Mitsubishi PUHZ-SW75VHA, PUHZ-SW75VHA-BS.UK, PUHZ-SW75VHAR3-BS.UK, PUHZ-SW75VHAR4-BS.UK, PUHZ-SW100VHA-BS.UK Service Manual

...
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES
................................
2
2. REFERENCE MANUAL
.................................
3
.................................
4
4. FEATURES
.....................................................
8
5. SPECIFICATIONS
..........................................
9
6. DATA
.............................................................
13
7. OUTLINES AND DIMENSIONS
...................
15
8. WIRING DIAGRAM
......................................
17
9. WIRING SPECIFICATIONS
..........................
24
10.
REFRIGERANT SYSTEM DIAGRAM
..............
25
11. TROUBLESHOOTING
..................................
27
12. DISASSEMBLY PROCEDURE
.....................
82
R410A
PUHZ-SW75VHA.UK PUHZ-SW75VHA-BS.UK
Salt proof model
PUHZ-SW75VHA-BS
PUHZ-SW100VHA-BS
PUHZ-SW100YHA-BS
PUHZ-SW120VHA-BS
PUHZ-SW120YHA-BS
Note:
This manual describes service data of the outdoor units only.
PUHZ-SW75VHA-BS.UK PUHZ-SW75VHAR3-BS.UK PUHZ-SW75VHAR4-BS.UK PUHZ-SW100VHA-BS.UK PUHZ-SW100VHAR3-BS.UK PUHZ-SW100VHAR4-BS.UK PUHZ-SW100YHA-BS.UK PUHZ-SW100YHAR1-BS.UK PUHZ-SW100YHAR3-BS.UK PUHZ-SW100YHAR4-BS.UK PUHZ-SW120VHA-BS.UK PUHZ-SW120VHAR3-BS.UK PUHZ-SW120VHAR4-BS.UK PUHZ-SW120YHA-BS.UK PUHZ-SW120YHAR1-BS.UK PUHZ-SW120YHAR3-BS.UK PUHZ-SW120YHAR4-BS.UK
Outdoor unit [Model Name]
PUHZ-SW75VHA
PUHZ-SW100VHA
PUHZ-SW100YHA
PUHZ-SW120VHA
PUHZ-SW120YHA
[Service ref.]
PUHZ-SW75VHA.UK PUHZ-SW75VHAR3.UK PUHZ-SW75VHAR4.UK PUHZ-SW100VHA.UK PUHZ-SW100VHAR3.UK PUHZ-SW100VHAR4.UK PUHZ-SW100YHA.UK PUHZ-SW100YHAR1.UK PUHZ-SW100YHAR3.UK PUHZ-SW100YHAR4.UK PUHZ-SW120VHA.UK PUHZ-SW120VHAR3.UK PUHZ-SW120VHAR4.UK PUHZ-SW120YHA.UK PUHZ-SW120YHAR1.UK PUHZ-SW120YHAR3.UK PUHZ-SW120YHAR4.UK
PARTS CATALOG (OCB533)
Revision:
Added PUHZ-SW75VHAR4.UK,
PUHZ-SW75VHAR4-BS.UK, PUHZ-SW100VHAR4.UK, PUHZ-SW100VHAR4-BS.UK, PUHZ-SW100YHAR4.UK, PUHZ-SW100YHAR4-BS.UK, PUHZ-SW120VHAR4.UK, PUHZ-SW120VHAR4-BS. UK, PUHZ-SW120YHAR4.UK and PUHZ-SW120YHAR4-BS.UK
in REVISED EDITION-D.
Some descriptions have been modified.
Please void OCH533 REVISED EDITION-C.
No. OCH533
REVISED EDITION-D
August 2015
SPLIT-TYPE, AIR TO WATER HEAT PUMP
2
PUHZ-SW100YHA(-BS).UK PUHZ-SW100YHAR1(-BS).UK PUHZ-SW120YHA(-BS).UK PUHZ-SW120YHAR1(-BS).UK
Power circuit board (P.B.) has been changed.
1 TECHNICAL CHANGES
PUHZ-SW75VHA(-BS).UK PUHZ-SW75VHAR3(-BS).UK
PUHZ-SW100VHA(-BS).UK PUHZ-SW100VHAR3(-BS).UK PUHZ-SW100YHAR1(-BS).UK PUHZ-SW100YHAR3(-BS).UK PUHZ-SW120VHA(-BS).UK PUHZ-SW120VHAR3(-BS).UK PUHZ-SW120YHAR1(-BS).UK PUHZ-SW120YHAR3(-BS).UK
Added a new function "Energy Monitor" which allows remote controller to display power consumption and heat output.
Service ref. have been changed as follows.
PUHZ-SW75VHAR3(-BS).UK PUHZ-SW75VHAR4(-BS).UK PUHZ-SW100VHAR3(-BS).UK PUHZ-SW100VHAR4(-BS).UK PUHZ-SW100YHAR3(-BS).UK PUHZ-SW100YHAR4(-BS).UK PUHZ-SW120VHAR3(-BS).UK PUHZ-SW120VHAR4(-BS).UK PUHZ-SW120YHAR3(-BS).UK PUHZ-SW120YHAR4(-BS).UK
A compliance with ErP directive Lot 1 has been authorized.
All circuit boards (C.B./P.B./N.F./CONV.B) have been changed (including a change of production site).
OCH533D
3
2
REFERENCE MANUAL
INDOOR UNIT SERVICE MANUAL
Model name Service ref. Service manual No.
EHST20C-VM6HB EHST20C-YM9HB EHST20C-TM9HB EHST20C-VM2B EHST20C-VM6B EHST20C-YM9B EHST20C-VM6EB EHST20C-YM9EB EHST20C-VM6SB
EHST20C-VM6HB.UK EHST20C-YM9HB.UK EHST20C-TM9HB.UK EHST20C-VM2B.UK EHST20C-VM6B.UK EHST20C-YM9B.UK EHST20C-VM6EB.UK EHST20C-YM9EB.UK EHST20C-VM6SB.UK
OCH531
EHSC-VM2B EHSC-VM6B EHSC-YM9B EHSC-TM9B EHSC-VM6EB EHSC-YM9EB ERSC-VM2B
EHSC-VM2B.UK EHSC-VM6B.UK EHSC-YM9B.UK EHSC-TM9B.UK EHSC-VM6EB.UK EHSC-YM9EB.UK ERSC-VM2B.UK
OCH532
EHST20C-VM2C EHST20C-VM6C EHST20C-YM9C EHST20C-TM9C EHST20C-VM2EC EHST20C-VM6EC EHST20C-YM9EC EHST20C-MHCW EHST20C-MEC ERST20C-VM2C ERST20C-MEC
EHST20C-VM2C(R1).UK EHST20C-VM6C(R1).UK EHST20C-YM9C(R1).UK EHST20C-TM9C(R1).UK EHST20C-VM2EC(R1).UK EHST20C-VM6EC(R1).UK EHST20C-YM9EC(R1).UK EHST20C-MHCW(R1).UK EHST20C-MEC(R1).UK ERST20C-VM2C(R1).UK ERST20C-MEC(R1).UK
OCH570
EHSC-MEC EHSC-VM2C EHSC-VM2EC EHSC-VM6C EHSC-VM6EC EHSC-YM9C EHSC-YM9EC EHSC-TM9C ERSC-MEC ERSC-VM2C
EHSC-MEC(R1).UK EHSC-VM2C(R1).UK EHSC-VM2EC(R1).UK EHSC-VM6C(R1).UK EHSC-VM6EC(R1).UK EHSC-YM9C(R1).UK EHSC-YM9EC(R1).UK EHSC-TM9C(R1).UK ERSC-MEC(R1).UK ERSC-VM2C(R1).UK
OCH571
OCH533D
4
3 SAFETY PRECAUTION
Cautions for units utilizing refrigerant R410A
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Use new refrigerant pipes.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contamination such as sulfur hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness.
Store the piping indoors, and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.
In case of using the existing pipes for R22, be careful with the following:
· Be sure to perform replacement operation before test run.
· Change flare nut to the one provided with this product. Use a newly flared pipe.
· Avoid using thin pipes.
Do not use refrigerant other than R410A.
If other refrigerant (R22, etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil, etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil, etc.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil, etc.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Use the specified refrigerant only.
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
3-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must disconnected.
Preparation before the repair service.
• Prepare the proper tools.
• Prepare the proper protectors.
• Provide adequate ventilation.
• After stopping the operation of the air conditioner, turn off the power-supply breaker.
• Discharge the condenser before the work involving the electric parts.
Precautions during the repair service.
• Do not perform the work involving the electric parts with wet hands.
• Do not pour water into the electric parts.
• Do not touch the refrigerant.
• Do not touch the hot or cold areas in the refrigerating cycle.
• When the repair or the inspection of the circuit needs to be done without turning off the power,
exercise great caution not to touch the live parts.
OCH533D
5
Gravimeter
Unit
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is a syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
No. Tool name Specifications
1
Gauge manifold · Only for R410A
· Use the existing fitting
specifications
. (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
2
Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3
Electronic scale
4
Gas leak detector
· Use the detector for R134a, R407C or R410A.
5
Adaptor for reverse flow check
· Attach on vacuum pump.
6
Refrigerant charge base
7
Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8
Refrigerant recovery equipment
OCH533D
6
3-3. PRECAUTIONS WHEN REUSING EXISTING R22 REFRIGERANT PIPES
Flowchart
Perform the airtight test, vacuum air purging, additional refrigerant charging (if necessary), and gas leak check.
• Refer to the owchart below to determine if the existing pipes can be used and if it is necessary to use a lter dryer.
