Mitsubishi Electronics PUHY-80TMU-A, 100TMU-A User Manual

AIR CONDITIONERS CITY MULTI Series Y
Models PUHY-80TMU-A, 100TMU-A
Service Handbook
Service Handbook PUHY-80TMU-A, 100TMU-A
- Inadequate connection and fastening may generate heat and cause a fire.
• Prepare for typhoons and other strong winds and earth­quakes and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in
injury.
• Always use an air cleaner, humidifier, electric heater, and other accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Im-
proper installation by the user may result in water leakage, electric shock, or fire.
• Never repair the unit. If the air conditioner must be re­paired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric
shock, or fire may result.
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poison-
ous gases will be released.
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric
shock, or fire may result.
• Have all electric work done by a licensed electrician ac­cording to “Electric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock and fire may result.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed properly, dust or water
may enter the outdoor unit and fire or electric shock may re­sult.
• When installing and moving the air conditioner to another
refrigerant (R22) specified on the unit.
- If a different refrigerant or air is mixed with the original refriger-
ant, the refrigerant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to pre-
vent the safety limit from being exceeded. Should the refriger­ant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage,
electric shock, or fire may result.
• After completing installation work, make sure that refriger­ant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater,
stove, oven, or other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection de-
vice is shorted and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
Before installation and electric work
ss
ss
s Before installing the unit, make sure you read all
the “Safety precautions”.
ss
ss
s The “Safety precautions” provide very important
points regarding safety. Make sure you follow them.
ss
ss
s This equipment may have an adverse effect on
equipment on the same electrical supply system.
ss
ss
s Please report to or take consent by the supply au-
thority before connection to the system.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided. : Indicates that important instructions must be followed. : Indicates a part which must be grounded. : Indicates that caution should be taken with rotating parts.
(This symbol is displayed on the main unit label.) <Color: Yellow>
: Indicates that the main switch must be turned off before
servicing. (This symbol is displayed on the main unit label.) <Color: Blue>
: Beware of electric shock (This symbol is displayed on the
main unit label.) <Color: Yellow>
: Beware of hot surface (This symbol is displayed on the main
unit label.) <Color: Yellow>
ELV
: Please pay attention to electric shock because this
is not Safety Extra Low-Voltage (SELV) circuit. And at servicing, please shut down the power supply
for both Indoor Unit and Outdoor Unit .
Warning:
Carefully read the labels affixed to the main unit.
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage,
electric shock, or fire.
• Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting
in injuries.
• Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not ap­plied to the terminals.
Safety precautions
site, do not charge it with a refrigerant different from the
Contents
1 COMPONENT OF EQUIPMENT 1
[1] Appearance of Components 1 [2] Refirigerant Circuit Diagram and Thermal Sensor
Standard operation data
iger 6
[3] PUHY-80, 100TMU-A ELECTRICAL WIRING
DIAGRAM 7
9
[4] [5] Function of dip SW and rotary SW 11
2 TEST RUN 15
[1] Before Test Run 15 [2] Test Run Method 19
3 GROUPING REGISTRATION OF INDOOR UNITS WITH
M-NET REMOTE CONTROLLER 20
4 CONTROL 26
[1] Control of Outdoor Unit 26 [2] Operation Flow Chart 31 [3] List of Major Component Functions 36 [4] Resistance of Temperature Sensor
Refrigerant Amount and Operating Characteristics
38
5 REFRIGERANT AMOUNT ADJUSTMENT 39
[1] 39 [2] Adjustment and Judgement of Refrigerant Amount 39
6 TROUBLESHOOTING 44
[1] Principal Parts 44 [2] Self-diagnosis and Countermeasures Depending on the
Check Code Displayed 62
[3] LED Monitor Display......................................................
...............................................................................
............................................................
...............................................................................
...........................................................
....................................................
...........................................
..................................................
...............................................
............................................
.......................................................................
...........
................................
.................................................
..................................................
................................................................
.............................................................
..............................
...............................
...............................
.......
.......
