Mitsubishi PUMY-P60NKMU, PUMY-P60NKMU-BS Service Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
HFC
utilized
R410A
TECHNICAL & SERVICE MANUAL
November 2013
No. OCH502
REVISED EDITION-C
Outdoor unit [Model Name]
PUMY-P60NKMU
PUMY-P60NKMU-BS
[Service Ref.]
PUMY-P60NKMU PUMY-P60NKMU-BS
CONTENTS
1. SAFETY PRECAUTION
2. OVERVIEW OF UNITS
4. DATA
5. OUTLINES AND DIMENSIONS
6. WIRING DIAGRAM
7.
8. TROUBLESHOOTING
9. ELECTRICAL WIRING
10. REFRIGERANT PIPING TASKS
11. DISASSEMBLY PROCEDURE
................................................................
NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION
..........................................
.........................................
Revision:
• Replaced troubleshooting table with flow chart in
REVISED EDITION-C.
• Some descriptions have been modified.
• Please void OCH502 REVISED EDITION-B.
Note :
• This service manual
describes technical data of outdoor unit. As for indoor units, refer to its service manual.
...................................
.....................................
.....................
.....
....................................
.................................
..................
.....................
2
5
10
11
17
18
19
29
100
103
109
Model name indication
OUTDOOR UNIT
PARTS CATALOG (OCB502)
Use new refrigerant pipes.
Store the piping indoors, and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
Avoid using thin pipes.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil etc.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil etc.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contaminants such as sulfur, oxides, dirt, shaving particles, etc, which are hazard to refrigerant cycle. In addition, use pipes with specified thickness.
The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbenzene oil in a small amount.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Use the specified refrigerant only.
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
1 SAFETY PRECAUTION
OCH502C
CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
2
[1] Cautions for service
OCH502C
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type. Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
·
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.
Gauge manifold · Only for R410A
1
Charge hose · Only for R410A
2
Electronic scale
3
Gas leak detector · Use the detector for R134a, R407C or R410A.
4
Adaptor for reverse flow check · Attach on vacuum pump.
5
Refrigerant charge base
6
Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
7
Refrigerant recovery equipment
8
Tool name Specifications
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
· Use pressure performance of 5.09MPa·G or over.
· Cylinder with syphon
specifications
. (UNF1/2)
33
Cautions for refrigerant piping work
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
0.8
0.8
0.8
1.0
1.0
0.8
0.8
0.8
1.0
1.0
Nominal
dimensions(inch)
Diagram below: Piping diameter and thickness
Outside
diameter
(mm)
Thickness
(mm)
R410A R22
*
*
Use 1/2H or H pipes.
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
9.1
13.2
16.6
19.7
9.0
13.0
16.2
19.4
23.3
Nominal
dimensions(inch)
Flare cutting dimensions
Outside
diamer (mm)
Dimension A
( ) (mm)
+0
-0.4
R410A R22
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
17.0
22.0
26.0
29.0
17.0
22.0
24.0
27.0
36.0
Nominal
dimensions(inch)
Flare nut dimensions
Outside
diameter(mm)
Dimension B(mm)
R410A R22
Gauge manifold Charge hose Gas leak detector
Refrigerant recovery equipment Refrigerant cylinder Applied oil
Safety charger
Charge valve
Vacuum pump
Flare tool
Bender Pipe cutter Welder and nitrogen gas cylinder Refrigerant charging scale Vacuum gauge or thermis­tor vacuum gauge and vacuum valve Charging cylinder
Air purge, refrigerant charge and operation check Gas leak check Refrigerant recovery Refrigerant charge Apply to flared section
Prevent compressor malfunction when charging refrigerant by
spraying liquid refrigerant Prevent gas from blowing out
when detaching charge hose Vacuum drying and air purge
Flaring work of piping
Bend the pipes Cut the pipes Weld the pipes Refrigerant charge Check the degree of vacuum. (Vacuum valve prevents back flow of oil and refri­gerant to thermistor vacuum gauge) Refrigerant charge
Tool exclusive for R410A Tool exclusive for R410A Tool for HFC refrigerant Tool exclusive for R410A Tool exclusive for R410A Ester oil, ether oil and alkylbenzene oil (minimum amount) Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can be used if equipped with adap­ter for reverse flow check Tools for other refrigerants can be used by adjusting flaring dimension Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used
Tool exclusive for R410A
Tools and materials Use R410A tools Can R22 tools be used?
(Usable if equipped with adapter for rever­ se flow)
(Usable by adjusting flaring dimension)
Can R407C tools be used?
Ester oil, ether oil: Alkylbenzene oil: minimum amount
(Usable if equipped with adapter for rever­ se flow)
(Usable by adjusting flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) : Tools for other refrigerants can be used under certain conditions. : Tools for other refrigerants can be used.
OCH502C
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
1 Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness shown below. (Never use pipes of 0.7 mm or below.)
2 Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrig­erants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A has been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also has partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes. Use torque wrench corresponding to each dimension.
Dimension A
3 Tools for R410A (The following table shows whether conventional tools can be used or not.)
4
Dimension B
(1) Auxiliary heating operation controls another heat source that depends on the main system's operations,
which means the interlock operation shown in "b)" will be possible.
a)
b) Different Indoor unit applications that can be applied:
(2) Outdoor unit DIPSW5-4 for auxiliary heating control:
Set DIPSW5-4 when power is turned off at unit.
OFF:
Disable auxiliary Heating Function (Initial setting)
ON :
Enable auxiliary Heating Function
Indoor unit must be R410A UL model for this function to operate.
2-1. Auxiliary HEATING ON/OFF CONTROL SET-UP
(3) Determine required indoor fans speed during defrost mode:
0 20k 27k 39k 62K
None Black Blue White Red
Stopped
Setting on
remote
controller
Very Low Low High
Note: The setting will be disabled "when Heater contact signal is OFF".
CN22 input resistance ()
CN22 input (cable color)
Fan speed setting
OFF
Fan airflow rate setting
During defrost operation
ON
Wiring
CN22
a) With no auxiliary heating output the Indoor fan normally goes off to prevent cold drafts during the defrost cycles. b) With auxiliary heating control the auxiliary heat will be on during defrost mode, thus cold drafts will not be present. (Ducted units only) c) For models PEFY and PDFY (Ducted) recommended to use "Black" (20K) connector. d) For models PLFY, PCFY, PKFY and PFFY (Ductless) recommended "None", no connector required. e) To set the fan airflow rate to be used during defrost operation, insert the resistance that is packed within the optional adaptor cable kit (PAC-YU24HT-F) into the CN22 sensor input. You can choose at what speed the indoor fan operates during defrost cycles bases on chart below.
2
OCH502C
OVERVIEW OF UNITS
55
(4) Determine fan airflow setting during indoor thermo-OFF conditions:
A
OCH502C
a) These settings are done within Indoor DIPSW1-7 and DIPSW1-8, see chart below for options. b) Recommended SW1-7 OFF and SW1-8 ON will determine airflow based on "Setting on the remote controller".
Auxiliary heating
signal
Thermo condition
SW1-7 SW1-8
OFF OFF Very low
ON OFF Low
OFF ON
ON
ON
Fan speed
setting
OFF ON
Setting on
remote
controller
Stopped
Fan speed
setting
Setting on
remote
controller
(5) Setting outdoor unit and auxiliary heat switch over temperatures.
When the DIPSW 5-4 is set to "ON", the outdoor unit and the contact output operates as shown below.
a) Outdoor default setting and operations are shown below:
Stage 1
mb. decreasing - Outdoor unit HP operation
Amb. increasing - Defrost : Heater contact ON signal
- Other than defrost : Contact OFF
Stage 2
- Outdoor unit HP operation
- Heater contact ON signal
a
-12
-C
[10-F]
When the set temperature ranges overlap, the previously set pattern (1,2 or 3) has a priority. The stage 1 has the highest priority, 2 the second and then 3.
b) Based on above chart listed the sequence of operation on "On ambient decrease"
Stage 1 :(TH7 = > 10 Stage 2 :(TH7 = 10
Stage 3 :(TH7 = < -12
c) Based on above chart listed the sequence of operation on "On ambient increase"
Stage 3 :(TH7 = < 0 Stage 2 :(TH7 = > 0
Stage 1 :(TH7 = > 20
b
-C
0
[32-F]
c
-C
10
[50-F]
:
) : the outdoor unit runs in HP mode.
:
to -12:) : the outdoor unit runs in HP mode with auxiliary heating.
:
) : Auxiliary heating only (Outdoor unit is OFF).
:
) : Auxiliary heating only (Outdoor unit is OFF).
:
to 20:) : Auxiliary heating with outdoor unit in HP mode.
