9-1. Power supply for Outdoor unit ......................................................................................................... 69
9-2. Power cable specifications .............................................................................................................. 70
9-3. Power supply examples ................................................................................................................... 71
10.M-NET CONTROL ................................................................................................................................... 72
in.73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3/16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variatio n.
2
1. SPECIFICATIONS
Model PURY-M250YNW-A1 (-BS)
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW28.0
(Nominal)kcal/h25,000
BTU/h95,500
Power inputkW8.40
Current inputA14.1-13.4-12.9
EERkW/kW3.33
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW31.5
(Nominal)kcal/h27,100
BTU/h107,500
Power inputkW9.15
Current inputA15.4-14.6-14.1
COPkW/kW3.44
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/1~37
Sound pressure level (meas ured in anechoic room) *4 dB <A>60.5/61.0
Sound power level (measured in anechoic room) *4 dB <A>78.5/80.0
RefrigerantType x original chargeR32 x 5.2 kg (12 lbs)
ControlHBC controller
Net weightkg (lbs)227 (501)
Heat exchangerSalt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)-
Defrosting methodAuto-defrost mode (Reversed refrigerant cycle, Hot gas)
DrawingExternalWKL94T598
WiringWKE94G769
Standard attachmentDocumentInstallation Manual
Accessory-
Optional parts
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variation.
3
1. SPECIFICATIONS
Model PURY-M300YNW-A1 (-BS)
Number of HBC controllerSingle HBCDouble HBC
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW33.5
(Nominal)kcal/h30,000
Power inputkW11.659.88
Current inputA19.6-18.6-18.016.6-15.8-15.2
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW37.5
(Nominal)kcal/h32,300
PURY-M-YNW-A1, EM-YNW-A1
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10 ~125/2~45
Sound pressure level (measured in anechoic room) *4 dB <A>61.0/67.0
Sound power level (measured in anechoic room) *4 dB <A>80.0/86.5
in.73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3/16
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variatio n.
4
1. SPECIFICATIONS
Model PURY-M350YNW-A1 (-BS)
Number of HBC controllerSingle HBCDouble HBC
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW40.0
(Nominal)kcal/h35,000
Power inputkW14.9312.15
Current inputA25.2-2 3.9-23.020.5-19.4-18.7
EERkW/kW2.673.29
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW45.0
(Nominal)kcal/h38,700
Power inputkW13.1412.16
Current inputA22.1-2 1.0-20.320.5-19.5-18.7
COPkW/kW3.423.70
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/1~35
Sound pressure level (meas ured in anechoic room) *4 dB <A>62 .5/64.0
Sound power level (measured in anechoic room) *4 dB <A>81.0/83.0
in.73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3/16
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variation.
5
1. SPECIFICATIONS
Model PURY-M400YNW-A1 (-BS)
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW45.0
(Nominal)kcal/h40,000
Power inputkW15.15
Current inputA25.5-24.2-23.4
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW50.0
(Nominal)kcal/h45,000
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
PURY-M-YNW-A1, EM-YNW-A1
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/1~40
Sound pressure level (measured in anechoic room) *4 dB <A>65.0/69.0
Sound power level (measured in anechoic room) *4 dB <A>83.0/88.0
in.73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3/16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variatio n.
6
1. SPECIFICATIONS
Model PURY-M450YNW-A1 (-BS)
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW50.0
(Nominal)kcal/h45,000
BTU/h170,600
Power inputkW15.47
Current inputA26.1-24.8-23.9
EERkW/kW3.23
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW56.0
(Nominal)kcal/h50,000
BTU/h191,100
Power inputkW16.18
Current inputA27.3-25.9-25.0
COPkW/kW3.46
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/1~45
Sound pressure level (meas ured in anechoic room) *4 dB <A>65.5/70.0
Sound power level (measured in anechoic room) *4 dB <A>83.0/89.0
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variation.
