Please read the following safety precautions carefully before installing the unit to ensure safety.
Indicates a risk of death or serious injury.
Indicates a risk of serious injury or structural damage.
Make sure that this manual is passed on to the end user to retain for future reference.
Retain this manual for future reference. When the unit is reinstalled or repaired, have this manual available to those who pro-
vide these services. Make sure that this manual is passed on to any future users.
All electric work must be performed by qualified personnel.
Air tightness test must be performed by qualified personnel.
[1] General Precautions
General Precautions
Do not use refrigerant other than the type indicated in the manuals provided with the
unit and on the nameplate. Doing so may
cause the unit or pipes to burst, or result in
explosion or fire during use, during repair,
or at the time of disposal of the unit. It may
also be in violation of applicable laws. MITSUBISHI ELECTRIC CORPORATION cannot
be held responsible for malfunctions or accidents resulting from the use of the wrong
type of refrigerant.
Do not install the unit in a place where large
amounts of oil, steam, organic solvents, or
corrosive gases, such as sulfuric gas, are
present or where acidic/alkaline solutions
or sprays containing sulfur are used frequently. These substances can compromise the performance of the unit or cause
certain components of the unit to corrode,
which can result in refrigerant leakage, water leakage, injury, electric shock, malfunctions, smoke, or fire.
Do not try to defeat the safety features of the
unit or make unauthorized setting changes.
Forcing the unit to operate the unit by defeating the safety features of the devices
such as the pressure switch or the temperature switch, making unauthorized changes
to the switch settings, or using accessories
other than the ones recommended by Mitsubishi Electric may result in smoke, fire, or
explosion.
To reduce the risk of shorting, current leakage, electric shock, malfunctions, smoke, or
fire, do not splash water on electric parts.
To reduce the risk of electric shock, malfunctions, smoke or fire, do not operate the
switches/buttons or touch other electrical
parts with wet hands.
To reduce the risk of pipe burst and explosion, do not allow gas refrigerant and refrigerant oil to be trapped in the refrigerant
circuit.
To reduce the risk of burns or frost bites, do
not touch the refrigerant pipes or refrigerant
circuit components with bare hands during
and immediately after operation.
To reduce the risk of burns, do not touch
any electrical parts with bare hands during
or immediately after stopping operation.
To reduce the risk of injury from falling
tools, keep children away while installing,
inspecting, or repairing the unit.
Keep the space well ventilated. Refrigerant
can displace air and cause oxygen starvation. If leaked refrigerant comes in contact
with a heat source, toxic gas may be generated.
i
Always replace a fuse with one with the correct current rating. The use of improperly
rated fuses or a substitution of fuses with
steel or copper wire may result in bursting,
fire or explosion.
To reduce the risk of electric shock, smoke,
and fire due to infiltration of dust and water,
properly install all required covers.
To reduce the risk of electric shock, smoke,
and fire due to infiltration of dust and water,
properly install all required terminal block
covers and insulation sheets.
To reduce the risk of electric shock, smoke,
and fire due to infiltration of dust and water,
properly install all required covers and panels on the terminal box and control box.
To reduce the risk of injury from units falling
or falling over, periodically check the installation base for damage.
Consult an authorized agency for the proper
disposal of the unit. Refrigerant oil and refrigerant that may be left in the unit pose a
risk of fire, explosion, or environmental pollution.
To reduce the risk of fire or explosion, do
not place flammable materials or use flammable sprays around the unit.
To reduce the risk of being caught in rotating parts, electric shock, and burns, do not
operate the unit without all required panels
and guards being installed.
To reduce the risk of injury, do not sit,
stand, or place objects on the unit.
The unit described in this manual is not intended for use with food, animals, plants,
precision instruments, or art work.
To reduce the risk of water leakage and malfunctions, do not turn off the power immediately after stopping operation. Leave the
unit turned on for at least 5 minutes before
turning off the power.
Do not install the unit over things that are
vulnerable to water damage from condensation dripping.
To reduce the risk of injury, electric shock,
and malfunctions, do not touch or allow cables to come in contact with the edges of
components.
[2] Transportation and Installa tion
To reduce the risk of injury, do not touch the
heat exchanger fins or sharp edges of components with bare hands.
Always wear protective gears when touching electrical components on the unit. Several minutes after the power is switched off,
residual voltage may still cause electric
shock.
To reduce the risk of electric shock and
burns, always wear protective gear when
working on units.
To reduce the risk of injury, do not insert fingers or foreign objects into air inlet/outlet
grills. If the unit is left on a damaged base, it
may fall and cause injury.
To reduce the risk of injury, always wear
protective gear when working on units.
Do not release refrigerant into the atmosphere. Collect and reuse the refrigerant, or
have it properly disposed of by an authorized agency. Refrigerant poses environmental hazards if released into the air.
Transportation and Installation
Lift the unit by placing the slings at designated locations. Support the outdoor unit
securely at four points to keep it from slipping and sliding. If the unit is not properly
supported, it may fall and cause personal
injury.
ii
To reduce the risk of injury, do not carry the
product by the PP bands that are used on
some packages.
[3] Installation
Installation
To reduce the risk of injury, products weighing 20 kg or more should be carried by two
or more people.
Do not install the unit where there is a risk
of leaking flammable gas.
