Air-Conditioners For Building Application
Hyper Heating Inverter Y-Series
OUTDOOR UNIT
For use with R410A
PUHY-HP-THMU-A
INST ALLA TION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
MANUEL D’INSTALLATION
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
s Before installing the unit, make sure you read all the “Saf ety
ss
precautions”.
ss
s The “Safety precautions” provide very important points re-
ss
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury
or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the
unit.
Warning:
Carefully read the labels attached to the outdoor unit.
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user ma y result in w ater leakage, electric shock,
or fire.
• Install the unit at a place that can withstand its weight.
-Failure to do so may cause the unit to fall down, resulting in injuries and
damage to the unit.
• Use the specified cables for wiring. Make the connections securely so
that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Prepare for str ong winds and earthquakes and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in injury and
damage to the unit.
•Always use filters and other accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
•Never attempt to repair the unit without the proper qualifications. If the
air conditioner must be repaired consult the dealer, contractor or qualified
Refrigeration Engineer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may
result.
•Have all electric work done by a licensed electrician according to “Electric
Facility Engineering Standard” and “Interior Wire Regulations” and the
instructions given in this manual and always use a dedicated power
supply.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
• Securely install the outdoor unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water may enter
the outdoor unit and fire or electric shock may result.
11.4. Wiring of main power supply and equipment capacity ............ 16
12. Test run/Typical unit operation .................................................................. 17
13. Rating plate information ............................................................................ 17
• When installing and moving the air conditioner to another site, do not
charge it with a refrigerant different from the refrigerant specified on the
unit.
- If a diff erent refrigerant or air is mix ed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration from exceeding the safety limit if
the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prev ent the saf ety
limit from being exceeded. Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or
an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or
fire may result.
• After completing installation work, make sure that refrigerant gas is not
leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
or operated forcibly, or parts other than those specified by Mitsubishi Electric
are used, fire or explosion may result.
•To dispose of this product, consult your dealer.
• The installer and system specialist shall secure safety against leakage
according to local regulation or standards.
- Choose the appropriate wire size and the s witch capacities for the main power
supply described in this manual if local regulations are not available.
•Pay special attention to the place of installation, such as a basement, etc.
where refrigeration gas can accumulate, since refrigerant is heavier than
the air.
• For outdoor units that allow outside air intake to the indoor unit, the
installation site must be carefully chosen to ensure only clean air can
enter the room.
- Direct exposure to outdoor air may have harmful effects on people or food.
1.2. Precautions for devices that use R410A
refrigerant
Caution:
• Do not use existing refrigerant piping.
- The old refrigerant and refrigerant oil in the existing piping contains a large
amount of chlorine which may cause the refrigerant oil of the new unit to
deteriorate.
- R410A is a high-pressure refrigerant and can cause the existing piping to
burst.
• Use refrigerant piping made of phosphorus deoxidized copper and copper alloy seamless pipes and tubes. In addition, be sure that the inner
and outer surfaces of the pipes are clean and free of hazardous sulphur ,
oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping ma y cause the refriger-
ant oil to deteriorate.
• Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and
compressor failure may result.
2
• Apply onl y a small amount of ester oil, ether oil, or alkyl benzene to flare
connections (for indoor unit).
- Infiltration of a large amount of mineral oil may cause the refrigerant oil to
deteriorate.
• Use liquid refrigerant to fill the system.
- If gas refrigerant is used to fill the system, the composition of the refrigerant
in the cylinder will change and performance may drop.
• Do not use a refrigerant other than R410A.
- If another refrigerant (R22, etc.) is mixed with R410A, the chlorine in the
refrigerant may cause the refrigerant oil to deteriorate.
• Use a vacuum pump with a reverse flow check valve.
- The v acuum pump oil may flo w back into the refrigerant cycle and cause the
refrigerant oil to deteriorate.
• Do not use the following tools that are used with conventional refrigerants.
(Gauge manifold, charge hose, gas leak detector, reverse flow c heck valve,
refrigerant charge base, refrigerant recovery equipment)
- If the conv entional refrigerant and refrigerant oil are mix ed in the R410A, the
refrigerant may deteriorate.
- If water is mixed in the R410A, the refrigerant oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conven-
tional refrigerants will not react to it.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Be especially careful when managing the tools.
- If dust, dirt, or water gets into the refrigerant cycle, the refrigerant may dete-
riorate.
1.3. Before installation
Caution:
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
• When installing the unit in a hospital, communication station, or similar
place, provide sufficient protection against noise.
