Before installing the unit, thoroughly read the following safety precautions.
Observe these safety precautions for your safety.
WARNING
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or death.
CAUTION
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or damage to the unit.
After reading this manual, give it to the user to retain for future reference.
Keep this manual for easy reference. When the unit is moved or repaired, give this manual to those who provide these
services.
When the user changes, make sure that the new user receives this manual.
WARNING
Ask your dealer or a qualified technician to install the
unit.
Improper installation by the user may result in water leakage, electric shock, smoke, and/or fire.
Properly install the unit on a surface that can withstand the weight of the unit.
Unit installed on an unstable surface may fall and cause injury.
Only use specified cables. Securely connect each cable so that the terminals do not carry the weight of the
cable.
Improperly connected or fixed cables may produce heat
and start a fire.
Take appropriate safety measures against strong
winds and earthquakes to prevent the unit from falling.
If the unit is not installed properly, the unit may fall and
cause serious injury to the person or damage to the unit.
Do not make any modifications or alterations to the
unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock,
smoke, and/or fire.
In the event of a refrigerant leak, thoroughly ventilate
the room.
If refrigerant gas leaks and comes in contact with an open
flame, poisonous gases will be produced.
When installing the All-Fresh type units, take it into
consideration that the outside air may be discharged
directly into the room when the thermo is turned off.
Direct exposure to outdoor air may have an adverse effect
on health. It may also result in food spoilage.
Properly install the unit according to the instructions
in the installation manual.
Improper installation may result in water leakage, electric
shock, smoke, and/or fire.
Have all electrical work performed by an authorized
electrician according to the local regulations and instructions in this manual, and a dedicated circuit must
be used.
Insufficient capacity of the power supply circuit or improper
installation may result in malfunctions of the unit, electric
shock, smoke, and/or fire.
Do not touch the heat exchanger fins.
The fins are sharp and dangerous.
HWE08040GB
ii
WARNING
Securely attach the terminal block cover (panel) to the
unit.
If the terminal block cover (panel) is not installed properly,
dust and/or water may infiltrate and pose a risk of electric
shock, smoke, and/or fire.
Only use the type of refrigerant that is indicated on the
unit when installing or reinstalling the unit.
Infiltration of any other type of refrigerant or air into the unit
may adversely affect the refrigerant cycle and may cause
the pipes to burst or explode.
When installing the unit in a small room, exercise caution and take measures against leaked refrigerant
reaching the limiting concentration.
Consult your dealer with any questions regarding limiting
concentrations and for precautionary measures before installing the unit. Leaked refrigerant gas exceeding the limiting concentration causes oxygen deficiency.
Consult your dealer or a specialist when moving or reinstalling the unit.
Improper installation may result in water leakage, electric
shock, and/or fire.
After completing the service work, check for a gas
leak.
If leaked refrigerant is exposed to a heat source, such as a
fan heater, stove, or electric grill, poisonous gases may be
produced.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature
switch by defeating the safety features of these devices, or
the use of accessories other than the ones that are recommended by MITSUBISHI may result in smoke, fire, and/or
explosion.
Only use accessories recommended by MITSUBISHI.
Ask a qualified technician to install the unit. Improper installation by the user may result in water leakage, electric
shock, smoke, and/or fire.
Control box houses high-voltage parts.
When opening or closing the front panel of the control box,
do not let it come into contact with any of the internal components. Before inspecting the inside of the control box,
turn off the power, keep the unit off for at least 10 minutes,
and confirm that the voltage between FT-P and FT-N on
INV Board has dropped to DC20V or less. (It takes about
10 minutes to discharge electricity after the power supply is
turned off.)
HWE08040GB
ii
Precautions for handling units for use with R410A
CAUTION
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the re-
sidual refrigerant and refrigerating machine oil in the existing piping may cause the refrigerating machine oil in the
new unit to deteriorate.
R410A is a high-pressure refrigerant and can cause the
existing pipes to burst.
Use refrigerant pipes made of phosphorus deoxidized
copper. Keep the inner and outer surfaces of the pipes
clean and free of such contaminants as sulfur, oxides,
dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes
may cause the refrigerant oil to deteriorate.
Store the pipes to be installed indoors, and keep both
ends of the pipes sealed until immediately before brazing. (Keep elbows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerating machine oil to deteriorate or
cause the unit to malfunction.
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the refrigerating machine oil to deteriorate.
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and
may result in performance loss.
Use a vacuum pump with a reverse-flow check valve.
If a vacuum pump that is not equipped with a reverse-flow
check valve is used, the vacuum pump oil may flow into the
refrigerant cycle and cause the refrigerating machine oil to
deteriorate.
Prepare tools for exclusive use with R410A. Do not use
the following tools if they have been used with the conventional refrigerant (gauge manifold, charging hose,
gas leak detector, reverse-flow check valve, refrigerant
charge base, vacuum gauge, and refrigerant recovery
equipment.).
If the refrigerant or the refrigerating machine oil left on
these tools are mixed in with R410A, it may cause the refrigerating machine oil to deteriorate.
Infiltration of water may cause the refrigerating machine
oil to deteriorate.
Gas leak detectors for conventional refrigerants will not
detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant will change, and the unit may experience power loss.
Exercise special care when handling the tools for use
with R410A.
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerating machine oil to deteriorate.
Only use refrigerant R410A.
The use of other types of refrigerant that contain chlorine
(i.e. R22) may cause the refrigerating machine oil to deteriorate.
HWE08040GB
iiiiii
Before installing the unit
WARNING
Do not install the unit where a gas leak may occur.
If gaseous refrigerant leaks and piles up around the unit, it
may be ignited.
Do not use the unit to keep food items, animals, plants,
artifacts, or for other special purposes.
The unit is not designed to preserve food products.
Do not use the unit in an unusual environment.
Do not install the unit where a large amount of oil or steam
is present or where acidic or alkaline solutions or chemical
sprays are used frequently. Doing so may lead to a remarkable drop in performance, electric shock, malfunctions, smoke, and/or fire.
The presence of organic solvents or corrosive gas (i.e.
ammonia, sulfur compounds, and acid) may cause gas
leakage or water leakage.
When installing the unit in a hospital, take appropriate
measures to reduce noise interference.
High-frequency medical equipment may interfere with the
normal operation of the air conditioner or vice versa.
Do not install the unit on or over things that cannot get
wet.
When the humidity level exceeds 80% or if the drainage
system is clogged, the indoor unit may drip water. Drain water is also discharged from the outdoor unit. Install a centralized drainage system if necessary.
HWE08040GB
iv
Before installing the unit (moving and reinstalling the unit) and performing
electrical work
CAUTION
Properly ground the unit.
Do not connect the grounding wire to a gas pipe, water pipe,
lightning rod, or grounding wire from a telephone pole. Improper grounding may result in electric shock, smoke, fire,
and/or malfunction due to noise interference.
Do not put tension on the power supply wires.
If tension is put on the wires, they may break and result in
excessive heat, smoke, and/or fire.
Install an earth leakage breaker to avoid the risk of
electric shock.
Failure to install an earth leakage breaker may result in
electric shock, smoke, and/or fire.
Use the kind of power supply wires that are specified
in the installation manual.
The use of wrong kind of power supply wires may result in
current leak, electric shock, and/or fire.
Use breakers and fuses (current breaker, remote
switch <switch + Type-B fuse>, moulded case circuit
breaker) with the proper current capacity.
The use of wrong capacity fuses, steel wires, or copper
wires may result in malfunctions, smoke, and/or fire.
Periodically check the installation base for damage.
If the unit is left on a damaged platform, it may fall and
cause injury.
Properly install the drain pipes according to the instructions in the installation manual. Keep them insulated to avoid dew condensation.
Improper plumbing work may result in water leakage and
damage to the furnishings.
Exercise caution when transporting products.
Products weighing more than 20 kg should not be carried
alone.
Do not carry the product by the PP bands that are used on
some products.
Do not touch the heat exchanger fins. They are sharp and
dangerous.
When lifting the unit with a crane, secure all four corners
to prevent the unit from falling.
Properly dispose of the packing materials.
Nails and wood pieces in the package may pose a risk of
injury.
Plastic bags may pose a risk of choking hazard to chil-
dren. Tear plastic bags into pieces before disposing of
them.
Do not spray water on the air conditioner or immerse
the air conditioner in water.
Otherwise, electric shock and/or fire may result.
When handling units, always wear protective gloves to
protect your hands from metal parts and high-temperature parts.
HWE08040GB
vv
Before the test run
CAUTION
Turn on the unit at least 12 hours before the test run.
Keep the unit turned on throughout the season. If the unit is
turned off in the middle of a season, it may result in malfunctions.
To avoid the risk of electric shock or malfunction of the
unit, do not operate switches with wet hands.
Do not touch the refrigerant pipes with bare hands during and immediately after operation.
During or immediately after operation, certain parts of the
unit such as pipes and compressor may be either very cold
or hot, depending on the state of the refrigerant in the unit
at the time. To reduce the risk of frost bites and burns, do
not touch these parts with bare hands.
Do not operate the unit without panels and safety
guards.
Rotating, high-temperature, or high-voltage parts on the unit
pose a risk of burns and/or electric shock.
Do not turn off the power immediately after stopping
the operation.
Keep the unit on for at least five minutes before turning off
the power to prevent water leakage or malfunction.
Do not operate the unit without the air filter.
Dust particles may build up in the system and cause malfunctions.
HWE08040GB
vi
CONTENTS
I
II
III
IV
V
VI
VII
VIII
IX
X
Read Before Servicing
[1] Read Before Servicing.............................................................................................................. 3
[2] Necessary Tools and Materials ................................................................................................ 4
[10] Remedies to be taken in case of a Refrigerant Leak .......................................................11
[11] Characteristics of the Conventional and the New Refrigerants .......................................12
[12] Notes on Refrigerating Machine Oil ................................................................................. 13
HWE08040GB
- 1 -
- 2 -
[ I Read Before Servicing ]
IRead Befo re Servicing
[1] Read Before Servicing
1. Check the type of refrigerant used in the system to be serviced.
Refrigerant Type
Multi air conditioner for building application CITY MULTI THMU-A, YHMU-A series R410A
2. Check the symptoms exhibited by the unit to be serviced.
Refer to this service handbook for symptoms relating to the refrigerant cycle.
3. Thoroughly read the safety precautions at the beginning of this manual.
4. Preparing necessary tools: Prepare a set of tools to be used exclusively with each type of refrigerant.
Refer to "Necessary Tools and Materials" for information on the use of tools.(page 4)
5. Verification of the connecting pipes: Verify the type of refrigerant used for the unit to be moved or replaced.
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free
of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
6. If there is a leak of gaseous refrigerant and the remaining refrigerant is exposed to an open flame, a poisonous gas
hydrofluoric acid may form. Keep workplace well ventilated.
CAUTION
Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.
The use of refrigerant that contains chloride, such as R22, will cause the refrigerating machine oil to deteriorate.
HWE08040GB
- 3 -
[ I Read Before Servicing ]
[2] Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C)
1. To be used exclusively with R410A (not to be used if used with R22 or R407C)
Tools/MaterialsUseNotes
Gauge ManifoldEvacuation and refrigerant chargingHigher than 5.09MPa[738psi] on the
Charging HoseEvacuation and refrigerant chargingThe hose diameter is larger than the
Refrigerant Recovery CylinderRefrigerant recovery
Refrigerant CylinderRefrigerant chargingThe refrigerant type is indicated. The
Charging Port on the Refrigerant Cylinder Refrigerant chargingThe charge port diameter is larger
Flare NutConnection of the unit with the pipesUse Type-2 Flare nuts.
2. Tools and materials that may be used with R410A with some restrictions
Tools/MaterialsUseNotes
Gas Leak DetectorGas leak detectionThe ones for use with HFC refrigerant
Vacuum PumpVacuum dryingMay be used if a check valve adapter
Flare ToolFlare processingFlare processing dimensions for the
Refrigerant Recovery EquipmentRefrigerant recoveryMay be used if compatible with
high-pressure side
conventional model.
cylinder is pink.
than that of the current port.
may be used.
is attached.
piping in the system using the new refrigerant differ from those of R22. Refer to next page.
R410A.
3. Tools and materials that are used with R22 or R407C that may also be used with R410A
Tools/MaterialsUseNotes
Vacuum Pump with a Check ValveVacuum drying
BenderBending pipes
Torque WrenchTightening flare nutsOnly the flare processing dimensions
for pipes that have a diameter of
ø12.70 (1/2") and ø15.88 (5/8") have
been changed.
Pipe CutterCutting pipes
Welder and Nitrogen CylinderWelding pipes
Refrigerant Charging MeterRefrigerant charging
Vacuum GaugeVacuum level check
4. Tools and materials that must not be used with R410A
Tools/MaterialsUseNotes
Charging CylinderRefrigerant chargingProhibited to use
Tools for R410A must be handled with special care to keep moisture and dust from infiltrating the cycle.
HWE08040GB
- 4 -
[ I Read Before Servicing ]
[3] Piping Materials
Do not use the existing piping!
1. Copper pipe materials
O-material (Annealed)Soft copper pipes (annealed copper pipes). They can easily be bent with hands.
1/2H-material (Drawn)Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed)
The distinction between O-materials (Annealed) and 1/2H-materials (Drawn) is made based on the strength of the pipes them-
selves.
O-materials (Annealed) can easily be bent with hands.
1/2H-materials (Drawn) are considerably stronger than O-material (Annealed) at the same thickness.
2. Types of copper pipes
Maximum working pressureRefrigerant type
3.45 MPa [500psi]R22, R407C etc.
4.30 MPa [624psi]R410A etc.
3. Piping materials/Radial thickness
Use refrigerant pipes made of phosphorus deoxidized copper.
The operation pressure of the units that use R410A is higher than that of the units that use R22.
Use pipes that have at least the radial thickness specified in the chart below.
(Pipes with a radial thickness of 0.7 mm or less may not be used.)
at the same radial thickness.
Pipe size (mm[in])Radial thickness (mm)Type
ø6.35[1/4"]0.8t
ø9.52[3/8"]0.8t
ø12.7[1/2"]0.8t
ø15.88[5/8"]1.0t
ø19.05[3/4"]1.0t
ø22.2[7/8"]1.0t
ø25.4[1"]1.0t
ø28.58[1-1/8"]1.0t
ø31.75[1-1/4"]1.1t
ø34.93[1-3/8"]1.1t
ø41.28[1-5/8"]1.2t
The pipes in the system that uses the refrigerant currently on the market are made with O-material (Annealed), even if the
pipe diameter is less than ø19.05 (3/4"). For a system that uses R410A, use pipes that are made with 1/2H-material (Drawn)
unless the pipe diameter is at least ø19.05 (3/4") and the radial thickness is at least 1.2t.
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
O-material (Annealed)
1/2H-material,
H-material (Drawn)
HWE08040GB
- 5 -
[ I Read Before Servicing ]
4. Thickness and refrigerant type indicated on the piping materials
Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5. Flare processing (O-material (Annealed) and OL-material only)
The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.
Flare processing dimensions (mm[in])
Pipe size (mm[in])
A dimension (mm)
R410AR22, R407C
ø6.35[1/4"]9.19.0
ø9.52[3/8"]13.213.0
ø12.7[1/2"]16.616.2
Dimension A
ø15.88[5/8"]19.719.4
ø19.05[3/4"]24.023.3
If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0
and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
6. Flare nut
The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.
Flare nut dimensions (mm[in])
Pipe size (mm[in])
B dimension (mm)
R410AR22, R407C
ø6.35[1/4"]17.017.0
ø9.52[3/8"]22.022.0
ø12.7[1/2"]26.024.0
Dimension B
ø15.88[5/8"]29.027.0
ø19.05[3/4"]36.036.0
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
HWE08040GB
- 6 -
[ I Read Before Servicing ]
[4] Storage of Piping
1. Storage location
Store the pipes to be used indoors. (Warehouse at site or owner's warehouse)
If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe.
2. Sealing the pipe ends
Both ends of the pipes should be sealed until just before brazing.
Keep elbow pipes and T-joints in plastic bags.
The new refrigerator oil is 10 times as hygroscopic as the conventional refrigerating machine oil (such as Suniso) and, if not
handled with care, could easily introduce moisture into the system. Keep moisture out of the pipes, for it will cause the oil to
deteriorate and cause a compressor failure.
