Mitsubishi PURY-M400YNW-A1, PURY-M250YNW-A1, PURY-M200YNW-A1, PURY-M500YNW-A1, PURY-M450YNW-A1 Data Book

...
AIR CONDITIONING SYSTEMS
MODEL
PURY-M200-500YNW-A1 (-BS) PURY-EM200-500YNW-A1 (-BS)
GENERAL LINE-UP
GENERAL LINE-UP
Heat Recovery R2-Series
PURY-M300YNW-A1(-BS)
PURY-M500YNW-A1(-BS)
PURY-M250YNW-A1(-BS)PURY-M200YNW-A1(-BS)
8, 10, 12HP
PURY-M450YNW-A1(-BS)
PURY-M400YNW-A1(-BS)PURY-M350YNW-A1(-BS)
14, 16, 18HP
20HP
Heat Recovery High efficiency R2-Series
PURY-EM250YNW-A1(-BS)PURY-EM200YNW-A1(-BS)
PURY-EM300YNW-A1(-BS)
8, 10, 12HP
PURY-EM450YNW-A1(-BS)
PURY-EM400YNW-A1(-BS)PURY-EM350YNW-A1(-BS)
14, 16, 18HP
PURY-EM500YNW-A1(-BS)
20HP
MEES18K068
CONTENTS
PURY-M-YNW-A1, PURY-EM-YNW-A1
I.R2-Series
1. SPECIFICATIONS .................................................................................................................................... 2
2. EXTERNAL DIMENSIONS ....................................................................................................................... 16
3. CENTER OF GRAVITY ............................................................................................................................ 28
4. ELECTRICAL WIRING DIAGRAMS ......................................................................................................... 30
5. SOUND LEVELS ...................................................................................................................................... 33
5-1. Sound levels in cooling mode .......................................................................................................... 33
5-2. Sound levels in heating mode.......................................................................................................... 39
6. VIBRATION LEVEL .................................................................................................................................. 45
7. OPERATION TEMPERATURE RANGE...................................................................................................46
8. CAPACITY TABLES ................................................................................................................................. 47
8-1. Correction by temperature ............................................................................................................... 48
8-2. Correction by total indoor................................................................................................................. 60
8-3. Correction by piping length.............................................................................................................. 64
8-4. Correction at frost and defrost ......................................................................................................... 67
8-5. Correction by antifreeze solution concentration............................................................................... 68
9. ELECTRICAL WORK................................................................................................................................ 69
9-1. Power supply for Outdoor unit ......................................................................................................... 69
9-2. Power cable specifications .............................................................................................................. 70
9-3. Power supply examples ................................................................................................................... 71
10.M-NET CONTROL ................................................................................................................................... 72
10-1.Address setting................................................................................................................................ 72
11.PIPING DESIGN ...................................................................................................................................... 73
11-1.R32 Piping material ......................................................................................................................... 73
11-2.Piping Design .................................................................................................................................. 74
11-3.Refrigerant charging calculation ...................................................................................................... 83
11-4.Water piping .................................................................................................................................... 84
R2-Series
MEES18K068
1
1. SPECIFICATIONS
I.R2-Series1. SPECIFICATIONS
Model PURY-M200YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 22.4
(Nominal) kcal/h 20,000
Power input kW 5.53
Current input A 9.3-8.8-8.5
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 25.0
(Nominal) kcal/h 21,500
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
PURY-M-YNW-A1, EM-YNW-A1
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~30
Sound pressure level (measured in anechoic room) *4 dB <A> 59.0/59.0
Sound power level (measured in anechoic room) *4 dB <A> 76.0/78.0
Refrigerant High pressure mm (in.) 15.88 (5/8) Brazed
piping diameter Low pressure mm (in.) 19.05 (3/4) Brazed
FAN Type x Quantity Propeller fan x 1
Compressor Type Inverter scroll hermetic compressor
External finish Pre-coated galvanized steel sh eets (+powder coating for -BS type)
External dimension H x W x D mm 1,858 (1,798 without legs) x 920 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Refrigerant Type x original charge R32 x 5.2 kg (12 lbs)
Net weight kg (lbs) 227 (501)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing External WKL94T598
Standard attachment Document Installation Manual
Optional parts
EER kW/kW 4.05
Power input kW 6.39
Current input A 10.7-10.2-9.8
COP kW/kW 3.91
Air flow rate m3/min 170
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*5 External static press. 0 Pa (0 mmH2O)
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 4.6
Case heater kW - (- V)
Lubricant MEL46EH
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Control HBC controller
Wiring WKE94G769
Accessory -
BTU/h 76,400
BTU/h 85,300
L/s 2,833
cfm 6,003
<MUNSELL 5Y 8/1 or similar>
in. 73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3/16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variatio n.
2
1. SPECIFICATIONS
Model PURY-M250YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 28.0
(Nominal) kcal/h 25,000
BTU/h 95,500
Power input kW 8.40
Current input A 14.1-13.4-12.9
EER kW/kW 3.33
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 31.5
(Nominal) kcal/h 27,100
BTU/h 107,500
Power input kW 9.15
Current input A 15.4-14.6-14.1
COP kW/kW 3.44
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~37
Sound pressure level (meas ured in anechoic room) *4 dB <A> 60.5/61.0
Sound power level (measured in anechoic room) *4 dB <A> 78.5/80.0
Refrigerant High pressure mm (in.) 15.88 (5/8) Brazed
piping diameter Low pressure mm (in.) 22.2 (7/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3/min 185
L/s 3,083
cfm 6,532
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*5 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 7 .0
Case heater kW - (- V)
Lubricant MEL46EH
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,858 (1,798 without legs) x 920 x 740
in. 73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switc h at 4.15 MPa (601 psi)
Inverter circuit (COMP./FA N) Ove r-heat protection, Over-cur rent protection
Compressor -
Fan motor -
Refrigerant Type x original charge R32 x 5.2 kg (12 lbs)
Control HBC controller
Net weight kg (lbs) 227 (501)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing External WKL94T598
Wiring WKE94G769
Standard attachment Document Installation Manual
Accessory -
Optional parts
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variation.
