Before obtaining access to terminal, all supply
circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the followings.
· Be sure to perform replacement operation before test run.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
3
Page 4
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
Gauge manifold·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
Charge hose·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
Electronic scale
Gas leak detector·Use the detector for R134a, R407C or R410A.
Adaptor for reverse flow check·Attach on vacuum pump.
Refrigerant charge base
Refrigerant cylinder·Only for R410A ·Top of cylinder (Pink)
·Cylinder with syphon
Refrigerant recovery equipment
specifications
. (UNF1/2)
4
Page 5
5
2-3. Precautions when reusing existing R22 refrigerant pipes
(1) Flowchart
Measure the existing pipe thickness and check
for damage.
The existing pipe thickness meets specifications and the pipes are not damaged.
Check if the existing air conditioner can operate.
The existing air conditioner can operate.The existing air conditioner cannot operate.
After operating the cooling system for about
30 minutes, do a pump down work.
Disconnect the existing air conditioner from
the pipes.
The existing piping can be reused.
After flaring the pipes again, connect the
new air conditioner.
Use a refrigerant recovery device to recover the refrigerant.
Check the oil condition when recovering refrigerant.
Oil is clean. (Clear to brownish color)
In case that existing pipes were
used for gas or oil heat pump
system, be sure to clean the pipes.
Oil is dirty. (Black color)
The existing pipe thickness does not meet
specifications or the pipes are damaged.
When the compressor bearings
are seized, winding is damaged
or the compressor breaks down,
iron particles or oil deterioration will
blacken the oil.
The existing pipes cannot be reused.
Use new pipes.
Perform the following inspections: air
tightness test, vacuum dryness (additional
refrigerant charge), gas leakage check
Replacement operation
Test operation
·When performing replacement operation, make sure that DIP SW8-2 on outdoor unit controller board is
set to ON.
+Chemical compounds containing chlorine left in existing pipes are recovered by replace filter.
LThe air conditioner automatically performs cooling operation through replace filter for about 2 hours.
Connecting a new air conditioner to existing R22 refrigerant pipes
Flare the pipe for the use with R410A refrigerant.
Use the flare nut attached to indoor and outdoor unit of the new air conditioner only.
When reusing existing R22 refrigerant pipes of which gas pipe is :28.58mm and, when the outdoor unit is installed to lower
position than the indoor unit, be sure to change the setting of the DIP SW8-1 on the controller circuit board of the outdoor
unit to ON.
=This is to increase the speed of refrigerant passing in the gas pipe so that refrigerant oil can smoothly flow in the system.
• Use a different-diameter joint or brazing for the connection.
When reusing standard-size existing R22 refrigerant pipes.
The pipes can be reused with pipe length restriction described on TECHNICAL DATA BOOK.
Page 6
(2) Cautions for refrigerant piping work
1/4
3/8
1/2
5/8
3/4
6.35
9.52
12.70
15.88
19.05
17.0
22.0
26.0
29.0
36.0
17.0
22.0
24.0
27.0
36.0
Nominal
dimensions(inch)
Flare nut dimensions
Outside
diameter
Dimension B
(mm)
R410AR22
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working
pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7mm or below.)
Diagram below: Piping diameter and thickness
Nominal
dimensions (inch)
1/4
3/8
1/2
5/8
3/4
7/8
1
1-1/8
Outside
diameter (mm)
6.35
9.52
12.70
15.88
19.05
22.20
25.40
28.58
Thickness (mm)
R410AR22
0.8
0.8
0.8
1.0
—
—
—
—
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because of its working pressure higher than that of other refriger
ants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also
have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring
dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes.
Use torque wrench corresponding to each dimension.
-
Dimension A
Flare cutting dimensions
Nominal
dimensions(inch)
Outside
diameter
1/4
3/8
1/2
5/8
3/4
6.35
9.52
12.70
15.88
19.05
Dimension A
R410AR22
9.1
13.2
16.6
19.7
24.0
+0
( )
-0.4
9.0
13.0
16.2
19.4
23.3
(mm)
Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materialsUseR410A toolsCan R22 tools be used?
Gauge manifold
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
Air purge, refrigerant charge and
operation check
Gas leak check
Refrigerant recovery
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Refrigerant charge
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Refrigerant charge
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil, ether oil and
alkylbenzene oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adopter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT. (Max.30m)
The refrigerant circuit with LEV(Linear Expansion Valve) and accumulator always control the optimal refrigerant level
regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often
causes problems. It is completely eliminated by chargeless system. This unique system improves the quality
and reliability of the work done. It also helps to speed up the installation time.
7
Page 8
4SPECIFICATIONS
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Airflow
Main piping:
Liquid line size
:12.7 over all length [m]
% 0.12 [kg/m]
=
Additional charge amount
for 70 m
RP200 3.6 kg
RP250 4.8 kg
+
+
+–
Calculate the additional charge amount based on the following procedure.
If the calculation results in an amount that is smaller than the "Additional charge amount for 70m," perform the additional charge using the amount shown
in "Additional charge amount for 70m."
5-1. ADJUSTING THE AMOUNT OF REFRIGERANT
5-2. COMPRESSOR TECHNICAL DATA
DWÛ&
Unit
Compressor model
PUHZ-RP200, 250YHA2
ANB52FFJMT
U-V
0.30
Winding
Resistance
U-W
0.30
( )
W-V
0.30
5-3. NOISE CRITERION CURVES
MICROPHONE
1.5m
1m
UNIT
GROUND
PUHZ-RP200YHA2
PUHZ-RP250YHA2
90
80
70
60
50
40
COOLING
HEATING
58
59
SPL(dB)
MODE
LINE
NC-70
NC-60
NC-50
NC-40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
< Connected for Option (Contact Input)>
Connector<Connection for Option>
Connector<Connection for Option>
Relay
Switch<Status of communication>
Switch<Address setting:1st digit>
Switch<Address setting:2nd digit>
LED<Power Supply:DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission:Sending>
LED<Transmission:Receiving>
LED<Power Supply:DC12V>
NAME
POWER
SUPPLY
3N~
400V 50Hz
NO FUSE
BREAKER
TB1
L1
L2
L3
N
RED
WHT
BLK
BLU
GRN/YLW
2
N. F.
CNAC1
(WHT)
31
LI 1
LI 2
UU
LI 3
U
NI
U
U
GD2GD1
BLK
CNDC
(PNK)
BLK
CNCT
(RED)
31
2
WHT
CNAC2
(RED)
3112
LO 1
RED
LO 2
WHT
LO3
BLK
+
1 MODEL SELECT
MODEL
200Y
U
13
CNL
(BLU)
WHT
ACL4
250Y
+
2. SW5 -1 to 5 : Function Switch
SW6
ON
OFF
12345678
ON
OFF
12345678
ON
OFF
ON
OFF
SW5-6+2
123456
123456
13
Page 14
8WIRING SPECIFICATIONS
8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
P200, P250
Outdoor unit modelRP200, 250
Outdoor unit
Power supply
Outdoor unit input capacity *1
Main switch (Breaker)
Wiring
Wire No. %
size(mm
Outdoor unit power supply5 % Min. 4
Indoor unit-Outdoor unit *2Cable length 50 m : 3 % 4 (Polar)/Cable length 80 m : 3 % 6 (Polar)
Indoor unit-Outdoor unit earth1 % Min. 2.5
2
)
Remote controller-Indoor unit *32 % 0.69 (Non-polar)
Outdoor unit L1-N, L2-N, L3-NAC 220 - 230 - 240 V
Circuit rating
Indoor unit-Outdoor unit S1-S2 *4AC 220 - 230 - 240 V
Indoor unit-Outdoor unit S2-S3 *4DC 24 V
Remote controller-Indoor unit *4DC 14 V
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
*2. Max. 80 m Total Max. including all indoor/indoor connection is 80 m.
• Use one cable for S1 and S2 and another for S3 as shown in the picture.
• Max. 50m Total Max. for PEA-200, 250, 400, 500
Wiring size 3%1.5(Polar)
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord.
(Design 60245 IEC 57)
3. Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.
Phase
Frequency & Voltage
380/400/415V 50Hz
3 phase(4 wires)
3N~(3ph 4-wires), 50 Hz,
380 - 400 - 415 V
32 A
Isolator
A-Control
Outdoor Unit
S1
S2
S3
3 poles isolator
S1
S2
S3
A-Control
Indoor Unit
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation
between power line and communication signal line. Therefore, please turn off the main power supply when servicing.
And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use
3-pole type.
Synchronized twin and triple system Electrical wiring
• Synchronized twin• Synchronized triple
Outdoor
Unit
power
supply
Earth leakage breaker
Wiring circuit breaker or
isolating switch
Outdoor
unit
unit
L1
L2
3
L
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
Remote
controller
2
Indoor
unit
1
2
S1
S2
S3
Unit
power
supply
Earth leakage breaker
Wiring circuit breaker or
isolating switch
Outdoor
unit
L1
L2
L
3
N
Indoor/outdoor
connection cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
2
Remote
controller
Indoor
unit
1
2
S1
S2
S3
Indoor
unit
1
2
S1
S2
S3
14
Page 15
S1
S2
S3
Indoor/outdoor
unit connection
cable
Indoor
unit
Unit
power
supply
Unit
power
supply
Outdoor
unit No.1
L1
L2
L3
N
S1
S2
S3
L1
L2
L3
N
Earth leakage breaker
Wiring circuit breaker or
isolating switch
S1
S2
S3
Indoor/outdoor
unit connection
cable
TB4-1
TB4-2
Unit
power
supply
Outdoor
unit No.2
L
1
L2
L3
N
S1
S2
S3
1
2
Remote
controller
1:1 System (Indoor : PEA-200, 250)1:2 System (Indoor : PEA-400, 500)
Indoor
unit
L1
L2
L3
N
S1
S2
S3
1
Remote
controller
2
supply
Unit
power
Unit
power
supply
Earth leakage breaker
Wiring circuit breaker or
isolating switch
Outdoor
unit
1
L
L2
L3
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
8-2. SEPARATE INDOOR UNIT/ OUTDOOR UNIT POWER SUPPLIES
Simultaneous twin/triple/four system
<For models without heater>
The optional indoor power supply terminal kit is required.
*
L
1
L
2
L
3
N
S1
S2
S3
L
L
N
S1
S2
S3
1
2
L
N
N
S1
S1
S2
S2
S3
S3
1
1
2
2
L
N
S1
S2
S3
1
2
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table below.
If the optional indoor power supply terminal kit is used, change the indoor unit electrical
box wiring referring to the figure in the right and the DIP switch settings of the
outdoor unit control board.
Indoor unit specifications
Indoor power supply terminal kit (option)
Indoor unit electrical box connector connection change
Label affixed near each wiring diagram
for the indoor and outdoor units
Outdoor unit DIP switch settings (when
using separate indoor unit/outdoor unit
power supplies only)
ON
OFF
Required
Required
Required
3
12(SW8)
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Indoor unit power supplied from outdoor unit
(when shipped from factory)
Connectors (connections when shipped
from the factory are for indoor unit power
supplied from outdoor unit.)
BLUE
BLUE
YELLOW
YELLOW
CND
Set the SW8-3 to ON.
* There are 3 types of labels (Labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model
Indoor unit power supply
Indoor unit input capacity
Main switch (Breaker)
Indoor unit power supply
Indoor unit power supply earth
)
2
Indoor unit-Outdoor unit
(mm
Wiring
Indoor unit-Outdoor unit earth
Wire No. % size
Remote controller-Indoor unit
Indoor unit L-N*4
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
rating
Circuit
Remote controller-Indoor unit
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductor of the supply.
*2. Max. 120 m
*3. The 10 m wire is attached in the remote controller accessory. Max. 500 m
*4. The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and indoor unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed
flexible cable. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
*1
*2
*3
*4
*4
*4
15
RP35~140
~/N (single), 50 Hz, 230 V
16 A
2 % Min. 1.5
1 % Min. 1.5
2 % Min. 0.3
–
2 % 0.3 (Non-polar)
AC 230 V
–
DC24 V
DC12 V
control board
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cales
Remote controller
Indoor unit
Option
Indoor unit power supply
ORANGE
CND
Indoor unit
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Separate indoor unit/outdoor unit power
supplies
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.
BLUE
YELLOW
Connectors
CND
Indoor unit
control board
ORANGE
CND
YELLOW
BLUE
Page 16
8-3. INDOOR – OUTDOOR CONNECTING CABLE
WIRING SPECIFICATIONS FOR 220-240 V 50 Hz
(INDOOR-OUTDOOR CONNECTING CABLE)
Cross section of cableWire size (mm2)Number of wiresPolarityL (m)*6
Round
Flat
Flat
Round
2.53
2.53
1.54
2.54
Clockwise : S1-S2-S3
* Pay attention to stripe of yellow and green.
Not applicable
(Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Clockwise : S1-S2-S3-Open
*Connect S1 and S3 to the opposite angle.
Not applicable
(30)
*2
*5
(18)
*3
(30)
*4
*1 : Power supply cords of appliances shall not be lighter than design 60245 IEC or
227 IEC.
*2 : In case that cable with stripe of yellow and green is available.
*3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm.
*4 : In case of regular polarity connection (S1-S2-S3).
*5 : In the flat cables are connected as this picture, they can be used up to 30 m.
2
Indoor/Outdoor separate
power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
*6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity
or materials, etc.
Wire No. % Size ($)
Max. 120m
2 % Min. 0.3
—
(3C Flat cable 2)
+ The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient
insulation to ground or a poor electrical contact at the intermediate connection point.
16
Page 17
8-4. M-NET WIRING METHOD
(Points to notice)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET P.C. board may burn out.
(3) Use 2-core x 1.25mm
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
2
shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
Group
remote
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 00
M-NET
address 03
A-control
remote
controller
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the central-control remote controller.
Bad example (Multi spot grounding of shield wire)
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
Good example 1 (Single spot grounding of shield wire)
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
Good example 2 (Single spot grounding of shield wire)
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
If there are more than 2 grounding spots on the shield wire, noise may enter into the shield wire because the ground wire
and shield wire form 1 circuit and the electric potential difference occurs due to the impedance difference among grounding
spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and shield wire
do not form 1 circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
17
Page 18
ƔM-NET wiring
2
5
2
13
SW11
ones
digit
SW12
tens
digit
3
4
3
4
5
6
5
6
M-NET
terminal
block
M1 M2 S
Transmission
12
3
4
2
5
1
6
0
7
9
8
3
4
2
5
1
6
0
7
9
8
ON
OFF
1
3
4
5
2
6
6
ON
OFF
1
3
4
5
2
6
14
OFF
OFF
ON
ON
wire
3
2
1
0
9
8
3
2
1
0
9
8
1
1
Ground
wire
Shield
part
50
4
5
6
7
~
4
5
6
7
3
4
5
2
7
3
4
5
2
15
3
4
2
5
1
6
0
7
9
8
3
4
2
5
1
6
0
7
9
8
6
6
2
(1) Use 2-core x 1.25mm
shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block. Connect one core of the
transmission wire (non-polar) to M1 terminal and the other to M2. Peel the
shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(M1, M2, S) on M-NET terminal block should be individually wired to the other
outdoor unit’s terminal, i.e. M1 to M1, M2 to M2 and S to S. In this case, choose one of those outdoor units and drive a
screw to fix an ground wire on the plate as shown on the right figure.
8-4-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
<Setting example>
M-NET Address No.
(SW11 for ones digit and SW12 for tens digit), which
is located on the M-NET board of outdoor unit.
(Initial setting: all addresses are set to “0”.)
Switng
setting
8-4-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group setting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Initial setting: all
switches are OFF. (All refrigerant addresses are “00”.)]
Refrigerant
address
ON
OFF
1
ON
OFF
1
ON
OFF
1
3
4
5
2
6
0
ON
OFF
1
3
4
5
2
6
8
ON
OFF
1
3
4
5
2
6
1
ON
OFF
1
3
4
5
2
6
9
ON
OFF
1
3
4
5
2
6
2
ON
OFF
1
3
4
5
2
6
10
ON
OFF
1
3
4
5
2
6
3
ON
OFF
1
3
4
5
2
6
11
ON
OFF
1
3
4
5
2
6
4
ON
OFF
1
3
4
5
2
6
12
8-4-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above section. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
Group AGroup BGroup C
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
+ Refrigerant addresses can be overlapped if they are in the different group.
Group AGroup B
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
A-control
remote
controller
Refrigerant
address 01
M-NET
address 02
Refrigerant
address 01
M-NET
address 03
TB5
TB5
A-control
remote
controller
Refrigerant
address 00
M-NET
address 04
Refrigerant
address 00
M-NET
address 04
A-control
remote
controller
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 02
M-NET
address 05
+ In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the
group for the outdoor unit whose refrigerant address is “00”.
18
Page 19
9REFRIGERANT SYSTEM DIAGRAM
Unit : mm
PUHZ-RP200YHA2
Ball valve
Refrigerant GAS pipe
:25.4(:1 inch)
Refrigerant LIQUID pipe
:9.52(:3/8 inch)
Strainer
(#50)
Service
port
(check)
Accumulator
Stop valve
(with service port)
Strainer
(#40)
4-way valve
Strainer
(#100)
Restrictor
valve
Strainer
(#100)
Muffler
Compressor
Linear expansion
valve
Outdoor heat exchanger
High pressure
switch(63H)
Service
port
(check)
Thermistor
(TH4)
Refrigerant flow in cooling
Refrigerant flow in heating
Distributor
Strainer
(#100)
Thermistor
(TH7)
Thermistor
(TH6)
Thermistor
(TH3)
PUHZ-RP250YHA2
Ball valve
Refrigerant GAS pipe
:25.4(:1 inch)
Stop valve
(with service port)
Refrigerant LIQUID pipe
:12.7(:1/2 inch)
High pressure
switch(63H2)
Strainer
(#50)
Service
port
(check)
Strainer
(#100)
Linear
expansion valve B
Strainer
(#100)
Power
receiver
Restrictor
valve
Capillary tube
O.D.4.0I.D.3.0L500
4-way valve
Low pressure
switch(63L)
Linear expansion valve A
Muffler
Compressor
Replace
filter
High pressure
switch (63H1)
Service
port
(check)
Bypass valve
Heat exchanger
Thermistor (TH4)
(Discharge)
Strainer
(#100)
Thermistor (TH7)
Thermistor (TH6)
Thermistor (TH3)
Distributor
Replace filter
19
Bypass valve
Page 20
OFF
12
ON
<SW4>
Stop Operation
Cooling Heating
9-1. Refrigerant recovering (pump down)
Perform the following procedures to recover the refrigerant when moving the indoor unit or the outdoor unit.
Turn on the power supply (circuit breaker).
+When power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If
“CENTRALLY CONTROLLED” is displayed, the refrigerant recovering (pump down) cannot be completed normally.
After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor
(outdoor unit) and fans (indoor and outdoor units) start operating and refrigerant recovering operation begins. LED1 and
LED2 on the control board of the outdoor unit are lit.
+Set the SWP switch (push-button type) to ON in order to perform refrigerant recovering operation only when the unit is
stopped. However, refrigerant recovering operation cannot be performed until compressor stops even if the unit is stopped.
Wait 3 minutes until compressor stops and set the SWP switch to ON again.
Because the unit automatically stops in about 2 to 3 minutes after the refrigerant recovering operation (LED1 is not lit
and LED2 is lit), be sure to quickly close the gas stop valve.
+In case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then
repeat step
3 minutes later.
+If the refrigerant recovering operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain
stopped until the power supply is turned off.
Turn off the power supply (circuit breaker.)
9-2. Unit replacement operation
When reusing the existing pipes that carried R22 refrigerant for the RP200 and RP250 models, replacement operation
must be performed before performing a test run.
If new pipes are used, these procedures are not necessary.
During replacement operation, “C5” is displayed on “A-Control Service Tool(PAC-SK52ST)”.
Replacement operation procedures
Turn on the power supply.
Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start replacement operation.
• The replacement operation is performed using the cooling system. Cool air will flow from the indoor unit during the replace-
ment operation.
TEST RUN
• During the replacement operation,
control board of the outdoor unit blink together.
The duration of the replacement operation is determined by the length of the piping. Always perform the replacement
operation for longer than the stipulated time.