[5] Pipe Processing
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Use a minimum amount of oil.
Use only ester oil, ether oil, and alkylbenzene.
HWE08040GB
- 7 -
[ I Read Before Servicing ]
[6] Brazing
No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide
scale, water, and dust) out of the refrigerant system.
Example: Inside the brazed connection
Use of oxidized solder for brazingUse of non-oxidized solder for brazing
1. Items to be strictly observed
Do not conduct refrigerant piping work outdoors if raining.
Use non-oxidized solder.
Use a brazing material (BCuP-3) that requires no flux when brazing between copper pipes or between a copper pipe and
copper coupling.
If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.
2. Reasons
The new refrigerating machine oil is 10 times as hygroscopic as the conventional oil and is more likely to cause unit failure if
water infiltrates into the system.
Flux generally contains chloride. Residual flux in the refrigerant circuit will cause sludge to form.
3. Notes
Do not use commercially available antioxidants because they may cause the pipes to corrode or refrigerating machine oil to
deteriorate.
HWE08040GB
- 8 -
[ I Read Before Servicing ]
[7] Air Tightness Test
No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak.
Halide torch R22 leakage detector
1. Items to be strictly observed
Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight-
ness, taking temperature variations into account.
Refrigerant R410A must be charged in its liquid state (vs. gaseous state).
2. Reasons
Oxygen, if used for an air tightness test, poses a risk of explosion. (Only use nitrogen to check air tightness.)
Refrigerant R410A must be charged in its liquid state. If gaseous refrigerant in the cylinder is drawn out first, the composition
of the remaining refrigerant in the cylinder will change and become unsuitable for use.
3. Notes
Procure a leak detector that is specifically designed to detect an HFC leak. A leak detector for R22 will not detect an
HFC(R410A) leak.
1. Vacuum pump with a reverse-flow check valve (Photo1)
To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum
pump with a reverse-flow check valve.
A reverse-flow check valve may also be added to the vacuum pump currently in use.
2. Standard of vacuum degree (Photo 2)
Use a vacuum pump that attains 0.5Torr(65Pa) or lower degree of vacuum after 5 minutes of operation, and connect it directly
to the vacuum gauge. Use a pump well-maintained with an appropriate lubricant. A poorly maintained vacuum pump may not
be able to attain the desired degree of vacuum.
3. Required precision of vacuum gauge
Use a vacuum gauge that registers a vacuum degree of 5Torr(650Pa) and measures at intervals of 1Torr(130Pa). (A recommended vacuum gauge is shown in Photo2.)
Do not use a commonly used gauge manifold because it cannot register a vacuum degree of 5Torr(650Pa).
4. Evacuation time
After the degree of vacuum has reached 5Torr(650Pa), evacuate for an additional 1 hour. (A thorough vacuum drying re-
moves moisture in the pipes.)
Verify that the vacuum degree has not risen by more than 1Torr(130Pa) 1hour after evacuation. A rise by less than
1Torr(130Pa) is acceptable.
If the vacuum is lost by more than 1Torr(130Pa), conduct evacuation, following the instructions in section 6. Special vacuum
drying.
5. Procedures for stopping vacuum pump
To prevent the reverse flow of vacuum pump oil, open the relief valve on the vacuum pump side, or draw in air by loosening
the charge hose, and then stop the operation.
The same procedures should be followed when stopping a vacuum pump with a reverse-flow check valve.
6. Special vacuum drying
When 5Torr(650Pa) or lower degree of vacuum cannot be attained after 3 hours of evacuation, it is likely that water has pen-
etrated the system or that there is a leak.
If water infiltrates the system, break the vacuum with nitrogen. Pressurize the system with nitrogen gas to
0.5kgf/cm
2
G(0.05MPa) and evacuate again. Repeat this cycle of pressurizing and evacuation either until the degree of vac-
uum below 5Torr(650Pa) is attained or until the pressure stops rising.
Only use nitrogen gas for vacuum breaking. (The use of oxygen may result in an explosion.)
HWE08040GB
- 10 -
[ I Read Before Servicing ]
[9] Refrigerant Charging
Cylinder with a siphon
Cylinder without a siphon
Cylin-
Cylin-
der
der
Cylinder color R410A is pink.Refrigerant charging in the liquid state
ValveValve
liquid
liquid
1. Reasons
R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled
the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid
phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and become unsuitable for use.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check
the type of the cylinder on the label before use.
[10] Remedies to be taken in case of a Refrigerant Leak
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in the
liquid state.)
Refer to "IX [5] Refrigerant Leak".(page 265)
HWE08040GB
- 11 -
[ I Read Before Servicing ]
[11] Characteristics of the Conventional and the New Refrigerants
1. Chemical property
As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant.
However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will
accumulate at the bottom of the room and may cause hypoxia.
If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a confined area.
New Refrigerant (HFC type)Conventional Refriger-
ant (HCFC type)
R410AR407CR22
R32/R125R32/R125/R134aR22
Composition (wt%)(50/50)(23/25/52)(100)
Type of RefrigerantPseudo-azeotropic
Refrigerant
Non-azeotropic
Refrigerant
Single Refrigerant
ChlorideNot includedNot includedIncluded
Safety ClassA1/A1A1/A1A1
Molecular Weight72.686.286.5
Boiling Point (°C/°F)-51.4/-60.5-43.6/-46.4-40.8/-41.4
Steam Pressure
1.557/2260.9177/1330.94/136
(25°C,MPa/77°F,psi) (gauge)
Saturated Steam Density
(25°C,kg/m
3
/77°F,psi)
64.042.544.4
FlammabilityNonflammableNonflammableNonflammable
Ozone Depletion Coefficient (ODP)
Global Warming Coefficient (GWP)
*1
*2
Refrigerant Charging MethodRefrigerant charging in
Replenishment of Refrigerant after a Refrigerant
000.055
173015301700
the liquid state
Refrigerant charging in
the liquid state
Refrigerant charging in
the gaseous state
AvailableAvailableAvailable
Leak
*1 When CFC11 is used as a reference
*2 When CO
is used as a reference
2
2. Refrigerant composition
R410A is a pseudo-azeotropic HFC blend and can almost be handled the same way as a single refrigerant, such as R22. To
be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn
out, the composition of the remaining refrigerant will change and become unsuitable for use.
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced.
3. Pressure characteristics
The pressure in the system using R410A is 1.6 times as great as that in the system using R22.
Pressure (gauge)
Temperature (°C/°F)
R410AR407CR22
MPa/psiMPa/psiMPa/psi
-20/-40.30/440.18/260.14/20
0/320.70/1020.47/680.40/58
20/681.34/1940.94/1360.81/117
40/1042.31/3351.44/2091.44/209
60/1403.73/5412.44/3542.33/338
65/1494.17/6052.75/3992.60/377
HWE08040GB
- 12 -
[ I Read Before Servicing ]
[12] Notes on Refrigerating Machine Oil
1. Refrigerating machine oil in the HFC refrigerant system
HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system.
Note that the ester oil used in the system has properties that are different from commercially available ester oil.
RefrigerantRefrigerating machine oil
R22 Mineral oil
R407CEster oil
R410A Ester oil
2. Effects of contaminants
*1
Refrigerating machine oil used in the HFC system must be handled with special care to keep contaminants out.
The table below shows the effect of contaminants in the refrigerating machine oil on the refrigeration cycle.
3. The effects of contaminants in the refrigerating machine oil on the refrigeration cycle.
CauseSymptomsEffects on the refrigerant cycle
Water infiltrationFrozen expansion valve
and capillary tubes
Clogged expansion valve and capillary tubes
Poor cooling performance
Compressor overheat
Motor insulation failure
Burnt motor
Coppering of the orbiting scroll
Lock
Burn-in on the orbiting scroll
Sludge formation and adhesion
Acid generation
Oxidization
Oil degradation
Sludge formation and adhesionClogged expansion valve and capillary tubes
Mineral oil
etc.
Poor cooling performance
Compressor overheat
Oil degradationBurn-in on the orbiting scroll
*1. Contaminants is defined as moisture, air, processing oil, dust/dirt, wrong types of refrigerant, and refrigerating machine oil.
HWE08040GB
- 13 -
- 14 -
II
Restrictions
[1] System configuration ....................................................................................................... 17
[2] Types and Maximum allowable Length of Cables ...........................................................18
[3] Switch Settings and Address Settings ............................................................................. 19
[4] Sample System Connection............................................................................................. 26
[5] An Example of a System to which an MA Remote Controller is connected..................... 27
[6] An Example of a System to which an M-NET Remote Controller is connected............... 37
[7] An Example of a System to which both MA Remote Controller and M-NET Remote
Controller are connected.................................................................................................. 39
[8] Restrictions on Pipe Length ............................................................................................. 41
HWE08040GB
- 15 -
- 16 -
[ II Restrictions ]
IIRestrictions
[1] System configuration
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
Outdoor
units
Composing unitsMaximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable in-
door units
72 - - - 36 - 9615P06 - P96models
96 - - - 48 - 12420
R410A series indoor units
120 - - - 60 - 15626
1447272 - 72 - 18731
1689672 - 84 - 21836
19212072 - 96 - 24941
21612096 - 108 - 28046
240120120 - 120 - 31250
2641207272132 - 343
2881209672144 - 374
31212012072156 - 405
33612012096168 - 436
360120120120180 - 468
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE08040GB
- 17 -
[ II Restrictions ]
[2] Types and Maximum allowable Length of Cables
1. Wiring work
(1) Notes
1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this manual.
2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference.
(Do not put the control cable and power supply cable in the same conduit tube.)
3) Provide grounding for the outdoor unit as required.
4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing.
5) Do not connect power supply wiring to the terminal block for transmission line. Doing so will damage the electronic components on the terminal block.
6) Use 2-core shielded cables as transmission cables.
Use a separate 2-core control cable for each refrigerant system. Do not use a single multiple-core cable to connect indoor
units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and
malfunctions.
TB
TB
3
7
TB
TB
7
3
Outdoor unit
TB3TB7TB3TB
TB3TB
7
7
2-core shielded cable
TB3TB
7
2-core shielded cable
TB3: Terminal block for indoor-outdoor transmission line TB7: Terminal block for centralized control
Indoor unit
Remote Controller
TB
TB
3
7
TB
TB
7
3
Outdoor unit
TB3TB7TB3TB
TB3TB
7
7
multiple-core cable
TB3TB
7
Indoor unit
Remote Controller
(2) Control wiring
Different types of control wiring are used for different systems.
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System
to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work.
Types and maximum allowable length of cables
Control lines are categorized into 2 types: transmission line and remote controller line.
Use the appropriate type of cables and observe the maximum allowable length specified for a given system. If a given system
has a long transmission line or if a noise source is located near the unit, place the unit away from the noise source to reduce
noise interference.
1) M-NET transmission line
Cable type
Facility
type
TypeShielded cable CVVS, CPEVS, MVVS
Number of
cores
Cable sizeLarger than 1.25mm
All facility types
2-core cable
2
[AWG16]
Maximum transmission
line distance between the
outdoor unit and the far-
200 m [656ft] max.
thest indoor unit
Maximum transmission
line distance for centralized control and Indoor/
outdoor transmission line
(Maximum line distance
500 m [1640ft] max.
*The maximum overall line length from the power supply unit on the transmission lines for
centralized control to each outdoor unit or to the system controller is 200m [656ft] max.
via outdoor unit)
HWE08040GB
- 18 -
[ II Restrictions ]
2) Remote controller wiring
MA remote controller
*1
M-NET remote controller
*2
TypeCVVCVV
Number of
cores
Cable type
Cable size
Maximum overall line
length
2-core cable2-core cable
0.3 to 1.25mm
[AWG22 to 16]
(0.75 to 1.25mm
[AWG18 to 16]
2 *3
2) *4
0.3 to 1.25mm
[AWG22 to 16]
(0.75 to 1.25mm
[AWG18 to 16]
The section of the cable that exceeds 10m
200 m [656ft] max.
[32ft] must be included in the maximum indoor-outdoor transmission line distance.
2 *3
2) *4
*1 MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and
wireless remote controller.
*2 M-NET remote controller refers to ME remote controller and ME simple remote controller.
*3 The use of cables that are smaller than 0.75mm
2
(AWG18) is recommended for easy handling.
*4 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi-
cations shown in the parenthesis.
[3] Switch Settings and Address Settings
1. Switch setting
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System
to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work.
Set the switches while the power is turned off.
If the switch settings are changed while the unit is being powered, those changes will not take effect, and the unit will not
function properly.
Units on which to set the switchesSymbolUnits to which the power must be shut off
*3
CITY MULTI indoor unitMain/sub unitICOutdoor units
LOSSNAY, OA processing unit
*1
LCOutdoor units
Air handling kitICOutdoor units
and Indoor units
*3
and LOSSNAY
*3
or field supplied air handling
unit
M-NET remote controllerMain/sub remote
RCOutdoor units
*3
controller
MA remote controllerMain/sub remote
MAIndoor units
controller
CITY MULTI outdoor unit
*2
OC,OS1,OS2Outdoor units
*3
*1. Applicable when LOSSNAY units are connected to the indoor-outdoor transmission line.
*2. The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of
capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
*3. Turn off the power to all the outdoor units in the same refrigerant circuit.
The need for address settings and the range of address setting depend on the configuration of the system.
Unit or controllerAddress setting
Setting methodFacto-
range
CITY MULTI indoor unit
Main/sub unit00,
01 to 50
*1
Assign the smallest address to the main indoor unit in the
group, and assign sequential address numbers to the rest
of the indoor units in the same group.
*4
M-NET adapter
M-NET control interface
Free Plan adapter
LOSSNAY, OA processing unit
Air handling kit
00,
01 to 50
*1
Assign an arbitrary but unique address to each of
these units after assigning an address to all indoor
units.
M-NET remote
controller
Main remote
controller
Sub remote
controller
101 to 150Add 100 to the smallest address of all the indoor units
in the same group.
151 to 200
*2
Add 150 to the smallest address of all the indoor units
in the same group.
MA remote controllerNo address settings required. (The main/sub setting must be made if 2
remote controllers are connected to the system.)
CITY MULTI outdoor unit00,
51 to 100
System controller Group remote
201 to 250Assign an address that equals the sum of the smallest
controller
System remote
controller
ON/OFF remote controller
Schedule timer
(compatible
*1,*3
Assign sequential addresses to the outdoor units in the
same refrigerant circuit. The outdoor units in the same
refrigerant circuit are automatically designated as OC
and OS.
*5
group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the
range listed on the left to each unit.
Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the
range listed on the left to each unit.
with M-NET)
Central controller
G(B)-50A
000,
201 to 250
Assign an arbitrary but unique address within the
range listed on the left to each unit. The address must
be set to "000" to control the K-control unit.
LM adapter201 to 250Assign an arbitrary but unique address within the
range listed on the left to each unit.
ry set-
ting
00
00
101
Main
00
201
202
000
247
*1. Address setting is not required for a City Multi system that consists of a single refrigerant circuit (with some exceptions).
*2. To set the M-NET remote controller address to "200", set the rotary switches to "00".
*3. To set the outdoor unit address to "100," set the rotary switches to "50."
*4. Some indoor units have 2 or 3 controller boards that require address settings.
No. 2 controller board address must be equal to the sum of the No. 1 controller board address and 1, and the No.3
controller board address must equal to the No. 1 controller address and 2.
*5. The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of
capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
HWE08040GB
- 20 -
[ II Restrictions ]
(2) Power supply switch connector connection on the outdoor unit
(Factory setting: The male power supply switch connector is connected to CN41.)
System configuration
Connection to
the system controller
Power supply unit
for transmission
lines
Group operation
of units in a system with multiple
Power supply switch connector connection
outdoor units
System with
one outdoor unit
System with
multiple outdoor
units
___Leave CN41 as it is
(Factory setting)
Not connected_Not grouped
GroupedDisconnect the male connector from the fe-
With connection
to the indoor
unit system
With connection
to the centralized control
system
Not requiredGrouped/not
grouped
Not required
(Powered from the
*1
Grouped/not
grouped
outdoor unit)
Required *
1
Grouped/not
grouped
male power supply switch connector (CN41)
and connect it to the female power supply
switch connector (CN40) on only one of the
outdoor units.
