Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
In case of using the existing pipes for R22, be careful with
the followings.
· For RP4, 5 and 6, be sure to perform replacement opera tion before test run.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant
charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
2-1. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
3
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.Specifications
1Gauge manifold·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3Electronic scale
4Gas leak detector·Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check·Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder·Only for R410ATop of cylinder (Pink)
8Refrigerant recovery equipment
specifications
Cylinder with syphon
. (UNF1/2)
4
2-2. Changed point
Connecting a new air conditioner
1Flaring work should be done so that flare meets the dimension for R410A.
Use flare nut provided with indoor and outdoor unit.
2When using gas piping of [19.05mm for RP4, 5 or 6.
Make sure that DIP SW8-1 on outdoor unit controller board is set to ON.
WThis is to keep the pressure on pipes within permissible range.
●Use different diameter joint or adjust the piping size by brazing.
3When using pipes larger than specified size for RP1.6, 2, 2.5 or 3.
Make sure that DIP SW8-1 on outdoor unit controller board is set to ON.
W
This is to prevent oil flow ratio from lowering due to the decrease in flowing refrigerant.
●Use different diameter joint or adjust the piping size by brazing.
4When existing pipes are specified size.
The pipes can be reused referring to table 1 on page 18.
●Use different diameter joint or adjust the piping size by brazing.
★When using existing pipes for RP4, 5 and 6.
Make sure that DIP SW8-2 on outdoor unit controller board is set to ON and perform
replacement operation.
wChemical compounds containing chlorine left in existing pipes are collected by rep lace filter.
●The air conditioner automatically performs cooling operation through replace filter
for about 2 hours.
Measure the existing pipe thickness and check for damage.
Check if existing air conditioner can operate.
Existing air conditioner can
operate.
Disconnect existing air conditioner from piping.
Existing pipes can be reused.
In case the unit is RP1.6, 2,
2.5 ro 3 which utilizes AB oil.
In case the unit is RP4, 5
or 6 which utilize ester oil.
Perform cooling operation
for about 30 minutes and
then do a pump down work.
Use a refrigerant recovery
equipment to collect the refrigerant.
Check the oil condition
when collecting the refrigerant.
Disconnect existing air conditioner
from pipes and clean pipes using
cleaning device.
Existing air conditioner
cannot operate.
The existing pipe thickness meets specifications and the pipes are not damaged.
The existing pipe thickness does not meet
specifications or the pipes are damaged.
Oil is clean.
Connect a new air conditioner.Connect a new air conditioner.
Perform replacement operation.
Oil is dirty.
Attach a filter drier.
When the compressor bearings
are glazed, rotation scratches
are present, or the compressor
breaks down, iron particles or
oil deterioration will blacken the
oil.
·When performing replacement operation, make sure that DIP SW8-2 on outdoor unit controller board is
set to ON.
wChemical compounds containing chlorine left in existing pipes are collected by replace filter.
●The air conditioner automatically performs cooling operation through replace filter for about 2 hours.
Existing pipes cannot be
reused. Use new pipes.
• Precautions when reusing existing R22 refrigerant pipes
(1) Flowchart
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
Air purge and refrigerant charge
Operation check and the two above
Gas leak check
Collection of refrigerant
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Charge refrigerant
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Charge refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil and alkylbenzene
oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adopter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
Tool exclusive for R410A
Tools and materialsUseR410A toolsCan R22 tools be used?
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
Can R407C tools be used?
Ester oil:
Alkylbenzene oil: minimum amount
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410Ais same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working
pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
1Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7mm or below.)
2Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because of its working pressure higher than that of other refrigerants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also
have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring
dimensions for R410A below. For 1/2” and 5/8”, the dimension B changes.
Use torque wrench corresponding to each dimension.
Dimension A
3Tools for R410A (The following table shows whether conventional tools can be used or not.)
6
Dimension B
3COMBINATION OF INDOOR AND OUTDOOR UNITS
Heat pump type
Outdoor unit
PUHZ-RP
PEAD-RP·EA.UK
PEAD-RP·EA1.UK
PLA-RP·AA.UK
PLA-RP·AA1.UK
PEAD-RP·GA.UK
PLA-RP·AA
PLA-RP·AA1
—
—
OC293
REVISED EDITION-B
OC297
REVISED EDITION-B
PKA-RP·GAL
OC301
REVISED EDITION-A
PKA-RP·FAL
OC305
PCA-RP·GA
OC311
Indoor unit
Service
Manual No.
Service Ref.
45
Heat pump
without
electric heater
VHA
VHA
1
VHA
VHA
1
VHA
VHA
1
VHA
VHA
1
6
3
22.5
VHAVHAVHA
VHA
1
1.6
——
—
—
—
—
—
————
———
4PART NAMES AND FUNCTIONS
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
(Max.30m(PUHZ-RP1.6~RP6))
The refrigerant circuit with LEV(Linear Expansion Valve) and power receiver always control the optimal refrigerant
level regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during
installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality
and reliability of the work done.It also helps to speed up the installation time.
PUHZ-RP6VHAPUHZ-RP6VHA1
7
5SPECIFICATIONS
Service Ref.
Function
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Crankcase heater
Heat exchanger
FanFan(drive) o No.
OUTDOOR UNIT
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current
Model
Motor output
Starter type
Protection devices
Fan motor output
Airflow
Charge
Oil (Model)
K
/min(CFM
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NOISE
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
12
7OUTLINES AND DIMENSIONS
Service panel
for charge plug
w 1 In the place where short cycle tends to occur, cooling and heating
capacity and power consumption might get lowered 10%. Air outlet
guide (optional PAC-SG58SG) will help them improve.
w 2 If air discharges to the wall, the surface might get stained.
Minimum installation space for outdoor unit
100 mm or more as long as
no obstacle is placed on the
rear and light-and-left sides
of the unit.
2 sides should be open in
the right, left and rear side.
w 2
w 1
100 mm or more
500 mm or more
Basically open
100 mm or more
Free space around the outdoor unit
(basic example)
350 mm or more
w 1
Air intake
Air discharge
Air intake
Connection for
gas pipe
Service port
Connection for
liquid pipe
Service panel
4-10 o 21 oval hole
(M10 foundation bolt)
[33 drain hole
[33 drain hole
43.6
152
155
400
347.5
45.4
365
330
300
40
Handle for
moving
600
10
300
150
287.5
Installation bolt pitch: 500
800
69
35
43
183
90
155
23
32.5
18
1. FOUNDATION BOLTS
2. PIPING-WIRING DIRECTION
Piping and wiring connection can
be made from the rear direction only.
3. ATTACHING THE CONDUIT
In order to attach the conduit, it is
necessary to fix the metal plate with
2 screws to the back panel. Procure
the metal plate and make screw holes
locally. It is recommended to use the
metal plate shown below. Align the
metal plate to the marks on the unit
and attach it.
<Foundation bolt height>
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts, washer and nut must
be purchased locally.)
18 or below
40
20
60
80
w Conduit hole
w The position and the size of
conduit hole depend on the
conduit to be used.
Holes for metal plate fixing screw
w The size of hole depends on the
screw to be used.
The cable shall not be lighter than design 245 IEC or 227 IEC.
The cable length may vary depending on the condition of installation, humidity or materials, etc.
Cross section
of cable
Wire size
2
)
(mm
Number
of wires
PolarityL(m)
Round
2.5
3
Clockwise : S1-S2-S3
Flat
2.5
3
Not applicable
(Because center wire has no cover finish)
Flat
1.5
4
From left to right : S1-Open-S2-S3
Round
2.5
4
Clockwise : S1-S2-S3-Open
Connect S1 and S3 to the opposite angle
✽1 : In case that cable with stripe of yellow and green is available.
✽2 : In the flat cables are connected as this picture, they can be used up to 80m.
(50)
✽1
Not
applicable
✽2
(45)
✽3
60
✽4
(3C Flat cable ✕ 2)
S1 S2 S3
✽3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
✽4 : In case of regular polarity connection (S1-S2-S3).
<Table 2> Additional refrigerant charging amount for pipe of standard diameter
<Table 3>
Outdoor unit
Permitted
pipe length
Additional refrigerant charging amount for pipe
length exceeding 30 m (kg)
PUHZ-RP1.6, 2VHA
PUHZ-RP2.5, 3VHA, 2.5, 3VHA
1
PUHZ-RP4-6VHA, RP4-6VHA
1
Outdoor unit
Number of
bends
Height
difference
50m or less
50m or less
75m or less
Permitted
pipe length
50m or less
50m or less
75m or less
75m or less
2.1
3.1
5.1
4.6
11 — 20m 21 — 30m
2.3
3.3
5.3
4.8
2.5
3.5
5.5
5.0
31 — 40m
2.7
(0.2)
4.1
(0.6)
6.1
(0.6)
5.6
(0.6)
2.9
(0.4)
4.7
(1.2)
6.7
(1.2)
6.2
(1.2)
—
—
—
—
7.3
(1.8)
6.8
(1.8)
—
—
—
—
7.9
(2.4)
7.4
(2.4)
41 — 50m 51 — 60m 61 — 75m
Recharge refrigerant amount or additional amount in parentheses
PUHZ-RP1.6, 2VHA
PUHZ-RP2.5, 3VHA
PUHZ-RP2.5, 3VHA
1
PUHZ-RP4-6VHA
PUHZ-RP4-6VHA
1
Liquid
pipe
(mm)
Gas
pipe
(mm)
[6.35
[9.52[12.7
[9.52
OD
Thick-
ness
OD
Thick-
ness
RP1.6
RP2
RP2.5
RP3
RP4
RP5
RP6
t0.8
[12.7
t0.8
[15.88
t1.0
[12.7
t0.8
[15.88
t1.0
[19.05
t1.0
[15.88
t1.0
[19.05
t1.0
t0.8
t0.8
: Standard piping
: It can be used, however, additional refrigerant charge is required when the pipe length exceeds 20m. Refer to <table 4>.
: It cannot be used.
: It can be used.
: It can be used, however, the capacity is lowered. Refer to (c) Capacity correction.
<Table 1> Pipe length for 1:1 system
*1: Set DIP SW8-1 on outdoor unit controller board to ON.
*2: The maximum length is 50 m in case of using existing pipes.
[Marks in the table above]
50m
t0.8
30m30m
10m30m30m
50m
30m
50m
50m
10m
50m
(*1)
75m
(*2)
50m
10m30m30m10m50m
75m
(*2)
75m
(*2)
50m
(*1)
30m
(*1)
50m
(*1)
50m
(*1)
50m
(*1)
50m
(*1)
50m10m30m30m30m
(*1)
<Table 4>
Required additional charge when the pipe size is larger than the standard diameter
[9.52
[12.7
[12.7
RP1.6, 2
RP2.5, 3
RP4-6
Liquid pipe dia
Chargeless
30m
30m
50m
60 g per 1 m longer than 20 m
100 g per 1 m longer than 20 m
100 g per 1 m longer than 20 m
20m
20m
20m
Max. pipe length
Refrigerant amount to be added
The height difference between indoor and outdoor unit should be kept within 30 m for all models.
(1) 1:1 system
(a) Maximum pipe length
(b) Adjusting the amount of refrigerant
• Additional refrigerant charge is not necessary for the pipe length up to 30 m. When the pipe length exceeds 30 m or service
(refrigerant replacement) is performed, charge proper amount of refrigerant for each pipe length referring to table below.
Use refrigerant R410A. Use charge hose exclusive for R410A.
• When charging additional refrigerant, charge the refrigerant from low-pressure side of the port valve using a safety charger.
• Make sure that air purge for this unit at refrigerant replacement is performed from both high-pressure check valve and ser-
vice port. If air purge is performed only from one of them, air in not purged enough.
• When replacing refrigerant, charge the refrigerant from service port. When charged refrigerant is less than specified amount,
charge the refrigerant again from low pressure side of the port valve using a safety charger.
• Tighten the service port cap (nut) of stop valve firmly. The tightening torque is 12 to 16 N·m. (to prevent slow-leak)
• Check additional refrigerant charging amount referring to table 4 when liquid pipe is one size larger than standard diameter,
and table 2 when the pipe is standard diameter.
21
(c) Capacity correction
Cooling
Heating
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
11
Capacity curves for PUHZ-RP • HA model <Standard size>
100
95
90
85
80
Capacity ratio [%]
75
Note: The permitted pipe length is up to 55m for RP1.6, 2, 2.5, 3 model.
70
5 101520253035404550556065707580
Corrected pipe length
22
Capacity curve for PUHZ-RP1.6, 2 models
<When gas pipe is one size smaller than standard size>
Cooling RP1.6, 2.5 models
Cooling RP3 model
Heating RP1.6, 2, 2.5,
3, 4, 5 and 6 models
(Up to 55m for RP1.6,
2, 2.5, 3 model)
Cooling RP2, 4 models
Cooling RP5 model
Cooling RP6 model
100
95
90
Cooling RP2
Capacity ratio [%]
85
80
5 10152025303540455055
Heating RP1.6, RP2
Cooling RP1.6
Corrected pipe length
22
33
Capacity curve for PUHZ-RP2.5, 3 models
<When gas pipe is one size smaller than standard size>
100
Heating RP2.5, RP3
95
90
Cooling RP2.5
Capacity ratio [%]
85
Cooling RP3
80
5 10152025303540455055
Corrected pipe length
44
When gas pipe is one size larger than standard size for PUHZ-RP4, 5 and 6.
1 Capacity can be obtained by referring to capacity curves of standard size.
23
1. Refrigerant collecting (pump down)
TEST RUN
OFF
12
ON
<SW4>
AB
CD
A Stop C operation
B Cooling D Heating
Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit.
1Before collecting the refrigerant, first make sure that the all of the SW5 DIP switches for function changes on the control
board of the outdoor unit are set to OFF. If all of the SW5 switches are not set to OFF, record the settings and then set all of
the switches to OFF. Now, start refrigerant collecting operation. After moving the unit to a new location and completing the
test run, set the SW5 switches to the previously recorded settings.
2Turn on the power supply (circuit breaker).
wWhen power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If
“CENTRALLY CONTROLLED” is displayed, the refrigerant collecting (pump down) cannot be completed normally.
3After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor
(outdoor unit) and ventilators (indoor and outdoor units) start operating and refrigerant collecting operation begins. LED1 and
LED2 on the control board of the outdoor unit are lit.
wSet the SWP switch (push-button type) to ON in order to perform refrigerant collecting operation only when the unit is
stopped. However, refrigerant collecting operation cannot be performed until compressor stops even if the unit is stopped.
Wait three minutes until compressor stops and set the SWP switch to ON again.
4Because the unit automatically stops in about two to three minutes after the refrigerant collecting operation (LED1 is not lit
and LED2 is lit), be sure to quickly close the gas stop valve.
wIn case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then
repeat step 3 three minutes later.
wIf the refrigerant collecting operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain
stopped until the power supply is turned off.
5Turn off the power supply (circuit breaker.)
2. Unit replacement operation
When reusing the existing pipes that carried R22 refrigerant for the RP4, RP5 and RP6 models, replacement operation
must be performed before performing a test run.
1If new pipes are used, these procedures are not necessary.
2If existing pipes that carried R22 refrigerant are used for the RP3 model, these procedures are not necessary. (The replace-
ment operation cannot be performed.)
3During replacement operation, “C5” is displayed on “A-Control Service Tool(PAC-SK52ST)”. (This is applied to only RP4,
RP5 and RP6 models.)
• Replacement operation procedures
1Turn on the power supply.
2Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start replacement operation.
• The replacement operation is performed using the cooling system. Cool air will flow from the indoor unit during the replacement operation.
• During the replacement operation, is displayed on the remote controller and LED1 (green) and LED2 (red) on the
control board of the outdoor unit flash together.
3Replacement operation requires at least two hours to complete.
• After setting switch SW8-2 to ON, the unit automatically stops after two hours.
• Replacement operation can be performed repeatedly by setting switch SW8-2 from OFF to ON. Make sure to perform the
operation more than 2 hours. (If the operation is performed less than 2 hours, the existing pipes cannot be cleaned
enough and the unit may be damaged.)
• If replacement operation is performed over 2 hours, this action is recorded into nonvolatile memory of control board.
4Set switch SW8-2 to OFF. (Replacement operation is completed.)
wThe unit can be operated normally by remote controller even if SW8-2 remains ON.
wIf the indoor temperature is less than 15:, the compressor will operate intermittently but the unit is not faulty.
3. Start and finish of test run
• Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
1Set the operation mode (cooling/heating) using SW4-2.
2Turn on SW4-1 to start test run with the operation mode set by SW4-2.
3Turn off SW4-1 to finish the test run.
• There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion pipe is just moving to adjust opening pulse.
• There may be a knocking sound around the machine room for several seconds after compressor
starts operating, but this is no problem with product because the check valve, itself, generates the
sound because pressure difference is small in the refrigerant circuit.
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
24
11TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is
reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according
to “11-4. Self-diagnosis action table”.
Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “11-5. Troubleshooting
by inferior phenomena”.
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, matters related to wiring
and etc.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
1Re-check the abnormal symptom.
2Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “11-5. Troubleshooting
by inferior phenomena”.
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
11-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.
Actions to be taken for service, which depends on whether or not the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
25
11-2. Check point under test run
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
TEST RUN button
TEST RUN display
LIQUID PIPE TEMPERATURE display
(MA remote controller)
(1) Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Merger and
check that it is 1.0M" or over.
wDon’t use 500V Merger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Make sure that all of the SW5 switches for function changes on the control board of the outdoor unit are set to OFF. If all of
the SW5 switches are not set to OFF, record the settings and then set all of the switches to OFF. And perform emergency
operation. After finishing emergency operation, set the SW5 switches to the recorded settings.
• Turn on power supply twelve hours before test run in order to protect compressor.
• For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “Selection of Functions through Remote Controller”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
11-2-1. Test run by remote controller
Operating procedures
1. Turn on the main power supply.
2. Press TEST RUN button twice.
3. Press OPERATION SWITCH
button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for
correct running.
While the room temperature display on the remote
controller is “H0”, the remote controller is disabled.
Wait until “H0” disappears before using remote controller.
“H0” appears for about 2 minutes after power supply is
turned on. w1
The TEST RUN appears on the screen.