83
Propeller fan
Fan motor
-1-
Rear Controller Box
INV board
MAIN board
Choke coil(L2)
Interrigent Power Module(IPM)
Magnetic contactor(52C)
Capacitor (C1)(Smoothing capacitor)
Gate Amplifier board(G/A board)
Diode stack(DS) Power board
Terminal block(TB7)Transmission
Terminal block (TB3) Transmission
Terminal block (TB1) Power source
-2-
MAIN board
CNS1 M-NET Transmission (DC30V)
CNS2 M-NET Transmission (Centralized control) (DC30V)
CN40 M-NET Transmission Power supply
CNVCC3 Power source for contorl
1-2 DC30 V 1-3 DC30 V 4-6 DC12 V 5-6 DC5 V
CN51 Indication distance 3-4 Compressor ON/
Off
3-4 trouble
LD1 Service LED
CNRS53 Serial transmission to INV board
CN3D
CN3S
CNFAN1 control for MF1
CNAC3
CN20 power source
SW1,2,3,4 Dip Switch
-3-
INV board
CNDC2 1-3 DC310 V
CN15V2 Power supply IPM control
1-2 DC15 V 5-6 DC15 V 9-0 DC15 V C-D DC15 V
CNL2 Choke coil
CNRS2
Serial transmission
to MAIN board
CNAC2 Power source
1 L2 5 N
CNFAN
Control for
MF1
CN52C
Control for
52C
CNVCC2 power supply
CNCT
CNVCC4
CNTH
CNDR2 IPM control signal
SW1
-4-
G/A board
Power board
DC310V
CNDC1 1 - 3 DC310V
CN15V1 Power Supply IPM control
1 - 2 DC15V 5 - 6 DC15V 9 - 0 DC15V C - D DC15V
CNDR1 IPM control signal
-5-
[2] Refirigerant Circuit Diagram and Thermal Sensor
1 PUHY-80TMU-A, 100TMU-A
TH1
TH6
TH7
TH8
TH5
TH2
O/S
63HS
CJ1
Comp
HEXFHEXB
SCC
LEV1
ST7
BV2
ST2
Indoor
Unit
BV1
ST1
CJ2
CV1
ST6
SV1
CP1
SV2
SLEV
SA
MA
CP2
63H
High pressure safety valve
Accumulator
-6-
[3] PUHY-80, 100TMU-A ELECTRICAL WIRING DIAGRAM
CNS2
(3P)
FN3
FN2
1 2
C
CNS2
(3P)
FN3
FN2
C 1
R 1
52C
DCCT
1 2 3
TH6 TH5TH8TH7TH2 TH1 63HS
SW3-10 are OFF for Model 80.
and ON for Model 100.
Trouble
Compressor ON/OFF
Snow sensor
Compressor ON/OFF
Night mode
Ground
123451234
5
54321
32132
1
1 2 3 1 2 3 4 5 6 7 8
1 2
1 2 3
1 2
321
L1L2L3
+
DS(Diode stack)
Power source
3~208~230V
SLEV
CN20
(7P)
CN03
(3P)
CN02
(8P)
CN01
(2P)
CNH
(3P)
CNLV1
(5P)
Blue
CNLV2
(5P)
Red
CN51
(5P)
CN3D
(3P)
CN3S
(3P)
Red
CNS1
(2P)
CNS2
(3P)
T B 3
T B 7
A B
1 2 3 4
1 2 3 4
CN40
(4P)
CN41
(4P)
54321
Connect to
indoor and
remote
controller
GR
Red
Black
-
Red
12V
DSA
3 2 1
1 2
THHS
52
1234567123456
12345
CNRS3
(7P)
CNVCC3
(6P)
CNAC3
(5P)
GL3L1
Control circuit board
(MAIN-BOARD)
LD1
1
10
1
10
1
10
OFF ONOFF ONOFF ON
Unit address setting switch
X 0 1
A B Shield
G
L3
F2
6.3A
F1
6.3A
ZNR1~4
Red
CNFAN1
(5P)
Red
54321
CN38
(3P)
Green
CN34
(6P)
CN33
(6P)
CN32
(3P)
321
321
65432
1
65432
1
FN4
FN6
FN2
FN3
FN1
Noise filter board
(POWER-BOARD)
Red White Black Green
Red White Black
F01
2A
R2
1 2 1 2
Green
CNTH
(2P)
CNL2
(2P)
Red
CN30V
(2P)
Red
CNFAN
(3P)
R2
U W
1 2 1 2
MF
L2
R2
F01
2A
12345
12345
6
CNVCC4
(2P)
1
2
CNAC2
(5P)
1234567
CNVCC2
(6P)
123
Red
Black
+
1 2 3 4
CNRS2
(7P)
CNCT
(4P)
(3P)
Yellow
CNDC1
(3P)
1 2 3 4
CN52C
CN15V1
(14P)
CNDR1
(9P)
CNDC2
(3P)
Yellow
CNDR2
(9P)
CN15V2
(14P)
Power circuit board
(INV-BOARD)
Black
White
Red
Gate amp board
(G/A-BOARD)
1 2 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3
1 2 3
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3 4 5 6 7 8 9
U V W
F01
3.15A
21
S4
SV
CNVCC5
(2P)
1
2
1
2
GL3L1
Detection
Circuit
ONOFF
10
1
2
CNE
(2P)
1
L2 L1
Ground
X01
N
P
DCL
V
LEV1
SW1SW2SW3SW4
SWU1SWU2
X04
X05
X02
63H
MF
CH1
SV1
60Hz
TB1
MC
2
IPM
1
1357
1 2 3
-7-
S W U 1 ~ 2
T B 1
Switch unit address set
Terminal block power source
T B 3
T B 7
Terminal block transmisson
GR
Ground terminal
Terminal block transmisson
centralized control
L D 1
S W 1
S W 2 ~4
Switch function selection
Switch display selection self-diagnosis
Luminous diode
T H 8
bypass outlet temp.
