Mitsubishi PQRY-P200YMF-C, PQRY-P250YMF-C, CMB-P104, CMB-P105, CMB-P106 Service Handbook

...
Page 1
Models PQRY-P200YMF-C, P250YMF-C
CMB-P104, P105, P106, P108, P1010, P1013, P1016V-E
Service Handbook
Page 2
Contents
1 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT .... 3
[1] Storage of Piping Material................................................................. 4
[2] Piping Machining............................................................................... 5
[3] Necessary Apparatus and Materials and Notes on Their Handling .. 6
[4] Brazing.............................................................................................. 7
[5] Airtightness Test................................................................................ 8
[6] Vacuuming ........................................................................................ 8
[7] Charging of Refrigerant..................................................................... 9
[8] Dryer ................................................................................................. 9
2 COMPONENT OF EQUIPMENT ........................................................... 10
[1] Appearance of Components ........................................................... 10
[2] Refrigerant Circuit Diagram and Thermal Sensor........................... 17
[3] Electrical Wiring Diagram................................................................ 19
[4] Standard Operation Data ................................................................ 27
[5] Function of Dip SW and Rotary SW................................................ 29
[6] External Input/Output Specifications............................................... 32
3 TEST RUN ............................................................................................. 33
[1] Before Test Run .............................................................................. 33
[2] Address setting ............................................................................... 37
[3] Test Run Method ............................................................................. 42
4 GROUPING REGISTRATION OF INDOOR UNITS WITH REMOTE
CONTROLLER....................................................................................... 43
5 CONTROL.............................................................................................. 49
[1] Control of Heat Source Unit ............................................................ 49
[2] Control box cooling system............................................................. 53
[3] Control of BC Controller.................................................................. 54
[4] Operation Flow Chart...................................................................... 55
[5] List of Major Component Functions ................................................ 61
[6] Resistance of Temperature Sensor................................................. 64
6 REFRIGERANT AMOUNT ADJUSTMENT ............................................ 65
[1] Refrigerant Amount and Operating Characteristics ........................ 65
[2] Adjustment and Judgement of Refrigerant Amount ........................ 65
7 TROUBLESHOOTING ........................................................................... 70
[1] Principal Parts................................................................................. 70
[2] BC Controller Disassembly Procedure ........................................... 98
[3] Self-diagnosis and Countermeasures Depending on the
Check Code Displayed ................................................................. 104
[4] LED Monitor Display ..................................................................... 127
8 PREPARATION, REPAIRS AND REFRIGERANT REFILLING
WHEN REPAIRING LEAKS ................................................................. 137
[1] Location of leaks: Extension piping or indoor units (when cooling) ... 137
[2] Location of leaks: Heat Source Unit (Cooling mode) .................... 137
[3] Location of Leaks: Extension Piping or Indoor Units
(Heating mode) ............................................................................. 138
[4] Location of Leaks: Heat Source Unit (when Heating) ................... 138
9 CHECK THE COMPOSITION OF THE REFRIGERANT..................... 139
0 DIFFERENCES BETWEEN THE PREVIOUS REFRIGERANT
AND THE NEW REFRIGERANT ......................................................... 141
[1] Chemical Characteristics .............................................................. 141
[2] Chances in Composition ............................................................... 141
[3] Pressure Characteristics............................................................... 142
A REFRIGERATOR OIL .......................................................................... 143
[1] Refrigerator Oil with HFC Based Refrigerants .............................. 143
[2] Influence of Contaminants ............................................................ 143
–1–
Page 3
Safety precautions
Before installation and electric work
Before installing the unit, make sure you read all the “Safety precautions”.
The “Safety precautions” provide very important points regarding safety. Make sure you follow them.
This equipment may not be applicable to EN61000-3-2: 1995 and EN61000-3-3: 1995.
This equipment may have an adverse effect on equipment on the same electrical supply system. Please report to or take consent by the supply
authority before connection to the system.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided. : Indicates that important instructions must be followed. : Indicates a part which must be grounded. : Indicates that caution should be taken with rotating parts.
(This symbol is displayed on the main unit label.) <Color: Y ellow>
: Indicates that the main switch must be turned off before
servicing. (This symbol is displayed on the main unit label.) <Color: Blue>
: Beware of electric shock (This symbol is displayed on the
main unit label.) <Color: Yellow>
: Beware of hot surface (This symbol is displayed on the
main unit label.) <Color: Yellow>
: Please pay attention to electric shock fully because
ELV
this is not Safety Extra Low-Voltage (SELV) circuit. And at servicing, please shut down the power supply
for both of Indoor Unit and Heat Source Unit.
Warning:
Carefully read the labels affixed to the main unit.
Warning:
• Ask the dealer or an authorized technician to install the air
conditioner.
- Improper installation by the user may result in water leakage, electric shock, or fire.
Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
• Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and
cause a fire.
• Prepare for typhoons and other strong winds and earth­quakes and install the unit at the specified place.
- Improper installation may cause the unit to topple and result
in injury.
• Always use an air cleaner, humidifier, electric heater, and other accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories.
Improper installation by the user may result in water leakage, electric shock, or fire.
• Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric
shock, or fire may result.
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame,
poisonous gases will be released.
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric
shock, or fire may result.
• Have all electric work done by a licensed electrician according to “Electric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock and fire may result.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed properly, dust or water
may enter the heat source unit and fire or electric shock may result.
• When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrigerant (R407C) specified on the unit.
- If a different refrigerant or air is mixed with the original
refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to
prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage,
electric shock, or fire may result.
• After completing installation work, make sure that refriger­ant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater,
stove, oven, or other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protec­tion devices.
- If the pressure switch, thermal switch, or other protection
device is shorted and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
• To dispose of this product, consult your dealer.
• The installer and system specialist shall secure safety against leakage according to local regulation or standards.
- Following standards may be applicable if local regulation are
not available.
• Pay a special attention to the place, such as a basement, etc. where refrigeration gas can stay, since refrigerant is heavier than the air.
2
Page 4
11
1 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT
11
Caution
Do not use the existing refrigerant piping.
• The old refrigerant and refrigerator oil in the existing piping contains a large amount of chlorine which may cause the refrigerator oil of the new unit to deterio­rate.
Use refrigerant piping made of **C1220T phospho­rus deoxidized copper as specified in the *JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
• Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil to deteriorate.
*JIS: Japanese Industrial Standard **: Comparable to CU-DHP (CUPROCLIMA), Cu-bl
(AFNOR), C12200 (ASTN), SF-Cu (DIN)
Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
• If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
Use a vacuum pump with a reverse flow check valve.
• The vacuum pump oil may flow back into the refriger­ant cycle and cause the refrigerator oil to deteriorate.
Do not use the following tools that have been used with conventional refrigerants. (Gauge manifold, charge hose, gas leak detector , re­verse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment.)
• If the conventional refrigerant and refrigerator oil are mixed in the R407C, the refrigerant may deterio­rated.
• If water is mixed in the R407C, the refrigerator oil may deteriorate.
• Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
Do not use a charging cylinder .
• Using a charging cylinder may cause the refrigerant to deteriorate.
Be especially careful when managing the tools.
• If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
• The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to seal the system.
• If gas refrigerant is used to seal the system, the com­position of the refrigerant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R407C.
• If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerator oil to de­teriorate.
If the refrigerant leaks, recover the refrigerant in the refrigerant cycle, then recharge the cycle with the specified amount of the liquid refrigerant indicated on the air conditioner.
• Since R407C is a nonazeotropic refrigerant, if addi­tionally charged when the refrigerant leaked, the com­position of the refrigerant in the refrigerant cycle will change and result in a drop in performance or abnor­mal stopping.
–3–
Page 5
[1] Storage of Piping Material
(1) Storage location
Store the pipes to be used indoors. (Warehouse at site or owners warehouse) Storing them outdoors may cause dirt, waste, or water to infiltrate.
(2) Pipe sealing before storage
Both ends of the pipes should be sealed until immediately before brazing. Wrap elbows and Ts in plastic bags for storage.
* The new refrigerator oil is 10 times more hygroscopic than the conventional refrigerator oil (such as Suniso). Water
infiltration in the refrigerant circuit may deteriorate the oil or cause a compressor failure. Piping materials must be stored with more care than with the conventional refrigerant pipes.
–4–
Page 6
[2] Piping Machining
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
Use only the necessary minimum quantity of oil !
Reason :
1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside.
Notes :
Introducing a great quantity of mineral oil into the refrigerant circuit may also cause a compressor failure.
Do not use oils other than ester oil, ether oil or alkylbenzene.
5
Page 7
[3] Necessary Apparatus and Materials and Notes on Their Handling
The following tools should be marked as dedicated tools for R407C.
<<Comparison of apparatus and materials used for R407C and for R22>>
Apparatus Used Use R22 R407C
Gauge manifold Evacuating, refrigerant filling Current product Charging hose Operation check Current product Charging cylinder Refrigerant charging Current product Do not use. Gas leakage detector Gas leakage check Current product Shared with R134a Refrigerant collector Refrigerant collection R22 For R407C use only Refrigerant cylinder Refrigerant filling R22
Identification of dedi­cated use for R407C :Record refrigerant
name and put brown belt on upper part of cylinder.
Vacuum pump Vacuum drying Current product
Vacuum pump with a check valve Current product Flare tool Flaring of pipes Current product Bender Bending of pipes Current product Application oil Applied to flared parts Current product
Torque wrench Tightening of flare nuts Current product Pipe cutter Cutting of pipes Current product Welder and nitrogen cylinder Welding of pipes Current product Refrigerant charging meter Refrigerant charging Current product Vacuum gauge Checking the vacuum degree Current product
Symbols :
Tools for R407C must be handled with more care than those for conventional refrigerants. They must not come into contact with any water or dirt.
To be used for R407C only. Can also be used for conventional refrigerants.
Can be used by attaching an adapter with a check valve.
Ester oil or Ether oil or Alkybenzene (Small amount)
–6–
Page 8
[4] Brazing
No changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt, etc.) does not enter the refrigerant circuit.
Example : Inner state of brazed section
When non-oxide brazing was not used When non-oxide brazing was used
Items to be strictly observed :
1. Do not conduct refrigerant piping work outdoors on a rainy day.
2. Apply non-oxide brazing.
3. Use a brazing material (Bcup-3) which requires no flux when brazing between copper pipes or between a copper pipe and copper coupling.
4. If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends of them.
Reasons :
1. The new refrigerant oil is 10 times more hygroscopic than the conventional oil. The probability of a machine failure if water infiltrates is higher than with conventional refrigerant oil.
2. A flux generally contains chlorine. A residual flux in the refrigerant circuit may generate sludge.
Note :
Commercially available antioxidants may have adverse effects on the equipment due to its residue, etc. When applying non-oxide brazing, use nitrogen.
–7–
Page 9
[5] Airtightness Test
No changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407C leakage.
Halide torch R22 leakage detector
Items to be strictly observed :
1. Pressurize the equipment with nitrogen up to the design pressure and then judge the equipments airtightness, taking temperature variations into account.
2. When investigating leakage locations using a refrigerant, be sure to use R407C.
3. Ensure that R407C is in a liquid state when charging.
Reasons :
1. Use of oxygen as the pressurized gas may cause an explosion.
2. Charging with R407C gas will lead the composition of the remaining refrigerant in the cylinder to change and this refrigerant can then not be used.
Note :
A leakage detector for R407C is sold commercially and it should be purchased.
[6] Vacuuming
1. Vacuum pump with check valve A vacuum pump with a check valve is required to prevent the vacuum pump oil from flowing back into the refrigerant circuit when the vacuum pump power is turned off (power failure). It is also possible to attach a check valve to the actual vacuum pump afterwards.
2. Standard degree of vacuum for the vacuum pump Use a pump which reaches 0.5 Torr (500 MICRON) or below after 5 minutes of operation. In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the vacuum pump is not properly maintained, the degree of vacuum may be too low.
3. Required accuracy of the vacuum gauge Use a vacuum gauge that can measure up to 5 Torr. Do not use a general gauge manifold since it cannot measure a vacuum of 5 Torr.
4. Evacuating time
Evacuate the equipment for 1 hour after 755 mmHg (5 Torr) has been reached.
After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.
5. Operating procedure when the vacuum pump is stopped In order to prevent a backflow of the vacuum pump oil, open the relief valve on the vacuum pump side or loosen the charge hose to drawn in air before stopping operation. The same operating procedure should be used when using a vacuum pump with a check valve.
–8–
Page 10
[7] Charging of Refrigerant
R407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.
For a cylinder with a syphon attached For a cylinder without a syphon attached
Cylin-
Cylin-
der
Cylinder color identification R407C-brown Charged with liquid refrigerant
der
Valve
Liquid
Valve
Liquid
Reasons :
1. R407C is a mixture of 3 refrigerants, each with a different evaporation temperature. Therefore, if the equipment is charged with R407C gas, then the refrigerant whose evaporation temperature is closest to the outside temperature is charged first while the rest of refrigerants remain in the cylinder.
Note :
In the case of a cylinder with a syphon, liquid R407C is charged without turning the cylinder up side down. Check the type of cylinder before charging.
[8] Dryer
1. Replace the dryer when the refrigerant circuit is opened (Ex. Change the compressor, full gas leakage). Be sure to replace the dryer with a CITY MULTI Series WR2 (PQRY) (For use with R407C).
If any other product is used, the unit will be damaged.
2. Opening the refrigerant circuit after changing to a new dryer is less than 1 hour. The replacement of the dryer should be the last operation performed.
–9–
Page 11
22
2 COMPONENT OF EQUIPMENT
22
[1] Appearance of Components
Heat source unit
Heatexchanger
Control Box
4-way Valve
SV Block
Compressor
CV Block
Drier
–10–
Accumulator
Page 12
Control Box
Front View
INV board
Transformer (T01)
RELAY board
MAIN board
Inner View
T erminal block TB8 UNIT ON/OFF, Pump inter lock
Intelligent Power
Module (IPM)
G/A board
Cooling fan (MF1)
T erminal block TB1A Power Source
DC reactor (DCL)
Terminal block TB3 Transmission
T erminal block TB7 Transmission (Centralized Control)
Choke coil (L2)
Fuse (F3)
Capacitor (C2, C3)
Diode
stack
(DS)
Fuse (F5, F6)
Magnetic Contactor (52C)
–11–
Noise Filter
SNB board (Back Side)
Page 13
MAIN board
CNTR CNVCC4 CNS1 CNS2 CN40 CN41
Power source for control (5V)
CNVCC3
Power source for control
1-2 30 V, 1-3 30 V, 4-6 12 V, 5-6 5 V
CN51
CN3D
LD1 Service LED
SW3SW4CN20
SWU1SWU2
SW1SW2
–12–
Page 14
INV board
CNVDC 1-4 DC-560V
CN15V2 Power supply for IPM control
CNR
CN52C Control for 52C
CNFAN Control for MF1
CNAC2 Power source
1 L2 3 N 5 G
SW1
CNRS2 Serial transmission to MAIN board
CNVCC4 Power supply (5V)
CNL2 Choke coil
CNVCC2 Power supply
1-2 30V, 1-3 30V 4-6 12V, 5-6 5V
CNDR2 Out put to G/A board
CNTH
CNACCT
–13–
Page 15
RELAY board
SNB board
–14–
Page 16
BC controller
BC board
CNTR
CN02 M-NET transmission
CN03
CN12 Power supply
1 EARTH 3 N 5 L
SW4 SW2 SW1
–15–
Page 17
RELAY 10 board
RELAY 4 board
–16–
Page 18
[2] Refrigerant Circuit Diagram and Thermal Sensor
: Strainer
: Check valve
: Service port
: Solenoid valve
: Thermal sensor
: Capillary
: Liner valve expansion
: Ball valve
ST
CV
SP
SV
LEV
TH
CP
BV
Heat source unit
ST8
CV11
CV7
SV72
TH6
SV71
BV1
CV3
CV2
CV5
CV4
ST1
CV6
BV2
Orifice
CV10
CV9
CV8
Solenoid Valv es
Distributor
Block
SV6
SV4
SV3
SV5
Water heat exchanger
(Double coil type)
Water
Circulating
ST7d
ST7b ST7cST7a
Check V alves Block
SLEV
CP1
CJ2
SV1
ST6
SV2
TH1
Comp
Accumulator
TH10
ST4
THINV
Low pressure sensor
Air Heat Exchanger
TH2
CP4
LEV2
Drier
TH9
4way valve
SV73
High pressure sensor
SP1
ST2
ST5
Oil
separator
CV1
High pressure
Switch
–17–
Page 19
: Solenoid valve
: Orifice
: Capillary
: Check valve
: Thermal sensor
: Strainer
SP : Service port
ACC : Accumulator
BC controller, Indoor unit
Indoor
units
SVC
Valves Block
SVA
SVB
TH23
TH21
TH11
TH22
PS1
LEV
LEV1
PS3
BC controller
CMB-P104V-E
Gas/liquid separator
TH12
TH15
LEV3
TH16
–18–
Page 20
<ELECTRICAL WIRING DIAGRAM>
FB1
SNB board
EARTH
BOX BODY
BOX BODY
8A F
600VAC
F5
8A F
600VAC
F6
L3L1L2
Green
ACCT
-U
PQRY-P250YMF-C
PQRY-P200YMF-C 30A
50A
no fuse breaker
(4P)
CNACCT
4
(14P)
CN15V1
(9P)
CNDR1
IPM
FB2
(G/A board)
Gate amp board
N
P
WVU
432
1
5
White Gray
Black
Purple
Orange
Orange
Yellow
987612345 14131110 12
987612345
987612345
987612341234
1234
5 14131110 12
(4P)
CNDC1
(2P)
CNE
Refer to the service handbook
about the switch operations.
