Mitsubishi Electronics PUHZ-RP250YHM-A User Manual

Page 1
OUTDOOR UNIT
PUHZ-RP250YHM-A
For use with R410A
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
GB
Page 2
5
15
*
15
*
450
*
300
*
<A>
A
30
450
*
300
*
C
BB
C
A
100
450
*
100
*
BB
C
C
A
15
*
C
AAA
450 450
900
300
*
300
*
BB
C
C
A
(1)
<A> : Top view
<B> : Side view
<C> : When there is little space up to an obstruction
A :Front B : Unit height C :Back D : Air outlet guide (Procured at the site)
(2)
(3)
(4)
240
45°
100
*
*
B
A
450 450
B
A
100*
450
A
50
50
*
*
<A>
*
A
CC
450
h
H
B
A
h
H
500
<B>
1000
C
*
D
50
6
2
8m
A
<C>
C
40°
(mm)
8m
1000
B
A
*
B
900 300
A :Front B : Must be open C :Wall height (H)
(mm)
Page 3
7
7.1
8
9
30mm
A
A: M10 anchor bolt procured at the site. B Corner is not seated. C Fixing bracket for hole-in anchor bolt (3 locations to fix with screws).
B
C
8.2
A : Outdoor unit B : Indoor unit
A
A
B
Å Outdoor model
RP250
ı Liquid pipe
ø9.52
(mm)
A
Ç Gas pipe
ø22.2
9.2
C
D
A
<A> Valve liquid side/
()
flared type
A
<B> Valve
gas side/
()
flanged type
D
E
A : Close-packed packing B : Hollow packing C :Valve D :Packing E : Connecting pipe with flange
A
A : Example of closure materials (field supply) B : Fill the gap at the site
B
B
C
A: Service port
For vacuuming in the refrigerant pipes on the site. (Tightening torque 12 N·m)
B: Shaft
Fully closed at the factory, when connecting the piping, and when vacuuming. Open fully after these operations are completed. <When opening>
• Turn the shaft counterclockwise with a hexagonal wrench.
• Turn around the shaft until it stops. <When closing>
• Turn the shaft clockwise with a hexagonal wrench.
• Turn around the shaft until it stops.
C: Flare nut
Coat the flare contact surface with refrigerating machine oil (small amount of ester oil, ether oil, or alkyl benzene) and tighten the nut with a double-ended wrench (refer to the following table for tightening torque).
D: Cap
Remove the cap before operating the shaft. Be sure to return it to the original position after completing the operation.
E:Packing
Coat both sides of the packing with machine refrigerating oil (small amount of ester oil, ether oil, or alkyl benzene) and tighten the flange. (Tightening torque 25 N·m)
B
F: Connecting pipe (accessory)
Be sure to remove the connecting pipe from the valve and braze it outside the unit.
G: Field piping
Braze to the connecting pipe with unoxidized brazing.
H: ø9.52 mm I: ø22.2 mm
H
E
F
G
I
3
Page 4
9.3
F
D
C
A
B
D
E
A
C
A : Nitrogen gas
B
B
C
LOW
D
B In case of the R410A cylinder having no syphon pipe.
HI
E
J
B :To indoor unit
G
C : System analyzer D : Low knob
H
E : Hi knob
I
F :Valve G : Liquid pipe H : Gas pipe I : Outdoor unit J : Service port
9.4
B
LOW
M
A : System analyzer B : Low knob C : Hi knob D :Valve E : Liquid pipe F : Gas pipe G : Service port H : Three-way joint I :Valve J :Valve K : R410A cylinder L : Scale M :Vacuum pump N :To indoor unit O : Outdoor unit
EN
N
A
HI
C
H
F
O
G
I
K
J
L
A
A : Syphon pipe
A : Steel wire B : Piping C : Asphaltic oily mastic or asphalt D : Heat insulation material A E : Outer covering B
<A> Inner wall (concealed)
A B
<E> Roof pipe shaft
G
C
<F> Penetrating portion on fire
limit and boundary wall
I
D
B
H F
<B> Outer wall
D
A
1m1m
A B
A
B
[Fig. 9.4.3][Fig. 9.4.2]
C
D
E
E
B
E
A
D
A : Liquid pipe B : Gas pipe C : Electric wire D : Finishing tape E : Insulator
<C> Outer wall (exposed)
E
B
I
<D> Floor (waterproofing)
D
F
G
B
A : Sleeve B : Heat insulating material C :Lagging D : Caulking material
J
E : Band F :Waterproofing layer G : Sleeve with edge H : Lagging material I : Mortar or other incombustible caulking J : Incombustible heat insulation material
4
Page 5
10
[Fig. 10.2.1]
[Fig. 10.2.2]
Power supply terminal block
Control box
A
(TB1)
L1 L2 L3 N
B
Terminal block for indoor –
outdoor transmission line
(TB3)
C
10.2
A : Power source B :Transmission line C : Earth screw
A : Cable strap B : Power source line C :Transmission line
[Fig. 10.3.1]
A
C
B
10.3
OC
IC
M1 M2 S
TB7
A
(51)
TB3
M1 M2
(01)
TB5 TB15
M1 M2 12S
A : Shielded wire
AB
[Fig. 10.4.1]
A : Switch (Breakers for
wiring and current leakage)
B : Breakers for current
leakage
C : Outdoor unit
3N~380–415V
1
, L2, L
3,
L
N
RC
10.4
BA
C
PE
5
Page 6
Contents
1. Safety precautions ...................................................................................... 6
1.1. Before installation and electric work .......................................... 6
1.2. Precautions for devices that use R410A refrigerant .................. 6
1.3. Before installation ...................................................................... 7
1.4. Before installation (relocation) - electrical work ......................... 7
1.5. Before starting the test run ........................................................ 7
2. About the product ....................................................................................... 7
3. Specifications .............................................................................................. 8
4. Parts included list ........................................................................................ 8
5. Space required around unit ........................................................................ 8
6. Lifting method ............................................................................................. 8
7. Installation of unit ........................................................................................ 8
7.1. Installation ................................................................................. 8
8. Refrigerant piping installation ..................................................................... 9
8.1. Caution ...................................................................................... 9
8.2. Refrigerant piping system .......................................................... 9
GB
1. Safety precautions
1.1. Before installation and electric work
s Before installing the unit, make sure you read all the “Safety
DFEINLPGRRUTRCZSVSLHGPO
precautions”.
