For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing
the air-conditioner unit.
INSTALLATIONSHANDBUCH
Aus Sicherheitsgründen und zur richtigen Verwendung vor der Installation die vorliegende Bedienungsanleitung
und die Installationsanleitung der Innenanlage gründlich durchlesen die Klimaanlage.
MANUEL D’INSTALLATION
Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil
intérieur pour une utilisation sûre et correcte.
INSTALLATIEHANDLEIDING
Lees deze handleiding en de installatiehandleiding van het binnenapparaat zorgvuldig door voordat u met het
installeren van de airconditioner begint.
MANUAL DE INSTALACIÓN
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad interior
antes de instalar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente il presente manuale ed il manuale d’installazione dell’unità
interna prima di installare il condizionatore d’aria.
EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ
Για σωστή και ασφαλή χρήση, διαβάστε προσεκτικά αυτό το εγχειρίδιο καθώς και το εγχειρίδιο εγκατάστασης
της εσωτερικής μονάδας, προτού εγκαταστήσετε τη μονάδα του κλιματιστικού.
MANUAL DE INSTALAÇÃO
Para uma utilização segura e correcta, leia atentamente este manual e o manual de instalação da unidade
interior antes de instalar o aparelho de ar condicionado.
INSTALLATIONSMANUAL
Læs af sikkerhedshensyn denne manual samt manualen til installation af indendørsenheden grundigt, før du
installerer klimaanlægget.
INSTALLATIONSMANUAL
Läs bruksanvisningen och inomhusenhetens installationshandbok noga innan luftkonditioneringen installeras
så att den används på ett säkert och korrekt sätt.
MONTAJ ELKİTABI
Emniyetli ve doğru kullanım için, klima cihazını monte etmeden önce bu kılavuzu ve iç ünite montaj kılavuzunu
tamamıyla okuyun.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для обеспечения безопасной и надлежащей эксплуатации внимательно прочтите данное руководство
и руководство по установке внутреннего прибора перед установкой кондиционера.
INSTALLASJONSHÅNDBOK
For å sikre trygg og riktig bruk skal denne håndboken samt installasjonshåndboken for innendørsenheten leses
grundig gjennom før du installerer klimaanleggenheten.
INSTRUKCJA MONTAŻU
Aby zapewnić bezpieczne i prawidłowe korzystanie z urządzenia, przed montażem klimatyzatora należy
dokładnie zapoznać się z treścią niniejszej instrukcji oraz instrukcji montażu jednostki wewnętrznej.
3. Installing the outdoor unit ..........................................................................7
4. Installing the refrigerant piping ..................................................................7
Caution:
• Do not vent R410A into the atmosphere.
Conrmation of parts attached
In addition to this manual, the following part is supplied with the outdoor unit.
It is used for grounding the S terminal of transmission terminal block TB7. For details
refer to “6. Electrical work”.
Grounding lead wire
1. Safety precautions
► Before installing the unit, make sure you read all the “Safety precau-
tions”.
► Please report to or take consent by the supply authority before connec-
tion to the system.
GB
► PUMY-SP·VKM series complying with IEC/EN 61000-3-12
► PUMY-SP·VKM series is designed for use in the residential, commercial
and light-industrial environment.
► PUMY-SP·YKM series is designed as professional equipment.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
5. Drainage piping work ...............................................................................15
6. Electrical work .........................................................................................15
7. Test run ....................................................................................................24
8. Special functions .....................................................................................25
After installation work has been completed, explain the “Safety Precautions,” use, and
maintenance of the unit to the customer according to the information in the Operation
Manual and perform the test run to ensure normal operation. Both the Installation
Manual and Operation Manual must be given to the user for keeping. These manuals
must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels afxed to the main unit.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
Warning:
• The unit must not be installed by the user. Ask a dealer or an authorized
technician to install the unit. If the unit is installed incorrectly, water leakage,
electric shock, or re may result.
• This appliance is intended to be used by expert or trained users in shops, in
light industry and on farms, or for commercial use by lay persons.
• For installation work, follow the instructions in the Installation Manual and
use tools and pipe components specically made for use with R410A refrigerant. The R410A refrigerant in the HFC system is pressurized 1.6 times the
pressure of usual refrigerants. If pipe components not designed for R410A
refrigerant are used and the unit is not installed correctly, the pipes may burst
and cause damage or injuries. In addition, water leakage, electric shock, or
re may result.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incorrectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Consult a dealer regarding the appropriate measures to prevent the allowable concentration from being exceeded.
Should the refrigerant leak and cause the concentration limit to be exceeded,
hazards due to lack of oxygen in the room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a ame, poisonous gases will be released.
• All electric work must be performed by a qualied technician according to
local regulations and the instructions given in this manual. The units must be
powered by dedicated power lines and the correct voltage and circuit breakers
must be used. Power lines with insufcient capacity or incorrect electrical
work may result in electric shock or re.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. If the pipes are not connected correctly, the
unit will not be properly grounded and electric shock may result.
• Use only specied cables for wiring. The wiring connections must be made
securely with no tension applied on the terminal connections. Also, never
splice the cables for wiring (unless otherwise indicated in this document).
Failure to observe these instructions may result in overheating or a re.
• The terminal block cover panel of the outdoor unit must be rmly attached. If
the cover panel is mounted incorrectly and dust and moisture enter the unit,
electric shock or re may result.
• The appliance shall be installed in accordance with national wiring regulations.
• If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualied persons in order to avoid a hazard.
• When installing or relocating, or servicing the air conditioner, use only the
specied refrigerant (R410A) to charge the refrigerant lines. Do not mix it with
any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high
pressure in the refrigerant line, and may result in an explosion and other
hazards.
The use of any refrigerant other than that specied for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or an
authorized technician to install them. If accessories are incorrectly installed,
water leakage, electric shock, or re may result.
• Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are
not performed correctly, water leakage, electric shock, or re may result.
• The user should never attempt to repair the unit or transfer it to another location. If the unit is installed incorrectly, water leakage, electric shock, or re
may result. If the air conditioner must be repaired or moved, ask a dealer or
an authorized technician.
• After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes into contact with the ame of a heater or
portable cooking range, poisonous gases will be released.