S
M2
M1
L1
1
PE
R6
31422
3
123
5
1
F01
250VAC
2A F
13
CN20
(3P)
221
CNVCC4
(2P)
CNVCC3
(6P)
CNVCC2
(6P)
CNVCC4
(2P)
31
CNS1
(2P)
CN51
(5P)
CNAC2
(5P)
2
CNS2
(3P)
CNAC3
(4P)
1
CNX10
(3P)
CNR
(3P)
2
CN52C
(3P)
3
CNVDC
CNTH
(2P)
12V
5 : SW3-3 OFF : water freeze signal
4 : Compressor ON/OFF
N
L3
Power source
3N~
380/400/415V
50/60Hz
(MAIN board)
TB1A
L2
L1NL3
L2
F1
250VAC
2A F
PE
White
Red
Black
Blue
White
Red
Black
Blue
White
Red
Black
Blue
Green/
Yellow
Connect to
Indoor and
remote
controller
TB3
M1
M2
TB7
~
DS
~ –
~
+
ZNR4
C1
R5
R1
52C
+
+
DCL
C2
C3
R2
R3
T01
F3
250VAC
1A F
CNTR1
White
V
Red
Black
3
21
21213212132
23412
1
2
1
7654321
7654321
5
6
23415
6
52C
X02
X01
X10
CNRS3
(7P)
CNRS2
(7P)
CNFAN
(3P)
THHS
CNTR
(3P)
CN15V2
(14P)
CNDR2
(9P)(4P)
CNL2
(2P)
CN30V
(2P)
MF1
R7
L2
Power circuit board
(INV board)
Controller Box
Red Brown
Brown
Black
White
Red
Blue
Control circuit board
TB1B
NF
L1L2L3
N
L1L2L3
N
L1L2L3
N
Terminal
Block
Terminal
Block
Noise
Filter
Diode
stack
BOX BODY
BOX BODY
12
BOX BODY
BOX BODY
ACCT
-W
Inverter
U
W
MC1
Motor
(Compressor)
(4P)
CNPW
432
1
432
1
123
4
CNAC4
(4P)
123
4
(9P)
CN81
56789
X21
X22
X23
SV72
SV71
SV73
135
7
(7P)
CN83
X25
432
1
TB8
63PW
CNOUT2
(6P)
12345
6
12345
6
AC1AC4
(to CNAC3)
(3P)
CN3D
231
TH6
THINV
321321
Red White Black
Red White Black
TH1
63LS63HS
21
LEV2SLEV
(5P)
CNLV2
(5P)
CNLV1
54321543215438762132121
(3P)
CNL
(3P)
CNH
(2P)
CN01
(8P)
CN02
(3P)
CN03
(2P)
CN06
21
(2P)
CN09
21
(2P)
CN12
321321
26W
SV5
X10
SV6
SV3
SV4
21S4
SV2
63H
CH1
SV1
(to CNAC4)
AC4
AC1
412
3
X01
X04
X05
(3P)
CN32
(3P)
CN33
(6P)
CN34
(6P)
CN36
(6P)
CN37
(3P)
CN38
X02
32132
1
32165
4
32165
4
32165
4
32154
X07
X06
123
X09
X08
CNRT1
(5P)
(4P)
CN63PW
(6P)
CNOUT1
detection
circuit
detection
circuit
circuit
detection
DEMAND
RELAY board
Freeze protect
switch
High pressure
switch
Crank case heater
(Compressor)
Unit ON/OFF
Pump interlock
TH9TH10 TH2
ON
: trouble signal
[3] Electrical Wiring Diagram
PQRY-P200·250YMF-C
19
Page 21
21S4
SV1
SV2
SV3
SV4
SV72SV71SV5
SV6
SV73
SSR
<Operation of self-diagnosis switch (SW1) and LED display>
<LED display>
Display
Relay output
display
(Lighting)
Check display1
(Blinking)
(at factory shipment)
Display at LED lighting (blinking) Remarks SW1 operation
FLAG1 FLAG2 FLAG3 FLAG4 FLAG5 FLAG6 FLAG7 FLAG8
Display the address and error code by turns
Always
lighting
FLAG8 always lights
at microcomputer
power ON
During
compressor
run
Crankcase
heater
51
1102
FLAG1
FLAG2
FLAG3
FLAG4
FLAG8
FLAG7
FLAG6
FLAG5
ON:1
OFF:0
1 2 3 4 5 6 7 8 9 10
ON:1
OFF:0
1 2 3 4 5 6 7 8 9 10
* please refer to the service handbook about other switch settings of LED display.
LD1
INV board
MAIN board
RELAY
board
TB8
TB1A
TB3
TB7
T01
G/A board
IPM
C1
ZNR4
THHS
DCL
ACCT
R2
C2
C3
R3
NF
52C
MF1
L2
R5
R1
R7
F3
R6
DS
F6
F5
TB1B
TB8
TB3
TB7
TB1A
SNB
board
FB1~2
Ferrite core
Earth terminal
Aux. relay
L2
Discharge pipe temp. detect
Saturation evapo. temp. detect
Thermistor
TH2
TH1
TH6
OA temp. detect
(Heat exchanger capacity control)
Solenoid valve
(Heat exchanger capacity control)
(Heat exchanger for inverter)
Solenoid valve
SV3~6
High pressure sensor
Low pressure sensor63LS
63HS
SLEV
Choke coil (Transmission)
Intelligent power module
IPM
Electronic expansion valve
Electronic expansion valve (Oil return)
LEV2
Fan motor (Radiator panel)
SV1, SV2 Solenoid valve (Discharge-suction bypass)
4-way valve21S4
Varistor
NameSymbol
DCL
(Power factor improvement)
< Symbol explanation >
DC reactor
ACCT-U, W
Current Sensor
ZNR4
(Inverter main circuit)
52C
MF1
Magnetic contactor
X1~10
SV71~73
X21~25
THINV
TH10
TH9
Compressor shell temp.
High pressure liquid temp.
THHS
Radiator panel temp. detect
heat exchanger for inverter
Outlet temp. detect of
< Controller box internal layout >
(Upside) (Underside)
< Unit internal layout >
SV73
SV1
(Upside)
(Underside)
SEPARATOR
BOX
CONTROLLER
63LS
63HS
TH10
TH1
63H
SV2
SLEV
LEV2
TH9
ACCUMULATOR
MC
OIL
SV71SV72
INVERTER
26W
21S4
TH2
THINV
TH6
SV6
SV5
SV4
SV3
PQRY-P200·250YMF-C
20
Page 22
Symbol explanation
PE
1
2
3
1
2
3
EARTH
Terminal block
(for Transmission)
TB02
Terminal block
(for power source)
TB01
NameSymbol
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Expansion valve
Thermister sensor
Transformer
NameSymbol
SV1 5A
SV1 5B
SV1 5C
SVM
TR
TH11 16
LEV1,3
PS1,3 Pressure sensor
Transmission line
Shield wire
/N 220V 240V 50Hz
Power source
BC Board
LEV1
TB01
16
15
2
1
2
1
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
SV1C
SV1A
SV1B
}
3
1
CNTR
CN02
CN12
153
31
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
TR
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X21
}
DC 30V
654321654321
LEV3
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
12321
CN03
CN13
CN10
CN11
CN07 CN05
L
N
TH11
TH12
TH15
TH16
PS1
PS3
20 22V
TB02
M2
M1
CN26
CN27
CN28
CN29
TB01
220 240V
SV5C
SV5A
SV5B
7
5
3
1
X10
X9
X34
CN30
SVM
CN36
1
1
1
1
Note:1.TB02 is terminal block for transmission.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
CMB-P105V-E
21
Page 23
PE
1
2
3
1
2
3
EARTH
Transmission line
Shield wire
/N 220V 240V 50Hz
Power source
BC Board
31
LEV1
TB01
SV6B SV6A SV6C
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
SVM
SV1C
SV1A
SV1B
}
4321
1234
CN38
3
1
CNTR
CN02
CN12
153
31
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
TR
3
CNVCC1
12
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
}
DC 30V
654321654321
LEV3
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
12321
CN51 CN50
CNOUT 1
CNOUT 3
CN03
CN13
CN10
CN11
CN07 CN05
L
N
TH11
TH12
TH15
TH16
PS1
PS3
20 22V
TB02
M2
M1
CN26
CN27
CN28
CN29
CN30
CN31
TB01
220 240V
CN36
Symbol explanation
Terminal block
(for Transmission)
TB02
Terminal block
(for power source)
TB01
NameSymbol
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Expansion valve
Thermister sensor
Transformer
NameSymbol
SV1 6A
SV1 6B
SV1 6C
SVM
TR
TH11 16
LEV1,3
PS1,3 Pressure sensor
1
1
1
1
7654321123456
Note:1.TB02 is terminal block for transmission.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
CMB-P106V-E
22
Page 24
PE
1
2
3
1
2
3
EARTH
}
Power source
}}
L
N
Power source
/N 220V 240V 50Hz
Transmission line
Shield wire
SVM
BC Board
CN38
1
3
1
CNTR
CN50
CN51
7654321123456
CN02
CN12
153
31
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
3
TR
3
CNVCC1
12
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
}
DC 30V
654321654321
LEV3 LEV1
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
123
21
CN03
CN13
CN10
CN11
CN07 CN05
CN36
TH11
TH12
TH15
TH16
PS1
PS3
20 22V
TB02
M2
M1
CN26
CN27
CN28
CN29
CN30
CN31
TB01
220 240V
LEV1
7654321
TB01
SV6B SV6A
SV6C
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
RELAY4 Board
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
CN32
CN33
CN39
3
1
SV7C
SV7A
SV7B
SV8C
SV8A
SV8B
SV1C
SV1A
SV1B
X14
X13
X36
X37 X15 X16
98765432116 15 1011121314
12345678910111213141516
CN52
75317531
Symbol explanation
Terminal block
(for Transmission)
TB02
Terminal block
(for power source)
TB01
NameSymbol
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Expansion valve
Thermister sensor
Transformer
NameSymbol
SV1 8A
SV1 8B
SV1 8C
SVM
TR
TH11 16
LEV1,3
PS1,3 Pressure sensor
CNOUT 1
CNOUT 3
1
Note:1.TB02 is terminal block for transmission.
1
1
1
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
CMB-P108V-E
23
Page 25
PE
1
2
3
1
2
3
EARTH
}
Power source
}}
L
N
Power source
/N 220V 240V 50Hz
Transmission line
Shield wire
SV10B SV10A SV10C
SV9B SV9A SV9C
BC Board
CN38
1
3
1
CNTR
CN50
CN51
7654321123456
CN02
CN12
153
31
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
7
5
3
1
3
TR
3
CNVCC1
12
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
}
DC 30V
654321654321
LEV3 LEV1
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
123
21
CN03
CN13
CN10
CN11
CN07 CN05
CN36
TH11
TH12
TH15
TH16
PS1
PS3
20 22V
TB02
M2
M1
CN26
CN27
CN28
CN29
CN30
CN31
TB01
220 240V
LEV1
7654321123456
CN35
TB01
SV6B SV6A SV6C
SVM
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
RELAY4 Board
SV5C
SV5A
SV5B
SV4B
SV4A
SV4C
SV3B
SV3A
SV3C
SV2B
SV2A
SV2C
CN32
CN33
CN34
CN39
3
1
SV7C
SV7A
SV7B
SV8C
SV8A
SV8B
SV1C
SV1A
SV1B
X14
X13
X36
X37 X15 X16
98765432116 15 1011121314
12345678910111213141516
X18
X17
X38
X39 X19 X20
CN52CN53
5731753175317533 31
Symbol explanation
Terminal block
(for Transmission)
TB02
Terminal block
(for power source)
TB01
NameSymbol
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Expansion valve
Thermister sensor
Transformer
NameSymbol
SV1 10A
SV1 10B
SV1 10C
SVM
TR
TH11 16
LEV1,3
PS1,3 Pressure sensor
CNOUT 1
CNOUT 3
1
1
1
1
Note:1.TB02 is terminal block for transmission.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
CMB-P1010V-E
24
Page 26
PE
EARTH
3
2
1
3
2
1
TB02
TB01
Name
Symbol
Terminal block
(for Transmission)
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Terminal block
(for power source)
Pressure sensor
Expansion valve
Thermister sensor
Transformer
Name
SV1~13A
SV1~13B
SV1~13C
SVM
Symbol
TR
TH11~16
LEV1,3
PS1,3
M1
M2
DC 30V
}
Shield wire
Transmission line
Power source
}
L
N
Power source
~/N 220V~240V 50Hz
RELAY10
Board
BC Board
CN39
13
654321 1234567
CN51
CN50
135
CN12
13
CNOUT3
CNOUT1
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
7
5
3
1
1571571357
13
21
CNVCC2
3
CN42
X46
X47
X48
1
2
3
8
7
6
5
4
3
2
1
4
CNOUT2
CNOUT4
CN41
CN40
X41
X44
X40
X43
X42
X45
X20
X18
X19
X17
X39
X38
3
CNVCC1
12
X16
X15
X37
X36 X13 X14
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
6 5432
1
6 5432
1
LEV3 LEV1
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
12321
CN03
CN02
CN13
CN10
CN11
CN07 CN05
33
CN34
CN33
1357
CN32
TH11
TH12
TH15
TH16
TR
TB02
CN38
CN26
CN27
CN28
CN29
CN30
CN31
TB01
CN35
3
1
CNTR
4
1
2
3
4
5
6
7
8
3
2
1
SV1B
SV1A
SV1C
SV2C
SV2A
SV2B
SV3C
SV3A
SV3B
SV4C
SV4A
SV4B
SV5B
SV5A
SV5C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SV9C
SV9A
SV9B
SV10C
SV10A
SV10B
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
14 13 12 11 101516 123456789
SV8B SV8A SV8C
SV7B SV7A SV7C
SVM
SV6C
SV6A
SV6B
SV11C
SV11A
SV11B
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
SV12C
SV12A
SV12B
SV13C
SV13A
SV13B
PS1
PS3
Note : 1. TB02 is transmission terminal block.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
20 22V 220 240V
CN36
1
1
1
1
CMB-P1013V-E
25
Page 27
PE
EARTH
3
2
1
3
2
1
TB02
TB01
Name
Symbol
Terminal block
(for Transmission)
Solenoid valve
Solenoid valve
Solenoid valve
Solenoid valve
Terminal block
(for power source)
Pressure sensor
Expansion valve
Thermister sensor
Transformer
Name
SV1~16A
SV1~16B
SV1~16C
SVM
Symbol
TR
TH11~16
LEV1,3
PS1,3
M1
M2
DC 30V
}
Shield wire
Transmission line
Power source
}
L
N
Power source
~/N 220V~240V 50Hz
CN39
13
654321 1234567
CN51
CN50
135
CN12
13
CNOUT3
CNOUT1
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
1
3
5
7
7
5
3
1
1571571357
13
21
CNVCC2
3
CN42
X46
X47
X48
1
2
3
8
7
6
5
4
3
2
1
4
CNOUT2
CNOUT4
CN41
CN40
X41
X44
X40
X43
X42
X45
X20
X18
X19
X17
X39
X38
3
CNVCC1
12
X16
X15
X37
X36 X13 X14
X2
X1
X30
X4
X3
X31
X6
X5
X32
X8
X7
X33
X10
X9
X34
X12
X11
X35
X21
6 5432
1
6 5432
1
LEV3 LEV1
1
2
3
CNP1
1
2
3
CNP3
2
1
1
2
3
4
5
6
7
8
4
3
2
1
12321
CN03
CN02
CN13
CN10
CN11
CN07 CN05
33
CN34
CN33
1357
CN32
TH11
TH12
TH15
TH16
TR
TB02
CN38
CN26
CN27
CN28
CN29
CN30
CN31
TB01
CN35
3
1
CNTR
4
1
2
3
4
5
6
7
8
3
2
1
SV1B
SV1A
SV1C
SV2C
SV2A
SV2B
SV3C
SV3A
SV3B
SV4C
SV4A
SV4B
SV5B
SV5A
SV5C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SV9C
SV9A
SV9B
SV10C
SV10A
SV10B
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
14 13 12 11 101516 123456789
SV8B SV8A SV8C
SV7B SV7A SV7C
SVM
SV6C
SV6A
SV6B
SV11C
SV11A
SV11B
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
SV12C
SV12A
SV12B
SV13C
SV13A
SV13B
PS1
PS3
1
1
1
1
Note : 1. TB02 is transmission terminal block.
Never connect power line to it.
2.
1
:SVM is not built in depending on models.
1
2
2
1
1
3
5
7
1
3
5
7
1
3
5
7
X57
X53
X52
X56
X55
CN45
CN44
CN43
X50
SV14C
SV14A
SV14B
SV15A
SV15B
SV16C
SV16A
SV16B
SV15C
X54
X51
X49
RELAY10
Board
BC Board
20 22V 220 240V
CN36
CMB-P1016V-E
26
Page 28
[4] Standard Operation Data
1 Cooling operation
Items
Power source Ambient temp.
Indoor
Circulated water temp. (Intet)
Quantity
Indoor unit
Quantity in operation Model Main pipe
Condition
Piping
Branch pipe
Total piping length Indoor unit fan notch Refrigerant volume
Compressor volts / Frequency
Heat source unit
Heat source unit
V/Hz
DB/WB
°C
Q’ty
m
kg
V
V/Hz
A
PQRY-P200YMF-C PQRY-P250YMF-C
380-415V/50Hz • 60Hz 380-415V/50Hz • 60Hz
27.0/19.0 27.0/19.0 30 30
44 44
63 63 50 25 125 40 63 25
55
55555555
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
11.4 12.2
380 415 380 415
270/77 270/77 340/95 340/95
14.0 12.8 18.8 17.2 Indoor unit BC controller (1, 3) Oil return
LEV opening
High pressure/Low pressure
BC controller liquid/Intermediate
Pressure
Discharge (TH1)
Accumulator
Heat source
Suction (Comp)
unit
CS circuit (TH2) Shell bottom (Comp)
Sectional temperature
Indoor unit
LEV inlet Heat exchanger outlet
αOC
Inlet Outlet
Pulse
kg/cm
(MPa)
˚C
330 460 430 300 410 330 460 300
2000 240 2000 260
180 330
22.0/5.3 21.5/5.0
2
G
(2.20/0.52) (2.15/0.50)
20.9/20.9 20.4/20.4
(2.09/2.09) (2.04/2.04)
101 99.0
77 10 10 12 12
4.9 4.3 70 78 26 30 15 15
0.23 0.23
–27–
Page 29
2 Heating operation
Items
Power source Ambient temp. C
Circulated water temp.
Indoor
Quantity
Indoor unit
Quantity in operation Model Main pipe
Condition
Piping
Branch pipe
Total piping length Indoor unit fan notch Refrigerant volume
Compressor volts/Frequency
Heat source unit total current
Heat source unit
V/Hz
DB/WB
°C
Qty
m
kg
V
V/Hz
A
PQRY-P200YMF-C PQRY-P250YMF-C
380-415V/50Hz 60Hz 380-415V/50Hz 60Hz
20.0/– 20.0/– 20 20
44 44
63 63 50 25 125 40 63 25
55
55555555
25 25
Hi Hi Hi Hi Hi Hi Hi Hi
11.4 12.2
380 415 380 415
250/75 250/75 330/93 330/93
13.1 12.0 16.1 14.8 Indoor unit BC controller (1, 3) Oil return
LEV opening
High pressure/Low pressure
BC controller liquid/Intermediate
Pressure
Discharge (TH1)
Heat
Accumulator
source unit
Suction (Comp) CS circuit Shell bottom (Comp)
Sectional temperature
Indoor unit
LEV inlet Heat exchanger outlet
αOC
Inlet Outlet
(TH2)
Pulse
kg/cm
(MPa)
˚C
600 950 750 400 750 600 950 400
60 600 60 850
115 115
22.0/5.6 22.0/5.4
2
G
(2.20/0.56) (2.20/0.54)
21.0/18.0 21.0/18.0
(2.10/1.80) (2.10/1.80)
75 79
1 14 21 1
75 55 60 38 40 80 85
0.28 0.28
–28–
Page 30
[5] Function of Dip SW and Rotary SW
(1) Heat source unit
Switch Function
1~2
SWU SW1
SW2
SW3
SW4
Unit address setting
1~8
For self diagnosis/ operation monitoring
9~10
1
Centralized control switch
2
Deletion of connection information.
3
Deletion of error history.
4
Adjustment of refrigerant Volume
5 6 7
Operation ON signal output switching Relay contact output TB8-1,2
8
Disregard pump interlock trouble.
9
10
SW3-2 Function valid/
1
invalid Indoor unit test operation
2
CN51-3,5 Output switching
3
Freeze prevention operation
4
Target Te (α) at cooling-
5
only Pump down operation
6
Target Tc (High pressure)
7
at heating 8 9
10
1
SW4-2 function valid/
Invalid 2
Configuration compensa-
tion value 3
Models
Function according to switch operation Switch set timing
When off When on When off When on
Set on 51~100 with the dial switch.
