Mitsubishi PUHY-RP_Y(S)JM-A, PURY-RP_YJM-A DATA BOOK

MODEL
DATA BOOK
REPLACE MULTI
1.OUTDOOR UNIT
Y SERIES ................................................................................................................. 1
R2 SERIES............................................................................................................. 57
3.SYSTEM DESIGN
Y SERIES ............................................................................................................. 177
R2 SERIES........................................................................................................... 229
4.CONTROLLER ................................................................................................. 273
Y SERIES
OUTDOOR UNITS
I.Y SERIES
1. SPECIFICATIONS........................................................................................................................................... 2
2. EXTERNAL DIMENSIONS .............................................................................................................................. 15
3. CENTER OF GRAVITY ................................................................................................................................... 19
4. ELECTRICAL WIRING DIAGRAMS................................................................................................................ 20
5. SOUND LEVELS ............................................................................................................................................. 21
6. CAPACITY TABLES........................................................................................................................................ 25
6-1. Correction by temperature....................................................................................................................... 25
6-2. Correction by total indoor......................................................................................................................... 35
6-3. Correction by refrigerant piping length..................................................................................................... 39
6-4. Correction at frost and defrost ................................................................................................................. 42
6-5. Operation temperature range .................................................................................................................. 43
7. OPTIONAL PARTS.......................................................................................................................................... 44
7-1. OUTDOOR TWINNING KIT..................................................................................................................... 44
8. UNIT SELECTION........................................................................................................................................... 45
8-1. Indoor and outdoor unit selection ............................................................................................................ 45
8-2. Calculation samples................................................................................................................................. 47
8-3. Pipe diameter correction factor ................................................................................................................ 50
OUTDOOR UNITS
1
1. SPECIFICATIONS
I.Y SERIES1. SPECIFICATIONS
Model PUHY-RP200YJM-A(-BS) PUHY-RP250YJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 22.4 28.0
(Nominal) *1 kcal / h 19,300 24,100
*1 BTU / h 76,400 95,500
Power input kW 5.68 8.28
Current input A 9.5-9.1-8.7 13.9-13.2-12.7
COP kW / kW 3.94 3.38
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F) 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F) -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 25.0 31.5
(Nominal) *2 kcal / h 21,500 27,100
Power input kW 5.69 7.83
Current input A 9.6-9.1-8.7 13.2-12.5-12.1
COP kW / kW 4.39 4.02
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F) 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F) -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~17 P15~P250 / 1~21
Sound pressure level (measured in anechoic room) dB <A> 56 57
Refrigerant Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed
piping diameter Gas pipe mm (in.) 28.58(1-1/8) Brazed 28.58(1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.8 6.8
Case heater kW 0.035(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit LEV and HIC circuit
Net weight kg (lbs) 230(508) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C666 KD94C666
Wiring KE94C427 KE94C427
Standard attachment Document Installation Manual Installation Manual
Accessory Refrigerant conn. pipe Refrigerant conn. pipe
Optional parts
*2 BTU / h 85,300 107,500
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5 Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
Header: CMY-Y104/108/1010-G Header: CMY-Y104/108/1010-G
type)
(601,479 psi)
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pressure switch at 4.15,3.3MPa
type)
(601,479 psi)
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS 2
1. SPECIFICATIONS
Model PUHY-RP300YJM-A(-BS) PUHY-RP350YJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 33.5 40.0
(Nominal) *1 kcal / h 28,800 34,400
*1 BTU / h 114,300 136,500
Power input kW 9.37 12.28
Current input A 15.8-15.0-14.4 20.7-19.6-18.9
COP kW / kW 3.57 3.25
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F) 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F) -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 37.5 45.0
(Nominal) *2 kcal / h 32,300 38,700
Power input kW 9.86 13.12
Current input A 16.6-15.8-15.2 22.1-21.0-20.2
COP kW / kW 3.80 3.42
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F) 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F) -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~26 P15~P250 / 1~30
