13. PARTS LIST ····················································86
1
···22
OUTDOOR UNIT
1TECHNICAL CHANGE
PUMY-P125YMA ➔ PUMY-P125YMA1
1. Addition of new function (Auto Change Over)
PUMY-P125YMA : Not equipped
PUMY-P125YMA1 : Equipped
2. Difference of operation switching logic for the outdoor output connector (CN3D)
PUMY-P125YMA : CN3D 1-2 ······ OPEN : Heating CLOSE : Cooling
PUMY-P125YMA1 : CN3D 1-2 ······ OPEN : Cooling CLOSE : Heating
3. Difference of the role of SW5-1 (function selection switch)
PUMY-P125YMA : Fix the operation frequency ······························ ON : Fix OFF : Normal
PUMY-P125YMA1 : Auto Change Over from Remote Controller ······ ON : Enable OFF : Disable
2
2SAFETY PRECAUTION
Cautions for using with the outdoor unit which adopts R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to deteriorate.
· Do not use copper pipes which are broken, deformed or discolour .
In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust /
dirt, shaving particles, oils, moisture or any other contamination.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil will
result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before
brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections.
-The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to fill the system.
-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance
may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
· Use a vacuum pump with a service port.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
· Do not use the following tools that are used with conventional refrigerant.
(Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge,
refrigerant recovery equipment)
-If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated.
-If water is mixed in the R407C, the refrigerant oil may deteriorate.
-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.
· Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
· Be especially careful when managing the tools.
-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Do not use the drier which is sold in the field.
-The drier for R407C refrigerant is pre-attached to outdoor unit refrigerant circuit.
-Some drier in the field are not in conformity with R407C refrigerant.
3
Gravimeter
Unit
[1] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No.Tool nameSpecifications
1Gauge manifold·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF 7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2Charge hose·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3Electronic scale
4Gas leak detector·Use the detector for R407C.
5Adapter for reverse flow check.·Attach on vacuum pump.
6Refrigerant charge base.
7Refrigerant cylinder.·For R407C·Top of cylinder (Brown)
·Cylinder with syphon
8Refrigerant recovery equipment.
[2] Notice on repair service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[3] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
• A handy remote controller for use in conjunction
with the Melans centralized management system.
• Addresses must be set.
• Addresses setting is not necessary.
•
Only the indoor unit for MA remote controller
(the end of model name is -A) can be used.
MA remote controller
PAR-20MAA-E
3-1. UNIT CONSTRUCTION
Outdoor unit
5HP
PUMY-P125VMA
PUMY-P125YMA
PUMY-P125YMA
1
Indoor unit
that can be
connected
Branching pipe
components
Capacity
Number of units
Total system wide capacity
CMY-Y62-C-ECMY-Y64-CCMY-Y68
Branch header
(2 branches)
Type 20~Type 125
1~8 units
50~130% of outdoor unit capacity
Branch header
(4 branches)
Branch header
(8 branches)
CMY-S65
Multi distribution
Piping on outdoor
unit
(5 branches)
Decorative panel
5
3-2. UNIT SPECIFICATIONS
P L F Y - P 80 V AM - APU M Y - P 125 V M A
PAC type
AM
KM
M
KM
LMD
Frequency
conversion
controller
Refrigerant
R407C/R22
commonness
Refrigerant
R407C
NEW frequency converter
one-to-many air conditioners
(flexible design type)
Indicates equivalent
to Cooling capacity
Indicates equivalent
to Cooling capacity
Power supply
V: Single phase
220-230-240V 50Hz
220V 60Hz
Power supply
V: Single phase
220-230-240V 50Hz
Y: 3-phase
380-400-415V 50Hz
380V 60Hz
L : Ceiling cassette
K : Wall-mounted type
E : Hidden skylight type
C: Ceiling suspended type
M: Ceiling cassette type
F : Floor standing type
}
M-NET
control
M-NET control
MA control
Sub-number
Frequency
conversion
controller
Outdoor unit
MULTI-S
Service Ref.
w
PUMY-P125VMA
PUMY-P125YMA
PUMY-P125YMA1
Capacity
Cooling (kW)
Heating (kW)
14.0
16.0
3.5Motor for compressor (kW)
Cooling
W.B. 15~24°C
D.B. -5~46°C
Heating
D.B. 15~27°C
W.B. -15~15.5°C
Indoor-side intake air temperature
Outdoor-side intake air temperature
(1) Outdoor Unit
Cooling / Heating capacity indicates the maximum value at operation under the following condition.