LED monitering display
Centralized control not connected. Storing of refrigeration system connection information.
Ordinary control
– –
The relay closes during compressor operation.
Normal
– –
SW3-2 Function invalid
Stop all indoor units.
Water heat exchanger freeze prevention signal Normal
– –
Changes as shown below by on off change 0% 3% 6% 9% 12% –6% –3% 0%
– –
– –
2˚C
Invalid
50˚C
– –
Model P200
Invalid
Centralized control connected. Deletion of refrigeration system connection information. Deletion
Refrigerant volume adjustment operation.
The relay closes during reception of the cooling or the heating operation signal from the controller. (Note: It is output even if the thermostat is OFF (when the compressor is stopped).)
Disregard trouble
SW3-2 Function valid
All indoor units test operation ON. Heat source unit abnormal output Freeze prevention operation*
– –
– –
5˚C
Valid
53˚C
– –
Model P250
Valid
Before power is turned on. During normal operation when power is on. Should be set on OFF. Before power is turned on.
Before power is turned on.
During normal operation when power is on.
During normal operation when power is on.
At all times
At all times
During normal operation when power is on. When SW3-1 is ON after power is turned on. At all times
At all times At all times
During Comp stop (only when power changes from OFF ON) During normal operation when power is on.
When switching on the power. During normal operation when power is on. When SW4-1 in ON.
Invalid 2 hours after compressor starts.
– –
– –
– –
Note:
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.
* Freeze prevention operation
When the water temp. (TH6) below less 5˚C during compressor is stopping, the compressor starts to run with coolingmode to prevent the water freeze.
–29–
Page 31
(2) Indoor unit
ON
OFF
ON
OFF
ON
OFF
DIP SW1, 3
Switch SW name
1
Room temp. sensor position
2
Clogged filter detect.
3
Filter duration
4
OA intake
5
Remote display select.
SW1
Humidifier control
6
Heating thermo. OFF airflow
7
Heating thermo. OFF airflow
8
Power failure automatic
9
return
10
Power source start/stop
1
Model selection
Cooling capacity saving for PKFY-P. VAM, effective/ineffective
SW3
2
Louver
3
Vane
4
Vane swing function
5
Vane horizontal angle
6
Vane angle set for cooling
7
Heating 4deg up
8
Operation by SW
OFF ON OFF ON
Indoor unit inlet
None 100h
Ineffective
Fan output display
At stationary heating
Very low speed
SW1-7 setting
Ineffective
Ineffective
Heat pump
None
None None
1st setting
Down blow B, C
Effective
Built in remote controller
Provided
2500h
Effective
Thermo. ON signal display
Always at heat
Low speed
Set airflow
Effective
Effective
Cool.only
Provided
Provided Provided
2nd setting
Horizontal
Ineffective
Switch set timing
At unit stopping
(at remote
controller OFF)
Remarks
Always ineffective for PKFY-P.VAM
Not provided for PKFY-P.VAM Provided for PLFY-P.VGM (ON) setting
Always down blow B,C for PKFY-P.VAM Horizontal (ON) setting for PLFY-P.VLMD
Ineffective (ON) setting for floor standing
Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the
table below.)
PDFY-P
PFFY-P PCFY-P PKFY-P
VM-AONVLRM-A, VLEM-A
OFF
OFF
ON OFF
VGM-AONVAM-A VGM-A
OFF
OFF
OFF
ON
ON OFF ON
Switch
SW1
SW3
Model
3 6 7 3 4 6 8
VBM-A
OFF OFF
ON
OFF
PLFY-P
VLMD-A
ON
OFF
ON
OFFONON
VKM-A
VML-A VMH-A
OFF ON
ON
OFF
PEFY-P 20~80VMM-A
OFF
ON
OFF ON
100~140VMM-A
OFF OFF
Note 2: The Dip SW setting is only effective during unit stopping (remote controller OFF) for SW1, 2, 3 and 4 commonly
and the power source is not required to reset.)
3: When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat of OFF.
Setting of DIP SW2
Model P20 P25 P32 P40 P50 P63 Capacity (model name) code
SW2 setting
45 681013
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
Model P71 P80 P100 P125 P140 P200 P250 Capacity (model name) code
SW2 setting
14 16 20 25 28 40 50
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
–30–
Page 32
Setting of DIP SW4 Setting of DIP SW5
3
1
2
Model Circuit board used
PMFY-P-VBM-A PLFY-P-VLMD-A PDFY-P20 ~ 80VM-A PLFY-P40 ~ 63VKM-A PLFY-P80 ~ 125VKM-A PCFY-P-VGM-A PKFY-P-VGM-A PKFY-P-VAM-A PEFY-P20 ~ 80VMM-A PFFY -P-VLEM-A, P-VLRM-A PEFY-P20 ~ 32VML-A PEFY-P40 ~ 140VMH-A PEHY-P200·250VMH-A PDFY-P100·125VM-A PEFY-P100 ~ 140VMM-A
Phase control
Relay selection
1234
ON OFF ON OFF
––––
ON OFF ON OFF
OFF OFF OFF ON
ON OFF OFF ON OFF ON OFF ON OFF OFF ON ON
––––
ON ON OFF OFF OFF OFF OFF
ON ON ON – OFF OFF OFF
ON OFF OFF – OFF OFF ON
ON ON ON OFF
SW4
220V 240V
Switch Function Operation by switch Switch set timing
(PLFY-P-VKM-A) (PCFY-P-VGM-A)
Ceiling height 3 3.5 m 2 2.8 m 1 2.3 m
Always after powering
SWA
Ceiling height setting
3 2 1
*The ceiling
height is changed by SWB setting.
(PDFY-P20 ~ 80VM-A, PEFY-P20 ~ 80VMM-A)
SWA
External static pressure setting
3 2 1
*
For other models, change the setting of static pressure by replacing the connector.
100Pa
50Pa 30Pa
(PLFY-P-VLMD-A)
SWA
SWB
For options
Setting of air outlet opening
3
*As this switch is used by interlocking with SWC,
2 1
refer to the item of SWC for detail.
(PLFY-P-VKM-A)
2-way 3-way 4-way
SWA
SWB
123
2-way 3.5 m 3.8 m 3.8 m 3-way 3.0 m 3.3 m 3.5 m 4-way 2.7 m 3.0 m 3.5 m
(PLFY-P-VKM-A, PCFY-P-VGM-A, PKFY-P-VGM-A, PDFY-P-VM-A)
SWC
Airflow control
Option
Standard
*Set to the option to install the high efficiency
filter
(3) BC controller unit
DIP SW4
Switch Function
SW4
1 Models V-E type V-D type
2~8 ––
Function according to switch operation
When off When on
*If the EPROM for the BC controller is WF30334, the controller is exclusively V-D type.
Always after powering
Always after powering
Always after powering
Always after powering
–31–
Page 33
[6] External Input/Output Specifications
(1) Output
1 Operation ON signal
Terminal No. TB8-1, 2 Output Relay contacts output Rated voltage: L1 - N: 220 ~ 240 V
Rated load: 1 A
Operation
2 COMP ON/OFF signal
Connector No. CN51-3, 4 Connector : B5B-XH-A (JST) Output DC 12 V Operation DC 12 V is output during compressor operation.
3 Water freeze / trouble signal
Connector No. CN51-3, 5 Connector : B5B-XH-A (JST) Output DC 12 V Operation
When DIP switch 2-7 is OFF The relay closes during compressor operation.
When DIP switch 2-7 is ON The relay closes during reception of the cooling or the heating operation signal from the controller. (Note: It is output even if the thermostat is OFF (when the compressor is stopped).)
When DIP switch 3-3 is OFF If the water temperature (TH 6) drops below 5°C while the unit is stopped, DC 12 V is output.
When DIP switch 3-3 is ON DC 12 V is output when the heat source unit is stopped abnormally.
(2) Input
1 Pump Interlock
Terminal No. TB8-3, 4 Input Level signal Operation If the circuit between TB8-3 and TB8-4 is open, compressor operation is prohibited.
2 Demand
Connector No. CN3D-1, 3 Connector : B3B-EH (JST) Input Level signal Operation If the circuit between CN3D-1 and CN3D-3 is opened, compressor operation is prohibited.
–32–
Page 34
33
3 TEST RUN
33
[1] Before Test Run
(1) Check points before test run
Neither refrigerant leak nor loose power source/ transmission lines should be found.
1
Confirm that the resistance between the power source terminal block and the ground exceeds 2M by measur­ing it with a DC500V megger. Do not run if it is lower than 2MΩ.
2
Note) Never apply the megger to the MAIN board. If applied, the MAIN board will be broken.
Confirm that the Ball valve at both gas and liquid sides is being fully opened.
3
Note) Certainly close the cap.
Be sure that the crankcase heater has been powered by turning the main power source on at least 12 hours
4
before starting the test run. The shorter powering time causes compressor trouble.
(2) Caution at inverter check
Because the inverter power portion in heat source unit electrical part box have a lot of high voltage portion, be sure to follow the instructions shown below.
During energizing power source, never touch inverter power portion because high voltage (approx. 580V) is
1
applied to inverter power portion.
When checking,
1
Shut off main power source, and check it with tester, etc.
2
Allow 10 minutes after shutting off main power source.
2
Open the MAIN board mounting panel, and check whether voltage of both ends of electrolytic capacitor is
3
20V or less.
–33–
Page 35
(3) Check points for test run when mounting options
Built-in optional parts Mounting of drain
water lifting-up mechanism
1
2
3
Mounting of perme­able film humidifier
(4) Attention for mounting drain water lifting-up mechanism
Work
Disassembling and assembling of drain water lifting-up mechanism
Check humidifier operations and water supply status in heating (test run) mode.
1
2
Content of test run
Release connector of pump circuit, check error detection by pouring water into drain pan water inlet.
After that, connect connector of circuit.
Check pump operations and drain­age status in cooling (test run) mode.
Content of test run
Lead wire from control box not damaged.
Rubber cap properly inserted to drain water outlet of drain pan?
Check point
Local remote controller displays code No. 2503, and the mechanism stops.
No overflow from drain pan. Drain water comes out by operations of
drain pump. Sound of pump operations is heard, and
drain water comes out. No water leak from connecting portions
of each water piping. Water is supplied to water supply tank,
and float switch is operating.
Check point Result
Insulation pipe
Result
Mounting of float switch
Electric wiring
Insulation pipe of gas and liquid
3
pipes dealt with as shown in the right figure?
Drain pan and piping cover mounted
4
without gap? Drain pan hooked on cut projection
5
of the mechanism?
Float switch installed without contacting with drain pan?
1
No mistakes in wiring? Connectors connected surely and
2
tightly? No tension on lead wire when sliding
3
control box?
No gap
1
Float switch moves smoothly . Float switch is mounted on
2
mounting board straightly without deformation.
Float switch does not contact with
3
copper pipe. Wiring procedure is exactly followed. Connector portion is tightly hooked.
–34–
Page 36
(5) Check points for system structure
ex. PQRY -P200YMF-B
Check points from installation work to test run.
Classification
Installation and piping
Power source wiring
Portion
1
2
3
4
5
6
7
8
1
2
3
Check item
Instruction for selecting combination of heat source unit, and indoor unit followed? (Maximum number of indoor units which can be connected, connecting model name, and total capacity .)
Follow limitation of refrigerant piping length? For ex­ample, 70m or less (total length : 220m) at the farthest.
Connecting piping size of branch piping correct? Refrigerant piping diameter correct? Refrigerant leak generated at connection? Insulation work for piping properly done? Specified amount of refrigerant replenished?
Pitch and insulation work for drain piping properly done? Specified switch capacity and wiring diameter of main
power source used? Proper grounding work done on heat source unit?
The phases of the L line (L1, L2, L3) correct?
Trouble
Not operate.
Not cool (at cooling). Not heat (at heating).
Not cool, not heat, error stop. Condensation drip in piping. Not cool, not heat, error stop.
Water leak, condensation drip in drain piping.
Error stop, not operate.
Electric shock. Error stop, not operate.
4
L line and N line connected correct?
The some electric pars should be damaged.
–35–
Page 37
CENTRALLY CONTROLLED
STAND BY DEFROST
ERROR CODE
D A I L Y
AUTO OFF
CENTRALLY CONTROLLED
CLOCK
REMAINDER
ON OFF
˚C
1Hr.
NOT AVAILABLE
˚C
CHECK MODE
FILTER
CHECK
TEST RUN
LIMIT TEMP.
ON/OFF
TEMP
FILTER
CHECK TEST
ON OFF
CLOCK
PAR-F27MEA
TIMER SET
D A I L Y
AUTO OFF
CHECK
STAND BY DEFROST
TEMP
2 31
PAR-F27MEA
TIMER SET
1Hr.
˚C
ON OFF
CLOCK
REMAINDER
ERROR CODE
˚C
ON OFF
CLOCK
NOT AVAILABLE
CHECK MODE
LIMIT TEMP.
ON/OFF
FILTER
TEST RUN
CHECK TEST
FILTER
M-NET Remote Controller
Classification Transmission
line
System set
Portion Check item
Limitation of transmission line length followed? For
1
example, 200m or less (total length : 500m) at the farthest.
2 1.25mm2 or more transmission line used?
(Remote controller 10m or less 0.75mm
2
)
3 2-core cable used for transmission line?
Transmission line apart from power source line by 5cm or more?
4
5 One refrigerant system per transmission line?
The short circuit connector is changed form CN41 to
6
CN40 on the MAIN board when the system is centralized control? (Just one outdoor unit. Not all outdoor units.)
7 • No connection trouble in transmission line? 8 Connection of wrong remote controller line terminals?
• MA Remote controller : TB15
• M-NET Remote controller : TB5
Address setting properly done? (M-NET Remote
1
controller, indoor unit and outdoor unit.) Setting of address No. done when shutting off power
2
source? Address numbers not duplicated?
3
Turned on SW3-8 on indoor unit circuit board when
4
mounting room thermistor sensor?
Trouble
Erroneous operation, error stop.
Erroneous operation, error stop.
Error stop in case multiple-core cable is used.
Erroneous operation, error stop. Not operate.
Not operate.
Error stop or not operate. Never finish the initial mode.
Error stop or not operate.
Can not be properly set with power source turned on.
Not operate. Set temperature not obtained at
heating operations (Thermostat stop is difficult)
Before starting
Refrigerant piping ball valve (Liquid pressure pipe, gas
1
pressure pipe) opened?
2
Turn on power source 12 hours before starting operations?
–36–
Error stop.
Error stop, compressor trouble.
Page 38
[2] Address setting
(1) Switch operation
In order to constitute CITY MULTI in a complete system, switch operation for setting the unit address No. and connection No. is required.
1 Unit address No. group No. and connection No.
The unit address No. is determined by the address setting switch of the heat source unit, indoor unit and remote controller.
2 Caution for switch operations
Connection No. setting
0
1
2
F
3
E
4
D
5
C
6
B
7
8
A
9
Rotary switch
Unit address No. setting
0
1
9
2
8
3
7
4
6
5
0
1
9
2
8
3
7
4
6
5
1
Be sure to shut off power source before switch setting. If operated with power source on, switch can not operate properly.
2
3
Address switch shall follow decimal system with 2 digits. Set 000 ~ 250
Heat source unit Indoor unit
0
1
9
8
7
6
5
10 1
0
1
9
2
8
3
7
4
6
5
2
3
4
Remotecontroller
0
1
9
8
7
6
5
10 1
0
1
9
2
8
3
7
4
6
5
Indoor unit Heat source unit
2
3
4
BC controller Remote controller (Main) Pair remote controller (Sub) MJ-103
No units with identical unit address shall exist in one system. If set erroneously, system can not operate.
(2) Address setting and switch operations
1 In case of system with a single system (In case higher rank controller such as remote controller for centralized control is not connected)
Unit
Indoor unit
Heat source unit
BC controller
Remote controller (Main)
Remote controller (Sub)
Remote controller
MJ-103
Fresh Master
Address setting
01~50
51~99, 100
51~99, 100
101~150
151~199, 200
000, 201~250
1~50
1
Fixed
1
Fixed
8
7
9
100
8
7
8
7
8
7
0
1
2
3
4
6
5
8
7
Example
0
1
9
2
3
4
6
5
10 1
0
1
9
2
3
4
6
5
10 1
0
1
9
2
3
4
6
5
10 1
0
1
9
2
8
3
7
4
6
5
10 1
0
1
9
2
8
3
7
4
6
5
10 1
0
1
9
8
7
4
6
5
10 1
0
1
9
2
3
4
6
5
10 1
0
1
9
2
8
3
7
4
6
5
0
1
9
8
7
6
5
0
1
9
8
7
6
5
2
3
The smallest address of indoor unit in same refrigerant
2
system + 50
3
4
*If the address is to be 100, use “50.”
The address of Heat source unit + 1
2
3
*If the address is to be 100, use “50.”
4
0
1
The smallest address of indoor unit in the group + 100
9
2
8
3
*The place of "100" is fixed to "1"
7
4
6
5
The address of main remote controller + 50
0
1
9
2
8
*The address automatically becomes "200" if it is set as
3
7
4
6
5
"00"
0
1
9
2
8
3
7
4
6
5
· The Fresh Master system allows you to select opera­tions using the remote controller or using the indoor
0
1
9
2
8
3
7
4
6
5
unit. Use the dip switch (SW3-1) to make this selection. See the section Fresh Master operation/Remote controller switching for settings.
· For operations using the remote controller, use the same setting method as for the indoor unit.
· For operations using the indoor unit, settings should be within the range 01 – 50, without respect to the group.
01~50 51~99,100 51~99,100 101~150 151~199, 200 000, 201~250
Note
Lossnay unit
1~50
0
1
9
2
8
3
7
4
6
5
10 1
–37–
0
1
9
8
7
6
5
Set within the range 01 – 50 with no duplications.
2
3
4
Page 39
2 Branch number switch (Indoor Units and Fresh Master)
Match the indoor units refrigerant pipe with the BC controllers end connection number. When combining branches, choose the smallest connection number in the series. The indoor unit capacity limit for connecting to a branch is 80. Max. 3sets for 1 connection. When selecting connection number 16, choose 0 as the setting for the branch number switch.
Connecting one unit to one branch
1 2 3 4 5 6
BC controller
1 2 3 4 5 6
Combining branches Connecting more than one unit to one branch
BC controller
1 2 3 4 5 6
1
Above 80
BC controller
1 2 3 4 5 6
3 4 5 6
1 1 2 3 4 5 6
Below 80
3 In the case of group operations of indoor units of different refrigerant system
(Including the case of connecting with higher rank controller such as remote controller for centralized controller). Group setting shall be done with remote controller. ( When the centralized remote controller is connected, the setting should be done with the centralized remote controller.) Address setting can be done on each unit freely. Regarding transmission wiring, provide 2-wire jumper system (Centralized system transmission line) to outdoor units to be connected to indoor unit in the same group, and mount short circuit connector on CN41 to CN40 for replacement for one of the outdoor units. (However, when the higher rank controller like that for centralized controller is connected, do not replace the short circuit connector to CN40.)
–38–
Page 40
(3) Examples of switch settings
System diagram Description
1 Individual operation
Heat source unit
TB3
51
52
BC controller
Indoor unit
01
101
Remote controller
Indoor unit Indoor unit
02
102
Remote controller
03
103
Remote controller
[Switch settings]
(1) Address switch
Unit
Indoor unit
Remote controller
Heat source unit
BC controller
Note 1. For remote controllers, it is not necessary to set
digits in the hundreds column.
