Mitsubishi Electronics PUHY-P144, PUHY-P168, PUHY-P216, PUHY-P36, PUHY-P240YTSHMU-A User Manual

...
Safety Precautions
Before installing the unit, thoroughly read the following safety precautions.Observe these safety precautions for your safety.
WARNING
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or death.
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or damage to the unit.
After reading this manual, give it to the user to retain for future reference.Keep this manual for easy reference. When the unit is moved or repaired, give this manual to those who provide these
services. When the user changes, make sure that the new user receives this manual.
WARNING
Ask your dealer or a qualified technician to install the unit.
Improper installation by the user may result in water leak­age, electric shock, smoke, and/or fire.
Properly install the unit on a surface that can with­stand the weight of the unit.
Unit installed on an unstable surface may fall and cause in­jury.
Only use specified cables. Securely connect each ca­ble so that the terminals do not carry the weight of the cable.
Improperly connected or fixed cables may produce heat and start a fire.
Take appropriate safety measures against strong winds and earthquakes to prevent the unit from falling.
If the unit is not installed properly, the unit may fall and cause serious injury to the person or damage to the unit.
Do not make any modifications or alterations to the unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock, smoke, and/or fire.
In the event of a refrigerant leak, thoroughly ventilate the room.
If refrigerant gas leaks and comes in contact with an open flame, poisonous gases will be produced.
When installing the All-Fresh type units, take it into consideration that the outside air may be discharged directly into the room when the thermo is turned off.
Direct exposure to outdoor air may have an adverse effect on health. It may also result in food spoilage.
Properly install the unit according to the instructions in the installation manual.
Improper installation may result in water leakage, electric shock, smoke, and/or fire.
Have all electrical work performed by an authorized electrician according to the local regulations and in­structions in this manual, and a dedicated circuit must be used.
Insufficient capacity of the power supply circuit or improper installation may result in malfunctions of the unit, electric shock, smoke, and/or fire.
Do not touch the heat exchanger fins.
The fins are sharp and dangerous.
HWE08040 GB
ii
WARNING
Securely attach the terminal block cover (panel) to the unit.
If the terminal block cover (panel) is not installed properly, dust and/or water may infiltrate and pose a risk of electric shock, smoke, and/or fire.
Only use the type of refrigerant that is indicated on the unit when installing or reinstalling the unit.
Infiltration of any other type of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.
When installing the unit in a small room, exercise cau­tion and take measures against leaked refrigerant reaching the limiting concentration.
Consult your dealer with any questions regarding limiting concentrations and for precautionary measures before in­stalling the unit. Leaked refrigerant gas exceeding the lim­iting concentration causes oxygen deficiency.
Consult your dealer or a specialist when moving or re­installing the unit.
Improper installation may result in water leakage, electric shock, and/or fire.
After completing the service work, check for a gas leak.
If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, poisonous gases may be produced.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature switch by defeating the safety features of these devices, or the use of accessories other than the ones that are recom­mended by MITSUBISHI may result in smoke, fire, and/or explosion.
Only use accessories recommended by MITSUBISHI.
Ask a qualified technician to install the unit. Improper instal­lation by the user may result in water leakage, electric shock, smoke, and/or fire.
Control box houses high-voltage parts.
When opening or closing the front panel of the control box, do not let it come into contact with any of the internal com­ponents. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
HWE08040 GB
ii
Precautions for handling units for use with R410A
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the re-
sidual refrigerant and refrigerating machine oil in the exist­ing piping may cause the refrigerating machine oil in the new unit to deteriorate.
R410A is a high-pressure refrigerant and can cause the
existing pipes to burst.
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
Store the pipes to be installed indoors, and keep both ends of the pipes sealed until immediately before braz­ing. (Keep elbows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate or cause the unit to malfunction.
Use a small amount of ester oil, ether oil, or alkylben­zene to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the re­frigerating machine oil to deteriorate.
Charge liquid refrigerant (as opposed to gaseous re­frigerant) into the system.
If gaseous refrigerant is charged into the system, the com­position of the refrigerant in the cylinder will change and may result in performance loss.
Use a vacuum pump with a reverse-flow check valve.
If a vacuum pump that is not equipped with a reverse-flow check valve is used, the vacuum pump oil may flow into the refrigerant cycle and cause the refrigerating machine oil to deteriorate.
Prepare tools for exclusive use with R410A. Do not use the following tools if they have been used with the con­ventional refrigerant (gauge manifold, charging hose, gas leak detector, reverse-flow check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.).
If the refrigerant or the refrigerating machine oil left on
these tools are mixed in with R410A, it may cause the re­frigerating machine oil to deteriorate.
Infiltration of water may cause the refrigerating machine
oil to deteriorate.
Gas leak detectors for conventional refrigerants will not
detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrig­erant will change, and the unit may experience power loss.
Exercise special care when handling the tools for use with R410A.
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate.
Only use refrigerant R410A.
The use of other types of refrigerant that contain chlorine (i.e. R22) may cause the refrigerating machine oil to deteri­orate.
HWE08040 GB
iiiiii
Before installing the unit
WARNING
Do not install the unit where a gas leak may occur.
If gaseous refrigerant leaks and piles up around the unit, it may be ignited.
Do not use the unit to keep food items, animals, plants, artifacts, or for other special purposes.
The unit is not designed to preserve food products.
Do not use the unit in an unusual environment.
Do not install the unit where a large amount of oil or steam
is present or where acidic or alkaline solutions or chemical sprays are used frequently. Doing so may lead to a re­markable drop in performance, electric shock, malfunc­tions, smoke, and/or fire.
The presence of organic solvents or corrosive gas (i.e.
ammonia, sulfur compounds, and acid) may cause gas leakage or water leakage.
When installing the unit in a hospital, take appropriate measures to reduce noise interference.
High-frequency medical equipment may interfere with the normal operation of the air conditioner or vice versa.
Do not install the unit on or over things that cannot get wet.
When the humidity level exceeds 80% or if the drainage system is clogged, the indoor unit may drip water. Drain wa­ter is also discharged from the outdoor unit. Install a central­ized drainage system if necessary.
HWE08040 GB
iv
Before installing the unit (moving and reinstalling the unit) and performing electrical work
Properly ground the unit.
Do not connect the grounding wire to a gas pipe, water pipe, lightning rod, or grounding wire from a telephone pole. Im­proper grounding may result in electric shock, smoke, fire, and/or malfunction due to noise interference.
Do not put tension on the power supply wires.
If tension is put on the wires, they may break and result in excessive heat, smoke, and/or fire.
Install an earth leakage breaker to avoid the risk of electric shock.
Failure to install an earth leakage breaker may result in electric shock, smoke, and/or fire.
Use the kind of power supply wires that are specified in the installation manual.
The use of wrong kind of power supply wires may result in current leak, electric shock, and/or fire.
Use breakers and fuses (current breaker, remote switch <switch + Type-B fuse>, moulded case circuit breaker) with the proper current capacity.
The use of wrong capacity fuses, steel wires, or copper wires may result in malfunctions, smoke, and/or fire.
Periodically check the installation base for damage.
If the unit is left on a damaged platform, it may fall and cause injury.
Properly install the drain pipes according to the in­structions in the installation manual. Keep them insu­lated to avoid dew condensation.
Improper plumbing work may result in water leakage and damage to the furnishings.
Exercise caution when transporting products.
Products weighing more than 20 kg should not be carried
alone.
Do not carry the product by the PP bands that are used on
some products.
Do not touch the heat exchanger fins. They are sharp and
dangerous.
When lifting the unit with a crane, secure all four corners
to prevent the unit from falling.
Properly dispose of the packing materials.
Nails and wood pieces in the package may pose a risk of
injury.
Plastic bags may pose a risk of choking hazard to chil-
dren. Tear plastic bags into pieces before disposing of them.
Do not spray water on the air conditioner or immerse the air conditioner in water.
Otherwise, electric shock and/or fire may result.
When handling units, always wear protective gloves to protect your hands from metal parts and high-tempera­ture parts.
HWE08040 GB
vv
Before the test run
Turn on the unit at least 12 hours before the test run.
Keep the unit turned on throughout the season. If the unit is turned off in the middle of a season, it may result in malfunc­tions.
To avoid the risk of electric shock or malfunction of the unit, do not operate switches with wet hands.
Do not touch the refrigerant pipes with bare hands dur­ing and immediately after operation.
During or immediately after operation, certain parts of the unit such as pipes and compressor may be either very cold or hot, depending on the state of the refrigerant in the unit at the time. To reduce the risk of frost bites and burns, do not touch these parts with bare hands.
Do not operate the unit without panels and safety guards.
Rotating, high-temperature, or high-voltage parts on the unit pose a risk of burns and/or electric shock.
Do not turn off the power immediately after stopping the operation.
Keep the unit on for at least five minutes before turning off the power to prevent water leakage or malfunction.
Do not operate the unit without the air filter.
Dust particles may build up in the system and cause mal­functions.
HWE08040 GB
vi
CONTENTS
I
II
III
IV
V
VI
VII
VIII
IX
X
Read Before Servicing
[1] Read Before Servicing.............................................................................................................. 3
[2] Necessary Tools and Materials ................................................................................................ 4
[3] Piping Materials ........................................................................................................................ 5
[4] Storage of Piping ...................................................................................................................... 7
[5] Pipe Processing........................................................................................................................ 7
[6] Brazing...................................................................................................................................... 8
[7] Air Tightness Test..................................................................................................................... 9
[8] Vacuum Drying (Evacuation) ..................................................................................................10
[9] Refrigerant Charging .............................................................................................................. 11
[10] Remedies to be taken in case of a Refrigerant Leak............................................................ 11
[11] Characteristics of the Conventional and the New Refrigerants ............................................ 12
[12] Notes on Refrigerating Machine Oil ...................................................................................... 13
Restrictions
[1] System configuration .............................................................................................................. 17
[2] Types and Maximum allowable Length of Cables .................................................................. 18
[3] Switch Settings and Address Settings .................................................................................... 19
[4] Sample System Connection ................................................................................................... 26
[5] An Example of a System to which an MA Remote Controller is connected ........................... 27
[6] An Example of a System to which an M-NET Remote Controller is connected ..................... 37
[7] An Example of a System to which both MA Remote Controller and M-NET Remote
Controller are connected ........................................................................................................39
[8] Restrictions on Pipe Length.................................................................................................... 41
Outdoor Unit Components
[1] Outdoor Unit Components and Refrigerant Circuit ................................................................. 47
[2] Control Box of the Outdoor Unit.............................................................................................. 49
[3] Outdoor Unit Circuit Board...................................................................................................... 52
Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers .......................................... 65
[2] Group Settings and Interlock Settings via the ME Remote Controller .................................... 66
[3] Interlock Settings via the MA Remote Controller .................................................................... 70
[4] Using the built-in Temperature Sensor on the Remote Controller .......................................... 71
Electrical Wiring Diagram
[1] Electrical Wiring Diagram of the Outdoor Unit ........................................................................ 75
[2] Electrical Wiring Diagram of Transmission Booster................................................................ 78
Refrigerant Circuit
[1] Refrigerant Circuit Diagram .................................................................................................... 81
[2] Principal Parts and Functions ................................................................................................. 82
Control
[1] Functions and Factory Settings of the Dipswitches ................................................................ 89
[2] Controlling the Outdoor Unit ................................................................................................... 96
[3] Operation Flow Chart............................................................................................................ 108
Test Run Mode
[1] Items to be checked before a Test Run ................................................................................ 115
[2] Test Run Method .................................................................................................................. 116
[3] Operating Characteristic and Refrigerant Amount................................................................ 117
[4] Adjusting the Refrigerant Amount......................................................................................... 117
[5] Refrigerant Amount Adjust Mode.......................................................................................... 120
[6] The following symptoms are normal. .................................................................................... 122
[7] Standard Operation Data (Reference Data) ......................................................................... 123
Troubleshooting
[1] Error Code Lists.................................................................................................................... 149
[2] Responding to Error Display on the Remote Controller........................................................ 152
[3] Investigation of Transmission Wave Shape/Noise ............................................................... 231
[4] Troubleshooting Principal Parts............................................................................................ 234
[5] Refrigerant Leak ................................................................................................................... 265
[6] Compressor Replacement Instructions................................................................................. 267
[7] Troubleshooting Using the Outdoor Unit LED Error Display................................................. 269
HWE08040 GB
LED Monitor Display on the Outdoor Unit Board
[1] How to Read the LED on the Service Monitor ...................................................................... 273
HWE08040 GB
I
Read Before Servicing
[1] Read Before Servicing .......................................................................................................3
[2] Necessary Tools and Materials.......................................................................................... 4
[3] Piping Materials .................................................................................................................5
[4] Storage of Piping ...............................................................................................................7
[5] Pipe Processing.................................................................................................................7
[6] Brazing............................................................................................................................... 8
[7] Air Tightness Test..............................................................................................................9
[8] Vacuum Drying (Evacuation) ........................................................................................... 10
[9] Refrigerant Charging........................................................................................................ 11
[10] Remedies to be taken in case of a Refrigerant Leak .......................................................11
[11] Characteristics of the Conventional and the New Refrigerants .......................................12
[12] Notes on Refrigerating Machine Oil ................................................................................. 13
HWE08040 GB
- 1 -
- 2 -
[ I Read Before Servicing ]
IRead Befo re Servicing
[1] Read Before Servicing
1. Check the type of refrigerant used in the system to be serviced. Refrigerant Type
Multi air conditioner for building application CITY MULTI THMU-A, YHMU-A series R410A
2. Check the symptoms exhibited by the unit to be serviced.
Refer to this service handbook for symptoms relating to the refrigerant cycle.
3. Thoroughly read the safety precautions at the beginning of this manual.
4. Preparing necessary tools: Prepare a set of tools to be used exclusively with each type of refrigerant.
Refer to "Necessary Tools and Materials" for information on the use of tools.(page 4)
5. Verification of the connecting pipes: Verify the type of refrigerant used for the unit to be moved or replaced.
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free
of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
6. If there is a leak of gaseous refrigerant and the remaining refrigerant is exposed to an open flame, a poisonous gas hydrofluoric acid may form. Keep workplace well ventilated.
Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.The use of refrigerant that contains chloride, such as R22, will cause the refrigerating machine oil to deteriorate.
HWE08040 GB
- 3 -
[ I Read Before Servicing ]
[2] Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C)
1. To be used exclusively with R410A (not to be used if used with R22 or R407C)
Tools/Materials Use Notes
Gauge Manifold Evacuation and refrigerant charging Higher than 5.09MPa[738psi] on the
Charging Hose Evacuation and refrigerant charging The hose diameter is larger than the
Refrigerant Recovery Cylinder Refrigerant recovery
Refrigerant Cylinder Refrigerant charging The refrigerant type is indicated. The
Charging Port on the Refrigerant Cylinder Refrigerant charging The charge port diameter is larger
Flare Nut Connection of the unit with the pipes Use Type-2 Flare nuts.
2. Tools and materials that may be used with R410A with some restrictions
Tools/Materials Use Notes
Gas Leak Detector Gas leak detection The ones for use with HFC refrigerant
Vacuum Pump Vacuum drying May be used if a check valve adapter
Flare Tool Flare processing Flare processing dimensions for the
Refrigerant Recovery Equipment Refrigerant recovery May be used if compatible with
high-pressure side
conventional model.
cylinder is pink.
than that of the current port.
may be used.
is attached.
piping in the system using the new re­frigerant differ from those of R22. Re­fer to next page.
R410A.
3. Tools and materials that are used with R22 or R407C that may also be used with R410A
Tools/Materials Use Notes
Vacuum Pump with a Check Valve Vacuum drying
Bender Bending pipes
Torque Wrench Tightening flare nuts Only the flare processing dimensions
for pipes that have a diameter of ø12.70 (1/2") and ø15.88 (5/8") have been changed.
Pipe Cutter Cutting pipes
Welder and Nitrogen Cylinder Welding pipes
Refrigerant Charging Meter Refrigerant charging
Vacuum Gauge Vacuum level check
4. Tools and materials that must not be used with R410A
Tools/Materials Use Notes
Charging Cylinder Refrigerant charging Prohibited to use
Tools for R410A must be handled with special care to keep moisture and dust from infiltrating the cycle.
HWE08040 GB
- 4 -
[ I Read Before Servicing ]
[3] Piping Materials
Do not use the existing piping!
1. Copper pipe materials
O-material (Annealed) Soft copper pipes (annealed copper pipes). They can easily be bent with hands.
1/2H-material (Drawn) Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed)
The distinction between O-materials (Annealed) and 1/2H-materials (Drawn) is made based on the strength of the pipes them-
selves.
O-materials (Annealed) can easily be bent with hands. 1/2H-materials (Drawn) are considerably stronger than O-material (Annealed) at the same thickness.
2. Types of copper pipes
Maximum working pressure Refrigerant type
3.45 MPa [500psi] R22, R407C etc.
4.30 MPa [624psi] R410A etc.
3. Piping materials/Radial thickness
Use refrigerant pipes made of phosphorus deoxidized copper. The operation pressure of the units that use R410A is higher than that of the units that use R22. Use pipes that have at least the radial thickness specified in the chart below. (Pipes with a radial thickness of 0.7 mm or less may not be used.)
at the same radial thickness.
Pipe size (mm[in]) Radial thickness (mm) Type
ø6.35 [1/4"] 0.8t
ø9.52 [3/8"] 0.8t
ø12.7 [1/2"] 0.8t
ø15.88 [5/8"] 1.0t
ø19.05 [3/4"] 1.0t
ø22.2 [7/8"] 1.0t
ø25.4 [1"] 1.0t
ø28.58 [1-1/8"] 1.0t
ø31.75 [1-1/4"] 1.1t
ø34.93 [1-3/8"] 1.1t
ø41.28 [1-5/8"] 1.2t
The pipes in the system that uses the refrigerant currently on the market are made with O-material (Annealed), even if the
pipe diameter is less than ø19.05 (3/4"). For a system that uses R410A, use pipes that are made with 1/2H-material (Drawn) unless the pipe diameter is at least ø19.05 (3/4") and the radial thickness is at least 1.2t.
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
O-material (Annealed)
1/2H-material,
H-material (Drawn)
HWE08040 GB
- 5 -
[ I Read Before Servicing ]
4. Thickness and refrigerant type indicated on the piping materials
Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5. Flare processing (O-material (Annealed) and OL-material only)
The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.
Flare processing dimensions (mm[in])
Pipe size (mm[in])
A dimension (mm)
R410A R22, R407C
ø6.35 [1/4"] 9.1 9.0
ø9.52 [3/8"] 13.2 13.0
ø12.7 [1/2"] 16.6 16.2
Dimension A
ø15.88 [5/8"] 19.7 19.4
ø19.05 [3/4"] 24.0 23.3
If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0 and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
6. Flare nut
The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.
