Before obtaining access to terminal, all supply circuits must be disconnected.
Preparation before the repair service.
• Prepare the proper tools.
• Prepare the proper protectors.
• Provide adequate ventilation.
• After stopping the operation of the air conditioner, turn off the power-supply beaker.
• Discharge the condenser before the work involving the electric parts.
Precautions during the repair service.
• Do not perform the work involving the electric parts with wet hands.
• Do not pour water into the electric parts.
• Do not touch the refrigerant.
• Do not touch the hot or cold areas in the refrigerating cycle.
• When the repair or the inspection of the circuit needs to be done without turning off the power,
exercise great caution not to touch the live parts.
1-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Tools for R410A
Gauge manifold
Charge hose
Gas leak detector
Torque wrench
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction
of compressor.
Vacuum pump adaptor
Electronic refrigerant
charging scale
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency
will be lowered.
2
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.Tool nameSpecifications
Gauge manifold· Only for R410A
1
· Use the existing fitting
· Use high-tension side pressure of 5.3 MPa·G or over.
Charge hose· Only for R410A
2
· Use pressure performance of 5.09 MPa·G or over.
Electronic scale
3
Gas leak detector· Use the detector for R134a, R407C or R410A.
4
Adaptor for reverse flow check· Attach on vacuum pump.
5
Refrigerant charge base
6
Refrigerant cylinder· Only for R410A Top of cylinder (Pink)
7
Refrigerant recovery equipment
8
specifications
—
—
Cylinder with syphon
—
. (UNF1/2)
3
1-3. CAUTIONS FOR REFRIGERANT PIPING WORK
Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materialsUseR410A toolsCan R22 tools be used?
Gauge manifold
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
Air purge, refrigerant charge
and operation check
Gas leak check
Refrigerant recovery
Refrigerant charge
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Bend the pipes
Cut the pipes
Weld the pipes
Charge refrigerant
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Refrigerant charge
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adapter for reverse flow check
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
Quantitykg (lbs)7.1 (15.7)
Guaranteed operating
range (Outdoor)
Outlet water temp.
(Max. in heating, Min. in cooling)
Nominal return water
temperature range
Heating°C-25 ~ +35
Cooling°C-5 *
Heating°C+60
Cooling°C+5
Heating°C+10 ~ +59
Cooling°C+8 ~ +28
Water fl ow rate rangeL/min28.7 ~ 68.9
A9.6
A13.7
%95
%95
LP switch
Discharge thermo
kW0.150 × 2
(CFM)(4,940)
mm (in.)
mm (in.)
mm (in.)
1050 (41-5/16)
330 + 30 *³ (13+1-3/16)
1338 (52-11/16)
4
~ +46
Maximum outlet water temperature
65
]
㷄
60
55
50
45
Maximum outlet water temptemperature [
40
-25-20-15-10 -5 0 5 10
*1 Hot gas with 4-way valve
*2 at distance of 1m from outdoor unit
*3 grill
*4 With the optional air outlet guide, the operation at
-15㷄 outdoor temperature is possible.
Ambient tem perature [㷄]
6
3
DATA
3-1. Addition of refrigerant
At time
of
shipping
30 m and less31-40 m41-50 m51-60 m61-70 m71-80 m
Total piping length (one way)
Amount of additional refrigerant charge (kg)
For single combination
(1 indoor unit)
For twin / triple /
quadruple combination
(2-4 indoor units)
When length exceeds 50 m for twin / triple / quadruple combination
When the total length of the piping exceeds 50 m, calculate the amount of additional charge based on the following requirements.
Note: If the calculation produces a negative number (i.e. a “minus” charge), of if calculation results in an amount that is less than the “Additional charage amount for 50 m”,
perform the additional charge using the amount shown in “Additional charge amount for 50 m”.
Amount of additional
charge
Additional charge amount
for 50 meters
7.1 kg
Main piping:
Liquid line size
ø12.7 overall length ×
=
0.17
(kg)
<Limits of refrigerant piping installation>
No additional
charge necessary
+++–
(m) × 0.17 (kg/m)
1.8 kg
A: Main piping
B, C, D, E: Branch
HRP200 : A+B+C(+D)(+E) ≤ 80 m
* “D” is for triple“.
* “E” is for four (quadruple).
