15. PARTS LIST ·······················································79
Model name
indication
16. OPTIONAL PARTS ······························BackCover
····6
···················17
PUHZ-RP8YHA
PUHZ-RP10YHA
1SAFETY PRECAUTION
Use new refrigerant pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
In case of using the existing pipes for R22, be careful with
the followings.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant
charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
1-1. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
2
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.Specifications
1Gauge manifold·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3Electronic scale
4Gas leak detector·Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check·Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder·Only for R410ATop of cylinder (Pink)
8Refrigerant recovery equipment
specifications
Cylinder with syphon
. (UNF1/2)
3
1-2. CHANGED POINT
Measure the existing pipe thickness and check
for damage.
The existing pipe thickness meets specifications and the pipes are not damaged.
The existing pipe thickness does not meet
specifications or the pipes are damaged.
Check if the existing air conditioner can operate.
The existing air conditioner can operate.The existing air conditioner cannot operate.
After operating the cooling system for about
30 minutes, do a pump down work.
Use a refrigerant collecting device to collect the refrigerant.
Check the oil condition when collecting the refrigerant.
Oil is clean. (Clear to brownish color)
Oil is dirty. (Black color)
When the compressor bearings are
glazed, rotation scratches are present,
or the compressor breaks down, iron
particles or oil deterioration will blacken
the oil.
Disconnect the existing air conditioner from
the pipes.
The existing piping can be reused.
After flaring the pipes again, connect the
new air conditioner.
The existing pipes cannot be reused.
Use new pipes.
Perform the following inspections: air
tightness test, vacuum dryness (additional
refrigerant charge), gas leakage check
Replacement operation
Test operation
Replacement operation is the operation by which impurities remaining in
the existing piping (chlorinated compounds) are captured by the activated
carbon filter (replacement filter) in the outdoor unit.
• This model will automatically begin the replacement operation after it has been
installed when it enters the initialization phase for normal heating or cooling. However , the unit will not automatically perf orm the replacement operation if it is moved
to a new location where it will be used with existing R22 refrigerant piping. Under
such conditions, always use the SW8-2 operations to perform the replacement
operation before beginning the test operation.
• Precautions when reusing existing R22 refrigerant pipes
(1) Flowchart
Connecting a new air conditioner to existing R22 refrigerant pipes
1 Flare the pipe for the use with R410A refrigerant.
Use the flare nut attached to indoor and outdoor unit of the new air conditioner only.
2 When reusing existing R22 refrigerant pipes of which gas pipe is [28.58mm and, in addition, when the outdoor unit is
installed to lower position than the indoor unit, be sure to change the setting of the DIP SW8-1 on the controller circuit
board of the outdoor unit to ON.
✽ This is to increase the speed of refrigerant passing in the gas pipe so that refrigerant oil can smoothly flow in the system.
• Use a different-diameter joint or brazing for the connection.
3 When reusing standard-size existing R22 refrigerant pipes.
The pipes can be reused with pipe length restriction described on 12-1.
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
Air purge and refrigerant charge
Operation check and the two above
Gas leak check
Collection of refrigerant
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Charge refrigerant
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Charge refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil and alkylbenzene
oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adopter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
Tool exclusive for R410A
Tools and materialsUseR410A toolsCan R22 tools be used?
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
Can R407C tools be used?
Ester oil:
Alkylbenzene oil: minimum amount
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410Ais same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working
pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
1Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7mm or below.)
2Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because of its working pressure higher than that of other refrigerants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also
have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring
dimensions for R410A below. For 1/2” and 5/8”, the dimension B changes.
Use torque wrench corresponding to each dimension.
Dimension A
3Tools for R410A (The following table shows whether conventional tools can be used or not.)
5
Dimension B
2COMBINATION OF INDOOR AND OUTDOOR UNITS
2-1. 1:1 SYSTEM
Outdoor unit
Indoor unit
PEH-RP·MYA
2-2. SYNCHRONIZED TWIN, TRIPLE AND QUADRUPLE SYSTEM
Ratio of distributingPart No.
