• Outdoor controller board (C.B.) has been changed. (S/W version up)
1. DRAIN HOSE HEATER (option: PAC-SE60RA-E) is connectable.
2. The starting temperature of FLASH INJECTION is settable.
PUHZ-HRP 71VHA
PUHZ-HRP100VHA
• Pressure sensor (63HS) has been added.
• Compressor (MC) has been changed.
ANB33FJCMT
• Thermistor (Discharge / TH4) has been changed.
• Fan motors (MF1,2) have been changed.
• Fan grilles have been changed.
• Electrical parts have been changed.
Controller circuit board (C.B.), Power circuit board (P.B.),
Noise fi lter circuit board (N.F.) and Active fi lter module (ACTM) (including P.B.)
Before obtaining access to terminal, all supply circuits must be disconnected.
Preparation before the repair service.
• Prepare the proper tools.
• Prepare the proper protectors.
• Provide adequate ventilation.
• After stopping the operation of the air conditioner, turn off the power-supply breaker.
• Discharge the condenser before the work involving the electric parts.
Precautions during the repair service.
• Do not perform the work involving the electric parts with wet hands.
• Do not pour water into the electric parts.
• Do not touch the refrigerant.
• Do not touch the hot or cold areas in the refrigerating cycle.
• When the repair or the inspection of the circuit needs to be done without turning off the power,
exercise great caution not to touch the live parts.
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the followings.
· Be sure to perform replacement operation before test run.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used indoors during
installation, and both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Gauge manifold
Charge hose
Gas leak detector
Torque wrench
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition change
may occur in refrigerant and the efficiency will be lowered.
3
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.
Gauge manifold
1
Charge hose
2
Electronic scale
3
Gas leak detector· Use the detector for R134a, R407C or R410A.
4
Adaptor for reverse flow check· Attach on vacuum pump.
5
Refrigerant charge base
6
Refrigerant cylinder
7
Refrigerant recovery equipment
8
Tool name
Specifications
· Only for R410A
· Use the existing fitting
· Use high-tension side pressure of 5.3 MPa·G or over.
· Only for R410A
· Use pressure performance of 5.09 MPa·G or over.
· Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
specifications
—
—
—
. (UNF1/2)
[4] Refrigerant leakage detection function
This air conditioner can detect refrigerant leakage which may happen during a long period of use. In order to enable the
leakage detection, settings are required to let the unit memorize the initial conditions (initial learning).
Refer to 14-3. INITIAL SETTINGS FOR REFRIGERANT LEAKAGE DETECTION FUNCTION.
4
3-3. PRECAUTIONS WHEN REUSING EXISTING R22 REFRIGERANT PIPES
(1) Flowchart
Measure the existing pipe thickness and check for damage.
The existing pipe thickness meets specifications and the pipes are not damaged.
Check if existing air conditioner can operate.
Existing air conditioner can
operate.
Perform cooling operation
for about 30 minutes and
then do a pump down work.
Disconnect existing air conditioner from piping.
Existing pipes can be reused.
Existing air conditioner
cannot operate.
Use a refrigerant recovery
equipment to recover the
refrigerant.
In case existing pipes were used
+
for gas or oil heat pump system,
be sure to clean the pipes.
The existing pipe thickness does not meet
specifications or the pipes are damaged.
Existing pipes cannot be
reused. Use new pipes.
In case the unit is HRP·HA2R1
Connect a new air conditioner.
In case the unit is HRP·HA(2)
Connect a new air conditioner.
Perform replacement operation.
·When performing replacement operation, make sure that DIP SW8-2 on outdoor unit controller board is
set to ON.
+Chemical compounds containing chlorine left in existing pipes are collected by replace filter.
●The air conditioner automatically performs cooling operation through replace filter for about 2 hours.
Connecting a new air conditioner
Flaring work should be done so that flare meets the dimension for R410A.
Use flare nut provided with indoor and outdoor unit.
When using gas piping of :19.05mm for HRP100, 125.
Make sure that DIP SW8-1 on outdoor unit controller board is set to ON.
This is to keep the pressure on pipes within permissible range.
● Use different diameter joint or adjust the piping size by brazing.
When using pipes larger than specified size for HRP71.
Make sure that DIP SW8-1 on outdoor unit controller board is set to ON.
This is to prevent oil flow ratio from lowering due to the decrease in flowing refrigerant.
● Use different diameter joint or adjust the piping size by brazing.