Note 2. When setting heat source unit address or BC
controller address to 100, set the address setting switch to 50.
Range
01~50
101~150
Note 1
51~100
Note 2
51~100
Note 2
Setting
Indoor unit setting + 100 Smallest address among
indoor units + 50 Heat source unit + 1
(2) Branch number switch
Match the indoor units refrigerant pipe with the BC controllers end connection number.
2 Group operation
Heat source unit
TB3
51
52
BC controller
Indoor unit Indoor unit Indoor unit
01 02 03
103101
Remote controller
Remote controller (Main)
153
Remote controller (Sub)
[Switch settings]
(1) Address switch
Unit
IC (Main)
IC (Sub)
Remote controller
(Main)
Remote controller
(Sub)
Heat source unit
BC controller
Notes 1 and 2 : same as above.
Range
01~50
01~50
101~150
Note 1
151~200
Note 1
51~100
Note 2
51~100
Note 2
(2) Branch number switch
Same as 1 Individual operation.
Setting
Smallest address among several indoor units that form a single group.
Address other than the IC (Main) among several indoor units that form a single group. Use numerical order starting after the IC (Main).
Address of IC (Main) within the same group + 100
Address of IC (Main) within the same group +
150 Smallest address among
indoor units + 50 Heat source unit + 1
–39–
Page 41
System diagram Description
3 System for operating with OA processing unit (Lossnay)
Heat source unit
TB3
52
51
BC controller
Indoor unit Indoor unit Indoor unit Fresh Master
01 02 03
04
[Switch settings]
This is the same as 1 Individual operation. However, keep the Fresh Master address within the 1 ~50 range to avoid duplication with other indoor units.
[Registering with a remote controller]
Registers operation of Fresh Master and indoor units using the remote controller.
101 102 103
Remote controller
System for operating multiple-refrigerant + OA processing unit
4
Remote controller
Remote controller
In series with ventilation
(Lossnay)
Change
CN40CN41
Heat source unit
51
TB7
TB3
BC controller
Indoor unit
01
52
Remote controller
Indoor unit Indoor unit Indoor unit
02 03 04
103101
Remote controller
Indoor unit
01, 02, 03
OA processing unit
04← →
[Switch settings]
Same as 1 Individual operation.
*Remote controllers for groups using different refrigerants connect to transfer line of the latest indoor unit in the group.
[Managing electrical supply connector CN40]
Changes the single electrical supply connector of an outdoor unit group from CN41 to CN40.
[Registration using a remote controller]
1 Group setting
After power is turned on, this changes indoor units and network remote controllers to group setting.
Heat source unit
TB3
55
TB7
56
BC controller
08
Fresh Master
Indoor unit Indoor unit Indoor unit
07 06 05
107
Remote controller
In series with ventilation
Remote controller
101 103
← → ← →
Indoor unit
01, 02 03, 04 05, 06
107
← →
2 Operation registration
After power is turned on, this activates operation registration for Fresh Master and indoor units
using remote controllers.
Indoor unit
OA processing unit
07
01, 02, 03 04, 05, 06
← →
08
07
–40–
Page 42
System diagram Description
5 PAC-SC30GR connection
Change
Where a group remote controller is connected to a transfer line for indoor units.
CN40CN41
Indoor unit
Indoor unit Indoor unit Indoor unit
104 105
Remote controller
Heat source unit
Heat source unit
Electrical supply device
51
TB7
TB3
52
BC controller
54
TB7
TB3
56
BC controller
GR
201
GR
201
Connect to one or the other
Indoor unit Indoor unit
01 02 03
101 103
Remote controller
0504 06
Remote controller
In series with ventilation
Remote controller
[Switch settings]
Address switch settings are the same as 1 Individual operation. This turns on the central manager switch (SW2-1) of the outdoor unit.
*Remote controllers for groups using different refrigerants connect to transfer line of the latest indoor unit in the group.
[Managing electrical supply connector CN40]
When a group remote controller (GR) is connected to a transfer line for indoor units, this changes the single electrical supply connector in an outdoor unit group from CN41 to CN 40. When connected to a transfer line for central manag­ers, leave it as is (on CN41). (receiving electrical power from an electrical supply device)
[Registration using a group remote controller]
1 After power is turned on, this changes indoor units
to group setting with a group remote controller
2 This sets the relations between indoor units and
remote controllers using a group remote controller.
Indoor unit
101 103 104 107
← → ← →
← →
Group remote controllers can be connected to both indoor/outdoor unit transfer lines and central manager transfer lines.
Remote controller
01, 02 03 04 05, 06
6 MJ-103 MTR connection
Heat source unit
51
TB7
TB3
Heat source unit
55
TB7
TB3
MJ-103MTR
BC controller
BC controller
Indoor unit Indoor unit
52
Fresh Master
56
000
Electrical supply device
01 02 03 04
08 07 06 05
101 103
Remote controller
Indoor unit
107
Remote controller
In series with ventilation
Indoor unit Indoor unit
Remote controller
Indoor unit Indoor unit
[Switch settings]
Address switch settings are the same as 1 Individual operation This turns on the central manager switch (SW2-1) of the outdoor unit.
[Registration using a central controller]
1 Group setting
· After turning on the power, this activates group setting for indoor units using a central controller.
· This activates settings for indoor units and remote controllers using a central controller.
Remote controller
101 103
← → ← →
Indoor unit
01, 02 03, 04 05, 06
107
← →
2 Settings for Lossnay and indoor units are made
using a central controller.
Indoor unit
Fresh Master
01~07
07
08← →
–41–
Page 43
[3] Test Run Method
TEST RUN
Operation procedure
Turn on universal power supply at least 12 hours before getting started Displaying “HO” on display panel for
1
about two minutes
2 Press
3 Press
Press
4
warm or cold air is blowing out
5 Press
6 Press
7 Make sure that indoor unit fans operate normally 8 Make sure that interlocking devices such as ventilator operate normally if any
9 Press
Note 1: If check code is displayed on remote controller or remote controller does not operate normally.
2: Test run automatically stops operating after two hours by activation of timer set to two hours. 3: During test run, test run remaining time is displayed on time display section. 4: During test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temperature
5: When pressing
6: When pressing
or button to change wind Make sure that horizontal or downward blow is adjustable.
ON/OFF
display section.
controller. However, it is not a malfunction.
remote controller. However, it is not a malfunction.
button twice Displaying TEST RUN’’ on display panel
selection button Make sure that air is blowing out
select button to change from cooling to heating operation, and vice versa Make sure that
adjust button Make sure that air blow is changed
button to cancel test run Stop operation
adjust button, depending on the model, NOT A VAILABLE may be displayed on remote
or button, depending on the model, NOT A VAILABLE may be displayed on
–42–
Page 44
4
GROUPING REGISTRATION OF INDOOR UNITS WITH M-NET REMOTE CONTROLLER
(1) Switch function
• The switch operation to register with the remote controller is shown below:
1Hr
NOT AVAILABLE
˚C
ON/OFF
C Switch to assign
indoor unit address
F Delete switch G Registered mode
STAND BY DEFROST
CENTRALLY CONTROLLED
D A I L Y
AUTO OFF
CHECK
˚C
TEMP
ON OFF
CLOCK
REMAINDER
ERROR CODE
ON OFF
CLOCK
selector switch
E Confirmation switch
PAR-F27MEA
TIMER SET
H Switch to assign inter-
locked unit address
Name Name of actual switch Description
Registration/ordinary mode selection switch
Symbol
of switch
A + B
FILTER
+
This switch selects the ordinary mode or registered mode (ordinary mode represents that to operate indoor units). * To select the registered mode, press the
switch continuously for over 2 seconds under stopping state. [Note] The registered mode can not be obtained for a while after powering. Pressing the
FILTER
+
CONTROLLED”.
Switch to assign indoor unit address
C
of TEMP
This switch assigns the unit address for “INDOOR UNIT ADDRESS NO.”
FILTER
CHECK MODE
TEST RUN
LIMIT TEMP.
FILTER
CHECK TEST
A
Registration/ ordinary mode selector switch
D Registration switch
Registration/
B
ordinary mode selector switch
FILTER
+
switch displays “CENTRALL Y
Registration switch
Confirmation switch
Delete switch
Registered mode selector switch
Switch to assign interlocked unit address
D
TEST RUN
E
This switch is used for group/interlocked registration.
This switch is used to retrieve/identify the content of group and interlocked (connection information) registered.
F
CLOCK → ON → OFF
G
This switch is used to retrieve/identify the content of group and interlocked (connection information) registered.
This switch selects the case to register indoor units as group (group setting mode) or that as interlocked (interlocked setting mode). *The unit address is shown at one spot for the group setting mode while at two spots for the interlocked setting mode.
H
of TIMER SET
This switch assigns the unit address of “OA UNIT ADDRESS NO.”
–43–
Page 45
(2) Attribute display of unit
At the group registration and the confirmation/deletion of registration/connection information, the type (attribute) of the unit is displayed with two English characters.
Display Type (Attribute) of unit/controller
Indoor unit connectable to remote controller Outdoor unit
Local remote controller System controller (MJ)
[Description of registration/deletion/retrieval]
The items of operation to be performed by the remote controller are given below. Please see the relating paragraph for detail.
1 Group registration of indoor unit
The group of the indoor units and operating remote controller is registered.
It is usually used for the group operation of indoor units with different refrigerant system.
2 Retrieval/identification of group registration information of indoor units
The address of the registered indoor units in group is retrieved (identified).
3 Retrieval/identification of registration information
The connection information of any unit (indoor/outdoor units, remote controller or the like) is retrieved (identified).
4 Deletion of group registration information of indoor units
The registration of the indoor units under group registration is released (deleted).
5 Deletion of the address not existing
This operation is to be conducted when 6607 error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alteration/modification of the group composi­tion.
Caution:
When MELANS (MJ-103MTRA for example) is being connected, do not conduct the group/pair registration using the remote controller. The group/pair registration should be conducted by MELANS. (For detail, refer to the instruc­tion exclusively prepared for MELANS.)
–44–
Page 46
(3) Group registration of indoor unit
1) Registration method
Group registration of indoor unit ........................................................................ 1
The indoor unit to be controlled by a remote controller is registered on the remote controller.
[Registration procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
(A + B) at the same time for 2 seconds to change to the registration mode. (See the figure below.)
2 Assign the indoor unit address to “INDOOR UNIT ADDRESS NO. by operating the
adjustment) (C). Then press the
TEST RUN
switch (D) to register. In the figure below, the INDOOR UNIT ADDRESS NO. is being set
to 001.
3 After completing the registration, press the
FILTER
+ switch (A + B) at the same time for 2 seconds to
change to the original ordinary mode (with the remote controller under stopping).
Ordinary mode
Remote controller under stopping • “HO under displaying
FILTER
+ switch
(Room temperature
˚C
INDOOR UNIT ADDRESS NO
Group setting mode
˚C
TEMP
PAR-F27MEA
TIMER SET
ERROR CODE OA UNIT ADDRESS NO
1
ERROR CODE OA UNIT ADDRESS NO
ON OFF
CLOCK
ON/OFF
CHECK TEST
FILTER
1
2 + 3
˚C
INDOOR UNIT
ERROR CODE OA UNIT ADDRESS NO
ADDRESS NO
Registration complete
Indicates the type of unit (Indoor unit in this case)
˚C
ERROR CODE OA UNIT ADDRESS NO
Registration error
88 flickers indicating registra­tion error. (when the indoor unit registered is not existing)
˚C
ERROR CODE OA UNIT ADDRESS NO
2 Assign the
address (C)
System example
Remote controller
1 Change to the
registration mode (A + B)
Indoor units
3 Press the
registration switch (D)
Group
Confirm the indoor unit address No.
Confirm the connection of the transmission line.
45
Page 47
2) Method of retrieval/confirmation
Retrieval/confirmation of group registration information on indoor unit .............. 2
The address of the indoor unit being registered on the remote controller is displayed.
[Operation procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
+ B) at the same time for 2 seconds to change to the registration mode.
2 In order to confirm the indoor unit address already registered, press
switch (E). (See figure below.) When the group
of plural sets is registered, the addresses will be displayed in order at each pressing of
3 After completing the registration, continuously press the
FILTER
+ switch ( A + B) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
Registered
FILTER
+ switch (A
switch (E).
PAR-F27MEA
TEMP
TIMER SET
CLOCK
ON OFF
ON/OFF
CHECK TEST
FILTER
1
1
Indicates the type of unit (Indoor unit in this case)
No registration.
˚C
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
Note: Only one address will be displayed
1 Press the switch for confirmation (E)
Retrieval/confirmation of registration information ................................................ 3
The registered information on a certain unit (indoor unit, outdoor unit, remote controller or the like) is displayed.
[Operation procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
+ B) at the same time for 2 seconds to change to the registration mode.
2 Operate
switch (G) for the interlocked setting mode. (See figure below.)
3 Assign the unit address of which registration information is desired to confirm with the
(H). Then press the Each pressing of
4 After completing the retrieval/confirmation, continuously press the
switch (E) to display it on the remote controller. (See figure below.)
switch (E) changes the display of registered content. (See figure below.)
FILTER
for 2 seconds to change to the original ordinary mode (with the remote controller under stopping).
when the registration is one even the switch is how often pressed
FILTER
+ switch (A
(TIMER SET) switch
+ switch (A + B) at the same time
–46–
Page 48
PAR-F27MEA
TEMP
TIMER SET
CLOCK
ON OFF
ON/OFF
CHECK TEST
FILTER
1 + 2
Registered
˚C
(Alternative
display)
˚C
˚C
(Alternative
display)
2
confirmation (E)
INDOOR UNIT ADDRESS NO
˚C
˚C
ERROR CODE OA UNIT ADDRESS NO
* Same display will appear when
the unit of “007” is not existing.
No registration
˚C
ERROR CODE
1 Set the address2 Press the switch for
3) Method of deletion
Deletion of group registration information of indoor unit ...................................... 4
[Operation procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
switch (A + B) at the same time for 2 seconds to change to the registration mode.
2 Press the
switch (E) to display the indoor unit address registered. (As same as 2)
3 In order to delete the registered indoor unit being displayed on the remote controller, press the
two times continuously. At completion of the deletion, the attribute display section will be shown as “ – – “. (See figure below.) Note: Completing the deletion of all indoor units registered on the remote controller returns to “HO” display.
4 After completing the registration, continuously press the
FILTER
+ switch ( A + B) at the same time for 2
seconds to change to the original ordinary mode (with the remote controller under stopping).
OA UNIT ADDRESS NO
FILTER
CLOCK → ON → OFF
+
(F) switch
TEMP
ON OFF
CLOCK
PAR-F27MEA
TIMER SET
1 Press the switch for confirmation (F)
twice continuously.
ON/OFF
CHECK TEST
FILTER
1
In case group re­gistration with other indoor unit is existing
1
In case no group registration with other indoor unit is existing
47
Deletion completed
˚C
INDOOR UNIT ADDRESS NO
“– –” indicates the deletion completed.
Deletion completed
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
Page 49
4) Deletion of information on address not existing
Deletion of information on address not existing................................................... 5
This operation is to be conducted when “6607” error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alteration/modification of group composition, and the address not existing will be deleted. Note: The connection information (connection between indoor unit and outdoor unit) on the refrigerant system can
not be deleted. An example to delete the system controller of “250” from the indoor unit of “007” is shown below.
[Operation procedure]
1 With the remote controller under stopping or at the display of “HO, continuously press the
FILTER
+ switch (A
+ B) at the same time for 2 seconds to change to the registration mode.
2 Operate 3 Assign the unit address existing to OA UNIT ADDRESS No. with the
switch (G) for the interlocked setting mode ( ii ). (See the figure below.)
(TIMER SET) switch (H), and press switch (E) to call the address to be deleted. (See the figure below .) As the error display on the remote controller is usually transmitted from the indoor unit, OA UNIT ADDRESS No. is used as the address of the indoor unit.
4 Press the 5 After completing the deletion, continuously press the
CLOCK → ON → OFF
switch (F) twice. (See the figure below.)
FILTER
+ switch (A + B) at the same time for 2 seconds
to return to the original ordinary mode (with the remote controller under stopping).
Deletion completed
When both indoor
INDOOR UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
(Alternative
display)
unit and interlocked unit addresses are existing
3
INDOOR UNIT ADDRESS NO
˚C
ERROR CODE OA UNIT ADDRESS NO
(Alternative
display)
INDOOR UNIT ADDRESS NO
PAR-F27MEA
2 Press the switch for
confirmation (E)
˚C
ERROR CODE OA UNIT ADDRESS NO
1 + 2
TEMP
ON OFF
CLOCK
TIMER SET
3 Press the deletion switch (F) twice
1 Set the address (H)
ON/OFF
CHECK TEST
FILTER
3
Deletion of address not existing
˚C
INDOOR UNIT ADDRESS NO
Deletion completed
˚C
INDOOR UNIT ADDRESS NO
INDOOR UNIT ADDRESS NO
(Alternative
˚C
ERROR CODE OA UNIT ADDRESS NO
*
ERROR CODE OA UNIT ADDRESS NO
display)
ERROR CODE OA UNIT ADDRESS NO
*
48
Page 50
55
5 CONTROL
55
[1] Control of Heat Source Unit
(1) Initial processing
• When turning on power source, initial processing of microcomputer is given top priority.
• During initial processing, control processing corresponding to operation signal is suspended. The control process­ing is resumed after initial processing is completed. (Initial processing : Data processing in microcomputer and initial setting of each LEV opening, requiring approx. 2 minutes at the maximum.)
(2) Control at staring
• In case unit is started within 2 hours after turning on power source at low ambient temperature (+5˚C or less), the unit does not start operating for 30 minutes at the maximum.
(3) Bypass, capacity control
• Solenoid valve consists of bypass solenoid valve (SV1, SV2) bypassing between high pressure side and low pressure sider. The following operation will be provided.
1) Bypass solenoid valves SV1 and SV2 (both “open” when turned on)
Item
When starting compressor After thermost “ON is returned and
after 3 minutes restart When compressor stops in cooling or
heating mode After operation stops During oil recovery operations During 20Hz operations, at fall in low
pressure
When high pressure rises (Pd)
When high pressure (Pd) rises during 20Hz operations (3 minutes after starting)
When discharge temperature rises (3 minutes after starting)
Compressor
SV1
ON (Open) OFF (Close) Turned on for 4 minutes Turned on for 4 minutes
Always turned on
Turned on for 3 minutes Always turned on.
When Pd reaches
27.5kg/cm2G (2.70MPa)
When Pd is under 24kg/cm2G (2.35MPa) and 30 seconds
SV2
ON (Open) OFF (Close)
– –
Always turned on.
When Ps is 1.5kg/ cm2G (0.15MPa) or less
When Pd reaches
26.5kg/cm2G (2.60MPa)
Turned on when high pressure (Pd) ex­ceeds pressure limit
When temp. exceeds 130˚C
When Ps is 2.5kg/ cm2G (0.25MPa) or more
When Pd is under
23.5kg/cm2G (2.30MPa) and 30 seconds
When high pressure (Pd) is 20kg/cm2G (1.96MPa) or less
When discharge temp. is 115˚C
Bypass solenoid valve (SV1)
Start Thermo.