-Inverter equipment, private power generator, high-frequency medical equip-
ment, or radio communication equipment may cause the air conditioner to
operate erroneously , or f ail to operate. On the other hand, the air conditioner
may affect such equipment by creating noise that disturbs medical treatment
or image broadcasting.
• Do not install the unit on or over things that are subject to water dama ge.
- When the room humidity exceeds 80% or when the drain pipe is clogged,
condensation may drip from the indoor unit. P erform collective drainage w ork
together with the outdoor unit, as required.
1.4. Before installation (relocation) - electri-
cal work
Caution:
•Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
• Install the power cable so that tension is not applied to the cable.
-Tension may cause the cable to break and generate heat and cause a fire.
• Install a leak circuit breaker, as required.
- If a leak circuit breaker is not installed, electric shock may result.
• Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Use only a circuit breaker and fuse of the specified capacity.
-A fuse or circuit breaker of a larger capacity, or the use of a substitute simple
steel or copper wire may result in a general unit failure or fire.
• Do not wash the air conditioner units.
-Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit ma y f all and cause personal injury
or property damage.
• Install the drain piping according to this Installation Manual to ensure
proper drainage. Wrap thermal insulation around the pipes to prevent
condensation.
- Improper drain piping ma y cause water leakage causing damage to furniture
and other possessions.
• Be very careful about transporting the product.
- One person should not carry the product. Its weight is in excess of 20 kg
[45LBS].
- Some products use PP bands f or pac kaging. Do not use any PP bands as a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, support it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot
slip sideways.
• Safely dispose of the packing materials.
-Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
-Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which has not been torn
apart, they face the risk of suffocation.
1.5. Before starting the test run
Caution:
•Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can
result in irreversible damage to internal parts. Keep the power switch turned
on during the operational season. Make sure of the phase order of power
supply and voltage between each phase.
• Do not touch the switches with wet fingers.
-Touching a switch with wet fingers can result in an electric shock.
• Do not touch the refrigerant pipes during and immediately after operation.
- During and immediately after operation, the refrigerant pipes may be hot or
cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may
suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not turn off the power immediately after stopping operation.
- Always wait at least 5 minutes before turning off the power. Otherwise,
drainage water leakage or mechanical failure of sensitive parts may occur.
• Do not touch the surface of the compressor during servicing.
- If the unit is connected to a supply and not running, the crank case heater
located at the base of the compressor may still be operating.
GBDFEINLPGRRUTRCZSVSLHGPO
2. About the product
• This unit uses R410A-type refrigerant
• Piping for systems using R410A may be different from that for systems using
conventional refrigerant because the design pressure in systems using R410A
is higher. Refer to the Data Book for more information.
• Some of the tools and equipment used for installation with systems that use
other types of refrigerant cannot be used with the systems using R410A. Refer
to the Data Book for more information.
• Do not use the existing piping, as it contains chlorine, which is found in conventional refrigerating machine oil and refrigerant. This chlorine will deteriorate
the refrigerant machine oil in the new equipment. The existing piping must not
be used as the design pressure in systems using R410A is higher than that in
the systems using other types of refrigerant and the existing pipes may burst.
3
3. Combination of outdoor unit
Component units of PUHY-HP144 to HP192 are listed below.
Outdoor unit model
PUHY-HP72THMU-A(-BS)
PUHY-HP96THMU-A(-BS)
PUHY-HP144TSHMU-A(-BS)
PUHY-HP192TSHMU-A(-BS)
* PUHY-HP144/192TSHMU-A(-BS) require “Twinning Kit” to connect component unit modules in the field.
PUHY-HP72THMU-A(-BS)
PUHY-HP96THMU-A(-BS)
Component unit models
-
PUHY-HP72THMU-A(-BS)
PUHY-HP96THMU-A(-BS)
4. Specifications
-
-
Model
Sound level (60Hz)
External static pressure
Indoor units
Operation
temperature
GBDFEINLPGRRUTRCZSVSLHGPO
*1: The total indoor capacity of units run simultaneously is 130% or less.
*2: To enable high static pressure, set the DipSW on the main panel as follows.
SW3-9: ON, SW3-10 60Pa compatible: OFF, 30Pa compatible: ON
6. Space required for unit installation and operation
1 In case of single installation
• Secure enough space around the unit as shown in the figure below.
[Fig. 6.0.1]
(1) If the distance is 300 mm [11-13/16 in] or more between the rear side and
the wall
<A> T op view
A
300*
[11-13/16]
450*
[17-23/32]
15*15*
[19/32][19/32]
(Unit: mm [in])
(3) If the wall height (H) of the front, rear or side exceeds the wall height
2
0 Pa*
50 ~ 130%*
06 ~ 96
<Liquid side>
1 pc.
