Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
March 2010
No. OCS11
REVISED EDITION-B
TECHNICAL DATA BOOK
<Indoor unit>
[Model names]
PLA-RP·BA/BA2/BA3
PEAD-RP·JA(L)
PEAD-RP·EA(2)
PEAD-RP·GA
PKA-RP·HAL
PKA-RP·KAL
PKA-RP·GAL
PKA-RP·FAL(2)
<Outdoor unit>
[Model names]
PUHZ-HRP71/100VHA
PUHZ-HRP100/125YHA
R410A
INVERTER
Revision :
• PLA-RP·BA3, PKA-RP·HAL/KAL
and PEAD-RP·JA(L) are added,
and the data of PUHZ-HRP·HA2
has been modified in REVISED
EDITION-B.
• Some descriptions have been
modified.
• Please void OCS11
REVISED EDITION-A.
PUHZ-HRP71/100VHA2
PUHZ-HRP100/125YHA2
CONTENTS
1. REFERENCE SERVICE MANUAL ············································· 2
2. SPECIFICATIONS ······································································ 3
3. OUTLINES AND DIMENSIONS ···············································12
4. WIRING DIAGRAM ··································································· 24
5. REFRIGERANT SYSTEM DIAGRAM ······································ 36
6. PERFORMANCE CURVES ······················································ 38
7. CORRECTION FACTORS ························································ 40
8. APPLICABLE EXTENSION PIPE FOR EACH MODEL ·········· 41
9. AIR FLOW DA TA ······································································ 44
10. NOISE CRITERION CURVES ·················································· 60
11. OPTIONAL PARTS ············································································ 7 4
Zubadan
Page 2
1
REFERENCE SERVICE MANUAL
For information on service, please refer to the service manual as follows.
1-1. INDOOR UNIT
Model Name Service Ref. Service Manual No.
PLA-RP35/50/60/100/125BA
PLA-RP71/100/125BA2
PLA-RP100BA3 PLA-RP100BA3
PKA-RP35/50HAL PKA-RP35/50HAL
PKA-RP60/100KAL PKA-RP60/100KAL.TH
PEAD-RP35/50/60/71/100/125JA(L) PEAD-RP35/50/60/71/100/125JA(L).UK
PKA-RP35/50GAL PKA-RP35/50GAL#1 OC330
PKA-RP60/100FAL
PKA-RP50FAL2
PEAD-RP50/60/71/125EA
PEAD-RP35/100EA2
PEAD-RP60/71/100GA PEAD-RP60/71/100GA#1.UK HWE0506
PLA-RP35/50/60/100/125BA#2.UK
PLA-RP71/100/125BA2.UK
PKA-RP60/100FAL#1
PKA-RP50FAL2#1
PEAD-RP50/60/71/125EA#1.UK
PEAD-RP35/100EA2#1.UK
OCH412
OCB412
OCH459
OCB459
OCH453
OCB453
OCH452
OCB452
HWE08130
BWE08240
OC331
HWE0521
1-2. OUTDOOR UNIT
Model Name Service Ref. Service Manual No.
PUHZ-HRP71/100VHA
PUHZ-HRP100/125YHA
PUHZ-HRP71/100VHA2
PUHZ-HRP100/125YHA2
PUHZ-HRP71/100VHA
PUHZ-HRP100/125YHA
PUHZ-HRP71/100VHA2R1
PUHZ-HRP100/125YHA2R1
OCH425
OCB425
2
Page 3
2
SPECIFICATIONS
2-1. CEILING CASSETTE TYPE
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW
Total input kW
EER
Energy label class
SHF
Heating Capacity Btu/h
kW
Total input kW
COP
Energy label class
Booster heater kW
Power supply Phase
Cycle Hz
Voltage V
Breaker size A
Indoor unit Air flow CMM
Outdoor unit Air flow CMM
Refrigerant pipe size Gas side O.D. mm
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
(Low-Medium2-Medium1-High)
External pressure Pa
Sound level
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension W : mm
Unit (Panel) D : mm
Weight kg
Unit (Panel) lbs
Field drain pipe O.D. mm
Sound level at cooling
Sound level at heating
External finish
Dimension W : mm
Weight kg
Liquid side O.D. mm
Height difference
Length
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 32°C, W.B. 23°C
D.B. 19°C, W.B. 15°C D.B. -5°C *
D.B. 28°C
D.B. 17°C
Indoor Outdoor
CFM
dB(A)
H : mm
W : inch
D : inch
H : inch
inch
CFM
dB(A)
dB(A)
D : mm
H : mm
W : inch
D : inch
H : inch
lbs
inch
inch
m
m
D.B. 46°C
D.B. 21°C, W.B. 15°C
D.B. -25°C, W.B. -25°C
PLA-RP71BA2 PLA-RP100BA2
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2
24,200 34,100
7.1 ( 4.9 - 8.1 ) 10.0 ( 4.9 - 11.4 )
1.94 2.44
3.66 4.10
AA
0.73 0.74
27,300 38,200
8.0 ( 4.5 - 10.2 ) 11.2 ( 4.5 - 14.0 )
1.90 2.54
4.21 4.41
AA
-1
50
230
32 40
14 - 16 - 18 - 21
495 - 565 - 635 - 740
10-3/16 (1-3/8) 11-3/4 (1-3/8)
23 (6)
51 (13)
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
* If optional air protect guide is installed : D.B.-18°C
20 - 23 - 26 - 30
710 - 810 - 920 - 1060
0
32 - 34 - 37 - 40 28 - 30 - 32 - 34
White Munsell 6.4Y 8.9/0.4
840 (950)
840 (950)
298 (35) 258 (35)
33-1/16 (37-3/8)
33-1/16 (37-3/8)
27 (6)
60 (13)
32
1-1/4
100
3,530
51
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
120
265
15.88
5/8
9.52
3/8
Max. 30
Max. 75
Single phase 230V 50Hz
PLA-RP100BA3
PUHZ-HRP100VHA2
34,100
10.0 ( 4.9 - 11.4 )
2.44
4.10
A
0.74
38,200
11.2 ( 4.5 - 14.0 )
2.54
4.41
A
-
40
20 - 23 - 26 - 30
710 - 810 - 920 - 1060
32 - 34 - 37 - 40
298 (35)
11-3/4 (1-3/8)
26 (6)
57 (13)
3
Page 4
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW
Total input kW
EER
Energy label class
SHF
Heating Capacity Btu/h
kW
Total input kW
COP
Energy label class
Booster heater kW
Power supply Phase
Cycle Hz
Voltage V
Breaker size A
Indoor unit Air flow CMM
(Low-Medium2-Medium1-High)
CFM
External pressure Pa
Sound level
(Low-Medium2-Medium1-High)
dB(A)
External finish (Panel)
Dimension W : mm
Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
Unit (Panel) lbs
Field drain pipe O.D. mm
inch
Outdoor unit Air flow CMM
CFM
Sound level at cooling
Sound level at heating
dB(A)
dB(A)
External finish
Dimension W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit
Lower limit
Upper limit
Lower limit
m
m
D.B. 32°C, W.B. 23°C
D.B. 19°C, W.B. 15°C D.B. -5°C *
D.B. 28°C
D.B. 17°C
Indoor Outdoor
D.B. 46°C
D.B. 21°C, W.B. 15°C
D.B. -25°C, W.B. -25°C
PLA-RP100BA2 PLA-RP125BA2
PUHZ-HRP100YHA2 PUHZ-HRP125YHA2
34,100 42,700
10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 )
2.50 3.79
4.00 3.30
AA
0.74 0.71
38,200 47,800
11.2 ( 4.5 - 14.0 ) 14.0 ( 5.0 - 16.0 )
2.60 3.57
4.31 3.92
AA
--
PLA-RP100BA3
PUHZ-HRP100YHA2
34,100
10.0 ( 4.9 - 11.4 )
2.50
4.00
A
0.74
38,200
11.2 ( 4.5 - 14.0 )
2.60
4.31
A
-
3
50
400
16
20 - 23 - 26 - 30 22 - 25 - 28 - 31
710 - 810 - 920 - 1060 780 - 880 - 990 - 1090
00
32 - 34 - 37 - 40 34 - 36 - 39 - 41
20 - 23 - 26 - 30
710 - 810 - 920 - 1060
0
32 - 34 - 37 - 40
White Munsell 6.4Y 8.9/0.4
840 (950)
840 (950)
298 (35)
33-1/16 (37-3/8)
33-1/16 (37-3/8)
11-3/4 (1-3/8)
27 (6)
60 (13)
26 (6)
57 (13)
27 (6)
60 (13)
32
1-1/4
100
3,530
51
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
134
295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
3. Guaranteed voltage
198~264V, 50Hz(HRP100, 125Y : 342~457V, 50Hz)
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
* If optional air protect guide is installed : D.B.-18°C
3 phase 400V 50Hz
4
Page 5
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW
Total input kW
EER
Energy label class
SHF
Heating Capacity Btu/h
kW
Total input kW
COP
Energy label class
Booster heater kW
Power supply Phase
Cycle Hz
Voltage V
Breaker size A
Indoor unit Air flow CMM
(Low-Medium2-Medium1-High)
CFM
External pressure Pa
Sound level
(Low-Medium2-Medium1-High)
dB(A)
External finish (Panel)
Dimension W : mm
Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
Unit (Panel) lbs
Field drain pipe O.D. mm
inch
Outdoor unit Air flow CMM
CFM
Sound level at cooling
Sound level at heating
dB(A)
dB(A)
External finish
Dimension W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit
Lower limit
Upper limit
Lower limit
m
m
D.B. 32°C, W.B. 23°C
D.B. 19°C, W.B. 15°C D.B. -5°C *
D.B. 28°C
D.B. 17°C
Indoor Outdoor
D.B. 46°C
D.B. 21°C, W.B. 15°C
D.B. -25°C, W.B. -25°C
PLA-RP100BA PLA-RP100BA PLA-RP125BA
PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA
34,100 34,100 42,700
10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 )
3.02 3.02 3.87
3.31 3.31 3.23
AAA
0.74 0.74 0.71
38,200 38,200 47,800
11.2 ( 4.5 - 14.0 ) 11.2 ( 4.5 - 14.0 ) 14.0 ( 5.0 - 16.0 )
3.10 3.10 3.88
3.61 3.61 3.61
AAA
---
13
50 50
230 400
32 16
20 - 23 - 26 - 30 22 - 25 - 28 - 31
710 - 810 - 920 - 1060 780 - 880 - 990 - 1090
00
32 - 34 - 37 - 40 34 - 36 - 39 - 41
White Munsell 6.4Y 8.9/0.4
840 (950)
840 (950)
298 (35)
33-1/16 (37-3/8)
33-1/16 (37-3/8)
11-3/4 (1-3/8)
25 (6)
55 (13)
32
1-1/4
100
3,530
52
53
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
120 134
265 295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
3. Guaranteed voltage
198~264V, 50Hz(HRP100, 125Y : 342~457V, 50Hz)
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
* If optional air protect guide is installed : D.B.-18°C
V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz
5
Page 6
2-2. CEILING-CONCEALED TYPE
Model Name Indoor Unit PEAD-RP71JA(L) PEAD-RP100JA(L) PEAD-RP100JA(L) PEAD-RP125JA(L)
Outdoor Unit
Cooling Capacity Btu/h 24,200 34, 100 34, 100 42,700
kW 7.1 (3.3 - 8.1) 10.0 (4.9 - 11.4) 10.0 (4.9 - 11.4) 12.5 (5.5 - 14.0)
Total Input kW 2.15 (2.13) 3.06 (3.04) 3.06 (3.04) 3.89 (3.87)
EER 3.30 (3.33) 3.27 (3.29) 3.27 (3.29) 3.21 (3.23)
Energy label class A A A A
SHF 0.83 0.82 0.82 0.84
Heating Capacity Btu/h 27,300 38,200 38,200 47,800
kW 8.0 (3.5 - 10.2) 11.2 (4.5 - 14.0) 11.2 (4.5 - 14.0) 14.0 (5.0 - 16.0)
Total Input kW 2.34 3.10 3.10 3.88
COP 3.42 3.61 3.61 3.61
Energy label class B A A A
Booster heater kW ----
Power supply Phase
Cycle Hz 50 50
Voltage V 230 400
Breaker size A 32 40 16
Indoor unit Air fl ow
(Low - Middle - High)
CMM 17.5 - 21 - 25 24 - 29 - 34 24 - 29 - 34 29.5 - 35.5 - 42
CFM 618 - 742 - 883 847 - 1,024 - 1,201 847 - 1,024 - 1,201 1,042 - 1,253 - 1,483
External pressure Pa 35 / 50 / 70 / 100 / 150
Sound level
dB(A) 26 - 30 - 34 29 - 34 - 38 29 - 34 - 38 33 - 36 - 40
(Low - Middle - High/50Pa)
External fi nish Galvanized sheets
Dimension W : mm 1,100 1,400
D : mm 732
H : mm 250
W : inch 43-5/16 55-1/8
D : inch 28-7/8
H : inch 9-7/8
Weight kg 33 (32) 41 (40) 41 (40) 43 (42)
lbs 73 (71) 91 (89) 91 (89) 95 (93)
Field drain pipe O.D. mm 32
inch 1-1/4
Outdoor Unit Air fl ow CMM 100
CFM 3,530
Sound level at cooling dB(A) 51
Sound level at heating dB(A) 52
External fi nish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
D : mm 330 + 30
H : mm 1,350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
Weight kg 120 134
lbs 265 295
Refrigerant
pipe size
Gas side O.D. mm 15.88
inch 5/8
Liquid side O.D. mm 9.52
inch 3/8
Refrigerant
pipe length
Height difference m Max. 30
Length m Max. 75
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2
[
13
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 32°C, W.B. 23°C
D.B. 19°C, W.B. 15°C D.B. -5°C *
D.B. 28°C
D.B. 17°C
Indoor Outdoor
D.B. 46°C
D.B. 21°C, W.B. 15°C
D.B. -25°C, W.B. -25°C
3. Guaranteed voltage
Indoor unit : 198 ~ 264V, 50Hz
Outdoor unit : 198 ~ 264V, 50Hz (V)
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
* If optional air protect guide is installed : D.B.-18°C
342 ~ 457V, 50Hz (Y)
(V) Single phase 230V 50Hz
(Y) 3 phase 400V 50Hz
6
Page 7
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW
Total input kW
EER
Energy label class
SHF
Heating Capacity Btu/h
kW
Total input kW
COP
Energy label class
Booster heater kW
Power supply Phase
Cycle Hz
Voltage V
Breaker size A
Indoor unit Air flow CMM
(Low-High)
CFM
External pressure Pa
Sound level
(Low-High)
dB(A)
External finish (Panel)
Dimension W : mm
Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
Unit (Panel) lbs
Unit drain pipe
PEAD-RP71EA PEAD-RP100EA2
PUHZ-HRP71VHA PUHZ-HRP100VHA
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2
24,200 34,100
7.1 (4.9 - 8.1 ) 10.0 ( 4.9 - 11.4 )
2.15 3.06
3.30 3.27
AA
0.83 0.86
27,300 38,200
8.0 ( 4.5 - 10.2 ) 11.2 ( 4.5 - 14.0 )
2.34 3.10
3.42 3.61
BA
-1
50
230
32 (VHA)/ 40 (VHA2) 32
20 - 25 33.5 - 42
706 - 883 1,183 - 1,483
70 70
37-41 44-50
Galvanized sheets
1,175 1,415
740
325
46-1/8 55-11/16
29-1/8
12-13/16
44 65
97 143
R1 (External thread)
Outdoor unit Air flow CMM
CFM
Sound level at cooling
Sound level at heating
dB(A)
dB(A)
External finish
Dimension W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit
Lower limit
Upper limit
Lower limit
m
m
D.B. 32°C, W.B. 23°C
D.B. 19°C, W.B. 15°C D.B. -5°C *
D.B. 28°C
D.B. 17°C
Indoor Outdoor
D.B. 46°C
D.B. 21°C, W.B. 15°C
D.B. -25°C, W.B. -25°C
100
3,530
52 (VHA)/ 51 (VHA2)
53 (VHA)/ 52 (VHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
120
265
15.88
5/8
9.52
3/8
Max. 30
Max. 75
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
* If optional air protect guide is installed : D.B.-18°C
Single phase 230V 50Hz
7
Page 8
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW
Total input kW
EER
Energy label class
SHF
Heating Capacity Btu/h
kW
Total input kW
COP
Energy label class
Booster heater kW
Power supply Phase
Cycle Hz
Voltage V
Breaker size A
Indoor unit Air flow CMM
(Low-High)
CFM
External pressure Pa
Sound level
(Low-High)
dB(A)
External finish (Panel)
Dimension W : mm
Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
Unit (Panel) lbs
Unit drain pipe
PEAD-RP100EA2 PEAD-RP125EA
PUHZ-HRP100YHA PUHZ-HRP125YHA
PUHZ-HRP100YHA2 PUHZ-HRP125YHA2
34,100 42,700
10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 )
3.06 3.89
3.27 3.21
AA
0.86 0.82
38,200 47,800
11.2 ( 4.5 - 14.0 ) 14.0 ( 5.0 - 16.0 )
3.10 3.88
3.61 3.61
AA
-3
50
400
16
33.5 - 42 33.5 - 42
1,183 - 1,483 1,183 - 1,483
70 70
44 - 50 44 - 50
Galvanized sheets
1,415
740
325
55-11/16
29-1/8
12-13/16
65
143
R1 (External thread)
Outdoor unit Air flow CMM
CFM
Sound level at cooling
Sound level at heating
dB(A)
dB(A)
External finish
Dimension W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit
Lower limit
Upper limit
Lower limit
m
m
D.B. 32°C, W.B. 23°C
D.B. 19°C, W.B. 15°C D.B. -5°C *
D.B. 28°C
D.B. 17°C
Indoor Outdoor
D.B. 46°C
D.B. 21°C, W.B. 15°C
D.B. -25°C, W.B. -25°C
100
3,530
52 (YHA)/ 51 (YHA2)
53 (YHA)/ 52 (YHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
134
295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
3. Guaranteed voltage
Indoor unit:198~264V, 50Hz Outdoor unit:342~457V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
* If optional air protect guide is installed : D.B.-18°C
3 phase 400V 50Hz
8
Page 9
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW
Total input kW
EER
Energy label class
SHF
Heating Capacity Btu/h
kW
Total input kW
COP
Energy label class
Booster heater kW
Power supply Phase
Cycle Hz
Voltage V
Breaker size A
Indoor unit Air flow CMM
(Low-High)
CFM
External pressure Pa
Sound level
(Low-High)
dB(A)
External finish (Panel)
Dimension W : mm
Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
Unit (Panel) lbs
Unit drain pipe mm
inch
Outdoor unit Air flow CMM
CFM
Sound level at cooling
Sound level at heating
dB(A)
dB(A)
External finish
Dimension W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit
Lower limit
Upper limit
Lower limit
m
m
D.B. 32°C, W.B. 23°C
D.B. 19°C, W.B. 15°C D.B. -5°C *
D.B. 28°C
D.B. 17°C
Indoor Outdoor
D.B. 46°C
D.B. 21°C, W.B. 15°C
D.B. -25°C, W.B. -25°C
PEAD-RP71GA PEAD-RP100GA PEAD-RP100GA
PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2
24,200 34,100 34,100
7.1 ( 4.9 - 8.1 ) 10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 )
2.15 3.08 3.08
3.30 3.25 3.25
AAA
0.83 0.86 0.86
27,300 38,200 38,200
8.0 ( 4.5 - 10.2 ) 11.2 ( 4.5 - 14.0 ) 11.2 ( 4.5 - 14.0 )
2.34 3.28 3.28
3.42 3.41 3.41
BBB
--13
50 50
230 400
32 (VHA)/ 40 (VHA2) 32 16
20-25 26.5-33
706-883 935-1,165
10/50/70 10/50/70
35-38/37-41/37-43 40-43/42-45/42-46
Galvanized sheets
1,171 1,411
740
275
46-1/8 55-9/16
29-1/8
10-13/16
42 50
93 111
R1 (External thread)
1-1/4
100
3,530
52 (VHA, YHA)/ 51 (VHA2, YHA2)
53 (VHA, YHA)/ 52 (VHA2, YHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
120 134
265 295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
3. Guaranteed voltage
198~264V, 50Hz(HRP100Y : 342~457V, 50Hz)
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
* If optional air protect guide is installed : D.B.-18°C
V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz
9
Page 10
2-3. WALL-MOUNTED TYPE
Model Name
Cooling
Heating
Power supply
Indoor unit
Outdoor Unit
Refrigerant
pipe size
Refrigerant
pipe length
NOTE: 1. Rating conditions (ISO T1)
Indoor Unit PKA-RP100KAL PKA-RP100KAL
Outdoor Unit PUHZ-HRP100VHA2 PUHZ-HRP100YHA2
Capacity Btu/h 34,100
Total Input kW 2.93
EER 3.41
Energy label class A
SHF 0.73
Capacity Btu/h 38,200
Total Input kW 3.10
COP 3.61
Energy label class A
Booster heater kW Phase
Cycle Hz 50 50
Voltage V 230 400
Breaker size A 40 16
Air fl ow
(Low - Middle - High)
External pressure Pa 0
Sound level
(Low - Middle - High/50Pa)
External fi nish Munsell 1.0Y 9.2/0.2
Dimension W : mm 1,170
Weight kg 21
Field drain pipe O.D. mm 16
Air fl ow CMM 100
Sound level at cooling dB(A) 51
Sound level at heating dB(A) 52
External fi nish Ivory Munsell 3Y 7.8/1.1
Dimension W : mm 950
Weight kg 120 134
Gas side O.D. mm 15.88
Liquid side O.D. mm 9.52
Height difference m Max. 30
Length m MAx. 75
Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Heating Indoor : D.B. 20 (68°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor Outdoor
Cooling
Heating
Upper limit
Lower limit
Upper limit
Lower limit
D.B. 35°C, W.B. 22.5°C
D.B. 19°C, W.B. 15°C D.B. -5°C +1
D.B. 28°C
D.B. 17°C
kW 10.0 (4.9 - 11.4)
kW 11.2 (4.5 - 14.0)
[
13
CMM 20 - 23 - 26
CFM 705 - 810 - 920
dB(A) 41 - 45 - 49
D : mm 295
H : mm 365
W : inch 46-1/16
D : inch 11-5/8
H : inch 14-3/8
lbs 46
inch 5/8
CFM 3,530
D : mm 330 + 30
H : mm 1,350
W : inch 37-3/8
D : inch 13 + 1-3/16
H : inch 53-1/8
lbs 265 295
inch 5/8
inch 3/8
3. Guaranteed voltage
198~264V, 50Hz (V) / 342~457V, 50Hz (Y)
D.B. 46°C
D.B. 21°C, W.B. 15°C
D.B. -15°C, W.B. -15°C
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
+ 1. If optional air protect guide is installed : D.B.-15
V : Single phase 230V 50Hz
Y : 3 phase 400V 50Hz
10
Page 11
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW
Total input kW
EER
Energy label class
SHF
Heating Capacity Btu/h
kW
Total input kW
COP
Energy label class
Booster heater kW
Power supply Phase
Cycle Hz
Voltage V
Breaker size A
Indoor unit Air flow CMM
(Low-High)
CFM
External pressure Pa
Sound level
(Low-High)
dB(A)
External finish (Panel)
Dimension W : mm
Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
Unit (Panel) lbs
Field drain pipe I.D.
