Mitsubishi Electric PUMY-P125VMA Service Manual

SPLIT-TYPE, HEAT PMUP AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
R407C
Outdoor unit [Model name] [Service Ref.]
PUMY-P125VMA PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA
2003
No.OC272
REVISED EDITION-A
Revision :
•PUMY-P125VMAand PUMY-P125YMA1 are added in REVISED EDITION-A.
•Please void OC272.
PUMY-P125YMA
CONTENTS
1. TECHNICAL CHANGE ·····································2
2. SAFETY PRECAUTION ····································3
3. OVERVIEW OF UNITS······································5
4. SPECIFICATIONS·············································8
5. DATA ·······························································10
6. OUTLINES AND DIMENSIONS······················18
7. WIRING DIAGRAM·········································19
NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION
9. TROUBLESHOOTING ····································34
10. ELECTRICAL WIRING ····································72
11. REFRIGERANT PIPING TASKS·····················75
12. DISASSEMBLY ···············································80
13. PARTS LIST ····················································86
1
···22
OUTDOOR UNIT
1 TECHNICAL CHANGE
PUMY-P125YMA ➔ PUMY-P125YMA1
1. Addition of new function (Auto Change Over)
PUMY-P125YMA : Not equipped PUMY-P125YMA1 : Equipped
2. Difference of operation switching logic for the outdoor output connector (CN3D)
PUMY-P125YMA : CN3D 1-2 ······ OPEN : Heating CLOSE : Cooling PUMY-P125YMA1 : CN3D 1-2 ······ OPEN : Cooling CLOSE : Heating
3. Difference of the role of SW5-1 (function selection switch)
PUMY-P125YMA : Fix the operation frequency ······························ ON : Fix OFF : Normal PUMY-P125YMA1 : Auto Change Over from Remote Controller ······ ON : Enable OFF : Disable
2
2 SAFETY PRECAUTION
Cautions for using with the outdoor unit which adopts R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refriger­ant oil of the new unit to deteriorate.
· Do not use copper pipes which are broken, deformed or discolour .
In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust /
dirt, shaving particles, oils, moisture or any other contamination.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil will result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections.
-The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to fill the system.
-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance
may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
· Use a vacuum pump with a service port.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
· Do not use the following tools that are used with conventional refrigerant. (Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge,
refrigerant recovery equipment)
-If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated.
-If water is mixed in the R407C, the refrigerant oil may deteriorate.
-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.
· Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
· Be especially careful when managing the tools.
-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Do not use the drier which is sold in the field.
-The drier for R407C refrigerant is pre-attached to outdoor unit refrigerant circuit.
-Some drier in the field are not in conformity with R407C refrigerant.
3
Gravimeter
Unit
[1] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF 7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2 Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3 Electronic scale 4 Gas leak detector ·Use the detector for R407C. 5 Adapter for reverse flow check. ·Attach on vacuum pump. 6 Refrigerant charge base. 7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8 Refrigerant recovery equipment.
[2] Notice on repair service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[3] Refrigerant recharging
(1) Refrigerant recharging process
1 Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
4
3 OVERVIEW OF UNITS
20 25 32 40 50 63 71
80 100 125
– 32VKM-A 40VKM-A 50VKM-A 63VKM-A
– 80VAM-A
100VAM-A 125VAM-A
20VLMD-A 25VLMD-A 32VLMD-A 40VLMD-A 50VLMD-A 63VLMD-A
80VLMD-A 100VLMD-A 125VLMD-A
20VML-A / VMM-A 25VML-A / VMM-A 32VML-A / VMM-A 40VMH-A / VMM-A 50VMH-A / VMM-A 63VMH-A / VMM-A 71VMH-A / VMM-A
80VMH-A / VMM-A 100VMH-A / VMM-A 125VMH-A / VMM-A
20VM-A 25VM-A 32VM-A 40VM-A 50VM-A 63VM-A 71VM-A
80VM-A 100VM-A 125VM-A
20VAM-A 25VAM-A 32VGM-A 40VGM-A 50VGM-A 63VFM-A
– –
100VFM-A
20VLEM-A 25VLEM-A 32VLEM-A 40VLEM-A 50VLEM-A 63VLEM-A
– – – –
20VLRM-A 25VLRM-A 32VLRM-A 40VLRM-A 50VLRM-A 63VLRM-A
– – – –
– – –
40VGM-A
63VGM-A
– 100VGM-A 125VGM-A
PLFY-P PLFY-P PEFY-P PDFY-P PKFY-P PCFY-P PFFY-P PFFY-P
Capacity
Model
Cassette Ceiling
4-way flow 2-way flow
20VBM-A 25VBM-A 32VBM-A 40VBM-A
– – – – – –
PMFY-P
1-way flow
Ceiling
Concealed
Ceiling mounted
built-in
Ceiling
Suspended
Wall Mounted
Floor standing
Exposed Concealed
Remote
controller
Name
Model number
Functions
M-NET remote controller
PAR-F27MEA-E
• A handy remote controller for use in conjunction with the Melans centralized management system.
• Addresses must be set.
• Addresses setting is not necessary.
Only the indoor unit for MA remote controller
(the end of model name is -A) can be used.
MA remote controller
PAR-20MAA-E
3-1. UNIT CONSTRUCTION
Outdoor unit
5HP
PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA
1
Indoor unit that can be connected
Branching pipe components
Capacity
Number of units
Total system wide capacity
CMY-Y62-C-E CMY-Y64-C CMY-Y68
Branch header
(2 branches)
Decorative panel
Type 20~Type 125
1~8 units
50~130% of outdoor unit capacity
Branch header
(4 branches)
Branch header
(8 branches)
CMY-S65
Multi distribution
Piping on outdoor
unit
(5 branches)
5
3-2. UNIT SPECIFICATIONS
P L F Y - P 80 V AM - A PU M Y - P 125 V M A
PAC type
AM KM M KM LMD
Frequency conversion controller
Refrigerant R407C/R22 commonness
Refrigerant R407C
NEW frequency converter one-to-many air conditioners (flexible design type)
Indicates equivalent to Cooling capacity
Indicates equivalent to Cooling capacity
Power supply V: Single phase 220-230-240V 50Hz 220V 60Hz
Power supply V: Single phase 220-230-240V 50Hz
Y: 3-phase 380-400-415V 50Hz 380V 60Hz
L : Ceiling cassette K : Wall-mounted type E : Hidden skylight type C: Ceiling suspended type M: Ceiling cassette type F : Floor standing type
}
M-NET control
M-NET control
MA control
Sub-number
Frequency conversion controller
Outdoor unit
MULTI-S
Service Ref.
w
PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA1
Capacity
Cooling (kW) Heating (kW)
14.0
16.0
3.5Motor for compressor (kW)
Cooling W.B. 15~24°C D.B. -5~46°C
Heating D.B. 15~27°C W.B. -15~15.5°C
Indoor-side intake air temperature Outdoor-side intake air temperature
(1) Outdoor Unit
Cooling / Heating capacity indicates the maximum value at operation under the following condition.
w. Cooling Indoor : D.B. 27°C / W.B. 19.0°C
Outdoor : D.B. 35°C
Heating Indoor : D.B. 20°C
Outdoor : D.B. 7°C / W.B. 6°C
(2) Method for identifying MULTI-S model
Indoor unit < When using Model 80 >
Outdoor unit <When using model 125 >
(3) Operating temperature range
Notes D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
6
3-3. SYSTEM LAYOUT
A
B
a
indoor
1
C
b
indoor
2
D
c
indoor
3
e
d
indoor
4
indoor
5
First branch
(branching connector)
Outdoor unit
125
80 40 40
Outdoor unit
Indoor unit
Type 20 ~ Type 125
PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA
1
1~8 units
63~163
Indoor unit that can connected Available capacity of indoor unit Total capacity of units that can be included system
(50-130% of outdoor unit capacity)
3-3-1. System layout
One outdoor unit using branching connectors can be connected to a maximum of eight indoor units.
Examples of a branching method
3-3-2. Notes on the connection of indoor and outdoor units
Note: When the total capacity of indoor units exceeds the capacity of the outdoor unit (more than 100%), the rated power of
each indoor unit will be less when they are running simultaneously.
3-3-3. Capacity for outdoor unit
(1) Branching pipe
Model
CMY-Y62C-E
Branching connector
(2) Examples of System Construction (All models)
PIping method
Indoor units
CMY-Y64-C CMY-Y68 CMY-S65
Outdoor unit
NUMBER OF BRANCHING POINTS
2 4 8 5
Total capacity of
indoor units.
160
7
4 SPECIFICATIONS
PUMY-P125VMA
14.0
6.10
28.3-27.1-26.0 98 17
16.0
6.03
28.0-26.7-25.7 98 17
Single phase 220-230-240V 50Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 1020 o 350 (+30)
Crossover fin
EEV48FAM
Fully enclosed type o 1
Frequency converter start
3.5
Cooling 27-100% Heating 25-100%
1.9 (104Hz) —
1.4 (MEL32)
Propeller (direct) o 2
90(3,177)
60 o 2
Reverse cycle
High pressure pressure sensor (3.0MPa)
Thermal switch Thermal switch
Overheating, excessive current protection
54
127(280)
19.05
9.52
R407C o 8.5
Expansion valve
Item
Service Ref.
Unit
Standard performance
Heating Cooling
Rated Cooling capacity Rated power consumption Operating current Operating power factor Starting current Rated Heating capacity Rated power consumption Operating current Operating power factor Starting current Rated power supply
Type o charge amount Control method
External finish (Munsell colour-coded markings) Dimensions H o W o D (Note 1) Heat exchanger type
Defrost method Pressure gauge
Noise level Weight
Refrigerant pipe size
Refrigerant
Model Type o quantity Starting method Motor output Capacity control Daily cooling capacity Heater <crankcase> Refrigerating oil (Model) Type o quantity Airflow Motor output
High pressure protection Compressor protection Blower protection Frequency converter circuit
Compressor
Protection
devices
Gas Liquid
Fan
kW kW
A %
A kW kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min(CFM)
W
dB
kg(lbs)
[ mm [ mm
kg
Note 1: External dimensions in parentheses indicate the dimensions of protruding parts. Note 2: Rating conditions (JIS B 8616) Cooling : Indoor : D.B. 27: W.B. 19:
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 20:
: Outdoor : D.B. 7: W.B. 6:
8
Item
Rated Cooling capacity Rated power consumption Operating current Operating power factor Starting current Rated Heating capacity Rated power consumption Operating current Operating power factor
Standard performance
External finish (Munsell colour-coded markings) Dimensions H o W o D (Note 1) Heat exchanger type
Fan
Defrost method Pressure gauge
Protection
Noise level Weight
Refrigerant pipe size
Refrigerant Note 1: External dimensions in parentheses indicate the dimensions of protruding parts.
Note 2: Rating conditions (JIS B 8616) Cooling : Indoor : D.B. 27: W.B. 19:
Heating Cooling
Starting current Rated power supply
Model Type o quantity Starting method Motor output Capacity control Daily cooling capacity
Compressor
Heater <crankcase> Refrigerating oil (Model) Type o quantity Airflow Motor output
High pressure protection Compressor protection Blower protection
devices
Frequency converter circuit
Type o charge amount Control method
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 20:
: Outdoor : D.B. 7: W.B. 6:
Service Ref.
Gas Liquid
Unit
kW kW
A %
A kW kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min(CFM)
W
dB
kg(lbs)
[ mm [ mm
kg
3 phase 380-400-415V 50Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 1020 o 350 (+30)
Fully enclosed type o 1
Frequency converter start
Cooling 27-100% Heating 25-100%
Propeller (direct) o 2
High pressure pressure sensor (3.0MPa)
Overheating, excessive current protection
PUMY-P125YMA PUMY-P125YMA
14.0
5.95
9.6-9.1-8.8 94
8.0
16.0
5.58
9.2-8.8-8.5 92
8.0
Crossover fin
EEV48FAK
3.5
1.9 (104Hz) —
1.4 (MEL32)
90(3,177)
60 o 2
Reverse cycle
Thermal switch Thermal switch
54
127(280)
19.05
9.52
R407C o 8.5
Expansion valve
1
9
5 DATA
Model 20
Model Number for indoor unit
Model Capacity
kW
22
Model 2528Model 3236Model 4045Model 5056Model 6371Model 7180Model 8090Model 100
112
Model 125
140
5-1. COOLING AND HEATING CAPACITYAND CHARACTERISTICS
5-1-1. Method for obtaining system cooling and heating capacity:
To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings of all the indoor units connected to the outdoor unit (see table below), and then use this total to find the standard capacity with the help of the tables on page 11 to 14.
(1) Capacity of indoor unit
(2) Sample calculation
1 System assembled from indoor and outdoor unit (in this example the total capacity of the indoor units is greater than that of the outdoor unit)
• Outdoor unit PUMY-P125YMA
• Indoor unit PKFY-P25VAM-A o 2 , PLFY-P50VLMD-A o 2 2 According to the conditions in 1 , the total capacity of the indoor unit will be: 28 o 2 + 56 o 2 = 168
Capacity (kW)
Cooling
14.60
AB
Heating
16.33
Outdoor unit power consumption (kW)
Cooling
6.04
Heating
5.14
Outdoor unit current (A)
Cooling
8.9
Heating
7.8
5-1-2. Method for obtaining the heating and cooling capacity of an indoor unit:
(1) The capacity of each indoor unit (kW) = the capacity A (or B ) o
(2) Sample calculation (using the system described above in 4-1-1. (2) ):
During cooling: During heating:
• The total model capacity of the indoor unit is:
2.8 o 2 + 5.6 o 2=16.8kW Therefore, the capacity of PKFY-P25VAM-A and PLFY-P50VLMD-A will be calculated as follows by using the formula in 4-1-2. (1):
Model 25=14.6 o = 2.43kW
Model 50=14.6 o = 4.87kW
2.8
16.8
5.6
16.8
total model capacity of all indoor units
• The total model capacity of indoor unit is:
3.2 o 2 + 6.3 o 2=19.0 Therefore, the capacity of PKFY-P25VAM-A and PLFY­P50VLMD-A will be calculated as follows by using the formula in 4-1-2. (1):
Model 25=16.33 o = 2.75kW
Model 50=16.33 o = 5.41kW
model capacity
3.2
19.0
6.3
19.0
10
5-2. STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units (kW)
Capacity (kW)
Power consumption (kW) Current (A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
2.58
2.61
2.65
2.69
2.73
2.76
2.80
2.84
2.88
2.92
2.96
3.00
3.04
3.08
3.12
3.16
3.20
3.25
3.29
3.33
3.38
3.42
3.47
3.51
3.56
3.60
3.65
3.69
3.74
3.79
3.84
3.89
3.93
3.98
4.03
4.08
4.13
4.19
4.24
4.29
4.34
4.39
4.45
4.50
4.55
4.61
4.66
4.72
4.77
4.83
4.89
4.94
5.00
5.06
5.12
5.17
2.86
2.89
2.93
2.97
3.01
3.04
3.08
3.12
3.16
3.20
3.23
3.27
3.31
3.35
3.39
3.43
3.47
3.51
3.55
3.59
3.64
3.68
3.72
3.76
3.80
3.85
3.89
3.93
3.98
4.02
4.06
4.11
4.15
4.20
4.24
4.29
4.33
4.38
4.42
4.47
4.52
4.56
4.61
4.66
4.70
4.75
4.80
4.85
4.90
4.94
4.99
5.04
5.09
5.14
5.19
5.24
11.0
11.1
11.3
11.5
11.6
11.8
11.9
12.1
12.3
12.4
12.6
12.8
12.9
13.1
13.3
13.5
13.6
13.8
14.0
14.2
14.4
14.6
14.8
15.0
15.1
15.3
15.5
15.7
15.9
16.1
16.3
16.6
16.8
17.0
17.2
17.4
17.6
17.8
18.0
18.3
18.5
18.7
18.9
19.2
19.4
19.6
19.9
20.1
20.3
20.6
20.8
21.1
21.3
21.5
21.8
22.0
12.2
12.3
12.5
12.6
12.8
13.0
13.1
13.3
13.5
13.6
13.8
13.9
14.1
14.3
14.5
14.6
14.8
15.0
15.1
15.3
15.5
15.7
15.8
16.0
16.2
16.4
16.6
16.8
16.9
17.1
17.3
17.5
17.7
17.9
18.1
18.3
18.5
18.6
18.8
19.0
19.2
19.4
19.6
19.8
20.0
20.2
20.4
20.7
20.9
21.1
21.3
21.5
21.7
21.9
22.1
22.3
70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98
99 100 101 102 103 104 105 106 107 108 109
110 111 112 113 114 115 116 117 118
119 120 121 122 123 124 125
7.00
7.10
7.20
7.30
7.40
7.50
7.60
7.70
7.80
7.90
8.00
8.10
8.20
8.30
8.40
8.50
8.60
8.70
8.80
8.90
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.20
10.30
10.40
10.50
10.60
10.70
10.80
10.90
11.00
11.10
11.20
11.30
11.40
11.50
11.60
11.70
11.80
11.90
12.00
12.10
12.20
12.30
12.40
12.50
7.88
8.00
8.11
8.22
8.33
8.44
8.56
8.67
8.78
8.89
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.22
10.33
10.45
10.56
10.67
10.79
10.90
11.02
11.13
11.24
11.36
11.47
11.59
11.70
11.81
11.93
12.04
12.16
12.27
12.38
12.50
12.63
12.75
12.88
13.00
13.13
13.25
13.38
13.50
13.63
13.75
13.88
14.00
14.13
w
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the formula on page 8.
240V, 50Hz
5-2-1. PUMY-P125VMA STANDARD CAPACITY DIAGRAM
11
5-2-2. PUMY-P125VMA STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units (kW)
Capacity (kW)
Power consumption (kW) Current (A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
5.23
5.29
5.35
5.41
5.47
5.53
5.59
5.66
5.72
5.78
5.84
5.91
5.97
6.04
6.10
6.11
6.11
6.11
6.12
6.12
6.12
6.13
6.13
6.13
6.14
6.14
6.14
6.15
6.15
6.15
6.15
6.16
6.16
6.16
6.17
6.17
6.17
6.18
6.18
6.18
6.19
6.19
6.19
6.20
6.20
6.20
6.21
6.21
6.21
6.22
6.22
6.22
6.22
6.23
6.23
6.23
6.24
5.29
5.34
5.39
5.45
5.50
5.55
5.60
5.65
5.71
5.76
5.81
5.87
5.92
5.97
6.03
6.02
6.00
5.98
5.96
5.95
5.93
5.91
5.90
5.88
5.86
5.85
5.83
5.81
5.79
5.78
5.76
5.74
5.73
5.71
5.69
5.68
5.66
5.64
5.62
5.61
5.59
5.57
5.56
5.54
5.52
5.51
5.49
5.47
5.46
5.44
5.42
5.40
5.39
5.37
5.35
5.34
5.32
22.3
22.5
22.8
23.1
23.3
23.6
23.8
24.1
24.4
24.6
24.9
25.2
25.4
25.7
26.0
26.0
26.0
26.0
26.1
26.1
26.1
26.1
26.1
26.1
26.1
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.3
26.3
26.3
26.3
26.3
26.3
26.3
26.4
26.4
26.4
26.4
26.4
26.4
26.4
26.5
26.5
26.5
26.5
26.5
26.5
26.5
26.5
26.6
26.6
22.6
22.8
23.0
23.2
23.4
23.6
23.9
24.1
24.3
24.5
24.8
25.0
25.2
25.4
25.7
25.6
25.6
25.5
25.4
25.3
25.3
25.2
25.1
25.0
25.0
24.9
24.8
24.8
24.7
24.6
24.5
24.5
24.4
24.3
24.3
24.2
24.1
24.0
24.0
23.9
23.8
23.7
23.7
23.6
23.5
23.5
23.4
23.3
23.2
23.2
23.1
23.0
23.0
22.9
22.8
22.7
22.7
126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182
12.60
12.70
12.80
12.90
13.00
13.10
13.20
13.30
13.40
13.50
13.60
13.70
13.80
13.90
14.00
14.02
14.04
14.06
14.08
14.10
14.12
14.15
14.17
14.19
14.21
14.23
14.25
14.27
14.30
14.32
14.34
14.36
14.38
14.40
14.42
14.45
14.47
14.49
14.51
14.53
14.55
14.57
14.60
14.62
14.64
14.66
14.68
14.70
14.72
14.75
14.77
14.79
14.81
14.83
14.85
14.87
14.89
14.25
14.38
14.50
14.63
14.75
14.88
15.00
15.13
15.25
15.38
15.50
15.63
15.75
15.88
16.00
16.01
16.02
16.03
16.04
16.06
16.07
16.08
16.09
16.10
16.12
16.13
16.14
16.15
16.16
16.17
16.19
16.20
16.21
16.22
16.23
16.25
16.26
16.27
16.28
16.29
16.31
16.32
16.33
16.34
16.35
16.36
16.38
16.39
16.40
16.41
16.42
16.44
16.45
16.46
16.47
16.48
16.50
w
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the formula on page 8.
240V, 50Hzw
12
5-2-3. PUMY-P125YMA, PUMY-P125YMA1 STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units (kW)
Capacity (kW)
Power consumption (kW) Current (A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
2.47
2.50
2.54
2.57
2.61
2.64
2.68
2.72
2.76
2.80
2.83
2.87
2.91
2.95
2.99
3.03
3.07
3.12
3.16
3.20
3.24
3.29
3.33
3.37
3.42
3.46
3.51
3.55
3.60
3.65
3.69
3.74
3.79
3.84
3.88
3.93
3.98
4.03
4.08
4.13
4.18
4.24
4.29
4.34
4.39
4.44
4.50
4.55
4.61
4.66
4.72
4.77
4.83
4.88
4.94
5.00
2.63
2.66
2.70
2.73
2.77
2.80
2.84
2.87
2.91
2.94
2.98
3.02
3.05
3.09
3.13
3.16
3.20
3.24
3.27
3.31
3.35
3.39
3.43
3.47
3.51
3.55
3.59
3.62
3.67
3.71
3.75
3.79
3.83
3.87
3.91
3.95
3.99
4.04
4.08
4.12
4.16
4.21
4.25
4.30
4.34
4.38
4.43
4.47
4.52
4.56
4.61
4.65
4.70
4.74
4.79
4.84
3.8
3.9
3.9
4.0
4.0
4.1
4.1
4.2
4.2
4.3
4.3
4.4
4.4
4.5
4.6
4.6
4.7
4.8
4.8
4.9
5.0
5.0
5.1
5.2
5.2
5.2
5.3
5.4
5.4
5.5
5.6
5.7
5.7
5.8
5.9
5.9
6.0
6.1
6.2
6.2
6.3
6.3
6.4
6.5
6.6
6.6
6.7
6.8
6.9
7.0
7.1
7.1
7.2
7.3
7.4
7.5
4.2
4.2
4.3
4.3
4.4
4.4
4.5
4.5
4.5
4.6
4.7
4.7
4.8
4.8
4.9
4.9
5.0
5.1
5.1
5.2
5.2
5.3
5.4
5.4
5.5
5.5
5.5
5.6
5.7
5.7
5.8
5.9
5.9
6.0
6.0
6.1
6.2
6.2
6.3
6.4
6.4
6.4
6.5
6.6
6.6
6.7
6.8
6.8
6.9
7.0
7.0
7.1
7.2
7.2
7.3
7.4
70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98
99 100 101 102 103 104 105 106 107 108 109 110
111 112 113 114 115 116 117 118 119 120 121 122 123 124 125
7.00
7.10
7.20
7.30
7.40
7.50
7.60
7.70
7.80
7.90
8.00
8.10
8.20
8.30
8.40
8.50
8.60
8.70
8.80
8.90
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.20
10.30
10.40
10.50
10.60
10.70
10.80
10.90
11.00
11.10
11.20
11.30
11.40
11.50
11.60
11.70
11.80
11.90
12.00
12.10
12.20
12.30
12.40
12.50
7.88
8.00
8.11
8.22
8.33
8.44
8.56
8.67
8.78
8.89
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.22
10.33
10.45
10.56
10.67
10.79
10.90
11.02
11.13
11.24
11.36
11.47
11.59
11.70
11.81
11.93
12.04
12.16
12.27
12.38
12.50
12.63
12.75
12.88
13.00
13.13
13.25
13.38
13.50
13.63
13.75
13.88
14.00
14.13
w
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the formula on page 8.
415V, 50Hz
13
5-2-4. PUMY-P125YMA, PUMY-P125YMA1 STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units (kW)
Capacity (kW)
Power consumption (kW) Current (A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
5.05
5.11
5.17
5.23
5.29
5.35
5.41
5.47
5.53
5.59
5.65
5.71
5.77
5.84
5.95
5.96
5.96
5.96
5.97
5.97
5.97
5.98
5.98
5.98
5.99
5.99
5.99
5.99
6.00
6.00
6.00
6.01
6.01
6.01
6.02
6.02
6.02
6.03
6.03
6.03
6.03
6.04
6.04
6.04
6.05
6.05
6.05
6.06
6.06
6.06
6.07
6.07
6.07
6.07
6.08
6.08
6.08
4.88
4.93
4.98
5.03
5.07
5.12
5.17
5.22
5.27
5.32
5.36
5.41
5.46
5.51
5.58
5.57
5.55
5.53
5.52
5.50
5.49
5.47
5.46
5.44
5.43
5.41
5.39
5.38
5.36
5.35
5.33
5.32
5.30
5.28
5.27
5.25
5.24
5.22
5.21
5.19
5.17
5.16
5.14
5.13
5.11
5.10
5.08
5.06
5.05
5.03
5.02
5.00
4.99
4.97
4.95
4.94
4.92
7.6
7.6
7.7
7.7
7.8
7.9
8.0
8.1
8.2
8.3
8.4
8.5
8.5
8.6
8.8
8.8
8.8
8.8
8.8
8.8
8.8
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
7.5
7.5
7.5
7.6
7.7
7.7
7.8
7.9
8.0
8.0
8.1
8.2
8.3
8.3
8.4
8.4
8.4
8.4
8.3
8.3
8.3
8.3
8.3
8.2
8.2
8.2
8.2
8.1
8.1
8.1
8.1
8.0
8.0
8.0
8.0
7.9
7.9
7.9
7.9
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.7
7.7
7.7
7.7
7.6
7.6
7.6
7.6
7.6
7.5
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
12.60
12.70
12.80
12.90
13.00
13.10
13.20
13.30
13.40
13.50
13.60
13.70
13.80
13.90
14.00
14.02
14.04
14.06
14.08
14.10
14.12
14.15
14.17
14.19
14.21
14.23
14.25
14.27
14.30
14.32
14.34
14.36
14.38
14.40
14.42
14.45
14.47
14.49
14.51
14.53
14.55
14.57
14.60
14.62
14.64
14.66
14.68
14.70
14.72
14.75
14.77
14.79
14.81
14.83
14.85
14.87
14.89
14.25
14.38
14.50
14.63
14.75
14.88
15.00
15.13
15.25
15.38
15.50
15.63
15.75
15.88
16.00
16.01
16.02
16.03
16.04
16.06
16.07
16.08
16.09
16.10
16.12
16.13
16.14
16.15
16.16
16.17
16.19
16.20
16.21
16.22
16.23
16.25
16.26
16.27
16.28
16.29
16.31
16.32
16.33
16.34
16.35
16.36
16.38
16.39
16.40
16.41
16.42
16.44
16.45
16.46
16.47
16.48
16.50
w
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the formula on page 8.