3
1. SPECIFICATIONS
Model PURY-M300YNW-A1 (-BS)
Number of HBC controller Single HBC Double HBC
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 33.5
(Nominal) kcal/h 30,000
Power input kW 11.65 9.88
Current input A 19.6-18.6-18.0 16.6-15.8-15.2
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 37.5
(Nominal) kcal/h 32,300
PURY-M-YNW-A1, EM-YNW-A1
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10 ~125/2~45
Sound pressure level (measured in anechoic room) *4 dB <A> 61.0/67.0
Sound power level (measured in anechoic room) *4 dB <A> 80.0/86.5
Refrigerant High pressure mm (in.) 15.88 (5/ 8) Brazed
piping diameter L ow pressure mm (in.) 22.2 (7/8) Brazed
FAN Type x Quantity Propeller fan x 1
Compressor Type Inverter scroll hermetic compressor
External finish Pre-coated galvanized steel sh eets (+powder coating for -BS type)
External dimension H x W x D mm 1,858 (1,798 without legs) x 920 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Refrigerant Type x original charge R32 x 5.2 kg (12 lbs)
Net weight kg (lbs) 227 (501)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing External WKL94T598
Standard attachment Document Installation Manual
Optional parts Main HBC controller: CMB-WM108,1016V-AA
EER kW/kW 2.87 3.39
Power input kW 11.00 10.33
Current input A 18.5-17.6-17.0 17.4-16.5-15.9
COP kW/kW 3.40 3.63
Air flow rate m
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*5 External static press. 0 Pa (0 mmH
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 8.0
Case heater kW - (- V)
Lubricant MEL46EH
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Control HBC controller
Wiring WKE94G769
Accessory -
BTU/h 114,300
BTU/h 128,000
3
/min 240
L/s 4,000
cfm 8,474
O)
2
<MUNSELL 5Y 8/1 or similar>
in. 73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3/16
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variatio n.
4
1. SPECIFICATIONS
Model PURY-M350YNW-A1 (-BS)
Number of HBC controller Single HBC Double HBC
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 40.0
(Nominal) kcal/h 35,000
Power input kW 14.93 12.15
Current input A 25.2-2 3.9-23.0 20.5-19.4-18.7
EER kW/kW 2.67 3.29
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 45.0
(Nominal) kcal/h 38,700
Power input kW 13.14 12.16
Current input A 22.1-2 1.0-20.3 20.5-19.5-18.7
COP kW/kW 3.42 3.70
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~35
Sound pressure level (meas ured in anechoic room) *4 dB <A> 62 .5/64.0
Sound power level (measured in anechoic room) *4 dB <A> 81.0/83.0
Refrigerant High pressure mm (in.) 15.88 (5/8) Brazed
piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 2
Air flow rate m
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.46 x 2
*5 External static press. 0 Pa (0 mmH
Compressor Type Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 9.6
Case heater kW - (- V)
Lubricant MEL46EH
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
External dimension H x W x D mm 1,858 (1,798 without legs) x 1,240 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R32 x 8.0 kg (18 lbs)
Control HBC controller
Net weight kg (lbs) 270 (596)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External WKL94T599
Wiring WKE94G770
Standard attachment Document Installation Manual
Accessory -
Optional parts Main HBC controller: CMB-WM108,1016V-AA
BTU/h 136,500
BTU/h 153,500
3
/min 250
L/s 4,167
cfm 8,828
O)
2
<MUNSELL 5Y 8/1 or similar>
in. 73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3/16
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variation.
5
1. SPECIFICATIONS
Model PURY-M400YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 45.0
(Nominal) kcal/h 40,000
Power input kW 15.15
Current input A 25.5-24.2-23.4
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 50.0
(Nominal) kcal/h 45,000
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
PURY-M-YNW-A1, EM-YNW-A1
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~40
Sound pressure level (measured in anechoic room) *4 dB <A> 65.0/69.0
Sound power level (measured in anechoic room) *4 dB <A> 83.0/88.0
Refrigerant High pressure mm (in.) 19.05 (3/4) Brazed
piping diameter L ow pressure mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 2
Compressor Type Inverter scroll hermetic compressor
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
External dimension H x W x D mm 1,858 (1,798 without legs) x 1,240 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Refrigerant Type x original charge R32 x 8.0 kg (18 lbs)
Net weight kg (lbs) 273 (602)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External WKL94T599
Standard attachment Document Installation Manual
Optional parts
EER kW/kW 2.97
Power input kW 14.08
Current input A 23.7-22.5-21.7
COP kW/kW 3.55
Air flow rate m3/min 315
Control, Driving mechanism Inverter-control, Direct-dri ven by motor
Motor output kW 0.46 x 2
*5 External static press. 0 Pa (0 mmH2O)
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 12.2
Case heater kW - (- V)
Lubricant MEL46EH
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Control HBC controller
Wiring WKE94G770
Accessory -
BTU/h 153,500
BTU/h 170,600
L/s 5,250
cfm 11,123
<MUNSELL 5Y 8/1 or similar>
in. 73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3/16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variatio n.