If flammable gas accumulates around the
unit, it may ignite and cause a fire or explosion.
To reduce the risk of injury from coming in
contact with units, install units where they
are not accessible to people other than
maintenance personnel.
To reduce the risk of injury, properly dispose of the packing materials so that children will not play with them.
Properly dispose of the packing materials.
Plastic bags pose suffocation hazard to
children.
All drainage work should be performed by
the dealer or qualified personnel according
to the instructions detailed in the Installation Manual. Improper drainage work may
cause water leakage and resultant damage
to the furnishings.
Consult your dealer and take appropriate
measures to safeguard against refrigerant
leakage and resultant oxygen starvation. An
installation of a refrigerant gas detector is
recommended.
Any additional parts must be installed by
the dealer or qualified personnel. Only use
the parts specified by Mitsubishi Electric.
Installation by unauthorized personnel or
use of unauthorized parts or accessories
may result in water leakage, electric shock,
or fire.
Take appropriate safety measures against
wind gusts and earthquakes to prevent the
unit from toppling over and causing injury.
To reduce the risk of injury from units falling
or falling over, install the unit on a surface
that is strong enough to support its weight.
To reduce the risk of injury from units falling
or falling over, periodically check the installation base for damage.
Remove packing materials from the unit before operating the unit. Note that some accessories may be taped to the unit. Properly
install all accessories that are required. Failing to remove the packing materials or failing to install required accessories may
result in refrigerant leakage, oxygen deprivation, smoke, or fire.
Do not install the unit over things that are
vulnerable to water damage. Provide an adequate collective drainage system for the
drain water from unit as necessary.
Do not install the unit over things that are
vulnerable to water damage. When the indoor humidity exceeds 80% or if the drain
water outlet becomes clogged, condensation may drip from the indoor unit onto the
ceiling or floor.
To reduce the risk of damage to the unit and
resultant electric leak and electric shock,
keep small animals, snow, and rain water
from entering the unit by closing the gap in
the pipe and wire access holes.
To reduce the risk of rain water or drain water from entering the room and damaging
the interior, drainage work must be performed by your dealer or qualified personnel according to the instructions detailed in
the Installation Manual.
iii
To reduce the risk of drain water overflow,
install the unit horizontally, using a level.
[4] Piping Work
Piping Work
To reduce the risk of injury, including frost
bites, that may result from being blasted
with refrigerant, use caution when operating the refrigerant service valve. If refrigerant leaks out and comes in contact with an
open flame, toxic gases may be generated.
To reduce the risk of refrigerant catching
fire and causing burns, remove the refrigerant gas and the residual refrigerant oil in the
pipes before heating them.
To reduce the risk of pipe damage, refrigerant leakage, and oxygen deprivation, use
pipes that meet the pipe thickness specifications, which vary by the type of refrigerant used, pipe diameter, and pipe material.
To reduce the risk of pipe burst or explosion, evacuate the refrigerant circuit using a
vacuum pump, and do not purge the system
with refrigerant.
To reduce the risk of explosion and deterioration of refrigerant oil caused by chloride,
do not use oxygen, flammable gas, or refrigerant that contains chloride as a pressurizing gas.
To prevent explosion, do not heat the unit
with refrigerant gas in the refrigerant circuit.
To reduce the risk of refrigerant leakage and
resultant oxygen deprivation, use the flare
nut with holes that is supplied with the refrigerant service valve.
To reduce the risk of refrigerant leakage and
resultant oxygen deprivation, use the flare
nut that is supplied with the unit or its equivalent that meets applicable standards.
To reduce the risk of damage to the unit,
and resultant refrigerant leakage and oxygen deprivation, tighten flare nuts to a specified torque.
To reduce the risk of oxygen deprivation
and gas poisoning, check for gas leakage
and keep fire sources away.
Insulate pipe connections after completing
the air tightness test. Performing an air
tightness test with the pipe being insulated
may lead to failure to detect refrigerant leakage and cause oxygen deprivation.
To reduce the risk of pipe damage and resultant refrigerant leakage and oxygen deprivation, keep the field-installed pipes out
of contact with the edges of components.
To reduce the risk of pipe bursting and explosion due to abnormal pressure rise, do
not allow any substances other than R410A
(such as air) to enter the refrigerant circuit.
[5] Wiring Work
Wiring Work
To reduce the risk of wire breakage, overheating, smoke, and fire, keep undue force
from being applied to the wires.
To reduce the risk of water leakage and resultant damage to the furnishings, drain
piping work must be performed by your
dealer or qualified personnel according to
the instructions detailed in the Installation
Manual.
To keep the ceiling and floor from getting
wet due to condensation, properly insulate
the pipes.
To reduce the risk of wire breakage, overheating, smoke, or fire, properly secure the
cables in place and provide adequate slack
in the cables so as not to stress the terminals.
iv
To reduce the risk of injury or electric
shock, switch off the main power before
performing electrical work.
All electric work must be performed by a
qualified electrician according to the local
regulations, standards, and the instructions
detailed in the Installation Manual. Capacity
shortage to the power supply circuit or improper installation may result in malfunction, electric shock, smoke, or fire.
To reduce the risk of electric shock, smoke,
or fire, install an earth leakage breaker on
the power supply to each unit.