:
) : Outdoor unit in HP mode only.
d
-C
20
[68-F]
TH7 = Outdoor temperature
Stage 3
- Outdoor unit OFF (Standby)
- Heater contact ON signal
6
(6) Locally procured wiring
A basic connection method is shown.
(i.e. interlocked operation with the electric heater with the fan speed setting on high)
Recommended circuit
CN24
Remote control Board Relay circuit
Adapter
Indoor unit
control board
Outdoor unit
control board
Electric Heater
power source
Electric Heater
Red 1
White 2
Dip switch SW5-4 "ON"
Preparations in the field
Maximum cable length is 10 m (32ft)
Red 1
Red 2
YellowGreen
1-phase power supply
208V, 230V/60Hz
Control board
FS1, 2 ----- Thermal fuse
H1, H2 ----- Heater
26H --------- Overheat protection
thermostat
88H --------- Electromagnetic contactor
Wiring diagram
For relay X use the specifications given below operation coil
Rated voltage : 12VDC Power consumption : 0.9W or less
*Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU24HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm
2
to 1.25 mm2 (AWG22 to AWG16)
Do not extend the cable more than 10 meters (32ft).
OCH502C
X
X
+
R
S
R
S
CN24
88H
88H
FS1
FS2 FS1
FS2
88H
H1
H2
26H
CN22
7
2-2. UNIT CONSTRUCTION
Model
Ceiling
Ceiling
Ceiling Concealed mounted Wall Mounted
Concealed
4-way flow
1-way flow
built-in
Exposed
Concealed
(Fresh Air)*
PLFY-P PMFY-P PEFY-P PDFY-P PKFY-P PCFY-P PFFY-P PEFY-P PVFY-P
Capacity
NCMU-E NBMU-E NBMU-E NMAU-E NMHU-E NMSU-E NMU-E NBMU-E NHMU-E
NKMU-E
NKMU-E NEMU-E
NRMU-E E00A
NMHU-E-F
06 08
12 15
18 24 27 30 36 48 54 72
Ceiling Cassette
Ceiling
Vertical
concealed
Suspended
Floor Standing
OCH502C
Outdoor unit
Indoor unit that can be connected
Branching pipe components
Capacity
Number of units
Total system wide capacity
CMY-Y62-G-E CMY-Y64-G-E CMY-Y68-G-E
Branch header
(2 branches)
P60
Type 06 ~ Type 72
1~ 12 unit
50% ~130% of outdoor unit capacity
Branch header
(4 branches)
Branch header
(8 branches)
Decorative panel
Remote
controller
Name
Model number
Functions
• A handy remote controller for use in conjunction with the Melans centralized management system.
M-NET remote controller
• Addresses must be set.
*It is possible only by 1:1 system. (1 indoor unit of Fresh Air type is connected with 1 outdoor unit.) Operating temperature range (outdoor temperature) for fresh air type indoor units differ from other indoor units. Refer to 2-2(2).
PAR-F27MEA-US
MA remote controller
PAR-21MAAU-J, PAR-30MAAU-J
• Address setting is not necessary.
8
2-3. UNIT SPECIFICATIONS
P L F Y - P 30 N B M U - E PU M Y - P 60 N
K M U -BS
PAC ty pe
Frequency conversion controller
Refrigerant R410A/R22 commonness
Refrigerant R410A
NEW frequency converter one-to-many air conditioners (flexible design type)
Indicates equivalent to Cooling capacity
Indicates equivalent to Cooling capacity
Power supply N: Single phase 208/230V 60Hz
Power supply
N: Single phase 208/230V 60Hz
L : Ceiling cassette K : Wall-mounted type E : Hidden skylight type C : Ceiling suspended type M : Ceiling cassette type F : Floor standing type
Outdoor unit model type
Sub-number
Unit model type
UL model
M-NET control
M-NET control
UL model
Salt proof type
Frequency conversion controller
Outdoor unit
MULTI-S
Cooling
W.B. 15 - 24°C [59 - 75°F]
Heating
D.B. 15 - 27°C [59 - 81°F]
:%í&>í)@
Indoor-side intake air temperature Outdoor-side intake air temperature
'%í&>)@
OCH502C
(1) Method for identifying MULTI-S model
Indoor unit < When using Model 30 >
(2) Operating temperature range
Outdoor unit <When using model 60 >
Notes D.B. : Dry Bulb Temperature W.B. : Wet Bulb Temperature *10 - 46°C DB [50 - 115°FDB] : In the case of connecting PKFY-P06/P08 type indoor unit.
Ŷ In the case of connecting fresh air type indoor unit
Indoor-side and Outdoor-side intake air temperature
** Thermo-off (FAN-mode) automatically starts if the outdoor temp. is lower than 21:D.B.[70°FD.B.]. ***Thermo-off (FAN-mode) automatically starts if the outdoor temp. is higher than 20:D.B.[68°FD.B.].
(3) Guaranteed voltage
198 - 253V, 60Hz
Capacity of Fresh
air type indoor
P30
P54
Cooling
D.B.21 - 43:[70 - 109°F] ** W.B.15.5 - 35:[60 - 95°F]
D.B.21 - 43:[70 - 109°F] ** W.B.15.5 - 35:[60 - 95°F]
9
Heating
'%í - 20:[14 - 68°F] ***
'%í:[23 - 68°F] ***
3
OCH502C
SPECIFICATIONS
Item
Cooling Capacity Btu/h Heating Capacity Btu/h
***
Input (Cool Input Current (Cool Power factor (Cool) Input (Heat Input Current (Heat Power factor (Heat)
EER (Cool COP (Heat Connectable indoor units (Max.
Max. Connectable Capacity Btu/h 78,000(130%
Power Supply Single phase , 60Hz , 208/230V Breaker Size Max. fuse size Min.Circuit.Ampacity
Sound level (Cool/Heat
External finish Munsell 3Y 7.8/1.1 Refrigerant control Linear Expansion Valve Compressor Hermetic
Crankcase heater W
Heat exchanger Plate fin coil (Anti corrosion fin treatment
Fan Fan(drive
Dimensions (HoWoD
Weight kg [lb
Refrigerant R410A
Protection High pressure protection HP switch devices
Total Piping length (Max. Farthest m [ft] 80 [262] Max Height difference m [ft] 50 [164] * Chargeless length m [ft] 0 [0]
Guaranteed operation range
)
)
***
***
)
***
***
)
***
)
***
***
)
)
Model
Motor output kW 3.0 Capacity control
Starting method Inverter
) o
No. Propeller fan o 2 Fan motor output kW 0.16 + 0.16 Airflow m
)
Charge kg [lb Oil (Model
Compressor protection Fan motor protection Overheating/Voltage protection
Piping diameter
)
)
Liquid [mm[in] 9.52 [3/8
Gas [mm[in] 19.05 [3/4
Service Ref.
kW
A
%
kW
A
%
Btu/h/W
W/W
)
dB 58 / 59
%
3
/min [CFM] 140 [4,940]
W mm [in
D mm [in H mm [in
L [oz]
m [ft]
(
cool
(
heat
Rating conditions Cooling Indoor : D.B. 26.7°C / W.B. 19.4°C [D.B. 80°F / W.B. 67°F] Outdoor : D.B. 35°C [D.B. 95°F] Heating Indoor : D.B. 21.1°C [D.B. 70°F] Outdoor : D.B. 8.3°C / W.B. 6.1°C [D.B. 47°F / W.B. 43°F]
PUMY-P60NKMU(-BS)
60,000 66,000
4.80
21.5
97.0
6.15
27.6
97.0
12.5
3.14 12
)
40A 42A 25A
ANB66FFZMT
Cooling 38-100 Heating 29-100
)
] ] ]
]
]
)
)
í: DB [23 - 115
1,050 [41-5/16]
330+30 [13+1-3/16
1,338 [52+11/16
142 [313]
5.1 [11.2
2.3 [73] (FV50S
Compressor thermo, Over current detection
150 [492]
í::%>í
]
]
]
)
]
)
F DB]**
°
F WB]
°
*40m [140ft] : In the case of installing outdoor unit lower than indoor unit.
**
10 - 46°C [50 - 115°F]DB : In the case of connecting PKFY-P06/P08 type
indoor unit. ***Electrical data is for only outdoor unit. (In case of connecting 4 indoor units of PKFY-P06NBMU×2 and PKFY-
P24NKMU×2)
Btu/h=kW × 3,412 CFM=K/min × 35.31 lbs=kg/ 0.4536 Note: Above specification data is subject to rounding variation.
