Mitsubishi PUMY-71VM, PUMY-71VM1, PUMY-71VM2, PUMY-125VM, PUMY-125VM1 Service Manual

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
Outdoor unit [Model names] [Service Ref.]
PUMY-71VM PUMY-71VM
1999
No.OC183
REVISED EDITION-B
PUMY-71VM
1
PUMY-71VM2
PUMY-125VM PUMY-125VM
PUMY-125VM
1
PUMY-125VM2
PUMY-125YM PUMY-125YM
PUMY-125YM
PUMY-125YMA PUMY-125YMA
CONTENTS
1. TECHNICAL CHANGE ·····································2
2. OVERVIEW OF UNITS······································3
3. SPECIFICATIONS·············································6
4. DATA ·······························································12
5. OUTLINES AND DIMENSIONS······················32
7.
NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION
8. TROUBLESHOOTING ····································54
9. ELECTRICAL WIRING····································89
10. REFRIGERANT PIPING TASKS ·····················93
11. DISASSEMBLY················································98
12. PARTS LIST ··················································103
1
···42
Revision:
• PUMY-71VM2, PUMY-125VM2, PUMY-125YM1, PUMY-125YMA are added in Revised Edition-B.
• Please destroy OC183 Revised Edition-A.
1 TECHNICAL CHANGE
CHANGE POINTS
CONTENTS
OF
CHANGE
Outdoor unit Service Ref. Base outdoor unit Service Ref.
PUMY-
71VM
2
71VM1
125VM2 125VM1
125YM1 125YM
FAN MOTOR CAPACITOR FAN MOTOR
COMPRESSOR
HIGH PRESSURE SENSOR
SEPARATOR ASSY MULTI CONTROLLER BOARD
3.5+ 3.0+ PA6V40-UB PU6V60-GB PA6V40-UA PU6V60-GA PA6V60-UC PU6V60-GB PA6V60-UB PU6V60-GA PA6V60-UE PU6V60-GD PA6V60-UD PU6V60-GC CHV253FAA EHV33FAG EHV46FAA EHV46FAG EHV46FAD EHV46FAK Maker change Substrate connection wiring is attached. Change in accordance with high pressure sensor. Change in accordance with high pressure sensor.
Substrate connection wiring is not provided.
( ) ( )
— — — —
— —
— — —
— — —
— — — — —
— —
Change of the service parts. Refer to the parts list for the details.
ww
Only PUMY-125YMA is new model.
2
2 OVERVIEW OF UNITS
20 25 32 40 50 63 71
80 100 125
-
­32VKM 40VKM 50VKM 63VKM
­80VAM
100VAM 125VAM
20VLMD 25VLMD 32VLMD 40VLMD 50VLMD 63VLMD
-
80VLMD 100VLMD 125VLMD
20VML / VMM 25VML / VMM
32VML / VMM 40VMH / VMM 50VMH / VMM 63VMH / VMM 71VMH / VMM 80VMH / VMM
100VMH / VMM 125VMH / VMM
20VM 25VM 32VM 40VM 50VM 63VM 71VM
80VM 100VM 125VM
20VAM 25VAM 32VGM 40VGM 50VGM 63VFM
-
-
100VFM
-
20VLEM 25VLEM 32VLEM 40VLEM 50VLEM 63VLEM
-
-
-
-
20VLRM 25VLRM 32VLRM 40VLRM 50VLRM 63VLRM
-
-
-
-
-
-
-
40VGM
-
63VGM
-
­100VGM 125VGM
PLFY-P PLFY-P PEFY-P PDFY-P PKFY-P PCFY-P PFFY-P PFFY-P
Capacity
Model
Cassette Ceiling
4-way flow 2-way flow
20VBM 25VBM 32VBM 40VBM
-
-
-
-
-
-
PMFY-P
1-way flow
Ceiling
Concealed
Ceiling mounted
built-in
Ceiling
Suspended
Wall Mounted
Floor standing
Exposed Concealed
Remote
controller
Name
Model number
Functions
M-NET remote controller
PAR-F27MEA-E
• A handy remote controller for use in conjunction with the Melans centralized management system.
• Addresses must be set.
• Addresses setting is not necessary.
Only the indoor unit for MA remote controller
(the end of model name is -A) can be used.
MA remote controller
PAR-20MAA-E
2-1. UNIT CONSTRUCTION
Outdoor unit
Indoor unit that can be connected
Outdoor unit
Indoor unit that can be connected
Capacity
Number of units
Total systemwide capacity
Capacity
Number of units
Total systemwide capacity
3HP
PUMY-71VM
2~4units
50~130% of outdoor unit capacity
3HP
PUMY-71VM PUMY-71VM2
Type 20~Type 80
1~4units
50~130% of outdoor unit capacity
Type 20~Type 125
1
5HP
PUMY-125VM,PUMY-125YM
2~5units
5HP
PUMY-125VM1, PUMY-125YM PUMY-125VM2, PUMY-125YM1
PUMY-125YMA
Type 20~Type 125
1~8units
CMY-Y62-C-E CMY-Y64-C CMY-Y68
Branching pipe components
Branch header
(2 branches)
Branch header
(4 branches)
Branch header
(8 branches)
Decorative panel
3
CMY-S65
Multi distribution
Piping on outdoor
unit
(5 branches)
2-2. UNIT SPECIFICATIONS
P L F Y - P 80 V AM - A PU M Y - 125 Y M A
PAC type
AM KM M KM LMD
Frequency conversion controller
NEW frequency converter one-to-many air conditioners (flexible design type)
Indicates equivalent to Cooling capacity
Indicates equivalent to Cooling capacity
Power supply V: Single phase 220/230/240V 50Hz 220V 60Hz
Power supply V: Single phase 220/230/240V 50Hz 220V 60Hz Y: 3-phase 380/400/415V 50Hz 380V 60Hz
L: Ceiling cassette K: Wall-mounted type E: Hidden skylight type C: Ceiling suspended type M: Ceiling cassette type
}
M-NET control
M-NET control
MA control
Sub-number
Frequency conversion controller
Outdoor unit
MULTI-S
• Model 125 (5hp)..........For 5 rooms (VM)
...........For 8 rooms VM
1 YM
VM
2 YM1
YMA
( )
Service Ref.
w1
PUMY-71VM PUMY-71VM
1
PUMY-71VM2 w2
w1
PUMY-125VM PUMY-125VM
1
PUMY-125YM
w2
PUMY-125VM2 PUMY-125YM1 PUMY-125YMA
Capacity
Cooling (kW) Heating (kW)
8.3
9.3
2.6
8.0
9.0
2.6
14.5
16.3
3.5
14.0
16.0
3.5Motor for compressor (kW)
Cooling W.B. 15~24°C D.B. -5~46°C
Heating D.B. 15~27°C W.B. -15~15.5°C
Indoor-side intake air temperature Outdoor-side intake air temperature
(1) Outdoor Unit
Cooling / Heating capacity indicates the maximum value at operation under the following condition.
w1. Cooling Indoor : D.B. 27°C / W.B. 19.5°C
Outdoor : D.B. 35°C
Heating Indoor : D.B. 21°C
Outdoor : D.B. 9°C / W.B. 6°C
(2) Method for identifying MULTI-S model
Indoor unit < When using Model 80 >
w2. Cooling Indoor : D.B. 27°C / W.B. 19.0°C
Outdoor : D.B. 35°C
Heating Indoor : D.B. 20°C
Outdoor : D.B. 7°C / W.B. 6°C
Outdoor unit <When using model 125 >
(3) Operating temperature range
Notes D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
4
2-3. SYSTEM LAYOUT
A
B
a
indoor
1
C
b
indoor
2
D
c
indoor
3
e
d
indoor
4
indoor
5
First branch
(branching connector)
Outdoor unit
71
25 25 40
125
80 40 40
Outdoor unit
Indoor unit
Type 20 ~ Type 80 Type 20 ~ Type 125
PUMY-71VM
PUMY-71VM
1
PUMY-71VM2
PUMY-125VM
PUMY-125VM
1
PUMY-125VM2 PUMY-125YM PUMY-125YM
1
PUMY-125YMA
1~8 units
63~163
2~4 units
35~92
2~5 units
63~163
1~4 units
35~92
Indoor unit that can connected Available capacity of indoor unit
Total capacity of units that can be included system (50-130% of outdoor unit capacity)
2-3-1. System layout
One outdoor unit using branching connectors can be connected to a maximum of five or eight indoor units.
Examples of a branching method
2-3-2. Notes on the connection of indoor and outdoor units
Note: When the total capacity of indoor units exceeds the capacity of the outdoor unit (more than 100%), the rated power of
each indoor unit will be less when they are running simultaneously.
2-3-3. Capacity for outdoor unit
(1) Branching pipe
Model
CMY-Y62C-E
Branching connector
(2) Examples of System Construction (All models)
PIping method
Indoor units
CMY-Y64-C CMY-Y68 CMY-S65
Outdoor unit
NUMBER OF BRANCHING POINTS
2 4 8 5
Total capacity of
indoor units.
PIping method
90
5
Indoor units
Outdoor unit
Total capacity of
indoor units.
160
3 SPECIFICATIONS
Item
Rated Cooling capacity Rated power consumption Operating current Operating power factor Starting current Rated Heating capacity Rated power consumption Operating current Operating power factor
Standard performance
External finish (Munsell colour-coded markings) Dimensions H o W o D (Note 1) Heat exchanger type
Compressor
Fan
Defrost method Pressure gauge
Protection
Noise level Weight
Refrigerant pipe size
Refrigerant
Note 1: External dimensions in parentheses indicate the dimensions of protruding parts. Note 2: Rating conditions (JIS B 8615)
Heating Cooling
Starting current Rated power supply
Model Type o quantity Starting method Motor output Capacity control Daily cooling capacity Heater <crankcase> Refrigerating oil (Model) Type o quantity Airflow Motor output
High pressure protection Compressor protection Blower protection
devices
Frequency converter circuit
Type o charge amount Control method
Cooling : Indoor : D.B. 27: W.B. 19.5:
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 21:
: Outdoor : D.B. 7: W.B. 6:
Service Ref
Gas Liquid
kcal/h
kW
A
%
A
kcal/h
kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min
W
dB
kg
[ mm [ mm
kg
7,100
3.50
17.5-16.7-16.0 91
15.0
8,000
3.65
18.2-17.4-16.7 91
15.0 Single phase 220-230-240V 50Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 900 o 320 (+30) 1280 o 1020 o 350 (+30)
CHV253FAA
Fully enclosed type o 1
Frequency converter start
2.6
Cooling 27-100% Heating 24-100%
1.1 (110Hz) 25-28-30
1.07 (MS56) Propeller (direct) o 2
95
40 o 2
High pressure pressure sensor (3.0MPa)
Overheating, excessive current protection
52 93
15.88
9.52
R22 o 5
PUMY-125VM PUMY-71VM Unit
12,500
6.57
34.9-33.5-32.2 85
22.0
14,000
6.10
32.6-31.2-29.9 85
22.0
Crossover fin
EHV46FAA
3.5
Cooling 27-100% Heating 25-100%
1.9 (104Hz) 38-41-45
1.4 (MS32)
90
60 o 2
Reverse cycle
Thermal switch Thermal switch
54
130
19.05
9.52
R22 o 8.5
Expansion valve
6
Item
Service Ref
Rated Cooling capacity Rated power consumption Operating current Operating power factor Starting current Rated Heating capacity Rated power consumption Operating current Operating power factor
Standard performance
Heating Cooling
Starting current
Rated power supply External finish (Munsell colour-coded markings) Dimensions H o W o D (Note 1)
Unit
kcal/h
kW
A
%
A
kcal/h
kW
A
%
A
mm
7,100
3.50 / 3.63
17.5-16.7-16.0 / 18.1 91
15.0
8,000
3.65 / 3.53
18.2-17.4-16.7 / 17.6 91
15.0
Single phase 220-230-240V 50Hz / 220V 60Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 900 o 320 (+30) 1280 o 1020 o 350 (+30)
Heat exchanger type
Model Type o quantity Starting method Motor output Capacity control
Compressor
Daily cooling capacity Heater <crankcase> Refrigerating oil (Model) Type o quantity Airflow
Fan
Motor output
kW
%
Legal tons
W
L
k/min
W
Cooling 27-100% Heating 24-100%
CHV253FAA
Fully enclosed type o 1
Frequency converter start
2.6
1.1 (110Hz) —
1.07 (MS56) Propeller (direct) o 2
95
40 o 2 Defrost method Pressure gauge
High pressure protection
High pressure pressure sensor (3.0MPa) Compressor protection Blower protection
Protection
devices
Frequency converter circuit
Noise level Weight
Refrigerant pipe size
Refrigerant
Type o charge amount Control method
Gas Liquid
dB
kg
[ mm [ mm
kg
Overheating, excessive current protection
52 93
15.88
9.52
R22 o 5
Note 1: External dimensions in parentheses indicate the dimensions of protruding parts. Note 2: Rating conditions (JIS B 8615) Cooling: Indoor : D.B. 27: W.B. 19.5:
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 21:
: Outdoor : D.B. 7: W.B. 6:
Crossover fin
Cooling 27-100% Heating 25-100%
Reverse cycle
Thermal switch Thermal switch
Expansion valve
PUMY-125VM
1 PUMY-71VM1
12,500
6.57 / 6.43
34.9-33.5-32.2 / 33.6 85 / 87
22.0
14,000
6.10 / 6.03
32.6-31.2-29.9 / 31.5 85 / 87
22.0
EHV46FAA
3.5
1.9 (104Hz) —
1.4 (MS32)
90
60 o 2
54
130
19.05
9.52
R22 o 8.5
7
Item
Service Ref
Rated Cooling capacity Rated power consumption Operating current Operating power factor Starting current Rated Heating capacity Rated power consumption Operating current Operating power factor
Standard performance
Heating Cooling
Starting current
Rated power supply External finish (Munsell colour-coded markings) Dimensions H o W o D (Note 1) Heat exchanger type
Model Type o quantity Starting method Motor output Capacity control Daily cooling capacity
Compressor
Heater <crankcase> Refrigerating oil (Model) Type o quantity Airflow
Fan
Motor output Defrost method Pressure gauge
High pressure protection
Compressor protection
Blower protection
Protection
devices
Frequency converter circuit Noise level Weight
Refrigerant pipe size
Refrigerant
Type o charge amount Control method
Gas Liquid
Unit
kW kW
A
%
A kW kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min
W
dB
kg
[ mm [ mm
kg
2 PUMY-71VM2
8.0
3.50 / 3.63
17.5-16.7-16.0 / 18.1 91
15.0
9.0
3.65 / 3.53
18.2-17.4-16.7 / 17.6 91
15.0
PUMY-125VM
14.0
6.57 / 6.43
34.9-33.5-32.2 / 33.6 85 / 87
22.0
16.0
6.10 / 6.03
32.6-31.2-29.9 / 31.5 85 / 87
22.0
Single phase 220-230-240V 50Hz / 220V 60Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 900 o 320 (+30) 1280 o 1020 o 350 (+30)
Crossover fin
EHV33FAG
EHV46FAG
Fully enclosed type o 1
Frequency converter start
2.6
Cooling 36-100% Heating 32-100%
1.1 (83Hz) —
1.4 (MS32)
Cooling 27-100% Heating 25-100%
3.5
1.9 (104Hz) —
1.4 (MS32)
Propeller (direct) o 2
95
40 o 2
90
60 o 2
Reverse cycle
High pressure pressure sensor (3.0MPa)
Thermal switch Thermal switch
Overheating, excessive current protection
52
102
15.88
9.52
R22 o 5
54
130
19.05
9.52
R22 o 8.5
Expansion valve
Note 1: External dimensions in parentheses indicate the dimensions of protruding parts. Note 2: Rating conditions (JIS B 8616) Cooling: Indoor : D.B. 27: W.B. 19.0:
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 20:
: Outdoor : D.B. 7: W.B. 6:
8
Item
Rated Cooling capacity Rated power consumption Operating current Operating power factor Starting current Rated Heating capacity Rated power consumption Operating current Operating power factor
Standard performance
External finish (Munsell colour-coded markings) Dimensions H o W o D (Note 1) Heat exchanger type
Compressor
Fan
Defrost method Pressure gauge
Protection
Noise level Weight
Refrigerant pipe size
Refrigerant Note 1: External dimensions in parentheses indicate the dimensions of protruding parts.
Note 2: Rating conditions (JIS B 8615) Cooling : Indoor : D.B. 27: W.B. 19.5:
Heating Cooling
Starting current Rated power supply
Model Type o quantity Starting method Motor output Capacity control Daily cooling capacity Heater <crankcase> Refrigerating oil (Model) Type o quantity Airflow Motor output
High pressure protection Compressor protection Blower protection
devices
Frequency converter circuit
Type o charge amount Control method
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 21:
: Outdoor : D.B. 7: W.B. 6:
Service Ref
Gas Liquid
Unit
kcal/h
kW
A
%
A
kcal/h
kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min
W
dB
kg
[ mm [ mm
kg
3 phase 380-400-415V 50Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 1020 o 350 (+30)
Fully enclosed type o 1
Frequency converter start
Cooling 27-100% Heating 25-100%
Propeller (direct) o 2
High pressure pressure sensor (3.0MPa)
Overheating, excessive current protection
PUMY-125YM
12,500
5.95
9.6-9.1-8.8 94
8.0
14,000
5.58
9.0-8.6-8.3 94
8.0
Crossover fin
EHV46FAD
3.5
1.9 (104Hz) —
1.4 (MS32)
90
60 o 2
Reverse cycle
Thermal switch Thermal switch
54
127
19.05
9.52
R22 o 8.5
Expansion valve
9
Item
Rated Cooling capacity Rated power consumption Operating current Operating power factor Starting current Rated Heating capacity Rated power consumption Operating current Operating power factor
Standard performance
External finish (Munsell colour-coded markings) Dimensions H o W o D (Note 1) Heat exchanger type
Compressor
Fan
Defrost method Pressure gauge
Protection
Noise level Weight
Refrigerant pipe size
Refrigerant
Note 1: External dimensions in parentheses indicate the dimensions of protruding parts. Note 2: Rating conditions (JIS B 8616) Cooling : Indoor : D.B. 27: W.B. 19.0:
Heating Cooling
Starting current Rated power supply
Model Type o quantity Starting method Motor output Capacity control Daily cooling capacity Heater <crankcase> Refrigerating oil (Model) Type o quantity Airflow Motor output
High pressure protection Compressor protection Blower protection
devices
Frequency converter circuit
Type o charge amount Control method
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 20:
: Outdoor : D.B. 7: W.B. 6:
Service Ref
Gas Liquid
Unit
kW kW
A
%
A kW kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min
W
dB
kg
[ mm [ mm
kg
3 phase 380-400-415V 50Hz / 380V 60Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 1020 o 350 (+30)
Fully enclosed type o 1
Frequency converter start
Cooling 27-100% Heating 25-100%
Propeller (direct) o 2
High pressure pressure sensor (3.0MPa)
Overheating, excessive current protection
PUMY-125YM1
14.0
5.95
9.6-9.1-8.8 / 9.6 94
8.0
16.0
5.58
9.0-8.6-8.3 / 9.0 94
8.0
Crossover fin
EHV46FAK
3.5
1.9 (104Hz) —
1.4 (MS32)
90
60 o 2
Reverse cycle
Thermal switch Thermal switch
54
127
19.05
9.52
R22 o 8.5
Expansion valve
10
Item
Rated Cooling capacity Rated power consumption Operating current Operating power factor Starting current Rated Heating capacity Rated power consumption Operating current Operating power factor
Standard performance
External finish (Munsell colour-coded markings) Dimensions H o W o D (Note 1) Heat exchanger type
Compressor
Fan
Defrost method Pressure gauge
Protection
Noise level Weight
Refrigerant pipe size
Refrigerant Note 1: External dimensions in parentheses indicate the dimensions of protruding parts.
Note 2: Rating conditions (JIS B 8616) Cooling : Indoor : D.B. 27: W.B. 19.0:
Heating Cooling
Starting current Rated power supply
Model Type o quantity Starting method Motor output Capacity control Daily cooling capacity Heater <crankcase> Refrigerating oil (Model) Type o quantity Airflow Motor output
High pressure protection Compressor protection Blower protection
devices
Frequency converter circuit
Type o charge amount Control method
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 20:
: Outdoor : D.B. 7: W.B. 6:
Service Ref
Gas Liquid
Unit
kW kW
A
%
A kW kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min
W
dB
kg
[ mm [ mm
kg
3 phase 380-400-415V 50Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 1020 o 350 (+30)
Fully enclosed type o 1
Frequency converter start
Cooling 27-100% Heating 25-100%
Propeller (direct) o 2
High pressure pressure sensor (3.0MPa)
Overheating, excessive current protection
PUMY-125YMA
14.0
5.95
9.6-9.1-8.8 94
8.0
16.0
5.58
9.0-8.6-8.3 94
8.0
Crossover fin
EHV46FAK
3.5
1.9 (104Hz) —
1.4 (MS32)
90
60 o 2
Reverse cycle
Thermal switch Thermal switch
54
127
19.05
9.52
R22 o 8.5
Expansion valve
11
4 DATA
Model 20
Model Number for indoor unit
Model Capacity
Kcal/h kW w
20 22
Model 25
25 28
Model 32
32 36
Model 40
40 45
Model 50
50 56
Model 63
63 71
Model 71
71 80
Model 80
80 90
Model 100
100
112
Model 125
125 140
4-1. COOLING AND HEATING CAPACITY AND CHARACTERISTICS
4-1-1. Method for obtaining system cooling and heating capacity:
To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings of all the indoor units connected to the outdoor unit (see table below), and then use this total to find the standard capacity with the help of the tables on p.13~27.
(1) Capacity of indoor unit
w : Model of indoor unit “–A”
(2) Sample calculation
1System assembled from indoor and outdoor unit (in this example the total capacity of the indoor units is greater than that of the outdoor unit)
• Outdoor unit PUMY-125YM
• Indoor unit PKFY-P25VAM o 2 , PLFY-P50VLMD o 2
2According to the conditions in 1, the total capacity of the indoor unit will be: 25 o 2 + 50 o 2 = 150 3The following figures are obtained from the 150 total capacity row of the standard capacity table (p.23):
Capacity (kcal/h)
Cooling
13,026
AB
Heating
14,288
Outdoor unit power consumption (kW)
Cooling
6.15
Heating
5.98
Outdoor unit current (A)
Cooling
9.4
Heating
9.2
4-1-2. Method for obtaining the heating and cooling capacity of an indoor unit:
(1) The capacity of each indoor unit (kcal/h) = the capacity A(or B) o
(2) Sample calculation (using the system described above in 4-1-1. (2) ):
During cooling: During heating:
• The total model capacity of the indoor unit is: 25 o 2 + 50 o 2=150kcal/h Therefore, the capacity of PKFY-P25VAM and PLFY-P50VLMD will be calculated as follows by using the formula in 4-1-2. (1):
Model 25=13,026 o = 2,171kcal/h
Model 50=13,026 o = 4,342kcal/h
25
150
50
150
• The total model capacity of indoor unit is: 28 o 2 + 56 o 2=168kcal/h Therefore, the capacity of PKFY-P25VAM and PLFY­P50VLMD will be calculated as follows by using the for­mula in 4-1-2. (1):
Model 25=14,288 o = 2,381kcal/h
Model 50=14,288 o = 4,762kcal/h
total model capacity of all indoor units
model capacity
28
168
56
168
12
4-2. STANDARD CAPACITY DIAGRAM
• PUMY-71VM, PUMY-71VM1 STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units(kcal/h)
40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93
Capacity (kcal/h) Power consumption (kW) Current (A)
Cooling Heating
4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 6300 6400 6500 6600 6700 6800 6900 7000 7100 7122 7144 7166 7189 7211 7223 7255 7277 7299 7322 7344 7366 7388 7410 7432 7455 7477 7499 7542 7543 7566 7588
4500 4610 4720 4830 4940 5050 5160 5270 5380 5490 5600 5715 5831 5946 6062 6177 6292 6408 6523 6638 6754 6869 6985 7100 7213 7325 7438 7550 7663 7775 7888 8000 8012 8024 8036 8049 8061 8073 8085 8097 8109 8121 8133 8146 8158 8170 8182 8194 8206 8218 8231 8243 8255 8267
Cooling Heating
2.02
2.07
2.12
2.17
2.22
2.27
2.31
2.36
2.41
2.46
2.51
2.55
2.59
5.64
2.69
2.74
2.79
2.83
2.88
2.93
2.98
3.02
3.07
3.11
3.16
3.21
3.26
3.31
3.36
3.40
3.45
3.50
3.50
3.51
3.51
3.52
3.52
3.53
3.53
3.54
3.54
3.55
3.55
3.56
3.56
3.57
3.57
3.58
3.58
3.59
3.60
3.60
3.61
3.61
2.41
2.45
2.49
2.53
2.58
2.63
2.67
2.71
2.75
2.79
2.83
2.87
2.92
2.96
3.00
3.04
3.08
3.12
3.16
3.20
3.24
3.28
3.31
3.35
3.39
3.42
3.46
3.49
3.54
3.58
3.61
3.65
3.64
3.63
3.61
3.60
3.58
3.57
3.55
3.54
3.52
3.51
3.48
3.47
3.45
3.44
3.42
3.41
3.39
3.38
3.36
3.35
3.33
3.32
220V, 50Hz
Cooling Heating
10.1
10.4
10.6
10.8
11.1
11.3
11.6
11.8
12.0
12.3
12.5
12.7
13.0
13.2
13.4
13.7
13.9
14.2
14.4
14.6
14.9
15.1
15.3
15.6
15.8
16.0
16.3
16.5
16.8
17.0
17.2
17.5
18.7
18.8
18.8
18.8
18.8
18.9
18.9
18.9
18.9
19.0
19.0
19.0
19.0
19.1
19.1
19.1
19.1
19.2
19.2
19.2
19.3
19.3
12.0
12.2
12.4
12.7
12.9
13.1
13.3
13.5
13.7
13.9
14.2
14.4
14.6
14.8
15.0
15.2
15.4
15.6
15.8
16.0
16.2
16.4
16.5
16.7
16.9
17.1
17.3
17.5
17.7
17.9
18.0
18.2
19.5
19.4
19.3
19.2
19.1
19.1
19.0
18.9
18.8
18.7
18.6
18.6
18.5
18.4
18.3
18.2
18.1
18.1
18.0
17.9
17.8
17.7
13
• PUMY-71VM1 STANDARD CAPACITY DIAGRAM
10.8
11.0
11.2
11.5
11.7
11.9
12.1
12.3
12.5
12.7
12.9
13.1
13.3
13.5
13.7
13.9
14.1
14.3
14.5
14.7
14.9
15.1
15.2
15.4
15.6
15.8
16.0
16.1
16.3
16.5
16.7
16.8
17.0
17.2
17.3
17.5
17.6
17.6
17.6
17.5
17.4
17.4
17.3
17.2
17.1
17.1
17.0
16.9
16.9
16.8
16.7
16.6
16.6
16.5
16.4
16.4
16.3
16.2
16.2
Total capacity of
indoor units(kcal/h)
Capacity (kcal/h) Power consumption (kW) Current (A)
Cooling Heating
Cooling Heating
Cooling Heating 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93
3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 6300 6400 6500 6600 6700 6800 6900 7000 7100 7122 7144 7166 7189 7211 7233 7255 7277 7299 7322 7344 7366 7388 7410 7432 7455 7477 7499 7521 7543 7566 7588
3906 4025 4144 4263 4381 4500 4610 4720 4830 4940 5050 5160 5270 5380 5490 5600 5715 5831 5946 6062 6177 6292 6408 6523 6638 6754 6869 6985 7100 7213 7325 7438 7550 7663 7775 7778 8000 8012 8024 8036 8049 8061 8073 8085 8097 8109 8121 8133 8146 8158 8170 8182 8194 8206 8218 8231 8243 8255 8267
1.86
1.91
1.96
2.01
2.06
2.10
2.15
2.20
2.25
2.30
2.35
2.40
2.45
2.50
2.55
2.60
2.64
2.69
2.74
2.79
2.84
2.89
2.94
2.99
3.04
3.09
3.13
3.18
3.23
3.28
3.33
3.38
3.43
3.48
3.53
3.58
3.63
3.63
3.64
3.64
3.65
3.65
3.66
3.66
3.67
3.67
3.68
3.68
3.69
3.69
3.70
3.70
3.71
3.71
3.72
3.73
3.73
3.74
3.74
2.11
2.15
2.19
2.24
2.28
2.33
2.37
2.41
2.45
2.50
2.54
2.58
2.62
2.66
2.70
2.74
2.78
2.82
2.86
2.90
2.94
2.98
3.02
3.06
3.09
3.13
3.17
3.20
3.24
3.28
3.31
3.35
3.38
3.42
3.46
3.49
3.53
3.52
3.51
3.49
3.48
3.46
3.45
3.43
3.42
3.40
3.39
3.37
3.36
3.34
3.33
3.31
3.30
3.28
3.27
3.25
3.24
3.22
3.21
9.6
9.8
10.1
10.3
10.6
10.8
11.0
11.3
11.5
11.8
12.0
12.2
12.5
12.7
13.0
13.2
13.4
13.7
13.9
14.2
14.4
14.6
14.9
15.1
15.3
15.6
15.8
16.0
16.3
16.5
16.7
17.0
17.2
17.4
17.7
17.9
18.1
18.2
18.2
18.2
18.2
18.3
18.3
18.3
18.3
18.4
18.4
18.4
18.4
18.5
18.5
18.5
18.5
18.6
18.6
18.6
18.6
18.7
18.7
220V, 60Hz
14
• PUMY-71VM2 STANDARD CAPACITY DIAGRAM
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the table on page 12.
