Mitsubishi Electric PRC- 8MYA, PRC-10MYA, PRC-12MYA, PRC-15MYA, PRC-20MYA Installation Manual

...
MITSUBISHI ELECTRIC AIR CONDITIONERS
CONTENTS
1. Safety precautions.
2. Selection of installed place.
3. Space required around units.
4. Preparation before installation.
5. Installation of the unit.
7. Electric wiring.
8. Before starting the trial run.
PAGE 1 2 3 3 5 5 6 8
Note
1. Please read this manual to have the correct, safe use before installation.
2. Please keep this manual in the place where it is always seen to use this manual with "Operation manual" after reading.
3. The customer must not install and not transfer the unit by themselves. (Safety and the function cannot be secured.)
INSTALLATION MANUAL
Service ref.
PRC- 8MYA(-03) PRC-10MYA(-03) PRC-12MYA(-03) PRC-15MYA(-03) PRC-20MYA(-03) PRC-24MYA(-03) PRC-32MYA(-03)
Model
PRC- 8MYA PRC-10MYA PRC-12MYA PRC-15MYA PRC-20MYA PRC-24MYA PRC-32MYA
Cooling only
1
Warning.
Use only optional parts authorized by Mitsubishi Electric.
If the accessories are installed improperly, water leakage, electric shock or fire may result. Ask your dealer or an authorized company to install them.
Danger and the extent caused when wrong handling is done are divided by displaying warning and attention and are explained.
1. Safety precautions.
1)
Before doing electrical work.
1.1 Before installation.
The Installation Manual details the suggested installation method. Any structural alteration necessary for installation must comply with local building code requirements. After you have read this manual, keep it and the Operation Manual in a safe place for easy reference whenever a question arises. If the unit is going to be operated by another person, make sure that this manual is given to him or her. The unit should not be installed by the user. (Safety and the function cannot be secured)
Caution.
When installing the power lines, do not apply tension to the cables.
The tighten or loosen the connections may cause generate heat and cause fire.
When installing at a watery place, provide an electric leak breaker.
Failure to mount the electric leak breaker may cause electric shock.
Ventilate the room if refrigerant leaks during Installation.
The refrigerant heated generates poisonous gas by decomposition which can cause poisoning.
The unit must be installed on stable, level surface in a place where there is no accumulation of snow, leaves or rubbish. The unit should be installed in a location where air and noise emitted by the unit will not disturb the neighbors.
If the unit is loosely mounted, it may fall, and cause injury.
The terminal block cover of unit must be firmly attached to prevent entry of dust and moisture.
Improper mounting of the cover cause electric shock or fire.
For the power lines, use standard cables of sufficient current capacity.
Otherwise, current leakage, overheating or fire may occur.
Use breaker or fuse with proper capacity. Make sure that each appliance has a main power switch.
 Using a wire or copper wire instead of proper capacity can cause fire
or trouble. Other appliances connected to the same line could cause an overload.
The unit must be properly earth connected.
Do not connect the earth wire to gas pipe, city water pipe, lightning rod or telephone earth wire. Improper earth connection may cause electric shock.
Ask your dealer or specialized subcontractor for installation.
Conducting installation work by yourself improperly may cause a fire, electric shock or water leakage.
For installation, conduct the work correctly by following the Installation Manual.
Improper installation may cause a fire, electric shock or water leakage.
Use only the specified refrigerant (R-22) to charge the refrigerant circuit. Do not mix it with any other refrigerant and do not allow air to remain in the circuit.
Air enclosed in the circuit can cause high pressure resulting in a rupture and other hazards. 
Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely.
The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electric shock.
Install the unit on a spot sufficiently durable against the unit weight.
Insufficient durability can cause an injury by the falling down of unit.
All electrical work must be performed by licensed technician, according to local regulations and the instructions given in this manual.
Power lines with insufficient capacity or improper electric work may result in electrical shock or fire.
Never repair the unit, remodel or transfer it to another site by yourself.
If they are performed improperly, water leakage, electric shock or fire may result. If you need to have the unit repaired or moved, consult your dealer.
After completing installation work, make sure that refrigerant gas has not leaked.
If refrigerant gas has leaked and exposed to fan heater, stove, oven and so on, it may generate noxious gases. Please do the gas leakage inspection before starting.
Take a proper measure to suppress the critical concentration of refrigerant, if leaked when installing the unit in a small room.
The limit density is made not to be exceeded even if the refrigerant leaks by any chance. You are necessary to measure the ventilation in order to prevent the accident. If the refrigerant leaks, hypoxia accident may caused. For the countermeasure to be taken, consult your dealer.
Use only the specified cables for wiring. The connections must be made secured without tension the terminals.
Improper connection or fastening can cause a fire or electric shock.
The unit should be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons or strong winds.
Improper installation work can cause an injury by the falling down of the unit.
Before operating the unit ,make sure you read all the "Safety precautions".
"Safety precautions" lists important points about safety. Please be sure to follow them.