415V, 50Hzw
14
5-3. CORRECTING COOLING AND HEATING CAPACITY
Service Ref. PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA1
Rated cooling capacity Rated heating capacity
Indoor D.B. 27°C / W.B. 19°C Outdoor D.B. 35°C
Indoor D.B. 20°C Outdoor D.B. 7°C / W.B. 6°C
0.4
-5 0 10 20 30 40 46
0.6
0.8
1.0
1.2
1.4
0.6
0.8
1.0
1.2
1.4
22 20 18 16
22
20 18 16
0.4
-12 -10 0 105-5 15
0.6
0.8
1.0
1.2
1.4
0.6
0.8
1.0
1.2
1.4
15 20
25
20 15
25
5-3-1. Correcting Changes in Air Conditions
(1)The performance curve charts (Figure 1, 2) show the rated capacity (total capacity) under the stated conditions when standard
length for piping (5m) is used. The rated power is derived from the capacity ratio and power ratio obtained for the indoor and outdoor intake temperatures at time 1.
• Standard conditions:
• Use the rated capacity and rated power values given in the characteristics table for each indoor unit.
• The capacity is the single value on the side of the outdoor unit; the capacity on the sides of each indoor unit must be added to obtain the total capacity.
(2)The capacity of each indoor unit may be obtained by multiplying the total capacity obtained in (1) by the ratio between the
individual capacity at the rated time and the total capacity at the rated time.
Individual capacity under stated conditions = total capacity under the stated conditions o
(3)Capacity correction factor curve
individual capacity at the rated time
total capacity at the rated time
Figure 1. PUMY-P125VMA PUMY-P125YMA
PUMY-P125YMA
Cooling performance curve
Cooling Capacity (ratio)
Cooling Power consumption (ratio)
Outdoor <D.B. ::>
1
INDOOR <W.B. :>
INDOOR <W.B. :>
Figure 2. PUMY-P125VMA PUMY-P125YMA
PUMY-P125YMA
Heating performance curve
Heating Capacity (ratio)
Heating Power consumption (ratio)
Outdoor <W.B. ::>
1
INDOOR <D.B. :>
INDOOR <D.B. :>
15
5-3-2. Correcting Capacity for Changes in the Length of Refrigerant Piping
1.0
0.95
0.9 5 10152025303540455055
1.0
63 (50%) 94 (75%)
125 (100%) 163 (130%)
0.95
0.9
0.85
0.8 5 10152025303540455055
(1) During cooling, to obtain the ratio (and the equivalent piping length) of the outdoor units rated capacity and the total
in-use indoor capacity, first find the capacity ratio corresponding to the standard piping length (5m) from Figures 3 at first, and then multiply by the cooling capacity from Figure 1 to obtain the actual capacity.
(2) During heating, to find the equivalent piping length, first find the capacity ratio corresponding to standard piping length (5m)
from Figure 4, and then multiply by the heating capacity from Figure 2 to obtain the actual capacity.
(1) Cooling capacity correction factor Figure 3. PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA1
Cooling capacity correction curve
Total capacity for indoor unit
Cooling Capacity (ratio)
piping length (m)
(2) Heating capacity correction factor Figure 4. PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA1
Heating capacity correction curve
Heating Capacity (ratio)
piping length (m)
(3) Method for Obtaining the Equivalent Piping Length
Equivalent length for type 125 = (length of piping to farthest indoor unit) + (0.35 o number of bends in the piping) (m)
Length of piping to farthest indoor unit: type 125.....70m
5-3-3. Correction of Heating Capacity for Frost and Defrosting
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature (W.B.°C)
Correction factor
6
1.0
4
0.98
2
0.89
0.88
16
0
-2
0.89
-4
0.9
-6
0.95
-8
0.95
-10
0.95
PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA
90
80
SPL(dB) LINE
NOTCH
Hi 54
1
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
NC-20
MICROPHONE
1m
1m
17
6 OUTLINES AND DIMENSIONS
• OUTDOOR UNITS PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA1
Optional parts
(base branching
pipe) installation
hole
Terminal block for transmission
Terminal block for central control
Terminal block for power source
Liquid refrigerant pipe
connection {9.52 (3/8F)
Gas refrigerant-pipe
connection {19.05 (3/4F)
Knock out hole for right piping
Knock out holes for
power line 2-{27
Knock out holes for power line 2-{29
unit : mm
shaped notched holes
(standard bolt M10)
Bottom piping hole
Air intake
Air outlet
Handle for
Optional parts
installation hole
Rear air intake
Side air intake
Handle for moving
moving
Knock out hole for
front piping
Oval holes
Piping cover
Rear piping hole
(standard bolt M10)
Drain hole
(3-{33 hole)
18
when a piping cover is used for aesthetic reasons.
1...Indicates the dimensions of the cutoff valve connector.
2...Make sure that the panel can be easily removed for maintenance
7 WIRING DIAGRAM
PUMY-P125VMA
SYMBOL
TB1 Terminal Block(Power Supply)
Terminal Block(Transmission)TB3 4-Way Valve21S4
Terminal Block(Centralized Control)
TB7 CE
Smoothing Capacitor
C1,C2
Fan Motor Capacitor
DCL1~4
Reactor Resistor(Rush Current Protection)
RS ACTM Active Filter Module
Thermistor(Discharge Temperature Detection)
TH1 TH2
Thermistor (Low Pressure Saturated Temp.Detection)
TH5
Thermistor (Pipe Temp.Detection / Judging Defrost)
Thermistor(Outdoor Temp.Detection)
TH6 THHS A/B
Thermistor(Radiator Panel) A;ACTM,B;IGBT
63HS
High Pressuer Sensor
(Discharge Pressure Detection)
Thermal Switch(Compressor)49C
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
NO FUSE BREAKER 32A
POWER SUPPLY ~ / N 220-230-240V
NAME
L N
SYMBOL
SV LEV(A) Expansion Valve
MF1,MF2
MC
P.B. Power Circuit Board
U/V/W CN2~6 CNDC CNAF IGBT LED1
SC-S,R
SC-P1,P2 SC-N1,N2
*1 The address automatically becomes "100" if it is
TB3
set as "01~50".
BRN
M1
BRN
M2
S
TB7
ORN
M1
ORN
M2
S
TB1
L N
Magnetic Contactor52C
NAME
Solenoide Valve(Hot Gas Bypass)
Fan Motor(Inner Thermostat) Compressor(Inner Thermostat)
Connection Terminal(U/V/W Phase)
Connector Connector Connector Converter,Inverter Light Emitting Diode(Inverter Control Status)
Screw Type Terminal(L./N-Phase) Screw Type Terminal(DC Voltage) Screw Type Terminal(DC Voltage)
< M.B.>
TH2
TH5
TH6
TH1
63HS
LEV
65432 LEV-A (WHT)
CNS1
2
(RED)
1
CNS2
2
(YLW)
1
TH2
2
(WHT)
1
TH5
2
(GRN)
1
TH6
2
(RED)
1
TH1
2
(WHT)
1 3
63HS
2
(WHT)
1
(WHT)
SYMBOL
Noise Filter Circuit BoardN.F.
LI/LO
Connection Lead(L-Phase)
NI/NO
Connection Lead(N-Phase) Connection Terminal(Ground)
EI
CNAC2
Connector Connector
CN5
Multi Circuit BoardM.B.
F1,F2
Fuse(6.3A)
SW1 Switch(Display Selection)
Switch(Function Selection)
SW2
Switch(Test Run)
SW3
Switch(Model Selection)
SW4
Switch(Function Selection)
SW5
SW5-1 Auto Change Over OFF;disabled ON;enabled
Switch(Function Selection)SW6 Switch(Unit Address Selection,1st digit)
SWU1
Switch(Unit Address Selection,2nd digit)
SWU2
49C
6
YLW YLW
1
31
49C(GRY)
0
1
9
*1
8
7
6
5
SWU2 SWU1
ON
OFF
1
ON
OFF
12345678910
CN4
CNDC(PNK)
1
2
321
CN3S(WHT)
LED2LED1
0
1
9
2
2
8
3
3
7
4
4
6
5
(1st digit)(2nd digit)
SW1
ON
OFF
3456782 1 3456782
SW2
CN2 (WHT)
131432 567
CN51
(WHT)
ON
OFF
OFF
NAME
321
CN3D(WHT)
1 2 3 4 5
SW4
SW5
SW3
ON
21
7
WHT WHT
MF2
(WHT)
3.12V
4.COMP. ON
5.Error
1234 1234
4321
SW6
ON
OFF
1 3456782
SYMBOL
Connector(Multi system)
CNS1
Connector(Centralized Control)
CNS2
Connector
CN4
Connector(Centralized Control Power Supply)
CN40 CN41
Connector(For String Jumper Connector)
CN51
Connector(Connected for Option)
Compressor drive signal,Error signal
CN3D
Connector(Connected for Option) Auto Change Over Signal
CN3S
Connector(Connected for Option) Demand Signal
Relay(Magnetic Contactor)
X500
Relay(4-Way Valve)
X501
Relay(Solenoid Valve)
X502
Digital Indication LED
LED1,2
Operation Inspection Indication
RED
C2
MF2
ORN
BLU
WHT
31
BLU
WHT
13 13
F.C
CN40(WHT)CN41(WHT)
F1
(6.3A) (6.3A)
MF1
RED ORN
BLU
31
BLU
MF1
(WHT)
X500
21S4(GRN)
X501
X502
F2
CNAC
31
(RED)
NAME
C2
52C(ORG)
1 3
1 3
SV(BLK)
1 3
CH(BLU)
1 3
YLW YLW
BLU BLU
BLK BLK
52C
21S4
SV1
W V U
LED1
< P.B.>
BLK WHT RED
Always lit---SV121S4
MC
CE
+
21
31
CN5
(RED)
LI
NI
< N.F.>
NOTES: 1. Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2. Symbols used in wiring diagram above are. :Terminal block, :Connector, :Insertion tab.
3. Self-diagnosis function The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LED1,2 (LED indication)found on the multi-controller of the outdoor unit. LED indication : Set all contacts of SW1 to OFF.
4. For the system utilizing R-converter units(PAC-SF29LB),the following functions are not available. SW3;TEST RUN SW5-1;AUTO CHANGE OVER CN3D;AUTO CHANGE OVER(external singnal)
5. The input for CN3D 1-2(AUTO CHANGE OVER EXTERNAL SIGNEL)is as follows. Short;heating Open;Cooling(It differs from Service ref.PUMY-P125YMA)
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
Bit
Indication
•When fault requiring inspection has occurred The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.
CNAC2 (RED)
LO
NO
EI
1 876543
Compressor operated
2
52C
THHS_A
THHS_B
RS
52C
2 1
2 1
2 1
2 1
CN4
(WHT)
CN3
(WHT)
CN6
(WHT)
CN5
(RED)
SCR-N1
SCR-P1
13
IGBT
CNDC
(PNK)
+
-
­+
+
51234
CNAF (WHT)
743215
66 CN2 (WHT)
SCR-S
SCR-R
SCR-P2 SCR-N2
L2
652341
P
N1 N2
I
ACTM
(Example) When the compressor and SV1 are turned during cooling operation.
78563421
DCL3DCL4
DCL1DCL2
L1
+
-
19
PUMY-P125YMA
9
8
7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
RD2
123 CN3S (RED)
CN3S CONNECTOR <DEMAND SIGNAL>
operated
NOTES : 1. Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2. Symbols used in wiring diagram above are. : Terminal block, : Connector, :Insertion tab.
3. Self-diagnosis function The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch (SW1) and LD1(LED indication) found on the multi-controller of the outdoor unit. LED indication : Set all contacts of SW1 to OFF.
7
8
5
634
2
1
(Example) When the compressor and SV1 are turned during cooling operation.
Always lit---SV121S4
1 876543
52C
2
Compressor
Indication
Bit
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
•When fault requiring inspection has occurred The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.
NO FUSE BREAKER 25A
L1 L2 L3
N
X
X
1
1
(WHT)
CN3D
(WHT)
CN51
(WHT)
CN41
(WHT)
CN40
5321432143214321
YLW
CB2
CB1
CNR
(WHT)
CNR
(WHT)
(RED)
CNA
<POWER SUPPLY BOARD>
(YLW)
49C
(RED)
CN1
FUSE1 (6.3A)
FUSE2 (2A)
SLEV
6
1
2
5764
49C
YLW
31 1234567
1234567
123671234561236
123671236
CN4CN3CN2
CN4CN3CN2
(YLW)(YLW) (WHT)
(YLW)(RED) (YLW) (WHT)
24321 12345678
109876543212876543
SW3 SW5
OFF
ON
OFF
ON
SW4
SW1 SW2
OFF
ON
1
1
ON OFF
ON OFF
(YLW)
ACCT
654321
132
CN1
3
63HS
654132123113 2121
THHS
TH1TH2TH5TH6
63HS
THHS
TH2TH6 TH5 TH1
(BLK) (WHT) (GRN)(GRN) (WHT) (WHT)
SLEV
(WHT)
BLU
~
~
~
LO1 LO2 LO3
LI3
E
N
LI2
LI1
(RED)
31
CNA
13
GRN
6
YLW
YLW
WHT
BLK
RS1
RB2 RB1
RD1
BLK
RED
BLU
WHT
GRN
E
P
N
C03
C02C01
NP1PN1
10
3 5 6 8
10
3568
+ –
IPM
WV
-
+
+
-
RED WHT BLK
31 13
31
(BLU) 52C
X71
YLW
YLW
52C
31
(GRN)
21S4
X72
BLU
BLU
21S4
SV1
BLK
BLK
13
(BLK) SV1
(WHT) MF2
(WHT) MF1
MF1
C1
31
WHT
BLU
WHT
BLURED
ORN
RED
ORN
BLU
WHT
31
BLU
52C
N
BLU
L3
BLK
L1
RED
S
M1 M2
S
M2
M1
LD1
SWU1
(1st digit)
SWU2
(2nd digit)(3rd digit)
SWU3
<RESISTOR BOARD>
CNS1
(RED)
CNS2
(YLW)
F.C
2
1
1
GRN/YLW
ZNR
+
+
BLU
BLK
2
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
WHT
BLK
WHT
RED
WHT
ORN
ORN
BRN
BRN
GROUND
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
POWER SUPPLY 3N~ 380/220-415/240V 50Hz
W
V
U
U
X73
TB3
TB7
L2
TB1
MF2
C2
MC
DCL
DM
NF
<MULTI CONTROLLER BOARD>
<IPM RADIATOR PANEL TEMPERATURE DETECTION>
<DISCHARGE TEMPERATURE DETECTION>
<OUTDOOR TEMPERATURE DETECTION>
<LOW PRESSURE SATURATED TEMPERATURE DETECTION>
<PIPE TEMPERATURE DETECTION
• JUDGING DEFROST>
THERMISTOR
SYMBOL
TERMINAL BLOCK <TRANSMISSION>
SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT>
SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT>
SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT>
SWITCH <FUNCTION SELECTION>
SWITCH <MODEL SELECTION>
SWITCH <TEST RUN>
THERMISTOR
NAME
SWITCH <FUNCTION SELECTION>
SWITCH <DISPLAY SELECTION>
TERMINAL BLOCK <CENTRALIZED CONTROL>
SOLENOID VALVE <HOT GAS BYPASS>
TERMINAL BLOCK <POWER SUPPLY>
THERMISTOR
SYMBOL
SMOOTHING CAPACITOR
C03 CAPACITOR <FILTER>
C01,C02
CONNECTOR <DISCHARGE CIRCUIT, POWER SUPPLY>
CNR
RESISTOR <RUSH CURRENT PROTECT>
RS1
RESISTOR <DISCHARGE>
RB1,RB2
RESISTOR <VOLTAGE BALANCE ADJUSTMENT>
RD1,RD2
RELAYX
X73 RELAY <SOLENOID VALVE>
X72 RELAY <4-WAY VALVE>
C1,C2 FAN MOTOR CAPACITOR
SWU3
SWU2
SWU1
SW5
SW4
SW3
THHS
INTELLIGENT POWER MODULEIPM
FAN CONTROLF.C
CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY>
CN40
CONNECTOR <FOR STORING JUMPER CONNECTOR>
CN41
CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT>
CN51
CONNECTOR <INVERTER SIGNAL 5V>
CN4
CONNECTOR <POWER SUPPLY 30V,12V,5V>
CN3
CONNECTOR <POWER SYNC SIGNAL, PROTECTION>
CN2
CONNECTOR <CONTROLLER DRIVE CONTROL>
CN1
CONNECTOR <POWER SUPPLY>CNA
CONNECTOR <CURRENT DETECTION>
ACCT
NAME
SYMBOL
NAME
SW2
SW1
CONNECTOR <AUTO CHANGE OVER SIGNAL>
CN3D
REACTOR
THERMAL SWITCH <COMPRESSOR>
TH2
TH5
TH6
63HS
52C
21S4
TH1
SV1
SLEV
MF1,MF2
LD1 X71
CNS1 CNS2
ZNR
FUSE2
TB7
TB3
TB1
MC
DCL
NF
FUSE1
49C
CONNECTOR <MULTI SYSTEM> CONNECTOR <CENTRALIZED CONTROL>
FUSE (2A)
DIGITAL INDICATION LED <OPERATION INSPECTION INDICATION>
FAN MOTOR <INNER THERMOSTAT>
EXPANSION VALVE
HIGH PRESSURE SENSOR <DISCHARGE PRESSURE DETECTION>
MAGNETIC CONTACTOR
4-WAY VALVE
RELAY <MAGNETIC CONTACTOR>
VARISTOR
FUSE (6.3A)
COMPRESSOR <INNER THERMOSTAT>
NOISE FILTER
THERMISTOR
THERMISTOR
CB1,CB2DMSMOOTHING CAPACITOR
DIODE MODULE
NAME
SYMBOL
20
PUMY-P125YMA1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
9
8
7
6
5
4
3
2
1
0
RD2
123
CN3S
(WHT)
CN3S
CONNECTOR <DEMAND SIGNAL>
operated
NOTES: 1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.Symbols used in wiring diagram above are. :Terminal block, :Connector, :Insertion tab.
3.Self-diagnosis function The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication) found on the multi-controller of the outdoor unit. LED indication : Set all contacts of SW1 to OFF.
4.For the system utilizing R-converter units(PAC-SF29LB), the following functions are not available. SW3 : TEST RUN SW5-1 : AUTO CHANGE OVER CN3D : AUTO CHANGE OVER(external singnal)
5.The input for CN3D 1-2(AUTO CHANGE OVER EXTERNAL SIGNEL)is as follows. Short : heating Open : Cooling(It differs from Service ref. PUMY-P125YMA)
78563421
(Example) When the compressor and SV1 are turned during cooling operation.
Always lit---SV121S4
1 876543
52C
2
Compressor
Indication
Bit
• During normal operation The LED indicates the drive state of the controller in the outdoor unit.
• When fault requiring inspection has occurred The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.
50Hz
380/220-415/240V
3N~
NO FUSE BREAKER 25A
L1 L2 L3
N
X
X
1
1
(WHT)
CN3D
(WHT)
CN51
(WHT)
CN41
(WHT)
CN40
5321432143214321
YLW
CB2
CB1
CNR
(WHT)
CNR
(WHT)(RED)
CNA
<POWER SUPPLY BOARD>
(YLW)
49C
(RED)
CN1
FUSE1 (6.3A)
FUSE2 (2A)
SLEV
6
1
2
5764
49C
YLW
31 1234567
1234567
123671234561236
123671236
CN4CN3CN2
CN4CN3CN2
(YLW)(YLW) (WHT)
(YLW)(RED) (YLW) (WHT)
24321 12345678
109876543212876543
SW3 SW5
OFF
ON
OFF
ON
SW4
SW1 SW2
OFF
ON
1
1
ON OFF
ON OFF
(YLW)
ACCT
654321
132
CN1
3
63HS
654132123113 2121
THHS
TH1TH2TH5TH6
63HS
THHS
TH2TH6 TH5 TH1
(BLK) (WHT) (GRN)(GRN) (WHT) (WHT)
SLEV
(WHT)
BLU
+
~
~
~
LO1 LO2 LO3
LI3
E
N
LI2
LI1
(RED)
31 CNA
13
GRN
6
YLW
YLW
WHT
BLK
RS1
RB2 RB1
RD1
BLK
RED
BLU
WHT
GRN
E
P
N
C03
C02C01
NP1PN1
10
3 5 6 8
10
3568
+
-
IPM
WV
-
+
+
-
RED WHT BLK
31 13
31
(BLU) 52C
X71
YLW
YLW
52C
31
(GRN)
21S4
X72
BLU
BLU
21S4
SV1
BLK
BLK
13
(BLK)
SV1
(WHT)
MF2
(WHT)
MF1
MF1
C1
31
WHT
BLU
WHT
BLURED
ORN
RED
ORN
BLU
WHT
31
BLU
52C
N
BLU
L3
BLK
L1
RED
S
M1
M2
S
M2
M1
LD1
SWU1
(1st digit)
SWU2
(2nd digit)(3rd digit)
SWU3
<RESISTOR BOARD>
CNS1
(RED)
CNS2
(YLW)
F.C
2
1
1
GRN/YLW
ZNR
-
+
BLU
BLK
2
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
WHT
BLK
WHT
RED
WHT
ORN
ORN
BRN
BRN
GROUND
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
POWER SUPPLY
W
V
U
U
X73
TB3
TB7
L2
TB1
MF2
C2
MC
DCL
DM
NF
<MULTI CONTROLLER BOARD>
<IPM RADIATOR PANEL TEMP. DETECTION>
<DISCHARGE TEMP. DETECTION>
<OUTDOOR TEMP. DETECTION>
THERMISTOR
<LOW PRESSURE SATURATED TEMP. DETECTION>
TERMINAL BLOCK <TRANSMISSION>
SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT>
SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT>
SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT>
SWITCH <FUNCTION SELECTION> SW5-1 AUTO CHANGE OVER OFF : disabled ON : enabled
SWITCH <MODEL SELECTION>
SWITCH <TEST RUN>
THERMISTOR
NAME
SWITCH <FUNCTION SELECTION>
SWITCH <DISPLAY SELECTION>
TERMINAL BLOCK <CENTRALIZED CONTROL>
SOLENOID VALVE <HOT GAS BYPASS>
TERMINAL BLOCK <POWER SUPPLY>
THERMISTOR
SMOOTHING CAPACITOR
C03 CAPACITOR <FILTER>
C01,C02
CONNECTOR <DISCHARGE CIRCUIT,POWER SUPPLY>
CNR
RESISTOR <RUSH CURRENT PROTECT>
RS1
RESISTOR <DISCHARGE>
RB1,RB2
RESISTOR <VOLTAGE BALANCE ADJUSTMENT>
RD1,RD2
RELAY
X
X73
RELAY <SOLENOID VALVE>
X72
RELAY <4-WAY VALVE>
C1,C2 FAN MOTOR CAPACITOR
SWU3
SWU2
SWU1
SW5
SW4
SW3
THHS
INTELLIGENT POWER MODULE
IPM
FAN CONTROLF.C
CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY>
CN40
CONNECTOR <FOR STORING JUMPER CONNECTOR>
CN41
CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT>
CN51
CONNECTOR <INVERTER SIGNAL 5V>
CN4
CONNECTOR <POWER SUPPLY 30V,12V,5V>
CN3
CONNECTOR <POWER SYNC SIGNAL,PROTECTION>
CN2
CONNECTOR <CONTROLLER DRIVE CONTROL>
CN1
CONNECTOR <POWER SUPPLY>
CNA
CONNECTOR <CURRENT DETECTION>
ACCT
NAMENAME
SW2
SW1
CONNECTOR <AUTO CHANGE OVER SIGNAL>
CN3D
REACTOR
THERMAL SWITCH <COMPRESSOR>
TH2
TH5
TH6
63HS
52C
21S4
TH1
SV1
SLEV
MF1,MF2
LD1
X71
CNS1 CNS2
ZNR
FUSE2
TB7
TB3
TB1
MC
DCL
NF
FUSE1
49C
CONNECTOR <MULTI SYSTEM> CONNECTOR <CENTRALIZED CONTROL>
FUSE (2A)
DIGITAL INDICATION LED <OPERATION INSPECTION INDICATION>
FAN MOTOR <INNER THERMOSTAT>
EXPANSION VALVE
HIGH PRESSURE SENSOR <DISCHARGE PRESSURE DETECTION>
MAGNETIC CONTACTOR
4-WAY VALVE
RELAY <MAGNETIC CONTACTOR>
VARISTOR
FUSE (6.3A)
COMPRESSOR <INNER THERMOSTAT>
NOISE FILTER
THERMISTOR
THERMISTOR
<PIPE TEMP. DETECTION • JUDGING DEFROST>
CB1,CB2
DMSMOOTHING CAPACITOR DIODE MODULE
NAME
SYMBOL SYMBOL SYMBOL SYMBOL
21
8
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
051
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
056
001
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
010
101
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
002
102 104 154
1111
11
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
009
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
008
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
003
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
007
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
006
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
004
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
005
1 A transmission wire must be
connected to each refrigerant
system (outdoor and indoor).
2 Set addresses:
Outdoor unit ..............051-100
Indoor unit .................001-050
Remote controller .....101-200
3 PUMY-P125VMA has no SW 3(3rd digit).
The address automatically become
"100" if it is set as "01~50".