10
4
OCH502C
DATA
4-1. COOLING AND HEATING CAPACITY AND CHARACTERISTICS
4-1-1. Method for obtaining system cooling and heating capacity:
To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings of all the indoor units connected to the outdoor unit (see table below), and then use this total to find the standard capacity with the help of the tables on 4-2. STANDARD CAPACITY DIAGRAM.
(1) Capacity of indoor unit
Model number for
indoor unit
Model Capacity 6 8 12 15 18 24 27 30 36 48 54 72
(2) Sample calculation
1 System assembled from indoor and outdoor unit (in this example the total capacity of the indoor units is greater than that of
the outdoor unit)
• Outdoor unit PUMY-P60NKMU
• Indoor unit PKFY-P08NAMU-E o 2 , PLFY-P18NBMU-E o 3
2 According to the conditions in 1, the total capacity of the indoor unit will be: 8 o 2 + 18 o 3 = 70 3 The following figures are obtained from the 52 total capacity row of the standard capacity table (4-2.):
Capacity (Btu/h)
Cooling Heating Cooling Heating Cooling Heating
62,000
A
Model 06 Model 08 Model 12 Model 15 Model 18 Model 24 Model 27 Model 30 Model 36 Model 48 Model 54 Model 72
68,000
B
Outdoor unit power consumption (kW)
4.62 5.91 20.3 26.0
Outdoor unit current (A)/230V
4-1-2. Method for obtaining the heating and cooling capacity of an indoor unit:
(1) The capacity of each indoor unit (Btu/h) = the capacity A (or B) o
(2) Sample calculation (using the system described above in 4-1-1. (2) ):
During cooling: During heating:
• The total model capacity of the indoor unit is: 8000 o 2 + 18000 o 3 = 70000Btu/h Therefore, the capacity of PKFY-P08NAMU-E and PLFY-P18NBMU-E will be calculated as follows by using the formula in 4-1-2. (1):
Model 08= 62,000 o = 7,090 Btu/h
Model 18= 62,000 o = 15,940 Btu/h
8000
70000
18000 70000
• The total model capacity of indoor unit is: 9000 o 2 + 20000 o 3 = 78000 Btu/h Therefore, the capacity of PKFY-P08NAMU-E and PLFY-P18NBMU-E will be calculated as follows by using the formula in 4-1-2. (1):
Model 08= 68,000 o = 7,850 Btu/h
Model 18= 68,000 o = 17,440 Btu/h
total model capacity of all indoor units
model capacity
9000 78000 20000 78000
11
4-2. STANDARD OPERATION DATA (REFERENCE DATA)
OCH502C
Operation
Ambient temperature
Indoor unit
Operating conditions
Piping
Fan speed Hi Amount of refrigerant kg [lbs-oz] 8.5 [18] Electric current A 21.4 27.4
Outdoor unit
LEV opening Indoor unit Pulse 171 (P06)/426 (P24) 215 (P06)/534 (P24) Pressure High pressure/Low pressure MPa [psi] 2.83/0.94 [411/136] 2.93/0.66 [425/95]
Temp. of each section
Voltage V 230 Compressor frequency Hz 45 56
Outdoor unit
Indoor unit
Indoor Outdoor 35°C/— [95°F/—] 8.3°C/6.1°C [47°F/43°F] No. of connected units No. of units in operation 4 Model 06×2/24×2 Main pipe Branch pipe 2.5 [8-1/4] Total pipe length 15 [49-1/4]
Discharge Heat exchanger outlet 38 [100] 3 [37] Accumulator inlet 13 [55] 0 [32] Compressor inlet 14 [57] 1 [30] Compressor shell bottom 74 [165] 68 [154] LEV inlet 27 [81] 40 [104] Heat exchanger inlet 10 [50] 61 [142]
DB/WB
Unit
m [ft]
°C [°F]
26.7°C/19.4°C [80°F/67°F] 21.1°C/— [70°F/—]
74 [165] 68 [154]
Outdoor unit model
PUMY-P60NKMU(-BS)
4
5 [16-3/8]
12
4-3. STANDARD CAPACITY DIAGRAM
OCH502C
PUMY-P60NKMU PUMY-P60NKMU-BS
Total capacity of indoor units
Capacity
(Btu/h)
Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating 6 6000 7000 0.71 1.06 8.45 1.94 3.1 4.6 3.4 5.1 7 7000 8100 0.82 1.15 8.56 2.06 3.6 5.1 4.0 5.6 8 8000 9200 0.92 1.24 8.67 2.18 4.0 5.4 4.5 6.0 9 9000 10300 1.03 1.32 8.77 2.28 4.5 5.8 5.0 6.4
10 10000 11400 1.13 1.40 8.86 2.38 5.0 6.2 5.5 6.8 11 11000 12500 1.23 1.48 8.95 2.47 5.4 6.5 6.0 7.2 12 12000 13600 1.33 1.56 9.04 2.56 5.8 6.8 6.5 7.6 13 13000 14700 1.43 1.63 9.12 2.64 6.3 7.2 6.9 7.9 14 14000 15800 1.52 1.71 9.20 2.71 6.7 7.5 7.4 8.3 15 15000 16900 1.62 1.78 9.27 2.77 7.1 7.8 7.9 8.7 16 16000 18000 1.71 1.86 9.34 2.83 7.5 8.2 8.3 9.0 17 17000 19100 1.81 1.94 9.40 2.89 7.9 8.5 8.8 9.4 18 18000 20200 1.90 2.02 9.46 2.94 8.3 8.9 9.2 9.8 19 19000 21300 2.00 2.09 9.52 2.98 8.8 9.2 9.7 10.2 20 20000 22400 2.09 2.18 9.58 3.02 9.2 9.6 10.1 10.6 21 21000 23500 2.18 2.26 9.63 3.05 9.6 9.9 10.6 11.0 22 22000 24600 2.27 2.34 9.68 3.08 10.0 10.3 11.0 11.4 23 23000 25700 2.36 2.43 9.73 3.10 10.4 10.7 11.5 11.8 24 24000 26800 2.45 2.51 9.78 3.12 10.8 11.0 11.9 12.2 25 25000 27900 2.54 2.60 9.82 3.14 11.2 11.4 12.3 12.6 26 26000 29000 2.63 2.70 9.87 3.15 11.6 11.8 12.8 13.1 27 27000 30100 2.72 2.79 9.92 3.16 11.9 12.3 13.2 13.5 28 28000 31200 2.81 2.88 9.96 3.17 12.3 12.7 13.6 14.0 29 29000 32300 2.90 2.98 10.01 3.17 12.7 13.1 14.1 14.5 30 30000 33400 2.98 3.08 10.05 3.18 13.1 13.5 14.5 15.0 31 31000 34500 3.07 3.18 10.10 3.18 13.5 14.0 14.9 15.5 32 32000 35600 3.15 3.29 10.14 3.17 13.8 14.4 15.3 16.0 33 33000 36700 3.24 3.39 10.19 3.17 14.2 14.9 15.7 16.5 34 34000 37800 3.32 3.50 10.24 3.16 14.6 15.4 16.1 17.0 35 35000 38900 3.40 3.61 10.29 3.16 14.9 15.9 16.5 17.5 36 36000 40000 3.48 3.72 10.35 3.15 15.3 16.4 16.9 18.1 37 37000 41100 3.56 3.84 10.40 3.14 15.6 16.9 17.3 18.6 38 38000 42200 3.63 3.95 10.46 3.13 15.9 17.4 17.6 19.2 39 39000 43200 3.71 4.06 10.52 3.12 16.3 17.8 18.0 19.7 40 40000 44300 3.78 4.17 10.59 3.11 16.6 18.3 18.4 20.3 41 41000 45400 3.85 4.29 10.65 3.10 16.9 18.8 18.7 20.8 42 42000 46500 3.92 4.41 10.73 3.09 17.2 19.4 19.0 21.4 43 43000 47600 3.98 4.52 10.80 3.08 17.5 19.9 19.3 22.0 44 44000 48700 4.04 4.64 10.88 3.08 17.7 20.4 19.6 22.5 45 45000 49800 4.10 4.75 10.97 3.07 18.0 20.9 19.9 23.1 46 46000 50900 4.16 4.86 11.06 3.07 18.3 21.4 20.2 23.6 47 47000 52000 4.21 4.98 11.15 3.06 18.5 21.8 20.4 24.2 48 48000 53100 4.26 5.08 11.25 3.06 18.7 22.3 20.7 24.7 49 49000 54200 4.31 5.18 11.36 3.06 18.9 22.8 20.9 25.2 50 50000 55300 4.36 5.28 11.48 3.07 19.1 23.2 21.2 25.7 51 51000 56400 4.40 5.38 11.59 3.07 19.3 23.6 21.4 26.1 52 52000 57500 4.44 5.46 11.72 3.08 19.5 24.0 21.6 26.5 53 53000 58600 4.47 5.55 11.86 3.10 19.6 24.4 21.7 26.9 54 54000 59700 4.50 5.62 12.00 3.11 19.8 24.7 21.9 27.3 55 55000 60800 4.53 5.69 12.14 3.13 19.9 25.0 22.0 27.6 56 56000 61900 4.55 5.75 12.30 3.15 20.0 25.2 22.1 27.9 57 57000 63000 4.57 5.80 12.47 3.18 20.1 25.5 22.2 28.2 58 58000 64100 4.59 