge)
Saturated Steam Density
(25°C,kg/m
3
/77°F,psi)
64.042.544.4
FlammabilityNonflammableNonflammableNonflammable
Ozone Depletion Coefficient (ODP)
Global Warming Coefficient (GWP)
Refrigerant Charging MethodRefrigerant charging in
Replenishment of Refrigerant after a Refrigerant
*1
*2
000.055
173015301700
the liquid state
Refrigerant charging in
the liquid state
Refrigerant charging in
the gaseous state
AvailableAvailableAvailable
Leak
*1 When CFC11 is used as a reference
*2 When CO
is used as a reference
2
2. Refrigerant composition
R410A is a pseudo-azeotropic HFC blend and can almost be handled the same way as a single refrigerant, such as R22. To
be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn
out, the composition of the remaining refrigerant will change and become unsuitable for use.
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced.
3. Pressure characteristics
The pressure in the system using R410A is 1.6 times as great as that in the system using R22.
Pressure (gauge)
Temperature (°C/°F)
R410AR407CR22
MPa/psiMPa/psiMPa/psi
-20/-40.30/440.18/260.14/20
0/320.70/1020.47/680.40/58
20/681.34/1940.94/1360.81/117
40/1042.31/3351.44/2091.44/209
60/1403.73/5412.44/3542.33/338
65/1494.17/6052.75/3992.60/377
HWE1116DGB
- 13 -
[ I Read Before Servicing ]
[12] Notes on Refrigerating Machine Oil
1. Refrigerating machine oil in the HFC refrigerant system
HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system.
Note that the ester oil used in the system has properties that are different from commercially available ester oil.
RefrigerantRefrigerating machine oil
R22 Mineral oil
R407CEster oil
R410A Ester oil
2. Effects of contaminants
*1
Refrigerating machine oil used in the HFC system must be handled with special care to keep contaminants out.
The table below shows the effect of contaminants in the refrigerating machine oil on the refrigeration cycle.
3. The effects of contaminants in the refrigerating machine oil on the refrigeration cycle.
CauseSymptomsEffects on the refrigerant cycle
Water infiltrationFrozen expansion valve
and capillary tubes
Clogged expansion valve and capillary tubes
Poor cooling performance
Compressor overheat
Motor insulation failure
Burnt motor
Coppering of the orbiting scroll
Lock
Burn-in on the orbiting scroll
Clogged expansion valve, capillary tubes, and
drier
Hydrolysis
Air infiltrationOxidization
Adhesion to expansion valve and capillary
tubes
Sludge formation and adhesion
Acid generation
Oxidization
Oil degradation
Poor cooling performance
Infiltration of
contaminants
Dust, dirt
Infiltration of contaminants into the compressor
Compressor overheat
Burn-in on the orbiting scroll
Sludge formation and adhesionClogged expansion valve and capillary tubes
Mineral oil
etc.
Poor cooling performance
Compressor overheat
Oil degradationBurn-in on the orbiting scroll
*1. Contaminants is defined as moisture, air, processing oil, dust/dirt, wrong types of refrigerant, and refrigerating machine oil.
HWE1116DGB
- 14 -
II
Restrictions
[1] System configuration ....................................................................................................... 17
[2] Types and Maximum allowable Length of Cables ...........................................................18
[3] Switch Settings and Address Settings ............................................................................. 19
[4] Sample System Connection............................................................................................. 26
[5] An Example of a System to which an MA Remote Controller is connected..................... 28
[6] An Example of a System to which an ME Remote Controller is connected..................... 42
[7] An Example of a System to which both MA Remote Controller and ME Remote
Controller are connected.................................................................................................. 44
[8] Restrictions on Pipe Length ............................................................................................. 47
HWE1116DGB
- 15 -
HWE1116DGB
- 16 -
[ II Restrictions ]
II Restrictions
[1] System configuration
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
Outdoor
units
Composing unitsMaximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable in-
door units
72 - - 36 - 10818P06 - P96 models
96 - - 48 - 14424
R410A series indoor units
120 - - 60 - 18030
144 - - 72 - 21636
144727272 - 21636
168967284 - 25242
192969696 - 28848
21612096108 - 32450
240120120120 - 36050
264144120132 - 39650
288144144144 - 43250
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
3) There is no P144 that consists of two P72 units in the TKMU series.
HWE1116DGB
- 17 -
[ II Restrictions ]
[2] Types and Maximum allowable Length of Cables
1. Wiring work
(1) Notes
1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this manual.
2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference.
(Do not put the control cable and power supply cable in the same conduit tube.)
3) Provide grounding for the outdoor unit as required.
4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing.
5) Do not connect power supply wiring to the terminal block for transmission line. Doing so will damage the electronic components on the terminal block.
6) Use 2-core shielded cables as transmission cables.
Use a separate 2-core control cable for each refrigerant system. Do not use a single multiple-core cable to connect indoor
units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and
malfunctions.
Outdoor unit
TB3TB7TB3TB
2-core shielded cable
TB3TB7TB3TB
2-core shielded cable
7
7
BC Controller
Indoor unit
Remote Controller
Outdoor unit
TB3TB7TB3TB
TB3TB7TB3TB
BC Controller
7
multiple-core cable
7
Indoor unit
Remote Controller
TB3: Terminal block for indoor-outdoor transmission line TB7: Terminal block for centralized control
7) When extending the transmission cable, be sure to extend the shield wire.
(2) Control wiring
Different types of control wiring are used for different systems.
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System
to which both MA Remote Controller and ME Remote Controller are connected" before performing wiring work.
Types and maximum allowable length of cables
Control lines are categorized into 2 types: transmission line and remote controller line.
Use the appropriate type of cables and observe the maximum allowable length specified for a given system. If a given system
has a long transmission line or if a noise source is located near the unit, place the unit away from the noise source to reduce
noise interference.
1) M-NET transmission line
Facility
type
TypeShielded cable CVVS, CPEVS, MVVS
Cable type
Number of
cores
Cable sizeLarger than 1.25mm
Maximum transmission
line distance between the
outdoor unit and the farthest indoor unit
Maximum transmission
line distance for centralized control and Indoor/
outdoor transmission line
(Maximum line distance
500 m [1640ft] max.
*The maximum overall line length from the power supply unit on the transmission lines for
centralized control to each outdoor unit or to the system controller is 200m [656ft] max.
via outdoor unit)
HWE1116DGB
- 18 -
All facility types
2-core cable
2
[AWG16]
200 m [656ft] max.
[ II Restrictions ]
2) Remote controller wiring
MA remote controller
*1
ME remote controller
*5
TypeCVVCVV
Number of
cores
Cable type
Cable size
Maximum overall line
length
2-core cable2-core cable
0.3 to 1.25mm
[AWG22 to 16]
(0.75 to 1.25mm2 )
[AWG18 to 16]
2 *2 *4
*3
0.3 to 1.25mm
[AWG22 to 16]
(0.75 to 1.25mm2 )
[AWG18 to 16]
The section of the cable that exceeds 10m
200 m [656ft] max.
[32ft] must be included in the maximum indoor-outdoor transmission line distance.
2 *2
*3
*1 MA remote controller refers to MA remote controller (PAR-20MAU, PAR-21MAAU, PAR-30MAAU), Simple MA Re-
mote Controller, and wireless remote controller.
*2 The use of cables that are smaller than 0.75mm
2
(AWG18) is recommended for easy handling.
*3 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi-
cations shown in the parenthesis.
*4 When connecting PAR-30MAAU, use a 0.3mm
2
sheathed cable.
*5 ME remote controller refers to ME remote controller and Simple ME Remote Controller.
[3] Switch Settings and Address Settings
1. Switch setting
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System
to which both MA Remote Controller and ME Remote Controller are connected" before performing wiring work.
Set the switches while the power is turned off.
If the switch settings are changed while the unit is being powered, those changes will not take effect, and the unit will not
function properly.
Units on which to set the switchesSymbolUnits to which the power must be shut off
CITY MULTI indoor unitMain/sub unitICOutdoor units
LOSSNAY, OA processing unit
*1
ME remote controllerMain/sub remote
LCOutdoor units
RCOutdoor units
*3
and Indoor units
*3
and LOSSNAY
*3
controller
MA remote controller
*4
Main/sub remote
MAIndoor units
controller
CITY MULTI outdoor unit
*2
OC,OSOutdoor units
BC controllerMainBCOutdoor units
Sub1, 2BS1, BS2Outdoor units
*3
*3
and BC controller
*3 *5
and BC controller
*1. Applicable when LOSSNAY units are connected to the indoor-outdoor transmission line.
*2. The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity
from large to small (if two or more units have the same capacity, in the order of address from small to large).
*3. Turn off the power to all the outdoor units in the same refrigerant circuit.
*4. When a PAR-30MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
*5. When setting the switch SW4 of the control board, set it with the outdoor unit power on. (Refer to VII [1] -1- (1).)
The need for address settings and the range of address setting depend on the configuration of the system.
Unit or controllerSym-
bol
Address
setting
Setting methodFactory
range
CITY MULTI
indoor unit
M-NET
adapter
M-NET control interface
Free Plan
adapter
LOSSNAY, OA processing unitLC0, 01 to
ME remote
controller
MA remote controllerMANo address settings required. (The main/sub setting must be made if
CITY MULTI outdoor unitOCOS0, 51 to
Auxiliary
outdoor unit
Main/sub unitIC0, 01 to
Main remote
RC101 to
controller
Sub remote
RC151 to
controller
50
50
150
200
*1 *4 *6
*1 *4 *6
*3
2 remote controllers are connected to the system.)
*1 *2
100
*6
BC controller
(main)
BC0, 51 to
100
*6
*1 *2
Assign the smallest address to the main indoor unit in the
group, and assign sequential address numbers to the rest
of the indoor units in the same group.
In an R2 system with a sub BC controller, make the settings for the indoor units in the following order.
(i) Indoor unit to be connected to the main BC controller
(ii) Indoor unit to be connected to sub BC controller 1
(iii) Indoor unit to be connected to sub BC controller 2
Make the settings for the indoor units in the way that the
formula "(i) < (ii) < (iii)" is true.
Assign an arbitrary but unique address to each of these
units after assigning an address to all indoor units.
Add 100 to the smallest address of all the indoor units in
the same group.
Add 150 to the smallest address of all the indoor units in
the same group.
*7
Assign an address that equals the lowest address of the indoor
units in the same refrigerant circuit plus 50.
Assign sequential addresses to the outdoor units in the same re-
frigerant circuit. The outdoor units in the same refrigerant circuit
are automatically designated as OC and OS.
*5
Assign an address that equals the address of the outdoor
unit in the same refrigerant system plus 1.
If a given address overlaps any of the addresses that are
assigned to the outdoor units or to the sub BC controller,
use a different, unused address within the setting range.
BC controller
(sub1, 2)
BS1
BS2
51 to
100
Assign an address to both the sub BC controller 1 and 2
*2
that equals the lowest address of the indoor units that
are connected to each of them plus 50.
If a sub BC controller is connected, the automatic startup
function is not available.
address
setting
00
00
101
Main
00
00
*1. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the
setting range.
*2. To set the outdoor unit address or the auxiliary outdoor unit address to "100," set the rotary switches to "50."
*3. To set the ME remote controller address to "200," set the rotary switches to "00."
*4. Some models of indoor units have two or three control boards.
Assign an address to the No.1, No. 2, and No. 3 control boards so that the No. 2 control board address equals the No. 1 control board
address plus 1, and that the No. 3 control board address equals the No. 1 control board address plus 2.
*5. The outdoor units in the same refrigerant circuit are automatically designated as OC, and OS. They are designated as OC, and OS in
the descending order of capacity (ascending order of address if the capacities are the same).
*6. No address settings are required for units in a system with a single outdoor unit (with some exceptions).
Address setting is required if a sub BC controller is connected.
*7. When a PAR-30MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
HWE1116DGB
- 20 -
[ II Restrictions ]
System
controller
Unit or controllerSym-
bol
Group remote con-
GRSC201 to
troller
System remote controller
ON/OFF remote controller
SR
SC
AN
SC
Schedule timer (compatible with M-NET)STSC
Central controller
TRSC000
AG-150A
G(B)-50A
GB-24A
Expansion controller
TR000
PAC-YG50ECA
BM adapter
SC000
BAC-HD150
LM adapter
SC201 to
LMAP03U
Address
setting
range
250
201 to
250
201 to
250
201 to
250
250
Setting methodFactory
Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the range
listed on the left to each unit.
Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the range
listed on the left to each unit.
Assign an arbitrary but unique address within the range
listed on the left to each unit. The address must be set to
"000" to control the K-control unit.
Assign an arbitrary but unique address within the range
listed on the left to each unit. The address must be set to
"000" to control the K-control unit.
Assign an arbitrary but unique address within the range
listed on the left to each unit. The address must be set to
"000" to control the K-control unit.
Assign an arbitrary but unique address within the range
listed on the left to each unit.
address
setting
201
202
000
000
000
247
HWE1116DGB
- 21 -
[ II Restrictions ]
(2) Power supply switch connector connection on the outdoor unit
(Factory setting: The male power supply switch connector is connected to CN41.)
There are limitations on the total number of units that are connectable to each refrigerant system. Refer to the System Design
Manual for details.
System configuration
Connection to
the system controller
Power supply unit
for transmission
lines
Group operation
of units in a system with multiple
Power supply switch connector connection
outdoor units
System with one
outdoor unit
System with multiple outdoor units
___Leave CN41 as it is
(Factory setting)
Not connected_Not grouped
GroupedDisconnect the male connector from the fe-
With connection
to the indoor
unit system
With connection
to the centralized control system
Not requiredGrouped/not
grouped
Not required
(Powered from
*1
Grouped/not
grouped
the outdoor unit)
Required *1Grouped/not
grouped
male power supply switch connector (CN41)
and connect it to the female power supply
switch connector (CN40) on only one of the
outdoor units.
*Connect the S (shielded) terminal on the
terminal block (TB7) on the outdoor unit
whose CN41 was replaced with CN40 to
the ground terminal ( ) on the electric box.
Leave CN41 as it is
(Factory setting)
*2
*1 The need for a power supply unit for transmission lines depends on the system configuration.
*2 The replacement of the power jumper connector from CN41 to CN40 must be performed on only one outdoor unit in the
system.
(3) Settings for the centralized control switch for the outdoor unit (Factory setting: SW5-1 is set to OFF.)