Cooling mode:
Heating mode: Check if warm air blows. (It takes a little
while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to
provide optimum fan speeds. Therefore, the fan keeps
running at a low speed to meet the current outside air
condition unless it exceeds its available maximum power.
Then, in actuality, the fan may stop or run in the reverse
direction depending on the outside air, but this does not
mean malfunction.
Check if cool air blows and water is drained.
6. Press the ON/OFF button to reset the test run in progress.
7. Turn off the main power supply.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after two hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin and triple operation. Malfunctions may not
be displayed regardless of incorrect wiring.
w1 After turning on the power supply, the system will go into startup mode, “H0” will blink on the display section of the room
temperature, and lamp(red) of the remote controller will flash.
As to INDOOR BOARD LED, LED1 and LED2 will be lit up in case the address is 0, or turned off in case the address is not
0. LED3 will blink.
As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will light up. (After the startup mode of the system finishes,
LED2(red) will be turned off.)
In case OUTDOOR BOARD LED is digital display, — and —will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from
the symptoms.
The below symptoms are under test run mode. “startup” in the table means the display status of w1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “H0”, and
cannot be operated.
After power is turned on, “H0” is displayed
for 3 minutes, then error code is
displayed.
No display appears even when remote
controller operation switch is turned on.
(Operation lamp does not light up.)
Display appears but soon disappears
even when remote controller is operated.
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed,
green(once) and red(once) blink
alternately. <F1>
After “startup” is displayed,
green(once) and red(twice) blink
alternately. <F3, F4, F9>
After “startup” is displayed,
green(twice) and red(once) blink
alternately. <EA. Eb>
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed, only
green lights up. <00>
26
Cause
• After power is turned on, “H0” is displayed for 2 minutes during
system startup. (Normal)
• Incorrect connection of outdoor terminal block (L, N and S1,
S2, S3.)
• Outdoor unit’s safeguard installation connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity
is wrong for S1, S2, S3.)
• Remote controller transmission wire short.
• There is no outdoor unit of address 0.
(Address is other than 0.)
• Remote controller transmission wire burnout.
• After canceling function selection, operation is not possible for
about 30 seconds. (Normal)
wPress the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the
LCD
Contents of inferior phenomena
P1
P2
P4
P5
P6
P8
P9
Abnormality of room temperature thermistor
Abnormality of pipe temperature thermistor/Liquid
Abnormality of drain sensor
Drain overflow protection is working.
Freezing/overheating protection is working.
Abnormality of pipe temperature
Abnormality of pipe temperature thermistor/Cond./Eva
LCD
Contents of inferior phenomena
U1~UP
F3~F9
E0~E5
E6~EF
----
FFFF
Malfunction outdoor unit
Malfunction
outdoor unit
Remote controller transmitting error
Indoor/outdoor unit communication error
No error history
No applied unit
LED1
(microcomputer power supply)
LED2
(remote controller)
LED3
(indoor/outdoor communication)
Lits when power is supplied.
Remote controller
The indoor unit should be connected to the outdoor unit with address “0” setting.
Flash when indoor and outdoor unit are communicating.
ON
SW4
12
A Stop
B Cooling
C Operation
D Heating
A
CD
B
(Factory setting)
contents of LCD display.
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
11-2-2. Test run by outdoor unit SW4
The setting of test run (ON/OFF) and its operation mode (cooling/heating) can be set by SW4 on the controller board of outdoor unit. Check that SW5-1 is set to OFF before performing test run. If SW5-1 is set to ON, turn it OFF and then perform test
run. After finishing test run, set SW5-1 back to ON.
1Set operation mode(cooling or heating) by SW4-2.
2Start test run by setting SW4-1 to ON ( ) with the indicated operation mode of SW4-2.
3Finish test run by setting SW4-1 to OFF ( ).
• Operation mode cannot be changed by SW4-2 during test run.
Stop test run to change operation mode by SW4-1, and restart test run by SW4-1 after
the mode is changed.
• Test run automatically stops 2 hours later by 2-hour OFF timer function.
• Test run can be performed by the remote controller.
• The remote controller display of test run by outdoor unit is the same as that of test run by
remote controller.
27
11-3. Malfunction-diagnosis method by remote controller
Mode number
Setting number
Refrigerant address
Unit number
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
E
G
CDH
F
I
A
B
J
1
2
a)
3(1)
c)
b)
d)
e)
11-3-1. Error history of unit
(1) Wired remote controller
<In case of trouble during operation>
If there is a trouble on air conditioner, both indoor unit and outdoor unit will stop and digital display shows what was wrong.
1 “CHECK” and refrigerant address are displayed at set tem-
perature display. Error code and unit number are displayed
at clock display alternately.
(If outdoor unit is malfunctioning, unit number is 00.)
2 The refrigerant address and error code initially sent from the
unit are displayed in case of group control system which
one remote controller controls plural refrigerant systems.
3 Press the “ON/OFF” button to cancel error code.
In case of central control by the controller of MELANS, cancel the error code by the controller of the MELANS, and in
case of distant-handy combined operation, cancel the error
code by cancelling distant operation.
<Malfunction-diagnosis method at maintenance service>
Digital control has memory function that memorizes latest error
code even if it is cancelled by remote controller or power is
shut off, so error histories can be searched by following the
procedure below.
Search error histories of each unit by remote controller.
1 Turn to self-diagnosis mode.
Press the H “CHECK” button twice within three seconds,
and following display appears.
a) Refrigerant address for self-diagnosis
2 Set refrigerant address number that you want to diagnose.
Press the F(temp.) button to set refrigerant address
to be diagnosed.
Refrigerant address has number from 00 to 15.
Three seconds after setting, lighted self-diagnosed refrigerant address begins blinking and self-diagnosis process
begins.
3 Self-diagnosis result display
(1) When there is an error history.
(Refer to 11-4. for details of error code contents.)
b) Alternating display
c) Error code
d) Attribute of error search
e) Unit number
(2) When there is no error history.
(3) When the address does not exist.
28
4 To cancel self-diagnosis
(2)
(3)
5 (1)
b)
(2)
(3)
There are following two methods to cancel self-diagnosis:
Press the H “CHECK” button twice within three seconds.
➜Self-diagnosis is cancelled and the display screen will
return to the status before self-diagnosis.
Press the I “ON/OFF” button.
➜Self-diagnosis is cancelled and indoor unit will stop.
This operation is ineffectual when the operation of remote
controller is prohibited.
During self-diagnosis at maintenance service, all the indoor
units start performing fan operation except for the indoor
unit indicating the latest error. Then outdoor units of the
same refrigerant system also start performing fan operation
intermittently for 3 minutes. (The fan is on for 3 seconds
and then off for 5 seconds.)
The unit with error can be inspected by using this. In case
unit other than indoor unit, such as outdoor unit and controller of MELANS, has an error, all the indoor units of the
same refrigerant system stop fan operation and outdoor
units operate intermittently for 3 minutes.
5 To delete error code
When something is wrong with air conditioner, error code
(P1 etc.) is memorized, but error code can be deleted after
termination of service.
<To delete error cord with remote controller>
(1)Display the error cord at the self-diagnosis result display
screen.
b) Alternating display
(2)The address for self-diagnosis will blink when the D
w button is pressed twice within three seconds.
(3) The display (3) shown on the left will be appeared when
the error cord has been reset. Note that the error content
will be redisplayed if error cord resetting is unsuccessful.
<To delete error cord with switch of outdoor unit>
Refer to 11-10. Function of switches, connectors and
jumpers.
29
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK
display
Temperature
button
CHECK
button
Refrigerant
address
display
HOUR
button
ON/OFF
button
Inspected unit
Error code
P1
P2
P4
P5
P6
P8
P9
E4, E5
Beep output
beep O 1 time
beep O 2 times
beep O 4 times
beep O 5 times
beep O 6 times
beep O 8 times
beep O 2 times
Other than above
Operation LED
1 sec. O 1 time
1 sec.O 2 times
1 sec.O 4 times
1 sec.O 5 times
1 sec.O 6 times
1 sec.O 8 times
1 sec.O 2 times
Other than above
Indoor unit
Inspected unit
Check code
F1–F9
U0–UP
E6–EE
No check code
(normal)
Beep output
beep beep O 1 time
Other than above
No output
beep beep beep
Operation LED
(0.4sec+0.4sec)
O 1 time
Other than above
Lights off
Lights off
Outdoor
unit
No check code
(mistake of matching with refrigerant
address)
(2) Digital wireless remote controller
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and refrigerant
address "00" flashes.
• Check that the remote controller's
display has stopped before continuing.
2. Press the temperature
buttons.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermittent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
4. Point the remote controller at the
• The check mode is cancelled.
sensor on the indoor unit and
press the ON/OFF button.
✽ Malfunction diagnosis can be performed only for refrigerant system control-
ling wireless units.
30
11-3-2. Wired Remote controller Diagnosis
1
a)
2
3(1)
(2)
(3)
(4)
b)
If operation can not be carried out from remote controller, try
remote controller diagnosis with following process.
1 First, check the electricity current marker.
When correct voltage (DC12V) is not supplied to remote
controller, the electricity current marker is put out.
If the electricity current marker is not lighted, check the
remote controller wiring and the indoor units.
a) Electric current marker
2 Transfer to remote controller diagnosis mode
Hold down the H “CHECK” button for five seconds or more,
and following display appears.
Press the A “FILTER” button, and remote controller diagnosis will begin.
3 Remote controller diagnosis result
(1) When the remote controller is functioning correctly
Check other possible causes, as there is no problem
with remote controller.
Consider the unit is normal when remote controller transmits the result of diagnosis to indoor or outdoor unit and
receives the same data back.
(2) When remote controller has malfunction
The remote controller must be replaced.
If the transmitting-receiving circuit is defective, [‘NG’]
blinks.
"NG" will be displayed when remote controller transmits
the result of diagnosis to indoor or outdoor unit, and
receives no response.
When there might be other problems than diagnosed remote
controller,
(3) There might be noise on transmission path or damage of
other remote controllers or indoor units. Check the trans-
mission path and other controllers.
If the transmission is not possible, [E3] blinks.
"E3" will be displayed when remote controller transmits
the result of diagnosis to indoor or outdoor unit and
receives different data back.
(4) The number of data errors means the difference
between the number of bits sent from remote controller
and the actual number of bits sent to transmission path.
If the data error is displayed, noise and etc. are interfer-
ing with the transmission data. Check the transmission
path.
If the data error has occurred, [ERC] and number of data
errors are displayed.
b) Number of generated data errors (maximum 66 errors)
When the number of data errors is 02.
Transmission data from remote controller
Transmission data on transmission path
4 Cancel the remote controller diagnosis
Hold down the H “CHECK” button for five seconds or more
to cancel remote controller diagnosis, then [H0] operation
lamp will blink and the display screen will return to the status before remote controller diagnosis in about 30 seconds.
31
11-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is put on>
Error Code
None
Meaning of error code and detection method
1 No voltage is supplied to terminal
2 Electric power is not charged
3 Electric power is not supplied to
—
4 Disconnection of reactor (DCL
5 Disconnection of outdoor noise
block(TB1) of outdoor unit.
a) Power supply breaker is put
b) Contact failure or discon-
c) Open phase (L or N phase)
to power supply terminal of
outdoor power circuit board.
a) Contact failure of power
b) Open phase on the outdoor
outdoor controller circuit board.
a) Disconnection of connector
or ACL)
filter circuit board or parts failure
in outdoor noise filter circuit
board
(Note 1) Refer to indoor unit section for code P and code E.
Case
off.
nection of power supply
terminal
supply terminal
power circuit board
RP3V :Disconnection of
connector R or S
RP4V~6V :Disconnection of
connector SC-R or SC-S
(CNDC)
1 Check following items.
a) Power supply breaker
b) Connection of power supply terminal block.
c) Connection of power supply terminal block.
2 Check following items.
a) Connection of power supply terminal block.
b) Connection of terminal on outdoor power
RP1.6-3V :Disconnection of connector R or S.
RP4V-6V :Disconnection of connector SC-R
3 Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector, LD1 and
LD2 for RP1.6-3V and CNDC for RP4-6V, on
the outdoor power circuit board.
Refer to page 48, 52 and 53.
.
4 Check connection of reactor. (DCL or ACL)
RP1.6-3V: Check connection of “LO” and
“NO” on the outdoor noise filter circuit board.
Check connection of “R” and “S” on the
outdoor power circuit board.
Refer to page 49, 50 and 52.
RP4-6V: Check connection of “L1” and “L2”
on the active filter module.(ACTM)
Judgment and action
(TB1)
(TB1)
(TB1)
circuit board.
Refer to page 52.
or SC-S. Refer to page 53.
F3
(5202)
F5
(5201)
F9
(4119)
63L connector open
Abnormal if 63L connector circuit is open
for three minutes continuously after power
supply.
63L: Low-pressure switch
<PUHZ-RP4~6VHA only>
63H connector open
Abnormal if 63H connector circuit is open
for three minutes continuously after power
supply.
63H: High-pressure switch
2 connector open
Abnormal if both 63H and 63L connector
circuits are open for three minutes continuously after power supply.
2 Check the 63L side of connecting wire.
3 Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
1 Check connection of 63H connector on
outdoor controller circuit board.
Refer to 11-9.
2 Check the 63H side of connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
1 Check connection of connector(63H,63L) on
outdoor controller circuit board.
Refer to 11-9.
2 Check the 63H and 63L side of connecting
wire.
3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
32
Error Code
EA
(6844)
Eb
(6845)
EC
(6846)
Meaning of error code and detection method
Indoor/outdoor unit connector
mis-wiring, excessive number of units
(4 units or more)
1. Outdoor controller circuit board can
automatically check the number of
connected indoor units. Abnormal if the
number cannot be checked automatically
due to mis-wiring of indoor/outdoor unit
connecting wire and etc. after power is
turned on for 4 minutes.
2. Abnormal if outdoor controller circuit
board recognizes the number of
connected indoor units as “4 units or
more”.
Mis-wiring of indoor/outdoor unit
connecting wire (converse wiring or
disconnection)
Outdoor controller circuit board can
automatically set the unit number of indoor
units.
Abnormal if the indoor unit number can
not be set within four minutes after power
on because of mis-wiring (converse wiring
or disconnection) of indoor/outdoor unit
connecting wire.
Start-up time over
The unit can not finish start-up process
within four minutes after power on.
1 Contact failure or mis-wiring of
2 Diameter or length of
3 4 or more indoor units are
4 Defective transmitting receiving
5 Defective transmitting receiving
6 Defective indoor power board
7 Two or more outdoor units
8 Noise has entered into power
1 Contact failure or mis-wiring of
2 Diameter or length of
4 Defective transmitting receiving
5 Defective transmitting receiving
6 Defective indoor power board.
7 Two or more outdoor units
8 Noise has entered into power
1 Contact failure of indoor/
2 Diameter or length of indoor/
7 Two or more outdoor units
8 Noise has entered into power
Case
indoor/outdoor unit connecting
wire
indoor/outdoor unit connecting
wire is out of specified capacity.
connected to one outdoor unit.
circuit of outdoor controller
circuit board
circuit of indoor controller
board
have refrigerant address “0” .
(In case of group control)
supply or indoor / outdoor unit
connecting wire.
indoor/outdoor unit connecting
wire
indoor/outdoor unit connecting
wire is out of specified capacity.
circuit of outdoor controller circuit
board.
circuit of indoor controller board
have refrigerant address “0” .
(In case of group control)
supply or indoor/outdoor unit
connecting wire.
outdoor unit connecting wire
outdoor unit connecting wire is
out of specified capacity.
have refrigerant address “0” .
(In case of group control)
supply or indoor/outdoor unit
connecting wire.
Judgment and action
1 Check disconnection or looseness or polarity
of indoor/outdoor unit connecting wire of
indoor and outdoor units.
2 Check diameter and length of indoor/outdoor
unit connecting wire.
Total wiring length: 80m
(including wiring connecting each indoor unit
and between indoor and outdoor unit)
Also check if the connection order of flat
cable is S1, S2, S3.
3 Check the number of indoor units that are
connected to one outdoor unit. (If EA is
detected)
4~6 Put the power off once, and on again to
check.
Replace outdoor controller circuit board,
indoor controller board or indoor power
board if abnormality occurs again.
7 Check if refrigerant addresses (SW1-3 to
SW1-6 on outdoor controller circuit board)
are overlapping in case of group control
system.
8 Check transmission path, and remove the
cause.
w The descriptions above, 1-8, are for EA, Eb
and EC.
33
<Abnormalities detected while unit is operating>
<Abnormalities detected while unit is operating>
Error Code
U1
(1302)
U2
(1102)
Meaning of error code and detection method
Abnormal high pressure (High-pressure
switch 63H worked)
Abnormal if high-pressure switch 63H
worked ( w ) during compressor operation.
w RP1.6-2VHA : 4.15 MPa
RP2.5-6VHA : 4.41 MPa
RP2.5-6VHA1 : 4.15 MPa
63H: High-pressure switch
Abnormal high discharging temperature
(1) Abnormal if discharge temperature
thermistor (TH4) exceeds 125: or
110: continuously for 5 minutes.
Abnormal if condenser/evaporator
temperature thermistor (TH5) exceeds
40: during defrosting and discharge
temperature thermistor (TH4) exceeds
110:.
(2) Abnormal if discharge super heat
(Cooling: TH4 – TH5 / Heating: TH4 –
TH6) increases.
All the conditions in Aor B are detected
simultaneously for 10 minutes
continuously after 6 minutes past from
compressor start-up (including the
thermostat indication or recovery from
defrosting).
<Condition A>
• Heating mode
• When discharge super heat is less
than 70 deg.
• When the TH6 temp is more than the
value obtained by TH7 – 5 deg.
• When the condensing temp of TH5 is
less than 35:.
Case
1 Short cycle of indoor unit
2 Clogged filter of indoor unit
3 Decreased airflow caused by
dirt of indoor fan
4 Dirt of indoor heat exchanger
5 Locked indoor fan motor
6 Malfunction of indoor fan motor
7 Defective operation of stop
valve (Not full open)
8 Clogged or broken pipe
9 Locked outdoor fan motor
0 Malfunction of outdoor fan
motor
1 Short cycle of outdoor unit
2 Dirt of outdoor heat exchanger
3 Decreased airflow caused by
defective inspection of outside
temperature thermistor
(It detects lower temperature
than actual temperature.)