mm
inch
Outdoor unit Air flow CMM
CFM
Sound level at cooling
Sound level at heating
dB(A)
dB(A)
External finish
Dimension W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Heating
Height difference
Length
Upper limit
Lower limit
Upper limit
Lower limit
m
m
D.B. 32°C, W.B. 23°C
D.B. 19°C, W.B. 15°C D.B. -5°C *
D.B. 28°C
D.B. 17°C
Indoor Outdoor
D.B. 46°C
D.B. 21°C, W.B. 15°C
D.B. -25°C, W.B. -25°C
PKA-RP100FAL PKA-RP100FAL
PUHZ-HRP100VHA PUHZ-HRP100YHA
PUHZ-HRP100VHA2 PUHZ-HRP100YHA2
34,100 34,100
10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 )
2.93 2.93
3.41 3.41
AA
0.77 0.77
38,200 38,200
11.2 ( 4.5 - 14.0 ) 11.2 ( 4.5 - 14.0 )
3.10 3.10
3.61 3.61
AA
--
13
50 50
230 400
32 (VHA)/ 40 (VHA2) 16
22 - 28
780 - 990
0
41 - 46
White Munsell 3.4Y 7.7/0.8
1680
235
340
66-1/8
9-1/4
13-3/8
28
62
20
13/16
100
3,530
52
(VHA, YHA)/ 51 (VHA2, YHA2)
53 (VHA, YHA)/ 52 (VHA2, YHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
120 134
265 295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
3. Guaranteed voltage
198~264V, 50Hz(HRP100Y : 342~457V, 50Hz)
4. Above data are based on the indicated voltage.
Indoor unit Single phase 230V 50Hz
Outdoor unit
* If optional air protect guide is installed : D.B.-18°C
V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz
11
Page 12
3
OUTLINES AND DIMENSIONS
INDOOR UNIT
PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA PLA-RP100BA PLA-RP125BA
PLA-RP71BA2 PLA-RP100BA2 PLA-RP100BA3 PLA-RP125BA2
Cut out hole
100
14-:2.8
Burring hole
Ceiling
Unit : mm
130
167
155
++
Max. 4.0m
Branch duct hole
840
Suspension bolt
M10 or W3/8
Suspension bolt
lower edge
Air intake grille
Ceiling
Grille
1500mm
or more
20~45
Fresh air
intake hole
160
150
C
90
1
2
170
140
+
+
950
Indoor unit
Obstacle
D
50~70
+
Control wire entry
500
Air outlet hole
M
83 36
1000mm
or more
Ceiling hole
Suspension bolt pitch
160
Remote controller
terminal block
Indoor unit/Outdoor unit
connecting terminal block
Indoor power supply
terminal block(Option part)
187.5
Power supply wire,
Indoor unit/Outdoor unit
connecting wire entry
Air intake hole
M
Air outlet hole
3000mm or more
Floor
860~910
810
840
597
500
950
377 284 60
Indoor unit
160
Grille
M
M
83 36
1800mm or more
from floor
For high
attachment
20~45
Detail connecting of Branch duct(Both aspects)
20~45 860~910
(7.5) (7.5)
+35
620
605
- 5
Suspension bolt pitch
24
160
Drain pipe
connected to VP-25
A
190
156
105
+
+
+
0
+5
Ceiling
17
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
Auto vane
(Air outlet)
597
Air intake hole
Vane motor
Note1. Please choose the Grille from a standard grille, Auto-Grille.
2. As for drain pipe, please use VP-25(O.D. :32 PVC TUBE).
Drain pump is included.
Raise is max 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8.
(Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions + marked on the figure.
3) The optional high efficiency filter must be used jointly with optional multi-functional casement,
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/Water dew.)
8. As for necessary installation/service space, please refer to left figure.
Models
PLA-RP35/50BA
PLA-RP60BA
PLA-RP71BA,BA2
PLA-RP100,125BA
PLA-RP100BA3
PLA-RP100, 125,140BA2
Branch duct hole
Ceiling hole
Burring hole pitch
Detail drawing of fresh air intake hole
20~45
Connected the attached
socket.
()
Keep approximately
10 to 15mm space
between unit ceiling
and ceiling slab.
B
+
In case of standard grille : PLP-6BA / PLP-6BAMD
35
In case of Auto-Grille : PLP-6BAJ
In case of wireless remote controller : PLP-6BALM
Emergency operation
switch<Cooling>and
Emergency Up/Down switch<Up>
Emergency operation
switch<Heating>and
Emergency Up/Down switch<Down>
Receiver
Refrigerant pipe
···:6.35
Flared connection
···1/4F
Refrigerant pipe
:6.35 / :9.52
Flared connection
1/4F / 3/8F
(compatible)
Refrigerant pipe
···:9.52
Flared connection
···3/8F
158
+
DEFROST/STAND BY lamp
Operation lamp
1
Refrigerant pipe
···:12.7
Flared connection
···1/2F
Refrigerant pipe
···:15.88
Flared connection
···5/8F
70°
:175
Burring hole
3-:2.8
2
90 100 100 90
350
:150
Cut out hole
Burring hole pitch
:125
120°
Cut out hole
120°
:100
Ceiling
Auto Grille
Air intake grille up/down discharge
L.L Filter
Air intake grille
B A CDE
80
74
87
241 258
298
400
85 77
440 281
12
Page 13
PEAD-RP35, 50, 60, 71, 100, 125JA
:
2.9
2xE-
15
Air
outlet
D (Duct)
100x(E-1)=F
100
30
20
40
57
10
58
Suspension bolt hole
4-14x30 Slot
643 (Suspension bolt pitch)
57
A
Air
inlet
B(Suspension bolt pitch)
23
Unit : mm
210 18
G 21
C
Air Filter
Refrigerant piping
2
Flare connection (liquid)
2×2-:2.9
Refrigerant piping
1
Flare connection (gas)
NOTE 1. Use M10 screw for the Suspension bolt (field supply).
2. Keep the service space for the maintenance at the bottom.
3. This chart indicates for PEAD-RP60
models,which have 2 fans. PEAD-RP35
4. In case of the inlet duct is used,remove the air filter
(supply with the unit), then install the filter
(field supply) at suction side.
More than 10mm
Ceiling surface
Make the access door at the appointed position properly for service maintenance.
More than 20mm
32
23
40
100
178 (Duct)
•71•
10
122
33
136
100•125•140JA
•
50JA models have 1 fan.
Access door
238
67
356
732
700
Drain pipe
(O.D.:32)
Terminal block
(Remote controller transmission line)
Drain pump
Drain pipe(O.D.:32)
(Spontaneous draining)
PEAD-RP35,50JA
PEAD-RP60,71JA
PEAD-RP100,125JA
PEAD-RP140JA
41
Model A
6
N-
:
2.9
217
J
P
175±5mm
(Actual length)
250
Control box
Terminal block
(Indoor/Outdoor connecting line)
E11D
C
900 954 860 9
1000
110 0B1154
1400
1454
1600
1654
1200
1500
1700
K
Q
1060
1360
15601416
1000
1300
1500
F
G
858 800
1058
1358
1558
Kx(L-1)=M
Qx(R-1)=S
Less than 300mm
Drain hose (I.D.:32)
<accessory>
Liquid pipe
Gas pipe
:12.7
:15.88
:6.35
:9.52
Less than 700mm
J
11
112 11 2
50
H
50
Note2
Required space for service and maintenance
250~300
450
777
450
More than 300
Access door
13
PEAD-RP35,50JA
PEAD-RP60,71JA
PEAD-RP100,125JA
PEAD-RP140JA
JQ S
H Model
54 260 4 780 10 40.5 273 4
1000
1200
5454320
1500
1700
330
37055
L49K
990
4
1280
148012124040
P10N
M
340
330
R
819
1020
4 40
1320
5
1520
5 380
Page 14
PEAD-RP35, 50, 60, 71, 100, 125JAL
2xE-:2.9
15
Suspension bolt hole
4-14x30 Slot
Unit : mm
210 18
Air
outlet
D (Duct)
100x(E-1)=F
100
30
20
40
Refrigerant piping
2
Flare connection (liquid)
2×2-
Refrigerant piping
1
Flare connection (gas)
NOTE 1. Use M10 screw for the Suspension bolt (field supply).
2. Keep the service space for the maintenance at the bottom.
3. This chart indicates for PEAD-RP60
models,which have 2 fans. PEAD-RP35
4. In case of the inlet duct is used,remove the air filter
(supply with the unit), then install the filter
(field supply) at suction side.
57
10
58
23
40
100
178 (Duct)
:
2.9
57
32
122
33
•71•
100•125•140JAL
•
50JAL models have 1 fan.
643 (Suspension bolt pitch)
10
136
67
356
732
700
PEAD-RP35,50JAL
PEAD-RP60,71JAL
PEAD-RP100,125JAL
PEAD-RP140JAL
Air
inlet
Drain pipe(O.D.:32)
Model A
110 0B115 4
1400
1600
A
217
900 954 860 9
1454
1654
G
C
B(Suspension bolt pitch)
21
23
Terminal block
(Remote controller transmission line)
250
Control box
Terminal block
(Indoor/Outdoor connecting line)
E11D
C
1000
1200
1060
1500
1360
1700
15601416
F
1000
1300
1500
Air Filter
175±5mm
(Actual length)
Gas pipe
G
: 12.7
858 800
1058
: 15.88
1358
1558
Liquid pipe
:6.35
:9.52
Drain hose (I.D.
<accessory>
:
32)
More than 10mm
Ceiling surface
Make the access door at the appointed position properly for service maintenance.
More than 20mm
50
H
50
Note2
Required space for service and maintenance
250~300
450
Access door
450
More than 300
777
Access door
J
6
N-
:
2.9
P
K
Q
PEAD-RP35,50JAL
PEAD-RP60,71JAL
PEAD-RP100,125JAL
PEAD-RP140JAL
Kx(L-1)=M
Qx(R-1)=S
JQ S
H Model
54 260 4 780 10 40.5 273 4
1000
1200
1500
1700
330
5454320
37055
M
L49K
990
4
1280
148012124040
P10N
340
330
J
11
112 112
R
819
1020
4 40
1320
5
1520
5 380
14
Page 15
PEAD-RP35EA2
PEAD-RP50EA
PEAD-RP60EA
Model
RP35,50
RP60
+ Initial setting
Refrigerant piping flare connection (liquid : F copper tube):HP
1
Refrigerant piping flare connection (gas :G copper tube):LP
2
Drain R1(External thread)
3
4
Electrical parts box
5
Drain Pump (Option)
6
Drain Pipe (Option) ... Flexible joint VP-25(I.D.
7
Filter
305 772
In case of rear inlet
21
256
F
:
32)
30
4
10
40
282
176
E D C B A
R410A Outdoor unit : 6.35 +
804 830
-
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
R407C Outdoor unit : 9.52
Outdoor unit (SUZ) : 6.35
1044 1070 290 280 1012
R407C Outdoor unit : 9.52 +
3.5
Air inlet
288
7
3.5
R410A Outdoor unit : 12.7 +
R407C Outdoor unit : 15.88
Set
61 227
1
2
450
G
15.88
Access door
30 640
10
35
109
Air outlet
450
24
179
Service space:500 or more
50~150
55
197
365~465
159
18
13
75
44
243
6
85
80
45
277
5
3
Unit : mm
81 B C
10-:3 (RP35,50)
12-:3 (RP60)
10
Lifting bolt hole
(14 22)
56 355
10-:3 (RP35,50)
10
:
3 (RP60)
12-
13 E
30
29
81
A
C
A
D
B 81
In case of bottom inlet
PEAD-RP71EA
PEAD-RP100EA2
PEAD-RP125EA
Model
RP71
RP100,125
+ Initial s
1
Refrigerant piping flare connection (liquid :9.52 copper tube):HP
2
Refrigerant piping flare connection (gas :F copper tube):LP
3
Drain R1 (External thread)
4
Electrical parts box
5
Drain Pump (Option)
6
Drain Pipe (Option) ... Flexible joint VP25(I.D.:32)
7
Filter
280 1012
1252
etting
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
Air inlet
7
3.5
15
E D C B A
R410A Outdoor unit : 15.88 +
1284 1310 370 360
R407C outdoor unit : 19.05 1584 1610 470 460 1552 RP140
30
30
3.5
40
319
261
181
7
3.5
282
Air outlet
40
176
256
10
Air inlet
81
A
B C 81
10-:3 (RP35,50)
12-
:
3 (RP60)
10
Service space:500 or more
29
365~465
122
45
307
323
50~150
81
55
197
308
81
13
44
75
243
6
113
5
3
A
CB
CB 81
A
E1 3
450
F
15.88 1044 1070 290
Access door
450
Set
680
4
30
10 53 169
2
1
35
20
210
140
Air outlet
81
12-:3
10
Lifting bolt hole
(14x22)
375
12-:3
80
10
30 D
15
Page 16
PEAD-RP60GA
PEAD-RP71GA
PEAD-RP100GA
Unit : mm
Model A B C D E
RP60
RP71
RP100
*
Initial setting
1125
1125
1365
1090
1090
1330
1050
1050
1290
1012
1012
1252
FG H J
7
840
840
7
1080
9
8
8
10
Outdoor unit(SUZ) : 6.35
Other outdoor unit : 9.52
9.52
9.52
*
R410A Outdoor unit : 15.88 *
R407C Outdoor unit : 19.05
15.88
15.88
16
Page 17
197
387
192
599
Top side
Front side
155
688
898
55
295
Front side (Grille open)
169
158
184
457 Gas pipe
539 Liquid pipe
610 Drain hose
Terminal block for outdoor unit
Terminal block for power supply (option)
Terminal block for
MA-remote controller (option)
Emergency operation switch
(cooling/heating)
Under side
Vane (auto)
Operation lamp
612
DEFROST/STAND BY lamp
Receiver
Knockout hole
for lower piping
Louver (manual)
Knockout hole
for lower piping
C
8
B
Size
Refrigerant pipe : :6.35
Flared connection : 1/4F
Refrigerant pipe : :12.7
Flared connection : 1/2F
:16 O.D
Liquid pipe
Gas pipe
Drain hose
Knockout hole
for right piping
Right side
Mount board
21.8
0
20
32.7
53.5
66
128.5
153.5
231.5
273.2
449
281
193.5
180.3
278.3
167
140
115
0
174
213
238
394
449
253.5
232.5
203.5
178.5
166
103.5
91
78.5
116
41
28.5
16
0
372.3
356.3
327.5
291.5
265
225
200
1257015
0
15
70
125
200
225
265
238
291.5
327.5
372.3
356.3
Indoor unit outline
Mount board
4-:9 Bolt hole
77-:5.1
Tapping
screw hole
0
58
3.8
Center measurement hole :2.5
A
B
43
6
60
46
56
46
43
59
C
56
12.5
43
D
43
6
56
69
Knockout hole for piping
Knockout hole
for left piping
Left side
Sleeve
(purchased locally)
:65~ :80
:65~ :80
Through hole
249
A
5
Min.7
250mm or greater with optional
drain pump installation.
