Before obtaining access to terminal, all supply
circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the followings.
· Be sure to perform replacement operation before test run.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
3
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
Gauge manifold·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
Charge hose·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
Electronic scale
Gas leak detector·Use the detector for R134a, R407C or R410A.
Adaptor for reverse flow check·Attach on vacuum pump.
Refrigerant charge base
Refrigerant cylinder·Only for R410A ·Top of cylinder (Pink)
·Cylinder with syphon
Refrigerant recovery equipment
specifications
. (UNF1/2)
4
5
2-3. Precautions when reusing existing R22 refrigerant pipes
(1) Flowchart
Measure the existing pipe thickness and check
for damage.
The existing pipe thickness meets specifications and the pipes are not damaged.
Check if the existing air conditioner can operate.
The existing air conditioner can operate.The existing air conditioner cannot operate.
After operating the cooling system for about
30 minutes, do a pump down work.
Disconnect the existing air conditioner from
the pipes.
The existing piping can be reused.
After flaring the pipes again, connect the
new air conditioner.
Use a refrigerant recovery device to recover the refrigerant.
Check the oil condition when recovering refrigerant.
Oil is clean. (Clear to brownish color)
In case that existing pipes were
used for gas or oil heat pump
system, be sure to clean the pipes.
Oil is dirty. (Black color)
The existing pipe thickness does not meet
specifications or the pipes are damaged.
When the compressor bearings
are seized, winding is damaged
or the compressor breaks down,
iron particles or oil deterioration will
blacken the oil.
The existing pipes cannot be reused.
Use new pipes.
Perform the following inspections: air
tightness test, vacuum dryness (additional
refrigerant charge), gas leakage check
Replacement operation
Test operation
·When performing replacement operation, make sure that DIP SW8-2 on outdoor unit controller board is
set to ON.
+Chemical compounds containing chlorine left in existing pipes are recovered by replace filter.
LThe air conditioner automatically performs cooling operation through replace filter for about 2 hours.
Connecting a new air conditioner to existing R22 refrigerant pipes
Flare the pipe for the use with R410A refrigerant.
Use the flare nut attached to indoor and outdoor unit of the new air conditioner only.
When reusing existing R22 refrigerant pipes of which gas pipe is :28.58mm and, when the outdoor unit is installed to lower
position than the indoor unit, be sure to change the setting of the DIP SW8-1 on the controller circuit board of the outdoor
unit to ON.
=This is to increase the speed of refrigerant passing in the gas pipe so that refrigerant oil can smoothly flow in the system.
• Use a different-diameter joint or brazing for the connection.
When reusing standard-size existing R22 refrigerant pipes.
The pipes can be reused with pipe length restriction described on TECHNICAL DATA BOOK.
(2) Cautions for refrigerant piping work
1/4
3/8
1/2
5/8
3/4
6.35
9.52
12.70
15.88
19.05
17.0
22.0
26.0
29.0
36.0
17.0
22.0
24.0
27.0
36.0
Nominal
dimensions(inch)
Flare nut dimensions
Outside
diameter
Dimension B
(mm)
R410AR22
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working
pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7mm or below.)
Diagram below: Piping diameter and thickness
Nominal
dimensions (inch)
1/4
3/8
1/2
5/8
3/4
7/8
1
1-1/8
Outside
diameter (mm)
6.35
9.52
12.70
15.88
19.05
22.20
25.40
28.58
Thickness (mm)
R410AR22
0.8
0.8
0.8
1.0
—
—
—
—
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because of its working pressure higher than that of other refriger
ants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also
have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring
dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes.
Use torque wrench corresponding to each dimension.
-
Dimension A
Flare cutting dimensions
Nominal
dimensions(inch)
Outside
diameter
1/4
3/8
1/2
5/8
3/4
6.35
9.52
12.70
15.88
19.05
Dimension A
R410AR22
9.1
13.2
16.6
19.7
24.0
+0
( )
-0.4
9.0
13.0
16.2
19.4
23.3
(mm)
Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materialsUseR410A toolsCan R22 tools be used?
Gauge manifold
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
Air purge, refrigerant charge and
operation check
Gas leak check
Refrigerant recovery
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Refrigerant charge
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Refrigerant charge
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil, ether oil and
alkylbenzene oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adopter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT. (Max.30m)
The refrigerant circuit with LEV(Linear Expansion Valve) and accumulator always control the optimal refrigerant level
regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often
causes problems. It is completely eliminated by chargeless system. This unique system improves the quality
and reliability of the work done. It also helps to speed up the installation time.
7
4SPECIFICATIONS
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Airflow
Main piping:
Liquid line size
:12.7 over all length [m]
% 0.12 [kg/m]
=
Additional charge amount
for 70 m
RP200 3.6 kg
RP250 4.8 kg
+
+
+–
Calculate the additional charge amount based on the following procedure.
If the calculation results in an amount that is smaller than the "Additional charge amount for 70m," perform the additional charge using the amount shown
in "Additional charge amount for 70m."