System configurationCentralized control switch settings
*1
Connection to the system controller Not connectedLeave it to OFF. (Factory setting)
Connection to the system controller Connected
*2
ON
*1. Set SW5-1 on all outdoor units in the same refrigerant circuit to the same setting.
*2. When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
(4) Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to "OFF".)
To stop the fan during heating Thermo-OFF (SW1-7 and 1-8 on the indoor units to be set to ON), use the built-in thermistor
on the remote controller or an optional thermistor.
1) To use the built-in sensor on the remote controller, set the SW1-1 to ON.
Some models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
(Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models is ON.
2) When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON.
When using an optional temperature sensor, install it where room temperature can be detected.
(5) Various start-stop controls (Indoor unit settings)
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
Function
Power ON/OFF by the
*1,*2,*3
plug
Automatic restoration
after power failure
Operation of the indoor unit when the operation is resumed after the unit
was stopped
Indoor unit will go into operation regardless of its operation status before
power off (power failure). (In approx. 5 minutes)
Indoor unit will go into operation if it was in operation when the power was
turned off (or cut off due to power failure). (In approx. 5 minutes)
Indoor unit will remain stopped regardless of its operation status before
Setting (SW1)
910
OFFON
ONOFF
OFFOFF
power off (power failure).
*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the
belt heater and may cause the compressor to malfunction when the unit is put back into operation.
*2. Not applicable to units with a built-in drain pump or humidifier.
*3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir-
cuits will be turned on or off by the plug.
*4. Requires that the dipswitch settings for all the units in the group be made.
*5. To control the external input to and output from the air conditioners with the PLC software for general equipment via the
G(B)-50A, set SW1-9 and SW1-10 to ON. With these settings made, the power start-stop function becomes disabled. To
use the auto recovery function after power failure while these settings are made, set SW1-5 to ON.
*4 *5
HWE1116DGB
- 22 -
[ II Restrictions ]
CAUTION
(6) Miscellaneous settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.")
When using indoor unit as a cooling-only unit, set SW3-1 to ON.
(7) Various types of control using input-output signal connector on the outdoor unit (various connection options)
TypeUsageFunction
Input Prohibiting cooling/heating operation (thermo OFF) by an external
DEMAND (level)CN3D
input to the outdoor unit.
Performs a low level noise operation of the outdoor unit by an external input to the outdoor unit.
Low-noise mode
*3 *4
(level)
Terminal
to be
*1
used
*2
Option
Adapter for
external input
(PACSC36NA-E)
* It can be used as the silent operation device for each refrigerant
system.
Forces the outdoor unit to perform a fan operation by receiving signals from the snow sensor.
*5
Cooling/heating operation can be changed by an external input to
Snow sensor signal
input (level)
Auto-changeoverCN3N
CN3S
the outdoor unit.
Out-
How to extract signals from the outdoor unit
put
*It can be used as an operation status display device.
*It can be used for an interlock operation with external devices.
Operation status of
the compressor
Error status
*5
*6
CN51Adapter for
external output
(PACSC37SA-E)
*1. For detailed drawing, refer to "Example of wiring connection".
*2. For details, refer to section (4) on the next page, and section (8) Demand control for further details.
*3. Low-noise mode is valid when Dip SW6-8 on the outdoor unit is set to OFF. When DIP SW6-8 is set to ON, 4 levels of
on-DEMAND are possible, using different configurations of low-noise mode input and DEMAND input settings. When 2
or more outdoor units exist in one refrigerant circuit system, 8 levels of on-DEMAND are possible.
*4. By setting Dip SW6-7, the Low-noise mode can be switched between the Capacity priority mode and the Low-noise pri-
ority mode.
When SW6-7 is set to ON: The low-noise mode always remains effective.
When SW6-7 is set to OFF: The low noise mode is cancelled when certain outside temperature or pressure criteria are
met, and the unit goes into normal operation (capacity priority mode).
Low-noise mod is effective.Capacity priority mode becomes effective.
CoolingHeatingCoolingHeating
TH7<30°C[86°F] and
63HS1<32kg/cm
2
TH7>3°C[37°F] and
63LS>4.6kg/cm
2
TH7>35°C[95°F] or
63HS1>35kg/cm
2
TH7<0°C[32°F] or
63LS<3.9kg/cm
*5. Each outdoor unit in the system with multiple outdoor units requires the signal input/output setting to be made.
*6. Take out signals from the outdoor unit (OC) if multiple outdoor units exist in a single system.
1) Wiring should be covered by insulation tube with supplementary insulation.
2) Use relays or switches with IEC or equivalent standard.
3) The electric strength between accessible parts and control circuit should have 2750V or more.
X : Cooling / Heating
Y : Validity / Invalidity of X
X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
(2) CN3S
Relay circuit
Outdoor unit
control board
CN51
Preparations
in the field
X : Relay
Snow sensor : The outdoor fan runs when X is closed
2. Optional part : PAC-SC36NA-E or field supply.
X
OFF
OFF
ON
Normal
CoolingONHeating
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
1
2
Outdoor unit
control board
CN3S
Adapter 2
X
3
Maximum cable
length is 10m
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
in stop mode or thermostat mode.
(4) CN3D
Relay circuit
Adapter
X
Y
1
2
3
Outdoor unit
2
control board
CN3D
Preparations
in the field
Maximum cable
X : Low-noise mode
length is 10m
Y : Compressor ON/OFF
X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC
1
2
Outdoor unit
2
control board
CN3D
Relay circuit
X
Adapter
3
Preparations
in the field
X : Low-noise mode
X : Relay
Maximum cable
length is 10m
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
2. Optional part : PAC-SC36NA-E or field supply.
Low-noise mode : The noise level is reduced by controlling the maximum
fan frequency and maximum compressor frequency.
HWE1116DGB
- 24 -
[ II Restrictions ]
(8) Demand control
1) General outline of control
Demand control is performed by using the external signal input to the 1-2 and 1-3 pins of CN3D on the outdoor units (OC and OS).
Between 2 and 8 steps of demand control is possible by setting Dip SW6-8 on the outdoor units (OC and OS).
NoDemand control switch
Dip SW6-8
Input to CN3D*
2
OCOS
12 steps (0-100%)OFFOFFOC
2
ONOFFOC
4 steps (0-50-75-100%)
3OFFONOS
8 steps
4
(0-25-38-50-63-75-88-100%)
*1 Available demand functions
P72-P144T(Y)KMU-A models (single-outdoor-unit system) : 2 and 4 steps shown in the rows 1 and 2 in the table above only.
P144-P288T(Y)SKMU-A models (two-outdoor-unit system OC+OS) : 2-8 steps shown in the rows 1, 2, 3, and 4 in the table
above only.
*2 Signal is input to CN3D on the outdoor unit whose SW6-8 is set to ON. When SW6-8 is set to OFF on all outdoor units, the
signal is input to the CN3D on the OC.
Outdoor units whose SW6-8 is set to ON are selectable in a single refrigerant system.
*3 If wrong sequence of steps are taken, the units may go into the Thermo-OFF (compressor stop) mode.
Ex) When switching from 100% to 50%
(Incorrect) 100%0%50% The units may go into the Thermo-OFF mode.
(Correct) 100%75%50%
*4 The percentage of the demand listed in the table above is an approximate value based on the compressor volume and does
not necessarily correspond with the actual capacity.
*5 Notes on using demand control in combination with the low-noise mode
To enable the low-noise mode, it is necessary to short-circuit 1-2 pin of CN3D on the outdoor unit whose SW6-8 is set to OFF.
When SW6-8 is set to ON on all outdoor units, the following operations cannot be performed.
Performing 4-step demand in combination with the low-noise operation in a single-outdoor-unit system.
Performing 8-step demand in combination with the low-noise operation in a two-outdoor-unit system.
ONONOC and OS
2) Contact input and control content
2-step demand control
The same control as the Thermo-OFF is performed by closing 1-3 pin of CN3D.
CN3D
1-3
Open100%
Close0%
4-step demand control (When SW6-8 is set to ON on an outdoor unit)
Demand capacity is shown below.
CN3D1-2P
1-3POpenClose
Open100%75%
Close0%50%
8-step demand control (When SW6-8 is set to ON on two outdoor units)
Demand capacity is shown below.
8-step demandNo.2 CN3D
1-2POpenClose
No.1 CN3D1-2P1-3POpenCloseOpenClose
OpenOpen100%50%88%75%
Close50%0%38%25%
CloseOpen88%38%75%63%
Close75%25%63%50%
*1. The outdoor units whose SW6-8 is set to ON are designated as No. 1 and No. 2 in the order of address from small to large.
Ex) When outdoor units whose SW6-8 is set to ON are designated as OC and OS, OC=No. 1 and OS=No. 2.
HWE1116DGB
- 25 -
[ II Restrictions ]
[4] Sample System Connection
Examples of typical system connection are shown on pages [5] to [7].
Refer to the Installation Manual that came with each device or controller for details.
(1) An example of a system to which an MA remote controller is connected
System
configuration
System with one out-
1
2
door unit
System with one out-
door unit
Connection to the system controller
NO
NO
Address start up for in-
door and outdoor units
Grouping of units in a
3
system with multiple
NO
outdoor units
System with one out-
4
5
6
door unit
System with one out-
door unit
System with one out-
door unit
With connection to transmission line
for centralized control
With connection to indoor-outdoor
transmission line
With connection to transmission line
for centralized control
(2) An example of a system to which an ME remote controller is connected
System
configuration
System with one out-
1
door unit
Connection to the system controller
With connection to transmission line
for centralized control
Address start up for indoor
Automatic
address setup
Manual
address setup
Manual
address setup
Manual
address setup
Manual
address setup
Manual
address setup
and outdoor units
Manual
address setup
Notes
Connection of
multiple LOSSNAY units
Connection of
multiple LOSSNAY units
Notes
(3) An example of a system to which both MA remote controller and ME remote controller are connected
System
configuration
System with one out-
1
door unit
Connection to the system controller
With connection to transmission
line for centralized control
Address start up for indoor and outdoor units
Manual
address setup
Notes
*MA remote controller and ME remote controller cannot both be connected to the same group.
HWE1116DGB
- 26 -
[ II Restrictions ]
HWE1116DGB
- 27 -
[ II Restrictions ]
[5] An Example of a System to which an MA Remote Controller is connected
1. System with one outdoor unit (automatic address setup for both indoor and outdoor units)
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OS
00
TB3
M1 M2M1 M2M1 M2
TB7
S
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OC
00
TB3
M1 M2
TB7
L3L1L2
BC
00
TB02
S
M1 M2
S
M1
TB5
M2
IC
00
S
L4L5
15
TB
12
m1
GroupGroup
00
TB5STB
M1
M2
IC
15
12
Interlock operation with
the ventilation unit
LC
00
TB5
M1
M2
S
*1
S
M1 M2
TB02
00
BS
*1. When BS is connected to the system,
automatic address setup is not available.
L11
m4
A1 B2
MA
(2) Cautions
1) ME remote controller and MA remote controller cannot both
be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to
a group of indoor units. It is not possible to connect a pair of
PAR-30MAAU.
3) When the number of the connected indoor units is as shown
in the table below, one or more transmission boosters (sold
separately) are required.
To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor
units that are listed in the specifications for each outdoor
unit.)
Number of transmission
booster (sold separately) required
1 unit 2 units
When the P72 and P96 models
are not included in the connected indoor units
When the P72 and P96 models
are included in the connected
indoor units
27 - 50 units -
21 - 39 units 40 - 50 units
The table above shows the number of transmission boost-
ers that is required by the system with three BC controllers.
For each BC controller that is subtracted from the abovementioned system, two additional indoor units can be connected.
M1
A1 B2
MA
TB5
M2
A1 B2
MA
L12L13
IC
TB
15
12
S
m5
A1 B2
MA
A1 B2
RC
GroupGroup
0000
TB5STB
M1
M2
IC
A1 B2
15
12
A1 B2
MA
MA
IC
00
15
TB5STB
M1
M2
12
m2
m3
4) Automatic address setup is not available if start-stop input(CN32, CN51, CN41) is used for a group operation of indoor units. Refer to "[5] 2. Manual address setup for both
indoor and outdoor units"(page 30)
5) To connect more than 2 LOSSNAY units to indoor units in
the same system, refer to "[5] 2. An example of a system
with one outdoor unit to which 2 or more LOSSNAY units are
connected".(page 30)
(3) Maximum allowable length
1) Indoor/outdoor transmission line
2
Maximum distance (1.25mm
[AWG16] or larger)
L1 +L2+L3+L4+L5 200m[656ft]
L1 +L2+L3+L11+L12+L13 200m[656ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16])
m1 200m [656ft]
m2+m3 200m [656ft]
m4+m5 200m [656ft]
*When connected to the terminal block on the Simple remote controller, use cables that meet the following cable
size specifications: 0.75 - 1.25 mm
2
[AWG18-14].
*When connecting PAR-30MAAU, use a 0.3 mm
sheathed cable.
2
- 28 -
GBHWE1116D
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
units (OC and OS), of the terminal block for indoor-outdoor transmission line (TB02) on the main BC controller
(BC), and of the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC). (Non-polarized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity from large to small (if two or more units have the
same capacity, in the order of address from small to
large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor
units (OC and OS), the S terminal of the terminal block
(TB02) on the BC controller (BC), and the S terminal of
the terminal block (TB5) on the indoor unit (IC) with the
shield of the shielded cable.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Connect terminals 1 and 2 on the terminal block for MA
remote controller line (TB15) on the indoor unit (IC) to the
terminal block on the MA remote controller (MA).
(Non-polarized two-wire)
When 2 remote controllers are connected to the system
When 2 remote controllers are connected to the system,
connect terminals 1 and 2 of the terminal block (TB15) on
the indoor unit (IC) to the terminal block on the two MA
remote controllers.
Set one of the MA remote controllers as a sub controller.
(Refer to the Instruction Manual for the MA remote controller for the setting method.)
Group operation of indoor units
To perform a group operation of indoor units (IC), daisychain terminals 1 and 2 on the terminal block (TB15) on
all indoor units (IC) in the same group, and then connect
terminals 1 and 2 on the terminal block (TB15) on the indoor unit on one end to the terminal block on the MA remotecontroller. (Non-polarized two-wire)
When performing a group operation of indoor units that
have different functions, "Automatic indoor/outdoor addresssetup" is not available.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal
block(TB5) on the indoor unit (IC) to the appropriate terminals on the terminal block (TB5) on LOSSNAY (LC).