When existing pipes are specified size.
The pipes can be reused referring to TECHNICAL DATA BOOK (OCS11).
● Use different diameter joint or adjust the piping size by brazing.
* When using existing pipes for HRP71, 100, 125HA(2).
Make sure that DIP SW8-2 on outdoor unit controller board is set to ON and perform
replacement operation.
+ Chemical compounds containing chlorine left in existing pipes are collected by replace filter.
● The air conditioner automatically performs cooling operation through replace filter for about 2 hours.
HRP·HA(2)HRP·HA2R1
5
(2) Cautions for refrigerant piping work
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working
pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
1 Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7 mm or below.)
Diagram below: Piping diameter and thickness
Nominal
dimensions(inch)
1/4
3/8
1/2
5/8
3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
(mm)
Thickness
R410AR22
0.8
0.8
0.8
1.0
—
(mm)
0.8
0.8
0.8
1.0
1.0
2 Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrigerants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been
specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A
also has partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe
flaring dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes.
Use torque wrench corresponding to each dimension.
Dimension A
Dimension B
Flare cutting dimensions
Nominal
dimensions(inch)
1/4
3/8
1/2
5/8
3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
+0
Dimension A
R410AR22
9.1
13.2
16.6
19.7
—
( )
-0.4
9.0
13.0
16.2
19.4
23.3
Flare nut dimensions
(mm)
dimensions(inch)
Nominal
1/4
3/8
1/2
5/8
3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
Dimension B
R410A
17.0
22.0
26.0
29.0
+
-
3 Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materialsUseR410A toolsCan R22 tools be used?
Gauge manifold
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
Air purge, refrigerant charge
and operation check
Gas leak check
Refrigerant recovery
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Charge refrigerant
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Refrigerant charge
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil, ether oil and alkylbenzene oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adopter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
Industry-first flash injection circuit is equipped, which enables to
keep the equal capacity with the rating even when outside temperature is -15:.
HIGH SPEED HEATING START UP
The performance of heating start up is improved. Compared to
RP type, Zubadan reduced the time for heating start up by about
half. After starting operation, the airflow temperature goes up to
45: quickly in 10 minutes. With industry-first shorter and less
frequent defrost, defrosting time is cut down by 15% compared
to RP type and heating operation can continuously run for maximum 150 minutes.
WIDE HEATING RANGE
The heating range is expanded to -25: compared to RP type
which is up to -20
:.
(kW)
Performance
about
15
10
Heating capacity
0
(kW)
Heating capacity(Peak)
+1 Condition
Room temp. 20(D.B.) Outdoor temp. 2(D.B.)/1(W.B.) : Unit HRP100, Hi notch
30%UP
-25-20-15-10-50
Outdoor W.B. temp.
HRP100
Outlet air temp.45
15
13kW
(Outlet air temp. 45)
10
0
0
About 10min.
5101520
+1
About 50% CUT
Elapsed time(min.)
HRP125
RP125
RP100
RP71
When stabled,
hot air of 50
It doesn’t reach 50
when outside air temp.
is too low,
Stable
About 19 min.
RP type:
Outlet air temp. 45
HRP100
HRP71
(Indoor PKA type)
Expanded
-
Up to -25
11~
-20
RP type
-
25
-25-20 -15-10-50
HRP type
Outdoor wet-bulb temperature
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
Max.30m (PUHZ-HRP71/100/125)
The refrigerant circuit with LEV (Linear Expansion Valve) and power receiver always control the optimal refrigerant level
regardless of the length (30 m max. and 5 m min.) of piping. The additional refrigerant charging work during installation
often causes problems. It is completely eliminated by chargelss system. This unique system improves the quality and reliability of the work done. It also helps to speed up the installation time.
REFRIGERANT LEAKAGE DETECTION FUNCTION
PUHZ-HRP·HA(2) can detect refrigerant leakage which may happen during a long period of use.