Total capacity of
w
indoor units(kW)
40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98
99 100 101 102 103 104
Capacity (kW)
Cooling Heating
4.00
4.10
4.20
4.30
4.40
4.50
4.60
4.70
4.80
4.90
5.00
5.10
5.20
5.30
5.40
5.50
5.60
5.70
5.80
5.90
6.00
6.10
6.20
6.30
6.40
6.50
6.60
6.70
6.80
6.90
7.00
7.10
7.20
7.30
7.40
7.50
7.60
7.70
7.80
7.90
8.00
8.02
8.05
8.07
8.09
8.12
8.14
8.16
8.19
8.21
8.23
8.25
8.28
8.30
8.32
8.35
8.37
8.39
8.41
8.44
8.46
8.48
8.51
8.53
8.55
4.44
4.56
4.67
4.78
4.89
5.00
5.12
5.24
5.35
5.47
5.59
5.71
5.83
5.94
6.06
6.18
6.30
6.41
6.53
6.64
6.75
6.87
6.98
7.10
7.20
7.32
7.43
7.54
7.66
7.77
7.88
8.00
8.11
8.22
8.33
8.44
8.56
8.67
8.78
8.89
9.00
9.01
9.03
9.04
9.05
9.06
9.08
9.09
9.10
9.11
9.13
9.14
9.15
9.16
9.18
9.19
9.20
9.21
9.23
9.24
9.25
9.26
9.28
9.29
9.30
Power consumption (kW)
Cooling Heating
1.83
1.87
1.91
1.95
1.99
2.03
2.08
2.12
2.15
2.21
2.25
2.29
2.33
2.37
2.41
2.45
2.50
2.54
2.57
2.62
2.66
2.70
2.75
2.78
2.82
2.87
2.91
2.95
2.99
3.03
3.08
3.13
3.17
3.20
3.25
3.29
3.33
3.38
3.41
3.45
3.50
3.50
3.50
3.51
3.51
3.52
3.52
3.53
3.53
3.54
3.54
3.55
3.55
3.56
3.56
3.57
3.57
3.58
3.58
3.59
3.59
3.59
3.59
3.60
3.60
220V, 50Hz 220V, 60Hz
2.05
2.09
2.13
2.16
2.20
2.24
2.27
2.30
2.35
2.39
2.42
2.27
2.50
2.53
2.57
2.62
2.66
2.68
2.73
2.77
2.81
2.86
2.90
2.93
2.98
3.02
3.05
3.10
3.14
3.18
3.23
3.27
3.31
3.35
3.39
3.43
3.48
3.53
3.56
3.61
6.65
6.65
3.63
3.62
3.60
3.58
3.57
3.55
3.54
3.53
3.52
3.51
3.49
3.48
3.46
3.44
3.41
3.40
3.39
3.38
3.37
3.36
3.33
3.33
3.31
Current (A)
Cooling Heating
9.1
9.3
9.5
9.8
10.0
10.2
10.4
10.6
10.8
11.0
11.2
11.4
11.6
11.8
12.0
12.2
12.5
12.7
12.8
13.1
13.3
13.5
13.7
13.9
14.1
14.3
14.6
14.8
15.0
15.2
15.4
15.6
15.8
16.0
16.2
16.4
16.6
16.9
17.0
17.2
17.5
17.5
17.5
17.5
17.5
17.6
17.6
17.6
17.6
17.7
17.7
17.7
17.7
17.8
17.8
17.8
17.8
17.9
17.9
17.9
17.9
17.9
17.9
18.0
18.0
Power consumption (kW)
Cooling Heating
10.3
10.5
10.6
10.8
11.0
11.2
11.4
11.5
11.7
11.9
12.1
12.3
12.5
12.6
12.8
13.1
13.3
13.4
13.6
13.8
14.0
14.3
14.5
14.7
14.9
15.1
15.2
15.5
15.7
15.9
16.1
16.3
16.5
16.8
16.9
17.1
17.4
17.6
17.8
18.0
18.2
18.2
18.1
18.1
18.0
17.9
17.8
17.8
17.7
17.6
17.6
17.5
17.4
17.4
17.3
17.2
17.0
17.0
16.9
16.9
16.8
16.8
16.7
16.6
16.5
1.90
1.94
1.98
2.02
2.07
2.11
2.16
2.20
2.23
2.29
2.33
2.37
2.41
2.45
2.50
2.54
2.59
2.63
2.66
2.72
2.76
2.80
2.85
2.89
2.93
2.98
3.02
3.06
3.11
3.15
3.19
3.24
3.28
3.32
3.37
3.41
3.45
3.50
3.54
3.58
3.63
3.63
3.63
3.64
3.64
3.65
3.65
3.66
3.66
3.67
3.67
3.68
3.68
3.69
3.69
3.70
3.70
3.71
3.71
3.72
3.72
3.72
3.72
3.73
3.73
1.99
2.02
2.06
2.09
2.13
2.16
2.20
2.23
2.27
2.31
2.34
2.20
2.42
2.45
2.49
2.53
2.57
2.60
2.64
2.68
2.72
2.76
2.80
2.84
2.88
2.92
2.95
2.99
3.04
3.08
3.12
3.16
3.20
3.24
3.28
3.32
3.36
3.41
3.45
3.49
3.53
3.53
3.51
3.50
3.48
3.47
3.46
3.44
3.43
3.41
3.40
3.39
3.37
3.36
3.35
3.33
3.30
3.29
3.28
3.27
3.26
3.25
3.23
3.22
3.20
220V, 50Hz/60Hz
Current (A)
Cooling Heating
9.5
9.7
9.9
10.1
10.3
10.5
10.8
11.0
11.2
11.4
11.6
11.8
12.1
12.3
12.5
12.7
12.9
13.2
13.3
13.6
13.8
14.0
14.3
14.4
14.6
14.9
15.1
15.3
15.5
15.7
15.9
16.2
16.4
16.6
16.8
17.0
17.2
17.5
17.7
17.9
18.1
18.1
18.1
18.2
18.2
18.2
18.2
18.3
18.3
18.3
18.3
18.4
18.4
18.4
18.4
18.5
18.5
18.6
18.6
18.6
18.6
18.6
18.6
18.7
18.7
9.9
10.1
10.3
10.4
10.6
10.8
11.0
11.1
11.4
11.5
11.7
11.9
12.1
12.2
12.4
12.6
12.8
13.0
13.2
13.4
13.6
13.8
14.0
14.2
14.4
14.6
14.7
15.0
15.2
15.4
15.6
15.8
16.0
16.2
16.4
16.6
16.8
17.0
17.2
17.4
17.6
17.6
17.5
17.5
17.4
17.3
17.3
17.2
17.1
17.0
17.0
16.9
16.8
16.8
16.7
16.6
16.5
16.4
16.4
16.3
16.3
16.2
16.1
16.1
16.0
15
• PUMY-125VM, PUMY-125VM1 STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units(kcal/h)
63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98
99 100 101 102 103 104 105 106 107 108 109 110
111 112 113 114 115 116 117 118
Capacity (kcal/h)
Cooling
6300 6400 6500 6600 6700 6800 6900 7000 7100 7200 7300 7400 7500 7600 7700 7800 7900 8000 8100 8200 8300 8400 8500 8600 8700 8800 8900 9000 9100 9200 9300 9400 9500 9600 9700 9800
9900 10000 10100 10200 10300 10400 10500 10600 10700 10800 10900 11000 11100 11200 11300 11400 11500 11600 11700 11800
Heating
7100 7213 7325 7438 7550 7663 7776 7888 8000 8111 8222 8333 8445 8556 8667 8778 8889 9000 9110 9220 9330 9440 9550 9660 9770 9880
9990 10100 10210 10320 10430 10540 10650 10760 10870 10980 11090 11200 11312 11424 11536 11648 11760 11872 11984 12096 12208 12320 12432 12544 12656 12768 12880 12992 13104 13216
Power consumption (kW) Current (A)
Cooling
2.74
2.78
2.83
2.87
2.92
2.96
3.01
3.06
3.11
3.16
3.21
3.25
3.30
3.35
3.40
3.45
3.51
3.57
3.62
3.67
3.73
3.78
3.84
3.89
3.95
4.01
4.07
4.13
4.19
4.25
4.31
4.37
4.43
4.50
4.56
4.62
4.68
4.75
4.81
4.88
4.95
5.02
5.08
5.15
5.22
5.29
5.35
5.43
5.50
5.57
5.64
5.72
5.79
5.86
5.94
6.02
Heating
2.88
2.92
2.97
3.01
3.07
3.11
3.15
3.20
3.24
3.29
3.33
3.38
3.43
3.47
3.52
3.57
3.61
3.66
3.71
3.76
3.80
3.85
3.90
3.96
4.01
4.06
4.11
4.16
4.21
4.26
4.31
4.36
4.41
4.46
4.51
4.57
4.62
4.67
4.72
4.78
4.84
4.89
4.95
5.00
5.05
5.11
5.16
5.22
5.27
5.33
5.38
5.44
5.50
5.55
5.61
5.68
Cooling
14.6
14.9
15.1
15.4
15.6
15.8
16.1
16.3
16.6
16.9
17.2
17.4
17.6
17.9
18.2
18.5
18.8
19.1
19.3
19.6
19.9
20.2
20.5
20.8
21.1
21.4
21.7
22.1
22.4
22.7
23.1
23.4
23.7
24.0
24.4
24.7
25.0
25.4
25.7
26.1
26.4
26.8
27.2
27.5
27.9
28.3
28.6
29.0
29.4
29.8
30.2
30.6
31.0
31.4
31.7
32.2
220V, 50Hz
Heating
15.4
15.6
15.9
16.1
16.4
16.6
16.8
17.1
17.3
17.6
17.8
18.1
18.3
18.6
18.8
19.1
19.3
19.6
19.9
20.1
20.3
20.6
20.9
21.2
21.4
21.7
22.0
22.2
22.5
22.8
23.0
23.3
23.6
23.9
24.1
24.5
24.7
25.0
25.3
25.6
25.9
26.1
26.5
26.7
27.0
27.3
27.6
27.9
28.2
28.5
28.8
29.1
29.4
29.7
30.0
30.3
16
• PUMY-125VM, PUMY-125VM1 STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units(kcal/h)
119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163
Capacity (kcal/h) Power consumption (kW) Current (A)
Cooling Heating
11900 12000 12100 12200 12300 12400 12500 12521 12542 12563 12584 12605 12626 12647 12668 12689 12710 12731 12753 12774 12795 12816 12837 12859 12879 12900 12921 12942 12963 12984 13005 13026 13047 13068 13089 13110 13131 13153 13174 13195 13216 13237 13258 13279 13300
13328 13440 13552 13664 13776 13888 14000 14012 14023 14035 14046 14058 14069 14081 14092 14104
14115 14127 14138 14150 14161 14173 14184 14196 14207 14219 14230 14242 14253 14265 14276 14288 14299
14311 14322 14334 14345 14357 14368 14380 14391 14403 14414 14426 14437
Cooling Heating
6.09
6.17
6.24
6.32
6.40
6.48
6.57
6.57
6.57
6.57
6.58
6.58
6.58
6.58
6.58
6.59
6.59
6.59
6.59
6.60
6.60
6.60
6.60
6.60
6.60
6.61
6.61
6.61
6.61
6.62
6.62
6.62
6.62
6.62
6.63
6.63
6.63
6.63
6.64
6.64
6.64
6.64
6.64
6.65
6.65
5.73
5.79
5.85
5.91
5.97
6.02
6.10
6.08
6.06
6.04
6.03
6.01
5.99
5.97
5.95
5.93
5.91
5.89
5.88
5.86
5.84
5.82
5.80
5.78
5.76
5.74
5.73
5.71
5.69
5.67
5.64
5.62
5.60
5.58
5.57
5.55
5.53
5.51
5.49
5.47
5.45
5.43
5.42
5.40
5.38
220V, 50Hz
Cooling Heating
32.6
33.0
33.4
33.8
34.2
34.6
34.9
34.9
34.9
34.9
35.2
35.2
35.2
35.2
35.2
35.2
35.2
35.2
35.2
35.3
35.3
35.3
35.3
35.3
35.3
35.4
35.4
35.4
35.4
35.4
35.4
35.4
35.4
35.4
35.5
35.5
35.5
35.5
35.5
35.5
35.5
35.5
35.5
35.6
35.6
30.6
30.9
31.3
31.6
31.9
32.2
32.6
32.5
32.4
32.3
32.2
32.1
32.0
31.9
31.8
31.7
31.6
31.5
31.4
31.3
31.2
31.1
31.0
30.9
30.8
30.7
30.6
30.5
30.4
30.3
30.2
30.1
30.0
29.9
29.8
29.7
29.6
29.5
29.4
29.3
29.2
29.0
29.0
28.9
28.8
17
• PUMY-125VM1 STANDARD CAPACITY DIAGRAM
15.1
15.3
15.5
15.8
16.0
16.2
16.4
16.7
16.9
17.1
17.4
17.6
17.9
18.1
18.3
18.6
18.8
19.1
19.3
19.6
19.8
20.1
20.3
20.6
20.8
21.1
21.3
21.6
21.9
22.1
22.4
22.6
22.9
23.2
23.4
23.7
24.0
24.2
24.5
24.8
25.1
25.3
25.6
25.9
26.2
26.5
26.7
27.0
27.3
27.6
27.9
28.2
28.5
28.7
29.0
29.3
29.6
Total capacity of
indoor units(kcal/h)
Capacity (kcal/h) Power consumption (kW) Current (A)
Cooling Heating
Cooling Heating
Cooling Heating 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119
2.68
2.72
2.77
2.81
2.86
2.90
2.95
2.99
3.04
3.09
3.14
3.18
3.23
3.28
3.33
3.38
3.44
3.49
3.54
3.59
3.65
3.70
3.76
3.81
3.87
3.92
3.98
4.04
4.10
4.16
4.22
4.28
4.34
4.40
4.46
4.52
4.58
4.65
4.71
4.78
4.84
4.91
4.97
5.04
5.11
5.18
5.24
5.31
5.38
5.45
5.52
5.60
5.67
5.74
5.81
5.89
5.96
2.85
2.89
2.94
2.98
3.03
3.07
3.11
3.16
3.20
3.25
3.29
3.34
3.39
3.43
3.48
3.53
3.57
3.62
3.67
3.72
3.76
3.81
3.86
3.91
3.96
4.01
4.06
4.11
4.16
4.21
4.26
4.31
4.36
4.41
4.46
4.52
4.57
4.62
4.67
4.73
4.78
7.83
4.89
4.94
4.99
5.05
5.10
5.16
5.21
5.27
5.32
5.38
5.44
5.49
5.55
5.61
5.66
14.2
14.4
14.6
14.9
15.1
15.3
15.6
15.8
16.1
16.3
16.5
16.8
17.1
17.3
17.6
17.8
18.1
18.4
18.7
18.9
19.2
19.5
19.8
20.1
20.4
20.7
20.9
21.2
21.5
21.9
22.2
22.5
22.8
23.1
23.4
23.7
24.1
24.4
24.7
25.1
25.4
25.7
26.1
26.4
26.8
27.1
27.5
27.8
28.2
28.5
28.9
29.3
29.6
30.0
30.4
30.8
31.2
6300 6400 6500 6600 6700 6800 6900 7000 7100 7200 7300 7400 7500 7600 7700 7800 7900 8000 8100 8200 8300 8400 8500 8600 8700 8800 8900 9000 9100 9200 9300 9400 9500 9600 9700 9800
9900 10000 10100 10200 10300 10400 10500 10600 10700 10800 10900 11000 11100 11200 11300 11400 11500 11600 11700 11800 11900
7100 7213 7325 7438 7550 7663 7775 7888 8000 8111 8222 8333 8445 8556 8667 8778 8889 9000 9110 9220 9330 9440 9550 9660 9770 9880
9990 10100 10210 10320 10430 10540 10650 10760 10870 10980
11090 11200 11312 11424 11536 11648 11760 11872
11984 12096 12208 12320 12432 12544 12656 12768 12880 12992 13104 13216 13328
220V, 60Hz
18
• PUMY-125VM1 STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units(kcal/h)
120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163
Capacity (kcal/h) Power consumption (kW) Current (A)
Cooling Heating
12000 12100 12200 12300 12400 12500 12521 12542 12563 12584 12605 12626 12647 12668 12689 12710 12731 12753 12774 12795 12816 12837 12858 12879 12900 12921 12942 12963 12984 13005 13026 13047 13068 13089
13110 13131 13153 13174 13195 13216 13237 13258 13279 13300
13440 13552 13664 13776 13888 14000 14012 14023 14035 14046 14058 14069 14081 14092 14104 14115 14127 14138 14150 14161 14173 14184 14196 14207 14219 14230 14242 14253 14265 14276 14288 14299 14311 14322 14334 14345 14357 14368 14380 14391 14403 14414 14426 14437
Cooling Heating
6.04
6.11
6.19
6.26
6.34
6.43
6.43
6.43
6.43
6.44
6.44
6.44
6.44
6.44
6.45
6.45
6.45
6.45
6.46
6.46
6.46
6.46
6.46
6.47
6.47
6.47
6.47
6.47
6.48
6.48
6.48
6.48
6.48
6.49
6.49
6.49
6.49
6.50
6.50
6.50
6.50
6.50
6.51
6.51
5.72
5.78
5.84
5.90
5.95
6.03
6.01
5.99
5.97
5.96
5.94
5.92
5.90
5.88
5.86
5.84
5.82
5.81
5.79
5.77
5.75
5.73
5.71
5.69
5.67
5.66
5.64
5.62
5.60
5.58
5.56
5.54
5.52
5.51
5.49
5.47
5.45
5.43
5.41
5.39
5.37
5.36
5.34
5.32
220V, 60Hz
Cooling Heating
31.5
31.9
32.3
32.7
33.1
33.6
33.6
33.6
33.6
33.6
33.6
33.6
33.6
33.6
33.6
33.6
33.7
33.7
33.7
33.7
33.7
33.7
33.7
33.7
33.7
33.8
33.8
33.8
33.8
33.8
33.8
33.8
33.8
33.8
33.9
33.9
33.9
33.9
33.9
33.9
33.9
33.9
33.9
33.9
29.9
30.2
30.5
30.8
31.1
31.5
31.4
31.3
31.2
31.1
31.0
30.9
30.8
30.7
30.6
30.5
30.5
30.4
30.3
30.2
30.1
30.0
29.9
29.8
29.7
29.6
29.5
29.4
29.3
29.2
29.1
29.0
28.9
28.8
28.7
28.6
28.5
28.4
28.3
28.2
28.1
28.0
27.9
27.9
19
• PUMY-125VM2 STANDARD CAPACITY DIAGRAM
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the table on page 12.
Total capacity of
w
indoor units(kW)
70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98
99 100 101 102 103 104 105 106 107 108 109
110 111 112 113 114 115 116 117 118
119 120 121 122 123 124 125 126 127 128
Capacity (kW)
Cooling Heating
7.00
7.10
7.20
7.30
7.40
7.50
7.60
7.70
7.80
7.90
8.00
8.10
8.20
8.30
8.40
8.50
8.60
8.70
8.80
8.90
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.20
10.30
10.40
10.50
10.60
10.70
10.80
10.90
11.00
11.10
11.20
11.30
11.40
11.50
11.60
11.70
11.80
11.90
12.00
12.10
12.20
12.30
12.40
12.50
12.60
12.70
12.08
7.88
8.00
8.11
8.22
8.33
8.44
8.56
8.67
8.78
8.89
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.22
10.33
10.45
10.56
10.67
10.79
10.90
11.02
11.13
11.24
11.36
11.47
11.59
11.70
11.81
11.93
12.04
12.16
12.27
12.38
12.50
12.63
12.75
12.88
13.00
13.13
13.25
13.38
13.50
13.63
13.75
13.88
14.00
14.13
14.25
14.38
14.50
Power consumption (kW) Power consumption (kW)
Cooling
2.73
2.76
2.80
2.84
2.88
2.92
2.96
3.00
3.05
3.09
3.12
3.17
3.21
3.26
3.30
3.35
3.39
3.45
3.49
3.53
3.58
3.63
3.68
3.72
3.78
3.82
3.88
3.92
3.98
4.03
4.07
4.13
4.18
4.24
4.28
4.34
4.39
4.45
4.51
4.56
4.62
4.68
4.74
4.79
4.85
4.90
4.97
5.02
5.09
5.15
5.21
5.27
5.33
5.39
5.45
5.52
5.58
5.64
5.71
220V, 50Hz 220V, 60Hz
Current (A)
Heating
2.88
2.91
2.95
2.98
3.03
3.06
3.10
3.14
3.18
3.21
3.26
3.30
3.33
3.38
3.42
3.45
3.50
3.54
3.57
3.62
3.66
3.71
3.75
3.79
3.84
3.88
3.92
3.96
4.01
4.06
4.10
4.14
4.19
4.23
4.27
4.32
4.36
4.42
4.46
4.50
4.55
4.60
4.65
4.70
4.74
4.79
4.84
4.89
4.94
4.98
5.04
5.08
5.14
5.18
5.24
5.29
5.33
5.39
5.44
Cooling Heating
14.6
14.8
15.0
15.2
15.4
15.6
15.8
16.1
16.3
16.5
16.7
16.9
17.2
17.4
17.7
17.9
18.1
18.4
18.7
18.9
19.1
19.4
19.7
19.9
20.2
20.4
20.7
21.0
21.3
21.6
21.8
22.1
22.4
22.7
22.9
23.2
23.5
23.8
24.1
24.4
24.7
25.0
25.3
25.6
25.9
26.2
26.6
26.9
27.2
27.5
27.9
28.2
28.5
28.8
29.2
29.5
29.8
30.2
30.5
15.4
15.6
15.8
16.0
16.2
16.4
16.6
16.8
17.0
17.2
17.4
17.7
17.8
18.1
18.3
18.5
18.7
18.9
19.1
19.4
19.6
19.8
20.1
20.3
20.5
20.8
21.0
21.2
21.5
21.7
21.9
22.2
22.4
22.6
22.9
23.1
23.3
23.6
23.9
24.1
24.3
24.6
24.8
25.1
25.4
25.6
25.9
26.1
26.4
26.7
26.9
27.2
27.5
27.7
28.0
28.3
28.5
28.8
29.1
Cooling Heating
2.67
2.70
2.74
2.78
2.82
2.85
2.90
2.94
2.98
3.03
3.06
3.10
3.14
3.19
3.23
3.27
3.32
3.37
3.41
3.46
3.50
3.56
3.60
3.64
3.70
3.74
3.79
3.84
3.89
3.94
3.99
4.04
4.10
4.15
4.19
4.25
4.30
4.36
4.41
4.46
4.52
4.58
4.64
4.69
4.74
4.80
4.86
4.92
4.98
5.04
5.10
5.15
5.22
5.27
5.34
5.40
5.46
5.52
5.59
2.84
2.87
2.92
2.95
2.99
3.03
3.07
3.10
3.14
3.18
3.22
3.26
3.30
3.34
3.38
3.41
3.46
3.50
3.53
3.58
3.62
3.66
3.71
3.75
3.79
3.84
3.88
3.91
3.97
4.01
4.05
4.10
4.14
4.18
4.23
4.27
4.31
4.37
4.41
4.45
4.50
4.55
4.59
4.65
4.69
4.73
4.79
4.83
4.88
4.93
4.98
5.03
5.08
5.12
5.18
5.23
5.27
5.33
5.38
220V, 50Hz/60Hz
Current (A)
Cooling Heating
13.9
14.1
14.3
14.5
14.7
14.9
15.1
15.4
15.6
15.8
16.0
16.2
16.4
16.7
16.9
17.1
17.3
17.6
17.8
18.1
18.3
18.6
18.8
19.0
19.3
19.5
19.8
20.0
20.3
20.6
20.8
21.1
21.4
21.7
21.9
22.2
22.5
22.8
23.0
23.3
23.6
23.9
24.2
24.5
24.8
25.1
25.4
25.7
26.0
26.3
26.6
26.9
27.3
27.6
27.9
28.2
28.5
28.9
29.2
14.8
15.0
15.2
15.4
15.6
15.8
16.0
16.2
16.4
16.6
16.8
17.1
17.2
17.4
17.7
17.8
18.1
18.3
18.5
18.7
18.9
19.1
19.4
19.6
19.8
20.0
20.3
20.4
20.7
20.9
21.2
21.4
21.6
21.9
22.1
22.3
22.5
22.8
23.0
23.3
23.5
23.8
24.0
24.3
24.5
24.7
25.0
25.2
25.5
25.7
26.0
26.3
26.5
26.8
27.0
27.3
27.6
27.8
28.1
20
• PUMY-125VM2 STANDARD CAPACITY DIAGRAM
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the table on page 12.
Total capacity of
w
indoor units(kW)
129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182
Capacity (kW)
Cooling Heating
12.90
13.00
13.10
13.20
13.30
13.40
13.50
13.60
13.70
13.80
13.90
14.00
14.02
14.04
14.06
14.08
14.10
14.12
14.15
14.17
14.19
14.21
14.23
14.25
14.27
14.30
14.32
14.34
14.36
14.38
14.40
14.42
14.45
14.47
14.49
14.51
14.53
14.55
14.57
14.60
14.62
14.64
14.66
14.68
14.70
14.72
14.75
14.77
14.79
14.81
14.83
14.85
14.87
14.89
14.63
14.75
14.88
15.00
15.13
15.25
15.38
15.50
15.63
15.75
15.88
16.00
16.01
16.02
16.03
16.04
16.06
16.07
16.08
16.09
16.10
16.12
16.13
16.14
16.15
16.16
16.17
16.19
16.20
16.21
16.22
16.23
16.25
16.26
16.27
16.28
16.29
16.31
16.32
16.33
16.34
16.35
16.36
16.38
16.39
16.40
16.41
16.42
16.44
16.45
16.46
16.47
16.48
16.50
Power consumption (kW) Power consumption (kW)
Cooling
5.77
5.84
5.91
5.97
6.04
6.11
6.17
6.24
6.30
6.37
6.45
6.57
6.58
6.58
6.58
6.59
6.59
6.59
6.60
6.60
6.60
6.61
6.61
6.61
6.61
6.63
6.63
6.63
6.64
6.64
6.64
6.65
6.65
6.65
6.66
6.66
6.66
6.66
6.67
6.67
6.67
6.68
6.68
6.68
6.69
6.69
6.69
6.70
6.70
6.70
6.70
6.71
6.71
6.71
220V, 50Hz 220V, 60Hz
Current (A)
Heating
5.50
5.54
5.60
5.65
6.71
6.76
5.82
5.86
5.91
5.97
6.02
6.10
6.09
6.07
6.05
6.03
6.01
6.00
5.98
5.97
5.95
5.94
5.91
5.89
5.88
5.86
5.85
5.83
5.82
5.79
5.77
5.76
5.74
5.73
5.71
5.70
5.67
5.65
5.64
5.62
5.61
5.59
5.58
5.55
5.53
5.52
5.50
5.49
5.47
5.46
5.43
5.41
5.40
5.38
Cooling Heating
30.9
31.2
31.6
31.9
32.3
32.7
33.0
33.4
33.7
34.1
34.5
34.9
35.2
35.2
35.2
35.3
35.3
35.3
35.3
35.3
35.3
35.4
35.4
35.4
35.4
35.4
35.4
35.4
35.5
35.5
35.5
35.5
35.5
35.5
35.6
35.6
35.6
35.6
35.7
35.7
35.7
35.7
35.7
35.7
35.8
35.8
35.8
35.8
35.8
35.8
35.8
35.9
35.9
35.9
29.4
29.6
29.9
30.2
30.5
30.8
31.1
31.2
31.6
31.9
32.2
32.6
32.6
32.4
32.3
32.3
32.2
32.1
32.0
31.9
31.8
31.7
31.6
31.5
31.5
31.3
31.3
31.2
31.1
31.0
30.9
30.8
30.7
30.6
30.5
30.5
30.3
30.2
30.2
30.0
30.0
29.9
29.8
29.7
29.6
29.5
29.4
29.3
29.2
29.2
29.1
28.9
28.9
28.8
Cooling Heating
5.65
5.72
5.78
5.85
5.91
5.98
6.04
6.11
6.17
6.24
6.31
6.43
6.44
6.44
6.44
6.45
6.45
6.45
6.46
6.46
6.46
6.47
6.47
6.47
6.47
6.48
6.48
6.48
6.49
6.49
6.49
6.51
6.51
6.51
6.52
6.52
6.52
6.52
6.53
6.53
6.53
6.54
6.54
6.54
6.55
6.55
6.55
6.56
6.56
6.56
6.56
6.57
6.57
6.57
5.44
5.48
5.53
5.59
5.64
5.70
5.75
5.79
5.85
5.90
5.95
6.03
6.02
6.00
5.98
5.97
5.94
5.93
5.91
5.90
5.88
5.87
5.85
5.82
5.81
5.79
5.78
5.76
5.75
5.73
5.71
5.70
5.67
5.66
5.64
5.63
5.61
5.59
5.58
5.55
5.54
5.52
5.51
5.49
5.47
5.46
5.44
5.42
5.40
5.39
5.37
5.35
3.34
5.32
220V, 50Hz/60Hz
Current (A)
Cooling Heating
29.5
29.9
30.2
30.5
30.9
31.2
31.6
31.9
32.2
32.6
33.0
33.6
33.7
33.7
33.7
33.7
33.7
33.7
33.8
33.8
33.8
33.8
33.8
33.8
33.8
33.9
33.9
33.9
33.9
33.9
33.9
34.0
34.0
34.0
34.0
34.0
34.0
34.0
34.1
34.1
34.1
34.2
34.2
34.2
34.2
34.2
34.2
34.3
34.3
34.3
34.3
34.3
34.3
34.3
28.4
28.6
28.9
29.2
29.5
29.8
30.0
30.3
30.5
30.8
31.1
31.5
31.4
31.3
31.2
31.2
31.1
31.0
30.9
30.8
30.7
30.7
30.5
30.4
30.4
30.3
30.2
30.1
30.0
29.9
29.8
29.8
29.6
29.6
29.5
29.4
29.3
29.2
29.1
29.0
29.0
28.9
28.8
28.7
28.6
28.5
28.4
28.3
28.2
28.2
28.1
27.9
27.9
27.8
21
• PUMY-125YM STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units(kcal/h)
Capacity (kcal/h)
Power consumption (kW) Current (A)
Cooling
Heating
Cooling
Heating
Cooling
Heating 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118
2.48
2.52
2.56
2.60
2.65
2.68
2.73
2.77
2.81
2.86
2.91
2.94
2.99
3.04
3.08
3.13
3.18
3.23
3.28
3.32
3.38
3.42
3.48
3.53
3.58
3.63
3.68
3.74
3.79
3.85
3.90
3.96
4.02
4.07
4.13
4.18
4.24
4.30
4.36
4.42
4.48
4.54
4.60
4.66
4.73
4.79
4.85
4.91
4.98
5.04
5.11
5.18
5.25
5.31
5.38
5.45
2.64
2.67
2.72
2.76
2.80
2.84
2.88
2.92
2.96
3.01
3.04
3.09
3.14
3.17
3.22
3.27
3.30
3.35
3.40
3.44
3.48
3.53
3.57
3.62
3.66
3.71
3.76
3.80
3.85
3.90
3.94
3.99
4.03
4.08
4.13
4.18
4.23
4.28
4.32
4.38
4.42
4.47
4.53
4.57
4.62
4.67
4.72
4.77
4.82
4.88
4.92
4.98
5.03
5.08
5.14
5.19
3.8
3.9
3.9
4.0
4.1
4.1
4.2
4.2
4.3
4.4
4.5
4.5
4.6
4.7
4.7
4.8
4.9
5.0
5.0
5.1
5.2
5.3
5.3
5.4
5.5
5.6
5.7
5.7
5.8
5.9
6.0
6.1
6.2
6.3
6.3
6.4
6.5
6.6
6.7
6.8
6.9
7.0
7.1
7.2
7.3
7.4
7.4
7.5
7.6
7.7
7.8
8.0
8.1
8.2
8.3
8.4
4.0
4.1
4.2
4.2
4.3
4.4
4.4
4.5
4.5
4.6
4.7
4.7
4.8
4.9
4.9
5.0
5.1
5.1
5.2
5.3
5.3
5.4
5.5
5.6
5.6
5.7
5.8
5.8
5.9
6.0
6.1
6.1
6.2
6.3
6.3
6.4
6.5
6.6
6.6
6.7
6.8
6.9
6.9
7.0
7.1
7.2
7.2
7.3
7.4
7.5
7.6
7.6
7.7
7.8
7.9
8.0
6300 6400 6500 6600 6700 6800 6900 7000 7100 7200 7300 7400 7500 7600 7700 7800 7900 8000 8100 8200 8300 8400 8500 8600 8700 8800 8900 9000 9100 9200 9300 9400 9500 9600 9700 9800
9900 10000 10100 10200 10300 10400 10500 10600 10700 10800 10900 11000 11100 11200 11300 11400 11500 11600 11700 11800
7100 7213 7325 7438 7550 7663 7776 7888 8000
8111 8222 8333 8445 8556 8667 8778 8889 9000 9110 9220 9330 9440 9550 9660 9770 9880 9990
10100 10210 10320 10430 10540 10650 10760 10870 10980
11090 11200 11312 11424 11536 11648 11760 11872
11984 12096 12208 12320 12432 12544 12656 12768 12880 12992 13104 13216
400V, 50Hz
22
• PUMY-125YM STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units(kcal/h)
119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163
Capacity (kcal/h) Power consumption (kW) Current (A)
Cooling Heating
11900 12000 12100 12200 12300 12400 12500 12521 12542 12563 12584 12605 12626 12647 12668 12689 12710 12731 12753 12774 12795 12816 12837 12858 12879 12900 12921 12942 12963 12984 13005 13026 13047 13068 13089
13110 13131 13153 13174 13195 13216 13237 13258 13279 13300
13328 13440 13552 13664 13776 13888 14000 14012 14023 14035 14046 14058 14069 14081 14092 14104 14115 14127 14138 14150 14161 14173 14184 14196 14207 14219 14230 14242 14253 14265 14276 14288 14299 14311 14322 14334 14345 14357 14368 14380 14391 14403 14414 14426 14437
Cooling Heating
5.52
5.59
5.65
5.73
5.79
5.87
5.95
5.96
5.97
5.97
5.98
5.99
6.00
6.01
6.01
6.02
6.03
6.04
6.05
6.05
6.06
6.07
6.08
6.09
6.09
6.10
6.11
6.12
6.13
6.13
6.14
6.15
6.16
6.17
6.17
6.18
6.19
6.20
6.21
6.21
6.22
6.23
6.24
6.25
6.25
5.24
5.29
5.35
5.40
5.46
5.51
5.58
5.60
5.61
5.63
5.64
5.66
5.68
5.69
5.71
5.72
5.74
5.76
5.77
5.79
5.80
5.82
5.84
5.85
5.87
5.88
5.90
5.92
5.93
5.95
5.96
5.98
6.00
6.01
6.03
6.04
6.06
6.08
6.09
6.11
6.12
6.14
6.16
6.17
6.19
400V, 50Hz
Cooling Heating
8.5
8.6
8.7
8.8
8.9
9.0
9.1
9.1
9.1
9.1
9.2
9.2
9.2
9.2
9.2
9.2
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.6
9.6
9.6
9.6
9.6
8.0
8.1
8.2
8.3
8.4
8.5
8.6
8.6
8.6
8.6
8.7
8.7
8.7
8.7
8.8
8.8
8.8
8.8
8.9
8.9
8.9
8.9
9.0
9.0
9.0
9.0
9.1
9.1
9.1
9.1
9.2
9.2
9.2
9.2
9.3
9.3
9.3
9.3
9.4
9.4
9.4
9.4
9.5
9.5
9.5
23
• PUMY-125YM1, PUMY-125YMA STANDARD CAPACITY DIAGRAM
Total capacity of indoor units(kW)
Capacity (kW)
Power consumption (kW) Current (A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
2.47
2.50
2.54
2.57
2.61
2.64
2.68
2.72
2.76
2.80
2.83
2.87
2.91
2.95
2.99
3.03
3.07
3.12
3.16
3.20
3.24
3.29
3.33
3.37
3.42
3.46
3.51
3.55
3.60
3.65
3.69
3.74
3.79
3.84
3.88
3.93
3.98
4.03
4.08
4.13
4.18
4.24
4.29
4.34
4.39
4.44
4.50
4.55
4.61
4.66
4.72
4.77
4.83
4.88
4.94
5.00
2.63
2.66
2.70
2.73
2.77
2.80
2.84
2.87
2.91
2.94
2.98
3.02
3.05
3.09
3.13
3.16
3.20
3.24
3.27
3.31
3.35
3.39
3.43
3.47
3.51
3.55
3.59
3.62
3.67
3.71
3.75
3.79
3.83
3.87
3.91
3.95
3.99
4.04
4.08
4.12
4.16
4.21
4.25
4.30
4.34
4.38
4.43
4.47
4.52
4.56
4.61
4.65
4.70
4.74
4.79
4.84
3.8
3.9
3.9
4.0
4.0
4.1
4.1
4.2
4.2
4.3
4.3
4.4
4.4
4.5
4.6
4.6
4.7
4.8
4.8
4.9
5.0
5.0
5.1
5.2
5.2
5.2
5.3
5.4
5.4
5.5
5.6
5.7
5.7
5.8
5.9
5.9
6.0
6.1
6.2
6.2
6.3
6.3
6.4
6.5
6.6
6.6
6.7
6.8
6.9
7.0
7.1
7.1
7.2
7.3
7.4
7.5
4.1
4.1
4.2
4.2
4.3
4.3
4.4
4.4
4.4
4.5
4.6
4.6
4.7
4.7
4.8
4.8
4.9
5.0
5.0
5.1
5.1
5.2
5.2
5.3
5.4
5.4
5.4
5.5
5.5
5.6
5.7
5.7
5.8
5.9
5.9
6.0
6.0
6.1
6.2
6.2
6.3
6.3
6.4
6.4
6.5
6.6
6.6
6.7
6.8
6.8
6.9
7.0
7.0
7.1
7.2
7.2
70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98
99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125
7.00
7.10
7.20
7.30
7.40
7.50
7.60
7.70
7.80
7.90
8.00
8.10
8.20
8.30
8.40
8.50
8.60
8.70
8.80
8.90
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.20
10.30
10.40
10.50
10.60
10.70
10.80
10.90
11.00
11.10
11.20
11.30
11.40
11.50
11.60
11.70
11.80
11.90
12.00
12.10
12.20
12.30
12.40
12.50
7.88
8.00
8.11
8.22
8.33
8.44
8.56
8.67
8.78
8.89
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.22
10.33
10.45
10.56
10.67
10.79
10.90
11.02
11.13
11.24
11.36
11.47
11.59
11.70
11.81
11.93
12.04
12.16
12.27
12.38
12.50
12.63
12.75
12.88
13.00
13.13
13.25
13.38
13.50
13.63
13.75
13.88
14.00
14.13
w
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the table on page 12.
415V, 50Hz
24
• PUMY-125YM1, PUMY-125YMA STANDARD CAPACITY DIAGRAM
Total capacity of indoor units(kW)
Capacity (kW)
Power consumption (kW) Current (A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
5.05
5.11
5.17
5.23
5.29
5.35
5.41
5.47
5.53
5.59
5.65
5.71
5.77
5.84
5.95
5.96
5.96
5.96
5.97
5.97
5.97
5.98
5.98
5.98
5.99
5.99
5.99
5.99
6.00
6.00
6.00
6.01
6.01
6.01
6.02
6.02
6.02
6.03
6.03
6.03
6.03
6.04
6.04
6.04
6.05
6.05
6.05
6.06
6.06
6.06
6.07
6.07
6.07
6.07
6.08
6.08
6.08
4.88
4.93
4.98
5.03
5.07
5.12
5.17
5.22
5.27
5.32
5.36
5.41
5.46
5.51
5.58
5.57
5.55
5.53
5.52
5.50
5.49
5.47
5.46
5.44
5.43
5.41
5.39
5.38
5.36
5.35
5.33
5.32
5.30
5.28
5.27
5.25
5.24
5.22
5.21
5.19
5.17
5.16
5.14
5.13
5.11
5.10
5.08
5.06
5.05
5.03
5.02
5.00
4.99
4.97
4.95
4.94
4.92
7.6
7.6
7.7
7.7
7.8
7.9
8.0
8.1
8.2
8.3
8.4
8.5
8.5
8.6
8.8
8.8
8.8
8.8
8.8
8.8
8.8
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
7.3
7.4
7.4
7.4
7.5
7.6
7.7
7.7
7.8
7.9
7.9
8.0
8.1
8.2
8.3
8.2
8.2
8.2
8.2
8.1
8.1
8.1
8.1
8.1
8.0
8.0
8.0
8.0
7.9
7.9
7.9
7.9
7.8
7.8
7.8
7.8
7.8
7.7
7.7
7.7
7.7
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.5
7.5
7.5
7.5
7.4
7.4
7.4
7.4
126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182
12.60
12.70
12.80
12.90
13.00
13.10
13.20
13.30
13.40
13.50
13.60
13.70
13.80
13.90
14.00
14.02
14.04
14.06
14.08
14.10
14.12
14.15
14.17
14.19
14.21
14.23
14.25
14.27
14.30
14.32
14.34
14.36
14.38
14.40
14.42
14.45
14.47
14.49
14.51
14.53
14.55
14.57
14.60
14.62
14.64
14.66
14.68
14.70
14.72
14.75
14.77
14.79
14.81
14.83
14.85
14.87
14.89
14.25
14.38
14.50
14.63
14.75
14.88
15.00
15.13
15.25
15.38
15.50
15.63
15.75
15.88
16.00
16.01
16.02
16.03
16.04
16.06
16.07
16.08
16.09
16.10
16.12
16.13
16.14
16.15
16.16
16.17
16.19
16.20
16.21
16.22
16.23
16.25
16.26
16.27
16.28
16.29
16.31
16.32
16.33
16.34
16.35
16.36
16.38
16.39
16.40
16.41
16.42
16.44
16.45
16.46
16.47
16.48
16.50
w
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the table on page 12.