detect at Sub-cool coil
T H H S
Rediator panel temp.detect
6 3 H S
High pressure sensor
S L E V
L E V 1
Electronic expansion valve
(Oil return)
Electronic expansion valve
(Sub-cool coil bypass)
L 2
Choke coil(Transmission)
T H 7
liquid outlet temp.
detect at Sub-cool coil
T H 5
T H 2
T H 1
pipe temp.detect
T H 6
OA temp.detect
saturation
evapo.temp.detect
Thermistor
Thermistor
6 3 H
High pressure switch
S V 1 , S V 2
Solenoid valve
(Discharge-suction bypass)
C H 1
Crankcase heater (Compressor)
D S A
Surge absorber
Motor Compressor
Motor Fan Heat exchanger
Motor Fan Radiator panel
M F 1
M F
M C
5 2 C
Magnetic contactor
(Inverter main circuit)
Z N R 1 ~ 4
Varistor
C 1
Capacitor Smoothing
Resistor rush current protect
D C C T
Current Sensor
R 1
R 2
Resistor power regulation
D C L
DC reactor
(Power factor improvement)
I P M
Intelligent Power Module
D S
Diode stack
Symbol
Name
Symbol
Name
Symbol
Name
Symbol
Name
discharge pipe temp.detect
4-way valve
2 1 S 4
OFF : 0
ON : 1
(at factory shipment)
FLAG7
FLAG1
FLAG6
Display
Relay output
display
(Lighting)
During
compressor
run
Crankcase
heater
0000~9999
Display the address and error codes by turns
21S4
SV1 SV2
Check display
(Blinking)
Display at LED lighting (blinking) Remarks SW1 operation
FLAG3 FLAG4FLAG2 FLAG5
FLAG8
FLAG8 always lights at
microcomputer power ON
Always
lighting
<Operation of self-diagnosis switch (SW1) and LED display>
<LED display>
LD1
FLAG8
FLAG7
FLAG6
FLAG5
FLAG4
FLAG3
FLAG2
FLAG1
1 2 3 4 5 6 7 8 9 10
-8-
[4] Standard operation data
1 Cooling operation
75 81
111 157
Discharge (TH1) Heat exchanger outlet (TH5)
Inlet
Accumulator
Outlet
Suction (Comp) low pressure saturation
temperature (TH2) Shell bottom (Comp)
SCC outlet (TH7) Bypass outlet (TH8) LEV inlet Heat exchanger outlet
Outdoor units
Items
Condition
Pressure
LEV opening
Sectional temperature
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
Ambient temp.
Indoor unit
Piping
Indoor unit fan notch Refrigerant volume
Outdoor unit
Compressor volts/Frequency
Indoor unit SC (LEV1) Oil return (SLEV)
DB/WB
Set
m
(Ft)
PUHY-80TMU-A PUHY-100TMU-A
kg(oz)
A
V
V/Hz
Pulse
Outdoor unit
85(185) 95(203) 40(104) 42(108)
7(45) 5(41)
9(48) 7(45) 7(45) 10(50) 6(43) 4(39)
60(140) 60(140)
27(81) 27(81)
8(46) 6(43)
26(79) 26(79)
10(50) 10(50)
2.00/0.50 (290/72)
1.99/0.46 (288/67)
°C
(°F)
MPa(psi)
High pressure/Low pressure (after O/S) (before MA)
Indoor unit
24 24 20 10 48 16 24 10
5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4)
Hi Hi Hi Hi Hi Hi Hi Hi
440 440 380 300 450 320 440 300
26.7°C(80°F)/19.4°C(67°F) 35°C(95°F)
4 4
4 4
5(16.4) 5(16.4)
25(82) 25(82)
10.2(360) 12.5(441)
27.4
208
134/76
230
134/76
208
171/98
230
171/98
24.8 35.2 31.8
-9-
00
87 111
Discharge (TH1) Heat exchanger inlet (TH5)
Inlet
Accumulator
Outlet
Suction (Comp) low pressure saturation
temperature (TH2) Shell bottom (Comp)
Heat exchanger inlet LEV inlet
2 Heating operation
Outdoor units
Items
Condition
Pressure
LEV opening
Sectional temperature
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
Ambient temp.
Indoor unit
Piping
Indoor unit fan notch Refrigerant volume
Outdoor unit
Compressor volts/Frequency
Indoor unit SC (LEV1) Oil return (SLEV)
DB/WB
Set
m
PUHY-200TM-A PUHY-250TM-A
27.5
208
149/85
24.9
230
149/85
35.6
208
174/100
32.2
230
174/100
kg
A
V
V/Hz
Pulse
80
85(185)
6(46) 8(46)
1(30) 2(28)1(30) 2(28)1(30) 2(28)2(28) 2(28)
35(95) 44(111)
71(160) 71(160)
33(91) 33(91)
1.72/0.36 (249/52)
1.72/0.36 (249/52)
MPa(psi)
High pressure/Low pressure (after O/S) (before MA)
°C
(°F)
Outdoor unit
Indoor unit
24 24 20 10 48 16 24 10
5(16.4) 5(16.4)5(16.4)5(16.4)5(16.4)5(16.4)5(16.4)5(16.4)
Hi Hi Hi Hi Hi Hi Hi Hi
510 510 450 300 350 380 510 300
21.1°C(70°F)
8.3°C(47°F)/6.1°C(43°F) 4 4
4 4
5(16.4) 5(16.4)
25(82) 25(82)
10.2(360) 12.5(441)
-10-
[5] Function of dip SW and rotary SW
(1) Outdoor unit
Switch Function
Function According to Switch Operation Switch Set Timing
When Off When On When Off When On Unit Address Setting For self diagnosis/ operation monitoring
– Centralized Control Switch Deletion of connection information.