7
1. SPECIFICATIONS
Model PURY-M500YNW-A1 (-BS)
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW56.0
(Nominal)kcal/h50,000
Power inputkW22.25
Current inputA37.5-35.6-34.3
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW63.0
(Nominal)kcal/h54,200
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
PURY-M-YNW-A1, EM-YNW-A1
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/1~50
Sound pressure level (measured in anechoic room) *4 dB <A>63.5/64.5
Sound power level (measured in anechoic room) *4 dB <A>82.0/84.0
in.73-3/16 (70-13/16 without legs) x 68-15/16 x 29-3/16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variatio n.
8
1. SPECIFICATIONS
Model PURY-EM200YNW-A1 (-BS)
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW22.4
(Nominal)kcal/h20,000
BTU/h76,400
Power inputkW5.13
Current inputA8.6-8.2-7.9
EERkW/kW4.36
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW25.0
(Nominal)kcal/h21,500
BTU/h85,300
Power inputkW6.23
Current inputA10.5-9.9-9.6
COPkW/kW4.01
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/1~30
Sound pressure level (meas ured in anechoic room) *4 dB <A>59.0/59.0
Sound power level (measured in anechoic room) *4 dB <A>76.0/78.0
RefrigerantType x original chargeR32 x 5.2 kg (12 lbs)
ControlHBC controller
Net weightkg (lbs)231 (510)
Heat exchangerSalt-resistant cross fin & aluminium tube
HIC circuit (HIC: Heat Inter-Changer)-
Defrosting methodAuto-defrost mode (Reversed refrigerant cycle, Hot gas)
DrawingExternalWKL94T601
WiringWKE94G769
Standard attachmentDocumentInstallation Manual
Accessory-
Optional parts
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variation.
9
1. SPECIFICATIONS
Model PURY-EM250YNW-A1 (-BS)
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW28.0
(Nominal)kcal/h25,000
Power inputkW7.69
Current inputA12.9-12.3-11.8
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW31.5
(Nominal)kcal/h27,100
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
PURY-M-YNW-A1, EM-YNW-A1
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/1~37
Sound pressure level (measured in anechoic room) *4 dB <A>60.5/61.0
Sound power level (measured in anechoic room) *4 dB <A>78.5/80.0
in.73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3 /16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variatio n.
10
1. SPECIFICATIONS
Model PURY-EM300YNW-A1 (- BS)
Number of HBC controllerSingle HBCDouble HBC
Power source3-ph ase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW33.5
(Nominal)kcal/h30,000
Power inputkW10.038.52
Current inputA16.9-16.0-15.514.3-13.6-13.1
EERkW/kW3.333.93
Temp. range ofIndoorW.B.15.0~24 .0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW37.5
(Nominal)kcal/h32,300
Power inputkW10.469.93
Current inputA17.6-16.7-16.116.7-15.9-15.3
COPkW/kW3.583.77
Temp. range ofIndoorD.B.15.0~27.0° C (59~81°F)
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/2~45
Sound pressure level (measured in anechoic room) *4 dB <A>61.0/67.0
Sound power level (measured in anechoic room) *4dB <A>80.0/86.5
in.73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3/16
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
PURY-M-YNW-A1, EM-YNW-A1
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variation.
11
1. SPECIFICATIONS
Model PURY-EM350YNW-A1 (-BS)
Number of HBC controllerSingle HBCDouble HBC
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW40.0
(Nominal)kcal/h35,000
Power inputkW13.9111.33
Current inputA23.4-22.3-21.519.1-18.1-17.5
Temp. range ofIndoorW.B.15.0 ~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW45.0
(Nominal)kcal/h38,700
PURY-M-YNW-A1, EM-YNW-A1
Temp. range ofIndoorD.B.15.0~27. 0°C (59~81°F)
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/1~35
Sound pressure level (measured in anechoic room) *4 dB <A>62.5/64.0
Sound power level (measured in anechoic room) *4dB <A>81.0/83.0
in.73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3/16
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variatio n.
12
1. SPECIFICATIONS
Model PURY-EM400YNW-A1 (-BS)
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW45.0
(Nominal)kcal/h40,000
BTU/h153,500
Power inputkW13.84
Current inputA23.3-22.1-21.3
EERkW/kW3.25
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW50.0
(Nominal)kcal/h45,000
BTU/h170,600
Power inputkW13.88
Current inputA23.4-22.2-21.4
COPkW/kW3.60
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~1 25/1~40
Sound pressure level (meas ured in anechoic room) *4 dB <A>65.0/69.0
Sound power level (measured in anechoic room) *4dB <A>83.0/88.0
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variation.