w. Cooling Indoor: D.B. 27°C / W.B. 19.0°C
Outdoor : D.B. 35°C
Heating Indoor: D.B. 20°C
Outdoor : D.B. 7°C / W.B. 6°C
(2) Method for identifying MULTI-S model
■ Indoor unit < When using Model 80 >
■ Outdoor unit <When using model 125 >
(3) Operating temperature range
Notes D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
6
3-3. SYSTEM LAYOUT
A
B
a
indoor
1
C
b
indoor
2
D
c
indoor
3
e
d
indoor
4
indoor
5
First branch
(branching connector)
Outdoor unit
125
804040
Outdoor unit
Indoor unit
Type 20 ~ Type 125
PUMY-P125VMA
PUMY-P125YMA
PUMY-P125YMA
1
1~8 units
63~163
Indoor unit that can connected
Available capacity of indoor unit
Total capacity of units that can be included system
(50-130% of outdoor unit capacity)
3-3-1. System layout
One outdoor unit using branching connectors can be connected to a maximum of eight indoor units.
■Examples of a branching method
3-3-2. Notes on the connection of indoor and outdoor units
Note: When the total capacity of indoor units exceeds the capacity of the outdoor unit (more than 100%), the rated power of
each indoor unit will be less when they are running simultaneously.
3-3-3. Capacity for outdoor unit
(1) Branching pipe
Model
CMY-Y62C-E
Branching connector
(2) Examples of System Construction (All models)
PIping method
Indoor units
CMY-Y64-C
CMY-Y68
CMY-S65
Outdoor unit
NUMBER OF BRANCHING POINTS
2
4
8
5
Total capacity of
indoor units.
160
7
4SPECIFICATIONS
PUMY-P125VMA
14.0
6.10
28.3-27.1-26.0
98
17
16.0
6.03
28.0-26.7-25.7
98
17
Single phase 220-230-240V 50Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 1020 o 350 (+30)
Crossover fin
EEV48FAM
Fully enclosed type o 1
Frequency converter start
3.5
Cooling 27-100% Heating 25-100%
1.9 (104Hz)
—
1.4 (MEL32)
Propeller (direct) o 2
90(3,177)
60 o 2
Reverse cycle
—
High pressure pressure sensor (3.0MPa)
Thermal switch
Thermal switch
Overheating, excessive current protection
54
127(280)
19.05
9.52
R407C o 8.5
Expansion valve
Item
Service Ref.
Unit
Standard performance
Heating Cooling
Rated Cooling capacity
Rated power consumption
Operating current
Operating power factor
Starting current
Rated Heating capacity
Rated power consumption
Operating current
Operating power factor
Starting current
Rated power supply
Type o charge amount
Control method
External finish (Munsell colour-coded markings)
Dimensions H o W o D (Note 1)
Heat exchanger type
Defrost method
Pressure gauge
Noise level
Weight
Refrigerant pipe size
Refrigerant
Model
Type o quantity
Starting method
Motor output
Capacity control
Daily cooling capacity
Heater <crankcase>
Refrigerating oil (Model)
Type o quantity
Airflow
Motor output
High pressure protection
Compressor protection
Blower protection
Frequency converter circuit
Compressor
Protection
devices
Gas
Liquid
Fan
kW
kW
A
%
A
kW
kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min(CFM)
W
dB
kg(lbs)
[ mm
[ mm
kg
Note 1: External dimensions in parentheses indicate the dimensions of protruding parts.
Note 2: Rating conditions (JIS B 8616)
Cooling : Indoor : D.B. 27: W.B. 19:
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 20:
: Outdoor : D.B. 7: W.B. 6:
8
Item
Rated Cooling capacity
Rated power consumption
Operating current
Operating power factor
Starting current
Rated Heating capacity
Rated power consumption
Operating current
Operating power factor
Standard performance
External finish (Munsell colour-coded markings)
Dimensions H o W o D (Note 1)
Heat exchanger type
Compressor
Fan
Defrost method
Pressure gauge
Protection
Noise level
Weight
Refrigerant pipe size
Refrigerant
Note 1: External dimensions in parentheses indicate the dimensions of protruding parts.
Model
Type o quantity
Starting method
Motor output
Capacity control
Daily cooling capacity
Heater <crankcase>
Refrigerating oil (Model)
Type o quantity
Airflow
Motor output
High pressure protection
Compressor protection
Blower protection
devices
Frequency converter circuit
Type o charge amount
Control method
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 20:
: Outdoor : D.B. 7: W.B. 6:
Service Ref.