2
1. Safety precautions
1.1. Before installation
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is installed
in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas,
areas exposed to high salt content such as the seaside, or areas where the
unit will be covered by snow, the performance can be signicantly reduced
and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, ow,
or accumulate. If combustible gas accumulates around the unit, re or explosion may result.
• The outdoor unit produces condensation during the heating operation. Make
sure to provide drainage around the outdoor unit if such condensation is likely
to cause damage.
1.2. Before installation (relocation)
Caution:
• Be extremely careful when transporting the units. Two or more persons are
needed to handle the unit, as it weighs 20 kg or more. Do not grasp the packaging bands. Wear protective gloves to remove the unit from the packaging
and to move it, as you can injure your hands on the ns or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials, such
as nails and other metal or wooden parts may cause stabs or other injuries.
• The base and attachments of the outdoor unit must be periodically checked
for looseness, cracks or other damage. If such defects are left uncorrected,
the unit may fall down and cause damage or injuries.
1.3. Before electric work
Caution:
• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of sufcient capacity. Otherwise, a
short circuit, overheating, or re may result.
• When installing the power lines, do not apply tension to the cables. If the
connections are loosened, the cables can snap or break and overheating or
re may result.
• When installing the unit in a hospital or communications ofce, be prepared for
noise and electronic interference. Inverters, home appliances, high-frequency
medical equipment, and radio communications equipment can cause the air
conditioner to malfunction or breakdown. The air conditioner may also affect
medical equipment, disturbing medical care, and communications equipment,
harming the screen display quality.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all are nuts to specication using a torque wrench. If tightened too
much, the are nut can break after an extended period and refrigerant can
leak out.
GB
• Be sure to ground the unit. Do not connect the ground wire to gas or water
pipes, lightning rods, or telephone grounding lines. If the unit is not properly
grounded, electric shock may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and
molded case circuit breaker) with the specied capacity. If the circuit breaker
capacity is larger than the specied capacity, breakdown or re may result.
1.4. Before starting the test run
Caution:
• Turn on the main power switch more than 12 hours before starting operation.
Starting operation just after turning on the power switch can severely damage
the internal parts. Keep the main power switch turned on during the operation
season.
• Before starting operation, check that all panels, guards and other protective
parts are correctly installed. Rotating, hot, or high voltage parts can cause
injuries.
• Do not touch any switch with wet hands. Electric shock may result.
1.5. Using R410A refrigerant air conditioners
Caution:
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. Make sure the insides of the pipes are clean
and do not contain any harmful contaminants such as sulfuric compounds,
oxidants, debris, or dust. Use pipes with the specied thickness. (Refer to
4.1.) Note the following if reusing existing pipes that carried R22 refrigerant.
- Replace the existing are nuts and are the ared sections again.
- Do not use thin pipes. (Refer to 4.1.)
• Store the pipes to be used during installation indoors and keep both ends of
the pipes sealed until just before brazing. (Leave elbow joints, etc. in their
packaging.) If dust, debris, or moisture enters the refrigerant lines, oil deterioration or compressor breakdown may result.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration
oil applied to the ared sections. If mineral oil is mixed in the refrigeration
oil, oil deterioration may result.
• Do not touch the refrigerant pipes with bare hands during operation. The
refrigerant pipes are hot or cold depending on the condition of the owing
refrigerant. If you touch the pipes, burns or frostbite may result.
• After stopping operation, be sure to wait at least ve minutes before turning
off the main power switch. Otherwise, water leakage or breakdown may result.
• Do not use refrigerant other than R410A refrigerant. If another refrigerant is
used, the chlorine will cause the oil to deteriorate.
• Use the following tools specically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant. Contact your
nearest dealer for any questions.
• Be sure to use the correct tools. If dust, debris, or moisture enters the refrigerant lines, refrigeration oil deterioration may result.
• Do not use a charging cylinder. If a charging cylinder is used, the composition
of the refrigerant will change and the efciency will be lowered.
3
2. Installation location
330+40
GB
981
225
600
Fig. 2-1
1050
370
(mm)
2.1. Refrigerant pipe
Refer to Fig. 4-1, 4-2.
2.2. Choosing the outdoor unit installation location
• Avoid locations exposed to direct sunlight or other sources of heat.
• Select a location from which noise emitted by the unit will not inconvenience neighbors.
• Select a location permitting easy wiring and pipe access to the power source and
indoor unit.
• Avoid locations where combustible gases may leak, be produced, ow, or accumulate.
• Note that water may drain from the unit during operation.
• Select a level location that can bear the weight and vibration of the unit.
• Avoid locations where the unit can be covered by snow. In areas where heavy snow
fall is anticipated, special precautions such as raising the installation location or
installing a hood on the air intake must be taken to prevent the snow from blocking the air intake or blowing directly against it. This can reduce the airow and a
malfunction may result.
• Avoid locations exposed to oil, steam, or sulfuric gas.
• Use the transportation handles of the outdoor unit to transport the unit. If the unit
is carried from the bottom, hands or ngers may be pinched.
2.3. Outline dimensions (Outdoor unit) (Fig. 2-1)
Constraints on indoor unit installation
You should note that indoor units that can be connected to this outdoor unit are the
following models.
• Indoor units with model numbers 15-140 can be connected.
When using Branch box, Indoor units with model numbers 15-100 can be connected.
Refer to the table 1 below for possible room, indoor unit combinations.
Verication
The rated capacity should be determined by observing the table below. The unit’s
quantities are limited as shown in the following table 2. For the next step, make
sure that the total rated capacity selected will stay in a range of 50% – 130% of the
outdoor unit capacity.
• PUMY-SP112 6.3 – 16.2 kW
• PUMY-SP125 7.1 – 18.2 kW
• PUMY-SP140 8.0 – 20.2 kW
Table 1-1 City Multi indoor units
Indoor unit type
Rated capacity
(Cooling) (kW)
Indoor unit type
Rated capacity
(Cooling) (kW)
Table 1-2 M series, P series, S series
Indoor unit type
Rated capacity
(Cooling) (kW)
15 20 22 25 28 32 36 40 45 50 56 63
1.7 2.2 2.5 2.8 3.2 3.6 4.0 4.5 5.0 5.6 6.3 7.1
71 80 100 125 140
8.0 9.0 11.2 14.0 16.0
15202225354250607180 100
1.5 2.0 2.2 2.5 3.5 4.2 5.0 6.0 7.1 8.0 10.0
Table 2 Connectable indoor units quantities
ModelOnly systemMixed system
PUMY-SP1121-92-8Max. 5Max. 5Max. 7 or 8*1Max. 3 or 2*1
PUMY-SP1251-102-8Max. 5Max. 5Max. 8Max. 3
PUMY-SP1401-122-8Max. 5Max. 5Max. 8Max. 3
Only City Multi indoor units
(Connection without Branch
box)
Only M series, P series,
S series indoor units
(Connection with Branch box)
Connection with
*1 When connecting 7 indoor units via branch box, connectable citymulti indoor units
are 3; connecting 8 indoor units via branch box, connectable citymulti indoor units
are 2.