415V, 50Hzw
25
• PUMY-125YM1, PUMY-125YMA STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units(kW)
Capacity (kW)
Power consumption (kW) Current (A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
2.47
2.50
2.54
2.57
2.61
2.64
2.68
2.72
2.76
2.80
2.83
2.87
2.91
2.95
2.99
3.03
3.07
3.12
3.16
3.20
3.24
3.29
3.33
3.37
3.42
3.46
3.51
3.55
3.60
3.65
3.69
3.74
3.79
3.84
3.88
3.93
3.98
4.03
4.08
4.13
4.18
4.24
4.29
4.34
4.39
4.44
4.50
4.55
4.61
4.66
4.72
4.77
4.83
4.88
4.94
5.00
2.63
2.66
2.70
2.73
2.77
2.80
2.84
2.87
2.91
2.94
2.98
3.02
3.05
3.09
3.13
3.16
3.20
3.24
3.27
3.31
3.35
3.39
3.43
3.47
3.51
3.55
3.59
3.62
3.67
3.71
3.75
3.79
3.83
3.87
3.91
3.95
3.99
4.04
4.08
4.12
4.16
4.21
4.25
4.30
4.34
4.38
4.43
4.47
4.52
4.56
4.61
4.65
4.70
4.74
4.79
4.84
4.2
4.2
4.3
4.3
4.4
4.5
4.5
4.6
4.6
4.7
4.7
4.8
4.9
4.9
5.0
5.1
5.1
5.2
5.3
5.3
5.4
5.5
5.6
5.6
5.7
5.7
5.8
5.9
5.9
6.0
6.1
6.2
6.3
6.3
6.4
6.5
6.6
6.7
6.7
6.8
6.9
6.9
7.0
7.1
7.2
7.3
7.4
7.4
7.5
7.6
7.7
7.8
7.9
8.0
8.1
8.2
4.4
4.5
4.6
4.6
4.7
4.7
4.8
4.8
4.9
4.9
5.0
5.0
5.1
5.2
5.2
5.3
5.3
5.4
5.5
5.5
5.6
5.7
5.7
5.8
5.9
5.9
5.9
6.0
6.1
6.1
6.2
6.3
6.3
6.4
6.5
6.5
6.6
6.7
6.7
6.8
6.9
6.9
6.9
7.0
7.1
7.2
7.2
7.3
7.4
7.4
7.5
7.6
7.7
7.7
7.8
7.9
70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98
99 100 101 102 103 104 105 106 107 108 109 110
111 112 113 114 115 116 117 118 119 120 121 122 123 124 125
7.00
7.10
7.20
7.30
7.40
7.50
7.60
7.70
7.80
7.90
8.00
8.10
8.20
8.30
8.40
8.50
8.60
8.70
8.80
8.90
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.20
10.30
10.40
10.50
10.60
10.70
10.80
10.90
11.00
11.10
11.20
11.30
11.40
11.50
11.60
11.70
11.80
11.90
12.00
12.10
12.20
12.30
12.40
12.50
7.88
8.00
8.11
8.22
8.33
8.44
8.56
8.67
8.78
8.89
9.00
9.10
9.20
9.30
9.40
9.50
9.60
9.70
9.80
9.90
10.00
10.10
10.22
10.33
10.45
10.56
10.67
10.79
10.90
11.02
11.13
11.24
11.36
11.47
11.59
11.70
11.81
11.93
12.04
12.16
12.27
12.38
12.50
12.63
12.75
12.88
13.00
13.13
13.25
13.38
13.50
13.63
13.75
13.88
14.00
14.13
w
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the table on page 12.
380V, 50Hz/60Hz
26
• PUMY-125YM1, PUMY-125YMA STANDARD CAPACITY DIAGRAM
Total capacity of
indoor units(kW)
Capacity (kW)
Power consumption (kW) Current (A)
Cooling
Heating
Cooling
Heating
Cooling
Heating
5.05
5.11
5.17
5.23
5.29
5.35
5.41
5.47
5.53
5.59
5.65
5.71
5.77
5.84
5.95
5.96
5.96
5.96
5.97
5.97
5.97
5.98
5.98
5.98
5.99
5.99
5.99
5.99
6.00
6.00
6.00
6.01
6.01
6.01
6.02
6.02
6.02
6.03
6.03
6.03
6.03
6.04
6.04
6.04
6.05
6.05
6.05
6.06
6.06
6.06
6.07
6.07
6.07
6.07
6.08
6.08
6.08
4.88
4.93
4.98
5.03
5.07
5.12
5.17
5.22
5.27
5.32
5.36
5.41
5.46
5.51
5.58
5.57
5.55
5.53
5.52
5.50
5.49
5.47
5.46
5.44
5.43
5.41
5.39
5.38
5.36
5.35
5.33
5.32
5.30
5.28
5.27
5.25
5.24
5.22
5.21
5.19
5.17
5.16
5.14
5.13
5.11
5.10
5.08
5.06
5.05
5.03
5.02
5.00
4.99
4.97
4.95
4.94
4.92
8.3
8.3
8.4
8.5
8.6
8.6
8.7
8.8
8.9
9.0
9.1
9.2
9.3
9.4
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
8.0
8.1
8.0
8.1
8.2
8.3
8.4
8.4
8.5
8.6
8.7
8.7
8.8
8.9
9.0
9.0
9.0
8.9
8.9
8.9
8.9
8.8
8.8
8.8
8.8
8.7
8.7
8.7
8.7
8.6
8.6
8.6
8.6
8.5
8.5
8.5
8.5
8.4
8.4
8.4
8.4
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.2
8.2
8.2
8.2
8.1
8.1
8.1
8.0
126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182
12.60
12.70
12.80
12.90
13.00
13.10
13.20
13.30
13.40
13.50
13.60
13.70
13.80
13.90
14.00
14.02
14.04
14.06
14.08
14.10
14.12
14.15
14.17
14.19
14.21
14.23
14.25
14.27
14.30
14.32
14.34
14.36
14.38
14.40
14.42
14.45
14.47
14.49
14.51
14.53
14.55
14.57
14.60
14.62
14.64
14.66
14.68
14.70
14.72
14.75
14.77
14.79
14.81
14.83
14.85
14.87
14.89
14.25
14.38
14.50
14.63
14.75
14.88
15.00
15.13
15.25
15.38
15.50
15.63
15.75
15.88
16.00
16.01
16.02
16.03
16.04
16.06
16.07
16.08
16.09
16.10
16.12
16.13
16.14
16.15
16.16
16.17
16.19
16.20
16.21
16.22
16.23
16.25
16.26
16.27
16.28
16.29
16.31
16.32
16.33
16.34
16.35
16.36
16.38
16.39
16.40
16.41
16.42
16.44
16.45
16.46
16.47
16.48
16.50
w
w Before calculating the sum of total capacity of indoor units, please convert
the valve into the kW model capacity following the table on page 12.
380V, 50Hz/60Hz
27
4-3. CORRECTING COOLING AND HEATING CAPACITY
0.4
-5 0 10 20 30 40 46
0.6
0.8
1.0
1.2
1.4
0.6
0.8
1.0
1.2
1.4
22 20 18 16
22 20 18 16
0.4
-12 -10 0 105-5 15
0.6
0.8
1.0
1.2
1.4
0.6
0.8
1.0
1.2
1.4
15 20
25
20 15
25
Service Ref PUMY-VM/VM1/YM PUMY-VM2/YM1/YMA
Rated cooling capacity Rated heating capacity
Indoor D.B. 27°C / W.B. 19.5°C Outdoor D.B. 35°C
Indoor D.B. 21°C Outdoor D.B. 7°C / W.B. 6°C
Indoor D.B. 27°C / W.B. 19.0°C Outdoor D.B. 35°C
Indoor D.B. 20°C Outdoor D.B. 7°C / W.B. 6°C
4-3-1. Correcting Changes in Air Conditions
(1)The performance curve charts (Figure 1, 2, 3, 4) show the rated capacity (total capacity) under the stated conditions when
standard length for piping (5m) is used. The rated power is derived from the capacity ratio and power ratio obtained for the indoor and outdoor intake temperatures at time 1.
• Standard conditions:
• Use the rated capacity and rated power values given in the characteristics table for each indoor unit.
• The capacity is the single value on the side of the outdoor unit; the capacity on the sides of each indoor unit must be added to obtain the total capacity.
(2)The capacity of each indoor unit may be obtained by multiplying the total capacity obtained in (1) by the ratio between the
individual capacity at the rated time and the total capacity at the rated time.
Individual capacity under stated conditions = total capacity under the stated conditions o
(3)Capacity correction factor curve
individual capacity at the rated time
total capacity at the rated time
Figure 1. PUMY-VM Cooling performance curve Figure 2. PUMY-VM Heating performance curve
PUMY-VM
1 PUMY-VM1
PUMY-YM PUMY-YM
Heating Capacity (ratio)
Heating Power consumption (ratio)
Cooling Capacity (ratio)
Cooling Power consumption (ratio)
INDOOR <W.B. :>
INDOOR <W.B. :>
INDOOR <D.B. :>
INDOOR <D.B. :>
Outdoor <D.B. ::>
28
Outdoor <W.B. ::>
Figure 3. PUMY-VM2 Cooling performance curve Figure 4. PUMY-VM2 Heating performance curve
0.4
-5 0 10 20 30 40 46
0.6
0.8
1.0
1.2
1.4
0.6
0.8
1.0
1.2
1.4
22 20 18 16
22 20 18 16
0.4
-12 -10 0 105-5 15
0.6
0.8
1.0
1.2
1.4
0.6
0.8
1.0
1.2
1.4
15 20
25
20 15
25
PUMY-YM
1 PUMY-VM1
PUMY-YMA PUMY-YMA
Cooling Capacity (ratio)
Cooling Power consumption (ratio)
INDOOR <W.B. :>
INDOOR <W.B. :>
Heating Capacity (ratio)
Heating Power consumption (ratio)
INDOOR <D.B. :>
INDOOR <D.B. :>
Outdoor <D.B. ::>
Outdoor <W.B. ::>
29
4-3-2. Correcting Capacity for Changes in the Length of Refrigerant Piping
1.0
0.95
0.9 5 10152025303540455055
1.0
35 (50%) 53 (75%)
71 (100%) 93 (130%)
0.95
0.9
0.85
0.8 5 101520253035404550
1.0
63 (50%) 94 (75%)
125 (100%) 163 (130%)
0.95
0.9
0.85
0.8 5 10152025303540455055
(1) During cooling, to obtain the ratio (and the equivalent piping length) of the outdoor units rated capacity and the total
in-use indoor capacity, first find the capacity ratio corresponding to the standard piping length (5m) from figures 5 and 6 at first, and then multiply by the cooling capacity from Figure 1 to obtain the actual capacity.
(2) During heating, to find the equivalent piping length, first find the capacity ratio corresponding to standard piping length (5m)
from Figure 7, and then multiply by the heating capacity from Figure 2 to obtain the actual capacity.
(1) Cooling capacity correction factor Figure 5. PUMY-71VM, PUMY-71VM
Cooling Capacity (ratio)
piping length (m)
Figure 6. PUMY-125VM, PUMY-125VM1, PUMY-125YM, PUMY-125VM2, PUMY-125YM1, PUMY-125YMA
Cooling capacity correction curve
1, PUMY-71VM2 Cooling capacity correction curve
Total capacity for indoor unit
Total capacity for indoor unit
Cooling Capacity (ratio)
piping length (m)
(2) Heating capacity correction factor Figure 7. PUMY Series Heating capacity correction curve
Heating Capacity (ratio)
piping length (m)
(3) Method for Obtaining the Equivalent Piping Length
Equivalent length for type 125 = (length of piping to farthest indoor unit) + (0.35 o number of bends in the piping) (m)
Length of piping to farthest indoor unit: type 125.....70m
4-3-3. Correction of Heating Capacity for Frost and Defrosting
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature (°CWB)
Correction factor
6
1.0
4
0.98
2
0.89
0.88
30
0
-2
0.89
-4
0.9
-6
0.95
-8
0.95
-10
0.95
PUMY-71VM PUMY-71VM1 PUMY-71VM2
90
NOTCH
Hi 52
SPL(dB) LINE
PUMY-125VM PUMY-125VM
1/VM2
PUMY-125YM/YMA
90
NOTCH
Hi 54
SPL(dB) LINE
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1m
MICROPHONE
1m
Ambient temperature 27:
Test conditions are based on JIS Z8731
31
5 OUTLINES AND DIMENSIONS
• OUTDOOR UNITS PUMY-71VM PUMY-71VM1 PUMY-71VM2
Optional parts
(base branching
pipe) installation
hole
Terminal block for transmission
Terminal block for central control
Terminal block for Power source
Gas refrigerant-pipe
connection {15.88(5/8F)
Liquid refrigerant-pipe
connection {9.52(3/8F)
Knock out hole for right piping
Knock out holes for power line 2-{27
unit : mm
shaped notched holes
(standard bolt M10)
Air intake
Air intake
Air outlet
Service panel
Handle for
Optional parts
moving
installation hole
Side air intake
Rear air intake
Handing for moving
Knock out holes for
power line 2-{27
Knock out hole
for front piping
Piping cover
Oval holes
(standard bolt M10)
Bottom piping hole
Drain hole
(3-{33 hole)
Handle for moving
32
Rear piping hole
when a piping cover is used for aesthetic reasons.
1...Indicates the dimensions of the cutoff valve connector.
2...Make sure that the panel can be easily removed for maintenance
PUMY-125VM PUMY-125VM1 PUMY-125VM2 PUMY-125YM PUMY-125YM1 PUMY-125YMA
Optional parts
(base branching
pipe) installation
hole
unit : mm
Knock out holes for power line 2-{29
Air intake
Terminal block for transmission
Terminal block for central control
Terminal block for power source
Air outlet
Handle for
Optional parts
installation hole
moving
Liquid refrigerant pipe
Gas refrigerant-pipe
connection {9.52 (3/8F)
connection {19.05 (3/4F)
Knock out hole for right piping
Knock out holes for
power line 2-{27
Knock out hole for
front piping
Oval holes
Piping cover
(standard bolt M10)
shaped notched holes
(standard bolt M10)
Bottom piping hole
Drain hole
(3-{33 hole)
Rear air intake
Side air intake
Handle for moving
33
Rear piping hole
when a piping cover is used for aesthetic reasons.
1...Indicates the dimensions of the cutoff valve connector.
2...Make sure that the panel can be easily removed for maintenance
6 WIRING DIAGRAM
21
2
1
5
4123
67
7
5
4321
CN2
6
1234
5
21
321
2
321
6
3
21
6
5
43 1263
7
321
54321
4321
6
V
U
U
W
WHT
12
3
6
C5
RED
RED
10
9652
1
7
3621
4
5
3
2123
1
1231121321
1
2
CN40
CN3D
(WHT)
(WHT)
C2
C1
ORN
ORN
RED
RED
WHT
WHT
BLU
WHT
MF1
MF2
CN41
<MULTI CONTROLLER BOARD>
TH1
26C
SLEV
TH5
63HS
TH6
TH2
SV152C
21S4
TB3
ON
OFF
CH
SW2
X3
X1
X2
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
FUSE2
(6A)
ORN ORN
BRN
YLW
(WHT)
(GRN)
(GRN)
(WHT)
RED
RED
BLK
BLK
WHT
BLU
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
2
RED
6
3
1
1 2
F.C
1234
CNCT
CN51
1
2
AC,CT
(YLW)
(YLW)
CNS2
(RED)
CNS1
(WHT)
(WHT)
(WHT)
(WHT) (WHT)
(BLK)
THHS
ON
OFF
SW5
FUSE1
(2A)
WHT
RED
YLW
645
12345678910
87654321
6
CN4
CN3
CN2
CN1
CN3
CN1
CN5
CN6
CH
CNA
52C 21S4
SV1
MF1
MF2
CND
<POWER SUPPLY BOARD>
SWU3
(3rd digit)
(2nd digit)
SWU2
(1st digit)
SWU1
LD1
(YLW)
(WHT)
(YLW)
(RED)
(WHT)
(YLW)
(RED)
(WHT)
(WHT)
(YLW)
26C
(BLK)
M1 M2
S
M1
1
3
RED
WHT
31
3
1
3
1
31
3
1
31
1
3
0
1
2 3
4
5
6
7
8
9
9
8 7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
N(-)
P(+)
P(+)
N(-)
V
W
U
V
W
RED
WHT
BLU
63 7
CN4
CN6
CN5
<GATE AMP BOARD>
AC.CT
<IPM>
(YLW)
(WHT)
(WHT)
CNCT
RED
FUSE(30A)
3 4
1
NF1
2
N
TB1
L
TB7
POWER SUPPLY
BRN
RED
WHT
RED
WHT
GRN/YLW
M2
S
52C
RED
RED
R1
D1
+
C3
ZNR
DS
R2
DCL
RED
RED
WHT
WHT
RED
63HS
TH6 TH5
SLEV
TH2 TH1
THHS
MC
12 321
SW3
ON
OFF
SW4
4
SW1
OFF
ON
34567821
1[ 220-240V 50Hz
10
9652
1
NAME
SYMBOL
NAME NAME
SYMBOL SYMBOL
AC,CT CH CNA CND CNS1 CNS2 CN1 CN2 CN3 CN4 CN5 CN6 CN40 CN41 CN51 CN3D CNCT C1,2 C3 C5 DS D1 DCL
F.C FUSE1 FUSE2 FUSE IPM LD1
MC MF1,2 NF1 R1 R2 SLEV SV1 SW1 SW2 SW3 SW4 SW5 SWU1 SWU2 SWU3 TB1
TB3 TB7
THHS TH1
TH2 TH5 TH6
X1 X2
X3 ZNR 21S4 26C 52C
63HS
CURRENT DETECTION CRANKCASE HEATER CONNECTOR <POWER SUPPLY> CONNECTOR <DC POWER SUPPLY> CONNECTOR <MULTI SYSTEM> CONNECTOR <CENTRALIZED CONTROL> CONNECTOR <CONTROLLER DRIVE CONTROL> CONNECTOR <POWER SYNC SIGNAL , PROTECTION> CONNECTOR <POWER SUPPLY 30V , 12V , 5V> CONNECTOR <INVERTER SIGNAL 5V> CONNECTOR <IPM POWER SUPPLY> CONNECTOR <IPM POWER SUPPLY , TROUBLE OUTPUT> CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> CONNECTOR <FOR STORING JUMPER CONNECTOR> CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> CONNECTOR <DEMAND SIGNAL,SILENT MODE INPUT> CONNECTOR <CURRENT DETECTION> FAN MOTOR CAPACITOR CAPACITOR<SMOOTHING> CAPACITOR<POWER FACTOR IMPROVEMENT> DIODE STACK DIODE <POWER FACTOR IMPROVEMENT> REACTOR
FAN CONTROL FUSE(2A) FUSE(6A) FUSE(30A) INTELLIGENT POWER MODULE DIGITAL INDICATION LED <OPERATION INSPECTION INDICATION> COMPRESSOR FAN MOTOR (INNER THERMOSTAT) NOISE FILTER RESISTOR<RUSH CURRENT PROTECT> RESISTOR<DISCHARGE> EXPANSION VALVE SOLENOID COIL <HOT GAS BYPASS> SWITCH <DISPLAY SELECTION SELFDIAGNOSIS> SWITCH <FUNCTION SELECTION> SWITCH <TEST RUN> SWITCH <MODEL SELECTION> SWITCH <FUNCTION SELECTION> SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT> SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT> SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT> TERMINAL BLOCK <POWER SUPPLY>
TERMINAL BLOCK <TRANSMISSION> TERMINAL BLOCK <TRANSMISSION> (CENTRALIZED CONTROL) THERMISTOR <IPM RADIATOR PANEL TEMPERATURE DETECTION> THERMISTOR<DISCHARGE TEMPERA TURE DETECTION> THERMISTOR <LOW PRESSURE SATURATED TEMPERATURE DETECTION> THERMISTOR <PIPE TEMPERATURE DETECTION,JUDGING DEFROST> THERMISTOR<OUTDOOR TEMPERA TURE DETECTION> RELAY <CRANKCASE HEATER,MAGNETIC CONTACTOR> RELAY<4-WAY VALVE> RELAY<SOLENOID VALVE> VARISTOR 4-WAY COIL THERMAL SWITCH <COMPRESSOR> MAGNETIC CONTACTOR <INVERTER MAIN CIRCUIT> HIGH PRESSURE SENSOR <DISCHARGE PRESSURE DETECTION>
Always lit
87
-
1
2
436
587
(Example) When the compressor and SV1 are turned during heating operation.
6
-
-
5
SV1
4
21S4
3
2
52C
1
Indication
Bit
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
1.Refer to the wiring boards of the indoor units for details on wiring of each indoor unit.
2.The transmission line is two-wire type and has no polarity.
3.Mark shows the terminal board,mark the connector .Symbols in parentheses () show the colors of connectors.
4.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication) found on the multi-controller of the outdoor unit. LED indication : Set all contacts of SW1 to OFF.
Compressor operated
PUMY-71VM
34
PUMY-125VM
SYMBOL
NAME NAME
SYMBOL
NAME
SYMBOL
AC,CT AR CB CH CNA CND CNS1 CNS2 CN1 CN2 CN3 CN4 CN5 CN6 CN40 CN41 CN51 CN3D C1,2 C3,4 C5,6 C7 D DB1,DB2
DCL F.C FUSE1 FUSE2 FUSE IPM LD1
MC MF1,2 NF RB RS SLEV SV1 SW1 SW2 SW3 SW4 SW5 SWU1 SWU2 SWU3 TB1
CURRENT DETECTION SURGE ABSORBER SMOOTHING CAPACITOR CRANKCASE HEATER CONNECTOR <POWER SUPPLY> CONNECTOR <DC POWER SUPPLY> CONNECTOR <MULTI SYSTEM> CONNECTOR <CENTRALIZED CONTROL> CONNECTOR <CONTROLLER DRIVE CONTROL> CONNECTOR <POWER SYNC SIGNAL , PROTECTION> CONNECTOR <POWER SUPPLY 30V,12V,5V> CONNECTOR <INVERTER SIGNAL 5V> CONNECTOR <IPM POWER SUPPLY> CONNECTOR <IPM POWER SUPPLY , TROUBLE OUTPUT> CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> CONNECTOR <FOR STORING JUMPER CONNECTOR> CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> CONNECTOR <DEMAND SIGNAL , SILENT MODE INPUT> FAN MOTOR CAPACITOR CAPACITOR <POWER FACTOR IMPROVEMENT> CAPACITOR CAPACITOR <FILTER> DIODE <POWER FACTOR IMPROVEMENT> DIODE STACK
REACTOR FAN CONTROL FUSE(2A) FUSE(6A) FUSE(60A) INTELLIGENT POWER MODULE DIGITAL INDICATION LED <OPERATIOIN INSPECTION INDICATION> COMPRESSOR FAN MOTOR (INNER THERMOSTAT) NOISE FILTER RESISTOR <DISCHARGE> RESISTOR <RUSH CURRENT PROTECT> EXPANSION VALVE SOLENOID COIL <HOT GAS BYPASS> SWITCH <DISPLAY SELECTION SELFDIAGNOSIS> SWITCH <FUNCTION SELECTION> SWITCH <TEST RUN> SWITCH <MODEL SELECTION> SWITCH <FUNCTION SELECTION> SWITCH <UNIT ADDRES SELECTION , 1ST DIGIT> SWITCH <UNIT ADDRESS SELECTION 2ND DIGIT> SWITCH <UNIT ADDRESS SELECTION 3RD DIGIT> TERMINAL BLOCK <POWER SUPPLY>
TB3 TB7
THHS TH1
TH2 TH5 TH6 X1 X2
X3 X4 ZNR 21S4 26C 52C
63HS
TERMINAL BLOCK <TRANSMISSION> TERMINAL BLOCK <TRANSMISSION> (CENTRALIZED CONTROL) THERMISTOR <IPM RADIATOR PANEL TEMPERATURE DETECTION> THERMISTOR <DISCHARGE TEMPERATURE DETECTION> THERMISTOR <LOW PRESSURE SATURATED TEMPERATURE DETECTION> THERMISTOR <PIPE TEMPERATURE DETECTION . JUDGING DEFROST> THERMISTOR <OUTDOOR TEMPERATURE DETECTION> RELAY < MAGNETIC CONTACTOR / CRANKCASE HEATER> RELAY<4-WAY VALVE> RELAY<SOLENOID VALVE> RELAY VARISTOR 4-WAY COIL THERMAL SWITCH <COMPRESSOR> MAGNETIC CONTACTOR <INVERTER MAIN CIRCUIT> HIGH PRESSURE SENSOR <DISCHARGE PRESSURE DETECTION>
-
4.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit.
LED indication:Set all contacts of SW1 to OFF.
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.The transmission line is two-wire type and has no polarity.
3.Mark shows the terminal board, mark the connector. Symbols in parentheses() show the colors of connectors.
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
Bit
Indication
Compressor operated
2
52C
3
4
5
6
78
1
21S4
SV1
-
-
Always lit
(Example) When the compressor and SV1 are
turned during heating operation.
1
243658
7
THHS
CN40 CN51 CN3D
(WHT) (WHT)(WHT)
CNS2
1
(YLW)
2
CNS1
1
(RED)
2
8
SWU3
<MULTI CONTROLLER BOARD>
4321
CN41
(WHT)
LD1
0
0
0
1
1
9
2 3
7
4
6
5
(2nd digit)(3rd digit)
9
8 7
6
5
SWU2
2 3
4
9
8 7
6
SWU1
(1st digit)
321543214321
1
2 3
4
5
CN1
6
3
THHS
(BLK)
(RED)
2
2132311
TH6
TH5
(WHT)
(GRN)
SW1
ON
OFF
12 876543
SW4
SW3
ON
OFF
12 4321 12345678
(YLW)
CN2
3
1
2
6
5
4
26C
<POWER SUPPLY BOARD>
3
4
2
5
6
1
2
3
6
TB3
M1 M2
M1 M2
S
TB7
S
TB1
L
N
BRN
BRN
ORN ORN
RED
RED
BLK
BLK
GRN
GRN/YLW
AR
RED
C5
FUSE(60A)
C6
RED
143
2
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
NO FUSE BREAKER 30A
POWER SUPPLY ~ (1 PHASE) 220-240V 50Hz
L
N
NF
RED BLK
GRN/YLW
FUSE2 (6A)
CNA
3
1
RED
BLU
3
WHT
CH
CH
1
WHT
DB1 DB2
YLW
X4
8
35
CH
2 3
1
X2X1X3
21S4
52C
1
3
1
3
YLW
52C SV1
YLW 7
3
YLW
RED
RED
21S4
BLK
RED
2
ZNR
3
RED
52C
1
BLK
X4
RS
3
BRN
BRN
SV1
1
RED
RED
DCL
C3 C4
5
CN1
(RED)
F.C
MF2
MF1
1
1
3
3
BLU
BLU
WHT
WHT
MF1
MF2
RED
RED
ORN
ORN
C2
C1
D
1
2
RED
WHT
3
RED
BLU
BLU
BLK
BLK
BRN
+
2
6
RB
CB
-
BLK
(YLW)
CND
2
1
RED
CN2
FUSE1 (2A)
3
BLK
RED
C7
BLK
<IPM>
(YLW)
CN5
2
1
2
1
CN5 CN6
(WHT) (WHT)
P(+)
N(-)
TH1
TH2TH5TH6
3121
TH2
TH1
(WHT)(GRN)
ON
OFF
ON
OFF
CN3
1
YLW
YLW
1
21
26C
(BLK)
(WHT)
CN6
10
9
6
5
6
5
10
6
9
<GATE AMP BOARD>
RED
WHT
V
U
W
MC
CN3
BLU
SW5
7
7
1
1
WVX4U
SW2
(WHT)
6
2
2
AC.CT
63HS
63HS
(WHT)
263
546
3
2
(WHT)
(WHT)
3
3
3
SLEV
3
6
456
123
321
SLEV
(WHT)
10987654321
1
1
CN4
657
AC.CT
(YLW)
(YLW)
213
4
2 1
RED
WHT
7
54362
1
7
CN4
(YLW)
PUMY-71VM1
21
2
1
5
4123
67
7
5
4321
CN2
6
1234
5
21
321
2
321
6
3
21
6
5
43 1263
7
321
54321
4321
6
V
U
U
W
WHT
12
3
6
C5
RED
RED
10
9652
1
7
3621
4
5
3
2123
1
1231
121321
1
2
CN40
CN3D
(WHT)
(WHT)
C2
C1
ORN
ORN
RED
RED
BLU
WHT
MF1
MF2
CN41
<MULTI CONTROLLER BOARD>
TH1
26C
SLEV
TH5
63HS
TH6
TH2
SV152C
21S4
ON
OFF
SW2
X3
X1
X2
FUSE2
(6A)
YLW
(WHT)
(GRN)
(GRN)
(WHT)
RED
RED
BLK
BLK
WHT
BLU
2
RED
6
3
1
1 2
F.C
1234
CNCT
CN51
1
2
AC,CT
(YLW)
(YLW)
CNS2
(RED)
CNS1
(WHT)
(WHT)
(WHT)
(WHT) (WHT)
(BLK)
THHS
ON
OFF
SW5
FUSE1
(2A)
WHT
RED
YLW
645
12345678910
87654321
6
CN4
CN3
CN2
CN1
CN3
CN1
CN5
CN6
CH
CNA
52C 21S4
SV1
MF1
MF2
CND
<POWER SUPPLY BOARD>
SWU3
(3rd digit)
(2nd digit)
SWU2
(1st digit)
SWU1
LD1
(YLW)
(WHT)
(YLW)
(RED)
(WHT)
(YLW)
(RED)
(WHT)
(WHT)
(YLW)
26C
(BLK)
1
3
RED
WHT
31
3
1
3
1
31
3
1
31
1
3
0
1
2 3
4
5
6
7
8
9
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
N(-)
P(+)
P(+)
N(-)
V
W
U
V
W
RED
WHT
BLU
63 7
CN4
CN6
CN5
<GATE AMP BOARD>
AC.CT
<IPM>
(YLW)
(WHT)
(WHT)
CNCT
FUSE(30A)
3 4
1
NF1
2
RED WHT
52C
RED
RED
R1
D1
+ C3
ZNR
DS
R2
DCL
RED
RED
WHT
WHT
RED
63HS
TH6 TH5
SLEV
TH2 TH1
THHS
MC
12 321
SW3
ON
OFF
SW4
4
SW1
OFF
ON
34567821
10
9652
1
TB3
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
ORN ORN
BRN
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
M1 M2
S
M1
NN
TB1
LL
TB7
POWER SUPPLY ~ (1 PHASE) 220-240/220V 50/60Hz
NO FUSE BREAKER 30A
BRN
RED WHT
RED
GRN/YLW
M2
S
NAME
SYMBOL
NAME NAME
SYMBOL SYMBOL
AC,CT CNA CND CNS1 CNS2 CN1 CN2 CN3 CN4 CN5 CN6 CN40 CN41 CN51 CN3D CNCT C1,2 C3 C5 DS D1 DCL
F.C FUSE1 FUSE2 FUSE IPM LD1
MC MF1,2 NF1 R1 R2 SLEV SV1 SW1 SW2 SW3 SW4 SW5 SWU1 SWU2 SWU3
TB1 TB3 TB7
THHS TH1
TH2 TH5 TH6
X1 X2 X3 ZNR 21S4 26C 52C
63HS
CURRENT DETECTION CONNECTOR <POWER SUPPLY> CONNECTOR <DC POWER SUPPLY> CONNECTOR <MULTI SYSTEM> CONNECTOR <CENTRALIZED CONTROL> CONNECTOR <CONTROLLER DRIVE CONTROL> CONNECTOR <POWER SYNC SIGNAL , PROTECTION> CONNECTOR <POWER SUPPLY 30V , 12V , 5V> CONNECTOR <INVERTER SIGNAL 5V> CONNECTOR <IPM POWER SUPPLY> CONNECTOR <IPM POWER SUPPLY , TROUBLE OUTPUT> CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> CONNECTOR <FOR STORING JUMPER CONNECTOR> CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> CONNECTOR <DEMAND SIGNAL,SILENT MODE INPUT> CONNECTOR <CURRENT DETECTION> FAN MOTOR CAPACITOR CAPACITOR<SMOOTHING> CAPACITOR<POWER FACTOR IMPROVEMENT> DIODE STACK DIODE <POWER FACTOR IMPROVEMENT> REACTOR
FAN CONTROL FUSE(2A) FUSE(6A) FUSE(30A) INTELLIGENT POWER MODULE DIGITAL INDICATION LED <OPERATION INSPECTION INDICATION> COMPRESSOR FAN MOTOR (INNER THERMOSTAT) NOISE FILTER RESISTOR<RUSH CURRENT PROTECT> RESISTOR<DISCHARGE> EXPANSION VALVE SOLENOID COIL <HOT GAS BYPASS> SWITCH <DISPLAY SELECTION SELFDIAGNOSIS> SWITCH <FUNCTION SELECTION> SWITCH <TEST RUN> SWITCH <MODEL SELECTION> SWITCH <FUNCTION SELECTION> SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT> SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT> SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT>
TERMINAL BLOCK <POWER SUPPLY> TERMINAL BLOCK <TRANSMISSION> TERMINAL BLOCK <TRANSMISSION> (CENTRALIZED CONTROL) THERMISTOR <IPM RADIATOR PANEL TEMPERATURE DETECTION> THERMISTOR<DISCHARGE TEMPERA TURE DETECTION> THERMISTOR <LOW PRESSURE SATURATED TEMPERATURE DETECTION> THERMISTOR <PIPE TEMPERATURE DETECTION,JUDGING DEFROST> THERMISTOR<OUTDOOR TEMPERA TURE DETECTION> RELAY <MAGNETIC CONTACTOR> RELAY<4-WAY VALVE> RELAY<SOLENOID VALVE> VARISTOR 4-WAY COIL THERMAL SWITCH <COMPRESSOR> MAGNETIC CONTACTOR <INVERTER MAIN CIRCUIT> HIGH PRESSURE SENSOR <DISCHARGE PRESSURE DETECTION>
Always lit
87
-
1
2
436
587
(Example) When the compressor and SV1 are turned during heating operation.
6
-
-
5
SV1
4
21S4
3
2
52C
1
Indication
Bit
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.The transmission line is two-wire type and has no polarity.