Sound pressure level (measured in anechoic room) dB <A> 59 60
Refrigerant Liquid pipe mm (in.) 12.7(1/2) Brazed 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58(1-1/8) Brazed 34.93(1-3/8) Brazed
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.2 9.9
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C666 KD94C666
Wiring KE94C427 KE94C427
Standard attachment Document Installation Manual Installation Manual
Accessory Refrigerant conn. pipe Refrigerant conn. pipe
Optional parts
*2 BTU / h 128,000 153,500
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
Header: CMY-Y104/108/101 0-G Header: CMY-Y104/108/101 0-G
type)
(601,479 psi)
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pre ssure switch at 4.15,3.3MPa
type)
(601,479 psi)
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS
3
1. SPECIFICATIONS
Model PUHY-RP400YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 45.0
(Nominal) *1 kcal / h 38,700
*1 BTU / h 153,500
Power input kW 11.87
Current input A 20.0-19.0-18.3
COP kW / kW 3.79
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 50.0
(Nominal) *2 kcal / h 43,000
Power input kW 11.38
Current input A 19.2-18.2-17.5
COP kW / kW 4.39
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 59
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP200YJM-A(-BS) PUHY-RP200YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 6.5kg (15lbs)
Net weight kg (lbs) 230(508) 230(508)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.8 4.8
Case heater kW 0.035(240 V) 0.035(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 170,600
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5 Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/1010-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pressure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS 4
1. SPECIFICATIONS
Model PUHY-RP450YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-41 5V 50/60Hz
Cooling capacity *1 kW 50.0
(Nominal) *1 kcal / h 43,000
*1 BTU / h 170,600
Power input kW 14.40
Current input A 24.3-23.0-22.2
COP kW / kW 3.47
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 56.0
(Nominal) *2 kcal / h 48,200
Power input kW 13.42
Current input A 22.6-21.5-20.7
COP kW / kW 4.17
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 59.5
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP200YJM-A(-BS) PUHY-RP250YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 230(508) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 19.05(3/4) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.8 6.8
Case heater kW 0.035(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 191,100
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/101 0-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pre ssure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS
5
1. SPECIFICATIONS
Model PUHY-RP500YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 56.0
(Nominal) *1 kcal / h 48,200
*1 BTU / h 191,100
Power input kW 16.96
Current input A 28.6-27.1-26.2
COP kW / kW 3.30
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 63.0
(Nominal) *2 kcal / h 54,200
Power input kW 15.67
Current input A 26.4-25.1-24.2
COP kW / kW 4.02
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 60
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 6.8 6.8
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 215,000
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5 Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/1010-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pressure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS 6
1. SPECIFICATIONS
Model PUHY-RP550YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-41 5V 50/60Hz
Cooling capacity *1 kW 63.0
(Nominal) *1 kcal / h 54,200
*1 BTU / h 215,000
Power input kW 18.58
Current input A 31.3-29.7-28.7
COP kW / kW 3.39
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 69.0
(Nominal) *2 kcal / h 59,300
Power input kW 17.69
Current input A 29.8-28.3-27.3
COP kW / kW 3.90
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 61
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) B razed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 6.8 8.2
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 235,400
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/101 0-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pre ssure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS
7
1. SPECIFICATIONS
Model PUHY-RP600YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 69.0
(Nominal) *1 kcal / h 59,300
*1 BTU / h 235,400
Power input kW 19.94
Current input A 33.6-31.9-30.8
COP kW / kW 3.46
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 76.5
(Nominal) *2 kcal / h 65,800
Power input kW 20.13
Current input A 33.9-32.2-31.1
COP kW / kW 3.80
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP300YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.2 8.2
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 261,000
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5 Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/1010-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pressure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS 8
1. SPECIFICATIONS
Model PUHY-RP650YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-41 5V 50/60Hz
Cooling capacity *1 kW 73.0
(Nominal) *1 kcal / h 62,800
*1 BTU / h 249,100
Power input kW 22.00
Current input A 37.1-35.2-34.0
COP kW / kW 3.31
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 81.5
(Nominal) *2 kcal / h 70,100
Power input kW 22.70
Current input A 38.3-36.4-35.0
COP kW / kW 3.59
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP300YJM-A(-BS) PUHY-RP350YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7(1/2) B razed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 28.58(1-1/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.2 9.9