Table 3 Connectable Branch box quantities
ModelBranch box
PUMY-SP112/125/1401-2
Combinations in which the total capacity of indoor units exceeds the capacity of the
outdoor unit will reduce the cooling capacity of each indoor unit below their rated
cooling capacity. Thus, combine indoor units with an outdoor unit within the outdoor
unit’s capacity, if possible.
One Branch boxTwo Branch box
Branch box
City Multi indoor
units
Connection with
Branch box
City Multi indoor
units
4
2. Installation location
2.4. Connecting a PEFY-P∙VMA3-E
When using a PEFY-P∙VMA3-E, use the following combinations for the connected indoor units.
PUMY-SP112PUMY-SP125PUMY-SP140
OK
NO
PEFY-P25VMA3-E × 2
+
PEFY-P32VMA3-E × 2
All combinations excluding the above
combinations
Ex. 1: PEFY-P25VMA3-E × 2
+
PEFY-P32VMA-E × 2
Ex. 2: PEFY-P25VMA3-E × 2
+
PEFY-P32VMA3-E × 1
Ex. 3: PEFY-P32VMA3-E × 4
(A combination for a PUMY-SP125)
Ex. 4: PEFY-P25VMA3-E × 2
+
PEFY-P32VMA3-E × 2
+
MSZ-FH25VE × 1
PEFY-P25VMA3-E × 1
+
PEFY-P32VMA3-E × 3
All combinations excluding the above
combinations
Ex. 1: PEFY-P32VMA3-E × 3
+
PEFY-P32VMA-E × 1
Ex. 2: PEFY-P32VMA3-E × 3
Ex. 3: PEFY-P25VMA3-E × 2
+
PEFY-P32VMA3-E × 2
(A combination for a PUMY-SP112)
Ex. 4: PEFY-P32VMA3-E × 3
+
PLFY-P20VFM-E × 1
+
SEZ-KD25VA × 1
Ex. 1: A ceiling-concealed unit other than a VMA3 series is selected. Combinations
with a ceiling-concealed different series are not possible.
Ex. 2: The number of units is incorrect.
Ex. 3: The combination is for a unit with a different capacity.
Ex. 4: The combination is not an “OK” combination.
PEFY-P32VMA3-E × 2
+
PEFY-P40VMA3-E × 2
All combinations excluding the above
combinations
Ex. 1: PEFY-P32VMA3-E × 3
+
PEFY-P40VMA-E × 1
Ex. 2: PEFY-P32VMA3-E × 2
+
PEFY-P40VMA3-E × 1
Ex. 3: PEFY-P32VMA3-E × 4
(A combination for a PUMY-SP125)
Ex. 4: PEFY-P32VMA3-E × 3
+
PCFY-P40VKM-E × 1
+
MSZ-SF15VA × 1
GB
2.5. Connecting a PLFY-EP∙VEM-E
For the PLFY-EP∙VEM-E, up to 2 units can be connected.
Other indoor units*1 can be connected within the total rated capacity and maximum number of connected units.
*1 Excluding the PEFY-P∙VMA3-E and PEFY-P∙VMH-EF.
5
2. Installation location
2.6. Ventilation and service space
2.6.1. When installing a single outdoor unit
Minimum dimensions are as follows, except for Max., meaning Maximum dimensions, indicated.
Refer to the gures for each case.
1 Obstacles at rear only (Fig. 2-2)
2 Obstacles at rear and above only (Fig. 2-3)
3 Obstacles at rear and sides only (Fig. 2-4)
4 Obstacles at front only (Fig. 2-5)
∗ When using an optional air outlet guide, the clearance is 500 mm or more.
5 Obstacles at front and rear only (Fig. 2-6)
∗ When using an optional air outlet guide, the clearance is 500 mm or more.
6 Obstacles at rear, sides, and above only (Fig. 2-7)
• Do not install the optional air outlet guides for upward airow.
GB
150
Fig. 2-2
Max.500
Fig. 2-3
300
2.6.2. When installing multiple outdoor units
Leave 25 mm space or more between the units.
1 Obstacles at rear only (Fig. 2-8)
2 Obstacles at rear and above only (Fig. 2-9)
• No more than 3 units must be installed side by side. In addition, leave space as shown.
• Do not install the optional air outlet guides for upward airow.
3 Obstacles at front only (Fig. 2-10)
∗ When using an optional air outlet guide, the clearance is 1000 mm or more.
4 Obstacles at front and rear only (Fig. 2-11)
∗ When using an optional air outlet guide, the clearance is 1000 mm or more.
5 Single parallel unit arrangement (Fig. 2-12)
∗ When using an optional air outlet guide installed for upward airow, the clearance is 1000 mm
or more.
6 Multiple parallel unit arrangement (Fig. 2-13)
∗ When using an optional air outlet guide installed for upward airow, the clearance is 1500 mm
or more.
7 Stacked unit arrangement (Fig. 2-14)
• The units can be stacked up to 2 units high.
• No more than 2 stacked units must be installed side by side. In addition, leave space as shown.
1000
200
200
Fig. 2-4
300
UNIT: mm
1000*
Fig. 2-5
Fig. 2-6
1500
Fig. 2-9
1000*
150
Max.300
500
1500
250
Max.500
250
Fig. 2-7
Fig. 2-10
1500*
500
1500
300
Fig. 2-8
500
1500*
Fig. 2-11
500
150
1500
800
Fig. 2-14
1000
600
Fig. 2-12
150
2000*
3000*
600
1500
Fig. 2-13
6
2. Installation location
A
Fig. 2-15Fig. 2-16
3. Installing the outdoor unit
2.6.3. Windy location installation
When installing the outdoor unit on a rooftop or other location unprotected from the
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds.