Synchronized twin50:50MSDD-50WR-E
Synchronized triple33:33:33MSDT-111R-E
Synchronized quadruple25:25:25:25MSDF-1111R-E
6
3FEATURES
PUHZ-RP8YHA
PUHZ-RP10YHA
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
(Max.30m)
The refrigerant circuit with LEV(Linear Expansion Valve) and accumulator always control the optimal refrigerant
level regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during
installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality
and reliability of the work done.It also helps to speed up the installation time.
7
4SPECIFICATIONS
Service Ref.
Function
Capacity
Total input
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Crankcase heater
Heat exchanger
FanFan(drive) o No.
Defrost method
OUTDOOR UNIT
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current
Model
Motor output
Starter type
Protection devices
Fan motor output
Airflow
Charge
Oil (Model)
/min(CFM
K
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
The cable length may vary depending on the condition of installation, humidity or materials, etc.
Cross section
of cable
Wire size
2
)
(mm
Number
of wires
PolarityL(m) ✽5
Round
2.5
3
Clockwise : S1-S2-S3
Flat
2.5
3
Not applicable
(Because center wire has no cover finish)
applicable
Flat
1.5
4
From left to right : S1-Open-S2-S3
Round
2.5
4
Clockwise : S1-S2-S3-Open
Connect S1 and S3 to the opposite angle
(30)
✽1
Not
✽2
(18)
✽3
30
✽4
✽1 : In case that cable with stripe of yellow and green is available.
✽2 : In the flat cables are connected as this picture, they can be used up to 30m.
(3C Flat cable ✕ 2)
S1 S2 S3
✽3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm2.
✽4 : In case of regular polarity connection (S1-S2-S3).
✽5 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or materials, etc.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate
connections).
Intermediate connections can lead to communication errors if water enters the cables and causes
insufficient insulation to ground or a poor electrical contact at the intermediate connection point.
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering
the cables.)
13
9
Outdoor unit
Power supply
Phase
Frequency & Voltage
Outdoor unit (A)
Wire No.
32
4
32
4
Models (Outdoor unit)
3N~(3ph 4wires)
50Hz, 380-400-415V
Outdoor unit
Power supply
Input capacity
Main switch/Breaker
Indoor unit/Outdoor unit connecting
Wire No. o size (e)
Remote controller-indoor unit connecting
Wire No. o size (e)
Control circuit rating
Wiring
Cable 2C o 0.69
This wire is accessory of remote controller
(Wire length: 10m, Non-polar)
Indoor unit-Outdoor unit: S1-S2 AC220V-230V-240V
S2-S3 DC24V
Remote controller-Indoor unit: DC14V
RP8RP10
Cable length 50 m : 3 o 4 (Polar)
Cable length 80 m : 3 o 6 (Polar)
1
2
S1
S2
S3
S1
S2
S3
Indoor/outdoor
unit connection
cable
Indoor
unit
Unit
power
supply
Outdoor
unit
Remote
controller
L1
L2
L3
N
Grounding
L1
L2
L3
N
1
2
1
2
S1
Indoor
unit
S2
S3
S1
S2
S3
S1
S2
S3
Unit
power
supply
Indoor/outdoor
unit connection
cable
Indoor
unit
Outdoor
unit
Remote
controller
Grounding
1
2
1
2
1
2
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
Indoor/outdoor
connection cable
Indoor
unit
Unit
power
supply
Indoor
unit
Indoor
unit
Outdoor
unit
Remote
controller
L1
L2
L3
N
Grounding
1
2
1
2
S1
S2
S3
S1
S2
S3
S1
S2
S3
1
2
S1
S2
S3
1
2
S1
S2
S3
Indoor/outdoor
connection cable
Indoor
unit
Unit
power
supply
Indoor
unit
Indoor
unit
Outdoor
unit
Remote
controller
L1
L2
L3
N
Grounding
Indoor
unit
SPECIFICATIONS FOR ELECTRICAL WORK
9-1. FIELD ELECTRICAL WIRING (POWER WIRING SPECIFICATIONS)
PUHZ-RP•YHA
Check items
1. Wiring size must comply with the applicable local and national code.
2. Be careful about choosing the installation location for the earth leakage breaker and how it is installed as the initial electric
current may cause it to malfunction.
