Mitsubishi Electronics PUHY-80TMU-A, 100TMU-A User Manual

Page 1
AIR CONDITIONERS CITY MULTI Series Y
Models PUHY-80TMU-A, 100TMU-A
Service Handbook
Service Handbook PUHY-80TMU-A, 100TMU-A
Page 2
- Inadequate connection and fastening may generate heat and cause a fire.
• Prepare for typhoons and other strong winds and earth­quakes and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in
injury.
• Always use an air cleaner, humidifier, electric heater, and other accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Im-
proper installation by the user may result in water leakage, electric shock, or fire.
• Never repair the unit. If the air conditioner must be re­paired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric
shock, or fire may result.
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poison-
ous gases will be released.
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric
shock, or fire may result.
• Have all electric work done by a licensed electrician ac­cording to “Electric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock and fire may result.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed properly, dust or water
may enter the outdoor unit and fire or electric shock may re­sult.
• When installing and moving the air conditioner to another
refrigerant (R22) specified on the unit.
- If a different refrigerant or air is mixed with the original refriger-
ant, the refrigerant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to pre-
vent the safety limit from being exceeded. Should the refriger­ant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage,
electric shock, or fire may result.
• After completing installation work, make sure that refriger­ant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater,
stove, oven, or other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection de-
vice is shorted and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
Before installation and electric work
ss
ss
s Before installing the unit, make sure you read all
the “Safety precautions”.
ss
ss
s The “Safety precautions” provide very important
points regarding safety. Make sure you follow them.
ss
ss
s This equipment may have an adverse effect on
equipment on the same electrical supply system.
ss
ss
s Please report to or take consent by the supply au-
thority before connection to the system.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided. : Indicates that important instructions must be followed. : Indicates a part which must be grounded. : Indicates that caution should be taken with rotating parts.
(This symbol is displayed on the main unit label.) <Color: Yellow>
: Indicates that the main switch must be turned off before
servicing. (This symbol is displayed on the main unit label.) <Color: Blue>
: Beware of electric shock (This symbol is displayed on the
main unit label.) <Color: Yellow>
: Beware of hot surface (This symbol is displayed on the main
unit label.) <Color: Yellow>
ELV
: Please pay attention to electric shock because this
is not Safety Extra Low-Voltage (SELV) circuit. And at servicing, please shut down the power supply
for both Indoor Unit and Outdoor Unit .
Warning:
Carefully read the labels affixed to the main unit.
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage,
electric shock, or fire.
• Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting
in injuries.
• Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not ap­plied to the terminals.
Safety precautions
site, do not charge it with a refrigerant different from the
Page 3
Contents
1 COMPONENT OF EQUIPMENT 1
[1] Appearance of Components 1 [2] Refirigerant Circuit Diagram and Thermal Sensor
Standard operation data
iger 6
[3] PUHY-80, 100TMU-A ELECTRICAL WIRING
DIAGRAM 7
9
[4] [5] Function of dip SW and rotary SW 11
2 TEST RUN 15
[1] Before Test Run 15 [2] Test Run Method 19
3 GROUPING REGISTRATION OF INDOOR UNITS WITH
M-NET REMOTE CONTROLLER 20
4 CONTROL 26
[1] Control of Outdoor Unit 26 [2] Operation Flow Chart 31 [3] List of Major Component Functions 36 [4] Resistance of Temperature Sensor
Refrigerant Amount and Operating Characteristics
38
5 REFRIGERANT AMOUNT ADJUSTMENT 39
[1] 39 [2] Adjustment and Judgement of Refrigerant Amount 39
6 TROUBLESHOOTING 44
[1] Principal Parts 44 [2] Self-diagnosis and Countermeasures Depending on the
Check Code Displayed 62
[3] LED Monitor Display......................................................
...............................................................................
............................................................
...............................................................................
...........................................................
....................................................
...........................................
..................................................
...............................................
............................................
.......................................................................
...........
................................
.................................................
..................................................
................................................................
.............................................................
..............................
...............................
...............................
.......
.......
83
Page 4
Propeller fan
Fan motor
-1-
Page 5
Rear Controller Box
INV board
MAIN board
Choke coil(L2)
Interrigent Power Module(IPM)
Magnetic contactor(52C)
Capacitor (C1)(Smoothing capacitor)
Gate Amplifier board(G/A board)
Diode stack(DS) Power board
Terminal block(TB7)Transmission
Terminal block (TB3) Transmission
Terminal block (TB1) Power source
-2-
Page 6
MAIN board
CNS1 M-NET Transmission (DC30V)
CNS2 M-NET Transmission (Centralized control) (DC30V)
CN40 M-NET Transmission Power supply
CNVCC3 Power source for contorl
1-2 DC30 V 1-3 DC30 V 4-6 DC12 V 5-6 DC5 V
CN51 Indication distance 3-4 Compressor ON/
Off
3-4 trouble
LD1 Service LED
CNRS53 Serial transmission to INV board
CN3D
CN3S
CNFAN1 control for MF1
CNAC3
CN20 power source
SW1,2,3,4 Dip Switch
-3-
Page 7
INV board
CNDC2 1-3 DC310 V
CN15V2 Power supply IPM control
1-2 DC15 V 5-6 DC15 V 9-0 DC15 V C-D DC15 V
CNL2 Choke coil
CNRS2
Serial transmission
to MAIN board
CNAC2 Power source
1 L2 5 N
CNFAN
Control for
MF1
CN52C
Control for
52C
CNVCC2 power supply
CNCT
CNVCC4
CNTH
CNDR2 IPM control signal
SW1
-4-
Page 8
G/A board
Power board
DC310V
CNDC1 1 - 3 DC310V
CN15V1 Power Supply IPM control
1 - 2 DC15V 5 - 6 DC15V 9 - 0 DC15V C - D DC15V
CNDR1 IPM control signal
-5-
Page 9
[2] Refirigerant Circuit Diagram and Thermal Sensor
1 PUHY-80TMU-A, 100TMU-A
TH1
TH6
TH7
TH8
TH5
TH2
O/S
63HS
CJ1
Comp
HEXFHEXB
SCC
LEV1
ST7
BV2
ST2
Indoor
Unit
BV1
ST1
CJ2
CV1
ST6
SV1
CP1
SV2
SLEV
SA
MA
CP2
63H
High pressure safety valve
Accumulator
-6-
Page 10
[3] PUHY-80, 100TMU-A ELECTRICAL WIRING DIAGRAM
CNS2
(3P)
FN3
FN2
1 2
C
CNS2
(3P)
FN3
FN2
C 1
R 1
52C
DCCT
1 2 3
TH6 TH5TH8TH7TH2 TH1 63HS
SW3-10 are OFF for Model 80.
and ON for Model 100.
Trouble
Compressor ON/OFF
Snow sensor
Compressor ON/OFF
Night mode
Ground
123451234
5
54321
32132
1
1 2 3 1 2 3 4 5 6 7 8
1 2
1 2 3
1 2
321
L1L2L3
+
DS(Diode stack)
Power source
3~208~230V
SLEV
CN20
(7P)
CN03
(3P)
CN02
(8P)
CN01
(2P)
CNH
(3P)
CNLV1
(5P)
Blue
CNLV2
(5P)
Red
CN51
(5P)
CN3D
(3P)
CN3S
(3P)
Red
CNS1
(2P)
CNS2
(3P)
T B 3
T B 7
A B
1 2 3 4
1 2 3 4
CN40
(4P)
CN41
(4P)
54321
Connect to
indoor and
remote
controller
GR
Red
Black
-
Red
12V
DSA
3 2 1
1 2
THHS
52
1234567123456
12345
CNRS3
(7P)
CNVCC3
(6P)
CNAC3
(5P)
GL3L1
Control circuit board
(MAIN-BOARD)
LD1
1
10
1
10
1
10
OFF ONOFF ONOFF ON
Unit address setting switch
X 0 1
A B Shield
G
L3
F2
6.3A
F1
6.3A
ZNR1~4
Red
CNFAN1
(5P)
Red
54321
CN38
(3P)
Green
CN34
(6P)
CN33
(6P)
CN32
(3P)
321
321
65432
1
65432
1
FN4
FN6
FN2
FN3
FN1
Noise filter board
(POWER-BOARD)
Red White Black Green
Red White Black
F01
2A
R2
1 2 1 2
Green
CNTH
(2P)
CNL2
(2P)
Red
CN30V
(2P)
Red
CNFAN
(3P)
R2
U W
1 2 1 2
MF
L2
R2
F01
2A
12345
12345
6
CNVCC4
(2P)
1
2
CNAC2
(5P)
1234567
CNVCC2
(6P)
123
Red
Black
+
1 2 3 4
CNRS2
(7P)
CNCT
(4P)
(3P)
Yellow
CNDC1
(3P)
1 2 3 4
CN52C
CN15V1
(14P)
CNDR1
(9P)
CNDC2
(3P)
Yellow
CNDR2
(9P)
CN15V2
(14P)
Power circuit board
(INV-BOARD)
Black
White
Red
Gate amp board
(G/A-BOARD)
1 2 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3
1 2 3
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3 4 5 6 7 8 9
U V W
F01
3.15A
21
S4
SV
CNVCC5
(2P)
1
2
1
2
GL3L1
Detection
Circuit
ONOFF
10
1
2
CNE
(2P)
1
L2 L1
Ground
X01
N
P
DCL
V
LEV1
SW1SW2SW3SW4
SWU1SWU2
X04
X05
X02
63H
MF
CH1
SV1
60Hz
TB1
MC
2
IPM
1
1357
1 2 3
-7-
Page 11
S W U 1 ~ 2
T B 1
Switch unit address set
Terminal block power source
T B 3
T B 7
Terminal block transmisson
GR
Ground terminal
Terminal block transmisson
centralized control
L D 1
S W 1
S W 2 ~4
Switch function selection
Switch display selection self-diagnosis
Luminous diode
T H 8
bypass outlet temp.
detect at Sub-cool coil
T H H S
Rediator panel temp.detect
6 3 H S
High pressure sensor
S L E V
L E V 1
Electronic expansion valve
(Oil return)
Electronic expansion valve
(Sub-cool coil bypass)
L 2
Choke coil(Transmission)
T H 7
liquid outlet temp.
detect at Sub-cool coil
T H 5
T H 2
T H 1
pipe temp.detect
T H 6
OA temp.detect
saturation
evapo.temp.detect
Thermistor
Thermistor
6 3 H
High pressure switch
S V 1 , S V 2
Solenoid valve
(Discharge-suction bypass)
C H 1
Crankcase heater (Compressor)
D S A
Surge absorber
Motor Compressor
Motor Fan Heat exchanger
Motor Fan Radiator panel
M F 1
M F
M C
5 2 C
Magnetic contactor
(Inverter main circuit)
Z N R 1 ~ 4
Varistor
C 1
Capacitor Smoothing
Resistor rush current protect
D C C T
Current Sensor
R 1
R 2
Resistor power regulation
D C L
DC reactor
(Power factor improvement)
I P M
Intelligent Power Module
D S
Diode stack
Symbol
Name
Symbol
Name
Symbol
Name
Symbol
Name
discharge pipe temp.detect
4-way valve
2 1 S 4
OFF : 0
ON : 1
(at factory shipment)
FLAG7
FLAG1
FLAG6
Display
Relay output
display
(Lighting)
During
compressor
run
Crankcase
heater
0000~9999
Display the address and error codes by turns
21S4
SV1 SV2
Check display
(Blinking)
Display at LED lighting (blinking) Remarks SW1 operation
FLAG3 FLAG4FLAG2 FLAG5
FLAG8
FLAG8 always lights at
microcomputer power ON
Always
lighting
<Operation of self-diagnosis switch (SW1) and LED display>
<LED display>
LD1
FLAG8
FLAG7
FLAG6
FLAG5
FLAG4
FLAG3
FLAG2
FLAG1
1 2 3 4 5 6 7 8 9 10
-8-
Page 12
[4] Standard operation data
1 Cooling operation
75 81
111 157
Discharge (TH1) Heat exchanger outlet (TH5)
Inlet
Accumulator
Outlet
Suction (Comp) low pressure saturation
temperature (TH2) Shell bottom (Comp)
SCC outlet (TH7) Bypass outlet (TH8) LEV inlet Heat exchanger outlet
Outdoor units
Items
Condition
Pressure
LEV opening
Sectional temperature
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
Ambient temp.
Indoor unit
Piping
Indoor unit fan notch Refrigerant volume
Outdoor unit
Compressor volts/Frequency
Indoor unit SC (LEV1) Oil return (SLEV)
DB/WB
Set
m
(Ft)
PUHY-80TMU-A PUHY-100TMU-A
kg(oz)
A
V
V/Hz
Pulse
Outdoor unit
85(185) 95(203) 40(104) 42(108)
7(45) 5(41)
9(48) 7(45) 7(45) 10(50) 6(43) 4(39)
60(140) 60(140)
27(81) 27(81)
8(46) 6(43)
26(79) 26(79)
10(50) 10(50)
2.00/0.50 (290/72)
1.99/0.46 (288/67)
°C
(°F)
MPa(psi)
High pressure/Low pressure (after O/S) (before MA)
Indoor unit
24 24 20 10 48 16 24 10
5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4)
Hi Hi Hi Hi Hi Hi Hi Hi
440 440 380 300 450 320 440 300
26.7°C(80°F)/19.4°C(67°F) 35°C(95°F)
4 4
4 4
5(16.4) 5(16.4)
25(82) 25(82)
10.2(360) 12.5(441)
27.4
208
134/76
230
134/76
208
171/98
230
171/98
24.8 35.2 31.8
-9-
Page 13
00
87 111
Discharge (TH1) Heat exchanger inlet (TH5)
Inlet
Accumulator
Outlet
Suction (Comp) low pressure saturation
temperature (TH2) Shell bottom (Comp)
Heat exchanger inlet LEV inlet
2 Heating operation
Outdoor units
Items
Condition
Pressure
LEV opening
Sectional temperature
Indoor Outdoor Quantity Quantity in operation Model Main pipe Branch pipe Total piping length
Ambient temp.
Indoor unit
Piping
Indoor unit fan notch Refrigerant volume
Outdoor unit
Compressor volts/Frequency
Indoor unit SC (LEV1) Oil return (SLEV)
DB/WB
Set
m
PUHY-200TM-A PUHY-250TM-A
27.5
208
149/85
24.9
230
149/85
35.6
208
174/100
32.2
230
174/100
kg
A
V
V/Hz
Pulse
80
85(185)
6(46) 8(46)
1(30) 2(28)1(30) 2(28)1(30) 2(28)2(28) 2(28)
35(95) 44(111)
71(160) 71(160)
33(91) 33(91)
1.72/0.36 (249/52)
1.72/0.36 (249/52)
MPa(psi)
High pressure/Low pressure (after O/S) (before MA)
°C
(°F)
Outdoor unit
Indoor unit
24 24 20 10 48 16 24 10
5(16.4) 5(16.4)5(16.4)5(16.4)5(16.4)5(16.4)5(16.4)5(16.4)
Hi Hi Hi Hi Hi Hi Hi Hi
510 510 450 300 350 380 510 300
21.1°C(70°F)
8.3°C(47°F)/6.1°C(43°F) 4 4
4 4
5(16.4) 5(16.4)
25(82) 25(82)
10.2(360) 12.5(441)
-10-
Page 14
[5] Function of dip SW and rotary SW
(1) Outdoor unit
Switch Function
Function According to Switch Operation Switch Set Timing
When Off When On When Off When On Unit Address Setting For self diagnosis/ operation monitoring
– Centralized Control Switch Deletion of connection information.
Deletion of error history.
Adjustment of Refrigerant Volume
– Disregard ambient air sensor errors, fluid overflow errors. Forced defrosting
Defrost prohibited timer
– SW3-2 Function Valid/ Invalid Indoor Unit Test Operation Defrosting start temperature of TH5. Defrosting end temperature of TH5. Opening angle of IC except when heater thermostat is ON during defrosting.
Target Pd (High pressure)
– –
– –
– –
– –
– –
– –
– –
– –
– –
Models
LED Display "°F" "psig" Display "°C" "kgf/cmG "Display When switching on the power
Fan characteristics ( )
Standard High external
static pressure
When switching on the power
– Centralized control not connected. Storing of refrigeration system connection information.
Ordinary control
– Errors valid.
Ordinary control
50 min.
– SW3-2 Function Invalid
Stop all indoor units.
-2°C
(28.4°F) (32°F)
8HP: 12°C(53.6°F)
10HP: 8°C(46.4°F)
(no operation)
18kg/cm
2
G
(256psi)
20kg/cm2G
(284psi) – –
Model 80
Set on 00 or 51~100 with the dial switch. (
2)
LED Monitering Display
– Centralized control connected. Deletion of refrigeration system connection information. Deletion
Refrigerant volume adjustment operation.
– Disregard errors.
Start forced defrosting.
90 min.
– SW3-2 Function Valid
All indoor units test operation ON.
0°C
15
(59°F)
°C
2000
– Model 100
During normal operation when power is on.
Before power is turned on. During normal operation when power is on. Should be set on OFF. Before power is turned on.
Before power is turned on.
During normal operation when power is on.
– During normal operation when power is on.
During normal operation when power is on. (Except during defrosting)
– During normal operation when power is on. When SW3-1 is ON after power is turned on. During normal operation when power is on. During normal operation when power is on. (Except during defrosting)
– When switching on the power. During normal operation when power is on.
– When switching on the power.
Invalid 2 hours after compressor starts.
During normal operation when power is on.
10 minutes or more after compressor starts.
Note:
1. SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
1
2. If the address is set from 01 to 50, it automatically becomes 100.
SWU
SW1
SW2
SW3
SW4
1~2 1~8
9~10
1
2
3
4
5 6
7
8
9
10
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
-11-
Page 15
2. SW4-9 setting
Fan characteristics curve:DIPSW4-7ON,230V/60Hz
Fan characteristics curve:DIPSW4-7ON,208V/60Hz
0
5
10
15
20
25
30
35
40
45
50
150 160 180 190 200 210 220 230 240
Standard Airflow rate
200(m
3
/min)
Fan characteristics curve:DIPSW4-7OFF[FactorySetting],208V230V/60Hz
Continuous operation range
Airflow rate (m3/min)
External static pressure (Pa)
170
-12-
Page 16
(2) Indoor unit
DIP SW1, 3
Model 32 40 48 Capacity (model name) code
16 20 25
SW2 setting
Model 08 10 12 16 20 24 Capacity (model name) code
45 681013
SW2 setting
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the
table below.)
2: The DipSW setting is only effective during unit stopping (remote controller OFF) for SW1, 2, 3 and 4 commonly
and the power source is not required to reset.)
3: When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat of OFF.
Setting of DIP SW2
Model
Switch
SW1
SW3
3 6 7 3 4 6 8
PLFY-NAMU-A
ON ON
OFF
ON
ON OFF OFF
Indoor unit inlet
None
100h
Ineffective Fan output display At stationary heating
Very low speed
SW1-7 setting
Ineffective
Heat pump
None
None None
1st setting
Down blow B, C
Effective
– –
Built in remote controller
Provided
2500h
Effective
Thermo. ON signal display
Always at heat.
Low speed
Set airflow
Effective
Cool.only
Provided
Provided Provided
2nd setting
Horizontal
Ineffective
– –
Room temp. sensor position Clogged filter detect. Filter duration OA intake Remote display select. Humidifier control Heating thermo. OFF airflow Heating thermo. OFF airflow Power failure automatic
return
Model selection
Louver
Vane Vane swing function Vane horizontal angle Vane angle set for cooling
Heating 4deg (7.2 deg) up Note : °C scale (°F scale)
– –
Always ineffective for PKFY-NAMU
Not provided for PKFY-NAMU Provided for PLFY-NGMU (ON) setting
Always down blow B,C for PKFY-NAMU
SW1
SW3
1 2 3 4 5 6 7 8
9
10
1
2
3 4 5 6 7
8 9
10
Switch SW name
Operation by SW
Switch set timing
OFF ON OFF ON
Remarks
At unit stopping
(at remote
controller OFF)
Cooling capacity saving
for PKFY-NAMU, effective/ineffective
PDFY-NMU-A
ON
ON OFF OFF OFF OFF OFF
PKFY
OFF OFF OFF
ON
OFF OFF
NAMU-A NGMU-A
OFF ON
-13-
Page 17
Setting of DIP SW4 Setting of DIP SW5
1234
ON OFF ON OFF
OFF OFF OFF ON
ON OFF OFF ON
OFF OFF ON ON
––––
OFF OFF ON
PDFY-10 ~ 32 PLFY-12 ~ 24 PLFY-32 ~ 48 PKFY-P-8 PKFY-P-12 PDFY-40, 48
Model Circuit board used
SW4
Phase control
Relay selection
-14-
Page 18
TEST RUN
[1] Before Test Run
(1) Check points before test run
1 Neither refrigerant leak nor loose power source/ transmission lines should be found, if found correct immediately.
2 Confirm that the resistance between the power source terminal block and the ground exceeds 2M by measur-
ing it with a DC500V megger. Do not run if it is lower than 2MΩ. Note : Never apply the megger to the MAIN board. If applied, the MAIN board will be broken.