Strong wind entering the air outlet may impede the normal airow and a malfunction
may result.
The following shows two examples of precautions against strong winds.
1 Install an optional air guide if the unit is installed in a location where strong winds
B
from a typhoon, etc. may directly enter the air outlet. (Fig. 2-15)
A Air guide
2 Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-16)
B Wind direction
Max. 30
A M10 (3/8") bolt
B Base
C As long as possible.
* When installing a single outdoor unit, the clearance is 15 mm or more.
B
D Vent
E Set deep in the ground.
A
C
Min. 500
600600
225225
Min. 25*
1050
E
(mm)
D
33040
370
• Be sure to install the unit in a sturdy, level surface to prevent rattling noises during
operation. (Fig. 3-1)
<Foundation specications>
Foundation boltM10 (3/8″)
Thickness of concrete120 mm
Length of bolt70 mm
Weight-bearing capacity320 kg
• Make sure that the length of the foundation bolt is within 30 mm of the bottom surface
of the base.
• Secure the base of the unit rmly with four-M10 foundation bolts in sturdy locations.
Installing the outdoor unit
• Do not block the vent. If the vent is blocked, operation will be hindered and breakdown may result.
• In addition to the unit base, use the installation holes on the back of the unit to attach
wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 15 mm or
less) and install on site.
Warning:
• The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incorrectly installed unit may fall down and cause damage or injuries.
Caution:
• Install unit on a rigid structure to prevent excessive operation sound or vibration.
GB
Fig. 3-1
4. Installing the refrigerant piping
4.1. Precautions for devices that use R410A refrigerant
• Refer to 1.5. for precautions not included below on using air conditioners with
R410A refrigerant.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration
oil applied to the ared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specied in the table to the below. Make sure the insides of the pipes are clean
and do not contain any harmful contaminants such as sulfuric compounds,
oxidants, debris, or dust.
Warning:
When installing or relocating, or servicing the air conditioner, use only the
specied refrigerant (R410A) to charge the refrigerant lines. Do not mix it with
any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high
pressure in the refrigerant line, and may result in an explosion and other hazards.
The use of any refrigerant other than that specied for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst case,
this could lead to a serious impediment to securing product safety.
Pipe size (mm)ø6.35ø9.52ø12.7ø15.88
Thickness (mm)0.80.80.81.0
• Do not use pipes thinner than those specied above.
• The thicknesses listed in the table above are based on Japanese standards.
Use pipes with a maximum working pressure of 4.15 MPa [601 PSIG] or
higher according to local standards.
7
4. Installing the refrigerant piping
GB
A
A
H
B
C
A+B+C+D+a+b+c+d+e [ 120 m
L = A+B+C+D+e [ 70 m
ℓ = B+C+D+e [ 50 m
H [ 50 m (Outdoor lower H [ 30 m)
h [ 15 m
BC
ahbcd
L
r
D
CCC
e
C
4.1.1. Connection without Branch box (Fig. 4-1)
A (mm)
L: The farthest piping length from the outdoor unit to an indoor unit.
B, C, D (mm)
L: The farthest piping length from the outdoor unit to an indoor unit.
Liquid pipe
A
ø9.52ø15.88
Liquid pipe
A
ø9.52ø15.88
Gas pipe
B
Gas pipe
B
a, b, c, d, e, f (mm)
Model number
A
H
A+a+b+c+d+e+f [ 120 m
L = A+f [ 70 m, ℓ = f [ 50 m
H [ 50 m (Outdoor lower H [ 30 m)
h [ 15 m
A
B
b
a
cd
C C
h
C C
L
r
D
ef
C
A Outdoor unit
B First branch (CMY)
C Indoor unit
D Cap
C
Fig. 4-1
D
15, 20, 25, 32, 40, 50
a, b, c, d, e, f [ 30 m
a, b, c, d, e, f ˃ 30 mø9.52*1
63, 71, 80, 100, 125, 140ø9.52ø15.88
*1 If the piping length after the rst joint exceeds 30 m, use a pipe size of ø9.52 for
the pipes of the system that exceeds 30 m.
E
4-Branching header
F
CMY-Y64-G-ECMY-Y68-G-E
Liquid pipe
A
Branch kit model
CMY-Y62-G-E
ø6.35
8-Branching header
G
Gas pipe
B
ø12.7
* When connecting the CONNECTION KIT (PAC-LV11M-J) and an M-series indoor
unit, refer to the installation manual for the CONNECTION KIT when selecting the
pipe size and piping length.
A Outdoor unit
A
c1
D
b1
B Branch box (PAC-MK∙BC(B))
C Indoor unit
D First branch (MSDD)
L
b2
4.1.2. Connection with Branch box (Fig. 4-2)
Flared connections
• This unit has ared connections on each indoor unit and branch box and outdoor
unit sides.
• Remove the valve cover of the outdoor unit, then connect the pipe.
• Refrigerant pipes are used to connect the branch box and outdoor unit.
B
B
H
a1
h1
C
CCC
h3
h2
a4a3a2
C
a6a5
CC
I
a7 a8
C
Fig. 4-2
c1 + b1 + b2 + a1 + a2 + a3 + a4 + a5 + a6 + a7 + a8 [ 120 m
c1 + b2 + a8 [ 80 m (b2 [ 55 m, a8 [ 25 m)
c1 + b1 + b2 [ 55 m
b2 [ 50 m
a8 [ 25 m
a1 + a2 + a3 + a4 + a5 + a6 + a7 + a8 [ 95 m
H [ 50 m (In case of outdoor unit is set higher than indoor unit)
H [ 30 m (In case of outdoor unit is set lower than indoor unit)
h1 + h2 [ 15 m
h2 [ 15 m
h3 [ 12 m
Total piping length
Farthest piping length (L)
Piping length between outdoor unit and branch boxes
Farthest branch box from the rst joint (b2)
Farthest piping length after branch box (l)
Total piping length between branch boxes and indoor units
In indoor/outdoor section (H)*1
In branch box/indoor unit section (h1)
In each branch unit (h2)
In each indoor unit (h3)
*1 Branch box should be placed within the level between the outdoor unit and indoor units.