• If the diameter of the existing pipes is different from the specied diameter, refer to technological data materials to conrm if the pipes can be used.
Measure the existing pipe thickness and check for damage.
The existing pipe thickness meets specica­tions and the pipes are not damaged.
Check if the existing outdoor unit can operate.
After operating the cooling system for about 30 minutes, do a pump down work.
Disconnect the existing outdoor unit from the pipes.
Attach the new outdoor unit
The existing pipes cannot be reused. Use new pipes.
• If the existing outdoor unit cannot operate, use
a refrigerant recovery device to collect the refrigerant.
Use new pipes for SW75, SW100 and SW120 models.
The existing pipe thickness does not meet
specications or the pipes are damaged.
3-4. PRECAUTIONS FOR SALT PROOF TYPE "-BS" MODEL
Although "-BS" model has been designed to be resistant to salt damage, observe the following precautions to maintain the per­formance of the unit.
1. Avoid installing the unit in a location where it will be exposed directly to seawater or sea breeze.
2. If the cover panel may become covered with salt, be sure to install the unit in a location where the salt will be washed away by rainwater. (If a sunshade is installed, rainwater may not clean the panel.)
3. To ensure that water does not collect in the base of the outdoor unit, make sure that the base is level, not at angle. Water collecting in the base of the outdoor unit could cause rust.
4. If the unit is installed in a coastal area, clean the unit with water regularly to remove any salt build-up.
5. If the unit is damaged during installation or maintenance, be sure to repair it.
6. Be sure to check the condition of the unit regularly.
7. Be sure to install the unit in a location with good drainage.
OCH533D
7
Cautions for refrigerant piping work
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
1 Thickness of pipes Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7mm or below.)
2 Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrig­erants. Therefore, to enhance airtightness and strength, flare cutting dimension of copper pipe for R410A has been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also has partly been changed to increase strength as shown below. Set copper pipe correctly referring to copper pipe flaring dimensions for R410A below. For 1/2 and 5/8 inch pipes, the dimension B changes. Use torque wrench corresponding to each dimension.
3 Tools for R410A (The following table shows whether conventional tools can be used or not.)
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
0.8
0.8
0.8
1.0
0.8
0.8
0.8
1.0
1.0
Nominal
dimensions(inch)
Diagram below: Piping diameter and thickness
Outside
diameter
(mm)
Thickness
(mm)
R410A R22
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
9.1
13.2
16.6
19.7
9.0
13.0
16.2
19.4
23.3
Nominal
dimensions(inch)
Flare cutting dimensions
Outside
diameter
Dimension A
( )
+0
-0.4
(mm)
R410A R22
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
17.0
22.0
26.0
29.0
17.0
22.0
24.0
27.0
36.0
Nominal
dimensions(inch)
Flare nut dimensions
Outside
diameter
Dimension B
(mm)
R410A R22
Gauge manifold Charge hose Gas leak detector
Refrigerant recovery equipment Refrigerant cylinder Applied oil
Safety charger
Charge valve
Vacuum pump
Flare tool
Bender Pipe cutter Welder and nitrogen gas cylinder Refrigerant charging scale Vacuum gauge or thermis­tor vacuum gauge and vacuum valve Charging cylinder
Air purge, refrigerant charge and operation check Gas leak check Refrigerant recovery Refrigerant charge Apply to flared section
Prevent compressor malfunction when charging refrigerant by
spraying liquid refrigerant Prevent gas from blowing out
when detaching charge hose Vacuum drying and air purge
Flaring work of piping
Bend the pipes Cut the pipes Weld the pipes Refrigerant charge Check the degree of vacuum. (Vacuum valve prevents back flow of oil and refri­gerant to thermistor vacuum gauge) Refrigerant charge
Tool exclusive for R410A Tool exclusive for R410A Tool for HFC refrigerant Tool exclusive for R410A Tool exclusive for R410A Ester oil and alkylbenzene oil (minimum amount) Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can be used if equipped with adap­ter for reverse flow check Tools for other refrigerants can be used by adjusting flaring dimension Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used
Tool exclusive for R410A
Tools and materials Use R410A tools Can R22 tools be used?
(Usable if equipped with adapter for rever­ se flow)
(Usable by adjusting flaring dimension)
Can R407C tools be used?
Ester oil: Alkylbenzene oil: minimum amount
(Usable if equipped with adapter for rever­ se flow)
(Usable by adjusting flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) : Tools for other refrigerants can be used under certain conditions. : Tools for other refrigerants can be used.
Dimension A
Dimension B
OCH533D
8
4 FEATURES
PUHZ-SW75VHA PUHZ-SW75VHA-BS
CHARGELESS SYSTEM PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT. (Maximum 10 m (PUHZ-SW75–120))
The refrigerant circuit with LEV (Linear Expansion Valve) and accumulator always control the optimal refrigerant level regard­less of the length (10 m maximum and 5 m minimum) of piping. The additional refrigerant charging work during installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality and reliability of the work done. It also helps to speed up the installation time.
PUHZ-SW100VHA PUHZ-SW100YHA PUHZ-SW120VHA PUHZ-SW120YHA PUHZ-SW100VHA-BS PUHZ-SW100YHA-BS PUHZ-SW120VHA-BS PUHZ-SW120YHA-BS
OCH533D
9
5 SPECIFICATIONS
<Reference data> Plate heat exchanger (ACH70-40 plates)
Nominal water ow L/min 22.9
Heating (A7/W35)
Capacity kW 8.00
COP 4.40
Power input kW 1.82
Heating (A7/W45)
Capacity kW 8.00
COP 3.40
Power input kW 2.35
Heating (A2/W35)
Capacity kW 7.50
COP 3.40
Power input kW 2.20
Heating (A2/W45)
Capacity kW 7.50
COP 2.83
Power input kW 2.65
Nominal water ow L/min 18.9
Cooling (A35/W7)
Capacity kW 6.60
EER 2.55
Power input kW 2.59
Cooling (A35/W18)
Capacity kW 7.10
EER 4.01
Power input kW 1.77
Rating conditions
Nominal operating condition
Heating (A7/W35)
Outside air temperature (Dry-bulb) + 7°C
Outside air temperature (Wet-bulb) + 6°C
Water temperature (inlet/outlet) + 30°C/+ 35°C
Heating (A7/W45)
Outside air temperature (Dry-bulb) + 7°C
Outside air temperature (Wet-bulb) + 6°C
Water temperature (inlet/outlet) + 40°C/+ 45°C
Heating (A2/W35)
Outside air temperature (Dry-bulb) + 2°C
Outside air temperature (Wet-bulb) + 1°C
Water temperature (inlet/outlet) + 30°C/+ 35°C
Heating (A2/W45)
Outside air temperature (Dry-bulb) + 2°C
Outside air temperature (Wet-bulb) + 1°C
Water temperature (inlet/outlet) + 40°C/+ 45°C
Cooling (A35/W7)
Outside air temperature (Dry-bulb) + 35°C
Outside air temperature (Wet-bulb) + 24°C
Water temperature (inlet/outlet) + 12°C/+ 7°C
Cooling (A35/W18)
Outside air temperature (Dry-bulb) + 35°C
Outside air temperature (Wet-bulb) + 24°C
Water temperature (inlet/outlet) + 23°C/+ 18°C
Note: "COP" and "Power input" in the above table do NOT contain the "pump input (based on EN 14511)".