Required space (Indoor unit)
Min.50
Min.220
Min.150
550mm or greater with optional
drain pump installation.
Min.250
Min.50
55mm or greater with left
or rear left piping or drain
pump installation.
Wall hole for
right rear piping
Knockout hole for
left rear piping (70 × 310)
Wall hole for
left piping
Air inlet
Air inlet
Air outlet
PKA-RP35HAL
PKA-RP50HAL
Unit : mm
17
Page 18
PKA-RP60KAL
PKA-RP100KAL
Left side
65.2
140.3
Unit : mm
Top side
423.7
11
Front side
431.7
Right side
Knockout hole
for left piping
53
30
32
18
35
Sleeve
(purchased locally)
75
365
A
66
Through hole
75~
80
Knockout hole for piping
C
77
67
65
65
10.7
7.8
Required space (Indoor unit)
74
(855)
1170
Front side (Grille open)
Filter hook
Under side
Vane (auto)
B
75-W5.1
BA
77
67
77
87
7.8
Air inlet
Tapping screw hole
65
Min. 48
108 mm or greater with left or
rear left piping or drain pump
installation
444 (Gas pipe)
482 (Liquid pipe)
585 (Drain hose)
Louver (manual)
Knockout hole
for lower piping
15.5
0
25
50
75
100
117
125
142
192
242
279.5
292
585
4-W 9 Bolt hole
408.5
439
454
517.4
439
530.5
430.5
Wall hole for
left rear piping
241
123
154
134
Temporarily fixing hole
314
364
384
384
339
Operation lamp
DEFROST/STAND BY lamp
Receiver
Terminal block for outdoor unit
Terminal block for power supply (option)
Terminal block for
MA-remote controller (option)
Emergency operation switch
(cooling/heating)
Piping connection department
Liquid pipe
Gas pipe
Drain hose
B
0
54
Center measurement hole W2.5
3
Mount board
110
189
Knockout hole for
left rear piping
(75×480)
110
60
60
01010
0
Wall hole for
right rear piping
Mount board
C
295
Refrigerant pipe : 9.52
Flared connection : 3/8F
Refrigerant pipe : 15.88
Flared connection : 5/8F
5
Knockout hole for
right piping
16 O.D
364
384.5
384
408.5
Indoor unit outline
439
454
465.5
439
449.2
216.5
R37.5
314
339
349.2
54
32
25
12.5
0
12.5
37.5
62.5
87.5
104.5
129.5
167
217
229.5
264
292
308.5
311
585
Min. 7
550 mm or greater with optional
265 mm or greater with optional
drain pump installation
drain pump installation
Air outlet
Min. 220 Min. 72.4
Min. 50.5
Min. 250
18
Page 19
PKA-RP35GAL PKA-RP50GAL Unit : mm
Knockout hole for
right piping
Refrigerant pipe.
Drain pipe.
Less than 15
Right side
Air intake
245
Air intake
21
198
70
Wiring hole
60
235
Auto vane
Knockout hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
60
70 35
235
160 40
80
Service panel
(Power supply access)
Terminal block to
outdoor unit
190
395 400
Terminal block for
power supply
(Heater (PKH-P35, 50GALH only))
31 280
(Right side piping
86
581 54
449
installation)
153
—
P35, 50
:6.35
RP35, 50
:9.52 —:15.88
:9.52
:12.7
:15.88
Air intake
715 225
Air intake
340 80 280 233
Front view
Left side
245
340
990
Air outlet
705
12-Louvers(manual)
53
21
70
Lower side
60
Right side
Knock out hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole.
Allowing clearances
Front view
79
50
Less than 130
180 or more 30 or more
(Necessary clearance for
unit installation)
Unit center
Installation plate
balance point hole
50 or more 150 or more
Details of installation plate
Filter grip
Front view(to open the grille)
190
230
R52.5
5
R52.
272
R52.5
310
322
495
345
320
260
205
150
95
35
0
20
32
75
135
190
245
300
360
405
495
0355580130
0
R52.5
(Flexible hose total length800)
700
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
Gas pipe
Liquid pipe
installation)
(Left side piping
35
425
Unit drain pipe O.D.20
190
170
0
Right-rear
piping hole
210
230
Knockout hole for
right-rear piping
420
GAS SIDE
LIQUID SIDE
+1 Sleeves are available on the market.
+2 This size shows the lower end of through hole.
:90~:100 :90
Through hole
: Initial flare nut size
Sleeve +1
35, 50
Model
19
for bolts
14-:14hole
49-:5hole
for tapping screw
Left-rear
piping hole
Knockout hole for
left-rear piping
Page 20
PKA-RP50FAL2 Unit : mm
PKA-RP60FAL
A
Left side
Knockout hole for
left piping
Drain hose for
left-hand side piping
340
25
235
552
45
Air outlet
235
1090
1110
To p
235
45
Front
1400
Air intake
Drain hose
Lower side
Auto vanes
1120
552
45
Air outlet
235
Liquid pipe
Display section
62.5
Receiving
section
13
Right side
235
197
Terminal block for indoor/outdoor connecting line
58
42
(Gas pipe)
55
120
183
(Liquid pipe)
Liquid pipe :9.52(3/8F)
240
Gas pipe :15.88(5/8F)
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
Power lamp
Knockout hole for right piping
Refrigerant pipe. Drain pipe
C
15
Bolt
107
111
Terminal block for heater (PKH only)
Gas pipe
Drain hose O.D.20
Wall fixture
66-ø6 hole for
tapping screw
32-ø12 hole for bolt
225
Under panel
Removable at left-hand
side piping
Unit center
990
10 91=(910)
900
18
18
Drainage range
on left-hand side
240 280 314
12-ø6 hole for
tapping screw
Drainage range
on right-hand side
180
Range for left rear piping opening
Knockout hole for under-piping
Refrigerant pipe. Drain pipe
245
455
285
19
91
610
Louvers (manual)
29 80
10
30 30
184 30
90
Rear piping opening
280
60
Sleeve +1
: 90
B
+ 1 Sleeves are available on the market.
Through hole
: 90~ : 100
Use the current nuts meeting
the pipe size of the outdoor unit.
Knockout hole for wiring
AB C
30
100
439
37
74
39
98
65
37
32
74
Available pipe size
RP60,71 / P60,71
:9.52
:15.88
LIQUID SIDE
GAS SIDE
RP50
:6.35
:9.52
:12.7
:15.88
30
100
39
37
4
20
: Initial flare nut size
Page 21
PKA-RP100FAL Unit : mm
Left side
A
Knockout hole for left piping
Drain hose for left-hand side piping
340
To p
Display section
62.5
Emergency switch(Heat)
235
235
45
235
45
235
45
Front
235
45
Knockout hole for right piping
Receiving
13
section
1680
Air intake
1370
197
Liquid pipe
Terminal block for indoor/outdoor connecting line
42
25
1400
Air outlet
694
1110
Drain hose
Drain hose
Lower side
Air outlet
694
183
240
(Gas pipe)
55
120
(Liquid pipe)
Emergency switch(Cool)
Defrosting Initial heating lamp
Power lamp
Right side
235
C
15
58
102
111
Terminal block for heater (PKH only)
Gas pipe
Bolt
Drain hose O.D.20
Available pipe size
Auto vane
Louvers (manual)
Under panel
(Removable at left-hand side piping)
Knockout hole for under-piping
Refrigerant pipe. Drain pipe
RP100
LIQUID SIDE
GAS SIDE
B
:Initial flare nut size
Use the current nuts meeting the pipe size
of the outdoor unit.
:9.52
:15.88
:19.05
P100
:9.52
:19.05
84-ø6 hole for
tapping screw
41-ø12 hole
for bolt
Unit out line
Wall fixture
18
18
Drainage range
on left-hand side
295 225
Unit center
1270
13 91=(1183)
240 280 314
595
900
Drainage range
on right-hand side
180
91
750
Range for left rear piping opening Range for left rear piping opening
12-ø6 hole for tapping screw
19
245
285
21
10
30 30
184 30
90
Rear piping opening
Knockout hole for wiring
29 80
280
60
AB C
30
100
439
37
74
39
98
65
37
32
74
30
100
39
37
4
Page 22
OUTDOOR UNIT Unit : mm
PUHZ-HRP71VHA
PUHZ-HRP100VHA
PUHZ-HRP100YHA
PUHZ-HRP125YHA
A
1,079
930
(19)
2-U Shaped notched holes
(Foundation Bolt M10)
600 175 175
Rear Air Intake
Installation Feet
Side Air Intake
417
330
A
28 370
53 56
45
42
66
2-12 x 36 Oval holes
(Foundation Bolt M10)
Air Discharge
30
Terminal connection
950
Earth terminal
322
Left···Power supply wiring
Right···Indoor/Outdoor wiring
Service panel
Handle for moving
635
1350
+1 447
+1 443
2
1
371
Front piping cover
Rear piping cover
71
71
23
Bottom piping hole
(Knockout)
81 219
HRP·VHA
Drain hole
(5-W 33)
145 145 220 30 145
HRP·YHA
Handle for moving
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
FOUNDATION
30
Over 150mm
Over 10mm
Less than
500
Over
10
Over
Over 10mm
r 1000mm
500
Over
Service space
Ove
Please secure the unit firmly
with 4 foundation (M10) bolts.
3 FOUNDATION BOLTS
Dimensions of space needed
for service access are
2 SERVICE SPACE
The diagram below shows a
basic example.
1 FREE SPACE (Around the unit)
<Foundation bolt height>
(Bolts and washers must be
purchased locally.)
150
Over
shown in the below diagram.
FREE
Explanation of particular details are
given in the installation manuals etc.
Side Air Intake
Rear Air Intake
Handle for moving
Handle for moving
Handle for moving
···Refrigerant GAS pipe connection (FLARE)W 15.88(5/8 inch)
···Refrigerant LIQUID pipe connection (FLARE)W 9.52(3/8 inch)
Example of Notes
+ 1 ···Indication of STOP VALVE connection location.
27Knockout)
W
Power supply wiring hole
(2-
Rear trunking hole
(Knockout)
92
W
45 40
Right trunking hole
(Knockout)
27Knockout)
W
40
Power supply wiring hole
(2-
Air intake
Right piping hole
(Knockout)
27Knockout)
W
Power supply wiring hole
(2-
Piping Knockout Hole Details
92
W
75
45
40
92
W
Front trunking hole
(Knockout)
27 92
73 63
Rear piping hole
(Knockout)
92
65
27 55
23 73 63
92
19 55
73 63
23
23
27 55
65
92
Front piping hole
(Knockout)
22
Page 23
PUHZ-HRP71VHA2
PUHZ-HRP100VHA2
PUHZ-HRP100YHA2
PUHZ-HRP125YHA2
Unit : mm
A
1,079
930
(19) 28 370
175
(Foundation Bolt M10)
2-U Shaped notched holes
600 175
Rear Air Intake
Installation Feet
Side Air Intake
417
330
A
2
Terminal connection
Right··· Indoor/Outdoor wiring
53 56
45
42
66
2-12 x 36 Oval holes
Air Discharge
30
Left ····Power supply wiring
(Foundation Bolt M10)
950
Earth terminal
322
Handle for moving
Service panel
Handle
for
moving
1
Handle for moving
635
1350
371
+1 447
+1 443
HRP·YHA2
Front piping cover
Rear piping cover
Bottom piping hole
(Knockout)
71
71
23
81 219
HRP·VHA2
Drain hole
(5- 33)
145 145 220 30 145
Piping and wiring connections
front, right, rear and below.
can be made from 4 directions:
4 PIPING-WIRING DIRECTIONS
FOUNDATION
30
Over
Over 150mm
Less than
500
Over
10
Ove
500
Over
Service space
r 10mm
(Bolts and washers must be
shown in the below diagram.
purchased locally.)
150
Over
FREE
<Foundation bolt height>
Please secure the unit firmly
with 4 foundation (M10) bolts.
3 FOUNDATION BOLTS
Dimensions of space needed
for service access are
2 SERVICE SPACE
Side Air Intake
Rear Air Intake
Handle for moving
9.52(3/8 inch)
Handle for moving
Handle for moving
Power supply wiring hole
(2- 27Knockout)
Rear trunking hole
(Knockout)
40
45
Right trunking hole
(Knockout)
27Knockout)
Power supply wiring hole
(2-
Air intake
75 40
(Knockout)
Right piping hole
45 40
27Knockout)
(2-
Power supply wiring hole
92
92
73 63
92
(Knockout)
Rear piping hole
92
65
27 55
23 73 63
92
19 55
73 63
23 27 92
23
27 55
65
92
given in the installation manuals etc.
basic example.
Explanation of particular details is
The diagram below shows a
1 FREE SPACE (Around the unit)
Over 10mm
Over 1000mm
···Refrigerant LIQUID pipe connection (FLARE)
···Refrigerant GAS pipe connection (FLARE) 15.88(5/8 inch)
Example of Notes
1 ···Indication of STOP VALVE connection location.
23
Piping Knockout Hole Details
(Knockout)
Front trunking hole
Front piping hole
(Knockout)
Page 24
4
WIRING DIAGRAM
4-1. INDOOR UNIT
PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA PLA-RP100BA PLA-RP125BA
PLA-RP71BA2 PLA-RP100BA2 PLA-RP100BA3 PLA-RP125BA2
[LEGEND]
SYMBOL SYMBOL NAME NAME
I.B
DCL
DP
FS
INDOOR CONTROLLER BOARD
CN2L
CONNECTOR (LOSSNAY)
CN32
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CN41
CN51
CONNECTOR (CENTRALLY CONTROL)
FUSE
FUSE (T6.3AL250V)
LED1
POWER SUPPLY (I.B)
LED2
POWER SUPPLY (R.B)
LED3
TRANSMISSION (INDOOR-OUTDOOR)
SW1
SWITCH (MODEL SELECTION) + See table 1
SW2
SWITCH (CAPACITY CODE) + See table 2
SWE
CONNECTOR (EMERGENCY OPERATION)
X1
RELAY (DRAIN PUMP)
REACTOR
DRAIN PUMP
DRAIN FLOAT SWITCH
FAN MOTOR
MF
VANE MOTOR
MV
TB2
TERMINAL BLOCK (Indoor unit Power (option))
TB4
TERMINAL BLOCK (
TERMINAL BLOCK (REMOTE CONTROLLER
TB5,TB6
TRANSMISSION LINE)
TH1
ROOM TEMP. THERMISTOR
(0 / 15k , 25 / 5. 4k DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0 / 15k , 25 / 5. 4k DETECT)
TH5
COND. / EVA. TEMP. THERMISTOR
OPTION PART
(0 / 15k , 25 / 5. 4k DETECT)
PCB FOR WIRELESS REMOTE CONTROLLER
W.B
BZ
BUZZER
LED1
LED (OPERATION INDICATION : GREEN)
LED2
LED (PREPARATION FOR HEATING : ORANGE)
RECEIVING UNIT
RU
SW1
EMERGENCY OPERATION (HEAT / DOWN)
SW2
EMERGENCY OPERATION (COOL / UP)
INDOOR/OUTDOOR CONNECTING LINE
Refer to tables 1 and 2
TB5
1
J42 J41
CN51(WHT)
Pair No.
51
ON OFF
AUTO GRILLE
POWER
CNAC
(WHT)
31
3
CN3G
TRANSMISSION
WIRES
DC12V
CN32
(WHT)
113
CN41(WHT)
41
SWE
FLOAT SW
CN4F
(WHT)
4
FS
1 31 35
CN3A
I.B
VAN E
18
20
19
3
1 3
AUTO GRILLE
CN3G
11 4 1 6 9
(BLK)
5 5 5 5
MMMM
MV
MV MV MV
GRILLE
CNV(
WHT)
WIRELESS
CN90
(WHT)
9
CNB
SW1
SW2
1234567891011121314151617
BZ
LED2
LED1
RU
W.B
LED3 LED2 LED1
I-SEE SENSOR
SENSOR MOTOR
CN4Y
(WHT)
4 5
I-SEE
M
SENSOR
MT
I-SEE SENSOR
CORNER PANEL
(OPTION PART)
2
TB6
R.B
SW2 SW1
CN2L
21
I-SEE
CN6Y
(RED)
U.B
AUTOMATIC FILTER ELEVATION PANEL
(OPTION PART)
2
1
INDOOR/OUTDOOR
COMMUNICATION
2 1
REMOCON
CN22
(BLU)
LIQUID/PIPE
CN44
(WHT)
14
t° t° t°
TH2 TH5 TH1
<Table 1> SW1 (MODEL SELECTION)
MODELS
PLA-RP·BA
PLA-RP71/100/125BA2
)
PLA-RP140BA2
PLA-RP100BA3
<Table 2> SW2 (CAPACITY CODE)
CAPACITY
35
50
60
71
The black square ( ) indicates a switch position.
OUTDOOR
135
CN01
FAN
CNMF
(WHT)
MS
MF
(BLK)
–
+
31
M
1~
3~
DP
3
1
CN3C
(BLU)
INTAKE
CN20
(RED)
74 1
2 1
+ Be sure to turn off the source power
and then disconnect fan motor connector.
(Failure to do so will cause trouble in Fan motor)
X1
D.U.M
(BLU)
CNP
SW1
SETTING
12345
12345
12345
12345
YLW
FUSE
SETTING
12345
ON
OFF
12345
ON
OFF
12345
ON
OFF
SW2
CAPACITY
SETTING
12345
100
ON
OFF
125
ON
OFF
140
ON
OFF
ON
OFF
DCL
Please set the voltage using the
remote controller.