Remote
controller
Remote
controller
Remote
controller
Remote
controller
105
Remote
controller
157
Remote
controller
107
Remote
controller
For centralized
management
For remote
controller
Address SW Address SW Address SW Address SW Address SW
Piping
Outdoor unit
Outdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unitIndoor unitIndoor unitIndoor unitIndoor unit
Address SW Address SW Address SW Address SW Address SW
Address SWAddress SWAddress SWAddress SWAddress SW
Address SWAddress SW
For centralized
management
For remote
controller
Transmission wire
2
1
NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION
8-1. TRANSMISSION SYSTEM SETUP
22
8-2. REFRIGERANT SYSTEM DIAGRAM
Flare
Flare
Strainer #100
Strainer #100
Strainer (#100)
Strainer
Strainer #100
(Refrigerant flow)
Cooling Heating
#50
Strainer
Compressor (MC)
Expansion valve (LEV(A), SLEV)
Accumulator
Overcooling heat exchanger
Outdoor heat exchanger
Service port
Service port
Thermistor TH2 (Saturation temperature of suction pressure)
Capillary tube 2
Capillary tube 4
Dryer
Capillary tube 3
Oil separator
Check valve (low pressure)
Thermistor THHS (Radiator panel temperature sensor)
W Only PUMY-P125VMA Thermistor THHS-A Thermistor THHS-B
Thermistor TH6 (outdoor air temperature sensor)
4-way valve
High-pressure sensor discharge pressure sensor (63HS)
Capillary tube 1
Check valve (High pressure)
Electromag­netic valve (SV1)
Thermistor TH5 (piping temperature monitoring and determination)
Thermistor TH1 (discharge temperature sensor)
Outdoor unit
PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA
Refrigerant Piping Specifications (dimensions of flared connector)
1
Capacity
20 , 25 , 32 , 40
Indoor unit
50 , 63 , 71, 80
100 , 125
Outdoor unit
PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA
Capillary tube 1 (for return of oil from oil separator)
{2.5 O {0.6 O L500
1
125
Concerning the Compressor
This system has a scroll compressor. This compressor uses a low pressure shell that typically has a temperature in the range 30-80°C. In addition, compressor wiring should be in the direction of rotation to the right. Wire colors are red (U), white(V), black (W), yellow and yellow (thermal switch).
Item
Capillary tube 2 (for Evaporating
temperature detection)
Liquid piping Gas piping
{6.35 <1/4”> {9.52 <3/8”> {9.52 <3/8”> {9.52 <3/8”>
Capillary tube 3 (for maintaining equilibrium between upper and lower coils)
{12.7 <1/2”> {15.88 <5/8”> {19.05 <3/4”> {19.05 <3/4”>
({4 O {3.0 O L200) O 2{2.5 O {0.6 O L500
23
Capillary tube 4 (for SV1)
{4 O {2.4 O L360
8-3. SYSTEM CONTROL
For indoor-outdoor transmission wire
Remote control wire
indoor-outdoor trnasmission cable
2 remote controllers
Group operation (maximum 16 indoor units)
Outdoor unit
Indoor unit
Indoor unit Indoor unit
NR
NR
Remote controller network
Indoor unit Indoor unit
NR NR NR
8-3-1. Operating a Single Refrigerant System
When operating either alone or as part of a group, a M-NET remote controller (NR) may be used to control a single refrigerant system that does not overlap with any other system.
<Example of system arrangement>
Using a M-NET remote controller (NR)
Address setting must be performed.The NR wire and indoor and outdoor transmission wires must be a non-polar two wire cable.One NR may be connected to a maximum of 16 indoor unit. Two NR units may be used to perform control tasks (the second one pressed will have priority if two are pressed
simultaneously).
For the system utilizing R-Converter units (PAC-SF29LB), the following systems are not available. Group operation
system, centralized controller, group remote controller, etc. (See the installation manual of R-Converter units.)
If the user plans to install multiple refrigerant
systems and a centralized controller in the future, it is strongly suggested that a NR be used.
24
8-3-2. System Controller (SC) to Perform Centralized Control
Transmission wire for central­ized control
<Room A>
For transmission wire
PAC-SC33KUA PAC-SC34KUA
<Room B>
<Room D> <Room E>
<Room C>
Outdoor
unit
Indoor unit
A
Indoor unit Indoor unit Indoor unit
Remote controller network
Remote control
wire
Indoor • outdoor transmission wire (Shielded wire)
SC: Centralized controller, linked system control board, group remote controller, etc.
A : M-NET or MA remote controller
(Coexistence of M-NET remote controller and MA remote controller is not admitted in the same system.)
Indoor unit
Indoor unitIndoor unitIndoor unitIndoor unitIndoor unit
Power supply installation
System controller
Outdoor
unit
Indoor • outdoor transmission wire (Shielded wire)
A
A
A
AA
<Example of System Arrangement>
The following diagram shows the use of system controller (SC) to control a system that includes the multiple outdoor unit.
Note 1) The NR, SC, indoor and outdoor unit all require address settings.
Indoor unit
Outdoor unit
M-NET R/C (Main)
M-NET R/C (Sub)
SC
MA Remote controller
ww
The address automatically becomes “100” if it is set as “01~50”. (PUMY-P125VMA)
Linked settings must be made within a group.
The lowest address of an indoor unit within a refrigerant system is +50.
The lowest address of an indoor unit within a group is +100.
The address of the main remote controller is +50.
Unnecessary address setting (Necessary main/sub setting)
1 ~ 50
51 ~ 100
ww
101 ~ 150 151 ~ 200
0 or 201 ~ 250
2) Indoor unit that may be connected with an SC are shown as follows.
Centralized controller Multi-unit controller board Group controller
3) There may be a maximum of two controllers when a group has 16 indoor units or less.
4) The transmission wire must have a power supply when an SC is used. Please connect the power supply for the transmission wire to the centralized controller transmission wire.
SC with 2 units or less SC with 3 to 5 units
5) Use a shielded wire (at least 1.25mm
50 group /50 units 24 group /50 units 8 group /16 units
Power supply for transmission wire PAC-SC33KU Power supply for transmission wire PAC-SC34KU
2
)for the indoor, outdoor, and centralized controller transmission wires. In addition, all shielded wires in a system must be grounded at one point. If the length of the remote control wire exceeds 10m, use an insulated wire for the extra portion.
25
8-3-3. Example for the System
OC
IC
(051)
M1 M2
S
TB512TB15
12
TB15
NR
(001)
IC
M1 M2
S
TB5
(002)
NR
M1 M2 SM1 M2 S
TB3 TB7
L2
L1
r1 L3
r2
TB6
(101)
TB6
(102)
OC
(051)
IC
M1 M2 S
TB5
(001)
IC
TB5
(002)
NR
TB6
(101)
NR
TB6
(151)
NR
TB6
(102)
NR
TB6
(152)
M1 M2 S
M1 M2 SM1 M2 S
TB3 TB7
12
TB15
12
TB15
OC
IC
(051)
M1 M2 S
TB5
NR
(001)
IC
M1 M2 S
TB5
(002)
TB6
(101)
M1 M2 SM1 M2 S
TB3 TB7
Main
Sub
12
TB15
12
TB15
• Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed in the standard system with detailed explanation. The explanation for the system in this section : Use one single outdoor unit and multiple outdoor units for M-NET remote
control system. Use one single outdoor unit and multiple indoor units in the multiple outdoor units for the M-NET remote control system.
A. Example of a M-NET remote controller system (address setting is necessary.)
Example of wiring control cables Wiring Method and Address Setting
1. Standard operation
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use non-polarized two wire.
b. Connect terminals M1 and M2 on transmission
cable terminal block (TB5) for each indoor unit with the terminal block (TB6) for the remote controller (NR).
c. Set the address setting switch as shown below.
• One remote controller for each indoor unit.
• Inside ( ) Address: There is no need for setting the 100 position on the remote controller.
2. Operation using two remote controllers
• Using two remote controllers for each indoor unit.
Main
3. Group operation
• Multiple indoor units operated together by one remote controller
Combinations of 1through 3 above are possible.
Sub
Main
Sub
Unit
Indoor unit (IC)
Outdoor unit
(OC)
Remote
controller (NR)
Range
001 to 050 051 to 100 101 to 150
Setting Method
Use the most recent address of all the indoor unit plus 50. Indoor unit address plus
100.
a. Same as above. b. Same as above. c. Set address switch as shown below.
Unit
Indoor Unit (IC)
Outdoor unit
(OC)
Main Remote
Controller (NR)
Sub Remote
Controller (NR)
Range
001 to 050 051 to 100
101 to 150 151 to 200
Setting Method
Use the most recent address of all the indoor units plus 50. Indoor unit address plus
100. Indoor unit address plus
150.
a. Same as above. b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) of the IC main unit with the most most recent address within the same indoor unit (IC) group to terminal block (TB6) on the remote controller.
c. Set the address setting switch as shown below.
Unit
IC (Main)
IC (Sub)
Outdoor Unit
Main Remote
Controller
Sub Remote
Controller
Range
001 to 050
001 to 050
051 to 100 101 to 150 151 to 200
Use the most recent address within the same group of indoor units. Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be in sequence with the IC (Main). Use the most recent address of all the indoor units plus 50. Set at an IC (Main) address within the same group plus 100. Set at an IC (Main) address within the same group plus 150.
Setting Method
d. Use the indoor unit (IC) within the group with the most functions as the IC (Main) unit.
26
• Name, Symbol and the Maximum Remote controller Units for Connection
OC
IC
Main Sub
(051)
M1 M2 S
TB5
NR
(001)
IC
M1 M2 S
TB5
(002)
TB6
(102)
M1 M2 SM1 M2 S
TB3 TB7
1
2
TB15
1
2
TB15
1
2
TB15
1
2
TB15
IC
M1 M2
SM1 M2
S
TB5
(001)
IC
TB5
(002)
NR
Main Sub Main Sub
TB6
(101)
NR
TB6
(151)
NR
TB6
(102)
NR
TB6
(104)
NR
TB6
(103)
M1 M2 SM1 M2 S
TB3 TB7
OC
(051)
12
TB15
12
TB15
IC
M1 M2 S1
2M1 M2
S
TB5
TB6
TB15
1
2
TB15
(001)
IC
TB5
(002)
M1 M2 SM1 M2 S
TB3 TB7
OC
(051)
MANR
(101)
Name
Outdoor unit
Indoor unit
M-NET remote
controller
Symbol
OC
IC
NR
Maximum units for connection
One OC unit can be connect to 1-8 IC units Maximum two NR for one indoor unit, Maximum 16 NR for one OC
Permissible Lengths Prohibited items
Longest transmission cable length (1.25 mm
1 + L2, L2 + L3, L3 + L1 [ 200m
L
2
)
Remote controller cable length
1. If 0.5 to 0.75 mm
2
R1, R2 [10m
2. If the length exceeds 10 meters, the exceeding section should be 1.25 mm
2
and that section should be a value within the total extension length of the transmission cable and maximum transmission cable
length. (L
3)
Same as above
• M-NET remote controller(NR) and MA remote controller(MA) cannot be used together.
• Do not connect anything with TB15 of indoor unit(IC).
• Use the indoor unit(IC) address plus 150 as the sub remote controller address. In this case, it should be 152.
• Three or more remote controller (NR) cannot be connected to one indoor unit.
Same as above
• The remote controller address is the indoor
unit main address plus
100. In this case, it should be 101.
27
B. Example of a group operation system with two or more outdoor units and a M-NET remote controller.
M1 M2 S
M1 M2 S
TB7
TB3
IC
(051)
M1 M2 S
TB512TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
NR
(001)
IC
M1 M2 S
TB5
(002)
IC
M1 M2 S
TB5
(004)
IC
M1 M2 S
TB5
(003)
IC
M1 M2 S
TB5
(005)
IC
M1 M2 S
TB5
(007)
IC
M1 M2 S
TB5
(006)
L1
L8
R1
R4
L9
L2 L3 L4
L5 L6 L7
TB6
(101)
NR
TB6
(105)
NR
TB6
(103)
NR
TB6
(155)
CN40
OC
Between terminal blocks
M1 M2 S
M1 M2 S
TB7
TB3
(052)
OC
R2
R3
Shielded wire
(Shielding wires and address settings are necessary.)
Examples of Transmission Cable WiringWiring Method Address Settings
Group 3
Group 5Group 1
Sub remote controller
( ) Address
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block
(TB3) of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block (TB6) on the remote controller (NR).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor
unit (OC).
e. Use the grounded wire to connect the S-terminal on the transmission terminal of the outdoor unit (OC) and the
grounded terminal for the electrical components box. f. On one outdoor unit only, change the jumper connector on the control panel from CN41 to CN40. g. Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which
the jumper connector was inserted into CN40 in Step above to the ground terminal ; in the electrical component
box. h. Set the address setting switch as follows.
Main Remote Controller
Sub Remote Controller
Unit
IC (Main)
IC (Sub)
Outdoor Unit
001 to 050 001 to 050 051 to 100
101 to 150 151 to 200
i. The group setting operations among the multiple indoor units is done by the remote controller (NR) after the electrical
power has been turned on.
Range
Use the most recent address within the same group of indoor units. Use an address, other than that of the IC (Main) from among the units within
the same group of indoor units. This must be in sequence with the IC (Main).
Setting Method
Use the most recent address of all the indoor units plus 50. Set at an IC (Main) address within the same group plus 100. Set at an IC (Main) address within the same group plus 150.
28
• Name, Symbol, and the Maximum Units for Connection
M1 M2 S
TB7
IC
(051)
M1 M2 S
TB512TB15
12
TB15
12
TB15
12
TB15
NR
Shielded wire
Remote controller
(001)
IC
M1 M2 S
TB5
(002)
IC
M1 M2 S
TB5
(004)
IC
M1 M2 S
TB5
(003)
IC
M1 M2 S
TB5
(005)
IC
M1 M2 S
TB5
(007)
IC
M1 M2 S
TB5
(006)
TB6
(101)
NR
TB6
(105)
NR
TB6
(103)
NR
TB6
(155)
CN40
OC
M1 M2 S
TB7
(052)
OC
M1 M2 S
TB3
M1 M2 S
TB3
12
TB15
12
TB15
12
TB15
• Max length via outdoor units : L1+L2+L3+L4+L5+L6+L7+L9 L1+L2+L3+L4+L5+L6+L8+L9 [ 500 meters (1.25mm2)
• Max transmission cable length : L
• Remote controller cable length : R
1+L2+L3+L4, L5+L6+L7, L5+L6+L8, L7+L8 [ 200 meters (1.25mm
1,R2, R3, R4 [ 10 meters (0.5 to 0.75mm
If the length exceeds 10 meters, use a 1.25 mm
tion (L
Permissible Length
8) should be included in the calculation of the maximum length and overall length.
2
)
2
)
2
shielded wire. The length of this sec-
Prohibited items
Group 3
Group 5Group 1
• The terminal S on the terminal block (TB7) for the central control panel should be connected to the ground terminal ; of the electric components box for one outdoor unit only.
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to different outdoor units (OC).
• Set all addresses to ensure that they are not overlapped.
• It cannot be connected M-NET remote controller and MA remote controller with indoor unit of the same group using
together.
29
C. Example of a MA remote controller system (address setting is not necessary.)
OC
IC
(000)
M1 M2
S 21 21
TB5 TB15 TB15
MA
(000)
IC
M1 M2
S
TB5
(000)
MA
M1 M2 SM1 M2 S
TB3 TB7
L2
L1
r1
r2
OC
(000)
IC
M1 M2 12 12S
TB5 TB15 TB15
(000)
IC
TB5
(000)
MA MA
M1 M2 S
M1 M2 SM1 M2 S
TB3 TB7
MA MA
r3
r5
r4
r6
r7
r7
OC
IC
(000)
M1 M2 S 1 2
TB5 TB15
12
TB15
MA
(000)
IC
M1 M2 S
TB5
(000)
M1 M2 SM1 M2 S
TB3 TB7
NOTE : In the case of same group operation, need to set the address that is only main indoor unit.
Example of wiring control cables Wiring Method and Address Setting
1. Standard operation
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use non-polarized two wire.
b. Connect terminals 1 and 2 on transmission cable
terminal block (TB15) for each indoor unit with the terminal block for the MA remote controller (MA).
• One remote controller for each indoor unit.
• Inside ( ) Address: There is no need for setting the 100 position on the remote controller.
2. Operation using two remote controllers
a. The same as above. b. The same as above. c. In the case of using tow remote controllers, connect
terminals 1 and 2 on transmission cable terminal block (TB15) for each indoor unit with the terminal block for tow remote controllers.
· Set the sub remote controller position for one of MA remote controller’s main switch. Refer to the installation manual of MA remote controller
• Using two remote controllers for each indoor unit.
3. Group operation
• Multiple indoor units operated together by one remote controller
Combinations of 1through 3 above are possible.
a. The same as above. b. The same as above. c. Connect terminals 1 and 2 on transmission cable ter-
minal block (TB15) of each indoor unit, which is doing group operation with the terminal block the MA remote controller. Use non-polarized tow wire.
d. In the case of same group operation, need to set the
address that is only main indoor unit. Please set the address of the indoor unit with the most functions in the same group in the number that 01-50 is young.
30
Permissible Lengths Prohibited items
IC
M1 M2 S1
2M1 M2
S
TB5 TB15
1
2
TB15
(001)
IC
TB5
(002)
M1 M2 SM1 M2 S
TB3 TB7
OC
(051)
MAMA
IC
M1 M2 S1
2M1 M2
S
TB5 TB15
1
2
TB15
(000)
IC
TB5
(000)
M1 M2 SM1 M2 S
TB3 TB7
OC
(000)
MA MAMAMAMA
IC
M1 M2 S1
2M1 M2
S
TB5 TB15
1
2
TB15
(000)
IC
TB5
(000)
M1 M2 SM1 M2 S
TB3 TB7
OC
(000)
MAMANR
Longest transmission cable length
1 + L2 [ 200m (1.25 mm
L
2
)
MA remote controller cable length
R
1, R2 [ 200m (0.3 ~ 1.25 mm
2
Longest transmission cable length The same as above. MA remote controller cable length
R
3 +R4, R5 +R6 [ 200m
(0.3 ~ 1.25 mm
2
)
The MA remote controller and the M-NET remote controller cannot be used together with the indoor unit
)
the of the same group.
Three MA remote controller or more cannot be connect with the indoor unit of the same group.
Longest transmission cable length The same as above. MA remote controller cable length
R
7 +R8 [ 200m (0.3 ~ 1.25 mm
2
)
The second MA remote control is connected with the terminal block(TB15) for the MA remote con­trol of the same indoor unit(IC) as the first remote control.
31
D. Example of a group operation with two or more outdoor units and a MA remote controller.
M1 M2 S
M1 M2 S
TB7
TB3
IC
(051)
M1 M2 S 1 2
TB5 TB15
MA
(001)
IC
M1 M2 S
TB5
(002)
IC
M1 M2 S
TB5 TB15
(004)
IC
M1 M2 S
TB5
(003)
IC
M1 M2 S
TB5 TB15
(005)
IC
M1 M2 S
TB5 TB15TB15TB15
(007)
IC
M1 M2 S
TB5 TB15
(006)
L
1
L8
R1
R4
L9
L2 L3 L4
L5 L6 L7
MAMAMA
Sub remote
controller
CN40 CN41
CN41
OC
Between terminal blocks
M1 M2 S
M1 M2 S
TB7
TB3
(052)
OC
R2
R3
Shielded wire
12
12
12 12
12 12
(Shielding wires and address settings are necessary.)
Examples of Transmission Cable WiringWiring Method Address Settings
Group 3
Group 5Group 1
( ) Address
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1, M2 and S and the ground terminal on the transmission cable terminal block
(TB3) of each outdoor unit (OC) to terminals M1, M2 and S on the transmission cable block (TB15) of the indoor unit (IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block on the remote controller (MA).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor
unit (OC).
e. Use the grounded wire to connect the S-terminal on the transmission terminal of the outdoor unit (OC) and the
grounded terminal for the electrical components box.
Range
001 to 050 001 to 050 051 to 100
Use the most recent address within the same group of indoor units. Use an address, other than that of the IC (Main) from among the units within
the same group of indoor units. This must be in sequence with the IC (Main). Use the most recent address of all the indoor units plus 50.
f. On one outdoor unit only, change the jumper connector on the control panel from CN41 to CN40. g. Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which
the jumper connector was inserted into CN40 in Step above to the ground terminal ; in the electrical component box.
h. Set the address setting switch as follows.
Unit
IC (Main)
IC (Sub)
Outdoor Unit
Setting Method
32
• Name, Symbol, and the Maximum Units for Connection
M1 M2 S
TB7
IC
(051)
M1 M2 S 1 2 1 2 1 2
TB5 TB15
12
TB15 TB15 TB15
MA
Shielded wire
(001)
IC
M1 M2 S
TB5
(002)
IC
M1 M2 S
TB5
(004)
IC
M1 M2 S
TB5
(003)
IC
M1 M2 S
TB5
(005)
IC
M1 M2 S
TB5
(007)
IC
Group 1 Group 3 Group 5
M1 M2 S
TB5
(006)
MAMAMA
CN40
OC
M1 M2 S
TB7
(052)
OC
M1 M2 S
TB3
M1 M2 S
TB3
1212
TB15 TB15
12
TB15
• Max length via outdoor units : L1+L2+L3+L4+L5+L6+L7+L9 L1+L2+L3+L4+L5+L6+L8+L9 [ 500 meters (1.25mm2)
• Max transmission cable length : L
• Remote controller cable length : R
1+L2+L3+L4, L5+L6+L7, L5+L6+L8, L7+L8 [ 200 meters (1.25mm
1,R2, R3, R4 [ 10 meters (0.5 to 0.75mm
If the length exceeds 10 meters, use a 1.25 mm
tion (L
Permissible Length
8) should be included in the calculation of the maximum length and overall length.
2
)
2
)
2
shielded wire. The length of this sec-
Prohibited items
• The terminal S on the terminal block (TB7) for the central control panel should be connected to the ground terminal ; of the electric components box for one outdoor unit only.
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to different outdoor units (OC).
• M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wring together
33
9 TROUBLESHOOTING
PAR-20MAA
ON/OFF
TEST RUN
˚C
1Hr.
FILTER
CHECK TEST
TEMP.
TIMER SET
Check code indicator (see NOTE 1) Test run remaining time indicator (see NOTE 3)
Display panel
ON/OFF button 9
ON/OFF LED (Lights up in operation)
LOUVER button 6
TEST RUN button 2
AIR DIRECTION button 2
AIR SPEED button 5
TEST RUN indicator
Indoor unit liquid pipe temperature indicator
(see NOTE 4)
(Cooling/Heating) OPERATION SWITCH button 3,4
Control panel
9-1. CHECK POINTS FOR TEST RUN
9-1-1. Procedures of test run
(1) Before test run, make sure that following work is completed.
• Installation related : Make sure that the panel of cassette type and electrical wiring is done. Otherwise electrical functions like auto vane will not operate normally.
• Piping related : Perform leakage test of refrigerant and drain piping. Make sure that all joints are perfectly insulated. Check stop valves on both liquid and gas side for full open.
• Electrical wiring related :
Check ground wire, transmission cable, remote controller cable, and power supply cable for secure connection. Make sure that all switch settings of address or adjustments for special specification systems are correctly settled.
(2) Safety check :
With the insulation tester of 500V, inspect the insulation resistance. Do not touch the transmission cable and remote controller cable with the tester. The resistance should be over 1.0 M. Do not proceed inspection if the resistance in under 1.0 MΩ. Inspect between the outdoor unit power supply terminal block and ground first, metallic parts like refrigerant pipes or the electrical box next, then inspect all electrical wiring of outdoor unit, indoor unit, and all linked equipment .
(3) Before operation :
a) Turn the power supply switch of the outdoor unit to on for compressor protection. For a test run, wait at least 12 hours from this point. b) Register control systems into remote controller(s). Never touch the on/ off switch of the remote controller(s). Refer to “ 8-1-2 M-NET
Remote Controller Settings” on page 29 as for settings . In MA remote controller(s), this registration is unnecessary.
(4) More than 12 hours later form power supply to the outdoor unit, turn all power switch to on for test run. Perform test run according to the
“Operation procedure” table of the bottom of this page. While test running, make test run reports .
(5) When you deliver the unit after test run, instruct the end user for proper usage of the system using owners’ manual and the test run report
you made to certificate normal operation. If abnormalities are detected during test run, refer to “ 8-1-3 Countermeasures for Error During Test Run” on page 31. As for DIP switch setting of outdoor unit, refer to” 8-5. INTERNAL SWITCH FUNCTION TABLE” on page 54.
1 Turn on the main power supply the all units at least 12 hrs. before test run. ”HO” appears on display panel for 3 min. 2 12 hrs later, press TEST RUN button twice to perform test run. “TEST RUN “ appears on display panel. 3 Press OPERATION SWITCH button to make sure that air blows out. 4 Select Cooling (or Heating) by OPERATION SWITCH button to make sure that cool (or warm) air blow out. 5 Press Fan speed button to make sure that fan speed in changed by the button. 6 Press AIR DIRECTION button or LOUVER button to make sure that air direction is adjustable(horizontal, downward, upward, and each angle). 7 Check outdoor fans for normal operation. 8 Check interlocked devices (like ventilator) for normal operation, if any. This is the end of test run operation. 9 Press ON/OFF button to stop and cancel test run.
NOTE 1 : If error code appears on remote controller or remote controller malfunction , refer to “ 8-1-3 Countermeasures for Error During Run”
on page 31. NOTE 2 : During test run operation 2-hours off timer activates automatically and remaining time is on remote controller and test run stops 2 later. NOTE 3 : During test run, the indoor liquid pipe temperature is displayed on remote controller instead of room temperature. NOTE 4 : Depend on a model, “This function is not available” is appears when air direction button is pressed, however, this is not malfunction.
Operation procedure
34
9-1-2. Special Function Operation and Settings (for M-NET Remote Controller)
The addresses of indoor unit and linked units are displayed simultaneously.
(alternating display)
These alternating IC or LC displays will appear when entry is completed normally.
A flashing “88” will appear if there is a problem with the entry (indicating that the unit does not exist).
• It is necessary to perform “group settings” and “paired settings” at making group settings of different refrigerant systems (multiple outdoor unit). (A) Group settings: Enter the indoor unit controlled by the remote controller, check the content of entries, and clear
entries, etc.
(B) Paired settings: Used to set the linked operation of a Lossnay unit.
(1) Entering address: Follow the steps below to enter the addresses of the indoor unit using the remote controller.
a) Group settings
• Turning off the remote controller: Press the ON/OFF button to stop operation (the indicator light will go off).
• Changing to indoor unit address display mode: If the FILTER and k buttons on the remote controller are pressed simultaneously and held for two seconds, the display shown in Figure 1 will appear.
• Changing address: Press the temperature adjustment buttons to change the displayed address to the address to be entered.