Gas
Liquid
Unit
kW
kW
A
%
A
kW
kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min(CFM)
W
dB
kg(lbs)
[ mm
[ mm
kg
3 phase 380-400-415V 50Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 1020 o 350 (+30)
Fully enclosed type o 1
Frequency converter start
Cooling 27-100% Heating 25-100%
Propeller (direct) o 2
High pressure pressure sensor (3.0MPa)
Overheating, excessive current protection
PUMY-P125YMA
PUMY-P125YMA
14.0
5.95
9.6-9.1-8.8
94
8.0
16.0
5.58
9.2-8.8-8.5
92
8.0
Crossover fin
EEV48FAK
3.5
1.9 (104Hz)
—
1.4 (MEL32)
90(3,177)
60 o 2
Reverse cycle
—
Thermal switch
Thermal switch
54
127(280)
19.05
9.52
R407C o 8.5
Expansion valve
1
9
5DATA
Model 20
Model Number for indoor unit
Model Capacity
kW
22
Model 2528Model 3236Model 4045Model 5056Model 6371Model 7180Model 8090Model 100
112
Model 125
140
5-1. COOLING AND HEATING CAPACITY AND CHARACTERISTICS
5-1-1. Method for obtaining system cooling and heating capacity:
To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings
of all the indoor units connected to the outdoor unit (see table below), and then use this total to find the standard capacity with
the help of the tables on page 11 to 14.
(1) Capacity of indoor unit
(2) Sample calculation
1System assembled from indoor and outdoor unit (in this example the total capacity of the indoor units is greater than
that of the outdoor unit)
• Outdoor unit PUMY-P125YMA
• Indoor unit PKFY-P25VAM-A o 2 , PLFY-P50VLMD-A o 22According to the conditions in 1, the total capacity of the indoor unit will be: 28 o 2 +
56 o 2 = 168
Capacity (kW)
Cooling
14.60
AB
Heating
16.33
Outdoor unit power consumption (kW)
Cooling
6.04
Heating
5.14
Outdoor unit current (A)
Cooling
8.9
Heating
7.8
5-1-2. Method for obtaining the heating and cooling capacity of an indoor unit:
(1) The capacity of each indoor unit (kW) = the capacity A(or B) o
(2) Sample calculation (using the system described above in 4-1-1. (2) ):
During cooling: During heating:
• The total model capacity of the indoor unit is:
2.8 o 2 + 5.6 o 2=16.8kW
Therefore, the capacity of PKFY-P25VAM-A and
PLFY-P50VLMD-A will be calculated as follows by
using the formula in 4-1-2. (1):
Model 25=14.6 o= 2.43kW
Model 50=14.6 o= 4.87kW
2.8
16.8
5.6
16.8
total model capacity of all indoor units
• The total model capacity of indoor unit is:
3.2 o 2 + 6.3 o 2=19.0
Therefore, the capacity of PKFY-P25VAM-A and PLFYP50VLMD-A will be calculated as follows by using the
formula in 4-1-2. (1):
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the formula on page 8.
415V, 50Hzw
14
5-3. CORRECTING COOLING AND HEATING CAPACITY
Service Ref.PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA1
Rated cooling capacity
Rated heating capacity
Indoor D.B. 27°C / W.B. 19°C
Outdoor D.B. 35°C
Indoor D.B. 20°C
Outdoor D.B. 7°C / W.B. 6°C
0.4
-5 010203040 46
0.6
0.8
1.0
1.2
1.4
0.6
0.8
1.0
1.2
1.4
22
20
18
16
22
20
18
16
0.4
-12 -100105-515
0.6
0.8
1.0
1.2
1.4
0.6
0.8
1.0
1.2
1.4
15
20
25
20
15
25
5-3-1. Correcting Changes in Air Conditions
(1)The performance curve charts (Figure 1, 2) show the rated capacity (total capacity) under the stated conditions when standard
length for piping (5m) is used. The rated power is derived from the capacity ratio and power ratio obtained for the indoor and
outdoor intake temperatures at time 1.
• Standard conditions:
• Use the rated capacity and rated power values given in the characteristics table for each indoor unit.
• The capacity is the single value on the side of the outdoor unit; the capacity on the sides of each indoor unit must be
added to obtain the total capacity.
(2)The capacity of each indoor unit may be obtained by multiplying the total capacity obtained in (1) by the ratio between the
individual capacity at the rated time and the total capacity at the rated time.