3. Power supply cords and indoor unit / Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flex-
ible cord. (design 254 IEC 57)
1:1 systemSynchronized twin, triple and quadruple system
Electrical wiring
• Synchronized twin
• Synchronized triple
• Synchronized quadruple
14
9-2. M-NET WIRING METHOD
Group
remote
controller
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
A-control
remote
controller
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 00
M-NET
address 03
Power
supply
unit for
transmission
wire
Central
remote
controller
M-NET transmission wire
✕ Bad example (Multi spot grounding of shield wire)
Good example 1 (Single spot grounding of shield wire)
Power
supply
appliance
M-NET type
outdoor unit
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
Good example 2 (Single spot grounding of shield wire)
(Points to notice)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET p.c. board may be burn out.
(3) Use 2-core x 1.25mm2shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
If there are more than two grounding spots on the shield wire, noise may enter into the shield wire because the ground
wire and shield wire form one circuit and the electric potential difference occurs due to the impedance difference among
grounding spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and
shield wire do not form one circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the central-control remote controller.
15
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
12
~
50
M-NET Address No.
<Setting example>
Switng
setting
SW11
ones
digit
SW12
tens
digit
OFF
ON
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
0
Refrigrant
address
OFF
ON
8
OFF
ON
1
OFF
ON
9
OFF
ON
10
OFF
ON
11
OFF
ON
12
OFF
ON
13
OFF
ON
14
OFF
ON
15
OFF
ON
2
OFF
ON
3
OFF
ON
4
OFF
ON
5
OFF
ON
6
OFF
ON
7
System
controller
A-control
remote
controller
Group AGroup BGroup C
A-control
remote
controller
TB5
A-control
remote
controller
Refrigerant
address 00
M-NET
address 01
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 00
M-NET
address 04
Power
supply
unit for
transmission
wire
A-control
remote
controller
A-control
remote
controller
TB5
Group AGroup B
Refrigerant
address 00
M-NET
address 01
Refrigerant
address 01
M-NET
address 02
Refrigerant
address 00
M-NET
address 04
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 02
M-NET
address 05
System
controller
Power
supply
unit for
transmission
wire
● M-NET wiring
(1) Use 2-core x 1.25mm
2
shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block.Connect one core of the
transmission wire (non-polar) to Aterminal and the other to B. Peel the
shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(A, B, S) on M-NET terminal block should be individually wired to the other
M-NET
terminal
block
ABS
Transmission
wire
Ground
wire
Shield
part
outdoor unit’s terminal, i.e. Ato A, B to B and S to S.In this case, choose one of those outdoor units and drive a screw
to fix an ground wire on the plate as shown on the right figure.
9-2-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to Free Combo
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in Free Combo system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
(SW11 for ones digit and SW12 for tens digit), which
is located on the M-NET p.c. board of outdoor unit.
(Factory setting: all addresses are set to “0”.)
9-2-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group setting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller circuit board. [Factory
setting: all switches are OFF. (All refrigerant addresses are “00”.)]
9-2-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above
section. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
w Refrigerant addresses can be overlapped if they are in the different group.
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in
the group for the outdoor unit whose refrigerant address is “00”.
