TECHNICAL DATA BOOK
CONTENTS
1. REFERENCE SERVICE MANUAL·············································2
2. SPECIFICATIONS ······································································3
3. OUTLINES AND DIMENSIONS················································30
4. WIRING DIAGRAM···································································54
5. REFRIGERANT SYSTEM DIAGRAM ······································75
6. PERFORMANCE CURVES ······················································80
7. CORRECTION FACTORS ························································82
8. APPLICABLE EXTENSION PIPE FOR EACH MODEL ··········83
9. AIR FLOW DATA ······································································92
10. NOISE CRITERION CURVES·················································111
11. OPTIONAL PARTS···································································124
<Indoor unit>
[Model names]
R410A
PLA-RP·BA(2)
PLA-RP·AA(2)
PEAD-RP·EA(2)
PEAD-RP·GA
PEA-RP·GA
PKA-RP·GAL
PKA-RP·FAL(2)
PCA-RP·GA(2)
PCA-RP·HA
PSA-RP·GA
<Outdoor unit>
[Model names]
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
PUHZ-RP35/50/60/71/100/125/140VHA2
PUHZ-RP35/50/60/71/100VHA3
PUHZ-RP100/125/140YHA2
PUHZ-RP100YHA3
PUHZ-RP200/250YHA2
April 2008
INVERTER
kW Model
No. OCS05
REVISED EDITION-E
Revision:
• PLA-RP·BA2 and PUHZRP·HA3 are added in
REVISED EDITION-E.
• Some descriptions have been
modified.
• Please void OCS05 REVISED
EDITION-D.
For information on service, please refer to the service manual as follows.
Model name Service Ref. Service
Manual No.
PLA-RP35/50/60/71AA
PLA-RP35/50/60/71/100/125/140BA
PLA-RP71/100/125BA2
PLA-RP35/50/60/71/100/125/140BA
(1).UK
PLA-RP71/100/125BA2.UK
PLA-RP35/50/60/71/100/125/140BA
PLA-RP35/50/60/71AA.UK
PLA-RP35/50/60/71AA
OC335
OCH412
OCB412
OCH416
OCB416
OC327
PLA-RP100/125/140AA2
OC357
PLA-RP100/125/140AA2.UK
PCA-RP50/60/71/100/125/140GA PCA-RP50/60/71/100/125/140GA
OC328
PCA-RP50GA2
PCA-RP50GA2
PCA-RP71/125HA PCA-RP71/125HA
OC329
PKA-RP35/50GAL PKA-RP35/50GAL
OC330
PKA-RP60/71/100FAL
PKA-RP50FAL2
PKA-RP60/71/100FAL
PKA-RP50FAL2
OC331
PSA-RP71/100/125/140GA PSA-RP71/100/125/140GA
OC332
PEAD-RP50/60/71/125/140EA
PEAD-RP50/60/71/125/140EA.UK
HWE05210
PEAD-RP35/100EA2
PEAD-RP35/100EA2.UK
PEAD-RP60/71/100GA PEAD-RP60/71/100GA.UK
HWE05060
PEA-RP200/250/400/500GA PEA-RP200/250/400/500GA.TH-AF
PEA-RP200/250GA.TH-AFMF
HWE0708A
1-2. OUTDOOR UNIT
Model name Service Ref. Service
Manual No.
PUHZ-RP35/50/60/71VHA2
PUHZ-RP100/125/140VHA2
PUHZ-RP100/125/140YHA2
PUHZ-RP35/50/60/71/100VHA3
PUHZ-RP100YHA3
PUHZ-RP35/50/60/71VHA2
(1)
PUHZ-RP100/125/140VHA2(1)
PUHZ-RP100/125/140YHA2(1)
PUHZ-RP35/50/60/71/100VHA3
PUHZ-RP100YHA3
PUHZ-RP60/71/100VHA3#1
PUHZ-RP100YHA3#1
PUHZ-RP125/140VHA2#2
PUHZ-RP125/140YHA2#2
OC374
OCH428
OCB428
PUHZ-RP200/250YHA2
PUHZ-RP200/250YHA2
1-1. INDOOR UNIT
1
REFERENCE SERVICE MANUAL
3
2
SPECIFICATIONS
2-1. CEILING CASSETTE TYPE
Model name Indoor unit PLA-RP35BA PLA-RP50BA
Outdoor unit PUHZ-RP35VHA2 PUHZ-RP50VHA2
PUHZ-RP35VHA3 PUHZ-RP50VHA3
Cooling Capacity Btu/h 12,300 17,100
kW 3.6(1.6-4.5) 5.0(2.3-5.6)
Total input kW 1.07 1.55
EER 3.36 3.23
Energy label class
AA
SHF 0.84 0.81
Heating Capacity Btu/h 14,000 20,500
kW 4.1(1.6-5.2) 6.0(2.5-7.3)
Total input kW 1.12 1.66
COP 3.66 3.61
Energy label class A A
Booster heater kW ––
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16
Indoor unit Air flow CMM 11-12-13-15 12-14-16-18
(Low-Medium2-Medium1-High)
CFM 390-425-460-530 425-495-565-635
External pressure Pa 0 0
Sound level
dB(A) 27-28-29-31 28-29-31-32
(Low-Medium2-Medium1-High)
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/8)
Weight kg 22(6)
Unit (Panel) lbs 49(13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 35
CFM 1,240
Sound level at cooling
dB(A) 44
Sound level at heating
dB(A) 46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800
D : mm 300+23
H : mm 600
W : inch 31-1/2
D : inch 11-13/16 + 7/8
H : inch 23-5/8
Weight kg 45(VHA2)/42(VHA3)
lbs 99(VHA2)/92(VHA3)
Refrigerant pipe size Gas side O.D. mm 12.7
inch 1/2
Liquid side O.D. mm 6.35
inch 1/4
Refrigerant pipe length
Height difference
m Max. 30
Length
m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
Cooling
Upper limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 46˚ C
Lower limit
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
Heating
Upper limit
D.B. 28˚ C
D.B. 21˚ C, W.B. 15˚ C
Lower limit
D.B. 17˚ C
D.B. -11˚ C, W.B. -12˚ C
4. Above data are based on the indicated voltage.
w If optional air protect guide installed. D.B.-15:
Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz
Model name Indoor unit PLA-RP60BA PLA-RP71BA
Outdoor unit PUHZ-RP60VHA2
PUHZ-RP60VHA3
PUHZ-RP71VHA2
Cooling Capacity Btu/h 20,500 24,200
kW 6.0(2.7-6.7) 7.1(3.3-8.1)
Total input kW 1.65 2.12
EER 3.64 3.35
Energy label class A A
SHF 0.76 0.73
Heating Capacity Btu/h 23,900 27,300
kW 7.0(2.8-8.2) 8.0(3.5-10.2)
Total input kW 1.85 2.21
COP 3.78 3.61
Energy label class A A
Booster heater kW ––
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 25
Indoor unit Air flow CMM 12-14-16-18 14-16-18-21
(Low-Medium2-Medium1-High)
CFM 425-495-565-635 495-565-635-740
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 28-29-31-32 28-30-32-34
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/8)
Weight kg 23(6)
Unit (Panel) lbs 51(13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 55
CFM 1,940
Sound level at cooling
Sound level at heating
dB(A) 47
dB(A) 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8
Weight kg 75(VHA2)/68(VHA3)
lbs 165(VHA2)/150(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Upper limit
Heating
Lower limit
Height difference
Length
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C
m Max. 30
m Max. 50
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PLA-RP71BA2 PLA-RP125BA2
Outdoor unit PUHZ-RP71VHA3 PUHZ-RP125VHA2
Cooling Capacity Btu/h 24,200 42,700
kW 7.1(3.3-8.1) 12.5(5.5-14.0)
Total input kW 1.94 3.73
EER 3.66 3.35
Energy label class A A
SHF 0.73 0.71
Heating Capacity Btu/h 27,300 47,800
kW 8.0(3.5-10.2) 14.0(5.0-16.0)
Total input kW 1.90 3.51
COP 4.21
PLA-RP100BA2
PUHZ-RP100VHA3
34,100
10.0(4.9-11.4)
2.44
4.10
A
0.74
38,200
11.2(4.5-14.0)
2.54
4.41 3.99
Energy label class A A
Booster heater kW ––A–
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32 25
Indoor unit Air flow CMM 14-16-18-21 22-25-28-31
(Low-Medium2-Medium1-High)
CFM 495-565-635-740 780-880-990-1090
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 28-30-32-34
20-23-26-30
710-810-920-1060
0
32-34-37-40 34-36-39-41
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (35) 298 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/8) 11-3/4 (1-3/8)
Weight kg
Unit (Panel) lbs
23(6)
51(13)
27(6)
60(13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling
Sound level at heating
dB(A) 47 50
dB(A) 48
55
1,940
49
51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943 1,350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8 53-1/8
Weight kg 68 116
lbs 150 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Upper limit
Lower limit
Upper limit
Lower limit
Height difference
Length
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
m Max. 30
m Max. 75 Max. 50
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Model name Indoor unit PLA-RP100BA PLA-RP125BA PLA-RP140BA
Outdoor unit PUHZ-RP100VHA2 PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.02 3.87 4.65
EER 3.31 3.23 3.01
Energy label class A A B
SHF 0.74 0.71 0.71
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.10 3.88 4.43
COP 3.61 3.61 3.61
Energy label class A A A
Booster heater kW –––
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32
Indoor unit Air flow CMM 20-23-26-30 22-25-28-31
(Low-Medium2-Medium1-High)
CFM 710-810-920-1060 780-880-990-1090
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 32-34-37-40 34-36-39-41
40
24-26-29-32
850-920-1020-1130
0
36-39-42-44
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/8)
Weight kg 27(6)
Unit (Panel) lbs 60(13)
25(6)
55(13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling
Sound level at heating
dB(A) 49 50
dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121 116
lbs 267 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Upper limit
Lower limit
Upper limit
Lower limit
Height difference
Length
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5: w
D.B. 28˚ C
D.B. 17˚ C
m Max. 30
m Max. 75
D.B. 46:
D.B. 21:, W.B. 15:
D.B. -20:, W.B. -20:
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Model name Indoor unit PLA-RP100BA PLA-RP125BA PLA-RP140BA
Outdoor unit PUHZ-RP100YHA2 PUHZ-RP125YHA2 PUHZ-RP140YHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.02 3.87 4.65
EER 3.31 3.23 3.01
Energy label class
AAB
SHF 0.74 0.71 0.71
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.10 3.88 4.43
COP 3.61 3.61 3.61
Energy label class
AAA
Booster heater kW –––
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 20-23-26-30 22-25-28-31
(Low-Medium2-Medium1-High)
CFM 710-810-920-1060 780-880-990-1090
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 32-34-37-40 34-36-39-41
24-26-29-32
850-920-1020-1130
0
36-39-42-44
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/8)
Weight kg 27 (6)
Unit (Panel) lbs 60 (13)
25 (6)
55 (13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling
Sound level at heating
dB(A) 49 50
dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135 130
lbs 298 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit
Lower limit
Upper limit
Lower limit
m Max. 30
m Max. 75
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -20˚ C, W.B. -20˚ C
3. Guaranteed voltage
Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
Model name Indoor unit PLA-RP100BA2 PLA-RP125BA2
Outdoor unit PUHZ-RP100YHA3 PUHZ-RP125YHA2
Cooling Capacity Btu/h 34,100 42,700
kW 10.0(4.9-11.4) 12.5(5.5-14.0)
Total input kW 2.50 3.79
EER 4.00 3.30
Energy label class
AA
SHF 0.74 0.71
Heating Capacity Btu/h 38,200 47,800
kW 11.2(4.5-14.0) 14.0(5.0-16.0)
Total input kW 2.60 3.57
COP 4.31 3.92
Energy label class
AA
Booster heater kW ––
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 20-23-26-30 22-25-28-31
(Low-Medium2-Medium1-High)
CFM 710-810-920-1060 780-880-990-1090
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 32-34-37-40 34-36-39-41
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/8)
Weight kg 27 (6)
Unit (Panel) lbs 60 (13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling
Sound level at heating
dB(A) 49 50
dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 130
lbs 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit
Lower limit
Upper limit
Lower limit
m Max. 30
m Max. 75
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -20˚ C, W.B. -20˚ C
3. Guaranteed voltage
Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
Model name Indoor unit PLA-RP35AA PLA-RP50AA
Outdoor unit PUHZ-RP35VHA2 PUHZ-RP50VHA2
Cooling Capacity Btu/h 12,300 17,100
kW 3.6(1.6-4.5) 5.0(2.3-5.6)
Total input kW 1.07 1.55
EER 3.36 3.23
Energy label class A A
SHF 0.89 0.86
Heating Capacity Btu/h 14,000 20,500
kW 4.1(1.6-5.2) 6.0(2.5-7.3)
Total input kW 1.12 1.62
COP 3.66 3.70
Energy label class A A
Booster heater kW - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16
Indoor unit Air flow CMM 11-12-13-14 14-15-16-18
(Low-Medium2-Medium1-High) CFM 390-425-460-495 495-530-565-635
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 27-28-29-31 28-29-31-33
External finish (Panel) White Munsell 0.70Y 8.59/0.97
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/16)
Weight kg 24 (5)
Unit (Panel) lbs 53 (11)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 35
CFM 1,240
Sound level at cooling dB(A) 44
Sound level at heating dB(A) 46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800
D : mm 300+23
H : mm 600
W : inch 31-1/2
D : inch 11-13/16 + 7/8
H : inch 23-5/8
Weight kg 45
lbs 99
Refrigerant pipe size Gas side O.D. mm 12.7
inch 1/2
Liquid side O.D. mm 6.35
inch 1/4
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PLA-RP60AA PLA-RP71AA
Outdoor unit PUHZ-RP60VHA2 PUHZ-RP71VHA2
Cooling Capacity Btu/h 20,500 24,200
kW 6.0(2.7-6.7) 7.1(3.3-8.1)
Total input kW 1.65 1.97
EER 3.64 3.60
Energy label class A A
SHF 0.78 0.74
Heating Capacity Btu/h 23,900 27,300
kW 7.0(2.8-8.2) 8.0(3.5-10.2)
Total input kW 1.85 2.34
COP 3.78 3.42
Energy label class A B
Booster heater kW - -
Power supply Phase
[
1
Cycle Hz 50
Voltage V 230
Breaker size A 25
Indoor unit Air flow CMM 14-15-16-18 15-16-18-20
(Low-Medium2-Medium1-High) CFM 495-530-565-635 530-565-635-705
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 28-29-31-33 28-30-32-34
External finish (Panel) White Munsell 0.70Y 8.59/0.97
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/16)
Weight kg 24 (5)
Unit (Panel) lbs 53 (11)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 55
CFM 1,940
Sound level at cooling dB(A) 47
Sound level at heating dB(A) 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8
Weight kg 75
lbs 165
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
Outdoor unit PUHZ-RP100VHA2 PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.02 3.87 4.65
EER 3.31 3.23 3.01
Energy label class A A B
SHF 0.78 0.74 0.71
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.02 3.88 4.69
COP 3.61 3.61 3.41
Energy label class A A B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32 40
Indoor unit Air flow CMM 19-21-23-27 24-25-27-30
(Low-Medium2-Medium1-High)
CFM 670-740-810-950 850-880-950-1060
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 33-36-39-41 37-40-43-45
External finish (Panel) White Munsell 0.70Y 8.59/0.97
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/16)
Weight kg 32 (5)
Unit (Panel) lbs 71 (11)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121 116
lbs 267 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5: w
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15:
D.B. -20:, W.B. -20:
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
Outdoor unit PUHZ-RP100YHA2 PUHZ-RP125YHA2 PUHZ-RP140YHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.02 3.87 4.65
EER 3.31 3.23 3.01
Energy label class A A B
SHF 0.78 0.74 0.71
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.02 3.88 4.69
COP 3.61 3.61 3.41
Energy label class A A B
Booster heater kW - - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 19-21-23-27 24-25-27-30
(Low-Medium2-Medium1-High)
CFM 670-740-810-950 850-880-950-1060
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 33-36-39-41 37-40-43-45
External finish (Panel) White Munsell 0.70Y 8.59/0.97
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/16)
Weight kg 32 (5)
Unit (Panel) lbs 71 (11)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135 130
lbs 298 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -20˚ C, W.B. -20˚ C
3. Guaranteed voltage
Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
2-2. CEILING-CONCEALED TYPE
Model name Indoor unit PEAD-RP35EA2 PEAD-RP50EA
Outdoor unit PUHZ-RP35VHA2 PUHZ-RP50VHA2
PUHZ-RP35VHA3 PUHZ-RP50VHA3
Cooling Capacity Btu/h 12,300 16,700
kW 3.6(1.6-4.5) 4.9(2.3-5.6)
Total input kW 1.12 1.52
EER 3.21 3.22
Energy label class A A
SHF 0.89 0.82
Heating Capacity Btu/h 14,000 20,500
kW 4.1(1.6-5.2) 6.0(2.5-7.3)
Total input kW 1.20 1.65
COP 3.41 3.64
Energy label class B A
Booster heater kW - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16
Indoor unit Air flow CMM 13.5-17
(Low-High) CFM 476-600
External pressure Pa 30(70)
Sound level dB(A) 36-40
(Low-High) (70Pa : 38-44)
External finish Galvanized sheets
Dimension W : mm 935
D : mm 700
H : mm 295
W : inch 36-13/16
D : inch 27-5/8
H : inch 11-5/8
Weight kg 33 35
lbs 73 77
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 35
CFM 1,240
Sound level at cooling dB(A) 44
Sound level at heating dB(A) 46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800
D : mm 300+23
H : mm 600
W : inch 31-1/2
D : inch 11-13/16 + 7/8
H : inch 23-5/8
Weight kg 45(VHA2)/42(VHA3)
lbs 99(VHA2)/92(VHA3)
Refrigerant pipe size Gas side O.D. mm 12.7
inch 1/2
Liquid side O.D. mm 6.35
inch 1/4
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Upper limit
Heating
Lower limit
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PEAD-RP60EA PEAD-RP71EA
Outdoor unit PUHZ-RP60VHA2 PUHZ-RP71VHA2
PUHZ-RP60VHA3 PUHZ-RP71VHA3
Cooling Capacity Btu/h 20,500 24,200
kW 6.0(2.7-6.7) 7.1(3.3-8.1)
Total input kW 1.86 2.15
EER 3.23 3.30
Energy label class A A
SHF 0.79 0.83
Heating Capacity Btu/h 23,900 27,300
kW 7.0(2.8-8.2) 8.0(3.5-10.2)
Total input kW 1.90 2.34
COP 3.68 3.42
Energy label class A B
Booster heater kW - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 25
Indoor unit Air flow CMM 17-21 20-25
(Low-High) CFM 600-741 706-883
External pressure Pa 30(70) 70(130)
Sound level dB(A) 37-41 37-41
(Low-High) (70Pa : 39-46) (130Pa : 40-45)
External finish Galvanized sheets
Dimension W : mm 1175
D : mm 700 740
H : mm 295
325
W : inch 46-1/8
D : inch 27-5/8 29-1/8
H : inch 11-5/8
12-13/16
Weight kg 42 44
lbs 92 97
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 55 55
CFM 1,940 1,940
Sound level at cooling dB(A) 47 47
Sound level at heating dB(A) 48 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950 950
D : mm 330+30 330+30
H : mm 943 943
W : inch 37-3/8 37-3/8
D : inch 13 + 1-3/16 13 + 1-3/16
H : inch 37-1/8 37-1/8
Weight kg 75(VHA2)/68(VHA3)
lbs 165(VHA2)/150(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88 15.88
inch 5/8 5/8
Liquid side O.D. mm 9.52 9.52
inch 3/8 3/8
Refrigerant pipe length Height difference m Max. 30 Max. 30
Length m Max. 50 Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Upper limit
Heating
Lower limit
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
Outdoor unit PUHZ-RP100VHA2
PUHZ-RP100VHA3
PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.06 3.89 4.65
EER 3.27 3.21 3.01
Energy label class A A B
SHF 0.86 0.82 0.83
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.19 3.88 4.69
COP 3.51 3.61 3.41
Energy label class B A B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32 40
Indoor unit Air flow CMM 33.5-42 36.5-46
(Low-High) CFM 1183-1483 1288-1624
External pressure Pa 70(130)
Sound level dB(A) 44-50 46-51
(Low-High) (130Pa : 46-52) (130Pa : 47-53)
External finish Galvanized sheets
Dimension W : mm 1415 1715
D : mm 740
H : mm 325
W : inch 55-11/16 67-1/2
D : inch 29-1/8
H : inch 12-13/16
Weight kg 65 70
lbs 143 154
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121(VHA2)/116(VHA3) 116
lbs 267(VHA2)/256(VHA3) 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5: w
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15:
D.B. -20:, W.B. -20:
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
Outdoor unit
PUHZ-RP100YHA2
PUHZ-RP100YHA3
PUHZ-RP125YHA2 PUHZ-RP140YHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.06 3.89 4.65
EER 3.27 3.21 3.01
Energy label class A A B
SHF 0.86 0.82 0.83
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.19 3.88 4.69
COP 3.51 3.61 3.41
Energy label class B A B
Booster heater kW - - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 33.5-42 36.5-46
(Low-High) CFM 1183-1483 1288-1624
External pressure Pa 70(130)
Sound level dB(A) 44-50 46-51
(Low-High) (130Pa : 46-52) (130Pa : 47-53)
External finish Galvanized sheets
Dimension W : mm 1415 1715
D : mm 740
H : mm 325
W : inch 55-11/16 67-1/2
D : inch 29-1/8
H : inch 12-13/16
Weight kg 65 70
lbs 143 154
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135(YHA2)/130(YHA3) 130
lbs 298(YHA2)/287(YHA3) 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -20˚ C, W.B. -20˚ C
3. Guaranteed voltage
Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
Model name Indoor unit PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
Outdoor unit PUHZ-RP60VHA2 PUHZ-RP71VHA2 PUHZ-RP100VHA2
PUHZ-RP60VHA3 PUHZ-RP71VHA3 PUHZ-RP100VHA3
Cooling Capacity Btu/h 20,500 24,200 34,100
kW 6.0(2.7-6.7) 7.1(3.3-8.1) 10.0(4.9-11.4)
Total input kW 1.68 2.15 3.08
EER 3.57 3.30 3.25
Energy label class A A A
SHF 0.88 0.83 0.86
Heating Capacity Btu/h 23,900 27,300 38,200
kW 7.0(2.8-8.2) 8.0(3.5-10.2) 11.0(4.5-14.0)
Total input kW 1.77 2.34 3.23
COP 3.95 3.42 3.41
Energy label class A B B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 25 32
Indoor unit Air flow CMM 16.5-21 20-25 26.5-33
(Low-High) CFM 582-741 706-883 935-1165
External pressure Pa 10/50/70 10/50/70
Sound level dB(A) 33-37/35-40/36-42 35-38/37-41/37-43 40-43/42-45/42-46
(Low-High) (10/50/70Pa) (10/50/70Pa) (10/50/70Pa)
External finish Galvanized sheets
Dimension W : mm 1171 1411
D : mm 740
H : mm 275
W : inch 46-1/8 55-9/16
D : inch 29-1/8
H : inch 10-13/16
Weight kg 42 50
lbs 93 111
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 55 100
CFM 1,940 3,530
Sound level at cooling dB(A) 47 49
Sound level at heating dB(A) 48 51
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8 53-1/8
Weight kg 75(VHA2)/68(VHA3) 121(VHA2)/116(VHA3)
lbs 165(VHA2)/150(VHA3) 267(VHA2)/256(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30 Max. 30
Length m Max. 50 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w 1
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C w 2
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w1. If optional air protect guide installed. D.B.-15:
w2. For RP100 D.B. -20:, W.B. -20:
Single phase 230V 50Hz
Model name Indoor unit PEAD-RP100GA
Outdoor unit PUHZ-RP100YHA2
PUHZ-RP100YHA3
Cooling Capacity Btu/h 34,100
kW 10.0(4.9-11.4)
Total input kW 3.08
EER 3.25
Energy label class A
SHF 0.86
Heating Capacity Btu/h 38,200
kW 11.0(4.5-14.0)
Total input kW 3.23
COP 3.41
Energy label class B
Booster heater kW -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 26.5-33
(Low-High) CFM 935-1165
External pressure Pa 10/50/70
Sound level dB(A) 40-43/42-45/42-46
(Low-High) (10/50/70Pa)
External finish Galvanized sheets
Dimension W : mm 1411
D : mm 740
H : mm 275
W : inch 55-9/16
D : inch 29-1/8
H : inch 10-13/16
Weight kg 50
lbs 111
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49
Sound level at heating dB(A) 51
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 943
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135
(YHA2)/130(YHA3)
lbs 298(YHA2)/287(YHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -20˚ C, W.B. -20˚ C
3. Guaranteed voltage
Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
Model name Indoor unit PEA-RP200GA PEA-RP250GA
Outdoor unit PUHZ-RP200YHA2 PUHZ-RP250YHA2
Cooling Capacity Btu/h 65,000 75,000
kW 19.0(9.0-22.4) 22.0(11.2-28.0)
Total input kW 6.70 8.34
EER
Energy label class
2.84 2.64
CD
SHF 0.81 0.86
Heating Capacity Btu/h 76,000 92,000
kW 22.4(9.5-25.0) 27.0(12.5-31.5)
Total input kW 6.50 8.20
COP 3.45 3.29
Energy label class B C
Booster heater kW - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A Indoor 15 / Outdoor 32
Indoor unit Air flow CMM 52-65 64-80
(Low-High) CFM 1835-2295 2260-2825
External pressure Pa 150
Sound level dB(A) 48-51 49-52
(Low-High)
External finish Galvanized steel
Dimension W : mm 1600 1400
D : mm 634
H : mm 400
W : inch 63 55-1/8
D : inch 25
H : inch 15-3/4
Weight kg 70 77
lbs 155 170
Unit drain pipe R1
Outdoor unit Air flow CMM 130
CFM 4590
Sound level at cooling dB(A) 58
Sound level at heating dB(A) 59
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135
lbs 298
Refrigerant pipe size Gas side O.D. mm 25.4
inch 1
Liquid side O.D. mm 12.7
inch 1/2
9.52
3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 120
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w 1
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -20˚ C, W.B. -20˚ C
3. Guaranteed voltage
342~457V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit 3 phase 400V 50Hz
