Mitsubishi PUHY-P200YREM-A, PUHY-P250YREM-A Service Manual

Service Handbook
2004
AIR CONDITIONERS CITY MULTI
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Issued in Mar. 2004 MEE03K220 Printed in Japan
New publication, effective Mar. 2004
Specifications subject to change without notice
Service Handbook Replace Multi PUHY-P200·250YREM-A
Caution to REPLACE MULTI Installation Work
Flow of installation work in the field Items to be observed
•Please note that our Corporation is not liable to the reliability of existing piping, wiring and power system for reuse (in relation with the gas leak of piping, partially defective/disconnection of wiring, deteriorated insulation, characteristic faults due to worn out system).
•For limitation on the refrigerant piping and applicable piping diameter, check the existing piping for reuse in accordance with the specified check sheet by refer­ring products catalogs and manuals for judgement to reuse.
•If vapor condensation was found in the past, check the thermal insulation.
•For a portion suffered by condensation dripping, check the deterioration of the insulation, and repair the insulation materials if required.
•When the copper piping is seriously deteriorated, do not use parts with verdigris or black spots.
•For reusing the existing control wiring between the outdoor unit, and remote con­troller, check the wire type , siz e or the lik e based on the chec k sheet to judge the possibility.
•Even when the above does not meet the item on the check sheet, existing wiring may be reused depending on the number of connecting indoor units and piping length. Ask us for detail.
•For the power source system, employ the voltage and number of phase meeting the outdoor unit, indoor unit and heat storage unit, and adopt the breaker capac­ity and wiring size based on the power source wiring connection diagram.
•When the existing power source system (including the power source wiring) is used, check the system for deterioration and damages.
•Check the refrigerating machine oil used in the existing system. (As is found at the oil inspection, if the refrigerating machine oil used in the existing system is mineral oil, use the ester oil sampling kit for inspection.
•When the length of piping for reuse is unknown, additional refrigerant charge is to be calculated based on the quantity of recovered refrigerant. For this reason, you are kindly requested to recover all refrigerant inside the existing outdoor/ indoor units and extended piping to check and record the quantity. (The stan­dard of additional refrigerant is (Quantity of R22 recovered - Charged quantity of existing outdoor unit + 3kg). Adjust the refrigerant quantity after mineral oil re­covery operation.)
Outdoor unit
•Confirm the space around the outdoor unit. (Verifying the installation space of the oil trap kit)
Turn the power source on, and confirm the normality of the system
•Check the remote controller or outdoor unit for error display.
•Run the indoor unit for fan operation after turning the remote controller on, and check the air feeding and direction.
Do not run the compressor until finishing the mineral oil recovery operation.
Mount the valve to the field piping (extended piping). (The ball valve is being attached to the outdoor unit.)
Execute an airtight test to check the existing piping for deterioration or leaking.
Calculate the quantity required by the extended piping, and charge the addi-
tional refrigerant. Make sure to enter the value in the additional refrigerant charge column on the label of combined outdoor unit being pasted on the outdoor unit.
Without applying any operation, keep the ball v alves of the outdoor unit c losed
before mineral oil recovery operation.
It is necessary to charge refrigerant in a rated quantity and adjust the quantity. Be sure to execute when the piping length is unknown. For detail, consult the agent of your dealer.
Enter required items in the request form of REPLACE MULTI mineral oil recovery work.
During local installation work
Before local installation work
Confirming the possibility of existing refrigerant piping for reuse
Confirming the possibility of existing control wiring for reuse
Confirming the possibility of existing power source system for reuse
Confirming the objective range for replacing
Recovering the refrigerant of old system
Removing the outdoor/indoor units, re­mote controllers, etc.
Installing the outdoor/indoor units, remote controllers, etc., and executing electrical work
Setting the address, checking the system
Executing the piping work (mounting of ball valve). Air tightening and evacuating the existing piping and charging refrigerant
Operating mineral oil recovery
Executing test run and adjustment (for final verification of operation).
Safety Precautions
• Before installing the unit, make sure you read all the “Safety precautions”.
• The “Saf ety precautions” provide very important points regarding safety. Make sure you f ollo w them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided. : Indicates that important instructions must be followed. : Indicates a part which must be grounded. : Beware of electric shock (This symbol is displayed on the
main unit label.) <Color: Yellow>
Warning:
Carefully read the labels affixed to the main unit.
Warning
Ask your dealer or specialized contractor for installation.
If your own installation work is improper, fire, electric shock or water leakage may result.
Connect wiring using the specified cable and fas­ten it securely to prevent the external force of the cable from being transferred to the terminal connecting sections.
Improper connection or fastening may cause heat
generation or fire.
Conduct specified installation work durable against strong winds around buildings.
Improper installation work can cause trouble i.e. the unit toppling over.
Never attempt to repair the unit. For repair, ask your dealer.
Improper repair may result in water leakage, electric shock or fire.
Do not touch the heat exchanger fins.
Improper handling may cause cuts.
When refrigerant gas is leaked during work, conduct ventilation.
If refrigerant gas comes into contact with fire, it may cause the generation of poisonous gases.
Please conduct correct installation work by observing this Installation Manual.
Improper installation work may result in water leak­age, electric shock or fire.
Conduct all electrical work by a licensed en­gineer according to “Technical Standard re­lating to Electrical Facility,” “Wiring Regula­tion of Power Company,” and instructions in this Manual, and always use an exclusive cir­cuit.
Insufficient power source capacity or improper instal­lation may cause electric shock or fire.
When installing or moving the unit, do not charge other than the specified refrigerant (R407C) into the refrigeration cycle.
Air if mixed generates abnormally high pressure in­side the refrigeration cycle which may damage the unit.
Do not reconstruct or reset the protection devices.
If the protection devices like the pressure switch or thermal switch is forcibly operated by short circuit­ing, or parts other than that specified by Mitsubishi Electric are used, fire or explosion may be caused.
Precautions for Devices that Use R407C Refrigerant
Caution
Use refrigerant piping made of phosphorus deoxidized copper and copper alloy seam­less pipes and tubes. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, ox­ides, dust/dirt, shaving particles, moisture, or any other contaminant.
Contaminants on the inside of the refrigerant piping may cause the refrigerating machine oil to deterio­rate.
Store the piping to be used during installa­tion indoors and keep both ends of the pip­ing sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerating machine oil to coat flares and flange connections.