5-1. ADJUSTING THE AMOUNT OF REFRIGERANT
5-2. COMPRESSOR TECHNICAL DATA
DWÛ&
Unit
Compressor model
PUHZ-RP200, 250YHA2
ANB52FFJMT
U-V
0.30
Winding
Resistance
U-W
0.30
( )
W-V
0.30
5-3. NOISE CRITERION CURVES
MICROPHONE
1.5m
1m
UNIT
GROUND
PUHZ-RP200YHA2
PUHZ-RP250YHA2
90
80
70
60
50
40
COOLING
HEATING
58
59
SPL(dB)
MODE
LINE
NC-70
NC-60
NC-50
NC-40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
< Connected for Option (Contact Input)>
Connector<Connection for Option>
Connector<Connection for Option>
Relay
Switch<Status of communication>
Switch<Address setting:1st digit>
Switch<Address setting:2nd digit>
LED<Power Supply:DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission:Sending>
LED<Transmission:Receiving>
LED<Power Supply:DC12V>
NAME
POWER
SUPPLY
3N~
400V 50Hz
NO FUSE
BREAKER
TB1
L1
L2
L3
N
RED
WHT
BLK
BLU
GRN/YLW
2
N. F.
CNAC1
(WHT)
31
LI 1
LI 2
UU
LI 3
U
NI
U
U
GD2GD1
BLK
CNDC
(PNK)
BLK
CNCT
(RED)
31
2
WHT
CNAC2
(RED)
3112
LO 1
RED
LO 2
WHT
LO3
BLK
+
1 MODEL SELECT
MODEL
200Y
U
13
CNL
(BLU)
WHT
ACL4
250Y
+
2. SW5 -1 to 5 : Function Switch
SW6
ON
OFF
12345678
ON
OFF
12345678
ON
OFF
ON
OFF
SW5-6+2
123456
123456
13
8WIRING SPECIFICATIONS
8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
P200, P250
Outdoor unit modelRP200, 250
Outdoor unit
Power supply
Outdoor unit input capacity *1
Main switch (Breaker)
Wiring
Wire No. %
size(mm
Outdoor unit power supply5 % Min. 4
Indoor unit-Outdoor unit *2Cable length 50 m : 3 % 4 (Polar)/Cable length 80 m : 3 % 6 (Polar)
Indoor unit-Outdoor unit earth1 % Min. 2.5
2
)
Remote controller-Indoor unit *32 % 0.69 (Non-polar)
Outdoor unit L1-N, L2-N, L3-NAC 220 - 230 - 240 V
Circuit rating
Indoor unit-Outdoor unit S1-S2 *4AC 220 - 230 - 240 V
Indoor unit-Outdoor unit S2-S3 *4DC 24 V
Remote controller-Indoor unit *4DC 14 V
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
*2. Max. 80 m Total Max. including all indoor/indoor connection is 80 m.
• Use one cable for S1 and S2 and another for S3 as shown in the picture.
• Max. 50m Total Max. for PEA-200, 250, 400, 500
Wiring size 3%1.5(Polar)
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord.
(Design 60245 IEC 57)
3. Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.
Phase
Frequency & Voltage
380/400/415V 50Hz
3 phase(4 wires)
3N~(3ph 4-wires), 50 Hz,
380 - 400 - 415 V
32 A
Isolator
A-Control
Outdoor Unit
S1
S2
S3
3 poles isolator
S1
S2
S3
A-Control
Indoor Unit
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation
between power line and communication signal line. Therefore, please turn off the main power supply when servicing.
And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use
3-pole type.
Synchronized twin and triple system Electrical wiring
• Synchronized twin• Synchronized triple
Outdoor
Unit
power
supply
Earth leakage breaker
Wiring circuit breaker or
isolating switch
Outdoor
unit
unit
L1
L2
3
L
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
Remote
controller
2
Indoor
unit
1
2
S1
S2
S3
Unit
power
supply
Earth leakage breaker
Wiring circuit breaker or
isolating switch
Outdoor
unit
L1
L2
L
3
N
Indoor/outdoor
connection cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
2
Remote
controller
Indoor
unit
1
2
S1
S2
S3
Indoor
unit
1
2
S1
S2
S3
14
S1
S2
S3
Indoor/outdoor
unit connection
cable
Indoor
unit
Unit
power
supply
Unit
power
supply
Outdoor
unit No.1
L1
L2
L3
N
S1
S2
S3
L1
L2
L3
N
Earth leakage breaker
Wiring circuit breaker or
isolating switch
S1
S2
S3
Indoor/outdoor
unit connection
cable
TB4-1
TB4-2
Unit
power
supply
Outdoor
unit No.2
L
1
L2
L3
N
S1
S2
S3
1
2
Remote
controller
1:1 System (Indoor : PEA-200, 250)1:2 System (Indoor : PEA-400, 500)
Indoor
unit
L1
L2
L3
N
S1
S2
S3
1
Remote
controller
2
supply
Unit
power
Unit
power
supply
Earth leakage breaker
Wiring circuit breaker or
isolating switch
Outdoor
unit
1
L
L2
L3
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
8-2. SEPARATE INDOOR UNIT/ OUTDOOR UNIT POWER SUPPLIES
Simultaneous twin/triple/four system
<For models without heater>
The optional indoor power supply terminal kit is required.