1 pc.
restriction
<B> Side view
h
H
B
PUHY-HP144TSHMU-A
59dB <A>
1
1 ~ 22
4 Adapter
<Check joint>
2 pcs.
2 pcs.
A
h
500
PUHY-HP192TSHMU-A
60dB <A>
1 ~ 24
5 Packing
(Inside ø23, Outside ø30)
–
1 pc.
(Unit: mm [in])
H
[19-11/16]
(2) If the distance is 100 mm [3-15/16 in] or more between the rear side and
the wall
<A> T op view
A
100*
[3-15/16]
450*
[17-23/32]
50*50*
[1-31/32][1-31/32]
(Unit: mm [in])
4
• When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defined here, add the height that exceeds the height
limit <h> to the figures that are marked with an asterisk (*).
<Wall height limit> Front: Up to the unit height
(4) If there are obstacles at the upper part of the unit
<C> When there is little space up to an obstruction
45°
240
[9-15/32]
A FrontB Unit height
C BackD Air outlet guide (field-supplied)
Back: Up to 500mm [19-11/16 in] from the unit bottom
Side: Up to the unit height
(Unit: mm [in])
1000
[39-3/8]
D
50
A
[1-31/32]
C
2 In case of collective installation and continuous installation
[Fig. 6.0.2]
(Unit: mm [in])
B
B
AAA
30
[1-3/16]
100
[3-15/16]
A
300*
450*
450*100*
15*
100*
[19/32]
[11-13/16][17-23/32]
[3-15/16][17-23/32]
C
BB
BB
CC
[17-23/32] [17-23/32][17-23/32][3-15/16]
A
C
C
A
C
A
A
450*450450
C
450450
[17-23/32] [17-23/32]
300*300*
C
BB
A
C
1000*
[39-3/8]
A FrontB Must be open
C Wall height (H)
C
A
B
[11-13/16][11-13/16]
900
[35-7/16]
300*
[11-13/16]
900
B
[35-7/16]
• When multiple units are installed adjacent to each other, secure enough space
to allow for air circulation and walkway between groups of units as shown in
the figures.
• At least two sides must be left open.
• As with the single installation, add the height that exceeds the height limit <h>
to the figures that are marked with an asterisk (*).
GBDFEINLPGRRUTRCZSVSLHGPO
7. Transporting the unit
[Fig. 7.0.1]
40
8
[26]
• Use suspension ropes that will withstand the weight of the unit.
• When moving the unit, use a 4-point suspension, and a void giving impacts to
the unit (Do not use 2-point suspension).
• Place protective pads on the unit where it comes in contact with the ropes to
protect the unit from being scratched.
• Set the angle of roping at 40˚ or less.
• Use 2 ropes that are each longer than 8 m [26ft].
8
[26]
• Place protective padding at the corners of the product to protect the product
from scratches or dents that might be caused by the rope.
Caution:
Be very careful when carrying/moving the product.
- When installing the outdoor unit, suspend the unit at the specified location of the
unit base. Stabilize as necessary so that it does not mov e to the side and support
it at 4 points. If the unit is installed or suspended with 3-point support, the unit
may become unstable and fall.
(Unit: m [ft])
5
8. Installation of unit
8.1. Installation
[Fig. 8.1.1]
30
[1-3/16]
A
B
GBDFEINLPGRRUTRCZSVSLHGPO
C
A Field-supplied M10 anchor boltB Corner is not seated.
C Fixing bracket for the hole-in anchor bolt (3 locations to fix with screws)
[Fig. 8.1.2]
Outlet
InletInlet
H
• In abnormally harsh environments such as clod and/or windy areas, sufficient
countermeasures to guard against excessive wind and snow should be taken
to ensure the unit's correct operation. When the unit is expected to operate in
cooling mode in conditions under 10°C [50°F], in snowy areas, in environments
subject to strong winds or rain, install air inlet and outlet ducting as shown in
[Fig. 8.1.2].
Inlet
(Unit: mm [in])
•
Fix unit tightly with bolts so that unit will not fall down due to earthquakes or strong winds.
• Use concrete base or an angle bracket as the foundation of unit.
•
Vibration may be transmitted to the installation section and noise and vibration may
be generated from the floor and walls, depending on the installation conditions.
Therefore, provide ample vibrationproofing (cushion pads, cushion frame, etc.).
• Be sure that the corners are firmly seated. If the corners are not firmly seated,
the installation feet may be bent.
• The projecting length of the anchor bolt should be less than 30 mm [1-3/16 in].