s The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
:Beware of electric shock. (This symbol is displayed on the main unit label.)
<Color: yellow>
Warning:
Carefully read the labels affixed to the main unit.
HIGH VOLTAGE WARNING:
• Control box houses high-voltage parts.
• When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
• Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock,
or fire.
• Install the unit at a place that can withstand its weight.
- Failure to do so may cause the unit to fall down, resulting in injuries and
damage to the unit.
• Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
•Prepare for strong winds and earthquakes and install the unit at the speci­fied place.
- Improper installation may cause the unit to topple and result in injury and
damage to the unit.
Always use filters and other accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
• Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
9. Additional refrigerant charge ..................................................................... 10
9.1. Calculation of additional refrigerant charge ............................. 10
9.2. Precautions concerning piping connection and
valve operation ........................................................................ 10
9.3. Airtight test, evacuation, and refrigerant charging ................... 11
9.4. Thermal insulation of refrigerant piping ................................... 11
10. Wiring (For details, refer to the installation manual of
each unit and controller.) .......................................................................... 12
10.1. Caution .................................................................................... 12
10.2. Control box and connecting position of wiring ......................... 12
10.3. Wiring transmission cables ...................................................... 12
10.4. Wiring of main power supply and equipment capacity ............ 12
11. Test run ..................................................................................................... 13
11.1. The following phenomena do not represent faults. .................. 13
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may
result.
Have all electric work done by a licensed electrician according to “Electric Facility Engineering Standard” and “Interior Wire Regulations” and the instructions given in this manual and always use a dedicated power supply.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
• Securely install the outdoor unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water may enter
the outdoor unit and fire or electric shock may result.
• When installing and moving the air conditioner to another site, do not charge it with a refrigerant different from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the safety
limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or
fire may result.
• After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
or operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
•To dispose of this product, consult your dealer.
• The installer and system specialist shall secure safety against leakage according to local regulation or standards.
- The size of the wire and capacities of the switch for the main power supply
are applicable if local regulations are not available.
• Pay special attention to the place of installation, such as a basement, etc. where refrigeration gas can accumulate, since refrigeration is heavier than the air.
• For outdoor units that allow fresh air intake to the indoor unit, the installation site must be carefully chosen because outdoor air can directly blow into the room when the thermostat is turned off.
- Direct exposure to outdoor air may have harmful effects on people or food.
1.2. Precautions for devices that use R410A
refrigerant
Caution:
• Do not use existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping contains a large
amount of chlorine which may cause the refrigerator oil of the new unit to deteriorate.
- R410A is a high-pressure refrigerant and can cause the existing piping to
burst.
6
Page 7
• Use refrigerant piping made of phosphorus deoxidized copper and cop­per alloy seamless pipes and tubes. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contami­nant.
- Contaminants on the inside of the refrigerant piping may cause the refriger-
ant residual oil to deteriorate.
• Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and
compressor failure may result.
• Apply a small amount of ester oil, ether oil, or alkyl benzene to flares. (for indoor unit)
- Infiltration of a large amount of mineral oil may cause the refrigerator oil to
deteriorate.
• Use liquid refrigerant to fill the system.
- If gas refrigerant is used to fill the system, the composition of the refrigerant
in the cylinder will change and performance may drop.
• Do not use a refrigerant other than R410A.
- If another refrigerant (R22, etc.) is mixed with R410A, the chlorine in the
refrigerant may cause the refrigerator oil to deteriorate.
• Use a vacuum pump with a reverse flow check valve.
- The vacuum pump oil may flow back into the refrigerant cycle and cause the
refrigerator oil to deteriorate.
• Do not use the following tools that are used with conventional refriger­ants. (Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, refrigerant recovery equipment)
- If the conventional refrigerant and refrigerator oil are mixed in the R410A,
the refrigerant may deteriorated.
- If water is mixed in the R410A, the refrigerator oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conven-
tional refrigerants will not react to it.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Be especially careful when managing the tools.