*Connect the S (shielded) terminal on the ter-
minal block (TB7) on the outdoor unit whose
CN41 was replaced with CN40 to the
ground terminal ( ) on the electric box.
Leave CN41 as it is
(Factory setting)
*2
*1 The need for a power supply unit for transmission lines depends on the system configuration.
*2 The replacement of the power jumper connector from CN41 to CN40 must be performed on only one outdoor unit in the
system.
(3) Settings for the centralized control switch for the outdoor unit (Factory setting: SW2-1 are set to OFF.)
System configurationCentralized control switch settings *
1
Connection to the system controller Not connectedLeave it to OFF. (Factory setting)
Connection to the system controller Connected *
2
ON
*1 Set SW2-1 on all outdoor units in the same refrigerant circuit to the same setting.
*2 When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
(4) Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to "OFF".)
To stop the fan during heating Thermo-OFF (SW1-7 and 1-8 on the indoor units to be set to ON), use the built-in thermistor
on the remote controller or an optional thermistor.
1) To use the built-in sensor on the remote controller, set the SW1-1 to ON.
Some models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
(Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models is ON.
2) When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON.
When using an optional temperature sensor, install it where room temperature can be detected.
(5) Various start-stop controls (Indoor unit settings)
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
Function
Power ON/OFF by
the plug
*1,*2,*3
Automatic restoration
after power failure
Operation of the indoor unit when the operation is resumed after the unit was
stopped
Indoor unit will go into operation regardless of its operation status before power
off (power failure). (In approx. 5 minutes)
Indoor unit will go into operation if it was in operation when the power was
turned off (or cut off due to power failure). (In approx. 5 minutes)
Indoor unit will remain stopped regardless of its operation status before power
Setting (SW1)
910
OFFON
ONOFF
OFFON
off (power failure).
*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the
crankcase heater and may cause the compressor to malfunction when the unit is put back into operation.
*2. Not applicable to units with a built-in drain pump or humidifier.
*3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir-
cuits will be turned on or off by the plug.
*4. Requires that the dipswitch settings for all the units in the group be made.
*5. To control the external input to and output from the air conditioners with the PLC software for general equipment via the
G(B)-50A, set SW1-9 and SW1-10 to ON. With these settings made, the power start-stop function becomes disabled. To
use the auto recovery function after power failure while these settings are made, set SW1-5 to ON.
*4 *5
HWE08040GB
- 21 -
[ II Restrictions ]
(6) Miscellaneous settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.")
When using indoor unit as a cooling-only unit, set SW3-1 to ON.
(7) Various types of control using input-output signal connector on the outdoor unit (various connection options)
TypeUsageFunction
Input Prohibiting cooling/heating operation (thermo OFF) by an external
DEMAND (level)CN3D
input to the outdoor unit.
*It can be used as the DEMAND control device for each system.
Performs a low level noise operation of the outdoor unit by an external input to the outdoor unit.
Low-noise mode
*3*4
(level)
to be
used
*1
*2
Option
Adapter for
external input
(PACSC36NA-E)
Terminal
* It can be used as the silent operation device for each refrigerant
system.
Forces the outdoor unit to perform a fan operation by receiving signals from the snow sensor.
*5
Cooling/heating operation can be changed by an external input to
Snow sensor signal
CN3S
input (level)
Auto-changeoverCN3N
the outdoor unit.
Out-
How to extract signals from the outdoor unit
put
*It can be used as an operation status display device.
*It can be used for an interlock operation with external devices.
Operation status of
the compressor
Error status
*5
*6
CN51Adapter for
external output
(PACSC37SA-E)
*1. For detailed drawing, refer to "Example of wiring connection".
*2. For details, refer to (1) through (4) shown below.
*3. Low-noise mode is valid when Dip SW4-4 on the outdoor unit is set to OFF. When DIP SW4-4 is set to ON, 4 levels of
on-DEMAND are possible, using different configurations of low-noise mode input and DEMAND input settings.When 2
or more outdoor units exist in one refrigerant circuit system, 8 levels of on-DEMAND are possible. When 3 outdoor units
exist in one refrigerant circuitsystem, 12 levels of on-DEMAND are possible.
*4. By setting Dip SW5-5, the Low-noise mode can be switched between the Capacity priority mode and the Low-noise pri-
ority mode.
When SW5-5 is set to ON: The Low-noise mode always remains effective.
When SW5-5 is set to OFF: The Low-noise mode is cancelled when certain outside temperature or pressure criteria are
met, and the unit goes into normal operation (capacity priority mode).
Low-noise mode is effectiveCapacity priority mode becomes effective
CoolingHeatingCoolingHeating
TH7 < 30°C [86°F]
and
63HS1 < 32kg/cm
TH7 > 3°C [37°F]
2
and
63LS > 4.6kg/cm
2
TH7 > 35°C [95°F]
or
63HS1 > 35kg/cm
TH7 < 0°C [32°F]
2
or
63LS < 3.9kg/cm
*5. Each outdoor unit in the system with multiple outdoor units requires the signal input/output setting to be made.
*6. Take out signals from the outdoor unit (OC) if multiple outdoor units exist in a single system.
CAUTION
1) Wiring should be covered by insulation tube with supplementary insulation.
2) Use relays or switches with IEC or equivalent standard.
3) The electric strength between accessible parts and control circuit should have 2750V or more.
Snow sensor : The outdoor fan runs when X is closed
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
in stop mode or thermostat mode.
2. Optional part : PAC-SC36NA-E or field supply.
X
OFF
OFF
Y
ON
X : Cooling / Heating
Y : Validity / Invalidity of X
X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Normal
CoolingONHeating
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
Adapter
2
1
2
3
Maximum cable
length is 10m
Outdoor unit
control board
CN3S
(4) CN3D
Relay circuit
Preparations
in the field
X : Low-noise mode
Y : Compressor ON/OFF
X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Adapter
X
Y
Maximum cable
length is 10m
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC
1
2
3
Outdoor unit
2
control board
CN3D
1
2
Outdoor unit
2
control board
CN3D
Relay circuit
X
Adapter
3
Preparations
in the field
X : Low-noise mode
X : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Maximum cable
length is 10m
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
Low-noise mode : The noise level is reduced by controlling the maximum
fan frequency and maximum compressor frequency.
HWE08040GB
- 23 -
[ II Restrictions ]
1) SW4-4: OFF (Compressor ON/OFF, Low-noise mode)
CN3D 1-3PCompressor ON/OFF
OpenCompressor ON
Short-circuitCompressor OFF
*1
CN3D 1-2PLow-noise mode
*2
OpenOFF
Short-circuitON
*1. When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON , this function cannot be used.
*2. This function and the 4 levels or 8 levels on-DEMAND function can be used together. Input the order to CN3D 1-2P on
the outdoor unit whose SW4-4 is set to OFF.
2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND)
(*3)
CN3D 1-2P
CN3D 1-3POpenShort-circuit
Open100% (No DEMAND)75%
Short-circuit0% (Compressor OFF)50%
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
Note the following steps to be taken when using the STEP DEMAND
(Example) When switching from 100% to 50%
Demand control
steps
If the step listed as the wrong example above is taken, thermo may go off.
The percentage of the demand listed in the table above is an approximate value based on the
compressor volume and does not necessarily correspond with the capacity.
When this function is enabled, the night mode cannot be enabled.
(Wrong)
(Correct)
100%
100%
0%
75%
50%
50%
3) When SW4-4 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND)
*4. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
*5. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.
(*4, *5)
HWE08040GB
- 24 -
[ II Restrictions ]
4) When SW4-4 on the all outdoor units in one refrigerant circuit system is set to ON (12 levels of on-DEMAND)
12 levels
of on-DEMAND
No.2 CN3D1-2POpen
1-3POpenShort-circuit
No.3 CN3D1-2POpenShort-circuitOpenShort-circuit
No.1
CN3D
1-2P1-3POpenShort-
circuit
OpenShort-
circuit
OpenShort-
circuit
OpenShort-
OpenOpen100%67%92%84%67%34%59%50%
Short-
67%34%59%50%34%0%25%17%
circuit
Short-circuitOpen92%59%84%75%59%25%50%42%
Short-
84%50%75%67%50%17%42%34%
circuit
12 levels
of on-DEMAND
No.2 CN3D1-2PShort-circuit
1-3POpenShort-circuit
No.3 CN3D1-2POpenShort-circuitOpenShort-circuit
No.1
CN3D
1-2P1-3POpenShort-
circuit
OpenShort-
circuit
OpenShort-
circuit
OpenShort-
OpenOpen92%59%84%75%84%50%75%67%
Short-
59%25%50%42%50%17%42%34%
circuit
Short-circuitOpen84%50%75%67%75%42%67%59%
Short-
75%42%67%59%67%34%59%50%
circuit
(*4)
circuit
circuit
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
*4. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.
HWE08040GB
- 25 -
[ II Restrictions ]
[4] Sample System Connection
Examples of typical system connection are shown on pages [5] to [7].
Refer to the Installation Manual that came with each device or controller for details.
(1) An example of a system to which an MA remote controller is connected
System
configuration
System with one out-
1.
2.
door unit
System with one out-
door unit
Grouping of units in a
3.
system with multiple
outdoor units
System with one out-
4.
5.
door unit
System with one out-
door unit
Connection to the system controller
NO
NO
NO
With connection to transmission line
for centralized control
With connection to indoor-outdoor
transmission line
Address start up for in-
door and outdoor units
Automatic
address setup
Manual
address setup
Manual
address setup
Manual
address setup
Manual
address setup
Notes
Connection of
multiple LOSSNAY units
(2) An example of a system to which an M-NET remote controller is connected
System
configuration
System with one out-
1.
door unit
Connection to the system controller
With connection to transmission line
for centralized control
Address start up for indoor
and outdoor units
Manual
address setup
Notes
(3) An example of a system to which both MA remote controller and M-NET remote controller are connected
System
configuration
System with one out-
1.
door unit
Connection to the system controller
With connection to transmission
line for centralized control
Address start up for indoor and outdoor units
Manual
address setup
Notes
HWE08040GB
- 26 -
[ II Restrictions ]
[5] An Example of a System to which an MA Remote Controller is connected
1. System with one outdoor unit (automatic address setup for both indoor and outdoor units)
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OS1OS2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
00
TB7
TB3
S
TB3
TB7
M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2
TB3
S
L2L1
Group Group
OC
0000
TB7
S
IC
00
TB5STB
L3 L4
IC
00
15
1 2
m1
TB5STB
15
1 2
Interlock operation with
the ventilation unit
LC
00
TB5
M1M2M1M2M1M2
S
L11
m4
A B
MA
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) A transmission booster is required in a system to which
more than 32 indoor units (26 units if one or more indoor
units of the 72 model or above is connected) are connected.
4) Automatic address setup is not available if start-stop input (CN32, CN51, CN41) is used for a group operation of
indoor units. Refer to "[5] 2. Manual address setup for
both indoor and outdoor units".(page 29)
5) To connect more than 2 LOSSNAY units to indoor units
in the same system, refer to the next section "[5] 2. An
example of a system with one outdoor unit to which 2 or
more LOSSNAY units are connected".(page 29)
A B
MA
L12 L13
GroupGroup
IC
A B
RC
A B
MA
IC
0000
15
TB
TB5
M1M2 M1 M2 M1 M2
S1 2
m5
MA
A B
MA
A B
TB5STB
15
1 2
A B
MA
m2
m3
(3) Maximum allowable length
1) Indoor/outdoor transmission line
2
Maximum distance (1.25mm
[AWG16] or larger)
L1 +L2+L3+L4 200m[656ft]
L1 +L2+L11+L12+L13 200m[656ft]
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Maximum overall line length
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 on the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
units (OC, OS1, OS2) (Note 1), and terminals M1 and M2
on the terminal block for indoor-outdoor transmission line
(TB5) on each indoor unit (IC). (Non-polarized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units
have the same capacity, in the order of address from
small to large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor
units (OC, OS1, OS2), and the S terminal on the terminal
block (TB5) on the indoor unit (IC) with the shield wire of
the shielded cable.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Connect terminals 1 and 2 on the terminal block for MA
remote controller line (TB15) on the indoor unit (IC) to the
terminal block on the MA remote controller (MA). (Nonpolarized two-wire)
When 2 remote controllers are connected to the system
When 2 remote controllers are connected to the system,
connect terminals 1 and 2 of the terminal block (TB15) on
the indoor unit (IC) to the terminal block on the two MA
remote controllers.
Set one of the MA remote controllers to sub. (Refer to
(5) Address setting method
MA remote controller function selection or the installation
manual for the MA remote controller for the setting method.)
Group operation of indoor units
To perform a group operation of indoor units (IC), daisychain terminals 1 and 2 on the terminal block (TB15) on
all indoor units (IC) in the same group, and then connect
terminals 1 and 2 on the terminal block (TB15) on the indoor unit on one end to the terminal block on the MA remote controller. (Non-polarized two-wire)
When performing a group operation of indoor units that
have different functions, "Automatic indoor/outdoor address setup" is not available.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals
on the terminal block (TB5) on LOSSNAY (LC). (Non-polarized two-wire)
Interlock operation setting with all the indoor units in the
same system will automatically be made. (It is required
that the Lossnay unit be turned on before the outdoor
unit.)
Refer to "[5] 2. Manual address setup for both indoor and
outdoor units" in the following cases: performing an interlock operation of part of the indoor units in the system
with a LOSSNAY unit, using LOSSNAY alone without interlocking it with any units, performing an interlock operation of more than 16 indoor units with a LOSSNAY unit,
or connecting two or more LOSSNAY units to indoor
units in the same system.
5) Switch setting
No address settings required.
Proce-
dures
Unit or controller
1Indoor unitMain unitICNo settings re-
Sub unitIC
Address setting
range
quired.
Setting
method
Notes
-To perform a group operation of indoor units that
have different functions,
refer to [5] 2.(page 29)
2LOSSNAYLCNo settings re-
-00
quired.
3MA
remote controller
Main
remote controller
Sub
remote controller
MANo settings re-
quired.
MASub
remote controller
-Main
Settings to
be made according to
the remote
controller
function selection
4Outdoor unit (Note)OC
OS1
No settings required.
-00
OS2
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
Factory
setting
00
- 28 -
GBHWE08040
[ II Restrictions ]
2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected
(manual address setup for both indoor and outdoor units)
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
L1
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
53
TB7
TB3
S
TB3
TB7
M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2
TB3
S
L2
OCOS1OS2
5152
TB7
S
IC
01
TB5STB
M1M2 M1 M2 M1 M2
L3 L4
GroupGroup
IC
02
15
1 2
TB5STB
15
1 2
TB5
Interlock operation with
the ventilation unit
LC
05
S
L11
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) A transmission booster is required in a system to which
more than 32 indoor units (26 units if one or more indoor
units of the 72 model or above is connected) are connected.
A B
MA
L12 L13
Group
IC
A B
MA
IC
0403
TB5
S
15
TB
1 2
A B
MA
TB5STB
15
1 2
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 1.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as [5] 1.
LC
06
TB5
S
M1M2M1M2M1M2
HWE08040GB
29- 29 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 1.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
(5) Address setting method
Proce-
dures
Unit or controller
1Indoor unitMain
IC01 to 50Assign the smallest ad-
Address
setting
unit
Sub unitAssign sequential numbers
2LOSSNAYLC01 to 50Assign an arbitrary but
3MA
remote controller
Main
remote
control-
MANo
settings required.
ler
Sub
remote
control-
MASub
remote
controller
ler
4Outdoor unitOC
51 to 100Assign sequential address
OS1
OS2
range
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals
on the terminal block (TB5) on LOSSNAY (LC). (Non-polarized two-wire)
Interlock setting between the indoor units and LOSS-
NAY units must be entered on the remote controller. (Refer to "IV [3] Interlock Settings via the MA Remote
Controller" or the installation manual for the MA remote
controller for the setting method.)
5) Switch setting
Address setting is required as follows.
Setting methodNotes
To perform a group operadress to the main unit in the
group.
tion of indoor units that
have different functions,
designate the indoor unit
starting with the address of
the main unit in the same
group +1. (Main unit ad-
in the group with the great-
est number of functions as
the main unit.
dress +1, main unit address +2, main unit
address +3, etc.)
None of these addresses
unique address to each of
these units after assigning
may overlap any of the in-
door unit addresses.
an address to all indoor
units.