The refrigerating machine oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to seal the system.
If gas refrigerant is used to seal the system, the com­position of the refrigerant in the cylinder will change and performance may drop.
Do not use other refrigerant other than
R407C.
Use of other refrigerants (R22 for example) may de­teriorate refrigerating machine oil due to chlorine generation.
Use a vacuum pump with reverse flow pro­tection.
Otherwise the vacuum pump oil will reversely flow into the refrigerant circuit causing the possible dete­rioration of the refrigerating machine.
Do not use the following tools used for con­ventional refrigerant. (Gauge manifold, Charging hose, Gas leak detector, Reverse flow protector, Cap for re­frigerant charge, Refrigerant recovery de­vice)
Mixing of conventional refrigerant /refrigerating ma­chine oil may cause to deteriorate the refrigerating machine oil.
Mixing with water may cause deterioration of the re­frigerating machine oil.
As this refrigerant does not contain chloride, the gas leak detector for conventional refrigerant gas can not be used.
Do not use a charging cylinder.
Use of a charging cylinder changes the composition of refrigerant resulting in possible performance de­terioration.
More careful management is required for the tools than that for the conventional.
Dust, trash or water content if mixed into the refrig­erant circuit may cause to deteriorate the refrigerat­ing machine oil.
Caution to Equipment Used for Replacing
Caution
Do not operate any valves before conduct­ing mineral oil recovery operation.
Operating valves before conducting mineral oil recov­ery operation may cause a deterioration in the perfor­mance of mineral oil recovery.
For mineral oil recovery operation, the sys­tem controller and MA remote controller may be required to be remove sometimes.
Improper handling can lead to an inability to perform oil recovery operation.
For removal, follow the instruction displayed on the PC for mineral oil recovery.
Mount the controllers again after finishing the oil re­covery operation.
Observe a safe distance from the indoor unit fan which runs during the mineral oil recov­ery operation.
Working in the surrounding of the indoor unit fan can cause personal injury.
Record the quantity of refrigerant replenished. (Enter into the column for replenished refrigerant quantity on the label of the indoor unit.)
Missing the description may deteriorate the perfor­mance of mineral oil recovery.
Malfunction or poor cooling/heating may also be caused.
During the mineral oil recovery operation, an error display may be shown on the remote controller or system controller.
When an error display was shown during mineral oil recovery operation, reset the error display after fin­ishing the operation.
To conduct the refrigerant recovery/evacua­tion of the inside of exiting piping, choose tools only used with R407C e.g. charging hose.
Using a charging hose for R407C causes it to mix the conventional refrigerating machine oil leading to the deterioration of refrigerating machine oil.
Before Conducting Installation Work/Electrical Work
Caution
Do not install the unit at a place where com­bustible gas can possibly be generated.
Leaked combustible gas if stagnated around the unit may cause explosion.
Do not use the unit in a special atmosphere.
Use in an atmosphere containing high levels of oil, steam or sulfide gas may seriously degrades the per­formance or damage parts.
Do not install the unit on a material which is not designed to be wet.
If liquid drips from the oil trap kit, apply centralised drainage work to the oil trap kit.
Apply grounding work securely.
Do not connect the grounding line to gas pipe, city
water pipe, lightning rod or telephone grounding line. Improper grounding may cause electric shock.
For the power source wiring, refrain from giving tensile force to the wiring.
Disconnection, heat generation or fire may be
caused.
Make sure to mount a leak breaker to the power source.
Otherwise electric shock may be caused.
Be sufficiently careful in transporting products.
Do not transport a product with a weight exceeding 20kg by a single person.
Some products are packed with PP band. Do not use it as a means of transporting.
During transport cuts may be caused by the fin sur­face of the heat exchanger , please refrain from touch­ing it without gloves.
Do not use the same switch or the like for plural outdoor units.
Otherwise, malfunction, heat generation or fire may be caused.
When installing the unit in hospitals or com­munication equipment plants, prepare mea­sures to prevent noise generation before­hand.
The noise may cause the erroneous operation or failure and may giv e negative effect to medial equip­ment or communication equipment to disturb medi­cal treatment on human bodies or hinders image broadcasting or generates noise.
Check possibility for the reuse of existing refrigerant piping by observing this manual.
The conventional refrigerating machine oil is con-
tained inside existing piping and some residual oil deteriorates oil recovery performance which may lead to the deterioration of refrigerating machine oil.
The piping specification (diameter, length , height
difference) out of the use specified range may hinder the mineral oil recovery performance, possibly lead­ing to deterioration of refrigerating machine oil.
Do not use breakers or fuses other than that with correct capacities.
Use of a fuse with excessively large capacity or wire/ copper wire may cause troubles or fire.
For the power source wiring, use wire with rated current capacity.
Otherwise an electric leak, heat generation or fire
may be caused.
When using existing wiring (for power source or transmission) or switches, check them for disconnection and deterioration beforehand.
Otherwise an electric leak, heat generation or fire
may be caused.
Dispose the packing materials properly.
As the packing materials are using metal products
or wooden pieces such as nails, nail wounds may be caused if it is improperly treated. Please observe caution to avoid this from occuring.
Dispose the polyethylene bag for packing only after tearing. Otherwise a suffocation accident may be caused by children play with the disposed bag.
Be sure to mount the valve to the field piping (extended piping).
After mineral oil recovery, the oil trap kit can not be removed disabling air conditioning operation.
Provide thermal insulation to the valve on the field piping (extended piping) properly.
Insufficient thermal insulation generates condensa­tion that may cause to deteriorate the performance.
Provide thermal insulation (including lagging) after recovering mineral oil.
Before Conducting Mineral Oil Recovery Operation
Caution
Turn the power source on 12 hours or more before starting operation.
Otherwise trouble may be caused. Do not turn the power off during the operating season.
Do not operate the unit without the panels or guard.
Touching the rotating parts, high temperature parts or high voltage may cause personal injury such as burns or electric shock.
Do not operate switches with wet fingers.
Electric shock may be caused.
Do not turn off the power source immediately after stopping.
Be sure to wait for 5 minutes or more. Otherwise water leakage or troubles may be caused.
Do not touch the refrigerant piping during operation or immediately after stopping with bare hands.