* Use one of he following methods to complete replacement operation. When the replacement operation ends, the unit will
automatically stop.
(1)Set SW8-2 from ON to OFF. (When ending a replacement operation of
less than 2 hours.)
• Each time SW8-2 is set from OFF to ON, the replacement operation can
be started. Always perform the replacement operation for longer than the
stipulated time.
(2) The replacement operation will automatically stop after 2 hours. (It will end with SW8-2 still in the ON position.)
• When the replacement operation has ended automatically after 2 hours of operation, there is no need to set SW8-2 from
ON to OFF; normal air conditioning operations can be started with the SW8-2 being set to ON. However, to repeat the
replacement operation, SW8-2 will have to be returned to OFF and then set to ON.
is displayed on the remote controller and LED1 (green) and LED2 (red) on the
<Required replacement operation times>
Piping Length
0 to 20 meters 30 minutes or more
21 to 30 meters 45 minutes or more
31 to 70 meters 60 minutes or more
"Replacement
Operation Time"
9-3. Start and finish of test run
• Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
Set the operation mode (cooling/heating) using SW4-2.
Turn on SW4-1 to start test run with the operation mode set by SW4-2.
Turn off SW4-1 to finish the test run.
• There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion valve is just moving to adjust opening pulse.
• There may be a knocking sound around the machine room for several seconds after compressor
starts operating, but this is no problem with product because the check valve, itself, generates the
sound since pressure difference is small in the refrigerant circuit.
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
20
Page 21
10TROUBLESHOOTING
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.
Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the
table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action according
to “10-4. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the
trouble according to “10-5. Troubleshooting by inferior
phenomena”.
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring and etc.
Reset error code logs and restart the unit after finishing
service.
There is no abnormality in electrical component,
controller board, remote controller and etc.
Re-check the abnormal symptom.
Conduct trouble shooting and ascertain the cause of the
trouble
phenomena”.
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
according to “10-5. Troubleshooting
by inferior
10-2. CHECK POINT UNDER TEST RUN
(1) Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Megger and
check that it is 1.0M or over.
+Don’t use 500V Megger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Turn on power supply 12 hours before test run in order to protect compressor.
• For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “11. Function setting”.
• Make sure to read operation manual before test run. (Especially items to secure safety.)
21
Page 22
"TEST RUN" and the currently selected
operation mode are displayed altemately.
Displays the remaining
test run time.
[TEST] button
Pipe (liquid) temperature
Operating procedures
1. Turn on the main power supply.
2. Press TEST button twice.
3. Press OPERATION SWITCH
button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for
correct running.
6. Press the ON/OFF button to reset the test run in progress.
7. Register the contact number.
While the room temperature display on the remote
controller is “PLEASE WAIT”, the remote controller is disabled.
Wait until “PLEASE WAIT” disappears before using remote controller.
“PLEASE WAIT” appears for about 2 minutes after power
supply is turned on. +1
The TEST RUN appears on the screen.
Cooling mode:
Heating mode: Check if warm air blows. (It takes a little
while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to
provide optimum fan speeds. Therefore, the fan keeps
running at a low speed to meet the current outside air
condition unless it exceeds its available maximum power.
Then, in actuality, the fan may stop or run in the reverse
direction depending on the outside air, but this does not
mean malfunction.
Check if cool air blows and water is drained.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after 2 hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin, triple and quadruple operation. Malfunctions
may not be displayed regardless of incorrect wiring.
+1 After turning on the power supply, the system will go into startup mode, “PLEASE WAIT” will blink on the display section
of the room temperature, and lamp(green) of the remote controller will blink.
As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case the
address is not 0. LED3 will blink.
As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will be lit up. (After the startup mode of the system finishes,
LED2(red) will be turned off.)
In case OUTDOOR BOARD LED is digital display, — and — will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from
the symptoms.
The below symptoms are under test run mode. “startup” in the table means the display status of +1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “PLEASE
WAIT”, and
After power is turned on, “PLEASE WAIT”
is displayed for 3 minutes, then error code
is displayed.
No display appears even when remote
controller operation switch is turned on.
(Operation lamp does not light up.)
Display appears but soon disappears
even when remote controller is operated.
+Press the remote controller’s
LCD
P1
P2
P4
P5
P6
P8
P9
Fb
cannot be operated.
CHECK
Contents of trouble
Abnormality of room temperature thermistor
Abnormality of pipe temperature thermistor/Liquid
Abnormality of drain sensor/ Float switch connector open
Drain overflow protection is working.
Freezing/overheating protection is working.
Abnormality of pipe temperature
Abnormality of pipe temperature thermistor/Cond./Eva
Abnormality of indoor controller board
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed,
green(once) and red(once) blink
alternately. <F1>
After “startup” is displayed,
green(once) and red(twice) blink
alternately. <F3, F5, F9>
After “startup” is displayed,
green(twice) and red(once) blink
alternately. <EA. Eb>
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed, only
green lights up. <00>
• After power is turned on, “PLEASE WAIT” is displayed for 2
minutes during
• Outdoor unit’s protection device connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity
is wrong for S1, S2, S3.)
• Remote controller transmission wire is short.
• There is no outdoor unit of address 0.
(Address is other than 0.)
• Remote controller transmission wire is open.
• After canceling function selection, operation is not possible for
about 30 seconds. (Normal)
system startup. (Normal)
button twice to perform self-diagnosis. See the table below for the contents of LCD dis-
LCD
Malfunction outdoor unit
U1~UP
Malfunction
F3~F9
E0~E5
Remote controller transmitting error
E6~EF
Indoor/outdoor unit communication error
No error history
---No applied unit
FFFF
Forced compressor stop(due to water leakage abnormality)
PA
outdoor unit
Contents of trouble
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
(microcomputer power supply)
LED1
(remote controller)
LED2
(indoor/outdoor communication)
LED3
Lits when power is supplied.
Lits when power is supplied for wired remote controller.
The indoor unit should be connected to the outdoor unit with address “0” setting.
Blinks when indoor and outdoor unit are communicating.
Cause
1, L2, L3 and
22
Page 23
TEST RUN
TEST RUN
MODE
MODE
HEAT
FAN
VANE
,
ON/OFF
MODE
CHECK
TEST RUN
SET
TEST RUN
FAN
VANE
LOUVER
RESET
CLOCK
TEMP
AUTO STOP
AUTO START
h
min
Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M.
Turn on the main power to the unit.
Press the
(Start this operation from the status of remote controller display
turned off.)
and current operation mode are displayed.
A
Press the
check whether cool air is blown out from the unit.
Press the
check whether warm air is blown out from the unit.
Press the
from the unit.
Press the
properly.
Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps to .
• It is not possible to run in FAN, DRY or AUTO mode.
button twice continuously.
( ) button to activate
( ) button to activate
COOL
mode, then
mode, then
button and check whether strong air is blown out
button and check whether the auto vane operates
23
Page 24
10-3. HOW TO PROCEED "SELF-DIAGNOSIS"
10-3-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop,
and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the temperature
display, and the error code and unit number are displayed alternately as
shown below.
(If the outdoor unit is malfunctioning, the unit number will be "00".)
In the case of group control, for which one remote controller controls
multiple refrigerant systems, the refrigerant address and error code of the
unit that first experienced trouble (i.e., the unit that transmitted the error
code) will be displayed.
To clear the error code, press the button.
Error code (2 or 4 digits)
ON/OFF
(Alternating Display)
Address (3 digits) or unit number (2 digits)
When using remote-/local-controller combined operation, cancel the error code after turning off remote operation. During
central control by a MELANS controller, cancel the error code by pressing the
ON/OFF
button.
10-3-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote
controller or power is turned off.
Check the error code history for each unit using the remote controller.
Switch to self-diagnosis mode.
Press the
will change as shown below.
CHECK
button twice within 3 seconds. The display content
Unit number or refrigerant address
to be diagnosed
Set the unit number or refrigerant address you want to diagnose.
Press the [TEMP] buttons ( and ) to select the desired number
or address. The number (address) changes between [01] and [50] o r [00]
an d
[15].
The refrigerant address will begin to blink
approximately 3 seconds after being
selected and the self-diagnosis process will begin.
Display self-diagnosis results.
<When there is error code history>
(Alternating Display)
Error code (2 or 4 digits)
<When there is no error code history><When there is no corresponding unit>
Address (3 digits) or unit number (2 digits)
Reset the error history.
Display the error history in the diagnosis result display screen (see step
).
24
Page 25
CHECK
Press the
address or refrigerant address will blink.
Cancel self-diagnosis.
Self-diagnosis can be cancelled by the following 2 methods.
Press the
Press the
ON/OFF
CHECK
ON/OFF
button twice within 3 seconds. The self-diagnosis
button twice within 3 seconds. Self-diagnosis will be cancelled and the screen will return to the previous state in effect before the
button. Self-diagnosis will be cancelled and the indoor unit will stop.
start of self-diagnosis.
When the error history is reset, the display will look like the one shown below.
However, if you fail to reset the error history, the error content will be displayed
again.
10-3-3. Remote Controller Diagnosis
If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.
First, check that the power-on indicator is lit.
If the correct voltage (DC12 V) is not supplied to the remote controller, the
indicator will not light.
If this occurs, check the remote controller's wiring and the indoor unit.
Power on indicator
Switch to the remote controller self-diagnosis mode.
Press the
will change as shown below.
CHECK
button for 5 seconds or more. The display content
Press the
FILTER
button to start self-diagnosis.
Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
Check for other possible causes, as there is no problem with the remote
controller.
[Where the remote controller is not defective, but cannot be operated.]
(Error display 2) [E3], [6833] or [6832] blinks.
There might be noise or interference on the transmission path, or the indoor
unit or other remote controllers are defective. Check the transmission path
and other controllers.
The remote controller must be replaced with a new one.
(Error display 3)
The number of data errors is the difference between the number of bits sent
from the remote controller and the number actually transmitted through the
transmission path. If such a problem is occurring, the transmitted data is
affected by noise, etc. Check the transmission path.
Press the
approximately 30 seconds, the state in effect before the diagnosis will be restored.
button for 5 seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will blink. After
25
Page 26
10-3-4. Malfunction-diagnosis method by wireless remote controller
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
CHECK
display
ON/OFF
button
CHECK
button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VANE
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
h
min
Refrigerant
address
display
Temperature
button
HOUR
button
1. Press the CHECK button twice.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit tent buzzer sound, the operation lamp
blinks, and the error code is output.
(It takes 3 seconds at most for error
code to appear.)
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• The check mode is cancelled.
26
Page 27
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp blink
pattern
Beep
Self-check
starts
(Start signal
received)
Beep Beep BeepBeepBeep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
rd
0.5 sec.
th
n
On
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
[Output pattern B]
Beeper sounds
OPERATION
INDICATOR
lamp blink
pattern
BeepBeep Beep BeepBeep
1st2nd3
Off
Self-check
starts
(Start signal
received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
PAForced compressor stop(due to water leakage abnormality)
6P6Freezing/Overheating protection operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
11
–
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
Remote controller transmission error
–E1, E2Remote controller control board error
nd
1st2
Off
Number of blinks/beeps in pattern indicates
the check code in the following table
rd
th
n
On
0.5 sec.
· · · Repeated
Beep Beep
nd
1st2
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
· · · Repeated
SymptomRemark
As for indoor
unit, refer to
indoor unit's
service manual.
[Output pattern B]
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinksCheck code
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
SymptomRemark
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
E9
UP
U3,U4
UF
U2
U1,Ud
U5
U8
U6
U7
U9,UH
–
–
Others
*1 If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating
protection operation
Abnormal temperature of heatsink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormality of power module
Abnormality of superheat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
For details, check
the LED display
of the outdoor
controller board.
*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
27
Page 28
10-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
Error Code
Abnormal point and detection method
No voltage is supplied to terminal
block(TB1) of outdoor unit.
a) Power supply breaker is
b) Contact failure or disconnec-
c) Open phase (L2 or N phase)
(Note 1) Refer to indoor unit section for code P and code E.
Case
Check following items.
a) Power supply breaker
b), c) Connection of power supply terminal
turned off.
tion of power supply
terminal
Judgment and action
block(TB1)
None—
63L connector open
Abnormal if 63L connector circuit is open
for 3 minutes continuously after power supply.
F3
(5202)
63L: Low-pressure switch
<RP250 only>
Electric power is not supplied to
outdoor controller circuit board.
a) Disconnection of connector
(CNDC)
Disconnection of reactor
(ACL4)
Disconnection of outdoor noise
filter circuit board or parts failure in outdoor noise filter circuit
board
Defective outdoor controller
circuit board
Disconnection or contact failure
of 63L connector on outdoor
controller circuit board.
Disconnection or contact failure
of 63L.
63L is working due to refriger-
ant leakage or defective parts.
Defective outdoor controller
circuit board.
Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector CNDC on
the outdoor noise filter circuit board.
Refer to 10-9.
Check connection of reactor. (ACL4)
a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 10-9.
Replace controller board (When items above
are checked but the units cannot be repaired).
Check connection of 63L connector on
outdoor controller circuit board.
Refer to 10-9.
Check the 63L side of connecting wire.
Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace the parts if the parts are defective.
Replace outdoor controller circuit board.
F5
(5201)
F9
(4119)
63H connector open
Abnormal if 63H connector circuit is open
for 3 minutes continuously after power supply.
63H: High-pressure switch
2 connector open
Abnormal if both 63H and 63L connector
circuits are open for 3 minutes continuously
after power supply.
of 63H connector on outdoor
controller circuit board
Disconnection or contact failure
of 63H
63H is working due to defective
parts.
Defective outdoor controller
circuit board
Disconnection or contact failure
of connector (63H,63L) on
outdoor controller circuit board.
Disconnection or contact failure
of 63H, 63L.
63H and 63L are working due
to defective parts.
Defective outdoor controller
circuit board.
Check connection of 63H connector on
outdoor controller circuit board.
Refer to 10-9.
Check the 63H side of connecting wire.
Check continuity by tester.
Replace the parts if the parts are defective.
Replace outdoor controller circuit board.
Check connection of connector(63H,63L) on
outdoor controller circuit board.
Refer to 10-9.
Check the 63H and 63L side of connecting
wire.
Check continuity by tester.
Replace the parts if the parts are defective.
Replace outdoor controller circuit board.
28
Page 29
Error Code
EA
(6844)
Eb
(6845)
Abnormal point and detection method
Indoor/outdoor unit connector
miswiring, excessive number of units
1. Outdoor controller circuit board can
automatically check the number of
connected indoor units. Abnormal if the
number cannot be checked automatically due to miswiring of indoor/outdoor
unit connecting wire and etc. after power
is turned on for 4 minutes.
2. Abnormal if outdoor controller circuit
board recognizes excessive number of
indoor units.
Miswiring of indoor/outdoor unit
connecting wire (converse wiring or disconnection)
Outdoor controller circuit board can
automatically set the unit number of indoor
units.
Abnormal if the indoor unit number cannot be set within 4 minutes after power on
because of miswiring (converse wiring or
disconnection) of indoor/outdoor unit connecting wire.
Case
Contact failure or miswiring of
indoor/outdoor unit connecting
wire
Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
Excessive number of indoor
units are connected to 1 outdoor unit.(5 units or more)
Defective transmitting receiving
circuit of outdoor controller
circuit board
Defective transmitting receiving
circuit of indoor controller board
Defective indoor power board
2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
Noise has entered into power
supply or indoor / outdoor unit
connecting wire.
Contact failure or miswiring of
indoor/outdoor unit connecting
wire
Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
Defective transmitting receiving
circuit of outdoor controller circuit
board
Defective transmitting receiving
circuit of indoor controller board
Defective indoor power board
2 or more outdoor units have
refrigerant address “0”.
(In case of group control)
Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
Judgment and action
Check disconnection or looseness or polar-
ity of indoor/outdoor unit connecting wire of
indoor and outdoor units.
Check diameter and length of indoor/outdoor
unit connecting wire.
Total wiring length: 80m
(Including wiring connecting each indoor unit
and between indoor and outdoor unit)
Also check if the connection order of flat
cable is S1, S2, S3.
Check the number of indoor units that are
connected to one outdoor unit. (If EA is
detected.)
~ Turn the power off once, and on again to
check.
Replace outdoor controller circuit board,
indoor controller board or indoor power
board if abnormality occurs again.
Check if refrigerant addresses (SW1-3 to
SW1-6 on outdoor controller circuit board)
are overlapping in case of group control
system.
Check transmission path, and remove the
cause.
+ The descriptions above, -, are for EA, Eb
and EC.
EC
(6846)
Start-up time over
The unit cannot finish start-up process
within 4 minutes after power on.
Contact failure of indoor/
outdoor unit connecting wire
Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
29
Page 30
<Abnormalities detected while unit is operating>
Error Code
U1
(1302)
Abnormal point and detection method
High pressure (High-pressure switch
63H(RP200)/63H1 or 63H2(RP250)
worked)
Abnormal if high-pressure switch
63H(RP200)/63H1 or 63H2(RP250) worked
( + ) during compressor operation.
+ 63H1: 4.15 MPa
63H, 63H2: 3.6 MPa
63H, 63H1, 63H2: High-pressure switch
Case
Short cycle of indoor unit
Clogged filter of indoor unit
Decreased airflow caused by
dirt of indoor fan
Dirt of indoor heat exchanger
Locked indoor fan motor
Malfunction of indoor fan motor
Defective operation of stop
valve (Not fully open)
Clogged or broken pipe
Locked outdoor fan motor
Malfunction of outdoor fan
motor
Short cycle of outdoor unit
Dirt of outdoor heat exchanger
Decreased airflow caused by
defective inspection of outside
temperature thermistor
(It detects lower temperature
than actual temperature.)
Disconnection or contact failure
of connector (63H) on outdoor
controller board
Disconnection or contact failure
of 63H connection
Defective outdoor controller
board
Defective action of linear
expansion valve
Malfunction of fan driving
circuit
Judgment and action
~Check indoor unit and repair defect.
Check if stop valve is fully open.
Check piping and repair defect.
~ Check outdoor unit and repair defect.
Check the inspected temperature of outside
temperature thermistor on LED display.
(SW2 on A-Control Service Tool : Refer to
10-10.)
~Turn the power off and check F5 is
displayed when the power is turned again.
When F5 is displayed, refer to “Judgment
and action” for F5.
Check linear expansion valve.
Refer to 10-7.
Replace outdoor controller board.
U2
(1102)
U3
(5104)
High discharging temperature
(1) Abnormal if discharge temperature ther-
mistor (TH4) exceeds 125or 110
continuously for 5 minutes.
Abnormal if condenser/evaporator tem
perature thermistor (TH5) exceeds 40
during defrosting and discharge temperature thermistor (TH4) exceeds 110
Open/short circuit of discharge
temperature thermistor (TH4)
Abnormal if open (3 or less) or short
(217 or more) is detected during
compressor operation.
(Detection is inoperative for 10 minutes
of compressor starting process and for 10
minutes after and during defrosting.)
which become below freezing point when water enters in
refrigerant circuit.
Disconnection or contact
failure of connector (TH4) on
the outdoor controller circuit
board
Defective thermistor
Defective outdoor controller
circuit board
Check intake superheat.
Check leakage of refrigerant.
Charge additional refrigerant.
Check if stop valve is fully open.
Turn the power off and check if U3 is dis-
played when the power is turned on again.
When U3 is displayed, refer to “Judgement
and action” for U3.
Check linear expansion valve.
Refer to 10-7.
After recovering refrigerant, remove water
from entire refrigerant circuit under vacuum
more than 1 hour.
Check connection of connector (TH4) on the
outdoor controller circuit board.
Check breaking of the lead wire for
thermistor (TH4). Refer to 10-9.
Check resistance value of thermistor (TH4) or
temperature by microcomputer.
(Thermistor/TH4: Refer to 10-7.)
(SW2 on A-Control Service Tool: Refer to
10-10.)
Replace outdoor controller board.