1.4 kg2.8 kg
0.9 kg1.8 kg
Main piping:
Liquid line size
ø9.52 overall length ×
0.14 (Gas line: ø25.4)
(m) × 0.14 (kg/m)
Indoor unit
Outdoor unit
Multi distribution pipe (option)
Height difference (Indoor unitOutdoor unit) Max. 30 m
Height difference (Indoor unitIndoor unit) Max. 1 m
piping
Max. 20m
Branch piping:
Liquid line size
ø9.52 overall length ×
0.05 (Gas line: ø15.88)
(m) × 0.05 (kg/m)
Permissible total
piping length
A+B+C+D+E
80 m and less
|
B-C|or|B-D|or
|
B-E|or|C-D|or
|
C-E|or|D-E
8 m and less
4.2 kg5.6 kg7.0 kg
Calculate the amount of additional refrigerant
charge using formula provided below.
Branch piping:
Liquid line size
ø6.35 overall length ×
0.02
(m) × 0.02 (kg/m)
A+B or A+C
or
A+D or A+E
70 m and less
No. of bends
|
Within 15
Charge-less
piping length
A+B+C+D+E
30 m and less
4.3 (kg)
3-2. NOISE CRITERION CURVES
MICROPHONE
1m
1.5m
UNIT
GROUND
PUHZ-HRP200YKA
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
NOISE
10
631252505001000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MODE
COOLING
HEATING
SPL(dB)
58
59
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
7
3-3. Standard operation data Reference data (connect to Plate HEX)
(ACH50-50 plates) o 2 pcs [connected in parallel]
Mode
Cooling
(A35/W7)
CapacityW20,000 23,000
Total
InputkW9.016.31
Outdoor unitPUHZ-HRP200YKA
Phase, Hz3, 50
VoltageV400
CurrentA13.79.6
Electrical circuit
Discharge pressureMPa3.02.0
Suction pressureMPa0.70.6
Discharge temperatureºC7973
Heating
(A7/W35)
Condensing temperature
ºC4935
Suction temperatureºC88
Evaporating temperature
Evaporator inlet temperature
Refrigerant circuit
Evaporator outlet temperature
Condenser inlet temperature
Condenser outlet temperature
ºC62
ºC7——
ºC6——
ºC——65
ºC——34
Flow volumeL/min57.365.9
Water
Outlet water temperature
conditions
Intake air
temperature
Outdoor
conditions
Piping length : Main 2.5m, Branch 2.5m / 2.5m
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1 (MPa) = 10.2 (kgf/cm²)
Cooling and heating capacity is lowered according to the piping length. Capacity can be obtained by referring to the following
capacity curves.
Corrected pipe length (m) = actual pipe length (m) + number of bends × 0.3 (m)
100
95
90
85
80
Capacity ratio [%]
75
70
5 101520253035404550556065707580
Corrected pipe length [m]
8
Cooling
Heating
HRP200
HRP200
4
OUTLINES AND DIMENSIONS
PUHZ-HRP200YKA
19
225
2-U Shaped notched holes
(Foundation Bolt M10)
600
Rear Air Intake
Installation Feet
225
417
370
330
40
53560
28
42
2-12×36 Oval holes
60
70
30
Terminal connection
Left···Power supply wiring
Right···Indoor/Outdoor wiring
(Foundation Bolt M10)
1050
Earth terminal
Air Discharge
362
Service panel
Handle for moving
632
1338
Air intake
986
982
1
2
Brazing
369
*1,*2 : 442
*1 450
342
Rear piping cover
Front piping cover
81
26
Bottom piping hole
(Knockout)
86
Drain hole
154136
Unit: mm
(5-ø33)
110 160160160
45
Side Air Intake
4 PIPING-WIRING DIRECTIONS
Piping and wiring connections
can be made from 4 directions:
FRONT,Right,Rear and Below.
FOUNDATION
<Foundation bolt height>
FREE
30
Less than
500
Over
10
Over
Service space
Over 10mm
Over 10mm
500
Over
3 FOUNDATION BOLTS
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
150
Over
2 SERVICE SPACE
Dimensions of space needed
for service access are
shown in the below diagram.
1 FREE SPACE (Around the unit)
The diagram below shows a
basic example.
Explanation of particular details are
given in the installation manuals etc.