Deletion of error history.
Adjustment of Refrigerant Volume
– Disregard ambient air sensor errors, fluid overflow errors. Forced defrosting
Defrost prohibited timer
– SW3-2 Function Valid/ Invalid Indoor Unit Test Operation Defrosting start temperature of TH5. Defrosting end temperature of TH5. Opening angle of IC except when heater thermostat is ON during defrosting.
Target Pd (High pressure)
– –
– –
– –
– –
– –
– –
– –
– –
– –
Models
LED Display "°F" "psig" Display "°C" "kgf/cmG "Display When switching on the power
Fan characteristics ( )
Standard High external
static pressure
When switching on the power
– Centralized control not connected. Storing of refrigeration system connection information.
Ordinary control
– Errors valid.
Ordinary control
50 min.
– SW3-2 Function Invalid
Stop all indoor units.
-2°C
(28.4°F) (32°F)
8HP: 12°C(53.6°F)
10HP: 8°C(46.4°F)
(no operation)
18kg/cm
2
G
(256psi)
20kg/cm2G
(284psi) – –
Model 80
Set on 00 or 51~100 with the dial switch. (
2)
LED Monitering Display
– Centralized control connected. Deletion of refrigeration system connection information. Deletion
Refrigerant volume adjustment operation.
– Disregard errors.
Start forced defrosting.
90 min.
– SW3-2 Function Valid
All indoor units test operation ON.
0°C
15
(59°F)
°C
2000
– Model 100
During normal operation when power is on.
Before power is turned on. During normal operation when power is on. Should be set on OFF. Before power is turned on.
Before power is turned on.
During normal operation when power is on.
– During normal operation when power is on.
During normal operation when power is on. (Except during defrosting)
– During normal operation when power is on. When SW3-1 is ON after power is turned on. During normal operation when power is on. During normal operation when power is on. (Except during defrosting)
– When switching on the power. During normal operation when power is on.
– When switching on the power.
Invalid 2 hours after compressor starts.
During normal operation when power is on.
10 minutes or more after compressor starts.
Note:
1. SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
1
2. If the address is set from 01 to 50, it automatically becomes 100.
SWU
SW1
SW2
SW3
SW4
1~2 1~8
9~10
1
2
3
4
5 6
7
8
9
10
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
-11-
2. SW4-9 setting
Fan characteristics curve:DIPSW4-7ON,230V/60Hz
Fan characteristics curve:DIPSW4-7ON,208V/60Hz
0
5
10
15
20
25
30
35
40
45
50
150 160 180 190 200 210 220 230 240
Standard Airflow rate
200(m
3
/min)
Fan characteristics curve:DIPSW4-7OFF[FactorySetting],208V230V/60Hz
Continuous operation range
Airflow rate (m3/min)
External static pressure (Pa)
170
-12-
(2) Indoor unit
DIP SW1, 3
Model 32 40 48 Capacity (model name) code
16 20 25
SW2 setting
Model 08 10 12 16 20 24 Capacity (model name) code
45 681013
SW2 setting
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the
table below.)
2: The DipSW setting is only effective during unit stopping (remote controller OFF) for SW1, 2, 3 and 4 commonly
and the power source is not required to reset.)
3: When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat of OFF.
Setting of DIP SW2
Model
Switch
SW1
SW3
3 6 7 3 4 6 8
PLFY-NAMU-A
ON ON
OFF
ON
ON OFF OFF
Indoor unit inlet
None
100h
Ineffective Fan output display At stationary heating
Very low speed
SW1-7 setting
Ineffective
Heat pump
None
None None
1st setting
Down blow B, C
Effective
– –
Built in remote controller
Provided
2500h
Effective
Thermo. ON signal display
Always at heat.
