Mitsubishi PUMY-P VHMB, PUMY-P YHMB, PUMY-P100VHMB, PUMY-P100VHMB-BS, PUMY-P125VHMB Specifications

...
PUMY-P VHMB(-BS)
OUTDOOR UNIT S Series
Specifications
When the outdoor unit is installed below the indoor unit, top-bottom differential is 20m [65ft].
*1
PUMY-P VHMB(-BS) PUMY-P YHMB(-BS)
OUTDOOR UNIT S (Heat Pump) series Cooling or Heating
The CITY MULTI S-Series for homes and small offices offers all the features and benefits of our large commercial CITY MULTI S-Series. The compact outdoor unit utilizes R410A refrigerant and an INVERTER-driven compressor to use energy effectively.
A maximum of 12 CITY MULTI indoor units can be connected with up to 130% connected capacity, depending on diversity.
Building Comfort solutions in the home or small office
Refrigerant Piping Lengths
Total length Maximum allowable length Farthest indoor from first branch
Vertical differentials between units
Indoor/outdoor (outdoor higher) Indoor/outdoor (outdoor lower) Indoor/indoor
Maximum meters [Feet]
120[393 ] 80[262 ] 30 [98]
Maximum meters [Feet]
30 [98] 20 [65] 12 [39]
Outdoor unit
Indoor unit
Between indoor units top-bottom differential 12m [39ft]
Furthest piping length 80m [262ft]
Large Residences
[4-6HP]
Small Offices
Top-bottom differential 30m [98ft] *1
Page95
Outdoor unit
PUMY-P VHMB(-BS)
OUTDOOR UNIT S Series
Specifications
Power source Cooling capacity (Nominal)
Compressor
FAN
Protection
Refrigerant
Power input Current input COP (kW/kW) Indoor Outdoor
Power input Current input COP (kW/kW) Indoor temp. Outdoor temp.
Total capacity Model/Quantity
Liquid (High press.) Gas (Low press.)
Type Starting method Motor output
Air flow rate
Type Quantity Motor output High pressure protection Inverter circuit (COMP./FAN) Compressor Type Original charge
PUMY-P100VHMB(-BS) PUMY-P125VHMB(-BS) PUMY-P140VHMB(-BS)
kW
BTU/h
kW
A
W.B. D.B.
kW
BTU/h
kW
A
D.B. W.B.
dB<A>
mm(in.) mm(in.)
mm (in.)
kg (lb)
kW
m
3
/min L/s cfm
kW
11
22
Note:
1 Nominal cooling conditions
Indoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DB Pipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)
2 Nominal heating conditions
Indoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WB Pipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)
11.2
38,200
3.34
15.4-14.8-14.1, 15.4
3.35
12.5
42,700
3.66
16.9-16.2-15.5, 16.9
3.42
P15 ~ P125 / 1 ~ 8
49 / 51
ø9.52 (ø3/8)
ø15.88 (ø5/8)
1,350 950 330 (53-3/16 37-7/16 13)
127 (280 lb)
2.2
100 1,667 3,532
Propeller fan 2
0.06 2
R410A 8.5kg (19 lb)
14.0
47,800
4.32
20.0-19.1-18.3, 20.0
3.24
16.0
54,600
4.33
20.0-19.1-18.3, 20.0
3.69
P15 ~ P140 / 1 ~ 10
50 / 52
ø9.52 (ø3/8)
ø15.88 (ø5/8)
1,350 950 330 (53-3/16 37-7/16 13)
127 (280 lb)
2.9
100 1,667 3,532
Propeller fan 2
0.06 2
R410A 8.5kg (19 lb)
15.5
52,900
5.35
24.7-23.6-22.7, 24.7
2.9
18.0
61,400
5.58
25.8-24.7-23.6, 25.8
3.23
P15 ~ P140 / 1 ~ 12
51 / 53
ø9.52 (ø3/8)
ø15.88 (ø5/8)
1,350 950 330 (53-3/16 37-7/16 13)
127 (280 lb)
3.3
100 1,667 3,532
Propeller fan 2
0.06 2
R410A 8.5kg (19 lb)
1-phase 220-230-240V 50Hz, 1-phase 220V 60Hz
15 ~ 24˚C (59 ~ 75˚F)
- 5 ~ 46˚C (23 ~ 115˚F)
10 to 46˚CD.B. (50 to 115˚FD.B.) : in case of connecting PKFY-P15 / P20 / P25 type indoor unit.
15 ~ 27˚C (59 ~ 81˚F)
-15 ~ 15˚C (5 ~ 59˚F)
50 ~ 130% of outdoor unit capacity
Galvanized steel sheet <MUNSELL 3Y 7.8/1.1>
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp.
Inverter
High pressure sensor, High pressure switch 4.15 MPa
Over-heat protection, Over-current protection
Discharge thermo protection, Over-current protection
Page96
Outdoor Unit