6
1. SPECIFICATIONS
Model PURY-M450YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 50.0
(Nominal) kcal/h 45,000
BTU/h 170,600
Power input kW 15.47
Current input A 26.1-24.8-23.9
EER kW/kW 3.23
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 56.0
(Nominal) kcal/h 50,000
BTU/h 191,100
Power input kW 16.18
Current input A 27.3-25.9-25.0
COP kW/kW 3.46
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~45
Sound pressure level (meas ured in anechoic room) *4 dB <A> 65.5/70.0
Sound power level (measured in anechoic room) *4 dB <A> 83.0/89.0
Refrigerant High pressure mm (in.) 19.05 (3/4) Brazed
piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 2
Air flow rate m3/min 317
L/s 5,283
cfm 11,193
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.46 x 2
*5 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 13.1
Case heater kW - (- V)
Lubricant MEL46EH
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,858 (1,798 without le gs) x 1,240 x 740
in. 73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switc h at 4.15 MPa (601 psi)
Inverter circuit (COMP./FA N) Ove r-heat protection, Over-cur rent protection
Compressor -
Fan motor -
Refrigerant Type x original charge R32 x 10.8 kg (24 lbs)
Control HBC controller
Net weight kg (lbs) 293 (646)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External WKL94T599
Wiring WKE94G770
Standard attachment Document Installation Manual
Accessory -
Optional parts
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variation.
7
1. SPECIFICATIONS
Model PURY-M500YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 56.0
(Nominal) kcal/h 50,000
Power input kW 22.25
Current input A 37.5-35.6-34.3
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 63.0
(Nominal) kcal/h 54,200
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
PURY-M-YNW-A1, EM-YNW-A1
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~50
Sound pressure level (measured in anechoic room) *4 dB <A> 63.5/64.5
Sound power level (measured in anechoic room) *4 dB <A> 82.0/84.0
Refrigerant High pressure mm (in.) 19.05 (3/4) Brazed
piping diameter L ow pressure mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 2
Compressor Type Inverter scroll hermetic compressor
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
External dimension H x W x D mm 1,858 (1,798 without legs) x 1,750 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Refrigerant Type x original charge R32 x 10.8 kg (24 lbs)
Net weight kg (lbs) 337 (743)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External WKL94T600
Standard attachment Document Installation Manual
Optional parts
EER kW/kW 2.51
Power input kW 18.26
Current input A 30.8-29.2-28.2
COP kW/kW 3.45
Air flow rate m3/min 295
Control, Driving mechanism Inverter-control, Direct-dri ven by motor
Motor output kW 0.92 x 2
*5 External static press. 0 Pa (0 mmH2O)
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 17.4
Case heater kW - (- V)
Lubricant MEL46EH
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Control HBC controller
Wiring WKE94G771
Accessory -
BTU/h 191,100
BTU/h 215,000
L/s 4,917
cfm 10,416
<MUNSELL 5Y 8/1 or similar>
in. 73-3/16 (70-13/16 without legs) x 68-15/16 x 29-3/16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variatio n.
8
1. SPECIFICATIONS
Model PURY-EM200YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 22.4
(Nominal) kcal/h 20,000
BTU/h 76,400
Power input kW 5.13
Current input A 8.6-8.2-7.9
EER kW/kW 4.36
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 25.0
(Nominal) kcal/h 21,500
BTU/h 85,300
Power input kW 6.23
Current input A 10.5-9.9-9.6
COP kW/kW 4.01
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~30
Sound pressure level (meas ured in anechoic room) *4 dB <A> 59.0/59.0
Sound power level (measured in anechoic room) *4 dB <A> 76.0/78.0
Refrigerant High pressure mm (in.) 15.88 (5/8) Brazed
piping diameter Low pressure mm (in.) 19.05 (3/4) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3/min 170
L/s 2,833
cfm 6,003
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*5 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 4 .5
Case heater kW - (- V)
Lubricant MEL46EH
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,858 (1,798 without legs) x 920 x 740
in. 73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switc h at 4.15 MPa (601 psi)
Inverter circuit (COMP./FA N) Ove r-heat protection, Over-cur rent protection
Compressor -
Fan motor -
Refrigerant Type x original charge R32 x 5.2 kg (12 lbs)
Control HBC controller
Net weight kg (lbs) 231 (510)
Heat exchanger Salt-resistant cross fin & aluminium tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing External WKL94T601
Wiring WKE94G769
Standard attachment Document Installation Manual
Accessory -
Optional parts
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variation.
9
1. SPECIFICATIONS
Model PURY-EM250YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 28.0
(Nominal) kcal/h 25,000
Power input kW 7.69
Current input A 12.9-12.3-11.8
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 31.5
(Nominal) kcal/h 27,100
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
PURY-M-YNW-A1, EM-YNW-A1
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~37
Sound pressure level (measured in anechoic room) *4 dB <A> 60.5/61.0
Sound power level (measured in anechoic room) *4 dB <A> 78.5/80.0
Refrigerant High pressure mm (in.) 15.88 (5/8) Brazed
piping diameter Low pressure mm (in.) 22.2 (7/8) Brazed
FAN Type x Quantity Propeller fan x 1
Compressor Type Inverter scroll hermetic compressor
External finish Pre-coated galvanized steel sheets (+po wder coating for -BS type)
External dimension H x W x D mm 1,858 (1,798 without legs) x 920 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Refrigerant Type x original charge R32 x 5.2 kg (12 lbs)
Net weight kg (lbs) 231 (510)
Heat exchanger Salt-resistant cross fin & aluminium tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing External WKL94T601
Standard attachment Document Installation Manual
Optional parts
EER kW/kW 3.64
Power input kW 8.84
Current input A 14.9-14.1-13.6
COP kW/kW 3.56
Air flow rate m3/min 185
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*5 External static press. 0 Pa (0 mmH2O)
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 6.7
Case heater kW - (- V)
Lubricant MEL46EH
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Control HBC controller
Wiring WKE94G769
Accessory -
BTU/h 95,500
BTU/h 107,500
L/s 3,083
cfm 6,532
<MUNSELL 5Y 8/1 or similar>
in. 73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3 /16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variatio n.