3.Mark shows the terminal board, mark the connector. Symbols in parentheses () show the colors of connectors.
4.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit. LED indication : Set all contacts of SW1 to OFF.
Compressor operated
36
PUMY-125VM1
SYMBOL
NAME
NAME
SYMBOL
NAME
SYMBOL AC,CT AR CB CNA CND CNS1 CNS2 CN1 CN2 CN3 CN4 CN5 CN6 CN40 CN41 CN51 CN3D C1,2 C3,4 C5,6 C7 D DB1,DB2
DCL F.C FUSE1 FUSE2 FUSE IPM LD1
MC MF1,2 NF RB RS SLEV SV1 SW1 SW2 SW3 SW4 SW5 SWU1 SWU2 SWU3
CURRENT DETECTION SURGE ABSORBER SMOOTHING CAPACITOR CONNECTOR <POWER SUPPLY> CONNECTOR <DC POWER SUPPLY> CONNECTOR <MULTI SYSTEM> CONNECTOR <CENTRALIZED CONTROL> CONNECTOR <CONTROLLER DRIVE CONTROL> CONNECTOR <POWER SYNC SIGNAL , PROTECTION> CONNECTOR <POWER SUPPLY 30V,12V,5V> CONNECTOR <INVERTER SIGNAL 5V> CONNECTOR <IPM POWER SUPPLY> CONNECTOR <IPM POWER SUPPLY , TROUBLE OUTPUT> CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> CONNECTOR <FOR STORING JUMPER CONNECTOR> CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> CONNECTOR <DEMAND SIGNAL , SILENT MODE INPUT> FAN MOTOR CAPACITOR CAPACITOR <POWER FACTOR IMPROVEMENT> CAPACITOR CAPACITOR <FILTER> DIODE <POWER FACTOR IMPROVEMENT> DIODE STACK
REACTOR FAN CONTROL FUSE(2A) FUSE(6A) FUSE(60A) INTELLIGENT POWER MODULE DIGITAL INDICATION LED <OPERATIOIN INSPECTION INDICATION> COMPRESSOR FAN MOTOR (INNER THERMOSTAT) NOISE FILTER RESISTOR <DISCHARGE> RESISTOR <RUSH CURRENT PROTECT> EXPANSION VALVE SOLENOID COIL <HOT GAS BYPASS> SWITCH <DISPLAY SELECTION SELFDIAGNOSIS> SWITCH <FUNCTION SELECTION> SWITCH <TEST RUN> SWITCH <MODEL SELECTION> SWITCH <FUNCTION SELECTION> SWITCH <UNIT ADDRES SELECTION , 1ST DIGIT> SWITCH <UNIT ADDRESS SELECTION 2ND DIGIT> SWITCH <UNIT ADDRESS SELECTION 3RD DIGIT>
TB1 TB3 TB7
THHS TH1
TH2 TH5 TH6 X1
X2 X3 X4 ZNR 21S4 26C 52C
63HS
TERMINAL BLOCK <POWER SUPPLY> TERMINAL BLOCK <TRANSMISSION> TERMINAL BLOCK <TRANSMISSION> (CENTRALIZED CONTROL) THERMISTOR <IPM RADIATOR PANEL TEMPERATURE DETECTION> THERMISTOR <DISCHARGE TEMPERATURE DETECTION> THERMISTOR <LOW PRESSURE SATURATED TEMPERATURE DETECTION> THERMISTOR <PIPE TEMPERATURE DETECTION . JUDGING DEFROST> THERMISTOR <OUTDOOR TEMPERATURE DETECTION> RELAY < MAGNETIC CONTACTOR> RELAY <4-WAY VALVE> RELAY <SOLENOID VALVE> RELAY VARISTOR 4-WAY COIL THERMAL SWITCH <COMPRESSOR> MAGNETIC CONTACTOR <INVERTER MAIN CIRCUIT> HIGH PRESSURE SENSOR <DISCHARGE PRESSURE DETECTION>
-
4.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication) found on the multi-controller of the outdoor unit. LED indication:Set all contacts of SW1 to OFF.
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.The transmission line is two-wire type and has no polarity.
3.Mark shows the terminal board, mark the connector. Symbols in parentheses() show the colors of connectors.
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
Bit
Indication
Compressor operated
2
52C
3
4
5
6
78
1
21S4
SV1
-
-
Always lit
(Example) When the compressor and SV1 are
turned during heating operation.
1
243658
7
THHS
CN40 CN51 CN3D
(WHT) (WHT)(WHT)
CNS2
1
(YLW)
2
CNS1
1
(RED)
2
8 7
SWU3
<MULTI CONTROLLER BOARD>
4321
CN41
(WHT)
LD1
0
0
0
1
1
9
2 3
4
6
5
(2nd digit)(3rd digit)
9
8
7
6
5
SWU2
2 3
4
9
8 7
6
5
SWU1
(1st digit)
321543214321
1
2
3
4
CN1
6
3
THHS
(BLK)
(RED)
2
2132311
TH6
TH5
(WHT)
(GRN)
SW1
ON
OFF
12 876543
SW4
SW3
ON
OFF
12 4321 12345678
(YLW)
CN2
3
1
2
6
5
4
<POWER SUPPLY BOARD>
3
2
4
5
6
1
2
3
6
TB3
M1 M2
M2
M1
S
TB7
S
TB1
L N
BRN BRN
ORN ORN
RED
RED
BLK
BLK
GRN
GRN/YLW
RED
C5 C6
AR
RED
FUSE(60A)
143
2
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
NO FUSE BREAKER 30A
POWER SUPPLY ~ (1 PHASE) 220-240 50/60Hz
L N
NF
RED BLK
GRN/YLW
FUSE2 (6A)
3
1
RED
CNA
BLU
3
CH
1
DB1 DB2
YLW
X4
8
37
CH
2 3
1
X2X1X3
21S4
52C
1
3
1
3
YLW
YLW
RED
RED
21S4
52C SV1
BLK
RED
2
ZNR
3
52C
BLK
1
X4
RS
YLW 7
3
BRN
BRN
SV1
1
3
RED
RED
DCL
C3
BLU
C4
RED
5
CN1
(RED)
F.C
MF2
MF1
1
1
3
3
BLU
BLU
WHT
WHT
MF1
MF2
RED
RED
ORN
ORN
C2
C1
D
1
2
RED
WHT
3
RED
BLU
+
2
6
BLK
BLK
BRN
RB
CB
-
BLK
(YLW)
CN2
FUSE1 (2A)
(YLW)
CN5
CND
2
2
1
3
1
BLK
RED
2
1
CN5 CN6
(WHT) (WHT)
RED
P(+)
C7
BLK
N(-)
<IPM>
TH1
TH2TH5TH6
3121
TH2
(WHT)(GRN)
ON
OFF
ON
OFF
1
26C
YLW
YLW
1
21
26C
(BLK)
(WHT)
10
9
6
5
6
5
10
6
9
<GATE AMP BOARD>
RED
WHT
V
U
W
MC
TH1
CN3
CN3
CN6
BLU
7
7
1
1
SW5
6
WVX4U
63HS
63HS
(WHT)
SW2
(WHT)
3 (WHT)
(WHT)
2
3
2
AC.CT
263
546
2
3
3
SLEV
3
6
456
123
321
SLEV
(WHT)
10987654321
1
1
CN4
2
AC.CT
(YLW)
1
RED
(YLW)
213
4
657
WHT
7
54362
1
7
CN4
(YLW)
PUMY-71VM2
21
2
1
5
4123
6
7
7
5
4
3
2
1
CN2
6
1234
5
21
10
96521321
2
321
6
3
2
1
6
5
43
1263
7
321543214321
6
V
U
U
W
WHT
12
3
6
C5
10
9652
1
7
3621
4
5
3
2123
11231
121321
1
2
CN40
CN3D
(WHT)
(WHT)
C2
C1
ORN
ORN
RED
RED
BLU
WHT
MF1
MF2
CN41
<MULTI CONTROLLER BOARD>
TH1
26C
SLEV
TH5
63HS
TH6
TH2
SV152C
21S4
TB3
ON
OFF
SW2
X3
X1
X2
X4
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
FUSE2
(6A)
ORN ORN
BRN
YLW
(WHT)
(GRN)
(GRN)
(WHT)
RED
RED
BLK
BLK
BLK
BLK
WHT
BLU
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
2
RED
6
3
1
1 2
F.C
1234
CNCT
CN51
1
2
AC,CT
(YLW)
(YLW)
CNS2
(RED)
CNS1
(WHT)
(WHT)
(WHT)
(WHT) (WHT)
(BLK)
THHS
ON
OFF
SW5
FUSE1
(2A)
WHT
RED
YLW
645
12345678910
87654321
6
CN4
CN3
CN2
CN1
CN3
CN1
CN5
CN6
CH
CNA
52C 21S4
SV1
MF1
MF2
CND
<POWER SUPPLY BOARD>
SWU3
(3rd digit)
(2nd digit)
SWU2
(1st digit)
SWU1
LD1
(YLW)
(WHT)
(YLW)
(RED)
(WHT)
(YLW)
(RED)
(WHT)
(WHT)
(YLW)
26C
(BLK)
M1 M2
S
M1
1
3
RED
WHT
3
1
3
13
1
31
3
1
31
1
3
0
1
2 3
4
5
6
7
8
9
9
8 7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
0
N(-)
P(+)
P(+)
N(-)
V
W
U
V
W
RED
WHT
BLU
63 7
CN4
CN6
CN5
<GATE AMP BOARD>
AC.CT
<IPM>
(YLW)
(WHT)
(WHT)
CNCT
FUSE(30A)
3 4
1
NF1
2
NN
TB1
LL
TB7
POWER SUPPLY ~ (1 PHASE) 220-240/220V 50/60Hz
NO FUSE BREAKER 30A
BRN
RED
WHT
REDRED
WHT
GRN/YLW
M2
S
52C
WHT BLU
YLW
R1
D1
+
C3
ZNR
DS
R2
DCL
RED
WHT BLU BLU
BLU
REDRED
63HS
TH6 TH5
SLEV
TH2 TH1
THHS
MC
12 321
SW3
ON
OFF
SW4
4
SW1
OFF
ON
34567821
NAMENAME NAME
SYMBOL SYMBOL
SYMBOL AC,CT CNA CND CNS1 CNS2 CN1 CN2 CN3 CN4 CN5 CN6 CN40 CN41 CN51 CN3D CNCT C1,2 C3 C5 DS D1 DCL F.C
FUSE1 FUSE2 FUSE IPM LD1
MC MF1,2 NF1 R1 R2 SLEV SV1 SW1 SW2 SW3 SW4 SW5 SWU1 SWU2 SWU3 TB1 TB3
TB7 THHS TH1
TH2 TH5 TH6
X1 X2 X3 ZNR 21S4 26C 52C
63HS X4
CURRENT DETECTION CONNECTOR <POWER SUPPLY> CONNECTOR <DC POWER SUPPLY> CONNECTOR <MULTI SYSTEM> CONNECTOR <CENTRALIZED CONTROL> CONNECTOR <CONTROLLER DRIVE CONTROL> CONNECTOR <POWER SYNC SIGNAL , PROTECTION> CONNECTOR <POWER SUPPLY 30V , 12V , 5V> CONNECTOR <INVERTER SIGNAL 5V> CONNECTOR <IPM POWER SUPPLY> CONNECTOR <IPM POWER SUPPLY , TROUBLE OUTPUT> CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> CONNECTOR <FOR STORING JUMPER CONNECTOR> CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> CONNECTOR <DEMAND SIGNAL,SILENT MODE INPUT> CONNECTOR <CURRENT DETECTION> FAN MOTOR CAPACITOR CAPACITOR<SMOOTHING> CAPACITOR<POWER FACTOR IMPROVEMENT> DIODE STACK DIODE <POWER FACTOR IMPROVEMENT> REACTOR FAN CONTROL
FUSE(2A) FUSE(6A) FUSE(30A) INTELLIGENT POWER MODULE DIGITAL INDICATION LED <OPERATION INSPECTION INDICATION> COMPRESSOR FAN MOTOR (INNER THERMOSTAT) NOISE FILTER RESISTOR<RUSH CURRENT PROTECT> RESISTOR<DISCHARGE> EXPANSION VALVE SOLENOID COIL <HOT GAS BYPASS> SWITCH <DISPLAY SELECTION SELFDIAGNOSIS> SWITCH <FUNCTION SELECTION> SWITCH <TEST RUN> SWITCH <MODEL SELECTION> SWITCH <FUNCTION SELECTION> SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT> SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT> SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT> TERMINAL BLOCK <POWER SUPPLY> TERMINAL BLOCK <TRANSMISSION>
TERMINAL BLOCK <TRANSMISSION> (CENTRALIZED CONTROL) THERMISTOR <IPM RADIATOR PANEL TEMPERATUER DETECTION> THERMISTOR<DISCHARGE TEMPERA TUER DETECTION> THERMISTOR <LOW PRESSURE SATURATED TEMPERATUER DETECTION> THERMISTOR
<PIPE TEMPERATUER DETECTION,JUDGING DEFROST> THERMISTOR<OUTDOOR TEMPERA TUER DETECTION> RELAY<MAGNETIC CONTACTOR> RELAY<4-WAY VALVE> RELAY<SOLENOID VALVE> VARISTOR 4-WAY COIL THERMAL SWITCH <COMPRESSOR> MAGNETIC CONTACTOR <INVERTER MAIN CIRCUIT> HIGH PRESSURE SENSOR <DISCHARGE PRESSURE DETECTION> RELAY
-
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.The transmission line is two-wire type and has no polarity.
3.Mark shows the terminal block, mark the connector.Symbols in parentheses() show the colors of connectors.
4.Self-diagnosis function The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication) found on the multi-controller of the outdoor unit. LED indication:Set all contacts of SW1 to OFF.
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
Bit
Indication
Compressor operated
2
52C
3
4
5
6
78
1
21S4
SV1
-
-
Always lit
(Example) When the compressor and SV1 are
turned during heating operation.
1
243658
7
38
PUMY-125VM2
SYMBOL SYMBOL
NAME NAME NAME
SYMBOL
AC,CT AR CB CNA CND CNS1 CNS2 CN1 CN2 CN3 CN4 CN5 CN6 CN40 CN41 CN51 CN3D C1,2 C3,4 C5,6 C7 D DB1,DB2 DCL
F.C FUSE1 FUSE2 FUSE IPM LD1
MC MF1,2 NF RB RS SLEV SV1 SW1 SW2 SW3 SW4 SW5 SWU1 SWU2 SWU3 TB1 TB3
CURRENT DETECTION SURGE ABSORBER SMOOTHING CAPACITOR CONNECTOR <POWER SUPPLY> CONNECTOR <DC POWER SUPPLY> CONNECTOR <MULTI SYSTEM> CONNECTOR <CENTRALIZED CONTROL> CONNECTOR <CONTROLLER DRIVE CONTROL> CONNECTOR <POWER SYNC SIGNAL , PROTECTION> CONNECTOR <POWER SUPPLY 30V,12V,5V> CONNECTOR <INVERTER SIGNAL 5V> CONNECTOR <IPM POWER SUPPLY> CONNECTOR <IPM POWER SUPPLY , TROUBLE OUTPUT> CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> CONNECTOR <FOR STORING JUMPER CONNECTOR> CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> CONNECTOR <DEMAND SIGNAL , SILENT MODE INPUT> FAN MOTOR CAPACITOR CAPACITOR <POWER FACTOR IMPROVEMENT> CAPACITOR CAPACITOR <FILTER> DIODE <POWER FACTOR IMPROVEMENT> DIODE STACK REACTOR
FAN CONTROL FUSE(2A) FUSE(6A) FUSE(60A) INTELLIGENT POWER MODULE DIGITAL INDICATION LED <OPERATION INSPECTION INDICATION> COMPRESSOR FAN MOTOR (INNER THERMOSTAT) NOISE FILTER RESISTOR <DISCHARGE> RESISTOR <RUSH CURRENT PROTECT> EXPANSION VALVE SOLENOID COIL <HOT GAS BYPASS> SWITCH <DISPLAY SELECTION SELF DIAGNOSIS> SWITCH <FUNCTION SELECTION> SWITCH <TEST RUN> SWITCH <MODEL SELECTION> SWITCH <FUNCTION SELECTION> SWITCH <UNIT ADDRESS SELECTION, 1ST DIGIT> SWITCH <UNIT ADDRESS SELECTION, 2ND DIGIT> SWITCH <UNIT ADDRESS SELECTION, 3RD DIGIT> TERMINAL BLOCK <POWER SUPPLY> TERMINAL BLOCK <TRANSMISSION>
TB7 THHS TH1
TH2 TH5 TH6 X1
X2 X3 X4 ZNR 21S4 26C 52C
63HS
TERMINAL BLOCK
<TRANSMISSION> (CENTRALIZED CONTROL)
THERMISTOR
<IPM RADIATOR PANEL TEMPERATURE DETECTION>
THERMISTOR <DISCHARGE TEMPERATURE DETECTION>
THERMISTOR
<LOW PRESSURE SATURATED TEMPERATURE DETECTION>
THERMISTOR
<PIPE TEMPERATURE DETECTION . JUDGING DEFROST>
THERMISTOR
<OUTDOOR TEMPERATURE DETECTION>
RELAY<MAGNETIC CONTACTOR>
RELAY<4-WAY VALVE>
RELAY<SOLENOID VALVE>
RELAY
VARISTOR
4-WAY COIL
THERMAL SWITCH <COMPRESSOR>
MAGNETIC CONTACTOR
<INVERTER MAIN CIRCUIT>
HIGH PRESSURE SENSOR
<DISCHARGE PRESSURE DETECTION>
-
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.The transmission line is two-wire type and has no polarity.
3.Mark shows the terminal block, mark the connector. Symbols in parentheses() show the colors of connectors.
4.Self-diagnosis function The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication) found on the multi-controller of the outdoor unit. LED indication:Set all contacts of SW1 to OFF.
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
Bit
Indication
Compressor operated
2
52C
3
4
5
6
78
1
21S4
SV1
-
-
Always lit
(Example) When the compressor and SV1 are
turned during heating operation.
1
243658
7
THHS
TH1
TH2TH5TH6
63HS
3
CN40 CN51 CN3D
(WHT) (WHT)(WHT)
CNS2
1
(YLW)
2
CNS1
1
(RED)
2
SWU3
TB3
M1
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
NO FUSE BREAKER 100A
POWER SUPPLY ~(1PHASE) 220-240/220V 50/60Hz
M2
M2
M1
S
S
LL
NN
TB7
TB1
BRN BRN
ORN
ORN
RED
RED
RED
BLK
BLK
GRN
GRN/YLW
C5 C6
<MULTI CONTROLLER BOARD>
<POWER SUPPLY BOARD>
AR
RED
FUSE(60A)
NF
143
2
RED
BLK
GRN/YLW
4321
CN41
(WHT)
LD1
0
0
0
1
1
9
2
8
3
7
4
6
5
FUSE2
(6A)
CNA
3
11
RED
9
9
2
8
8
3
7
7
4
6
6
5
SWU1
SWU2
(1st digit)
(2nd digit)(3rd digit)
CH CN6
1
3
3
BLU
YLW
52C SV1
DB1 DB2
2
3
1
YLW
YLW
X4
7
8
39
1
2 3
4
5
52C
X2X1X3
YLW
21S4
RED
2
3
BLK
1
321543214321
21S4
1
3
RED
RED
BLK
ZNR
52C
RS
3
BRN
BRN
CN1
6
6
CN1
F.C
MF2
MF1
SV1
131
3
RED
X4
1
RED
DCL
C3 C4
5
3
RED
WHT
BLU
WHT
MF1
MF2
RED
RED
ORN
C2
C1
D
1
2
RED
WHT
3
RED
BLU
BLU
2
6
RB
BLK
BLK
BLK
BRN
2311
THHS
TH6
TH5
(WHT)
(GRN)
3
32
(RED)
BLU
ORN
+ –
(BLK)
(RED)
2
CB
SW1
ON
OFF
12 876543
SW3
ON
OFF
12 4321 12345678
(YLW)
CN2
5
1
6
3
4
6
1
45
3
(YLW)
CN2
FUSE1 (2A)
(YLW)
CN5
CND
32
1
1
RED
BLK
1
RED
P(+)
C7
BLK
N(–)
<IPM>
21
2
SW4
1
TH2
OFF
OFF
3121
TH1
(WHT)(GRN)
ON
ON
CN3
7
26C
YLW
YLW
2
2
1
(WHT)
5
7
21
26C
CN3
(BLK)
6
9
10
1
6
6
9
10
5
2
CN5 CN6
(WHT) (WHT)
1
<GATE AMP BOARD>
BLU
RED
WHT
V
U
W
MC
SW2
SW5
(WHT)
6
(WHT)
2
2
WVX4U
AC.CT
63HS
(WHT)
263
546
3
2
(WHT)
3
3
3
321
1
1
123
SLEV
SLEV
(WHT)
10987654321
7
456
CN4
6
657
(YLW)
AC.CT
(YLW)
4
4
5
CN4
(YLW)
7
362
2 1
RED
WHT
213
1
PUMY-125YM
SMOOTHING CAPACITOR
C03
CAPACITOR <FILTER>
C01,C02
CONNECTOR <DISCHARGE CIRCUIT,POWER SUPPLY>
CNR
RESISTOR <RUSH CURRENT PROTECT>
RS1
RESISTOR <DISCHARGE>
RB1,RB2
RESISTOR <VOLTAGE BALANCE ADJUSTMENT>
RD1,RD2
RELAYX
X73
RELAY <SOLENOID VALVE>
X72
RELAY <4-WAY VALVE>
TERMINAL BLOCK <TRANSMISSION>
C1,C2
FAN MOTOR CAPACITOR
SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT>
SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT>
SWU3
SWU2
SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT>
SWU1
SWITCH <FUNCTION SELECTION>SW5
SWITCH <MODEL SELECTION>SW4
SWITCH <TEST RUN>SW3
THERMISTOR
<IPM RADIATOR PANEL TEMP. DETECTION>
THHS
INTELLIGENT POWER MODULEIPM
FAN CONTROL
F.C
CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY>
CN40
CONNECTOR <FOR STORING JUMPER CONNECTOR>
CN41
CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT>
CN51
CONNECTOR <INVERTER SIGNAL 5V>
CN4
CONNECTOR <POWER SUPPLY 30V,12V,5V>
CN3
CONNECTOR <POWER SYNC SIGNAL,PROTECTION>
CN2
CONNECTOR <CONTROLLER DRIVE CONTROL>
CN1
CONNECTOR <POWER SUPPLY>
CNA
CURRENT DETECTION
ACCT
SYMBOL
NAME
SYMBOL
NAMESYMBOL
NAME
SW2
SW1
SWITCH <FUNCTION SELECTION>
SWITCH <DISPLAY SELECTION>
CONNECTOR <DEMAND SIGNAL/SILENT MODE INPUT>
CN3D
REACTOR
THERMAL SWITCH <COMPRESSOR>
TERMINAL BLOCK <CENTRALIZED CONTROL>
TH2
TH5
TH6
63HS
52C
21S4
TH1
SV1
SLEV
MF1,MF2
LD1
X71
CNS1 CNS2
ZNR
FUSE2
TB7
TB3
TB1
MC
DCL
NF
FUSE1
49C
CONNECTOR <MULTI SYSTEM>
CONNECTOR <CENTRALIZED CONTROL>
FUSE(2A)
DIGITAL INDICATION LED
<OPERATION INSPECTION INDICATION>
FAN MOTOR(INNER THERMOSTAT)
EXPANSION VALVE
SOLENOID COIL <HOT GAS BYPASS>
HIGH PRESSURE SENSOR
<DISCHARGE PRESSURE DETECTION>
MAGNETIC CONTACTOR
4-WAY COIL
RELAY <MAGNETIC CONTACTOR>
VARISTOR
FUSE(6.3A)
COMPRESSOR(INNER THERMOSTAT)
NOISE FILTER
TERMINAL BLOCK <POWER SUPPLY>
THERMISTOR <DISCHARGE TEMP. DETECTION>
THERMISTOR
<LOW PRESSURE SATURATED TEMP. DETECTION>
THERMISTOR <OUTDOOR TEMP. DETECTION>
THERMISTOR
<PIPE TEMP. DETECTION:JUDGING DEFROST>
CB1,CB2
DM
SMOOTHING CAPACITOR
DIODE MODULE
NAME
SYMBOL
9
8
7
6
5
4
3
2
1
0
NO FUSE BREAKER 25A
L1 L2 L3
N
X
X
1
RD2
1
(WHT)
CN3D
(WHT)
CN51
(WHT)
CN41
(WHT)
CN40
53214321
43214321
YLW
CB2
CB1
CNR
(WHT)
CNR
(WHT)
(RED)
CNA
<POWER SUPPLY BOARD>
(YLW)
49C
(RED)
CN1
FUSE1
(6.3A)
FUSE2
(2A)
SLEV
6
1
2
5764
49C
YLW
31 1234567
1234567
12367123456
1236
123671236
CN4
CN3
CN2
CN4CN3CN2
(YLW)
(YLW)
(WHT)
(YLW)
(RED)
(YLW) (WHT)
2
4321
12345678
10987654321
2876543
SW3
SW5
OFF
ON
OFF
ON
SW4
SW1
SW2
OFF
ON
1
1
ON
OFF
ON
OFF
(YLW)
ACCT
654321
132
CN1
3
63HS
654
1321231
13 2121
THHS
TH1TH2TH5TH6
63HS
THHS
TH2
TH6 TH5
TH1
(BLK) (WHT)
(GRN)
(GRN)
(WHT)
(WHT)
SLEV
(WHT)
BLU
-
+
~
~
~
LO1 LO2 LO3
LI3
E
N
LI2
LI1
(RED)
31
CNA
13
GRN
6
YLW
YLW
WHT
BLK
RS1
RB2
RB1
RD1
BLK
RED
BLU
WHT
GRN
E
P
N
C03
C02C01
N
P1PN1
10
3 5 6 8
10
3
568
+ –
IPM
WV
+
+
RED WHT BLK
31 13
31
(BLU) 52C
X71
YLW
YLW
52C
31
(GRN)
21S4
X72
BLU
BLU
21S4
SV1
RED
RED
13
(BLK) SV1
(WHT)
MF2
(WHT)
MF1
MF1
C1
31
WHT
BLU
WHT
BLU
RED
ORN
RED
ORN
BLU
WHT
31
BLU
52C
N
BLU
L3
BLK
L1
RED
S
M1 M2
S
M2
M1
LD1
SWU1
(1rd digit)
SWU2
(2rd digit)(3rd digit)
SWU3
<RESISTOR BOARD>
CNS1 (RED)
CNS2 (YLW)
F.C
2
1
1
GRN/YLW
ZNR
+
BLU
BLK
2
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
WHT
BLK
WHT
RED
WHT
ORN
ORN
BRN
BRN
GROUND
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
POWER SUPPLY 3N~ 380/220-415/240V 50Hz 380/220 60Hz
W
V
U
U
X73
TB3
TB7
L2
TB1
MF2
C2
MC
DCL
DM
NF
<MULTI CONTROLLER BOARD>
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.Symbols used in wiring diagram above are. :Terminal block, :Connector, :Insertion tab.
3.Self-diagnosis function The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit. LED indication : Set all contacts of SW1 to OFF.
78563421
(Example)
When the compressor and SV1 are turned during heating operation.
Always lit---
SV1
21S4
1 8
7654
3
52C
2
Compressor operated
Indication
Bit
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
40
PUMY-125YM1, PUMY-125YMA
SMOOTHING CAPACITOR
C03
CAPACITOR <FILTER>
C01,C02
CONNECTOR <DISCHARGE CIRCUIT,POWER SUPPLY>
CNR
RESISTOR <RUSH CURRENT PROTECT>
RS1
RESISTOR <DISCHARGE>
RB1,RB2
RESISTOR <VOLTAGE BALANCE ADJUSTMENT>
RD1,RD2
RELAYX
X73
RELAY <SOLENOID VALVE>
X72
RELAY <4-WAY VALVE>
TERMINAL BLOCK <TRANSMISSION>
C1,C2
FAN MOTOR CAPACITOR
SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT>
SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT>
SWU3
SWU2
SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT>
SWU1
SWITCH <FUNCTION SELECTION>SW5
SWITCH <MODEL SELECTION>SW4
SWITCH <TEST RUN>SW3
THERMISTOR
<IPM RADIATOR PANEL TEMP. DETECTION>
THHS
INTELLIGENT POWER MODULEIPM
FAN CONTROL
F.C
CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY>
CN40
CONNECTOR <FOR STORING JUMPER CONNECTOR>
CN41
CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT>
CN51
CONNECTOR <INVERTER SIGNAL 5V>
CN4
CONNECTOR <POWER SUPPLY 30V,12V,5V>
CN3
CONNECTOR <POWER SYNC SIGNAL,PROTECTION>
CN2
CONNECTOR <CONTROLLER DRIVE CONTROL>
CN1
CONNECTOR <POWER SUPPLY>
CNA
CURRENT DETECTION
ACCT
SYMBOL
NAME
SYMBOL
NAMESYMBOL
NAME
SW2
SW1
SWITCH <FUNCTION SELECTION>
SWITCH <DISPLAY SELECTION>
CONNECTOR <DEMAND SIGNAL/SILENT MODE INPUT>
CN3D
REACTOR
THERMAL SWITCH <COMPRESSOR>
TERMINAL BLOCK <CENTRALIZED CONTROL>
TH2
TH5
TH6
63HS
52C
21S4
TH1
SV1
SLEV
MF1,MF2
LD1
X71
CNS1 CNS2
ZNR
FUSE2
TB7
TB3
TB1
MC
DCL
NF
FUSE1
49C
CONNECTOR <MULTI SYSTEM>
CONNECTOR <CENTRALIZED CONTROL>
FUSE(2A)
DIGITAL INDICATION LED
<OPERATION INSPECTION INDICATION>
FAN MOTOR(INNER THERMOSTAT)
EXPANSION VALVE
SOLENOID COIL <HOT GAS BYPASS>
HIGH PRESSURE SENSOR
<DISCHARGE PRESSURE DETECTION>
MAGNETIC CONTACTOR
4-WAY COIL
RELAY <MAGNETIC CONTACTOR>
VARISTOR
FUSE(6.3A)
COMPRESSOR(INNER THERMOSTAT)
NOISE FILTER
TERMINAL BLOCK <POWER SUPPLY>
THERMISTOR <DISCHARGE TEMP. DETECTION>
THERMISTOR
<LOW PRESSURE SATURATED TEMP. DETECTION>
THERMISTOR <OUTDOOR TEMP. DETECTION>
THERMISTOR
<PIPE TEMP. DETECTION:JUDGING DEFROST>
CB1,CB2
DM
SMOOTHING CAPACITOR
DIODE MODULE
NAME
SYMBOL
9
8
7
6
5
4
3
2
1
0
NO FUSE BREAKER 25A
L1 L2 L3
N
X
X
1
RD2
1
(WHT)
CN3D
(WHT)
CN51
(WHT)
CN41
(WHT)
CN40
53214321
43214321
YLW
CB2
CB1
CNR
(WHT)
CNR
(WHT)
(RED)
CNA
<POWER SUPPLY BOARD>
(YLW)
49C
(RED)
CN1
FUSE1
(6.3A)
FUSE2
(2A)
SLEV
6
1
2
5764
49C
YLW
31 1234567
1234567
12367123456
1236
123671236
CN4
CN3
CN2
CN4CN3CN2
(YLW)
(YLW)
(WHT)
(YLW)
(RED)
(YLW) (WHT)
2
4321
12345678
10987654321
2876543
SW3
SW5
OFF
ON
OFF
ON
SW4
SW1
SW2
OFF
ON
1
1
ON
OFF
ON
OFF
(YLW)
ACCT
654321
132
CN1
3
63HS
654
1321231
13 2121
THHS
TH1TH2TH5TH6
63HS
THHS
TH2
TH6 TH5
TH1
(BLK) (WHT)
(GRN)
(GRN)
(WHT)
(WHT)
SLEV
(WHT)
BLU
-
+
~
~
~
LO1 LO2 LO3
LI3
E
N
LI2
LI1
(RED)
31
CNA
13
GRN
6
YLW
YLW
WHT
BLK
RS1
RB2
RB1
RD1
BLK
RED
BLU
WHT
GRN
E
P
N
C03
C02C01
N
P1PN1
10
3 5 6 8
10
3
568
+ –
IPM
WV
+
+
RED WHT BLK
31 13
31
(BLU) 52C
X71
YLW
YLW
52C
31
(GRN)
21S4
X72
BLU
BLU
21S4
SV1
RED
RED
13
(BLK) SV1
(WHT)
MF2
(WHT)
MF1
MF1
C1
31
WHT
BLU
WHT
BLU
RED
ORN
RED
ORN
BLU
WHT
31
BLU
52C
N
BLU
L3
BLK
L1
RED
S
M1 M2
S
M2
M1
LD1
SWU1
(1rd digit)
SWU2
(2rd digit)(3rd digit)
SWU3
<RESISTOR BOARD>
CNS1 (RED)
CNS2 (YLW)
F.C
2
1
1
GRN/YLW
ZNR
+
BLU
BLK
2
FOR CENTRALIZED CONTROL DC 30V (Non-polar)
WHT
BLK
WHT
RED
WHT
ORN
ORN
BRN
BRN
GROUND
TO INDOOR UNIT CONNECTING WIRES DC 30V (Non-polar)
POWER SUPPLY 3N~ 380/220-415/240V 50Hz 380/220V 60Hz
W
V
U
U
X73
TB3
TB7
L2
TB1
MF2
C2
MC
DCL
DM
NF
<MULTI CONTROLLER BOARD>
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.Symbols used in wiring diagram above are. :Terminal block, :Connector, :Insertion tab.
3.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication) found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
78563421
(Example) When the compressor and SV1 are
turned during heating operation.
Always lit---
SV1
21S4
1 8
7654
3
52C
2
Compressor operated
Indication
Bit
•During normal operation The LED indicates the drive state of the controller in the outdoor unit.
41
7
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
051
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
056
001
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
010
101
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
002
102 104 154
1111
11
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
009
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
008
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
003
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
007
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
006
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
004
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
005
1 A transmission wire must be
connected to each refrigerant
system (outdoor and indoor).