To reduce the risk of electric shock, smoke,
or fire, install an inverter circuit breaker on
the power supply to each unit. (Applicable
to inverter units only)
Use properly rated breakers and fuses
(earth leakage breaker, local switch <switch
+ fuse>, no-fuse breaker). The use of a
breaker with a breaking capacity greater
than the specified capacity may cause electric shock, malfunctions, smoke, or fire.
Use properly rated breakers and fuses (inverter circuit breaker, local switch <switch +
fuse>, no-fuse breaker). The use of a breaker with a breaking capacity greater than the
specified capacity may cause electric
shock, malfunctions, smoke, or fire. (Applicable to inverter units only)
To reduce the risk of current leakage, overheating, smoke, or fire, use properly rated
cables with adequate current carrying capacity.
Proper grounding must be provided by a licensed electrician.
Do not connect the grounding wire to a gas
pipe, water pipe, lightning rod, or telephone
wire. Improper grounding may result in
electric shock, smoke, fire, or malfunction
due to electrical noise interference.
To reduce the risk of current leakage, wire
breakage, smoke, or fire, keep the wiring
out of contact with the refrigerant pipes and
other parts, especially sharp edges.
[6] Relocation and Repairs
Relocation and Repairs
To reduce the risk of refrigerant leakage,
water leakage, injury, electric shock, and
fire, units should only be moved or repaired
by your dealer or qualified personnel.
To reduce the risk of wire shorting, electric
shock, malfunctions, or fire, keep circuit
boards dust free, and do not touch them
with your hands or tools.
[7] Additional Precautions
To reduce the risk of wire shorting, electric
leak, electric shock, smoke, or fire, do not
perform maintenance work in the rain.
To reduce the risk of injury, electric shock,
and fire, properly reinstall all removed components after completing repair work.
To reduce the risk of refrigerant and water
leakage, check the pipe supports and insulation for damage during inspection or repair, and replace or repair the ones that are
found to be deteriorated.
Additional Precautions
To avoid damage to the unit, use appropriate tools to install, inspect, or repair the
unit.
v
To reduce the risk or malfunction, turn on
the power at least 12 hours before starting
operation, and leave the power turned on
throughout the operating season.
To reduce the risk of the vacuum pump oil
backflowing into the refrigerant cycle and
causing the refrigerant oil to deteriorate,
use a vacuum pump with a check valve.
Recover all refrigerant in the units, and dispose of it properly according to any applicable laws and regulations.
To reduce the risk of deterioration of refrigerant oil and compressor malfunctions
caused by a refrigerant that contains chloride, such as R22, only use R410A.
Provide a maintenance access to allow for
the inspection of pipes above the ceiling or
the buried pipes.
Take appropriate measures against electrical noise interference when installing the air
conditioners in hospitals or facilities with
radio communication capabilities. Inverter,
high-frequency medical, or wireless communication equipment as well as power
generators may cause the air conditioning
system to malfunction. Air conditioning
system may also adversely affect the operation of these types of equipment by creating
electrical noise.
To reduce the risk of damage to the unit,
leave the valves on the unit closed until refrigerant charging is completed.
Have a set of tools for exclusive use with
R410A. Consult your nearest Mitsubishi
Electric Dealer.
Keep dust, dirt, and water off charging hose
and flare tool. Infiltration of dust, dirt, or water into the refrigerant circuit may cause the
refrigerant oil to deteriorate or damage the
compressor.
Use refrigerant piping and couplings that
meet the applicable standards. For refrigerant pipes, use pipes made of phosphorus
deoxidized copper. Keep the inner and outer surfaces of pipes and couplings clean
and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and
moisture. Failure to follow these directions
may result in the deterioration of refrigerant
oil or compressor damage.
Store the piping materials indoors, and
keep both ends of the pipes sealed until immediately before brazing. Keep elbows and
other joints in plastic bags. Infiltration of
dust, dirt, or water into the refrigerant circuit may cause the refrigerant oil to deteriorate or damage the compressor.
Place a wet towel on the refrigerant service
valve before brazing the pipes to keep its
temperature from rising above 120ºC and
damaging the surrounding equipment.
Direct the blazing torch flame away from the
adjacent cables and sheet metal to keep
them from being overheated and damaged.
Prepare tools for exclusive use with R410A.
Do not use the following tools if they have
been used with the conventional refrigerant
(R22): gauge manifold, charging hose, refrigerant leak detector, check valve, refrigerant charge spout, vacuum gauge, and
refrigerant recovery equipment. R410A
does not contain chloride, so leak detectors
for use with older types of refrigerants will
not detect an R410A leak. Infiltration of the
residual refrigerant, refrigerant oil, or water
on these tools may cause the refrigerant oil
in the new system to deteriorate or damage
the compressor.
Apply ester oil, ether oil, or a small amount
of alkyl benzene to flares and flanges. The
use and accidental infiltration of mineral oil
into the system may cause the refrigerant
oil to deteriorate or damage the compressor.
To reduce the risk of oxidized film from entering the refrigerant pipe and causing the
refrigerant oil to deteriorate or damaging
the compressor, braze pipes under nitrogen
purge.
Do not use the existing refrigerant piping. A
large amount of chloride that is contained in
the residual refrigerant and refrigerant oil in
the existing piping may cause the refrigerant oil in the new unit to deteriorate or damage the compressor.
