Outdoor Unit: 16-TON PURY-P192YSKMU-A (-BS)
(Consists of Two PURY-P96YKMU-A (-BS) and One CMY-R100CBK2 Twinning Kit)
Job Name:
Schedule Reference: Date:
OUTDOOR VRF HEAT PUMP WITH HEAT RECOVERY
SYSTEM FEATURES
• INVERTER-driven compressor
• Air-source, simultaneous cooling and heating
• Long line lengths - for details see Engineering Manual
• Connects to CITY MULTI indoor units
• Controlled via CITY MULTI Controls Network
UNIT OPTION
□ Standard Model……..….........…...………….PURY-P192YSKMU-A
□ Sea Coast (BS) Model………....……….PURY-P192YSKMU-A-BS
OPTIONAL PARTS
□ Twinning Kit (required)..............................................…CMY-R100CBK2
□ Joint Kit.............................…for details see Pipe Accesories Submittal
□ Joint Adapter Kit................…for details see Pipe Accesories Submittal
□ Low Ambient Kit ....... ... .....…..for details see Low Ambient Kit Submittal
□ Snow/Hail Guards K it.... ..…for details see Snow/Hail Guards Kit Submittal
Specications System Module 1 Module 2
Unit Type PURY-P192YSKMU-A (-BS) PURY-P96YKMU-A (-BS) PURY-P96YKMU-A (-BS)
Nominal Cooling Capacity (460V) Btu/h 192,000 96,000 96,000
Nominal Heating Capacity (460V) Btu/h 215,000 108,000 108,000
Operating Temperature Range *1
External Dimensions (H x W x D)
Net Weight Lbs. / kg 1,148 (520) 574 (260) 574 (260)
External Finish
Electrical Power Requirements Voltage, Phase, Hertz Refer to Module Data** 460V, 3-Phase, 60Hz
Minimum Circuit Ampacity (MCA) A Refer to Module Data** 15 15
Maximum Fuse Size A Refer to Module Data** 20 20
Piping Diameter
F r o m T w i n n i n g K i t t o I n d o o r U n i t s
(Brazed) (In. / mm)
Max. Total Refrigerant Line Length Ft. 2,461
Max. Refrigerant Line Length
(Between ODU & IDU)
Max. Control Wiring Length Ft. 1,650
Indoor Unit
Sound Pressure Level dB(A) 61 Refer to System Data
Fan
Type x Quantity
Airow Rate CFM 6,200 6,200
External Static Pressure In. WG (Pa) Refer to Module Data Selectable; 0, 0.12 or 0.24”WG; factory set to 0”W.G.
Compressor Operating Range 8% to 100% Refer to System Data
Compressor Type x Quantity Refer to Module Data
Refrigerant Refer to Module Data
Protection Devices
AHRI Ratings
(Ducted/Non-Ducted)
Simultaneous Rating
(Ducted/Non-Ducted)
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants
Standard: ≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.
Sea Coast (BS): ≥1μm thick; Salt Spray Test Method - no unusual rust development to 960 hours.
Cooling (Outdoor) *2
Heating (Outdoor) -4~60° F (-20~15.5° C) WB
In.
mm
Liquid (High Pressure) 7/8 (22.2) Brazed
Gas (Low Pressure) 1-1/8 (28.58) Brazed
Ft. 541
Total Capacity 50~150% of ODUs Refer to System Data
Model / Quantity P06~P96/1~48 Refer to System Data
High Pressure
Inverter Circuit
(Comp. / Fan)
Fan Motor Thermal switch Thermal switch
EER 11.6 / 11.9
COP 3.64 / 3.47
SCHE *3 17.40 / 21.81 Refer to System Data
Refer to Module Data
Refer to Module Data
Refer to Module Data Pre-coated galvanized steel sheet
Refer to Module Data
Refer to Module Data
64-31/32 x 48-1/16 x 29-5/32
1,650 x 1,220 x 740
Propeller fan x 1 Propeller fan x 1
Inverter-driven Scroll
Hermetic x 1
R410A x 26 lbs + 1 oz
High pressure sensor, High
pressure switch at 4.15 MPa
Over-current protection Over-current protection
23~115° F (-5~46° C) DB
Refer to System Data
Refer to System Data
(11.8 kg)
(601 psi)
Refer to System DataIEER 19.3 / 18.2
64-31/32 x 48-1/16 x 29-5/32
1,650 x 1,220 x 740
Inverter-driven Scroll
Hermetic x 1
R410A x 26 lbs + 1 oz
(11.8 kg)
High pressure sensor, High
pressure switch at 4.15 MPa
(601 psi)
NOTES:
*1. Harsh weather environments may demand performance enhancing equipment.
