Mitsubishi PUHZ-W112VHA, PUHZ-W112VHA-BS Service Manual

SERVICE MANUAL
AIR TO WATER HEAT PUMP
No. OCH562
CONTENTS
1. SAFETY PRECAUTION
...................................
2
............................................
5
3. DATA
...............................................................
7
4. OUTLINES AND DIMENSIONS
.......................
9
5. WIRING DIAGRAM
........................................
10
6. WIRING SPECIFICATIONS
............................
11
7. REFRIGERANT SYSTEM DIAGRAM
...............
12
8. TROUBLESHOOTING
...................................
13
9. DISASSEMBLY PROCEDURE
......................
41
June 2014
Note:
This manual describes service
data of outdoor unit only.
R410A
[Model Name]
PUHZ-W112VHA
Salt proof model
PUHZ-W112VHA-BS
PARTS CATALOG (OCB562)
[Service Ref.]
PUHZ-W112VHA
PUHZ-W112VHA-BS
Outdoor unit
2
SAFETY PRECAUTION
1
1-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
Preparation before the repair service.
• Prepare the proper tools.
• Prepare the proper protectors.
• Provide adequate ventilation.
• After stopping the operation of the air conditioner, turn off the power-supply breaker.
• Discharge the condenser before the work involving the electric parts.
Precautions during the repair service.
• Do not perform the work involving the electric parts with wet hands.
• Do not pour water into the electric parts.
• Do not touch the refrigerant.
• Do not touch the hot or cold areas in the refrigerating cycle.
• When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to touch the live parts.
Cautions for units utilizing refrigerant R410A
1-2. CAUTIONS RELATED TO NEW REFRIGERANT
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Electronic refrigerant charging scale
Vacuum pump adaptor
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Use the specified refrigerant only.
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
OCH562
3
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in the unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Gravimeter
Unit
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.
Tool name
Specifications
1
Gauge manifold
· Only for R410A
· Use the existing fitting
specifications
. (UNF1/2)
· Use high-tension side pressure of 5.3 MPa·G or over.
2
Charge hose
· Only for R410A
· Use pressure performance of 5.09 MPa·G or over.
3
Electronic scale
4
Gas leak detector · Use the detector for R134a, R407C or R410A.
5
Adaptor for reverse flow check · Attach on vacuum pump.
6
Refrigerant charge base
7
Refrigerant cylinder
· Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8
Refrigerant recovery equipment
OCH562
4
Although "-BS" model has been designed to be resistant to salt damage, observe the following precautions to maintain the performance of the unit.
1. Avoid installing the unit in a location where it will be exposed directly to seawater or sea breeze.
2. If the cover panel may become covered with salt, be sure to install the unit in a location where the salt will be washed away by rainwater. (If a sunshade is installed, rainwater may not clean the panel.)
3. To ensure that water does not collect in the base of the outdoor unit, make sure that the base is level, not at angle. Water collecting in the base of the outdoor unit could cause rust.
4. If the unit is installed in a coastal area, clean the unit with water regularly to remove any salt build-up.
5. If the unit is damaged during installation or maintenance, be sure to repair it.
6. Be sure to check the condition of the unit regularly.
7. Be sure to install the unit in a location with good drainage.
1-4. PRECAUTIONS FOR SALT PROOF TYPE "-BS" MODEL
1-3. CAUTIONS FOR REFRIGERANT PIPING WORK
Tools for R410A (The following table shows whether conventional tools can be used or not.)
Gauge manifold Charge hose Gas leak detector
Refrigerant recovery equipment Refrigerant cylinder Safety charger
Charge valve
Vacuum pump
Bender Pipe cutter Welder and nitrogen gas cylinder Refrigerant charging scale Vacuum gauge or thermis­tor vacuum gauge and vacuum valve Charging cylinder
Air purge, refrigerant charge and operation check Gas leak check Refrigerant recovery Refrigerant charge Prevent compressor malfunction
when charging refrigerant by spraying liquid refrigerant
Prevent gas from blowing out when detaching charge hose
Vacuum drying and air purge
Bend the pipes Cut the pipes Weld the pipes Charge refrigerant Check the degree of vacuum. (Vacuum valve prevents back flow of oil and refri­gerant to thermistor vacuum gauge) Refrigerant charge
Tool exclusive for R410A Tool exclusive for R410A Tool for HFC refrigerant Tool exclusive for R410A Tool exclusive for R410A Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can be used if equipped with adap­ter for reverse flow check Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used
Tool exclusive for R410A
Tools and materials Use R410A tools Can R22 tools be used?
(Usable if equipped with adapter for rever­ se flow)
Can R407C tools be used?
(Usable if equipped with adapter for rever­ se flow)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) : Tools for other refrigerants can be used under certain conditions. : Tools for other refrigerants can be used.
OCH562
5
PUHZ-W112VHA(-BS)
noitidnoc gnitarepo lanimoN)ycneuqerF ,egatloV ,esahP( ylppus rewoP
Nominal water flow rate (Heating mode) L/min
Heating(A7/W35)
Heating
7 +)blub-yrD( erutarepmet ria edistuOWkyticapaC
(A7/W35)
6 +)blub-teW( erutarepmet ria edistuOPOC
53+/03+)teltuo/telni( erutarepmet retaWWktupni rewoP
Heating
WkyticapaC
Heating(A2/W35)
(A2/W35)
2 +)blub-yrD( erutarepmet ria edistuOPOC 1 +)blub-teW( erutarepmet ria edistuOWktupni rewoP
Pr
essure diffe
rence (water circuit)   )teltuo/telni( erutarepmet retaWaPk /+35
Heating pump input (based on EN14511) kW
Cooling(A35/W7)
53+)blub-yrD( erutarepmet ria edistuOnim/L)edom gnilooC( etar wolf retaw lanimoN
Cooling
42 +)blub-teW( erutarepmet ria edistuOWkyticapaC
(A35/W7)
7+/21+)teltuo/telni( erutarepmet retaW)POC( REE
Power input kW
Cooling(A35/W18)
Cooling
53+)blub-yrD( erutarepmet ria edistuOWkyticapaC
(A35/W18)
42 +)blub-teW( erutarepmet
ria edistuO)POC( REE
81+/32+)teltuo/telni( erutarepmet retaWWktupni rewoP
Pressur
e
difference (water circuit)  kPa
Cooling pump input (based on EN14511) kW
Note: "COP" and "Power input" in the above table are values that contains the "pump input (based on EN 14511) ".
regnahcxe taeh etalPsnoitacificeps tinu roodtuO
Model name
MITSUBISHI
Running current Heating
(A7/W35)
A
Cooling
(A35/W7)
A
Power factor Heating
(A7/W35)
%
Cooling
(A35/W7)
mm05:A %
mm664:B Atnerruc .xaM
Breaker size
A
MWA2-46LM
29.5
0.01
11.20
0.01
3.34
3.35
6.3
15.8 98 98
11.1
1φ, 230V, 50Hz
32
2.80
2.22
11.20
4.47
3.57
5
2.51
32.1
28.7
10.00
10.00
4.50
PUHZ-W112VHA(-BS)
W
Water OUT
Ref. IN
(Heating)
B
mm801:W gnisac retuO mm225:H hsinif lanretxE mm231:D lortnoc tnaregirfeR
setalp 64rosserpmoC Model Motor output kW Start type
erutarepmet retaw teltuo mumixaMsecived noitcetorP
Oil (Model) L
Wretaeh esacknarC
Heat exchanger Air
Water
.oN×)evird(naFnaF
Fan motor output
kW
Air flow
m
3
/min
(CFM) Defrost method Noise level (SPL) Heating dB
Cooling dB
Dimensions Width mm (in)
Depth mm (in) Height mm (in)
)bl( gkthgieW
Refrigerant
Quantity kg (lb)
Guaranteed operating Heating
range (Outdoor) Cooling
Outl
et water temp. Heat
ing
(Max in heating, Min in cooling)
Cooling
Return water Heating
R410A
(3,530)
Reverse cycle
*1
Propeller fan × 2
0.074 x 2
133
1020 (40-3/16)
330 +30
*4
(13+1-3/16)
53
*2
1350 (53-1/8)
Galvanized plate
53
*2 *3
-
2.5
4.0 (8.8)
-20
*5
+35
-5
*6
+46
+5
*7
+59
+60
+5
ANB33FNMMT
100
Plate fin coil
Plate heat exchanger
Comp.surface thermo
900 (FV50S)
Inverter
HP switch/LP switch
Discharge thermo
Hermetic scroll
Linear expansion valve
Munsell 3Y 7.8/1.1
H
D
Water IN
Ref. OUT (Heating)
Thermistor
(TH32)
A
*1 Hot gas with four-way valve *2 at distance of 1m from outdoor unit *3 A weighted sound power level in accordance
with ISO9614-1 for EN14511 testing is
69 dBA.
*4 grill *5 Lower limit of use is -5for EN14511 testing
purposes.
*6 With the optional air outlet guide, min. operation
temperature will be -15.
*
temperature range Cooling
1.23~4.41nim/Legnar etar wolf retaW
+8 +28
7 Lowest entering temperature is 12
for EN14511
testing purposes.
40
45
50
55
60
65
-20 -15 -10 -5 0 5 10
Maximum outlet water temperature []
SPECIFICATIONS
2
2-1. SPECIFICATIONS
OCH562
6
2-2. AVAILABLE RANGE (WATER FLOW RATE, RETURN WATER TEMP.)
Note: If using the unit out of the available range, the parts of unit might be damaged.
<Heating>
14.0 19.0 24.0 29.0 34.0 39.0
Table 3
Water flow rate [L/min]
5.0
7.0
9.0
11.0
13.0
15.0
17.0
19.0
21.0
23.0
25.0
Return water temp [:]
<Applicable Models>
• PUHZ-W112VHA(-BS)
Available range
<Cooling>
14.0 19.0 24.0
29.0
34.0 39.0
Table 6
Water flow rate [L/min]
5.0
7.0
9.0
11.0
13.0
15.0
Return water temp [:]
<Applicable Models>
• PUHZ-W112VHA(-BS)
17.0
Available range
OCH562
7
DATA
3
1.5m
1m
MICROPHONE
UNIT
GROUND
3-1. NOISE CRITERION CURVES
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
90
80
70
60
50
40
30
20
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
BAND CENTER FREQUENCIES, Hz
COOLING
MODE
HEATING
53
SPL(dB)
53
LINE
PUHZ-W112VHA PUHZ-W112VHA-BS
OCH562
8
3-2. STANDARD OPERATION DATA
Mode
Cooling (A35/W7) Heating (A7/W35)
Total
Capacity W 10,000 11,200
Input kW 3.57 2.51
Electrical circuit
Outdoor unit
PUHZ-W112VHA
Phase, Hz 1, 50
Voltage V 230
Current A 15.8 11.1
Refrigerant circuit
Discharge pressure MPa 2.63 2.08
Suction pressure MPa 0.83 0.67
Discharge temperature ºC 69 60
Condensing temperature
ºC 45 36
Suction temperature ºC 9 6
Water
conditions
Flow volume L/min 28.7 32.1
Outlet water temperature
ºC 7 35
Outdoor
conditions
Intake air temperature
D.B. ºC 35 7
W.B. ºC 24 6
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is: 1 (MPa) = 10.2 (kgf/cm
2
)
OCH562
9
PUHZ-W112VHA PUHZ-W112VHA-BS
Rear Air Intake
2-12×36 oval holes
(Foundation Bolt M10)
2-U Shaped notched holes
(Foundfation Bolt M10)
Installation Feet
Side Air Intake
Air Discharge
30 330
210 600 210
28
53
370 19
417
Handle for moving
Service panel
Terminal connections
Left···Power supply wiring
Right···Controller wiring
Earth terminal
Handle for moving
Handle for moving
1020
322
1350
1079
371
23
635
Power supply
wiring hole
(2-
{27Knock Out)
Front cover
see Detail
Air Intake
4074
34
Handle for moving
Rear Air Intake
Handle for moving
Water OUT
Water IN
59
Handle for moving
Side Air Intake
Detail
Scale 1:6
ISO 228-1
G1 B
46674
24
Drain hole
(5-
{33)
21981
30 256
133 133 133
FOUNDATION
<Foundation bolt height>
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
30
Service space
Dimensions of space needed
for service access are
shown in the below diagram.
Over 300
500
500
Over 10
FREE
Over 300mm
Over 10mm
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
Over 10mm
1 FREE SPACE (Around the unit)
2 SERVICE SPACE
3 FOUNDATION BOLTS
Less than
Over
Over
Over 500mm
Unit: mm
OUTLINES AND DIMENSIONS
4
OCH562
10
PUHZ-W112VHA PUHZ-W112VHA-BS
1 2 3 4 5 6 7 8
OFF
ON
112V
MODEL
SW6
*
1 MODEL SELECT
*
2. SW5 -1 to 5 : Function Switch
SW5-6 *2
OFF
ON
1 2 3 4 5 6
The black square ( )indicates a switch position.