Flare nut dimensions (mm[in])
Pipe size (mm[in])
B dimension (mm)
R410A R22, R407C
ø6.35 [1/4"] 17.0 17.0
ø9.52 [3/8"] 22.0 22.0
ø12.7 [1/2"] 26.0 24.0
Dimension B
ø15.88 [5/8"] 29.0 27.0
ø19.05 [3/4"] 36.0 36.0
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the local standards.
HWE08040 GB
- 6 -
[ I Read Before Servicing ]
[4] Storage of Piping
1. Storage location
Store the pipes to be used indoors. (Warehouse at site or owner's warehouse) If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe.
2. Sealing the pipe ends
Both ends of the pipes should be sealed until just before brazing. Keep elbow pipes and T-joints in plastic bags.
The new refrigerator oil is 10 times as hygroscopic as the conventional refrigerating machine oil (such as Suniso) and, if not handled with care, could easily introduce moisture into the system. Keep moisture out of the pipes, for it will cause the oil to deteriorate and cause a compressor failure.
[5] Pipe Processing
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Use a minimum amount of oil. Use only ester oil, ether oil, and alkylbenzene.
HWE08040 GB
- 7 -
[ I Read Before Servicing ]
[6] Brazing
No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide scale, water, and dust) out of the refrigerant system.
Example: Inside the brazed connection
Use of oxidized solder for brazing Use of non-oxidized solder for brazing
1. Items to be strictly observed
Do not conduct refrigerant piping work outdoors if raining.Use non-oxidized solder.Use a brazing material (BCuP-3) that requires no flux when brazing between copper pipes or between a copper pipe and
copper coupling.
If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.
2. Reasons
The new refrigerating machine oil is 10 times as hygroscopic as the conventional oil and is more likely to cause unit failure if
water infiltrates into the system.
Flux generally contains chloride. Residual flux in the refrigerant circuit will cause sludge to form.
3. Notes
Do not use commercially available antioxidants because they may cause the pipes to corrode or refrigerating machine oil to deteriorate.
HWE08040 GB
- 8 -
[ I Read Before Servicing ]
[7] Air Tightness Test
No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak.
Halide torch R22 leakage detector
1. Items to be strictly observed
Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight-
ness, taking temperature variations into account.
Refrigerant R410A must be charged in its liquid state (vs. gaseous state).
2. Reasons
Oxygen, if used for an air tightness test, poses a risk of explosion. (Only use nitrogen to check air tightness.)Refrigerant R410A must be charged in its liquid state. If gaseous refrigerant in the cylinder is drawn out first, the composition
of the remaining refrigerant in the cylinder will change and become unsuitable for use.
3. Notes
Procure a leak detector that is specifically designed to detect an HFC leak. A leak detector for R22 will not detect an HFC(R410A) leak.
HWE08040 GB
- 9 -
[ I Read Before Servicing ]
[8] Vacuum Drying (Evacuation)
(Photo1) 15010H (Photo2) 14010
Recommended vacuum gauge: ROBINAIR 14010 Thermistor Vacuum Gauge
1. Vacuum pump with a reverse-flow check valve (Photo1)
To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum pump with a reverse-flow check valve. A reverse-flow check valve may also be added to the vacuum pump currently in use.
2. Standard of vacuum degree (Photo 2)
Use a vacuum pump that attains 0.5Torr(65Pa) or lower degree of vacuum after 5 minutes of operation, and connect it directly to the vacuum gauge. Use a pump well-maintained with an appropriate lubricant. A poorly maintained vacuum pump may not be able to attain the desired degree of vacuum.
3. Required precision of vacuum gauge
Use a vacuum gauge that registers a vacuum degree of 5Torr(650Pa) and measures at intervals of 1Torr(130Pa). (A recom­mended vacuum gauge is shown in Photo2.) Do not use a commonly used gauge manifold because it cannot register a vacuum degree of 5Torr(650Pa).
4. Evacuation time
After the degree of vacuum has reached 5Torr(650Pa), evacuate for an additional 1 hour. (A thorough vacuum drying re-
moves moisture in the pipes.)
Verify that the vacuum degree has not risen by more than 1Torr(130Pa) 1hour after evacuation. A rise by less than
1Torr(130Pa) is acceptable.
If the vacuum is lost by more than 1Torr(130Pa), conduct evacuation, following the instructions in section 6. Special vacuum
drying.
5. Procedures for stopping vacuum pump
To prevent the reverse flow of vacuum pump oil, open the relief valve on the vacuum pump side, or draw in air by loosening the charge hose, and then stop the operation. The same procedures should be followed when stopping a vacuum pump with a reverse-flow check valve.
6. Special vacuum drying
When 5Torr(650Pa) or lower degree of vacuum cannot be attained after 3 hours of evacuation, it is likely that water has pen-
etrated the system or that there is a leak.
If water infiltrates the system, break the vacuum with nitrogen. Pressurize the system with nitrogen gas to
0.5kgf/cm
2
G(0.05MPa) and evacuate again. Repeat this cycle of pressurizing and evacuation either until the degree of vac-
uum below 5Torr(650Pa) is attained or until the pressure stops rising.
Only use nitrogen gas for vacuum breaking. (The use of oxygen may result in an explosion.)
HWE08040 GB
- 10 -
[ I Read Before Servicing ]
[9] Refrigerant Charging
Cylinder with a siphon
Cylinder without a siphon
Cylin-
Cylin-
der
der
Cylinder color R410A is pink. Refrigerant charging in the liquid state
Valve Valve
liquid
liquid
1. Reasons
R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and be­come unsuitable for use.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check the type of the cylinder on the label before use.
[10] Remedies to be taken in case of a Refrigerant Leak
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in the liquid state.) Refer to "IX [5] Refrigerant Leak".(page 265)
HWE08040 GB
- 11 -
[ I Read Before Servicing ]
[11] Characteristics of the Conventional and the New Refrigerants
1. Chemical property
As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant. However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will accumulate at the bottom of the room and may cause hypoxia. If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a con­fined area.
New Refrigerant (HFC type) Conventional Refriger-
ant (HCFC type)
R410A R407C R22
R32/R125 R32/R125/R134a R22
Composition (wt%) (50/50) (23/25/52) (100)
Type of Refrigerant Pseudo-azeotropic
Refrigerant
Non-azeotropic
Refrigerant
Single Refrigerant
Chloride Not included Not included Included
Safety Class A1/A1 A1/A1 A1
Molecular Weight 72.6 86.2 86.5
Boiling Point (°C/°F) -51.4/-60.5 -43.6/-46.4 -40.8/-41.4
Steam Pressure
1.557/226 0.9177/133 0.94/136
(25°C,MPa/77°F,psi) (gauge)
Saturated Steam Density (25°C,kg/m
3
/77°F,psi)
64.0 42.5 44.4
Flammability Nonflammable Nonflammable Nonflammable
Ozone Depletion Coefficient (ODP)
Global Warming Coefficient (GWP)
*1
*2
Refrigerant Charging Method Refrigerant charging in
Replenishment of Refrigerant after a Refrigerant
0 0 0.055
1730 1530 1700
the liquid state
Refrigerant charging in
the liquid state
Refrigerant charging in
the gaseous state
Available Available Available
Leak
*1 When CFC11 is used as a reference *2 When CO
is used as a reference
2
2. Refrigerant composition
R410A is a pseudo-azeotropic HFC blend and can almost be handled the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and become unsuitable for use. If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced.
3. Pressure characteristics
The pressure in the system using R410A is 1.6 times as great as that in the system using R22.
Pressure (gauge)
Temperature (°C/°F)
R410A R407C R22
MPa/psi MPa/psi MPa/psi
-20/-4 0.30/44 0.18/26 0.14/20
0/32 0.70/102 0.47/68 0.40/58
20/68 1.34/194 0.94/136 0.81/117
40/104 2.31/335 1.44/209 1.44/209
60/140 3.73/541 2.44/354 2.33/338
65/149 4.17/605 2.75/399 2.60/377
HWE08040 GB
- 12 -
[ I Read Before Servicing ]
[12] Notes on Refrigerating Machine Oil
1. Refrigerating machine oil in the HFC refrigerant system
HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system. Note that the ester oil used in the system has properties that are different from commercially available ester oil.
Refrigerant Refrigerating machine oil
R22 Mineral oil
R407C Ester oil
R410A Ester oil
2. Effects of contaminants
*1
Refrigerating machine oil used in the HFC system must be handled with special care to keep contaminants out. The table below shows the effect of contaminants in the refrigerating machine oil on the refrigeration cycle.
3. The effects of contaminants in the refrigerating machine oil on the refrigeration cycle.
Cause Symptoms Effects on the refrigerant cycle
Water infiltration Frozen expansion valve
and capillary tubes
Clogged expansion valve and capillary tubes Poor cooling performance Compressor overheat Motor insulation failure Burnt motor Coppering of the orbiting scroll Lock Burn-in on the orbiting scroll
Clogged expansion valve, capillary tubes, and drier Poor cooling performance Compressor overheat
Burn-in on the orbiting scroll
Hydrolysis
Air infiltration Oxidization
Adhesion to expansion valve and capillary tubes
Dust, dirt
Infiltration of contaminants
Infiltration of contaminants into the com­pressor
Sludge formation and ad­hesion Acid generation Oxidization Oil degradation
Sludge formation and adhesion Clogged expansion valve and capillary tubes
Mineral oil etc.
Poor cooling performance Compressor overheat
Oil degradation Burn-in on the orbiting scroll
*1. Contaminants is defined as moisture, air, processing oil, dust/dirt, wrong types of refrigerant, and refrigerating machine oil.
HWE08040 GB
- 13 -
- 14 -
II
Restrictions
[1] System configuration ....................................................................................................... 17
[2] Types and Maximum allowable Length of Cables ...........................................................18
[3] Switch Settings and Address Settings ............................................................................. 19
[4] Sample System Connection............................................................................................. 26
[5] An Example of a System to which an MA Remote Controller is connected..................... 27
[6] An Example of a System to which an M-NET Remote Controller is connected............... 37
[7] An Example of a System to which both MA Remote Controller and M-NET Remote
Controller are connected.................................................................................................. 39
[8] Restrictions on Pipe Length ............................................................................................. 41
HWE08040 GB
- 15 -
- 16 -
[ II Restrictions ]
IIRestrictions
[1] System configuration
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
Outdoor
units
Composing units Maximum total capacity
of connectable indoor
units
Maximum number of connectable in-
door units
Types of connectable in-
door units
72 - - - 36 - 96 15 P06 - P96models
96 - - - 48 - 124 20
R410A series indoor units
120 - - - 60 - 156 26
144 72 72 - 72 - 187 31
168 96 72 - 84 - 218 36
192 120 72 - 96 - 249 41
216 120 96 - 108 - 280 46
240 120 120 - 120 - 312 50
264 120 72 72 132 - 343
288 120 96 72 144 - 374
312 120 120 72 156 - 405
336 120 120 96 168 - 436
360 120 120 120 180 - 468
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE08040 GB
- 17 -
[ II Restrictions ]
[2] Types and Maximum allowable Length of Cables
1. Wiring work
(1) Notes
1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this man­ual.
2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference. (Do not put the control cable and power supply cable in the same conduit tube.)
3) Provide grounding for the outdoor unit as required.
4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing.
5) Do not connect power supply wiring to the terminal block for transmission line. Doing so will damage the electronic compo­nents on the terminal block.
6) Use 2-core shielded cables as transmission cables. Use a separate 2-core control cable for each refrigerant system. Do not use a single multiple-core cable to connect indoor
units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and malfunctions.
TB
TB
3
7
TB
TB
7
3
Outdoor unit
TB3TB7TB3TB
TB3TB
7
7
2-core shielded cable
TB3TB
7
2-core shielded cable
TB3: Terminal block for indoor-outdoor transmission line TB7: Terminal block for centralized control
Indoor unit
Remote Controller
TB
TB
3
7
TB
TB
7
3
Outdoor unit
TB3TB7TB3TB
TB3TB
7
7
multiple-core cable
TB3TB
7
Indoor unit
Remote Controller
(2) Control wiring
Different types of control wiring are used for different systems. Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work.
Types and maximum allowable length of cables
Control lines are categorized into 2 types: transmission line and remote controller line. Use the appropriate type of cables and observe the maximum allowable length specified for a given system. If a given system
has a long transmission line or if a noise source is located near the unit, place the unit away from the noise source to reduce noise interference.
1) M-NET transmission line
Cable type
Facility type
Type Shielded cable CVVS, CPEVS, MVVS
Number of cores
Cable size Larger than 1.25mm
All facility types
2-core cable
2
[AWG16]
Maximum transmission line distance between the outdoor unit and the far-
200 m [656ft] max.
thest indoor unit
Maximum transmission line distance for central­ized control and Indoor/ outdoor transmission line (Maximum line distance
500 m [1640ft] max. *The maximum overall line length from the power supply unit on the transmission lines for centralized control to each outdoor unit or to the system controller is 200m [656ft] max.
via outdoor unit)
HWE08040 GB
- 18 -
[ II Restrictions ]
2) Remote controller wiring
MA remote controller
*1
M-NET remote controller
*2
Type CVV CVV
Number of cores
Cable type
Cable size
Maximum overall line length
2-core cable 2-core cable
0.3 to 1.25mm [AWG22 to 16] (0.75 to 1.25mm [AWG18 to 16]
2 *3
2) *4
0.3 to 1.25mm [AWG22 to 16] (0.75 to 1.25mm [AWG18 to 16]
The section of the cable that exceeds 10m
200 m [656ft] max.
[32ft] must be included in the maximum in­door-outdoor transmission line distance.
2 *3
2) *4
*1 MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and
wireless remote controller. *2 M-NET remote controller refers to ME remote controller and ME simple remote controller. *3 The use of cables that are smaller than 0.75mm
2
(AWG18) is recommended for easy handling.
*4 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi-
cations shown in the parenthesis.
[3] Switch Settings and Address Settings
1. Switch setting
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work. Set the switches while the power is turned off. If the switch settings are changed while the unit is being powered, those changes will not take effect, and the unit will not function properly.
Units on which to set the switches Symbol Units to which the power must be shut off
*3
CITY MULTI indoor unit Main/sub unit IC Outdoor units
LOSSNAY, OA processing unit
*1
LC Outdoor units
Air handling kit IC Outdoor units
and Indoor units
*3
and LOSSNAY
*3
or field supplied air handling
unit
M-NET remote controller Main/sub remote
RC Outdoor units
*3
controller
MA remote controller Main/sub remote
MA Indoor units
controller
CITY MULTI outdoor unit
*2
OC,OS1,OS2 Outdoor units
*3
*1. Applicable when LOSSNAY units are connected to the indoor-outdoor transmission line. *2. The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of
capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
*3. Turn off the power to all the outdoor units in the same refrigerant circuit.
HWE08040 GB
- 19 -
[ II Restrictions ]
2. M-NET Address settings (1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
Unit or controller Address setting
Setting method Facto-
range
CITY MULTI in­door unit
Main/sub unit 00,
01 to 50
*1
Assign the smallest address to the main indoor unit in the group, and assign sequential address numbers to the rest of the indoor units in the same group.
*4
M-NET adapter
M-NET control in­terface
Free Plan adapt­er
LOSSNAY, OA processing unit Air handling kit
00, 01 to 50
*1
Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
M-NET remote controller
Main remote controller
Sub remote controller
101 to 150 Add 100 to the smallest address of all the indoor units
in the same group.
151 to 200
*2
Add 150 to the smallest address of all the indoor units in the same group.
MA remote controller No address settings required. (The main/sub setting must be made if 2
remote controllers are connected to the system.)
CITY MULTI outdoor unit 00,
51 to 100
System controller Group remote
201 to 250 Assign an address that equals the sum of the smallest
controller
System remote controller
ON/OFF re­mote controller
Schedule timer (compatible
*1,*3
Assign sequential addresses to the outdoor units in the same refrigerant circuit. The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
*5
group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the range listed on the left to each unit.
Assign an address that equals the sum of the smallest group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the range listed on the left to each unit.
with M-NET)
Central con­troller G(B)-50A
000, 201 to 250
Assign an arbitrary but unique address within the range listed on the left to each unit. The address must be set to "000" to control the K-control unit.
LM adapter 201 to 250 Assign an arbitrary but unique address within the
range listed on the left to each unit.
ry set-
ting
00
00
101
Main
00
201
202
000
247
*1. Address setting is not required for a City Multi system that consists of a single refrigerant circuit (with some exceptions). *2. To set the M-NET remote controller address to "200", set the rotary switches to "00". *3. To set the outdoor unit address to "100," set the rotary switches to "50." *4. Some indoor units have 2 or 3 controller boards that require address settings.
No. 2 controller board address must be equal to the sum of the No. 1 controller board address and 1, and the No.3
controller board address must equal to the No. 1 controller address and 2.
*5. The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of
capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
HWE08040 GB
- 20 -
[ II Restrictions ]
(2) Power supply switch connector connection on the outdoor unit
(Factory setting: The male power supply switch connector is connected to CN41.)
System configu­ration
Connection to the system con­troller
Power supply unit for transmission lines
Group operation of units in a sys­tem with multiple
Power supply switch connector connection
outdoor units
System with one outdoor unit
System with multiple outdoor units
_ _ _ Leave CN41 as it is
(Factory setting)
Not connected _ Not grouped
Grouped Disconnect the male connector from the fe-
With connection to the indoor unit system
With connection to the central­ized control system
Not required Grouped/not
grouped
Not required (Powered from the
*1
Grouped/not grouped
outdoor unit)
Required *
1
Grouped/not grouped
male power supply switch connector (CN41) and connect it to the female power supply switch connector (CN40) on only one of the outdoor units.
*Connect the S (shielded) terminal on the ter-
minal block (TB7) on the outdoor unit whose CN41 was replaced with CN40 to the ground terminal ( ) on the electric box.
Leave CN41 as it is (Factory setting)
*2
*1 The need for a power supply unit for transmission lines depends on the system configuration. *2 The replacement of the power jumper connector from CN41 to CN40 must be performed on only one outdoor unit in the
system.
(3) Settings for the centralized control switch for the outdoor unit (Factory setting: SW2-1 are set to OFF.)
System configuration Centralized control switch settings *
1
Connection to the system controller Not connected Leave it to OFF. (Factory setting)
Connection to the system controller Connected *
2
ON
*1 Set SW2-1 on all outdoor units in the same refrigerant circuit to the same setting. *2 When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
(4) Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to "OFF".)