-Main
Settings to be made according to the remote controller function selection
To set the address to 100,
to the outdoor units in the
same refrigerant circuit.
set the rotary switches to
50.
The outdoor units are automatically designated as
OC, OS1, and OS2.(Note)
Factory
setting
00
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 30 -
GBHWE08040
[ II Restrictions ]
3. Group operation of units in a system with multiple outdoor units
(1) Sample control wiring
L11
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OS2
53
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OS1
52
TB3
Not
connect
TB7
S
S
CN41 CN40 Replace
SW2-1 OFF
Not
connect
TB3
TB7
Group
OC
51
S
Connect
IC
01
15
TB5STB
1 2
M1M2 M1 M2 M1 M2 M1 M2
A B
Interlock operation with
L12
Group
IC
03
15
TB5STB
1 2
m2
A B
the ventilation unit
Group
IC
06
TB5STB
15
1 2
A B
TB5
LC
07
S
L31
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OS2
56
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
S
Not
connect
L21
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
55
TB3
TB7
OS1
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OC
54
Not
connect
TB5
M1M2
TB3
TB7
S
Not
connect
S
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
4) Replacement of male power jumper connector (CN41)
must be performed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for
transmission line for centralized control (TB7) on only
one of the outdoor units.
6) A transmission booster is required in a system to which
more than 32 indoor units (26 units if one or more indoor
units of the 72 model or above is connected) are connected.
MA
m3
L22
IC
15
TB
S
1 2
Group
MA
IC
0402
15
TB5STB
1 2 1 2
A B
MA
MA
IC
05
TB5 TB15
S
M1M2M1M2
(3) Maximum allowable length
1) Indoor/outdoor transmission line
2
Maximum distance (1.25mm
[AWG16] or larger)
L11+L12 200m [656ft]
L21+L22 200m [656ft]
2) Transmission line for centralized control
Maximum line distance via outdoor unit
1) Indoor/outdoor transmission line
Same as [5] 1.
Only use shielded cables.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block
3) MA remote controller wiring
for transmission line for centralized control (TB7) on the
outdoor units (OC) in different refrigerant circuits and on
the OC, OS1, and OS2 in the same refrigerant circuit
If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the control board from CN41 to CN40 on
only one of the outdoor units.
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the or-
4) LOSSNAY connection
5) Switch setting
der of capacity from large to small (if two or more units
have the same capacity, in the order of address from
small to large).
(5) Address setting method
Proce-
dures
1Indoor
Unit or controller
Main unitIC01 to 50Assign the smallest ad-
unit
Address setting
range
dress to the main unit in
the group.
Sub unitAssign sequential num-
bers starting with the address of the main unit in
the same group +1. (Main
unit address +1, main unit
address +2, main unit address +3, etc.)
2LOSSNAYLC01 to 50Assign an arbitrary but
unique address to each of
these units after assigning
an address to all indoor
units.
3MA
remote
controller
Main
remote
controller
Sub
remote
controller
4Outdoor unitOC
MANo
settings required.
MASub
remote controller
Settings to be made according to the remote controller function selection
51 to 100Assign sequential address
OS1
OS2
to the outdoor units in the
same refrigerant circuit.
The outdoor units are automatically designated as
OC, OS1, and OS2.
(Note)
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on
the outdoor units (OC, OS1, OS2) with the shield wire of
the shielded cable. Short-circuit the earth terminal ( )
and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with
CN40.
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 2.
Same as [5] 2.
Address setting is required as follows.
Setting methodNotes
To perform a group
Factory
setting
00
operation of indoor
units that have different functions, designate the indoor unit in
the group with the
greatest number of
functions as the main
unit.
None of these ad-
00
dresses may overlap
any of the indoor unit
addresses.
-Main
To set the address to
00
100, set the rotary
switches to 50.
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 32 -
GBHWE08040
[ II Restrictions ]
4. A system in which a system controller is connected to the transmission line for centralized control and which is powered from an outdoor unit
(1) Sample control wiring
Interlock operation with
15
1 2
the ventilation unit
IC
03
TB5STB
1 2
LC
07
TB5
15
S
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS2
53
TB3
M1 M2 M1 M2 M1 M2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS1
52
TB3
CN41 CN40 Replace
SW2-1 OFF ON
OC
51
TB3
L12L11
Group Group Group
IC
01
15
TB5STB
1 2
M1 M2 M1 M2 M1 M2 M1 M2
IC
02
TB5STB
L31
TB7
S
M1 M2 M1 M2 M1 M2
Not
connect
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS2
56
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
S
Not
connect
TB7
S
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS1
55
TB3
TB7
S
Not
connect
Not
connect
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
TB7
S
Connect
OC
54
TB3
TB7
S
Not
connect
System controller
A B S
L32
TB5
Note1
A B
MA
L22L21
IC
15
TB
S
1 2
A B
MA
TB5STB
m2m1
m3
Note1 When only the LM adapter is connected,
leave SW2-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 208/230V.
A B
MA
IC
GroupGroup
0504
15
1 2
IC
06
TB5STB
15
1 2
A B
MA
A B
MA
LC
08
TB5
M1 M2 M1 M2 M1 M2 M1 M2
S
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
4) Replacement of male power jumper connector (CN41)
must be performed only on one of the outdoor units.
5) Short-circuit the shield terminal (S terminal) and the
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Maximum line distance via outdoor unit
earth terminal ( ) on the terminal block for transmission
line for centralized control (TB7) on the outdoor unit
whose power jumper connector is mated with CN40.
6) A transmission booster is required in a system to which
more than 32 indoor units (26 units if one or more indoor
units of the 72 model or above is connected) are connected.
7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
HWE08040GB
33- 33 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 1.
Only use shielded cables.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control
Daisy-chain terminals A and B on the system controller,
terminals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on the outdoor
units (OC) in different refrigerant circuits and on the outdoor units (OC, OS1, and OS2) in the same refrigerant
circuit.
If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the control board from CN41 to CN40 on
only one of the outdoor units.
If a system controller is connected, set the central control
switch (SW2-1) on the control board of all outdoor units
to "ON."
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units
have the same capacity, in the order of address from
small to large).
Only use shielded cables.
(5) Address setting method
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on
the outdoor units (OC, OS1, OS2) with the shield wire of
the shielded cable. Short-circuit the earth terminal ( )
and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with
CN40.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals
on the terminal block for indoor-outdoor transmission line
(TB5) on LOSSNAY (LC). (Non-polarized 2-core cable)
Indoor units must be interlocked with the LOSSNAY unit
using the system controller. (Refer to the operation manual for the system controller for the setting method.) Interlock setting from the remote controller is required if the
ON/OFF remote controller alone or the LM adapter alone
is connected.
5) Switch setting
Address setting is required as follows.
Proce-
dures
Unit or controller
Address
setting
range
Setting methodNotes
1Indoor unitMain unit IC01 to 50Assign the smallest ad-
dress to the main unit in
the group.
Sub unitAssign sequential num-
bers starting with the address of the main unit in
the same group +1. (Main
unit address +1, main unit
address +2, main unit address +3, etc.)
2LOSSNAYLC01 to 50Assign an arbitrary but
unique address to each of
these units after assigning an address to all indoor units.
3MA
remote controller
Main
remote
control-
MANo
settings required.
-Enter the same indoor
ler
Sub
remote
controller
4Outdoor unitOC
MASub
remote controller
51 to 100Assign sequential adOS1
OS2
Settings to be made according to the remote
controller function selection
dress to the outdoor units
in the same refrigerant
circuit.
The outdoor units are automatically designated as
OC, OS1, and
OS2.(Note)
To perform a group operation of indoor units that
have different functions,
designate the indoor unit
in the group with the
greatest number of functions as the main unit.
None of these addresses
may overlap any of the indoor unit addresses.
unit group settings on the
system controller as the
ones that were entered
on the MA remote controller.
To set the address to
100, set the rotary switches to 50.
Factory
setting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 34 -
GBHWE08040
[ II Restrictions ]
5. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except
LM adapter)
(1) Sample control wiring
Interlock operation with
15
1 2
the ventilation unit
IC
03
TB5STB
15
1 2
TB5
LC
07
S
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS2
53
TB3
M1 M2 M1 M2 M1 M2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS1
52
TB3
CN41 CN40 Replace
SW2-1 OFF ON
51
TB3
L12L11
OC
Group Group Group
IC
01
15
TB5STB
M1 M2 M1 M2 M1 M2 M1 M2
1 2
IC
02
TB5STB
L31
TB7
S
M1 M2 M1 M2 M1 M2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS2
Not
connect
56
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
S
Not
connect
TB7
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS1
55
TB3
TB7
S
Not
connect
S
Not
connect
TB7
S
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OC
54
TB3
TB7
S
Not
connect
Connect
L25
System controller
TB5
A B S
A B
MA
L22L21
IC
m2m1
m3
TB5STB
M1 M2 M1 M2
15
TB
1 2
S
A B
MA
Note1
A B
MA
IC
GroupGroup
0504
15
1 2
M1 M2
IC
06
TB5STB
15
1 2
A B
MA
A B
MA
TB5
M1 M2
LC
08
S
Note1 LM adapters cannot be connected to the
indoor-outdoor transmission line.
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
4) Replacement of male power jumper connector (CN41)
must be performed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for
transmission line for centralized control (TB7) on only
one of the outdoor units.
2) Transmission line for centralized control
Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger)
L25+L31+L12(L11) 500m [1640ft]
L12(L11)+L31+L22(L21) 500m [1640ft]
3) MA remote controller wiring
Same as [5] 1.
6) A maximum of 3 system controllers can be connected to
the indoor-outdoor transmission line, with the exception
that only one G(B)-50A may be connected.
7) When the total number of indoor units exceeds 26, it may
not be possible to connect a system controller on the indoor-outdoor transmission line.
8) In a system to which more than 18 indoor units including
one or more indoor units of 72 model or above are connected, there may be cases in which the system controller cannot be connected to the indoor-outdoor
transmission line.
HWE08040GB
35- 35 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 on the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
units (OC, OS1, OS2) (Note 1), terminals M1 and M2 on
the terminal block for indoor-outdoor transmission line
(TB5) on each indoor unit (IC), and the S terminal on the
system controller. (Non-polarized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units
have the same capacity, in the order of address from
small to large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor
units (OC, OS1, OS2), the S terminal on the terminal
block (TB5) on the indoor unit (IC), and the S terminal on
the system controller with the shield wire of the shielded
cable.
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block
for transmission line for centralized control (TB7) on the
outdoor units (OC) in different refrigerant circuits and on
the OC, OS1, and OS2 in the same refrigerant circuit.
If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the control board from CN41 to CN40 on
only one of the outdoor units.
(5) Address setting method
Set the central control switch (SW2-1) on the control
board of all outdoor units to "ON."
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on
the outdoor units (OC, OS1, OS2) with the shield wire of
the shielded cable. Short-circuit the earth terminal ( )
and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with
CN40.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor units (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-polarized twowire)
Indoor units must be interlocked with the LOSSNAY unit
using the system controller. (Refer to the operation manual for the system controller for the setting method.) Interlock setting from the remote controller is required if the
ON/OFF remote controller alone is connected.
5) Switch setting
Address setting is required as follows.
Proce-
dures
1Indoor
Unit or controller
Main unit IC01 to 50Assign the smallest address
unit
Address set-
ting range
Setting methodNotes
to the main unit in the group.
Sub unitAssign sequential numbers
starting with the address of
the main unit in the same
group +1. (Main unit address
+1, main unit address +2,
main unit address +3, etc.)
2LOSSNAYLC01 to 50Assign an arbitrary but
unique address to each of
these units after assigning an
address to all indoor units.
3MA
remote
controller
4Outdoor unitOC
Main
remote
controller
Sub
remote
controller
MANo
settings required.
MASub
remote controller
Settings to be made according to the remote controller
function selection
51 to 100Assign sequential address to
OS1
OS2
the outdoor units in the same
refrigerant circuit.
-Enter the same indoor unit
The outdoor units are automatically designated as OC,
OS1, and OS2. (Note)
To perform a group operation of indoor units that have
different functions, designate the indoor unit in the
group with the greatest
number of functions as the
main unit.
None of these addresses
may overlap any of the indoor unit addresses.
group settings on the system controller as the ones
that were entered on the MA
remote controller.
To set the address to 100,
set the rotary switches to 50.
Factory
setting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 36 -
GBHWE08040
[ II Restrictions ]
[6] An Example of a System to which an M-NET Remote Controller is connected
(1) Sample control wiring
Interlock operation with
1 2
15
the ventilation unit
GroupGroupGroup
IC
03
TB5STB
15
1 2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS2
53
TB3
M1 M2 M1 M2 M1 M2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS1
52
TB3
CN41 CN40 Replace
SW2-1 OFF ON
OC
51
TB3
L12L11
IC
01
15
TB5STB
M1 M2 M1 M2 M1 M2 M1 M2
1 2
IC
02
TB5STB
TB5
LC
07
S
TB7
S
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OC
54
TB3
TB7
S
Not
connect
System controller
Connect
A B S
m1
A B
101
RC
Group
TB5
m3
A B
A B
154
L32
104
RC
RC
Note1
A B
102
RC
L22L21
IC
IC
Group
A B
103
RC
0504
15
TB5STB
15
TB
S
1 2
m2
Note1 When only the LM adapter is connected,
leave SW2-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 208/230V.
1 2
TB5STB
A B
106
RC
IC
06
15
1 2
LC
08
TB5
M1 M2 M1 M2 M1 M2 M1 M2
S
Not
connect
Not
connect
TB7
S
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS1
55
TB3
TB7
S
Not
connect
Not
connect
TB7
S
M1 M2 M1 M2 M1 M2
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
L31
OS2
56
TB3
M1 M2 M1 M2 M1 M2
TB7
M1 M2 M1 M2 M1 M2
S
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 3 M-NET remote controllers can be connected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
4) Replace the power jumper connector of the control board
from CN41 to CN40 on only one of the outdoor units.
5) Provide an electrical path to ground for the S terminal on
the terminal block for centralized control on only one of
the outdoor units.
6) A transmission booster must be connected to a system
in which the total number of connected indoor units exceeds 20.
7) A transmission booster is required in a system to which
more than 16 indoor including one or more indoor units
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Same as [5] 4.
3) M-NET remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16])
m1 10m [32ft]
m2+m3 10m [32ft]
If the standard-supplied cable must be extended, use a
cable with a diameter of 1.25mm
2
[AWG16]. The section
of the cable that exceeds 10m [32ft] must be included in
the maximum indoor-outdoor transmission line distance
described in (1).
When connected to the terminal block on the Simple remote controller, use cables that meet the following cable
size specifications: 0.75 - 1.25 mm
2
[AWG18-14].
of the 72 model or above are connected.
8) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
HWE08040GB
37- 37 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 3.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control
Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3) M-NET remote controller wiring
M-NET remote controller is connectable anywhere on
the indoor-outdoor transmission line.
(5) Address setting method
Proce-
dures
1Indoor
Unit or controller
Main unitIC01 to 50Assign the smallest ad-
unit
Sub unitAssign sequential num-
2LOSSNAYLC01 to 50Assign an arbitrary but
3M-NET
remote
controller
Main
remote
controller
Sub
RC101 to 150Add 100 to the main unit
RC151 to 200Add 150 to the main unit
remote
controller
4Outdoor unitOC
51 to 100Assign sequential adOS1
OS2
Address setting
range
When 2 remote controllers are connected to the system
Refer to the section on Switch Setting.
Performing a group operation (including the group
operation of units in different refrigerant circuits).
Refer to the section on Switch Setting.
4) LOSSNAY connection
Same as [5] 4.
5) Switch setting
Address setting is required as follows.
Setting methodNotes
To perform a group
dress to the main unit in
the group.
operation of indoor
units that have differ-
ent functions, desig-
bers starting with the address of the main unit in
the same group +1.
(Main unit address +1,
main unit address +2,
nate the indoor unit in
the group with the
greatest number of
functions as the main
unit.
main unit address +3,
etc.)
None of these adunique address to each
of these units after assigning an address to all
dresses may overlap
any of the indoor unit
addresses.
indoor units.
It is not necessary to
address in the group
set the 100s digit.
To set the address
to 200, set the rota-
address in the group
ry switches to 00.