*
L
1
L
2
L
3
N
S1
S2
S3
L
L
N
S1
S2
S3
1
2
L
N
N
S1
S1
S2
S2
S3
S3
1
1
2
2
L
N
S1
S2
S3
1
2
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table below.
If the optional indoor power supply terminal kit is used, change the indoor unit electrical
box wiring referring to the figure in the right and the DIP switch settings of the
outdoor unit control board.
Indoor unit specifications
Indoor power supply terminal kit (option)
Indoor unit electrical box connector connection change
Label affixed near each wiring diagram
for the indoor and outdoor units
Outdoor unit DIP switch settings (when
using separate indoor unit/outdoor unit
power supplies only)
ON
OFF
Required
Required
Required
3
12(SW8)
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Indoor unit power supplied from outdoor unit
(when shipped from factory)
Connectors (connections when shipped
from the factory are for indoor unit power
supplied from outdoor unit.)
BLUE
BLUE
YELLOW
YELLOW
CND
Set the SW8-3 to ON.
* There are 3 types of labels (Labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model
Indoor unit power supply
Indoor unit input capacity
Main switch (Breaker)
Indoor unit power supply
Indoor unit power supply earth
)
2
Indoor unit-Outdoor unit
(mm
Wiring
Indoor unit-Outdoor unit earth
Wire No. % size
Remote controller-Indoor unit
Indoor unit L-N*4
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
rating
Circuit
Remote controller-Indoor unit
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductor of the supply.
*2. Max. 120 m
*3. The 10 m wire is attached in the remote controller accessory. Max. 500 m
*4. The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and indoor unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed
flexible cable. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
*1
*2
*3
*4
*4
*4
15
RP35~140
~/N (single), 50 Hz, 230 V
16 A
2 % Min. 1.5
1 % Min. 1.5
2 % Min. 0.3
–
2 % 0.3 (Non-polar)
AC 230 V
–
DC24 V
DC12 V
control board
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cales
Remote controller
Indoor unit
Option
Indoor unit power supply
ORANGE
CND
Indoor unit
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Separate indoor unit/outdoor unit power
supplies
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.
BLUE
YELLOW
Connectors
CND
Indoor unit
control board
ORANGE
CND
YELLOW
BLUE
8-3. INDOOR – OUTDOOR CONNECTING CABLE
WIRING SPECIFICATIONS FOR 220-240 V 50 Hz
(INDOOR-OUTDOOR CONNECTING CABLE)
Cross section of cableWire size (mm2)Number of wiresPolarityL (m)*6
Round
Flat
Flat
Round
2.53
2.53
1.54
2.54
Clockwise : S1-S2-S3
* Pay attention to stripe of yellow and green.
Not applicable
(Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Clockwise : S1-S2-S3-Open
*Connect S1 and S3 to the opposite angle.
Not applicable
(30)
*2
*5
(18)
*3
(30)
*4
*1 : Power supply cords of appliances shall not be lighter than design 60245 IEC or
227 IEC.
*2 : In case that cable with stripe of yellow and green is available.
*3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm.
*4 : In case of regular polarity connection (S1-S2-S3).
*5 : In the flat cables are connected as this picture, they can be used up to 30 m.
2
Indoor/Outdoor separate
power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
*6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity
or materials, etc.
Wire No. % Size ($)
Max. 120m
2 % Min. 0.3
—
(3C Flat cable 2)
+ The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient
insulation to ground or a poor electrical contact at the intermediate connection point.
16
8-4. M-NET WIRING METHOD
(Points to notice)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET P.C. board may burn out.
(3) Use 2-core x 1.25mm
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
2
shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
Group
remote
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 00
M-NET
address 03
A-control
remote
controller
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the central-control remote controller.
Bad example (Multi spot grounding of shield wire)
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
Good example 1 (Single spot grounding of shield wire)
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
Good example 2 (Single spot grounding of shield wire)
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
If there are more than 2 grounding spots on the shield wire, noise may enter into the shield wire because the ground wire
and shield wire form 1 circuit and the electric potential difference occurs due to the impedance difference among grounding
spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and shield wire
do not form 1 circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
17
ƔM-NET wiring
2
5
2
13
SW11
ones
digit
SW12
tens
digit
3
4
3
4
5
6
5
6
M-NET
terminal
block
M1 M2 S
Transmission
12
3
4
2
5
1
6
0
7
9
8
3
4
2
5
1
6
0
7
9
8
ON
OFF
1
3
4
5
2
6
6
ON
OFF
1
3
4
5
2
6
14
OFF
OFF
ON
ON
wire
3
2
1
0
9
8
3
2
1
0
9
8
1
1
Ground
wire
Shield
part
50
4
5
6
7
~
4
5
6
7
3
4
5
2
7
3
4
5
2
15
3
4
2
5
1
6
0
7
9
8
3
4
2
5
1
6
0
7
9
8
6
6
2
(1) Use 2-core x 1.25mm
shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block. Connect one core of the
transmission wire (non-polar) to M1 terminal and the other to M2. Peel the
shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(M1, M2, S) on M-NET terminal block should be individually wired to the other
outdoor unit’s terminal, i.e. M1 to M1, M2 to M2 and S to S. In this case, choose one of those outdoor units and drive a
screw to fix an ground wire on the plate as shown on the right figure.