7 Check if stop valve is full open.
8 Check piping and repair defectives.
9~2 Check outdoor unit and repair defectives.
3 Check the inspected temperature of outside
temperature thermistor on LED display.
(SW2 on A-Control Service Tool : Refer to
page 58.)
4~6Put the power off and check F5 is
displayed when the power is put again.
When F5 is displayed, refer to “Judgment
and action” for F5.
7 Check linear expansion valve.
Refer to 11-6.
8 Replace outdoor controller board.
1 Check intake super heat.
Check leakage of refrigerant.
Charge additional refrigerant.
2 Check if stop valve is full open.
34 Put the power off and check if U3 is dis-
played when the power is put again.
When U3 is displayed, refer to “Judgement
and action” for U3.
5 Check linear expansion valve.
Refer to 11-6.
<Condition B>
• During comp operation (Cooling and
Heating)
• When discharge super heat is less
than 80 deg in Cooling.
• When discharge super heat is less
than 90 deg in Heating.
• When condensing temp of TH6 is
more than –40:. (In Cooling only.)
34
Error Code
U3
(5104)
U4
(TH3:5105)
(TH6:5107)
(TH7:5106)
(TH8:5110)
U5
(4230)
U6
(4250)
U7
(1520)
Meaning of error code and detection method
Open/short circuit of discharge
temperature thermistor (TH4)
Abnormal if open (3: or less) or short
(217: or more) is detected during
compressor operation.
(Detection is inoperative for 10 minutes of
compressor starting process and for 10
minutes after and during defrosting.)
Open/short of outdoor unit thermistors
(TH3, TH6, TH7, and TH8)
Abnormal if open or short is detected
during compressor operation.
Open detection of thermistors TH3 and
TH6 is inoperative for 10 seconds to 10
minutes after compressor starting and 10
minutes after and during defrosting.
WCheck which unit has abnormality in its
thermistor by switching the mode of
SW2.
(Refer to page 63.)
Abnormal if heat sink thermistor(TH8)
detects temperature indicated below.
RP1.6V, 2VHA·······84:
RP2.5V, 3VHA·······77:
RP4-6VHA·············85:
Abnormality of power module
Check abnormality by driving power module
in case overcurrent is detected.
(UF or UP error condition)
Abnormality of super heat due to low
discharge temperature (RP3VHA)
Abnormal if discharge super heat is
continuously detected less than or equal
to 0: for 3 minutes even though linear
expansion valve has minimum open pulse
after compressor starts operating for 10
minutes.
(RP1.6-3VHA only)
Thermistor <Outdoor pipe>
Thermistor <Outdoor 2-phase pipe>
Thermistor <Outdoor>
Thermistor <Heat sink>
Name
1 The outdoor fan motor is
2 Failure of outdoor fan motor
3 Air flow path is clogged.
4 Rise of ambient temperature
5 Defective thermistor
6 Defective input circuit of
7 Failure of outdoor fan drive
1 Outdoor stop valve is closed.
2 Decrease of power supply voltage
3 Looseness, disconnection or
4 Defective compressor
5 Defective outdoor power circuit
1 Disconnection or loose
2 Defective holder of discharge
3 Disconnection or loose connection
4 Disconnection or loose
5 Defective linear expansion valve.
Case
failure of connector (TH4) on
the outdoor controller circuit
board.
circuit board
of connectors
Outdoor controller circuit
board: TH3,TH6/TH7
Outdoor power circuit board:
CN3
circuit board
Open detectionShort detection
– 40: or below
– 40: or below
– 40: or below
– 27: or below
locked.
outdoor power circuit board
circuit
converse of compressor wiring
connection
board
connection of discharge
temperature thermistor. (TH4)
temperature thermistor.
of linear expansion valve’s coil.
connection of linear expansion
valve’s connector.
Judgment and action
1 Check connection of connector (TH4) on the
outdoor controller circuit board.
Check breaking of the lead wire for
thermistor (TH4). Refer to 11-9.
2 Check resistance value of thermistor (TH4) or
temperature by microcomputer.
(Thermistor/TH4: Refer to 11-6.)
(SW2 on A-Control Service Tool: Refer to
page 58.)
on the outdoor controller circuit board.
Check connection of connector (CN3) on the
outdoor power circuit board.
Check breaking of the lead wire for thermistor
)
(TH3,TH6,TH7,TH8). Refer to page 48, 52 and 53.
2 Check resistance value of thermistor
(TH3,TH6,TH7,TH8) or check temperature by
microcomputer.
(Thermistor/TH3,TH6,TH7,TH8: Refer to page 43.)
(SW2 on A-Control Service Tool: Refer to
page 58.)
3 Replace outdoor controller circuit board.
WEmergency operation is available in case of
abnormalities of TH3, TH6 and TH7.
Refer to 11-8.
90: or above
90: or above
90: or above
102: or above
12 Check outdoor fan.
Refer to (9) in “12-2 Trouble shooting by
inferior phenomena ” on Service Technical
Guide for OCT04.
3 Check air flow path for cooling.
4 Check if there is something which causes
temperature rise around outdoor unit.
(Upper limit of ambient temperature is 46:.)
Turn off power, and on again to check if U5
is displayed within 30 minutes.
If U4 is displayed instead of U5, follow the
action to be taken for U4.
5 Check resistance value of thermistor (TH8)
or temperature by microcomputer.
(Thermistor/TH8: Refer to 11-6.)
(SW2 on A-Control Service Tool: Refer to
page 58.)
controller circuit board, disconnect the wiring
to compressor from the outdoor power circuit
board and check the output voltage among
phases, U, V, W, during test run. No defect
on board if voltage among phases (U-V, V-W
and W-U) is same. Make sure to perform the
voltage check with same performing frequency.
36
Error Code
E0
(No display)
E3
(No display)
E8
(6840)
E9
(6841)
EF
(6607
or
6608)
Ed
(0403)
Meaning of error code and detection method
Remote controller communication error
(Signal receiving error)
(1) Abnormal if any signal from IC of refrig-
erant address “0” could not be normally
received for three minutes.
(2) Abnormal if sub remote controller could
not receive any signal for two minutes.
Remote controller communication error
(Transmitting error)
(1) Abnormal if sub remote controller could
not find blank of transmission path for
six seconds.
(2) Abnormal if remote controller could not
finish transmitting 30 times continuously.
Indoor/outdoor unit communication
error (Signal receiving error)
(Outdoor unit)
(1) Abnormal if outdoor controller circuit
board could not receive anything
normally for three minutes.
Indoor/outdoor unit communication
error (Transmitting error) (Outdoor unit)
(1) Abnormal if “0” receiving is detected 30
times continuously though outdoor controller circuit board has transmitted “1”.
(2) Abnormal if outdoor controller circuit
board could not find blank of transmission
path for three minutes.
Non defined error code
This code is displayed when non defined
error code is received.
Serial communication error
1.Abnormal if serial communication
between outdoor controller circuit
board and outdoor power circuit board
is defective.
2. Abnormal if communication between
outdoor controller circuit board and
M-NET board is not available.
1 Defective communication cir-
2 Defective communication cir-
3 Noise has entered into trans-
4 All remote controllers are set
1 Defective communication cir-
2 Noise has entered into trans-
3 Two remote controllers are set
1 Contact failure of indoor/out-
2 Defective communication circuit
3 Defective communication cir-
4 Noise has entered into indoor/
1 Indoor/ outdoor unit connecting
2 Defective communication circuit
3 Noise has entered power supply.
4 Noise has entered indoor/ out-
1 Noise has entered transmis-
2 Noise has entered indoor/ out-
3 Outdoor unit is not a series of
4 Model name of remote con-
1 Breaking of wire or contact
2 Breaking of wire or contact
3 Defective communication circuit
4 Defective communication circuit
1 Breaking of wire or contact
2 Contact failure of M-NET board
3 Noise has entered into M-NET
Case
cuit of remote controller
cuit of indoor controller board
of refrigerant address “0”
mission line of remote con-
troller.
as “sub” remote controller. In
this case, E4 is displayed at
outdoor LED, and E0 is displayed at remote controller.
cuit of remote controller
mission line of remote con-
troller.
as "main."
(In case of 2 remote controllers)
door unit connecting wire.
of outdoor controller circuit board.
cuit of indoor controller board
outdoor unit connecting wire.
wire has contact failure.
of outdoor controller circuit board.
door unit connecting wire.
sion wire of remote controller.
door unit connecting wire.
power-inverter.
troller is PAR-S25A.
failure of connector CN2
between the outdoor controller
circuit board and the outdoor
power circuit board.
failure of connector CN4
between the outdoor controller
circuit board and the outdoor
power circuit board.
of outdoor power circuit board
of outdoor controller circuit board
for outdoor power circuit board
failure of connector between
outdoor controller circuit board
and M-NET board
power supply line
transmission wire.
Judgment and action
1~3 Diagnose remote controller.
Take actions as follows according to
diagnosis result.
a) When “RC OK” is displayed,
remote controllers have no problem.
Put the power off, and on again to
check. If, “H0” is displayed for four
minutes or more, replace indoor controller board.
b) When “RC NG” is displayed,
replace remote controller.
c) When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
4 Set a remote controller to main, and the
other to sub.
w The descriptions above, 1-3, are for E0 and
E3.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor or outdoor units.
2~4 Put the power off, and on again to check.
Replace indoor controller board or outdoor
controller circuit board if abnormality is
displayed again.
1 Check disconnection or looseness of
indoor/outdoor unit connecting wire.
2~4 Put the power off, and on again to check.
Replace outdoor controller circuit board if
abnormality is displayed again.
12 Put the power off, and on again to check.
Replace indoor controller board or outdoor
controller circuit board if abnormality is
displayed again.
3 Replace outdoor unit with power-inverter type
outdoor unit.
4 Replace remote controller with MA remote
controller.
12 Check connection of each connector CN2
and CN4 between the outdoor controller
circuit board and the outdoor power circuit
board.
connection wire between outdoor controller circuit board (CNMNT) and M-NET board (CN5).
2 Check disconnection, looseness, or breaking of
connection wire between outdoor controller circuit board(CNMNT) and M-NET board (CND).
3 Refer to (4) in “ 2-2. M-NET Wiring method ”
on Service Technical Guide for OCT04.
37
Error Code
123456
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
ON
OFF
A-Control Service Tool SW2 setting
Temperature display of indoor liquid pipe
Indoor 1
Temperature display of indoor liquid pipe
Indoor 2
Temperature display of indoor condenser/
evaporator pipe Indoor 1
Temperature display of indoor condenser/
evaporator pipe Indoor 2
P8
Meaning of error code and detection method
Abnormality of pipe temperature
1 Slight temperature difference
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes later of compressor start and 6 minutes later of the liquid or condenser/evaporator pipe is out of cooling range.
Note 1) It takes at least 9 min. to detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : Indoor pipe temperature
2 Converse connection of
(TH2 or TH5) – intake temperature
(TH1) [ -3 deg
TH: Lower temperature between: liquid
3 Converse wiring of indoor/
pipe temperature and condenser/
evaporator temperature
4 Defective detection of indoor
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
5 Stop valve is not opened
detected as abnormal when
condenser/evaporator pipe temperature is
not in heating range within 20 minutes.
between indoor room
temperature and pipe <liquid
or condenser / evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
extension pipe (on plural units
connection)
outdoor unit connecting wire
(on plural units connection)
room temperature and pipe
<condenser / evaporator>
temperature thermistor
completely.
Judgment and action
1~4 Check pipe <liquid or condenser /
evaporator> temperature with room
temperature display on remote
controller and outdoor controller circuit
board.
Pipe <liquid or condenser / evaporator>
temperature display is indicated by
setting SW2 of outdoor controller circuit
board as follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
<M-NET communication error>
Error Code
A0
(6600)
A2
(6602)
A3
(6603)
Meaning of error code and detection method
Address duplicate definition
This error is displayed when transmission
from the units of same address is detected.
Note) The address and attribute displayed
Hard ware error of transmission
processor
Transmission processor intended to transmit “0”, but “1” appeared on transmission
wire.
Note) The address and attribute display at
BUS BUSY
1. Over error by collision damage
Abnormal if transmitting is not possible
for 8-10 minutes continuously because
of collision of transmission.
2. Data could not reach transmission wire
for 8-10 minutes continuously because
of noise or etc.
Note) The address and attribute displayed
at remote controller indicate the controller that detected abnormality.
remote controller indicate the controller that detected abnormality.
at remote controller indicate the controller that detected abnormality.
(Note) “Indoor unit” in the text indicates M-NET board in outdoor unit.
CaseJudgment and action
1 There are two or more same
address of controller of outdoor unit, indoor unit, FRESH
MASTER, or LOSSNAY.
2 Noise has entered into trans-
mission signal and signal was
transformed.
1
Error is detected if wave form is
transformed when wiring works of
transmission wire of outdoor unit,
indoor unit, FRESH MASTER or
LOSSNAYare done, or polarity is
changed with the power on and
transmission data collide each other.
2 Defective transmitting receiving
circuit of transmission processor
Search the unit with same address as abnormality
occurred. If the same address is found, shut of the
power supply of outdoor unit and indoor unit and
FRESH MASTER or LOSSNAY at the same time
for two minutes or more after the address is corrected, and put the power on again.
Check transmission wave form or noise on transmission wire.
1 If the works of transmission wire is done with
the power on, shut off the power supply of
outdoor unit and indoor unit and FRESH
MASTER or LOSSNAY at the same time for
two minutes or more, and put the power on
again.
2 Check transmission wave form or noise on
transmission wire.
3 Transmission data is changed by
the noise on transmission.
Transmission processor could
1
not transmit because short cycle
voltage of noise and the like
have entered into transmission
wire continuously.
2 Transmission quantity has
increased and transmission is
not possible because there was
wiring mistake of terminal block
for transmission wire (TB3) and
terminal block for central control
(TB7) in outdoor unit.
3 Transmission are mixed with
others and occupation rate on
transmission wire rose because
of defective repeater (a function
to connector or disconnect transmission of control and central
control system) of outdoor unit,
then abnormality is detected.
1 Check if transmission wire of indoor unit,
FRESH MASTER, LOSSNAY, or remote controller is not connected to terminal block for
central control (TB7) of outdoor unit.
2 Check if transmission wore of indoor unit,
FRESH MASTER or LOSSNAY is not connected to terminal block for transmission
wire of outdoor unit.
3 Check if terminal block for transmission wire
(TB3) and terminal block for central control
(TB7) is not connected.
4 Check transmission wave form or noise on
transmission wire.
38
Error Code
A6
(6606)
Meaning of error code and detection method
Communication error with communica-
tion processor
Defective communication between unit
processor and transmission processor
Note) The address and attribute display at
remote controller indicate the controller that detected abnormality.
1 Data of transmission proces-
2 Address forwarding from unit
CaseJudgment and action
sor or unit processor is not
transmitted normally because
of accidental trouble such as
noise or thunder surge.
processor is not transmitted
normally because of defective
transmission processor hardware.
Shut of the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSSNAY
at the same time for two minutes or more, and
put the power on again. System returns normally if abnormality was accidental malfunction.
If the same abnormality generates again,
abnormality-generated controller may be defective.
A7
(6607)
NO ACK signal
1. Transmitting side controller detects
abnormal if a massage was transmitted
but there is no reply (ACK) that a massage was received. Transmitting side
detects abnormality every 30 seconds,
six times continuously.
Note) The address and attribute displayed
at remote controller is indicate the
controller that did not reply (ACK).
2. If displayed address or attribute is outdoor unit,
Indoor unit detects abnormality when
indoor unit transmitted to outdoor unit
and there was no reply (ACK).
3. If displayed address or attribute is
indoor unit,
Remote controller detects abnormality
when remote controller transmitted to
indoor unit and there was no reply
(ACK).
Common factor that has no relation with abnormality source.
1 The unit of former address
does not exist as address
switch has changed while the
unit was energized.
2 Extinction of transmission wire
voltage and signal is caused by
over-range transmission wire.
• Maximum distance ······200m
•
Remote controller line
3 Extinction of transmission wire
voltage and signal is caused by
type-unmatched transmission
wire.
Type······
With shield wire-
CVVS, CPEVS
With normal wire (no shield)-
VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter····1.25mm2or more
4 Extinction of transmission wire
voltage and signal is caused
by over-numbered units.
indoor unit of multi- refrigerant
system, if remote controller
transmit to indoor unit while
outdoor unit power supply of
one refrigerant system is put
off or within two minutes of
restart, abnormality is detected.
2 Contact failure of transmission
wire of remote controller or
indoor unit
3 Disconnection of transmission
connector (CN2M) of indoor unit
4 Defective transmitting receiv-
ing circuit of indoor unit or
remote controller
··(12m)
Always try the followings when the error
“A7” occurs.
1 Shut off the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or
more, and put the power on again. If malfunction was accidental, the unit returns to
normal.
2 Check address switch of abnormality-gener-
ated address.
3 Check disconnection or looseness of abnor-
mality-generated or abnormality-detected
transmission wire (terminal block and connector)
4 Check if tolerance range of transmission wire
is not exceeded.
5 Check if type of transmission wire is correct
or not.
If there were some trouble of 1-5 above,
repair the defective, then shut off the power
supply of outdoor unit and indoor unit and
FRESH MASTER or LOSSNAY at the same
time for two minutes or more, and put the
power on again.
• If there was no trouble with 1-5 above in single refrigerant system (one outdoor unit), controller of displayed address or attribute is
defective.
• If there was no trouble with 1-5 above in different refrigerant system (two or more outdoor
units), judge with 6.
6 If address of abnormality source is the
address that should not exist, there is the
unit that memorizes nonexistent address
information. Delete useless address information with manual setting function of remote
controller.
Only the system FRESH MASTER or LOSSNAY are connected to, or the system that is
equipped with group setting of different
refrigerant system.
If there was no trouble with 1-6 above,
replace the controller board of displayed
address or attribute.
If the unit does not return normally, multi-controller board of outdoor unit may be defective
(repeater circuit).
Replace multi-controller board one by one to
check if the unit returns normally.
