• Replaced troubleshooting
table with flow chart in
REVISED EDITION-C.
• Some descriptions have
been modified.
• Please void OCH502
REVISED EDITION-B.
Note :
• This service manual
describes technical data
of outdoor unit. As for
indoor units, refer to its
service manual.
...................................
.....................................
.....................
.....
....................................
.................................
..................
.....................
2
5
10
11
17
18
19
29
100
103
109
Model name
indication
OUTDOOR UNIT
PARTS CATALOG (OCB502)
Use new refrigerant pipes.
Store the piping indoors, and both ends of the
piping sealed until just before brazing.
(Leave elbow joints, etc. in their packaging.)
Avoid using thin pipes.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant
charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Make sure that the inside and outside of refrigerant piping is clean and it has no contaminants
such as sulfur, oxides, dirt, shaving particles, etc,
which are hazard to refrigerant cycle.
In addition, use pipes with specified thickness.
The refrigerant oil applied to flare and flange
connections must be ester oil, ether oil or
alkylbenzene oil in a small amount.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
Use the specified refrigerant only.
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the
unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the
spec labels provided with our products.
We will not be held responsible for mechanical failure,
system malfunction, unit breakdown or accidents caused
by failure to follow the instructions.
1SAFETY PRECAUTION
OCH502C
CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
2
[1] Cautions for service
OCH502C
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
·
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.
Gauge manifold· Only for R410A
1
Charge hose· Only for R410A
2
Electronic scale
3
Gas leak detector· Use the detector for R134a, R407C or R410A.
4
Adaptor for reverse flow check· Attach on vacuum pump.
5
Refrigerant charge base
6
Refrigerant cylinder· Only for R410A · Top of cylinder (Pink)
7
Refrigerant recovery equipment
8
Tool nameSpecifications
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
Air purge, refrigerant charge
and operation check
Gas leak check
Refrigerant recovery
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Refrigerant charge
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Refrigerant charge
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil, ether oil and
alkylbenzene oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adapter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
Tool exclusive for R410A
Tools and materialsUseR410A toolsCan R22 tools be used?
(Usable if equipped
with adapter for rever se flow)
(Usable if equipped
with adapter for rever se flow)
(Usable by adjusting
flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
OCH502C
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working
pressure of R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
1 Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7 mm or below.)
2 Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrigerants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A has been
specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A
also has partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe
flaring dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes.
Use torque wrench corresponding to each dimension.
Dimension A
3 Tools for R410A (The following table shows whether conventional tools can be used or not.)
4
Dimension B
(1) Auxiliary heating operation controls another heat source that depends on the main system's operations,
which means the interlock operation shown in "b)" will be possible.
a)
b) Different Indoor unit applications that can be applied:
(2) Outdoor unit DIPSW5-4 for auxiliary heating control:
Set DIPSW5-4 when power is turned off at unit.
OFF:
Disable auxiliary Heating Function (Initial setting)
ON :
Enable auxiliary Heating Function
Indoor unit must be R410A UL model for this function to operate.
2-1. Auxiliary HEATING ON/OFF CONTROL SET-UP
(3) Determine required indoor fans speed during defrost mode:
020k27k39k62K
NoneBlackBlueWhiteRed
Stopped
Setting on
remote
controller
Very LowLowHigh
Note: The setting will be disabled "when Heater contact signal is OFF".
CN22 input resistance ()
CN22 input (cable color)
Fan speed setting
OFF
Fan airflow rate setting
During defrost operation
ON
Wiring
CN22
a) With no auxiliary heating output the Indoor fan normally goes off to prevent cold drafts during the defrost cycles.
b) With auxiliary heating control the auxiliary heat will be on during defrost mode, thus cold drafts will not be present.
(Ducted units only)
c) For models PEFY and PDFY (Ducted) recommended to use "Black" (20K) connector.
d) For models PLFY, PCFY, PKFY and PFFY (Ductless) recommended "None", no connector required.
e) To set the fan airflow rate to be used during defrost operation, insert the resistance that is packed within the optional
adaptor cable kit (PAC-YU24HT-F) into the CN22 sensor input.
You can choose at what speed the indoor fan operates during defrost cycles bases on chart below.
2
OCH502C
OVERVIEW OF UNITS
55
(4) Determine fan airflow setting during indoor thermo-OFF conditions:
A
OCH502C
a) These settings are done within Indoor DIPSW1-7 and DIPSW1-8, see chart below for options.
b) Recommended SW1-7 OFF and SW1-8 ON will determine airflow based on "Setting on the remote controller".
Auxiliary heating
signal
Thermo condition
SW1-7SW1-8
OFFOFFVery low
ONOFFLow
OFFON
ON
ON
Fan speed
setting
OFFON
Setting on
remote
controller
Stopped
Fan speed
setting
Setting on
remote
controller
(5) Setting outdoor unit and auxiliary heat switch over temperatures.
When the DIPSW 5-4 is set to "ON", the outdoor unit and the contact output operates as shown below.
a) Outdoor default setting and operations are shown below:
Stage 1
mb. decreasing- Outdoor unit HP operation
Amb. increasing - Defrost : Heater contact ON signal
- Other than defrost : Contact OFF
Stage 2
- Outdoor unit HP operation
- Heater contact ON signal
a
-12
-C
[10-F]
When the set temperature ranges overlap, the previously set pattern (1,2 or 3) has a priority.