•Post-installed anchor bolts (i.e., bolts not firmly cemented into the base) are
not compatible with this product unless fixing brackets are first mounted on the
four locations.
Note:
1. Height of frame base for snow damage prev ention (H) shall be twice as high as
expected snowfall. Width of frame base shall not exceed that of the unit. The
frame base shall be made of angle steel, etc., and designed so that snow and
wind slip through the structure. (If frame base is too wide, snow will be
accumulated on it.)
2.
Install unit so that wind will not directly lash against openings of inlet and outlet ducts.
3. Build frame base at customer referring to this figure.
Material : Galvanized steel plate 1.2T
Painting : Overall painting with polyester powder
Color : Munsell 5Y8/1 (same as that of unit)
4. When the unit is used in a cold region and the heating operation is continuously
performed for a long time when the outside air temperature is below freezing,
install a heater to the unit base or take other appropriate measures to prevent
water from freezing on the base.
Warning:
•
Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
•
Have installation work in order to protect against strong winds and earthquakes.
Any installation deficiency may cause unit to fall down, resulting in a per sonal injury.
When building the foundation, give full attention to the floor strength, dr ain water disposal
<during operation, drain water flows out of the unit>, and piping and wiring routes.
Precautions when routing the pipes and wires below the unit (Without
detachable leg)
When routing the pipes and wires below the unit, be sure that the foundation and
base work do not block the base through-holes. Also make sure the foundation is
at least 100 mm [3-15/16 in] high so that the piping can pass under the unit.
9. Refrigerant piping installation
The pipe is connected via a terminal-branch type connection in which refrigerant
piping from the outdoor unit is branched at the terminal and is connected to each
of the indoor units.
The method of pipe connection is as follows: flare connection for the indoor units,
gas pipes for outdoor units, flare connection for P72 and brazed connection for
P96 ~ P192; liquid pipes, flare connection. Note that the branched sections are brazed.
Warning:
Always use extreme care to prevent the refrigerant gas from leaking while
using fire or flame. If the refrigerant gas comes in to contact with a flame
from any source, such as a gas stove, it breaks down and generates a poisonous gas which can cause gas poisoning. Never weld in an unventilated
room. Alwa ys conduct an inspection f or gas leaka ge after installation of the
refrigerant piping has been completed.
6
9.1. Caution
This unit uses refrigerant R410A. Follow the local regulations on materials and
pipe thickness when selecting pipes. (Refer to the table on page 7.)
1 Use the following materials for refrigeration piping.
• Material: Use copper alloy seamless pipes made of phosphorus deoxi-
dized copper. Ensure the inner and outer surfaces of the pipes are clean
and free from hazardous sulfur, oxide, dusts, shaving particles, oils, and
moisture (contamination).
Size: Refer to item 9.2. for detailed information on refrigerant piping system.
•
2 Always observe the restrictions on the refrigerant piping (such as rated length,
height difference, and piping diameter) to prevent equipment failure or a decline in heating/cooling performance.
3 Branching cannot be made after header branching (corresponding parts are
marked with
4 Do not install outdoor unit piping when it is raining.
5 Commercially available piping often contains dust and other materials. Alwa ys
blow it clean with a dry inert gas.
6 Use care to prevent dust, water or other contaminants from entering the piping
during installation.
7 Reduce the number of bending portions as much as possible, and make bend-
ing radius as big as possible.
8 For indoor and outdoor branching, be sure to use the following twinning pipe
sets (sold separately).
in the diagram below).
To the outdoor unit
To the outdoor unit
CAP
9 Use an adapter if a specified refrigerant pipe has a different diameter from that
of a branching pipe.
0 Braze only with non-oxide brazing material for piping. Failure to do so
may damage the compressor. Be sure to perf orm the non-oxidation brazing with a nitrogen purge.
Do not use any commercially available anti-oxidizing agent since it may
cause pipe corrosion and degrading of the refrigerant oil.
Please contact Mitsubishi Electric for more details.
(Refer to item 10.2. for details of the piping connection and valve operation)
A Always insulate the piping properly. Insufficient insulation will result in a de-
cline in heating/cooling performance, water drops from condensation forming
and other such problems. (Ref er to item 9 f or installation of refrigerant piping.)
B When connecting the refrigerant piping, make sure the valve of the outdoor
unit is completely closed (the factory setting). Do not operate it until the refrigerant piping for the outdoor and indoor units has been connected, a refrigerant
leakage test has been performed, and the evacuation process has been completed.
C Never use refrigerant to perform an air purge. Always evacuate using a
vacuum pump.