Outdoor unit
w 1. If optional air protect guide is installed : D.B.-15:
3 phase 400V 50Hz
136
300
Model name Indoor unit PKA-RP35GAL PKA-RP50GAL
Outdoor unit PUHZ-RP35VHA2 PUHZ-RP50VHA2
Cooling Capacity Btu/h 12,300 15,700
Total input kW 1.03 1.63
EER 3.50 2.82
Energy label class A C
SHF 0.84 0.74
Heating Capacity Btu/h 14,000 15,400
Total input kW 1.27 1.40
COP 3.23 3.21
Energy label class C C
Booster heater kW - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16
Indoor unit Air flow CMM 9-10-11-12
(Low-Medium2-Medium1-High) CFM 320-355-390-425
External pressure Pa 0
Sound level
(Low-Medium2-Medium1-High)
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 990
Weight kg 16
Field drain pipe I.D. mm 20
Outdoor unit Air flow CMM 35
Sound level at cooling dB(A) 44
Sound level at heating dB(A) 46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800
Weight kg 45(VHA2)/42(VHA3)
Refrigerant pipe size Gas side O.D. mm 12.7
Liquid side O.D. mm 6.35
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
kW 3.6(1.6-4.5) 4.6(2.3-5.4)
kW 4.1(1.6-5.2) 4.5(2.5-6.2)
dB(A) 36-38-41-43
D : mm 235
H : mm 340
W : inch 39
D : inch 9-1/4
H : inch 13-3/8
lbs 35
inch 13/16
CFM 1,240
D : mm 300+23
H : mm 600
W : inch 31-1/2
D : inch 11-13/16 + 7/8
H : inch 23-5/8
lbs 99(VHA2)/92(VHA3)
inch 1/2
inch 1/4
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C
PUHZ-RP35VHA3 PUHZ-RP50VHA3
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL
Outdoor unit PUHZ-RP60VHA2 PUHZ-RP71VHA2 PUHZ-RP100VHA2
Cooling Capacity Btu/h 20,500 24,200 34,100
kW 6.0(2.7-6.7) 7.1(3.3-8.1) 10.0(4.9-11.4)
Total input kW 1.55 1.98 2.93
EER 3.87 3.59 3.41
Energy label class A A A
SHF 0.83 0.77 0.77
Heating Capacity Btu/h 23,900 27,300 38,200
kW 7.0(2.8-8.2) 7.6(3.5-10.2) 11.2(4.5-14.0)
Total input kW 2.01 2.23 3.25
COP 3.48 3.41 3.45
Energy label class B B B
Booster heater kW - - -
Power supply
Phase
Cycle
[ 1
Hz 50
PKA-RP50FAL2
PUHZ-RP50VHA2
PUHZ-RP50VHA3
17,000
5.0(2.3-5.6)
1.66
3.01
B
0.86
20,500
6.0(2.5-7.3)
1.76
3.41
B
-
PUHZ-RP60VHA3 PUHZ-RP71VHA3 PUHZ-RP100VHA3
Voltage V 230
Breaker size A 25 32
Indoor unit Air flow CMM 15-20 22-28
(Low-High)
External pressure
Sound level
(Low-High)
CFM 530-705 780-990
Pa 0
dB(A) 39-45 41-46
16
15-20
530-705
39-45
External finish Munsell 3.4Y 7.7/0.8
Dimension W : mm 1400 1680
1400
D : mm 235
H : mm 340
W : inch 55-1/8 66-1/8
55-1/8
D : inch 9-1/4
H : inch 13-3/8
Weight kg 24 28
lbs 53 62
24
53
Field drain pipe I.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 55 100
CFM 1,940 3,530
Sound level at cooling
dB(A) 47 49
Sound level at heating dB(A) 48 51
35
1,240
44
46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8 53-1/8
Weight kg 75(VHA2)/68(VHA3)
lbs 165(VHA2)/150(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30 Max. 30
Length m Max. 50 Max. 75
800
300+23
600
31-1/2
11 - 13/16
23-5/8
45(VHA2)/42(VHA3)
99(VHA2)/92(VHA3)
12.7
1/2
6.35
1/4
Max. 30
Max. 50
950
330+30
37-3/8
13 + 1-3/16
121(VHA2)/116(VHA3)
267(VHA2)/256(VHA3)
15.88
5/8
9.52
3/8
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w 1
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C w 2
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w1. If optional air protect guide installed. D.B.-15:
w2. For RP100 D.B. -20:, W.B. -20:
Single phase 230V 50Hz
Model name Indoor unit PKA-RP100FAL
Outdoor unit PUHZ-RP100YHA2
PUHZ-RP100YHA3
Cooling Capacity Btu/h 34,100
kW 10.0(4.9-11.4)
Total input kW 2.93
EER 3.41
Energy label class A
SHF 0.77
Heating Capacity Btu/h 38,200
kW 11.2(4.5-14.0)
Total input kW 3.25
COP 3.45
Energy label class B
Booster heater kW -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 22-28
(Low-High) CFM 780-990
External pressure Pa 0
Sound level
(Low-High)
dB(A) 41-46
External finish Munsell 3.4Y 7.7/0.8
Dimension W : mm 1680
D : mm 235
H : mm 340
W : inch 66-1/8
D : inch 9-1/4
H : inch 13-3/8
Weight kg 28
lbs 62
Field drain pipe I.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49
Sound level at heating dB(A) 51
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135(YHA2)/130(YHA3)
lbs 298(YHA2)/287(YHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -20˚ C, W.B. -20˚ C
3. Guaranteed voltage
Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
2-4. CEILING SUSPENDED TYPE
Model name Indoor unit PCA-RP50GA PCA-RP60GA PCA-RP71GA
Outdoor unit PUHZ-RP50VHA2 PUHZ-RP60VHA2 PUHZ-RP71VHA2
PUHZ-RP50VHA3 PUHZ-RP60VHA3 PUHZ-RP71VHA3
Cooling Capacity Btu/h 16,000 20,500 24,200
kW 4.7(2.3-5.4) 6.0(2.7-6.7) 7.1(3.3-8.1)
Total input kW 1.67 1.63 2.14
EER 2.81 3.68 3.32
Energy label class C A A
SHF 0.76 0.86 0.74
Heating Capacity Btu/h 18,800 23,900 27,300
kW 5.5(2.5-6.6) 7.0(2.8-8.2) 7.6(3.5-10.2)
Total input kW 1.71 2.03 2.23
COP 3.22 3.45 3.41
Energy label class C B B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16 25
Indoor unit Air flow CMM 10-11-12-13 14-15-16-18
Outdoor unit Air flow CMM 35 55
Refrigerant pipe size Gas side O.D. mm 12.7 15.88
Refrigerant pipe length Height difference m Max. 30 Max. 30
(Low-Medium2-Medium1-High)
External pressure
Sound level
(Low-Medium2-Medium1-High)
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 1000 1310
Weight kg 27 34
Field drain pipe O.D. mm 26
Sound level at cooling
Sound level at heating dB(A) 46 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800 950
Weight kg 45
Liquid side O.D. mm 6.35 9.52
Length m Max. 50 Max. 50
CFM 355-390-425-460 495-530-565-635
Pa 0
dB(A) 37-38-40-42 37-39-41-43
D : mm 680
H : mm 210
W : inch 39-3/8 51-9/16
D : inch 26-3/4
H : inch 8-1/4
lbs 60 75
inch 1
CFM 1,240 1,940
dB(A) 44 47
D : mm
H : mm 600 943
W : inch 31-1/2 37-3/8
D : inch
H : inch 23-5/8 37-1/8
(VHA2)/42(VHA3) 75 (VHA2)/68(VHA3)
lbs 99(VHA2)/92(VHA3) 165(VHA2)/150(VHA3)
inch 1/2 5/8
inch 1/4 3/8
PCA-RP50GA2
PUHZ-RP50VHA2
PUHZ-RP50VHA3
5.0(2.3-5.6)
6.0(2.5-7.3)
14-15-16-18
495-530-565-635
37-39-41-43
330+23
13 + 7/8
17,000
1.66
3.01
B
0.88
20,500
1.76
3.41
B
-
1310
51-9/16
34
75
330+30
13 + 1-3/16
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PCA-RP100GA PCA-RP125GA PCA-RP140GA
Outdoor unit PUHZ-RP100VHA2
PUHZ-RP100VHA3
PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 2.92 3.88 4.65
EER 3.42 3.22 3.01
Energy label class A A B
SHF 0.75 0.77 0.75
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.26 4.11 4.60
COP 3.44 3.41 3.48
Energy label class B B B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32 40
Indoor unit Air flow CMM 20-21-23-25 27-30-32-34
(Low-Medium2-Medium1-High)
CFM 705-810-840-885 955-1060-1130-1200
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 40-41-43-45 41-43-45-46 42-44-46-48
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 1310 1620
D : mm 680
H : mm 270
W : inch 51-9/16 63-3/4
D : inch 26-3/4
H : inch 10-5/8
Weight kg 37 43 45
l b s 8 29 59 9
Field drain pipe O.D. mm 26
inch 1
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121(VHA2)/116(VHA3) 116
lbs 267(VHA2)/256(VHA3) 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5: w
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15:
D.B. -20:, W.B. -20:
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PCA-RP100GA PCA-RP125GA PCA-RP140GA
Outdoor unit PUHZ-RP100YHA2
PUHZ-RP100YHA3
PUHZ-RP125YHA2 PUHZ-RP140YHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 2.92 3.88 4.65
EER 3.42 3.22 3.01
Energy label class A A B
SHF 0.75 0.77 0.75
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.26 4.11 4.60
COP 3.44 3.41 3.48
Energy label class B B B
Booster heater kW - - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 20-21-23-25 27-30-32-34
(Low-Medium2-Medium1-High)
CFM 705-810-840-885 955-1060-1130-1200
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 40-41-43-45 41-43-45-46 42-44-46-48
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 1310 1620
D : mm 680
H : mm 270
W : inch 51-9/16 63-3/4
D : inch 26-3/4
H : inch 10-5/8
Weight kg 37 43 45
lbs 82 95 99
Field drain pipe O.D. mm 26
inch 1
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135(YHA2)/130(YHA3) 130
lbs 298(YHA2)/287(YHA3) 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -20˚ C, W.B. -20˚ C
3. Guaranteed voltage
Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
Model name Indoor unit PCA-RP71HA PCA-RP125HA PCA-RP125HA
Outdoor unit PUHZ-RP71VHA2
PUHZ-RP71VHA3
PUHZ-RP125VHA2 PUHZ-RP125YHA2
Cooling Capacity Btu/h 24,200 42,700 42,700
kW 7.1(3.3-8.1) 12.5(5.5-14.0) 12.5(5.5-14.0)
Total input kW 2.21 3.88 3.88
EER 3.21 3.22 3.22
Energy label class A A A
SHF 0.74 0.77 0.77
Heating Capacity Btu/h 27,300 47,800 47,800
kW 7.6(3.5-10.2) 13.8(5.0-16.0) 13.8(5.0-16.0)
Total input kW 2.23 4.05 4.05
COP 3.41 3.41 3.41
Energy label class B B B
Booster heater kW - - -
Power supply Phase [ 13
Cycle Hz 50 50
Voltage V 230 400
Breaker size A 25 16
Indoor unit Air flow CMM 17-19 30-38
(Low-High) CFM 600-670 1060-1350
External pressure Pa 0 0
Sound level
(Low-High)
dB(A) 34-38 44-50
External finish Stainless steel
Dimension W : mm 1136 1520
D : mm 650
H : mm 280
W : inch 44-3/4 59-7/8
D : inch 25-5/8
H : inch 11
Weight kg 41 56
lbs 90 124
Field drain pipe O.D. mm 26
inch 1
Outdoor unit Air flow CMM 55 100
CFM 1,940 3,530
Sound level at cooling dB(A) 47 50
Sound level at heating dB(A) 48 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950 950
D : mm 330+30 330+30
H : mm 943 1350
W : inch 37-3/8 37-3/8
D : inch 13 + 1-3/16 13 + 1-3/16
H : inch 37-1/8 53-1/8
Weight kg 75(VHA2)/68(VHA3) 116 130
lbs 165(VHA2)/150(VHA3) 256 287
Refrigerant pipe size Gas side O.D. mm 15.88 15.88
inch 5/8 5/8
Liquid side O.D. mm 9.52 9.52
inch 3/8 3/8
Refrigerant pipe length Height difference m Max. 30 Max. 30
Length m Max. 50 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w 1
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C w 2
3. Guaranteed voltage
198~264V, 50Hz (RP125Y : 342~457V, 50Hz)
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w1. If optional air protect guide installed. D.B.-15:
w2. F
r RP125 D.B. -20:, W.B. -20:
V: Single phase 230V 50Hz
, Y: 3 phase 400V 50H
Model name Indoor unit PSA-RP71GA
Outdoor unit PUHZ-RP71VHA2
Cooling Capacity Btu/h 24,200
kW 7.1(3.3-8.1)
Total input kW 2.20
EER 3.23
Energy label class A
SHF 0.73
Heating Capacity Btu/h 27,300
kW 7.6(3.5-10.2)
Total input kW 2.23
COP 3.41
Energy label class B
Booster heater kW -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 25
Indoor unit Air flow CMM 15-18
(Low-High) CFM 530-635
External pressure Pa 0
Sound level
(Low-High)
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 600
Weight kg 43
Field drain pipe I.D. mm 20
Outdoor unit Air flow CMM 55
Sound level at cooling dB(A) 47
Sound level at heating dB(A) 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
Weight kg 75(VHA2)/68(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
Liquid side O.D. mm 9.52
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -11˚ C, W.B. -12˚ C
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
dB(A) 40-45
D : mm 270
H : mm 1900
W : inch 23-5/8
D : inch 10-5/8
H : inch 74-13/16
lbs 98
inch 13/16
CFM 1,940
D : mm 330+30
H : mm 943
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8
lbs 165(VHA2)/150(VHA3)
inch 5/8
inch 3/8
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
PUHZ-RP71VHA3
Single phase 230V 50Hz
Model name Indoor unit PSA-RP100GA PSA-RP125GA PSA-RP140GA
Outdoor unit PUHZ-RP100VHA2
PUHZ-RP100VHA3
PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.4(5.5-14.0) 13.8(5.5-15.3)
Total input kW 2.99 4.12 4.91
EER 3.34 3.01 2.81
Energy label class A B C
SHF 0.81 0.75 0.74
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.28 4.11 4.97
COP 3.41 3.41 3.22
Energy label class B B C
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32 40
Indoor unit Air flow CMM 24-31 26-33 27-35
(Low-High) CFM 850-1060 920-1165 955-1240
External pressure Pa 0
Sound level
(Low-High)
dB(A) 44-49 46-51 47-52
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 600
D : mm 350
H : mm 1900
W : inch 23-5/8
D : inch 13-3/4
H : inch 74-13/16
Weight kg 51 53
lbs 112 117
Field drain pipe I.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121(VHA2)/116(VHA3) 116
lbs 267(VHA2)/256(VHA3) 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5: w
D.B. 28˚ C
D.B. 17˚ C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15:
D.B. -20:, W.B. -20:
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PSA-RP100GA PSA-RP125GA PSA-RP140GA
Outdoor unit PUHZ-RP100YHA2
PUHZ-RP125YHA2 PUHZ-RP140YHA2
PUHZ-RP100YHA3
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.4(5.5-14.0) 13.8(5.5-15.3)
Total input kW 2.99 4.12 4.91
EER 3.34 3.01 2.81
Energy label class A B C
SHF 0.81 0.75 0.74
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.28 4.11 4.97
COP 3.41 3.41 3.22
Energy label class B B C
Booster heater kW - - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 24-31 26-33 27-35
(Low-High) CFM 850-1060 920-1165 955-1240
External pressure Pa 0
Sound level
(Low-High)
dB(A) 44-49 46-51 47-52
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 600
D : mm 350
H : mm 1900
W : inch 23-5/8
D : inch 13-3/4
H : inch 74-13/16
Weight kg 51 51 53
lbs 112 112 117
Field drain pipe I.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135(YHA2)/130(YHA3) 130
lbs 298(YHA2)/287(YHA3) 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚ F) W.B. 19: (66˚ F) Outdoor : D.B. 35: (95˚ F) W.B. 24: (75˚ F)
Heating Indoor : D.B. 20: (68˚ F) Outdoor : D.B. 7: (45˚ F) W.B. 6: (43˚ F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 35˚ C, W.B. 22.5˚ C
D.B. 19˚ C, W.B. 15˚ C D.B. -5˚ C w
D.B. 28˚ C
D.B. 17˚ C
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 46˚ C
D.B. 21˚ C, W.B. 15˚ C
D.B. -20˚ C, W.B. -20˚ C
3. Guaranteed voltage
Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
30
3
OUTLINES AND DIMENSIONS
377 284 60
()
Ceiling hole
Branch duct hole
Drain pipe
connected to VP-25
Ceiling
Grille
Drain hole
Models
Auto vane
(Air outlet)
Air intake grille
Ceiling
Cut out hole
Cut out hole
Cut out hole
Burring hole pitch
Burring hole pitch
Burring hole
Burring hole
Power supply wire,
Indoor unit/Outdoor unit
connecting wire entry
Indoor unit/Outdoor
connecting terminal
Indoor power supply
terminal block(Option part)
Control wire entry
Air intake hole
Air intake hole
Air outlet hole
Air outlet hole
Connected the attached
flexible pipe or socket.
Keep approximately
10 to 15mm space
between unit ceiling
and ceiling slab.
Branch duct hole
Fresh air
intake hole
Ceiling hole
Suspension bolt pitch
Suspension bolt pitch
Remote controller
terminal block
Suspension bolt
M10 or W3/8
(7.5) (7.5)
605
+35
- 5
620
DEFROST/STAND BY lamp
Receiver
Operation lamp
In case of standard grille : PLP-6BA / PLP-6BAMD
In case of wireless remote controller : PLP-6BALM
Auto grille
Air intake grille up/down discharge
Emergency operation
switch<Cooling>and
Emergency Up/Down switch<Up>
160
160
500
500
597
83 36
950
83 36
950
597
A
17
+5
0
B 35
190
156
105
140
50~70
160
840
150
90
C
D
840
187.5
20~45
860~910
20~45
810
20~45
860~910
20~45
24
160
ww
w
w
w
w
w
w
w
M
M
M
M
120
°
120
°
[175
[125
167
158
Vane motor
2
1
Drain pump clean hole
and Drain emergency
drainage hole
130
100
70°
155
350
90 100 100 90
B A CDE
241 258
80
87
74
400
298
85 77
440
281
2
1
Refrigerant pipe
··· [6.35
Flared connection
··· 1/4 inch
Refrigerant pipe
··· [9.52
Flared connection
··· 3/8 inch
Refrigerant pipe
··· [12.7
Flared connection
··· 1/2 inch
Refrigerant pipe
··· [15.88
Flared connection
··· 5/8 inch
Refrigerant pipe
[ 6.35 / [ 9.52
Flared connection
1/4 inch/3/8 inch
(compatible)
PLA-RP35/50BA
PLA-RP60BA
PLA-RP71BA
PLA-RP71BA2
PLA-RP100,125,140BA
PLA-RP100,125BA2
Detail drawing of fresh air intake hole
Detail connecting of branch duct(Both aspects)
3-[ 2.8
14-[ 2.8
[150
[100
Emergency
switch<Heating>and
Emergency Up/Down switch<Down>
In case of auto-grille : PLP-6BAJ
Suspension bolt
lower edge
170
w
Ceiling
Air intake grille
Max. 4.0m
L.L Filter
Ceiling
Grille
Indoor unit
1500mm
or more
1000mm
or more
3000mm or more
1800mm or more
from floor
For high
attachment
Indoor unit
Obstacle
Floor
Note 1. Please choose the grille from a standard grille, auto-grille.
2. As for drain pipe, please use VP-25(O.D. [ 32 PVC TUBE).
Drain pump is included.
Max. lifting height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8.
(Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions w marked on the figure.
3) The optional high efficiency filter becomes optional multi-functional casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/water dew.)
8. As for necessary installation/service space, please refer to the left figure.
INDOOR UNIT
PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA
PLA-RP100BA PLA-RP125BA PLA-RP140BA
PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2
Unit : mm
Unit : mm
PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA
PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
90
100 100 90
_
70
{ 175
3 - { 2.8
Burring hole
158
350
Detail drawing of fresh air intake
120
_
Branch duct hole
(Cut out hole)
{150
{125
Burring hole pitch
120_
{ 100
(Cut out hole)
Ceiling surface
100
14 - { 2.8
Burring hole
130
167
155
Suspension bolt lower edge
Fresh air intake
159 192
Branch duct hole
840
89
98
Suspension bolt M10
or W3/8
1
2
170
140
C
50 - 70
Power line entry
Ceiling hole
860 - 910
810
Suspension bolt pitch
159
Terminal block
197 159
840
Feeding hole
(Drain pump)
Control wire entry
374 286 60
20 - 45 20 - 45
16
Drain pipe
VP-25connection
(O.D.{ 32)
105
Ceiling surface
605
860 - 910 20 - 45 20 - 45
Ceiling hole
Suspension bolt pitch
159
A
B
190
0
+5
30
17
Branch
duct hole
135
0
+5
High efficiency filter
& Fresh air intake casement (option)
A
(WIRELESS PANEL)
Emergency operation switch (cooling)
Emergency operation switch (heating)
Receiver
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
1 LIQUID SIDE
DEFROST/STAND BY lamp
Operation lamp
RP35, 50
RP60 RP71
[ 6.35 [ 6.35 ——
17
RP100, 125, 140
[ 9.52 [ 9.52 [ 9.52 [ 9.52
2 GAS SIDE
[12.7 ———
[15.88 [15.88 [15.88 [15.88
——— [19.05
: Initial flare nut size
Air intake grille
A
950
411
Air outlet hole
51 77
PLA-RP35,50AA
PLA-RP60,71AA
PLA-RP100,125,140AA2
Models
577
Air intake hole
M
M
411
Air outlet hole
950
A
B
C
241
258
80
281
298
84
Grille
Drain hole
M
M
77 51
Auto vane
577
Air intake hole
Vane motor
32
PEAD-RP35EA2
PEAD-RP50EA
PEAD-RP60EA
PEAD-RP71EA
PEAD-RP100EA2
PEAD-RP125EA
PEAD-RP140EA
2
1
3
4
5
6
7
Refrigerant piping flare connection (liquid [ F copper tube):HP
Refrigerant piping flare connection (gas [ G copper tube):LP
Drain R1(External thread)
Electrical parts box
Drain Pump (Option)
Drain Pipe (Option) ... Flexible joint VP-25(I.D.
[
32)
Filter
R407C Outdoor unit : 9.52
F
R410A Outdoor unit : 6.35 w
R407C Outdoor unit : 9.52 w
Outdoor unit (SUZ) : 6.35
E D C B A
804 830
-
305 772
Model
RP60
R407C Outdoor unit : 15.88
G
R410A Outdoor unit : 12.7 w
15.88
1044 1070 290 280 1012
RP35,50
w Initial flare nut size
2
1
3
4
Air inlet
Air outlet
Access door
55
50~150
81
197
Service space:500 or more
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
5
6
75
44
18
365~465
B 81
10
56 355
7
159
243
Air outlet
Air inlet
7
Lifting bolt hole
(14× 22)
10- [3 (RP35,50)
12-
[
3 (RP60)
In case of rear inlet
In case of bottom inlet
10- [3 (RP35,50)
12-
[
3 (RP60)
D
30
C
10
81 B C
A
450
450
10- [3 (RP35,50)
12-
[
3 (RP60)
176
40
288
256
3.5
3.5
10
109
179
10
35
24
30 640
30
21
277
80
45
282
13
13 E
A
61 227
29
85
40
176
10
15
3.5
256
B C 81
10
81
A
Set
R407C outdoor unit : 19.05 1584 1610 470 460 1552 RP140
15.88 1044 1070 290
F
R410A Outdoor unit : 15.88 w
E D C B A
1284 1310 370 360
280 1012
1252
Model
RP100,125
RP71
w Initial flare nut size
7
44
243
308
323
75
6
5
13
Refrigerant piping flare connection (liquid [ 9.52 copper tube):HP
Refrigerant piping flare connection (gas [ F copper tube):LP
Drain R1 (External thread)
Electrical parts box
Drain Pump (Option)
Drain Pipe (Option) ... Flexible joint VP25(I.D.[ 32)
Filter
Service space:500 or more
81
365~465
197
81
50~150
55
29
Access door
Air outlet
Air inlet
4
3
1
2
7
6
5
4
3
2
1
113
307
122
12-[3
(14x22)
Lifting bolt hole
45
Set
210
12-[3
450
450
140
282
680
3.5
3.5
30
319
261
181
40
30
A
C B
81
10
375
10
80
C B 81
A
E 13
30 D
20
35
30
10 53 169
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
33
PEAD-RP60GA
PEAD-RP71GA
PEAD-RP100GA
Unit : mm
Model A B C D E
7
7
9
8
9.52
9.52
15.88
15.88
8
10
FG H J
RP60
RP71
RP100
1125
1125
1365
1090
1090
1330
1050
1050
1290
1012
1012
1252
840
840
1080
Outdoor unit(SUZ) : 6.35
Other outdoor unit : 9.52 w
R410A Outdoor unit : 15.88 w
R407C Outdoor unit : 19.05
w Initial flare nut size
Return air
sensor
A
Rubber bush <Remote
controller wiring>
Rubber bush
<Outdoor unit
connection wiring>
Rubber bush
<Power supply wiring>
A
4- [12
Drain R1
Top view
Control box
Return air
duct flange
Supply air
duct flange
<For hanging bolt M10>
[Field supply]
22- [3.1
24- [3 Holes
Refrigerant pipe
[ 9.52 (3/8 braze)
Refrigerant pipe
[ 25.4 (1 braze)
<Accessory>
Pipe cover···················2pcs.
(For dew condensation prevention of local piping and unit connection)
Remote controller········1pc.
Return air
Left side view
Supply air
Front view
75
55
129 70
42
124 34
131
530
50
95 250 11
7x130(=910)
10
130
130
45
45
31 31
1102
200
10
8x130(=1040)
1300
20
199
100
40
20
462
144
1284
400
155 1000 105
40 1260 40
1340
1400
565 39
22 330
145
89
35
130
130
35
634
262 73
10
54
10
376
25 100 100 25
Rubber bush <Remote
controller wiring>
Rubber bush
<Outdoor unit
connection wiring>
Rubber bush
<Power supply
wiring>
A
A
4- [ 12
Drain R1
Top view
Control box
22- [ 3.1
<For hanging bolt M10>
[Field supply]
Return air
duct flange
Supply air
duct flange
26- [ 3 Holes
Left side view
Supply air
Return air
Front view
Return air
sensor
<Accessory>
Pipe cover··················2pcs.
(For dew condensation prevention of local piping and unit connection)
Remote controller·······1pc.
Refrigerant pipe
[ 12.7 (1/2 braze)
Refrigerant pipe
[ 25.4 (1 braze)
42
144 145
755570 129
124
131
50 530
34
130
95 250 11
10
66
1302
1484
7x130(=910)
130
45
45
200
20
100
20
199
40
1500
462
66 9X130(=1170)
10
25 100 100 25
10 10
1540
40 1460 40
255 205
376
1000
1600
73 262
400
39 565
54
634
35
130
89
330 22
130
35
36
PEA-RP400, 500GA
Unit : mm
45
Refrigerant pipe
PEA-RP400GA :
[
9.52 (3/8 braze)
PEA-RP500GA :
[
12.7 (1/2 braze)
[2 places (*2 part)]
*2*1*2
*1
Refrigerant pipe [ 25.4 (1 braze)
[2 places (*1 part)]
Return air sensor
(2 places)
Drain R1
24- [3.1
36- [3 HOLES
Left side view
Front view
Top view
Return air
Supply air
4- [15
<For hanging bolt M12>
[Field supply]
Return air duct flange
Control box
Supply air duct flange
A
Rubber bush
<Remote controller wiring>
Rubber bush
<Power supply wiring>
Rubber bush
<Outdoor unit connection wiring>
A
<Accessory>
Pipe cover··················4pcs.
(For dew condensation prevention of local piping and unit connection)
Remote controller·······1pc.
81
117 156 117
10
20 1840
10
40
60
60
61
60
40 40
1800
1880
50 664
525
22
102
22.5
120
4X120(=480)
22.5
595
1824
50
764
280 1125 395
340 188 22
1947
570
40 130 130 40
10
33
29
130
12X130(=1560)
29
149 1618
100
42.5
130
8X130(=1040) 42.5
10
203 320 141
20
425 59
700
39
37
PKA-RP35GAL PKA-RP50GAL
BYOFF
ONSTAND
HEATCOOL
OFF BY
ON STAND
COOL HEAT
ÅrÇoÇoÅqÅ@ ëOñ Å@ÇeÇqÇnÇmÇs ÅrÇoÇoÅqÅ@ ëOñ Å@ÇeÇqÇnÇmÇs
r.SLI
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
r.S
L
I
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
Knockout hole for right piping
Refrigerant pipe.Drain pipe.
Wiring hole
21
Right side
Less than 15
70
245
60
235
Auto vane
Front view
Air intake
Air intake
Air intake
Air intake
198
53
340
715 225
340 80 280 233
990
21
Left side
Knock out hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole.