The stage 1 has the highest priority, 2 the second and then 3.
b) Based on above chart listed the sequence of operation on "On ambient decrease"
Stage 1 :(TH7 = > 10
Stage 2 :(TH7 = 10
Stage 3 :(TH7 = < -12
c) Based on above chart listed the sequence of operation on "On ambient increase"
Stage 3 :(TH7 = < 0
Stage 2 :(TH7 = > 0
Stage 1 :(TH7 = > 20
b
-C
0
[32-F]
c
-C
10
[50-F]
:
) : the outdoor unit runs in HP mode.
:
to -12:) : the outdoor unit runs in HP mode with auxiliary heating.
:
) : Auxiliary heating only (Outdoor unit is OFF).
:
) : Auxiliary heating only (Outdoor unit is OFF).
:
to 20:) : Auxiliary heating with outdoor unit in HP mode.
:
) : Outdoor unit in HP mode only.
d
-C
20
[68-F]
TH7 = Outdoor temperature
Stage 3
- Outdoor unit OFF (Standby)
- Heater contact ON signal
6
(6) Locally procured wiring
A basic connection method is shown.
(i.e. interlocked operation with the electric heater with the fan speed setting on high)
Recommended circuit
CN24
Remote control BoardRelay circuit
Adapter
Indoor unit
control board
Outdoor unit
control board
Electric Heater
power source
Electric
Heater
Red1
White 2
Dip switch
SW5-4 "ON"
Preparations in the field
Maximum cable length
is 10 m (32ft)
Red1
Red2
YellowGreen
1-phase power
supply
208V, 230V/60Hz
Control board
FS1, 2 ----- Thermal fuse
H1, H2 ----- Heater
26H --------- Overheat protection
thermostat
88H --------- Electromagnetic contactor
Wiring diagram
For relay X use the specifications given below operation coil
Rated voltage : 12VDC
Power consumption : 0.9W or less
*Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU24HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm
2
to 1.25 mm2 (AWG22 to AWG16)
Do not extend the cable more than 10 meters (32ft).
• A handy remote controller for use in conjunction
with the Melans centralized management system.
M-NET remote controller
• Addresses must be set.
*It is possible only by 1:1 system.
(1 indoor unit of Fresh Air type is connected with 1 outdoor unit.)
Operating temperature range (outdoor temperature) for fresh air type indoor units differ from other indoor units.
Refer to 2-2(2).
PAR-F27MEA-US
MA remote controller
PAR-21MAAU-J, PAR-30MAAU-J
• Address setting is not necessary.
8
2-3. UNIT SPECIFICATIONS
P L F Y - P 30 N B M U - EPU M Y - P 60 N
K M U -BS
PAC ty pe
Frequency
conversion
controller
Refrigerant
R410A/R22
commonness
Refrigerant
R410A
NEW frequency converter
one-to-many air conditioners
(flexible design type)
Indicates equivalent
to Cooling capacity
Indicates equivalent
to Cooling capacity
Power supply
N: Single phase
208/230V 60Hz
Power supply
N: Single phase
208/230V 60Hz
L : Ceiling cassette
K : Wall-mounted type
E : Hidden skylight type
C : Ceiling suspended type
M : Ceiling cassette type
F : Floor standing type
Outdoor unit
model type
Sub-number
Unit model type
UL model
M-NET control
M-NET control
UL model
Salt proof
type
Frequency
conversion
controller
Outdoor unit
MULTI-S
Cooling
W.B. 15 - 24°C [59 - 75°F]
Heating
D.B. 15 - 27°C [59 - 81°F]
:%í&>í)@
Indoor-side intake air temperature
Outdoor-side intake air temperature
'%í&>)@
OCH502C
(1) Method for identifying MULTI-S model
■
Indoor unit < When using Model 30 >
(2) Operating temperature range
■
Outdoor unit <When using model 60 >
Notes D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
*10 - 46°C DB [50 - 115°FDB] : In the case of connecting PKFY-P06/P08 type indoor unit.
Ŷ In the case of connecting fresh air type indoor unit
Indoor-side and Outdoor-side
intake air temperature
** Thermo-off (FAN-mode) automatically starts if the outdoor temp. is lower than 21:D.B.[70°FD.B.].
***Thermo-off (FAN-mode) automatically starts if the outdoor temp. is higher than 20:D.B.[68°FD.B.].
*40m [140ft] : In the case of installing outdoor unit lower than indoor unit.
**
10 - 46°C [50 - 115°F]DB : In the case of connecting PKFY-P06/P08 type
indoor unit.
***Electrical data is for only outdoor unit.
(In case of connecting 4 indoor units of PKFY-P06NBMU×2 and PKFY-
P24NKMU×2)
Btu/h=kW × 3,412 CFM=K/min × 35.31 lbs=kg/ 0.4536
Note: Above specification data is subject to rounding variation.
10
4
OCH502C
DATA
4-1. COOLING AND HEATING CAPACITY AND CHARACTERISTICS
4-1-1. Method for obtaining system cooling and heating capacity:
To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings
of all the indoor units connected to the outdoor unit (see table below), and then use this total to find the standard capacity with
the help of the tables on 4-2. STANDARD CAPACITY DIAGRAM.