D Be sure to charge the system using liquid refrigerant.
E Either a lack or an excess of refrigerant causes the unit to make an emergency
stop. Charge the system with an appropriate amount of refrigerant. When servicing, always check the notes concerning pipe length and amount of additional
refrigerant at both locations, the refrigerant volume calculation table on the
back of the service panel and the additional refrigerant section on the labels
for the combined number of indoor units. (Refer to item 9.2. for detailed information on refrigerant piping system.)
GBDFEINLPGRRUTRCZSVSLHGPO
Indoor twinning pipe set model
Line branch
Downstream indoor unit capacity
Less than 72 in total
CMY-Y102S-G2
Downstream indoor unit capacity
More than 73 and less than
144 in total
CMY-Y102L-G2
Downstream indoor unit capacity
More than 145 and less than
288 in total
CMY-Y202-G2
Warning:
When installing and moving the unit, do not charge the system with any
other refrigerant other than the refrigerant specified on the unit.
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to malfunction and may result in severe damage.
Caution:
• Use a vacuum pump with a reverse flow check valve.
- If the vacuum pump does not have a reverse flow check valve, the vacuum
pump oil may flow back into the refrigerant cycle and cause deterioration of
the refrigerant oil.
• Do not use the tools shown below used with conventional refrigerant.
(Gauge manifold, charge hose, gas leak detector , chec k valve, refrigerant
charge base, vacuum gauge, refrigerant recovery equipment)
- Mixing of conv entional refrigerant and refrigerator oil may cause the refriger-
ant oil to deteriorate.
9.2. Refrigerant piping system
Connection Example
[Fig. 9.2.1]
[Outdoor model : P72 ~ P96]
Header branch
4 branches
CMY-Y104-G
- Mixing of water will cause the refrigerant oil to deteriorate.
- R410A refrigerant does not contain any chlorine. Theref ore , gas leak detectors for conventional refrigerants will not react to it.
• Manage the tools used for R410A more carefully than normal.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant oil will deteriorate.
•Never use existing refrigerant piping.
- The large amount of chlorine in conv entional refrigerant and refrigerant oil in
the existing piping will cause the new refrigerant to deteriorate.
• Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and
the compressor may fail.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Do not use special detergents for washing piping.
8 branches
CMY-Y108G
10 branches
CMY-Y1010-G
Outdoor Twinning Kit model
Total outdoor model
P144 ~ P192
CMY-Y100VBK2
A
A
A
BCD
abcd
B
C
CCC
e
C
A
F
B
b
a
cde
CC
D
CC
C
7
[Outdoor model : P144 ~ P192]
F
F
unit 1
unit 2
unit 1
unit 2
A
A2A1
A Outdoor unitB 1st branch
C Indoor unitD Cap
E Outdoor T winning KitF Header
GBDFEINLPGRRUTRCZSVSLHGPO
* The total length of A1 and A2 is less than 10 m [32 ft].
Refer to [Fig. 9.2.2] for the positioning of twinning pipes.
[Fig. 9.2.2]
<A>Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards (towards the twinning pipes).
A
C
B
<B>When the piping on the outdoor unit side (from the twinning pipe) exceeds 2 m [6 ft], ensure a trap (gas pipe only) within 2 m [6 ft].
Make sure the height of the trap is 200 mm [7-7/8 in] or more.
If there is no trap, oil can accumulate inside the pipe, causing a shortage of oil and may damage the compressor.
F
2[6
]
C
D
E
C
(Unit: m [ft])
F
C
8
<C>Slope of twinning pipes
G
Make sure the slope of the twinning pipes are at an angle within ±15˚ to the ground.
If the slope exceeds the specified angle, the unit may be damaged.
F
±15°
<D>Pipe connection example
H
GBDFEINLPGRRUTRCZSVSLHGPO
I
H
J
A Downward slopeB Upward slopeC 1st branchD Trap (gas pipe only)E Within 2 m [6 ft]
F Twinning pipeG Slope of the twinning pipes are at an angle within ±15˚ to the groundH Pipes on site
I Twinning KitJ Straight run of pipe that is 500 mm [19-11/16 in] or more
10. Additional refrigerant charge
At the time of shipping, the outdoor unit is charged with refrigerant.
This charge does not include the amount needed for extended piping and additional
charging of each refrigerant line will be required on site. In order that future servicing
may be properly provided, always keep a record of the size and length of each
refrigerant line and the amount of additional charge by writing it in the space provided
on the outdoor unit.
10.1. Calculation of additional refrigerant
charge
• Calculate the amount of additional charge based on the length of the piping
extension and the size of the refrigerant line.