To stop the fan during heating Thermo-OFF (SW1-7 and 1-8 on the indoor units to be set to ON), use the built-in thermistor on the remote controller or an optional thermistor.
1) To use the built-in sensor on the remote controller, set the SW1-1 to ON. Some models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
(Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models is ON.
2) When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON. When using an optional temperature sensor, install it where room temperature can be detected.
(5) Various start-stop controls (Indoor unit settings)
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
Function
Power ON/OFF by the plug
*1,*2,*3
Automatic restoration after power failure
Operation of the indoor unit when the operation is resumed after the unit was
stopped
Indoor unit will go into operation regardless of its operation status before power off (power failure). (In approx. 5 minutes)
Indoor unit will go into operation if it was in operation when the power was turned off (or cut off due to power failure). (In approx. 5 minutes)
Indoor unit will remain stopped regardless of its operation status before power
Setting (SW1)
910
OFF ON
ON OFF
OFF ON
off (power failure).
*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the
crankcase heater and may cause the compressor to malfunction when the unit is put back into operation. *2. Not applicable to units with a built-in drain pump or humidifier. *3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir-
cuits will be turned on or off by the plug. *4. Requires that the dipswitch settings for all the units in the group be made. *5. To control the external input to and output from the air conditioners with the PLC software for general equipment via the
G(B)-50A, set SW1-9 and SW1-10 to ON. With these settings made, the power start-stop function becomes disabled. To
use the auto recovery function after power failure while these settings are made, set SW1-5 to ON.
*4 *5
HWE08040 GB
- 21 -
[ II Restrictions ]
(6) Miscellaneous settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.") When using indoor unit as a cooling-only unit, set SW3-1 to ON.
(7) Various types of control using input-output signal connector on the outdoor unit (various connection options)
Type Usage Function
Input Prohibiting cooling/heating operation (thermo OFF) by an external
DEMAND (level) CN3D
input to the outdoor unit.
*It can be used as the DEMAND control device for each system.
Performs a low level noise operation of the outdoor unit by an ex­ternal input to the outdoor unit.
Low-noise mode
*3*4
(level)
to be
used
*1
*2
Option
Adapter for external input (PAC­SC36NA-E)
Terminal
* It can be used as the silent operation device for each refrigerant system.
Forces the outdoor unit to perform a fan operation by receiving sig­nals from the snow sensor.
*5
Cooling/heating operation can be changed by an external input to
Snow sensor signal
CN3S
input (level)
Auto-changeover CN3N
the outdoor unit.
Out-
How to extract signals from the outdoor unit
put
*It can be used as an operation status display device. *It can be used for an interlock operation with external devices.
Operation status of the compressor
Error status
*5
*6
CN51 Adapter for
external out­put (PAC­SC37SA-E)
*1. For detailed drawing, refer to "Example of wiring connection".
*2. For details, refer to (1) through (4) shown below.
*3. Low-noise mode is valid when Dip SW4-4 on the outdoor unit is set to OFF. When DIP SW4-4 is set to ON, 4 levels of
on-DEMAND are possible, using different configurations of low-noise mode input and DEMAND input settings.When 2 or more outdoor units exist in one refrigerant circuit system, 8 levels of on-DEMAND are possible. When 3 outdoor units exist in one refrigerant circuitsystem, 12 levels of on-DEMAND are possible.
*4. By setting Dip SW5-5, the Low-noise mode can be switched between the Capacity priority mode and the Low-noise pri-
ority mode. When SW5-5 is set to ON: The Low-noise mode always remains effective. When SW5-5 is set to OFF: The Low-noise mode is cancelled when certain outside temperature or pressure criteria are met, and the unit goes into normal operation (capacity priority mode).
Low-noise mode is effective Capacity priority mode becomes effective
Cooling Heating Cooling Heating
TH7 < 30°C [86°F] and 63HS1 < 32kg/cm
TH7 > 3°C [37°F]
2
and 63LS > 4.6kg/cm
2
TH7 > 35°C [95°F] or 63HS1 > 35kg/cm
TH7 < 0°C [32°F]
2
or 63LS < 3.9kg/cm
*5. Each outdoor unit in the system with multiple outdoor units requires the signal input/output setting to be made. *6. Take out signals from the outdoor unit (OC) if multiple outdoor units exist in a single system.
CAUTION
1) Wiring should be covered by insulation tube with supplementary insulation.
2) Use relays or switches with IEC or equivalent standard.
3) The electric strength between accessible parts and control circuit should have 2750V or more.
2
HWE08040 GB
- 22 -
[ II Restrictions ]
Example of wiring connection
(1) CN51
Distant control board
ecruosrewoppmaL
1
L
L
2
L1 : Outdoor unit error display lamp L2 : Compressor operation lamp (compressor running state) X, Y : Relay (coil =<0.9W : DC12V)
1. Optional part : PAC-SC37SA-E or field supply.
(3) CN3N
Relay circuit
X
Y
Preparations
in the field
Adapter
Maximum cable length is 10m
Relay circuit Adapter
X Y
Y
X
Preparations
in the field
2
1 2
3
Maximum cable length is 10m
Outdoor unit control board
CN3N
(2) CN3S
1
5 4 3
Outdoor unit control board
CN51
Relay circuit
X
Preparations
in the field
X : Relay
Snow sensor : The outdoor fan runs when X is closed
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
in stop mode or thermostat mode.
2. Optional part : PAC-SC36NA-E or field supply.
X
OFF
OFF
Y
ON
X : Cooling / Heating Y : Validity / Invalidity of X X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Normal
CoolingONHeating
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
Adapter
2
1 2
3
Maximum cable length is 10m
Outdoor unit control board
CN3S
(4) CN3D
Relay circuit
Preparations
in the field
X : Low-noise mode Y : Compressor ON/OFF X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Adapter
X
Y
Maximum cable length is 10m
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum appicable load =< 1mA at DC
1 2
3
Outdoor unit
2
control board
CN3D
1 2
Outdoor unit
2
control board
CN3D
Relay circuit
X
Adapter
3
Preparations
in the field
X : Low-noise mode X : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Maximum cable length is 10m
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
Low-noise mode : The noise level is reduced by controlling the maximum
fan frequency and maximum compressor frequency.
HWE08040 GB
- 23 -
[ II Restrictions ]
1) SW4-4: OFF (Compressor ON/OFF, Low-noise mode)
CN3D 1-3P Compressor ON/OFF
Open Compressor ON
Short-circuit Compressor OFF
*1
CN3D 1-2P Low-noise mode
*2
Open OFF
Short-circuit ON
*1. When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON , this function cannot be used. *2. This function and the 4 levels or 8 levels on-DEMAND function can be used together. Input the order to CN3D 1-2P on
the outdoor unit whose SW4-4 is set to OFF.
2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND)
(*3)
CN3D 1-2P
CN3D 1-3P Open Short-circuit
Open 100% (No DEMAND) 75%
Short-circuit 0% (Compressor OFF) 50%
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
Note the following steps to be taken when using the STEP DEMAND
(Example) When switching from 100% to 50%
Demand control
steps
If the step listed as the wrong example above is taken, thermo may go off. The percentage of the demand listed in the table above is an approximate value based on the compressor volume and does not necessarily correspond with the capacity. When this function is enabled, the night mode cannot be enabled.
(Wrong)
(Correct)
100%
100%
0%
75%
50%
50%
3) When SW4-4 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND)
8 levels of on-DEMAND No.2 CN3D
1-2P Open Short-circuit
No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit
Open Open 100% 50% 88% 75%
Short-circuit 50% 0% 38% 25%
Short-circuit Open 88% 38% 75% 63%
Short-circuit 75% 25% 63% 50%
*4. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON. *5. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.
(*4, *5)
HWE08040 GB
- 24 -
[ II Restrictions ]
4) When SW4-4 on the all outdoor units in one refrigerant circuit system is set to ON (12 levels of on-DEMAND)
12 levels of on-DE­MAND
No.2 CN3D 1-2P Open
1-3P Open Short-circuit
No.3 CN3D 1-2P Open Short-circuit Open Short-circuit
No.1 CN3D
1-2P 1-3P Open Short-
circuit
Open Short-
circuit
Open Short-
circuit
Open Short-
Open Open 100% 67% 92% 84% 67% 34% 59% 50%
Short-
67% 34% 59% 50% 34% 0% 25% 17%
circuit
Short-circuit Open 92% 59% 84% 75% 59% 25% 50% 42%
Short-
84% 50% 75% 67% 50% 17% 42% 34%
circuit
12 levels of on-DE­MAND
No.2 CN3D 1-2P Short-circuit
1-3P Open Short-circuit
No.3 CN3D 1-2P Open Short-circuit Open Short-circuit
No.1 CN3D
1-2P 1-3P Open Short-
circuit
Open Short-
circuit
Open Short-
circuit
Open Short-
Open Open 92% 59% 84% 75% 84% 50% 75% 67%
Short-
59% 25% 50% 42% 50% 17% 42% 34%
circuit
Short-circuit Open 84% 50% 75% 67% 75% 42% 67% 59%
Short-
75% 42% 67% 59% 67% 34% 59% 50%
circuit
(*4)
circuit
circuit
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON. *4. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.
HWE08040 GB
- 25 -
[ II Restrictions ]
[4] Sample System Connection
Examples of typical system connection are shown on pages [5] to [7]. Refer to the Installation Manual that came with each device or controller for details.
(1) An example of a system to which an MA remote controller is connected
System
configuration
System with one out-
1.
2.
door unit
System with one out-
door unit
Grouping of units in a
3.
system with multiple
outdoor units
System with one out-
4.
5.
door unit
System with one out-
door unit
Connection to the system controller
NO
NO
NO
With connection to transmission line
for centralized control
With connection to indoor-outdoor
transmission line
Address start up for in-
door and outdoor units
Automatic
address setup
Manual
address setup
Manual
address setup
Manual
address setup
Manual
address setup
Notes
Connection of multiple LOSS­NAY units
(2) An example of a system to which an M-NET remote controller is connected
System
configuration
System with one out-
1. door unit
Connection to the system controller
With connection to transmission line
for centralized control
Address start up for indoor
and outdoor units
Manual
address setup
Notes
(3) An example of a system to which both MA remote controller and M-NET remote controller are connected
System
configuration
System with one out-
1. door unit
Connection to the system controller
With connection to transmission
line for centralized control
Address start up for in­door and outdoor units
Manual
address setup
Notes
HWE08040 GB
- 26 -
[ II Restrictions ]
[5] An Example of a System to which an MA Remote Controller is connected
1. System with one outdoor unit (automatic address setup for both indoor and outdoor units) (1) Sample control wiring
Leave the male connector on CN41 as it is.
SW2-1 OFF
Leave the male connector on CN41 as it is.
SW2-1 OFF
OS1OS2
Leave the male connector on CN41 as it is.
SW2-1 OFF
00
TB7
TB3
S
TB3
TB7
M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2
TB3
S
L2L1
Group Group
OC
0000
TB7
S
IC
00
TB5STB
L3 L4
IC
00
15
1 2
m1
TB5STB
15
1 2
Interlock operation with the ventilation unit
LC
00
TB5
M1M2M1M2M1M2
S
L11
m4
A B
MA
(2) Cautions
1) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) A transmission booster is required in a system to which more than 32 indoor units (26 units if one or more indoor units of the 72 model or above is connected) are con­nected.
4) Automatic address setup is not available if start-stop in­put (CN32, CN51, CN41) is used for a group operation of indoor units. Refer to "[5] 2. Manual address setup for both indoor and outdoor units".(page 29)
5) To connect more than 2 LOSSNAY units to indoor units in the same system, refer to the next section "[5] 2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected".(page 29)
A B
MA
L12 L13
GroupGroup
IC
A B
RC
A B
MA
IC
0000
15
TB
TB5
M1M2 M1 M2 M1 M2
S 1 2
m5
MA
A B
MA
A B
TB5STB
15
1 2
A B
MA
m2
m3
(3) Maximum allowable length
1) Indoor/outdoor transmission line
2
Maximum distance (1.25mm
[AWG16] or larger) L1 +L2+L3+L4 200m[656ft] L1 +L2+L11+L12+L13 200m[656ft]
2) Transmission line for centralized control No connection is required.
3) MA remote controller wiring Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16]) m1 200m [656ft] m2+m3 200m [656ft] m4+m5 200m [656ft]
IC
00
TB5STB
15
1 2
HWE08040 GB
27- 27 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Daisy-chain terminals M1 and M2 on the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor units (OC, OS1, OS2) (Note 1), and terminals M1 and M2 on the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC). (Non-polarized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are au­tomatically designated as OC, OS1, and OS2 in the or­der of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor units (OC, OS1, OS2), and the S terminal on the terminal block (TB5) on the indoor unit (IC) with the shield wire of the shielded cable.
2) Transmission line for centralized control No connection is required.
3) MA remote controller wiring Connect terminals 1 and 2 on the terminal block for MA
remote controller line (TB15) on the indoor unit (IC) to the terminal block on the MA remote controller (MA). (Non­polarized two-wire)
When 2 remote controllers are connected to the sys­tem
When 2 remote controllers are connected to the system, connect terminals 1 and 2 of the terminal block (TB15) on the indoor unit (IC) to the terminal block on the two MA remote controllers.
Set one of the MA remote controllers to sub. (Refer to
(5) Address setting method
MA remote controller function selection or the installation manual for the MA remote controller for the setting meth­od.)
Group operation of indoor units
To perform a group operation of indoor units (IC), daisy­chain terminals 1 and 2 on the terminal block (TB15) on all indoor units (IC) in the same group, and then connect terminals 1 and 2 on the terminal block (TB15) on the in­door unit on one end to the terminal block on the MA re­mote controller. (Non-polarized two-wire)
When performing a group operation of indoor units that
have different functions, "Automatic indoor/outdoor ad­dress setup" is not available.
4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals on the terminal block (TB5) on LOSSNAY (LC). (Non-po­larized two-wire)
Interlock operation setting with all the indoor units in the
same system will automatically be made. (It is required that the Lossnay unit be turned on before the outdoor unit.)
Refer to "[5] 2. Manual address setup for both indoor and
outdoor units" in the following cases: performing an inter­lock operation of part of the indoor units in the system with a LOSSNAY unit, using LOSSNAY alone without in­terlocking it with any units, performing an interlock oper­ation of more than 16 indoor units with a LOSSNAY unit, or connecting two or more LOSSNAY units to indoor units in the same system.
5) Switch setting No address settings required.
Proce-
dures
Unit or controller
1 Indoor unit Main unit IC No settings re-
Sub unit IC
Address setting
range
quired.
Setting
method
Notes
- To perform a group opera­tion of indoor units that have different functions, refer to [5] 2.(page 29)
2 LOSSNAY LC No settings re-
-00
quired.
3MA
remote con­troller
Main remote con­troller
Sub remote con­troller
MA No settings re-
quired.
MA Sub
remote controller
-Main
Settings to be made ac­cording to the remote controller function se­lection
4 Outdoor unit (Note) OC
OS1
No settings re­quired.
-00
OS2
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
Factory
setting
00
- 28 -
GBHWE08040
[ II Restrictions ]
2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected (manual address setup for both indoor and outdoor units)
(1) Sample control wiring
Leave the male connector on CN41 as it is.
SW2-1 OFF
L1
Leave the male connector on CN41 as it is.
SW2-1 OFF
Leave the male connector on CN41 as it is.
SW2-1 OFF
53
TB7
TB3
S
TB3
TB7
M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2
TB3
S
L2
OCOS1OS2
5152
TB7
S
IC
01
TB5STB
M1M2 M1 M2 M1 M2
L3 L4
GroupGroup
IC
02
15
1 2
TB5STB
15
1 2
TB5
Interlock operation with the ventilation unit
LC
05
S
L11
(2) Cautions
1) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) A transmission booster is required in a system to which more than 32 indoor units (26 units if one or more indoor units of the 72 model or above is connected) are con­nected.
A B
MA
L12 L13
Group
IC
A B
MA
IC
0403
TB5
S
15
TB
1 2
A B
MA
TB5STB
15
1 2
(3) Maximum allowable length
1) Indoor/outdoor transmission line Same as [5] 1.
2) Transmission line for centralized control No connection is required.
3) MA remote controller wiring Same as [5] 1.
LC
06
TB5
S
M1M2M1M2M1M2
HWE08040 GB
29- 29 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Same as [5] 1.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control No connection is required.
3) MA remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
(5) Address setting method
Proce-
dures
Unit or controller
1 Indoor unit Main
IC 01 to 50 Assign the smallest ad-
Address
setting
unit
Sub unit Assign sequential numbers
2 LOSSNAY LC 01 to 50 Assign an arbitrary but
3MA
remote con­troller
Main remote control-
MA No
settings re­quired.
ler
Sub remote control-
MA Sub
remote controller
ler
4 Outdoor unit OC
51 to 100 Assign sequential address OS1 OS2
range
4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals on the terminal block (TB5) on LOSSNAY (LC). (Non-po­larized two-wire)
Interlock setting between the indoor units and LOSS-
NAY units must be entered on the remote controller. (Re­fer to "IV [3] Interlock Settings via the MA Remote Controller" or the installation manual for the MA remote controller for the setting method.)
5) Switch setting Address setting is required as follows.
Setting method Notes
To perform a group opera­dress to the main unit in the group.
tion of indoor units that
have different functions,
designate the indoor unit
starting with the address of the main unit in the same group +1. (Main unit ad-
in the group with the great-
est number of functions as
the main unit.
dress +1, main unit ad­dress +2, main unit address +3, etc.)
None of these addresses unique address to each of these units after assigning
may overlap any of the in-
door unit addresses. an address to all indoor units.
-Main
Settings to be made ac­cording to the remote con­troller function selection
To set the address to 100, to the outdoor units in the same refrigerant circuit.
set the rotary switches to
50. The outdoor units are auto­matically designated as OC, OS1, and OS2.(Note)
Factory
setting
00
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 30 -
GBHWE08040
[ II Restrictions ]
3. Group operation of units in a system with multiple outdoor units (1) Sample control wiring
L11
Leave the male connector on CN41 as it is.
SW2-1 OFF
OS2
53
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
Leave the male connector on CN41 as it is.
SW2-1 OFF
OS1
52
TB3
Not connect
TB7
S
S
CN41 CN40 Replace
SW2-1 OFF
Not connect
TB3
TB7
Group
OC
51
S
Connect
IC
01
15
TB5STB
1 2
M1M2 M1 M2 M1 M2 M1 M2
A B
Interlock operation with
L12
Group
IC
03
15
TB5STB
1 2
m2
A B
the ventilation unit
Group
IC
06
TB5STB
15
1 2
A B
TB5
LC
07
S
L31
Leave the male connector on CN41 as it is.