60
70
245
(Necessary clearance for
unit installation)
Right side
Allowing clearances
Front view
Less than 130
50 or more 150 or more
180 or more 30 or more
for bolts
Left-rear
piping hole
left-rear piping
R52.5
R52.5
Installation plate
balance point hole
Details of installation plate
49-[ 5hole
for tapping screw
Knockout hole for
right-rear piping
Right-rear
piping hole
Unit center
14-[ 14hole
Knockout hole for
425
420
170
190
210
230
0
322
0355580130
190
230
272
310
0
35
95
150
205
260
320
345
495
20
75
135
190
245
300
360
405
495
32
0
w1 Sleeves are available on the market.
w2 This size shows the lower end of through hole.
[ 90~[ 100[90
Through hole
Sleeve w 1
35, 50
Model
R52.5
R52.5
Gas pipe
Liquid pipe
Terminal block for
Terminal block to
outdoor unit
Filter grip
Service panel
(Power supply access)
(Flexible hose total length800)
(Right side piping
installation)
(Left side piping
installation)
Unit drain pipe O.D.20
Front view(to open the grille)
700
449
86
581 54
31 280
35
Knockout hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
12-Louvers(manual)
Air outlet
Lower side
80
50
395 400
190
60
70 35
79
160 40
235
705
power supply (Heater (PKH-P35, 50GALH only))
153
GAS SIDE
LIQUID SIDE
RP35, 50
P35, 50
[6.35
[9.52
[12.7
[15.88
—
[ 9.52—[ 15.88
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
: initial flaare nut size
38
Unit : mm
PKA-RP50FAL2
PKA-RP60FAL
PKA-RP71FAL
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Left side
1400
1090
Air intake
235
C
Knockout hole for right piping
Refrigerant pipe. Drain pipe
Knockout hole for
left piping
Drain hose for
left-hand side piping
Drain hose
Lower side
Auto vanes
(Gas pipe)
Drain hose O.D.20
Bolt
Gas pipe
15
(Liquid pipe)
Liquid pipe [ 9.52(3/8F)
Gas pipe [ 15.88(5/8F)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
29 80
280
30 30
184 30
60
10
39
37
65
100
AB C
Knockout hole for wiring
25
1110
183
240
B
1120
552
55
120
107
111
Air outlet
552
Air outlet
Louvers (manual)
Under panel
Removable at left-hand
side piping
Knockout hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
12-ø6 hole for
tapping screw
66-ø6 hole for
tapping screw
Wall fixture
Unit center
32-ø12 hole for bolt
225
18
18
91
900
990
455
285
245
19
240 280 314
610
90
Drainage range
on left-hand side
Drainage range
on right-hand side
10 91=(910)
180
Terminal block for heater (PKH only)
Terminal block for indoor/outdoor connecting line
Display section
Receiving
section
Power lamp
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
6GAS SIDE
5LIQUID SIDE
RP50
[
6.35
[
9.52
[
15.88
[
12.7
:Initial flare nut size
Available pipe size
[
9.52
[
15.88
[ 90
RP60,71 / P60,71
w
1 Sleeves are available on the market.
Use the current nuts meeting
the pipe size of the outdoor unit.
Sleeve w 1
Through hole
[ 90~ [ 100
39
Unit : mm
PKA-RP100FAL
235
45
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Display section
Receiving
section
Power lamp
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
Left side
1680
1370
Air intake
235
C
Knockout hole for right piping
Knockout hole for left piping
Drain hose for left-hand side piping
Drain hose
Drain hose
Lower side
Auto vane
(Gas pipe)
Bolt
Gas pipe
15
(Liquid pipe)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
29 80
280
30 30
184 30
60
10
39
37
65
100
AB C
Knockout hole for wiring
25
1110
183
240
B
1400
55
120
102
111
694
Air outlet
694
Air outlet
Louvers (manual)
Under panel
(Removable at left-hand side piping)
Knockout hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening Range for left rear piping opening
12-ø6 hole for tapping screw
84-ø6 hole for
tapping screw
Wall fixture
Unit out line
Unit center
41-ø12 hole
for bolt
295 225
18
18
91
900
1270
595
285
245
19
240 280 314
750
90
Drainage range
on right-hand side
13 91=(1183)
180
Drainage range
on left-hand side
Terminal block for heater (PKH only)
Terminal block for indoor/outdoor connecting line
Drain hose O.D.20
: Initial flare nut size
GAS SIDE
LIQUID SIDE
RP100
[9.52
[15.88
[19.05
P100
[9.52
[19.05
Use the current nuts meeting the pipe size
of the outdoor unit.
Available pipe size
40
PCA-RP50GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
180
210
157
15
85
182 liquid
201 gas
241 (Drainage)
Air intake
918
161 90
254
680
506 56
Electrical box
226
70
6
2
7
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
525
928
352
263
171
138
86
46 175 1
131
38
38
79
161
32
179
42
6~7
Ceiling
Electrical box
[Front view]
When electrical
box is pulled
down
3
2
8
5
1
4
[15.88
[9.52
P50
[15.88
[12.7
[6.35
Available pipe size
[ 9.52
4 GAS SIDE
5 LIQUID SIDE
RP50
Use the current nuts meeting the pipe size of the outdoor unit.
: Initial flare nut size
1 Drainage pipe connection (26mm I.D.)
2 Drainage pipe connection (for the left arrangement)
3 Knockout hole for left drain-piping arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection)
5 Refrigerant-pipe connection (liquid pipe side/flared connection)
6 Knockout hole for upper drain pipe arrangement
7 Knockout hole for left drain pipe arrangement
8 Knockout hole for wiring arrangement
Unit : mm
41
PCA-RP50GA2
PCA-RP60GA
PCA-RP71GA
161 90
254
680
506 56
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
1290
1214
210
180
81 76
1310
Air outlet
1228
Air intake
85
182
201
241
15
157
(Liquid)
(5/8 inch Gas)
(Drainage)
7
2
Electrical box
70
226
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ Front view ]
Ceiling
32
179
161
38
3879
42
6~7
525
1235
416
263
171
138
86
131
175 1
46
: Initial flare nut size
4 GAS SIDE
5 LIQUID SIDE
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP71,P60,P71
RP60
[6.35
[9.52
[15.88
RP50
[6.35
[9.52
[12.7
[15.88
[9.52
[15.88
1 Drainage pipe connection (26mm I.D.)
2 Drainage pipe connection (for the left arrangement)
3 Knockout hole for left drain-piping arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection)
5 Refrigerant-pipe connection (liquid pipe side/flared connection)
6 Knockout hole for upper drain pipe arrangement
7 Knockout hole for left drain pipe arrangement
8 Knockout hole for wiring arrangement
Unit : mm
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
161 90
254
680
506 56
1228
Air intake
1214
270
207
81 96
1310
Air outlet
1240 (suspension bolt pitch)
140
150
320 80
18
70
6
87
182
198
245
16
217
(3/8 inch Liquid)
(5/8 inch,
3/4 inch gas)
(Drainage)
7
2
Electrical box
70
229
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ Front view ]
Ceiling
93
160
38
38 140
42 239
6~7
525
1235
687
263
171
138
86
192
236
1
45
Use the current nuts meeting the pipe size of the outdoor unit.
:Initial flare nut size
4 GAS SIDE
5
LIQUID SIDE
Available pipe size
RP100
[9.52
[15.88
[19.05
P100
[9.52
[19.05
1 Drainage pipe connection (26mm I.D.)
2 Drainage pipe connection (for the left arrangement)
3 Knockout hole for left drain-piping arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection)
5 Refrigerant-pipe connection (liquid pipe side/flared connection)
6 Knockout hole for upper drain pipe arrangement
7 Knockout hole for left drain pipe arrangement
8 Knockout hole for wiring arrangement
Unit : mm
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
43
PCA-RP125GA
PCA-RP140GA
161 90
254
680
506 56
1535
Air intake
1524
270
207
81 96
1620
Air outlet
1547(suspension bolt pitch)
140
150
320 80
18
70
6
87
182
198
245
16
217
(3/8 inch Liquid)
(5/8 inch,
3/4 inch gas)
(Drainage)
7
2
Electrical box
70
229
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ Front view ]
Ceiling
93
160
38
38 140
42 239
6~7
525
1545
687
263
171
138
86
192
236
1
45
:Initial flare nut size
RP125,140
[19.05
[15.88
[9.52
Use the current nuts meeting the pipe size of the outdoor unit.
4 GAS SIDE
5 LIQUID SIDE
Available pipe size
P125,140
[19.05
[9.52
1 Drainage pipe connection (26mm I.D.)
2 Drainage pipe connection (for the left arrangement)
3 Knockout hole for left drain-piping arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection)
5 Refrigerant-pipe connection (liquid pipe side/flared connection)
6 Knockout hole for upper drain pipe arrangement
7 Knockout hole for left drain pipe arrangement
8 Knockout hole for wiring arrangement
Unit : mm
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
(Gap to ceiling)
90˚
130
9
[222
[200
Terminal block box
7 8
(122)
480
Allowing clearances
6
4
85
140 18
45
210
2
165
120
1
90
366
38
318
176
105
650
Less than
Rear wall
Adjustable part
2 ~ 3
300
Ceiling
Less than
Less than
250
100 1136
or more
500
or more
295
254
70~90
43
320 80
495
<Suspension bolt pitch>
243
75
6Knockout hole for wiring arrangement : 2- [ 27
7Terminal block(indoor/outdoor connecting line)
5Knockout hole for upper refrigerant-pipe arrangement
3Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
1Refrigerant-pipe connection(gas pipe side/flared connection : 5/8 inch)
4Knockout hole for behind refrigerant-piping arrangement
2Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8 inch)
<gas>
197
<liquid>
175
110
21
130 15
5
2
· Optional parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.)
8Terminal block(remote controller)
9Knockout hole (duct for fresh air intake): 2- [ 200
75
Suspension bolt
1
280
13
70
289
<Air outlet>
75
3
650
<Flexible hose(accessory)>
Inspection port
(pipe sensor)
<Air outlet>
1224
<Suspension bolt pitch>
1180
986
1136
handle
16
288
<Filter contour dimension>
<Air intake>
Filter (3-pieces)
258 110 102
or more
100
360
Filter element for the exchange
model:PAC-SG38KF-E (12pcs.)
1098
<Air intake>
Terminal block box
Electrical box
The half bottom of FAN CASING
can be separated.
1.Use M10 or W3/8 screw for anchor bolt.
NOTES.
250
Less than
or more
500
(Gap to ceiling)
90˚
[222
[200
2~3
9
130
440 440 298
7 8
Allowing clearances
Terminal block box
(122) 246
6
165
295
254
243
280
90 120
<Air outlet>
110 102
38 210
176
105
3
13
70
289
650
Rear wall
Adjustable part
handle
<Flexible hose(accessory)>
16
<Filter contour dimension>
Inspection port
(pipe sensor)
Filter (4-pieces)
4
2
85 45
140 18
1
70~90
43
320 80 1564
495
<Suspension bolt pitch>
75
1Refrigerant-pipe connection(gas pipe side/flared connection : 5/8 inch, 3/4 inch)
3Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
2Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8 inch)
4Knockout hole for behind refrigerant-piping arrangement
5Knockout hole for upper refrigerant-pipe arrangement
6Knockout hole for wiring arrangement : 2- [ 27
<gas>
197
175
<liquid>
110
21
· Optional parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.)
9Knockout hole (duct for fresh air intake) : 2- [ 200
7Terminal block(indoor/outdoor connecting line)
8Terminal block(remote controller)
1
75
Suspension bolt
650
Less than
288
258
300
Less than
100 1520 100
or more
Ceiling
or more
: Initial flare nut size
360
[ 9.52
<Air intake>
Filter element for the exchange
RP125
model:PAC-SG38KF-E (12pcs.)
[ 15.88
[ 19.05
130 15
5
2
Terminal block box
Electrical box
<Suspension bolt pitch>
1608
<Air outlet>
1370 75
1520
The half bottom of
FAN CASING
can be separated.
1482
<Air intake>
2 LIQUID SIDE
Available pipe size
1.Use M10 or W3/8 screw for anchor bolt.
NOTES.
1 GAS SIDE
Use the current nuts meeting the pipe size
of the outdoor unit.
300 or more
1
5 or more
2
Front 1,000 or more
Knockout hole
for under-piping
Front side
218
VIEW "A"
95
100
90
175
55 143
Rear side
20
160
Knockout hole
for bottom fixing
277
100 or more 100 or more
40 66
Liquid pipe [ 9.52(3/8 inch)
95
Electrical parts box
461 22
Terminal block for
indoor/outdoor
connection.
1. Service access allows for
insertion of screw driver.
2. Adjustable
186
Drain pipe
Gas pipe [ 15.88(5/8 inch)
47
767
714 123
590
480
110
105
Knockout hole for piping and wiring
(140 80 oval)
20
A
132
Knockout hole
for branch duct
240
Rear side
10
38 38
15
111
Knockout hole for
under-piping(120 70 oval)
130
100
125
340
370
Front side
10
270
250
40
50 260
Metal fixture
against overturning
520
260
240
20 10
130 130
controller
766
130 71
Terminal block for
heater power supply
(Only PSH-P·GAH)
1900
50
608
827 30
216
115
Knockout hole for
wiring [ 27
(Provided on both sides)
180
235
70
Knockout hole for refrigerant and drainage
90 60 oval (Provided on both sides)
530
600
PSA-RP100GA
PSA-RP125GA
PSA-RP140GA
Unit : mm
[ 9.52
P100,125,140—[ 19.05
300 or more
1
5 or more
2
Front 1,000 or more
100 or more 100 or more
1. Service access allows for
insertion of screw driver.
2. Adjustable
261
Knockout hole
for under-piping
Front side
218
VIEW "A"
95
Knockout hole for
under-piping(120 70 oval)
[ 9.52
RP100,125,140
[ 15.88
[ 19.05
Use the current nuts meeting the pipe size
of the outdoor unit.
201
120
140
255
350
LIQUID SIDE
Available pipe size
77
Rear side
20
120
277
Knockout hole
for bottom fixing
330
: Initial flare nut size
GAS SIDE
Terminal block for
indoor/outdoor
40 66
Liquid pipe [ 9.52(3/8 inch)
95
Electrical parts box
461 22
connection.
Terminal block for
heater power supply
(Only PSH-P·GAH)
[ 19.05(3/4 inch)
Gas pipe [ 15.88(5/8 inch)
Drain pipe
47
767
714 123
590
480
110
105
Knockout hole for piping and wiring
(140 80 oval)
20
115
50
70
260
315
Knockout hole for
A
wiring [ 27 (Provided on both sides)
132
130
111
100
125
Front side
10
340
370
Metal fixture
520
against overturning
260
Knockout hole
for branch duct
240
Rear side
10
38 38
15
40
50 260
240
20 10
130 130
controller
1900
766
130 71
608
827 30
216
Knockout hole for refrigerant and drainage
90 60 oval (Provided on both sides)
530
600
OUTDOOR UNIT
PUHZ-RP35VHA2 PUHZ-RP35VHA3
PUHZ-RP50VHA2 PUHZ-RP50VHA3
Unit : mm
400
347.5
43.6
152
Air intake
[ 33 drain hole
45.4
4-10 o 21 oval hole
(M10 foundation bolt)
18
Handle for
moving
Air intake
Air discharge
[ 33 drain hole
155
330
365
300
40
23
32.5
Service panel
Service panel
for charge plug
Connection for
liquid pipe
600
300
10
150
287.5
Installation bolt pitch: 500
800
Free space around the outdoor unit
(basic example)
100 mm or more as long as
no obstacle is placed on the
rear and light-and-left sides
of the unit.
100 mm or more
w 1
500 mm or more
w 2
2 sides should be open in
the right, left and rear side.
w 1
100 mm or more
Basically open
350 mm or more
155
90
69
Service port
1. FOUNDATION BOLTS
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts, washer and nut must
be purchased locally.)
<Foundation bolt height>
FOUNDATION
18 or below
w The position and the size of conduit hole
depend on the conduit to be used.
w Conduit hole
35
Connection for
gas pipe
183
2. PIPING-WIRING DIRECTION
Piping and wiring connection can
be made from the rear direction only.
3. ATTACHING THE CONDUIT
In order to attach the conduit, it is
necessary to fix the metal plate with
2 screws to the back panel. Procure
the metal plate and make screw holes
locally. It is recommended to use the
metal plate shown below. Align the
metal plate to the marks on the unit
and attach it.
40
20
43
Minimum installation space for outdoor unit
w 1. In the place where short cycle tends to occur, cooling and heating
capacity and power consumption might get lowered by 10%. Air outlet
guide (optional PAC-SG58SG) will help them improve.
w 2. If air discharges to the wall, the surface might get stained.
80
60
Holes for metal plate fixing screw
w The size of hole depends on the screw to be used.
Unit : mm
PUHZ-RP60VHA2 PUHZ-RP60VHA3
PUHZ-RP71VHA2 PUHZ-RP71VHA3
417
(19) 370 28
2-U Shaped notched holes
(Foundfation Bolt M10)
175 600 175
Rear Air Intake
Installation Feet
330
56
53
45
65 42
2-12o 36 oval holes
(Foundation Bolt M10)
Air Discharge
30
Side Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
Left···Power supply wiring
Reight···Indoor/Outdoor wiring
Terminal Connections
Service panel
Handle for moving
950
Earth terminal
322
Handle for moving
Side Air Intake
Handle for moving
673
2
1
473
943
Handle for moving
w1 447
w1 443
Rear piping cover
Front piping cover
71
71
23
Bottom piping hole
(Knockout)
81 219
Drain hole
(5-{ 33)
145
145 220 30 145
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
3 FOUNDATION BOLTS 2 SERVICE SPACE
<Foundation bolt height>
purchased locally.)
Over100
Dimensions of space needed
for service access are
shown in the below diagram.
Over 100mm
FREE
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
1 FREE SPACE (Around the unit)
Over 10mm
FOUNDATION
30
Less than
500
Over
500
Over
Over10
Service space
Over 10mm
Over 500mm
Rear Air Intake
···Refrigerant GAS pipe connction (FLARE) { 15.88(5/8 inch)
···Refrigerant LIQUID pipe connection (FLARE) { 9.52(3/8 inch)
Example of Notes
1
2
w 1 ···Indication of STOP VALVE connection location
Handle for moving
Air Intake
Power supply wiring hole
(2-{ 27Knockout)
Rear trunking hole
(Knockout)
40 45
Right trunking hole
(Knockout)
Power supply wiring hole
(2-{ 27Knockout)
40 75
Right piping hole
(Knockout)
45
40
Power supply wiring hole
(2-{ 27Knockout)
Piping Knockout Hole Details
Front trunking hole
(Knockout)
92
{
92
{
732363
92
{
Rear piping hole
(Knockout)
92
65
27 55
23 73 63
92
19 55
73 63
23 2792
27 55
65
92
Front piping hole
(Knockout)
PUHZ-RP100VHA2
PUHZ-RP100VHA3
PUHZ-RP125VHA2
PUHZ-RP140VHA2
PUHZ-RP100YHA2
PUHZ-RP100YHA3
PUHZ-RP125YHA2
PUHZ-RP140YHA2
Unit : mm
2-U Shaped notched holes
(Foundation Bolt M10)
(19) 28 370
417
A
930
1,079
A
53 56
45
42
66
2-12 x 36 Oval holes
(Foundation Bolt M10)
Terminal connection
Left···Power supply wiring
Right···Indoor/Outdoor wiring
Service panel
Handle for moving
2
1
w1 447
w1 443
Front piping cover
Rear piping cover
71
71
Bottom piping hole
(Knockout)
RP·V
Drain hole
(5-{ 33)
RP·Y
600 175 175
Rear Air Intake
Installation Feet
330
Side Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
Please secure the unit firmly
with 4 foundation (M10) bolts.
3 FOUNDATION BOLTS 2 SERVICE SPACE
Dimensions of space needed
for service access are
<Foundation bolt height>
(Bolts and washers must be
purchased locally.)
150
Over
shown in the diagram below.
Over 150mm
FREE
30
FOUNDATION
30
Less than
500
Over
500
Over
10
Over
Service space
Over 10mm
Air Discharge
950
Earth terminal
322
Handle for moving
Side Air Intake
Rear Air Intake
1350
Handle for moving
Handle for moving
Handle for moving
371 635
Air intake
23
27Knockout)
{
Power supply wiring hole
(2-
Rear trunking hole
(Knockout)
45 40
Right trunking hole
(Knockout)
27Knockout)
{
Power supply wiring hole
(2-
75 40
Right piping hole
(Knockout)
45 40
27Knockout)
{
Power supply wiring hole
(2-
81 219
92
{
92
{
92
{
145 145 220 30 145
Rear piping hole
(Knockout)
92
65
27 55
23 73 63
92
19 55
73 63
23 27 92
23 73 63
27 55
65
92
The diagram below shows a basic
example.
Explantion of particular details is
given in the installation manuals etc.
1 FREE SPACE (Around the unit)
Over 10mm
Over 1000mm
Example of Notes
1···Refrigerant GAS pipe connction (FLARE){ 15.88(5/8 inch)
2···Refrigerant LIQUID pipe connection (FLARE){ 9.52(3/8 inch)
w 1···Indication of STOP VALVE connection location.
Piping Knockout Hole Details
Front trunking hole
(Knockout)
Front piping hole
(Knockout)
PUHZ-RP200YHA2
PUHZ-RP250YHA2
Unit : mm
175 600 175
417
370 28 19
)
999
995
53
40560
60 37
70
Terminal Connections
Left···Power supply wiring
Right···Indoor/Outdoor wiring
(
Handle for moving
Service Panel
1
2
Brazing
*1 439
*1 A
*2 339
Front piping cover
Rear piping cover
71
71
Bottom piping hole
(Knockout)
Drain hole
(5-[ 33)
2-U Shaped notched holes
(foundation Bolt M10)
Installation Feet
Rear Air Intake
Side Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
3 FOUNDATION BOLTS 2 SERVICE SPACE
purchased locally.)
150
Over
Dimensions of space needed
for service access are
shown in the below diagram.
FREE
2-12o 36 oval holes
(Foundation Bolt M10)
FOUNDATION
30
Less than
500
Over
Over
10
Over
Service space
Over 10mm
Air Discharge
500
330 30
<Foundation bolt height>
Over 150mm
Earth terminal
950
322
Handle for moving
Side Air Intake
Side Air Intake
Rear Air Intake
Handle for moving
Handle for moving
1350
Handle for moving
A
447
2
[ 9.52
(3/8 inch)
421
[ 12.7
(1/2 inch)
371 635
Air Intake
23
Power supply wiring hole
(2-[ 27Knockout)
Rear trunking hole
(Knockout)
40 45
55 27
Right trunking hole
(Knockout)
40 75
Power supply wiring hole
(2-[ 27Knockout)
63 73
Right piping hole
(Knockout)
55 27
40 45
Power supply wiring hole
(2-[ 27Knockout)
81 219
Rear piping hole
92
[ 92
63 73 23
[ 92
92 27 23
63 73 23
[ 92
145 145 145 220 30
(Knockout)
65
55 19
92
65
92
The diagram below shows a basic
example.
Explantion of particular details is
given in the installation manuals etc.
1 FREE SPACE (Around the unit)
Over 10mm
Over 1000mm
· · · ·Refrigerant GAS pipe connction (FLARE)[ 19.05(3/4 inch)
Example of Notes
1
· · · ·Refrigerant LIQUID pipe connection (FLARE)
*1· · · ·Indication of STOP VALVE connection location.
*2· · · ·Refrigerant GAS PIPE connention(BRAZING) O.D[ 25.4
2
PUHZ-RP250YHA2
PUHZ-RP200YHA2
Piping Knockout Hole Details
Front trunking hole
(Knockout)
Front piping hole
(Knockout)
52
WIRED REMOTE CONTROLLER
Unit : mm
53
WIRELESS REMOTE CONTROLLER
Unit : mm
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
<Table 2>SW2(CAPACITY CODE)
Manufacture/Service
PLA-RP35BA
MODELS
SW2
ON
OFF
12345
Manufacture/Service
PLA-RP100BA
MODELS
ON
OFF
12345
PLA-RP50BA
ON
OFF
12345
PLA-RP125BA
ON
OFF
12345
PLA-RP60BA
ON
OFF
12345
PLA-RP140BA
ON
OFF
12345
PLA-RP71BA
ON
OFF
12345
11 4 1 6 9
113
1 3
4
51
41
1234567891011121314151617
18
19
20
CN2L
ON OFF
SWE
J42 J41
SW2 SW1
LED3 LED2 LED1
LED2
LED1
RU
SW2
SW1
CNB
3
9
5 5 5 5
4 5
3
t° t° t°
FS
TH2 TH5 TH1
MV
BZ
MV MV MV
MMMM
W.B
TB6
R.B
I.B
MT
M
14
21
21
21
1
2
1
2
Refer to tables 1 and 2.
TRANSMISSION
WIRES
DC12V
TB4
YLW
ORN
ORN
BRN
YLW
YLW
ORN
DCL
TO OUTDOOR
UNIT
135
31
DC325V
X1
M
1~
DP
D.U.M
CNP
(BLU)
ZNR02
ZNR01
FUSE
DSA
OUTDOOR
CN01
(BLK)
RECTIFICATION
U
U
S1
S2
S3
741
3~
MF
MS
CN3G
U.B
AUTOMATIC FILTER ELEVATION PANEL
(OPTIONAL PART)
CN3A
31
AUTO GRILLE
POWER
CNAC
(WHT)
1
3
REMOCON
CN22
(BLU)
I-SEE SENSOR
CN4Y
(WHT)
I-SEE
SENSOR MOTOR
CN6Y
(RED)
WIRELESS
CN90
(WHT)
AUTO GRILLE
CN3G
(BLK)
I-SEE SENSOR
CORNER PANEL
(OPTIONAL PART)
I-SEE
SENSOR
GRILLE
VANE
CNV(
WHT)
Pair No.
FAN
CNMF
(WHT)
INTAKE
CN20
(RED)
FLOAT SW
CN4F
(WHT)
LIQUID/PIPE
CN44
(WHT)
TB5
CN32
(WHT)
CN51(WHT)
CN41(WHT)
<Table 1>SW1(MODEL SELECTION)
Manufacture/Service
SW1
ON
OFF
12345
w Be sure to turn off the power source
and then disconnect fan motor connector.
(Failure to do so will cause trouble in Fan motor.)