5.84 12.64 3.21 20.2 25.7 22.3 28.4 59 59000 65200 4.60 5.87 12.82 3.25 20.2 25.8 22.3 28.5 60 60000 66000 4.60 5.95 13.04 3.25 20.2 26.1 22.3 28.9 61 60200 66200 4.61 5.90 13.05 3.29 20.2 25.9 22.4 28.6 62 60400 66400 4.61 5.90 13.09 3.30 20.2 25.9 22.4 28.6 63 60600 66600 4.61 5.90 13.13 3.31 20.2 25.9 22.4 28.7 64 60800 66800 4.62 5.90 13.17 3.31 20.3 25.9 22.4 28.7 65 61000 67000 4.62 5.91 13.21 3.32 20.3 25.9 22.4 28.7 66 61200 67200 4.62 5.91 13.26 3.33 20.3 26.0 22.4 28.7 67 61400 67400 4.62 5.91 13.30 3.34 20.3 26.0 22.4 28.7 68 61600 67600 4.62 5.91 13.34 3.35 20.3 26.0 22.4 28.7 69 61800 67800 4.62 5.91 13.38 3.36 20.3 26.0 22.4 28.7 70 62000 68000 4.62 5.91 13.42 3.37 20.3 26.0 22.4 28.7 71 62200 68200 4.62 5.91 13.47 3.38 20.3 26.0 22.4 28.7 72 62400 68400 4.62 5.91 13.51 3.39 20.3 26.0 22.4 28.7 73 62600 68600 4.62 5.91 13.56 3.40 20.3 26.0 22.4 28.7 74 62800 68800 4.62 5.91 13.60 3.41 20.3 26.0 22.4 28.7 75 63000 69000 4.62 5.91 13.64 3.42 20.3 26.0 22.4 28.7 76 63200 69200 4.62 5.91 13.69 3.43 20.3 26.0 22.4 28.7 77 63400 69400 4.62 5.91 13.74 3.44 20.3 26.0 22.4 28.7 78 63600 69600 4.61 5.91 13.78 3.45 20.2 25.9 22.4 28.7
Power consumption
(kW)
EER / COP
Current (A) / 230V Current (A) / 208V
13
4-4. CORRECTING COOLING AND HEATING CAPACITY
OCH502C
4-4-1. Correcting changes in air conditions
(1) The performance curve charts (Figure 1, 2) show the ratio by the temperature condition change when the rated capacity (total
capacity) and the rated input are presumed 1, under standard length (7.6 m [25 ft]) and standard temperature condition.
• Standard conditions:
Rated cooling capacity
Rated heating capacity
• Use the rated capacity and rated input given in “4-2.”.
• The input is the single value on the side of the outdoor unit; the input on the sides of each indoor unit must be added to obtain the total input.
(2) The capacity of each indoor unit may be obtained by multiplying the total capacity obtained in (1) by the ratio between the
individual capacity at the rated time and the total capacity at the rated time.
Indoor D.B. 26.7°C / W.B. 19.4°C [D.B.80°F / W.B.67°F] Outdoor D.B. 35°C [D.B.95°F]
Indoor D.B. 21.1°C [D.B.70°F] Outdoor D.B. 8.3°C / W.B. 6.1°C [D.B.47°F / W.B.43°F]
Individual capacity under stated conditions = total capacity under the stated conditions o
(3) Capacity correction coefficient curve
Figure 1 Cooling performance curve
1.4
1.3
1.2
1.1
1.0
0.9
Ratio of cooling capacity
0.8
0.7
0.6
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
Ratio of power input
-10 0 10 20 30 40 50
14 32 50 68 86 104 122
OUTDOOR
:WB (°FWB)
24 (75.2)
22 (71.6)
20 (68)
18 (64.4)
16 (60.8)
INDOOR
:WB(°FWB)
24 (75.2) 22 (71.6) 20 (68) 18 (64.4) 16 (60.8)
INDOOR
[°CDB]
[°FDB]
Figure 2 Heating performance curve
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
Ratio of heating capacity
Ratio of power input
-25 -20 -15 -10 -5 0 1510520
-13 -4 5 14 23 32 595041 68
individual capacity at the rated time
total capacity at the rated time
:DB (°FDB)
15 (59)
21.1 (70)
25 (77)
27.2 (81)
INDOOR
:DB(°FDB)
15 (59)
21.1 (70)
25 (77)
27.2 (81)
INDOOR
[°CWB]
[°FWB]
OUTDOOR
14
Figure 3 High heating performance curve
OCH502C
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
Ratio of heating capacity
:DB (°FDB)
15 (59)
21.1 (70)
25 (77)
27.2 (81)
INDOOR
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
-25 -20 -15 -10 -5 0 1510520
-13 -4 5 14 23 32 595041 68
OUTDOOR
:DB (°FDB)
15 (59)
21.1 (70)
25 (77)
27.2 (81)
INDOOR
[°CWB]
[°FWB]
4-4-2. Correcting capacity for changes in the length of refrigerant piping
(1) During cooling, obtain the ratio (and the equivalent piping length) of the outdoor units rated capacity and the total in-use
indoor capacity, and find the capacity ratio corresponding to the standard piping length from Figure 3. Then multiply by the cooling capacity from Figure 1 to obtain the actual capacity.
(2) During heating, find the equivalent piping length, and find the capacity ratio corresponding to standard piping length from
Figure 3. Then multiply by the heating capacity from Figure 2 to obtain the actual capacity.
Figure 3 Capacity correction curve
105
Ratio of power input
100
95
90
85
Capacity ratio [%]
80
75
0 10203040506070 80 [m] 0 33 66 98 131 164 197 230 263 [ft]
Corrected pipe length
• Method for obtaining the equivalent piping length
Equivalent length for type P60 = (length of piping to farthest indoor unit) + (0.3 o number of bends in the piping) (m) Length of piping to farthest indoor unit: 80 m [262 ft]
Heating
Cooling
15
4-4-3. Correction of heating capacity for frost and defrosting
1.5m
[4.9 ft]
1m [3.3 ft]
MICROPHONE
UNIT
GROUND
OCH502C
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature (W.B.°F)
Outdoor Intake temperature (W.B.°C)
Correction factor
43 39 36 32 28 25 21 18 14
6420-2-4-6-8-10
1.0 0.98 0.89 0.88 0.89 0.9 0.95 0.95 0.95
4-5. NOISE CRITERION CURVES
SPL(dB)
PUMY-P60NKMU PUMY-P60NKMU-BS
90
80
MODE COOLING HEATING
LINE 58 59
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
16
5
OCH502C
OUTLINES AND DIMENSIONS
PUMY-P60NKMU PUMY-P60NKMU-BS
2-U Shaped notched holes
(Foundation Bolt M10<W3/8>)
225
<8-27/32>
Rear Air Intake
600<23-5/8>
Installation Feet
225
<8-27/32>
4 PIPING-WIRING DIRECTIONS
Piping and wiring connections
can be made from 4 directions:
FRONT, Right, Rear and Below.
Side Air Intake
56<2-7/32>
40<1-9/16>
417<16-13/32>
330<13>
0
53<2-3/32>
42
70
<1-21/32>
61<2-13/32>
<2-3/4>
25<31/32>
28<1-3/32> 19<3/4>370<14-9/16>
Terminal connection
Left࡮࡮࡮For the power supply
2-12×36 Oval holes
(Foundation Bolt M10<W3/8>)
Air Discharge
Ground for the power supply
("GR"marking position)
1050<41-11/32>
362<14-1/4>
Handle for moving
Side Air IntakeRear Air Intake
Center࡮࡮࡮For the transmission line
Right࡮࡮For concentration control
Ground for the transmission line
Ground for concentration control
( )
Service panel
Handle for moving
632<24-7/8>
Handle for
moving
1338<52-11/16>
Air intake
1079<42-15/32>
Unit : mm <inch>
Rear piping cover
Front piping cover
+
1ޓ450<17-23/32>
+
1ޓ393<15-15/32>
2
1
26<1-1/32>
369<14-17/32>
86<3-3/8>
81<3-3/16>
<6-1/16>
154
22.5<7/8>
3/4 Conduit
attachment
When installing the conduit.