30
Page 31
Thermistors
Open detectionShort detection
Symbol
Name
TH3
TH6
TH7
TH8
– 40 or below
– 40 or below
– 40 or below
– 35 or below
90 or above
90 or above
90 or above
170or above
Thermistor <Outdoor pipe>
Thermistor <Outdoor 2-phase pipe>
Thermistor <Outdoor>
Thermistor <Heatsink>
Error Code
U4
(TH3:5105)
(TH6:5107)
(TH7:5106)
(TH8:5110)
Abnormal point and detection method
Open/short of outdoor unit thermistors
(TH3, TH6, TH7, and TH8)
Abnormal if open or short is detected
during compressor operation.
Open detection of thermistors TH3 and
TH6 are inoperative for 10 seconds to 10
minutes after compressor starting and 10
minutes after and during defrosting.
Check which unit has abnormality in its
thermistor by switching the mode of SW2.
(PAC-SK52ST)
(Refer to 10-10.)
Heatsink thermistor(TH8) is in the power
module.
Case
Disconnection or contact failure
of connectors
Outdoor controller circuit
(
board: TH3,TH7/6
Defective thermistor
Defective outdoor controller
circuit board
Defective outdoor power circuit
board (TH8 open/ short)
)
Judgment and action
Check connection of connector (TH3,TH7/6) on
the outdoor controller circuit board.
Check breaking of the lead wire for thermistor
(TH3,TH6,TH7). Refer to 10-9.
Check resistance value of thermistor
(TH3,TH6,TH7) or check temperature by
microcomputer.
(Thermistor/TH3,TH6,TH7 : Refer to 10-7.)
(SW2 on A-Control Service Tool:
Refer to 10-10.)
Replace outdoor controller circuit board.
Replace outdoor power circuit board.
Emergency operation is available in case of
abnormalities of TH3, TH6 and TH7.
Refer to 10-8.
Temperature of heatsink
Abnormal if heatsink thermistor(TH8)
detects temperature 95.+Heatsink thermistor is in the power mod-
ule.
U5
(4230)
Power module
Check abnormality by driving power module
in case overcurrent is detected.
U6
(4250)
U8
(4400)
(UF or UP error condition)
Outdoor fan motor
The outdoor fan motor is considered to be
abnormal if the rotational frequency of fan
motor is abnormal when detected during
operation.
Fan motor rotational frequency is abnormal if;
• 100 rpm or below detected continuously
for 15 seconds at 20 or more outside
air temperature.
• 50 rpm or below or 1500 rpm or more
detected continuously for 1 minute.
The outdoor fan motor is
locked.
Failure of outdoor fan motor
Air flow path is clogged.
Rise of ambient temperature
Defective thermistor
Defective input circuit of
outdoor power circuit board
Failure of outdoor fan drive circuit
Outdoor stop valve is closed.
Decrease of power supply voltage
Looseness, disconnection or
converse of compressor wiring
connection
Defective compressor
Defective outdoor power circuit
board
Failure in the operation of
the DC fan motor
Failure in the outdoor circuit
controller board
31
Check outdoor fan.
Check air flow path for cooling.
Check if there is something which causes
temperature rise around outdoor unit.
(Upper limit of ambient temperature is 46.)
Turn off power, and on again to check if U5
is displayed within 30 minutes.
If U4 is displayed instead of U5, follow the
action to be taken for U4.
Check temperature(TH8) by microcomputer.
(SW2 on A-Control Service Tool: Refer to
10-10.)
Replace outdoor power circuit board.
Replace outdoor controller circuit board.
Open stop valve.
Check facility of power supply.
Correct the wiring (U·V·W phase) to
compressor. Refer to 10-9 (Outdoor power
circuit board).
Check compressor referring to 10-6.
Replace outdoor power circuit board.
Check or replace the DC fan motor.
Check the voltage of the outdoor circuit
controller board during operation.
Replace the outdoor circuit controller
board. (When the failure is still indicated
even after performing the remedy
above.)
Page 32
Error Code
U9
(4220)
Ud
(1504)
Abnormal point and detection method
Abnormality such as overvoltage or
voltage shortage and abnormal
synchronous signal to main circuit
Abnormal if any of followings are detected
during compressor operation;
• Instantaneous decrease of DC bus volt-
age to 400V
• Increase of DC bus voltage to 760V
• Decrease of input current of outdoor unit
to 0.5A only if operation frequency is
more than or equal to 40Hz or compressor current is more than or equal to 5A.
Overheat protection
Abnormal if outdoor pipe thermistor (TH3)
detects 70or more during compressor
operation.
Case
Decrease of power supply voltage
Disconnection of compressor
wiring
Defective 52C drive circuit of
outdoor power circuit board
Disconnection or loose con-
nection of CN5 on the outdoor
power circuit board
Disconnection or loose con-
nection of CN2 on the outdoor
power circuit board
Defective outdoor controller cir-
cuit board
Defective outdoor fan (fan
motor) or short cycle of outdoor
unit during cooling operation
Defective outdoor pipe ther-
mistor (TH3)
Defective outdoor controller board
Judgment and action
Check the facility of power supply.
Correct the wiring (U·V·W phase) to compressor.
Refer to 10-9 (Outdoor power circuit board).
Replace outdoor power circuit board.
Check CN5 wiring on the outdoor power
circuit board. Refer to 10-9.
Check CN2 wiring on the outdoor power
circuit board. Refer to 10-9.
Replace outdoor controller circuit board.
Check outdoor unit air passage.
Turn the power off and on again to check
the error code. If U4 is displayed, follow the
U4 processing direction.
Abnormal if overcurrent of DC bus or
compressor is detected within 30 seconds
after compressor starts operating.
Compressor current sensor error or
input current error
Abnormal if compressor current sensor
detects –1.0A to 1.0A within 3 minutes
after compressor starts operating. (This
error is ignored in case of test run mode.)
Low pressure(RP200)
Abnormal if the following conditions are
detected for continuously 1-3 minutes after
compressor starts heating operation for 5
minutes.
1. Heating mode
Detection mode1
TH7-TH34 and
TH5-Indoor room temperature2
Detection mode2
TH7-TH32and
TH5-Indoor room temperature4 and
TH2-Indoor room temperature4
2.Cooling mode
TH6-TH72 and
TH3-TH72and
Indoor room temperature - Indoor liquid
pipe temperature (TH2)5
Thermistor
TH3 : Outdoor liquid pipe temperature
TH5 : Indoor cond./eva. temperature
TH6 : Outdoor 2-phase pipe temperature
TH7 : Outdoor temperature
Stop valve is closed.
Decrease of power supply voltage
Looseness, disconnection or
converse of compressor wiring
connection
Defective compressor
Defective outdoor power board
Dip switch setting difference of
outdoor controller circuit board
Disconnection of compressor
wiring
Defective circuit of current
sensor on outdoor power
circuit board
Stop valve of outdoor unit is
closed during operation.
Leakage or shortage of refrigerant
Malfunction of linear expansion
valve
Clogging with foreign objects in
refrigerant circuit
+Clogging occurs in the parts
which become below freezing point when water enters in
refrigerant circuit.
Open stop valve.
Check facility of power supply.
Correct the wiring (U·V·W phase) to
compressor.
Refer to 10-9 (Outdoor power circuit board).
Check compressor.
Refer to 10-6.
Replace outdoor power circuit board.
Check the dip switch setting of outdoor con-
troller circuit board.
Correct the wiring (U·V·W phase) to
compressor. Refer to 10-9 (Outdoor power
circuit board).
Replace outdoor power circuit board.
Check stop valve.
Check intake superheat.
Check leakage of refrigerant.
Check additional refrigerant.
Check linear expansion valve.
Refer to 10-7.
After recovering refrigerant, remove water
from entire refrigerant circuit under vacuum
more than 1 hour.
32
Page 33
Error Code
UL
(1300)
UP
(4210)
Abnormal point and detection method Judgment and action
Low pressure (63L worked)(RP250)
Abnormal if 63L is worked (under
-0.03MPa) during compressor operation.
63L: Low-pressure switch
Compressor overcurrent interruption
Abnormal if overcurrent DC bus or compressor is detected after compressor starts
operating for 30 seconds.
Stop valve of outdoor unit is
closed during operation.
Disconnection or loose con-
nection of connector (63L) on
outdoor controller circuit board
Disconnection or loose connec-
tion of 63L
Defective outdoor controller cir-
cuit board
Leakage or shortage of refrigerant
Malfunction of linear expansion
valve
Stop valve of outdoor unit is
closed.
Decrease of power supply volt-
age
Looseness, disconnection or
converse of compressor wiring
connection
Defective fan of indoor/outdoor
units
Short cycle of indoor/outdoor
units
Defective input circuit of out-
door controller board
Defective compressor
Defective outdoor power circuit
board
Dip switch setting difference of
outdoor controller circuit board
Case
Check stop valve.
~ Turn the power off and on again to check
if F3 is displayed on restarting.
If F3 is displayed, follow the F3 process-
ing direction.
Correct to proper amount of refrigerant.
Check linear expansion valve.
Refer to 10-7.
Open stop valve.
Check facility of power supply.
Correct the wiring (U·V·W phase) to com-
pressor. Refer to 10-9 (Outdoor power circuit
board).
ler circuit board, disconnect the wiring to compressor from the outdoor power circuit board
and check the output voltage among phases,
U, V, W, during test run. No defect on board
if voltage among phases (U-V, V-W and W-U)
is same. Make sure to perform the voltage
check with same performing frequency.
Check compressor. Refer to 10-6.
Replace outdoor power circuit board.
Check the dip switch setting of outdoor con-
troller cannot receive any transmission
normally from indoor unit of refrigerant
address “0” for 3 minutes.
(Error code : E0)
Abnormal if sub-remote controller could
not receive any signal for 2 minutes.
(Error code: E0)
Abnormal if indoor controller board can
not receive any data normally from
or
or
remote controller board or from other
indoor controller board for 3 minutes.
(Error code: E4)
Indoor controller board cannot receive
any signal from remote controller for 2
minutes. (Error code: E4)
Remote controller control board
Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
Abnormal if the clock function of remote
controller cannot be operated normally.
(Error code: E2)
Contact failure at transmission
wire of remote controller
All remote controllers are set
as “sub” remote controller.
In this case, E0 is displayed
on remote controller, and E4
is displayed at LED (LED1,
LED2) on the outdoor controller
circuit board.
Miswiring of remote controller
Defective transmitting receiving
circuit of remote controller
Defective transmitting receiv-
ing circuit of indoor controller
board of refrigerant address “0”
mitted data at the same time, compares
the data,and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E5)
Indoor/outdoor unit communication
error (Signal receiving error)
(Outdoor unit)
(1) Abnormal if outdoor controller circuit
board could not receive anything
normally for 3 minutes.
Indoor/outdoor unit communication
error (Transmitting error) (Outdoor unit)
(1) Abnormal if “0” receiving is detected 30
times continuously though outdoor controller circuit board has transmitted “1”.
(2) Abnormal if outdoor controller circuit
board could not find blank of transmission path for 3 minutes.
Non defined error code
This code is displayed when non defined
error code is received.
2 remote controllers are set as
“main.”
(In case of 2 remote controllers)
Remote controller is connected
with 2 indoor units or more.
Repetition of refrigerant
address
Defective transmitting receiving
circuit of remote controller
Defective transmitting receiv-
ing circuit of indoor controller
board
Noise has entered into trans-
mission wire of remote controller.
Contact failure of indoor/out-
door unit connecting wire
Defective communication cir-
cuit of outdoor controller circuit
board
Defective communication circuit
of indoor controller board
Noise has entered into indoor/
outdoor unit connecting wire.
Indoor/ outdoor unit connecting
wire has contact failure.
Defective communication cir-
cuit of outdoor controller circuit
board
Noise has entered power sup-
ply.
Noise has entered indoor/ out-
door unit connecting wire.
Noise has entered transmission
wire of remote controller.
Noise has entered indoor/ out-
door unit connecting wire.
Outdoor unit is not a inverter
models.
Model name of remote control-
ler is PAR-S25A.
Case
Set a remote controller to main, and the
other to sub.
Connect remote controller with only one
indoor unit.
Change the address to a separate setting.
~Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When “RC NG” is displayed, replace
remote controller.
c)When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormal-
ity.
Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor or outdoor units.
~ Turn the power off, and on again to
check. Replace indoor controller board or
outdoor controller circuit board if abnormality is displayed again.
Check disconnection or looseness of indoor/
outdoor unit connecting wire.
~ Turn the power off, and on again to
check. Replace outdoor controller circuit
board if abnormality is displayed again.
Turn the power off, and on again to check.
Replace indoor controller board or outdoor
controller circuit board if abnormality is
displayed again.
Replace outdoor unit with inverter type out-
door unit.
Replace remote controller with MA remote
controller.
Ed
(0403)
Serial communication error
1.Abnormal if serial communication
between outdoor controller circuit
board and outdoor power circuit board
is defective.
2. Abnormal if communication between
outdoor controller circuit board and
M-NET board is not available.
Breaking of wire or contact
failure of connector CN2
between the outdoor controller
circuit board and the outdoor
power circuit board
Breaking of wire or contact
failure of connector CN4
between the outdoor controller
circuit board and the outdoor
power circuit board
Defective communication circuit
of outdoor power circuit board
Defective communication cir-
cuit of outdoor controller circuit
board for outdoor power circuit
board
Breaking of wire or contact
failure of connector between
outdoor controller circuit board
and M-NET board
Contact failure of M-NET board
power supply line
Noise has entered into M-NET
transmission wire.
34
Check connection of each connector CN2
and CN4 between the outdoor controller
circuit board and the outdoor power circuit
board.
Replace outdoor power circuit board.
Replace outdoor controller circuit board.
Check disconnection, looseness, or breaking
of connection wire between outdoor controller circuit board (CNMNT) and M-NET board
(CN5).
Check disconnection, looseness, or breaking
of connection wire between outdoor controller circuit board(CNMNT) and M-NET board
(CND).
Check M-NET transmission wiring method.
Page 35
Error Code
1234 56
ON
OFF
1234 56
ON
OFF
123456
ON
OFF
123456
ON
OFF
A-Control Service Tool SW2 setting
Temperature display of indoor liquid pipe
Indoor 1
Temperature display of indoor liquid pipe
Indoor 2
Temperature display of indoor condenser/
evaporator pipe Indoor 1
Temperature display of indoor condenser/
evaporator pipe Indoor 2
P8
(1110)
Abnormal point and detection method
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporator pipe
is out of cooling range.
Note 1) It takes at least 9 minutes to
detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : Indoor pipe temperature
(TH2 or TH5) – room temperature
(TH1) -3
TH: Lower temperature between liquid pipe
temperature and condenser/
evaporator temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
between indoor room
temperature and pipe <liquid
or condenser / evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
Converse connection of
extension pipe (on plural units
connection)
Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
Defective detection of indoor
room temperature and pipe
<condenser / evaporator>
temperature thermistor
Stop valve is not opened
completely.
Judgment and action
~Check pipe <liquid or condenser / evapo-
rator> temperature with room temperature display on remote controller and
outdoor controller circuit board.
Pipe <liquid or condenser / evaporator>
temperature display is indicated by setting SW2 of outdoor controller circuit
board as follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
)
Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
<M-NET communication error>(Note) “Indoor unit” in the text indicates M-NET board in outdoor unit.
Error CodeAbnormal point and detection method CaseJudgment and action
(6600)
(6602)
(6603)
Address duplicate definition
This error is displayed when transmission
A0
from the units of same address is detected.
Note) The address and attribute displayed
at remote controller indicate the controller that detected abnormality.
Hardware error of transmission
processor
Transmission processor intended to transmit “0”, but “1” appeared on transmission
A2
wire.
Note) The address and attribute displayed
at remote controller indicate the controller that detected abnormality.
BUS BUSY
1. Overtime error by signal collision damage
Abnormal if transmitting signal is not
possible for 8-10 minutes continuously
because of collision of transmission.
2. Data could not reach transmission wire
for 8-10 minutes continuously because
of noise or etc.
A3
Note) The address and attribute displayed
at remote controller indicate the controller that detected abnormality.
There are 2 or more same
address of controller of outdoor unit, indoor unit, FRESH
MASTER, or LOSSNAY.
Noise has entered into trans-
mission signal and signal was
transformed.
Error is detected if waveform is
transformed when wiring works of
transmission wire of outdoor unit,
indoor unit, FRESH MASTER or
LOSSNAY are done, or polarity is
changed with the power on and
transmission data collide each other.
Defective transmitting receiving
circuit of transmission processor
Transmission data is changed by
the noise on transmission.
Transmission processor could
not transmit signal because short
cycle voltage of noise and the
like have entered into transmission wire continuously.
Transmission quantity has
increased and transmission of
signal is not possible because
there was wiring mistake of terminal block for transmission wire
(TB3) and terminal block for central control (TB7) in outdoor unit.
Transmission is mixed with
others and occupation rate on
transmission wire rose because
of defective repeater (a function
to connector or disconnect transmission of control and central
control system) of outdoor unit,
then abnormality is detected.
35
Search the unit with same address as abnormality
occurred. If the same address is found, turn the
power supply of outdoor unit and indoor unit and
FRESH MASTER or LOSSNAY at the same time
for 2 minutes or more after the address is corrected, and turn the power on again.
Check transmission waveform or noise on transmission wire.
If the work of transmission wire is done with
the power on, turn off the power supply of
outdoor unit and indoor unit and FRESH
MASTER or LOSSNAY at the same time for
2 minutes or more, and turn the power on
again.
Check transmission waveform or noise on
transmission wire.
Check if transmission wire of indoor unit,
FRESH MASTER, LOSSNAY, or remote controller is not connected to terminal block for
central control (TB7) of outdoor unit.
Check if transmission wire of indoor unit,
FRESH MASTER or LOSSNAY is not connected to terminal block for transmission wire
of outdoor unit.
Check if terminal block for transmission wire
(TB3) and terminal block for central control
(TB7) is not connected.
Check transmission waveform or noise on
transmission wire.
Page 36
Error CodeAbnormal point and detection method CaseJudgment and action
A6
(6606)
Communication error with communication processor
Defective communication between unit
processor and transmission processor
Note) The address and attribute displayed
at remote controller indicate the controller that detected abnormality.
Data of transmission proces-
sor or unit processor is not
transmitted normally because
of accidental trouble such as
noise or thunder surge.
Address forwarding from unit
processor is not transmitted
normally because of defective
transmission processor hardware.
Turn off the power supply of outdoor unit,
indoor unit and FRESH MASTER or LOSSNAY
at the same time for 2 minutes or more, and
turn the power on again. System returns normally if abnormality was accidental malfunction. If the same abnormality generates again,
abnormality-generated controller may be defective.
A7
(6607)
NO ACK signal
1. Transmitting side controller detects
abnormality if a message was transmitted but there is no reply (ACK) that a
message was received. Transmitting
side detects abnormality every 30 seconds, 6 times continuously.
Note) The address and attribute displayed
at remote controller indicate the controller that did not reply (ACK).
2. If displayed address or attribute is out
door unit, indoor unit detects abnormality
when indoor unit transmits signal to outdoor unit and there was no reply (ACK).
3. If displayed address or attribute is indoor
unit, remote controller detects abnormality when remote controller transmits signal to indoor unit and there was no reply
(ACK).
-
Common factor that has no relation with abnormality source
The unit of former address
does not exist as address
switch has changed while the
unit was energized.
Extinction of transmission wire
voltage and signal is caused by
over-range transmission wire.
• Maximum distance·······200m
•
Remote controller line
Extinction of transmission wire
voltage and signal is caused by
type-unmatched transmission
wire.
Type······
With shield wire CVVS, CPEVS
With normal wire (no shield) VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter····1.25mm
Extinction of transmission wire
voltage and signal is caused
by over-numbered units.
indoor unit of multi-refrigerant
system, if remote controller
transmits signal to indoor unit
while outdoor unit power supply of one refrigerant system
is turned off or within 2 minutes of restart, abnormality is
detected.
Contact failure of transmission
wire of remote controller or
indoor unit
Disconnection of transmission
connector (CN2M) of indoor
unit
Defective transmitting receiving
circuit of indoor unit or remote
controller
(12m)
2
or more
Always try the followings when the error
“A7” occurs.
Turn off the power supply of outdoor
unit, indoor unit and FRESH MASTER or
LOSSNAY at the same time for 2 minutes or
more, and turn the power on again. If malfunction was accidental, the unit returns to
normal.