39
Continued to the next page.
From the previous page.
Error Code
Meaning of error code and detection method
4. If displayed address or attribute is
remote controller,
Indoor unit detects abnormality when
indoor unit transmitted to remote controller and there was no reply (ACK).
CaseJudgment and action
1 During group operation with
indoor unit of multi- refrigerant
system, if indoor unit transmit
to remote controller while outdoor unit power supply of one
refrigerant system is put off or
within two minutes of restart,
abnormality is detected.
2 Contact failure of transmission
wire of remote controller or
indoor unit
3 Disconnection of transmission
connector (CN2M) of indoor
unit
4 Defective transmitting receiv-
ing circuit of indoor unit or
remote controller
Same as mentioned in “A7” of the previous
page.
A7
(6607)
5. If displayed address or attribute is
FRESH MASTER,
Indoor unit detects abnormality when
indoor unit transmitted to FRESH MASTER and there was no reply (ACK).
6. If displayed address or attribute is
LOSSNAY,
Indoor unit detects abnormality when
indoor unit transmitted to LOSSNAY and
there was no reply (ACK).
1 During sequential operation of
indoor unit and FRESH MASTER of other refrigerant system, if indoor unit transmits to
FRESH MASTER while outdoor unit power supply of
same refrigerant system with
FRESH MASTER is put off or
within two minutes of restart,
abnormality is detected.
2 Contact failure of transmission
wire of indoor unit or FRESH
MASTER
3 Disconnection of transmission
connector (CN2M) of indoor
unit or FRESH MASTER
4 Defective transmitting receiv-
ing circuit of indoor unit or
FRESH MASTER
1 If the power supply of LOSS-
NAY is off, indoor unit detects
abnormality when it transmits
to LOSSNAY.
2 During sequential operation of
indoor unit and LOSSNAY of
other refrigerant system, if
indoor unit transmits to LOSSNAY while outdoor unit power
supply of same refrigerant system with LOSSNAY is put off
or within two minutes of
restart, abnormality is detected.
3 Contact failure of transmission
wire of indoor unit of LOSSNAY
4 Disconnection of transmission
connector (CN2M) of indoor
unit
5 Defective transmitting receiv-
ing circuit of indoor unit or
LOSSNAY
7. If displayed address or attribute is
nonexistent,
1 The unit of former address
does not exist as address
switch has changed while the
unit was energized.
2 Abnormality is detected when
indoor unit transmitted
because the address of
FRESH MASTER and LOSSNAY are changed after
sequential operation of
FRESH MASTER and LOSSNAY by remote controller.
40
Error Code
A8
(6608)
Meaning of error code and detection method
M-NET•NO RESPONSE
Abnormal if a massage was transmitted
and there were reply (ACK) that massage
was received, but response command
does not return. Transmitting side detects
abnormality every 30 seconds, six times
continuously.
Note) The address and attribute displayed
at remote controller is indicate the
controller that did not reply (ACK).
1 Transmitting condition is
2 Extension of transmission wire
3 Extension of transmission wire
4 Accidental malfunction of
CaseJudgment and action
repeated fault because of
noise and the like.
voltage and signal is caused
by over-range transmission
wire.
• Maximum distance ······200m
Remote controller line
•
voltage and signal is caused
by type-unmatched transmission wire.
Type······
With shield wire-
CVVS, CPEVS
With normal wire (no shield)-
VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter····1.25mm2or more
abnormality-generated
controller
··(12m)
1 Check transmission wave form or noise on
transmission wire.
2 Shut off the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or
more, and put the power on again. If malfunction was accidental, the unit returns to
normal. If the same abnormality generates
again, controller of displayed address and
attribute may be defective.
11-5. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
1. Remote controller display does not
work.
2. “H0” display is remained on the
remote controller.
1DC12V is not supplied to remote controller.
(Power supply display is not indicated on LCD.)
2DC12~15V is supplied to remote controller, however,
no display is indicated.
• “H0” is not displayed.
• “H0” is displayed.
1At longest 2 minutes after the power supply “H0” is
displayed to start up.
2Communication error between the remote controller
and indoor unit
3Communication error between the indoor and outdoor
unit
4Outdoor unit protection device connector is open.
FactorCountermeasure
1Check LED2 on indoor controller board.
(1) When LED2 is lit.
Check the remote controller wiring for
breaking or contact failure.
(2) When LED2 is blinking.
Check short circuit of remote controller
wiring.
(3) When LED2 is not lit.
Refer to No.3 below.
2Check the following.
• Failure of remote controller if “H0” is not
displayed
• Refer to No.2 below if “H0” is displayed.
1Normal operation
2Self-diagnosis of remote controller
3“H0” is displayed for 6 minutes at most. in
case of indoor/outdoor unit communica-
tion error. Check LED3 on indoor controller board.
(1)When LED3 is not blinking.
Check indoor/outdoor connecting wire
for mis-wiring.
(Converse wiring of S1 and S2, or
break of S3 wiring.)
(2)When LED3 is blinking.
Indoor/outdoor connecting wire is normal.
4Check LED display on outdoor controller
circuit board. Refer to page 56 and 57.
Check protection device connector (63L
and 63H) for contact failure.
Refer to 11-9.
3. When pressing the remote controller
operation switch the OPERATION
display is appeared but it will be
turned off soon.
1After cancelling to select function from the remote
controller, the remote controller operation switch will
be not accepted for approx. 30 seconds.
41
1Normal operation
Phenomena
4. Even controlling by the wireless
remote controller no beep is heard
and the unit does not start operating. Operation display is indicated
on wireless remote controller.
5. When operating by the wireless
remote controller, beep sound is
heard, however, unit does not start
operating.
6. Remote controller display works
normally and the unit performs
cooling operation, however, the
capacity cannot be fully obtained.
(The air does not cool well.)
7. Remote controller display works normally and the unit performs heating
operation, however, the capacity
cannot be fully obtained.
Factor
1The pair number settings of the wireless remote
controller and indoor controller board are mismatched.
1No operation for 2 minutes at most after the power
supply ON.
2Hand-held remote controller operation is prohibited.
• Remote controlling adaptor is connected to CN32
on the indoor controller board.
• Hand-held remote controller operation is prohibited
by centralised controller etc. since it is connected to
MELANS.
3Factor of No.2 above.
1Refrigerant shortage
2Filter clogging
3Heat exchanger clogging
4Air duct short cycle
1Linear expansion valve fault
Opening cannot be adjusted well due to linear expansion valve fault.
2Refrigerant shortage
3Lack of insulation for refrigerant piping
4Filter clogging
5Heat exchanger clogging
6Air duct short cycle
7Bypass circuit of outdoor unit fault
Countermeasure
1Check the pair number settings.
1Normal operation
2Normal operation
3Check the details of No.2 above.
1• If refrigerant leaks, discharging tempera-
ture rises and LEV opening increases.
Inspect leakage by checking the tem-
perature and opening.
• Check pipe connections for gas leakage.
2Open suction grill and check the filter.
Clean the filter by removing dirt or dust on
it.
3• If the filter is clogged, indoor pipe tem-
perature rises and discharging pressure
increases. Check if heat exchanger is
clogged by inspecting discharging pres
sure.
• Clean the heat exchanger.
4Remove the shield.
1• Discharging temperature and indoor
heat exchanger temperature does not
rise.
Inspect the failure by checking discharging pressure.
• Replace linear expansion valve.
2• If refrigerant leaks, discharging tempera
ture rises and LEV opening increases.
Inspect leakage by checking the temperature and opening.
• Check pipe connections for gas leakage.
3Check the insulation.
4Open suction grill and check the filter.
Clean the filter by removing dirt or dust on
it.
5• If the filter is clogged, indoor pipe tem-
perature rises and discharging pressure
increases. Check if heat exchanger is
clogged by inspecting discharging pressure.
• Clean the heat exchanger.
6Remove the shield.
7Check refrigerant system during operation.
8. 1For 3 minutes after temperature
adjuster turns off, the compressor
will not start operating even if
temperature adjuster is turned on.
2For 3 minutes after temperature
adjuster turns on, the compressor
will not stop operating even if
temperature adjuster is turned off.
(Compressor stops operating
immediately when turning off by
the remote controller.)
12Normal operation
(For protection of compressor)
12Normal operation
42
11-6. HOW TO CHECK THE PARTS
4
6
2
3
1
2
3
4
5
6
5
1
M
Blue
Brown
Yellow
Orange
Red
White
Parts name
Check points
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10:~30:)
Disconnect the connector then measure the resistance using a tester.
(
Winding temperature 20
:)
Thermistor (TH3)
<Outdoor pipe>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Outdoor>
Thermistor (TH8)
<Heat sink>
Normal
160k"~410k"
4.3k"~9.6k"
39k"~105k"
TH4
TH3
TH6
TH7
TH8
Abnormal
Open or short
Normal
(1) - (6)
Red - White
(1) - (4)
Red - Orange
(2) - (5)
Brown - Yellow
(2) - (3)
Brown - Blue
Abnormal
46±4"
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20
:
)
Solenoid valve coil
<Four-way valve>
(21S4)
Pin number of relay
connector is different
from that motor
connector
Motor for compressor
(MC)
Linear expansion valve
( LEV(A),LEV(B) )
Normal
Abnormal
Open or short
RP1.6-3VRP4-6V
Open or short
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20
:
)
Normal
1197±10"
Abnormal
Open or short
Solenoid valve coil
<Bypass valve>
(SV)
RP2.5-6VHA only
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
Fan motor(MF1,MF2)
Normal
RP1.6V, 2V
66.5±3.3"
RP2.5-6V
15.1±0.5"
2350±170"1370±100"
RP1.6V, 2VRP4-6V
0.300"~0.340"
RP2.5V, 3V
0.865"~0.895"0.266"
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
(1) Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the outdoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
❈ 1. When linear expansion valve operation stops, all output phase
become OFF.
❈ When the switch is turned on, 700 pulse closing valve signal will
be sent till it goes to
A point in order to define the valve position.
(The pulse signal is being sent for about 20 seconds.)
When the valve moves smoothly, there is no noise or vibration
occurring from the linear expansion valve : however, when the
pulse number moves from B to A or when the valve is locked,
more noise can be heard than normal situation.
No noise is heard when the pulse number moves from B to A in
case coil is burn out or motor is locked by open-phase.
❈ Noise can be detected by placing the ear against the screw dri-
ver handle while putting the screw driver to the linear expansion
valve.
45
(3) How to attach and detach the coil of linear expansion valve
<Composition>
Linear expansion valve is separable into the main body and the coil as shown in the diagram below.
Coil
Lead wire
<How to detach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and detach the coil by pulling it
upward.
Be sure to detach the coil holding main body firmly. Otherwise
pipes can bend due to pressure.
Stopper
Main body
<How to attach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and attach the coil by inserting it
downward into the main body. Then securely attach the coil stopper to pipe B. (At this time, be careful that stress is not added to
lead wire and main body is not wound by lead wire.) If the stopper is not firmly attached to pipe B, coil may be detached from
the main body and that can cause defective operation of linear
expansion valve.
To prevent piping stress, be sure to attach the coil holding the
main body of linear expansion valve firmly. Otherwise pipe may
break.
B
A
A
Be sure to attach the
stopper to pipe B.
46
11-8. EMERGENCY OPERATION
SW4
12Cooling
Heating
ON
ON
OFF
CN31
Shorting pins
SW4
12Cooling
Heating
ON
Inspected content
Open/short of pipe thermistor (TH3/TH6)
Indoor/outdoor unit communication error •Signal receiving error (Outdoor unit)
Indoor/outdoor unit communication error •Transmitting error (Indoor unit)
Communication error other than outdoor unit
Communicaiton error between outdoor controller board and M-NET board (Serial communication error)
Error code
U4
E8
E9
E0 ~ E7
Ed
●When following abnormalities occur, emergency operation will be available.
(1) When the error codes shown below are displayed on outdoor unit or microcomputer for wired remote controller or indoor
unit has a failure, but no other problems are found, emergency operation will be available by setting the emergency operation switch (SWE) to ON and short-circuiting the connector (CN31) on outdoor controller board.
(2) Check the following items and cautions for emergency operation
1Make sure that there is no abnormality in outdoor unit other than the above abnormalities. (Emergency operation will
not be available when error code other than the above are indicated.)
2For emergency operation, it is necessary to set the emergency operation switch (SWE) on indoor controller board. Refer
to the electrical wiring diagram of indoor unit for how to set the indoor unit.)
3During emergency operation, the air-conditioner will continuously be operated by supplying power and stopping it: It can
not be turned on or off by remote control, and temperature control is not possible.
4Do not perform emergency heating operation for an extended period of time: If the outdoor unit starts defrosting during
this period, cold air will blow out from the indoor unit.
5Do not perform emergency cooling operation for more than 10 hours: Neglecting this could result in freezing the heat
exchanger in indoor unit.
(3) Emergency operation procedure
1Turn the main power supply off.
2Turn on the emergency operation switch (SWE) on indoor controller board.
3Set the shorting pins of emergency operation connector (CN31) on outdoor controller board to ON.
4Use SW4-2 on outdoor controller board to set the operation mode (cooling or heating). (SW4-1 is not used.)
5Turning the main power supply on will start the emergency operation.
(4) Releasing emergency operation
1Turn the main power supply off.
2Set the emergency operation switch (SWE) on indoor controller board to OFF.
3Set the shorting pins of emergency operation connector (CN31) on outdoor controller
board to OFF.
4Set SW4-2 on outdoor controller board as shown in the right.
wIf shorting pins are not set on emergency operation connector (CN31), the setting remains OFF.
47
11-9. TEST POINT DIAGRAM
Outdoor controller circuit board
Communication
power supply
ZD71 Voltage
developed across:
16-30V DC
+
FAN11•FAN21
(FAN21 is only for RP4-6VHA.)
Connect to fan motor (MF).
FAN12•FAN22
(FAN22 is only for RP4-6VHA.)
Connect to fan motor (MF)
(Detection of position)
1 to 5
2 to 5
3 to 5
5V DC pulse
(Detected while the
}
motor is rotating.)
1 to 4 : +
[
5 : –
]
CNS
(Indoor/outdoor unit
connecting wire)
CN2
Connect to the outdoor
power circuit board (CN2)
1-5:
Power circuit board
Transmitting signal to
the controller circuit board
(0-5V DC)
2-5: Zero cross signal
(0-5V DC)
3-4: Not used
(RP1.6-3VHA)
18V DC (RP4-6VHA)
6-5: 15V DC
7-5: 15V DC
[5: – 1,2,6,7: + ]
[4: – 3: + ]
CNAC
1 to 3: Power supply
for outdoor controller
circuit board
(220V-240V AC)
5 to 7: Power supply
for indoor/outdoor unit
connection wire
(220V-240V AC)
21S4
Four-way valve
63H
High pressure switch
63L
Low pressure switch
Only for RP4-6VHA
52C
52C relay
Only for RP4-6VHA
SV2
RP2.5-3:Bypass valve
RP4-6:Replace valve
Test point for
voltage check
(Between 1 to 3
220-240V AC)
–
➔
CN4
Transmission
to outdoor
power circuit
board (CN4)
CN52C
52C relay
(Connect to the
outdoor noise
filter circuit board
(CN52C))
Only for RP1.6-3VHA
LED1, LED2
Operating inspection
indicators
LED3: Short-circuited
(with jumper wire mounted)
LED4: Not used
(nothing mounted)
48
SWP
Pump down
CN31
Emergency
operation
CNDC
300-380V DC
+
Connect from
}
outdoor power
–
circuit board
(LD1-LD2)
LEV-A, LEV-B
Linear expansion
valve
TH6
Thermistor
<Outdoor 2-phase pipe>
TH7
Thermistor<Outdoor>
TH3
Thermistor
<Outdoor pipe>
TH4
Thermistor
<Discharge>
CNDM
1 to 2: Input of silent mode
1 to 3: Input of external
contact point
CNVMNT
Connected to outdoor
M-NET board
CNM
A-control service
inspection kit
CNMNT
Connected to outdoor
M-NET board
Control power
+
supply voltage
}
–
5V DC:
4.75-5.25V DC
SW6(J1~J6)
Model setup
SW1
Forced defrost,
detect history
record reset,
refrigerant address
LO, NO
Voltage of 220-240V AC is output
(Connect to the outdoor power
circuit board (SC-R, SC-S))
CNAC1, CNAC2
220-240V AC
(Connect to the
outdoor controller
circuit board
(CNAC))
EI
Connect to
the earth
CN5
Primary current
(Connect to the
outdoor power
circuit board
(CN5))
LI, NI
Voltage of 220-240V AC is input
(Connect to the terminal block(TB1))
51
Outdoor Power circuit board
PUHZ-RP1.6VHA
PUHZ-RP2VHA
PUHZ-RP2.5VHA
PUHZ-RP2.5VHA1
PUHZ-RP3VHA
PUHZ-RP3VHA1
Brief Check of DIP-IPM and DIP-PFC
W Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.). If they
are short-circuited, it means that they are broken.
1. Check of DIP-IPM
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
2. Check of DIP-PFC
P1 - L , P1 - N , L - N1 , N - N1
Note:The marks, L , N , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram above are not actually printed on the board.
LD1-LD2
300-380V DC
Connect to
the outdoor
controller
circuit board
(CNDC)
(Red)
+
1
3
–
(White)
R, S
Connect to the ACL
220-240V AC
P1NLN1
N2
U, V, W
Connect to the compressor (MC)
Voltage among phases: 5V to 180V AC
WVUP2
DIP-PFC
N1
LD9
Connect to
the earth
Only RP2.5,
3VHA
DIP-IPM
CN2
Connect to the outdoor controller circuit board (CN2)
1-5:Outdoor power circuit board
to the outdoor controller circuit board (0-5V DC)
2-5: Zero cross signal (0-5V DC)
3-4: Not used
6-5: 15V DC
7-5: 15V DC
1, 2, 6, 7 : +
[
➔ Transmitting signal
]
5 : –
7
1
CN3
Thermistor
<Heat sink>
(TH8)
52
CN4
Connect from the
outdoor controller
circuit board
(CN4)
CN5
Primary current detection
(Connect to the outdoor
noise filter circuit board
(CN5))
Outdoor Power circuit board
PUHZ-RP4VHA
PUHZ-RP4VHA1
PUHZ-RP5VHA
PUHZ-RP5VHA1
PUHZ-RP6VHA
PUHZ-RP6VHA1
CN5
Detection of
primary current
(Connect to the
outdoor noise filter
circuit board (CN5))
CN3
Temperature
<Heat sink>
(TH8)
Brief Check of POWER MODULE
W Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.).