• Entering the displayed address: Press the TEST RUN button to enter the indoor unit with the displayed address. The type of the unit will be displayed as shown in Figure 2 if entry is completed normally. If a selected indoor unit does not exist, an error signal will be displayed as shown in Figure 3. When this happens, check whether the indoor unit actually exists and perform entry again.
• Returning to the normal mode after completing entry: Press the FILTER and k buttons simultaneously and hold for two seconds to return to the normal mode.
Figure 1 (A) Group setting display
Figure 2 Normal completion of entry
Figure 3 Entry error signal
Flashing “88” indicates entry errorType of unit is displayed
b) Paired Settings
• Turn off the remote controller: Press the remote controller’s ON/OFF button to turn it off (the indicator light will go off).
• Put in indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for two seconds.
The above steps are the same as when making group settings (A).
• Changing to the linked operation unit address display state: The display shown in Figure 4 will appear when the
a
button on the remote control is pressed.
• Displaying the address of the Lossnay unit and linked indoor unit: In this situation, the indoor unit number will be the lowest address of the group. The Lossnay unit will not operate if this setting is
incorrect.
If the temperature adjustment buttons are pressed, the address may be changed to the indoor unit that are
to be linked.
If the time setting buttons are pressed, the address of the linked units may be changed to the address where
it is desired to enter the Lossnay .
• Linking the Lossnay and the indoor unit: The display shown in Figure 5 will appear when the TEST RUN button is pressed. The indoor unit whose address is displayed and the Lossnay unit with a linked address will operate in a linked manner.
If it is desired to display the address of the Lossnay in the indoor unit address, display the indoor
unit address in the linked unit address, and the above content will also be recorded.
Apart from the indoor unit with the lowest address in the group, display and enter the addresses of the other indoor unit
that are to be linked with the Lossnay unit.
• Returning to the normal mode after completing entry: Press the FILTER and k buttons on the remote controller simultaneously and hold for two seconds to return to the normal mode.
Figure 4 (B) Making paired settings
Figure 5 Completing normal entry
35
(2) Address check: Refer to section (1) regarding address entry.
"88" will appear in the room temperature display location.
"--" will appear in the room temperature display location.
a) In making group settings:
• Turn off the remote controller: Press the remote controller's ON/OFF button to stop operation (the indicator light will go off).
• Locate the indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for two seconds.
• Display indoor unit address: The entered indoor units address and type will be displayed each time the button is pressed.
When one entry is made, only one address will be displayed no matter how many times the w button is pressed.
• Returning to the normal mode after completing check: Simultaneously press the FILTER and k buttons on the remote controller and hold for two seconds to return to the normal mode.
b) In making paired settings:
• Turn off the remote controller: Press the remote controller's ON/OFF button to stop operation (the indicator light will go off).
• Put in indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for two seconds.
• Changing to the linked operation unit address display state: Press the a button on the remote control.
• Displaying the address of the indoor unit to be checked: Change the address to that of the indoor unit to be checked by press­ing the temperature adjustment buttons .
• Displaying the address of the linked Lossnay unit: Press the w button to display the addresses of the linked Lossnay and indoor unit in alternation.
• Displaying the addresses of other entered units: The addresses of the other entered units will be displayed in alternating fash­ion after resting the w button again.
• Returning to the normal mode after completing the check: Simultaneously press the FILTER and k buttons on the remote controller and hold for two seconds to return to the normal mode.
(3) Clearing an address: Refer to section (1) regarding the address entry and section (2) regarding checking addresses.
a) In making group settings:
• Turn off the remote controller: The procedure is same as a) in (2) Address check.
• Put in the indoor unit address display mode: The procedure is same as a) in (2) Address check.
• Displaying the indoor unit address to be cleared: The procedure is same as a) in (2) Address check.
• Clearing indoor unit address : ......Pressing the q button on the remote controller twice will clear the address entry of the
displayed indoor unit, resulting in the display shown in Figure 6. The display shown in Figure 7 will appear if an abnormality occurs and the entry is not cleared. Please repeat the clearing procedure.
• Returning to the normal mode after clearing an address: The procedure is same as a) in (2) Address check.
Figure 6 Display after address has been
cleared normally
Figure 7 Display when an abnormality
has occurred during clearing
b) In making paired settings:
• Turn off the remote controller: The procedure is same as b) in (2) Address check.
• Put into the indoor unit address display mode: The procedure is same as b) in (2) Address check.
• Put into the linked unit address display mode: The procedure is same as b) in (2) Address check.
• Display the address of the Lossnay unit or the indoor unit to be cleared.
• Deleting the address of a linked indoor unit: Pressing the q button on the remote controller twice will clear the address entry of the displayed indoor unit, resulting in the display shown in Figure 8.
• Returning to the normal mode after clearing an address: The procedure is same as b) in (2) Address check.
Figure 8 Display after address has been cleared normally
(altenating display)
"--" will appear in the unit type display location when an address has been cleared normally.
"88" will appear in the unit type display location when an abnormality has occurred during clearing.
36
9-1-3. Countermeasures for Error During Test Run
12 34 56 78 LD1
Check code Check codeTrouble Trouble
1102 1108 1302 1500 1501 1505 2502 2503 4115 4116 4220 4230 4250
5101
5102 5103
5105 5106
5110
5201 5300
Discharge temperature trouble Compressor's inner thermal sensor trouble High pressure trouble Excessive refrigerant replenishment Insufficient refrigerant Vacuum operation protection Drain pump trouble Drain sensor trouble (THd) Power synchronization signal trouble Indoor unit fan rotation trouble Inverter main voltage drop Overheat protection of radiator panel Multiple IPM errors (Over current trouble)
Intake thermistor trouble (TH21) or discharge thermistor trouble (TH1)
Liquid pipe thermistor trouble (TH22) or low pressure saturation thermistor trouble (TH2)
Gas pipe temperature sensor trouble (TH23) Piping temperature sensor trouble (TH5) Outdoor temperature sensor trouble (TH6) ACTM/IGBT Radiator panel thermistor trouble (THHS-A/B) (PUMY-P125VMA) IPM
Radiator panel
thermistor trouble (THHS)
(PUMY-P125YMA, PUMY-P125YMA
1)
Pressure sensor trouble (63HS) Current sensor error (PUMY-P125VMA)
Duplicated unit address setting Transmission error (Transmission processor
hardware error) Transmission error (Transmission route BUSY) Transmission and reception error
(Communication trouble with transmission processor) Transmission and reception error (No ACK error)
No response MA communication receive signal error
(no receive signal) MA communication send signal error
(starting bit detection error) MA communication send error (H/W error) MA communication receive error
(Synchronous recovery error) Total capacity error
Capacity code error Connecting unit number error Address set error Remote controller sensor trouble Communication trouble with Power Board (PUMY-P125VMA)
6600 6602
6603 6606
6607 6608
6831
6832 6833
6834 7100
7101 7102 7105
7111
0403
• If a problems occurs during test run, a code number will appear in the temperature display area on the remote controller (or LD1 on the outdoor unit), and the air conditioning system will automatically cease operating.
Determine the nature of the abnormality and apply corrective measures.
3
21S4
4
SV1
52C : Compressor Contactor 21S4 : Four-way valve SV1 : Bypass valve
5
37
The operational status of the outdoor unit controller is displayed on the LD1 of the outdoor unit under normal conditions (when all SW1’s are OFF)
Field
Display item
Example: When the air conditioner is in the heating mode and the SV1 and compressor turned on.
1
Compressor
is operating
2
52C
6
7
8
Lit steadily
Display
1102
Meaning and detecting method
Discharge temperature abnormality
When the discharge temperature thermistor
1
(TH1) detects 125 the compressor stops and restarts operation in 3 minutes.
2
When the thermistor detects 125 again (2nd detection) within 30 minutes since the compressor has stopped, the compressor stops and restarts operation in 3 minutes.
3
When the thermistor detects 125 again (3rd detection) within 30 minutes since the compressor has stopped 2 times, the compressor stops abnormally. <1102> is displayed.
4
When the thermistor detects 125; or more after 30 minutes since the compressor has stopped (1st or 2nd time), it becomes the 1st detection or the same
performance as above-mentioned 1.
5
It is being delay for abnormal stop during 30 minutes since the compressor has stopped. In this time, check delay code <1202> will be displayed.
;or more (1st detection),
;or more
;or more
Causes
1) Gas leakage, Gas shortage
2) Overloaded operation
3) Indoor linear expansion valve operation defective
4) Ball valve operation defective
5) Outdoor fan block and defective of fan motor (heating mode)
6) Gas leakage between high and low pressure (Defective of 4-way valve or compressor)
7) Solenoid valve (SV1) performance defective (control failure to prevent the discharge temp. from rising by SV1)
8) Thermistor defective
9) Input circuit defective of multi controller board
Check points
Check the refrigerant amount. Check the indoor/outdoor unit operating
condition and status. Perform cool or heat operation to check the condition.
Check ball valve is fully opened. Check the outdoor fan motor.
Check the operating condition.
Check the solenoid valve performance.
Check the thermistor resistance.
Check the intake temperature in discharge temperature thermistor (TH1) by LD1. (See 5101 Discharge temperature thermistor error)
1108
1302
Compressor inner thermo abnormality When the inner thermo performs (1st
1
detection) during the compressor operation, the compressor stops and restarts operation in 3 minutes.
When the inner thermo performs again (2nd
2
detection) within 30 minutes since the compressor has stopped, or does not recover within 30 minutes, it stops abnormally. In this time <1108> is displayed.
When the inner thermo performs after 30
3
minutes since the compressor has stopped (1st stop), it is the 1st detection and becomes the same performance as above-
mentioned It is being delay for abnormal stop during
4
30 minutes since the compressor has stopped. In this time, check delay code <1208> will be displayed.
High-pressure pressure abnormality When high-pressure pressure sensor
1
detects 2.94MPa or more (1st detection) during the compressor operation, the compressor stops and restarts operation in 3 minutes
1.
1) Low voltage supplied to power supply terminal block
2) Power supply L2 or L3 phase is opened. (When L1 phase is opened, power supply of the micro computer is not supplied.)
3) Compressor failure (Over current by motor rare short, etc.)
4) Overloaded operation
5) Gas leakage, Gas shortage
6) Inner thermo defective
7) Input circuit defective of multi controller board or power supply board
1) Indoor unit short cycle
2) Indoor unit filter clogging
3) Air flow capacity decrease due to indoor fan dirt
4) Indoor heat exchanger dirt
Measure the terminal voltage. Check the voltage reduction.
Check the open phase.
Check the coil resistance.
Check the indoor/outdoor unit operating condition and status.
Check the refrigerant amount.
Check the current flows in inner thermo.
When the inner thermo is normal and input circuit is defective, even if the inner thermo performs, the compressor does not operate and becomes error in 30 minutes.
Check the indoor unit. Check the indoor unit filter.
Check the indoor fan.
Check the indoor unit heat exchanger.
38
Display
1302
Meaning and detecting method
2
When the sensor detects 2.94MPa or more again (2nd detection) within 30 minutes since the compressor has stopped, the compressor stops again and restarts operation in 3 minutes.
When the sensor detects 2.94MPa or more
3
again (3rd detection) within 30 minutes since the compressor has stopped, the compressor stops again and restarts operation in 3 minutes.
When the sensor detects 2.94MPa or more
4
again (4th detection) within 30 minutes after 3rd compressor stop, it stops abnormally.
When the sensor detects 2.94MPa or more
5
after 30 minutes since the compressor has stopped (1st or 2nd or 3rd time), it becomes the 1st detection or the same
performance as above-mentioned
6
It is being delay for abnormal stop during 30 minutes since the compressor has stopped. In this time, check delay code <1402> will be displayed.
Note) For first 7 minutes in COOL or HEAT starting, error detected pressure of high­pressure pressure sensor is 3.14MPa.
In this time <1302> is displayed.
1.
Causes
5) Indoor fan motor lock Check the indoor fan motor.
6) Indoor fan motor failure Check the indoor fan motor.
7) 4-way valve performance failure (Stop in the middle of performance)
8) Ball valve performance failure (not full-opened)
9) Pipe clogged or broken
10) Indoor linear expansion valve performance failure
11) Outdoor fan motor lock
12) Outdoor fan motor failure
13) Outdoor unit short cycle
14) Outdoor heat exchanger dirt
15) Decrease in airflow capacity which the outdoor unit intakes because of intake defective of outer temperature thermistor. (Intake less than the actual outer air)
16) Indoor unit capacity codes miss setting (If the capacity code is set greatly, initial frequency rises and high­pressure is easy to rise.)
17) Solenoid valve (SV1) performance failure (High-pressure pressure cannot be controlled by SV1)
Change COOL/HEAT operation mode to perform the 4-way valve. If any defective, replace the 4-way valve.
Check the ball valve full-opened.
Repair the defective points. Operate COOL or HEAT operation,
and check the operation condition.
Check the outdoor unit fan motor. Check the outdoor unit fan motor.
Check the outdoor unit. Check the outdoor unit heat
exchanger. Check intake temperature of the outer
temperature thermistor by LD1. (See 5106 Outer temperature thermistor error)
Check the capacity set switch in the indoor controller board. If it is wrong setting reset it. Check is available for the outdoor unit. (See 7101 Capacity code error)
Check the solenoid valve performance.
Check points
18) Indoor thermistor (liquid pipe temperature detection) detecting failure (thermistor removed) (Hot adjust time becomes long.)
19) High-pressure pressure sensor defective
20) High-pressure pressure sensor input circuit defective in multi controller board.
1500 Refrigerant over charged abnormality 1) Refrigerant over charged Check the refrigerant amount.
When below 5 conditions are satisfied
1
during the compressor operation (1st detection), the compressor stops and restarts operation in 3 minutes.
1. Cool mode, outer temp. is 20 Heat mode, outer temp. is 15
; or less
; or more
2) Light-loaded operation (Wrong determination)
3) Performance defective of the indoor's linear expansion valve and outdoor's electronic expansion valve.
Check the thermistor installed condition. Operate in trial mode and check the pipe temperature change by the remote controller.
Check the high-pressure pressure sensor.
Check the high-pressure pressure sensor.
Check the indoor/outdoor unit operating condition and status.
Perform cool or heat operation to check the condition.
39
Display
1500 2. The compressor has operated
1501
Meaning and detecting method
consecutively 20 minutes or more, since the indoor unit operation capacity had changed (including the compressor operation start).
3. Operation frequency is 80Hz or more.
4. Discharge super heat is below 10
5. Sub cool step continues for 5 minutes or more by SN=4.
2
Same condition as 1 is satisfied again within 60 minutes since the compressor has stopped, it stops abnormally. In this time, <1500> is displayed.
3
Same condition as 1 is satisfied again after 60 minutes since the compressor has stopped (1st time), it becomes the first
detection and same performance as 1.
It is being delay for abnormal stop during
4
60 minutes since the compressor has stopped. In this time, check delay code <1600> will be displayed. Refrigerant shortage abnormality
When the conditions of below detecting
1
mode 1 or 2 are satisfied (1st detection) during the compressor operation, the compressor stops and restarts operation in 3 minutes.
<Detecting mode 1> When the below conditions are satisfied
completely.
1. SW5-5 is OFF.
2. Compressor is operating in HEAT mode. 4) Error detection of discharge super
3. Discharge super heat is 60; or more.
4. Difference of outer temperature thermistor (TH6) and outdoor piping temp. thermistor
(TH5) applies to the formula of (TH6-TH5)<5;.
5. High-pressure pressure sensor is below
1.08MPa. <Detecting mode 2> When the below conditions are satisfied
completely.
1. Compressor is operating.
2. When cooling, discharge super heat is
; or more.
70 When heating, discharge super heat is 95;
or more. When the conditions of detecting mode
2
1and 2are satisfied again (2nd detection) within 30 minutes since the compressor has stopped, it stops abnormally. In this time, <1501> is displayed.
When the conditions of detecting mode
3
1and 2are satisfied again after 30 minutes since the compressor has stopped (1st time), it becomes the 1st detection and
same performance as above It is being delay for abnormal stop during 30
4
minutes since the compressor has stopped. In this time, check delay code <1600> will be displayed.
1.
;.
Causes
4) Discharge super heat detection error
1 High-pressure pressure sensor
failure
2 Discharge temperature thermistor
failure
3 Thermistor input circuit defective in
the multi controller board., and high­pressure pressure sensor input circuit failure
1) Gas leakage, Gas shortage Check the refrigerant amount.
2) When heating operation, refrigerant shortage feeling operation
(When heating, air flow or thermo OFF are mixed-operation, it cause a refrigerant shortage operation.)
3) Ball valve performance failure (not full opened.)
heat
1 High-pressure pressure sensor
defective
2 Discharge temperature thermistor
defective
3 Thermistor input circuit defective and
high-pressure pressure sensor defective in multi controller board
5) Error detection of TH5/TH6
1
Check the high-pressure pressure sensor.
Check the resistance of discharge
2
temp. thermistor. Set the SW1 to and
3
check the high-pressure pressure sensor level.
Set the SW1 to and check the discharge temp. thermistor level.
When the high-pressure pressure sensor and discharge temp. thermistor are normal, if the above mentioned detecting pressure level and temp. are big different from the actual pressure and temp., replace the multi controller board.
Check the operation condition and refrigerant amount.
Check the ball valve is full opened.
Check the high-pressure pressure
1
sensor. Check the resistance of discharge
2
temperature thermistor. Set the SW1 to and
3
check the high-pressure pressure sensor level.
Set the SW1 to and check the discharge temp. thermistor level.
When the high-pressure pressure sensor and discharge temp. thermistor are normal, if the above mentioned detecting pressure level and temp. are big different from the actual pressure and temp. replace the multi controller board.
Check the resistance of thermistor.
1
1 Thermistor defective
Set the SW1 to and
2 Thermistor input circuit defective in
multi controller board
2
check the outdoor pipe temp. thermistor level.
3
Set the SW1 to and check the outer temp. thermistor level.
Check points
21345678
on
21345678
on
21345678
on
21345678
on
21345678
on
21345678
on
40
Display
1505
Meaning and detecting method
Vacuum operation protection
When the suction pressure saturation temperature thermistor (TH2) detects -13; or less and ''[indoor temperature-liquid pipe temperature][ 8deg'' for 3minutes continuously, the 1st COOL operation (compressor operation) after power supply on, it stops abnormally. In this time, <1505> is displayed
Causes
1) Ball valve performance failure (not full opened.)
2) Light-loaded operation (When outer temperature is low, the operation is liable to change to this mode.)
3) Low-pressure over suction by refrigerant shortage
Check points
Check the ball valve is full opened.
Check the indoor/outdoor unit operating condition and status.
Check the refrigerant amount.
2502 Drain pump abnormality
When either of the undermentioned
1
condition is satisfied (when determined drain sensor goes under water) while the indoor unit operation (excluding the case of abnormal stop) and after 3minutes since the drain pump has operated, the indoor unit stops abnormally (however fan continues the normal control). In this time, <2502> is displayed.
· Turn on the side heater of drain sensor, then when temperature up from the detected temperature before turning on is below 20; during 40 seconds.
· The detected temperature is below 63; after 40seconds since the side heater of drain sensor has turned on.
4) Pipe clogging and broken
5) Indoor linear expansion valve performance defective
1) Drain pump trouble
2) Drain defective
· Drain pump clogging
· Drain pipe clogging
3) Open circuit of drain sensor side heater
4) Contact failure of drain sensor connector
5) Dew condensation on drain sensor
· Drain water descends along lead wire.
· Drain water waving due to filter clogging.
6) Indoor controller board defective
· Drain pump drive circuit failure
· Drain heater output circuit failure
Repair the defective points. Perform cool or heat operation to
check the condition.
Check the drain pump. Performance
Please confirm whether water can be drained.
Confirm the resistance of the drain sensor side heater. (approx. 82'at normal between connector CN50 1 and 3 in the indoor controller board)
Check the connector contact failure.
1
Check the drain sensor lead- wire mounted.
Check the filter clogging
2
If the above mentioned checkpoints has any problem, replace the indoor controller board.
When condition which the outdoor unit is
2
stopped forcibly consists, or the drain sensor detects continuously to go under water 5 times, and also detects ''[liquid pipe temperature-suction temperature][ -10deg'' for 30minutes continuously, the indoor unit stops abnormally (however, fan operates by normal control) that indoor unit and excluding [Fan mode or OFF] in same refrigerant system. Also, the outdoor unit which is connected to that indoor unit with refrigerant system stops abnormality (compressor is inhibited to operation). In this time, <2502> is displayed.
7) Both of above mentioned 1)~6) and the indoor linear expansion valve full­closed failure (leakage) happens synchronistically.
41
Check whether the indoor linear expansion valve leaks or not.
Display
2502 Drain pump abnormality
2503 Drain sensor (THd, DS) abnormality
Meaning and detecting method
(Note) Address/Attribute displayed on the remote controller shows the indoor unit which is cause of trouble.
<Detected timing>
Always detecting regardless of the indoor unit status.
<Abnormality clear>
Abnormality is cleared by either of two of the following;
· Reset power supply of the indoor unit and outdoor unit in same refrigerant system, which is the cause of trouble in the refrigerant system.
· Reset power supply of the indoor unit, which is the cause of trouble. (However, power supply interception of 10 minutes or more is necessary.)
(Note) Above 1 and 2 detects independently.
When the drain sensor detects short/open while the operation.
Short: detection of 90; or more
Open: detection of -40; or less
Causes
1) Connector (CN50) contact failure (insertion failure)
2) Thermistor wiring disconnection or half disconnection
Check points
Check whether the indoor controller
1
board connector (CN50) is disconnected or not.
2
Check whether the thermistor wiring is disconnected or not.
4115
Power supply synchronous signal abnormality
When power supply synchronous signal
1
(once a second) is not read, stop the compressor and restarts operation in 3 minutes. (When the synchronous signal is not read at just before of compressor start, the compressor does not start and stops operation 3 minutes.)
2
For 30minutes after the compressor stop (PUMY-P125VMA : 4minutes), it is being to delay abnormal stop. Then, when SW1 is set, the outdoor units address No. and check code <4165> blinks on the 4 digit digital display alternately.
SW1 setting
3
When power supply synchronous signal (once a second) is not read again during abnormal delay, the compressor stops abnormally. Then, the outdoor units address No. and check code <4115> blinks on the 4 digit digital display alternately.
21345678
on
3) Thermistor defective
4) Indoor controller board (detecting circuit) failure
1) Disconnection or contact failure by loose of connector (CN2) is connected to power supply board.
2) Power supply synchronous detected circuit failures in the power supply board.
3) Power supply synchronous detected circuit failure in the multi controller board.
Check the resistance of thermistor.
3
0;···15k' 10;···9.6 k' 20;···6.3 k' 30;···4.3 k'
40;···3.0 k' If abnormality is not found in the
4
method of the above-mentioned from 1 to 3, it is defective of the indoor controller board.
Check the connector insertion.
Replace the power supply board.
Replace the multi controller board.
42
4116 Fan rotational frequency abnormality
(Detected only PKFY-P·VAM-A)
1) Fan rotational frequency detecting connector (CN33) disconnection in the indoor controller board.
Display
Meaning and detecting method
Causes
Check points
Check whether the connector (CN33) in the indoor controller board is disconnected or not.
When rotational frequency of the fan is detected 180rpm or less, or 2000rpm or more (1st detection) while the indoor unit fan operation, the fan stops for 30seconds.
2) Fan output connector (FAN1) disconnection in the indoor power board.
Check whether the connector (FAN1) in the indoor power board is disconnected or not.
When the rotational frequency of the fan is detected 180rpm or less, or 2000rpm or more again after the fan restarts, the indoor unit stop abnormally (fan stops). In this time, <4116> is displayed.
3) Fan rotational frequency detecting connector (CN33) wiring breakage in the controller board or fan output connector (FAN1) breakage in the indoor power board
Check whether the wiring is disconnected or not.
4) Filter clogging Check the filter.
5) Indoor fan motor trouble Check the indoor fan motor.
When there is no problem in the above-mentioned from 1 to 5;
6) Fan rotational frequency detecting circuit failure in the indoor controller board or fan output circuit failure in the indoor power board.
(1) In the case of abnormality after the fan operation; Replace the indoor controller board. When the fan does not recover even if the indoor controller board is replaced, replace the indoor power board.
(2) In the case of abnormality without fan operation, replace the indoor power board.
4220
PUMY-P125VMA
Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit
Abnormal if any of followings are detected during compressor operation;
• Decrease of DC bus voltage to 270V
• Instantaneous decrease of DC bus voltage to 200V
• Increase of DC bus voltage to 400V
1) Decrease of power supply voltage
2) Disconnection of compressor wiring
3) Defective 52C
4) Disconnection or loose connection of CN52C
5) Defective ACT module
6) Defective ACT module drive circuit of outdoor power board
7) Disconnection or loose connection of CNAF
8) Defective 52C drive circuit of outdoor control board
9) Disconnection or loose connection of CN5
10) Disconnection or loose connection of CN2
Check the facility of power supply. Correct the wiring (U•V•W phase) to
compressor. Replace 52C.
Check CN52C wiring.
Replace ACT module. Replace outdoor power board.
Check CNAF wiring.
Replace outdoor controller board.
Check CN5 wiring.
Check CN2 wiring.
1
2
1
2
3
4
5
6
1
2
3
4
5
6
7
8
9
0
43
Display
4220
Meaning and detecting method
PUMY-P125YMA PUMY-P125YMA
1
Shortage abnormality of inverter bus-bar voltage
When direct current bus-bar voltage
1
reduces extremely during the compressor operation, the compressor stops and restarts operation in 3minutes.
It is being delay to stop abnormally for 30
2
minutes after the compressor stop. Then, when SW1 is set, the outdoor unit address No. and check code <4320> blinks alternately on the 4 digit digital display.
SW1 setting
When detecting abnormality of direct bus-
3
21345678
on
bar voltage decrease again during being delay abnormality, it performs the same action as 1. Also, when the abnormality is not detected, it operates normally. Hereafter, action 1 is repeated until 5th abnormal detection.
Causes
1) Power supply terminal voltage is low.
Measure the terminal voltage, and check whether the voltage decreases
Check points
or not.
2) Power supply L2,L3-phase is
Check the power supply is opened.
opened.
3) Diode stack (Diode module)
Check the resistance of diode stack.
defective.
4) Connector lead wire disconnection,
Check the defective points.
contact failure. Power supply board connecting
connector (CND)-Between smoothing capacitor (CB1 and CB2).
Power supply board connecting connector (52C)-Between electron­magnetic contactor (52C)
5) Connector (CN2) disconnection,
Check the connector insertion.
contact failure.
6) Instant power failure It happens by accident, and does not have the possibility to happen again.