10
1. SPECIFICATIONS
Model PURY-EM300YNW-A1 (- BS)
Number of HBC controller Single HBC Double HBC
Power source 3-ph ase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 33.5
(Nominal) kcal/h 30,000
Power input kW 10.03 8.52
Current input A 16.9-16.0-15.5 14.3-13.6-13.1
EER kW/kW 3.33 3.93
Temp. range of Indoor W.B. 15.0~24 .0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 37.5
(Nominal) kcal/h 32,300
Power input kW 10.46 9.93
Current input A 17.6-16.7-16.1 16.7-15.9-15.3
COP kW/kW 3.58 3.77
Temp. range of Indoor D.B. 15.0~27.0° C (59~81°F)
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/2~45
Sound pressure level (measured in anechoic room) *4 dB <A> 61.0/67.0
Sound power level (measured in anechoic room) *4 dB <A> 80.0/86.5
Refrigerant High pressure mm (in.) 15.88 (5/8) Brazed
piping diameter Low pressure mm (in.) 22.2 (7/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*5 External static press. 0 Pa (0 mmH
Compressor Type Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 7.7
Case heater kW - (- V)
Lubricant MEL46EH
External finish Pre-coate d galvanized steel sheets (+powder co ating for -BS type)
External dimension H x W x D mm 1,858 (1,798 without legs) x 920 x 740
Protection devices High pressure protection High pressure sensor, High pre ssure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FA N) Over-heat protection, Over-current protectio n
Compressor -
Fan motor -
Refrigerant Type x original charge R32 x 5.2 kg (12 lbs)
Control HBC controller
Net weight kg (lbs) 23 1 (510)
Heat exchanger Salt-resistant cross fin & aluminium tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing External WKL94T601
Wiring WKE94G769
Standard attachment Document Installation Manual
Accessory -
Optional parts Main HBC controller: CMB -WM108,1016V-AA
BTU/h 114,300
BTU/h 128,000
3
/min 240
L/s 4,000
cfm 8,474
O)
2
<MUNSELL 5Y 8/1 or similar>
in. 73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3/16
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, above specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variation.
11
1. SPECIFICATIONS
Model PURY-EM350YNW-A1 (-BS)
Number of HBC controller Single HBC Double HBC
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 40.0
(Nominal) kcal/h 35,000
Power input kW 13.91 11.33
Current input A 23.4-22.3-21.5 19.1-18.1-17.5
Temp. range of Indoor W.B. 15.0 ~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 45.0
(Nominal) kcal/h 38,700
PURY-M-YNW-A1, EM-YNW-A1
Temp. range of Indoor D.B. 15.0~27. 0°C (59~81°F)
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~35
Sound pressure level (measured in anechoic room) *4 dB <A> 62.5/64.0
Sound power level (measured in anechoic room) *4 dB <A> 81.0/83.0
Refrigerant High pressure mm (in.) 1 5.88 (5/8) Brazed
piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 2
Compressor Type Inverter scroll hermetic compressor
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
External dimension H x W x D mm 1,858 (1,798 without legs) x 1,240 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Refrigerant Type x original charge R32 x 8.0 kg (18 lbs)
Net weight kg (lbs) 276 (609)
Heat exchanger Salt-resistant cross fin & aluminium tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing External WKL94T602
Standard attachment Document Installation Manual
Optional parts Main HBC contro ller: CMB-WM108,1016V-AA
EER kW/kW 2.87 3.53
Power input kW 13.10 12.16
Current input A 22.1-21.0-20.2 20.5-19.5-18.7
COP kW/kW 3.43 3.70
Air flow rate m
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.46 x 2
*5 External static press. 0 Pa (0 mmH
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 9.6
Case heater kW - (- V)
Lubricant MEL46EH
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Control HBC controller
Wiring WKE94G770
Accessory -
BTU/h 136,500
BTU/h 153,500
3
/min 250
L/s 4,167
cfm 8,828
O)
2
<MUNSELL 5Y 8/1 or similar>
in. 73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3/16
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, above specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variatio n.
12
1. SPECIFICATIONS
Model PURY-EM400YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 45.0
(Nominal) kcal/h 40,000
BTU/h 153,500
Power input kW 13.84
Current input A 23.3-22.1-21.3
EER kW/kW 3.25
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 50.0
(Nominal) kcal/h 45,000
BTU/h 170,600
Power input kW 13.88
Current input A 23.4-22.2-21.4
COP kW/kW 3.60
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~1 25/1~40
Sound pressure level (meas ured in anechoic room) *4 dB <A> 65.0/69.0
Sound power level (measured in anechoic room) *4 dB <A> 83.0/88.0
Refrigerant High pressure mm (in.) 19.05 (3/4) Brazed
piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 2
Air flow rate m3/min 315
L/s 5,250
cfm 11,123
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.46 x 2
*5 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 11.1
Case heater kW - (- V)
Lubricant MEL46EH
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,858 (1,798 without legs) x 1,240 x 740
in. 73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R32 x 8.0 kg (18 lbs)
Control HBC con troller
Net weight kg (lbs) 280 (618)
Heat exchanger Salt-resistant cross fin & aluminium tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External WKL94T602
Wiring WKE94G770
Standard attachment Document Installation Manual
Accessory -
Optional parts
Main HBC controller: CMB-WM108,1016V-A A
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variation.
13
1. SPECIFICATIONS
Model PURY-EM450YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 50.0
(Nominal) kcal/h 45,000
Power input kW 15.24
Current input A 25.7-24.4-23.5
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 56.0
(Nominal) kcal/h 50,000
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
PURY-M-YNW-A1, EM-YNW-A1
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~125/1~45
Sound pressure level (measured in anechoic room) *4 dB <A> 65.5/70.0
Sound power level (measured in anechoic room) *4 dB <A> 83.0/89.0
Refrigerant High pressure mm (in.) 19.05 (3/4) Brazed
piping diameter L ow pressure mm (in.) 28.58 (1-1/8) Bra zed
FAN Type x Quantity Propeller f an x 2
Compressor Type Inverter scroll hermetic compressor
External finish Pre-coated galvanized steel sheets (+po wder coating for -BS type)
External dimension H x W x D mm 1,858 (1,798 without legs) x 1,240 x 740
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Refrigerant Type x original charge R32 x 10.8 kg (24 lbs)
Net weight kg (lbs) 305 (673)
Heat exchanger Salt-resistant cross fin & aluminium tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External WKL94T602
Standard attachment Document Installation Manual
Optional parts
EER kW/kW 3.28
Power input kW 15.77
Current input A 26.6-25.2-24.3
COP kW/kW 3.55
Air flow rate m3/min 315
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.46 x 2
*5 External static press. 0 Pa (0 mmH2O)
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 12.7
Case heater kW - (- V)
Lubricant MEL46EH
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Control HBC controller
Wiring WKE94G770
Accessory -
BTU/h 170,600
BTU/h 191,100
L/s 5,250
cfm 11,123
<MUNSELL 5Y 8/1 or similar>
in. 73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3 /16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variatio n.