Set the attachment to the
inner side of each panel.
60<2-3/8>
27.8<1-3/32>
22.2<7/8>
:
:
92
:
37<1-15/32>Knockout)
24<15/16>Knockout)
:
:
Conduit hole
(
Conduit hole
(
60<2-3/8>
Bottom piping hole
(Knockout)
<5-11/32>
136
24.7<31/32>
5<3/16>
100
Scale 1:5
<3-15/16>
1/2 Conduit
attachment
Rear piping hole
(Knockout)
<3-5/8>
33<1-5/16>)
:
Drain hole
5-
160
<6-5/16>
160
<6-5/16>
160
<6-5/16>
110<4-11/32>
45<1-25/32>
92<3-5/8>
75<2-15/16>
<Foundation bolt height>
3 FOUNDATION BOLTS
Please secure the unit firmly
with 4 foundation (M10<W3/8>) bolts.
(Bolts and washers must be
purchased locally.)
<5-29/32>
150
Min.
2 SERVICE SPACE
Dimensions of space needed
for service access are
shown in the below diagram.
Min. 10mm<3/8>Min. 10mm<3/8>
FREE
1 FREE SPACE (Around the unit)
The diagram below shows a basic example.
Explantion of particular details are
given in the installation manuals etc.
FOUNDATION
30<1-3/16>
Max.
<19-11/16>
500
Min.
Min.
10<3/8>
Min.
500
<19-11/16>
Service space
Min. 1000mm<39-3/8> Min. 150mm<5-29/32>
1717
Handle for
moving
Example of Notes
2
1
ޓޓ࡮࡮࡮Refrigerant GAS pipe connection (FLARE):19.053/4F)
ޓޓ࡮࡮࡮Refrigerant LIQUID pipe connection (FLARE): 9.523/8F
+㧝࡮࡮࡮Indication of STOP VALVE connection location.
55<2-3/16>27<1-1/16>
55<2-3/16>
53<2-3/32> 60<2-3/8>
55<2-3/16>
60<2-3/8>
Piping Knockout Hole Details
5<3/16>
60<2-3/8>
Rear trunking hole
(Knockout)
5<3/16>
24<15/16>Knockout)
37<1-15/32>Knockout)
:
:
Conduit hole
(
Conduit hole
(
Right piping hole
(Knockout)
:24<15/16>Knockout)
Conduit hole
(
5
37<1-15/32>Knockout)
60
:
Conduit hole
(
Front trunking hole
(Knockout)
<3/16>
<2-3/8>
92
:
73<2-7/8>
73<2-7/8>
92
:
92
27<1-1/16>
<3-5/8>
<3-5/8>
<3-5/8>
26<1-1/32>
73<2-7/8> 60<2-3/8>
Right trunking hole
(Knockout)
29<1-5/32>
55<2-3/16>
92<3-5/8>
26<1-1/32>
27<1-1/16> 55<2-3/16>
75<2-15/16>
92<3-5/8>
Front piping hole
(Knockout)
26<1-1/32>
6
OCH502C
WIRING DIAGRAM
PUMY-P60NKMU PUMY-P60NKMU-BS
MULTI.B.
17
MF1
MS
~
3
MF2
17
MS
~
3
52C
(
BLK
31313
TB3
2
RED
M1
M2
RED
S
TO INDOOR UNIT CONNECTING WIRES DC 30V(Non-polar)
TB7
2
YLW
M1
M2
YLW
S
FOR CENTRALIZED CONTROL DC 30V(Non-polar)
POWER SUPPLY
~
/N
AC208/230V 60Hz
X505
CN4
(WHT)
12
2
2
CN3N (BLU)
1
CNS1 (RED)
13
BLK
LEV-A LEV-B
MM
6
6
1
CNLVB
CNLVA
(RED)
(WHT)
2
22
3
5
1
CN51 (WHT)
CNS2
CN41
(YLW)
(WHT)
1214 1441
CN52C
(RED)
3117
52C
52C
E4
E I
N I L I
BLK
* MODEL SELECT 1:ON 0:OFF
PUMY-P60NKMU(-BS)
The black square ( ) indicates a switch position.
SWU2 SWU1
CN40
(WHT)
M-P.B.
MODEL
SW5
SW4
*
LED1
CN102
(WHT)
41
CN2
(WHT)
CN1
(WHT)
P. B .
BLK
E3
(RED)
CNAC2
1
3
BLK
E2
1
3
(WHT)
CNAC1
1234561 011000020
SW6
SW2?SW8SW1
SW7SW3
LED2
41 TP1
(BLK)
135
2
2
2
SW4 SW8
63HS63LS
TH7 TH6 TH3 TH4 TH2
t° t° t° t° t°
CNF1 (WHT)
CNF2 (WHT)
3
1
2
CNDC (PNK)
X504
21S4
)
(
GRN
)
(
1
21S4
WHT
CB
RED
TB1
RED
L1
BLU
L2
GRN/YLW
GR
141
3121212
63HS
TH7/6
TH3
(
SV1
WHT
SV1
12
(WHT)
WHT
CN4
U
X502
)
2
RED
WHT
(RED)
63H (YLW) 1
3
71
X501
SS
(
WHT
)
131
7
TH8
SV2 BLU
X503
)
W
(WHT)
13
63LS
(BLU)
TRANS
(
2
WVU
BLK
V
MS
3~
MC
63H
CN3D
CN3S
(WHT) TH2 BLK
)
12
CNAC (RED
2
N2
WHT
DCL
(RED)
131313
CN52C
(RED)
13
3
LED3
)
CNDC (PNK)
IGBT
WHT
TH4
)
(
WHT
)
(
CN2
(WHT)
7
F1
F2
CN2
(WHT)
P2
DCL2 DCL1
SYMBOL NAME SYMBOL NAME SYMBOL NAME
TB1 Terminal Block <Power Supply TB3 Terminal Block <Comunication Line TB7 Terminal Block < MC Motor For Compressor MF1,MF2 Fan Motor 21S4 Solenoid Valve <Four-Way Valve 63H High Pressure Switch
High Pressure Sensor
63HS 63LS Low Pressure Sensor SV1 Solenoid Valve <Bypass Valve TH2
Thermistor <HIC Pipe
TH3
Thermistor <Outdoor Pipe TH4 Thermistor <Compressor TH6 Thermistor <Low Pressure Saturated TH7
Thermistor <Outdoor
Thermistor <Heat Sink
TH8
Electronic Expansion Valve
LEV-A,LEV-B
Cautions when servicing
!
• WARNING: When the main supply is turned off, the voltage [340 V] in the main capacitor will drop to 20 V in approx. 2 minutes (input voltage: 230 V). When servicing, make sure that LED1, LED2 on the outdoor circuit board goes out, and then wait for at least 1 minute.
• Components other than the outdoor board may be faulty: Check and take corrective action, referring to the service manual.
Do not replace the outdoor board without checking.
NOTES:
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit. Self-diagnosis function The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch (SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit. LED indication : Set all contacts of SW1 to OFF.
• During normal operation
• The LED indicates the drive state of the controller in the outdoor unit.
Bit
Compressor
Indication
operated
• When fault requiring inspection has occurred The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.
>
Centralized Control Line
>
>
>
>
>
>
>
1
2
52C321S44SV15(SV2)
Reactor
DCL
>
CB Main Smoothing Capacitor
>
P.B. Power Circuit Board
Connection Terminal <U/V/W-Phase
TABU/V/W TABLI/NI
Connection Terminal <L/N-Phase Connection Terminal <DC Voltage
TABP2
Connection Terminal <DC Voltage
TABN2
Connection Terminal <Reactor
DCL1,DCL2
Power Module
IGBT
Connection Terminal <Ground
EI,E2,E3,E4
MULTI.B.
Controller Circuit Board
SW1
Switch <Display Selection
SW2
Switch <Function Selection SW3 SW4 SW5 SW6
Switch <Test Run
Switch <Model Selection
Switch <Function Selection
Switch <Function Selection
>
18
SW7 SW8 SWU1
>
SWU2 SS
>
>
CN3D
>
CN3S
>
CN3N CN51
>
LED1,LED2
>
>
>
>
> >
LED3 F1,F2 X501
M-P.B.
TP1
~
505
678
Always lit
Switch <Function Selection Switch <Model Selection Switch <Unit Address Selection, 1st digit Switch <Unit Address Selection, 2nd digit> Connector <Connection For Option Connector <Connection For Option Connector <Connection For Option Connector <Connection For Option Connector <Connection For Option LED <Operation Inspection Display LED <Power Supply to Main Microcomputer> Fuse <T6. 3AL250V Relay M-NET Power Circuit Board ConnectionTerminal <Ground>
[Example] When the compressor and SV1 are turned during cooling operation.