SW2-1 OFF
OS2
56
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
S
Not connect
L21
Leave the male connector on CN41 as it is.
SW2-1 OFF
55
TB3
TB7
OS1
Leave the male connector on CN41 as it is.
SW2-1 OFF
OC
54
Not connect
TB5
M1M2
TB3
TB7
S
Not connect
S
(2) Cautions
1) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be performed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for transmission line for centralized control (TB7) on only one of the outdoor units.
6) A transmission booster is required in a system to which more than 32 indoor units (26 units if one or more indoor units of the 72 model or above is connected) are con­nected.
MA
m3
L22
IC
15
TB
S
1 2
Group
MA
IC
0402
15
TB5STB
1 2 1 2
A B
MA
MA
IC
05
TB5 TB15
S
M1M2M1M2
(3) Maximum allowable length
1) Indoor/outdoor transmission line
2
Maximum distance (1.25mm
[AWG16] or larger) L11+L12 200m [656ft] L21+L22 200m [656ft]
2) Transmission line for centralized control Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger)
L12+L31+L22 500m [1640ft] L11+L31+L21 500m [1640ft]
3) MA remote controller wiring Same as [5] 1.
HWE08040 GB
31- 31 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Same as [5] 1.
Only use shielded cables.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control Daisy-chain terminals M1 and M2 on the terminal block
3) MA remote controller wiring
for transmission line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the OC, OS1, and OS2 in the same refrigerant circuit If a power supply unit is not connected to the transmis­sion line for centralized control, replace the power jump­er connector on the control board from CN41 to CN40 on only one of the outdoor units.
The outdoor units in the same refrigerant circuit are au­tomatically designated as OC, OS1, and OS2 in the or-
4) LOSSNAY connection
5) Switch setting
der of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
(5) Address setting method
Proce-
dures
1 Indoor
Unit or controller
Main unit IC 01 to 50 Assign the smallest ad-
unit
Address setting
range
dress to the main unit in the group.
Sub unit Assign sequential num-
bers starting with the ad­dress of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit ad­dress +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but
unique address to each of these units after assigning an address to all indoor units.
3MA
re­mote con­troller
Main remote controller
Sub remote controller
4 Outdoor unit OC
MA No
settings required.
MA Sub
remote controller
Settings to be made ac­cording to the remote con­troller function selection
51 to 100 Assign sequential address OS1 OS2
to the outdoor units in the same refrigerant circuit. The outdoor units are au­tomatically designated as OC, OS1, and OS2. (Note)
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on the outdoor units (OC, OS1, OS2) with the shield wire of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the out­door unit whose power jumper connector is mated with CN40.
Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 2.
Same as [5] 2.
Address setting is required as follows.
Setting method Notes
To perform a group
Factory
setting
00 operation of indoor units that have differ­ent functions, desig­nate the indoor unit in the group with the greatest number of functions as the main unit.
None of these ad-
00 dresses may overlap any of the indoor unit addresses.
-Main
To set the address to
00 100, set the rotary switches to 50.
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 32 -
GBHWE08040
[ II Restrictions ]
4. A system in which a system controller is connected to the transmission line for centralized control and which is pow­ered from an outdoor unit
(1) Sample control wiring
Interlock operation with
15
1 2
the ventilation unit
IC
03
TB5STB
1 2
LC
07
TB5
15
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS2
53
TB3
M1 M2 M1 M2 M1 M2
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS1
52
TB3
CN41 CN40 Replace
SW2-1 OFF ON
OC
51
TB3
L12L11
Group Group Group
IC
01
15
TB5STB
1 2
M1 M2 M1 M2 M1 M2 M1 M2
IC
02
TB5STB
L31
TB7
S
M1 M2 M1 M2 M1 M2
Not connect
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS2
56
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
S
Not connect
TB7
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS1
55
TB3
TB7
S
Not connect
Not connect
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
TB7
S
Connect
OC
54
TB3
TB7
S
Not connect
System controller
A B S
L32
TB5
Note1
A B
MA
L22L21
IC
15
TB
S
1 2
A B
MA
TB5STB
m2 m1
m3
Note1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). Note2 LM adapters require the power supply capacity of single-phase AC 208/230V.
A B
MA
IC
GroupGroup
0504
15
1 2
IC
06
TB5STB
15
1 2
A B
MA
A B
MA
LC
08
TB5
M1 M2 M1 M2 M1 M2 M1 M2
S
(2) Cautions
1) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be performed only on one of the outdoor units.
5) Short-circuit the shield terminal (S terminal) and the
(3) Maximum allowable length
1) Indoor/outdoor transmission line Same as [5] 3.
2) Transmission line for centralized control Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger) L32+L31+L12(L11) 500m [1640ft] L32+L22(L21) 500m [1640ft] L12(L11)+L31+L22(L21) 500m[1640ft]
3) MA remote controller wiring Same as [5] 1.
earth terminal ( ) on the terminal block for transmission line for centralized control (TB7) on the outdoor unit whose power jumper connector is mated with CN40.
6) A transmission booster is required in a system to which more than 32 indoor units (26 units if one or more indoor units of the 72 model or above is connected) are con­nected.
7) When a power supply unit is connected to the transmis­sion line for centralized control, leave the power jumper connector on CN41 as it is (factory setting).
HWE08040 GB
33- 33 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Same as [5] 1. Only use shielded cables.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control Daisy-chain terminals A and B on the system controller,
terminals M1 and M2 on the terminal block for transmis­sion line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the out­door units (OC, OS1, and OS2) in the same refrigerant circuit. If a power supply unit is not connected to the transmis­sion line for centralized control, replace the power jump­er connector on the control board from CN41 to CN40 on only one of the outdoor units. If a system controller is connected, set the central control switch (SW2-1) on the control board of all outdoor units to "ON."
The outdoor units in the same refrigerant circuit are au­tomatically designated as OC, OS1, and OS2 in the or­der of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Only use shielded cables.
(5) Address setting method
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on the outdoor units (OC, OS1, OS2) with the shield wire of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the out­door unit whose power jumper connector is mated with CN40.
3) MA remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-polarized 2-core cable)
Indoor units must be interlocked with the LOSSNAY unit
using the system controller. (Refer to the operation man­ual for the system controller for the setting method.) In­terlock setting from the remote controller is required if the ON/OFF remote controller alone or the LM adapter alone is connected.
5) Switch setting Address setting is required as follows.
Proce-
dures
Unit or controller
Address
setting
range
Setting method Notes
1 Indoor unit Main unit IC 01 to 50 Assign the smallest ad-
dress to the main unit in the group.
Sub unit Assign sequential num-
bers starting with the ad­dress of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit ad­dress +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but
unique address to each of these units after assign­ing an address to all in­door units.
3MA
remote con­troller
Main remote control-
MA No
settings re­quired.
- Enter the same indoor
ler
Sub remote control­ler
4 Outdoor unit OC
MA Sub
remote con­troller
51 to 100 Assign sequential ad­OS1 OS2
Settings to be made ac­cording to the remote controller function selec­tion
dress to the outdoor units in the same refrigerant circuit. The outdoor units are au­tomatically designated as OC, OS1, and OS2.(Note)
To perform a group oper­ation of indoor units that have different functions, designate the indoor unit in the group with the greatest number of func­tions as the main unit.
None of these addresses may overlap any of the in­door unit addresses.
unit group settings on the system controller as the ones that were entered on the MA remote con­troller.
To set the address to 100, set the rotary switch­es to 50.
Factory
setting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 34 -
GBHWE08040
[ II Restrictions ]
5. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except LM adapter)
(1) Sample control wiring
Interlock operation with
15
1 2
the ventilation unit
IC
03
TB5STB
15
1 2
TB5
LC
07
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS2
53
TB3
M1 M2 M1 M2 M1 M2
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS1
52
TB3
CN41 CN40 Replace
SW2-1 OFF ON
51
TB3
L12L11
OC
Group Group Group
IC
01
15
TB5STB
M1 M2 M1 M2 M1 M2 M1 M2
1 2
IC
02
TB5STB
L31
TB7
S
M1 M2 M1 M2 M1 M2
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS2
Not connect
56
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
S
Not connect
TB7
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS1
55
TB3
TB7
S
Not connect
S
Not connect
TB7
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OC
54
TB3
TB7
S
Not connect
Connect
L25
System controller
TB5
A B S
A B
MA
L22L21
IC
m2 m1
m3
TB5STB
M1 M2 M1 M2
15
TB
1 2
S
A B
MA
Note1
A B
MA
IC
GroupGroup
0504
15
1 2
M1 M2
IC
06
TB5STB
15
1 2
A B
MA
A B
MA
TB5
M1 M2
LC
08
S
Note1 LM adapters cannot be connected to the indoor-outdoor transmission line.
(2) Cautions
1) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be performed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for transmission line for centralized control (TB7) on only one of the outdoor units.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
2
Maximum distance (1.25mm
[AWG16] or larger) L11+L12 200m [656ft] L21+L22 200m [656ft] L25 200m [656ft]
2) Transmission line for centralized control Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger) L25+L31+L12(L11) 500m [1640ft] L12(L11)+L31+L22(L21) 500m [1640ft]
3) MA remote controller wiring Same as [5] 1.
6) A maximum of 3 system controllers can be connected to the indoor-outdoor transmission line, with the exception that only one G(B)-50A may be connected.
7) When the total number of indoor units exceeds 26, it may not be possible to connect a system controller on the in­door-outdoor transmission line.
8) In a system to which more than 18 indoor units including one or more indoor units of 72 model or above are con­nected, there may be cases in which the system control­ler cannot be connected to the indoor-outdoor transmission line.
HWE08040 GB
35- 35 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Daisy-chain terminals M1 and M2 on the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor units (OC, OS1, OS2) (Note 1), terminals M1 and M2 on the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC), and the S terminal on the system controller. (Non-polarized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are au­tomatically designated as OC, OS1, and OS2 in the or­der of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor units (OC, OS1, OS2), the S terminal on the terminal block (TB5) on the indoor unit (IC), and the S terminal on the system controller with the shield wire of the shielded cable.
2) Transmission line for centralized control Daisy-chain terminals M1 and M2 on the terminal block
for transmission line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the OC, OS1, and OS2 in the same refrigerant circuit. If a power supply unit is not connected to the transmis­sion line for centralized control, replace the power jump­er connector on the control board from CN41 to CN40 on only one of the outdoor units.
(5) Address setting method
Set the central control switch (SW2-1) on the control board of all outdoor units to "ON."
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on the outdoor units (OC, OS1, OS2) with the shield wire of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the out­door unit whose power jumper connector is mated with CN40.
3) MA remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor units (IC) to the appropriate termi­nals on the terminal block for indoor-outdoor transmis­sion line (TB5) on LOSSNAY (LC). (Non-polarized two­wire)
Indoor units must be interlocked with the LOSSNAY unit
using the system controller. (Refer to the operation man­ual for the system controller for the setting method.) In­terlock setting from the remote controller is required if the ON/OFF remote controller alone is connected.
5) Switch setting Address setting is required as follows.
Proce-
dures
1 Indoor
Unit or controller
Main unit IC 01 to 50 Assign the smallest address
unit
Address set-
ting range
Setting method Notes
to the main unit in the group.
Sub unit Assign sequential numbers
starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but
unique address to each of these units after assigning an address to all indoor units.
3MA
remote control­ler
4 Outdoor unit OC
Main remote controller
Sub remote controller
MA No
settings re­quired.
MA Sub
remote con­troller
Settings to be made accord­ing to the remote controller function selection
51 to 100 Assign sequential address to OS1 OS2
the outdoor units in the same refrigerant circuit.
- Enter the same indoor unit
The outdoor units are auto­matically designated as OC, OS1, and OS2. (Note)
To perform a group opera­tion of indoor units that have different functions, desig­nate the indoor unit in the group with the greatest number of functions as the main unit.
None of these addresses may overlap any of the in­door unit addresses.
group settings on the sys­tem controller as the ones that were entered on the MA remote controller.
To set the address to 100, set the rotary switches to 50.
Factory
setting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 36 -
GBHWE08040
[ II Restrictions ]
[6] An Example of a System to which an M-NET Remote Controller is connected
(1) Sample control wiring
Interlock operation with
1 2
15
the ventilation unit
GroupGroupGroup
IC
03
TB5STB
15
1 2
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS2
53
TB3
M1 M2 M1 M2 M1 M2
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS1
52
TB3
CN41 CN40 Replace
SW2-1 OFF ON
OC
51
TB3
L12L11
IC
01
15
TB5STB
M1 M2 M1 M2 M1 M2 M1 M2
1 2
IC
02
TB5STB
TB5
LC
07
S
TB7
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OC
54
TB3
TB7
S
Not connect
System controller
Connect
A B S
m1
A B
101
RC
Group
TB5
m3
A B
A B
154
L32
104
RC
RC
Note1
A B
102
RC
L22L21
IC
IC
Group
A B
103
RC
0504
15
TB5STB
15
TB
S
1 2
m2
Note1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). Note2 LM adapters require the power supply capacity of single-phase AC 208/230V.
1 2
TB5STB
A B
106
RC
IC
06
15
1 2
LC
08
TB5
M1 M2 M1 M2 M1 M2 M1 M2
S
Not connect
Not connect
TB7
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS1
55
TB3
TB7
S
Not connect
Not connect
TB7
S
M1 M2 M1 M2 M1 M2
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
L31
OS2
56
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
S
(2) Cautions
1) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
2) No more than 3 M-NET remote controllers can be con­nected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replace the power jumper connector of the control board from CN41 to CN40 on only one of the outdoor units.
5) Provide an electrical path to ground for the S terminal on the terminal block for centralized control on only one of the outdoor units.
6) A transmission booster must be connected to a system in which the total number of connected indoor units ex­ceeds 20.
7) A transmission booster is required in a system to which more than 16 indoor including one or more indoor units
(3) Maximum allowable length
1) Indoor/outdoor transmission line Same as [5] 3.
2) Transmission line for centralized control Same as [5] 4.
3) M-NET remote controller wiring Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16]) m1 10m [32ft] m2+m3 10m [32ft] If the standard-supplied cable must be extended, use a cable with a diameter of 1.25mm
2
[AWG16]. The section of the cable that exceeds 10m [32ft] must be included in the maximum indoor-outdoor transmission line distance described in (1). When connected to the terminal block on the Simple re­mote controller, use cables that meet the following cable size specifications: 0.75 - 1.25 mm
2
[AWG18-14].
of the 72 model or above are connected.
8) When a power supply unit is connected to the transmis­sion line for centralized control, leave the power jumper connector on CN41 as it is (factory setting).
HWE08040 GB
37- 37 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Same as [5] 3.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3) M-NET remote controller wiring M-NET remote controller is connectable anywhere on
the indoor-outdoor transmission line.
(5) Address setting method
Proce-
dures
1 Indoor
Unit or controller
Main unit IC 01 to 50 Assign the smallest ad-
unit
Sub unit Assign sequential num-
2 LOSSNAY LC 01 to 50 Assign an arbitrary but
3M-NET
remote controller
Main remote controller
Sub
RC 101 to 150 Add 100 to the main unit
RC 151 to 200 Add 150 to the main unit remote controller
4 Outdoor unit OC
51 to 100 Assign sequential ad­OS1 OS2
Address setting
range
When 2 remote controllers are connected to the sys­tem
Refer to the section on Switch Setting.
Performing a group operation (including the group operation of units in different refrigerant circuits).
Refer to the section on Switch Setting.
4) LOSSNAY connection Same as [5] 4.
5) Switch setting Address setting is required as follows.
Setting method Notes
To perform a group dress to the main unit in the group.
operation of indoor
units that have differ-
ent functions, desig-
bers starting with the ad­dress of the main unit in the same group +1. (Main unit address +1, main unit address +2,
nate the indoor unit in
the group with the
greatest number of
functions as the main
unit.
main unit address +3, etc.)
None of these ad­unique address to each of these units after as­signing an address to all
dresses may overlap
any of the indoor unit
addresses. indoor units.
It is not necessary to
address in the group
set the 100s digit.
To set the address
to 200, set the rota-
address in the group
ry switches to 00.
To set the address to dress to the outdoor units in the same refrig-
100, set the rotary
switches to 50. erant circuit. The out­door units are automatically designat­ed as OC, OS1, and OS2. (Note)
Factory
setting
00
00
101
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 38 -
GBHWE08040
[ II Restrictions ]
[7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected
(1) Sample control wiring
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
TB3
M1 M2 M1 M2 M1 M2
L11 L12
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
TB3
CN41 CN40 Replace
SW2-1 OFF ON
OCOS1OS2
515253
TB3
Group Group
IC
01
TB5 TB
M1 M2
S
15
1 2
TB5 TB
M1 M2
IC
02
15
1 2
S
TB5 TB
M1 M2
IC
06
15
1 2
S
Not connect
Not connect
TB7
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OC
54
TB3
TB7
S
S
Not connect
System controller
A B S
TB7
M1 M2 M1 M2 M1 M2
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
L31
OS2
56
TB3
M1 M2 M1 M2 M1 M2
TB7
S
M1 M2 M1 M2 M1 M2
TB7
Not connect
Not connect
S
L21 L22
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS1
55
TB3
TB7
S
(2) Cautions
1) Be sure to connect a system controller.
2) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote controller addresses that are smaller than those of the in­door units that are connected to the M-NET remote con­troller.
4) No more than 2 M-NET remote controllers can be con­nected to a group of indoor units.
5) No more than 2 MA remote controllers can be connected to a group of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
7) Replace the power jumper connector of the control board from CN41 to CN40 on only one of the outdoor units.
8) Provide an electrical path to ground for the S terminal on the terminal block for centralized control on only one of the outdoor units.
9) A transmission booster must be connected to a system in which the total number of connected indoor units ex­ceeds 20.
10) A transmission booster is required in a system to which more than 16 indoor including one or more indoor units of the 72 model or above are connected.
11) When a power supply unit is connected to the transmis­sion line for centralized control, leave the power jumper connector on CN41 as it is (factory setting).
Connect
L32
Note1
TB5
M1 M2
A B
MA
IC
GroupGroup
IC
0403
15
TB
S
1 2
A B
MA
TB5 TB
M1 M2
S
1 2
A B
104
RC
Note1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
Note2 LM adapters require the power supply capacity of single-phase AC 208/230V.
A B
106
RC
IC
05
15
TB5 TB
M1 M2
S
15
1 2
(3) Maximum allowable length
1) Indoor/outdoor transmission line Same as [5] 3.
2) Transmission line for centralized control Same as [5] 4.
3) MA remote controller wiring Same as [5] 1.