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 278,100
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/101 0-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pre ssure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS
9
1. SPECIFICATIONS
Model PUHY-RP700YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 80.0
(Nominal) *1 kcal / h 68,800
*1 BTU / h 273,000
Power input kW 23.59
Current input A 39.8-37.8-36.4
COP kW / kW 3.39
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 88.0
(Nominal) *2 kcal / h 75,700
Power input kW 21.35
Current input A 36.0-34.2-33.0
COP kW / kW 4.12
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 61.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP200YJM-A(-BS) PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Inverter
Motor output kW 4.8 6.8 6.8
Case heater kW 0.035(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over- heat protection Over-heat protection Over -heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 230(508) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 19.05(3/4) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 300,300
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Ove r-current pro-
Header: CMY-Y104/108/1010-G
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS 10
1. SPECIFICATIONS
Model PUHY-RP750YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 85.0
(Nominal) *1 kcal / h 73,100
*1 BTU / h 290,000
Power input kW 25.70
Current input A 43.3-41.2-39.7
COP kW / kW 3.30
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 95.0
(Nominal) *2 kcal / h 81,700
Power input kW 23.63
Current input A 39.8-37.8-36.5
COP kW / kW 4.02
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Invert er
Motor output kW 6.8 6.8 6.8
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over-heat protection Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 324,100
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
Over-heat protection, Over-current pro-
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
tection
Header: CMY-Y104/108/1010-G
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS
11
1. SPECIFICATIONS
Model PUHY-RP800YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 90.0
(Nominal) *1 kcal / h 77,400
*1 BTU / h 307,100
Power input kW 27.19
Current input A 45.9-43.6-42.0
COP kW / kW 3.31
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 100.0
(Nominal) *2 kcal / h 86,000
Power input kW 25.44
Current input A 42.9-40.7-39.3
COP kW / kW 3.93
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Inverter
Motor output kW 6.8 6.8 8.2
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over- heat protection Over-heat protection Over -heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 341,200
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Ove r-current pro-
Header: CMY-Y104/108/1010-G
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS 12
1. SPECIFICATIONS
Model PUHY-RP850YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 96.0
(Nominal) *1 kcal / h 82,600
*1 BTU / h 327,600
Power input kW 28.57
Current input A 48.2-45.8-44.1
COP kW / kW 3.36
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 108.0
(Nominal) *2 kcal / h 92,900
Power input kW 27.97
Current input A 47.2-44.8-43.2
COP kW / kW 3.86
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 63.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP300YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Invert er
Motor output kW 6.8 8.2 8.2
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over-heat protection Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 368,500
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
Over-heat protection, Over-current pro-
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
tection
Header: CMY-Y104/108/1010-G
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS
13
1. SPECIFICATIONS
Model PUHY-RP900YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 101.0
(Nominal) *1 kcal / h 86,900
*1 BTU / h 344,600
Power input kW 29.61
Current input A 49.9-47.4-45.7
COP kW / kW 3.41
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 113.0
(Nominal) *2 kcal / h 97,200
Power input kW 29.73
Current input A 50.1-47.6-45.9
COP kW / kW 3.80
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 64
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP300YJM-A(-BS) PUHY-RP300YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Inverter
Motor output kW 8.2 8.2 8.2
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over- heat protection Over-heat protection Over -heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 385,600
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Ove r-current pro-
Header: CMY-Y104/108/1010-G
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS 14
2. EXTERNAL DIMENSIONS
172
143
142
ø15.88 Brazed
(
ø12.7 Brazed) (ø28.58 Brazed)
ø34.93 Brazed
ø12.7 Brazed
ø28.58 Brazed
(
ø22.2 Brazed)
ø28.58 Brazed
(
ø19.05 Brazed)
PUHY-RP350YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
ø12.7 Brazed
(
ø9.52 Brazed)
BA
GasLiquid
GasLiquid
Connection specifications for
the refrigerant service valve
PUHY-RP250YJM-A(-BS)
PUHY-RP200YJM-A(-BS)
Position dimensions
for the refrigerant
service valve
(Mounting pitch)
(Mounting pitch)
Refrigerant service
valve <gas>
Refrigerant service
valve <liquid>
Model
Connecting pipe specifications
2×2-14×20 Oval hole
Refrigerant service
valve <gas>
Refrigerant service
valve <liquid>
ø34 Knockout hole
ø52 Knockout hole
ø52 or ø27 Knockout hole
ø65 or ø40 Knockout hole
150 × 92 Knockout hole
102 × 72 Knockout hole
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Front through hole
For transmission cables
For wires
For pipes
SpecificationsUsage
NO.
Note1. Please refer to (2/2) for information
regarding necessary spacing around the
unit and foundation work.