Individual capacity under stated conditions = total capacity under the stated conditions o
(3)Capacity correction factor curve
individual capacity at the rated time
total capacity at the rated time
Figure 1. PUMY-P125VMA PUMY-P125YMA
PUMY-P125YMA
Cooling performance curve
Cooling
Capacity
(ratio)
Cooling
Power
consumption
(ratio)
1
INDOOR
<W.B. :>
INDOOR
<W.B. :>
Figure 2. PUMY-P125VMA PUMY-P125YMA
PUMY-P125YMA
Heating performance curve
Heating
Capacity
(ratio)
Heating
Power
consumption
(ratio)
1
INDOOR
<D.B. :>
INDOOR
<D.B. :>
Outdoor <D.B. ::>
Outdoor <W.B. ::>
15
5-3-2. Correcting Capacity for Changes in the Length of Refrigerant Piping
1.0
0.95
0.9
5 10152025303540455055
1.0
63 (50%)
94 (75%)
125 (100%)
163 (130%)
0.95
0.9
0.85
0.8
5 10152025303540455055
(1) During cooling, to obtain the ratio (and the equivalent piping length) of the outdoor units rated capacity and the total
in-use indoor capacity, first find the capacity ratio corresponding to the standard piping length (5m) from Figures 3
at first, and then multiply by the cooling capacity from Figure 1 to obtain the actual capacity.
(2) During heating, to find the equivalent piping length, first find the capacity ratio corresponding to standard piping length (5m)
from Figure 4, and then multiply by the heating capacity from Figure 2 to obtain the actual capacity.
(3) Method for Obtaining the Equivalent Piping Length
Equivalent length for type 125 = (length of piping to farthest indoor unit) + (0.35 o number of bends in the piping) (m)
Length of piping to farthest indoor unit: type 125.....70m
5-3-3. Correction of Heating Capacity for Frost and Defrosting
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction
factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature (W.B.°C)
Correction factor
6
1.0
4
0.98
2
0.89
0
0.88
-2
0.89
-4
0.9
-6
0.95
-8
0.95
-10
0.95
16
PUMY-P125VMA
PUMY-P125YMA
PUMY-P125YMA
90
80
NOTCH
SPL(dB) LINE
Hi54
1
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63125250500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
NC-20
1m
MICROPHONE
1m
17
6OUTLINES AND DIMENSIONS
• OUTDOOR UNITS
PUMY-P125VMA
PUMY-P125YMA
PUMY-P125YMA1
Optional parts
(base branching
pipe) installation
hole
Terminal block for transmission
Terminal block for central control
Terminal block for power source
Liquid refrigerant pipe
connection {9.52 (3/8F)
Gas refrigerant-pipe
connection {19.05 (3/4F)
Knock out hole for right piping
Knock out holes for
power line 2-{27
Knock out holes for power line 2-{29
unit : mm
shaped notched holes
(standard bolt M10)
Air intake
Air outlet
Handle for
Optional parts
installation hole
Rear air intake
Side air intake
moving
Knock out hole for
front piping
Oval holes
Piping cover
(standard bolt M10)
Bottom piping hole
Drain hole
(3-{33 hole)
Handle for moving
18
Rear piping hole
when a piping cover is used for aesthetic reasons.
✻1...Indicates the dimensions of the cutoff valve connector.
✻2...Make sure that the panel can be easily removed for maintenance
Connector(Connected for Option)
Auto Change Over Signal
CN3S
Connector(Connected for Option)
Demand Signal
Relay(Magnetic Contactor)
X500
Relay(4-Way Valve)
X501
Relay(Solenoid Valve)
X502
Digital Indication LED
LED1,2
Operation Inspection Indication
WHT
WHT
F.C
F1
MF1
RED
ORN
BLU
31
BLU
MF1
(WHT)
X500
21S4(GRN)
X501
X502
F2
CNAC
31
(RED)
C2
52C(ORG)
1
3
1
3
SV(BLK)
1
3
CH(BLU)
1
3
YLW
YLW
BLU
BLU
BLK
BLK
52C
21S4
SV1
RED
C2
ORN
BLU
BLU
CN40(WHT)CN41(WHT)
(6.3A)(6.3A)
W
V
U
LED1
< P.B.>
BLK
WHT
RED
MC
CE
+
CN5
(RED)
LI
NI
< N.F.>
21
31
CNAC2
(RED)
LO
NO
EI
THHS_A
THHS_B
RS
52C
2
1
2
1
2
1
2
1
CN4
(WHT)
CN3
(WHT)
CN6
(WHT)
CN5
(RED)
SCR-N1
SCR-P1
13
IGBT
CNDC
(PNK)
+
-
+
+
51234
CNAF (WHT)
743215
66
CN2 (WHT)
SCR-S
SCR-R
SCR-P2
SCR-N2
NOTES: 1. Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2. Symbols used in wiring diagram above are. :Terminal block, :Connector, :Insertion tab.
3. Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LED1,2
(LED indication)found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
4. For the system utilizing R-converter units(PAC-SF29LB),the following functions are not available.
SW3;TEST RUN SW5-1;AUTO CHANGE OVER CN3D;AUTO CHANGE OVER(external singnal)
5. The input for CN3D 1-2(AUTO CHANGE OVER EXTERNAL SIGNEL)is as follows.
Short;heating Open;Cooling(It differs from Service ref.PUMY-P125YMA)
•During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
Bit
Indication
1876543
Compressor
operated
2
52C
Always lit---SV121S4
•When fault requiring inspection has occurred
The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.