Ask your Mitsubishi Electric representative for more details about your region.
*2. For details on extended cooling operation range down to -10° F DB, see Low Ambient Kit Submittal.
Specications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
*3. Simultaneous Cooling and Heating Efciency
** Each individual module requires a separate electrical connection.
Refer to electrical data for each individual module.

Outdoor Unit: PURY-P192YSKMU-A (-BS) – DIMENSIONS
PURY-P144,168,192YSKMU-A(-BS)
Unit : mm(in.)
Outdoor unit 2Outdoor unit 1
Intake
air
To BC controller
To BC controller
a
b
Twinning pipe(High pressure)
<optional parts>
e
96
P192
P9
P72P72P72
P168P144
P96
ø22.2(7/8)
fd
ec
(Note 5)
-
ø19.05(3/4)
ø19.05(3/4)ø19.05(3/4)
ø15.88(5/8)ø15.88(5/8)ø15.88(5/8) ø19.05(3/4)
ffdd
eecc
(Note 5)(Note 5)
--
ø19.05(3/4)
f
30(1-3/16)
1220(48-1/16) 1220(48-1/16)
Twinning pipe(Low pressure)
<optional parts>
d
Intake
air
1650(64-31/32)
c
Front view
Component
unit model
Unit model
CMY-R100CBK2
High pressure
Low pressure
Twinning Kit
~Outdoor unit
ø22.2(7/8)
ø28.58(1-1/8)
Discharge air
740(29-5/32)
Specications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
PURY-P144YSKMU-A(-BS) PURY-P168YSKMU-A(-BS) PURY-P192YSKMU-A(-BS)
PURY-P72YKMU-A(-BS) PURY-P96YKMU-A(-BS) PURY-P96YKMU-A(-BS)
PURY-P72YKMU-A(-BS) PURY-P72YKMU-A(-BS) PURY-P96YKMU-A(-BS)
b
a
Low pressure
Left view
Package unit name
Intake
air
Twinning pipe connection size
High pressure
Outdoor unit 1
Outdoor unit 2
Outdoor Twinning Kit(optional parts)
BC controller~Twinning pipe
Component unit name
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Be sure to see the Installation Manual for details of Twinning pipe installation.
5.Connect the outdoor unit 1 with the Twinning pipe (Low pressure) (section "d" in the figure).
3.The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm(19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).

Model: PURY-P96YKMU-A (-BS) – DIMENSIONS
PURY-P72,96YKMU-A(-BS)
Unit : mm(in.)
(1)
(1)
ø25.4
ø25.4
Low
pressure
Service valveRefrigerant pipe
High
pressure
(1)
ø25.4
(3-1/16)(5-17/32)
Specifications
(1)
ø25.4
140 × 77 Knockout hole
150 × 94 Knockout hole
ø45 Knockout hole
(1-25/32)
(7/8)
(1-3/8)
(3-23/32)(5-29/32)
ø65 Knockout hole
ø62.7 or ø34.5 Knockout hole
(2-15/32)
ø52 Knockout hole
ø43.7 or ø22.2 Knockout hole
(1-3/4)
(2-1/16)
(2-9/16)
ø34 Knockout hole
(1-11/32)
Note 1.Please refer to the engineering manual for information
regarding necessary spacing around the unit and
foundation work. Outdoor unit must be mounted
at least 12" off the ground or 12" above the highest
average snow depth, whichever is greater.
2.At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120°C(248°F).