8
L
4. Installing the refrigerant piping
■ In case of using 1-branch box
Flare connection employed. (No. brazing)
Branch box (PAC-MK∙BC(B))
A
BBBBB
■ In case of using 2-branch boxes
L
2 branches pipe (joint) (MSDD)
: optional parts.
A
A
BBBBB
Branch box #1 (PAC-MK∙BC(B))
A
Branch box #2 (PAC-MK∙BC(B))
Fig. 4-3
(1) Valve size for outdoor unit
For liquidø9.52 mm
For gasø15.88 mm
(2) Valve size for branch box
A UNIT
B UNIT
C UNIT
D UNIT
E UNIT
* 3-branch type : only A, B, C unit
Liquid pipeø6.35 mm
Gas pipeø9.52 mm
Liquid pipeø6.35 mm
Gas pipeø9.52 mm
Liquid pipeø6.35 mm
Gas pipeø9.52 mm
Liquid pipeø6.35 mm
Gas pipeø9.52 mm
Liquid pipeø6.35 mm
Gas pipeø12.7 mm
The lineup of a connectable indoor unit depends on a district/areas/
country.
Branch box
■
Model nameNumber of connected units
PAC-MK3
PAC-MK5
✽
Note:
= 0, 1, 2, ....
The PAC-MK31/32BC(B) and PAC-MK51/52BC(B) cannot be connected.
Pipe size (Branch box–Indoor unit) Case of M series or S series indoor unit
■
Indoor
unit type
Pipe size
(ømm)
* If the pipe size of indoor unit is different, use a different-diameter joint.
Liquidø9.52
✽
BC(B)3-branches (Max. 3 units)
✽
BC(B)5-branches (Max. 5 units)
(kW)15 – 42506071 – 80
Liquidø6.35ø6.35ø9.52
Gasø9.52ø12.7ø15.88ø15.88
and capacity of indoor units. Match the piping connection size of branch box with indoor unit.
If the piping connection size of branch box does not
match the piping connection size of indoor unit, use
optional different-diameter (deformed) joints to the
branch box side. (Connect deformed joint directly to
the branch box side.)
Pipe size (Branch box–Indoor unit) Case of P series indoor unit
■
Indoor
unit type
Pipe size
(ømm)
*1 The lineup of a connectable indoor unit depends on a district/areas/
country.
*2 When using 35, 50 type indoor unit of P series, use the are nut attached
to the indoor unit.
Do not use the are nut in the indoor unit accessory. If it is used, a gas
leakage or even a pipe extraction may occur.
(kW)35 – 5060 – 100
Liquidø6.35ø9.52
Gasø12.7ø15.88
9
4. Installing the refrigerant piping
4.1.3. Mixed system (City Multi indoor units and M/S/P series indoor units via Branch box)
4.1.3-1 In case of using 1-branch box
A
H
Permissible
length (One-way)
GB
Permissible
height difference
(One-way)
L1
C
a2 a3
a1
EE
E
e1
B
d2
d1
c2b2
EE
h3
Total piping length
Farthest piping length (L1)
Farthest piping length. Via Branch box (L2)
Piping length between outdoor unit and branch box
Farthest piping length from the rst joint
Farthest piping length after branch box
Total piping length between branch boxes and indoor units
In indoor/outdoor section (H) *1
In branch box/indoor unit section (h1)
In each indoor unit (h3)
L2
b1c1
D
a4 a5 a6a7 a8
h1
F
FFF
A Outdoor Unit
B First joint (CMY, MSDD)
C Branch header (CMY)
D Branch box (PAC-MK∙BC(B))
F
E CityMulti Indoor unit
F M/S/P series Indoor unit
e1 + d1 + d2 + c1 + c2 + b1 + b2 + a1 + a2 + a3 + a4 + a5 + a6 + a7 + a8 [ 120 m
e1 + d2 + a1 or e1 + d1 + c1 + b2 [ 70 m
e1 + d1 + c1 + b1 + a8 [ 80 m
e1 + d1 + c1 + b1 [ 55 m
d1 + c1 + b1 or d2 + a1 [ 50 m
a8 [ 25 m
a4 + a5 + a6 + a7 + a8 [ 95 m
H [ 50 m (In case of outdoor unit is set higher than indoor unit)
H [ 30 m (In case of outdoor unit is set lower than indoor unit)
h1 [ 15 m
h3 [ 12 m
*1: Branch box should be placed within the level between the outdoor unit and indoor units.
4.1.3-2 In case of using 2-branch boxes
A
C
H
a1
E
Permissible
length (One-way)
Permissible
height difference
(One-way)
Number of bends
L1
a2a3
EE
d1
B
c1
c2
b1
D
h1
a4 a5 a6a7 a8a9 a10 a11
F
h3
FF
Total piping length
Farthest piping length (L1)
Farthest piping length. Via Branch box (L2)
Piping length between outdoor unit and branch boxes
Farthest piping length from the rst joint
Farthest piping length after branch box
Farthest branch box from outdoor unit
Total piping length between branch boxes and indoor units
In indoor/outdoor section (H) *1
In branch box/indoor unit section (h1+h2)
In each branch unit (h1)
In each indoor unit (h3)
L2
b2
D
h2
A Outdoor Unit
B First joint (CMY, MSDD)
F
F
FF
F
C Branch header (CMY)
D Branch box (PAC-MK∙BC(B))
E CityMulti Indoor unit
F M/S/P series Indoor unit
d1 + c2 + b2 [ 55 m
a4 + a5 + a6 + a7 + a8 + a9 + a10 + a11 [ 95 m
H [ 50 m (In case of outdoor unit is set higher than indoor unit)
H [ 30 m (In case of outdoor unit is set lower than indoor unit)
h1 + h2 [ 15 m
h2 [ 15 m
h3 [ 12 m
*1: Branch box should be placed within the level between the outdoor unit and indoor units.
10
4. Installing the refrigerant piping
4.1.3-3 Selecting pipe size
System pipe size
A Outdoor Unit
B First joint (CMY, MSDD)
C Branch header (CMY)
D Branch box (PAC-MK
E City Multi Indoor unit
F M/S/P series Indoor unit
L2
CD
fghij
F F F
Liquid pipeø6.35 mm
Gas pipeø9.52 mm
Liquid pipeø6.35 mm
Gas pipeø9.52 mm
Liquid pipeø6.35 mm
Gas pipeø9.52 mm
Liquid pipeø6.35 mm
Gas pipeø9.52 mm
Liquid pipeø6.35 mm
Gas pipeø12.7 mm
L1: The farthest piping length from the outdoor unit to an indoor unit.