4
When the 6th voltage decrease of direct bus bar is detected during being delay abnormality, it stops abnormally. In this time, the outdoor unit address No. and check code <4220> blinks alternately on the 4 digit digital display.
4230 Radiator panel shield temperature
1
When the radiator panel temperature thermistor (THHS) detects abnormality (1w detection) stops the outdoor unit once and restarts operation in 3minutes.
2
It is being delay to stop abnormally for 30minutes after the compressor stop. (PUMY-P125VMA : 10 minutes) Then, when SW1 is set, outdoor unit address No. and check delay code <4330> blinks alternately on the 4 digit digital display.
SW1 setting When the radiation shield temperature
3
21345678
on
thermistor (THHS) detects abnormality again (2nd detection) during delay abnormality, perform the same action as 1.
When the radiation shield temperature
4
thermistor (THHS) detects abnormality on 3rd time during delay abnormality, it stops abnormally. (PUMY-P125VMA : 5 minutes) Then, the outdoor unit address No. check code <4230> blinks alternately on the 4 digit digital display.
7) Lightening serge, single interruption
by external noise.
8) Direct bus-bar voltage shortage
It happens by accident, and does not have the possibility to happen again.
Replace the power supply board.
detecting circuit failure in power supply board
1) Outdoor fan motor lock Check the outdoor fan motor.
2) Outdoor fan motor trouble Check the outdoor fan motor.
3) Block of duct which cooled air passes
Check whether the air duct for cooling is opened.
4) Surrounding temperature-rise Check whether there is a heat source in surroundings of the outdoor unit. (Surroundings temperature upper limit is 46;)
5) Thermistor failure Check the resistance of thermistor.
1
(Use tester)
21345678
6) Thermistor input circuit failure in the
multi controller board
2
Change the SW1 to and check the temperature in radiation
on
shield temperature thermistor. When there is a big difference between the detected temp. and thermistor temp. replace the multi controller board.
Abnormality detecting temperature in radiation shield temperature thermistor
Abnormal temperature (;)
Type 125VMA 125YMA
85 84
44
on
21345678
on
21345678
When the compressor is interrupted again by over current after restarting in 3minutes, it stops and restarts in 3minutes. Perform the same action as 2 and 3.
5) Disconnection of connector and lead wire, and miss-wiring Between multi controller board (CN4)
and power supply board (CN4)
Start-up the compressor and check the status of interrupting.
When the compressor is not interrupted within 30seconds after restarting in 3minutes, clear the delay of limited abnormal stop and back to normal.
Display
Meaning and detecting method
Causes
Check points
(1) When the compressor stops (output signal stop) after immediately after output signal comes out and is interrupted abnormally.
When the above action 4 is repeated and the compressor is interrupted within 30seconds after 7th start-up (PUMY-P125VMA : after 15th start-up), or the compressor is interrupted during confined the current-carry, it stops abnormally. Then, the outdoor unit address No. and check delay code <4250> blinks alternately on the 4 digit digital display.
Generation of short-circuit current is assumed.
(5),6),7),12),13)) (2) After 5seconds of start-up, when the compressor stops by interruption, being delay and repeats to confine current-carry for 3minutes restart­up interruption to confine current-carry restart-up and becomes interruption-abnormality after approx. 18minutes from start-up.
(When the compressor is interrupted by over current during the operation)
The compressor is assumed not to start-up by torque shortage or lock. (5), 6), 7), 9), 10), 11), 12))
When over current limit is detected after 30seconds from start-up, the compressor stops and restarts in 3minutes.
(3) When the compressor stops after a while by the interception though the compressor starts once, and restarts in 3minutes.
The compressor is being delay to stop abnormally for 5minutes after the compressor stop.
(PUMY-P125VMA : 6minutes) Then, the outdoor unit address No. and check delay code <4350> blinks alternately on the 4 digit digital display.
SW1 setting
It is presumed to stop since the frequency goes up and the load grows though the compressor starts. (4), 5),
6), 7), 8)) Check the miss-wiring, terminal loosing and disconnection of connector and lead wire.
When the compressor is interrupted again within 2minutes after restarting in 3minutes, it stops abnormally. Then, the outdoor unit address No. and check delay code <4250> blinks alternately on the 4 digit digital display. PUMY-P125VMA : 6minutes, 4minutes.
Repair of defective points. (5), 11))
When the compressor is not interrupted within 2minutes
(PUMY-P125VMA : 3minutes) after restarting in 3minutes, it becomes the 1st detection and performs the same action as 1 and 2.
Check the resistance of IPM. In the case of abnormality, replace the gate ampere board and IPM. Check the resistance of diode stack.
6) IPM (intelligent power module) drive circuit in the gate amplifier defective
7) IPM (intelligent power module) drive signal output circuit defective, power factor detecting circuit failure in the multi controller board.
8) Current detection defective (AC,CT)
9) Compressor lock
10) Liquid sealing start-up of the compressor
11) Open-phase at the compressor side
12) IPM (intelligent power module) failure
13) Power supply board abnormality detecting circuit failure and IPM drive power supply circuit failure
In the case of abnormality, replace the diode stack.
When excluding of 456, Switch off and disconnect the connection of the compressor after confirming charge of main circuit electrolysis capacitor is discharged enough. Then, switch on and operate in no-load.
(1) When the compressor is interrupted again. Replace the power supply board when the compressor does not back to normal even if the gate amplifier board is replaced. Replace the multi controller board when the compressor does not back to normal even if the power supply board is replaced. (2) Check the balance of inverter output voltage. If it is unbalanced,··· Replace the power supply board when the compressor does not back to normal even if the gate ampere is replaced. Replace the multi controller board when the compressor does not back to normal even if the power supply board is replaced.
1
2
3
4
5
4
6
3
4
5
6
7
4250
PUMY-P125YMA PUMY-P125YMA
1
1) Single interruption by external noise.
IPM abnormality Over current limited
(When the compressor is interrupted by over current at its start-up.)
2) Single interruption by lightening serge
The interruption happens by accident. Since the interception only once returns automatically after restarting in 3minutes, the possibility to stop abnormally is very few.
When over current limit is detected within 30seconds from start-up, the compressor stops and restarts in 3minutes.
3) Power supply abnormality
Measure a receiving voltage and check the power supply capacity
While the compressor stops for 3minutes, confine the current-carry.
(a) Voltage decrease to 340V or less.
Check whether the phase is opened or not. Check from 4) to 13) by following procedure;
When SW1 setting during delay of interruption abnormality stop, the outdoor unit address No. and check delay code <4350> blinks alternately on the 4 digit digital display.
(b) Power supply open-phase
SW1 setting
(Current increase in the compressor by the voltage decrease)
4) Diode stack defective When it is opened-phase, same phenomenon occurs as power supply open-phase.
1
2
1
2
3
45
To be continued on the next page.
From the preceding page.
Display
4250
5101
Meaning and detecting method
Suction temperature thermistor (TH21) abnormality When controller detects short (high temp.)/open (low temp.) in thermistor during the operation, the operation stops and the operation changes to protect mode of restarting in 3minutes. If the thermistor does not recover in 3minutes, the operation stops abnormally. In this time, <5101> is displayed. Then, if the thermistor recover in 3minutes, it operates normally.
Short: Detected 90; or more Open: Detected —40; or less
Discharge temperature thermistor (TH1) abnormality
1
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
2
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5101> is displayed.
While the compressor is protected not to
3
restart in 3minutes, the unit is delayed abnormal stop. Then, the outdoor unit address No. and check delay code <1202> blinks alternately on the 4 digit digital display.
SW1 setting
For 10 minutes after starting compressor,
4
for defrosting or for 3minutes after recover
on
of defrosting, above-mentioned short/open are not detected.
Short: 216;or more (1k') Open: 0; or less (700k')
Note) When outer temperature thermistor (TH6) is 5; or less on cooling, open detecting is not determined as abnormality.
21345678
Causes
8
When not applying from 4 to 7, it
Check points
applies to 9) and 10). Check the compressor.
In case of 10), recheck the compressor again after 12 hours with former power supply.
PUMY-P125VMA
1) Stop valve of outdoor unit is closed.
2) Decrase of power supply voltage
3)
Looseness, disconnection or converse of compressor wiring connection
4) Defective fan of indoor/outdoor units
5) Short cycle of indoor/outdoor units
6) Defective input circuit of outdoor
Open stop valve.
1
2
Check facility of power supply.
3
Correct the wiring (U•V•W phase) to compressor.
Check indoor/outdoor fan.
4
Solve short cycle.
5
6
Replace outdoor controller board.
controller board
7) Defective compressor
1) Connector (CN20) contact failure Check whether the connector
7
Check compressor.
1
(CN20) in the indoor controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
Check whether the thermistor wiring
2
is disconnected or not.
3
0;···15k' 10;···9.6k' 20;···6.3k' 30;···4.3k' 40;···3.0k'
4) Detecting circuit failure in the indoor controller board
When there is no problem in above
4
mentioned 123,replace the indoor controller board.
1) Connector (TH1) contact failure Check whether the connector (TH1)
1
in the multi controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
2
Check whether the thermistor wiring is disconnected or not.
3
When the resistance is not below value, replace the thermistor. 0;··· about 700k' 10;··· about 410k' 20;··· about 250k' 30;··· about 160k'
4) Multi controller board input circuit failure
40;··· about 104k' Set the SW1 to
4
When the temperature in multi
21345678
on
controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
46
Display
5102
Meaning and detecting method
Liquid pipe temperature thermistor (TH22) abnormality
When the thermistor detects short/open during the operation, the operation stops and the operation changes to protect mode of restarting in 3minutes. If the thermistor does not recover in 3minutes, the operation stops abnormally. In this time, <5102> is displayed. Then, if the thermistor recover in 3minutes, it operates
normally. Short: Detected 90; or more Open: Detected -40; or less
Causes
1) Connector (CN21) contact failure Check whether the connector
1
Check points
(CN21) in the indoor controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure
2
Check whether the thermistor wiring is disconnected or not.
3
Check the resistance of thermistor;
0;···15k' 10;···9.6k' 20;···6.3k' 30;···4.3k' 40;···3.0k'
Low pressure saturation temperature thermistor (TH2) abnormality
1
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
2
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5102> is displayed.
While the compressor is protected not to
3
restart in 3minutes, the unit is delayed abnormal stop. Then, the outdoor unit address No. and check delay code <1211> blinks alternately on the 4 digit digital display.
SW1 setting
For 10 minutes after starting compressor,
4
21345678
on
for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.
Short: 100; or more (0.5k') Open: -46; or less (200k')
4) Detecting circuit failure in the indoor controller board
When there is no problem in above
4
mentioned 123,replace the indoor controller board.
1) Connector (TH2) contact failure Check whether the connector (TH2)
1
in the multi controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
2
Check whether the thermistor wiring is disconnected or not.
3
0;···15k' 10;···9.6k' 20;···6.3k'
30;···4.3k' 40;···3.0k'
21345678
4) Multi controller board input circuit failure
4
Set the SW1 to When the temperature in multi
on
controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
47
Display
Meaning and detecting method
5103 Gas pipe temperature thermistor (TH23)
abnormality
When the thermistor detects short/open after 3minutes-continuous thermo ON during cooling or dry operation, the operation stops and the operation changes to protect mode of restarting in 3minutes. If the thermistor does not recover in 3minutes, the the operation stops abnormally. In this time, <5103> is displayed. Then, if the thermistor recover in 3minutes, it operates normally.
Short: Detected 90; or more
Open: Detected -40; or less
Causes
1) Connector (CN29) contact failure Check whether the connector (CN29)
1
Check points
in the indoor controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
2
Check whether the thermistor wiring is disconnected or not.
3
0;···15k'
10;···9.6k' 20;···6.3k' 30;···4.3k' 40;···3.0k'
5105
Condenser outlet temperature thermistor (TH5) abnormality
1
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
2
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5105> is displayed.
While the compressor is protected not to
3
restart in 3minutes, the unit is delayed abnormal stop. Then, the outdoor unit address No. and check delay code <1205> blinks alternately on the 4 digit digital display.
SW1 setting
For 10 minutes after starting compressor,
4
21345678
on
for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.
Short: 88; or more (0.4k')
Open: -39; or less (115k')
4) Detecting circuit failure in the indoor controller board
4
When there is no problem in above mentioned 123,replace the indoor controller board.
1) Connector (TH5) contact failure Check whether the connector (TH5)
1
in the multi controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
2
Check whether the thermistor wiring is disconnected or not.
3
When the resistance is not below value, replace the thermistor.
0;···15k' 10;···9.6k' 20;···6.3k'
30;···4.3k' 40;···3.0k'
21345678
4) Multi controller board input circuit failure
4
Set the SW1 to
When the temperature in multi
on
controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
48
Display
5106
Meaning and detecting method
Outer temperature thermistor (TH6) abnormality
1
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
2
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5106> is displayed.
While the compressor is protected not to
3
restart in 3minutes, the unit is delayed abnormal stop. Then, the outdoor unit address No. and check delay code <1221> blinks alternately on the 4 digit digital display.
SW1 setting
4
For 10 minutes after starting compressor, for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.
Short: 88; or more (0.4k') Open: -39; or less (115k')
5110 PUMY-P125VMA:
Radiator panel temperature thermistor (THHS-A, THHS-B) abnormality
PUMY-P125YMA, PUMY-P125YMA
IPM radiator panel temperature thermistor (THHS) abnormality
When controller detects short/open in
1
thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes. When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
2
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5110> is displayed.
3
While the compressor is protected not to restart in 3minutes, the unit is delayed abnormal stop. Then, the outdoor unit address No. and check delay code <1214> blinks alternately on the 4 digit digital display.
SW1 setting
4
For 10 minutes after starting compressor, for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected. (PUMY-P125YMA, PUMY-P125YMA1)
PUMY-P125VMA:
Short:102; or more (2.9k') Open: -27; or less (950k')
21345678
on
on
21345678
Causes
1) Connector (TH6) contact failure Check whether the connector (TH6)
1
Check points
in the multi controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
Check whether the thermistor wiring
2
is disconnected or not.
3
When the resistance is not below value, replace the thermistor.
0;···15k' 10;···9.6k' 20;···6.3k' 30;···4.3k' 40;···3.0k'
21345678
4) Multi controller board input circuit failure
4
Set the SW1 to When the temperature in multi
on
controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
1:
1) Connector (THHS) contact failure Check whether the connector (THHS)
1
in the multi controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
Check whether the thermistor wiring
2
is disconnected or not.
3
When the resistance is not below value, replace the thermistor.
0;···180k' 10;···105k' 20;···63k' 30;···39k'
4) Multi controller board input circuit failure
40;···25k'
Set the SW1 to
4
When the temperature in multi
21345678
on
controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
PUMY-P125YMA, PUMY-P125YMA
Short:132; or more (1.2k') Open: -30; or less (1200k')
1:
49
Display
5201
Meaning and detecting method
Pressure sensor (63HS) abnormality
1
When detected pressure in high-pressure pressure sensor is 1MPa or less during the operation, the compressor stops and restarts operation in 3minutes.
2
When the detected pressure is 1MPa or less at just before of restarting, the compressor stops abnormally. In this time, <5201> is displayed.
For 3minutes after the compressor stops,
3
the unit delays to abnormal stop. Then, the outdoor unit address No. and check delay code <1402> blinks alternately on the 4digit digital display.
SW1 setting For 3minutes after starting compressor,
4
for defrosting or for 3minutes after recover of defrosting, abnormality is not determined as abnormality.
21345678
on
Causes
1) High-pressure pressure sensor failure
2) Internal pressure decrease by gas leakage
3) Connector contact failure, disconnection
4) Multi controller board input circuit failure
Check points
1
Check the high-pressure pressure sensor.
Check the internal pressure.
2
Check the high-pressure pressure
3
sensor.
Check the high-pressure pressure
4
sensor.
5300 Current sensor error
Abnormal if current sensor detects –1.5A to
1.5A during compressor operation. (This error is ignored in case of SW6-3 ON. (PUMY-P125VMA))
6600 Duplex address error
Detected error when transmission of unit with the same address is confirmed,
Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.
6602 Transmission processor H/W error
'' 1 '' shows on the transmission line though the transmission processor transmitted '' 0''.
Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.
1) Disconnection of compressor wiring
2) Defective circuit of current sensor on outdoor power board
1) There are 2units or more with the same address among the outdoor unit or indoor unit or lossnay controller, remote controller.
2) When noise has occurred in the transmission signal, and the signal has changed.
1) When the wiring for either of the indoor unit, the outdoor unit or lossnay transmission line is constructed or polarity is changed with the power supply turned on, the transmission waves change in case that the transmission data collides mutually. It causes to detect error.
2) Transmission processor circuit failure
Correct the wiring (U•V•W phase) to
1
compressor.
2
Replace outdoor power board.
Look for the unit, which is source of
1
abnormality with the same address. When the same address is found, correct the address and turn off power supply of outdoor unit, indoor unit, and lossnay for 2minutes or more as the same time. Then, turn on power supply.
Check the transmitted wave and the
2
noise on the transmission line.
When the transmission line is
1
constructed with the current flowed, turn off power supply of outdoor unit, indoor unit and lossnay for 2minutes or more as the same time. Then, turn on power supply.
Check the transmitted wave and the
2
noise on the transmission line.
3) When the transmission data has changed by the noise.
50
Display
6603 Transmission bus busy error
Meaning and detecting method
1
Over error by collision 1) The transmission processor cannot
Abnormality when the state, which cannot be transmitted by collision of transmission, is consecutive for 8 to 10minutes.
Causes
be transmitted since a short cycle voltage of the noise etc. mixes on the transmission line consecutively.
Check points
1
Check whether the transmission line of the indoor unit, fresh master, lossnay and remote controller is connected to the outdoor unit terminal board (TB7) for centralized controller or not.
6606
2
The state that data cannot to be output to the transmission line by the noise happens for 8 to 10minutes consecutively.
Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.
Signal communication error with transmission processor
Signal communication error between unit processor and transmission processor
Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.
2) The transmission volume increases and cannot be transmitted since the wiring method is mistaken and the routing technique to the terminal board (TB3) for the transmission line of the outdoor unit and the terminal board (TB7) for centralized control cannot be transmitted.
3) The share becomes high since the data exists together to other transmitted data by a defective repeater (function which connects and intercepts the transmission of controlling system and centralized control system), and it causes abnormal detection.
1) It happened since the noise and lightening serge that happened by chance had not normally transmitted the data of the unit/transmission processor.
2
Check whether the transmission line with the other refrigerant system of the indoor unit and lossnay is connected to the outdoor unit terminal board (TB3) for transmission or not.
3
Check whether the outdoor unit terminal board for transmission line (TB3) and for centralized controller (TB7) are connected or not.
4
Check the transmitted wave and the noise on the transmission line.
Turn off power supply of outdoor unit, indoor unit, and lossnay for 2minutes or more at the same time. Then, turn on power supply. It recovers normally at the malfunction that happens by chance. When same abnormality occurs again, it is defective of a generation former controller.
2) The address transmission from the unit processor was not normally transmitted by the hardware of transmission processor defective.
51
Display
6607
Meaning and detecting method No ACK Abnormality which controller of the
1
sending side detects when there is no answer (ACK) from other side though data was transmitted once. It is detected 6 times every 30seconds continuously.
Note) Address/Attribute displayed on the remote controller shows the controller, which did not send back replay (ACK).
Causes
Factor that not related to origin
1) Since the address switch was changed with the current passed, the unit in the last address does not exist.
2) Decline of transmission voltage and signal by transmission line tolerance over
· The furthest point···200m
· Remote controller line···(12m) (See page 18-27 for details)
3) Decline of transmission line voltage and signal by unmatched kind of line. Kind···Shield line-CVVS,CPEVS No shield···VCTF, VCTFK,
CVV, CVS, VVR, VVF, VCT Line diameter···1.25 e or more
4) Decline of transmission line voltage and signal by a number of over­connected units.
5) Miss operation of origin controller, which happens by chance.
6) Origin controller defective
Check points
1
Turn off power supply of outdoor unit, indoor unit fresh master and lossnay for 2minutes or more at the same time. Then, turn on power supply. It recovers normally at the malfunction that happens by chance.
Check the address switch in the
2
address, which occurs abnormality.
3
Check whether the transmission line is connected / loosen or not at origin. (Terminal board or connector)
Check whether the transmission line
4
tolerance is over or not.
Check whether the kind of
5
transmission line is mistaken or not. When there is any trouble from above
1-5, turn off power supply of outdoor unit, indoor unit and lossnay for 2minutes or more at the same time. Then, turn on power supply.
1) When the cause of displayed address and attribute is on the outdoor unit side
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the outdoor unit.)
2) When the cause of displayed address and attribute is on the indoor unit side
(The remote controller detects when there is no reply (ACK) on transmitting from the remote controller to the indoor unit.)
1) Contact failure of outdoor unit or indoor unit transmission line
2) Indoor unit transmission connector (CN2M) disconnection
3) Sending/receiving signal circuit failure in the indoor/outdoor unit
1) When operating with multi refrigerant system indoor units, the remote controller transmits the signal to the indoor unit after the other refrigerant system outdoor unit is turned off or turned on again in 2minutes, and detects abnormality.
2) Contact failure of remote controller or indoor unit transmission line.
3) Indoor unit transmission connector (CN2M) disconnection.
4) Sending/receiving signal circuit failure in the indoor unit or remote controller.
When there is not any trouble in single refrigerant system (1outdoor unit) from above1-5, controller defective in displayed address and attribute. When there is not any trouble in different refrigerant system (2outdoor unit or more) from above1-5, determine it after 6.
When the address, which should not
6
exist, is an origin, since there is the indoor unit which memorizes the address data, cancel the unnecessary address data by the manual setting function of remote controller. However, they are limited to the system, which sets the group between different refrigerant systems, or which fresh master /lossnay are connected.
When there is not any trouble from above 1-6, replace the displayed address/attribute controller board.
In this time, when the error does not recover to normal, the outdoor unit multi controller board (repeater circuit) defective is expected.
Check the recovery by replacing the multi controller board one by one.
52
Display
6607
Meaning and detecting method
3) When the cause of displayed address and attribute is on the remote controller side
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the remote controller unit.)
Causes
1) When operating with multi refrigerant system indoor units, the indoor units transmits the signal to the remote controller after the other refrigerant system outdoor unit is turned off or turned on again in 2minutes, and detects abnormality.
2) Contact failure of remote controller or indoor unit transmission line
3) Indoor unit transmission connector (CN2M) disconnection.
4) Sending/receiving signal circuit failure in the indoor unit or remote controller.
Check points
4) When the cause of displayed address and attribute is on the fresh master side
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the fresh master.)
5) When the cause of displayed address and attribute is on the lossnay side
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the lossnay.)
1) When synchronized operating with other refrigerant system fresh master, the indoor units transmits the signal to the fresh master after the fresh master and same refrigerant system outdoor unit is turned off or turned on again in 2minutes, and detects abnormality.
2) Contact failure of fresh master or indoor unit transmission line
3) Indoor unit or fresh master transmission connector (CN2M) disconnection.
4) Sending/receiving signal circuit failure in the indoor unit or fresh master.
1) When the lossnay power supply is Off, the indoor unit detects abnormality at signal transmitting to the lossnay.
53
Display
6607
Meaning and detecting method
Causes
2) When synchronized operating with other refrigerant system lossnay, the indoor units transmits the signal to the lossnay after the lossnay and same refrigerant system outdoor unit is turned off or turned on again in 2minutes, and detects abnormality
3) Contact failure of lossnay or indoor unit transmission line
4) Indoor unit transmission connector (CN2M) disconnection.
5) Sending/receiving signal circuit failure in the indoor unit or lossnay.
Check points
6608
6) When the controller of displayed address and attribute is not recognized
No response
Though there was a replay (ACK) of having received signal from the other side, it is the abnormality when the response command does not return. The sending side detects the abnormality continuously six times every 30 seconds. Note) Address/Attribute displayed on the remote controller shows the controller, which did not response.
1) Since the address switch was changed with the current passed, the unit in the last address does not exist.
2) Since the fresh master/lossnay address are changed after synchronized setting of fresh master / lossnay by the remote controller, abnormality is detected at transmitting from the indoor unit.
1) Transmission repeats the failure by the noise etc.
2) Decline of transmission voltage and signal by transmission line tolerance over.
· The furthest point···200m
· Remote controller line···(12m) (See page 18-27 for details)
3) Decline of transmission line voltage and signal by unmatched kind of line.
Kind···Shield wire-CVVS,CPEVS
No shield ···VCTF, VCTFK,
CVV, CVS, VVR, VVF, VCT wire diameter···1.25eor more
Check the transmission wave and
1
noise on the transmission line.
Turn off power supply of outdoor unit,
2
indoor unit and lossnay for 2minutes or more at the same time. Then, turn on power supply again. It recovers normally at the malfunction that happens by chance. When same abnormality occurs again, it is defective of displayed address and attribute.
4) Miss operation of origin controller, which happens by chance.
54
Display
Meaning and detecting method
Causes
Check points
6810 UR communication abnormality (UR: Unit
Remote controller) Communications between the unit remote controller and indoor unit is not normal.
When there is no display of address and attribute to the remote controller. (When detecting by the unit remote controller)
1) It is abnormality though the unit remote controller transmitted ''H'', when "L" reception is detected continuously three times.
2) It is abnormality when there is no response from the indoor unit for 3 minutes against to ''monitor request'' from the unit remote controller.
3) It is abnormality when there is no response 3times continuously from the indoor unit against to ''operation /setting'' from the unit remote controller.
When the cause of displayed address and attribute is on the indoor unit side.
1) It is abnormality though the indoor unit transmitted ''H'', when "L" reception is detected continuously three times.
2) It is abnormality when the indoor units cannot receive the transmission signal from the unit remote controller for 3minutes.
1) Contact failure of the unit remote controller transmission line in the unit remote controller or indoor unit.
2) Decline of transmission voltage and signal on the unit remote controller transmission line by the unit remote controller transmission line tolerance over
3) When the transmission signal of unit remote controller changes by noise.
4) Unit remote controller transmitting / receiving signal circuit failure in the unit remote controller or indoor unit.
1
Check whether the transmission line of the indoor unit or unit remote controller is connected / loosen or not.
Check whether the unit remote
2
controller transmission line tolerance is over or not.
Check the transmission wave and
3
noise on the transmission signal of unit remote controller.
When there is not any trouble from
4
above 1-3, replace the indoor controller board or unit remote controller.
Check of following conditions is available by LED1/LED2 in the indoor controller board.
· When LED1 and 2 blinks at the same time.
The indoor unit is transmitting to the unit remote controller.