L2
652341
P
N1
N2
I
L1
ACTM
(Example)
When the compressor and SV1 are
turned during cooling operation.
78563421
DCL3DCL4
DCL1DCL2
+
-
19
PUMY-P125YMA
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
RD2
123
CN3S
(RED)
CN3S CONNECTOR <DEMAND SIGNAL>
operated
NOTES : 1. Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2. Symbols used in wiring diagram above are. : Terminal block, : Connector, :Insertion tab.
3. Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch (SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
7
8
5
634
2
1
(Example)
When the compressor and SV1 are
turned during cooling operation.
Always lit---SV121S4
1876543
52C
2
Compressor
Indication
Bit
•During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
•When fault requiring inspection has occurred
The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.
NO FUSE BREAKER
25A
L1
L2
L3
N
X
X
1
1
(WHT)
CN3D
(WHT)
CN51
(WHT)
CN41
(WHT)
CN40
5321432143214321
YLW
CB2
CB1
CNR
(WHT)
CNR
(WHT)
(RED)
CNA
<POWER SUPPLY BOARD>
(YLW)
49C
(RED)
CN1
FUSE1
(6.3A)
FUSE2
(2A)
SLEV
6
1
2
5764
49C
YLW
311234567
1234567
123671234561236
123671236
CN4CN3CN2
CN4CN3CN2
(YLW)(YLW)(WHT)
(YLW)(RED)(YLW)(WHT)
2432112345678
109876543212876543
SW3SW5
OFF
ON
OFF
ON
SW4
SW1SW2
OFF
ON
1
1
ON
OFF
ON
OFF
(YLW)
ACCT
654321
132
CN1
3
63HS
6541321231132121
THHS
TH1TH2TH5TH6
63HS
THHS
TH2TH6 TH5TH1
(BLK) (WHT)(GRN)(GRN)(WHT) (WHT)
SLEV
(WHT)
BLU
~
~
~
LO1
LO2
LO3
LI3
E
N
LI2
LI1
(RED)
31
CNA
13
GRN
6
YLW
YLW
WHT
BLK
RS1
RB2 RB1
RD1
BLK
RED
BLU
WHT
GRN
E
P
N
C03
C02C01
NP1PN1
10
3
5
6
8
10
3568
+
–
IPM
WV
-
+
+
-
RED
WHT
BLK
3113
31
(BLU)
52C
X71
YLW
YLW
52C
31
(GRN)
21S4
X72
BLU
BLU
21S4
SV1
BLK
BLK
13
(BLK)
SV1
(WHT)
MF2
(WHT)
MF1
MF1
C1
31
WHT
BLU
WHT
BLURED
ORN
RED
ORN
BLU
WHT
31
BLU
52C
N
BLU
L3
BLK
L1
RED
S
M1
M2
S
M2
M1
LD1
SWU1
(1st digit)
SWU2
(2nd digit)(3rd digit)
SWU3
<RESISTOR BOARD>
CNS1
(RED)
CNS2
(YLW)
F.C
2
1
1
GRN/YLW
ZNR
–
+
–
+
BLU
BLK
2
FOR CENTRALIZED
CONTROL
DC 30V (Non-polar)
WHT
BLK
WHT
RED
WHT
ORN
ORN
BRN
BRN
GROUND
TO INDOOR UNIT
CONNECTING WIRES
DC 30V (Non-polar)
DIGITAL INDICATION LED
<OPERATION INSPECTION INDICATION>
FAN MOTOR <INNER THERMOSTAT>
EXPANSION VALVE
HIGH PRESSURE SENSOR
<DISCHARGE PRESSURE DETECTION>
MAGNETIC CONTACTOR
4-WAY VALVE
RELAY <MAGNETIC CONTACTOR>
VARISTOR
FUSE (6.3A)
COMPRESSOR <INNER THERMOSTAT>
NOISE FILTER
THERMISTOR
THERMISTOR
CB1,CB2DMSMOOTHING CAPACITOR
DIODE MODULE
NAME
SYMBOL
20
PUMY-P125YMA1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
9
8
7
6
5
4
3
2
1
0
RD2
123
CN3S
(WHT)
CN3S
CONNECTOR <DEMAND SIGNAL>
operated
NOTES: 1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.Symbols used in wiring diagram above are. :Terminal block, :Connector, :Insertion tab.
3.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
4.For the system utilizing R-converter units(PAC-SF29LB), the following functions are not available.