131 35
SYMBOL SYMBOL NAME NAME
I.B
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
SURGE ABSORBER
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
POWER SUPPLY (I.B)
POWER SUPPLY (R.B)
TRANSMISSION (INDOOR-OUTDOOR)
RELAY (DRAIN PUMP)
SWITCH (MODEL SELECTION) w See table 1
SWITCH (CAPACITY CORD) w See table 2
CONNECTOR (EMERGENCY OPERATION)
FAN MOTOR
VANE MOTOR
DRAIN-UP MACHINE
DRAIN FLOAT SWITCH
TERMINAL BLOCK (Indoor unit Power (option))
TERMINAL BLOCK (
INDOOR/OUTDOOR CONNECTING LINE
)
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
REACTOR
ROOM TEMP. THERMISTOR
(0: / 15k", 25: / 5. 4k" DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0: / 15k", 25: / 5. 4k" DETECT)
COND. / EVA. TEMP. THERMISTOR
(0: / 15k", 25: / 5. 4k" DETECT)
MF
FUSE
MV
ZNR01,02
DSA
DP
CN2L
FS
CN32
TB2
CN41
CN51
TB4
DCL
LED1
TB5,TB6
LED2
TH1
LED3
X1
TH2
SW1
TH5
SW2
SWE
[LEGEND]
TO OUTDOOR UNIT
1
3
5
31
CN01
(BLK)
ORN
YLW
BLU
RED
GRN/YLW
I.B
w 1(Fig. 1)
I.B
TB2
POWER SUPPLY
~(1PHASE)
230V 50Hz
ORN
ORN
YLW
BRN
TB4
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
L
N
S1
S2
S3
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
W.B
RU
BZ
LED1
LED2
SW1
SW2
OPTIONAL PART
PCB FOR WIRELESS REMOTE CONTROLLER
RECEIVING UNIT
BUZZER
LED (OPERATION INDICATION : GREEN)
LED (PREPARATION FOR HEATING : ORANGE)
EMERGENCY OPERATION (HEAT / DOWN)
EMERGENCY OPERATION (COOL / UP)
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to Fig 1.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
4-1. INDOOR UNIT
PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA
PLA-RP100BA PLA-RP125BA PLA-RP140BA
PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2
[LEGEND]
SYMBOL SYMBOL NAME NAME
I.B
DCL
DP
FS
INDOOR CONTROLLER BOARD
CN2L
CONNECTOR (LOSSNAY)
CN32
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CN41
CN51
CONNECTOR (CENTRALLY CONTROL)
DSA
SURGE ABSORBER
FUSE
FUSE (T6.3AL250V)
LED1
POWER SUPPLY (I.B)
LED2
POWER SUPPLY (R.B)
LED3
TRANSMISSION (INDOOR-OUTDOOR)
SW1
SWITCH (MODEL SELECTION) w See table 1
SW2
SWITCH (CAPACITY CODE) w See table 2
SWE
CONNECTOR (EMERGENCY OPERATION)
X1
RELAY (DRAIN PUMP)
ZNR01,02
VARISTOR
REACTOR
DRAIN-UP MACHINE
DRAIN FLOAT SWITCH
<Table 2>SW2(CAPACITY CODE)
SW2
Manufacture/Service MODELS
3
GRILLE
5 5 5 5
MV MV MV MV
VANE
1
12345
12345
12345
CNV(
1011121314151617181920
WIRELESS
CNB
SW1
SW2
PLA-RP71BA2
PLA-RP100BA2
PLA-RP125BA2
I.B
13
AUTO GRILLE
CN3G
(BLK)
M M M M
WHT)
CN90
(WHT)
9
ON
OFF
ON
OFF
ON
OFF
BZ
RU
123456789
LED3 LED2 LED1
I-SEE
SENSOR
CN4Y
(WHT)
9
14
4
I-SEE
SENSOR
LED2
I-SEE SENSOR
CORNER PANEL
(OPTION PART)
LED1
W.B
OPTION PART
Refer to tables 1 and 2.
SENSOR MOTOR
16
5
M
MT
FAN MOTOR
MF
VANE MOTOR
MV
TB2
TERMINAL BLOCK (Indoor unit Power (option))
TB4
TERMINAL BLOCK (
TERMINAL BLOCK (REMOTE CONTROLLER
TB5,TB6
TRANSMISSION LINE)
TH1
ROOM TEMP. THERMISTOR
(0: / 15kΩ , 25: / 5. 4kΩ DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0: / 15kΩ , 25: / 5. 4kΩ DETECT)
TH5
COND. / EVA. TEMP. THERMISTOR
(0: / 15kΩ , 25: / 5. 4kΩ DETECT)
PCB FOR WIRELESS REMOTE CONTROLLER
W.B
BZ
BUZZER
LED1
LED (OPERATION INDICATION : GREEN)
LED2
LED (PREPARATION FOR HEATING : ORANGE)
RECEIVING UNIT
RU
SW1
EMERGENCY OPERATION (HEAT / DOWN)
SW2
EMERGENCY OPERATION (COOL / UP)
CN2L
U.B
21
J42 J41
Pair No.
3
TRANSMISSION
WIRES
DC12V
CN32
(WHT)
CN51(
51
CN41(
41
SWE
ON
AUTO GRILLE
POWER
CNAC
(WHT)
1314 14
SW2 SW1
21
TB6
R.B
I-SEE
CN6Y
(RED)
1 33 1 5
CN3G
AUTOMATIC FILTER ELEVATION PANEL
(OPTION PART)
Notes:
1.SymboIs used in wiring diagram above are,
:Connector, : : Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make sure to
match the terminal numbers (S1, S2, S3) for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check
the outdoor unit electric wiring for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting
wires.(specification of 230V), adopting superimposed system of
power and signal.
w 1:When work to supply power separately to indoor and outdoor
units was applied, refer to Fig 1.
w 2:For power supply system of this unit, refer to the caution label
located near this diagram.
INDOOR/OUTDOOR CONNECTING LINE
<Table 1>SW1(MODEL SELECTION)
SW1
Manufacture/Service
2
1
INDOOR/OUTDOOR
COMMUNICATION
CN22
(BLU)
LIQUID/PIPE
CN44
(WHT)
t° t° t°
TH5 TH2 FS TH1
12345
13
CN3C
(BLU)
RECTIFICATION
INTAKE
CN20
(RED)
12 7 4 1
I.B
1123
WHT)
WHT)
OFF
FLOAT SW
CN4F
(WHT)
CN3A
TB5
REMOCON
)
DCL
ON
OFF
YLW
OUTDOOR
CN01
15 3
(BLK)
DC325V
FAN
CNMF
(WHT)
MS
DSA
ZNR02
3~
MF
U
1~
DP
M
U
ZNR01
X1
D.U.M
1 3
CNP
(BLU)
FUSE
YLW
ORN
ORN
BRN
YLW
ORN
TB4
S1
S2
S3
TO OUTDOOR
UNIT
w Be sure to turn off the power source
and then disconnect fan motor connector.
(Failure to do so will cause trouble in fan motor)
w 1(Fig. 1
)
CN01
(BLK)
5
3
1
1
3
CN3C(BLU)
I.B
YLW
ORN
INDOOR/OUTDOOR
COMMUNICATION
RED
BLU
GRN/YLW
YLW
ORN
ORN
BRN
TB2
TB4
S1
S2
S3
L
N
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR UNIT
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
56
PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA
32 1
32 1
53 1
MF
FAN
(WHT)
RED
WHT
BLK
BLK
X1
X4
X1 X4
C
BCR
31
DP
D.U.M
CNP
(BLU)
YLW
YLW
ORN
ORN
YLW
31 31 31 31
YLW
YLW
D.HEATER
CNC(RED)
RED
WHT
WHT
BRN
POWER
CNDK
(RED)
POWER
CND
(ORN)
21
POWER
CN2D
(WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
31 31
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
CN41 CN51 CN2L
CN32
9
WIRELESS
CN90
(WHT)
BZ
5
VANE
CN6V
(GRN)
CN2S
(WHT)
CNSK
(RED)
W.B
LED2
CNB
LED1
SW1 SW2
RU
21
2
2 1
1
REMOCON
CN22
(BLU)
TB5
TRANSMISSION WIRES
DC12V
TB6
R.B
BLU
BLU
32 1 2 1 2 1
D.SENSOR
CN31
(WHT)
INTAKE
CN20
(RED)
HEATER
CN24
(YLW)
LIQUID
CN21
(WHT)
DS
TH2
21
PIPE
CN29
(BLK)
TH3
TH1
LED3 LED2 LED1
ON
OFF
SWE
Refer to tables 1
and 2.
SW2 SW1
9 5
10
76 321 84
5MV5MV5
5
MV5MV
GRILLE
H2
S1
S2
TB2
TB4
POWER SUPPLY
~(1PHASE)
230V 50Hz
RED
BLU
YLW
ORN
ORN
BRN
GRN/YLW
S3
TB4
TO OUTDOOR UNIT
TO OUTDOOR UNIT
L
S1
S2
S3
N
DC
13.1V
1
2
2
3
1
P.B
ZNR
FUSE
I.B
I.B
YLW
ORN
BRN
ORN
YLW
ORN
W 1 (Fig.1)
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
1 2 3 4 5
ON
OFF
MODELS
Table 1
SW1
Manufacture/Service
PLA-RP. AA
1 2 3 4 5
ON
OFF
MODELS
Table 2
SW2
Manufacture/Service
PLA-RP35AA
PLH-P35AAH
PLA-RP50AA
PLH-P50AAH
PLA-RP60AA
PLH-P60AAH
PLA-RP71AA
PLH-P71AAH
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
PLH-P. AAH
TB2
I.B
HEATER CN24
(YLW)
[PLH-P.AAH models only]
POWER SUPPLY
~(1PHASE)
230V 50Hz
88H
FS1
26H
FS2
H1
L
RED RED RED
BLU
GRN/YLW
WHT
WHT
WHT GRY
N
2
1
2
6
5
1
88H
YLW
YLW
INDOOR POWER BOARD
[LEGEND]
P.B
INDOOR CONTROLLER BOARD I.B
FUSE(T6.3AL250V) FUSE
CN2L
VARISTOR ZNR
CONNECTOR(LOSSNAY)
CN32
FAN CONTROL ELEMENT BCR
CONNECTOR(REMOTE SWITCH)
CN41 CONNECTOR(HA TERMINAL-A)
CN51 CONNECTOR(CENTRALLY CONTROL)
SW1
SWITCH(MODEL SELECTION)w See table 1
SWITCH(
CAPACITY CORD
)w See table 2
SW2
SWE
CONNECTOR(EMERGENCY OPERATION)
X1 RELAY(DRAIN PUMP)
X4 RELAY(FAN MOTOR)
LED1 POWER SUPPLY(I.B)
LED2 POWER SUPPLY(I.B)
LED3 TRANSMISSION(INDOOR-OUTDOOR)
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C CAPACITOR(FAN MOTOR)
MF FAN MOTOR
MV VANE MOTOR
DP DRAIN-UP MACHINE
DS DRAIN SENSOR
H2 DEW PREVENTION HEATER
TB4 TERMINAL BLOCK (INDOOR/
OUTDOOR CONNECTING LINE)
TB2
TERMINAL BLOCK (HEATER)w PLH-P.AAH
models only or option for PLA-RP.AA models.
TB5, TB6 TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
TH1 ROOM TEMP.THERMISTOR
(0:/15k", 25:/5.4k" DETECT)
TH2 PIPE TEMP.THERMISTOR/LIQUID
(0:/15k", 25:/5.4k" DETECT)
TH5 COND./EVA. TEMP. THERMISTOR
(0:/15k", 25:/5.4k" DETECT)
R.B
WIRED REMOTE CONTROLLER BOARD
W.B
HEATER
WIRELESS REMOTE CONTROLLER BOARD
RU RECEIVING UNIT
FS1 THERMAL FUSE(72:, 16A)
FS2 THERMAL FUSE(104:, 16A)
H1 HEATER
26H HEATER THERMAL SWITCH
88H HEATER CONTACTOR
BZ BUZZER
LED1 LED(RUN INDICATOR)
LED2 LED(HOT ADJUST)
SW1 SWITCH(HEATING ON/OFF)
SW2 SWITCH(COOLING ON/OFF)
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification
of 230V), adopting superimposed system of power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to Fig 1.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
57
PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
S1
S2
S3
TB4
TO
OUTDOOR
UNIT
YLW
ORN
YLW YLW
ORN
BRN
ORN
1
1 1
3
1
2
2
5
1
2
3
1
3
5
5 3
RECTIFIER
TRANS
IPM
P.B
MF
1
2
3
9 5
10
7 6 32 1 84
5MV5MV5
5
MV5MV
GRILLE
H2
GRILLE
BLK
X1
J41
J42
X1
3 1 2 1 3
DP
D.U.M
CNP
(BLU)
YLW
YLW
ORN
ORN
YLW
BLK
WHT
PNK
3 1 331 3 1
YLW
YLW
D.HEATER
CNC
(RED)
CN33
(GRN)
CN02
(GRN)
CN01
(BLK)
POSITION DETECTION
SENSOR INPUT
CN3
(WHT)
CN03
(BLU)
CN2S
(WHT)
FAN
CN2
(GRN)
CN4
(WHT)
FUSE
ZNR
DCL
FAN
WHT
BRN
POWER
CND
(ORN)
2 1
POWER
CN2D
(WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
CN41 CN51 CN2L
CN32
9
WIRELESS
CN90
(WHT)
BZ
5
5
VANE
CN6V
(GRN)
W.B
I.B
LED2
CNB
LED1
SW1 SW2
RU
2 1
2
2 1
1
REMOCON
CN22
(BLU)
TB5
TRANSMISSION WIRES
DC12V
TB6
R.B
BLU
BLU
2 1 2 1 21
D.SENSOR
CN31
(WHT)
INTAKE
CN20
(RED)
LIQUID
CN21
(WHT)
DS
TH2
2 1
PIPE
CN29
(BLK)
TH5
TH1
LED3
Pair No.
LED2 LED1
ON
OFF
SWE
Refer to tables 1
and 2.
w Be sure to turn off the power source
and then disconnect fan motor connector.
(Failure to do so will cause trouble in fan motor.)
SW2 SW1
BLK
WHT
RED
3 1
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
TB4
YLW
ORN
ORN
BRN
TO OUTDOOR UNIT
S1
S2
S3
I.B
P.B
TB2
POWER SUPPLY
~(1PHASE)
230V 50Hz
RED
BLU
GRN/YLW
L
N
3
1
5
CN01
(BLK)
YLW
ORN
w 1 (Fig.1)
1 2 3 4 5
ON
OFF
(Table 1) SW1 (MODEL SELECTION)
SW1
Manufacture/Service
(Table 2) SW2 (CAPACITY CORD)
1 2 3 4 5
ON
OFF
MODELS
SW2
Manufacture/Service
PLA-RP100AA2 PLA-RP140AA2
PLA-RP125AA2
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
MODELS
Manufacture/Service
INDOOR POWER BOARD
[ LEGEND]
P.B
INDOOR CONTROLLER BOARD I.B
CN2L CONNECTOR(LOSSNAY)
CN32
CONNECTOR(REMOTE SWITCH)
CN41 CONNECTOR(HA TERMINAL-A)
CN51 CONNECTOR(CENTRALLY CONTROL)
SW1
SWITCH(MODEL SELECTION)w See table 1
SWITCH(
CAPACITY CORD
)w See table 2
SW2
SWE
CONNECTOR(EMERGENCY OPERATION)
X1 RELAY(DRAIN PUMP)
LED1 POWER SUPPLY(I.B)
LED2 POWER SUPPLY(I.B)
LED3 TRANSMISSION(INDOOR-OUTDOOR)
FUSE
FUSE(T5AL250V)
ZNR VARISTOR
IPM POWER MODULE
SYMBOL NAME SYMBOL NAME SYMBOL NAME
MF FAN MOTOR
MV VANE MOTOR
DP DRAIN-UP MACHINE
DS DRAIN SENSOR
DCL REACTOR
H2 DEW PREVENTION HEATER
TB2
TERMINAL BLOCK (Indoor unit Power (option))
TB4 TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TB5, TB6 TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
TH1 ROOM TEMP.THERMISTOR
(0:/15k", 25:/5.4k" DETECT)
TH2 PIPE TEMP.THERMISTOR/LIQUID
(0:/15k", 25:/5.4k" DETECT)
TH5 COND./EVA. TEMP. THERMISTOR
(0:/15k", 25:/5.4k" DETECT)
R.B
WIRED REMOTE CONTROLLER BOARD
W.B
WIRELESS REMOTE CONTROLLER BOARD
RU RECEIVING UNIT
BZ BUZZER
LED1 LED(RUN INDICATOR)
LED2 LED(HOT ADJUST)
SW1 SWITCH(HEATING ON/OFF)
SW2 SWITCH(COOLING ON/OFF)
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification
of 230V), adopting superimposed system of power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to Fig 1.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
58
PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA
PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
<w A>
N
L
S1
S2
12
21
12
S3
TO CND
TO OUTDOOR
UNIT
TO CN3C
ON
OFF
12345
ON
OFF
12345
ON
OFF
12345
ON
OFF
12345
ON
OFF
12345
ON
OFF
12345
ON
OFF
12345
54321
OFF
ON
50EA
60EA
71EA
35EA(2)
100EA(2)
125EA
140EA
Capacity cord
switch
Model selection
switch
SW2
SW1
MODELS
POWER SUPPLY
~(1PHASE)
230V 50Hz
(IN CASE OF CONNECTING
THE REPLACEMENT WIRING)
TO OUTDOOR UNIT
TO MA-REMOTE
CONTROLLER
DC8.7-13V
I.B.
X6
X4
X5
X1
ZNR
FUSE
P.B.
CN31
1
3
DS
INSIDE SECTION OF CONTROL BOX
B
L
U
B
L
U
B
L
U
B
L
U
TB5
(RED)
6 435 21
C
MF
X6 X5 X4
X1
(RED)
CNDK
(BLU)
CNP
(WHT)
FAN
1
Y
L
W
O
R
N
(ORN)
31
CND
2
1
(RED)
LED1
LED2
LED3
CN2L
OFF
ON
SWE
SW2
SW1
(RED)
(WHT)
P
N
K
P
N
K
B
L
K
B
L
K
W
H
T
B
L
K
B
L
K
W
H
T
W
H
T
W
H
T
1
2
31
CN2S
CNSK
(WHT)
(RED)
YLW
ORN
BRN
B
R
N
O
R
N
(BLU)
WHT
BLK
CN2D
(WHT)
(BLU)
(RED)
(WHT)
(BLK)
(WHT)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
w A
DP
6 435 21
2
1
TB4
S3
S1
S2
2
1 3 31
6 435 21
MF
C
12
CN24
321
12
3
1
2
1
212
TH5 TH2 TH1
1
2
CN3C
31
13 75
CN22
CN20 CN21 CN29
CN31
CN90
CN41
CN51
CN32
2
1
123456789 4 3214 5 321
<PEAD-RP71·100·125·140EA, 100EA2>
External static pressure 130Pa
<PEAD-RP71·100·125·140EA, 100EA2>
External static pressure 70Pa
<PEAD-RP35·50·60EA, 35EA2>
External static pressure 70Pa
Optional parts
Optional parts
<PEAD-RP35·50·60EA, 35EA2>
External static pressure 30Pa
(OPTIONAL PARTS)
DRAIN PUMP
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS) DP
DS
TRANSMISSION(INDOOR·OUTDOOR)
LED3
SWITCH(MODEL SELECTION)
SW1
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1
POWER SUPPLY(I.B.)
CN90
CN51
CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
COND./EVA. TEMP. THERMISTOR
(0: /15t , 25:/5.4t DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0: /15t , 25:/5.4t DETECT)
INTAKE AIR TEMP. THERMISTOR
(0: /15t , 25:/5.4t DETECT)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
DRAIN SENSOR
DRAIN PUMP
TH5
TH2
TH1
TB5
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK TB4
MF
C
NAME NAME
SYMBOL SYMBOL
NAME
[LEGEND]
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
CN41
CN32
CN2L
I.B.
SYMBOL
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification
of 230V), adopting superimposed system of power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to wA.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
59
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
Capacity cord
switch
Model selection
switch
SW2 SW1
ON
OFF
12345
ON
OFF
12345
ON
OFF
12345
54321
OFF
ON
100GA
71GA
60GA
MODELS
<w A>
N
L
S1
S2
12
21
12
S3
TO CND
TO OUTDOOR
UNIT
TO CN3C
POWER SUPPLY
~(1PHASE)
230V 50Hz
(IN CASE OF CONNECT
THE REPLACEMENT WIRING)
TO MA-REMOTE
CONTROLLER
DC8.7-13V
TO OUTDOOR UNIT
X6
X5
X4
X1 ZNR
FUSE
P.B.
I.B.
X1
Y
L
W
O
R
N
X6 X5 X4
2
1
(RED)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
(WHT)
B
L
U
B
L
U
B
L
U
B
L
U
(BLK)
(WHT)
(RED)
(BLU)
B
L
K
W
H
T
BLK
WHT
(WHT)
(BLU)
B
R
N
BRN
O
R
N
ORN
YLW
(BLU) (RED) (ORN)
(RED)
(WHT)
B
L
K
W
H
T
B
L
K
W
H
T
(WHT)
(WHT)
O
R
G
B
L
K
B
L
U
B
L
K
Y
L
W
Y
L
W
G
R
Y
w A
*
(Initial setting)
240V 230V 220V
20Pa
60Pa
75Pa
10Pa
50Pa
70Pa 50Pa
35Pa
5Pa
RED
WHT
BLU
CONNECTOR COLOR
2
1
TB5
TB4
S3
S1
S2
2 1
CNP
1 3 31
31
13
CNSK
2
1
CN2S
6 435 21
MF
C
1
2
CN24
3
21
12
3
1
2
121
2
TH5 TH2
TH1
LED1
LED2
LED3
1
2
CN2D
CN3C
31
CND CNDK
13 7
FAN
5
OFF
ON
SWE
SW2
SW1
CN2L
CN22
CN20 CN21 CN29
CN31
CN90
CN41
CN51
CN32
2
1
123456789
4
321
54321
INSIDE SECTION OF CONTROL BOX
*External static pressure
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS)
TRANSMISSION(INDOOR·OUTDOOR)
LED3
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1
POWER SUPPLY(I.B.)
CN90
CN51
CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
COND./EVA. TEMP. THERMISTOR
(0: /15t , 25:/5.4t DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0: /15t , 25:/5.4t DETECT)
INTAKE AIR TEMP.THERMISTOR
(0: /15t , 25:/5.4t DETECT)
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
TH5
TH2
TH1
TB4
TB5
MF
C
NAME NAME
SYMBOL SYMBOL
NAME
[LEGEND]
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CORD)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
SWITCH(MODEL SELECTION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
SW1
CN41
CN32
CN2L
I.B.
SYMBOL
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to wA.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
OUTDOOR UNIT
CIRCUIT BREAKER
(FIELD SUPPLY)
PEA-RP200,250GA:15A
DSR
DSA
(3P)
(Hi)
C02
(6P)
(Lo)
C01
C01
5
4
TH5
TH2
TH1
INDOOR UNIT
POWER SUPPLY
3N~PE
380/400/415V
50Hz
BLACK
WHITE
RED
N
BLACK
WHITE
RED
TB2
L3
L2
L1
PE
52F
Hi
Lo
321
52F
123
MF1
TB6
LCD
REMOTE CONTROLLER
FB
TB4
S3S2S1
X6 X5 X4
3 75 1
FAN
ZNR
FUSE
4 123
SW2
OFF
ON
5
TAB1
3
1
CNSK
2
1
CN2S
DC
13.1V
CN2D
CN90
CN22
CN2L
CNDK
CND
CN32
CN31
CN51
12345
31
31
31 12
DC13.1V
LED1
LED2
LED3
21212
1
213
365
4
987
312
CN3C
CN20
CN21
CN41
CN29
123
4
121
2
2
1
1
2
TB5
Hi
52F
Lo
52F
X1
X1
X1
49F
51F
X6 X5 X4
12345
SW1
OFF
ON
SWE
OFF
ON
SWITCH (MODEL SELECTION)
SWITCH (CAPACITY CODE)
CONNECTOR (EMERGENCY OPERATION)
SNB
BOARD 1
ZNR5~7 VARISTOR
DSA,DSR ARRESTER
INDOOR UNIT
NAME SYMBOL
COND./EVA. TEMP.
LIQUID PIPE TEMP.
ROOM TEMP.
52FHi MAGNETIC CONTACTOR (INDOOR FAN MOTOR<HIGH SPEED>)
SURGE KILLER CR1,2
SW1
TH5
LED (TRANSMISSION<INDOOR·OUTDOOR>) LED3
LED (POWER SUPPLY<REMOTE CONTROLLER>) LED2
LED (POWER SUPPLY) LED1
SWE
SW2
X4-6 AUXILIARY RELAY
VARISTOR ZNR
FUSE (T6.3AL250V) FUSE
THERMISTOR
TERMINAL BLOCK
INTERNAL THERMOSTAT (INDOOR FAN MOTOR)
OVER CURRENT RELAY (INDOOR FAN MOTOR)
FAN MOTOR (INDOOR)
TH2
TH1
TB2,4,5
49F
51F
MF1
52FLo MAGNETIC CONTACTOR (INDOOR FAN MOTOR<LOW SPEED>)
AUXILIARY RELAY X1
FERRITE CORE FB
BOARD
CONTROLLER
INDOOR
CN2L
CN31
CN90
CN51
CN41
CN32
CONNECTOR (DRAIN SENSOR)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CONNECTOR (LOSSNAY)
4. Indoor and outdoor connecting wires have polarities, make sure
to match wiring and terminal.
5. Emergency operation
If a trouble occurs with either the remote controller or the indoor microcom-
puter and no other trouble exists, emergency operation for cooling or heating
can be performed by changing the setting of connector (SWE) "ON" on the
indoor controller board.
SWE :ON / Indoor fan is running at high speed.
TERMINAL BLOCK TB6
SYMBOL
REMOTE CONTROLLER
NAME
SNB BOARD 1
REMOTE
CONTROLLER
BOARD
POWER BOARD
INDOOR
INDOOR
CONTROLLER
BOARD
Note:1. The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
51F
Caution,
1. To protect fan motor from abnormal current, overcurrent relays are installed.
Therefore, do not change factory set value of overcurrent relays.
6. mark is connector. mark is terminal.
CR1 CR2
ZNR5~7
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
GREEN/YELLOW
INDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
TAB1
TAB1
FAN
CNDK
31
1 5 73
X4 X5 X6
CN20
CN21
CN41
CN29
123
4
121
2
2
1
CN2D
CN90
CN22
CN2L
CND
CN32
CN31
CN51
12345
FUSE
ZNR
31
31 12
DC13.1V
LED1
LED2
LED3
21212
1
213
365
4
987
312
CN3C
3
1
CNSK
2
1
CN2S
DC
13.1V
3
1
CNSK
2
1
CN2S
DC
13.1V
CN2D
CN90
CN22
CN2L
FAN
CNDK
CND
CN32
CN31
CN51
12345
FUSE
ZNR
31
31
31 12
DC13.1V
1 5 73
X4 X5 X6
LED1
LED2
LED3
21212
1
213
365
4
987
312
CN3C
CN20
CN21
CN41
CN29
123
4
121
2
2
1
FB11
S1
1
2
REMOTE CONTROLLER
S2
S3
TB5
TB6
LCD
X1
FB21
S1S2S3
X2
TH1-1
TH2-1
TH5-1
TH5-2
TH2-2
TH1-2
TB4-2
TB4-1
FB12
FB22
X4 X5 X6
X4 X5 X6
51F
BLUE
POWER SUPPLY
3N~PE
380/400/415V
50Hz
CIRCUIT BREAKER
(FIELD SUPPLY)
PEA-RP400,500GA:15A
BLACK
WHITE
RED
DSR
DSA
N
BLACK
WHITE
RED
TB2
L3L2L1
PE
52F
C01 C02
123
MF1
123
52F
C01
5
4
X01
X02
49F
SWE
OFF
ON
345
SW1
OFF
ON5ON
OFF
34
12
21
SWE
OFF
ON
345
SW1
OFF
ON5ON
OFF
SW2
34
12
21
SW2
AUXILIARY RELAY X4-6
MF1
51F
49F
TB2,4-1,4-2,5
TH1-1,1-2
TH2-1,2-2
FAN MOTOR (INDOOR)
OVER CURRENT RELAY (INDOOR FAN MOTOR)
INTERNAL THERMOSTAT (INDOOR FAN MOTOR)
TERMINAL BLOCK
THERMISTOR
INDOOR UNIT
FUSE FUSE (T6.3AL250V)
ZNR VARISTOR
TH5-1,5-2
CR SURGE KILLER
MAGNETIC CONTACTOR (INDOOR FAN MOTOR) 52F
ROOM TEMP.
LIQUID PIPE TEMP.
COND./EVA. TEMP.
FERRITE CORE FB11,FB12
FB21,FB22
INDOOR
CONTROLLER
BOARD
X1,2 AUXILIARY RELAY
NAME SYMBOL
SNB
BOARD 1
ZNR5~7 VARISTOR
DSA,DSR ARRESTER
SW2
SWE
LED1 LED (POWER SUPPLY)
LED2 LED (POWER SUPPLY<REMOTE CONTROLLER>)
LED3 LED (TRANSMISSION<INDOOR·OUTDOOR>)
SWITCH (MODEL SELECTION) SW1
SWITCH (CAPACITY CORD)
CONNECTOR (EMERGENCY OPERATION)
OUTDOOR UNIT
TERMINAL BLOCK
NAME SYMBOL
TB3,TB8
CN2L
CN31
CN90
CN51
CN41
CN32
CONNECTOR (DRAIN SENSOR)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CONNECTOR (LOSSNAY)
REMOTE CONTROLLER
TERMINAL BLOCK
NAME SYMBOL
TB6
4. Indoor and outdoor connecting wires have polarities, make sure to
match wiring and terminal.