7
5
SPECIFICATIONS
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Airflow
Defrost method
OUTDOOR UNIT
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
REFRIGERANT PIPING
*
/min(CFM
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
mm(in.)
mm(in.)
kW
W
kW
dB
dB
PUHZ-HRP71/100VHA
Single 50Hz, 230V
A
Linear Expansion Valve
ANB33FJCMT ANB33FJEMT
0.086+0.086 0.074+0.074
)
52
53
330+30(13+1-3/16)
L
28
Munsell 3Y 7.8/1.1
Hermetic
2.5
Inverter
HP switch
LP switch
Discharge thermo
—
Plate fin coil
Propeller fan % 2
100(3,530)
Reverse cycle
950(37-3/8)
1,350(53-1/8)
120(265)
R410A
5.5(12.1)
1.40(FV50S)
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 30m
Max. 75m
PUHZ-HRP71/100VHA2
PUHZ-HRP71/100VHA2R1
Cooling
HeatingCoolingHeating
51
52
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Airflow
Defrost method
OUTDOOR UNIT
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
REFRIGERANT PIPING
/min(CFM
*
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Terminal Block
Connector
Connector
Connector
Switch
Switch
Switch
LED
LED
LED
LED
LED
>
NAME
<
M-NET connection>
<
Transmission>
<
Power Supply>
<
M-NET communication>
<
Status of communication>
<
Address setting : 1s digit>
<
Address setting : 10s digit>
<
Power Supply : DC5V>
<
Connection to Outdoor Unit>
<
Transmission : Sending>
<
Transmission : Receiving>
<
Power Supply : DC12V>
SW5-6 +2
ON
OFF
123456
ON
OFF
123456
+3 Setting of the starting ambient temp. of the flash injection.
The black square (■) indicates a switch position.
Ambient temp.
3°C or less
(lnitial setting)
SW9-3,4 +4
ON
OFF
1234
Ambient temp.
0°C or less
SW9-3,4 +4
ON
OFF
1234
+4. SW9-1 to 2 : Function Switch
Ambient temp.
-3°C or less
19
SW9-3,4 +4
ON
OFF
1234
Ambient temp.
-6°C or less
SW9-3,4 +4
ON
OFF
1234
9
WIRING SPECIFICATIONS
9-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity*1
Main switch (Breaker)
)
Outdoor unit power supply
2
. %
Indoor unit-Outdoor unit
ing
Indoor unit-Outdoor unit ear
Wir
Wire No
Remote controller-Indoor unit
size (mm
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Circuit rating
Remote controller-Indoor unit
*1.
A breaker with at least 3 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductor of the supply.
*2. Refer to 9-3.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
th*2
*2
*3
*4
*4
*4
*4
Caution:
Be sure to install N-Line. Without N-Line, it could cause damage to the unit.
Notes: 1. Wiring size must comply with the applicable local and national code..
2. Power supply cables and Indoor/Outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable.
(Design 60245 IEC 57)
3. Use an earth wire which is longer than other cables so that it wil not become disconnected when tension is applied.
HRP71V, HRP100VHA
~/N (single), 50 Hz,
230 V
32 A
3 % Min. 4
3)
% 1.5 (Polar
1 % Min. 1.5
2 %)
0.3 (Non-polar
AC 230 V
AC 230 V
DC 24 V
DC 12 V
HRP100VHA2(R1)
~/N (single), 50 Hz,
230 V
40 A
3 % Min. 6
3 % 1.5 (Polar)
1 % Min. 1.5
2 % 0.3 (Non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 12 V
HRP100, 125Y
3N ~ (3phase), 50 Hz,
400 V
16 A
5 % Min. 1.5
3 % 1.5 (Polar)
1 % Min. 1.5
2 % 0.3 (Non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 12 V
Power supply
Isolator
S1
A-Control
Outdoor Unit
S2
S3
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation
between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch
the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
Turn on the main power when the ambient temperature is -20°C or higher.
In below -20°C condition, it needs at least 4hr standby to operate in order to warm the electrical parts.
3 poles isolator
S1
S2
S3
A-Control
Indoor Unit
1:1 system Electrical wiringSynchronized twin system Electrical wiring
• Synchronized twin
Indoor
unit
1
2
S1
S2
S3
Unit
power
supply
Earth leakage breaker
Wiring circuit breaker or
isolating switch
Outdoor
unit
L
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
Remote
controller
2
Unit
power
supply
Earth leakage breaker
Wiring circuit breaker or
isolating switch
Outdoor
unit
L
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
Remote
controller
2
20
9-2. SEPARATE INDOOR UNIT/ OUTDOOR UNIT POWER SUPPLIES
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
1:1 System
<For models without heater>
* The optional indoor power supply terminal kit is required.
L
N
S1
S2
S3
L
N
S1
S2
S3
1
2
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Simultaneous twin system
<For models without heater>
* The optional indoor power supply terminal kits are required.