SW3 : TEST RUN SW5-1 : AUTO CHANGE OVER CN3D : AUTO CHANGE OVER(external singnal)
5.The input for CN3D 1-2(AUTO CHANGE OVER EXTERNAL SIGNEL)is as follows.
Short : heating Open : Cooling(It differs from Service ref. PUMY-P125YMA)
78563421
(Example)
When the compressor and SV1 are
turned during cooling operation.
Always lit---SV121S4
1876543
52C
2
Compressor
Indication
Bit
• During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
• When fault requiring inspection has occurred
The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.
50Hz
380/220-415/240V
3N~
NO FUSE BREAKER
25A
L1
L2
L3
N
X
X
1
1
(WHT)
CN3D
(WHT)
CN51
(WHT)
CN41
(WHT)
CN40
5321432143214321
YLW
CB2
CB1
CNR
(WHT)
CNR
(WHT)(RED)
CNA
<POWER SUPPLY BOARD>
(YLW)
49C
(RED)
CN1
FUSE1
(6.3A)
FUSE2
(2A)
SLEV
6
1
2
5764
49C
YLW
311234567
1234567
123671234561236
123671236
CN4CN3CN2
CN4CN3CN2
(YLW)(YLW)(WHT)
(YLW)(RED)(YLW)(WHT)
2432112345678
109876543212876543
SW3SW5
OFF
ON
OFF
ON
SW4
SW1SW2
OFF
ON
1
1
ON
OFF
ON
OFF
(YLW)
ACCT
654321
132
CN1
3
63HS
654132123113 2121
THHS
TH1TH2TH5TH6
63HS
THHS
TH2TH6 TH5TH1
(BLK) (WHT)(GRN)(GRN)(WHT) (WHT)
SLEV
(WHT)
BLU
–
+
~
~
~
LO1
LO2
LO3
LI3
E
N
LI2
LI1
(RED)
31
CNA
13
GRN
6
YLW
YLW
WHT
BLK
RS1
RB2 RB1
RD1
BLK
RED
BLU
WHT
GRN
E
P
N
C03
C02C01
NP1PN1
10
3
5
6
8
10
3568
+
-
IPM
WV
-
+
+
-
RED
WHT
BLK
3113
31
(BLU)
52C
X71
YLW
YLW
52C
31
(GRN)
21S4
X72
BLU
BLU
21S4
SV1
BLK
BLK
13
(BLK)
SV1
(WHT)
MF2
(WHT)
MF1
MF1
C1
31
WHT
BLU
WHT
BLURED
ORN
RED
ORN
BLU
WHT
31
BLU
52C
N
BLU
L3
BLK
L1
RED
S
M1
M2
S
M2
M1
LD1
SWU1
(1st digit)
SWU2
(2nd digit)(3rd digit)
SWU3
<RESISTOR BOARD>
CNS1
(RED)
CNS2
(YLW)
F.C
2
1
1
GRN/YLW
ZNR
-
+
BLU
BLK
2
FOR CENTRALIZED
CONTROL
DC 30V (Non-polar)
WHT
BLK
WHT
RED
WHT
ORN
ORN
BRN
BRN
GROUND
TO INDOOR UNIT
CONNECTING WIRES
DC 30V (Non-polar)
POWER SUPPLY
W
V
U
U
X73
TB3
TB7
L2
TB1
MF2
C2
MC
DCL
DM
NF
<MULTI CONTROLLER BOARD>
<IPM RADIATOR PANEL TEMP. DETECTION>
<DISCHARGE TEMP. DETECTION>
<OUTDOOR TEMP. DETECTION>
THERMISTOR
<LOW PRESSURE SATURATED TEMP. DETECTION>
TERMINAL BLOCK <TRANSMISSION>
SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT>
SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT>
SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT>
SWITCH <FUNCTION SELECTION>
SW5-1 AUTO CHANGE OVER
OFF : disabled ON : enabled
This system has a scroll compressor. This compressor uses a low pressure shell that typically has a temperature in the
range 30-80°C.
In addition, compressor wiring should be in the direction of rotation to the right. Wire colors are red (U), white(V),
black (W), yellow and yellow (thermal switch).
{2.5 O {0.6 O L500
1
23
({4 O {3.0 O L200) O 2{2.5 O {0.6 O L500
{4 O {2.4 O L360
8-3. SYSTEM CONTROL
For indoor-outdoor
transmission wire
Remote
control wire
indoor-outdoor trnasmission cable
2 remote controllers
Group operation (maximum
16 indoor units)
Outdoor
unit
Indoor unit
Indoor unitIndoor unit
NR
NR
Remote controller
network
Indoor unitIndoor unit
NRNRNR
8-3-1. Operating a Single Refrigerant System
When operating either alone or as part of a group, a M-NET remote controller (NR) may be used to control a single
refrigerant system that does not overlap with any other system.