Low speed
Set airflow
Effective
Cool.only
Provided
Provided Provided
2nd setting
Horizontal
Ineffective
– –
Room temp. sensor position Clogged filter detect. Filter duration OA intake Remote display select. Humidifier control Heating thermo. OFF airflow Heating thermo. OFF airflow Power failure automatic
return
Model selection
Louver
Vane Vane swing function Vane horizontal angle Vane angle set for cooling
Heating 4deg (7.2 deg) up Note : °C scale (°F scale)
– –
Always ineffective for PKFY-NAMU
Not provided for PKFY-NAMU Provided for PLFY-NGMU (ON) setting
Always down blow B,C for PKFY-NAMU
SW1
SW3
1 2 3 4 5 6 7 8
9
10
1
2
3 4 5 6 7
8 9
10
Switch SW name
Operation by SW
Switch set timing
OFF ON OFF ON
Remarks
At unit stopping
(at remote
controller OFF)
Cooling capacity saving
for PKFY-NAMU, effective/ineffective
PDFY-NMU-A
ON
ON OFF OFF OFF OFF OFF
PKFY
OFF OFF OFF
ON
OFF OFF
NAMU-A NGMU-A
OFF ON
-13-
Setting of DIP SW4 Setting of DIP SW5
1234
ON OFF ON OFF
OFF OFF OFF ON
ON OFF OFF ON
OFF OFF ON ON
––––
OFF OFF ON
PDFY-10 ~ 32 PLFY-12 ~ 24 PLFY-32 ~ 48 PKFY-P-8 PKFY-P-12 PDFY-40, 48
Model Circuit board used
SW4
Phase control
Relay selection
-14-
TEST RUN
[1] Before Test Run
(1) Check points before test run
1 Neither refrigerant leak nor loose power source/ transmission lines should be found, if found correct immediately.
2 Confirm that the resistance between the power source terminal block and the ground exceeds 2M by measur-
ing it with a DC500V megger. Do not run if it is lower than 2MΩ. Note : Never apply the megger to the MAIN board. If applied, the MAIN board will be broken.
3 Confirm that the Ball valve at both gas and liquid sides are fully opened.
Note : Close the cap.
4 Be sure that the crankcase heater has been powered by turning the main power source on at least 12 hours
before starting the test run. The shorter powering time causes compressor trouble.
(2) Caution at inverter check
Because the inverter power portion in outdoor unit electrical part box have a lot of high voltage portion, be sure to follow the instructions shown below.
During energizing power source, never touch inverter power portion because high voltage (approx. 320V) is applied to inverter power portion.
When checking,
Shut off main power source, and check it with tester, etc.
Allow 10 minutes after shutting off main power source.
Open the MAIN board mounting panel, and check whether voltage of both ends of electrolytic capacitor is 20V or less.
1
2
1
2
3
2
-15-
(3) Check points for test run when mounting options
(4) Attention for mounting drain water pump mechanism
Check point
Local remote controller displays code No. 2503, and the mechanism stops.
No overflow from drain pan. Drain water comes out by operation of
drain pump. Sound of pump operations is heard, and
drain water comes out. No water leak from connecting portions
of each water piping. Water is supplied to water supply tank,
and float switch is operating.
Built-in optional parts Mounting of drain
water pump mechanism
Mounting of perme­able film humidifier
Content of test run
Release connector of pump circuit, check error detection by pouring water into drain pan water inlet.
After that, connect connector of circuit.
Check pump operations and drain­age status in cooling (test run) mode.
Check humidifier operations and water supply status in heating (test run) mode.
1
2
3
4
5
Result
1
2
3
Work
Disassembling and assembling of drain water pump mechanism
Mounting of float switch
Electric wiring
Float switch moves smoothly . Float switch is mounted on
mounting board straight without deformation.
Float switch does not contact the
copper pipe. Wiring procedure is exactly followed. Connector portion is tightly hooked.
Content of test run
Lead wire from control box not damaged.
Rubber cap properly inserted in to drain water outlet of drain pan?
Insulation pipe of gas and liquid pipes dealt with as shown on next page?
Drain pan and piping cover mounted without gap?
Drain pan hooked on cut projection of the mechanism?
Float switch installed without contacting the drain pan?
No mistakes in wiring? Connectors connected securely and
tightly? No tension on lead wire when sliding
control box?
1 2
3
1
2
3
Check point Result
Insulation pipe
No gap
-16-
Trouble
Not operate.
Not cool (at cooling). Not heat (at heating).
Not cool, not heat, error stop. Condensation drip in piping. Not cool, not heat, error stop.
Water leak, condensation drip in drain piping.
Error stop, not operate.
Electric shock. Error stop, not operate.
Classification
Installation and piping
Power source wiring
Portion
1
2
3
Check item
Instruction for selecting combination of outdoor unit, and indoor unit followed? (Maximum number of indoor units which can be connected, connecting model name, and total capacity.)
Follow limitation of refrigerant piping length? For example, 70m (229ft) or less (total length : 220m (721ft)) at the farthest.
Connecting piping size of branch piping correct? Refrigerant piping diameter correct? Refrigerant leak generated at connection? Insulation work for piping properly done? Specified amount of refrigerant replenished?
Pitch and insulation work for drain piping properly done? Specified switch capacity and wiring diameter of main
power source used?
Proper grounding work done on outdoor unit? The phases of the L line (L1, L2, L3) correct?
1
2
3
4
5
6
7
8
(5) Check points for system structure
Check points from installation work to test run.
-17-
Classification Transmission
line
Portion
1
2
3
4
5
6
7
8
Check item
Limitation of transmission line length followed? For example, 200m (656ft) or less (total length : 500m (1640ft)) at the farthest.
1.25mm2 (AWG16) or more transmission line used? (Remote controller 10m (32ft) or less 1.25mm2 (AWG16))
2-core cable used for transmission line?