If they are short-circuited, it means that they are broken.
1. Check of POWER MODULE
1.Check of DIODE circuit
2.Check of IGBT circuit
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
Note:The marks, L , N , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram above are not actually printed on the board.
CN4
Connect to the
outdoor controller
circuit board
(CN4)
L - P1 , N - P1 , L - N1 , N - N1
CN2
Connect to the outdoor controller circuit
board (CN2)
1-5: Power circuit board
signal to the controller board (0-5V DC)
CNAF
Connect to
ACTM
2-5: Zero cross signal (0-5V DC)
3-4: 18V DC
6-5: 15V DC
7-5: 15V DC
[ 5 : – 1, 2, 6, 7 : + ]
[ 4 : – 3 : + ]
➔ Transmitting
N1
P2
P1
W
U
N2
N
TAB-U, TAB-V,
TAB-W
Connect to the
compressor (MC)
Voltage among
phases:
V
L
5V-180V AC
SC-R, SC-S
Connect to the
outdoor noise filter
circuit board
(LO, NO)
220V-240V AC
SC-P2, SC-N2
Connect to
ACTM and the
soothing
capacitor
SC-P1
Connect to 52C
SC-N1
Connect to ACTM
POWER
MODULE
53
CNDC
–
300V-370V DC
}
+
Connect to the outdoor controller
circuit board (CNDC)
Switch
Type
of
switch
Dip
switch
SW1
1
2
No.
FunctionEffective timing
Action by the switch operation
Compulsory defrostingStartNormal
When compressor is working
in heating operation. w
Abnormal history clear
Refrigerant address setting
When power supply ON
ClearNormaloff or operating
SW4
1
6
5
4
3
2
Test runOperatingOFF
Under suspension
Test run mode settingHeatingCooling
ONOFF
123
0123
456ON123456ON123456ON123456
ON
123
4567
456ON123456ON123456ON123456
ON
123
891011
456ON123456ON123456ON123456
ON
123
12131415
456ON123456ON123456ON123456
ON
11-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS
1
2
3
4
3
4
5
6
1
2
3
ONOFF
No.
FunctionEffective timing
Action by the switch operation
No function
Power failure
automatic recovery w1
No function
No function
No function
No function
No function
No function
Use of existing pipe
Replacement operation
No function
Pump down
Switch
SW5
SW7
Dip
switch
Push
switch
SW8
SWP
Type of
Switch
—
Auto recovery
—
—
—
—
—
—
Used
Start
—
Start
—
No auto recovery
—
—
—
—
—
—
Not used
Normal
—
Normal
—
When power supply ON
—
—
Always
—
—
—
—
Always
Under suspension
—
Under suspension
Switch to “Low-level
Sound Priority Mode”
w2
1
2
1
OFF
OFF
Mode 1
Mode 2
Mode 3
OFF
ON
ON
ON
2Cooling
Regulate max Hz
to spec.
Regulate max Hz
to spec.
Regulate max Hz
to spec.
Regulate max Hz
to spec.
Only TH7 } 30°C
regulate max Hz
to spec.
No regulation
Heating
Low-level Sound
Priority Mode
(1) Function of switches
Compulsory defrosting should be done as follows.
1Change the DIP SW1-1 on the outdoor controller board from OFF to ON.
2Compulsory defrosting will start by the above operation 1 if these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor started operating or previous compulsory defrosting finished.
• Pipe temperature is less than or equal to 8:.
3Compulsory defrosting will finish if certain conditions are satisfied.
wCompulsory defrosting can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again. This
depends on the service conditions.
w1 Power failure automatic recovery’ can be set by either remote controller or this DIP SW. If one of them is set to ON,
‘Auto recovery’ activates. Please set “Auto recovery” basically by remote controller because all units have not DIP SW.
Please refer to mode 01 in the table on page 66.
w2 SW7-1,2 to “Low-level Sound Priority Mode” available in “Low-level Sound Priority Mode” mode only.
Unit enters into Low-level sound priority mode by SW7-1, 2 and external signal input setting.
Inputting external signals to the outdoor unit decreases the outdoor unit operation sound 3 to 4 dB lower than that of usual.
Adding a commercial timer or on-off switch contactor setting to the CNDM connector which is optional contactor for Demand
input located on the outdoor controller board enables to control compressor operation frequency. In Low-level sound priority
mode, the maximum outdoor fan steps is regulated to 8 and the maximum operation frequency of the compressor is
regulated to specified range in cool mode. In heating mode, the maximum compressor operation frequency is regulated to
specified range.
W The performance is depends on the load of conditioned air of the room.
How to wiring
Purchased at local
Relay
supply
~
SW1
SW1 : Switch
X : Relay (Contact spec. : DC1mA)
1) Make the circuit as shown above with Adaptor for external signal input(PAC-SC36NA).
2) Turn SW1 to on for Low-level sound priority mode.
Turn SW1 to off to release Low-level sound priority mode and normal operation.
(b) On demand control (Local wiring)
Demand control is available by external input. In this mode, the outdoor unit stops and indoor unit operates with fan mode.
W The setting of SW-7 is not required for the demand control.
How to wiring
Basically, the wiring is the same.
Connect an SW 1 which is procured at field to the between Orange and Red(1 and 3) of the Adaptor for external signal
input(PAC-SC36NA), and insulate the tip of the brown lead wire.
<Low-level sound priority mode circuit>
Insulate this point securely as
this is not used.
X
X
Max. 10 m including local wiring
Adaptor for external
signal input
(PAC-SC36NA)
Red
3
Brown
Orange
2
1
Outdoor unit
controller board
3
2
1
CNDM
<Outdoor unit controller board>
CNDM
55
<Display function of inspection for outdoor unit>
F3
F5
F9
—
—
—
E6
E7
—
—
E0
E3
E4
E5
EF
Ed
A0~A8
[Display]
(1)Normal condition
(2)Abnormal condition
Unit condition
Outdoor controller boardA-Control Service Tool
LED1 (Green)LED2 (Red)Error code
When the power is turned on
When unit stops
When compressor is warming up
When unit operates
LightedLighted
Lighted
Lighted
Lighted
Not lighted
Indication of the display
Alternately blinking display
Operation mode
Not lighted
Lighted
00, etc.
08, etc.
C5, H7 etc.
IndicationError
Error
code
w1
Outdoor controller board
ContentsInspection method
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
2 blinking 1 blinking
2 blinking
3 blinking
4 blinking
5 blinking
Connector(63L) is open.
Connector(63H) is open.
2 connectors are open.
Startup time over
Error code is not defined.
Mis-wiring of indoor/outdoor unit connecting wire, excessive number of indoor
units (4 units or more)
Mis-wiring of indoor/outdoor unit connecting wire (converse wiring or disconnection)
Indoor/outdoor unit communication error
(signal receiving error) is detected by indoor unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by indoor
unit.
Indoor/outdoor unit communication error
(signal receiving error) is detected by
outdoor unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by outdoor
unit.
Remote controller signal receiving
error is detected by remote controller.
Remote controller transmitting error
is detected by remote controller.
Remote controller signal receiving
error is detected by indoor unit.
Remote controller transmitting error
is detected by indoor unit.
Serial communication error
<Communication between outdoor
controller board and outdoor power
board>
<Communication between outdoor
controller board and M-NET p.c. board>
Communication error of high prior
signal(M-NET)
W1.Error code displayed on remote controller.
W2.Refer to service manual for indoor unit.
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if 4 or more indoor units are connected to outdoor unit.
3Check if noise entered into indoor/outdoor connecting wire
or power supply.
4Re-check error by turning off power, and on again.
1
Check if connector (63L or 63H) on the outdoor controller
board is not disconnected.
2
Check continuity of pressure switch (63L or 63H) by tester.
1
Check if connector (CN4) on outdoor controller board and
outdoor power board is not disconnected.
2
Check if there is poor connection of connector on outdoor
controller board(CNMNT and CNVMNT).
3
Check M-NET communication signal.
1Check if remote controller is MA remote controller(PAR-20MAA).
2Check if noise entered into transmission wire of remote controller.
3Check if noise entered into indoor/outdoor connecting wire.
4Re-check error by turning off power, and on again.
1Check if connecting wire of indoor unit or remote controller
is connected correctly.
2Check if noise entered into transmission wire of remote
controller.
3Re-check error by turning off power, and on again.
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if noise entered into indoor/outdoor connecting wire or
power supply.
3
Check if noise entered into indoor/outdoor controller board.
4
Re-check error by turning off power, and on again.
P.32
P.32
P.32
P.33
P.33
P.33
w2
w2
P.37
P.37
P.37
P.37
w2
w2
P.37
P.37
P.38~
P.41
Detailed
reference
page
The blinking patterns of both LED1(green) and LED2(red) indicate the types of abnormality when it occurs. Types of
abnormality can be indicated in details by connecting an optional part ‘A-Control Service Tool (PAC-SK52ST)’ to connector
CNM on outdoor controller board.
56
OperationLED5/LED6 (Red)
Lit
Normal (Stop)
Normal (Operating)
Fan stops.
Controller board is outputting waveform for fan driving.
Contents
Operation
LED5/LED6 (Red)
Importance
2 blinks1
2
3
4
5
6 blinks
8 blinks
7 blinks
Abnormal
is detected
Abnormality of bus voltage: Abnormal if bus voltage inspected for 1.5msec. is less than 60V or more than 390V.
Abnormality of overcurrent: Abnormal if current value of DC bus in fan controller board is over the cut-off point.
Abnormality of startup failure: Abnormal if the operating speed does not reach 100rpm even 12 sec passed after startup.
Abnormality of position detection: Abnormal if the position of U-phase cannot be detected after starting up fan.
Abnormality of disconnection: Abnormal if the first pattern of U/V/W-phase position detected after startup is H/H/H or L/L/L.
Meaning of error code and detection method
Remark
These
LEDs
are not
used
for
service.
U2
U7
U1
UF
UP
UH
U6
U3
U4
U5
U9
P1
P2
P9
P4
P5
P6
P8
IndicationError
Error
code
w1
Outdoor controller board
ContentsInspection method
LED1 (Green)
LED2 (Red)
3 blinking 1 blinking
2 blinking
W1 Error code displayed on remote controller
W2 Refer to service manual for indoor unit.
4 blinking
5 blinking
6 blinking
7 blinking
1 blinking
2 blinking
3 blinking
4 blinking
4 blinking
Abnormality of shell thermostat
and discharging temperature (TH4)
Abnormality of super heat due
to low discharge temperature
1Check if stop valves are open.
2Check if connectors (TH4, LEV-A, and LEV-B) on outdoor controller board are not
disconnected.
3Check if unit fills with specified amount of refrigerant.
4Measure resistance values among terminals on indoor valve and outdoor linear
expansion valve using a tester.
Abnormal high pressure (High
pressure switch 63H worked.)
1Check if indoor/outdoor units have a short cycle on their air ducts.
2Check if connector (63H) on outdoor controller board is not disconnected.
3Check if heat exchanger and filter is not dirty.
4Measure resistance values among terminals on linear expansion valve using a
tester.
1Check if stop valves are open.
2Check looseness, disconnection, and converse connection of compressor wiring.
3Measure resistance values among terminals on compressor using a tester.
4Check if outdoor unit has a short cycle on its air duct.
Compressor over current breaking (Start-up locked)
Compressor over current breaking
Abnormality of current sensor (P.B.)
Abnormality of power module
Open/short of discharge thermistor (TH4)
Open/short of outdoor thermistor (TH8)
Open/short of outdoor thermistors
(TH3, TH6, TH7 and TH8)
1
Check if connectors (TH3, TH4, TH6 and TH7) on outdoor controller board and conn-
ector (CN3) on outdoor power board are not disconnected.
2
Measure resistance value of outdoor thermistors.
Abnormality of radiator panel
temperature
1Check if indoor/outdoor units have a short cycle on their air ducts.
2Measure resistance value of outdoor thermistor(TH8).
Abnormality of voltage1Check looseness, disconnection, and converse connection of compressor wiring.
2Measure resistance value among terminals on compressor using a tester.
3Check the continuity of contactor (52C).
4Check if power supply voltage decreases.
5Check the wiring of CN52C.
6Check the wiring of CNAF. (RP4~6VHA only)
Abnormality of room temperature thermistor (TH1)
Abnormality of pipe temperature thermistor /Liquid (TH2)
Abnormality of pipe temperature
thermistor/Condenser-Evaporator
1Check if connectors (CN20, CN21 and CN29) on indoor controller board are not
disconnected.
2Measure resistance value of indoor thermistors.
Abnormality of drain sensor (DS)
Indoor drain overflow protection
1Check if connector (CN31) on indoor controller board is not disconnected.
2Measure resistance value of indoor thermistors.
3Measure resistance value among terminals on drain-up machine using a tester.
4Check if drain-up machine works.
5Check drain function.
1Check if indoor unit has a short cycle on its air duct.
2Check if heat exchanger and filter is not dirty.
3Measure resistance value on indoor and outdoor fan motors.
4Check if the inside of refrigerant piping is not clogged.
Abnormality of pipe
temperature
1Check if indoor thermistors (TH2 and TH5) are not disconnected from holder.
2Check if stop valve is open.
3Check converse connection of extension pipe. (on plural units connection)
4Check if indoor/outdoor connecting wire is connected correctly. (on plural units
connection)
W3 LED1 on power board for RP4, RP5 and RP6
1 blink: Power is supplied. 3 blinks:
Power is supplied to warm up compressor.
2 blinks: Power is supplied to compressor. Blinking: Limited control is being performed.
P.34
P.35
P.34
P.36
P.36
P.36
P.35
P.35
P.35
P.35
P.36
W2
W2
W2
W2
W2
W2
Detailed
reference
page
LED indications of fan operating condition (LED5 and LED6 on controller board)
57
<Outdoor unit operation monitor function>
1ON23456
1ON23456
1 second
interval
DisplayOperation Model
The tens digit : Operation mode
The ones digit : Relay output
O
C
H
d
Display
0
1
2
3
4
5
6
7
8
A
Compressor
Warming-up
Compressor
4-way valve
Solenoid valve
—
—
—
—
ON
ON
ON
ON
—
—
—
—
—
—
—
—
—
—
ON
ON
—
—
ON
ON
—
—
ON
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
—
OFF / FAN
COOLING / DRY w
HEATING
DEFROSTING
Display
Contents to be inspected (When power is turned on)
F3
F5
F9
E8
E9
EA
Eb
Ec
E0~E7
63L connector(red) is open.
63H connector(yellow) is open.
2 connectors (63H/63L) are open.
Indoor/outdoor communication error (Signal receiving error) (Outdoor unit)
Indoor/outdoor communication error (Transmitting error) (Outdoor unit)
Mis-wiring of indoor/outdoor unit connecting wire, excessive number of indoor units (4 units or more)
Mis-wiring of indoor/outdoor unit connecting wire(converse wiring or disconnection)
Startup time over
Communication error except for outdoor unit
Display
Inspection unit
0
1
2
3
Outdoor unit
Indoor unit 1
Indoor unit 2
Indoor unit 3
Display
Contents to be inspected (During operation)
U1
U2
U3
U4
U5
U6
U7
UF
UH
UL
UP
P1~P8
A0~A7
Abnormal high pressure (63H worked)
Abnormal high discharging temperature, shortage of refrigerant
Open/short circuit of discharging thermistor(TH4)
Open/short of outdoor unit thermistors(TH3, TH6, TH7 and TH8)
Abnormal temperature of heat sink
Abnormality of power module
Abnormality of super heat due to low discharge temperature
Compressor overcurrent interruption (When Comp. locked)
Current sensor error
Abnormal low pressure (63L worked)
Compressor overcurrent interruption
Abnormality of indoor units
Communication error of high-prior signal (M-NET)
[When option part ‘A-Control Service Tool(PAC-SK52ST)’ is connected to outdoor controller board(CNM)]
Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of error code by
controlling DIP SW2 on ‘A-Control Service Tool’.
Operation indicator SW2 : Indicator change of self diagnosis
SW2 setting
Display detail
Explanation for displayUnit
<Digital indicator LED1 working details>
(Be sure the 1 to 6 in the SW2 are set to OFF.)
(1) Display when the power supply ON.
When the power supply ON, blinking displays by turns.
Wait for 4 minutes at the longest.
(2) When the display lights. (Normal operation)
1Operation mode display.
(Lighting)
LED1
wC5 is displayed during replacement
operation. <except RP3VHA>
2Display during error postponement
Postponement code is displayed when
compressor stops due to the work of
protection device.
Postponement code is displayed while
error is being postponed.
(3) When the display blinks
Inspection code is displayed when compressor stops due to the work of protection devices.
SW2
(Initial setting)
58
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
10
1ON23456
1
05
4
25
2
45
1
25
1
50
1ON23456
Display detail
Pipe temperature / Liquid(TH3)
– 40~90
Explanation for displayUnit
– 40~90
(When the coil thermistor detects 0: or below, “–”
and temperature are displayed by turns.)
(Example) When -10:;
0.5 secs. 0.5secs. 2 secs.
:
Discharge temperature (TH4)
3~217
Output step of outdoor FAN
0~10
The number of ON / OFF times of
compressor
0~9999
Compressor integrating operation times
0~9999
Compressor operating current.
0~50
3~217
(When the discharge thermistor detects 100: or
more, hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 105:;
0.5 secs. 0.5secs. 2 secs.
0~10
0~9999
(When the number of times is 100 or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 42500 times (425 ✕100 times);
0.5 secs. 0.5secs. 2 secs.
0~9999
(When it is 100 hours or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 2450 hours (245 ✕10 hours);
0.5 secs. 0.5secs. 2 secs.
0~50
wOmit the figures after the decimal fractions.
:
Step
100 times
10 hours
A
Compressor operating frequency
0~225
0~255
(When it is 100Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 125Hz;
0.5 secs. 0.5secs. 2 secs.