Nominal water ow L/min 32.1
Heating (A7/W35)
Capacity kW 11.2
COP 4.45
Power input kW 2.51
Heating (A7/W45)
Capacity kW 11.2
COP 3.42
Power input kW 3.27
Heating (A2/W35)
Capacity kW 10.0
COP 3.32
Power input kW 3.02
Heating (A2/W45)
Capacity kW 10.0
COP 2.66
Power input kW 3.76
Nominal water ow L/min 26.1
Cooling (A35/W7)
Capacity kW 9.10
EER 2.75
Power input kW 3.31
Cooling (A35/W18)
Capacity kW 10.0
EER 4.35
Power input kW 2.30
PUHZ-SW75VHA(-BS).UK PUHZ-SW75VHAR3(-BS).UK
PUHZ-SW100VHA(-BS).UK PUHZ-SW100VHAR3(-BS).UK PUHZ-SW100YHA(-BS).UK PUHZ-SW100YHAR1/R3(-BS).UK
PUHZ-SW120VHA(-BS).UK PUHZ-SW120VHAR3(-BS).UK PUHZ-SW120YHA(-BS).UK PUHZ-SW120YHAR1/R3(-BS).UK
Nominal water ow L/min 45.9
Heating (A7/W35)
Capacity kW 16.0
COP 4.10
Power input kW 3.90
Heating (A7/W45)
Capacity kW 16.0
COP 3.23
Power input kW 4.95
Heating (A2/W35)
Capacity kW 12.0
COP 3.24
Power input kW 3.70
Heating (A2/W45)
Capacity kW 12.0
COP 2.52
Power input kW 4.76
Nominal water ow L/min 35.8
Cooling (A35/W7)
Capacity kW 12.5
EER 2.32
Power input kW 5.38
Cooling (A35/W18)
Capacity kW 14.0
EER 4.08
Power input kW 3.43
OCH533D
10
Nominal water ow L/min 22.9
Heating (A7/W35)
Capacity kW 8.00
COP 4.40
Power input kW 1.82
Heating (A7/W45)
Capacity kW 8.00
COP 3.40
Power input kW 2.35
Heating (A2/W35)
Capacity kW 7.50
COP 3.40
Power input kW 2.20
Heating (A2/W45)
Capacity kW 7.50
COP 2.83
Power input kW 2.65
Nominal water ow L/min 18.9
Cooling (A35/W7)
Capacity kW 6.60
EER 2.86
Power input kW 2.31
Cooling (A35/W18)
Capacity kW 7.10
EER 4.43
Power input kW 1.60
Rating conditions
Nominal operating condition
Heating (A7/W35)
Outside air temperature (Dry-bulb) + 7°C
Outside air temperature (Wet-bulb) + 6°C
Water temperature (inlet/outlet) + 30°C/+ 35°C
Heating (A7/W45)
Outside air temperature (Dry-bulb) + 7°C
Outside air temperature (Wet-bulb) + 6°C
Water temperature (inlet/outlet) + 40°C/+ 45°C
Heating (A2/W35)
Outside air temperature (Dry-bulb) + 2°C
Outside air temperature (Wet-bulb) + 1°C
Water temperature (inlet/outlet) + 30°C/+ 35°C
Heating (A2/W45)
Outside air temperature (Dry-bulb) + 2°C
Outside air temperature (Wet-bulb) + 1°C
Water temperature (inlet/outlet) + 40°C/+ 45°C
Cooling (A35/W7)
Outside air temperature (Dry-bulb) + 35°C
Outside air temperature (Wet-bulb) + 24°C
Water temperature (inlet/outlet) + 12°C/+ 7°C
Cooling (A35/W18)
Outside air temperature (Dry-bulb) + 35°C
Outside air temperature (Wet-bulb) + 24°C
Water temperature (inlet/outlet) + 23°C/+ 18°C
Nominal water ow L/min 32.1
Heating (A7/W35)
Capacity kW 11.2
COP 4.45
Power input kW 2.51
Heating (A7/W45)
Capacity kW 11.2
COP 3.42
Power input kW 3.27
Heating (A2/W35)
Capacity kW 10.0
COP 3.32
Power input kW 3.01
Heating (A2/W45)
Capacity kW 10.0
COP 2.66
Power input kW 3.76
Nominal water ow L/min 26.1
Cooling (A35/W7)
Capacity kW 9.10
EER 2.75
Power input kW 3.31
Cooling (A35/W18)
Capacity kW 10.0
EER 4.35
Power input kW 2.30
PUHZ-SW75VHAR4(-BS).UK
PUHZ-SW100VHAR4(-BS).UK PUHZ-SW100YHAR4(-BS).UK
PUHZ-SW120VHAR4(-BS).UK PUHZ-SW120YHAR4(-BS).UK
Nominal water ow L/min 45.9
Heating (A7/W35)
Capacity kW 16.0
COP 4.10
Power input kW 3.90
Heating (A7/W45)
Capacity kW 16.0
COP 3.23
Power input kW 4.95
Heating (A2/W35)
Capacity kW 12.0
COP 3.24
Power input kW 3.70
Heating (A2/W45)
Capacity kW 12.0
COP 2.52
Power input kW 4.76
Nominal water ow L/min 35.8
Cooling (A35/W7)
Capacity kW 12.5
EER 2.32
Power input kW 5.39
Cooling (A35/W18)
Capacity kW 14.0
EER 4.08
Power input kW 3.43
OCH533D
11
A
kW
W
kW
K
/min(CFM
)
dB
dB mm (in) mm (in) mm (in)
kg (lb)
kg (lb)
L mm (in) mm (in)
Power supply (phase, cycle, voltage) Max. current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices
Crankcase heater Heat exchanger Fan Fan(drive) o No. Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant Charge Oil (Model) Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Service Ref.
PUHZ-SW75VHA-BS.UK PUHZ-SW75VHAR3-BS.UK
PUHZ-SW75VHA.UK PUHZ-SW75VHAR3.UK
TNB220FLHMT
Propeller fan o 1
0.074
55(1,940)
48 51
943(37-1/8)
75(165)
3.2(7.0)
0.87(FV50S)
2 to 40 m
Munsell 3Y 7.8/1.1
Linear Expansion Valve
Hermetic
Inverter
Plate fin coil
Reverse cycle
950(37-3/8)
330+30(13+1-3/16)
R410A
9.52(3/8)
15.88(5/8) Flared Flared
Maximum 10 m
HP switch
Comp. surface thermo
Discharge thermo
Over current detection
Single, 50Hz, 230V
OUTDOOR UNIT
REFRIGERANT PIPING
1.3
19
A
kW
W
kW
K
/min(CFM
)
dB
dB mm (in) mm (in) mm (in)
kg (lb)
kg (lb)
L mm (in) mm (in)
Power supply (phase, cycle, voltage) Max. current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices
Crankcase heater Heat exchanger Fan Fan(drive) o No. Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant Charge Oil (Model) Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Cooling
Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Service Ref.
PUHZ-SW75VHAR4-BS.UK
PUHZ-SW75VHAR4.UK
SNB220FAGMC-L1
Propeller fan o 1
0.074
55(1,940)
48 51
943(37-1/8)
75(166)
3.2(7.0)
0.60(FV50S)
2 to 40 m
Munsell 3Y 7.8/1.1
Linear Expansion Valve
Hermetic
Inverter
Plate fin coil
Reverse cycle
950(37-13/32)
330+30(13+1-3/16)
R410A
9.52(3/8)
15.88(5/8) Flared Flared
Maximum 30 m
HP switch
Comp. surface thermo
Discharge thermo
Over current detection
Single, 50Hz, 230V
OUTDOOR UNIT
REFRIGERANT PIPING
1.5
17
OCH533D
12
3 phase, 50Hz, 400V
13
Munsell 3Y 7.8/1.1
Linear Expansion Valve
Hermetic
Inverter
Plate fin coil
Propeller fan o 2
0.074+0.074 100(3,353)
Reverse cycle
950(37-13/32)
330+30(13+1-3/16)
1,350(53-1/8)
130(287)
R410A
4.6(10.1)
1.40(FV50S)
9.52(3/8)
15.88(5/8) Flared Flared
Maximum 30 m
2 to 75 m
A
kW
W
kW
K
/min(CFM
)
dB dB
m (in) mm (in) mm (in)
kg (lb)
kg (lb)
L mm (in) mm (in)
Power supply (phase, cycle, voltage) Max. current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices
Crankcase heater Heat exchanger Fan Fan(drive) o No. Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Service Ref.
OUTDOOR UNIT
REFRIGERANT PIPING
ANB33FNDMT
2.5
ANB42FNDMT
2.5
HP switch LP switch
Discharge thermo
Comp.surface thermo
Over current detection
50 54
51 54
PUHZ-SW100YHA.UK
PUHZ-SW120YHA.UK PUHZ-SW100YHAR3.UK PUHZ-SW120YHAR3.UK PUHZ-SW100YHAR4.UK PUHZ-SW120YHAR4.UK
PUHZ-SW120YHA-BS.UK PUHZ-SW120YHAR3-BS.UK PUHZ-SW120YHAR4-BS.UK
PUHZ-SW100YHA-BS.UK PUHZ-SW100YHAR3-BS.UK PUHZ-SW100YHAR4-BS.UK
A
kW
W
kW
K
/min(CFM
)
dB dB
m (in) mm (in) mm (in)
kg (lb)
kg (lb)
L mm (in) mm (in)
Power supply (phase, cycle, voltage) Max. current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices
Crankcase heater Heat exchanger Fan Fan(drive) o No. Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Service Ref.
50 54
Munsell 3Y 7.8/1.1
Linear Expansion Valve
Hermetic
Inverter
Plate fin coil
Propeller fan o 2
0.074+0.074 100(3,353)
Reverse cycle
950(37-13/32)
330+30(13+1-3/16)
1,350(53-1/8)
118(261)
R410A
4.6(10.2)
1.40(FV50S)
9.52(3/8)
15.88(5/8) Flared Flared
Maximum 30 m
2 to 75 m
29.5
HP switch
LP switch
Discharge thermo Comp. surface thermo Over current detection
Single 50Hz, 230V
OUTDOOR UNIT
REFRIGERANT PIPING
51 54
ANB42FNEMT
2.5
ANB33FNEMT
2.5
PUHZ-SW100VHAR4.UK
PUHZ-SW120VHAR4.UK
PUHZ-SW100VHA.UK PUHZ-SW120VHA.UK
PUHZ-SW100VHAR3.UK
PUHZ-SW120VHAR3.UK
PUHZ-SW100VHAR4-BS.UK
PUHZ-SW100VHA-BS.UK
PUHZ-SW100VHAR3-BS.UK
PUHZ-SW120VHAR4-BS.UK
PUHZ-SW120VHA-BS.UK
PUHZ-SW120VHAR3-BS.UK
OCH533D
13
6 DATA
6-1. REFILLING REFRIGERANT CHARGE (R410A : kg)
6-2. COMPRESSOR TECHNICAL DATA
Service Ref.
Piping length (one way)
Initial
charged
10 m 20 m 30 m 40 m 50 m 60 m 75 m
PUHZ-SW75VHA(-BS).UK PUHZ-SW75VHAR3(-BS).UK
3.2 3.6 4.0 4.6 3.2
PUHZ-SW75VHAR4(-BS).UK 3.2 3.35 3.5 4.1 3.2
PUHZ-SW100VHA(-BS).UK PUHZ-SW100VHAR3(-BS).UK PUHZ-SW100YHA(-BS).UK PUHZ-SW100YHAR1(-BS).UK PUHZ-SW100YHAR3(-BS).UK
4.6 4.8 5.0 5.6 6.2 6.8 7.4 4.6
PUHZ-SW100V/YHAR4(-BS).UK
4.6 4.8 5.0 5.6 6.2 6.8 7.5 4.6
PUHZ-SW120VHA(-BS).UK PUHZ-SW120VHAR3(-BS).UK PUHZ-SW120YHA(-BS).UK PUHZ-SW120YHAR1(-BS).UK PUHZ-SW120YHAR3(-BS).UK
4.6 4.8 5.0 5.6 6.2 6.8 7.4 4.6
PUHZ-SW120V/YHAR4(-BS).UK
4.6 4.8 5.0 5.6 6.2 6.8 7.5 4.6
U-V
U-W
W-V
Service Ref.