2. The detachable leg can be removed at site.
3. At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120°C.
<Accessories>
Connecting pipe
<Gas> · Elbow (IDø25.4 × ODø25.4)
· Pipe (IDø25.4 × ODø19.05)
· Pipe (IDø25.4 × ODø22.2)
· Pipe (IDø25.4 × ODø28.58)
· Pipe (IDø25.4 × ODø34.93)
<Liquid>
· Pipe (IDø9.52 × ODø9.52)
· Pipe (IDø9.52 × ODø12.7)
· Pipe (IDø12.7 × ODø12.7)
· Pipe (IDø12.7 × ODø15.88)
···RP200, RP250, RP300, RP350
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
···RP200
···RP250, RP300
···RP200, RP250, RP300, RP350
···RP350
···RP200, RP250, RP300
···RP200, RP250, RP300
···RP350
···RP350
*2 *2
*2
*2
*2
221 150
145
*1
*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*2 Indicates dimensions and connection specifications in the case the unit is
used in combination with other outdoor units.
83
(front and back, 2 points)
Note 2*
5555
60 60
760
A
B
(60)
Detachable leg
(60)
1710
72
(760)
Control box
80 760 80
18
724 (721~727)
18
92 86
131
251
186
132
6
5
4
3
2
1
25
Intake
air
90
204
102
251
240
Intake
air
Service
panel
1410
1650
760
920
88
25
54
Intake
air
Discharge air
145
98
Front view
Left side view
Top view
Bottom view
PUHY-RP200, 250, 300, 350YJM-A (-BS)
Unit : mm
2. EXTERNAL DIMENSIONS
OUTDOOR UNITS
15
2. EXTERNAL DIMENSIONS
Secure enough space around the unit as shown in the figure below.
When the height of the walls on the front, back or on the sides <H>
exceeds the wall height limit as defined below, add the height
that exceeds the height limit <h> to the figures that are marked
with an asterisk.
1. Required space around the unit
In case of single installation
2. Foundation work
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm from
the unit bottom
Side: Up to the unit height
<field supply required>
<field supply required>
Detachable leg
Detachable leg
Corner of the
installation leg
M10 anchor bolt
<field supply required>
30 mm max.
• With a space of at least
300 mm to the wall on
the back of the unit
With a space of at least
100 mm to the wall on
the back of the unit
30 mm max.
<Side view>
H
h
h
H
Front
<Top view> <Top view>
Front
Corner of the
installation leg
M10 anchor bolt
<field supply required>
Front
Unit height
<To be left open>
<To be left open>
<To be left open>
<To be left open>
<To be left open>
<To be left open>
<To be left open>
30 min.
450 min.
450 min.
15 min.*
15 min.*
50 min.*
50 min.*
300 min.*
450 min.*
100 min.*
450 min.*
300 min.*450 min.*
100 min.*450 min.*
100 min.
450 min.*
450 min.
450 min.
100 min.*
15 min.*
300 min.*900 min.300 min.*
300 min.*900 min.
1000 min.*
500
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.
In case of collective installation
When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h>
to the figures that are marked with an asterisk.
If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000 mm or more as inlet space/
passage space for each six units.
Take into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure. (Fig.A, B)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30 mm. (Fig.A, B)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.C, D)
To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
<Unit: mm>
Front
Front
Wall <H>
Wall <H>
Wall <H>
Wall <H>
Wall <H>
Wall <H> Wall <H>
Wall <H>
<To be left open>
<To be left open>
Front
<To be left open>
<Unit: mm>
Front
Wall <H>
Wall <H>
Front
Front
Front
Front
Front
Front
Fixing plate
Fixing plate
Fig.D (with detachable legs)
Fig.C (without detachable legs)
Fig.B (with detachable legs)
Fig.A (without detachable legs)
PUHY-RP200, 250, 300, 350YJM-A (-BS)
Unit : mm
OUTDOOR UNITS 16
2. EXTERNAL DIMENSIONS
Detachable leg
Note 2*
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. The detachable leg can be removed at site.
3. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
4. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500 mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5. Only use the Twinning pipe by Mitsubishi (optional parts).