Charge refrigerant in the liquid state. If refrigerant is charged in the gas phase, the
composition of the refrigerant in the cylinder will change, compromising the unit's
performance.
vi
Do not use a charging cylinder. The use of a
charging cylinder will change the composition of the refrigerant, compromising the
unit's performance.
Charge the system with an appropriate
amount of refrigerant in the liquid phase.
Refer to the relevant sections in the manuals to calculate the appropriate amount of
refrigerant to be charged. Refrigerant overcharge or undercharge may result in performance drop or abnormal stop of operation.
To reduce the risk of power capacity shortage, always use a dedicated power supply
circuit.
To reduce the risk of both the breaker on the
product side and the upstream breaker from
tripping and causing problems, split the
power supply system or provide protection
coordination between the earth leakage
breaker and no-fuse breaker.
Have a backup system, if failure of the unit
has a potential for causing significant problems or damages.
vii
viii
CONTENTS
Chapter 1Check Before Servicing
1-1Preparation for Piping Work..................................................................................................................3
1-2Handling and Characteristics of Piping Materials, Refrigerant, and Refrigerant Oil ....................... 5
1-3Working with Refrigerant Piping.........................................................................................................10
1-4Precautions for Wiring......................................................................................................................... 15
6-1Read before Test Run ........................................................................................................................149
6-2MA and ME Remote Controller Functions and Specifications....................................................... 150
6-3Making the Group and Interlock Settings from an ME Remote Controller ...................................151
6-4Selecting Remote Controller Functions from an ME Remote Controller...................................... 155
6-5Making Interlock Settings from an MA Remote Controller............................................................. 157
6-6Changing the Room Temperature Detection Position.................................................................... 159
6-7Test Run Method ................................................................................................................................ 160
6-8Operation Characteristics and Refrigerant Charge ........................................................................161
6-9Evaluating and Adjusting Refrigerant Charge................................................................................. 161
6-10 The Following Symptoms Are Normal ............................................................................................. 166
6-11 Standard Operation Data (Reference Data) .....................................................................................167
Chapter 7Troubleshooting Using Error Codes
7-1Error Code and Preliminary Error Code Lists .................................................................................175
7-2Error Code Definitions and Solutions: Codes [0 - 999]...................................................................179
HWE13080GB
CONTENTS
7-3Error Code Definitions and Solutions: Codes [1000 - 1999]........................................................... 180
7-4Error Code Definitions and Solutions: Codes [2000 - 2999]........................................................... 184
7-5Error Code Definitions and Solutions: Codes [3000 - 3999]........................................................... 191
7-6Error Code Definitions and Solutions: Codes [4000 - 4999]........................................................... 192
7-7Error Code Definitions and Solutions: Codes [5000 - 5999]........................................................... 210
7-8Error Code Definitions and Solutions: Codes [6000 - 6999]........................................................... 223
7-9Error Code Definitions and Solutions: Codes [7000 - 7999]........................................................... 239
Chapter 8Troubleshooting Based on Observed Symptoms
8-17 BC Controller Maintenance Instructions..........................................................................................319
8-18 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit..................... 322
Chapter 9LED Status Indicators on the Outdoor Unit Circuit Board
9-1LED Status Indicators ........................................................................................................................ 325
9-2LED Status Indicators Table .............................................................................................................328
HWE13080GB
Chapter 1Check Before Servicing
1-1Preparation for Piping Work ................................................................................................................ 3
1-1-1Read before Servicing ............................................................................................................................ 3
1-2-2Storage of Piping Materials..................................................................................................................... 7
1-3-2Air Tightness Test ................................................................................................................................. 11
1-4Precautions for Wiring ....................................................................................................................... 15
HWE13080GB
- 1 -
HWE13080GB
- 2 -
[1-1 Preparation for Piping Work ]
CAUTION
1 Check Before Servicing
1-1Preparation for Piping Work
1-1-1Read before Servicing
1. Check the type of refrigerant used in the system to be serviced.
Refrigerant Type
Multi air conditioner for building application CITY MULTI H2i (Hyper Heating Inverter) R2 TKMU-A-H, YKMU-A series : R410A
2. Check the symptoms exhibited by the unit to be serviced.
Refer to this service handbook for symptoms relating to the refrigerant cycle.
3. Thoroughly read the safety precautions at the beginning of this manual.
4. Preparing necessary tools: Prepare a set of tools to be used exclusively with each type of refrigerant.
For information about the correct use of tools, refer to the following page(s). [1-1-2 Tool Preparation](page 4)
5. Verification of the connecting pipes: Verify the type of refrigerant used for the unit to be moved or replaced.
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free
of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
6. If there is a leak of gaseous refrigerant and the remaining refrigerant is exposed to an open flame, a poisonous gas
hydrofluoric acid may form. Keep workplace well ventilated.
1 Check Before Servicing
Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.
The use of refrigerant that contains chloride, such as R22, will cause the refrigerating machine oil to deteriorate.
HWE13080GB
- 3 -
[1-1 Preparation for Piping Work ]
1-1-2Tool Preparation
Prepare the following tools and materials necessary for installing and servicing the unit.
Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C)
1. To be used exclusively with R410A (not to be used if used with R22 or R407C)
Tools/MaterialsUseNotes
Gauge ManifoldEvacuation and refrigerant chargingHigher than 5.09MPa[738psi] on the
Charging HoseEvacuation and refrigerant chargingThe hose diameter is larger than the
Refrigerant Recovery CylinderRefrigerant recovery
Refrigerant CylinderRefrigerant chargingThe refrigerant type is indicated. The
Charging Port on the Refrigerant Cylinder Refrigerant chargingThe charge port diameter is larger
Flare NutConnection of the unit with the pipesUse Type-2 Flare nuts.
2. Tools and materials that may be used with R410A with some restrictions
high-pressure side
conventional model.
cylinder is pink.
than that of the current port.
Tools/MaterialsUseNotes
Gas Leak DetectorGas leak detectionThe ones for use with HFC refrigerant
may be used.
Vacuum PumpVacuum dryingMay be used if a check valve adapter
is attached.
Flare ToolFlare processingFlare processing dimensions for the
piping in the system using the new refrigerant differ from those of R22. Refer to the following page(s). [1-2-1
Piping Materials](page 5)
Refrigerant Recovery EquipmentRefrigerant recoveryMay be used if compatible with
R410A.
3. Tools and materials that are used with R22 or R407C that may also be used with R410A
Tools/MaterialsUseNotes
Vacuum Pump with a Check ValveVacuum drying
BenderBending pipes
Torque WrenchTightening flare nutsOnly the flare processing dimensions
for pipes that have a diameter of
ø12.7 (1/2") and ø15.88 (5/8") have
been changed.
Pipe CutterCutting pipes
Welder and Nitrogen CylinderWelding pipes
Refrigerant Charging MeterRefrigerant charging
Vacuum GaugeVacuum level check
4. Tools and materials that must not be used with R410A
Tools/MaterialsUseNotes
Charging CylinderRefrigerant chargingProhibited to use
Tools for R410A must be handled with special care to keep moisture and dust from infiltrating the cycle.
HWE13080GB
- 4 -
[1-2 Handling and Characteristics of Piping Materials, Refrigerant, and Refrigerant Oil ]
1-2Handling and Characteristics of Piping Materials,
Refrigerant, and Refrigerant Oil
1-2-1Piping Materials
Do not use the existing piping!
1. Copper pipe materials
O-material (Annealed)Soft copper pipes (annealed copper pipes). They can easily be bent with hands.
1/2H-material (Drawn)Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed)
at the same radial thickness.
The distinction between O-materials (Annealed) and 1/2H-materials (Drawn) is made based on the strength of the pipes them-
selves.
O-materials (Annealed) can easily be bent with hands.
1/2H-materials (Drawn) are considerably stronger than O-material (Annealed) at the same thickness.
2. Types of copper pipes
Maximum working pressureRefrigerant type
3.45 MPa [500psi]R22, R407C etc.
4.30 MPa [624psi]R410A etc.
1 Check Before Servicing
3. Piping materials/Radial thickness
Use refrigerant pipes made of phosphorus deoxidized copper.
The operation pressure of the units that use R410A is higher than that of the units that use R22.
Use pipes that have at least the radial thickness specified in the chart below.
(Pipes with a radial thickness of 0.7 mm or less may not be used.)
Pipe size (mm[in])Radial thickness (mm)Type
ø6.35[1/4"]0.8t
ø9.52[3/8"]0.8t
ø12.7[1/2"]0.8t
ø15.88[5/8"]1.0t
ø19.05[3/4"]1.0t
ø22.2[7/8"]1.0t
ø25.4[1"]1.0t
ø28.58[1-1/8"]1.0t
ø31.75[1-1/4"]1.1t
ø34.93[1-3/8"]1.1t
ø41.28[1-5/8"]1.2t
The pipes in the system that uses the refrigerant currently on the market are made with O-material (Annealed), even if the
pipe diameter is less than ø19.05 (3/4"). For a system that uses R410A, use pipes that are made with 1/2H-material (Drawn)
unless the pipe diameter is at least ø19.05 (3/4") and the radial thickness is at least 1.2t.
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
O-material (Annealed)
1/2H-material,
H-material (Drawn)
HWE13080GB
- 5 -
[1-2 Handling and Characteristics of Piping Materials, Refrigerant, and Refrigerant Oil ]
4. Thickness and refrigerant type indicated on the piping materials
Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5. Flare processing (O-material (Annealed) and OL-material only)
The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.
Flare processing dimensions (mm[in])
A dimension (mm)
Pipe size (mm[in])
R410AR22, R407C
ø6.35[1/4"]9.19.0
ø9.52[3/8"]13.213.0
ø12.7[1/2"]16.616.2
Dimension A
ø15.88[5/8"]19.719.4
ø19.05[3/4"]24.023.3
If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0
and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
6. Flare nut
The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.
Flare nut dimensions (mm[in])
B dimension (mm)
Pipe size (mm[in])
R410AR22, R407C
ø6.35[1/4"]17.017.0
ø9.52[3/8"]22.022.0
ø12.7[1/2"]26.024.0
Dimension B
ø15.88[5/8"]29.027.0
ø19.05[3/4"]36.036.0
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
HWE13080GB
- 6 -
[1-2 Handling and Characteristics of Piping Materials, Refrigerant, and Refrigerant Oil ]
1-2-2Storage of Piping Materials
1. Storage location
Store the pipes to be used indoors. (Warehouse at site or owner's warehouse)
If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe.