(1) Capacity of indoor unit
Model number for
indoor unit
Model Capacity6812151824273036485472
(2) Sample calculation
1 System assembled from indoor and outdoor unit (in this example the total capacity of the indoor units is greater than that of
the outdoor unit)
• Outdoor unit PUMY-P60NKMU
• Indoor unit PKFY-P08NAMU-E o 2 , PLFY-P18NBMU-E o 3
2 According to the conditions in 1, the total capacity of the indoor unit will be: 8 o 2 + 18 o 3 = 70
3 The following figures are obtained from the 52 total capacity row of the standard capacity table (4-2.):
Capacity (Btu/h)
CoolingHeatingCoolingHeatingCoolingHeating
62,000
A
Model 06 Model 08 Model 12 Model 15 Model 18 Model 24 Model 27 Model 30 Model 36 Model 48 Model 54 Model 72
68,000
B
Outdoor unit power consumption (kW)
4.625.9120.326.0
Outdoor unit current (A)/230V
4-1-2. Method for obtaining the heating and cooling capacity of an indoor unit:
(1) The capacity of each indoor unit (Btu/h) = the capacity A (or B) o
(2) Sample calculation (using the system described above in 4-1-1. (2) ):
During cooling: During heating:
• The total model capacity of the indoor unit is:
8000 o 2 + 18000 o 3 = 70000Btu/h
Therefore, the capacity of PKFY-P08NAMU-E and
PLFY-P18NBMU-E will be calculated as follows by
using the formula in 4-1-2. (1):
Model 08= 62,000 o = 7,090 Btu/h
Model 18= 62,000 o = 15,940 Btu/h
8000
70000
18000
70000
• The total model capacity of indoor unit is:
9000 o 2 + 20000 o 3 = 78000 Btu/h
Therefore, the capacity of PKFY-P08NAMU-E and
PLFY-P18NBMU-E will be calculated as follows by
using the formula in 4-1-2. (1):
Model 08= 68,000 o = 7,850 Btu/h
Model 18= 68,000 o = 17,440 Btu/h
total model capacity of all indoor units
model capacity
9000
78000
20000
78000
11
4-2. STANDARD OPERATION DATA (REFERENCE DATA)
OCH502C
Operation
Ambient
temperature
Indoor unit
Operating
conditions
Piping
Fan speed—Hi
Amount of refrigerantkg [lbs-oz]8.5 [18]
Electric currentA21.427.4
Indoor
Outdoor35°C/— [95°F/—]8.3°C/6.1°C [47°F/43°F]
No. of connected units
No. of units in operation4
Model—06×2/24×2
Main pipe
Branch pipe2.5 [8-1/4]
Total pipe length15 [49-1/4]
Individual capacity under stated conditions = total capacity under the stated conditions o
(3) Capacity correction coefficient curve
Figure 1 Cooling performance curve
1.4
1.3
1.2
1.1
1.0
0.9
Ratio of cooling capacity
0.8
0.7
0.6
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
Ratio of power input
-1001020304050
1432506886104122
OUTDOOR
:WB (°FWB)
24 (75.2)
22 (71.6)
20 (68)
18 (64.4)
16 (60.8)
INDOOR
:WB(°FWB)
24 (75.2)
22 (71.6)
20 (68)
18 (64.4)
16 (60.8)
INDOOR
[°CDB]
[°FDB]
Figure 2 Heating performance curve
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
Ratio of heating capacity
Ratio of power input
-25-20-15-10-501510520
-13-4514233259504168
individual capacity at the rated time
total capacity at the rated time
:DB (°FDB)
15 (59)
21.1 (70)
25 (77)
27.2 (81)
INDOOR
:DB(°FDB)
15 (59)
21.1 (70)
25 (77)
27.2 (81)
INDOOR
[°CWB]
[°FWB]
OUTDOOR
14
Figure 3 High heating performance curve
OCH502C
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
Ratio of heating capacity
:DB (°FDB)
15 (59)
21.1 (70)
25 (77)
27.2 (81)
INDOOR
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
-25-20-15-10-501510520
-13-4514233259504168
OUTDOOR
:DB (°FDB)
15 (59)
21.1 (70)
25 (77)
27.2 (81)
INDOOR
[°CWB]
[°FWB]
4-4-2. Correcting capacity for changes in the length of refrigerant piping
(1) During cooling, obtain the ratio (and the equivalent piping length) of the outdoor units rated capacity and the total in-use
indoor capacity, and find the capacity ratio corresponding to the standard piping length from Figure 3. Then multiply by
the cooling capacity from Figure 1 to obtain the actual capacity.
(2) During heating, find the equivalent piping length, and find the capacity ratio corresponding to standard piping length from
Figure 3. Then multiply by the heating capacity from Figure 2 to obtain the actual capacity.
• Method for obtaining the equivalent piping length
Equivalent length for type P60 = (length of piping to farthest indoor unit) + (0.3 o number of bends in the piping) (m)
Length of piping to farthest indoor unit: 80 m [262 ft]
Heating
Cooling
15
4-4-3. Correction of heating capacity for frost and defrosting
1.5m
[4.9 ft]
1m [3.3 ft]
MICROPHONE
UNIT
GROUND
OCH502C
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction
factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature (W.B.°F)
Outdoor Intake temperature (W.B.°C)
Correction factor
433936322825211814
6420-2-4-6-8-10
1.00.980.890.880.890.90.950.950.95
4-5. NOISE CRITERION CURVES
SPL(dB)
PUMY-P60NKMU
PUMY-P60NKMU-BS
90
80
MODE
COOLING
HEATING
LINE
58
59
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
16
5
OCH502C
OUTLINES AND DIMENSIONS
PUMY-P60NKMU
PUMY-P60NKMU-BS
2-U Shaped notched holes
(Foundation Bolt M10<W3/8>)
225
<8-27/32>
Rear Air Intake
600<23-5/8>
Installation Feet
225
<8-27/32>
4 PIPING-WIRING DIRECTIONS
Piping and wiring connections
can be made from 4 directions:
FRONT, Right, Rear and Below.