(Non-polarized two-wire)
Interlock operation setting with all the indoor units in the
same system will automatically be made. (It is required
that the Lossnay unit be turned on before the outdoorunit.)
When performing an interlocked operation of part of the
indoor units in the system with a LOSSNAY unit, using a
LOSSNAY unit alone without interlocking it with any
units, performing an interlock operation of more than 16
indoor units with a LOSSNAY unit, or connecting two or
more LOSSNAY units to the same refrigerant system,
the automatic IC/OC address setup function is not
available.(page 30)
5) Switch setting
No address settings required.
(5) Address setting method
Proce-
dures
Unit or controller
1Indoor unitMain unitICNo settings
2LOSSNAYLCNo settings
3MA
remote controller
4Outdoor unitOCOSNo settings
5Auxiliary
outdoor unit
Sub unitIC
Main
MANo settings
remote controller
Sub
MASub
remote controller
BC
BCNo settings
controller
Address set-
ting range
required.
required.
required.
remote controller
required.
required.
Setting methodNotes
-Port number setting is re-
Factory
setting
00
quired
To perform a group operation of indoor units that feature different functions, the
automatic IC/OC address
setup function is not available.
-00
-It is not possible to connect a
Main
pair of PAR-30MAAU.
Settings to be
made with the
Sub/Main
switch
-00
-00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the
same).
HWE1116DGB
29- 29 -
[ II Restrictions ]
2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected
(manual address setup for both indoor and outdoor units)
(1) Sample control wiring
Interlock operation with the ventilation unit
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OS
52
TB3
M1 M2
L1L2
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
TB7
M1 M2
S
TB3
M1 M2
L3
OC
51
TB7
M1 M2
S
BC
TB02
M1 M2
IC
53
S
01
TB5STB
M1M2M1M2M1 M2
L4L5
GroupGroup
15
12
m1
IC
02
TB5STB
15
12
TB5
LC
05
S
M1 M2
TB02
57
BS
A1 B2
MA
S
L11
Group
TB5
IC
S
IC
L12L13
15
TB
12
m2
A1 B2
MA
m3
IC
0403
TB5STB
IC
A1 B2
MA
15
12
LC
06
TB5
M1M2M1M2M1M2
S
0807
TB5
15
TB
S
12
A1 B2
M1M2M1M2
TB5STB
15
12
A1 B2
(2) Cautions
1) ME remote controller and MA remote controller cannot both be
connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a
group of indoor units. It is not possible to connect a pair of PAR30MAAU.
3) When the number of the connected indoor units is as shown in
the table below, one or more transmission boosters (sold separately) are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that
are listed in the specifications for each outdoor unit.)
When the P72 and P96 models are not included in the connected indoor units
When the P72 and P96 models are included in the connected indoor units
* If the BC address overlaps any of the addresses that are assigned to either the OC, OS, or BS, use a different, unused address.
OC, OS, and BS addresses (lowest indoor unit address in the group plus +50) have higher priority than the BS address.
MA
MA
The table above shows the number of transmission boost-
ers that is required by the system with three BC controllers.
For each BC controller that is subtracted from the abovementioned system, two additional indoor units can be connected.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 1.
2) Transmission line for centralized control
No connection is required.
Number of transmission
booster (sold separately)
required
1 unit 2 units
27 - 50
units
21 - 39
units
40 - 50
units
-
3) MA remote controller wiring
Same as [5] 1.
- 30 -
GBHWE1116D
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
units (OC and OS), of the terminal block for indoor-outdoor transmission line (TB02) on the main and sub BC
controllers (BC and BS), and of the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit
(IC). (Non-polarized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity from large to small (if two or more units have the
same capacity, in the order of address from small to
large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor
units (OC and OS), the S terminal of the terminal block
(TB02) on BC and BS, and the S terminal of the terminal
block (TB5) on the indoor unit (IC) with the shield of the
shielded cable.
(5) Address setting method
Proce-
dures
1Indoor
Unit or controller
Main unitIC01 to 50
Address
setting
range
unit
Sub unit
2LOSSNAYLC01 to 50
3MA
remote
controller
Main
remote
controller
Sub
remote
controller
MANo set-
tings required.
MASub
remote
controller
4Outdoor unitOCOS51 to 100
5Auxiliary
outdoor
BCcontroller (Sub)
BS51 to 100
unit
BC controller (Main)
BCOC (or OS if it exists) +1
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals
on the terminal block (TB5) on LOSSNAY (LC). (Non-polarized two-wire)
Interlock setting between the indoor units and LOSS-
NAY units must be entered on the remote controller. (Refer to "IV [3] Interlock Settings via the MA Remote
Controller(page 94)" or the installation manual for the
MA remote controller for the setting method.)
5) Switch setting
Address setting is required as follows.
Setting methodNotes
Assign the smallest address to the main
unit in the group.
In a system with a sub BC controller,
make the settings for the indoor units in
the following order.
(i) Indoor unit to be connected to the main
BC controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2
Make the settings for the indoor units in
the way that the formula "(i) < (ii) < (iii)"
is true.
Assign sequential numbers starting with
the address of the main unit in the same
group +1. (Main unit address +1, main unit
address +2, main unit address +3, etc.)
Assign an arbitrary but unique address to
each of these units after assigning an address to all indoor units.
-It is not possible to con-
Settings to be made with the Sub/
Main switch
Assign sequential address to the out door
units in the same refrigerant circuit.
The outdoor units are automatically des-
ignated as OC and OS.(Note)
Assign an address that equals the sum of
the smallest address of the indoor units
that are connected to the sub BC controller
and 50.
Port number setting is
required
To perform a group op-
eration of indoor units
that feature different
functions, designate
the indoor unit in the
group with the greatest
number of functions as
the main unit.
None of these addresses may
overlap any of the indoor unit
addresses.
nect a pair of PAR30MAAU.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC controller overlaps any of the
addresses that are assigned
to the outdoor units or to the
sub BC controller, use a different, unused address within the setting range.
The use of a sub BC control-
ler requires the connection
of a main BC controller.
Fac-
tory
setting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the
same).
HWE1116DGB
31- 31 -
[ II Restrictions ]
3. Group operation of units in a system with multiple outdoor units
(1) Sample control wiring
L12
IC
01
15
12
m2
A1 B2
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OS
52
TB3
M1 M2
TB7
M1 M2
S
L11
Move the male connector
from CN41 to CN40.
SW5-1 OFF
To be left
unconnected
TB3
M1 M2
TB7
M1 M2
51
OC
S
To be connected
BC
53
TB02
M1 M2
TB5STB
S
M1 M2M1 M2
Group
TB5STB
Interlock operation with
the ventilation unit
GroupGroup
TB5
M1 M2
LC
07
S
IC
03
15
12
m1
A1 B2
TB5STB
M1 M2
IC
06
15
12
A1 B2
L31
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
M1 M2
M1 M2
TB3
TB7
L21
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
M1 M2
TB3
TB7
OC
55
S
To be left
unconnected
M1 M2M1 M2
BC
57
TB02
S
M1 M2
OS
56
S
To be left
unconnected
(2) Cautions
1) ME remote controller and MA remote controller cannot both
be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to
a group of indoor units. It is not possible to connect a pair of
PAR-30MAAU.
3) Do not connect the terminal blocks (TB5) on the indoor units
that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must
be performed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for
transmission line for centralized control (TB7) on only one of
the outdoor units.
6) When the number of the connected indoor units is as shown
in the table below, one or more transmission boosters (sold
separately) are required.
To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor
units that are listed in the specifications for each outdoor
unit.)
Number of transmission booster (sold separately) required
1 unit 2 units
When the P72 and P96 models are not included in the connected indoor units
When the P72 and P96 models are included in the connected indoor units
27 - 50 units -
21 - 39 units 40 - 50 units
TB5
MA
m3
L22
IC
MA
Group
IC
0402
TB5STB
TB
15
S
12
15
M1 M2
1212
A1 B2
MA
M1 M2
m4
m5
ers that is required by the system with three BC controllers. For each BC controller that is subtracted from the
above-mentioned system, two additional indoor units
can be connected.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L11+L12 200m [656ft]
L21+L22 200m [656ft]
2) Transmission line for centralized control
L31+L21 200m [656ft]
3) MA remote controller wiring
Same as [5] 1.
4) Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger)
L12(L11)+L31+L22(L21) 500m [1640ft]
MA
IC
05
TB5 TB15
S
2
[AWG16] or larger)
The left table shows the number of transmission boost-
- 32 -
GBHWE1116D
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 2.
Shielded cable connection
Same as [5] 2.
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block for
transmission line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the OC
and OS (Note a) in the same refrigerant circuit.
If a power supply unit is not connected to the transmission
line for centralized control, replace the power jumper connector on the control board from CN41 to CN40 on only one
of the outdoor units.
a) The outdoor units in the same refrigerant circuit are automat-
ically designated as OC and OS in the order of capacity from
large to small (if two or more units have the same capacity,
in the order of address from small to large).
b) If TB7's on the outdoor units in the same refrigerant circuit
are not daisy-chained, connect the transmission line for the
central control system to TB7 of the OC. (Note a).To maintain the central control even during an OC failure or a power
failure, connect TB7 on OC and OS together. (If there is a
problem with the outdoor unit whose power jumper was
(5) Address setting method
Proce-
dures
1Indoor
Unit or controller
Main unitIC01 to 50
Address
setting
range
unit
Sub unit
2LOSSNAYLC01 to 50
3MA
remote
controller
Main
remote
controller
Sub
remote
controller
MANo set-
tings required.
MASub
remote
controller
4Outdoor unit OCOS51 to 100
5Auxiliary
outdoor
BCcontroller (Sub)
BS51 to 100
unit
BC controller (Main)
BCOC (or OS if it exists) +1
moved from CN41 to CN40, central control is not possible,
even if TB7's are daisy-chained.)
c) When connecting TB7, only commence after checking that
the voltage is below 20 VDC.
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on
the outdoor units (OC, OS) with the shield wire of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose
power jumper connector is mated with CN40.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Same as [5] 2.
5) Switch setting
Address setting is required as follows.
Setting methodNotes
Assign the smallest address to the main
unit in the group.
In a system with a sub BC controller,
make the settings for the indoor units in
the following order.
(i) Indoor unit to be connected to the main
BC controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2
Make the settings for the indoor units in
the way that the formula "(i) < (ii) < (iii)"
is true.
Assign sequential numbers starting with
the address of the main unit in the same
group +1. (Main unit address +1, main unit
address +2, main unit address +3, etc.)
Assign an arbitrary but unique address to
each of these units after assigning an address to all indoor units.
-It is not possible to con-
Settings to be made with the Sub/
Main switch
Assign sequential address to the out door
units in the same refrigerant circuit.
The outdoor units are automatically des-
ignated as OC and OS.(Note)
Assign an address that equals the sum of
the smallest address of the indoor units
that are connected to the sub BC controller
and 50.
Port number setting is
required
To perform a group op-
eration of indoor units
that feature different
functions, designate
the indoor unit in the
group with the greatest
number of functions as
the main unit.
None of these addresses may
overlap any of the indoor unit
addresses.
nect a pair of PAR30MAAU.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC controller overlaps any of the
addresses that are assigned
to the outdoor units or to the
sub BC controller, use a different, unused address within the setting range.
The use of a sub BC control-
ler requires the connection
of a main BC controller.
Fac-
tory
setting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the
same).
HWE1116DGB
33- 33 -
[ II Restrictions ]
4. A system in which a system controller is connected to the transmission line for centralized control and which is powered from an outdoor unit
(1) Sample control wiring
Interlock operation with
15
12
the ventilation unit
IC
03
TB5STB
12
LC
07
15
TB5
M1 M2
S
L11
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OS
52
TB3
M1 M2M1 M2
Move the male connector
from CN41 to CN40.
SW5-1 OFF
OC
51
TB3
53
TB02
M1 M2
L12
BC
Group
IC
01
15
S
TB5STB
M1 M2
12
GroupGroup
IC
02
TB5STB
M1 M2M1M2
L31
TB7
M1 M2
S
To be left
unconnected
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OS
56
TB3
TB7
M1 M2M1 M2
S
To be left
unconnected
L21
TB7
M1 M2
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OC
55
TB3
M1 M2M1 M2
TB7
S
To be connected
To be left
S
unconnected
L32
System controller
ABS
Note1
BC
57
TB02
M1 M2
S
(2) Cautions
1) ME remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of
indoor units. It is not possible to connect a pair of PAR-30MAAU.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be performed only on one of the outdoor units.
5) When the System controller is connected TB7 side and TKMU outdoor
unit model is used, connect a PAC-SC51KUA to TB7 side. If a PACSC51KUA cannnot be used, connect the System controller to TB3 side.
When YKMU outdoor unit model is used, the male power supply connector can be connected to CN40, and the System controller can be connected to TB7 side.
6) Short-circuit the shield terminal (S terminal) and the earth terminal ( )
on the terminal block for transmission line for centralized control (TB7) on
the outdoor unit whose power jumper connector is mated with CN40.
7) When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
Number of transmission booster
(sold separately) required
1 unit 2 units
When the P72 and P96 models are
not included in the connected indoor units
When the P72 and P96 models are
included in the connected indoor
units
27 - 50 units -
21 - 39 units 40 - 50 units
Group
TB5
M1 M2
A1B
2
MA
L22
IC
TB
15
12
S
A1B
MA
TB5STB
m2m1
2
m3
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 208 - 230V.
A1B
2
MA
IC
Group
0504
15
12
IC
06
TB5STB
15
12
A1B
MA
A1B
2
MA
LC
08
TB5
S
M1 M2M1 M2M1 M2
2
The left table shows the number of transmission boosters
that is required by the system with three BC controllers. For
each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
8) When a power supply unit is connected to the transmission
line for centralized control, leave the power jumper connector on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
L31+L32(L21) 200m [656ft]
Daisy-chain terminals A and B on the system controller, terminals M1 and M2 on the terminal block for transmission line
for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the outdoor units (OC and
OS) in the same refrigerant circuit. (Note b)
If a power supply unit is not connected to the transmission
line for centralized control, replace the power jumper connector on the control board from CN41 to CN40 on only one
of the outdoor units.