The refrigerant piping or the refrigerant circuit parts of the compressor during operation or immediately after stopping may have low or high temperature. Touching with bare hands may cause a burn or frost­bite.
Do not run the outdoor unit during a test run until finishing the mineral oil recovery operation.
The indoor unit fan will run.
Caution to Mineral Oil Recovery Operation
Warning
Caution
Be sufficiently careful to avoid the oil trap kit, falling or toppling over.
If this happens the oil trap kit may be damaged and refrigerant piping may malfunction.
Falling down during flushing operation causes the leak of refrigerant from the joint which is dangerous if contacts it human body.
After flushing operation, check the residual pres­sure inside the oil trap kit with a pressure gauge. If the residual pressure is exceeding 0.294MPa, recover refrigerant inside the oil trap kit to reduce the pressure to within 0.2 ~ 0.294MPa.
Under high inner pressure, pressure rises during storing, inducing a dangerous situation.
Under low inner pressure, water content or foreign matter enters during storing, causing corrosion to the oil trap kit which may cause troubles.
Be careful not to expose the oil trap kit unit (especially electrical parts) to rain water.
The electrical parts if wet with rain water may cause machine trouble.
The electrical parts if wet with rain water may cause electrical shock.
Conduct oil recovery from the oil recovery ser­vice valve outdoor or at a place with good ventila­tion. Use leather gloves when opening the oil re­covery service valve and open it slowly.
If done in a closed space, suffocation can be caused.
Opening the oil recovery service valve fully and
quickly allows oil to splash, which is dangerous.
As the oil recovered is of low temperature, frostbite may be caused if it touches skin.
When the oil trap kit is transported while ly­ing sideways, do not place any thing on the sheet metal of the kit.
Otherwise, the sheet metal or inner piping may be deformed leading to breakage.
Before removing the oil trap kit after flush­ing operation, make sure to discharge and process the oil recovered from the oil recov­ery service valve.
If it is not discharged, the oil accumulated inside will flow out during flushing operation hindering proper recovery of mineral oil thus leading to machine trouble.
For inspection, use the ester oil sampling kit when the refrigerating machine oil used in the existing unit is mineral oil.
(
Confirm the type of refrigerating machine oil used in the
existing unit by reading the name plate or the like.
)
Proper checking can not be executed if not using the kit meeting the refrigerating machine oil used by the existing unit. This possibly causes machine trouble.
Contents
¡ PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT ... 2
[1] Storage of Piping Material................................................................. 2
[2] Piping Machining............................................................................... 3
[3] Necessary Apparatus and Materials and Notes on Their Handling .. 4
[4] Brazing.............................................................................................. 5
[5] Airtightness Test ................................................................................ 6
[6] Vacuuming ........................................................................................ 6
[7] Charging of Refrigerant..................................................................... 7
[8] Dryer ................................................................................................. 7
COMPONENT OF EQUIPMENT .............................................................
8
[1] Appearance of Components ............................................................. 8
[2] Refrigerant Circuit Diagram and Thermal Sensor........................... 14
[3] Electrical Wiring Diagram................................................................ 15
[4] Standard Operation Data ................................................................ 16
[5] Function of Dip SW and Rotary SW................................................ 18
£ TEST RUN .............................................................................................21
[1] Before Test Run ..............................................................................21
[2] Test Run Method ............................................................................. 25
¢ GROUPING REGISTRATION OF INDOOR UNITS WITH REMOTE
CONTROLLER.......................................................................................
26
CONTROL.............................................................................................. 32
[1] Control of Outdoor Unit ................................................................... 32
[2] Operation Flow Chart...................................................................... 37
[3] List of Major Component Functions ................................................ 42
[4] Resistance of Temperature Sensor................................................. 44
§ REFRIGERANT AMOUNT ADJUSTMENT ............................................
45
[1] Refrigerant Amount and Operating Characteristics ........................ 45
[3] Refrigerant Volume Adjustment Mode Operation ........................... 48
TROUBLESHOOTING ...........................................................................
50
[1] Principal Parts................................................................................. 50
[2] Trouble and Remedy of Remote Controller.....................................
[4] Self-diagnosis and Countermeasures Depending on the Check
Code Displayed...............................................................................
62
[3] Investigation of Transmission Wave Shape/noise ..........................
69
[5] LED Monitor Display ....................................................................... 95
PREPARATION, REPAIRS AND REFRIGERANT REFILLING WHEN
REPAIRING LEAKS .............................................................................
113
[3]
Location of leaks: Extension piping or indoor units (when cooling)113
[4] Location of leaks: Outdoor unit (when heating) ............................ 115
114
ª CHECK THE COMPOSITION OF THE REFRIGERANT
........................
116
0 CAUTIONS WHEN REPLACING THE OUTDOOR UNIT MAIN
BOARD
...................................................................................................
118
[1]
[2] Location of leaks: Outdoor unit (Cooling mode)............................ 113
Location of leaks: Extension piping or indoor units
(Heating mode)
[2] Adjustment and Judgement of Refrigerant Amount ........................ 45
72
- 1 -
[1] Storage of Piping Material
(1) Storage location
Store the pipes to be used indoors. (Warehouse at site or owner’s warehouse) Storing them outdoors may cause dirt, waste, or water to infiltrate.
(2) Pipe sealing before storage
Both ends of the pipes should be sealed until immediately before brazing. Wrap elbows and T’s in plastic bags for storage.
The new refrigerator oil is 10 times more hygroscopic than the conventional refrigerator oil (such as Suniso). Water infiltration in the refrigerant circuit may deteriorate the oil or cause a compressor failure. Piping materials must be stored with more care than with the conventional refrigerant pipes.
OK
OK
NO
NO
¡ PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT
- 2 -
[2] Piping Machining
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
Use only the necessary minimum quantity of oil.
Reason :
1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside.
Notes :
Introducing a great quantity of mineral oil into the refrigerant circuit may also cause a compressor failure.
Do not use oils other than ester oil, ether oil or alkylbenzene.
- 3 -
[3] Necessary Apparatus and Materials and Notes on Their Handling
The following tools should be marked as dedicated tools for R407C.