16
10REFRIGERANT SYSTEM DIAGRAM
Strainer
#50
Strainer
#50
Strainer
#100
Strainer
#100
Strainer
#100
Strainer
#100
Oil
separator
Strainer
#100
Stop valve
(with service port)
Stop valve
(with service port)
Charge plug
(Low pressure)
Accumulator
Oil-back hole
Strainer#40
Linear expansion valve
Low pressure switch 63L
Compressor
Capillary tube1
Capillary tube2
Replace
filter
High pressure switch 63H
Bypass valve
Charge plug
(High pressure)
Thermistor TH4
(Discharge)
Thermistor TH6
(Outdoor 2-phase pipe)
Thermistor TH7
(Outdoor)
Thermistor TH3
(Outdoor pipe)
Thermistor TH32
(Outdoor pipe)
Heat exchanger
4-way valve
Refrigerant GAS pipe
connection
(RP8:1, RP10:1-1/8)
Refrigerant flow in cooling
Refrigerant flow in heating
PUHZ-RP8YHA
PUHZ-RP10YHA
17
11CAPACITY CURVES
Cooling capacity
1.4
Indoor intake air wet-bulb temperature <W.B. :>
1.2
1
0.8
Cooling capacity ratio
0.6
-5051015202530354046
1.2
1.0
0.8
22
20
18
0.6
Cooling input ratio
16
0.4
Cooling input
-5051015202530354046
Outdoor intake air dry-bulb temperature <D.B. :>
Heating capacityHeating input
Indoor intake air dry-bulb temperature <D.B. :>
Indoor intake air wet-bulb temperature <W.B. :>
Outdoor intake air dry-bulb temperature <D.B. :>
Indoor intake air dry-bulb temperature <D.B. :>
22
20
18
16
Outdoor intake air wet-bulb temperature <W.B. :>Outdoor intake air wet-bulb temperature <W.B. :>
Note : These diagrams show the case where the operation frequency of a compressor is fixed.
18
12APPLICABLE EXTENSION PIPE FOR EACH MODEL
70m
[30m]
SW
SW : When the outdoor unit is located lower than
the indoor unit, set DIP SW8-1 on the outdoor
unit controller board to ON.
RP8
RP10
Liquid
pipe
(mm)
OD
Thick-
ness
OD
Thick-
ness
gas
pipe
(mm)
[
19.05
t1.0
20m
[20m]
20m
[20m]
[
22.2
t1.0
50m
[30m]
50m
[30m]
[
25.4
t1.0
Normal piping
70mw1
[30m]
70m
[30m]
[
28.58
t1.0
SW
70m
[30m]
70m
[30m]
[
19.05
t1.0
20m
[20m]
20m
[20m]
[
22.2
t1.0
50m
[30m]
50m
[30m]
[
25.4
t1.0
70m
[30m]
70m
[30m]
[
28.58
t1.0
SW
70m
[30m]
Normal piping
70mw1
[30m]
[
28.58
t1.0
SW
50m
[20m]
50m
[20m]
[
31.75
t1.0
w
2
SW
50m
[20m]
w
2
50m
[20m]
[
25.4
t1.0
50m
[20m]
50m
[20m]
[
22.2
t1.0
50m
[20m]
50m
[20m]
Note : The maximum pipe length is 80m in case of new piping.
w1 Be sure to use hard (tempered) one for pipe over [22.2.(Do not use soft (annealed) one.)
w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
<Table 1> Maximum pipe length (RP8·RP10)
<
Marks in the table above
>
[
9.52
t0.8
[
12.7
t0.8
[
15.88
t1.0
The maximum pipe length
Charge-less pipe length
: It can be used.
: Cooling capacity is lowered.➝ Refer to <Table6>
: Additional refrigerant charge is required when
the pipe length exceeds 20m.➝ Refer to <Table7>
Amount of additional refrigerant charge (kg)
30 m and less 31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less 71-80 m and less
0.9 kg1.8 kg2.7 kg3.6 kg
1.2 kg2.4 kg3.6 kg4.8 kg
Outdoor unit
permitted
pipe length
RP8
RP10
80m or less
At time of shipping
(kg)
10.5
10.5
No additional
charge necessary
The additional charge
amount is obtained by
the following formula.
Main piping:
Liquid line size
[9.52 overall length [m]
Main piping:
Liquid line size
[12.7 over all length [m]o 0.12 [kg/m]
–=
Additional charge amount
for 70 m
RP8 3.6 kg
RP10 4.8 kg
+
+
+
Calculate the additional charge amount based on the following procedure.
If the calculation results in an amount that is smaller than the "Additional charge amount for 70m," perform the additional charge using the amount shown
in "Additional charge amount for 70m."
12-1. 1:1 SYSTEM
(1) Pipe length
(2) Adjusting the amount of refrigerant
Check additional refrigerant charging amount referring to table 7 when the liquid pipe diameter is larger than
the standard size, and table 2 when the pipe of the standard diameter is used.
