Mitsubishi Electric PUNZ-RP-HA-A Installation Manual

Air-Conditioners
PUHZ-RP·HA-A
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
FOR INSTALLER
English
Contents
ELV
1. Safety precautions ................................................................................... 2
2. Installation location .................................................................................. 3
3. Installing the outdoor unit ......................................................................... 4
4. Installing the refrigerant piping ................................................................. 5
5. Drainage piping work ............................................................................... 7
1. Safety precautions
tions”.
s Please report to or take consent by the supply authority before connec-
tion to the system.
Warning: Describes precautions that must be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the “Safety Precautions,” use, and maintenance of the unit to the customer according to the information in the Op­eration Manual and perform the test run to ensure normal operation. Both the Instal­lation Manual and Operation Manual must be given to the user for keeping. These manuals must be passed on to subsequent users.
Warning:
• The unit must not be installed by the user. Ask a dealer or an authorized
technician to install the unit. If the unit is installed incorrectly, water leakage, electric shock, or fire may result.
• For installation work, follow the instructions in the Installation Manual and use
tools and pipe components specifically made for use with R410A refrigerant. The R410A refrigerant in the HFC system is pressurized 1.6 times the pressure of usual refrigerants. If pipe components not designed for R410A refrigerant are used and the unit is not installed correctly, the pipes may burst and cause damage or injuries. In addition, water leakage, electric shock, or fire may result.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor­rectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down and cause damage or injuries.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Consult a dealer regarding the appro­priate measures to prevent the allowable concentration from being exceeded. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual. The units must be powered by dedicated power lines and the correct voltage and circuit break­ers must be used. Power lines with insufficient capacity or incorrect electri­cal work may result in electric shock or fire.
6. Electrical work .......................................................................................... 8
7. Test run .................................................................................................... 8
8. Special Functions .................................................................................... 9
9. System controll (Fig. 9-1) ......................................................................... 9
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts.
: Indicates that the main switch must be turned off before servicing.
: Beware of electric shock.
: Beware of hot surface.
: At servicing, please shut down the power supply for both the Indoor and
Outdoor Unit.
Warning:
Carefully read the labels affixed to the main unit.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. If the pipes are not connected correctly, the unit will not be properly grounded and electric shock may result.
• Use only specified cables for wiring. The connections must be made securely without tension on the terminals. If the cables are connected or installed in­correctly, overheating or fire may result.
• The terminal block cover panel of the outdoor unit must be firmly attached. If the cover panel is mounted incorrectly and dust and moisture enter the unit, electric shock or fire may result.
• When installing or moving the air conditioner, use only the specified refriger­ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig­erant and do not allow air to remain in the lines. Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them. If accessories are incorrectly in­stalled, water leakage, electric shock, or fire may result.
• Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are not performed correctly, water leakage, electric shock, or fire may result.
• The user should never attempt to repair the unit or transfer it to another loca­tion. If the unit is installed incorrectly, water leakage, electric shock, or fire may result. If the air conditioner must be repaired or moved, ask a dealer or an authorized technician.
• After installation has been completed, check for refrigerant leaks. If refriger­ant leaks into the room and comes into contact with the flame of a heater or portable cooking range, poisonous gases will be released.
1.1. Before installation
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is in­stalled in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, areas exposed to high salt content such as the seaside, or areas where the unit will be covered by snow, the performance can be significantly re­duced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, flow, or accumulate. If combustible gas accumulates around the unit, fire or explo­sion may result.
• The outdoor unit produces condensation during the heating operation. Make sure to provide drainage around the outdoor unit if such condensation is likely to cause damage.
1.2. Before installation (relocation)
Caution:
• Be extremely careful when transporting the units. Two or more persons are needed to handle the unit, as it weighs 20 kg or more. Do not grasp the packaging bands. Wear protective gloves to remove the unit from the pack­aging and to move it, as you can injure your hands on the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials, such as nails and other metal or wooden parts may cause stabs or other injuries.
• The base and attachments of the outdoor unit must be periodically checked for looseness, cracks or other damage. If such defects are left uncorrected, the unit may fall down and cause damage or injuries.