<<Comparison of apparatus and materials used for R407C and for R22>>
Apparatus Used Use R22 R407C
Gauge manifold Evacuating, refrigerant filling Current product Charging hose Operation check Current product Charging cylinder Refrigerant charging Current product Do not use. Gas leakage detector Gas leakage check Current product Shared with R134a Refrigerant collector Refrigerant collection R22 For R407C use only Refrigerant cylinder Refrigerant filling R22
Vacuum pump Vacuum drying Current product
Vacuum pump with a check valve Current product Flare tool Flaring of pipes Current product Bender Bending of pipes Current product Application oil Applied to flared parts Current product
Torque wrench Tightening of flare nuts Current product Pipe cutter Cutting of pipes Current product Welder and nitrogen cylinder Welding of pipes Current product Refrigerant charging meter Refrigerant charging Current product Vacuum gauge Checking the vacuum degree Current product
Symbols :
To be used for R407C only. Can also be used for conventional refrigerants.
Tools for R407C must be handled with more care than those for conventional refrigerants. They must not come into contact with any water or dirt.
Identification of dedi­cated use for R407C :Record refrigerant
name and put brown belt on upper part of cylinder.
Can be used by attaching an adapter with a check valve.
Ester oil or Ether oil or Alkybenzene (Small amount)
- 4 -
[4] Brazing
No changes from the conventional method, but special care is required so that foreign matter (i.e. oxide scale, water, dirt, etc.) does not enter the refrigerant circuit.
Example : Inner state of brazed section
When non-oxide brazing was not used When non-oxide brazing was used
Items to be strictly observed :
1. Do not conduct refrigerant piping work outdoors on a rainy day.
2. Apply non-oxide brazing.
3. Use a brazing material (BCuP-3) which requires no flux when brazing between copper pipes or between a copper pipe and copper coupling.
4. If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends of them.
Reasons :
1. The new refrigerant oil is 10 times more hyg roscopic than the conventional oil. The probability of a machine failure if water infiltrates is higher than with conventional refrigerant oil.
2. A flux generally contains chlorine. A residual flux in the refrigerant circuit may generate sludge.
Note :
Commercially available antioxidants may have adverse effects on the equipment due to its residue, etc. When applying non-oxide brazing, use nitrogen.
- 5 -
[5] Airtightness Test
No changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407C leakage.
Halide torch R22 leakage detector
Items to be strictly observed :
1. Pressurize the equipment with nitrogen up to the design pressure and then judge the equipments airtightness, taking temperature variations into account.
2. When investigating leakage locations using a refrigerant, be sure to use R407C.
3. Ensure that R407C is in a liquid state when charging.
Reasons :
1. Use of oxygen as the pressurized gas may cause an explosion.
2. Charging with R407C gas will lead the composition of the remaining refr igerant in the cylinder to change and this refrigerant can then not be used.
Note :
A leakage detector for R407C is sold commercially and it should be purchased.
[6] Vacuuming
1. Vacuum pump with check valve A vacuum pump with a check v alve is required to prevent the vacuum pump oil from flowing back into the refrigerant circuit when the vacuum pump power is turned off (power failure). It is also possible to attach a check valve to the actual vacuum pump afterwards.
2. Standard degree of vacuum for the vacuum pump Use a pump which reaches 65Pa or below after 5 minutes of operation. In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the vacuum pump is not properly maintained, the degree of vacuum may be too low.
3. Required accuracy of the vacuum gauge Use a vacuum gauge that can measure up to 650Pa. Do not use a general gauge manifold since it cannot measure a vacuum of 650Pa.
4. Evacuating time
Evacuate the equipment for 1 hour after 650Pa has been reached.
After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.
5. Operating procedure when the vacuum pump is stopped In order to prevent a backflow of the vacuum pump oil, open the relief valve on the vacuum pump side or loosen the charge hose to drawn in air before stopping operation. The same operating procedure should be used when using a vacuum pump with a check valve.
NO
NO
- 6 -
[7] Charging of Refrigerant
R407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.
For a cylinder with a syphon attached For a cylinder without a syphon attached
Cylinder color identification R407C-Gray Charged with liquid refrigerant
R410A-Pink
Reasons :
1. R407C is a mixture of 3 refrigerants, each with a different evaporation temperature. Therefore, if the equipment is charged with R407C gas, then the refrigerant whose ev apor ation temperature is closest to the outside temper ature is charged first while the rest of refrigerants remain in the cylinder.
Note :
In the case of a cylinder with a syphon, liquid R407C is charged without turning the cylinder up side down. Check the type of cylinder before charging.
[8] Dryer
1. Replace the dryer when the refrigerant circuit is opened (Ex. Change the compressor, full gas leakage). Be sure to replace the dryer with a CITY MULTI (For use with R407C).
If any other product is used, the unit will be damaged.
2. Opening the refrigerant circuit after changing to a new dryer is less than 1 hour. The replacement of the dryer should be the last operation performed.