(4-minute)
OFF
Thermo. ON
(2-minute) (3-minute)
Stop
(4) Frequency control
• Depending on capacity required, capacity control change and frequency change are performed to keep constant evaporation temperature in cooling operations, and high pressure saturation temperature in heating operation.
• Frequency change is perfprmed at the rate of 2Hz/second across 20 ~ 105Hz range.
1) Frequency control starting
• 60Hz is the upper limit for 3 minutes after starting.
• 75Hz is the upper limit within 30 minutes at the first starting compressor after turning on power source.
–49–
Page 51
2) Pressure limit The upper limit of high pressure (Pd) is set for each frequency. When the limit is exceeded, frequency is reduced every 10 seconds. (Frequency decrease rate (Hz) : 22% of the present value)
<P200YMF-C> <P250YMF-C>
3) Discharge temperature limit Discharge temperature (Td) of compressor is detected during operation. If the upper limit is exceeded, the fre­quency is reduced. (Change rate : 5% of the present value)
• 30 seconds after starting compressor, control is performed every minute.
• Operation temperature is 130˚C.
4) Periodical frequency control Frequency controll is periodically performed except for the frequency controls at operation start, status change, and protection.
1 Cycle of periodical frequency control
Periodical frequency control is performed every minute after the time specified below has passed.
• 20 sec after starting compressor
• 20 sec after frequency control by discharge temperature or pressure limit
2 Amount of frequency change
The amount of frequency change is controlled corresponding to evaporation temperature and high pressure saturation temperature.
3 Back up of frequency control by bypass valve
During 20Hz operations, frequency is backed up by turning on (opening) bypass valve (SV2).
• Cooling During 20Hz operations 3 minutes after starting compressor, bypass valve is turned on when, Ps is 1.5kg/cm
2
G (0.15MPa) or less and turned off when Ps is 2.5kg/cm2G (0.25MPa) or more.
• Heating During 20Hz operations 3 minutes after starting compressor, SV2 turned on when high pressure (Pd) exceeds pressure limit and turned off when Pd falls to 20kg/cm
ON OFF
1.5kg/cm2G 2.5kg/cm2G (0.15MPa) (0.25MPa)
2
G (1.96MPa) or less.
ON OFF
20kg/cm2G 27kg/cm2G (1.96MPa) (2.65MPa)
(5) Oil return control (Electronic expansion valve <SLEV>)
• Oil return LEV (SLEV) opening is dependent on compressor frequency and ambient temperature.
• SLEV is closed (0) when compressor stops, and SLEV is set (50) for 10 minutes after starting compressor.
–50–
Page 52
(6) Judgement of refrigerant amount
80
60
40
Discharge Superheat
20
0
20 40 60 80 100
Cooling Mode
AL=0
AL=1
AL=2
F(Hz)
Heating Mode
100
AL=0
80
60
AL=1
40
Discharge Superheat
20
AL=2
0
-30 -20 -10 0 10 20 30 Te(°C)
–51–
Page 53
(7) Control of heat source unit fan and heat source unit heat exchanger capacity
1) Control system Depending on capacity required, control SV3~6, SV71~73, for maintaining evaporation temperature (0˚C) in cooling operations, and high pressure saturated temperature (52˚C) in heating operations.
2) Heat exchanger pattern
Mode Cooling-only
SV3 SV4 SV5 SV6 SV71 SV72 SV73
Heat Exchanger Switching
× ×× ××××
ЧЧЧЧЧ ЧЧЧЧЧЧ ЧЧЧЧ × 8 HP only
× ЧЧЧЧЧ10 HP only × ××× × 10 HP only ЧЧЧЧЧЧЧ
Cooling-main × ××
× ×
×× Ч ЧЧЧЧЧ8 HP only ××× ×
ЧЧЧЧЧЧ ЧЧЧЧ ×
×× ×××8 HP only × ЧЧЧЧЧ10 HP only × ××× × 10 HP only × × ×××10 HP only ЧЧЧЧЧЧЧ ЧЧЧЧЧ ЧЧЧ ЧЧЧ
Heating-only ×××
××× × ×
×
×××× 10 HP only
××
×××
×
×× × ××× ×
Heating-main ×××
×××× 10 HP only
××
×××
×
×× × ××× ×
Remarks
–52–
Page 54
[2] Control box cooling system
In PQRY, in order to cool the parts in the control box which emit heat, a refrigerant evaporator has been placed in the bottom of the control box (unit frame side). (See the figure.) The control box is also mounted in the frame and when the inverter operates, it operates the control box internal cooling fan as well as supplying refrigerant to the evaporator, thus creating air passages in the direction shown by the arrows.
(1) Cooling fan control
(a) If the temperature of fin is over 80°C when the inverter is just
turned on, run the fan until the temperature drops below 80°C. During this operation, turning on the inverter is prohibited.
(b) When the inverter is operating Always ON
(c) Once the fan goes on, it forcibly remains ON for 5 minutes.
Note: By mounting the control box in the frame, a structure is
created where air passages are formed, so when mount­ing the control box, be sure to push it in to the back. Also, at that time, be careful of tearing of the seal material affixed to the frame.
(2) LEV 2 control
(a)LEV2 control range.
0
LEV 2 150 pulses
(b)LEV2 Control method
SHB=THINV-TH2 THHS
6 SHB SHB<6
THHS 55˚C THHS<55˚C
TH10
TH10>80
TH10 80
PQRY Control box
Cooling fan
Heat sink
Refrigerant piping
Evaporator
LEV2
(INV Cooling LEV)
IPM
DS
THINV
TH2
PQRY Control Box Layout Diagram
(Internal air passages)
DCL
Frame
LEV2
– –
UP UP UP
DOWN
–53–
Page 55
[3] Control of BC Controller
(1) Control of SVA, SVB and SVC
SVA, SVB and SVC are turned on and off depending on connection mode.
Mode
Connection
SVA ON OFF OFF OFF SVB OFF ON OFF OFF SVC ON OFF OFF OFF
(2) Control of LEV
LEV opening (sj) is controlled corresponding to operation mode as follows: (Number of pulse)
Operation mode Cooling-only Heating-only Cooling-main Heating-main Stop
Cooling Heating Stop Defrost
LEV1
LEV3
Superheat
*1
control
Differential
*2
pressure control
*3
* Please confirm that the above parts of BC controllers are being color-corded and shown with the name plate inside
the BC controller unit.
2000
Superheat
control *1
Control every minute so that superheat amount detected by bypass inlet and oulet temperatures (TH12, TH15) stay in the specified range.
Control every minute so that detected differential pressure (PS1, PS3) stay in the specified range.
60 or more pulses are sometimes detected because of rise in liquid side pressure (PS1).
60
Differential
Pressure control
*2
Liquid level control *3
Differential pressure control
*2
60
Differential
pressure control
*2
1000
60
–54–
Page 56
[4] Operation Flow Chart
(1) Heat source unit
Start
HO blinks on the remote
controller
Oil return LEV (SLEV), INV
cooling LEV (LEV2) fully closed
1. 52C OFF
2. Inverter output 0Hz
3. All solenoid valve OFF
NO
Fan
dress No. to remote
NO
Breaker
turned on
YES
Set indoor ad-
controller
YES
Operation command
YES
Operation
mode
Error mode
NO
NO
Normal operations Trouble observed Stop
Note : 1
Cooling-only, Heating-only, Cooling/heating mixed
Note : 2
YES
Error stop
52C ON
Note : 3
Operation
mode
Cooling (Cooling-
only) operations
Note : 1 For about 3 minutes after turning on power source, address and group information of heat source unit, BC, controller indoor
unit, and remote controller are retrieved by remote controller, during which “HO” blinks on and off on remote controller . In case indoor unit is not grouped to remote controller, “HO” display on remote controller continues blinking even after 3 minutes after turning on power source.
Note : 2 Two trouble modes included indoor unit side trouble, (BC controller trouble) and heat source unit side trouble. In the case of
indoor unit side trouble, error stop is observed in heat source unit only when all the indoor units are in trouble. However, if one or more indoor units are operating normally, heat source unit shows only LED display without undergoing stop.
Note : 3 On PUHY system, operation mode conforms to mode command by indoor unit. However, when heat source unit is being under
cooling operation, the operation of indoor unit will be prohibited even by setting a part of indoor units under operation, or indoor unit under stopping or fan mode to heating mode. Reversely when heat source unit is being heating operation, the same condition will be commenced. On PURY system, operation mode conforms to mode command by BC controller.
Note : 4 In case BC controller issues cooling/heating mixed operation mode, heat source unit decides operation mode of cooling-main
operation or heating-main operation.
Heating (Heating-
only) operations
Operation mode command to (BC controller) heat source unit
Cooling/heating mixed
Note : 4
Operation
mode
Cooling-main
operations
Heating-main
operations
Error code blinks on the outdoor controller board
Error command to
BC controller
Error code blinks on the
remote controller
–55–
Page 57
(2) BC controller
Start
NO
Breaker
turned on
YES
Operation
NO
1.Operation mode judgement (cooling-only, heating-only, cooling/heating mixed)
2.Transmission to heat source unit
Receiving operation mode
command from heat source unit
command
YES
Error mode
Note : 1
YES
Normal operations Trouble observed Stop
NO
Fan
Solenoid valve OFF,
LEV fully closed.
Cooling-only
operations
Note : 1 Two error modes include indoor unit side trouble, BC controller trouble, and heat source unit side trouble. In the case of
indoor unit side trouble, error stop is observed in the concerned indoor unit only, and in the cases of BC controller and heat source unit side troubles, error stop is observed in all the indoor units, BC controller, and heat source unit.
Operation mode
Operation mode
Heating-only
operations
Cooling/heating mixed
Operation mode
Cooling-main
operations
Heating-main
operations
Error stop
Error code blinks on the outdoor controller board
Error command to
BC controller
Error code blinks on the
remote controller
–56–
Page 58
(3) Indoor unit
Start
Breaker
turned on
YES
NO
Normal operations Trouble observed Stop
YES
3-minute drain
pupm ON
Operation SW
turned on
NO
1. Protection function self-holding cancelled.
2. Indoor unit LEV fully closed.
Remove controller display extinguished
FAN stop
Drain pump
ON
NO
YES
Note :1
Note :2
Error mode
YES
Error stop
Error code blinks on the remote controller
Error command to heat source unit
Indoor unit LEV fully closed
Note :1
Error code blinks on the heat source controller board
NO
Cooling mode
Cooling
display
Prohibition Prohibition
YES
Heating
mode
Heating
display
NO
Cooling operations
Heating operations
Operation mode
Dry display
YES
NO
Dry operation
Prohibition Remote controller blinking
Dry mode
Cooling/heating automatic mode
Cooling/heating automatic display
Note :3Note :3 Note :3
NO
YES
NO
Cooling/heating automatic operations
Prohibition Prohibition
Fan mode
Fan display
YES
Fan operations
Note : 1 Indoor unit LEV fully closed : 41-pulse Note : 2 Two error modes include indoor unit trouble, (BC controller trouble) and heat source unit side trouble. In the case of indoor
unit trouble, error stop is observed in the concerned indoor unit only, and in the cases of (BC controller and) heat source unit side troubles, error stop is observed in all the indoor units connected.
Note : 3 “Prohibition” status is observed (when several indoor units are connected to one connection, of BC controller and) when
connection mode is different from indoor unit operation mode. (Operation mode display on the remote controller blinks on and off, fan stops, and indoor unit LEV is fully closed.)
–57–
Page 59
(4) Cooling operation
Cooling operation
NO
YES
4-way valve OFF
Indoor unit fan
operations
Test run start
NO
Thermostat ON
YES
3-minute
restart
prevention
NO
Normal operations Test run Stop
YES
1.Inverter output 0Hz
2.Indoor unit LEV, oil return LEV (SLEV), INV cooling LEV (LEV2) fully closed
3.Solenoid valve OFF
4.BC controller solenoid valve OFF
5.BC controller LEV fully closed
1.Inverter frequency control
2.Indoor unit LEV, oil return LEV (SLEV), INV cooling LEV (LEV2) control
3.Solenoid valve control
4.BC controller solenoid valve control
5.BC controller LEV control
–58–
Page 60
(5) Heating operation
Heating operation
4-way valve ON
NO
Thermostat ON
YES
NO
Test run start
NO
YES
3-minute
restart
prevention
NO
Normal operations Stop Test run
YES
1.Indoor unit fan very low speed operations
2.Inverter output 0Hz
3.Indoor unit LEV, oil return LEV (SLEV), INV cooling LEV (LEV2) fully closed
4.Solenoid valve OFF
5.BC controller solenoid valve OFF
6.BC controller LEV fully closed
1.Indoor and heat source unit fan control
2.Inverter frequency control
3.Indoor unit LEV, oil return LEV (SLEV), INV cooling LEV (LEV2) control
4.Solenoid valve control
5.BC controller solenoid valve control
6.BC controller LEV control
–59–
Page 61
(6) Dry operation
Dry operations
4-way valve OFF
Normal operations Thermostat ON Stop
1.Indoor unit fan stop
2.Inverter output 0Hz
3.Indoor unit LEV, oil return LEV (SLEV), INV Cooling LEV (LEV2) closed
4.Solenoid valve OFF
5.BC controller solenoid valve OFF
6.BC controller LEV fully closed
Test run start
NO
NO
Inlet temp. 18˚C
YES
1.Heat source unit (Compressor) intermittent operations
2.Indoor unit fan intermittent opera­tions
YES
(Synchronized with compressor : low speed, OFF operations)
YES
Note : 1
Note : 2
Thermostat ON
Note : 1 When indoor unit inlet temperature exceeds 18˚C, heat source unit (compressor) and indoor unit fan start intermittent
Note : 2 Thermostat is always kept on in test run, and indoor and heat source unit intermittent operation (ON) time is a little longer
operations synchronously. Operations of heat source unit, BC controller, indoor unit LEV and solenoid valve accompanying compressor are the same as those in cooling operations.
than normal operations.
–60–
Page 62
[5] List of Major Component Functions
Name Symbol (function) Application Specification Check method
Compressor
High pressure sensor
Low pressure sensor
Pressure switch
Thermistor
Heat source unit
MC
63HS
63LS
63H
TH1 (discharge)
TH2 (low pressure saturation temperature)
Adjust refrigerant circulation by control­ling operating frequency and capacity control valve with operating pressure.
1) High press. detection.
2) Frequency control and high pressure protection
1) Detects low pressure
2) Calculates the refrigerant circulation configuration.
3) Protects the low pressure
1) High pressure detection
2) High pressure protection
1) Discharge temperature detection
2) High pressure protection
20˚C :250k 70˚C : 34k 30˚C : 160k 80˚C : 24kΩ 40˚C : 104k 90˚C : 17.5k 50˚C : 70k 100˚C : 13.0kΩ 60˚C : 48k 110˚C : 9.8kΩ
1) Detects the saturated vapor tempera­ture.
2) Calculates the refrigerant circulation configuration.
3) Controls the compressor frequency.
4) Controls the valves for heat ex­changer capacity control.
Low pressure shell scroll type with capacity control mechanism Winding resistance: Each phase 0.388 (20˚C)
Pressure
Con­nector
Con­nector
63HS
63LS
0~30 kg/cm (0~2.94MPa) Vout 0.5~3.5 V
Gnd (black) Vout (white) Vc (DC5V) (red)
Pressure 0~10 kg/cm2G (0~0.98MPa) Vout 0.5~3.5 V
Gnd (black) Vout (white) Vc (DC5V) (red)
2
G
Setting 30kg/cm2G (2.94MPa) OFF
R120=7.465k B25/120=4057
Rt = 7.465exp {4057( - )}
1
273+t
1
273+120
R0=33k B0/100=3965 Rt = 33exp{3965( - )}
1
273+t
1
273+0
-20˚C : 92k
-10˚C : 55k 0˚C : 33k 10˚C : 20k 20˚C : 13k 30˚C : 8.2k
Continuity check
Resistance value check
Resistance value check
TH6 (Inlet water air temperature)
TH9
THINV
1) Inlet water temperature detection
2) Liquid level heater, and opening setting for oil return
1) Detects the CS circuit fluid tempera­ture.
2) Calculates the refrigerant circulation configuration.
1) Detects the temperature at the inverter cooler’s heat exchanger outlet.
2) Controls the LEV2 opening angle.
R0=15k B0/100=3460 Rt = 15exp{3460( - )}
1
273+t
1
273+0
0˚C : 15k 10˚C : 9.7k 20˚C : 6.4k 25˚C : 5.3k 30˚C : 4.3k 40˚C : 3.1k
–61–
Page 63
Name Symbol (function) Application Specification Check method
Thermistor
Heat source unit
Solenoid valve
TH10
THHS
SV1 (discharge ­suction bypass)
SV2 (discharge ­suction bypass)
1) Detects the compressor shell temperature.
2) Provides compressor shell overheat­ing protection.
1) Detects the inverter cooling fin temperature.
2) Provides inverter overheating protection.
1) High/low press. bypass at starting/ stopping and capacity control at low load
2) Discharge press. rise suppression
Capacity control and high press. rise suppression (backup for frequency control)
R120=7.465k B25/120=4057 Rt =
7.465exp {4057( - )}
1
273+t
1
273+120
20˚C : 250k 70˚C : 34k 30˚C : 160k 80˚C : 24k 40˚C : 104k 90˚C : 17.5k 50˚C : 70k 100˚C : 13.0k 60˚C : 48k 110˚C : 9.8k
R50=17k B25/50=4170 Rt = 17exp{4170( - )}
273+t
1
1
273+50
-20˚C : 605.0k50˚C : 17.0k
-10˚C : 323.3k60˚C : 11.5k 0˚C : 180.9k70˚C : 8.0k 10˚C : 105.4k80˚C : 5.7k 20˚C : 63.8k90˚C : 4.1k 30˚C : 39.9k100˚C : 3.0k 40˚C : 25.7k
AC 220~240V Open at energizing and close at deenergizing
Continuity check by tester
Temperature of inlet and outlet.
Linear expansion valve
Linear expansion valve
Thermistor
Indoor unit
SV3 ~ 6 SV71~73
SLEV
LEV2
LEV
TH21 (inlet air tempera­ture)
TH22 (piping tempera­ture)
TH23 (gas side piping temperature)
Control of heat exchanger capacity.
Adjustment of liquid refrigerant (oil) return foam accumulator
Controls the volume of refrigerant flowing to the inverter coolers heat exchanger.
1) Adjust superheat of heat source unit heat exchanger outlet at cooling.
2) Adjust subcool of indoor unit heat exchanger at heating.
Indoor unit control (thermostat)
1) Indoor unit control (freeze prevention, hot adjust, etc.)
2) LEV control in heating operation (Subcool detection)
LEV control in cooling operation (Superheat detector)
DC12V stepping motor drive Valve opening 0~450 pulse (SLEV), 0~150 pulse (LEV2)
DC12V Opening of stepping motor driving valve 60~2,000 pulses
R0 = 15k B0/100 = 3460
Rt = 15exp {3460 ( - )}
1
273+t1273+0
0°C : 15k 10°C : 9.7k 20°C : 6.4k 25°C : 5.3k 30°C : 4.3k 40°C : 3.1k
Continuity check with tester for white-red­orange yellow-brown-blue
Resistance value check
62
Page 64
Name Symbol (function) Application Specification Check method
Pressure sensor
Thermistor
BC controller
Solenoid valve
PS1
PS3
TH11 (liquid inlet temperature)
TH12 (bypass outlet pressure)
TH15 (bypass outlet temperature)
TH16 (bypass inlet temperature)
SVA
SVB
1) Liquid pressure (high-pressure) detection
2) LEV control
1) Intermediate pressure detection
2) LEV control
LEV control (liquid refrigerant control)
LEV control (superheat control)
LEV control (superheat control)
LEV control (subcool control)
Supplies refrigerant to cooling indoor unit.