If a system controller is connected, set the central control
switch (SW5-1) on the control board of all outdoor units to
"ON."
a) The outdoor units in the same refrigerant circuit are automat-
ically designated as OC and OS in the order of capacity from
large to small (if two or more units have the same capacity,
in the order of address from small to large).
b) If TB7's on the outdoor units in the same refrigerant circuit
are not daisy-chained, connect the transmission line for the
central control system to TB7 of the OC. (Note a).To maintain the central control even during an OC failure or a power
failure, connect TB7 on OC and OS together. (If there is a
problem with the outdoor unit whose power jumper was
(5) Address setting method
moved from CN41 to CN40, central control is not possible,
even if TB7's are daisy-chained.)
c) When connecting TB7, only commence after checking that
the voltage is below 20 VDC.
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal of the terminal block (TB7) on the
system controller, OC, and OS with the shield of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose
power jumper connector is mated with CN40.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block (TB5)
on the indoor unit (IC) to the appropriate terminals on the
terminal block for indoor-outdoor transmission line (TB5) on
LOSSNAY (LC). (Non-polarized two-wire)
Indoor units must be interlocked with the LOSSNAY unit us-
ing the system controller. (Refer to the operation manual for
the system controller for the setting method.) Interlock setting from the remote controller is required if the ON/OFF remote controller alone or the LM adapter alone is connected.
5) Switch setting
Address setting is required as follows.
Proce-
dures
1Indoor
Unit or controller
Main unitIC01 to
unit
Sub unit
2LOSSNAYLC01 to
3MA
remote
controller
Main
remote controller
Sub
remote controller
MA
MA
4Outdoor unit (Note)OC
OS
5Auxiliary
outdoor
BCcontroller (Sub)
BS
unit
BC controller (Main)
BCOC (or OS if it exists) +1
Ad-
dress
setting
Setting methodNotes
range
Assign the smallest address to the main unit
50
50
No settings required.
Sub
remote
controller
51 to 100Assign sequential address to the outdoor
51 to 100 Assign an address that equals the sum of the
in the group.
In a system with a sub BC controller, make
the settings for the indoor units in the following order.
(i) Indoor unit to be conn ected to the main BC
controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2
Make the settings for the indoor units in the
way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the
address of the main unit in the same group
+1. (Main unit address +1, main unit address
+2, main unit address +3, etc.)
Assign an arbitrary but unique address to
each of these units after assigning an address
to all indoor units.
-
Settings to be made with the Sub/
Main switch
units in the same refrigerant circuit.
The outdoor units are automatically desig-
nated as OC and OS.(Note)
smallest address of the indoor units that are
connected to the sub BC controller and 50.
Port number setting is re-
quired
To perform a group opera-
tion of indoor units that feature different functions,
designate the indoor unit in
the group with the greatest
number of functions as the
main unit.
None of these addresses may overlap any of the indoor unit addresses.
Make the same indoor unit group
settings with the system controller
as the ones that were made with the
MA remote controller. It is not possible to connect a pair of PAR30MAAU.
To set the address to 100, set the
rotary switches to 50.
If the addresses that is assigned to
the main BC controller overlaps
any of the addresses that are assigned to the outdoor units or to
the sub BC controller, use a different, unused address within the
setting range.
The use of a sub BC controller re-
quires the connection of a main
BC controller.
Fac-
tory
setting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE1116DGB
35- 35 -
[ II Restrictions ]
5. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except
LM adapter)
(1) Sample control wiring
Interlock operation with
15
12
the ventilation unit
GroupGroupGroup
IC
03
TB5STB
12
M2M1M2M1
LC
07
TB5
15
S
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OS
52
TB3
M2M1M2M1
L11
CN41 CN40 Replace
SW5-1 OFF ON
51
TB3
L12
OC
BC
53
TB02
M2M1
IC
01
15
S
TB5STB
M2M1M2M1
12
IC
02
TB5STB
L21
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
TB7
55
TB3
TB7
M2M1
OC
M2M1
M2M1
S
S
Not
Connect
Connect
L25
BC
57
TB02
M2M1
S
Note1
System controller
ABS
GroupGroup
L31
TB7
M2M1
S
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OS
56
TB3
M2M1
TB7
M2M1
S
Not
Connect
Not
Connect
(2) Cautions
1) ME remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group
of indoor units. It is not possible to connect a pair of PAR-30MAAU.
3) Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be performed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for transmission line for centralized control (TB7) on only one of the outdoor
units.
6) A maximum of 3 system controllers can be connected to the indooroutdoor transmission line, with the exception that only one G(B)-50A
may be connected.
7) When the total number of indoor units exceeds 20 (12 if one or more
indoor units of the 72 model or above is connected), it may not be
possible to connect a system controller to the indoor-outdoor transmission line.
8) When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
TB5
A1B
2
MA
L22
IC
15
TB
12
S
A1B
MA
TB5STB
M2M1M2M1
m2m1
2
m3
When the P72 and P96 models are not
included in the connected indoor units
When the P72 and P96 models are included in the connected indoor units
The table above shows the number of transmission boosters that is
required by the system with three BC controllers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.
Refer to the DATABOOK for further information about how many
booster units are required for a given system.
A1B
2
MA
IC
0504
15
12
Note1 LM adapters cannot be connected to the
indoor-outdoor transmission line.
IC
06
TB5STB
M2M1
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
2) Transmission line for centralized control
L31+L21 200m [656ft]
3) MA remote controller wiring
Same as [5] 1.
4) Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger)
L25+L31+L12(L11) 500m [1640ft]
L12(L11)+L31+L22(L21) 500m [1640ft]
A1B
2
MA
LC
08
TB5
15
12
A1B
MA
S
M2M1
2
Number of transmission booster (sold separately) required
1 unit 2 units
27 - 50 units -
21 - 39 units 40 - 50 units
2
[AWG16] or larger)
- 36 -
GBHWE1116D
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block for indooroutdoor transmission line (TB3) on the outdoor units (OC and OS)
(Note a), of the terminal block for indoor-outdoor transmission line
(TB02) on the main and sub BC controllers (BC and BS), of the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC), and the S terminal of the system controller.(Nonpolarized two-wire)
Only use shielded cables.
a) The outdoor units in the same refrigerant circuit are automatically
designated as OC and OS in the order of capacity from large to small
(if two or more units have the same capacity, in the order of address
from small to large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor units (OC and
OS), the S terminal of the terminal block (TB02) on the BC and BS,
and the S terminal of the terminal block (TB5) on the indoor unit (IC)
with the shield of the shielded cable.
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on the outdoor units (OC) in
different refrigerant circuits and on the OC and OS in the same refrigerant circuit. (Note b)
If a power supply unit is not connected to the transmission line for
centralized control, replace the power jumper connector on the control board from CN41 to CN40 on only one of the outdoor units.
Set the central control switch (SW5-1) on the control board of all outdoor units to "ON."
b) If TB7's on the outdoor units in the same refrigerant circuit are not
(5) Address setting method
daisy-chained, connect the transmission line for the central control
system to TB7 of the OC. (Note a).To maintain the central control
even during an OC failure or a power failure, connect TB7 on OC
and OS together. (If there is a problem with the outdoor unit whose
power jumper was moved from CN41 to CN40, central control is not
possible, even if TB7's are daisy-chained.)
c) When connecting TB7, only commence after checking that the volt-
age is below 20 VDC.
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on the outdoor units (OC, OS) with the shield wire of the shielded cable. Shortcircuit the earth terminal ( ) and the S terminal on the terminal
block (TB7) on the outdoor unit whose power jumper connector is
mated with CN40.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block (TB5) on the indoor units (IC) to the appropriate terminals on the terminal block for
indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-polarized two-wire)
Indoor units must be interlocked with the LOSSNAY unit using the
system controller. (Refer to the operation manual for the system
controller for the setting method.) Interlock setting from the remote
controller is required if the ON/OFF remote controller alone is connected.
5) Switch setting
Address setting is required as follows.
Proce-
dures
1Indoor
Unit or controller
Main unitIC01 to
unit
Sub unit
2LOSSNAYLC01 to
3MA
remote
controller
Main
remote controller
Sub
remote controller
MA
MA
4Outdoor unitOC
OS
5Auxiliary
outdoor
BCcontroller (Sub)
BS
unit
BC controller (Main)
BCOC (or OS if it exists) +1
Address
setting
range
Assign the smallest address to the main unit
50
50
No settings required.
Sub
remote
controller
51 to 100Assign sequential address to the outdoor
51 to 100 Assign an address that equals the sum of the
in the group.
In a system with a sub BC controller, make
the settings for the indoor units in the following order.
(i) Indoor unit to be connected to the main BC
controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2
Make the settings for the indoor units in the
way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the
address of the main unit in the same group
+1. (Main unit address +1, main unit address
+2, main unit address +3, etc.)
Assign an arbitrary but unique address to
each of these units after assigning an address
to all indoor units.
Settings to be made with the Sub/
Main switch
units in the same refrigerant circuit.
The outdoor units are automatically desig-
nated as OC and OS.(Note)
smallest address of the indoor units that are
connected to the sub BC controller and 50.
Setting methodNotes
-
Port number setting is
required
To perform a group op-
eration of indoor units
that feature different
functions, designate
the indoor unit in the
group with the greatest
number of functions as
the main unit.
None of these addresses may
overlap any of the indoor unit
addresses.
Make the same indoor unit
group settings with the system
controller as the ones that
were made with the MA remote
controller.
It is not possible to connect a
pair of PAR-30MAAU.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC controller overlaps any of the
addresses that are assigned
to the outdoor units or to the
sub BC controller, use a different, unused address within the setting range.
The use of a sub BC control-
ler requires the connection
of a main BC controller.
Factory set-
ting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE1116DGB
37- 37 -
[ II Restrictions ]
6. A system with multiple BC controller connections (with a system controller connected to the centralized control line)
(1) Sample control wiring
L31
L11
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
M1M2
M1M2
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
M1M2
M1M2M1M2
OS
52
TB3
TB7
S
OS
55
TB3
TB7
S
Move the male connector
from CN41 to CN40
SW5-1 OFF ON
To be left
unconnected
L21
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
To be left
unconnected
L32
OC
BC
51
TB3
M1M2M1M2
TB7
S
M1M2
To be connected
OC
BC
54
TB3
M1M2
TB7
S
M1M2
To be left
unconnected
System
controller
ABS
L12
Group
IC
112122212
5357
TB02
01
15
TB5STB
S
M1M2
12
M1M2M1M2M1M2M1M2M1M2M1M2M1M2M1M2M1M2
m2
A1 B2
MA
m3
GroupGroupGroup
IC
02
TB5STB
12
15
TB5STB
BS
IC
04
57
15
TB02
12
A1 B2
MA
L22
IC
07
15
TB5STB
S
12
A1 B2
MA
GroupGroupGroup
IC
11211
5659
TB5
TB02
S
Note1
TB
15
12
S
M1M2M1M2
A1 B2
MA
*1 When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
IC
0503
TB5STB
m1
12
A1 B2
IC
06
15
TB5STB
M1M2
MA
3231
15
12
M1M2
TB02
BS
IC
09
TB5STB
S
15
12
M1M2
A1 B2
MA
Numbers in the square indicate port numbers.
Connection to BC controllers
Interlock operation with the ventilation unit
*2 LM adapters require the power supply capacity of single-phase AC 208 - 230V.
TB5STB
TB5STB
M1M2
12
LC
13
TB5
15
S
BS
IC
08
61
15
TB02
12
IC
10
15
TB5
12
M1M2
IC
12
11
15
TB5STB
S
LC
14
S
12
A1 B2
MA
IC
12
12
TB5STB
(2) Cautions
1) ME remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group
of indoor units. It is not possible to connect a pair of PAR-30MAAU.
3) Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be performed only on one of the outdoor units.
5) Short-circuit the S (shield) terminal of the terminal block for the central control unit (TB7) and the ground terminal ( ) on the outdoor
unit whose power jumper was moved from CN41 to CN40.
6) When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
Number of transmission
booster (sold separately)
required
1 unit 2 units
When the P72 and P96 models are not included in the connected indoor units
When the P72 and P96 models are included in the connected indoor units
27 - 50
units
21 - 39
units
40 - 50
units
-
The table above shows the number of transmission boost-
ers that is required by the system with three BC controllers.
For each BC controller that is subtracted from the abovementioned system, two additional indoor units can be connected.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
7) When a power supply unit is connected to the transmission
line for centralized control, leave the power jumper connector on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
2
Maximum distance (1.25mm
[AWG16] or larger)
L11+L12 200m [656ft]
L21+L22 200m [656ft]
2) Transmission line for centralized control
L31+L32(L21) 200m [656ft]
3) MA remote controller wiring
Maximum overall line length
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
units (OC and OS) (Note a), of the terminal block for indoor-outdoor transmission line (TB02) on the main and
sub BC controllers (BC and BS), and of the terminal
block for indoor-outdoor transmission line (TB5) on each
indoor unit (IC). (Non-polarized two-wire)
Only use shielded cables.
a) The outdoor units in the same refrigerant circuit are auto-
matically designated as OC and OS in the order of capacity from large to small (if two or more units have the
same capacity, in the order of address from small to
large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor units
(OC and OS), the S terminal of the terminal block (TB02)
on the BC and BS, and the S terminal of the terminal
block (TB5) on the indoor unit (IC) with the shield of the
shielded cable.
2) Transmission line for centralized control
Daisy-chain terminals A and B of the system controller,
M1 and M2 terminals of TB7 (terminal block for centralized control system connection) on the outdoor units
(OC) in different refrigerant systems, and M1 and M2 terminals of TB7 (terminal block for centralized control system connection) on the outdoor units (OC and OS ) in the
same refrigerant circuit. (Note b)
If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the control board from CN41 to CN40 on
only one of the outdoor units.
When connecting a system controller, set the centralized
control switch (SW5-1) on the control board of all indoor
units to "ON."
cuit are not daisy-chained, connect the transmission line
for the central control system to TB7 of the OC. (Note
a).To maintain the central control even during an OC failure or a power failure, connect TB7 on OC and OS together. (If there is a problem with the outdoor unit whose
power jumper was moved from CN41 to CN40, central
control is not possible, even if TB7's are daisy-chained.)
c) When connecting TB7, only commence after checking
that the voltage is below 20 VDC.