<Table 2>
19
(3) Capacity correction
70
75
80
85
90
95
100
5 10152025303540455055606570758085
Corrected pipe length (m)
Capacity ratio [%]
RP8·10
Heating RP8·10
70
75
80
85
90
95
100
510152025303540455055
Corrected pipe length [m]
Capacity ratio [%]
Heating RP8([22.2), RP10([25.4)
Cooling RP8([22.2)
Cooling RP10([25.4)
70
75
80
85
90
95
100
510152025
Corrected pipe length [m]
Cpacity ratio [%]
Cooling RP10([22.2)
Cooling RP8([19.05)
Heating RP8([19.05), RP10([22.2)
Cooling and heating capacity is lowered according to the piping length. Capacity can be obtained by referring
to the following capacity curves.
When the diameter of the gas pipe is smaller than the standard size, cooling capacity is lowered comparing to
the operation using the standard diameter pipe.
The lowered capacity can be obtained by referring to the capacity curves for gas pipe which is one or two size
smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends o 0.3 (m)
1. Capacity curves 1 <Standard size>
2. Capacity curves 2 <When the gas pipe's diameter is one-size-smaller than the standard
3. Capacity curves 3 <When the gas pipe's diameter is two-size-smaller than the standard
20
12-2. SYNCHRONIZED TWIN, TRIPLE AND QUADRUPLE SYSTEM
(1) Synchronized twin
Maximum pipe length (Main pipe[A]+Branch pipe diameter [ B and C ])
Main pipe
(mm)[A]
Branch
pipe
[mm]
[B, C]
w1 The maximum pipe length is 80m in case of new pipping.
w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
[6.35
[12.7
[9.52
[15.88
[9.52
[19.05
[12.7
[19.05
(2) Synchronized triple
Maximum pipe length (Main pipe [A] + Branch pipe [ B, C and D ])
Main pipe
(mm)[A]
Branch
pipe
[mm]
[B, C, D]
w1 The maximum pipe length is 80m in case of new pipping.
w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
Maximum pipe length (Main pipe[A]+Branch pipe [ B, C, D and E ])
Main pipe
(mm)[A]
Branch
pipe
[mm]
[B, C, D, E]
w1 The maximum pipe length is 80m in case of new pipping.
w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
: It can be used.
: Cooling capacity is lowered.➝ Refer to <Table6>
: Additional refrigerant charge is required when
the pipe length exceeds 20m.➝ Refer to <Table7>
The maximum pipe length
Charge-less pipe length
[9.52
Normal
sw
piping
70mw1
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
sw
sw
50m
[30m]
50m
[30m]
50m
[30m]
the indoor unit, set DIP SW8-1 on the outdoor
unit controller board to ON.
[12.7[15.88[9.52[12.7[15.88
20m
[20m]
20m
[20m]
20m
[20m]
50m
[30m]
50m
[30m]
50m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
sw
sw
sw
50m
50m
[20m]
[20m]
sw
50m
50m
[20m]
[20m]
sw
50m
50m
[20m]
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
w2
50m
[20m]
sw
w2
sw
20m
50m
[20m]
[20m]
sw
w2
sw
50m
20m
[20m]
[20m]
20m
[20m]
50m
[30m]
50m
[30m]
50m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
RP10 quadruple (RP2.5✕4)RP8 quadruple (RP2✕4)
20m
[20m]
20m
[20m]
20m
[20m]
50m
[30m]
50m
[30m]
50m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
Normal
piping
70mw1
[30m]
70m
[30m]
70m
[30m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
w2
50m
[20m]
w2
50m
[20m]
w2
50m
[20m]
21
Pipe diameter and thickness
OD
[6.35
(mm)
Thickness
(mm)
Be sure to use hard (tempered) one for pipe over [22.2.(Do not use soft (annealed) one.)