Side Air Intake
56<2-7/32>
40<1-9/16>
417<16-13/32>
330<13>
0
53<2-3/32>
42
70
<1-21/32>
61<2-13/32>
<2-3/4>
25<31/32>
28<1-3/32>19<3/4>370<14-9/16>
Terminal connection
LeftFor the power supply
2-12×36 Oval holes
(Foundation Bolt M10<W3/8>)
Air Discharge
Ground for the power supply
("GR"marking position)
1050<41-11/32>
362<14-1/4>
Handle for moving
Side Air IntakeRear Air Intake
CenterFor the transmission line
RightFor concentration control
Ground for the transmission line
Ground for concentration control
( )
Service panel
Handle for moving
632<24-7/8>
Handle for
moving
1338<52-11/16>
Air intake
1079<42-15/32>
Unit : mm <inch>
Rear piping cover
Front piping cover
+
1ޓ450<17-23/32>
+
1ޓ393<15-15/32>
2
1
26<1-1/32>
369<14-17/32>
86<3-3/8>
81<3-3/16>
<6-1/16>
154
22.5<7/8>
3/4 Conduit
attachment
When installing the conduit.
Set the attachment to the
inner side of each panel.
60<2-3/8>
27.8<1-3/32>
22.2<7/8>
:
:
92
:
37<1-15/32>Knockout)
24<15/16>Knockout)
:
:
Conduit hole
(
Conduit hole
(
60<2-3/8>
Bottom piping hole
(Knockout)
<5-11/32>
136
24.7<31/32>
5<3/16>
100
Scale 1:5
<3-15/16>
1/2 Conduit
attachment
Rear piping hole
(Knockout)
<3-5/8>
33<1-5/16>)
:
Drain hole
㧔5-
160
<6-5/16>
160
<6-5/16>
160
<6-5/16>
110<4-11/32>
45<1-25/32>
92<3-5/8>
75<2-15/16>
<Foundation bolt height>
3 FOUNDATION BOLTS
Please secure the unit firmly
with 4 foundation (M10<W3/8>) bolts.
(Bolts and washers must be
purchased locally.)
<5-29/32>
150
Min.
2 SERVICE SPACE
Dimensions of space needed
for service access are
shown in the below diagram.
Min. 10mm<3/8>Min. 10mm<3/8>
FREE
1 FREE SPACE (Around the unit)
The diagram below shows a basic example.
Explantion of particular details are
given in the installation manuals etc.
FOUNDATION
30<1-3/16>
Max.
<19-11/16>
500
Min.
Min.
10<3/8>
Min.
500
<19-11/16>
Service space
Min. 1000mm<39-3/8>Min. 150mm<5-29/32>
1717
Handle for
moving
Example of Notes
2
1
ޓޓRefrigerant GAS pipe connection (FLARE):19.05㧔3/4F)
• WARNING: When the main supply is turned off, the voltage [340 V] in the main capacitor will drop to 20 V in approx. 2
minutes (input voltage: 230 V). When servicing, make sure that LED1, LED2 on the outdoor circuit board goes out, and then
wait for at least 1 minute.
• Components other than the outdoor board may be faulty: Check and take corrective action, referring to the service manual.
Do not replace the outdoor board without checking.
NOTES:
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch
(SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
• During normal operation
• The LED indicates the drive state of the controller in the outdoor unit.
Bit
Compressor
Indication
operated
• When fault requiring inspection has occurred
The LED alternately indicates the inspection code and the location of the unit in which
the fault has occurred.
>
Centralized Control Line
>
>
>
>
>
>
>
1
2
52C321S44SV15(SV2)
Reactor
DCL
>
CBMain Smoothing Capacitor
>
P.B.Power Circuit Board
Connection Terminal <U/V/W-Phase
TABU/V/W
TABLI/NI
Connection Terminal <L/N-Phase
Connection Terminal <DC Voltage
TABP2
Connection Terminal <DC Voltage
TABN2
Connection Terminal <Reactor
DCL1,DCL2
Power Module
IGBT
Connection Terminal <Ground
EI,E2,E3,E4
MULTI.B.
Controller Circuit Board
SW1
Switch <Display Selection
SW2
Switch <Function Selection
SW3
SW4
SW5
SW6
Switch <Test Run
Switch <Model Selection
Switch <Function Selection
Switch <Function Selection
>
18
SW7
SW8
SWU1
>
SWU2
SS
>
>
CN3D
>
CN3S
>
CN3N
CN51
>
LED1,LED2
>
>
>
>
>
>
LED3
F1,F2
X501
M-P.B.
TP1
~
505
678
Always lit
Switch <Function Selection
Switch <Model Selection
Switch <Unit Address Selection, 1st digit
Switch <Unit Address Selection, 2nd digit>
Connector <Connection For Option
Connector <Connection For Option
Connector <Connection For Option
Connector <Connection For Option
Connector <Connection For Option
LED <Operation Inspection Display
LED <Power Supply to Main Microcomputer>
Fuse <T6. 3AL250V
Relay
M-NET Power Circuit Board
ConnectionTerminal <Ground>
[Example]
When the compressor and
SV1 are turned during cooling
operation.
• Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed
in the standard system with detailed explanation.
The explanation for the system in this section : Use 1 single outdoor unit and multiple outdoor units for M-NET remote control
system.
Use 1 single outdoor unit and multiple indoor units in the multiple outdoor
units for the M-NET remote control system.
A. Example of a M-NET remote controller system (address setting is necessary.)
Example of wiring control cablesWiring Method and Address Setting
1. Standard operation
• 1 remote controller for each
indoor unit.