2
• When installing the unit in a hospital or communications office, be prepared for noise and electronic interference. Inverters, home appliances, high-fre­quency medical equipment, and radio communications equipment can cause the air conditioner to malfunction or breakdown. The air conditioner may also affect medical equipment, disturbing medical care, and communications equip­ment, harming the screen display quality.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too much, the flare nut can break after an extended period and refrigerant can leak out.
1. Safety precautions
D
E
C
B
A
950
300+30
943 (1350)
175
600
370
1.3. Before electric work
Caution:
Be sure to install circuit breakers. If not installed, electric shock may result.
For the power lines, use standard cables of sufficient capacity. Otherwise, a
short circuit, overheating, or fire may result.
When installing the power lines, do not apply tension to the cables. If the connections are loosened, the cables can snap or break and overheating or fire may result.
1.4. Before starting the test run
Caution:
Turn on the main power switch more than 12 hours before starting operation. Starting operation just after turning on the power switch can severely dam­age the internal parts. Keep the main power switch turned on during the op­eration season.
Before starting operation, check that all panels, guards and other protective parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.
Do not touch any switch with wet hands. Electric shock may result.
1.5. Using R410A refrigerant air conditioners
Caution:
Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust. Use pipes with the specified thickness. (Refer to page 5) Note the following if reusing existing pipes that carried R22 refriger­ant.
- Replace the existing flare nuts and flare the flared sections again.
- Do not use thin pipes. (Refer to page 5)
Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing. (Leave elbow joints, etc. in their packaging.) If dust, debris, or moisture enters the refrigerant lines, oil dete­rioration or compressor breakdown may result.
Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections. If mineral oil is mixed in the refrigeration oil, oil deterioration may result.
Be sure to ground the unit. Do not connect the ground wire to gas or water pipes, lighting rods, or telephone grounding lines. If the unit is not properly grounded, electric shock may result.
Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specified capacity. If the circuit breaker capacity is larger than the specified capacity, breakdown or fire may result.
Do not touch the refrigerant pipes with bare hands during operation. The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant. If you touch the pipes, burns or frostbite may result.
After stopping operation, be sure to wait at least five minutes before turning off the main power switch. Otherwise, water leakage or breakdown may re­sult.
Do not use refrigerant other than R410A refrigerant. If another refrigerant is used, the chlorine will cause the oil to deteriorate.
Use the following tools specifically designed for use with R410A refrigerant. The following tools are necessary to use R410A refrigerant. Contact your nearest dealer for any questions.
Tools (for R410A)
Gauge manifold Flare tool
Charge hose Size adjustment gauge
Gas leak detector Vacuum pump adapter
Torque wrench Electronic refrigerant charging scale
Be sure to use the correct tools. If dust, debris, or moisture enters the refrig­erant lines, refrigeration oil deterioration may result.
Do not use a charging cylinder. If a charging cylinder is used, the composi­tion of the refrigerant will change and the efficiency will be lowered.
2. Installation location
Fig. 2-1
Fig. 2-2
2.1. Refrigerant pipe (Fig. 2-1)
s Check that the difference between the heights of the indoor and outdoor
units, the length of refrigerant pipe, and the number of bends in the pipe are within the limits shown below.
Models
RP3 max. 50 m max. 30 m max. of 15
RP4-6 max. 75 m max. 30 m max. of 15
Height difference limitations are binding regardless of which unit, indoor or outdoor, is positioned higher.
D Indoor unit E Outdoor unit
A Pipe length B Height C Number of
(one way) difference bends (one way)
2.2. Choosing the outdoor unit installation location
Avoid locations exposed to direct sunlight or other sources of heat.
Select a location from which noise emitted by the unit will not inconvenience
neighbors.
Select a location permitting easy wiring and pipe access to the power source and indoor unit.
Avoid locations where combustible gases may leak, be produced, flow, or accumulate.
Note that water may drain from the unit during operation.
Select a level location that can bear the weight and vibration of the unit.
Avoid locations where the unit can be covered by snow. In areas where heavy snow
fall is anticipated, special precautions such as raising the installation location or installing a hood on the air intake must be taken to prevent the snow from blocking the air intake or blowing directly against it. This can reduce the airflow and a mal­function may result.