Cylin-
der
Cylin-
der
Valve Valve
Liquid
Liquid
- 7 -
COMPONENT OF EQUIPMENT
[1] Appearance of Components
Outdoor unit
PUHY-P200, 250YREM-A
Propeller fan
Accumlator
CSC
SCC
4way valve
Dryer
Compressor
Fan motor
Heat exchanger
Control box
- 8 -
Controller Box
FANCON board
ACCT
INV board
MAIN board
Noise filter
Choke coil (L2)
Terminal block TB1A Power Source
Terminal block TB7 Transmission (Centralized control)
Terminal block TB3 Transmission
Inteligent Power Module (IPM)
G/A board
DCCT
Diode stack (DS)
Magnetic contactor (52C)
Capacitor (C2, C3) (Smoothing capacitor)
- 9 -
MAIN board
CN51 Indication distance 3-4 Compressor ON/OFF 3-5 T roub le
CNRS3 Serial transmission to INV board
CN3D
SW1
CNTR CNFC1
CNVCC4 Power source for control(5V)
CN20 Power supply
3 L1 1 N
SW3
SW4
SW2 SWU2
SWU1
CNS1 CNS2 CN40 CN41 CNVCC3
Power Source for control
1-2 30V 1-3 30V 4-6 12V 5-6 5V
CN3S
CN3N
LD1 Service LED
SWU3
CNTYP1
- 10 -
INV board
CNDR2 Out put to G/A board
CNTH
CNCT DCCT
CN15V2 Power supply
CNFG Frame grounding
for IPM control
CNCT2 ACCT
CNAC2 I Power source 1 L2 3 N 5 G
CN52AC Control for 52C
CNRS2CN FAN
Control for MF1
Serial transmission to MAIN board
SW1
CNVDC 1-4 DC-560V
CNVCC4 Power supply (5V)
CNL2 Choke coil
CNVCC2 Power supply
1-2 30V, 1-3 30V 4-6 12V, 5-6 5V
- 11 -
FANCON board
CNFAN
CNPOW
CNFC2
CN15V1
CNDR1
CNIPM1
G/A board
Terminal for signal grounding
CNDC1 CNDC2
- 12 -
- 13 -
RELAY 10 board
RELAY 4 board
SLEV
ST2
TH5
SCC
TH8
ST7
ST4
LEV1
TH7
TH1
TH6
21S4
ST1
CJ1
O/S
63HS
Com
CJ2
CV1
ST3
SV1
CP1
ST5
S
M
63LS
63H
TH2
Dryer
CP2
ST10
SV4
ST9
HEX 1
ST11
HEX 2
SV2
ST6
BV3
CP3
SV3
ST8
BV1
BV2
[2] Refrigerant Circuit Diagram and Thermal Sensor
1PUHY-P200/250YREM-A
- 14 -
p
A
A
[3]
1 PUHY-P200·250YREM-A
Electrical Wiring Diagram
<SYMBOL EXPLANATION>
Symbol
DCL
ACCT-U,W
52C
ZNR4 Varistor
DC reactor (Power factor improvement)
Current Sensor
Magnetic contactor (Inverter main circuit)
N a m e
Fan motor (Radiator panel)MF1
Solenoid valve (Discharge--suction bypass)SV1, SV2
4--way valve
21S4
1
Symbol
SLEV
SV3
Solenoid valve (Heat exchanger capacity control)
SV4
Solenoid valve (Heat exchanger capacity control)
LEV1
Electric expansion valve (Sub-cool coil bypass)
N a m e
Choke coil (Transmission)L2
IPM Intelligent power module
TH5
TH2
TH1
N a m eSymbol
OA temp. detect
Pipe temp. detect
TH6
Saturation evapo. temp. detect
Discharge pipe temp. detect
Thermistor
Thermistor
bypass outlet temp. detect at Sub--cool coil
TH8
Symbol N a m e
THHS Radiator panel temp. detect
Aux. relayX1~10 Earth terminal
DCCT
Current Sensor
Electric expansion valve (Sub-cool coil bypass)
63HS High pressure sensor 63LS Low pressure sensor
liquid outlet temp. detect at Sub--cool coil
TH7
R20
CNTYP1
(2P)
C4
BOX BODY
F01 250VAC 6.3AF
F03 250VAC 6.3AF F02 250VAC 6.3AF
52C
ACCT
-U
BOX BODY
N
BOX BODY
BOX BODY
CNPOW
(5P)
SV3
SV4
circuit
detection
1
2
3
4
5
6
NF
TB1B
BOX BODY
X10
21S4
63H
X06
CN36 (6P)
CNFC1
(6P)
CNFC2
(6P)
CNFAN
(5P)
Control circuit board
(MAIN board)
Blue
Red
White
Black
Brown
Red
BOX BODY
Power circuit board (INV board)
L2
MF1
THHS
CNVCC3
(6P)
CNVCC4
(2P)
X10
X01
X02
23
Black
Red
V
W
U
White
CNTR1
R3
R2
C3
C2
DCL
52C
C1
ZNR4
~
~
~
TB7
M2
M1
TB3
Blue
Black
Red
White
PE
L2
TB1A
CH1
SV1
L3
N
12V
CN51
(5P)
1
5
2 4
3
PE
1
L1
M1
S
Yellow
Orange
Purple
Black
White
Gray
1 2 3 4
V W
N
U
MF
51234
P
N
L1 L2 L3
IPM
Orange
Brown
CN04
MC1
DCCT
DC-DC Converter
CN3S
(3P)
CN3N
(3P)
SNOW
OFF
ON
1-2
CN3N
OFF
ON
1-3 ON
OFF
Mode
Auto
changeover
Normal
HEAT COOL
1
SV2
CN02
(8P)
321
TH6
63LS63HS
Red
White
Black
TH2
TH1
TH7TH5
LEV1
TH8
SLEV
no fuse breaker
Inverter Controller Box
PUHY-P200YREM-A PUHY-P250YREM-A
30A 30A
3216548721321321321543215421
CN03
(3P)
CN01
(2P)
CNH (3P)
CNL (3P)
CNLV1
(5P)
CNSLV
(5P)
Refer to the service handbook about the switch operations.
Crank case heater (Compressor)
High pressure switch
1 2 3
CN38
(3P)
6 5 4 3 2 1
6 5 4 3 2 1
X03
X04 X05
X01
X02
CN32 (3P)
CN33 (3P)
CN34 (6P)
M2
Connect to Indoor and remote controller
L2
L3
N
L1
Green/ Yellow
L2
L3
N
L1
L2
L3
N
L1
Blue
Black
Red
White
L2
L3
N
L1
Blue
Black
Red
DS
White
Power source 3N~ 380/400/415V 50/60Hz
Terminal Block
Noise Filer
Terminal Block
L1 L2 L3 N
Diode stack
R1 R5
3214
3214
3 2
1
4
321476589
CNS2
(3P)
CNS1
(2P)
CN20
(3P)
32121
321321
CNTR
(3P)
F1 250VAC 2A T
F3 250VAC 1A F
T01
CNDC2
(4P)
UVW
Gate amp board (G/A board)
ACCT
-W
Motor (Compressor)
321654879 321654879
10 1211 13 14
3214321432 145
123123
Red
White
Black
1
2
3
4
5
6
5
4
3
2
1
4
3
2
1
Fan motor (Heat exchanger)
Fan control board (Fancon board)
CN3D
(3P)
1
2
3
1
2
3
1
2
3
Compressor
ON/OFF
NIGHT MODE
ORDEMEND
5: Trouble
4: Compressor ON/OFF
F02 700VDC 2A T
F01 250VAC 2A T
CNDR2
(9P)
CNVDC
(4P)
CNCT
(4P)
CNAC2I
(5P)
CNRS2
(7P)
CNVCC2
(6P)
CN15V2
(14P)
CNCT2
(4P)
1 2 3
1
5 6
2 4
3
1
5 6
2 4
3
1 2 3
1 2
1 2
1
5 6 7
2 4
3
1
5 6 7
2 4
3
CNRS3
(7P)
CNVCC4
(2P)
CNX10
(3P)
CN15V1
(14P)
CNDR1
(9P)
CNDC1
(4P)
321476589
121110 13 14
3 2 1
3 2 1
CN52CAC
(3P)
CNFAN
(3P)
CNTH
(2P)
CNL2
(2P)
2121
CNFG
(2P)
21
- 15 -
Cooling Outdoor unit
Items
PUHY-P200YREM-A
PUHY-P250YREM-A
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
27.0/19.0 27.0/19.0
35.0/24.0 35.0/24.0 4 4
4 4
71 63 50 20 100 71 63 20
55
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.7 11.7
270 420 360 250 360 270 420 250
122 200
1 272
50
2.00/0.55 2.08/0.54
81 80 42 44 16 16 17 17 20 20
55 44 44 20 22 13 13 20 20 14 14
0.23 0.23
10.6 9.7 14.4 13.2 380 415 380 415
Indoor unit fan notch Refrigerant volume Total current Volts Indoor unit SC (LEV1) Oil back (SLEV)
High pressure/Low pressure (after O/S) (before Accumulator)
Pressure
DB/WB
Set
m
kg
A V
Pulse
MPa
˚C
Condition
Sectional temperature
Outdoor unit
LEV opening
Inlet Outlet
Outdoor unit
Indoor unit
OC
Ambient temp.