TB1 MC MF1, MF2 21S4 63H
TH3 TH4
TH7
LEV-A, LEV-B DCL
Terminal Block <Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve)
High Pressure Switch 63L Low Pressure Switch 63HS
High Pressure Sensor
Thermistor <Liquid
>
Thermistor <Discharge
>
TH6 Thermistor <Plate HEX Liquid
>
Thermistor <Ambient
>
TH33 Thermistor <Suction
>
TH32 Thermistor
<
Inlet Water
>
Linear Expansion Valve
Reactor
CB Main Smoothing Capacitor CY1, CY2 Capacitor
Power Module
Controller Circuit Board
Connector
<
Emergency Operation
>
Connector <Connection
for Option
>
Switch <Manual Defrost, Defect History, Record Reset, Function Switch
>
Switch <Function Switch
>
Switch <Function Switch, Model Select
>
SW1
Connector <Connection for Option
>
Connector <Connection for Option
>
SS
Connector <Connection for Option
>
CN51
CNDM
SW2
SW6
Switch <Function Switch
>
SW8
Switch <Function Switch
>
SW7
SV1
LED3
LED <Operation/Inspection Indicators
>
C. B.
NI
SYMBOL NAME SYMBOL NAME
Connection Terminal <N-Phase
>
Connection Terminal <Reactor
>
Connection Terminal <Ground
>
DCL1, DCL2 IGBT EI, E2, E3, E4
Power Circuit Board
Connection Terminal
<
U/V/W-Phase
>
P. B.
LI
Connection Terminal <L-Phase
>
U, V, W
Switch <Model Select
>
SW5
CN31
Relay
Fuse
<
T6.3AL250V
>
F1, F2, F3, F4 X51, X52, X54
TH8 Thermistor(internal)
<
Heat Sink
>
Thermistor <Comp. Surface
>
TH34
Switch
<
Function Switch
>
SW9
MS 3
~
MF1
1
3
1
7
3
4
1
1 1 2 1
1 7
2
CNF1
(WHT)
TRANS
MS 3
~
MF2
1
7
CNF2
(WHT)
CNDC
(PNK)
TH7/6
(
RED
)
TH3
(WHT)
TH4
(WHT)
TH7
t° t° t° t°
TH6 TH3 TH4
1 2
TH32
(
BLK
)
TH32
1 3
TH33
(
YLW
)
TH33
63HS
63HS
(WHT)
3
1
CNS
(WHT)
63H
(
YLW
)
CN52C
(RED)
3
1
3
1
63H
63L
(
RED
)
3
1
63L
C. B.
IGBT
LED3
2
2
3
7
CN2
(WHT)
F3
1 2
1 31 3
CNAC
(WHT)
CN4
(WHT)
1
2
3
4
F4
F2
F1
21S4
(GRN)
X52
X54
1 3
SS
(WHT)
SV1
(
GRY
)
X51
21S4
1
5
CN51
(WHT)
1
3
CNDM
(WHT)
DCL2
N2
P2
MS 3~
U
U
V
V
W
W
CN2
(WHT)
CN4
(WHT)
1
7
1
2
2
CNDC
(
PNK
)
BLK
BLK
WHT
WHT
CY1 CY2
LINI
EI
E4
E2
E3
POWER SUPPLY ~/N 230V 50Hz
Interface unit / Flow temp. controller
TB1
L N S1 S2 S3
MC
3
1
3
1
2
RED
CNAC1
(WHT)
CNAC2
(RED)
1
3
1
3
CN52C
(RED)
52C
52C
BLU
YLW
GRN/YLW
ORN
BRN
RED
WHT
WHT
RED
RED
BLK
BLK
BLK
BLK
DCL1
DCL
CB
TH8
P. B.
SW9SW2
M M
51 1
LEV-A (WHT)
LEV-B
(RED)
LEV-BLEV-A
5
TH34
(RED)
TH34
12
1 3
1
5
CNVMNT
(WHT)
CNMNT
(WHT)
*
1
SW5SW8
SW7
SW6SW1
CN31
*
1
5 WIRING DIAGRAM
OCH562
11
WIRING SPECIFICATIONS6
FIELD ELECTRICAL WIRING (power wiring specifications)
Caution: Be sure to install N-line. Without N-line, it could cause damage to the unit.
Notes: 1. Wiring size must comply with the applicable local and national codes.
2.
Power supply cables and the cables between Controller and Outdoor unit shall not be lighter than polychloroprene sheathed
exible cables. (Design 60245 IEC 57
)
3. Be sure to connect the cables between Controller and Outdoor unit directly to the units (no intermediate connections are al­lowed).
Intermediate connections may result in communication errors. If water enters at the intermediate connection point, it may
cause insufcient insulation to ground or a poor electrical contact .
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.)
4. Install an earth longer than other cables.
ledom tinu roodtuO 112V
Outdoor unit power supply
~/N (single), 50 Hz, 230 V
32A1*yticapac rekaerB tiucriC tinu roodtuO
Wiring
Wire No. ×
size (mm²)
6 .niM × 3htrae ,ylppus rewop tinu roodtuO
Interface unit/Flow temp. controller-Outdoor unit *2 3 × 1.5 (polar)
Interface unit/Flow temp. controller-Outdoor unit earth *2 1 × Min. 1.5
Remote controller-Interface unit/Flow temp. controller 2 × 0.3 (Non-polar)
Circuit rating
Outdoor unit L-N (single) Outdoor unit L1-N, L2-N, L3-N (3phase)
*3 AC 230 V
Interface unit/Flow temp. controller-Outdoor unit S1-S2 *3 AC 230 V
Interface unit/Flow temp. controller-Outdoor unit S2-S3 *3 DC 24 V
Remote controller-Interface unit/Flow temp. controller *3 DC 12 V
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
*2. Max. 80 m *3.The figures are NOT always against the ground. S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT
electrically insulated by the transformer or other device.
Make sure that the current leakage breaker is one compatible with higher harmonics. Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter. The use of an inadequate breaker can cause the incorrect operation of inverter.
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between Interface unit/ Flow temp. controller and outdoor unit, please use 3-pole type.
S1
S2
S3
S1
S2
S3
A-Control
Outdoor Unit
3 poles isolator
Power supply
Isolator
Interface unit/ Flow temp. controller
OCH562
12
REFRIGERANT SYSTEM DIAGRAM7
Distributor
TH7
Strainer(#100)
Strainer(#100)
Receiver
Power
LEV-B
TH6
TH32
Plate HEX
Water IN
Water OUT
Strainer (#100)
TH3
STOP VALVE
CHECK/V
CHECK/V
H/P SW
L/P SW
TH4TH33
TH34
TH8 P/B
LEV-A
COMP
REV/V
P-Sensor
Strainer (#100)
Strainer (#100)
MUFFLER
Refrigerant flow in heating
Refrigerant flow in cooling
COMP
H/P SW
L/P SW
Plate HEX
REV/V
STOP VALVE
CHECK/V
P-Sensor
P/B
LEV-A
LEV-B
TH33
TH32
TH3
TH4
TH6
TH7
TH8
TH34
Power Receiver
DC inverter scroll compressor (Mitsubishi Electric Corporation)
For protection (OFF:4.15MPa)
For protection (OFF:-0.03MPa)
MWA2-46LM (MITSUBISHI)
Change the refrigerant circuit (Heating / Cooling) and for Defrosting
For refrigerant charge
High pressure / Low pressure / For production test use
For calculation of the condensing temperature from high pressure
Inverter power board
Heating:Secondary LEV Cool
ing:Primary LEV
Heating:Primary LEV Cooling:Second
ary LEV
For LEV control
For freeze protection and for compressor frequency control
Heating:Evaporating temperature Cooling:Sub cool liquid temperature
For LEV control and for compressor protection
Heating:Sub cool liquid temperature Cooling:Evaporating temperature
For fan control and for compressor frequency control
For power board protection
For compressor protection
For accumulat
ion of refrigerant
Compressor
Hi
gh pressure switch (63H)
Low pressure switch (63L)
Plate Heat Exchanger
Reversing (4-way) valve (21S4)
Stop valve
Check valve
Pressure sensor (63HS)
Power board
Linear expansion valve -A
Linear expansion valve -B
Suction temperature thermistor
Inlet water temperature thermistor
Liquid temperature thermistor
Discharge temperature thermistor
Plate HEX liquid temperature thermistor
Ambient temperature thermistor
Heatsink temperature thermistor
Comp. surface temperature thermistor
Power Rece
iver
Symbol Part name
Detail
PUHZ-W112VHA PUHZ-W112VHA-BS
OCH562
13
TROUBLESHOOTING8
<Check code display by self-diagnosis and actions to be taken for service (summary)>
Present and past check codes are logged and displayed on the control board of outdoor unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
8-1. TROUBLESHOOTING
8-2. CHECK POINT UNDER TEST RUN
Before test run
After installation of outdoor units, piping work and electric wiring work, re-check that there is no water leakage, loosened
connections and incorrect polarity.
Measure impedance between the ground and the power supply terminal block (L, N) on the outdoor unit by 500 V Megger
and check that it is 1.0 M
or over.
Turn on power supply 12 hours before test run in order to protect compressor.
Make sure to read operation manual before test run. (Especially items to secure safety.)
Unit conditions at service Check code Actions to be taken for service (summary)
The trouble is reoccurring.
Displayed
Judge what is wrong and take a corrective action according to “8-3. SELF-DIAGNOSIS ACTION TABLE”.
Not displayed
Conduct troubleshooting and ascertain the cause of the trouble.
The trouble is not reoccurring.
Logged
1
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise, etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, matters related to wiring, etc.
2
Reset check code logs and restart the unit after nishing
service.
1
There is no abnormality in electrical component,
controller board, etc.
Not logged
1
Re-check the abnormal symptom.
2
Conduct troubleshooting and ascertain the cause of the
trouble.
3
Continue to operate unit for the time being if the cause
is not ascertained.
4
There is no abnormality concerning of parts such as
electrical component, controller board, etc.
OCH562
14
8-3. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
Check code
Abnormal point and detection method
Case
Judgment and action
None
F3
63L connector open
Abnormal if 63L connector circuit is open for 3 minutes continuously from being switched on. 63L: Low-pressure switch
1 Disconnection or contact failure
of 63L connector on outdoor controller circuit board
2 Disconnection or contact failure
of 63L
3 63L is working due to refriger-
ant leakage or defective parts.
4 Defective outdoor controller
circuit board
1 Check connection of 63L connector on
outdoor controller circuit board.
Refer to "8-6. TEST POINT DIAGRAM".
2 Check the 63L side of connecting wire.
3 Check refrigerant pressure.
Charge additional refrigerant. Check continuity of 63L. Replace low pressure switch if it is defective.
4 Replace outdoor controller circuit board.
1
No voltage is supplied to terminal block (TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or
disconnection of power supply terminal
c) Open phase (L or N phase)
2 Electric power is not charged
to power supply terminal of outdoor power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board Disconnection of connector LI, NI
3 Electric power is not supplied
to outdoor controller circuit board.
a) Disconnection of connector
(CNDC)
4 Disconnection of reactor (DCL)
5 Defective outdoor power circuit
board
6 Defective outdoor controller
circuit board
1 Check following items.
a) Power supply breaker
b) Connection of power supply terminal
block. (TB1)
c) Connection of power supply terminal
block. (TB1)
2 Check following items.
a) Connection of power supply terminal block.
(TB1)
b) Connection of terminal on outdoor power
circuit board.
Check connection of the connector LI or NI. Refer to "8-6. TEST POINT DIAGRAM".
3 Check connection of the connector CNDC on
the outdoor controller circuit board. Check connection of the connector CNDC on the outdoor power circuit board.
Refer to "8-6.
TEST POINT DIAGRAM".
4 Check connection of reactor. (DCL) Check connection of "DCL1" and "DCL2" on
the outdoor power circuit board.
5 Replace outdoor power circuit board.
6 Replace outdoor controller circuit board
(When items above are checked but the units can not be repaired.)
F9
2 connector open
Abnormal if both 63H and 63L connector circuits are open for 3 minutes continuously from being switched on.
63H: High-pressure switch 63L: Low-pressure switch
1 Disconnection or contact failure
of connector (63H,63L) on outdoor controller circuit board.
2 Disconnection or contact failure
of 63H, 63L
3 63H and 63L are working due
to defective parts.
4 Defective outdoor controller
board.
1 Check connection of connector (63H,63L) on
outdoor controller circuit board.