- If dust, dirt, or water gets into the refrigerant cycle, the refrigerant may dete-
riorate.
1.3. Before installation
1.4. Before installation (relocation) - electri­cal work
Caution:
• Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or telephone ground lines. Improper grounding may result in electric shock.
• Install the power cable so that tension is not applied to the cable.
-Tension may cause the cable to break and generate heat and cause a fire.
• Install a leak circuit breaker, as required.
- If a leak circuit breaker is not installed, electric shock may result.
• Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Use only a circuit breaker and fuse of the specified capacity.
-A fuse or circuit breaker of a larger capacity, or the use of a substitute simple steel or copper wire may result in a general unit failure or fire.
• Do not wash the air conditioner units.
-Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury or property damage.
• Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage causing damage to furniture
and other possessions.
• Be very careful about transporting the product.
- One person should not carry the product. Its weight is in excess of 20kg.
- Some products use PP bands for packaging. Do not use any PP bands as a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, support it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
-Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which has not been torn apart, they face the risk of suffocation.
GB
DFEINLPGRRUTRCZSVSLHGPO
Caution:
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instru­ments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
• When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
-Inverter equipment, private power generator, high-frequency medical equip-
ment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80% or when the drain pipe is clogged,
condensation may drip from the indoor unit. Perform collective drainage work together with the outdoor unit, as required.
2. About the product
• This unit uses R410A-type refrigerant.
• Piping for systems using R410A may be different from that for systems using conventional refrigerant because the design pressure in systems using R410A is higher. Refer to the Data Book for more information.
• Some of the tools and equipment used for installation with systems that use other types of refrigerant cannot be used with the systems using R410A. Refer to the Data Book for more information.
• Do not use the existing piping, as it contains chlorine, which is found in con­ventional refrigerating machine oil and refrigerant. This chlorine will deteriorate the refrigerant machine oil in the new equipment. The existing piping must not be used as the design pressure in systems using R410A is higher than that in the systems using other types of refrigerant and the existing pipes may burst.
1.5. Before starting the test run
Caution:
•Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result in irreversible damage to internal parts. Keep the power switch turned on during the operational season. Make sure of the phase order of power supply and voltage between each phase.
• Do not touch the switches with wet fingers.
-Touching a switch with wet fingers can result in an electric shock.
• Do not touch the refrigerant pipes during and immediately after opera­tion.
- During and immediately after operation, the refrigerant pipes may be hot or
cold, depending on the condition of the refrigerant flowing through the refrig­erant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not turn off the power immediately after stopping operation.
- Always wait at least 5 minutes before turning off the power. Otherwise,
drainage water leakage or mechanical failure of sensitive parts may occur.
• Do not touch the surface of the compressor during servicing.
- If unit is connected to a supply and not running, the crank case heater located
at the base of the compressor may still be operating.
7
Page 8
3. Specifications
Model Noise level External static pressure
Operation temperature
Standard type
Cooling mode: – 5°CDB ~ 43°CDB Heating mode: – 12°CWB ~ 15°CWB
PUHZ-RP250YHM-A
4. Parts included list
1 Connecting pipe (flange)
Model
RP250
<Gas side>
1 pc.
5. Space required around unit
1 In case of single installation
GB
• Secure enough space around the unit as shown in the figure on page 2.
[Fig. 5.0.1] (P.2)
<A> Top view <B> Side view
<C> When there is little space up to an obstruction A Front B Unit height
DFEINLPGRRUTRCZSVSLHGPO
C Back D Air outlet guide (Procured at the site)
(1) If the distance is 300 mm or more between the rear side and the wall
(2) If the distance is 100 mm or more between the rear side and the wall
(3) If the wall height (H) of the front, rear or side exceeds the wall height
restriction
• When the height of the walls on the front, back or on the sides <H> exceeds the wall height limit as defined here, add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm from the unit bottom Side: Up to the unit height
58dB <A>
0 Pa
2 Packing
(Inside
ø23, Outside ø30)
1 pc.
(4) If there are obstacles at the upper part of the unit
2 In case of collective installation
[Fig. 5.0.2] (P.2)
A Front B Must be open C Wall height (H)
• When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and walkway between groups of units as shown in the figures on page 2.
• At least two sides must be left open.
• As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.
6. Lifting method
[Fig. 6.0.1] (P.2)
• Use suspension ropes that will withstand the weight of the unit.
• When moving the unit, use a 4-point suspension, and avoid giving impacts to the unit (Do not use 2-point suspension).
• Place protective pads on the unit where it comes in contact with the ropes to protect the unit from being scratched.
• Set the angle of roping at 40° or less.
• Use 2 ropes that are each longer than 8 meters.
• Place protective padding at the corners of the product to protect the product from scratches or dents that might be caused by the rope.
7. Installation of unit
7.1. Installation
[Fig. 7.1.1] (P.3)
A M10 anchor bolt procured at the site. B Corner is not seated. C Fixing bracket for the hole-in anchor bolt (3 locations to fix with screws).
• Fix unit tightly with bolts so that unit will not fall down due to earthquakes or strong winds.
• Use concrete or an angle bracket as the foundation of unit.