Indoor unit
Piping
Discharge (TH1) Heat exchanger outlet (TH5)
Accumulator
Suction (Comp) CS circuit (TH2) Shell bottom (Comp) SCC outlet (TH7) Bypass outlet (TH8) LEV inlet Heat exchanger outlet
[4] Standard Operating Data
1 PUHY-P200·250YREM-A
- 16 -
Outdoor unit
Items
PUHY-P200YREM-A PUHY-P250YREM-A
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
20.0/– 20.0/–
7.0/6.0 7.0/6.0 44 44
55
71 63 50 20 100 71 63 20
10 10 10 10 10 10 10 10
45 45
Hi Hi Hi Hi Hi Hi Hi Hi
11.7 11.7
290 470 410 250 330 290 470 250
0
123
0
200
2.10/0.43 2.10/0.38
73 80
0 –2 20 20
42 –4 –6 33 33
34 34
60 60
0.28 0.28
11.4 10.5 15.1 13.8 380 415 380 415
Indoor unit fan notch Refrigerant volume Total current V
olts Indoor unit SC (LEV1) Oil back (SLEV)
High pressure/Low pressure (after O/S) (before Accumulator)
Pressure
DB/WB
Set
m
kg
A V
Pulse
MPa
˚C
Condition
Sectional temperature
Outdoor unit
LEV opening
Discharge (TH1) Heat exchanger inlet (TH5)
Accumulator
Suction (Comp) CS circuit (TH2) Shell bottom (Comp)
Heat exchanger outlet
Heat exchanger inlet
Inlet Outlet
Outdoor unit
Indoor unit
OC
Ambient temp.
Indoor unit
Piping
Heating
- 17 -
1 PUHY-P200·250YREM-A
Switch Function
Function according to switch operation Switch set timing
When off When on When off When on
SWU
SW1
SW2
SW3
SW4
1~2
1~8
3
9~10
1
2
3
4 5
6
7
8
9
10
1
2
3
4
5 6
7
8 9
10
1
2
3
Unit address setting Refrigerant model
For self diagnosis/ operation monitoring
Centralized control switch
Deletion of connection information.
Deletion of error history.
Refrigerant amount adjustments
– Disregard ambient air sensor errors, liquid overflow errors. Forced defrosting
Defrost prohibited timer
– SW3-2 Function valid/ invalid Indoor unit test operation
Defrosting start tempera­ture of TH Defrosting end tempera­ture of TH5. Opening angle of IC except when heater thermostat is ON during defrosting.
– Pump down
Target Tc (High pressure) in Heating
Models
Models SW4-2 Function valid/
invalid Configuration compensa­tion value
Set on 51~100 with the dial switch.
LED Monitering Displa
See Note2.
R407C R22
y
– Centralized control not connected. Storing of refrigeration system connection information.
Ordinary control
– Errors valid.
Ordinary control
39 min.
– SW3-2 Function invalid
Stop all indoor units.
(no operation)
Ordinary control
49˚C
Invalid
– Centralized control connected. Deletion of refrigeration system connection information. Deletion
Adjustment operation
– Disregard errors.
Start forced defrosting.
90 min.
– SW3-2 Function valid
All indoor units test operation ON.
–7˚C
For 2 minutes.For 2 minutes.
2000
Pump down
53˚C
Valid
Before power is turned on.
During normal operation when power is on. Should be set on OFF. Before power is turned on.
Before power is turned on.
During normal operation when power is on.
During normal operation when power is on (only when switching from OFF/ON)
– During normal operation when power is on.
During normal operation when power is on. (Except during defrosting)
– During normal operation when power is on. When SW3-1 is ON after power is turned on. During normal operation when power is on. During normal operation when power is on. (Except during defrosting)
– During normal operation (only when switching from OFF/ON) During normal operation when power is on.
– Before power is turned on. During normal operation when power is on. When SW4-1 is ON.
––– – ––– – ––
– –
––
Night mode/Step demand
SWU3
R407C
Exist
R407C
Different unit model error
(7130)
Not exist
Different unit model error
(7130)
R22
R22
TH2
Night mode
Step demand
During normal operation when power is on.
– –
––
During normal operation when power is on.
10 minutes or more after compressor starts.
Note 1
Note 2
• SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
• If the address is set from 01 to 50, it automatically becomes 100.
The refrigerant model is recognized with SW3 and TH2.
Changes as shown below by on off change 0% 3%
6% 9% 12% –6% –3% 0%
4 5 6 7 8 9
10
[5] Function of Dip SW and Rotary SW
(1) Outdoor unit
Before power is turned on.
SW3-9
OFF
OFF
P200YREM-A–P250YREM-A
ON
ON
SW3-10
10˚C 15˚C
– 10˚C
- 18 -
(2) Indoor unit
DIP SW1, 3
Model P71 P80 P100 P125 P140 P200 P250 Capacity (model name) code
14 16 20 25 28 40 50
SW2 setting
Model P20 P25 P32 P40 P50 P63 Capacity (model name) code
45 681013
SW2 setting
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the
2: When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat of OFF.
table belo
Note 3: The DipSW setting is only effective during unit stopping (remote controller OFF) for SW1,2,3 and 4 commonly
and the power source is not required reset.
w.)