Refer to "8-6. TEST POINT DIAGRAM". 2 Check the 63H and 63L side of connecting
wire.
3 Check continuity of 63H and 63L. Replace the pressure switch if it is defective. 4 Replace outdoor controller circuit board.
F5
63H connector open
Abnormal if 63H connector circuit is open for 3 minutes continuously from being switched on. 63H: High-pressure switch
1 Disconnection or contact failure
of 63H connector on outdoor controller circuit board
2 Disconnection or contact failure
of 63H
3 63H is working due to defective
parts.
4 Defective outdoor controller
circuit board
1 Check connection of 63H connector on
outdoor controller circuit board.
Refer to "8-6. TEST POINT DIAGRAM".
2 Check the 63H side of connecting wire.
3 Check for continuity of 63H.
Replace high pressure switch if it is defective. 4 Replace outdoor controller circuit board.
OCH562
15
Check code
Abnormal point and detection method
Judgment and action
Case
Eb
Miswiring of Interface unit/Flow temp. controller-outdoor unit connecting wire (converse wiring or disconnection)
Outdoor controller circuit board can automatically set the unit number of Interface unit/Flow temp. controller.
Abnormal if the Interface unit/Flow temp. controller number cannot be set within 4 minutes after power on because of miswiring (converse wiring or disconnection) of Interface unit/Flow temp. controller-outdoor unit connecting wire.
EC
Start-up time over
The unit cannot finish start-up process within 4 minutes after power on.
Contact failure of Interface unit
/Flow temp. controller-outdoor
unit connecting wire
Diameter or length of Interface
unit/Flow temp. controller­outdoor unit connecting wire is out of specified capacity.
Noise has entered into power
supply or Interface unit/Flow temp. controller-outdoor unit connecting wire.
Contact failure or miswiring
of Interface unit/Flow temp. controller-outdoor unit connecting wire
Diameter or length of Interface
unit/Flow temp. controller­outdoor unit connecting wire is out of specified capacity.
Defective transmitting receiving
circuit of outdoor controller circuit board
Defective transmitting receiving
circuit of Interface/Flow temp. controller board
Noise has entered into power
supply or Interface unit/Flow temp. controller-outdoor unit connecting wire.
Miswiring of Interface unit/Flow temp. controller-outdoor unit connecting wire
1. Outdoor controller circuit board can automatically check the number of connected Interface unit/Flow temp. con-
troller. Abnormal if the number cannot be checked automatically due to miswiring of Interface unit/Flow temp. controller­outdoor unit connecting wire and etc. after power is turned on for 4 minutes.
2. Abnormal if outdoor controller circuit board recognizes excessive number of Interface unit/Flow temp. controller.
Check disconnection or looseness or polarity
of Interface unit/Flow temp. controller-outdoor unit connecting wire of Interface unit/Flow temp. controller and outdoor units.
Check diameter and length of Interface unit/
Flow temp. controller-outdoor unit connecting
wire. Total wiring length: 80 m (Including wiring connecting each Interface
unit/Flow temp. controller unit and between
Interface unit/Flow temp. controller and out-
door unit) Also check if the connection order of flat
cable is S1, S2, S3.
Check the number of Interface unit/Flow
temp. controller that is connected to 1 out-
door unit. (If EA is detected.)
~ Turn the power off once, and on again to
check. Replace outdoor controller circuit board or Interface/Flow temp. controller board if abnormality occurs again.
Check transmission path, and remove the
cause.
Note:
The descriptions above, - , are for EA, Eb
and EC.
Contact failure or miswiring
of Interface unit/Flow temp. controller-outdoor unit connecting wire
Diameter or length of Interface
unit/Flow temp. controller­outdoor unit connecting wire is out of specified capacity.
Excessive number of Interface
unit/Flow temp. controller is connected to 1 outdoor unit.
(2 units or more)
Defective transmitting receiving
circuit of outdoor controller
circuit board
Defective transmitting receiving
circuit of Interface/Flow temp. controller board
Noise has entered into power
supply or Interface/Flow
temp. controller-outdoor unit connecting wire.
EA
OCH562
16
<Abnormalities detected while unit is operating>
Check code
Abnormal point and detection method
Judgment and action
High pressure (High-pressure switch 63H operated)
Abnormal if high-pressure switch 63H oper­ated ( * ) during compressor operation. *4.15 MPa
63H: High-pressure switch
1 Decreased water flow 2 Clogged filter of water pipe 3 Dirt of plate heat exchanger 4 Locked water pump 5 Malfunction of water pump 6 Clogged or broken pipe 7 Locked outdoor fan motor 8 Malfunction of outdoor fan
motor
9 Short cycle of outdoor unit
0 Dirt of outdoor heat exchanger 1 Decreased airflow caused by
defective inspection of outside temperature thermistor
(It detects lower temperature
than actual temperature.)
2 Disconnection or contact failure
of connector (63H) on outdoor controller board
3 Disconnection or contact failure
of 63H connection
4 Defective outdoor controller
board
5 Defective operation of linear
expansion valve
6 Malfunction of fan driving circuit
1~5 Check water circuit and repair the defect.
6 Check piping and repair the defect. 7~0 Check outdoor unit and repair the defect.
1 Check the detected temperature of outside
temperature thermistor on LED display.
(SW2: Refer to "
8-7.OUTDOOR UNIT
OPERATION MONITOR FUNCTION".)
2~4 Turn the power off and check F5 is
displayed when the power is turned on again.
When F5 is displayed, refer to “Judgment
and action” for F5.
5 Check linear expansion valve. Refer to "8-5.HOW TO CHECK THE
COMPONENTS".
6 Replace outdoor controller board.
Case
U2
High discharging temperature
Abnormal if discharge temperature thermistor (TH4) exceeds 125: or 110: continuously for 5 minutes. Abnormal if during defrosting discharge temperature thermistor (TH4) exceeds 110 : continuously for 30 minutes.
High comp. surface temperature
Abnormal if comp. surface temperature (TH34) exceeds 170:. In the case of high comp. surface tem­perature error, compressor does not restart unless the thermistor (TH34) becomes less than 95:.
1 Overheated compressor
operation caused by insufficient refrigerant
2 Defective thermistor 3 Defective outdoor controller
board
4 Defective operation of linear
expansion valve
5 In the case of the unit does not
restart :
Detection temp. of thermistor
(TH34) ] 95:
1 Check intake super heat. Check leakage of refrigerant. Charge additional refrigerant. 23 Turn the power off and check if U3 is
displayed when the power is turned ON
again. When U3 is displayed, refer to “Judgement and action” for U3.
4 Check linear expansion valve. Refer to "8-5.HOW TO CHECK THE
COMPONENTS".
U3
Open/short circuit of discharge temperature thermistor (TH4)/comp. surface thermistor (TH34)
Abnormal if open (3: or less) or short (217: or more) is detected during compressor operation. (Open (3: or less) detection is inoperative for 10 minutes of compressor starting process and for 10 minutes after or during defrosting.)
1 Disconnection or contact failure
of connector (TH4/TH34) on the outdoor controller circuit board.
2 Defective thermistor 3 Defective outdoor controller
circuit board
1 Check connection of connector (TH4/TH34) on the outdoor controller circuit board.
Check the lead wire for thermistor (TH4/TH34)
.
Refer to "8-6. TEST POINT DIAGRAM".
2 Check resistance value of thermistor (TH4/
TH34) or temperature on LED display. (Thermistor/TH4/TH34: Refer to "8-5.HOW TO CHECK THE COMPONENTS".)
(SW2: Refer to"8-7.OUTDOOR UNIT
OPERATION MONITOR FUNCTION".)
3 Replace outdoor controller board.
U1
OCH562
17
Check code
Abnormal point and detection method
Case
Judgment and action
U5
Temperature of heatsink
Abnormal if heatsink thermistor (TH8) detects 94°C.
1 The outdoor fan motor is
locked.
2 Failure of outdoor fan motor 3 Air flow path is clogged. 4 Ambient temperature is high. 5 Defective thermistor 6 Defective input circuit of
outdoor power circuit board
7 Failure of outdoor fan drive
circuit
12 Check outdoor fan.
3 Check air flow path for cooling. 4 Check if there is something which causes
temperature rise around outdoor unit.
(Upper limit of ambient temperature is 46:.) Turn off power, and on again to check if U5 is displayed within 30 minutes. If U4 is dis­played instead of U5, refer to check code U4.
5 Check resistance value of thermistor (TH8)
or temperature by microcomputer. (Thermistor/TH8: Refer to "8-5.HOW TO CHECK THE COMPONENTS".) (SW2: Refer to "8-7. OUTDOOR UNIT OPERATION MONITOR FUNCTION".)
6 Replace outdoor power circuit board. 7 Replace outdoor controller circuit board.
U4
Open/short of outdoor unit thermistors (TH3, TH32, TH33, TH6, TH7, and TH8)
Abnormal if open or short is detected during compressor operation. Open detection of thermistors TH3, TH32 and TH6 is not detected for 10 seconds to 10 minutes after compressor starting and 10 minutes after and during defrosting. Note: Check which unit has abnormality in its thermis­tor by switching the mode of SW2. (Refer to "8-7.OUTDOOR UNIT OPERATION MONITOR FUNCTION".)
Heatsink thermistor (TH8) is in
the power module.
1 Check connection of connector (TH3, TH32,
TH33, TH6/TH7) on the outdoor controller circuit board. Check connection of connector (CN3) on the outdoor power circuit board. Check the lead wire for thermistor (TH3, TH32, TH33, TH6, TH7, TH8). Refer to "8-6. TEST POINT DIAGRAM".
2
Check resistance value of thermistor (TH3, TH32, TH33, TH6, TH7, TH8) or check temperature on LED display. (Thermistor/TH3, TH32, TH33, TH6, TH7, TH8: Refer to "8-5.HOW TO CHECK THE COMPONENTS.")
(SW2: Refer to
"8-7.OUTDOOR UNIT
OPERATION MONITOR FUNCTION".
)
3 Replace outdoor controller circuit board.
1 Disconnection or contact failure
of connectors Outdoor controller circuit board: TH3, TH32, TH33, TH6/TH7
Outdoor power circuit board:
CN3
2 Defective thermistor 3 Defective outdoor controller
circuit board
(
)
U6
Power module
Check abnormality by driving power module in case overcurrent is detected. (UF or UP error condition)
1 Defective outdoor power circuit
board
2 Decrease of power supply voltage 3 Loosens, disconnection or
reverse of compressor wiring connection
4 Defective compressor
1 Replace outdoor power circuit board. 2 Check facility of power supply. 3 Correct the wiring (U
•V•
W phase) to compressor. Refer to "8-6. TEST POINT DIAGRAM (Outdoor power circuit board)".
4 Check compressor referring to "8-4.HOW TO
CHECK THE PARTS".
U7
Too low superheat due to low discharge temperature
Abnormal if discharge superheat is continuously detected -15: or less for 3 minutes even though linear expansion valve has minimum open pulse after compressor starts operating for 10 minutes.
1 Disconnection or loose
connection of discharge temperature thermistor (TH4)
2 Defective holder of discharge
temperature thermistor
3 Disconnection or loose connection
of linear expansion valve’s coil
4 Disconnection or loose
connection of linear expansion valve’s connector
5 Defective linear expansion valve
12 Check the installation conditions of dis-
charge temperature thermistor (TH4).
3 Check the coil of linear expansion valve. Refer to "8-5.HOW TO CHECK THE
COMPONENTS".
4 Check the connection or contact of LEV-A and
LEV-B on outdoor controller circuit board.
5 Check linear expansion valve. Refer to "8-4.HOW TO CHECK THE PARTS".
Thermistors
Open detection Short detection
Symbol Name
TH3 Thermistor <Liquid temperature> - 40°C or below 90°C or above TH32 Thermistor <Inlet water temperature> - 40°C or below 102°C or above TH33 Thermistor <Suction pipe temperature> - 40°C or below 90°C or above
TH6 Thermistor <Plate HEX liquid temperature> - 40°C or below 90°C or above
TH7 Thermistor <Ambient temperature> - 40°C or below 90°C or above
TH8 Internal thermistor - 35°C or below 170°C or above
U8
Outdoor fan motor
Abnormal if rotational frequency of the fan motor is not detected during DC fan motor operation. Fan motor rotational frequency is abnormal if;
• 100 rpm or below detected continuously
for 15 seconds at 20: or more outside air temperature
• 50 rpm or below or 1500 rpm or more
detected continuously for 1 minute.
1 Failure in the operation of the
DC fan motor
2 Failure in the outdoor circuit
controller board
1 Check or replace the DC fan motor.
2 Check the voltage of the outdoor circuit
controller board during operation.
