Mitsubishi PUHZ-RP35VHA2, PUHZ-RP50VHA2, PUHZ-RP60VHA2, PUHZ-RP571VHA2, PUHZ-RP100VHA2 SERVICE MANUAL

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL DATA BOOK
R410A
April 2008
No. OCS05
REVISED EDITION-E
<Indoor unit>
[Model names]
<Outdoor unit>
[Model names]
INVERTER
PLA-RP·BA(2) PLA-RP·AA(2) PEAD-RP·EA(2) PEAD-RP·GA PEA-RP·GA PKA-RP·GAL PKA-RP·FAL(2) PCA-RP·GA(2) PCA-RP·HA PSA-RP·GA
PUHZ-RP35/50/60/71/100/125/140VHA2 PUHZ-RP35/50/60/71/100VHA3 PUHZ-RP100/125/140YHA2 PUHZ-RP100YHA3 PUHZ-RP200/250YHA2
Revision:
• PLA-RP·BA2 and PUHZ­RP·HA3 are added in REVISED EDITION-E.
• Some descriptions have been modified.
• Please void OCS05 REVISED
EDITION-D.
kW Model
CONTENTS
1. REFERENCE SERVICE MANUAL·············································2
2. SPECIFICATIONS ······································································3
3. OUTLINES AND DIMENSIONS················································30
4. WIRING DIAGRAM···································································54
5. REFRIGERANT SYSTEM DIAGRAM ······································75
6. PERFORMANCE CURVES ······················································80
7. CORRECTION FACTORS ························································82
9. AIR FLOW DATA ······································································92
10. NOISE CRITERION CURVES·················································111
11. OPTIONAL PARTS···································································124
For information on service, please refer to the service manual as follows.
Model name Service Ref. Service
Manual No.
PLA-RP35/50/60/71AA
PLA-RP35/50/60/71/100/125/140BA PLA-RP71/100/125BA2
PLA-RP35/50/60/71/100/125/140BA
(1).UK
PLA-RP71/100/125BA2.UK
PLA-RP35/50/60/71/100/125/140BA
PLA-RP35/50/60/71AA.UK
PLA-RP35/50/60/71AA
OC335
OCH412 OCB412
OCH416 OCB416
OC327
PLA-RP100/125/140AA2
OC357
PLA-RP100/125/140AA2.UK
PCA-RP50/60/71/100/125/140GA PCA-RP50/60/71/100/125/140GA
OC328
PCA-RP50GA2
PCA-RP50GA2
PCA-RP71/125HA PCA-RP71/125HA
OC329
PKA-RP35/50GAL PKA-RP35/50GAL
OC330
PKA-RP60/71/100FAL PKA-RP50FAL2
PKA-RP60/71/100FAL PKA-RP50FAL2
OC331
PSA-RP71/100/125/140GA PSA-RP71/100/125/140GA
OC332
PEAD-RP50/60/71/125/140EA
PEAD-RP50/60/71/125/140EA.UK
HWE05210
PEAD-RP35/100EA2
PEAD-RP35/100EA2.UK
PEAD-RP60/71/100GA PEAD-RP60/71/100GA.UK
HWE05060
PEA-RP200/250/400/500GA PEA-RP200/250/400/500GA.TH-AF
PEA-RP200/250GA.TH-AFMF
HWE0708A
1-2. OUTDOOR UNIT
Model name Service Ref. Service
Manual No.
PUHZ-RP35/50/60/71VHA2 PUHZ-RP100/125/140VHA2 PUHZ-RP100/125/140YHA2 PUHZ-RP35/50/60/71/100VHA3 PUHZ-RP100YHA3
PUHZ-RP35/50/60/71VHA2
(1)
PUHZ-RP100/125/140VHA2(1) PUHZ-RP100/125/140YHA2(1) PUHZ-RP35/50/60/71/100VHA3 PUHZ-RP100YHA3 PUHZ-RP60/71/100VHA3#1 PUHZ-RP100YHA3#1 PUHZ-RP125/140VHA2#2 PUHZ-RP125/140YHA2#2
OC374
OCH428 OCB428
PUHZ-RP200/250YHA2
PUHZ-RP200/250YHA2
1-1. INDOOR UNIT
1
REFERENCE SERVICE MANUAL
2
2
Model name Indoor unit PLA-RP35BA PLA-RP50BA
Outdoor unit PUHZ-RP35VHA2 PUHZ-RP50VHA2
PUHZ-RP35VHA3 PUHZ-RP50VHA3
Cooling Capacity Btu/h 12,300 17,100
kW 3.6(1.6-4.5) 5.0(2.3-5.6)
Total input kW 1.07 1.55
EER 3.36 3.23 Energy label class
AA
SHF 0.84 0.81
Heating Capacity Btu/h 14,000 20,500
kW 4.1(1.6-5.2) 6.0(2.5-7.3)
Total input kW 1.12 1.66
COP 3.66 3.61
Energy label class A A
Booster heater kW ––
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16
Indoor unit Air flow CMM 11-12-13-15 12-14-16-18
(Low-Medium2-Medium1-High)
CFM 390-425-460-530 425-495-565-635
External pressure Pa 0 0
Sound level
dB(A) 27-28-29-31 28-29-31-32
(Low-Medium2-Medium1-High)
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/8)
Weight kg 22(6)
Unit (Panel) lbs 49(13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 35
CFM 1,240
Sound level at cooling
dB(A) 44
Sound level at heating
dB(A) 46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800
D : mm 300+23
H : mm 600
W : inch 31-1/2
D : inch 11-13/16 + 7/8
H : inch 23-5/8
Weight kg 45(VHA2)/42(VHA3)
lbs 99(VHA2)/92(VHA3)
Refrigerant pipe size Gas side O.D. mm 12.7
inch 1/2
Liquid side O.D. mm 6.35
inch 1/4
Refrigerant pipe length
Height difference
m Max. 30
Length
m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C w
Heating
Upper limit
D.B. 28˚C
D.B. 21˚C, W.B. 15˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data are based on the indicated voltage.