LEV-Aopening pulse
0~480
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 150 pulse;
0.5 secs. 0.5secs. 2 secs.
Error postponement code history (1)
of outdoor unit
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
“00” is displayed in case of no postponement.
Operation mode on error occurringOperation mode of when operation stops due to
error is displayed by setting SW2 like below.
(SW2)
59
Hz
Pulse
Code
display
Code
display
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
15
1302
45
1
05
Display detail
Pipe temperature / Liquid(TH3) on error
occurring
– 40~90
Explanation for displayUnit
– 40~90
(When the coil thermistor detects 0: or below, “–”
and temperature are displayed by turns.)
(Example) When –15:;
0.5 secs. 0.5secs. 2 secs.
:
Compressor temperature (TH4) or
discharge temperature (TH4) on error
occurring
3~217
Compressor operating current on error
occurring
0~20
Error code history (1) (latest)
Alternate display of abnormal unit
number and code
Error code history (2)
Alternate display of error unit number
and code
3~217
(When the temperature is 100: or more, the
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 130:;
0.5 secs. 0.5secs. 2 secs.
0~20
When no error history,
“ 0 ” and “– –” are displayed by turns.
When no error history,
“ 0 ” and “– –” are displayed by turns.
:
A
Code
display
Code
display
Thermostat ON time
0~999
Test run elapsed time
0~120
0~999
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 245 minutes;
0.5 secs. 0.5secs. 2 secs.
0~120
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 105 minutes;
0.5 secs. 0.5secs. 2 secs.
60
Minute
Minute
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
Capacity
RP1.6V
RP2V
RP2.5V
RP3V
Code
9
10
11
14
Capacity
RP4V
RP5V
RP6V
Code
20
25
28
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P /
Cooling only
Single phase / Three phase
Display details
0 : H·P 1 : Cooling only
0 :
Single phase
2 :
Three phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
1ON23456
1ON23456
1ON23456
Display detail
The number of connected indoor units
Explanation for display
0~3
(The number of connected indoor units are displayed.)
Unit
Unit
Capacity setting display
Outdoor unit setting information
Indoor pipe temperature / Liquid
(TH2(1))
Indoor 1
– 39~88
Displayed as an outdoor capacity code.
(Example) When heat pump,three phase and
defrosting (normal) are set up, “20” is
displayed.
– 39~88
(When the temperature is 0: or less, “–” and
– 39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
8~39
61
:
:
:
:
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
Display detail
Indoor setting temperature
17~30
Explanation for displayUnit
17~30
:
1ON23456
Outdoor pipe temperature / Cond./
Eva. (TH6)
-39~88
Outdoor outside temperature (TH7)
-39~88
Outdoor heat sink temperature (TH8)
-40~200
Discharge super heat. SHd
0~255
Cooling = TH4-TH6
Heating = TH4-TH5
Sub cool. SC
0~130
Cooling = TH6-TH3
Heating = TH5-TH4
-39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
-39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
-40~200
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
(When the thermistor detects 100: or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
:
:
:
°C
°C
Input current of outdoor unit
LEV-B opening pulse
Targeted operation frequency
0~255
DC bus voltage
180~370
0~500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
0~255
(When it is 100Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
180~370
(When it is 100V or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
0.1 A
Pulse
Hz
V
62
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
00
1
25
1
Display detail
Capacity save
0~255
When air conditioner is connected to
M-NET and capacity save mode is
demanded, “0”~”100” is displayed.
When there is no setting
of capacity save “100” is
displayed.
Error postponement code history (2)
of outdoor unit
Explanation for displayUnit
0~100
(When the capacity is 100% hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 100%;
0.5 secs. 0.5secs. 2 secs.
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
“00” is displayed in case of no postponement.
%
Code
display
Error postponement code history (3)
of outdoor unit
Error code history (3) (Oldest)
Alternate display of abnormal unit number and code.
Error thermistor display
When there is no error thermistor,
“–“ is displayed.
Operation frequency on error occurring
0~255
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
“00” is displayed in case of no postponement.
When no error history, “0” and “– –“ are displayed by
turns.
3: Outdoor pipe temperature /Liquid (TH3)
6: Outdoor pipe temperature /Cond./Eva. (TH6)
7: Outdoor outside temperature (TH7)
8: Outdoor radiator panel (TH8)
0~255
(When it is 100Hz or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 125Hz;
0.5 secs. 0.5secs. 2 secs.
Code
display
Code
display
Code
display
Hz
Fan step on error occurring
0~10
0~10
Step
63
SW2 setting
1ON23456
30
1
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
15
15
15
15
Display detail
LEV-Aopening pulse on error occurring
0~480
Explanation for displayUnit
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 secs. 0.5secs. 2 secs.
Pulse
Indoor room temperature (TH1) on error
occurring
8~39
Indoor pipe temperature / Liquid (TH2)
on error occurring
-39~88
Indoor pipe temperature / Cond./ Eva.
(TH5) on error occurring
-39~88
Outdoor pipe temperature / Cond./ Eva.
(TH6) on error occurring
-39~88
8~39
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
:
:
:
:
Outdoor outside temperature (TH7) on
error occurring
-39~88
Outdoor heat sink temperature (TH8) on
error occurring
-40~200
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
-40~200
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
64
:
:
SW2 setting
50
1
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
15
1
15
4
1ON23456
Normal
Overvoltage error
Undervoltage error
T phase interruption error
Abnormal power synchronous signal
PFC error
(Overvoltage / Undervoltage / Overcurrent)
W Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
T phase interruption (04) + PFC error (10) = 14
Power circuit board
Controller circuit board
Controller circuit board
Power circuit board
Power circuit board
—
DescriptionDetection pointDisplay
00
01
02
04
08
10
Display detail
Discharge super heat on error occurring
SHd
0~255
Cooling = TH4-TH6
Heating = TH4-Th5
Explanation for displayUnit
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs. 0.5secs. 2 secs.
:
Sub cool on error occurring. SC
0~130
Cooling = TH6-TH3
Heating = TH5-TH2
Thermostat-on time until error stops
0~999
Indoor pipe temperature / Liquid
(TH2 (3))
Indoor 3
-39~88
Indoor pipe temperature / Cond./ Eva.
(TH5 (3))
Indoor 3
-39~88
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 secs. 0.5secs. 2 secs.
0~999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs. 0.5secs. 2 secs.
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
:
Minute
:
:
Replacement operation
WIf replacement operation is conducted
even once, “1” is displayed.
If replacement operation time is less
than 2 hrs. “0” is displayed.
U9 Error status during the Error
postponement period
Energy saving air
flow (Heating mode)
Direct add-on type
humidifier (Only for
power-cassette)
Swing
Set temperature in
heating mode 4deg-up
Fan speed when the
heating thermostat is OFF
Quiet operation mode of
power cassette
Fan speed when the
cooling thermostat is OFF
Detection of abnormality
of the pipe temperature (P8)
100Hr
2500Hr
No filter sign indicator
standard
High ceiling 1
High ceiling 2
4 directions
3 directions
2 directions
Not supported
Supported
No vanes
Equipped with vane (No.1 setting)
Equipped with vane (No.2 setting)
Disabled
Enabled
Not supported
Supported
Not available
Available
Available
Not available
Extra low
Low (4-speed model) Low (2-speed model)
Set fan speed
Normal
Quiet
Set fan speed
Stop
Available
Not available
1
2
3
1
2
3
1
2
3
1
2
1
2
3
1
2
1
2
1
2
1
2
3
1
2
1
2
1
2
1
2
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
07
08
09
10
11
12
13
23
24
25
26
27
28
4-way Cassette
PLA-AA
(powercassette)
PLA-AA.UK
(powercassette)
Ceiling concealed
Initial setting
(when sent from the factory)
–: Not available
PEAD-EA
PEAD-GA
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Ceiling
Concealed
Wall Mounted
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
PKA-FAL PKA-GAL
—
—
—
—
—
—
—
Ceiling
Suspended
PCA-GA
Function
Settings
Mode No.
Setting No.
Initial setting
(when sent from the factory)
Remarks
Power failure
automatic recovery
Indoor temperature
detecting
LOSSNAY
connectivity
Power supply
voltage
Auto operating
mode
Frost prevention
temperature
Humidifier control
Change of
defrosting control
OFF
ON
Operating indoor units
(The average is considered as indoor temperature.)
Indoor unit with remote controller
Remote controller's internal sensor
Not supported
Supported (indoor unit not equipped with outdoor air intake)
Supported (indoor unit equipped with outdoor air intake)
240V
220V,230V
Auto energy-saving operation ON
Auto energy-saving operation OFF
2: (Normal)
3:
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
Standard
For high humidity
1
2
1
2
3
1
2
3
1
2
1
2
1
2
1
2
1
2
01
02
03
04
05
15
16
17
The setting is
applied to all
the units in the
same
refrigerant
system.
11-11. SELECTING FUNCTIONS USING THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
<Table 1> Function selections
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number
on Page 67.)
W1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the
indoor unit number on Page 67.
• When setting functions for a simultaneous- Twin Triple indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number on Page 67.
• When setting the same functions for an entire simultaneous Twin Triple-indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to 4 setting the indoor unit number on Page 67.
66
11-11-1. Selecting functions using the wired remote controller
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
F
E
G
CD
A
J
B
123
4
[Flow of function selection procedure]
The flow of function selection procedure is shown below. The flow is described in case of setting indoor temperature detecting
shown in table 1 on the preceding page. Refer to procedure 1 to 0 when actually setting functions.
Selecting functions using the wired remote controller
1 Check the function selection setting.
2 Switch to function setting mode. w
(Press A and B at the same time
with the remote controller stopped.)
w For modes 15 and higher,
press J and B at the same
time.
3 Specify refrigerant address "00" (outdoor unit)
(This operation is not necessary for single
refrigerant system.)
4 Specify unit No. "00". (indoor unit)
1 Mode number
2 Setting number
3 Refrigerant address
4 Unit number
YES
9
For mode 01 to 13, press Aand B at the same time
and for mode 15 to 28, press B and J to go to function
select mode.
[Operating instructions]
11
Checking the function settings
If you change the setting in the function setting procedure, the contents of setting will be changed for the designated mode.
Change the setting after recording all the previous setting into the checklist of table 1 by following steps 2 to 7. In addition,
read the installation manual packed with indoor units to be informed of initial setting.
22
Turning off the remote controller
Press the
A FILTER and B TEST RUN buttons simultaneous-
ly and hold them for at least 2 seconds.
(For modes 15 and higher, press J and B simultaneously for
33
Setting the refrigerant address No. of outdoor unit
Press CTIMER SET button to select the refrigerant
address from No.00 to No.15. (Set the refrigerant address to
No.00 in case of single refrigerant grouping system.)
at least 2 seconds.) FUNCTION will start to flash. After a
while, the refrigerant address display will start to flash .
3
FUNCTION
FUNCTION
W If the unit stops two seconds after the FUNCTION display starts to flash or [88] starts to flash in the room temperature display, a transmission problem may have occurred. Check to see if there are some sources of transmission interference (noise)
nearby.
If you make a mistake during any points of this procedure, you can quit the function setting by pressing 0
then return to step 2.
67
44
FUNCTION
1
(a)
(c)
(h)
(g)
(b)
(f)
(d)(e)
3 00 refrigerant address
FUNCTION
1
FUNCTION
FUNCTION
2
2
Setting the indoor unit number
Press D(CLOCK ON OFF) and [--] will start to flash in the unit
number display (4) .
4
Press C(TIMER SET) button to select the unit
number from 00, 01, 02, 03, 04, and AL.
FUNCTION
•Set the unit number to 00 if the mode such as power failure automatic recovery, indoor temperature detecting or
LOSSNAY connectivity is desired to be selected.
•Select the unit number from 01 to 04 if the function setting is desired to be done for each of them individually.
•Set the unit number to AL if the function setting is desired to be done for all of units simultaneously.
55
Confirming the refrigerant address and indoor unit number
Press E MODE button to confirm the refrigerant address and
unit number.
After a while, [--] will flash in the mode number display (I).
WIf [88] appears in the room temperature display section, the
selected refrigerant address does not exist in the system.
Also, if [F] appears in the unit number display section, the
selected unit number does not exist. Enter the correct refrig-
erant address and unit number at steps 2 and 3.
FUNCTION
Designated indoor unit starts fan draft operation by pressingE
MODE button. Check which indoor unit is designated for function setting by doing this. In addition, all the units of the
selected refrigerant address start fan draft operation if the unit
number is set to 00 or AL.
Example) When the refrigerant address is set to 00 and the
unit number is 02;
(a) Outdoor unit
(b) Indoor unit
(c) Unit number 01
(d) Unit number 02
(e) Unit number 03
(f) Fan draft
(g) Designation
(h) Remote controller
WIf any undesignated indoor units start fan draft operation
under multiple refrigerant grouping system, refrigerant
addresses may be overlapped. Reassign refrigerant addresses at the DIP switch of the outdoor unit.
66
Selecting the mode number
Press F(TEMP) buttons to set the desired mode number. (It is possible to set the number of available mode only.)
77
Selecting the setting of designated mode
Press G button, and the setting number will start to flash.
Press F(TEMP) button to select the setting number.
Check the current status of the setting by doing this.
68
88
Registering the settings from steps 33to 77into memory
The mode and setting numbers (1)(2) will start to flash when the MODE button E is pressed and registration will begin. The
numbers are set when the flashing stays lit.
FUNCTION
21
21
FUNCTION
WIf [---] appears in the room temperature display as the mode/setting number, or if a flashing [88] display appears, a transmission problem may have occurred. Check to see if there are some sources of transmission interference (noise) nearby.
99
Registering other settings simultaneously
Repeat steps 3 to 8 to make other function settings.
00
Completing the function settings
Press A FILTER and B TEST RUN buttons simultaneously for at least two seconds. (For modes 15 and higher, press J andB simultaneously for at least 2 seconds.) After a while, the function selection screen will disappear and air conditioner OFF
display will appear.
WDo not use the remote controller for 30 seconds after completing the function
setting. (Any requests will be rejected.)
FUNCTION
Note
Make sure to check all settings with and etc. on the checklist of table 1 if
you have changed the settings of indoor units by this procedure after installation construction.
69
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESET
SET
CLOCK
h
CHECK
min
h
The flow of the function selection procedure is shown below. This example shows how to turn
off the function that raises the set temperature by 4 degrees during HEAT operation .
The procedure is given after the flow chart.
1 Check the function selection setting.
2 Switch to function selection mode.
(Enter address "50" in troubleshooting
mode, then press the HOUR button.)
Troubleshooting mode is the mode entered when
you press the INSPECT button twice to display
"INSPECT".
3 Specify unit No. "01" (since the function applies to unit 01).
(Set address "01" while still in troubleshooting mode, then press the MINUTE button.)
Note: You can't specify the refrigerant address.
4
Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation).
(Set address "24" while still in troubleshooting mode, then press the HOUR button.)
6
Finished
8 End function selection mode.
(End troubleshooting mode.)
YES
NO
Note: When you switch to function selection mode
on the wireless remote controller's operation
area, the unit ends function selection mode
automatically if nothing is input for 10 minutes
or longer.
5 Select setting No. "02" (OFF).
(Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change
unit No.
YES
NO
7
11-11-2. Selecting functions using the wireless remote controller (Type C)
h
min
Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refrigerant system with wireless function. Refrigerant address cannot be specified by the wireless remote controller.
[Flow of function selection procedure]
[Operating instructions]
1 Check the function settings.
2 Press the button twice continuously. → CHECK is lit and “00” blinks.
Press the temp button once to set “50”. Direct the wireless remote controller toward the receiver of the indoor unit and press
the button.
3 Set the unit number.
Press the temp button to set the unit number. (Press “01” to specify the indoor unit whose unit number is 01.)
Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
By setting unit number with the button, specified indoor unit starts performing fan operation.
Detect which unit is assigned to which number using this function. If unit number is set to AL, all the indoor units in same
refrigerant system start performing fan operation simultaneously.
* If a unit number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the unit number
setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the unit number
setting.
4 Select a mode.
Press the temp button to set a mode. Press “24” to turn on the function that raises the set temperature by 4 degree
during heat operation. Direct the wireless remote controller toward the sensor of the indoor unit and press the button.
→ The sensor-operation indicator will flash and beeps will be heard to indicate the current setting number.
Current setting number: 1 = 1 beep (one second)
2 = 2 beeps (one second each)
* If a mode number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the mode
number.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the mode
number.
5 Select the setting number.
Press the temp button to select the setting number. (02: Not available)
Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
→ The sensor-operation indicator will flash and beeps will be heard to indicate the the setting number.
Setting number: 1 = 2 beeps (0.4 seconds each)
* If a setting number that cannot be recognized by the unit is entered, the setting will turn back to the original setting.
6 Repeat steps 4 and 5 to make an additional setting without changing unit number.
7 Repeat steps 3 to 5 to change unit number and make function settings on it.
8 Complete the function settings
* Do not use the wireless remote controller for 30 seconds after completing the function setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the setting number.
1. Removing the top panel, service panel, front panel and
back panel
(1) Remove the top panel fixing screws (4 ✕ 10), one from the
right and two from the eft side, and detach the top panel.
(2) Remove 1 service panel fixing screw (4 ✕ 10) and detach
the service panel by pulling it downward. (See photo 2.)
(3) Remove the front panel fixing screws (4 ✕ 10), 5 from the
front, 2 from the right and 2 from the left side, and detach
the front panel.
(4) Remove the back panel fixing screws (4 ✕ 10), 4 from the
right and 3 from the rear side, and detach the back panel.
Photo 1
Grille
Photo 2
Front panel
PHOTOS
Top panel
Top panel
fixing screws
Back panel
Service panel
for charge
plug
Service panel
Service panel
fixing screw
Pull down
2. Removing the fan motor
(1) Remove the top panel. (See photo 1.)
(2) Remove the front panel. (See photo 1.)
(3) Remove 1 nut (M6, left-screw) and detach the propeller.
(4) Disconnect the connectors, FAN11 and FAN12 on the
controller circuit board in the electrical parts box.
(5) Loosen the clamp for the lead wire in the motor support.
(6) Remove 4 fan motor fixing screws (4 ✕ 18) and detach the
fan motor. (See photo 3.)