3 Replace the outdoor circuit controller board.
(when the failure is still indicated even after performing the remedy 1 above.)
OCH562
18
U9
(4220)
Detailed
codes
To find out the details about U9 error, turn ON SW2-1, 2-2, 2-3, 2-4, 2-5 and 2-6 when U9 error occurs. To find out the detail history (latest) about U9 error, turn ON SW2-1, 2-2 and 2-6. Refer to "8-7.OUTDOOR UNIT OPERATION MONITOR FUNCTION".
01
Overvoltage error
• Increase in DC bus voltage to
400 V
1 Abnormal increase in power source
voltage
2 Disconnection of compressor wiring
3 Defective outdoor power circuit
board
4 Compressor has a ground fault.
1 Check the field facility for the power
supply.
2 Correct the wiring (U.V.W phase) to
compressor. Refer to "8-6. TEST POINT DIAGRAM (Outdoor power circuit board)".
3 Replace outdoor power circuit board. 4 Check compressor for electrical insula-
tion. Replace compressor.
02
Undervoltage error
• Instantaneous decrease in DC
bus voltage to 200 V
1 Decrease in power source voltage, instantaneous stop. 2 Disconnection or loose connection of CN52C on the outdoor power circuit board/controller circuit board 3 Defective converter drive circuit in outdoor power circuit board 4 Defective 52C drive circuit in outdoor power circuit board 5 Disconnection or loose connection of main smoothing capacitor CB 6 Disconnection or loose connection of CN2 on the outdoor power circuit board /controller circuit board 7 Power circuit failure on DC supply for 18V DC output on outdoor controller circuit board
1 Check the field facility for the power  supply.
2 Check CN52C wiring.
3 Replace outdoor power circuit board.
4 Replace outdoor power circuit board.
5 Check CB wiring.
6 Check CN2 wiring.
7 Replace outdoor controller circuit board.
04
Input current sensor error/ L1-phase open error
• Decrease in input current
through outdoor unit to 0.1A only if operation frequency is more than or equal to 40Hz or compressor current is more than or equal to 6A.
1 Defective input current detection circuit in outdoor power circuit board 2 Defective outdoor controller circuit board
1 Replace outdoor power circuit board.
2 Replace outdoor controller circuit board.
08
Abnormal power synchronous signal
• No input of power synchronous
signal to power circuit board
• Power synchronous signal
of 44 Hz or less, or 65 Hz or more is detected on power circuit board.
1 Distortion of power source voltage,
noise superimposition.
2 Disconnection or loose connection
of earth wiring
3 Disconnection or loose connection
of CN2 on the outdoor power circuit board /controller circuit board
4 Defective power synchronous signal
circuit in outdoor controller circuit board
5 Defective power synchronous signal
circuit in outdoor power circuit board
1 Check the field facility for the power
supply.
2 Check earth wiring.
3 Check CN2 wiring.
4 Replace outdoor controller circuit board.
5 Replace outdoor power circuit board.
Continue to the next page.
Check code
Abnormal point and detection method
Case
Judgment and action
10
PFC error (Overvoltage/ Undervoltage/Overcurrent)
• PFC detected any of the fol-
lowings
a) Increase of DC bus voltage
to 420V.
b) Decrease in PFC control
voltage to 12V DC or lower
c) Increase in input current to
50A peak (For models equipped with single-phase PFC only)
Not applicable for W112VHA models. Check for the switch settings for Model
Select on the outdoor controller circuit board.
20
PFC/IGBT error (Undervoltage)
When Compressor is running, DC bus voltage stays at 310V or lower for consecutive 10 seconds
1 Incorrect switch settings on the
outdoor controller circuit board for model select
2 Defective outdoor power circuit
board
3 Defective outdoor controller
circuit board
1 Correction of a model select
2 Replace outdoor power circuit board.
3 Replace outdoor controller circuit board.
OCH562
19
Check code
Abnormal point and detection method
Case
Judgment and action
UF
Compressor overcurrent interruption (When compressor locked)
Abnormal if overcurrent of DC bus or compressor is detected within 30 seconds after compressor starts operating.
1 Decrease of power supply
voltage
2 Looseness, disconnection or
converse of compressor wiring connection
3 Defective compressor 4 Defective outdoor power board 5 Decreased water flow 6 Clogged filter of water pipe 7 Clogged plate heat exchanger 8 Locked water pump 9 Malfunction of water pump
1 Check facility of power supply.
2 Correct the wiring (U
•V•
W phase) to
compressor.
Refer to "8-6. TEST POINT DIAGRAM
(Outdoor power circuit board)" .
3 Check compressor. Refer to
"8-4.HOW TO
CHECK THE PARTS".
4 Replace outdoor power circuit board. 5
~
9 Check water circuit and repair the defect.
Ud
Overheat protection
Abnormal if outdoor pipe thermistor (TH3) detects 70: or more or condensing temperature of pressure sensor (63HS) detects 70: or more during compressor operation.
1
Defective outdoor fan (fan motor) or short cycle of outdoor unit during cooling operation
2 Defective outdoor pipe
thermistor (TH3)
3 Defective outdoor controller
board
4 Defective pressure sensor
1 Check outdoor unit air passage.
23 Turn the power off and on again to check
the check code. If U4 is displayed, follow the U4 processing direction.
4 Check pressure by microcomputer. (Pressure sensor/ 63HS) (SW2: Refer to "
8-7.OUTDOOR UNIT
OPERATION MONITOR FUNCTION".)
UH
Current sensor error or input current error
· Abnormal if current sensor detects –1.0 A to 1.0 A during compressor operation.
(This error is ignored during test run.)
·
Abnormal if 38 A of input current is detected
or 34 A or more of input current is detected for 10 seconds continuously.
1 Disconnection of compressor
wiring
2 Defective circuit of current
sensor on outdoor power circuit board
3 Decrease of power supply
voltage
1 Correct the wiring (U
•V•
W phase) to compres­sor. Refer to "8-6. TEST POINT DIAGRAM (Outdoor power circuit board)".
2 Replace outdoor power circuit board. 3 Check the facility of power supply.
UP
Compressor overcurrent interruption
Abnormal if overcurrent DC bus or compressor is detected after compressor starts operating for 30 seconds.
1
Decrease of power supply voltage
2 Looseness, disconnection or
converse of compressor wiring connection
3 Defective fan of outdoor units 4 Short cycle of indoor/outdoor
units
5 Defective input circuit of out-
door controller board
6 Defective compressor 7 Decreased water flow 8 Clogged filter of water pipe 9 Clogged plate heat exchanger
0 Locked water pump 1 Malfunction of water pump
1 Check facility of power supply. 2 Correct the wiring (U
•V•
W phase) to compressor. Refer to "8-6. TEST POINT DIAGRAM (Outdoor power circuit board)".
3 Check outdoor fan. 4 Solve short cycle. 5 Replace outdoor controller circuit board. 6 Check compressor.
Refer to "8-4.HOW TO CHECK THE PARTS".
Note: Before the replacement of the outdoor
controller circuit board, disconnect the wiring to compressor from the outdoor power circuit board and check the output voltage among phases, U, V, W, during test run. No defect on board if voltage among phases (U-V, V-W and W-U) is same. Make sure to perform the voltage check with same performing frequency.
7~1 Check water circuit and repair the defect.
UL
Low pressure (63L operated)
Abnormal if 63L is operated (under -0.03 MPa) during compressor operation. 63L: Low-pressure switch
1 Stop valve of outdoor unit is
closed during operation.
2 Disconnection or loose
connection of connector (63L) on outdoor controller board
3 Disconnection or loose
connection of 63L
4 Defective outdoor controller
board
5 Leakage or shortage of
refrigerant
6 Malfunction of linear expansion
valve
1 Check stop valve.
2~4 Turn the power off and on again to check
if F3 is displayed on restarting. If F3 is displayed, follow the F3 processing direction.
5 Correct to proper amount of refrigerant.
6 Check linear expansion valve.
Refer to "8-5.HOW TO CHECK THE COMPONENTS".
OCH562
20
Check code
Abnormal point and detection method
Judgment and action
Case
E0
or
E4
Remote controller transmission error (E0)/signal receiving error (E4)
Abnormal if main or sub remote controller
cannot receive any transmission normally from Interface unit/Flow temp. controller of refrigerant address “0” for 3 minutes.
(Check code: E0)
Abnormal if sub-remote controller could
not receive any signal for 2 minutes. (Check code: E0)
Abnormal if Interface/Flow temp.
controller board can not receive any data normally from remote controller board or from other Interface/Flow temp. controller board for 3 minutes.
(Check code: E4)
Interface/Flow temp. controller board
cannot receive any signal from remote controller for 2 minutes.
(Check code: E4)
Check disconnection or looseness of
Interface unit/Flow temp. controller unit or transmission wire of remote controller.
Set one of the remote controllers “main”, If
there is no problem with the action above.
Check wiring of remote controller.
• Total wiring length: max. 500 m
(Do not use cable × 3 or more.)
The number of connecting remote controller
:
Refer to the indoor units service manual.
When it is not the above-mentioned problem of
~ Diagnose remote controllers.
a) When “RC OK” is displayed, remote
controllers have no problem.
Turn the power off, and on again to check. If abnormality generates again, replace Interface/Flow temp. controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
Contact failure at transmission
wire of remote controller
All remote controllers are set
as “sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit
board. Miswiring of remote controller Defective transmitting receiving
circuit of remote controller Noise has entered into the
transmission wire of remote
controller.
E1
or
E2
Remote controller control board
Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the remote controller control board. (Check code: E1)
Abnormal if the clock function of remote
controller cannot be operated normally. (Check code: E2)
Defective remote controller
Replace remote controller.
Remote controller transmission error (E3)/signal receiving error (E5)
1
Abnormal if remote controller could not find blank of transmission path for 6 seconds and could not transmit.
(Check code: E3)
2
When remote controller receives the transmitted data same time and compares these data. Abnormal if the data is judged to be different for 30 continuous times. (Check code: E3)
1
Abnormal if Interface/Flow temp. controller board could not find blank of transmission path. (Check code: E5)
2
When Interface/Flow temp. controller receives the transmitted data same time and compares these data. Abnormal if the data is judged to be different for 30 con­tinuous times. (Check code: E5)
1 Set a remote controller to main, and the
other to sub.
2~4 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem. Turn the power off, and on again to check. When becoming abnormal again, replace indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormal­ity.
1 2 remote controllers are set as
“main.”
(In case of 2 remote controllers)
Note that some models can
only connect 1 remote control-
ler. For more detail, refer to the
indoor unit's service manual.
2 Defective transmitting receiving
circuit of remote controller
3 Defective transmitting receiving
circuit of Interface/Flow temp.
controller board
4 Noise has entered into trans-
mission wire of remote control-
ler.
E3
or
E5
E6
Interface unit/Flow temp. controller-out­door unit communication error (Signal receiving error)
1 Abnormal if Interface/Flow temp.
controller board cannot receive any signal normally for 6 minutes after turning the power on.
2 Abnormal if Interface/Flow temp.
controller board cannot receive any signal normally for 3 minutes.
1
Contact failure, short circuit or, miswiring (converse wiring) of Interface unit/Flow temp. control­ler-outdoor unit connecting wire
2 Defective transmitting receiving
circuit of Interface/Flow temp. controller board
3 Defective transmitting receiving
circuit of Interface/Flow temp. controller board
4
Noise has entered into Interface unit/Flow temp. controller­outdoor unit connecting wire.
* Check LED display on the outdoor control circuit
board. (Connect A-control service tool, PAC­SK52ST.)
1 Check disconnection or looseness of
Interface unit/Flow temp. controller-outdoor unit connecting wire of Interface unit/Flow temp. controller or outdoor unit.
2~4 Turn the power off, and on again to check.
If abnormality generates again, replace Interface/Flow temp. controller board or outdoor controller circuit board.
E8
Interface unit/Flow temp. controller­outdoor unit communication error (Signal receiving error) (Outdoor unit)
(1) Abnormal if outdoor controller circuit
board could not receive anything
normally for 3 minutes.
1 Contact failure of Interface unit/
Flow temp. controller-outdoor unit connecting wire
2 Defective communication circuit
of outdoor controller circuit board
3 Defective communication
circuit of Interface/Flow temp. controller board
4
Noise has entered into Interface unit/Flow temp. controller­outdoor unit connecting wire.
1 Check disconnection or looseness of
Interface unit/Flow temp. controller-outdoor unit connecting wire of Interface unit/Flow temp. controller or outdoor unit.
2~4 Turn the power off, and on again to
check. Replace Interface/Flow temp. controller board or outdoor controller circuit board if abnormality is displayed again.