12345678
>
>
>
> > > > >
>
>
7
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
051
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
056
001
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
010
101
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
002
102 104 154
1111
11
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
009
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
008
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
003
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
007
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
006
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
004
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
005
A transmission wire must be
connected to each refrigerant
system (outdoor and indoor).
Set addresses:
Outdoor unit ..............051-100
Indoor unit .................001-050
Remote controller .....101-200
PUMY has no 100ths digit switch.
The address automatically become
"100" if it is set as "01~50".
Remote
controller
Remote
controller
Remote
controller
Remote
controller
105
Remote
controller
157
Remote
controller
107
Remote
controller
For centralized
management
For remote
controller
Address SW Address SW Address SW Address SW Address SW
Piping
Outdoor unit
Outdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unitIndoor unitIndoor unitIndoor unitIndoor unit
Address SW Address SW Address SW Address SW Address SW
Address SWAddress SWAddress SWAddress SWAddress SW
Address SWAddress SW
For centralized
management
For remote
controller
Transmission wire
OCH502C
NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION
7-1. TRANSMISSION SYSTEM SETUP
19
7-2. REFRIGERANT SYSTEM DIAGRAM
Refrigerant Gas pipe <3/4>
Refrigerant
Liquid pipe
<3/8>
Accumulator
Thermistor (TH6) (Saturation temperature of suction pressure)
Solenoid valve (SV1)
Check valve (High pressure)
Check valve (Low pressure)
High pressure sensor (63HS)
High pressure switch (63H)
Low pressure sensor (63LS)
Thermistor (TH7) (Outdoor temperature)
(Pipe temperature)
Thermistor (TH4)
Thermistor (TH3)
Oil separator
Service port
Service port
4-way valve
Strainer
Strainer
Capillary tube
Strainer
Strainer
Ball valve
Stop valve
Distributor
Strainer Strainer
Compressor
Strainer
Refrigerant piping specifications <dimensions of flared connector>
Capillary tube for oil separator : :2.5 % :0.8 % L800 Capillary tube for solenoid valve : :4.0 % :3.0 % L500
Capacity
Item
Liquid piping
Gas piping
P06, P08, P12, P15, P18
P24, P30, P36, P48, P54
P60
Indoor unit
Outdoor unit
:6.35 <1/4>
:9.52 <3/8>
:9.52 <3/8>
:12.7 <1/2>
:15.88 <5/8>
:19.05 <3/4>
P72 :9.52 <3/8> :19.05 <3/4>
Thermistor (TH2) (HIC)
(
Compressor
)
HIC
LEV-B
LEV-A
OCH502C
PUMY-P60NKMU PUMY-P60NKMU-BS
Unit: mm <inch>
20
7-3. SYSTEM CONTROL
TB5
TB15
01
101
RC
(Main)
151
IC
TB3
TB7
51
OC
TB5
TB15
02
IC
RC
(Sub)
102
RC
(Main)
152
RC
(Sub)
12
M1M2
S
M1M2
S
M1M2
S
12
M1M2
S
AB AB AB AB
TB5
12
TB15
01
101
IC
AB
M1 M2
TB3
S
TB7
51
OC
L
1
L3
L2
TB5
TB15
02
IC
102
RC
l1
l2
M1 M2
S
M1 M2
S
12
M1 M2
S
AB
OCH502C
Example for the System
• Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed in the standard system with detailed explanation. The explanation for the system in this section : Use 1 single outdoor unit and multiple outdoor units for M-NET remote control
system. Use 1 single outdoor unit and multiple indoor units in the multiple outdoor units for the M-NET remote control system.
A. Example of a M-NET remote controller system (address setting is necessary.)
Example of wiring control cables Wiring Method and Address Setting
1. Standard operation
• 1 remote controller for each
indoor unit.
• There is no need for setting
the 100 position on the remote controller.
2. Operation using 2 remote controllers
• Using 2 remote controllers for each indoor unit.
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use non­polarized 2 wire.
b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) for each indoor unit with the terminal block (TB6) for the remote controller (RC).
c. Set the address setting switch (on outdoor unit P.C.B)
as shown below.
Unit
Indoor unit (IC)
Outdoor unit
(OC)
Remote
controller (RC)
Range
001 to 050
051 to 100
101 to 150
Setting Method
— Use the smallest address of all the indoor unit plus 50. Indoor unit address plus
100.
a. Same as above. b. Same as above. c. Set address switch (on outdoor unit P.C.B) as
shown below.
Unit
Indoor Unit (IC)
Outdoor unit
(OC)
Main Remote
Controller (RC)
Sub Remote
Controller (RC)
Range
001 to 050
051 to 100
101 to 150
151 to 200
Setting Method
— Use the smallest address of all the indoor units plus 50. Indoor unit address plus
100. Indoor unit address plus
150.
3. Group operation
OC
51
101
TB5
M1 M2
AB
RC
TB3
TB7
M1 M2
S
M1 M2
S
• Multiple indoor units operated
Combinations of 1 through 3 above are possible.
together by 1 remote controller
IC(Main)
01
S
TB15
12
TB5
M1 M2
IC(Sub)
02
S
21
TB15
12
a. Same as above. b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) of the IC main unit with the most recent address within the same indoor unit (IC) group to terminal block (TB6) on the remote controller.
c. Set the address setting switch (on outdoor unit P.C.B)
as shown below.
Unit
IC (Main)
IC (Sub)
Outdoor Unit
Main Remote
Controller
Sub Remote
Controller
Range
001 to 050
001 to 050
051 to 100
101 to 150
151 to 200
Use the smallest address within the same group of indoor units. Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be in sequence with the IC (Main). Use the smallest address of all the indoor units plus 50. Set at an IC (Main) address within the same group plus 100.
Set at an IC (Main) address within the same group plus 150.
Setting Method
d. Use the indoor unit (IC) within the group with the
most functions as the IC (Main) unit.
• Name, Symbol and the Maximum Remote controller Units for Connection
OCH502C
Name Symbol Maximum units for connection
Outdoor unit OC
Indoor unit IC 1 OC unit can be connected to 1-12 IC units
M-NET remote
controller
RC
Maximum 2 RC for 1 indoor unit, Maximum 12 RC for 1 OC
Permissible Lengths Prohibited items
Longest transmission cable length (1.25 mm² [AWG16]) L1 + L2, L2 + L3, L3 + L1 [ 200m [656ft] Remote controller cable length
1.
If 0.5 to 1.25 mm² [AWG20 to AWG16]
R1, R2 [10m [33ft]
2. If the length exceeds 10 meters [33ft], the exceeding section should be 1.25 mm² [AWG16] and that section should be a value within the total extension length of the transmission cable and maximum transmission cable length. (L
3)
Same as above
M-NET remote controller (RC) and MA remote controller (MA) cannot be used together.
• Do not connect anything with TB15 of indoor unit (IC).
TB3
M1 M2
TB3
M1M2
S
OC
51
S
OC
51
M1 M2
TB7
M1M2
TB7
S
S
TB5
M1M2
TB5
M1 M2
AB
101
RC
IC
01
TB15
12
S
IC
01
TB15
12
S
TB5
M1M2
TB5
M1 M2
S
02
IC
02
TB15
12
S
AB
TB15
MA
IC
• Use the indoor unit (IC)
TB15
12
address plus 150 as the sub remote controller address. In this case, it should be 152.
• 3 or more remote con-
AB
101
RC
(Main)
AB AB ABAB
151
RC
(Sub)
102
RC
(Main)
103
(Sub)
RC
104
RC
troller (RC) cannot be connected to 1 indoor unit.
Same as above
TB3
M1 M2
S
OC
51
TB7
M1 M2
IC(Main)
01
TB5
TB15
12
M1 M2
S
S
TB5
M1 M2
IC(Sub)
02
S
TB15
12
• The remote controller address is the indoor unit main address plus
AB
102
RC
100. In this case, it should be 101.
22
B. Example of a group operation system with 2 or more outdoor units and a M-NET remote controller.
TB7
TB3
IC
(51)
TB5
RC
(01)
IC
TB5
(03)
IC
TB5
(02)
IC
TB5
(04)
IC
TB5
(05)
IC
TB5
(07)
IC
TB5
(06)
L2
L1
(101)
RC
(105)
RC
(104)
RC
(155)
OC
TB7
(53)
OC
3
Power Supply
Unit
System controller
L3
L6
L7
L4
L5
2
4
1
: Group: Group: Group: Shielded Wire: Sub Remote Controller
N
N
N
N
M1M2
S
M1M2
S
M1 M2
S
M1 M2
S
ABABAB
M1 M2
S
M1 M2
S
M1 M2
S
S
M1M2
S
TB3
M1M2
S
M1M2
S
AB
M1M2
M1 M2
S
M1 M2
S
OCH502C
(Address settings are necessary.)