• Vibration may be transmitted to the installation section and noise and vibration may be generated from the floor and walls, depending on the installation con­ditions. Therefore, provide ample vibrationproofing (cushion pads, cushion frame, etc.).
• Build the foundation in such way that the corner of the installation leg is se­curely supported as shown in the figure. (Fig. 7.1.1) When using a rubber isolating cushion, please ensure it is large enough to cover the entire width of each of the unit's legs. If the corners are not firmly seated, the installation feet may be bent.
• The projecting length of the anchor bolt should be less than 30 mm.
• Hole-in anchor bolts are not compatible with this product. However, if fixing brackets are mounted on the 4 locations of the unit attachment part, hole-in anchor bolts can be used.
Caution:
Be very careful when carrying/moving the product.
- When installing the outdoor unit, suspend the unit at the specified location of the unit base. Stabilize as necessary so that it does not move to the side and support it at 4 points. If the unit is installed or suspended with 3-point support, the unit may become unstable and fall.
Warning:
• Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
•Have installation work in order to protect against strong winds and
earthquakes. Any installation deficiency may cause unit to fall down, resulting in a personal injury.
When building the foundation, give full attention to the floor strength, drain water disposal <during operation, drain water flows out of the unit>, and piping and wir­ing routes.
Precautions when routing the pipes and wires below the unit
When routing the pipes and wires below the unit, be sure that the foundation and base work do not block the base through-holes. Also make sure the foundation is at least 100 mm high so that the piping can pass under the unit.
8
Page 9
8. Refrigerant piping installation
The pipe is connected via a terminal-branch type connection in which refrigerant piping from the outdoor unit is branched at the terminal and is connected to each of the indoor units. The method of pipe connection is as follows: flare connection for the indoor units, gas pipes for outdoor units, brazed connection; liquid pipes, flare connection. Note that the branched sections are brazed.
Warning:
Always use extreme care to prevent the refrigerant gas from leaking while using fire or flame. If the refrigerant gas comes in to contact with a flame from any source, such as a gas stove, it breaks down and generates a poi­sonous gas which can cause gas poisoning. Never weld in an unventilated room. Always conduct an inspection for gas leakage after installation of the refrigerant piping has been completed.
8.1. Caution
This unit uses refrigerant R410A. Follow the local regulations on materials and pipe thickness when selecting pipes. (Refer to the table below.)
1 Use the following materials for refrigeration piping.
• Material: Use copper alloy seamless pipes made of phosphorus deoxi­dized copper. Ensure the inner and outer surfaces of the pipes are clean and free from hazardous sulfur, oxide, dusts, shaving particles, oils, and moisture (contamination).
• Size: Refer to item 8.2. for detailed information on refrigerant piping sys­tem.
2 Commercially available piping often contains dust and other materials. Always
blow it clean with a dry inert gas.
3 Use care to prevent dust, water or other contaminants from entering the piping
during installation.
4 Reduce the number of bending portions as much as possible, and make bend-
ing radii as big as possible.
Copper pipe size and radial thickness for R410A.
Size (mm) Radial thickness (mm) Pipe type
ø6.35 0.8 Type-O ø9.52 0.8 Type-O
ø12.7 0.8 Type-O ø15.88 1.0 Type-O ø19.05 1.2 Type-O ø19.05 1.0 Type-1/2H or H
ø22.2 1.0 Type-1/2H or H
ø25.4 1.0 Type-1/2H or H ø28.58 1.0 Type-1/2H or H ø31.75 1.1 Type-1/2H or H ø34.93 1.2 Type-1/2H or H ø41.28 1.4 Type-1/2H or H
*For pipe sized ø19.05 for R410A air conditioner, choice of pipe type is up to you.
5 Always observe the restrictions on the refrigerant piping (such as rated length,
height difference, and piping diameter) to prevent equipment failure or a de­cline in heating/cooling performance.
6 Either a lack or an excess of refrigerant causes the unit to make an emergency
stop. Charge the system with an appropriate amount of refrigerant. When serv­icing, always check the notes concerning pipe length and amount of additional refrigerant at both locations, the refrigerant volume calculation table on the back of the service panel and the additional refrigerant section on the labels for the combined number of indoor units (Refer to item 8.2. for detailed infor­mation on refrigerant piping system).
7 Be sure to charge the system using liquid refrigerant.
8 Never use refrigerant to perform an air purge. Always evacuate using a
vacuum pump.
9 Always insulate the piping properly. Insufficient insulation will result in a de-
cline in heating/cooling performance, water drops from condensation and other such problems (Refer to item 9.4 for thermal insulation of refrigerant piping).
0 When connecting the refrigerant piping, make sure the valve of the outdoor
unit is completely closed (the factory setting) and do not operate it until the refrigerant piping for the outdoor and indoor units has been connected, a re­frigerant leakage test has been performed and the evacuation process has been completed.
A Braze only with non-oxide brazing material for piping. Failure to do so
may damage the compressor. Be sure to perform the non-oxidation braz­ing with a nitrogen purge. Do not use any commercially available anti-oxidizing agent since it may cause pipe corrosion and degrading of the refrigerant oil. Please contact Mitsubishi Electric for more details.