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal of the terminal block (TB7) on
the system controller, OC, and OS with the shield of the
shielded cable. Short-circuit the earth terminal ( ) and
the S terminal on the terminal block (TB7) on the outdoor
unit whose power jumper connector is mated with CN40.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals
on the terminal block for indoor-outdoor transmission line
(TB5) on LOSSNAY (LC). (Non-polarized two-wire)
Indoor units must be interlocked with the LOSSNAY unit
using the system controller. (Refer to the operation manual for the system controller for the setting method.) Interlock setting from the remote controller is required if the
ON/OFF remote controller alone or the LM adapter alone
is connected.
5) Switch setting
Address setting is required as follows.
b) If TB7's on the outdoor units in the same refrigerant cir-
HWE1116DGB
39- 39 -
[ II Restrictions ]
(5) Address setting method
Pro-
cedur
es
1Indoor
Unit or controller
Main unit IC01 to 50
Address
setting
range
unit
Sub unit
2LOSSNAYLC01 to 50
3MA
remote
controller
Main remote
controller
Sub remote controller
4Outdoor unitOC
No set-
MA
tings required.
Sub re-
MA
mote
controller
51 to 100The sum of the smallest address of the indoor units in
OS
5Auxilia-
ry outdoor
unit
BC
controller
(Sub)
BC controller
(Main)
51 to 100 Assign an address that equals the sum of the smallest
BS
BC51 to
100
Setting methodNotes
Assign the smallest address to the main unit in the
group.
In a system with a sub BC controller, make the set-
tings for the indoor units in the following order.
(i) Indoor unit to be connected to the main BC control-
ler
(ii) Indoor unit to be connected to sub BC controller 1
(iii) Indoor unit to be connected to sub BC controller 2
Make the settings for the indoor units in the way that
the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the address of
the main unit in the same group +1. (Main unit address
+1, main unit address +2, main unit address +3, etc.)
Assign an arbitrary but unique address to each of these
units after assigning an address to all indoor units.
-
Settings to be made with the Sub/Main switch
the same system and 50.
Assign sequential address to the outdoor units in the
same refrigerant circuit.
The outdoor units are automatically designated as
OC and OS.(Note)
address of the indoor units that are connected to the
sub BC controller and 50.
OC (or OS if it exists) +1
Port number setting is re-
quired
To perform a group opera-
tion of indoor units that
feature different functions,
designate the indoor unit
in the group with the
greatest number of functions as the main unit.
None of these addresses may
overlap any of the indoor unit addresses.
Make the same indoor unit group
settings with the system controller
as the ones that were made with
the MA remote controller.
It is not possible to connect a pair
of PAR-30MAAU.
To set the address to 100, set
the rotary switches to 50.
To set the address to 100, set
the rotary switches to 50.
If the addresses that is assigned
to the main BC controller overlaps any of the addresses that
are assigned to the outdoor
units or to the sub BC controller, use a different, unused address within the setting range.
The use of a sub BC controller
requires the connection of a
main BC controller.
Fac-
tory
setting
00
00
Mai
n
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
- 40 -
GBHWE1116D
[ II Restrictions ]
HWE1116DGB
41- 41 -
[ II Restrictions ]
[6] An Example of a System to which an ME Remote Controller is connected
(1) Sample control wiring
L11
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OS
52
TB3
M1M2M1M2
TB7
M1M2
S
Leave the male
connector on
CN41 as it is.
L31
SW5-1 OFF ON
OS
56
TB3
M1M2M1M2
TB7
M1M2M1M2
S
Move the male connector
from CN41 to CN40.
SW5-1 OFF ON
To be left
unconnected
L21
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
To be left
unconnected
OC
51
TB3
TB7
M1 M2
S
OC
55
TB3
TB7
S
System controller
To be connected
To be left
unconnected
L32
ABS
Note1
BC
53
TB02
M1M2
BC
Group
IC
01
Group
TB5STB
M1M2
A1 B2
101
RC
S
57
TB02
M1M2
S
m3
A1 B2
154
RC
*1 When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
*2 LM adapters require the power supply capacity of single-phase AC 208 - 230V.
L12
GroupGroup
02
15
12
m1
L22
TB5STB
M1M2
A1 B2
102
RC
IC
0504
TB5
M1M2M1M2M1M2M1M2
A1 B2
104
RC
TB5STB
TB
15
12
S
m2
Interlock operation with the ventilation unit
IC
IC
03
Group
TB5STB
A1 B2
103
RC
IC
15
12
IC
06
15
TB5STB
A1 B2
106
RC
15
12
12
15
12
TB5
LC
07
TB5
S
M1M2M1M2
LC
08
S
(2) Cautions
1) ME remote controller and MA remote controller cannot both
be connected to the same group of indoor units.
2) No more than 2 ME remote controllers can be connected to
a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units
that are connected to different outdoor units with each other.
4) Replace the power jumper connector of the control board
from CN41 to CN40 on only one of the outdoor units.
5) Provide an electrical path to ground for the S terminal on the
terminal block for centralized control on only one of the outdoor units.
6) When the number of the connected indoor units is as shown
in the table below, one or more transmission boosters (sold
separately) are required.
To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor
units that are listed in the specifications for each outdoor
unit.)
Number of transmission bo oster
(sold separately) required
1 unit 2 units 3 units
When the P72 and P96 models are not
included in the connected indoor units
When the P72 and P96 models are included in the connected indoor units
15 - 34
units
11 - 26
units
The left table shows the number of transmission boosters
35 - 50
units
27 - 42
units
-
43 - 50
units
that is required by the system with three BC controllers. For
each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
7) When a power supply unit is connected to the transmission
line for centralized control, leave the power jumper connector on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Same as [5] 4.
3) ME remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16])
m1 10m [32ft]
m2+m3 10m [32ft]
If the standard-supplied cable must be extended, use a
cable with a diameter of 1.25mm
2
[AWG16]. The section
of the cable that exceeds 10m [32ft] must be included in
the maximum indoor-outdoor transmission line distance
described in (1).
When connected to the terminal block on the Simple remote controller, use cables that meet the following cable
size specifications: 0.75 - 1.25 mm
4) Maximum line distance via outdoor unit
(1.25 mm
2
[AWG16] or large)
2
[AWG18-16].
Same as [5] 4.
- 42 -
GBHWE1116D
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 2.
Shielded cable connection
Same as [5] 2.
2) Transmission line for centralized control
Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3) ME remote controller wiring
ME remote controller is connectable anywhere on the in-
door-outdoor transmission line.
(5) Address setting method
Ad-
Proce-
dures
Unit or controller
dress
setting
range
1Indoor
unit
Main unitIC01 to
50
Sub unit
2LOSSNAYLC01 to
50
3ME
remote
controller
4Outdoor unitOC
Main
remote controller
Sub
remote controller
RC101 to
150
RC151 to
200
51 to 100Assign sequential address to the outdoor
OS
5Auxiliary
outdoor
BCcontroller (Sub)
51 to 100 Assign an address that equals the sum of the
BS
unit
BC controller (Main)
BCOC (or OS if it exists) +1
When 2 remote controllers are connected to the system
Refer to the section on Switch Setting.
Performing a group operation (including the group
operation of units in different refrigerant circuits).
Refer to the section on Switch Setting.
4) LOSSNAY connection
Same as [5] 4.
5) Switch setting
Address setting is required as follows.
Setting methodNotes
Assign the smallest address to the main unit
in the group.
In a system with a sub BC controller, make
the settings for the indoor units in the following order.
(i) Indoor unit to be connected to the main BC
controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2
Make the settings for the indoor units in the
way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the
address of the main unit in the same group
+1. (Main unit address +1, main unit address
+2, main unit address +3, etc.)
Assign an arbitrary but unique address to
each of these units after assigning an address
to all indoor units.
Add 100 to the main unit address in
the group
Add 150 to the main unit address in
the group
units in the same refrigerant circuit.
The outdoor units are automatically desig-
nated as OC and OS.(Note)
smallest address of the indoor units that are
connected to the sub BC controller and 50.
Port number setting is
required
To perform a group op-
eration of indoor units
that have different functions, set the indoor unit
in the group with the
greatest number of
functions as the main
unit.
None of these addresses may
overlap any of the indoor unit
addresses.
It is not necessary to set the
100s digit.
To set the address to 200,
set the rotary switches to 00.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC controller overlaps any of the
addresses that are assigned
to the outdoor units or to the
sub BC controller, use a different, unused address within the setting range.
The use of a sub BC control-
ler requires the connection
of a main BC controller.
Fac-
tory
setting
00
00
101
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the
same).
HWE1116DGB
43- 43 -
[ II Restrictions ]
[7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected
(1) Sample control wiring
L12
GroupGroup
IC
01
15
TB5STB
M1M2M1M2M1M2
12
IC
02
TB5STB
15
12
IC
06
TB5STB
15
12
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OS
52
TB3
M1M2
L11
Move the male connector
from CN41 to CN40.
SW5-1 OFF ON
M1M2
51
TB3
OC
BC
53
TB02
M1M2
S
TB7
M1M2
S
Leave the male
connector on
CN41 as it is.
L31
SW5-1 OFF ON
OS
55
TB3
TB7
S
To be left
unconnected
L21
To be left
unconnected
TB7
M1M2
S
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OC
54
TB3
TB7
S
M1 M2M1 M2
To be connected
To be left
unconnected
L32
Note1
System controller
ABS
M1 M2M1 M2M1 M2
BC
56
TB02
S
(2) Cautions
1) Be sure to connect a system controller.
2) ME remote controller and MA remote controller cannot both be connected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote controller addresses that are smaller than those of the indoor units that are connected to the ME remote controller.
4) No more than 2 ME remote controllers can be connected to a group
of indoor units.
5) No more than 2 MA remote controllers can be connected to a group
of indoor units. It is not possible to connect a pair of PAR-30MAAU.
6) Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
7) Replace the power jumper connector of the control board from CN41
to CN40 on only one of the outdoor units.
8) Provide an electrical path to grou nd for the S terminal on the terminal
block for centralized control on only one of the outdoor units.
9) When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
Number of transmission booster
(sold separately) required
1 unit 2 units 3 units
When the P72 and P96 models
are not included in the connected
indoor units
When the P72and P96 models
are included in the connected indoor units
15 - 34
units
11 - 26
units
35 - 50
units
27 - 42
units
-
43 - 50
units
A1 B2
A1 B2
106
MA
L22
IC
GroupGroup
IC
0403
TB5
TB
15
12
S
A1 B2
MA
*1 When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
*2 LM adapters require the power supply capacity of single-phase AC 208 - 230V.
TB5STB
A1 B2
104
RC
15
12
05
TB5STB
M1M2M1M2M1 M2
RC
IC
15
12
The left table shows the number of transmission boost-
ers that is required by the system with three BC controllers. For each BC controller that is subtracted from the
above-mentioned system, two additional indoor units
can be connected.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
10) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
- 44 -
GBHWE1116D
[ II Restrictions ]
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Same as [5] 4.
3) MA remote controller wiring
Same as [5] 1.
4) ME remote controller wiring
Same as [6]
5) Maximum line distance via outdoor unit
(1.25 mm
2
[AWG16] or larger)
Same as [5] 4.
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 2.
Shielded cable connection
Same as [5] 2.
2) Transmission line for centralized control
Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3) MA remote controller wiring
When 2 remote controllers are connected to the system
Group operation of indoor units
Same as [5] 1.
4) ME remote controller wiring
When 2 remote controllers are connected to the system
Group operation of indoor units
Same as [6]
5) LOSSNAY connection
Same as [5] 4.
6) Switch setting
Address setting is required as follows.
HWE1116DGB
45- 45 -
[ II Restrictions ]
(5) Address setting method
Pro-
ce-
dure
Unit or controller
s
1Opera-
tion with
the
Indoor
unit
Main
unit
IC01 to
50
MA remote
controller
2Opera-
tion with
the
ME remote
MA
remote
controller
Indoor
unit
Sub
unit
Main remote
controller
Sub
remote
controller
Main
unit
Sub
unit
IC01 to
50
No
MA
settings required.
Sub
MA
remote
controller
IC01 to 50Assign the smallest address
IC01 to
50
controller
ME
remote
controller
Main remote
controller
Sub
remote
controller
RC101 to
150
RC151 to
200
3LOSSNAYLC01 to
50
4Outdoor unitOCOS51 to
100
5Auxiliary
outdoor
BCcontroller (Sub)
BS51 to
100
unit
BC controller
(Main)
BCOC (or OS if it exists) +1
Ad-
dress
set-
ting
range
Setting methodNotes
Assign the smallest address to
the main unit in the group.
In a system with a sub BC con-
troller, make the settings for the
indoor units in the following order.
(i) Indoor unit to be connected to
the main BC controller
(ii) Indoor unit to be connected to
sub BC controller 1
(iii) Indoor unit to be connected to
sub BC controller 2
Make the settings for the indoor
units in the way that the formula "(i)
< (ii) < (iii)" is true.
Assign sequential numbers starting with the address of the main
unit in the same group +1. (Main
unit address +1, main unit address
+2, main unit address +3, etc.)
-
Assign an address smaller than that of
the indoor unit that is connected to the
ME remote controller.
Enter the same indoor unit group set-
tings on the system controller as the
ones that were entered on the MA remote controller.
To perform a group operation of indoor
units that have different functions, designate the indoor unit in the group with
the greatest number of functions as the
main unit.
Port number setting is required.
It is not possible to connect a pair
of PAR-30MAAU.
Settings to be made according
to the remote controller function selection
Assign an address higher than those of
to the main unit in the group.
Assign sequential numbers
starting with the address of the
main unit in the same group
+1. (Main unit address +1,
main unit address +2, main
unit address +3, etc.)
Add 100 to the main unit address in the group.
the indoor units that are connected to
the MA remote controller.
Make the initial settings for the indoor
unit group settings via the system controller.
To perform a group operation of indoor
units that have different functions, designate the indoor unit in the group with
the greatest number of functions as the
main unit.
Port number setting is required.
Addresses that are assigned to the in-
door units that are connected to t he sub
BC controller should be higher than the
addresses that are assigned to the indoor units that are connected to the
main BC controller.
It is not necessary to set the 100s
digit.
To set the address to 200, set it to
00.
Add 150 to the main unit address in the group.
Assign an arbitrary but unique
address to each of these units
None of these addresses may over-
lap any of the indoor unit addresses.
after assigning an address to
all indoor units.
Assign sequential address to the
outdoor units in the same refrigerant circuit.
The outdoor units are automati-
cally designated as OC and
OS.(Note)
Assign an address that equals the
sum of the smallest address of the
indoor units that are connected to
the sub BC controller and 50.
To set the address to 100, set it to 50.