Compressor model
Winding
Resistance
( " )
U-V
U-W
W-V
Service Ref.
Compressor model
Winding
Resistance
( " )
ANB33FNEMT
(at 20°C)
(at 20°C)
0.19
0.19
0.19
PUHZ-SW100VHA.UK PUHZ-SW100VHAR3.UK PUHZ-SW100VHAR4.UK
PUHZ-SW100VHA-BS.UK PUHZ-SW100VHAR3-BS.UK PUHZ-SW100VHAR4-BS.UK
SNB220FAGMC-L1
0.95
0.95
0.95
PUHZ-SW75VHAR4.UK
PUHZ-SW75VHAR4-BS.UK
ANB33FNDMT
0.30
0.30
0.30
ANB42FNDMT
ANB42FNEMT
0.30
0.30
0.30
TNB220FLHMT
0.88
0.88
0.88
PUHZ-SW75VHA.UK
PUHZ-SW75VHAR3.UK
PUHZ-SW75VHA-BS.UK
PUHZ-SW75VHAR3-BS.UK
PUHZ-SW100YHA.UK PUHZ-SW100YHAR1.UK PUHZ-SW100YHAR3.UK PUHZ-SW100YHAR4.UK
PUHZ-SW100YHA-BS.UK PUHZ-SW100YHAR1-BS.UK PUHZ-SW100YHAR3-BS.UK PUHZ-SW100YHAR4-BS.UK
PUHZ-SW120YHA.UK PUHZ-SW120YHAR1.UK PUHZ-SW120YHAR3.UK PUHZ-SW120YHAR4.UK
PUHZ-SW120YHA-BS.UK PUHZ-SW120YHAR1-BS.UK PUHZ-SW120YHAR3-BS.UK PUHZ-SW120YHAR4-BS.UK
PUHZ-SW120VHA.UK PUHZ-SW120VHAR3.UK PUHZ-SW120VHAR4.UK
PUHZ-SW120VHA-BS.UK PUHZ-SW120VHAR3-BS.UK PUHZ-SW120VHAR4-BS.UK
0.19
0.19
0.19
Additional charge is required for pipes longer than 10 m.
OCH533D
14
6-3. NOISE CRITERION CURVES
1.5m
1m
MICROPHONE
UNIT
GROUND
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
PUHZ-SW75VHA(-BS).UK PUHZ-SW75VHAR3(-BS).UK PUHZ-SW75VHAR4(-BS).UK
COOLING
MODE
HEATING
48
SPL(dB)
51
LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
PUHZ-SW100VHA(-BS).UK PUHZ-SW100VHAR3(-BS).UK PUHZ-SW100VHAR4(-BS).UK PUHZ-SW100YHA(-BS).UK PUHZ-SW100YHAR1(-BS).UK PUHZ-SW100YHAR3(-BS).UK PUHZ-SW100YHAR4(-BS).UK
COOLING
MODE
HEATING
50
SPL(dB)
54
LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
PUHZ-SW120VHA(-BS).UK PUHZ-SW120VHAR3(-BS).UK PUHZ-SW120VHAR4(-BS).UK PUHZ-SW120YHA(-BS).UK PUHZ-SW120YHAR1(-BS).UK PUHZ-SW120YHAR3(-BS).UK PUHZ-SW120YHAR4(-BS).UK
COOLING
MODE
HEATING
51
SPL(dB)
54
LINE
OCH533D
15
7 OUTLINES AND DIMENSIONS
Unit : mm
Air Intake
Rear Air Intake
Handle for moving
Handle for moving
322
950
473
943
23
*1 447
*1 431
A
2
1
Handle for moving
Handle for moving
Service panel
Earth terminal
Left···Power supply wiring
Right···Indoor/Outdoor wiring
Terminal Connections
Rear piping cover
Front piping cover
Side Air Intake
Handle for moving
40
54
28 370 19
417
53
57 41
600 175175
330
Rear Air Intake
Air Discharge
Side Air Intake
Installation Feet
2-U Shaped notched holes
(Foundation Bolt M10)
2-12 o 36 oval holes
(Foundation Bolt M10)
30
220 145 145 14530
81 219
71
71
Bottom piping hole
(Knockout)
Drain hole
(5-[33)
Piping Knockout Hole Details
19 55
23 27 92
92
4075
73 63
Right piping hole
(Knockout)
Right trunking hole
(Knockout)
Power supply wiring hole
(2-[27Knockout)
[92
27 55
7323 63
40
92
65
45
Front piping hole
(Knockout)
Front trunking hole
(Knockout)
Power supply wiring hole
(2-[27Knockout)
[92
4045
65
92
27 55
23 73 63
Rear piping hole
(Knockout)
Rear trunking hole
(Knockout)
Power supply wiring hole
(2-[27Knockout)
[92
Example of Notes
1 Refrigerant GAS pipe connection (FLARE)[15.88(5/8 inch)
2 Refrigerant LIQUID pipe connection (FLARE)[9.52(3/8 inch)
*1...Indication of STOP VALVE connection location.
Over
Over
Less than
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
3 FOUNDATION BOLTS2 SERVICE SPACE
1 FREE SPACE (Around the unit)
The diagram below shows a
basic example.
Explanation of particular details is
given in the installation manuals etc.
Over10
500
500
Over100
Dimensions of space needed
for service access are
shown in the below diagram.
Service space
30
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
<Foundation bolt height>
FOUNDATION
over 100mm
over 500mm
over 10mm
FREE
over 10mm
VHA/R3
VHAR4
673A670
PUHZ-SW75VHA.UK PUHZ-SW75VHAR3.UK PUHZ-SW75VHAR4.UK PUHZ-SW75VHA-BS.UK PUHZ-SW75VHAR3-BS.UK PUHZ-SW75VHAR4-BS.UK
OCH533D
16
Handle for moving
Side Air Intake
Front piping cover
Rear piping cover
Air intake
Rear Air Intake
Handle for moving
Handle for moving
Terminal connection
Left···Power supply wiring
Right···Indoor/Outdoor wiring
Earth terminal
Service panel
Handle for moving
1
2
Air Discharge
Rear Air Intake
Side Air Intake
1····Refrigerant GAS pipe connection (FLARE){15.88(5/8 inch)
2····Refrigerant LIQUID pipe connection (FLARE){ 9.52(3/8 inch)
*1 ···Indication of STOP VALVE connection location.
Example of Notes
Piping Knockout Hole Details
600175 175
330
417
42
66
53 56
45
(19)28 370
2-U Shaped notched holes
(Foundation Bolt M10)
2-12 x 36 Oval holes
(Foundation Bolt M10)
Installation Feet
30
45 40
65
92
27 55
23 73 63
Rear piping hole
(Knockout)
Rear trunking hole
(Knockout)
Power supply wiring hole
(2-
{
27Knockout)
{
92
19 55
92
75 40
73 63 23 27 92
Right piping hole
(Knockout)
Right trunking hole
(Knockout)
Power supply wiring hole
(2-
{
27Knockout)
{
92
92
65
4540
27 55
23
73 63
Front piping hole
(Knockout)
Front trunking hole
(Knockout)
Power supply wiring hole
(2-
{
27Knockout)
{
92
14514522030 145
81 219
71
71
Bottom piping hole
(Knockout)
Drain hole
(5-{33)
1350
23
950
A
*1 447
*1 431
371 635
322
Handle for moving
VHA
YHA
1,079
A
930
Unit : mm
Over
Over
Over
Over
Less than
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
3 FOUNDATION BOLTS2 SERVICE SPACE
1 FREE SPACE (Around the unit)
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
<Foundation bolt height>
Dimensions of space needed
for service access are
shown in the below diagram.
The diagram below shows a
basic example.
Explanation of particular details is
given in the installation manuals etc.
30
FOUNDATION
10
500
500
150
Service space
FREE
Over 10mm
Over 10mm
Over 150mm
Over 1000mm
PUHZ-SW100VHA.UK
PUHZ-SW100VHAR3.UK PUHZ-SW100VHAR4.UK
PUHZ-SW100VHA-BS.UK
PUHZ-SW100VHAR3-BS.UK PUHZ-SW100VHAR4-BS.UK
PUHZ-SW100YHA.UK
PUHZ-SW100YHAR1.UK PUHZ-SW100YHAR3.UK PUHZ-SW100YHAR4.UK
PUHZ-SW100YHA-BS.UK
PUHZ-SW100YHAR1-BS.UK PUHZ-SW100YHAR3-BS.UK PUHZ-SW100YHAR4-BS.UK
PUHZ-SW120VHA.UK
PUHZ-SW120VHAR3.UK PUHZ-SW120VHAR4.UK
PUHZ-SW120VHA-BS.UK
PUHZ-SW120VHAR3-BS.UK PUHZ-SW120VHAR4-BS.UK
PUHZ-SW120YHA.UK
PUHZ-SW120YHAR1.UK PUHZ-SW120YHAR3.UK
PUHZ-SW120YHAR4.UK
PUHZ-SW120YHA-BS.UK
PUHZ-SW120YHAR1-BS.UK PUHZ-SW120YHAR3-BS.UK PUHZ-SW120YHAR4-BS.UK
OCH533D
17
8 WIRING DIAGRAM
BH79B652H01
PUHZ−SW75VHA WIRING DIAGRAM
1 2 3 4 5 6 7 8
OFF
ON
75V
MODEL
SW6
*
1 MODEL SELECT
The black square ( ) indicates a switch position.