(Refer to item 9.2. for details of the piping connection and valve operation)
B Never perform outdoor unit piping connection work when it is raining.
Warning:
When installing and moving the unit, do not charge the system with any other refrigerant other than the refrigerant specified on the unit.
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal­function and may result in severe damage.
Caution:
• Use a vacuum pump with a reverse flow check valve.
- If the vacuum pump does not have a reverse flow check valve, the vacuum pump oil may flow back into the refrigerant cycle and cause deterioration of the refrigerator oil.
• Do not use the tools shown below used with conventional refrigerant. (Gauge manifold, charge hose, gas leak detector, check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment)
- Mixing of conventional refrigerant and refrigerator oil may cause the refrig-
erator oil to deteriorate.
- Mixing of water will cause the refrigerator oil to deteriorate.
- R410A refrigerant does not contain any chlorine. Therefore, gas leak detec-
tors for conventional refrigerants will not react to it.
• Manage the tools used for R410A more carefully than normal.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerator oil will dete-
riorate.
•Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerator oil
in the existing piping will cause the new refrigerant to deteriorate.
• Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing.
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and
the compressor may fail.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Do not use special detergents for washing piping.
8.2. Refrigerant piping system
Connection example
[Fig. 8.2.1] (P.3)
Å Outdoor model ı Liquid pipe Ç Gas pipe A Outdoor unit B Indoor unit
GB
DFEINLPGRRUTRCZSVSLHGPO
9
Page 10
9. Additional refrigerant charge
At the time of shipping, the outdoor unit is charged with refrigerant. This charge does not include the amount needed for extended piping and addi­tional charging of each refrigerant line will be required on site. In order that future servicing may be properly provided, always keep a record of the size and length of each refrigerant line and the amount of additional charge by writing it in the space provided on the outdoor unit.
9.1. Calculation of additional refrigerant charge
• Calculate the amount of additional charge based on the length of the piping
extension and the size of the refrigerant line.
• Use the table below as a guide to calculating the amount of additional charging
and charge the system accordingly.
• If the calculation results in a fraction of less than 0.1 kg, round up to the next
0.1 kg. For example, if the result of the calculation was 11.38 kg, round the result up to 11.4 kg.
GB
<Additional Charge>
Additional refrigerant charge
(kg)
Liquid pipe size Total length of
= + 3.0 kg
ø9.52 × 0.06
(m) × 0.06 (kg/m)
DFEINLPGRRUTRCZSVSLHGPO
9.2. Precautions concerning piping connec­tion and valve operation
• Conduct piping connection and valve operation accurately.
• The gas side connecting pipe is assembled in the factory before shipment.
1 For brazing to the connecting pipe with flange, remove the connecting pipe
with flange from the valve, and braze it outside of the unit.
2 The refrigerant circuit is closed with a round, close-packed packing upon
shipment to prevent gas leak between flanges. As no operation can be done under this state, be sure to replace the packing with the hollow pack­ing attached at the piping connection.
3 At the mounting of the hollow packing, wipe off dust attached on the flange
sheet surface and the packing. Coat refrigerating machine oil (Ester oil, ether oil or alkylbenzene [small amount]) onto both surfaces of the pack­ing.
A Close-packed packing B Hollow packing C Valve D Packing E Connecting pipe with flange
• After evacuation and refrigerant charge, ensure that the handle is fully open. If
operating with the valve closed, abnormal pressure will be imparted to the high- or low-pressure side of the refrigerant circuit, giving damage to the com­pressor, four-way valve, etc.
• Determine the amount of additional refrigerant charge by using the formula,
and charge refrigerant additionally through the service port after completing piping connection work.
• After completing work, tighten the service port and cap securely so as not to
generate any gas leakage.
• Flare machining dimension for systems using R410A is larger than that for
systems using other types of refrigerant in order to increase the air tightness.
• Refer to the table on the below for flare machining dimensions, and follow the
regulations set forth by the local authorities.
flare machining dimension (mm)
dimension A
R410A
9.1
13.2
16.6
19.7
24.0
dimension B
R410A
17.0
22.0
26.0
29.0
36.0
A
flare nut size (mm)
outer diameter
ø6.35 ø9.52
ø12.7 ø15.88 ø19.05
outer diameter
ø6.35
ø9.52
B
ø12.7 ø15.88 ø19.05
[Fig. 9.2.2] (P.3)
A Service port
For vacuuming in the refrigerant pipes on the site. (Tightening torque 12 N·m)
B Shaft
Fully closed at the factory, when connecting the piping, and when vacuuming. Open fully after these operations are completed. <When opening>
• Turn the shaft counterclockwise with a hexagonal wrench.
• Turn around the shaft until it stops. <When closing>
• Turn the shaft clockwise with a hexagonal wrench.
• Turn around the shaft until it stops.
C Flare nut
Coat the flare contact surface with refrigerating machine oil (small amount of ester oil, ether oil, or alkyl benzene) and tighten the nut with a double-ended wrench (refer to the following table for tightening torque).
D Cap
Remove the cap before operating the shaft. Be sure to return it to the original position after completing the operation.