If the addresses that is assigned to the
main BC controller overlaps any of the
addresses that are assigned to the outdoor units or to the sub BC controller,
use a different, unused address within
the setting range.
The use of a sub BC controller requires
the connection of a main BC controller.
Factory set-
ting
00
Main
00
101
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
- 46 -
GBHWE1116D
[ II Restrictions ]
[8] Restrictions on Pipe Length
(1) System that requires 16 BC controller ports or fewer <System with only the main BC controller or standard BC con-
troller>
Outdoor unit
*Use a main BC controller when connecting the outdoor units of
P144 model or above.
Branch joint
(CMY-Y102S-G2)
b
B
c
Maximum of 3 units per port
Total capacity of P54 or below
Indoor
d
h2
HH'
h1
Reducer (P06 - P18 models)
(Supplied with the BC Controller)
a
IndoorIndoorIndoor
(P06 - P54 models)(P72 - P96 models)
A
BC controller
Junction pipe
(CMY-R160-J)
Unit: m [ft]
OperationPipe sectionsAllowable length of pipes
LengthTotal pipe lengthA+B+a+b+c+dRefer to the restrictions on the total piping
length in the graph on the next page.
Total pipe length from the outdoor unit
to the farthest indoor unit
Between outdoor unit and BC control-
A+B+d165 [541] or less
(Equivalent length 190 [623] or less)
A110 [360] or less
ler
*1
Height
difference
Between BC controller and indoor unitB+d40 [131] or less
Between indoor
and outdoor units
Outdoor unit
above indoor unit
Outdoor unit be-
H50 [164] or less
H'40 [131] or less
low indoor unit
Between indoor unit and BC controllerh115[49](10[32]) or less
Between indoor unitsh215[49](10[32]) or less
*2
*2
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the
restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
1) To connect the P72 through P96 models of indoor units, use an optional twinning pipe kit (Model: CMY-R160-J) and merge
the two ports before connecting them.
2) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port.
3) Note the following when connecting multiple indoor units to a single port.
Those indoor units connected to the same port must be installed in the same room.
Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.
HWE1116DGB
- 47 -
[ II Restrictions ]
Restrictions on pipe length [PURY-P72, P96TKMU-A, PURY-P72, P96YKMU-A]
Pipe length between outdoor unit and BC controller (m[ft])
100 110
The height difference and the pipe length between BC controller and indoor units
70
[229]
60
[196]
50
[164]
40
[131]
30
[98]
20
[64]
Pipe length between main BC
10
controller and farthest indoor unit (m[ft])
[32]
0
051015
Height difference between main BC controller and farthest indoor unit (m[ft])
[16][32][49]
HWE1116DGB
- 48 -
[ II Restrictions ]
(2) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P144 model or
below.>
Outdoor unit
HH'
Reducer (P06 - P18 models)
(Supplied with the BC Controller)
h1
(P06 - P54 models)(P72 - P96 models)
Branch joint
(CMY-Y202-G2)
A
BC controller (main)
Junction pipe
a
(CMY-R160-J)
IndoorIndoorIndoorIndoor
b
(CMY-Y102L-G2)
(CMY-Y102S-G2)
C
Branch joint
(
CMY-Y102S-G2)
B
c
Maximum of 3 units per port
Total capacity of P54 or below
d
BC controller (sub)
D
BC controller (sub)
E
Indoor
e
Indoor
h1
h3
h2
h1
f
Unit: m [ft]
OperationPipe sectionsAllowable length of pipes
LengthTotal pipe lengthA+B+C+D+E+a+b+c+d+e+fRefer to the restrictions on the total pip-
ing length in the graphon the next page.
Total pipe length from the outdoor unit to the farthest indoor
A+C+E+f165 [541] or less
(Equivalent length 190 [623] or less)
unit
Between outdoor unit and BC
A110 [360] or less
controller
*1
Height
difference
Between BC controller and indoor unit
Outdoor unit
above in-
Between indoor
door unit
B+d or C+D+e
40 [131] or less
or C+E+f
H50 [164] or less
and outdoor
units
Outdoor unit
H'40 [131] or less
below indoor unit
Between indoor unit and BC
h115 [49](10[32]) or less
*2
controller
Between indoor unitsh215 [49](10[32]) or less
*2
Between the BC controller
(main or sub) and the sub BC
h315 [49] or less
controller
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the
restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
HWE1116DGB
- 49 -
[ II Restrictions ]
1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes
will be used between the main and the sub BC controllers.
2) When connecting two sub BC controllers, observe the maximum allowable length in the table above.
3) When connecting two sub BC controllers, install them in parallel.
4) To connect the P72 through P96 models of indoor units, use an optional twinning pipe kit (Model: CMY-R160-J) and merge
the two ports before connecting them.
5) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port.
6) Note the following when connecting multiple indoor units to a single port.
Those indoor units connected to the same port must be installed in the same room.
Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.
7) The maximum capacity of the indoor units that is connectable to the CMB-P-NU-GB types of sub BC controllers is P126 or
below (when two GB type controllers are connected P126 or below for both combined).
The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016NU-HB is P126 or below.
If at least one CMB-P1016NU-HB unit is connected, the maximum total capacity of connectable indoor units to a system with
two sub controllers is P168 or below.
Restrictions on pipe length [PURY-P120, P144TKMU-A, PURY-P120, P144Y(S)KMU-A]
Pipe length between outdoor unit and BC controller (m[ft])
100 110
The height difference and the pipe length between BC controller and indoor units
Pipe length between main BC
Height difference between main BC controller and farthest indoor unit (m[ft])
70
[229]
60
[196]
50
[164]
40
[131]
30
[98]
20
[64]
10
controller and farthest indoor unit (m[ft])
[32]
0
051015
[16][32][49]
HWE1116DGB
- 50 -
[ II Restrictions ]
(3) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P168 model or
above.>
Branch joint (CMY-R100VBK)
The distributor on the low-pressure side must be placed in the outdoor unit that has a larger capacity
2
index of the two, regardless of the relative positions of the outdoor units or their addresses.
If the distributor is placed in the outdoor unit that has a smaller capacity, refrigerant will not be properly
distributed and compressor failure may result.
(If outdoor units that have the same capacity are used in combination, the distributor can be placed in
either outdoor unit.)
Branch joint
(CMY-Y202-G2)
(CMY-Y102L-G2)
A
BC controller (main)
Junction pipe
a
(CMY-R160-J)
IndoorIndoorIndoorIndoor
b
C
B
(CMY-Y102S-G2)
Branch joint
(
CMY-Y102S-G2)
cd
Maximum of 3 units per port
Total capacity of P54 or below
BC controller (sub)
D
BC controller (sub)
E
Indoor
e
Indoor
h1
h3
h2
f
h1
h4
HH'
Outdoor unit
h1
1
Outdoor unit
F
Reducer (P06 - P18 models)
(Supplied with the BC Controller)
G
(P06 - P54 models)(P72 - P96 models)
Unit: m [ft]
OperationPipe sectionsAllowable length of pipes
LengthTotal pipe lengthF+G+A+B+C+D+E+a+b+c+d+e+fRefer to the restrictions on the total pip-
ing length in the graph on the next page.
Total pipe length from the outdoor unit to the farthest indoor
F(G)+A+C+E+f165 [541] or less
(Equivalent length 190 [623] or less)
unit
Between outdoor unit and BC
F(G)+A110 [360] or less
controller
Between BC controller and indoor unit
B+d or C+D+e
or C+E+f
40 [131] or less
*1
Between indoor unitsF+G5 [16] or less
Height
difference
Between indoor
Outdoor unit
above indoor unit
H50 [164] or less
and outdoor
units
Outdoor unit
H'40 [131] or less
below indoor unit
Between indoor unit and BC
h115 [49](10[32]) or less
*2
controller
Between indoor unitsh215 [49](10[32]) or less
*2
Between the BC controller
(main or sub) and the sub BC
h315 [49] or less
controller
Between outdoor unitsh40.1 [0.3] or less
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe
the restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
HWE1116DGB
- 51 -
[ II Restrictions ]
1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes
will be used between the main and the sub BC controllers.
2) When connecting two sub BC controllers, observe the maximum allowable length in the table above.
3) When connecting two sub BC controllers, install them in parallel.
4) To connect the P72 through P96 models of indoor units, use an optional twinning pipe kit (Model: CMY-R160-J) and merge
the two ports before connecting them.
5) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port.
6) Note the following when connecting multiple indoor units to a single port.
Those indoor units connected to the same port must be installed in the same room.
Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.
7) The maximum capacity of the indoor units that is connectable to the CMB-P-NU-GB types of sub BC controllers is P126 or
below (when two GB type controllers are connected P126 or below for both combined) .
The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016NU-HB is P126 or below.
If at least one CMB-P1016NU-HB unit is connected, the maximum total capacity of connectable indoor units to a system with
two sub controllers is P168 or below.
(3) Between the main and sub BC controllers (Section C)
Refrigerant pipe size (Brazed connection on all models )
Indoor unit
Liquid pipeHigh-pressure gas pipe Low-pressure gas pipe
- P72
ø9.52 [3/8"]
P73 - P108
P109 - P126
ø12.7 [1/2"]
P145 - P168ø15.88 [5/8"]
ø19.05 [3/4"]
[7/8"]
ø15.88 [5/8"]ø19.05 [3/4"]
ø19.05 [3/4"]
ø22.2 [7/8"]
Unit : mm [inch]
(Flare connection for all models)
ø19.05 [3/4"]
ø12.7 [1/2"]
ø22.2
[7/8"]
Unit : mm [inch]
ø22.2 [7/8"]
ø28.58 [1-1/8"]P127 - P144
Select the proper size pipes for the main unit based on the total capacity of the indoor units that are connected to both sub
BC controllers. Select the proper size pipes for the sub controller side based on the total capacity of the indoor units that are
connected to the sub controller.
HWE1116DGB
- 53 -
[ II Restrictions ]
2. Connecting the BC controller
(1) Size of the pipe that fits the standard BC controller ports
P72 - P120 models
Connection: Brazed connection
To outdoor unit
*1
Reducer
(Standard
supplied parts)
P18 model or below
P24 - P54 models P72 - P96 models
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units.
To connect other types of indoor units, follow the procedure below.
Maximum of 3 units per port
Total capacity of P54 or below
(All units connected to the same port
must be in the same operating mode.)
Unit : mm [inch]
Pipe sections
High-pressure side (gas)Low-pressure side (gas)
ø15.88 [5/8"]
(Brazed connection)
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
ø19.05 [3/4"]
(Brazed connection)
(Brazed connection)
ø28.58 [1-1/8"]
(Brazed connection)
ø15.88 [5/8"]
(Flare connection)
* BC controllers can only be connected to P72 - P120 models of outdoor units.
HWE1116DGB
- 54 -
[ II Restrictions ]
1) To connect P06 - P18 models of indoor units use
the reducer that is supplied with the BC controller.
2) To connect P72 - P96 models of indoor units (or when the
total capacity of indoor units exceeds P55), use a junction
pipe kit and merge the two nozzles.
50 [1-31/32"]
Liquid pipe side:3/8F
(Flare connection)
Gas pipe side:5/8F
Liquid pipe side: 6.35[1/4"]ID
Gas pipe side: 12.7[1/2"]ID
(Flare connection)
Liquid pipe side:3/8F
(Flare connection)
Gas pipe side:5/8F
(Flare connection)
234 [9-7/32"]
Liquid pipe side: 9.52[3/8”]ID
Gas pipe side: 19.05[3/4”]ID(*1)
Supplied with a thermal insulation cover
Note) Use the flare nut that is supplied with the BC controller.
3) To connect multiple indoor units to a port (or to a junction pipe)
Maximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below)
Maximum number of connectable indoor units: 3 units
Branch joint: Use CMY-Y102S-G2 (optional accessory).
Refrigerant pipe selection (size of the pipes A and B in the previous page) : Select the proper size pipes based
on the total capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor unitsLiquid pipeGas pipe
P54 or belowø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72ø9.52 [3/8"] ø19.05 [3/4"]
P73 - P96ø9.52 [3/8"] ø22.2 [7/8"]
Unit : mm [inch]
HWE1116DGB
- 55 -
[ II Restrictions ]
(2) Size of the pipe that fits the main BC controller ports
Maximum of 3 units per port
Total capacity of P54 or below
(All units connected to the same port
must be in the same operating mode.)
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor
units, follow the procedure below.
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.
2) To connect the P72 through P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use
an optional twinning pipe kit (Model: CMY-R160-J) to merge two ports before connecting them.
3) To connect multiple indoor units to a port (or to a junction pipe)
Maximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below)
Maximum number of connectable indoor units: 3 units
Branch joint: Use CMY-Y102S-G2 (optional accessory).
Refrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor unitsLiquid pipeGas pipe
P54 or belowø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72ø9.52 [3/8"] ø19.05 [3/4"]
P73 - P96ø9.52 [3/8"] ø22.2 [7/8"]
Operation
Pipe sections
High pressure side (Liquid)Low-pressure side (Gas)
Outdoor unit
side
PURY-P72TKMU-A
PURY-P72YKMU-A
ø15.88 [5/8"]
(Brazed connection)
PURY-P96TKMU-A
PURY-P96YKMU-A
PURY-P120TKMU-A
ø19.05 [3/4"]
(Brazed connection)
PURY-P120YKMU-A
PURY-P144TKMU-A
PURY-P144Y(S)KMU-A
PURY-P168TSKMU-A
PURY-P168YSKMU-A
ø22.2 [7/8"]
(Brazed connection)
PURY-P192TSKMU-A
PURY-P192YSKMU-A
PURY-P216TSKMU-A
PURY-P216YSKMU-A
PURY-P240TSKMU-A
PURY-P240YSKMU-A
PURY-P264TSKMU-A
ø28.58 [1-1/8"]
(Brazed connection)
PURY-P264YSKMU-A
PURY-P288TSKMU-A
PURY-P288YSKMU-A
Indoor unit sideø9.52 [3/8"] (Flare connection)ø15.88 [5/8"] (Flare connection)
Unit : mm [inch]
Unit : mm [inch]
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
(Brazed connection)
ø28.58 [1-1/8"]
(Brazed connection)
ø34.93 [1-3/8"]
(Brazed connection)
HWE1116DGB
- 56 -
[ II Restrictions ]
(3) Size of the pipe that fits the sub BC controller ports
Total capacity of P54 or below
(All units connected to the same port
must be in the same operating mode.)