• There is no need for setting
the 100 position on the remote
controller.
2. Operation using 2 remote controllers
• Using 2 remote controllers
for each indoor unit.
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit
(OC) to terminals M1 and M2 on the transmission
cable block (TB5) of each indoor unit (IC). Use nonpolarized 2 wire.
b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) for each indoor unit with the
terminal block (TB6) for the remote controller (RC).
c. Set the address setting switch (on outdoor unit P.C.B)
as shown below.
Unit
Indoor unit (IC)
Outdoor unit
(OC)
Remote
controller (RC)
Range
001 to 050
051 to 100
101 to 150
Setting Method
—
Use the smallest
address of all the indoor
unit plus 50.
Indoor unit address plus
100.
a. Same as above.
b. Same as above.
c. Set address switch (on outdoor unit P.C.B) as
shown below.
Unit
Indoor Unit (IC)
Outdoor unit
(OC)
Main Remote
Controller (RC)
Sub Remote
Controller (RC)
Range
001 to 050
051 to 100
101 to 150
151 to 200
Setting Method
—
Use the smallest
address of all the indoor
units plus 50.
Indoor unit address plus
100.
Indoor unit address plus
150.
3. Group operation
OC
51
101
TB5
M1 M2
AB
RC
TB3
TB7
M1 M2
S
M1 M2
S
• Multiple indoor units operated
Combinations of 1 through 3 above are possible.
together by 1 remote controller
IC(Main)
01
S
TB15
12
TB5
M1 M2
IC(Sub)
02
S
21
TB15
12
a. Same as above.
b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) of the IC main unit with the most
recent address within the same indoor unit (IC) group
to terminal block (TB6) on the remote controller.
c. Set the address setting switch (on outdoor unit P.C.B)
as shown below.
Unit
IC (Main)
IC (Sub)
Outdoor Unit
Main Remote
Controller
Sub Remote
Controller
Range
001 to 050
001 to 050
051 to 100
101 to 150
151 to 200
Use the smallest address within the
same group of indoor units.
Use an address, other than that of
the IC (Main) from among the units
within the same group of indoor
units. This must be in sequence with
the IC (Main).
Use the smallest address of all the
indoor units plus 50.
Set at an IC (Main) address within
the same group plus 100.
Set at an IC (Main) address within
the same group plus 150.
Setting Method
d. Use the indoor unit (IC) within the group with the
most functions as the IC (Main) unit.
• Name, Symbol and the Maximum Remote controller Units for Connection
OCH502C
NameSymbolMaximum units for connection
Outdoor unitOC—
Indoor unitIC1 OC unit can be connected to 1-12 IC units
M-NET remote
controller
RC
Maximum 2 RC for 1 indoor unit, Maximum 12 RC for 1 OC
2. If the length exceeds 10 meters
[33ft], the exceeding section
should be 1.25 mm² [AWG16]
and that section should be a
value within the total extension
length of the transmission cable
and maximum transmission
cable length. (L
3)
Same as above
•
M-NET remote controller (RC) and MA remote controller (MA) cannot be used together.
• Do not connect anything with TB15 of indoor unit (IC).
TB3
M1 M2
TB3
M1M2
S
OC
51
S
OC
51
M1 M2
TB7
M1M2
TB7
S
S
TB5
M1M2
TB5
M1 M2
AB
101
RC
IC
01
TB15
12
S
IC
01
TB15
12
S
TB5
M1M2
TB5
M1 M2
S
02
IC
02
TB15
12
S
AB
TB15
MA
IC
• Use the indoor unit (IC)
TB15
12
address plus 150 as the
sub remote controller
address. In this case, it
should be 152.
• 3 or more remote con-
AB
101
RC
(Main)
ABABABAB
151
RC
(Sub)
102
RC
(Main)
103
(Sub)
RC
104
RC
troller (RC) cannot be
connected to 1 indoor
unit.
Same as above
TB3
M1 M2
S
OC
51
TB7
M1 M2
IC(Main)
01
TB5
TB15
12
M1 M2
S
S
TB5
M1 M2
IC(Sub)
02
S
TB15
12
• The remote controller
address is the indoor
unit main address plus
AB
102
RC
100. In this case, it
should be 101.
22
B. Example of a group operation system with 2 or more outdoor units and a M-NET remote controller.
TB7
TB3
IC
(51)
TB5
RC
(01)
IC
TB5
(03)
IC
TB5
(02)
IC
TB5
(04)
IC
TB5
(05)
IC
TB5
(07)
IC
TB5
(06)
L2
L1
(101)
RC
(105)
RC
(104)
RC
(155)
OC
TB7
(53)
OC
3
Power Supply
Unit
System
controller
L3
L6
L7
L4
L5
2
4
1
: Group
: Group
: Group
: Shielded Wire
: Sub Remote Controller
N
N
N
N
M1M2
S
M1M2
S
M1 M2
S
M1 M2
S
ABABAB
M1 M2
S
M1 M2
S
M1 M2
S
S
M1M2
S
TB3
M1M2
S
M1M2
S
AB
M1M2
M1 M2
S
M1 M2
S
OCH502C
(Address settings are necessary.)
Examples of Transmission Cable WiringWiring Method Address Settings
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit
(IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit
(OC).
e. DO NOT change the jumper connector CN41 on MULTI controller board.
f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary. Connect the termi-
nal S on the power supply unit with the earth.
g. Set the address setting switch as follows.
UnitRangeSetting Method
IC (Main)01 to 00
IC (Sub)01 to 50
Outdoor Unit51 to 100
Main Remote Controller101 to 150
Sub Remote Controller151 to 200
MA Remote Controller—
h. The group setting operations among the multiple indoor units are done by the remote controller (RC) after the electri-
cal power has been turned on.