2. Sealing the pipe ends
1 Check Before Servicing
Both ends of the pipes should be sealed until just before brazing.
Keep elbow pipes and T-joints in plastic bags.
The new refrigerator oil is 10 times as hygroscopic as the conventional refrigerating machine oil (such as Suniso) and, if not
handled with care, could easily introduce moisture into the system. Keep moisture out of the pipes, for it will cause the oil to
deteriorate and cause a compressor failure.
1-2-3Pipe Processing
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Use a minimum amount of oil.
Use only ester oil, ether oil, and alkylbenzene.
HWE13080GB
- 7 -
[1-2 Handling and Characteristics of Piping Materials, Refrigerant, and Refrigerant Oil ]
1-2-4Characteristics of the New and Conventional Refrigerants
1. Chemical property
As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant.
However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will
accumulate at the bottom of the room and may cause hypoxia.
If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a confined area.
New Refrigerant (HFC type)Conventional Refriger-
ant (HCFC type)
R410AR407CR22
R32/R125R32/R125/R134aR22
Composition (wt%)(50/50)(23/25/52)(100)
Type of RefrigerantPseudo-azeotropic
Refrigerant
Non-azeotropic
Refrigerant
Single Refrigerant
ChlorideNot includedNot includedIncluded
Safety ClassA1/A1A1/A1A1
Molecular Weight72.686.286.5
Boiling Point (°C/°F)-51.4/-60.5-43.6/-46.4-40.8/-41.4
Steam Pressure
1.557/2260.9177/1330.94/136
(25°C,MPa/77°F,psi) (gauge)
Saturated Steam Density
(25°C,kg/m
3
/77°F,psi)
64.042.544.4
FlammabilityNonflammableNonflammableNonflammable
Ozone Depletion Coefficient (ODP)
Global Warming Coefficient (GWP)
*1
*2
Refrigerant Charging MethodRefrigerant charging in
Replenishment of Refrigerant after a Refrigerant
000.055
173015301700
the liquid state
Refrigerant charging in
the liquid state
Refrigerant charging in
the gaseous state
AvailableAvailableAvailable
Leak
*1 When CFC11 is used as a reference
*2 When CO
is used as a reference
2
2. Refrigerant composition
R410A is a pseudo-azeotropic HFC blend and can almost be handled the same way as a single refrigerant, such as R22. To
be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn
out, the composition of the remaining refrigerant will change and become unsuitable for use.
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced.
3. Pressure characteristics
The pressure in the system using R410A is 1.6 times as great as that in the system using R22.
Pressure (gauge)
Temperature (°C/°F)
R410AR407CR22
MPa/psiMPa/psiMPa/psi
-20/-40.30/440.18/260.14/20
0/320.70/1020.47/680.40/58
20/681.34/1940.94/1360.81/117
40/1042.31/3351.44/2091.44/209
60/1403.73/5412.44/3542.33/338
65/1494.17/6052.75/3992.60/377
HWE13080GB
- 8 -
[1-2 Handling and Characteristics of Piping Materials, Refrigerant, and Refrigerant Oil ]
1-2-5Refrigerant Oil
1. Refrigerating machine oil in the HFC refrigerant system
HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system.
Note that the ester oil used in the system has properties that are different from commercially available ester oil.
RefrigerantRefrigerating machine oil
R22 Mineral oil
R407CEster oil
R410A Ester oil
2. Effects of contaminants
*1
Refrigerating machine oil used in the HFC system must be handled with special care to keep contaminants out.
The table below shows the effect of contaminants in the refrigerating machine oil on the refrigeration cycle.
3. The effects of contaminants in the refrigerating machine oil on the refrigeration cycle.
CauseSymptomsEffects on the refrigerant cycle
Water infiltrationFrozen expansion valve
and capillary tubes
Clogged expansion valve and capillary tubes
Poor cooling performance
Compressor overheat
Motor insulation failure
Burnt motor
Coppering of the orbiting scroll
Lock
Burn-in on the orbiting scroll
Clogged expansion valve, capillary tubes, and
drier
Hydrolysis
Air infiltrationOxidization
Adhesion to expansion valve and capillary
tubes
Sludge formation and adhesion
Acid generation
Oxidization
Oil degradation
Poor cooling performance
Infiltration of
contaminants
Dust, dirt
Infiltration of contaminants into the compressor
Compressor overheat
Burn-in on the orbiting scroll
Sludge formation and adhesionClogged expansion valve and capillary tubes
Mineral oil
etc.
Poor cooling performance
Compressor overheat
Oil degradationBurn-in on the orbiting scroll
1 Check Before Servicing
*1. Contaminants is defined as moisture, air, processing oil, dust/dirt, wrong types of refrigerant, and refrigerating machine oil.
HWE13080GB
- 9 -
[1-3 Working with Refrigerant Piping ]
1-3Working with Refrigerant Piping
1-3-1Pipe Brazing
No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide
scale, water, and dust) out of the refrigerant system.
Example: Inside the brazed connection
Use of no inert gas during brazingUse of inert gas during brazing
1. Items to be strictly observed
Do not conduct refrigerant piping work outdoors if raining.
Use inert gas during brazing.