ø19.05
ø41.28
a
Outdoor unit 2
760
920 30 920
ø9.52
RP350
ø28.58ø12.7
RP300
ø22.2ø12.7
RP250
PUHY-RP300YJM-A(-BS)
PUHY-RP350YJM-A(-BS)
PUHY-RP650YSJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP600YSJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP550YSJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP500YSJM-A(-BS)
PUHY-RP200YJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP450YSJM-A(-BS)
Twinning pipe~Outdoor unit
d or f
Gas
Liquid
c or e
RP200
Unit model
b
Gas
Liquid
Outdoor unit 1
ø9.52 ø19.05
ø22.2
(60)
1650
1710
Intake
air
Outdoor unit 2Outdoor unit 1
Discharge air
Intake
air
Intake
air
Left side view
To indoor unit
Front view
c
d
b
a
f
e
Gas Twinning pipe <optional parts>
Liquid Twinning pipe <optional parts>
To indoor unit
Twinning pipe connection size
PUHY-RP400YSJM-A(-BS)
PUHY-RP200YJM-A(-BS)
PUHY-RP200YJM-A(-BS)
Package unit name
Component unit name
Outdoor Twinning Kit (optional parts)
Indoor unit~Twinning pipe
ø34.93
ø15.88
CMY-RP100VBK
PUHY-RP400, 450, 500, 550, 600, 650YSJM-A (-BS)
Unit : mm
OUTDOOR UNITS
17
2. EXTERNAL DIMENSIONS
Note 2*
Detachable leg
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. The detachable leg can be removed at site.
3. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
4. The pipe section before the Twinning pipe (sections "a" , "b" , "c" and "d" in the figure) must have at least 500 mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5. Only use the Twinning pipe by Mitsubishi (optional parts).
(60)
1710
30
920
1650
760
920
30
920
Liquid
PUHY-RP250YJM-A(-BS)
PUHY-RP700YSJM-A(-BS)
CMY-RP200VBK
ø19.05
ø41.28
ø19.05
ø34.93
d
c
a
Gas
b
Twinning pipe connection size
Gas
PUHY-RP250YJM-A(-BS)
Liquid
PUHY-RP250YJM-A(-BS)
Outdoor unit 3
PUHY-RP300YJM-A(-BS)
Outdoor unit 1
PUHY-RP800YSJM-A(-BS)
Outdoor unit 2
Component unit name
PUHY-RP250YJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP250YJM-A(-BS)
Package unit name
Outdoor Twinning Kit (optional parts)
Indoor unit~Twinning pipe 2
PUHY-RP250YJM-A(-BS)
Twinning pipe 1~Twinning pipe 2
PUHY-RP750YSJM-A(-BS)
PUHY-RP200YJM-A(-BS) PUHY-RP300YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP900YSJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP850YSJM-A(-BS)
Twinning pipe~Outdoor unit
ø12.7
RP250
RP200
ø9.52
Liquid
Gas
e or g or i f or h or j
ø19.05
ø22.2ø9.52
RP300
ø22.2
Unit model
f
e
To indoor unit
To indoor unit
i
b
a
j
c
d
g
h
Front view
Liquid Twinning pipe 1
<optional parts>
Gas Twinning pipe 1
<optional parts>
Liquid Twinning pipe 2
<optional parts>
Gas Twinning pipe 2
<optional parts>
Outdoor unit 3
Left side view
Outdoor unit 2Outdoor unit 1
Intake
air
Intake
air
Intake
air
Discharge air
PUHY-RP700, 750, 800, 850, 900YSJM-A (-BS)
Unit : mm
OUTDOOR UNITS 18
3. CENTER OF GRAVITY
PUHY-RP200, RP250, RP300, RP350YJM-A (-BS)
760
80
Y
724
1410
Z
920
X
760
Model X Y Z
Unit: mm
330 337 550 325 342 550 325 352 550 325 352 550
PUHY-RP200YJM-A (-BS) PUHY-RP250YJM-A (-BS) PUHY-RP300YJM-A (-BS) PUHY-RP350YJM-A (-BS)
3. CENTER OF GRAVITY
OUTDOOR UNITS
19
4. ELECTRICAL WIRING DIAGRAMS
PUHY-RP200, 250, 300, 350YJM-A (-BS)
HIC bypass, Controls refrigerant
flow in HIC circuit
Oil flow control
SLEV
Refrigerant charging port for
auto-charge
SV8
SV5b
Outdoor unit heat exchanger
capacity control
SV3
Capacity control, Refrigerant
phase control in auto-cleaning
Middle pressure
63HS2
Pressure protection for pre-
existing pipes
63H2
For opening/closing the bypass
circuit
For opening/closing the bypass
circuit
Solenoid
valve
Pipe temperature
Z24, 25
Thermistor
Discharge pipe temperature
ACC inlet pipe temperature
Subcooled liquid refrigerant
temperature
OA temperature
IPM temperature
Function setting connector
THHS
TH7
TH6
TH5
TH4
TH3
Power supply
Explanation
Indoor/Outdoor transmission
cable
Central control transmission
cable
Terminal
block
TB7
TB3
TB1
Symbol
Pressure control, Refrigerant flow
rate control
DC reactor
DCL
SV1a
LEV2a, b
LEV1
Linear
expansion
valve
Solenoid
valve
CT12, 22, 3
CH11
Crankcase heater (for heating the compressor)
Current sensor (AC)
Magnetic relay (inverter main circuit)
72C
Low pressure
Discharge pressure
High pressure protection for the
outdoor unit
Pressure
switch
Pressure
sensor
63LS
63H1
Symbol
Explanation
4-way valve
21S4a, b
For opening/closing the bypass
circuit under the O/S
SV1b
SV9
63HS1
<Symbol explanation>
*1. Single-dotted lines indicate wiring
not supplied with the unit.