Use the smallest address within the same group of indoor units.
Use an address, other than the IC (Main) in the same group of indoor units.
This must be in sequence with the IC (Main).
Use the smallest address of all the indoor units plus 50.
*The address automatically becomes “100” if it is set as “01 - 50”.
Set at an IC (Main) address within the same group plus 100.
Set at an IC (Main) address within the same group plus 150.
Unnecessary address setting (Necessary main/ sub setting)
23
• Name, Symbol, and the Maximum Units for Connection
OCH502C
• Longest length via outdoor units : L1+L2+L3+L4, L1+L2+L3+L5, L1+L2+L6+L7[ 500 meters [1450 ft] (1.25 mm² [AWG16])
1,R2, R2+R3, R4[ 10 meters [33 ft] (0.5 to 1.25 mm² [AWG20 to AWG16])
If the length exceeds 10 meters [33 ft], use a 1.25 mm² [AWG16] shielded wire. The
Permissible Length
length of this section (L
and overall length.
8) should be included in the calculation of the maximum length
Prohibited items
OC
(51)
TB7TB3
M1 M2
S
M1 M2
S
OC
(53)
TB7
TB3
M1 M2
S
Unit
M1M2
S
System
controller
M1M2
S
S
M1M2
Power Supply
: Group
: Group
: Group
: Shielded Wire
: Sub Remote Controller
( ): Address
TB5
M1 M2
TB5
M1 M2
AB
RC
(104)
(02)
(04)
IC
S
IC
S
TB5
M1 M2
(105)
RC
TB5
M1 M2
(05)
(07)
IC
S
IC
S
IC
(01)
TB5
M1 M2
S
ABABAB
(101)
RC
IC
(03)
TB5
M1 M2
S
(155)
RC
IC
(06)
TB5
M1 M2
S
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to
different outdoor units (OC).
• Set all addresses to ensure that they are not overlapped.
• M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wring
together
24
C. Example of a MA remote controller system (address setting is not necessary.)
OCH502C
NOTE : In the case of same group operation, need to set the address that is only main indoor unit.
Example of wiring control cablesWiring Method and Address Setting
1. Standard operation
L
1L2
OC
00
TB3
TB7
M1 M2SM1 M2
S
TB5
M1 M2
IC
00
TB15
12
S
N1
AB
TB5
M1 M2
IC
00
TB15
12
S
AB
a. Use feed wiring to connect terminals M1 and M2
on transmission cable block (TB3) for the outdoor
unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use
non-polarized 2 wire.
b. Connect terminals 1 and 2 on transmission cable
terminal block (TB15) for each indoor unit with the
terminal block for the MA remote controller (MA).
N2
• 1 remote controller for each
indoor unit.
2. Operation using two remote controllers
OC
00
IC
00
TB5
TB3
TB7
M1 M2SM1 M2
S
N3
• Using 2 remote controllers
for each indoor unit.
M1 M2
TB15
S
12
AB
MA
3. Group operation
OC
00
IC
00
TB3
TB7
M1 M2SM1 M2
S
N7
TB5
TB15
M1 M2SM1 M2
AB
MAMA
IC
00
TB5
TB15
M1 M2
S
N4
AB
MAMAMA
12
N5
ABAB
IC
00
TB5
S
M1 M2
S
N6
TB15
12
a. The same as above.
b. The same as above.
c. In the case of using 2 remote controllers, connect
terminals 1 and 2 on transmission cable terminal
block (TB15) for each indoor unit with the terminal
block for 2 remote controllers.
· Set the sub remote controller position for one of
MA remote controller’s main switch.
Refer to the installation manual of MA remote con-
troller
a. The same as above.
b. The same as above.
c. Connect terminals 1 and 2 on transmission cable
terminal block (TB15) of each indoor unit, which is
doing group operation with the terminal block the MA
remote controller. Use non-polarized 2 wire.
d. In the case of same group operation, need to set the
address that is only main indoor unit. Please set the
smallest address within number 01-50 of the indoor
unit with the most functions in the same group.
• Multiple indoor units operated
together by 1 remote controller
Combinations of 1 through 3 above are possible.
MA
N8
25
Permissible LengthsProhibited items
OCH502C
Longest transmission cable length
L
1 + L2[ 200 m [656 ft] (1.25 mm²
[AWG16])
MA remote controller cable length
R
1, R2[ 200 m [656 ft] (0.3 ~ 1.25
mm² [AWG22 to AWG16])
Longest transmission cable length
The same as above.
MA remote controller cable length
R
3 +R4, R5 +R6[ 200 m [656 ft]
(0.3 ~ 1.25 mm² [AWG22 to
AWG16])
TB3
M1 M2
S
OC
00
OC
00
TB7
M1 M2
The MA remote controller and the
M-NET remote controller cannot be
used together with the indoor unit
of the same group.
IC
00
TB5
TB15
S
M1 M2
12
S
AB
TB5
M1 M2
IC
00
TB15
12
S
ABAB
MAMARC
3 MA remote controller or more
cannot be connected with the
indoor unit of the same group.
IC
00
IC
00
Longest transmission cable length
The same as above.
MA remote controller cable length
R
7 +R8[ 200 m [656 ft] (0.3 ~ 1.25
mm² [AWG22 to AWG16])
TB3
M1 M2
TB3
M1 M2
S
S
OC
TB7
M1 M2
TB7
M1 M2
TB5
TB15
S
M1 M2
ABABABABAB
12
S
MA
TB5
TB15
12
M1 M2
S
MAMAMAMA
The second MA remote controller is
connected with the terminal block
(TB15) for the MA remote controller
of the same indoor unit (IC) as the
first remote control.