w If optional air protect guide installed. D.B.-15:
Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz
Outdoor unit
3. Guaranteed voltage 198~264V, 50Hz
SPECIFICATIONS
2-1. CEILING CASSETTE TYPE
3
Model name Indoor unit PLA-RP60BA PLA-RP71BA
Outdoor unit PUHZ-RP60VHA2
PUHZ-RP60VHA3
PUHZ-RP71VHA2
Cooling Capacity Btu/h 20,500 24,200
kW 6.0(2.7-6.7) 7.1(3.3-8.1)
Total input kW 1.65 2.12
EER 3.64 3.35
Energy label class A A
SHF 0.76 0.73
Heating Capacity Btu/h 23,900 27,300
kW 7.0(2.8-8.2) 8.0(3.5-10.2)
Total input kW 1.85 2.21
COP 3.78 3.61
Energy label class A A
Booster heater kW ––
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 25
Indoor unit Air flow CMM 12-14-16-18 14-16-18-21
(Low-Medium2-Medium1-High)
CFM 425-495-565-635 495-565-635-740
External pressure Pa 0 0
Sound level (Low-Medium2-Medium1-High)
dB(A) 28-29-31-32 28-30-32-34
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/8)
Weight kg 23(6)
Unit (Panel) lbs 51(13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 55
CFM 1,940
Sound level at cooling
Sound level at heating
dB(A) 47
dB(A) 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8
Weight kg 75(VHA2)/68(VHA3)
lbs 165(VHA2)/150(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit Upper limit
Heating
Lower limit
Height difference
Length
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
m Max. 30
m Max. 50
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
4
Model name Indoor unit PLA-RP71BA2 PLA-RP125BA2
Outdoor unit PUHZ-RP71VHA3 PUHZ-RP125VHA2
Cooling Capacity Btu/h 24,200 42,700
kW 7.1(3.3-8.1) 12.5(5.5-14.0)
Total input kW 1.94 3.73
EER 3.66 3.35
Energy label class A A
SHF 0.73 0.71
Heating Capacity Btu/h 27,300 47,800
kW 8.0(3.5-10.2) 14.0(5.0-16.0)
Total input kW 1.90 3.51
COP 4.21
PLA-RP100BA2
PUHZ-RP100VHA3
34,100
10.0(4.9-11.4)
2.44
4.10
A
0.74
38,200
11.2(4.5-14.0)
2.54
4.41 3.99
Energy label class A A
Booster heater kW ––A–
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 3225
Indoor unit Air flow CMM 14-16-18-21 22-25-28-31
(Low-Medium2-Medium1-High)
CFM 495-565-635-740 780-880-990-1090
External pressure Pa 0 0
Sound level (Low-Medium2-Medium1-High)
dB(A) 28-30-32-34
20-23-26-30
710-810-920-1060
0
32-34-37-40 34-36-39-41
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (35) 298 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/8) 11-3/4 (1-3/8)
Weight kg
Unit (Panel) lbs
23(6)
51(13)
27(6)
60(13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling
Sound level at heating
dB(A) 47 50
dB(A) 48
55
1,940
49
51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943 1,350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8 53-1/8
Weight kg 68 116
lbs 150 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Upper limit Lower limit Upper limit Lower limit
Height difference
Length
Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
m Max. 30
m Max. 75Max. 50
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
5
Model name Indoor unit PLA-RP100BA PLA-RP125BA PLA-RP140BA
Outdoor unit PUHZ-RP100VHA2 PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.02 3.87 4.65
EER 3.31 3.23 3.01
Energy label class A A B
SHF 0.74 0.71 0.71
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.10 3.88 4.43
COP 3.61 3.61 3.61
Energy label class A A A
Booster heater kW –––
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32
Indoor unit Air flow CMM 20-23-26-30 22-25-28-31
(Low-Medium2-Medium1-High)
CFM 710-810-920-1060 780-880-990-1090
External pressure Pa 0 0
Sound level (Low-Medium2-Medium1-High)
dB(A) 32-34-37-40 34-36-39-41
40
24-26-29-32
850-920-1020-1130
0
36-39-42-44
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/8)
Weight kg 27(6)
Unit (Panel) lbs 60(13)
25(6)
55(13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling
Sound level at heating
dB(A) 49 50
dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121 116
lbs 267 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Upper limit Lower limit Upper limit Lower limit
Height difference
Length
Indoor Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
m Max. 30
m Max. 75
D.B. 46:
D.B. 21:, W.B. 15:
D.B. -20:, W.B. -20:
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
6
Model name Indoor unit PLA-RP100BA PLA-RP125BA PLA-RP140BA
Outdoor unit PUHZ-RP100YHA2 PUHZ-RP125YHA2 PUHZ-RP140YHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.02 3.87 4.65
EER 3.31 3.23 3.01 Energy label class
AAB
SHF 0.74 0.71 0.71
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.10 3.88 4.43
COP 3.61 3.61 3.61 Energy label class
AAA
Booster heater kW –––
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 20-23-26-30 22-25-28-31
(Low-Medium2-Medium1-High)
CFM 710-810-920-1060 780-880-990-1090
External pressure Pa 0 0
Sound level (Low-Medium2-Medium1-High)
dB(A) 32-34-37-40 34-36-39-41
24-26-29-32
850-920-1020-1130
0
36-39-42-44
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/8)
Weight kg 27 (6)
Unit (Panel) lbs 60 (13)
25 (6)
55 (13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling
Sound level at heating
dB(A) 49 50
dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135 130
lbs 298 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit Lower limit Upper limit Lower limit
m Max. 30
m Max. 75