OCH562
21
Check code
Abnormal point and detection method Judgment and action
Case
E9
Interface unit/Flow temp. controller­outdoor unit communication error (Transmitting error) (Outdoor unit)
(1) Abnormal if “0” receiving is detected 30
times continuously though outdoor con­troller circuit board has transmitted “1”.
(2) Abnormal if outdoor controller circuit
board could not find blank of transmission path for 3 minutes.
1
Interface unit/Flow temp. controller-outdoor unit connecting wire has contact failure.
2 Defective communication circuit
of outdoor controller circuit board
3 Noise has entered power supply. 4 Noise has entered Interface
unit/Flow temp. controller­outdoor unit connecting wire.
1 Check disconnection or looseness of
Interface unit/Flow temp. controller-outdoor unit connecting wire.
2~4 Turn the power off, and on again to
check. Replace outdoor controller circuit board if abnormality is displayed again.
EF
Non defined check code
This code is displayed when non defined check code is received.
1 Noise has entered transmission
wire of remote controller.
2 Noise has entered Interface
unit/Flow temp. controller­outdoor unit connecting wire.
12 Turn the power off, and on again to check. Replace Interface/Flow temp. controller
board or outdoor controller circuit board if abnormality is displayed again.
Ed
Serial communication error
Abnormal if serial communication between outdoor controller circuit board and outdoor power circuit board is defective.
1 Wire disconnection or contact
failure of connector CN2 between the outdoor controller circuit board and the outdoor power circuit board
2 Wire disconnection or contact
failure of connector CN4 between the outdoor controller circuit board and the outdoor power circuit board
3 Defective communication circuit
of outdoor power circuit board
4 Defective communication circuit
of outdoor controller circuit board for outdoor power circuit board
12 Check connection of each connector CN2
and CN4 between the outdoor controller circuit board and the outdoor power circuit board.
3 Replace outdoor power circuit board.
4 Replace outdoor controller circuit board.
P6
Freezing/overheating protection is working
(1) Freezing protection
<Cooling mode> Abnormal if plate heat exchanger pipe temperature (TH6) stays at -5: or lower for 10 seconds or abnormal if plate heat exchanger pipe thermistor (TH6) stays at
-2: or lower and compressor operation frequency is minimum for 5 minutes after compressor starts operating for 6 min­utes. <Heating mode> Abnormal if inlet water temperature ther­mistor (TH32) is 15: or lower, and the following condition (1 or 2) are detected.
1. 1 minute has passed since defrost­ing operation started and plate heat exchanger pipe temperature thermistor (TH6) stays at -6: or lower for con­tinuously 30 seconds.
2. During defrosting operation and plate heat exchanger pipe temperature ther­mistor (TH6) stays at -16: or lower for continuously 10 seconds.
(2) Overheating protection <Heating mode>
Abnormal if condensing temperature of pressure sensor (63HS) detects Tcond. : or more and compressor operation frequency is less than or equal to 30 Hz. Detection is inoperative during defrosting.
(1) Freezing protection
<Cooling mode>
1 Reduced water flow
· Clogged filter
· Leakage of water
2 Low temperature
· Low-load
· Inlet water is too cold.
3 Defective water pump 4 Defective outdoor fan control 5 Overcharge of refrigerant 6
Defective refrigerant circuit (clogs)
7
Malfunction of linear expansion valve
<Heating mode> 1 Reduced water flow
· Clogged filter
· Leakage of water
2 Low temperature
· Low-load
· Inlet water is cold.
3 Defective water pump 4
Leakage or shortage of refrigerant
5
Malfunction of linear expansion valve
(2) Overheating protection
<Heating mode>
1 Reduced water flow
· Clogged filter
· Leakage of water
2 High temperature
· Over-load
· Inlet water is too warm.
3 Defective water pump 4 Overcharge of refrigerant 5
Defective refrigerant circuit (clogs)
6
Malfunction of linear expansion valve
(1) Freezing protection
<Cooling mode>
12 Check water piping.
3 Check water pump. 4 Check outdoor fan motor. 5~7 Check operating condition of refrigerant
circuit.
7 Check linear expansion valve.
<Heating mode>
12 Check water piping.
3 Check water pump. 4 Correct to proper amount of refrigerant. 5 Check linear expansion valve. Refer to "8-5.
HOW TO CHECK THE COMPONENTS".
(2) Overheating protection
<Heating mode>
12 Check water piping.
3 Check water pump.
45
Check operating condition of refrigerant circuit.
6 Check linear expansion valve.
Ambient temperature (TH7)
stage-g
stage-f
stage-e
stage-d
stage-c
stage-b
stage-a
[ :]
Tcond
stage-a stage-b stage-c stage-d stage-e stage-f stage-g
-18 -17 -15 -14 -12 -11 -9 -8 -6 -5 -3 -2
W112
Model
63 60 57
53
48 48 48
Tcond
stage-x
stage-x stage-y
61 59
stage-y
34 35 39 40
OCH562
22
Check code
Abnormal point and detection method
Judgment and action
Case
P8
Pipe temperature
Abnormal if the following conditions are detected for continuously 3 minutes after compressor starts operating for 10 minutes.
1. Cooling mode T63HS-TH7 [ 2: and TH3-TH7 [ 4: or T63HS-TH3 < 0: and TH32-TH6 [ 0: and
Compressor operation frequency is 61Hz or more.
2. Heating mode
T63HS-TH32 [ 2: and TH6-TH32 [ 1: and TH7-TH3 [ 1: and Compressor operation frequency is 61Hz or more.
T63HS: Condensing temperature of pressure
sensor (63HS)
Thermistor
TH3: Liquid temperature TH32: Inlet water temperature TH6: Plate HEX Liquid temperature TH7: Ambient temperature
1 Leakage or shortage of
refrigerant
2 Malfunction of linear expansion
valve
3 Refrigerant circuit is clogged
with foreign objects.
Note: Clogging occurs in the parts
which become below freezing point when water enters in refrigerant circuit.
4 Disconnection of thermistor
holder.
1 Check intake superheat. Check leakage of refrigerant.
2 Check linear expansion valve.
3 After recovering refrigerant, remove water
from entire refrigerant circuit under vacuum more than 1 hour.
4 Check temperature display on outdoor
controller circuit board. Temperature display is indicated by setting SW2 of outdoor controller circuit board. Check the holder of thermistor.
UE
Abnormal pressure of pressure sensor (63HS)
Abnormal if pressure sensor (63HS) detects
0.1 MPa or less. Detection is inoperative for 3 minutes after compressor starting and 3 minutes after and during defrosting.
1 Disconnection or contact failure
of connector (63HS) on the outdoor controller circuit board
2 Defective pressure sensor 3 Defective outdoor controller
circuit board
1
Check connection of connector (63HS) on the
outdoor controller circuit board.
Check breaking of the lead wire for thermistor (63HS). 2 Check pressure by microcomputer. (Pressure sensor/ 63HS) (SW2: Refer to "
8-7. OUTDOOR UNIT OPERATION MONITOR".) FUNCTION".
3 Replace outdoor controller board.
PE
Inlet water temperature
Abnormal if the following conditions are detected for continuously 10 seconds.
1. Cooling mode During compressor operation TH32 < 3:
2. Heating mode (exclude defrosting) During compressor operation TH32 < -10:
3. Defrosting mode During compressor operation TH32 < 0:
Thermistor
TH32: Inlet water temperature
1 Reduced water flow
· Clogged filter
· Leak of water
2 Low temperature
· Low-load
· Low temperature inlet water
3 Defective water pump
4 Leakage or shortage of
refrigerant
12 Check water piping.
3 Check water pump.
4 Check intake superheat.
Check leakage of refrigerant.
OCH562
23
8-4. HOW TO CHECK THE PARTS PUHZ-W112VHA PUHZ-W112VHA-BS
1 2 3 4 5
M
Gray
Orange
Red
Yellow
Black
Parts name
Check points
Disconnect the connector then measure the resistance with a tester. (At the ambient temperature of 10 to 30:)
TH3: Liquid pipe temp. TH4: Discharge temp. TH6: Plate Hex liquid pipe temp. TH7: Ambient temp. TH8: Heatsink temp. TH32: Inlet water temp. TH33: Suction pipe temp. TH34: Comp. surface thermistor
Normal
160 to 410 k"
4.3 to 9.6 k"
4.4 to 9.8 k" 39 to 105 k"
TH4
TH34
TH3 TH6
TH7 TH33 TH32
TH8
Abnormal
Open or short
Measure the resistance between the terminals with a tester. (At the ambient temperature of 20
:
)
Solenoid valve coil <Four-way valve> (21S4)
Compressor (MC)
Normal
Abnormal
Open or short
Refer to the next page.Fan motor (MF1)
1435 ± 150 "
Normal
Abnormal
Open or short
0.188 "
Measure the resistance between the terminals with a tester. (Winding temperature 20
:
)
W
V
U
Linear expansion valve (LEV-A) (LEV-B)
Disconnect the connector then measure the resistance with a tester. (Winding temperature 20°C)
Normal
Gray - Black Gray - Red
Gray - Yellow
Gray - Orange
Abnormal
46±3
Open or short
OCH562
24
Notes
· High voltage is applied to the connector (CNF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNF1, 2) of the motor with the power supply on. (It may damage the outdoor controller circuit board and fan motor.) Self check Symptom: The outdoor fan does not run.
1
2
Check method of DC fan motor (fan motor / outdoor controller circuit board)
No
Wiring contact check
Check contact of fan motor connector (CNF1) (CNF2)
Recover wiring.
END
END
Replace fan motor. Replace
outdoor controller circuit board.
Replace outdoor controller circuit board.
Replace outdoor controller circuit board.
Replace fan motor.
Replace fan motor.
Check fan motor rotation.
Check fan motor rotation.
Is the voltage normal?
Is the fuse normal?
Is there contact failure?
Check fuse (F5) on outdoor controller circuit board.
Yes
Yes
No
No
Yes
Power supply check
Measure the voltage on the outdoor controller circuit.
TEST POINT1 VDC DC 280-380 V (between 1 (+) and 4 (-) of CNF1,2)
2 VCC DC 15 V (between 5 (+) and 4 (-) of CNF1,2)
NG
OK
NG
OK
OCH562
25
8-5. HOW TO CHECK THE COMPONENTS
<Thermistor feature chart>
Low temperature thermistors
• Thermistor <Liquid pipe> (TH3)
• Thermistor <Plate Hex liquid pipe> (TH6)
• Thermistor <Ambient> (TH7)
• Thermistor <Suction pipe> (TH33)
0: 15 kΩ 10: 9.6 kΩ 20: 6.3 kΩ 25: 5.2 kΩ
0: 180 kΩ 25: 50 kΩ 50: 17 kΩ 70: 8 kΩ 90: 4 kΩ
30: 4.3 kΩ 40: 3.0 kΩ
Thermistor R0 = 15 kΩ ± 3% B constant = 3480 ± 2%
R
t =15exp{3480(
273+t – 273
)}
1
Thermistor R50 = 17 kΩ ± 2% B constant = 4150 ± 3%
Rt =17exp{4150(
273+t – 323
)}
1
Thermistor R120 = 7.465k' ± 2%
B constant = 4057 ± 2%
R
t =7.465exp{4057(
273+t – 393
)}
1
1
Medium temperature thermistor
• Thermistor <Heatsink> (TH8)
20: 250 kΩ 30: 160 kΩ 40: 104 kΩ 50: 70 kΩ 60: 48 kΩ
70: 34 kΩ 80: 24 kΩ 90: 17.5 kΩ 100: 13.0 kΩ 110 : 9.8 kΩ
High temperature thermistors
• Thermistor <Discharge pipe> (TH4)
• Thermistor <Comp. surface> (TH34)
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
Temperature (:)
Resistance (k")
200
150
100
50
0
25 50 75 100 125
Temperature (:)
Resistance (k")
500
400
300
200
100
0
25
50 75 100 120
Temperature (:)
Resistance (k")
1
1
OCH562
26
Low temperature thermistor
• Thermistor <Inlet water> (TH32)
0: 15 kΩ 10: 9.6 kΩ 20: 6.3 kΩ 25: 5.2 kΩ
30: 4.3 kΩ 40: 3.0 kΩ
Thermistor R0 = 15 kΩ ± 2.5% B constant = 3450 ± 2%
R
t =15exp{3450(
273+t – 273
)}
1
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
Temperature(:)
Resistance (k")
1
0.5
2.5 5
2.5
4.5
Vout (V)
PRESSURE (MPa)
3
2
1
WHT
BLU
BLK
SENSOR
5V DC
GND
63HS
Vout
MICRO PROCESSOR
MULTI CONTROLLER BOARD
3-1 : 5V (DC) 2-1 : Output Vout (DC)
<HIGH PRESSURE SENSOR>
OCH562
27
<Output pulse signal and the valve operation>
(2) Linear expansion valve operation
Open
Extra tightening (about 32 pulse)
Pulse number
500 pulse Opening a valve all the way
Close
Valve position (capacity)
Opening a valve : 8 7 6 5 4 3 2 1 8 Closing a valve : 1 2 3 4 5 6 7 8 1 The output pulse shifts in above order.