· When only LED2 blinks. The unit remote controller is
transmitting to the indoor unit. Or, other indoor unit is transmitting to
the unit remote controller.
·When LED1 and 2 does not blink. The indoor unit and unit remote
controller is not transmitting.
6831 6834
6832 6833
Signal reception abnormality (Remote controller) Following symptoms are regarded as abnormality.
1) When the remote controller cannot receive the signal from indoor controller normally even once for 3 minutes
2) When sub-remote controller cannot receive the signal even once for 2 minutes
Signal transmission abnormality (Remote controller) Following symptoms are regarded as abnormality.
1) When sub-remote controller cannot transmit the signal to the transmission path for 6 seconds
2) When the remote controller cannot finish transmitting the signal for 30 times on end
Defect of the transmission and reception
1
circuit of the remote controller. Defect of the transmission and
2
reception circuit of the indoor controller board
Noise occurs on the transmission line
3
of the remote controller All remote controllers are set as
4
sub-remote controller.
Defect of the transmission and
1
reception circuit of the remote controller Noise occurs on the transmission line
2
of the remote controller There are two main remote controllers.
3
55
1~3
Perform a check of the remote controller. According to the results, perform the following disposals.
• When "RC OK" is displayed The remote controller is normal. Turn off the power supply and turn it
on again. If "HO" is displayed for 4 minutes or more, replace the indoor controller board.
• When "RC NG" is displayed Replace the remote controller.
• When "RC 6832 or 6833" or "ERC 00-66" is displayed These displays may be due to noise, etc.
4 Set one remote controller to main
remote controller and the other to sub-remote controller.
Display
7100
Meaning and detecting method
When connected total models of the indoor units exceed the specified level (130% of the outdoor unit models), error code <7100> is displayed.
Causes
1) Connecting total models of the indoor unit exceed the specified level.
125: Possible up to 163 (code 33)
Check points
1
Check the total models of connected indoor unit.
Check the model code registration
2
switch (indoor controller board SW2) of connected indoor unit.
7101 Capacity code error
When the connected indoor unit models cannot be connected, <7101> is displayed.
2) There is a mistake in the registration of model name code of the outdoor unit.
The indoor unit models is not possible to connect,
The indoor unit of 20-125(code 4-25) is possible to connect.
Check the model code registration switch (outdoor multi controller board SW4) of the outdoor unit.
Check the model code registration
1
switch (indoor controller board SW2) in the connected indoor unit.
The outdoor unit SW1 operation can
2
check model code of the connected indoor units.
Code of indoor unit No.1
Code of indoor unit No.2
Code of indoor unit No.3
Code of indoor unit No.4
Code of indoor unit No.5
Code of indoor unit No.6
Code of indoor unit No.7
21345678
on
21345678
on
21345678
on
21345678
on
21345678
on
21345678
on
21345678
on
7102 Number of connecting unit over
When the connecting unit exceeds a number of limitations, error code <7102> is displayed.
Even if the indoor unit is not connected, becomes <7102> is display.
0403 Serial communication error
Abnormal if serial communication between outdoor multi board and outdoor power board is defective.
Connecting unit exceeds a number of limitations. It is assumed abnormality excluding the following cases;
1) The indoor unit can be totally connected up to 8 units. The indoor unit can be connected up to 8 units
2) Ventilation unit connecting is only 1unit.
1 Breaking of wire or contact failure of connector CN2 2 Breaking of wire or contact failure of connector CN4 3 Defective communication circuit of outdoor power board 4 Defective communication circuit of outdoor multi board for power board
56
Code of indoor unit No.8
21345678
on
Check whether the connecting unit exceeds a number of limitations or not.
12 Check connection of each connector CN2, CN4.
3 Replace outdoor power board. 4 Replace outdoor multi board.
Display
7105 Address setting error
Meaning and detecting method
Address setting of the outdoor unit is wrong.
Causes
Addresses miss setting of the outdoor unit.
The outdoor unit is not set in 000 or in the range of 51-100.
Check points
Check the address setting of the outdoor unit. The address should be set in 000 or 51-100.
When the setting is out of the range, reset it, turn off power supply of the outdoor unit, indoor unit and lossnay for 2minutes or more at the same time, and turn on power supply again.
7111 When an old type remote controller for
Remote controller sensor abnormality In the case of network remote controller, it
is an abnormality when incapable response returns from the net work remote controller during the operation.
M-NET is used, and the remote controller sensor is specified (SW1-1 is ON).
Replace the remote controller to net work remote controller.
9-2. Remote controller diagnosis
• MA remote controller is equipped with the diagnosis function. Check the remote controller with this function when the unit does not operate with the remote controller.
(1)
Electric current marker
(2)
(1) First, check the electricity current maker.
If the correct voltage (DC 8.7~13V) is not supplied on the remote controller, the electric current marker will be lit. If the electricity current marker is not lit, check the remote controller wiring and the indoor units.
(2) Transfer to remote control diagnosis mode.
Hold down the CHECK button for five seconds or more to display the diagram on the left.
Press the FILTER button to commence diagnosis of remote controller.
(3)
a)
b)
(3) Remote controller diagnosis results.
a) The remote control is functioning correctly.
Check other possible causes as there are on problems with the remote controller.
b) The remote controller has a nonconformity.
The remote controller must be replaced. Error display 1 (“NG”) flashes to show a nonconformity in the transmitter-receiver circuit.
To be continued on the next page.
57
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
“ ” indicator: Appears when current is carried.
Symptom or inspection code Cause Inspection method and solution
Though the content of operation is displayed on the remote controller, some indoor units do not operate.
• The power supply of the indoor unit is not on.
The address of the indoor units in same group or the remote controller
is not set correctly.
The group setting between outdoor units is not registered to the remote
controller.
• The fuse on the indoor unit controller board is blown.
• Check the part where the abnormality occurs.
1 The entire system 2 In the entire refrigerant system 3 In same group only 4 One indoor unit only
<In case of the entire system or in the entire refrigerant system>
Check the self-diagnosis LED
of the outdoor unit.
• Check the items shown in the left that are related to the outdoor unit.
<In case of in same group only or one indoor unit only>
• Check the items shown in the left that are related to the indoor unit.
Though the indoor unit operates, the display of the remote controller goes out soon.
• The power supply of the indoor unit is not on.
• The fuse on the indoor unit controller board is blown.
( ) is not displayed on the remote controller.
(M-NET remote controller
is not fed.)
• The power supply of the outdoor unit is not on.
The number of connected indoor unit in the refrigeration system is over
the limit or the number of connected remote controller is over the limit.
M-NET remote controller is connected to MA remote controller cable.
• The transmission line of the indoor/outdoor unit is shorted or down.
• M-NET remote controller cable is shorted or down.
"HO" keeps being displayed or it is displayed periodically. ("HO" is usually displayed for 3 minutes at the longest after the power supply of the outdoor unit is on.)
• The power supply for the feeding expansion unit for the transmission line is not on.
• The address of the outdoor unit remains "00".
The address of the indoor unit or the remote controller is not set correctly.
• MA remote controller is connected to the transmission line of the indoor/outdoor unit.
The remote controller does not operate though ( ) is displayed.
• The transmission line of the indoor/outdoor unit is connected to TB15.
• The transmission line of the indoor/outdoor unit is shorted, down or badly contacted.
From the preceding page.
a)
Potential problems other than those diagnosed for the remote controller.
a) Single transmission not possible if error display 2 (“6832
or 6833”) flashes. There is “noise” on the transmission line, or damage of other remote controller for the indoor units can be considered. Check the transmission path and other controller
b)
• When the number of data errors generated is 02.
Remote controller transmission data Transmission data at transmission path
9-3. Remote controller trouble
b) Data error has occurred when error display three shows
“ERC” and number of data errors. Number of generated data error (maximum 66 errors). The number of generated data error stands for the difference in the number of bits of transmitted data from the remote controller and the actual number of bits that were transmitted along the transmission path. If this error occurs, “noise”, etc., is interfering with the transmission data. Check the transmission path.
(4) Cancel the remote controller diagnosis.
Hold down the CHECK button for five seconds or more to cancel the remote controller diagnosis. The “HO” operation lamp will flash, and the display screen will rectum to the status before remote controller diagnosis in approximately 30 seconds.
(1) For M-NET remote controller systems
58
Symptom Even the cooling (heating)
operation selection button is pressed, the indoor unit cannot be operated. The auto vane runs freely.
Fan setting changes during heating.
Fan stops during heating operation. Fan does not stop while operation has been stopped. No setting of fan while start SW has been turned on.
Indoor unit remote controller shows “HO” indicator for about two minutes when turning ON power supply.
Drain pump does not stop while unit has been stopped. Drain pump continues to operate while unit has been stopped.
Display of remote controller "Cooling (Heating)" blinks
Normal display
Normal display
"Defrost "
Light out
STAND BY
“HO” blinks
Light out
CAUSE The indoor unit can not cool (heat) if other indoor units are heating (cooling).
Because of the control operation of auto vane, it may change over to horizontal blow automatically from the downward blow in cooling in cause the downward blow operation has been continued for one hour. At defrosting in heating, hot adjusting and thermostat OFF, it automatically changes over to horizontal blow.
Ultra-low speed operation is commenced at thermostat OFF. Light air automatically change over to set value by time or piping temperature at thermostat ON.
The fan is to stop during defrosting.
Fan is to run for one minute after stopping to exhaust residual heat (only in heating).
Ultra-low speed operation for 5 minutes after SW ON or until piping temperature becomes 35°C. There low speed operate for 2 minutes, and then set notch is commenced. (Hot adjust control) System is being driven.
Operate remote controller again after “HO” disappears.
After a stop of cooling operation, unit continues to operate drain pump for three minutes and then stops it.
Unit continues to operate drain pump if drainage is generated, even during a stop.
(2) For MA remote controller systems
Symptom or inspection code Cause Inspection method and solution
Though the content of operation is displayed on the remote controller, some indoor units do not operate.
Though the indoor unit operates, the display of the remote controller goes out soon.
( ) is not displayed on the remote controller. (MA remote controller is not fed.)
"HO" keeps being displayed or it is displayed periodically. ("HO" is usually displayed for 3 minutes at the longest after the power supply of the outdoor unit is on.)
The
remote controller does not
operate though ( ) is displayed.
• The power supply of the indoor unit is not on.
• Wiring between indoor units in same group is not finished.
• The indoor unit and Slim model are connected to same group.
• The fuse on the indoor unit controller board is blown.
• The power supply of the indoor unit (Master) is not on.
• In case of connecting the system controller, the setting of the system controller does not correspond to that of MA remote controller.
• The fuse on the indoor unit (Master) controller board is blown. The remote controller is not fed until the power supply of both indoor unit
and outdoor unit is on and the start-up of both units is finished normally.
• The power supply of the indoor unit is not on.
• The power supply of the outdoor unit is not on.
• The number of connected remote controller is over the limit (Maximum: 2 units) or the number of connected indoor unit that is over the limit (Maximum: 16 units).
The address of the indoor unit is "00" and the address for the outdoor
unit is the one other than "00".
The transmission line of the indoor/outdoor unit is connected to TB15.
• MA remote controller is connected to the transmission line of the indoor/outdoor unit .
• The remote controller cable is shorted or down.
• The power supply cable or the transmission line is shorted or down.
• The fuse on the indoor unit controller board is blown.
• The power supply of the outdoor unit is not on.
• The power supply of the feeding expansion unit for the transmission line is not on.
• The setting of MA remote controller is not main remote controller, but sub-remote controller.
• MA remote controller is connected to the transmission line of the indoor/outdoor unit
• The power supply of the indoor unit (Master) is not on.
• The transmission line of the indoor/outdoor unit is connected to TB15.
• The transmission line of the indoor/outdoor unit is shorted, down or badly contacted.
•The fuse on the indoor unit controller board is blown.
.
• Check the part where the abnormality occurs.
1 The entire system 2 In the entire refrigerant system 3 In same group only 4 One indoor unit only
<In case of the entire system or in the entire refrigerant system>
Check the self-diagnosis LED
of the outdoor unit.
• Check the items shown in the left that are related to the outdoor unit.
<In case of in same group only or one indoor unit only>
• Check the items shown in the left that are related to the indoor unit.
9-4. The following Symptom do not represent trouble (emergency)
59
9-5. INTERNAL SWITCH FUNCTION TABLE
9-5-1. Outdoor unit internal switch function table (PUMY-P125VMA)
Switch
SW U1 1st digit
SW U2 2nd digit
SW1 Digital Display Switching
Step
Rotary switch
1~8
0
1
9
2
8
3
7
4
6
5
SWU2
(2nd digit)
Function
(1st digit)
ON
OFF
0
1
9
2
8
3
7
4
6
5
SWU1
1
2345678
W The address automatically becomes "100" if it is set as "01~50"
Operation in Each Switch Setting
ON OFF When to Set
Before turning the power on
Can be set either during operation or not.
Remarks
<Factory Settings>
0
1
9
2
8
3
7
4
6
5
SWU2
(2nd digit)
SWU1
(1st digit)
<Factory Settings>
ON
OFF
1
2345678
0
1
9
2
8
3
7
4
6
5
SW2 function Switching
Outdoor unit
SW3 Trial operation
SW4 Model Switching
Selects operating system startup
1
Connection Information Clear Switch
2
Abnormal data clear switch input
3
Refrigerant Volume Adjustment Operation
4
During the FAN or COOL mode, and thermo - OFF
5
or OFF in heating operation, set the opening of linear expansion valve on indoor unit.
6
During the FAN or COOL mode, and thermo - OFF in heating operation, set the opening of linear expansion valve on indoor unit.
7
Forced defrost
8
Defrost detection switching
9
Defrost disabled time selection
10
Vacuum operation protection (error code 1505) is not detected.
Enable/disable operation from outdoor
1
unit ON/OFF from the outdoor unit.
2
1~4
Service ref.
PUMY-P125VMA
SW4
ON
OFF
1
Clear Clear abnormal data Run adjustment mode.
Active
Active
Forced defrost
Cumulative 60 min.
Active
Enable ON
234
Start upDoesn´t start up Do not clear Normal Normal
Inactive
Inactive
Normal
Continuous 30 min.
(ordinary) Inactive
Disable OFF
Before turning the
<Factory Settings>
power on
OFF to ON any time after the power is turned on.
Can be set during compressor stopping.
OFF
While unit stopping.
OFF ➔ ON, during compressor running in heating mode.
While unit stopping.
Any time after the
<Factory Settings>
power is turned on.
w1
<Factory Settings> Set for each capacity.
Before the power is turned on.
ON
1
2345678910
ON
OFF
1
2
1
Auto Change Over from Remote Controller
2
Fixing the indoor units linear expansion valve opening
3
Fixing the outdoor unit electronic expansion valve opening.
Enable fixing at the desired frequency
SW5 function switching
4
Maintain outdoor fan at fixed speed
5
and ignore outdoor temperature sensor abnormality
Ignore refrigerant filling abnormality
6 7
Switching the target discharge pressure (Pdm)
8
Switching the target evaporation temperature (ETm)
1
SW6 function switching
Switching the Input Current Limit Level
2
Switching the High Pressure Limit Level
3
Ignore current sensor error
w1 For the system utilizing R-Converter units (PAC-SF29LB), SW3 trial operation function is not available.
Enable Fix
Disable
Normal
Fix Normal Enable Disable
Active
Active Pdm switching ETm switching 2 Amp down
0.2 MPS up Active
Inactive
Inactive Normal Normal Normal Normal Inactive
60
Before the power is turned on.
OFF ON while compressor is not operating
Any time after the power is turned on.
<Factory Settings>
ON
OFF
While unit stopping.
Can be set when off or during operation
Before turning the power on While unit stopping While unit stopping
<Factory Settings>
ON
OFF
1
2345678
1
2345678
Outdoor unit
Switch
SW U1 1st digit
SW U2 2nd digit
SW U3 3rd digit
SW1 Digital Display Switching
SW2 function Switching
SW5 function switching
SW3 Trial operation
SW4 Model Switching
Step
Operation in Each Switch Setting
ON OFF When to Set
Remarks
Before turning the power on
Before the power is turned on.
Before the power is turned on.
Can be set when off or during operation
SWU3
(3rd digit)
Rotary switch
1 2 3 4 5
6
7
8 9
10
1
2
1
2
3
4 5
6 7 8
Function
1~8
1~4
Can be set either during operation or not.
Before turning the power on
While unit stopping.
Any time after the power is turned on.
OFF to ON any time after the power is turned on.
Can be set during compressor stopping.
Active
Active
Active
Enable
Inactive
Inactive
Active
Active Pdm switching ETm switching
Inactive
Inactive Normal Normal
ON
Fix
Enable
Fix
OFF
Disable
Inactive
Start upDoesn´t start up
Clear
Do not clear
Normal Normal
Normal
Disable
Normal
Fix Normal Enable Disable
Normal
Continuous 30 min.
(ordinary)
Clear abnormal data Run adjustment mode.
Selects operating system startup Connection Information Clear Switch Abnormal data clear switch input Refrigerant Volume Adjustment Operation During the FAN or COOL mode, and thermo - OFF
or OFF in heating operation, set the opening of linear expansion valve on indoor unit.
During the FAN or COOL mode, and thermo - OFF in heating operation, set the opening of linear expansion valve on indoor unit.
Forced defrost
Cumulative 60 min.
Forced defrost
Defrost detection switching Defrost disabled time selection
Vacuum operation protection (error code 1505) is not detected.
Enable/disable operation from outdoor unit
ON/OFF from the outdoor unit.
<Factory Settings>
<Factory Settings>
<Factory Settings>
<Factory Settings>
<Factory Settings>
<Factory Settings> Set for each capacity.
PUMY-P125YMA :
Fix the operation frequency
PUMY-P125YMA
1 :
Auto Change Over from Remote Controller Fixing the indoor units linear expansion
valve opening Fixing the outdoor unit electronic
expansion valve opening. Enable fixing at the desired frequency Maintain outdoor fan at fixed speed
and ignore outdoor temperature sensor abnormality
Ignore refrigerant filling abnormality Switching the target discharge pressure (Pdm) Switching the target evaporation temperature (ETm)
0
1
2
3
4
5
6
7
8
9
SWU2
(2nd digit)
0
1
2
3
4
5
6
7
8
9
SWU1
(1st digit)
0
1
2
3
4
5
6
7
8
9
SWU3
(3rd digit)
0
1
2
3
4
5
6
7
8
9
SWU2
(2nd digit)
0
1
2
3
4
5
6
7
8
9
SWU1
(1st digit)
0
1
2
3
4
5
6
7
8
9
1
ON
OFF
2345678
1
ON
OFF
2345678
1
ON
OFF
2345678
1
ON
OFF
234
1
ON
OFF
2345678910
1
ON
OFF
2
OFF ➔ ON, during compressor running in heating mode.
OFF ON while compressor is not operating
OFF ON while compressor is not operating
While unit stopping.
While unit stopping.
Service ref.
SW4
PUMY-P125YMA PUMY-P125YMA1
w1 For the system utilizing R-Converter units (PAC-SF29LB), SW3 trial operation function is not available.
w1
9-5-2. Outdoor unit internal switch function table (PUMY-P125YMA, PUMY-P125YMA1)
61
9-6. Outdoor unit input/output connector
CN51
CN3S
X
5 4 3
Distant control board
External output adapter
Outdoor unit control board
Relay circuit
Maximum cable length is 10m
Lamp power
Y
X
X Y
L
1
L2
L1 : Error display lamp L
2 : Compressor operation lamp
X, Y : Relay (Coil standard of 0.9W or less for DC 12V)
Preparations in the field
1 2
External output adapter
Outdoor unit control board
Maximum cable length is 10m
X : Comp ON/OFF ON : Comp OFF
OFF : Normal
Preparations in the field
CN3D
X
Y
X
Y
SW1
SW2
1 2
3
Distant control board
External output adapter
Outdoor unit control board
Relay circuit
Maximum cable length is 10m
Lamp power
X, Y : Relay (DC1mA)
For the system utilizing R-Converter units (PAC-SF29LB), the following systems are not available.
Group operation system, centralized controller, group remote controller, etc. (See the installation manul of R-Converter units.)
For the system utilizing R-Converter units (PAC-SF29LB), the following functions are not available.
Test run (SW3), auto change over, auto change over (external signal). (See the installation manul of R-Converter units.)
Preparations in the field
SW1
SW2
PUMY-P125YMA PUMY-P125VMA PUMY-P125YMA
1
PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA
1
ON
Cooling
Heating
Validity of SW1
OFF
Heating Cooling
Invalidity of SW1
State (CN51)
Comp ON/OFF (CN3S)
Auto change over (CN3D)
62
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50 Temperature (:)
Resistance (K")
M
4
6
2 3
5
1
Blue
Brown
Yellow
Orange
Red
White
Expansion valve (LEV(A), SLEV)
Parts name
Check points
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
Disconnect the connector then measure the resistance using a tester. (
Part wiring temperature
20:)
•Thermistor (TH1) <Discharge temperature detection>
•Thermistor (TH2) <Low pressure saturated temperature detection>
•Thermistor (TH5) <Pipe temperature detection / judging defrost>
•Thermistor (TH6) <Outdoor temperature detection>
•Thermistor (THHS A/B) <Radiator panel>
PUMY-P125VMA
•Thermistor (THHS) <IPM radiator panel temperature thermistor detection>
PUMY-P125YMA,YMA
1
Normal
160k"~410k"
4.3k"~9.6k"
TH1 TH2 TH5 TH6
Abnormal
Open or short
Measure the resistance between the terminals using a tester. (Part wiring temperature 20C°)
4-WAY COIL (21S4)
Normal
1430"
Normal
(1) - (5)
White - Red
(2) - (6)
Yellow - Brown
(3) - (5)
Orange - Red
(4) - (6)
Blue - Brown
Abnormal
Abnormal
150" ±10%
Open or short
Normal
1970"
Abnormal
Open or short
Open or short
Measure the resistance between the terminals using a tester. (Part wiring temperature 20C°)
SOLENOID COIL (SV1)
Measure the resistance between the terminals using a tester. (Part wiring temperature 20C°)
FAN MOTOR (MF1,2)
Normal
107.5" ±10%
128.0" ±10%
Motor lead wire
Abnormal
Open or short
White — Blue Blue — Red
Red
White
Blue
Orange
Protector
Opening and closing temperature of protector. Open: 135i5°C (Fan motor OFF) Close: 86i15°C (Fan motor ON)
THHS A/B THHS
39k"~105k"
9-7. HOW TO CHECK THE PARTS
PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA1
<Thermistor feature chart>
Low temperature thermistors
•Thermistor (TH2) <Low pressure saturated temperature detection>
•Thermistor (TH5) <Pipe temperature detection / judging defrost>
•Thermistor (TH6) <Outdoor temperature detection> Thermistor R0 = 15k' ±3%
B constant = 3480k' ±2%
R 0: 15k'
10: 9.6k' 20: 6.3k' 25: 5.2k'
t =15exp{3480(
273+t – 273
1
1
30: 4.3k'
)}
40: 3.0k'
63
To be continued on the next page.
200
150
100
50
0
25 50 75 100110 125
Temperature (:)
Resistance (K")
500
400
300
200
100
0
25
50 75 100 120
Temperature (:)
Resistance (K")
200
150
100
50
0
25 50 75 100 125
Temperature (:)
Resistance (K")
From the preceding page.
PUMY-P125VMA
Medium temperature thermistor
•Thermistor (THHS A/B) <Radiator panel> Thermistor R50 = 17k' ±2%
B constant = 4150k' ±3%
1
t =17exp{4150(
R
1
273+t – 323
)}
0: 180k' 25: 50k' 50: 17k' 70: 8k' 90: 4k'
PUMY-P125YMA, PUMY-P125YMA
1
Medium temperature thermistor
•Thermistor (THHS) <IPM radiator panel temperature thermistor detection> Thermistor R50 = 17k' ±2%
B constant = 4170k' ±3%
1
t =17exp{4170(
R
1
273+t – 323
)}
0: 180k' 25: 50k' 50: 17k' 70: 8k' 90: 4k'
High temperature thermistor
•Thermistor (TH1) <Discharge temperature detection> Thermistor R120 = 7.465k' ±2%
B constant = 4057k' ±2%
1
t =7.465exp{4057(
R 20: 250k'
30: 160k' 40: 104k' 50: 70k' 60: 48k'
1
273+t – 393
)}
70: 34k' 80: 24k' 90: 17.5k' 100: 13.0k' 110: 9.8k'
64
A
E
D
C
B
Closing
Opening
Completely sealed (80-100 pulses)
Number of pulses
Valve fully open at 2,000 pulses
Valve position (volume)
Expansion valve (LEV(A), SLEV: Outdoor unit)
M
LEV(A), SLEV
Blue
{
4
{
3
{
2
{
1
{
4
{
3
{
2
{
1
2 5 1 3 4 6
6 5 4 3 2 1
BRN RED BLU ORN YLW WHT
Brown Yellow
Red
White
Orange
1
5
2 3
6
4
Relay connector (Only LEV(A))
Controller board
DC12V
Drive circuit
Connector (CN60)
(LEV(A), SLEV)
11
Notes on expansion valve action
• LEV(A), SLEV to stepping motor ON/OFF after outdoor controller board has received pulse signal.
• The valve position can be changed according to the pulse signal number ratio. <connection between the LEV(A), SLEV and the outdoor controller board>
Note: Because the numbers of the relay connector and the connector on the controller board side are different, wiring work
must rely on the colors of the wires.
<Output pulse signal and valve action>
Valve closing:1➔2➔3➔4➔1 Valve opening:4➔3➔2➔1➔4
The address of the pulse output is shifted using the procedures mentioned earlier.
w1. All output phase will turn OFF when the LEV(A), SLEV
stops operating.
2. When the output phase is terminated or when the phase
Output(phase)
{1 {2 {3 {4
ON
ON OFF OFF
2 LEV(A), SLEV action
Output
1
23
OFF
ON ON
OFF
OFF OFF
ON ON
4
ON OFF OFF
ON
shift is not according to frequency, the motor rotation will become irregular, causing the motor to vibrate or lockup.
w When the power supply is on, the closing signal of 2,200
• The noise can be heard by resting your ear on the handle
65
pulse will be transmitted to decide the position of the valve.
The valve position can be determined when point A is
reached.
The LEV(LEV(A), SLEV) will not vibrate or make noise when the valve is operating smoothly. However, when the number of pulses change from E to A ,or if the valve lockup, there may be more noise than under normal circumstances.
of a screwdriver that is pressed against the top of the LEV(LEV(A), SLEV) valve.
To be continued on the next page.
Problem Check point Corrective measure
Remove the connector from the controller board and connect diagnostic LEDs.