To set the address to
dress to the outdoor
units in the same refrig-
100, set the rotary
switches to 50.
erant circuit. The outdoor units are
automatically designated as OC, OS1, and
OS2. (Note)
Factory
setting
00
00
101
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 38 -
GBHWE08040
[ II Restrictions ]
[7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
TB3
M1 M2 M1 M2 M1 M2
L11 L12
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
TB3
CN41 CN40 Replace
SW2-1 OFF ON
OCOS1OS2
515253
TB3
Group Group
IC
01
TB5 TB
M1 M2
S
15
1 2
TB5 TB
M1 M2
IC
02
15
1 2
S
TB5 TB
M1 M2
IC
06
15
1 2
S
Not
connect
Not
connect
TB7
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OC
54
TB3
TB7
S
S
Not
connect
System controller
A B S
TB7
M1 M2 M1 M2 M1 M2
S
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
L31
OS2
56
TB3
M1 M2 M1 M2 M1 M2
TB7
S
M1 M2 M1 M2 M1 M2
TB7
Not
connect
Not
connect
S
L21 L22
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS1
55
TB3
TB7
S
(2) Cautions
1) Be sure to connect a system controller.
2) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote
controller addresses that are smaller than those of the indoor units that are connected to the M-NET remote controller.
4) No more than 2 M-NET remote controllers can be connected to a group of indoor units.
5) No more than 2 MA remote controllers can be connected
to a group of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
7) Replace the power jumper connector of the control board
from CN41 to CN40 on only one of the outdoor units.
8) Provide an electrical path to ground for the S terminal on
the terminal block for centralized control on only one of
the outdoor units.
9) A transmission booster must be connected to a system
in which the total number of connected indoor units exceeds 20.
10) A transmission booster is required in a system to which
more than 16 indoor including one or more indoor units
of the 72 model or above are connected.
11) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
Connect
L32
Note1
TB5
M1 M2
A B
MA
IC
GroupGroup
IC
0403
15
TB
S
1 2
A B
MA
TB5 TB
M1 M2
S
1 2
A B
104
RC
Note1 When only the LM adapter is connected,
leave SW2-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 208/230V.
A B
106
RC
IC
05
15
TB5 TB
M1 M2
S
15
1 2
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Same as [5] 4.
3) MA remote controller wiring
Same as [5] 1.
4) M-NET remote controller wiring
Same as [5] 1.
HWE08040GB
39- 39 -
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 3.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control
Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
(5) Address setting method
Proce-
dures
1Opera-
tion
with the
MA re-
Unit or controller
In-
Main unitIC01 to 50
door
unit
Sub unit
mote
controller
MA
remote
controller
Main re-
mote con-
troller
Sub
remote
MANo
MASub
controller
2Opera-
tion
with the
Indoor
unit
M-NET
remote
Main unitIC01 to 50Assign the smallest ad-
Sub unit
controller
MNET
remote
controller
Main re-
mote con-
troller
Sub
remote
controller
RC101 to
RC151 to
3LOSSNAYLC01 to 50
4Outdoor unitOC
OS1
OS2
Address
setting
range
settings
required.
remote
controller
150
200
51 to 100
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) M-NET remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
5) LOSSNAY connection
Same as [5] 4.
6) Switch setting
Address setting is required as follows.
Setting methodNotes
Assign the smallest address
to the main unit in the group.
Assign sequential numbers starting with the address of the main unit in
the same group +1. (Main
unit address +1, main unit
address +2, main unit address +3, etc.)
-
Settings to be made according to the remote
controller function selection
dress to the main unit in
the group.
Assign sequential numbers starting with the address of the main unit in
the same group +1. (Main
unit address +1, main unit
address +2, main unit address +3, etc.)
Add 100 to the main unit
address in the group.
Add 150 to the main unit
Assign an address smaller
than that of the indoor unit that
is connected to the M-NET remote controller.
Enter the same indoor unit
group settings on the system
controller as the ones that
were entered on the MA remote controller.
To perform a group operation
of indoor units that have different functions, designate the
indoor unit in the group with
the greatest number of functions as the main unit.
Enter the indoor unit group set-
tings on the system controller
(MELANS).
Assign an address larger than
those of the indoor units that
are connected to the MA remote controller.
To perform a group operation
of indoor units that have different functions, designate the
indoor unit in the group with
the greatest number of functions as the main unit.
It is not necessary to set
the 100s digit.
To set the address to 200,
set the rotary switches to
00.
address in the group.
Assign an arbitrary but
unique address to each of
these units after assigning an address to all indoor units.
Assign sequential address to the outdoor units
in the same refrigerantcircuit. The outdoor units
are automatically designated as OC, OS1, and
OS2.(Note)
None of these addresses
may overlap any of the indoor unit addresses.
To set the address to 100,
set the rotary switches to 50.
Factory
setting
00
Main
00
101
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
- 40 -
GBHWE08040
[ II Restrictions ]
[8] Restrictions on Pipe Length
(1) End branching
P72 - P120 models
Outdoor unit
A
D
First branch
(Branch joint)
B
Branch joint
(Outdoor unit above indoor unit)
(Outdoor unit below indoor unit)
'
H
H
C
a
Indoor Indoor Indoor
1
L
d
Indoor Indoor Indoor
b
2
c
3
4
OperationPipe sections
LengthTotal pipe lengthA+B+C+D
+a+b+c+d+e+f
Height
difference
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
Total pipe length from the first branch to the farthest indoor unit ( )
Between indoor and
outdoor units
Outdoor unit above indoor unit
Outdoor unit below in-
A+B+C+c or
A+D+f
B+C+c or
D+f
H50 [164] or less
H'40 [131] or less
door unit
Between indoor unitsh15 [49] or less
Branch header
cap
e
5
f
6
h
Allowable length of
pipes
1000 [3280] or less
165 [541] or less
(Equivalent length 190
[623] or less)
40 [131] or less
Unit: m [ft]
HWE08040GB
- 41 -
[ II Restrictions ]
P144 - P360 models
The figure shows a system with three outdoor units. (P264-P360 models)
Note1 Install the pipe that connects the branch pipe and the outdoor units in
the way that it has a downward inclination toward the branch pipe.
Provide a trap on the pipe (gas pipe only) within 2 m from the
joint pipe if the total length of the pipe that connects the joint
pipe and the outdoor unit exceeds 2 m.
h2
BDA
C
Second gas refrigerant distributor
Second liquid refrigerant distributor
First liquid refrigerant distributor
First gas refrigerant distributor
H
First branch
h1
Downward inclination
Upward inclination
L
To indoor unit
To indoor unit
(Note)
EFGI
a
Indoor Indoor Indoor Indoor
JKM
e
Indoor Indoor Indoor Indoor
5
c
b
d
E
3
21
g
f
6
4
i
7
8
Note : "Total sum of downstream unit model numbers"
in the table is the sum of the model numbers
of the units after point E in the figure.
OperationPipe sections
2m [6ft]
2m [6ft] Max.
To indoor unit
Joint pipe
Trap
(gas pipe
only)
To downstream units
Allowable length of
To indoor unit
Joint pipe
pipes
LengthBetween outdoor unitsA+B+C+D10 [32] or less
Total pipe lengthA+B+C+D+E+F+G+I+J
1000 [3280] or less
+K+M+a+b+c+d+e+f+g
+i
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
Total pipe length from the first branch to the far-
A(B)+C+E+J+K+M+i
G+I+J+i40 [131] or less
165 [541] or less
(Equivalent length 190
[623] or less)
thest indoor unit ( )
Height
difference
Between indoor and outdoor unitsH50 [164] or less
(40 [131] or below if
outdoor unit is below in-
door unit)
Between indoor unitsh115 [49] or less
Between outdoor unitsh20.1[0.3] or less
Unit: m [ft]
HWE08040GB
- 42 -
[ II Restrictions ]
1. Refrigerant pipe size
(1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdoor unit pipe size)
Control box houses high-voltage parts.
When opening or closing the front panel of the control box, do not let it come into contact with any of
the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes,
and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less.
(It takes about 10 minutes to discharge electricity after the power supply is turned off.)
1. PUHY-P72, P96THMU-A
DC reactor (DCL)
Electromagnetic relay(72C)
Rush current
protection resistor
(R1) Note.2
Noise filter
Note.2
Terminal block for
power supply
(TB1)
Note.1
Ground terminal
Fan board
INV board
Smoothing capacitor(C1)
Control board
M-NET board
Terminal block for transmission line
(TB3, TB7)
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the waterproof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
HWE08040GB
- 49 -
[ III Outdoor Unit Components ]
2. PUHY-P120THMU-A
DC reactor (DCL)
Electromagnetic relay
(72C)
Diode stack
Noise filter
Current sensor
(ACCT3)
Current sensor
(DCCT1)
Terminal block for
power supply
(TB1)
Ground terminal
Smoothing capacitor(C1)
3. PUHY-P72, P96, P120YHMU-A
Note.2
Note.1
Fan board
Current sensor
(ACCT2)
INV boardControl board
IPM
Current sensor
(ACCT1)
Terminal block for transmission line
(TB3, TB7)
M-NET board
Electromagnetic relay(72C)
DC reactor (DCL)
Noise filter
Terminal block for
power supply
(TB1)
Fuse(F4)
Capacitor(C100)
Rush current protection resistor
(R1,R5) Note.2
Fan board
Control board
M-NET board
Fuse(F5)
Ground
terminal
Note.1
INV board
Terminal block for transmission line
(TB3, TB7)
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the waterproof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
HWE08040GB
- 50 -
[ III Outdoor Unit Components ]
4. Transformer Box (PUHY-P72, P96, P120YHMU-A)
Transformer
(T03)
Transformer
(T02)
HWE08040GB
- 51 -
[ III Outdoor Unit Components ]
[3] Outdoor Unit Circuit Board
1. Outdoor unit control board
CNAC2
L1
L2
CN505
72C driving output
(THMU)
CN51
Output 12VDC
Compressor
ON/OFF output
Error output
Actuator
driving output
CN72
72C driving output
(YHMU)
CNDC
Bus voltage input
P
N
CN2
Serial communication signal input
INV board
GND
Output 17VDC
CN801
Pressure switch
connection
CN332
Output 18VDC
GND
(Fan board)
CN4
GND
Serial communication signal output
LEV
driving output
LED1
Service LED
SWU1,2
Address switch
SW1-5
switch
Dip
Sensor
input
LED3
Lit when powered
LED2
Lit during normal
CPU operation
HWE08040GB
CNAC
L1
L2
LED3
Lit
when powered
F01
Fuse
250V AC/3.15A
External signal input (contact input)
CN102
Power supply input for centralized control system (30VDC)
Indoor/outdoor transmission line input/output (30VDC)
- 52 -
CN41
Power supply for
CN40
centralized control OFF
Power supply for
centralized control ON
CNVCC2
Output 12VDC
Output 5VDC
CNIT
Output 12VDC
GND
Output 5VDC
Power supply detection input
Power supply ON/OFF signal output
CNS2
Transmission line input/output
for centralized control system (30VDC)
GND
[ III Outdoor Unit Components ]
2. M-NET board
(THMU only)
F01
250V
3.15A
Grounding
CN03(THMU only)
Bus voltage input
P
N
CN04
Bus voltage input
(YHMU only)
Bus voltage output
(THMU only)
P
N
CN102
Power supply output for centralized
control system (30VDC)
Indoor/outdoor transmission line
input/output (30VDC)
Grounding
Grounding
TB3
Indoor/outdoor transmission block
Ground terminal for
transmission line
CNS2
Transmission line
input/output for
centralized control
system (30VDC)
TB7
Terminal block for
transmission line for
centralized control
CNIT
Input 12VDC
GND
Input 5VDC
Power supply
detection output
Power supply
ON/OFF signal input
LED1
Power supply for
indoor
transmission line
TP1,2
Check pins for
indoor/outdoor
transmission line
HWE08040GB
- 53 -
[ III Outdoor Unit Components ]
3. INV board
(1) PUHY-P72, P96THMU-A
SC-P1
Rectifier diode output (P)
C30,31,32
Smoothing capacitor
RSH1,2
Overcurrent detection
resistor
CN6
Open: No-load operation setting
Short-circuited: Normal setting
IGBT
(Rear)
CN5V
GND
Output 5VDC
LED1
Lit: Inverter in normal operation
Blink: Inverter error
CN4
GND
Serial communication signal output
CNDC
Bus voltage output
P
N
(INV Boar)
CN2
S
erial communication signal output
SC-P2
Bus voltage Input(
TB-P(Note)
Bus voltage output(P
P)
)
TB-N(Note)
Bus voltage output
(N)
SC-T
Input(L3)
CT3
Current sensor(
L3)
SC-S
Input(L2)
SC-R
Input(L1)
CT12
Current sensor
CT22
Current sensor
(U)
SC-U
Inverter output(U)
GND
Input 17VDC
SC-V
Inverter output(V)
SC-W
Inverter output(W)
(W)
Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
HWE08040GB
- 54 -
[ III Outdoor Unit Components ]
(2) PUHY-P120THMU-A
CNCT2
Current (AC) sensor input
ACCT1
ACCT2
CNCT
Current (DC) sensor input
FT-N(Note)
BUS voltage output
SC-P1
Bus voltage input/output(P)
(N)
IPM-P
BUS voltage output
(IPM input)
CNTH
Thermistor input
(THHS)
CNTYP
Function setting input
(Z26)
(P)
IPM-N
BUS voltage input/output(N)
(IPM input)
CNCT3
Current (AC) sensor input
(ACCT3)
LED1
Inverter in
normal operation
CNIPM
IPM driving power supply output
and signal output
IPM error signal input (IPM output)
CNDC1
BUS voltage output
P
N
LED2
Inverter error
LED4
Lit during normal
CPU operation
SW1
ON: No-load operation setting
OFF: Normal setting
: Fixed to OFF
CN5V
GND
Output 5VDC
CN2
Serial communication
signal output
GND
Output 17VDC
CN4
GND
(Fan board)
Serial communication
signal input
LED3
Lit while charging
CNFG
Functional earth
F02
Fuse
250VAC 3.15A
CNDC2
BUS voltage input
P
N
CNDC3
BUS voltage output
P
N
Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the terminals to remove them.
HWE08040GB
- 55 -
[ III Outdoor Unit Components ]
(3) PUHY-P72, P96, P120YHMU-A
Bus voltage check
terminal (P)
Note
IGBT
(Rear)
CN1
Bus voltage output
N
P
Bus voltage check
terminal (N)
Note 1
SC-L1
Input(L1)
SC-L2
Input(L2)
SC-P1
SC-P2
Bus voltage Input(P)
Rectifier diode output (P)
CN6
Open: No-load operation setting
LED1
Lit: Inverter in normal operation
Blink: Inverter error
Short-circuited: Normal setting
CN5V
GND
Output 5VDC
RSH1
Overcurrent detection
resistor
CN4
GND
CNTYP Inverter
board type
SC-V
Inverter output(V)
SC-W
Inverter output(W)
SC-U
Inverter output(U)
(INV Board)
Serial communication
signal output
CN2
S
erial communication
signal output
GND
Input 17VDC
SC-L3
Input(L3)
CT22
Current sensor(W)
CT3
Current sensor(L3)
CT12
Current sensor(U)
C30 C37
Smoothing capacitor
1) Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less.
(It takes about 10 minutes to discharge electricity after the power supply is turned off.)