Examples of Transmission Cable WiringWiring Method Address Settings
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit
(OC). e. DO NOT change the jumper connector CN41 on MULTI controller board. f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary. Connect the termi-
nal S on the power supply unit with the earth. g. Set the address setting switch as follows.
Unit Range Setting Method
IC (Main) 01 to 00
IC (Sub) 01 to 50
Outdoor Unit 51 to 100
Main Remote Controller 101 to 150
Sub Remote Controller 151 to 200
MA Remote Controller
h. The group setting operations among the multiple indoor units are done by the remote controller (RC) after the electri-
cal power has been turned on.
Use the smallest address within the same group of indoor units. Use an address, other than the IC (Main) in the same group of indoor units. This must be in sequence with the IC (Main). Use the smallest address of all the indoor units plus 50.
*The address automatically becomes “100” if it is set as “01 - 50”. Set at an IC (Main) address within the same group plus 100.
Set at an IC (Main) address within the same group plus 150.
Unnecessary address setting (Necessary main/ sub setting)
23
• Name, Symbol, and the Maximum Units for Connection
OCH502C
• Longest length via outdoor units : L1+L2+L3+L4, L1+L2+L3+L5, L1+L2+L6+L7 [ 500 meters [1450 ft] (1.25 mm² [AWG16])
• Longest transmission cable length : L
• Remote controller cable length : R
1, L3+L4, L3+L5, L6, L2+L6, L7 [ 200 meters [656 ft] (1.25 mm² [AWG16])
1,R2, R2+R3, R4 [ 10 meters [33 ft] (0.5 to 1.25 mm² [AWG20 to AWG16])
If the length exceeds 10 meters [33 ft], use a 1.25 mm² [AWG16] shielded wire. The
Permissible Length
length of this section (L and overall length.
8) should be included in the calculation of the maximum length
Prohibited items
OC
(51)
TB7TB3
M1 M2
S
M1 M2
S
OC
(53)
TB7
TB3
M1 M2
S
Unit
M1M2
S
System controller
M1M2
S
S
M1M2
Power Supply
: Group: Group: Group: Shielded Wire: Sub Remote Controller
( ): Address
TB5
M1 M2
TB5
M1 M2
AB
RC
(104)
(02)
(04)
IC
S
IC
S
TB5
M1 M2
(105)
RC
TB5
M1 M2
(05)
(07)
IC
S
IC
S
IC
(01)
TB5
M1 M2
S
AB AB AB
(101)
RC
IC
(03)
TB5
M1 M2
S
(155)
RC
IC
(06)
TB5
M1 M2
S
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to different outdoor units (OC).
• Set all addresses to ensure that they are not overlapped.
• M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wring together
24
C. Example of a MA remote controller system (address setting is not necessary.)
OCH502C
NOTE : In the case of same group operation, need to set the address that is only main indoor unit.
Example of wiring control cables Wiring Method and Address Setting
1. Standard operation
L
1 L2
OC
00
TB3
TB7
M1 M2SM1 M2
S
TB5
M1 M2
IC
00
TB15
12
S
N1
AB
TB5
M1 M2
IC
00
TB15
12
S
AB
a. Use feed wiring to connect terminals M1 and M2
on transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmis­sion cable block (TB5) of each indoor unit (IC). Use non-polarized 2 wire.
b. Connect terminals 1 and 2 on transmission cable
terminal block (TB15) for each indoor unit with the terminal block for the MA remote controller (MA).
N2
• 1 remote controller for each indoor unit.
2. Operation using two remote controllers
OC
00
IC
00
TB5
TB3
TB7
M1 M2SM1 M2
S
N3
• Using 2 remote controllers
for each indoor unit.
M1 M2
TB15
S
12
AB
MA
3. Group operation
OC
00
IC
00
TB3
TB7
M1 M2SM1 M2
S
N7
TB5
TB15
M1 M2SM1 M2
AB
MAMA
IC
00
TB5
TB15
M1 M2
S
N4
AB
MA MA MA
12
N5
AB AB
IC
00
TB5
S
M1 M2
S
N6
TB15
12
a. The same as above. b. The same as above. c. In the case of using 2 remote controllers, connect
terminals 1 and 2 on transmission cable terminal block (TB15) for each indoor unit with the terminal block for 2 remote controllers.
· Set the sub remote controller position for one of MA remote controller’s main switch.
Refer to the installation manual of MA remote con-
troller
a. The same as above. b. The same as above. c. Connect terminals 1 and 2 on transmission cable
terminal block (TB15) of each indoor unit, which is doing group operation with the terminal block the MA remote controller. Use non-polarized 2 wire.
d. In the case of same group operation, need to set the
address that is only main indoor unit. Please set the smallest address within number 01-50 of the indoor unit with the most functions in the same group.
• Multiple indoor units operated together by 1 remote controller
Combinations of 1 through 3 above are possible.
MA
N8
25
Permissible Lengths Prohibited items
OCH502C
Longest transmission cable length L
1 + L2 [ 200 m [656 ft] (1.25 mm²
[AWG16]) MA remote controller cable length
R
1, R2 [ 200 m [656 ft] (0.3 ~ 1.25
mm² [AWG22 to AWG16])
Longest transmission cable length The same as above. MA remote controller cable length
R
3 +R4, R5 +R6 [ 200 m [656 ft]
(0.3 ~ 1.25 mm² [AWG22 to AWG16])
TB3
M1 M2
S
OC
00
OC
00
TB7
M1 M2
The MA remote controller and the M-NET remote controller cannot be used together with the indoor unit of the same group.
IC
00
TB5
TB15
S
M1 M2
12
S
AB
TB5
M1 M2
IC
00
TB15
12
S
ABAB
MAMARC
3 MA remote controller or more cannot be connected with the indoor unit of the same group.
IC
00
IC
00
Longest transmission cable length The same as above. MA remote controller cable length
R
7 +R8 [ 200 m [656 ft] (0.3 ~ 1.25
mm² [AWG22 to AWG16])
TB3
M1 M2
TB3
M1 M2
S
S
OC
TB7
M1 M2
TB7
M1 M2
TB5
TB15
S
M1 M2
AB AB AB AB AB
12
S
MA
TB5
TB15
12
M1 M2
S
MA MA MAMA
The second MA remote controller is connected with the terminal block (TB15) for the MA remote controller of the same indoor unit (IC) as the first remote control.
IC00
00
TB5
TB15
12
M1 M2
S
S
TB5
M1 M2
S
IC
00
TB15
12
26
AB
MA
AB
MA
D. Example of a group operation with 2 or more outdoor units and a MA remote controller.
OCH502C
(Address settings are necessary.)
L1
L2
L6
Examples of Transmission Cable Wiring
L7
: Group: Group: Group: Shielded Wire: Sub Remote Controller
( ): Address
OC
(51)
TB7
TB3
M1 M2SM1 M2
OC
(53)
TB7
TB3
M1 M2
M1M2
S
Power Supply
Unit
M1M2
S
System controller
M1M2
S
IC
(05)
TB15
S
12
AB AB
MAMAMA
IC
(07)
TB15
S
12
IC
2
m
(06)
TB5
TB15
M1M2
S
12
1
m4
m
3
m
IC
(01)
S
TB15 TB15
M1 M2
S
12
AB
m3
MA
L3
IC
(03)
TB15
S
M1 M2
TB5
S
12
IC
2
m
(02)
TB5TB5
M1 M2
S
12
1
m
M1M2
TB5
L4
IC
(04)
TB5
M1 M2
TB15
S
12
AB
TB5
M1 M2
1
m
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit
(OC). e. DO NOT change the jumper connector CN41 on MULTI controller board. f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary. Connect the termi-
nal S on the power supply unit with the earth. g. Set the address setting switch as follows.
Unit Range Setting Method
IC (Main) 01 to 00
IC (Sub) 01 to 50
Wiring Method Address Settings
Outdoor Unit 51 to 100
Main Remote Controller 101 to 150
Sub Remote Controller 151 to 200
MA Remote Controller
Use the smallest address within the same group of indoor units. Use an address, other than the IC (Main) in the same group of indoor units. This must be in sequence with the IC (Main). Use the smallest address of all the indoor units plus 50.
*The address automatically becomes “100” if it is set as “01 - 50”. Set at an IC (Main) address within the same group plus 100.
Set at an IC (Main) address within the same group plus 150.