E Packing
Coat both sides of the packing with machine refrigerating oil (small amount of ester oil, ether oil, or alkyl benzene) and tighten the flange. (Tightening torque 25 N·m)
F Connecting pipe (accessory)
Be sure to remove the connecting pipe from the valve and braze it outside the unit.
G Field piping
Braze to the connecting pipe with unoxidized brazing.
H ø9.52 mm I ø22.2 mm
Appropriate tightening torque:
Outer diameter of copper pipe (mm)
ø9.52
ø12.7 ø15.88 ø19.05
ø25.4
Appropriate tightening torque and its angle:
Outer diameter of copper pipe (mm)
ø9.52
ø12.7 ø15.88 ø19.05
Cap (N·m)
22 20 25 25 40
Tightening torque
(N·m)
35 - 42
50 - 57.5
75 - 80
100 - 140
Shaft (N·m)
5
9 15 15 30
Tightening angle
(°)
60 to 90
30 to 60
20 to 35
Size of hexagonal
wrench (mm)
4 4 6 6
10
Warning:
When connecting a pipe to the service valve, be sure to use only the supplied open-end flare nut, with small holes cut into the flats.
* Using a regular flare nut (i.e., non-supplied) will result in any water that natu-
rally flows into the nut being unable to escape. Consequently, when the temperature becomes low, this water inside the nut may freeze and cause damage to the joint. This, in turn, may result in a gas leakage.
Note: If a torque wrench is not available, use the following method as a standard; When you tighten the flare nut with a wrench, you will reach a point where the tightening torque will abruptly increase. Turn the flare nut beyond this point by the angle shown in the table above.
Caution:
•Always remove the connecting pipe from the valve and braze it outside the unit.
-Brazing the connecting pipe while it is installed will heat the valve and cause
trouble or gas leakage. The piping, etc. inside the unit may also be burned.
• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerat­ing machine oil to coat flares and flange connections.
- The refrigerating machine oil will degrade if it is mixed with a large amount of
mineral oil.
•Keep the valve closed until refrigerant charging to the pipes to be added on site has been completed. Opening the valve before charging the re­frigerant may result in unit damage.
• Do not use a leak detection additive.
A Example of closure materials (field supply) B Fill the gap at the site
Make sure to seal-off the space around areas where the wires and refrigerant pipes enter the unit to ensure that small animals, rainwater, or snow cannot enter the unit through such openings and cause damage to the unit.
10
Page 11
Caution:
Make sure to seal-off and excess space around areas where the wires and refrigerant pipes enter the unit.
• Small animals, rainwater, or snow entering through the openings may cause damage to the device.
9.3. Airtight test, evacuation, and refrigerant
charging
1 Airtight test
Perform with the valve of the outdoor unit closed, and pressurize the connec­tion piping and the indoor unit from the service port provided on the valve of the outdoor unit. (Always pressurize from both the liquid pipe and the gas pipe service ports.)
Airtight test procedure
(1) After pressurizing to the design pressure (4.15 MPa) using nitrogen gas, allow it to stand for
about one day. If the pressure does not drop, airtightness is good. However, if the pressure drops, since the leaking point is unknown, the following bubble test may also be performed.
(2) After the pressurization described above, spray the flare connection parts, brazed parts, and
other parts that may leak with a bubbling agent (Kyuboflex, etc.) and visually check for bubbles.
(3) After the airtight test, wipe off the bubbling agent.
Observe the following restrictions when conducting an air tightness test to prevent negative effects on the refrigerating machine oil. Also, with nonazeotropic refriger­ant (R410A), gas leakage causes the composition to change and affects perform­ance. Therefore, perform the airtightness test cautiously.
[Fig. 9.3.1] (P.4)
A Nitrogen gas B To indoor unit C System analyzer D Low knob E Hi knob F Valve G Liquid pipe H Gas pipe I Outdoor unit J Service port
Restriction
• If a flammable gas or air (oxygen) is used as the pressurization gas, it may catch fire or explode.
GB
Caution:
Only use refrigerant R410A.
- The use of other refrigerants such as R22 or R407C, which contains chlorine, will deteriorate the refrigerating machine oil or cause the compressor to malfunc­tion.
2 Evacuation
Evacuate with the valve of the outdoor unit closed and evacuate both the con­nection piping and the indoor unit from the service port provided on the valve of the outdoor unit using a vacuum pump. (Always evacuate from the service port of both liquid pipe and gas pipe.) After the vacuum reaches 650 Pa [abs], continue evacuation for at least one hour or more. Then, stop the vacuum pump and leave it for 1 hour. Ensure the degree of vacuum has not increased.
(If the degree of vacuum increase is larger than 130 Pa, water might have entered. Apply pressure to dry nitrogen gas up to 0.05 MPa and vacuum again.) Finally, seal in with the liquid refrigerant through the liquid pipe, and
adjust the gas piping to obtain an appropriate amount of the refrigerant during operation. * Never perform air purging using refrigerant.
[Fig. 9.3.2] (P.4)
A System analyzer B Low knob C Hi knob D Valve E Liquid pipe F Gas pipe G Service port H Three-way joint I Valve J Valve K R410A cylinder L Scale M Vacuum pump N To indoor unit O Outdoor unit
Note:
•Always add an appropriate amount of refrigerant. Also always charge the
system with liquid refrigerant.