HWE08040GB
- 56 -
[ III Outdoor Unit Components ]
4. Fan board
(1) PUHY-P72, P96, P120THMU-A
CNVDC
Bus voltage input
NP
F01
Fuse
250VAC 15A
LED3
Lit during normal
CPU operation
CN18V
Input 18VDC GND
CN4
GNDSerial communication signal output GND(Control board)Serial communication signal output
CN22
GND(INV board)Input 5VDC
Serial communication signal input
GND(INV board)Input 17VDC
CN21
Serial communication signal output
GND(INV board)Input 17VDC
THBOX
Thermistor
(Control box internal temperature
detection)
LED1
Inverter in normal operation
LED2
Inverter error
R630
Overcurrent detection
resistor
HWE08040GB
CNINV
Inverter output
WVU
DIP IPM(Rear)
- 57 -
[ III Outdoor Unit Components ]
(2) PUHY-P72, P96, P120YHMU-A
CNVDC
Bus voltage input
N
P
CNINV
Inverter output
W
V
U
R630,R631
Overcurrent detection
resistor
DIP IPM Rear
CN18V
Input 18VDC
GND
LED3
Lit during normal
CPU operation
CN4
GND
Serial communication signal output
CN5
GND(Control board)
Serial communication signal output
CN21
Serial communication signal output
GND(INV board)
Input 17VDC
CN22
GND(INV board)
Input 5VDC
Serial communication signal input
GND(INV board)
Output 17VDC
THBOX
Thermistor
(Control box internal temperature
detection)
LED1
Inverter in normal operation
LED2
Inverter error
HWE08040GB
- 58 -
[ III Outdoor Unit Components ]
5. Noise Filter
(1) PUHY-P72, P96THMU-A
F2
Fuse
250VAC 6.3A
F1
Fuse
250VAC 6.3A
Grounding
TB21
Input/output(L1)
CN02
Output
L1L2
TB22
Input/output(L2)
TB23
Input/output(L3)
CN01
Input
L3L2L1
HWE08040GB
- 59 -
[ III Outdoor Unit Components ]
(2) PUHY-P120THMU-A
R1,2
Rush current
protection resistor
F3
Fuse
250VAC 6.3A
Grounding
CN02
Output
L1L2
F1
Fuse
250VAC 6.3A
F2
Fuse
250VAC 6.3A
TB42
Bus voltage output(N)
TB31
Bus voltage output(P)
CN03
72C drive input
Electromagnetic relay
(72C)
Diode stack rectified voltage
input (Diode stack output)
Output
(Diode stack input)
TB23
Input
(L3)
TB22
Input
(L2)
TB21
Input
(L1)
CN01
Input
L3L2L1
HWE08040GB
- 60 -
[ III Outdoor Unit Components ]
(3) PUHY-P72, P96, P120YHMU-A
CN4
Output
(Rectified L2-L3 current)
P
N
CN2
Surge absorber circuit
Surge absorber circuit
Short circuit
Short circuit
F1,F2,F3,F4
Fuse
250VAC 6.3A
Grounding
CN1A
Input
L1
CN5
Output
(Rectified L2-L3 current)
P
N
CN6
Input
L2
L3
Grounding
CN1B
Input
L3
L2
HWE08040GB
TB21
Input/output(L1)
TB22
Input/output(L2)
- 61 -
TB23
Input/output(L3)
[ III Outdoor Unit Components ]
HWE08040GB
- 62 -
IV
Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers ................................... 65
[2] Group Settings and Interlock Settings via the ME Remote Controller .............................66
[3] Interlock Settings via the MA Remote Controller ............................................................. 70
[4] Using the built-in Temperature Sensor on the Remote Controller ...................................71
HWE08040GB
- 63 -
- 64 -
[ IV Remote Controller ]
IV Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers
There are two types of remote controllers: M-NET (ME) remote controller, which is connected on the indoor-outdoor
transmission line, and MA remote controller, which is connected to each indoor unit.
1. Comparison of functions and specifications between MA and ME remote controllers
Functions/specificationsMA remote controller
*1*2
M-NET (ME) remote controller
*2*3
Remote controller address settings Not requiredRequired
Indoor/outdoor unit address settings
Not required (required only by a system
with one outdoor unit)
*4
Wiring methodNon-polarized 2-core cable
Required
Non-polarized 2-core cable
To perform a group operation, daisy-
chain the indoor units using non-polarized 2-core cables.
Remote controller connectionConnectable to any indoor unit in the
group
Interlock with the ventilation unitEach indoor unit can individually be in-
terlocked with a ventilation unit. (Set up
via remote controller in the group.)
Changes to be made upon grouping change
MA remote controller wiring between indoor units requires rewiring.
Connectable anywhere on the indoor-outdoor transmission line
Each indoor unit can individually be interlocked with a ventilation unit. (Set up via
remote controller.)
Either the indoor unit address and remote
controller address must both be changed,
or the registration information must be
changed via MELANS.
*1. MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and wire-
less remote controller.
*2. Either the MA remote controller or the M-NET remote controller can be connected when a group operation of units in a
system with multiple outdoor units is conducted or when a system controller is connected.
*3. M-NET remote controller refers to ME remote controller and ME simple remote controller.
*4. Depending on the system configuration, some systems with one outdoor unit may require address settings.
2. Remote controller selection criteria
MA remote controller and M-NET remote controller have different functions and characteristics. Choose the one that better
suits the requirements of a given system. Use the following criteria as a reference.
MA remote controller
*1*2
There is little likelihood of system expansion and group-
ing changes.
Grouping (floor plan) has been set at the time of instal-
lation.
M-NET (ME) remote controller
There is a likelihood of centralized installation of remote
controllers, system expansion, and grouping changes.
Grouping (floor plan) has not been set at the time of in-
stallation.
*1*2
To connect the remote controller directly to the OA pro-
cessing unit.
*1. M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
*2. A system controller must be connected to a system to which both MA remote controller and M-NET remote controller are
connected.
<System with MA remote controller><System with M-NET remote controllers>
Outdoor unit
M-NET transmission line
(indoor/outdoor transmission line)
Outdoor unit
M-NET transmission line
(indoor/outdoor transmission line)
groupgroup
MA remote controller
HWE08040GB
Indoor unit
M-NET remote controller
- 65 -
groupgroup
Indoor unit
[ IV Remote Controller ]
[2] Group Settings and Interlock Settings via the ME Remote Controller
1. Group settings/interlock settings
Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the
indoor/outdoor unit address.
(A) Group settings...........Registration of the indoor units to be controlled with the remote controller,
and search and deletion of registered information.
(B) Interlock settings........Registration of LOSSNAY units to be interlocked with the indoor units,
and search and deletion of registered information
[Operation Procedures]
(1) Address settings
Register the indoor unit to be controlled with the remote controller.
1
Bring up either the blinking display of HO by turning on the unit or the
normal display by pressing the ON/OFF button.
The display window must look like one of the two figures below to proceed to the
next step.
C
G
E
STAND BY
DEFROST
PAR-F27MEA
CENTRALLY CONTROLLED
DAILY
AUTO OFF
CLOCK
REMAINDER
˚C
TEMP.
CLOCK→ON→OFF
TIMER SET
ON OFF
1Hr.
NOT AVAILABLE
˚C
FILTER
CHECK MODE
TEST RUN
LIMIT TEMP.
ON/OFF
CHECK TEST
FILTER
F
?
A
D
[Blinking display of HO ]
Bring up the Group Setting window.
2
-Press and hold buttons [FILTER] and [ ]
simultaneously for 2 seconds to bring up the display as
A
B
[Normal display]
shown below.
Indoor unit address display window
3
Select the unit address.
-
Select the address of the indoor unit to be registered by pressing
button
through the addresses.
4
Register the indoor unit whose address appears on the
C
[TEMP. ( ) or ( )] to advance or go back
display.
- Press button [TEST] to register the indoor unit address
D
whose address appears on the display.
- If registration is successfully completed, unit type will appear
on the display as shown in the figure below.
- If the selected address does not have a corresponding indoor
unit, an error message will appear on the display. Check the
address, and try again.
<Successful completion of registration>
Unit type (Indoor unit in this case)
<Deletion error>
H
B
(B) Interlock Settings (A) Group Settings
6
Bring up the Interlock Setting window.
-Press button [ ] to bring up the following display.
G
Press again to go back to the Group Setting window as shown
under step .
Indoor unit
address
display window
7
Bring up the address of the indoor unit and the address of the
2
Interlocked unit
address
display window
Both the indoor unit address and
interlocked unit address will be
displayed together.
To search for an address,
go to section (2) Address Search.
LOSSNAY to be interlocked on the display.
- Select the address of the indoor unit to be registered by pressing
button [TEMP. ( ) or ( )] to advance or go back through
C
the addresses.
- Select the address of the LOSSNAY unit to be interlocked by
pressing button [TIMER SET ( ) or ( )] to advance or go back
through the interlocked unit addresses.
8
Make the settings to interlock LOSSNAY units with indoor
units.
- Press button [TEST] while both the indoor unit address and
H
D
the address of the LOSSNAY units to be interlocked
are displayed to enter the interlock setting.
- Interlock setting can also be made by bringing up the
LOSSNAY address in the indoor unit address display
window and the indoor unit address in the interlocked unit
address display window.
If registration is successfully
blinks to indicate a registration error.
(Indicates that selected address does not have a
corresponding unit.)
5
To register the addresses for multiple indoor units, repeat
steps and above.
3
4
(Displayed alternately)
completed, the two displays as
shown on the left will appear
alternately.
If the registration fails,
will blink on the display.
(Indicates that the selected
address does not have a
corresponding unit.)
To search for an address,
go to section (2) Address Search.
NOTE : Interlock all the indoor units in the group with the
LOSSNAY units; otherwise, the LOSSNAY units will
not operate.
To next page.
HWE08040GB
- 66 -
[ IV Remote Controller ]
(C) To return to the normal display
When all the group settings and interlock settings are made, take the
following step to go back to the normal display.
10
Press and hold buttons [FILTER] and [ ]
simultaneously for 2 seconds to go back to the
window as shown in step .
A
1
B
(2) Address search
To search for the address of indoor units that have been entered into
the remote controller, follow steps and .
1
2
(A) To search group settings
11
Bring up the Group Setting window.
- Each pressing of button [ ] will bring up the address of a
E
registered indoor unit and its unit type on the display.
<Entry found>
Unit type
(Indoor unit in this case)
<No entries found>
- When only one unit address is registered, the same address
will remain on the display regardless of how many times the
button is pressed.
- When the address of multiple units are registered
(i.e. 011, 012, 013 ), they will be displayed one at a time in
an ascending order with each pressing of button [ ] .
E
Repeat steps and in the previous page to interlock
9
all the indoor units in a group with the LOSSNAY unit.
To go back to the normal display,
follow step .
7
8
To search for an address,
10
go to section (2) Address Search.
(B) Interlock setting search
After performing step , proceed as follows:
12
Bring up the address of the indoor unit to be searched on
6
the display.
- Select the address of the indoor unit to be searched by pressing
H
button [TIMER SET ( ) or ( )] to advance or go back
through the interlocked addresses.
LOSSNAY can be searched in the same manner by bringing up
the LOSSNAY address in the Interlocked unit address display window.
13
Bring up on the display the address of the LOSSNAY unit
that was interlocked with the indoor unit in step .
- With each pressing of button [ ], the address of the
E
LOSSNAY and indoor unit that is interlocked with it will be
displayed alternately.
Address of an interlocked
LOSSNAY unit
(Displayed alternately)
12
14
To delete an address, go to
section (3) Address Deletion.
Bring up the address of another registered unit on the
display.
- After completing step , a subsequent pressing of button
E
[ ] will bring up the address of another registered
13
unit.
(The display method is the same as the one in step .)
To go back to the normal display,
follow step .
10
Address of another
interlocked unit
(Displayed alternately)
To delete an address,
(3) Address deletion
go to section (3) Address Deletion .
The addresses of the indoor units that have been entered into the remote controller can be deleted by deleting the group settings.
The interlock settings between units can be deleted by deleting the interlock settings.
Follow the steps in section (2) Address Search to find the address to be deleted and perform deletion with the address being displayed in the
display window. To delete an address, the address must first be bought up on the display.
15
Delete the registered indoor unit address or the interlock setting between units.
- Press button ? [CLOCK ON OFF] twice while either the indoor unit address or the address of the interlocked unit is displayed on the
F
display to delete the interlock setting.
13
HWE08040GB
- 67 -
[ IV Remote Controller ]
(A) To delete group settings
(B) To delete interlock settings
<Successful completion of deletion>
will be displayed in the room temperature display window.
(Displayed alternately)
- If a transmission error occurs, the selected setting will not be
deleted, and the display will appear as shown below.
In this case, repeat the steps above.
<Deletion error>
will be displayed in the room temperature display window.
To go back to the normal display, follow step .
10
(4) Making (A) Group settings and (B) Interlock settings of a group from any arbitrary remote controller
(A) Group settings and (B) Interlock settings of a group can be made from any arbitrary remote controller.
Refer to (B) Interlock Settings under section 1 Group Settings/Interlock Settings for operation procedures.
Set the address as shown below.
(A) To make group settings
Interlocked unit address display window...Remote controller address
Indoor unit address display window...........The address of the indoor unit to be controlled with the remote controller
(B) To make interlock settings
Interlocked unit address display window...LOSSNAY address
Indoor unit address display window..........The address of the indoor unit to be interlocked with the LOSSNAY
If deletion is successfully
completed, will appear in
the unit type display window.
If the deletion fails, will
appear in the unit type display
window. In this case, repeat the
steps above.
- -
2. Remote controller function selection via the ME remote controller
In the remote controller function selection mode, the settings for four types of functions can be made or changed as necessary.
1) Skip-Auto-Mode setting
The automatic operation mode that is supported by some simultaneous cooling/heating type units can be made unselectable via the ME remote
controller.
2) Operation mode display selection mode (Display or non-display of COOL/HEAT during automatic operation mode)
When the automatic operation mode is selected, the indoor unit will automatically perform a cooling or heating operation based on the room
temperature. In this case, or will appear on the remote controller display.
This setting can be changed so that only will appear on the display.
3) Room temperature display selection mode (Display or non-display of room temperature)
Although the suction temperature is normally displayed on the remote controller, the setting can be changed so that it will not appear on the
remote controller.
4) Narrowed preset temperature range mode
The default temperature ranges are 19 C to 30 C in the cooling/dry mode and 17 C to 28 C in the heating mode and 19 C to 28 C in the auto mode.
By changing these ranges (raising the lower limit for the cooling/dry mode and lowering the upper limit for the heating mode), energy can be saved.
NOTE
When making the temperature range setting on the simultaneous cooling/heating type units that supports the automatic operation mode to save on
energy consumption, enable the Skip-Auto-Mode setting to make the automatic operation mode unselectable. If the automatic operation mode is
selected, the energy-saving function may not work properly.
When connected to the air conditioning units that do not support the automatic operation mode, the setting for the Skip-Auto-Mode, restricted preset
temperature range mode (AUTO), and operation mode display selection mode are invalid. If an attempt is made to change the preset temperature range,
“LIMIT TEMP.” appears on the display.
PAR-F27MEA
TEMP.
TIMER SET
CLOCKĺONĺOFF
ON/OFF
FILTER
CHECK TEST
Normal display
11
Remote controller function selection mode
Skip-Auto-Mode setting
Temperature range setting mode (AUTO)
Operation mode display selection mode (Display or non-display of the automatic mode)
5
Restricted preset temperature range mode (Cooling)
4
Restricted preset temperature range mode (Heating)
Room temperature display selection mode
[Function selection mode sequence on the remote controller]
*2
3
2
3
2
*2
3
2
3
2
3
2
3
*1 *1
2
[Normal display]
1
: Press and hold the [CHECK] and
[ ] buttons simultaneously
for two seconds.
2
: [SET TEMP.
3
: [SET TEMP.
2
3
*1 : Skip-Auto-Mode is enabled
*2 : Skip-Auto-Mode is disabled
( ) ]
( ) ]
button
button
HWE08040GB
- 68 -
[ IV Remote Controller ]
[Operation Procedures]
1. Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display will appear as shown in the previous page (Normal
display).
2. Press buttons [CHECK] and [ ] simultaneously for 2 seconds to go into the “Skip-Auto-Mode setting.”
under the remote controller function selection mode. Press button [SET TEMP. ( )] or [SET TEMP. ( )] to go into the other four modes
1
2
3
under the remote controller function selection mode.
Skip-Auto-Mode setting (Making the automatic operation mode unselectable)
This setting is valid only when the controller is connected to the simultaneous cooling/heating type air conditioning units that
support the automatic operation mode.
“ ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button switches
4
between “ON” and “OFF.”
[TIMER SET ( ) (( ))] button
When set to “ON,” the automatic operation mode is available for selection in the function selection mode.
When set to “OFF,” the automatic operation mode is not available for selection in the function selection mode, and an automatic operation
cannot be performed.
(The automatic operation mode is skipped in the function selection mode sequence.)
Operation mode display selection mode (Changing the type of display that appears during the automatic mode operation)
When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.
will blink, and either
switch between “ON” and “OFF.”
“ON”or“
OFF” will light up.
Press button [TIMER SET ( ) or ( )] in this state to
4
[TIMER SET ( ) (( ))] button
When it is set to ON, will appear on the display during automatic operation mode.