14
1. SPECIFICATIONS
Model PURY-EM500YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 56.0
(Nominal) kcal/h 50,000
BTU/h 191,100
Power input kW 18.06
Current input A 30.4-28.9-27.9
EER kW/kW 3.10
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling *3 Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 63.0
(Nominal) kcal/h 54,200
BTU/h 215,000
Power input kW 17.45
Current input A 29.4-27.9-26.9
COP kW/kW 3.61
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
heating *3 Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity WP10~125, W10~1 25/1~50
Sound pressure level (meas ured in anechoic room) *4 dB <A> 63.5/64.5
Sound power level (measured in anechoic room) *4 dB <A> 82.0/84.0
Refrigerant High pressure mm (in.) 19.05 (3/4) Brazed
piping diameter Low pressure mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 2
Air flow rate m3/min 295
L/s 4,917
cfm 10,416
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 2
*5 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 13.8
Case heater kW - (- V)
Lubricant MEL46EH
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,858 (1,798 without legs) x 1,750 x 740
in. 73-3/16 (70-13/16 without legs) x 68-15/16 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R32 x 10.8 kg (24 lbs)
Control HBC con troller
Net weight kg (lbs) 348 (768)
Heat exchanger Salt-resistant cross fin & aluminium tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External WKL94T603
Wiring WKE94G771
Standard attachment Document Installation Manual
Accessory -
Optional parts
Main HBC controller: CMB-WM108,1016V-A A
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2) Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2) Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.) with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O). Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units. When installing new units, moving the existing units, or changing the layout of the room, ensure that installation restrictions are observed. For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual. Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is subject to rounding variation.
15
2. EXTERNAL DIMENSIONS
PURY-M200, 250, 300YNW-A1(-BS)
Unit: mm
1
3
4
7
Intake
air
Front view
Intake
air
Intake
air
Discharge air
Left side view
Rear view
2
5
6
8
(Mounting pitch)
Bottom view
(Mounting pitch)
2×5-ø4.6 Hole
(Make hole at the plastic fan guard
for snow hood attachment)
<Snow hood attachment hole>
Top view
Sling hole
Detachable leg
(front and back, 2 points)
Note 2*
2×2-14×31 Oval hole
2×2-14×20 Oval hole(without detachable leg)
Intake
air
Refrigerant
service valve
<High pressure>
Refrigerant
service valve
<Low pressure>
Service
panel
Control box
(INV Box)
Control box
(MAIN Box)
For transmission cables
For wires
For pipes
NO.
Usage Specifications
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Bottom through hole
Front through hole
148 × 84 Knockout hole
ø65 or ø40 Knockout hole
ø52 or ø27 Knockout hole
ø65 Knockout hole
ø52 Knockout hole
ø34 Knockout hole
150 × 94 Knockout hole
Connecting pipe specifications
ø34 Knockout hole
Note 1.Please refer to the next page for information regarding necessary
spacing around the unit and foundation work.
2.The detachable leg can be removed at site.
3.At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of refrigerant
service valve under 120°C.
4.This unit has restrictions for the safety, so refer to
SAFETY HANDLING FOR R32 or the Installation Manual.
*1 Connect the refrigerant pipe to the service valve
according to the Installation Manual.
Bottom through hole
Model
Diameter
Refrigerant pipe
Service valve
M250
ø22.2
ø22.2 Brazed *1
ø15.88 Brazed *1
ø28.58
M200
High pressure Low pressure
M300
High pressure Low pressure
ø19.05 Brazed *1
132
207
256
148125
90
110
125
1495 303
1798
(60)
1858
5656
20
54
592
110
185
681(678~684)
29.5
(740)
80760
80
166
181
152
172
216
160
243
150128
94 79
181
29.5
84
71
35
920
19.519.5 881
740
150
600=150×470
54
20
116
(60)
1
243
567
8
2. EXTERNAL DIMENSIONS
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
16
2. EXTERNAL DIMENSIONS
Unit: mm
PURY-M200, 250, 300YNW-A1(-BS)
Front
Front
<Top view>
*
<Unit:mm>
<Top view>
M10 anchor bolt
<field supply required>
Fixing plate
<field supply required>
<To be left open>
Front
Wall <H>
<To be left open>
Front
<Unit:mm>
Fixing plate
<field supply required>
M10 anchor bolt
<field supply required>
Wall <H>
<To be left open>
<To be left open>
<To be left open>
Front
Wall <H>
Wall <H>
Wall <H>
Wall <H>
Front
Front
<To be left open>
Wall <H>
Front
Wall <H>
<To be left open>
<To be left open>
Front
Front
Front
Wall <H>
Wall <H>
Front
<To be left open>
<To be left open>
Detachable leg
Fig.A (without detachable legs)
Fig.B (with detachable legs)
Fig.C (without detachable legs) Fig.D (with detachable legs)
Detachable leg
<Wall height limit> Front :Up to the unit height
Back :Up to the unit height
Side :Up to the unit height
<Side view>
Front
1. Required space around the unit
●In case of single installation
1 Secure enough space around the unit as shown in the figure below.
· With a space of at least
300mm to the wall on
the back of the unit
2 When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
2. Foundation work
1 Take into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
2 Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure.(Fig.A,B)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A,B)
4 Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts.(Fig.C,D)
5
To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
7 Refer to the Installation Manual when installing units on an installation base.
●In case of collective installation
· With a space of at least
100mm to the wall on
the back of the unit
15 min.