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C
3. Guaranteed voltage Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
7
Model name Indoor unit PLA-RP100BA2 PLA-RP125BA2
Outdoor unit PUHZ-RP100YHA3 PUHZ-RP125YHA2
Cooling Capacity Btu/h 34,100 42,700
kW 10.0(4.9-11.4) 12.5(5.5-14.0)
Total input kW 2.50 3.79
EER 4.00 3.30 Energy label class
AA
SHF 0.74 0.71
Heating Capacity Btu/h 38,200 47,800
kW 11.2(4.5-14.0) 14.0(5.0-16.0)
Total input kW 2.60 3.57
COP 4.31 3.92 Energy label class
AA
Booster heater kW ––
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 20-23-26-30 22-25-28-31
(Low-Medium2-Medium1-High)
CFM 710-810-920-1060 780-880-990-1090
External pressure Pa 0 0
Sound level (Low-Medium2-Medium1-High)
dB(A) 32-34-37-40 34-36-39-41
External finish (Panel) White Munsell 6.4Y 8.9/0.4
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (35)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/8)
Weight kg 27 (6)
Unit (Panel) lbs 60 (13)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling
Sound level at heating
dB(A) 49 50
dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 130
lbs 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit Lower limit Upper limit Lower limit
m Max. 30
m Max. 75
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C
3. Guaranteed voltage Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
8
Model name Indoor unit PLA-RP35AA PLA-RP50AA
Outdoor unit PUHZ-RP35VHA2 PUHZ-RP50VHA2
Cooling Capacity Btu/h 12,300 17,100
kW 3.6(1.6-4.5) 5.0(2.3-5.6)
Total input kW 1.07 1.55
EER 3.36 3.23
Energy label class A A
SHF 0.89 0.86
Heating Capacity Btu/h 14,000 20,500
kW 4.1(1.6-5.2) 6.0(2.5-7.3)
Total input kW 1.12 1.62
COP 3.66 3.70
Energy label class A A
Booster heater kW - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16
Indoor unit Air flow CMM 11-12-13-14 14-15-16-18
(Low-Medium2-Medium1-High) CFM 390-425-460-495 495-530-565-635
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 27-28-29-31 28-29-31-33
External finish (Panel) White Munsell 0.70Y 8.59/0.97
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/16)
Weight kg 24 (5)
Unit (Panel) lbs 53 (11)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 35
CFM 1,240
Sound level at cooling dB(A) 44
Sound level at heating dB(A) 46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800
D : mm 300+23
H : mm 600
W : inch 31-1/2
D : inch 11-13/16 + 7/8
H : inch 23-5/8
Weight kg 45
lbs 99
Refrigerant pipe size Gas side O.D. mm 12.7
inch 1/2
Liquid side O.D. mm 6.35
inch 1/4
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
9
Model name Indoor unit PLA-RP60AA PLA-RP71AA
Outdoor unit PUHZ-RP60VHA2 PUHZ-RP71VHA2
Cooling Capacity Btu/h 20,500 24,200
kW 6.0(2.7-6.7) 7.1(3.3-8.1)
Total input kW 1.65 1.97
EER 3.64 3.60
Energy label class A A
SHF 0.78 0.74
Heating Capacity Btu/h 23,900 27,300
kW 7.0(2.8-8.2) 8.0(3.5-10.2)
Total input kW 1.85 2.34
COP 3.78 3.42
Energy label class A B
Booster heater kW - -
Power supply Phase
[
1
Cycle Hz 50
Voltage V 230
Breaker size A 25
Indoor unit Air flow CMM 14-15-16-18 15-16-18-20
(Low-Medium2-Medium1-High) CFM 495-530-565-635 530-565-635-705
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 28-29-31-33 28-30-32-34
External finish (Panel) White Munsell 0.70Y 8.59/0.97
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 10-3/16 (1-3/16)
Weight kg 24 (5)
Unit (Panel) lbs 53 (11)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 55
CFM 1,940
Sound level at cooling dB(A) 47
Sound level at heating dB(A) 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8
Weight kg 75
lbs 165
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
10
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
Outdoor unit PUHZ-RP100VHA2 PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.02 3.87 4.65
EER 3.31 3.23 3.01
Energy label class A A B
SHF 0.78 0.74 0.71
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.02 3.88 4.69
COP 3.61 3.61 3.41
Energy label class A A B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32 40
Indoor unit Air flow CMM 19-21-23-27 24-25-27-30
(Low-Medium2-Medium1-High)
CFM 670-740-810-950 850-880-950-1060
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 33-36-39-41 37-40-43-45
External finish (Panel) White Munsell 0.70Y 8.59/0.97
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/16)
Weight kg 32 (5)
Unit (Panel) lbs 71 (11)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121 116
lbs 267 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -20:, W.B. -20:
11
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
Outdoor unit PUHZ-RP100YHA2 PUHZ-RP125YHA2 PUHZ-RP140YHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.02 3.87 4.65
EER 3.31 3.23 3.01
Energy label class A A B
SHF 0.78 0.74 0.71
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.02 3.88 4.69
COP 3.61 3.61 3.41
Energy label class A A B
Booster heater kW - - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 19-21-23-27 24-25-27-30
(Low-Medium2-Medium1-High)
CFM 670-740-810-950 850-880-950-1060
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 33-36-39-41 37-40-43-45
External finish (Panel) White Munsell 0.70Y 8.59/0.97
Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8)