When it is set to OFF, only will appear on the display during automatic operation mode.
Restricted preset temperature range mode (The range of preset temperature can be changed.)
1) Temperature range setting for the cooling/dry mode
will light up in the display window, and the temperature range for the cooling/dry mode will appear on the display.
[Lower limit temperature]: Appears in the preset temperature display window [Upper limit temperature: Appears in the time display window
Switch between the Lower and Upper limit temperature setting by pressing the [CLOCK-ON-OFF] button. The selected temperature setting blinks.
[TIMER SET ( ) (( ))] button
[The left figure shows the display that appears when the current temperature range setting is between 19 C and 30 C in the Cool/Dry mode,
and the lower limit temperature is selected to be set.]
Press button [TIMER SET ( ) or ( )] to set the lower limit temperature to the desired temperature.
4
[Settable range for the lower limit temperature] : 19 C30 C (Settable up to the upper limit temperature that is shown on the display)
[Settable range for the upper limit temperature] : 30 C 19 C (Settable up to the lower limit temperature that is shown on the display)
2) Temperature range setting for heating
“ ” and the settable temperature range for heating appear on the display.
As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range.
5
[Settable range for the lower limit temperature] : 17 C28 C (Settable up to the upper limit temperature that is shown on the display)
[Settable range for the upper limit temperature] : 28 C 17 C (Settable up to the lower limit temperature that is shown on the display)
3) Temperature range setting for the automatic mode
When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.
“ ” and the temperature range for the automatic operation mode appear on the display.
As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range.
5
[Settable range for the lower limit temperature] : 19 C28 C (Settable up to the upper limit temperature that is shown on the display)
[Settable range for the upper limit temperature] : 28 C 19 C (Settable up to the lower limit temperature that is shown on the display)
5
4
4
Room temperature display selection mode (Switching between the display or non-display of room temperature on the controller)
“ 88 C ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button
4
switches between “ON” and “OFF.”
˚C˚C
[TIMER SET ( ) (( ))] button
When set to “ON,” room temperature always appears on the display during operation.
When set to “OFF,” room temperature does not appear on the display during operation.
HWE08040GB
- 69 -
[ IV Remote Controller ]
[3] Interlock Settings via the MA Remote Controller
1. LOSSNAY interlock setting (Make this setting only when necessary.)
Make this setting only when necessary.
Perform this operation to enter the interlock setting between the LOSSNAY and the indoor units to which the remote controller is connected, or to
search and delete registered information.
In the following example, the address of the indoor unit is 05 and the address of the LOSSNAY unit is 30.
[Operation Procedures]
Press the [ON/OFF] button on the remote controller to bring the unit to a stop.
1
The display window on the remote controller must look like the figure below to proceed to step .
Press and hold the [FILTER] and [ ] buttons simultaneously for two seconds to perform a search for the LOSSNAY that is interlocked with the
2
indoor unit to which the remote controller is connected.
Search result
3
- The indoor unit address and the interlocked LOSSNAY address will appear alternately.
<Indoor unit address and indoor unit> <LOSSNAY address and LOSSNAY>
- Without interlocked LOSSNAY settings
2
4
If no settings are necessary, exit the window by pressing and holding the [FILTER] and [ ] buttons simultaneously for 2 seconds.
Go to step 1. Registration Procedures to make the interlock settings with LOSSNAY units, or go to step 2. Search Procedures to search for a
particular LOSSNAY unit.
Go to step 3. Deletion Procedures to delete any LOSSNAY settings.
< 1. Registration Procedures >
5
To interlock an indoor unit with a LOSSNAY unit, press the [ TEMP. ( ) or ( )] button on the remote controller that is connected to the indoor
unit, and select its address (01 to 50).
6
Press the [ CLOCK ( ) or ( )] button to select the address of the LOSSNAY to be interlocked (01 to 50).
Indoor unit address LOSSNAY address
7
Press the [TEST] button to register the address of the selected indoor unit and the interlocked LOSSNAY unit.
- Registration completed
The registered indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
- Registration error
If the registration fails, the indoor unit address and the LOSSNAY address will be displayed alternately.
Registration cannot be completed: The selected unit address does not have a corresponding indoor unit or a LOSSNAY unit.
Registration cannot be completed: Another LOSSNAY has already been interlocked with the selected indoor unit.
HWE08040GB
- 70 -
[ IV Remote Controller ]
< 2. Search Procedures >
8
To search for the LOSSNAY unit that is interlocked with a particular indoor unit, enter the address of the indoor unit into the remote controller that is
connected to it.
<Indoor unit address>
9
Press the [ MENU] button to search for the address of the LOSSNAY unit that is interlocked with the selected indoor unit.
- Search completed (With a LOSSNAY connection)
The indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
- Search completed (No interlocked settings with a LOSSNAY exist.)
- The selected address does not have a corresponding indoor unit.
< 3. Deletion Procedures >
Take the following steps to delete the interlock setting between a LOSSNAY unit and the interlocked indoor unit from the remote controller
that is connected to the indoor unit.
Find the address of the LOSSNAY to be deleted (See section 2. Search Procedures. ), and bring up the result of the search for both the
10
indoor unit and LOSSNAY on the display.
11
Press the [ ON/OFF] button twice to delete the address of the LOSSNAY unit that is interlocked with the selected indoor unit.
- Registration completed
The indoor unit address and , and the interlocked LOSSNAY address and will appear alternately.
-Deletion error
If the deletion fails
[4] Using the built-in Temperature Sensor on the Remote Controller
1. Selecting the position of temperature detection (Factory setting: SW1-1 on the controller board on the indoor unit is
set to OFF.)
To use the built-in sensor on the remote controller, set the SW1-1 on the controller board on the indoor unit to ON.
Some models of remote controllers are not equipped with a built-in temperature sensor. Use the built-in temperature sensor
on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
HWE08040GB
- 71 -
- 72 -
V
Electrical Wiring Diagram
[1] Electrical Wiring Diagram of the Outdoor Unit .................................................................75
[2] Electrical Wiring Diagram of Transmission Booster......................................................... 78
HWE08040GB
- 73 -
- 74 -
[ V Electrical Wiring Diagram ]
VElectrical Wiring Diagram
[1] Electrical Wiring Diagram of the Outdoor Unit
1. Electrical wiring diagram of the outdoor unit
(1) PUHY-P72, P96THMU-A
LEV1
LEV2a
LEV2b
M
M
M
Z24
Z25
1
654
3
2123456
CNLVA
CNDC
21
122131
21
pink
31
CN4
CN332
CNT02
CN801
CNT01
blue
yellow
CN2
7
5
2
Power
CPU power
supply circuit
CNAC2
black
CNLVB
1
P
63H1
red
failure
detection
132
circuit
CN505
6
X72
black
1
1
234
5
CNLVC
red
ONOFF
1
OFF
1
1
LED1
1
ON OFF ON OFF ON OFF ON
1
SWU1
1's digit
Control Board
SWU2
10's digit
X03
X02
X01
CN503
blue
CN502
CN501
3
3
3
1
2
1
1
10
10
10
10
10
Unit address setting
X04
CN504
green
1
1
3
CNTYP5
green
LED1
Display
setting
SW4 SW3 SW2 SW1
SW5
Function setting
Compressor ON/OFF output
Error detection output
*3
543
1
CN51
12V
X05
CN506
1
3
6
2
CNTYP4
TH6
t°
4
1
CN213
green
TH5
TH7
TH3
t°
t°
t°
1
1
2
21223
CN212
red
CN990
LED3:Lit when powered
X09
CN508
black
163
63LS
63HS1
3
2
1
3
2
3
1
CN202
red
CN201
LED2:CPU in operation
2
CN40
321
1
ON
4321
F01
TH2
TH4
t°
t°
1
2
2
1
CN215
black
CN211
4521
2323123
red
CNIT
1
yellow
CNS2
OFF
432112 431
CN41CN102CN3D
Power selecting
connector
3123
red
CN3S
1
blue
CN3N
yellow
CN3K
AC250V
3.15A T
12
red
CNAC
red
CNIT
TB7
yellow
CNS2
Indoor/Outdoor
transmission line
TB3
LED1:Power supply to
CN102
M-NET power
supply
circuit
F01
AC250V
3.15A T
G
M1 M2 M1 M2 S
TP2
TP1
M-NET Board
Central control
transmission
*4
Indoor/Outdoor
transmission
cable
cable
123
4512
1234
CN04
red
1313
CN03
black
*3
123
4
6
blue
CN21
CN22
CN4
12 45
21
CN18V
blue
F01
AC250V
15A T
FAN Board
CNVDC
red
A2
12345
red
THBOX
operation
LED3:CPU in
IPM
R630
C630
6
1
3
CNINV
U
Fan motor
(Heat exchanger)
white
72C
21S4b
A1
t°
operation
LED1:Normal
LED2:Error
1
4
2
V
W
M
3~
SV1a
black
R1
*5
CH11
black
13142343
red
2
1
CN4
31
CN5V
2
1
CN6
SC-P1
INV Board
3334
24
DCL
SV5b
21S4a
1
2
5
3
1
C1
CNDC
pink
yellow
RSH2
C32
+++
C31
RSH1
t°
C30
/Error(Blink)
R30
LED1:Normal operation(Lit)
U
ZNR1
IGBT
*5
TB-N
*5
TB-P
SC-P2
red
red
72C
44
C1
+
THHS
black
7
CN2
SC-V
SV9
CT22
SC-W
CT12
SC-U
SC-R
SC-S
CT3
SC-T
CN02
CX6
3
1
CY3
CY2
CY1
DSA1
Noise Filter
G
black
white
red
red
white
black
white
black
red
L
CX5
TB23
CX4
TB22
TB21
F2
AC250V
6.3A T
CX2
CX3
Z2
Z3
Z4
U
1
U
U
3
U
5
Z1
CX1
CN01
F1
AC250V
6.3A T
black
W
white
3~
V
MS
U
red
Motor
(Compressor)
Ground
L3L2
black
whitered
L1
L3L2
L1
Power supply
3~
60Hz
not supplied with the unit.
box boundaries.
input/output signal connectors.
outdoor units in the same refrigerant
*1.Single-dotted lines indicate wiring
*2.Dot-dash lines indicate the control
*3.Refer to the Data book for connecting
Explanation
Central control transmission
cable
Indoor/Outdoor transmission
cable
Power supply
Terminal
block
Symbol
TB1
TB3
TB7
system together.
*4.Daisy-chain terminals (TB3) on the
*5.Faston terminals have a locking
Subcool bypass outlet
temperature
OA temperature
ACC inlet pipe temperature
Discharge pipe temperature
Pipe temperature
Subcooled liquid refrigerant
temperature
Thermistor
TH2
TH3
TH4
TH5
TH6
TH7
208/230V
function.Make sure the terminals
are securely locked in place after
insertion.Press the tab on the
terminals to removed them.
IGBT temperature
Control box internal temperature
Function setting connector
THHS
Z24,25
THBOX
TB1
Explanation
High pressure protection for the
outdoor unit
Cooling/Heating switching
Heat exchanger capacity control
Discharge pressure
Low pressure
HIC bypass,Controls refrigerant
Outdoor unit heat exchanger
capacity control
Pressure control,Refrigerant flow
rate control
For opening/closing the bypass
circuit under the O/S
flow in HIC circuit
For opening/closing the bypass
circuit
4-way valve
Pressure
sensor
Pressure
switch
Magnetic relay(inverter main circuit)
Current sensor(AC)
Crankcase heater(for heating the compressor)
Symbol
63H1
63HS1
63LS
72C
CH11
21S4b
21S4a
<Symbol explanation>
HWE08040GB
- 75 -
CT12,22,3
Linear
expansion
DC reactor
LEV1
DCL
valve
LEV2a,b
Solenoid
valve
SV5b
SV1a
SV9
[ V Electrical Wiring Diagram ]
(2) PUHY-P120THMU-A
LEV2a
M
1
2
3
4
6
CNLVB
red
1
Control Board
Power
failure
detection
circuit
X72
CN505
black
black
1
2
3
1
LEV2b
M
12345
CNLVC
red
LED1
X01
CN501
1
3
LEV1
M
122
6
536
5
4
CNDC
211131
2
2
2
1
pink
3
1
CNLVA
CN4
CN332
CNT02
CN801
CNT01
blue
yellow
CN2
752
CPU power
supply circuit
CNAC2
P
63H1
ON
1
ON
1
OFF
1
OFF ON
1
OFF ON
ONOFF
1
OFF
SWU1
SWU2
X02
CN502
1
2
3
LED1
Display
SW1
10
SW2
10
SW3
10
SW4
10
SW5
10
Function setting
1's digit
CN51
10's digit
12V
Unit address setting
X04
X03
CN506
CN503
blue
CN504
green
1
3
116
TH6
TH7
TH3
t°
t°
Z25
Z24
1
1223412
1
2
1
3
CN212
CN213
red
green
green
CNTYP5
CNTYP4
setting
Error detection output
Compressor ON/OFF output
*3
1
3
5
4
X05
X07
X08
CN507
red
CN508
3
black
635
1
TH5
63HS1
63LS
32132
1
t°
121
3
3
2
red
CN201
CN202
CN990
ON
4
3
CN40
1
LED2:CPU in operation
LED3:Lit when powered
F01
X09
163
TH4
TH2
t°
t°
2t°112
CN211
CN215
black
51232132
4
red
CNIT
2
yellow
CNS2
OFF
41
23
CN41
1
4
Power selecting
connector
3
2
CN102
21 1
CN3D
13
2
red
CN3S
1
33
blue
CN3N
yellow
CN3K
AC250V
3.15A T
1
2
CNAC
red
red
CNIT
yellow
CNS2
Power supply to
:
LED1
CN102
M-NET power
red
black
F01
G
S
TB7
Indoor/Outdoor
transmission line
M2 M1 M2
TB3
M1
supply
circuit
AC250V
3.15A T
TP2
TP1
M-NET Board
Central control
transmission
*4
Indoor/Outdoor
transmission
cable
cable
12
3
45
12
1
2
3
4
CN04
3
1
3
1
CN03
*3
432
1
654
blue
CN21
5
4
CN22
2
CN4
12
1
CN18V
blue
F01
AC250V
15A T
FAN Board
CNVDC
3
2
1
red
THBOX
operation
LED3:CPU in
IPM
R630
C630
1
3
6
CNINV
U
Fan motor
(Heat exchanger)
t°
operation
LED1:Normal
LED2:Error
124
V
W
M
3~
21S4b
SV1a
THHS
CH11
Z26
t°
SV5b
21S4a
1
7
521
2
1
CN2
3
yellow
CN5V
ON
SW1
OFF
6
1
Function
setting
LED2:Error
LED1:Normal operation
operation
LED4:CPU in
2
CNCT3
black
1
2
CNTYP
1
2
CNTH
green
CNCT
3121
1
CNCT2
blue
432
72C
R2R1
DCL
TB31
red
CN03
black
31
Noise
Filter
4
SV5c
SV9
21S4c
CN4
LED3:Charge
INV Board
*5
R01
Z5
black
72C
TB42
F3
AC250V
3
1
CN02
black
U
C41
6.3A T
FT-N
IPM power
supply
circuit
25
CNIPM
1
red
+
-
Diode Stack
CY1
2
1
CNFG
blue
CNDC1
P
DCCT1
~~~
CX6
CX5
CY2
DSA1
G
F02
1
4
1
CX4
CY3
G
AC250V
3.15A T
4
C008
C007
SC-P1
U
Z4
pink
CNDC3
11
3
4
CNDC2
ACCT1
red
U
white
V
ACCT2
black
W
N
IPM
C1
black
L
ACCT3
TB23
TB22
TB21
AC250V
6.3A T
F2
CX2
CX3
Z2
Z3
1
U
U
U
5
Z1
CX1
CN01
F1
AC250V
6.3A T
red
U
white
3~
V
MS
W
Motor
black
(Compressor)
Ground
L3
blackwhitered
L2
L1
L3
L2
L1
Power supply
3~
TB1
not supplied with the unit.
box boundaries.
input/output signal connectors.
outdoor units in the same refrigerant
*1.Single-dotted lines indicate wiring
*2.Dot-dash lines indicate the control
*3.Refer to the Data book for connecting
Explanation
Central control transmission
cable
Indoor/Outdoor transmission
cable
Subcool bypass outlet
Power supply
Thermistor
Terminal
block
60Hz
208/230V
Symbol
Explanation
TH2
TB1
TB3
TB7
High pressure protection for the
outdoor unit
Discharge pressure
Low pressure
Cooling/Heating switching
Heat exchanger capacity control
system together.