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor
units, follow the procedure below.
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.
2) To connect the P72 through P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use
an optional twinning pipe kit (Model: CMY-R160-J) to merge two ports before connecting them.
3) To connect multiple indoor units to a port (or to a junction pipe)
Maximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below)
Maximum number of connectable indoor units: 3 units
Branch joint: Use CMY-Y102S-G2 (optional accessory).
Refrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor unitsLiquid pipeGas pipe
P54 or belowø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72ø9.52 [3/8"] ø19.05 [3/4"]
P73 - P96ø9.52 [3/8"] ø22.2 [7/8"]
OperationPipe sections
Total capacity of the indoor units that are connected to the BC
High-pressure side
(liquid)
Low-pressure side
(gas)
controller
On the BC controller
side
P72 model or below
P73 - P108
ø15.88 [5/8"]
(Brazed connection)
ø19.05 [3/4"]
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
(Brazed connection)
(Brazed connection)
P109 - P126
P127 - P144
P145 - P168
ø22.2 [7/8"]
(Brazed connection)
ø28.58 [1-1/8"]
(Brazed connection)
Unit : mm [inch]
Unit : mm [inch]
Liquid pipe side
ø9.52 [3/8"]
(Brazed connection)
ø12.7 [1/2"]
(Brazed connection)
ø15.88 [5/8"]
(Brazed connection)
HWE1116DGB
- 57 -
[ II Restrictions ]
HWE1116DGB
- 58 -
III
Outdoor Unit Components
[1] Outdoor Unit Components and Refrigerant Circuit .......................................................... 61
[2] Control Box of the Outdoor Unit....................................................................................... 65
[3] Outdoor Unit Circuit Board............................................................................................... 70
[4] BC Controller Components .............................................................................................. 81
[5] Control Box of the BC Controller...................................................................................... 84
[6] BC Controller Circuit Board.............................................................................................. 85
HWE1116DGB
- 59 -
HWE1116DGB
- 60 -
[ III Outdoor Unit Components ]
III Outdoor Unit Components
[1] Outdoor Unit Components and Refrigerant Circuit
1. Front view of a outdoor unit
(1) PURY-P72, P96TKMU-A
PURY-P72, P96YKMU-A
Fin guardFin guard
Fan guardFan guard
FanFan
Control boxControl box
Transformer box
Transformer box
(YKMU-A only)
(YKMU-A only)
Heat exchangerHeat exchanger
Side panelsSide panels
HWE1116DGB
Front panelsFront panels
- 61 -
[ III Outdoor Unit Components ]
Fan guards
Fans
Control box
Fan box
Heat exchanger
Transformer box
(YKMU-A only)
Front panels
Fin guard
Side panel
Side panel
(2) PURY-P120, P144TKMU-A
PURY-P120, P144YKMU-A
Fin guard
Fan guards
Fans
Side panel
Control box
Fan box
Side panel
Heat exchanger
Transformer box
(YKMU-A only)
Front panels
HWE1116DGB
- 62 -
[ III Outdoor Unit Components ]
2. Refrigerant circuit
(1) PURY-P72, P96TKMU-A
PURY-P72, P96YKMU-A
Solenoid valve (SV9)
4-way valve (21S4a)
Check valve
(CV7a)
Low-pressure sensor
(63LS)
High-pressure switch
(63H1)
High-pressure sensor (63HS1)
Transformer box
Transformer box
(YKMU-A only)
(YKMU-A only)
Check valve
(CV5a)
Solenoid valve
(SV5b)
Solenoid valve block
(SV4d, SV4b, SV4a)
Refrigerant service
valve on the low
pressure side
Refrigerant service
valve on the high
pressure side
Accumulator
Compressor
cover
Solenoid valve
(SV1a)
Compressor
Oil separator
High-pressure check joint
Low-pressure check joint
Linear expansion
valve (LEV5a)
Check valve
(CV3a)
Check valve
(CV9a)
Check valve
(CV2a)
HWE1116DGB
Check valve
(CV6a)
Check valve
(CV4a)
Check valve
(CV8a)
- 63 -
[ III Outdoor Unit Components ]
(2) PURY-P120, P144TKMU-A
PURY-P120, P144YKMU-A
Check valve
(CV7a)
4-way valve
(21S4a)
4-way valve
(21S4b)
Bidirectional
solenoid
valve (SV4c)
Check valve
(CV7b)
Check valve
(CV6b)
Check valve
(CV4b)
Solenoid valve (SV9)
Solenoid valve block
(SV4d, SV4b, SV4a)
Low-pressure
sensor
(63LS)
High-pressure switch
(63H1)
High-pressure
sensor
(63HS1)
Low-pressure check joint
High-pressure check joint
Compressor cover
Check valve (CV5a)
Check valve
(CV5b)
Check valve
(CV3a)
Check valve
(CV2b)
Check valve
(CV2a)
Linear expansion
valve (LEV5a)
Refrigerant service valve
on the low pressure side
Refrigerant service
valve on the high
pressure side
Oil separator
Compressor
Solenoid valve (SV1a)
Solenoid valve (SV5b)
Accumulator
Linear expansion
valve (LEV5b)
Check valve
(CV6a)
Check valve
(CV4a)
Check valve
(CV8a)
The YKMU model has a transformer box.
HWE1116DGB
- 64 -
[ III Outdoor Unit Components ]
FAN INV board
M-NET board
INV board
Noise filter
(R1) Note 2
DC reactor
(DCL)
[2] Control Box of the Outdoor Unit
<HIGH VOLTAGE WARNING>
Control box houses high-voltage parts.
When opening or closing the front panel of the control box, do not let it come into contact with any of
the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes,
and check that the the voltage of the electrolytic capacitor (Inverter main circuit) is 20VDC or below.
(It takes about 10 minutes to discharge electricity after the power supply is turned off.)
1. PURY-P72TKMU-A
Rush current
protection resistor
Electromagnetic
relay (72C)
Control board
Terminal block
for power supply
(TB1)
Note 1
Ground terminal
Terminal block for
transmission line
(TB3, TB7)
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the waterproof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
3) Control box houses high temperature parts. Be well careful even after turning off the power source.
4) Perform the service after disconnecting the fan board connector (CNINV) and the inverter board connector (CN1 or
CNFAN). To plug or unplugconnectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when the
outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
5) To connect wiring to TB7, check that the voltage is 20 VDC or below.
6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1 or CNFAN) back to the inverter
board after servicing.
7) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
8) When the power is turned on, the compressor is energized even while it is not operating. Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor.
Check the compressor for a graound fault. If the insulation resistance is 1.0 M or below, connect all power supply wires to
the compressor and turn on the power to the outdoor unit. The liquid refrigerant in the compressor will evaporate by energizing
the compressor.
HWE1116DGB
- 65 -
[ III Outdoor Unit Components ]
FAN INV board
Control board
M-NET board
IPM
Note 2
Noise filter
Rush current
protection resistor
(R1) Note 2
DC reactor
(DCL)
INV board
Current sensor
(ACCT1)
Current sensor
(DCCT1)
Current sensor
(ACCT2)
Diode stack
Electromagnetic
contactor (72C)
2. PURY-P96, P120, P144TKMU-A
Terminal block
for power supply
(TB1)
Ground
terminal
Note 1
Smoothing
capacitor (C1)
Terminal block for
transmission line
(TB3, TB7)
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the waterproof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
3) Control box houses high temperature parts. Be well careful even after turning off the power source.
4) Perform the service after disconnecting the fan board connector (CNINV) and the inverter board connector (CN1 or
CNFAN). To plug or unplugconnectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when the
outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
5) To connect wiring to TB7, check that the voltage is 20 VDC or below.
6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1 or CNFAN) back to the inverter
board after servicing.
7) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
8) When the power is turned on, the compressor is energized even while it is not operating. Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor.
Check the compressor for a graound fault. If the insulation resistance is 1.0 M or below, connect all power supply wires to
the compressor and turn on the power to the outdoor unit. The liquid refrigerant in the compressor will evaporate by energizing
the compressor.
HWE1116DGB
- 66 -
[ III Outdoor Unit Components ]
INV board
Noise filter
DC reactor
(DCL)
(72C)
Capacitor
(C100)
3. PURY-P72, P96, P120, P144YKMU-A
Electromagnetic relay
Note 2
Terminal block
for power supply
(TB1)
Fuse (F4)
Fuse (F5)
Ground terminal
Rush current protection resistor
(R1, R5) Note 2
FAN INV board
Note 1
Control board
M-NET board
Terminal block for transmission line
(TB3, TB7)
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the waterproof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
3) Control box houses high temperature parts. Be well careful even after turning off the power source.
4) Perform the service after disconnecting the fan board connector (CNINV) and the inverter board connector (CN1 or
CNFAN). To plug or unplugconnectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when the
outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
5) To connect wiring to TB7, check that the voltage is 20VDC or below.
6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1 or CNFAN) back to the inverter
board after servicing.
7) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 V DC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
8) When the power is turned on, the compressor is energized even while it is not operating. Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor.
Check the compressor for a graound fault. If the insulation resistance is 1.0 M or below, connect all power supply wires to
the compressor and turn on the power to the outdoor unit. The liquid refrigerant in the compressor will evaporate by energizing
the compressor.
1) Handle the fan box with care. If the front or the bottom panel becomes damaged, water or dust may enter the fan box, damaging its internal parts.
2) Perform the service after disconnecting the fan board connector (CNINV) and the connect board connector (CN103).
To plug or unplugconnectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the
main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when the outdoor
unit fan rotates in windy conditions.
3) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN103) back to the connect board
after servicing.
HWE1116DGB
- 69 -
[ III Outdoor Unit Components ]
(208/230 VAC)
[3] Outdoor Unit Circuit Board
1. Outdoor unit control board
For information about the display of SW4 function settings, refer to sectionVII [1] Functions and Factory Settings of the
Dipswitches(page 137)
HWE1116DGB
- 70 -
[ III Outdoor Unit Components ]
2. M-NET board
Grounding
CN04
Bus voltage input
P
N
CN102
Power supply output for centralized
control system (30VDC)
Indoor/outdoor transmission line
input/output (30VDC)
Grounding
Grounding
TB3
Indoor/outdoor transmission block
Ground terminal for
transmission line
CNS2
Transmission line
input/output for
centralized control
system (30VDC)
TB7
Terminal block for
centralized control
transmission line
CNIT
12VDC Input
GND
5VDC Input
Power supply
detection output
Power supply
ON/OFF signal input
LED1
Power supply for
indoor
transmission line
TP1,2
Check pins for
indoor/outdoor
transmission line
HWE1116DGB
- 71 -
[ III Outdoor Unit Components ]
3. INV board
(1) PURY-P72TKMU-A
F001
Fuse
250 VAC 3.15A
SC-P1
Diode rectifier
output (P)
CNVDC
Bus voltage output
P
P
N
N
CNFAN
Bus voltage output
N
P
LED4
Lit during normal
CPU operation
LED1
Inverter in normal operation (Lit)
/Error (blinking)
CN2
Serial signal output
GND
17VDC input
17VDC output
CN4
GND (FAN INV board)
Serial communication signal input
IGBT
Back
SC-P2
Bus voltage input (P)
C011 - C016
Smoothing capacitor
SC-T
Input (L3)
TB-P (Note 1)
Bus voltage
check terminal (P)
TB-N (Note 1)
Bus voltage
check terminal (N)
SC-S
Input (L2)
SC-R
Input (L1)
CT11
Current sensor (U)
CT12
Current sensor (W)
SW001
ON: No-load
operation
setting
OFF: Normal
operation
setting
Set to OFF
PSH01 - 03
Overcurrent
detection
resistor
SC-V
Inverter output (V)
SC-W
Inverter output (W)
SC-U
Inverter output (U)
1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the electrolytic capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge
electricity after the power supply is turned off.
2) Control box houses high temperature parts. Be well careful even after turning off the power source.
3) Perform the service after disconnecting the fan board connector (CNINV) and the inverter board connector (CN1 or
CNFAN). To plug or unplug connectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when the
outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
4) To connect wiring to TB7, check that the voltage is 20 VDC or below.
5) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1 or CNFAN) back to the inverter
board after servicing.
6) When the power is turned on, the compressor is energized even while it is not operating. Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor.
Check the compressor for a ground fault. If the insulation resistance is 1.0 M or below, connect all power supply wires to the
compressor and turn on the power to the outdoor unit. The liquid refrigerant in the compressor will evaporate by energizing
the compressor.
HWE1116DGB
- 72 -
[ III Outdoor Unit Components ]
(2) PURY-P96, P120, P144TKMU-A
1) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
2) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
3) Control box houses high temperature parts. Be well careful even after turning off the power source.
4) Perform the service after disconnecting the fan board connector (CNINV) and the inverter board connector (CN1 or
CNFAN). To plug or unplug connectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when the
outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
5) To connect wiring to TB7, check that the voltage is 20 VDC or below.
6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1 or CNFAN) back to the inverter
board after servicing.
7) When the power is turned on, the compressor is energized even while it is not operating. Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor.
Check the compressor for a ground fault. If the insulation resistance is 1.0 M or below, connect all power supply wires to the
compressor and turn on the power to the outdoor unit. The liquid refrigerant in the compressor will evaporate by energizing
the compressor.
HWE1116DGB
- 73 -
[ III Outdoor Unit Components ]
(3) PURY-P72, P96, P120, P144YKMU-A
1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
3) Control box houses high temperature parts. Be well careful even after turning off the power source.
4) Perform the service after disconnecting the fan board connector (CNINV) and the inverter board connector (CN1 or
CNFAN). To plug or unplugb connectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when
the outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
5) To connect wiring to TB7, check that the voltage is 20 VDC or below.
6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1 or CNFAN) back to the inverter
board after servicing.
7) When the power is turned on, the compressor is energized even while it is not operating. Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor.
Check the compressor for a ground fault. If the insulation resistance is 1.0 M or below, connect all power supply wires to the
compressor and turn on the power to the outdoor unit. The liquid refrigerant in the compressor will evaporate by energizing
the compressor.
HWE1116DGB
- 74 -
[ III Outdoor Unit Components ]
4. Fan board
(1) PURY-P72, P96, P120, P144TKMU-A
1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
2) Control box houses high temperature parts. Be well careful even after turning off the power source.
3) Perform the service after disconnecting the fan board connector (CNINV) and the inverter board connector (CN1 or
CNFAN). To plug or unplugconnectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when the
outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
4) To connect wiring to TB7, check that the voltage is 20 VDC or below.
5) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1 or CNFAN) back to the inverter
board after servicing.
HWE1116DGB
- 75 -
[ III Outdoor Unit Components ]
(2) PURY-P72, P96, P120, P144YKMU-A
1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
2) Control box houses high temperature parts. Be well careful even after turning off the power source.
3) Perform the service after disconnecting the fan board connector (CNINV) and the inverter board connector (CN1 or
CNFAN). To plug or unplugconnectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when the
outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
4) To connect wiring to TB7, check that the voltage is 20 VDC or below.
5) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1 or CNFAN) back to the inverter
board after servicing.
HWE1116DGB
- 76 -
[ III Outdoor Unit Components ]
Ground
Ground
TB32
Bus voltage input (P)
CN110
Power supply detection
signal output
CN012
Output
CN001
Input
CNR1
Rush current
protection
resistor (R1)
connection
TB21
Input/output (L1)
TB22
Input/output (L2)
TB23
Input/output (L3)
F002
Fuse
250 VAC 6.3A T
F001
Fuse
250 VAC 6.3A T
TB31
Bus voltage output (P)
X001
Electromagnetic
relay (72C)
CN72C
72C drive signal input
L3
L2
L1
L2
L1
5. Noise Filter
(1) PURY-P72TKMU-A
HWE1116DGB
- 77 -
[ III Outdoor Unit Components ]
(2) PURY-P96, P120, P144TKMU-A
CNR1
Rush current
protection registor
(R1) connection
CN012
Output
L1
L2
Ground
F001
Fuse
250 VAC 6.3A T
CN110
Power supply detection
signal output
Ground
F003
Fuse
250 VAC 6.3A T
TB31
Bus voltage output (P)
CN72C
72C drive input
X001
Electromagnetic relay
(72C)
TB42
Bus voltage output (N)
Diode stack
Rectifier voltage input
(Diode stack output)
Output
(Diode stack input)
F002
Fuse
250 VAC 6.3A T
CN001
Input
L3
L2
L1
TB21
Input (L1)
TB22
Input (L2)
TB23
Input (L3)
HWE1116DGB
- 78 -
[ III Outdoor Unit Components ]
(3) PURY-P72, P96, P120, P144YKMU-A
CN4
Output
(Rectified L2-L3 current)
P
N
CN2
Surge absorber circuit
Surge absorber circuit
Short circuit
Short circuit
F1,F2,F3,F4
Fuse
250VAC 6.3A
Grounding
CN1A
Input
L1
CN5
Output
(Rectified L2-L3 current)
P
N
CN6
Input
L2
L3
Grounding
CN1B
Input
L3
L2
HWE1116DGB
TB21
Input/output(L1)
TB22
Input/output(L2)
- 79 -
TB23
Input/output(L3)
[ III Outdoor Unit Components ]
6. Connect board
1
1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
2) Control box houses high temperature parts. Be well careful even after turning off the power source.
3) Perform the service after disconnecting the fan board connector (CNINV) and the connector board connector
(CN103). To plug or unplugconnectors, check that the outdoor unit fan is not rotating and that the voltage of capacitor in the main circuit is 20 VDC or below. The capacitor may collect a charge and cause an electric shock when the
outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.
4) To connect wiring to TB7, check that the voltage is 20 VDC or below.
5) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN103) back to the connector board
after servicing.
HWE1116DGB
- 80 -
[ III Outdoor Unit Components ]
[4] BC Controller Components
1. CMB-P NU-G, GA, HA
(1) Front
(2) Rear view <G type>
Liquid pipe (Indoor unit side)
Gas pipe (Indoor unit side)
Gas/Liquid separator
Tube in tube heat exchanger
TH12
PS1
TH11
SVM1
LEV3
LEV1
PS3
TH16
TH15
HWE1116DGB
- 81 -
[ III Outdoor Unit Components ]
(3) Rear view <GA type>
Gas/Liquid separator
Tube in tube heat exchanger
(4) Rear view <HA type>
TH11
TH12
LEV2
TH16
PS3
TH15
PS1
LEV3
LEV1
SVM2
SVM1
PS3
Tube in tube
heat exchanger
Gas/Liquid separator
TH12
TH11
PS1
TH15
LEV3
LEV1
LEV2
SVM2
SVM2b
SVM1b
SVM1
TH16
HWE1116DGB
- 82 -
[ III Outdoor Unit Components ]
2. CMB-P NU-GB, HB
(1) Front
(2) Rear view
Liquid pipe (Indoor unit side)
Gas pipe (Indoor unit side)
TH12
LEV3
TH15
HWE1116DGB
- 83 -
[ III Outdoor Unit Components ]
[5] Control Box of the BC Controller
1. CMB-P1016NU-G, GA, HA
Transformer
Terminal block for
power supply
Terminal block for
transmission line
Relay board
BC controller board
HWE1116DGB
- 84 -
[ III Outdoor Unit Components ]
[6] BC Controller Circuit Board
1. BC controller circuit board (BC board)
SW4
HWE1116DGB
SW5
SW6
SW1SW2
- 85 -
[ III Outdoor Unit Components ]
2. RELAY BOARD (RELAY 4 board)
3. RELAY BOARD (RELAY 10 board)
HWE1116DGB
- 86 -
IV
Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers ................................... 89
[2] Group Settings and Interlock Settings via the ME Remote Controller .............................90
[3] Interlock Settings via the MA Remote Controller ............................................................. 94
[4] Using the built-in Temperature Sensor on the Remote Controller ...................................95
HWE1116DGB
- 87 -
HWE1116DGB
- 88 -
[ IV Remote Controller ]
IV Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers
There are two types of remote controllers: ME remote controller, which is connected on the indoor-outdoor transmission
line, and MA remote controller, which is connected to each indoor unit.
1. Comparison of functions and specifications between MA and ME remote controllers
Functions/specificationsMA remote controller
*1*2
ME remote controller
*2*3
Remote controller address settings Not requiredRequired
Indoor/outdoor unit address settings
Wiring methodNon-polarized 2-core cable
Not required (required only by a system
with one outdoor unit)
*4
Required
Non-polarized 2-core cable
To perform a group operation, daisy-
chain the indoor units using non-polarized 2-core cables.
Remote controller connectionConnectable to any indoor unit in the
group
Interlock with the ventilation unitEach indoor unit can individually be in-
terlocked with a ventilation unit. (Set up
via remote controller in the group.)
Changes to be made upon grouping change
MA remote controller wiring between indoor units requires rewiring.
Connectable anywhere on the indoor-outdoor transmission line
Each indoor unit can individually be interlocked with a ventilation unit. (Set up via
remote controller.)
Either the indoor unit address and remote
controller address must both be changed,
or the registration information must be
changed via MELANS.
*1. MA remote controller refers to MA remote controller (PAR-20MAU, PAR-21MAAU, PAR-30MAAU), Simple MA Remote
Controller, and wireless remote controller.
*2. Either the MA remote controller or the ME remote controller can be connected when a group operation of units in a sys-
tem with multiple outdoor units is conducted or when a system controller is connected.
*3. ME remote controller refers to ME remote controller and Simple ME Remote Controller.
*4. Depending on the system configuration, some systems with one outdoor unit may require address settings.
2. Remote controller selection criteria
MA remote controller and ME remote controller have different functions and characteristics. Choose the one that better suits
the requirements of a given system. Use the following criteria as a reference.
MA remote controller
*1*2
There is little likelihood of system expansion and group-
ing changes.
Grouping (floor plan) has been set at the time of instal-
lation.
ME remote controller
There is a likelihood of centralized installation of remote
controllers, system expansion, and grouping changes.
Grouping (floor plan) has not been set at the time of in-
stallation.
*1*2
To connect the remote controller directly to the OA pro-
cessing unit.
*1. ME remote controller and MA remote controller cannot both be connected to the same group of indoor units.
*2. A system controller must be connected to a system to which both MA remote controller and ME remote controller are con-
nected.
<System with MA remote controller><System with ME remote controllers>
Outdoor unit
M-NET transmission line
(indoor/outdoor transmission line)
groupgroup
Outdoor unit
M-NET transmission line
(indoor/outdoor transmission line)
groupgroup
BC
controller
MA remote controller
HWE1116DGB
Indoor unit
- 89 -
BC
controller
ME remote controller
Indoor unit
[ IV Remote Controller ]
[2] Group Settings and Interlock Settings via the ME Remote Controller
1. Group settings/interlock settings
Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the
indoor/outdoor unit address.
(A) Group settings...........Registration of the indoor units to be controlled with the remote controller,
and search and deletion of registered information.
(B) Interlock settings........Registration of LOSSNAY units to be interlocked with the indoor units,
and search and deletion of registered information
[Operation Procedures]
(1) Address settings
Register the indoor unit to be controlled with the remote controller.
1
Bring up either one of the following displays on the remote controller:
The blinking display of HO, which appears when the power is turned on, or the
normal display, which appears when the unit is stopped. The display window must
look like one of the two figures below to proceed to the next step.
C
G
E
MODE TIMER
PAR-F27MEA-US
SET TEMP.
TIMER SET
CLOCKONOFF
FAN SPEED
LOUVER
ON/OFF
AIR DIRECTION
VENTILATION
FILTER
CHECK
F
?
A
TEST
D
[Blinking display of HO ]
Bring up the Group Setting window.
2
-Press and hold buttons [FILTER] and [LOUVER]
simultaneously for 2 seconds to bring up the display as
A
B
[Normal display]
shown below.
Indoor unit address display window
3
Select the unit address.
-
Select the address of the indoor unit to be registered by pressing
button
through the addresses.
4
Register the indoor unit whose address appears on the
C
[SET TEMP. ( ) or ( )] to advance or go back
display.
- Press button [TEST] to register the indoor unit address
D
whose address appears on the display.
- If registration is successfully completed, unit type will appear
on the display as shown in the figure below.
- If the selected address does not have a corresponding indoor
unit, an error message will appear on the display. Check the
address, and try again.
<Successful completion of registration>
Unit type (Indoor unit in this case)
<Deletion error>
H
B
(B) Interlock Settings (A) Group Settings
6
Bring up the Interlock Setting window.
-Press button [MODE] to bring up the following display.
G
Press again to go back to the Group Setting window as shown
under step .
Indoor unit
address
display window
7
Bring up the address of the indoor unit and the address of the
2
Interlocked unit
address
display window
Both the indoor unit address and
interlocked unit address will be
displayed together.
To search for an address,
go to section (2) Address Search.
LOSSNAY to be interlocked on the display.
- Select the address of the indoor unit to be registered by pressing
C
button [SET TEMP. ( ) or ( )] to advance or go back through
the addresses.
- Select the address of the LOSSNAY unit to be interlocked by
pressing button [TIMER SET ( ) or ( )] to advance or go back
H
through the interlocked unit addresses.
8
Make the settings to interlock LOSSNAY units with indoor
units.
- Press button [TEST] while both the indoor unit address and
D
the address of the LOSSNAY units to be interlocked
are displayed to enter the interlock setting.
- Interlock setting can also be made by bringing up the
LOSSNAY address in the indoor unit address display
window and the indoor unit address in the interlocked unit
address display window.
blinks to indicate a registration error.
(Indicates that selected address does not have a
corresponding unit.)
5
To register the addresses for multiple indoor units, repeat
steps and above.
3
4
To search for an address,
go to section (2) Address Search.
Next page.
HWE1116DGB
If registration is successfully
completed, the two displays as
shown on the left will appear
alternately.
(Displayed alternately)
If the registration fails,
will blink on the display.
(Indicates that the selected
address does not have a
corresponding unit.)
NOTE : Interlock all the indoor units in the group with the
LOSSNAY units; otherwise, the LOSSNAY units will
not operate.
- 90 -
[ IV Remote Controller ]
(C) To return to the normal display
When all the group settings and interlock settings are made, take the
following step to go back to the normal display.
10
Press and hold buttons [FILTER] and [LOUVER]
A
B
simultaneously for 2 seconds to go back to the
window as shown in step .
1
(2) Address search
To search for the address of indoor units that have been entered into
the remote controller, follow steps and .
1
2
(A) To search group settings
11
Bring up the Group Setting window.
- Each pressing of button [TIMER ] will bring up the address of a
E
registered indoor unit and its unit type on the display.
<Entry found>
Unit type
(Indoor unit in this case)
<No entries found>
- When only one unit address is registered, the same address
will remain on the display regardless of how many times the
button is pressed.
- When the address of multiple units are registered
(i.e. 011, 012, 013 ), they will be displayed one at a time in
an ascending order with each pressing of button [TIMER ] .
E
Repeat steps and in the previous page to interlock
9
all the indoor units in a group with the LOSSNAY unit.
To go back to the normal display,
follow step
7
8
To search for an address,
10
go to section (2) Address Search.
(B) Interlock setting search
After performing step , proceed as follows:
12
Bring up the address of the indoor unit to be searched on
6
the display.
- Select the address of the indoor unit to be searched by pressing
H
button [TIMER SET ( ) or ( )] to advance or go back
through the interlocked addresses.
LOSSNAY can be searched in the same manner by bringing up
the LOSSNAY address in the Interlocked unit address display window.
13
Bring up on the display the address of the LOSSNAY unit
that was interlocked with the indoor unit in step .
- With each pressing of button [TIMER], the address of the
E
LOSSNAY and indoor unit that is interlocked with it will be
displayed alternately.
Address of an interlocked
LOSSNAY unit
(Displayed alternately)
12
14
To delete an address, go to
section (3) Address Deletion.
Bring up the address of another registered unit on the
display.
- After completing step , a subsequent pressing of button
E
[TIMER] will bring up the address of another registered
13
unit.
(The display method is the same as the one in step .)
To go back to the normal display,
follow step
10
Address of another
interlocked unit
(Displayed alternately)
To delete an address,
(3) Address deletion
go to section (3) Address Deletion .
The addresses of the indoor units that have been entered into the remote controller can be deleted by deleting the group settings.
The interlock settings between units can be deleted by deleting the interlock settings.
Follow the steps in section (2) Address Search to find the address to be deleted and perform deletion with the address being displayed in the
display window. To delete an address, the address must first be bought up on the display.
15
Delete the registered indoor unit address or the interlock setting between units.
- Press button ? [CLOCK ON OFF] twice while either the indoor unit address or the address of the interlocked unit is displayed on the
F
display to delete the interlock setting.
13
HWE1116DGB
- 91 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.