IC00
00
TB5
TB15
12
M1 M2
S
S
TB5
M1 M2
S
IC
00
TB15
12
26
AB
MA
AB
MA
D. Example of a group operation with 2 or more outdoor units and a MA remote controller.
OCH502C
(Address settings are necessary.)
L1
L2
L6
Examples of Transmission Cable Wiring
L7
: Group
: Group
: Group
: Shielded Wire
: Sub Remote Controller
( ): Address
OC
(51)
TB7
TB3
M1 M2SM1 M2
OC
(53)
TB7
TB3
M1 M2
M1M2
S
Power Supply
Unit
M1M2
S
System
controller
M1M2
S
IC
(05)
TB15
S
12
ABAB
MAMAMA
IC
(07)
TB15
S
12
IC
2
m
(06)
TB5
TB15
M1M2
S
12
1
m4
m
3
m
IC
(01)
S
TB15TB15
M1 M2
S
12
AB
m3
MA
L3
IC
(03)
TB15
S
M1 M2
TB5
S
12
IC
2
m
(02)
TB5TB5
M1 M2
S
12
1
m
M1M2
TB5
L4
IC
(04)
TB5
M1 M2
TB15
S
12
AB
TB5
M1 M2
1
m
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit
(IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit
(OC).
e. DO NOT change the jumper connector CN41 on MULTI controller board.
f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary. Connect the termi-
nal S on the power supply unit with the earth.
g. Set the address setting switch as follows.
UnitRangeSetting Method
IC (Main)01 to 00
IC (Sub)01 to 50
Wiring Method Address Settings
Outdoor Unit51 to 100
Main Remote Controller101 to 150
Sub Remote Controller151 to 200
MA Remote Controller—
Use the smallest address within the same group of indoor units.
Use an address, other than the IC (Main) in the same group of indoor units.
This must be in sequence with the IC (Main).
Use the smallest address of all the indoor units plus 50.
*The address automatically becomes “100” if it is set as “01 - 50”.
Set at an IC (Main) address within the same group plus 100.
Set at an IC (Main) address within the same group plus 150.
Unnecessary address setting (Necessary main/ sub setting)
h. The group setting operations among the multiple indoor units are done by the remote controller (RC) after the electri-
cal power has been turned on.
27
• Name, Symbol, and the Maximum Units for Connection
OCH502C
Longest length via outdoor unit (M-NET cable):
L
1+L2+L3+L4
and L1+L2+L6+L7 [ 500 m [1640 ft] (1.25 e [AWG16] or more)
Longest transmission cable length (M-NET cable):
L
1
and L3+L4 and L6 and L2+L6 and L7 [ 200 m
Remote controller cable length:
m1
Permissible LengthProhibited items
and m1+m2+m3 and m1+m2+m3+m4
[ 200 m
[656 ft]
[656 ft]
(1.25 e
[AWG16]
(0.3 to 1.25 e
or more)
[AWG22 to AWG16]
)
OC
(51)
TB7TB3
M1M2
M1M2
S
S
OC
(53)
TB7
TB3
M1M2
S
Unit
M1 M2
S
System
controller
M1 M2
S
S
M1M2
Power Supply
: Group
: Group
: Group
: Shielded Wire
: Sub Remote Controller
( ): Address
IC
(01)
TB5 TB15TB15
M1 M2
S
12
AB
MA
IC
(03)
TB15
TB5
M1 M2
S
12
TB5
M1 M2
TB5
M1 M2
IC
(02)
IC
(04)
S
S
IC
(05)
TB15TB5
M1 M2
TB5
M1 M2
S
12
ABAB
MAMAMA
IC
(07)
S
12
12
TB15TB15
12
AB
IC
(06)
TB15TB5
M1 M2
S
12
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to
different outdoor units (OC).
• M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wring
together.
28
8TROUBLESHOOTING
ON/OFF
TEST RUN
°C
1Hr.
FILTER
CHECK TEST
TEMP.
TIMER SET
Check code indicator (see NOTE 1)
Test run remaining time indicator (see NOTE 3)
Display panel
(M-NET Remote controller)
ON/OFF button
ON/OFF LED (Lights up in operation)
LOUVER button
TEST RUN button
AIR DIRECTION button
FAN SPEED button
TEST RUN indicator
Indoor unit liquid pipe temperature indicator
(see NOTE 4)
(Cooling/Heating)
OPERATION
SWITCH button
,
Control panel
OCH502C
8-1. CHECK POINTS FOR TEST RUN
8-1-1. Procedures of test run
(1) Before a test run, make sure that the following work is completed.
• Installation related :
Make sure that the panel of cassette type and electrical wiring are done.
Otherwise electrical functions like auto vane will not operate normally.
• Piping related :
Perform leakage test of refrigerant and drain piping.
Make sure that all joints are perfectly insulated.
Check stop valves on both liquid and gas side for full open.
• Electrical wiring related :
Check ground wire, transmission cable, remote controller cable, and power supply cable for secure connection.
Make sure that all switch settings of address or adjustments for special specification systems are correctly settled.
(2) Safety check :
With the insulation tester of 500V, inspect the insulation resistance.
Do not touch the transmission cable and remote controller cable with the tester.
The resistance should be over 1.0 M". Do not proceed inspection if the resistance is under 1.0 M".