• Use a gauge manifold, charging hose, and other parts for the refrigerant
indicated on the unit.
• Use a graviometer. (One that can measure down to 0.1 kg.)
• Use a vacuum pump with a reverse flow check valve.
(Recommended vacuum gauge: ROBINAIR 14830A Thermistor Vacuum Gauge) Also use a vacuum gauge that reaches 65 Pa [abs] or below after operat­ing for five minutes.
3 Refrigerant Charging
Since the refrigerant used with the unit is nonazerotropic, it must be charged in the liquid state. Consequently, when charging the unit with refrigerant from a cylinder, if the cylinder does not have a syphon pipe, charge the liquid refriger­ant by turning the cylinder upside-down as shown in Fig. 9.3.3. If the cylinder has a syphon pipe like that shown in the picture on the right, the liquid refriger­ant can be charged with the cylinder standing upright. Therefore, give careful attention to the cylinder specifications. If the unit should be charged with gas refrigerant, replace all the refrigerant with new refrigerant. Do not use the re­frigerant remaining in the cylinder.
[Fig. 9.3.3] (P.4)
A Syphon pipe B
In case of the R410A cylinder having no syphon pipe.
9.4. Thermal insulation of refrigerant piping
Be sure to add insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a possibility of condensation drip, etc. Pay special attention to insulation work in the ceiling ple­num.
[Fig. 9.4.1] (P.4)
A Steel wire B Piping C Asphaltic oily mastic or asphalt D Heat insulation material A E Outer covering B
Heat
insulation
material A
Outer
covering B
Note:
• When using polyethylene cover as covering material, asphalt roofing shall not be required.
• No heat insulation must be provided for electric wires.
[Fig. 9.4.2] (P.4)
[Fig. 9.4.3] (P.4)
Penetrations
[Fig. 9.4.4] (P.4)
When filling a gap with mortar, cover the penetration part with steel plate so that the insulation material will not be caved in. For this part, use incombustible mate­rials for both insulation and covering. (Vinyl covering should not be used.)
• Insulation materials for the pipes to be added on site must meet the following specifications:
Thickness Temperature Resistance
* Installation of pipes in a high-temperature high-humidity environment, such as
the top floor of a building, may require the use of insulation materials thicker than the ones specified in the chart above.
* When certain specifications presented by the client must be met, ensure that
they also meet the specifications on the chart above.
Glass fiber + Steel wire
Adhesive + Heat - resistant polyethylene foam + Adhesive tape
Indoor Vinyl tape Floor exposed Water-proof hemp cloth + Bronze asphalt Outdoor Water-proof hemp cloth + Zinc plate + Oily paint
A Liquid pipe B Gas pipe C Electric wire D Finishing tape E Insulator
<A> Inner wall (concealed) <B> Outer wall
<C> Outer wall (exposed) <D> Floor (waterproofing)
<E> Roof pipe shaft
<F> Penetrating portion on fire limit and boundary wall
A Sleeve B Heat insulating material C Lagging D Caulking material E Band F Waterproofing layer G Sleeve with edge H Lagging material I Mortar or other incombustible caulking J Incombustible heat insulation material
ø6.35 to 25.4 mm
10 mm min.
Pipe size
ø28.58 to 41.28 mm
15 mm min.
100°C min.
DFEINLPGRRUTRCZSVSLHGPO
11
Page 12
10. Wiring (For details, refer to the installation manual of each unit and controller.)
10.1. Caution
1 Follow ordinance of your governmental organization for technical standard re-
lated to electrical equipment, wiring regulations and guidance of each electric power company.
2 Wiring for control (hereinafter referred to as transmission line) shall be (5 cm or
more) apart from power source wiring so that it is not influenced by electric noise from power source wiring (Do not insert transmission line and power source wire in the same conduit).
3 Be sure to provide designated grounding work the to the outdoor unit.
4 Give some allowance to wiring for electrical part box of indoor and outdoor
units, because the box is sometimes removed at the time of service work.
5 Never connect the main power source to terminal block of transmission line. If
connected, electrical parts will burn out.
6 Use 2-core shield cable for transmission line. If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor trans-
GB
mitting and receiving will cause erroneous operations.
7 Only the transmission line specified should be connected to the terminal block
for outdoor unit transmission. Erroneous connection does not allow the system to operate.
10.2. Control box and connecting position of
DFEINLPGRRUTRCZSVSLHGPO
1 Outdoor unit
1. Remove the front panel of the control box by removing the 4 screws and push-
2. Connect the indoor - outdoor transmission line to the terminal block (TB3) for
3. In the case of indoor-outdoor transmission line, connect the shield ground to
4. Fix the connected wires securely in place with the cable strap at the bottom of
wiring
ing it up a little before pulling it out.
the indoor - outdoor transmission line. If multiple outdoor units are connected in the same refrigerant system, daisy­chain TB3 (M1, M2, outdoor transmission line for the outdoor units to TB3 (M1, M2, only one of the outdoor units.
the grounding terminal (
the terminal block. External force applied to the terminal block may damage it resulting in a short circuit, ground fault, or a fire.