L
N
S1
S2
S3
1
2
L
N
S1
S2
S3
1
2
L
N
S1
S2
S3
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table
below. If the optional indoor power supply terminal kit is used, change the indoor
unit electrical box wiring referring to the figure in the right and the DIP switch
settings of the outdoor unit control board.
Indoor unit specifications
Indoor power supply terminal kit (option)
Indoor unit electrical box connector connection change
Label affixed near each wiring diagram
for the indoor and outdoor units
Outdoor unit DIP switch settings (when
using separate indoor unit/outdoor unit
power supplies only)
ON
OFF
Required
Required
Required
3
12(SW8)
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Indoor unit power supplied from outdoor unit
(when shipped from factory)
Connectors (
BLUE
BLUE
YELLOW
YELLOW
CND
Set the SW8-3 to ON.
* There are three types of labels (labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cords
Remote controller
Indoor unit
Option
Initial setting:
for indoor unit power
supplied from outdoor unit)
ORANGE
CND
Indoor unit
control board
Indoor unit power supply
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cords
Remote controller
Indoor unit
Option
Indoor unit power supply
Indoor unit earth
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Separate indoor unit/outdoor unit power
supplies
YELLOW
BLUE
BLUE
YELLOW
Connectors
CND
Indoor unit
control board
ORANGE
CND
Indoor unit model
Indoor unit power supply
Indoor unit input capacity
Main switch (Breaker)
Indoor unit power supply
Indoor unit power supply earth
)
2
Indoor unit-Outdoor unit
(mm
Wiring
Indoor unit-Outdoor unit earth
Wire No. % size
Remote controller-Indoor unit
Indoor unit L-N*4
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
rating
Circuit
Remote controller-Indoor unit
*1
*2
*3
*4
*4
*4
RP35~125
~/N (single), 50 Hz, 230 V
16 A
2 % Min. 1.5
1 % Min. 1.5
2 % Min. 0.3
–
2 % 0.3 (Non-polar)
AC 230 V
–
DC24 V
DC12 V
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductor of the supply.
*2. Max. 120 m
*3.The 10 m wire is attached in the remote controller accessory. Max. 500 m
*4.The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and indoor unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable.
(Design 60245 IEC 57)
3. Install an earth longer than other cables.
21
9-3. INDOOR – OUTDOOR CONNECTING CABLE
The cable shall not be lighter than design 60245 IEC or 60227 IEC.
Wire No. % Size ($)
Outdoor power supply
Max. 45m
Max. 50m
Max. 80m
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
+ The max. cable length may vary depending on the condition of installation, humidity or materials, etc.
Indoor/Outdoor separate
power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
+ The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient
insulation to ground or a poor electrical contact at the intermediate connection point.
3 % 1.5 (polar)
1 % Min. 1.5
3 % 2.5 (polar)
1 % Min. 2.5
Wire No. % Size ($)
Max. 120m
2 % Min. 0.3
3 % 2.5 (polar) and S3 separated
1 % Min. 2.5
—
22
9-4. M-NET WIRING METHOD
(Points to notice)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5 cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET P.C. board may burn out.
(3) Use 2-core x 1.25mm2 shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
Group
remote
controller
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the central-control remote controller.
M-NET transmission wire
Power
supply
unit for
transmission
wire
A-control
remote
controller
Bad example (Multi spot grounding of shield wire)
Central
remote
controller
Power
supply
appliance
Refrigerant
address 00
M-NET
address 01
M-NET type
outdoor unit
A-control
remote
controller
M-NET type
outdoor unit
Refrigerant
address 00
M-NET
address 02
M-NET type
outdoor unit
Refrigerant
address 00
M-NET
address 03
A-control
remote
controller
Good example 1 (Single spot grounding of shield wire)
Central
remote
controller
M-NET transmission wire
Good example 2 (Single spot grounding of shield wire)
Central
remote
controller
M-NET transmission wire
If there are more than 2 grounding spots on the shield wire, noise may enter into the shield wire because the ground wire
and shield wire form one circuit and the electric potential difference occurs due to the impedance difference among ground-
ing spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and shield
wire do not form one circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
Power
supply
appliance
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
23
M-NET wiring
2
(1) Use 2-core × 1.25mm
shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block. Connect one core of the
transmission wire (non-polar) to A(M1) terminal and the other to B(M2). Peel the
shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(A(M1), B(M2), S) on M-NET terminal block should be individually wired to the other
M-NET
terminal
block
ABS
Transmission
wire
Ground
wire
Shield
part
outdoor unit’s terminal, i.e. A(M1) to A(M1), B(M2) to B(M2) and S to S. In this case, choose one of those outdoor units
and drive a screw to fix an ground wire on the plate as shown on the right figure.