Setting of DIP SW2
Indoor unit inlet
None
100h
Ineffective Fan output display At stationary heating
Very low speed
SW1-7 setting
Ineffective
Ineffective
Heat pump
None
None None
1st setting
Down blow B, C
Effective
Effective
– –
Built in remote controller
Provided
2500h
Effective
Thermo. ON signal display
Always at heat.
Low speed
Set airflow
Effective
Effective
Cool.only
Provided
Provided Provided
2nd setting
Horizontal
Ineffective
Ineffective
– –
Room temp. sensor position Clogged filter detect. Filter duration OA intake Remote display select. Humidifier control Heating thermo. OFF airflow Heating thermo. OFF airflow Power failure automatic
return Power source start/stop Model selection
Louver
Vane Vane swing function Vane horizontal angle V Vane first angle
ane angle set for cooling
Heating 4deg up
– –
Alw
PLFY-VLMD-B only
ays ineffective for PKFY-P.VAM
Not provided for PKFY-P.VAM Provided for PLFY-P.VGM (ON) setting
Always down blow B,C for PKFY-P.VAM Horizontal (ON) setting for PLFY-P. VLMD-A
Ineffective (ON) setting for floor standing
SW1
SW3
1 2 3 4 5 6 7 8
9
10
1
2
3 4 5
6
7 8 9
10
Switch SW name
Operation by SW
Switch set timing
OFF ON OFF ON
Remarks
At unit stopping
(at remote
controller OFF)
Cooling capacity saving for PKFY-P. VAM, effective/ineffective
Model
Switch
SW1
SW3
3 6 7 3 4 6 8
PLFY-P
VAM-A(2)
OFF OFF
VLMD-B
VKM-A
OFF
ON
ON
ON
OFFONON
ON
PEFY-P
VML-A VMH-A
20~80VMM-A
100~140VMM-A
OFF
OFF ON
OFF ON
ON
ON
OFF OFF
OFF
OFF
ON OFF
ON OFF ON
ON
ON
ON
OFF
PDFY-P PFFY-P PCFY-P PKFY-P
VM-A
ON
VLRM-A, VLEM-A
OFF
VGM-A
PMFY-P
VBM-A
ON
V AM-A VGM-A
OFF OFF
OFF OFF
OFF
OFF
OFF
- 19 -
OFF
ON
OFF
ON
Ceiling height 3 3.5 m 2 2.8 m 1 2.3 m
Switch Function Operation by switch Switch set timing
SWA
SWA
SWA
SWB
SWC
Ceiling height setting
External static pressure setting
For options
Setting of air outlet opening
Airflow control
(PLFY-P-VKM-A) (PCFY-P-VGM-A)
(PLFY-P125VLMD-B)
(PLFY-P-VKM-A)
(PLFY-P-VKM-A, PCFY-P-VGM-A, PKFY-P-VGM-A, PDFY-P-VM-A)
The ceiling height is changed by SWB setting.
As this switch is used by interlocking with SWC, refer to the item of SWC for detail.
SWA
SWB
123
2-way 3.5 m 3.8 m 3.8 m 3-way 3.0 m 3.3 m 3.5 m 4-way 2.7 m 3.0 m 3.5 m
Set to the option to install the high efficiency filter
Always after powering
Always after powering
Always after powering
Always after powering
Always after powering
3
1
2
2-way
4-way
3-way
3
1
2
3
1
2
3
1
2
Option
Standard
(PDFY-P20 ~ 80VM-A, PEFY-P20 ~ 80VMM-A)
100Pa
50Pa 30Pa
For other models, change the setting of static pressure by replacing the connector.
Setting of DIP SW4 Setting of DIP SW5
12345
ON OFF ON OFF
ON OFF ON OFF
OFF
OFF
OFF OFF ON
ON OFF OFF
OFF
ON
ON
OFF ON OFF ON OFF
OFF
OFF ON ON
ON
– –
– –
––
– – – –
– –
ON ON
ON
ON
OFF OFF
OFF
OFF
OFF
OFF OFF OFF
ON ON ON
OFF OFF OFF
ON OFF OFF
OFF OFF ON
ON ON ON OFF
PMFY-P-VBM-A PLFY-P125VLMD-B PDFY-P20 ~ 80VM-A PLFY-P40 ~ 63VKM-A PLFY-P80 ~ 125VAM-A(2) PCFY-P-VGM-A PKFY-P-VGM-A PKFY-P-VAM-A PEFY PLFY-P20~100VLMD-B
-P20 ~ 80VMM-A
PFFY-P-VLEM-A, P-VLRM-A PEFY-P20 ~ 32VML-A PEFY-P40 ~ 140VMH-A PEHY-P200·250VMH-A
PDFY-P100·125VM-A PEFY-P100 ~ 140VMM-A
Model Circuit board used
SW4
Phase control
Relay selection
220V 240V
- 20 -
£ TEST RUN
[1] Before Test Run
(1) Check points before test run
1 Neither refrigerant leak nor loose power source/ transmission lines should be found.
2 Confirm that the resistance between the power source terminal block and the ground exceeds 2M by measur-
ing it with a DC500V megger. Do not run if it is lower than 2MΩ. Note) Never apply the megger to the MAIN board. If applied, the MAIN board will be broken.
3 Confirm that the Ball valve at both gas and liquid sides is being fully opened.
Note) Certainly close the cap.
45Be sure that the cr
Prior to Ver.E
The number of indoor units and the total number of remote controllers id displayed within the parenthesis ( ).
16 (32) 16 (32)
200 or lower
200 or higher
After Ver.F
20 (40) 16 (32)
(
1) Capability of the connected indoor units
Number of connected indoor units that
can be connected without a RP.
Remote controller type
Remote controller PAR-F25MA
ankcase heater has been powered by turning the main power source on at least 12 hours
before starting the test run. The shorter powering time causes compressor trouble.
(2) Caution at inverter check
Because the inverter power portion in outdoor unit electrical part box have a lot of high voltage portion, be sure to follow the instructions shown below.