For the setting method,please refer to
the indoor unit Installation Manual.
YLW
ORN
ORN
BRN
12345
12345
TB4
YLW
ORN
S1
S2
S3
ON
OFF
ON
OFF
ON
OFF
TO OUTDOOR
UNIT
Notes:
1.SymboIs used in wiring diagram above are, : Connector,
: Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make
sure to match terminal numbers (S1, S2, S3) for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check
the outdoor unit electric wiring diagram for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting
wires.(specification of 230V), adopting superimposed system for
power and signal.
+ 1:If indoor and outdoor units have separate power supplies,
refer to Fig. 1.
+ 2:For power supply system of this unit, refer to the caution label
located near this diagram.
+ 1(Fig. 1)
CN01
(BLK)
5
3
1
I.B
CN3C
(BLU)
31
I.B
YLW
ORN
INDOOR/OUTDOOR
COMMUNICATION
RED
BLU
GRN/YLW
YLW
ORN
ORN
BRN
24
TB2
TB4
S1
S2
S3
L
N
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR UNIT
Page 25
MS
3~
342
1
124
3
1
2
1
3
5
1
124
3
2
1
542
3
3214
2
1
2
1
4
1
3
1~
M
45671 211 2 3
35 1
213
4
1
2
INSIDE SECTION OF CONTROL BOX
I.B.
P.B.
Drainpump
Fan motor
X10
SW6
SW5
B
CN4F
CN4F
FS
FOR PEAD-RP·JA
REFER TO "B" FOR PEAD-RP·JAL
ONLY FOR PEAD-RP·JA
(Blue)
(Blue)
(Red)
(Blue)
(Red)
CN2A
2
1
LED3
CN3C
(Blue)
TB15
2
1
S3
TO CN3C
TO OUTDOOR
UNIT
TO CND
S3
1
S2
S1
L
N
<A>
2
ACL
1
2
(Blue)
SW2
SW1
CN22
CN2L
TB4
S1
S2
TH1
t˚
TH5
TH2
t˚ t˚
CNXA2
CNXB1
LED1
LED2
U
DC280-340V
Rectifier circuit
U
(Red)
X01
CNMF CNXA1 CNXC1
CNP
ACL
CN32
SWE
CN20
CN90
CN105
CN41
CN51
CNXB2
CNXC2
F01
DSA
ZNR02
CND
ZNR01
(Red)
CN44
(Black)
OFF
ON
(IN CASE OF CONNECT
THE REPLACEMENT WIRING)
POWER SUPPLY
~ (1PHASE)
220-240V 50Hz
A
TO MA REMOTE
CONTROLLER
TO OUTDOOR UNIT
Connector (0-10V Analog input)
Connector (IT terminal)
Connector (Wireless)
Indoor controller board
Varistor
Aux. relay
Fuse AC250V 6.3A
Connector (Centrally control)
Connector (HA terminal-A)
LED(Remote controller supply)
Indoor controller board
Connector (Remote switch)
LED(Transmission indoor-outdoor)
Arrester
Intake air temp. Thermistor
Pipe temp. Thermistor/liquid
Cond./eva.temp. Thermistor
AC reactor (Power factor improvement)
Connector (Lossnay)
LED(Power supply)
Terminal block
(Remote controller transmission line)
Terminal block
Float switch
(Indoor/outdoor connecting line)
Power supply board
Aux. relay
Switch (for model selection)
Switch (for capacity code)
Switch (for model selection)
Switch (for model selection)
Connector (emergency operation)
CN2A
CN2L
CN32
CN41
CN51
CN90
CN105
LED1
LED2
LED3
I.B.
I.B.
P. B .
SW1
SW2
SW5
SW6
SWE
F01
ZNR01, 02
DSA
X01
X10
TH1
TH2
TH5
ACLFSTB4
TB15
SYMBOL
NAME
SYMBOL
NAME
SYMBOL
NAME
SYMBOL EXPLANATION
NOTE: 1. Since the outdoor side electric wiring may change, be sure to
check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities,
make wiring matching terminal numbers (S1,S2,S3).
3. Symbols used in wiring diagram above are, terminal block,
connector.
<Table 1> SW1 (MODEL SELECTION)
<Table 2> SW2 (CAPACITY CODE)
SETTING
CAPACITY
SW2
100
ON
OFF
12345
50
35
ON
OFF
12345
ON
OFF
12345
125
ON
OFF
12345
60
ON
12345
OFF
OFF
140
ON
OFF
12345
71
ON
12345
CAPACITY
SETTING
SW1
PEAD-RP·JA(L)
MODELS
ON
OFF
12345
The black square ( ) indicates a switch position.
SW5
ON
OFF
12345
SW6
ON
OFF
12
678
PEAD-RP35JA(L) PEAD-RP50JA(L) PEAD-RP60JA(L) PEAD-RP71JA(L)
PEAD-RP100JA(L) PEAD-RP125JA(L)
25
Page 26
PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA
PEAD-RP100EA2 PEAD-RP125EA
[LEGEND]
SYMBOL
I.B.
INDOOR CONTROLLER BOARD
FUSE
FUSE(T6.3AL250V)
ZNR
VAR IST OR
CN2L
CONNECTOR(LOSSNAY)
NAME
CN24 CONNECTOR(HEATER)
CN32
CONNECTOR(REMOTE SWITCH)
CN41
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
CN51
CONNECTOR(WIRELESS) DP
CN90
POWER SUPPLY(I.B.)
LED1
LED2
POWER SUPPLY(REMOTE CONTROLLER)
LED3
TRANSMISSION(INDOOR·OUTDOOR)
SW1
SWITCH(MODEL SELECTION)
TO MA-REMOTE
CONTROLLER
DC8.7-13V
TO OUTDOOR UNIT
WHT
BLK
SWITCH(CAPACITY CODE)
SW2
SWITCH(EMERGENCY OPERATION)
SWE
RELAY(DRAIN PUMP)
X1
RELAY(FAN MOTOR)
X4
RELAY(FAN MOTOR)
X5
RELAY(FAN MOTOR)
X6
P. B .
INDOOR POWER BOARD
DRAIN PUMP
(OPTIONAL PARTS)
DRAIN PUMP
DRAIN SENSOR
DS
C
CAPACITOR(FAN MOTOR)
MF
FAN MOTOR
TERMINAL BLOCK TB4
(INDOOR/OUTDOOR CONNECTING LINE)
TB5
TERMINAL BLOCK(REMOTE CONTROLLER)
TH1
INTAKE AIR TEMP. THERMISTOR
(0 /15k , 25 /5.4k DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0 /15k , 25 /5.4k DETECT)
TH5
COND./EVA. TEMP. THERMISTOR
(0 /15k , 25 /5.4k DETECT)
INSIDE SECTION OF CONTROL BOX
DS
TH5 TH2 TH1
1
SYMBOL SYMBOL
B
B
L
L
U
U
1
1
2
2
CN20 CN21 CN29
CN22
(RED)
(BLU)
1
2
CN2L
(RED)
LED1
LED2
LED3
2
CN2D
1
(WHT)
(BLU)
CN3C
(ORN)
CND
31
B
O
R
R
N
N
B
TB5
L
B
U
2
1
TB4
S3
BRN
ORN
S2
S1
YLW
+ A
L
U
1
(WHT)
31
O
R
N
2
1
2
(BLK)
FUSE
Y
L
W
W
H
T
1
3
CN31
123456789 4 3214 5 321
12
2
3
CN31
(WHT)
CN90
(WHT)
CN41
(WHT)
12
CN24
(YLW)
X1
ZNR
(RED)
CNDK
W
B
H
L
T
K
B
L
K
2
1
CN2S
(WHT)
W
H
T
31
B
L
K
P. B .
CNSK
(RED)
X1
(BLU)
CNP
1 3 31
DP
Optional parts
<PEAD-RP35·50·60EA, 35EA2>
External static pressure 70Pa
(RED)
NAME NAME
I.B.
321
CN51
(WHT)
CN32
(WHT)
SW1
SW2
SWE
ON
OFF
X6 X5 X4
X5
X4
X6
1 3 75
(WHT)
W
H
T
6 435 21
FAN
P
P
B
N
N
L
K
K
K
<PEAD-RP35·50·60EA, 35EA2>
External static pressure 30Pa
<PEAD-RP71·100·125·140EA, 100EA2>
External static pressure 70Pa
6 435 21
(WHT)
Optional parts
6 435 21
(RED)
MF
MF
C
C
<PEAD-RP71·100·125·140EA, 100EA2>
External static pressure 130Pa
SW1
MODELS
Model selection
switch
35EA(2)
50EA
60EA
71EA
100EA(2)
125EA
140EA
The black square ( ) indicates
a switch position.
54321
ON
OFF
SW2
Capacity cord
switch
12345
12345
12345
12345
12345
12345
12345
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
<+ A>
(IN CASE OF CONNECTING
THE REPLACEMENT WIRING)
POWER SUPPLY
L
~(1PHASE)
N
12
TO CND
21
12
TO CN3C
230V 50Hz
S1
S2
TO OUTDOOR
S3
UNIT
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification
of 230V), adopting superimposed system for power and signal.
+ 1: If indoor and outdoor units have separate power supplies, refer to +A.
+ 2: For power supply system of this unit, refer to the caution label located near this diagram.
26
Page 27
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
[LEGEND]
SYMBOL
I.B.
INDOOR CONTROLLER BOARD
FUSE
FUSE(T6.3AL250V)
ZNR
VAR ISTO R
CONNECTOR(LOSSNAY)
CN2L
CN24 CONNECTOR(HEATER)
CN32
CONNECTOR(REMOTE SWITCH)
CN41
CONNECTOR(HA TERMINAL-A)
CN51
CONNECTOR(CENTRALLY CONTROL)
CONNECTOR(WIRELESS)
CN90
POWER SUPPLY(I.B.)
LED1
LED2
POWER SUPPLY(REMOTE CONTROLLER)
LED3
TRANSMISSION(INDOOR·OUTDOOR)
NAME
WHT
BLK
B
L
U
CN22
(BLU)
LED1
LED2
LED3
2
1
SW1
SW2
SWE
X1
X4
X5
X6
P. B .
C
MF
TB4
B
L
U
1
1
O
R
N
2
CN2D
(WHT)
(BLU)
CN3C
31
B
R
N
1
2
2
CN20 CN21
(RED)
1
2
CN2L
(RED)
CN29
(BLK)
(WHT)
FUSE
CND CNDK
31
Y
O
L
R
W
N
SWITCH(MODEL SELECTION)
SWITCH(CAPACITY CODE)
SWITCH(EMERGENCY OPERATION)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
INDOOR POWER BOARD
CAPACITOR(FAN MOTOR)
FAN MOTOR
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
INSIDE SECTION OF CONTROL BOX
TH5 TH2 TH1
1
12
2
3
CN31
(WHT)
ZNR
W
H
T
123456789
CN90
(WHT)
B
L
K
X1
321
4
CN41
(WHT)
X1
(BLU) (RED) (ORN)
CNP
1 3 31
SYMBOL SYMBOL
TERMINAL BLOCK(REMOTE CONTROLLER)
TB5
TH1
INTAKE AIR TEMP.THERMISTOR
(0 /15k , 25 /5.4k DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0 /15k , 25 /5.4k DETECT)
TH5
COND./EVA. TEMP. THERMISTOR
(0 /15k , 25 /5.4k DETECT)
1
CN24
(YLW)
2
CN51
(WHT)
G
R
Y
54321
X5
X4
5
Y
Y
L
L
W
W
NAME NAME
I.B.
21
3
CN32
(WHT)
SW1
SW2
SWE
ON
OFF
X6 X5 X4
X6
1 3 7
(WHT)
FAN
B
L
K
B
W
W
B
L
H
K
T
B
TB5
L
TO MA-REMOTE
CONTROLLER
DC8.7-13V
TO OUTDOOR UNIT
<+ A>
(IN CASE OF CONNECT
THE REPLACEMENT WIRING)
12
2 1
TO CND
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for
power and signal.
+ 1: If indoor and outdoor units have separate power supplies, refer to +A.
+ 2: For power supply system of this unit, refer to the caution label located near this diagram.
12
TO CN3C
2
1
TB4
S3
S2
S1
B
U
L
U
BRN
ORN
YLW
POWER SUPPLY
L
~(1PHASE)
N
230V 50Hz
S1
S2
TO OUTDOOR
S3
UNIT
+ A
2
21
MODELS
100GA
The black square ( ) indicates a switch position.
1
CN2S
(WHT)
60GA
71GA
L
H
K
T
P. B .
1 3
CNSK
(RED)
Model selection
switch
54321
ON
OFF
SW2 SW1
Capacity cord
switch
12345
12345
12345
ON
OFF
ON
OFF
ON
OFF
B
L
U
MF
C
B
O
L
R
K
G
*External static pressure
*
CONNECTOR COLOR
6 435 21
(WHT)
BLU
WHT
(INITIAL SETTING)
RED
5Pa
35Pa
10Pa
50Pa
70Pa 50Pa
240V 230V 220V
20Pa
60Pa
75Pa
27
Page 28
PKA-RP35HAL PKA-RP50HAL
[Explanation of symbols]
Symbol
I.B Indoor controller board
CN2L Connector (LOSSNAY)
CN32 Connector ( Remote switch)
CN41 Connector (HA terminal-A)
CN51 Connector (Centrally control)
CN90 Connector (Remote operation adapter)
FUSE FUSE(T3.15AL250V)
LED1 Power supply (I.B)
LED2 Power supply (R.B)
LED3 Transmission (Indoor-outdoor)
SW1 Switch (Model selection) + See table 1
SW2
Switch (Capacity code) + See table 2
Connector (Emergency operation)
SWE
X1 Relay (Drain pump (option))
Drain pump (option) power supply (Drain pump (option))
CNP
CN4F Drain float switch (Drain pump (option))
R.B
Wired remote controller(option)
TB6
Terminal block (Remote controller transmission line)
Name
Symbol
M Vane motor
MS Fan motor
S.W
TB2 Terminal block(Indoor unit Power (option))
TB4 Terminal block (Indoor/outdoor connecting line)
TB5
TH1 Room temp. Thermistor
TH2
TH5
W.B PCB for wireless remote controller
DCL REACTOR
Switch board
SWE2 Emergency operation
Terminal block (Remote controller transmission line(option))
(0 /15k , 25 /5.4k Detect)
Pipe temp. Thermistor/liquid
(0 /15k , 25 /5.4k Detect)
Cond./eva. temp. Thermistor
(0 /15k , 25 /5.4k Detect)
LED1 LED (Operation indication : Green)
LED2 LED (Preparation for heating: Orange)
REC1 Receiving unit
DRAIN PUMP (OPTION)
DP
DRAIN FLOAT SWITCH (OPTION)
FS
Name
MS
3~
DCL
I.B
CNMF
6
(WHT)
FUSE
CN01
(BLK)
3
X1
1
CNP(BLU)
3
CN3C
(BLU)
1
LDSWE(A)
(BLU)
CNRU
(WHT)
1
CN22
(BLU)
2
When attaching drain
pump (option)
FLOAT SW
CN4F
(WHT)
1
3
5
14
6
FS
ORN
BLK
DP
M
1~
ORN
BRN
W.B
LD101(B)
YLW YLW YLW
LED1
ORN
2
RU
REC1
LED2
TB4
TO
S1
OUTDOOR
S2
UNIT
S3
S.W
LDSWE(B)
SWE2
+
CN01
(BLK)
1
3
5
(OPTION PARTS)
1(Fig. 1)
I.B
YLW
ORN
SWE
ON
OFF
Refer to
tables
1and 2
CN151
(WHT)
11
M
T11 DB1
LED1
LED3
LED2
CN90
(WHT)
11 1 5
2
CN2L
(RED)
CN20
(RED)
t
TH1 TH2 TH5
CN41
(WHT)
CN44
(WHT)
14 14 2 5
tt
4
1
1 13 9
CN32
(WHT)
CN51
(WHT)
CN4F
(WHT)
When attaching
drain pump(option),
remove the jumper
connector CN4F
and fit the drain
float switch (FS).
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
I.B
1
CN3C(BLU)
4. This diagram shows the wiring of indoor and outdoor connecting wires. (specification of
230V), adopting superimposed system for power and signal.
+
1:
If indoor and outdoor units have separate power supplies
+
2: For power supply system of this unit, refer to the caution label located near this diagram.
, refer to Fig 1.
<Table 1>
SW1
(MODEL SELECTION)
SETTING
12345
<Table 2>
SW2 (CAPACITY CODE)
MODELS
RP35
RP50
The black square ( ) indicates
a switch position.
BLU
1
BLU
2
TB5
GRN/YLW
INDOOR/OUTDOOR
3
COMMUNICATION
RED
BLU
YLW
ORN
ORN
BRN
R.B
TB6
TB2
TB4
S1
S2
S3
1
2
L
N
ON
OFF
SETTING
12345
12345
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR
UNIT
ON
OFF
ON
OFF
28
Page 29
PKA-RP60KAL PKA-RP100KAL
[LEGEND]
SYMBOL SYMBOL NAME NAME
I.B
CN2L
CN32
CN41
CN51
CN90
FUSE
LED1
LED2
LED3
SW1
SW2
SWE
X1
CNP
CN4F
R.B
TB6
Indoor controller board
Connector (LOSSNAY)
Connector (Remote switch)
Connector (HA terminal-A)
Connector (Centrally control)
Connector (Remote operation adapter)
FUSE (T3.15AL250V)
Power supply (I.B)
Power supply (R.B)
Transmission (Indoor-outdoor)
Switch (Model selection) + See table 1
Switch (Capacity code) + See table 2
Connector (Emergency operation)
Relay (Drain pump(option))
Drain pump (option) power supply (Drain pump(option))
Drain float switch (Drain pump (option))
Wired remote controller
Terminal block (Remote controller transmission line)
MF
M
MS
S.W
TB2
TB4
TB5
TH1
TH2
TH5
W.B
DCL
DP
Vane motor
Fan motor
Switch board
Emergency operation
SWE2
Terminal block (Indoor unit Power (option))
Terminal block (Indoor/outdoor connecting line)
Terminal block
Room temp. Thermistor
(0 / 15k , 25 / 5. 4k Detect)
Pipe temp. Thermistor/liquid
(0 / 15k , 25 / 5. 4k Detect)
Cond. / eva. temp. Thermistor
(0 / 15k , 25 / 5. 4k Detect)
PCB for wireless remote controller
LED1
LED (Operation indication : Green)
LED2
LED (Preparation for heating : Orange)
Receiving unit
REC1
REACTOR
DRAIN PUMP (OPTION)
DRAIN FLOAT SWITCH (OPTION)
FS
(Remote controller transmission line)
+ 1(Fig. 1)
CN01
I.B
(BLK)
1
3
5
I.B
3 1
CN3C (BLU)
YLW
ORN
INDOOR/OUTDOOR
COMMUNICATION
RED
BLU
GRN/YLW
YLW
ORN
ORN
BRN
The black square ( ) indicates a switch position.