The display and its meaning are given below.
Warning
Erroneous handling gives a high possibility to induce serious results such as death or heavy injury.
Caution
Erroneous handling may induce serious injury depending on the situation.
Warning.
Carefully read the labels affixed to the main unit.
The symbols used here represent that as follows.
Never do this.
Never touch without wearing glove on your hands.
Make sure to connect earth line.
2)
Before constructing the installation or transfer.
Do not leave the mounting base being damaged.
The damaged base may cause the falling down of the unit which may give injury.
Install drain piping (hose) according to this Installation Manual to ensure proper drainage.
Improper drain piping (hose) may cause water leakage and damage to furniture or other possessions.
Do not touch the metal edges inside the unit without wearing glove on your hands.
Touching directly it may injure your hands.
Do not place objects under the units to avoid damage of condensation.
When the room is high humidity or when the drain pipe is clogged, water may drip from the unit.
Never install on the place where a combustible gas might leak.
The gas may ignite or explode when the gas leaks and collects in surroundings of the unit.
For special use as for foods, animals/plants, precision equipment or art objects, the applicability should be confirmed earlier.
As the use for the applications other than that designed originally may result in the deterioration of the quality. Consult your dealer in this regard.
When the unit is installed at telecommunication centers or hospitals, take a proper provision against noise.
The erroneous operation of air conditioner may be induced by inverter equipment, independent power device, medical equipment or communication equipment.
Do not operate the air conditioner without the air filter set place.
Dust may accumulate, and cause a failure.
Do not touch the compressor or refrigerant piping without wearing glove on your hands.
Touching directly such the parts can cause a burn or frostbite as it becomes high or low temperature according to the refrigerant state.
Do not handle the switch with wet hands.
Otherwise electric shock can be resulted.
The unit should be securely installed level surface.
When the unit inclines, it causes the water leak and the breakdown. Please confirm the horizontal with the spirit level.
Do not use the unit under a special atmosphere.
Installing the unit at the following places may cause a trouble, a place where is much machine oil, salt , humidity or dust, spa district, a place full of sulfur gas, volatile gas, or corrosive gas, a place near high frequency processing machine.
Do not wash the unit with water.
If washed with water, electric shock may be caused.
At emergency (if you smell something burning), stop operation and turn the power source switch off.
Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electric shock.
Do not remove the panel or the fan guard from the unit when it is running.
You could be injured if you touch rotating, hot or high-voltage parts .
Process the packing material surely.
Be sure to safety dispose the packing materials. Packing materials, such as catches and other metal or wooden parts, may cause stabs or other injuries. Tear off and discard plastic packing bags so that children will not play any of them. If children play with a plastic bags which was not torn off, it may cause a risk of suffocation.
2
The base and attachments of the unit should be periodically checked for looseness, cracks or other damage.
If such defects are left uncorrected, the unit may fall and cause personal injury or property damage.
3)
Before starting.
2. Selection of installed place.
Select space for installing unit, which will meet the following conditions.
Please pay attention to the refrigerant (Freon gas).
A non flammable, non-toxic, odourless refrigerant is used for this air conditioner.
The refrigerant is collected on the floor side in the room because the specific gravity are larger than air. And, it causes the hypoxia accident.
When the refrigerant gas leaks by any chance, the user must ventilates air enough by stopping the drive of the unit and opening the door.
Place where no direct thermal radiation from other heat sources. Place where no possibility of short cycle operations caused by exhaust heat from unit. Place where no possibility of annoying neighbors by noise from unit. Place where no exposition to strong wind. Place where no possibility of snow wind. Place where with strength which bears weight unit. Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leak of combustible gas is expected. Avoid unit installation in a place where acidic spray (sulfur) are often used. Place without dispersion of oil and steam.
Remote controller is not allowed to install for the place where direct sunshine strikes.
Remote controller should be pushed with finger.
It occasionally causes the electric shock and the breakdown.
Please do not use the unit in the following places.
Place where a lot of oil (The machine oil is contained), moistures, and dust exist. Place where a lot of salinity such as beach districts exists. Place where sulfur gas, volatile gas, and corroded gas are filled. Place where acid solution is frequently used. Place where special spray is frequently used. Hot spring zone. Near machine (high cycle welding machine etc.) generating high cycle. Place where ventilation entrance of unit is closed by snowfall. The main body might corrode when the unit is used in such a place, the refrigerant leak, the performance of the unit decrease remarkably, and it cause the damage of parts of the unit.
Be very careful about unit transportation.
When carrying in unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make unit unstable, resulting in a fall of it. The unit should not be carried by only one person if it is more than 20 kg. It occasionally causes the damage of the unit and health to be impaired. Some units use PP bands for packing. Do not use any PP band for delivery purpose. It may cause the injury. Do not touch the heat exchanger fins with your bare hands. Doing so may cut your hands.
Do not operate the air conditioner without the eliminator set place.
Drain may drop into down flow supply duct.