Connecting pipe specifications
740(29-5/32)
19.5
1181(46-1/2)
19.5
150(5-29/32)
600
70
(23-5/8)
(2-25/32)
Diameter
Low
High
Model
(25/32)
Top view
1220(48-1/16)
(25/32)
*1
pressure
(3/4)
ø19.05 Brazed
*1
pressure
(5/8)
ø15.88 Brazed
PURY-P72YKMU
(11-15/16)
303
Control box
*1
(7/8)
ø22.2 Brazed
*1
(3/4)
ø19.05 Brazed
PURY-P96YKMU
*1 Use the pipe joint(field supply) and connect to the refrigerant service valve piping.
Intake
air
Intake
air
1650(64-31/32)
1347(53-1/16)
Service
panel
Transformer box
Front through hole
Front through hole
(Uses when twinning
Usage
For pipes
1
NO.
1
8
5
4
2
2
77
89
75(2-31/32)
236
(9-5/16)
145
217
Front through hole
Bottom through hole
kit (optional
parts) is mounted.)
<Sling hole>
2X2-80(3-5/32)X35(1-13/32) Oval hole
(3-17/32) (3-1/16)
58(2-5/16)
140(5-17/32)
272
251
(9-29/32)
(5-23/32)
(8-9/16)
Front through hole
For wires
4
5
3
2X2-14(9/16)X20(13/16) Oval hole
Front view
83(3-9/32)301
150(5-29/32)
272
227
(8-15/16)
(10-23/32)
(10-23/32)
(11-7/8)
Bottom through hole
Bottom through hole
6
7
(1-3/16)
29.5
(3-5/16)
(5-3/4)
146
(4-25/32)
121
(5-3/4)
146
(7-23/32)
196
Front through hole
For transmission cables
8
(740)(29-5/32)
(Mounting pitch)
681
(26-13/16)
(3-23/32)
94 84
Refrigerant service
80
valve <Low pressure>
1060(41-3/4)
3
80
6
7
Refrigerant service
valve <High pressure>
(1-3/16)
29.5
(3-5/32)
Bottom view
(Mounting pitch)
(3-5/32)
<Snow hood attachment hole>
4X5-ø4.6(3/16) Hole
(Make hole at the plastic fan guard
for snow hood attachment)
Discharge air
Specications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
Refrigerant service valve
Intake
air
Refrigerant service valve
<High pressure>
<Low pressure>
(10-11/32)
262
20
20
54(2-5/32)
57
(2-1/4)
(13/16)(13/16)
586(23-3/32)
57
(2-1/4)
Left side view

Twinning Kit: CMY-R100CBK2
CMY-R100CBK2
Low-pressure pipe twinning kit
1-3/32”
1”
5-1/4”
<Low-pressure pipe twinning kit(Accessory)>
High-pressure twinning pipe
3-5/32"
3/4"
1-13/32”
3/4"
7/8"
<Deformed pipe(Accessory)>
2-15/32"
(3Pcs.)
5/8”
3/4”
(Outside diameter)
1”
(Outside diameter)
8-7/16”
4-5/32”
2-3/8”
1"
21/32"
17-1/32”
1”
1”
3-5/32"
<Pipe for routing through the bottom
(Accessory)>
3/4"
(Outside diameter)
1-5/32”
(Outside diameter)
7/8”
(Outside diameter)
21/32”
1-1/4”
3-17/32”
<Pipe for routing through the front
(Accessory)>
1"
4-17/32"
<Elbow pipe(Accessory)>
1-31/32"
6-15/16”
1-31/32"
1-7/16”
1-7/16”
<Deformed pipe(Accessory)>
7/8"
(Outside diameter)
7-17/32"
1-5/32"
1-5/32"
7/8"
7/8"
3/4"
3/4”
2-15/32"
2-5/16"
Ref: CMY_R100VBK_EXD_EUDB_SI
Notes:
FORM# PURY-P192YSKMU-A (-BS) - 201407
Specications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
1340 Satellite Boulevard
Suwanee, GA 30024
Toll Free: 800-433-4822
www.mehvac.com