3 Confirm that the Ball valve at both gas and liquid sides are fully opened.
Note : Close the cap.
4 Be sure that the crankcase heater has been powered by turning the main power source on at least 12 hours
before starting the test run. The shorter powering time causes compressor trouble.
(2) Caution at inverter check
Because the inverter power portion in outdoor unit electrical part box have a lot of high voltage portion, be sure to follow the instructions shown below.
During energizing power source, never touch inverter power portion because high voltage (approx. 320V) is applied to inverter power portion.
When checking,
Shut off main power source, and check it with tester, etc.
Allow 10 minutes after shutting off main power source.
Open the MAIN board mounting panel, and check whether voltage of both ends of electrolytic capacitor is 20V or less.
1
2
1
2
3
2
-15-
Page 19
(3) Check points for test run when mounting options
(4) Attention for mounting drain water pump mechanism
Check point
Local remote controller displays code No. 2503, and the mechanism stops.
No overflow from drain pan. Drain water comes out by operation of
drain pump. Sound of pump operations is heard, and
drain water comes out. No water leak from connecting portions
of each water piping. Water is supplied to water supply tank,
and float switch is operating.
Built-in optional parts Mounting of drain
water pump mechanism
Mounting of perme­able film humidifier
Content of test run
Release connector of pump circuit, check error detection by pouring water into drain pan water inlet.
After that, connect connector of circuit.
Check pump operations and drain­age status in cooling (test run) mode.
Check humidifier operations and water supply status in heating (test run) mode.
1
2
3
4
5
Result
1
2
3
Work
Disassembling and assembling of drain water pump mechanism
Mounting of float switch
Electric wiring
Float switch moves smoothly . Float switch is mounted on
mounting board straight without deformation.
Float switch does not contact the
copper pipe. Wiring procedure is exactly followed. Connector portion is tightly hooked.
Content of test run
Lead wire from control box not damaged.
Rubber cap properly inserted in to drain water outlet of drain pan?
Insulation pipe of gas and liquid pipes dealt with as shown on next page?
Drain pan and piping cover mounted without gap?
Drain pan hooked on cut projection of the mechanism?
Float switch installed without contacting the drain pan?
No mistakes in wiring? Connectors connected securely and
tightly? No tension on lead wire when sliding
control box?
1 2
3
1
2
3
Check point Result
Insulation pipe
No gap
-16-
Page 20
Trouble
Not operate.
Not cool (at cooling). Not heat (at heating).
Not cool, not heat, error stop. Condensation drip in piping. Not cool, not heat, error stop.
Water leak, condensation drip in drain piping.
Error stop, not operate.
Electric shock. Error stop, not operate.
Classification
Installation and piping
Power source wiring
Portion
1
2
3
Check item
Instruction for selecting combination of outdoor unit, and indoor unit followed? (Maximum number of indoor units which can be connected, connecting model name, and total capacity.)
Follow limitation of refrigerant piping length? For example, 70m (229ft) or less (total length : 220m (721ft)) at the farthest.
Connecting piping size of branch piping correct? Refrigerant piping diameter correct? Refrigerant leak generated at connection? Insulation work for piping properly done? Specified amount of refrigerant replenished?
Pitch and insulation work for drain piping properly done? Specified switch capacity and wiring diameter of main
power source used?
Proper grounding work done on outdoor unit? The phases of the L line (L1, L2, L3) correct?
1
2
3
4
5
6
7
8
(5) Check points for system structure
Check points from installation work to test run.
-17-
Page 21
Classification Transmission
line
Portion
1
2
3
4
5
6
7
8
Check item
Limitation of transmission line length followed? For example, 200m (656ft) or less (total length : 500m (1640ft)) at the farthest.
1.25mm2 (AWG16) or more transmission line used? (Remote controller 10m (32ft) or less 1.25mm2 (AWG16))
2-core cable used for transmission line?
Transmission line apart from power source line by 5cm (2in) or more? One refrigerant system per transmission line? The short circuit connector is changed form CN41 to
CN40 on the MAIN board when the system is centralized control? (Just one outdoor unit. Not all outdoor units.)
No connection trouble in transmission line? Connection of wrong remote controller line terminals?
MA Remote controller : TB15
M-NET Remote controller : TB5
Trouble
Erroneous operation, error stop.
Erroneous operation, error stop.
Error stop in case multiple-core cable is used.
Erroneous operation, error stop. Not operate. Not operate.
Error stop or not operate. Never finish the initial mode.
System set
Before starting
Error stop or not operate.
Can not be properly set with power source turned on.
Not operate. Set temperature not obtained at
heating operations (Thermostat stop is difficult)
Error stop.
Error stop, compressor trouble.
1
2
1
2 3
4
Address setting properly done? (M-NET Remote controller, indoor unit and outdoor unit.)
Setting of address No. done when shutting off power source?
Address numbers not duplicated? Turned on SW3-8 on indoor unit circuit board when
mounting room thermistor sensor?
Refrigerant piping ball valve (Liquid pressure pipe, gas pressure pipe) opened?
Turn on power source 12 hours before starting operations?
2 31
SET TEMP. ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE
DRY COOL
DAILY
TIMER
CHECK
AUTO
ONCLOCK
SET TEMP.
REMAINDER
NOT AVAILABLE
SENSOR
INSIDE FILTER
TEST RUN
VENTILATION
EROR CODE
AUTO
OFF
CENTRALLY CONTROLLED
AUTO FAN
HEAT
STAND BY DEFROST
FAN SPEED
TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
-18-
CENTRALLY CONTROLLED
DRY COOL
TIMER
DAILY
AUTO FAN
STAND BY DEFROST
PAR-F27MEA-US
AUTO
SET TEMP.
REMAINDER
CHECK
HEAT
EROR CODE
SET TEMP. ON/OFF
CLOCK ON OFF
MODE
TIMER FAN SPEED
TIMER SET
AUTO
ONCLOCK
OFF
FAN SPEED
VENTILATION
NOT AVAILABLE
AIR DIRECTION
LOUVER VENTILATION
SENSOR
TEST RUN
INSIDE FILTER
CHECK TEST
FILTER
Page 22
[2] Test Run Method
Operation procedure
Turn on universal power supply at least 12 hours before starting Displaying HO on display panel for about two minutes
Press
TEST
1
2
3
4
5
6
7
8
9
button twice Displaying TEST RUN’’ on display panel
Press
MODE
button Make sure that air is blowing out
Press
MODE
button to change from cooling to heating operation, and vice versa Make sure that warm or cold
air is blowing out
Press
FAN SPEED
adjust button Make sure that air blow is changed
Press
AIR DIRECTION
or
LOUVER
ON/OFF
button to change direction of air blowing make sure that horizontal or
downward blow is adjustable.
Make sure that indoor unit fans operate normally Make sure that interlocking devices such as ventilator operate normally if any
Press button to cancel test run Stop operation
Note 1: If check code is displayed on remote controller or remote controller does not operate normally.
2: Test run automatically stops operating after two hours by activation of timer set to two hours. 3: During test run, test run remaining time is displayed on time display section. 4: During test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temperature
display section.
5: When pressing
FAN SPEED
adjust button, depending on the model, NOT A V AILABLE may be displayed on
remote controller. However, it is not a malfunction.
6: When pressing
AIR DIRECTION
or
LOUVER
button, depending on the model, NOT A V AILABLE may be
displayed on remote controller. However, it is not a malfunction.
-19-
Page 23
3
GROUPING REGISTRATION OF INDOOR UNITS WITH M-NET REMOTE CONTROLLER
(1) Switch function
The switch operation to register with the remote controller is shown below:
Registration/ ordinary mode selector switch
Registration/ordinary mode selection switch
Switch to assign indoor unit address
Registration switch
Confirmation switch
Delete switch
Registered mode selector switch
Switch to assign interlocked unit address
+
This switch selects the ordinary mode or registered mode (ordinary mode represents that to operate indoor units).
To select the registered mode, press the
FILTER
+
LOUVER
button continuously for over 2 seconds under stopping state. [Note] The registered mode can not be obtained for a while after powering. Pressing the
FILTER
+
LOUVER
button displays “CENTRALLY
CONTROLLED. This button assigns the unit address for INDOOR UNIT ADDRESS
NO.
This button is used for group/interlocked registration.
This button is used to retrieve/identify the content of group and interlocked (connection information) registered.
This button is used to retrieve/identify the content of group and interlocked (connection information) registered.
This button selects the case to register indoor units as group (group setting mode) or that as interlocked (interlocked setting mode).
The unit address is shown at one spot for the group setting mode
while at two spots for the interlocked setting mode.
This button assigns the unit address of OA UNIT ADDRESS NO.
Symbol
of switch
Registered mode selector switch
Confirmation switch
Switch to assign indoor unit address
Switch to assign inter-
locked unit address
Registration switch
+
FILTER
TEST RUN
Name Name of actual switch Description
of TEMP
CLOCK ONOFF
of TIMER SET
Registration/ ordinary mode selector switch
SET TEMP. ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE
DRY COOL
DAILY
TIMER
CHECK
AUTO
ONCLOCK
SET TEMP .
REMAINDER
NOT AV AILABLE
SENSOR
INSIDE FILTER
TEST RUN
VENTILATION
EROR CODE
AUTO
OFF
CENTRALLY CONTROLLED
AUTO FAN
HEAT
STAND BY DEFROST
FAN SPEED
TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
Delete switch
LOUVER
TIMER
MODE
A
A
B
B
F
F
G
G
E
E
D
D
C
C
H
H
ii
i
-20-
Page 24
(2) Attribute display of unit
At the group registration and the confirmation/deletion of registration/connection information, the type (attribute) of the unit is displayed with two English characters.
Display Type (Attribute) of unit/controller
Indoor unit connectable to remote controller Outdoor unit
Local remote controller System controller (MJ)
[Description of registration/deletion/retrieval]
The items of operation to be performed by the remote controller are given below. Please see the relating paragraph for detail.
Group registration of indoor unit
The group of the indoor units and operating remote controller is registered.
It is usually used for the group operation of indoor units with different refrigerant system.
Retrieval/identification of group registration information of indoor units
The address of the registered indoor units in group is retrieved (identified).
Retrieval/identification of registration information
The connection information of any unit (indoor/outdoor units, remote controller or the like) is retrieved (identified).
Deletion of group registration information of indoor units
The registration of the indoor units under group registration is released (deleted).
Deletion of the address not existing
This operation is to be conducted when 6607 error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alteration/modification of the group composi­tion.
Caution:
When MELANS (G-50 for example) is being connected, do not conduct the group/pair registration using the remote controller. The group/pair registration should be conducted by MELANS. (For detail, refer to the instruc­tion exclusively prepared for MELANS.)
1
2
3
4
5
-21-
Page 25
(3) Group registration of indoor unit
1) Registration method
Group registration of indoor unit ........................................................................
The indoor unit to be controlled by a remote controller is registered on the remote controller.
[Registration procedure]
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2 seconds to change to the registration mode. (See the figure below.) Assign the indoor unit address to INDOOR UNIT ADDRESS NO. by operating the (Room temperature adjustment) ( ). Then press the
TEST RUN
button ( ) to register. In the figure below , the INDOOR UNIT ADDRESS NO. is being set to 001. After completing the registration, press the
FILTER
+
LOUVER
button ( + ) at the same time for 2 seconds to
change to the original ordinary mode (with the remote controller under stopping).
Remote controller under stopping HO under displaying
Ordinary mode
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
˚C
Group setting mode
Confirm the indoor unit address No.
Confirm the connection of the transmission line.
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
˚C
Registration complete
Registration error
Indicates the type of unit (Indoor unit in this case)
88 flickers indicating registra­tion error. (when the indoor unit registered is not existing)
Assign the address ( )
Change to the registration mode ( + )
Press the registration switch ( )
Remote controller
Indoor units
Group
+
1
AB
AB
C
D
1
2
3
1
1
23
1
C
D
AB
23
System example
-22-
Page 26
2) Method of retrieval/confirmation
2
1
2
Retrieval/confirmation of group registration information on indoor unit...............
The address of the indoor unit being registered on the remote controller is displayed.
[Operation procedure]
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button
( + ) at the same time for 2 seconds to change to the registration mode.
In order to confirm the indoor unit address already registered, press
TIMER
button ( ). (See figure below.) When the
group of plural sets is registered, the addresses will be displayed in order at each pressing of
TIMER
button ( ).
After completing the registration, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
Retrieval/confirmation of registration information ................................................
The registered information on a certain unit (indoor unit, outdoor unit, remote controller or the like) is displayed.
[Operation procedure]
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button
( + ) at the same time for 2 seconds to change to the registration mode.
Operate
MODE
button ( ) for the interlocked setting mode. (See figure below.)
Assign the unit address of which registration information is desired to confirm with the (TIMER SET) switch
( ). Then press the
TIMER
button ( ) to display it on the remote controller. (See figure below.)
Each pressing of
TIMER
button ( ) changes the display of registered content. (See figure below.)
After completing the retrieval/confirmation, continuously press the
FILTER
+
LOUVER
button ( + ) at the same
time for 2 seconds to change to the original ordinary mode (with the remote controller under stopping).
Registered
No registration.
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
˚C
Press the switch for confirmation ( )
Note: Only one address will be displayed
when the registration is one even the switch is how often pressed
Indicates the type of unit (Indoor unit in this case)
SET TEMP . ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
3
AB
E
E
A
1
1
1
AB
G
HE
AB
E
2 3
4
E
3
B
-23-
Page 27
3) Method of deletion
Deletion of group registration information of indoor unit ......................................
[Operation procedure]
With the remote controller under stopping or at the display of HO, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2 seconds to change to the registration mode. Press the
TIMER
button ( ) to display the indoor unit address registered. (As same as )
In order to delete the registered indoor unit being displayed on the remote controller , press the
CLOCK →→ON OFF
TIMER
( ) button two times continuously. At completion of the deletion, the attribute display section will be shown as “ – – “. (See figure below.) Note: Completing the deletion of all indoor units registered on the remote controller returns to “HO” display. After completing the registration, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
ERROR CODE OA UNIT ADDRESS NO
˚C
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
Set the address
Press the switch for confirmation ( )
Registered
No registration
* Same display will appear when
the unit of “007” is not existing.
twice continuously.
Deletion completed
Deletion completed
In case of group re­gistration with other indoor unit is existing
In case of no group registration with other indoor unit is existing
+
“– –” indicates the deletion completed.
ßC
ßC
(Alternative
display)
ßC
ßC
(Alternative
display)
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
SET TEMP . ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
SET TEMP . ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
21
1
1
1
1
AFB
AB
E
2
3
4
12
4
2
2
E
Press the switch for confirmation (
E
)
-24-
Page 28
4) Deletion of information on address not existing
Deletion of information on address not existing ...................................................
This operation is to be conducted when “6607” error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alteration/modification of group composition, and the address not existing will be deleted. Note: The connection information (connection between indoor unit and outdoor unit) on the refrigerant system can
not be deleted. An example to delete the system controller of “250” from the indoor unit of “007” is shown below .
[Operation procedure]
With the remote controller under stopping or at the display of “HO”, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2 seconds to change to the registration mode. Operate
MODE
button ( ) for the interlocked setting mode ( ii ). (See the figure below.)
Assign the unit address existing to OA UNIT ADDRESS No.” with the (TIMER SET) switch ( ), and press
TIMER
button ( ) to call the address to be deleted. (See the figure below.) As the error display on the remote controller is usually transmitted from the indoor unit, OA UNIT ADDRESS No. is used as the address of the indoor unit. Press the
CLOCK →→ON OFF
TIMER
button ( ) twice. (See the figure below.)
After completing the deletion, continuously press the
FILTER
+
LOUVER
button ( + ) at the same time for 2
seconds to return to the original ordinary mode (with the remote controller under stopping).
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
(Alternative
display)
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
(Alternative
display)
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
ßC
(Alternative
display)
When both indoor unit and interlocked unit addresses are existing
Deletion of address not existing
Set the address ( )
Press the deletion switch ( ) twice
Deletion completed
Deletion completed
+
Press the switch for confirmation ( )
SET TEMP . ON/OFF
PAR-F27MEA-US
FILTER
CHECK TEST
CLOCK ON OFF
MODE TIMER FAN SPEED
LOUVER VENTILATION
AIR DIRECTION
TIMER SET
5
1
AB
AB
G
E
F
H
2 3
3
3
1
1
2
E
3 F
H
2
4
5
-25-
Page 29
4
CONTROL
[1] Control of Outdoor Unit
(1) Initial processing
• When turning on power source, initial processing of microcomputer is given top priority.
• During initial processing, control processing corresponding to operation signal is suspended. The control processing is resumed after initial processing is completed. (Initial processing : Data processing in microcomputer and initial setting of each LEV opening, requiring approx. 2 minutes at the maximum.)
(2) Control at staring
• In case unit is started within 2 hours after turning on power source at low outdoor air temperature (+5˚C (41°F) or less), the unit does not start operating for 30 minutes at the maximum .
(3) Bypass, capacity control
• Solenoid valve consists of bypass solenoid valve (SV1, SV2) bypassing between high pressure side and low pres­sure side. The following operation will be provided.
1) Bypass solenoid valves SV1 and SV2 (both "open" when turned on) SV1
ON (Open) OFF (Close)
Turned on for 4 minutes Turned on for 2 minutes
Always turned on
Turned on for 3 minutes
Always turned on
Always turned on in oil recovery operation after low frequency continuous operations
When Pd reaches When Pd is
27.5kg/cm
2
G
24kg/cm2G (341psi) or
(391psi) or more less 30 seconds
Item
When starting compressor After thermost "ON is returned
and after 3 minutes restart When compressor stops in
cooling or heating mode After operation stops During defrosting operations
(See figure below
1)
During oil recovery operations
During 20Hz operations, at fall in low pressure saturation temperature. (ET) (3 minutes or more after starting)
When high pressure rises (Pd)
When high pressure rises (Pd) during 20Hz operations (3 minutes after starting)
When discharge temperature rises (3 minutes after starting)
Ex. SV1
When low pressure saturation temp. (ET) is -15˚C (5°F) or more
When Pd is 23kg/ cm
2
G (327psi) or less
after 30 seconds When high pressure
(Pd) is 20kg/cm
2
G
(284psi) or less When discharge
temp. is 115˚C (239°F) or less
SV2
 
 
OFF (Close)
ON (Open)
When low pressure saturation temp. (ET) is -30˚C (-22°F) or less
When Pd reaches
26kg/cm
2
G (370psi)
or more
Turned on when high pressure (Pd) ex­ceeds pressure limit
When temp. exceeds 130˚C (266°F) and Pd reaches 15kg/cm2G (213psi) or more
Start
Thermo. OFF
Thermo. ON
(4-minute)
(3-minute)
Stop
Bypass solenoid valve (SV1)
Compressor
(2-minute)
(4-minute)
Defrost­ing time (*1)
-26-
Page 30
30
(4) Frequency control
Depending on capacity required, capacity control change and frequency change are performed to keep constant evaporation temperature (0˚C) in cooling operations, and high pressure (18kg/cm
2
G) in heating operation.
Frequency change is perfprmed at the rate of 3Hz/second across 20 ~ 110Hz range.
1) Frequency control starting
60Hz is the upper limit for 3 minutes after starting.
75Hz is the upper limit within 2 hours after turning on power source, and 30 minutes after starting compressor.
2) Pressure limit The upper limit of high pressure (Pd) is set for each frequency. When the limit is exceeded, frequency is reduced every 10 seconds. (Frequency decrease rate (Hz) : 22% of the present value)
3) Discharge temperature limit Discharge temperature (Td) of compressor is detected during operation. If the upper limit is exceeded, the frequency is reduced. (Change rate : 5% of the present value)
30 seconds after starting compressor, control is performed every minute.
Operation temperature is 130˚C (266°F).
4) Periodical frequency control Frequency controll is periodically performed except for the frequency controls at operation start, status change, and protection.
1 Cycle of periodical frequency control
Periodical frequency control is performed every minute after the time specified below has passed.
20 sec after starting compressor or finishing defrostoing operations
20 sec after frequency control by discharge temperature or pressure limit
2 Amount of frequency change
The amount of frequency change is controlled corresponding to evaporation temperature (ET) and high pressure
(Pd).
<80TM>
<100TM>
25 (356)
23 (327) 22 (313)
25 (356)
24 (341) 22 (313)
kg/cm2G (psi)
kg/cm2G (psi)
-27-
Page 31
28˚C (82.4°F) or more
111 111 157
20 ~ 30˚C (68~86°F)
87 87 134
22˚C (71.6°F) or less
64 64 87
3 Back up of frequency control by bypass valve
During 20Hz operations, frequency is backed up by turning on (opening) bypass valve (SV2).
• Cooling During 20Hz operations 3 minutes after starting compressor, bypass valve is turned on when ET is -30˚C (-22°F) or less, and turned off when ET is -15˚C (5°F) or more.