Handle for moving
Side Air Intake
Rear Air Intake
Over 150mm
Over 1000mm
Handle for
moving
Handle for
moving
Power supply wiring hole
(ø40Knockout)
Rear trunking hole
(Knockout)
60
6055
Power supply wiring hole
(ø27Knockout)
Power supply wiring hole
(ø40Knockout)
Power supply wiring hole
(ø27Knockout)
Power supply wiring hole
(ø27Knockout)
6373
Right trunking hole
(Knockout)
60
75 50
63
27
92
Right piping hole
(Knockout)
6373
60 55
60
Rear piping hole
ø92
27
55
26
ø92
55
73
26
27
55
92
ø92
(Knockout)
92
75
29 92
26
75
···Refrigerant GAS pipe connection (attached JOINT)ø25.4(Brazing locally)
Switch
Switch<Pump Down
Connector<Emergency Operation
LED<Operation Inspection Indicators
Fuse<T6.3AL250V
Connector<Connection for Option
Connector<Connection for Option
Connector<A-Control Service Inspection Kit
Connector
<
Connected to Optional M-NET Adapter Board
Connector
<
Connected to Optional M-NET Adapter Board
Connector
<
Connected for Option (Contact Input)
Connector<Connection for Option>
Connector<Connection for Option>
Relay
>
>
>
>
>
>
>
>
>
>
INDOOR
UNIT
POWER
SUPPLY
3N~
400V 50Hz
MF1
MS
3~
MF2
MS
3~
TB2
S1
S2
S3
C.B.
1
1
CNS
(WHT)
CY1
3
CY2
1
ORN
BRN
TB1
L1
L2
L3
N
CNF1
(WHT)
7
CNF2
(WHT)
7
3
1
2
CNDC
(PNK)
YLW
RED
WHT
BLK
BLU
GRN/YLW
TH7TH3 TH4
TH6
TH32
t°t° t° t°
2
1
TH7/6
TH32
(RED)
(BLK)
TRANS
CNAC
(WHT)
12
3
RED
WHT
FUSE1
FUSE2
RED
WHT
N. F.
LI 1
LI 2
LI 3
NI
4
UU
U
U
4121
(WHT)
U
TH3
BLK
t°
21
TH4
(WHT)
7
2
2
RS
RED
CNAC1
63H
(YLW)
CN2
(WHT)
F3
F4
(WHT)
63H
31
7
P. B.
7
(WHT)
1
2
1
2
1
BLK
BLK
TB-P1
63L
63L
(RED)
71
CN2
CN4
(WHT)
CN5
(RED)
X52A
DCL
31
31
63HS
63HS
(WHT)
LEV-ALEV-B
MM
31
LEV-A
(WHT)
LED1
LED2
CN4
(WHT)
2
1
2
21S4
TB-P2
GD2GD1
BLK
61
LEV-B
(RED)
1
5
1
LEV-C
(BLU)
X52
13
21S4
(GRN)
RED
CB1CB2
CNDC
(PNK)
2
LEV-C
M
3
5
61
3151
CNVMNT
CNMNT
(WHT)
(WHT)
CNM
(WHT)
6
X54
13
SV1
(GRY)
SC-W
SC-V
SC-U
TB-C1TB-N1
WHT
CNCT
(RED)
31
WHT
2
U
13
CNL
(BLU)
WHT
14
5
TB-L3
TB-L2
TB-L1
BLK
SW5SW8SW4SWP
X51
13
SS
(WHT)
+1+1
SW6SW1
CN31
WHT
RED
CNAC2
(RED)
3112
LO 1
LO 2
LO3
ACL4
BLK
SW7
SW9
1
3
(WHT)
CNDM
1
CN51
(WHT)
5
BLK
WHT
RED
RED
WHT
BLK
When M-NET adapter is connected
5
+3
ABS
MC
W
V
MS
3~
U
+1 MODEL SELECT
MODEL
ON
HRP
OFF
200Y
+2 SW5 -1 to 5 : Function Switch.
+3 Setting of the starting ambient temp. of the
flash Injection.
indicates a switch position.
Ambient temp.