Check address switch of abnormality-gener-
ated address.
Check disconnection or looseness of abnor-
mality-generated or abnormality-detected
transmission wire (terminal block and connector)
Check if tolerance range of transmission wire
is not exceeded.
Check if type of transmission wire is correct
or not.
If there were some trouble of - above,
repair the defect, then turn off the power supply of outdoor unit, indoor unit and FRESH
MASTER or LOSSNAY at the same time for 2
minutes or more, and turn the power on again.
• If there was no trouble with - above in
single refrigerant system (one outdoor unit),
controller of displayed address or attribute is
defective.
• If there was no trouble with - above in dif-
ferent refrigerant system (2 or more outdoor
units), judge with .
If address of abnormality source is the
address that should not exist, there is the
unit that memorizes nonexistent address
information. Delete useless address information with manual setting function of remote
controller.
Only the system FRESH MASTER or
LOSSNAY are connected to, or the system
that is equipped with group setting of different refrigerant system.
If there was no trouble with - above, replace
the controller board of displayed address or
attribute.
If the unit does not return to normal, multi-controller board of outdoor unit may be defective
(repeater circuit).
Replace multi-controller board one by one to
check if the unit returns to normal.
36
Continued to the next page
Page 37
From the previous page
Error CodeAbnormal point and detection method CaseJudgment and action
4. If displayed address or attribute is
remote controller, indoor unit detects
abnormality when indoor unit transmits
signal to remote controller and there
was no reply (ACK).
During group operation with
indoor unit of multi- refrigerant
system, if indoor unit transmit
signal to remote controller
while outdoor unit power supply of one refrigerant system
is put off or within 2 minutes of
restart, abnormality is detected.
Contact failure of transmission
wire of remote controller or
indoor unit
Disconnection of transmission
connector (CN2M) of indoor
unit
Defective transmitting receiving
circuit of indoor unit or remote
controller
Same as mentioned in “A7” of the previous
page
A7
(6607)
5. If displayed address or attribute is
FRESH MASTER, indoor unit detects
abnormality when indoor unit transmits
signal to FRESH MASTER and there
was no reply (ACK).
6. If displayed address or attribute is
LOSSNAY, indoor unit detects abnormality when indoor unit transmits signal to
LOSSNAY and there was no reply (ACK).
During sequential operation
of indoor unit and FRESH
MASTER of other refrigerant
system, if indoor unit transmits
signal to FRESH MASTER
while outdoor unit power supply of same refrigerant system with FRESH MASTER is
turned off or within 2 minutes
of restart, abnormality is
detected.
Contact failure of transmission
wire of indoor unit or FRESH
MASTER
Disconnection of transmission
connector (CN2M) of indoor
unit or FRESH MASTER
Defective transmitting receiving
circuit of indoor unit or FRESH
MASTER
If the power supply of
LOSSNAY is off, indoor unit
detects abnormality when it
transmits signal to LOSSNAY.
During sequential operation
of indoor unit and LOSSNAY
of other refrigerant system, if
indoor unit transmits signal to
LOSSNAY while outdoor unit
power supply of same refrigerant system with LOSSNAY
is turned off or within 2 minutes of restart, abnormality is
detected.
Contact failure of transmis-
sion wire of indoor unit of
LOSSNAY
Disconnection of transmission
connector (CN2M) of indoor
unit
Defective transmitting receiv-
ing circuit of indoor unit or
LOSSNAY
7. If displayed address or attribute is nonexistent.
The unit of former address
does not exist as address
switch has changed while the
unit was energized.
Abnormality is detected
when indoor unit transmits
signal because the address
of FRESH MASTER and
LOSSNAY are changed after
sequential operation of FRESH
MASTER and LOSSNAY by
remote controller.
37
Page 38
Error CodeAbnormal point and detection method CaseJudgment and action
M-NET NO RESPONSE
Abnormal if a message was transmitted
and there were reply (ACK) that message
was received, but response command
does not return. Transmitting side detects
abnormality every 30 seconds, 6 times
continuously.
Note) The address and attribute displayed
at remote controller indicate the controller that did not reply (ACK).
A8
(6608)
Transmitting condition is
repeated fault because of
noise and the like.
Extension of transmission wire
voltage and signal is caused
by over-range transmission
wire.
• Maximum distance ······200m
Remote controller line
•
Extension of transmission wire
voltage and signal is caused
by type-unmatched transmission wire.
Type······
With shield wire CVVS, CPEVS
With normal wire (no shield) VCTF, VCTFK, CVV
(12m)
Check transmission waveform or noise on
transmission wire.
Turn off the power supply of outdoor unit
and indoor unit and FRESH MASTER or
LOSSNAY at the same time for 2 minutes or
more, and turn the power on again. If malfunction was accidental, the unit returns to
normal. If the same abnormality generates
again, controller of displayed address and
attribute may be defective.
CVS, VVR, VVF, VCT
Diameter······1.25mm
Accidental malfunction of
abnormality-generated
controller
2
or more
10-5. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
1. Remote controller display does not
work.
2. “PLEASE WAIT” display is remained
on the remote controller.
DC12V is not supplied to remote controller.
(Power supply display is not indicated on LCD.)
DC12~15V is supplied to remote controller, however,
no display is indicated.
• “PLEASE WAIT” is not displayed.
• “PLEASE WAIT” is displayed.
At longest 2 minutes after the power supply “PLEASE
WAIT” is displayed to start up.
Communication error between the remote controller
and indoor unit
Communication error between the indoor and outdoor
unit
Outdoor unit protection device connector is open.
FactorCountermeasure
Check LED2 on indoor controller board.
(1) When LED2 is lit.
Check the remote controller wiring for
breaking or contact failure.
(2) When LED2 is blinking.
Check short circuit of remote controller
wiring.
(3) When LED2 is not lit.
Refer to phenomena No.3 below.
Check the following.
• Failure of remote controller if “PLEASE
WAIT” is not displayed
• Refer to phenomena No.2 below if
“PLEASE WAIT” is displayed.
Normal operation
Self-diagnosis of remote controller
”PLEASE WAIT” is displayed for 6 min-
utes at most in case of indoor/outdoor
unit communication error. Check LED3 on
indoor controller board.
(1)When LED3 is not blinking.
Check indoor/outdoor connecting wire
for miswiring.
(Converse wiring of S1 and S2, or
break of S3 wiring.)
(2)When LED3 is blinking.
Indoor/outdoor connecting wire is nor mal.
Check LED display on outdoor controller
circuit board. Refer to 10-10.
Check protection device connector (63H)
for contact failure.
Refer to 10-9.
3. When pressing the remote controller
operation switch, the OPERATION
display is appeared but it will be
turned off soon.
After cancelling to select function from the remote
controller, the remote controller operation switch will
not be accepted for approx. 30 seconds.
38
Normal operation
Page 39
Phenomena
4. Even controlled by the wireless
remote controller, no beep is heard
and the unit does not start operating. Operation display is indicated
on wireless remote controller.
Factor
The pair number settings of the wireless remote con-
troller and indoor controller board are mismatched.
Countermeasure
Check the pair number settings.
5. When operating by the wireless
remote controller, beep sound is
heard, however, unit does not start
operating.
6. Remote controller display works
normally and the unit performs cooling operation, however, the capacity
cannot be fully obtained. (The air is
not cool enough.)
7. Remote controller display works
normally and the unit performs heating operation, however, the capacity
cannot be fully obtained.
No operation for 2 minutes at most after the power
supply ON.
Local remote controller operation is prohibited.
• Remote controlling adaptor is connected to CN32
on the indoor controller board.
• Local remote controller operation is prohibited
by centralised controller etc. since it is connected to
MELANS.
Phenomena of No.2.
Refrigerant shortage
Filter clogging
Heat exchanger clogging
Air duct short cycle
Linear expansion valve fault
Opening cannot be adjusted well due to linear expan sion valve fault.
Refrigerant shortage
Lack of insulation for refrigerant piping
Filter clogging
Heat exchanger clogging
Air duct short cycle
Bypass circuit of outdoor unit fault
Normal operation
Check the phenomena of No.2.
• If refrigerant leaks, discharging tempera-
ture rises and LEV opening increases.
Inspect leakage by checking the tem-
perature and opening.
• Check pipe connections for gas leakage.
Open suction grille and check the filter.
Clean the filter by removing dirt or dust on
it.
• If the filter is clogged, indoor pipe tem-
perature rises and discharging pressure
increases. Check if heat exchanger is
clogged by inspecting discharging
pressure.
• Clean the heat exchanger.
Remove the shield.
• Discharging temperature and indoor
heat exchanger temperature does not
rise.
Inspect the failure by checking discharg
ing pressure.
• Replace linear expansion valve.
• If refrigerant leaks, discharging tempera-
ture rises and LEV opening increases.
Inspect leakage by checking the temperature and opening.
• Check pipe connections for gas leakage.
Check the insulation.
Open suction grille and check the filter.
Clean the filter by removing dirt or dust
on it.
• If the filter is clogged, indoor pipe tem-
perature rises and discharging pressure
increases. Check if heat exchanger is
clogged by inspecting discharging pressure.
• Clean the heat exchanger.
Remove the shield.
Check refrigerant system during opera-
tion.
8. For 3 minutes after temperature
adjuster turns off, the compressor
will not start operating even if
temperature adjuster is turned on.
For 3 minutes after temperature
adjuster turns on, the compressor
will not stop operating even if
temperature adjuster is turned off.
(Compressor stops operating
immediately when turning off by
the remote controller.)
Normal operation
(For protection of compressor)
39
Normal operation
Page 40
Symptoms: “PLEASE WAIT” is kept being displayed on the remote controller.
Diagnosis flowCause
Check the display time of “PLEASE WAIT”
after turning on the main power.
6 minutes
or more
Check the LED display of the
outdoor controller circuit board.
2 minutes
How long is “PLEASE WAIT”
kept being displayed on the
remote controller?
2 to 6
minutes
Are any error codes
displayed on the
remote controller?
YES
or less
NO
“PLEASE WAIT”
•
will be displayed
during the start-up
diagnosis after turning
on the main power.
Inspection method and
troubleshooting
• Normal.
The start-up diagnosis will
be over in around 2 minutes.
Are any error codes
displayed on the LED?
NO
YES
• Miswiring of indoor/
outdoor connecting
wire
• Breaking of indoor/
outdoor connecting
wire (S3)
• Defective indoor
controller board
• Defective outdoor
controller circuit
board
• Defective indoor
controller board
• Defective remote
controller
• Refer to “Self-diagnosis
action table” in order to
solve the trouble.
• In case of communication
errors, the display of
remote controller may not
match the LED display of
the outdoor unit.
40
Page 41
Symptoms: Nothing is displayed on the remote controller
LED display of the indoor
controller board
LED1 :
LED2 :
LED3 :
Diagnosis flowCause
Check the voltage between S1
and S2 on the terminal block
(TB4) of the indoor unit which
is used to connect the indoor
unit and the outdoor unit.
AC 198V to AC 264V?
YES
NO
Check the voltage among L(L3) and
N on the terminal block (TB1) of the
outdoor power circuit board.
AC 198V to AC 264V?
NO
YES
Check the voltage between S1
and S2 on the terminal block
(TB1) of the outdoor unit which
is used to connect the indoor
unit and the outdoor unit.
•
Troubles concerning
power supply
Inspection method and
troubleshooting
• Check the power wiring
to the outdoor unit.
• Check the breaker.
Check the voltage of indoor
controller board (CN2D).
DC 12V to DC 16V?
YES
NO
Check the voltage of the unit after
removing the indoor power board
(CN2S).
DC 12V to DC 16V?
YES
NO
AC 198V to AC 264V?
YES
NO
• Bad wiring of the
outdoor controller
board
• The fuses on the
outdoor controller
circuit board are
blown.
• Bad wiring of the
outdoor controller
board
• The fuses on the
outdoor controller
circuit board are
blown.
• Defective indoor
controller board
• Miswiring, breaking
or poor connection of
in door/outdoor
connecting wire
• Check the wiring of the
outdoor unit.
• Check if the wiring is bad.
Check if the fuses are blown.
The fuses on the outdoor
controller circuit board will
be blown when the indoor
/outdoor connecting wire
short-circuits.
• Check if miswiring, breaking
or poor contact is causing this
problem. Indoor/outdoor
connecting wire is polarized
3-core type. Connect the
indoor unit and the outdoor
unit by wiring each pair of
S1, S2 and S3 on the both
side of indoor/outdoor
terminal blocks.
• Replace the indoor
controller board.
•
Check if there is miswiring
or breaking of wire.
41
• Defective indoor
power board
• Replace the indoor
power board.
Page 42
Symptoms: Nothing is displayed on the remote controller
LED display of the indoor
controller board
LED1 :
LED2 :
LED3 : or
Diagnosis flowCause
Check the voltage between S1 and
of the
indoor unit which is used to connect the indoor unit and the
outdoor unit.
AC 198V to AC 264V?
YES
Check the status
of the indoor controller
board LED3 display.
Blinking.
Check the refrigerant address of
the outdoor unit. (SW1-3 to 1-6)
Is the refrigerant
address “0”?
YES
Check the LED display of the
outdoor unit after turning on the
main power again.
S2 on the terminal block (TB4)
NO
Not lighting.
Check the looseness or disconnection
of the indoor/outdoor connecting wire.
Are there looseness or
disconnection of the indoor/
outdoor connecting wire?
NO
NO
YES
•
Breaking or poor contact
of the indoor/outdoor
connecting wire
• Normal
Only the unit which
has the refrigerant
address “0” supplies
power to the remote
controller.
Inspection method and
troubleshooting
• Fix the breaking or poor
contact of the indoor/outdoor
connecting wire.
• Set the refrigerant
address to “0”. In case of
the multiple grouping
system, recheck the
refrigerant address again.
Is anything displayed?
Displayed.
Is “EA” or “Eb”
displayed?
YES
Check the voltage between S2
and S3 on the terminal block of
the outdoor unit.
DC 17V to DC 28V?
YES
NO
Not displayed.
NO
Is “E8” displayed?
Can the unit be restarted?
Can all the indoor
unit be operated?
NO
YES
• Defective outdoor
controller circuit
board
YES
• Defective outdoor
controller circuit
board
NO
• Defective indoor
controller board
• Influence of
electromagnetic noise
• Defective outdoor
power circuit board
• Defective indoor
power board
• Replace the outdoor
controller circuit board.
• Replace the outdoor
controller circuit board.
Replace the indoor controller
•
board of the indoor unit which
doesn’t operate.
• Not abnormal.
There may be the influence
of electromagnetic noise.
Check the transmission wire
and get rid of the causes.
• Replace the outdoor
power circuit board.
• Replace the indoor
power board.
42
Page 43
Symptoms: Nothing is displayed on the remote controller
LED display of the indoor
controller board
LED1 :
LED2 : or
LED3 : —
Diagnosis flowCause
Check the voltage of the
terminal block (TB6) of
the remote controller.
DC 10V to DC 16V?
NO
Check the status
of the LED2.
Blinking
Check the status of the LED2
after disconnecting the remote
controller wire from the terminal
block (TB5) of the indoor unit.
YES
Lighting
• Defective
remote controller
• Breaking or poor
contact of the remote
controller wire
Inspection method and
troubleshooting
• Replace the
remote controller.
• Check if there is breaking
or poor contact of the
remote controller wire.
Check the voltage of the
terminal block (TB5)
connecting the remote
controller wire.
If it is not between DC 10V
and DC16V, the indoor
controller board must be
defective.
Check the status
of the LED2.
Blinking
Lighting
43
• The remote controller
wire short-circuits
• Defective indoor
controller board
• Check if the remote
controller wire is
short-circuited.
• Replace the indoor
controller board.
Page 44
• Before repair
Frequent calling from customers
Phone Calls From CustomersHow to Respond Note
Unit does
not operate
at all.
The operating display of
remote controller does not
come on.
Unit cannot be restarted for a
while after it’s stopped.
Error code appears and blinks
on the display of remote
controller.
Check if power is supplied to air conditioner.
Nothing appears on the display unless power is
supplied.
Wait around 3 minutes to restart unit.
The air conditioner is in a state of being protected
by the microcomputer’s directive. Once the
compressor is stopped, the unit cannot be
restarted for 3 minutes. This control is also applied
when the unit is turned on and off by remote
controller.
Error code will be displayed if any protection
devices of the air conditioner are actuated.
What is error code?
Refer to “SELF-DIAGNOSIS
ACTION TABLE”.
Check if servicing is
required for the error.
Remote
controller
“PLEASE WAIT” is displayed
on the screen.
“FILTER” is displayed on the
screen.
“STANDBY” is displayed on
the screen.
“DEFROST” is displayed on
the screen. (No air comes out
of the unit.)
Wait around 2 minutes.
An automatic startup test will be conducted for
2 minutes when power is supplied to the air
conditioner. “PLEASE WAIT” will be kept being
displayed while that time.
This indicates that it is time to clean the air filters.
Clean the air filters. Press the FILTER button on
the remote controller twice to clear “FILTER” from
the display.
See the operation manual that came with the
product for how to clean the filters.
This is displayed when the unit starts HEAT
operation, when the thermostat puts the
compressor in operation mode, or when the
outdoor unit ends DEFROST operation and
returns to HEAT operation.
The display will automatically disappear around
10 minutes later.
While “STANDBY” is displayed on the remote
controller, the airflow amount will be restricted
because the indoor unit’s heat exchanger is not
fully heated up. In addition to that, the up/down
vane will be automatically set to horizontal blow
in order to prevent cold air from directly blowing
out to human body. The up/down vane will return
to the setting specified by the remote controller
when “STANDBY” is released.
The outdoor unit gets frosted when the outside
temperature is low and the humidity is high.
“DEFROST” indicates the DEFROST
operation is being performed to melt this frost. The
DEFROST operation ends in around 10 minutes
(at most 15 minutes).
During the DEFROST operation, the indoor unit’s
heat exchanger becomes cold, so the fan is
stopped. The up/down vane will be automatically
set to horizontal blow in order to prevent cold air
from directly blowing out to human body. The
display will turn into “STANDBY” when DEFROST
operation ends.
Display time of “FILTER”
depends on the model.
Long life filter: 2500 hrs.
Regular filter: 100 hrs.
44
Page 45
Phone Calls From CustomersHow to RespondNote
The room cannot be cooled or heated sufficiently.
Sound
comes out
from the air
conditioner.
Something
is wrong
with the
blower…..
An gas escaping sound is heard
sometimes.
A cracking sound is heard
sometimes.
A buzzing sound is heard
sometimes.
A ticking sound is heard from
the outdoor unit sometimes.
A sound, similar to water
flowing, is heard from the unit.
The fan speed doesn’t match
the setting of the remote
controller during DRY
operation.(No air comes out
sometimes during DRY
operation.)
The fan speed doesn’t match
the setting of the remote
controller in HEAT operation.
Check the set temperature of remote controller.
The outdoor unit cannot be operated if the set
temperature is not appropriate.
The outdoor unit operates in the following modes.
COOL: When the set temperature is lower
than the room temperature.
HEAT: When the set temperature is higher
than the room temperature.
Check if filters are dirty and clogged. If filters
are clogged, the airflow amount will be reduced
and the unit capacity will be lowered. See the
instruction manual that came with the product for
how to clean the filters.
Check there is enough space around the air
conditioner.
If there are any obstacles in the air intake or air
outlet of indoor/outdoor units, they block the
airflow direction so that the unit capacity will be
lowered.
This is not a malfunction.
This is the sound which is heard when the flow of
refrigerant in the air conditioner is switched.
This is not a malfunction.
This is the sound which is heard when internal
parts of units expand or contract when the
temperature changes.
This is not a malfunction.
This is the sound which is heard when the outdoor
unit starts operating.
This is not a malfunction.
This is the sound which is heard when the fan of
the outdoor unit is controlling the airflow amount
in order to keep the optimum operating condition.
This is not a malfunction.
This is the sound which is heard when the
refrigerant is flowing inside the indoor unit.
This is not a malfunction.
During the DRY operation, the blower’s ON/OFF is
controlled by the microcomputer to prevent
overcooling and to ensure efficient
The fan speed cannot be set by the remote
controller during DRY operation.