Photo 3
Nut
Photo 4
Fan
motor
(MF1)
Propeller
Fan motor fixing screws
Electrical parts box
4 hooks
Clamp
Motor support
71
Fan motor fixing screws
OPERATING PROCEDUREPHOTOS
3. Removing the electrical parts box
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Disconnect the indoor/outdoor connecting wire from
terminal block.
(5) Remove all the following connectors from controller circuit board;
fan motor, linear expansion valve, thermistor<Outdoor pipe>,
thermistor<Outdoor>, high pressure switch, four-way valve
and bypass valve.
Pull out the disconnected wire from the electrical parts box.
<Diagram symbol in the connector housing>
(6) Remove the terminal cover and disconnect the compressor
lead wire.
(7) Remove the electrical parts box fixing screws, 1 from the
front, the right and the rear side, and detach the electrical
parts box by pulling it upward.
Photo 5
Terminal
cover
Electrical parts box
Motor for
compressor (MC)
Controller circuit
board (C.B.)
Terminal
block
(TB1)
Electrical
parts box
fixing
screw
4. Removing the thermistor <Outdoor 2-phase pipe> (TH6)
and thermistor <Outdoor pipe> (TH3)
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel fixing screws, 4 from the right and
3 from the rear side, and detach the back panel.
(See photo 1.)
(5) Disconnect the connector TH3 (white) or TH6/7 (red) on
the controller circuit board in the electrical parts box.
(6) Loosen the clamp for the lead wire in the rear of the
electrical parts box.
(7) Pull out the thermistor <Outdoor pipe> (TH3) and
thermistor <Outdoor 2-phase pipe> (TH6) from the
sensor holder.
Note: In case of replacing the thermistor <Outdoor 2-phase pipe>
(TH6), replace it together with the thermistor <Outdoor>
(TH7), since they are combined together. Refer to No. 5
below to remove the thermistor <Outdoor> (TH7).
Photo 6
Electrical
parts box
Thermistor
<Outdoor 2-phase pipe>
(TH6)
Clamp
Thermistor
<Outdoor 2-phase
pipe> (TH6)
72
OPERATING PROCEDUREPHOTOS
5. Removing the thermistor <Outdoor> (TH7)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the connector TH7 (red) on the controller circuit
board in the electrical parts box.
(4) Loosen the clamp for the lead wire in the rear of the
electrical parts box. (See photo 4.)
(5) Pull out the thermistor <Outdoor> (TH7) from the sensor
holder.
Note: In case of replacing thermistor <Outdoor> (TH7), replace
it together with thermistor <Outdoor 2-phase pipe> (TH6),
since they are combined together. Refer to No.4 above
to remove thermistor <Outdoor 2-phase pipe>.
6. Removing the thermistor <Discharge> (TH4)
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(6) Pull out the thermistor <Discharge> (TH4) from the sensor
holder. (See photo 8.)
w When attaching the thermistor <Discharge> (TH4), place it
to its original position.
Photo 7
Photo 8
Electrical parts box
Sensor holder
Thermistor <Outdoor>
(TH7)
Thermistor <Discharge>
(TH4)
7. Removing the solenoid valve coil <Four-way valve> (21S4)
and linear expansion valve coil (LEV (A), LEV (B))
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(7) Remove the solenoid valve coil <Four-way valve> by
sliding the coil to the right.
[Removing the linear expansion valve coil (LEV (A), LEV (B)) ]
(6) Remove the linear expansion valve coil by sliding the coil
upward.
Photo 9
Linear expansion
valve coil (LEV B)
Linear expansion valve
Linear expansion
valve coil (LEV A)
solenoid valve coil
<Four-way valve>
(21S4)
Four-way
valve
solenoid valve coil
<Four-way valve>
fixing screw
73
OPERATING PROCEDUREPHOTOS
8. Removing the four-way valve
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(6) Remove the solenoid valve coil <Four-way valve>
(See photo 8.)
(7) Collect the refrigerant.
(8) Remove the welded part of four-way valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the four-way valve, cover it with a we
cloth to prevent it from heating (120°C or more),
then braze the pipes so that the inside of pipes are
not oxidized.
9. Removing linear expansion valve
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(6) Remove the linear expansion valve coil . (See photo 8.)
(7) Collect the refrigerant.
(8) Remove the welded part of linear expansion valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the back panel.
Note 3: When installing the linear expansion valve, cover it
with a wet cloth to prevent it from heating (120°C or
more), then braze the pipes so that the inside of
pipes are not oxidized.
Photo 10
Linear expansion
valve coil (LEV B)
Linear expansion valve
Linear expansion
valve coil (LEV A)
solenoid valve coil
<Four-way valve>
(21S4)
Four-way
valve
solenoid valve coil
<Four-way valve>
fixing screw
10. Removing the high pressure switch (63H)
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(6) Pull out the lead wire of high pressure switch.
(7) Collect the refrigerant.
(8) Remove the welded part of high pressure switch.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the back panel.
Note 3: When installing the high pressure switch, cover it with
a wet cloth to prevent it from heating (100°C or more),
then braze the pipes so that the inside of pipes are
not oxidized.
11. Removing the reactor (ACL)
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove 3 reactor fixing screws (4 ✕ 20) and remove the
reactor.
w The reactor is attached to the rear of the electrical parts box.
Photo 11
High pressure
switch (63H)
Charge plug
Photo 12
Reactor fixing screw
Reactor
(ACL)
74
Electrical
parts box
Reactor fixing screws
OPERATING PROCEDUREPHOTOS
12. Removing the motor for compressor (MC)
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(6) Remove 3 separator fixing screws (4 ✕ 10) and remove
the separator.
(7) Collect the refrigerant.
(8) Remove 3 compressor fixing nuts by using a spanner or a
monkey wrench.
(9) Remove the welded pipe of motor for compressor inlet
and outlet.
Note: Collect refrigerant without spreading it in the air.
Photo 13
Motor for
compressor
(MC)
Separator
Separator
fixing screw
Power
receiver
Valve bed
Compressor
fixing nut
13. Removing the power receiver
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(6) Collect the refrigerant.
(7) Remove 4 welded pipes of power receiver inlet and outlet.
(8) Remove 2 receiver leg fixing screws (4 ✕ 10).
(9) Remove the power receiver together with the receiver leg.
Note: Collect refrigerant without spreading it in the air.
high pressure switch, four-way valve and bypass valve.
Then remove a screw (4 ✕ 8) from the valve bad to
remove the lead wire.
Pull out the disconnected wire from the electrical parts box.
<Diagram symbol in the connector housing>
(5) Remove the terminal cover and disconnect the compressor
lead wire.
(6) Remove an electrical parts box fixing screw (4 ✕ 10) and
detach the electrical parts box by pulling it upward. The
electrical parts box is fixed with 2 hooks on the left and 1
hook on the right.
Front panel fixing screws
Photo 3
Valve bed
Screw
Cover panel fixing screws
Fan motor
fixing screws
Electrical parts box
Controller circuit
board
(C.B.)
Electrical parts
box fixing screw
Terminal block
(TB1)
Terminal cover
Motor for
compressor (MC)
Cover panel
(Front)
76
OPERATING PROCEDUREPHOTOS
4. Removing the thermistor <Outdoor 2-phase pipe> (TH6)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the connectors, TH6 and TH7 (red), on the
controller circuit board in the electrical parts box.
(4) Loosen the clamp for the lead wire in the rear of the
electrical parts box.
(5) Pull out the thermistor <Outdoor 2-phase pipe> (TH6)
from the sensor holder.
Note: In case of replacing thermistor <Outdoor 2-phase pipe>
(TH6), replace it together with thermistor <Outdoor>
(TH7), since they are combined together. Refer to No.5
below to remove thermistor <Outdoor>.
5. Removing the thermistor <Outdoor> (TH7)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the connector TH7 (red) on the controller circuit
board in the electrical parts box.
(4) Loosen the clamp for the lead wire in the rear of the
electrical parts box. (See photo 4.)
(5) Pull out the thermistor <Outdoor> (TH7) from the sensor
holder.
Photo 4
Controller
circuit board
(C.B.)
Photo 5
Electrical
parts box
Thermistor
<Outdoor 2-phase pipe>
(TH6)
Clamp
Note: In case of replacing thermistor <Outdoor> (TH7), replace
it together with thermistor <Outdoor 2-phase pipe> (TH6),
since they are combined together. Refer to No.4 above
to remove thermistor <Outdoor 2-phase pipe>.
6. Removing the thermistor <Outdoor pipe> (TH3) and
thermistor <Discharge> (TH4)
(1) Remove the service panel. (See figure 1.)
(2) Disconnect the connectors, TH3 (white) and TH4 (white),
on the controller circuit board in the electrical parts box.
(3) Loosen the clamp for the lead wire in the rear of the
electrical parts box. (See photo 4.)
(4) Pull out the thermistor <Outdoor pipe> (TH3) and
thermistor <Discharge> (TH4) from the sensor holder.
Thermistor
<Outdoor>
(TH7)
Photo 6
Sensor holder
77
Thermistor
<Discharge>
(TH4)
Thermistor
<Outdoor pipe>
(TH3)
OPERATING PROCEDURE
PHOTOS
7. Removing the solenoid valve coil <Four-way valve> (21S4),
linear expansion valve coil (LEV(A), LEV(B)) and
solenoid valve coil <Bypass valve> (SV)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
[Removing the solenoid valve coil <Four-way valve>]
(5) Remove the solenoid valve coil <Four-way valve> by
sliding the coil toward you.
(6) Disconnect the connector 21S4 (green) on the controller
board in the electrical parts box.
[Removing the linear expansion valve coil]
(4) Remove the linear expansion valve coil by sliding the coil upward.
(5) Disconnect the connectors, LEV A(white) and LEV B (red),
on the controller circuit board in the electrical parts box.
[Removing the solenoid valve coil <Bypass valve>]
(4) Remove the solenoid valve coil <Bypass valve> fixing screw
(M4 ✕ 6).
(5) Remove the solenoid valve coil <Bypass valve> by sliding the
coil upward.
(6) Disconnect the connector SV2 (blue) on the controller
circuit board in the electrical parts box.
8. Removing the four-way valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball
valve and stop valve fixing screws (5 ✕ 16) and then
remove the valve bed.
(5) Remove 3 right side panel fixing screw (5 ✕ 10) in the
rear of the unit and then remove the right side panel.
(6) Remove the solenoid valve coil <Four-way valve>.
(See photo 7.)
(7) Collect the refrigerant.
(8) Remove the welded part of four-way valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the four-way valve, cover it with a wet cloth
to prevent it from heating (120°C or more), then braze the
pipes so that the inside of pipes are not oxidized.
9. Removing the linear expansion valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball
valve and stop valve fixing screws (5 ✕ 16) and then
remove the valve bed.
(5) Remove 3 right side panel fixing screw (5 ✕ 10) in the
rear of the unit and then remove the right side panel.
(6) Remove the linear expansion valve. (See photo 7.)
(7) Collect the refrigerant.
(8) Remove the welded part of linear expansion valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the linear expansion valve, cover it
with a wet cloth to prevent it from heating (120°C or
more), then braze the pipes so that the inside of pipes are not oxidized.
Photo 7
Linear expansion
valve coil (LEV B)
Solenoid
valve coil
<Bypass valve>
fixing screw
Solenoid
valve coil
<Bypass valve>
(SV)
Photo 8
Solenoid
valve coil
<Bypass valve>
(SV)
Bypass
valve
Linear
expansion
valve
Charge plug
(High pressure)
Linear expansion
valve coil (LEV B)
solenoid valve coil
<Four-way valve>
(21S4)
Linear expansion
valve coil (LEV A)
Four-way valve
solenoid
valve coil
<Four-way valve>
fixing screw
solenoid
valve coil
<Four-way valve>
(21S4)
Linear expansion
valve coil (LEV A)
Linear
expansion
valve
Four-way
valve
Stop valve
Charge plug
(Low pressure)
78
OPERATING PROCEDURE
PHOTOS
10. Removing the bypass valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 right side panel fixing screws (5 ✕ 10) in the
rear of the unit and remove the right side panel.
(5) Remove the bypass valve solenoid coil. (See photo 7.).
(6) Collect the refrigerant.
(7) Remove the welded part of bypass valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
11. Removing the high pressure switch (63H)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 right side panel fixing screws (5 ✕ 10) in the
rear of the unit and remove the right side panel.
(5) Pull out the lead wire of high pressure switch.
(6) Collect the refrigerant.
(7) Remove the welded part of high pressure switch.
Photo 9
Solenoid valve coil
<Bypass valve>
(SV)
Bypass
valve
Linear
expansion
valve
Solenoid valve coil
<Four-way valve>
(21S4)
Photo 10
Lead wire of
high pressure switch
Linear expansion
valve coil (LEV B)
High pressure switch (63H)
Linear expansion
valve coil (LEV A)
Linear
expansion
valve
Four-way
valve
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the high pressure switch, cover it with
a wet cloth to prevent it from heating (100°C or more),
then braze the pipes so that the inside of pipes are
not oxidized.
12. Removing the reactor (ACL)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 reactor fixing screws (4 ✕ 16) and remove the
reactor.
w The reactor is attached to the rear of the electrical parts box.
Photo 11
Reactor fixing screw
Reactor
(ACL)
79
Reactor fixing screws
Electrical parts box
OPERATING PROCEDURE
PHOTOS
13. Removing the motor for compressor (MC)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 2 front cover panel fixing screws (5 ✕ 10) and
remove the front cover panel. (See photo 3.)
(4) Remove 2 back cover panel fixing screws (5 ✕ 10) and
remove the back cover panel.
(5) Remove the electrical parts box. (See photo 3.)
(6) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball valve
and stop valve fixing screws (5 ✕ 16) and then remove the
valve bed.
(7) Remove 3 right side panel fixing screw (5 ✕ 10) in the rear
of the unit and then remove the right side panel.
(8) Remove 3 separator fixing screws (4 ✕ 10) and remove
the separator.
(9) Collect the refrigerant.
(10) Remove the 3 points of the motor for compressor fixing
nut using a spanner or a monkey wrench.
(11) Remove the welded pipe of motor for compressor inlet
and outlet and then remove the compressor.
Note: Collect refrigerant without spreading it in the air.
Photo 12
Valve bed
Motor for
compressor
(MC)
Separator
Separator
fixing screw
Valve bed
fixing
screws
Power
receiver
Compressor
fixing nut
14. Removing the power receiver
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 2 front cover panel fixing screws (5 ✕ 10) and
remove the front cover panel. (See photo 3.)
(4) Remove 2 back cover panel fixing screws (5 ✕ 10) and
remove the back cover panel.
(5) Remove the electrical parts box. (See photo 3.)
(6) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball valve
and stop valve fixing screws (5 ✕ 16) and then remove the
valve bed.
(7) Remove 3 right side panel fixing screw (5 ✕ 10) in the
rear of the unit and then remove the right side panel.
(8) Collect the refrigerant.
(9) Remove 4 welded pipes of power receiver inlet and outlet.
(10) Remove 2 receiver leg fixing screws (4 ✕ 10).
Note: Collect refrigerant without spreading it in the air.
Photo 13
Inlet
Outlet
Power
receiver
Receiver
leg
Receiver leg
fixing screws
80
PUHZ-RP4VHA PUHZ-RP5VHA PUHZ-RP6VHA
OPERATING PROCEDURE
1. Removing the service panel and top panel
(1) Remove 3 service panel fixing screws (5 ✕ 10) and slide
the hook on the right downward to remove the service
panel.
(2) Remove screws (3 for front, 3 for rear/5 ✕ 10) of the top
panel and remove it.
2. Removing the fan motor (MF1, MF2)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 5 fan grille fixing screws (5 ✕ 10) to detach the
fan grille. (See figure 1.)
(4) Remove a nut (for right handed screw of M6) to detach
the propeller. (See photo 1.)
(5) Disconnect the connectors, FAN11, FAN12, FAN21 and
FAN 22 on controller circuit board in electrical parts box.
(6) Remove 4 fan motor fixing screws (5 ✕ 25) to detach the
fan motor. (See photo 2.)
Figure 1
Grille
fixing
screws
Grille
fixing
screws
Photo 1
Nut
PHOTOS & ILLUSTRATION
Top panel fixing screws
Slide
Front panel
Propeller
Photo 2
Fan motor fixing screws
Top panel
Service panel
Fan grille
Service panel
fixing screws
Fan
motor
3. Removing the electrical parts box
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the indoor/outdoor connecting wire from
terminal block.
(4) Remove all the following connectors from controller circuit board;
fan motor, linear expansion valve, thermistor <Outdoor pipe>,
thermistor <Discharge>, thermistor <Outdoor 2-phase pipe>,
thermistor <Outdoor>, thermistor <Heat sink>,
high pressure switch, low pressure switch,
solenoid valve coil <Four-way valve> and solenoid valve
coil <Bypass valve>. Then remove a screw (4 ✕ 8) from
the valve bad to remove the lead wire.
Pull out the disconnected wire from the electrical parts box.
(6) Remove an electrical parts box fixing screw (4 ✕ 10) and
detach the electrical parts box by pulling it upward. The
electrical parts box is fixed with 2 hooks on the left and 1
hook on the right.
Photo 3
Screw
Fan motor fixing screws
Controller circuit board
(C.B.)
Electrical
parts box
Electrical parts
box fixing screw
Terminal block
(TB1)
Valve bed
Motor for
compressor
(MC)
Terminal cover
Cover panel
(Front)
Cover panel fixing screws
81
OPERATING PROCEDUREPHOTOS
4. Removing the thermistor <Outdoor 2-phase pipe> (TH6)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the connectors, TH6 and TH7 (red), on the
controller circuit board in the electrical parts box.
(4) Loosen the clamp for the lead wire in the rear of the
electrical parts box.
(5) Pull out the thermistor <Outdoor 2-phase pipe> (TH6)
from the sensor holder.
Note: In case of replacing thermistor <Outdoor 2-phase pipe>
(TH6), replace it together with thermistor <Outdoor>
(TH7) since they are combined together. Refer to No.5
below to remove thermistor <Outdoor>.
5. Removing the thermistor <Outdoor> (TH7)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the connector TH7 (red) on the controller circuit
board in the electrical parts box.