SW5-6
*
2
OFF
ON
1 2 3 4 5 6
*
2 SW5 -1 to 5 : Function Switch
SYMBOL NAME SYMBOL NAME SYMBOL NAME TB1 MC MF1 21S4 63H 63HS TH3 TH4 TH6 TH7 TH8 TH34 LEV-A, LEV-B ACL CY1, CY2
Terminal Block <Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch High Pressure Sensor Thermistor <Liquid> Thermistor <Discharge> Thermistor <2-Phase Pipe> Thermistor <Ambient> Thermistor <Heat Sink> Thermistor <Comp. Surface> Linear Expansion Valve Reactor Capacitor
P. B.
N. F.
C. B.
Power Circuit Board Connection Terminal <L/N-Phase> Connection Terminal <U/V/W-Phase> Power Module Converter Main Smoothing Capacitor Noise Filter Circuit Board Connection Terminal <L-Phase> Connection Terminal <N-Phase> Connection Terminal <Ground> 52C Relay Controller Circuit Board Switch <Manual Defrost, Defect History, Record Reset, Refrigerant Address> Switch <Test Operation>
R, S U, V, W IPM PFC CB1, CB2, CB3
LI, LO NI, NO EI, E2, E3 52C
SW1
SW4
SW5 SW6 SW7 SW8 SW9 SWP CN31 CNDM CN51 SV1/CH SS CNM LED1, LED2 F1, F2, F3, F4 X51, X52, X54
Switch <Function Switch, Model Select> Switch <Model Select> Switch <Function Switch> Switch <Function Switch> Switch <Function Switch> Switch <Pump Down> Connector <Emergency Operation> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> LED <Operation Inspection Indicators> Fuse <T6.3AL250V> Relay
C. B.
P. B.
TH8
TH6TH7 TH4TH3
U
CB3
N. F.
21S4
L N S1 S2 S3
INDOOR
UNIT
POWER SUPPLY
~/N 230V 50Hz
TB1
V
W
5
2
2
2
2
RED
WHT
BLK
t° t° t°
M C
CN5
(RED)
CNAC2
(RED)
CNAC1
(WHT)
LO N O
LI N I
EI
CN52C
(BLK)
3
1
1
3
2
1
1
2
52C
CN2
(WHT)
CN3
(WHT)
CN5
(RED)
CN4
(WHT)
1
7
1 2
1 2
2
1
LEV-A
CNS
(WHT)
CNAC (WHT)
CNDC (PNK)
F2
F1
F3
F4
21S4
(GRN)
CN2
(WHT)
CN4
(WHT)
CN3S
(WHT)
TH7/6 (RED)
TH3
(WHT)
TH4
(WHT)
TR AN S
C NV M NT
(WHT)
C NM N T
(WHT)
C NM
(WHT)
LED1
LED2
X52
SV1 /CH
(GRY)
X54
63H
(YLW)
CN52C
(RED)
2
5
2
1 4 1 2 2 1
1
3
31 1 5
1
14
1
3
1 3
1 2
1 7
3
1
13
1 2
3 4
31 31
LE V-A (WHT)
51
MS
3~
CB2CB1
R
S
U
V
W
PFC
IPM
AC L
E3E2
RED
BLU
RE D
W H T
RE D
W H T
YLW
ORN
BRN
RE D
W H T
RE D
W H T
CY1 CY2
GRN/YLW
SS
(WHT)
X51
31
MS 3~
MF1
CNF1 (WHT)
1
7
63H
31
TH34
2 1 TH34 (RED)
63HS
(WHT)
63HS
LE V-B (RED)
M
LEV-B
51
M
CNDM
(WHT)
CN51
(WHT)
1
3 1
5
C NF2 (WHT)
1
7
63L
(RED)
1 3
+ + +
SW7
SW6SW1
SW9
CN31
*1*
1
SW5SW8SW4 SWP
PUHZ-SW75VHA.UK PUHZ-SW75VHAR3.UK PUHZ-SW75VHA-BS.UK PUHZ-SW75VHAR3-BS.UK
OCH533D
18
PUHZ-SW75VHAR4.UK PUHZ-SW75VHAR4-BS.UK
SYMBOL NAME SYMBOL NAME TB1 MC MF1 21S4 63H 63HS TH3 TH4 TH6 TH7 TH8 TH34 LEV-A, LEV-B ACL CY1, CY2 P. B.
Terminal Block <Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (4-Way Valve) High Pressure Switch High Pressure Sensor Thermistor <Liquid> Thermistor <Discharge> Thermistor <2-Phase Pipe> Thermistor <Ambient> Thermistor <Heat Sink> Thermistor <Comp. Surface> Linear Expansion Valve Reactor Capacitor Power Circuit Board
C. B. Controller Circuit Board
Fuse <T6.3AL250V> Switch <Manual Defrost, Defect History Record Reset, Refrigerant Address> Switch <Function Switch> Switch <Function Switch, Model Select> Switch <Model Select> Switch <Function Switch> Switch <Function Switch> Switch <Function Switch> Switch <Pump Down> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option>
F1, F2, F3, F4
SW1
SW4 SW5 SW6 SW7 SW8 SW9 SWP CNDM SV1/CH SV3/SS CNM
1 2 3 4 5 6 7 8
OFF
ON
75V
MODEL
SW6
*
1 MODEL SELECT
The black square ( ) indicates a switch position.
SW5-6
*
2
OFF
ON
1 2 3 4 5 6
*
2 SW5 -1 to 5 : Function Switch
C. B.
P. B.
TH8
TH6TH7 TH4TH3
U
21S4
L N S1 S2 S3
TO
INDOOR UNIT
POWER SUPPLY
~/N 230V 50Hz
TB1
V
W
2
2
CY2
CY1
t° t°
MC
CNAC2
(RD)
S/N1 R/L1
CN2 (RD)
CNDC
(PK)
CN4 (WH)
CN6 (WH)
1
7
1
1
3
3
CNAC1
(WH)
1
3
121
LEV-A
CNS (WH)
CNAC
(WH)
CNDC
(PK)
F2
F1
F3
F4
21S4 (GN)
CN4 (WH)
TH7/6
(RD)
TH3
(WH)
TH4
(WH)
TR AN S
C NM (WH)
LED1
LED2
X52
SV1/CH
(GY)
X54
63H (YE)
2
1 4 1 2 2 1
1
3
1
14
1
3
1 3
1 2
7
3
1
13
1
2
3 4
7
1
31
LE V-A
(WH)
51
MS
3~
Uo
Vo
Wo
AC L
E3
EI
E4
RD
WH
RD
BK
WH
YE
OG
BN
BK
BK
BK
DB2
DB1
TBL2TBL4
GNYE
SV3/SS
(WH)
X51
31
MS
3~
MF1
CNF1 (WH)
1
7
63H
31
TH34
2 1
TH34
(RD)
63HS (WH)
63HS
LE V-B
(RD)
M
LEV-B
51
M
CNDM
(WH)
+
+
+
~
~
~
~
~
~
+
IC710
Q600
DB3
7
CN2 (RD)
*1 *1
SW7
SW6SW1
SW9
SW5SW8SW4 SWP
OCH533D
19
PUHZ-SW100VHA.UK PUHZ-SW100VHAR3.UK PUHZ-SW100VHA-BS.UK PUHZ-SW100VHAR3-BS.UK PUHZ-SW120VHA.UK PUHZ-SW120VHAR3.UK PUHZ-SW120VHA-BS.UK PUHZ-SW120VHAR3-BS.UK
BH79B653H01
100V
120V
SYMBOL NAME SYMBOL NAME SYMBOL NAME TB1 MC MF1, MF2 21S4 63H 63L 63HS TH3 TH4 TH6 TH7 TH8 TH34 LEV-A, LEV-B DCL CB CY1, CY2
Terminal Block <Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch High Pressure Sensor Thermistor <Liquid> Thermistor <Discharge> Thermistor <2-Phase Pipe> Thermistor <Ambient> Thermistor (internal) <Heat Sink> Thermistor <Comp. Surface> Linear Expansion Valve Reactor Main Smoothing Capacitor Capacitor
P. B. Power Circuit Board
Connection Terminal <U/V/W-Phase> Connection Terminal <L-Phase> Connection Terminal <N-Phase> Connection Terminal Connection Terminal Connection Terminal <Reactor> Power Module Connection Terminal <Ground> 52C Relay Controller Circuit Board Switch <Manual Defrost, Defect History, Record Reset, Refrigerant Address> Switch <Test Operation> Switch <Function Switch, Model Select> Switch <Model Select>
SW7 SW8 SW9 SWP CN31 CNDM CN51 SV1/CH SS CNM LED1, LED2 F1, F2, F3, F4 X51, X52, X54
Switch <Function Switch> Switch <Function Switch> Switch <Function Switch> Switch <Pump Down> Connector <Emergency Operation> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> LED <Operation Inspection Indicators> Fuse <T6.3AL250V> Relay