8-4-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
<Setting example>
M-NET Address No.
(SW11 for ones digit and SW12 for tens digit), which
is located on the M-NET board of outdoor unit.
(Initial setting: all addresses are set to “0”.)
Switng
setting
8-4-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group setting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Initial setting: all
switches are OFF. (All refrigerant addresses are “00”.)]
Refrigerant
address
ON
OFF
1
ON
OFF
1
ON
OFF
1
3
4
5
2
6
0
ON
OFF
1
3
4
5
2
6
8
ON
OFF
1
3
4
5
2
6
1
ON
OFF
1
3
4
5
2
6
9
ON
OFF
1
3
4
5
2
6
2
ON
OFF
1
3
4
5
2
6
10
ON
OFF
1
3
4
5
2
6
3
ON
OFF
1
3
4
5
2
6
11
ON
OFF
1
3
4
5
2
6
4
ON
OFF
1
3
4
5
2
6
12
8-4-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above section. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
Group AGroup BGroup C
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
+ Refrigerant addresses can be overlapped if they are in the different group.
Group AGroup B
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
A-control
remote
controller
Refrigerant
address 01
M-NET
address 02
Refrigerant
address 01
M-NET
address 03
TB5
TB5
A-control
remote
controller
Refrigerant
address 00
M-NET
address 04
Refrigerant
address 00
M-NET
address 04
A-control
remote
controller
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 02
M-NET
address 05
+ In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the
group for the outdoor unit whose refrigerant address is “00”.
18
9REFRIGERANT SYSTEM DIAGRAM
Unit : mm
PUHZ-RP200YHA2
Ball valve
Refrigerant GAS pipe
:25.4(:1 inch)
Refrigerant LIQUID pipe
:9.52(:3/8 inch)
Strainer
(#50)
Service
port
(check)
Accumulator
Stop valve
(with service port)
Strainer
(#40)
4-way valve
Strainer
(#100)
Restrictor
valve
Strainer
(#100)
Muffler
Compressor
Linear expansion
valve
Outdoor heat exchanger
High pressure
switch(63H)
Service
port
(check)
Thermistor
(TH4)
Refrigerant flow in cooling
Refrigerant flow in heating
Distributor
Strainer
(#100)
Thermistor
(TH7)
Thermistor
(TH6)
Thermistor
(TH3)
PUHZ-RP250YHA2
Ball valve
Refrigerant GAS pipe
:25.4(:1 inch)
Stop valve
(with service port)
Refrigerant LIQUID pipe
:12.7(:1/2 inch)
High pressure
switch(63H2)
Strainer
(#50)
Service
port
(check)
Strainer
(#100)
Linear
expansion valve B
Strainer
(#100)
Power
receiver
Restrictor
valve
Capillary tube
O.D.4.0I.D.3.0L500
4-way valve
Low pressure
switch(63L)
Linear expansion valve A
Muffler
Compressor
Replace
filter
High pressure
switch (63H1)
Service
port
(check)
Bypass valve
Heat exchanger
Thermistor (TH4)
(Discharge)
Strainer
(#100)
Thermistor (TH7)
Thermistor (TH6)
Thermistor (TH3)
Distributor
Replace filter
19
Bypass valve
OFF
12
ON
<SW4>
Stop Operation
Cooling Heating
9-1. Refrigerant recovering (pump down)
Perform the following procedures to recover the refrigerant when moving the indoor unit or the outdoor unit.
Turn on the power supply (circuit breaker).
+When power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If
“CENTRALLY CONTROLLED” is displayed, the refrigerant recovering (pump down) cannot be completed normally.
After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor
(outdoor unit) and fans (indoor and outdoor units) start operating and refrigerant recovering operation begins. LED1 and
LED2 on the control board of the outdoor unit are lit.
+Set the SWP switch (push-button type) to ON in order to perform refrigerant recovering operation only when the unit is
stopped. However, refrigerant recovering operation cannot be performed until compressor stops even if the unit is stopped.
Wait 3 minutes until compressor stops and set the SWP switch to ON again.
Because the unit automatically stops in about 2 to 3 minutes after the refrigerant recovering operation (LED1 is not lit
and LED2 is lit), be sure to quickly close the gas stop valve.
+In case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then
repeat step
3 minutes later.
+If the refrigerant recovering operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain
stopped until the power supply is turned off.
Turn off the power supply (circuit breaker.)