[9.52 [12.7[
0.8
0.80.81.01.01.01.01.0
15.88[19.05
[22.2 [25.4[
28.58
[
31.75
1.1
1
1
44
BC
2
4
D
1
4
E
1
1 Indoor unit
2
Outdoor unit
3
Main piping
4
Branch piping
5
Multi disttibution
pipe (option)
1
5
3
2
A
<Table 6> Lowered cooling capacity by the smaller gas pipe diameter
Pipe length
5m and less
6~10m
11~20m
21~30m
31~40m
41~50m
gas pipe [22.2gas pipe [19.05
100%
100~96%
96~91%
91~86%
86~83%
83~80%
100%
100~91%
91~81%
Height difference (Indoor unit-
1
Outdoor unit) Max. 40 m
Height difference (Indoor unit-
2
Indoor unit) Max. 1 m
Distance between indoor and indoor units
3
pipe length.
B—C B—D B—E
C—D C—E D—E
Number of pipe bends
4
Within 15
points8 points between main pipe A and
each branch pipe (B, C, D, E).
RP10 Cooling capacity ratioRP8 Cooling capacity ratio
gas pipe [25.4gas pipe [22.2
100%
100~98%
98~94%
94~91%
91~88%
88~86%
100%
100~95%
95~88%
<Table 7> Additional refrigerant amount when the liquid pipe of the larger diameter is used.
30 m and less 31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less 71-80 m and less
No additional
charge necessary
0.9 kg1.8 kg2.7 kg3.6 kg
1.2 kg2.4 kg3.6 kg4.8 kg
Amount of additional refrigerant charge (kg)
A+B+C+D
The additional charge
amount is obtained by
the following formula.
When length exceeds 70 m
When the total length of the piping exceeds 70 m, calculate the amount of additional charge based on the following requirements.
Note: If the calculation produces a negative number (i.e. a “minus” charge), of if calculation results in an amount that is less than the
“Additional charge amount for 70 m,”perform the additional charge using the amount shown in “Additional charge amount for 70 m.”
Amount of additional
charge
Additional charge amount
for 70 m
Main piping:
Liquid line size
[12.7 overall length
0.12
RP83.6 kg
RP10 4.8 kg
Main piping:
Liquid line size
+++
[9.52 overall length
0.09 (Gas line:[28.58)
Branch piping: Liquid
line size
[9.52 overall length
0.06 (Gas line: [15.88)
Branch piping: Liquid
line size
[6.35 overall length
0.02 (Gas line: [15.88)
–=
3.6 (kg)
1. Perform refrigerant piping connections for the indoor / outdoor unit while the outdoor unit's stopvalve is completely
closed (factory setting), and then vacuumize the refrigerant lines through the service port of the outdoor unit.
2. Open the stop valves of the outdoor unit completely.
This will completely connects the refrigerant lines of the indoor and outdoor units.
Handling of the stop valve is shown on the outdoor unit.
Note :
· Apply refrigerating machine oil over the flare seat surface. Do not apply to the threaded portion.
(It will cause the flare nut to loosen.)
· Use two wrenches to tighten piping connection.
· Use leak detector or soapy water to check for gas leaks after connections are completed.
· For the insulation of the connection at the indoor side, make sure to use the attached insulation materials and
thoroughly follow the instruction shown in the manual.
· Always use a non-oxidizing brazing material when brazing the pipes.
Adjusting the amount of refrigerant
Check additional refrigerant charging amount referring to the procedure 2 below when the liquid pipe diameter of the main
piping Ais larger than the standard size.
1 When the standard diameter pipe is used for the main piping A, calculate the additional refrigerant amount by
referring to <Table 2> as well as the 1:1 system.
2 When the liquid pipe diameter of the main piping A is one size larger than the standard size:
· When the extension pipe length (main piping + branch piping) does not exceeds 20m, adjustment of the
refrigerant is not necessary (charge-less).
· When the extension pipe length (main piping + branch piping) exceeds 20m, charge the amount of refrigerant
that is obtained by the formula shown in <Table 7>.
If the calculation produces a negative number (i.e. a "minus" charge), additional charging is not necessary.
Note: Apply 0 to L1 to L3 corresponding to the piping that are not used.
Correcting the capacity value
When calculating the lowered capacity by the extension pipe length, use the longest length between the indoor and the outdoor
units.
23
Refrigerant collecting (pump down)
OFF
12
ON
<SW4>
AB
CD
A Stop C operation
B Cooling D Heating
Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.