3°C or less
(lnitial setting)
0°C or less
-3°C or less
-6°C or less
+4 SW9-1 to 2 : Function Switch
5
SW11
SW1
CN5
(WHT)
1
LED2
SW12
LED3
LED4
M-NET SUBSTRATE
2
CND
1
(WHT)
CN2M
(WHT)
31
LED1
LED5
3
TB7
M-NET
SW6
12345678
SW9-3.4 +4
ON
OFF
1234
ON
OFF
1234
ON
OFF
1234
ON
OFF
1234
SW5-6 +2
ON
OFF
123456
10
WIRING SPECIFICATIONS6
D
For Heater
L
N
* With Heater
model only
S1
S2
S3
E
A
B
S2S1LN
S3
C
E
D
For PowerFor Power
For HeaterFor HeaterFor Heater
DDDD
B
E
Note: Only for Air to water application
When multiple indoor units (Hydro boxes) are connected to the outdoor unit, wire the PCB of either one of the indoor unit and the outdoor unit (S1,S2,S3).
It is impossible to connect the PCBs of multiple indoor units to the outdoor unit.
A Indoor unit
B Outdoor unit
C Remote controller
D Main switch (Breaker)
E Earth
C
AAA
EE
E
FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit modelHRP200Y
Outdoor unit power supply
Outdoor unit input capacity Main switch (Breaker)*132 A
*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
*2. Max. 80 m Total Max. including all indoor/indoor connection is 80 m.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The fi gures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
Outdoor unit power supply5 × Min. 4
)
2
Indoor unit-Outdoor unit*2
Wiring
Indoor unit-Outdoor unit earth*21 × Min. 2.5
Wire No. ×
size (mm
Remote controller-Indoor unit*32 × 0.3 (Non-polar)
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2*4AC 230 V
Indoor unit-Outdoor unit S2-S3*4DC 24 V
Circuit rating
Remote controller-Indoor unit*4DC 12 V
• Use one cable for S1 and S2 and another for S3 as shown in the picture.
*4AC 230 V
3N~ (3 ph 4-wires),
50 Hz, 400 V
Cable length 50m:3×4 (Polar)/
Cable length 80m:3×6 (Polar)
Notes: 1. Wiring size must comply with the applicable local and national code.
2.
(Design 60245 IEC 57
3. Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.
Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed fl exible cord.
)
Caution: Be sure to install N-line. Without N-line, it could cause damage to the unit.
Power supply
Isolator
S1
A-Control
Outdoor Unit
S2
S3
Warning:
· In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation
between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3
terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
· Turn on the main power when the ambient temperature is - 20°C or higher.
· In below - 20°C condition, it needs at least 4hr stand by to operate in order to warm the electrical parts.
3 poles isolator
S1
S2
S3
A-Control
Indoor Unit
11
INDOOR-OUTDOOR CONNECTING CABLE (HRP200)
Cross section of cableWire size (mm2) Number of wiresPolarityL (m)*6
Round
Flat
Flat
Round
2.53
2.53
1.54
2.54
Clockwise : S1-S2-S3
*Pay attention to stripe of yellow and green
Not applicable
(Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Clockwise : S1-S2-S3-Open
*Connect S1 nad S3 to the opposite angle
Not applicable
(30)
*2
*5
(18)
*3
(30)
*4
*1 :Power supply cords of appliances shall not be lighter than design 60245 IEC or
227 IEC.
*2 :In case that cable with stripe of yellow and green is available.
*3 :In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm
*4 :In case of regular polarity connection (S1-S2-S3).
*5 :In the flat cables are connected as this picture, they can be used up to 30 m.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication error if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at
the intermediate connection point.
2
.
S1
S2
S3
*6 :Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or
materials, etc.
Outlet water temperature thermistorFor fl ow temp. controller
Liquid pipe temperature thermistorFor fl ow temp. controller
<Reference>
System example
13
TROUBLESHOOTING8
8-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the control board of outdoor unit. Actions to be taken for service,
which depends on whether or not the trouble is reoccurring at service, are summarized in the table below. Check the contents
below before investigating details.
Unit conditions at serviceError codeActions to be taken for service (summary)
The trouble is reoccurring.
The trouble is not reoccurring.
Displayed
Not displayed
Logged
Not logged
Judge what is wrong and take a corrective action according to
“8-3. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the
trouble.
Consider the temporary defects such as the work of
1
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc. Recheck the symptom, and check the installation environment,
refrigerant amount, weather when the trouble occurred,
matters related to wiring and etc.
Reset error code logs and restart the unit after fi nishing
2
service.
There is no abnormality in electrical component, controller
3
board, and etc.
Re-check the abnormal symptom.
1
Conduct troubleshooting and ascertain the cause of the
2
trouble.