5. Emergency operation
If a trouble occurs with either the remote controller or the indoor microcom-
puter and no other trouble exists, emergency operation for cooling or heating
can be performed by changing the setting of connector (SWE) "ON" on the
indoor controller board.
SWE :ON / Indoor fan is running at high speed.
(No.2)
INDOOR
CONTROLLER
BOARD
(No.1)
REMOTE
CONTROLLER
BOARD
INDOOR
POWER
BOARD
(No.1)
(No.2)
INDOOR
CONTROLLER
BOARD
(No.2)
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
SNB BOARD 1
(No.1)
INDOOR
POWER BOARD
Note:1. The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
51F
6. mark is connector. mark is terminal.
Caution,
1.To protect fan motor from abnormal current, overcurrent relays are installed.
Therefore, do not change factory set value of overcurrent relays.
CR
ZNR5~7
62
PKA-RP35GAL PKA-RP50GAL
P.B
INDOOR POWER BOARD
SYMBOL NAME
[LEGEND]
I.B
INDOOR CONTROLLER BOARD
FUSE FUSE (T6.3AL250V)
ZNR VARISTOR
CN2L CONNECTOR <LOSSNAY>
CN32 CONNECTOR <REMOTE SWITCH>
CN41 CONNECTOR <HA TERMINAL-A>
CN51 CONNECTOR <CENTRALLY CONTROL>
SW1 SWITCH <MODEL SELECTION>w See Table 1.
SW2 SWITCH <CAPACITY CODE>w See Table 2.
SWE SWITCH <EMERGENCY OPERATION>
X4 RELAY <FAN MOTOR>
BCR
POWER SUPPLY <R.B>
LED1 POWER SUPPLY <I.B>
LED2
TRANSMISSION <INDOOR-OUTDOOR> LED3
FAN CONTROL ELEMENT
C CAPACITOR <FAN MOTOR>
FAN MOTOR
VANE MOTOR
MF
MV
SYMBOL NAME
TB4
TERMINAL BLOCK <INDOOR/ OUTDOOR
TB2
TERMINAL BLOCK (HEATER) w PKH-P.GALH
models only or option for PKA-RP.GAL models.
CONNECTING LINE>
TERMINAL BLOCK <REMOTE CONTROLLER
TRANSMISSION LINE> <OPTION>
ROOM TEMP.THERMISTOR
<0:/ 15k", 25:/ 5.4k" DETECT>
PIPE TEMP.THERMISTOR/ LIQUID
<0:/ 15k", 25:/ 5.4k" DETECT>
COND./ EVA.TEMP.THERMISTOR
<0:/ 15k", 25:/ 5.4k" DETECT>
TB5,TB6
TH5
TH1
TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED <RUN INDICATOR>
LED <HOT ADJUST>
SWITCH (HEATING ON/ OFF>
SWITCH (COOLING ON/ OFF>
WIRED REMOTE CONTROLLER BOARD
R.B
HEATER
RU
BZ
LED1
LED2
SW1
SW2
NAME SYMBOL
HEATER
H1
THERMAL FUSE <84:10A>
FS2
THERMAL FUSE <104:10A>
FS1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
INTAKE
CN20
(
RED
)
LIQUID
CN21
(
WHT
)
PIPE
CN29
(
BLK
)
1 2
1 2
1 2
1 3 1 3 1 3 1 2
TH5 TH1
TH2
REMOCON
CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
2
1
TRANSMISSION WIRES DC12V
SWE
ON
OFF
SW2 SW1
LED3 LED2 LED1
ZNR
FUSE
X4
CN41 CN2L
CN51 CN32
WIRELESS
CN90
(
WHT
)
VANE
CN6V
(
GRN
)
MV
6
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2SW1
9
FAN
(
WHT
)
1 3 5
1
1
2
1
2
3
2 3
BLK
WHT
WHT
RED
RED
C
MF
X4
BCR
TO
OUTDOOR
UNIT
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
YLW
ORN
BLK
WHT
P.B
I.B
POWER
CNDK
(RED)
CNDK
(RED)
DC13.1V
CN2S
(WHT)
POWER
CND
(ORN)
POWER
CN2D(WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
3 1 3 1
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
TB2
TB4
POWER
SUPPLY
~(1PHASE)
230V 50Hz
RED
BLU
YLW
ORN
ORN
BRN
TO
OUTDOOR
UNIT
L
S1
S2
S3
N
I.B
YLW
ORN
w 1 (Fig.1)
Refer to tables 1
and 2 for service PCB.
GRN/YLW
TB2
I.B
HEATER
CN24
(YLW)
POWER SUPPLY
~(1PHASE)
230V 50Hz
88H
FS2
26H
H1
L
RED RED 5 3 RED
BLU
GRN/YLW
WHT
RED
61
RED GRY
N
2
1
2
6
5
1
FS1
88H
YLW
YLW
SW1
Service board
SW2
Service board Service board
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
MODELS
PKA-RP35GAL
PKH-P35GALH
1 2 3 4 5
ON
OFF
MODELS
PKA-RP50GAL
PKH-P50GALH
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
PKH-P35,50GALH models only
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to Fig 1.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
63
PKA-RP50FAL2 PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL
INTAKE
CN20
(
RED
)
LIQUID
CN21
(
WHT
)
PIPE
CN29
(
BLK
)
1 2
1 2
1 2
1 3 1 3 1 3 1 2
TH5 TH1
TH2
REMOCON
CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
2
1
TRANSMISSION WIRES DC12V
SWE
ON
OFF
SW2 SW1
LED3 LED2 LED1
ZNR
FUSE
X4
CN41 CN2L
CN51 CN32
WIRELESS
CN90
(
WHT
)
VANE
CN6V
(
GRN
)
MV
6
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2SW1
9
FAN
(
WHT
)
1 3 5
1
1
2
1
2
3
2 3
BLK
WHT
WHT
RED
RED
C
MF
X4
BCR
TO
OUTDOOR
UNIT
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
YLW
ORN
BLK
WHT
P.B
I.B
Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual
SW1
Table 1
Service board
SW2
Table 2
Service board Service board Service board
POWER
CNDK
(RED)
CNDK
(RED)
DC13.1V
CN2S
(WHT)
POWER
CND
(ORN)
POWER
CN2D(WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
3 1 3 1
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
TB2
TB4
POWER
SUPPLY
(1PHASE)
230V 50Hz
RED
BLU
YLW
ORN
ORN
BRN
TO
OUTDOOR
UNIT
L
S1
S2
S3
N
I.B
YLW
ORN
w
1 (Fig.1)
Refer to tables 1
and 2 for service PCB.
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
MODELS
PKA-RP50FAL2
PKA-RP60FAL
PKH-P60FALH
1 2 3 4 5
ON
OFF
MODELS
PKA-RP71FAL
PKH-P71FALH
1 2 3 4 5
ON
OFF
MODELS
PKA-RP100FAL
PKH-P100FALH
TB2
I.B
HEATER
CN24
(YLW)
PKH-P60 P100FALH models only
POWER SUPPLY
(1PHASE)
230V 50Hz
88H
FS2
26H
H1
L
RED RED 5 3 RED
BLU
GRN/YLW
WHT
RED
61
RED GRY
N
2
1
2
6
5
1
FS1
88H
YLW
YLW
GRN/YLW
P.B
INDOOR POWER BOARD
SYMBOL NAME
[LEGEND]
I.B
INDOOR CONTROLLER BOARD
FUSE FUSE(T6.3AL250V)
ZNR VARISTOR
CN2L CONNECTOR(LOSSNAY)
CN32 CONNECTOR(REMOTE SWITCH)
CN41 CONNECTOR(HA TERMINAL-A)
CN51 CONNECTOR(CENTRALLY CONTROL)
SW1 SWITCH (MODEL SELECTION)
w
See Table 1.
SW2 SWITCH (CAPACITY CODE)
w
See Table 2.
SWE SWITCH(EMERGENCY OPERATION)
X4 RELAY(FAN MOTOR)
BCR
POWER SUPPLY(R.B)
LED1 POWER SUPPLY(I.B)
LED2
TRANSMISSION(INDOOR-OUTDOOR) LED3
FAN CONTROL ELEMENT
C CAPACITOR(FAN MOTOR)
FAN MOTOR
VANE MOTOR
MF
MV
SYMBOL NAME
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR
TB2
TERMINAL BLOCK (HEATER)
w
PKH-P.FALH
models only or option for PKA-RP.FAL models.
CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )(OPTION)
ROOM TEMP.THERMISTOR
(0
;
/15k', 25;/5.4k' DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0
;
/15k', 25;/5.4k' DETECT)
COND./EVA.TEMP.THERMISTOR
(0
;
/15k', 25;/5.4k' DETECT)
TB5
TH5
TH1
TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR )
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
WIRED REMOTE CONTROLLER BOARD(OPTION)
TERMINAL BLOCK(REMOTE CONTROLLER
THERMAL FUSE(117
;
10A:60,71FALH/
117
;
16A:100FALH)
TRANSMISSION LINE)
R.B
HEATER
RU
BZ
LED1
LED2
SW1
SW2
NAME SYMBOL
HEATER
H1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
TB6
FS1,2
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to Fig 1.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
64
PCA-RP50GA PCA-RP50GA2 PCA-RP60GA PCA-RP71GA
PCA-RP100GA PCA-RP125GA PCA-RP140GA
X4 X1
FAN
(
WHT
)
1 3 1 3 1 3 1 3 5
1 2 3
BLK
WHT
RED
C
MF
DP
X4
X1
BCR
POWER
CNDK
(RED)
D.U.M
CNP
(BLU)
(OPTION)
ZNR
POWER
CND
(ORN)
1
2
1
2
3
P.B
I.B
CNDK
(RED)
DC13.1V
CN2S
(WHT)
WHT
RED
YLW
ORN
BLK
BLK
BLK
BLK
BLK
BLU
BLU
BRN
ORN
WHT
FUSE
1 2
POWER
CN2D(WHT)
1 3
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
SWE
ON
OFF
SW2 SW1
Refer to tables 1
and 2 for service PCB.
LED3 LED2 LED1
TO OUTDOOR UNIT
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
50~71 TYPE
CN41 CN2L
CN51 CN32
VANE
CN6V
(
GRN
)
MV
6 6
9
MV
6 6
WIRELESS
CN90
(
WHT
)
INTAKE
CN20
(
RED
)
LIQUID
CN21
(
WHT
)
D.SENSOR
CN31
(
WHT
)
CN31
DRAIN SENSOR
DS
PIPE
CN29
(
BLK
)
1 2 1 2 3
1 2 3
1 2
1 2
TH5 TH1
TH2
REMOCON
CN22
(
BLU
)
1 2
2
1
TB5
R.B
TB6
12
TRANSMISSION WIRES DC12V
1 2
1 2
W.B
BZ
CNB
RECEIVER
RU
LED1 LED2 SW2 SW1
100~140 TYPE
MV
5 5
31 31
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
TB2
TB4
POWER SUPPLY
~(1PHASE)
230V 50Hz
RED
BLU
YLW
GRN/YLW
ORN
ORN
BRN
TO OUTDOOR UNIT
L
S1
S2
S3
N
I.B
YLW
ORN
W
1 (Fig.1)
(
WHT
)
I.B
HEATER
CN24
(YLW)
26H
RED
61
RED GRY
2
6
5
1
88H
YLW
YLW
TB2
POWER SUPPLY
~(1PHASE)
230V 50Hz
88H
FS2
H1
L
RED RED 5 3 RED
BLU
GRN/YLW
WHT
N
2
1
FS1
PCH-P50~P140GAH
models only
Please set the voltage using the remote
controller.
For the setting method, please refer to
the indoor unit Installation Manual.
SW1
Table 1
Service board
1 2 3 4 5
ON
OFF
MODELS
PCA-RP.GA
PCH-P.GAH
SW2
Table 2
Service board
1 2 3 4 5
ON
OFF
MODELS
PCA-RP50GA
PCH-P50GAH
1 2 3 4 5
ON
OFF
PCA-RP50GA2
PCA-RP60GA
PCH-P60GAH
1 2 3 4 5
ON
OFF
PCA-RP71GA
PCH-P71GAH
Service board
1 2 3 4 5
ON
OFF
MODELS
PCA-RP100GA
PCH-P100GAH
1 2 3 4 5
ON
OFF
PCA-RP125GA
PCH-P125GAH
1 2 3 4 5
ON
OFF
PCA-RP140GA
PCH-P140GAH
P.B
INDOOR POWER BOARD
SYMBOL NAME
[LEGEND]
I.B
INDOOR CONTROLLER BOARD
FUSE FUSE (T6.3AL250V)
ZNR VARISTOR
CN2L CONNECTOR(LOSSNAY)
CN32 CONNECTOR(REMOTE SWITCH)
CN41 CONNECTOR(HA TERMINAL-A)
CN51 CONNECTOR(CENTRALLY CONTROL)
SW1 SWITCH (MODEL SELECTION) W See Table 1.
SW2 SWITCH (CAPACITY CODE) W See Table 2.
SWE SWITCH(EMERGENCY OPERATION)
X4 RELAY(FAN MOTOR)
X1 RELAY(DRAIN PUMP)
BCR
POWER SUPPLY(R.B)
LED1 POWER SUPPLY(I.B)
LED2
TRANSMISSION(INDOOR-OUTDOOR) LED3
FAN CONTROL ELEMENT
C CAPACITOR(FAN MOTOR)
FAN MOTOR
VANE MOTOR
MF
MV
DRAIN-UP MACHINE (OPTION)
DP
DRAIN SENSOR (OPTION)
DS
SYMBOL NAME
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TB2
TERMINAL BLOCK (HEATER) W PCH-P.GAH
models only or option for PCA RP.GA models.
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )
ROOM TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0;/15k', 25;/5.4k' DETECT)
COND./EVA.TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
TB5,TB6
TH5
TH1
TH2
W.B
WIRELESS REMOTE CONTROLLER BOARD(OPTION)
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR)
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
WIRED REMOTE CONTROLLER BOARD
R.B
HEATER
RU
BZ
LED1
LED2
SW1
SW2
NAME SYMBOL
HEATER
H1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
THERMAL FUSE(
98;10A:50GAH/117;16A:100GAH
110;16A:60,71,125,140GAH)
FS1,2
[Servicing]
Fasten terminal of the terminal board "TB4" that equips lock system.
To remove the fastened terminal, pull it while pressing the protruding
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
When installing drain-up
machine (Optional part)
W
When installing optional
drain-up machine, disconnect
the CN31 jumper connector
and replace it with the
drain sensor (DS).
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to Fig 1.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
65
PCA-RP71HA PCA-RP125HA
SYMBOL
[LEGEND]
NAME SYMBOL NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
MF1, MF2
C1, C2
H2
FAN MOTOR
CAPACITOR(FAN MOTOR)
DEW PREVENTION HEATER
VARISTOR
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROLL)
POWER SUPPLY (I. B)
POWER SUPPLY (R. B)
TRANSMISSION(INDOOR-OUTDOOR)
RELAY (DEW PREVENTION HEATER)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH (MODEL SELECTION)
See Table 1.
SWITCH (CAPACITY CODE) See Table 2.
SWITCH (EMERGENCY OPERATION)
P. B
I. B
FUSE
ZNR
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
X1
X4
X5
X6
SW1
TB2
TB4
TB5,TB6
TH1
TH2
TH5
R. B
TERMINAL BLOCK(INDOOR UNIT
POWER (OPTION))
TERMINAL BLOCK(INDOOR/OUTDOOR
CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP.THERMISTOR
(0˚C/15kΩ , 25˚C/5.4kΩ DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15kΩ , 25˚C/5.4kΩ DETECT)
COND./ EVA.TEMP.THERMISTOR
(0˚C/15kΩ , 25˚C/5.4kΩ DETECT)
WIRED REMOTE CONTROLLER BOARD
SW2
SWE
Service board
SW1
Table 1
1 2 3 4 5
ON
OFF
Service board
SW2
Table 2
1 2 3 4 5
MODELS
PCA-RP71HA
ON
OFF
Service board
1 2 3 4 5
MODELS
PCA-RP125HA
ON
OFF
MF1
BLU
BLK
WHT
YLW
BLU
BLK
WHT
YLW
ORN
ORN
C1
RED
RED
13 13 13 12
1
2
1
2
3
13
11
654321
MF2
BLU
YLW
YLW
ORN
BLK
RED
WHT
WHT
YLW
BLK
WHT
YLW
BLU
BLK
WHT
YLW
ORN
BRN
C2
GRY
RED
654321
D.HEATER
CNC
(RED)
For PCA-RP125HA
X6 X5 X4
X6 X5 X4
ZNR
FUSE
SWE
FAN
(WHT)
SW2 SW1
LED3 LED2 LED1
H2
OFF
ON
12 12 12
12 13
12
WHT
WHT
REMOCON
CN22
(BLU)
TH1 TH2 TH5
BLU
BLU
BLK
BLK
1
2
2
1
TB5
INTAKE
CN20
(RED)
LIQUID
CN21
(WHT)
PIPE
CN29
(BLK)
R.B
TB6
TRANSMISSION WIRES DC12V
CN41 CN2L
CN32 CN51
ROWER
CNDK
(RED)
ROWER
CND
(ORN)
DC13.1V
CNDK
(RED)
CN2S
(WHT)
P.B
I.B
BRN
YLW
ORN
ORN
S1
S2
S3
TB4
TO
OUTDOOR
UNIT
ROWER
CN2D(WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
Refer to tables 1
and 2 for service PCB.
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
3 1 3 1
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
TB4
POWER
SUPPLY
~(1PHASE)
230V 50Hz
RED
TB2
BLU
TO
OUTDOOR
UNIT
L
S1
S2
S3
N
I.B
YLW
ORN
ORN
ORN
YLW
GRN/YLW
BRN
w 1 (Fig.1)
1357
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to Fig 1.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
66
PSA-RP71GA PSA-RP100GA PSA-RP125GA PSA-RP140GA
1357
MF
ORN
C
RED
BLK
BLU
YLW
13 13 13 12
1
2
2
1
3
13
ML
YLW
YLW
BLK
ORN
YLW
YLW
ORNS1S2
S3
WHT
WHT
WHT
BRN
ORN
RED
I.B
FAN
(WHT)
LOUVER
CNL
(YLW)
X4 X5 X6
X6
X5 X4
X2
ZNR
FUSE
X2
LED3 LED2 LED1
SWE
ON
OFF
POWER
CNDK
(RED)
POWER
CND
(ORN)
POWER
CN2D
(WHT)
WIRELESS
CN90
(WHT)
2
1
REMOCON
CN22
(BLU)
CN32
CN2L
2
1
TB6
2
2
1
1
2
1
LIQUID
CN21
(WHT)
INTAKE
CN20
(RED)
PIPE
CN29
(BLK)
CN24 CN41
CN51
R.B
TRANSMISSION
WIRES DC12V
BLU
BLU
TH1
TH2
TH5
SW1 SW2
TB4
RED RED
WHT
RED
BLU
GRN/YLW
88H
FS1 FS2
H
53
1
2
L
N
TB2
POWER SUPPLY
~(1 PHASE)
230V 50Hz
2
1
6
5
RED
RED
YLW
26H
88H
YLW
YLW
16
HEATER
CN24
(YLW)
I.B
PSH -P.GAH
models only
INDOOR UNIT
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
Refer to tables 1
and 2 for service PCB.
P.B
CNSK
(RED)
CN2S
(WHT)
DC13.1V
TO
OUTDOOR
UNIT
31 31
POWER
CND
(ORN)
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
TB2
TB4
POWER SUPPLY
~(1PHASE)
230V 50Hz
RED
BLU
GRY/YLW
RED
BLU
TO
OUTDOOR
UNIT
L
S1
S2
S3
N
I.B
YLW
ORN
ORN
BRN
1 (Fig.1)
Service board
SW2
Table 2
1 2 3 4 5
MODELS
PSA-RP71GA
PSH-P71GAH
PSA-RP100GA
PSH-P100GAH
PSA-RP125GA
PSH-P125GAH
PSA-RP140GA
PSH-P140GAH
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
Service board
SW2
Table 1
1 2 3 4 5
MODELS
PSA-RP.GA
PSH-P.GAH
ON
OFF
P.B
INDOOR POWER BOARD
SYMBOL NAME
[LEGEND]
SYMBOL NAME SYMBOL NAME
I.B
I.B
INDOOR CONTROLLER BOARD
FUSE FUSE (T6.3AL250V)
ZNR VARISTOR
CN2L CONNECTOR (LOSSNAY)
CN32 CONNECTOR (REMOTE SWITCH)
CN41 CONNECTOR (HA TERMINAL-A)
CN51 CONNECTOR (CENTRALLY CONTROL)
SW1
SWITCH (MODEL SELECTION) See Table 1.
SW2
SWITCH (CAPACITY CODE) See Table 2.
SWE SWITCH (EMERGENCY OPERATION)
X4 RELAY (FAN MOTOR)
X5 RELAY (FAN MOTOR)
X6 RELAY (FAN MOTOR)
X2
RELAY (LOUVER)
POWER SUPPLY (R.B)
LED1 POWER SUPPLY (I.B)
LED2
TRANSMISSION (INDOOR-OUTDOOR) LED3
WIRED REMOTE CONTROLLER BOARD
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
R.B
TB6
HEATER
HEATER
THERMAL FUSE (110˚ C16A)
H
FS1,2
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
C CAPACITOR (FAN MOTOR)
FAN MOTOR
MF
LOUVER MOTOR
ML
TB2
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TB4
TERMINAL BLOCK (HEATER) PSH-P.GAH
models only or option for PSA-RP.GA models.
ROOM TEMP.THERMISTOR
(0˚ C/15kΩ , 25˚ C/5.4kΩ DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0˚ C/15kΩ , 25˚ C/5.4kΩ DETECT)
COND./EVA.TEMP.THERMISTOR
(0˚ C/15kΩ , 25˚ C/5.4kΩ DETECT)
TH1
TH2
TH5
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification
of 230V), adopting superimposed system of power and signal.
w 1: When supplying power separately to indoor and outdoor units, refer to Fig 1.
w 2: For power supply system of this unit, refer to the caution label located near this diagram.
67
4-2. OUTDOOR UNIT
PUHZ-RP35VHA2 PUHZ-RP50VHA2 PUHZ-RP60VHA2 PUHZ-RP71VHA2
P. B.
C. B.
CNF1
(WHT)
MF1
MS
3~
7
1
TRANS
CNDC
(PNK)
3
1
TH7/6
(RED)
63H
(YLW)
TH3
(WHT)
TH4
(WHT)
TH7 TH6 TH3 TH4
4 12 1
TH33
(YLW)
TH33
1t° 32 1
31
t°
t° t° t°
63H
LEV-A
(WHT)
LEV-A
LEV-B
(RED)
LEV-B
6 1
MM
LED1
LED2
6 1
CNVMNT
(WHT)
31
CNDM
(WHT)
CN51
(WHT)
315 1
CNMNT
(WHT)
CNM
(WHT)
5 1
3
5
SW7
SW6 SW1
SW9
CN31
1
w 1w1
SW5 SW8 SW4 SWP
14
X55
X51
CNS
(WHT)
CNAC
(WHT)
SV2
(BLU)
w 3 60 / 71 only
SS
(WHT)
21S4
(GRN)
X52
F1
F2
F4
F3
2 1
43
SV 21S4
31
1 3 1 3 1 3
CN4
(WHT)
12
2
CN52C
(RED)
221
CN2
(WHT)
7 1
5
CN5
(WHT)
31
LED2
SW1
SW11
SW12
LED3
LED4
TB7
LED1
LED5
2
1
CND
(WHT)
CN2M
(WHT)
M-NET SUBSTRATE
M-NET
BLK
BLK
ABS
When M-NET adaptor is connected
5
3
5
1
WHT
UU
LI
BLK
EI
NI
LO NO
E2
w 4
E3
U
N. F.
1
2
2
3
1
3
1
1
2
2
CN5
(RED)
CNAC1
(WHT)
CNAC2
(RED)
CN52C
(BLK)
52C
RED
POWER SUPPLY
~/N 230V 50Hz
INDOOR
UNIT
TB1
L N S1 S2 S3
RED
BLU
YLW
GRN/YLW
ORN
BRN
3
1
CNAC1
(WHT)
U
LI NI EI
CY2
w 4 For 60/ 71
CY1
CB1 CB2 CB3
TABU
TABV
THB
IPM
TABW
TABR
TABS
CN3
(WHT)
CN2
(WHT)
CN4
(WHT)
CN5
(RED)
1
7
1
2
1
2
1
2
2
2
5
t°
WHT
RED
PFC
RED
WHT
RED
WHT
ACL
w 3 60/ 71 ony
MS
3~
BLK
WHT
RED
UVW
MC
TB1
MC
MF1
21S4
63H
TH3, TH33
TH4
TH6
TH7
TH8
LEV-A, LEV-B
ACL
Terminal Block<Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
SV Solenoid Valve (Bypass Valve)
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<Heat Sink>
Electronic Expansion Valve
Reactor
Power Circuit Board
Connection Terminal<U/V/W-Phase>
P.B.
U/V/W
Noise Filter Circuit Board
Connection Terminal<L-Phase>
Connection Terminal<Ground>
N.F.
LI/LO
Connection Terminal<N-Phase>
NI/NO
E
Controller Circuit Board
Switch<Forced Defrost, Defect History
Record Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
Switch<Function Setup>
Switch<Pump Down>
Connector<Emergency Operation>
SW1
SW4
SW5
SW7
Switch
SW8
SWP
CN31
CNM
CNVMNT
CNDM
LED1,LED2
Light Emitting Diodes
<Operation Inspection Indicators>
Connector<A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
< Connected for Option (Contact Input)>
C.B.