Transmission line apart from power source line by 5cm (2in) or more? One refrigerant system per transmission line? The short circuit connector is changed form CN41 to
CN40 on the MAIN board when the system is centralized control? (Just one outdoor unit. Not all outdoor units.)
No connection trouble in transmission line? Connection of wrong remote controller line terminals?
MA Remote controller : TB15
M-NET Remote controller : TB5
Trouble
Erroneous operation, error stop.
Erroneous operation, error stop.
Error stop in case multiple-core cable is used.
Erroneous operation, error stop. Not operate. Not operate.
Error stop or not operate. Never finish the initial mode.
System set
Before starting
Error stop or not operate.
Can not be properly set with power source turned on.
Not operate. Set temperature not obtained at
heating operations (Thermostat stop is difficult)
Error stop.
Error stop, compressor trouble.
1
2
1
2 3
4
Address setting properly done? (M-NET Remote controller, indoor unit and outdoor unit.)
Setting of address No. done when shutting off power source?
Address numbers not duplicated? Turned on SW3-8 on indoor unit circuit board when
mounting room thermistor sensor?
Refrigerant piping ball valve (Liquid pressure pipe, gas pressure pipe) opened?
Turn on power source 12 hours before starting operations?
2 31
SET TEMP. ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE
DRY COOL
DAILY
TIMER
CHECK
AUTO
ONCLOCK
SET TEMP.
REMAINDER
NOT AVAILABLE
SENSOR
INSIDE FILTER
TEST RUN
VENTILATION
EROR CODE
AUTO
OFF
CENTRALLY CONTROLLED
AUTO FAN
HEAT
STAND BY DEFROST
FAN SPEED
TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
-18-
CENTRALLY CONTROLLED
DRY COOL
TIMER
DAILY
AUTO FAN
STAND BY DEFROST
PAR-F27MEA-US
AUTO
SET TEMP.
REMAINDER
CHECK
HEAT
EROR CODE
SET TEMP. ON/OFF
CLOCK ON OFF
MODE
TIMER FAN SPEED
TIMER SET
AUTO
ONCLOCK
OFF
FAN SPEED
VENTILATION
NOT AVAILABLE
AIR DIRECTION
LOUVER VENTILATION
SENSOR
TEST RUN
INSIDE FILTER
CHECK TEST
FILTER
[2] Test Run Method
Operation procedure
Turn on universal power supply at least 12 hours before starting Displaying HO on display panel for about two minutes
Press
TEST
1
2
3
4
5
6
7
8
9
button twice Displaying TEST RUN’’ on display panel
Press
MODE
button Make sure that air is blowing out
Press
MODE
button to change from cooling to heating operation, and vice versa Make sure that warm or cold
air is blowing out
Press
FAN SPEED
adjust button Make sure that air blow is changed
Press
AIR DIRECTION
or
LOUVER
ON/OFF
button to change direction of air blowing make sure that horizontal or
downward blow is adjustable.
Make sure that indoor unit fans operate normally Make sure that interlocking devices such as ventilator operate normally if any
Press button to cancel test run Stop operation
Note 1: If check code is displayed on remote controller or remote controller does not operate normally.
2: Test run automatically stops operating after two hours by activation of timer set to two hours. 3: During test run, test run remaining time is displayed on time display section. 4: During test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temperature
display section.
5: When pressing
FAN SPEED
adjust button, depending on the model, NOT A V AILABLE may be displayed on
remote controller. However, it is not a malfunction.
6: When pressing
AIR DIRECTION
or
LOUVER
button, depending on the model, NOT A V AILABLE may be
displayed on remote controller. However, it is not a malfunction.
-19-
3
GROUPING REGISTRATION OF INDOOR UNITS WITH M-NET REMOTE CONTROLLER
(1) Switch function
The switch operation to register with the remote controller is shown below:
Registration/ ordinary mode selector switch
Registration/ordinary mode selection switch
Switch to assign indoor unit address
Registration switch
Confirmation switch
Delete switch
Registered mode selector switch
Switch to assign interlocked unit address
+
This switch selects the ordinary mode or registered mode (ordinary mode represents that to operate indoor units).
To select the registered mode, press the
FILTER
+
LOUVER
button continuously for over 2 seconds under stopping state. [Note] The registered mode can not be obtained for a while after powering. Pressing the
FILTER
+
LOUVER
button displays “CENTRALLY
CONTROLLED. This button assigns the unit address for INDOOR UNIT ADDRESS
NO.
This button is used for group/interlocked registration.
This button is used to retrieve/identify the content of group and interlocked (connection information) registered.
This button is used to retrieve/identify the content of group and interlocked (connection information) registered.
This button selects the case to register indoor units as group (group setting mode) or that as interlocked (interlocked setting mode).
The unit address is shown at one spot for the group setting mode
while at two spots for the interlocked setting mode.
This button assigns the unit address of OA UNIT ADDRESS NO.