U, V, W LI NI P2 N2 DCL1, DCL2 IGBT EI, E2, E3, E4 52C
C. B.
SW1
SW4 SW5 SW6
POWER SUPPLY ~/N 230V 50Hz
INDOOR UNIT
P. B.
W
DCL
C B
L N S1 S2 S3
TB1
V
U
2
RED
WHT
BLK
MC
C N2
(WHT)
C N4
(WHT)
1 7
21
3 1
RED
BLU
YLW
ORN
BRN
WHT
RED
GRN/YLW
B LK
(RED)
CNAC2
(WHT)
CNAC1
LINI
EI
E3
CN52C
(RED)
3
1
1
3
52C
52C
1 3
DCL1
DCL2
+
P2
N2
+
-
UVW
CNDC
(PNK)
+
B LK
2
MS
3~
E2
B LK
E4
B LK
CY1 CY2
IGBT
RE D W H T
C. B.
TH6TH7 TH4TH3
21S4
t° t°
LEV-A
CNS
(WHT)
CNAC
(WHT)
CNDC (PNK)
F2
F1
F3
F4
21S4
(GRN)
CN2
(WHT)
C N4
(WHT)
TH7/6 (RED)
TH3
(WHT)
TH4
(WHT)
TRANS
CNVMNT
(WHT)
CNMNT
(WHT)
CNM
(WHT)
LED1
LED2
X52
SV1 /CH
(GRY)
X54
63H
(YLW)
2
7
1 4 1 2 2 1
1 3
31 1 5
1 14
1 2
1 7
3
1
13
1
2
3 4
31 31
LEV-A
(WHT)
51
SS
(WHT)
X51
31
MS 3~
MF1
1
7
63L63H
63L
(RED)
1 3
31
TH34
2 1 TH34 (RED)
63HS
(WHT)
63HS
LEV-B (RED)
M
LEV-B
51
M
MF2
CNF2
(WHT)
CNF1
(WHT)
1
7
2
7
CN52C
(RED)
3
1 3
3
TH8
CN3S
(WHT)
1
3
CNDM
(WHT)
CN51
(WHT)
1
3 1
5
~
~
MS 3~
1 2 3 4 5 6 7 8
OFF
ON
MODEL
SW6 SW5-6 *2
OFF
ON
1 2 3 4 5 6
1 2 3 4 5 6 7 8
OFF
ON
OFF
ON
1 2 3 4 5 6
*
2 SW5 -1 to 5 : Function Switch
SW7
SW6SW1
SW9
CN31
*1*
1
SW5SW8SW4 SWP
*
1 MODEL SELECT
The black square ( ) indicates a switch position.
OCH533D
20
PUHZ-SW100VHAR4.UK PUHZ-SW120VHAR4.UK PUHZ-SW100VHAR4-BS.UK PUHZ-SW120VHAR4-BS.UK
*1 *1
POWER SUPPLY ~/N 230V 50Hz
TO
INDOOR
UNIT
W
DCL
L
N S1 S2 S3
TB1
V
U
2
RD
WH
BK
MC
CN4 (WH)
3
1
RD
BU
YE
OG
BN
GNYE
BK
CNAC2
(RD)
CNAC1
(WH)
LINI
EI
E3
CN52C
(RD)
3
1
1
3
DCL1
DCL2
+
+
-
UVW
CNDC
(PK)
BK
2
MS
3~
E2
BK
E4
BK
CY1
CY2
IGBT
7
3
3
TH8
~
~
CN52C
(RD)
P. B.
BK WH
C. B.
TH6TH7 TH4TH3
21S4
t° t°
LEV-A
CNS
(WH)
CNAC
(WH)
CNDC
(PK)
F2
F1
F3
F4
21S4 (GN)
CN2
(RD)
CN4
(WH)
TH7/6
(RD)
TH3
(WH)
TH4
(WH)
TRANS
CNM
(WH)
LED1
LED2
X52
SV1/CH
(GY)
X54
63H
(YE)
2
7
1 4 1 2 2 1
1 3
1
14
1 2
1 7
1
3
13
1 2
3 4
31 31
LEV-A
(WH)
51
SV3/SS
(WH)
X51
31
MF1
CNF1 (WH)
1
7
63L63H
63L
(RD)
1 3
31
TH34
2 1 TH34 (RD)
63HS (WH)
63HS
LEV-B
(RD)
M
LEV-B
51
M
MF2
CNF2 (WH)
1
7
2
SW7
SW6SW1
SW9
SW5SW8SW4 SWP
31
CNDM
(WH)
MS
3~
MS
3~
1 2
CN2 (RD)
1 7
31
31
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
ON
100V
MODEL
SW6 SW5-6 *2
OFF
ON
OFF
ON
120V
OFF
ON
1 2 3 4 5 6
1 2 3 4 5 6
*1 MODEL SELECT
The black square (
) indicates a switch position.
*2 SW5 -1 to 5 : Function Switch
Thermistor <2-Phase Pipe>
TB1
MC MF1, MF2 21S4 63H 63L 63HS TH3 TH4 TH6
TH7 TH8 TH34
DCL CY1, CY2
Terminal Block <Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (4-Way Valve) High Pressure Switch Low Pressure Switch High Pressure Sensor Thermistor <Liquid> Thermistor <Discharge>
Thermistor <Ambient> Thermistor internal <Heat Sink> Thermistor <Comp. Surface> Linear Expansion Valve Reactor Capacitor
Power Circuit Board
P. B .
SYMBOL NAME SYMBOL NAME SYMBOL NAME
SW8 SW9 SWP CNDM SV1/CH SV3/SS CNM F1, F2, F3, F4
Switch <Function Switch>
Switch <Function Switch> Switch <Pump Down> Connector <Connection for Option
>
Connector <Connection for Option
>
Connector <Connection for Option
>
Connector <Connection for Option
>
Fuse <T6.3AL250V>
LEV-A, LEV-B
Switch <Function Switch>
Switch <Function Switch, Model Select> Switch <Model Select> Switch <Function Switch>
SW4
SW1
Record Reset, Refrigerant Address
>
Controller Circuit Board
C. B.
SW5 SW6 SW7
Switch <Manual Defrost, Defect History
OCH533D
21
PUHZ-SW100/120YHA WIRING DIAGRAM
BH79B654H01
TB1 TB2 MC MF1, MF2 21S4 63H 63L 63HS TH3 TH4 TH6 TH7 TH8 TH34 LEV-A, LEV-B ACL1, ACL2, ACL3, ACL4 CY1, CY2 CK RS
Terminal Block <Power Supply> Terminal Block <Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch High Pressure Sensor Thermistor <Liquid> Thermistor <Discharge> Thermistor <2-Phase Pipe> Thermistor <Ambient> Thermistor <Heat Sink> Thermistor <Comp. Surface> Linear Expansion Valve Reactor Capacitor Capacitor Rush Current Protect Resistor
Power Circuit Board Connection Terminal <U/V/W-Phase>
P. B.
TB-U/V/W
Noise Filter Circuit Board Connection Terminal
<L1/L2/L3/N-Power Supply
>
N. F.
LI1/LI2/LI3/NI
Connection Terminal
<L1/L2/L3/N-Power Supply
>
LO1/LO2/LO3/NO
Converter Circuit Board
CONV. B.
Connection Terminal <Ground>
GD1, GD3
Connection Terminal <L1-Power Supply>
L1-A1/IN
Connection Terminal <L1-Power Supply>
L1-A2/OU
Connection Terminal <L2-Power Supply>
L2-A2/OU
Connection Terminal <L3-Power Supply>
L3-A2/OU
Connection Terminal
N-IN
Connection Terminal
CK-OU
SYMBOL NAME SYMBOL NAME SYMBOL NAME
Connection Terminal
<L1/L2/L3-Power Supply
>
TB-L1/L2/L3
SW4 SW5 SW6 SW7 SW8 SW9 SWP CN31 CNDM CN51 SV1/CH SS CNM LED1, LED2 F1, F2, F3, F4 X51, X52, X54
SW1
C. B.
Connection Terminal
TB-N
52C Relay
X52CA
Switch <Manual Defrost, Defect History, Record Reset, Refrigerant Address> Switch <Test Operation> Switch <Function Switch, Model Select> Switch <Model Select> Switch <Function Switch> Switch <Function Switch> Switch <Function Switch> Switch <Pump Down> Connector <Emergency Operation> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> LED <Operation Inspection Indicators> FUSE <T6.3AL250V> Relay
Controller Circuit Board
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
ON
100Y
MODEL
SW6 SW5-6 *2
OFF
ON
OFF
ON
120Y
OFF
ON
1 2 3 4 5 6
1 2 3 4 5 6
*
2 SW5 -1 to 5 : Function Switch
P. B.
U
POWER SUPPLY 3N~ 400V 50Hz
TB1
V
W
RED
WHT
BLK
MC
7
L1
L2
L3
N
N. F.
CNAC1
(WHT)
31
CNDC (PNK)
31
CNL
(BLU)
13
CNAC2
(RED)
31
CNCT (RED)
1 2
LO1
LO2
LO3
NO
GD1
NI
LI1
LI2
LI3
GD3
S1
S2
S3
CK
2
3
2
3
ACL4
ACL3
ACL2
ACL1
RED
WHT
BLK
BLU
RED
WHT
BLK
BLU
TB2
CN7
(WHT)
3
1
L3-OU
L3-A2
L2-OU
L2-A2
L1-OU
L1-A2
L1-A1
L1-IN
N-IN
CK-OU
X52CA
RED
RED
BLK
BLU
RED
RED
BLK
BLK
WHT
WHT
RED
WHT
BLK
YLW
ORN
BRN
BLK
RED
GRN/YLW
BLK
BLK
CONV. B.