L2: The farthest piping length for the main pipes from the outdoor unit to the branch
box.
L3: The farthest piping length from the rst joint.
a, b, c – j
Indoor unit series
City Multi
Model number
15 – 50
Liquid pipe
A
L3 [ 30m
ø6.35
L3 ˃ 30m ø9.52*1
Gas pipe
B
ø12.7
63 – 140ø9.52ø15.88
M series or S series 15 – 42ø6.35ø9.52
50 ø6.35ø12.7
60 ø6.35ø15.88
71, 80ø9.52ø15.88
P series35 – 50ø6.35ø12.7
60 – 100ø9.52ø15.88
* If the pipe size of indoor unit is different, use a different-diameter joint.
*1 If the piping length after the rst joint exceeds 30 m, use a pipe size of ø9.52 for
• Conduct sufcient anti-condensation and insulation work to prevent water dripping
from the refrigerant piping. (liquid pipe/gas pipe)
• Increase insulation depending on the environment where the refrigerant piping
is installed, or condensation may occur on the surface of the insulation material.
(Insulation material Heat-resistant temperature: 120 °C, Thickness: 15 mm or more)
* When the refrigerant piping is used in locations subject to high temperature and
humidity such as in the attic, further addition of insulation may be required.
• To insulate the refrigerant piping, apply heat-resistant polyethylene foam between
the indoor unit and insulation material as well as to the net between the insulation
material lling all gaps.
(Condensation forming on the piping may result in condensation in the room or
burns when contacting the piping.)
• Be sure to separate thermal insulation for gas and liquid refrigerant pipes.
• The indoor parts of the drain pipe should be wrapped with polyethylene foam insulation materials (specic gravity of 0.03, thickness of 9 mm or more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening
are nut. A
• Use 2 wrenches to tighten piping connections. B
• Use leak detector or soapy water to check for gas leaks after connections are
completed.
• Apply refrigerating machine oil over the entire are seat surface. C
• Use the are nuts for the following pipe size. D
City Multi Indoor unit
Gas sidePipe size (mm)ø12.7ø15.88ø15.88
Liquid side Pipe size (mm)ø6.35*1ø9.52ø9.52
*1 If the farthest piping length after the rst joint exceeds 30 m, use a pipe size of ø9.52.
• When bending the pipes, be careful not to break them. Bend radius of 100 mm to
150 mm is sufcient.
• Make sure the pipes do not contact the compressor. Abnormal noise or vibration
may result.
1 Pipes must be connected starting from the indoor unit.
Flare nuts must be tightened with a torque wrench.
2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil (Ap-
plied on site).
• When usual pipe sealing is used, refer to Table 3 for aring of R410A refrigerant
pipes.
The size adjustment gauge can be used to conrm A measurements.
* To connect the CONNECTION KIT (PAC-LV11M-J), refer to the installation
A Stop valve <Liquid side>
B Stop valve <Gas side>
C Service port
D Open/Close section
D Service panel
E Bend radius : 100 mm - 150 mm
F Strap
Fig. 4-10
C
D
E
F
G
E Local pipe
F Sealed, same way for gas side
G Pipe cover
Fig. 4-11
E
B
C
4.3. Refrigerant piping (Fig. 4-10)
Remove the service panel D (three screws) and the front piping cover A (two screws)
and rear piping cover B (ve screws).
1 Perform refrigerant piping connections for the indoor/outdoor unit when the outdoor
unit’s stop valve is completely closed.
2 Vacuum-purge air from the indoor unit and the connection piping.
3 After connecting the refrigerant pipes, check the connected pipes and the indoor
unit for gas leaks. (Refer to 4.4. Refrigerant pipe airtight testing method)
4 Vacuumize the refrigerant lines through the service port of the liquid and gas stop
valves. And then open the stop valves completely (for both the liquid and gas stop
valves). This will completely connect the refrigerant lines of the indoor and outdoor
units.
• If the stop valves are left closed and the unit is operated, the compressor and
control valves will be damaged.
• Use a leak detector or soapy water to check for gas leaks at the pipe connection sections of the outdoor unit.
• Do not use the refrigerant from the unit to purge air from the refrigerant lines.
• After the valve work is completed, tighten the valve caps to the correct torque:
20 to 25 N·m (200 to 250 kgf·cm).
Failure to replace and tighten the caps may result in refrigerant leakage. In
addition, do not damage the insides of the valve caps as they act as a seal to
prevent refrigerant leakage.
5 Use sealant to seal the ends of the thermal insulation around the pipe connection
sections to prevent water from entering the thermal insulation.
4.4. Refrigerant pipe airtight testing method
(1) Connect the testing tools.
• Make sure the stop valves A B are closed and do not open them.
• Add pressure to the refrigerant lines through the service port C of the liquid
stop valve A and the gas stop valve B.
(2) Do not add pressure to the specied pressure all at once; add pressure little by little.
1 Pressurize to 0.5 MPa (5 kgf/cm
pressure does not decrease.
2 Pressurize to 1.5 MPa (15 kgf/cm
pressure does not decrease.
3 Pressurize to 4.15 MPa (41.5 kgf/cm
perature and refrigerant pressure.
(3) If the specied pressure holds for about one day and does not decrease, the pipes
have passed the test and there are no leaks.
• If the surrounding temperature changes by 1°C, the pressure will change by
about 0.01 MPa (0.1 kgf/cm
(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the source
of the gas leak.
2
G), wait ve minutes, and make sure the
2
G), wait ve minutes, and make sure the
2
G) and measure the surrounding tem-
2
G). Make the necessary corrections.
GB
13
4. Installing the refrigerant piping
A Valve
B Unit side
C Cap
D Local pipe side
E Pipe cover
F Service port
G Wrench hole
GB
C
(1)(2)
AA
HH
FF
BB
CC
GG
II
EE
DD
H Double spanner section
(Do not apply a spanner other than to this section. Doing
so would cause coolant leaks.)