This is not a malfunction.
1) When the HEAT operation starts, to prevent the
unit from blowing cold air, the fan speed is
gradually increased from zero to the set speed,
in proportion to the temperature rise of the
discharged air.
2) When the room temperature reaches the set
temperature and the outdoor unit stops,
the unit starts the LOW AIR operation.
3) During the HEAT operation, the DEFROST
operation is performed to defrost the outdoor
unit. During the DEFROST operation, the
blower is stopped to prevent cold air coming
out of the indoor unit.
dehumidification.
The up/down vane will be
automatically set to
horizontal blow in these
cases listed up on the left
( 1)~3)). After a while, the
up/down vane will be
automatically moved
according to the setting of
the remote controller.
45
Page 46
Phone Calls From CustomersHow to RespondNote
Something
is wrong
with the
blower….
Something
is wrong
with the
airflow
direction
....
Air blows out for a while after
HEAT operation is stopped.
The airflow direction is
changed during COOL
operation.
The airflow direction is
changed during HEAT
operation.(The airflow
direction cannot be set by
remote controller.)
The airflow direction doesn’t
change.(Up/down vane,
left/right louver)
This is not a malfunction.
The blower is operating just for cooling down the
heated-up air conditioner. This will be done within
1 minute.
This control is conducted only when the HEAT
operation is stopped with the electric heater ON.
If the up/down vane is set to downward in COOL
operation, it will be automatically set to horizontal
blow by the microcomputer in order to prevent
water from dropping down.
“1 Hr.” will be displayed on the remote controller if
the up/down vane is set to downward with the fan
speed set to be less than “LOW”.
In HEAT operation, the up/down vane is
automatically controlled according to the
temperature of the indoor unit’s heat exchanger.
In the following cases written below, the up/down
vane will be set to horizontal blow, and the setting
cannot be changed by remote controller.
1) At the beginning of the HEAT operation
2) While the outdoor unit is being stopped by
thermostat or when the outdoor unit gets started
to operate.
3) During DEFROST operation
The airflow direction will be back to the setting of
remote controller when the above situations are
released.
1) Check if the vane is set to a fixed position.
(Check if the vane motor connector is removed.)
2) Check if the air conditioner has a function for
switching the air direction.
3) If the air conditioner doesn’t have that
function, “NOT AVAILABLE” will be displayed
on the remote controller when “AIR
DIRECTION” or “LOUVER” button is pressed.
However, this control is
also applied to the models
which has no electric
heater.
“STANDBY” will be
displayed on the remote
controller in case of 1) and
2) “DEFROST” will be
displayed on the screen in
case of 3).
The air conditioner starts operating even
though any buttons on the remote controller
are not pressed.
The air conditioner stops even though any
buttons on the remote controller are not
pressed.
Check if you set ON/OFF timer.
The air conditioner starts operating at the time
designated if ON timer has been set before.
Check if any operations are ordered by distant
control system or the central remote controller.
While “CENTRALLY CONTROLLED INDICATOR”
is displayed on the remote controller, the air
conditioner is under the control of external
directive.
Check if power is recovered from power failure
(black out).
The units will automatically start operating when
power is recovered after power failure (black out)
occurs. This function is called “power failure
automatic recovery".
Check if you set ON/OFF timer.
The air conditioner stops operating at the time
designated if OFF timer has been set before.
Check if any operations are ordered by distant
control system or the central remote controller.
While “CENTRALLY CONTROLLED INDICATOR”
is displayed on the remote controller, the air
conditioner is under the control of external
directive.
There might be a case that
“CENTRALLY
CONTROLLED
INDICATOR” will not be
displayed.
There might be a case that
“CENTRALLY
CONTROLLED
INDICATOR” will not be
displayed.
46
Page 47
Phone Calls From CustomersHow to Respond Note
A white mist is expelled from the indoor unit.
Water or moisture is expelled from the outdoor
unit.
The display of wireless remote controller gets dim
or doesn’t come on.
The indoor unit doesn’t receive a signal from
remote controller at a long distance.
This is not a malfunction.
This may occur when the operation gets started in
the room of high humidity.
Cooling; when pipes or piping joints are cooled, they
get sweated and water drips down.
Heating; water drips down from the heat exchanger.
* Make use of optional parts “Drain Socket” and
“Drain pan” if these water needs to be collected and
drained out for once.
Batteries are being exhausted. Replace them and
press the reset button of remote controller.
47
Page 48
10-6. HOW TO CHECK THE PARTS
PUHZ-RP200YHA2PUHZ-RP250YHA2
Parts name
Thermistor (TH3)
<Outdoor pipe>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Outdoor>
Fan motor(MF1,MF2)
4-way valve coil
(21S4)
Compressor
(MC)
U
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10~30)
TH4
Normal
160k~410k
Abnormal
TH3
TH6
4.3k~9.6k
Open or short
TH7
Refer to next page.
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
Normal
1435±150
)
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(Winding temperature 20
)
NormalAbnormal
V
W
Linear expansion valve
(LEV-A) RP200
M
Gray
Orange
Red
Yellow
Black
1
2
3
4
5
6
Linear expansion valve
( LEV-A, LEV-B)
RP250
M
Red
Brown
Blue
Orange
Yellow
White
1
2
3
4
5
6
Bypass valve coil
(SV)
0.30
Open or short
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20)
Normal
Gray - BlackGray - Red
Gray - Yellow
Gray - Orange
46±3
Disconnect the connector then measure the resistance
(
Winding temperature 20
)
Normal
Red - White
Red - Orange
Brown - Yellow
Brown - Blue
with
a tester.
Abnormal
Open or short
46±4
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
)
NormalAbnormal
Abnormal
Open or short
1197±10
Open or short
48
Page 49
Check method of DC fan motor (fan motor / outdoor controller circuit board)
Notes
· High voltage is applied to the connecter (CNF1, 2) for the fan motor. Give attention to the service.
· Do not pull out the connector (CNF1, 2) for the motor with the power supply on.
(It causes trouble of the outdoor controller circuit board and fan motor.)
Self check
Symptom : The outdoor fan cannot turn around.
Fuse check
Check the fuse (F5) on outdoor
controller board.
Did the fuse blow?
No
Wiring contact check
Contact of fan motor connector (CNF1, 2)
Is there no contact failure?
Yes
Power supply check (Remove the connector (CNF1, 2))
Measure the voltage in the outdoor controller circuit
TEST POINT
: VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC250~330V
Yes
No
Replace outdoor controller board (C.B)
and fan motor (MF1, 2).
Recover wiring.
board.
TEST POINT : VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC15V
(1) Operation summary of the linear expansion valve
• Linear expansion valve opens/closes through stepping motor after receiving the pulse signal from the outdoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
Outdoor controller board
DC12V
1
:4
:3
:2
:1
Gray
Orange
Red
Yellow
Black
Drive circuit
3
4
5
6
:4
:3
:2
:1
LEV
3
2
M
5
1
6
4
Connector LEV-A
<Output pulse signal and the valve operation>
OFF
ON
OFF
OFF
Output
5678
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
Output
(Phase)
:1
:2
:3
:4
234
1
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
(2) Linear expansion valve operation
Valve position (capacity)
Close
Open
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
Opening a valve : 8 ¡7 ¡6 ¡5 ¡4 ¡3 ¡2 ¡1 ¡8
Closing a valve : 1 ¡2 ¡3 ¡4 ¡5 ¡6 ¡7 ¡8 ¡1
The output pulse shifts in above order.
• When linear expansion valve operation stops, all output phase
become OFF.
• When the switch is turned on, 700 pulse closing valve signal will be
sent till it goes to
point in order to define the valve position. (The
pulse signal is being sent for about 20 seconds.)
• When the valve moves smoothly, there is no sound or vibration
occurring from the linear expansion valve ; however, when the pulse
number moves from
to or when the valve is locked, sound can
be heard.
No sound is heard when the pulse number moves from
to in
case coil is burnt out or motor is locked by open-phase.
• Sound can be detected by placing the ear against the screw driver
handle while putting the screw driver to the linear expansion valve.
htning (about 32 pulse
Extra ti
Pulse number
500 pulse
Opening a valve
all the way
51
Page 52
g
)
Linear expansion valve
(RP250)
(1) Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the outdoor controller circuit board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller circuit board and the linear expansion valve>
Outdoor controller board
DC12V
1
LEV
3
2
M
5
1
6
4
:4
:3
:2
:1
Red
Brown
Blue
Orange
Yellow
White
2
3
4
5
6
Drive circuit
:4
:3
:2
:1
<Output pulse signal and the valve operation>
OFF
ON
OFF
OFF
Output
5678
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
Open
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
Output
(Phase)
:1
:2
:3
:4
234
1
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
(2) Linear expansion valve operation
Valve position (capacity)
Close
Connector LEV-A
LEV-B
Opening a valve : 8 ¡7 ¡6 ¡5 ¡4 ¡3 ¡2 ¡1 ¡8
Closing a valve : 1 ¡2 ¡3 ¡4 ¡5 ¡6 ¡7 ¡8 ¡1
The output pulse shifts in above order.
• When linear expansion valve operation stops, all output phase
become OFF.
• When the switch is turned on, 700 pulse closing valve signal will be
sent till it goes to
point in order to define the valve position. (The
pulse signal is being sent for about 20 seconds.)
• When the valve moves smoothly, there is no sound or vibration
occurring from the linear expansion valve ; however, when the pulse
number moves from
to or when the valve is locked, sound can
be heard.
No sound is heard when the pulse number moves from
to in
case coil is burnt out or motor is locked by open-phase.
• Sound can be detected by placing the ear against the screw driver
handle while putting the screw driver to the linear expansion valve.
Extra ti
htning (about 32 pulse
500 pulse
Opening a valve
all the way
Pulse number
52
Page 53
53
y
(3) How to attach and detach the coil of linear expansion valve(RP200)
A
<Composition>
Linear expansion valve is separable into the main body and the coil as shown in the diagram below.
Stopper
Coil
Lead wire
<How to detach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and detach the coil by pulling it
upward.
Be sure to detach the coil holding main body firmly. Otherwise
pipes can bend due to pressure.
Main bod
<How to attach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and attach the coil by inserting it
downward into the main body. Then securely attach the coil stopper to main body. (At this time, be careful that stress is not added
to lead wire and main body is not wounded by lead wire.) If the
stopper is not firmly attached to main body, coil may be detached
from the main body and that can cause defective operation of linear expansion valve.
To prevent piping stress, be sure to attach the coil holding the
main body of linear expansion valve firmly. Otherwise pipe may
break.
Be sure to attach
the stopper.
A
Page 54
(4) How to attach and detach the coil of linear expansion valve(RP250)
A
Be sure to attach the
stopper to pipe B.
B
A
<Composition>
Linear expansion valve is separable into the main body and the coil as shown in the diagram below.
Coil
Lead wire
<How to detach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and detach the coil by pulling it
upward.
Be sure to detach the coil holding main body firmly. Otherwise
pipes can bend due to pressure.
Stopper
Main body
<How to attach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and attach the coil by inserting it
downward into the main body. Then securely attach the coil stopper to pipe B. (At this time, be careful that stress is not added to
lead wire and main body is not wound by lead wire.) If the stopper is not firmly attached to pipe B, coil may be detached from
the main body and that can cause defective operation of linear
expansion valve.
To prevent piping stress, be sure to attach the coil holding the
main body of linear expansion valve firmly. Otherwise pipe may
break.
54
Page 55
10-8. EMERGENCY OPERATION
s
SW4
12Cooling
Heating
ON
(1) When the error codes shown below are displayed on outdoor unit or microcomputer for wired remote controller or indoor
unit has a failure, but no other problems are found, emergency operation will be available by setting the emergency opera tion switch (SWE) to ON and short-circuiting the connector (CN31) on outdoor controller board.
When following abnormalities occur, emergency operation will be available.
Error code
U4
E8
E9
E0 ~ E7
Ed
(2) Check the following items and cautions for emergency operation
Make sure that there is no abnormality in outdoor unit other than the above abnormalities. (Emergency operation will
not be available when error code other than the above are indicated.)
For emergency operation, it is necessary to set the emergency operation switch (SWE) on indoor controller board. Refer
to the electrical wiring diagram of indoor unit for how to set the indoor unit.
During emergency operation, the air-conditioner will continuously be operated by supplying power and stopping it; it can
not be turned on or off by remote control, and temperature control is not possible.
Do not perform emergency heating operation for an extended period of time; if the outdoor unit starts defrosting during
this period, cold air will blow out from the indoor unit.
Do not perform emergency cooling operation for more than 10 hours; neglecting this could result in freezing the heat
exchanger in indoor unit.
(3) Emergency operation procedure
Turn the main power supply off.Turn on the emergency operation switch (SWE) on indoor controller board.Set the shorting pins of emergency operation connector (CN31) on outdoor controller board to ON.Use SW4-2 on outdoor controller board to set the operation mode (cooling or heating). (SW4-1 is not used.)
Inspected content
Open/short of pipe thermistor (TH3/TH6)
Indoor/outdoor unit communication error •Signal receiving error (Outdoor unit)
Indoor/outdoor unit communication error •Transmitting error (Indoor unit)
Communication error other than outdoor unit
Communicaiton error between outdoor controller board and M-NET board (Serial communication error)
ON
CN31
Shorting pin
SW4
ON
Heating
12Cooling
OFF
Turning the main power supply on will start the emergency operation.
(4) Releasing emergency operation
Turn the main power supply off.Set the emergency operation switch (SWE) on indoor controller board to OFF.Set the shorting pins of emergency operation connector (CN31) on outdoor controller
board to OFF.
Set SW4-2 on outdoor controller board as shown in the right.
+If shorting pins are not set on emergency operation connector (CN31), the setting remains OFF.
55
Page 56
(5) Operation data during emergency operation
During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation
are set to the following values:
Operation mode
Operation data
COOL
Room temperature (TH1)
Indoor pipe temperature (TH2)
Indoor 2-phase pipe temperature (TH5)
Set temperature
Outdoor pipe temperature (TH3)
Outdoor discharge pipe temperature (TH4)
Outdoor 2-phase pipe temperature (TH6)
Outdoor air temperature (TH7)
Temperature difference code
(room temperature - set temperature) (Tj)
Discharge superheat (SHd)
Sub-cool (SC)
+1: If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data.
When the unit enters emergency operation and TH values are mismatched, set the thermistors to open/short. And the
unit runs emergency operation with the values listed above.
+2: If one thermistor is set to open/short, the values of SHd/SC will be different from the list above.
[Example] When liquid temperature thermistor (TH3) has an open or short circuit.
10-9. TEST POINT DIAGRAM
Outdoor controller circuit board
PUHZ-RP200YHA2PUHZ-RP250YHA2
SW7
Demand control setting
SW1
Forced defrost, detect history record reset,
refrigerant address
<CAUTION> TEST POINT is high voltage.
SW6
Model select
SW4
Test operation
SWP
Pump down
SW5
Function switch
SW8
Wiring replace
Pipe replace
CNM
Connect to A control
service tool
CNMNT
Connect to
M-NET adapter(CN5)
CNVMNT
Connect to
M-NET adapter(CND)
LEV-A, B
Linear expansion
valve
TH4
Thermistor
<Discharge>
CN51
External signal output
• Compressor operating
signal
• Abnormal signal
CNDM
to :
Input of low-level
sound priority mode
to :
Input of external con-
tact point
CN4
Transmission to outdoor power circuit
board (CN4)
SV2
Bypass valve
21S4
4-way valve
63L
Low pressure switch
(RP250)
TH3
Thermistor
<Outdoor pipe>
TH7/6
Thermistor
<Outdoor/
2-phase pipe>
63H
High pressure
switch
VFG
(TEST POINT )
(Voltage between
right pins of PC5C
and PC5D, pin 3
and pin 4)
(Same as
(+)-(-))
(CNF1
VSP
(TEST POINT )
(Voltage between pins
of C5A, C5B): DC 0V
(when stopped), DC 1–
6.5V
(when operated)
CNF1, CNF2
Connect to the fan motor
-: 280V DC
-: 15V DC
-: 0-6.5V DC
-: 15V DC(When stopped)
7.5V DC(When operated)
(0V-15V pulse)
CNDC
Connect to the outdoor noise filter circuit
board(CNDC)
CN2
Connect to the outdoor
power circuit board (CN2)
-: Reception from
power circuit board
-: Zero cross signal
(0-5V DC)
,: Not used
-: 16V DC
-: 16V DC
CNAC
to : Power supply for
outdoor controller circuit
board (220V-240V AC)
to : Power supply for
indoor and outdoor unit
connection wire
(220-240V AC)
LI1-LI2/LI-LI3/LI3-LI1 : AC380/400/415V input
LI1-NI/LI2-NI/LI3-NI : AC220/230/240V input
(Connect to the terminal block (TB1))
CNAC1, CNAC2
AC220/230/240V
(Connect to the
outdoor controller
circuit board (CNAC))
GD2
Connect to the earth
CNDC
(Connect to the
outdoor controller
circuit board
(CNDC))
CNCT
Primary current
(Connect to the
outdoor power
circuit board (CN5))
CNL
Connect to the ACL4
LO1, LO2, LO3
POWER SUPPLY
LO1-LO2/LO2-LO3/LO3-LO1 : AC380/400/415V OUTPUT
(Connect to the outdoor power circuit board (TB-L1, L2, L3))
58
Page 59
Outdoor power circuit board
PUHZ-RP200YHA2
PUHZ-RP250YHA2
CN2
Connect to the outdoor controller circuit
board (CN2)
-3RZHUFLUFXLWERDUGĺ7UDQVPLWWLQJ
signal to the controller board (0-5V DC)
-: Zero cross signal (0-5V DC)
-: Not used
-: 16V DC
-: 16V DC
[ : – , , , @
Brief check of POWER MODULE
Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.).
If they are short-circuited, it means that they are broken.
1. Check of POWER MODULE
.Check of DIODE circuit
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
Note:The marks, L1 , L2 , L3 , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram are not actually printed on the board.
SC-U, SC-V, SC-W
Connect to the compressor (MC)
Voltage among phases: 10V-400V AC
CN4
Connect to the
outdoor controller circuit
board
(CN4)
CN5
Detection of
primary current
(Connect to
the outdoor
noise filter
circuit board
(CNCT))
TB-P1
Connect to DCL
TAB connecter on
X52A
Connect to the
RS resistor
TB-C1
Connect to the
smoothing capacitor
– , CB2 +
CB1
TB-P2
Connect to the smoothing
capacitor CB1
+
TB-L1, TB-L2,
TB-L3
Connect to the
outdoor noise filter circuit board
(L01, L02, L03)
380V-415V AC
POWER
MODULE
TB-N1
Connect to the
smoothing capacitor
CB2
–
59
Page 60
10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS
(1) Function of switches
Type
of
switch
Dip
switch
Switch
SW1
SW4
No.
1
2
3
4
FunctionEffective timing
Forced defrost
+
1StartNormal
Abnormal history clear
123
123
Refrigerant address setting
5
6
1
2
Test runOperatingOFF
Test run mode settingHeatingCooling
123
123
+1.Forced defrost should be done as follows.
Change the DIP SW1-1 on the outdoor controller board from OFF to ON.
Forced defrost will start by the above operation if these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor started operating or previous forced defrost finished.
• Pipe temperature is less than or equal to 8.
• Forced defrost will finish if certain conditions are satisfied.
Forced defrost can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again. This
depends on the service conditions.
Action by the switch operation
ONOFF
When compressor is working
in heating operation. +
ClearNormaloff or operating
ON
456ON123456ON123456ON123456
012 3
456ON123456ON123456ON123456
456 7
456ON123456ON123456ON123456
891011
456ON123456ON123456ON123456
12131415
ON
ON
ON
When power supply ON
Under suspension
Type of
Switch
Dip
switch
Push
switch
Switch
SW5
SW7
+4
SW8
SW9
SWP
No.