9-2. Unit replacement operation
When reusing the existing pipes that carried R22 refrigerant for the RP200 and RP250 models, replacement operation
must be performed before performing a test run.
If new pipes are used, these procedures are not necessary.
During replacement operation, “C5” is displayed on “A-Control Service Tool(PAC-SK52ST)”.
Replacement operation procedures
Turn on the power supply.
Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start replacement operation.
• The replacement operation is performed using the cooling system. Cool air will flow from the indoor unit during the replace-
ment operation.
TEST RUN
• During the replacement operation,
control board of the outdoor unit blink together.
The duration of the replacement operation is determined by the length of the piping. Always perform the replacement
operation for longer than the stipulated time.
* Use one of he following methods to complete replacement operation. When the replacement operation ends, the unit will
automatically stop.
(1)Set SW8-2 from ON to OFF. (When ending a replacement operation of
less than 2 hours.)
• Each time SW8-2 is set from OFF to ON, the replacement operation can
be started. Always perform the replacement operation for longer than the
stipulated time.
(2) The replacement operation will automatically stop after 2 hours. (It will end with SW8-2 still in the ON position.)
• When the replacement operation has ended automatically after 2 hours of operation, there is no need to set SW8-2 from
ON to OFF; normal air conditioning operations can be started with the SW8-2 being set to ON. However, to repeat the
replacement operation, SW8-2 will have to be returned to OFF and then set to ON.
is displayed on the remote controller and LED1 (green) and LED2 (red) on the
<Required replacement operation times>
Piping Length
0 to 20 meters 30 minutes or more
21 to 30 meters 45 minutes or more
31 to 70 meters 60 minutes or more
"Replacement
Operation Time"
9-3. Start and finish of test run
• Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
Set the operation mode (cooling/heating) using SW4-2.
Turn on SW4-1 to start test run with the operation mode set by SW4-2.
Turn off SW4-1 to finish the test run.
• There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion valve is just moving to adjust opening pulse.
• There may be a knocking sound around the machine room for several seconds after compressor
starts operating, but this is no problem with product because the check valve, itself, generates the
sound since pressure difference is small in the refrigerant circuit.
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
20
10TROUBLESHOOTING
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.
Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the
table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action according
to “10-4. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the
trouble according to “10-5. Troubleshooting by inferior
phenomena”.
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring and etc.
Reset error code logs and restart the unit after finishing
service.
There is no abnormality in electrical component,
controller board, remote controller and etc.
Re-check the abnormal symptom.
Conduct trouble shooting and ascertain the cause of the
trouble
phenomena”.
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
according to “10-5. Troubleshooting
by inferior
10-2. CHECK POINT UNDER TEST RUN
(1) Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Megger and
check that it is 1.0M or over.
+Don’t use 500V Megger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Turn on power supply 12 hours before test run in order to protect compressor.
• For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “11. Function setting”.
• Make sure to read operation manual before test run. (Especially items to secure safety.)
21
"TEST RUN" and the currently selected
operation mode are displayed altemately.
Displays the remaining
test run time.
[TEST] button
Pipe (liquid) temperature
Operating procedures
1. Turn on the main power supply.
2. Press TEST button twice.
3. Press OPERATION SWITCH
button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for
correct running.
6. Press the ON/OFF button to reset the test run in progress.
7. Register the contact number.
While the room temperature display on the remote
controller is “PLEASE WAIT”, the remote controller is disabled.
Wait until “PLEASE WAIT” disappears before using remote controller.
“PLEASE WAIT” appears for about 2 minutes after power
supply is turned on. +1
The TEST RUN appears on the screen.
Cooling mode:
Heating mode: Check if warm air blows. (It takes a little
while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to
provide optimum fan speeds. Therefore, the fan keeps
running at a low speed to meet the current outside air
condition unless it exceeds its available maximum power.
Then, in actuality, the fan may stop or run in the reverse
direction depending on the outside air, but this does not
mean malfunction.
Check if cool air blows and water is drained.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after 2 hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin, triple and quadruple operation. Malfunctions
may not be displayed regardless of incorrect wiring.
+1 After turning on the power supply, the system will go into startup mode, “PLEASE WAIT” will blink on the display section
of the room temperature, and lamp(green) of the remote controller will blink.
As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case the
address is not 0. LED3 will blink.
As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will be lit up. (After the startup mode of the system finishes,
LED2(red) will be turned off.)
In case OUTDOOR BOARD LED is digital display, — and — will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from
the symptoms.
The below symptoms are under test run mode. “startup” in the table means the display status of +1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “PLEASE
WAIT”, and
After power is turned on, “PLEASE WAIT”
is displayed for 3 minutes, then error code
is displayed.
No display appears even when remote
controller operation switch is turned on.
(Operation lamp does not light up.)
Display appears but soon disappears
even when remote controller is operated.
+Press the remote controller’s
LCD
P1
P2
P4
P5
P6
P8
P9
Fb
cannot be operated.