Pulses will be issued for 10 seconds when the power is turned on. It indicates that there is an abnormality in the operating circuit if any LEDs don't turn on or off.
If the linear expansion valve (indoor unit) or electronic expansion valve (outdoor unit) becomes locked and the motor is still operating, the motor will emit a clicking noise and will not function. This clicking noise indicates an abnormality.
Use an all-purpose electrical meter to measure the resistance between the different coils (red-white, red-orange, brown-yellow, brown-blue). Normal resistance is within a range of 150'±10%.
In order to check the linear expansion valve, operate one indoor unit in the fan mode and another in the cooling mode. Then, use the outdoor multi controller board to operate the monitor and check the pipe temperature of the indoor unit (liquid pipe temperature). The linear expansion valve should be fully closed when the fan is operating. The temperature measured by the temperature sensor will drop if there is any leakage. If the measured temperature is significantly lower than that on the remote controller, this indicates that the valve is not closed. It is not necessary to replace the linear expansion valve if the leak of refrigerant is small and does not cause a malfunction.
1 Check improperly connected connector terminals and the wire colors. 2 Remove the connector on the controller board side and check electrical
conductance
Malfunction in microp­rocessor operating circuit
Locked expansion valve
Short circuit or broken circuit in expansion valve motor coil
Valve does no close completely
Incorrect connection or connection failure
Replace the indoor unit controller board or Replace the outdoor multi controller board.
Replace the linear expa­nsion valve or electronic expansion valve
Replace the linear expa­nsion valve or electronic expansion valve
Replace the linear expa­nsion valve if there is a major leak of refrigerant.
Continuity check of wrong part.
6 5 4 3 2 1
1k" LED
Temperature sensor
<liquid pipe>
Linear expansion valve
From the preceding page.
3 Troubleshooting
66
0
1
2
3
4
5
6
7
8
9
101112131415161718192021222324252627282930
SW1 setting
12345678
00000000
10000000
01000000
11000000
00100000
10100000
01100000
11100000
00010000
10010000
01010000
11010000
00110000
10110000
01110000
11110000
00001000
10001000
01001000
11001000
00101000
10101000
01101000
11101000
00011000
10011000
01011000
11011000
00111000
10111000
01111000
Relay output display
Check display
Indoor unit check status
Protection input
Protection input
Protection input
Abnormality delay display 1
Abnormality delay display 2
Abnormality delay display 3
Abnormality delay history 1
Abnormality delay history 2
Abnormality delay history 3
Abnormality code history 2
Abnormality code history 3
Abnormality code history 4
Abnormality code history 5
Abnormality code history 6
Abnormality code history 7
Abnormality code history 8
Abnormality code history 9
Cumulative time
Cumulative time
Outdoor unit operation display
Indoor unit operation mode
Indoor unit operation display
Capacity code (No. 1 indoor unit)
Capacity code (No. 2 indoor unit)
Capacity code (No. 3 indoor unit)
Capacity code (No. 4 indoor unit)
Capacity code (No. 5 indoor unit)
1
Compressor operation
No.1 unit check
TH1 abnormality
TH1 abnormality delay
TH1 abnormality delay
2
52C
No.2 unit check
TH2 abnormality
TH2 abnormality delay
TH2 abnormality delay
3
21S4
No.3 unit check
TH6 abnormality
Indoor unit capacity
TH6 abnormality delay
TH6 abnormality delay
4
SV
No.4 unit check
IPM abnormality
TH5 abnormality
Over capacity
IPM abnormality delay
TH5 abnormality
delay
IPM abnormality delay
TH5 abnormality delay
7
No.7 unit check
5
No.5 unit check
6
No.6 unit check
THHS abnormality
THHS abnormality delay
THHS abnormality delay
8
Lighting always
No.8 unit check
63HS abnormality
63HS abnormality delay
ON: light on OFF: light off
•When abnormality occurs, check display.
Check: light on Normal: light off
Display input microprocessor
protection (abnormality)
Display all abnormalities
remaining in abnormality
delay
Display all abnormalities
remaining in abnormality
delay history
•Display abnormalities up to
present (including abnormality
terminals)
•History record in 1 is the
latest; records become older
in sequence; history record
in 10 is the oldest.
Display of cumulative
compressor operating time
Thermo ON : light on Thermo OFF : light off
•Display of indoor unit
capacity code
•The No. 1 unit will start from
the address with the lowest
number
Notes
Alternating display of addresses
0000-9999 and abnormality code
(including abnormality delay code)
0~9999(unit::1-hour)
0~9999(unit::10-hour)
0~255
Excitation Current
No.1 unit mode
No.1 unit operation
Restart after 3 minutes
No.2 unit mode
No.2 unit operation
Compressor operation
No.3 unit mode
No.3 unit operation
Abnormality(detection)
No.4 unit mode
No.4 unit operation
No.5 unit mode
No.5 unit operation
No.6 unit mode
No.6 unit operation
No.7 unit mode
No.7 unit operation
No.8 unit mode
No.8 unit operation
0000~9999 (Alternating display of addresses and error code)
Display mode
Display on the LD1 (display data)
No.
Delay code
1202
1205
1208
1211
1214
1221
Delay code
1402
1600
1601
4165
4320
4330
4350
Abnormality delay
Discharge temperature abnormality
Discharge temperature sensor (TH1) abnormality
Intake outlet temperature sensor (TH5) abnormality
Compressor internal thermostat abnormality
Radiator panel thermistor (THHS) abnormality
Outside air temperature sensor (TH6) abnormality
Abnormality delay
High-pressure abnormality
Pressure sensor (63HS) abnormality
Over charge refrigerant abnormality
Insufficient refrigerant abnormality
Power synchronization signal abnormality
Radiator panel temperature abnormality
IPM abnormality
Abnormality in the
number of linked units
High-pressure
abnormality delay
High-pressure
abnormality delay
High-pressure
abnormality
Discharge temperature
abnormality
Address double
setting abnormality
Discharge temperature
abnormality delay
Discharge temperature
abnormality delay
Internal thermostat
abnormality delay
Internal thermostat
abnormality delay
Inner thermostat
abnormality
Radiator panel
abnormality
Radiator panel
overheating delay
Radiator panel
overheating delay
Vacuum operation
abnormality
Power synchronization
signal abnormality
Restrict power
IPM abnormality
Power synchronization
signal abnormality delay
Restrict power IPM
abnormality delay
Refrigerant over
charge delay
Refrigerant over
charge abnormality
Refrigerant over charge
abnormality delay
Restrict power IPM
abnormality delay
Power synchronization
signal abnormality delay
Insufficient voltage
abnormality
63HS sensor
abnormality delay
Insufficient voltage
abnormality delay
Insufficient voltage
abnormality delay
Saturation temperature of suction pressure
sensor (TH2) abnormality
Frequency converter insufficient
wiring voltage abnormality
Cooling : light on Heating: light flashing
Stop fan: light off
Abnormality code history 10
(the oldest)
Abnormality code history 1
(the latest)
Single-phase
current delay(CT)
Single-phase
current delay(CT)
Indoor unit
address error
Outdoor unit
address error
9-8. OUTDOOR UNIT FUNCTIONS
SW:setting
0....OFF
1....ON
67
Notes
•Display of indoor unit
operating mode
Light on/light off
Input: light off No input: light on
8
7
3-min.delay/no
6
Heating
thermo
OFF
Excitation current/no
5
Heating
thermo
ON
Refrigerant pull back/no
4
Cooling
thermo
OFF
DEFROST/NO
Display on the LD1 (display data)
3
Cooling
thermo
ON
Abnormal/Normal
Display of communication demand capacity
PUMY-P125VMA
PUMY-P125VMA
PUMY-P125VMA
Display of actual operating frequency
Display of target frequency
Display of number of outdoor
fan control steps (target)
Display of opening pulse of
outdoor SLEV and indoor LEV
Display of outdoor subcool
(SC) data and detection data
from high-pressure sensor and
each thermistor
2
Heating/Cooling
1
OFF Fan
ON/OFF
0~255
Demand junction
0.0~50.0 (A)
Display mode
IC1 operation mode
IC2 operation mode
IC3 operation mode
IC4 operation mode
IC5 operation mode
OC operational mode
External connection status
Communication demand capacity
Compressor operating current
SW1 setting
11111000
12345678
00000100
313233343536373840414564656667686970717273747576777880818283848586
No.
11000100
10000100
01000100
01100100
00100100
10100100
00010100
0.0~50.0 (A)
0~500 (V)
0~FF(16 progressive)
0~255
0~20
step number (cooling)
control
Input current of outdoor unit
DC bus voltage
Operational frequency
Target frequency
Outdoor fan control step number
EER fan
OC SLEV opening pulse
10110100
10010100
00000010
11000010
10000010
01000010
00100010
68
0~2000
IC1 LEV Opening pulse
IC2 LEV Opening pulse
IC3 LEV Opening pulse
IC4 LEV Opening pulse
IC5 LEV Opening pulse
High-pressure sensor (Pd)
11100010
01100010
10100010
00010010
10010010
01010010
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
TH1(Td)
TH2(ET)
TH6
TH5
THHS
IC1 TH23
IC2 TH23
IC3 TH23
IC4 TH23
IC5 TH23
IC1 TH22
00110010
10110010
01110010
00001010
11001010
10001010
01001010
01101010
00101010
10101010
11010010
IC2 TH22
11101010 87
Notes
Display of outdoor subcool
(SC) data and detection data
from high-pressure sensor and
each thermistor
678
45
3
step data
subcool
Display of target
Display of indoor SC/SH data
Display of discharge superheat data
Display of all control target data
Display of actual frequency at time of abnormality delay
Display of fan step number at time of abnormality delay
Display of opening pulse outdoor SLEV
and indoor LEV at time of abnormality
delay
Display on the LD1 (display data)
2
1
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
Display mode
IC3 TH22
IC4 TH22
IC5 TH22
IC1 TH21
IC2 TH21
IC3 TH21
IC4 TH21
12345678
00011010
10011010
01011010
11011010
00111010
SW1 setting
8889909192939495969798
No.
10111010
0~4
IC5 TH21
Outdoor SC (cooling)
Target subcool step
01111010
11111010
00000110
10000110
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
during heating: subcool (SC)/during cooling: superheat (SH)
IC1 SC/SH
IC2 SC/SH
IC3 SC/SH
01000110
11000110
00100110
99
100
-99.9~999.9
Pdm(0.0~22.0)
IC4 SC/SH
IC5 SC/SH
Discharge superheat
Target Pd display (heating)
10100110
01100110
11100110
10010110
101
102
103
ETm(-1.0~8.0)
SCm(0.0~10.0)
SCm/SHm(0.0~14.0)
Target ET display (cooling)
Target outdoor SC (cooling)
Target indoor SC/SH (IC1)
Target indoor SC/SH (IC2)
01010110
11010110
00110110
10110110
105
106
107
108
109
Target indoor SC/SH (IC3)
Target indoor SC/SH (IC4)
Target indoor SC/SH (IC5)
01110110
11110110
00001110
111
110
112
0~FF(16 progressive)
0~20
Fan step number at time of abnormality delay
Actual frequency of abnormality delay
00000001
10000001
128
129
0~2000
OC SLEV opening pulse abnormality delay
IC1 LEV opening pulse abnormality delay
IC2 LEV opening pulse abnormality delay
IC3 LEV opening pulse abnormality delay
IC4 LEV opening pulse abnormality delay
IC5 LEV opening pulse abnormality delay
01000001
11000001
00100001
10100001
01100001
11100001
130
131
132
133
134
135
69
Display of data from high-pressure sensor,
all thermistors, and SC/SH at time of
abnormality delay
78
Display on the LD1 (display data)
2345 6
Display of actual frequency at time of abnormality
Display of fan step number at time of abnormality
Display of opening pulse of outdoor SLEV
and indoor LEV at time of abnormality
Display of data from high-pressure sensor
and all thermistors at time of abnormality
Display of data from SC/SH and all
thermistors at time of abnormality
1
Display mode Notes
High-pressure sensor data at time of abnormality delay
TH1 sensor data at time of abnormality delay
TH2 sensor data at time of abnormality delay
TH5 sensor data at time of abnormality delay
10010001
01010001
137
138
139
11010001
12345678
00010001
SW1 setting
No.
136
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
THHS sensor data at time of abnormality delay
OC SC (cooling) at time of abnormality delay
IC1 SC/SH at time of abnormality delay
IC2 SC/SH at time of abnormality delay
IC3 SC/SH at time of abnormality delay
IC4 SC/SH at time of abnormality delay
IC5 SC/SH at time of abnormality delay
11110001
01110001
00110001 140
10110001
141
142
00001001
143
144
10001001
01001001
145
146
0~FF(16progressive)
0~20
Actual frequency at time of abnormality
Fan step number at time of abnormality
00000011
10000011
192
193
0~2000
opening pulse at time of abnormality
IC1 LEV opening pulse at time of abnormality
IC2 LEV opening pulse at time of abnormality
IC3 LEV opening pulse at time of abnormality
IC4 LEV opening pulse at time of abnormality
IC5 LEV opening pulse at time of abnormality
High-pressure sensor data at abnormality
OC SLEV
11000011
01000011
00100011
194
195
196
10100011
197
01100011 198
TH 1 sensor data at time of abnormality
11100011
00010011
10010011
199
200
201
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
sensor data at time of abnormality
sensor data at time of abnormality
sensor data at time of abnormality
OC SC (Cooling) at time of abnormality
IC1 SC/SH at time of abnormality
IC2 SC/SH at time of abnormality
IC3 SC/SH at time of abnormality
IC4 SC/SH at time of abnormality
TH 2
01010011 202
TH 5
11010011
203
THHS
00110011
10110011
204
205
01110011
206
11110011
207
IC5 SC/SH at time of abnormality
00001011
10001011
01001011
208
209
210
70
Display of indoor unit capacity mode
78
Display of indoor unit operating mode
Heating
Heating
Cooling
Display of opening pulse of outdoor
SLEV and indoor LEV
OFF
thermo
ON
thermo
OFF
thermo
Display of indoor SC/SH data
Display of all control target data
Display of opening pulse of indoor LEV
at time of abnormality
Display of opening pulse of indoor LEV
at time of abnormality
Display on the LD1 (display data)
2345 6
1
0~255
Display mode Notes
IC6 Capacity code
IC7 Capacity code
IC8 Capacity code
ON
thermo
Cooling
OFF Fan
IC6 operation mode
IC7 operation mode
0~2000
IC8 operation mode
IC6 LEV opening pulse
IC7 LEV opening pulse
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
IC8 LEV opening pulse
IC6 TH23
IC7 TH23
IC8 TH23
IC6 TH22
IC7 TH22
IC8 TH22
IC6 TH21
IC7 TH21
IC8 TH21
during heating:subcool (SC)/during cooling:superheat (SH)
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
IC6 SC/SH
IC7 SC/SH
SCm/SHm (0.0~14.0)
IC8 SC/SH
IC6 target SC/SH
IC7 target SC/SH
0~2000
IC8 target SC/SH
IC6 LEV opening pulse at abnormality delay
IC7 LEV opening pulse at abnormality delay
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
IC8 LEV opening pulse at abnormality delay
IC6 SC/SH at abnormality delay
IC7 SC/SH at abnormality delay
0~2000
IC8 SC/SH at abnormality delay
IC6 LEV opening pulse at time of abnormality
IC7 LEV opening pulse at time of abnormality
IC8 LEV opening pulse at time of abnormality
IC6 SC/SH at abnormality
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
IC7 SC/SH at abnormality
IC8 SC/SH at abnormality
10101011
213
01101011 214
11101011 215
00011011
216
10011011
217
01011011
218
11001011
00101011
12345678
SW1 setting
No.
211
212
11011011 219
00111011 220
10111011 221
01111011
222
11111011
223
00000111 224
10000111 225
01000111
226
71
11000111
227
00100111 228
10100111
229
01100111
230
11100111 231
00010111
232
10010111
233
01010111
234
11010111
235
00110111 236
10110111 237
01110111
238
11110111 239
00001111 240
10001111 241
01001111
242
11001111
243
00101111 244
10101111
245
01101111
246
10 ELECTRICAL WIRING
Outdoor unit
Grounded
Circuit breaker
Power supply single phase 220-230-240V, 50Hz
Outdoor unit
Indoor unit
Grounded
Grounded
Junction box
Circuit breaker
N
Power supply (3phase 380-400-415V, 50Hz)
• PUMY-P125VMA
• PUMY-P125YMA PUMY-P125YMA
1
Circuit breaker
Power supply single phase 50Hz 220-230-240V
This chapter provides an introduction to electrical wiring for the MULTI-S series, together with notes concerning power wiring, wiring for control (transmission wires and remote controller wires), and the frequency converter.
10-1. OVERVIEW OF POWER WIRING
(1) Please refer to your electric power company about the indoor wiring specifications for the power wire diameter
and capacity of protective devices (switches and leakage of breakers).
(2) Taking into consideration voltage drops caused by the length of the wires when operating devices installed
downstream, determine the specifications of wires able to handle the maximum current or voltage. In addition, protective devices must be able to protect against current leakage or excessive current.
(3) It is generally necessary to include leakage breakers when installing wiring for the CITY MULTI-S series.
Protective switches (excessive current protection) along main or branch lines should typically consist of fuse-less
breakers (ELB). (4) Please perform grounding. (5) It is suggested that you consult with your electric power company concerning restrictions on electrical specifications.
10-2. WIRE DIAMETER AND MAIN POWER SWITCH CAPACITY
10-2-1. Wiring diagram for main power supply
10-2-2. Power supply wire diameter and capacity
Minimum wire cross section area(mm2)
2.5
Branch line
Branch line
Model
PUMY-P125VMA
PUMY-P125YMA
PUMY-P125YMA
Outdoor unit
Model
All Models
Indoor unit
Main line
5.5(6)
1
Minimum wire cross section area(mm)
Main line
[1.6
Grounded
5.5(6)
Grounded
[1.6
2.5
Interrupting current
Interrupting current
32A
25A
15A
72
Breaker
Performance characteristic
32A,30mA for 0.1 sec. or less
25A,30mA for 0.1 sec. or less
Breaker
Performance characteristic
15A, 30mA for 0.1 sec. or less
10-3. DESIGN FOR CONTROL WIRING
L2
Outdoor unit
L3
L1
L4
1.25mm
2
shielded wire
R
R
Indoor unit
(Note 1)
(Note 2)
Grounded
Remote controller
Please note that the types and numbers of control wires needed by the CITY MULTI-S series will depend on the remote controllers and whether they are linked with the system.
10-3-1. Selection number of control wires
M-NET remote controller
Use
Remote controller indoor unit Wires connecting indoor units Wires connecting indoor units with outdoor unit Wires connecting outdoor units
wires
Transmission
10-3-2. Control signal wires
Transmission wires
• Types of transmission cables : Shielding wire CVVS or CPEVS.
• Cable diameter : More than 1.25E
• Maximum wiring length : Within 200 m
10-3-3. Remote controller wiring
Remote controller used in system control operations.
• Group operation involving different refrigerant systems.
• Linked operation with upper control system.
2 wires (non-polar)
Kind of remote control cable
Cable diameter
Remarks
2-core cable (unshielded)
0.3 to 1.25E When 10m is exceeded, use cable with the same specifications as 10-3-2. Transmission line wiring
10-3-4. Permissible length of control wiring
• Maximum extension length of wiring
(L1+L2+L3+L4).....less than 500m
• Maximum wire length
(L1+L2+L4 or L1+L3 or L2+L3+L4).....less than 200m
• Remote controller wire
(R)....network controller wire is less than 10m
Note 1: Please make sure that the transmission wire is
grounded at the outdoor unit ground terminal.
Note 2: If the remote controller wire is greater than 10m,
the excess portion should use shielded wire at least 1.25mm total length of the farthest wire is less than 200m.
2
in size. Please make sure that the
73
10-4. SYSTEM SWITCH SETTING
Outdoor unit
Power supply 3 phase 4 wire. 50Hz 380-400-415V
Power supply Single phase. 50Hz 220-230-240V
Grounded
Group operation
Remote controller wire
Junction box
Indoor unit
circuit breaker
L1,L2,L3
N
15A circuit breaker
[1.6mm 2
[1.6mm 2
0.5~0.75mm
2
2
1.25mm
2
2
In order to identify the destinations of signals to the outdoor units, indoor units, and remote controller of the MULTI-S series, each microprocessor must be assigned an identification number (address). The addresses of outdoor units, indoor units, and remote controller must be set using their settings switches. Please consult the installation manual that comes with each unit for detailed information on setting procedures.
10-5. EXAMPLE EXTERNAL WIRING DIAGRAM FOR A BASIC SYSTEM
10-5-1. Example using a M-NET remote controller
10-6. METHOD FOR OBTAINING ELECTRICAL CHARACTERISTICS WHEN A CAPACITY
AGREEMENT IS TO BE SIGNED WITH AN ELECTRIC POWER COMPANY
The electrical characteristics of connected indoor unit system for air conditioning systems, including the MULTI-S series, will depend on the arrangement of the indoor and outdoor units. First read the data on the selected indoor and outdoor units and then use the following formulas to calculate the electrical characteristics before applying for a capacity agreement with the local electric power company.
10-6-1. Obtaining the electrical characteristics of a MULTI-S series system
(1)Procedure for obtaining total power consumption
Total power consumption of each indoor unit
1 power consumption of outdoor unit
Total power consumption of system
1 Please note that the power consumption of the outdoor unit will vary depends on the total capacity of the selected
indoor units.
(2)Method of obtaining total current
Total current through each indoor unit
2 current through outdoor unit
current through system
Total
2 Please note that the
(3) Method of obtaining system power factor
Use the following formula and the total power and current obtained in parts 1 and 2 on the previous page to calculate the system power factor.
10-6-2. Applying to an electric power company for power and total current
Calculations should be performed separately for heating and cooling employing the same methods; use the largest resulting value in your application to the electric power company.
current through the outdoor unit will vary depending on the total capacity of the selected indoor units.
System power factor =
Page numbers in this technical manual
See the technical manual of each indoor unit
Standard capacity table—P.8-10
See the technical manual of each indoor unit
Page numbers in this technical manual
See the technical manual of each indoor unit
Standard capacity table—P.8-10
See the technical manual of each indoor unit
(Total system power consumption)
(Total system current x voltage)
74
Power consumption
1
2
1+2 <kW>
Subtotal
1
2
1+2 <A>
o 100%
11 REFRIGERANT PIPING TASKS
11-1. REFRIGERANT PIPING SYSTEM
A
Line-Branch Method
Connection Examples (Connecting to Four Indoor Units)
Permissible
Length
Permissible High/
Low Difference
Total Piping Length Farthest Piping Length Farthest Piping Length After First Branch High/Low Difference in Indoor/Outdoor Section High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Pipng
(1) Section From Oudoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d)
(3) Section From Branch to
Each Section of Piping
Branch (B,C)
Select the size from the table to the right.
A+B+C+a+b+c+d is 100 meters or less
(L)
A+B+C+d is 70 meters or less
(R)
B+C+d is 30meters or less
(H)
30 meters or less (If the outdoor unit is lower, 20 meters or less)
(h)
12 meters or less Use an optional branch piping kit (CMY-Y62-C-E).
(1) Refrigerant Piping Diameter In Section (Outdoor Unit Piping Diameter)
PUMY-P125
(3) Refrigerant Piping Diameter In Section
A
H
B
h
B
a
C
1
C
b
C
23
From Outdoor Unit to First Branch
Piping Diameter (mm)Model
Liquid Line
Gas Line
From Branch to Branch
80 or less
80 or more
c
C
{9.52 {19.05
Liquid Line (mm) Gas Line (mm)Downstream Unit Model Total
L
R
d
C
4
Outdoor Unit
A
First Branch
B
Indoor unit
C
(2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit
(Indoor Unit Piping Diameter)
Model number
40 or lower
50 to 80
100, 125
{9.52 {9.52
Piping Diameter (mm)
Liquid Line
Gas Line
Liquid Line
Gas Line
Liquid Line
Gas Line
{15.88 {19.05
{6.35 {12.7 {9.52 {15.88 {9.52 {19.05
Additional refrigerant charge
• Refrigerant of 3kg equivalent to 50-m total extended piping length is already included
when the outdoor unit is shipped.
Thus, if the total extended piping length is
50m or less, there is no need to charge with additional refrigerant.
• If the total extended piping length exceeds 50m, calculate the required additional
refrigerant charge using the procedure shown on the right.
• If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
<Additional Charge>
Additional refrigerant charge
(kg)
Liquid pipe size Total length of {9.52 0.06
=
(m) 0.06 (kg/m)
Liquid pipe size Total length of {6.35 0.024
+
(m) 0.024 (kg/m)
Refrigerant amount for outdoor unit
<Example> Indoor 1 : 25 A : {9.52 10m a : {6.35 5m
2 : 50 B : {9.52 10m b : {9.52 10m 3 : 25 C : {9.52 10m c : {6.35 10m
At the conditions below:
4 : 50 d : {9.52 10m
The total length of each liquid line is as follows
{9.52 : A + B + C + b + d = 10 + 10 + 10 + 10 + 10 = 50m {6.35 : a + c = 5 + 10 = 15m
Therefore, <Calculation example> Additional refrigerant charge = 50 0.06 + 15 0.024 – 3.0 = 0.4kg (rounded up)
75
125: 3.0kg
Header-Branch Method
Connection Examples (Connecting to Four Indoor Units)
A
A
L
H
B
R
Permissible
Length
Permissible High/
Low Difference
Total Piping Length Farthest Piping Length Farthest Piping Length After First Branch High/Low Difference in Indoor/Outdoor Section High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Piping
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d)
Each Section of Piping
Select the size from the table to the right.
Additional refrigerant charge
• Refrigerant of 3kg equivalent to 50-m total extended piping length is already included
when the outdoor unit is shipped.
Thus, if the total extended piping length is 50m or less, there is no need to charge with additional refrigerant.
• If the total extended piping length exceeds 50m, calculate the required additional
refrigerant charge using the procedure shown on the right.