50 min.* 50 min.*
100 min.*
450 min.*
300 min.*
100 min.30 min.
450 min.450 min.* 450 min. 100 min.*
450 min.* 100 min.*
450 min.*
1000 min.*
900 min.
300 min.*
900 min.
300 min.*300 min.*
15 min.*
450 min.450 min.
450 min.* 300 min.*
15 min.*
30mm max.30mm max.
Unit height
h
H
Unit height
h
H
1 When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>
to the figures that are marked with an asterisk.
4 If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each six units.
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
17
2. EXTERNAL DIMENSIONS
PURY-M350,400,450YNW-A1(-BS)
Unit: mm
Note 1.Please refer to the next page for information regarding necessary
spacing around the unit and foundation work.
2.The detachable leg can be removed at site.
3.At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of refrigerant
service valve under 120°C.
4.This unit has restrictions for the safety, so refer to
SAFETY HANDLING FOR R32 or the Installation Manual.
NO.
1
243
567
8
740
70
150 85 85130 150
18
1204181240
110
(740)
185
29.5
681(678~684)
29.5
94
79
181
160
243
150
128
125
132
207
256
90
110
8471
35
56
116
(60)
20
54
592
54
20
56
148
152
216
166
125
(60)
3031495
1798
1858
90
1060
90
172
2
5
68
(Mounting pitch)
Bottom view
(Mounting pitch)
2×2-14×31 Oval hole
2×2-14×20 Oval hole(without detachable leg)
1
Sling hole
Detachable leg
(front and back, 2 points)
Note 2*
Control box
3
4
7
Service
panel
Intake
air
Intake
air
Discharge air
Intake
air
Intake
air
2×6-ø4.6 Hole
(Make hole at the plastic fan guard
for snow hood attachment)
<Snow hood attachment hole>
Top view
Front view
Left side view
Rear view
Refrigerant
service valve
<High pressure>
Refrigerant
service valve
<Low pressure>
For transmission cables
For wires
For pipes
Usage
Specifications
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Bottom through hole
Front through hole
148 × 84 Knockout hole
ø65 or ø40 Knockout hole
ø52 or ø27 Knockout hole
ø65 Knockout hole
ø52 Knockout hole
ø34 Knockout hole
150 × 94 Knockout hole
Connecting pipe specifications
ø34 Knockout hole
*1 Connect the refrigerant pipe to the service valve
according to the Installation Manual.
Bottom through hole
Model
Diameter
Refrigerant pipe
Service valve
M400
ø28.58
ø15.88 Brazed *1
ø28.58
M350
High pressure Low pressure
ø28.58 Brazed
ø19.05 Brazed *1
M450
High pressure Low pressure
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
18
2. EXTERNAL DIMENSIONS
Unit: mm
PURY-M350,400,450YNW-A1(-BS)
<Wall height limit> Front :Up to the unit height
Back :Up to the unit height
Side :Up to the unit height
1. Required space around the unit
●In case of single installation
1 Secure enough space around the unit as shown in the figure below.
· With a space of at least
300mm to the wall on
the back of the unit
2 When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
2. Foundation work
1 Take into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
2 Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure.(Fig.A,B)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A,B)
4 Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts.(Fig.C,D)
5
To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
7 Refer to the Installation Manual when installing units on an installation base.
●In case of collective installation
· With a space of at least
100mm to the wall on
the back of the unit
1 When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>
to the figures that are marked with an asterisk.
4 If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each six units.
Front
Front
<Top view>
<Unit:mm>
<Top view>
M10 anchor bolt
<field supply required>
Fixing plate
<field supply required>
<To be left open>
Front
Wall <H>
<To be left open>
Front
<Unit:mm>
Fixing plate
<field supply required>
M10 anchor bolt
<field supply required>
Wall <H>
<To be left open>
<To be left open>
<To be left open>
Front
Wall <H>
Wall <H>
Wall <H>
Wall <H>
Front
Front
<To be left open>
Wall <H>
Front
Wall <H>
<To be left open>
<To be left open>
Front
Front
Front
Wall <H>
Wall <H>
Front
<To be left open>
<To be left open>
Detachable leg
Fig.A (without detachable legs)
Fig.B (with detachable legs)
Fig.C (without detachable legs) Fig.D (with detachable legs)
Detachable leg
<Side view>
Front
15 min.*
50 min.* 50 min.*
100 min.*450 min.*
300 min.*
100 min.
30 min.
450 min.450 min.* 450 min.
100 min.*
450 min.* 100 min.*
450 min.*
1000 min.*
900 min.
300 min.*
900 min.
300 min.*300 min.*
15 min.*
450 min.450 min.
450 min.* 300 min.*
15 min.*
30mm max.
30mm max.
Unit height
h
H
Unit height
h
H
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
19
2. EXTERNAL DIMENSIONS
PURY-M500YNW-A1(-BS)
Unit: mm
Note 1.Please refer to the next page for information regarding necessary
spacing around the unit and foundation work.
2.The detachable leg can be removed at site.
3.At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of refrigerant
service valve under 120°C.
4.This unit has restrictions for the safety, so refer to
SAFETY HANDLING FOR R32 or the Installation Manual.
NO.