CHECK
Contents of trouble
Abnormality of room temperature thermistor
Abnormality of pipe temperature thermistor/Liquid
Abnormality of drain sensor/ Float switch connector open
Drain overflow protection is working.
Freezing/overheating protection is working.
Abnormality of pipe temperature
Abnormality of pipe temperature thermistor/Cond./Eva
Abnormality of indoor controller board
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed,
green(once) and red(once) blink
alternately. <F1>
After “startup” is displayed,
green(once) and red(twice) blink
alternately. <F3, F5, F9>
After “startup” is displayed,
green(twice) and red(once) blink
alternately. <EA. Eb>
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed, only
green lights up. <00>
• After power is turned on, “PLEASE WAIT” is displayed for 2
minutes during
• Outdoor unit’s protection device connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity
is wrong for S1, S2, S3.)
• Remote controller transmission wire is short.
• There is no outdoor unit of address 0.
(Address is other than 0.)
• Remote controller transmission wire is open.
• After canceling function selection, operation is not possible for
about 30 seconds. (Normal)
system startup. (Normal)
button twice to perform self-diagnosis. See the table below for the contents of LCD dis-
LCD
Malfunction outdoor unit
U1~UP
Malfunction
F3~F9
E0~E5
Remote controller transmitting error
E6~EF
Indoor/outdoor unit communication error
No error history
---No applied unit
FFFF
Forced compressor stop(due to water leakage abnormality)
PA
outdoor unit
Contents of trouble
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
(microcomputer power supply)
LED1
(remote controller)
LED2
(indoor/outdoor communication)
LED3
Lits when power is supplied.
Lits when power is supplied for wired remote controller.
The indoor unit should be connected to the outdoor unit with address “0” setting.
Blinks when indoor and outdoor unit are communicating.
Cause
1, L2, L3 and
22
TEST RUN
TEST RUN
MODE
MODE
HEAT
FAN
VANE
,
ON/OFF
MODE
CHECK
TEST RUN
SET
TEST RUN
FAN
VANE
LOUVER
RESET
CLOCK
TEMP
AUTO STOP
AUTO START
h
min
Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M.
Turn on the main power to the unit.
Press the
(Start this operation from the status of remote controller display
turned off.)
and current operation mode are displayed.
A
Press the
check whether cool air is blown out from the unit.
Press the
check whether warm air is blown out from the unit.
Press the
from the unit.
Press the
properly.
Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps to .
• It is not possible to run in FAN, DRY or AUTO mode.
button twice continuously.
( ) button to activate
( ) button to activate
COOL
mode, then
mode, then
button and check whether strong air is blown out
button and check whether the auto vane operates
23
10-3. HOW TO PROCEED "SELF-DIAGNOSIS"
10-3-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop,
and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the temperature
display, and the error code and unit number are displayed alternately as
shown below.
(If the outdoor unit is malfunctioning, the unit number will be "00".)
In the case of group control, for which one remote controller controls
multiple refrigerant systems, the refrigerant address and error code of the
unit that first experienced trouble (i.e., the unit that transmitted the error
code) will be displayed.
To clear the error code, press the button.
Error code (2 or 4 digits)
ON/OFF
(Alternating Display)
Address (3 digits) or unit number (2 digits)
When using remote-/local-controller combined operation, cancel the error code after turning off remote operation. During
central control by a MELANS controller, cancel the error code by pressing the
ON/OFF
button.
10-3-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote
controller or power is turned off.
Check the error code history for each unit using the remote controller.
Switch to self-diagnosis mode.
Press the
will change as shown below.
CHECK
button twice within 3 seconds. The display content
Unit number or refrigerant address
to be diagnosed
Set the unit number or refrigerant address you want to diagnose.
Press the [TEMP] buttons ( and ) to select the desired number
or address. The number (address) changes between [01] and [50] o r [00]
an d
[15].
The refrigerant address will begin to blink
approximately 3 seconds after being
selected and the self-diagnosis process will begin.
Display self-diagnosis results.
<When there is error code history>
(Alternating Display)
Error code (2 or 4 digits)
<When there is no error code history><When there is no corresponding unit>
Address (3 digits) or unit number (2 digits)
Reset the error history.
Display the error history in the diagnosis result display screen (see step
).
24
CHECK
Press the
address or refrigerant address will blink.
Cancel self-diagnosis.
Self-diagnosis can be cancelled by the following 2 methods.
Press the
Press the
ON/OFF
CHECK
ON/OFF
button twice within 3 seconds. The self-diagnosis
button twice within 3 seconds. Self-diagnosis will be cancelled and the screen will return to the previous state in effect before the
button. Self-diagnosis will be cancelled and the indoor unit will stop.
start of self-diagnosis.
When the error history is reset, the display will look like the one shown below.
However, if you fail to reset the error history, the error content will be displayed
again.
10-3-3. Remote Controller Diagnosis
If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.
First, check that the power-on indicator is lit.
If the correct voltage (DC12 V) is not supplied to the remote controller, the
indicator will not light.
If this occurs, check the remote controller's wiring and the indoor unit.