Inspect between the outdoor unit power supply terminal block and ground first, metallic parts like refrigerant pipes or the
electrical box next, then inspect all electrical wiring of outdoor unit, indoor unit, and all linked equipment .
(3) Before operation :
a) Turn the power supply switch of the outdoor unit to on for compressor protection. For a test run, wait at least 12 hours
from this point.
b) Register control systems into remote controller(s). Never touch the on/off switch of the remote controller(s). Refer
to “ 8-1-2. Special Function Operation and Settings (for M-NET Remote Controller)” as for settings. In MA remote
controller(s), this registration is unnecessary.
(4) More than 12 hours later from power supply to the outdoor unit, turn all power switch to on for the test run. Perform test run
according to the “Operation procedure” table of the bottom of this page. While test running, make test run reports .
(5) When you deliver the unit after the test run, instruct the end user for proper usage of the system using owners’ manual and
the test run report you made to certificate normal operation. If abnormalities are detected during test run, refer to “8-1-3.
Countermeasures for Error During Test Run”. As for DIP switch setting of outdoor unit, refer to “8-5. INTERNAL SWITCH
FUNCTION TABLE”.
Turn on the main power supply of all units at least 12 hours before test run. ”HO” appears on display panel for 3 min.
1
12 hours later, press TEST RUN button twice to perform test run. “TEST RUN “ appears on display panel.
2
Press OPERATION SWITCH button to make sure that air blows out.
3
Select Cooling (or Heating) by OPERATION SWITCH button to make sure that cool (or warm) air blows out.
4
Press Fan speed button to make sure that fan speed is changed by the button.
5
Press AIR DIRECTION button or LOUVER button to make sure that air direction is adjustable (horizontal, downward, upward, and each angle).
6
Check outdoor fans for normal operation.
7
Check interlocked devices (like ventilator) for normal operation, if any. This is the end of test run operation.
8
Press ON/OFF button to stop and cancel test run.
9
Notes: 1. If error code appears on remote controller or remote controller malfunctions, refer to “ 8-1-3. Countermeasures for Error During Run”.
2.
3. During test run, the indoor liquid pipe temperature is displayed on remote controller instead of room temperature.
4.
During test run operation, 2-hour off timer activates automatically and remaining time is on remote controller and test run stops 2 hours later.
Depending on a model, “This function is not available” appears when air direction button is pressed. However, this is not malfunction
Operation procedure
2929
.
8-1-2. Special Function Operation and Settings (for M-NET Remote Controller)
(alternating
display)
These alternating IC or LC displays will appear
when entry is completed normally.
A flashing “88” will appear if there is a
problem with the entry (indicating that the
unit does not exist).
OCH502C
• It is necessary to perform “group settings” and “paired settings” at making group settings of different refrigerant systems
(multiple outdoor unit).
(A) Group settings: Enter the indoor unit controlled by the remote controller, check the content of entries, and clear entries,
etc.
(B) Paired settings: Used to set the linked operation of a Lossnay unit.
(1) Entering address: Follow the steps below to enter the addresses of the indoor unit using the remote controller.
a) Group settings
• Turning off the remote controller: Press the ON/OFF button to stop operation (the indicator light will go off).
• Changing to indoor unit address display mode: If the FILTER and k buttons on the remote controller are pressed simultaneously and held for 2 seconds, the display shown in Figure 1 will appear.
• Changing address: Press the temperature adjustment
be entered.
• Entering the displayed address: Press the TEST RUN button to enter the indoor unit with the displayed address.
The type of the unit will be displayed as shown in Figure 2 if entry is completed normally.
If a selected indoor unit does not exist, an error signal will be displayed as shown in Figure 3. When this happens, check
whether the indoor unit actually exists and perform entry again.
• Returning to the normal mode after completing entry: Press the FILTER and k buttons simultaneously and hold for 2
seconds to return to the normal mode.
buttons to change the displayed address to the address to
Figure 1. (A) Group setting display
b) Paired Settings
• Turn off the remote controller: Press the remote controller’s ON/OFF button to turn it off (the indicator light will go off).
• Put in indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and
hold for 2 seconds.
*The above steps are the same as when making group settings (A).
• Changing to the linked operation unit address display state: The display shown in Figure 4 will appear when the
button on the remote control is pressed.
• Displaying the address of the Lossnay unit and linked indoor unit: In this situation, the indoor unit number will be the lowest
address of the group. The Lossnay unit will not operate if this setting is incorrect.
* If the temperature adjustment buttons are pressed, the address may be changed to the indoor unit that are to be
linked.
* If the time setting buttons are pressed, the address of the linked units may be changed to the address where it is
desired to enter the Lossnay .
• Linking the Lossnay and the indoor unit: The display shown in Figure 5 will appear when the TEST RUN button is pressed.
The indoor unit whose address is displayed and the Lossnay unit with a linked address will operate in a linked manner.
* If it is desired to display the address of the Lossnay in the indoor unit address, display the indoor unit address in the linked
unit address, and the above content will also be recorded.
* Apart from the indoor unit with the lowest address in the group, display and enter the addresses of the other indoor unit that
are to be linked with the Lossnay unit.
• Returning to the normal mode after completing entry: Press the FILTER and k buttons on the remote controller simultaneously and hold for 2 seconds to return to the normal mode.
Figure 2. Normal completion of entry
Figure 3. Entry error signal
Flashing “88” indicates entry error.Type of unit is displayed.
a
Figure 4. (B) Making paired settings
The addresses of indoor
unit and linked units are
displayed simultaneously.
Figure 5. Completing normal entry
30
Loading...
+ 84 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.