H : inch 11-3/4 (1-3/16)
Weight kg 32 (5)
Unit (Panel) lbs 71 (11)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135 130
lbs 298 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C
12
3. Guaranteed voltage Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
2-2. CEILING-CONCEALED TYPE
Model name Indoor unit PEAD-RP35EA2 PEAD-RP50EA
Outdoor unit PUHZ-RP35VHA2 PUHZ-RP50VHA2
PUHZ-RP35VHA3 PUHZ-RP50VHA3
Cooling Capacity Btu/h 12,300 16,700
kW 3.6(1.6-4.5) 4.9(2.3-5.6)
Total input kW 1.12 1.52
EER 3.21 3.22
Energy label class A A
SHF 0.89 0.82
Heating Capacity Btu/h 14,000 20,500
kW 4.1(1.6-5.2) 6.0(2.5-7.3)
Total input kW 1.20 1.65
COP 3.41 3.64
Energy label class B A
Booster heater kW - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16
Indoor unit Air flow CMM 13.5-17
(Low-High) CFM 476-600
External pressure Pa 30(70)
Sound level dB(A) 36-40
(Low-High) (70Pa : 38-44)
External finish Galvanized sheets
Dimension W : mm 935
D : mm 700
H : mm 295
W : inch 36-13/16
D : inch 27-5/8
H : inch 11-5/8
Weight kg 33 35
lbs 73 77
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 35
CFM 1,240
Sound level at cooling dB(A) 44
Sound level at heating dB(A) 46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800
D : mm 300+23
H : mm 600
W : inch 31-1/2
D : inch 11-13/16 + 7/8
H : inch 23-5/8
Weight kg 45(VHA2)/42(VHA3)
lbs 99(VHA2)/92(VHA3)
Refrigerant pipe size Gas side O.D. mm 12.7
inch 1/2
Liquid side O.D. mm 6.35
inch 1/4
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
13
Model name Indoor unit PEAD-RP60EA PEAD-RP71EA
Outdoor unit PUHZ-RP60VHA2 PUHZ-RP71VHA2
PUHZ-RP60VHA3 PUHZ-RP71VHA3
Cooling Capacity Btu/h 20,500 24,200
kW 6.0(2.7-6.7) 7.1(3.3-8.1)
Total input kW 1.86 2.15
EER 3.23 3.30
Energy label class A A
SHF 0.79 0.83
Heating Capacity Btu/h 23,900 27,300
kW 7.0(2.8-8.2) 8.0(3.5-10.2)
Total input kW 1.90 2.34
COP 3.68 3.42
Energy label class A B
Booster heater kW - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 25
Indoor unit Air flow CMM 17-21 20-25
(Low-High) CFM 600-741 706-883
External pressure Pa 30(70) 70(130)
Sound level dB(A) 37-41 37-41
(Low-High) (70Pa : 39-46) (130Pa : 40-45)
External finish Galvanized sheets
Dimension W : mm 1175
D : mm 700 740
H : mm 295
325
W : inch 46-1/8
D : inch 27-5/8 29-1/8
H : inch 11-5/8
12-13/16
Weight kg 42 44
lbs 92 97
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 55 55
CFM 1,940 1,940
Sound level at cooling dB(A) 47 47
Sound level at heating dB(A) 48 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950 950
D : mm 330+30 330+30
H : mm 943 943
W : inch 37-3/8 37-3/8
D : inch 13 + 1-3/16 13 + 1-3/16
H : inch 37-1/8 37-1/8
Weight kg 75(VHA2)/68(VHA3)
lbs 165(VHA2)/150(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88 15.88
inch 5/8 5/8
Liquid side O.D. mm 9.52 9.52
inch 3/8 3/8
Refrigerant pipe length Height difference m Max. 30 Max. 30
Length m Max. 50 Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
14
Model name Indoor unit PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
Outdoor unit PUHZ-RP100VHA2
PUHZ-RP100VHA3
PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.06 3.89 4.65
EER 3.27 3.21 3.01
Energy label class A A B
SHF 0.86 0.82 0.83
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.19 3.88 4.69
COP 3.51 3.61 3.41
Energy label class B A B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32 40
Indoor unit Air flow CMM 33.5-42 36.5-46
(Low-High) CFM 1183-1483 1288-1624
External pressure Pa 70(130)
Sound level dB(A) 44-50 46-51
(Low-High) (130Pa : 46-52) (130Pa : 47-53)
External finish Galvanized sheets
Dimension W : mm 1415 1715
D : mm 740
H : mm 325
W : inch 55-11/16 67-1/2
D : inch 29-1/8
H : inch 12-13/16
Weight kg 65 70
lbs 143 154
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121(VHA2)/116(VHA3) 116
lbs 267(VHA2)/256(VHA3) 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -20:, W.B. -20:
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
15
Model name Indoor unit PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
Outdoor unit
PUHZ-RP100YHA2
PUHZ-RP100YHA3
PUHZ-RP125YHA2 PUHZ-RP140YHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 3.06 3.89 4.65
EER 3.27 3.21 3.01
Energy label class A A B
SHF 0.86 0.82 0.83
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.19 3.88 4.69
COP 3.51 3.61 3.41
Energy label class B A B
Booster heater kW - - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 33.5-42 36.5-46
(Low-High) CFM 1183-1483 1288-1624
External pressure Pa 70(130)
Sound level dB(A) 44-50 46-51
(Low-High) (130Pa : 46-52) (130Pa : 47-53)
External finish Galvanized sheets
Dimension W : mm 1415 1715
D : mm 740
H : mm 325
W : inch 55-11/16 67-1/2
D : inch 29-1/8
H : inch 12-13/16
Weight kg 65 70
lbs 143 154
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135(YHA2)/130(YHA3) 130
lbs 298(YHA2)/287(YHA3) 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C
3. Guaranteed voltage Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
16
Model name Indoor unit PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
Outdoor unit PUHZ-RP60VHA2 PUHZ-RP71VHA2 PUHZ-RP100VHA2
PUHZ-RP60VHA3 PUHZ-RP71VHA3 PUHZ-RP100VHA3
Cooling Capacity Btu/h 20,500 24,200 34,100
kW 6.0(2.7-6.7) 7.1(3.3-8.1) 10.0(4.9-11.4)