Notes:
1. SymboIs used in wiring diagram above are, :Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers
(S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric
wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V),
adopting superimposed system for power and signal.
+ 1
If indoor and outdoor units have separate power supplies
, refer to Fig 1.
+ 2 For power supply system of this unit, refer to the caution label located near this diagram.
TB2
TB4
S1
S2
S3
L
N
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR
UNIT
29
Page 30
PKA-RP35GAL PKA-RP50GAL
[LEGEND]
SYMBOL NAME
P. B
I.B
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE FUSE (T6.3AL250V)
ZNR VARISTOR
CN2L CONNECTOR <LOSSNAY>
CN32 CONNECTOR <REMOTE SWITCH>
CN41 CONNECTOR <HA TERMINAL-A>
CN51 CONNECTOR <CENTRALLY CONTROL>
SW1 SWITCH <MODEL SELECTION>+ See Table 1.
SW2 SWITCH <CAPACITY CODE>+ See Table 2.
SWE SWITCH <EMERGENCY OPERATION>
X4 RELAY <FAN MOTOR>
BCR
FAN CONTROL ELEMENT
LED1 POWER SUPPLY <I.B>
POWER SUPPLY <R.B>
LED2
TRANSMISSION <INDOOR-OUTDOOR> LED3
P. B
CNDK
(RED)
1
MF
1
2 3
C
WHT
RED
I.B
1 3 5
FAN
(
)
WHT
BCR
SW2 SW1
SWE
ON
OFF
Refer to tables 1
and 2 for service PCB.
BLK
X4
X4
POWER
CNDK
(RED)
2
3
WHT
RED
LED3 LED2 LED1
PKH-P35,50GALH models only
HEATER
CN24
1
2
(YLW)
I.B
YLW
YLW
61
88H
26H
RED
6
RED GRY
5
DC13.1V
POWER
CND
(ORN)
ZNR
H1
SYMBOL NAME
C CAPACITOR <FAN MOTOR>
MF
MV
TB2
TB4
TB5,TB6
TH1
TH2
TH5
CN2S
(WHT)
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (HEATER) +PKH-P.GALH
models only or option for PKA-RP.GAL models.
TERMINAL BLOCK <INDOOR/ OUTDOOR
CONNECTING LINE>
TERMINAL BLOCK <REMOTE CONTROLLER
TRANSMISSION LINE> <OPTION>
ROOM TEMP.THERMISTOR
<0/ 15k, 25 / 5.4k DETECT>
PIPE TEMP.THERMISTOR/ LIQUID
<0/ 15k, 25 / 5.4k DETECT>
COND./ EVA.TEMP.THERMISTOR
<0/ 15k, 25 / 5.4k DETECT>
1
2
YLW
ORN
BLK
WHT
1 3 1 3 1 3 1 2
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
CN41 CN2L
CN51 CN32
PIPE
CN29
)
(
BLK
1 2
TH2
1
WHT
2
GRN/YLW
)
TH5 TH1
88H
FUSE
INTAKE
CN20
(
)
RED
1 2
FS1
POWER
CN2D(WHT)
LIQUID
CN21
(
WHT
1 2
FS2
TB4
YLW
ORN
ORN
BRN
VAN E
CN6V
(
GRN
WIRELESS
CN90
(
WHT
REMOCON
CN22
(
)
BLU
1 2
TB2
L
RED RED 5 3 RED
N
BLU
W.B
R.B
HEATER
S1
TO
S2
OUTDOOR
S3
UNIT
MV
I.B
POWER
CND
(ORN)
6
)
)
2
TRANSMISSION WIRES DC12V
1
TB5
Please set the voltage using the
POWER SUPPLY
~(1PHASE)
230V 50Hz
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
RU
BZ
BUZZER
LED1
LED <RUN INDICATOR>
LED2
LED <HOT ADJUST>
SW1
SWITCH (HEATING ON/ OFF>
SW2
SWITCH (COOLING ON/ OFF>
WIRED REMOTE CONTROLLER BOARD
THERMAL FUSE <104
FS1
THERMAL FUSE <8410A>
FS2
HEATER
H1
HEATER THERMAL SWITCH
26H
HEATER CONTACTOR
88H
NAME SYMBOL
10A>
+ 1 (Fig.1)
TB2
RED
BLU
GRN/YLW
TB4
YLW
ORN
ORN
YLW
ORN
BRN
L
N
S1
S2
S3
POWER
SUPPLY
~(1PHASE)
230V 50Hz
TO
OUTDOOR
UNIT
3 1 3 1
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
9
CNB
BZ
RU
RECEIVER
LED1 LED2 SW2 SW1
W.B
R.B
1
TB6
2
SW1
Service board
1 2 3 4 5
The black square ( ) indicates a switch position.
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for
power and signal.
+ 1: If indoor and outdoor units have separate power supplies, refer to Fig 1.
+ 2: For power supply system of this unit, refer to the caution label located near this diagram.
MODELS
PKA-RP35GAL
ON
PKH-P35GALH
OFF
Service board Service board
1 2 3 4 5
SW2
MODELS
PKA-RP50GAL
ON
PKH-P50GALH
OFF
1 2 3 4 5
ON
OFF
30
Page 31
PKA-RP50FAL2 PKA-RP60FAL PKA-RP100FAL
[LEGEND]
SYMBOL NAME
P. B
I.B
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE FUSE(T6.3AL250V)
ZNR VARISTOR
CN2L CONNECTOR(LOSSNAY)
CN32 CONNECTOR(REMOTE SWITCH)
CN41 CONNECTOR(HA TERMINAL-A)
CN51 CONNECTOR(CENTRALLY CONTROL)
SW1 SWITCH (MODEL SELECTION)
SW2 SWITCH (CAPACITY CODE)
SWE SWITCH(EMERGENCY OPERATION)
X4 RELAY(FAN MOTOR)
BCR
FAN CONTROL ELEMENT
LED1 POWER SUPPLY(I.B)
POWER SUPPLY(R.B)
LED2
TRANSMISSION(INDOOR-OUTDOOR) LED3
P. B
MF
1
2 3
C
BLK
WHT
RED
I.B
X4
POWER
CNDK
(RED)
FAN
(
WHT
BCR
1 3 5
)
X4
LED3 LED2 LED1
SW2 SW1
SWE
ON
OFF
Refer to tables 1
and 2 for service PCB.
Table 1
SW1
Service board
1 2 3 4 5
The black square ( ) indicates a switch position.
ON
OFF
+
See Table 1.
+
See Table 2.
CNDK
(RED)
1
DC13.1V
2
3
WHT
RED
POWER
(ORN)
Table 2
MODELS
PKA-RP50FAL2
PKA-RP60FAL
PKH-P60FALH
SYMBOL NAME
CND
C CAPACITOR(FAN MOTOR)
MF
MV
TB2
TB4
TB5
TH1
TH2
TH5
CN2S
(WHT)
YLW
ORN
FUSE
ZNR
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (HEATER)
models only or option for PKA-RP.FAL models.
TERMINAL BLOCK(INDOOR/OUTDOOR
CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )(OPTION)
ROOM TEMP.THERMISTOR
/15k, 25/5.4k DETECT)
(0
PIPE TEMP.THERMISTOR/LIQUID
/15k, 25/5.4k DETECT)
(0
COND./EVA.TEMP.THERMISTOR
(0
/15k, 25/5.4k DETECT)
Please set the voltage
using the remote controller.
For the setting method,
1
2
BLK
please refer to the indoor
unit Installation Manual
WHT
1 3 1 3 1 3 1 2
POWER
CN2D(WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
CN41 CN2L
CN51 CN32
LIQUID
INTAKE
CN21
CN20
(
(
RED
1 2
)
)
WHT
1 2
TH2
Service board Service board Service board
1 2 3 4 5
ON
OFF
PIPE
CN29
(
)
BLK
1 2
TH5 TH1
MODELS
PKA-RP71FAL
PKH-P71FALH
REMOCON
CN22
(
PKH-P60 P100FALH models only
TB4
YLW
ORN
ORN
BRN
VAN E
CN6V
(
GRN
WIRELESS
CN90
(
WHT
)
BLU
1 2
SW2
1 2 3 4 5
W.B
RU
BZ
LED1
LED2
SW1
SW2
R.B
TB6
HEATER
FS1,2
H1
26H
88H
I.B
POWER
CND
(ORN)
)
+
PKH-P.FALH
S1
S2
S3
TO
OUTDOOR
UNIT
6
MV
)
2
TRANSMISSION WIRES DC12V
1
TB5
MODELS
PKA-RP100FAL
ON
PKH-P100FALH
OFF
RED
BLU
GRN/YLW
YLW
ORN
ORN
BRN
NAME SYMBOL
10A:60,71FALH/
TB2
L
N
TB4
S1
S2
S3
POWER
SUPPLY
(1PHASE)
230V 50Hz
TO
OUTDOOR
UNIT
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR )
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
WIRED REMOTE CONTROLLER BOARD(OPTION)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
THERMAL FUSE(117
117
16A:100FALH)
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
+
1 (Fig.1)
YLW
ORN
3 1 3 1
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
9
CNB
BZ
RU
RECEIVER
1 2 3 4 5
LED1 LED2 SW2 SW1
R.B
ON
OFF
1
2
W.B
TB6
HEATER
CN24
1
2
I.B
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for
power and signal.
+ 1: If indoor and outdoor units have separate power supplies, refer to Fig 1.
+ 2: For power supply system of this unit, refer to the caution label located near this diagram.
(YLW)
YLW
YLW
61
88H
26H
RED
6
RED GRY
5
H1
FS1
FS2
WHT
RED RED 5 3 RED
BLU
TB2
L
N
POWER SUPPLY
(1PHASE)
230V 50Hz
88H
1
2
GRN/YLW
31
Page 32
4-2. OUTDOOR UNIT
PUHZ-HRP71VHA PUHZ-HRP100VHA
[LEGEND]
SYMBOL
TB1
MC
MF1, MF2
21S4
63H
63L Low Pressure Switch
SV
TH3,TH32,TH33
TH4
TH6
TH7
TH8
LEV-A, LEV-B,LEV-C
DCL
ACTM
CB
CY1,CY2
Terminal Block<Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Solenoid Valve (Bypass Valve)
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<Heatsink>
Electronic Expansion Valve
Reactor
Active Filter Module
Main Smoothing Capacitor
Capacitor
NAME SYMBOL NAME SYMBOL NAME
P. B.
TABU/V/W
TABS/T
TABP1/P2/P
TABN1/N2/N
DS2, DS3
IPM
N.F.
LI / LO
NI / NO
EI, E2
52C
C.B.
SW1
SW4
SW5
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal <L/N-Phase>
Connection Terminal<DC Voltage>
Connection Terminal<DC Voltage
Diode Bridge
Power Module
Noise Filter Circuit Board
Connection Terminal<L-Phase>
Connection Terminal<N-Phase>
Connection Terminal<Ground>
52C Relay
Controller Circuit Board
<Forced Defrost, Defect History Record
Switch
Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
SW6
SW7
SW8
SW9
>
SWP
CN31
SS
CNM
CNMNT
CNVMNT
CNDM
LED1,LED2
F1~F4
X51,X52,X55
Switch<Model Select>
Switch<Function Setup>
Switch<Function Setup>
Switch
Switch<Pump Down>
Connector<Emergency Operation>
Connector<Connection for Option>
Connector
<A-Control Service Inspection Kit
Connector
<Connected to Optional M-NET Adapter Board
Connector
<Connected to Optional M-NET Adapter Board
Connector
< Connected for Option (Contact Input)>
LED<Operation Inspection Indicators>
Fuse< T6.3AL250V >
Relay
>
>
>
MF1
MF2
MS
3~
MS
3~
C. B.
1
1
LEV-C
M
LEV-B
5
6
1
LEV-B
(RED)
1 3 1 3 1 3
X52
5
1
LEV-C
(BLU)
CNVMNT
(WHT)
6
SV 21S4
3
3 1
CNM
(WHT)
X55
SV2
(BLU)
CNMNT
(WHT)
CN52C
(RED)
5
+1+
1
5 1
SW5 SW8 SW4 SWP
SW6 SW1
14 1
CN31
221
X51
SS
(WHT)
3 1
CN2
63L
63L
(RED)
3 1
LED2
7 1
7
LEV-A
MM
6 1
LEV-A
(WHT)
LED1
CN4
(WHT)
21
2
21S4
(GRN)
TH3
(WHT)
2 1
4 3
°
t
°
TH4
(WHT)
63H
63H
(YLW)
F3
F4
(WHT)
TH7 TH6 TH3 TH4
TH32
TH33
t
°
t
°
7
CNF1
(WHT)
7
CNF2
(WHT)
3
2
CNDC
1
(PNK)
CNS
(WHT)
31
t°t°t
2
4 12 1
12 1
3
1
TH32
TH33
TH7/6
(BLK)
(YLW)
(RED)
TRANS
F2
CNAC
(WHT)
F1
P. B.
4
1
CNAF
(WHT)
6
7
1
CN2
IPM
(WHT)
7
1
2
(WHT)
1
2
(RED)
1
2
(WHT)
TABN
TABP
CN3
CN5
CN4
TABP2
RED
TABU
RED
UVW
TH8
t
°
2
2
WHT
CB
RED
WHT
MS
3~
TABV
BLK
CNDC
(PNK)
2
1
3
TABN1
BLK
TABW
MC
TABT
BLU
DS3
TABS
WHT
DS2
TABP1
RED
U
TABN2
WHT
When M-NET adapter is connected
5
SW7
SW9
1
(WHT)
CNDM
CN51
(WHT)
CNAC2
CNAC1
(WHT
3
1
5
3
1
(RED
3
1
WHT
LO NO
)
)
LI NI
RED
ABS
52C
U
BLU
5
CN5
(WHT)
1
LED2
LED3
LED4
M-NET SUBSTRATE
2
CN2M
(WHT)
1
LED5
TB7
M-NET
N. F.
CN52C
(BLK)
(RED
U
BLU
1
2
CN5
1
2
SW1
LED1
E2
EI
CND
(WHT)
31
3
)
SW11
SW12
2
BLK
2
BLK
M-NET ADAPTER
SYMBOL
TB7
Terminal Block<M-net connection>
CN5
Connector<Transmission>
CND
Connector<Power Supply>
CN2M
Connector<M-NET communication>
SW1
Switch<Status of communication>
SW11
Switch<Address setting : 1st digit>
SW12
Switch<Address setting : 2nd digit>
LED1
LED<Power Supply : DC5V>
LED2
LED<Connection to Outdoor Unit>
LED3
LED<Transmission : Sending>
LED4
LED<Transmission : Recelving>
LED5
LED<Power Supply : DC12V>
NAME
DCL
RED
BLK
BLK
ACTM
4
WHT
L1
L2
6 1
RED
P
N1
N2
WHT
Io
RED
L N S1 S2 S3
POWER SUPPLY
~/N 230V 50Hz
BLU
YLW
GRN/YLW
INDOOR
UNIT
ORN
BRN
CY1
CY2
TB1
+
1MODEL SELECT
The black square () indicates a switch position.
MODEL
71V
100V
SW6
ON
OFF
12345678
ON
OFF
12345678
ON
OFF
ON
OFF
SW5-6+2
123456
123456
32
Page 33
PUHZ-HRP100YHA PUHZ-HRP125YHA
[LEGEND]
SYMBOL
TB1
TB2 Terminal Block<Indoor/Outdoor >
MC
MF1, MF2
21S4
63H
63L Low Pressure Switch
SV
TH3,TH32,TH33
TH4
TH6
TH7
LEV-A, LEV-B, LEV-C
ACL1~ACL4
CB1, CB2
CK
CY1, CY2
RS
M-NET ADAPTER
TB7 Terminal Block<M-NET connection >
CN5
CND
CN2M
SW1
SW11
Terminal Block<Power Supply>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Solenoid Valve (Bypass Valve)
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Electronic Expansion Valve
Reactor
Main Smoothing Capacitor
Capacitor
Capacitor
Rush Current Protect Resistor
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting: 1st digit>
MF1
MS
3~
MF2
MS
3~
TB2
S1
INDOOR
UNIT
POWER SUPPLY
3N~
400V 50Hz
S2
S3
NAME SYMBOL NAME SYMBOL NAME
SW12 Switch<Address setting. 2nd digit >
LED1
LED2
LED3
LED4
LED5
TH33
CY1
1
1
CNS
(WHT)
C.B.
3
CY2
2
1
t
°
CNF1
(WHT)
3
12 1
7
TH33
(YLW)
CNF2
(WHT)
7
3
TRANS
1
CNDC
(PNK)
F2
F1
BLK
YLW
ORN
BRN
P.B.
TB-U/V/W
TB-L1/L2/L3
TB-P2
TB-C1
TB-N1
X52A
N.F.
LI1/LI2/LI3/NI
LO1/LO2/LO3/NO
CONV.B.
L1-A1/IN
L1-A2/OU
L2-A2/OU
L3-A2/OU
LED<Power Supply: DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission: Sending>
LED<Transmission: Receiving>
LED<Power Supply: DC12V>
TH7 TH6 TH3 TH4
TH32
t
°
1
TH32
(BLK)
CNAC
(WHT)
2
12
34
BLU
t°t°t°t
TH7/6
(RED)
4 12 1
TH3
(WHT)
(WHT)
F3
F4
CN2
°
TH4
(WHT)
7 1
7
63H
(YLW)
P.B.
2
2
RED
RS
RED
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal
Connection Terminal
Connection Terminal
Connection Terminal
52C Relay
Noise Filter Circuit Board
Connection Terminal
Connection Terminal
Connection Terminal<Ground>GD1, GD3
Converter Circuit Board
Connection Terminal<L1-Power Supply>
Connection Terminal<L1-Power Supply>
Connection Terminal<L2-Power Supply>
Connection Terminal<L3-Power Supply>
Connection TerminalN-IN
Connection TerminalCK-OU
63L
63H
LEV-A LEV-B
MM
6 1
LEV-A
(WHT)
3 1
63L
3 1
(RED)
LED2
X52
1 3
21S4
(GRN)
37
(WHT)
2
1
2
1
X52A
CN7
CN4
(WHT)
CN5
(RED)
3 1
7 1
CN2
(WHT)
+
--
+
--
TB-P2
RED
++
CB1 CB2 CK
N.F.