Power on indicator
Switch to the remote controller self-diagnosis mode.
Press the
will change as shown below.
CHECK
button for 5 seconds or more. The display content
Press the
FILTER
button to start self-diagnosis.
Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
Check for other possible causes, as there is no problem with the remote
controller.
[Where the remote controller is not defective, but cannot be operated.]
(Error display 2) [E3], [6833] or [6832] blinks.
There might be noise or interference on the transmission path, or the indoor
unit or other remote controllers are defective. Check the transmission path
and other controllers.
The remote controller must be replaced with a new one.
(Error display 3)
The number of data errors is the difference between the number of bits sent
from the remote controller and the number actually transmitted through the
transmission path. If such a problem is occurring, the transmitted data is
affected by noise, etc. Check the transmission path.
Press the
approximately 30 seconds, the state in effect before the diagnosis will be restored.
button for 5 seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will blink. After
25
10-3-4. Malfunction-diagnosis method by wireless remote controller
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
CHECK
display
ON/OFF
button
CHECK
button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VANE
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
h
min
Refrigerant
address
display
Temperature
button
HOUR
button
1. Press the CHECK button twice.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit tent buzzer sound, the operation lamp
blinks, and the error code is output.
(It takes 3 seconds at most for error
code to appear.)
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• The check mode is cancelled.
26
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp blink
pattern
Beep
Self-check
starts
(Start signal
received)
Beep Beep BeepBeepBeep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
rd
0.5 sec.
th
n
On
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
[Output pattern B]
Beeper sounds
OPERATION
INDICATOR
lamp blink
pattern
BeepBeep Beep BeepBeep
1st2nd3
Off
Self-check
starts
(Start signal
received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
PAForced compressor stop(due to water leakage abnormality)
6P6Freezing/Overheating protection operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
11
–
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
Remote controller transmission error
–E1, E2Remote controller control board error
nd
1st2
Off
Number of blinks/beeps in pattern indicates
the check code in the following table
rd
th
n
On
0.5 sec.
· · · Repeated
Beep Beep
nd
1st2
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
· · · Repeated
SymptomRemark
As for indoor
unit, refer to
indoor unit's
service manual.
[Output pattern B]
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinksCheck code
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
SymptomRemark
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
E9
UP
U3,U4
UF
U2
U1,Ud
U5
U8
U6
U7
U9,UH
–
–
Others
*1 If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating
protection operation
Abnormal temperature of heatsink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormality of power module
Abnormality of superheat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
For details, check
the LED display
of the outdoor
controller board.
*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
27
10-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
Error Code
Abnormal point and detection method
No voltage is supplied to terminal
block(TB1) of outdoor unit.
a) Power supply breaker is
b) Contact failure or disconnec-
c) Open phase (L2 or N phase)
(Note 1) Refer to indoor unit section for code P and code E.
Case
Check following items.
a) Power supply breaker
b), c) Connection of power supply terminal
turned off.
tion of power supply
terminal
Judgment and action
block(TB1)
None—
63L connector open
Abnormal if 63L connector circuit is open
for 3 minutes continuously after power supply.
F3
(5202)
63L: Low-pressure switch
<RP250 only>
Electric power is not supplied to
outdoor controller circuit board.
a) Disconnection of connector
(CNDC)
Disconnection of reactor
(ACL4)
Disconnection of outdoor noise
filter circuit board or parts failure in outdoor noise filter circuit
board
Defective outdoor controller
circuit board
Disconnection or contact failure
of 63L connector on outdoor
controller circuit board.
Disconnection or contact failure
of 63L.
63L is working due to refriger-
ant leakage or defective parts.
Defective outdoor controller
circuit board.
Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector CNDC on
the outdoor noise filter circuit board.
Refer to 10-9.
Check connection of reactor. (ACL4)
a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 10-9.
Replace controller board (When items above
are checked but the units cannot be repaired).
Check connection of 63L connector on
outdoor controller circuit board.
Refer to 10-9.
Check the 63L side of connecting wire.
Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace the parts if the parts are defective.
Replace outdoor controller circuit board.
F5
(5201)
F9
(4119)
63H connector open
Abnormal if 63H connector circuit is open
for 3 minutes continuously after power supply.
63H: High-pressure switch
2 connector open
Abnormal if both 63H and 63L connector
circuits are open for 3 minutes continuously
after power supply.
of 63H connector on outdoor
controller circuit board
Disconnection or contact failure
of 63H
63H is working due to defective
parts.
Defective outdoor controller
circuit board
Disconnection or contact failure
of connector (63H,63L) on
outdoor controller circuit board.
Disconnection or contact failure
of 63H, 63L.
63H and 63L are working due
to defective parts.
Defective outdoor controller
circuit board.
Check connection of 63H connector on
outdoor controller circuit board.
Refer to 10-9.
Check the 63H side of connecting wire.
Check continuity by tester.
Replace the parts if the parts are defective.
Replace outdoor controller circuit board.
Check connection of connector(63H,63L) on
outdoor controller circuit board.