BRN
INDOOR
UNIT
C. B.
TH6TH7
TH4TH3
21S4
t° t° t° t°
LEV-A
CNS
(WHT)
CNAC (WHT)
CNDC (PNK)
F2
F1
F3
F4
21S4
(GRN)
CN2
(WHT)
CN4
(WHT)
TH7/6 (RED)
TH3
(WHT)
TH4
(WHT)
TRANS
CNVMNT
(WHT)
CNMNT
(WHT)
CNM
(WHT)
LED1
LED2
X52
SV1 /CH
(GRY)
X54
63H
(YLW)
2
7
1 4 1 2 2 1
1 3
31 1 5
1 14
1 2
1 7
3
1
13
1 2
3 4
31 31
LEV-A (WHT)
51
SS
(WHT)
X51
31
MS
3~
MF1
CNF1 (WHT)
1
7
63L63H
63L
(RED)
1 3
31
TH34
2 1
TH34
(RED)
63HS
(WHT)
63HS
LEV-B (RED)
M
LEV-B
51
M
MF2
CNF2
(WHT)
1
7
CN7
(WHT)
1 3 1 2
CN6 (WHT)
1 2
CN5 (RED)
CN2
(WHT)
1 7 1 2
CN4
(WHT)
TB-N
TB-U
TB-V
TB-W
TB-L3
TB-L2
TB-L1
TH8
RS
RED
MS
3~
22
2
CN3S
(WHT)
1
3
CNDM
(WHT)
CN51
(WHT)
1
3 1
5
CN52C
(RED)
1 3
MS
3~
BRN
CY1
CY2
SW7
SW6SW1
SW9
CN31
*1*
1
SW5SW8SW4 SWP
+
-
+
*
1 MODEL SELECT
The black square ( ) indicates a switch position.
PUHZ-SW100YHA.UK PUHZ-SW120YHA.UK PUHZ-SW100YHA-BS.UK PUHZ-SW120YHA-BS.UK
OCH533D
22
PUHZ-SW100/120YHA WIRING DIAGRAM
TB1 TB2 MC MF1, MF2 21S4 63H 63L 63HS TH3 TH4 TH6 TH7 TH8 TH34 LEV-A, LEV-B ACL1, ACL2, ACL3, ACL4 CY1, CY2 CK RS
Terminal Block <Power Supply> Terminal Block <Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch High Pressure Sensor Thermistor <Liquid> Thermistor <Discharge> Thermistor <2-Phase Pipe> Thermistor <Ambient> Thermistor <Heat Sink> Thermistor <Comp. Surface> Linear Expansion Valve Reactor Capacitor Capacitor Rush Current Protect Resistor
Power Circuit Board Connection Terminal <U/V/W-Phase>
P. B.
TB-U/V/W
Noise Filter Circuit Board Connection Terminal
<L1/L2/L3/N-Power Supply
>
N. F.
LI1/LI2/LI3/NI
Connection Terminal
<L1/L2/L3/N-Power Supply
>
LO1/LO2/LO3/NO
Converter Circuit Board
CONV. B.
Connection Terminal <Ground>
GD1, GD3
Connection Terminal <L1-Power Supply>
L1-A1/IN
Connection Terminal <L1-Power Supply>
L1-A2/OU
Connection Terminal <L2-Power Supply>
L2-A2/OU
Connection Terminal <L3-Power Supply>
L3-A2/OU
Connection Terminal
N-IN
Connection Terminal
CK-OU
SYMBOL NAME SYMBOL NAME SYMBOL NAME
Connection Terminal
<L1/L2/L3-Power Supply
>
TB-L1/L2/L3
SW4 SW5 SW6 SW7 SW8 SW9 SWP CN31 CNDM CN51 SV1/CH SS CNM LED1, LED2 F1, F2, F3, F4 X51, X52, X54
SW1
C. B.
Connection Terminal
TB-N
52C Relay
X52CA/B
Switch <Manual Defrost, Defect History, Record Reset, Refrigerant Address> Switch <Test Operation> Switch <Function Switch, Model Select> Switch <Model Select> Switch <Function Switch> Switch <Function Switch> Switch <Function Switch> Switch <Pump Down> Connector <Emergency Operation> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> Connector <Connection for Option> LED <Operation Inspection Indicators> FUSE <T6.3AL250V> Relay
Controller Circuit Board
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
ON
100Y
MODEL
SW6 SW5-6 *2
OFF
ON
OFF
ON
120Y
OFF
ON
1 2 3 4 5 6
1 2 3 4 5 6
*
2 SW5 -1 to 5 : Function Switch
P. B.
U
POWER SUPPLY 3N~ 400V 50Hz
TB1
V
W
RED
WHT
BLK
MC
7
L1
L2
L3
N
N. F.
CNAC1
(WHT)
31
CNDC (PNK)
31
CNL
(BLU)
13
CNAC2
(RED)
31
CNCT (RED)
1 2
LO1
LO2
LO3
NO
GD1
NI
LI1
LI2
LI3
GD3
S1
S2
S3
CK
2
3
2
3
ACL4
ACL3
ACL2
ACL1
RED
WHT
BLK
BLU
RED
WHT
BLK
BLU
TB2
CN7
(WHT)
3
1
L3-OU
L3-A2
L2-OU
L2-A2
L1-OU
L1-A2
L1-A1
L1-IN
N-IN
CK-OU
X52CA
RED
RED
BLK
BLU
RED
RED
BLK
BLK
WHT
WHT
RED
BLK BLK
WHT
YLW
ORN
BRN
BLK
RED
GRN/YLW
BLK
BLK
CONV. B.
BRN
INDOOR
UNIT
C. B.
TH6TH7
TH4TH3
21S4
t° t° t°
LEV-A
CNS
(WHT)
CNAC (WHT)
CNDC (PNK)
F2
F1
F3
F4
21S4
(GRN)
CN2
(WHT)
CN4
(WHT)
TH7/6 (RED)
TH3
(WHT)
TH4
(WHT)
TRANS
CNVMNT
(WHT)
CNMNT
(WHT)
CNM
(WHT)
LED1
LED2
X52
SV1
/CH
(GRY)
X54
63H
(YLW)
2
7
1 4 1 2 2 1
1 3
31 1 5
1 14
1 2
1 7
3
1
13
1 2
3 4
31 31
LEV-A (WHT)
51
SS
(WHT)
X51
31
MS 3~
MF1
CNF1
(WHT)
1
7
63L
63H
63L
(RED)
1 3
31
TH34
2 1 TH34
(RED)
63HS
(WHT)
63HS
LEV-B (RED)
M
LEV-B
51
M
MF2
CNF2 (WHT)
1
7
CN7
(WHT)
1 3 1 2
CN6
(WHT)
1 2
CN5 (RED)
CN2
(WHT)
1 7 1 2
CN4
(WHT)
TB-N
TB-U
TB-V
TB-W
L3IN
TB-L2
TB-L1
TH8
RS
RED
MS
3~
22
2
CN3S
(WHT)
1
3
CNDM
(WHT)
CN51
(WHT)
1
3 1
5
CN52C
(RED)
1 3
MS 3~
BRN
CY1
CY2
SW7
SW6SW1
SW9
CN31
*1*
1
SW5SW8SW4 SWP
+
-
+
*
1 MODEL SELECT
The black square ( ) indicates a switch position.
X52CB
TB-L3L3OUT
PUHZ-SW100YHAR1.UK PUHZ-SW100YHAR3.UK PUHZ-SW100YHAR1-BS.UK PUHZ-SW100YHAR3-BS.UK PUHZ-SW120YHAR1.UK PUHZ-SW120YHAR3.UK PUHZ-SW120YHAR1-BS.UK PUHZ-SW120YHAR3-BS.UK
OCH533D
23
PUHZ-SW100YHAR4.UK PUHZ-SW120YHAR4.UK PUHZ-SW100YHAR4-BS.UK PUHZ-SW120YHAR4-BS.UK
TB1 TB2 MC MF1, MF2 21S4 63H 63L 63HS TH3 TH4 TH6 TH7 TH8
ACL1, ACL2, ACL3, ACL4 CY1, CY2 CK RS
Terminal Block <Power Supply> Terminal Block <Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (4-Way Valve) High Pressure Switch Low Pressure Switch High Pressure Sensor Thermistor <Liquid> Thermistor <Discharge> Thermistor <2-Phase Pipe> Thermistor <Ambient> Thermistor <Heat Sink>
Linear Expansion Valve
Reactor
Capacitor Capacitor Rush Current Protect Resistor
Power Circuit Board
P. B.
Noise Filter Circuit Board
N. F.
Converter Circuit Board
CONV. B.
SYMBOL
NAME SYMBOL NAME SYMBOL NAME
SW5 SW6 SW7 SW8 SW9 SWP CNDM SV1/CH SV3/SS CNM F1, F2, F3, F4
Switch <Function Switch, Model Select
>
Switch <Model Select> Switch <Function Switch> Switch <Function Switch> Switch <Function Switch> Switch <Pump Down> Connector <Connection for Option
>
Connector <Connection for Option
>
Connector <Connection for Option
>
Connector <Connection for Option
>
Fuse <T6.3AL250V>
TH34
Thermistor <Comp. Surface>
LEV-A, LEV-B
SW4
SW1
Switch <Manual Defrost, Defect History Record Reset, Refrigerant Address
>
Switch <Function Switch>
Controller Circuit Board
C. B.
*1 *1
U
POWER SUPPLY 3N
~
400V 50Hz
TB1
V W
RD
WH
BK
MC
7
L1
L2
L3
N
CNAC1
(WH)
31
CNDC
(PK)
31
CNL (BU)
13
CNAC2
(RD)
31
CNCT
(RD)
1
2
LO1
LO2
LO3
NO
GD1
NI
LI1
LI2
LI3
GD3
S1
S2
S3
CK
2
3
2
3
ACL4
ACL3
ACL2
ACL1
RD
WH
BK
BU
RD
WH
BK
BU
TB2
CN7
(WH)