• If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
a
C
1
h
c
b
C
C
2
3
d
C
4
A+a+b+c+d is 100 meters or less
(L)
A+d is 70 meters or less
(R)
d is 30 meters or less
(H)
30 meters or less (If the outdoor unit is lower, 20 meters or less)
(h)
12 meters or less Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
•The CMY-Y68- cannot be connected with 100,125 type indoor units. Branch header (4 branches)
CMY-Y64-C
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch (Out­door Unit Piping Diameter)
Branch header (8 branches)
CMY-Y68
(2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit (Indoor Unit Piping Diameter)
Piping Diameter (mm)Model
PUMY-P125
Liquid Line
Gas Line
{9.52 {19.05
40 or lower
50 to 80
100,125
<Additional Charge>
Additional refrigerant charge
(kg)
Liquid pipe size Total length of {9.52 0.06
=
(m) 0.06 (kg/m)
Liquid pipe size Total length of {6.35 0.024
+
(m) 0.024 (kg/m)
<Example> Indoor 1 : 50 A : {9.52 30m a : {9.52 15m
2 : 40 b : {6.35 10m 3 : 25 c : {6.35 10m
At the conditions below:
4 : 20 d : {6.35 20m
The total length of each liquid line is as follows
{9.52 : A + a = 30 + 15 = 45m {6.35 : b + c + d = 10 + 10 + 20 = 40m
Therefore, <Calculation example> Additional refrigerant charge = 45
0.06 + 40 0.024 – 3.0 = 0.7kg (rounded up)
Outdoor Unit
A
First Branch
B
Indoor unit
C
Piping Diameter (mm)Model number
Liquid Line
Gas Line
Liquid Line
Gas Line
Liquid Line
Gas Line
Refrigerant amount for outdoor unit
125: 3.0kg
{6.35 {12.7 {9.52 {15.88 {9.52 {19.05
76
Method of Combined Branching of Lines and Headers
Connection Examples (Connecting to Five Indoor Units)
A
Note:Pipe re-branching after the header branching
is not possible.
A
C
B
H
B
C
c
3
D D D
a
D
1
L
R
b
Note:The total of downstream unit models in the
table is the total of models as seen from point A in the figure above.
E
A
d e
4
2
G
5
Outdoor unit
A
First branching (branching
B
joint)
h
Branching joint
C
Indoor unit
D
Branching header
D
E
To downstream unit
F
Blind caps
G
F
Permissible
Length
Permissible High/
Low Difference
Total Piping Length Farthest Piping Length Farthest Piping Length After First Branch High/Low Difference in Indoor/Outdoor Section High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Piping
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d,e)
(3) Section From Branch to
Each Section of Piping
Branch (B,C)
Select the size from the table to the right.
Additional refrigerant charge
• Refrigerant of 3kg equivalent to 50-m total extended piping length is already included when the outdoor unit is shipped. Thus, if the total extended piping length is 50m or less, there is no need to charge with additional refrigerant.
• If the total extended piping length exceeds 50m, calculate the required additional refrigerant charge using theprocedure shown on the right.
• If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
A+B+C+a+b+c+d+e is 100 meters or less
(L)
A+B+b is 70 meters or less
(R)
B+b is 30 meters or less
(H)
30 meters or less (If the outdoor unit is lower, 20 meters or less)
(h)
12 meters or less Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Branch Joint
CMY-Y62-C-E
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch (Out­door Unit Piping Diameter)
Branch Header (4 branches)
CMY-Y64-C
(2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit (Indoor Unit Piping Diameter)
Branch Header (8 branches)
Piping Diameter (mm)Model
PUMY-P125
Liquid Line
Gas Line
{9.52 {19.05
40 or lower
50 to 80
100,125
(3) Refrigerant Piping Diameter In Section
From Branch to Branch
Liquid Line (mm) Gas Line (mm)Downstream Unit Model Total
80 or less
80 or more
{9.52 {9.52
{15.88 {19.05
<Additional Charge>
Additional refrigerant charge
(kg)
Liquid pipe size Total length of {9.52 0.06
=
(m) 0.06 (kg/m)
Liquid pipe size Total length of {6.35 0.024
+
(m) 0.024 (kg/m)
<Example> Indoor 1 : 50 A : {9.52 10m a : {9.52 5m
2 : 40 B : {9.52 20m b : {6.35 10m 3 : 32 C : {9.52 10m c : {6.35 5m 4 : 20 d : {6.35 5m 5 : 20 e : {6.35 5m
The total length of each liquid line is as follows
{9.52 : A + B + C + a = 10 + 20 +10 + 5 = 45m {6.35 : b + c + d + e = 10 + 5 + 5 + 5 = 25m
Therefore, <Calculation example> Additional refrigerant charge = 45 0.06 + 25 0.024 – 3.0 = 0.3kg (rounded up)
CMY-Y68
Piping Diameter (mm)Model number
Liquid Line
Gas Line
Liquid Line
Gas Line
Liquid Line
Gas Line
Refrigerant amount for outdoor unit
125: 3.0kg
At the conditions below:
{6.35 {12.7 {9.52 {15.88 {9.52 {19.05
77
Multi-distribution piping on outdoor unit
Connection Examples (Connecting up to Five Indoor Units)
*If multi-distribution piping on outdoor unit is done, a maximum of 5 indoor units can be connected.
Permissible
Length
Permissible High/
Low Difference
Total Piping Length Farthest Piping Length
High/Low Difference in Indoor/Outdoor Section High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
A
L
B
a
b
H
h
C
C
1
2
c
d
C
C
3
4
e
C
5
Cannot redistribute the piping.
a+b+c+d+e is 100 meters or less
(L)
e is 30 meters or less
(H)
30 meters or less (20 meters or less if the outdoor unit is below.)
(h)
12 meters or less Use multi-distribution piping on outdoor unit kit CMY-S65 ( 5 branches).
*Cannot be connected with 100,125 type indoor units.
Outdoor Unit
A
First Branch
B
Indoor unit
C
Select Each Section of Refrigerant Piping
• Section the piping size for each section from the branch to the indoor unit (a,b,c,d,e) using the chart on the right.
Additional refrigerant charge
• Refrigerant of 3kg equivalent to 50-m total extended piping length is already included
when the outdoor unit is shipped. Thus, if the total extended piping length is 50m or less, there is no need to charge with additional refrigerant.
• If the total extended piping length exceeds 50m, calculate the required additional refrigerant charge using theprocedure shown on the right.
• If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
• Refrigerant Piping Diameter In Section From Branch to Indoor Unit (Indoor Unit Piping Diameter)
Model number
40 or lower
50 to 80
Piping Diameter (mm)
Liquid Line
Gas Line
Liquid Line
Gas Line
{6.35 {12.7 {9.52 {15.88
<Additional Charge>
Additional refrigerant charge
(kg)
Liquid pipe size Total length of {9.52 0.06
=
(m) 0.06 (kg/m)
Liquid pipe size Total length of {6.35 0.024
+
(m) 0.024 (kg/m)
<Example> Indoor 1 : 20 a : {6.35 10m
2 : 20 b : {6.35 20m 3 : 20 c : {6.35 20m 4 : 50 d : {9.52 20m 5 : 50 e : {9.52 30m
The total length of each liquid line is as follows
{9.52 : d + e = 20 + 30 = 50m {6.35 : a + b + c = 10 + 20 + 20 = 50m
Therefore, Additional refrigerant charge = 50
0.06 + 50 0.024 – 3.0 = 1.2kg (rounded up)
Refrigerant amount for outdoor unit
125: 3.0kg
78
11-2. PRECAUTIONS AGAINST REFRIGERANT LEAKAGE
Indoor unit
All refrigerant of this system will leak out to this room if there is leakage at this indoor unit.
Direction of refrigerant flow
Outdoor unit
11-2-1. Introduction
R-22 refrigerant of this air conditioner is non-toxic and non­flammable but leaking of large amount from an indoor unit into the room where the unit is installed may be deleterious. To prevent possible injury, the rooms should be large enough to keep the R407C concentration specified by KHK : (a high pressure gas safety association) installation guide­lines S0010 as follows.
Maximum concentration Maximum refrigerant concentration of R407C of a room is 0.31 kg/K accordance with the installation guidelines.
To facilitate calculation, the maximum concentration is expressed in units of O/K ( kg of R407C per K)
Maximum concentration of R407C: 0.31O/K
(KHK installation guidelines S0010)
(2) Calculate room volumes (in K) and find the room
with the smallest volume
The part with represents the room with the smallest volume.
(a) Situation in which there are no partitions
(b) There are partitions, but there are openings that allow
the effective mixing of air.
Outdoor unit
Indoor unit
Outdoor unit
11-2-2. Confirming procedure of R407C concentration
Follow 1) to 4) to confirm the R407C concentration and take appropriate treatment, if necessary.
(1) Calculate total refrigerant amount by each refrig-
erant system based on one indoor unit. Total refrigerant amount is prechrged refrigerant amount of the indoor unit at ex-factory plus addi­tional charged amount at field installation.
Note: When single refrigeration system is consists of several independent refrigeration circuit, figure out the total refrig­erant amount by each independent refrigerant circuit.
Indoor unit
Opening
Wall
(c) If the smallest room has mechanical ventilation appara-
tus that is linked to a household gas detection and alarm device, the calculations should be performed for the second smallest room.
Ventilation apparatus
The smallest room
The second smallest room
(situation in which there are no door openings or in which there are open­ings above and blow doors that occupy at least 0.15% of the floor area)
Outdoor unit
Indoor unit
(3) Use the results of calculations (1)and (2) to calcu-
late the refrigerant concentration:
Total refrigerant in the refrigerating unit (O) The smallest room in which an indoor
unit has been installed (K)
If the calculation results do not exceed the maximum concen­tration, perform the same calculations for the larger second and third room, etc., until it has been determined that nowhere will the maximum concentration be exceeded.
[ maximum concentration(O/K)
Maximum concentration of R407C:0.31O/K
79
12 DISASSEMBLY
Service Ref. : PUMY-P125VMA
PUMY-P125YMA PUMY-P125YMA
1. Please pay attention to safety when assembling or disassembling heavy items.
2. The refrigerant system must be vacuum-pumped before performing piping maintenance.
1
OPERATING PROCEDURE PHOTOS
1. Side and top panel disassembly procedures:
(1) Remove the side panel screws (3 pcs : 5o10 screws)
so that the hanging portion on the right side can be slid downward. Remove the side panel.
(2) Remove the top panel screws (5o10 screws :
3 pcs in front, 2 pcs in back) and take off the top panel. <If the rear screws on the top panel cannot be removed> Remove the front screws on the top panel (3 pcs : 5o10 screws) and lift up the front part of the top panel.
2. Propeller and fan motor disassembly procedures:
(1) Remove the side panel (See photo 1) (2) Remove the top panel (See photo 1) (3) Remove the fan protection cover fixing screw
(1 pc : 15o15), and take off the fan guard by rotating it to the left.
(4) [PUMY-P125VMA]
Remove the fan motor wires (MF1) (MF2) from the multi circuit board. Remove the capacitor wires.
Photo 1
Fan protection covers
Fan protection cover fixing screws
Photo 2 PUMY-P125VMA
Propeller
Top panel installation screws
Front panel
Top panel
Side panel installation screws
Side panel (for service)
Power circuit board
Multi circuit board
[PUMY-P125YMA, PUMY-P125YMA
Remove the fan motor wires (MF1) (MF2) from the power supply board. Remove the capacitor wires.
(5) Loosen the fan motor wire clips (3 pcs). (6) Remove the propeller. (7) Remove the fan motor screws (3 pcs : 5o16 screws)
and remove the fan motors.
]
1
Electrical parts box
Fan motors
Photo 3 PUMY-P125YMA, PUMY-P125YMA1
Power supply board
Multi controller board
Propeller
Electrical parts box
Fan motors
80
OPERATING PROCEDURE PHOTOS
3. Thermistor (TH6: outdoor air temperature sensor detection) disassembly procedures:
(1) Remove the side panel (See photo 1) (2) Remove the top panel (See photo 1) (3) Remove the thermistor holder fixing screw (1 pc : 4o10),
and remove the thermistor holder.
(4) Remove the Thermistor (outdoor air temperature
detection).
(5) Remove the TH6 wire from the multi-functional
controller board in the electrical box and pull out of the electrical box.
4. Electrical parts box disassembly procedures:
[PUMY-P125VMA]
(1) Remove the side panel (See photo 1) (2) Remove the top panel (See photo 1) (3) Disconnect the following wires from the
multi controller board.
• Thermistor (Discharge temperature detection):TH1
• Thermistor (Low pressure saturated temperature detection):TH2
• Thermistor (Pipe temperature defection / Judging defrost):TH5
• Thermistor (Outdoor temperature detection): TH6
• High-pressure sensor (Discharge pressure detection): 63HS
• Expansion valve: LEV(A)
• Fan motor: MF1 and MF2
• Solenoid valve: SV
• 4-way valve: 21S4
Photo 4
Rear panel
Photo 5 PUMY-P125VMA
Power circuit board
Thermistor (air temperature
detection)
Thermistor holder screw
Thermistor holder
Heat exchanger
Board plate
Electrical parts box
Rear panel
Multi circuit board
(4) Remove the board plate.
Pull wires out of the electrical parts box after disconnecting them.
(6) After removing the connector cover, remove the compressor
wire and the inner thermostat terminal. (7) Remove the electrical box screw (1 pc : 4 o 10). (8) Remove the valve bed screws from the right side of
the valve bed (2 pcs : 4 o 10).
(9) Remove the electrical box after slightly loosening the
rear panel. The electrical box is held by two claws on the left and one on the right.
Electric parts box screw
Valve bed screws
Connector cover Valve bed
81
OPERATING PROCEDURE PHOTOS
5. Electrical parts box disassembly procedures: [PUMY-P125YMA, PUMY-P125YMA
(1) Remove the side panel (See photo 1) (2) Remove the top panel (See photo 1) (3) Disconnect the following wires from the
multi controller board.
• Thermistor (Discharge temperature detection):TH1
• Thermistor (Low pressure saturated temperature detection):TH2
• Thermistor (Pipe temperature defection • judging defrost):TH5
• Thermistor (Outdoor temperature detection): TH6
• High-pressure sensor (Discharge pressure detection): 63HS
• Expansion valve: SLEV
(4) Remove the board plate. (5) Disconnect the following wires from the power supply
board:
• Fan motor: MF1 and MF2
• Solenoid valve: SV1
• 4-way valve: 21S4 Pull wires out of the electrical box after disconnecting them.
(6) After removing the connector cover, remove the compressor
wire and the inner thermostat terminal.
(7) Remove the electrical box screw (1 pc : 4 o 10). (8) Remove the valve bed screws from the right side of
the valve bed (2 pcs : 4 o 10).
(9) Remove the electrical box after slightly loosening the
rear panel. The electrical box is held by two claws on the left and one on the right.
]
1
Photo 6 PUMY-P125YMA, PUMY-P125YMA
Power supply board
Board plate
Connector cover Valve bed
1
Electrical parts box
Rear panel
Multi controller board
Electric parts box screw
Valve bed screws
6. Solenoid valve coil and 4-way valve coil disassembly procedures:
(1) Remove the side panel (See photo 1). (2) Remove the top panel (See photo 1). (3) Remove the electrical parts box (See photo 5 or 6). (4) Remove coil screws (Solenoid valve: 1 pc M4x6;
4-way valve: 1 pc M5x6), and remove the solenoid valve (SV1) and 4-way valve (21S4) wires from the power supply board.
Photo 7
Solenoid valve coil
4-way valve
4-way valve coil
82
OPERATING PROCEDURE PHOTOS
7. Thermistor disassembly procedures:
(1) Remove the side panel (See photo 1) (2) Remove the top panel (See photo 1) (3) Remove the electrical parts box (See photo 5 or 6) (4) Recover gas from the refrigerant circuit. (5) Remove the Thermistor
(discharge temperature detection: TH1), (Low pressure saturated temperature detection: TH2), (Pipe temperature detection / judging defrost: TH5).
To remove TH1, cut the bands holding it and remove
the piping cover.
Photo 8
Thermistor (TH1)
Bands
Photo 9
Oil separator
Piping cover
Thermistor (TH2)
Welding part of high pressure sensor
Thermistor (TH5)
8. Compressor disassembly procedures:
(1) Remove the side panel (See photo 1) (2) Remove the top panel (See photo 1) (3) Remove the screws (2 pcs : 5o10, 1 pc : 4o10) and the
front panel. (4) Remove the electrical parts box (See photo 5 or 6). (5) Remove screws (3 pcs : 4o10, 4 pcs : 5o16) and the
valve bed (including the ball valve mounting portion). (6) Recover gas from the refrigerant circuit. (7) Remove the separator screw. (1 pc : 4o10) (8) Remove the welded portions of the compressor
discharge and intake pipes. (9) Remove the compressor leg cover on the separator side. (10)Remove the compressor leg mounting nuts (3 pcs).
(use an adjustable wrench)
(11)Move the separator to the left and remove the
compressor.
9. Accumulator disassembly procedures:
(1) Remove the compressor (See photo 10). (2) Remove the welded portions of the accumulator. (3) Lift up the accumulator and pull it out from the rear.
Compressor
Photo 10
Separator
Separator installation screw
Compressor
Installation nuts
Accumulator
83
OPERATING PROCEDURE PHOTOS
10. Four-way valve disassembly procedures:
(1) Remove the side panel (See photo 1). (2) Remove the top panel (See photo 1). (3) Remove the electrical parts box (See photo 5 or 6). (4) Recover gas from the refrigerant circuit. (5) Remove the 4-way valve coil (See photo 7). (6) Remove the mounting screws from the gas side ball
valve (2 pcs : 5o16). (7) Remove the field piping from the outdoor unit (gas side). (8) Remove the welded portion.
1 Upper and lower heat exchanger inlet (T connector). 2 Accumulator inlet (T connector) 3 4-way valve inlet
(9) Remove 4-way valve.
Do not expose 4-way valve to above 120°C.
Photo 11
Pipe of heat exchanger inlet (T connector)
Accumulator inlet (T connector)
4-way valve
4-way valve inlet
Gas side ball valve
11. Solenoid valve disassembly procedures:
(1) Remove the side panel (See photo 1). (2) Remove the electrical parts box (See photo 5 or 6). (3) Recover gas from the refrigerant circuit. (4) Remove the solenoid valve coil (See photo 7). (5) Remove the welded portions of the solenoid valve.
(take care excessive heating)
12. Expansion valve disassembly procedures:
(1) Remove the side panel (See photo 1). (2) Remove the electrical parts box (See photo 5 or 6). (3) Recover gas from the refrigerant circuit. (4) Remove welded portions of expansion valve.
(take care excessive heating)
To remove welded portion, cut the band holding it and
remove the rubber tube.
Photo 12
Photo 13
Oil separator
Welding parts
Rubber tube
Fixing screws
Band
Solenoid valve coil
Expansion valve
Welding parts
84
OPERATING PROCEDURE PHOTOS
13. High pressure sensor (63HS)disassembly procedures:
(1) Remove the side panel (See photo 1). (2) Remove the high pressure sensor wire. (3) Recover gas from the refrigerant circuit. (4) Remove the welded portion of high pressure sensor. (5) Remove the mounting screw fastening the high
pressure sensor mounting plate (1 pc : 4o10).
(6) Remove the high pressure sensor mounting screws
(2 pcs : 4o10).
Photo 14
Separator
High pressure sensor mount
fixing screw
High pressure sensor
Welding part
14. Capillary tube disassembly procedures:
(1) Remove the side panel (See photo 1). (2) Remove the top panel (See photo 1). (3) Remove the electrical parts box (See photo 5 or 6). (4) Recover gas from the refrigerant circuit. (5) Remove the field piping from the unit (liquid side) (6) Remove the welded portions of capillary tube.
To remove welded portions, cut the band holding it and
remove the rubber tube.
Photo 15
Capillary tube 3Capillary tube 4
Capillary tube 1 Capillary tube 2
85
13 PARTS LIST
1 2 3 4 5 6 7 8
9 10 11 12 13
Part No. Specification
No.
Wiring
Diagram
Symbol
Recom­mended
Q,ty
Price
Unit
Amount
Part Name
Q,ty/set
PUMY­P125VMA
Remarks
(Drawing No.)
FAN MOTOR CAPACITOR MULTI CIRCUIT BOARD FUSE POWER CIRCUIT BOARD THERMISTOR (RADIATOR PANEL) NOISE FILTER CIRCUIT BOARD TERMINAL BLOCK TERMINAL BLOCK REACTOR RESISTOR (RUSH CURRENT PROTECTION) ACTIVE FILTER MODULE SMOOTHING CAPACITOR MAGNETIC CONTACTOR
3.5µF 440VAC
6.3A 250V
3P(M1, M2, S) 3P(L, N, ;)
1,600µ / 400WV S-U12 230V
2 1 2 1 2 1 2 1 4 1 1 1 1
C1,2 M.B. F1, F2 P.B. THHS A/B N.F . TB3,7 TB1 DCL1,2,3,4 RS ACTE CE 52C
R01 580 255 T7W E19 315 T7W 520 239 T7W E08 313 R01 E65 202 T7W E04 346 T7W A12 716 T7W A13 716 T7W E01 259 T7W E01 234 T7W E00 233 T7W E05 254 T7W E02 259
ELECTRICAL PARTS PUMY-P125VMA
4
13
1
12
5
2
6
7
3
8
11
10
9
86
ELECTRICAL PARTS PUMY-P125YMA PUMY-P125YMA1
2
15
14
13
VARISTOR
1
5
12
6
7
3
4
Part No. Specification
No.
R01 580 255
1
T7W E02 239
2
T7W 520 239
3
T7W E11 315
4
T7W E18 315 T7W E00 259
5
T7W E00 311
6
T7W 249 708
7
T7W E00 234
8
T7W A12 716
9
T7W E10 716
10
T7W E01 346
11
T7W E03 254
12
T7W E00 349
13
T7W E00 292
14
R01 36A 202
15
FAN MOTOR CAPACITOR FUSE FUSE MULTI CONTROLLER BOARD MULTI CONTROLLER BOARD REACTOR POWER SUPPLY BOARD MAGNETIC CONTACTOR RESISTOR BOARD TERMINAL BLOCK TERMINAL BLOCK NOISE FILTER CAPACITOR VARISTOR DIODE MODULE THERMISTOR (IPM RADIATOR PANEL)
Part Name
8
3.5µF 440VAC 2A 250V
6.3A 250V
S-U12 230V
3P(M1,M2,S) 5P(L1,L2,L3,N,;)
9
Q,ty/set
PUMY-P125
YMA YMA
2
2
1
1
1
1 1
1 1
1
1
1
1
1
1
1
2
2
1
1
1
1
2
2
1
1
1
1
1
1
10
Remarks
(Drawing No.)
1
Wiring
Diagram
Symbol
C1,2 FUSE2 FUSE1
DCL
52C
TB3,7 TB1 NF C03 ZNR DM THHS
11
Recom-
mended
Q,ty
Unit
Price
Amount
87
FUNCTIONAL PARTS PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA1
27
26
1
2
25
24
23
22 21
20 19
18 17 16
15 14
345
88
13
12
11
10
6
7
8
9
Part number that is circled is not shown in the figure.
Part No. SpecificationNo.
1
R01 KL5 115
2
R01 30L 097
3
R01 35A 202
4
R01 E00 268
5
R01 E30 202
6
R01 J01 425 T97 500 218
7
T97 500 216
8
R01 E02 410
9
R01 E03 411
10
R01 38A 440
11
R01 42L 450
12
R01 28W 413
13
T7W E02 242
14
R01 E06 403
15
R01 KP1 467 T7W E37 202
16
R01 E29 202
17
T7W E13 425
18
R01 38A 425
19
R01 E10 425
20
R01 E02 428
21
T7W E00 242
22
R01 37A 490 R01 05A 401
23
R01 V39 401 T7W E36 202
24
R01 E31 202
25
R01 E23 408
26
T7W E19 763
27
T7W E18 763
28
R01 E00 405
PROPELLER NUT
THERMISTOR (DISCHARGE TEMPERATURE DETECTION)
HIGH PRESSURE SENSOR
THERMISTOR (PIPE TEMPERATURE DETECTION / JUDGING DEFROST)
CAPILLARY TUBE 1 COMPRESSOR COMPRESSOR BALL VALVE BALL VALVE ACCUMULATOR STRAINER CHARGE PLUG 4-WAY COIL 4-WAY VALVE MUFFLER
THERMISTOR (LOW PRESSURE SATURATED TEMPERATURE DETECTION) THERMISTOR (LOW PRESSURE SATURATED TEMPERATURE DETECTION)
CAPILLARY TUBE 2 CAPILLARY TUBE 3 CAPILLARY TUBE 4 SOLENOID VALVE SOLENOID COIL OIL SEPARATOR EXPANSION VALVE EXPANSION VALVE
THERMISTOR (OUTDOOR TEMPERATURE DETECTION) THERMISTOR (OUTDOOR TEMPERATURE DETECTION)
HEAT EXCHANGER FAN MOTOR FAN MOTOR DRYER
Part Name
M8
[2.5O[0.6O500mm EEV-48FAM EEV-48FAK 3/8" 3/4"
[2.5O[0.6O500mm [4.0O[3.0O200mm [4.0O[2.4O360mm
PA6V60-GD PA6V60-GC
Q,ty/set
PUMY-P125
YMA
YMA
VMA
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
1
Wiring
Diagram
Symbol
TH1 63HS TH5
MC MC
21S4
TH2 TH2
SV1
LEV(A) SLEV TH6 TH6
MF2 MF1
Recom­mended
Q,ty
Unit
Price
Amount
89
STRUCTURAL PARTS PUMY-P125VMA PUMY-P125YMA PUMY-P125YMA1
2 1 14 13 SCREW
3
12
11
8910
45 3 7
No.
Part No. Part Name Specification
R01 KN4 675
1
R01 38A 668
2
R01 KL5 655
3
R01 38A 686
4
R01 E01 130
5 6
T7W E06 658
7
R01 38A 682
8
R01 38A 661
9
R01 KP2 698
10
11
T7W E00 641
12
R01 38A 641
13
R01 KP2 662
14
FAN GUARD FRONT PANEL PANEL HANDLE BASE MOTOR SUPPORT SEPARATOR ASSY PANEL COVER REAR PANEL SERVICE PANEL REAR GUARD MOTOR PLATE TOP PANEL TOP PANEL SCREW (5O10) SIDE PANEL LEFT
6
PUMY-P125
VMA
2 1 3 1 1 1 1 1 1 1 1 1
11
1
Q,ty/set
YMA
2 1 3 1 1 1 1 1 1 1 1
1
11
1
(Drawing No.)
YMA1
2 1 3 1 1 1
(BG00G362G27) 1 1 1 1 1
(BG00C965G20)
1
11
(Z004B293H10)
1
Remarks
Wiring
Diagram
Symbol
Recom­mended
Q,ty
Unit
Price
Amount
90
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
cCopyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Sep. 2003 No.OC272 REVISED EDITON-A PDF 11 Distributed in Dec. 2001 No.OC272 PDF 300 Made in Japan.
New publication, effective Sep. 2003 Specifications subject to change without notice.
Loading...