• Heating During 20Hz operations 3 minutes after starting compressor, SV2 turned on when high pressure (Pd) exceeds pressure limit (See previous page.), and turned off when Pd falls to 20kg/cm
2
G or less.
(5) Oil return control (Electronic expansion valve <SLEV>)
Oil return LEV (SLEV) opening is dependent on frequency and outdoor air tem­perature. SLEV is closed (0) when compressor stops, and SLEV is set (64) for 10 minutes after starting compressor
.
Operation mode
Cooling (Dry)
Operation mode
Heating
Frequency
Outdoor air temp.
20 ~ 74Hz 75 ~96Hz 97Hz or more
Note :1. Differential of outdoor air temperature is 2 degrees.
2. The opening shown above may be expanded for preventing rise in discharge temperature (at Td
>
=
90˚C).
(Number of pulse)
Frequency
Outdoor air temp.
20 ~ 74Hz
75 ~96Hz 97Hz or more
87 87 111
ON OFF
ON OFF
-30˚C
(-22°F)
(284psi) (313psi)
(5°F)
-15˚C
20kg/cm2G 22kg/cm2G
(6) Subcool coil control (electronic expansion valve <LEV1>)
• The amount of super heat detected from the bypass outlet temperature of subcool coil (TH8) is controlled to be within a certain range for each 20 sec.
• The opening angle is corrected and controlled depending on the outlet/inlet temperature of subcool coil (TH5, TH7) and the discharge temperature.
• However, the valve will be closed (0) at heating and compressor stopping.
• It will fully open at defrosting.
(7) Defrost operation control
1) Starting of defrost operations
• After integrated 50 minutes of compressor operations, defrosting operations start when –2˚C (28.4°F) or less of piping temperature (TH5) is detected for 10 consecutive minutes.
• Forcible defrosting operations start by turning on forcible defrost switch (SW2-7) if 10 minutes have already elapsed after compressor start or completion of defrosting operations.
2) Completion of defrosting operations Defrosting operations stop when 10 minutes have passed since start of defrosting operation, or piping temperature (TH5) reaches 12˚C (53.6°F) (80TMU), 8˚C (46.4°F) (100TMU) or more. (Defrosting operations do not stop for 2 minutes after starting, except when piping temperature exceeds 20˚C.)
3) Defrosting prohibition Defrosting operations do not start during oil recovery, and for 10 minutes after starting compressor.
4) Trouble during defrosting operations When trouble is detected during defrosting operations, the defrosting operations stop, and defrosting prohibition time decided by integrated operation time of compressor is set to be 20 minutes.
-28-
Page 32
5) Change in number of operating indoor units during defrosting operations
In case number of operating indoor units changes during defrosting operations, the defrosting operations continue, and control of unit number change is performed after the defrosting operations are finished.
Even in case all indoor units stop or thermostat is turned off during defrosting operations, the defrosting operations do not stop until expected defrosting activities are completed.
(8) Control of liquid level detecting heater
Detect refrigerant liquid level in accumulator, and heat refrigerant with liquid level heater for judging refrigerant amount. 6 steps of duty control is applied to liquid level heater depending on frequency and outdoor air temperature, 1minute after starting compressor.
(9) Judgement of refrigerant amount
TdSH=Discharge Super Heat.
=Td-Tsg (low pressure saturation temperature)
TdSH 50<TdSH 45<TdSH<50 40<TdSH<45 20<TdSH<40 TdSH<20
-
-
-
-
15°C<TH5
AL=0 AL=0 AL=0 AL=1 AL=2
-
-
-
-
-
-
20~45Hz
AL=0 AL=1 AL=1 AL=1 AL=2
Compressor
Frequency
46~70Hz
AL=0 AL=0 AL=1 AL=1 AL=2
71Hz~Fmax
AL=0 AL=0 AL=0 AL=1 AL=2
TdSH 90<TdSH 70<TdSH<90 50<TdSH<70 20<TdSH<50 TdSH<20
-
-
-
-
-
-
-
-
TH5<5°C
AL=0 AL=1 AL=1 AL=1 AL=2
TH5
-
-
5°C<TH5<15°C
AL=0 AL=0 AL=1 AL=1 AL=2
Cooling
Heating
-29-
Page 33
Starts
Finish
30 seconds
LEV opening before change
LEV opening at refrigerant recovery (Indoor unit LEV opening 500 pulse)
(10) Refrigerant recovery control
Refrigerant recovery is conducted to prevent refrigerant from accumulating in the stopped unit (fan unit), the unit under cooling mode and that with heating thermostat being turned off.
1) Start of refrigerant recovery 1 Refrigerant recovery is started when the two items below are fully satisfied.
30 minutes has passed after finishing refrigerant recovery.
The level detector detects AL = 0 for 3 minutes continuously, or when the discharge SH is high.
2) Refrigerant recovery operation
Refrigerant is recovered by opening LEV of the objective indoor units (indoor units under stop. fan, and cooling
modes, and that with heating thermostat being turned off) for 30 seconds.
The regular capacity control of the outdoor unit and the regular LEV control of the indoor unit are not applied during
refrigerant recovery operation, but are fixed with the value before the recovery operation. These controls will be conducted one minute after finishing the recovery operation.
Defrosting operation is prohibited during the recovery operation, and it will be conducted after finishing the recovery
operation.
(11) Control of outdoor unit fan and outdoor unit heat exchanger capacity
1) Control system Depending on capacity required, control outdoor fan flow rate with phase control, for maintaining evaporation tem­perature (0˚C (32°F) when TH6
>
=
20˚C (68°F) , lower than 0˚C (32°F) when TH6<20˚C (68°F) ) in cooling operations,
and high pressure 18kg/cm
2
G (256psi) in heating operations.
2) Control
Outdoor unit fan stops when compressor stops.
Fan is in full operation for 5 seconds after starting.
Outdoor unit fan stops during defrosting operations.
-30-
Page 34
YES
NO
YES
NO
YES
YES
NO
NO
[2] Operation Flow Chart
(1) Outdoor unit (Cooling, heating modes)
Note: 1 For about 2 minutes after turning on power source, address and group information of outdoor unit, indoor unit, and remote
controller are retrieved by remote controller, during which "HO" blinks on and off on remote controller. In case indoor unit is not grouped to remote controller, "HO" display on remote controller continues blinking even after 2 minutes after turning on power source.
Note: 2 Two trouble modes included indoor unit side trouble, and outdoor unit side trouble. In the case of indoor unit side trouble, error
stop is observed in outdoor unit only when all the indoor units are in trouble. However, if one or more indoor units are operating normally, outdoor unit shows only LED display without undergoing stop.
Note : 3 Operation mode conforms to mode command by indoor unit. However, when outdoor unit is being under cooling operation,
the operation of indoor unit will be prohibited even by setting a part of indoor units under operation, or indoor unit under stopping or fan mode to heating mode. Reversely when outdoor unit is being heating operation, the same condition will be commenced.
"HO" blinks on remote controller temperature display
Start
Breaker
turned on
Set indoor ad-
dress No. to remote
controller
Operation command
Operation
mode
52C ON
Operation
mode
Protection function
self-holding
Outdoor unit LED
trouble display
Cooling
operations
Heating
operations
Operation mode command to indoor unit controller
1. 52C OFF
2. Inverter output 0Hz
3. Fan stop
4. All solenoid valve OFF
Normal operations Trouble observed Stop
Note: 3
Note: 2
Note: 1
1. Protection function self­holding cancelled
2. Oil return LEV, SC coil LEV fully closed
Fan
Cooling, Heating
Error mode
Error stop
Error command to
indoor unit
-31-
2
2
Page 35
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
(2) Indoor unit (Cooling, heating, dry, and fan modes)
Start
Breaker
turned on
Operation
SW turned on
1. Protection function self-holding cancelled
2. Indoor unit
LEV
fully
closed
Remote controller
display extinguished
Aux. heater
ON
FAN stop
Drain pump
ON
1. Aux. heater OFF
2. 1 minute low FAN speed
3-minute drain
pump ON
Protection function
self-holding
Error command
to outdoor unit
Indoor unit LEV
fully closed
Heating
mode
Cooling
mode
Operation mode
Fan mode
Dry mode
Cooling
display
Heating
display
Dry display
Fan displays
Cooling
operations
Prohibition
Prohibition
Prohibition
Heating
operations
Dry
operations
Fan
operations
Prohibition
"Remote con-
troller blinking"
Note: 1
Note: 2
Note: 3
Note: 3
Note: 3
Normal operations Trouble observed Stop
Note: 4
Note : 1 At indoor unit LEV fully closed, the opening angle indicates 41.
Note : 2 The error mode includes that of indoor unit and that of outdoor unit. In the former case, the indoor unit in question only
stops in error mood, while in the later case, all indoor units connected to the outdoor unit stop in error mode.
Note: 3 T he operation mode follows the mode command from the indoor unit. However, when the outdoor unit is under cooling
operation, the operation of the indoor unit will be prohibited even a part of indoor units or indoor unit under stopping or fan mode is put into heating mode. Contrarily, when the outdoor unit is under heating operation, the same condition will be commenced.
Note: 4 The auxiliary heater can only be equipped to the product of special specification.
Error mode
Error stop
Error display
-32-
1
1
2
Page 36
YES
NO
YES
YES
NO
NO
(3) Cooling operation
Note : 1 Indoor unit fan operates at set notch in cooling operation regardless of thermostat ON/OFF.
Cooling operation
4-way valve OFF
Indoor unit fan
operations
Test run start
Thermostat ON
Note: 1
3-minute
restart pre-
vention
1. Inverter output 0Hz
2. Indoor unit LEV, oil return LEV,
Subcool coil bypass LEV fully closed
3. Solenoid valve OFF
4. Outdoor unit fan stop
1. Inverter frequency control
2. Indoor unit LEV, oil return LEV, Subcool coil bypass LEV fully closed
3. Solenoid valve control
4. Outdoor unit fan control
2 : (6) 1 or 3 : (6) 2
Normal operations Test run Stop
-33-
Page 37
YES
NO
(4) Heating operation (Only for PUHY)
Normal operations Defrosting operations Stop Test run
Heating operation
Defrosting
operation
4-way valve ON
Test run start
Thermostat ON
3-minute
restart pre-
vention
Defrosting finish
Defrosting
finish
4-way valve OFF
Note: 1 Note: 2
YES
1 : (6) 4 or 3 : (6) 2
1. Indoor unit fan very low speed operations
2. Inverter output 0Hz
3. Indoor unit LEV, oil return LEV, Subcool bypass LEV fully closed
4. Solenoid valve OFF
5. Outdoor unit fan stop
1. Indoor and outdoor unit fan control
2. Inverter frequency control
3. Indoor unit LEV, oil return LEV, Subcool bypass LEV control
4. Solenoid valve control
1. Indoor unit fan stop
2. Inverter defrost frequency control
3. Indoor unit LEV fully opened, oil return LEV fully closed, Subcool bypass LEV fully opened
4. Solenoid valve control
5. Outdoor unit fan stop
Note : 1 When outdoor unit starts defrosting, it transmits defrost operations command to indoor unit, and the indoor unit starts
defrosting operations. Similarly when defrosting operation stops, indoor unit returns to heating operation after receiving defrost end command of outdoor unit.
Note : 2 Defrosting start condition : After integrated 50 minutes of compressor operations, and –2˚C or less outdoor unit coil
temperature.
Defrosting end condition : After 15 minutes of defrosting operation or the outdoor unit coil temperature having risen to 12˚C
(80TMU), 8˚C (100TMU) or more for 80TMU and 100TMU.
Note: 1 Note: 2
-34-
NO
YES
NO
YES
NO
YES
Page 38
YES
NO
YES
YES
NO
(5) Dry operation
Normal operations Thermostat ON Stop
Dry operations
4-way valve OFF
Thermostat ON
Test run start
Inlet temp.
>
=
18˚C
Note: 2
Note: 1
1. Indoor unit fan stop
2. Inverter output 0Hz
3. Indoor unit LEV, oil return LEV, Subcool bypass LEV fully closed
4. Solenoid valve OFF
5. Outdoor unit fan stop
1. Outdoor unit (Compressor) intermittent operations
2. Indoor unit fan intermittent operations (Synchronized with compressor : low speed, OFF operations)
2 : (6) 1 or 3 : (6) 2
Note : 1 When indoor unit inlet temperature exceeds 18˚C, outdoor unit (compressor) and indoor unit fan start intermittent operations
synchronously. Operations of outdoor unit, indoor unit LEV and solenoid valve accompanying compressor are the same as those in cooling operations.
Note : 2 Thermostat is always kept on in test run, and indoor and outdoor unit intermittent operation (ON) time is a little longer than
normal operations.
-35-
Page 39
Low pressure shell scroll type with capacity control mechanism Winding resistance: Each phase 0.107 (20˚C)
Setting 30kg/cm2G OFF
R120=7.465k B
25/120=4057
Rt =
7.465exp{4057( – )}
R0=15k B
0/100=3460
Rt = 15exp{3460( – )}
R
50=17k
B25/50=4170 Rt =
Com- MC pressor
Pressure 63HS sensor
Pressure 63H switch
Thermistor TH1
(discharge)
TH2 (low pressure saturation temperature)
TH5 (piping temperature)
TH6 (outdoor air temperature)
TH7 (subcool coil outlet tempe­rature)
TH8 (subcool coil bypass outlet temperature)
THHS
Symbol
(function)
Part code Application Specification Check method
Adjust refrigerant circulation by con­trolling operating frequency and ca­pacity control valve with operating pressure.
1) High press. detection.
2) Frequency control and high pres­sure protection
1) High pressure detection
2) High pressure protection
1) Discharge temperature detection
2) High pressure protection
1) Detects the saturated vapor tem­perature.
2) Calculates the refrigerant circulation configuration.
3) Controls the compressor frequency.
4) Controls the outdoor units fan air volume.
1) Frequency control
2) Defrost control and liquid level de­tection at heating
1) Outdoor air temperature detection
2) Fan control, liquid level heater, and opening setting for oil return
Subcool coil bypass LEV (LEV1) con­trol
Subcool coil bypass LEV (LEV1) con­trol
1) Detects the inverter cooling fin temperature.
2) Provides inverter overheating protection.
3) Controls the control box cooling fan.
1
1
273+t 393
Continuity check
Resistance value check
Resistance value check
Name
Outdoor unit
[3] List of Major Component Functions
1 1
273+t 273
Gnd (black) Vout (white) Vcc (DC5V) (red)
Con­nector
Pressure 0~30 kg/cm2G Vout 0.5~3.5 V
63HS
0˚C (32˚F) : 15k 10˚C (50˚F) : 9.7k 20˚C (68˚F) : 6.4k 25˚C (77˚F) : 5.3k 30˚C (86˚F) : 4.3k 40˚C (104˚F) : 3.1k
20˚C (68˚F) : 250kΩ70˚C (158˚F) : 34k
30˚C (86˚F) : 160kΩ80˚C (176˚F) : 24k
40˚C (104˚F) : 104kΩ90˚C (194˚F) : 17.5k
50˚C (122˚F) : 70kΩ100˚C (212˚F) : 13.0k
60˚C (140˚F) : 48kΩ110˚C (230˚F) : 9.8k
-20˚C (-4˚F) : 605.0k
-10˚C (14˚F) : 323.3k 0˚C (32˚F) : 180.9k 10˚C (50˚F) : 105.4k 20˚C (68˚F) : 63.8k 30˚C (86˚F) : 39.9k 40˚C (104˚F) : 25.7k 50˚C (122˚F) : 17.0k 60˚C (140˚F) : 11.5k 70˚C (158˚F) : 8.0k 80˚C (176˚F) : 5.7k 90˚C (194˚F) : 4.1k 100˚C (212˚F): 3.0k
R
0=33k
B
0/100=3965
Rt = 33exp{3965( – )}
1 1
273+t
273+0
0˚C (32˚F) : 33k
-10˚C (14˚F) : 55k
-20˚C (-4˚F)
: 92k
10˚C (50˚F) : 20k 20˚C (68˚F) : 13k 30˚C (86˚F) : 8.2k
-36-
Page 40
Symbol
(function)
Part code Application Specification Check method
Name
Solenoid valve
Electronic expansion valve
Liquid level detection heater
Electronic expansion valve
Thermistor
SV1 (discharge ­suction by­pass)
SV2 (discharge ­suction by­pass)
SLEV
LEV1 (SC coil)
CH2, CH3 (accumulator liquid level detection)
LEV
TH21 (inlet air temperature)
TH22 (piping temperature)
TH23 (gas side piping temperature)
1) High/low press. bypass at starting/ stopping and capacity control at low load
2) Discharge press. rise suppression
Capacity control and high press. rise suppression (backup for frequency control)
Adjustment of liquid refrigerant (oil) return foam accumulator
Adjustment of bypass flow rate from outdoor unit liquid line at cooling
Heating of refrigerant in accumulator liquid level detection circuit
1) Adjust superheat of outdoor unit heat exchanger outlet at cooling.
2) Adjust subcool of indoor unit heat exchanger at heating.
Indoor unit control (thermostat)
1) Indoor unit control (freeze prevention, hot adjust, etc.)
2) LEV control in heating operation (Subcool detection)
LEV control in cooling operation (Superheat detector)
Indoor unit
AC 220V Open at energizing and close at deenergizing
AC 220V Open at energizing and close at deenergizing
DC12V stepping motor drive Valve opening 0~480 pulse
Cord heater :2.8k
(1.4k+1.4k) AC220V 20W (10W + 10W)
DC12V Opening of stepping motor driving valve 60~2,000 pulses
R
0 = 15k
B
0/100 = 3460
Continuity check by tester
Resistance value check
Continuity check with tester for white­red-orange yellow-brown-blue
Resistance value check
Outdoor unit
: 15k 10˚C (50˚F) : 9.7k 20˚C (68˚F) : 6.4k 25˚C (77˚F) : 5.3k 30˚C (86˚F) : 4.3k 40˚C (104˚F) : 3.1k
Rt = 15exp{3460( – )}
1 1
273+t 273
0˚C (32˚F)
-37-
Page 41
[4] Resistance of Temperature Sensor
Thermistor for low temperature Thermistor Ro= 15k ± 3% (TH5 ~ 8) Thermistor R120 = 7.465k ± 2% (TH1) R
t = 15exp {3460 ( - )} Rt = 7.465exp {4057 ( - )}
˚F= × ˚C + 32 ˚F= × ˚C + 32
Thermistor Ro = 33k ± 1% (TH2) Thermistor R50 = 17k ± 2% (THHS) R
t = 33exp {3965 ( - )} Rt = 17exp {4170 ( - )}
˚F= × ˚C + 32 ˚F= × ˚C + 32
1
273+tc
1
273+tc
1
273+tc
1
273+tc
1
273+50
Temperature (˚C)[˚F] Temperature (˚C)[˚F]
Temperature (˚C)[˚F] Temperature (˚C)[˚F]
Resistance (k)
Resistance (k
)
Resistance (k)
Resistance (k)
1
273+0
1
273+120
1
273+0
9 5
9 5
9 5
9 5
-38-
Page 42
REFRIGERANT AMOUNT ADJUSTMENT5
Clarify relationship between the refrigerant amount and operating characteristics of CITY MULTI, and perform service activities such as decision and adjustment of refrigerant amount on the market.
[1] Refrigerant Amount and Operating Characteristics
The followings are refrigerant amount and operating characteristics which draw special attention.
During cooling operations, required refrigerant amount tends to increase (refrigerant in accumulator decreases) in proportion to increase in the number of operating indoor units. However, the change of increase rate is small.
During heating operations, liquid level of accumulator is the highest when all the indoor units are operating.
Discharge temperature hardly changes when increasing or decreasing refrigerant amount with accumulator filled with refrigerant.
Compressor shell temperature is 20~70 (36~126) degrees higher than low pressure saturation temperature (Te) when refrigerant amount is appropriate. Judged as over replenishment when temperature difference from low pressure saturation temperature (Te) is 10 (18) degrees or less.
[2] Adjustment and Judgement of Refrigerant Amount
(1) Symptom
The symptoms shown in the table below are the signs of excess or lack of refrigerant amount. Be sure to adjust the amount of refrigerant in refrigerant amount adjustment mode, by checking operation status, judging refrigerant amount, and performing selfdiagnosis with LED Dip s/w 1, 1-10, for overall judgement of excess or lack of refriger­ant amount.
Tendency of discharge temperature
During cooling operations, discharge temperature tends to rise at overload than low temperature.
During heating operations, discharge temperature tends to rise at low temperature than overload.
The lower the operating frequency is, the higher the discharge temperature tends to become of deteriorated compressor efficiency.
Comparison including control system
Emergency stop at 1500 remote controller display (excessive refrigerant replenishment)
Operating frequency does not fully increase, thus resulting in insufficient capacity
Emergency stop at 1102 remote controller display (discharge temperature trouble)
Emergency stop occurs when the remote control display is at
1501. (insufficient refrigerant)
Excessive refrigerant replenishment
Insufficient refrigerant replenishment
Insufficient refrigerant
1
2
3
4
5
1
2
3
4
Note : ˚C Scale (˚F Scale)
-39-
Page 43
(2) Refrigerant Volume Adjustment Operation
1) Operating Characteristics Refrigerant Volume Characteristic items related to operating characteristics and the refrigerant volume are shown below.