Inverter
IPM
Main Smoothing Capacitor
CB1~CB3
52C Relay
52C
SYMBOL NAME
[LEGEND]
SYMBOL NAME SYMBOL NAME
Connection Terminal<L/N-Phase>
R/S
CNMNT
Connector
<Connected to Optional M-NET Adapter Board>
Switch<Model Select>
SW6
Switch
SW9
Fuse<T6.3AL250V>
F1~4
X51,X52,X55
Relay
SS
Connector<Connection for Option>
SYMBOL
M-NET ADAPTER
NAME
TB7
CN5
CND
CN2M
SW1
SW11
Terminal Block<M-net connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1st digit>
SYMBOL NAME
SW12
LED1
LED2
LED3
LED4
LED5
Switch<Address setting : 2nd digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Receiving>
LED<Power Supply : DC12V>
12345678
12345678
12345678
OFF
ON
35V
MODEL
SW6
w 1MODEL SELECT
SW5-6 w2
OFF
ON
OFF
ON
50V
OFF
ON
OFF
123456
123456
123456
OFF
ON
60V
ON
12345678
w 2. SW5 -1 to 5 : Function Switch
OFF
123456
OFF
ON
71V
ON
68
PUHZ-RP35VHA3 PUHZ-RP50VHA3
12345678
12345678
OFF
ON
35V
MODEL
SW6
w 1MODEL SELECT
SW5-6 w 2
OFF
ON
OFF
ON
50V
OFF
ON
123456
123456
w2. SW5 -1 to 5 : Function Switch
P. B.
C. B.
CNF1
(WHT)
MF1
MS
3~
7
1
TRANS
CNDC
(PNK)
3
1
TH7/6
(RED)
63H
(YLW)
TH3
(WHT)
TH4
(WHT)
TH7 TH6 TH3 TH4
4 12 1
TH33
(YLW)
TH33
1t° 32 1
31
t°
t° t° t°
63H
LEV-A
(WHT)
LEV-A
LEV-B
(RED)
LEV-B
6 1
MM
LED1
LED2
6 1
CNVMNT
(WHT)
31
CNDM
(WHT)
CN51
(WHT)
315 1
CNMNT
(WHT)
CNM
(WHT)
5 1
3
5
SW7
SW6 SW1
SW9
CN31
1
w 1w1
SW5 SW8 SW4 SWP
14
X55
X51
CNS
(WHT)
CNAC
(WHT)
SV2
(BLU)
SS
(WHT)
21S4
(GRN)
X52
F1
F2
F4
F3
2 1
4 3
21S4
31
1 3 1 3 1 3
CN4
(WHT)
12
2
CN52C
(RED)
221
CN2
(WHT)
7 1
5
CN5
(WHT)
31
LED2
SW1
SW11
SW12
LED3
LED4
TB7
LED1
LED5
2
1
CND
(WHT)
CN2M
(WHT)
M-NET SUBSTRATE
M-NET
ABS
When M-NET adaptor is connected
5
3
5
1
WHT
UU
LI
EI
NI
LO NO
E2
E3
N. F.
1
2
2
3
1
3
1
1
2
2
CN5
(RED)
CNAC1
(WHT)
CNAC2
(RED)
CN52C
(BLK)
BLK
BLK
52C
RED
POWER SUPPLY
~/N 230V 50Hz
INDOOR
UNIT
TB1
L N S1 S2 S3
RED
BLU
BLK
YLW
GRN/YLW
ORN
BRN
CY2
CY1
CB1 CB2 CB3
TABU
TABV
TH8
IPM
TABW
TABR
TABS
CN3
(WHT)
CN2
(WHT)
CN4
(WHT)
CN5
(RED)
1
7
1
2
1
2
1
2
2
2
5
t°
WHT
RED
PFC
RED
WHT
RED
WHT
ACL
MS
3~
BLK
WHT
RED
UVW
MC
TB1
MC
MF1
21S4
63H
TH3, TH33
TH4
TH6
TH7
TH8
LEV-A, LEV-B
ACL
Terminal Block <Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Thermistor <Outdoor Pipe>
Thermistor <Discharge>
Thermistor <Outdoor 2-Phase Pipe>
Thermistor <Outdoor>
Thermistor <Heat Sink>
Electronic Expansion Valve
Reactor
CY1,CY2
Reactor
Power Circuit Board
Connection Terminal <U/V/W-Phase>
P.B.
U/V/W
Noise Filter Circuit Board
Connection Terminal <L-Phase>
Connection Terminal <Ground>
N.F.
LI/LO
Connection Terminal <N-Phase>
NI/NO
EI,E2,E3
Controller Circuit Board
Switch <Forced Defrost, Defect History
Record Reset, Refrigerant Address>
Switch <Test Operation>
Switch <Function Switch>
Switch <Function Setup>
Switch <Pump Down>
Connection for Option
SW1
SW4
SW5
SW7
Switch <Function Setup>
SW8
SWP
CN51
CNM
CNVMNT
CNDM
LED1,LED2
Light Emitting Diodes
<Operation Inspection Indicators>
Connector <A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
< Connected for Option (Contact Input)>
C.B.
Power Module
IPM
Main Smoothing Capacitor
CB1~CB3
52C Relay
52C
SYMBOL NAME SYMBOL NAME SYMBOL NAME
Connection Terminal <L/N-Phase>
R/S
CNMNT
Connector
<Connected to Optional M-NET Adapter Board>
Switch <Model Select>
SW6
Connector <Emergency Operation>
CN31
Switch
SW9
Fuse <T6.3AL250V>
F1~4
X51,X52,X55
Relay
SS
Connector <Connection for Option>
SYMBOL
M-NET ADAPTER
NAME
TB7
CN5
CND
CN2M
SW1
SW11
Terminal Block <M-net connection>
Connector <Transmission>
Connector <Power Supply>
Connector <M-NET communication>
Switch <Status of communication>
Switch <Address setting : 1st digit>
SYMBOL NAME
SW12
LED1
LED2
LED3
LED4
LED5
Switch <Address setting : 2nd digit>
LED <Power Supply : DC5V>
LED <Connection to Outdoor Unit>
LED <Transmission : Sending>
LED <Transmission : Receiving>
LED <Power Supply : DC12V>
69
PUHZ-RP60VHA3 PUHZ-RP71VHA3
TB1
MC
MF1
21S4
63H
TH3, TH33
TH4
TH6
TH7
TH8
LEV-A, LEV-B
ACL
Terminal Block <Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
SV Solenoid Valve (Bypass Valve)
Thermistor <Outdoor Pipe>
Thermistor <Discharge>
Thermistor <Outdoor 2-Phase Pipe>
Thermistor <Outdoor>
Thermistor <Heat Sink>
TH32 Thermistor <Shell>
Electronic Expansion Valve
Reactor
CY1,CY2
Reactor
Power Circuit Board
Connection Terminal <U/V/W-Phase>
P.B.
U/V/W
Noise Filter Circuit Board
Connection Terminal <L-Phase>
Connection Terminal <Ground>
N.F.
LI/LO
Connection Terminal <N-Phase>
NI/NO
EI,E2,E3
Controller Circuit Board
Switch <Forced Defrost, Defect History
Record Reset, Refrigerant Address>
Switch <Test Operation>
Switch <Function Switch>
Switch <Function Setup>
Switch <Pump Down>
Connection for Option
SW1
SW4
SW5
SW7
Switch <Function Setup>
SW8
SWP
CN51
CNM
CNVMNT
CNDM
LED1,LED2
Light Emitting Diodes
<Operation Inspection Indicators>
Connector <A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
< Connected for Option (Contact Input)>
C.B.
Main Smoothing Capacitor
CB1~CB3
52C Relay
52C
SYMBOL NAME SYMBOL NAME SYMBOL NAME
Connection Terminal <L/N-Phase>
R/S
CNMNT
Connector
<Connected to Optional M-NET Adapter Board>
Switch <Model Select>
SW6
Connector <Emergency Operation>
CN31
Switch
SW9
X51,X52,X55
Relay
SS
Connector <Connection for Option>
Fuse <T6.3AL250V>
F1~4
Power Module
IPM
12345678
MODEL
SW6
w 1MODEL SELECT
SW5-6 w 2
OFF
123456
OFF
ON
60V
ON
12345678
w 2. SW5 -1 to 5 : Function Switch
OFF
123456
OFF
ON
71V
ON
P. B.
C. B.
CNF1
(WHT)
MF1
MS
3~
7
1
TRANS
CNDC
(PNK)
3
1
TH7/6
(RED)
63H
(YLW)
TH3
(WHT)
TH4
(WHT)
TH7 TH6 TH3 TH4
4 12 1
TH33
(YLW)
TH33
1t° 32 1
31
t° t° t°
TH32
(BLK)
TH32
21
t° t°
63H
LEV-A
(WHT)
LEV-A
LEV-B
(RED)
LEV-B
6 1
MM
LED1
LED2
6 1
CNVMNT
(WHT)
31
CNDM
(WHT)
CN51
(WHT)
315 1
CNMNT
(WHT)
CNM
(WHT)
5 1
3
5
SW7
SW6 SW1
SW9
CN31
1
w 1w1
SW5 SW8 SW4 SWP
14
X55
X51
CNS
(WHT)
CNAC
(WHT)
SV2
(BLU)
SS
(WHT)
21S4
(GRN)
X52
F1
F2
F4
F3
2 1
4 3
SV 21S4
31
1 3 1 3 1 3
CN4
(WHT)
12
2
CN52C
(RED)
221
CN2
(WHT)
7 1
5
CN5
(WHT)
31
LED2
SW1
SW11
SW12
LED3
LED4
TB7
LED1
LED5
2
1
CND
(WHT)
CN2M
(WHT)
M-NET SUBSTRATE
M-NET
ABS
When M-NET adaptor is connected
5
3
5
1
WHT
U
U
LI
EI
NI
LO NO
E2
E3
N. F.
1
2
2
3
1
3
1
1
2
2
CN5
(RED)
CNAC1
(WHT)
CNAC2
(RED)
CN52C
(BLK)
52C
RED
POWER SUPPLY
~/N 230V 50Hz
INDOOR
UNIT
TB1
L N S1 S2 S3
RED
BLU
BLK
BLK
BLK
YLW
GRN/YLW
ORN
BRN
CY2
CY1
CB1 CB2 CB3
TABU
TABV
TH8
IPM
TABW
TABR
TABS
CN3
(WHT)
CN2
(WHT)
CN4
(WHT)
CN5
(RED)
1
7
1
2
1
2
1
2
2
2
5
t°
WHT
RED
PFC
RED
WHT
RED
WHT
ACL
MS
3~
BLK
WHT
RED
UVW
MC
SYMBOL
M-NET ADAPTER
NAME
TB7
CN5
CND
CN2M
SW1
SW11
Terminal Block <M-net connection>
Connector <Transmission>
Connector <Power Supply>
Connector <M-NET communication>
Switch <Status of communication>
Switch <Address setting : 1st digit>
SYMBOL NAME
SW12
LED1
LED2
LED3
LED4
LED5
Switch <Address setting : 2nd digit>
LED <Power Supply : DC5V>
LED <Connection to Outdoor Unit>
LED <Transmission : Sending>
LED <Transmission : Receiving>
LED <Power Supply : DC12V>
[LEGEND]
SYMBOL NAME
TB1
MC
MF1, MF2
21S4
63H
SV Solenoid Valve (Bypass Valve)
TH3, TH33
TH4
TH6
TH7
TH8
LEV-A, LEV-B
DCL
ACTM
CB
P.B.
MF1
MS
3~
MF2
MS
3~
Terminal Block<Power Supply, Indoor/Outdoor >
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<
Heat Sink>
Electronic Expansion Valve
Reactor
Active Filter Module
Main Smoothing Capacitor
Power Circuit Board
Connection Terminal<U/V/W-Phase>
TABU/V/W
TABS/T
Connection Terminal <L/N-Phase>
7
7
CNDC
(PNK)
CNF1
(WHT)
CNF2
(WHT)
3
1
F2
F1
TH33
TH33
(YLW)
TRANS
C. B.
1
1
CNS
(WHT)
2
31
P. B.
4
1
CNAF
(WHT)
6
7
1
CN2
(WHT)
7
TH8
1
CN3
2
(WHT)
t°
2
1
CN5
2
(RED)
2
1
CN4
2
(WHT)
WHT
TABN
CB
TABP
RED
SYMBOL NAME SYMBOL NAME
TABP1/P2/P
TABN1/N2/N
DS2, DS3
IPM
N.F.
LI / LO
NI / NO
EI, E2
52C
C.B.
SW1
SW4
SW5
SW6
SW7
SW8
SW9
LEV-A
4 12 1
BLK
MC
TH3
(WHT)
TABW
F3
F4
TH4
(WHT)
CN2
(WHT)
CNDC
(PNK)
1
3
63H
63H
(YLW)
7
31
7 1
2
TABN1
LEV-A
(WHT)
LED2
21S4
(GRN)
U
BLK
TH7 TH6 TH3 TH4
t° t° t° t°
3t° 12 1
TH7/6
(RED)
CNAC
(WHT)
2 1
43
IPM
TABP2
RED
TABV
TABU
RED
WHT
V
UVW
MS
3~
Connection Terminal<DC Voltage>
Connection Terminal<DC Voltage>
Diode Bridge
Power Module
Noise Filter Circuit Board
Connection Terminal<L-Phase>
Connection Terminal<N-Phase>
Connection Terminal<Ground>
52C Relay
Controller Circuit Board
Switch<Forced Defrost, Defect History Record
Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
Switch<Function Setup>
Switch
Switch
LEV-B
MM
6 1
1
LEV-B
(RED)
LED1
CN4
(WHT)
21
2
X52
1 3 1 3 1 3
TABT
DS3
TABS
DS2
TABP1
TABN2
WHT
BLU
WHT
RED
3
5
6
31
CNVMNT
CNMNT
(WHT)
(WHT)
CNM
(WHT)
CN52C
(RED)
221
X55
SV2
(BLU)
SV 21S4
Switch<Pump Down>
SWP
Connector<Emergency Operation>
CN31
Connector<Connection for Option>
SS
CNM
Connector<A-Control Service Inspection Kit>
Connector
CNMNT
<Connected to Optional M-NET Adapter Board>
Connector
CNVMNT
<Connected to Optional M-NET Adapter Board>
Connector
CNDM
< Connected for Option (Contact Input)>
Light Emitting Diodes
LED1, LED2
<Operation Inspection Indicators>
Fuse< T6.3AL250V>
F1~F4
Relay
X51,X52,X55
When M-NET adaptor is connected
5
SW11
CN5
SW1
(WHT)
5
1
LED2
SW12
52C
U
ABS
BLU
LED3
LED4
M-NET SUBSTRATE
2
CN2M
(WHT)
1
LED5
TB7
M-NET
N. F.
1
2
CN52C
(BLK)
E2
1
2
CN5
(RED)
EI
U
BLU
LED1
CND
(WHT)
31
3
2
2
BLK
BLK
w 1w1
5 1
SW5 SW8 SW4 SWP
SW7
SW6 SW1
X51
SS
(WHT)
CN31
CNAC2
CNAC1
SW9
315 1
(WHT)
CNDM
CN51
(WHT)
WHT
LO NO
3
1
(RED)
3
1
(WHT)
LI NI
RED
14 1
BLK
4
WHT
L1
L2
6 1
RED
P
N1
N2
WHT
Io
DCL
RED
BLK
M-NET ADAPTER
SYMBOL
Terminal Block<M-net connection>
TB7
Connector<Transmission>
CN5
Connector<Power Supply>
CND
Connector<M-NET communication>
CN2M
Switch<Status of communication>
SW1
Switch<Address setting>
SW11
Switch<Address setting : 2nd digit>
SW12
LED<Power Supply : DC5V>
LED1
LED<Connection to Outdoor Unit>
LED2
LED<Transmission : Sending>
LED3
LED<Transmission : Receiving>
LED4
LED<Power Supply : DC12V>
LED5
ACTM
NAME
BLU
RED
L N S1 S2 S3
POWER SUPPLY
~/N 230V 50Hz
YLW
GRN/YLW
INDOOR
UNIT
ORN
BRN
w 1. MODEL SELECT
MODEL
CY1
CY2
100V
TB1
w 2. SW5 -1 to 5 : Function Switch
SW6
ON
OFF
12345678
ON
OFF
SW5-6 w2
123456
71
PUHZ-RP125VHA2 PUHZ-RP140VHA2 PUHZ-RP100VHA3
12345678
12345678
12345678
OFF
ON
100V
MODEL
SW6
w1. MODEL SELECT
w2. SW5 -1 to 5 : Function Switch
SW5-6 w 2
OFF
ON
OFF
ON
125V
OFF
ON
OFF
123456
123456
123456
OFF
ON
140V
ON
TB1
MC
MF1, MF2
21S4
63H
TH3, TH33
TH4
TH6
TH7
TH8
LEV-A, LEV-B
DCL
Terminal Block <Power Supply, Indoor/Outdoor >
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
SV Solenoid Valve (Bypass Valve)
Thermistor <Outdoor Pipe>
TABU/V/W
TABS/T
Connection Terminal <U/V/W-Phase>
Thermistor <Discharge>
Thermistor <Outdoor 2-Phase Pipe>
Thermistor <Outdoor>
Thermistor <
Heat Sink>
TH32 Thermistor <
Shell>
Electronic Expansion Valve
Reactor
Connection Terminal <L/N-Phase>
P.B.
Power Circuit Board
ACTM
Active Filter Module
CB
Main Smoothing Capacitor
CY1,CY2
Capacitor
Diode Bridge
Noise Filter Circuit Board
Connection Terminal <L-Phase>
Connection Terminal <Ground>
52C Relay
N.F.
LI / LO
Connection Terminal <N-Phase>
NI / NO
EI, E2
Controller Circuit Board
C.B.
DS2, DS3
52C
Power Module
IPM
SYMBOL NAME SYMBOL NAME SYMBOL NAME
Connection Terminal <DC Voltage>
TABP1/P2/P
Connection Terminal <DC Voltage>
TABN1/N2/N
Switch <Function Setup>
Switch <Forced Defrost, Defect History Record
Reset, Refrigerant Address>
Switch <Test Operation>
Switch <Function Switch>
Switch <Model Select>
SW7
SW1
SW4
SW5
SW6
Switch <Function Setup>
SW8
Switch
SW9
Switch <Pump Down>
SWP
Connector <Emergency Operation>
CN31
LED1, LED2
F1~F4
Light Emitting Diodes
<Operation Inspection Indicators>
Connection for Option
CN51
CNM
CNMNT
CNVMNT
CNDM
Connector <A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
< Connected for Option (Contact Input)>
Fuse < T6.3AL250V>
X51,X52,X55
Relay
SS
Connector <Connection for Option>
SYMBOL
M-NET ADAPTER
NAME
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
Terminal Block <M-net connection>
Connector <Transmission>
Connector <Power Supply>
Connector <M-NET communication>
Switch <Status of communication>
Switch <Address setting>
Switch <Address setting : 2nd digit>
LED <Power Supply : DC5V>
LED <Connection to Outdoor Unit>
LED <Transmission : Sending>
LED <Transmission : Receiving>
LED <Power Supply : DC12V>
CN5
(WHT)
31
LED2
SW1
SW11
SW12
LED3
LED4
TB7
LED1
LED5
2
1
CND
(WHT)
CN2M
(WHT)
M-NET SUBSTRATE
M-NET
ABS
When M-NET adaptor is connected
CNVMNT
(WHT)
31
CNDM
(WHT)
CN51
(WHT)
315 1
CNMNT
(WHT)
CNM
(WHT)
5 1
LEV-A
(WHT)
LEV-A
C. B.
LEV-B
(RED)
LEV-B
6
3
5
1
TH7/6
(RED)
63H
(YLW)
TRANS
X55
X51
TH3
(WHT)
CNDC
(PNK)
CNF1
(WHT)
CNF2
(WHT)
TH4
(WHT)
TH7 TH6 TH3 TH4
4 12 1
TH33
(YLW)
TH33
3t° 12 1
SW7
SW6 SW1
SW9
CN31
14 1
MF1
MF2
MS
3~
MM
MS
3~
7
1
CN2
(WHT)
CNS
(WHT)
CNAC
(WHT)
CN4
(WHT)
SV2
(BLU)
SS
(WHT)
21S4
(GRN)
21
LED1
LED2
X52
F1
F2
F4
F3
w 1w1
2 1
4 3
SW5 SW8 SW4 SWP
IPM
MS
3~
UVW
SV 21S4
6 1
31
7
1
3
1
2
31
7 1
7
2
t° t° t°
TH32
(BLK)
TH32
21
t° t°
1 3 1 3 1 3
CN52C
(RED)
221
TABN
TABP
CN3
(WHT)
CNAF
(WHT)
CN2
(WHT)
CN4
(WHT)
CN5
(RED)
TH8
CB
1
4
1
7
7
1
2
1
2
1
2
2
2
3
2
6
RED
RED
TABP2
WHT
WHT
t°
P. B.
CNDC
(PNK)
TABU
TABV
TABW
BLK
WHT
DS2
DS3
U
TABT
TABS
TABP1
TABN1
BLK
1
TABN2
WHT
WHT
BLU
BLU
RED
U
CY1
CY2
LI NI
LO NO
EI
E2
U
POWER SUPPLY
~/N 230V 50Hz
INDOOR
UNIT
TB1
L N S1 S2 S3
N. F.
MC
1
2
2
3
1
3
1
1
2
2
CN5
(RED)
RED
RED
CNAC1
(WHT)
CNAC2
(RED)
CN52C
(BLK)
52C
BLU
BLK
BLK
DCL
ACTM
L1
L2
N2
N1
P
Io
RED
BLK
RED
WHT
WHT
BLK
6 1
4
BLU
YLW
GRN/YLW
ORN
BRN
63H
5
3
5
1
RED
TB1
MC
MF1, MF2
21S4
63H
TH3, TH33
TH4
TH6
TH7
LEV-A, LEV-B
ACL1~ACL4
Terminal Block<Power Supply >
TB7 Terminal Block<M-NET connection >
CN5
Connector<
Transmission>
CND
Connector<
Power Supply>
CN2M
Connector<
M-NET communication>
SW1
Switch<
Status of communication>
SW11
Switch<
Address setting: 1st digit>
SW12 Switch<Address setting. 2nd digit >
LED1
LED<
Power Supply: DC5V>
LED2
LED<
Connection to Outdoor Unit>
LED3
LED<
Transmission: Sending>
LED4
LED<
Transmission: Receiving>
LED5
LED<
Power Supply: DC12V>
TB2 Terminal Block<Indoor/Outdoor >
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
SV
Solenoid Valve (Bypass Valve)
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Electronic Expansion Valve
Reactor
RS
Rush Current Protect Resistor
CB1, CB2
Main Smoothing Capacitor
CK
Capacitor
Power Circuit Board
Connection Terminal<U/V/ W-Phase>
P.B.
TB-U/V/ W
Noise Filter Circuit Board
Connection Terminal<
L1/L2/L3 /N-Power Supply>
N.F.
LI1/LI2 /LI3/NI
Connection Terminal<
L1/L2/L3 /N-Power Supply>
LO1/LO2 /LO3/ NO
Controller Circuit Board
Connector<Emergency Operation>
Switch
SW8
CN31
C.B.
Connection Terminal
N-IN
Connection Terminal
CK-OU
Connection Terminal<Ground>
GD1, GD3
Connection Terminal<L1-Power Supply>
L1-A1/IN
SYMBOL
M-NET ADAPTER
NAME
[LEGEND]
SYMBOL NAME SYMBOL NAME
Connection Terminal
TB-P2
Connection Terminal<
L1/L2/ L3-Power Supply>
TB-L1/L2/ L3
Switch
SW9
Switch<Pump Down>
SWP
Connection Terminal<L1-Power Supply>
L1-A2/ OU
Connection Terminal<L2-Power Supply>
L2-A2/ OU
Connection Terminal<L3-Power Supply>
L3-A2/ OU
Converter Circuit Board
CONV.B.
Switch<Forced Defrost, Defect History Record
Reset, Refrigerant Adress>
Switch<Function Switch>
Switch<Function Setup>
SW1
SW5
Switch<Model Select>
SW6
SW7
Switch<Test Operation>
SW4
LED1/LED2
LED<Operatiion Inspection Indicators>
CNM
CNMNT
CNVMNT
Connector<A-Control Service Inspection Kit>
Connector
<Connect to Optional M-NET Adapter Board>
Connector
<Connect to Optional M-NET Adapter Board>
CN3S
Connector< Connection for Option>
CNDM
Connector
< Connection for Option
(Contact Input)>
CN51
Connector< Connection for Option>
FUSE<T6.3AL250V>
F1~F4
Connection Terminal
TB-C1
Connection Terminal
TB-N1
LEV-A
(WHT)
6 1
3
LEV-B
(RED)
6 1
CNVMNT
(WHT)
CN4
(WHT)
CNMNT
(WHT)
315 1
CN5
(WHT)
31
LED2
SW1
SW11
SW12
LED3
LED4
TB7
LED1
LED5
5
1
2
3
1
CND
(WHT)
CN2M
(WHT)
M-NET
When M-NET adaptor is connected)
7 1
2
1
2
1
12
34
CNS
(WHT)
1 3
21S4
(GRN)
MF1
TRANS
MF2
CNF1
(WHT)
CNF2
(WHT)
1
3
CNDC
(PNK)
CN2
(WHT)
CNAC
(WHT)
1 3
SV2
(BLU)
X55
X51
X52
1 3
SS
(WHT)
+
--
--
+
++
+
+
ACL1
ACL2
ACL3
ACL4
CN7
(WHT)
CN2
(WHT)
TB-P2
CB1 CB2 CK
TB-C1
L3-OU
L2-OU
L1-OU
L3-A2
L2-A2
L1-A2
L1-A1
L1-IN
N-IN
CK-OU
TB-N1
TB-W
BLK
WHT
RED
BLK
WHT
RED
BLK
BRN
BLK
BLK
BLU
WHT
RED
RED
RED
RED
RED
BLK
BLU
GRN/
YLW
WHT
RED
TB-V
TB-U
TB-L3
TB-L2
TB-L1
W
V
U
MC
CN4
(WHT)
BLK
BLU
CNAC1
(WHT)
CN7
(WHT)
WHT
WHT
CN5
(RED)
CNCT
(RED)
CNAC2
(RED)
CNL
(BLU)
CNDC
(PNK)
RS
P.B.
C.B.
N.F.
CONV.B.
LO1
GD1
GD3
LO2
LO3
NO
LI1
LI2
LI3
NI
TB1
NO FUSE
BREAKER
TB2
POWER SUPPLY
3N~
400V 50Hz
INDOOR
UNIT
1
F2
F1
F3
F4
TH7/6
(RED)
63H
(YLW)
TH3
(WHT)
TH4
(WHT)
TH7 TH6 TH3 TH4
4 12 1
TH33
(YLW)
TH33
3t° 12 1
31
t° t° t° t°
63H
221
7
2
3
12345678
OFF
ON
100Y
MODEL
SW6
w1. MODEL SELECT
w2. SW5 -1 to 5 : Function Switch
SW5-6 w2
OFF
ON
123456
37
RED
WHT
BLK
7
1
7
1
7 1
RED
RED
3
3
1
3 121
LEV-A LEV-B
MM
LED1
LED2
CNM
(WHT)
1 14
3
1
3
1
5
1
3
5
CNDM
(WHT)
CN3S
(WHT)
CN51
(WHT)
SW7
SW6 SW1
SW9
CN31
w 1w1
SW5 SW8 SW4 SWP
SV 21S4
ABS
MS
3~
+
+
WHT
--
1 3 3 1
3 1
UU
U
U
U
L1
L2
L3
N
S1
S2
S3
YLW
ORN
BRN
31
MS
3~
MS
3~
2
2
2
2
2
2
M-NET SUBSTRATE
BLK
BLK
BLK
BLU
U
73
PUHZ-RP100YHA3 PUHZ-RP125YHA2 PUHZ-RP140YHA2
TB1
MC
MF1, MF2
21S4
63H
TH3, TH33
TH4
TH6
TH7
LEV-A, LEV-B
ACL1~ACL4
Terminal Block <Power Supply >
TB7 Terminal Block <M-NET connection >
CN5
Connector <
Transmission>
CND
Connector <
Power Supply>
CN2M
Connector <
M-NET communication>
SW1
Switch <
Status of communication>
SW11
Switch <
Address setting: 1st digit>
SW12 Switch <Address setting. 2nd digit >
LED1
LED <
Power Supply: DC5V>
LED2
LED <
Connection to Outdoor Unit>
LED3
LED <
Transmission: Sending>
LED4
LED <
Transmission: Receiving>
LED5
LED <
Power Supply: DC12V>
TB2 Terminal Block <Indoor/Outdoor >
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
SV
Solenoid Valve (Bypass Valve)
Thermistor <Outdoor Pipe>
Thermistor <Discharge>
Thermistor <Outdoor 2-Phase Pipe>
Thermistor <Outdoor>
TH32 Thermistor <Shell>
Electronic Expansion Valve
Reactor
RS
Rush Current Protect Resistor
X52A
52C Relay
CB1, CB2
Main Smoothing Capacitor
CK
Capacitor
Power Circuit Board
Connection Terminal <U/V/ W-Phase>
P.B.
TB-U/V/ W
Noise Filter Circuit Board
Connection Terminal <
L1/L2/L3 /N-Power Supply>
N.F.
LI1/LI2 /LI3/NI
Connection Terminal <
L1/L2/L3 /N-Power Supply>
LO1/LO2 /LO3/ NO
Controller Circuit Board
Connector <Emergency Operation>
Switch <Function Setup>
SW8
CN31
C.B.