2 Set addresses:
Outdoor unit ................051-100
Indoor unit ...................001-050
Remote controller .......101-200
Remote
controller
Remote
controller
Remote
controller
Remote
controller
105
Remote
controller
157
Remote
controller
107
Remote
controller
For centralized
management
For remote
controller
Address SW Address SW Address SW Address SW Address SW
Piping
Outdoor unit
Outdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unitIndoor unitIndoor unitIndoor unitIndoor unit
Address SW Address SW Address SW Address SW Address SW
Address SWAddress SWAddress SWAddress SWAddress SW
Address SWAddress SW
For centralized
management
For remote
controller
Transmission wire
2
1
NECESSARY CONDITIONS FOR SYSTEM CONSTRUCTION
7-1. TRANSMISSION SYSTEM SETUP
[Example : PUMY-125VM1]
42
7-2. REFRIGERANT SYSTEM DIAGRAM
Flare
Flare
Flare
Strainer
Strainer
Strainer
Strainer
Strainer
(Refrigerant flow)
Cooling Heating
Strainer
Compressor (MC)
Electronic expansion valve (SLEV)
Accumulator
Overcooling heat exchanger
Outdoor heat exchanger
Flare
Liquid pipe
Gas pipe
Connector
Connector
Service port
Service port
Thermistor TH23 for monitoring gas pipe temperature
Thermistor TH21 (intake temperature detection)
Thermistor TH22 (piping temperature detection)
Indoor heat exchanger
Linear expansion valve (LEV)
Thermistor TH2 (Saturation temperature of suction pressure)
Capillary tube 2
Capillary tube 3
Oil separator
Check valve (low pressure)
Thermistor THHS (Radiator panel temperature sensor)
Thermistor TH6 (outdoor air temperature sensor)
4-way valve
High-pressure sensor discharge pressure sensor (63HS)
Capillary tube 1
Check valve (High prssure)
Electromag­netic valve (SV1)
Thermistor TH5 (pipng temperature monitoring and determination)
Thermistor TH1 (discharge temperature sensor)
Indoor unit Outdoor unit
Refrigerant Piping Specifications (dimensions of flared connector)
Capacity
Indoor unit
Outdoor unit
PUMY-71VM PUMY-71VM
Item
20 , 25 , 32 , 40
50 , 63 , 71, 80
100 , 125
71
125
Capillary tube 1(for return of oil from oil separator)
1
{2.5 O {0.6 O 500r
Liquid piping Gas piping
{6.35 <1/4”> {9.52 <3/8”> {9.52 <3/8”>
{9.52 <3/8”> {9.52 <3/8”>
Capillary tube 2
(for Evaporating tempera­ture detection)
Capillary tube 3(for maintaining equilibrium between upper and lower coils)
{12.7 <1/2”> {15.88 <5/8”> {19.05 <3/4”>
{15.88 <5/8”> {19.05 <3/4”>
({4 O {3.0 O 500r) O 2{2.5 O {0.6 O 500r
PUMY-71VM2 PUMY-125VM
PUMY-125VM PUMY-125YM/YM1 PUMY-125YMA
1/VM2
{2.5 O {0.6 O 500r
({4 O {3.0 O 200r) O 2{2.5 O {0.6 O 500r
Concerning the Compressor
This system has a scroll compressor. This compressor uses a low pressure shell that typically has a temperature in the range 30-80°C. In addition, compressor wiring should be in the direction of rotation to the right. Wire colors are red (U), white(V), blue or black (W), yellow and yellow (thermal switch).
43
7-3. SYSTEM CONTROL
For indoor-outdoor transmission wire
Remote control wire
indoor-outdoor trnasmission cable
2 remote controller
Group operation (maximum 16 indoor units)
Outdoor unit
Indoor unit
Indoor unit Indoor unit
NR
NR
Remote controller network
Indoor unit Indoor unit
NR NR NR
7-3-1. Operating a Single Refrigerant System
When operating either alone or as part of a group, a M-NET remote controller (NR) may be used to control a single refrigerant system that does not overlap with any other system.
<Example of system arrangement>
Using a M-NET remote controller (NR)
Address setting must be performed.The NR wire and indoor and outdoor transmission wires must be a non-polar two wire cable.One NR may be connected to a maximum of 16 indoor unit. Two NR units may be used to perform control tasks (the second one pressed will have priority if two are pressed
simultaneously).
If the user plans to install multiple refrigerant
systems and a centralized controller in the future, it is strongly suggested that a NR be used.
44
7-3-2. System Controller (SC) to Perform Centralized Control
Transmission wire for central­ized control
<Room A>
For transmission wire
PAC-SC33KUA PAC-SC34KUA
<Room B>
<Room D> <Room E>
<Room C>
Outdoor
unit
Indoor unit
A
Indoor unit Indoor unit Indoor unit
Remote controller network
Remote control
wire
Indoor • outdoor transmission wire (Shielded wire)
SC: Centralized controller, linked system control board, group remote controller, etc.
A : M-NET or MA remote controller
(Coexistence of M-NET remote controller and MA remote controller is not admitted in the same system.)
Indoor unit
Indoor unitIndoor unitIndoor unitIndoor unitIndoor unit
Power supply installation
System controller
Outdoor
unit
Indoor • outdoor transmission wire (Shielded wire)
A
A
A
AA
<Example of System Arrangement>
The following diagram shows the use of system controller (SC) to control a system that includes the multiple outdoor unit.
Note 1) The NR, SC, indoor and outdoor unit all require address settings.
Indoor unit
Outdoor unit
M-NET R/C (Main)
M-NET R/C (Sub)
SC
MA Remote controller
Linked settings must be made within a group.
The lowest address of an indoor unit within a refrigerant system is +50.
The lowest address of an indoor unit within a group is +100.
The address of the main remote controller is +50.
Unnecessary address setting (Necessary main/sub set-
1 ~ 50
51 ~ 100 101 ~ 150 151 ~ 200
0 or 201 ~ 250
2) Indoor unit that may be connected with an SC are shown as follows.
Centralized controller Multi-unit controller board Group controller
3) There may be a maximum of two controllers when a group has 16 indoor units or less.
4) The transmission wire must have a power supply when an SC is used. Please connect the power supply for the transmission wire to the centralized controller transmission wire.
SC with 2 units or less SC with 3 to 5 units
5) Use a shielded wire (at least 1.25mm2)for the indoor, outdoor, and centralized controller transmission wires.
In addition, all shielded wires in a system must be grounded at one point. If the length of the remote control wire exceeds 10m, use an insulated wire for the extra portion.
50 group /50 units 24 group /50 units 8 group /16 units
Power supply for transmission wire PAC-SC33KU Power supply for transmission wire PAC-SC34KU
45
7-3-3. Example for the System
OC
IC
(051)
M1 M2
S
TB512TB15
12
TB15
NR
(001)
IC
M1 M2
S
TB5
(002)
NR
M1 M2 SM1 M2 S
TB3 TB7
L2
L1
r1 L3
r2
TB6
(101)
TB6
(102)
OC
(051)
IC
M1 M2 S
TB5
(001)
IC
TB5
(002)
NR
TB6
(101)
NR
TB6
(151)
NR
TB6
(102)
NR
TB6
(152)
M1 M2 S
M1 M2 SM1 M2 S
TB3 TB7
12
TB15
12
TB15
OC
IC
(051)
M1 M2 S
TB5
NR
(001)
IC
M1 M2 S
TB5
(002)
TB6
(101)
M1 M2 SM1 M2 S
TB3 TB7
Main
Sub
12
TB15
12
TB15
• Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed in the standard system with detailed explanation. The explanation for the system in this section : Use one single outdoor unit and multiple outdoor units for M-NET remote
control system. Use one single outdoor unit and multiple indoor units in the multiple outdoor units for the M-NET remote control system.
A. Example of a M-NET remote controller system (address setting is necessary.)
Example of wiring control cables Wiring Method and Address Setting
1. Standard operation
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use non-polarized two wire.
b. Connect terminals M1 and M2 on transmission
cable terminal block (TB5) for each indoor unit with the terminal block (TB6) for the remote controller (NR).
c. Set the address setting switch as shown below.
• One remote controller for each indoor unit.
• Inside ( ) Address: There is no need for setting the 100 position on the remote controller.
2. Operation using two remote controllers
• Using two remote controllers for each indoor unit.
Main
3. Group operation
• Multiple indoor units operated together by one remote controller
Combinations of 1through 3 above are possible.
Sub
Main
Sub
Unit
Indoor unit (IC)
Outdoor unit
(OC)
Remote
controller (NR)
Range
001 to 050 051 to 100 101 to 150
Setting Method
Use the most recent address of all the indoor unit plus 50. Indoor unit address plus
100.
a. Same as above. b. Same as above. c. Set address switch as shown below.
Unit
Indoor Unit (IC)
Outdoor unit
(OC)
Main Remote
Controller (NR)
Sub Remote
Controller (NR)
Range
001 to 050 051 to 100
101 to 150 151 to 200
Setting Method
Use the most recent address of all the indoor units plus 50. Indoor unit address plus
100. Indoor unit address plus
150.
a. Same as above. b. Connect terminals M1 and M2 on transmission cable
terminal block (TB5) of the IC main unit with the most most recent address within the same indoor unit (IC) group to terminal block (TB6) on the remote controller.
c. Set the address setting switch as shown below.
Unit
IC (Main)
IC (Sub)
Outdoor Unit
Main Remote
Controller
Sub Remote
Controller
Range
001 to 050
001 to 050
051 to 100 101 to 150 151 to 200
Use the most recent address within the same group of indoor units. Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be in sequence with the IC (Main). Use the most recent address of all the indoor units plus 50. Set at an IC (Main) address within the same group plus 100. Set at an IC (Main) address within the same group plus 150.
Setting Method
d. Use the indoor unit (IC) within the group with the most functions as the IC (Main) unit.
46
• Name, Symbol and the Maximum Units for Connection
OC
IC
Main Sub
(051)
M1 M2 S
TB5
NR
(001)
IC
M1 M2 S
TB5
(002)
TB6
(102)
M1 M2 SM1 M2 S
TB3 TB7
1
2
TB15
1
2
TB15
1
2
TB15
1
2
TB15
IC
M1 M2
SM1 M2
S
TB5
(001)
IC
TB5
(002)
NR
Main Sub Main Sub
TB6
(101)
NR
TB6
(151)
NR
TB6
(102)
NR
TB6
(104)
NR
TB6
(103)
M1 M2 SM1 M2 S
TB3 TB7
OC
(051)
12
TB15
12
TB15
IC
M1 M2 S1
2M1 M2
S
TB5
TB6
TB15
1
2
TB15
(001)
IC
TB5
(002)
M1 M2 SM1 M2 S
TB3 TB7
OC
(051)
MANR
(101)
Name
Outdoor unit
Indoor unit
Network remote
controller
Symbol
OC
IC
NR
VM
VM1/VM2
YM/YM1/YMA
VM
VM1/VM2
YM/YM1/YMA
Maximum units for connection
One OC unit can be connect to 2-5 units (Type 71:2-4units) One OC unit can be connect to 1-8 units (Type 71:1-4units) One OC unit can be connect to 1-8 units Maximum two units for one, Maximum 10 units for one OC (Type 71:8units) Maximum two units for one, Maximum 10 units for one OC (Type 71:8units) Maximum two units for one, Maximum 16 units for one OC
Permissible Lengths Prohibited items
Longest transmission cable length (1.25 mm L
1 + L2, L2 + L3, L3 + L1 [ 200m
2
)
Remote controller cable length
1. If 0.5 to 0.75 mm
2
R1, R2 [10m
2. If the length exceeds 10 meters, the exceeding section should be 1.25 mm
2
and that section should be a value within the total extension length of the transmission cable and maximum transmission cable
length. (L
3)
Same as above
• M-NET remote controller(NR) and MA remote controller(MA) cannot be used together.
• Do not connect anything with TB15 of indoor unit(IC).
• Use the indoor unit(IC) address plus 150 as the sub remote controller address. In this case, it should be 152.
• Three or more remote controller (NR) cannot be connected to one indoor unit.
Same as above
• The remote controller address is the indoor
unit main address plus
100. In this case, it should be 101.
47
B. Example of a group operation system with two or more outdoor units and a M-NET remote controller.
M1 M2 S
M1 M2 S
TB7
TB3
IC
(051)
M1 M2 S
TB512TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
NR
(001)
IC
M1 M2 S
TB5
(002)
IC
M1 M2 S
TB5
(004)
IC
M1 M2 S
TB5
(003)
IC
M1 M2 S
TB5
(005)
IC
M1 M2 S
TB5
(007)
IC
M1 M2 S
TB5
(006)
L1
L8
R1
R4
L9
L2 L3 L4
L5 L6 L7
TB6
(101)
NR
TB6
(105)
NR
TB6
(103)
NR
TB6
(155)
CN40
OC
Between terminal blocks
M1 M2 S
M1 M2 S
TB7
TB3
(052)
OC
R2
R3
Shielded wire
(Shielding wires and address settings are necessary.)
Examples of Transmission Cable WiringWiring Method Address Settings
Group 3
Group 5Group 1
Sub remote controller
( ) Address
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block
(TB3) of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block (TB6) on the remote controller (NR).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor
unit (OC).
e. Use the grounded wire to connect the S-terminal on the transmission terminal of the outdoor unit (OC) and the
grounded terminal for the electrical components box. f. On one outdoor unit only, change the jumper connector on the control panel from CN41 to CN40. g. Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which
the jumper connector was inserted into CN40 in Step above to the ground terminal ; in the electrical component
box. h. Set the address setting switch as follows.
Unit
IC (Main)
IC (Sub)
Outdoor Unit
Main Remote Controller
Sub Remote Controller
i. The group setting operations among the multiple indoor units is done by the remote controller (NR) after the electrical
power has been turned on.
001 to 050 001 to 050
051 to 100 101 to 150 151 to 200
Range
Use the most recent address within the same group of indoor units. Use an address, other than that of the IC (Main) from among the units within
the same group of indoor units. This must be in sequence with the IC (Main). Use the most recent address of all the indoor units plus 50.
Set at an IC (Main) address within the same group plus 100. Set at an IC (Main) address within the same group plus 150.
48
Setting Method
• Name, Symbol, and the Maximum Units for Connection
M1 M2 S
TB7
IC
(051)
M1 M2 S
TB512TB15
12
TB15
12
TB15
12
TB15
NR
Shielded wire
Remote controller
(001)
IC
M1 M2 S
TB5
(002)
IC
M1 M2 S
TB5
(004)
IC
M1 M2 S
TB5
(003)
IC
M1 M2 S
TB5
(005)
IC
M1 M2 S
TB5
(007)
IC
M1 M2 S
TB5
(006)
TB6
(101)
NR
TB6
(105)
NR
TB6
(103)
NR
TB6
(155)
CN40
OC
M1 M2 S
TB7
(052)
OC
M1 M2 S
TB3
M1 M2 S
TB3
12
TB15
12
TB15
12
TB15
• Max length via outdoor units : L1+L2+L3+L4+L5+L6+L7+L9 L1+L2+L3+L4+L5+L6+L8+L9 [ 500 meters (1.25mm2)
• Max transmission cable length : L
• Remote controller cable length : R
1+L2+L3+L4, L5+L6+L7, L5+L6+L8, L7+L8 [ 200 meters (1.25mm
1,R2, R3, R4 [ 10 meters (0.5 to 0.75mm
If the length exceeds 10 meters, use a 1.25 mm
tion (L
Permissible Length
8) should be included in the calculation of the maximum length and overall length.
2
)
2
)
2
shielded wire. The length of this sec-
Prohibited items
Group 3
Group 5Group 1
• The terminal S on the terminal block (TB7) for the central control panel should be connected to the ground terminal ;
of the electric components box for one outdoor unit only.
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to
different outdoor units (OC).
• Set all addresses to ensure that they are not overlapped.
• It cannot be connected M-NET remote controller and MA remote controller with indoor unit of the same group using
together.
49
C. Example of a MA remote controller system (address setting is not necessary.)
OC
IC
(000)
M1 M2
S 21 21
TB5 TB15 TB15
MA
(000)
IC
M1 M2
S
TB5
(000)
MA
M1 M2 SM1 M2 S
TB3 TB7
L2
L1
r1
r2
OC
(000)
IC
M1 M2 12 12S
TB5 TB15 TB15
(000)
IC
TB5
(000)
MA MA
M1 M2 S
M1 M2 SM1 M2 S
TB3 TB7
MA MA
r3
r5
r4
r6
r7
r7
OC
IC
(000)
M1 M2 S 1 2
TB5 TB15
12
TB15
MA
(000)
IC
M1 M2 S
TB5
(000)
M1 M2 SM1 M2 S
TB3 TB7
NOTE : In the case of same group operation, need to set the address that is only main indoor unit.
Example of wiring control cables Wiring Method and Address Setting
1. Standard operation
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit (OC) to terminals M1 and M2 on the transmission cable block (TB5) of each indoor unit (IC). Use non-polarized two wire.
b. Connect terminals 1 and 2 on transmission cable
terminal block (TB15) for each indoor unit with the terminal block for the MA remote controller (MA).
• One remote controller for each indoor unit.
• Inside ( ) Address: There is no need for setting the 100 position on the remote controller.
2. Operation using two remote controllers
• Using two remote controllers for each indoor unit.
3. Group operation
• Multiple indoor units operated together by one remote controller
Combinations of 1through 3 above are possible.
a. The same as above. b. The same as above. c. In the case of using tow remote controllers, connect
terminals 1 and 2 on transmission cable terminal block (TB15) for each indoor unit with the terminal block for tow remote controllers.
· Set the sub remote controller position for one of MA remote controller’s main switch.
Refer to the installation manual of MA remote
controller
a. The same as above. b. The same as above. c. Connect terminals 1 and 2 on transmission cable ter-
minal block (TB15) of each indoor unit, which is doing group operation with the terminal block the MA remote controller. Use non-polarized tow wire.
d. In the case of same group operation, need to set the
address that is only main indoor unit. Please set the address of the indoor unit with the most functions in the same group in the number that 01-50 is young.
50
Permissible Lengths Prohibited items
IC
M1 M2 S1
2M1 M2
S
TB5 TB15
1
2
TB15
(001)
IC
TB5
(002)
M1 M2 SM1 M2 S
TB3 TB7
OC
(051)
MAMA
IC
M1 M2 S1
2M1 M2
S
TB5 TB15
1
2
TB15
(000)
IC
TB5
(000)
M1 M2 SM1 M2 S
TB3 TB7
OC
(000)
MA MAMAMAMA
IC
M1 M2 S1
2M1 M2
S
TB5 TB15
1
2
TB15
(000)
IC
TB5
(000)
M1 M2 SM1 M2 S
TB3 TB7
OC
(000)
MAMANR
Longest transmission cable length L
1 + L2 [ 200m (1.25 mm
2
)
MA remote controller cable length
R
1, R2 [ 200m (0.3 ~ 1.25 mm
2
Longest transmission cable length The same as above. MA remote controller cable length
R
3 +R4, R5 +R6 [ 200m
(0.3 ~ 1.25 mm
2
)
The MA remote controller and the M-NET remote controller cannot be used together with the indoor unit
)
the of the same group.
Three MA remote controller or more cannot be connect with the indoor unit of the same group.
Longest transmission cable length The same as above. MA remote controller cable length
R
7 +R8 [ 200m (0.3 ~ 1.25 mm
The second MA remote control is connected with the terminal block(TB15) for the MA remote con-
2
)
trol of the same indoor unit(IC) as the first remote control.
51
D. Example of a group operation with two or more outdoor units and a MA remote controller.
M1 M2 S
M1 M2 S
TB7
TB3
IC
(051)
M1 M2 S 1 2
TB5 TB15
MA
(001)
IC
M1 M2 S
TB5
(002)
IC
M1 M2 S
TB5 TB15
(004)
IC
M1 M2 S
TB5
(003)
IC
M1 M2 S
TB5 TB15
(005)
IC
M1 M2 S
TB5 TB15TB15TB15
(007)
IC
M1 M2 S
TB5 TB15
(006)
L
1
L8
R1
R4
L9
L2 L3 L4
L5 L6 L7
MA
MA
MA
Sub remote
controller
CN40 CN41
CN41
OC
Between terminal blocks
M1 M2 S
M1 M2 S
TB7
TB3
(052)
OC
R2
R3
Shielded wire
12
12
12 12
12 12
(Shielding wires and address settings are necessary.)
Examples of Transmission Cable WiringWiring Method Address Settings
Group 3
Group 5Group 1
( ) Address
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1, M2 and S and the ground terminal on the transmission cable terminal block
(TB3) of each outdoor unit (OC) to terminals M1, M2 and S on the transmission cable block (TB15) of the indoor unit (IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
Unit
001 to 050 001 to 050
051 to 100
Range
Use the most recent address within the same group of indoor units. Use an address, other than that of the IC (Main) from among the units within
the same group of indoor units. This must be in sequence with the IC (Main). Use the most recent address of all the indoor units plus 50.
recent address within the same group to the terminal block on the remote controller (MA).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor
unit (OC).
e. Use the grounded wire to connect the S-terminal on the transmission terminal of the outdoor unit (OC) and the
grounded terminal for the electrical components box. f. On one outdoor unit only, change the jumper connector on the control panel from CN41 to CN40. g. Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which
the jumper connector was inserted into CN40 in Step above to the ground terminal ; in the electrical component box. h. Set the address setting switch as follows.
IC (Main)
IC (Sub)
Outdoor Unit
Setting Method
52
• Name, Symbol, and the Maximum Units for Connection
M1 M2 S
TB7
IC
(051)
M1 M2 S 1 2 1 2 1 2
TB5 TB15
12
TB15 TB15 TB15
MA
Shielded wire
(001)
IC
M1 M2 S
TB5
(002)
IC
M1 M2 S
TB5
(004)
IC
M1 M2 S
TB5
(003)
IC
M1 M2 S
TB5
(005)
IC
M1 M2 S
TB5
(007)
IC
Group 1 Group 3 Group 5
M1 M2 S
TB5
(006)
MA
MA
MA
CN40
OC
M1 M2 S
TB7
(052)
OC
M1 M2 S
TB3
M1 M2 S
TB3
1212
TB15 TB15
12
TB15
• Max length via outdoor units : L1+L2+L3+L4+L5+L6+L7+L9 L1+L2+L3+L4+L5+L6+L8+L9 [ 500 meters (1.25mm2)
• Max transmission cable length : L
• Remote controller cable length : R
1+L2+L3+L4, L5+L6+L7, L5+L6+L8, L7+L8 [ 200 meters (1.25mm
1,R2, R3, R4 [ 10 meters (0.5 to 0.75mm
If the length exceeds 10 meters, use a 1.25 mm
tion (L
Permissible Length
8) should be included in the calculation of the maximum length and overall length.
2
)
2
)
2
shielded wire. The length of this sec-
Prohibited items
• The terminal S on the terminal block (TB7) for the central control panel should be connected to the ground terminal ;
of the electric components box for one outdoor unit only.
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to
different outdoor units (OC).
• M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wring
together
53
8 TROUBLESHOOTING
PAR-20MAA
ON/OFF
TEST RUN
˚C
1Hr.
FILTER
CHECK TEST
TEMP.
TIMER SET
Check code indicator (see NOTE 1) Test run remaining time indicator (see NOTE 3)
Display panel
On/Off button 9
On/Off LED (Lights up in operation)
Wind adiust button 6
Test run button 2
Air speed adjust button 5
Test run indicator
Indoor unit liquid pipe temperature indicator
(see NOTE 4)
Cooling/Heating select button 3,4
Control panel
8-1. CHECK POINTS FOR TEST RUN
8-1-1. Procedures for test run
(1) Check after connection is completed: Check whether the installation, piping installation, electrical wiring is completed before test run.
• Installation: Check that the decorative panel of inset series is installed.
The wires on the decorative panel cannot be operation if connection is not completed.
• Piping : Check that the refrigerant and the drain pipe are qualified for leakage test. Also, warm protection measures should be adopted for connection parts.
Check that additional charge for refrigerant is completed and to make sure that the liquid side and the gas side of the valve
is completely open.
• Electrical wiring: Check that the grounded wire, transmission wire, the remote controller wire and power supply cord are connected.
Please check that the switch for the specific address setting, and the setting for optional specifications.
(2) Safety check: The resistance between the 500V Mega Ohm measurement table for power supply terminal block (twice for switch) and the
grounded wiring (the metal parts for refrigerant wiring and the electrical components box for machines) should be 1.0 Mor more.
Do not contact the transmission wire and the remote controller wire, etc. with the 500V Mega Ohm table.Check all the wiring for outdoor/indoor unit and other linked installation.Do not continue any operation before confirming the insulated resistance (1.0 Mor more).
(3) Preparation for operation: Set the main switch of the remote controller circuit to the “ON” position.
1 Entries for the control system should be made on the remote controller. Refer to 2. Guide to special function operation and settings for entries of the control system (P.55). 2 Set the main switch of the outdoor unit to the “ON” position after entries are made. Do not operate the operate/stop switch on the remote controller.
Set the main switch of the outdoor switch to the “ON” position for 12 hours or above before operation starts.
The reason for setting the main switch to the “ON” position is to supply power to protect the compressor.
(4) Test run: Test run can be now started. Set all the main switch to the “ON” position.
• Fill in the test run performance report.
• Follow the instructions below for test run.
(5) Operating instructions: Hand in the operation manual and the report for test run performance to the client with a clear explanation for
proper use.
If abnormalities are occurred during the test run, please refer to corrective measures for problems occurring during the test run
(Page 57).
Refer to the internal switch function table (Page 80) for the outdoor internal switch function.
Operation procedure
1 Turn on universal power supply at least 12 hours before getting started displaying “HO” on display panel for about three minutes. 2 Press TEST RUN button twice displaying “TEST RUN” on display panel. 3 Press a select button check whether air is blowing out. 4 Press a select button to change from cooling to heating operation, and make sure that warm or cold air is blowing out. 5 Press l adjust button Check whether air speed is changed. 6 Press or k button to change wind Check whether horizontal or downward blow is adjustable. 7 Check whether outdoor unit fans operate normally. 8 Check whether interlocking devices such as ventilator operate normally if any. 9 Press ON/OFF button to cancel test run Stop operation.
NOTE 1: If check code is displayed on remote controller or remote controller does not operate normally, see page 57. NOTE 2: Test run automatically stops operating after two hours by activation of timer set to two hours. NOTE 3: During the test run, the test run remaining time is displayed on time display section. NOTE 4: During the test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temp,display section. NOTE 5: When pressing adjust button, depending on the model, “This function is not available” may be displayed on remote
controller. However, it is not a malfunction.
54
8-1-2. Special Function Operation and Settings (for M-NET Remote Controller)
The addresses of indoor unit and linked units are displayed simultaneously.
(altenating display)
These alternating IC or LC displays will appear when entry is completed normally.
A flashing “88” will appear if there is a problem with the entry (indicating that the unit does not exist).
• It is necessary to perform “group settings” and “paired settings” when making group settings of different refrigerant systems (multiple outdoor unit). (A) Group settings: Enter the indoor unit controlled by the remote controller, check the content of entries, and clear
entries, etc.
(B) Paired settings: Used to set the linked operation of a Lossnay unit.
(1) Entering address: Follow the steps below to enter the addresses of the indoor unit using the remote controller.
Group settings
• Turning off the remote controller: Press the ON/OFF button to stop operation (the indicator light will go off).
• Changing to indoor unit address display mode: If the FILTER and k buttons on the remote controller are pressed simultaneously and held for two seconds, the display shown in Figure 1 will appear.
• Changing address: Press the temperature adjustment buttons to change the displayed address to the address to be entered.
• Entering the displayed address: Press the TEST RUN button to enter the indoor unit with the displayed address. The type of the unit will be displayed as shown in Figure 2 if entry is completed normally. If a selected indoor unit does not exist, an error signal will be displayed as shown in Figure 3. When this happens, check whether the indoor unit actually exists and perform entry again.
• Returning to the normal mode after completing entry: Press the FILTER and k buttons simultaneously and hold for two seconds to return to the normal mode.
Figure 1 (A) Group setting display
Paired Settings
• Turn off the remote controller: Press the remote controller’s ON/OFF button to turn it off (the indicator light will go off).
• Put in indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for two seconds.
The above steps are the same as when making group settings (A).
• Changing to the linked operation unit address display state: The display shown in Figure 4 will appear when the button on the remote control is pressed.
• Displaying the address of the Lossnay unit and linked indoor unit: In this situation, the indoor unit number will be the lowest address of the group. The Lossnay unit will not operate if this setting is
incorrect.
If the temperature adjustment buttons are pressed, the address may be changed to the indoor unit that are
to be linked.
If the time setting buttons are pressed, the address of the linked units may be changed to the address where
it is desired to enter the Lossnay .
• Linking the Lossnay and the indoor unit: The display shown in Figure 5 will appear when the TEST RUN button is pressed. The indoor unit whose address is displayed and the Lossnay unit with a linked address will operate in a linked manner.
If it is desired to display the address of the Lossnay in the indoor unit address, display the indoor
unit address in the linked unit address, and the above content will also be recorded.
Apart from the indoor unit with the lowest address in the group, display and enter the addresses of the other indoor unit
that are to be linked with the Lossnay unit.
• Returning to the normal mode after completing entry: Press the FILTER and k buttons on the remote controller simultaneously and hold for two seconds to return to the normal mode.
Figure 2 Normal completion of entry
Figure 3 Entry error signal
Flashing “88” indicates entry errorType of unit is displayed
a
Figure 4 (B) Making paired settings
Figure 5 Completing normal entry
55
(2) Address check: Refer to section (1) concerning address entry.
"88" will appear in the room temperature display location.
"--" will appear in the room temperature display location.
When making group settings:
• Turn off the remote controller: Press the remote controller's ON/OFF button to stop operation (the indicator light will go off).
• Locate the indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for two seconds.
• Display indoor unit address: The entered indoor units address and type will be displayed each time the button is pressed.
When one entry is made, only one address will be displayed no matter how many times the w button is pressed.
• Returning to the normal mode after completing check: Simultaneously press the FILTER and k buttons on the remote controller and hold for two seconds to return to the normal mode.
When making paired settings:
• Turn off the remote controller: Press the remote controller's ON/OFF button to stop operation (the indicator light will go off).
• Put in indoor unit address display mode: Press the FILTER and k buttons on the remote controller simultaneously and hold for two seconds.
• Changing to the linked operation unit address display state: Press the a button on the remote control.
• Displaying the address of the indoor unit to be checked: Change the address to that of the indoor unit to be checked by pressing the tempera­ture adjustment buttons .
• Displaying the address of the linked Lossnay unit: Press the w button to display the addresses of the linked Lossnay and indoor unit in alternation.
• Displaying the addresses of other entered units: The addresses of the other entered units will be displayed in alternating fashion after resting the w button again.
• Returning to the normal mode after completing the check: Simultaneously press the FILTER and k buttons on the remote controller and hold for two seconds to return to the normal mode.
(3) Clearing an address: Refer to section (1) regarding the address entry and section (2) regarding checking addresses.
When making group settings:
• Turn off the remote controller: The procedure is the same as in the group settings part of section (1) on checking the address.
• Put in the indoor unit address display mode: The procedure is the same as in the group settings part of section (2) on checking the
address.
• Displaying the indoor unit address to be cleared: The procedure is the same as in the group settings part of section (2) on checking the
address.
• Clearing indoor unit address:.......Pressing the q button on the remote controller twice will clear the address entry of the
displayed indoor unit, resulting in the display shown in Figure 6. The display shown in Figure 7 will appear if an abnormality occurs and the entry is not cleared. Please repeat the clearing procedure.
• Returning to the normal mode after clearing an address: The procedure is the same as in the group settings part of section (2) on checking the address.
Figure 6 Display after address has been
cleared normally
Figure 7 Display when an abnormality
has occurred during clearing
When making paired settings:
• Turn off the remote controller: The procedure is the same as in the group settings part of section (2) on checking the address.
• Put into the indoor unit address display mode: The procedure is the same as in the group settings part of section (2) on checking the
address.
• Put into the linked unit address display mode: The procedure is the same as in the group settings part of section (2) on checking the address.
• Display the address of the Lossnay unit or the indoor unit to be cleared.
• Deleting the address of a linked indoor unit: Pressing the q button on the remote controller twice will clear the address entry of the dis-
played indoor unit, resulting in the display shown in Figure 8.
• Returning to the normal mode after clearing an address: The procedure is the same as in the group settings part of section (2) on check­ing the address.
Figure 8 Display after address has been cleared normally
"--" will appear in the unit type display location when an address has
(altenating display)
been cleared normally. "88" will appear in the unit type display location when an abnormality
has occurred during clearing.
56
8-1-3. Corrective Measures for Symptom Occurring During Test Run
12 34 56 78 LD1
Check code Check codeTrouble Trouble
1102 1108 1302 1500 1501 1505 2502 2503 4115 4116 4220 4230 4250
5101
5102 5103
5105 5106 5110
Discharge temperature trouble Compressor's inner thermal sensor trouble High pressure trouble Excessive refrigerant replenishment Insufficient refrigerant Vacuum operation protection Drain pump trouble Drain sensor trouble (THd) Power synchronization signal trouble Indoor unit fan rotation trouble Inverter main voltage drop Overheat protection of radiator panel Multiple IPM errors
Intake thermistor trouble (TH21) or discharge thermistor trouble (TH1)
Liquid pipe thermistor trouble (TH22) or intake pressure saturation pressure thermistor trouble (TH2)
Gas pipe temperature sensor trouble (TH23) Piping temperature sensor trouble (TH5) Outdoor temperature sensor trouble (TH6) IPM heat sink thermistor trouble (THHS)
Pressure sensor trouble (63HS) Duplicated unit address setting
Transmission error (Transmission processor hardware error)
Transmission error (Transmission route BUSY) Transmission and reception error
(Communication trouble with transmission processor) Transmission and reception error (No ACK error)
No response MA communication receive signal error
(no receive signal) MA communication send signal error
(starting bit detection error) MA communication send error (H/W error) MA communication receive error
(Synchronous recovery error) total capacity error
Capacity code error Connecting unit number error Address set error Remote controller sensor trouble
5201 6600
6602 6603
6606 6607
6608 6831
6832 6833
6834 7100
7101 7102 7105
7111
• If a problem occurs during test run, a code number will appear in the temperature display area on the remote controller (or LD1 on the outdoor unit), and the air conditioning system will automatically cease operating.
Determine the nature of the abnormality and apply corrective measures.
The operational status of the outdoor unit controller is displayed on the LD1 of the outdoor unit under normal conditions (when all SW1’s are OFF)
Field
Display item
Example: When the air conditioner is in the heating mode and the SV1 and compressor turned on.
1
Compressor
is operating
2
52C
3
21S4
4
SV1
52C : Compressor Contactor 21S4 : Four-way valve SV1 : Bypass valve
57
5
6
7
8
Lit steadily
Display
1102
Meaning and detecting method
Discharge temperature abnormality
When the discharge temperature thermistor
1
(TH1) detects 125 the compressor stops and restarts operation in 3 minutes.
2
When the thermistor detects 125 again (2nd detection) within 30 minutes since the compressor has stopped, the compressor stops and restarts operation in 3 minutes.
3
When the thermistor detects 125 again (3rd detection) within 30 minutes since the compressor has stopped 2 times, the compressor stops abnormally. <1102> is displayed.
4
When the thermistor detects 125; or more after 30 minutes since the compressor has stopped (1st or 2nd time), it becomes the 1st detection or the same
performance as above-mentioned 1.
5
It is being delay for abnormal stop during 30 minutes since the compressor has stopped. In this time, check delay code <1202> will be displayed.
;or more (1st detection),
;or more
;or more
Causes
1) Gas leakage, Gas shortage
2) Overloaded operation
3) Indoor linear expansion valve operation defective
4) Ball valve operation defective
5) Outdoor fan block and defective of fan motor (heating mode)
6) Gas leakage between high and low pressure (Defective of 4-way valve or compressor)
7) Solenoid valve (SV1) performance defective (control failure to prevent the discharge temp. from rising by SV1)
8) Thermistor defective
9) Input circuit defective of multi controller board
Check points
Check the refrigerant amount. Check the indoor/outdoor unit operating
condition and status.
Perform cool or heat operation to check the condition.
Check ball valve is fully opened. Check the outdoor fan motor.
Check the operating condition.
Check the solenoid valve performance.
Check the thermistor resistance.