1
243
567
8
(740)
132
650
148
8471
110
125
90
207
256
(60)
116
35
740
831831
19.5
19.5
70
150
600=150×4
1750
49
185
152
1495 303
1798
(60)
1858
172
216
166
110
29.5
681(678~684)
29.5
80
685
768
653 150
94 79
181
795795
80
20
54
59254
20
60
60
Control box
3
4
7
Intake
air
Intake
air
Discharge air
5
6
8
Intake
air
Intake
air
Detachable leg
(front and back, 3 points)
Note 2*
2×7-ø4.6 Hole
(Make hole at the plastic fan guard
for snow hood attachment)
<Snow hood attachment hole>
Top v i e w
1
Service
panel
2
(Mounting pitch)
Bottom view
(Mounting pitch)
Front view
Left side view
Rear view
Sling hole
(Mounting pitch)
2×3-14×31 Oval hole
2×3-14×20 Oval hole(without detachable leg)
Refrigerant
service valve
<High pressure>
Refrigerant
service valve
<Low pressure>
For transmission cables
For wires
For pipes
Usage Specifications
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Bottom through hole
Front through hole
148 × 84 Knockout hole
ø65 or ø40 Knockout hole
ø52 or ø27 Knockout hole
ø65 Knockout hole
ø52 Knockout hole
ø34 Knockout hole
150 × 94 Knockout hole
Connecting pipe specifications
ø34 Knockout hole
Bottom through hole
Model
Diameter
Refrigerant pipe
Service valve
ø28.58
ø19.05 Brazed *1
ø28.58
M500
High pressure Low pressure
ø28.58 Brazed
High pressure Low pressure
*1 Connect the refrigerant pipe to the service valve
according to the Installation Manual.
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
20
2. EXTERNAL DIMENSIONS
PURY-M500YNW-A1(-BS)
<Wall height limit> Front :Up to the unit height
Back :Up to the unit height
Side :Up to the unit height
1. Required space around the unit
●In case of single installation
1 Secure enough space around the unit as shown in the figure below.
· With a space of at least
300mm to the wall on
the back of the unit
2 When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
2. Foundation work
1 Take into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
2 Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure.(Fig.A,B)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A,B)
4 Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts.(Fig.C,D)
5
To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
7 Refer to the Installation Manual when installing units on an installation base.
●In case of collective installation
· With a space of at least
100mm to the wall on
the back of the unit
1 When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>
to the figures that are marked with an asterisk.
4 If there is a wall at both the front and the rear of the unit, install up to three units
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each three units.
<Top view>
<Unit:mm>
<Top view>
M10 anchor bolt
<field supply required>
Fixing plate
<field supply required>
<Unit:mm>
Fixing plate
<field supply required>
M10 anchor bolt
<field supply required>
Detachable leg
Fig.A (without detachable legs)
Fig.B (with detachable legs)
Fig.C (without detachable legs) Fig.D (with detachable legs)
Detachable leg
Front
Front
<To be left open>
Front
Wall <H>
Wall <H>
<To be left open>
<To be left open>
Front
Wall <H>
Wall <H>
<To be left open>
<To be left open>
Front
Wall <H>
Wall <H>
Front
Front
<To be left open>
Front
Front
Front
Wall <H>
Wall <H>
Front
Wall <H>
<To be left open>
<To be left open>
Wall <H>
Front
<To be left open>
<To be left open>
<Side view>
Front
30mm max.
30mm max.
450 min.*
300 min.*
15 min.*15 min.*
50 min.*
50 min.*
450 min.*
100 min.*
30 min.
100 min.
450 min.* 450 min. 450 min. 100 min.*
15 min.*
450 min. 450 min.
900 min.
300 min.*300 min.*
1000 min.*
300 min.*
900 min.
300 min.*
450 min.*
100 min.*450 min.*
Unit height
h
H
Unit height
h
H
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
21
2. EXTERNAL DIMENSIONS
PURY-EM200, 250, 300YNW-A1(-BS)
Unit: mm
1
3
4
7
Intake
air
Front view
Intake
air
Intake
air
Discharge air
Left side view
Rear view
2
5
6
8
(Mounting pitch)
Bottom view
(Mounting pitch)
2×5-ø4.6 Hole
(Make hole at the plastic fan guard
for snow hood attachment)
<Snow hood attachment hole>
Top view
Sling hole
Detachable leg
(front and back, 2 points)
Note 2*
2×2-14×31 Oval hole
2×2-14×20 Oval hole(without detachable leg)
Intake
air
Refrigerant
service valve
<High pressure>
Refrigerant
service valve
<Low pressure>
Service
panel
Control box
(INV Box)
Control box
(MAIN Box)
For transmission cables
For wires
For pipes
NO.
Usage Specifications
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Bottom through hole
Front through hole
148 × 84 Knockout hole
ø65 or ø40 Knockout hole
ø52 or ø27 Knockout hole
ø65 Knockout hole
ø52 Knockout hole
ø34 Knockout hole
150 × 94 Knockout hole
Connecting pipe specifications
ø34 Knockout hole
Note 1.Please refer to the next page for information regarding necessary
spacing around the unit and foundation work.
2.The detachable leg can be removed at site.
3.At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of refrigerant
service valve under 120°C.
4.This unit has restrictions for the safety, so refer to
SAFETY HANDLING FOR R32 or the Installation Manual.
*1 Connect the refrigerant pipe to the service valve
according to the Installation Manual.
Bottom through hole
Model
Diameter
Refrigerant pipe
Service valve
EM250
ø22.2
ø22.2 Brazed *1
ø15.88 Brazed *1
ø28.58
EM200
High pressure Low pressure
EM300
High pressure Low pressure
ø19.05 Brazed *1
132
207
256
148125
90
110
125
1495 303
1798
(60)
1858
5656
20
54
592
110
185
681(678~684)
29.5
(740)
80760
80
166
181
152
172
216
160
243
150128
94 79
181
29.5
84
71
35
920
19.519.5 881
740
150
600=150×470
54
20
116
(60)
1
243
567
8
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
22
2. EXTERNAL DIMENSIONS
Unit: mm
PURY-EM200, 250, 300YNW-A1(-BS)
Front
Front
<Top view>
*
<Unit:mm>
<Top view>
M10 anchor bolt
<field supply required>
Fixing plate
<field supply required>
<To be left open>
Front
Wall <H>
<To be left open>
Front
<Unit:mm>
Fixing plate
<field supply required>
M10 anchor bolt
<field supply required>
Wall <H>
<To be left open>
<To be left open>
<To be left open>
Front
Wall <H>
Wall <H>
Wall <H>
Wall <H>
Front
Front
<To be left open>
Wall <H>
Front
Wall <H>
<To be left open>
<To be left open>
Front
Front
Front
Wall <H>
Wall <H>
Front
<To be left open>
<To be left open>
Detachable leg
Fig.A (without detachable legs)
Fig.B (with detachable legs)
Fig.C (without detachable legs) Fig.D (with detachable legs)