Unnecessary address setting (Necessary main/ sub setting)
h. The group setting operations among the multiple indoor units are done by the remote controller (RC) after the electri-
cal power has been turned on.
27
• Name, Symbol, and the Maximum Units for Connection
OCH502C
Longest length via outdoor unit (M-NET cable):
L
1+L2+L3+L4
and L1+L2+L6+L7 [ 500 m [1640 ft] (1.25 e [AWG16] or more)
Longest transmission cable length (M-NET cable):
L
1
and L3+L4 and L6 and L2+L6 and L7 [ 200 m
Remote controller cable length:
m1
Permissible LengthProhibited items
and m1+m2+m3 and m1+m2+m3+m4
[ 200 m
[656 ft]
[656 ft]
(1.25 e
[AWG16]
(0.3 to 1.25 e
or more)
[AWG22 to AWG16]
)
OC
(51)
TB7TB3
M1M2
M1M2
S
S
OC
(53)
TB7
TB3
M1M2
S
Unit
M1 M2
S
System controller
M1 M2
S
S
M1M2
Power Supply
: Group: Group: Group: Shielded Wire: Sub Remote Controller
( ): Address
IC
(01)
TB5 TB15 TB15
M1 M2
S
12
AB
MA
IC
(03)
TB15
TB5
M1 M2
S
12
TB5
M1 M2
TB5
M1 M2
IC
(02)
IC
(04)
S
S
IC
(05)
TB15TB5
M1 M2
TB5
M1 M2
S
12
AB AB
MAMAMA
IC
(07)
S
12
12
TB15 TB15
12
AB
IC
(06)
TB15TB5
M1 M2
S
12
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to different outdoor units (OC).
• M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wring together.
28
8 TROUBLESHOOTING
ON/OFF
TEST RUN
°C
1Hr.
FILTER
CHECK TEST
TEMP.
TIMER SET
Check code indicator (see NOTE 1) Test run remaining time indicator (see NOTE 3)
Display panel
(M-NET Remote controller)
ON/OFF button
ON/OFF LED (Lights up in operation)
LOUVER button
TEST RUN button
AIR DIRECTION button
FAN SPEED button
TEST RUN indicator
Indoor unit liquid pipe temperature indicator (see NOTE 4)
(Cooling/Heating) OPERATION SWITCH button ,
Control panel
OCH502C
8-1. CHECK POINTS FOR TEST RUN
8-1-1. Procedures of test run
(1) Before a test run, make sure that the following work is completed.
• Installation related : Make sure that the panel of cassette type and electrical wiring are done. Otherwise electrical functions like auto vane will not operate normally.
• Piping related : Perform leakage test of refrigerant and drain piping. Make sure that all joints are perfectly insulated. Check stop valves on both liquid and gas side for full open.
• Electrical wiring related : Check ground wire, transmission cable, remote controller cable, and power supply cable for secure connection. Make sure that all switch settings of address or adjustments for special specification systems are correctly settled.
(2) Safety check :
With the insulation tester of 500V, inspect the insulation resistance. Do not touch the transmission cable and remote controller cable with the tester. The resistance should be over 1.0 M". Do not proceed inspection if the resistance is under 1.0 M". Inspect between the outdoor unit power supply terminal block and ground first, metallic parts like refrigerant pipes or the
electrical box next, then inspect all electrical wiring of outdoor unit, indoor unit, and all linked equipment .
(3) Before operation :
a) Turn the power supply switch of the outdoor unit to on for compressor protection. For a test run, wait at least 12 hours
from this point.
b) Register control systems into remote controller(s). Never touch the on/off switch of the remote controller(s). Refer
to “ 8-1-2. Special Function Operation and Settings (for M-NET Remote Controller)” as for settings. In MA remote controller(s), this registration is unnecessary.
(4) More than 12 hours later from power supply to the outdoor unit, turn all power switch to on for the test run. Perform test run
according to the “Operation procedure” table of the bottom of this page. While test running, make test run reports .
(5) When you deliver the unit after the test run, instruct the end user for proper usage of the system using owners’ manual and
the test run report you made to certificate normal operation. If abnormalities are detected during test run, refer to “8-1-3. Countermeasures for Error During Test Run”. As for DIP switch setting of outdoor unit, refer to “8-5. INTERNAL SWITCH FUNCTION TABLE”.
Turn on the main power supply of all units at least 12 hours before test run. ”HO” appears on display panel for 3 min.
1
12 hours later, press TEST RUN button twice to perform test run. “TEST RUN “ appears on display panel.
2
Press OPERATION SWITCH button to make sure that air blows out.
3
Select Cooling (or Heating) by OPERATION SWITCH button to make sure that cool (or warm) air blows out.
4
Press Fan speed button to make sure that fan speed is changed by the button.
5
Press AIR DIRECTION button or LOUVER button to make sure that air direction is adjustable (horizontal, downward, upward, and each angle).
6
Check outdoor fans for normal operation.
7
Check interlocked devices (like ventilator) for normal operation, if any. This is the end of test run operation.
8
Press ON/OFF button to stop and cancel test run.
9
Notes: 1. If error code appears on remote controller or remote controller malfunctions, refer to “ 8-1-3. Countermeasures for Error During Run”.
2.
3. During test run, the indoor liquid pipe temperature is displayed on remote controller instead of room temperature.
4.
During test run operation, 2-hour off timer activates automatically and remaining time is on remote controller and test run stops 2 hours later.
Depending on a model, “This function is not available” appears when air direction button is pressed. However, this is not malfunction
Operation procedure
2929
.
8-1-2. Special Function Operation and Settings (for M-NET Remote Controller)
(alternating display)
These alternating IC or LC displays will appear when entry is completed normally.
A flashing “88” will appear if there is a problem with the entry (indicating that the unit does not exist).
OCH502C
• It is necessary to perform “group settings” and “paired settings” at making group settings of different refrigerant systems (multiple outdoor unit). (A) Group settings: Enter the indoor unit controlled by the remote controller, check the content of entries, and clear entries,
etc.
(B) Paired settings: Used to set the linked operation of a Lossnay unit.
(1) Entering address: Follow the steps below to enter the addresses of the indoor unit using the remote controller.
a) Group settings
• Turning off the remote controller: Press the ON/OFF button to stop operation (the indicator light will go off).
• Changing to indoor unit address display mode: If the FILTER and k buttons on the remote controller are pressed simul­taneously and held for 2 seconds, the display shown in Figure 1 will appear.
• Changing address: Press the temperature adjustment be entered.
• Entering the displayed address: Press the TEST RUN button to enter the indoor unit with the displayed address. The type of the unit will be displayed as shown in Figure 2 if entry is completed normally. If a selected indoor unit does not exist, an error signal will be displayed as shown in Figure 3. When this happens, check whether the indoor unit actually exists and perform entry again.
• Returning to the normal mode after completing entry: Press the FILTER and k buttons simultaneously and hold for 2 seconds to return to the normal mode.
buttons to change the displayed address to the address to
Figure 1. (A) Group setting display
b) Paired Settings
• Turn off the remote controller: Press the remote controller’s ON/OFF button to turn it off (the indicator light will go off).
• Put in indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for 2 seconds.
*The above steps are the same as when making group settings (A).
• Changing to the linked operation unit address display state: The display shown in Figure 4 will appear when the button on the remote control is pressed.
• Displaying the address of the Lossnay unit and linked indoor unit: In this situation, the indoor unit number will be the lowest address of the group. The Lossnay unit will not operate if this setting is incorrect.
* If the temperature adjustment buttons are pressed, the address may be changed to the indoor unit that are to be
linked.
* If the time setting buttons are pressed, the address of the linked units may be changed to the address where it is
desired to enter the Lossnay .
• Linking the Lossnay and the indoor unit: The display shown in Figure 5 will appear when the TEST RUN button is pressed. The indoor unit whose address is displayed and the Lossnay unit with a linked address will operate in a linked manner.
* If it is desired to display the address of the Lossnay in the indoor unit address, display the indoor unit address in the linked
unit address, and the above content will also be recorded.
* Apart from the indoor unit with the lowest address in the group, display and enter the addresses of the other indoor unit that
are to be linked with the Lossnay unit.
• Returning to the normal mode after completing entry: Press the FILTER and k buttons on the remote controller simulta­neously and hold for 2 seconds to return to the normal mode.
Figure 2. Normal completion of entry
Figure 3. Entry error signal
Flashing “88” indicates entry error.Type of unit is displayed.
a
Figure 4. (B) Making paired settings
The addresses of indoor unit and linked units are displayed simultaneously.
Figure 5. Completing normal entry
30
Loading...
+ 84 hidden pages