CNAC1
(WHT)
NO FUSE
BREAKER
TB1
L1
L2
L3
N
RED
WHT
BLK
BLU
GRN/YLW
LI1
LI2
U U
LI3
U
NI
U
U
GD1
BLK
3 1
<L1/L2/L3-Power Supply>
<L1/L2/L3/N-Power Supply
<L1/L2/L3/N-Power Supply
>
>
LEV-C
M
3
5
LED1
LEV-B
(RED)
1 3
6 1
5
1
X55
SV2
(BLU)
3 15 1
CNVMNT
(WHT)
1 14
CNM
(WHT)
CN4
(WHT)
6
LEV-C
(BLU)
SV 21S4
TB-W
TB-V
TB-U
TB-L3
TB-L2
TB-L1
+
+
TB-C1
TB-N1
BLK
WHT
CNDC
GD3
(PNK)
BLK
2
C.B.
SW1
SW4
SW5
SW6
SW7
SW8
SW9
SWP
CN31
LED1, LED2
F1~F4
CNM
CNMNT
CNVMNT
CNDM
CN3S
CN51
SS
X51,X52,X55
5
CNMNT
(WHT)
221
X51
1 3
SS
(WHT)
BLK
WHT
RED
BLK
WHT
RED
CNCT
(RED)
+
Controller Circuit Board
Switch
<Forced Defrost, Defect History Record
Reset, Refrigerant Adress>
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
Switch<Function Setup>
Switch<Function Setup>
Switch
Switch<Pump Down>
Connector<Emergency Operation>
LED<Operatiion Inspection Indicators>
Fuse<T6.3AL250V>
Connector<A-Control Service Inspection Kit>
Connector
<Connect to Optional M-NET Adapter Board>
Connector
<Connect to Optional M-NET Adapter Board>
Connector
< Connection for Option
Connector< Connection for Option>
Connector< Connection for Option>
Connector< Connection for Option>
Relay
+
1+1
SW5 SW8 SW4 SWP
MC
W
V
U
2
SW7
SW6 SW1
SW9
CN31
1
3
CN3S
(WHT)
1
3
(WHT)
CNDM
1
CN51
(WHT)
5
+ 1MODEL SELECT
The black square ( ) indicates a switch position.
MODEL
100Y
125Y
MS
+
2. SW5 -1 to 5 : Function Switch
3
~
3
CNAC2
(RED)
3 12 1
LO1
LO2
LO3
NO
(Contact Input)
When M-NET adapter is connected)
5
SW6
ON
OFF
12345678
ON
OFF
12345678
BLK
BLK
WHT
L3-A2
L3-OU
3
CN7
1
(WHT)
L1-A1
RED
RED
WHT
BLK
BLU
+
U
--
1 3 3 1
CNL
WHT
(BLU)
WHT
ACL4
ABS
WHT
L2-OU
CONV.B.
L1-IN
RED
>
5
SW1
CN5
(WHT)
1
LED2
LED3
LED4
M-NET SUBSTRATE
2
1
CN2M
(WHT)
LED1
LED5
TB7
M-NET
SW5-6 + 2
ON
OFF
123456
ON
OFF
123456
RED
RED
L2-A2
L1-A2
L1-OU
N-IN
CK-OU
BLK
BLU
ACL1
ACL2
ACL3
CND
(WHT)
31
3
SW11
SW12
33
Page 34
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2
[LEGEND]
SYMBOL
TB1
MC
MF1, MF2
21S4
63H High Pressure Switch
63L Low Pressure Switch
63HS High Pressure Sensor
TH3 Thermistor<Liquid>
TH4
TH6
TH7
TH32 Thermistor<Suction>
TH33 Thermistor<Ref. check>
LEV-A, LEV-B,LEV-C
DCL
CE
CY1,CY2
MF1
MS
~
3
MF2
MS
~
3
Terminal Block<Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
Thermistor<Discharge>
Thermistor<2-Phase>
Thermistor<Ambient>
Electronic Expansion Valve
Reactor
Main Smoothing Capacitor
Capacitor
C.B.
CNS
(WHT)
7
7
2
31
CNF1
(WHT)
CNF2
(WHT)
3
1
CNDC
(PNK)
1
1
NAME SYMBOL NAME SYMBOL NAME
TH6
t° t° t°
4 12 1
)
2 1
4 3
TH3
(WHT)
TH4
(WHT)
7
(YLW)
CN2
(
WHT
63H
63H
TH7 TH3 TH4
TH33
TH32
t°
t°
3t°12 1 31
2
1
TH33
TH7/6
TH32
(YLW)
(RED)
(BLK)
TRANS
F2
CNAC
(
WHT
F1
P.B.
U/V/W
LI
NI
DCL1, DCL2
IGBT
E1,E2,E3,E4
C.B.
SW1
SW4
SW5
SW6
SW7
SW8
SW9
SWP
63HS
63L
63HS
(WHT)
31
63L
31
(RED)
LED2
CN4
(WHT)
)
7 1
2
F3
21S4
F4
(GRN)
21S4
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal <L-Phase>
Connection Terminal<
Recator
Power Module
Connection Terminal (Ground)
Controller Circuit Board
Switch
<Manual Defrost, Defect History Record
Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch, Model Select>
Switch<Model Select>
Switch<Function Set up>
Switch<Function Set up>
Switch<Function Switch>
Switch<Pump Down>
LEV-C
LEV-A LEV-B
MM
LEV-A
(
WHT
LED1
21
M
3
5
6 1
6 1
315 1
LEV-B
)
(RED
1 14
5
1
6
LEV-C
(BLU)
X52
CNVMNT
(WHT
CNM
(WHT)
X54
SV1
(GRY)
)
CN52C
(RED)
)
1 3 1 3 1 3
CNMNT
(WHT
331
CN31
SV1
SS
N-Phase
>
5
+ 1+2
SW5 SW8 SW4 SWP
SW7
SW6 SW1
)
SW9
CN31
1
3
(WHT)
CNDM
1
CN51
(WHT)
5
X51
SS
(WHT
)
CNM
CNDM
LED1,LED2
F1~F4
X51,X52,X54
When M-NET adapter is connected
5
2
1
ABS
Connector<Emergency Operation>
Connector<Connection for Option
Connector<Connection for Option>
Connector
<A-Control Service Inspection Kit
Connector
< Connected for Option (Contact Input)>
LED<Operation Inspection Indicators>
Fuse<T6.3AL250V
Relay
M-NET ADAPTER
SYMBOL
Terminal Block
TB7
5
CN5
SW1
(WHT)
1
LED2
LED3
LED4
M-NET ADAPTER
CN2M
(WHT)
LED1
LED5
3
TB7
M-NET
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
SW11
SW12
CND
(WHT)
31
<
Transmission>
Connector
<
Power Supply>
Connector
Connector
<
M-NET communication>
<
Status of communication>
Switch
<
Address setting : 1s digit>
Switch
<
Address setting : 10s digit>
Switch
<
Power Supply : DC5V>
LED
LED
<
Connection to Outdoor Unit>
<
Transmission : Sending>
LED
LED
<
Transmission : Receiving>
<
Power Supply : DC12V>
LED
>
NAME
<
M-NET connection>
>
>
2
2
1
CN4
(WHT)
WHT
CE
RED
W
U
V
BLK
RED
WHT
V
W
U
MS
~
3
7
1
CN2
(WHT)
N2
P2
DCL2
DCL1
DCL
MC
+3 Setting of the starting ambient temp. of the flash injection.
The black square ( ) indicates a switch position.
Ambient temp.
3°C or less
(lnitial setting)
SW9-3,4 + 4
ON
OFF
1234
Ambient temp.
0°C or less
SW9-3,4 + 4
ON
OFF
1234
+ 4. SW9-1 to 2 : Function Switch
CNDC
(PNK)
2
3
IGBT
CN52C
(RED)
1
3
52C
52C
1
E4
EI
BLK
BLK
BLU
RED
L N S1 S2 S3
POWER SUPPLY
~/N 230V 50Hz
Ambient temp.
-3°C or less
U
YLW
GRN/YLW
INDOOR
UNIT
ON
OFF
U
ORN
BRN
SW9-3,4 + 4
1234
P. B.
E3
CNAC2
(RED)
E2
CNAC1
(WHT)
LI NI
CY1
CY2
TB1
-6°C or less
BLK
1
3
BLK
1
RED
3
WHT
+ 1 MODEL SELECT
The black square ( ) indicates a switch position.
MODEL
71V
100V
SW6
ON
OFF
12345678
ON
OFF
12345678
SW5-6 + 2
ON
OFF
123456
ON
OFF
123456
+2 SW5 -1 to 5 : Function Switch
Ambient temp.
SW9-3,4 + 4
ON
OFF
1234
34
Page 35
PUHZ-HRP100YHA2 PUHZ-HRP125YHA2
[LEGEND]
SYMBOL
TB1
TB2 Terminal Block<Indoor/Outdoor >
MC
MF1, MF2
21S4
63H
63L Low Pressure Switch
63HS High Pressure Sensor
TH3 Thermistor<Liquid>
TH4
TH6
TH7
TH32 Thermistor<Suction>
TH33 Thermistor<Ref. check>
LEV-A, LEV-B, LEV-C
ACL1~ACL4
RS
CB1, CB2
CK
MF1
MS
3~
MF2
MS
3~
TB2
INDOOR
UNIT
POWER SUPPLY
3N~
400V 50Hz
Terminal Block<Power Supply>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Ambient>
Electronic Expansion Valve
Reactor
Rush Current Protect Resistor
Main Smoothing Capacitor
Capacitor
C.B.
1
7
1
7
2
CNS
(WHT)
3
1
S1
S2
S3
YLW
ORN
BRN
NAME SYMBOL NAME SYMBOL NAME
TH6
t° t° t°
4 12 1
TH3
(WHT)
U U
U
U
63H
TH4
(WHT)
63H
(YLW)
CN2
(WHT)
F3
F4
P.B.
2
2
RS
U
GD1
BLK
TH7 TH3 TH4
TH33
TH32
t°
t°
3t°12 1 31
2
1
TH33
TH7/6
TH32
(YLW)
(RED)
(BLK)
TRANS
CNAC
(
WHT)
12
F1
34
N.F.
LI1
RED
LI2
WHT
LI3
BLK
NI
BLU
GRN/YLW
3
1
TB1
CNF1
(WHT)
CNF2
(WHT)
CNDC
(PNK)
L1
L2
L3
N
F2
63L
31
63L
31
(RED)
7 1
7
37
CN7
(WHT)
2
CN4
(WHT)
1
CN5
2
(RED)
1
X52A
RED
RED
CNAC1
(WHT)
P.B.
TB-U/V/W
TB-L1/L2/L3
TB-P2
TB-C1
TB-N1
X52A
N.F.
LI1/LI2/LI3/NI
LO1/LO2/LO3/NO
GD1, GD3
CONV.B.
L1-A1/IN
L1-A2/OU
L2-A2/OU
L3-A2/OU
N-IN
CK-OU
63HS
LEV-A LEV-B
63HS
LEV-A
(WHT)
(WHT)
LED2
CN4
(WHT)
21S4
31
CN2
(WHT)
RED
3 1
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal
Connection Terminal
Connection Terminal
Connection Terminal
52C Relay
Noise Filter Circuit Board
Connection Terminal
Connection Terminal
Connection Terminal<Ground>
Converter Circuit Board
Connection Terminal<L1-Power Supply>
Connection Terminal<L1-Power Supply>
Connection Terminal<L2-Power Supply>
Connection Terminal<L3-Power Supply>
Connection Terminal
Connection Terminal
LEV-C
M
MM
6 1
LED1
5
221
1
X52
1 3
21S4
(GRN)
7 1
+
--
+
--
+
TB-P2
++
CB1 CB2 CK
3
5
6 1
LEV-B
CNVMNT
(RED)
(WHT)
1 14
CNM
(WHT)
6
LEV-C
(BLU)
X54
1 3
SV1
(GRY)
+
TB-N1
TB-C1
BLK
WHT
GD3
BLK
315 1
TB-V
TB-L3
TB-L2
TB-L1
CNDC
(PNK)
CNMNT
(WHT)
TB-W
TB-U
2
<L1/L2/L3-Power Supply>
<L1/L2/L3/N-Power Supply
<L1/L2/L3/N-Power Supply
5
+ 1+2
SW5 SW8 SW4 SWP
SW7
SW6 SW1
SW9
CN31
1
3
(WHT)
CNDM
1
CN51
(WHT)
5
X51
1 3
SS
(WHT)
BLK
MC
W
WHT
V
MS
3
~
U
RED
BLK
WHT
RED
2
CNCT
(RED)
+
BRN
WHT
3 12 1
+
U
--
1 3 3 1
CNL
(BLU)
C.B.
SW1
SW4
SW5
SW6
SW7
SW8
SW9
>
>
SWP
CN31
SV1
SS
LED1, LED2
CNM
CNDM
F1~F4
X51,X52,X54
When M-NET adapter is connected
5
ABS
+ 1 MODEL SELECT
The black square ( ) indicates a switch position.
MODEL
ON
100Y
OFF
ON
125Y
OFF
2 SW5 -1 to 5 : Function Switch
+
BLK
BLK
L3-OU
3
3
CN7
1
L1-A1
CNAC2
(RED)
LO1
RED
LO2
WHT
LO3
BLK
NO
BLU
ACL4
Controller Circuit Board
Switch
<Manual Defrost, Defect History Record
Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch, Model select>
Switch<Model Select>
Switch<Function Set up>
Switch<Function Set up>
Switch<Function Switch>
Switch<Pump Down>
Connector<Emergency Operation>
<
Connection for Option
Connector
Connector< Connection for Option>
LED<Operation Inspection Indicators>
Connector<A-Control Service Inspection Kit>
Connector
< Connection for Option
Fuse<T6.3AL250V>
Relay
M-NET ADAPTER
SYMBOL
TB7
CN5
SW11
SW12
L1-A2
CK-OU
BLK
SW5-6 + 2
ON
OFF
123456
ON
OFF
123456
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
5
SW1
CN5
(WHT)
1
LED2
LED3
LED4
M-NET ADAPTER
2
1
CN2M
(WHT)
LED1
LED5
3
TB7
M-NET
SW6
12345678
12345678
RED
WHT
WHT
L2-A2
L3-A2
L2-OU
CONV.B.
(WHT)
L1-IN
RED
RED
BLU
ACL1
ACL2
ACL3
CND
(WHT)
31
RED
L1-OU
N-IN
(Contact Input)
>
>
NAME
<
M-NET connection>
Terminal Block
Connector
<
Transmission>
<
Power Supply>
Connector
Connector
<
M-NET communication>
<
Status of communication>
Switch
<
Address setting : 1s digit>
Switch
<
Address setting : 10s digit>
Switch
<
Power Supply : DC5V>
LED
LED
<
Connection to Outdoor Unit>
<
Transmission : Sending>
LED
<
Transmission : Receiving>
LED
<
Power Supply : DC12V>
LED
+3 Setting of the starting ambient temp. of the flash injection.
The black square ( ) indicates a switch position.
Ambient temp.
3°C or less
(lnitial setting)
SW9-3,4 + 4
ON
OFF
1234
Ambient temp.
0°C or less
SW9-3,4 + 4
ON
OFF
1234
+ 4. SW9-1 to 2 : Function Switch
Ambient temp.
-3°C or less
35
SW9-3,4 + 4
ON
OFF
1234
Ambient temp.
-6°C or less
SW9-3,4 + 4
ON
OFF
1234
Page 36
5
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT unit : mm
PLA-RP·BA/BA2/BA3 PKA-RP·GAL
PKA-RP·FAL(2) PEAD-RP·JA(L)
PEAD-RP·EA(2) PEAD-RP·GA
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Thermistor TH5
(Cond./Eva. temperature)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
Distributor
with strainer(#50)
Thermistor TH1
(Room temperature)
Thermistor TH2
Pipe temperature (Liquid)
(Flare)
Strainer(#50)
PKA-RP·HAL
PKA-RP·KAL
Thermistor TH5
(Cond./ Eva.temperature)
Heat exchanger
Thermistor TH1
(Room temperature)
Thermistor TH2
Pipe temperature(Liquid)
Distributor with strainer
(#50/#50: HAL)
(#50/#100: KAL)
Strainer (#50)
Refrigerant GAS pipe connection
(Flare)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Strainer (#50)
36
Page 37
5-2. OUTDOOR UNIT
Unit : mm (inch)
PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA
Thermistor TH7
(Outdoor)
Thermistor
TH6
(Outdoor
2-phase pipe)
Thermistor TH3
(Outdoor pipe)
Distributor
Thermistor TH33
(Outdoor pipe)
Bypass
valve
Replace
filter
Refrigerant
GAS pipe
connection
(5/8 inch)
Ball valve
Strainer
#50
Linear
expansion valve B
Charge plug
(Low pressure)
Strainer
#100
Power
receiver
Solenoid valve
(Four-way valve)
Charge plug
(High pressure)
Low pressure
switch 63L
Strainer
#100
Strainer
#100
Muffler
Compressor
High pressure
switch 63H
Thermistor
TH32
(Outdoor pipe)
Thermistor TH4
(Discharge)
Linear expansion valve A
Injection port
Heat exchanger
Strainer
#100
Refrigerant
LIQUID pipe
connection
(3/8 inch)
Stop valve
(with service port)
Strainer
#100
Linear
expansion valve C
Heat interchange circuit
Restrictor
valve
Strainer
#100
Refrigerant flow in cooling
Refrigerant flow in heating
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2
Thermistor TH7
(Outdoor)
Thermistor
TH6
(Outdoor
2-phase pipe)
Thermistor TH3
(Outdoor pipe)
Distributor
Thermistor TH33
(Outdoor pipe)
Refrigerant
GAS pipe
connection
(5/8 inch)
Ball valve
Strainer
#50
Charge plug
(Low pressure)
Solenoid valve
(Four-way valve)
Charge plug
(High pressure)
Low pressure
switch 63L
Strainer
#100
High pressure
sensor(63HS)
Muffler
High pressure
switch 63H
Thermistor
TH32
(Outdoor pipe)
Thermistor TH4
(Discharge)
Heat exchanger
Strainer
#100
Refrigerant
LIQUID pipe
connection
(3/8 inch)
Linear
expansion valve B
Stop valve
(with service port)
Strainer
#100
Strainer
#100
Power
receiver
Linear
expansion valve C
Strainer
#100
37
Compressor
Linear expansion valve A
Injection port
Heat interchange circuit
Refrigerant flow in cooling
Refrigerant flow in heating
Page 38
PERFORMANCE CURVES 6
FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-HRP·VHA(2), PUHZ-HRP·YHA(2)
Rated cooling capacity
1.4
Indoor intake air wet-bulb temperature <W.B. :>
1.2
1.0
0.8
Cooling capacity ratio
0.6
-5 0 5 10 15 20 25 30 35 40 46
Rated cooling input
1.2
1.0
Outdoor intake air dry-bulb temperature <D.B. >
22
22
20
18
16
20
18
16
0.8
0.6
Cooling input ratio
Indoor intake air wet-bulb temperature <W.B. :>
0.4
-5 0 5 10 15 20 25 30 35 40 46
Outdoor intake air dry-bulb temperature <D.B. >
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
38
Page 39
Rated heating capacity
1.4
1.2
1.0
Capacity ratio
0.8
0.6
-25 -20 -15 -10 -5 0 5 10 15
15
20
25
Indoor intake air dry-bulb temperature <: D.B.>
Outdoor ambient temp.(˚CWB)
Rated heating input
2.5
2.0
1.5
Input ratio
1.0
0.5
-25 -20 -15 -10 -5 0 5 10 15
25
20
15
Indoor intake air dry-bulb temperature <: D.B.>
Outdoor ambient temep.(ºCWB)
39
Page 40
7
CORRECTION FACTORS
PUHZ-HRP71, 100VHA(2) PUHZ-HRP100, 125YHA(2)
Cooling capacity correction factors
Outdoor unit
PUHZ-HRP71VHA(2) 1.00 0.988 0.966 0.946 0.929 0.913 0.905 0.897 0.876 0.870
5m 10m 20m 30m 40m 50m 55m 60m 70m 80m
Refrigerant piping length (one way)
PUHZ-HRP100VHA(2)
PUHZ-HRP100YHA(2)
PUHZ-HRP125YHA(2) 1.00 0.981 0.946 0.914 0.885 0.858 0.845 0.834 0.812 0.792
Heating capacity correction factors
Outdoor unit
PUHZ-HRP71VHA(2) 1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955
PUHZ-HRP100VHA(2)
PUHZ-HRP100YHA(2)
PUHZ-HRP125YHA(2) 1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955
1.00 0.985 0.957 0.931 0.908 0.886 0.876 0.865 0.846 0.829
Refrigerant piping length (one way)
5m 10m 20m 30m 40m 50m 55m 60m 70m 80m
1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955
40
Page 41
APPLICABLE EXTENSION PIPE FOR EACH MODEL 8
8-1. PIPE LENGTH
8-1-1. 1:1 SYSTEM
Pipe length
<Table 1> Maximum pipe length
Liquid
OD
pipe
Thickness
(mm)
Gas
OD
pipe
(mm)
Thickness
:12.7
HRP71~125
+ The maximum length is 75m in case of new pipes.