Symbol
of switch
Registered mode selector switch
Confirmation switch
Switch to assign indoor unit address
Switch to assign inter-
locked unit address
Registration switch
+
FILTER
TEST RUN
Name Name of actual switch Description
of TEMP
CLOCK ONOFF
of TIMER SET
Registration/ ordinary mode selector switch
SET TEMP. ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE
DRY COOL
DAILY
TIMER
CHECK
AUTO
ONCLOCK
SET TEMP .
REMAINDER
NOT AV AILABLE
SENSOR
INSIDE FILTER
TEST RUN
VENTILATION
EROR CODE
AUTO
OFF
CENTRALLY CONTROLLED
AUTO FAN
HEAT
STAND BY DEFROST
FAN SPEED
TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
Delete switch
LOUVER
TIMER
MODE
A
A
B
B
F
F
G
G
E
E
D
D
C
C
H
H
ii
i
-20-
(2) Attribute display of unit
At the group registration and the confirmation/deletion of registration/connection information, the type (attribute) of the unit is displayed with two English characters.
Display Type (Attribute) of unit/controller
Indoor unit connectable to remote controller Outdoor unit
Local remote controller System controller (MJ)
[Description of registration/deletion/retrieval]
The items of operation to be performed by the remote controller are given below. Please see the relating paragraph for detail.
Group registration of indoor unit
The group of the indoor units and operating remote controller is registered.
It is usually used for the group operation of indoor units with different refrigerant system.
Retrieval/identification of group registration information of indoor units
The address of the registered indoor units in group is retrieved (identified).
Retrieval/identification of registration information
The connection information of any unit (indoor/outdoor units, remote controller or the like) is retrieved (identified).
Deletion of group registration information of indoor units
The registration of the indoor units under group registration is released (deleted).
Deletion of the address not existing
This operation is to be conducted when 6607 error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alteration/modification of the group composi­tion.
Caution:
When MELANS (G-50 for example) is being connected, do not conduct the group/pair registration using the remote controller. The group/pair registration should be conducted by MELANS. (For detail, refer to the instruc­tion exclusively prepared for MELANS.)
1
2
3
4
5
-21-
(3) Group registration of indoor unit
1) Registration method
Group registration of indoor unit ........................................................................
The indoor unit to be controlled by a remote controller is registered on the remote controller.
[Registration procedure]
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2 seconds to change to the registration mode. (See the figure below.) Assign the indoor unit address to INDOOR UNIT ADDRESS NO. by operating the (Room temperature adjustment) ( ). Then press the
TEST RUN
button ( ) to register. In the figure below , the INDOOR UNIT ADDRESS NO. is being set to 001. After completing the registration, press the
FILTER
+
LOUVER
button ( + ) at the same time for 2 seconds to
change to the original ordinary mode (with the remote controller under stopping).
Remote controller under stopping HO under displaying
Ordinary mode
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
˚C
Group setting mode
Confirm the indoor unit address No.
Confirm the connection of the transmission line.
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
˚C
Registration complete
Registration error
Indicates the type of unit (Indoor unit in this case)
88 flickers indicating registra­tion error. (when the indoor unit registered is not existing)
Assign the address ( )
Change to the registration mode ( + )
Press the registration switch ( )
Remote controller
Indoor units
Group
+
1
AB
AB
C
D
1
2
3
1
1
23
1
C
D
AB
23
System example
-22-
2) Method of retrieval/confirmation
2
1
2
Retrieval/confirmation of group registration information on indoor unit...............
The address of the indoor unit being registered on the remote controller is displayed.
[Operation procedure]
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button
( + ) at the same time for 2 seconds to change to the registration mode.
In order to confirm the indoor unit address already registered, press
TIMER
button ( ). (See figure below.) When the
group of plural sets is registered, the addresses will be displayed in order at each pressing of
TIMER
button ( ).
After completing the registration, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
Retrieval/confirmation of registration information ................................................
The registered information on a certain unit (indoor unit, outdoor unit, remote controller or the like) is displayed.
[Operation procedure]
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button
( + ) at the same time for 2 seconds to change to the registration mode.
Operate
MODE
button ( ) for the interlocked setting mode. (See figure below.)
Assign the unit address of which registration information is desired to confirm with the (TIMER SET) switch
( ). Then press the
TIMER
button ( ) to display it on the remote controller. (See figure below.)
Each pressing of
TIMER
button ( ) changes the display of registered content. (See figure below.)
After completing the retrieval/confirmation, continuously press the
FILTER
+
LOUVER
button ( + ) at the same
time for 2 seconds to change to the original ordinary mode (with the remote controller under stopping).
Registered
No registration.
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
˚C
Press the switch for confirmation ( )
Note: Only one address will be displayed
when the registration is one even the switch is how often pressed
Indicates the type of unit (Indoor unit in this case)
SET TEMP . ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
3
AB
E
E
A
1
1
1
AB
G
HE
AB
E
2 3
4
E
3
B
-23-
3) Method of deletion
Deletion of group registration information of indoor unit ......................................