• Use the table below as a guide for calculating the amount of additional charg-
ing and then charge the system accordingly.
• If the calculation results in a fraction of less than 0.1 kg [4 oz], round up to the
next 0.1 kg [4 oz]. For example, if the result of the calculation was 11.38 kg
[402 oz], round the result up to 11.4 kg [404 oz].
<Additional Charge>
Additional
refrigerant charge
(kg) [oz]
Liquid pipe size
Total length of
ø19.05 mm [3/4"]
=++
(m) × 0.29 (kg/m)
(ft)
×
3.1 (oz/ft)
Liquid pipe size
Total length of
+++ α
ø9.52 mm [3/8"]
(m) × 0.06 (kg/m)
(ft)
×
0.65 (oz/ft)
Liquid pipe size
Total length of
ø15.88 mm [5/8"]
(m) × 0.2 (kg/m)
(ft)
×
2.15 (oz/ft)
Liquid pipe size
Total length of
ø6.35 mm [1/4"]
(m) × 0.024 (kg/m)
(ft)
×
0.26 (oz/ft)
Liquid pipe size
Total length of
ø12.7 mm [1/2"]
(m) × 0.12 (kg/m)
(ft)
×
1.29 (oz/ft)
<Example>
Indoor
1: 48 A: ø12.7 mm [1/2"] 40 m [131 ft] a: ø9.52 mm [3/8"] 10 m [32 ft]
2: 36 B: ø9.52 mm [3/8"] 10 m [32 ft] b: ø9.52 mm [3/8"] 5 m [16 ft]
3: 15 C: ø9.52 mm [3/8"] 15 m [49 ft] c: ø6.35 mm [1/4"] 10 m [32 ft]
4: 12 D: ø9.52 mm [3/8"] 10 m [32 ft] d: ø6.35 mm [1/4"] 10 m [32 ft]
5: 24e: ø9.52 mm [3/8"] 10 m [32 ft]
The total length of each liquid line is as follows:
ø12.7 mm [1/2"]: A = 40 m [131 ft] = 40 m [131 ft]
ø9.52 mm [3/8"]: B + C + D + a + b + e
= 10 m [32 ft] + 15 m [49 ft] + 10 m [32 ft] + 10 m [32 ft] +
5 m [16 ft] + 10 m [32 ft] = 60 m [193 ft]
ø6.35 mm [1/4"]: c + d = 10 m [32 ft] + 10 m [32 ft] = 20 m [64 ft]
Therefore,
<Calculation example>
Additional refrigerant charge
= 40 m [131 ft] × 0.12 kg/m [1.29 oz/ft] + 60 m [193 ft] × 0.06 kg/m [0.65 oz/ft]
+ 20 m [64 ft] × 0.024 kg/m [0.26 oz/ft] + 3.5 kg [124 oz] = 12.4 kg [435 oz]
Value of α
Total capacity of connecting indoor unitsα
Models~ 272.0 kg [71 oz]
Models28~ 542.5 kg [89 oz]
Models55~ 1263.0 kg [106 oz]
Models 127~ 1443.5 kg [124 oz]
Models 145~ 1804.5 kg [160 oz]
Models 181~ 2345.0 kg [177 oz]
Models 235~6.0 kg [212 oz]
At the
conditions
below:
9
10.2. Precautions concerning piping connection and valve operation
• Conduct piping connection and valve operation accurately.
• The gas side connecting pipe is assembled in the factory before shipment.
1 For brazing to the connecting pipe with flange, remove the connecting
pipe with flange from the valve, and braze it outside of the unit.
2 The refrigerant circuit is closed with a round, close-packed packing upon
shipment to prevent gas leak between flanges. As no operation can be
done under this state, be sure to replace the packing with the hollow packing attached at the piping connection.
3 At the mounting of the hollow packing, wipe off dust attached on the flange
sheet surface and the packing. Coat refrigerating machine oil (Ester oil,
ether oil or alkylbenzene [small amount]) onto both surfaces of the packing.
[Fig. 10.2.1]
C
A Close-packed packing
B Hollow packing
GBDFEINLPGRRUTRCZSVSLHGPO
D
E
• After evacuation and refrigerant charge, ensure that the handle is fully open. If
operating with the valve closed, abnormal pressure will be imparted to the
high- or low-pressure side of the refrigerant circuit, giving damage to the compressor, four-way valve, etc.
• Determine the amount of additional refrigerant charge by using the formula,
and charge refrigerant additionally through the service port after completing
piping connection work.