4) M-NET remote controller wiring Same as [5] 1.
HWE08040 GB
39- 39 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Same as [5] 3.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3) MA remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
(5) Address setting method
Proce-
dures
1Opera-
tion with the MA re-
Unit or controller
In-
Main unit IC 01 to 50 door unit
Sub unit
mote control­ler
MA re­mote con­troller
Main re-
mote con-
troller
Sub
remote
MA No
MA Sub
controller
2Opera-
tion with the
In­door unit
M-NET remote
Main unit IC 01 to 50 Assign the smallest ad-
Sub unit
control­ler
M­NET re­mote con­troller
Main re-
mote con-
troller
Sub
remote
controller
RC 101 to
RC 151 to
3 LOSSNAY LC 01 to 50
4 Outdoor unit OC
OS1 OS2
Address
setting
range
settings required.
remote controller
150
200
51 to 100
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) M-NET remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
5) LOSSNAY connection Same as [5] 4.
6) Switch setting Address setting is required as follows.
Setting method Notes
Assign the smallest address to the main unit in the group.
Assign sequential num­bers starting with the ad­dress of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit ad­dress +3, etc.)
-
Settings to be made ac­cording to the remote controller function selec­tion
dress to the main unit in the group.
Assign sequential num­bers starting with the ad­dress of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit ad­dress +3, etc.)
Add 100 to the main unit address in the group.
Add 150 to the main unit
Assign an address smaller
than that of the indoor unit that is connected to the M-NET re­mote controller.
Enter the same indoor unit
group settings on the system controller as the ones that were entered on the MA re­mote controller.
To perform a group operation
of indoor units that have differ­ent functions, designate the indoor unit in the group with the greatest number of func­tions as the main unit.
Enter the indoor unit group set-
tings on the system controller (MELANS).
Assign an address larger than
those of the indoor units that are connected to the MA re­mote controller.
To perform a group operation
of indoor units that have differ­ent functions, designate the indoor unit in the group with the greatest number of func­tions as the main unit.
It is not necessary to set
the 100s digit.
To set the address to 200,
set the rotary switches to
00.
address in the group.
Assign an arbitrary but unique address to each of these units after assign­ing an address to all in­door units.
Assign sequential ad­dress to the outdoor units in the same refrigerantcir­cuit. The outdoor units are automatically desig­nated as OC, OS1, and OS2.(Note)
None of these addresses may overlap any of the in­door unit addresses.
To set the address to 100, set the rotary switches to 50.
Factory
setting
00
Main
00
101
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 40 -
GBHWE08040
[ II Restrictions ]
[8] Restrictions on Pipe Length
(1) End branching
P72 - P120 models
Outdoor unit
A
D
First branch (Branch joint)
B
Branch joint
(Outdoor unit above indoor unit)
(Outdoor unit below indoor unit)
' H
H
C
a
Indoor Indoor Indoor
1
L
d
Indoor Indoor Indoor
b
2
c
3
4
Operation Pipe sections
Length Total pipe length A+B+C+D
+a+b+c+d+e+f
Height difference
Total pipe length (L) from the outdoor unit to the farthest indoor unit
Total pipe length from the first branch to the far­thest indoor unit ( )
Between indoor and outdoor units
Outdoor unit above in­door unit
Outdoor unit below in-
A+B+C+c or
A+D+f
B+C+c or
D+f
H 50 [164] or less
H' 40 [131] or less
door unit
Between indoor units h 15 [49] or less
Branch header
cap
e
5
f
6
h
Allowable length of
pipes
1000 [3280] or less
165 [541] or less
(Equivalent length 190
[623] or less)
40 [131] or less
Unit: m [ft]
HWE08040 GB
- 41 -
[ II Restrictions ]
P144 - P360 models The figure shows a system with three outdoor units. (P264-P360 models)
Note1 Install the pipe that connects the branch pipe and the outdoor units in
the way that it has a downward inclination toward the branch pipe.
Provide a trap on the pipe (gas pipe only) within 2 m from the joint pipe if the total length of the pipe that connects the joint pipe and the outdoor unit exceeds 2 m.
h2
B DA
C
Second gas refrigerant distributor Second liquid refrigerant distributor
First liquid refrigerant distributor First gas refrigerant distributor
H
First branch
h1
Downward inclination
Upward inclination
L
To indoor unit
To indoor unit
(Note)
E F G I
a
Indoor Indoor Indoor Indoor
J K M
e
Indoor Indoor Indoor Indoor
5
c
b
d
E
3
21
g
f
6
4
i
7
8
Note : "Total sum of downstream unit model numbers" in the table is the sum of the model numbers of the units after point E in the figure.
Operation Pipe sections
2m [6ft]
2m [6ft] Max.
To indoor unit Joint pipe
Trap (gas pipe only)
To downstream units
Allowable length of
To indoor unit Joint pipe
pipes
Length Between outdoor units A+B+C+D 10 [32] or less
Total pipe length A+B+C+D+E+F+G+I+J
1000 [3280] or less
+K+M+a+b+c+d+e+f+g
+i
Total pipe length (L) from the outdoor unit to the farthest indoor unit
Total pipe length from the first branch to the far-
A(B)+C+E+J+K+M+i
G+I+J+i 40 [131] or less
165 [541] or less
(Equivalent length 190
[623] or less)
thest indoor unit ( )
Height difference
Between indoor and outdoor units H 50 [164] or less
(40 [131] or below if
outdoor unit is below in-
door unit)
Between indoor units h1 15 [49] or less
Between outdoor units h2 0.1[0.3] or less
Unit: m [ft]
HWE08040 GB
- 42 -
[ II Restrictions ]
1. Refrigerant pipe size (1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdoor unit pipe size)
Outdoor unit set name
Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch]
(total capacity)
72 model ø9.52 [3/8"] ø19.05 [3/4"]
96 model ø9.52 [3/8"]
120 model ø9.52 [3/8"]
*1
*2
ø22.2 [7/8"]
ø22.2 [7/8"]
144 model ø12.7 [1/2"] ø28.58 [1-1/8"]
168 model ø15.88 [5/8"] ø28.58 [1-1/8"]
192 model ø15.88 [5/8"] ø28.58 [1-1/8"]
216 model ø15.88 [5/8"] ø28.58 [1-1/8"]
240 model ø15.88 [5/8"] ø28.58 [1-1/8"]
264 - 312 model ø19.05 [3/4"] ø34.93 [1-3/8"]
336 - 360 model ø19.05 [3/4"] ø41.28 [1-5/8"]
*1. Use ø12.7 [1/2"] pipes if the piping length exceeds 90 m [295 ft].
*2. Use ø12.7 [1/2"] pipes if the piping length exceeds 40 m [131 ft].
(2) Size of the refrigerant pipe between the first branch and the indoor unit (indoor unit pipe size)
model Pipe diameter (mm) [inch]
06 - 15 models Liquid pipe ø6.35 [1/4"]
Gas pipe ø12.7 [1/2"]
18 - 54 models Liquid pipe ø9.52 [3/8"]
Gas pipe ø15.88 [5/8"]
72 model Liquid pipe ø9.52 [3/8"]
Gas pipe ø19.05 [3/4"]
96 model Liquid pipe ø9.52 [3/8"]
Gas pipe ø22.2 [7/8"]
(3) Size of the refrigerant pipe between the branches for connection to indoor units
Total capacity of the
Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch]
downstream units
- 54 ø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]
P72 - P108 ø9.52 [3/8"] ø22.2 [7/8"]
P109 - P144 ø12.7 [1/2"] ø28.58 [1-1/8"]
P145 - P240 ø15.88 [5/8"] ø28.58 [1-1/8"]
P241 - P308 ø19.05 [3/4"] ø34.93 [1-3/8"]
P309 - ø19.05 [3/4"] ø41.28 [1-5/8"]
HWE08040 GB
- 43 -
[ II Restrictions ]
(4) Size of the refrigerant pipe between the first distributor and the second distributor
Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch]
ø19.05 [3/4"] ø34.93 [1-3/8"]
(5) Size of the refrigerant pipe between the first distributor or the second distributor and outdoor units
Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch]
72 model ø9.52 [3/8"] ø22.2 [7/8"]
96 model
120 model ø12.7 [1/2"]
* Only applicable to the 120 model and below
HWE08040 GB
- 44 -
III
Outdoor Unit Components
[1] Outdoor Unit Components and Refrigerant Circuit .......................................................... 47
[2] Control Box of the Outdoor Unit....................................................................................... 49
[3] Outdoor Unit Circuit Board............................................................................................... 52
HWE08040 GB
- 45 -
- 46 -
[ III Outdoor Unit Components ]
III Outdoor Unit Components
[1] Outdoor Unit Components and Refrigerant Circuit
1. PUHY-P72, P96, P120THMU-A PUHY-P72, P96, P120YHMU-A
(1) Front view of a outdoor unit
Fan guard
Fan
Fin guard
Heat exchanger
Front panel
Control Box
HWE08040 GB
- 47 -
[ III Outdoor Unit Components ]
2. PUHY-P72, P96THMU-A PUHY-P72, P96YHMU-A
(1) Refrigerant circuit
Check valve
4-way valve(21S4b)
4-way valve(21S4a)
Subcool coil
Linear Expansion Valve(LEV1)
Solenoid valve(SV5b)
Linear Expansion Valve(LEV2a,2b)
Liquid side valve
Low pressure sensor(63LS)
Gas side valve
Solenoid valve (SV1a)
Solenoid valve (SV9)
High pressure sensor(63HS1)
High-pressure switch(63H1)
Transformer Box (YHMU-A only)
Accumulator
Low pressure check joint
High pressure check joint
Compressor cover
Compressor
Oil separator
3. PUHY- P120THMU-A PUHY- P120YHMU-A
(1) Refrigerant circuit
4-way valve(21S4c)
High pressure check joint
Low pressure check joint
Solenoid valve(SV5c)
Linear Expansion Valve
(LEV2a,2b)
Linear Expansion
Valve(LEV1)
Solenoid valve(SV5b)
Liquid side valve
Subcool coil
4-way valve(21S4a)
4-way valve(21S4b)
Solenoid valve (SV9)
Gas side valve
Low pressure sensor(63LS)
Check valve
Solenoid valve (SV1a)
Accumulator
Transformer Box (YHMU-A only)
High pressure sensor(63HS1)
High-pressure switch(63H1)
Compressor cover
Compressor
Oil separator
HWE08040 GB
- 48 -
[ III Outdoor Unit Components ]
[2] Control Box of the Outdoor Unit
<HIGH VOLTAGE WARNING>
Control box houses high-voltage parts. When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
1. PUHY-P72, P96THMU-A
DC reactor (DCL)
Electromagnetic relay(72C)
Rush current protection resistor (R1) Note.2
Noise filter
Note.2
Terminal block for
power supply
(TB1)
Note.1
Ground terminal
Fan board
INV board
Smoothing capacitor(C1)
Control board
M-NET board
Terminal block for transmission line (TB3, TB7)
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the water­proof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter­minals to remove them.
HWE08040 GB
- 49 -
[ III Outdoor Unit Components ]
2. PUHY-P120THMU-A
DC reactor (DCL)
Electromagnetic relay
(72C)
Diode stack
Noise filter
Current sensor
(ACCT3)
Current sensor
(DCCT1)
Terminal block for
power supply
(TB1)
Ground terminal
Smoothing capacitor(C1)
3. PUHY-P72, P96, P120YHMU-A
Note.2
Note.1
Fan board
Current sensor (ACCT2)
INV board Control board
IPM
Current sensor (ACCT1)
Terminal block for transmission line (TB3, TB7)
M-NET board
Electromagnetic relay(72C)
DC reactor (DCL)
Noise filter
Terminal block for power supply
(TB1)
Fuse(F4)
Capacitor(C100)
Rush current protection resistor (R1,R5) Note.2
Fan board
Control board
M-NET board
Fuse(F5)
Ground terminal
Note.1
INV board
Terminal block for transmission line (TB3, TB7)
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the water­proof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter­minals to remove them.
HWE08040 GB
- 50 -
[ III Outdoor Unit Components ]
4. Transformer Box (PUHY-P72, P96, P120YHMU-A)
Transformer (T03)
Transformer (T02)
HWE08040 GB
- 51 -
[ III Outdoor Unit Components ]
[3] Outdoor Unit Circuit Board
1. Outdoor unit control board
CNAC2 L1 L2
CN505 72C driving output (THMU)
CN51
Output 12VDC Compressor ON/OFF output
Error output
Actuator driving output
CN72 72C driving output (YHMU)
CNDC Bus voltage input P N
CN2
Serial communication signal input
INV board
GND Output 17VDC
CN801 Pressure switch connection
CN332 Output 18VDC GND (Fan board)
CN4 GND Serial communication signal output
LEV driving output
LED1 Service LED
SWU1,2 Address switch
SW1-5
switch
Dip
Sensor input
LED3 Lit when powered
LED2 Lit during normal CPU operation
HWE08040 GB
CNAC L1 L2
LED3 Lit when powered
F01 Fuse 250V AC/3.15A
External signal input (contact input)
CN102
Power supply input for centralized control system (30VDC) Indoor/outdoor transmission line input/output (30VDC)
- 52 -
CN41 Power supply for
CN40
centralized control OFF Power supply for centralized control ON
CNVCC2 Output 12VDC Output 5VDC
CNIT Output 12VDC GND Output 5VDC Power supply detection input
Power supply ON/OFF signal output CNS2 Transmission line input/output for centralized control system (30VDC)
GND
[ III Outdoor Unit Components ]
2. M-NET board
(THMU only) F01 250V
3.15A
Grounding
CN03(THMU only) Bus voltage input P N
CN04 Bus voltage input (YHMU only) Bus voltage output (THMU only) P N
CN102
Power supply output for centralized control system (30VDC) Indoor/outdoor transmission line input/output (30VDC)
Grounding
Grounding
TB3 Indoor/outdoor transmission block
Ground terminal for transmission line
CNS2 Transmission line input/output for centralized control system (30VDC)
TB7 Terminal block for transmission line for centralized control
CNIT Input 12VDC GND Input 5VDC Power supply detection output Power supply ON/OFF signal input
LED1 Power supply for indoor transmission line
TP1,2 Check pins for indoor/outdoor transmission line
HWE08040 GB
- 53 -
[ III Outdoor Unit Components ]
3. INV board (1) PUHY-P72, P96THMU-A
SC-P1 Rectifier diode output (P)
C30,31,32 Smoothing capacitor
RSH1,2 Overcurrent detection resistor
CN6 Open: No-load operation setting Short-circuited: Normal setting
IGBT (Rear)
CN5V GND Output 5VDC
LED1 Lit: Inverter in normal operation Blink: Inverter error
CN4 GND
Serial communication signal output
CNDC Bus voltage output P N
(INV Boar)
CN2
S
erial communication signal output
SC-P2 Bus voltage Input(
TB-P(Note) Bus voltage output(P
P)
)
TB-N(Note) Bus voltage output
(N)
SC-T Input(L3)
CT3 Current sensor(
L3)
SC-S Input(L2)
SC-R Input(L1)
CT12 Current sensor
CT22 Current sensor
(U)
SC-U Inverter output(U)
GND Input 17VDC
SC-V Inverter output(V)
SC-W Inverter output(W)
(W)
Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter­minals to remove them.
HWE08040 GB
- 54 -
[ III Outdoor Unit Components ]
(2) PUHY-P120THMU-A
CNCT2 Current (AC) sensor input ACCT1 ACCT2
CNCT Current (DC) sensor input
FT-N(Note) BUS voltage output
SC-P1 Bus voltage input/output(P)
(N)
IPM-P BUS voltage output (IPM input)
CNTH Thermistor input (THHS)
CNTYP Function setting input (Z26)
(P)
IPM-N BUS voltage input/output(N) (IPM input)
CNCT3 Current (AC) sensor input (ACCT3)
LED1 Inverter in normal operation
CNIPM
IPM driving power supply output and signal output
IPM error signal input (IPM output)
CNDC1 BUS voltage output P N
LED2 Inverter error
LED4 Lit during normal CPU operation
SW1 ON: No-load operation setting OFF: Normal setting : Fixed to OFF
CN5V GND Output 5VDC
CN2 Serial communication
signal output GND Output 17VDC
CN4 GND (Fan board) Serial communication
signal input
LED3 Lit while charging
CNFG Functional earth
F02 Fuse 250VAC 3.15A
CNDC2 BUS voltage input P N
CNDC3 BUS voltage output P N
Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter­minals to remove them.