Total input kW 1.68 2.15 3.08
EER 3.57 3.30 3.25
Energy label class A A A
SHF 0.88 0.83 0.86
Heating Capacity Btu/h 23,900 27,300 38,200
kW 7.0(2.8-8.2) 8.0(3.5-10.2) 11.0(4.5-14.0)
Total input kW 1.77 2.34 3.23
COP 3.95 3.42 3.41
Energy label class A B B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 25 32
Indoor unit Air flow CMM 16.5-21 20-25 26.5-33
(Low-High) CFM 582-741 706-883 935-1165
External pressure Pa 10/50/70 10/50/70
Sound level dB(A) 33-37/35-40/36-42 35-38/37-41/37-43 40-43/42-45/42-46
(Low-High) (10/50/70Pa) (10/50/70Pa) (10/50/70Pa)
External finish Galvanized sheets
Dimension W : mm 1171 1411
D : mm 740
H : mm 275
W : inch 46-1/8 55-9/16
D : inch 29-1/8
H : inch 10-13/16
Weight kg 42 50
lbs 93 111
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 55 100
CFM 1,940 3,530
Sound level at cooling dB(A) 47 49
Sound level at heating dB(A) 48 51
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8 53-1/8
Weight kg 75(VHA2)/68(VHA3) 121(VHA2)/116(VHA3)
lbs 165(VHA2)/150(VHA3) 267(VHA2)/256(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30 Max. 30
Length m Max. 50 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C w2
17
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w1. If optional air protect guide installed. D.B.-15: w2. For RP100 D.B. -20:, W.B. -20:
Single phase 230V 50Hz
Model name Indoor unit PEAD-RP100GA
Outdoor unit PUHZ-RP100YHA2
PUHZ-RP100YHA3
Cooling Capacity Btu/h 34,100
kW 10.0(4.9-11.4)
Total input kW 3.08
EER 3.25
Energy label class A
SHF 0.86
Heating Capacity Btu/h 38,200
kW 11.0(4.5-14.0)
Total input kW 3.23
COP 3.41
Energy label class B
Booster heater kW -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 26.5-33
(Low-High) CFM 935-1165
External pressure Pa 10/50/70
Sound level dB(A) 40-43/42-45/42-46
(Low-High) (10/50/70Pa)
External finish Galvanized sheets
Dimension W : mm 1411
D : mm 740
H : mm 275
W : inch 55-9/16
D : inch 29-1/8
H : inch 10-13/16
Weight kg 50
lbs 111
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49
Sound level at heating dB(A) 51
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 943
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135
(YHA2)/130(YHA3)
lbs 298(YHA2)/287(YHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C
18
3. Guaranteed voltage Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
Model name Indoor unit PEA-RP200GA PEA-RP250GA
Outdoor unit PUHZ-RP200YHA2 PUHZ-RP250YHA2
Cooling Capacity Btu/h 65,000 75,000
kW 19.0(9.0-22.4) 22.0(11.2-28.0)
Total input kW 6.70 8.34
EER
Energy label class
2.84 2.64
CD
SHF 0.81 0.86
Heating Capacity Btu/h 76,000 92,000
kW 22.4(9.5-25.0) 27.0(12.5-31.5)
Total input kW 6.50 8.20
COP 3.45 3.29
Energy label class B C
Booster heater kW - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A Indoor 15 / Outdoor 32
Indoor unit Air flow CMM 52-65 64-80
(Low-High) CFM 1835-2295 2260-2825
External pressure Pa 150
Sound level dB(A) 48-51 49-52
(Low-High)
External finish Galvanized steel
Dimension W : mm 16001400
D : mm 634
H : mm 400
W : inch 6355-1/8
D : inch 25
H : inch 15-3/4
Weight kg 70 77
lbs 155 170
Unit drain pipe R1
Outdoor unit Air flow CMM 130
CFM 4590
Sound level at cooling dB(A) 58
Sound level at heating dB(A) 59
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135
lbs 298
Refrigerant pipe size Gas side O.D. mm 25.4
inch 1
Liquid side O.D. mm 12.7
inch 1/2
9.52
3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 120
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C
3. Guaranteed voltage 342~457V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit 3 phase 400V 50Hz Outdoor unit
w1. If optional air protect guide is installed : D.B.-15:
3 phase 400V 50Hz
136
300
19
2-3. WALL MOUNTED TYPE
Model name Indoor unit PKA-RP35GAL PKA-RP50GAL
Outdoor unit PUHZ-RP35VHA2 PUHZ-RP50VHA2
PUHZ-RP35VHA3 PUHZ-RP50VHA3
Cooling Capacity Btu/h 12,300 15,700
kW 3.6(1.6-4.5) 4.6(2.3-5.4)
Total input kW 1.03 1.63
EER 3.50 2.82
Energy label class A C
SHF 0.84 0.74
Heating Capacity Btu/h 14,000 15,400
kW 4.1(1.6-5.2) 4.5(2.5-6.2)
Total input kW 1.27 1.40
COP 3.23 3.21
Energy label class C C
Booster heater kW - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16
Indoor unit Air flow CMM 9-10-11-12
(Low-Medium2-Medium1-High) CFM 320-355-390-425
External pressure Pa 0
Sound level
(Low-Medium2-Medium1-High)
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 990
Weight kg 16
Field drain pipe I.D. mm 20
Outdoor unit Air flow CMM 35
Sound level at cooling dB(A) 44
Sound level at heating dB(A) 46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800
Weight kg 45(VHA2)/42(VHA3)
Refrigerant pipe size Gas side O.D. mm 12.7
Liquid side O.D. mm 6.35
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
dB(A) 36-38-41-43
D : mm 235
H : mm 340
W : inch 39
D : inch 9-1/4
H : inch 13-3/8
lbs 35
inch 13/16
CFM 1,240
D : mm 300+23
H : mm 600
W : inch 31-1/2
D : inch 11-13/16 + 7/8
H : inch 23-5/8
lbs 99(VHA2)/92(VHA3)
inch 1/2
inch 1/4
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
20
Model name Indoor unit PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL
Outdoor unit PUHZ-RP60VHA2 PUHZ-RP71VHA2 PUHZ-RP100VHA2
Cooling Capacity Btu/h 20,500 24,200 34,100
kW 6.0(2.7-6.7) 7.1(3.3-8.1) 10.0(4.9-11.4)