• After completing work, tighten the service port and cap securely so as not to
generate any gas leakage.
• Flare machining dimension for systems using R410A is larger than that for
systems using other types of refrigerant in order to increase the air tightness.
• Refer to the table on the below for flare machining dimensions, and follow the
regulations set forth by the local authorities.
flare machining dimension (mm)
outer diameter
ø6.35
A
ø9.52
ø12.7
ø15.88
ø19.05
flare nut size (mm)
outer diameter
ø6.35
ø9.52
B
ø12.7
ø15.88
ø19.05
A
C Valve
D Packing
E Connecting pipe with flange
B
size in inches
1/4"
3/8"
1/2"
5/8"
3/4"
size in inches
1/4"
3/8"
1/2"
5/8"
3/4"
dimension A
R410A
13.2
16.6
19.7
24.0
dimension B
R410A
17.0
22.0
26.0
29.0
36.0
9.1
A Service port
For vacuuming in the refrigerant pipes on the site.
(Tightening torque 12 N·m [120 kg·cm])
B Shaft
Fully closed at the factory, when connecting the piping, and when vacuuming.
Open fully after these operations are completed.
<When opening>
• Turn the shaft counterclockwise with a hexagonal wrench.
• Turn around the shaft until it stops.
<When closing>
• Turn the shaft clockwise with a hexagonal wrench.
• Turn around the shaft until it stops.
C Flare nut
Coat the flare contact surface with refrigerating machine oil (small amount of
ester oil, ether oil, or alkyl benzene) and tighten the nut with a double-ended
wrench (refer to the following table for tightening torque).
D Cap
Remove the cap before operating the shaft. Be sure to return it to the original
position after completing the operation.
E Packing
Coat both sides of the packing with machine refrigerating oil (small amount of
ester oil, ether oil, or alkyl benzene) and tighten the flange.
(Tightening torque 25 N·m [250 kg·cm])
F Connecting pipe (accessory)
Be sure to remove the connecting pipe from the valve and braze it outside the unit.
G Field piping
Braze to the connecting pipe with unoxidized brazing.
H ø9.52 mm [3/8"] (PUHY-HP72, HP96, when combining PUHY-HP72, HP96)
ø12.7 mm [1/2"] (PUHY-HP72, HP96)
I ø22.2 mm [7/8"] (PUHY-HP96)
J ø19.05 mm [3/4"] (PUHY-HP72)
Appropriate tightening torque:
Outer diameter of
copper pipe (mm [in])
ø9.52 [3/8]
ø12.7 [1/2]
ø15.88 [5/8]
ø19.05 [3/4]
ø25.4 [1]
Cap (N·m /kg·cm)
22/220
20/200
25/250
25/250
40/400
Shaft (N·m /kg·cm)
5/50
9/90
15/150
15/150
30/300
Size of hexagonal
wrench (mm)
4
4
6
6
10
Appropriate tightening torque and its angle:
Outer diameter of
copper pipe (mm [in])
ø9.52 [3/8]
ø12.7 [1/2]
ø15.88 [5/8]
ø19.05 [3/4]
Tightening torque
(N·m/kg·cm)
35 - 42/350 - 420
50 - 57.5/500 - 575
75 - 80/750 - 800
100 - 140/1000 - 1400
Tightening angle
(°)
60 to 90
30 to 60
20 to 35
Warning:
When connecting a pipe to the service valve, be sure to use only the supplied
open-end flare nut, with small holes cut into the flats.
* Using a regular flare nut (i.e., non-supplied) will result in any water that
naturally flows into the nut being unable to escape.
Consequently , when the temperature becomes lo w, this water inside the nut
may freeze and cause damage to the joint. This, in turn, may result in a gas
leakage.
[Fig. 10.2.3]
[Fig. 10.2.2]
<A> Valve
liquid side/
()
flared type
A
B
C
<B> Valve
gas side/
()
flanged type
H
10
<C> Valve
gas side/
()
flared type
D
Note:
If a torque wrench is not available, use the following method as a standard;
When you tighten the flare nut with a wrench, you will reach a point where
the tightening torque will abruptly increase. Turn the flare nut beyond this
point by the angle shown in the table above.
E
C
F
G
I
J
Caution:
F
D
•Always remove the connecting pipe from the valve and braze it outside
the unit.
-Brazing the connecting pipe while it is installed will heat the valve and cause
trouble or gas leakage. The piping, etc. inside the unit may also be burned.
• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerating machine oil to coat flares and flange connections.
- The refrigerating machine oil will deg rade if it is mix ed with a large amount of
mineral oil.