1 Before collecting the refrigerant, first make sure that the all of the SW5 DIP switches
for function changes on the control board of the outdoor unit are set to OFF. If all of the
SW5 switches are not set to OFF, record the settings and then set all of the switches
to OFF. Start collecting the refrigerant. After moving the unit to a new location and
completing the test run, set the SW5 switches to the previously recorded settings.
2
Supply power (circuit breaker).
* When power is supplied, make sure that “CENTRALLY CONTROLLED” is not
displayed on the remote controller. If “CENTRALLY CONTROLLED” is displayed, the refrigerant collecting (pump down) cannot be completed normally.
3
After the liquid stop valve is closed, set the SWP switch on the control board of the
outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and
outdoor units) start operating and refrigerant collecting operation begins. LED1
and LED2 on the control board of the outdoor unit are lit.
* Set the SWP switch (push-button type) to ON in order to perform refrigerant
collecting operation only when the unit is stopped.
However, refrigerant collecting operation cannot be performed until compressor stops even if the unit is stopped.
Wait three minutes until compressor is completely stopped and set the SWP
switch to ON again.
4 As the unit automatically stops after two or three minutes of refrigerant
collecting operation (LED1 if not lit and LED2 is lit), be sure to quickly
close the gas stop valve.
If the unit stops while both LED1 and LED2 are lit, open the liquid valve
completely, wait three minutes, then repeat the step 3.
* If the refrigerant collecting operation has been completed normally
(LED1 and LED2 are lit), the unit will remain stopped until the power
supply is turned off.
5 Turn off the power supply (circuit breaker).
* Note that when the length of the extension piping is long, it may not be
possible to perform a pump-down operation.When performing the pumpdown operation, make sure that the low pressure is lowered to near
0 MPa (gauge).
Unit replacement operation
· This model will automatically begin the replacement operation after it has been
installed when it enters the initialization phase for normal heating or cooling. Ho wever , the unit will not automatically perf orm the replacement operation if it is moved
to a new location where it will be used with existing R22 refrigerant piping. Under
such conditions, always use the SW8-2 operations to perform the replacement
operation before beginning the test operation.
Some models can perform the replacement operation only by SW8-2 operation.
Refer to the outdoor unit's Installation Manual for detail.
Replacement operation procedures (When moving the unit and connecting it
to existing R22 piping.)
1 Supply power.
2
Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start
replacement operation.
* The replacement operation is performed using the cooling system. Cool air will
flow from the indoor unit during the replacement operation.
* During the replacement operation,
and LED1 and LED2 on the control board of the outdoor unit flash together.
The duration of the replacement operation is determined by the length of the pip-
3
ing. Alwa ys perform the replacement operation f or longer than the stipulated time.
* Always perform one of the following operations at the completion of the re-
placement operation. The replacement operation will end and the unit will automatically stop.
TEST RUN
is displayed on the remote controller
(1)Set SW8-2 from ON to OFF. (When ending a replacement operation of less
than 2 hours.)
· Each time SW8-2 is set from OFF to ON, the replacement operation can be
started. Always perf orm the replacement operation for longer than the stipulated time.
Required replacement operation times
Piping Length
0 to 20 meters30 minutes or more
21 to 30 meters45 minutes or more
31 to 70 meters60 minutes or more
(2)The replacement operation will automatically stop after 2 hours. (It will end with
SW8-2 still in the ON position.)
· When the replacement operation has ended automatically after 2 hours of
operation, there is no need to set SW8-2 from ON to OFF; normal air conditioning operations can bestarted with the SW8-2 being set to ON.However, to repeat the replacement operation, SW8-2 will have to be returned
to OFF and then set to ON.
* If the indoor temperature is below 15:, the compressor will operate
intermittently but the unit is not faulty.
Replacement
Operation Time
Start and finish of test run
• Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit
By using the DIP switch SW4 on the control board of the outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
1Set the operation mode (cooling/heating) using SW4-2.
2Turn on SW4-1 to start test run with the operation mode set by SW4-2.
3Turn off SW4-1 to finish the test run.