9-4-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
(SW11 for ones digit and SW12 for tens digit), which
is located on the M-NET board of outdoor unit.
(Initial setting: all addresses are set to “0”.)
<Setting example>
M-NET Address No.
SW11
Switch
setting
ones
digit
SW12
tens
digit
12
3
3
4
2
1
0
2
1
0
4
2
5
5
1
6
6
0
7
7
9
9
8
8
3
3
4
4
2
5
5
1
6
6
0
7
7
9
9
8
8
50
3
4
2
5
1
6
0
7
9
8
~
3
4
2
5
1
6
0
7
9
8
9-4-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group setting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Initial setting: all
switches are OFF. (All refrigerant addresses are “00”.)]
Refrigerant
address
ON
OFF
1
ON
OFF
1
ON
OFF
1
3
4
5
2
6
0
ON
OFF
1
3
4
5
2
6
8
ON
OFF
1
3
4
5
2
6
1
ON
OFF
1
3
4
5
2
6
9
ON
OFF
1
3
4
5
2
6
2
ON
OFF
1
3
4
5
2
6
10
ON
OFF
1
3
4
5
2
6
3
ON
OFF
1
3
4
5
2
6
11
ON
OFF
1
3
4
5
2
6
4
ON
OFF
1
3
4
5
2
6
12
ON
OFF
1
3
4
5
2
6
5
ON
OFF
1
3
4
5
2
6
13
ON
OFF
1
3
4
2
6
3
4
2
14
3
5
5
4
5
2
6
OFF
6
6
7
ON
1
3
4
5
2
6
15
9-4-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above section. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
Group AGroup BGroup C
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
A-control
remote
controller
TB5
w Refrigerant addresses can be overlapped if they are in the different group.
Group AGroup B
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
Refrigerant
address 01
M-NET
address 02
TB5
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 00
M-NET
address 04
A-control
remote
controller
Refrigerant
address 00
M-NET
address 04
A-control
remote
controller
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 02
M-NET
address 05
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the
group for the outdoor unit whose refrigerant address is “00”.
Refrigerant flow in cooling
Refrigerant flow in heating
Thermistor TH7
(Outdoor)
Thermistor
TH6
(Outdoor
2-phase pipe)
Thermistor TH3
(Outdoor pipe)
Distributor
Thermistor TH33
(Outdoor pipe)
25
10-1. Refrigerant recovering (pump down)
Perform the following procedures to recover the refrigerant when moving the indoor unit or the outdoor unit.
1 Turn on the power supply (circuit breaker).
w When power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If
“CENTRALLY CONTROLLED” is displayed, the refrigerant recovering (pump down) cannot be completed normally.
2 After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor
(outdoor unit) and fans (indoor and outdoor units) start operating and refrigerant recovering operation begins. LED1 and
LED2 on the control board of the outdoor unit are lit.
Set the SWP switch (push-button type) to ON in order to perform refrigerant recovering operation only when the unit is
w
stopped. However, refrigerant recovering operation cannot be performed until compressor stops even if the unit is stopped.
Wait 3 minutes until compressor stops and set the SWP switch to ON again.
3 Because the unit automatically stops in about 2 to 3 minutes after the refrigerant recovering operation (LED1 is not lit and
LED2 is lit), be sure to quickly close the gas stop valve.
w In case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then
repeat step 2 3 minutes later.
w If the refrigerant collecting operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain
stopped until the power supply is turned off.
4 Turn off the power supply (circuit breaker).
10-2. Unit replacement operation (except for PUHZ-HRP·HA2R1)
When reusing the existing pipes that carried R22 refrigerant for the HRP71, HRP100 and HRP125 models, replacement
operation must be performed before performing a test run.
1 If new pipes are used, these procedures are not necessary.
2 During replacement operation, “C5” is displayed on “A-Control Service Tool (PAC-SK52ST)”.
Replacement operation procedures
1 Turn on the power supply.
2 Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start replacement operation.
• The replacement operation is performed using the cooling system. Cool air will flow from the indoor unit during the replacement operation.
• During the replacement operation,
control board of the outdoor unit blink together.