Supplies refrigerant to heating indoor unit.
PS1/PS3
Con­nector
Pressure 0~30 kg/cm (0~2.94MPa) Vout 0.5~3.5 V
Gnd (black) Vout (white) Vc (DC5V) (red)
2
R0=15k B0/100=3460 Rt = 15exp{3460( - )}
1
273+t
1
273+0
0˚C : 15k 10˚C :9.7k 20˚C :6.4k 25˚C :5.3k 30˚C :4.3k 40˚C :3.1k
AC 220~240V Open when energized Closed when de-energized
G
Continuity check by a tester
Electronic expansion valve
SVC
LEV1
LEV3
Supplies refrigerant to cooling indoor unit.
Liquid level control Pressure control
Liquid level control Pressure control
12V DC stepping motor drive 0 to 2000 valve opening pulse
Same as LEV of indoor unit.
–63–
Page 65
[6] Resistance of Temperature Sensor
Thermistor for low temperature Thermistor R
t = 15exp {3460 ( - )} Rt = 7.465exp {4057 ( - )}
R
o= 15kΩ ± 3% (TH3 ~ 9, THINV) Thermistor R120 = 7.465kΩ ± 2% (TH1, 10)
1
273+t
1
273+0
273+t
1
1
273+120
50
40
30
20
Resistance (kΩ)
10
0
–20 –10 10 20 30 40 500
25
20
15
10
Resistance (kΩ)
5
0
90 100 110 120
Temperature (˚C) Temperature (˚C)
Thermistor R R
t = 33exp {3965 ( - )} Rt = 17exp {4170 ( - )}
o = 33kΩ ± 1% (TH2) Thermistor R50 = 17kΩ ± 2% (THHS)
1
273+t
1
273+0
1
273+t
273+50
1
Resistance (kΩ)
Resistance (kΩ)
Temperature (˚C) Temperature (˚C)
–64–
Page 66
66
6 REFRIGERANT AMOUNT ADJUSTMENT
66
Clarify relationship between the refrigerant amount and operating characteristics of CITY MULTI, and perform service activities such as decision and adjustment of refrigerant amount on the market.
[1] Refrigerant Amount and Operating Characteristics
The followings are refrigerant amount and operating characteristics which draw special attention.
During cooling operations, required refrigerant amount tends to increase (refrigerant in accumulator decreases)
1
in proportion to increase in the number of operating indoor units. However, the change of increase rate is small.
2
During heating operations, liquid level of accumulator is the highest when all the indoor units are operating.
Discharge temperature hardly changes when increasing or decreasing refrigerant amount with accumulator
3
filled with refrigerant.
During cooling operations, discharge temperature tends to rise at overload than low temperature.
Tendency of
4
discharge temperature
During heating operations, discharge temperature tends to rise at low temperature than overload.
The lower operating frequency is, the higher discharge temperature tends to become of deteriorated compressor efficiency.
Comparison including control system
Compressor shell temperature is 20~70 degrees higher than low pressure saturation temperature (Te) when refrigerant amount is appropriate.
5
Judged as over replenishment when temperature difference from low pressure saturation temperature (Te) is 10 degrees or less.
[2] Adjustment and Judgement of Refrigerant Amount
(1) Symptom
The symptoms shown in the table below are the signs of excess or lack of refrigerant amount. Be sure to adjust refrigerant amount in refrigerant amount adjustment mode, by checking operation status, judging refrigerant amount, and performing selfdiagnosis with LED, for overall judgement of excess or lack of refrigerant amount.
Emergency stop at 1500 remote controller display (excessive
1
refrigerant replenishment) Operating frequency does not fully increase, thus resulting in
2
insufficient capacity Emergency stop at 1102 remote controller display (discharge
3
temperature trouble) Emergency stop occurs when the remote control display is at
4
1501. (insufficient refrigerant)
Excessive refrigerant replenishment
Insufficient refrigerant replenishment
Insufficient refrigerant
–65–
Page 67
(2) Refrigerant amount
1 Checking the operating condition
Operate all the indoor units on cooling or on heating, checking the discharge temperature, sub-cooling (BC control­ler), low pressure saturation temperature, inlet temperature, shell bottom temperature, liquid level, liquid step, etc. and rendering an overall judgment.
Note :
Depending on the operating state, AL = 0 has the meaning does not mean that there is insufficient refrigerant.
Condition
Judgement 1 Outlet temperature is high. (110°C or higher) 2 Low pressure saturation temperature is extremely low. 3 Inlet superheating is high (if normal, SH = 20 deg or lower).
Refrigerant volume tends toward insufficient.
4 Shell bottom temperature is high (the difference with the low pressure saturation
temperature is 70 deg. or greater)
5 Shell temperature is low (the difference with the low pressure saturation tem-
perature is 10 deg. or lower).
Rifrigerant volume tends toward overcharge.
6 Liquid level AL = 2
2 Check the refrigerant volume by self-diagnosis using the LED.
Set the self-diagnosis switch (SW1) as shown below and check the past information (history) concerning the refrigerant volume.
12345678910
Set SW1 as shown in he figure at right.
ON
If LD8 lights up, it indicates the refrigerant charge abnormal delay state just before emergency stop due to refriger­ant overcharge (1500).
3 Additional refrigerant charge volume
At the time of shipping from the factory, the heat source unit is charged with the amount of coolant shown in the following table, but since no extension piping is included, please carry out additional charging on-site.
Heat source unit model name PQRY-P200YMF-C PQRY-P250YMF-C Refrigerant charge volume 7.5kg 8.5 kg
Calculation formula Calculate the additional refrigerant volume by calculating the size of the extension liquid piping and its length (units: m).
Additional refrigerant volume (kg) = (0.12 × L
1) + (0.06 × L2) + (0.024 × L3) + α
1: Length of ø12.7 liquid pipe (m)
L L
2: Length of ø9.52 liquid pipe (m)
L
3: Length of ø6.35 liquid pipe (m)
α: refer to the calculation table.
In the calculation results, round up fractions smaller than 0.01 kg. (Example: 18.54 kg 18.6 kg)
–66–
Page 68
(α Calculation Table)
Total capacity of Connected indoor units α P200 P250
100~160 125~160 1.5 161~300 161~375 2.0
Caution :
When charging with refrigerant, be sure to charge from the liquid side. If charging from the gas side, it will cause the refrigerant composition to change inside the unit and the composition of the refrigerant remaining in the canister will also change.
–67–
Page 69
(3) Refrigerant amount adjustment
Adjustment starts.
Start cooling operation of all indoor units in a test run mode. Note 1
Has the
compressor been
operated for more than
30min?
Was the operation condition stabilized?
The high pressure > 13kg/cm2G?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
TH1 115˚C?
Fill refrigerant little by little from the low-pressure side service port.
YES NO
Note 1)As the refrigerant volume can not be adjusted in the heating mode,
retrieve the refrigerant, evacuate air and then fill the specified volume of refrigerant if it is necessary to adjust the refrigerant volume in the winter season.
Is the
thermostat turned
on/off in order for the indoor
unit to prevent from
frosting?
Stop the refrigerant volume adjustment and retrieve the refrigerant. After evacuating air, fill the specified volume of refrigerant.
Are all indoor units SHs more than 6deg?
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
5deg SC11?
Note 2
10 SC16 30deg?
Note 3
Is the LEV opening
degree stable when SH
< 6deg?
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
Retrieve the refrigerant little by little
30deg < SC16?
from the low-pressure side service port.
Fill refrigerant little by little from the low-pressure side service port.
*Operate for 5 minutes after adjusting the refrigerant and make a judgement.
TH1 110˚C?
Adjustment completed.
Fill refrigerant little by little from the low-pressure side service port.
–68–
Note 2)SC11 : Liquid refrigerant sub-cool for BC controller inlet Note 3)SC16 : Liquid refrigerant sub-cool for BC controller outlet
Page 70
Time required for recovering refrigerant from low pressure service port (minute)
Low pressure
2
(kg/cm
Refrigerant amount
G) (MPa)
3.5~4.5 4.5~5.5 5.5 ~ 7.5
(0.34~0.44) (0.44~0.54) (0.54~0.74)
to be drawn out (kg)
1 4.0 3.5 3.5 2 8.0 7.0 6.5 3 12.0 10.5 10.0 4 16.0 14.0 13.0 5 20.0 18.0 16.5 6 24.0 21.5 19.5 7 28.0 25.0 23.0 8 32.0 28.5 26.0
9 36.0 32.0 29.5 10 40.0 35.5 32.5 11 44.0 39.0 36.0
Additional evacuation, refrigerant replacement, and refrigerant replacement WR2 series has unique refrigerant circuit structure which makes possible 2-pipe cooling-heating simultaneous opera­tions. Therefore, in the case of total replacement or replenishment of refrigerant in this system, the following evacuation and refrigerant replenishment procedures are required. 1 Perform evacuation by connecting to system analyzer joint of service port of high pressure ball valve and high
pressure charge plug, and joint of service port of low pressure ball valve and low pressure charge plug.
2 Perform refrigerant charge from low pressure circuit only, after finishing evacuation, closing vacuum pump valve,
shutting off high pressure circuit of system analyzer, and opening valve of refrigerant cylinder. (In case service port of ball valve and charge plug can not be jointed as shown in the figure, use two vacuum pumps and evacuate high pressure side and low pressure side circuits separately.)
Note 1: Though refrigerant gas itself is harmless, airtight room should be opened before gas release for preventing
oxygen shortage.
2: When releasing gas, use blotting paper, etc. so that oil spouted with the gas does not spread out.
B
C
J
HI
A
A Ball valve of the high pressure side B Service port C Ball valve of the low pressure side D Charge plug E High pressure F Low pressure G Evacuation H Evacuation I Replenish of refrigerant J System analyzer
LO
K
H
I
G
D
F
E
N Valve O R407C cylinder P Scale Q Vacuum pump
P-YMF-C : Use a vacuum pump with a reverse flow
R A high-precision gravimeter measurable up to 0.1kg
should be used. If you are unable to prepare such a high-precision gravimeter, you may use a charge cylinder.
L
check valve
M
N
Q
R
O
P
K Lo knob L Hi knob M 3-way joint
69
Page 71
77
7 TROUBLESHOOTING
77
[1] Principal Parts
Pressure sensor
(1) Judging failure
1) Check for failure by comparing the sensing pressure according to the high pressure/low pressure pressure sensor and the pressure gauge pressure. Turn on switches 1, 3, 5, 6 (High) and 2, 4, 5, 6 (Low) of the digital display select switch (SW1) as shown below, and the sensor pressure of the high pressure/low pressure sensors is displayed digitally by the light emitting diode LD1.
1234567 8910
High pressure
Low pressure
ON
1234567 8910
ON
1 In the stopped condition, compare the pressure readings from the gauge and from the LD1 display.
2
(a) If the gauge pressure is 0~1 kg/cm (b) If the pressure according to the LD1 display is 0~1 kg/cm
G (0.098MPa), the internal pressure is dropping due to gas leakage.
2
G (0.098MPa), there is faulty contact at the connec-
tor, or it is disconnected. Proceed to 4.
(c) If the pressure according to the LD1 display is 32 kg/cm
2
G (3.14MPa) or higher, proceed to 3.
(d) If other than (a), (b) or (c), compare the pressure readings during operation. Proceed to 2.
2 Compare the pressure readings from the gauge and from the LD1 display while in the running condition.
(a) If the difference between the two pressures is within 1 kg/cm
2
G (0.098MPa), both the affected pressure sensor
and the main MAIN board are normal.
(b) If the difference between the two pressures exceeds 1 kg/cm
2
G (0.098MPa), the affected pressure sensor is
faulty (deteriorating performance).
(c) If the pressure reading in the LD1 display does not change, the affected pressure sensor is faulty.
3 Disconnect the pressure sensor from the MAIN board and check the pressure according to the LD1 display.
(a) If the pressure is 0~1 kg/cm (b) If the pressure is 32 kg/cm
2
G (0.098MPa) on the LD1 display, the affected pressure sensor is faulty.
2
G (3.14MPa) (in the case of the low pressure sensor, 10 kg/cm2G (0.98MPa)) or
higher, the MAIN board is faulty.
4 Disconnect the pressure sensor from the MAIN board and short out the No. 2 and No. 3 pins of the connector
(63HS, 63LS), then check the pressure by the LD1 display. (a) If the pressure according to the LD1 display is 32 kg/cm
10 kg/cm
2
G (0.98MPa)) or higher , the affected pressure sensor is faulty.
2
G (3.14MPa) (in the case of the low pressure sensor,
(b) If other than (a), the MAIN board is faulty.
2) Pressure sensor configuration. The pressure sensors are configured in the circuit shown in the figure at right. If DC 5 V is applied between the red and black wires, a voltage corresponding to the voltage between the white and black wires is output and this voltage is picked up by the microcomputer. Output voltages are as shown below.
High pressure 0.1 V per 1 kg/cm Low pressure 0.3 V per 1 kg/cm
2
G (0.098MPa)
2
G (0.098MPa)
Connector
63HS/
63LS
Vout 0.5~3.5 V
GND (Black) Vout (White) Vcc (DC5V) (Red)
–70–
Page 72
* Connector connection specifications on the pressure sensor body side.
The connectors pin numbers on the pressure sensor body side differ from the pin numbers on the main circuit board side.
Sensor body side MAIN board side
Vcc Pin 1 Pin 3
Vout Pin 2 Pin 2
GND Pin 3 Pin 1
Solenoid valve (SV1~6, SV71~73)
Check if the control boards output signals and the operation of the solenoid valves match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED’s. Each LED shows whether the relays for the following parts are ON or OFF . When a LED lights up, it indicates that the relay is ON.
SW1
1234567 8910
ON
1234567 8910
ON
12345678
SV6SV5
LED
SV4SV3SV2SV1
SV73SV72SV71
1) In the case of SV1 (Bypass Valve) (a) When the compressor starts, SV1 is ON for 4 minutes, so check operation by whether the solenoid valve is
emitting an operating noise.
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the
bypass circuit and the sound of the refrigerant.
2) In the case of SV2 (Bypass) (a) SV2 goes ON in accordance with the rise in the high pressure in the cooling mode and heating mode, so check
its operation by the LED display and the operating noise emitted by the solenoid valve. (Conditions during operation: See Control of Heat Source Unit.)
(b) Changes in the operating condition by solenoid valve operation can be confirmed by the temperature of the
bypass circuit and the sound of the refrigerant.
3) SV3~6, SV71~73 (Control of heat exchanger capacity) (a) Operations can be confirmed by LED display and operating sound of solenoid valve, because one or more of
SV3~5, SV71 are turned on depending on conditions during cooling-only operations.
(b) Operation can be confirmed by LED display and operating sound of solenoid valve, because all of SV3~5, SV73
are turned on during heating-only operations.
(c) Operations can be confirmed by LED display and operating sound of solenoid valve, because one or more of
SV3~6, SV71~73 are turned on depending on conditions during cooling-principal and heating-principal opera­tions.
71
Page 73
(d) The refrigerant flow is as following figure. Hot gas (high pressured) flows in cooling mode and cool gas/liquid
(low pressured) flows in heating mode. Please refer to the Refrigerant Circuit Diagram. And, ON/OFF of Solenoid valve is depends on the amount of running indoor units, ambient temperature and so on. So please check by LED Monitor Display. The SV coil is taken off, then it is possible to open caps and check plungers. But the special tool which is on the Service Parts List is needed.
Solenoid Valves Block
Distributor
SV3
SV4
➁➂➃➄
HEXA
HEXB HEXC HEXD HEXE
SV5
CV9CV8
SV6
CV7
SV71
CV10
CV4
CV5
CV6
Orifice
CV2
CV3
* Closed torque : 13kg·m (1.3N·m)
–72–
Page 74
LEV for heat source unit
The valve opening angle changes in proportion to the number of pulses. (Connections between the heat source units MAIN board and SLEV, LEV2)
Pulse signal output and valve operation
Output (phase)
Output states
1234567 8
ø1 ON OFF OFF OFF OFF OFF ON ON ø2 ON ON ON OFF OFF OFF OFF OFF ø3 OFF OFF ON ON ON OFF OFF OFF ø4 OFF OFF OFF OFF ON ON ON OFF
LEV valve closing and valve opening operations
Valve Closing
Valve Opening
Valve Opening Angle (Flow Rate)
Fully Open 480 pulses
Output pulses change in the following orders when the
Valve is Closed 1→2→3→4→5→6→7→8→1 Valve is Open 8→7→6→5→4→3→2→1→8
*1. When the LEV opening angle does not change, all the
output phases are off.
2. When the output is out of phase or remains ON continuously, the motor cannot run smoothly, but move jerkily and vibrates.
* When the power is switched ON, a 520 pulse valve
opening signal is output to make sure the valve’s position, so that it is definitely at point A. (The pulse signal is output for approximately 17 seconds.)
* When the valve operates smoothly, there is no sound
from the LEV and no vibration occurs, but when the valve is locked, it emits a noise.
* Whether a sound is being emitted or not can be
determined by holding a screwdriver, etc. against it, then placing your ear against the handle.
* If there is liquid refrigerant inside the LEV, the sound
may become lower.
Pulse Count
–73–
Page 75
LEV for BC controller and indoor unit
1 LEV receives pulse signal from microcomputer, and operates valve with stepping motor. 2 Valve opening changes in proportion to the number of pulses.
Connection of microcomputer circuit board and LEV
Intermediate connector (mounted on outdoor unit only)
Brown Red Blue Orange Yellow White
Connector In the case of indoor board : CN60 In the case of multi board : CNLV
Microcomputer circuit boad
Operarion circuit
Note: Pay attention to colors of lead wires because numbers of intermediate connec­tors are different from those of circuit board side connectors.
Pulse signal output and valve operations
Output (phase)
No.
ø1 ø2 ø3 ø4
OFF ON ON OFF OFF OFF ON ON
Output states
123 4
ON OFF OFF ON ON ON OFF OFF
Closing and opening operations of valve
D
Valve opening
Valve opening (Flow rate)
Valve closing
E
A
C
Full opening (2000 pulses)
1 Valve open : Output pulse changes in order of 1 →23→41. Valve close : Output pulse changes in order of 4→3214. 2 All output phases are turned OFF when LEV opening does not
change.
3 In case output phase is lacking or kept “ON, motor can not rotate
smoothly, generating ticking sound and vibration.
1 When turning on power source, issue valve closing signal of 2,200
pulses, so that valve opening is located at point A.
2 When valve runs smoothly , no sound or vibration is generated from
LEV. However, big sound is observed when valve opening changes from point E to A or valve is locked.
(Sound generation can be identified from the bundle of screwdriver
attached to the valve.)