<Example of system arrangement>
Using a M-NET remote controller (NR)
✽ Address setting must be performed.
✽ The NR wire and indoor and outdoor transmission wires must be a non-polar two wire cable.
✽ One NR may be connected to a maximum of 16 indoor unit.
✽ Two NR units may be used to perform control tasks (the second one pressed will have priority if two are pressed
simultaneously).
✽ For the system utilizing R-Converter units (PAC-SF29LB), the following systems are not available. Group operation
system, centralized controller, group remote controller, etc. (See the installation manual of R-Converter units.)
✽ If the user plans to install multiple refrigerant
systems and a centralized controller in the
future, it is strongly suggested that a NR be
used.
24
8-3-2. System Controller (SC) to Perform Centralized Control
2) Indoor unit that may be connected with an SC are shown as follows.
Centralized controller
Multi-unit controller board
Group controller
3) There may be a maximum of two controllers when a group has 16 indoor units or less.
4) The transmission wire must have a power supply when an SC is used. Please connect the power supply for
the transmission wire to the centralized controller transmission wire.
SC with 2 units or less
SC with 3 to 5 units
5) Use a shielded wire (at least 1.25mm
50 group /50 units
24 group /50 units
8 group /16 units
Power supply for transmission wire PAC-SC33KU
Power supply for transmission wire PAC-SC34KU
2
)for the indoor, outdoor, and centralized controller transmission wires.
In addition, all shielded wires in a system must be grounded at one point. If the length of the remote control
wire exceeds 10m, use an insulated wire for the extra portion.
25
8-3-3. Example for the System
OC
IC
(051)
M1 M2
S
TB512TB15
12
TB15
NR
(001)
IC
M1 M2
S
TB5
(002)
NR
M1 M2 SM1 M2 S
TB3TB7
L2
L1
r1L3
r2
TB6
(101)
TB6
(102)
OC
(051)
IC
M1 M2 S
TB5
(001)
IC
TB5
(002)
NR
TB6
(101)
NR
TB6
(151)
NR
TB6
(102)
NR
TB6
(152)
M1 M2 S
M1 M2 SM1 M2 S
TB3TB7
12
TB15
12
TB15
OC
IC
(051)
M1 M2 S
TB5
NR
(001)
IC
M1 M2 S
TB5
(002)
TB6
(101)
M1 M2 SM1 M2 S
TB3TB7
Main
Sub
12
TB15
12
TB15
• Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed
in the standard system with detailed explanation.
The explanation for the system in this section : Use one single outdoor unit and multiple outdoor units for M-NET remote
control system.
Use one single outdoor unit and multiple indoor units in the multiple outdoor
units for the M-NET remote control system.
A. Example of a M-NET remote controller system (address setting is necessary.)
Example of wiring control cablesWiring Method and Address Setting
1. Standard operation
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit
(OC) to terminals M1 and M2 on the transmission
cable block (TB5) of each indoor unit (IC). Use
non-polarized two wire.
b. Connect terminals M1 and M2 on transmission
cable terminal block (TB5) for each indoor unit with
the terminal block (TB6) for the remote controller
(NR).
c. Set the address setting switch as shown below.
• One remote controller for each
indoor unit.
• Inside ( ) Address: There is no need
for setting the 100 position on the
remote controller.
2. Operation using two remote controllers
• Using two remote controllers
for each indoor unit.
3. Group operation
• Multiple indoor units operated
together by one remote
controller
Combinations of 1through 3 above are possible.
Main
Sub
Main
Sub
Unit
Indoor unit (IC)
Outdoor unit
(OC)
Remote
controller (NR)
Range
001 to 050
051 to 100
101 to 150
Setting Method
Use the most recent
address of all the indoor
unit plus 50.
Indoor unit address plus
100.
a. Same as above.
b. Same as above.
c. Set address switch as shown below.
Unit
Indoor Unit (IC)
Outdoor unit
(OC)
Main Remote
Controller (NR)
Sub Remote
Controller (NR)
Range
001 to 050
051 to 100
101 to 150
151 to 200
Setting Method
Use the most recent
address of all the indoor
units plus 50.
Indoor unit address plus
100.
Indoor unit address plus
150.
a. Same as above.
b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) of the IC main unit with the most
most recent address within the same indoor unit (IC)
group to terminal block (TB6) on the remote controller.
c. Set the address setting switch as shown below.
Unit
IC (Main)
IC (Sub)
Outdoor Unit
Main Remote
Controller
Sub Remote
Controller
Range
001 to 050
001 to 050
051 to 100
101 to 150
151 to 200
Use the most recent address within
the same group of indoor units.