3 Replacement operation requires at least 2 hours to complete.
• After setting switch SW8-2 to ON, the unit automatically stops after 2 hours.
• Replacement operation can be performed repeatedly by setting switch SW8-2 from OFF to ON. Make sure to perform
the operation more than 2 hours. (If the operation is performed less than 2 hours, the existing pipes cannot be cleaned
enough and the unit may be damaged.)
• If replacement operation is performed over 2 hours, this action is recorded into nonvolatile memory of control board.
4 Set switch SW8-2 to OFF. (Replacement operation is completed.)
w The unit can be operated normally by remote controller even if SW8-2 remains ON.
w If the indoor temperature is less than 15:, the compressor will operate intermittently but the unit is not faulty.
TEST RUN
is displayed on the remote controller and LED1 (green) and LED2 (red) on the
10-3. Start and finish of test run
• Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
1 Set the operation mode (cooling/heating) using SW4-2.
2 Turn on SW4-1 to start test run with the operation mode set by SW4-2.
3 Turn off SW4-1 to finish the test run.
• There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion pipe is just moving to adjust opening pulse.
• There may be a knocking sound around the machine room for several seconds after compressor
starts operating, but this is no problem with product because the check valve itself generates the
sound because pressure difference is small in the refrigerant circuit.
<SW4>
ON
OFF
12
Stop Operation
Cooling Heating
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
26
11TROUBLESHOOTING
11-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.
Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the
table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action according
to “11-4. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the
trouble according to “11-5. Troubleshooting by inferior
phenomena”.
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring and etc.
Reset error code logs and restart the unit after finishing
service.
There is no abnormality in electrical component,
controller board, remote controller and etc.
Re-check the abnormal symptom.
Conduct trouble shooting and ascertain the cause of the
trouble
according to “11-5. Troubleshooting
by inferior
phenomena”.
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
11-2. CHECK POINT UNDER TEST RUN
(1) Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block (L, N) on the outdoor unit by 500V Megger
and check that it is 1.0M" or over.
Do not use 500V Megger to indoor/outdoor connecting wire terminal block (S1, S2, S3) and remote controller terminal block
w
(1, 2). This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Turn on power supply 12 hours before test run in order to protect compressor.
• For specific models which requires higher ceiling settings or power failure automatic recovery, make proper changes of set-
tings referring to the description of “Selection of Functions through Remote Controller”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
27
"TEST RUN" and the currently selected
operation mode are displayed altemately.
Displays the remaining
test run time.
[TEST] button
Operating procedures
1. Turn on the main power supply.
2. Press TEST button twice.
3. Press OPERATION SWITCH
button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for
correct running.
While the room temperature display on the remote
controller is “PLEASE WAIT”, the remote controller is disabled.
Wait until “PLEASE WAIT” disappears before using remote controller.
“PLEASE WAIT” appears for about 2 minutes after power
supply is turned on. +1
The TEST RUN appears on the screen.
Cooling mode:
Heating mode: Check if warm air blows. (It takes a little
while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to
provide optimum fan speeds. Therefore, the fan keeps
running at a low speed to meet the current outside air
condition unless it exceeds its available maximum power.
Then, in actuality, the fan may stop or run in the reverse
direction depending on the outside air, but this does not
mean malfunction.
Check if cool air blows and water is drained.
6. Press the ON/OFF button to reset the test run in progress.
Pipe (liquid) temperature
7. Register the contact number.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after 2 hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin operation. Malfunctions may not be displayed regardless of incorrect wiring.
w1 After turning on the power supply, the system will go into startup mode, “PLEASE WAIT” will blink on the display section
of the room temperature, and lamp (green) of the remote controller will flash.
As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case
the address is not 0. LED3 will blink.
As to OUTDOOR BOARD LED, LED1 (green) and LED2 (red) will be lit up. (After the startup mode of the system finishes, LED2 (red) will be turned off.)
In case OUTDOOR BOARD LED is digital display, — and — will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from
the symptoms.
The below symptoms are under test run mode. “startup” in the table means the display status of w1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “PLEASE
WAIT”, and
cannot be operated.
After power is turned on, “PLEASE WAIT”
is displayed for 3 minutes, then error code
is displayed.
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed,
green(once) and red(once) blink
alternately. <F1>
After “startup” is displayed,
green(once) and red(twice) blink
• After power is turned on, “PLEASE WAIT” is displayed for 2
minutes during
• Outdoor unit’s protection device connector is open.