B
Additional tightening zone
(870 ~ 100 pulses)
Number of pulse(SJ)
–74–
Page 76
Judgment methods and likely failure mode
Caution:
The specifications of the heat source unit (heat source LEV) and indoor unit (indoor LEV) differ. For this reason, there are cases where the treatment contents differ, so follow the treatment specified for the appropriate LEV as indicated in the right column.
Failure Mode Judgment Method T reatment Affected LEV
Microcomputer driver circuit failure
1 Disconnect the control board connector and connect
the check LED as shown in the figure below.
Indoor, BC controller
When the base power supply is turned on, the indoor LEV outputs pulse signals for 10 seconds, the heat source LEV outputs pulse signals for 17 seconds, and BC controller outputs pulse signals for 10-20 seconds. If the LED does not light up, or lights up and remains on, the driver circuit is abnormal.
Heat source
In the case of driver circuit failure, replace the control board.
Indoor
BC controller
Heat source
LEV mechanism is locked.
The LEV motor coils have a disconnected wire or is shorted.
Fully closed failure (valve leaks)
1 If the LEV is locked up, the drive motor turns with no
load and a small clicking sound is generated. Generation of this sound when the LEV is fully closed or fully open is abnormal.
Measure the resistance between the coils (red - white, red
- orange, brown - yellow, brown - blue) using a tester. They are normal if the resistance is within 150Ω ± 10%.
Measure the resistance between the coils (gray - orange, gray - red, gray - yellow, gray - black) using a tester . They are normal if the resistance is within 46Ω ± 3%.
1 If you are checking the indoor unit’s LEV, operate the
indoor units blower and the other indoor units in the cooling mode, then check the piping temperatures (liquid pipe temperatures) of the indoor units by the operation monitor through the heat source unit’s control board. When the fan is running, the linear expansion valve is fully closed, so if there is leakage,
Thermistor liquid pipe (tempera­ture sensor)
Linear Expansion Valve
minimal leakage, it is not necessary to replace the LEV if there are no other effects.
the temperature sensed by the thermistor (liquid pipe temperature sensor) will become low. If the temperature is considerably low compared to the remote control’s intake temperature display, it can be judged that there is a fully closed failure. In the case of
Replace the LEV .
Replace the LEV coils.
Replace the LEV coils.
If there is a large amount of leakage, replace the LEV.
Indoor
BC controller
Heat source
Indoor
BC controller
Heat source
Indoor
BC controller
Faulty wire connections in the connector or faulty contact.
1 Check for pins not fully inserted on the connector and
check the colors of the lead wires visually.
2 Disconnect the control board’s connector and conduct
a continuity check using a tester.
–75–
Check the continuity at the places where trouble is found.
Indoor
BC controller
Heat source
Page 77
Heat source LEV (SLEV) coil removal procedure (configuration) As shown in the figure, the heat source LEV is made in such a way that the coils and the body can be separated.
Coils
Stopper
Lead wires
<Removing the coils> Fasten the body tightly at the bottom (Part A in the figure) so that the body will not move, then pull out the coils toward the top. If they catch on the stopper and are difficult to take out, turn the coils left and right until the stoppers are free from the stopper indentations, then pull the coils out. If you take out the coils only without gripping the body , undue force will be applied to the piping and the pipe may be bent over, so be sure to fasten the body in such a way that it will not move.
Body
Indentation for Stopper (12 places around the circumference)
Part A
<Installing the coils> Fasten the body tightly at the bottom (Part A in the figure) so that the body will not move, then insert the coils from the top, inserting the coils stopper securely in one of the indentations on the body. (There are four indentations for the stopper on the body around its circumference, and it doesnt matter which indentation is used. However, be careful not to apply undue force to the lead wires or twist them around inside the body.) If the coils are inserted without gripping the body, it may exert undue force on the piping, causing it to become bent, so be sure to hold the body firmly so that it wont move when install­ing the coils.
Part A
–76–
Page 78
Check valves block (PQRY-P200·250YMF-C)
The refrigerant flow in the pipe 6, 7, 8 and 9 are depend on ON/OFF of the SV3, 4, 5 and 6. Please confirm by LED monitor display. You can open the cap of valve A, B and C, but 3 types of hexagon socket screw keys. The size is as follows.
Distributor
SV3
SV4
SV5
SV6
HEXA
HEXB HEXC HEXD HEXE
ST7b ST7cST7a
CV7
TH6
SV71
ST7d
CV9CV8
CV10
Check Valves Block
➅➆➇➈
CV4
CV6
Orifice
CV5
CV2
➀➁➂
CV3
BV1
ST1
BV2
* Closed torque : A : 1.7kg·m (0.17N·m)
B : 20kg·m (2.0N·m) C : 13kg·m (1.3N·m)
–77–
Page 79
Intelligent Power Module (IPM)
Measure resistances between each terminal of IPM with tester, and use the results for troubleshooting. Specified resistance value is dependent on tester type to be used for resistance measurement, because diode inside IPM has non-linearity, thus difference of impedance and voltage in tester being influential. As the internal impedance of resistance range of analog tester equals to the center value of meter indication, the affect of internal impedance can be minimized if the tester having close center value of resistance range. Because internal voltage is normally 1.5V, the tester to be used for troubleshooting of IPM should satisfy the following conditions.
Internal voltage 1.5V (Power source : one dry cell battery) Central value of resistance range 10 ~ 40
The measured values for troubleshooting are shown in the table below. (Use the minimum range for tester resistance range.)
External view Internal circuit diagram
1471016
B
P
N
Judged value
Tester
+
Tester –
P U V
W
N
W
V
P
UVWN
∞∞∞∞
2~ 100
2~ 100
2~ 100
2~ 1002~1002~1002~100
3
2
Pre-Driver
1 6
5
Pre-Driver
4 9
8
Pre-Driver
U
7 11
13
Pre-Driver
10
14
Pre-Driver
15
Pre-Driver
12
∞ ∞
Over heating
16
protection circuit
P
U
V
W
B
N
Diode stack Perform continuity check with tester. Judged as normal if the following characteristics are observed. (Use the minimum range for tester resistance range.)
Tester
Tester -
1 10~50Ω∞ 2 10~50Ω∞ 3 10~50Ω∞
Tester -
Tester
123
1 10~50
+
2 10~50 3 10~50
1 2 3
+–
+–
78
Page 80
(5) Trouble and remedy of remote controller
Symptom Cause Checking method & countermeasure
12Despite pressing of
remote controller switch, operation does not start with no electronic sound.
(No powering signal
appears.)
1) M-NET transmission power source is not supplied from heat source unit. 1 Main power source of heat source unit is not
connected.
2 Slipping off of connector on heat source unit circuit
board. Main board : CNS1, CNVCC3, CNVCC4 INV board :
3 Faulty power source circuit of heat source unit.
Faulty INV board,
Blown fuse (F1 on INV board)
Broken diode stack
Broken resistor (R1, R5) for rush current protection
2) Short circuit of transmission line.
3) Erroneous wiring of M-NET transmission line at heat source unit. 1 Transmission line disconnection or slipping off from terminal
block.
2 Erroneous connection of indoor/outdoor transmission line to
TB7.
4) Slipping off of transmission wiring at remote controller.
5) Faulty remote controller .
a) Check transmission terminal block of
remote controller for voltage. i) In case of 17 ~ 30V
Faulty network remote controller
ii) In case of less than 17V
See “Transmission Power Circuit
(30V) Check Procedure”.
CNAC2, CNVCC2, CNVCC4, CNL2
The cause of 2) and 3) is displayed with self-diagnosis LED for 7102 error.
At about 10 seconds after turning remote controller operation switch ON, the display distinguishes and the operation
1) Power source is not fed to indoor unit from transformer.
1 Main power source of indoor unit is not turned on. 2 Slipping off of connector (CND, CNT, CN3T) on indoor controller board. 3 Blown fuse on indoor controller board. 4 Faulty or disconnected transformer of indoor unit. 5 Faulty indoor controller board.
stops.
2) Faulty outdoor control circuit board or being out of control. As normal transmission is failed between indoor and heat source units, heat source unit model can not be recognized.
Checking method & countermeasure
Check indoor LED3
Lighting?
Lighting
Check for the change of LED display by operating dip switch SW1 for self-diagnosis.
Extinguishing or unable to confirm
Check indoor unit power source terminal block voltage
AC 220~240V?
YES
Check fuse on circuit board
Blown?
NO
Check connector slipping off (CND, CNT, CN3T)
Slipped off?
NO
Check transformer resistance value
Within rated?
YES
Check self-diagnosis func­tion of heat source unit
Changed?
NO
YES
YES
*1
NO
NO
Check main power source of power source wiring.
Check 220V~240V circuit for short circuit and ground fault.
Improper connector connection
Check cause of trans­former disconnection.
Ground fault on circuit board
Ground fault on sensor, LEV
Apply power source again.
Check self-diagnosis function after powering heat source unit again.
NO
Faulty heat source unit control circuit board
Repair faulty point.
YES
Faulty indoor controller board
Changed?
YES
Casual trouble
*1 Check the transformer in accordance with the TROUBLE SHOOTING in the indoor units service handbook.
–79–
Page 81
Symptom Cause
3 HO display on re-
mote controller does not disappear and switch is ineffective.
(Without using MELANS)
1) Heat source unit address is set to “000.”
2) Erroneous address.
1 Address setting miss of indoor unit to be coupled with remote controller. 2 Address setting miss of remote controller.
3) Faulty wiring of transmission terminal block TB5 of indoor unit in the same group with remote controller.
4) Centralized control SW2-1 of heat source unit is turned ON.
5) Setting to interlocking system from indoor unit (Switch 3-1 = OFF), while Fresh Master is intended to use by remote controller operation (indoor unit attribute).
6) Disconnection or faulty wiring of indoor unit transmission line.
7) Disconnection between indoor unit M-NET transmission line terminal block (TB5) and connector CN2M.
8) More than 2 sets of power supply connector (CN40) are inserted into centralized control transmis­sion line of heat source unit.
9) Faulty heat source unit control circuit board.
10)Faulty indoor controller board.
11)Faulty remote controller.
(Interlocking control with MELANS)
12)No grouping registration from MELANS (Neglecting to set the relation between indoor unit and network remote controller).
13)Slipping off of centralized control transmission line (TB7) at heat source unit.
14)At system connected with MELANS, power supply connector (CN40) is inserted to centralized control transmission line of heat source unit.
Checking method & countermeasure
(Indoor unit = remote controller - 100.)
(Remote controller = indoor unit + 100.)
In case no MELANS used
Same symptom for all units in a single refriger­ant system?
YES
Check heat source unit address
51 ~ 100?
YES
Check centralized control switch SW2-1 at heat source unit
ON?
NO
Faulty heat source unit control circuit board
NO
NO
YES
Heat source unit address setting miss
Switch setting miss Make it ON OFF
Address setting miss of remote controller
Indoor address setting miss
Transmission line wiring miss of in­door unit M-NET
Slipping off of CN2M connector
Confirm address of remote controller with “HO” displayed
Indoor unit + 100?
Check address of coupling indoor unit
Remote controller
-100? YES
Check voltage of indoor unit M­NET transmission terminal block
17 ~ 30V?
Check connection between indoor unit M-NET trans­mission terminal block (TB5) and connector CN2M
YES
Check Fresh Master SW3-1
YES
Slipping off?
NO
NO
Faulty indoor controller board or remote controller
ON?
YES
Repair spot in trouble
Setting miss of Fresh Master SW3-1
In case with MELANS used
When MELANS is used, “HO” display on the remote controller will disappear at the group registration of the indoor unit and local remote controller. If HO does not disappear after the registration, check the items 12) ~ 14) in the Cause column.
–80–
Page 82
Symptom Cause Checking method & countermeasure
4 88 appears on re-
mote controller at the registration and access remote controller
[Generates at registration and confirmation]
1) Erroneous address of unit to be coupled.
2) Slipping off of transmission line of unit to be coupled (No connection).
3) Faulty circuit board of unit to be coupled.
4) Installation miss of transmission line.
a) Confirm the address of unit to be
coupled.
b) Check the connection of transmission
line.
c) Check the transmission terminal block
voltage of unit to be coupled. i) Normal if voltage is DC17 ~ 30V ii) Check the item d) in case other than i).
[Confirmation of different refrigerant system controller]
5) Breaking of power source of heat source unit to be confirmed.
6) Slipping off of centralized control transmission line (TB7) of heat source unit.
7) Power supply connector (CN40) is not inserted into centralized control transmission line in grouping with different refrigerant system without using MELANS.
8) More than 2 sets of power supply connector are inserted into the centralized control transmission line of heat source unit.
9) In the system connected with MELANS, power supply connector (CN40) is inserted into the centralized control transmission line of heat source unit.
10)Short circuit of centralized control transmission line.
d) Confirm the power source of heat source
unit to be coupled with the unit to be confirmed.
e) Confirm that the centralized control
transmission line (TB7) of heat source unit is not slipped off.
f) Confirm the voltage of centralized control
transmission line. i) Normal in case of 10V ~ 30V ii) Check the items 7) ~ 10) left in case
that other than i).
–81–
Page 83
Transmission Power Circuit (30 V) Check Procedure If “” is not displayed by the remote control, investigate the points of the trouble by the following procedure and correct it.
No. Check Item Judgment Response
1
Disconnect the transmission line from TB3 and check the TB3 voltage.
DC24~30 V
Check the transmission line for the following, and correct any defects. Broken wire, short circuit, grounding, faulty contact.
2
Check if the following connectors are disconnected in the outdoor units control box. MAIN Board: CNS1, CNVCC3, CNVCC4 INV Board: CNVCC2, CNVCC4, CNL2, CNR, CNAC2
3
Disconnect the wires from CNVCC3 on the Main board and check the voltage between pins 1 and 3 on the wire side of the CNVCC3.
Tester + ..... 1 pin
Tester - ..... 3 pin
4
Disconnect the wiring from CNVCC2 on the INV board and check the voltage between pins 1 and 3 of CNVCC2.
Tester + ..... 1 pin
Tester - ..... 3 pin
5
Disconnect the wiring from CNL2 on the INV board, and check the resistance at both ends of choke coil L2.
6
Disconnect the wiring from CNR on the INV board, and check the resistance at both ends of R7.
Except the above-mentioned Connector disconnected
Except the above-mentioned
DC24~30 V
Except the above-mentioned DC24~30 V
Except the above-mentioned
0.5~2.5 Except the above-mentioned 19~25 Except the above-mentioned
to No. 2 Connect the connectors as shown on the electric
wiring diagram plate. to No. 3
Check the wiring between CNS1 and TB3 for the following, and correct any defects. Broken wire, short circuit, grounding, faulty contact. If there is no trouble, replace the Main board.
to No. 4 Check the wiring between CNVCC2 and
CNVCC3 for the following, and correct any defects. Broken wire, short circuit, grounding, faulty contact.
to No. 5 to No. 6 Replace choke coil L2. to No. 7 Replace R7.
7
Check the resistance at both ends of F01 on the INV board.
8
Check the voltage between pins 1 and 3 of CNAC2 on the INV board.
9
Check the voltage between L2 and N on power supply terminal block TB1.
0 Except the above-mentioned AC198~264 V Except the above-mentioned AC198~264 V
Except the above-mentioned
to No. 8 Replace F01 Replace the INV board. to No. 9 Check the wiring to CNAC2 for the following and
correct any defects. Broken wire, faulty contact.
Check the power supply wiring and base power supply, and correct any defects.
–82–
Page 84
(6) Investigation of transmission wave shape/noise
Control is performed by exchanging signals between heat source unit, indoor unit and remote controller by M-NET transmission. If noise should enter into the transmission line, the normal transmission will be hindered causing erroneous operation.
1) Symptom caused by the noise entered into transmission line
Cause Erroneous operation Error code
Noise entered into transmission line
Signal changes and is misjudged as the signal of other address.
Transmission wave shape changes to other signal due to
6600
6602
noise. Transmission wave shape changes due to noise, and can
6607
not be received normally thus providing no reply (ACK). Transmission can not be made continuously due to the
6603
entry of fine noise. Transmission can be made normally, but reply (ACK) or
answer can not be issued normally due to noise.
6607 6608
2) Method to confirm wave shape
No fine noise allowed *1
<with transmission>
<without transmission>
VHL
52 µs Logical
VBN
52 µs value 0
Logical
52 µs value 1
52 µs52 µs
No fine noise allowed *1
Check the wave shape of transmission line with an oscilloscope to confirm that the following conditions are being satisfied.
1 The figure should be 104µs/bit ± 1%. 2 No finer wave shape (noise) than the transmission signal (52µs ± 1%) should be allowed. *1 3 The sectional voltage level of transmission signal should be as follows.
Logic value Transmission line voltage level
0VHL = 2.0V or more 1VBN = 1.3V or less
*1 However, minute noise from the DC-DC converter or inverter operation may be picked up.
–83–
Page 85
3) Checking and measures to be taken
(a) Measures against noise
Check the items below when noise can be confirmed on wave shape or the error code in the item 1) is generated.
Items to be checked Measures to be taken
1 Wiring of transmission and power lines in
crossing.
2 Wiring of transmission line with that of other
system in bundle.
3 Use of shield wire for transmission line (for
both indoor unit control and centralized control).
4 Repeating of shield at the repeating of
transmission line with indoor unit.
Checking for wiring method
5 Are the unit and transmission lines grounded
as instructed in the INSTALLATION MANUAL?
6 Earthing of the shield of transmission line (for
indoor unit control) to heat source unit.
7 Arrangement for the shield of transmission line
(for centralized control).
Check for earthing
Isolate transmission line from power line (5cm or more). Never put them in a same conduit.
Wire transmission line isolating from other transmission line. Wiring in bundle may cause erroneous operation like crosstalk.
Use specified transmission wire.
Type : Shield line CVVS/CPEVS Wire diameter : 1.25mm2 or more
The transmission line is wired with 2-jumper system. Wire the shield with jumper system as same for transmission line. When the jumper wiring is not applied to the shield, the effect against noise will be reduced.
Connect to ground as shown in the INSTALLATION MANUAL.
One point earthing should be made at heat source unit. Without earthing, transmission signal may be changed as the noise on the transmission line has no way to escape.
For the shield earth of the transmission line for centralized control, the effect of noise can be minimized if it is from one of the heat source units in case of the group operation with different refrigerant systems, and from the upper rank controller in case the upper rank controller is used. However, the environment against noise such as the distance of trans­mission line, the number of connecting sets, the type of connecting con­troller, and the place of installation, is different for the wiring for central­ized control. Therefore, the state of the work should be checked as fol­lows. a) No earthing
Group operation with different refrigerant systems One point earthing at heat source unit
Upper rank controller is used Earthing at the upper rank controller
b) Error is generated even though one point earth is being con-
nected. Earth shield at all heat source units.
Connect to ground as shown in the users manual.
(b) When the wave height value of transmission wave shape is low, 6607 error is generated, or remote controller is
under the state of “HO.”
Items to be checked Measures to be taken
8 The farthest distance of transmission line is
exceeding 200m.
9 The types of transmission lines are different.
0 No transmission power (30V) is being supplied
to the idoor unit or the remote control.
A Faulty indoor unit/remote controller.
Confirm that the farthest distance from heat source unit to indoor unit/ remote controller is less than 200m.
Use the transmission wire specified.
Type of transmission line : Shield wire CVVS/CPEVS Wire dia. of transmission line : 1.25mm2 or more
Refer to Transmission Power Supply (30V) Circuit Check Procedure.