(4) Loosen the clamp for the lead wire in the rear of the
electrical parts box. (See photo 4.)
(5) Pull out the thermistor <Outdoor> (TH7) from the sensor
holder.
Photo 4
Controller
circuit board
(C.B.)
Photo 5
Electrical
parts box
Thermistor
<Outdoor 2-phase pipe>
(TH6)
Clamp
Note: In case of replacing thermistor <Outdoor> (TH7),
replace it together with thermistor <Outdoor 2-phase
pipe> (TH6), since they are combined together. Refer to
No.4 above to remove thermistor <Outdoor 2-phase pipe>.
6. Removing the thermistor <Outdoor pipe> (TH3) and
thermistor <Discharge> (TH4)
(1) Remove the service panel. (See figure 1.)
(2) Disconnect the connectors, TH3 (white) and TH4 (white),
on the controller circuit board in the electrical parts box.
(3) Loosen the clamp for the lead wire in the rear of the
electrical parts box. (See photo 4.)
(4) Pull out the thermistor <Outdoor pipe> (TH3) and
thermistor <Discharge> (TH4) from the sensor holder.
Thermistor
<Outdoor>
(TH7)
Photo 6
Sensor holder
Thermistor
<Discharge>
(TH4)
82
Thermistor
<Outdoor pipe>
(TH3)
OPERATING PROCEDURE
PHOTOS
7. Removing the solenoid valve coil <Four-way valve> (21S4),
and linear expansion valve coil (LEV(A), LEV(B))
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
[Removing the solenoid valve coil <Four-way valve>]
(4) Remove the solenoid valve coil <Four-way valve> by
sliding the coil toward you.
(5) Disconnect the connector 21S4 (green) on the controller
circuit board in the electrical parts box.
[Removing the linear expansion valve coil]
(3) Remove the linear expansion valve coil by sliding the coil
upward.
(4) Disconnect the connectors, LEV A(white) and LEV B (red),
on the controller circuit board in the electrical parts box.
8. Removing the four-way valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball
valve and stop valve fixing screws (5 ✕ 16) and then
remove the valve bed.
(4) Remove 4 right side panel fixing screw (5 ✕ 10) in the
rear of the unit and then remove the right side panel.
(5) Remove the solenoid valve coil <Four-way valve>.
(See photo 7.)
(6) Collect the refrigerant.
(7) Remove the welded part of four-way valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the four-way valve, cover it with a wet
cloth to prevent it from heating (120°C or more),
then braze the pipes so that the inside of pipes are
not oxidized.
9. Removing linear expansion valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball
valve and stop valve fixing screws (5 ✕ 16) and then
remove the valve bed.
(4) Remove 4 right side panel fixing screw (5 ✕ 10) in the
rear of the unit and then remove the right side panel.
(5) Remove the linear expansion valve. (See photo 7.)
(6) Collect the refrigerant.
(7) Remove the welded part of linear expansion valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the linear expansion valve, cover it
with a wet cloth to prevent it from heating (120°C or
more), then braze the pipes so that the inside of pipes are not oxidized.
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 right side panel fixing screws (5 ✕ 10) in the
rear of the unit and remove the right side panel.
(4) Remove the bypass valve solenoid coil fixing screw
(M4 ✕ 6).
(5) Remove the solenoid valve coil <Bypass valve> by
sliding the coil upward.
(6) Disconnect the connector SV2 (blue) on the controller
circuit board in the electrical parts box.
(7) Collect the refrigerant.
(8) Remove the welded part of bypass valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
11. Removing the high pressure switch (63H) and
low pressure switch (63L)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 right side panel fixing screws (5 ✕ 10) in the
rear of the unit and remove the right side panel.
(4) Pull out the lead wire of high pressure switch and low
pressure switch.
(5) Collect the refrigerant.
(6) Remove the welded part of high pressure switch and low
pressure switch.
Photo 9
Photo 10
Low pressure switch (63L)
Solenoid valve coil
<Bypass valve>
fixing screw
Solenoid
valve coil
<Bypass valve>
(SV)
Bypass
valve
High pressure switch (63H)
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the high pressure switch, cover it with
a wet cloth to prevent it from heating (100°C or more),
then braze the pipes so that the inside of pipes are
not oxidized.
12. Removing the reactor (DCL1, DCL2) and capacitor (CE)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
<Removing the reactor>
(4) Remove 8 reactor fixing screws (4 ✕ 10) and remove the
reactor.
<Removing the capacitor>
(4) Remove 2 capacitor band fixing screws (4 ✕ 10) and
remove the capacitor.
w The reactor and capacitor is attached to the rear of the
electrical parts box.
Photo 11
Reactor
fixing
screws
Reactor
(DCL1, DCL2)
Four-way
valve
Electrical parts box
Reactor
fixing
screws
84
Capacitor (CE)
Capacitor band
fixing screws
OPERATING PROCEDURE
PHOTOS
13. Removing the motor for compressor (MC)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 2 front cover panel fixing screws (5 ✕ 10) and
remove the front cover panel. (See photo 3.)
(4) Remove 2 back cover panel fixing screws (5 ✕ 10) and
remove the back cover panel.
(5) Remove the electrical parts box. (See photo 3.)
(6) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball valve
and stop valve fixing screws (5 ✕ 16) and then remove the
valve bed.
(7) Remove 3 right side panel fixing screw (5 ✕ 10) in the rear
of the unit and then remove the right side panel.
(8) Remove 3 separator fixing screws (4 ✕ 10) and remove
the separator.
(9) Collect the refrigerant.
(10) Remove the 3 points of the motor for compressor fixing
nut using a spanner or a monkey wrench.
(11) Remove the welded pipe of motor for compressor inlet
and outlet and then remove the compressor.
Note: Collect refrigerant without spreading it in the air.
Photo 12
Power
receiver
Valve bed
Valve bed
fixing
screws
Separator
Motor for
compressor
(MC)
Separator
fixing screw
Compressor
fixing nut
14. Removing the power receiver
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 2 front cover panel fixing screws (5 ✕ 10) and
remove the front cover panel. (See photo 3.)
(4) Remove 2 back cover panel fixing screws (5 ✕ 10) and
remove the back cover panel.
(5) Remove the electrical parts box. (See photo 3.)
(6) Remove 3 right side panel fixing screw (5 ✕ 10) in the
rear of the unit and then remove the right side panel.
(7) Collect the refrigerant.
(8) Remove 4 welded pipes of power receiver inlet and outlet.
(9) Remove 2 receiver leg fixing screws (4 ✕ 10).
Note: Collect refrigerant without spreading it in the air.
Photo 13
Power
receiver
Inlet
Separator
Outlet
Four-way
valve
85
PUHZ-RP4VHA1 PUHZ-RP5VHA1 PUHZ-RP6VHA1
OPERATING PROCEDURE
1. Removing the service panel and top panel
(1) Remove 3 service panel fixing screws (5 ✕ 10) and slide
the hook on the right downward to remove the service
panel.
(2) Remove screws (3 for front, 3 for rear/5 ✕ 10) of the top
panel and remove it.
2. Removing the fan motor (MF1, MF2)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 5 fan grille fixing screws (5 ✕ 10) to detach the
fan grille. (See figure 1.)
(4) Remove a nut (for right handed screw of M6) to detach
the propeller. (See photo 1.)
(5) Disconnect the connectors, FAN11, FAN12, FAN21 and
FAN 22 on controller circuit board in electrical parts box.
(6) Remove 4 fan motor fixing screws (5 ✕ 25) to detach the
fan motor. (See photo 2.)
Figure 1
Grille
fixing
screws
Grille
fixing
screws
Photo 1
Nut
PHOTOS & ILLUSTRATION
Top panel fixing screws
Slide
Front panel
Propeller
Photo 2
Fan motor fixing screws
Top panel
Service panel
Fan grille
Service panel
fixing screws
Fan
motor
3. Removing the electrical parts box
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the indoor/outdoor connecting wire from
terminal block.
(4) Remove all the following connectors from controller circuit board;
fan motor, linear expansion valve, thermistor <Outdoor pipe>,
thermistor <Discharge>, thermistor <Outdoor 2-phase pipe>,
thermistor <Outdoor>, thermistor <Heat sink>,
high pressure switch, low pressure switch,
solenoid valve coil <Four-way valve> and solenoid valve
coil <Bypass valve>. Then remove a screw (4 ✕ 8) from
the valve bad to remove the lead wire.
Pull out the disconnected wire from the electrical parts box.
<Diagram symbol in the connector housing>
(6) Remove an electrical parts box fixing screw (4 ✕ 10) and
detach the electrical parts box by pulling it upward. The
electrical parts box is fixed with 2 hooks on the left and 1
hook on the right.
Photo 3
Controller circuit board
(C.B.)
Screw
Cover panel fixing screws
Fan motor fixing screws
Electrical
parts box
Electrical parts
box fixing screw
Terminal block
(TB1)
Valve bed
Motor for
compressor
(MC)
Terminal cover
Cover panel
(Front)
86
OPERATING PROCEDUREPHOTOS
4. Removing the thermistor <Outdoor 2-phase pipe> (TH6)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the connectors, TH6 and TH7 (red), on the
controller circuit board in the electrical parts box.
(4) Loosen the clamp for the lead wire in the rear of the
electrical parts box.
(5) Pull out the thermistor <Outdoor 2-phase pipe> (TH6)
from the sensor holder.
Note: In case of replacing thermistor <Outdoor 2-phase pipe>
(TH6), replace it together with thermistor <Outdoor>
(TH7) since they are combined together. Refer to No.5
below to remove thermistor <Outdoor>.
5. Removing the thermistor <Outdoor> (TH7)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the connector TH7 (red) on the controller circuit
board in the electrical parts box.
(4) Loosen the clamp for the lead wire in the rear of the
electrical parts box. (See photo 4.)
(5) Pull out the thermistor <Outdoor> (TH7) from the sensor
holder.
Photo 4
Controller
circuit board
(C.B.)
Photo 5
Electrical
parts box
Thermistor
<Outdoor 2-phase pipe>
(TH6)
Clamp
Note: In case of replacing thermistor <Outdoor> (TH7),
replace it together with thermistor <Outdoor 2-phase
pipe> (TH6), since they are combined together. Refer to
No.4 above to remove thermistor <Outdoor 2-phase pipe>.
6. Removing the thermistor <Outdoor pipe> (TH3) and
thermistor <Discharge> (TH4)
(1) Remove the service panel. (See figure 1.)
(2) Disconnect the connectors, TH3 (white) and TH4 (white),
on the controller circuit board in the electrical parts box.
(3) Loosen the clamp for the lead wire in the rear of the
electrical parts box. (See photo 4.)
(4) Pull out the thermistor <Outdoor pipe> (TH3) and
thermistor <Discharge> (TH4) from the sensor holder.
Thermistor
<Outdoor>
(TH7)
Photo 6
Thermistor
<Discharge>
(TH4)
Sensor holder
Thermistor
<Outdoor pipe>
(TH3)
87
Motor for
compressor
(MC)
OPERATING PROCEDURE
PHOTOS
7. Removing the solenoid valve coil <Four-way valve> (21S4),
and linear expansion valve coil (LEV(A), LEV(B))
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
[Removing the solenoid valve coil <Four-way valve>]
(4) Remove the solenoid valve coil <Four-way valve> by
sliding the coil toward you.
(5) Disconnect the connector 21S4 (green) on the controller
circuit board in the electrical parts box.
[Removing the linear expansion valve coil]
(3) Remove the linear expansion valve coil by sliding the coil
upward.
(4) Disconnect the connectors, LEV A(white) and LEV B (red),
on the controller circuit board in the electrical parts box.
8. Removing the four-way valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball
valve and stop valve fixing screws (5 ✕ 16) and then
remove the valve bed.
(4) Remove 4 right side panel fixing screw (5 ✕ 10) in the
rear of the unit and then remove the right side panel.
(5) Remove the solenoid valve coil <Four-way valve>.
(See photo 7.)
(6) Collect the refrigerant.
(7) Remove the welded part of four-way valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the four-way valve, cover it with a wet
cloth to prevent it from heating (120°C or more),
then braze the pipes so that the inside of pipes are
not oxidized.
9. Removing linear expansion valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball
valve and stop valve fixing screws (5 ✕ 16) and then
remove the valve bed.
(4) Remove 4 right side panel fixing screw (5 ✕ 10) in the
rear of the unit and then remove the right side panel.
(5) Remove the linear expansion valve. (See photo 7.)
(6) Collect the refrigerant.
(7) Remove the welded part of linear expansion valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the linear expansion valve, cover it
with a wet cloth to prevent it from heating (120°C or
more), then braze the pipes so that the inside of pipes are not oxidized.
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 right side panel fixing screws (5 ✕ 10) in the
rear of the unit and remove the right side panel.
(4) Remove the bypass valve solenoid coil fixing screw
(M4 ✕ 6).
(5) Remove the solenoid valve coil <Bypass valve> by
sliding the coil upward.
(6) Disconnect the connector SV2 (blue) on the controller
circuit board in the electrical parts box.
(7) Collect the refrigerant.
(8) Remove the welded part of bypass valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
11. Removing the high pressure switch (63H) and
low pressure switch (63L)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 right side panel fixing screws (5 ✕ 10) in the
rear of the unit and remove the right side panel.
(4) Pull out the lead wire of high pressure switch and low
pressure switch.
(5) Collect the refrigerant.
(6) Remove the welded part of high pressure switch and low
pressure switch.
Photo 9
Four-way
valve
Solenoid valve coil
<Bypass valve>
fixing screw
Photo 10
High pressure switch (63H)
Solenoid
valve coil
<Bypass valve>
(SV)
Bypass
valve
Four-way
valve
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by removing
the right side panel.
Note 3: When installing the high pressure switch, cover it with
a wet cloth to prevent it from heating (100°C or more),
then braze the pipes so that the inside of pipes are
not oxidized.
12. Removing the reactor (DCL) and capacitor (CE)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
<Removing the reactor>
(4) Remove 4 reactor fixing screws (4 ✕ 10) and remove the
reactor.
<Removing the capacitor>
(4) Remove 2 capacitor band fixing screws (4 ✕ 10) and
remove the capacitor.
w The reactor and capacitor is attached to the rear of the
electrical parts box.
Photo 11
Reactor
fixing
screws
Reactor
(DCL)
Low pressure
switch (63L)
Electrical parts box
Reactor
fixing
screws
89
Capacitor (CE)
Capacitor band
fixing screws
OPERATING PROCEDURE
PHOTOS
13. Removing the motor for compressor (MC)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 2 front cover panel fixing screws (5 ✕ 10) and
remove the front cover panel. (See photo 3.)
(4) Remove 2 back cover panel fixing screws (5 ✕ 10) and
remove the back cover panel.
(5) Remove the electrical parts box. (See photo 3.)
(6) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball valve
and stop valve fixing screws (5 ✕ 16) and then remove the
valve bed.
(7) Remove 3 right side panel fixing screw (5 ✕ 10) in the rear
of the unit and then remove the right side panel.
(8) Remove 3 separator fixing screws (4 ✕ 10) and remove
the separator.
(9) Collect the refrigerant.
(10) Remove the 3 points of the motor for compressor fixing
nut using a spanner or a monkey wrench.
(11) Remove the welded pipe of motor for compressor inlet
and outlet and then remove the compressor.
Note: Collect refrigerant without spreading it in the air.
Photo 12
Valve bed
Separator
Separator
fixing screw
Valve bed
fixing
screws
Power
receiver
Motor for
compressor
(MC)
Compressor
fixing nut
14. Removing the power receiver
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 2 front cover panel fixing screws (5 ✕ 10) and
remove the front cover panel. (See photo 3.)
(4) Remove 2 back cover panel fixing screws (5 ✕ 10) and
remove the back cover panel.
(5) Remove the electrical parts box. (See photo 3.)
(6) Remove 3 valve bed fixing screws (4 ✕ 10) and 4 ball valve
and stop valve fixing screws (5 ✕ 16) and then remove the
valve bed.
(7) Remove 3 right side panel fixing screw (5 ✕ 10) in the
rear of the unit and then remove the right side panel.
(8) Collect the refrigerant.
(9) Remove 4 welded pipes of power receiver inlet and outlet.
(10) Remove 2 receiver leg fixing screws (4 ✕ 10).
Note: Collect refrigerant without spreading it in the air.
GRILLE
FRONT PANEL
BASE ASSY
SEPARATOR
SERVICE PANEL
SERVICE PANEL
BACK PANEL
MOTOR SUPPORT
CONDENSER NET
TOP PANEL
LABEL (MITSUBISHI)
LABEL (INVERTER)
F.ST SCREW
F.ST SCREW
SIDE PANEL (L)
FAN GRILLE
FRONT PANEL
SEPARATOR
BASE ASSY
MOTOR SUPPORT
VALVE BED ASSY
HANDLE
COVER PANEL (FRONT)
COVER PANEL (REAR)
SIDE PANEL (R)
SERVICE PANEL
LABEL (MITSUBISHI)
LABEL (INVERTER)
REAR GUARD
TOP PANEL
HANDLE
STRUCTURAL PARTS
PUHZ-RP4VHA
PUHZ-RP4VHA1
PUHZ-RP5VHA
PUHZ-RP5VHA1
PUHZ-RP6VHA
PUHZ-RP6VHA1
3
17
1
2
18
16
15
141213
9
No.
10
11
12
13
14
15
16
17
18
Part No.Part Name
1
2
R01 E02 662
3
T7W E02 691
4
T7W E02 667
5
6
R01 E14 686
7
R01 E07 130
8
9
R01 30L 655
R01 E00 658
R01 E01 658
R01 E04 661
T7W E03 668
R01 E01 698
R01 E04 641
R01 E00 655
—
—
—
—
—
F.ST SCREW
SIDE PANEL (L)
FAN GRILLE
FRONT PANEL
SEPARATOR
BASE ASSY
MOTOR SUPPORT
VALVE BED ASSY
HANDLE
COVER PANEL (FRONT)
COVER PANEL (REAR)
SIDE PANEL (R)
SERVICE PANEL
LABEL (MITSUBISHI)
LABEL (INVERTER)
REAR GUARD
TOP PANEL
HANDLE