Total input kW 1.55 1.98 2.93
EER 3.87 3.59 3.41
Energy label class A A A
SHF 0.83 0.77 0.77
Heating Capacity Btu/h 23,900 27,300 38,200
kW 7.0(2.8-8.2) 7.6(3.5-10.2) 11.2(4.5-14.0)
Total input kW 2.01 2.23 3.25
COP 3.48 3.41 3.45
Energy label class B B B
Booster heater kW - - -
Power supply
Phase
Cycle
[ 1
Hz 50
PKA-RP50FAL2
PUHZ-RP50VHA2
PUHZ-RP50VHA3
17,000
5.0(2.3-5.6)
1.66
3.01
B
0.86
20,500
6.0(2.5-7.3)
1.76
3.41
B
-
PUHZ-RP60VHA3 PUHZ-RP71VHA3 PUHZ-RP100VHA3
Voltage V 230
Breaker size A 25 32
Indoor unit Air flow CMM 15-20 22-28
(Low-High)
External pressure
Sound level
(Low-High)
CFM 530-705 780-990
Pa 0
dB(A) 39-45 41-46
16
15-20
530-705
39-45
External finish Munsell 3.4Y 7.7/0.8
Dimension W : mm 1400 1680
1400
D : mm 235
H : mm 340
W : inch 55-1/8 66-1/8
55-1/8
D : inch 9-1/4
H : inch 13-3/8
Weight kg 24 28
lbs 53 62
24
53
Field drain pipe I.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 55 100
CFM 1,940 3,530
Sound level at cooling
dB(A) 47 49
Sound level at heating dB(A) 48 51
35
1,240
44
46
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 943 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8 53-1/8
Weight kg 75(VHA2)/68(VHA3)
lbs 165(VHA2)/150(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30 Max. 30
Length m Max. 50 Max. 75
800
300+23
600
31-1/2
11 - 13/16
23-5/8
45(VHA2)/42(VHA3)
99(VHA2)/92(VHA3)
12.7
1/2
6.35
1/4
Max. 30
Max. 50
950
330+30
37-3/8
13 + 1-3/16
121(VHA2)/116(VHA3)
267(VHA2)/256(VHA3)
15.88
5/8
9.52
3/8
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C w2
21
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w1. If optional air protect guide installed. D.B.-15: w2. For RP100 D.B. -20:, W.B. -20:
Single phase 230V 50Hz
Model name Indoor unit PKA-RP100FAL
Outdoor unit PUHZ-RP100YHA2
PUHZ-RP100YHA3
Cooling Capacity Btu/h 34,100
kW 10.0(4.9-11.4)
Total input kW 2.93
EER 3.41
Energy label class A
SHF 0.77
Heating Capacity Btu/h 38,200
kW 11.2(4.5-14.0)
Total input kW 3.25
COP 3.45
Energy label class B
Booster heater kW -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 22-28
(Low-High) CFM 780-990
External pressure Pa 0
Sound level
(Low-High)
dB(A) 41-46
External finish Munsell 3.4Y 7.7/0.8
Dimension W : mm 1680
D : mm 235
H : mm 340
W : inch 66-1/8
D : inch 9-1/4
H : inch 13-3/8
Weight kg 28
lbs 62
Field drain pipe I.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49
Sound level at heating dB(A) 51
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135(YHA2)/130(YHA3)
lbs 298(YHA2)/287(YHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C
3. Guaranteed voltage Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
22
2-4. CEILING SUSPENDED TYPE
Model name Indoor unit PCA-RP50GA PCA-RP60GA PCA-RP71GA
Outdoor unit PUHZ-RP50VHA2 PUHZ-RP60VHA2 PUHZ-RP71VHA2
PUHZ-RP50VHA3 PUHZ-RP60VHA3 PUHZ-RP71VHA3
Cooling Capacity Btu/h 16,000 20,500 24,200
kW 4.7(2.3-5.4) 6.0(2.7-6.7) 7.1(3.3-8.1)
Total input kW 1.67 1.63 2.14
EER 2.81 3.68 3.32
Energy label class C A A
SHF 0.76 0.86 0.74
Heating Capacity Btu/h 18,800 23,900 27,300
kW 5.5(2.5-6.6) 7.0(2.8-8.2) 7.6(3.5-10.2)
Total input kW 1.71 2.03 2.23
COP 3.22 3.45 3.41
Energy label class C B B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 16 25
Indoor unit Air flow CMM 10-11-12-13 14-15-16-18
Outdoor unit Air flow CMM 35 55
Refrigerant pipe size Gas side O.D. mm 12.7 15.88
Refrigerant pipe length Height difference m Max. 30 Max. 30
(Low-Medium2-Medium1-High)
External pressure
Sound level (Low-Medium2-Medium1-High)
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 1000 1310
Weight kg 27 34
Field drain pipe O.D. mm 26
Sound level at cooling
Sound level at heating dB(A) 46 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 800 950
Weight kg 45
Liquid side O.D. mm 6.35 9.52
Length m Max. 50 Max. 50
CFM 355-390-425-460 495-530-565-635
Pa 0
dB(A) 37-38-40-42 37-39-41-43
D : mm 680
H : mm 210
W : inch 39-3/8 51-9/16
D : inch 26-3/4
H : inch 8-1/4
lbs 60 75
inch 1
CFM 1,240 1,940
dB(A) 44 47
D : mm
H : mm 600 943
W : inch 31-1/2 37-3/8
D : inch
H : inch 23-5/8 37-1/8
(VHA2)/42(VHA3) 75(VHA2)/68(VHA3)
lbs 99(VHA2)/92(VHA3) 165(VHA2)/150(VHA3)
inch 1/2 5/8
inch 1/4 3/8
PCA-RP50GA2
PUHZ-RP50VHA2
PUHZ-RP50VHA3
5.0(2.3-5.6)
6.0(2.5-7.3)
14-15-16-18
495-530-565-635
37-39-41-43
330+23
13 + 7/8
17,000
1.66
3.01
B
0.88
20,500
1.76
3.41
B
-
1310
51-9/16
34
75
330+30
13 + 1-3/16
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
23
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
Model name Indoor unit PCA-RP100GA PCA-RP125GA PCA-RP140GA
Outdoor unit PUHZ-RP100VHA2
PUHZ-RP100VHA3
PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 2.92 3.88 4.65
EER 3.42 3.22 3.01
Energy label class A A B
SHF 0.75 0.77 0.75
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.26 4.11 4.60
COP 3.44 3.41 3.48
Energy label class B B B
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32 40
Indoor unit Air flow CMM 20-21-23-25 27-30-32-34
(Low-Medium2-Medium1-High)
CFM 705-810-840-885 955-1060-1130-1200
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 40-41-43-45 41-43-45-46 42-44-46-48
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 1310 1620
D : mm 680
H : mm 270
W : inch 51-9/16 63-3/4
D : inch 26-3/4