• There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion pipe is just moving to adjust opening pulse.
• There may be a knocking sound around the machine room for several seconds after compressor
starts operating, but this is no problem with product because the check valve, itself, generates the
sound because pressure difference is small in the refrigerant circuit.
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
24
13TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is
reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according
to “13-4. SELF-DIAGNOSIS ACTION TABLE”.
Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “13-5. TROUBLESHOOTING BY INFERIOR PHENOMENA”.
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, matters related to wiring
and etc.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
1Re-check the abnormal symptom.
2Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “13-5.
TROUBLE SHOOTING BY INFERIOR PHENOMENA”.
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality concerning of parts such as
electrical component, controller circuit board,
remote controller and etc.
13-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.
Actions to be taken for service, which depends on whether or not the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
25
13-2. CHECK POINT UNDER TEST RUN
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
TEST RUN button
TEST RUN display
LIQUID PIPE TEMPERATURE display
(MA remote controller)
(1) Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Merger and
check that it is 1.0M" or over.
wDon’t use 500V Merger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Make sure that all of the SW5 switches for function changes on the control board of the outdoor unit are set to OFF. If all of
the SW5 switches are not set to OFF, record the settings and then set all of the switches to OFF. And perform emergency
operation. After finishing emergency operation, set the SW5 switches to the recorded settings.
• Turn on power supply twelve hours before test run in order to protect compressor.
• For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “Selection of Functions through Remote Controller”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
13-2-1. Test run by remote controller
A
B
Operating procedures
1. Turn on the main power supply.
2. Press TEST button twice.
3. Press OPERATION SWITCH
button.
4. Press AIR DIRECTION
5. Check the outdoor unit fan for
correct running.
6. Press the ON/OFF button to reset the test run in progress.
7. Turn off the main power supply.
B button.
While the room temperature display on the remote
controller is “H0”, the remote controller is disabled.
Wait until “H0” disappears before using remote controller.
“H0” appears for about 2 minutes after power supply is
turned on. w1
The TEST appears on the screen.
Cooling mode:
A
Heating mode: Check if warm air blows. (It takes a little
while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to
provide optimum fan speeds. Therefore, the fan keeps
running at a low speed to meet the current outside air
condition unless it exceeds its available maximum power.
Then, in actuality, the fan may stop or run in the reverse
direction depending on the outside air, but this does not
mean malfunction.
Check if cool air blows and water is drained.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after two hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin and triple operation. Malfunctions may not
be displayed regardless of incorrect wiring.
w1 After turning on the power supply, the system will go into startup mode, “H0” will blink on the display section of the room
temperature, and lamp(red) of the remote controller will flash.
As to INDOOR BOARD LED, LED1 and LED2 will be lit up in case the address is 0, or turned off in case the address is not
0. LED3 will blink.
As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will light up. (After the startup mode of the system finishes,
LED2(red) will be turned off.)
In case OUTDOOR BOARD LED is digital display, — and —will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from
the symptoms.
The below symptoms are under test run mode. “startup” in the table means the display status of w1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “H0”, and
cannot be operated.
After power is turned on, “H0” is displayed
for 3 minutes, then error code is
displayed.
No display appears even when remote
controller operation switch is turned on.
(Operation lamp does not light up.)
Display appears but soon disappears
even when remote controller is operated.
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed,
green(once) and red(once) blink
alternately. <F1>
After “startup” is displayed,
green(once) and red(twice) blink
alternately. <F3, F4, F9>
After “startup” is displayed,
green(twice) and red(once) blink
alternately. <EA. Eb>
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed, only
green lights up. <00>
• After power is turned on, “H0” is displayed for 2 minutes during
system startup. (Normal)
• Incorrect connection of outdoor terminal block (L, N and S1,
S2, S3.)
• Outdoor unit’s safeguard installation connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity
is wrong for S1, S2, S3.)
• Remote controller transmission wire short.
• There is no outdoor unit of address 0.
(Address is other than 0.)
• Remote controller transmission wire burnout.
• After canceling function selection, operation is not possible for
about 30 seconds. (Normal)
Cause
26
Loading...
+ 60 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.