• When linear expansion valve operation stops, all output phase
become OFF.
• When the switch is turned on, 700 pulse closing valve signal will be
sent till it goes to
point in order to define the valve position. (The
pulse signal is being sent for about 20 seconds.)
• When the valve moves smoothly, there is no sound or vibration
occurring from the linear expansion valve: however, when the pulse number moves from to or when the valve is locked, sound can be heard.
No sound is heard when the pulse number moves from to in
case coil is burnt out or motor is locked by open-phase.
• Sound can be detected by placing the ear against the screw driver
handle while putting the screw driver to the linear expansion valve.
LEV
M
1
6
1
Gray
Orange
Red
Yellow
Black
3
4
5
2
Connector LEV-A
LEV-B
DC12V
Outdoor controller board
Drive circuit
3
2
5
4
Linear expansion valve
(1) Operation summary of the linear expansion valve
• Linear expansion valve opens/closes through stepping motor after receiving the pulse signal from the outdoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the outdoor controller board and the linear expansion valve>
1
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
Output
(Phase)
Output
1
2
3
4
2 3 4
5 6 7 8
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OCH562
28
Main body
Lead wire
Stopper
Coil
Be sure to attach the stopper.
A
(3) How to attach and detach the coil of linear expansion valve
<Composition> Linear expansion valve is separable into the main body and the coil as shown in the diagram below.
<How to detach the coil>
Hold the lower part of the main body (shown as A) firmly so that the main body does not move and detach the coil by pulling it upward. Be sure to detach the coil holding main body firmly. Otherwise pipes can bend due to pressure.
<How to attach the coil>
Hold the lower part of the main body (shown as A) firmly so that the main body does not move and attach the coil by inserting it downward into the main body. Then securely attach the coil stop­per to main body. (At this time, be careful that stress is not added to lead wire and main body is not wound by lead wire.) If the stopper is not firmly attached to main body, coil may be detached from the main body and that can cause defective operation of lin­ear expansion valve. To prevent piping stress, be sure to attach the coil holding the main body of linear expansion valve firmly. Otherwise pipe may break.
A
OCH562
29
CNS
S1-S2: 230 V AC
CNAC
2 to 4: Power supply for outdoor controller circuit board (230 V AC) 1 to 3: Power supply for indoor and outdoor unit connec­tion wire (230 V AC)
CNF1, CNF2 Connect to the fan motor
1-4: 280-380 V DC 5-4: 15 V DC 6-4: 0-6.5 V DC 7-4: 15 V DC (When stopped)
7.5 V DC (When operated) (0 V-15 V pulse)
21S4
4-way valve
63H
High pressure switch
CN4
Transmission to out­door power circuit board (CN4)
SW6
Model select
SW5
Function switch
SW1
Forced defrost, detect history record reset
CNDM
1 to 2: Input of low-level sound priority mode
TH4
Thermistor <Discharge>
TH3
Thermistor <Liquid pipe>
TH7/6
Thermistor <Outdoor/ Plate Hex liquid>
CNDC
280-380 V DC (1+, 3-) (Outdoor power circuit board for)
VFG
(Voltage between right pins of PC5C and PC5D, pin 3 and pin 4) (Same as
(CNF1
7(+)-4(-))
VSP
(Voltage between pins of C5A, C5B): DC 0 V (when stopped), DC 1– 6.5 V (when operated)
SW2
Operation monitor function
LEV-A,B
Linear expansion valve
SW8
Function switch
CN2
Connect to the outdoor power circuit board (CN2) 1-5: Reception from
power circuit board
2-5: Zero cross signal (0-5 V DC) 3-4:
18V DC
6-5: 16V DC 7-5: 16V DC
CN52C
Connect to the power circuit board (CN52C) (HW140V)
TH32
Thermistor <Inlet water temperature>
63L
Low pressure switch
TH33
Thermistor <Suction pipe temperature>
SW7
Function switch
8-6. TEST POINT DIAGRAM Outdoor controller circuit board PUHZ-W112VHA PUHZ-W112VHA-BS
<CAUTION> TEST POINT 1 is high voltage.
TH34
Thermistor <Comp. surface>
SW9
Function switch
SV1
Connection for option (Drain hose heater output)
OCH562
30
CNAC1, CNAC2
230 V AC Connect to the out­door controller circuit board (CNAC)
NI, LI
Voltage of 230 V AC is input (Connect to the terminal block (TB1))
EI, E4
Connect to the earth
DCL1, DCL2
Connect to DCL
P2
Connect to the smooth­ing capacitor CB +
U/V/W
Connect to the compres­sor (MC) Voltage among phases: 10 V-180 V AC
CNDC
280-380 V DC (1+, 3-) Connect to the outdoor controller circuit board (CNDC)
E2, E3
Connect to the earth
CN52C
52C driving signal Connect to the outdoor controller circuit board (CN52C)
CN2 Connect to the outdoor controller circuit board (CN2) 1-5: Transmitting signal to outdoor controller circuit board (0-5 V DC) 2-5: Zero cross signal (0-5 V DC) 3-4: 18 V DC 6-5: 16 V DC 7-5: 16 V DC
N2
Connect to the smoothing capacitor CB -
CN4 Connect to the outdoor controller circuit board (CN4)
Brief Check of POWER MODULE
Usually, they are in a state of being short-circuited if they are broken. Measure the resistance in the following points (connectors, etc.). If they are short-circuited, it means that they are broken.
1. Check of POWER MODULE 1 Check of DIODE circuit
R - L1 , S - L1 , R - N1 , S - N1 2 Check of IGBT circuit L2 - N1 3 Check of INVERTER circuit P - U , P - V , P - W , N1 - U , N1 - V , N1 - W
Power module
Note: The marks R , S , L1 , L2 , P , N1 , U , V and W
shown in the diagram are not actually printed on the board.
S R
W V U L2 P N1 L1
Outdoor power circuit board PUHZ-W112VHA PUHZ-W112VHA-BS
OCH562
31
8-7. OUTDOOR UNIT OPERATION MONITOR FUNCTION
SW2 setting
1ON2 3 4 5 6
Display detail
Explanation for display Unit
Operation indicator SW2: Indicator change of self diagnosis
<Digital indicator LED3 working details>
(Be sure that the 1 to 6 in the SW2 are set to OFF.)
(1) Display when the power supply is ON.
When the power supply is ON, blinking displays by turns. Wait for 10 seconds at the longest.
(2) When the display lights (Normal operation)
1 Operation mode display
1ON2 3 4 5 6
(Initial setting)
SW2
1 second
interval
LED3
(Lighting)
Display Operation Model
The tens digit : Operation mode
The ones digit : Relay output
O C H
d
Display
0 1 2 3 4 5 6 7 8 A
Compressor
Warming-up Compressor
4-way valve
Solenoid valve
— — —
— ON ON ON ON
— — — — — — —
— ON ON
— ON ON
— ON ON
— ON
ON
ON
ON
ON
— —
OFF
COOLING
HEATING
DEFROSTING
2 Display during error postponement
Postponement code is displayed when compressor stops due to the work of protection device. Postponement code is displayed while error is being postponed.
(3) When the display blinks
Inspection code is displayed when compressor stops due to the work of protection devices.
Display
Inspection unit
0 Outdoor unit
Display
Contents to be inspected (During operation) U1 Abnormal high pressure (63H operated) U2 Abnormal high discharging temperature, shortage of refrigerant U3 Open/short circuit of discharging thermistor (TH4, TH34) U4 Open/short of outdoor unit thermistors (TH3, TH32, TH6, TH7, TH8 and TH33) U5 Abnormal temperature of heatsink U6 Abnormality of power module U7 Abnormality of superheat due to low discharge temperature U8 Abnormality in outdoor fan motor U9 Voltage fault, Input current sensor error Ud Overheat protection UF Compressor overcurrent interruption (When Comp. locked)
UH Current sensor error
UP Compressor overcurrent interruption P6 Abnormality of Interface or FTC units P8 Abnormality of pipe temperature UE Abnormality pressure of pressure sensor PE Abnormality of inlet water temperature Ed Serial communication error
Display
Contents to be inspected (When power is turned on) F5 63H connector(yellow) is open. E8 Interface unit/Flow temp. controller-outdoor communication error (Signal receiving error) (Outdoor unit) E9 Interface unit/Flow temp. controller-outdoor communication error (Transmitting error) (Outdoor unit) EA
Miswiring of Interface unit/Flow temp. controller-outdoor unit connecting wire, excessive number of indoor units (2 units or more)
Eb
Miswiring of Interface unit/Flow temp. controller-outdoor unit connecting wire (converse wiring or disconnection)
EC Startup time over
E0~E7 Communication error except for outdoor unit
The black square () indicates a switch position.
OCH562
32
SW2 setting
1ON2 3 4 5 6
Display detail
Explanation for display Unit
Pipe temperature / Liquid (TH3)
- 40 to 90
- 40 to 90 (When the coil thermistor detects 0: or below, “–” and temperature are displayed by turns.) (Example) When -10:;
0.5 secs. 0.5 secs. 2 secs.
:
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
Discharge temperature (TH4) 3 to 217
Fan steps 0 to 10
Compressor ON/OFF 0 to 9999
Compressor accumulated operation hours 0 to 9999
3 to 217 (When the discharge thermistor detects 100: or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 105:;
0.5 secs. 0.5 secs. 2 secs.
:
Step
100 times
10 hours
0 to 10
0 to 9999 (When the number of times is 100 or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 42500 times (425
100 times);
0.5 secs. 0.5 secs. 2 secs.
0 to 9999 (When it is 100 hours or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 2450 hours (245
10 hours);
0.5 secs. 0.5 secs. 2 secs.
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
Compressor running current 0 to 50
LEV-A opening pulse 0 to 500
0 to 50 (Value after the decimal point will be truncated.)
0 to 500 (When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 150 pulse;
0.5 secs. 0.5 secs. 2 secs.
A
Pulse
Deferred error history (1)
Deferred error Blinking: being deferred Lighting: deferment is cancelled “00” is displayed in case of no deferment
Code
display
Code
display
Operation mode when the error occurred
Operation mode when the unit is stopped due to an error is displayed. The displayed code is when the SW2 is set as below.
1ON2 3 4 5 6
(SW2)
10
1ON2 3 4 5 6
Compressor running frequency 0 to 255
0 to 255 (When it is 100 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 105 Hz;
0.5 secs. 0.5 secs. 2 secs.
Hz
1
05
4
25
2
45
1
05
1
50
1ON2 3 4 5 6
The black square () indicates a switch position.
OCH562
33
SW2 setting
1ON2 3 4 5 6
Display detail
Explanation for display Unit
Pipe temperature/Liquid (TH3) when error occurred
- 40 to 90
- 40 to 90 (When the coil thermistor detects 0: or below, “–” and temperature are displayed by turns.) (Example) When - 15:;
0.5 secs. 0.5 secs. 2 secs.
:
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
Discharge temperature (TH4) when error occurred 3 to 217
Compressor current when error occurred 0 to 50
Error history (1) (latest) Alternate display of faulty unit number and check code
Error history (2) Alternate display of faulty unit number and check code
3 to 217 (When the temperature is 100: or more, the hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 130:;
0.5 secs. 0.5 secs. 2 secs.
:
A
Code
display
Code
display
0 to 50
When no error history, “ 0 ” and “– –” are displayed by turns.
When no error history, “ 0 ” and “– –” are displayed by turns.
1ON2 3 4 5 6
Compressor operation duration 0 to 999
0 to 999 (When it is 100 minutes or more, the hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 245 minutes;
0.5 secs. 0.5 secs. 2 secs.
Minute
15
1
30
2
45
1ON2 3 4 5 6
Capacity settings
The outdoor capacity code is shown as below
Code
display
1ON2 3 4 5 6
LEV-B opening when error occurred
Pulse
0 to 500 (When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 150 pulse;
0.5 secs. 0.5 secs. 2 secs.
1
50
Model Code PUHZ-W112 20
The black square (
) indicates a switch position.
OCH562
34
SW2 setting
Display detail
Explanation for display
Unit
1ON2 3 4 5 6
Plate HEX liquid pipe temperature (TH6)
- 39 to 88
:
- 39 to 88 (When the temperature is 0: or less, “–” and temperature are displayed by turns.)
1ON2 3 4 5 6
1ON2 3 4 5 6
Condensing temperature (T
63HS
)
- 39 to 88
- 39 to 88 (When the temperature is 0: or less, “–” and temperature are displayed by turns.)