H : inch 10-5/8
Weight kg 37 43 45
lbs829599
Field drain pipe O.D. mm 26
inch 1
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121(VHA2)/116(VHA3) 116
lbs 267(VHA2)/256(VHA3) 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -20:, W.B. -20:
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
24
Model name Indoor unit PCA-RP100GA PCA-RP125GA PCA-RP140GA
Outdoor unit PUHZ-RP100YHA2
PUHZ-RP100YHA3
PUHZ-RP125YHA2 PUHZ-RP140YHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3)
Total input kW 2.92 3.88 4.65
EER 3.42 3.22 3.01
Energy label class A A B
SHF 0.75 0.77 0.75
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.26 4.11 4.60
COP 3.44 3.41 3.48
Energy label class B B B
Booster heater kW - - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 20-21-23-25 27-30-32-34
(Low-Medium2-Medium1-High)
CFM 705-810-840-885 955-1060-1130-1200
External pressure Pa 0 0
Sound level
(Low-Medium2-Medium1-High)
dB(A) 40-41-43-45 41-43-45-46 42-44-46-48
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 1310 1620
D : mm 680
H : mm 270
W : inch 51-9/16 63-3/4
D : inch 26-3/4
H : inch 10-5/8
Weight kg 37 43 45
lbs 82 95 99
Field drain pipe O.D. mm 26
inch 1
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135(YHA2)/130(YHA3) 130
lbs 298(YHA2)/287(YHA3) 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C
3. Guaranteed voltage Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
25
Model name Indoor unit PCA-RP71HA PCA-RP125HA PCA-RP125HA
o
z
Outdoor unit PUHZ-RP71VHA2
PUHZ-RP71VHA3
PUHZ-RP125VHA2 PUHZ-RP125YHA2
Cooling Capacity Btu/h 24,200 42,700 42,700
kW 7.1(3.3-8.1) 12.5(5.5-14.0) 12.5(5.5-14.0)
Total input kW 2.21 3.88 3.88
EER 3.21 3.22 3.22
Energy label class A A A
SHF 0.74 0.77 0.77
Heating Capacity Btu/h 27,300 47,800 47,800
kW 7.6(3.5-10.2) 13.8(5.0-16.0) 13.8(5.0-16.0)
Total input kW 2.23 4.05 4.05
COP 3.41 3.41 3.41
Energy label class B B B
Booster heater kW - - -
Power supply Phase [ 13
Cycle Hz 50 50
Voltage V 230 400
Breaker size A 25 16
Indoor unit Air flow CMM 17-19 30-38
(Low-High) CFM 600-670 1060-1350
External pressure Pa 0 0
Sound level
(Low-High)
dB(A) 34-38 44-50
External finish Stainless steel
Dimension W : mm 1136 1520
D : mm 650
H : mm 280
W : inch 44-3/4 59-7/8
D : inch 25-5/8
H : inch 11
Weight kg 41 56
lbs 90 124
Field drain pipe O.D. mm 26
inch 1
Outdoor unit Air flow CMM 55 100
CFM 1,940 3,530
Sound level at cooling dB(A) 47 50
Sound level at heating dB(A) 48 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950 950
D : mm 330+30 330+30
H : mm 943 1350
W : inch 37-3/8 37-3/8
D : inch 13 + 1-3/16 13 + 1-3/16
H : inch 37-1/8 53-1/8
Weight kg 75(VHA2)/68(VHA3) 116 130
lbs 165(VHA2)/150(VHA3) 256 287
Refrigerant pipe size Gas side O.D. mm 15.88 15.88
inch 5/8 5/8
Liquid side O.D. mm 9.52 9.52
inch 3/8 3/8
Refrigerant pipe length Height difference m Max. 30 Max. 30
Length m Max. 50 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w1 D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C w2
3. Guaranteed voltage 198~264V, 50Hz (RP125Y : 342~457V, 50Hz)
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w1. If optional air protect guide installed. D.B.-15: w2. F
r RP125 D.B. -20:, W.B. -20:
V: Single phase 230V 50Hz
, Y: 3 phase 400V 50H
26
2-5. FLOOR STANDING TYPE
Model name Indoor unit PSA-RP71GA
Outdoor unit PUHZ-RP71VHA2
PUHZ-RP71VHA3
Cooling Capacity Btu/h 24,200
kW 7.1(3.3-8.1)
Total input kW 2.20
EER 3.23
Energy label class A
SHF 0.73
Heating Capacity Btu/h 27,300
kW 7.6(3.5-10.2)
Total input kW 2.23
COP 3.41
Energy label class B
Booster heater kW -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 25
Indoor unit Air flow CMM 15-18
(Low-High) CFM 530-635
External pressure Pa 0
Sound level
(Low-High)
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 600
Weight kg 43
Field drain pipe I.D. mm 20
Outdoor unit Air flow CMM 55
Sound level at cooling dB(A) 47
Sound level at heating dB(A) 48
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
Weight kg 75(VHA2)/68(VHA3)
Refrigerant pipe size Gas side O.D. mm 15.88
Liquid side O.D. mm 9.52
Refrigerant pipe length Height difference m Max. 30
Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
dB(A) 40-45
D : mm 270
H : mm 1900
W : inch 23-5/8
D : inch 10-5/8
H : inch 74-13/16
lbs 98
inch 13/16
CFM 1,940
D : mm 330+30
H : mm 943
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 37-1/8
lbs 165(VHA2)/150(VHA3)
inch 5/8
inch 3/8
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
27
Model name Indoor unit PSA-RP100GA PSA-RP125GA PSA-RP140GA
Outdoor unit PUHZ-RP100VHA2
PUHZ-RP100VHA3
PUHZ-RP125VHA2 PUHZ-RP140VHA2
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.4(5.5-14.0) 13.8(5.5-15.3)
Total input kW 2.99 4.12 4.91
EER 3.34 3.01 2.81
Energy label class A B C
SHF 0.81 0.75 0.74
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.28 4.11 4.97
COP 3.41 3.41 3.22
Energy label class B B C
Booster heater kW - - -
Power supply Phase [ 1
Cycle Hz 50
Voltage V 230
Breaker size A 32 40
Indoor unit Air flow CMM 24-31 26-33 27-35
(Low-High) CFM 850-1060 920-1165 955-1240
External pressure Pa 0
Sound level
(Low-High)
dB(A) 44-49 46-51 47-52
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 600
D : mm 350
H : mm 1900