1
2
3,4,5
6
1
FunctionEffective timing
No function
Power failure
automatic recovery +2
No function
Model select
Setting of demand
control
+3
2
Max Hz setting (cooling)
3
Max Hz setting (heating)
4
5
6
1
2
3
1
2
3,4
No function
Defrost Hz setting
Use of existing pipe
No function
Use of existing wires
No function
Function switch
No function
Pump down
Action by the switch operation
ONOFF
—
Auto recovery
—
SW7-1 SW7-2
OFF
ON
OFF
Max Hz(cooling)
Max Hz(heating)
—
For high humidity
Existing pipe
—
Existing wires
—
Valid
—
Start
OFF
0% (Operation stop)
OFF
ON
%
0.8
%
0.8
—
No auto recovery
—
Refer to next page.
Power consumption
(Demand switch ON)
50%
75%
Normal
Normal
—
Normal
New pipe
—
New wires
—
Normal
—
Normal
—
When power supply ON
—
Always
Always
Always
—
Always
Always
—
When power supply ON
—
Always
—
Under suspension
+2 “Power failure automatic recovery” can be set by either remote controller or this DIP SW. If one of them is set to ON,
“Auto recovery” activates. Please set “Auto recovery” basically by remote controller because all units do not have DIP SW.
Please refer to the indoor unit installation manual.
+3SW7-1,2 are used for demand control. SW7-1,2 are effective only at the demand control.
(Refer to next page : Special function (b))
+4Please do not use SW7-3~5 usually. Trouble might be caused by the usage condition.
Unit enters into Low-level sound priority mode by external signal input setting.
Inputting external signals to the outdoor unit decreases the outdoor unit operation sound 3 to 4 dB lower than that of usual.
Adding a commercial timer or on-off switch contactor setting to the CNDM connector which is optional contactor for demand
input located on the outdoor controller board enables to control compressor operation frequency.
The performance depends on the load of conditioned outdoor temperature.
How to wire
<Low-level sound priority mode circuit>
Insulate this point securely as
this is not used.
Procured locally
Relay
supply
~
SW1
X
X
SW1 : Switch
X : Relay (Contact spec. : DC1mA)
Max. 10 m including local wiring
Adapter for external
signal input
(PAC-SC36NA)
Red 3
Brown 2
Orange 1
Outdoor unit
controller board
CNDM
1) Make the circuit as shown above with adapter for external signal input(PAC-SC36NA).
2) Turn SW1 to on for Low-level sound priority mode.
Turn SW1 to off to release Low-level sound priority mode and normal operation.
(b) Demand control (Local wiring)
Demand control is available by external input. In this mode, power consumption is decreased within the range of usual
0~100%.
How to wire
Basically, the wiring is same with (a).
Connect an SW 1 which is procured locally between Orange and Red(1 and 3) of the adapter for external signal
input(PAC-SC36NA), and insulate the tip of the brown lead wire.
It is possible to set it to the following power consumption (compared with ratings) by setting the SW7-1, 2.
SW7-1SW7-2
OFF
ON
OFF
OFF
OFF
ON
Power consumption
(SW1 on)
0% (Operation stop)
50%
75%
61
Page 62
<Display function of inspection for outdoor unit>
The blinking patterns of both LED1(green) and LED2(red) indicate the types of abnormality when it occurs. Types of
abnormality can be indicated in details by connecting an optional part “A-Control Service Tool (PAC-SK52ST)” to connector
CNM on outdoor controller board.
[Display]
(1)Normal condition
Unit condition
When the power is turned on
When unit stops
When compressor is warming up
When unit operates
(2)Abnormal condition
IndicationError
Outdoor controller board
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
4 blinking
2 blinking 1 blinking
2 blinking
3 blinking
4 blinking
5 blinking
1.Error code displayed on remote controller
2.Refer to service manual for indoor unit.
Connector(63L) is open.
Connector(63H) is open.
2 connectors are open.
Abnormality of indoor controller
board
Miswiring of indoor/outdoor unit connecting wire, excessive number of indoor
units (5 units or more)
Miswiring of indoor/outdoor unit connecting wire (converse wiring or disconnection)
Startup time over
Indoor/outdoor unit communication error
(signal receiving error) is detected by indoor unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by indoor
unit.
Indoor/outdoor unit communication error
(signal receiving error) is detected by
outdoor unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by outdoor
unit.
Remote controller signal receiving
error is detected by remote controller.
Remote controller transmitting error
is detected by remote controller.
Remote controller signal receiving
error is detected by indoor unit.
Remote controller transmitting error
is detected by indoor unit.
Error code is not defined.
Serial communication error
<Communication between outdoor
controller board and outdoor power
board>
<Communication between outdoor
controller board and M-NET P.C. board>
Communication error of M-NET
system
Outdoor controller boardA-Control Service Tool
LED1 (Green)LED2 (Red)Error code
LightedLighted
Lighted
Lighted
Lighted
ContentsInspection method
Not lighted
Not lighted
Lighted
Error
code
+1
Check if connector (63L or 63H) on the outdoor controller
F3
board is not disconnected.
F5
Check continuity of pressure switch (63L or 63H) by tester.
F9
Replace indoor controller board
Fb
Check if indoor/outdoor connecting wire is connected correctly.
—
Check if 5 or more indoor units are connected to outdoor unit.
Check if noise entered into indoor/outdoor connecting wire
—
or power supply.
Re-check error by turning off power, and on again.
00, etc.
08, etc.
C5, H7 etc.
—
Check if indoor/outdoor connecting wire is connected correctly.
E6
Check if noise entered into indoor/outdoor connecting wire or
power supply.
E7
Check if noise entered into indoor/outdoor controller board.
Re-check error by turning off power, and on again.
—
—
Check if connecting wire of indoor unit or remote controller
E0
is connected correctly.
Check if noise entered into transmission wire of remote
E3
controller.
Re-check error by turning off power, and on again.
E4
E5
Check if remote controller is MA remote controller(PAR-21MAA).
Check if noise entered into transmission wire of remote controller.
EF
Check if noise entered into indoor/outdoor connecting wire.
Re-check error by turning off power, and on again.
Check if connector (CN4) on outdoor controller board and
outdoor power board is not disconnected.
Ed
Check if there is poor connection of connector on outdoor
controller board(CNMNT and CNVMNT).
A0~A8
Check M-NET communication signal.
Indication of the display
Alternately blinking display
Operation mode
Detailed
reference
P.28
P.29
(EA)
P.29
(Eb)
P.29
(EC)
P.34
(E8)
P.34
(E9)
P.33
P.34
P.33
P.34
P.34
P.34
P.35~
P.38
page
+2
+2
+2
62
Page 63
63
IndicationError
Outdoor controller board
LED1 (Green)
3 blinking 1 blinking
LED2 (Red)
Abnormality of discharging
temperature (TH4)
Shortage of refrigerant
2 blinking
Abnormal high pressure (High
pressure switch 63H worked.)
Abnormal low pressure
3 blinking
Abnormality of outdoor fan
motor rotational speed
Protection from overheat operation(TH3)
4 blinking
Compressor overcurrent
breaking(Start-up locked)
Compressor overcurrent breaking
Abnormality of current sensor (P.B.)
Abnormality of power module
5 blinking
Open/short of discharge thermistor (TH4)
Open/short of outdoor thermistors
(TH3, TH6, TH7 and TH8)
ContentsInspection method
Error
code
+1
Check if stop valves are open.
Check if connectors (TH4, LEV-A and LEV-B) on outdoor controller
board are not disconnected.
U2
Check if unit is filled with specified amount of refrigerant.
Measure resistance values among terminals on outdoor linear
expansion valve using a tester.
Check if indoor/outdoor units have a short cycle on their air ducts.
U1
Check if connector (63H or 63L) on outdoor controller board is not disconnected.
Check if heat exchanger and filter is not dirty.
Measure resistance values among terminals on linear expansion valve
UL
using a tester.
Check the outdoor fan motor.
U8
Check if connector (TH3) on outdoor controller board is disconnected.
Ud
Check if stop valves are open.
UF
Check looseness, disconnection, and converse connection of
compressor wiring.
Measure resistance values among terminals on compressor using a tester.
UP
Check if outdoor unit has a short cycle on its air duct.
UH
U6
Check if connectors
U3
and connector
Measure resistance value of outdoor thermistors.
U4
(TH3,TH4,TH6 and TH7)
(CN3)
on outdoor power board are not disconnected.
on outdoor controller board
Detailed
reference
page
P.30
P.30
P32
P.31
P.32
P.32
P.33
P.32
P.31
P.30
P.31
6 blinking
Abnormality of heatsink
temperature
4 blinking
7 blinking
1 blinking
Abnormality of voltageCheck looseness, disconnection, and converse connection of
Abnormality of room temperature thermistor (TH1)
Abnormality of pipe temperature thermistor /Liquid (TH2)
Abnormality of pipe temperature
thermistor/Condenser-Evaporator
2 blinking
Abnormality of drain sensor (DS)
Float switch connector open
1 Error code displayed on remote controller
2 Refer to service manual for indoor unit.
Check if indoor/outdoor units have a short cycle on their air ducts.
U5
Measure resistance value of outdoor thermistor(TH8).
compressor wiring.
Measure resistance value among terminals on compressor using a tester
U9
Check the continuity of contactor (52C).
Check if power supply voltage decreases.
Check the wiring of CN52C.
Check the wiring of CNAF.
Check if connectors (CN20, CN21, CN29 and CN44) on indoor
P1
controller board are not disconnected.
P2
Measure resistance value of indoor thermistors.
P9
Check if connector (CN31),(CN4F) on indoor controller board is not
P4
disconnected.
Measure resistance value of indoor thermistors.
Measure resistance value among terminals on drain-up machine using
a tester.
P5
Check if drain-up machine works.
Check drain function.
Check if indoor unit has a short cycle on its air duct.
Check if heat exchanger and filter is not dirty.
P6
Measure resistance value on indoor and outdoor fan motors.
Check if the inside of refrigerant piping is not clogged.
Check if indoor thermistors(TH2 and TH5) are not disconnected from holder.
Check if stop valve is open.
Check converse connection of extension pipe. (on plural units connection)
P8
Check if indoor/outdoor connecting wire is connected correctly.
(on plural units connection)
P.31
P.32
.
2
2
2
2
2
2
Page 64
<Outdoor unit operation monitor function>
1ON23456
1 second
interval
Display
Contents to be inspected (During operation)
U1
U2
U3
U4
U5
U6
U8
U9
Ud
UF
UH
UL
UP
P1~P8
A0~A7
Abnormal high pressure (63H worked)
Abnormal high discharging temperature, shortage of refrigerant
Open/short circuit of discharging thermistor(TH4)
Open/short of outdoor unit thermistors(TH3, TH6, TH7 and TH8)
Abnormal temperature of heatsink
Abnormality of power module
Abnormality in outdoor fan motor
Abnormality of voltage
Overheat protection
Compressor overcurrent interruption (When Comp. locked)
Current sensor error
Abnormal low pressure
Compressor overcurrent interruption
Abnormality of indoor units
Communication error of M-NET system
[When optional part “A-Control Service Tool(PAC-SK52ST)” is connected to outdoor controller board(CNM)]
Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of error code by
controlling DIP SW2 on “A-Control Service Tool”.
Operation indicator SW2 : Indicator change of self diagnosis
SW2 setting
1ON23456
Display detail
Explanation for displayUnit
<Digital indicator LED1 working details>
(Be sure that 1 to 6 in the SW2 are set to OFF.)
(1) Display when the power supply ON
When the power supply ON, blinking displays by turns.
Wait for 4 minutes at the longest.
(2) When the display lights (Normal operation)
Operation mode display.
(Lighting)
LED1
The tens digit : Operation mode
DisplayOperation Model
O
C
H
d
+C5 is displayed during replacement opera-
tion.
Display during error postponement
Postponement code is displayed when
compressor stops due to the work of protection device.
Postponement code is displayed while error
is being postponed.
(3) When the display blinks
Inspection code is displayed when
compressor stops due to the work
of protection devices.
OFF / FAN
COOLING / DRY +
HEATING
DEFROSTING
The ones digit : Relay output
Display
0
1
2
3
4
5
6
7
8
A
Warming-up
Compressor
—
—
—
—
—
—
—
—
ON
ON
Compressor
—
—
—
—
ON
ON
ON
ON
—
—
SW2
4-way valve
—
—
ON
ON
—
—
ON
ON
—
ON
(Initial setting)
Solenoid valve
—
ON
—
ON
—
ON
—
ON
—
—
Display
Display
E0~E7
Inspection unit
0
Outdoor unit
1
Indoor unit 1
2
Indoor unit 2
3
Indoor unit 3
4
Indoor unit 4
Contents to be inspected (When power is turned on)
63H connector(yellow) is open.
F5
Indoor/outdoor communication error (Signal receiving error) (Outdoor unit)
E8
Indoor/outdoor communication error (Transmitting error) (Outdoor unit)
E9
Miswiring of indoor/outdoor unit connecting wire, excessive number of indoor units (4 units or more)
EA
Miswiring of indoor/outdoor unit connecting wire(converse wiring or disconnection)
Eb
Startup time over
EC
Communication error except for outdoor unit
64
Page 65
SW2 setting
1ON23456
4
25
2
45
1ON23456
Display detail
Pipe temperature / Liquid(TH3)
– 40~90
Explanation for displayUnit
– 40~90
(When the coil thermistor detects 0 or below, “–”
and temperature are displayed by turns.)
(Example) When -10;
0.5 secs. 0.5secs. 2 secs.
10
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
Discharge temperature (TH4)
3~217
Output step of outdoor FAN
0~10
The number of ON / OFF times of compressor
0~9999
Compressor integrating operation times
0~9999
Compressor operating current
0~50
3~217
(When the discharge thermistor detects 100 or
more, hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 105;
0.5 secs. 0.5secs. 2 secs.
1
05
0~10
0~9999
(When the number of times is 100 or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 42500 times (425 × 100 times);
0.5 secs. 0.5secs. 2 secs.
0~9999
(When it is 100 hours or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 2450 hours (245 ×10 hours);
0.5 secs. 0.5secs. 2 secs.
0~50
+Omit the figures after the decimal fractions.
Step
100 times
10 hours
A
1ON23456
1ON23456
1ON23456
1ON23456
Compressor operating frequency
0~255
0~255
(When it is 100Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 125Hz;
0.5 secs. 0.5secs. 2 secs.
1
25
LEV-A opening pulse
0~480
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 150 pulse;
0.5 secs. 0.5secs. 2 secs.
1
50
Error postponement code history (1)
of outdoor unit
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
“00” is displayed in case of no postponement.
Operation mode on error occurringOperation mode of when operation stops due to
error is displayed by setting SW2 like below.
(SW2)
Hz
Pulse
Code
display
Code
display
65
Page 66
SW2 setting
1ON23456
Display detail
Pipe temperature / Liquid(TH3) on error
occurring
– 40~90
Explanation for displayUnit
– 40~90
(When the coil thermistor detects 0 or below, “–”
and temperature are displayed by turns.)
(Example) When –15;
0.5 secs. 0.5secs. 2 secs.
15
1ON23456
1ON23456
1ON23456
1ON23456
Compressor temperature (TH4) or
discharge temperature (TH4) on error
occurring
3~217
Compressor operating current on error
occurring
0~20
Error code history (1) (latest)
Alternate display of abnormal unit
number and code
Error code history (2)
Alternate display of error unit number
and code
3~217
(When the temperature is 100 or more, the
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 130;
0.5 secs. 0.5secs. 2 secs.
1
30
0~20
When no error history,
“ 0 ” and “– –” are displayed by turns.
When no error history,
“ 0 ” and “– –” are displayed by turns.
A
Code
display
Code
display
1ON23456
1ON23456
Thermo ON time
0~999
Test run elapsed time
0~120
LEV-B opening pulse
0~480
0~999
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 245 minutes;
0.5 secs. 0.5secs. 2 secs.
2
45
0~120
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 105 minutes;
0.5 secs. 0.5secs. 2 secs.
1
05
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 150 pulse;
0.5 secs. 0.5secs. 2 secs.
1
50
66
Minute
Minute
Pulse
Page 67
SW2 setting
1ON23456
1ON23456
Capacity
RP200
RP250
Code
40
50
1ON23456
Display detail
The number of connected indoor units
Explanation for display
0~4
(The number of connected indoor units are displayed.)
Unit
Unit
1ON23456
1ON23456
Capacity setting display
Outdoor unit setting information
Indoor pipe temperature / Liquid (TH2(1))
Indoor 1
– 39~88
Displayed as an outdoor capacity code.
• The tens digit (Total display for applied setting)
Setting details
H·P /
Cooling only
Single phase / 3 phase
Display details
0 : H·P 1 : Cooling only
0 :
Single phase
2 : 3 phase
• The ones digit
Setting details
Defrosting switch
(Example) When heat pump, 3 phase and defrosting
– 39~88
(When the temperature is 0 or less, “–” and
temperature are displayed by turns.)
-39~88
(When the temperature is 0 or less, “–” and
temperature are displayed by turns.)
-39~88
(When the temperature is 0 or less, “–” and
temperature are displayed by turns.)
-40~200
(When the temperature is 0 or less, “–” and
temperature are displayed by turns.)
(When the thermistor detects 100 or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
°C
°C
Input current of outdoor unit
1ON23456
U9 Error status
1ON23456
1ON23456
DC bus voltage
300-750
0~500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0.1 A
Code
display
300-750
(When it is 100V or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
V
68
Page 69
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
25
1
Display detail
Capacity save
0~255
When air conditioner is connected to
M-NET and capacity save mode is
demanded, “0”~”100” is displayed.
When there is no setting
of capacity save “100” is
displayed.
Error postponement code history (2)
of outdoor unit
Explanation for displayUnit
0~255
(When the capacity is 100% hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 100%;
0.5 secs. 0.5secs. 2 secs.
1
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
“00” is displayed in case of no postponement.
00
%
Code
display
Error postponement code history (3)
of outdoor unit
Error code history (3) (Oldest)
Alternate display of abnormal unit
number and code
Error thermistor display
When there is no error thermistor,
“–“ is displayed.
Operation frequency on error occurring
0~255
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
“00” is displayed in case of no postponement.
When no error history, “0” and “– –“ are displayed by
turns.
3: Outdoor pipe temperature / Liquid (TH3)
6: Outdoor pipe temperature / 2-phase (TH6)
7: Outdoor ambient temperature (TH7)
8: Outdoor heatsink (TH8)
0~255
(When it is 100Hz or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 125Hz;
0.5 secs. 0.5secs. 2 secs.
Code
display
Code
display
Code
display
Hz
Fan step on error occurring
0~10
0~10
Step
69
Page 70
SW2 setting
15
15
15
15
1ON23456
Display detail
LEV-A opening pulse on error occurring
0~480
Explanation for displayUnit
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 secs. 0.5secs. 2 secs.
1
30
Pulse
1ON23456
1ON23456
1ON23456
1ON23456
Indoor room temperature (TH1) on error
occurring
8~39
Indoor pipe temperature / Liquid (TH2)
on error occurring
-39~88
Indoor pipe temperature / Cond./ Eva.
(TH5) on error occurring
-39~88
Outdoor pipe temperature / 2 phase
(TH6) on error occurring
-39~88
8~39
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
1ON23456
1ON23456
Outdoor ambient temperature (TH7) on
error occurring
-39~88
Outdoor heatsink temperature (TH8) on
error occurring
-40~200
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
-40~200
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
70
Page 71
SW2 setting
1ON23456
1ON23456
15
1
1ON23456
1ON23456
Display detail
Discharge superheat on error occurring
SHd
0~255
Cooling = TH4-TH6
Heating = TH4-TH5
Explanation for displayUnit
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs. 0.5secs. 2 secs.
1
50
1ON23456
1ON23456
Subcool on error occurring SC
0~130
Cooling = TH6-TH3
Heating = TH5-TH2
Thermo-on time until error stops
0~999
Indoor pipe temperature / Liquid
(TH2 (3))
Indoor 3
-39~88
Indoor pipe temperature / Cond./ Eva.
(TH5 (3))
Indoor 3
-39~88
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 secs. 0.5secs. 2 secs.
0~999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs. 0.5secs. 2 secs.
4
15
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
Minute
U9 Error status during the Error
postponement period
DescriptionDetection pointDisplay
Normal
Overvoltage error
Undervoltage error
Input current sensor error
L
Preventive control for excessive temperature rise of discharge temperature
Preventive control for excessive temperature rise of condensing temperature
Frosting preventing control
Preventive control for excessive temperature rise of radiator panel
(Example)
The following controls are activated.