Check the intake temperature in discharge temperature thermistor (TH1) by LD1. (See 5101 Discharge temperature thermistor error)
1108
1302
Compressor inner thermo abnormality When the inner thermo performs (1st
1
detection) during the compressor operation, the compressor stops and restarts operation in 3 minutes.
When the inner thermo performs again (2nd
2
detection) within 30 minutes since the compressor has stopped, or does not recover within 30 minutes, it stops abnormally. In this time <1108> is displayed.
When the inner thermo performs after 30
3
minutes since the compressor has stopped (1st stop), it is the 1st detection and becomes the same performance as above-
mentioned It is being delay for abnormal stop during
4
30 minutes since the compressor has stopped. In this time, check delay code <1208> will be displayed.
High-pressure pressure abnormality When high-pressure pressure sensor
1
detects 2.94MPa or more (1st detection) during the compressor operation, the compressor stops and restarts operation in 3 minutes
1.
1) Low voltage supplied to power supply terminal block
2) Power supply L2 or L3 phase is opened. (When L1 phase is opened, power supply of the micro computer is not supplied.)
3) Compressor failure(Over current by motor rare short, etc.)
4) Overloaded operation
5) Gas leakage, Gas shortage
6) Inner thermo defective
7) Input circuit defective of multi controller board or power supply board
1) Indoor unit short cycle
2) Indoor unit filter clogging
3) Air flow capacity decrease due to indoor fan dirt
4) Indoor heat exchanger dirt
Measure the terminal voltage. Check the voltage reduction.
Check the open phase.
Check the coil resistance.
Check the indoor/outdoor unit operating condition and status.
Check the refrigerant amount.
Check the current flows in inner thermo.
When the inner thermo is normal and input circuit is defective, even if the inner thermo performs, the compressor does not operate and becomes error in 30 minutes.
Check the indoor unit. Check the indoor unit filter.
Check the indoor fan.
Check the indoor unit heat exchanger.
58
Display
1302
Meaning and detecting method
2
When the sensor detects 2.94MPa or more again (2nd detection) within 30 minutes since the compressor has stopped, the compressor stops again and restarts operation in 3 minutes.
Causes
5) Indoor fan motor lock Check the indoor fan motor.
6) Indoor fan motor failure Check the indoor fan motor.
7) 4-way valve performance failure (Stop in the middle of performance)
Change COOL/HEAT operation mode to perform the 4-way valve. If any defective, replace the 4-way valve.
Check points
When the sensor detects 2.94MPa or more
3
again (3rd detection) within 30 minutes after second compressor stop, it stops abnormally. In this time <1302> is displayed.
When the sensor detects 2.94MPa or more
4
after 30 minutes since the compressor has stopped (1st or 2nd time), it becomes the 1st detection or the same performance as
above-mentioned 1.
5
It is being delay for abnormal stop during 30 minutes since the compressor has stopped. In this time, check delay code <1402> will be displayed.
Note) For first 3 minutes in HEAT starting, error detected pressure of high-pressure pressure sensor is 3.14MPa.
8) Ball valve performance failure (not full-opened)
9) Pipe clogged or broken
10) Indoor linear expansion valve performance failure
11) Outdoor fan motor lock
12) Outdoor fan motor failure
13) Outdoor unit short cycle
14) Outdoor heat exchanger dirt
15) Decrease in airflow capacity which the outdoor unit intakes because of intake defective of outer temperature thermistor. (Intake less than the actual outer air)
16) Indoor unit capacity codes miss setting (If the capacity code is set greatly, initial frequency rises and high­pressure is easy to rise.)
17) Solenoid valve (SV1) performance failure (High-pressure pressure cannot be controlled by SV1)
18) Indoor thermistor (liquid pipe temperature detection) detecting failure (thermistor removed) (Hot adjust time becomes long.)
19) High-pressure pressure sensor defective
Check the ball valve full-opened.
Repair the defective points. Operate COOL or HEAT operation,
and check the operation condition.
Check the outdoor unit fan motor. Check the outdoor unit fan motor.
Check the outdoor unit. Check the outdoor unit heat
exchanger. Check intake temperature of the outer
temperature thermistor by LD1. (See 5106 Outer temperature thermistor error)
Check the capacity set switch in the indoor controller board. If it is wrong setting reset it. Check is available for the outdoor unit. (See 7101 Capacity code error)
Check the solenoid valve performance.
Check the thermistor installed condition. Operate in trial mode and check the pipe temperature change by the remote controller.
Check the high-pressure pressure sensor.
20) High-pressure pressure sensor input circuit defective in multi controller board.
1500 Refrigerant over charged abnormality 1) Refrigerant over charged Check the refrigerant amount.
When below 5 conditions are satisfied
1
during the compressor operation (1st detection), the compressor stops and restarts operation in 3 minutes.
1. Cool mode, outer temp. is 20 Heat mode, outer temp. is 15
; or more
; or less
2) Light-loaded operation (Wrong determination)
3) Performance defective of the indoors linear expansion valve and outdoors electronic expansion valve.
Check the high-pressure pressure sensor.
Check the indoor/outdoor unit operating condition and status.
Perform cool or heat operation to check the condition.
59
Display
1500 2. The compressor has operated
1501
Meaning and detecting method
consecutively 20 minutes or more, since the indoor unit operation capacity had changed (including the compressor operation start).
3. Operation frequency is 80Hz or more.
4. Discharge super heat is below 10
5. Sub cool step continues for 5 minutes or more by SN=4.
2
Same condition as 1 is satisfied again within 60 minutes since the compressor has stopped, it stops abnormally. In this time, <1500> is displayed.
3
Same condition as 1 is satisfied again after 60 minutes since the compressor has stopped (1st time), it becomes the first
detection and same performance as 1.
It is being delay for abnormal stop during
4
60 minutes since the compressor has stopped. In this time, check delay code <1600> will be displayed.
Refrigerant shortage abnormality When the conditions of below detecting
1
mode 1 or 2 are satisfied (1st detection) during the compressor operation, the compressor stops and restarts operation in 3 minutes.
<Detecting mode 1> When the below conditions are satisfied
completely.
1. SW5-5 is OFF.
2. Compressor is operating in HEAT mode. 4) Error detection of discharge super
3. Discharge super heat is 70; or more.
4. Difference of outer temperature thermistor (TH6) and outdoor piping temp. thermistor(TH5) applies to the formula of
(TH6-TH5)<5
5. High-pressure pressure sensor is below
1.18MPa. <Detecting mode 2> When the below conditions are satisfied
completely.
1. Compressor is operating.
2. When cooling, discharge super heat is
; or more.
80 When heating, discharge super heat is 90;
or more. When the conditions of detecting mode
2
1and 2are satisfied again (2nd detection) within 30 minutes since the compressor has stopped, it stops abnormally. In this time, <1501> is displayed.
When the conditions of detecting mode
3
1and 2are satisfied again after 30 minutes since the compressor has stopped (1st time), it becomes the 1st detection and
same performance as above It is being delay for abnormal stop during 30
4
minutes since the compressor has stopped. In this time, check delay code <1600> will be displayed.
;.
1.
;.
Causes
4) Discharge super heat detection error
1 High-pressure pressure sensor
failure
2 Discharge temperature thermistor
failure
3 Thermistor input circuit defective in
the multi controller board., and high­pressure pressure sensor input circuit failure
1) Gas leakage, Gas shortage Check the refrigerant amount.
2) When heating operation, refrigerant shortage feeling operation
(When heating, air flow or thermo OFF are mixed-operation, it cause a refrigerant shortage operation.)
3) Ball valve performance failure (not full opened.)
heat
1 High-pressure pressure sensor
defective
2 Discharge temperature thermistor
defective
3 Thermistor input circuit defective and
high-pressure pressure sensor defective in multi controller board
5) Error detection of TH5/TH6
1
Check the high-pressure pressure sensor.
Check the resistance of discharge
2
temp. thermistor. Set the SW1 to and
3
check the high-pressure pressure sensor level.
Set the SW1 to and check the discharge temp. thermistor level.
When the high-pressure pressure sensor and discharge temp. thermistor are normal, if the above mentioned detecting pressure level and temp. are big different from the actual pressure and temp., replace the multi controller board.
Check the operation condition and refrigerant amount.
Check the ball valve is full opened.
Check the high-pressure pressure
1
sensor. Check the resistance of discharge
2
temperature thermistor. Set the SW1 to and
3
check the high-pressure pressure sensor level.
Set the SW1 to and check the discharge temp. thermistor level.
When the high-pressure pressure sensor and discharge temp. thermistor are normal, if the above mentioned detecting pressure level and temp. are big different from the actual pressure and temp. replace the multi controller board.
Check the resistance of thermister.
1
Check points
21345678
on
21345678
on
21345678
on
21345678
on
1 Thermistor defective
21345678
2 Thermistor input circuit defective in
multi controller board
Set the SW1 to and
2
check the outdoor pipe temp. thermistor level.
3
Set the SW1 to and check the outer temp. thermistor level.
on
21345678
on
60
Display
1505
Meaning and detecting method
Vacuum operation protection
When the suction pressure saturation temperature thermistor(TH2) detects -20; or less for 4 consecutive minutes or more during the 1st COOL operation (compressor operation) after power supply on, it stops abnormally. In this time, <1505> is displayed
Causes
1) Ball valve performance failure (not full opened.)
2) Light-loaded operation (When outer temperature is low, the operation is liable to change to this mode.)
3) Low-pressure over suction by refrigerant shortage
Check points
Check the ball valve is full opened.
Check the indoor/outdoor unit operating condition and status.
Check the refrigerant amount.
2502 Drain pump abnormality
When either of the undermentioned
1
condition is satisfied (when determined drain sensor goes under water) while the indoor unit operation (excluding the case of abnormal stop) and after 3minutes since the drain pump has operated, the indoor unit stops abnormally (however fan continues the normal control). In this time, <2502> is displayed.
· Turn on the side heater of drain sensor, then when temperature up from the detected temperature before turning on is below 20; during 40 seconds.
· The detected temperature is below 63; after 40seconds since the side heater of drain sensor has turned on.
4) Pipe clogging and broken
5) Indoor linear expansion valve performance defective
1) Drain pump trouble
2) Drain defective
· Drain pump clogging
· Drain pipe clogging
3) Open circuit of drain sensor side heater
4) Contact failure of drain sensor connector
5) Dew condensation on drain sensor
· Drain water descends along lead wire.
· Drain water waving due to filter clogging.
Repair the defective points. Perform cool or heat operation to
check the condition.
Check the drain pump. Performance
Please confirm whether water can be drained.
Confirm the resistance of the drain sensor side heater. (approx. 82at normal between connector CN50 1 and 3 in the indoor controller board)
Check the connector contact failure.
1
Check the drain sensor lead- wire mounted.
Check the filter clogging
2
When condition which the outdoor unit is
2
stopped forcibly consists, or the drain sensor detects continuously to go under water 5 times, and also detects ''[liquid pipe temperature-suction temperature][ -10deg'' for 30minutes continuously, the indoor unit stops abnormally (however, fan operates by normal control) that indoor unit and excluding [Fan mode or OFF] in same refrigerant system. Also, the outdoor unit which is connected to that indoor unit with refrigerant system stops abnormality (compressor is inhibited to operation). In this time, <2502> is displayed.
6) Indoor controller board defective
· Drain pump drive circuit failure
· Drain heater output circuit failure
7) Both of above mentioned 1)~6) and the indoor linear expansion valve full­closed failure (leakage) happens synchronismtically.
If the above mentioned checkpoints has any problem, replace the indoor controller board.
Check whether the indoor linear expansion valve leaks or not.
61
Display
2502 Drain pump abnormality
2503 Drain sensor (THd, DS) abnormality
Meaning and detecting method
(Note) Address/Attribute displayed on the remote controller shows the indoor unit which is cause of trouble.
<Detected timing>
Always detecting regardless of the indoor unit status.
<Abnormality clear>
Abnormality is cleared by either of two of the following;
· Reset power supply of the indoor unit and outdoor unit in same refrigerant system, which is the cause of trouble in the refrigerant system.
· Reset power supply of the indoor unit, which is the cause of trouble. (However, power supply interception of 10 minutes or more is necessary.)
(Note) Above 1 and 2 detects independently.
When the drain sensor detects short/open while the operation.
Short: detection of 90; or more
Open: detection of -40; or less
Causes
1) Connector(CN50) contact failure (insertion failure)
2) Thermistor wiring disconnection or half disconnection
Check points
Check whether the indoor controller
1
board connector (CN50) is disconnected or not.
2
Check whether the thermistor wiring is disconnected or not.
4115
Power supply synchronous signal abnormality
When power supply synchronous signal
1
(once a second) is not read, stop the compressor and restarts operation in 3 minutes. (When the synchronous signal is not read at just before of compressor start, the compressor does not start and stops operation 3 minutes.)
2
For 30minutes after the compressor stop, it is being to delay abnormal stop. Then, when SW1 is set, the outdoor units address No. and check code <4165> blinks on the 4 digit digital display alternately. SW1 setting
When power supply synchronous signal
3
(once a second) is not read again during abnormal delay, the compressor stops abnormally. Then, the outdoor units address No. and check code <4115> blinks on the 4 digit digital display alternately.
21345678
on
3) Thermistor defective
4) Indoor controller board (detecting circuit) failure
1) Disconnection or contact failure by loose of connector (CNA) is connected to power supply board. (for VM type)
2) Disconnection or contact failure by loose of connector (CN2) is connected to power supply board.
3) Power supply synchronous detected circuit failures in the power supply board.
4) Power supply synchronous detected circuit failure in the multi controller board.
Check the resistance of thermistor.
3
0;···15k’ 10;···9.6 k’
20;···6.3 k’ 30;···4.3 k’
40;···3.0 k If abnormality is not found in the
4
method of the above-mentioned from 1 to 3, it is defective of the indoor controller board.
Check the connector insertion.
Check the connector insertion.
Replace the power supply board.
Replace the multi controller board.
62
Display
4116 Fan rotational frequency abnormality
4220
Meaning and detecting method
(Detected only PKFY-P·VAM) When rotational frequency of the fan is
1
detected 180rpm or less, or 2000rpm or more (1st detection) while the indoor unit fan operation, the fan stops for 30seconds.
When the rotational frequency of the fan is
2
detected 180rpm or less, or 2000rpm or more again after the fan restarts, the indoor unit stop abnormally (fan stops). In this time, <4116> is displayed.
Shortage abnormality of inverter bus-bar voltage
When direct current bus-bar voltage
1
reduces extremely during the compressor operation, the compressor stops and restarts operation in 3minutes.
Causes
1) Fan rotational frequency detecting connector (CN33) disconnection in the indoor controller board.
2) Fan output connector (FAN1) disconnection in the indoor power board.
3) Fan rotational frequency detecting connector (CN33) wiring breakage in the controller board or fan output connector (FAN1) breakage in the indoor power board
4) Filter clogging Check the filter.
5) Indoor fan motor trouble Check the indoor fan motor.
6) Fan rotational frequency detecting circuit failure in the indoor controller board or fan output circuit failure in the indoor power board.
1) Power supply terminal voltage is low.
2) Power supply L2,L3-phase is opened. [for YM type]
1
Check whether the connector (CN33) in the indoor controller board is disconnected or not.
Check whether the connector (FAN1)
2
in the indoor power board is disconnected or not.
Check whether the wiring is
3
disconnected or not.
4
5
When there is no problem in the
6
above-mentioned from 1 to 5; (1) In the case of abnormality after the
fan operation; Replace the indoor controller board.
When the fan does not recover even if the indoor controller board is replaced, replace the indoor power board.
(2) In the case of abnormality without fan operation, replace the indoor power board.
Measure the terminal voltage, and check whether the voltage decreases or not.
Check the power supply is opened.
Check points
It is being delay to stop abnormally for 30
2
minutes after the compressor stop. Then, when SW1 is set, the outdoor unit address No. and check code <4320> blinks alternately on the 4 digit digital display.
SW1 setting
When detecting abnormality of direct bus-
3
bar voltage decrease again during being delay abnormality, it performs the same action as 1. Also, when the abnormality is not detected, it operates normally. Hereafter, action 1 is repeated until 5th abnormal detection.
4
When the 6th voltage decrease of direct bus bar is detected during being delay abnormality, it stops abnormally. In this time, the outdoor unit address No. and check code <4220> blinks alternately on the 4 digit digital display.
21345678
on
3) Diode stack (Diode module) defective.
4) Connector lead wire disconnection, contact failure.
Power supply board connecting connector (CND)-Between smoothing capacitor (C3). (for 71VM type) for 125VM : CND-CB 125YM : CND-CB1 and CB2
Power supply board connecting connector (52C)-Between electro magnetic contactor (52C)
5) Connector (CN2) disconnection, contact failure.
Check the resistance of diode stack.
Check the defective points.
Check the connector insertion.
63
Display
Meaning and detecting method
Causes
Check points
4220 6) Instant power failure It happens by accident, and does not
have the possibility to happen again.
4230 Radiator panel shield temperature
1
When the radiator panel temperature thermistor (THHS) detects abnormality (1st detection) stops the outdoor unit once and restarts operation in 3minutes.
2
It is being delay to stop abnormally for 30minutes after the compressor stop. Then, when SW1 is set, outdoor unit address No. and check delay code <4330> blinks alternately on the 4 digit digital display.
SW1 setting When the radiation shield temperature
3
21345678
on
thermistor (THHS) detects abnormality again (2nd detection) during delay abnormality, perform the same action as
1. When the radiation shield temperature
4
thermistor (THHS) detects abnormality on 3rd time during delay abnormality, it stops abnormally. Then, the outdoor unit address No. check code <4230> blinks alternately on the 4 digit digital display.
Abnormality detecting temperature in radiation shield temperature thermistor
Type
125
Abnormal temp.( )
71
73 84
7) Lightening serge, single interruption by external noise.
8) Direct bus-bar voltage shortage
It happens by accident, and does not have the possibility to happen again.
Replace the power supply board. detecting circuit failure in power supply board
1) Outdoor fan motor lock Check the outdoor fan motor.
2) Outdoor fan motor trouble Check the outdoor fan motor.
3) Block of duct which cooled air passes
Check whether the air duct for cooling is opened.
4) Surrounding temperature-rise Check whether there is a heat source in surroundings of the outdoor unit. (Surroundings temperature upper limit is 46;)
5) Thermistor failure Check the resistance of thermistor.
1
(Use tester)
21345678
6) Thermistor input circuit failure in the
multi controller board
2
Change the SW1 to and check the temperature in radiation
on
shield temperature thermistor. When there is a big difference between the detected temp. and thermistor temp. replace the multi controller board.
;
4250
IPM abnormality Over current limited
(When the compressor is interrupted by over current at its start-up.)
1
When over current limit is detected within 30seconds from start-up, the compressor stops and restarts in 3minutes.
While the compressor stops for 3minutes,
2
confine the current-carry.
When SW1 setting during delay of
3
interruption abnormality stop, the outdoor unit address No. and check delay code <4350> blinks alternately on the 4 digit digital display.
SW1 setting
21345678
on
1) Single interruption by external noise.
2) Single interruption by lightening serge
3) Power supply abnormality (a) Voltage decrease to 180V or less
for VM type. Voltage decrease to 340V or less for YM type. (b) Power supply open-phase
(Current increase in the compressor by the voltage decrease)
4) Diode stack defective When it is opened-phase, same phenomenon occurs as power supply open-phase.
64
The interruption happens by accident. Since the interception only once returns automatically after restarting in 3minutes, the possibility to stop abnormally is very few.
1
Measure a receiving voltage and check the power supply capacity
Check whether the phase is opened
2
or not.
Check from 4) to 13) by following procedure;
4250
When the compressor is interrupted again by over current after restarting in 3minutes, it stops and restarts in 3minutes. Perform the same action as 2 and 3.
5) Disconnection of connector and lead wire, and miss-wiring For VM type
Start-up the compressor and check the status of interrupting.
When the compressor is not interrupted within 30seconds after restarting in 3minutes, clear the delay of limited abnormal stop and back to normal.
(a) Between power supply board (CN5) and gate amplifier board (CN5)
(1) When the compressor stops (output signal stop) after immediately after output signal comes out and is interrupted abnormally.
When the above action 4 is repeated and the compressor is interrupted within 30seconds after 7th start-up, or the compressor is interrupted during confined the current-carry, it stops abnormally. Then, the outdoor unit address No. and check delay code <4250> blinks alternately on the 4 digit digital display.
(b) Between power supply board (CN6) and gate amplifier board (CN6)
Generation of short-circuit current is assumed. (5),6),7),12),13))
(c) Between multi controller board (CN4) and gate amplifier board (CN4)
(2) After 5seconds of start-up, when the compressor stops by interruption, being delay and repeats to confine current-carry for 3minutes restart­up interruption to confine current-carry restart-up and becomes interruption-abnormality after approx. 18minutes from start-up.
(When the compressor is interrupted by over current during the operation)
(d) Disconnection of connector and lead wire in the multi controller board (AC.CT) For YM type (e) Between multi controller board (CN4) and power supply board (CN4)
The compressor is assumed not to start-up by torque shortage or lock. (5), 6), 7), 9), 10), 11), 12))
When over current limit is detected after 30seconds from start-up, the compressor stops and restarts in 3minutes.
(3) When the compressor stops after a while by the interception though the compressor starts once, and restarts in 3minutes.
The compressor is being delay to stop abnormally for 8minutes after the compressor stop. Then, the outdoor unit address No. and check delay code <4350> blinks alternately on the 4 digit digital display.
It is presumed to stop since the frequency goes up and the load grows though the compressor starts. (4), 5),
6), 7), 8))
SW1 setting
Check the miss-wiring, terminal loosing and disconnection of connector and lead wire.
When the compressor is interrupted again within 5minutes after restarting in 3minutes, it stops abnormally. Then, the outdoor unit address No. and check delay code <4250> blinks alternately on the 4 digit digital display.
Repair of defective points. (5), 11))
When the compressor is not interrupted within 5minutes after restarting in 3minutes, it becomes the 1st detection and performs the same action as 1 and
2.
Check the resistance of IPM. In the case of abnormality, replace the gate ampere board and IPM. Check the resistance of diode stack.
6) IPM (intelligent power module) drive circuit in the gate amplifier defective
7) IPM (intelligent power module) drive signal output circuit defective, power factor detecting circuit failure in the multi controller board.
8) Current detection defective (AC,CT)
9) Compressor lock
10) Liquid sealing start-up of the compressor
11) Open-phase at the compressor side
12) IPM (intelligent power module) failure
13) Power supply board abnormality detecting circuit failure and IPM drive power supply circuit failure
In the case of abnormality, replace the diode stack.
When excluding of 234, Switch off and disconnect the connection of the compressor after confirming charge of main circuit electrolysis capacitor is discharged enough. Then, switch on and operate in no-load.
(1) When the compressor is interrupted again. Replace the gate amplifier board (for VM type). Replace the power supply board when the compressor does not back to normal even if the gate amplifier board is replaced. Replace the multi controller board when the compressor does not back to normal even if the power supply board is replaced.
(2) Check the balance of inverter output voltage. If it is unbalanced,··· Replace the gate amplifier board (for VM type). Replace the power supply board when the compressor does not back to normal even if the gate ampere is replaced. Replace the multi controller board when the compressor does not back to normal even if the power supply board is replaced.
When not applying from 2 to 5, it applies to 9) and 10). Check the compressor.
In case of 10), recheck the compressor again after 12 hours of current carrying to the crank case heater.
1
2
3
4
5
4
6
1
2
3
4
5
6
Display
Meaning and detecting method
Causes
Check points
on
21345678
65
5101
Suction temperature thermistor (TH21) abnormality When controller detects short (high temp.)/open (low temp.) in thermistor during the operation, the operation stops and the operation changes to protect mode of restarting in 3minutes. If the thermistor does not recover in 3minutes, the operation stops abnormally. In this time, <5101> is displayed. Then, if the thermistor recover in 3minutes, it operates normally.
1) Connector(CN20) contact failure Check whether the connector (CN20) in the indoor controller board is connected or not.
2) Thermistor wiring disconnection or
half disconnection
Check whether the thermistor wiring is disconnected or not.
Short: Detected 90; or more
3) Thermistor failure Check the resistance of thermistor;
Open: Detected —40; or less
0;···15k’ 10;···9.6k’ 20;···6.3k’ 30;···4.3k’ 40;···3.0k’
4) Detecting circuit failure in the
indoor controller board
When there is no problem in above mentioned 123,replace the indoor controller board.
Discharge temperature thermistor (TH1) abnormality
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes.When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
1) Connector (TH1) contact failure Check whether the connector (TH1) in the multi controller board is connected or not.
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5101> is displayed.
2) Thermistor wiring disconnection or
half disconnection
Check whether the thermistor wiring is disconnected or not.
While the compressor is protected to restart in 3minutes, the unit is delayed to abnormal stop. Then, the outdoor unit address No. and check delay code <1202> blinks alternately on the 4 digit digital display.
3) Thermistor failure Check the resistance of thermistor; When the resistance is not below value, replace the thermistor.
SW1 setting
0;··· about 700k
For 10 minutes after starting compressor, for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.
10;··· about 410k’ 20;··· about 250k’
Short: 216;or more (1k)
30;··· about 160k
Open: 0; or less (700k)
40;··· about 104k
Note) When outer temperature thermistor (TH6) is 5; or less on cooling, open detecting is not determined as abnormality.
4) Multi controller board input circuit
failure
Set the SW1 to When the temperature in multi
controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
1
2
3
4
1
2
3
4
1
2
3
4
Display
Meaning and detecting method
Causes
Check points
on
21345678
on
21345678
66
Display
5102
Meaning and detecting method
Liquid pipe temperature thermistor (TH22) abnormality
When the thermistor detects short/open during the operation, the operation stops and the operation changes to protect mode of restarting in 3minutes. If the thermistor does not recover in 3minutes, the operation stops abnormally. In this time, <5102> is displayed. Then, if the thermistor recover in 3minutes, it operates
normally. Short: Detected 90; or more Open: Detected -40; or less
Causes
1) Connector(CN21) contact failure Check whether the connector
1
Check points
(CN21) in the indoor controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure
2
Check whether the thermistor wiring is disconnected or not.
3
Check the resistance of thermistor;
0;···15k’ 10;···9.6k’ 20;···6.3k’ 30;···4.3k’ 40;···3.0k’
Suction pressure saturation temperature thermistor (TH2) abnormality
1
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes.When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
2
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5102> is displayed.
While the compressor is protected to
3
restart in 3minutes, the unit is delayed to abnormal stop. Then, the outdoor unit address No. and check delay code <1211> blinks alternately on the 4 digit digital display.
SW1 setting
For 10 minutes after starting compressor,
4
21345678
on
for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.
Short: 100; or more (0.5k’ ) Open: -46; or less (200k’ )
4) Detecting circuit failure in the indoor controller board
When there is no problem in above
4
mentioned 123,replace the indoor controller board.
1) Connector (TH2) contact failure Check whether the connector (TH2)
1
in the multi controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
2
Check whether the thermistor wiring is disconnected or not.
3
0;···15k
10;···9.6k’ 20;···6.3k’
30;···4.3k’ 40;···3.0k’
21345678
4) Multi controller board input circuit
4
Set the SW1 to
on
failure
When the temperature in multi controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
67
Display
Meaning and detecting method
5103 Gas pipe temperature thermistor (TH23)
abnormality
When the thermistor detects short/open after 3minutes-continuous thermo ON during cooling or dry operation, the operation stops and the operation changes to protect mode of restarting in 3minutes. If the thermistor does not recover in 3minutes, the the operation stops abnormally. In this time, <5103> is displayed. Then, if the thermistor recover in 3minutes, it operates normally.
Short: Detected 90; or more
Open: Detected -40; or less
Causes
1) Connector(CN29) contact failure Check whether the connector (CN29)
1
Check points
in the indoor controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
2
Check whether the thermistor wiring is disconnected or not.
3
0;···15k
10;···9.6k’ 20;···6.3k’ 30;···4.3k’ 40;···3.0k’
5105
Condenser outlet temperature thermistor (TH5) abnormality
1
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes.When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
2
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5105> is displayed.
While the compressor is protected to
3
restart in 3minutes, the unit is delayed to abnormal stop. Then, the outdoor unit address No. and check delay code <1205> blinks alternately on the 4 digit digital display.
SW1 setting
21345678
on
4) Detecting circuit failure in the indoor controller board
4
When there is no problem in above mentioned 123,replace the indoor controller board.
1) Connector (TH5) contact failure Check whether the connector (TH5)
1
in the multic controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
2
Check whether the thermistor wiring is disconnected or not.
3
When the resistance is not below value, replace the thermistor.
0;···15k
10;···9.6k’ 20;···6.3k’
30;···4.3k’ 40;···3.0k’
For 10 minutes after starting compressor,
4
for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.
Short: 88; or more (0.4k)
Open: -39; or less (115k)
4) Multi controller board input circuit failure
68
21345678
4
Set the SW1 to
on
When the temperature in multi controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
Display
5106
Meaning and detecting method
Outer temperature thermistor (TH6) abnormality
1
When controller detects short/open in thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes.When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
2
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5106> is displayed.
While the compressor is protected to
3
restart in 3minutes, the unit is delayed to abnormal stop. Then, the outdoor unit address No. and check delay code <1221> blinks alternately on the 4 digit digital display.
SW1 setting
4
For 10 minutes after starting compressor,
21345678
on
for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.
Short: 88; or more (0.4k’ ) Open: -39; or less (115k’ )
Causes
1) Connector (TH6) contact failure Check whether the connector (TH6)
1
Check points
in the multi controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
Check whether the thermistor wiring
2
is disconnected or not.
3
When the resistance is not below value, replace the thermistor.
0;···15k
10;···9.6k’ 20;···6.3k’
30;···4.3k’ 40;···3.0k’
21345678
4) Multi controller board input circuit failure
4
Set the SW1 to When the temperature in multi
on
controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
5110 IPM radiator panel temperature thermistor
(THHS) abnormality When controller detects short/open in
1
thermistor during the operation, the outdoor unit stops once and restarts operation in 3minutes.When the detected temperature is normal at just before of restarting, the outdoor unit restarts.
2
When controller detects short/open in thermistor at just before of restarting, the unit stops abnormally. In this time, <5110> is displayed.
3
While the compressor is protected to restart in 3minutes, the unit is delayed to abnormal stop. Then, the outdoor unit address No. and check delay code <1214> blinks alternately on the 4 digit digital display.
SW1 setting
4
For 10 minutes after starting compressor,
21345678
on
for defrosting or for 3minutes after recover of defrosting, above-mentioned short/open are not detected.
Short:132; or more (1.2k’ ) Open: -30; or less (1200k’ )
1) Connector (THHS) contact failure Check whether the connector (THHS)
1
in the multi controller board is connected or not.
2) Thermistor wiring disconnection or half disconnection
3) Thermistor failure Check the resistance of thermistor;
Check whether the thermistor wiring
2
is disconnected or not.
3
When the resistance is not below value, replace the thermistor.
0;···180k’ 10;···105k’ 20;···63k’
30;···39k
4) Multi controller board input circuit failure
40;···25k Set the SW1 to
4
When the temperature in multi
21345678
on
controller board is not an actual temperature, replace the multi controller board.
-99.9: Open
999.9: Short
69
Display
5201 Pressure sensor (63HS) abnormality
6600 Duplex address error
Meaning and detecting method
1
When detected pressure in high-pressure pressure sensor is 1MPa or less during the operation, the compressor stops and restarts operation in 3minutes.
2
When the detected pressure is 1MPa or less at just before of restarting, the compressor stops abnormally. In this time, <5201> is displayed.
For 3minutes after the compressor stops,
3
the unit delays to abnormal stop. Then, the outdoor unit address No. and check delay code <1402> blinks alternately on the 4digit digital display.
SW1 setting For 3minutes after starting compressor,
4
for defrosting or for 3minutes after recover of defrosting, abnormality is not determined as abnormality.
Detected error when transmission of unit with the same address is confirmed,
Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.
21345678
on
Causes
1) High-pressure pressure sensor failure
2) Internal pressure decrease by gas leakage
3) Connector contact failure, disconnection
4) Multi controller board input circuit failure
1) There are 2units or more with the same address among the outdoor unit or indoor unit or lossnay controller, remote controller.
Check points
1
Check the high-pressure pressure sensor.
Check the internal pressure.
2
Check the high-pressure pressure
3
sensor.
Check the high-pressure pressure
4
sensor.
Look for the unit, which is source of
1
abnormality with the same address. When the same address is found, correct the address and turn off power supply of outdoor unit, indoor unit, and lossnay for 2minutes or more as the same time. Then, turn on power supply.
6602 Transmission processor H/W error
'' 1 '' shows on the transmission line though the transmission processor transmitted '' 0''.
Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.
2) When noise has occurred in the transmission signal, and the signal has changed.
1) When the wiring for either of the indoor unit, the outdoor unit or lossnay transmission line is constructed or polarity is changed with the power supply turned on, the transmission waves change in case that the transmission data collides mutually. It causes to detect error.
2) Transmission processor circuit failure
3) When the transmission data has changed by the noise.
Check the transmitted wave and the
2
noise on the transmission line.
When the transmission line is
1
constructed with the current flowed, turn off power supply of outdoor unit, indoor unit and lossnay for 2minutes or more as the same time. Then, turn on power supply.
Check the transmitted wave and the
2
noise on the transmission line.
70
Display
6603 Transmission bus busy error
Meaning and detecting method
1
Over error by collision 1) The transmission processor cannot
Abnormality when the state, which cannot be transmitted by collision of transmission, is consecutive for 8 to 10minutes.
Causes
be transmitted since a short cycle voltage of the noise etc. mixes on the transmission line consecutively.
Check points
1
Check whether the transmission line of the indoor unit, fresh master, lossnay and remote controller is connected to the outdoor unit terminal board (TB7) for centralized controller or not.
6606
2
The state that data cannot to be output to the transmission line by the noise happens for 8 to 10minutes consecutively.
Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.
Signal communication error with transmission processor
Signal communication error between unit processor and transmission processor
Note) Address/Attribute displayed on the remote controller shows the controller detecting abnormality.
2) The transmission volume increases and cannot be transmitted since the wiring method is mistaken and the routing technique to the terminal board (TB3) for the transmission line of the outdoor unit and the terminal board (TB7) for centralized control cannot be transmitted.
3) The share becomes high since the data exists together to other transmitted data by a defective repeater (function which connects and intercepts the transmission of controlling system and centralized control system), and it causes abnormal detection.
1) It happened since the noise and lightening serge that happened by chance had not normally transmitted the data of the unit/transmission processor.
2
Check whether the transmission line with the other refrigerant system of the indoor unit and lossnay is connected to the outdoor unit terminal board (TB3) for transmission or not.
3
Check whether the outdoor unit terminal board for transmission line (TB3) and for centralized controller (TB7) are connected or not.
4
Check the transmitted wave and the noise on the transmission line.
Turn off power supply of outdoor unit, indoor unit, and lossnay for 2minutes or more at the same time. Then, turn on power supply. It recovers normally at the malfunction that happens by chance. When same abnormality occurs again, it is defective of a generation former controller.
2) The address transmission from the unit processor was not normally transmitted by the hardware of transmission processor defective.
71
Display
6607
Meaning and detecting method No ACK Abnormality which controller of the
1
sending side detects when there is no answer (ACK) from other side though data was transmitted once. It is detected 6 times every 30seconds continuously.
Note) Address/Attribute displayed on the remote controller shows the controller, which did not send back replay (ACK).