Continue to operate unit for the time being if the cause is
3
not ascertained.
There is no abnormality concerning of parts such as
4
electrical component, controller board, and etc.
14
8-2. CHECK POINT UNDER TEST RUN
Before test run
• After installation of outdoor unit, piping work and electric wiring work, re-check that there is no water leakage, loosened con-
nections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block (L, N) on the outdoor unit by 500 V Megger
and check that it is 1.0 M or over.
• Turn on power supply 12 hours before test run in order to protect compressor.
• Make sure to read operation manual before test run. (Especially items to secure safety.)
Warning:
Do not use the system if the insulation resistance is less than 1.0 MΩ.
Caution:
Do not carry out this test on the control wiring (low voltage circuit) terminals.
Self-check
Turn on the power.
1
Press [CHECK] button twice.
2
Press [CHECK] button twice to fi nish self-check.
3
CHECK button B IC : Interface or FTC unit OC : Outdoor unit C Check code
A
Check codeSymptom
P1Flow water (TH1) sensor error
P2Refrigerant liquid Pipe (TH2) sensor error
P6Freezing/Overheating protection operation
P9Actual tank temp. (TH5) sensor error
FbFTC unit control system error (memory error, etc.)
E0~E5Signal transmission failure between remote controller and FTC.
E6~EFSignal transmission failure between outdoor unit and FTC.
– – – –No trouble generated in the past.
FFFFNo corresponding unit
U*, F*Outdoor unit failure. Refer to the outdoor unit wiring diagram.
TEMP.
ERROR CODE
ON/OFF
For description of each LED (LED1~5) provided on the FTC, refer to the following table.
LED 1 (Power for microprocessor)Indicates whether control power is supplied. Make sure that this LED is always lit.
LED 2 (Power for remote controller)Indicates whether power is supplied to the remote controller. This LED lights only in
the case of the FTC unit which is connected to the outdoor unit refrigerant address “0“.
LED 3 (Communication between FTC
and outdoor unit)
Indicates state of communication between the FTC and outdoor unit. Make sure that
this LED is always blinking.
LED 4—
LED 5—
15
8-3. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
Error Code
Abnormal point and detection method
1 No voltage is supplied to termi-
nal block(TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or disconnec-
tion of power supply
terminal
c) Open phase (L or N phase)
2 Electric power is not charged to
power supply terminal of outdoor power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board
Case
Judgment and action
1 Check following items.
a) Power supply breaker
b) Connection of power supply terminal block
(TB1)
c) Connection of power supply terminal block
(TB1)
2 Check following items.
a) Connection of power supply terminal block
(TB1)
b) Connection of terminal on outdoor
power circuit board
None
F3
F5
—
63L connector open
Abnormal if 63L connector circuit is open
for 3 minutes continuously after power supply.
63L: Low-pressure switch
63H connector open
Abnormal if 63H connector circuit is open
for 3 minutes continuously after power supply.
63H: High-pressure switch
3 Electric power is not supplied
to outdoor controller circuit
board.
a) Disconnection of connector
(CNDC)
4 Disconnection of reactor (DCL
or ACL)
5 Disconnection of outdoor noise
filter circuit board or parts failure in outdoor noise filter circuit
board
6 Defective outdoor power circuit
board
7 Defective outdoor controller
circuit board
1 Disconnection or contact failure
of 63L connector on outdoor
controller circuit board
2 Disconnection or contact failure
of 63L
3 63L is working due to refriger-
ant leakage or defective parts.
4 Defective outdoor controller
circuit board
1 Disconnection or contact failure
of 63H connector on outdoor
controller circuit board
2 Disconnection or contact failure
of 63H
3 63H is working due to defective
parts.
4 Defective outdoor controller
circuit board
3 Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector CNDC on
the outdoor noise filter. Refer to 8-7.
4 Checkconnection of reactor. (DCL or ACL)
5 a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 8-7.
6 Replace outdoor power circuit board.
7 Replace controller board (When items above
are checked but the units can not be repaired).
1 Check connection of 63L connector on
outdoor controller circuit board.
Refer to 8-7.
2 Check the 63L side of connecting wire.
3 Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
1 Check connection of 63H connector on
outdoor controller circuit board.
Refer to 8-7.
2 Check the 63H side of connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
F9
2 connector open
Abnormal if both 63H and 63L connector
circuits are open for three minutes continuously after power supply.