*2. Dot-dash lines indicate the control
box boundaries.
*3. Refer to the Data book for connecting
input/output signal connectors.
*4. Daisy-chain terminals (TB3) on the
outdoor units in the same refrigerant
system together.
*5. Faston terminals have a locking
function. Make sure the terminals
are securely locked in place after
insertion. Press the tab on the
terminals to remove them.
*6. Control box houses high-voltage parts.
Before inspecting the inside of the
control box, turn off the power, keep
the unit off for at least 10 minutes,
and confirm that the voltage between
FT-P and FT-N on INV Board has dropped
to DC20V or less.
SV8
X14
CN510
yellow
165
SV3
SV1b
63HS2
312
CN992
yellow
123
M
SLEV
65432
1
CNLVD
blue
2112
P
63H2
1
3
DCL
M1 M2
SV1a
Z3
21
M-NET power
supply circuit
C5
LED3: CPU in
operation
LED1: Normal
operation
SC-L1
SC-L2
1
2
W
U
SC-W
1
Z5
R1R2R3
C3
C2
F3F2F1
Z1 Z2
R4
D1
R5
R6
C11
DB1
C7C8C9
C10
C4
C1
C6
Power Source
3N~
50/60Hz
380/400/415V
N
L3L2L1
TB1
N
L3L2L1
L
F4
AC250V
6.3A T
black
white
red
3
1
CN3
green
TB24
N
TB23
L3
TB22
L2
TB21
L1
CN1B
4131
CN1A
UUU
F1,F2,F3
AC250V
6.3A T
U
Z4
DSA
CN2
653
1
Noise
Filter
U
ZNR01
U
31
CN5
red
3
CN4
blue
1
471
CNINV
CNVDC
4
1
FAN Board
F01
DC700V
4A T
C630
C631
R631
R630
IPM
CN18V
blue
CN4
red
CN5
21 1 3 12
234
1
CN21
blue
CN22
red
654
3
LED2: Error
Fan motor
(Heat exchanger)
M
3~
V
C100
R1 R5
*5
black
red
2
43
1
72C
black
red
SC-P1
SC-P2
4
CN1
1
LED1: Normal operation (lit)
/ Error(blink)
CN5V
yellow
CN6
21 3 1
CN4
1
2
CN2
152
7
1
CNTYP
black
C1
RSH1
THHS
*6
FT-P
FT-N
P
N
INV Board
+
+-
+
+++
+++
+
R34
C30
C32
C34
C36
R30
R32
C31
C33
C35
C37
R31
R33
black
white
red
R35
CT3
SC-L3
IPM
SC-U
SC-V
CT12 CT22
red white black
blackwhitered
U
V
W
MS
3~
Motor
(Compressor)
Central control
transmission
cable
Indoor/Outdoor
transmission
cable
Indoor/Outdoor
transmission
cable
*4
TP2TP1
TB7
SM2M1
TB3
M-NET Board
13
CN04
red
LED1: Power supply to
Indoor/Outdoor transmission line
CN102
4321
CNS2
yellow
21 5432
CNIT
red
1
63H1
P
LEV2b
M
LEV2a
M
M
LEV1
12345
6
CNLVA
CNLVB
red
12345
6
54321
6
CNLVC
red
3
1
CNTYP2
black
Z24
321
Z25
CNTYP5
green
CNTYP4
green
432
1
CN213
red
CN212
2
1
CN990
2
1
TH6
TH7
TH3
TH5
213
63LS
63HS1
213
TH4
321
CN202
red
CN201
231
CN211
2
1
red
CNIT
yellow
CNS2
51234
OFF
ON
14
14
CN41
CN40
CN102
4321
CN3D
123
red
CN3S
123
blue
CN3N
123
*3
CNAC
red
21
F01
AC250V
3.15A T
631
SV9
X09
CN508
black
X06
X07
135
6
CN507
red
6
3
SV5b
CN506
X05
3
1
21S4a
CN504
green
X04
X03
CH11
3
1
CN503
blue
2
1
CN502
X02
X01
21S4b
1
1
CN501
2
3
CNAC2
black
6
5
72C
1
2
CN72
red
31
CNDC
pink
12
CNT01
13 12 21 21
CN801
yellow
CNT02
CN332
blue
CN4
CN2
752
1
CPU power
supply circuit
Power failure
detection circuit
Control Board
LED1
SW1
ONOFF
1
10
SW2
ONOFF
1
10
SW3
ONOFF
1
10
SW4
ONOFF
1
10
ONOFF
1
10
SW5
543
12V
1
CN51
*3
SWU2 SWU1
10's
digit
1's
digit
Unit address
setting
LED1
Display
setting
Function
setting
Compressor ON/OFF output
Error detection output
TB7 Power
selecting
connector
LED3: Lit when powered
LED2: CPU in operation
4. ELECTRICAL WIRING DIAGRAMS
OUTDOOR UNITS 20