•Keep the valve closed until refrigerant charging to the pipes to be added
on site has been completed. Opening the valve before charging the refrigerant may result in unit damage.
• Do not use a leak detection additive.
[Fig. 10.2.4]
Caution:
Make sure to seal-off and excess space around areas where the wires and
refrigerant pipes enter the unit.
• Small animals and rainwater entering through the openings may cause
damage to the device.
10.3. Airtight test, evacuation, and refrigerant
charging
1 Airtight test
Perform with the valve of the outdoor unit closed, and pressurize the connection piping and the indoor unit from the service port provided on the valve of
the outdoor unit. (Always pressurize from both the liquid pipe and the gas pipe
service ports.)
[Fig. 10.3.1]
A
A Example of closure materials (field supply)
B Fill the gap at the site
Make sure to seal-off and excess space around areas where the wires and
refrigerant pipes enter the unit to ensure that small animals and rainwater cannot
enter the unit through such openings and cause damage to the unit.
1. Nitrogen gas pressurization
(1) After pressurizing to the design pressure (4.15 MPa [602 psi]) using nitrogen gas, allow it to
stand for about one day. If the pressure does not drop, airtightness is good.
However, if the pressure drops, since the leaking point is unknown, the following bubble test
may also be performed.
(2) After the pressurization described above, spray the flare connection parts, brazed parts, flanges,
and other parts that may leak with a bubbling agent (Kyuboflex, etc.) and visually check for
bubbles.
(3) After the airtight test, wipe off the bubbling agent.
2. Pressurization using refrigeration gas and nitrogen gas
(1) After first pressurizing with R410A liquid refrigerant to a gas pressure of approximately 0.2
Mpa [29 psi], pressurize to the design pressure of 4.15 Mpa [602 psi] using nitrogen gas.
However, do not pressurize at one time. Stop during pressurization and check that the pressure does not drop.
(2) Check for gas leaks by checking the flare connection parts, brazed parts, flanges, and other
parts which may leak using an R410A compatible electric leak detector.
(3) This test may be used together the with bubble type gas leak test.
B
Observe the following restrictions when conducting an air tightness test to prevent
negative effects on the refrigerating machine oil. Also, with nonaz eotropic refrigerant (R410A), gas leakage causes the composition to change and affects performance. Therefore, perform the airtightness test cautiously.
Airtight test procedure
B
B
C
A
C
A Nitrogen gasB To indoor unitC System analyzer
D Lo knobE Hi knobF Valve
G Liquid pipeH Gas pipeI Outdoor unit
J Service port
• If a flammable gas or air (oxygen) is used as the pressurization
gas, it may catch fire or explode.
• Do not use a refrigerant other than that indicated on the unit.
• Sealing with gas from a cylinder will cause the composition of
the refrigerant in the cylinder to change.
• Use a pressure gauge, charging hose, and other parts especially
designed for use with R410A.
• An electric leak detector for R22 cannot detect leaks of R410A.
• Do not use a haloid torch. (Leaks cannot be detected.)
LO
D
HI
E
Restriction
G
H
I
J
GBDFEINLPGRRUTRCZSVSLHGPO
Caution:
Only use refrigerant R410A.
- The use of other refrigerant such as R22 or R407C, which contains chlorine, will
deteriorate the refrigerating machine oil or cause the compressor to malfunction.
2 Evacuation
Evacuate with the valve of the outdoor unit closed and evacuate both the connection piping and the indoor unit from the service port provided on the valve
of the outdoor unit using a vacuum pump. (Always evacuate from the service
port of both liquid pipe and gas pipe.) After the vacuum reaches 650 Pa [abs]
[0.0943 psi/5 Torr], continue evacuation for at least one hour or more. Then,
stop the vacuum pump and leave it for 1 hour. Ensure the degree of vacuum
has not increased. (If the degree of vacuum increase is larger than 130 Pa
[0.01886 psi/1.0 Torr], water might have entered. Apply pressure to dry
nitrogen gas up to 0.05 MPa [7.25 psi] and vacuum again.) Finally, seal in
with the liquid refrigerant through the liquid pipe, and adjust the gas piping to
obtain an appropriate amount of the refrigerant during operation.
* Never perform air purging using refrigerant.
[Fig. 10.3.2]
EN
N
A
LO
B
A System analyzerB Lo knobC Hi knob
D ValveE Liquid pipeF Gas pipe
G Service portH Three-way jointI Valve
J ValveK R410A cylinderL Scale
M Vacuum pumpN To indoor unitO Outdoor unit
HI
C
H
F
O
G
I
K
J
L
M
11