Te r minal) on the outdoor units. Connect the indoor -
).
Te r minal) of
[Fig. 10.2.1] (P.5)
A Pow er source B Tr ansmission line C Earth screw
[Fig. 10.2.2] (P.5)
A Cable strap B Pow er source line C Tr ansmission line
2 Conduit tube installation
• Close by hammering the knockout holes for the conduit tube located on the base and the bottom part of the front panel.
• When installing the conduit tube directly through the knockout holes, remove the burr and protect the tube with masking tape.
• Use the conduit tube to narrow down the opening if there is a possibility of small animals entering the unit.
10.3. Wiring transmission cables
1 Types of control cables
1. Wiring transmission cables
•Types of transmission cables: Shielding wire CVVS, CPEVS or MVVS
• Cable diameter: More than 1.25 mm
• Maximum wiring length: Within 80 m
2. Remote control cables
• Remote Controller
Kind of remote control cable
Cable diameter
Remarks
* Connected with simple remote controller.
2 Wiring examples
• Controller name and symbol.
Outdoor unit Indoor unit Remote controller
<Examples of transmission cable wiring>
[Fig. 10.3.1]
A Shielded wire
Set the address setting switch of all unit as zero (0). (factory setting)
Name Code Outdoor unit controller Indoor unit controller Remote controller
2
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm Within 200 m
2
(0.75 to 1.25 mm2)*
OC
IC
RC
10.4. Wiring of main power supply and equipment capacity
Schematic Drawing of Wiring (Example)
[Fig. 10.4.1] (P.5)
A Switch (Breakers for wiring and current leakage) B Breakers for current leakage C Outdoor unit
Thickness of wire for main power supply, capacities of the switch and system impedance
Model
Outdoor unit
*1: Meets technical requirements of IEC61000-3-3
1. Use dedicated power supplies for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter. Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example, use wiring such as YZW.
6. A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer.
RP250
Minimum wire thickness (mm
Main cable
Warning:
• Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating or fire may result.
• Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
• Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of electric shock.
• Do not use anything other than a breaker and fuse with the correct ca­pacity. Using a fuse or wire of too large capacity may cause malfunction or fire.
Ground
4.0
2
)
Breaker for current leakage
30A 100mA 0.1sec. or less
Note:
• This device is intended for the connection to a power supply system with
• The user must ensure that this device is connected only to a power sup-
• This equipment complies with IEC 61000-3-12 provided that the short-
Local swtich (A)
Capacity Fuse
a maximum permissible system impedance shown in the above table at the interface point (power service box) of the user’s supply.
ply system which fulfils the requirement above. If necessary, the user can ask the public power supply company for the system impedance at the interface point.
circuit power S between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is con­nected only to a supply with a short-circuit power S equal to S
is greater than or equal to S
SC
(*2).
SC
Breaker for
wiring (NFB) (A)
3032 324.0
SC
System Impedance
(*2) at the interface point
SC
Max. Permissive
*1
greater than or
12
S
(*2)
SC
Model S
RP250 1.27
SC
(MVA)
Page 13
11. Test run
11.1. The following phenomena do not represent faults.
Phenomenon
Fan setting changes during heating.
Fan stops during heating operation. Fan does not stop while operation has been stopped. No setting of fan while start SW has been turned on.
Indoor unit remote controller shows “H0” or “PLEASE WAIT” indicator for about five min­utes when turning ON universal power sup­ply. Indoor unit emits noise when switching from heating to cooling and vice versa. Immediately after startup, the indoor unit emits the sound of the refrigerant flow. Warm air comes from an indoor unit that is not performing a heating operation.
Display of remote controller
Normal display
Defrost display No lighting
Heat ready
“H0” or “PLEASE WAIT” flashes
Normal display
Normal display
Normal display
Cause Ultra-low speed operation is commenced at thermostat OFF. Light air automatically changes over to set value by time or piping temperature at thermostat ON. The fan is to stop during defrosting. The fan is set to run for 1 minute after stopping to exhaust residual heat (only in heating). Ultra low-speed operation for 5 minutes after SW ON or until piping temperature becomes 35°C, low speed operation for 2 minutes thereafter, and then set notch is commenced (Hot adjust control). The system is being started up. Operate remote controller again after “H0” or “PLEASE WAIT” disappear.
This is a switching sound of the refrigerant circuit and does not imply a problem.
Unstable flow of the refrigerant emits a sound. This is temporary and does not imply a problem. The LEV is slightly open to prevent refrigerant, of the indoor unit that is not performing the heating operation, from being liquefied. This does not imply a problem.
GB
DFEINLPGRRUTRCZSVSLHGPO
13
Page 14
GB
E
F
E
INL
PGRRUTR
Page 15
GB
E
F
E
NL
PGRRUTR
Page 16
This product is designed and intended for use in the residential,
commercial and light-industrial environment.
The product at hand is based on the following EU regulations:
• Low Voltage Directive 2006/95/EC
• Electromagnetic Compatibility Directive 2004/108/EC
• Pressure Equipment Directive 97/23/EC
WT05737X01
Please be sure to put the contact address/telephone number on
this manual before handing it to the customer.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Printed in Japan