If the number of indoor units in operation increases during cooling, the required volume of refrigerant tends to increase (the amount of refrigerant in the accumulator tends to decrease), but the change is minimal.
The liquid level in the accumulator is at its highest when all the indoor units are operating during heating. If there is refrigerant in the accumulator, even if the volume of refrigerant is increased or decreased, there is practi-
cally no change in the outlet temperature.
During cooling, the discharge temperature rises more easily when there is an overload than when the temperature is low.
During heating, the discharge temperature rises more easily when the tempera­ture is low than when there is an overload.
The lower the operating frequency, the less efficient the compressor is, making it easier for the discharge temperature to rise.
The compressor shell temperature becomes 20~70 (36~126) deg. higher than the low pressure saturation tempera­ture (TH2) if the refrigerant volume is appropriate. If the difference with the low pressure saturation temperature (TH2) is 10 (18) deg. or less, it can be judged that the refrigerant is overcharged.
2) Adjusting and Judging the Refrigerant Volume
1 Symptoms
Overcharging with refrigerant can be considered as the cause of the following symptoms. When adjusting the refrigerant volume, be sure that the unit is in the operating condition, and carry out refrigerant volume judgment and self-diagnosis by the LED’s, judging overall whether the volume of refrigerant is in excess or is insufficient. Perform adjustments by running the unit in the refrigerant volume adjustment mode.
2 Refrigerant V olume a Checking the Operating Condition
Operate all the indoor units on cooling or on heating, checking the discharge temperature, sub-cooling, low pres­sure saturation temperature, inlet temperature, shell bottom temperature, liquid level, liquid step, etc. and rendering an overall judgment.
1 2
3
4
5
Tendency of discharge Temperature
Comparison when control is included.
Emergency stop occurs when the remote control display is at 1500 (refrigerant overcharge).
The operating frequency doesn’t rise high enough and capacity is not achieved. Emergency stop occurs when the remote control display is at 1102 (outlet
temperature overheating). Emergency stop occurs when the remote control display is at 1501 (insufficient
refrigerant).
1 2 3
4
Refrigerant overcharge
Insufficient refrigerant
Insufficient refrigerant
Judgement
Refrigerant volume tends toward insufficient.
Rifrigerant volume tends toward overcharge.
Condition 1 Outlet temperature is high. (125°C (257˚F) or higher) 2 Low pressure saturation temperature is extremely low. 3 Inlet superheating is high (if normal, SH = 20 (36) deg or lower). 4 Shell bottom temperature is high (the difference with the low pressure saturation
temperature is 70 (126) deg. or greater)
5 Shell temperature is low (the difference with the low pressure saturation tem-
perature is 10 (18) deg. or lower).
6 Dischange superheating is low (if normal, SH = 20 (36) deg or higher).
Note : ˚C Scale (˚F Scale)
Note : ˚C Scale (˚F Scale)
-40-
Page 44
b Check the refrigerant volume by self-diagnosis using the LED.
Set the self-diagnosis switch (SW1) as shown below and check the past information (history) concerning the refrigerant volume.
Set SW1 as shown in he figure at right.
If LD8 lights up, it indicates the refrigerant charge abnormal delay state just before emergency stop due to refriger­ant overcharge (1500).
3 Additional Refrigerant Charge Volume
At the time of shipping from the factory, the outdoor unit is charged with the amount of coolant shown in the follow­ing table, but since no extension piping is included, please carry out additional charging on-site.
Outdoor Unit Model Name PUHY-80TMU-A PUHY-100TMU-A Refrigerant Charge Volume 6.5kg 9kg
(14lb 6oz) (19lb 14oz)
Calculation Formula Calculate the additional refrigerant volume by calculating the size of the extension liquid piping and its length units (m)[ft].
Additional Refrigerant Volume (kg) = (0.12 × L
1) + (0.06 × L2) + (0.024 × L3) + A
[ (oz) = (1.29 × L1) + (0.65 × L2) + (0.26 × L3) + A ]
L
1: Length of ø12.7 (3/4") liquid pipe (m) [ft]
L2: Length of ø9.52 (3/8") liquid pipe (m) [ft] L3: Length of ø6.35 (1/4") liquid pipe (m) [ft] A: refer to the calculation table.
In the calculation results, round up fractions smaller than 0.01 kg. (Example: 18.54 kg 18.6 kg)
1.0oz (653.97oz 654oz)
(Calculation Table)
Total Capacity of A
Connected Indoor Units kg (oz)
~64 1.5 (53) 65~ 2.0 (71)
12345678910
ON
-41-
Page 45
3) Refrigerant Volume Adjustment Mode Operation
1 Procedure
TH1 Self-diagnosis Switch TH5 Self-diagnosis Switch
TH7 Self-diagnosis Switch Tc Self-diagnosis Switch
Using these, judge TH1, Tc - TH5 and Tc - TH7.
12345678910
ON
12345678910
ON
12345678910
ON
12345678910
ON
Operation
Measure
The outdoor unit LEV1 diverges more than usual during cooling operation.
Depending on the operating conditions, it may be necessary either to charge with supplementary refrigerant, or to
1
drain out some, but if such a case arises, please follow the procedure given below flow chart.
A
C
12345678910
ON
Switching the function select switch (SW2-4), located on the outdoor unit's control board, ON starts refrigerant volume adjustment mode operation and the following operation occurs. (Refrigerant recovery mode and oil recovery mode will be invalid.)
2
Additionary, if the LED monitor display switch (SW1) on the outdoor unit's control board is set to the composition of refrigerant circulating in the refrigeration cycle ( OC).
Note 1: Even if the refrigerant volume has reached a suitable level shortly after starting refrigerant volume
adjustment mode, if left for a sufficient length of time (once the refrigeration system has stabilized), there are times when this level may become unsuitable.
1) The refrigerant volume is suitable. When the refrigerant volume for TH5-TH7 is more than 5K at the outdoor unit, and 6 to 13K for SH at the indoor unit.
2) The current volume is suitable, however, may become unsuitable after a certain length of time. When the refrigerant volume for TH5-TH7 is less than 5K at the outdoor unit, or less than 6K for SH at the indoor unit.
Note 2: There are times when it becomes difficult to determine the volume when performing refrigerant
adjustments if the high pressure exceeds 1.37MPa.
Note 3: Based on the following flowchart, use TH1, TH5, TH7 and Tc to adjust the refrigerant volume. Use the
self-diagnosis switch (SW1) on the outdoor unit main PCB to display TH1, TH5, TH7 and Tc.
When running refrigerant volume adjustment mode in the cooling operation, if note 2 above applies, determine the suitable refrigerant volume after waiting until outdoor units TH 5-7 reach more than 5K, and the indoor unit SH is in the range of 6 to 9K.
Turn on the outdoor unit self-diagnosis switch and then monitor the LED for the indoor unit SH.
-42-
Page 46
Refrigerant adjustment method
Note 2 , Ensure that no refrigerant is released into the atmosphere
Note 1, Operated using outdoor unit DIP SW3-1 and 3-2.
Note 3 , Always charge the system with liquid refrigerant, if the system is charged with gas the composition will change and capacity will be reduced
Wait for 30minutes of
Note 1
compressor operation
= Yes = No
Note 4 , K = Degrees Kelvin
273K = 0°C
Wait 5minutes before making next judgment.
Wait 5minutes before making next judgment.
Wait 5minutes before making next judgment
Start
All indoor units are run in test cooling mode
Minimum of 30minutes continuous operation
TH1 equal or less than 115°C
Add a small amount of refrigerant to the low pressure service port.
Power supply to outdoor unit has been on for 8 hours
or 30minutes of compressor running
and a stable compressor frequency.
Tc-TH5 is less than or equal to 10K and greater than or equal to 3K
TH1 equal or less than 110°C
Tc-TH7 is greater than or equal to 20K
Tc-TH5 is less than 3K
Add asmall amount of refrigerant at the low pressure service port.
Add a small amount of refrigerant at low pressure service port.
Add a small amount of refrigerant at low pressure service port.
Remove a small amount of refrigerant at lowpressure service port.
System has the correct amount of refrigerant
FINISH
-43-
Page 47
6 TROUBLESHOOTING
[1] Principal Parts
Pressure Sensor
(1) Judging Failure
1) Check for failure by comparing the sensing pressure according to the high pressure sensor and the pressure gauge pressure. Turn on switches 1, 3, 5, 6 of the digital display select switch (SW1) as shown below, and the sensor pressure of the high pressure sensors is displayed digitally by the light emitting diode LD1.
High Pressure
1 In the stopped condition, compare the pressure readings from the gauge and from the LD1 display.
(a) If the gauge pressure is 0~0.098MPa (0~14.2 psi), the internal pressure is dropping due to gas leakage. (b) If the pressure according to the LD1 display is 0~0.098MPa (0~14.2 psi), there is faulty contact at the connec-
tor, or it is disconnected. Proceed to 4. (c) If the pressure according to the LD1 display is 3.14MPa (455 psi) or higher, proceed to 3. (d) If other than (a), (b) or (c), compare the pressure readings during operation. Proceed to 2.
2 Compare the pressure readings from the gauge and from the LD1 display while in the running condition.
(a) If the difference between the two pressures is within 0.098MPa (14.2 psi), both the affected pressure sensor
and the main MAIN board are normal. (b) If the difference between the two pressures exceeds 0.098MPa (14.2 psi), the affected pressure sensor is faulty
(deteriorating performance). (c) If the pressure reading in the LD1 display does not change, the affected pressure sensor is faulty.
3 Disconnect the pressure sensor from the MAIN board and check the pressure according to the LD1 display.
(a) If the pressure is 0~0.098MPa (0~14.2 psi) on the LD1 display, the affected pressure sensor is faulty. (b) If the pressure is 3.14MPa (455 psi) or higher, the MAIN board is faulty.
4 Disconnect the pressure sensor from the MAIN board and short out the No. 2 and No. 3 pins of the connector
(63HS), then check the pressure by the LD1 display. (a) If the pressure according to the LD1 display is 3.14MPa (455 psi) or higher, the affected pressure sensor
is faulty. (b) If other than (a), the MAIN board is faulty .
2) Pressure sensor configuration. The pressure sensors are configured in the circuit shown in the figure at right. If DC 5 V is applied between the red and black wires, a voltage corresponding to the voltage between the white and black wires is output and this voltage is picked up by the microcomputer. Output voltages are as shown below.
High Pressure 0.1 V per 0.098MPa (14.2 psi)
12345678910
ON
Connector
Vout 0.5~3.5 V
GND (Black) Vout (White) Vcc (DC5V) (Red)
63HS
-44-
Page 48
Solenoid Valve (SV1, SV2)
Check if the control board’s output signals and the operation of the solenoid valves match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED’s. Each LED shows whether the relays for the following parts are ON or OFF. When a LED lights up, it indicates that the relay is ON.
SW1
LED
12345678
12345678910
ON
12345678910
ON
Compressor
operating.
Crankcase
Heater
Lights up
all the
time.
21S4 SV1 SV2
1) In the case of SV1 (Bypass Valve)
(a) When the compressor starts, SV1 is ON for 4 minutes, so check operation by whether the solenoid valve is emitting
an operating noise.
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the bypass
circuit and the sound of the refrigerant.
2) In the case of SV2 (Bypass)
(a) SV2 goes ON in accordance with the rise in the high pressure in the cooling mode and heating mode, so check its
operation by the LED display and the operating noise emitted by the solenoid valve.
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the bypass
circuit and the sound of the refrigerant.
Connector connection specifications on the pressure sensor body side. The connector’s pin numbers on the pressure sensor body side differ from the pin numbers on the main circuit board side.
Sensor Body Side MAIN Board Side
Vcc Pin 1 Pin 3 Vout Pin 2 Pin 2 GND Pin 3 Pin 1
CH 2, 3
Fluid Level
Heater
-45-
Page 49
Outdoor LEV
The valve opening angle changes in proportion to the number of pulses. (Connections between the outdoor units MAIN board and SLEV, LEV1 (outdoor electronic expansion valve))
Pulse Signal Output and Valve Operation
LEV Valve Closing and Valve Opening Operations
When the power is switched ON, a 520 pulse valve opening signal is output to make sure the valve’s position, so that it is definitely at point A. (The pulse signal is output for approximately 17 seconds.)
When the valve operates smoothly, there is no sound from the LEV and no vibration occurs, but when the valve is locked, it emits a noise.
Whether a sound is being emitted or not can be de­termined by holding a screwdriver, etc. against it, then placing your ear against the handle.
If there is liquid refrigerant inside the LEV, the sound may become lower.
Output pulses change in the following orders when the
Valve is Closed 1 2 3 4 5 6 7 → 8 → 1 Valve is Open 8 7 6 5 4 3 2 → 1 → 8
1.When the LEV opening angle does not change, all the output phases are off.
2.When the output is out of phase or remains ON con­tinuously, the motor cannot run smoothly, but move jerkily and vibrates.
Output State
12345678
ø1 ON OFF OFF OFF OFF OFF ON ON ø2 ON ON ON OFF OFF OFF OFF OFF ø3 OFF OFF ON ON ON OFF OFF OFF ø4 OFF OFF OFF OFF ON ON ON OFF
Output (Phase)
No.
Driver Circuits
Outdoor MAIN Board (Connectors CNLV1, CNLV2)
Gray Black Yellow Red Orange
Valve Opening Angle (Flow Rate)
Valve Closing
Valve Opening
Fully Open 480 pulses
Pulse Count
-46-
Page 50
Judgment Methods and Likely Failure Mode
Caution:
The specifications of the outdoor unit (outdoor LEV) and outdoor units (indoor LEV) differ. For this reason, there are cases where the treatment contents differ, so follow the treatment specified for the appropriate LEV as indicated in the right column.
Disconnect the control board connector and connect the check LED as shown in the figure below.
When the base power supply is turned on, the indoor LEV outputs pulse signals for 10 seconds. If the LED does not light up, or lights up and remains on, the driver circuit is abnormal.
If the LEV is locked up, the drive motor turns with no load and a small clicking sound is generated. Generation of this sound when the LEV is fully closed or fully open is abnormal.
Measure the resistance between the coils (red - white, red
- orange, brown - yellow, brown - blue) using a tester. They are normal if the resistance is within 150 ± 10%.
Measure the resistance between the coils (gray - orange, gray - red, gray - yellow, gray - black) using a tester. They are normal if the resistance is within 46 ± 3%.
If you are checking the indoor unit’s LEV, operate the in­door unit in fan mode and at the same time operate other indoor units in the cooling mode, then check the piping temperatures (liquid pipe temperatures) of the indoor unit by the operation monitor through the outdoor unit control­ler board. When the fan is running, the linear expansion valve is fully closed, so if there is leakage, the temperature sensed by the thermistor (liquid pipe temperature sensor) will become low. If the temperature is considerably low
compared to the remote control’s in­take temperature display, it can be judged that there is a fully closed fail­ure. In the case of minimal leakage, it is not necessary to replace the LEV if there are no other effects.
1 Check for pins not fully inserted on the connector and
check the colors of the lead wires visually.
2 Disconnect the control board’s connector and conduct
a continuity check using a tester.
Microcomputer Driver Circuit Failure
LEV mechanism is locked.
The LEV motor coils have a disconnected wire or is shorted.
Fully Closed Failure (valve leaks)
Faulty wire connections in the connector or faulty contact.
In the case of driver circuit failure, replace the indoor unit’s control board.
Replace the LEV.
Replace the LEV coils.
Replace the LEV coils.
If there is a large amount of leakage, replace the LEV.
Check the continuity at the places where trouble is found.
Indoor
Indoor
Outdoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Failure Mode Judgment Method Treatment Affected LEV
Thermistor (TH21)
Linear Expansion Valve
-47-
Page 51
Outdoor LEV (SLEV, LEV1) Coil Removal Procedure (configuration) As shown in the figure, the outdoor LEV is made in such a way that the coils and the body can be separated.
<Removing the Coils> Fasten the body tightly at the bottom (Part A in the figure) so that the body will not move, then pull out the coils toward the top. If they catch on the stopper and are difficult to take out, turn the coils left and right until the stoppers are free from the stopper indentations, then pull the coils out. If you take out the coils only without gripping the body, undue force will be applied to the piping and the pipe may be bent over, so be sure to fasten the body in such a way that it will not move.
<Installing the Coils> Fasten the body tightly at the bottom (Part A in the figure) so that the body will not move, then insert the coils from the top, inserting the coils stopper securely in one of the indentations on the body. (There are four indentations for the stopper on the body around its circumference, and it doesnt matter which indentation is used. However, be careful not to apply undue force to the lead wires or twist them around inside the body.) If the coils are in­serted without gripping the body, it may exert undue force on the piping, causing it to become bent, so be sure to hold the body firmly so that it wont move when installing the coils.
Part A
Coils
Stopper
Lead Wires
Body
Indentation for Stopper (12 places around the circumference)
Part A
-48-
Page 52
Intelligent Power Module (IPM)
The measured v
Measure resistances between each terminal of IPM with tester, and use the results for troubleshooting.
alues for troubleshooting are shown in the table below.
Diode stack
P
(Restrictions to applicable tester are the same as those of IPM)
erform continuity check with tester. Judged as normal if the following characteristics are observed.
123
1 2 3
+
W
External view Internal circuit diagram
Judged value
∞ ∞ ∞
P
P
Tester
Black
N
5~ 200
5~ 200
5~ 200
5~ 200
5~ 200
5~ 200
U
V
W
NUVW
∞∞∞
∞ ∞
+
+
Tester
Black
1 2 3
123
N
P
B
V
V
U
P
W
N
B
U
3
2
1 6
5
4 9
8
7 11
13
10
14
15
12
16
Pre-Driver
Pre-Driver
Pre-Driver
Pre-Driver
Pre-Driver
Pre-Driver
Over heating
Temperature sensor
protection circuit
16 10 7 4 1
1 Focus on whether there is a complete open (∞Ω) state or short-circuit (~0).
The measured resistance value is a guideline and may deviate slightly. Measure between several similar measurement points. If the value does not differ by more than double or half from the other points, then judge the state as OK.
2 Restrictions to applicable tester
Use a tester with an internal power of 1.5V or more.
Battery type tester
A card tester with button battery has a low applied voltage, so the resistance value of the diode characteristics cannot be measured correctly. Use a measurement range that measures the low resistance when possible. An accurate measurement with less fluctuation will be possible.
5~ 200
5~ 200
5~ 200
5~ 200
5~ 200
5~ 200
Tester
Red
∞∞∞
Tester
Red
-49-
Page 53
1
2
Despite pressing of remote controller switch, operation does not start with no electronic sound.
(No powering signal appears.)
At about 10 seconds after turning remote controller operation switch ON, the display distinguishes and the operation stops.
1) M-NET transmission power source is not supplied from outdoor unit.
1Main power source of outdoor unit is not connected. 2Slipping off of connector on outdoor unit circuit
board Main board : CNS1, CNVCC3 INV board : CNDC2, CNVCC2, CNL2 G/A board : CNDC1
3
Faulty power source circuit of outdoor unit
Faulty INV board,
Blown fuse (F01 on G/A board)
Broken diode stack
Broken resistor (R1) for rush current protection
2) Short circuit of transmission line
3) Erroneous wiring of M-NET transmission line at outdoor unit 1Transmission line disconnection or slipping off from terminal
block
2Erroneous connection of indoor/outdoor transmission line to
TB7
4) Slipping off of transmission wiring at remote controller
5) Faulty remote controller
The cause of 2) and 3) is dis­played with self-diagnosis LED for 7102 error.
1) Power source is not fed to indoor unit from transformer.
1Main power source of indoor unit is not turned on. 2Slipping off of connector (CND, CNT, CN3T) on indoor controller board 3Blown fuse on indoor controller board 4 5
Faulty or disconnected transformer of indoor unit Faulty indoor controller board
3) Faulty outdoor control circuit board or being out of control As normal transmission is failed between indoor and outdoor units, outdoor unit model can not be recognized.
Checking method & countermeasure
Symptom Cause Checking method & countermeasure
(5) Trouble and remedy of remote controller
Extinguishing or unable to confirm
Check indoor LED1
Lighting?
Lighting
Check fuse on circuit board
Blown?
Check connector slip­ping off
(CND, CNT, CN3T)
Slipped off?
Check transformer resistance value
Within rated?
Check self-diagnosis function of outdoor unit
Check for the change of LED display by operating dip switch SW1 for self-diagnosis.
Changed?
Check main power source of power source wiring.
Apply power source again.
Check 220V circuit for short circuit and ground fault.
Improper connector connection
Changed?
Casual trouble
Repair faulty point.
Faulty outdoor unit control circuit board
Faulty indoor controller board
Check self-diagnosis function after powering outdoor unit again.
Check indoor unit power source terminal block voltage
NO
YES
YES
1
NO
NO
YES
NO
NO
YES
YES
YES
NO
Check cause of trans­former disconnection.
Ground fault on circuit board
Ground fault on sensor, LEV
208~230V?