Use a brazing material (BCuP-3) that requires no flux when brazing between copper pipes or between a copper pipe and
copper coupling.
If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.
2. Reasons
The new refrigerating machine oil is 10 times as hygroscopic as the conventional oil and is more likely to cause unit failure if
water infiltrates into the system.
Flux generally contains chloride. Residual flux in the refrigerant circuit will cause sludge to form.
3. Notes
Do not use commercially available antioxidants because they may cause the pipes to corrode or refrigerating machine oil to
deteriorate.
HWE13080GB
- 10 -
[1-3 Working with Refrigerant Piping ]
1-3-2Air Tightness Test
No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak.
Halide torch R22 leakage detector
1 Check Before Servicing
1. Items to be strictly observed
Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight-
ness, taking temperature variations into account.
Refrigerant R410A must be charged in its liquid state (vs. gaseous state).
2. Reasons
Oxygen, if used for an air tightness test, poses a risk of explosion. (Only use nitrogen to check air tightness.)
Refrigerant R410A must be charged in its liquid state. If gaseous refrigerant in the cylinder is drawn out first, the composition
of the remaining refrigerant in the cylinder will change and become unsuitable for use.
3. Notes
Procure a leak detector that is specifically designed to detect an HFC leak. A leak detector for R22 will not detect an
HFC(R410A) leak.
1. Vacuum pump with a reverse-flow check valve (Photo1)
To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum
pump with a reverse-flow check valve.
A reverse-flow check valve may also be added to the vacuum pump currently in use.
2. Standard of vacuum degree (Photo 2)
Use a vacuum pump that attains 0.5Torr(65Pa) or lower degree of vacuum after 5 minutes of operation, and connect it directly
to the vacuum gauge. Use a pump well-maintained with an appropriate lubricant. A poorly maintained vacuum pump may not
be able to attain the desired degree of vacuum.
3. Required precision of vacuum gauge
Use a vacuum gauge that registers a vacuum degree of 5Torr(650Pa) and measures at intervals of 1Torr(130Pa). (A recommended vacuum gauge is shown in Photo2.)
Do not use a commonly used gauge manifold because it cannot register a vacuum degree of 5Torr(650Pa).
4. Evacuation time
After the degree of vacuum has reached 5Torr(650Pa), evacuate for an additional 1 hour. (A thorough vacuum drying re-
moves moisture in the pipes.)
Verify that the vacuum degree has not risen by more than 1Torr(130Pa) 1hour after evacuation. A rise by less than
1Torr(130Pa) is acceptable.
If the vacuum is lost by more than 1Torr(130Pa), conduct evacuation, following the instructions in section 6. Special vacuum
drying.
5. Procedures for stopping vacuum pump
To prevent the reverse flow of vacuum pump oil, open the relief valve on the vacuum pump side, or draw in air by loosening
the charge hose, and then stop the operation.
The same procedures should be followed when stopping a vacuum pump with a reverse-flow check valve.
6. Special vacuum drying
When 5Torr(650Pa) or lower degree of vacuum cannot be attained after 3 hours of evacuation, it is likely that water has pen-
etrated the system or that there is a leak.
If water infiltrates the system, break the vacuum with nitrogen. Pressurize the system with nitrogen gas to
0.5kgf/cm
2
G(0.05MPa) and evacuate again. Repeat this cycle of pressurizing and evacuation either until the degree of vac-
uum below 5Torr(650Pa) is attained or until the pressure stops rising.
Only use nitrogen gas for vacuum breaking. (The use of oxygen may result in an explosion.)
HWE13080GB
- 12 -
[1-3 Working with Refrigerant Piping ]
7. Triple Evacuation
The method below can also be used to evacuate the system.
Evacuate the system to 4,000 microns from both service valves. System manifold gauges must not be used to measure vac-
uum. A micron gauge must be used at all times. Break the vacuum with Nitrogen (N2) into the discharge service valve to 0
PSIG.
Evacuate the system to 1,500 microns from the suction service valve. Break the vacuum with Nitrogen (N2) into the discharge
service valve to 0 PSIG.
Evacuate the system to 500 microns. System must hold the vacuum at 500 microns for a minimum of 1 hour.
Conduct a rise test for a minimum of 30 minutes
8. Notes
To evacuate air from the entire system
Applying a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1
and 2) is not enough to attain the desired vacuum pressure.
Be sure to apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure
sides (BV1 and 2) and also through the check joints on the high and low pressure sides (CJ1 and 2).
To evacuate air only from the outdoor units
Apply a vacuum through the check joints on the high and low pressure sides (CJ1, and 2).
To evacuate air from the indoor units and extension pipes
Apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1
and 2).
1 Check Before Servicing
HWE13080GB
- 13 -
[1-3 Working with Refrigerant Piping ]
1-3-4Refrigerant Charging
Cylinder with a siphon
Cylinder without a siphon
Cylin-
Cylin-
der
der
Cylinder color R410A is pink.Refrigerant charging in the liquid state
ValveValve
liquid
liquid
1. Reasons
R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled
the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid
phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and become unsuitable for use.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check
the type of the cylinder on the label before use.
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in
the liquid state.)
Refer to the following page(s).[8-14 Measures for Refrigerant Leakage](page 311)
HWE13080GB
- 14 -
[1-4 Precautions for Wiring ]
1-4Precautions for Wiring
Control boxes house high-voltage and high-temperature electrical parts.