Avoid locations exposed to oil, steam, or sulfuric gas.
Use the transportation handles of the outdoor unit to transport the unit. If the unit is
carried from the bottom, hands or fingers may be pinched.
2.3. Outline dimensions (Outdoor unit) (Fig. 2-2)
The figure in parentheses are for RP4-6 models.
3
2. Installation location
A
B
Max.30
B
A
C
600 600Min. 360
175 175
Min. 10
950
25
330
370
D
Fig. 2-3
Fig. 2-4
Fig. 2-5
2.4. Ventilation and service space
2.4.1. Windy location installation
When installing the outdoor unit on a rooftop or other location unprotected from the wind, situate the air outlet of the unit so that it is not directly exposed to strong winds. Strong wind entering the air outlet may impede the normal airflow and a malfunction may result. The following shows three examples of precautions against strong winds. 1 Face the air outlet towards the nearest available wall about 50 cm away from the
wall. (Fig. 2-3)
2 Install an optional air outlet guide and air guide if the unit is installed in a location
where strong winds from a typhoon, etc. may directly enter the air outlet. (Fig. 2-4)
A Air outlet guide
3 Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-5)
B Wind direction
2.4.2. When installing a single outdoor unit (Refer to the last page)
Minimum dimensions are as follows, except for Max., meaning Maximum dimensions, indicated. The figure in parentheses are for RP4-6 models. Refer to the figures for each case.
1 Obstacles at rear only (Fig. 2-6) 2 Obstacles at rear and above only (Fig. 2-7) 3 Obstacles at rear and sides only (Fig. 2-8) 4 Obstacles at front only (Fig. 2-9)
When using an optional air outlet guide, the clearance for RP4-6 models is 500 mm or more.
5 Obstacles at front and rear only (Fig. 2-10)
When using an optional air outlet guide, the clearance for RP4-6 models is 500 mm or more.
6 Obstacles at rear, sides, and above only (Fig. 2-11)
* Do not install the optional air outlet guides for upward airflow.
2.4.3. When installing multiple outdoor units (Refer to the last page)
Leave a 10 mm space or more between the units.
1 Obstacles at rear only (Fig. 2-12) 2 Obstacles at rear and above only (Fig. 2-13)
* No more than three units must be installed side by side. In addition, leave space as shown.
* Do not install the optional air outlet guides for upward airflow.
3 Obstacles at front only (Fig. 2-14)
When using an optional air outlet guide, the clearance for RP4-6 models is 1000 mm or
more.
4 Obstacles at front and rear only (Fig. 2-15)
When using an optional air outlet guide, the clearance for RP4-6 models is 1000 mm or
more.
5 Single parallel unit arrangement (Fig. 2-16)
When using an optional air outlet guide installed for upward airflow, the clearance is 500
(1000) mm or more.
6 Multiple parallel unit arrangement (Fig. 2-17)
When using an optional air outlet guide installed for upward airflow, the clearance is 1000
(1500) mm or more.
7 Stacked unit arrangement (Fig. 2-18)
* The units can be stacked up to two units high.
* No more than two stacked units must be installed side by side. In addition, leave space as
shown.
3. Installing the outdoor unit
(mm)
A M10 (3/8") bolt B Base C As long as possible. D Vent
Be sure to install the unit in a sturdy, level surface to prevent rattling noises during operation. (Fig. 3-1)
<Foundation specifications>
Foundation bolt M10 (3/8") Thickness of concrete 120 mm Length of bolt 70 mm Weight-bearing capacity 320 kg
Make sure that the length of the foundation bolt is within 30 mm of the bottom surface of the base.
Secure the base of the unit firmly with four-M10 foundation bolts in sturdy locations.
Installing the outdoor unit
Do not block the vent. If the vent is blocked, operation will be hindered and break­down may result.
In addition to the unit base, use the installation holes on the back of the unit to attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 15 mm or more) and install on site.
Warning:
The unit must be securely installed on a structure that can sustain its weight. If the unit is mounted on an unstable structure, it may fall down and cause damage or injuries.
The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons, or strong winds. An incor­rectly installed unit may fall down and cause damage or injuries.
4
Fig. 3-1
Loading...
+ 8 hidden pages