Causes
Factor that not related to origin
1) Since the address switch was changed with the current passed, the unit in the last address does not exist.
2) Decline of transmission voltage and signal by transmission line tolerance over
· The furthest point···200m
· Remote controller line···(12m) (See page 28-33 for details)
3) Decline of transmission line voltage and signal by unmatched kind of line.
Kind···Shield line-CVVS,CPEVS No shield···VCTF, VCTFK,
CVV, CVS, VVR, VVF, VCT Line diameter···1.25 e or more
4) Decline of transmission line voltage and signal by a number of over­connected units.
5) Miss operation of origin controller, which happens by chance.
6) Origin controller defective
Check points
1
Turn off power supply of outdoor unit, indoor unit fresh master and lossnay for 2minutes or more at the same time. Then, turn on power supply. It recovers normally at the malfunction that happens by chance.
Check the address switch in the
2
address, which occurs abnormality.
3
Check whether the transmission line is connected / loosen or not at origin. (Terminal board or connector)
Check whether the transmission line
4
tolerance is over or not.
Check whether the kind of
5
transmission line is mistaken or not. When there is any trouble from above
1-5, turn off power supply of outdoor unit, indoor unit and lossnay for 2minutes or more at the same time. Then, turn on power supply.
1) When the cause of displayed address and attribute is on the outdoor unit side
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the outdoor unit.)
2) When the cause of displayed address and attribute is on the indoor unit side
(The remote controller detects when there is no reply (ACK) on transmitting from the remote controller to the indoor unit.)
1) Contact failure of outdoor unit or indoor unit transmission line
2) Indoor unit transmission connector (CN2M) disconnection
3) Sending/receiving signal circuit failure in the indoor/outdoor unit
1) When operating with multi refrigerant system indoor units, the remote controller transmits the signal to the indoor unit after the other refrigerant system outdoor unit is turned off or turned on again in 2minutes, and detects abnormality.
2) Contact failure of remote controller or indoor unit transmission line.
3) Indoor unit transmission connector (CN2M) disconnection.
4) Sending/receiving signal circuit failure in the indoor / unit / remote controller.
When there is not any trouble in single refrigerant system (1outdoor unit) from above1-5, controller defective in displayed address and attribute. When there is not any trouble in different refrigerant system (2outdoor unit or more) from above1-5, determine it after 6.
When the address, which should not
6
exist, is an origin, since there is the indoor unit which memorizes the address data, cancel the unnecessary address data by the manual setting function of remote controller. However, they are limited to the system, which sets the group between different refrigerant systems, or which fresh master /lossnay are connected.
When there is not any trouble from above 1-6, replace the displayed address/attribute controller board.
In this time, when the error does not recover to normal, the outdoor unit multi controller board (repeater circuit) defective is expected.
Check the recovery by replacing the multi controller board one by one.
72
Display
Meaning and detecting method
Causes
Check points
6607
3) When the cause of displayed address and attribute is on the remote controller side
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the remote controller unit.)
4) When the cause of displayed address and attribute is on the fresh master side
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the fresh master
1) When operating with multi refrigerant system indoor units, the indoor units transmits the signal to the remote controller after the other refrigerant system outdoor unit is turned off or turned on again in 2minutes, and detects abnormality.
2) Contact failure of remote controller or indoor unit transmission line
3) Indoor unit transmission connector (CN2M) disconnection.
4) Sending/receiving signal circuit failure in the indoor / unit / remote controller.
1) When synchronized operating with other refrigerant system fresh master, the indoor units transmits the signal to the fresh master after the fresh master and same refrigerant system outdoor unit is turned off or turned on again in 2minutes, and detects abnormality.
5) When the cause of displayed address and attribute is on the lossnay side
(The indoor unit detects when there is no reply (ACK) on transmitting from the indoor unit to the lossnay.)
2) Contact failure of fresh master or indoor unit transmission line
3) Indoor unit or fresh master transmission connector (CN2M) disconnection.
4) Sending/receiving signal circuit failure in the indoor/fresh master.
1) When the lossnay power supply is Off, the indoor unit detects abnormality at signal transmitting to the lossnay.
73
Display
6607
Meaning and detecting method
Causes
2) When synchronized operating with other refrigerant system lossnay, the indoor units transmits the signal to the lossnay after the lossnay and same refrigerant system outdoor unit is turned off or turned on again in 2minutes, and detects abnormality
3) Contact failure of lossnay or indoor unit transmission line
4) Indoor unit transmission connector (CN2M) disconnection.
5) Sending/receiving signal circuit failure in the indoor/lossnay.
Check points
6608
6) When the controller of displayed address and attribute is not recognized
No response Though there was a replay (ACK) of having received signal from the other side, it is the abnormality when the response command does not return. The sending side detects the abnormality continuously six times every 30 seconds. Note) Address/Attribute displayed on the remote controller shows the controller, which did not response.
1) Since the address switch was changed with the current passed, the unit in the last address does not exist.
2) Since the fresh master/lossnay address are changed after synchronized setting of fresh master / lossnay by the remote controller, abnormality is detected at transmitting from the indoor unit.
1) Transmission repeats the failure by the noise etc.
2) Decline of transmission voltage and signal by transmission line tolerance over.
· The furthest point···200m
· Remote controller line···(12m) (See page 44-53 for details)
Check the transmission wave and
1
noise on the transmission line.
Turn off power supply of outdoor unit,
2
indoor unit and lossnay for 2minutes or more at the same time. Then, turn on power supply again. It recovers normally at the malfunction that happens by chance. When same abnormality occurs again, it is defective of displayed address and attribute.
3) Decline of transmission line voltage and signal by unmatched kind of line.
Kind···Shield wire-CVVS,CPEVS
No shield ···VCTF, VCTFK,
CVV, CVS, VVR, VVF, VCT wire diameter···1.25eor more
4) Miss operation of origin controller, which happens by chance.
74
Display
Meaning and detecting method
Causes
Check points
6810 UR communication abnormality (UR: Unit
Remote controller) Communications between the unit remote controller and indoor unit is not normal.
When there is no display of address and attribute to the remote controller. (When detecting by the unit remote controller)
1) It is abnormality though the unit remote controller transmitted ''H'', when "L" reception is detected continuously three times.
2) It is abnormality when there is no response from the indoor unit for 3 minutes against to ''monitor request'' from the unit remote controller.
3) It is abnormality when there is no response 3times continuously from the indoor unit against to ''operation /setting'' from the unit remote controller.
When the cause of displayed address and attribute is on the indoor unit side.
1) It is abnormality though the indoor unit transmitted ''H'', when "L" reception is detected continuously three times.
2) It is abnormality when the indoor units cannot receive the transmission signal from the unit remote controller for 3minutes.
1) Contact failure of the unit remote controller transmission line in the unit remote controller or indoor unit.
2) Decline of transmission voltage and signal on the unit remote controller transmission line by the unit remote controller transmission line tolerance over
3) When the transmission signal of unit remote controller changes by noise.
4) Unit remote controller transmitting / receiving signal circuit failure in the unit remote controller or indoor unit.
1
Check whether the transmission line of the indoor unit or unit remote controller is connected / loosen or not.
Check whether the unit remote
2
controller transmission line tolerance is over or not.
Check the transmission wave and
3
noise on the transmission signal of unit remote controller.
When there is not any trouble from
4
above 1-3, replace the indoor controller board or unit remote controller.
Check of following conditions is available by LED1/LED2 in the indoor controller board.
· When LED1 and 2 blinks at the same time.
The indoor unit is transmitting to the unit remote controller.
· When only LED2 blinks. The unit remote controller is
transmitting to the indoor unit. Or, other indoor unit is transmitting to
the unit remote controller.
·When LED1 and 2 does not blink. The indoor unit and unit remote
controller is not transmitting.
6831 6834
6832 6833
Signal reception abnormality (Remote controller) Following symptoms are regarded as abnormality.
1) When the remote controller cannot receive the signal from indoor controller normally even once for 3 minutes
2) When sub-remote controller cannot receive the signal even once for 2 minutes
Signal transmission abnormality (Remote controller) Following symptoms are regarded as abnormality.
1) When sub-remote controller cannot transmit the signal to the transmission path for 6 seconds
2) When the remote controller cannot finish transmitting the signal for 30 times on end
Defect of the transmission and reception
1
circuit of the remote controller. Defect of the transmission and
2
reception circuit of the indoor controller board
Noise occurs on the transmission line
3
of the remote controller All remote controllers are set as
4
sub-remote controller.
Defect of the transmission and
1
reception circuit of the remote controller Noise occurs on the transmission line
2
of the remote controller There are two main remote controllers.
3
1~3
Perform a check of the remote controller. According to the results, perform the following disposals.
• When "RC OK" is displayed The remote controller is normal. Turn off the power supply and turn it
on again. If "HO" is displayed for 4 minutes or more, replace the indoor controller board.
• When "RC NG" is displayed Replace the remote controller.
• When "RC 6832 or 6833" or "ERC 00-66" is displayed These displays may be due to noise, etc.
4 Set one remote controller to main
remote controller and the other to sub-remote controller.
75
Display
7100
Meaning and detecting method
When connected total models of the indoor units exceed the specified level (130% of the outdoor unit models), error code <7100> is displayed.
Causes
1) Connecting total models of the indoor unit exceed the specified level.
71: Possible up to 93 (code 18) 125: Possible up to 163 (code 33)
Check points
1
Check the total models of connected indoor unit.
Check the model code registration
2
switch (indoor controller board SW2) of connected indoor unit.
7101 Capacity code error
When the connected indoor unit models cannot be connected, <7101> is displayed.
2) There is a mistake in the registration of model name code of the outdoor unit.
The indoor unit models is not possible to connect,
The indoor unit of 20-80 (code 4-16) is possible to connect, (PUMY-71VM,71VM1,125VM) The indoor unit of 20-125(code 4-25) is possible to connect. (PUMY-125VM1,125YM)
Check the model code registration switch (outdoor multi controller board SW4) of the outdoor unit.
Check the model code registration
1
switch (indoor controller board SW2) in the connected indoor unit.
The outdoor unit SW1 operation can
2
check model code of the connected indoor units.
Code of indoor unit No.1
Code of indoor unit No.2
Code of indoor unit No.3
Code of indoor unit No.4
Code of indoor unit No.5
21345678
on
21345678
on
21345678
on
21345678
on
21345678
on
7102 Number of connecting unit over
When the connecting unit exceeds a number of limitations, error code <7102> is displayed.
Connecting unit exceeds a number of limitations. It is assumed abnormality excluding the following cases;
1) The indoor unit can be totally connected up to 8 units. The indoor unit can be connected up to 8 units (PUMY-125VM1,125YM)
2) The indoor unit can be connected 1 units or more. (Only PUMY-71VM,125VM)
3) Ventilation unit connecting is only 1unit.
76
Code of indoor unit No.6
Code of indoor unit No.7
Code of indoor unit No.8
21345678
on
21345678
on
21345678
on
Check whether the connecting unit exceeds a number of limitations or not.
Display
7105 Address setting error
Meaning and detecting method
Address setting of the outdoor unit is wrong.
Causes
Addresses miss setting of the outdoor unit.
The outdoor unit is not set in 000 or in the range of 51-100.
Check points
Check the address setting of the outdoor unit. The address should be set in 000 or 51-100.
When the setting is out of the range, reset it, turn off power supply of the outdoor unit, indoor unit and lossnay for 2minutes or more at the same time, and turn on power supply again.
7111 When an old type remote controller for
Remote controller sensor abnormality In the case of network remote controller, it
is an abnormality when incapable response returns from the net work remote controller during the operation.
M-NET is used, and the remote controller sensor is specified (SW1-1 is ON).
Replace the remote controller to net work remote controller.
8-2. Remote controller diagnosis
• MA remote controller is equipped with the diagnosis function of the remote controller. Check the remote controller with this function when the unit does not operate with the remote controller.
(1)
Electric current marker
(2)
(1) First, check the electricity current maker.
If the correct voltage (DC 8.7~13V) is not supplied on the remote controller, the electric current marker will be lit. If the electricity current marker is not lit, check the remote controller wiring and the indoor units.
(2) Transfer to remote control diagnosis mode.
Hold down the CHECK button for five seconds or more to display the diagram on the left.
Press the FILTER button to commence diagnosis of remote controller.
(3)
a)
b)
(3) Remote controller diagnosis results.
a) The remote control is functioning correctly.
Check other possible causes as there are on problems with the remote controller.
b) The remote controller has a nonconformity.
The remote controller must be replaced. Error display 1 (“NG”) flashes to show a nonconformity in the transmitter-receiver circuit.
To be continued on the next page.
77
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
“ ” indicator: Appears when current is carried.
Symptom or inspection code Cause Inspection method and solution
Though the content of operation is displayed on the remote controller, some indoor units do not operate.
• The power supply of the indoor unit is not on.
The address of the indoor units in same group or the remote controller
is not set correctly.
The group setting between outdoor units is not registered to the remote
controller.
• The fuse on the indoor unit controller board is blown.
• Check the part where the abnormality occurs.
1 The entire system 2 In the entire refrigerant system 3 In same group only 4 One indoor unit only
<In case of the entire system or in the entire refrigerant system>
Check the self-diagnosis LED
of the outdoor unit.
• Check the items shown in the left that are related to the outdoor unit.
<In case of in same group only or one indoor unit only>
• Check the items shown in the left that are related to the indoor unit.
Though the indoor unit operates, the display of the remote controller goes out soon.
• The power supply of the indoor unit is not on.
• The fuse on the indoor unit controller board is blown.
( ) is not displayed on the remote controller.
(M-NET remote controller
is not fed.)
• The power supply of the outdoor unit is not on.
The number of connected indoor unit in the refrigeration system is over the limit or the number of connected remote controller is over the limit.
M-NET remote controller is connected to MA remote controller cable.
• The transmission line of the indoor/outdoor unit is shorted or down.
• M-NET remote controller cable is shorted or down.
"HO" keeps being displayed or it is displayed periodically. ("HO" is usually displayed for 3 minutes at the longest after the power supply of the outdoor unit is on.)
• The power supply for the feeding expansion unit for the transmission line is not on.
• The address of the outdoor unit remains "00".
The address of the indoor unit or the remote controller is not set correctly.
• MA remote controller is connected to the transmission line of the indoor/outdoor unit.
The remote controller does not operate though ( ) is displayed.
• The transmission line of the indoor/outdoor unit is connected to TB15.
• The transmission line of the indoor/outdoor unit is shorted, down or badly contacted.
From the preceding page.
a)
Potential problems other than those diagnosed for the remote controller.
a) Single transmission not possible if error display 2 (“6832
or 6833”) flashes. There is “noise” on the transmission line, or damage of other remote controller for the indoor units can be considered. Check the transmission path and other controller
b)
• When the number of data errors generated is 02.
Remote controller transmission data Transmission data at transmission path
8-3. Remote controller trouble
b) Data error has occurred when error display three shows
“ERC” and number of data errors. Number of generated data error (maximum 66 errors). The number of generated data error stands for the difference in the number of bits of transmitted data from the remote controller and the actual number of bits that were transmitted along the transmission path. If this error occurs, “noise”, etc., is interfering with the transmission data. Check the transmission path.
(4) Cancel the remote controller diagnosis.
Hold down the CHECK button for five seconds or more to cancel the remote controller diagnosis. The “HO” operation lamp will flash, and the display screen will rectum to the status before remote controller diagnosis in approximately 30 seconds.
(1) For M-NET remote controller systems
78
Symptom Even the cooling (heating)
operation selection button is pressed, the indoor unit cannot be operated. The auto vane runs freely.
Fan setting changes during heating.
Fan stops during heating operation. Fan does not stop while operation has been stopped. No setting of fan while start SW has been turned on.
Indoor unit remote controller shows “HO” indicator for about two minutes when tur­ning ON power supply.
Drain pump does not stop while unit has been stopped. Drain pump continues to operate while unit has been stopped.
Display of remote controller "Cooling (Heating)" blinks
Normal display
Normal display
"Defrost "
Light out
STAND BY
“HO” blinks
Light out
CAUSE The indoor unit can not cool (heat) if other indoor units are heating (cooling).
Because of the control operation of auto vane, it may change over to horizontal blow automatically from the downward blow in cooling in cause the downward blow operation has been continued for one hour. At defrosting in heating, hot adjusting and thermostat OFF, it automatically changes over to horizontal blow.
Ultra-low speed operation is commenced at thermostant OFF. Light air automatically change over to set value by time or piping temperature at thermostat ON.
The fan is to stop during defrosting.
Fan is to run for one minute after stopping to exhaust residual heat (only in heating).
Utra-low speed operation for 5 minutes after SW ON or until piping temperature becomes 35°C. There low speed operate for 2 minu­tes, and then set notch is commenced. (Hot adjust control) System is being driven.
Operate remote controller again after “HO” disappears.
After a stop of cooling operation, unit continues to operate drain pump for three minutes and then stops it.
Unit continues to operate drain pump if drainage is generated, even during a stop.
(2) For MA remote controller systems
Symptom or inspection code Cause Inspection method and solution
Though the content of operation is displayed on the remote controller, some indoor units do not operate.
Though the indoor unit operates, the display of the remote controller goes out soon.
( ) is not displayed on the remote controller. (MA remote controller is not fed.)
"HO" keeps being displayed or it is displayed periodically. ("HO" is usually displayed for 3 minutes at the longest after the power supply of the outdoor unit is on.)
The
remote controller does not
operate though ( ) is displayed.
• The power supply of the indoor unit is not on.
• Wiring between indoor units in same group is not finished.
• The indoor unit and Slim model are connected to same group.
• The fuse on the indoor unit controller board is blown.
• The power supply of the indoor unit (Master) is not on.
• In case of connecting the system controller, the setting of the system controller does not correspond to that of MA remote controller.
• The fuse on the indoor unit (Master) controller board is blown. The remote controller is not fed until the power supply of both indoor unit
and outdoor unit is on and the start-up of both units is finished normally.
• The power supply of the indoor unit is not on.
• The power supply of the outdoor unit is not on.
• The number of connected remote controller is over the limit (Maximum: 2 units) or the number of connected indoor unit that is over the limit (Maximum: 16 units).
The address of the indoor unit is "00" and the address for the outdoor
unit is the one other than "00".
The transmission line of the indoor/outdoor unit is connected to TB15.
• MA remote controller is connected to the transmission line of the indoor/outdoor unit .
• The remote controller cable is shorted or down.
• The power supply cable or the transmission line is shorted or down.
• The fuse on the indoor unit controller board is blown.
• The power supply of the outdoor unit is not on.
• The power supply of the feeding expansion unit for the transmission line is not on.
• The setting of MA remote controller is not main remote controller, but sub-remote controller.
• MA remote controller is connected to the transmission line of the indoor/outdoor unit
• The power supply of the indoor unit (Master) is not on.
• The transmission line of the indoor/outdoor unit is connected to TB15.
• The transmission line of the indoor/outdoor unit is shorted, down or badly contacted.
•The fuse on the indoor unit controller board is blown.
.
• Check the part where the abnormality occurs.
1 The entire system 2 In the entire refrigerant system 3 In same group only 4 One indoor unit only
<In case of the entire system or in the entire refrigerant system>
Check the self-diagnosis LED
of the outdoor unit.
• Check the items shown in the left that are related to the outdoor unit.
<In case of in same group only or one indoor unit only>
• Check the items shown in the left that are related to the indoor unit.
8-4. The following Symptom do not represent trouble (emergency)
79
Outdoor unit
Switch
SW U1 1st digit
SW U2 2nd digit
SW U3 3rd digit
SW1 Digital Display Switching
SW2 function Switching
SW5 function switching
SW3 Trial operation
SW4 Model Switching
Step
Operation in Each Switch Setting
ON OFF When to Set
Remarks
Before turing the power on
Before the power is turned on.
Can be set when off or during operation
SWU3
(3rd digit)
Rotary switch
1 2 3 4 5
6
7
8 9
10
1
2
1 2
3
4 5
6 7 8
Function
1~8
1~4
Can be set either during operation or not.
Before turning the power on
While unit stopping.
Any time after the power is turned on.
OFF to ON any time after the power is turned on.
Can be set during compressor stopping.
Active
Active
Active
Enable
Inactive
Inactive
Active
Active Pdm switching ETm switching
Inactive
Inactive Normal Normal
Run
Fix Fix
Stop
Disable
Inactive
Start upDoesn´t start up
Clear
Do not clear
Normal Normal
Normal Normal
Fix Normal Enable Disable
Normal
Continuous 30 min.
(ordinary)
Clear abnormal data Run adjustment mode.
Selects operating system startup Connection Information Clear Switch Abnormal data clear switch input Refrigerant Volume Adjustment Operation Linear expansion valve opening
setting of suspending indoor unit in the heat mode.
Linear expansion valve opening setting of FAN. COOL•HEAT thermo OFF indoor unit in the heat mode.
Forced defrost
Cumulative 60 min.
Forced defrost
Defrost detection switching Defrost disabled time selection
Linear expansion valve opening setting of thermo OFF unit in the heat mode.
Enable/disable operation from outdoor unit
Run/stop from the outdoor unit.
<Factory Settings>
<Factory Settings>
<Factory Settings>
<Factory Settings>
<Factory Settings>
<Factory Settings> Set for each capacity.
Fix the operation frequency Fixing the indoor units linear expansion
valve opening Fixing the outdoor unit electronic
expansion valve opening. Enable fixing at the desired frequency Maintain outdoor fan at fixed speed
and ignore outdoor temperature sensor abnormality
Ignore refrigerant filling abnormality Switching the target discharge pressure (Pdm) Switching the target evaporation temperature (ETm)
0
1
2
3
4
5
6
7
8
9
SWU2
(2nd digit)
0
1
2
3
4
5
6
7
8
9
SWU1
(1st digit)
0
1
2
3
4
5
6
7
8
9
SWU3
(3rd digit)
0
1
2
3
4
5
6
7
8
9
SWU2
(2nd digit)
0
1
2
3
4
5
6
7
8
9
SWU1
(1st digit)
0
1
2
3
4
5
6
7
8
9
1
ON
OFF
2345678
1
ON
OFF
2345678
1
ON
OFF
2345678
1
ON
OFF
2345678910
1
ON
OFF
2
OFF ➔ ON, during compressor running in heating mode.
OFF ON while compressor is not operating
While unit stopping.
While unit stopping.
Service ref.
SW4
1
ON
OFF
234
Service ref.
SW4
PUMY-71VM PUMY-71VM1
PUMY-125VM PUMY-125VM1 PUMY-125YM
PUMY-125VM2 PUMY-125YM1 PUMY-125YMA
PUMY-71VM2
1
ON
OFF
234
1
ON
OFF
234 1
ON
OFF
234
8-5. INTERNAL SWITCH FUNCTION TABLE
Outdoor unit internal switch function table
80
8-6. HOW TO CHECK THE COMPONENTS
<Thermistor feature chart>
Low temperature thermistors
Saturation temperature of suction pressure thermistor (TH2) Pipe temperature thermistor (TH5) Outdoor temperature thermistor (TH6)
Thermistor R0 = 15k' ±3% B constant = 3480k' ±2%
t =15exp{3480(
R 0: 15k'
10: 9.6k' 20: 6.3k' 25: 5.2k'
Medium temperature thermistor
Radiator panel temperature thermistor (THHS)
1 1
273+t – 273
30: 4.3k' 40: 3.0k'
)}
Thermistor R50 = 17k' ±2% B constant = 4170k' ±3%
1
t =17exp{4170(
R 0: 180k'
25: 50k' 50: 17k' 70: 8k' 90: 4k'
High temperature thermistor
Discharge temperature thermistor (TH1) Thermistor R120 = 7.465k' ±2%
B constant = 4057k' ±2%
t =7.465exp{4057(
R 20: 250k'
30: 160k' 40: 104k' 50: 70k' 60: 48k'
1
273+t – 323
1
273+t – 393
70: 34k' 80: 24k' 90: 17.5k' 100: 13.0k' 110: 9.8k'
)}
1
)}
81
Linear expansion valve (LEV: Indoor unit), Electronic expansion valve (SLEV: Outdoor unit)
M
LEV SLEV
Blue
{4 {3 {2 {1
{4 {3 {2 {1
2 5 1 3 4 6
6 5 4 3 2 1
BRN RED BLU ORN YLW WHT
Brown Yellow
Red
White
Orange
1
5
2 3
6
4
Relay connector (Only LEV)
Controller board
DC12V
Drive circuit
Connector (CN60)
(SLEV)
11
Notes on expansion valve action
• LEV/SLEV to stepping motor ON/OFF after indoor/outdoor controller board has received pulse signal.
• The valve position can be changed according to the pulse signal number ratio. <connection between the LEV/SLEV and the indoor/outdoor controller board>
Note: Because the numbers of the relay connector and the connector on the controller board side are different, wiring work
must rely on the colors of the wires.
82
<Output pulse signal and valve action>
A
E
D
C
B
Closing
Opening
Completely sealed (80-100 pulses)
Number of pulses
Valve fully open at 2,000 pulses
Valve position (volume)
Problem Check point Corrective measure
Remove the connector from the controller board and connect diagnostic LEDs.
Pulses will be issued for 10 seconds when the power is turned on. It indicates that there is an abnormality in the operating circuit if any LEDs don't turn on or off.
If the linear expansion valve (indoor unit) or electronic expansion valve (outdoor unit) becomes locked and the motor is still operating, the motor will emit a clicking noise and will not function. This clicking noise indicates an abnormality.
Use an all-purpose electrical meter to measure the resistance between the different coils (red-white, red-orange, brown-yellow, brown-blue). Normal resistance is within a range of 150±10%.
In order to check the linear expansion valve, operate one indoor unit in the fan mode and another in the cooling mode. Then, use the outdoor multi controller board to operate the monitor and check the pipe temperature of the indoor unit (liquid pipe temperature). The linear expansion valve should be fully closed when the fan is operating. The temperature measured by the temperature sensor will drop if there is any leakage. If the measured temperature is significantly lower than that on the remote controller, this indicates that the valve is not closed. It is not necessary to replace the linear expansion valve if the leak of refrigerant is small and does not cause a malfunction.
1 Check improperly connected connector terminals and the wire colors. 2 Remove the connector on the controller board side and check electrical
conductance
Malfunction in microp­rocessor operating circuit
Locked expansion valve
Short circuit or broken circuit in expansion valve motor coil
Valve does no close completely
Incorrect connection or connection failure
Replace the indoor unit controller board or Replace the outdoor multi controller board.
Replace the linear expa­nsion valve or electronic expansion valve
Replace the linear expa­nsion valve or electronic expansion valve
Replace the linear expa­nsion valve if there is a major leak of refrigerant.
Continuity check of wrong part.
6 5 4 3 2 1
1k" LED
Temperature sensor
<liquid pipe>
Linear expansion valve
Output
Output(phase)
{1 {2 {3 {4
1
ON
ON OFF OFF
23
OFF
ON ON
OFF
2 LEV / SLEV action
OFF OFF
ON ON
4
ON OFF OFF
ON
Valve closing:1➔2➔3➔4➔1 Valve opening:4➔3➔2➔1➔4
The address of the pulse output is shifted using the procedures mentioned earlier.
w1. All output phase will turn OFF when the LEV or SLEV
stops operating.
2. When the output phase is terminated or when the phase shift is not according to frequency, the motor rotation will become irregular, causing the motor to vibrate or lockup.
w When the power supply is on, the closing signal of 2,200
pulse will be transmitted to decide the position of the valve. The valve position can be determined when point A is reached.
The LEV(SLEV) will not vibrate or make noise when the valve is operating smoothly. However, when the number of pulses change from E to A ,or if the valve lockup, there may be more noise than under normal circumstances.
• The noise can be heard by resting your ear on the handle of a screwdriver that is pressed against the top of the LEV(SLEV) valve.
3 Troubleshooting
83
8-7. OUTDOOR UNIT FUNCTIONS
0
1
2
3
4
5
6
7
8
9
10
11
121314
15161718192021
2223242526
27
282930
SW1 setting
12345678
00000000
10000000
01000000
11000000
00100000
10100000
01100000
11100000
00010000
10010000
01010000
11010000
00110000
10110000
01110000
11110000
00001000
10001000
01001000
11001000
00101000
10101000
01101000
11101000
00011000
10011000
01011000
11011000
00111000
10111000
01111000
Relay output display
Check display
Indoor unit check
Protection input
Protection input
Protection input
Abnormality delay display 1
Abnormality delay display 2
Abnormality delay display 3
Abnormality delay history 1
Abnormality delay history 2
Abnormality delay history 3
Abnormality code history 1 (the latest)
Abnormality code history 2
Abnormality code history 3
Abnormality code history 4
Abnormality code history 5
Abnormality code history 6
Abnormality code history 7
Abnormality code history 8
Abnormality code history 9
Abnormality code history 10 (the oldest)
Cumulative time
Cumulative time
Outdoor unit operation display
Indoor unit mode
Indoor unit operation display
Capacity code (No. 1 indoor unit)
Capacity code (No. 2 indoor unit)
Capacity code (No. 3 indoor unit)
Capacity code (No. 4 indoor unit)
Capacity code (No. 5 indoor unit)
1
Compressor operation
No.1 unit check
High-pressure abnormality
TH1 abnormality
Abnormality in the number of linked units
High-pressure abnormality delay
TH1 abnormality delay
High-pressure abnormality delay
TH1 abnormality delay
2
52C
No.2 unit check
Discharge temperature abnormality
TH2 abnormality
Address double setting abnormality
Discharge temperature abnormality delay
TH2 abnormality delay
Discharge temperature abnormality delay
TH2 abnormality delay
Refrigerant overfilling delay
3
21S4
No.3 unit check
Inner thermostat abnormality
TH6 abnormality
Indoor unit capacity
Internal thermostat abnormality delay
TH6 abnormality delay
Internal thermostat abnormality delay
TH6 abnormality delay
4
SV
No.4 unit check
IPM abnormality
TH5 abnormality
Over capacity
IPM abnormality delay
TH5 abnormality
delay
IPM abnormality delay
TH5 abnormality delay
7
No.7 unit check
Power synchronization signal abnormality
Restrict power IPM abnormality
Refrigerant over charge
Power synchronization signal abnormality
Restrict power IPM abnormality
Refrigerant over charge
Power synchronization signal abnormality
Restrict power IPM abnormality
5
No.5 unit check
Radiator panel abnormality
Indoor unit address error
Radiator panel overheating delay
Radiator panel overheating delay
6
No.6 unit check
Vacuum operation abnormality
THHS abnormality
Outdoor unit address error
THHS abnormality
delay
THHS abnormality delay
8
Lighting always
No.8 unit check
63HS abnormality
Insufficient voltage abnormality
63HS sensor abnormality delay
Single-phase current (CT)
Insufficient voltage abnormality delay
63HS abnormality delay
Single-phase power delay (CT)
Insufficient voltage abnormality delay
ON: light on OFF: light off
•When abnormaility occurs, check display.
Check: light on Normal: light off
Display input microprocessor
protection (abnormality)
Display all abnoramlities
remaining in abnormality
delay
Display all abnormalities
remaining in abnormality
delay history
•Display abnormalities up to
present (including abnorma-
lity terminals)
•History record in 1 is the
latest; records become older
in sequence; history record
in 10 is the oldest.
Display of cumulative
compressor operating time
Cooling : light on Heating: light flashing Stop fan: light off
Thermo ON : light on Thermo OFF : light off
•Display of indoor unit
capacity code
•The no. 1 unit will start from
the address with the lowest
number
Notes
Alternating display of addresses
0000-9999 and abnormality code
(including abnormality delay code)
0~9999(unit::1-hour)
0~9999(unit::10-hour)
0~255
Excitation Current
No.1 unit mode
No.1 unit operation
Restart after 3 minutes
No.2 unit mode
No.2 unit operation
Compressor operation
No.3 unit mode
No.3 unit operation
Abnomality(detection)
No.4 unit mode
No.4 unit operation
No.5 unit mode
No.5 unit operation
No.6 unit mode
No.6 unit operation
No.7 unit mode
No.7 unit operation
No.8 unit mode
No.8 unit operation
0000~9999 (Alternating display of addresses and error code)
Display mode
Display on the LD1 (display data)
No.
Delay code
1202
1205
1208
1211
1214
1221
Delay code
1402
1600
1601
4165
4320
4330
4350
Abnormality delay
Discharge temperature abnormality
Discharge temperature sensor (TH1) abnormality
Intake outlet temperature sensor (TH5) abnormality
Compressor internal thermostat abnormality
Saturation temperature of suction pressuse sensor (TH2) abnormality
Radiator panel thermistor (THHS) abnormality
Outside air temperature sensor (TH6) abnormality
Abnormality delay
High-pressure abnormality
Pressure sensor (63HS) abnormality
Over charge refrigerant abnormality
Insufficient refrigerant abnormality
Power synchronization signal abnormality
Frequency converter insufficient wiring voltage abnormality
Radiator panel temperature abnormality
IPM abnormality
SW:setting
0....OFF
1....ON
84
Notes
•Display of indoor unit
operating mode
8
7
6
Heating
thermo
5
Heating
thermo
4
Cooling
thermo
OFF
ON
OFF
Light on/light off
Input: light off No input: light on
Display of communication demand capacity
Display of actual operating frequency
Display of target frequency
Display of number of outdoor
fan control steps (target)
Display of openness (pulses) of
3-min.delay/no
Excitation current/no
power/no
Refrigerant pull back/no
DEFROST/NO
outdoor SLEV and indoor LEV
Display of outdoor subcool
(SC) data and detection data
from high-pressure sensor and
each thermistor
Display on the LD1 (display data)
3
Cooling
thermo
ON
Abnormal/Normal
2
Night mode
Heating/Cooling
1
Display mode
SW1 setting
12345678
No.
OFF Fan
Indoor unit mode (No. 1 unit)
Indoor unit mode (No. 2 unit)
Indoor unit mode (No. 3 unit)
11111000
00000100
10000100
31
32
33
ON/OFF
Demand junction
Indoor unit mode (No. 4 unit)
Indoor unit mode (No. 5 unit)
Outdoor unit operational mode
External connection status
11000100
01000100 34
00100100
10100100
353637
0~255
0~FF(16 progressive)
0~255
0~20
Communication demand capacity
Operational frequency
Target frequency
Outdoor fan control step number
01100100
00000010
10000010
01000010
3864656667
0~2000
EER fan control step number (cooling)
Outdoor SLEV opening
Indoor LEV opening (No.1 unit)
Indoor LEV opening (No.2 unit)
Indoor LEV opening (No.3 unit)
11000010
00100010 68
10100010
11100010
01100010
6970717273
Indoor LEV opening (No.4 unit)
Indoor LEV opening (No.5 unit)
High-pressure sensor (Pd)
TH1(Td)
TH2(ET)
TH6
TH5
THHS
00010010
10010010
01010010 74
11010010
00110010
757677
01110010
10110010
788081
00001010
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
TH23 (No.1 indoor unit)
TH23 (No.2 indoor unit)
TH23 (No.3 indoor unit)
TH23 (No.4 indoor unit)
TH23 (No.5 indoor unit)
TH22 (No.1 indoor unit)
TH22 (No.2 indoor unit)
11001010
10001010
01001010 82
838485
00101010
11101010
01101010
10101010
86
87
85
step data
Notes
Display of outdoor subcool
(SC) data and detection data
from high-pressure sensor and
each thermistor
678
45
3
subcool
Display of target
Display of indoor SC/SH data
Display of discharge superheat data
Display of all control target data
Display of actual frequency at time of abnormality delay
indoor LEV at time of abnormality
Display of fan step number at time of abnormality delay
delay
Display of openness (pulses) outdoor
SLEV and
Display on the LD1 (display data)
2
1
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
Display mode
TH22 (No.3 indoor unit)
TH22 (No.4 indoor unit)
12345678
00011010
SW1 setting
No.