Replace heat source unit circuit board or remote controller.
–84–
Page 86
4) Treatment of Inverter and Compressor Troubles If the compressor does not work when error codes 4240, 4250, 4340 or 4350 are detected, determine the point of malfunction by following the steps in the LED monitor display and countermeasures depending on the check code displayed, then perform the procedures below.
No. Check Item Symptoms Treatment
How many hours was the power kept on before
1
operation?
1 If it was kept on for 12 hours or
longer as specified.
2 It was kept on for less than the
specified period.
Go to [2].
Go to [2] after keeping the power on for the specified time.
When it is restarted, does
2
the trouble reappear?
3
Run the outdoor unit with the wiring to the compressor disconnected. At this time, change SW1-1 on the INV board to ON. Note) The terminals of the 3 disconnected wires should be isolated from each other.
*1 [Cautions when measuring the voltage and current of the inverters power circuit.]
1 The compressor stops and the
same error code is displayed.
1 The Inverter stops and the same
error code is displayed.
2 If the inverter’s output voltage is
output with good balance, *1.
3 If the balance in the inverter’s
output voltage is not good or if the inverters output voltages are all 0 V (a digital tester cannot be used) *1.
Perform the check of wiring shown in the explanation of each error code.
Check the IPM is faulty. (Go to “Individual Parts Failure Judgment Methods.”)
Check the coil resistance and insulation resistance of the compressor, and if it is normal, run it again, and if the trouble occurs again, replace the compressor. * Insulation resistance : 2M or more
Coil resistance : 0.359 ~ 0.716
Check the IPM. Judge that the IPM is faulty. (Go to “Indi- vidual Parts Failure Judgment Methods.”) If the IPM is normal, replace the G/A board, then perform this item again with SW1-1 ON. If the problem is not solved, replace the INV board. If the problem is solved and you connect the compressor again, turn SW1-1 OFF again. Check the compressors coil resistance and insulation resistance.
Since the voltage and current on the inverters power supply side and its output side do not have a sine waveform, the measurement values will differ depending on the measuring instrument and the circuit measured. In particular, as the inverters output voltage has a pulse waveform, the output frequency also changes, so differences in measurement values will be great depending on the measuring instrument.
1 When checking if the inverter’s output voltage is unbalanced or not (relative comparison of the voltages between
each of the lines), if you are testing with a portable tester, be sure to use an analog tester. Use a tester of a type which can be used to judge if the IPM or diode module is faulty. In particular, in cases where the inverters output frequency is low, there are cases where the variations in measured voltage values between the different wires will be great when a portable digital tester is used, when in actuality they are virtually equal, and there is danger of judging that the inverter is faulty.
2 It is recommended when checking the inverter’s output voltage values (when measuring absolute values), that, if a
measuring device for business frequencies is used, a rectified voltage meter (with a Correct measurement values cannot be obtained with an ordinary portable tester. (either analog or digital)
symbol) be used.
–85–
Page 87
5) Troubleshooting at breaker tripping
Check items Measures to be taken
1 Check the breaker capacity.
The breakers capacity should be proper.
2 Check the a short circuit or grounding in the electrical
system other than the inverter.
3 Check the resistance between terminals on the terminal
block TB1A for power source.
1 0 ~ several ohms or improper megohm value
4 Checking by powering again.
1 Main power source circuit breaker tripping
2 No display of remote controller
5 Operational check by operating air conditioner
Correct any defects.
Check each part inside the inverter power circuit
(resistance, megohm or the like).
a) Diode stack
Refer to Troubleshooting of diode stack.
b) IPM
Refer to Troubleshooting of IPM. c) Rush current protection resistor d) Electromagnetic contactor e) DC reactor * For c) ~ e), refer to Individual Parts Failure Judge-
ment Methods.
1 Normal operation without breaker tripping.
2 Breaker tripping
a) As there is a possibility of instantaneous short
circuit generated, find the mark of the short circuit
for repair. b) When a) is not applicable, the compressor may be
faulty.
The ground fault of inverter output/compressor can
be supposed.
Disconnect the wiring to the compressor and check
the insulation resistance of the following parts with
a megger. a) Compressor terminals. b) Inverter output.
–86–
Page 88
6) Individual Parts Failure Judgment Methods.
Part Name Judgment Method Diode Stack (DS) Refer to Judging Diode Stack Failure. Intelligent Power Module(IPM) Refer to Judging IPM Failure. Electromagnetic Contactor (52C) Measure the resistance value at each terminal.
A2A1
1/L1 3/L2 5/L3
Check Location Judgment Value
A1-A2 0.1k~1.3k
1/L1-2/T1 3/L2-4/T2
2/T1 4/T2 6/T3
Rush Current Protection Resistor (R1, 5) Measure the resistance between terminals: 4.5k~5.5k DC Reactor (DCL) Measure the resistance between terminals: 1 or lower
Measure the resistance between the terminals and the chassis:
Cooling Fan (MF1) Measure the resistance between terminals: 0.1k~1.5k
5/L3-6/T3
Transformer (T01) Measure the resistance between terminals on the primary side (CNTR1):
1.0k~2.5k Measure the resistance between terminals on the secondary side (CNTR): 20~60
AC Current sensor (ACCT) Measure the resistance between terminal between 1pin and 2pin, 3pin and
4pin : 35 ~ 45 (Ω)
[Caution at replacement of inverter parts]
1 IPM and G/A board should be replaced together at the same time.
When the IPM is damaged, the G/A board may possibly be broken, and the use of the broken G/A board damages the normal IPM. Therefore, replace the IPM and G/A board together at the same time. However, if the G/A board is damaged, judge that the IPM is faulty, then judge whether replacement is necessary or not.
2 Fully check wiring for incorrect and loose connection.
The incorrect or loose connection of the power circuit part wiring like IPM and diode module causes to damage the IPM. Therefore, check the wiring fully. As the insufficient tightening of screws is difficult to find, tighten them together additionally after finishing other works. For the wiring of the base for IPM, observe the wiring diagram below care­fully as it has many terminals.
3 Coat the grease for radiation provided uniformly onto the radiation surface of IPM /diode modules.
Coat the grease for radiation on the full surface in a thin layer, and fix the module securely with the screw for fastening. As the radiation grease attached on the wiring terminal causes poor contact, wipe it off if attached.
–87–
Page 89
Motor
(Compressor)
Red
White Black
IPM
UVW
N
G/A board
P
Black
Red
Capacitor
(C2,C3)
–88–
Page 90
(8) Troubleshooting the major components of the BC controller
1) Pressure sensor Pressure sensor troubleshooting flow
START
Check pressure sensor, PS1, PS3, connectors for discon­nection, looseness, or incor­rect attachment.
OK?
Yes
No
Unit running?
Yes
Check on the LED monitor dis­play .
TH2 or LPS of heat source unit.
HPS of heat source unit
PS1, PS3 of BC controller and
confirm the following relationship HPS > PS1 (puressure calculated value)
PS3 > LPS
OK?
Yes
Stop the unit (compres­sor OFF).
At least
10 minutes passed since
stopping?
Yes
Check PS1, PS3 on LED monitor display and confirm that none of the detected pressure values is below 1kg/cm2G (0.098MPa).
Note 1
No
Note 2
No
No
Note 2
Take corrective action.
Check that refrigerant pip­ing and transmission line connections are in agree­ment between heat source unit and BC controller.
No
OK?
Yes
Correct refrigerant piping and trans­mission line.
OK?
No
Yes
HPS PS1 PS3 LPS (pressure calculated value) (The difference is less than
1kg/cm2G
(0.098MPa)
OK?
No
Yes
No board or pressure sensor abnormality.
Check that refrigerant piping and transmission line connections are in agreement between heat source unit and BC controller.
OK?
No
Yes
Confirm the
following relationship PS1
PS3?
Yes
Correct refrigerant piping and the trans­mission line.
Check for the faulty connec­tor on applicable pressure sensor.
OK?
Remove the pressure sensor connector from the board, and check the pressure.
No
Pressure
range within 0 to 1kg/cm
(0.098MPa)
Short connectors 2 and 3 on the board and check the pressure.
Pressure of at least 32kg/cm2G (3.14MPa) indicated?
Replace the wrong puressure sensor by the correct pressure sensor, and confirm detected pres­sure is indicated correctly.
OK?
Yes
Yes
Note 3
Note 4
2
G
No
Repair faulty connection.
No
No
No
–89–
Change pres-
Yes
sure sensor.
Change board.
Page 91
Note 1 :
Symptoms of incorrect connection of BC controller pressure sensor to the board Symptom
Cooling-only Cooling-principal Heating-only Heating-principal
SC11 small SC16 small
PHM < 0
Normal
Insufficient cooling.
SC11 large SC16 small
PHM < 0
Warm indoor SC small. Warm in­door thermo ON especially noise.
Note 2 :
Check using LED monitor display switch (heat source unit MAIN board SW1)
Insufficient heating Warm indoor SC small
SC11 large
SC16 small Warm indoor thermo ON especially noise
PHM < 0
Measured Data
High pressure
Low pressure
BC controller pressure
Signal
HPS
LPS
PS1
SW1 Setting
1ON2345678910
1ON2345678910
1ON2345678910
(liquid measurement)
(intermediate)
PS3
1ON2345678910
Note 3 :
Check CNP1 (liquid measurement) and CMP3 (intermediate) connectors on BC controller board for disconnection or looseness.
Note 4 :
With the sensor of the applicable connector removed from the board, use the LED monitor display switch (Note 1) to check the pressure value.
Pressure Sensor Replacement Precaution
(Pressure sensor output voltage)
–90–
Page 92
2) T emperature sensor
Thermistor troubleshooting flow
Start
Note 1
Disconnect applicable thermistor connector from the board.
Note 2
Measure temperature of applicable thermistor (actual measured value).
Note 3
Check thermistor resistance value.
Compare temperature for thermistor resistance value with actual mea­sured valued.
No
difference?
Yes
Insert applicable thermistor connector into board, and check sensor input temperature on LED monitor for differ­ence.
No
difference?
Yes
No abnormality
No
Note 4
No
.
Note 5
Change thermistor.
Check for connection problem.
Change the controller board.
–91–
Page 93
Note 1 :
Board connector CN10 corresponds to TH11 through TH12, while connector CN11 corresponds to TH15 through TH16. Remove the applicable connector and check the sensor for each number.
Note 2, 3 :
1. Pull the sensor connector from the I/O board. Do not pull on the lead wire.
2. Measure resistance using a tester or other instrument.
3. Compare measured values with values on the graph below. A value within a range of ±10% is normal.
Resistance measurement point (connector)
Touch the probes of the tester or other instrument to the shaded areas to measure.
Temperature sensor resistance (graph)
Resistance value (kΩ)
Temperature (˚C)
Note 4 :
Check using LED monitor display switch (outdoor MAIN board SW1)
Measured Data Signal SW1 Setting
Liquid inlet temperature
Bypass outlet temperature
Bypass outlet temperature
Bypass inlet temperature
TH11
TH12
TH15
TH16
1ON2345678910
1ON2345678910
1ON2345678910
1ON2345678910
Thermistor Ro=15 k Rt=15exp 3460 ( – )
1
273+t1273t
–92–
Page 94
3) LEV , solenoid valve troubleshooting flow
No cooling
No heating
Note 1
Check disconnection or looseness of connectors.
Is there a problem?
Operate in cooling or heating (1 system only when there are plural systems)
Cooling or heating
operation?
Cooling operation
Check if LEV 1 is fully open
LEV 1 fully open?
Yes
Check if LEV3 is controlled by superheat.
LEV3 is not controlled.
Yes
Check if SVA, SVC are ON.
Yes
Heating operation
Note 2
No
Note 3
No
Correct the problem.
Check LEV1
Check LEV3
Check if LEV 1 is fully shut.
No
No
LEV 1 fully shut?
Yes
Check if LEV 3 is controlled by differential pressure.
LEV3 is not
controlled
Yes
Check if SVA, SVC are OFF.
Note 2
Note 3
SV A, SVC ON
Yes
Check if SVB is OFF.
SVB OFF
Yes Yes
No
No
Check SVA, SVC
Check SVB
Completion
No
Check if SVB is ON.
No
SV A, SVC OFF
Yes
SVB ON
–93–
Page 95
1 LEV
Note 1 :
Symptoms of incorrect connection to BC controller LEV board
LEV No. 1 3 Cooling-only Cooling-main Heating-only Heating-main
1) 1 3 Normal ←← ←
2) 3 1 Insufficient cooling SH12 small, SC11 small SC16 small Branch piping SC small
Insufficient cooling, insuf­ficient heating SH12 small, SC11 small SC16 large, Branch piping SC small
PHM large
Heating indoor SC small
PHM large
Insufficient cooling Heating indoor SC small
PHM large
Improper installation is the same for 1 and 2, so it is omitted here.
Note 2 : Method for checking LEV full open, full closed condition
1 Check LEV full opening (pulse) using the LED monitor display (outdoor controller board SW1).
Full opened: 2000 pulses Full closed: 60 pulses (LEV 1 may be greater than 60 during full heating operation.)
2 With LEV full opened, check for pressure differential by measuring temperature of piping on both sides. 3 With LEV full closed, check for refrigerant noise.
Note 3 :Use the following table to determine opening due to LEV differential pressure control and superheat
control.
BC controller LEV basic operation characteristics Region Failure mode
LEV1 pulse
Small Large
Small
LEV3 pulse
Large
Operating mode
Heating-only Heating-main Cooling-main
Cooling-only Cooling-main
Heating-only Heating-main
Cooling-only Cooling-main
Heating-only Heating-main
Description Normal range
High pressure (PS1) - medium pressure (PS3) is large. High pressure (PS1) - medium pressure (PS3) is small.
SH12 is large.
High pressure (PS1) - mid pressure (PS3) is small.
2.0 ~ 3.5 kg/cm2G (0.20~0.34MPa)
SH12<25
2.0 ~ 3.5 kg/cm2G (0.20~0.34MPa)
SC16>6
SC16 and SH12 are small.
High pressure (PS1) - mid pressure (PS3) is large.
SH12>5
2.0 ~ 3.5 kg/cm2G (0.20~0.34MPa)
–94–
Page 96
(Self-diagnostic monitor)
Measured data Signal Heat source unit MAIN board SW1 setting
LEV 1 pulse
1ON2345678910
LEV 3 pulse
BC controller bypass output superheat
BC controller intermediate subcool
BC controller liquid subcool
SH12
SC16
SC11
(Solenoid Valve Troubleshooting Flow)
Start
Visually check for disconnection between connec­tors and terminals, and confirm correct lead colors.
Intermediate connector
Brown
Red
To
LEV
Remove connectors from the board and use a tester to check conduction.
Check between connectors 1-3-5 and 2­4-6.
Use a tester to measure resistance between each coil (red-white, red-orange, brown-yellow, brown-blue). Correct value is: 150Ω±10%
Blue
Orange
Yellow
White
2 5 1 3 4 6
OK?
Yes
OK?
Yes
Brown
Red
Blue
Orange
Yellow
White
No
No
Controller board
6 5 4 3 2 1
1ON2345678910
1ON2345678910
1ON2345678910
1ON2345678910
Correction.
Adjust, repair.
Check for the following: LEV full open: ticking sound LEV full closed: no sound
OK?
Yes
Confirm if LEV is closed fully.
OK?
Yes
Attach check LEDs illustrated nearby to board connectors and confirm that LEDs light for 10 seconds.
OK?
Yes
End
No
Change LEV
No
Change LEV
6 5 4 3 2 1
10k LED
No
Change the board.
OK?
Yes
No
Change LEV
–95–
Page 97
2 Solenoid V alve
Solenoid valve
troubleshooting
Operation OFF?
Check solenoid valve wiring for incorrect connection, and connector disconnection or looseness.
No problem.
No
Operate cooler and heater for the applicable solenoid valve’s refrigerant system only .
Note 1
Clicking noise
produced when working
timing?
Yes
Yes
Measure piping temperature on both sides of solenoid valve and check for following. Solenoid valve ON: no differential Solenoid valve OFF: differential
Yes
Correct the problem.
No
Remove the coil and check for a magnetic force.
Measure pipe temperature of inlet and outlet sides of solenoid valve. No temperature differential: OK T emperature differential: NG
Magnetic force
is OK?
Yes
OK?
Yes
Note 3
No
No
Stop the unit.
Disconnect solenoid valve connector from the board and check for a solenoid coil conductance.
Conductance present?
Yes
With the solenoid valve con­nector is disconnected from the board, use remote controller to turn on the unit and check the output (220-240V) from the controller board.
220-240V output?
No
No
Yes
OK?
Yes
Solenoid valve normal
No
Solenoid valve faulty
–96–
Change the control board.
Change the solenoid valve.
Page 98
Solenoid valves (SVA, SVB, SVC) Coordination signals output from the board and solenoid valve operations.
Note 1 : (SVA, SVB, SVC)
SVA, SVB and SVC are turned on and off in accordance with operation mode.
Mode
Branch port
Cooling Heating Stopped Defrosting
SVA ON OFF OFF OFF SVB OFF ON OFF OFF SVC ON OFF OFF OFF
Note 2 : (SVA, SVB, SVC)
Measure temperature of piping on either side of SVA 1-A Measure temperature of piping on either side of SVB 1-B
B
A
4) BC controller transformer
BC Controller control board
CNTR CN03
Red Blue Brown Brown
1
Normal Malfunction
CNTR(1)-(3) Approximately 90
CN03(1)-(3) Approximately 1.7
Open or shorted
* Disconnect the connector before measurement.
–97–
Page 99
[2] BC Controller Disassembly Procedure
(1) Service panel
Procedure Photos & Illustrations
1. Remove the two screws securing the electric panel box, and then remove the box.
2. Remove the four screws securing the front panel and then remove the panel. Two of the screws are not visible until you remove the electric panel box.
3. Remove the two screws securing the ceiling panel. Next, lifting up on the panel slightly , slide it inwards and then remove it. The inside of the ceiling panel is hooked on a pin.
4. Remove the single screw that secures the side panel, and then remove the panel.
Celling panel
Celling panel fixing screw
Be careful on removing heavy parts.
BC control­ler unit
Pin
–98–
Page 100
(2) Control box
Procedure Photos
<CMB-P104, 105, 106V-E>
1. Removing the single screw that secures the elec­tric panel box cover provides access to the box con­tents for checking. 1 Check electrical lead wires and transmission
lead terminal connections.
2 Check the transformer. 3 Check the address switch. 4 Use the self-diagnostic switch to check the LED
display.
2. Disconnect the power supply lead, transmission lead, transformer lead connector, and address switch wiring connector. Removing the screw se­curing the inner cover provides access for checking the entire controller board.
3. Note the following precautions whenever replacing the controller board. 1 Be sure you do not confuse a Type A controller
board with a Type B controller board.
2 Take care to avoid mistakes when connecting
leads and connectors, and double-check for in­complete and loose connections.
3 Check to make sure that DIP switch settings are
the same before and after replacement.
Be careful on removing heavy parts.
Important!
You do not need to remove the two electric panel screws if you are checking electric panel box contents only .
<CMB-P108, 1010,1013,1016V-E>
Removing the single screw that secures the electric panel box cover provides access to the controller board and all of the relay board for checking. So it is not necessary to work according to avobe 2.
–99–
Loading...