Cause
1, L2, L3 and
alternately. <F3, F5, F9>
• Incorrect wiring between the indoor and outdoor unit (Polarity
is wrong for S1, S2, S3.)
• Remote controller transmission wire is short.
• There is no outdoor unit of address 0.
(Address is other than 0.)
• Remote controller transmission wire is open.
• After canceling function selection, operation is not possible for
about 30 seconds. (Normal)
No display appears even when remote
controller operation switch is turned on.
(Operation lamp does not light up.)
Display appears but soon disappears
even when remote controller is operated.
After “startup” is displayed,
green(twice) and red(once) blink
alternately. <EA. Eb>
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed, only
green lights up. <00>
w Press the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the contents of LCD display.
LCD
Abnormality of room temperature thermistor
P1
Abnormality of pipe temperature thermistor/Liquid
P2
Abnormality of drain sensor/ Float switch connector open
P4
Drain overflow protection is operating.
P5
Freezing/overheating protection is operating.
P6
Abnormality of pipe temperature
P8
Abnormality of pipe temperature thermistor/Cond./Eva
P9
Fb
Abnormality of indoor controller board
Contents of inferior phenomena
LCD
Malfunction outdoor unit
U1~UP
Malfunction
F3~F9
E0~E5
Remote controller transmitting error
Indoor/outdoor unit communication error
E6~EF
No error history
---No applied unit
FFFF
Forced compressor stop(due to water leakage abnormality)
PA
Contents of inferior phenomena
outdoor unit
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
(microprocessor power supply)
LED1
(remote controller)
LED2
(indoor/outdoor communication)
LED3
Lits when power is supplied.
Lits when power is supplied for wired remote controller.
The indoor unit should be connected to the outdoor unit with address “0” setting.
Blinks when indoor and outdoor unit are communicating.
28
,
ON/OFF
MODE
CHECK
TEST RUN
SET
TEST RUN
FAN
VAN E
LOUVER
RESET
CLOCK
TEMP
AUTO STOP
AUTO START
h
min
Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M".
1 Turn on the main power to the unit.
2 Press the
(Start this operation from the status of remote controller display
turned off.)
TEST RUN
A
3 Press the
check whether cool air is blown out from the unit.
4 Press the
check whether warm air is blown out from the unit.
5 Press the
from the unit.
6 Press the
properly.
7 Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps 2 to 7.
• It is not possible to run in FAN, DRY or AUTO mode.
TEST RUN
button twice continuously.
and current operation mode are displayed.
MODE
( ) button to activate
MODE
( ) button to activate
FAN
button and check whether strong air is blown out
VANE
button and check whether the auto vane operates
COOL
HEAT
mode, then
mode, then
29
11-3. HOW TO PROCEED “SELF-DIAGNOSIS”
11-3-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop,
and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the
temperature display, and the error code and unit number are
displayed alternately as shown below. (If the outdoor unit is
malfunctioning, the unit number will be “00”.)
In the case of group control, for which one remote controller controls
multiple refrigerant systems, the refrigerant address and error code of
the unit that first experienced trouble (i.e., the unit that transmitted
the error code) will be displayed.
To clear the error code, press the button.
ON/OFF
Error code (2 or 4 digits)
(Alternating Display)
Address (3 digits) or unit number (2 digits)
When using remote-/local-controller combined operation, cancel the error code after turning off remote operation. During
central control by a MELANS controller, cancel the error code by pressing the
ON/OFF
button.
11-3-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote
controller or power is turned off.
Check the error code history for each unit using the remote controller.
Switch to self-diagnosis mode.
Press the
will change as shown below.
CHECK
button twice within 3 seconds. The display content
Unit number or refrigerant address
to be diagnosed
Set the unit number or refrigerant address you want to diagnose.
Press the [TEMP] buttons ( and ) to select the desired number
or address. The number (address) changes between [01] and [50] or [00]
and
[15].
The refrigerant address will begin to blink
approximately 3 seconds after being
selected and the self-diagnosis process will begin.
Display self-diagnosis results.
<When there is error code history>
(For the definition of each error code, refer to the indoor unit's installation manual or service handbook.)
(Alternating Display)
Error code (2 or 4 digits)
<When there is no error code history><When there is no corresponding unit>
Reset the error history.
Display the error history in the diagnosis result display screen (see step
Address (3 digits) or unit number (2 digits)
).
30
Loading...
+ 88 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.