10011010
8889909192939495969798
TH22 (No.5 indoor unit)
TH21 (No.1 indoor unit)
TH21 (No.2 indoor unit)
TH21 (No.3 indoor unit)
TH21 (No.4 indoor unit)
TH21 (No.5 indoor unit)
01011010
11011010
00111010
10111010
01111010
11111010
0~4
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
during heating: subcool (SC)/during cooling: superheat (SH)
Indoor SC/SH (No.1 indoor unit)
Indoor SC/SH (No.2 indoor unit)
Indoor SC/SH (No.3 indoor unit)
Outdoor SC (cooling)
Target subcool step
00000110
10000110
01000110
Indoor SC/SH (No.4 indoor unit)
11000110
00100110
10100110
99
100
101
-99.9~999.9
Pdm(0.0~22.0)
ETm(-1.0~8.0)
SCm(0.0~10.0)
SCm/SHm(0.0~14.0)
Indoor SC/SH (No.5 indoor unit)
Discharge superheat
Target Pd display (heating)
Target ET display (cooling)
Target outdoor SC (cooling)
Target indoor SC/SH (No.1 unit)
Target indoor SC/SH (No.2 unit)
Target indoor SC/SH (No.3 unit)
Target indoor SC/SH (No.4 unit)
01100110
11100110
10010110
01010110
11010110
00110110
10110110
01110110
11110110
111
102
103
105
106
107
108
109
110
0~FF(16 progressive)
0~20
Target indoor SC/SH (No.5 unit)
Actual frequency of abnormality delay
Fan step number at time of abnormality delay
00001110
00000001
10000001
112
128
129
0~2000
Valve position at abnormality delay (SLEV:outdoor unit)
Valve position at abnormality delay (LEV:No.1 Indoor unit)
Valve position at abnormality delay (LEV:No.2 Indoor unit)
Valve position at abnormality delay (LEV:No.3 Indoor unit)
01000001
11000001
00100001
10100001
130
131
132
133
Valve position at abnormality delay (LEV:No.4 Indoor unit)
Valve position at abnormality delay (LEV:No.5 Indoor unit)
01100001
11100001
134
135
86
Display of data from high-pressure sensor,
all thermistors, and SC/SH at abnormality
delay
78
Display on the LD1 (display data)
2345 6
1
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
Display of actual frequency at time of abnormality
Display of fan step number at time of abnormality
Display of openness (pulses) of outdoor
SLEV and indoor LEV at time of abnormality
0~FF(16progressive)
0~20
0~2000
Display of data from high-pressure sensor
and all thermistors at time of abnormality
Display of data from SC/SH and all
thermistors at time of abnormality
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
Display mode Notes
High-pressure sensor data at time of abnormality delay
TH1 sensor data at abnormality delay
TH2 sensor data at abnormality delay
12345678
00010001
10010001
SW1 setting
No.
136
01010001
137
138
TH5 sensor data at abnormality delay
THHS sensor data at abnormality delay
Outdoor SC (cooling) at abnormality delay
SC/SH (No.1 indoor unit) at abnormality delay
SC/SH (No.2 indoor unit) at abnormality delay
SC/SH (No.3 indoor unit) at abnormality delay
SC/SH (No.4 indoor unit) at abnormality delay
SC/SH (No.5 indoor unit) at abnormality delay
Actual frequency at time of abnormality
Fan step number at time of abnormality
11110001
00110001
10110001
141
01110001
142
143
144
00001001
10001001
01001001
145
146
00000011
192
10000011
193
11010001
139
140
sensor data at time of abnormality
Openness of outdoor SLEV at time of abnormality
Openness of LEV at time of abnormality (No.1 unit)
Openness of LEV at time of abnormality (No.2 unit)
Openness of LEV at time of abnormality (No.3 unit)
Openness of LEV at time of abnormality (No.4 unit)
Openness of LEV at time of abnormality (No.5 unit)
High-pressure sensor data at abnormality delay
TH 1 sensor data at time of abnormality
TH 2
01000011
194
11000011
195
00100011
196
197
11100011
01100011
10100011
198
199
00010011 200
10010011
201
202
sensor data at time of abnormality
sensor data at time of abnormality
Outdoor SC (Cooling) at time of abnormality
TH 5
THHS
11010011
01010011
203
204
Indoor SC/SH (No. 1) at time of abnormality
01110011
00110011
10110011
205
206
87
Indoor SC/SH (No. 2) at time of abnormality
Indoor SC/SH (No. 3) at time of abnormality
Indoor SC/SH (No. 4) at time of abnormality
Indoor SC/SH (No. 5) at time of abnormality
11110011
00001011
10001011
01001011
207
208
209
210
Display of indoor unit capacity mode
78
Display of indoor unit operating mode
Heating
Heating
Cooling
Display of openness (pulses) of outdoor
SLEV and indoor LEV
OFF
thermo
ON
thermo
OFF
thermo
Display of indoor SC/SH data
Display of all control target data
Display of openness (pulses) of indoor LEV
at time of abnormality
Display of opeeness (pulses) of indoor LEV
at time of abnormality
Display on the LD1 (display data)
2345 6
1
0~255
Display mode Notes
Capacity code (No.6 indoor unit)
Capacity code (No.7 indoor unit)
Capacity code (No.8 indoor unit)
ON
thermo
Cooling
OFF Fan
Indoor unit mode (No.6 unit)
Indoor unit mode (No.7 unit)
0~2000
Indoor unit mode (No.8 unit)
Indoor LEV opening (No.6 unit)
Indoor LEV opening (No.7 unit)
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
Indoor LEV opening (No.8 unit)
TH23 (No.6 indoor unit)
TH23 (No.7 indoor unit)
TH23 (No.8 indoor unit)
TH22 (No.6 indoor unit)
TH22 (No.7 indoor unit)
TH22 (No.8 indoor unit)
TH21 (No.6 indoor unit)
TH21 (No.7 indoor unit)
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
during heating:supercooling (SC)/during cooling:overtheating (SH)
TH21 (No.8 indoor unit)
Indoor SC/SH (No.6 indoor unit)
Indoor SC/SH (No.7 indoor unit)
SCm/SHm (0.0~14.0)
Indoor SC/SH (No.8 indoor unit)
Target indoor SC/SH (No.6 unit)
Target indoor SC/SH (No.7 unit)
0~2000
Target indoor SC/SH (No.8 unit)
Valve position at abnormality delay (LEV:No.6 Indoor unit)
Valve position at abnormality delay (LEV:No.7 Indoor unit)
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
Valve position at abnormality delay (LEV:No.8 Indoor unit)
SC/SH (No.6 indoor unit) at abnormality delay
SC/SH (No.7 indoor unit) at abnormality delay
SC/SH (No.8 indoor unit) at abnormality delay
0~2000
Openness of LEV at time of abnormality (No.6 unit)
Openness of LEV at time of abnormality (No.7 unit)
-99.9 ~ 999.9 (short circuit/open: -99.9 or 999.9)
Openness of LEV at time of abnormality (No.8 unit)
Indoor SC/SH (No.6) at time of abnormality
Indoor SC/SH (No.7) at time of abnormality
Indoor SC/SH (No.8) at time of abnormality
11001011
00101011
12345678
SW1 setting
No.
211
212
10101011
213
01101011
214
11101011
215
00011011
216
10011011
217
01011011
218
11011011 219
00111011
220
10111011
221
01111011 222
11111011 223
00000111
224
10000111 225
01000111
226
11000111
227
00100111
228
88
10100111
229
01100111
230
11100111
231
00010111
232
10010111
233
01010111
234
11010111 235
00110111
236
10110111
237
01110111
238
11110111
239
00001111
240
10001111
241
01001111 242
11001111
243
00101111
244
10101111
245
01101111
246
9 ELECTRICAL WIRING
Outdoor unit
Indoor unit
Grounded
Grounded
Junction box
Circuit breaker
N
Power supply MODEL : PUMY-VM (single phase 220-230-240V, 50Hz) (single phase 220V, 60Hz) MODEL : PUMY-YM(A) (3phase 380-400-415V, 50Hz) (3phase 380V, 60Hz) : YM
1 only
Circuit breaker
Power supply single phase 50Hz 220-230-240V
single phase 60Hz 220V
This chapter provides an introduction to electrical wiring for the MULTI-S series, together with notes concerning power wiring, wiring for control (transmission wires and remote controller wires), and the frequency converter.
9-1. OVERVIEW OF POWER WIRING
(1) Please refer to your electric power company about the indoor wiring specifications for the power wire diameter
and capacity of protective devices (switches and leakage of breakers).
(2) Taking into consideration voltage drops caused by the length of the wires when operating devices installed
downstream, determine the specifications of wires able to handle the maximum current or voltage. In addition, protective devices must be able to protect against current leakage or excessive current.
(3) It is generally necessary to include leakage breakers when installing wiring for the Mr. SLIM MULTI-S series.
Protective switches (excessive current protection) along main or branch lines should typically consist of fuseless
breakers (ELB). (4) Please perform grounding. (5) It is suggested that you consult with your electric power company concerning restrictions on electrical specifications.
9-2. WIRE DIAMETER AND MAIN POWER SWITCH CAPACITY
9-2-1. Wiring diagram for main power supply
9-2-2. Power supply wire diameter and capacity
Model
PUMY-71VM
PUMY-71VM
PUMY-125VM
PUMY-125VM
PUMY-125VM2
PUMY-125YM
Outdoor unit
PUMY-125YM
PUMY -125YMA
Model
All Models
Indoor unit
1
Minimum wire cross section area(mm2)
5.5
14
2.5
Branch line
Branch line
Grounded
3.5
5.5
2.5
Grounded
[1.6
Main line
1
1
Minimum wire cross section area(mm)
Main line
[1.6
Interrupting current
30A
100A
25A
Interrupting current
15A
89
Breaker
Performance characteristic
30A,30mA for 0.1 sec. or less
100A,100mA for 0.1 sec. or less
25A,30mA for 0.1 sec. or less
Breaker
Performance characteristic
15A, 30mA for 0.1 sec. or less
9-3. DESIGN FOR CONTROL WIRING
L2
Outdoor unit
L3
L1
L4
1.25mm
2
shielded wire
R
R
Indoor unit
(Note 1)
(Note 2)
Grounded
Remote controller
Please note that the types and numbers of control wires needed by the Mr. SLIM MULTI-S series will depend on the remote controllers and whether they are linked with the system.
9-3-1. Selection number of control wires
M-NET remote controller
Use
Remote controller indoor unit Wires connecting indoor units Wires connecting indoor units with outdoor units Wires connecting outdoor units
wires
Transmission
9-3-2. Control signal wires
Transmission wires
• Types of transmission wires: Design feeder control wires using the information in the following table.
• Diameter of wire size: 1.25E
Remote controller used in system control operations.
• Group operation involving different refrigerant systems.
• Linked operation with upper control system.
2 wires (non-polar)
System
Transmission wire length
Examples of suitable
environments
(determined according
to amount of noise)
Type of transmission wire
Suitable for single refrigerant system
Noise-free environment such as residence or free-standing store
VCTF, VCTFK, CVV, CVS, VVR, VVF, VCT
120m or less
120m or longer
Clinics, hospitals, communications facili­ties, or office high-rises typically contain­ing noise-producing equipment such as frequency modulation devices, electri­cal generators, high-frequency medical apparatus, and wireless communication apparatus, etc.
Shielded wire CVVS,CPEVS
Multiple refrigerant system
regardless of length
All places
If the transmission distance is too long or if there is a source of noise close to an air conditioning unit, the noise problem can be avoided by using shielded wire or moving the unit away from the source.
• The length of wire is 120m or longer.
• Air conditioning units used in hospitals, communications facilities, or office high-rises containing noise-producing equipment such as frequency modulation devices, electrical generators, high-frequency medical apparatus, and wireless communication apparatus.
9-3-3. Remote controller wiring
M-NET remote controller
Type
Wire cross section area
Length
Non-shielded wire may be used for 10m or less; shielded wire must be used if distance is greater than 10m (note 2)
0.5-0.75mm2or greater Make sure that the greatest transmission distance is less than 200m. (shielded wire cross section area at least 1.25mm
9-3-4. Permissible length of control wiring
• Maximum extension length of wiring
(L1+L2+L3+L4).....less than 500m
• Maximum wire length
(L1+L2+L4 or L1+L3 or L2+L3+L4).....less than 200m
• Remote controller wire
(R)....network controller wire is less than 10m
Note 1: Please make sure that the transmission wire is
grounded at the outdoor unit ground terminal.
Note 2: If the remote controller wire is greater than 10m,
the excess portion should use shielded wire at least 1.25mm total length of the farthest wire is less than 200m.
2
in size. Please make sure that the
90
2
)
9-4. SYSTEM SWITCH SETTING
Outdoor unit
Power supply 3 phase 4 wire. 50Hz 380-400-415V
Power supply Single phase. 50Hz 220-230-240V
Grounded
Group operation
Remote controller wire
Junction box
Indoor unit
circuit breaker
L1,L2,L3
N
15A circuit breaker
[1.6mm 2
[1.6mm 2
0.5~0.75mm
2
2
1.25mm
2
2
In order to identify the destinations of signals to the outdoor units, indoor units, and remote controller of the MULTI-S series, each microprocessor must be assigned an identification number (address). The addresses of outdoor units, indoor units, and remote controller must be set using their settings switches. Please consult the installation manual that comes with each unit for detailed information on setting procedures.
9-5. EXAMPLE EXTERNAL WIRING DIAGRAM FOR A BASIC SYSTEM (PUMY-125YM)
9-5-1. Example using a M-NET remote controller
9-6. METHOD FOR OBTAINING ELECTRICAL CHARACTERISTICS WHEN A CAPACITY
The electrical characteristics of connected indoor unit system for air conditioning systems, including the MULTI-S series, will depend on the arrangement of the indoor and outdoor units. First read the data on the selected indoor and outdoor units and then use the following formulas to calculate the electrical characteristics before applying for a capacity agreement with the local electric power company.
9-6-1. Obtaining the electrical characteristics of a MULTI-S series system
(1)Procedure for obtaining total power consumption
1 Please note that the power consumption of the outdoor unit will vary depends on the total capacity of the selected
(2)Method of obtaining total current
2 Please note that the
AGREEMENT IS TO BE SIGNED WITH AN ELECTRIC POWER COMPANY
Total power consumption of each indoor unit
1 power consumption of outdoor unit
Total power consumption of system
indoor units.
Total current through each indoor unit
2 current through outdoor unit
current through system
Total
current through the outdoor unit will vary depending on the total capacity of the selected indoor units.
Page numbers in this technical manual
See the technical manual of each indoor unit
Standard capacity table—p.12-27
See the technical manual of each indoor unit
Page numbers in this technical manual
See the technical manual of each indoor unit
Standard capacity table—p.13-27
See the technical manual of each indoor unit
Power consumption
1
2
1+2 <kW>
Subtotal
1
2
1+2 <A>
91
(3) Method of obtaining system power factor
Use the following formula and the total power and current obtained in parts 1 and 2 on the previous page to calculate the system power factor.
System power factor =
(Total system power consumption)
(Total system current x voltage)
o 100%
9-6-2. Applying to an electric power company for power and total current
Calculations should be performed separately for heating and cooling employing the same methods; use the largest resulting value in your application to the electric power company.
92
10 REFRIGERANT PIPING TASKS
Line-Branch Method
Connection Examples (Connecting to Four Indoor Units)
Liquid Line
Gas Line
Piping Diameter (mm)Model
PUMY-71
PUMY-125
{9.52 {15.88
Liquid Line (mm) Gas Line (mm)Downstream Unit Model Total
80 or less
80 or more
{15.88 {19.05
{9.52 {9.52
Liquid Line
Gas Line
Liquid Line
Gas Line
Liquid Line
Gas Line
Piping Diameter (mm)
Model number
40 or lower
100, 125
50 to 80
{6.35 {12.7 {9.52 {15.88 {9.52 {19.05
Outdoor Unit First Branch Indoor unit
A B C
A+B+C+a+b+c+d is 100 meters or less (125 Type), 80 meters or less (71 Type) A+B+C+d is 70 meters or less (125 Type), 50 meters (71 Type) B+C+d is 30meters or less 30 meters or less (If the outdoor unit is lower, 20 meters or less) 12 meters or less Use an optional branch piping kit (CMY-Y62-C-E).
Total Piping Length Farthest Piping Length Farthest Piping Length After First Branch High/Low Difference in Indoor/Outdoor Section High/Low Difference in Indoor/Indoor Section
Permissible
Length
Permissible High/
Low Difference
(L)
(R)
(H)
(h)
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Pipng
Additional refrigerant charge
Select the size from the table to the right.
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch (Out­door Unit Piping Diameter)
(1) Section From Oudoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d)
(3) Section From Branch to
Branch (B,C)
(3) Refrigerant Piping Diameter In Section
From Branch to Branch
(2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit (Indoor Unit Piping Diameter)
Each Section of Piping
• Refrigerant of 3kg equivalent to 50-m total extended piping length (model 125) or 2.4kg equivalent to 40-m (model 71) is already in­cluded when the outdoor unit is shipped. Thus, if the total extended piping length is 50m or less (model 125) or 40m or less (model 71), there is no need to charge with additional refrigerant.
• If the total extended piping length exceeds 50m (model 125) or 40m (model 71), calcu­late the required additional refrigerant charge using the procedure shown on the right.
• If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
<Additional Charge>
<Example> Outdoor model : 71 Indoor 1 : 25 A : {9.52 10m a : {6.35 5m
2 : 20 B : {9.52 10m b : {6.35 10m 3 : 25 C : {9.52 10m c : {6.35 10m 4 : 20 d : {6.35 10m
The total length of each liquid line is as follows
{9.52 : A + B + C = 10 + 10 +10 = 30m {6.35 : a + b + c + d = 5 + 10 + 10 + 10 = 35m
Therefore, <Calculation example> Additional refrigerant charge = 30 0.06 + 35 0.024 – 2.4 = 0.3kg (rounded up)
Additional refrigerant charge
(kg)
Liquid pipe size Total length of {9.52 0.06
(m) 0.06 (kg/m)
=
Liquid pipe size Total length of {6.35 0.024
(m) 0.024 (kg/m)
+
Refrigerant amount for outdoor unit
71: 2.4kg
125: 3.0kg
At the conditions below:
Liquid Line
Gas Line
{9.52 {19.05
B
A
a
b
C
C
C
c
C
d
C
L
1
23
4
H
h
R
A
B
10-1. REFRIGERANT PIPING SYSTEM
93
Header-Branch Method
Connection Examples (Connecting to Four Indoor Units)
A
A
L
B
H
R
Permissible
Length
Permissible High/
Low Difference
Farthest Piping Length Farthest Piping Length After First Branch High/Low Difference in Indoor/Outdoor Section High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Piping
Total Piping Length
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d)
Each Section of Piping
Select the size from the table to the right.
Additional refrigerant charge
• Refrigerant of 3kg equivalent to 50-m total extended piping length (model 125) or 2.4kg equivalent to 40-m(model 71) is already included when the outdoor unit is shipped. Thus, if the total extended piping length is 50m or less (model 125) or 40m or less (model71), there is no need to charge with additional refrigerant.
• If the total extended piping length exceeds 50m (model 125) or 40m (model 71),
calculate the required additional refrigerant
charge using the procedure shown on the right.
• If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
a
C
1
h
c
b
C
C
2
3
d
C
4
A+a+b+c+d is 100 meters or less (125 Type), 80 meters or less (71Type)
(L)
A+d is 70 meters or less (125 Type), 50 meters (71Type)
(R)
d is 30 meters or less
(H)
30 meters or less (If the outdoor unit is lower, 20 meters or less)
(h)
12 meters or less Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
•The CMY-Y68- cannot be connected with 100,125 type indoor units. Branch header (4 branches)
CMY-Y64-C
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch (Out­door Unit Piping Diameter)
Branch header (8 branches)
CMY-Y68 (2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit (Indoor Unit Piping Diameter)
Piping Diameter (mm)Model
PUMY-71
PUMY-125
Liquid Line
Gas Line
Liquid Line
Gas Line
{9.52 {15.88
{9.52 {19.05
40 or lower
50 to 80
100,125
<Additional Charge>
Additional refrigerant charge
(kg)
Liquid pipe size Total length of {9.52 0.06
=
(m) 0.06 (kg/m)
Liquid pipe size Total length of {6.35 0.024
+
(m) 0.024 (kg/m)
<Example> Outdoor model : 125 Indoor 1 : 50 A : {9.52 30m a : {9.52 15m
2 : 40 b : {6.35 10m 3 : 25 c : {6.35 10m
At the conditions below:
4 : 20 d : {6.35 20m
The total length of each liquid line is as follows
{9.52 : A + a = 30 + 15 = 45m {6.35 : b + c + d = 10 + 10 + 20 = 40m
Therefore, <Calculation example> Additional refrigerant charge = 45
0.06 + 40 0.024 – 3.0 = 0.7kg (rounded up)
Outdoor Unit
A
First Branch
B
Indoor unit
C
Piping Diameter (mm)Model number
Liquid Line
Gas Line
Liquid Line
Gas Line
Liquid Line
Gas Line
Refrigerant amount for outdoor unit
125: 3.0kg
{6.35 {12.7 {9.52 {15.88 {9.52 {19.05
71:2.4kg
94
Method of Combined Branching of Lines and Headers
Connection Examples (Connecting to Five Indoor Units)
A
Note:Pipe re-branching after the header branching
is not possible.
A
C
B
H
B
C
1
c
3
D D D
L
R
b
a
D
Note:The total of downstream unit models in the
table is the total of models as seen from point A in the figure above.
E
A
d e
4
2
G
5
Outdoor unit
A
First branching (branching
B
joint)
h
Branching joint
C
Indoor unit
D
Branching header
D
E
To downstream unit
F
Blind caps
G
F
Permissible
Length
Permissible High/
Low Difference
Total Piping Length Farthest Piping Length Farthest Piping Length After First Branch High/Low Difference in Indoor/Outdoor Section High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Pipng
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d,e)
(3) Section From Branch to
Each Section of Piping
Branch (B,C)
Select the size from the table to the right.
Additional refrigerant charge
• Refrigerant of 3kg equivalent to 50-m total extended piping length (model 125) or 2.4kg equivalent to 40-m (model 71) is already included when the outdoor unit is shipped. Thus, if the total extended piping length is 50m or less (model 125) or 40m or less (model 71), there is no need to charge with additional refrigerant.
• If the total extended piping length exceeds 50m (model 125) or 40m (model 71), calculate the required additional refrigerant charge using the procedure shown on the right.
• If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
A+B+C+a+b+c+d+e is 100 meters or less (125 Type), 80 meters or less (71 Type)
(L)
A+B+b is 70 meters or less (125 Type), 50 meters (71 Type)
(R)
B+b is 30 meters or less
(H)
30 meters or less (If the outdoor unit is lower, 20 meters or less)
(h)
12 meters or less Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Branch Joint
CMY-Y62-C-E
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch (Out­door Unit Piping Diameter)
Piping Diameter (mm)Model
PUMY-71
PUMY-125
Liquid Line
Gas Line
Liquid Line
Gas Line
(3) Refrigerant Piping Diameter In Section
Branch Header (4 branches)
CMY-Y64-C
(2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit (Indoor Unit Piping Diameter)
{9.52 {15.88
{9.52
40 or lower
50 to 80
{19.05
100,125
Branch Header (8 branches)
Piping Diameter (mm)Model number
Liquid Line
Gas Line
Liquid Line
Gas Line
Liquid Line
Gas Line
From Branch to Branch
Liquid Line (mm) Gas Line (mm)Downstream Unit Model Total
80 or less
80 or more
{9.52 {9.52
{15.88 {19.05
<Additional Charge>
Additional refrigerant charge
(kg)
Liquid pipe size Total length of {9.52 0.06
=
(m) 0.06 (kg/m)
Liquid pipe size Total length of {6.35 0.024
+
(m) 0.024 (kg/m)
Refrigerant amount for outdoor unit
<Example> Outdoor model : 125 Indoor 1 : 50 A : {9.52 10m a : {9.52 5m
2 : 40 B : {9.52 20m b : {6.35 10m 3 : 32 C : {9.52 10m c : {6.35 5m
At the conditions
below: 4 : 20 d : {6.35 5m 5 : 20 e : {6.35 5m
The total length of each liquid line is as follows
{9.52 : A + B + C + a = 10 + 20 +10 + 5 = 45m {6.35 : b + c + d + e = 10 + 5 + 5 + 5 = 25m
Therefore, <Calculation example> Additional refrigerant charge = 45 0.06 + 25 0.024 – 3.0 = 0.3kg (rounded up)
CMY-Y68
125: 3.0kg
{6.35 {12.7 {9.52 {15.88 {9.52 {19.05
71:2.4kg
95
Multi-distribution piping on outdoor unit
Connection Examples (Connecting up to Five Indoor Units)
*If multi-distribution piping on outdoor unit is done, a maximum of 5 indoor units can be connected.
Total Piping Length
Permissible
Length
Permissible High/
Low Difference
Farthest Piping Length
High/Low Difference in Indoor/Outdoor Section High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
A
L
B
a
b
H
h
C
C
1
2
c
d
C
C
3
4
e
C
5
Cannot redistribute the piping.
a+b+c+d+e is 100 meters or less
(L)
e is 30 meters or less
(H)
30 meters or less (20 meters or less if the outdoor unit is below.)
(h)
12 meters or less Use multi-distribution piping on outdoor unit kit CMY-S65 ( 5 branches).
*Cannot be connected with 100,125 type indoor units.
Outdoor Unit
A
First Branch
B
Indoor unit
C
Select Each Section of Refrigerant Pipng
• Section the piping size for each section from the branch to the indoor unit (a,b,c,d,e) using the chart on the right.
Additional refrigerant charge
• Refrigerant of 3kg equivalent to 50-m total extended piping length (model 125) or 2.4kg
equivalent to 40-m (model 71) is already included when the outdoor unit is shipped. Thus, if the total extended piping length is 50m or less (model 125) or 40m or less (model 71), there is no need to charge with additional refrigerant.
• If the total extended piping length exceeds 50m (model 125) or 40m (model 71), calculate the required additional refrigerant charge using the procedure shown on the right.
• If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.
• Refrigerant Piping Diameter In Section From Branch to Indoor Unit (Indoor Unit Piping Diameter)
Model number
40 or lower
50 to 80
Piping Diameter (mm)
Liquid Line
Gas Line
Liquid Line
Gas Line
{6.35 {12.7 {9.52 {15.88
<Additional Charge>
Additional refrigerant charge
(kg)
Liquid pipe size Total length of {9.52 0.06
=
(m) 0.06 (kg/m)
Liquid pipe size Total length of {6.35 0.024
+
(m) 0.024 (kg/m)
<Example> Outdoor Unit: 125 Type Indoor 1 : 20 a : {6.35 10m
2 : 20 b : {6.35 20m 3 : 20 c : {6.35 20m 4 : 50 d : {9.52 20m 5 : 50 e : {9.52 30m
The total length of each liquid line is as follows
{9.52 : d + e = 20 + 30 = 50m {6.35 : a + b + c = 10 + 20 + 20 = 50m
Therefore, Additional refrigerant charge = 50
0.06 + 50 0.024 – 3.0 = 1.2kg (rounded up)
Refrigerant amount for outdoor unit
71:2.4kg
125: 3.0kg
96
10-2. PRECAUTIONS AGAINST REFRIGERANT LEAKAGE
Indoor unit
All refrigerant of this system will leak out to this room if there is leakage at this indoor unit.
Direction of refrigerant flow
Outdoor unit
10-2-1. Introduction
R-22 refrigerant of this air conditioner is non-toxic and non­flammable but leaking of large amount from an indoor unit into the room where the unit is installed may be deleterious. To prevent possible injury, the rooms should be large enough to keep the R-22 concentration specified by KHK : (a high pressure gas safety association) installation guide­lines S0010 as follows.
Maximum concentration Maximum refrigerant concentration of R-22 of a room is 0.3 kg/K accordance with the installation guidelines.
To facilitate calculation, the maximum concentration is expressed in units of O/K ( kg of R-22 per K)
Maximum concentration of R-22: 0.3O/K
(KHK installation guidelines S0010)
(2) Calculate room volumes (in K) and find the room
with the smallest volume
The part with represents the room with the smallest volume.
(a) Situation in which there are no partitions
(b) There are partitions, but there are openings that allow
the effective mixing of air.
Outdoor unit
Indoor unit
Outdoor unit
10-2-2. Confirming procedure of R-22 concentration
Follow 1) to 4) to confirm the R-22 concentration and take appropriate treatment, if necessary.
(1) Calculate total refrigerant amount by each refrig-
erant system based on one indoor unit. Total refrigerant amount is prechrged refrigerant amount of the indoor unit at ex-factory plus addi­tional charged amount at field installation.
Note: When single refrigeration system is consists of several independent refrigeration circuit, figure out the total refrig­erant amount by each independent refrigerant circuit.
Indoor unit
Opening
Wall
(c) If the smallest room has mechanical ventilation appara-
tus that is linked to a household gas detection and alarm device, the calculations should be performed for the second smallest room.
Ventilation apparatus
The smallest room
The second smallest room
(situation in which there are no door openings or in which there are open­ings above and blow doors that occupy at least 0.15% of the floor area)
Outdoor unit
Indoor unit
(3) Use the results of calculations (1)and (2) to calcu-
late the refrigerant concentration:
Total refrigerant in the refrigerating unit (O) The smallest room in which an indoor
unit has been installed (K)
[ maximum concentration(O/K)
Maximum concentration of R-22:0.3O/K
If the calculation results do not exceed the maximum concen­tration, perform the same calculations for the larger second and third room, etc., until it has been determined that nowhere will the maximum concentration be exceeded.
97
11 DISASSEMBLY
Service Ref. : PUMY-71VM
OPERATING PROCEDURE PHOTOS
1. Side and top panel disassembly procedures:
(1) Remove the side panel screws (3 pcs : 5o10 screws)
so that the hanging portion on the right side can be slid downward. Remove the side panel.
(2) Remove the top panel screws (5o10 screws :
3 pcs in front, 2 pcs in back) and take off the top panel. <If the rear screws on the top panel cannot be removed> Remove the front screws on the top panel (3 pcs : 5o10 screws) and lift up the front part of the top panel.
2. Fan and fan motor disassembly procedures:
(1) Remove the side panel (see 1) (2) Remove the top panel (see 1) (3) Remove the fan protection cover fixing screw
(15o15screw), and take off the fan guard by rotating it to the left.
(4) Remove the fan motor wires (MF1) (MF2) from
the power supply board. Remove the capacitor
wires. (5) Loosen the fan motor wire clips (3 pcs). (6) Remove the propeller-type blower. (7) Remove the fan motor screws (3 pcs : 5o16 screws)
and remove the fan motors.
1. Please pay attention to safety when assembling or disassembling heavy items.
2. The refrigerant system must be vacuum-pumped before performing piping maintenance.
Photo 1
Top panel installation screw
Fan protection cover
Fan protection cover fixing screw
Front panel
Photo 2
Fan
Top panel
Side panel installation screw
Side panel (for service)
Power supply board
Multi-controller board
3. Thermistor (TH6: outdoor air temperature sensor detection) disassembly procedures:
(1) Remove the side panel (see 1) (2) Remove the top panel (see 1) (3) Open the Thermistor clip and remove the Thrermistor
(outdoor air temperature detection).
(4) Remove the TH6 wire from the multi-functional
controller board in the electrical box and pull out of the electrical box.
Photo 3
98
Fan motor
Thermistor (air temperature detection)
Rear panel
Electrical box
Thermistor holder
Heat exchanger
OPERATING PROCEDURE PHOTOS
4. Electrical box disassembly procedures:
(1) Remove the side panel (see 1)
(2) Remove the top panel (see 1) (3) Disconnect the following wires from the
multi controller board.
• Thermistor (discharge temperature detection):TH1
• Thermistor (Low pressure saturated temperature detection):TH2
• Thermistor (pipe temperature, defection judging defrost):TH5
• Thermistor (outdoor temperature detection): TH6
• High-pressure sensor: 63HS (discharge pressure detection)
• Expansion valve: SLEV
(4) Disconnect the following wires from the power supply
board:
• Fan motor: MF1 and MF2
• Solenoid valve: SV1
• 4-way valve: 21S4
• Crankcase heater: CH Pull wires out of the electrical box after disconnecting them.
Photo 4
Power supply board
Electrical box
Rear panel
Multi-controller board
Electric box screw
(5) After removing the connector cover, remove the com-
presser wire and the inner thermostat terminal.
(6) Remove the electrical box screw (1 pc : 4 o 10). (7) Remove the valve bed screws from the right side of
the valve bed (2 pcs : 4 o 10).
(8) Remove the electrical box after slightly loosening the
rear panel. The electrical box is held by two claws on the left and one on the right.
5. Solenoid valve coil and 4-way valve coil disassembly procedures:
(1) Remove the side panel (see 1). (2) Remove the top panel (see 1). (3) Remove the electrical box (see 3). (4) Remove coil screws (Solenoid valve: 1 pc M4x6;
4-way valve: 1 pc M5x6), and remove the solenoid valve (SV1) and 4-way valve (21S4) wires from the power supply board. Note: The 4-way valve coil screw cannot be
removed by using a screwdriver; an adjustable or fixed wrench must be used.
Valve bed screws
Connector cover Valve bed
Photo 5
4-way valve
4-way valve coil
Solenoid valve coil
99
OPERATING PROCEDURE PHOTOS
6. Thermistor disassembly procedures:
(1) Remove the side panel (see 1) (2) Remove the top panel (see 1) (3) Remove the electric box (see 4) (4) Remove the Thermistor (discharge temperature
detection: TH1), (Low saturated pressure temperature sensor: TH2), (Pipe temperature, detection,
judging defrost: TH5).
To remove TH1, cut the band holding it and remove
the piping cover.
7. Compressor disassembly procedures:
(1) Remove the side panel (see 1) (2) Remove the top panel (see 1) (3) Remove the screws (2 pcs : 5o10, 1 pc : 4o10) and the
front panel. (4) Remove the electrical box (see 4 above). (5) Remove screws (3 pcs : 4o10, 4 pcs : 5o16) and the
valve bed (including the ball valve mounting portion). (6) Remove the separator screws. (1 pc : 4o10) (7) Remove the welded portions of the compressor
discharge and intake pipes. (8) Remove the side of the separator and the compressor
leg cover. (1 pc : 4o10 screw) (9) Remove the compressor leg mounting nuts (3 pcs).
(use an adjustable wrench)
(10)Move the separator to the left and remove the com-
presser.
Photo 6
Oil separator
Thermistor (TH2)
Thermistor (TH5)
Photo 7
Thermistor (TH1)
Band Piping cover
Compressor
Installation nuts
8. Accumulator disassembly procedures:
(1) Remove the compressor (see 7). (2) Remove the welded portions of the accumulator.
(take care not to strike the rear panel)
(3) Lift up the accumulator and pull it out from the rear.
Separator
Separator installation screw
Photo 8
Accumulator
100
Loading...