Connection Terminal
N-IN
Connection Terminal
CK-OU
Connection Terminal <Ground>
GD1, GD3
Connection Terminal <L1-Power Supply>
L1-A1/IN
SYMBOL
M-NET ADAPTER
NAME SYMBOL NAME SYMBOL NAME
Connection Terminal
TB-P2
Connection Terminal <
L1/L2/ L3-Power Supply>
TB-L1/L2/ L3
Switch
SW9
Switch <Pump Down>
SWP
Connection Terminal <L1-Power Supply>
L1-A2/ OU
Connection Terminal <L2-Power Supply>
L2-A2/ OU
Connection Terminal <L3-Power Supply>
L3-A2/ OU
Converter Circuit Board
CONV.B.
Switch <Forced Defrost, Defect History Record
Reset, Refrigerant Adress>
Switch <Function Switch>
SW1
SW5
Switch <Model Select>
SW6
Switch <Function Setup>
SW7
Switch <Test Operation>
SW4
LED1,LED2
LED <Operatiion Inspection Indicators>
CNM
CNMNT
CNVMNT
Connector <A-Control Service Inspection Kit>
Connector
<Connect to Optional M-NET Adapter Board>
Connector
<Connect to Optional M-NET Adapter Board>
CN3S
Connector < Connection for Option>
CNDM
Connector
< Connection for Option
(Contact Input)>
CN51
Connector < Connection for Option>
FUSE <T6.3AL250V>
F1~F4
Connection Terminal
TB-C1
Connection Terminal
TB-N1
LEV-A
(WHT)
6 1
3
LEV-B
(RED)
6 1
CNVMNT
(WHT)
CN4
(WHT)
CNMNT
(WHT)
315 1
CN5
(WHT)
31
LED2
SW1
SW11
SW12
LED3
LED4
TB7
LED1
LED5
5
1
2
5
1
CND
(WHT)
CN2M
(WHT)
M-NET
When M-NET adaptor is connected)
7 1
2
1
2
1
12
34
CNS
(WHT)
1 3
21S4
(GRN)
MF1
TRANS
MF2
CNF1
(WHT)
CNF2
(WHT)
1
3
CNDC
(PNK)
CN2
(WHT)
CNAC
(WHT)
1 3
SV2
(BLU)
X55
X51
X52
1 3
SS
(WHT)
+
--
--
+
++
+
+
ACL1
ACL2
ACL3
ACL4
CN7
(WHT)
CN2
(WHT)
TB-P2
CB1 CB2 CK
TB-C1
L3-OU
L2-OU
L1-OU
L3-A2
L2-A2
L1-A2
L1-A1
L1-IN
N-IN
CK-OU
TB-N1
TB-W
BLK
WHT
RED
BLK
WHT
RED
BLK
BLU
WHT
RED
RED
RED
RED
RED
BLK
BLK
BLK
WHT
BRN
BLU
GRN/YLW
WHT
RED
TB-V
TB-U
TB-L3
TB-L2
TB-L1
W
V
U
MC
CN4
(WHT)
BLK
BLU
CNAC1
(WHT)
CN7
(WHT)
WHT
WHT
CN5
(RED)
CNCT
(RED)
CNAC2
(RED)
CNL
(BLU)
CNDC
(PNK)
RS
P.B.
C.B.
N.F.
CONV.B.
LO1
GD1
GD3
LO2
LO3
NO
LI1
LI2
LI3
NI
TB1
NO FUSE
BREAKER
TB2
POWER SUPPLY
3N~
400V 50Hz
INDOOR
UNIT
1
F2
F1
F3
F4
TH7/6
(RED)
63H
(YLW)
TH3
(WHT)
TH4
(WHT)
TH7 TH6 TH3 TH4
4 12 1
TH33
(YLW)
TH33
3t° 12 1
31
t° t° t°
TH32
(BLK)
TH32
21
t° t°
63H
221
7
2
3
12345678
12345678
12345678
OFF
ON
100Y
MODEL
SW6
w1. MODEL SELECT
w2. SW5 -1 to 5 : Function Switch
SW5-6 w2
OFF
ON
OFF
ON
125Y
OFF
ON
OFF
123456
123456
123456
OFF
ON
140Y
ON
37
RED
WHT
BLK
7
1
7
1
7 1
RED
X52A
RED
3
3
1
3 121
LEV-A LEV-B
MM
LED1
LED2
CNM
(WHT)
1 14
3
1
3
1
5
1
3
5
CNDM
(WHT)
CN3S
(WHT)
CN51
(WHT)
SW7
SW6 SW1
SW9
CN31
w 1w1
SW5 SW8 SW4 SWP
SV 21S4
ABS
MS
3~
+
+
--
1 3 3 1
3 1
UU
U
U
U
L1
L2
L3
N
S1
S2
S3
YLW
ORN
BRN
31
MS
3~
MS
3~
2
2
2
2
M-NET SUBSTRATE
BLK
BLK
BLK
BLU
U
74
PUHZ-RP200YHA2 PUHZ-RP250YHA2
TH7/6
(RED)
TH3
(WHT)
TH4
(WHT
)
TH7TH6 TH3 TH4
4 12 121
63L
LEV-B
(RED)
LEV-B
M
LED1
LED2
6 1
LEV-A
(WHT)
LEV-A
M
6 1
CNVMNT
(WHT)
31
CNMNT
(WHT)
CNM
(WHT)
5 1
35
5
14 1
63L
(RED)
31
63H1
63H
(YLW)
31
63H
63H2
CN2
(WHT)
7
7
1
CN2
(WHT)
7
7
1
CNDM
(WHT)
CN3S
(WHT)
CN51
(WHT)
13131 5
X51
X52
SW7
SW6 SW1
SW9
CN31
w1 w1
w3.
For RP200
w 3.
For RP250
w 4.
RP250 only
w6.RP250 only
w5.
RP200
=
5 LINE
RP250
=
6 LINE
SW5 SW8 SW4
SWP
CN4
(WHT)
12
1 3 1 3
2
21S4
SS
(WHT)
21S4
(GRN)
X55
1 3
SV
SV2
(BLU)
CNAC
(WHT)
F4
F3
2 1
4 3
2
3
1
CNDC
(PNK)
CNS
(WHT)
31
TRANS
CNF1
(WHT)
CNF2
(WHT)
MF1
MS
3~
7
1
7
1
MF2
MS
3~
C. B.
P. B .
CN5
(WHT)
31
LED2
SW1
SW11
SW12
LED3
LED4
TB7
LED1
LED5
2
1
CND
(WHT)
CN2M
(WHT)
M-NET SUBSTRATE
M-NET
ABS
When M-NET adapter is connected
3
5
1
2
2
1
2
2
1
CN4
(WHT)
CN5
(RED)
WHT
FUSE1
FUSE2
WHT
RED RED
MS
3~
POWER
SUPPLY
3N~
400V 50Hz
INDOOR
UNIT
TB1
L3
L2
L1
N
U
U
UU
U
3 1
2
2
1 3
CNDC
(PNK)
CNL
(BLU)
3 1 12
CNCT
(RED)
CNAC2
(RED)
3 1
CNAC1
(WHT)
BLK
BLK
WHT
WHT
U
LO 1
LO 2
LO3
LI 1
LI 2
LI 3
NI
RED
WHT
BLU
BLK
GRN/YLW
GD2 GD1
RED
WHT
BLK
N. F.
TB2
DCL
ACL4
S3
S2
S1
ORN
YLW
CY2
CY1
BRN
NO FUSE
BREAKER
RED
RED
RS
RED
WHT
WHT
WHT
BLK
BLK
BLK
X52A
BLK
BLK
TB-P2
TB-P1
TB-C1 TB-N1
CB1 CB2
W
V
MC
U
TB-L1
TB-L2
TB-L3
SC-U
SC-V
SC-W
RED
MODEL
SW6
w
1 MODEL SELECT
SW5-6 w2
12345678
w
2. SW5 -1 to 5 : Function Switch
OFF
123456
OFF
ON
200Y
ON
12345678
OFF
123456
OFF
ON
250Y
ON
FUSE1, FUSE2
Connector<Connection for Option>
CN51
Relay
X51,X52,X55
Connector<Connection for Option>
CN3S
TB1
MC
MF1,MF2
21S4
63H,63H1,63H2
TH3
TH4
TH6
TH7
LEV-A,LEV-B
DCL
Terminal Block<Power Supply>
TB2 Terminal Block<Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
SV Solenoid Valve (Bypass Valve)
High Pressure Switch
63L Low Pressure Switch
Thermistor<Outdoor Pipe>
SC-U/V/W
TB-L1/L2/L3
Connection Terminal<U/V/W-Phase>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Fuse<T15AL250V>
Capacitor
Electronic Expansion Valve
Reactor
ACL4
Reactor
Connection Terminal<L1/L2/L3-Power supply>
P.B .
Power Circuit Board
RS
Rush Current Protect Resistor
CB1,CB2
CY1,CY2
Main Smoothing Capacitor
Connection Terminal
Noise Filter Circuit Board
Connection Terminal
<L1/L2/L3/NI-Power supply
>
Connection Terminal<Ground>
52C Relay
N.F.
LI1/ LI2/LI3/NI
LO1/ LO2/LO3
Connection Terminal
<L1/L2/L3-Power supply>
GD1,GD2
Controller Circuit Board
C.B.
TB-C1
X52A
Connection Terminal
TB-N1
SYMBOL
[LEGEND]
NAME SYMBOL NAME SYMBOL NAME
Connection Terminal
TB-P1
Connection Terminal
TB-P2
Switch<Function Setup>
Switch<Function Setup>
Switch<Forced Defrost, Defect History Record
Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
SW7
SW1
SW4
SW5
SW6
SW8
Switch
SW9
Switch<Pump Down>
SWP
Connector<Emergency Operation>
LED<Operation Inspection Indicators>
CN31
F3,F4
CNMNT
CNVMNT
CNDM
Connector
< Connected for Option (Contact Input)>
Fuse< T6.3AL250V
>
LED1,LED2
CNM
Connector<A-Control Service Inspection Kit>
SS
Connector<Connection for Option>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
<Connected to Optional M-NET Adapter Board>
Terminal Block(M-NET connection)
Connector<Transmission>
Connector<Power Supply>
LED<Power Supply:DC5V>
LED<Power Supply:DC12V>
LED<Connection to Outdoor Unit>
LED<Transmission:Sending>
LED<Transmission:Receiving>
Connector<M-NET communication>
SYMBOL
NAME
Switch<Address setting:2nd digit>
Switch<Status of communication>
Switch<Address setting:1st digit>
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
M-NET ADAPTER
75
5
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT
PLA-RP·BA(2) PLA-RP·AA(2) PCA-RP·GA(2) PCA-RP·HA
PKA-RP·GAL PKA-RP·FAL(2) PSA-RP·GA
PEAD-RP·EA(2) PEAD-RP·GA
Thermistor TH2
Pipe temperature (Liquid)
Distributor
with strainer(#50)
Thermistor TH5
(Cond./Eva. temperature)
Thermistor TH1
(Room temperature)
Refrigerant flow in cooling
Refrigerant flow in heating
Strainer(#50)
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Refrigerant LIQUID pipe connection
(Flare)
PEA-RP400GA PEA-RP500GA
PEA-RP200, 250GA
Heat exchanger
Room temperature
thermistor(TH1)
Pie temperature
thermistor/Liquid
(TH2)
Heat exchanger
Strainer
Condenser/evaporator
temperature thermistor
(TH5)
Strainer
Strainer
Condenser/evaporator
temperature thermistor
(TH5-2)
Refrigerant GAS pipe connection
Brazing
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
Brazing
Refrigerant GAS pipe connection
Brazing
Refrigerant flow in cooling
Refrigerant flow in heating
Room temperature
thermistor(TH1-1)
Room temperature
thermistor(TH1-2)
Pie temperature
thermistor/Liquid
(TH2-2)
Condenser/evaporator
temperature thermistor
(TH5-1)
Pie temperature
thermistor/Liquid
(TH2-1)
Refrigerant LIQUID pipe connection
Brazing
Strainer
Strainer
Refrigerant GAS pipe connection
Brazing
Refrigerant LIQUID pipe connection
Brazing
Strainer
77
PUHZ-RP60VHA2
PUHZ-RP71VHA2
5-2. OUTDOOR UNIT
Unit : mm (inch)
PUHZ-RP35VHA2 PUHZ-RP35VHA3
PUHZ-RP50VHA2 PUHZ-RP50VHA3
Thermistor TH7
(Outdoor)
Heat exchanger
Refrigerant GAS pipe
connection(1/2)
Refrigerant LIQUID pipe
connection(1/4)
Stop valve
Strainer
#100
Power
receiver
Linear
expansion valve B
Thermistor TH6
(Outdoor 2-phase pipe)
Thermistor TH3
(Outdoor pipe)
Charge plug
High pressure
switch 63H
Thermistor TH4
(Discharge)
Compressor
Strainer
#50
Solenoid valve
(Four-way valve)
Muffler
Distributor
Thermistor TH33
(Outdoor pipe)
Linear expansion valve A
Strainer
#100
Muffler
Stop valve
(with service port)
Thermistor TH33
(Outdoor pipe)
Distributor
Thermistor TH7
(Outdoor)
Heat exchanger
Refrigerant GAS pipe
connection(5/8)
Refrigerant LIQUID pipe
connection(3/8)
Stop valve
(with service port)
Strainer
#100
Powe r
receiver
Linear
expansion
valve B
Linear expansion valve A
Strainer
#100
Strainer
#100
Strainer
#100
Thermistor TH6
(Outdoor 2-phase pipe)
Thermistor TH3
(Outdoor pipe)
Charge plug
(Low pressure)
Charge plug
(High pressure)
High pressure
switch 63H
Bypass valve
Oil separator
Thermistor TH4
(Discharge)
Muffler
Strainer
#50
4-way valve
Compressor
Ball valve
Capillary tube
O.D.4. 0OI.D.2.4O L500
Capillary tube
O.D.2. 5OI.D.0.6O L1000
Refrigerant flow in cooling
Refrigerant flow in heating
78
PUHZ-RP100VHA2 PUHZ-RP125VHA2 PUHZ-RP140VHA2
PUHZ-RP100YHA2 PUHZ-RP125YHA2 PUHZ-RP140YHA2
PUHZ-RP100VHA3 PUHZ-RP100YHA3
Distributor
Thermistor TH7
(Outdoor)
Heat exchanger
Refrigerant GAS pipe
connection(5/8)
Refrigerant LIQUID pipe
connection(3/8)
Stop valve
(with service port)
Strainer
#100
Powe r
receiver
Linear
expansion valve B
Linear expansion valve A
Strainer
#100
Strainer
#100
Strainer
#100
Thermistor TH6
(Outdoor 2-phase pipe)
Thermistor TH3
(Outdoor pipe)
Charge plug
(Low pressure)
Charge plug
(High pressure)
High pressure
switch 63H
Replace filter
Thermistor TH4
(Discharge)
Thermistor TH32 (Shell)
(Only for RP100VHA3/YHA3
RP125,140)
Compressor
Strainer
#50
4-way valve
Strainer
#100
Strainer
#100
Muffler
Ball valve
Restrictor
valve
Bypass valve
Thermistor TH33
(Outdoor pipe)
Refrigerant flow in cooling
Refrigerant flow in heating
PUHZ-RP60VHA3 PUHZ-RP71VHA3 unit : mm(inch)
Distributor
Thermistor TH7
(Outdoor)
Heat exchanger
Refrigerant GAS pipe
connection [ 15.88(5/8)
Refrigerant LIQUID pipe
connection [ 9.52(3/8)
Stop valve
(with service port)
Strainer
#100
Powe r
receiver
Linear
expansion valve B
Linear expansion valve A
Strainer
#100
Strainer
#100
Strainer
#100
Thermistor TH6
(Outdoor 2-phase pipe)
Thermistor TH3
(Outdoor pipe)
Charge plug
(Low pressure)
Charge plug
(High pressure)
Replace filter
Thermistor TH4
(Discharge)
Thermistor TH32
(Shell)
Thermistor TH33
(Outdoor pipe)
Compressor
Strainer
#50
4-way valve
Strainer
#100
Muffler
Muffler
Stop valve
Restrictor
valve
Bypass valve
High pressure
switch 63H
PUHZ-RP200YHA2
Ball valve
Refrigerant GAS pipe
[ 25.4([ 1)
Refrigerant LIQUID pipe
[ 9.52([ 3/8)
Strainer
(#50)
Service
port
(check)
Accumulator
Stop valve
(with service port)
Strainer
(#40)
4-way valve
Strainer
(#100)
Restrictor
valve
Strainer
(#100)
Muffler
Compressor
Linear expansion
valve
Outdoor heat exchanger
High pressure
switch(63H)
Service
port
(check)
Thermistor
(TH4)
Refrigerant flow in cooling
Refrigerant flow in heating
Distributor
Strainer
(#100)
Thermistor
(TH7)
Thermistor
(TH6)
Thermistor
(TH3)
PUHZ-RP250YHA2
Ball valve
Refrigerant GAS pipe
[ 25.4([ 1)
Stop valve
(with service port)
Refrigerant LIQUID pipe
[ 12.7([ 1/2)
Strainer
(#50)
Strainer
(#100)
Linear
expansion valve B
Strainer
(#100)
High pressure
switch(63H2)
Service
port
(check)
Restrictor
valve
Power
receiver
Capillary tube
O.D.4. 0OI.D.3.0O L500
4-way valve
Low pressure
switch(63L)
Linear expansion valve A
Muffler
Compressor
Replace
filter
High pressure
switch (63H1)
Service
port
(check)
Bypass valve
Heat exchanger
Thermistor (TH4)
(Discharge)
Strainer
(#100)
Thermistor (TH7)
Thermistor (TH6)
Thermistor (TH3)
Distributor
Replace filter
Bypass valve
80
PERFORMANCE CURVES 6
Note : These diagrams show the case where the operation frequency of a compressor is fixed.
FOR THE COMBINATION OF OUTDOOR UNIT
-5 0 5 10 15 20 25 30 35 40 46
16
18
20
22
0.6
0.8
1.0
1.2
1.4
Cooling capacity ratio
Outdoor intake air dry-bulb temperature <D.B. :>
-5 0 5 10 15 20 25 30 35 40 46
16
18
20
22
0.4
0.6
0.8
1.0
1.2
Cooling input ratio
Outdoor intake air dry-bulb temperature <D.B. :>
Cooling capacity
Cooling input
Indoor intake air wet-bulb temperature <W.B. :>
Indoor intake air wet-bulb temperature <W.B. :>
81
Note : These diagrams show the case where the operation frequency of a compressor is fixed.
Heating capacity
Heating input
Indoor intake air dry-bulb temperature <D.B. :>
Indoor intake air dry-bulb temperature <D.B. :>
Outdoor intake air wet-bulb temperature <W.B. :>
Outdoor intake air wet-bulb temperature <W.B. :>
82
7-1. PUHZ-RP· VHA2 PUHZ-RP100-140YHA2 PUHZ-RP· VHA3 PUHZ-RP100YHA3
7
CORRECTION FACTORS
Refrigerant piping length (one way)
80m 70m 60m 55m 50m 40m 30m
20m
10m 5m
Outdoor unit
Cooling capacity correction factors
PUHZ-RP60VHA2
PUHZ-RP60VHA3
PUHZ-RP71VHA2
PUHZ-RP71VHA3
PUHZ-RP100VHA2
PUHZ-RP100VHA3
PUHZ-RP100YHA2
PUHZ-RP100YHA3
PUHZ-RP125VHA2
PUHZ-RP125YHA2
PUHZ-RP140VHA2
PUHZ-RP140YHA2
PUHZ-RP50VHA2
PUHZ-RP50VHA3
PUHZ-RP35VHA2
PUHZ-RP35VHA3
Outdoor unit
PUHZ-RP60VHA2
PUHZ-RP60VHA3
PUHZ-RP71VHA2
PUHZ-RP71VHA3
PUHZ-RP100VHA2
PUHZ-RP100VHA3
PUHZ-RP100YHA2
PUHZ-RP100YHA3
PUHZ-RP125VHA2
PUHZ-RP125YHA2
PUHZ-RP140VHA2
PUHZ-RP140YHA2
PUHZ-RP50VHA2
PUHZ-RP50VHA3
PUHZ-RP35VHA2
PUHZ-RP35VHA3
Refrigerant piping length (one way)
80m 70m 60m 55m 50m 40m 30m
20m
10m 5m
Heating capacity correction factors
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.992
0.985
0.992
0.988
0.985
0.981
0.976
0.976
0.957
0.976
0.966
0.957
0.946
0.931
0.962
0.931
0.962
0.946
0.931
0.914
0.893
0.949
0.908
0.949
0.929
0.908
0.885
0.858
0.936
0.886
0.936
0.913
0.886
0.858
0.827
0.930
0.876
0.930
0.905
0.876
0.845
0.813
—
—
—
—
0.865
0.834
0.800
—
—
—
—
0.846
0.812
0.775
—
—
—
—
0.829
0.792
0.753
Refrigerant piping length (one way)
60m 55m 50m 40m 30m
20m
10m 5m
Outdoor unit
Cooling capacity correction factors
PUHZ-RP200YHA2
PUHZ-RP250YHA2
1.00
1.00
0.985
0.981
0.958
0.946
0.931
0.914
0.908
0.885
0.887
0.858
0.876
0.845
0.865
0.834
Refrigerant piping length (one way)
125m 120m 110m 100m 90m
80m
75m 70m
125m 120m 110m 100m 90m
80m
75m 70m
Outdoor unit
PUHZ-RP200YHA2
PUHZ-RP250YHA2
0.847
0.812
0.838
0.802
0.829
0.792
0.815
0.772
0.800
0.758
0.790
0.743
0.780
0.730
0.778
0.725
Refrigerant piping length (one way)
60m 55m 50m 40m 30m
20m
10m 5m
Outdoor unit
Heatling capacity correction factors
PUHZ-RP200YHA2
PUHZ-RP250YHA2
1.00
0.997 0.991 0.985 0.979 0.973 0.970 0.967
Refrigerant piping length (one way)
Outdoor unit
PUHZ-RP200YHA2
PUHZ-RP250YHA2
0.961
0.958 0.955 0.949 0.943 0.937 0.931 0.928
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.997
0.997
0.997
0.997
0.997
0.997
0.997
0.991
0.991
0.991
0.991
0.991
0.991
0.991
0.985
0.985
0.985
0.985
0.985
0.985
0.985
0.979
0.979
0.979
0.979
0.979
0.979
0.979
0.973
0.973
0.973
0.973
0.973
0.973
0.973
0.970
0.970
0.970
0.970
0.970
0.970
0.970
—
—
—
—
0.967
0.967
0.967
—
—
—
—
0.961
0.961
0.961
—
—
—
—
0.955
0.955
0.955
83
APPLICABLE EXTENSION PIPE FOR EACH MODEL 8
8-1. PUHZ-RP· VHA2 PUHZ-RP100-140YHA2 PUHZ-RP· VHA3 PUHZ-RP100YHA3
8-1-1. PIPE LENGTH
(1) 1:1 SYSTEM
Pipe length
(2) TWIN AND TRIPLE SYSTEM
(a) TWIN SYSTEM (b) TRIPLE SYSTEM
50m
[30m]
<Marks in the table>
The maximum pipe length
Charge-less pipe length
: It can be used.
: Cooling capacity is lowered.
: Additional refrigerant charge is required when
the pipe length exceeds 10m.
RP35• 50
RP60• 71
RP100~140
Liquid
pipe
(mm)
<Table 1> Maximum pipe length
OD
Thickness
OD
Thickness
Gas
pipe
(mm)
[ 12.7
t0.8
30m
[20m]
30m
[30m]
[ 15.88
t1.0
w 2
30m
[20m]
Standard size
50m
[30m]
Standard size
50m w 3
[30m]
[ 19.05
t1.0
50m
[30m]
[ 15.88
t1.0
30m
[20m]
50m
[20m]
[ 19.05
t1.0
50m
[20m]
[ 9.52
t0.8
[ 9.52
t0.8
30m w 1
[30m]
[ 12.7
t0.8
Standard size
50m
[30m]
10m
[10m]
[ 15.88
t1.0
w 2
30m
[30m]
10m
[10m]
[ 6.35
t0.8
[ 12.7
t0.8
w1. RP50 : maximum pipe length is 10m.
w2. Change the SW8-1 on the outdoor controller circuit board from OFF to ON.
w3. The maximum length is 75m in case of new pipes.
[9.52
[
15.88
Standard size
50m w
[30m]
50m
[30m]
[9.52
[
15.88
Standard size
50m w
[30m]
[9.52
[
19.05
50m
[30m]
50m
[30m]
[6.35
[
12.7
[9.52
[
15.88
Standard size
50m
[30m]
50m
[30m]
[9.52
[
19.05
50m
[30m]
[12.7
[
19.05
50m
[20m]
50m
[20m]
[12.7
[
19.05
50m
[20m]
RP100(RP50o 2) RP71(RP35o 2)
RP125(RP60o 2) • RP140(RP71o 2)
[6.35
[12.7
[9.52
[15.88
[12.7
[19.05
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Branch
pipe
(mm)
[B, C]
Main pipe
(mm)
[A]
w The maximum length is 75m in case of new pipes.
<Table 2> Maximum pipe length
ø
9.52
ø 15.88
Standard size
50m w
[30m]
50m
[30m]
ø
9.52
ø 19.05
50m
[30m]
50m
[30m]
ø
12.7
ø 19.05
50m
[20m]
50m
[20m]
RP140(RP50o 3)
ø6.35
ø12.7
ø9.52
ø15.88
ø12.7
ø19.05
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
w The maximum length is 75m in case of new pipes.
Branch
pipe
(mm)
[B, C, D]
Main pipe
(mm)
[A]
<Table 3> Maximum pipe length
A
C
B
Indoor unit side
Outdoor unit side
Outdoor unit
Indoor unit
Indoor unit
Distribution pipe
H
h
<TWIN SYSTEM>
Total length A + B + C
RP71 : 50 m
RP100-140: 75 m
A
C
B
Indoor unit side
Outdoor unit side
Outdoor unit
Indoor unit
D
Indoor unit
Indoor unit
Distribution pipe
H
h
<TRIPLE SYSTEM>
Total length A + B + C + D
RP140: 75 m
84
8-1-2. ADJUSTING THE AMOUNT OF REFRIGERANT
• Check additional refrigerant charging amount referring to table 5, 6 when liquid pipe is 1 size larger than standard diameter.
2.5kg
3.5kg
5.0kg
31 – 40m
0.2kg
0.6kg
0.6kg
41 – 50m
0.4kg
1.2kg
1.2kg
51 – 60m
1.8kg
61 – 70m 71 – 75m
2.4kg
<Table 7> Additional refrigerant charging amount for pipe of standard diameter
Outdoor unit Type
Type
Permitted
pipe length
Additional refrigerant charging amount
for pipe length exceeding 30 m (kg)
Amount of unit
filling refrigerant (kg)
PUHZ-RP35,50
PUHZ-RP71
PUHZ-RP100~140
1 : 1
system
50m or less
75m or less
3.5kg
5.0kg
31 – 40m
0.6kg
0.6kg
41 – 50m
1.2kg
1.2kg
51 – 60m
1.8kg
61– 70m 71 – 75m
2.4kg
Outdoor unit
Permitted
pipe length
Additional refrigerant charging amount
for pipe length exceeding 30 m (kg)
Amount of unit
filling refrigerant (kg)
PUHZ-RP71
PUHZ-RP100~140
Twin Triple
system
50m or less
75m or less
[9.52
[12.7
[12.7
PUHZ-RP35,50
PUHZ-RP60,71
PUHZ-RP100~140
Liquid pipe O.D.
60 g per 1 m
100 g per 1 m
100 g per 1 m
Refrigerant amount to be added
<Table 6> Required additional charge when the pipe size is 1 size larger than the standard diameter (TWIN/TRIPLE SYSTEM)
<Table 5> Required additional charge when the pipe size is 1 size larger than the standard diameter (1:1 SYSTEM)
Outdoor unit
PUHZ-RP71~140
When the extension pipe length (main piping + branch piping) exceeds 20 m
Additional refrigerant amount W(g) = (100 o L1) + (60 o L2) + (30 o L3) - 2000
If the calculation produces a negative number ( W [ 0), additional charging is not necessary.