1 Check the transformer in accordance with the TROUBLE SHOOTING in the indoor units service handbook.
a) Check transmission terminal block of re-
mote controller for voltage.
i) In case of 17 ~ 30V
Faulty network remote controller
ii) In case of less than 17V
See “Transmission Power Circuit (30V) Check Procedure on Page 54.
-50-
Page 54
3
HO display on re­mote controller does not disappear and switch is ineffective.
Symptom Cause
(Without using MELANS)
1) Outdoor unit address is set to “00.”
2) Erroneous address 1Address setting miss of indoor unit to be coupled with remote controller
(Remote controller is not set to - 100.)
2Address setting miss of remote controller
(Indoor unit is not set to + 100.)
3) Faulty wiring of transmission terminal block
TB5
of indoor unit in the same group
with remote controller
4) Centralized control SW2-1 of outdoor unit is turned ON.
5) Disconnection or faulty wiring of indoor unit transmission line
6) Disconnection between indoor unit
M-NET
transmission line terminal block
(TB5) and connector CN2M
7) More than 2 sets of power supply connector (CN40) are inserted into centralized control transmission line of outdoor unit.
8) Faulty outdoor unit control circuit board
9) Faulty indoor controller board
10) Faulty remote controller
(Interlocking control with MELANS)
11) No grouping registration from MELANS (Neglecting to set the relation between indoor unit and net-
work remote controller)
12) Slipping off of centralized control transmission line (TB7) at outdoor unit
13) At system connected with MELANS, power supply connector (CN40) is inserted to centralized con-
trol transmission line of outdoor unit
In case no MELANS used
Same symptom for all units in a single refriger­ant system?
Check outdoor unit address
51 ~ 100?
Check centralized control switch SW2-1 at outdoor unit
ON?
Faulty outdoor unit control circuit board
Outdoor unit address set­ting miss
Switch setting miss Make it ON →OFF
Slipping off of CN2M connector
Repair spot in trouble
Setting miss of Fresh Master SW3-1
Indoor unit + 100?
Check address of coupling indoor unit
17 ~ 30V?
Slipping off?
Check Fresh Master SW3-1
ON?
Faulty indoor controller board or remote controller
Check voltage of indoor unit M­NET transmission terminal block
Address setting miss of remote controller
Indoor address setting miss
Transmission line wiring miss of in­door unit M-NET
Check connection between indoor unit M-NET trans­mission terminal block (TB5) and connector CN2M
YES
YES
NO
YES
NO
NO
YES
YES
YES
NO
In case with MELANS used When MELANS is used, HO display on the remote controller will disappear at the group registration of the indoor unit and local
remote controller. If HO does not disappear after the registration, check the items 12) ~ 14) in the Cause column.
Checking method & countermeasure
Remote controller
–100?
NO
NO
NO
YES
NO
Confirm address of remote controller with "HO" displayed
YES
-51-
Page 55
Symptom Cause Checking method & countermeasure
[Generates at registration and confirmation]
1) Erroneous address of unit to be coupled
2) Slipping off of transmission line of unit to be coupled (No connection)
3) Faulty circuit board of unit to be coupled
4) Installation miss of transmission line
[Confirmation of different refrigerant system con­troller]
5) Breaking of power source of outdoor unit to be confirmed
6) Slipping off of centralized control transmission line (TB7) of outdoor unit
7) Power supply connector (CN40) is not inserted into centralized control transmission line in grouping with different refrigerant system with­out using MELANS
8) More than 2 sets of power supply connector are inserted into the centralized control trans­mission line of outdoor unit
9) In the system connected with MELANS, power supply connector (CN40) is inserted into the centralized control transmission line of outdoor unit.
10) Short circuit of centralized control transmission line
a) Confirm the address of unit to be coupled. b) Check the connection of transmission line. c) Check the transmission terminal block voltage
of unit to be coupled i) Normal if voltage is DC17 ~ 30V ii) Check the item d) in case other than i).
d) Confirm the power source of outdoor unit to be
coupled with the unit to be confirmed
e) Confirm that the centralized control transmis-
sion line (TB7) of outdoor unit is not slipped off.
f) Confirm the voltage of centralized control trans-
mission line. i) Normal in case of 10V ~ 30V ii) Check the items 7) ~ 10) left in case that
other than i).
88 appears on re­mote controller at the registration and access remote controller
4
`
-52-
Page 56
Transmission Power Circuit (30 V) Check Procedure If
is not displayed by the remote control, investigate the points of the trouble by the following procedure and correct it.
DC24~30 V
Except the above-mentioned
Connector disconnected
Except the above-mentioned
DC24~30 V
Except the above-mentioned
DC24~30 V
Except the above-mentioned
0.5~2.5
Except the above-mentioned
DC280~342 V
Except the above-mentioned
0
Except the above-mentioned
20~24 Except the above­mentioned
refer to "Judging Diode stack Failure" Except the above-mentioned
AC187~253 V
Except the above-mentioned
No. Check Item Judgment Response
Disconnect the transmission line from TB3 and check the TB3 voltage.
Check if the following connectors are disconnected in the outdoor units control box. MAIN Board: CNS1, CNVCC3 INV Board: CNVCC2, CNL2, CNDC2
Disconnect the wires from CNVCC3 on the Main board and check the voltage between pins 1 and 3 on the wire side of the CNVCC3.
Tester + .......... 1 pin
Tester - .......... 3 pin
Disconnect the wiring from CNVCC2 on the INV board and check the voltage between pins 1 and 3 of CNVCC2.
Tester + .......... 1 pin
Tester - .......... 3 pin
Disconnect the wiring from CNL2 on the INV board, and check the resistance at both ends of choke coil L2.
Check the voltage between pins 1 and 3 of CNDC2 on the INV board.
Check the resistance at both ends of F01 on the G/A board.
Check the resistans at both ends of R1
Chcke the DS
Check the voltage between RS and T on power supply terminal block TB1.
Check the transmission line for the following, and correct any defects. Broken wire, short circuit, grounding, faulty contact.
to No. 2
Connect the connectors as shown on the electric wiring diagram plate.
to No. 3
Check the wiring between CNS1 and TB3 for the following, and correct any defects. Broken wire, short circuit, grounding, faulty contact. If there is no trouble, replace the Main board.
to No. 4
Check the wiring between CNVCC2 and CNVCC3 for the following, and correct any defects. Broken wire, short circuit, grounding, faulty contact.
to No. 5
to No. 6
Replace choke coil L2.
Replace the INV board.
to No. 7
to No. 8
Replace F01
to No. 9 Replace R1
to No.10 Replace DS
Check the wiring to TB1 for the following and correct any defects. Broken wire, faulty contact.
Check the power supply wiring and base power supply, and correct any defects.
1
2
3
4
5
6
7
8
9
10
-53-
Page 57
(6) Investigation of transmission wave shape/noise
Control is performed by exchanging signals between outdoor unit, indoor unit and remote controller by M-NET trans­mission. If noise should enter into the transmission line, the normal transmission will be hindered causing erroneous operation.
1) Symptom caused by the noise entered into transmission line
2) Method to confirm wave shape
Cause Erroneous operation Error code
Noise entered into Signal changes and is misjudged as the signal of other 6600 transmission line address.
Transmission wave shape changes to other signal due 6602 to noise.
Transmission wave shape changes due to noise, and can 6607 not be received normally thus providing no reply (ACK).
Transmission can not be made continuously due to the 6603 entry of fine noise.
Transmission can be made normally, but reply (ACK) or 6607 answer can not be issued normally due to noise. 6608
<with transmission>
<without transmission>
Check the wave shape of transmission line with an oscilloscope to confirm that the following conditions are being satisfied.
1 The figure should be 104µs/bit ± 1%. 2 No finer wave shape (noise) than the transmission signal (52µs ± 1%) should be allowed. ✻1 3 The sectional voltage level of transmission signal should be as follows.
1 However, minute noise from the DC-DC converter or inverter operation may be picked up.
Logical value Transmission line voltage level
0VHL = 2.0V or more 1VBN = 1.3V or less
No fine noise allowed ✻1
V
BN
VHL
52µs52µs52µs52µs52µs
Logical value "0
"
Logical value "1"
No fine noise allowed✻1
-54-
Page 58
3) Checking and measures to be taken
(a) Measures against noise
Check the items below when noise can be confirmed on wave shape or the error code in the item 1) is generated.
Items to be checked Measures to be taken
1 Wiring of transmission and power lines
in crossing
2 Wiring of transmission line with that of
other system in bundle
3 Use of shield wire for transmission line
(for both indoor unit control and central­ized control)
4 Repeating of shield at the repeating of
transmission line with indoor unit
5 Are the unit and transmission lines
grounded as instructed in the INSTAL­LATION MANUAL?
6 Earthing of the shield of transmission
line (for indoor unit control) to outdoor unit
7 Arrangement for the shield of transmis-
sion line (for centralized control)
Isolate transmission line from power line (5cm or more). Never put them in a same conduit.
Wire transmission line isolating from other transmission line. Wiring in bundle may cause erroneous operation like crosstalk.
Use specified transmission wire.
Type : Shield line CVVS/CPEVS Wire diameter : 1.25mm
2
or more
The transmission line is wired with 2-jumper system. Wire the shield with jumper system as same for transmission line. When the jumper wiring is not applied to the shield, the effect against noise will be reduced.
Connect to ground as shown in the INSTALLATION MANUAL.
One point earthing should be made at outdoor unit. Without earthing, transmission signal may be changed as the noise on the transmission line has no way to escape.
For the shield earth of the transmission line for centralized con­trol, the effect of noise can be minimized if it is from one of the outdoor units in case of the group operation with different refrig­erant systems, and from the upper rank controller in case the upper rank controller is used. However, the environment against noise such as the distance of transmission line, the number of connecting sets, the type of connecting controller, and the place of installation, is different for the wiring for centralized control. Therefore, the state of the work should be checked as follows. a) No earthing
• Group operation with different refrigerant systems One point earthing at outdoor unit
• Upper rank controller is used Earthing at the upper rank controller
b) Error is generated even though one point earth is being con-
nected. Earth shield at all outdoor units.
Connect to ground as shown in the user’s manual.
Checking for wiring method
Check for earthing
(b)When the wave height value of transmission wave shape is low, 6607 error is generated, or remote controller is
under the state of "HO."
8 The farthest distance of transmission
line is exceeding 200m.
9 The types of transmission lines are dif-
ferent.
; No transmission power (30 V) is being
supplied to the indoor unit or the remote control.
AFaulty indoor unit/remote controller
Confirm that the farthest distance from outdoor unit to indoor unit/remote controller is less than 200m.
Use the transmission wire specified.
Type of transmission line : Shield wire CVVS/CPEVS Wire dia.of transmission line: 1.25mm
2
or more
Refer to “Transmission Power Supply (30 V) Circuit Check Pro­cedure.”
Replace outdoor unit circuit board or remote controller.
Items to be checked Measures to be taken
-55-
Page 59
4) Treatment of Inverter and Compressor Troubles If the compressor does not work when error codes 4240 or 4250 are detected, determine the point of malfunction by following the steps in the appropriate sections on the pages starting from page 75, then perform the procedures below.
1 If it was kept on for 2 hours or longer
as specified
2 It was kept on for less than the
specified period.
1 The inverter stops and the same
error code is displayed.
1 The compressor stops and the same
error code is displayed.
2 If the inverter’s output voltage is
output with good balance,
1
3 If the balance in the inverter’s output
voltage is not good or if the inverter’s output voltages are all 0 V (a digital tester cannot be used)
1
No.
Check Item Symptoms Treatment
How many hours was the power kept on before operation?
When it is restarted, does the trouble reappear?
Run the outdoor unit with the wiring to the compressor disconnected. At this time, change SW1-1 on the INV board to ON. Note) The terminals of the 3
disconnected wires should be isolated from each other.
Go to [2].
Go to [2] after keeping the power on for the specified time.
Perform the check of wiring shown in the explanation of each error code.
Check the IPM is faulty. (Go to “Individual Parts Failure Judgment Methods.”)
Check the coil resistance and insulation resistance of the compressor, and if it is normal, run it again, and if the trouble occurs again, replace the compressor.
Insulation resistance : 1M or more Coil resistance : 0.11Ω(20˚C)
Check the IPM
1
2
3
1 [Cautions when measuring the voltage and current of the inverter’s power circuit.]
Since the voltage and current on the inverter’s power supply side and its output side do not have a sine waveform, the measurement values will differ depending on the measuring instrument and the circuit measured. In particular, as the inverter’s output voltage has a pulse waveform, the output frequency also changes, so differences in measurement values will be great depending on the measuring instrument. 1 When checking if the inverter’s output voltage is unbalanced or not (relative comparison of the voltages between each
of the lines), if you are testing with a portable tester, be sure to use an analog tester. Use a tester of a type which can be used to judge if the IPM or diode module is faulty. In particular, in cases where the inverter’s output frequency is low, there are cases where the variations in measured voltage values between the different wires will be great when a portable digital tester is used, when in actuality they are virtually equal, and there is danger of judging that the inverter is faulty.
2 It is recommended when checking the inverter’s output voltage values (when measuring absolute values), that, if a
measuring device for business frequencies is used, a rectified voltage meter (with a
symbol) be used.
Correct measurement values cannot be obtained with an ordinary portable tester. (either analog or digital)
Judge that the IPM is faulty. (Go to “Individual Parts Failure Judgment Methods.”) If the IPM is normal, replace the INV board, then perform this item again with SW1-1 ON. If the problem is solved and you connect the compressor again, turn SW1-1 OFF again. Check the compressor’s coil resistance and insulation resistance. If the problem is not solved, replace the INV board.
-56-
Page 60
5) Troubleshooting at breaker tripping
Check items 1 Check the breaker capacity. 2 Check the a short circuit or grounding in the electrical sys-
tem other than the inverter.
3 Check the resistance between terminals on the terminal
block TB1 for power source.
1 0 ~ several ohms or improper megohm value
4 Checking by powering again.
1 Main power source circuit breaker tripping
2 No display of remote controller
5 Operational check by operating air conditioner
1 Normal operation without breaker tripping.
2 Breaker tripping
Measures to be taken The breaker’s capacity should be proper. Correct any defects.
Check each part inside the inverter power circuit (re­sistance, megohm or the like). a) Diode stack
Refer to "Troubleshooting of diode stack."
b) IPM
Refer to "Troubleshooting of IPM." c) Rush current protection resistor d) Electromagnetic contactor e) DC reactor
For c) ~ e), refer to "Individual Parts Failure Judge-
ment Methods."
a) As there is a possibility of instantaneous short cir-
cuit generated, find the mark of the short circuit for
repair. b) When a) is not applicable, the compressor may be
faulty. The ground fault of inverter output/compressor can be
supposed. Disconnect the wiring to the compressor and check the insulation resistance of the following parts with a megger. a) Compressor terminals. b) Inverter output.
-57-
Page 61
6) Individual Parts Failure Judgment Methods.
[Caution at replacement of inverter parts]
1 The IPM and G/A board should be replaced together at the same time.
2 Fully check wiring for incorrect and loose connection.
3 Coat the grease for radiation provided uniformly onto the radiation surface of IPM/diode modules.
Coat the grease for radiation on the full surface in a thin layer, and fix the module securely with the screw for fastening. As the radiation grease attached on the wiring terminal causes poor contact, wipe it off if attached.
Part Name Judgment Method Diode Stack (DS) Refer to Judging Diode Stack Failure. (P49) Intelligent Power Module (IPM) Refer to Judging IPM Failure. (P49) Electromagnetic Contactor (52C) Measure the resistance value at each terminal.
DC Reactor (DCL) Measure the resistance between terminals: 1 or lower
Measure the resistance between the terminals and the chassis:
Cooling Fan (MF1) Measure the resistance between terminals: 0.1K~1.5K POWER board Measure the resistance valve at between each terminal, and between
each terminal and case.
Check Location Judgment Value
0-1 50~100k
2-4 6-8
10-12 14-16
Check Location Judgment Value
FN 3-6, FN 2-4
FN 1-2, FN 2-3,
FN4-6
FN1, FN2, FN3,
FN4, FN6-Case
Under 1
∞ ∞
When the IPM is damaged, the G/A board may possibly be broken, and the use of the broken G/A board damages the normal IPM. Therefore, replace the IPM and G/A board together at the same time. However, if the G/A board is damaged, judge that the IPM is faulty, then judge whether replacement is necessary or not
The incorrect or loose connection of the power circuit part wiring like IPM and diode module causes to damage the IPM. Therefore, check the wiring fully. As the insufficient tightening of screws is difficult to find, tighten them together additionally after finishing other works. For the wiring of the base for IPM, observe the wiring diagram below carefully as it has many terminals.
-58-
Page 62
Model PUHY-80TMU-A, 100TMU-A
To compressor
Red White Blue
Blue
Red
To capacitor (C1)
board
-59-
Page 63
Check Code List
Check Code Check Content
0403 Serial transmission trouble 0900 Trial operation 1102 Discharge temperature trouble 1111 Low pressure saturation temperature sensor trouble (TH2) 1302 High pressure trouble 1500 Refrigerant volume charge trouble 1505 Suction pressure trouble 2500 Leakage (water) trouble 2502 Drain pump trouble 2503 Drain sensor trouble 4102 Lacking power source error 4103 Reverse phase error/Lacking power source error 4115 Power supply sync signal trouble 4116 Fan speed trouble (motor trouble) 4200 VDC sensor/circuit trouble 4220 Bus voltage trouble 4230 Radiator panel overheat protection 4240 4250 [1]
[11]
[6]
[13]
Overcurrent protectio IPM Alarm output/Bus voltage abnormality
IAC sensor overcurrent abnormality
IAC sensor circuit/abnormality IAC sensor miss-wiring abnormality
n
4260 Cooling fan trouble
Air inlet (TH21:IC)
5101
Discharge (TH1:OC) Liquid pipe (TH22:IC)
5102
Low pressure saturation (TH2:OC)
5103
Gas pipe (TH23:IC)Thermal sensor 5105 trouble Liquid pipe (TH5) 5106 Ambient temperature (TH6) 5107 SC coil outlet (TH7) 5108 SC coil bypass outlet (TH8) 5110 Radiator panel (THHS) 5201 Pressure sensor trouble 5301
6600 Multiple address error 6602 Transmission processor hardware error 6603 Transmission circuit bus-busy error 6606 Communications with transmission processor error 6607 No ACK error 6608 No response error 7100 Total capacity error 7101 Capacity code error
-60-
Page 64
Check Code Check Content
6606 Communications with transmission processor abnormality 6607 No ACK abnormality 6608 No response abnormality 6831 MA communication, No-reception error 6832 MA communication, Synchronization recovery error 6833 MA communication, Transmission/reception handware error 6834 MA communication, Start bit error 7100 Total capacity abnormality 7101 Capacity code abnormality 7102 Connected unit count over 7105 Address setting abnormality 7106 Characteristics setting abnormality 7111 Remote control sensor abnormality
Intermittent fault check code
Trouble Delay Cope Trouble Delay Content
1202 (1102)
Preliminary discharge temperature abnormality or preliminary discharge thermal sensor abnormality (TH1) 1205 Preliminary liquid pipe temperature sensor abnormality (TH5) 1211 (1111)
Preliminary low pressure saturation abnormality or preliminary low pressure saturation sensor abnormality (TH2)
1214 Preliminary THHS sensor/circuit abnormality 1216 Preliminary sub-cool coil outlet thermal sensor abnormality (TH7) 1217 Preliminary sub-cool coil bypass outlet thermal sensor abnormality (TH8) 1221 Preliminary ambient temperature thermal sensor abnormality (TH6) 1402 (1302) Preliminary high pressure abnormality or preliminary pressure sensor abnormality
1601
Preliminary 1600 (1500) Preliminary lacked refrigerant abnormality
overcharged refrigerant abnormality
1605 (1505) Preliminary suction pressure abnormality
Preliminary serial transmission abnormality
4300 (5301) [6]
[9]
[13]
[1]
[11]
4300 (0403)
IAC sensor/circuit abnormality IAC sensor miss-wiring abnormality
4320 (4220) Preliminary bus voltage abnormality
4310 Preliminary overcurrent breaking trouble
4330 (4230) Preliminary heat sink overheating abnormality 4340 (4240) Preliminary overload protection
4350 (4250) IPM Alarm output/Bus voltage abnormality
IAC sensor overcurrent abnormality
4360 (4260)
Please refer to ( ) : Check Code. [ ] : Error detail No.
Preliminary cooling fan abnormality
-61-
Page 65
(1) Mechanical
Checking code Meaning, detecting method Cause Checking method & Countermeasure
Serial transmission trouble
Discharge temperature trouble
(
Outdoor unit
)
If serial transmission cannot be established between the MAIN and INV boards
1. When 140°C or more dis­charge temperature is de­tected during op-erations (the first time), outdoor unit stops once, mode is changed to restart mode af­ter 3 minutes, then the out­door unit restarts.
2. When 140°C or more temp. is detected again (the sec­ond time) within 30 minutes after stop of outdoor unit, er­ror stop is observed with code No. "1102" displayed.