During energizing power source, never touch inverter power portion because high voltage (approx. 580V) is applied to inverter power portion.
When checking,
Shut off main power source, and check it with tester, etc.
Allow 10 minutes after shutting off main power source.
Open the MAIN board mounting panel, and check whether voltage of both ends of electrolytic capacitor is 20V or less.
1
2
1
2
3
If any of the power supply wires (L1, L2, L3, N, ) are mistakenly connected, it is possible to damage the unit. Please exercise caution.
6
A transmission booster (RP) is required when the number of connected indoor unit models in a cooling system exceeds the number of models specified in the chart below. Note: The maximum number of units that can be controlled is determined by the indoor unit model, the type of
remote controller and their capabilities.
(
1) If even one unit that is higher than 200 exists in the cooling system, the maximum capacity will be 200 or higher.
Please refer to the installation manual for more details.
Before turning power on to the outdoor unit, first turn on the transmission booster. (If the outdoor unit are mistakenly
turned on first, turn on the transmission booster and then reset the outdoor unit power.)
- 21 -
(3) Check points for test run when mounting options
(4) Attention for mounting drain water lifting-up mechanism
Check point
Local remote controller displays code No. 2503, and the mechanism stops.
No overflow from drain pan. Drain water comes out by operations of
drain pump. Sound of pump operations is heard, and
drain water comes out. No water leakage from connecting
portions of water piping. Water is supplied to water supply tank,
and float switch is operating.
Built-in optional parts Mounting of drain
water removing mechanism
Mounting of perme­able film humidifier
Content of test run
Release connector of pump circuit, check error detection by pouring water into drain pan water inlet.
After that, connect connector of circuit.
Check pump operations and drain­age status in cooling (test run) mode.
Check humidifier operations and water supply status in heating (test run) mode.
1
2
3
4
5
Result
1
2
3
Work
Disassembling and assembling of drain water removing mechanism
Mounting of float switch
Electric wiring
Float switch moves smoothly. Float switch is mounted on
mounting board straigh and
without deformation.
Float switch has no contact with
copper pipe. Wiring procedure is exactly followed. Connector portion is tightly hooked.
Content of test run
Lead wire from the control box is not damaged.
Rubber cap is properly inserted into drain water outlet of the drain pan?
Insulation of gas and liquid pipe is dealt with as shown in the right figure?
Drain pan and piping cover are mounted without gap?
Drain pan hooked on cut projection of the mechanism?
Float switch is installed without contacting the drain pan?
No mistakes in wiring? Connectors connected securely and
tightly? No tension on lead wire when sliding
on control box?
1 2
3
1 2
3
Check point Result
Insulation pipe
No gap
- 22 -
- 23 -
(5) Check points for system structure
ex. PUHY-P200YREM-A
Check points from installation work to test run.
Trouble
Not operate.
Not cool (at cooling). Not heat (at heating).
Not cool, not heat, error stop. Condensation drip in piping. Not cool, not heat, error stop.
Water leak, condensation drip in drain piping.
Error stop, not operate.
Electric shock. Error stop, not operate. Some electric parts should be damaged.
Classification
Installation and piping
Power source wiring
Portion
1
2
3
4
5
6
7
8
1
2
3
4
Check item
Instruction for selecting combination of outdoor unit, and indoor unit followed? (Maximum number of indoor units which can be connected, connecting model name, and total capacity.)
Follow limitation of refrigerant piping length? For ex­ample, 80m or less (total length : 240m) at the farthest.
Connecting piping size of branch piping correct? Refrigerant piping diameter correct? Refrigerant leak generated at connection? Insulation work for piping properly done? Specified amount of refrigerant replenished?
Pitch and insulation work for drain piping properly done? Specified switch capacity and wiring diameter of main
power source used?
Proper grounding work done on outdoor unit? The phases of the L line (L1, L2, L3) correct? L line and N line connected correct?
Classification Transmission
line
Portion Check item
¡
Limitation of transmission line length followed? For example, 200m or less (total length : 500m) at the farthest.
1.25mm2 or more transmission line used?
(Remote controller 10m or less 0.75mm
2
)
£ 2-core cable used for transmission line?
¢
Transmission line apar t from power source line by 5cm or more?
One refrigerant system per transmission line?
§
The short circuit connector is changed form CN41 to CN40 on the MAIN board when the system is centralized control? (Just one outdoor unit. Not all outdoor units.)
No connection trouble in transmission line?
Connection of wrong remote controller line terminals?
MA Remote controller : TB15
M-NET Remote controller : TB5
Trouble
Erroneous operation, error stop.
Erroneous operation, error stop.
Error stop in case multiple-core cable is used.
Erroneous operation, error stop. Not operate. Not operate.
Error stop or not operate. Never finish the initial mode.
System set
Before starting
Error stop or not operate.
Can not be properly set with power source turned on.
Not operate. Set temperature not obtained at
heating operations (Thermostat stop is difficult)
Error stop.
Error stop, compressor trouble.
1
2
1
2 3
4
Address setting properly done? (M-NET Remote controller, indoor unit and outdoor unit.)
Setting of address No. done when shutting off power source?
Address numbers not duplicated? Turned on SW3-8 on indoor unit circuit board when
mounting room thermistor sensor?
Refrigerant piping ball valve (Liquid pressure pipe, gas pressure pipe) opened?
Turn on power source 12 hours before starting operations?
STAND BY DEFROST
ERROR CODE
D A I L Y
AUTO OFF
CENTRALLY CONTROLLED
CLOCK
REMAINDER
ON OFF
˚C
1Hr.
NOT AVAILABLE
˚C
CHECK MODE
FILTER
CHECK
TEST RUN
LIMIT TEMP.
ON/OFF
TEMP
FILTER
CHECK TEST
ON OFF
CLOCK
PAR-F27MEA
TIMER SET
2 31
Breakers
for Current
Leakage
Switch
- 24 -
1Hr.
˚C
ON OFF
CLOCK
REMAINDER
ERROR CODE
˚C
ON OFF
CLOCK
NOT AVAILABLE
CHECK MODE
LIMIT TEMP.
ON/OFF
FILTER
TEST RUN
FILTER
CHECK TEST
PAR-F27MEA
STAND BY DEFROST
CENTRALLY CONTROLLED
D A I L Y
AUTO OFF
CHECK
TEMP
TIMER SET
Loading...
+ 94 hidden pages