L1:
[12.7 liquid pipe length (m)
L2: [ 9.52 liquid pipe length (m)
L3: [ 6.35 liquid pipe length (m)
Outdoor unit
85
8-1-3. CAPACITY CORRECTION CURVES
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is 1 size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
1 size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
[Sample calculation]
Indoor unit RP60 oo 2 units (Twin system)
Outdoor unit RP125 oo 1
■ Condition Using existing pipes.
• Outdoor unit side
Liquid pipe [[ 12.7 / Gas pipe [[ 19.05
pipe length (A) 20m
• Indoor unit side
Liquid pipe [[ 9.52 / Gas pipe [[ 15.88
pipe length (B) 20m + (C) 15m
1) Farthest piping length 20m + 15m = 35m
Number of bends : 10
2) Corrected piping length 35m + 0.3 oo 10 = 38m
3) Capacity correction Outdoor unit side’ s gas pipe [[ 19.05
Standard [[ 15.88 → 1 size up
Refer to 11 Capacity curves <Standard size>
4) Capacity Cooling capacity = Standard cooling capacity oo 0.89
Heating capacity = Standard heating capacity oo 0.98
11
Capacity curves for PUHZ-RP · HA2 model <Standard size>
Cooling
Heating
100
95
90
85
80
75
70
5 1 01 52 02 53 03 54 04 55 05 56 06 57 07 58 0
Note: The permitted pipe length is up to 55m for RP35, 50, 60, 71 model.
The permitted pipe length is up to 80m for RP100 ~ 140 model.
Cooling RP71 model
Cooling RP35, 60 models
Cooling RP50, 100 models
Heating RP35, 50, 60,
71, 100, 125 and 140
models
(Up to 55m for RP35,
50, 60, 71 models)
Cooling RP125 model
Cooling RP140 model
Capacity ratio [%]
Corrected pipe length [m]
86
44
When gas pipe is one size larger than standard size for PUHZ-RP100, 125 and 140
.
1 Capacity can be obtained by referring to capacity curves of standard size.
33
Capacity curve for PUHZ-RP60, 71 models
<When gas pipe is 1 size smaller than standard size>
5 1 01 52 02 53 03 5
80
Capacity ratio [%]
Corrected pipe length [m]
85
90
95
100
Heating RP60, RP71 ([ 12.7)
Cooling RP60,RP71 ([ 12.7)
22
Capacity curve for PUHZ-RP35, 50 models
<When gas pipe is 1 size smaller than standard size>
5 1 01 52 02 53 03 5
80
Capacity ratio [%]
Corrected pipe length [m]
85
90
95
100
Heating RP35, RP50 ([ 9.52)
Cooling RP35 ([ 9.52)
Cooling RP50
([ 9.52)
Cooling
Heating
87
8-2. PUHZ-RP200· 250YHA2
8-2-1. 1:1 SYSTEM
(1) Pipe length
(2) Adjusting the amount of refrigerant
Check additional refrigerant charging amount referring to table 7 when the liquid pipe diameter is 1 size larger
than the standard size, and table 2 when the pipe of the standard diameter is used.
<Table 2>
<Table 1> Maximum pipe length (RP200· RP250)
Note :
w1 The maximum pipe length is 120m in case of new piping.
w2 When using [ 31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
• Be sure to use hard (tempered) one for pipe over [ 22.2(RP200)/ [ 19.05(RP250).(Do not use soft (annealed) one.)
70m
[30m]
SW
SW : When the outdoor unit is located lower than
the indoor unit, set DIP SW8-1 on the outdoor
unit controller board to ON.
<Marks in the table above>
The maximum pipe length
Charge-less pipe length
: It can be used.
: Cooling capacity is lowered. Refer to <Table6>.
: Additional refrigerant charge is required when
the pipe length exceeds 20m. Refer to <Table7>.
Liquid
pipe
(mm)
gas
pipe
(mm)
OD
Thick-
ness
OD
Thick-
ness
RP200
RP250
[ 9.52
t0.8
[ 12.7
t0.8
[ 15.88
t1.0
[ 19.05
t1.0
20m
[20m]
20m
[20m]
[ 22.2
t1.0
50m
[30m]
50m
[30m]
[ 25.4
t1.0
Standard size
70mw 1
[30m]
70m
[30m]
[ 28.58
t1.0
70m
[30m]
70m
[30m]
[ 19.05
t1.0
20m
[20m]
20m
[20m]
[ 22.2
t1.0
50m
[30m]
50m
[30m]
[ 25.4
t1.0
70m
[30m]
Standard size
70mw 1
[30m]
[ 22.2
t1.0
50m
[20m]
50m
[20m]
[ 25.4
t1.0
50m
[20m]
50m
[20m]
[ 28.58
t1.0
SW
50m
[20m]
50m
[20m]
[ 28.58
t1.0
70m
[30m]
70m
[30m]
[ 31.75
t1.0
w 2
SW
50m
[20m]
50m
[20m]
SW SW SWw2
SW SW
SW
Amount of additional refrigerant charge (kg)
30 m and less 31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less
71-120 m and less
0.9 kg 1.8 kg 2.7 kg 3.6 kg
1.2 kg 2.4 kg 3.6 kg 4.8 kg
Outdoor unit
permitted
pipe length
RP200
RP250
120m or less
Initial charge
(kg)
6.5
7.1
No additional
charge necessary
The additional charge
amount is obtained by
the following formula.
Main piping:
Liquid line size
[ 9.52 overall length [m]
o
0.09
[kg/m]
Branch piping: Liquid
line size
[ 9.52 overall length [m]
o 0.06 [kg/m]
Branch piping: Liquid
line size
[ 6.35 overall length [m]
o 0.02 [kg/m]
3.6 (kg)
Amount of additional
charge [kg]
Main piping:
Liquid line size
[ 12.7 over all length [m]
o 0.12 [kg/m]
– =
Additional charge amount
for 70 m
RP200 3.6 kg
RP250
4.8 kg
+
+
+
Calculate the additional charge amount based on the following procedure.
If the calculation results in an amount that is smaller than the "Additional charge amount for 70m," perform the additional charge using the amount shown
in "Additional charge amount for 70m."
• If the wiring connecting the indoor and outdoor units is longer than 80m, use separate indoor /outdoor unit
power supplies.
88
(3) Capacity correction
Cooling and heating capacity is lowered according to the piping length. Capacity can be obtained by referring
to the following capacity curves.
When the diameter of the gas pipe is smaller than the standard size, cooling capacity is lowered comparing to
the operation using the standard diameter pipe.
The lowered capacity can be obtained by referring to the capacity curves for gas pipe which is 1 or 2 size
smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends o 0.3 (m)
1. Capacity curves 1 <Standard size>
2. Capacity curves 2 <When the gas pipe's diameter is 1-size-smaller than the standard size>
3. Capacity curves 3 <When the gas pipe's diameter is 2-size-smaller than the standard size>
Cooling
Heating
RP200
RP250
RP200,250
5 101520253035404550556065707580859095100105110115 125 120
70
75
80
85
90
95
100
Corrected pipe length [m]
Capacity ratio [%]
70
75
80
85
90
95
100
5 1 0 1 52 02 53 03 54 04 5 5 05 5
Corrected pipe length [m]
Capacity ratio [%]
Heating RP200([ 22.2), RP250([ 25.4)
Cooling RP200([ 22.2)
Cooling RP250([ 25.4)
70
75
80
85
90
95
100
5 1 01 52 02 5
Corrected pipe length [m]
Cpacity ratio [%]
Cooling RP250([ 22.2)
Cooling RP200([ 19.05)
Heating RP200([ 19.05), RP250([ 22.2)
8-2-2. TWIN, TRIPLE AND QUADRUPLE SYSTEM
(1) Twin
(2) Triple
(3) Quadruple
Maximum pipe length (Main pipe[A]+Branch pipe diameter [ B and C ])
pipe
[mm]
[B, C]
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
[6.35
[12.7
[9.52
[15.88
[9.52
[19.05
[12.7
[19.05
Main pipe
(mm)[A]
Branch
w1 The maximum pipe length is 120m in case of new pipping.
w2 When using [ 31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
• Be sure to use hard (tempered) one for pipe over [22.2(RP200)/ [ 19.05(RP250).(Do not use soft (annealed) one.)
Maximum pipe length (Main pipe [A] + Branch pipe [ B, C and D ])
pipe
[mm]
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
[6.35
[12.7
[9.52
[15.88
[9.52
[19.05
[12.7
[19.05
Main pipe
(mm)[A]
Branch
[B, C, D]
w1 The maximum pipe length is 120m in case of new pipping.
w2 When using [ 31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
• Be sure to use hard (tempered) one for pipe over [22.2(RP200)/ [ 19.05(RP250).(Do not use soft (annealed) one.)
Maximum pipe length (Main pipe[A]+Branch pipe [ B, C, D and E ])
pipe
[mm]
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
[6.35
[12.7
[9.52
[15.88
[9.52
[19.05
[12.7
[19.05
Main pipe
(mm)[A]
Branch
[B, C, D, E]
w1 The maximum pipe length is 120m in case of new pipping.
w2 When using [ 31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
• Be sure to use hard (tempered) one for pipe over [22.2(RP200)/ [ 19.05(RP250).(Do not use soft (annealed) one.)
[9.52
[19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75
Standard
sw
size
[9.52
[9.52
70mw1
[30m]
70m
[30m]
70m
[30m]
Standard
size
70mw1
[30m]
70m
[30m]
70m
[30m]
Standard
size
70mw1
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
sw
sw
sw
sw
sw
sw
sw
sw
50m
20m
[30m]
[20m]
20m
50m
[20m]
[30m]
20m
50m
[20m]
[30m]
[ 19.05 [ 22.2 [ 25.4 [ 28.58 [ 19.05 [ 22.2 [ 25.4 [ 28.58 [ 22.2 [ 25.4 [ 28.58 [ 31.75 [ 19.05 [ 22.2 [ 25.4 [ 28.58 [ 19.05 [ 22.2 [ 25.4 [ 28.58 [ 22.2 [ 25.4 [ 28.58 [ 31.75
20m
50m
[20m]
[30m]
20m
50m
[20m]
[30m]
20m
50m
[20m]
[30m]
[ 19.05 [ 22.2 [ 25.4 [ 28.58 [ 19.05 [ 22.2 [ 25.4 [ 28.58 [ 22.2 [ 25.4 [ 28.58 [ 31.75 [ 19.05 [ 22.2 [ 25.4 [ 28.58 [ 19.05 [ 22.2 [ 25.4 [ 28.58 [ 22.2 [ 25.4 [ 28.58 [ 31.75
20m
50m
[20m]
[30m]
20m
50m
[20m]
[30m]
20m
50m
[20m]
[30m]
[ 12.7 [ 15.88 [ 9.52 [ 12.7 [ 15.88
20m
[20m]
20m
[20m]
20m
[20m]
50m
[30m]
50m
[30m]
50m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
sw
50m
50m
[20m]
[20m]
sw
50m
50m
[20m]
[20m]
sw
50m
50m
[20m]
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
sw
sw
w 2
50m
20m
[20m]
w 2
sw
50m
[20m]
w 2
sw
50m
[20m]
50m
[20m]
[30m]
sw
20m
50m
[20m]
[30m]
sw
20m
50m
[20m]
[30m]
[ 12.7 [ 15.88 [ 9.52 [ 12.7 [ 15.88
20m
[20m]
20m
[20m]
20m
[20m]
50m
[30m]
50m
[30m]
50m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
sw
50m
50m
[20m]
[20m]
sw
50m
50m
[20m]
[20m]
sw
50m
50m
[20m]
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
sw
sw
w 2
50m
20m
[20m]
w 2
sw
50m
[20m]
w 2
sw
50m
[20m]
50m
[20m]
[30m]
sw
20m
50m
[20m]
[30m]
sw
20m
50m
[20m]
[30m]
[ 12.7 [ 15.88 [ 9.52 [ 12.7 [ 15.88
20m
[20m]
20m
[20m]
20m
[20m]
50m
[30m]
50m
[30m]
50m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
sw
50m
50m
[20m]
[20m]
sw
50m
50m
[20m]
[20m]
sw
50m
50m
[20m]
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
sw
sw
w 2
50m
[20m]
sw
w 2
sw
20m
50m
[20m]
w 2
sw
50m
[20m]
50m
[20m]
[30m]
sw
20m
50m
[20m]
[30m]
20m
50m
[20m]
[30m]
SW SW
20m
70m
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
[20m]
SW
20m
[20m]
SW
20m
[20m]
SW
20m
[20m]
SW
20m
[20m]
SW
20m
[20m]
RP250 quadruple (RP60O 4) RP200 quadruple (RP50O 4)
SW
20m
70m
70m
[30m]
70m
[30m]
70m
[30m]
[30m]
70m
[30m]
70m
[30m]
[20m]
SW
20m
[20m]
SW
20m
[20m]
RP250 twin (RP125O 2) RP200 twin (RP100O 2)
50m
[30m]
50m
[30m]
50m
[30m]
Standard
size
70mw1
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
50m
[20m]
SW
50m
[20m]
SW
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
SW
w 2 SW
50m
[20m]
SW
w 2 SW
50m
[20m]
SW
w 2 SW
50m
[20m]
RP250 triple (RP71O 3) RP200 triple (RP60O 3)
SW
50m
[30m]
50m
[30m]
50m
[30m]
50m
[30m]
50m
[30m]
50m
[30m]
Standard
size
70mw1
[30m]
70m
[30m]
70m
[30m]
Standard
size
70mw1
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
70m
[30m]
50m
[20m]
SW
50m
[20m]
SW
50m
[20m]
SW
50m
[20m]
SW
50m
[20m]
SW
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
SW
w 2 SW
50m
[20m]
SW
w 2 SW
50m
[20m]
SW
w 2 SW
50m
[20m]
w 2 SW
SW
50m
[20m]
w 2 SW
SW
50m
[20m]
w 2 SW
SW
50m
[20m]
<
Marks in the table above
70m
[30m]
SW
>
SW : When the outdoor unit is located lower than
the indoor unit, set DIP SW8-1 on the outdoor
unit controller board to ON.
: It can be used.
: Cooling capacity is lowered. Refer to <Table6>.
: Additional refrigerant charge is required when
the pipe length exceeds 20m. Refer to <Table7>.
The maximum pipe length
Charge-less pipe length
Pipe diameter and thickness
OD
[ 6.35
(mm)
Thickness
(mm)
Be sure to use hard (tempered) one for pipe over [ 19.05(RP250)/[ 22.2(RP200).(Do not use soft (annealed) one.)
[ 9.52 [ 12.7 [
0.8
0.8 0.8 1.0 1.0 1.0 1.0 1.0
15.88[19.05
[ 22.2 [ 25.4 [
28.58
[
31.75
1.1
1
1 Indoor unit
2
Outdoor unit
3
Main piping
4
Branch piping
5
Multi distribution
pipe (option)
Height difference (Indoor unit-
1
Outdoor unit) Max. 30 m
Height difference (Indoor unit-
2
Indoor unit) Max. 1 m
3
Distance between indoor and indoor units
pipe length.
Number of pipe bends
4
Within 15 points
8 points between main pipe A and
each branch pipe (B, C, D, E).
Max. 8m
B— C B— D B— E
C— D C— E D— E
4 4
1
4
E
1
1
B C
2
4
D
1
5
3
2
A
<Table 6> Lowered cooling capacity by the smaller gas pipe diameter
Pipe length
5m and less
6~10m
11~20m
21~30m
31~40m
41~50m
Cooling capacity ratio
gas pipe [ 22.2 gas pipe [ 19.05
100%
100~95%
95~88%
88~83%
83~79%
79~75%
100%
100~88%
88~77%
<Table 7> Additional refrigerant amount when the liquid pipe of the larger diameter is used.
(Single /Simultaneous Twin / Simultaneous Triple / Simultaneous Quadruple)
When the extension pipe length (main piping + branch piping) exceeds 20m Capacity
RP200, RP250
Additional refrigerant amount W(g)=(180o L1 )+(120o L2 ) (90o L3 )+(30o L4 )-3000
L1 : [ 15.88 liquid pipe (m) L2 : [ 12.7 liquid pipe (m)
3 : [ 9.52 liquid pipe (m) L 4 : [ 6.35 liquid pipe (m)
L
If the calculation produces a negative number (i.e. a "minus" charge), additional charging is not necessary.
( W [ 0)
<Table 8>
Outdoor unit piping length or piping length
RP200
PR250
Permissible total A+B or A+C Charge-less
A+B+C+D+E A+D or A+E A+B+C+D+E
120 m and less 100 m and less 30 m and less
<Table 9>
Outdoor unit
RP200
RP250
B-C or B-D or
B-E or C-D or
C-E or D-E
8 m and less Within 15
Number of
pipe bends
91
1. Perform refrigerant piping connections for the indoor / outdoor unit while the outdoor unit's stop valve is completely
closed (Initial setting), and then vacuumize the refrigerant lines through the service port of the outdoor unit.
2. Open the stop valves of the outdoor unit completely.
This will completely connects the refrigerant circuits of the indoor and outdoor units.
Stop valve opening method is shown on the outdoor unit’ s installation manual.
Note :
· Apply refrigerating machine oil over the flare seat surface. Do not apply to the threaded portion.
(It will cause the flare nut to loosen.)
· Use 2 wrenches to tighten piping connection.
· Use leak detector or soapy water to check for gas leaks after connections are completed.
· For the insulation of the connection at the indoor side, make sure to use the attached insulation materials and
thoroughly follow the instruction shown in the manual.
· Always use a non-oxidizing brazing material when brazing the pipes.
Adjusting the amount of refrigerant
Check additional refrigerant charging amount referring to the procedure 2 below when the liquid pipe diameter of the main
piping A is larger than the standard size.
1 When the standard diameter pipe is used for the main piping A, calculate the additional refrigerant amount by
referring to <Table 2> as well as the 1:1 system.
2 When the liquid pipe diameter of the main piping A is one size larger than the standard size:
· When the extension pipe length (main piping + branch piping) does not exceed 20m, adjustment of the
refrigerant is not necessary (charge-less).
· When the extension pipe length (main piping + branch piping) exceeds 20m, charge the amount of refrigerant
that is obtained by the formula shown in <Table 7>.
If the calculation produces a negative number (i.e. a "minus" charge), additional charging is not necessary.
Note: Apply 0 to L
1, L 2, L 3 and L 4 which correspond to the liquid pipe size that are not used.
Correcting the capacity value
When calculating the lowered capacity by the extension pipe length, use the longest length between the indoor and the outdoor
units.
A+B+C+D
Amount of additional refrigerant charge (kg)
30 m and less 31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less
71-120 m and less
0.9 kg 1.8 kg 2.7 kg 3.6 kg
1.2 kg 2.4 kg 3.6 kg 4.8 kg
Outdoor unit
permitted
pipe length
RP200
RP250
120m or less
At time of shipping
(kg)
6.5
7.1
No additional
charge necessary
The additional charge
amount is obtained by
the following formula.
Main piping:
Liquid line size
[ 9.52 overall length
0.09 (Gas line:[ 28.58)
Branch piping: Liquid
line size
[ 9.52 overall length
0.06 (Gas line: [ 15.88)
Branch piping: Liquid
line size
[ 6.35 overall length
0.02 (Gas line: [ 15.88)
3.6 (kg)
Amount of additional
charge
Main piping:
Liquid line size
[ 12.7 overall length
0.12
– =
Additional charge amount
for 70 m
RP200
3.6 kg
RP250 4.8 kg
When the total length of the piping exceeds 70 m, calculate the amount of additional charge based on the following requirements.
Note: If the calculation produces a negative number (i.e. a “minus” charge), or if calculation results in an amount that is less than the
“Additional charge amount for 70 m,”perform the additional charge using the amount shown in “Additional charge amount for 70 m.”
+++
When length exceeds 70 m
<Table 10>
92
9
AIR FLOW DATA
9-1. OUTLET AIR SPEED AND COVERAGE RANGE
PLA-RP71AA
PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
28
4.9
7.4
30
6.6
8.9
30
6.6
8.9
Airflow
Air speed
Coverage range
m
3
/min.
m/sec.
m
20
4.0
5.7
14
2.8
4.0
18
3.6
5.2
18
3.6
5.2
PLA-RP35AA PLA-RP50AA
PLA-RP60AA
Airflow
Air speed
Coverage range
m
3
/min
m/sec
m
PCA-RP50GA
PCA-RP50GA2
PCA-RP60GA
PCA-RP71GA PCA-RP100GA
PCA-RP125GA PCA-RP140GA
25
4.1
12.6
34
4.4
15.2
34
4.4
15.2
18
3.8
10.4
18
3.8
10.4
13
3.7
8.8
Airflow
Air speed
Coverage range
m
3
/min
m/sec
m
19
2.9
7.9
38
4.2
13.2
PCA-RP71HA PCA-RP125HA
12
5.3
10(32.8)
PKA-RP35GAL
12
5.3
10(32.8)
PKA-RP50GAL
Airflow
Air speed
Coverage range
m
3
/min
m/sec
m(ft)
20
4.9
12.4(40.7)
PKA-RP71FAL
20
4.9
12.4(40.7)
PKA-RP50FAL2
PKA-RP60FAL
28
5.4
15.3(50.2)
PKA-RP100FAL
Airflow
Air speed
Coverage range
m3/min
m/sec
m(ft)
Airflow
Air speed
Coverage range
m
3
/min
m/sec
m
PSA-RP71GA PSA-RP100GA PSA-RP125GA PSA-RP140GA
18
2.6
8.3
31
4.5
14.3
33
4.8
15.2
35
4.9
16.1
PLA-RP71BA
PLA-RP71BA2
PLA-RP100BA
PLA-RP100BA2
PLA-RP125BA
PLA-RP125BA2
PLA-RP140BA
30
5.3
8.0
32
5.6
8.5
31
5.4
8.2
Airflow
Air speed
Coverage range
m
3
/min.
m/sec.
m
21
3.7
5.6
15
2.6
4.1
18
3.2
4.8
18
3.2
4.8
PLA-RP35BA PLA-RP50BA PLA-RP60BA
w The air coverage range is the distance to which the 0.25m/sec air can reach, when air is blown out horizontally from the unit
at the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
93
9-2. PLA-RP· BA(2)
9-2-1 FRESH AIR INTAKE AND BRANCH DUCT
1.
Branch duct hole and fresh air intake hole (Fig. 1)
At the time of installation, use the duct holes (cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
Branch duct hole
A
A
A
14-[ 2.8 burring hole
Indoor unit
[ 150 cut out hole
Fresh air intake hole
[ 175 burring hole pitch
Drain pipe
Fresh air intake hole diagram
Refrigerant pipe
3-[ 2.8 burring hole
Branch duct
hole diagram
(view from
either side)
[ 125 burring hole pitch
[ 100 cut out hole
Ceiling
Unit:mm
*158
120
120
350
90
70°
100 100 90
100
130
*155
*167
Fig. 1
94
3. Fresh air intake volume & static pressure characteristics
-200
-150
-100
-50
0
50
01234 56
3 At using multi-function casement, high efficiency filter
Static pressure[Pa]
-200
-150
-100
-50
0
50
01234 56
2 Direct intake to unit
Static pressure[Pa]
-200
-150
-100
-50
0
50
02468
2 Direct intake to unit
Static pressure[Pa]
Static pressure[Pa]
Static pressure[Pa]
-200
-150
-100
-50
0
50
02468
1 At using multi-function casement, standard filter
-200
-150
-100
-50
0
50
02468
3 At using multi-function casement, high efficiency filter
-200
-150
-100
-50
0
50
01234 56
Airflow rate [m3/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
Airflow rate [m
3
/min]
1 At using multi-function casement, standard filter
PLA-RP35~71BA(2)
PLA-RP100~140BA(2)
Static pressure[Pa]
4. Change of outlet numbers
5. Branch duct and change of outlet numbers
<4- way air flow and branch duct>
w Branch duct should be connected to one of the branch duct holes on the main unit.
Branch
duct
Air intake
Air
outlet
<3- way air flow and branch duct>
w Close the outlet on the side of branch duct and air flows in 3 directions.
Branch
duct
Air intake
Air
outlet
Air
outlet
closed
position
Air
outlet
closed
position
<2- way air flow and branch duct>
w The outlet on the side of branch duct and one of the other outlets are closed.
Air flows in 2 directions.
Air intake
Branch
duct
Air
outlet
closed
position
Air
outlet
closed
position
The optional air outlet is necessary.
To change the air outlet number to 3-, or 2-way outlet, the
outlet number should be closed with the operational air
outlet shutter.
When the air outlets are closed, close the vane by
removing the vane connector.
Indoor unit
Button
Vane motor
Up/down vanes
Connector
Vane motor
Connector
Button
Outlet concave
portion
Air outlet shutter plate
(Option)
4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct
30
30
Duct
20
10
Static pressure [Pa]
High
20
10
Static pressure [Pa]
Duct
High
Low
0
02
Airflow rate [m
468
3
/min]
0
02468
Low
Airflow rate [m
3
/min]
3-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct
80
70
60
Duct
Close
50
40
30
Static pressure [Pa]
20
High
10
Low
80
70
60
Duct
Close
50
40
30
Static pressure [Pa]
High
20
Low
10
0
024681 0
Airflow rate [m
3
/min]
2-way airflow (horizontal vane) Round duct
100
90
80
Duct
Close
Close
70
60
50
40
Static pressure [Pa]
30
20
High
Low
10
0
0 2 4 6 8 10 12
Airflow rate [m
3
/min]
0
024681 0
Airflow rate [m
3
/min]
2-way airflow (horizontal vane) Rectangular duct
100
90
80
70
60
50
40
Static pressure [Pa]
30
20
Low
10
0
024681 01 2
Duct
Close
High
Airflow rate [m
3
/min]
• Use 1 of the 2 duct holes on the indoor unit.
• Airflow rate of PLA-RP35~60BA can be calculated from the airflow rate based on the characteristic
of the duct for PLA-RP71BA(2).
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
Close
4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct
0
10
20
30
02468
Airflow rate [m
3
/min] Airflow rate [m3/min]
Static pressure [Pa]
0
10
20
30
02468
Static pressure [Pa]
High
High
Low
Duct
Duct
Low
0
10
20
30
40
50
60
70
80
024681 0
0
10
20
30
40
50
60
70
024681 0
3-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct
Airflow rate [m3/min] Airflow rate [m3/min]
Static pressure [Pa]
80
Static pressure [Pa]
High
Low
High
Low
Duct
Duct
Close Close
• Use 1 of the 2 duct holes on the indoor unit.
• Airflow rate of PLA-RP100BA(2), PLA-RP140BA can be calculated from the airflow rate based on the characteristic
of the duct for PLA-RP125BA(2).
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
0
10
20
30
40
50
60
70
80
90
100
024681 01 2
0
10
20
30
40
50
60
70
80
90
100
024681 01 2
Close
Close
Close
Close
2-way airflow (horizontal vane) Round duct 2-way airflow (horizontal vane) Rectangular duct
Airflow rate [m3/min] Airflow rate [m3/min]
Static pressure [Pa]
Static pressure [Pa]
High
Low
High
Low
Duct Duct
PLA-RP125BA PLA-RP125BA2
97
9-3. PLA-RP·AA, PLA-RP·AA2
9-3-1. Fresh air intake amount
98
9-3-2. BRANCH DUCT (Installation at site)
99
Branch duct airflow rate/static pressure characteristics
PLA-RP35AA
4-way airflow (horizontal vane) Rectangular duct 4-way airflow (horizontal vane) Round duct
3-way airflow (horizontal vane) Rectangular duct 3-way airflow (horizontal vane) Round duct
2-way airflow (horizontal vane) Rectangular duct 2-way airflow (horizontal vane) Round duct
100