:
0 to 150 (When it is 100 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns.
(Example) When 105 Hz;
0.5 secs. 0.5 secs. 2 secs.
Hz
Calculated maximum frequency 0 to 150
1ON2 3 4 5 6
:
Ambient temperature (TH7)
- 39 to 88
- 39 to 88 (When the temperature is 0: or less, “–” and temperature are displayed by turns.)
1ON2 3 4 5 6
Outdoor heatsink temperature (TH8)
- 40 to 200
:
- 40 to 200 (When the temperature is 0: or less, “–” and temperature are displayed by turns.) (When the thermistor detects 100: or more, hundreds digit, tens digit and ones digit are displayed by turns.)
1ON2 3 4 5 6
°C
Discharge superheat (SHd) 0 to 255
Cooling and Heating: SHd = TH4-T63HS
0 to 255 (When the SHd is 100°C or more, hundreds digit, tens digit and ones digit are displayed by turns.)
1ON2 3 4 5 6
Outdoor unit setting information
Code
display
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P /
Cooling only
Single phase / 3 phase
Display details
0 : H·P 1 : Cooling only
0 :
Single phase
2 :
3 phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
(Example) When heat pump, 3 phase and defrosting
(normal) are set up, “20” is displayed.
1ON2 3 4 5 6
Water inlet temperature (TH32) 0 to 100
:
0 to 100
1
05
The black square () indicates a switch position.
OCH562
35
1ON2 3 4 5 6
0.1 A
Input current of outdoor unit 0 to 500
0 to 500 (When it is 100 or more, hundreds digit, tens digit and ones digit are displayed by turns.)
1ON2 3 4 5 6
Pulse
LEV-B opening pulse 0 to 500
0 to 500 (When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns.)
Code
display
U9 error detail history (latest)
Direct current bus voltage 150 to 400
150 to 400 (When it is 100V or more, hundreds digit, tens digit and ones digit are displayed by turns.)
V
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
Code
display
Deferred error history (2) of outdoor unit
Deferred check code display Blinking: being deferred Lighting: deferment is cancelled “00” is displayed in case of no deferment.
Code
display
Deferred error history (3) of outdoor unit
1ON2 3 4 5 6
1ON2 3 4 5 6
Deferred check code display Blinking: being deferred Lighting: deferment is cancelled “00” is displayed in case of no deferment.
1ON2 3 4 5 6
%
When there is no setting of capacity save, “100” is displayed.
0 to 100
(When the capacity is 100%, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 100%;
0.5 secs. 0.5 secs. 2 secs.
00
1
Capacity save 0 to 100
The black square () indicates a switch position.
2 cycles
Number of defrost cycles 0 to FFFE
0 to FFFE (in hexadecimal notation) (When more than FF in hex (255 in decimal), the number is displayed in order of 16
3
's and 162's, and 161's and 160's places. (Example) When 5000 cycles;
0.5 secs. 0.5 secs. 2 secs.
C4
9
Normal Overvoltage error Undervoltage error Input current sensor error L
1-phase open error
Abnormal power synchronous signal PFC/IGBT error Undervoltage
* Display examples for multiple errors: Overvoltage (01) + Undervoltage (02) = 03 Undervoltage (02) + Power-sync signal error (08) = 0A L
1 phase open error (04) + PFC/IGBT error (20) = 24
Description Display
00 01 02
04
08
20
SW2 setting
Display detail
Explanation for display Unit
OCH562
36
SW2 setting
Display detail
Explanation for display Unit
Operation frequency when error occurred. 0 to 225
0 to 225 (When it is 100 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 105 Hz;
0.5 secs. 0.5 secs. 2 secs.
1ON2 3 4 5 6
Hz
Fan step when error occurred. 0 to 10
0 to 10
1ON2 3 4 5 6
Step
1
05
Ambient temperature (TH7) when error occurred.
- 39 to 88
- 39 to 88 (When the temperature is 0°C or less, “–” and temperature are displayed by turns.) (Example) When - 15°C;
0.5 secs. 0.5 secs. 2 secs.
1ON2 3 4 5 6
15
:
1ON2 3 4 5 6
Pulse
LEV-A opening pulse when error occurred. 0 to 500
0 to 500 (When it is 100 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 130 pulse;
0.5 secs. 0.5 secs. 2 secs.
:
Water inlet temperature (TH32) when error occurred. 0 to 100
0 to 100
30
1
1ON2 3 4 5 6
:
Plate HEX liquid pipe temperature (TH6) when error occurred.
- 39 to 88
- 39 to 88 (When the temperature is 0°C or less, “–” and temperature are displayed by turns.) (Example) When –15°C;
0.5 secs. 0.5 secs. 2 secs.
Condensing temperature when error occurred.
- 39 to 88
- 39 to 88 (When the temperature is 0°C or less, “–” and temperature are displayed by turns.) (Example) When –15°C;
0.5 secs. 0.5 secs. 2 secs.
1ON2 3 4 5 6
1ON2 3 4 5 6
15
15
:
Code
display
Error history (3) (Oldest) Faulty unit number and check code are displayed alternately.
When no error history, “0” and “– –“ are displayed by turns.
1ON2 3 4 5 6
3: Liquid pipe thermistor (TH3) 3: Water inlet temp. thermistor (TH32) 6: Plate HEX liquid pipe thermistor (TH6) 7: Ambient temp. thermistor (TH7) 8: Heatsink thermistor (TH8) 4: Discharge thermistor (TH4) 3: Suction pipe thermistor (TH33) 34: Comp. surface thermistor (TH34)
1ON2 3 4 5 6
Error thermistor display
When there is no error thermistor, “–“ is displayed.
Code
display
The black square (
) indicates a switch position.
OCH562
37
Outdoor heatsink temperature (TH8) when error occurred.
- 40 to 200
- 40 to 200 (When the temperature is 0°C or less, “–” and temperature are displayed by turns.) (When the temperature is 100°C or more, hundreds digit, tens digit and ones digit are displayed by turns.)
1ON2 3 4 5 6
:
:
0 to 255 (When the temperature is 100°C or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 150°C;
0.5 secs. 0.5 secs. 2 secs.
50
1
1ON2 3 4 5 6
Discharge superheat (SHd) when error occurred. 0 to 255
Cooling and Heating: SHd=TH4-T
63HS
SW2 setting
Display detail
Explanation for display Unit
Sub cool (SC) when error occurred. 0 to 130
Cooling: SC = T63HS-TH3 Heating: SC = T
63HS-TH6
0 to 130 (When the temperature is 100°C or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 115°C;
0.5 secs. 0.5 secs. 2 secs.
Compressor operation duration before the unit stops with error 0 to 999
0 to 999 (When it is 100 minutes or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 415 minutes;
0.5 secs. 0.5 secs. 2 secs.
Maximum frequency when error occurred 0 to 150
0 to 150 (When it is 100 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 105 Hz;
0.5 secs. 0.5 secs. 2 secs.
Requested capacity step when error occurred 0 to 7
0 to 7
Step
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
1ON2 3 4 5 6
:
Minute
Hz
15
1
15
4
1
05
1ON2345 6
Compressor frequency control status
The following code will be a help to know the operat­ing status of unit.
•Ten place (left side):
•First digit (Total figure of the corresponding relays
are displayed.)
Code
display
Display
Compressor frequency control
Input current restriction control
Compressor current restriction control
1 2
Display
Compressor frequency control
Discharge temp.control(not to over rise). Condensing temp.control(not to over rise).
1 2
Freezing protection control
4
Heatsink temp.control(not to over rise).
8
When the following 3 points are under control; (1) Input current restriction control. (2) Condensing temp. control (not to over rise). (3) Heatsink temp. control (not to over rise).
1a
LED
The black square () indicates a switch position.
OCH562
38
1ON2 3 4 5 6
U9 Error details (To be shown while error call is deferred.)
Code
display
1ON2345 6
Requested capacity step (Q STEP) 0 to 7
0 to 7
Step
SW2 setting
Display detail
Explanation for display Unit
:
Comp. surface temperature (TH34) 3 to 217
3 to 217 (When the temperature is 100: or more, the hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 130:;
0.5 secs. 0.5 secs. 2 secs.
1ON2 3 4 5 6
1ON2 3 4 5 6
Outdoor suction pipe temperature (TH33)
- 39 to 88
:
1
30
- 39 to 88 (When the temperature is 0°C or less, “–” and temperature are displayed by turns.) (Example) When –15°C;
0.5 secs. 0.5 secs. 2 secs.
15
The black square () indicates a switch position.
Normal Overvoltage error Undervoltage error Input current sensor error L
1-phase open error
Abnormal power synchronous signal PFC/IGBT error Undervoltage
* Display examples for multiple errors: Overvoltage (01) + Undervoltage (02) = 03 Undervoltage (02) + Power-sync signal error (08) = 0A L
1 phase open error (04) + PFC/IGBT error (20) = 24
Description Display
00 01 02
04
08
20
OCH562
39
Model name [Serial No. ]
Date
SW2 setting
1:ON / 0:OFF
SW2 setting
1:ON / 0:OFF
123456 123456
)edoM(derrucco rorre eht nehw edom noitarepO/erutarepmet retaw teltuO/telnI 010100
)edoC(]tsetaL[ )1( yrotsih rorrE/erutarepmet riA teltuO/telnI roodtuO 011100
)edoC()2( yrotsih rorrE/erutarepmet noitcuS/egrahcsiD 111100
)edoC(]tsedlO[ )3( yrotsih rorrE/erusserp noitcuS/egrahcsiD 000101
)edoC()1( yrotsih rorre derrefeD/) zH / V ( ycneuqerF/egatloV ylppus rewoP 100100
)edoC()2( yrotsih rorre derrefeD) nim/L
( emuloV wolf retaW 011001
Inlet water temp. [TH32] 001110 Deferred error history (3) (Code) 11100
1
Plate HEX liquid pipe temp. [TH6] 001010 Condensing temp.
[T
63HS
]
111101
Condensing temp.
[T
63HS
]
101010 Plate HEX liquid pipe temp. [TH6] 011101
Ambient temp. [TH7] 101110 Compressor running frequency (Hz) 010101
Compressor running frequency (Hz) 111000 Fan steps (Step) 110101
Fan steps (Step) 110000 Liquid pipe temp. [TH3] 110100
Liquid pipe temp. [TH3] 100000 Discharge temp. [TH4] 001100
Discharge temp. [TH4] 010000 LEV-A opening pulse [LEV-A] 001101
LEV-A opening pulse [LEV-A] 000100 LEV-B opening pulse [LEV-B] 100010
LEV-B opening pulse [LEV-B] 010001 Ambient temp. [TH7] 100011
Water inlet temp. [TH32] 000011
Requested capacity step
[Q
STEP
]
101111
Heat sink temp. [TH8] 010011
Comp. surface temp. [TH34] 011111
Calculated max. frequency (Hz) 011011
Suction temp. [TH33] 010111
Sub Cool [ SC ] 001011
Heat sink temp. [TH8] 011110
Compressor operation duration (Min) 101011
Discharge Super Heat [SHd]
[SC]
111110
Requested capacity step
[Q
STEP
]
111011
Calculated max. frequency (Hz) 111010
Discharge Super Heat [SHd] 110011
Compressor operation duration (Min) 000010
Compressor running current (A) 101100
Number of defrost cycle 000001
Capacity setting (Code) 010010
Demand capacity (%) 101001
Compressor ON/OFF (×100) 001000
Direct current bus line voltage (V) 001001
Compressor accumulated operation hours
(×10hours)
101000
Compressor running current (A)
9U
000110
error detail history (latest) (Code) 110001
Input current (0.1A) 100001
Check sum (Code) 110111
Compressor frequency control status * 100111 *
Temperature differential code [ΔTj] 000111
sutats noitarepo dedroceRataD noitarepO
Data Sheet for Air to Water Compact type
when error occurred
10ths digit 1:Input current restriction control 1st digit 1:Discharge temp. control 4:Freeze protection control
2:Compressor current restriction control 2:Condensing temp. control 8:Heat sink temp. control
PUHZ-W112VHA(-BS)
Applicable model
OCH562
40
8-8. FUNCTION OF SWITCHES PUHZ-W112VHA PUHZ-W112VHA-BS
Switch
Function
Selection
Initial setting* Function details Effective timing
Mark No. ON (with) OFF (without)
SW1
1 Forced defrosting ON to start usual setting OFF Switch ON to force defrosting Always
2 To clear error history ON to clear usual setting OFF
Switch ON to clear (erase) the followings: (1)
Check codes and
Suspension ags in RAM
(2)
Check codes and Suspension
ags in EEPROM
Always
3 No function Do NOT use PUHZ-W112VHA OFF
Always
4 Abnormal disregard Disregard Normal OFF
Check code (P8,UH): Abnormal detection disregard
5 No function Do NOT use PUHZ-W112VHA OFF
6 No function Do NOT use PUHZ-W112VHA OFF
SW5
1
Silent setting (FAN) Silent setting (FAN)
usual setting OFF
Fan speed setting in silent mode
Always
2 Silent setting (Hz) Silent setting (Hz) usual setting OFF
Hz setting in silent mode
3 No function Do NOT use PUHZ-W112VHA OFF
4 No function Do NOT use PUHZ-W112VHA OFF
5
Defrost control
selection
For high humidity Standard OFF
Switches to optimal defrosting operation for low-temperature and high-humidity regions.