13
1. SPECIFICATIONS
Model PURY-EM450YNW-A1 (-BS)
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW50.0
(Nominal)kcal/h45,000
Power inputkW15.24
Current inputA25.7-24.4-23.5
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW56.0
(Nominal)kcal/h50,000
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
PURY-M-YNW-A1, EM-YNW-A1
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~125/1~45
Sound pressure level (measured in anechoic room) *4 dB <A>65.5/70.0
Sound power level (measured in anechoic room) *4 dB <A>83.0/89.0
in.73-3/16 (70-13/16 without legs) x 48-7/8 x 29-3 /16
Main HBC controller: CMB-WM108,1016V-AA
Sub HBC controller: CMB-WM108,1016V-AB
R2-Series
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operat ion.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain restrictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, above specifications may be subje ct to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variatio n.
14
1. SPECIFICATIONS
Model PURY-EM500YNW-A1 (-BS)
Power source3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW56.0
(Nominal)kcal/h50,000
BTU/h191,100
Power inputkW18.06
Current inputA30.4-28.9-27.9
EERkW/kW3.10
Temp. range ofIndoorW.B.15.0~24.0°C (59~75°F)
cooling *3 OutdoorD.B.-5.0~52.0°C (23~126°F)
Heating capacity*2 kW63.0
(Nominal)kcal/h54,200
BTU/h215,000
Power inputkW17.45
Current inputA29.4-27.9-26.9
COPkW/kW3.61
Temp. range ofIndoorD.B.15.0~27.0°C (59~81°F)
heating *3 OutdoorW.B.-20.0~15.5°C (-4~60°F)
Indoor unitTotal capacity50~150% of outdoor unit capacity
connectableModel/QuantityWP10~125, W10~1 25/1~50
Sound pressure level (meas ured in anechoic room) *4 dB <A>63.5/64.5
Sound power level (measured in anechoic room) *4dB <A>82.0/84.0
RemarksDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
Notes:Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subj ect to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operation.
4.Cooling mode/Heating mode
5.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
6.R32 is flammable, and certain rest rictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
MEES18K068
referred to the Installation Manual.
Due to continuing improvement, a bove specifications may be subject to change without notice.
BTU/h =kW x 3,412
cfm=m3/min x 35.31
lbs=kg/0.4536
*Above specification data is
subject to rounding variation.
15
2. EXTERNAL DIMENSIONS
PURY-M200, 250, 300YNW-A1(-BS)
Unit: mm
1
3
4
7
Intake
air
Front view
Intake
air
Intake
air
Discharge air
Left side view
Rear view
2
5
6
8
(Mounting pitch)
Bottom view
(Mounting pitch)
2×5-ø4.6 Hole
(Make hole at the plastic fan guard
for snow hood attachment)
<Snow hood attachment hole>
Top view
Sling hole
Detachable leg
(front and back, 2 points)
Note 2*
2×2-14×31 Oval hole
2×2-14×20 Oval hole(without detachable leg)
Intake
air
Refrigerant
service valve
<High pressure>
Refrigerant
service valve
<Low pressure>
Service
panel
Control box
(INV Box)
Control box
(MAIN Box)
For transmission cables
For wires
For pipes
NO.
UsageSpecifications
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Bottom through hole
Front through hole
148 × 84 Knockout hole
ø65 or ø40 Knockout hole
ø52 or ø27 Knockout hole
ø65 Knockout hole
ø52 Knockout hole
ø34 Knockout hole
150 × 94 Knockout hole
Connecting pipe specifications
ø34 Knockout hole
Note 1.Please refer to the next page for information regarding necessary
spacing around the unit and foundation work.
2.The detachable leg can be removed at site.
3.At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of refrigerant
service valve under 120°C.
4.This unit has restrictions for the safety, so refer to
SAFETY HANDLING FOR R32 or the Installation Manual.
*1 Connect the refrigerant pipe to the service valve