8-1-2. TWIN SYSTEM
(1) TWIN SYSTEM
<Table 2> Maximum pipe length
Main pipe
(mm)
Branch
(mm)
[B, C]
+ The maximum length is 75m in case of new pipes.
[A]
pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
t0.8
:6.35
:12.7
:9.52
:15.88
:9.52
:19.05
:9.52
t0.8
:15.88
t1.0
Standard size
50m +
[30m]
:6.35
12.7
:
Standard size
:19.05
t1.0
50m
[30m]
:9.52
15.88
:
50m
[30m]
50m
[30m]
:15.88
t1.0
50m
[20m]
:9.52
15.88
:
Standard size
50m +
[30m]
50m
[30m]
:12.7
HRP100(RP50% 2) HRP71(RP35% 2)
t0.8
:19.05
50m
[20m]
:9.52
:
19.05
50m
[30m]
50m
[30m]
t1.0
<Marks in the table>
[30m]
:12.7
19.05
50m
[20m]
50m
[20m]
:9.52
15.88
:
Standard size
50m +
[30m]
:
50m
HRP125(RP60% 2)
:9.52
19.05
:
50m
[30m]
: It can be used.
: Additional refrigerant charge is required when
the pipe length exceeds 20m.
The maximum pipe length
Charge-less pipe length
:12.7
19.05
:
50m
[20m]
Indoor unit side
Indoor unit
h
H
Distribution pipe
B
Indoor unit
C
Outdoor unit
Outdoor unit side
A
<TWIN SYSTEM>
Total length A + B + C
Max. 75 m
Height difference
H(Indoor unit-Outdoor unit) Max. 30m
h(Indoor unit-Indoor unit) Max. 1m
Distance between indoor and indoor units
Pipe length |B-C|
Max. 8m
Number of bends (one way)
Max. 15 (Max. 8 points between main pipe A and each branch pipe(B, C))
41
Page 42
8-2. ADJUSTING THE AMOUNT OF REFRIGERANT
• Check additional refrigerant charging amount referring to table 5, 6 when liquid pipe is one size larger than standard diameter.
<Table 5> Required additional charge when the liquid pipe is one size larger than the standard diameter (1:1 SYSTEM)
Outdoor unit
PUHZ-HRP71-125
<Table 6> Required additional charge when the liquid pipe is one size larger than the standard diameter (TWIN SYSTEM)
Outdoor unit
PUHZ-HRP71-125
If the calculation produces a negative number ( W 0), additional charging is not necessary.
L1:
:
12.7 liquid pipe length (m)
L2::9.52 liquid pipe length (m)
L3::6.35 liquid pipe length (m)
<Table 7> Additional refrigerant charging amount for pipe of standard diameter
Outdoor unit Type
1 : 1
PUHZ-HRP71-125
system
Liquid pipe O.D.
:12.7
When the extension pipe length (main piping + branch piping) exceed 20 m
Additional refrigerant amount W(g) = (100 % L1) + (60 % L2) + (30 % L3) - 2000
Permitted
pipe length
75m or less
Refrigerant amount to be added (Exceeding 20m)
100 g per 1 m
Amount of unit
filling refrigerant (kg)
5.5kg
31 – 40m
Additional refrigerant charging amount
for pipe length exceeding 30 m (kg)
41 – 50m
0.6kg
1.2kg
51 – 60m
1.8kg
61 – 70m 71 – 75m
2.4kg
Twin
PUHZ-HRP71-125
system
Outdoor unit Type
Permitted
pipe length
75m or less
Amount of unit
filling refrigerant (kg)
5.5kg
31 – 40m
Additional refrigerant charging amount
for pipe length exceeding 30 m (kg)
0.6kg
41 – 50m
1.2kg
51 – 60m
1.8kg
61 – 70m 71 – 75m
2.4kg
42
Page 43
8-3. CAPACITY CORRECTION CURVES
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends × 0.3 (m)
[Sample calculation]
Indoor unit RP60 o 2 units (Twin system)
Outdoor unit HRP125 o 1
• Condition Using existing pipes.
• Outdoor unit side
Liquid pipe [ 12.7 / Gas pipe [19.05
pipe length (A) 20m
• Indoor unit side
Liquid pipe [ 9.52 / Gas pipe [15.88
pipe length (B) 20m + (C) 15m
1) Farthest piping length 20m + 15m = 35m
Number of bends : 10
2) Corrected piping length 35m + 0.3 o 10 = 38m
3) Capacity correction Outdoor unit side’s gas pipe [19.05
Standard [15.88 → 1 size up
Refer to 1 Capacity curves <Standard size>
4) Capacity Cooling capacity = Standard cooling capacity o 0.89
Heating capacity = Standard heating capacity o 0.98
1 Capacity curves for PUHZ-HRP · HA(2) model <Standard size>
100
95
90
85
Capacity ratio [%]
80
75
Note: The permitted pipe length is up to 80m.
70
5 1 01 52 02 53 03 54 04 55 05 56 06 57 07 58 0
Corrected pipe length [m]
2 When gas pipe is one size larger than standard size for PUHZ-HRP71-125.
1 Capacity can be obtained by referring to capacity curves of standard size.
Heating HRP71-125
Cooling HRP71 model
Cooling HRP100 model
Cooling HRP125 model
Cooling
Heating
43
Page 44
9
AIR FLOW DATA
9-1. OUTLET AIR SPEED AND COVERAGE RANGE
PLA-RP100BA
PLA-RP36BA PLA-RP50BA PLA-RP60BA PLA-RP71BA2
Air fl ow m 3/min. 15 18 18 21 30 31
Air speed m/sec. 2.6 3.2 3.2 3.7 5.3 5.4
Coverage range m 4.1 4.8 4.8 5.6 8 8.2
PKA-RP35GAL PKA-RP50GAL
3
Air fl ow m
Air speed m/sec. 5.3 5.3
Coverage range m (ft) 10 (32.8) 10(32.8)
Air fl ow m 3/min. 20 28
Air speed m/sec. 4.9 5.4
Coverage range m (ft) 12.4(40.7) 15.3 (50.2)
Air fl ow m
Air speed m/sec. 6.1 6.1
Coverage range m (ft) 10.8 (35.4) 10.8 (35.4)
/min. 12 12
PKA-RP50FAL2
PKA-RP60FAL
PKA-RP35HAL PKA-RP50HAL
3
/min. 12 12
PKA-RP100FAL
PLA-RP100BA2
PLA-RP100BA3
PLA-RP125BA
PLA-RP125BA2
PKA-RP60KAL
Air fl ow m 3/min. 22 26
Air speed m/sec. 6.0 6.8
Coverage range m (ft) 14.3 (46.9) 16.1 (52.8)
w The air coverage range is the distance to which the 0.25 m/sec air can reach, when air is blown out horizontally from the unit
at the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
PKA-RP100KAL
44
Page 45
9-2. PLA-RP·BA/BA2/BA3
9-2-1 FRESH AIR INTAKE AND BRANCH DUCT
1.
Branch duct hole and fresh air intake hole (Fig. 1)
At the time of i nstallation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
Fresh air intake hole
Refrigerant pipe
Indoor unit
Branch duct hole
Drain pipe
Branch duct
hole diagram
(view from
either side)
:175 burring hole pitch
70
90
Fig. 1
3-:2.8 burring hole
100 100 90
350
Fresh air intake hole diagram
120
*158
100
14-:2.8 burring hole
:150 cut out hole
:125 burring hole pitch
120
:100 cut out hole
Ceiling
130
*155
*167
45
Page 46
3. Fresh air intake volume & static pressure characteristics
PLA-RP35~60BA PLA-RP71BA2
At using multi-function casement, standard filter
50
0
-50
2 - inlet
-100
Static pressure[Pa]
-150
1 - inlet
-200
01234 56
Air flow rate [m3/min]
Direct intake to unit
50
0
-50
-100
Static pressure[Pa]
-150
-200
01234 56
Air flow rate [m
3
/min]
PLA-RP100BA/BA2/BA3, 125BA(2)
At using multi-function casement, standard filter
50
0
-50
2 - inlet
-100
Static pressure[Pa]
-150
1 - inlet
-200
02468
Direct intake to unit
50
Air flow rate [m
3
/min]
At using multi-function casement, high efficiency filter
50
0
-50
-100
Static pressure[Pa]
-150
-200
01234 56
Air flow rate [m
3
/min]
1 - inlet
2 - inlet
At using multi-function casement, high efficiency filter
50
0
-50
-100
Static pressure[Pa]
-150
-200
02468
Air flow rate [m
3
/min]
0
-50
-100
Static pressure[Pa]
-150
-200
02468
1 - inlet
Air flow rate [m
3
/min]
2 - inlet
46
Page 47
4. Change of outlet numbers
The optional air outlet is necessary.
To change the air outlet number to 3-, or 2-way outlet, the
outlet number should be closed with the operational air
outlet shutter.
When the air outlets are closed, close the vane by
removing the vane connector.
Indoor unit
Button
Vane motor
Up/down vanes
Connector
Vane motor
Connector
Button
5. Branch duct and change of outlet numbers
<4- way air flow and branch duct>
Branch
duct
Air intake
+ Branch duct should be connected to one of the branch duct holes on the main unit.
Air
outlet
Outlet concave
portion
Air outlet shutter plate
(Option)
<3- way air flow and branch duct>
Branch
duct
Air
outlet
closed
position
<2- way air flow and branch duct>
Branch
duct
Air
Air
outlet
outlet
closed
closed
position
position
Air intake
Air intake
+ Close the outlet on the side of branch duct and air flows in 3 directions.
Air
outlet
+ The outlet on the side of branch duct and one of the other outlets are closed.
Air flows in 2 directions.
Air
outlet
closed
position
47
Page 48
PLA-RP71BA2
4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct
30
30
20
10
Static pressure [Pa]
Low
0
02
3-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct
80
70
60
50
40
30
Static pressure [Pa]
20
Low
10
Duct
High
468
Airflow rate [m
Duct
Close
High
3
/min]
Duct
20
10
Static pressure [Pa]
High
Low
0
02468
Airflow rate [m
3
/min]
80
70
60
Duct
Close
50
40
30
Static pressure [Pa]
High
20
Low
10
0
024681 0
Airflow rate [m
3
/min]
2-way airflow (horizontal vane) Round duct
100
90
80
Duct
Close
Close
70
60
50
40
Static pressure [Pa]
30
20
High
Low
10
0
024681 01 2
Airflow rate [m
3
/min]
0
024681 0
Airflow rate [m
3
/min]
2-way airflow (horizontal vane) Rectangular duct
100
90
80
70
60
50
40
Static pressure [Pa]
30
20
Low
10
0
024681 01 2
Duct
Close
High
Airflow rate [m
3
/min]
• Use 1 of the 2 duct holes on the indoor unit.
• Airflow rate of PLA-RP35~60BA can be calculated from the airflow rate based on the characteristic
of the duct for PLA-RP71BA2.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
Close
48
Page 49
PLA-RP125BA(2)
4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct
30
30
Low
Duct
High
Duct
High
Duct
20
10
Static pressure [Pa]
Low
0
02468
Airflow rate [m
High
³
/min] Airflow rate [m³/min]
3-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct
80
70
60
50
40
Static pressure [Pa]
30
Duct
Close Close
High
20
10
Static pressure [Pa]
0
02468
80
70
60
50
40
Static pressure [Pa]
30
20
10
0
024681 0
Low
Airflow rate [m³/min] Airflow rate [m³/min]
20
10
0
0246 81 0
Low
2-way airflow (horizontal vane) Round duct 2-way airflow (horizontal vane) Rectangular duct
100
90
80
70
60
50
40
Close Close
High
Static pressure [Pa]
30
Low
20
10
0
024681 01 2
Airflow rate [m³/min] Airflow rate [m³/min]
Close Close
100
90
80
70
60
50
40
Static pressure [Pa]
30
20
10
0
024681 01 2
Low
Duct Duct
High
• Use 1 of the 2 duct holes on the indoor unit.
• Airflow rate of PLA-RP100BA/BA2/BA3 can be calculated from the airflow rate based on the characteristic
of the duct for PLA-RP125BA(2).