5. SOUND LEVELS
Measurement condition PUHY-RP200, 250, 300, 350YJM-A (-BS)
Measurement location
1m
1m
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 62.5 61.0 58.5 53.0 50.0 45.5 39.0 36.0 56.0
Low noise mode
50/60Hz 56.5 48.5 46.0 39.0 38.5 32.5 33.0 25.5 44.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP200YJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 59.0 62.0 60.0 54.0 50.5 46.0 41.0 35.0 57.0
Low noise mode
50/60Hz 58.0 53.5 44.0 39.0 36.5 32.5 31.0 24.5 44.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP250YJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
5. SOUND LEVELS
Sound level of PUHY-RP300YJM-A (-BS)
90
80
Standard Low
50/60Hz 50/60Hz
70
60
50
40
Octave band sound level (dB)
30
Approximate minimum
20
audible limit on continuous noise
10
63 125 250 500 1k 2k 4k 8k
Octave band central frequency (Hz)
Standard Low noise mode
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
50/60Hz 65.5 64.0 61.5 56.0 53.0 48.5 45.0 43.0 59.0 50/60Hz 61.5 60.0 49.5 45.0 42.0 39.0 40.0 38.0 50.0
63 125 250 500 1k 2k 4k 8k dB(A)
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
Sound level of PUHY-RP350YJM-A (-BS)
90
80
70
60
50
40
Octave band sound level (dB)
30
Approximate minimum
20
audible limit on continuous noise
10
63 125 250 500 1k 2k 4k 8k
Standard Low noise mode
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
50/60Hz 62.0 65.0 63.0 57.0 53.5 49.0 48.0 42.0 60.0 50/60Hz 62.0 54.0 48.5 46.0 41.5 40.0 41.5 39.5 50.0
Standard Low
Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A)
50/60Hz 50/60Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OUTDOOR UNITS
21
5. SOUND LEVELS
Measurement condition PUHY-RP400, 450, 500, 550, 600, 650YSJM-A (-BS)
Measurement location
1m
1m
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 62.0 65.0 63.0 57.0 53.5 49.0 44.0 38.0 60.0
Low noise mode
50/60Hz 61.0 56.5 47.0 42.0 39.5 35.5 34.0 27.5 47.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP500YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 65.5 64.0 61.5 56.0 53.0 48.5 42.0 39.0 59.0
Low noise mode
50/60Hz 59.5 51.5 49.0 42.0 41.5 35.5 36.0 28.5 47.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP400YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 66.0 66.0 63.5 58.0 55.0 50.5 46.5 43.5 61.0
Low noise mode
50/60Hz 63.5 61.0 50.5 46.0 43.0 40.0 40.5 38.0 51.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP550YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 64.0 64.5 62.5 56.5 53.0 48.5 43.0 38.5 59.5
Low noise mode
50/60Hz 60.5 54.5 48.0 42.0 40.5 35.5 35.0 28.0 47.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP450YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 68.5 67.0 64.5 59.0 56.0 51.5 48.0 46.0 62.0
Low noise mode
50/60Hz 64.5 63.0 52.5 48.0 45.0 42.0 43.0 41.0 53.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP600YSJM-A (-BS)
OUTDOOR UNITS 22
5. SOUND LEVELS
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 67.0 67.5 65.0 59.5 56.0 51.5 49.5 45.5 62.5
Low noise mode