3
1
L3-OU
L3-A2
L2-OU
L2-A2
L1-OU
L1-A2
L1-A1
L1-IN
N-IN
CK-OU
X52CA
X52CB
RD
RD
BK
BU
RD
RD
BK
BK
WH
WH
RD
RD
RD
WH
BK
BK
YE
OG
BN
BK
GNYE
BK
BK
TO
INDOOR
UNIT
C. B.
TH6TH7 TH4TH3
21S4
t° t° t°
LEV-A
CNS
(WH)
CNAC
(WH)
CNDC
(PK)
F2
F1
F3
F4
21S4 (GN)
CN2 (RD)
CN4
(WH)
TH7/6
(RD)
TH3 (WH)
TH4
(WH)
TRANS
CNM (WH)
LED1
LED2
X52
SV1/CH
(GY)
X54
63H
(YE)
2
7
1 4 1 2 2 1
1 3
1
14
1 2
1 7
1
3
13
1 2
3 4
31 31
LEV-A
(WH)
51
SV3/SS
(WH)
X51
31
MF1
CNF1
(WH)
1
7
63L63H
63L
(RD)
1 3
31
TH34
2 1
TH34
(RD)
63HS (WH)
63HS
LEV-B
(RD)
M
LEV-B
51
M
MF2
CNF2
(WH)
1
7
CN7 (WH)
1 3 1 2
CN6
(WH)
1 2
CN5 (RD)
CN2 (RD)
1 7 1 2
CN4
(WH)
TB-N
TB-U
TB-V
TB-W
TB-L3
TB-L1
L3OUT
TB-L2
L3IN
TH8
RS
MS
3~
22
2
CY1
CY2
SW7
SW6SW1
SW9
SW5SW8SW4 SWP
+
-
+
31
CNDM
(WH)
+
+
+
~~~
~
~
P. B.
N. F.
CONV. B.
MS
3~
MS
3~
8
8
1 2 3 4 5 6 7
1 2 3 4 5 6 7
OFF
ON
100Y
MODEL
SW6
SW5-6 *2
SW5-6 *2
OFF
ON
OFF
ON
120Y
OFF
ON
1 2 3 4 5 6
1 2 3 4 5 6
MODEL
SW6
*1 MODEL SELECT
The black square ( ) indicates a switch position.
*2 SW5 -1 to 5 : Function Switch
OCH533D
24
9 WIRING SPECIFICATIONS
FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model
SW75V SW100V SW120V SW100, 120Y
Outdoor unit power supply
~/N (single),
50 Hz, 230 V
~/N (single),
50 Hz, 230 V
~/N (single),
50 Hz, 230 V
3N~ (3 ph 4-wires),
50 Hz, 400 V
Outdoor unit input capacity Main switch (Breaker) *1 25 A 32 A 40 A 16 A
Wiring
Wire No. ×
size (mm
2
)
Outdoor unit power supply 3 × Min. 2.5 3 × Min. 4 3 × Min. 6 5 × Min. 1.5
Indoor unit-Outdoor unit *2 3 × 1.5 (Polar) 3 × 1.5 (Polar) 3 × 1.5 (Polar) 3 × 1.5 (Polar)
Indoor unit-Outdoor unit earth *2 1 × Min. 1.5 1 × Min. 1.5 1 × Min. 1.5 1 × Min. 1.5
Remote controller-Indoor unit *3 2 × 0.3 (Non-polar) 2 × 0.3 (Non-polar) 2 × 0.3 (Non-polar) 2 × 0.3 (Non-polar)
Circuit rating
Outdoor unit L-N (single) Outdoor unit L1-N, L2-N, L3-N (3 phase)
*4 230 V AC 230 V AC 230 V AC 230 V AC
Indoor unit-Outdoor unit S1-S2 *4 230 V AC 230 V AC 230 V AC 230 V AC
Indoor unit-Outdoor unit S2-S3 *4 24 V DC 24 V DC 24 V DC 24 V DC
Remote controller-Indoor unit *4 12 V DC 12 V DC 12 V DC 12 V DC
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
Make sure that the current leakage breaker is one compatible with higher harmonics. Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of inverter. *2. Maximum 45 m If 2.5 mm
2
is used, maximum 50 m.
If 2.5 mm
2
is used and S3 is separated, maximum 80 m.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The gures are NOT always against the ground.
S3 terminal has 24 V DC against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
S1
S2
S3
S1
S2
S3
Warning:
· In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
Notes: 1. Wiring size must comply with the applicable local and national codes.
2.
Power supply cables and the cables between Interface unit/Flow temp. controller and outdoor unit shall not be lighter than polychloroprene
sheathed exible cables. (Design 60245 IEC 57
)
3. Be sure to connect the cables between
Interface unit/Flow temp. controller
and outdoor unit directly to the units (no intermediate connections
are allowed).
Intermediate connections may result in communication errors. If water enters at the intermediate connection point, it may cause insufcient
insulation to ground or a poor electrical contact . (If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.)
4. Install an earth longer than other cables.
5. Do not construct a system with a power supply that is turned ON and OFF frequently.
Outdoor Unit
3 poles isolator
Power supply
Isolator
Indoor unit (Interface unit / Flow temp. controller)
Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in smoke emission, a re or communication failure.
OCH533D
25
10 REFRIGERANT SYSTEM DIAGRAM
unit: mm (in)
Distributor
Thermistor TH7 (Ambient)
Heat exchanger
Refrigerant LIQUID pipe connection [9.52(3/8)
Stop valve (with service port)
Strainer #100
Power receiver
Linear expansion valve B
Linear expansion valve A
Strainer #100
Thermistor TH6 (2-phase pipe)
Thermistor TH3 (Liquid)
High pressure switch 63H
Thermistor TH4 (Discharge)
Thermistor TH34
P.B TH8
(Comp. surface)
Compressor
Strainer #50
Strainer #100
Strainer #100
4-way valve
Charge plug
(Low pressure)
Charge plug (High pressure)
Stop valve
(with service port)
Refrigerant GAS pipe connection [15.88(5/8)
Pressure sensor 63HS
Distributor
Thermistor TH7 (Ambient)
Heat exchanger
Refrigerant GAS pipe connection ø15.88(5/8)
Refrigerant LIQUID pipe connection ø9.52(3/8)
Stop valve (with service port)
Strainer #100
Power receiver
Linear expansion valve B
Linear expansion valve A
Strainer #100
Strainer #100
Thermistor TH6 (2-phase pipe)
Thermistor TH3 (Liquid)
Charge plug (Low pressure)
Charge plug (High pressure)
High pressure switch 63H
Thermistor TH4 (Discharge)
Thermistor TH34 (Comp. surface)
Compressor
Strainer #50
4-way valve
Strainer #100
Strainer #100
Ball valve
Refrigerant flow in cooling
Refrigerant flow in heating
Pressure sensor 63HS
Low pressure switch 63L
P.B TH8
PUHZ-SW75VHA.UK PUHZ-SW75VHAR3.UK PUHZ-SW75VHAR4.UK PUHZ-SW75VHA-BS.UK PUHZ-SW75VHAR3-BS.UK PUHZ-SW75VHAR4-BS.UK
COMP
H/P SW
L/P SW
REV/V
Charge plug
P-Sensor
LEV-A
LEV-B
TH3
TH4
TH6
TH7
TH34
DC inverter twin rotary compressor (Mitsubishi Electric Corporation)
For protection (OFF:4.15MPa)
For protection (OFF:-0.03MPa) (SW100/120)
Change the refrigerant circuit (Heating / Cooling) and for Defrosting
High pressure / Low pressure / For production test use
For calculation of the condensing temperature from high pressure
Heating:Secondary LEV Cooling:Primary LE
V
Heating:Primary LEV Cooling:Second
ary LEV
Heating:Evaporating temperature Cooling:Sub cool liquid temperature
For LEV control and for compressor protection
Outdoor 2-phase pipe temperature
For fan control and for compressor frequency control
For compressor protection
For accumulation of refrigerant
Compressor
High pressure switch (63H)
Low pressure switch (63L)
Reversing (4-way) valve (21S4)
Charge plug
Pressure sensor (63HS)
Linear expansion valve -A
Linear expansi
on valve -B
Liquid temperature thermistor
Discharge
temperature thermistor
2-phase pipe temperature thermistor
Ambient temperature thermistor
Comp.surface temperature thermistor
Power Receiver
Symbol Part name
Detail
Power Receiver
PUHZ-SW100VHA.UK
PUHZ-SW100VHAR3.UK PUHZ-SW100VHAR4.UK
PUHZ-SW100VHA-BS.UK
PUHZ-SW100VHAR3-BS.UK PUHZ-SW100VHAR4-BS.UK
PUHZ-SW100YHA.UK
PUHZ-SW100YHAR1.UK PUHZ-SW100YHAR3.UK PUHZ-SW100YHAR4.UK
PUHZ-SW100YHA-BS.UK
PUHZ-SW100YHAR1-BS.UK PUHZ-SW100YHAR3-BS.UK PUHZ-SW100YHAR4-BS.UK
PUHZ-SW120VHA.UK
PUHZ-SW120VHAR3.UK PUHZ-SW120VHAR4.UK
PUHZ-SW120VHA-BS.UK
PUHZ-SW120VHAR3-BS.UK PUHZ-SW120VHAR4-BS.UK
PUHZ-SW120YHA.UK
PUHZ-SW120YHAR1.UK PUHZ-SW120YHAR3.UK
PUHZ-SW120YHAR4.UK
PUHZ-SW120YHA-BS.UK
PUHZ-SW120YHAR1-BS.UK PUHZ-SW120YHAR3-BS.UK PUHZ-SW120YHAR4-BS.UK
OCH533D
Loading...
+ 56 hidden pages