PUMY-P VHMB(-BS)
OUTDOOR UNIT
S Series
Specifications
Power source
Cooling capacity
(Nominal)
Temp.
range of
cooling
Heating capacity
(Nominal)
Temp.
range
of heating
Indoor unit
connectable
Sound pressure level
(measured in anechoic room)
Diameter of
refrigerant pipe
External finish
External dimension H ✕ W ✕ D
Net weight
Heat exchanger
Compressor
FAN
Protection
Refrigerant
Power input
Current input
COP (kW/kW)
Indoor
Outdoor
Power input
Current input
COP (kW/kW)
Indoor temp.
Outdoor temp.
Total capacity
Model/Quantity
Liquid (High press.)
Gas (Low press.)
Type
Starting method
Motor output
Air flow rate
Type ✕ Quantity
Motor output
High pressure protection
Inverter circuit (COMP./FAN)
Compressor
Type ✕ Original charge
PUMY-P100VHMB(-BS) PUMY-P125VHMB(-BS) PUMY-P140VHMB(-BS)
kW
BTU/h
kW
A
W.B.
D.B.
kW
BTU/h
kW
A
D.B.
W.B.
dB<A>
mm(in.)
mm(in.)
mm (in.)
kg (lb)
kW
m
3
/min
L/s
cfm
kW
❇1
❇1
❇2
❇2
Note:
❇1 Nominal cooling conditions
Indoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DB
Pipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)
❇2 Nominal heating conditions
Indoor 20˚C (68˚F) DB,Outdoor 7˚C (45˚F) DB/6˚C (43˚F) WB
Pipe length 7.5 m (24-9/16 ft), Level difference 0 m (0 ft)
11.2
38,200
3.34
15.4-14.8-14.1, 15.4
3.35
12.5
42,700
3.66
16.9-16.2-15.5, 16.9
3.42
P15 ~ P125 / 1 ~ 8
49 / 51
ø9.52 (ø3/8)
ø15.88 (ø5/8)
1,350 ✕ 950 ✕ 330 (53-3/16 ✕ 37-7/16 ✕ 13)
127 (280 lb)
2.2
100
1,667
3,532
Propeller fan ✕ 2
0.06 ✕ 2
R410A ✕ 8.5kg (19 lb)
14.0
47,800
4.32
20.0-19.1-18.3, 20.0
3.24
16.0
54,600
4.33
20.0-19.1-18.3, 20.0
3.69
P15 ~ P140 / 1 ~ 10
50 / 52
ø9.52 (ø3/8)
ø15.88 (ø5/8)
1,350 ✕ 950 ✕ 330 (53-3/16 ✕ 37-7/16 ✕ 13)
127 (280 lb)
2.9
100
1,667
3,532
Propeller fan ✕ 2
0.06 ✕ 2
R410A ✕ 8.5kg (19 lb)
15.5
52,900
5.35
24.7-23.6-22.7, 24.7
2.9
18.0
61,400
5.58
25.8-24.7-23.6, 25.8
3.23
P15 ~ P140 / 1 ~ 12
51 / 53
ø9.52 (ø3/8)
ø15.88 (ø5/8)
1,350 ✕ 950 ✕ 330 (53-3/16 ✕ 37-7/16 ✕ 13)
127 (280 lb)
3.3
100
1,667
3,532
Propeller fan ✕ 2
0.06 ✕ 2
R410A ✕ 8.5kg (19 lb)
1-phase 220-230-240V 50Hz, 1-phase 220V 60Hz
15 ~ 24˚C (59 ~ 75˚F)
- 5 ~ 46˚C (23 ~ 115˚F)
10 to 46˚CD.B. (50 to 115˚FD.B.) : in case of connecting PKFY-P15 / P20 / P25 type indoor unit.
15 ~ 27˚C (59 ~ 81˚F)
-15 ~ 15˚C (5 ~ 59˚F)
50 ~ 130% of outdoor unit capacity
Galvanized steel sheet <MUNSELL 3Y 7.8/1.1>
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp.
Inverter
High pressure sensor, High pressure switch 4.15 MPa
Over-heat protection, Over-current protection
Discharge thermo protection, Over-current protection