3. When 140°C or more temp. is detected 30 or more min­utes after stop of outdoor unit, the stop is regarded as the first time and the process shown in 1 is observed.
4. 30 minutes after stop of out-
door unit is intermittent fault check period with LED dis­played(1202).
Check 1, the connections, 2, contact at the connectors and 3, for broken wires in the following wiring.
CNRS2 - CNRS3 CNAC2 - TB1A
SW1-4 on the INV board should be OFF.
If the fuse is melted, (if the resis­tance between the both ends of fuse is ∞), replace the fuse.
If none of the items in 1) to 3) is ap­plicable, and if the trouble reappears even after the power is switched on again, replace the circuit board by the following procedure (when re­placing the circuit board, be sure to connect all the connectors, ground wires, etc. securely). 1 If serial transmission is restored
after the INV board only is re­placed, then the INV board is de­fective.
2 If serial transmission is not re-
stored, reinstall the INV board and replace the MAIN board. If serial transmission is restored, the MAIN board is defective.
3 If serial transmission is not re-
stored by 1 and 2 above, re-
place both boards. See Refrigerant amount check. Check operating conditions and op-
eration status of indoor/outdoor units.
Check operation status by actually performing cooling or heating opera­tions.
Cooling : Indoor LEV
LEV1
Heating : Indoor LEV
See Trouble check of LEV and so- lenoid valve.
Confirm that ball valve is fully opened.
Check outdoor fan. See Trouble check of outdoor fan.
Check operation status of cooling or heating.
See Trouble check of solenoid valve.
Check resistance of thermistor Check inlet temperature of sensor
with LED monitor.
0403
1102
1) Wiring is defective.
2) Switches are set wrong on the INV board.
3) A fuse (F01) on the INV board is defective.
4) The circuit board is defective.
1) Gas leak, gas shortage
2) Overload operations
3) Poor operations of indoor LEV
4) Poor operations of OC controller
LEV
Cooling : LEV1
5) Poor operations of ball valve
6) Outdoor unit fan block, motor
trouble, poor operations of fan controllerHeating
3) ~ 6) : Rise in discharge temp. by low pressure drawing
7) Gas leak between low and high
pressures 4-way valve trouble, compressor trouble, solenoid valve SV1 trouble
8) Poor operations of solenoid valve
SV2 Bypass valve SV2 can not control rise in discharge temp.
9
) Thermistor trouble
10
)Thermistor input circuit trouble on
control circuit board
[2] Self-diagnosis and Countermeasures Depending on the Check Code Displayed
-62-
Page 66
Checking code Meaning, detecting method Cause Checking method & Countermeasure
1.
2. When –40°C or less temp. is detected again (the second time) within 30 minutes after stop of outdoor unit, error stop is observed with code Nos. "1111" or displayed.
3. When –40°C or less tem­perature is detected 30 or more minutes after stop of outdoor unit, the stop is re­garded as the first time and the process shown in 1. is observed.
4. 30 minutes after stop of out­door unit is intermittent fault check period with LED dis­played.
Note:
1. Low press. saturation tem­perature trouble is not de­tected for 3 minutes after compressor start, and fin­ish of defrosting opera­tions, and during defrost­ing operations.
2.In the case of short/open of TH2 sensors before starting of compressor or within 10 minutes after starting of compressor, "1111" is displayed too.
Low pressure satura­tion tempera­ture sensor trouble (TH2)
1111 See Refrigerant amount check.
Check operating conditions andop­eration status of outdoor unit.
Check operation status by actually performing cooling or heating opera­tions.
Cooling : indoor LEV
LEV1
Heating : indoor LEV
See Trouble check of LEV and so- lenoid valve.
Confirm that ball valve is fully opened.
Check indoor unit, and take measu­res to troube
Check outdoor unit, and take mea­sures to trouble
Check outdoor unit fan. See Trouble check of outdoor unit fan.
See Trouble check of solenoid valve.
Check resistance of thermistor
See Trouble check of pressure sensor.
Check inlet temp. and press. of sen­sor by LED monitor.
Low pressure saturation temperature trouble
1) Gas leak, Gas shortage
2) Insufficient load operations
3) Poor operations of indoor LEV
4) Poor operations of OC controller LEV1.
Cooling : LEV1
5) Poor operations of ball valve
6) Short cycle of indoor unit
7) Clogging of indoor unit filter
8) Fall in air volume caused by dust on indoor unit fan
9
) Dust on indoor unit heat exchanger
10
)Indoor unit block, Motor trouble
5)~10) : Fall in low press. caused by lowered evaporating capacity in cooling operation.
11
)Short cycle of outdoor unit
12
)Dust on outdoor heat exchanger
13
)Indoor unit fan block, motor trouble,
and poor operations of fan control­ler
10)~12) : Fall in low press. caus­ed by lowered evaporating capa­city in heating operation.
14
)Poor operations of solenoid valve
SV2 Bypass valve (SV2) can not control low pressure drop.
15
)Thermistor trouble (TH2~TH6)
16
)Pressure sensor trouble
17
)Control circuit board thermistor
trouble and pressure sensor input circuit trouble
18
)Poor mounting of thermistor
(TH2~TH6)
When saturation tempera­ture sensor (TH2) detects –40°C or less (the first time) during operations, out­door unit stops once, mode is changed to restart mode after 3 minutes, then the outdoor unit restarts.
-63-
Page 67
–1.5
Checking code Meaning, detecting method Cause Checking method & Countermeasure
Check operations status by actually performing cooling or heating opera­tions.
Cooling : Indoor LEV
LEV1
Heating : Indoor LEV
See Trouble check of LEV and so- lenoid valve.
Confirm that ball valve is fully open­ed.
Check indoor unit and take mea­sures to trouble.
Check outdoor unit and take mea­sures to trouble.
Check outdoor unit fan See Trouble check of outdoor unit
fan.
See Trouble check of solenoid valve.
Check resistance of thermistor.
Check Trouble check of pressure sensor.
1. When press. sensor detects 28kg/cm
2
or more during op­erations (the first time), out­door unit stops once, mode is changed to restart mode after 3 minutes, then the out­door unit restarts.
2. When 30kg/cm
2
or more pres- sure is detected again (the second time) within 30 minutes after stop of outdoor unit,error stop is observed with code No. "1302" dis­played.
3. When 28kg/cm2 or more pres-sure is detected 30 or more minutes after stop of outdoor unit, the detection is regarded as the first time and the process shown in 1 is observed.
4. 30 minutes after stop of out­door unit is intermittent fault check period with LED dis­played.
5. Error stop is observed imme­diately when press. switch (30
+ 0
kg/cm2) operates in
addition to pressure sensor.
1302
High pressure trouble 1 (Outdoor unit)
1) Poor operations of indoor LEV
2) Poor operations of ball valve
3) Short cycle of indoor unit 4
) Clogging of indoor unit filter
5) Fall in air volume caused by dust on indoor unit fan
6) Dust on indoor unit heat exchanger
7) Indoor unit fan block, motor trouble
2)~7) : Rise in high pressure caused by lowered condensing capacity in heating operation
8) Short cycle of outdoor unit
9
) Dust on outdoor unit heat ex-
changer
10
) Outdoor unit fan block, motor trou-
ble, poor operations of fan control­ler
8)~10) : Rise in high press. caus­ed by lowered condensing capa­city in cooling operation
11
)Poor operations of solenoid valves
SV1, 2 (Bypass valves (SV1, 2) can not control rise in high pressure)
12
)Thermistor trouble (TH2, TH5, TH6)
13
) Pressure sensor trouble
-64-
Page 68
Checking code Meaning, detecting method Cause Checking method & Countermeasure
Check inlet temperature and press. of sensor with LED monitor.
See Trouble check of pressure sensor.
Once vacuum operation protection is commenced, do not attempt to re­start until taking the measures be­low. <Checking method>
Check ball valve for neglecting to open.
Check extended piping for clog­ging when ball valve is opened.
Check transmission line for erro­neous wiring. (Confirm the cor­rect wiring and piping connection between indoor and outdoor units by operating indoor unit one by one.)
<Countermeasure>
After checking with the above method, make error reset by power source reset.
Then operate for 10~15-minutes under the operation mode re­verse to that when the vacuum operation protection occurred (Heating if error occurred in cool­ing, while cooling if it occurred in heating), and then enter into the ordinary operation state.
When press. sensor detects 1kg/cm
2
or less just before starting of operation, erro stop is observed with code No. "1302" displayed.
<Condition 1>
1. Judging that the state when
the suction pressure reaches 0kg/cm2G during compres­sor operation indicates high pressure by the discharge temperature and low pres­sure saturation temperature, the back-up control by gas bypassing will be conducted.
2. The outdoor unit once stops
entering into the 3-minutes restart mode if the state of 1 continues for 3 minutes, and restarts after 3 minutes.
3. After restarting, if the same
state as 1 continues within 30 minutes from the stopping of 2, error stop will be com­menced displaying 1505.
4. Ineffective if the compressor
operating time (integrated) exceeds 60-minutes not de­tecting trouble.
High pressure trouble 1 (Outdoor unit)
High pressure trouble 2 (Outdoor unit)
Suction pressure trouble
16
)Control circuit board thermistor
trouble, press. sensor input cir­cuit trouble
17
)Poor mounting of thermistor
(TH2, TH5, H6)
18)Coming loose the connecter of pressure switch or cut of the wire.
1) Fall in internal press. caused by gas leak
2) Press. sensor trouble
3) Film breakage
4) Coming off of pin in connector portion, poor contact
5) Broken wire
6) Press. sensor input circuit trouble on control circuit board
Operation while neglecting to open ball valve. Especially for the ball valve at low pressure side. At cooling : Gas side ball valve At heating : Liquid side ball valve
When plural systems are existing, the low pressure abruptly drop at indoor stopping by the erroneous wiring of transmission line (differ­ent connection of transmission line and refrigerant piping).
Temporary vacuum condition due to refrigerant distribution unbal­ance (insufficient refrigerant of low pressure line) immediately af­ter charging refrigerant.
1302
1505
1500
1.
2.
3.
4.
5.
Overcharged refrigerant abnormality
1) Excessive refrigerant charge.
2)
Main circuit board thermistor input circuit trouble
Thermistor mounting trouble (TH1, TH2)
3)
Refer to the section on judging the refrigerant volume.
Check the sensor detection temperature and pressure with the LED monitor.
If the discharge SH
<
=
10K is detected during operation (at first detection), the outdoor unit stops at once. The 3­minute restart prevention mode is entered. After three minutes, the outdoor unit starts up again.
If the discharge SH
<
=
10K is detected again within 30 minutes after the outdoor unit stops (second detection), an abnormal stop is applied, and "1500" is displayed.
If discharge SH
<
=
10K is detected more than 30 minutes after the outdoor unit stops, the state is the same as the first detection and the same operation as 1 above takes place.
The abnormal stop delay period is in effect for 30 minutes after the outdoor unit stops. The abnormal stop delay period LED turns ON during this time.
If the abnormality detection prohibit switch (SW2-4) is ON, the same operation as the first detection will apply for the second and following detections.
-65-
Page 69
Checking code Meaning, detecting method Cause Checking method & Countermeasure
Leakage (water) trouble
Drain pump trouble
Drain sensor trouble
Water leak trouble
Water suspension trouble
Operation of float switch
Check water leaking of humidifier and clogging of drain pan.
Check operations of drain pump.
Measure resistance of indirect heater of drain sensor. (Normal: Approx. 82 between 1–3 of CN50)
Indoor board trouble if no other problems is detected. Operate in fan mode checking to make sure that the temperature of TH2 and TH3 rise to the around the same level.
Check resistance of thermistor
0°C:15k 10°C : 9.7kΩ 20°C : 6.4kΩ 30°C : 4.3k 40°C : 3.1kΩ
Check contact of connector Indoor port trouble if no other prob­lem is detected.
Confirm water leaking section.
Confirm supply water volume. Solenoid valve and connection Confirm connector section.
Confirm connecting section. Faulty float switch.
Turn power source OFF once, and turn ON after thawaing.
Check drain pump operations Check connect contact. Check float switch operations.
2500
2502
2503
2600
2601
1) Water leak due to humidifier or the like in trouble.
1) Drain sensor sinks in water be-
cause drain water level rises due to drain water lifting-up mechanism trouble.
2) Broken wire of indirect heater of
drain sensor
3) Detecting circuit (circuit board)
trouble Indoor LEV operation is faulty.
4) The trable of indoor LEV
1) Thermistor trouble
2) Poor contact of connector
(insufficient insertion)
3) Full-broken of half-broken ther-
mistor wire
4) Indoor unit circuit board (detecting
circuit) trouble
Water leak from piping of humidifier
1) Water is not supplied to water tank
for humidifying.
2) The solenoid valve for humidifying
is set to OFF.
3) Disconnection of float switch.
4) Faulty operation of float switch.
5) Freezing of water tank.
1) Drain up input trouble
2) Poor contact of float switch circuit
3) Float switch trouble
When drain sensor detects flooding during drain pump OFF.
The drain sensor's water drain* and after the drain pump is turn on for more than three minuites.
Drain sensor's water drain
condition when indirect heater of drain after 40 second's.
Rise in temperature of drain sensor is 20 deg or less or
The temperature of the drain sensor is 63°C or less.
Short/open is detected during drain pump operations. (Not de­tected when drain pump is not operating.) Short : 90°C or more detected Open : –40°C or less de­tected
When Float switch operates (point of contact : OFF), error stop is observed with code No. "2503" displayed.
-66-
Page 70
Checking code Meaning, detecting method Cause Checking method & Countermeasure
Open phase error
Reverse phase error
Check before the breaker, after the breaker or at the power supply ter­minal blocks TB1, and if there is an open phase, correct the connec­tions.
a) Check if a wire is disconnected. b) Check the voltage between
each of the wires.
Check 1 the connections, 2, the con­tact at the connector, 3, the tighten­ing torque at screw tightening loca­tions and 4 for wiring disconnec­tions. TB1~EN20 Refer to the circuit number and the wiring diagram plate.
If F1, F2 or F3 on the MAIN board is melted, (Resistance between both ends of the fuse is ), replace the fuses.
If none of the items in 1) to 4) is ap­plicable, and if the trouble reappears even after the power is switched on again, replace the MAIN board (when replacing the circuit board, be sure to connect all the connectors, etc. securely).
If there is reverse phase before the breaker, after the breaker or at the power supply terminal blocks TB1, reconnect the wiring.
Check before the breaker, after the breaker or at the power supply ter­minal blocks TB1, and if there is an open phase, correct the connec­tions.
a) Check if a wire is disconnected. b) Check the voltage between
each of the wires.
Check 1 the connections, 2, the con­tact at the connector, 3, the tighten­ing torque at screw tightening loca­tions and 4 for wiring disconnec­tions. TB1~EN20 Refer to the circuit number and the wiring diagram plate.
If F1 or F2 or F3 on the MAIN board is melted, (Resistance between both ends of the fuse is ), replace the fuses.
If none of the items in 1) to 4) is ap­plicable, and if the trouble reappears even after the power is switched on again, replace the MAIN board (when replacing the circuit board, be sure to connect all the connectors, etc. securely).
4102
4103
1) Open phase has occurred in the power supply (R, S, T).
2) The wiring is faulty.
3) The fuse is faulty.
4) The circuit board is faulty.
1) The phases of the power supply (R, S, T) have been reversed.
2) Open phase has occurred in the power supply (R, S, T).
3) The wiring is faulty.
4) The fuse is faulty.
5) The circuit board is faulty.
Open phase in the power sys­tem is being detected, so op­eration cannot be started.
Reverse phase (or open phase) in the power system is being detected, so operation cannot be started.
-67-
Page 71
Checking code Meaning, detecting method Cause Checking method & Countermeasure
Power supply sync signal trouble
Fan speed trouble (motor trouble)
Check before the breaker, after the breaker or at the power supply ter­minal blocks TB1 or TB1A, and if there is an open phase, correct the connections.
If the power supply voltage wave­form is distorted from a sine wave, improve the power supply environ­ment.
If F1, F2 or F3 on the MAIN board, or F3 is melted, (Resistance between both ends of the fuse is ), replace the fuses.
If none of the items in 1) to 3) is ap­plicable, and if the trouble reap­pears even after the power is switched on again, replace the MAIN board (when replacing the cir­cuit board, be sure to connect all the connectors, ground wires, etc. se­curely).
Confirm slipping off of connector (CN33) on indoor controller board.
Confirm slipping off of connector (FAN1) on indoor power board.
Check wiring for disconnection.
Check filter.
Check indoor fan motor.
When aboves have no trouble.
1) For trouble after operating fan. Replace indoor controller board. If not remedied, replace indoor power board.
2) For trouble without operating fan. Replace indoor power board.
4115
4116
1) There is an open phase in the power supply (R, S, T)
2) The power supply voltage is dis­torted.
3) A fuse is defective.
4) The circuit board is defective.
1) Slipping off of fan speed detecting connector (CN33) of indoor control­ler board
2) Slipping off of fan output connector (FAN1) of indoor power board
3) Disconnection of fan speed detect­ing connector (CN33) of indoor controller board, or that of fan out­put connector (FAN1) of indoor powr board.
4) Filter cologging
5) Trouble of indoor fan motor
6) Faulty fan speed detecting circuit of indoor controller board, or faulty fan output circuit of indoor power board.
The frequency cannot be deter­mined when the power is switched on. (The power supplys frequency cannot be detected. The out­door fan cannot be controlled by phase control.)
(Detects only for PKFY-NAM)
1. Detecting fan speed below 180rpm or over 2000rpm during fan operation at in­door unit (first detection) en­ters into the 3-minute restart prevention mode to stop fan for 30 seconds.
2. When detecting fan speed below 180rpm or over 2000rpm again at fan return­ing after 30 seconsd from fan stopping, error stop (fan also stops) will be com­menced displaying 4116.
-68-
Page 72
Checking code Meaning, detecting method Cause Checking method & Countermeasure
1 If VDC 150 V is detected
just before the inverter starts.
2 If VDC 400 V is detected
just before the inverter starts.
3 If the voltage of the INV
board’s sensor circuit input is what it should not normally be.
VDCsensor/ circuit trouble
4200 • Check if an instantaneous power
failure or power failure, etc. has oc­curred.
• Check if the voltage is the rated voltage value.
Check 1, the connections, 2, contact at the connectors, 3 tightening torque at screw tightened portions, 4, wiring polarities, 5, for broken wires, and 6, for grounding in the fol­lowing wiring.
TB1 ~ DS ~ POWER Board ~ 52C ~ R1 ~ DCL~C1 ~ IPM ~ G/A Board (F1) ~ CNDC1 ~ CNDC2 wiring
Check if the wiring polarities are as shown on the electric wiring dia­gram plate.
To judge failure of R1, go to “Indi­vidual Parts Failure Judgment Meth­ods.”
To judge failure of the 52C, go to “Individual Parts Failure Judgment Methods.”
To judge failure of the DS, go to “In­dividual Parts Failure Judgment Methods.”
To judge failure of the DCL, go to “Individual Parts Failure Judgment Methods.”
If none of the items in 1) to 6) is ap­plicable, and if the trouble reappears even after the power is switched on again, replace the INV board, (when replacing the circuit board, be sure to connect all the connectors, etc. securely)
1) Power supply voltage is abnormal.
2) The wiring is defective.
3) The rush current prevention resis­tors (R1) are defective.
4) The electromagnetic contactor (52C) is defective.
5) The diode stack (DS) is defective.
6) The reactor (DCL) is defective.
7) The INV board is defective.
-69-
Page 73
Checking code Meaning, detecting method Cause Checking method & Countermeasure
If VDC
220 V is detected dur-
ing inverter operation.
If the cooling fan stays ON for 5 minutes or longer during in­verter operation, and if THHS
92°C is detected.
Bus voltage trouble
Radiator panel overheat protection
4220
4230
Check if an instantaneous stop or power failure, etc. has occurred.
Check if the voltage is the rated voltage value.
Check 1, the connections, 2, contact at the connectors, 3 tightening torque at screw tightened portions, 4, wiring polarities, 5, for broken wires, and 6, for grounding in the fol­lowing wiring.
TB1 ~ DS ~ Power Board ~ 52C ~ R1 ~ DCL ~ C1 ~IPM ~ G/A Board (F1) ~ CNDC1 ~ CNDC2 Wiring CN15V1 ~ CN15V2 Wiring CNDR1 ~ CNDR2 Wiring
Check if the wiring polarities are as
shown on the wiring diagram plate.
To judge failure of R1, go to Individual Parts Failure Judgment Methods.
To judge failure of the 52C, go to Individual Parts Failure Judgment Methods.
To judge failure of the DS, go to In­dividual Parts Failure Judgment Methods.
To judge failure of the DCL, go to Individual Parts Failure Judgment Methods.
Check the wiring between the IPM and the compressor.
Check the compressors insulation resistance.
Check the capacity of C1. (If C1
<
=
3700 µF is defective)
If none of the items in 1) to 8) is ap­plicable, and if the trouble reappears even after the power is switched on again, replace the INV board (when replacing the circuit board, be sure to connect all the connectors, ground wires, etc. securely).