[Operation procedure]
With the remote controller under stopping or at the display of HO, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2 seconds to change to the registration mode. Press the
TIMER
button ( ) to display the indoor unit address registered. (As same as )
In order to delete the registered indoor unit being displayed on the remote controller , press the
CLOCK →→ON OFF
TIMER
( ) button two times continuously. At completion of the deletion, the attribute display section will be shown as “ – – “. (See figure below.) Note: Completing the deletion of all indoor units registered on the remote controller returns to “HO” display. After completing the registration, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
ERROR CODE OA UNIT ADDRESS NO
˚C
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
Set the address
Press the switch for confirmation ( )
Registered
No registration
* Same display will appear when
the unit of “007” is not existing.
twice continuously.
Deletion completed
Deletion completed
In case of group re­gistration with other indoor unit is existing
In case of no group registration with other indoor unit is existing
+
“– –” indicates the deletion completed.
ßC
ßC
(Alternative
display)
ßC
ßC
(Alternative
display)
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
SET TEMP . ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
SET TEMP . ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
21
1
1
1
1
AFB
AB
E
2
3
4
12
4
2
2
E
Press the switch for confirmation (
E
)
-24-
4) Deletion of information on address not existing
Deletion of information on address not existing ...................................................
This operation is to be conducted when “6607” error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alteration/modification of group composition, and the address not existing will be deleted. Note: The connection information (connection between indoor unit and outdoor unit) on the refrigerant system can
not be deleted. An example to delete the system controller of “250” from the indoor unit of “007” is shown below .
[Operation procedure]
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2 seconds to change to the registration mode. Operate
MODE
button ( ) for the interlocked setting mode ( ii ). (See the figure below.)
Assign the unit address existing to OA UNIT ADDRESS No.” with the (TIMER SET) switch ( ), and press
TIMER
button ( ) to call the address to be deleted. (See the figure below.) As the error display on the remote controller is usually transmitted from the indoor unit, OA UNIT ADDRESS No. is used as the address of the indoor unit. Press the
CLOCK →→ON OFF
TIMER
button ( ) twice. (See the figure below.)
After completing the deletion, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2
seconds to return to the original ordinary mode (with the remote controller under stopping).
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
(Alternative
display)
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
(Alternative
display)
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
(Alternative
display)
When both indoor unit and interlocked unit addresses are existing
Deletion of address not existing
Set the address ( )
Press the deletion switch ( ) twice
Deletion completed
Deletion completed
+
Press the switch for confirmation ( )
SET TEMP . ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
5
1
AB
AB
G
E
F
H
2 3
3
3
1
1
2
E
3 F
H
2
4
5
-25-
4
CONTROL
[1] Control of Outdoor Unit
(1) Initial processing
• When turning on power source, initial processing of microcomputer is given top priority.
• During initial processing, control processing corresponding to operation signal is suspended. The control processing is resumed after initial processing is completed. (Initial processing : Data processing in microcomputer and initial setting of each LEV opening, requiring approx. 2 minutes at the maximum.)
(2) Control at staring
• In case unit is started within 2 hours after turning on power source at low outdoor air temperature (+5˚C (41°F) or less), the unit does not start operating for 30 minutes at the maximum .
(3) Bypass, capacity control
• Solenoid valve consists of bypass solenoid valve (SV1, SV2) bypassing between high pressure side and low pres­sure side. The following operation will be provided.
1) Bypass solenoid valves SV1 and SV2 (both "open" when turned on) SV1
ON (Open) OFF (Close)
Turned on for 4 minutes Turned on for 2 minutes
Always turned on
Turned on for 3 minutes
Always turned on
Always turned on in oil recovery operation after low frequency continuous operations
When Pd reaches When Pd is
27.5kg/cm
2
G
24kg/cm2G (341psi) or
(391psi) or more less 30 seconds
Item
When starting compressor After thermost "ON is returned
and after 3 minutes restart When compressor stops in
cooling or heating mode After operation stops During defrosting operations
(See figure below
1)
During oil recovery operations
During 20Hz operations, at fall in low pressure saturation temperature. (ET) (3 minutes or more after starting)
When high pressure rises (Pd)
When high pressure rises (Pd) during 20Hz operations (3 minutes after starting)
When discharge temperature rises (3 minutes after starting)
Ex. SV1
When low pressure saturation temp. (ET) is -15˚C (5°F) or more
When Pd is 23kg/ cm
2
G (327psi) or less
after 30 seconds When high pressure
(Pd) is 20kg/cm
2
G
(284psi) or less When discharge
temp. is 115˚C (239°F) or less
SV2
 
 
OFF (Close)
ON (Open)
When low pressure saturation temp. (ET) is -30˚C (-22°F) or less
When Pd reaches
26kg/cm
2
G (370psi)
or more
Turned on when high pressure (Pd) ex­ceeds pressure limit
When temp. exceeds 130˚C (266°F) and Pd reaches 15kg/cm2G (213psi) or more
Start
Thermo. OFF
Thermo. ON
(4-minute)
(3-minute)
Stop
Bypass solenoid valve (SV1)
Compressor
(2-minute)
(4-minute)
Defrost­ing time (*1)
-26-
Loading...
+ 66 hidden pages