W : inch 23-5/8
D : inch 13-3/4
H : inch 74-13/16
Weight kg 51 53
lbs 112 117
Field drain pipe I.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 121(VHA2)/116(VHA3) 116
lbs 267(VHA2)/256(VHA3) 256
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 28˚C D.B. 17˚C
Indoor Outdoor
D.B. 46:
D.B. 21:, W.B. 15: D.B. -20:, W.B. -20:
3. Guaranteed voltage 198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz Outdoor unit
w If optional air protect guide installed. D.B.-15:
Single phase 230V 50Hz
28
Model name Indoor unit PSA-RP100GA PSA-RP125GA PSA-RP140GA
Outdoor unit PUHZ-RP100YHA2
PUHZ-RP125YHA2 PUHZ-RP140YHA2
PUHZ-RP100YHA3
Cooling Capacity Btu/h 34,100 42,700 47,800
kW 10.0(4.9-11.4) 12.4(5.5-14.0) 13.8(5.5-15.3)
Total input kW 2.99 4.12 4.91
EER 3.34 3.01 2.81
Energy label class A B C
SHF 0.81 0.75 0.74
Heating Capacity Btu/h 38,200 47,800 54,600
kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0)
Total input kW 3.28 4.11 4.97
COP 3.41 3.41 3.22
Energy label class B B C
Booster heater kW - - -
Power supply Phase [ 3
Cycle Hz 50
Voltage V 400
Breaker size A 16
Indoor unit Air flow CMM 24-31 26-33 27-35
(Low-High) CFM 850-1060 920-1165 955-1240
External pressure Pa 0
Sound level
(Low-High)
dB(A) 44-49 46-51 47-52
External finish White Munsell 0.70Y 8.59/0.97
Dimension W : mm 600
D : mm 350
H : mm 1900
W : inch 23-5/8
D : inch 13-3/4
H : inch 74-13/16
Weight kg 51 51 53
lbs 112 112 117
Field drain pipe I.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 100
CFM 3,530
Sound level at cooling dB(A) 49 50
Sound level at heating dB(A) 51 52
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330+30
H : mm 1350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 135(YHA2)/130(YHA3) 130
lbs 298(YHA2)/287(YHA3) 287
Refrigerant pipe size Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant pipe length Height difference m Max. 30
Length m Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor : D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 28˚C D.B. 17˚C
D.B. 46˚C
D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C
3. Guaranteed voltage Indoor unit 198~264V, 50Hz
Outdoor unit
4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz
Outdoor unit
w If optional air protect guide installed. D.B.-15:
342~457V, 50Hz
3 phase 400V 50Hz
29
3
37728460
()
Ceiling hole
Branch duct hole
Drain pipe connected to VP-25
Ceiling
Grille
Drain hole
Models
Auto vane (Air outlet)
Air intake grille
Ceiling
Cut out hole
Cut out hole
Cut out hole
Burring hole pitch
Burring hole pitch
Burring hole
Burring hole
Power supply wire, Indoor unit/Outdoor unit connecting wire entry
Indoor unit/Outdoor connecting terminal
Indoor power supply terminal block(Option part)
Control wire entry
Air intake hole
Air intake hole
Air outlet hole
Air outlet hole
Connected the attached flexible pipe or socket.
Keep approximately 10 to 15mm space between unit ceiling and ceiling slab.
Branch duct hole
Fresh air intake hole
Ceiling hole
Suspension bolt pitch
Suspension bolt pitch
Remote controller terminal block
Suspension bolt M10 or W3/8
(7.5)(7.5)
605
+35
- 5
620
DEFROST/STAND BY lamp
Receiver
Operation lamp
In case of standard grille : PLP-6BA / PLP-6BAMD
In case of wireless remote controller : PLP-6BALM
Auto grille Air intake grille up/down discharge
Emergency operation switch<Cooling>and Emergency Up/Down switch<Up>
160
160
500
500
597
83 36
950
8336
950
597
A
17
+5
0
B35
190
156
105
140
50~70
160
840
150
90
C
D
840
187.5
20~45
860~910
20~45
810
20~45
860~910
20~45
24
160
ww
w
w
w
w
w
w
w
M
M
M
M
120
°
120
°
[175
[125
167
158
Vane motor
2
1
Drain pump clean hole and Drain emergency drainage hole
130
100
70°
155
350
90 100 100 90
BA CDE
241 258
80
87
74
400
298
85 77
440
281
2
1
Refrigerant pipe
···[6.35 Flared connection
···1/4 inch
Refrigerant pipe
···[9.52 Flared connection
···3/8 inch
Refrigerant pipe
···[12.7 Flared connection
···1/2 inch
Refrigerant pipe
···[15.88 Flared connection
···5/8 inch
Refrigerant pipe [6.35 / [9.52 Flared connection
1/4 inch/3/8 inch
(compatible)
PLA-RP35/50BA
PLA-RP60BA
PLA-RP71BA PLA-RP71BA2
PLA-RP100,125,140BA PLA-RP100,125BA2
Detail drawing of fresh air intake hole
Detail connecting of branch duct(Both aspects)
3-[2.8
14-[2.8
[150
[100
Emergency switch<Heating>and Emergency Up/Down switch<Down>
In case of auto-grille : PLP-6BAJ
Suspension bolt lower edge
170
w
Ceiling
Air intake grille
Max. 4.0m
L.L Filter
Ceiling
Grille
Indoor unit
1500mm or more
1000mm
or more
3000mm or more
1800mm or more
from floor
For high attachment
Indoor unit
Obstacle
Floor
Note 1. Please choose the grille from a standard grille, auto-grille.
2. As for drain pipe, please use VP-25(O.D. [32 PVC TUBE). Drain pump is included.
Max. lifting height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions w marked on the figure.
3) The optional high efficiency filter becomes optional multi-functional casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/water dew.)
8. As for necessary installation/service space, please refer to the left figure.
OUTLINES AND DIMENSIONS
INDOOR UNIT PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA
PLA-RP100BA PLA-RP125BA PLA-RP140BA PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2
Unit : mm
30