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
49
Page 50
9-3. PEAD-RP·JA(L)
Fan performance
PEAD-RP35JA(L)
(External static pressure 35Pa) 220-240V 50Hz
60
50
Limit
40
Rated point
30
20
External static pressure (Pa)
10
0
7 9 1 11 31 51 71 92 1
Low
Airflow rate(m3/min)
High
Middle
PEAD-RP35JA(L)
(External static pressure 100Pa) 220-240V 50Hz
120
110
100
Limit
90
80
70
60
50
40
External static pressure (Pa)
30
20
10
0
7 9 11 13 15 17 19 21
Airflow rate(m3/min)
Rated point
High
Middle
Low
PEAD-RP35JA(L)
(External static pressure 50Pa) 220-240V 50Hz
70
60
Limit
50
40
30
20
External static pressure (Pa)
10
0
7 9 1 11 31 51 71 92 1
Low
Rated point
High
Middle
Airflow rate(m3/min)
PEAD-RP35JA(L)
(External static pressure 70Pa) 220-240V 50Hz
90
80
Limit
70
60
Rated point
High
PEAD-RP35JA(L)
(External static pressure 150Pa) 220-240V 50Hz
170
160
150
140
Limit
130
120
110
100
90
80
70
60
50
External static pressure (Pa)
40
30
20
10
0
7 9 1 11 31 51 71 92 1
Airflow rate(m3/min)
Rated point
Middle
Low
High
50
40
30
Middle
Low
External static pressure (Pa)
20
10
0
0
7 9 1 11 31 51 71 92 1
Airflow rate(m3/min)
50
Page 51
PEAD-RP50JA(L)
(External static pressure 35Pa) 220-240V 50Hz
70
60
50
40
30
20
External static pressure (Pa)
10
0
Limit
High
Rated point
Middle
Low
91 41 9
Airflow rate(m3/min)
PEAD-RP50JA(L)
(External static pressure 50Pa) 220-240V 50Hz
80
70
Limit
60
50
40
30
20
External static pressure (Pa)
10
0
91 41 9
Low
Middle
High
Rated point
Airflow rate(m3/min)
PEAD-RP50JA(L)
(External static pressure 70Pa) 220-240V 50Hz
100
PEAD-RP50JA(L)
(External static pressure 100Pa) 220-240V 50Hz
130
120
110
Limit
100
90
80
70
60
50
40
External static pressure (Pa)
30
20
10
0
91 41 9
Low
Rated point
High
Middle
Airflow rate(m3/min)
PEAD-RP50JA(L)
(External static pressure 150Pa) 220-240V 50Hz
180
170
160
150
140
130
120
110
100
External static pressure (Pa)
Limit
90
80
70
60
50
40
30
20
10
0
91 41 9
Low
Airflow rate(m3/min)
Rated point
High
Middle
90
80
Limit
70
60
50
40
30
External static pressure (Pa)
20
10
0
91 41 9
Low
Rated point
High
Middle
Airflow rate(m3/min)
51
Page 52
PEAD-RP60JA(L)
(External static pressure 35Pa) 220-240V 50Hz
60
50
Limit
40
30
20
Rated point
High
Middle
External static pressure (Pa)
10
0
10 15 20 25 30
Low
Airflow rate(m3/min)
PEAD-RP60JA(L)
(External static pressure 50Pa) 220-240V 50Hz
70
60
Limit
50
40
30
20
External static pressure (Pa)
10
0
10 15 20 25 30
Low
Rated point
High
Middle
Airflow rate(m3/min)
PEAD-RP60JA(L)
(External static pressure 70Pa) 220-240V 50Hz
90
PEAD-RP60JA(L)
(External static pressure 100Pa) 220-240V 50Hz
120
110
100
90
Limit
80
70
60
50
40
External static pressure (Pa)
30
20
10
0
10 15 20 25 30
Low
Rated point
High
Middle
Airflow rate(m3/min)
PEAD-RP60JA(L)
(External static pressure 150Pa) 220-240V 50Hz
170
160
150
140
130
120
110
100
90
80
70
60
50
External static pressure (Pa)
40
30
20
10
Limit
0
10 15 20 25 30
Airflow rate(m3/min)
Rated point
High
Middle
Low
80
70
Limit
60
50
40
30
External static pressure (Pa)
20
10
0
10 15 20 25 30
Low
Rated point
High
Middle
Airflow rate(m3/min)
52
Page 53
PEAD-RP71JA(L)
(External static pressure 35Pa) 220-240V 50Hz
70
60
50
40
30
20
External static pressure (Pa)
10
Limit
High
Rated point
Middle
Low
0
10 15 20 25 30
Airflow rate(m3/min)
PEAD-RP71JA(L)
(External static pressure 50Pa) 220-240V 50Hz
90
80
70
60
50
40
30
Limit
High
Rated point
Middle
Low
External static pressure (Pa)
20
10
0
10 15 20 25 30
Airflow rate(m3/min)
PEAD-RP71JA(L)
(External static pressure 70Pa) 220-240V 50Hz
100
90
80
70
60
50
Limit
High
Rated point
Middle
PEAD-RP71JA(L)
(External static pressure 100Pa) 220-240V 50Hz
130
120
110
100
90
80
70
60
50
40
External static pressure (Pa)
30
20
10
0
Limit
Low
10 15 20 25 30
High
Rated point
Middle
Airflow rate(m3/min)
PEAD-RP71JA(L)
(External static pressure 150Pa) 220-240V 50Hz
180
170
160
150
140
130
120
110
100
External static pressure (Pa)
Limit
90
80
70
60
50
40
30
20
10
0
10
15 20 25 30
Low
Airflow rate(m3/min)
High
Rated point
Middle
40
30
External static pressure (Pa)
20
10
0
10 15 20 25 30
Low
Airflow rate(m3/min)
53
Page 54
PEAD-RP100JA(L)
(External static pressure 35Pa) 220-240V 50Hz
70
Limit
60
50
40
30
20
External static pressure (Pa)
10
0
10 15 20 25 30 35 40 45
Low
Rated point
High
Middle
Airflow rate(m3/min)
PEAD-RP100JA(L)
(External static pressure 50Pa) 220-240V 50Hz
100
90
80
Limit
70
Middle
High
Rated point
60
50
40
30
External static pressure (Pa)
20
10
0
10 15 20 25 30 35 40 45
Low
Airflow rate(m3/min)
PEAD-RP100JA(L)
(External static pressure 70Pa) 220-240V 50Hz
120
110
100
Limit
90
80
70
60
50
40
External static pressure (Pa)
30
20
10
0
10 15 20 25 30 35 40 45
Low
Airflow rate(m3/min)
High
Rated point
Middle
PEAD-RP100JA(L)
(External static pressure 100Pa) 220-240V 50Hz
150
140
130
120
Limit
110
100
90
80
70
60
50
External static pressure (Pa)
40
30
20
10
0
10 15 20 25 30 35 40 45
Low
High
Rated point
Middle
Airflow rate(m3/min)
PEAD-RP100JA(L)
(External static pressure 150Pa) 220-240V 50Hz
200
190
180
170
160
Limit
150
140
130
120
110
100
90
80
70
60
External static pressure (Pa)
50
40
30
20
10
0
15 20 25 30 35 40 45
10
Low
Airflow rate(m3/min)
High
Rated point
Middle
54
Page 55
PEAD-RP125JA(L)
(External static pressure 35Pa) 220-240V 50Hz
70
Limit
60
50
40
30
20
External static pressure (Pa)
10
0
15 20 25 30 35 40 45
Low
Middle
High
Rated point
Airflow rate(m3/min)
PEAD-RP125JA(L)
(External static pressure 50Pa) 220-240V 50Hz
100
90
80
70
60
50
40
30
External static pressure (Pa)
20
10
0
15 20 25 30 35 40 45
Limit
Middle
Low
High
Rated point
Airflow rate(m3/min)
PEAD-RP125JA(L)
(External static pressure 70Pa) 220-240V 50Hz
150
140
130
120
Limit
110
100
90
80
70
60
50
40
External static pressure (Pa)
30
20
10
0
15 20 25 30 35 40 45
Low
Airflow rate(m3/min)
High
Middle
Rated point
PEAD-RP125JA(L)
(External static pressure 100Pa) 220-240V 50Hz
180
170
160
Limit
150
140
130
120
110
100
90
80
70
60
50
External static pressure (Pa)
40
30
20
10
0
15 20 25 30 35 40 45
Low
High
Middle
Rated point
Airflow rate(m3/min)
PEAD-RP125JA(L)
(External static pressure 150Pa) 220-240V 50Hz
230
220
210
200
190
Limit
180
170
160
150
140
130
120
110
100
90
80
70
External static pressure (Pa)
60
50
40
30
20
10
0
15
20 25 30 35 40 45
Low
Airflow rate(m3/min)
Middle
High
Rated point
55
Page 56
9-4. PEAD-RP·EA,EA2,GA
9-4-1. FAN PERFORMANCE AND CORRECTED AIR FLOW
PEAD-RP35EA2
PEAD-RP50EA
(1Pa 0.1mmAq)
External static pressure (Pa)
Fan Performance <30Pa>
140
120
100
80
60
40
20
6 8 10 12 14 16 18 20
Airflow (CMM)
Fan Performance <70Pa>
160
140
120
100
80
Corrected Airflow
Cooling
1.1
1.0
0.9
0.8
Correction factor
81 01 21 41 61 82 02 2
Airflow (CMM)
Heating
1.3
1.2
1.1
1.0
Capacity
input
PEAD-RP60EA
60
(1Pa 0.1mmAq)
40
External static pressure (Pa)
20
8 10121416182022
Airflow (CMM)
Fan Performance <30Pa>
120
100
80
60
40
(1Pa 0.1mmAq)
20
External static pressure (Pa)
81 01 21 41 61 82 02 22 4
Airflow (CMM)
Fan Performance <70Pa>
140
120
100
80
60
40
(1Pa 0.1mmAq)
External static pressure (Pa)
20
10 12 14 16 18 20 22 24 26
Airflow (CMM
Correction factor
0.9
0.8
81 01 21 41 61 82 02 2
Airflow (CMM)
Corrected Airflow
Cooling
1.1
1.0
0.9
0.8
Correction factor
12 14 16 18 20 22 24 26
Airflow (CMM)
Heating
1.3
1.2
1.1
1.0
Correction factor
0.9
0.8
12 14 16 18 20 22 24 26
Airflow (CMM)
Capacity
input
56
Page 57
PEAD-RP71EA
Fan performance <130Pa>
Recommended range
200
180
160
140
120
100
80
=
60
40
(1Pa 0.1mmAq)
20
External static pressure (Pa)
12 16 20 24 28 32
Airflow
Corrected Airflow
Cooling
1.1
1.0
0.9
Correction factor
0.8
12 16 20 24 28 32
PEAD-RP100EA2
PEAD-RP125EA
Hi
Lo
(CMM)
Airflow (CMM)
Capacity
Input
Fan performance <70Pa>
Recommended range
180
160
140
120
100
80
=
60
40
(1Pa 0.1mmAq)
20
External static pressure (Pa)
12 16 20 24 28 32
Airflow
Heating
1.3
1.2
1.1
1.0
Correction factor
0.9
0.8
12 16 20 24 28 32
Lo
Hi
(CMM)
Airflow (CMM)
Fan performance <130Pa>
Recommended range
220
200
180
160
140
120
100
80
=
60
(1Pa 0.1mmAq)
40
20
External static pressure (Pa)
Lo
32 34 36 38 40 42 44 46 48
Airflow
(CMM)
Hi
Corrected Air Flow
Cooling
1.1
1.0
0.9
Correction factor
0.8
32 34 36 38 40 42 44 46 48
Airflow (CMM)
Capacity
Input
Fan performance <70Pa>
Recommended range
220
200
180
160
140
120
100
80
=
60
(1Pa 0.1mmAq)
40
20
External static pressure (Pa)
32 34 36 38 40 42 44 46
Airflow
Heating
1.2
1.1
1.0
0.9
Correction factor
0.8
32 34 36 38 40 42 44 46 48
Hi
Lo
(CMM)
Airflow (CMM)
57
Page 58
PEAD-RP60GA
PEAD-RP71GA
58
Page 59
PEAD-RP100GA
59
Page 60
10
NOISE CRITERION CURVES
10-1. INDOOR UNIT
PLA-RP35BA PLA-RP50BA
NOTCH SPL(dB) LINE
High 31
Medium1 29
Medium2 28
Low 27
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH SPL(dB) LINE
High 32
Medium1 31
Medium2 29
Low 28
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
PLA-RP60BA
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH SPL(dB) LINE
High 32
Medium1 31
Medium2 29
Low 28
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PLA-RP71BA2
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH SPL(dB) LINE
High 34
Medium1 32
Medium2 30
Low 28
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
60
Page 61
PLA-RP100BA
PLA-RP100BA2
PLA-RP100BA3
NOTCH SPL(dB) LINE
High 40
Medium1 37
Medium2 34
Low 32
PLA-RP125BA
PLA-RP125BA2
NOTCH SPL(dB) LINE
High 41
Medium1 39
Medium2 36
Low 34
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
CEILING
UNIT
1.5m
MICROPHONE
61
Page 62
PEAD-RP·JA(L)
Ceiling concealed
2m
Model
PEAD-RP35JA(L) 23-26-29 23-27-30 24-28-31 26-29-33 29-33-37
PEAD-RP50JA(L) 25-30-34 26-31-35 28-32-36 29-33-37 31-35-39
PEAD-RP60JA(L) 25-28-32 25-29-33 26-30-34 27-31-35 29-34-38
PEAD-RP71JA(L) 25-29-34 26-30-34 27-31-35 28-32-36 30-35-39
PEAD-RP100JA(L) 28-33-38 29-34-38 30-35-39 31-36-40 34-40-43
PEAD-RP125JA(L) 31-36-40 33-36-40 33-37-41 34-39-42 37-41-45
Aux.duct
Measurement location
35Pa 50Pa 70Pa 100Pa 150Pa
2m
1.5m
Noise level at anechoic room (Low-Middle-High) Unit: dB(A)
Exrernal static pressure
62
Page 63
PEAD-RP35JA(L)
External static pressure 35Pa
80
High
Middle
Low
External static pressure 100Pa
80
High
Middle
Low
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 50Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 150Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
63
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
Page 64
PEAD-RP50JA(L)
External static pressure 35Pa
80
High
Middle
Low
External static pressure 100Pa
80
High
Middle
Low
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 50Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 150Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
64
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
Page 65
PEAD-RP60JA(L)
External static pressure 35Pa
80
High
Middle
Low
External static pressure 100Pa
80
High
Middle
Low
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 50Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 150Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
65
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
Page 66
PEAD-RP71JA(L)
External static pressure 35Pa
80
High
Middle
Low
External static pressure 100Pa
80
High
Middle
Low
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 50Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 150Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
66
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
Page 67
PEAD-RP100JA(L)
External static pressure 35Pa
80
High
Middle
Low
External static pressure 100Pa
80
High
Middle
Low
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 50Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 150Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
67
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
Page 68
PEAD-RP125JA(L)
External static pressure 35Pa
80
High
Middle
Low
External static pressure 100Pa
80
High
Middle
Low
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 50Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 150Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
80
bar)
70
60
50
40
30
20
Approximate
minimum audible
limit on continuous
noise
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
68
0
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
Page 69
PEAD-RP35EA2
PEAD-RP50EA
70
60
50
40
30
20
10
Approximate minimum
audible limit on
continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 30Pa)
High
Low
NC60
NC50
NC40
NC30
NC20
PEAD-RP35EA2
PEAD-RP50EA
70
60
50
40
30
20
10
Approximate minimum
audible limit on
continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 70Pa)
High
Low
NC60
NC50
NC40
NC30
NC20
PEAD-RP60EA
70
60
50
40
30
20
10
Approximate minimum
audible limit on
continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 30Pa)
High
Low
NC60
NC50
NC40
NC30
NC20
PEAD-RP60EA
70
60
50
40
30
20
10
Approximate minimum
audible limit on
continuous noise
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 70Pa)
High
Low
NC60
NC50
NC40
NC30
NC20
69
Page 70
70
Page 71
SOUND LEVELS
Low-Middle-High
Model Sound level dB (A)
PKA-RP35, 50HAL 36 - 40 - 43
PKA-RP60KAL 39 - 42 - 45
PKA-RP100KAL 41 - 45 - 49
PKA-RP35HAL
PKA-RP50HAL
External static pressure : 0Pa
Power source : 220, 230, 240V, 50Hz
70.0
65.0
60.0
55.0
50.0
45.0
40.0
35.0
30.0
25.0
Approximate minimum
audible limit on
20.0
continuous noise
15.0
Octave band pressure level (dB) 0dB=20 Pa
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
High
Low
NC-60
NC-50
NC-40
NC-30
NC-20
PKA-RP60KAL
External static pressure : 0Pa
Power source : 220, 230, 240V, 50Hz
70.0
65.0
60.0
55.0
50.0
45.0
40.0
35.0
30.0
25.0
20.0
Approximate minimum
audible limit on
15.0
Octave band pressure level (dB) 0dB=20Pa
continuous noise
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
High
Low
PKA-RP100KAL
NC-60
NC-50
NC-40
NC-30
NC-20
UNIT
1m
1m
MICROPHONE
External static pressure : 0Pa
Power source : 220, 230, 240V, 50Hz
WAL
70.0
65.0
60.0
55.0
50.0
45.0
40.0
35.0
30.0
25.0
20.0
Approximate minimum
audible limit on
15.0
continuous noise
Octave band pressure level (dB) 0dB=20Pa
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
High
Low
NC-60
NC-50
NC-40
NC-30
NC-20
71
Page 72
PKA-RP35GAL
PKA-RP50GAL
NOTCH
High
Medium1
Medium2
Low
SPL(dB)
43
41
38
36
LINE
PKA-RP50FAL2
PKA-RP60FAL
NOTCH
High
Low
SPL(dB)39LINE
45
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0 dB = 0.0002 μbar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
UNIT
1m
1m
MICROPHONE
WALL
PKA-RP100FAL
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0 dB = 0.0002 μbar)
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
46
41
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
72
Page 73
10-2. OUTDOOR UNIT
PUHZ-HRP71VHA
PUHZ-HRP100VHA
PUHZ-HRP100YHA
PUHZ-HRP125YHA
90
MODE
COOLING
HEATING
SPL(dB)
52
53
LINE
PUHZ-HRP71VHA2
PUHZ-HRP100VHA2
PUHZ-HRP100YHA2
PUHZ-HRP125YHA2
90
MODE
COOLING
HEATING
SPL(dB)
51
52
LINE
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
NOISE
10
63 125 250 500 1000 2000 4000 8000
MICROPHONE
BAND CENTER FREQUENCIES, Hz
1m
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
UNIT
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1.5m
GROUND
73
Page 74
11
OPTIONAL PARTS
11-1. INDOOR UNIT
Part Name Model Name Applicable model
Remote sensor PAC-SE41TS-E
Remote operation adapter
Multiple remote controller adapter
Remote on/off adapter PAC-SE55RA-E
Power supply terminal kit L/N/Earth PAC-SG96HR-E
L/N PAC-SG97HR-E
Decoration panel
Decoration panel with Wireless remote controller
Decoration panel with Wired remote controller
Automatic filter elevation panel
i-see sensor corner panel
Wireless signal receiver
Space panel
Air outlet shutter plate
Multi-function casement
Flange for fresh air intake
High-efficiency filter element (PAC-SH53TM-E is needed.)
Wired remote controller kit PAR-21MAAT-E PKA-RP•GAL/FAL(2)
(with terminal bed) PKA-RP•HAL/KAL
Drain pump
Motor
(for high external static pressure) PEAD-RP100EA2
Drain lift up mechanism PAC-KE03DM-F PEAD-RP•EA,EA2
Insulation kit PAC-SK010DK PEAD-RP•GA
Filter box
PAC-SF40RM-E (+1)
PAC-SA88HA-E (1 pc.)
PAC-725AD (10 pcs.)
PAC-SG94HR-E
PAC-SH52HR-E
PLP-6BA
PLP-6BALM
PLP-6BAMD
PLP-6BAJ
PAC-SA1ME-E
PAR-SA9FA-E
PAC-SH48AS-E
PAC-SH51SP-E
PAC-SH53TM-E
PAC-SH65OF-E
PAC-SH59KF-E
PAC-SH75DM-E
PAC-SH94DM-E
PAC-SE90DM-E PKA-RP•FAL(2)
PAC-SK003MT-F PEAD-RP125EA
PAC-KE92TB-E
PAC-KE93TB-E
PAC-KE94TB-E PEAD-RP100, 125JA(L)
All models
PEAD-RP•EA(2)
PKA-RP•GAL/FAL(2)
PKA-RP•HAL/KAL
PLA-RP•BA/BA2/BA3
PEAD-RP•GA/JA(L)
PLA-RP•BA/BA2/BA3
PKA-RP•HAL
PKA-RP•KAL
PEAD-RP35, 50JA(L)
PEAD-RP60, 71JA(L)
(+ 1) Unable to use with wireless remote contoller (except for PKA-RP·HAL/KAL).
74
Page 75
11-2. OUTDOOR UNIT
Part Name Model Name
M-NET adapter PAC-SF81MA-E PUHZ-HRP71-125
A-control service tool PAC-SK52ST
Drain socket PAC-SG61DS-E
Air outlet guide (HRP71/100/125 needs 2 pieces.) PAC-SG59SG-E
Air protect guide (HRP71/100/125 needs 2 pieces.) PAC-SH63AG-E
Drain pan PAC-SG64DP-E
Filter dryer
Distribution pipe
Joint pipe
Interface (cased) PAC-IF011B-E
Drain hose heater
(Unit Extension pipe)
(:9.52)
(Twin)
(:15.88 :19.05)
PAC-SG82DR-E
MSDD-50TR-E
PAC-SG75RJ-E
PAC-IF012B-E PUHZ-HRP71-125
PAC-SE60RA-E PUHZ-HRP71-125·HA2R1
Applicable model
PUHZ-HRP71-125
PUHZ-HRP71-125
PUHZ-HRP71-125
PUHZ-HRP71-125
PUHZ-HRP71-125
PUHZ-HRP71-125
PUHZ-HRP71-125
PUHZ-HRP71-125
PUHZ-HRP71-125
75
Page 76
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Mar. 2010 No.OCS11 REVISED EDITION-B PDF 4
Distributed in Sep. 2008 No.OCS11 REVISED EDITION-A PDF 6
Distributed in Oct. 2007 No.OCS11 PDF 7
Made in Japan
New publication, effective Mar. 2010
Specifications subject to change without notice.