• Primary current control
• Preventive control for excessive tempe rature rise of condensing temperature
• Preventive control for excessive tempe rature rise of heatsink
LED
1ON23456
Display detail
Controlling status of compressor
operating frequency
Explanation for displayUnit
The following code will be a help to know the
operating status of unit.
Code
display
Indoor pipe temperature / Liquid
(TH2(4))
Indoor 4
1ON23456
1ON23456
1ON23456
– 39~88
Indoor pipe temperature / (Cond./Eva.)
(TH5(4))
Indoor 4
– 39~88
Replacement operation
+If replacement operation is conducted
even once, "1" is displayed.
If replacement operation is less than 2
hrs, "0" is displayed.
– 39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
1: Conducted
0: Not yet
72
—
Page 73
11FUNCTION SETTING
Function
Settings
Mode No.
Setting No.
: Initial setting
(when sent from the factory)
Remarks
Power failure
automatic recovery
Indoor temperature
detecting 1
LOSSNAY
connectivity
Power supply
voltage
Auto operating
mode
Frost prevention
temperature
Humidifier control
Change of
defrosting control
OFF
ON
Average data from each indoor unit
Data from the indoor unit with remote controller
Data from main remote controller
Not supported
Supported
(Indoor unit does not intake outdoor air through LOSSNAY
)
Supported
(Indoor unit intakes outdoor air through LOSSNAY)
240V
220V, 230V
Auto energy-saving operation ON
Auto energy-saving operation OFF
2 (Normal)
3
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
Standard
For high humidity
1
2
1
2
3
1
2
3
1
2
1
2
1
2
1
2
1
2
01
02
03
04
05
15
16
17
The setting is
applied to all
the units in the
same
refrigerant
system.
11-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
(1) Functions available when setting the unit number to 00 (Select 00 referring to set the indoor unit number.)
1 The functions below are available only when the wired remote controller is used. The functions are not available for
floor standing models.
<Table 1> Function selections
Meaning of "Function setting"
Mode02:indoor temperature detecting
No.
No.1
No.2
No.3
OUTDOOR
INDOOR
INDOOR
Indoor temperature(ta)=
REMOTE
(SUB)
Average data of the
sensor on all the
REMOTE
(MAIN)
Initial
ta=(A+B)/2ta=(A+B)/2ta=Ata=A
setting
indoor units
Data of the sensor
ta=Ata=Bta=Ata=A
on the indoor unit that
connected with
remote controller
Data of the sensor
ta=Cta=Cta=Cta=C
on main remote
controller
73
OUTDOOR
INDOOR
REMOTE
(MAIN)
OUTDOOR
INDOOR
REMOTE
(SUB)
INDOOR
REMOTE
(MAIN)
REMOTE
(SUB)
OUTDOOR
INDOOR
REMOTE
(MAIN)
Page 74
(2) Functions available when setting the unit number to 01-04 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to setting the
unit number of Operating Procedure.
• When setting functions for a simultaneous twin/triple/quadruple indoor unit system, set the unit number to 01 to 04 for
each indoor unit in case of selecting different functions for each unit referring to setting the indoor unit number of
Operating Procedure.
• When setting the same functions for an entire simultaneous twin/triple/quadruple indoor unit system, set refrigerant
address to AL (07 in case of wireless remote controller) referring to setting the indoor unit number of Operating
Procedure.
: Initial setting (Factory setting
Mode
FunctionSettings
Filter sign100h1
Airflow
(
Fan speed
No.of air outlets4 directions1----
Optional high efficiency
filter
Vane setting
Energy saving airDisabled
flow(Heating mode
Optional humidifier
(
PLA only
Vane differential setting
in heating mode
(
cold wind prevention
SwingNot available Swing
Set temperature in heating
mode(4 deg up
Fan speed during theExtra low1
heating thermo OFF
Fan speed during the
cooling thermo OFF
Detection of abnormality of
the pipe temperature (P8)Not available
)
)
)
2500h072
No filter sign indicator
Quiet
Standard
High ceiling
3 directions092---2 directions
Not supported
Supported
No vanes
Vane No.1 setting
Vane No.2 setting
)
Enabled
Not supported
Supported
No.1 setting (TH5: 24-28
No.2 setting (Standard,TH5:28-32
)
No.3 setting (TH5: 32-38
Available Wave air flow
Available
Not available
Stop
Set fan speed
Set fan speed
Stop
Available
(
Vane No.3 setting : PLA only
)
)
PLA-BA
}
Temperature correction: Valid
Temperature correction: Invalid
)
)
PLA-BA
}
Setting
No.
No.
082---
10
112---
12
13
142--
23
24
252
27
28
4-Way
cassette
PLA-BA
3
1---
3---
3- --1
2
1---
3--1
2
1
2
1--
3-1
2
1
2
3
1
2
1
2
PEAD-EA(2)
PEAD-GA
---
---
-
---
---
-
----
----
--
--
Ceiling
concealed
PEA-GA
- : Not available
Ceiling suspended
PCA-GA(2)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
)
PCA-HA
mounted
PKA-GAL
PKA-FAL(2)
Wall
Mode No.11
Setting No. SettingsPLA-BAPCA-GA(2)
1
Vane No.3 setting
No Vanes
Less smudging
(
Downward position than the standard
)
No vane function
2Vane No.1 settingStandardStandard
3Vane No.2 setting
Less draft *
(
Upward position than the standard
)
Less draft *
(
Upward position than the standard
* Be careful of the smudge on ceiling.
74
)
Page 75
11-1-1. Selecting functions using the wired remote controller
First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room
temperature detection position is given.
For actual operations, refer to steps to .
Setting number
Mode number
Refrigerant addressUnit number
Selecting functions using the wired remote controller
Check the function selection setting.
Switch to function setting mode.
(Press
and at the same time
For modes 15 and higher,
press
with the remote controller stopped.)
Specify refrigerant address 00 (outdoor unit).
Specify unit No. 00. (indoor unit)
(Use
Select mode No. 02
and .)
Enter the setting.
(Press
(Specified indoor unit:
.)
BLOW operation)
(room temperature detection position).
Select setting No. 03 (remote controller fixed).
(Use
and .)
and at the same time.
NO
Modes 01 to 14 can be activated
and
by pressing buttons
simultaneously, and modes 15 to
28 by pressing buttons
and .
YES
Change refrigerant
address or unit No.
Enter the setting.
(Press
.)
Example:
Selecting room temperature
detection position
NO
Finished
YES
End function display.
(Press
and at the same time.)
The above procedure must be carried out only if changes are necessary.
75
Page 76
[Operating Procedure]
Check the setting items provided by function selection.
If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps
to , fill in the "Check" column in Table 1, then change them as necessary. For initial settings, refer to the indoor unit's installation manual.
Switch off the remote controller.
Hold down the ( mode is 15 to 28)and
buttons simultaneously for at least 2 seconds. will start to blink,
then the remote controller's display content will change as shown below.
* If the unit stops after
Check to see if there are any sources of noise or interference near the transmission path.
Note
If you have made operational mistakes during this procedure, exit function selection (see step ) then restart from step .
Set the indoor unit number.
Press the
area.
FILTER
Refrigerant address
display section
FUNCTION
SELECTION
ON/OFF
button so that "- -" blinks in the unit number display
Unit number
display section
FUNCTION
SELECTION
blinked for 2 seconds or "88" blinks in the room temperature display area for 2 seconds, a transmission error may have occurred.
TEST
Set the outdoor unit's refrigerant address.
Press the [
refrigerant address. The refrigerant address changes from "00" to "15".
(This operation is not possible for single refrigerant systems.)
Press the [
of the indoor unit for which you want to perform function selection. The unit
number changes to "00", "01", "02","03",04" and "AL" each time a button is
pressed.
CLOCK] buttons ( and ) to select the desired
CLOCK] buttons ( and ) to select the unit number
* To set modes 01 to 06 or 15 to 22, select unit number "00".
* To set modes 07 to 14 or 23 to 28, carry out as follows:
• To set each indoor unit individually, select "01" to "04".
• To set all the indoor units collectively, select "AL".
Confirm the refrigerant address and unit number.
Press the
number.
After a while, "- - " will start to blink in the mode number display area.
*"88" will blink in the room temperature display area if the selected refrigerant
address does not exist in the system.
Furthermore, if
refrigerant address display area also blinks, there are no units that correspond to the selected unit number. In this case, the refrigerant address and unit
number may be incorrect, so repeat steps and to set the correct ones.
Select the mode number.
Press the [
number.
(Only the selectable mode numbers can be selected.)
Select the setting content for the selected mode.
Press the
blink, so check the currently set content.
MODE
Mode number
display section
button to confirm the refrigerant address and unit
"F"
appears and blinks in the unit number display area and the
TEMP] buttons ( and ) to set the desired mode
button. The currently selected setting number will
MENU
When the refrigerant address and unit number are confirmed by pressing the
MODE
helps you find the location of the indoor unit for which you want to perform function
selection. However, if "00" or "AL" is selected as the unit number, all the indoor
units corresponding to the specified refrigerant address will start fan operation.
Example) When the refrigerant address is set to 00 and the unit number is 02.
Designate operation
* When grouping different refrigerant systems, if an indoor unit other than the
one to which the refrigerant address has been set to perform fan operation,
there may be another refrigerant address that is the same as the specified one.
In this case, check the DIP switch of the outdoor unit to see whether such a
refrigerant address exists.
Mode number
display section
Press the [
number.
button, the corresponding indoor unit will start fan operation. This
00 refrigerant address
Outdoor unit
Indoor unit
TEMP] buttons ( and ) to select the desired setting
Unit number 01Unit number 02
Remote controller
Mode number 02 = Indoor tempreture detection
Fan draft
Unit number 03
Setting number display section
Register the settings you have made in steps to .
Press the
to blink and registration starts.
* If " - - - " is displayed for both the mode number and setting number and "
Check to see if there are any sources of noise or interference near the transmission path.
If you wish to continue to select other functions, repeat steps to .
Complete function selection.
Hold down the ( mode is 15 to 28) and buttons
simultaneously for at least 2 seconds.
After a while, the function selection screen will disappear and the air condi-
tioner OFF screen will reappear.
Note
If a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check" column of Table
1 to indicate the change.
MODE
button. The mode number and setting number will start
FILTER
Setting number 1 = Indoor unit operating average
The mode number and setting number will stop blinking and remain lit, indicating the
end of registration.
" blinks in the room temperature display area, a transmission error may have occurred.
TEST
* Do not operate the remote controller for at least 30 seconds after completing
function selection. (No operations will be accepted even if they are made.)
Setting number 3 = Remote controller built-in sensor
76
Page 77
The flow of the function selection procedure is shown below. This example shows how to turn
off the function that raises the set temperature by 4 degrees during HEAT operation.
The procedure is given after the flow chart.
Check the function selection setting.
Switch to function selection mode.
(Enter address "50" in troubleshooting
mode, then press the HOUR button.)
Troubleshooting mode is the mode entered when
you press the CHECK button twice to display
"CHECK".
Specify unit No. "01" (since the function applies to unit 01).
(Set address "01" while still in troubleshooting mode, then press the MINUTE button.)
Note: You cannot specify the refrigerant address.
Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation).
(Set address "24" while still in troubleshooting mode, then press the HOUR button.)
Finished
End function selection mode.
(End troubleshooting mode.)
YES
NO
Note: When you switch to function selection mode
on the wireless remote controller's operation
area, the unit ends function selection mode
automatically if nothing is input for 10 minutes
or longer.
Select setting No. "02" (OFF).
(Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change
unit No.
YES
NO
11-1-2. Selecting functions using the wireless remote controller (Type C)
Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refrigerant system with wireless function. Refrigerant address cannot be specified by the wireless remote controller.
[Flow of function selection procedure]
CHECK
SET
FAN
VANE
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
h
min
HOUR button
MINUTE button
ON/OFF button
Check button
ON/OFF
MODE
CHECK
TEST RUN
[Operating instructions]
Check the function settings.
3UHVVWKHEXWWRQWZLFHFRQWLQXRXVO\ĺ&+(&.LVOLWDQG³´EOLQNV
Press the temp button once to set “50”. Direct the wireless remote controller toward the receiver of the indoor unit and press
the button.
CHECK
h
Set the unit number.
Press the temp button to set the unit number. (Press “01” to specify the indoor unit whose unit number is 01.)
Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
By setting unit number with the button, specified indoor unit starts performing fan operation.
min
Detect which unit is assigned to which number using this function. If unit number is set to AL, all the indoor units in same
refrigerant system start performing fan operation simultaneously.
* If a unit number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the unit number
setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double ping sound” may be heard. Reenter the unit number
setting.
Select a mode.
Press the temp button to set a mode. Press “24” to turn on the function that raises the set temperature by 4 degree
during heat operation. Direct the wireless remote controller toward the sensor of the indoor unit and press the button.
Setting number: 1 = 2 beeps (0.4 seconds each)
2 = 2 beeps (0.4 seconds each, repeated twice)
3 = 2 beeps (0.4 seconds each, repeated 3 times)
* If a setting number that cannot be recognized by the unit is entered, the setting will turn back to the original setting.
If the signal was not received by the sensor, you will not hear a beep or a “double ping sound” may be heard. Reenter the setting number.
*
Repeat steps and to make an additional setting without changing unit number.
Repeat steps to to change unit number and make function settings on it.
Complete the function settings.
Press button.
* Do not use the wireless remote controller for 30 seconds after completing the function setting.
77
min
h
h
Page 78
11-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode.
Change the setting when needed.
Item 1
1.Change language
("CHANGE LANGUAGE")
2.Function limit
("FUNCTION SELECTION")
3.Mode selection
("MODE SELECTION")
4.Display change
("DISP MODE SETTING")
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
[Function selection flowchart] Refer to next page.
[1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting.
(Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
[Detailed setting]
[4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
• Press the [
MENU] button to change the language.
Japanese (JP), English (GB), German (D), Spanish (E),
Russian (RU), Italian (I), Chinese (CH),? French (F)
[4] -2. Function limit
(1) Operation function limit setting (operation lock)
• To switch the setting, press the [ ON/OFF] button.
no1 : Operation lock setting is made on all buttons other than
the [
ON/OFF] button.
no2 : Operation lock setting is made on all buttons.
OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER]
and [ ON/OFF] buttons at the same time for 2 seconds.) on
the normal screen after the above setting is made..
(2) Use of automatic mode setting
When the remote controller is connected to the unit that has automatic operation mode, the following settings can be made.
• To switch the setting, press the [ ON/OFF] button.
ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.
OFF: The automatic mode is not displayed
when the operation mode is selected.
(3) Temperature range limit setting
After this setting is made, the temperature can be changed within the
set range.
• To switch the setting, press the [ ON/OFF] button.
LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode.
OFF (initial setting) : The temperature range limit is not active.
When the setting, other than OFF, is made, the temperature range limit setting
*
on cooling, heating and automatic mode is made at the same time. However
the range cannot be limited when the set temperature range has not changed.
•
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
•
To switch the upper limit setting and the lower limit setting, press the
button. The selected setting will flash and the temperature can be set.
Not necessary to set this mode. Refer to OPERATION MANUAL of
Optional Parts (Panel) for details on operation.
Fixed air flow direction mode
Not necessary to set this mode. Refer to OPERATION MANUAL of
indoor unit for details on operation.
The remote controller will be the main controller. (Initial setting value)
The remote controller will be the sub controller.
The clock function can be used. (Initial setting value)
The clock function cannot be used.
Weekly timer can be used. (Initial setting value)
Auto off timer can be used.
Simple timer can be used.
Timer mode cannot be used.
The set contact numbers are not displayed in case of error.
(Initial setting value)
The set contact numbers are displayed in case of error.
The temperature unit °C is used. (Initial setting value)
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
Room air temperature is not displayed.
One of “Automatic cooling” and “Automatic heating” is displayed
under the automatic mode is running. (Initial setting value)
Only “Automatic” is displayed under the automatic mode.
79
Page 80
12
MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER
12-1. HOW TO "MONITOR THE OPERATION DATA"
• Turning on the [Monitoring the operation data]
(3)
Example) Request code "004"
'LVFKDUJHWHPSHUDWXUHÛ&
Refrigerant address "00"
(7)
(5)
(1)
(2)
(4)
(1) Press the
(2) Press the
Note)
Operating the service inspection monitor
- - - ] appears on the screen (at
[
(The display (at
(3) Press the [TEMP] buttons (
[Screen
(4) Press the [CLOCK] buttons (
(5) Press the
(The requested data will be displayed at
Data collected during operation of the remote controller will be displayed.
The collected data such as temperature data will not be updated automatically even if the data changes.
To display the updated data, carry out step (4) again.
TEST
CHECK
It is not possible to switch to [Maintenance monitor] during data request in maintenance mode (i.e., while "
since no buttons are operative.
]
FILTER
button for 3 seconds so that [ Maintenance mode] appears on the screen (at ).
button for 3 seconds to switch to [Maintenance monitor].
) when [Maintenance monitor] is activated.
) now allows you to set a request code No.)
and ) to select the desired refrigerant address.
and ) to set the desired request code No.
button to perform data request.
in the same way as in maintenance mode.)
(6)
A: Maintenance mode
B: Refrigerant address
C: Data display area
D: Request code display area
- - - -"
is blinking)
Canceling the Monitoring the operation data
(6) While [Maintenance monitor] is displayed, press the
(7) To return to normal mode, press the
ON/OFF
CHECK
button.
button for 3 seconds to return to maintenance mode.
80
Page 81
12-2. REQUEST CODE LIST
* Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed.
Request content
Request code
Operation state
0
Compressor-Operating current (rms)
1
Compressor-Accumulated operating time
2
Compressor-Number of operation times
3
Discharge temperature (TH4)
4
Outdoor unit - Liquid pipe 1 temperature (TH3)
5
Outdoor unit - Liquid pipe 2 temperature
6
Outdoor unit-2-phase pipe temperature (TH6)
7
8
Outdoor unit-Outside air temperature (TH7)
9
Outdoor unit-Heatsink temperature (TH8)
10
11
Discharge superheat (SHd)
12
Sub-cool (SC)
13
14
15
Compressor-Operating frequency
16
Compressor-Target operating frequency
17
Outdoor unit-Fan output step
18
Outdoor unit-Fan 1 speed
19
(Only for air conditioners with DC fan motor)
Outdoor unit-Fan 2 speed
20
(Only for air conditioners with DC fan motor)
21
LEV (A) opening
22
LEV (B) opening
23
24
Primary current
25
DC bus voltage
26
27
28
Number of connected indoor units
29
Indoor unit-Setting temperature
30
Indoor unit-Intake air temperature <Measured by thermostat>
31
Indoor unit-Intake air temperature (Unit No. 1)
32
<Heat mode-4-deg correction>
Indoor unit-Intake air temperature (Unit No. 2)
33
<Heat mode-4-deg correction>
Indoor unit-Intake air temperature (Unit No. 3)
34
<Heat mode-4-deg correction>
Indoor unit-Intake air temperature (Unit No. 4)
35
<Heat mode-4-deg correction>
36
Indoor unit - Liquid pipe temperature (Unit No. 1)
37
Indoor unit - Liquid pipe temperature (Unit No. 2)
38
Indoor unit - Liquid pipe temperature (Unit No. 3)
39
Indoor unit - Liquid pipe temperature (Unit No. 4)
40
41
Indoor unit-Cond./Eva. pipe temperature (Unit No. 1)
42
Indoor unit-Cond./Eva. pipe temperature (Unit No. 2)
43
Indoor unit-Cond./Eva. pipe temperature (Unit No. 3)
44
Indoor unit-Cond./Eva. pipe temperature (Unit No. 4)
45
46
47
Thermo ON operating time
48
Test run elapsed time
49
Description
(Display range)
Refer to 12-2-1. Detail Contents in Request Code.