Check 1 connections, 2 contact at the connectors and 3 for broken wires in the following wiring.
MF1~CNFAN
If the fuse is defective, replace the fuse.
To judge failure of the MF1, go to Individual Parts Failure Judgment Methods.
To judge failure of the THHS, go to error code 5110.
If the air passage of the heat sink is clogged, clear the air passage.
If none of the items in 1) to 5) is ap­plicable, and if the trouble reappears even after the power is switched on again, replace the INV board (when replacing the circuit board, be sure to connect all the connectors, ground wires, etc. securely).
1) The power supply voltage is abnor­mal.
2) The wiring is defective.
3) The rush current prevention resis­tors (R1) are defective.
4) The electromagnetic contactor (52C) is defective.
5) The diode stack (DS) is defective.
6) The reactor (DCL) is defective.
7) The inverter output is grounded.
8) The capacitor (C1) is defective
9) The circuit board is defective.
1) The wiring is defective.
2) The INV board fuse (F01) is defec­tive.
3) The cooling fan (MF1) is defective.
4) The THHS sensor is defective.
5) The air passage is clogged.
6) The INV board is defective.
-70-
Page 74
Checking code Meaning, detecting method Cause Checking method & Countermeasure
If IDC 103 A is detected con­tinuously for 10 minutes during operation of the inverter after 5 or more seconds have passed since the inverter started.
1) IPM/VDC trouble
2) If IDC
200 A is detected
during inverter operation.
3) If VDC
350V or VDC 190V is detected during in­verter operates.
Overcurrent protection
Breaking of overcurrent
4240
4250
Is the units exhaust short cycling? Clean the heat exchanger. If the power supply voltage is less
than 198 V, it is outside specifications. If the external air temperature is
over than 43°C it is outside the specifications.
Is the indoor unit capacity total ap­propriate?
Are the outdoor/indoor unit capac­ity settings appropriate?
To judge failure of the THHS, go to the item for error code 5110.
To judge failure of the solenoid valve, go to Individual Parts Failure Judgment Methods for the Solenoid Valve.
Check 1 connections, 2 contact at the connectors and 3 for broken wires in the following wiring.
CNFAN1~MF1
Go to Treating Fan Motor Related Trouble.
Go to Treating Inverter/Compressor Related Trouble.
If none of the items in 1) to 10) is appli­cable, and if the trouble reappears even after the power is switched on again, re­place the MAIN board (when replacing the circuit board, be sure to connect all the connectors, ground wires, etc. se­curely).
Go to the item for error code 4230,
4240.
Check if an instantaneous power failure or power failure, etc. has oc­curred.
Check if the voltage is the rated voltage value.
Check 1, the connections, 2, contact at the connectors, 3 tightening torque at screw tightened portions, 4, wiring polarities, 5, for broken wires, and 6, for grounding in the fol­lowing wiring.
Check if the wiring polarities are as
shown on the wiring diagram plate.
Check the coil resistances and in­sulation resistance of the com­pressor.
Go to "Treatment of Inverter/Com­pressor Releated Trouble."
Go to the item for error code 4220.
1) Air passage Short Cycle
2) The heat exchanger is clogged.
3) Power Supply Voltage
4) External Air Temperature
5) Capacity Setting Error
6) The THHS sensor is defective.
7) The solenoid valves (SV1, 2) are defective, or the solenoid valve drive circuit is defective.
8) The wiring is defective.
9) Fan motor (MF) operation is defec­tive.
10)The inverter/compressor is defec-
tive.
11)The circuit board is defective.
1) Self protection by IPM break out, (over current, over heat, under con­trol voltage)
1) The power supply voltage is abnor­mal.
2) The wiring is defective.
3) The inverter/compressor is defec­tive.
(the same as error code 4220)
-71-
Page 75
Checking code Meaning, detecting method Cause Checking method & Countermeasure
If the heat sink temperature (THHS)
60°C for 10 minutes or longer just before the inverter starts.
If a heat sink temperature of (THHS) 40°C is detected just before starting of, and during operation of the inverter.
If IDC 20 A is detected just
before the inverter starts, or
If IDC 10 A is detected dur-
ing inverter operation after 5 seconds has passed since the inverter started when the INV boards SW1-1 is OFF.
Cooling fan trouble
Radiator panel
IDC sensor/ circuit trouble
4260
5110
5301
Same as 4230.
Judge that the THHS has failed. Go to error code 5110.
Check the contacts of CNTH on the INV board.
If none of the items in 1) to 2) is ap­plicable, and if the trouble reap­pears even after the power is switched on again, replace the INV board (when replacing the circuit board, be sure to connect all the connectors, ground wires, etc. se­curely).
Check the contacts of CNCT on the INV board.
Check the DCCT polarity.
With SW1-1 OFF, is the inverters output wiring open?
With SW1-1 OFF, is a compressor which is not specified for this model connected to the inverters output?
If none of the items in 1) to 3) is ap­plicable, and if the trouble reap­pears even after the power is switched on again, replace the INV board and the DCCT (when replac­ing the circuit board, be sure to con­nect all the connectors, ground wires, etc. securely) by the following procedure. 1 Replace the INV board only. If it
recovers, the INV board is defec­tive.
2 If it does not recover, reinstall the
INV board and replace the DCCT. If it recovers, the DCCT is defec-
tive. If it does not recover after 1 and 2 above, both the INV board and the DCCT are defective.
1) Same as “4230.”
1) The THHS Sensor is defective.
2) Contact is faulty.
3) The INV board is defective.
1) Contact is faulty.
2) The current sensor (DCCT) is con­nected with reverse polarity.
3) An error was made in the SW1-1 setting.
4) The INV board is defective. The current sensor (DCCT) is defective.
-72-
Page 76
Checking code Meaning, detecting method Cause Checking method & Countermeasure
<Other than THHS> 1 A short in the thermistor or
an open circuit was sensed. The outdoor unit switches to the temporary stop mode with restarting after 3 min­utes, then if the temperature detected by the thermistor just before restarting is in the normal range, restarting takes place.
2 If a short or open circuit in
the thermistor is detected just before restarting, error code 5101, 5102, 5105”,
5106, "5107", 5108 or5109 i s d i s played.
3 In the 3 minute restart mode,
the abnormal stop delay LED is displayed.
4 The above short or open cir-
cuit is not detected for 10 minutes after the compres­sor starts, or for 3 minutes during defrosting or after re-
covery following defrosting. <THHS> If a heat sink (THHS) tempera­ture of
-40°C is detected just after the inverter starts or during inverter operation.
1 When pressue sensor de-
tects 1kg/cm2 or less during operation, outdoor unit once stops with 3 minutes restart­ing mode, and restarts if the detected pressure of pres­sure sensor exceeds 1kg/ cm
2
imediately before re-
starting.
2 If the detected pressure of
sensor is less than 1kg/cm
2
immediately before restart­ing, error stop is com­menced displaying 5201.
3 Under 3 minutes restarting
mode, LED displays inter­mittent fault check.
4 During 3 minutes after com-
pressor start, defrosting and 3 minutes after defrosting operations, trouble detec­tion is ignored.
Discharge (TH1)
Low pressure saturation (TH2)
Liquid pipe (TH5)
Ambient tempera­ture (TH6)
SC coil outlet (TH7)
SC coil bypass outlet (TH8)
Radiator panel (THHS)
Pressure sensor trouble
5101
5102
5105
5106
5107
5108
5110
5201
Check the thermistors resistance. Check if the lead wires are pinched. Check for tearing of the insulation. Check if a pin is missing on the con-
nector. Check if a wire is disconnected. Check the temperature picked up by
the sensor using the LED monitor. If the deviation from the actual tem­perature is great, replace the MAIN circuit board. (In the case of the THHS, replace the INV board.)
1) Thermistor
2) Lead wires are being pinched.
3) Insulation is torn.
4) A connector pin is missing, or there is faulty contact.
5) A wire is disconnected.
6) The thermistor input circuit on the MAIN circuit board is faulty. (In the case of the THHS, replace the INV board.)
Thermal Sensor Error, Outdoor Unit
Short Circuit Detection Open Circuit Detection
TH1 240°C or higher (0.57 k)15°C or lower (321 kΩ) TH2 70°C or higher (1.71 kΩ) -40°C or lower (399 kΩ) TH3 70°C or higher (1.14 kΩ) -40°C or lower (130 kΩ) TH4 70°C or higher (1.14 kΩ) -40°C or lower (130 kΩ) TH5 110°C or higher (0.4 k) -40°C or lower (130 k) TH6 110°C or higher (0.4 k) -40°C or lower (130 k) TH7 70°C or higher (1.14 kΩ) -40°C or lower (130 kΩ) TH8 110°C or higher (0.4 k) -40°C or lower (130 k) THHS 100°C or higher (3.0 k)-40°C or lower (2.5 kΩ)
1) Pressutre sensor trouble.
2) Inner pressure drop due to a leak-
age
3) Broken cover.
4) Coming off of pin at connector por-
tion, poor contact.
5) Broken wire
6) Faulty thermistor input circuit of
MAIN board.
See Troubleshooting of pressure
sensor.
-73-
Page 77
Checking
code
Meaning, detecting method Cause Checking method & Countermeasure
6600
6602
Multiple address error
Transmission from units with the same address is detected.
Note:
The address/attribute shown on remote con­troller indica tes the con­troller which has de­tected error.
At the genration of 6600 error, release the error by remote controller (with stop key) and start again. a) If the error occures again within 5 minutes
Search for the unit which has the same ad-
dress with that of the source of the trouble.
When the same address is found, turn off the power source of outdoor unit, and in­door unit for 5 minutes or more after modify­ing the address, and then turn on it again.
b) When no trouble is generated even continuing
operation over 5 minutes
The transmission wave shape/noise on the
transmission line should be investigated in accordance with <Investigation method of transmission wave shape/noise>.
1) Two or more controllers of out­door unit, indoor unit, remote con­troller, etc. have the same ad­dress.
2) In the case that signal has changed due to noise entered into the transmission signal.
(2) Communication/system
Transmission processor hardware error
Though transmission proces­sor intends to transmit "0", "1" is displayed on transmission line.
Note:
The address/attribute shown on remote con­troller indicates the con­trol
ler which has detected
error.
1) At the collision of mutual transmission data generated during the wiring work or polarity change of the transmission line of indoor or outdoor unit while turning the power source on, the wave shape is changed and the error is detected.
2) 100V power source connection to indoor unit.
3) Ground fault of transmission line.
4) Insertion of power supply connector (CN40) of plural outdoor units at the grouping of plural refrigerant systems.
5) Insertion of power supply connector (CN40) of plural outdoor units in the connection system with MELANS.
6) Faulty controller of unit in trouble.
7) Change of transmission data due to the noise in transmission.
8) Connection system with plural refrigerant systems or MELANS for which voltage is not applied on the transmission line for central control.
-74-
Page 78
6602
Faulty controller of generating unit
YES
YES
Erroneous power source work
Erroneous transmission work
NO
NO
YES
NO
NO
NO
YES
YES
YES
Transmission line
installed while turning
power source on?
Shut off the power source of outdoor/in­door units/BC controller and make it again.
Check power source of in­door unit.
187V ~ 253V?
Check transmission line work and shield finish
Ground fault or shield
contacted with transmission
line?
System composition?
Single refrigerant system
Plural refrigerant system
Confirm supply power con­nector CN40 of outdoor unit
Only 1 set with CN40 inserted?
Modification of CN40 insertion method
Investigation of trans­mission line noise
Noise exist?
Investigation of the cause of noise
For the investigation method, follow <Investigation
method of transmission wave shape/noise>.
Modification of faulty point
Replace insertion of CN40 to CN41
CN40 inserted?
Confirm supply power con­nector CN40 of outdoor unit
MELANS connected system
Checking method and processing
6603
a) Check transmission wave shape/noise on
transmission line by following <Investigation method of transmission wave shape/noise>.
No noise indicates faulty controller of generat-
ing unit.
Noise if existed, check the noise.
Transmission processor hardware error
Transmission circuit bus­busy error
1Collision of data transmis-
sion: Transmission can not be per­formed for 4~10 consecutive minutes due to collision of data transmission.
2Data can not be transmitted
on transmission line due to noise for 4~10 consecutive minutes.
Note:
The address/attribute shown on remote con­troller indicates the con­troller which has de­tected error.
1) As the voltage of short frequency like noise is mixed in transmission line continuously, transmission processor can not transmit.
2) Faulty controller of generating unit.
Faulty controller of generating unit
Checking
code
Meaning, detecting method Cause Checking method & Countermeasure
-75-
Page 79
6606 Communications with
transmission processor error
Communication trouble be­tween apparatus processor and trans-mission processor.
Note:
The address/attribute shown on remote con­troller indicates the con­troller which has de­tected error.
1) Data is not properly transmitted due to casual errouneous opera­tion of the generating controller.
2) Faulty generating controller.
Turn off power sources of indoor unit and outdoor unit.
When power sources are turned off sepa­rately, microcomputer is not reset and nor­mal operations can not be restored.
Controller trouble is the source of the trouble
when the same trouble is observed again.
Checking
code
Meaning, detecting method Cause Checking method & Countermeasure
-76-
Page 80
Shut down OC unit power source, and make it again. It will return to normal state at an ac­cidental case. When normal state can not be re­covered, check for the 1) ~ 4) of the cause.
Shut down both OC and IC power so­urces simultaneously for 5 minutes or more, and make them again. It will return to normal state at an accidental case. When normal state can not be re­covered, check for the 1) ~ 5) of the cause.
Shut down OC power sources for 5 minutes or more, and make it again. It will return to normal state at an acci­dental case. When normal state can not be re­covered, check for the 1) ~ 4) of the cause.
Checking
code
Meaning, detecting method
6607
No ACK error
When no ACK signal is detected in 6 continuous times with 30 second interval by transmission side controller, the transmission side detects error.
Note: The address/attribute shown on remote controller indicates the controller not
providing the answer (ACK).
Generating unit address
Display of trouble
Detecting method
Cause Checking method & countermeasure
1) Poor contact of transmission line of OC or IC.
2) Damping of transmission line voltage/signal by acceptable range of transmission wiring exceeded.
Farthest : Less than 200m Remote controller wiring: Less than 10m
3) Erroneous sizing of transmission line (Not within the range below). Wire diameter : 1.25mm2 or more
4) Faulty control circuit board of OC
1) When IC unit address is changed or modified during operation.
2)
Faulty or slipping off of transmission wiring of IC
3) Slipping off of IC unit connector (CN2M)
4) Faulty IC unit controller
5) Faulty remote controller
1) Faulty transmission wiring at IC unit side
2) Faulty transmission wiring of RC
3) When remote controller address is changed or modified during operation
4) Faulty remote controller
No reply (ACK) at IC transmission to OC
No reply (ACK) at RC transmission to IC
No reply (ACK) at IC transmission to RC
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
System compo­sition
1 Outdoor
unit (OC)
2 Indoor
unit (IC)
3 Remote
controller (RC)
(1) Single refrigerant system
-77-
Page 81
Checking
code
Meaning, detecting method
No ACK error When no ACK signal is detected in 6 continuous times with 30 second interval by transmission
side controller, the transmission side detects error.
Note: The address/attribute shown on remote controller indicates the controller not
providing the answer (ACK).
Generating unit address
Display of trouble
Detecting method
No reply (ACK) at IC transmission to OC
No reply (ACK) at RC transmission to IC
No reply (ACK) at IC transmission to RC
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
System compo­sition
1 Outdoor
unit (OC)
2 Indoor
unit (IC)
3 Remote
controller (RC)
6607
(continued)
(2) Group operation system using plural refrigerants
Same as measure for single refriger­ant system
a) Shut down the power source of
both IC and OC for over 5 minutes simultaneously, and make them again. Normal state will be returned in­case of accidental trouble. If it does not return to normal, follow b).
b) Check for 1) ~ 5) of causes. If cause
is found, remedy it. If no cause is found, follow c).
c) Check other remote controller or
OC unit LED for troubleshooting for trouble. Trouble Modify the trouble ac-
cording to the con
tent
of check code.
No trouble→Faulty indoor controller
a) Shut down the power source of OC
for over 5 minute, and make it again. Normal state will be returned in case of accidental trouble. If it does not return to normal, follow b).
b) Check for 1) ~ 5) of causes. If cause
is found, remedy it. If no cause is found, follow c).
c) Same as that of c) for IC unit
When normal state can not be ob­tained, check 1) ~ 5) of causes.
Cause Checking method & countermeasure
As same that for single refrigerant system
1) Cause of 1) ~ 5) of Cause for single refriger­ant system
2) Slipping off or short circuit of transmission line of OC terminal block for centralized control (TB7)
3) Shut down of OC unit power source of one re­frigerant system
4) Neglecting insertion of OC unit power supply connector (CN40)
5) Inserting more than 2 sets of power supply connector (CN40) for centralized control use.
For generation after normal operation conduct­ed once, the following causes can be consider­ed.
Total capacity error (7100)
Capacity code setting error (7101)
Connecting set number error (7102)
Address setting error (7105)
1) Cause of 1) ~ 3) of Cause for single refri­gerant system
2) Slipping off or short circuit of transmission line of OC terminal block for centralized con­trol (TB7)
3) Shut down of OC unit power source of one refrigerant system
4) Neglecting insertion of OC unit power supply connector (CN40)
5) Inserting more than 2 sets of power supply connector(CN40) for centralized control use
At generation after normal operation conducted once, the following causes can be considered.
Total capacity error (7100)
Capacity code setting error (7101)
Connecting set number error (7102)
Address setting error (7105)
-78-
Page 82
Checking
code
Meaning, detecting method
No ACK error
When no ACK signal is detected in 6 continuous times with 30 second interval by transmission side controller, the transmission side detects error.
Note: The address/attribute shown on remote controller indicates the controller not
providing the answer (ACK).
Generating unit address
Display of trouble
Detecting method
No reply (ACK) at IC transmission to OC
No reply (ACK) at transmission of SC to IC
No reply (ACK) at transmission of IC to RC
No reply (ACK) at transmission of MELANS to RC
Remote
controller
(RC)
Remote
controller
(RC)
Remote
controller
(RC)
System compo­sition
1 Outdoor
unit (OC)
2 Indoor
unit (IC)
3 Remote
controller (RC)
6607
(continued)
As same that for single refrigerant system
Trouble of partial IC units:
1) Same cause as that for single refrigerant system
Trouble of all ICs in one refrigerant system:
1) Cause of total capacity error (7100)
2) Cause of capacity code setting error(7101)
3) Cause of connecting number error (7102)
4) Cause of address setting error (7105)
5) Slipping off or short circuit of transmission line of OC unit terminal block for central control (TB7)
6) Power source shut down of OC unit
7) Trouble of OC unit electrical system
Trouble of all ICs:
1) Cause of 1) ~ 7) of (b)
2) Insertion of power supply connector (CN40) into OC unit transmission line for central­ized control
3) Slipping off or power source shut down of power supply unit for transmission line
4) Faulty system controller (MELANS)
Same cause as that for plural refrigerant system
Trouble of partial IC units:
1) Same cause of that for single refrigerant system
Trouble of all ICs in one refrigerant system:
1) Error detected by OC unit Total capacity error (7100) Capacity code setting error (7101) Connecting number error (7102) Address setting error (7105)
2) Slipping off or short circuit of transmission line of OC unit terminal block for central control (TB7)
3) Power source shut down of OC unit
4) Trouble of OC unit electrical system
Trouble of all ICs:
1) Cause of 1) ~ 7) of (b)
2) Insertion of power supply connector (CN40) into OC unit transmission line for central­ized control
3) Slipping off or power shutdown of power supply unit for transmission line
4) Faulty MELANS
Same countermeasure as that for single refrigerant system
Same countermeasure as that for
single refrigerant system
Confirm OC trouble diagnosis LED
At trouble generation, check for
the content according to check code.
At no trouble, follow b).
Check the content of 5)~7) shown left.
Confirm voltage of transmission line for centralized control
More than 20V Confirm
1) 2)
left.
Less than 20V Confirm 3) left.
Same countermeasure as that for plur­al refrigerant system
Same countermeasure as that for
single refrigerant system
Confirm OC trouble diagnosis LED
At trouble generation, check for
the content according to check code.
At no trouble, follow (b).
Check the content of 2)~4) shown left.
Check the causes of 1) ~ 4) left.
(3) Connecting system with system controller (MELANS)
Cause Checking method & countermeasure
-79-
Page 83
Checking
code
Meaning, detecting method
No ACK error
When no ACK signal is detected in 6 continuous times with 30 second interval by transmission side controller, the transmission side detects error.
Note: The address/attribute shown on remote controller indicates the controller not
providing the answer (ACK).
Generating unit address
Display of trouble
Detecting method
No reply (ACK) at transmission of IC to SC
Remote
controller
(RC)
System compo­sition
4 System
controller (SC)
Address which should not be exist-ed
6607
(continued)
Trouble of partial remote controller:
1) Faulty wiring of RC transmission line
2) Slipping off or poor contact of RC transmis-
sion connector.