HWE08040 GB
- 55 -
[ III Outdoor Unit Components ]
(3) PUHY-P72, P96, P120YHMU-A
Bus voltage check terminal (P) Note
IGBT (Rear)
CN1 Bus voltage output N
P Bus voltage check terminal (N) Note 1
SC-L1 Input(L1)
SC-L2 Input(L2)
SC-P1
SC-P2 Bus voltage Input(P)
Rectifier diode output (P)
CN6 Open: No-load operation setting
LED1 Lit: Inverter in normal operation Blink: Inverter error
Short-circuited: Normal setting
CN5V GND Output 5VDC
RSH1 Overcurrent detection resistor
CN4 GND
CNTYP Inverter board type
SC-V Inverter output(V)
SC-W Inverter output(W)
SC-U Inverter output(U)
(INV Board) Serial communication signal output
CN2
S
erial communication signal output GND Input 17VDC
SC-L3 Input(L3)
CT22 Current sensor(W)
CT3 Current sensor(L3)
CT12 Current sensor(U)
C30 C37 Smoothing capacitor
1) Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
HWE08040 GB
- 56 -
[ III Outdoor Unit Components ]
4. Fan board
(1) PUHY-P72, P96, P120THMU-A
CNVDC Bus voltage input
NP
F01 Fuse 250VAC 15A
LED3 Lit during normal CPU operation
CN18V
Input 18VDC GND
CN4
GNDSerial communication signal output GND(Control boardSerial communication signal output
CN22
GND(INV boardInput 5VDC
Serial communication signal input
GND(INV boardInput 17VDC
CN21
Serial communication signal output
GND(INV boardInput 17VDC
THBOX Thermistor (Control box internal temperature detection)
LED1 Inverter in normal operation
LED2 Inverter error
R630 Overcurrent detection resistor
HWE08040 GB
CNINV Inverter output
WVU
DIP IPM(Rear)
- 57 -
[ III Outdoor Unit Components ]
(2) PUHY-P72, P96, P120YHMU-A
CNVDC Bus voltage input N P
CNINV Inverter output W V U
R630,R631 Overcurrent detection resistor
DIP IPM Rear
CN18V Input 18VDC GND
LED3 Lit during normal CPU operation
CN4 GND Serial communication signal output
CN5
GND(Control board)
Serial communication signal output
CN21 Serial communication signal output GND(INV board) Input 17VDC
CN22 GND(INV board) Input 5VDC Serial communication signal input GND(INV board) Output 17VDC
THBOX Thermistor (Control box internal temperature detection)
LED1 Inverter in normal operation
LED2 Inverter error
HWE08040 GB
- 58 -
[ III Outdoor Unit Components ]
5. Noise Filter
(1) PUHY-P72, P96THMU-A
F2 Fuse 250VAC 6.3A
F1 Fuse 250VAC 6.3A
Grounding
TB21 Input/output(L1)
CN02 Output
L1L2
TB22 Input/output(L2)
TB23 Input/output(L3)
CN01 Input
L3L2L1
HWE08040 GB
- 59 -
[ III Outdoor Unit Components ]
(2) PUHY-P120THMU-A
R1,2 Rush current protection resistor
F3 Fuse 250VAC 6.3A
Grounding
CN02 Output
L1L2
F1 Fuse 250VAC 6.3A
F2 Fuse 250VAC 6.3A
TB42 Bus voltage output(N)
TB31 Bus voltage output(P)
CN03 72C drive input
Electromagnetic relay
72C
Diode stack rectified voltage input (Diode stack output)
Output
Diode stack input
TB23 Input
L3)
TB22 Input
L2
TB21 Input
L1
CN01 Input
L3L2L1
HWE08040 GB
- 60 -
[ III Outdoor Unit Components ]
(3) PUHY-P72, P96, P120YHMU-A
CN4 Output (Rectified L2-L3 current) P N
CN2 Surge absorber circuit Surge absorber circuit Short circuit Short circuit
F1,F2,F3,F4 Fuse 250VAC 6.3A
Grounding
CN1A Input L1
CN5 Output (Rectified L2-L3 current) P N
CN6 Input L2 L3
Grounding
CN1B Input L3 L2
HWE08040 GB
TB21 Input/output(L1)
TB22 Input/output(L2)
- 61 -
TB23 Input/output(L3)
[ III Outdoor Unit Components ]
HWE08040 GB
- 62 -
IV
Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers ................................... 65
[2] Group Settings and Interlock Settings via the ME Remote Controller .............................66
[3] Interlock Settings via the MA Remote Controller ............................................................. 70
[4] Using the built-in Temperature Sensor on the Remote Controller ...................................71
HWE08040 GB
- 63 -
- 64 -
[ IV Remote Controller ]
IV Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers
There are two types of remote controllers: M-NET (ME) remote controller, which is connected on the indoor-outdoor transmission line, and MA remote controller, which is connected to each indoor unit.
1. Comparison of functions and specifications between MA and ME remote controllers
Functions/specifications MA remote controller
*1*2
M-NET (ME) remote controller
*2*3
Remote controller address settings Not required Required
Indoor/outdoor unit address set­tings
Not required (required only by a system with one outdoor unit)
*4
Wiring method Non-polarized 2-core cable
Required
Non-polarized 2-core cable
To perform a group operation, daisy-
chain the indoor units using non-polar­ized 2-core cables.
Remote controller connection Connectable to any indoor unit in the
group
Interlock with the ventilation unit Each indoor unit can individually be in-
terlocked with a ventilation unit. (Set up via remote controller in the group.)
Changes to be made upon group­ing change
MA remote controller wiring between in­door units requires rewiring.
Connectable anywhere on the indoor-out­door transmission line
Each indoor unit can individually be inter­locked with a ventilation unit. (Set up via remote controller.)
Either the indoor unit address and remote controller address must both be changed, or the registration information must be changed via MELANS.
*1. MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and wire-
less remote controller.
*2. Either the MA remote controller or the M-NET remote controller can be connected when a group operation of units in a
system with multiple outdoor units is conducted or when a system controller is connected.
*3. M-NET remote controller refers to ME remote controller and ME simple remote controller.
*4. Depending on the system configuration, some systems with one outdoor unit may require address settings.
2. Remote controller selection criteria
MA remote controller and M-NET remote controller have different functions and characteristics. Choose the one that better suits the requirements of a given system. Use the following criteria as a reference.
MA remote controller
*1*2
There is little likelihood of system expansion and group-
ing changes.
Grouping (floor plan) has been set at the time of instal-
lation.
M-NET (ME) remote controller
There is a likelihood of centralized installation of remote
controllers, system expansion, and grouping changes.
Grouping (floor plan) has not been set at the time of in-
stallation.
*1*2
To connect the remote controller directly to the OA pro-
cessing unit.
*1. M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
*2. A system controller must be connected to a system to which both MA remote controller and M-NET remote controller are
connected.
<System with MA remote controller> <System with M-NET remote controllers>
Outdoor unit
M-NET transmission line (indoor/outdoor transmission line)
Outdoor unit
M-NET transmission line (indoor/outdoor transmission line)
groupgroup
MA remote controller
HWE08040 GB
Indoor unit
M-NET remote controller
- 65 -
groupgroup
Indoor unit
[ IV Remote Controller ]
[2] Group Settings and Interlock Settings via the ME Remote Controller
1. Group settings/interlock settings
Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the indoor/outdoor unit address.
(A) Group settings...........Registration of the indoor units to be controlled with the remote controller,
and search and deletion of registered information.
(B) Interlock settings........Registration of LOSSNAY units to be interlocked with the indoor units,
and search and deletion of registered information
[Operation Procedures]
(1) Address settings
Register the indoor unit to be controlled with the remote controller.
1
Bring up either the blinking display of HO by turning on the unit or the
normal display by pressing the ON/OFF button.
The display window must look like one of the two figures below to proceed to the next step.
C
G
E
STAND BY DEFROST
PAR-F27MEA
CENTRALLY CONTROLLED
DAILY
AUTO OFF
CLOCK
REMAINDER
˚C
TEMP.
CLOCKON→OFF
TIMER SET
ON OFF
1Hr.
NOT AVAILABLE
˚C
FILTER
CHECK MODE
TEST RUN LIMIT TEMP.
ON/OFF
CHECK TEST
FILTER
F
?
A
D
[Blinking display of HO ]
Bring up the Group Setting window.
2
-Press and hold buttons [FILTER] and [ ] simultaneously for 2 seconds to bring up the display as
A
B
[Normal display]
shown below.
Indoor unit address display window
3
Select the unit address.
-
Select the address of the indoor unit to be registered by pressing
button
through the addresses.
4
Register the indoor unit whose address appears on the
C
[TEMP. ( ) or ( )] to advance or go back
display.
- Press button [TEST] to register the indoor unit address
D
whose address appears on the display.
- If registration is successfully completed, unit type will appear
on the display as shown in the figure below.
- If the selected address does not have a corresponding indoor
unit, an error message will appear on the display. Check the address, and try again.
<Successful completion of registration>
Unit type (Indoor unit in this case)
<Deletion error>
H
B
(B) Interlock Settings (A) Group Settings
6
Bring up the Interlock Setting window.
-Press button [ ] to bring up the following display.
G
Press again to go back to the Group Setting window as shown under step .
Indoor unit address display window
7
Bring up the address of the indoor unit and the address of the
2
Interlocked unit address display window
Both the indoor unit address and interlocked unit address will be displayed together.
To search for an address, go to section (2) Address Search.
LOSSNAY to be interlocked on the display.
- Select the address of the indoor unit to be registered by pressing button [TEMP. ( ) or ( )] to advance or go back through
C
the addresses.
- Select the address of the LOSSNAY unit to be interlocked by pressing button [TIMER SET ( ) or ( )] to advance or go back through the interlocked unit addresses.
8
Make the settings to interlock LOSSNAY units with indoor units.
- Press button [TEST] while both the indoor unit address and
H
D
the address of the LOSSNAY units to be interlocked are displayed to enter the interlock setting.
- Interlock setting can also be made by bringing up the LOSSNAY address in the indoor unit address display window and the indoor unit address in the interlocked unit address display window.
If registration is successfully
blinks to indicate a registration error. (Indicates that selected address does not have a corresponding unit.)
5
To register the addresses for multiple indoor units, repeat steps and above.
3
4
(Displayed alternately)
completed, the two displays as shown on the left will appear alternately. If the registration fails, will blink on the display. (Indicates that the selected address does not have a corresponding unit.)
To search for an address, go to section (2) Address Search.
NOTE : Interlock all the indoor units in the group with the LOSSNAY units; otherwise, the LOSSNAY units will not operate.
To next page.
HWE08040 GB
- 66 -
[ IV Remote Controller ]
(C) To return to the normal display When all the group settings and interlock settings are made, take the following step to go back to the normal display.
10
Press and hold buttons [FILTER] and [ ] simultaneously for 2 seconds to go back to the window as shown in step .
A
1
B
(2) Address search
To search for the address of indoor units that have been entered into the remote controller, follow steps and .
1
2
(A) To search group settings
11
Bring up the Group Setting window.
- Each pressing of button [ ] will bring up the address of a
E
registered indoor unit and its unit type on the display.
<Entry found>
Unit type (Indoor unit in this case)
<No entries found>
- When only one unit address is registered, the same address will remain on the display regardless of how many times the button is pressed.
- When the address of multiple units are registered (i.e. 011, 012, 013 ), they will be displayed one at a time in an ascending order with each pressing of button [ ] .
E
Repeat steps and in the previous page to interlock
9
all the indoor units in a group with the LOSSNAY unit.
To go back to the normal display, follow step .
7
8
To search for an address,
10
go to section (2) Address Search.
(B) Interlock setting search
After performing step , proceed as follows:
12
Bring up the address of the indoor unit to be searched on
6
the display.
- Select the address of the indoor unit to be searched by pressing
H
button [TIMER SET ( ) or ( )] to advance or go back through the interlocked addresses.
LOSSNAY can be searched in the same manner by bringing up the LOSSNAY address in the Interlocked unit address display window.
13
Bring up on the display the address of the LOSSNAY unit that was interlocked with the indoor unit in step .
- With each pressing of button [ ], the address of the
E
LOSSNAY and indoor unit that is interlocked with it will be displayed alternately.
Address of an interlocked LOSSNAY unit
(Displayed alternately)
12
14
To delete an address, go to section (3) Address Deletion.
Bring up the address of another registered unit on the display.
- After completing step , a subsequent pressing of button
E
[ ] will bring up the address of another registered
13
unit. (The display method is the same as the one in step .)
To go back to the normal display, follow step .
10
Address of another interlocked unit
(Displayed alternately)
To delete an address,
(3) Address deletion
go to section (3) Address Deletion .
The addresses of the indoor units that have been entered into the remote controller can be deleted by deleting the group settings. The interlock settings between units can be deleted by deleting the interlock settings. Follow the steps in section (2) Address Search to find the address to be deleted and perform deletion with the address being displayed in the display window. To delete an address, the address must first be bought up on the display.
15
Delete the registered indoor unit address or the interlock setting between units.
- Press button ? [CLOCK ON OFF] twice while either the indoor unit address or the address of the interlocked unit is displayed on the
F
display to delete the interlock setting.
13
HWE08040 GB
- 67 -
[ IV Remote Controller ]
(A) To delete group settings
(B) To delete interlock settings
<Successful completion of deletion>
will be displayed in the room temperature display window.
(Displayed alternately)
- If a transmission error occurs, the selected setting will not be deleted, and the display will appear as shown below. In this case, repeat the steps above.
<Deletion error>
will be displayed in the room temperature display window.
To go back to the normal display, follow step .
10
(4) Making (A) Group settings and (B) Interlock settings of a group from any arbitrary remote controller
(A) Group settings and (B) Interlock settings of a group can be made from any arbitrary remote controller. Refer to (B) Interlock Settings under section 1 Group Settings/Interlock Settings for operation procedures. Set the address as shown below.
(A) To make group settings Interlocked unit address display window...Remote controller address
Indoor unit address display window...........The address of the indoor unit to be controlled with the remote controller
(B) To make interlock settings Interlocked unit address display window...LOSSNAY address
Indoor unit address display window..........The address of the indoor unit to be interlocked with the LOSSNAY
If deletion is successfully completed, will appear in the unit type display window. If the deletion fails, will appear in the unit type display window. In this case, repeat the steps above.
- -
2. Remote controller function selection via the ME remote controller
In the remote controller function selection mode, the settings for four types of functions can be made or changed as necessary.
1) Skip-Auto-Mode setting The automatic operation mode that is supported by some simultaneous cooling/heating type units can be made unselectable via the ME remote controller.
2) Operation mode display selection mode (Display or non-display of COOL/HEAT during automatic operation mode) When the automatic operation mode is selected, the indoor unit will automatically perform a cooling or heating operation based on the room temperature. In this case, or will appear on the remote controller display. This setting can be changed so that only will appear on the display.
3) Room temperature display selection mode (Display or non-display of room temperature) Although the suction temperature is normally displayed on the remote controller, the setting can be changed so that it will not appear on the remote controller.
4) Narrowed preset temperature range mode The default temperature ranges are 19 C to 30 C in the cooling/dry mode and 17 C to 28 C in the heating mode and 19 C to 28 C in the auto mode.
By changing these ranges (raising the lower limit for the cooling/dry mode and lowering the upper limit for the heating mode), energy can be saved.
NOTE
When making the temperature range setting on the simultaneous cooling/heating type units that supports the automatic operation mode to save on energy consumption, enable the Skip-Auto-Mode setting to make the automatic operation mode unselectable. If the automatic operation mode is selected, the energy-saving function may not work properly.
When connected to the air conditioning units that do not support the automatic operation mode, the setting for the Skip-Auto-Mode, restricted preset temperature range mode (AUTO), and operation mode display selection mode are invalid. If an attempt is made to change the preset temperature range, “LIMIT TEMP.” appears on the display.
PAR-F27MEA
TEMP.
TIMER SET
CLOCKĺONĺOFF
ON/OFF
FILTER
CHECK TEST
Normal display
1 1
Remote controller function selection mode
Skip-Auto-Mode setting
Temperature range setting mode (AUTO)
Operation mode display selection mode (Display or non-display of the automatic mode)
5
Restricted preset temperature range mode (Cooling)
4
Restricted preset temperature range mode (Heating)
Room temperature display selection mode
[Function selection mode sequence on the remote controller]
*2
3
2
3
2
*2
3
2
3
2
3
2
3
*1 *1
2
[Normal display]
1
: Press and hold the [CHECK] and [ ] buttons simultaneously for two seconds.
2
: [SET TEMP.
3
: [SET TEMP.
2
3
*1 : Skip-Auto-Mode is enabled *2 : Skip-Auto-Mode is disabled
( ) ] ( ) ]
button button
HWE08040 GB
- 68 -
[ IV Remote Controller ]
[Operation Procedures]
1. Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display will appear as shown in the previous page (Normal display).
2. Press buttons [CHECK] and [ ] simultaneously for 2 seconds to go into the “Skip-Auto-Mode setting.” under the remote controller function selection mode. Press button [SET TEMP. ( )] or [SET TEMP. ( )] to go into the other four modes
1
2
3
under the remote controller function selection mode.
Skip-Auto-Mode setting (Making the automatic operation mode unselectable)
This setting is valid only when the controller is connected to the simultaneous cooling/heating type air conditioning units that support the automatic operation mode.
“ ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button switches
4
between “ON” and “OFF.”
[TIMER SET ( ) (( ))] button
When set to “ON,” the automatic operation mode is available for selection in the function selection mode. When set to “OFF,” the automatic operation mode is not available for selection in the function selection mode, and an automatic operation cannot be performed. (The automatic operation mode is skipped in the function selection mode sequence.)
Operation mode display selection mode (Changing the type of display that appears during the automatic mode operation)
When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.
will blink, and either
switch between “ON” and “OFF.”
“ON”or“
OFF” will light up.
Press button [TIMER SET ( ) or ( )] in this state to
4
[TIMER SET ( ) (( ))] button
When it is set to ON, will appear on the display during automatic operation mode. When it is set to OFF, only will appear on the display during automatic operation mode.
Restricted preset temperature range mode (The range of preset temperature can be changed.)
1) Temperature range setting for the cooling/dry mode
will light up in the display window, and the temperature range for the cooling/dry mode will appear on the display. [Lower limit temperature]: Appears in the preset temperature display window [Upper limit temperature: Appears in the time display window Switch between the Lower and Upper limit temperature setting by pressing the [CLOCK-ON-OFF] button. The selected temperature setting blinks.
[TIMER SET ( ) (( ))] button
[The left figure shows the display that appears when the current temperature range setting is between 19 C and 30 C in the Cool/Dry mode, and the lower limit temperature is selected to be set.]
Press button [TIMER SET ( ) or ( )] to set the lower limit temperature to the desired temperature.
4
[Settable range for the lower limit temperature] : 19 C 30 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 30 C 19 C (Settable up to the lower limit temperature that is shown on the display)
2) Temperature range setting for heating
“ ” and the settable temperature range for heating appear on the display. As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range.
5
[Settable range for the lower limit temperature] : 17 C 28 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 28 C 17 C (Settable up to the lower limit temperature that is shown on the display)
3) Temperature range setting for the automatic mode
When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.
“ ” and the temperature range for the automatic operation mode appear on the display. As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range.
5
[Settable range for the lower limit temperature] : 19 C 28 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 28 C 19 C (Settable up to the lower limit temperature that is shown on the display)
5
4
4
Room temperature display selection mode (Switching between the display or non-display of room temperature on the controller)
“ 88 C ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button
4
switches between “ON” and “OFF.”
˚C ˚C
[TIMER SET ( ) (( ))] button
When set to “ON,” room temperature always appears on the display during operation. When set to “OFF,” room temperature does not appear on the display during operation.
HWE08040 GB
- 69 -
[ IV Remote Controller ]
[3] Interlock Settings via the MA Remote Controller
1. LOSSNAY interlock setting (Make this setting only when necessary.)
Make this setting only when necessary.
Perform this operation to enter the interlock setting between the LOSSNAY and the indoor units to which the remote controller is connected, or to search and delete registered information.
In the following example, the address of the indoor unit is 05 and the address of the LOSSNAY unit is 30.
[Operation Procedures]
Press the [ON/OFF] button on the remote controller to bring the unit to a stop.
1
The display window on the remote controller must look like the figure below to proceed to step .
Press and hold the [FILTER] and [ ] buttons simultaneously for two seconds to perform a search for the LOSSNAY that is interlocked with the
2
indoor unit to which the remote controller is connected.
Search result
3
- The indoor unit address and the interlocked LOSSNAY address will appear alternately.