I Seal section
(Seal the end of the heat insulation material at the pipe
connection section with whatever seal material you
have on hand so that water does not inltrate the heat
insulation material.)
Fig. 4-12Fig. 4-13
B
A
D
* The gure to the left is an example
only. The stop valve shape, service port
position, etc., may vary according to the
model.
* Turn section A only.
(Do not further tighten sections A and
B together.)
C Charge hose
D Service port
4.5. Stop valve opening method
The stop valve opening method varies according to the outdoor unit model. Use the
appropriate method to open the stop valves.
(1) Gas side (Fig. 4-12)
1 Remove the cap and turn the valve rod counterclockwise as far as it will go with
the use of a 5 mm hexagonal wrench. Stop turning when it hits the stopper.
(ø15.88: Approximately 13 revolutions)
2 Make sure that the stop valve is open completely and rotate the cap back to its
original position.
(2) Liquid side (Fig. 4-13)
1 Remove the cap and turn the valve rod counterclockwise as far as it will go with
the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.
(ø9.52: Approximately 10 revolutions)
2 Make sure that the stop valve is open completely, push in the handle and rotate
the cap back to its original position.
Refrigerant pipes are protectively wrapped
• The pipes can be protectively wrapped up to a diameter of ø90 before or after connecting the pipes. Cut out the knockout in the pipe cover following the groove and
wrap the pipes.
Pipe inlet gap
• Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain.
(If the gaps are not closed, noise may be emitted or water and dust will enter the
unit and breakdown may result.)
Warning:
When installing the unit, securely connect the refrigerant pipes before starting
the compressor.
Precautions when using the charge valve (Fig. 4-14)
Do not tighten the service port too much when installing it, otherwise, the valve core
could be deformed and become loose, causing a gas leak.
After positioning section B in the desired direction, turn section A only and tighten it.
Do not further tighten sections A and B together after tightening section A.
Fig. 4-14
4.6. Additional refrigerant charge
Additional refrigerant charge
Refrigerant for the extended piping is not included in the outdoor unit when the unit is
shipped from the factory. Therefore, charge each refrigerant piping system with additional refrigerant at the installation site. In addition, in order to carry out service, enter
the size and length of each liquid pipe and additional refrigerant charge amounts in
the spaces provided on the “Refrigerant amount” plate on the outdoor unit.
Calculation of additional refrigerant charge
• Calculate the additional charge using the liquid pipe size and length of the extended piping.
• Calculate the additional refrigerant charge using the procedure shown to the
right, and charge with the additional refrigerant.
• For amounts less than 0.1 kg, round up the calculated additional refrigerant
charge.
(For example, if the calculated charge is 32.92 kg, round up the charge to 33.0
kg.)
<Additional Charge>
Calculation of refrigerant charge
Pipe size
Liquid pipe
ø6.35ø9.52~ 8.0 kW1.5 kg
(m) × 19.0 (g/m)(m) × 50.0 (g/m)8.1 ~ 16.0 kW2.5 kg
Included refrigerant amount when shipped from the factory
Included refrigerant amount
3.5 kg
Calculation example (Please see the lower half of Fig. 4-1.)
Outdoor model : SP140 A : ø9.52 [3/8"]/ø
1: P100 (11.2 kW)
2: P40 (4.5 kW)
The total length of each pipe size is as follows:
[3/8"]/ø15.88 [5/8"
ø9.52
[3/8"]/
[1/4"]/
ø15.88
ø12.7
ø9.52
ø6.35
The total capacity of connected indoor unit is as follows:
11.2 + 4.5 = 15.7
Therefore, the additional charge is as follows:
= 10 ×
= 5.0 kg
Pipe size
Liquid pipe
+
b : ø6.35 [1/4"]/ø12.7 [1/2"]
19.0
10001000
a : ø9.52 [3/8"]/ø15.88 [5/8"]
] : A = 30 m
[5/8"]
: a = 15 m
[1/2"]
: b = 10 m
+ (30 + 15) ×
connected indoor units
+
15.88 [5/8"
50.0
+ 2.5
Total capacity of
16.1 ~ 20.4 kW3.0 kg
] : 30 m
:
15 m
:
10 m
Amount for the
indoor units
For these
piping
lengths
14
5. Drainage piping work
Outdoor unit drainage pipe connection
When drain piping is necessary, use the drain socket or the drain pan (option).
Drain socketPAC-SG61DS-E
Drain panPAC-SH97DP-E
6. Electrical work
6.1. Caution
1 Follow ordinance of your governmental organization for technical standard related
to electrical equipment, wiring regulations and guidance of each electric power
company.
2 Wiring for control (hereinafter referred to as transmission line) shall be (5 cm or
more) apart from power source wiring so that it is not inuenced by electric noise
from power source wiring. (Do not insert transmission line and power source wire
in the same conduit.)
3 Be sure to provide designated grounding work to outdoor unit.
4 Give some allowance to wiring for electrical part box of indoor and outdoor units,
because the box is sometimes removed at the time of service work.
5 Never connect the main power source to terminal block of transmission line. If
connected, electrical parts will be burnt out.
6 Use 2-core shield cable for transmission line. If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations.
7 Only the transmission line specied should be connected to the terminal block for
outdoor unit transmission.
(Transmission line to be connected with indoor unit : Terminal block TB3 for
transmission line, Other : Terminal block TB7 for centralized control)
Erroneous connection does not allow the system to operate.
8 In case to connect with the upper class controller or to conduct group operation in
different refrigerant systems, the control line for transmission is required between
the outdoor units each other.
Connect this control line between the terminal blocks for centralized control. (2-
wire line with no polarity)
When conducting group operation in different refrigerant systems without connect-
ing to the upper class controller, replace the insertion of the short circuit connector
from CN41 of one outdoor unit to CN40.
9 Group is set by operating the remote controller.
0 When connecting the CONNECTION KIT (PAC-LV11M-J) and an M-series indoor
unit, refer to the installation manual for the CONNECTION KIT.
1 When connecting a branch box, be sure to turn on the indoor units and the branch
box before turning on the outdoor unit.
2 Use the strap on the unit to sufciently fasten the cables connected to the termi-
nal blocks. In addition, make sure that the fastened cables and the strap do not
interfere with the panels.