6 No function Do NOT use PUHZ-W112VHA OFF
SW6
1-3
Model Setting
Model
SW6
1 2 3
W 0 0 1
1=ON, 0=OFF
As shown in the left
table
4
Single phase /
3 phase
Do NOT use Single phase
5-8 Model Setting 2
Model
SW6
5 6 7 8
W112 0 1 1 0
1=ON, 0=OFF
As shown in the left
table
Make sure to set SW6-5 to 8 correctly
SW7 1-6 No function Do NOT use PUHZ-W112VHA OFF
SW8
1 Mode selection Energy saving mode Powerful mode OFF Always
2 Max. current setting
Model
Max. current
OFF ON
W112 29.5A 23.0A
OFF
When power supply
ON
3
Separate Interface/Flow temp.controller - outdoor
unit power supplies
Separate power
supply
Outdoor unit power
supply
OFF
Power supply connection method selection
When power supply
ON
SW9 1-4 No function Do NOT use
<Important Note>
All these dip switches on PUHZ-W112VHA are set as shown above. Spare PCBs, however, will be supplied without any settings, which means that all dip switches are switched OFF. When servicing, please make sure to set all switches correctly, referring to the previous PCB which is removed from the unit.
*1. Forced defrosting should be done as follows.
1 Change the DIP SW1-1 on the outdoor controller board from OFF to ON. 2 Forced defrosting will start by the above operation 1 if these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor starts operating or previous forced defrosting is finished.
• Pipe temperature is less than or equal to 8:.
Forced defrosting will finish if certain conditions are satisfied. Forced defrosting can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON. After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again. This depends on the service conditions.
OCH562
41
1. Removing the service panel and top panel (1) Remove 3 service panel fixing screws (5 × 12) and slide
the hook on the right downward to remove the service panel.
(2) Remove screws (3 for front, 3 for rear/5 × 12) of the top
panel and remove it.
2. Removing the fan motor (MF1, MF2)
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove 5 fan grille fixing screws (5 × 12) to detach the
fan grille. (See Photo 1)
(4) Remove a nut (for right handed screw of M6) to detach the
propeller. (See Photo 2)
(5) Disconnect the connectors, CNF1 and CNF2 on controller
circuit board in electrical parts box.
(6) Remove 4 fan motor fixing screws (5 × 20) to detach the
fan motor. (See Photo 3)
3. Removing the electrical parts box
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Disconnect the indoor/outdoor connecting wire and power
supply wire from terminal block. (4) Disconnect the connectors on the controller circuit board. (5) Remove the terminal cover and disconnect the compres-
sor lead wire. (6) Remove 2 electrical parts box fixing screw (4 × 10) and
detach the electrical parts box by pulling it upward. The
electrical parts box is fixed with 2 hooks on the left and 1
hook on the right.
Photo 1
Photo 2
Propeller
Front panel
Nut
Electrical parts box fixing screw
Terminal block (TB1)
Fan motor fixing screws
Fan motor
Fan motor fixing screws
Photo 3
Photo 4
Controller circuit board
Hook (right)
Top panel fixing screws
Top panel
Service panel fixing screws
Service panel
Grille fixing screws
Fan grille
Grille fixing screws
Slide
PUHZ-W112VHA PUHZ-W112VHA-BS
DISASSEMBLY PROCEDURE
9
Cover panel (front)
OPERATING PROCEDURE
PHOTOS & ILLUSTRATION
OCH562
42
Photo 5
4. Removing the thermistor <Plate HEX liquid> (TH6) and thermistor <Ambient> (TH7)
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Disconnect the connectors, TH7/6 (red) on the controller
circuit board in the electrical parts box. (4) Loosen the 2 wire clamps on top of the electrical parts box. (5) Loosen the fastener for the lead wire on the controller cir-
cuit board in the electrical parts box. (6) Loosen the cable strap for the lead wire on the bottom of
electrical parts box. (7) Pull out the thermistor <Plate HEX liquid> (TH6) and ther-
mistor <Ambient> (TH7) from the sensor holder.
Note: In case of replacing thermistor <Plate HEX liquid>
(TH6) or thermistor <Ambient> (TH7), replace it together.
5. Removing the thermistor <Discharge> (TH4)
and
thermistor <Comp. surface>
(TH34)
(1) Remove the service panel. (See Photo 1)
(2) Disconnect the connector TH4 (white) on the controller cir-
cuit board in the electrical parts box. (4) Loosen the wire clamp on separator. (5) Loosen the cable strap for the lead wire on the bottom of
electrical parts box. (6) Pull out the thermistor <Discharge> (TH4) from the sensor
holder.
[Removing the thermistor <Comp. surface> (TH34)]
(7) Remove the top damper, then pull out the thermistor
<Comp. surface> (TH34) from the holder of the compres-
sor shell.
Photo 8
6.
Removing the thermistor <Liquid> (TH3) and thermistor
<suction> (TH33)
(1) Remove the service panel. (See Photo 1) (2) Disconnect the connectors TH3 (white) and TH33 (yellow)
on the controller circuit board in the electrical parts box.
(3) Loosen the fastener for the lead wire on the controller cir-
cuit board in the electrical parts box. (4) Loosen the wire clamp and wire clip on separator. (5) Pull out the thermistor <Liquid> (TH3), <Suction> (TH33)
from the sensor holder.
Photo 7
Photo 6
Lead wire of thermistor <Ambient> (TH7)
Sensor holder
High pressure sensor (63HS)
High pressure sensor (63HS)
Thermistor <Liquid> (TH3)
Compressor (MC)
4-way value
Thermistor <Plate HEX liquid> (TH6)
Low pressure switch (63L)
Stay
Compressor (MC)
Thermistor <Discharge> (TH4)
Thermistor <Suction> (TH33)
Thermistor <Comp. surface> (TH34)
Top damper
OPERATING PROCEDURE
PHOTOS
OCH562
43
7. Removing the 4-way valve coil (21S4), and linear expan­sion valve coil (LEV-A, LEV-B)
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1)
[Removing the 4-way valve coil] (See Photo 9)
(3) Remove 4-way valve solenoid coil fixing screw (M4 × 6). (4) Remove the 4-way valve coil by sliding the coil toward you. (5) Disconnect the connector 21S4 (green) on the controller
circuit board in the electrical parts box.
(6) Loosen the fastener for the lead wire on the controller cir-
cuit board in the electrical parts box.
[Removing the LEV coil] (See Photo 10)
(3) Loosen the lead wires fixed to the pipes with bands. (4)
Remove the linear expansion valve coil by sliding the coil upward.
(5) Disconnect the connectors, LEV-A (white) and LEV-B (red)
on the controller circuit board in the electrical parts box.
8. Removing the 4-way valve
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical parts box. (See Photo 4) (4) Remove the cover panel (front).(See Photo 1) (5) Remove the stay. (6) Remove 5 right side panel fixing screws (5 × 12) (4: rear of
the unit/1: right side base) and remove the right side panel. (7) Remove the 4-way valve coil. (See Photo 9) (8) Recover refrigerant. (9) Remove the welded part of 4-way valve.
10. Removing the high pressure switch (63H) (See Photo 9) and the low pressure switch (63L)
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical parts box. (4) Remove the cover panel (front). (See Photo 1) (5) Remove the stay. (6) Remove 5 right side panel fixing screws (5 × 12) (4: rear
of the unit/1: right side base) and remove the right side panel.
(7) Pull out the lead wire of high pressure switch and low
pressure switch. (8) Recover refrigerant. (9) Remove the welded part of high pressure switch and low
pressure switch.
9. Removing LEV
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical parts box. (See Photo 4) (4) Remove the cover panel (front). (See Photo 1) (5) Remove 3 stay fixing screws (4 × 10) and remove the stay. (6)
Remove 5 right side panel fixing screws (5 × 12) (4: rear of
the unit/1: right side base) and remove the right side panel. (7) Remove the LEV coil. (8) Recover refrigerant. (9) Remove the welded part of LEV.
Photo 10
LEV (LEV-A)
Photo 9
High pressure switch (63H)
4-way valve coil fixing screw
4-way valve
LEV (LEV-B)
4-way valve
Heat exchanger
Photo 11
Low pressure switch (63L)
High pressure sensor (63HS)
Notes:
1. Recover refrigerant without spreading it in the air.
2. The welded part can be removed easily by remov­ing the right side panel.
3. When installing the follwing parts, cover it with a wet cloth to prevent it from heating, then braze the pipes so that the inside of pipes are not oxidized;
4-way valve (procedure 8), 120°C or more
LEV (procedure 9), 120°C or more
High pressure switch and low pressure switch (procedure 10),
100°C or more
Refer to the notes below.
Refer to the notes below.
Refer to the notes on the right.
OPERATING PROCEDURE
PHOTOS
OCH562
44
Photo 12
11. Removing high pressure sensor (63HS)
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Pull out the lead wire of high pressure sensor. (4) Remove the 4-way valve coil. (See Photo 9) (5) Recover refrigerant. (6) Remove the welded part of high pressure sensor.
Note 1:
Recover refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the high pressure sensor, make
sure to cover it with a wet cloth to prevent it from
heating (100˚C or more), then braze the pipes so
that the inside of pipes are not oxidized.
12. Removing the plate heat exchanger
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3)
Remove 2 screws (5 × 12) and remove the front cover panel. (4) Remove the electrical parts box. (See Photo 4) (5)
Remove 3 screws (4 × 10) and remove the stay. (6) Remove 5 screws (5 × 12) (4: rear of the unit/1: right side
base) and remove the right side panel. (7) Recover the refrigerant (8) Remove 2 welded pipes of plate heat exchanger inlet and
outlet. (9) Remove 3 plate heat exchanger fixing screws (4
×
10),
then remove the plate heat exchanger.
Note 1: Recover refrigerant without letting it out in the air. Note 2:
Before removing the thermistor <Inlet water> (TH32),
recover water in the plate heat exchanger.
Photo 13
Plate heat exchanger
Plate heat exchanger fixing screw
Heat exchanger
Plate heat exchanger fixing screw
Low pressure switch (63L)
High pressure sensor (63HS)
OPERATING PROCEDURE
PHOTOS
OCH562
45
14. Removing the power receiver
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove 2 front cover panel fixing screws (5 × 12) and
remove the front cover panel. (4) Remove the electrical parts box. (See Photo 4) (5) Remove 3 stay fixing screws (4 × 10) and remove the stay. (6) Remove 5 right side panel fixing screws (5 × 12) (4: rear
of
the unit/1: right side base) and remove the right side panel. (7) Recover refrigerant. (8) Remove 4 welded pipes of power receiver inlet and outlet. (9) Remove 2 receiver leg fixing screws (4 × 10).
Note: Recover refrigerant without spreading it in the air.
13. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove 2 front cover panel fixing screws (5 × 12) and
remove the front cover panel. (4) Remove the electrical parts box. (See Photo 4) (5) Remove 3 stay fixing screws (4 × 10) and remove the stay. (6)
Remove 5 right side panel fixing screws (5 × 12) (4: rear of
the unit/1: right side base) and remove the right side panel. (7) Remove 3 separator fixing screws (4 × 10) and remove
the separator. (8) Remove the soundproof cover for compressor. (9) Remove the terminal cover and remove the compressor
lead wire.
(10) Recover refrigerant. (11) Remove the 3 points of the compressor fixing nut using a
spanner or a adjustable wrench.
(12) Remove the welded pipe of compressor inlet and outlet
then remove the compressor.
Note: Recover refrigerant without spreading it in the air.
Photo 14
Pipes of power receiver
Compressor (MC)
Terminal cover
Compressor fixing nut
Plate heat exchanger fixing screw
Receiver leg fixing screw
Power receiver
OPERATING PROCEDURE
PHOTOS
OCH562
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2014 MITSUBISHI ELECTRIC CORPORATION Distributed in Jun. 2014 No. OCH562 Made in Japan
New publication, effective Jun. 2014 Specifications are subject to change without notice.
Loading...