They may still remain energized or hot after the power is turned off.
When opening or closing the front cover of the control box, keep out of contact with the internal parts.
Before inspecting the inside of the control box, turn off the power, leave the unit turned off for at least 10 minutes, and check
that the voltage of the electrolytic capacitor (inverter main circuit) has dropped to 20 VDC or less.
It will take approximately 10 minutes until the voltage is discharged after power off.
Disconnect the outdoor unit fan board connector (CNINV) before performing maintenance work.
Before connecting or disconnecting the connector, check that the outdoor unit fan is stopped and that the voltage of the main
circuit capacitor has dropped to 20 VDC or below.
If the outdoor unit fan is rotated by external forces such as strong winds, the main circuit capacitor can be charged and cause
an electric shock.
Refer to the wiring nameplate for details.
Reconnect the connector (CNINV) to the fan board after completion of maintenance work.
When the unit is turned on, the compressor will remain energized even when it is stopped to vaporize the liquid refrigerant
that accumulates in the compressor.
Before connecting wiring to TB7, check that the voltage has dropped below 20 VDC.
When a system controller is connected to the centralized control transmission cable to which power is supplied from the out-
door unit (power jumper on the outdoor unit is connected to CN40), be aware that power can be supplied to the centralized
control transmission and the system controller may detect an error and send an error notice if the outdoor unit fan is rotated
by external forces, such as strong winds, even when power to the outdoor unit is turned off.
When replacing the internal electrical components of the control box, tighten the screws to the recommended tightening
torque as specified below.
Recommended tightening torque for the internal electrical components of the control box
1 Check Before Servicing
ScrewRecommended tightening torque (N·m)
M30.69
M41.47
M52.55
M62.75
M86.20
∗1 When replacing semiconductor modules (e.g., diode stack, IPM, INV board (with IPM), fan board (with IPM)), apply heat-
sink silicone evenly to the mounting surface of the semiconductor module (or the semiconductor module on the back of
the circuit board). Next, tighten the screws holding the semiconductor module to one-third of the specified torque, and then
tighten the screws to the specified torque.
∗2 Deviating from the recommended tightening torque may cause damage to the unit or its parts.
Take the following steps to ensure that the screws are properly tightened.
1) Ensure that the spring washers are parallel to the terminal block.
Even if the tightening torque is observed, if the washers are not parallel to the terminal block, then the semiconductor module
is not installed properly.
Loose screws
Proper installation
Spring washers are parallel to
the terminal block
HWE13080GB
- 15 -
[1-4 Precautions for Wiring ]
2) Check the wires are securely fastened to the screw terminals.
Screw the screws straight down so as not to damage the screw threads.
Hold the two round terminals back to back to ensure that the screw will screw down straight.
After tightening the screw, mark a line through the screw head, washer, and terminals with a permanent marker.
Example
Mark a line.
Daisy-chain
Power wires, transmission lines, centralized transmission lines
Place the round terminals back to back.
Power supply terminal block, indoor-outdoor transmission line terminal block,
and centralized controller transmission line
Poor contact caused by loose screws may result in overheating and fire.
Continued use of the damaged circuit board may cause overheating and fire.
2-4-1Address Settings List ............................................................................................................................ 22
2-4-2Outdoor Unit Power Jumper Connector Connection.............................................................................24
2-4-3Outdoor Unit Centralized Controller Switch Setting .............................................................................. 24
2-4-4Room Temperature Detection Position Selection ................................................................................. 24
2-4-5Start/Stop Control of Indoor Units ......................................................................................................... 25
2-7Example System with an MA Remote Controller ............................................................................. 32
2-7-1Single Refrigerant System (Automatic Indoor/Outdoor Address Startup)............................................. 32
2-7-2Single Refrigerant System with Two or More LOSSNAY Units ............................................................ 34
2-7-3Grouped Operation of Units in Separate Refrigerant Circuits ............................................................... 36
2-7-4System with a Connection of System Controller to Centralized Control Transmission Line................. 38
2-7-5System with a Connection of System Controller to Indoor-Outdoor Transmission Line ....................... 40
2-7-6System with Multiple BC Controllers..................................................................................................... 42
2-8Example System with an ME Remote Controller ............................................................................. 46
2-8-1System with a Connection of System Controller to Centralized Control Transmission Line................. 46
2-9Example System with an MA and an ME Remote Controller .......................................................... 48
2-9-1System with a Connection of System Controller to Centralized Control Transmission Line................. 48
2-10Restrictions on Refrigerant Pipes ..................................................................................................... 51
2-10-1 Restrictions on Refrigerant Pipe Length ............................................................................................... 51
2-10-2 Restrictions on Refrigerant Pipe Size ................................................................................................... 57
2-10-3 BC Controller Connection Method ........................................................................................................ 58
HWE13080GB
- 17 -
HWE13080GB
- 18 -
[2-1 System Configurations ]
2 Restrictions
2-1System Configurations
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
Outdoor
units
Composing unitsMaximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable in-
door units
72 - - 36 - 10818P06 - P96 models
96 - - 48 - 14424
R410A series indoor units
144727272 - 21636
192969696 - 28848
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
2 Restrictions
HWE13080GB
- 19 -