Use an address, other than that of
the IC (Main) from among the units
within the same group of indoor
units. This must be in sequence with
the IC (Main).
Use the most recent address of all
the indoor units plus 50.
Set at an IC (Main) address within
the same group plus 100.
Set at an IC (Main) address within
the same group plus 150.
Setting Method
d. Use the indoor unit (IC) within the group with the
most functions as the IC (Main) unit.
26
—
—
• Name, Symbol and the Maximum Remote controller Units for Connection
OC
IC
MainSub
(051)
M1 M2 S
TB5
NR
(001)
IC
M1 M2 S
TB5
(002)
TB6
(102)
M1 M2 SM1 M2 S
TB3TB7
1
2
TB15
1
2
TB15
1
2
TB15
1
2
TB15
IC
M1 M2
SM1 M2
S
TB5
(001)
IC
TB5
(002)
NR
MainSubMainSub
TB6
(101)
NR
TB6
(151)
NR
TB6
(102)
NR
TB6
(104)
NR
TB6
(103)
M1 M2 SM1 M2 S
TB3TB7
OC
(051)
12
TB15
12
TB15
IC
M1 M2 S1
2M1 M2
S
TB5
TB6
TB15
1
2
TB15
(001)
IC
TB5
(002)
M1 M2 SM1 M2 S
TB3TB7
OC
(051)
MANR
(101)
Name
Outdoor unit
Indoor unit
M-NET remote
controller
Symbol
OC
IC
NR
Maximum units for connection
One OC unit can be connect to 1-8 IC units
Maximum two NR for one indoor unit, Maximum 16 NR for one OC
Permissible LengthsProhibited items
Longest transmission cable length
(1.25 mm
1 + L2, L2 + L3, L3 + L1 [ 200m
L
2
)
Remote controller cable length
1. If 0.5 to 0.75 mm
2
R1, R2 [10m
2. If the length exceeds 10 meters,
the exceeding section should
be 1.25 mm
2
and that section
should be a value within the
total extension length of the
transmission cable and
maximum transmission cable
length. (L
3)
Same as above
• M-NET remote controller(NR) and MA remote controller(MA) cannot be used together.
• Do not connect anything with TB15 of indoor unit(IC).
• Use the indoor unit(IC)
address plus 150 as
the sub remote controller
address. In this case, it
should be 152.
• Three or more remote
controller (NR) cannot
be connected to one
indoor unit.
Same as above
• The remote controller
address is the indoor
unit main address plus
100. In this case, it
should be 101.
27
B. Example of a group operation system with two or more outdoor units and a M-NET remote controller.
M1 M2 S
M1 M2 S
TB7
TB3
IC
(051)
M1 M2 S
TB512TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
NR
(001)
IC
M1 M2 S
TB5
(002)
IC
M1 M2 S
TB5
(004)
IC
M1 M2 S
TB5
(003)
IC
M1 M2 S
TB5
(005)
IC
M1 M2 S
TB5
(007)
IC
M1 M2 S
TB5
(006)
L1
L8
R1
R4
L9
L2L3L4
L5L6L7
TB6
(101)
NR
TB6
(105)
NR
TB6
(103)
NR
TB6
(155)
CN40
OC
Between
terminal blocks
M1 M2 S
M1 M2 S
TB7
TB3
(052)
OC
R2
R3
Shielded wire
(Shielding wires and address settings are necessary.)
Examples of Transmission Cable WiringWiring Method Address Settings
Group 3
Group 5Group 1
Sub remote
controller
( ) Address
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block
(TB3) of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the
indoor unit (IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block (TB6) on the remote controller (NR).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor
unit (OC).
e. Use the grounded wire to connect the S-terminal on the transmission terminal of the outdoor unit (OC) and the
grounded terminal for the electrical components box.
f. On one outdoor unit only, change the jumper connector on the control panel from CN41 to CN40.
g. Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which
the jumper connector was inserted into CN40 in Step above to the ground terminal ; in the electrical component
box.
h. Set the address setting switch as follows.
Unit
IC (Main)
IC (Sub)
Outdoor Unit
Main Remote Controller
Sub Remote Controller
Range
Use the most recent address within the same group of indoor units.
Use an address, other than that of the IC (Main) from among the units within
the same group of indoor units. This must be in sequence with the IC (Main).
Use the most recent address of all the indoor units plus 50.
Set at an IC (Main) address within the same group plus 100.
Set at an IC (Main) address within the same group plus 150.
001 to 050
001 to 050
051 to 100
101 to 150
151 to 200
Setting Method
i. The group setting operations among the multiple indoor units is done by the remote controller (NR) after the electrical
power has been turned on.
28
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.