<Indoor unit address and indoor unit> <LOSSNAY address and LOSSNAY>
- Without interlocked LOSSNAY settings
2
4
If no settings are necessary, exit the window by pressing and holding the [FILTER] and [ ] buttons simultaneously for 2 seconds. Go to step 1. Registration Procedures to make the interlock settings with LOSSNAY units, or go to step 2. Search Procedures to search for a particular LOSSNAY unit. Go to step 3. Deletion Procedures to delete any LOSSNAY settings.
< 1. Registration Procedures >
5
To interlock an indoor unit with a LOSSNAY unit, press the [ TEMP. ( ) or ( )] button on the remote controller that is connected to the indoor unit, and select its address (01 to 50).
6
Press the [ CLOCK ( ) or ( )] button to select the address of the LOSSNAY to be interlocked (01 to 50).
Indoor unit address LOSSNAY address
7
Press the [TEST] button to register the address of the selected indoor unit and the interlocked LOSSNAY unit.
- Registration completed The registered indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
- Registration error If the registration fails, the indoor unit address and the LOSSNAY address will be displayed alternately.
Registration cannot be completed: The selected unit address does not have a corresponding indoor unit or a LOSSNAY unit. Registration cannot be completed: Another LOSSNAY has already been interlocked with the selected indoor unit.
HWE08040 GB
- 70 -
[ IV Remote Controller ]
< 2. Search Procedures >
8
To search for the LOSSNAY unit that is interlocked with a particular indoor unit, enter the address of the indoor unit into the remote controller that is connected to it.
<Indoor unit address>
9
Press the [ MENU] button to search for the address of the LOSSNAY unit that is interlocked with the selected indoor unit.
- Search completed (With a LOSSNAY connection) The indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
- Search completed (No interlocked settings with a LOSSNAY exist.)
- The selected address does not have a corresponding indoor unit.
< 3. Deletion Procedures >
Take the following steps to delete the interlock setting between a LOSSNAY unit and the interlocked indoor unit from the remote controller that is connected to the indoor unit. Find the address of the LOSSNAY to be deleted (See section 2. Search Procedures. ), and bring up the result of the search for both the
10
indoor unit and LOSSNAY on the display.
11
Press the [ ON/OFF] button twice to delete the address of the LOSSNAY unit that is interlocked with the selected indoor unit.
- Registration completed The indoor unit address and , and the interlocked LOSSNAY address and will appear alternately.
-Deletion error If the deletion fails
[4] Using the built-in Temperature Sensor on the Remote Controller
1. Selecting the position of temperature detection (Factory setting: SW1-1 on the controller board on the indoor unit is set to OFF.)
To use the built-in sensor on the remote controller, set the SW1-1 on the controller board on the indoor unit to ON.
Some models of remote controllers are not equipped with a built-in temperature sensor. Use the built-in temperature sensor
on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
HWE08040 GB
- 71 -
- 72 -
V
Electrical Wiring Diagram
[1] Electrical Wiring Diagram of the Outdoor Unit .................................................................75
[2] Electrical Wiring Diagram of Transmission Booster......................................................... 78
HWE08040 GB
- 73 -
- 74 -
[ V Electrical Wiring Diagram ]
VElectrical Wiring Diagram
[1] Electrical Wiring Diagram of the Outdoor Unit
1. Electrical wiring diagram of the outdoor unit
(1) PUHY-P72, P96THMU-A
LEV1
LEV2a
LEV2b
M
M
M
Z24
Z25
1
654
3
2123456
CNLVA
CNDC
21
122131
21
pink
31
CN4
CN332
CNT02
CN801
CNT01
blue
yellow
CN2
7
5
2
Power
CPU power
supply circuit
CNAC2
black
CNLVB
1
P
63H1
red
failure
detection
132
circuit
CN505
6
X72
black
1
1
234
5
CNLVC
red
ONOFF
1
OFF
1
1
LED1
1
ON OFF ON OFF ON OFF ON
1
SWU1
1's digit
Control Board
SWU2
10's digit
X03
X02
X01
CN503
blue
CN502
CN501
3
3
3
1
2
1
1
10
10
10
10
10
Unit address setting
X04
CN504
green
1
1
3
CNTYP5
green
LED1
Display
setting
SW4 SW3 SW2 SW1
SW5
Function setting
Compressor ON/OFF output
Error detection output
*3
543
1
CN51
12V
X05
CN506
1
3
6
2
CNTYP4
TH6
4
1
CN213
green
TH5
TH7
TH3
1
1
2
21223
CN212
red
CN990
LED3:Lit when powered
X09
CN508
black
163
63LS
63HS1
3
2
1
3
2
3
1
CN202
red
CN201
LED2:CPU in operation
2
CN40
321
1
ON
4321
F01
TH2
TH4
1
2
2
1
CN215
black
CN211
4521
2323123
red
CNIT
1
yellow
CNS2
OFF
432112 431
CN41CN102CN3D
Power selecting
connector
3123
red
CN3S
1
blue
CN3N
yellow
CN3K
AC250V
3.15A T
12
red
CNAC
red
CNIT
TB7
yellow
CNS2
Indoor/Outdoor
transmission line
TB3
LED1:Power supply to
CN102
M-NET power
supply
circuit
F01
AC250V
3.15A T
G
M1 M2 M1 M2 S
TP2
TP1
M-NET Board
Central control
transmission
*4
Indoor/Outdoor
transmission
cable
cable
123
4512
1234
CN04
red
1313
CN03
black
*3
123
4
6
blue
CN21
CN22
CN4
12 45
21
CN18V
blue
F01
AC250V
15A T
FAN Board
CNVDC
red
A2
12345
red
THBOX
operation
LED3:CPU in
IPM
R630
C630
6
1
3
CNINV
U
Fan motor
(Heat exchanger)
white
72C
21S4b
A1
operation
LED1:Normal
LED2:Error
1
4
2
V
W
M
3~
SV1a
black
R1
*5
CH11
black
13142343
red
2
1
CN4
31
CN5V
2 1
CN6
SC-P1
INV Board
3334
24
DCL
SV5b
21S4a
1
2
5
3
1
C1
CNDC
pink
yellow
RSH2
C32
+++
C31
RSH1
C30
/Error(Blink)
R30
LED1:Normal operation(Lit)
U
ZNR1
IGBT
*5
TB-N
*5
TB-P
SC-P2
red
red
72C
44
C1
+
THHS
black
7
CN2
SC-V
SV9
CT22
SC-W
CT12
SC-U
SC-R
SC-S
CT3
SC-T
CN02
CX6
3
1
CY3
CY2
CY1
DSA1
Noise Filter
G
black
white
red
red
white
black
white
black
red
L
CX5
TB23
CX4
TB22
TB21
F2
AC250V
6.3A T
CX2
CX3
Z2
Z3
Z4
U
1
U
U
3
U
5
Z1
CX1
CN01
F1
AC250V
6.3A T
black
W
white
3~
V
MS
U
red
Motor
(Compressor)
Ground
L3L2
black
whitered
L1
L3L2
L1
Power supply
3~
60Hz
not supplied with the unit.
box boundaries.
input/output signal connectors.
outdoor units in the same refrigerant
*1.Single-dotted lines indicate wiring
*2.Dot-dash lines indicate the control
*3.Refer to the Data book for connecting
Explanation
Central control transmission
cable
Indoor/Outdoor transmission
cable
Power supply
Terminal
block
Symbol
TB1
TB3
TB7
system together.
*4.Daisy-chain terminals (TB3) on the
*5.Faston terminals have a locking
Subcool bypass outlet
temperature
OA temperature
ACC inlet pipe temperature
Discharge pipe temperature
Pipe temperature
Subcooled liquid refrigerant
temperature
Thermistor
TH2
TH3
TH4
TH5
TH6
TH7
208/230V
function.Make sure the terminals
are securely locked in place after
insertion.Press the tab on the
terminals to removed them.
IGBT temperature
Control box internal temperature
Function setting connector
THHS
Z24,25
THBOX
TB1
Explanation
High pressure protection for the
outdoor unit
Cooling/Heating switching
Heat exchanger capacity control
Discharge pressure
Low pressure
HIC bypass,Controls refrigerant
Outdoor unit heat exchanger
capacity control
Pressure control,Refrigerant flow
rate control
For opening/closing the bypass
circuit under the O/S
flow in HIC circuit
For opening/closing the bypass
circuit
4-way valve
Pressure
sensor
Pressure
switch
Magnetic relay(inverter main circuit)
Current sensor(AC)
Crankcase heater(for heating the compressor)
Symbol
63H1
63HS1
63LS
72C
CH11
21S4b
21S4a
<Symbol explanation>
HWE08040 GB
- 75 -
CT12,22,3
Linear
expansion
DC reactor
LEV1
DCL
valve
LEV2a,b
Solenoid
valve
SV5b
SV1a
SV9
[ V Electrical Wiring Diagram ]
(2) PUHY-P120THMU-A
LEV2a
M
1
2
3
4
6
CNLVB
red
1
Control Board
Power
failure
detection
circuit
X72
CN505
black
black
1
2
3
1
LEV2b
M
12345
CNLVC
red
LED1
X01
CN501
1
3
LEV1
M
122
6
536
5
4
CNDC
211131
2
2
2 1
pink
3
1
CNLVA
CN4
CN332
CNT02
CN801
CNT01
blue
yellow
CN2
752
CPU power
supply circuit
CNAC2
P
63H1
ON
1
ON
1
OFF
1
OFF ON
1
OFF ON
ON OFF
1
OFF
SWU1
SWU2
X02
CN502
1
2
3
LED1
Display
SW1
10
SW2
10
SW3
10
SW4
10
SW5
10
Function setting
1's digit
CN51
10's digit
12V
Unit address setting
X04
X03
CN506
CN503
blue
CN504
green
1
3
116
TH6
TH7
TH3
Z25
Z24
1
1223412
1
2
1
3
CN212
CN213
red
green
green
CNTYP5
CNTYP4
setting
Error detection output
Compressor ON/OFF output
*3
1
3
5
4
X05
X07
X08
CN507
red
CN508
3
black
635
1
TH5
63HS1
63LS
32132
1
121
3
3
2
red
CN201
CN202
CN990
ON
4 3
CN40
1
LED2:CPU in operation
LED3:Lit when powered
F01
X09
163
TH4
TH2
2t°112
CN211
CN215
black
51232132 4
red
CNIT
2
yellow
CNS2
OFF
41
23
CN41
1
4
Power selecting
connector
3 2
CN102
21 1
CN3D
13 2
red
CN3S
1
33
blue
CN3N
yellow
CN3K
AC250V
3.15A T
1
2
CNAC
red
red
CNIT
yellow
CNS2
Power supply to
:
LED1
CN102
M-NET power
red
black
F01
G
S
TB7
Indoor/Outdoor
transmission line
M2 M1 M2
TB3
M1
supply
circuit
AC250V
3.15A T
TP2
TP1
M-NET Board
Central control
transmission
*4
Indoor/Outdoor
transmission
cable
cable
12 3
45
12
1 2 3 4
CN04
3
1
3
1
CN03
*3
432
1
654
blue
CN21
5 4
CN22
2
CN4
12
1
CN18V
blue
F01
AC250V
15A T
FAN Board
CNVDC
3
2
1
red
THBOX
operation
LED3:CPU in
IPM
R630
C630
1
3
6
CNINV
U
Fan motor
(Heat exchanger)
operation
LED1:Normal
LED2:Error
124
V
W
M
3~
21S4b
SV1a
THHS
CH11
Z26
SV5b
21S4a
1
7
521
2
1
CN2
3
yellow
CN5V
ON
SW1
OFF
6
1
Function
setting
LED2:Error
LED1:Normal operation
operation
LED4:CPU in
2
CNCT3
black
1 2
CNTYP
1 2
CNTH
green
CNCT
3121
1
CNCT2
blue
432
72C
R2R1
DCL
TB31
red
CN03
black
31
Noise
Filter
4
SV5c
SV9
21S4c
CN4
LED3:Charge
INV Board
*5
R01
Z5
black
72C
TB42
F3
AC250V
3 1
CN02
black
U
C41
6.3A T
FT-N
IPM power
supply
circuit
25
CNIPM
1
red
+
-
Diode Stack
CY1
2
1
CNFG
blue
CNDC1
P
DCCT1
~~~
CX6
CX5
CY2
DSA1
G
F02
1
4
1
CX4
CY3
G
AC250V
3.15A T
4
C008
C007
SC-P1
U
Z4
pink
CNDC3
11 3
4
CNDC2
ACCT1
red
U
white
V
ACCT2
black
W
N
IPM
C1
black
L
ACCT3
TB23
TB22
TB21
AC250V
6.3A T
F2
CX2
CX3
Z2
Z3
1
U
U
U
5
Z1
CX1
CN01
F1
AC250V
6.3A T
red
U
white
3~
V
MS
W
Motor
black
(Compressor)
Ground
L3
blackwhitered
L2
L1
L3
L2
L1
Power supply
3~
TB1
not supplied with the unit.
box boundaries.
input/output signal connectors.
outdoor units in the same refrigerant
*1.Single-dotted lines indicate wiring
*2.Dot-dash lines indicate the control
*3.Refer to the Data book for connecting
Explanation
Central control transmission
cable
Indoor/Outdoor transmission
cable
Subcool bypass outlet
Power supply
Thermistor
Terminal
block
60Hz
208/230V
Symbol
Explanation
TH2
TB1
TB3
TB7
High pressure protection for the
outdoor unit
Discharge pressure
Low pressure
Cooling/Heating switching
Heat exchanger capacity control
system together.
*4.Daisy-chain terminals (TB3) on the
temperature
ACC inlet pipe temperature
Discharge pipe temperature
Pipe temperature
Subcooled liquid refrigerant
temperature
TH3
TH4
TH5
TH6
HIC bypass,Controls refrigerant
function.Make sure the terminals
are securely locked in place after
insertion.Press the tab on the
*5.Faston terminals have a locking
OA temperature
terminals to removed them.
IGBT temperature
Control box internal temperature
Function setting connector
TH7
THHS3Z24,25,26
THBOX
flow in HIC circuit
Pressure control,Refrigerant flow
rate control
For opening/closing the bypass
circuit under the O/S
For opening/closing the bypass
circuit
Outdoor unit heat exchanger
capacity control
Solenoid
4-way valve
Pressure
sensor
Pressure
switch
Magnetic relay(inverter main circuit)
Current sensor(AC)
Crankcase heater(for heating the compressor)
DC reactor
Symbol
21S4b,c
21S4a
63H1
<Symbol explanation>
HWE08040 GB
- 76 -
63HS1
63LS
72C
ACCT1,2,3
CH11
DCCT1 Current sensor(DC)
DCL
Linear
expansion
valve
LEV1
LEV2a,b
valve
SV1a
SV5b,c
SV9
[ V Electrical Wiring Diagram ]
(3) PUHY-P72, P96,P120YHMU-A
LEV1
12345
6
54321
CN2
5
2
7
supply circuit
ZNR01
CN72
2
M
CNLVB
red
1
red
1
LEV2a
65432
Power failure
detection circuit
U
CNAC2
black
2
1
M
CNLVC
3
M
6
CNLVA
63H1
P
CN4
CN332
blue
1
CNT02
3
1
CN801
yellow
2 1
CNT01
CPU power
pink
CNDC
3 21122
1
LEV2b
1
red
ONOFF
1
ON
1
OFF
ON
1
OFF
ONOFF
LED1
1
ON
1
OFF
1's
digit
SWU1
10's
digit
SWU2
Control Board
X01
X02
X03
CN501
CN502
CN503
blue
3
1
1
3
1
2
3
SW1
10
SW2
10
SW3
10
SW4
10
SW5
10
Unit address
setting
X04
CN504
green
CN506
6
1
Z24
Z25
1
2
1
3
1
green
CNTYP2
black
CNTYP4
CNTYP5
green
LED1
Display
setting
Function
setting
*3
Compressor ON/OFF output
Error detection output
1
4
5
3
CN51
12V
X05
X07
CN507
red
1
1
3
356
TH5
TH3
TH7
TH6
2
4
3
2
1
2
1
CN212
CN990
CN213
red
LED3:Lit when powered
X08
X09
CN508
black
3
6
1
63LS
3
2
1
1
1
2
1
3
3
CN202
red
LED2:CPU in operation
TH2
63HS1
3
2
2
1
2
1
CN201
CN215
black
TB7 Power
selecting
connector
CN40
F01
ON
4 3
12
AC250V
TH4
2
1
CN211
5 44 3
red
CNIT
21
21
yellow
CNS2
3 21
CN41
432
CN102
1
2
CN3D
3
11 2
red
CN3S
3
12
blue
3
CN3N
123
yellow
CN3K
3.15A T
21
CNAC
OFF
red
TP2
1
32
TP1
4
CNIT
red
5
S
M2
TB7
Indoor/Outdoor
1 2
1 2 3 4
CN04
red
3
1
transmission line
LED1:Power supply to
CNS2
yellow
CN102
M-NET power
supply circuit
G
M1
M2
TB3
M1
M-NET Board
Central control
transmission
*4
Indoor/Outdoor
transmission
cable
cable
*3
5
3
2
4
1
6
2
CN21
blue
1
CN5
3
red
1
CN4
1
LED3:CPU in
operation
2
CN18V
blue
C631
F01
DC700V
4A T
4
FAN Board
6
72C
1
5
4
3
2
CN22
red
IPM
R631
R630
C630
1
CNVDC
U
Fan motor
(Heat exchanger)
7
THBOX
V
M
4
3~
21S4b
operation
LED2:Error
LED1:Normal
C100
1
CNINV
W
CH11
21S4a
SV5b
SV1a
*7
7
2
1
CN4
1
3
yellow
CN5V
1 2
CN6
/ Error(Blink)
Normal operation(Lit)
:
*5
R5
R1
LED1
black
2
4
black
SC-P1
72C
1
3
FT-P
red
*6
DCL
P
SC-P2
red
CN1
3
1
R5
red
CN5
D1
R4
+
CN4
blue
3
1
GG
1
6
5
3
CN2
SV9
SV5c
21S4c
5
2
1
1
3
black
CNTYP
CN2
SC-V
C1
RSH1
THHS
ZNR1
U
IGBT
C35
C37
R31
C31
C33
FT-N
++++++
++
N
R30
C34
C32
C36
C30
4
1
1
Z5
F4
AC250V
6.3A T
Diode
Bridge
U
CN6
+-
C6
C5
R6
C4
C17
Noise
Filter
C10
U
F3
F1
F2
C3
Z4
DSA
U
Z3
U
Z2
F1,F2,F3
AC250V
6.3A T U
Z1
CT22
SC-W
SC-U
SC-L2
SC-L1
R33
red
R32
R34 R35
3
red
yellow
C9
C7
C8
C2
C1
black
white
red
CT12
SC-L3
CT3
black
white
INV Board
white
black
red
white
R2
R3
F5
F4
black
L
TB23
L3
TB22
L2L1
TB21
CN1B
black
1
R1
4
1
3
CN1A
black
W
white
V
MS
3~
U
Motor
red
(Compressor)
45678
L3
3
12
600V
3A F
600V
3A F
white
L1L2 L2
CNTR1
Ground
L3
L2
L1 L2 L3
TB1
red
L1
Power Source3~60Hz
432
CNTR2
CN06
460V
Transformer Box
1
T02
5
6
234
1
purple
460V
CNTR3
(Transformer)
2
3
4
1
T03
(Transformer)
56243
1
CN07
purple
460V
Explanation
High pressure protection for the
outdoor unit
Heat exchanger capacity control
Low pressure
Discharge pressure
Appliance
*7 do not exist
*7 exist
Model name
P120
in place after insertion. Press the tab
same refrigerant system together.