Detachable leg
<Wall height limit> Front :Up to the unit height
Back :Up to the unit height
Side :Up to the unit height
<Side view>
Front
1. Required space around the unit
●In case of single installation
1 Secure enough space around the unit as shown in the figure below.
· With a space of at least
300mm to the wall on
the back of the unit
2 When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
2. Foundation work
1 Take into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
2 Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure.(Fig.A,B)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A,B)
4 Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts.(Fig.C,D)
5
To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
7 Refer to the Installation Manual when installing units on an installation base.
●In case of collective installation
· With a space of at least
100mm to the wall on
the back of the unit
15 min.
50 min.* 50 min.*
100 min.*
450 min.*
300 min.*
100 min.30 min.
450 min.450 min.* 450 min. 100 min.*
450 min.* 100 min.*
450 min.*
1000 min.*
900 min.
300 min.*
900 min.
300 min.*300 min.*
15 min.*
450 min.450 min.
450 min.* 300 min.*
15 min.*
30mm max.30mm max.
Unit height
h
H
Unit height
h
H
1 When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>
to the figures that are marked with an asterisk.
4 If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each six units.
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
23
2. EXTERNAL DIMENSIONS
PURY-EM350,400,450YNW-A1(-BS)
Unit: mm
Note 1.Please refer to the next page for information regarding necessary
spacing around the unit and foundation work.
2.The detachable leg can be removed at site.
3.At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of refrigerant
service valve under 120°C.
4.This unit has restrictions for the safety, so refer to
SAFETY HANDLING FOR R32 or the Installation Manual.
NO.
1
243
567
8
740
70
150 8585130 150
18
1204
18
1240
110
(740)
185
29.5
681(678~684)
29.5
94
79
181
160
243
150
128
125
132
207
256
90
110
8471
35
56
116
(60)
20
54
592
54
20
56
148
152
216
166
125
(60)
3031495
1798
1858
90
1060
90
172
2
5
68
(Mounting pitch)
Bottom view
(Mounting pitch)
2×2-14×31 Oval hole
2×2-14×20 Oval hole(without detachable leg)
1
Sling hole
Detachable leg
(front and back, 2 points)
Note 2*
Control box
3
4
7
Service
panel
Intake
air
Intake
air
Discharge air
Intake
air
Intake
air
2×6-ø4.6 Hole
(Make hole at the plastic fan guard
for snow hood attachment)
<Snow hood attachment hole>
Top view
Front view
Left side view
Rear view
Refrigerant
service valve
<High pressure>
Refrigerant
service valve
<Low pressure>
For transmission cables
For wires
For pipes
Usage
Specifications
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Bottom through hole
Front through hole
148 × 84 Knockout hole
ø65 or ø40 Knockout hole
ø52 or ø27 Knockout hole
ø65 Knockout hole
ø52 Knockout hole
ø34 Knockout hole
150 × 94 Knockout hole
Connecting pipe specifications
ø34 Knockout hole
*1 Connect the refrigerant pipe to the service valve
according to the Installation Manual.
Bottom through hole
Model
Diameter
Refrigerant pipe
Service valve
EM400
ø28.58
ø15.88 Brazed *1
ø28.58
EM350
High pressure Low pressure
ø28.58 Brazed
ø19.05 Brazed *1
EM450
High pressure Low pressure
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
24
2. EXTERNAL DIMENSIONS
Unit: mm
PURY-EM350,400,450YNW-A1(-BS)
<Wall height limit> Front :Up to the unit height
Back :Up to the unit height
Side :Up to the unit height
1. Required space around the unit
●In case of single installation
1 Secure enough space around the unit as shown in the figure below.
· With a space of at least
300mm to the wall on
the back of the unit
2 When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
2. Foundation work
1 Take into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
2 Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure.(Fig.A,B)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A,B)
4 Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts.(Fig.C,D)
5
To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
7 Refer to the Installation Manual when installing units on an installation base.
●In case of collective installation
· With a space of at least
100mm to the wall on
the back of the unit
1 When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>
to the figures that are marked with an asterisk.
4 If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each six units.
Front
Front
<Top view>
<Unit:mm>
<Top view>
M10 anchor bolt
<field supply required>
Fixing plate
<field supply required>
<To be left open>
Front
Wall <H>
<To be left open>
Front
<Unit:mm>
M10 anchor bolt
<field supply required>
Wall <H>
<To be left open>
<To be left open>
<To be left open>
Front
Wall <H>
Wall <H>
Wall <H>
Wall <H>
Front
Front
<To be left open>
Wall <H>
Front
Wall <H>
<To be left open>
<To be left open>
Front
Front
Front
Wall <H>
Wall <H>
Front
<To be left open>
<To be left open>
Fig.A (without detachable legs)
Fig.B (with detachable legs)
Fig.C (without detachable legs)
Detachable leg
<Side view>
Front
15 min.*
50 min.* 50 min.*
100 min.*450 min.*
300 min.*
100 min.
30 min.
450 min.450 min.* 450 min.
100 min.*
450 min.* 100 min.*
450 min.*
1000 min.*
900 min.
300 min.*
900 min.
300 min.*300 min.*
15 min.*
450 min.450 min.
450 min.* 300 min.*
15 min.*
30mm max.
30mm max.
Unit height
h
H
Unit height
h
H
Fixing plate
<field supply required>
Detachable leg
Fig.D (with detachable legs)
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
MEES18K068
25