*4.Daisy-chain terminals (TB3) on the
temperature
ACC inlet pipe temperature
Discharge pipe temperature
Pipe temperature
Subcooled liquid refrigerant
temperature
TH3
TH4
TH5
TH6
HIC bypass,Controls refrigerant
function.Make sure the terminals
are securely locked in place after
insertion.Press the tab on the
*5.Faston terminals have a locking
OA temperature
terminals to removed them.
IGBT temperature
Control box internal temperature
Function setting connector
TH7
THHS3Z24,25,26
THBOX
flow in HIC circuit
Pressure control,Refrigerant flow
rate control
For opening/closing the bypass
circuit under the O/S
For opening/closing the bypass
circuit
Outdoor unit heat exchanger
capacity control
Solenoid
4-way valve
Pressure
sensor
Pressure
switch
Magnetic relay(inverter main circuit)
Current sensor(AC)
Crankcase heater(for heating the compressor)
DC reactor
Symbol
21S4b,c
21S4a
63H1
<Symbol explanation>
HWE08040GB
- 76 -
63HS1
63LS
72C
ACCT1,2,3
CH11
DCCT1Current sensor(DC)
DCL
Linear
expansion
valve
LEV1
LEV2a,b
valve
SV1a
SV5b,c
SV9
[ V Electrical Wiring Diagram ]
(3) PUHY-P72, P96,P120YHMU-A
LEV1
12345
6
54321
CN2
5
2
7
supply circuit
ZNR01
CN72
2
M
CNLVB
red
1
red
1
LEV2a
65432
Power failure
detection circuit
U
CNAC2
black
2
1
M
CNLVC
3
M
6
CNLVA
63H1
P
CN4
CN332
blue
1
CNT02
3
1
CN801
yellow
2
1
CNT01
CPU power
pink
CNDC
321122
1
LEV2b
1
red
ONOFF
1
ON
1
OFF
ON
1
OFF
ONOFF
LED1
1
ON
1
OFF
1's
digit
SWU1
10's
digit
SWU2
Control Board
X01
X02
X03
CN501
CN502
CN503
blue
3
1
1
3
1
2
3
SW1
10
SW2
10
SW3
10
SW4
10
SW5
10
Unit address
setting
X04
CN504
green
CN506
6
1
Z24
Z25
1
2
1
3
1
green
CNTYP2
black
CNTYP4
CNTYP5
green
LED1
Display
setting
Function
setting
*3
Compressor ON/OFF output
Error detection output
1
4
5
3
CN51
12V
X05
X07
CN507
red
1
1
3
356
TH5
TH3
TH7
TH6
t°
t°
t°
t°
2
4
3
2
1
2
1
CN212
CN990
CN213
red
LED3:Lit when powered
X08
X09
CN508
black
3
6
1
63LS
3
2
1
1
1
2
1
3
3
CN202
red
LED2:CPU in operation
TH2
63HS1
3
2
t°
2
1
2
1
CN201
CN215
black
TB7 Power
selecting
connector
CN40
F01
ON
4
3
12
AC250V
TH4
t°
2
1
CN211
5
44
3
red
CNIT
21
21
yellow
CNS2
3
21
CN41
432
CN102
1
2
CN3D
3
11
2
red
CN3S
3
12
blue
3
CN3N
123
yellow
CN3K
3.15A T
21
CNAC
OFF
red
TP2
1
32
TP1
4
CNIT
red
5
S
M2
TB7
Indoor/Outdoor
1
2
1
2
3
4
CN04
red
3
1
transmission line
LED1:Power supply to
CNS2
yellow
CN102
M-NET power
supply circuit
G
M1
M2
TB3
M1
M-NET Board
Central control
transmission
*4
Indoor/Outdoor
transmission
cable
cable
*3
5
3
2
4
1
6
2
CN21
blue
1
CN5
3
red
1
CN4
1
LED3:CPU in
operation
2
CN18V
blue
C631
F01
DC700V
4A T
4
FAN Board
6
72C
1
5
4
3
2
CN22
red
IPM
R631
R630
C630
1
CNVDC
U
Fan motor
(Heat exchanger)
7
THBOX
V
M
t°
4
3~
21S4b
operation
LED2:Error
LED1:Normal
C100
1
CNINV
W
CH11
21S4a
SV5b
SV1a
*7
7
2
1
CN4
1
3
yellow
CN5V
1
2
CN6
/ Error(Blink)
Normal operation(Lit)
:
*5
R5
R1
LED1
black
2
4
black
SC-P1
72C
1
3
FT-P
red
*6
DCL
P
SC-P2
red
CN1
3
1
R5
red
CN5
D1
R4
+
CN4
blue
3
1
GG
1
6
5
3
CN2
SV9
SV5c
21S4c
5
2
1
1
3
black
CNTYP
CN2
SC-V
C1
RSH1
THHS
t°
ZNR1
U
IGBT
C35
C37
R31
C31
C33
FT-N
++++++
++
N
R30
C34
C32
C36
C30
4
1
1
Z5
F4
AC250V
6.3A T
Diode
Bridge
U
CN6
+-
C6
C5
R6
C4
C17
Noise
Filter
C10
U
F3
F1
F2
C3
Z4
DSA
U
Z3
U
Z2
F1,F2,F3
AC250V
6.3A T
U
Z1
CT22
SC-W
SC-U
SC-L2
SC-L1
R33
red
R32
R34R35
3
red
yellow
C9
C7
C8
C2
C1
black
white
red
CT12
SC-L3
CT3
black
white
INV Board
white
black
red
white
R2
R3
F5
F4
black
L
TB23
L3
TB22
L2L1
TB21
CN1B
black
1
R1
4
1
3
CN1A
black
W
white
V
MS
3~
U
Motor
red
(Compressor)
45678
L3
3
12
600V
3A F
600V
3A F
white
L1L2 L2
CNTR1
Ground
L3
L2
L1 L2 L3
TB1
red
L1
Power Source3~60Hz
432
CNTR2
CN06
460V
Transformer Box
1
T02
5
6
234
1
purple
460V
CNTR3
(Transformer)
2
3
4
1
T03
(Transformer)
56243
1
CN07
purple
460V
Explanation
High pressure protection for the
outdoor unit
Heat exchanger capacity control
Low pressure
Discharge pressure
Appliance
*7 do not exist
*7 exist
Model name
P120
in place after insertion. Press the tab
same refrigerant system together.
*1.Single-dotted lines indicate wiring not supplied with the unit.
*2.Dot-dash lines indicate the control box boundaries.
Make sure the terminals are securely locked
*3.Refer to the Data book for connecting input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the outdoor units in the
*5.Faston terminals have a locking function.
the unit off for at least 10 minutes,
on the terminals to removed them.
Before inspecting the inside of the
control box,turn off the power,keep
and confirm that the voltage between
*6.Control box houses high-voltage parts.
FT-P and FT-N on INV Board has dropped
P72/P96
to DC20V or less.
*7.Difference of appliance
HWE08040GB
Cooling/Heating switching
4-way valve
Pressure
switch
Pressure
Symbol
21S4a
21S4b,c
63HS1
63H1
<Symbol explanation>
- 77 -
HIC bypass,Controls refrigerant
DC reactor
Linear
Crankcase heater(for heating the compressor)
Current sensor(AC)
Magnetic relay(inverter main circuit)
sensor
DCL
LEV1
CT12,22,3
CH11
72C
63LS
Outdoor unit heat exchanger
flow in HIC circuit
expansion
capacity control
For opening/closing the bypass
circuit under the O/S
Pressure control,Refrigerant flow
rate control
valve
Solenoid
valve
LEV2a,b
SV1a
SV5b,c
Central control transmission
cable
Indoor/Outdoor transmission
cable
Subcool bypass outlet
temperature
TB7
Pipe temperature
Thermistor
TH3
TH2
Discharge pipe temperature
TH4
Power supply
For opening/closing the bypass
circuit
Terminal
block
SV9
TB1
TB3
Subcooled liquid refrigerant
temperature
IGBT temperature
OA temperature
ACC inlet pipe temperature
Control box internal temperature
Function setting connector
TH5
TH6
TH7
THHS
Z24,25
THBOX
[ V Electrical Wiring Diagram ]
[2] Electrical Wiring Diagram of Transmission Booster
Terminal block for power supply
(TB1)
100V/200VAC
Grounding
250V 5A
L
Red
White
Green
Red Red
Red
Varistor
U
DSA
White Blue RedRed
1 2
1 2 1 2
CN3
Electronic control board
Red
White
Red
Varistor
U
White White
White
Red
Red
Blue
White
Choke coil
CN2
CN4
CN1
2
White
Red
1
Black
Red
White
1
2
4
3
Stabilized power supply
2
1
CN2
Noise filter
1
2
3
3
Green/Yellow
E
4
Black
Black
CN1
White
Red
Black
Red
Black
Black
S
Terminal block 2 for
B
transmission line (TB3)
Expanded (indoor unit) side
A
S
Terminal block 1 for
B
transmission line (TB2)
Expanded (outdoor unit) side
AC208-230V
Dead: cooling cycle
Outdoor unit heat exchanger
capacity at 100%
Live: heating cycle
Outdoor unit heat exchanger
capacity at 50%
or heating cycle
Same as indoor LEV
The resistance
value differs
from that of the
indoor LEV.
(Refer to the
section "LEV
Troubleshooti
ng."(page 238
))
Same as indoor LEV
Resistance
check
Continuity
check with a
tester
HWE08040GB
- 84 -
[ VI Refrigerant Circuit ]
2. Indoor Unit
Part
Name
Linear
expansion valve
Thermistor
Symbol
(functions)
Notes Usage Specification Check method
LEV1) Adjusts superheat at the
indoor heat exchanger
outlet during cooling
2) Adjusts subcool at the
heat exchanger outlet of
the indoor unit during
cooling
TH1
Indoor unit control (Thermo)
(Suction air
temperature)
TH2
(Pipe temperature)
1) Indoor unit control (Frost
prevention, Hot adjust)
2) LEV control during heating operation (subcool
detection).
TH3
(Gas pipe
LEV control during cooling operation (superheat detection)
temperature)
TH4
Indoor unit control (Thermo)
Outdoor air
temperature)
Temperature
Indoor unit control (Thermo)
sensor (Indoor air temperature)
DC12V
Opening of stepping motor
driving valve 0-(1400) pulses
[1] Functions and Factory Settings of the Dipswitches
1. Outdoor unit
(1) Control board
SwitchFunction
Function according to switch settingSwitch setting timing
OFFONOFFONOCOS
SWU1-2Unit address settingSet to 00 or 51-100 with the dial switchBefore power onCC
SW1 1-10
1
2
3
For self-diagnosis/
operation monitoring
Centralized control
switch
Deletion of connection information
Deletion of error history SW
Refer to the LED monitor display on the
outdoor unit board.
Without connection
to the centralized
controller
With connection to
the centralized controller
Anytime after power on
Before power on
Normal controlDeletionBefore power on
(OC) Storage of IC/
OC error history
(OS) Storage of OS
error history
(OC) Deletion of IC/
OC error history
(OS) Deletion of
OS error history
Anytime after power on
(When switched from OFF
to ON)
After being energized and
4Pump down modeNormal controlPump down mode
while the compressor is
stopped
5-----6------
SW2
Forced defrost
7
Note 3
Normal control
Forced defrost
starts
10 minutes
after compressor
startup
Anytime after power
on (When
switched
from OFF to
ON)
Defrost timer setting
8
Note 3
Target evaporation
9
temperature setting
50 minutes90 minutes
Depends on the setting combination with
the SW3-5 setting (Note 4)
Anytime after power on
(When switched from OFF
to ON)
Anytime after power on
Enable/disable refrigerant noise suppression function
10
during defrosting
(Fan operation
Normal control
Refrigerant noise
suppression
Befo
re powe
r on
against leaky indoor
unit LEV)
Units that re-
quire switch
setting
Note.2
CC
BB
A-
CC
A-
AA
BB
A-
A-
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) Refer to "VII [2] Controlling the Outdoor Unit" for details.(page 96)
4) The table below shows the combination of SW2-9 and SW3-5 settings and the target evaporation temperature setting that
corresponds to each combination.
Switch
OFFON
SW2-9
SW3-5OFF0°C [32°F] -4°C [25°F]
ON-2°C [28°F]-6°C [21°F]
HWE08040GB
- 89 -
[ VII Control ]
SwitchFunction
SW3
SW4
Units that
require
Function according to switch settingSwitch setting timing
switch set-
ting
Note.2
OFFONOFFONOCOS
Test run mode: en-
1
abled/disabled
Test run mode: ON/
2
OFF
Defrost start tem-
3
perature Note 5
Defrost end tem-
4
perature Note 5
SW3-2 disabledSW3-2 enabledAnytime after power on
Stops all ICs
Sends a test-run
signal to all IC
After power on and when
SW3-1 is on.
-10°C [14°F] -5°C [23°F]Anytime after power on
P72, P96
10°C [50°F]
P120
5°C [41°F]
Anytime after power on (except during defrost)
A-
A-
BB
BB
7°C [45°F]
Target evaporation
5
temperature setting
Temperature unit
6
setting
Target condensing
7
temperature setting
Depends on the setting combination with
the SW2-9 setting (Note 4)
Anytime after power on
°C°FAnytime after power on
49°C [120°F] 53°C [127°F] -
A-
CC
A-
for heating
8------
9Model setting
10Model setting
Enable/disable high
1
sensible temperature operation
Outdoor standard
static pressure
High static pressure
60Pa
Normal operation
mode
Outdoor high static
pressure
High static pressure
30Pa
High sensible temperature operation
mode
Before being energized
Before being energized
Before being energized
CC
CC
A-
2------
Refrigerant amount
3
adjustment
Low-noise mode/
4
step demand
switching
Automatic cooling/heating switchover (IC with
5
the minimum address)
Cumulative com-
6
pressor operation
time data deletion
Normal operation
mode
Low-noise mode
Note 3
Normal operation
mode
Cumulative compressor operation
time data is retained.
Refrigerant amount
adjust mode
Anytime after being energized (except during initial startup mode.
Automatically cancelled 60 minutes after compressor startup)
Step demand mode Before being energized
Automatic cooling/
heating switchover
Cumulative compressor operation
time data is deleted.
Before being energized
Anytime after power on
(when the unit is turned on)
A-
CC
A-
CC
7-----8-----9------
10------
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed.
Setting of CN3D is required.
4) The table below shows the combination of SW2-9 and SW3-5 settings and the target evaporation temperature setting that
corresponds to each combination.
Switch
OFFON
SW2-9
SW3-5OFF0°C [32°F] -4°C [25°F]
ON-2°C [28°F]-6°C [21°F]
5) Refer to VII [2] Controlling the Outdoor Unit -7- Defrost Operation Control for details.(page 99)
HWE08040GB
- 90 -
[ VII Control ]
Units that re-
quire switch
setting
Note.2
SwitchFunction
Function according to switch settingSwitch setting timing
OFFONOFFONOCOS
1
2----
Model setting
3----
----CC
4----
SW5
Low-noise mode
5
selection
Capacity priority
mode
Note 3
Low-noise modeBefore being energized
A-
6-----7Model setting---BB
8-----9------
10Heating backupIneffectiveEffectiveAny time after power onA-
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) When set to the capacity priority mode and if the following conditions are met, the Low-noise mode will terminate, and the unit
will go back into the normal operation mode.
Cooling: Outside temperature is high or high pressure is high.
Heating: Outside temperature is low or low pressure is low.
(2) INV board
1) PUHY-P72, P96, P120YHMU-A, PUHY-P72, P96THMU-A
Functions are switched with the following connector.
ConnectorFunction
Function according to connec-
tor
Setting timing
EnabledDisabledEnabledDisabled
CN6 shortcircuit con-
nector
Enabling/disabling the following error
detection functions;
ACCT sensor failure
(5301 Detail No. 115)
ACCT sensor circuit failure
Error detection enabled
Error detection disable
(No load operation is possible.)
CN6 short-circuit connector is mated with the mating connector.
Leave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the
equipment from damage.
HWE08040GB
- 91 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.