*1.Single-dotted lines indicate wiring not supplied with the unit.
*2.Dot-dash lines indicate the control box boundaries.
Make sure the terminals are securely locked
*3.Refer to the Data book for connecting input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the outdoor units in the
*5.Faston terminals have a locking function.
the unit off for at least 10 minutes,
on the terminals to removed them.
Before inspecting the inside of the
control box,turn off the power,keep
and confirm that the voltage between
*6.Control box houses high-voltage parts.
FT-P and FT-N on INV Board has dropped
P72/P96
to DC20V or less.
*7.Difference of appliance
HWE08040 GB
Cooling/Heating switching
4-way valve
Pressure
switch
Pressure
Symbol
21S4a
21S4b,c
63HS1
63H1
<Symbol explanation>
- 77 -
HIC bypass,Controls refrigerant
DC reactor
Linear
Crankcase heater(for heating the compressor)
Current sensor(AC)
Magnetic relay(inverter main circuit)
sensor
DCL
LEV1
CT12,22,3
CH11
72C
63LS
Outdoor unit heat exchanger
flow in HIC circuit
expansion
capacity control
For opening/closing the bypass
circuit under the O/S
Pressure control,Refrigerant flow
rate control
valve
Solenoid
valve
LEV2a,b
SV1a
SV5b,c
Central control transmission
cable
Indoor/Outdoor transmission
cable
Subcool bypass outlet
temperature
TB7
Pipe temperature
Thermistor
TH3
TH2
Discharge pipe temperature
TH4
Power supply
For opening/closing the bypass
circuit
Terminal
block
SV9
TB1
TB3
Subcooled liquid refrigerant
temperature
IGBT temperature
OA temperature
ACC inlet pipe temperature
Control box internal temperature
Function setting connector
TH5
TH6
TH7
THHS
Z24,25
THBOX
[ V Electrical Wiring Diagram ]
[2] Electrical Wiring Diagram of Transmission Booster
Terminal block for power supply (TB1)
100V/200VAC
Grounding
250V 5A
L
Red
White
Green
Red Red
Red
Varistor
U
DSA
White Blue RedRed
1 2
1 2 1 2
CN3
Electronic control board
Red
White
Red
Varistor
U
White White
White
Red
Red
Blue
White
Choke coil
CN2
CN4
CN1
2
White
Red
1
Black
Red
White
1
2
4
3
Stabilized power supply
2
1
CN2
Noise filter
1
2
3
3
Green/Yellow
E
4
Black
Black
CN1
White
Red
Black
Red
Black
Black
S
Terminal block 2 for
B
transmission line (TB3) Expanded (indoor unit) side
A
S
Terminal block 1 for
B
transmission line (TB2) Expanded (outdoor unit) side
A
HWE08040 GB
- 78 -
VI
Refrigerant Circuit
[1] Refrigerant Circuit Diagram ............................................................................................. 81
[2] Principal Parts and Functions ..........................................................................................82
HWE08040 GB
- 79 -
- 80 -
[ VI Refrigerant Circuit ]
VI Refrigerant Circuit
[1] Refrigerant Circuit Diagram
1. Outdoor unit (1) PUHY-P72, P96 models
TH7
SV5b
(2) PUHY-P120 models
HEX
TH3
21S4b
ST2
ST1
BV1
BV2
SV1a
CP1
LEV2a
LEV2b
TH5
63LS
ACC
ST6
ST7
21S4a
CJ1
O/S
Comp
ST3
TH6
63H1 63HS1
CV
TH4
CJ2
CP2SV9
TH2
SCC
LEV1
SV5c
TH7
SV5b
HEX
21S4c
SV9
TH3
21S4b
CP2
TH2
SCC
21S4a
CV
TH4
CJ2
LEV1
O/S
Comp
TH6
63H1 63HS1 CJ1
ST3
SV1a
CP1
ST7
LEV2a
LEV2b
ACC
ST6
63LS
TH5
ST2
ST1
BV1
BV2
HWE08040 GB
- 81 -
[ VI Refrigerant Circuit ]
[2] Principal Parts and Functions
1. Outdoor unit
Part
name
Com­pressor
High pres­sure sensor
Low pres­sure sensor
Symbols
(functions)
MC1 (Comp1)
Notes Usage Specifications Check method
Adjusts the amount of circulating refrigerant by adjusting the operat­ing frequency based on the oper­ating pressure data
63HS1 1) Detects high pressure
2) Regulates frequency and pro­vides high-pressure protec­tion
63LS 1) Detects low pressure
2) Provides low-pressure pro­tection
P72 and 96 models Low-pressure shell scroll compressor Wirewound resistance 20°C[68°F] :
0.268ohm(THMU)
0.981ohm(YHMU) P120 model
Low-pressure shell scroll compressor Wirewound resistance 20°C[68°F] :
0.161ohm(THMU)
0.583ohm(YHMU)
Pressure 0~4.15 MPa [601psi]
63HS1
Vout 0.5~3.5V
123
0.071V/0.098 MPa [14psi]
Con­nector
Con­nector
Pressure [MPa] =1.38 x Vout [V]-0.69 Pressure [psi] =(1.38 x Vout [V] - 0.69) x 145
1
GND (Black)
2
Vout (White)
3
Vcc (DC5V) (Red)
Pressure
63LS
0~1.7 MPa [247psi] Vout 0.5~3.5V
123
0.173V/0.098 MPa [14psi] Pressure [MPa] =0.566 x Vout [V] - 0.283 Pressure [psi] =(0.566 x Vout [V] - 0.283) x 145
1
GND (Black)
2
Vout (White)
3
Vcc (DC5V) (Red)
Pres­sure switch
63H1 1) Detects high pressure
2) Provides high-pressure pro­tection
4.15MPa[601psi] OFF setting
HWE08040 GB
- 82 -
[ VI Refrigerant Circuit ]
Part
name
Ther­mistor
Sole­noid valve
Symbols
(functions)
TH4 (Discharge)
Notes Usage Specifications Check method
1) Detects discharge air temper­ature
2) Provides high-pressure pro­tection
0°C[32°F] :698kohm
Degrees Celsius Resistance
R = 7.465k
120
R = 4057
25/120
R =
t
7.465
exp
4057
1
273 t
393
1
10°C[50°F] :413kohm 20°C[68°F] :250kohm 30°C[86°F] :160kohm 40°C[104°F] :104kohm 50°C[122°F] : 70kohm 60°C[140°F] : 48kohm 70°C[158°F] : 34kohm 80°C[176°F] : 24kohm 90°C[194°F] :17.5kohm 100°C[212°F] :13.0kohm 110°C[230°F] : 9.8kohm
TH2 LEV 1 is controlled based on the
TH2, TH3, and TH6 values.
TH3 (Pipe temperature)
1) Controls frequency
2) Controls defrosting during heating operation
3) Detects subcool at the heat exchanger outlet and controls LEV1 based on HPS data and TH3 data
TH7 (Outdoor tem­perature)
1) Detects outdoor air tempera­ture
2) Controls fan operation
Degrees Celsius
R = 15k
0
R = 3460
0/80
R = 15
t
exp
3460
1
273 t
0°C[32°F] :15kohm 10°C[50°F] :9.7kohm 20°C[68°F] :6.4kohm 25°C[77°F] :5.3kohm 30°C[86°F] :4.3kohm 40°C[104°F] :3.1kohm
273
TH5 LEV2a and LEV2b are controlled
based on the 63LS and TH5 val­ues.
TH6 Controls LEV1 based on TH2,
TH3, and TH6 data.
THHS Inverter heat sink tem­perature
Controls inverter cooling fan based on THHS temperature
Degrees Celsius
R = 17k
50
R = 4016
25/120
exp
R = 17
t
4016
1
273 t
323
1
THBOX Control box in­ternal tempera­ture detection
0°C[32°F] :161kohm 10°C[50°F] :97kohm 20°C[68°F] :60kohm 25°C[77°F] :48kohm 30°C[86°F] :39kohm 40°C[104°F] :25kohm
SV1a Discharge-suc­tion bypass
1) High/low pressure bypass at
start-up and stopping, and capacity control during low­load operation
AC208-230V Open while being powered/ closed while not being pow­ered
2) High-pressure-rise preven-
tion
SV5b Heat
Controls outdoor unit heat ex-
changer capacity exchanger capacity control
SV5c P120
model only
SV9 High-pressure-rise prevention Open while being powered/
closed while not being pow­ered
check
Resistance check
1
Continuity check with a tester
HWE08040 GB
- 83 -
[ VI Refrigerant Circuit ]
Part
name
Linear expan­sion
Symbols
(functions)
LEV1 (SC control)
Notes Usage Specifications Check method
Adjusts the amount of bypass flow
from the liquid pipe on the outdoor
unit during cooling
valve
LEV2a LEV2b
Adjusts refrigerant flow during
heating (Refrigerant flow adjust­ment)
Heater CH11 Heats the refrigerant in the com-
pressor
4-way valve
21S4a Changeover between heating and
cooling
21S4b 1) Changeover between heating
21S4c P120
model only
and cooling
2) Controls outdoor unit heat ex­changer capacity
DC12V Opening of a valve driven by a stepping motor 0-480 pulses (direct driven type)
DC12V Opening of a valve driven by a stepping motor 1400 pulses
Cord heater AC230V P72 and P96 models 1037 ohm 51W P120 model 928 ohm 57W
AC208-230V Dead: cooling cycle Live: heating cycle
AC208-230V Dead: cooling cycle Outdoor unit heat exchanger capacity at 100% Live: heating cycle Outdoor unit heat exchanger capacity at 50% or heating cycle
Same as in­door LEV The resistance value differs from that of the indoor LEV. (Refer to the section "LEV Troubleshooti ng."(page 238 ))
Same as in­door LEV
Resistance check
Continuity check with a tester
HWE08040 GB
- 84 -
[ VI Refrigerant Circuit ]
2. Indoor Unit
Part
Name
Linear expan­sion valve
Ther­mistor
Symbol
(functions)
Notes Usage Specification Check method
LEV 1) Adjusts superheat at the
indoor heat exchanger outlet during cooling
2) Adjusts subcool at the heat exchanger outlet of the indoor unit during cooling
TH1
Indoor unit control (Thermo) (Suction air temperature)
TH2 (Pipe temper­ature)
1) Indoor unit control (Frost prevention, Hot adjust)
2) LEV control during heat­ing operation (subcool detection).
TH3 (Gas pipe
LEV control during cooling op­eration (superheat detection)
temperature)
TH4
Indoor unit control (Thermo) Outdoor air temperature)
Temperature
Indoor unit control (Thermo) sensor (In­door air tem­perature)
DC12V Opening of stepping motor driving valve 0-(1400) puls­es
R0=15k R
0/80
=3460 Rt = 15exp{3460( - )}
1
273+t
1
273
0°C [32°F]:15kohm 10°C [50°F] :9.7kohm 20°C [68°F]:6.4kohm 25°C [77°F] :5.3kohm 30°C [86°F] :4.3kohm 40°C [104°F] :3.1kohm
Refer to the section "Continuity Test with a Tester". Continuity between white, red, and or­ange. Continuity between yellow, brown, and blue.
White
Red
Orange
Yellow
M
Brown Blue
Resistance check
HWE08040 GB
- 85 -
- 86 -
VII
Control
[1] Functions and Factory Settings of the Dipswitches ......................................................... 89
[2] Controlling the Outdoor Unit ............................................................................................ 96
[3] Operation Flow Chart..................................................................................................... 108
HWE08040 GB
- 87 -
- 88 -
[ VII Control ]
VII Control
[1] Functions and Factory Settings of the Dipswitches
1. Outdoor unit (1) Control board
Switch Function
Function according to switch setting Switch setting timing
OFF ON OFF ON OC OS
SWU 1-2 Unit address setting Set to 00 or 51-100 with the dial switch Before power on C C
SW1 1-10
1
2
3
For self-diagnosis/ operation monitoring
Centralized control switch
Deletion of connec­tion information
Deletion of error his­tory SW
Refer to the LED monitor display on the outdoor unit board.
Without connection to the centralized controller
With connection to the centralized con­troller
Anytime after power on
Before power on
Normal control Deletion Before power on
(OC) Storage of IC/ OC error history
(OS) Storage of OS error history
(OC) Deletion of IC/ OC error history
(OS) Deletion of OS error history
Anytime after power on (When switched from OFF to ON)
After being energized and
4 Pump down mode Normal control Pump down mode
while the compressor is stopped
5- - - - -­6- - - - --
SW2
Forced defrost
7
Note 3
Normal control
Forced defrost starts
10 minutes after com­pressor startup
Anytime af­ter power on (When switched from OFF to ON)
Defrost timer setting
8
Note 3
Target evaporation
9
temperature setting
50 minutes 90 minutes
Depends on the setting combination with the SW3-5 setting (Note 4)
Anytime after power on (When switched from OFF to ON)
Anytime after power on
Enable/disable re­frigerant noise sup­pression function
10
during defrosting (Fan operation
Normal control
Refrigerant noise suppression
Befo
re powe
r on
against leaky indoor unit LEV)
Units that re-
quire switch
setting Note.2
CC
BB
A-
CC
A-
AA
BB
A-
A-
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective. C: The setting is effective for the unit on which the setting is made.
3) Refer to "VII [2] Controlling the Outdoor Unit" for details.(page 96)
4) The table below shows the combination of SW2-9 and SW3-5 settings and the target evaporation temperature setting that corresponds to each combination.
Switch
OFF ON
SW2-9
SW3-5 OFF 0°C [32°F] -4°C [25°F]
ON -2°C [28°F] -6°C [21°F]
HWE08040 GB
- 89 -
[ VII Control ]
Switch Function
SW3
SW4
Units that
require
Function according to switch setting Switch setting timing
switch set-
ting
Note.2
OFF ON OFF ON OC OS
Test run mode: en-
1
abled/disabled Test run mode: ON/
2
OFF Defrost start tem-
3
perature Note 5
Defrost end tem-
4
perature Note 5
SW3-2 disabled SW3-2 enabled Anytime after power on
Stops all ICs
Sends a test-run signal to all IC
After power on and when SW3-1 is on.
-10°C [14°F] -5°C [23°F] Anytime after power on
P72, P96 10°C [50°F]
P120
5°C [41°F]
Anytime after power on (ex­cept during defrost)
A-
A-
BB
BB
7°C [45°F]
Target evaporation
5
temperature setting Temperature unit
6
setting Target condensing
7
temperature setting
Depends on the setting combination with the SW2-9 setting (Note 4)
Anytime after power on
°C °F Anytime after power on
49°C [120°F] 53°C [127°F] -
A-
CC
A-
for heating
8- - - - --
9 Model setting
10 Model setting
Enable/disable high
1
sensible tempera­ture operation
Outdoor standard static pressure
High static pressure 60Pa
Normal operation mode
Outdoor high static pressure
High static pressure 30Pa
High sensible tem­perature operation mode
Before being energized
Before being energized
Before being energized
CC
CC
A-
2- - - - --
Refrigerant amount
3
adjustment
Low-noise mode/
4
step demand switching
Automatic cooling/heat­ing switchover (IC with
5
the minimum address)
Cumulative com-
6
pressor operation time data deletion
Normal operation mode
Low-noise mode Note 3
Normal operation mode
Cumulative com­pressor operation time data is retained.
Refrigerant amount adjust mode
Anytime after being energized (ex­cept during initial startup mode. Automatically cancelled 60 min­utes after compressor startup)
Step demand mode Before being energized
Automatic cooling/ heating switchover
Cumulative com­pressor operation time data is deleted.
Before being energized
Anytime after power on (when the unit is turned on)
A-
CC
A-
CC
7- - - - -­8- - - - -­9- - - - --
10 - - - - - -
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective. C: The setting is effective for the unit on which the setting is made.
3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed. Setting of CN3D is required.
4) The table below shows the combination of SW2-9 and SW3-5 settings and the target evaporation temperature setting that corresponds to each combination.
Switch
OFF ON
SW2-9
SW3-5 OFF 0°C [32°F] -4°C [25°F]
ON -2°C [28°F] -6°C [21°F]
5) Refer to VII [2] Controlling the Outdoor Unit -7- Defrost Operation Control for details.(page 99)
HWE08040 GB
- 90 -
[ VII Control ]
Units that re-
quire switch
setting Note.2
Switch Function
Function according to switch setting Switch setting timing
OFF ON OFF ON OC OS
1 2----
Model setting
3----
----CC
4----
SW5
Low-noise mode
5
selection
Capacity priority mode Note 3
Low-noise mode Before being energized
A-
6- - - - -­7 Model setting - - - B B
8- - - - -­9- - - - --
10 Heating backup Ineffective Effective Any time after power on A -
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective. C: The setting is effective for the unit on which the setting is made.
3) When set to the capacity priority mode and if the following conditions are met, the Low-noise mode will terminate, and the unit will go back into the normal operation mode. Cooling: Outside temperature is high or high pressure is high. Heating: Outside temperature is low or low pressure is low.
(2) INV board
1) PUHY-P72, P96, P120YHMU-A, PUHY-P72, P96THMU-A
Functions are switched with the following connector.
Connector Function
Function according to connec-
tor
Setting timing
Enabled Disabled Enabled Disabled
CN6 short­circuit con-
nector
Enabling/disabling the following error detection functions; ACCT sensor failure (5301 Detail No. 115) ACCT sensor circuit failure
Error detec­tion enabled
Error detec­tion disable (No load op­eration is pos­sible.)
Anytime after power on
(5301 Detail No.117) IPM open/ACCT erroneous wiring (5301 Detail No. 119) Detection of ACCT erroneous wiring (5301 Detail No.120)
CN6 short-circuit connector is mated with the mating connector. Leave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the
equipment from damage.
HWE08040 GB
- 91 -
Loading...