3) Faulty RC
Trouble of all ICs in one refrigerant system
1) Error detected by OC unit
Total capacity error (7100) Capacity code setting error (7101) Connecting number error (7102) Address setting error (7105)
2) Slipping off or short circuit of transmission
line of OC unit terminal block for central control (TB7).
3) Power source shut down of OC unit
4) Trouble of OC unit electrical system
Trouble of all RC:
1) Cause of 1) ~ 7) of (b)
2) Inserting supply power connector (CN40)
to
OC transmission line for centralized control
3) Slipping off or power shutdown of power
supply unit for transmission line
4) Faulty MELANS
IC unit is keeping the memory of the original group setting with RC although the RC ad­dress was changed later. The same symptom will appear for the re­gistration with SC.
Check 1) ~ 3) left.
a) Confirm OC trouble diagnosis LED
At trouble generation, check for
the content according to check code.
At no trouble, follow b).
b) Check the content of 2) ~ 4) shown
left.
Check the causes 1)~4) left.
As some IC units are keeping the me­mory of the address not existing, delete the information. Employ one of the deleting method among two below.
1) Deletion by remote controller Delete unnecessary information by the manual setting function of re­mote controller.
2) Deletion by connecting inform­ation deleting switch of OC unit
Be careful that the use of this method will delete all the group information set with RC and all the interlocking information of IC unit.
1
Shut down OC unit power source, and wait for 5 minutes.
2 Turn on the dip switch SW2-2
provided on OC unit control cir­cuit board.
3 Make OC unit power source, and
wait for 5 minutes.
4
Shut down OC unit power source, and wait for 5 minutes.
5 Turn off the dip switch SW2-2
provided on OC unit control cir­cuit board.
6 Make OC unit power source.
(3) Connecting system with system controller (MELANS)
No relation with system
Cause Checking method & countermeasure
-80-
Page 84
Checking
code
6608 1) At the collision of mutual transmis-
sion data when transmission wiring is modified or the polarity is changed while turning the power source on, the wave shape changes detecting error.
2) Repeating of transmission error due to noise.
3) Damping of transmission line volt­age/signal due to exceeding of the acceptable range for transmission wiring.
Farthest Less than 200m
RC wiring Less than 12m
4) Damping of transmission voltage/ signal due to improper type of trans-mission line.
Wire size : More than 1.25mm
2
No response error
Though acknowledgement of receipt (ACK) is received after transmission, no response command is returned. Detected as error by transmis­sion side when the same symp­tom is re-peated 10 times with an interval of 3 seconds
Note:
The address/attribute shown on remote con­troller indicates the con­troller which has de­tected error.
a) Generation at test run
Turn off the power sources of OC unit, IC unit and Fresh Master for more than 5 minutes simultaneously, and make them again. Returning to normal state means the
trouble detection due to transmission line work while powering.
If generated again, follow b).
b) Check 3) and 4) of the causes left.
If cause is found, remedy it. If cause is not found, follow c).
c) Investigate the transmission wave shape/
noise on transmission line according to <Investigation method of transmission wave shape/noise>.
Much possibility if 6602 is generated.
Meaning, detecting method Cause Checking method & Countermeasure
(3) System error
Checking
code
Meaning, detecting method Cause Checking method & Countermeasure
7100
7101
7102
Total capacity error
Total capacity of indoor units in the same refrigerant system exceeds limitations.
Trouble source:
Outdoor unit
Capacity code error
Error display at erroneous con­nection of Indoor unit of which model name can not be con­nected
Trouble source :
Outdoor unit Indoor unit
Connected unit count over
Number of units connected in the same refrigerant system exceeds limitations.
Trouble source:
Outdoor unit
1) Total capacity of indoor units in the same refrigerant system ex­ceeds the following:
2) Erroneous setting of OC model
selector switch (SW3-10)
1) The Indoor unit model name
(model code) connected is not connectable.
Connectable range...... 08~48
2) Erroneous setting of the switch
(SW2) for setting of model name of Indoor unit connected.
1) Number of unit connected to ter-
minal block (TB3) for outdoor/in­door transmission line exceeds limitations given be-lows:
Item Limitation
1 Total of 1~13 (80)
Indoor unit 1~16 (100)
2 Total of Indoor
unit & RC
1~35
a) Check for the model total (capacity cord total)
of indoor units connected.
b) Check whether indoor unit capacity code
(SW2) is wrongly set. For erroneous switch setting, modify it, turn off
power source of outdoor unit, and indoor unit simultaneously for 5 minutes or more to modify the switch for setting the model name (capacity coad).
Check for the model selector switch (Dip switches SW3-10 on outdoor unit control circuit) of OC.
a) Check for the model name of the Indoor unit
connected.
b) Check for the switch (SW2 if indoor controller
for setting of Indoor unit model name of generating address. When it is not agreed to the model name, modify the capacity code while shutting off the power source of Indoor unit.
* The capacity of Indoor unit can be confirmed
by the self-diagnosios function (SW1 operation) of Indoor unit.
a) Check whether the connection of units to the
terminal block for indoor/outdoor transmission wiring (TB3) of outdoor unit is not exceeding the limitation.
(See 1 ~ 2 left.) b) Check for 2), 3), 4), left. c) Check for the connection of transmission
wiring to the terminal block for centralized
control is erroneously connected to the indoor/
outdoor transmission wiring terminal block
(TB3).
Model Total capacity
PUHY-80 104
PUHY-100 130
12345678910
SW3
ON OFF
.....
...
100 80
-81-
Page 85
7102
7105
7111
Connected unit count over
Address setting error
Erroneous setting of Outdoor unit address
Trouble source : Outdoor unit
Remote control sensor error
Error not providing the tem­perature designed to remote controller sensor.
Trouble source : Indoor unit
2) The Outdoor unit address is being set to 51~100 under automatic address mode (Remote controller displays HO).
3) Slipping off of transmission wiring at Outdoor unit.
4) Short circuit of transmission line in case of 3) & 4), remote controller displays HO.
1) Setting error of Outdoor unit ad­dress The address of Outdoor unit is not being set to 51~100.
1) In case when the old type remote controller for M-NET is used and the remote controller sensor is de­signed on indoor unit. (SW1-1 turned ON)
a) Check for the model total (capacity code total)
of indoor units connected.
Check that the address of Outdoor unit is being set to 51~100. Reset the address if it stays out of the range, while shutting the power source off.
a) Replace the old remote controller by the new
remote controller.
Checking
code
Meaning, detecting method Cause Checking method & Countermeasure
-82-
Page 86
0
1
2
3 4 5 6
7
8
9
10
11
12
13
14 15
16
17
18
19
20
0000000000
1000000000
0100000000
1100000000 0010000000 1010000000 0110000000
1110000000
0001000000
1001000000
0101000000
1101000000
0011000000
1011000000
0111000000 1111000000
0000100000
1000100000
0100100000
1100100000
0010100000
[3] LED Monitor Display
E: E2 Contents stored in the E2PROM; M: Monitored by the IC through communications; E*: Stored in service memory.
COMP Operat­ing
Unit No. 1
Unit No. 9
Unit No. 1
Unit No. 9
Unit No. 1
Unit No. 9
Permissible Stop
Cooling Refrigerant Recovery
High Pressure Error 1, 2
Suction Pressure Error
TH1 Error
TH7 Error
No SW1 Item Display Remarks
12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
Relay Output Display 1 (Lights up to display)
Check Display 1 OC Error
Relay Output Display 2
Check Display 2 (Including the IC)
Outdoor Unit Operation Display
Indoor Unit Check
Indoor Unit Operation Mode
Indoor Unit Thermostat
Outdoor Unit Operation Mode
Outdoor Unit Control Mode
Error Delay in Outdoor Unit
Crank­case Heater
Packet being sent
Unit No. 2
Unit No. 10
Unit No. 2
Unit No. 10
Unit No. 2
Unit No. 10
Standby
Configuration Detection Error
TH2 Error
TH8 Error
21S4
3 minutes, restart
Unit No. 3
Unit No. 11
Unit No. 3
Unit No. 11
Unit No. 3
Unit No. 11
Defrost­ing
Heating Refrigerant Recovery
Outlet Tempera­ture Error
SV1
Compres­sor operating
Unit No. 4
Unit No. 12
Unit No. 4
Unit No. 12
Unit No. 4
Unit No. 12
Cooling
Overcurrent Protection
Reverse Phase, Open Phase Error
SV2
Prelimi­nary Error
Unit No. 5
Unit No. 13
Unit No. 5
Unit No. 13
Unit No. 5
Unit No. 13
Cooling High Oil Recovery
Heat Sink Thermostat Operating
TH5 Error
Lights for Normal Operation
Unit No. 8
Unit No. 16
Unit No. 8
Unit No. 16
Unit No. 8
Unit No. 16
Heating Low Oil Recovery
Refrigerant Over­charge
THHS Error
LD8 is a relay output indicator which lights u at all times when the microcomputer’s power is ON. When sending of a monitoring re­quest to IC/BC is terminated, if there is no error, “- - - -” is displayed. E
*only for PUHY E
If there is no error, “- - - -” is displayed. E
E
E
Lights up if an abnormal stop has occurred in the IC. The indicator for Unit No. 1 goes off when error reset is carried out from the smallest address. M
Lights up during cooling. Blinks during heating. Goes off during stop and blower operation. M
Lights up when thermostat is ON. Goes off when thermostat is OFF. M
E
The flag correspond­ing to the item where there is an error delay lights up. E
0 ~ 9999
Address and error code reversed
SSR
Unit No. 7
Unit No. 15
Unit No. 7
Unit No. 15
Unit No. 7
Unit No. 15
Heating High Oil Recovery
INV Error
HPS Error
0 ~ 9999
Address and error code reversed
Error
Unit No. 6
Unit No.14
Unit No. 6
Unit No.14
Unit No. 6
Unit No.14
Heating
Cooling Low Oil Recovery
Overcurrent Break
TH6 Error
-83-
Page 87
21
22
23
24
25
26
27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
46 47 48 49 50 51
1010100000
0110100000
1110100000
0001100000
1001100000
0101100000
1101100000 0011100000 1011100000 0111100000 1111100000 0000010000 1000010000 0100010000 1100010000 0010010000 1010010000 0110010000 1110010000 0001010000 1001010000 0101010000 1101010000 0011010000 1011010000
0111010000 1111010000 0000110000 1000110000 0100110000 1100110000
High Pressure Error 1, 2
Suction Pressure Error
TH1 Error
TH7 Error
No SW1 Item Display Remarks
12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
Outdoor Unit Preliminary Error History
Error History 1
Inverter Error Detail
Error History 2 Inverter Error Detail Error History 3 Inverter Error Detail Error History 4 Inverter Error Detail Error History 5 Inverter Error Detail Error History 6 Inverter Error Detail Error History 7 Inverter Error Detail Error History 8 Inverter Error Detail Error History 9 Inverter Error Detail Error History 10 Inverter Error Detail Type of Prelimi-
nary Inverter Error
(Details of the inverter error in No. 17)
TH1 Data TH2 Data
TH5 Data TH6 Data
Low Pressure Error
Configuration Detection Error
TH2 Error
TH8 Error
Outlet Tempera­ture Error
Overcur­rent Protection
Reverse Phase, Open Phase Error
Heat Sink Thermostat Operation
TH5 Error
Refrigerant Over­charge
THHS Error
HPS Error
Overcur­rent Break
TH6 Error
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
-99.9 ~ 999.9
-99.9 ~ 999.9
Lights up if an error delay has occurred between the time the power was turned on and the present time. To turn the indicators off, switch the power OFF briefly. E
The error and error delay code are displayed. If the address and error code are shown in reverse, or there is no error, - - - - is displayed. E
If there is no error, -
- - - is displayed. E E
If there is no error, - - - - is always overwritten.
E
E
No. 52 THHS data are monitored by the inverter microcomputer.
-84-
Page 88
52 53 54 55 56 57 58 59 60
61
62
63 64 65
66
67 68 69 70
71
72 73 74 75 76 77 78 79 80 81 82 83 84 85 86
0010110000 1010110000 0110110000 1110110000 0001110000 1001110000 0101110000 1101110000
00111100
10111100
01111100
11111100 00000010 10000010
01000010
11000010 00100010 10100010 01100010
11100010
00010010 10010010 01010010 11010010 00110010 10110010 01110010 11110010 00001010 10001010 01001010 11001010 00101010 10101010 01101010
Hz
Low
-3 deg. or less
Low
-3 deg. or less
No SW1 Item Display Remarks
12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
THHS Data HPS Data TH7 Data TH8 Data
Accumulator Level Change in Hz AK
Difference from target TC
Difference from target ET
Target TC Target ET Temporary
requency Compressor
output frequency AK SLEV LEV1 Fan controller
output value
DC buss current
OC address IC1 address IC2 address IC3 address IC4 address IC5 address IC6 address IC7 address IC8 address IC9 address IC10 address IC11 address IC12 address IC13 address
Hz
0
Low
-3 ~ -2 deg.
Low
-3 ~ -2 deg.
Hz
+
Low
-2 ~ -1 deg.
Low
-2 ~ -1 deg.
–– ∆ AK
+
High 3 deg. or more
High 3 deg. or more
AK
0
High 2~3 deg.
High 2~3 deg.
AK
High 1~2 deg.
High 1~2 deg.
-99.9 ~ 999.9
↑ ↑ ↑
0~9 (AL= is also displayed)
E
Actual frequency out­put from inverter
Display fan controller output value used for control.
Stable region
Stable region
-99.9 ~ 999.9
0 ~ 9999
↑ ↑ ↑
0000 ~ 9999
-99.9 ~ 999.9
0000 ~ 9999
↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑
0000 ~ 9999
-85-
Page 89
87 88 89 90
91 92
93
94
95 96 97 98
99 100 101
102 103 104 105 106
107 108 109 110
111
112 113 114 115 116
11101010 00011010 10011010 01011010
11011010 00111010
10111010
01111010
11111010 00000110 10000110 01000110 11000110 00100110 10100110
01100110 11100110 00010110 10010110 01010110
11010110 00110110 10110110 01110110
11110110
00001110 10001110 01001110 11001110 00101110
No SW1 Item Display Remarks
12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
IC14 address IC15 address IC16 address Compressor
operat-
ion hour
upper 4 digits Lower 4 digits OC operation
mode
OC operation mode
Relay output display 1 Lighting display
TH1 data TH2 data
TH5 data TH6 data Pressure sensor
data THHS data TH7 datata TH8 data
Compressor output frequency
AK SLEV LEV1 Compressor
operating current OC operation
display
IC1 inlet temperature IC2 inlet temperature IC3 inlet temperature IC4 inlet temperature IC5 inlet temperature
0000 ~ 9999
↑ ↑
When there is an error stop with No92-111, the data on error stops or the data immediately before the error postponement stop, which is stored in service memory, are displayed.
Permitted mode stop
Cooling Refrigerant recovery
Com­pressor operation
Standby
52C
Defrost
Heating Refrigerant recovery
21S4
Cooling
SV1
Heating
Cooling Low oil recovery
SV4
Cooling High oil recovery
Heating High oil recovery
Heating Low oil recovery
-99.9 ~ 999.9
-99.9 ~ 999.9
↑ ↑
↑ ↑ ↑
0 ~ 9999
↑ ↑ ↑
-99.9 ~ 999.9
In forcible powering
3­minute restart
Compres­sor Operating
I
ntermit­tent fault check
Trouble
-99.9 ~ 999.9
↑ ↑ ↑ ↑
No.92-111 display the data immediately before error stop or error intermittent foult stop.
-86-
Page 90
10101110 01101110 11101110 00011110 10011110 01011110 11011110 00111110 10111110 01111110 11111110 00000001 10000001 01000001 11000001 00100001 10100001 01100001 11100001 00010001 10010001 01010001 11010001 00110001 10110001 01110001 11110001 00001001 10001001 01001001 11001001 00101001 10101001 01101001 11101001 00011001 10011001 01011001
No SW1 Item Display Remarks
12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
IC6 inlet temperature IC7 inlet temperature IC8 inlet temperature IC9 inlet temperature IC10 inlet temperature IC11 inlet temperature IC12 inlet temperature. IC13 inlet temperature IC14 inlet temperature IC15 inlet temperature IC16 inlet temperature IC1 liquid piping temp. IC2 liquid piping temp. IC3 liquid piping temp. IC4 liquid piping temp. IC5 liquid piping temp. IC6 liquid piping temp. IC7 liquid piping temp. IC8 liquid piping temp. IC9 liquid piping temp. IC10 liquid piping temp. IC11 liquid piping temp. IC12 liquid piping temp. IC13 liquid pipe temp. IC14 liquid piping temp. IC15 liquid piping temp. IC16 liquid piping temp. IC1 gas piping temp. IC2 gas piping temp. IC3 gas piping temp. IC4 gas piping temp. IC5 gas piping temp. IC6 gas piping temp. IC7 gas piping temp. IC8 gas piping temp. IC9 gas piping temp. IC10 gas piping temp. IC11 gas piping temp.
117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154
-99.9 ~ 999.9
↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑
-87-
Page 91
155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193
11011001 00111001 10111001 01111001 11111001 00000101 10000101 01000101 11000101 00100101
10100101 01100101 11100101 00010101 10010101 01010101 11010101 00110101 10110101 01110101 11110101 00001101 10001101 01001101 11001101 00101101 10101101 01101101 11101101 00011101 10011101 01011101 11011101 00111101 10111101 01111101 11111101 00000011 10000011
No SW1 Item Display Remarks
12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
IC12 gas piping temp. IC13 gas piping temp. IC14 gas piping temp. IC15 gas piping temp. IC16 gas piping temp. IC1SH IC2SH IC3SH IC4SH IC5SH IC6SH IC7SH IC8SH IC9SH IC10SH IC11SH IC12SH IC13SH IC14SH IC15SH IC16SH IC1SC IC2SC IC3SC IC4SC IC5SC IC6SC IC7SC IC8SC IC9SC IC10SC IC11SC IC12SC IC13SC IC14SC IC15SC IC16SC IC1 LEV Opening IC2 LEV Opening
-99.9 ~ 999.9
↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑
-88-
Page 92
194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231
01000011 11000011 00100011 10100011 01100011 11100011 00010011 10010011 01010011 11010011 00110011 10110011 01110011 11110011 00001011 10001011 01001011 11001011 00101011 10101011 01101011 11101011 00011011 10011011 01011011 11011011 00111011 10111011 01111011 11111011 00000111 10000111 01000111 11000111 00100111 10100111 01100111 11100111
No SW1 Item Display Remarks
12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
IC3 LEV Opening IC4 LEV Opening IC5 LEV Opening IC6 LEV Opening IC7 LEV Opening IC8 LEV Opening IC9 LEV Opening IC10 LEV Opening IC11 LEV Opening IC12 LEV Opening IC13 LEV Opening IC14 LEV Opening Angle IC15 LEV Opening IC16 LEV Opening IC1 operation mode IC2 operation mode IC3 operation mode IC4 operation mode IC5 operation mode IC6 operation mode IC7 operation mode IC8 operation mode IC9 operation mode IC10 operation mode IC11 operation mode IC12 operation mode IC13 operation mode IC14 operation mode IC15 operation mode IC16 operation mode IC1 capacity code IC2 capacity code IC3 capacity code IC4 capacity code IC5 capacity code IC6 capacity code IC7 capacity code IC8 capacity code
-99.9 ~ 999.9
↑ ↑ ↑ ↑ ↑ ↑
↑ ↑ ↑ ↑
↑ ↑ ↑
0: Stopped 1: Fan 2: Cooling 3: Heating 4: Dry
0000 ~ 9999
↑ ↑ ↑ ↑ ↑ ↑ ↑
-89-
Page 93
232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255
00010111 10010111 01010111 11010111 00110111 10110111 01110111 11110111 00001111 10001111 01001111 11001111 00101111 10101111 01101111 11101111 00011111 10011111 01011111 11011111 00111111 10111111 01111111 11111111
No SW1 Item Display Remarks
12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
IC9 capacity code IC10 capacity code IC11 capacity code IC12 capacity code IC13 capacity code IC14 capacity code IC15 capacity code IC16 capacity code IC1 filter IC2 filter IC3 filter IC4 filter IC5 filter IC6 filter IC7 filter IC8 filter IC9 filter IC10 filter IC11 filter IC12 filter IC13 filter IC14 filter IC15 filter IC16 filter
0000 ~ 9999
↑ ↑ ↑ ↑ ↑ ↑ ↑
-99.9 ~ 999.9
↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑
-90-
Page 94
AIR CONDITIONERS CITY MULTI Series Y
Models PUHY-80TMU-A, 100TMU-A
Service Handbook
Service Handbook PUHY-80TMU-A, 100TMU-A
Issued in March 2004
New publication effective March 2004.
Specifications subject to change without notice.
Page 95
3400 Lawrenceville Suwanee Road Suwanee, Georgia 30024
Toll Free: 800-433-4822 Toll Free Fax: 800-889-9904
www.mrslim.com
Specifications are subject to change without notice.
Loading...