Refer to 10-9.
Check the 63H and 63L side of connecting
wire.
Check continuity by tester.
Replace the parts if the parts are defective.
Replace outdoor controller circuit board.
28
Error Code
EA
(6844)
Eb
(6845)
Abnormal point and detection method
Indoor/outdoor unit connector
miswiring, excessive number of units
1. Outdoor controller circuit board can
automatically check the number of
connected indoor units. Abnormal if the
number cannot be checked automatically due to miswiring of indoor/outdoor
unit connecting wire and etc. after power
is turned on for 4 minutes.
2. Abnormal if outdoor controller circuit
board recognizes excessive number of
indoor units.
Miswiring of indoor/outdoor unit
connecting wire (converse wiring or disconnection)
Outdoor controller circuit board can
automatically set the unit number of indoor
units.
Abnormal if the indoor unit number cannot be set within 4 minutes after power on
because of miswiring (converse wiring or
disconnection) of indoor/outdoor unit connecting wire.
Case
Contact failure or miswiring of
indoor/outdoor unit connecting
wire
Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
Excessive number of indoor
units are connected to 1 outdoor unit.(5 units or more)
Defective transmitting receiving
circuit of outdoor controller
circuit board
Defective transmitting receiving
circuit of indoor controller board
Defective indoor power board
2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
Noise has entered into power
supply or indoor / outdoor unit
connecting wire.
Contact failure or miswiring of
indoor/outdoor unit connecting
wire
Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
Defective transmitting receiving
circuit of outdoor controller circuit
board
Defective transmitting receiving
circuit of indoor controller board
Defective indoor power board
2 or more outdoor units have
refrigerant address “0”.
(In case of group control)
Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
Judgment and action
Check disconnection or looseness or polar-
ity of indoor/outdoor unit connecting wire of
indoor and outdoor units.
Check diameter and length of indoor/outdoor
unit connecting wire.
Total wiring length: 80m
(Including wiring connecting each indoor unit
and between indoor and outdoor unit)
Also check if the connection order of flat
cable is S1, S2, S3.
Check the number of indoor units that are
connected to one outdoor unit. (If EA is
detected.)
~ Turn the power off once, and on again to
check.
Replace outdoor controller circuit board,
indoor controller board or indoor power
board if abnormality occurs again.
Check if refrigerant addresses (SW1-3 to
SW1-6 on outdoor controller circuit board)
are overlapping in case of group control
system.
Check transmission path, and remove the
cause.
+ The descriptions above, -, are for EA, Eb
and EC.
EC
(6846)
Start-up time over
The unit cannot finish start-up process
within 4 minutes after power on.
Contact failure of indoor/
outdoor unit connecting wire
Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
29
<Abnormalities detected while unit is operating>
Error Code
U1
(1302)
Abnormal point and detection method
High pressure (High-pressure switch
63H(RP200)/63H1 or 63H2(RP250)
worked)
Abnormal if high-pressure switch
63H(RP200)/63H1 or 63H2(RP250) worked
( + ) during compressor operation.
+ 63H1: 4.15 MPa
63H, 63H2: 3.6 MPa
63H, 63H1, 63H2: High-pressure switch
Case
Short cycle of indoor unit
Clogged filter of indoor unit
Decreased airflow caused by
dirt of indoor fan
Dirt of indoor heat exchanger
Locked indoor fan motor
Malfunction of indoor fan motor
Defective operation of stop
valve (Not fully open)
Clogged or broken pipe
Locked outdoor fan motor
Malfunction of outdoor fan
motor
Short cycle of outdoor unit
Dirt of outdoor heat exchanger
Decreased airflow caused by
defective inspection of outside
temperature thermistor
(It detects lower temperature
than actual temperature.)
Disconnection or contact failure
of connector (63H) on outdoor
controller board
Disconnection or contact failure
of 63H connection
Defective outdoor controller
board
Defective action of linear
expansion valve
Malfunction of fan driving
circuit
Judgment and action
~Check indoor unit and repair defect.
Check if stop valve is fully open.
Check piping and repair defect.
~ Check outdoor unit and repair defect.
Check the inspected temperature of outside
temperature thermistor on LED display.
(SW2 on A-Control Service Tool : Refer to
10-10.)
~Turn the power off and check F5 is
displayed when the power is turned again.
When F5 is displayed, refer to “Judgment
and action” for F5.
Check linear expansion valve.
Refer to 10-7.
Replace outdoor controller board.
U2
(1102)
U3
(5104)
High discharging temperature
(1) Abnormal if discharge temperature ther-
mistor (TH4) exceeds 125or 110
continuously for 5 minutes.
Abnormal if condenser/evaporator tem
perature thermistor (TH5) exceeds 40
during defrosting and discharge temperature thermistor (TH4) exceeds 110
Open/short circuit of discharge
temperature thermistor (TH4)
Abnormal if open (3 or less) or short
(217 or more) is detected during
compressor operation.
(Detection is inoperative for 10 minutes
of compressor starting process and for 10
minutes after and during defrosting.)