50/60Hz 65.0 61.0 52.0 48.5 45.0 42.5 44.0 42.0 53.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP650YSJM-A (-BS)
OUTDOOR UNITS
23
5. SOUND LEVELS
Measurement condition PUHY-RP700, 750, 800, 850, 900YSJM-A (-BS)
Measurement location
1m
1m
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 67.0 67.5 65.5 59.5 56.0 51.5 47.5 44.0 62.5
Low noise mode
50/60Hz 65.0 62.0 52.0 47.0 44.0 41.0 41.0 38.5 52.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP800YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 65.5 66.5 64.5 58.5 55.0 50.5 45.5 40.0 61.5
Low noise mode
50/60Hz 63.0 57.5 50.0 44.0 42.5 37.5 37.0 30.0 49.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP700YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 69.0 68.5 66.0 60.5 57.5 53.0 49.0 46.5 63.5
Low noise mode
50/60Hz 65.5 63.5 53.0 48.5 45.5 42.5 43.0 41.0 53.5
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP850YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 64.0 67.0 65.0 59.0 55.5 51.0 46.0 40.0 62.0
Low noise mode
50/60Hz 63.5 59.0 49.5 44.5 41.5 37.5 36.0 29.5 49.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP750YSJM-A (-BS)
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 70.5 69.0 66.5 61.0 58.0 53.5 50.0 48.0 64.0
Low noise mode
50/60Hz 66.5 65.0 54.5 50.0 47.0 44.0 45.0 43.0 55.0
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP900YSJM-A (-BS)
OUTDOOR UNITS 24
6. CAPACITY TABLES
6. CAPACITY TABLES
6-1. Correction by temperature
CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values and the ratios below, the capacity can be found for various temperatures.
PUHY-
Nominal Cooling Capacity
Input
RP200YJM-A RP250YJM-A
kW
BTU/h
kW
22.4
76,400
5.68
28.0
95,500
8.28
1.3
1.2
1.1
1.0
0.9
0.8
Ratio of cooling capacity
0.7
0.6
1.2
1.1
1.0
0.9
0.8
Ratio of power input
0.7
0.6
Indoor Temperature
PUHY-
Nominal Heating Capacity
Input
RP200YJM-A RP250YJM-A
kW
BTU/h
kW
25.0
85,300
5.69
31.5
107,500
7.83
0.5
-5 0 5 10 15 20 25 30 35 40 45
23 32 41 50 59 68 77 86 95 104 113
1.4
1.3
1.2
1.1
1.0
0.9
0.8
Ratio of heating capacity
0.7
0.6
1.1
1.0
0.9
Ratio of cooling capacity and power input Outdoor temperature
Indoor Temperature
0.8
Ratio of power input
0.7
0.6
0.5
-20
-4
-15 5
OUTDOOR UNITS
-10 14
Ratio of heating capacity and power input Outdoor temperature
-5
23
0
32
5
41
10 50
15 59
25
6. CAPACITY TABLES
Ratio of cooling capacity and power input Outdoor temperature
Ratio of heating capacity and power input Outdoor temperature
-5 0 5 10 15 20 25 30 35 40 45 23 32 41 50 59 68 77 86 95 104 113
1.1
1.2
1.0
0.9
0.8
0.7
0.6
0.5
Ratio of power input
-20
-4
-15 5
-10 14
-5
23
0
32
5
41
10 50
15 59
0.6
0.8
0.9
1.0
0.7
0.6
0.5
0.4
Ratio of power input
1.4
1.3
1.1
1.0
0.9
0.8
0.7
1.2
Ratio of cooling capacity
Indoor Temperature
1.3
1.2
1.0
0.9
0.8
0.7
1.1
Ratio of heating capacity
Indoor Temperature
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
PUHY-
RP300YJM-A RP350YJM-A
PUHY-
RP300YJM-A RP350YJM-A
PUHY-
RP400YSJM-A
PUHY-
RP400YSJM-A
33.5
114,300
9.37
40.0
136,500
12.28
37.5
128,000
9.86
45.0
153,500
13.12
45.0
153,500
11.87
50
170,600
11.38
OUTDOOR UNITS 26