GB
<PUMY-SP·VKM>
TB1
A
B1 B2
N
TB1
M1SM2M1SM2
C
N
B
B1 B2
TB1B
C
L
AB
<PUMY-SP·YKM>
L1
L2 L3
A Power source
B Power supply for branch box
C Screw on the electrical component box
D Transmission line
E
F
TB3TB7
D
E
M1SM2M1SM2
TB3TB7
F
D
E Ground for the terminal block (TB3)
F Screw on the electrical component box
Fig. 6-1
6.2. Control box and connecting position of wiring
(Fig. 6-1)
1. Connect the indoor unit transmission line to transmission terminal block (TB3), or
connect the wiring between outdoor units or the wiring with the centralized control
system to the centralized control terminal block (TB7).
When using shielded wiring, connect shield ground of the indoor unit transmission
line to the screw (F) and connect shield ground of the line between outdoor units
and the centralized control system transmission line to the shield (S) terminal of
the centralized control terminal block (TB7). In addition, in the case of outdoor
units whose power supply connector CN41 has been replaced by CN40, the shield
terminal (S) of terminal block (TB7) of the centralized control system should also
be connected to the screw (F) using attached lead wire.
2. Conduit mounting plates (ø27) are being provided. Pass the power supply and
transmission wires through the appropriate knock-out holes, then remove the
knock-out piece from the bottom of the terminal block and connect the wires.
3. Fix power source wiring to the terminal block by using buffer bushing for tensile
force (PG connection or the like).
4. The terminal block (TB1B) is for supplying power to the branch box (220
VAC. max 6 A).
Caution:
Never connect the transmission line for the indoor unit or the centralized control
system transmission line to this terminal block (TB1B). If the transmission
lines are connected, the indoor unit or centralized control could be damaged.
– 240
15
6. Electrical work
6.3. Wiring transmission cables
1 Types of control cables
1. Wiring transmission cables
• Types of transmission cables: Shielding wire CVVS, CPEVS or MVVS
• Cable diameter: More than 1.25 mm
2
• Maximum wiring length: Within 200 m
2. M-NET Remote control cables
Kind of remote control cableShielding wire CVVS, CPEVS or MVVS
Cable diameter 0.5 to 1.25 mm
Remarks
When 10 m is exceeded, use cable with the same
specications as transmission line wiring cables.
2
(0.75 to 1.25 mm2)*
* Connected with simple remote controller.
3. MA Remote control cables
Kind of remote control cableSheathed 2-core cable (unshielded) CVV
Cable diameter0.3 to 1.25 mm
2
(0.75 to 1.25 mm2)*
Remarks Within 200 m
* Connected with simple remote controller.
2 Wiring examples
• Controller name, symbol and allowable number of controllers.
NameSymbolAllowable number of controllers
Outdoor unit controllerOC–
PUMY-SP1121 to 9 units per 1 OC *1
M-IC
Indoor unit controller
A-IC
PUMY-SP125 1 to 10 units per 1 OC *1
PUMY-SP140 1 to 12 units per 1 OC *1
PUMY-SP112
2 to 8 units per 1 OC *1PUMY-SP125
PUMY-SP140
Branch box––0 to 2 units per 1 OC
Maximum of 12 control-
Remote controllerRC
M-NET RC *2, *3
lers for 1 OC (Can not be
connected if Branch box
is used.)
MA-RCMaximum of 2 per group
Note:
*1. The number of connectable units may be limited by some conditions such
as an indoor unit’s capacity or each unit’s equivalent power consumption.
*2. Don’t use the Lossnay controller (PZ-61DR-E, PZ-43SMF-E, PZ-52SF-E,
PZ-60DR-E).
*3. An ME remote controller can not be connected to a system that contains
a branch box.
GB
Example of a group operation system with multiple outdoor units (Shielding wires and address setting are necessary.)
<Examples of Transmission Cable Wiring>
■ Refer to Fig. 6-6 from Fig. 6-2.
<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2
and terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the terminal
block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for centralized control (TB7) for the outdoor unit (OC).
e. The jumper connector CN41 on the control panel does not change.
Connect shield ground of the indoor units transmission line to the shield (S) terminal of (TB3) and also connect (S) terminal to the screw (E or F) using attached lead wire.
f.
Connect shield ground of the line between outdoor units and the centralized control system transmission line to the shield (S) terminal of (TB7).
g. Set the address setting switch as follows.
UnitRangeSetting Method
M-IC (Main)01 to 50Use the most recent address within the same group of indoor units
M-IC (Sub)01 to 50
Outdoor unit51 to 100
M-NET RC (Main) *1101 to 150Set at an IC (Main) address within the same group plus 100
M-NET RC (Sub) *1151 to 200Set at an IC (Main) address within the same group plus 150
MA RC—Unnecessary address setting (Necessary main/sub setting)
*1 An ME remote controller cannot be connected to a system that contains a branch box.
Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be
in sequence with the IC (Main)
Use the most recent address of all the indoor units plus 50
* The address automatically becomes “100” if it is set as “01 - 50”.
h. The group setting operations among the multiple indoor units is done by the remote controller (M-NET RC) after the electrical power has been turned on.
<Permissible Lengths>
M-NET Remote controller
1
• Max length via outdoor units: L
• Max transmission cable length: L
• Remote controller cable length:
1+L2+L3+L4
r
and L1+L2+L3+L5 and L1+L2+L6+L7 [ 500 m (1.25 mm² or more)
1
and L3+L4 and L3+L5 and L2+L6 and L7 [ 200 m (1.25 mm² or more)
1
2
2
3
r
r
,
,
4
r
r
+
,
[ 10 m (0.5 to 1.25 mm²)
If the length exceeds 10 m, use a 1.25 mm² shielded wire. The length of this section (L
8
) should be included in the calculation of the
maximum length and overall length.
MA Remote controller
2
• Max length via outdoor unit (M-NET cable): L
• Max transmission cable length (M-NET cable): L
1
c
• Remote controller cable length:
and
1
c
1+L2+L3+L4
c
+
and L1+L2+L6+L7 [ 500 m (1.25 mm² or more)
1
and L3+L4 and L2+L6 and L7 [ 200 m (1.25 mm² or more)
2
3
1
2
3
c
c
and
c
+
+
4
c
c
+
+
[ 200 m (0.3 to 1.25 mm²)
16
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.