0 – 50
0 – 9999
0 – 9999
3 – 217
-40 – 90
-40 – 90
-39 – 88
-39 – 88
-40 – 200
0 – 255
0 – 130
0 – 255
0 – 255
0 – 10
0 – 9999
0 – 9999
0 – 500
0 – 500
0 – 50
180 – 370
0– 4
17 – 30
8 – 39
8 – 39
8 – 39
8 – 39
8 – 39
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
-39 – 88
0 – 999
0 – 120
UnitRemarks
10 hours
100 times
Hz
Hz
Step
rpm
rpm
Pulses
Pulses
Units
Minutes
Minutes
–
A
"0" is displayed if the air conditioner is a single-fan
type.
A
V
"0" is displayed if the target unit is not present.
is displayed if the target unit is not present.
"0"
is displayed if the target unit is not present.
"0"
Not possible to activate maintenance mode during the test run.
81
Page 82
Request content
Request code
Indoor unit-Control state
50
Outdoor unit-Control state
51
Compressor-Frequency control state
52
Outdoor unit-Fan control state
53
Actuator output state
54
Error content (U9)
55
56
57
58
59
Signal transmission demand capacity
60
Contact demand capacity
61
External input state (silent mode, etc.)
62
63
64
65
66
67
68
69
Outdoor unit-Capacity setting display
70
Outdoor unit-Setting information
71
72
Outdoor unit-SW1 setting information
73
Outdoor unit-SW2 setting information
74
75
Outdoor unit-SW4 setting information
76
Outdoor unit-SW5 setting information
77
Outdoor unit-SW6 setting information
78
Outdoor unit-SW7 setting information
79
Outdoor unit-SW8 setting information
80
Outdoor unit-SW9 setting information
81
Outdoor unit-SW10 setting information
82
83
M-NET adapter connection (presence/absence)
84
85
86
87
88
89
Display of execution of replace/wash operation
Outdoor unit-Microcomputer version information
90
Outdoor unit-Microcomputer version information (sub No.)
91
92
93
94
95
96
97
98
99
Outdoor unit - Error postponement history 1 (latest)
100
Outdoor unit - Error postponement history 2 (previous)
101
Outdoor unit - Error postponement history 3 (last but one)
0Normal
1Preparing for heat operation
2–
3–
4Heater is ON.
5Anti-freeze protection is ON.
6Overheat protection is ON.
7Requesting compressor to turn OFF
FThere are no corresponding units.
Power currently
supplied to compressor
–
ON
ON
C: Data display area
D: Request code display area
Compressor4-way valveSolenoid valve
Discharge temperature 69
Refrigerant address "00"
–
ON
ON
ON
ON
–
ON
ON
ON
ON
ON
–
ON
ON
ON
ON
[Outdoor unit – Control state] (Request code ":51")
Data displayState
0000Normal
0001Preparing for heat operation
0002Defrost
[Compressor – Frequency control state] (Request code ":52")
Data display
00
Frequency control state
Frequency control state
Frequency control state
DisplayCurrent limit control
0No current limit
1Primary current limit control is ON.
2Secondary current limit control is ON.
L Reduces maintenance work drastically.
L Enables you to check operation data of the indoor and outdoor units by remote controller.
Furthermore, use of maintenance stable-operation control that fixes the operating frequency, allows smooth inspection, even for
inverter models.
Smooth Maintenance Function
Easy maintenance information (unit)
CompressorOutdoor unitIndoor unit
Accumulated operating
time
(%10 hours)temperature ()temperature ()
Number of ON/OFFDischarge
times (%10 times)temperature ( )temperature ( )
OperatingOutside airFilter operating
current (A)temperature ()time* (Hours)
* The filter operating time is the time that has elapsed since the filter was reset.
Heat exchanger
Discharge temperature 64
Intake air
Heat exchanger
L Conventional inspection work
L
Outdoor unit
Remove the
service panel.
Measure the discharge
temperature.
L
L
Indoor unit
Measure
the intake air
temperature.
Measure the outside air
temperature
L
13-1. MAINTENANCE MODE OPERATION METHOD
*
If you are going to use 13-2. "GUIDE FOR OPERATION CONDITION", set the airflow to "High" before activating maintenance mode.
L Switching to maintenance mode
Maintenance mode can be activated either when the air conditioner is operated or stopped.
It cannot be activated during test run.
+ Maintenance information can be viewed even if the air conditioner is stopped.
N Remote controller button information
Compressor information
Operation mode
(1) Press the
[Display
TEST
]
MAINTENANCE
button for 3 seconds to switch to maintenance mode.
If stable operation is unnecessary or if you want to check the data with the air conditioner stopped, skip to step (4).
Outdoor unit information
Indoor unit information
Confirm
Activate/cancel maintenance mode
L Fixed Hz operation
The operating frequency can be fixed to stabilize operation of inverter model.
If the air conditioner is currently stopped, start it by this operation.
(2) Press the
[Display
(3) Press the
[Display
MODE
]
FILTER
] Waiting for stabilization
button to select the desired operation mode.
Stable cooling
operation
COOL
STABLE MODE
Stable heating
operation
HEAT
STABLE MODE
Stable operation
cancellation
STABLE MODE
CANCEL
( ) button to confirm the setting.
90
Stabilized
After 10 to 20 minutes
Page 91
L Data measurement
ON/OFF
ON/OFF
When the operation is stabilized, measure operation data as explained below.
(4) Press the [TEMP] buttons (
and ) to select the desired refrigerant address.
[Screen
]
(5) Select the type of data to be displayed.
After selecting, go to step (6).
Compressor information
button
Cumulative
]
operation time
COMP ON
x10 HOURS
MENU
[Display
Outdoor unit information
button
Heat exchanger
[Display
]
temperature
OUTDOOR UNIT
H·EXC. TEMP
Indoor unit information
button
Indoor room
[Display
]
temperature
INDOOR UNIT
INLET TEMP
ON/OFF NumberOperating current
COMP ON
x100 TIMES
Comp. discharge
temperature
OUTDOOR UNIT
OUTLET TEMP
Heat exchanger
temperature
INDOOR UNIT
H·EXC. TEMP
COMP ON
CURRENT (A)
Outdoor ambient
temperature
OUTDOOR UNIT
OUTDOOR TEMP
Filter operating
time
INDOOR UNIT
FILTER USE H
(6) Press the
FILTER
( ) button to confirm the setting.
[Display example for accumulated operating time]
Display
Waiting for response
Blinking
After approx.
10 seconds
(7) Data is displayed on the display (at ).
To check the data for each item, repeat steps (5) to (7).
(8) To cancel maintenance mode, press the
TEST
N Refrigerant address
Single refrigerant system
In the case of single refrigerant system, the refrigerant
address is "00" and no operation is required. Simultaneous
twin, triple and quadruple units belong to this category
(Single refrigerant system).
[1:1]
Refrigerant
address=00
Outdoor
unit
Indoor unit
01
[Twin]
Refrigerant
address=00
Outdoor
unit
Indoor unit
01
Indoor unit
02
12,340 hours
button for 3 seconds or press the
Multi refrigerant system (group control)
Up to 16 refrigerant systems (16 outdoor units) can be
connected as a group by 1 remote controller. To check or
set the refrigerant addresses.
Refrigerant
address
00
Outdoor
unit
Indoor unit
01
Refrigerant
address
01
Outdoor
unit
Indoor unit
01
Refrigerant
address
02
Outdoor
unit
Indoor unit
01
button.
Refrigerant
address
15
Outdoor
unit
Indoor unit
01
Remote
controller
Remote
controller
Remote
controller
91
Page 92
13-2. GUIDE FOR OPERATION CONDITION
Inspection itemResult
BreakerGoodRetightened
Terminal blockOutdoor UnitGoodRetightened
Loose con-
nection
(Insulation resistance)M
Power supply
(Voltage)V
Accumulated operating timeTime
Number of ON/OFF timesTimes
Com-
pressor
CurrentA
Refrigerant/heat exchanger temperature
Refrigerant/discharge temperature
Air/outside air temperatureCOOL HEAT
(Air/discharge temperature)COOL HEAT
Temperature
AppearanceGood
Outdoor Unit
Heat exchangerGood
Sound/vibrationNonePresent
Cleanli-
ness
Air/intake air temperatureCOOL HEAT
(Air/discharge temperature)COOL HEAT
Refrigerant/heat exchanger temperature
Filter operating time*Time
Temperature
Decorative panelGood
FilterGood
Indoor Unit
FanGood
Heat exchangerGood
Cleanliness
Sound/vibrationNonePresent
* The filter operating time is the time that has elapsed since the filter was reset.
Indoor UnitGoodRetightened
COOL HEAT
COOL HEAT
Cleaning required
Cleaning required
COOL HEAT
Cleaning required
Cleaning required
Cleaning required
Cleaning required
Check Points
Enter the temperature differences between ,, and into
the graph given below.
Operation state is determined according to the plotted areas on
the graph.
For data measurements, set the fan speed to "Hi" before activating maintenance mode.
ClassificationItemResult
Inspection
Temperature
Cool
difference
Inspection
Temperature
Heat
difference
* Fixed Hz operation may not be possible under the following tempera-
ture ranges.
A)In cool mode, outdoor intake air temperature is 40 or higher or
indoor intake air temperature is 23 or lower.
B)In heat mode, outdoor intake air temperature is 20 or higher or
indoor intake air temperature is 25 or lower.
* If the air conditioner is operated at a temperature range other than the
ones above but operation is not stabilized after 30 minutes or more have
elapsed, carry out inspection.
* In heat mode, the operation state may vary due to frost forming on the
outdoor heat exchanger.
Is "D000" displayed stably on the remote
controller?
Discharge temperature) – ( Outdoor
(
heat exchanger temperature)
Indoor intake air temperature) – (
(
Indoor heat exchanger temperature)
Is "D000" displayed stably on the remote
controller?
(
Discharge temperature) – ( Indoor
heat exchanger temperature)
Indoor heat exchanger temperature) –
(
(
Indoor intake air temperature)
Stable Unstable
Stable Unstable
AreaCheck item
Normal
Filter inspection
Inspection A
Inspection B
Inspection C
Normal operation state
Filter may be clogged. *1
Performance has dropped. Detailed in-
spection is necessary.
Refrigerant amount is dropping.
Filter or indoor heat exchanger may be
clogged.
Judgment
CoolHeat
* The above judgement is just a guide based on Japanese standard
conditions.
It may be changed depending on the indoor and outdoor
temperature.
*1 It may be judged as "Filter inspection" due to the outdoor and
indoor temperature, even though it is not clogged.
(1) Remove 3 service panel fixing screws (5 × 10) and slide
the hook on the right downward to remove the service
panel.
(2) Remove screws (3 for front, 3 for rear/5 × 10) of the top
panel and remove it.
2. Removing the fan motor (MF1, MF2)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 5 fan grille fixing screws (5 × 10) to detach the
fan grille. (See figure 1.)
(4) Remove a nut (for right handed screw of M6) to detach
the propeller. (See photo 1.)
(5) Disconnect the connectors, CNF1 and CNF2 on controller
circuit board in electrical parts box.
(6) Remove 4 fan motor fixing screws (5 × 25) to detach the
fan motor. (See photo 2.)
Figure 1
Grille
fixing
screws
Grille
fixing
screws
Photo 1
Nut
PHOTOS & ILLUSTRATION
Top panel fixing screws
Slide
Front panel
Propeller
Photo 2
Fan motor fixing screws
Top panel
Service panel
Fan grille
Service panel
fixing screws
Cover
panel(front)
Fan
motor
3. Removing the electrical parts box
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the indoor/outdoor connecting wire and power
supply wire from terminal block.
(4) Disconnect the connectors on the controller circuit board.
(5) Remove the terminal cover and disconnect the
compressor lead wire.
(6) Remove an electrical parts box fixing screw (4 × 10) and
detach the electrical parts box by pulling it upward. The
electrical parts box is fixed with 2 hooks on the left and 1
hook on the right.
Photo 3
Controller circuit
board (C.B.)
Fan motor fixing screws
Electrical parts box
Electrical parts box
fixing screw
93
Terminal
block (TB1)
Terminal
block (TB2)
Noise filter
circuit
board (N.F.)
Page 94
OPERATING PROCEDURE
4. Removing the thermistor <Outdoor 2-phase pipe> (TH6)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the connectors, TH6 and TH7 (red), on the
controller circuit board in the electrical parts box.
(4) Loosen the 2 wire clamps on top of the electrical parts box.
(5) Pull out the thermistor <Outdoor 2-phase pipe> (TH6)
from the sensor holder.
Note: In case of replacing thermistor <Outdoor 2-phase
pipe> (TH6), replace it together with thermistor
<Outdoor> (TH7) since they are combined together.
Refer to No.6 below to remove thermistor <Outdoor>.
Photo 4
Electrical parts box
PHOTOS
Thermistor
<Outdoor 2-phase pipe>(TH6)
Clamp
5. Removing the thermistor <Outdoor> (TH7)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Disconnect the connector TH7 (red) on the controller circuit
board in the electrical parts box.
(4) Loosen the 2 wire clamps on top of the electrical parts box.
(See photo 4.)
(5) Pull out the thermistor <Outdoor> (TH7) from the sensor
holder.
Note: In case of replacing thermistor <Outdoor> (TH7),
replace it together with thermistor <Outdoor 2 phase pipe> (TH6), since they are combined together.
Refer to No.5 above to remove thermistor <Outdoor
2-phase pipe>.
6. Removing the thermistor <Outdoor pipe> (TH3) and thermistor <Discharge> (TH4)
(1) Remove the service panel. (See figure 1.)
(2) Disconnect the connectors, TH3 (white) and TH4 (white)
on the controller circuit board in the electrical parts box.
(3) Loosen the clamp for the lead wire in the rear of the elec-
trical parts box.
[Removing the thermistor<Outdoor pipe>(TH3)]
(4) Pull out the thermistor <Outdoor pipe> (TH3) from the
sensor holder.
Photo 5
Lead wire of thermistor <Outdoor> (TH7)
Sensor holder
Photo 6(Photo:PUHZ-RP250YHA2)
Thermistor <Outdoor pipe> (TH3)
Thermistor
<Discharge>
(TH4)
[Removing the thermistor<Discharge>(TH4)]
For RP200
(4) Remove the soundproof cover(upper) for compressor.
(5) Pull out the thermistor <Discharge> (TH4) from the ther-
mo-holder of the compressor shell.
For RP250
(4) Pull out the thermistor <Discharge> (TH4) from the sen-
sor holder.
Soundproof
cover(upper) for
compressor
Compressor
(MC)
94
Page 95
OPERATING PROCEDURE
7. Removing the 4-way valve coil (21S4) and linear expansion valve coil (LEV-A, LEV-B) and bypass valve coil(SV)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box . (See photo 3.)
[Removing the 4-way valve coil]
(4) Remove 4-way valve coil fixing screw (M4 × 6).
(5) Remove the 4-way valve coil by sliding the coil toward you.
[Removing the linear expansion valve coil]
(4) Remove the linear expansion valve coil by sliding the coil
upward.
[Removing the bypass valve coil]
(4) Remove bypass valve coil fixing screw (M4 × 6).
(5) Remove the bypass valve coil by sliding the coil upward.
PHOTOS
Photo 7(Photo:PUHZ-RP200YHA2)
Bypass valve coil fixing
screw
Bypass
valve coil
Bypass
valve
Linear
expansion valve
coil(LEV-A)
Linear
expansion
valve
4-way
valve
coil
4-way valve
4-way valve coil fixing screw
8. Removing the 4-way valve and bypass valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 valve bed fixing screws (4 × 10), 4 ball valve
and stop valve fixing screws (5 × 16) then remove the
valve bed.
(5) Remove 3 right side panel fixing screws (5 × 10) in the
rear of the unit then remove the right side panel.
[Removing the 4-way valve]
(6) Remove the 4-way valve coil.
(7) Recover refrigerant.
(8) Remove the welded part of 4-way valve.
[Removing the bypass valve]
(6) Remove bypass valve coil.
(7) Recover refrigerant.
(8) Remove the welded part of bypass valve.
9. Removing the linear expansion valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 valve bed fixing screws (4 × 10), 4 ball valve
and stop valve fixing screws (5 × 16) then remove the
valve bed.
(4) Remove 4 right side panel fixing screws (5 × 10) in the rear
of the unit then remove the right side panel.
(5) Remove the linear expansion valve coil.
(6) Recover refrigerant.
(7) Remove the welded part of linear expansion valve.
Note 1: Recover refrigerant without spreading it in
the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the parts of refrigerant cir-
cuit, cover it with a wet cloth to prevent it
from heating (120°C or more), then braze
the pipes so that the inside of pipes are
not oxidized.
95
Page 96
OPERATING PROCEDURE
10. Removing the high pressure switch (63H)(63H1)(63H2)
and the low pressure switch (63L)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 3 right side panel fixing screws (5 × 10) in the
rear of the unit and remove the right side panel.
(4) Pull out the lead wire of high pressure switch and low
pressure switch.
(5) Recover refrigerant.
(6) Remove the welded part of high pressure switch and low
pressure switch.
63H(For RP200)
63H1, 63H2, 63L(For RP250)
Note 1: Recover refrigerant without spreading it in
the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the parts of refrigerant cir-
cuit, cover it with a wet cloth to prevent it
from heating (100°C or more), then braze
the pipes so that the inside of pipes are
not oxidized.
PHOTOS
Photo 8(Photo:PUHZ-RP200YHA2)
High pressure switch
11. Removing the compressor (MC)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 2 front cover panel fixing screws (5 × 10) and
remove the front cover panel.
(4) Remove 2 back cover panel fixing screws (5 × 10) and
remove the back cover panel.
(5) Remove the electrical parts box. (See photo 3.)
(6) Remove 3 valve bed fixing screws (4 × 10), 4 ball valve
and stop valve fixing screws (5 × 16), then remove the
valve bed.
(7) Remove 3 right side panel fixing screws (5 × 10) in the
the separator.
(9) Remove the soundproof cover for compressor.
(10) Remove the terminal cover and remove the compressor
lead wire.
(11) Recover refrigerant.
(12) Remove the 3 points of the compressor fixing nut using a
spanner or a adjustable wrench.
(13) Remove the welded pipe of compressor inlet and outlet
and remove the compressor.
Note: Recover refrigerant without spreading it in the air.
Photo 9
Compressor
terminal
Compressor
(MC)
Soundproof
cover
Compressor
fixing nut
96
Page 97
97
OPERATING PROCEDURE
12. Removing the accumulator(RP200)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 2 front cover panel fixing screws (5 × 10) and
remove the front cover panel.
(4) Remove 2 back cover panel fixing screws (5 × 10) and
remove the back cover panel.
(5) Remove the electrical parts box. (See photo 3.)
(6) Remove 3 valve bed fixing screws (4 × 10), 4 ball valve
and stop valve fixing screws (5 × 16) then remove the
valve bed.
(7) Remove 3 right side panel fixing screws (5 × 10) in the
rear of the unit and remove the right side panel.
(8) Recover refrigerant.
(9) Remove 2 welded pipes of accumulator inlet and outlet.
(10) Remove 2 accumulator leg fixing screws (4 × 10).
Note: Recover refrigerant without spreading it in the air.
Photo 11
Inlet
Outlet
Photo 10
Valve bed
fixing screw
Valve bed
Separator
Compressor
Separator fixing
screw
Compressor fixing nuts
PHOTOS
Accumulator
Valve bed
fixing screws
Accumulator
leg fixing
screws
Accumulator
13. Removing the power receiver(RP250)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove 2 front cover panel fixing screws (5 × 10) and
remove the front cover panel.
(4) Remove 2 back cover panel fixing screws (5 × 10) and
remove the back cover panel.
(5) Remove the electrical parts box. (See photo 3.)
(6) Remove 3 valve bed fixing screws (4 × 10) and 4 ball valve
and stop valve fixing screws (5 × 16) and then remove the
valve bed.
(7) Remove 3 right side panel fixing screws (5 × 10) in the
rear of the unit and then remove the right side panel.
(8) Recover refrigerant.
(9) Remove 4 welded pipes of power receiver inlet and outlet.
(10) Remove 2 receiver leg fixing screws (4 × 10).
Note: Recover refrigerant without spreading it in the air.
Photo 12
Compressor
(MC)
Pipes of power receiver
Receiver leg
fixing screws
Power receiver
Receiver leg
Page 98
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Nov. 2007 No.OCH428 PDF 8
Made in Japan
New publication, effective Nov. 2007
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.